Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 08:35:11
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1824.18 | 366.14 | 366.14 |
Net Site Energy | 1824.18 | 366.14 | 366.14 |
Total Source Energy | 5268.74 | 1057.52 | 1057.52 |
Net Source Energy | 5268.74 | 1057.52 | 1057.52 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 156.88 | 133.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 174.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 120.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 110.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1580.09 | 244.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 156.88 | 133.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 174.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 280.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 72.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 120.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 110.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 156.88 | 133.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 174.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 280.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 72.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 120.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 110.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 90.77 | 48.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 317.15 | 48.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 90.77 | 48.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 317.15 | 48.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1580.090 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1580.090 | 100.00 |
Total On-Site and Utility Electric Sources | 1580.090 | 100.00 |
Total Electricity End Uses | 1580.090 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 350.33 |
Time Setpoint Not Met During Occupied Cooling | 190.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2474.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.5763 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 7.5763 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 7.5763 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 06-FEB-07:10 | 23-DEC-07:19 | - | - | - | - | - | - | - | - | - | - | 04-JAN-12:09 |
Heating | 171881.05 | 104224.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 9359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21853.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 256.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6367.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7932.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 209717.90 | 112156.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 171881.05 | 104224.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 9359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 16082.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 256.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6367.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 7932.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 496.83 | 144.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 552.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 889.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 228.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2413.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 41.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 382.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5004.15 | 264.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 99.72 | 29.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 110.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 178.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 76.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1004.41 | 53.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 99.72 | 29.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 110.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 178.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 76.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1004.41 | 53.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.44 | 0.217928 | 0.237000 | 0.815045 | 0.581140 | 0.500000 | 0.001748 |
CORE_MID VAV BOX COMPONENT | 2.51 | 0.298130 | 0.316000 | 0.794378 | 0.795013 | 0.500000 | 0.001278 |
CORE_TOP VAV BOX COMPONENT | 2.73 | 0.274039 | 0.302000 | 0.825924 | 0.730771 | 0.500000 | 0.001390 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.865468 | 0.182550 | 0.201000 | 0.173959 | 0.486801 | 0.500000 | 0.002087 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.937574 | 0.106681 | 0.200000 | 0.187515 | 0.300000 | 0.500000 | 0.003571 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.17 | 0.135347 | 0.200000 | 0.233462 | 0.360924 | 0.500000 | 0.002815 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.11 | 0.089881 | 0.200000 | 0.222551 | 0.300000 | 0.500000 | 0.004239 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.656667 | 0.240596 | 0.262000 | 0.172047 | 0.641591 | 0.500000 | 0.001584 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.762104 | 0.131244 | 0.200000 | 0.152421 | 0.349985 | 0.500000 | 0.002903 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.906902 | 0.174210 | 0.200000 | 0.181380 | 0.464561 | 0.500000 | 0.002187 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.853774 | 0.117145 | 0.200000 | 0.170755 | 0.312386 | 0.500000 | 0.003252 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.742907 | 0.212667 | 0.226000 | 0.167897 | 0.567111 | 0.500000 | 0.001792 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.919064 | 0.108830 | 0.200000 | 0.183813 | 0.300000 | 0.500000 | 0.003501 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.04 | 0.152176 | 0.200000 | 0.207643 | 0.405803 | 0.500000 | 0.002504 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 1.01 | 0.099024 | 0.200000 | 0.202003 | 0.300000 | 0.500000 | 0.003848 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 22096.17 |
CORE_MID VAV BOX REHEAT COIL | 24598.21 |
CORE_TOP VAV BOX REHEAT COIL | 42874.99 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19641.78 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12942.03 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 19774.73 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12941.81 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 14422.69 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9597.42 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 14544.95 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9597.33 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 15179.28 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10069.91 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 15287.37 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10069.81 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.31 | 1.49 | 6.62 | 2.23 | 5.93 | 5.93 | 0.300000 | 0.376585 | 5.93 |
PACU_VAV_MID | 3.11 | 1.56 | 6.22 | 2.77 | 5.34 | 5.34 | 0.300000 | 0.519751 | 5.34 |
PACU_VAV_TOP | 3.41 | 1.64 | 6.82 | 3.99 | 6.26 | 6.26 | 0.300000 | 0.636999 | 6.26 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.93 |
PACU_VAV_MID_OA_CONTROLLER | 5.34 |
PACU_VAV_TOP_OA_CONTROLLER | 6.26 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.93 | 98192.98 | 0.800655 | 1.98 | 32727.72 | 0.800655 |
PACU_VAV_MID COOLING COIL | 5.34 | 88349.57 | 0.800655 | 1.78 | 29446.91 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 6.26 | 103692.07 | 0.800655 | 2.09 | 34560.57 | 0.800655 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 32566.01 |
PACU_VAV_MID HEATING COIL | 34004.69 |
PACU_VAV_TOP HEATING COIL | 34014.84 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.93 |
PACU_VAV_MID FAN | 5.34 |
PACU_VAV_TOP FAN | 6.26 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 32.411 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9320 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9163 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.269 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8390 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8573 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5538 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.27971961E-12 | 0.14534712E-14 | -0.84678956E-13 | 0.82684317E-16 |
43 | 6 | 0.26817376E-07 | 0.25687399E-09 | 0.61588016E-08 | -0.12527087E-12 |
44 | 5 | -0.18065003E-03 | 0.22251366E-05 | -0.93037841E-04 | 0.60936178E-08 |
45 | 4 | 0.28101542 | 0.10946024E-02 | 0.95683253E-01 | -0.32007147E-04 |
46 | 3 | -7.0457283 | 0.34231649E-01 | -2.2734647 | 0.27928366E-01 |
47 | 2 | 40.143429 | 0.12270019 | 14.996275 | -0.32523640 |
48 | 1 | -79.987958 | 0.55761501E-01 | -28.900564 | 1.0667320 |
49 | 0 | 46.824342 | 0.11295401E-02 | 16.297084 | |
50 | 7 | -0.28233695E-12 | 0.14433069E-14 | -0.85363548E-13 | 0.83491456E-16 |
51 | 6 | 0.27004714E-07 | 0.25312183E-09 | 0.62001510E-08 | -0.12627076E-12 |
52 | 5 | -0.18161011E-03 | 0.21898175E-05 | -0.93520278E-04 | 0.61339935E-08 |
53 | 4 | 0.28215201 | 0.10760039E-02 | 0.96091377E-01 | -0.32166146E-04 |
54 | 3 | -7.0682688 | 0.33616209E-01 | -2.2801509 | 0.28038740E-01 |
55 | 2 | 40.217804 | 0.12038787 | 15.023777 | -0.32606455 |
56 | 1 | -80.044990 | 0.54668782E-01 | -28.925243 | 1.0679473 |
57 | 0 | 46.824342 | 0.11065724E-02 | 16.296477 | |
58 | 6 | 0.22748378E-07 | 0.33059726E-09 | 0.52605359E-08 | -0.10371465E-12 |
59 | 5 | -0.15952455E-03 | 0.29533519E-05 | -0.82380770E-04 | 0.52144884E-08 |
60 | 4 | 0.25560578 | 0.14926938E-02 | 0.86578981E-01 | -0.28493712E-04 |
61 | 3 | -6.5408460 | 0.47808585E-01 | -2.1237636 | 0.25458881E-01 |
62 | 2 | 38.476406 | 0.17496760 | 14.378110 | -0.30668036 |
63 | 1 | -78.708466 | 0.80951212E-01 | -28.345189 | 1.0394692 |
64 | 0 | 46.824351 | 0.16689207E-02 | 16.311239 | |
65 | 7 | -0.18042418E-08 | -0.42925973E-15 | 0.63337540E-14 | -0.83764910E-16 |
66 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
67 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
68 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
69 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
70 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
71 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
72 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
73 | 7 | -0.17078159E-08 | -0.36552483E-15 | 0.71259391E-14 | -0.98899249E-16 |
74 | 6 | 0.68798867E-05 | 0.47165251E-08 | 0.31862110E-02 | -0.26728608E-04 |
75 | 5 | -0.49558197E-03 | 0.27953368E-05 | -0.22351660 | 0.19543146E-02 |
76 | 4 | 0.11404824E-01 | 0.12725100E-03 | 4.8260817 | -0.45231683E-01 |
77 | 3 | -0.10016651 | 0.10121065E-02 | -38.001848 | 0.39843745 |
78 | 2 | 0.35569192 | 0.16837830E-02 | 116.44586 | -1.4174299 |
79 | 1 | -0.51340120 | 0.51323984E-03 | -143.88489 | 2.0486714 |
80 | 0 | 0.25031121 | 0.12359947E-04 | 60.838472 | |
81 | 7 | -0.18042418E-08 | -0.42925997E-15 | 0.63337541E-14 | -0.83764912E-16 |
82 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
83 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
84 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
85 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
86 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
87 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
88 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
89 | 7 | -0.17076967E-08 | -0.36446083E-15 | 0.71390403E-14 | -0.94439575E-16 |
90 | 6 | 0.68803475E-05 | 0.47168467E-08 | 0.31862096E-02 | -0.26728597E-04 |
91 | 5 | -0.49561596E-03 | 0.27955299E-05 | -0.22351653 | 0.19543140E-02 |
92 | 4 | 0.11405612E-01 | 0.12725979E-03 | 4.8260805 | -0.45231671E-01 |
93 | 3 | -0.10017344 | 0.10121766E-02 | -38.001841 | 0.39843738 |
94 | 2 | 0.35571654 | 0.16838995E-02 | 116.44585 | -1.4174297 |
95 | 1 | -0.51343675 | 0.51327568E-03 | -143.88488 | 2.0486713 |
96 | 0 | 0.25032854 | 0.12360692E-04 | 60.838472 | |
97 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
98 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
99 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
100 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
101 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
102 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
103 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
104 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
105 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3822_SHGC_EAST_0.38 | 35 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 | ||
2 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 36 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 | ||
3 | WINDOW_U_0.3822_SHGC_WEST_0.38 | 37 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 | ||
4 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 38 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0134E-002 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0196E-002 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1193E-002 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1247E-002 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.8841E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9277E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6395E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6611E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1424 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8435E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1619 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.9066E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1021 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3950E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.2271E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5852E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0133E-002 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0194E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1192E-002 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1244E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.8834E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9261E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6393E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6609E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8873E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5106E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4359E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1835E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9412E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0071E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9184E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3003E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3645E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3880E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0036E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0205E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9093E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.9149E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2478E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2552E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8664E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9172E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2271E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2674E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8136E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8419E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6393E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6609E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6746E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1661E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8341E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6488E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7310E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1564E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.2271E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5852E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8667E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9174E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2274E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2678E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8140E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8429E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6395E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6611E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0278E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5776E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6115E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2675E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0568E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0610E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9184E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3003E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4720E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5462E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1396E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2228E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9859E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0140E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2479E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2553E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1390 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.1846E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1551 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1035 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1076 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.4577E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.7521E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.2047E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.6588E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.3837E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.2353E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0730E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.7679E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9140E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8008E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2370E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.1578E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7894E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.2666E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1859E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1631E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6532E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.7521E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2047E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.7945E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4492E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.4048E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.1552E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.8796E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9662E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8008E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2371E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1390 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.1839E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1551 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1035 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1076 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.4571E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.7517E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.2044E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.6589E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.3835E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.2354E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0728E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.7676E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9137E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8004E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2368E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.1580E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7893E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.2668E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.1858E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1630E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6531E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.7517E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2044E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.7946E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4491E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.4048E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.1550E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.8793E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9659E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8005E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2369E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 38723.20759 | 38723.20759 | 3.43901 | 3.43901 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 9010.49774 | 9010.49774 | 0.47580 | 0.47580 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90000 | 9.55238E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 28334.33713 | 28334.33713 | 2.51385 | 2.51385 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 17348.80774 | 17348.80774 | 0.90734 | 0.90734 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 30553.35036 | 30553.35036 | 2.73485 | 2.73485 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 33.45600 | 5.47459E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 30152.35032 | 30152.35032 | 1.58150 | 1.58150 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9669.44822 | 9669.44822 | 0.86547 | 0.86547 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.47504E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 13783.92395 | 13783.92395 | 0.72451 | 0.72451 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10475.13840 | 10475.13840 | 0.93757 | 0.93757 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 26.59867 | 5.46414E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 9081.64863 | 9081.64863 | 0.47738 | 0.47738 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13041.82988 | 13041.82988 | 1.16731 | 1.16731 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.47489E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 13877.05041 | 13877.05041 | 0.72942 | 0.72942 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12432.34199 | 12432.34199 | 1.11275 | 1.11275 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 9081.49400 | 9081.49400 | 0.47737 | 0.47737 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7336.44635 | 7336.44635 | 0.65667 | 0.65667 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.47504E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 10126.92175 | 10126.92175 | 0.53200 | 0.53200 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8514.50807 | 8514.50807 | 0.76210 | 0.76210 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 27.01800 | 5.46476E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 6738.05713 | 6738.05713 | 0.35401 | 0.35401 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10132.17310 | 10132.17310 | 0.90690 | 0.90690 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.47489E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 10212.54949 | 10212.54949 | 0.53651 | 0.53651 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9538.67897 | 9538.67897 | 0.85377 | 0.85377 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 30.84133 | 5.47057E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 6737.98848 | 6737.98848 | 0.35401 | 0.35401 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8300.06477 | 8300.06477 | 0.74291 | 0.74291 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.47504E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 10657.64764 | 10657.64764 | 0.55991 | 0.55991 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10268.26036 | 10268.26036 | 0.91906 | 0.91906 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76000 | 5.46288E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 7069.52317 | 7069.52317 | 0.37144 | 0.37144 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11599.39918 | 11599.39918 | 1.03821 | 1.03821 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 33.40667 | 5.47451E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 10733.36012 | 10733.36012 | 0.56389 | 0.56389 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11284.39314 | 11284.39314 | 1.01001 | 1.01001 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 7069.45047 | 7069.45047 | 0.37144 | 0.37144 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 76828.51 | 5.93184 | 5.93184 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 35920.76 | 2.23384 | 2.23384 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 70168.65 | 5.33720 | 5.33720 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 36036.34 | 2.77402 | 2.77402 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 80213.59 | 6.26404 | 6.26404 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 35713.71 | 3.99018 | 3.99018 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.43901 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21793 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23700 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81505 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58114 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.74829E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22096.17259 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.51385 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29813 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31600 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79438 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79501 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.27797E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24598.21029 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.73485 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27404 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30200 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.82592 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73077 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.39031E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 42874.99015 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86547 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18255 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20100 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17396 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48680 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.08709E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19641.78085 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93757 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10668 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18751 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.57138E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12942.02581 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.16731 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13535 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23346 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36092 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.81500E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19774.73275 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.11275 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.98809E-002 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22255 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.23894E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12941.80651 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65667 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24060 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17205 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64159 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.58356E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14422.68789 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76210 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13124 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15242 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34998 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.90299E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9597.42290 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90690 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17421 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18138 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46456 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18701E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14544.94691 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85377 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11714 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17075 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31239 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.25238E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9597.32636 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74291 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21267 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22600 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16790 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56711 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.79153E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15179.27504 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91906 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10883 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18381 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.50087E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10069.91236 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03821 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15218 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20764 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40580 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.50368E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15287.37343 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.01001 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.90236E-002 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20200 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.84757E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10069.81005 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.30923 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.49165 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.61846 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.23384 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.93184 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.93184 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.37658 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.11203 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.55573 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.22405 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.77402 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.33720 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.33720 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.51975 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.40898 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.64341 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.81796 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.99018 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.26404 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 6.26404 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.63700 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.93184 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.33720 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 6.26404 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.93184 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.93184 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 98192.97966 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.97708 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32727.72012 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 32566.01142 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.93184 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.33720 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.33720 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 88349.57304 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.77889 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 29446.91270 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 34004.68929 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.33720 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.26404 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.26404 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 103692.07288 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.08780 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34560.56789 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 34014.83832 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 6.26404 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 96503.32 | 329283.01 | 11.23 | 2.80 | 3.22 | 3.39 | 3.54 | 9.54 | 10.98 | 11.58 | 12.07 | 5.5690 | 4.4029 | 2.9516 | 1.2500 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 86829.30 | 296273.86 | 11.23 | 2.80 | 3.22 | 3.39 | 3.54 | 9.54 | 10.98 | 11.58 | 12.07 | 5.0108 | 3.9615 | 2.6557 | 1.1247 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 101907.79 | 347723.81 | 11.23 | 2.80 | 3.22 | 3.39 | 3.54 | 9.54 | 10.98 | 11.58 | 12.07 | 5.8809 | 4.6495 | 3.1169 | 1.3200 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.246 | 0.232 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.246 | 0.232 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 8.4272578742E-003 | 4.9899637509E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1492182934 | 9.9091027457E-002 | Pass | Pass | 0.2003812288 | 0.3921873792 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.2217729588E-002 | 1.4095860031E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.8704583164E-002 | 1.1789579369E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.2864139370E-002 | 6.5833382041E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 6.1244327028E-002 | 3.7032877537E-002 | Pass | Pass | 0.2005970572 | 0.3976870650 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1311810011 | 0.1872583607 | Pass | Pass | 11.1589094983 | 46.8459707612 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1266275990 | 0.1553759617 | Pass | Pass | 14.0348971252 | 63.1831907828 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1600934015 | 0.1492259266 | Pass | Pass | 141.9830466157 | 1688.6801112763 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1468937813 | 0.1517093296 | Pass | Pass | 29.9845726332 | 178.6524367686 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.3153785492E-002 | 2.6118046999E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.0441956387E-002 | 0.1023203564 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 9.4027814825E-002 | 9.7688277287E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.7817971080E-002 | 7.7530536782E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.7098450257E-002 | 2.7919536920E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 7.9967576553E-002 | 0.1256208930 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1374480260 | 0.1410856361 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.4879398543E-002 | 9.3405475707E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4219.11 | 139.37 | 0.00 | 1959.32 | 871.49 | 7189.29 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3822_SHGC_EAST_0.38 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3822_SHGC_EAST_0.38 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3822_SHGC_WEST_0.38 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3822_SHGC_WEST_0.38 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.171 | 0.381 | 0.381 | |||||||||||||||||
North Total or Average | 177.99 | 2.171 | 0.381 | 0.381 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.171 | 0.381 | 0.381 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.42 | 0.0000 | Y | 9.26 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.40 | 0.0000 | Y | 5.86 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.17 | 0.0000 | Y | 9.19 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.19 | 0.0000 | Y | 5.82 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.38 | 0.0000 | Y | 9.25 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.37 | 0.0000 | Y | 5.86 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.15 | 0.0000 | Y | 9.18 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.16 | 0.0000 | Y | 5.82 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.42 | 0.0000 | Y | 9.26 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.40 | 0.0000 | Y | 5.86 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.17 | 0.0000 | Y | 9.19 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.19 | 0.0000 | Y | 5.82 |
Interior Lighting Total | 7.5763 | 4982.19 | 37746.71 | 280.84 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 42.26 | 42.26 | 3.37 | |
EXTERIOR_LIGHTS_B | 5132.60 | AstronomicalClock | - | 83.67 | 71.25 | 68.64 | |
Exterior Lighting Total | 5557.43 | 72.02 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 98192.98 | 78618.73 | 19574.25 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 88349.57 | 70737.55 | 17612.02 | 0.80 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 103692.07 | 83021.60 | 20670.47 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 96503.3 | 2.80 | 9.54 | N/A | N/A | 11.23 | |
PACU_VAV_MID COOLING COIL | 86829.3 | 2.80 | 9.54 | N/A | N/A | 11.23 | |
PACU_VAV_TOP COOLING COIL | 101907.8 | 2.80 | 9.54 | N/A | N/A | 11.23 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 22096.17 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 24598.21 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 42874.99 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19641.78 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12942.03 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19774.73 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12941.81 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14422.69 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9597.42 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14544.95 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9597.33 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15179.28 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10069.91 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15287.37 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10069.81 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 32566.01 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 34004.69 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 34014.84 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.93 | 12901.09 | 2174.89 | 1.00 | 1.13 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.34 | 12267.34 | 2298.46 | 1.00 | 1.13 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 6.26 | 13623.58 | 2174.89 | 1.00 | 1.13 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 96503.32 | 2.80 | 9.54 | 11.23 | 5.5690 | 3.22 | 10.98 | 4.4029 | 3.39 | 11.58 | 2.9516 | 3.54 | 12.07 | 1.2500 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 86829.30 | 2.80 | 9.54 | 11.23 | 5.0108 | 3.22 | 10.98 | 3.9615 | 3.39 | 11.58 | 2.6557 | 3.54 | 12.07 | 1.1247 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 101907.79 | 2.80 | 9.54 | 11.23 | 5.8809 | 3.22 | 10.98 | 4.6495 | 3.39 | 11.58 | 3.1169 | 3.54 | 12.07 | 1.3200 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 38723.21 | 38723.21 | 39.37 | 3.439 | 3.439 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00881 | 22.95 | 0.00546 | 0.425 | 0.00 |
CORE_MID | 28334.34 | 28334.34 | 28.81 | 2.514 | 2.514 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 22.95 | 0.00546 | 0.425 | 0.00 |
CORE_TOP | 30553.35 | 30553.35 | 31.06 | 2.735 | 2.735 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00889 | 33.46 | 0.00547 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9669.45 | 9669.45 | 46.64 | 0.865 | 0.865 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00867 | 33.75 | 0.00548 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10475.14 | 10475.14 | 79.80 | 0.938 | 0.938 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00859 | 26.60 | 0.00546 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13041.83 | 13041.83 | 62.90 | 1.167 | 1.167 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00862 | 33.65 | 0.00547 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12432.34 | 12432.34 | 94.72 | 1.113 | 1.113 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00858 | 31.83 | 0.00547 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7336.45 | 7336.45 | 35.38 | 0.657 | 0.657 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00877 | 33.75 | 0.00548 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8514.51 | 8514.51 | 64.87 | 0.762 | 0.762 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00865 | 27.02 | 0.00546 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10132.17 | 10132.17 | 48.87 | 0.907 | 0.907 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00870 | 33.65 | 0.00547 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9538.68 | 9538.68 | 72.67 | 0.854 | 0.854 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00863 | 30.84 | 0.00547 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8300.06 | 8300.06 | 40.03 | 0.743 | 0.743 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00871 | 33.75 | 0.00548 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10268.26 | 10268.26 | 78.23 | 0.919 | 0.919 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00860 | 25.76 | 0.00546 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11599.40 | 11599.40 | 55.94 | 1.038 | 1.038 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00865 | 33.41 | 0.00547 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11284.39 | 11284.39 | 85.97 | 1.010 | 1.010 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00860 | 31.83 | 0.00547 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 9010.50 | 9010.50 | 9.16 | 0.476 | 0.476 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 0.425 | 0.00 |
CORE_MID | 17348.81 | 17348.81 | 17.64 | 0.907 | 0.907 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 0.425 | 0.00 |
CORE_TOP | 30152.35 | 30152.35 | 30.66 | 1.581 | 1.581 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 13783.92 | 13783.92 | 66.48 | 0.725 | 0.725 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9081.65 | 9081.65 | 69.19 | 0.477 | 0.477 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13877.05 | 13877.05 | 66.93 | 0.729 | 0.729 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9081.49 | 9081.49 | 69.19 | 0.477 | 0.477 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 10126.92 | 10126.92 | 48.84 | 0.532 | 0.532 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 6738.06 | 6738.06 | 51.33 | 0.354 | 0.354 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10212.55 | 10212.55 | 49.26 | 0.537 | 0.537 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 6737.99 | 6737.99 | 51.34 | 0.354 | 0.354 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 10657.65 | 10657.65 | 51.40 | 0.560 | 0.560 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 7069.52 | 7069.52 | 53.86 | 0.371 | 0.371 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 10733.36 | 10733.36 | 51.77 | 0.564 | 0.564 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 7069.45 | 7069.45 | 53.86 | 0.371 | 0.371 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -17.90 | 0.00096 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.93 | 5.93 | 2.23 | 2.23 | 5.9318 | 2.2338 | 5.9318 | 0.3766 | 0.3000 |
PACU_VAV_MID | 5.34 | 5.34 | 2.77 | 2.77 | 5.3372 | 2.7740 | 5.3372 | 0.5198 | 0.3000 |
PACU_VAV_TOP | 6.26 | 6.26 | 3.99 | 3.99 | 6.2640 | 3.9902 | 6.2640 | 0.6370 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 22096.173 | 22096.173 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 22096.17 | 12899.24 | 0.475805 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 9010.50 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 24598.210 | 24598.210 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24598.21 | 24598.21 | 0.907336 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 17348.81 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 42874.990 | 42874.990 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 42874.99 | 42874.99 | 1.581498 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 30152.35 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 19641.781 | 19641.781 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19641.78 | 19641.78 | 0.724512 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00779045 | 40.8967 | 13783.92 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 12942.026 | 12942.026 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12942.03 | 12942.03 | 0.477383 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00778802 | 40.8842 | 9081.65 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 19774.733 | 19774.733 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19774.73 | 19774.73 | 0.729416 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00779182 | 40.9038 | 13877.05 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12941.807 | 12941.807 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12941.81 | 12941.81 | 0.477375 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00778802 | 40.8842 | 9081.49 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 14422.688 | 14422.688 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14422.69 | 14422.69 | 0.531999 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00784322 | 41.1690 | 10126.92 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 9597.423 | 9597.423 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9597.42 | 9597.42 | 0.354013 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00784446 | 41.1755 | 6738.06 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 14544.947 | 14544.947 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14544.95 | 14544.95 | 0.536509 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00784481 | 41.1773 | 10212.55 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 9597.326 | 9597.326 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9597.33 | 9597.33 | 0.354010 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00784446 | 41.1755 | 6737.99 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 15179.275 | 15179.275 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15179.28 | 15179.28 | 0.559907 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00777305 | 40.8061 | 10657.65 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 10069.912 | 10069.912 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10069.91 | 10069.91 | 0.371441 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00777270 | 40.8044 | 7069.52 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 15287.373 | 15287.373 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15287.37 | 15287.37 | 0.563894 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00777473 | 40.8149 | 10733.36 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 10069.810 | 10069.810 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10069.81 | 10069.81 | 0.371438 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00777270 | 40.8044 | 7069.45 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 98192.980 | 78618.726 | 5.931838 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 95607.10 | 95607.10 | 5.931838 | 25.99 | 14.60 | 0.00811402 | 10.62 | 8.97 | 0.00811402 | 33.90 | 0.00547527 | 15.07 | 20.1484 | 24.00 | 0.00878036 | 38.3517 | 66229.82 | 0.00 | 101250.14 | 72121.97 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 32566.011 | 32566.011 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 32566.01 | 32566.01 | 1.779551 | -5.83 | -5.83 | 0.00316597 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 67.1613 | 19.34 | 0.00753422 | 43.8550 | 17866.75 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 88349.573 | 70737.550 | 5.337198 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 86022.92 | 86022.92 | 5.337198 | 26.22 | 14.62 | 0.00805104 | 10.49 | 8.86 | 0.00805104 | 33.90 | 0.00547527 | 15.07 | 22.3932 | 24.00 | 0.00879690 | 38.4226 | 59465.50 | 0.00 | 91100.27 | 64892.07 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 34004.689 | 34004.689 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 34004.69 | 34004.69 | 1.601159 | -8.82 | -8.82 | 0.00263542 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 74.6440 | 17.60 | 0.00735355 | 47.7438 | 17577.49 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 103692.073 | 83021.604 | 6.264038 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 100961.38 | 100961.38 | 6.264038 | 25.90 | 14.57 | 0.00811951 | 10.62 | 8.98 | 0.00811951 | 33.90 | 0.00547527 | 15.07 | 19.0799 | 24.00 | 0.00874647 | 38.2053 | 69668.27 | 0.00 | 106920.45 | 76161.01 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 34014.838 | 34014.838 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 34014.84 | 34014.84 | 1.879211 | -5.63 | -5.63 | 0.00337983 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 63.5995 | 17.36 | 0.00754057 | 49.6833 | 26108.56 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 22096.173 | 22096.173 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | Sensible | 22096.17 | 12899.24 | 1.0000 | 0.46506947 | 0.475805 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22096.17 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 9010.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 24598.210 | 24598.210 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 24598.21 | 24598.21 | 1.0000 | 0.88686445 | 0.907336 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24598.21 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 17348.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 42874.990 | 42874.990 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 42874.99 | 42874.99 | 1.0000 | 1.54581590 | 1.581498 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 42874.99 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 30152.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 19641.781 | 19641.781 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19641.78 | 19641.78 | 1.0000 | 0.70816523 | 0.724512 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19641.78 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00779045 | 21.00 | 0.00779045 | 40.8967 | 13783.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 12942.026 | 12942.026 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12942.03 | 12942.03 | 1.0000 | 0.46661210 | 0.477383 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12942.03 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00778802 | 21.00 | 0.00778802 | 40.8842 | 9081.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 19774.733 | 19774.733 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19774.73 | 19774.73 | 1.0000 | 0.71295868 | 0.729416 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19774.73 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00779182 | 21.00 | 0.00779182 | 40.9038 | 13877.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 12941.807 | 12941.807 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12941.81 | 12941.81 | 1.0000 | 0.46660419 | 0.477375 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12941.81 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00778802 | 21.00 | 0.00778802 | 40.8842 | 9081.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 14422.688 | 14422.688 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14422.69 | 14422.69 | 1.0000 | 0.51999593 | 0.531999 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14422.69 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00784322 | 21.00 | 0.00784322 | 41.1690 | 10126.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9597.423 | 9597.423 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9597.42 | 9597.42 | 1.0000 | 0.34602571 | 0.354013 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9597.42 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00784446 | 21.00 | 0.00784446 | 41.1755 | 6738.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 14544.947 | 14544.947 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14544.95 | 14544.95 | 1.0000 | 0.52440386 | 0.536509 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14544.95 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00784481 | 21.00 | 0.00784481 | 41.1773 | 10212.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9597.326 | 9597.326 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9597.33 | 9597.33 | 1.0000 | 0.34602223 | 0.354010 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9597.33 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00784446 | 21.00 | 0.00784446 | 41.1755 | 6737.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 15179.275 | 15179.275 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15179.28 | 15179.28 | 1.0000 | 0.54727394 | 0.559907 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15179.28 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00777305 | 21.00 | 0.00777305 | 40.8061 | 10657.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10069.912 | 10069.912 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10069.91 | 10069.91 | 1.0000 | 0.36306086 | 0.371441 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10069.91 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00777270 | 21.00 | 0.00777270 | 40.8044 | 7069.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 15287.373 | 15287.373 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15287.37 | 15287.37 | 1.0000 | 0.55117132 | 0.563894 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15287.37 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00777473 | 21.00 | 0.00777473 | 40.8149 | 10733.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10069.810 | 10069.810 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10069.81 | 10069.81 | 1.0000 | 0.36305717 | 0.371438 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10069.81 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00777270 | 21.00 | 0.00777270 | 40.8044 | 7069.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 98192.980 | 78618.726 | 5.931838 | -999.0 | -999.000 | -999.0000 | 1.08174 | 1.00000 | 1019.9236 | 1004.8586 | 0.9774 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.931838 | 5.79800147 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 95607.10 | 95607.10 | 0.9737 | 5.79800147 | 5.931838 | 25.99 | 14.60 | 0.00811402 | 46805.6 | 10.62 | 8.97 | 0.00811402 | 31122.6 | -999.0 | -999.00 | -999.00 | -999.00 | 12901.085 | 82706.01 | 33.90 | 0.00547527 | 15.07 | 1.19517000 | 20.1484 | 24.00 | 0.00878036 | 24.00 | 0.00878036 | 38.3517 | 66229.82 | 0.00 | 101250.14 | 72121.97 | 5.56902425 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.99 | 13.21 | 0.00913394 | 37141.4 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32566.011 | 32566.011 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.931838 | 5.79800147 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 32566.01 | 32566.01 | 1.0000 | 1.73940044 | 1.779551 | -5.83 | -5.83 | 0.00316597 | 2023.3 | 12.80 | 9.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32566.01 | -17.90 | 0.00095524 | -17.90 | 1.19517000 | 67.1613 | 18.85 | 0.00768733 | 19.34 | 0.00753422 | 43.8550 | 17866.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 88349.573 | 70737.550 | 5.337198 | -999.0 | -999.000 | -999.0000 | 1.05812 | 1.00000 | 1019.8065 | 1004.8586 | 0.9774 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.337198 | 5.21677778 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 86022.92 | 86022.92 | 0.9737 | 5.21677778 | 5.337198 | 26.22 | 14.62 | 0.00805104 | 46876.7 | 10.49 | 8.86 | 0.00805104 | 30837.2 | -999.0 | -999.00 | -999.00 | -999.00 | 12267.344 | 73755.57 | 33.90 | 0.00547527 | 15.07 | 1.19517000 | 22.3932 | 24.00 | 0.00879690 | 24.00 | 0.00879690 | 38.4226 | 59465.50 | 0.00 | 91100.27 | 64892.07 | 5.01075450 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.99 | 13.21 | 0.00913394 | 37141.4 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34004.689 | 34004.689 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.337198 | 5.21677778 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 34004.69 | 34004.69 | 1.0000 | 1.56503334 | 1.601159 | -8.82 | -8.82 | 0.00263542 | -2317.6 | 12.80 | 9.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34004.69 | -17.90 | 0.00095524 | -17.90 | 1.19517000 | 74.6440 | 17.90 | 0.00758162 | 17.60 | 0.00735355 | 47.7438 | 17577.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 103692.073 | 83021.604 | 6.264038 | -999.0 | -999.000 | -999.0000 | 1.08836 | 1.00000 | 1019.9338 | 1004.8586 | 0.9774 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.264038 | 6.12270647 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 100961.38 | 100961.38 | 0.9737 | 6.12270647 | 6.264038 | 25.90 | 14.57 | 0.00811951 | 46719.2 | 10.62 | 8.98 | 0.00811951 | 31136.5 | -999.0 | -999.00 | -999.00 | -999.00 | 13623.583 | 87337.79 | 33.90 | 0.00547527 | 15.07 | 1.19517000 | 19.0799 | 24.00 | 0.00874647 | 24.00 | 0.00874647 | 38.2053 | 69668.27 | 0.00 | 106920.45 | 76161.01 | 5.88090584 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.99 | 13.21 | 0.00913394 | 37141.4 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34014.838 | 34014.838 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.264038 | 6.12270647 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 34014.84 | 34014.84 | 1.0000 | 1.83681194 | 1.879211 | -5.63 | -5.63 | 0.00337983 | 2761.3 | 12.80 | 9.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34014.84 | -17.90 | 0.00095524 | -17.90 | 1.19517000 | 63.5995 | 15.81 | 0.00761613 | 17.36 | 0.00754057 | 49.6833 | 26108.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.93 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.34 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 6.26 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1439.83 | 2937.67 | 57.33 |
CORE_MID | 1386.00 | 3692.33 | 392.83 |
CORE_TOP | 2031.00 | 3946.50 | 1078.17 |
PERIMETER_TOP_ZN_3 | 3207.83 | 4124.83 | 2129.17 |
PERIMETER_TOP_ZN_2 | 3226.50 | 3756.83 | 1788.17 |
PERIMETER_TOP_ZN_1 | 3025.50 | 3264.50 | 1423.00 |
PERIMETER_TOP_ZN_4 | 3194.00 | 3994.50 | 1925.17 |
PERIMETER_BOT_ZN_3 | 2701.83 | 4181.83 | 1830.00 |
PERIMETER_BOT_ZN_2 | 2826.33 | 3615.83 | 1297.67 |
PERIMETER_BOT_ZN_1 | 2503.67 | 3426.17 | 1096.67 |
PERIMETER_BOT_ZN_4 | 2679.17 | 3821.83 | 1383.00 |
PERIMETER_MID_ZN_3 | 2698.50 | 3964.33 | 1553.83 |
PERIMETER_MID_ZN_2 | 2452.67 | 3127.50 | 1230.67 |
PERIMETER_MID_ZN_1 | 2741.00 | 2976.00 | 984.50 |
PERIMETER_MID_ZN_4 | 2768.50 | 3769.67 | 1405.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4719.17 | 4622.83 | 2474.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.17 | 0.00 | 0.17 | 0.00 |
CORE_TOP | 1.33 | 0.00 | 0.50 | 0.00 |
PERIMETER_TOP_ZN_3 | 84.00 | 7.67 | 31.50 | 5.50 |
PERIMETER_TOP_ZN_2 | 61.33 | 31.50 | 9.50 | 30.33 |
PERIMETER_TOP_ZN_1 | 47.17 | 41.83 | 8.83 | 39.83 |
PERIMETER_TOP_ZN_4 | 62.50 | 28.83 | 13.00 | 19.00 |
PERIMETER_BOT_ZN_3 | 7.00 | 0.00 | 4.33 | 0.00 |
PERIMETER_BOT_ZN_2 | 2.17 | 20.17 | 0.00 | 20.17 |
PERIMETER_BOT_ZN_1 | 329.67 | 87.83 | 328.33 | 86.50 |
PERIMETER_BOT_ZN_4 | 2.17 | 19.83 | 0.00 | 12.50 |
PERIMETER_MID_ZN_3 | 12.33 | 3.50 | 5.00 | 2.83 |
PERIMETER_MID_ZN_2 | 10.00 | 28.00 | 1.33 | 27.83 |
PERIMETER_MID_ZN_1 | 6.00 | 49.67 | 1.00 | 48.83 |
PERIMETER_MID_ZN_4 | 9.50 | 25.50 | 2.00 | 17.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 413.67 | 208.50 | 350.33 | 190.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.70 | 52.94 | 2698.04 | 1.034 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.70 | 52.94 | 2698.04 | 0.711 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.70 | 52.94 | 2698.04 | 0.704 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.57 | 11.16 | 568.77 | 0.793 | 0.083 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 1.467 | 0.088 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.57 | 11.16 | 568.77 | 1.461 | 0.084 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 1.465 | 0.088 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.57 | 11.16 | 568.77 | 0.680 | 0.044 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 1.216 | 0.047 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.57 | 11.16 | 568.77 | 1.074 | 1.329 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 1.126 | 0.047 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.57 | 11.16 | 568.77 | 0.775 | 0.070 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 1.368 | 0.079 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.57 | 11.16 | 568.77 | 1.417 | 0.070 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 1.374 | 0.073 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.70 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.70 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.70 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.70 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.70 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.70 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.54 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.56 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 16715086.74 | 0.00 | 16715086.74 | 0.00 | 16715086.74 | 13393058.27 | 5496.02 | 71.08 | 3192.89 | 130.75 |
CORE_MID | 11451576.31 | 0.00 | 11451576.31 | 0.00 | 11451576.31 | 13393058.27 | 6414.65 | 27.08 | 2318.27 | 121.37 |
CORE_TOP | 11319183.91 | 0.00 | 11319183.91 | 0.00 | 11319183.91 | 13393058.27 | 6414.63 | 21.25 | 2324.12 | 98.33 |
PERIMETER_TOP_ZN_3 | 2687727.36 | 0.00 | 2687727.36 | 579019.07 | 3266746.43 | 2823374.22 | 5525.72 | 38.41 | 3195.87 | 98.31 |
PERIMETER_TOP_ZN_2 | 3141231.24 | 0.00 | 3141231.24 | 386010.39 | 3527241.63 | 1787429.43 | 4058.93 | 2.05 | 4699.02 | 98.33 |
PERIMETER_TOP_ZN_1 | 4926968.66 | 0.00 | 4926968.66 | 579019.07 | 5505987.73 | 2823374.22 | 4093.20 | 4.47 | 4662.33 | 98.33 |
PERIMETER_TOP_ZN_4 | 3154078.31 | 0.00 | 3154078.31 | 386010.39 | 3540088.70 | 1787312.18 | 4083.20 | 8.94 | 4667.86 | 98.33 |
PERIMETER_BOT_ZN_3 | 2337777.35 | 0.00 | 2337777.35 | 307860.96 | 2645638.31 | 2823374.22 | 6150.94 | 61.73 | 2547.32 | 130.75 |
PERIMETER_BOT_ZN_2 | 2630684.48 | 0.00 | 2630684.48 | 205239.41 | 2835923.89 | 1787429.43 | 4022.18 | 22.35 | 4715.47 | 130.75 |
PERIMETER_BOT_ZN_1 | 3664337.56 | 0.00 | 3664337.56 | 4630536.35 | 8294873.91 | 2823374.22 | 4522.06 | 83.23 | 4154.71 | 130.75 |
PERIMETER_BOT_ZN_4 | 2449907.15 | 0.00 | 2449907.15 | 205239.41 | 2655146.56 | 1787312.18 | 4176.51 | 25.73 | 4557.76 | 130.75 |
PERIMETER_MID_ZN_3 | 2628402.43 | 0.00 | 2628402.43 | 481988.59 | 3110391.02 | 2823374.22 | 5670.14 | 43.03 | 3046.83 | 121.37 |
PERIMETER_MID_ZN_2 | 3119137.62 | 0.00 | 3119137.62 | 321323.80 | 3440461.41 | 1787429.43 | 4005.13 | 2.58 | 4752.29 | 1030.37 |
PERIMETER_MID_ZN_1 | 4782502.65 | 0.00 | 4782502.65 | 481988.59 | 5264491.24 | 2823374.22 | 4066.44 | 7.66 | 4685.91 | 121.37 |
PERIMETER_MID_ZN_4 | 2958217.56 | 0.00 | 2958217.56 | 321323.80 | 3279541.36 | 1787312.18 | 4020.85 | 11.27 | 4727.89 | 121.37 |
Total Facility | 77966819.31 | 0.00 | 77966819.31 | 8885559.83 | 86852379.14 | 67843644.98 | 6638.30 | 350.11 | 4916.35 | 1158.75 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7651 | 0.0000 | 0.7651 | 0.0000 | 0.7651 | 0.4247 | 2783.09 | 70.92 | 3088.99 |
CORE_MID | 0.5265 | 0.0000 | 0.5265 | 0.0000 | 0.5265 | 0.4247 | 3654.83 | 27.08 | 2261.09 |
CORE_TOP | 0.5218 | 0.0000 | 0.5218 | 0.0000 | 0.5218 | 0.4247 | 3646.87 | 21.25 | 2274.87 |
PERIMETER_TOP_ZN_3 | 0.1241 | 0.0000 | 0.1241 | 0.0131 | 0.1372 | 0.0895 | 2757.96 | 38.41 | 3146.62 |
PERIMETER_TOP_ZN_2 | 0.1452 | 0.0000 | 0.1452 | 0.0087 | 0.1539 | 0.0567 | 1291.18 | 2.05 | 4649.78 |
PERIMETER_TOP_ZN_1 | 0.2283 | 0.0000 | 0.2283 | 0.0131 | 0.2413 | 0.0895 | 1325.45 | 4.47 | 4613.09 |
PERIMETER_TOP_ZN_4 | 0.1452 | 0.0000 | 0.1452 | 0.0087 | 0.1539 | 0.0567 | 1315.45 | 8.94 | 4618.62 |
PERIMETER_BOT_ZN_3 | 0.1063 | 0.0000 | 0.1063 | 0.0070 | 0.1133 | 0.0895 | 3437.90 | 61.57 | 2443.53 |
PERIMETER_BOT_ZN_2 | 0.1203 | 0.0000 | 0.1203 | 0.0046 | 0.1250 | 0.0567 | 1310.28 | 22.35 | 4610.37 |
PERIMETER_BOT_ZN_1 | 0.1681 | 0.0000 | 0.1681 | 0.2090 | 0.3771 | 0.0895 | 1809.04 | 83.23 | 4050.73 |
PERIMETER_BOT_ZN_4 | 0.1115 | 0.0000 | 0.1115 | 0.0046 | 0.1161 | 0.0567 | 1464.69 | 25.70 | 4452.62 |
PERIMETER_MID_ZN_3 | 0.1211 | 0.0000 | 0.1211 | 0.0109 | 0.1320 | 0.0895 | 2910.32 | 43.03 | 2989.65 |
PERIMETER_MID_ZN_2 | 0.1354 | 0.0000 | 0.1354 | 0.0078 | 0.1432 | 0.0567 | 1245.44 | 2.58 | 3785.99 |
PERIMETER_MID_ZN_1 | 0.2214 | 0.0000 | 0.2214 | 0.0109 | 0.2322 | 0.0895 | 1306.62 | 7.66 | 4628.72 |
PERIMETER_MID_ZN_4 | 0.1360 | 0.0000 | 0.1360 | 0.0073 | 0.1433 | 0.0567 | 1261.20 | 11.24 | 4670.56 |
Total Facility | 3.5762 | 0.0000 | 3.5762 | 0.3056 | 3.8819 | 2.1513 | 3841.80 | 349.89 | 4780.85 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 26557565.51 | 0.00 | 26557565.51 | 22614548.33 | 4236.68 | 732.62 | 3790.69 | 130.75 |
PACU_VAV_MID | 23827144.90 | 0.00 | 23827144.90 | 22614548.33 | 4083.07 | 46.49 | 4630.44 | 121.37 |
PACU_VAV_TOP | 24103564.25 | 0.00 | 24103564.25 | 22614548.33 | 4105.34 | 65.20 | 4589.45 | 97.86 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.2147 | 0.0000 | 1.2147 | 0.7171 | 1523.75 | 732.62 | 3686.62 |
PACU_VAV_MID | 1.0975 | 0.0000 | 1.0975 | 0.7171 | 1323.25 | 46.49 | 4573.26 |
PACU_VAV_TOP | 1.1126 | 0.0000 | 1.1126 | 0.7171 | 1337.59 | 65.20 | 4540.21 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 2988.07 | 0.00 | 0.00 | 0.00 | 1916.21 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 2761.00 | 0.00 | 0.00 | 0.00 | 2168.55 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2775.69 | 0.00 | 0.00 | 0.00 | 2135.17 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.0248 | 0.0000 | 0.0000 | 0.0000 | 0.7484 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 1.8490 | 0.0000 | 0.0000 | 0.0000 | 0.7580 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 1.8696 | 0.0000 | 0.0000 | 0.0000 | 0.7527 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 824 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1580.09 | 15539.06 | 09-APR-17:10 | 209717.90 | 06-FEB-07:10 |
Electricity:Building | 1042.89 | 15341.49 | 01-JAN-08:50 | 74397.12 | 21-DEC-08:10 |
Electricity:Zone:CORE_BOTTOM | 310.83 | 4652.71 | 01-JAN-00:10 | 24063.48 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1042.89 | 15341.49 | 01-JAN-08:50 | 74397.12 | 21-DEC-08:10 |
InteriorLights:Electricity | 280.84 | 1316.11 | 01-JAN-08:50 | 28079.40 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 280.84 | 1316.11 | 01-JAN-08:50 | 28079.40 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 280.84 | 1316.11 | 01-JAN-08:50 | 28079.40 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 280.84 | 1316.11 | 01-JAN-08:50 | 28079.40 | 02-JAN-16:50 |
Electricity:Zone:CORE_MID | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 35.95 | 541.99 | 01-JAN-08:50 | 2674.44 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.26 | 40.03 | 01-JAN-08:50 | 1168.55 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.26 | 40.03 | 01-JAN-08:50 | 1168.55 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 22.76 | 343.10 | 01-JAN-07:50 | 1693.08 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.86 | 25.34 | 01-JAN-07:50 | 739.79 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.86 | 25.34 | 01-JAN-07:50 | 739.79 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 35.88 | 541.99 | 01-JAN-08:00 | 2674.43 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.19 | 40.03 | 01-JAN-08:00 | 1168.55 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.19 | 40.03 | 01-JAN-08:00 | 1168.55 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 22.72 | 343.10 | 01-JAN-08:50 | 1693.03 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.82 | 25.34 | 01-JAN-08:50 | 739.74 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.82 | 25.34 | 01-JAN-08:50 | 739.74 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 35.94 | 541.99 | 01-JAN-08:40 | 2674.44 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.25 | 40.03 | 01-JAN-08:40 | 1168.55 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.25 | 40.03 | 01-JAN-08:40 | 1168.55 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 22.75 | 343.10 | 01-JAN-07:50 | 1693.08 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.86 | 25.34 | 01-JAN-07:50 | 739.79 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.86 | 25.34 | 01-JAN-07:50 | 739.79 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 35.87 | 541.99 | 01-JAN-08:00 | 2674.43 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.18 | 40.03 | 01-JAN-08:00 | 1168.55 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.18 | 40.03 | 01-JAN-08:00 | 1168.55 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 22.71 | 343.10 | 01-JAN-08:40 | 1693.03 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.82 | 25.34 | 01-JAN-08:40 | 739.74 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.82 | 25.34 | 01-JAN-08:40 | 739.74 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 35.95 | 541.99 | 01-JAN-08:50 | 2674.44 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.26 | 40.03 | 01-JAN-08:50 | 1168.55 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.26 | 40.03 | 01-JAN-08:50 | 1168.55 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 22.76 | 343.10 | 01-JAN-07:50 | 1693.08 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.86 | 25.34 | 01-JAN-07:50 | 739.79 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.86 | 25.34 | 01-JAN-07:50 | 739.79 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 35.88 | 541.99 | 01-JAN-08:00 | 2674.43 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.19 | 40.03 | 01-JAN-08:00 | 1168.55 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.19 | 40.03 | 01-JAN-08:00 | 1168.55 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 22.72 | 343.10 | 01-JAN-08:50 | 1693.03 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.82 | 25.34 | 01-JAN-08:50 | 739.74 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.82 | 25.34 | 01-JAN-08:50 | 739.74 | 02-JAN-16:50 |
InteriorEquipment:Electricity | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 247.34 | 4344.73 | 01-JAN-00:10 | 18520.31 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 465.17 | 197.57 | 12-MAR-08:30 | 178504.22 | 06-FEB-07:10 |
ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 926.74 | 02-JAN-17:00 |
Transformer:ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 926.74 | 02-JAN-17:00 |
ElectricityPurchased:Facility | 1580.09 | 15539.06 | 24-JUN-18:20 | 209717.90 | 06-FEB-07:10 |
ElectricityPurchased:Plant | 1580.09 | 15539.06 | 24-JUN-18:20 | 209717.90 | 06-FEB-07:10 |
Cogeneration:ElectricityPurchased | 1580.09 | 15539.06 | 24-JUN-18:20 | 209717.90 | 06-FEB-07:10 |
General:Cogeneration:ElectricityPurchased | 1580.09 | 15539.06 | 24-JUN-18:20 | 209717.90 | 06-FEB-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1580.09 | 15539.06 | 24-JUN-18:20 | 209717.90 | 06-FEB-07:10 |
ElectricityNet:Plant | 1580.09 | 15539.06 | 24-JUN-18:20 | 209717.90 | 06-FEB-07:10 |
Cogeneration:ElectricityNet | 1580.09 | 15539.06 | 24-JUN-18:20 | 209717.90 | 06-FEB-07:10 |
General:Cogeneration:ElectricityNet | 1580.09 | 15539.06 | 24-JUN-18:20 | 209717.90 | 06-FEB-07:10 |
Heating:Electricity | 156.88 | 0.00 | 01-JAN-00:40 | 171881.05 | 06-FEB-07:10 |
General:Heating:Electricity | 156.88 | 0.00 | 01-JAN-00:40 | 171881.05 | 06-FEB-07:10 |
Fans:Electricity | 120.87 | 0.00 | 01-JAN-00:40 | 34957.46 | 24-JUL-15:30 |
General:Fans:Electricity | 120.87 | 0.00 | 01-JAN-00:40 | 34957.46 | 24-JUL-15:30 |
ExteriorLights:Electricity | 72.02 | 0.00 | 01-JAN-07:30 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 72.02 | 0.00 | 01-JAN-07:30 | 5557.43 | 01-JAN-06:10 |
Cooling:Electricity | 174.44 | 0.00 | 01-JAN-00:10 | 84403.91 | 26-JUN-15:10 |
General:Cooling:Electricity | 174.44 | 0.00 | 01-JAN-00:10 | 84403.91 | 26-JUN-15:10 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 7.89 | 0.00 | 01-JAN-00:10 | 789.03 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 641.94 | 12061.80 | 01-JAN-00:10 | 36271.65 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 244.09 | 1156.00 | 10-JAN-06:10 | 112156.86 | 23-DEC-07:20 |
NaturalGas:HVAC | 133.30 | 0.00 | 01-JAN-00:20 | 104241.97 | 23-DEC-07:30 |
Heating:NaturalGas | 133.30 | 0.00 | 01-JAN-00:20 | 104241.97 | 23-DEC-07:30 |
General:Heating:NaturalGas | 133.30 | 0.00 | 01-JAN-00:20 | 104241.97 | 23-DEC-07:30 |
NaturalGas:Plant | 110.80 | 1156.00 | 05-JAN-05:10 | 9796.16 | 07-FEB-12:30 |
WaterSystems:NaturalGas | 110.80 | 1156.00 | 05-JAN-05:10 | 9796.16 | 07-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 110.80 | 1156.00 | 05-JAN-05:10 | 9796.16 | 07-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2167.11 | 0.00 | 01-JAN-00:40 | 417911.81 | 26-JUN-15:20 |
EnergyTransfer:Building | 1181.44 | 0.00 | 01-JAN-00:40 | 175539.52 | 26-JUN-15:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 226.72 | 0.00 | 01-JAN-00:10 | 27391.87 | 05-SEP-08:00 |
Heating:EnergyTransfer | 140.32 | 0.00 | 01-JAN-00:40 | 161054.73 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 4357.29 | 26-DEC-07:10 |
General:Heating:EnergyTransfer | 140.32 | 0.00 | 01-JAN-00:40 | 161054.73 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 4357.29 | 26-DEC-07:10 |
Cooling:EnergyTransfer | 1041.12 | 0.00 | 01-JAN-00:40 | 175539.52 | 26-JUN-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 226.72 | 0.00 | 01-JAN-00:10 | 27391.87 | 05-SEP-08:00 |
General:Cooling:EnergyTransfer | 1041.12 | 0.00 | 01-JAN-00:40 | 175539.52 | 26-JUN-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 226.72 | 0.00 | 01-JAN-00:10 | 27391.87 | 05-SEP-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 58.62 | 0.00 | 01-JAN-00:40 | 15062.86 | 22-DEC-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.30 | 0.00 | 01-JAN-00:40 | 15062.86 | 22-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.30 | 0.00 | 01-JAN-00:40 | 15062.86 | 22-DEC-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 35.32 | 0.00 | 01-JAN-00:10 | 12636.91 | 26-JUN-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 35.32 | 0.00 | 01-JAN-00:10 | 12636.91 | 26-JUN-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 27.97 | 0.00 | 01-JAN-00:10 | 7440.92 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.83 | 0.00 | 01-JAN-00:10 | 7440.92 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.83 | 0.00 | 01-JAN-00:10 | 7440.92 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 17.14 | 0.00 | 01-JAN-00:10 | 5608.42 | 17-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 17.14 | 0.00 | 01-JAN-00:10 | 5608.42 | 17-JUL-14:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 28.32 | 0.00 | 01-JAN-00:10 | 5827.34 | 17-JUL-15:30 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 6.61 | 0.00 | 01-JAN-00:10 | 4354.88 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 6.61 | 0.00 | 01-JAN-00:10 | 4354.88 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 21.70 | 0.00 | 01-JAN-00:10 | 5827.34 | 17-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 21.70 | 0.00 | 01-JAN-00:10 | 5827.34 | 17-JUL-15:30 |
EnergyTransfer:Zone:CORE_MID | 147.23 | 0.00 | 01-JAN-00:10 | 19605.51 | 17-JUL-07:40 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.67 | 0.00 | 01-JAN-00:10 | 16825.53 | 26-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.67 | 0.00 | 01-JAN-00:10 | 16825.53 | 26-DEC-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 146.56 | 0.00 | 01-JAN-00:10 | 19605.51 | 17-JUL-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 146.56 | 0.00 | 01-JAN-00:10 | 19605.51 | 17-JUL-07:40 |
EnergyTransfer:Zone:CORE_TOP | 142.71 | 0.00 | 01-JAN-00:40 | 28065.69 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 6.08 | 0.00 | 01-JAN-00:10 | 28065.69 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 6.08 | 0.00 | 01-JAN-00:10 | 28065.69 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 136.63 | 0.00 | 01-JAN-00:40 | 21401.44 | 17-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 136.63 | 0.00 | 01-JAN-00:40 | 21401.44 | 17-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 45.28 | 0.00 | 01-JAN-00:40 | 9803.34 | 23-DEC-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 15.24 | 0.00 | 01-JAN-00:40 | 9803.34 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 15.24 | 0.00 | 01-JAN-00:40 | 9803.34 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.04 | 0.00 | 01-JAN-00:20 | 8145.85 | 17-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.04 | 0.00 | 01-JAN-00:20 | 8145.85 | 17-JUL-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 43.58 | 0.00 | 01-JAN-00:40 | 9756.71 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 8.23 | 0.00 | 01-JAN-00:40 | 8696.31 | 22-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 8.23 | 0.00 | 01-JAN-00:40 | 8696.31 | 22-DEC-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 35.35 | 0.00 | 01-JAN-00:20 | 9756.71 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 35.35 | 0.00 | 01-JAN-00:20 | 9756.71 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 70.47 | 0.00 | 01-JAN-00:40 | 13886.24 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 10.11 | 0.00 | 01-JAN-00:10 | 11954.04 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 10.11 | 0.00 | 01-JAN-00:10 | 11954.04 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 60.37 | 0.00 | 01-JAN-00:40 | 13886.24 | 28-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 60.37 | 0.00 | 01-JAN-00:40 | 13886.24 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 43.15 | 0.00 | 01-JAN-00:40 | 10781.32 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 8.99 | 0.00 | 01-JAN-00:10 | 8773.66 | 22-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 8.99 | 0.00 | 01-JAN-00:10 | 8773.66 | 22-DEC-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 34.16 | 0.00 | 01-JAN-00:20 | 10781.32 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 34.16 | 0.00 | 01-JAN-00:20 | 10781.32 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 32.81 | 0.00 | 01-JAN-00:10 | 6892.51 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 6.55 | 0.00 | 01-JAN-00:10 | 6892.51 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 6.55 | 0.00 | 01-JAN-00:10 | 6892.51 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 26.26 | 0.00 | 01-JAN-00:10 | 6477.55 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 26.26 | 0.00 | 01-JAN-00:10 | 6477.55 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 34.98 | 0.00 | 01-JAN-00:10 | 7826.17 | 17-JUL-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.98 | 0.00 | 01-JAN-00:10 | 6164.37 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.98 | 0.00 | 01-JAN-00:10 | 6164.37 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 32.00 | 0.00 | 01-JAN-00:10 | 7826.17 | 17-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 32.00 | 0.00 | 01-JAN-00:10 | 7826.17 | 17-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 65.77 | 0.00 | 01-JAN-00:10 | 14608.26 | 21-DEC-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 20.64 | 0.00 | 01-JAN-00:10 | 14608.26 | 21-DEC-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 20.64 | 0.00 | 01-JAN-00:10 | 14608.26 | 21-DEC-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 45.13 | 0.00 | 01-JAN-00:10 | 12494.96 | 26-JUN-16:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 45.13 | 0.00 | 01-JAN-00:10 | 12494.96 | 26-JUN-16:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 32.57 | 0.00 | 01-JAN-00:10 | 8247.35 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 3.14 | 0.00 | 01-JAN-00:10 | 6192.90 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 3.14 | 0.00 | 01-JAN-00:10 | 6192.90 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 29.43 | 0.00 | 01-JAN-00:10 | 8247.35 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 29.43 | 0.00 | 01-JAN-00:10 | 8247.35 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 37.55 | 0.00 | 01-JAN-00:10 | 7855.88 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 6.19 | 0.00 | 01-JAN-00:10 | 7855.88 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 6.19 | 0.00 | 01-JAN-00:10 | 7855.88 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 31.36 | 0.00 | 01-JAN-00:10 | 7479.95 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 31.36 | 0.00 | 01-JAN-00:10 | 7479.95 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 39.67 | 0.00 | 01-JAN-00:10 | 9533.05 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 3.46 | 0.00 | 01-JAN-00:10 | 6482.46 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 3.46 | 0.00 | 01-JAN-00:10 | 6482.46 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 36.21 | 0.00 | 01-JAN-00:10 | 9533.05 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 36.21 | 0.00 | 01-JAN-00:10 | 9533.05 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 65.75 | 0.00 | 01-JAN-00:10 | 12667.77 | 28-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 3.74 | 0.00 | 01-JAN-00:10 | 9674.79 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 3.74 | 0.00 | 01-JAN-00:10 | 9674.79 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 62.01 | 0.00 | 01-JAN-00:10 | 12667.77 | 28-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 62.01 | 0.00 | 01-JAN-00:10 | 12667.77 | 28-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 38.27 | 0.00 | 01-JAN-00:10 | 10018.32 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 3.56 | 0.00 | 01-JAN-00:10 | 6531.71 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 3.56 | 0.00 | 01-JAN-00:10 | 6531.71 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 34.72 | 0.00 | 01-JAN-00:10 | 10018.32 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 34.72 | 0.00 | 01-JAN-00:10 | 10018.32 | 16-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 51.77 | 0.00 | 01-JAN-00:10 | 6542.97 | 16-FEB-12:10 |
PlantLoopHeatingDemand:Plant | 51.77 | 0.00 | 01-JAN-00:10 | 6542.97 | 16-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 51.77 | 0.00 | 01-JAN-00:10 | 6542.97 | 16-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 51.77 | 0.00 | 01-JAN-00:10 | 6542.97 | 16-FEB-12:10 |
EnergyTransfer:HVAC | 933.90 | 0.00 | 01-JAN-00:40 | 238220.43 | 26-JUN-15:20 |
HeatingCoils:EnergyTransfer | 263.52 | 0.00 | 01-JAN-00:40 | 230508.86 | 23-DEC-07:10 |
CoolingCoils:EnergyTransfer | 670.39 | 0.00 | 01-JAN-00:10 | 238220.43 | 26-JUN-15:20 |
EnergyTransfer:Plant | 51.77 | 0.00 | 01-JAN-00:10 | 6542.97 | 16-FEB-12:10 |
WaterSystems:EnergyTransfer | 51.77 | 0.00 | 01-JAN-00:10 | 6542.97 | 16-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 51.77 | 0.00 | 01-JAN-00:10 | 6542.97 | 16-FEB-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.004 | -226.720 | 0.000 | 0.000 | 32.875 | 63.485 | 247.342 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -116.987 |
CORE_MID | 0.000 | 0.000 | 0.669 | -146.564 | 0.000 | 0.000 | 34.070 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -78.261 |
CORE_TOP | 0.000 | 0.000 | 6.080 | -136.627 | 0.000 | 0.000 | 34.825 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -94.362 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 15.243 | -30.041 | 0.000 | 0.000 | 7.545 | 9.264 | 26.688 | 18.877 | 0.000 | 0.159 | 0.000 | 0.000 | -33.596 | 0.000 | -7.200 | -6.938 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 8.229 | -35.349 | 0.000 | 0.000 | 4.688 | 5.862 | 16.895 | 42.390 | 0.000 | 0.105 | 0.001 | 0.000 | -21.562 | 0.000 | -4.891 | -16.367 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 10.106 | -60.367 | 0.000 | 0.000 | 7.263 | 9.191 | 26.688 | 87.733 | 0.000 | 0.155 | 0.002 | 0.000 | -32.699 | 0.000 | -7.560 | -40.510 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 8.987 | -34.164 | 0.000 | 0.000 | 4.773 | 5.822 | 16.895 | 39.045 | 0.000 | 0.108 | 0.001 | 0.000 | -22.180 | 0.000 | -4.900 | -14.385 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 6.550 | -26.263 | 0.000 | 0.000 | 7.533 | 9.253 | 26.688 | 19.186 | 0.000 | 0.093 | 0.001 | 0.000 | -34.812 | 0.000 | -4.006 | -4.221 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 2.980 | -31.998 | 0.000 | 0.000 | 4.644 | 5.856 | 16.895 | 42.529 | 0.000 | 0.057 | 0.003 | 0.000 | -22.827 | 0.000 | -2.784 | -15.353 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 20.636 | -45.131 | 0.000 | 0.000 | 7.439 | 9.185 | 26.688 | 88.473 | 0.000 | 3.531 | 0.001 | 0.000 | -34.704 | 0.000 | -48.213 | -27.905 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 3.136 | -29.432 | 0.000 | 0.000 | 4.714 | 5.817 | 16.895 | 39.208 | 0.000 | 0.058 | 0.001 | 0.000 | -23.462 | 0.000 | -2.785 | -14.148 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 6.192 | -31.358 | 0.000 | 0.000 | 7.461 | 9.264 | 26.688 | 18.640 | 0.000 | 0.136 | 4.783 | 0.000 | -35.473 | 0.000 | -6.332 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 3.459 | -36.213 | 0.000 | 0.000 | 3.441 | 5.862 | 16.895 | 42.203 | 0.000 | 0.090 | 0.002 | 0.000 | -22.678 | 0.000 | -4.288 | -8.772 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 3.742 | -62.011 | 0.000 | 0.000 | 7.173 | 9.192 | 26.688 | 87.450 | 0.000 | 0.131 | 0.002 | 0.000 | -34.488 | 0.000 | -6.645 | -31.232 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 3.560 | -34.715 | 0.000 | 0.000 | 4.717 | 5.822 | 16.895 | 38.888 | 0.000 | 0.090 | 0.000 | 0.000 | -23.397 | 0.000 | -4.303 | -7.557 |
TOPFLOOR_PLENUM | 23.305 | -35.315 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.162 | 22.863 | 0.000 | 0.000 | 0.000 | -11.015 | -0.001 |
MIDFLOOR_PLENUM | 10.827 | -17.144 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.199 | 17.104 | 0.000 | 0.000 | 0.000 | -10.986 | -0.000 |
FIRSTFLOOR_PLENUM | 6.614 | -21.703 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.153 | 23.812 | 0.000 | 0.000 | 0.000 | -8.876 | -0.000 |
Total Facility | 40.746 | -74.161 | 99.571 | -966.954 | 0.000 | 0.000 | 173.161 | 280.845 | 762.041 | 564.622 | 0.000 | 5.225 | 68.574 | 0.000 | -341.877 | 0.000 | -134.784 | -476.999 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 24-JUL-04:02 | 0.00 | 0.00 | 0.00 | -43656.19 | 0.00 | 0.00 | 0.00 | 615.87 | 5138.45 | 0.00 | 0.00 | 0.00 | 37901.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 24-JUL-04:02 | 0.00 | 0.00 | 0.00 | -32480.21 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 28689.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 17-JUL-04:02 | 0.00 | 0.00 | 0.00 | -35088.65 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 31297.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-14:32 | 0.00 | 0.00 | 0.00 | -11812.83 | 0.00 | 0.00 | 24.59 | 40.03 | 501.96 | 4983.32 | 0.00 | 400.78 | 5862.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 09-JUL-09:12 | 0.00 | 0.00 | 0.00 | -13992.65 | 0.00 | 0.00 | 14.19 | 25.34 | 317.77 | 9316.19 | 0.00 | 0.00 | 4347.87 | 0.00 | -0.00 | 0.00 | -28.70 | 0.00 |
PERIMETER_TOP_ZN_1 | 05-NOV-13:31 | 0.00 | 0.00 | 0.00 | -18052.95 | 0.00 | 0.00 | 21.86 | 40.03 | 501.96 | 17225.99 | 0.00 | 0.00 | 311.11 | 0.00 | -0.00 | 0.00 | -47.99 | 0.00 |
PERIMETER_TOP_ZN_4 | 11-JUN-16:31 | 0.00 | 0.00 | 0.00 | -16452.13 | 0.00 | 0.00 | 11.17 | 25.34 | 317.76 | 10942.22 | 0.00 | 4.01 | 5151.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 17-JUL-06:03 | 0.00 | 0.00 | 0.00 | -7130.75 | 0.00 | 0.00 | 144.93 | 240.13 | 669.29 | 2567.69 | 0.00 | 0.00 | 3515.63 | 0.00 | -0.00 | 0.00 | -6.92 | 0.00 |
PERIMETER_BOT_ZN_2 | 06-AUG-09:41 | 0.00 | 0.00 | 0.00 | -11397.52 | 0.00 | 0.00 | 15.28 | 25.34 | 317.77 | 8335.54 | 0.00 | 0.00 | 2714.97 | 0.00 | -0.00 | 0.00 | -11.38 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-13:21 | 0.00 | 0.00 | 0.00 | -14328.15 | 0.00 | 0.00 | 21.86 | 40.03 | 501.96 | 15407.99 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -49.06 | -1594.63 |
PERIMETER_BOT_ZN_4 | 10-SEP-16:41 | 0.00 | 0.00 | 0.00 | -13450.46 | 0.00 | 0.00 | 13.30 | 25.34 | 317.76 | 9912.40 | 0.00 | 14.27 | 3167.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-14:22 | 0.00 | 0.00 | 0.00 | -10003.92 | 0.00 | 0.00 | 26.13 | 40.03 | 501.96 | 5476.80 | 0.00 | 332.05 | 3626.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-09:01 | 0.00 | 0.00 | 0.00 | -14327.43 | 0.00 | 0.00 | 13.31 | 25.34 | 317.77 | 10114.20 | 0.00 | 0.00 | 3888.92 | 0.00 | -0.00 | 0.00 | -32.10 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-13:11 | 0.00 | 0.00 | 0.00 | -16522.80 | 0.00 | 0.00 | 21.04 | 40.03 | 501.96 | 15528.36 | 0.00 | 0.00 | 505.53 | 0.00 | -0.00 | 0.00 | -74.12 | 0.00 |
PERIMETER_MID_ZN_4 | 10-SEP-16:41 | 0.00 | 0.00 | 0.00 | -15992.63 | 0.00 | 0.00 | 12.11 | 25.34 | 317.76 | 9858.16 | 0.00 | 18.22 | 5761.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-13:30 | 0.00 | -12635.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.20 | 12565.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 17-JUL-14:30 | 0.00 | -5608.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.99 | 5441.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 17-JUL-12:07 | 0.00 | -7103.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.49 | 7043.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 26-JUN-15:20 | 0.00 | -23253.16 | 0.00 | -152273.55 | 0.00 | 0.00 | 17713.90 | 23688.37 | 43769.98 | 63389.41 | 0.00 | 3199.66 | 23765.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 06-FEB-07:01 | 0.00 | 0.00 | 16769.22 | 0.00 | 0.00 | 0.00 | 886.91 | 1847.70 | 8945.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -28449.57 |
CORE_MID | 26-DEC-06:01 | 0.00 | 0.00 | 21687.92 | 0.00 | 0.00 | 0.00 | 500.42 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25979.08 |
CORE_TOP | 06-FEB-05:01 | 0.00 | 0.00 | 32266.20 | 0.00 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -36056.94 |
PERIMETER_TOP_ZN_3 | 24-DEC-01:52 | 0.00 | 0.00 | 11247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3826.71 | 0.00 | -1544.30 | -6442.88 |
PERIMETER_TOP_ZN_2 | 24-DEC-01:52 | 0.00 | 0.00 | 11960.78 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 317.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2627.03 | 0.00 | -1043.93 | -8648.69 |
PERIMETER_TOP_ZN_1 | 24-DEC-05:12 | 0.00 | 0.00 | 14930.04 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3673.45 | 0.00 | -1210.74 | -10612.74 |
PERIMETER_TOP_ZN_4 | 24-DEC-05:12 | 0.00 | 0.00 | 13672.43 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 317.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2368.34 | 0.00 | -816.13 | -10846.82 |
PERIMETER_BOT_ZN_3 | 06-FEB-05:11 | 0.00 | 0.00 | 7931.08 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2772.57 | 0.00 | -410.07 | -5547.55 |
PERIMETER_BOT_ZN_2 | 06-FEB-05:11 | 0.00 | 0.00 | 9092.48 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1841.31 | 0.00 | -276.60 | -7480.45 |
PERIMETER_BOT_ZN_1 | 22-DEC-07:10 | 0.00 | 0.00 | 14987.43 | 0.00 | 0.00 | 0.00 | 208.17 | 389.51 | 669.28 | 0.00 | 0.00 | 0.00 | 19137.18 | 0.00 | -4030.54 | 0.00 | -31361.05 | 0.00 |
PERIMETER_BOT_ZN_4 | 06-FEB-05:11 | 0.00 | 0.00 | 9501.53 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1883.05 | 0.00 | -276.97 | -7847.39 |
PERIMETER_MID_ZN_3 | 24-DEC-07:01 | 0.00 | 0.00 | 9107.04 | 0.00 | 0.00 | 0.00 | 59.26 | 64.92 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3737.66 | 0.00 | -1413.89 | -4581.65 |
PERIMETER_MID_ZN_2 | 24-DEC-07:01 | 0.00 | 0.00 | 10194.40 | 0.00 | 0.00 | 0.00 | 37.65 | 41.10 | 317.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2562.26 | 0.00 | -953.29 | -7075.36 |
PERIMETER_MID_ZN_1 | 24-DEC-07:01 | 0.00 | 0.00 | 12566.71 | 0.00 | 0.00 | 0.00 | 59.19 | 64.92 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3874.86 | 0.00 | -1426.80 | -7891.13 |
PERIMETER_MID_ZN_4 | 24-DEC-07:01 | 0.00 | 0.00 | 10170.81 | 0.00 | 0.00 | 0.00 | 37.59 | 41.10 | 317.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2490.31 | 0.00 | -954.52 | -7122.42 |
TOPFLOOR_PLENUM | 22-DEC-06:12 | 17835.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -367.46 | -17468.21 |
MIDFLOOR_PLENUM | 06-FEB-07:11 | 8690.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -305.48 | -8384.67 |
FIRSTFLOOR_PLENUM | 22-SEP-05:02 | 6366.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -197.67 | -6168.70 |
Total Facility | 06-FEB-07:01 | 24098.73 | 0.00 | 167619.87 | 0.00 | 0.00 | 0.00 | 4631.35 | 9359.67 | 21853.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -30646.37 | 0.00 | -33768.63 | -163147.89 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.6185 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.9318 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 6.2241 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.3372 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.8180 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.2640 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.3092 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4916 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 3.1120 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5557 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.4090 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.6434 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4390 | 3.4390 | 0.8150 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5139 | 2.5139 | 0.7944 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7348 | 2.7348 | 0.8259 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8655 | 0.8655 | 0.1740 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9376 | 0.9376 | 0.1875 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1673 | 1.1673 | 0.2335 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1128 | 1.1128 | 0.2226 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6567 | 0.6567 | 0.1720 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7621 | 0.7621 | 0.1524 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9069 | 0.9069 | 0.1814 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8538 | 0.8538 | 0.1708 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7429 | 0.7429 | 0.1679 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9191 | 0.9191 | 0.1838 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0382 | 1.0382 | 0.2076 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0100 | 1.0100 | 0.2020 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.6185 | 5.9318 | 6.6185 | 1.4916 | 0.0000 | 1.0000 |
PACU_VAV_MID | 6.2241 | 5.3372 | 6.2241 | 1.5557 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.8180 | 6.2640 | 6.8180 | 1.6434 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7195 | 1.7195 | 0.8150 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2569 | 1.2569 | 0.7944 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3674 | 1.3674 | 0.8259 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4327 | 0.4327 | 0.1740 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4688 | 0.4688 | 0.1875 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5837 | 0.5837 | 0.2335 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5564 | 0.5564 | 0.2226 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3283 | 0.3283 | 0.1720 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3811 | 0.3811 | 0.1524 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4535 | 0.4535 | 0.1814 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4269 | 0.4269 | 0.1708 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3715 | 0.3715 | 0.1679 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4595 | 0.4595 | 0.1838 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5191 | 0.5191 | 0.2076 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5050 | 0.5050 | 0.2020 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.3092 | 1.4916 | 1.4916 | 1.4916 | 0.0000 | 1.0000 |
PACU_VAV_MID | 3.1120 | 1.5557 | 1.5557 | 1.5557 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.4090 | 1.6434 | 1.6434 | 1.6434 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 350.33 |
Number of hours cooling loads not met | 190.50 |
Number of hours not met | 540.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 156.88 | 171881.05 | 133.30 | 104241.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 174.44 | 84403.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 280.84 | 28079.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 72.02 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 641.30 | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 12.98 | 926.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 120.87 | 34957.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 110.80 | 9796.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 762.04 | 1580.09 |
Natural Gas | 0.00 | 244.09 |
Additional | 0.00 | 0.00 |
Total | 762.04 | 1824.18 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 56.37 |
Space Heating | 31.49 |
Space Cooling | 35.01 |
Fans (All) | 24.26 |
Service Water Heating | 0.00 |
Receptacle Equipment | 152.95 |
Miscellaneous (All) | 317.15 |
Subtotal | 317.15 |
Natural Gas [MJ/m2] | |
Space Heating | 26.75 |
Service Water Heating | 22.24 |
Miscellaneous (All) | 48.99 |
Subtotal | 48.99 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.40 |
Space Heating | 15.91 |
Space Cooling | 9.56 |
Fans (All) | 6.63 |
Service Water Heating | 6.07 |
Receptacle Equipment | 41.77 |
Miscellaneous | 4.66 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2429. | 8760. |
BLDG_EQUIP_SCH | 4487. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8732.83 | 27.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8738.33 | 21.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8736.83 | 23.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8749.83 | 10.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8734.83 | 25.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8744.00 | 16.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8737.67 | 22.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8679.50 | 80.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8679.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 80.50 | 0.00 | 0.00 | 0.00 |
Average | 8745.95 | 14.05 | 0.00 | 0.00 | 0.00 |
Sum | 157427.17 | 252.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8704.17 | 55.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8729.83 | 30.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8750.17 | 9.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8748.67 | 11.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8729.50 | 30.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8739.83 | 20.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8742.67 | 17.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8744.17 | 15.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8755.67 | 4.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8754.00 | 6.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8749.17 | 10.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8731.00 | 29.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8741.83 | 18.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8738.67 | 21.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8739.17 | 20.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8756.17 | 3.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8704.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 55.83 | 0.00 | 0.00 | 0.00 |
Average | 8743.04 | 16.96 | 0.00 | 0.00 | 0.00 |
Sum | 157374.67 | 305.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128287.00 | 17.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128297.33 | 6.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128303.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128303.67 | 17.00 | 0.00 | 0.00 | 0.00 |
Average | 34142.00 | 1.33 | 0.00 | 0.00 | 0.00 |
Sum | 614556.00 | 24.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123427E+11 | 17838.09 | 23-JAN-08:04 | 5.00 | 0.23 | 0.195640E+10 | 2608.49 | 11-JAN-14:30 | 5.00 | 0.23 |
February | 0.110783E+11 | 18844.66 | 22-FEB-08:03 | 0.50 | 0.30 | 0.175994E+10 | 2608.53 | 14-FEB-14:20 | 0.50 | 0.30 |
March | 0.157331E+11 | 34485.57 | 16-MAR-05:03 | 7.83 | 0.85 | 0.213488E+10 | 2608.37 | 23-MAR-09:20 | 7.33 | 2.78 |
April | 0.140263E+11 | 22560.58 | 21-APR-05:03 | 5.83 | 3.87 | 0.190175E+10 | 2606.78 | 13-APR-13:00 | 5.83 | 3.87 |
May | 0.209644E+11 | 34956.41 | 19-MAY-05:03 | 5.17 | 3.18 | 0.207583E+10 | 2606.73 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.271206E+11 | 41611.56 | 26-JUN-04:03 | 13.85 | 9.53 | 0.207067E+10 | 2606.72 | 20-JUN-13:00 | 13.85 | 9.53 |
July | 0.264895E+11 | 43646.46 | 24-JUL-04:02 | 18.00 | 14.77 | 0.192466E+10 | 2606.67 | 14-JUL-09:39 | 18.00 | 14.77 |
August | 0.284879E+11 | 43631.75 | 28-AUG-04:02 | 14.17 | 14.06 | 0.216077E+10 | 2606.69 | 10-AUG-09:50 | 14.17 | 14.06 |
September | 0.249896E+11 | 42873.04 | 11-SEP-04:02 | 16.78 | 8.40 | 0.191830E+10 | 2606.89 | 05-SEP-09:09 | 16.78 | 8.40 |
October | 0.191468E+11 | 39974.92 | 06-OCT-05:02 | 6.00 | 3.09 | 0.198785E+10 | 2606.76 | 03-OCT-13:09 | 6.00 | 3.09 |
November | 0.146854E+11 | 28739.91 | 09-NOV-06:03 | 9.17 | 4.69 | 0.195953E+10 | 2606.63 | 29-NOV-10:39 | -9.0 | -9.0 |
December | 0.116559E+11 | 18551.96 | 05-DEC-08:02 | -0.8 | -3.2 | 0.186857E+10 | 2608.93 | 05-DEC-10:30 | 2.50 | -2.1 |
Annual Sum or Average | 0.226721E+12 | 0.237191E+11 | ||||||||
Minimum of Months | 0.110783E+11 | 17838.09 | -0.8 | -3.2 | 0.175994E+10 | 2606.63 | -9.0 | -9.0 | ||
Maximum of Months | 0.284879E+11 | 43646.46 | 18.00 | 14.77 | 0.216077E+10 | 2608.93 | 18.00 | 14.77 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.315850E+09 | 3244.11 | 20-JAN-14:30 | 20.50 | 6.87 | 0.00 | 0.00 | 01-JAN-00:10 | 20.50 | 6.87 |
February | 0.391887E+09 | 3313.61 | 18-FEB-13:50 | 20.00 | 7.73 | 0.00 | 0.00 | 01-FEB-00:10 | 20.00 | 7.73 |
March | 0.131360E+10 | 7197.28 | 14-MAR-14:10 | 23.00 | 7.59 | 0.00 | 0.00 | 01-MAR-00:10 | 23.00 | 7.59 |
April | 0.133391E+10 | 6290.70 | 21-APR-13:30 | 15.50 | 6.04 | 0.00 | 0.00 | 01-APR-00:10 | 15.50 | 6.04 |
May | 0.317247E+10 | 9193.79 | 31-MAY-14:30 | 28.00 | 14.75 | 0.00 | 0.00 | 01-MAY-00:10 | 28.00 | 14.75 |
June | 0.760825E+10 | 12636.91 | 26-JUN-13:30 | 37.15 | 15.33 | 0.00 | 0.00 | 01-JUN-00:10 | 37.15 | 15.33 |
July | 0.701049E+10 | 11185.24 | 17-JUL-14:00 | 35.00 | 14.93 | 0.00 | 0.00 | 01-JUL-00:10 | 35.00 | 14.93 |
August | 0.710688E+10 | 12626.69 | 16-AUG-15:10 | 36.17 | 16.19 | 0.00 | 0.00 | 01-AUG-00:10 | 36.17 | 16.19 |
September | 0.460033E+10 | 9531.90 | 12-SEP-14:30 | 29.40 | 13.78 | 0.00 | 0.00 | 01-SEP-00:10 | 29.40 | 13.78 |
October | 0.164704E+10 | 7368.39 | 11-OCT-15:00 | 26.00 | 9.46 | 0.00 | 0.00 | 01-OCT-00:10 | 26.00 | 9.46 |
November | 0.606538E+09 | 4127.68 | 09-NOV-13:10 | 20.00 | 8.90 | 0.00 | 0.00 | 01-NOV-00:10 | 20.00 | 8.90 |
December | 0.207971E+09 | 2237.28 | 01-DEC-14:40 | 21.33 | 7.55 | 0.00 | 0.00 | 01-DEC-00:10 | 21.33 | 7.55 |
Annual Sum or Average | 0.353152E+11 | 0.00 | ||||||||
Minimum of Months | 0.207971E+09 | 2237.28 | 15.50 | 6.04 | 0.00 | 0.00 | 15.50 | 6.04 | ||
Maximum of Months | 0.760825E+10 | 12636.91 | 37.15 | 16.19 | 0.00 | 0.00 | 37.15 | 16.19 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 97436841.54 | 2386.86 | 05-JAN-05:01 | -17.0 | -17.0 | 0.00 | 0.00 | 01-JAN-00:10 | -17.0 | -17.0 |
February | 77381730.25 | 1954.89 | 28-FEB-07:01 | -2.7 | -3.1 | 0.00 | 0.00 | 01-FEB-00:10 | -2.7 | -3.1 |
March | 0.375243E+09 | 2625.29 | 15-MAR-16:00 | 19.00 | 5.38 | 0.00 | 0.00 | 01-MAR-00:10 | 19.00 | 5.38 |
April | 0.311544E+09 | 2203.65 | 15-APR-05:01 | -5.0 | -5.1 | 0.00 | 0.00 | 01-APR-00:10 | -5.0 | -5.1 |
May | 0.122184E+10 | 2893.49 | 18-MAY-15:00 | 23.00 | 11.61 | 0.00 | 0.00 | 01-MAY-00:10 | 23.00 | 11.61 |
June | 0.395612E+10 | 5572.92 | 26-JUN-15:20 | 39.20 | 15.68 | 0.00 | 0.00 | 01-JUN-00:10 | 39.20 | 15.68 |
July | 0.392027E+10 | 5608.42 | 17-JUL-14:30 | 34.50 | 14.66 | 0.00 | 0.00 | 01-JUL-00:10 | 34.50 | 14.66 |
August | 0.386348E+10 | 5063.36 | 21-AUG-14:40 | 27.00 | 14.47 | 0.00 | 0.00 | 01-AUG-00:10 | 27.00 | 14.47 |
September | 0.255432E+10 | 4728.22 | 05-SEP-15:40 | 24.60 | 13.98 | 0.00 | 0.00 | 01-SEP-00:10 | 24.60 | 13.98 |
October | 0.558558E+09 | 3188.58 | 11-OCT-16:00 | 24.00 | 8.61 | 0.00 | 0.00 | 01-OCT-00:10 | 24.00 | 8.61 |
November | 0.163993E+09 | 1971.15 | 30-NOV-05:01 | -12.8 | -13.4 | 0.00 | 0.00 | 01-NOV-00:10 | -12.8 | -13.4 |
December | 43475011.39 | 2676.42 | 20-DEC-05:11 | -19.0 | -19.2 | 0.00 | 0.00 | 01-DEC-00:10 | -19.0 | -19.2 |
Annual Sum or Average | 0.171436E+11 | 0.00 | ||||||||
Minimum of Months | 43475011.39 | 1954.89 | -19.0 | -19.2 | 0.00 | 0.00 | -19.0 | -19.2 | ||
Maximum of Months | 0.395612E+10 | 5608.42 | 39.20 | 15.68 | 0.00 | 0.00 | 39.20 | 15.68 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.270237E+09 | 3029.34 | 27-JAN-07:01 | -1.7 | -1.7 | 0.00 | 0.00 | 01-JAN-00:10 | -1.7 | -1.7 |
February | 0.210358E+09 | 2647.42 | 28-FEB-07:01 | -2.7 | -3.1 | 0.00 | 0.00 | 01-FEB-00:10 | -2.7 | -3.1 |
March | 0.694769E+09 | 2932.98 | 15-MAR-15:40 | 19.33 | 5.50 | 0.00 | 0.00 | 01-MAR-00:10 | 19.33 | 5.50 |
April | 0.508766E+09 | 2178.24 | 14-APR-17:01 | 2.67 | 0.26 | 0.00 | 0.00 | 01-APR-00:10 | 2.67 | 0.26 |
May | 0.176857E+10 | 3124.57 | 18-MAY-15:10 | 22.33 | 11.65 | 0.00 | 0.00 | 01-MAY-00:10 | 22.33 | 11.65 |
June | 0.432646E+10 | 6886.07 | 26-JUN-12:07 | 36.18 | 15.20 | 0.00 | 0.00 | 01-JUN-00:10 | 36.18 | 15.20 |
July | 0.427247E+10 | 7103.80 | 17-JUL-12:07 | 36.00 | 14.76 | 0.00 | 0.00 | 01-JUL-00:10 | 36.00 | 14.76 |
August | 0.446979E+10 | 5261.70 | 21-AUG-15:10 | 24.83 | 15.09 | 0.00 | 0.00 | 01-AUG-00:10 | 24.83 | 15.09 |
September | 0.337977E+10 | 5084.64 | 05-SEP-16:00 | 24.40 | 14.03 | 0.00 | 0.00 | 01-SEP-00:10 | 24.40 | 14.03 |
October | 0.119698E+10 | 3910.04 | 11-OCT-16:20 | 23.33 | 8.54 | 0.00 | 0.00 | 01-OCT-00:10 | 23.33 | 8.54 |
November | 0.439308E+09 | 2341.35 | 29-NOV-17:10 | -11.3 | -11.3 | 0.00 | 0.00 | 01-NOV-00:10 | -11.3 | -11.3 |
December | 0.165682E+09 | 2808.04 | 21-DEC-17:10 | -22.0 | -22.1 | 0.00 | 0.00 | 01-DEC-00:10 | -22.0 | -22.1 |
Annual Sum or Average | 0.217032E+11 | 0.00 | ||||||||
Minimum of Months | 0.165682E+09 | 2178.24 | -22.0 | -22.1 | 0.00 | 0.00 | -22.0 | -22.1 | ||
Maximum of Months | 0.446979E+10 | 7103.80 | 36.18 | 15.20 | 0.00 | 0.00 | 36.18 | 15.20 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.755899E+10 | 9626.54 | 25-JAN-16:20 | 13.67 | 4.08 | 0.175223E+10 | 2606.53 | 26-JAN-14:09 | 9.00 | 2.97 |
February | 0.672046E+10 | 8964.06 | 27-FEB-17:00 | 13.00 | 4.60 | 0.157872E+10 | 2608.25 | 28-FEB-14:30 | 4.50 | 2.83 |
March | 0.969397E+10 | 14432.24 | 15-MAR-16:00 | 19.00 | 5.38 | 0.198206E+10 | 2606.64 | 17-MAR-09:09 | 6.83 | 6.35 |
April | 0.856262E+10 | 12818.06 | 21-APR-16:00 | 13.00 | 5.24 | 0.176868E+10 | 2606.72 | 13-APR-13:00 | 13.00 | 5.24 |
May | 0.133117E+11 | 19412.94 | 18-MAY-05:03 | 11.67 | 7.89 | 0.204415E+10 | 2606.67 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.193189E+11 | 31933.63 | 26-JUN-04:03 | 13.85 | 9.53 | 0.206738E+10 | 2606.67 | 08-JUN-13:09 | 13.85 | 9.53 |
July | 0.190496E+11 | 32477.03 | 24-JUL-04:02 | 18.00 | 14.77 | 0.192126E+10 | 2606.65 | 14-JUL-09:30 | 18.00 | 14.77 |
August | 0.197068E+11 | 32349.29 | 21-AUG-04:02 | 19.17 | 11.93 | 0.215767E+10 | 2606.65 | 10-AUG-09:39 | 19.17 | 11.93 |
September | 0.164546E+11 | 32261.31 | 11-SEP-04:02 | 16.78 | 8.40 | 0.191118E+10 | 2608.36 | 22-SEP-09:50 | 6.23 | 2.21 |
October | 0.108479E+11 | 22453.32 | 12-OCT-05:02 | -0.8 | -0.8 | 0.189598E+10 | 2608.26 | 12-OCT-09:39 | 3.33 | 1.07 |
November | 0.844510E+10 | 12291.89 | 08-NOV-16:40 | 14.67 | 6.46 | 0.180030E+10 | 2606.58 | 10-NOV-10:50 | 4.83 | 4.83 |
December | 0.689369E+10 | 7771.23 | 15-DEC-13:30 | 11.50 | 3.22 | 0.164445E+10 | 2596.62 | 05-DEC-14:00 | 11.50 | 3.22 |
Annual Sum or Average | 0.146564E+12 | 0.225240E+11 | ||||||||
Minimum of Months | 0.672046E+10 | 7771.23 | -0.8 | -0.8 | 0.157872E+10 | 2596.62 | 3.33 | 1.07 | ||
Maximum of Months | 0.197068E+11 | 32477.03 | 19.17 | 14.77 | 0.215767E+10 | 2608.36 | 19.17 | 14.77 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.605931E+10 | 8910.80 | 20-JAN-16:30 | 15.00 | 6.47 | 0.163646E+10 | 2605.62 | 25-JAN-14:00 | 14.00 | 4.48 |
February | 0.537297E+10 | 7945.81 | 27-FEB-16:20 | 13.00 | 4.42 | 0.149074E+10 | 2606.48 | 27-FEB-14:00 | 13.00 | 4.42 |
March | 0.857092E+10 | 15436.93 | 15-MAR-15:40 | 19.33 | 5.50 | 0.189360E+10 | 2606.60 | 17-MAR-09:00 | 6.00 | 6.00 |
April | 0.790374E+10 | 14280.51 | 21-APR-14:00 | 15.00 | 5.55 | 0.170114E+10 | 2606.72 | 13-APR-13:00 | 15.00 | 5.55 |
May | 0.128416E+11 | 16804.07 | 18-MAY-15:20 | 21.67 | 11.66 | 0.201136E+10 | 2606.65 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.199650E+11 | 28349.32 | 26-JUN-04:03 | 13.85 | 9.53 | 0.206460E+10 | 2606.68 | 08-JUN-13:09 | 13.85 | 9.53 |
July | 0.195538E+11 | 35089.14 | 17-JUL-04:02 | 19.00 | 9.40 | 0.191941E+10 | 2606.65 | 11-JUL-09:30 | 19.00 | 9.40 |
August | 0.198412E+11 | 34216.08 | 21-AUG-04:02 | 19.17 | 11.93 | 0.215392E+10 | 2606.66 | 10-AUG-09:50 | 19.17 | 11.93 |
September | 0.155495E+11 | 30759.97 | 11-SEP-05:03 | 17.88 | 8.62 | 0.189407E+10 | 2606.85 | 05-SEP-09:09 | 17.88 | 8.62 |
October | 0.907710E+10 | 16233.77 | 11-OCT-16:00 | 24.00 | 8.61 | 0.179672E+10 | 2606.62 | 03-OCT-13:30 | 24.00 | 8.61 |
November | 0.673937E+10 | 11393.82 | 08-NOV-16:10 | 17.17 | 7.51 | 0.167574E+10 | 2606.55 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.515334E+10 | 7207.47 | 03-DEC-14:02 | 18.00 | 6.62 | 0.153184E+10 | 2521.49 | 15-DEC-14:00 | 9.00 | 3.00 |
Annual Sum or Average | 0.136628E+12 | 0.217696E+11 | ||||||||
Minimum of Months | 0.515334E+10 | 7207.47 | 13.00 | 4.42 | 0.149074E+10 | 2521.49 | 6.00 | 3.00 | ||
Maximum of Months | 0.199650E+11 | 35089.14 | 24.00 | 11.93 | 0.215392E+10 | 2606.85 | 24.00 | 11.93 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472551E+09 | 1738.72 | 20-JAN-14:00 | 21.00 | 6.96 | 0.316750E+09 | 518.68 | 20-JAN-16:10 | 17.00 | 7.18 |
February | 0.414507E+09 | 1356.29 | 27-FEB-13:40 | 14.00 | 4.75 | 0.286425E+09 | 510.91 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.111212E+10 | 3611.99 | 14-MAR-14:40 | 23.00 | 7.59 | 0.370091E+09 | 549.48 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.123519E+10 | 3585.70 | 20-APR-13:30 | 21.50 | 8.83 | 0.338665E+09 | 549.51 | 13-APR-13:00 | 21.50 | 8.83 |
May | 0.299560E+10 | 5812.41 | 17-MAY-13:30 | 29.00 | 11.78 | 0.413982E+09 | 549.50 | 18-MAY-09:09 | 20.33 | 11.73 |
June | 0.618058E+10 | 11715.31 | 25-JUN-17:21 | 32.15 | 14.00 | 0.435143E+09 | 549.88 | 12-JUN-13:39 | 32.15 | 14.00 |
July | 0.601348E+10 | 11812.74 | 16-JUL-14:32 | 35.67 | 14.60 | 0.404685E+09 | 549.68 | 18-JUL-13:30 | 33.00 | 14.80 |
August | 0.551410E+10 | 6973.60 | 16-AUG-14:00 | 37.00 | 16.36 | 0.452402E+09 | 549.50 | 21-AUG-09:09 | 25.33 | 14.07 |
September | 0.374206E+10 | 6627.05 | 11-SEP-14:30 | 28.85 | 13.58 | 0.392064E+09 | 549.54 | 05-SEP-09:09 | 28.85 | 13.58 |
October | 0.137529E+10 | 4120.79 | 11-OCT-14:40 | 26.33 | 9.55 | 0.351547E+09 | 549.49 | 11-OCT-13:09 | 26.33 | 9.55 |
November | 0.673227E+09 | 2261.43 | 09-NOV-13:50 | 20.00 | 8.66 | 0.324502E+09 | 549.48 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.312954E+09 | 1354.05 | 03-DEC-14:02 | 18.00 | 6.62 | 0.299593E+09 | 493.36 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.300417E+11 | 0.438585E+10 | ||||||||
Minimum of Months | 0.312954E+09 | 1354.05 | 14.00 | 4.75 | 0.286425E+09 | 493.36 | 14.00 | 4.75 | ||
Maximum of Months | 0.618058E+10 | 11812.74 | 37.00 | 16.36 | 0.452402E+09 | 549.88 | 33.00 | 14.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.791918E+09 | 2273.34 | 20-JAN-10:10 | 14.67 | 5.12 | 0.209696E+09 | 347.86 | 24-JAN-10:09 | 11.50 | 3.54 |
February | 0.837902E+09 | 3095.03 | 27-FEB-09:30 | 9.50 | 2.73 | 0.195394E+09 | 348.21 | 23-FEB-10:30 | 9.50 | 2.73 |
March | 0.179841E+10 | 6222.24 | 15-MAR-09:10 | 14.17 | 4.19 | 0.251709E+09 | 347.88 | 27-MAR-09:00 | 0.00 | -0.5 |
April | 0.187203E+10 | 6721.26 | 21-APR-09:00 | 12.00 | 5.98 | 0.227294E+09 | 347.89 | 13-APR-13:00 | 12.00 | 5.98 |
May | 0.348702E+10 | 7582.63 | 16-MAY-08:50 | 22.50 | 11.55 | 0.267867E+09 | 347.90 | 17-MAY-09:09 | 25.33 | 11.72 |
June | 0.646037E+10 | 10167.35 | 11-JUN-09:12 | 20.73 | 10.95 | 0.275846E+09 | 348.98 | 29-JUN-09:09 | 28.58 | 13.43 |
July | 0.608461E+10 | 13991.73 | 09-JUL-09:12 | 25.33 | 12.97 | 0.256452E+09 | 348.64 | 18-JUL-09:00 | 31.00 | 14.50 |
August | 0.625325E+10 | 13180.04 | 06-AUG-09:12 | 25.67 | 15.47 | 0.287033E+09 | 348.61 | 31-AUG-09:00 | 27.00 | 13.51 |
September | 0.437491E+10 | 10535.02 | 04-SEP-09:22 | 25.25 | 13.40 | 0.251203E+09 | 347.92 | 08-SEP-09:30 | 25.25 | 11.81 |
October | 0.182926E+10 | 5341.19 | 11-OCT-09:40 | 22.07 | 8.25 | 0.233227E+09 | 347.88 | 03-OCT-13:09 | 22.07 | 8.25 |
November | 0.984972E+09 | 3149.73 | 07-NOV-09:30 | 14.00 | 4.09 | 0.214930E+09 | 347.87 | 07-NOV-10:00 | 16.00 | 5.55 |
December | 0.574452E+09 | 1638.82 | 03-DEC-14:02 | 18.00 | 6.62 | 0.194519E+09 | 318.59 | 01-DEC-10:09 | 18.00 | 6.62 |
Annual Sum or Average | 0.353491E+11 | 0.286517E+10 | ||||||||
Minimum of Months | 0.574452E+09 | 1638.82 | 9.50 | 2.73 | 0.194519E+09 | 318.59 | 0.00 | -0.5 | ||
Maximum of Months | 0.646037E+10 | 13991.73 | 25.67 | 15.47 | 0.287033E+09 | 348.98 | 31.00 | 14.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362312E+10 | 12943.39 | 20-JAN-13:30 | 21.00 | 6.97 | 0.374327E+09 | 550.00 | 20-JAN-14:09 | 20.83 | 6.93 |
February | 0.330644E+10 | 12152.00 | 26-FEB-13:13 | 17.67 | 4.65 | 0.339545E+09 | 550.15 | 23-FEB-10:30 | 17.67 | 4.65 |
March | 0.402587E+10 | 12899.07 | 15-MAR-13:20 | 20.33 | 5.93 | 0.403294E+09 | 551.04 | 15-MAR-13:30 | 20.50 | 6.02 |
April | 0.273765E+10 | 9182.46 | 21-APR-13:10 | 15.83 | 6.37 | 0.354464E+09 | 549.53 | 13-APR-13:00 | 15.83 | 6.37 |
May | 0.426962E+10 | 8342.34 | 16-MAY-13:10 | 27.17 | 12.14 | 0.413286E+09 | 549.51 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.719216E+10 | 15159.02 | 25-JUN-16:01 | 32.70 | 13.74 | 0.433270E+09 | 550.08 | 30-JUN-13:50 | 35.82 | 14.30 |
July | 0.723819E+10 | 16085.08 | 09-JUL-13:12 | 33.67 | 13.44 | 0.403634E+09 | 549.50 | 11-JUL-09:30 | 25.50 | 13.66 |
August | 0.839871E+10 | 15717.46 | 20-AUG-15:12 | 28.00 | 13.96 | 0.451900E+09 | 558.53 | 31-AUG-13:20 | 30.00 | 11.86 |
September | 0.751580E+10 | 17131.05 | 04-SEP-13:22 | 29.40 | 13.40 | 0.396267E+09 | 592.83 | 28-SEP-13:30 | 30.50 | 11.31 |
October | 0.524213E+10 | 18038.18 | 01-OCT-13:31 | 17.00 | 8.82 | 0.374645E+09 | 571.37 | 10-OCT-13:30 | 24.50 | 8.32 |
November | 0.399932E+10 | 18051.77 | 05-NOV-13:31 | 21.00 | 6.43 | 0.373643E+09 | 553.86 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.281934E+10 | 16170.60 | 17-DEC-13:32 | 18.00 | 5.77 | 0.349497E+09 | 549.57 | 14-DEC-14:39 | 18.00 | 5.77 |
Annual Sum or Average | 0.603683E+11 | 0.466777E+10 | ||||||||
Minimum of Months | 0.273765E+10 | 8342.34 | 15.83 | 4.65 | 0.339545E+09 | 549.50 | 12.83 | 4.65 | ||
Maximum of Months | 0.839871E+10 | 18051.77 | 33.67 | 13.96 | 0.451900E+09 | 592.83 | 35.82 | 14.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.914783E+09 | 4665.83 | 20-JAN-16:00 | 18.00 | 7.49 | 0.209276E+09 | 347.83 | 23-JAN-14:00 | 19.00 | 5.82 |
February | 0.923887E+09 | 5004.34 | 17-FEB-16:30 | 13.50 | 6.66 | 0.190638E+09 | 347.84 | 17-FEB-14:00 | 13.50 | 6.66 |
March | 0.191857E+10 | 9958.39 | 12-MAR-17:12 | 17.33 | 5.43 | 0.234548E+09 | 347.84 | 08-MAR-14:00 | 17.33 | 5.43 |
April | 0.182224E+10 | 9131.63 | 08-APR-17:42 | 14.33 | 4.60 | 0.211420E+09 | 347.85 | 19-APR-13:00 | 22.00 | 9.00 |
May | 0.340383E+10 | 8952.21 | 31-MAY-16:00 | 28.00 | 14.86 | 0.254099E+09 | 347.85 | 04-MAY-13:00 | 28.00 | 14.86 |
June | 0.607346E+10 | 16456.68 | 11-JUN-16:31 | 28.17 | 12.60 | 0.272609E+09 | 347.86 | 20-JUN-13:00 | 23.30 | 16.53 |
July | 0.542944E+10 | 16301.01 | 02-JUL-17:01 | 28.00 | 12.40 | 0.253711E+09 | 347.86 | 11-JUL-09:30 | 25.50 | 13.66 |
August | 0.556444E+10 | 15800.59 | 13-AUG-16:42 | 22.17 | 9.87 | 0.282882E+09 | 347.86 | 21-AUG-09:09 | 25.33 | 14.07 |
September | 0.413165E+10 | 16020.11 | 10-SEP-16:52 | 30.50 | 12.19 | 0.242931E+09 | 347.86 | 01-SEP-13:00 | 30.50 | 12.19 |
October | 0.220320E+10 | 10825.64 | 09-OCT-16:12 | 21.67 | 8.64 | 0.219982E+09 | 347.84 | 11-OCT-13:09 | 26.17 | 9.50 |
November | 0.115510E+10 | 5705.93 | 07-NOV-15:30 | 21.50 | 7.27 | 0.210856E+09 | 347.84 | 06-NOV-14:00 | 21.50 | 7.27 |
December | 0.623817E+09 | 3489.52 | 01-DEC-15:30 | 19.50 | 7.14 | 0.196634E+09 | 347.83 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.341644E+11 | 0.277959E+10 | ||||||||
Minimum of Months | 0.623817E+09 | 3489.52 | 13.50 | 4.60 | 0.190638E+09 | 347.83 | 13.50 | 5.43 | ||
Maximum of Months | 0.607346E+10 | 16456.68 | 30.50 | 14.86 | 0.282882E+09 | 347.86 | 30.50 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.496578E+09 | 1435.83 | 20-JAN-14:10 | 20.83 | 6.93 | 0.315175E+09 | 474.51 | 25-JAN-14:00 | 14.00 | 4.48 |
February | 0.369063E+09 | 1516.86 | 27-FEB-13:05 | 14.00 | 4.75 | 0.283692E+09 | 474.34 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.910025E+09 | 1768.82 | 14-MAR-13:10 | 23.83 | 7.85 | 0.359908E+09 | 549.47 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.105952E+10 | 1432.48 | 20-APR-13:40 | 21.33 | 8.72 | 0.329681E+09 | 548.79 | 20-APR-13:50 | 21.17 | 8.62 |
May | 0.219565E+10 | 3873.41 | 17-MAY-13:30 | 29.00 | 11.78 | 0.412633E+09 | 549.49 | 18-MAY-09:09 | 20.33 | 11.73 |
June | 0.478216E+10 | 5943.53 | 26-JUN-12:09 | 36.18 | 15.20 | 0.434800E+09 | 549.51 | 20-JUN-13:00 | 36.18 | 15.20 |
July | 0.478598E+10 | 7130.61 | 17-JUL-06:03 | 22.50 | 11.12 | 0.404292E+09 | 550.15 | 25-JUL-13:30 | 28.00 | 16.23 |
August | 0.474097E+10 | 5524.14 | 18-AUG-14:00 | 35.00 | 13.50 | 0.453352E+09 | 549.50 | 10-AUG-09:50 | 35.00 | 13.50 |
September | 0.377040E+10 | 5953.32 | 11-SEP-14:30 | 28.85 | 13.58 | 0.398794E+09 | 549.54 | 05-SEP-09:09 | 28.85 | 13.58 |
October | 0.169708E+10 | 3366.89 | 11-OCT-14:40 | 26.33 | 9.55 | 0.369557E+09 | 549.48 | 11-OCT-13:09 | 26.33 | 9.55 |
November | 0.970131E+09 | 1963.30 | 09-NOV-13:40 | 20.00 | 8.72 | 0.332995E+09 | 549.48 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.486001E+09 | 1464.33 | 03-DEC-15:13 | 17.33 | 6.52 | 0.302766E+09 | 491.81 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.262636E+11 | 0.439765E+10 | ||||||||
Minimum of Months | 0.369063E+09 | 1432.48 | 14.00 | 4.75 | 0.283692E+09 | 474.34 | 14.00 | 4.48 | ||
Maximum of Months | 0.478598E+10 | 7130.61 | 36.18 | 15.20 | 0.453352E+09 | 550.15 | 36.18 | 16.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.778231E+09 | 1522.92 | 20-JAN-10:10 | 14.67 | 5.12 | 0.213002E+09 | 347.86 | 24-JAN-10:09 | 11.50 | 3.54 |
February | 0.748868E+09 | 2488.08 | 27-FEB-08:45 | 8.33 | 2.39 | 0.196974E+09 | 347.87 | 23-FEB-10:09 | 8.33 | 2.39 |
March | 0.143301E+10 | 4293.91 | 15-MAR-09:10 | 14.17 | 4.19 | 0.253384E+09 | 347.87 | 27-MAR-09:00 | 0.00 | -0.5 |
April | 0.152094E+10 | 4550.61 | 21-APR-09:10 | 12.00 | 5.90 | 0.228887E+09 | 347.89 | 13-APR-13:00 | 12.00 | 5.90 |
May | 0.267998E+10 | 5325.70 | 16-MAY-09:00 | 23.00 | 11.65 | 0.269722E+09 | 347.89 | 31-MAY-09:00 | 25.00 | 13.24 |
June | 0.547887E+10 | 8263.82 | 08-JUN-06:02 | 14.77 | 8.93 | 0.276150E+09 | 348.76 | 29-JUN-09:09 | 28.58 | 13.43 |
July | 0.518600E+10 | 10927.14 | 09-JUL-09:12 | 25.33 | 12.97 | 0.256902E+09 | 348.28 | 18-JUL-09:00 | 31.00 | 14.50 |
August | 0.575512E+10 | 11397.08 | 06-AUG-09:41 | 26.67 | 15.50 | 0.287975E+09 | 348.26 | 31-AUG-09:50 | 26.67 | 13.56 |
September | 0.445978E+10 | 10949.52 | 04-SEP-09:52 | 26.10 | 13.35 | 0.254671E+09 | 348.38 | 08-SEP-09:50 | 25.82 | 12.10 |
October | 0.208642E+10 | 4963.12 | 10-OCT-09:30 | 19.50 | 8.06 | 0.243545E+09 | 347.88 | 03-OCT-13:09 | 19.50 | 8.06 |
November | 0.119762E+10 | 3031.36 | 07-NOV-09:20 | 14.00 | 4.09 | 0.225685E+09 | 347.87 | 07-NOV-10:00 | 16.00 | 5.55 |
December | 0.673217E+09 | 1478.61 | 03-DEC-12:32 | 16.80 | 6.08 | 0.201729E+09 | 331.14 | 15-DEC-10:09 | 5.50 | 0.27 |
Annual Sum or Average | 0.319980E+11 | 0.290863E+10 | ||||||||
Minimum of Months | 0.673217E+09 | 1478.61 | 8.33 | 2.39 | 0.196974E+09 | 331.14 | 0.00 | -0.5 | ||
Maximum of Months | 0.575512E+10 | 11397.08 | 26.67 | 15.50 | 0.287975E+09 | 348.76 | 31.00 | 14.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185158E+10 | 9057.32 | 20-JAN-14:00 | 21.00 | 6.96 | 0.348363E+09 | 549.83 | 11-JAN-14:30 | 21.00 | 6.96 |
February | 0.138349E+10 | 11967.05 | 26-FEB-12:52 | 18.00 | 4.84 | 0.307247E+09 | 549.81 | 14-FEB-14:20 | 18.00 | 4.84 |
March | 0.199922E+10 | 9616.48 | 14-MAR-13:10 | 23.83 | 7.85 | 0.376378E+09 | 549.88 | 14-MAR-13:00 | 23.00 | 7.59 |
April | 0.128039E+10 | 5468.22 | 12-APR-12:08 | 19.33 | 7.40 | 0.329551E+09 | 549.51 | 13-APR-13:39 | 16.00 | 9.74 |
May | 0.235579E+10 | 7679.14 | 16-MAY-12:00 | 27.00 | 11.84 | 0.394693E+09 | 549.51 | 17-MAY-13:00 | 29.00 | 11.64 |
June | 0.625993E+10 | 12530.52 | 26-JUN-16:20 | 38.43 | 15.58 | 0.432326E+09 | 666.66 | 26-JUN-12:09 | 38.43 | 15.58 |
July | 0.629733E+10 | 12319.71 | 17-JUL-12:00 | 36.00 | 14.76 | 0.402721E+09 | 667.08 | 17-JUL-12:09 | 36.00 | 14.76 |
August | 0.785119E+10 | 12854.97 | 20-AUG-11:42 | 28.17 | 14.59 | 0.453024E+09 | 671.15 | 16-AUG-12:09 | 28.17 | 14.59 |
September | 0.732877E+10 | 13862.40 | 04-SEP-12:31 | 29.03 | 13.49 | 0.398530E+09 | 632.40 | 28-SEP-12:09 | 30.08 | 11.35 |
October | 0.416364E+10 | 14324.51 | 09-OCT-13:21 | 22.00 | 8.88 | 0.370680E+09 | 604.48 | 10-OCT-13:50 | 24.83 | 8.58 |
November | 0.268428E+10 | 12770.26 | 05-NOV-13:42 | 21.00 | 6.39 | 0.355233E+09 | 572.59 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.167598E+10 | 12890.53 | 17-DEC-14:02 | 17.92 | 5.75 | 0.322355E+09 | 549.51 | 11-DEC-14:09 | 17.92 | 5.75 |
Annual Sum or Average | 0.451316E+11 | 0.449110E+10 | ||||||||
Minimum of Months | 0.128039E+10 | 5468.22 | 17.92 | 4.84 | 0.307247E+09 | 549.51 | 16.00 | 4.84 | ||
Maximum of Months | 0.785119E+10 | 14324.51 | 38.43 | 15.58 | 0.453024E+09 | 671.15 | 38.43 | 15.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.841056E+09 | 3310.21 | 23-JAN-16:10 | 18.17 | 6.14 | 0.210693E+09 | 347.81 | 25-JAN-14:00 | 14.00 | 4.48 |
February | 0.765045E+09 | 3570.91 | 17-FEB-16:30 | 13.50 | 6.66 | 0.190795E+09 | 347.83 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.141047E+10 | 5698.73 | 12-MAR-17:12 | 17.33 | 5.43 | 0.237225E+09 | 347.84 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.139967E+10 | 6131.74 | 08-APR-17:42 | 14.33 | 4.60 | 0.213702E+09 | 347.84 | 19-APR-13:00 | 22.00 | 9.00 |
May | 0.245879E+10 | 5856.52 | 31-MAY-16:00 | 28.00 | 14.86 | 0.259457E+09 | 347.85 | 10-MAY-13:50 | 28.00 | 14.86 |
June | 0.493464E+10 | 12322.59 | 25-JUN-16:41 | 32.70 | 13.95 | 0.275034E+09 | 347.86 | 20-JUN-13:00 | 32.70 | 13.95 |
July | 0.439428E+10 | 12490.59 | 02-JUL-17:31 | 28.00 | 12.39 | 0.255607E+09 | 347.85 | 11-JUL-09:30 | 25.50 | 13.66 |
August | 0.489458E+10 | 13021.03 | 13-AUG-17:11 | 22.33 | 10.08 | 0.287015E+09 | 347.86 | 15-AUG-13:39 | 25.33 | 13.66 |
September | 0.401071E+10 | 13450.44 | 10-SEP-16:41 | 30.78 | 12.29 | 0.252732E+09 | 347.88 | 05-SEP-09:09 | 30.78 | 12.29 |
October | 0.229270E+10 | 11927.03 | 09-OCT-15:22 | 22.00 | 8.88 | 0.236089E+09 | 347.84 | 04-OCT-13:00 | 22.00 | 8.88 |
November | 0.131220E+10 | 4983.03 | 07-NOV-15:40 | 21.33 | 7.24 | 0.219787E+09 | 347.84 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.718642E+09 | 2714.80 | 04-DEC-15:30 | 18.00 | 5.80 | 0.200296E+09 | 347.83 | 04-DEC-14:00 | 18.00 | 5.80 |
Annual Sum or Average | 0.294328E+11 | 0.283843E+10 | ||||||||
Minimum of Months | 0.718642E+09 | 2714.80 | 13.50 | 4.60 | 0.190795E+09 | 347.81 | 14.00 | 4.48 | ||
Maximum of Months | 0.493464E+10 | 13450.44 | 32.70 | 14.86 | 0.287015E+09 | 347.88 | 32.70 | 14.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.745657E+09 | 1717.60 | 20-JAN-14:50 | 20.17 | 6.81 | 0.324036E+09 | 519.25 | 20-JAN-16:30 | 15.00 | 6.47 |
February | 0.627253E+09 | 1557.74 | 27-FEB-13:10 | 14.00 | 4.75 | 0.292524E+09 | 517.21 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.131888E+10 | 3456.45 | 14-MAR-15:00 | 23.00 | 7.59 | 0.380428E+09 | 549.48 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.141851E+10 | 3224.68 | 20-APR-13:30 | 21.50 | 8.83 | 0.348732E+09 | 549.51 | 13-APR-13:00 | 21.50 | 8.83 |
May | 0.308773E+10 | 5433.51 | 17-MAY-13:30 | 29.00 | 11.78 | 0.423015E+09 | 549.50 | 18-MAY-09:09 | 20.33 | 11.73 |
June | 0.592946E+10 | 9124.21 | 25-JUN-17:42 | 31.78 | 13.99 | 0.435907E+09 | 550.07 | 12-JUN-13:30 | 31.78 | 13.99 |
July | 0.579095E+10 | 10003.87 | 16-JUL-14:22 | 35.50 | 14.51 | 0.405291E+09 | 549.83 | 24-JUL-13:50 | 32.00 | 16.85 |
August | 0.539282E+10 | 6515.43 | 20-AUG-15:41 | 28.00 | 14.08 | 0.454031E+09 | 549.96 | 18-AUG-13:50 | 28.00 | 14.08 |
September | 0.386638E+10 | 7104.19 | 10-SEP-16:01 | 31.92 | 12.68 | 0.398072E+09 | 549.54 | 05-SEP-09:09 | 31.92 | 12.68 |
October | 0.167099E+10 | 3951.64 | 11-OCT-14:40 | 26.33 | 9.55 | 0.367899E+09 | 549.49 | 10-OCT-13:00 | 26.33 | 9.55 |
November | 0.978235E+09 | 2484.46 | 09-NOV-13:40 | 20.00 | 8.72 | 0.334716E+09 | 549.48 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.531705E+09 | 1448.73 | 14-DEC-13:30 | 16.15 | 4.27 | 0.304896E+09 | 513.28 | 04-DEC-14:00 | 16.15 | 4.27 |
Annual Sum or Average | 0.313586E+11 | 0.446954E+10 | ||||||||
Minimum of Months | 0.531705E+09 | 1448.73 | 14.00 | 4.27 | 0.292524E+09 | 513.28 | 14.00 | 4.27 | ||
Maximum of Months | 0.592946E+10 | 10003.87 | 35.50 | 14.51 | 0.454031E+09 | 550.07 | 32.00 | 16.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102258E+10 | 2970.08 | 20-JAN-09:40 | 12.67 | 4.18 | 0.157718E+09 | 338.71 | 20-JAN-11:09 | 18.33 | 6.81 |
February | 0.105285E+10 | 4166.55 | 27-FEB-09:10 | 9.17 | 2.67 | 0.146512E+09 | 338.72 | 27-FEB-08:20 | 9.17 | 2.67 |
March | 0.200695E+10 | 6690.05 | 15-MAR-08:50 | 13.17 | 3.86 | 0.186986E+09 | 338.73 | 27-MAR-10:09 | 0.33 | -0.4 |
April | 0.202849E+10 | 7014.51 | 21-APR-08:40 | 11.67 | 5.95 | 0.169504E+09 | 338.74 | 13-APR-14:09 | 11.67 | 5.95 |
May | 0.353347E+10 | 7704.87 | 16-MAY-08:30 | 21.50 | 11.33 | 0.199327E+09 | 338.95 | 16-MAY-08:50 | 22.50 | 11.55 |
June | 0.615997E+10 | 13500.54 | 11-JUN-09:02 | 20.37 | 10.85 | 0.203885E+09 | 340.49 | 26-JUN-10:30 | 32.15 | 15.77 |
July | 0.579530E+10 | 14077.34 | 16-JUL-08:21 | 31.50 | 14.54 | 0.190270E+09 | 343.49 | 17-JUL-07:19 | 26.00 | 12.45 |
August | 0.604264E+10 | 14328.74 | 06-AUG-09:01 | 25.33 | 15.45 | 0.212197E+09 | 340.56 | 07-AUG-10:30 | 29.00 | 14.95 |
September | 0.441628E+10 | 13543.47 | 04-SEP-09:12 | 24.97 | 13.41 | 0.186618E+09 | 339.16 | 18-SEP-08:00 | 22.70 | 10.68 |
October | 0.214944E+10 | 6603.10 | 09-OCT-09:53 | 15.00 | 8.94 | 0.174672E+09 | 338.93 | 26-OCT-08:00 | 8.00 | 3.61 |
November | 0.126530E+10 | 4124.41 | 07-NOV-09:10 | 14.00 | 4.09 | 0.161859E+09 | 338.72 | 07-NOV-11:09 | 16.67 | 5.90 |
December | 0.739437E+09 | 1680.13 | 17-DEC-11:53 | 16.00 | 5.22 | 0.146464E+09 | 336.31 | 15-DEC-09:50 | 16.00 | 5.22 |
Annual Sum or Average | 0.362127E+11 | 0.213601E+10 | ||||||||
Minimum of Months | 0.739437E+09 | 1680.13 | 9.17 | 2.67 | 0.146464E+09 | 336.31 | 0.33 | -0.4 | ||
Maximum of Months | 0.615997E+10 | 14328.74 | 31.50 | 15.45 | 0.212197E+09 | 343.49 | 32.15 | 15.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.412653E+10 | 14458.10 | 22-JAN-12:13 | 6.33 | 3.28 | 0.383441E+09 | 568.92 | 20-JAN-14:09 | 6.33 | 3.28 |
February | 0.370044E+10 | 15208.96 | 26-FEB-12:22 | 17.50 | 4.65 | 0.347558E+09 | 549.96 | 28-FEB-14:30 | 4.50 | 2.83 |
March | 0.426703E+10 | 12579.78 | 12-MAR-12:32 | 18.67 | 6.04 | 0.412634E+09 | 566.28 | 15-MAR-13:30 | 20.50 | 6.02 |
April | 0.290952E+10 | 8665.77 | 21-APR-13:10 | 15.83 | 6.37 | 0.364462E+09 | 549.76 | 21-APR-13:30 | 15.50 | 6.04 |
May | 0.426089E+10 | 7723.74 | 16-MAY-13:10 | 27.17 | 12.14 | 0.423392E+09 | 549.51 | 10-MAY-13:39 | 27.17 | 12.14 |
June | 0.680273E+10 | 14189.76 | 25-JUN-13:02 | 32.70 | 13.05 | 0.435179E+09 | 550.37 | 30-JUN-13:50 | 35.82 | 14.30 |
July | 0.686203E+10 | 13841.56 | 16-JUL-14:22 | 35.50 | 14.51 | 0.405045E+09 | 549.79 | 31-JUL-13:30 | 26.50 | 17.46 |
August | 0.810260E+10 | 14988.33 | 27-AUG-13:12 | 26.00 | 15.04 | 0.454366E+09 | 567.91 | 31-AUG-13:09 | 30.00 | 11.91 |
September | 0.754166E+10 | 16263.66 | 10-SEP-12:41 | 32.25 | 13.24 | 0.401333E+09 | 608.98 | 28-SEP-13:20 | 30.50 | 11.31 |
October | 0.566165E+10 | 16519.09 | 09-OCT-13:11 | 22.00 | 8.98 | 0.385935E+09 | 593.71 | 10-OCT-13:09 | 24.17 | 8.07 |
November | 0.455637E+10 | 14912.28 | 05-NOV-13:02 | 21.00 | 6.54 | 0.383882E+09 | 577.83 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.322085E+10 | 14503.40 | 17-DEC-11:53 | 16.00 | 5.22 | 0.360036E+09 | 549.59 | 15-DEC-14:39 | 16.00 | 5.22 |
Annual Sum or Average | 0.620123E+11 | 0.475726E+10 | ||||||||
Minimum of Months | 0.290952E+10 | 7723.74 | 6.33 | 3.28 | 0.347558E+09 | 549.51 | 4.50 | 2.83 | ||
Maximum of Months | 0.810260E+10 | 16519.09 | 35.50 | 15.04 | 0.454366E+09 | 608.98 | 35.82 | 17.46 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115218E+10 | 4507.08 | 20-JAN-16:00 | 18.00 | 7.49 | 0.213446E+09 | 347.83 | 23-JAN-14:00 | 19.00 | 5.82 |
February | 0.111481E+10 | 4910.77 | 17-FEB-16:30 | 13.50 | 6.66 | 0.193906E+09 | 347.84 | 17-FEB-14:00 | 13.50 | 6.66 |
March | 0.206731E+10 | 9635.51 | 12-MAR-17:12 | 17.33 | 5.43 | 0.240190E+09 | 347.84 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.195760E+10 | 8782.24 | 08-APR-17:42 | 14.33 | 4.60 | 0.216968E+09 | 347.85 | 13-APR-13:30 | 16.50 | 9.66 |
May | 0.336796E+10 | 8368.65 | 31-MAY-16:00 | 28.00 | 14.86 | 0.261755E+09 | 347.86 | 10-MAY-13:39 | 28.00 | 14.86 |
June | 0.575187E+10 | 15779.05 | 11-JUN-17:41 | 27.30 | 12.44 | 0.274620E+09 | 347.86 | 20-JUN-13:00 | 23.30 | 16.53 |
July | 0.514827E+10 | 14727.98 | 02-JUL-17:21 | 28.00 | 12.39 | 0.255450E+09 | 347.86 | 11-JUL-09:30 | 25.50 | 13.66 |
August | 0.534756E+10 | 15713.62 | 13-AUG-17:11 | 22.33 | 10.08 | 0.285978E+09 | 347.86 | 15-AUG-13:39 | 25.33 | 13.66 |
September | 0.410967E+10 | 15992.71 | 10-SEP-16:41 | 30.78 | 12.29 | 0.248930E+09 | 347.88 | 05-SEP-09:09 | 30.78 | 12.29 |
October | 0.245945E+10 | 14495.77 | 09-OCT-16:32 | 21.33 | 8.70 | 0.228174E+09 | 347.86 | 10-OCT-13:00 | 25.00 | 8.71 |
November | 0.143179E+10 | 5661.88 | 07-NOV-15:30 | 21.50 | 7.27 | 0.216125E+09 | 347.84 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.806594E+09 | 3372.94 | 01-DEC-15:30 | 19.50 | 7.14 | 0.199930E+09 | 347.84 | 15-DEC-14:00 | 9.00 | 3.00 |
Annual Sum or Average | 0.347150E+11 | 0.283547E+10 | ||||||||
Minimum of Months | 0.806594E+09 | 3372.94 | 13.50 | 4.60 | 0.193906E+09 | 347.83 | 9.00 | 3.00 | ||
Maximum of Months | 0.575187E+10 | 15992.71 | 30.78 | 14.86 | 0.285978E+09 | 347.88 | 30.78 | 16.53 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 1006157.80 | 16769.30 | 06-FEB-07:01 | -9.7 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 3219081.71 | 14298.84 | 26-DEC-07:02 | 6.83 |
Annual Sum or Average | 4225239.51 | |||
Minimum of Months | 0.00 | 0.00 | -9.7 | |
Maximum of Months | 3219081.71 | 16769.30 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363180E+10 | 14409.11 | 05-JAN-06:13 | -17.0 |
February | 0.371285E+10 | 15333.71 | 13-FEB-06:13 | -10.7 |
March | 0.269890E+10 | 11342.60 | 20-MAR-05:13 | 0.00 |
April | 0.178844E+10 | 14132.92 | 17-APR-05:13 | -8.0 |
May | 0.506808E+09 | 6471.43 | 02-MAY-06:01 | 0.17 |
June | 0.121680E+09 | 6209.21 | 26-JUN-04:03 | 13.85 |
July | 89494192.73 | 5961.77 | 03-JUL-05:03 | 11.00 |
August | 0.122645E+09 | 6445.80 | 07-AUG-05:03 | 16.17 |
September | 0.368630E+09 | 6184.50 | 11-SEP-04:02 | 16.78 |
October | 0.215095E+10 | 13542.53 | 30-OCT-05:13 | -10.0 |
November | 0.272883E+10 | 14528.87 | 30-NOV-06:13 | -12.0 |
December | 0.538358E+10 | 17835.66 | 22-DEC-06:12 | -20.7 |
Annual Sum or Average | 0.233046E+11 | |||
Minimum of Months | 89494192.73 | 5961.77 | -20.7 | |
Maximum of Months | 0.538358E+10 | 17835.66 | 16.78 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176954E+10 | 5660.43 | 22-JAN-12:13 | 6.33 |
February | 0.187664E+10 | 8690.17 | 06-FEB-07:11 | -9.3 |
March | 0.124195E+10 | 6629.25 | 20-MAR-06:11 | 0.00 |
April | 0.100195E+10 | 5389.00 | 17-APR-06:02 | -7.7 |
May | 0.203242E+09 | 2720.34 | 28-MAY-13:08 | 19.17 |
June | 26561959.61 | 3106.65 | 11-JUN-15:01 | 28.82 |
July | 32464748.34 | 2977.20 | 16-JUL-14:22 | 35.50 |
August | 27880649.00 | 3584.49 | 06-AUG-11:02 | 30.33 |
September | 69058143.65 | 4612.23 | 17-SEP-15:12 | 26.60 |
October | 0.800140E+09 | 5824.50 | 09-OCT-15:12 | 22.00 |
November | 0.144479E+10 | 6006.01 | 05-NOV-11:42 | 19.67 |
December | 0.233303E+10 | 7853.22 | 26-DEC-07:12 | 6.67 |
Annual Sum or Average | 0.108273E+11 | |||
Minimum of Months | 26561959.61 | 2720.34 | -9.3 | |
Maximum of Months | 0.233303E+10 | 8690.17 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106131E+10 | 3779.56 | 30-JAN-08:07 | -2.0 |
February | 0.112633E+10 | 4383.63 | 06-FEB-08:50 | -5.5 |
March | 0.801085E+09 | 4693.83 | 17-MAR-05:03 | 6.83 |
April | 0.620602E+09 | 4371.69 | 24-APR-07:09 | 1.00 |
May | 0.122337E+09 | 5115.75 | 09-MAY-05:03 | 3.33 |
June | 27325202.26 | 4107.95 | 03-JUN-05:03 | 15.18 |
July | 29345661.92 | 3825.59 | 29-JUL-05:03 | 16.17 |
August | 32534567.45 | 4103.56 | 22-AUG-04:03 | 14.92 |
September | 46657273.42 | 6365.92 | 22-SEP-05:02 | -1.7 |
October | 0.460180E+09 | 6273.05 | 16-OCT-05:02 | 1.00 |
November | 0.791315E+09 | 5390.82 | 10-NOV-06:03 | 5.67 |
December | 0.149464E+10 | 4806.79 | 26-DEC-07:02 | 6.83 |
Annual Sum or Average | 0.661366E+10 | |||
Minimum of Months | 27325202.26 | 3779.56 | -5.5 | |
Maximum of Months | 0.149464E+10 | 6365.92 | 16.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66090040.84 | 20213.65 | 02-JAN-06:01 | -2.8 |
February | 0.217094E+09 | 21525.92 | 06-FEB-06:01 | -10.0 |
March | 69616372.57 | 20826.85 | 20-MAR-05:01 | 0.00 |
April | 44856774.11 | 19863.15 | 17-APR-05:01 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 14597982.23 | 19219.13 | 31-OCT-06:01 | -9.0 |
November | 16329521.39 | 19208.52 | 01-NOV-06:01 | -2.8 |
December | 0.240702E+09 | 21687.81 | 26-DEC-06:01 | 7.00 |
Annual Sum or Average | 0.669286E+09 | |||
Minimum of Months | 0.00 | 0.00 | -10.0 | |
Maximum of Months | 0.240702E+09 | 21687.81 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.948076E+09 | 30298.02 | 02-JAN-05:01 | -2.2 |
February | 0.127702E+10 | 32266.28 | 06-FEB-05:01 | -10.0 |
March | 0.555647E+09 | 31170.36 | 20-MAR-04:01 | 0.83 |
April | 0.518657E+09 | 30715.54 | 17-APR-04:11 | -8.0 |
May | 27269189.88 | 27486.53 | 01-MAY-05:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.406404E+09 | 30180.78 | 30-OCT-04:01 | -10.0 |
November | 0.549013E+09 | 29116.00 | 30-NOV-06:01 | -12.0 |
December | 0.179747E+10 | 32063.98 | 26-DEC-05:11 | 4.33 |
Annual Sum or Average | 0.607955E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.0 | |
Maximum of Months | 0.179747E+10 | 32266.28 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252915E+10 | 10442.08 | 06-JAN-05:11 | -7.7 |
February | 0.284722E+10 | 10993.91 | 12-FEB-06:52 | -20.0 |
March | 0.162559E+10 | 11199.80 | 19-MAR-07:32 | -13.8 |
April | 0.936441E+09 | 10603.86 | 17-APR-04:11 | -8.0 |
May | 70478009.05 | 9238.83 | 01-MAY-05:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 20176494.42 | 8719.00 | 22-SEP-05:02 | -1.7 |
October | 0.110757E+10 | 10532.53 | 30-OCT-04:01 | -10.0 |
November | 0.179912E+10 | 10468.05 | 30-NOV-05:01 | -12.8 |
December | 0.430688E+10 | 11247.12 | 24-DEC-01:52 | -21.0 |
Annual Sum or Average | 0.152426E+11 | |||
Minimum of Months | 0.00 | 0.00 | -21.0 | |
Maximum of Months | 0.430688E+10 | 11247.12 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126137E+10 | 11152.08 | 05-JAN-05:01 | -17.0 |
February | 0.148927E+10 | 11646.35 | 12-FEB-06:52 | -20.0 |
March | 0.878517E+09 | 11891.50 | 19-MAR-06:52 | -15.6 |
April | 0.511402E+09 | 11322.51 | 17-APR-04:11 | -8.0 |
May | 28012213.83 | 9810.03 | 02-MAY-05:01 | 1.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 9895618.60 | 8873.67 | 22-SEP-06:01 | -1.4 |
October | 0.704680E+09 | 11245.81 | 30-OCT-04:01 | -10.0 |
November | 0.955575E+09 | 11188.37 | 30-NOV-05:01 | -12.8 |
December | 0.239016E+10 | 11960.86 | 24-DEC-01:52 | -21.0 |
Annual Sum or Average | 0.822888E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.0 | |
Maximum of Months | 0.239016E+10 | 11960.86 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131178E+10 | 13946.37 | 05-JAN-05:01 | -17.0 |
February | 0.184849E+10 | 14524.72 | 06-FEB-04:12 | -10.0 |
March | 0.128919E+10 | 14900.03 | 19-MAR-08:12 | -13.0 |
April | 0.841493E+09 | 14197.50 | 17-APR-04:11 | -8.0 |
May | 76744678.88 | 12332.00 | 01-MAY-05:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 18295166.35 | 11214.77 | 22-SEP-05:02 | -1.7 |
October | 0.985499E+09 | 14056.51 | 30-OCT-04:01 | -10.0 |
November | 0.109901E+10 | 13955.05 | 30-NOV-05:01 | -12.8 |
December | 0.263554E+10 | 14930.15 | 24-DEC-05:12 | -18.7 |
Annual Sum or Average | 0.101060E+11 | |||
Minimum of Months | 0.00 | 0.00 | -18.7 | |
Maximum of Months | 0.263554E+10 | 14930.15 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139412E+10 | 12751.86 | 06-JAN-05:11 | -7.7 |
February | 0.163526E+10 | 13230.90 | 12-FEB-06:52 | -20.0 |
March | 0.997414E+09 | 13626.29 | 19-MAR-06:52 | -15.6 |
April | 0.601180E+09 | 13056.17 | 17-APR-04:11 | -8.0 |
May | 51337246.33 | 11163.59 | 01-MAY-05:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 15372459.80 | 10036.83 | 22-SEP-06:01 | -1.4 |
October | 0.715937E+09 | 12913.79 | 30-OCT-04:01 | -10.0 |
November | 0.104641E+10 | 12796.68 | 30-NOV-05:01 | -12.8 |
December | 0.252963E+10 | 13672.48 | 24-DEC-05:12 | -18.7 |
Annual Sum or Average | 0.898666E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.252963E+10 | 13672.48 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134963E+10 | 7509.13 | 02-JAN-05:01 | -2.2 |
February | 0.162272E+10 | 7931.37 | 06-FEB-05:11 | -10.0 |
March | 0.773567E+09 | 7439.70 | 20-MAR-04:01 | 0.83 |
April | 0.360361E+09 | 7368.55 | 17-APR-04:01 | -8.0 |
May | 13726186.56 | 6494.82 | 02-MAY-05:01 | 1.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.244365E+09 | 6992.53 | 31-OCT-05:01 | -8.2 |
November | 0.445497E+09 | 7058.69 | 02-NOV-05:01 | -9.0 |
December | 0.173980E+10 | 7696.07 | 26-DEC-05:01 | 3.67 |
Annual Sum or Average | 0.654967E+10 | |||
Minimum of Months | 0.00 | 0.00 | -10.0 | |
Maximum of Months | 0.173980E+10 | 7931.37 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.524204E+09 | 8433.85 | 05-JAN-05:01 | -17.0 |
February | 0.732239E+09 | 9092.72 | 06-FEB-05:11 | -10.0 |
March | 0.338810E+09 | 8539.67 | 20-MAR-04:01 | 0.83 |
April | 0.164515E+09 | 8407.15 | 03-APR-04:01 | -8.0 |
May | 2734586.56 | 7267.44 | 02-MAY-06:01 | 0.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.156607E+09 | 8016.30 | 31-OCT-05:01 | -8.2 |
November | 0.219905E+09 | 8094.54 | 02-NOV-05:01 | -9.0 |
December | 0.840929E+09 | 8776.01 | 23-DEC-05:01 | -21.4 |
Annual Sum or Average | 0.297994E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.4 | |
Maximum of Months | 0.840929E+09 | 9092.72 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294801E+10 | 14180.38 | 05-JAN-07:10 | -17.0 |
February | 0.331594E+10 | 13051.25 | 06-FEB-07:50 | -8.3 |
March | 0.285245E+10 | 12592.04 | 29-MAR-06:10 | -7.7 |
April | 0.208161E+10 | 12391.55 | 17-APR-06:10 | -7.7 |
May | 0.869454E+09 | 11148.52 | 02-MAY-06:10 | 0.17 |
June | 36178972.47 | 8643.84 | 09-JUN-06:07 | 9.37 |
July | 22404214.74 | 8205.04 | 03-JUL-06:05 | 11.00 |
August | 33067560.15 | 6222.00 | 23-AUG-06:05 | 12.50 |
September | 0.198006E+09 | 10465.16 | 22-SEP-06:10 | -1.4 |
October | 0.204994E+10 | 12773.66 | 30-OCT-06:10 | -10.0 |
November | 0.239887E+10 | 13078.16 | 30-NOV-07:10 | -11.3 |
December | 0.383061E+10 | 14987.66 | 22-DEC-07:10 | -20.0 |
Annual Sum or Average | 0.206365E+11 | |||
Minimum of Months | 22404214.74 | 6222.00 | -20.0 | |
Maximum of Months | 0.383061E+10 | 14987.66 | 12.50 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.559034E+09 | 8773.73 | 05-JAN-05:01 | -17.0 |
February | 0.744283E+09 | 9501.75 | 06-FEB-05:11 | -10.0 |
March | 0.374820E+09 | 8875.63 | 20-MAR-04:01 | 0.83 |
April | 0.202267E+09 | 8794.55 | 17-APR-04:01 | -8.0 |
May | 8535962.24 | 7483.87 | 02-MAY-06:01 | 0.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.160552E+09 | 8306.51 | 31-OCT-05:01 | -8.2 |
November | 0.208648E+09 | 8325.01 | 01-NOV-05:01 | -3.0 |
December | 0.877437E+09 | 9131.13 | 23-DEC-05:01 | -21.4 |
Annual Sum or Average | 0.313558E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.4 | |
Maximum of Months | 0.877437E+09 | 9501.75 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101240E+10 | 8473.77 | 05-JAN-05:01 | -17.0 |
February | 0.125939E+10 | 8863.85 | 06-FEB-05:21 | -10.0 |
March | 0.523960E+09 | 8612.41 | 20-MAR-04:01 | 0.83 |
April | 0.307046E+09 | 8637.72 | 17-APR-04:01 | -8.0 |
May | 11090925.18 | 7410.77 | 01-MAY-05:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 735022.55 | 7016.57 | 22-SEP-06:01 | -1.4 |
October | 0.407182E+09 | 8552.34 | 30-OCT-04:01 | -10.0 |
November | 0.637456E+09 | 8505.81 | 30-NOV-05:01 | -12.8 |
December | 0.203263E+10 | 9107.03 | 24-DEC-07:01 | -19.3 |
Annual Sum or Average | 0.619189E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.3 | |
Maximum of Months | 0.203263E+10 | 9107.03 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.505928E+09 | 9494.92 | 05-JAN-05:01 | -17.0 |
February | 0.684631E+09 | 9877.05 | 06-FEB-05:21 | -10.0 |
March | 0.302550E+09 | 9561.63 | 20-MAR-04:01 | 0.83 |
April | 0.173030E+09 | 9572.74 | 17-APR-04:01 | -8.0 |
May | 3694827.83 | 7819.26 | 02-MAY-06:01 | 0.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 566175.87 | 7301.66 | 22-SEP-06:01 | -1.4 |
October | 0.288795E+09 | 9564.64 | 30-OCT-04:01 | -10.0 |
November | 0.363389E+09 | 9556.00 | 30-NOV-05:01 | -12.8 |
December | 0.113651E+10 | 10194.40 | 24-DEC-07:01 | -19.3 |
Annual Sum or Average | 0.345909E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.3 | |
Maximum of Months | 0.113651E+10 | 10194.40 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.451562E+09 | 11687.37 | 05-JAN-05:01 | -17.0 |
February | 0.775004E+09 | 12277.59 | 06-FEB-05:21 | -10.0 |
March | 0.394331E+09 | 11906.66 | 20-MAR-04:01 | 0.83 |
April | 0.281496E+09 | 11947.15 | 17-APR-04:01 | -8.0 |
May | 13122520.35 | 9961.38 | 02-MAY-06:01 | 0.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 844891.39 | 8967.62 | 22-SEP-06:01 | -1.4 |
October | 0.377061E+09 | 11776.69 | 30-OCT-04:01 | -10.0 |
November | 0.361696E+09 | 11628.31 | 30-NOV-05:01 | -12.8 |
December | 0.108688E+10 | 12566.70 | 24-DEC-07:01 | -19.3 |
Annual Sum or Average | 0.374200E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.3 | |
Maximum of Months | 0.108688E+10 | 12566.70 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.530828E+09 | 9413.41 | 05-JAN-05:01 | -17.0 |
February | 0.700245E+09 | 9873.99 | 06-FEB-05:21 | -10.0 |
March | 0.319399E+09 | 9515.30 | 20-MAR-04:01 | 0.83 |
April | 0.204143E+09 | 9619.06 | 17-APR-04:01 | -8.0 |
May | 9172536.38 | 7718.64 | 03-MAY-06:01 | 2.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 1291340.23 | 7761.04 | 22-SEP-06:01 | -1.4 |
October | 0.272618E+09 | 9515.31 | 30-OCT-04:01 | -10.0 |
November | 0.367645E+09 | 9447.78 | 30-NOV-05:01 | -12.8 |
December | 0.115442E+10 | 10170.81 | 24-DEC-07:01 | -19.3 |
Annual Sum or Average | 0.355976E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.3 | |
Maximum of Months | 0.115442E+10 | 10170.81 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.208150E+11 | 18520.31 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.188385E+11 | 18520.31 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.216654E+11 | 18520.31 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.200796E+11 | 18520.31 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.212402E+11 | 18520.31 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.208620E+11 | 18520.31 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.204550E+11 | 18520.31 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.216654E+11 | 18520.31 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.200739E+11 | 18520.31 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.208179E+11 | 18520.31 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.203773E+11 | 18520.31 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.204522E+11 | 18520.31 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.247342E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.188385E+11 | 18520.31 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.216654E+11 | 18520.31 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.834725E+09 | 1168.55 | 02-JAN-16:49 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.723462E+09 | 1113.39 | 06-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.823083E+09 | 950.57 | 21-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.720580E+09 | 868.71 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.763389E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.753320E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.709377E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.798669E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.726295E+09 | 720.41 | 01-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.781841E+09 | 1041.16 | 30-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.816057E+09 | 1168.55 | 06-NOV-16:49 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.812708E+09 | 1168.55 | 01-DEC-16:30 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.926350E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.709377E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.834725E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.524210E+09 | 739.79 | 02-JAN-16:49 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.456992E+09 | 704.99 | 06-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.521222E+09 | 585.02 | 21-MAR-07:10 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.457150E+09 | 518.57 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.485038E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.478827E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.450909E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.507567E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.460366E+09 | 456.08 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.493774E+09 | 651.68 | 30-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.514693E+09 | 739.79 | 06-NOV-16:49 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.511627E+09 | 739.79 | 01-DEC-16:30 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.586237E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.450909E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.524210E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.807455E+09 | 1168.55 | 02-JAN-16:49 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.712619E+09 | 1112.17 | 06-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.819505E+09 | 943.53 | 21-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.721833E+09 | 864.09 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.765957E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.756989E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.712464E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.801115E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.725617E+09 | 720.41 | 01-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.775537E+09 | 1034.52 | 30-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.797477E+09 | 1168.55 | 06-NOV-16:49 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.794463E+09 | 1168.55 | 01-DEC-16:30 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.919103E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.712464E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.819505E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.516022E+09 | 739.74 | 02-JAN-16:49 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.452097E+09 | 702.94 | 06-FEB-16:00 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.518768E+09 | 606.79 | 21-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.455578E+09 | 562.25 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.483497E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.477491E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.449524E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.505226E+09 | 456.05 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.459251E+09 | 512.47 | 25-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.492160E+09 | 659.83 | 30-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.507136E+09 | 739.74 | 06-NOV-16:49 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.504989E+09 | 739.74 | 01-DEC-16:30 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.582174E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.449524E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.518768E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.832250E+09 | 1168.55 | 02-JAN-16:49 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.721938E+09 | 1111.02 | 06-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.822283E+09 | 941.08 | 21-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.720200E+09 | 855.62 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.763068E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.753080E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.709093E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.799168E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.725706E+09 | 720.41 | 01-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.780652E+09 | 1035.65 | 30-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.814283E+09 | 1168.55 | 06-NOV-16:49 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.810812E+09 | 1168.55 | 01-DEC-16:30 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.925253E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.709093E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.832250E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.523376E+09 | 739.79 | 02-JAN-16:49 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.456147E+09 | 703.82 | 06-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.520702E+09 | 579.52 | 21-MAR-07:10 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.456930E+09 | 510.15 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.484812E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.478552E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.450657E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.507346E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.460065E+09 | 456.08 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.493163E+09 | 648.59 | 30-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.513911E+09 | 739.79 | 06-NOV-16:49 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.510804E+09 | 739.79 | 01-DEC-16:30 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.585646E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.450657E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.523376E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.806932E+09 | 1168.55 | 02-JAN-16:49 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.712038E+09 | 1109.72 | 06-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.819451E+09 | 933.65 | 21-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.721428E+09 | 850.75 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.765496E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.756529E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.712052E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.800775E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.725171E+09 | 720.41 | 01-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.775076E+09 | 1028.61 | 30-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.796656E+09 | 1168.55 | 06-NOV-16:49 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.793330E+09 | 1168.55 | 01-DEC-16:30 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.918493E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.712038E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.819451E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.515229E+09 | 739.74 | 02-JAN-16:49 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.451643E+09 | 701.68 | 06-FEB-16:00 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.518430E+09 | 602.33 | 21-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.455362E+09 | 556.30 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.483291E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.477314E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.449369E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.505021E+09 | 456.05 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.458913E+09 | 503.78 | 25-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.491682E+09 | 657.14 | 30-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.506449E+09 | 739.74 | 06-NOV-16:49 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.504385E+09 | 739.74 | 01-DEC-16:30 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.581709E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.449369E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.518430E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.834726E+09 | 1168.55 | 02-JAN-16:49 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.723462E+09 | 1113.39 | 06-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.823083E+09 | 950.56 | 21-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.720580E+09 | 868.69 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.763389E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.753320E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.709377E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.798669E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.726295E+09 | 720.41 | 01-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.781840E+09 | 1041.15 | 30-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.816057E+09 | 1168.55 | 06-NOV-16:49 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.812709E+09 | 1168.55 | 01-DEC-16:30 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.926350E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.709377E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.834726E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.524211E+09 | 739.79 | 02-JAN-16:49 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.456992E+09 | 704.98 | 06-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.521222E+09 | 585.01 | 21-MAR-07:10 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.457150E+09 | 518.56 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.485038E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.478827E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.450909E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.507567E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.460366E+09 | 456.08 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.493774E+09 | 651.68 | 30-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.514693E+09 | 739.79 | 06-NOV-16:49 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.511627E+09 | 739.79 | 01-DEC-16:30 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.586237E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.450909E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.524211E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.807609E+09 | 1168.55 | 02-JAN-16:49 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.713888E+09 | 1112.16 | 06-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.819525E+09 | 943.52 | 21-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.721833E+09 | 864.07 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.765957E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.756989E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.712464E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.801115E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.725617E+09 | 720.41 | 01-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.775536E+09 | 1034.51 | 30-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.797477E+09 | 1168.55 | 06-NOV-16:49 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.794463E+09 | 1168.55 | 01-DEC-16:30 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.919247E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.712464E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.819525E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.516023E+09 | 739.74 | 02-JAN-16:49 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.452097E+09 | 702.94 | 06-FEB-16:00 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.518768E+09 | 606.78 | 21-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.455578E+09 | 562.24 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.483497E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.477491E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.449524E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.505226E+09 | 456.05 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.459251E+09 | 512.48 | 25-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.492160E+09 | 659.82 | 30-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.507136E+09 | 739.74 | 06-NOV-16:49 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.504989E+09 | 739.74 | 01-DEC-16:30 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.582174E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.449524E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.518768E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.208150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.200796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.212402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.208620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.204550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.200739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.208179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.203773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.204522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.247342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.834725E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523314E+09 |
February | 0.901968E+09 | 0.723462E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842365E+09 |
March | 0.107774E+10 | 0.823083E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.909570E+09 |
April | 0.956342E+09 | 0.720580E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.956694E+09 |
May | 0.103597E+10 | 0.763389E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2210883.59 | 0.520135E+09 |
June | 0.103308E+10 | 0.753320E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46954305.55 | 0.231967E+09 |
July | 0.959235E+09 | 0.709377E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59545265.23 | 0.230983E+09 |
August | 0.107774E+10 | 0.798669E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32088391.01 | 0.226983E+09 |
September | 0.956342E+09 | 0.726295E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17814571.60 | 0.328970E+09 |
October | 0.994195E+09 | 0.781841E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 310012.54 | 0.694075E+09 |
November | 0.984487E+09 | 0.816057E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599730E+09 |
December | 0.959235E+09 | 0.812708E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4527.67 | 0.113490E+10 |
Annual Sum or Average | 0.119305E+11 | 0.926350E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158928E+09 | 0.719968E+10 |
Minimum of Months | 0.901968E+09 | 0.709377E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226983E+09 |
Maximum of Months | 0.107774E+10 | 0.834725E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59545265.23 | 0.113490E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.524210E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356419E+09 |
February | 0.571020E+09 | 0.456992E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572512E+09 |
March | 0.682301E+09 | 0.521222E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620862E+09 |
April | 0.605444E+09 | 0.457150E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650906E+09 |
May | 0.655854E+09 | 0.485038E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1478349.36 | 0.350985E+09 |
June | 0.654023E+09 | 0.478827E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31042210.67 | 0.155808E+09 |
July | 0.607275E+09 | 0.450909E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39640776.46 | 0.158116E+09 |
August | 0.682301E+09 | 0.507567E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20913565.56 | 0.154406E+09 |
September | 0.605444E+09 | 0.460366E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11438008.75 | 0.225714E+09 |
October | 0.629407E+09 | 0.493774E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 206071.67 | 0.475715E+09 |
November | 0.623262E+09 | 0.514693E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406245E+09 |
December | 0.607275E+09 | 0.511627E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 516.46 | 0.763563E+09 |
Annual Sum or Average | 0.755301E+10 | 0.586237E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104719E+09 | 0.489125E+10 |
Minimum of Months | 0.571020E+09 | 0.450909E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154406E+09 |
Maximum of Months | 0.682301E+09 | 0.524210E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39640776.46 | 0.763563E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.807455E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572954E+09 |
February | 0.901968E+09 | 0.712619E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895370E+09 |
March | 0.107774E+10 | 0.819505E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.956962E+09 |
April | 0.956342E+09 | 0.721833E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.979435E+09 |
May | 0.103597E+10 | 0.765957E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2209245.85 | 0.525284E+09 |
June | 0.103308E+10 | 0.756989E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46880396.61 | 0.228833E+09 |
July | 0.959235E+09 | 0.712464E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59547099.56 | 0.229671E+09 |
August | 0.107774E+10 | 0.801115E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31026363.62 | 0.234714E+09 |
September | 0.956342E+09 | 0.725617E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15340257.40 | 0.348595E+09 |
October | 0.994195E+09 | 0.775537E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 279961.10 | 0.740435E+09 |
November | 0.984487E+09 | 0.797477E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646109E+09 |
December | 0.959235E+09 | 0.794463E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120143E+10 |
Annual Sum or Average | 0.119305E+11 | 0.919103E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155283E+09 | 0.755979E+10 |
Minimum of Months | 0.901968E+09 | 0.712464E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228833E+09 |
Maximum of Months | 0.107774E+10 | 0.819505E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59547099.56 | 0.120143E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.516022E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357944E+09 |
February | 0.570983E+09 | 0.452097E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574520E+09 |
March | 0.682256E+09 | 0.518768E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620624E+09 |
April | 0.605404E+09 | 0.455578E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646394E+09 |
May | 0.655811E+09 | 0.483497E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1546619.55 | 0.353729E+09 |
June | 0.653980E+09 | 0.477491E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31757813.76 | 0.158785E+09 |
July | 0.607235E+09 | 0.449524E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40551051.71 | 0.155663E+09 |
August | 0.682256E+09 | 0.505226E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22015160.13 | 0.157205E+09 |
September | 0.605404E+09 | 0.459251E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11599464.08 | 0.226809E+09 |
October | 0.629366E+09 | 0.492160E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 230409.15 | 0.472994E+09 |
November | 0.623221E+09 | 0.507136E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408564E+09 |
December | 0.607235E+09 | 0.504989E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766556E+09 |
Annual Sum or Average | 0.755252E+10 | 0.582174E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107701E+09 | 0.489979E+10 |
Minimum of Months | 0.570983E+09 | 0.449524E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155663E+09 |
Maximum of Months | 0.682256E+09 | 0.518768E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40551051.71 | 0.766556E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.832250E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293752E+09 |
February | 0.901968E+09 | 0.721938E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462674E+09 |
March | 0.107774E+10 | 0.822283E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1498.04 | 0.498962E+09 |
April | 0.956342E+09 | 0.720200E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534011E+09 |
May | 0.103597E+10 | 0.763068E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1273528.18 | 0.277339E+09 |
June | 0.103308E+10 | 0.753080E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27242657.15 | 0.120502E+09 |
July | 0.959235E+09 | 0.709093E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35706293.65 | 0.119635E+09 |
August | 0.107774E+10 | 0.799168E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18260217.15 | 0.121925E+09 |
September | 0.956342E+09 | 0.725706E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10241893.06 | 0.187204E+09 |
October | 0.994195E+09 | 0.780652E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 170784.24 | 0.406002E+09 |
November | 0.984487E+09 | 0.814283E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346153E+09 |
December | 0.959235E+09 | 0.810812E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3809.88 | 0.638181E+09 |
Annual Sum or Average | 0.119305E+11 | 0.925253E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92900681.35 | 0.400634E+10 |
Minimum of Months | 0.901968E+09 | 0.709093E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119635E+09 |
Maximum of Months | 0.107774E+10 | 0.832250E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35706293.65 | 0.638181E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.523376E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203030E+09 |
February | 0.571020E+09 | 0.456147E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319657E+09 |
March | 0.682301E+09 | 0.520702E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 0.347476E+09 |
April | 0.605444E+09 | 0.456930E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372194E+09 |
May | 0.655854E+09 | 0.484812E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 808009.34 | 0.193936E+09 |
June | 0.654023E+09 | 0.478552E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17156952.71 | 85217575.26 |
July | 0.607275E+09 | 0.450657E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21760984.07 | 86537960.10 |
August | 0.682301E+09 | 0.507346E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11241017.63 | 87623146.46 |
September | 0.605444E+09 | 0.460065E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6079885.75 | 0.133345E+09 |
October | 0.629407E+09 | 0.493163E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113834.13 | 0.282603E+09 |
November | 0.623262E+09 | 0.513911E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237495E+09 |
December | 0.607275E+09 | 0.510804E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434972E+09 |
Annual Sum or Average | 0.755301E+10 | 0.585646E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57160686.03 | 0.278409E+10 |
Minimum of Months | 0.571020E+09 | 0.450657E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85217575.26 |
Maximum of Months | 0.682301E+09 | 0.523376E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21760984.07 | 0.434972E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.806932E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650208E+10 |
February | 0.901968E+09 | 0.712038E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647455E+10 |
March | 0.107774E+10 | 0.819451E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.68 | 0.566775E+10 |
April | 0.956342E+09 | 0.721428E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433827E+10 |
May | 0.103597E+10 | 0.765496E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85321007.51 | 0.276184E+10 |
June | 0.103308E+10 | 0.756529E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112412E+10 | 0.689269E+09 |
July | 0.959235E+09 | 0.712052E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911637E+09 | 0.646800E+09 |
August | 0.107774E+10 | 0.800775E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.980767E+09 | 0.947642E+09 |
September | 0.956342E+09 | 0.725171E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422242E+09 | 0.151661E+10 |
October | 0.994195E+09 | 0.775076E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7400524.70 | 0.509286E+10 |
November | 0.984487E+09 | 0.796656E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622064E+10 |
December | 0.959235E+09 | 0.793330E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735496E+10 |
Annual Sum or Average | 0.119305E+11 | 0.918493E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353148E+10 | 0.482133E+11 |
Minimum of Months | 0.901968E+09 | 0.712038E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646800E+09 |
Maximum of Months | 0.107774E+10 | 0.819451E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112412E+10 | 0.735496E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.515229E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203843E+09 |
February | 0.570983E+09 | 0.451643E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320173E+09 |
March | 0.682256E+09 | 0.518430E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.31 | 0.345879E+09 |
April | 0.605404E+09 | 0.455362E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368559E+09 |
May | 0.655811E+09 | 0.483291E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 854597.75 | 0.194097E+09 |
June | 0.653980E+09 | 0.477314E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17174072.35 | 87435386.43 |
July | 0.607235E+09 | 0.449369E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22096457.09 | 85029708.69 |
August | 0.682256E+09 | 0.505021E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11758536.78 | 89335398.33 |
September | 0.605404E+09 | 0.458913E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6004682.52 | 0.134299E+09 |
October | 0.629366E+09 | 0.491682E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113845.94 | 0.281617E+09 |
November | 0.623221E+09 | 0.506449E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238472E+09 |
December | 0.607235E+09 | 0.504385E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435914E+09 |
Annual Sum or Average | 0.755252E+10 | 0.581709E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58002198.76 | 0.278465E+10 |
Minimum of Months | 0.570983E+09 | 0.449369E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85029708.69 |
Maximum of Months | 0.682256E+09 | 0.518430E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22096457.09 | 0.435914E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.834726E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464613E+09 |
February | 0.901968E+09 | 0.723462E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733906E+09 |
March | 0.107774E+10 | 0.823083E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.796203E+09 |
April | 0.956342E+09 | 0.720580E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852413E+09 |
May | 0.103597E+10 | 0.763389E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1864965.63 | 0.455671E+09 |
June | 0.103308E+10 | 0.753320E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39966986.80 | 0.199597E+09 |
July | 0.959235E+09 | 0.709377E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51276757.37 | 0.199179E+09 |
August | 0.107774E+10 | 0.798669E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27114252.84 | 0.197571E+09 |
September | 0.956342E+09 | 0.726295E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15085994.42 | 0.292052E+09 |
October | 0.994195E+09 | 0.781840E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262286.05 | 0.621359E+09 |
November | 0.984487E+09 | 0.816057E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532897E+09 |
December | 0.959235E+09 | 0.812709E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1204.36 | 0.986455E+09 |
Annual Sum or Average | 0.119305E+11 | 0.926350E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135572E+09 | 0.633191E+10 |
Minimum of Months | 0.901968E+09 | 0.709377E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197571E+09 |
Maximum of Months | 0.107774E+10 | 0.834726E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51276757.37 | 0.986455E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.524211E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316215E+09 |
February | 0.421807E+09 | 0.456992E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498233E+09 |
March | 0.502994E+09 | 0.521222E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541267E+09 |
April | 0.447140E+09 | 0.457150E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577288E+09 |
May | 0.484071E+09 | 0.485038E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1247628.63 | 0.306151E+09 |
June | 0.482240E+09 | 0.478827E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26531870.49 | 0.133627E+09 |
July | 0.448971E+09 | 0.450909E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34168601.52 | 0.135861E+09 |
August | 0.502994E+09 | 0.507567E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17589635.38 | 0.133786E+09 |
September | 0.447140E+09 | 0.460366E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9790790.03 | 0.198754E+09 |
October | 0.465148E+09 | 0.493774E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 174833.53 | 0.422594E+09 |
November | 0.460569E+09 | 0.514693E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359676E+09 |
December | 0.448971E+09 | 0.511627E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.23 | 0.664662E+09 |
Annual Sum or Average | 0.557719E+10 | 0.586237E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89503410.81 | 0.428811E+10 |
Minimum of Months | 0.421807E+09 | 0.450909E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133627E+09 |
Maximum of Months | 0.502994E+09 | 0.524211E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34168601.52 | 0.664662E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.807609E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508293E+09 |
February | 0.901968E+09 | 0.713888E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780659E+09 |
March | 0.107774E+10 | 0.819525E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835884E+09 |
April | 0.956342E+09 | 0.721833E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.871336E+09 |
May | 0.103597E+10 | 0.765957E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1863036.51 | 0.460528E+09 |
June | 0.103308E+10 | 0.756989E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39490514.30 | 0.198018E+09 |
July | 0.959235E+09 | 0.712464E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50444855.81 | 0.199279E+09 |
August | 0.107774E+10 | 0.801115E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25877190.17 | 0.204501E+09 |
September | 0.956342E+09 | 0.725617E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12875725.77 | 0.307802E+09 |
October | 0.994195E+09 | 0.775536E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 198056.36 | 0.657295E+09 |
November | 0.984487E+09 | 0.797477E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570794E+09 |
December | 0.959235E+09 | 0.794463E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105052E+10 |
Annual Sum or Average | 0.119305E+11 | 0.919247E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130749E+09 | 0.664491E+10 |
Minimum of Months | 0.901968E+09 | 0.712464E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198018E+09 |
Maximum of Months | 0.107774E+10 | 0.819525E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50444855.81 | 0.105052E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.516023E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317422E+09 |
February | 0.570983E+09 | 0.452097E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499689E+09 |
March | 0.682256E+09 | 0.518768E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541411E+09 |
April | 0.605404E+09 | 0.455578E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574238E+09 |
May | 0.655811E+09 | 0.483497E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1264966.61 | 0.309992E+09 |
June | 0.653980E+09 | 0.477491E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26578847.09 | 0.137110E+09 |
July | 0.607235E+09 | 0.449524E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34074110.51 | 0.135008E+09 |
August | 0.682256E+09 | 0.505226E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18233172.42 | 0.137128E+09 |
September | 0.605404E+09 | 0.459251E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9465981.91 | 0.201174E+09 |
October | 0.629366E+09 | 0.492160E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 184609.66 | 0.421275E+09 |
November | 0.623221E+09 | 0.507136E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361630E+09 |
December | 0.607235E+09 | 0.504989E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666718E+09 |
Annual Sum or Average | 0.755252E+10 | 0.582174E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89801688.19 | 0.430280E+10 |
Minimum of Months | 0.570983E+09 | 0.449524E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135008E+09 |
Maximum of Months | 0.682256E+09 | 0.518768E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34074110.51 | 0.666718E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659947E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103194E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112574E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119839E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1754395.55 | 0.617293E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45757636.76 | 0.266252E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61317691.26 | 0.264418E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28971047.47 | 0.268556E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15189326.86 | 0.409554E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132007.20 | 0.886145E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756264E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139185E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153122E+09 | 0.887635E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264418E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61317691.26 | 0.139185E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808465E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127643E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139318E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147875E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2310658.08 | 0.777517E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58903819.11 | 0.341584E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78804660.30 | 0.339771E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37845178.48 | 0.340934E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20626288.64 | 0.511374E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208710.62 | 0.108780E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925316E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170499E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198699E+09 | 0.109861E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339771E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78804660.30 | 0.170499E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.805600E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128722E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140410E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147649E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1398212.45 | 0.803845E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50298295.89 | 0.343705E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63294151.68 | 0.343592E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31683551.75 | 0.343858E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14783300.24 | 0.503779E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48621.51 | 0.107600E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.920131E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170644E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161506E+09 | 0.110148E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343592E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63294151.68 | 0.170644E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 18520.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 18520.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 18520.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 18520.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 18520.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 18520.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 18520.31 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 18520.31 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 18520.31 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 18520.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 18520.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 18520.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:49 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1009.37 | 12-JAN-22:02 |
February | 1306.65 | 01-FEB-10:09 | 1113.39 | 06-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1293.06 | 05-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 950.57 | 21-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2881.79 | 19-MAR-07:00 |
April | 1306.65 | 03-APR-09:09 | 868.71 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1857.43 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.30 | 17-MAY-14:50 | 1003.66 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 286.93 | 25-JUN-17:42 | 658.45 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 498.83 | 16-JUL-11:54 | 644.47 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.41 | 02-AUG-16:00 | 816.13 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 720.41 | 01-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.25 | 10-SEP-14:57 | 693.11 | 21-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1041.16 | 30-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.07 | 11-OCT-14:00 | 1469.08 | 29-OCT-19:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1550.83 | 30-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 | 02-DEC-15:00 | 2395.36 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 644.47 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 498.83 | 2881.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 739.79 | 02-JAN-16:49 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 672.80 | 12-JAN-22:02 |
February | 827.22 | 01-FEB-10:09 | 704.99 | 06-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 862.03 | 05-FEB-23:00 |
March | 827.22 | 01-MAR-10:09 | 585.02 | 21-MAR-07:10 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1921.18 | 19-MAR-07:00 |
April | 827.22 | 03-APR-09:09 | 518.57 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1238.29 | 15-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.20 | 17-MAY-14:50 | 666.65 | 03-MAY-03:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.71 | 25-JUN-17:30 | 437.08 | 08-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 342.25 | 16-JUL-11:56 | 459.39 | 02-JUL-09:00 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.28 | 02-AUG-16:00 | 550.11 | 27-AUG-18:00 |
September | 827.22 | 01-SEP-09:09 | 456.08 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.23 | 10-SEP-15:00 | 461.03 | 21-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 651.68 | 30-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 11-OCT-14:00 | 979.38 | 29-OCT-19:00 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 06-NOV-16:49 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1033.89 | 30-NOV-06:00 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-16:30 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 02-DEC-15:00 | 1596.86 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.08 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 342.25 | 1921.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:49 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1014.51 | 12-JAN-22:02 |
February | 1306.65 | 01-FEB-10:09 | 1112.17 | 06-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1319.18 | 19-FEB-17:00 |
March | 1306.65 | 01-MAR-10:09 | 943.53 | 21-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2888.61 | 19-MAR-06:55 |
April | 1306.65 | 03-APR-09:09 | 864.09 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1857.44 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.30 | 17-MAY-14:50 | 1015.87 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 306.99 | 25-JUN-17:24 | 654.70 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 503.89 | 16-JUL-11:54 | 644.03 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.41 | 02-AUG-16:00 | 883.44 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 720.41 | 01-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.37 | 10-SEP-15:00 | 697.77 | 21-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1034.52 | 30-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.53 | 11-OCT-14:00 | 1493.99 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1550.86 | 30-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2395.37 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 644.03 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 503.89 | 2888.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-16:49 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 674.10 | 12-JAN-22:02 |
February | 827.17 | 01-FEB-10:09 | 702.94 | 06-FEB-16:00 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 862.03 | 05-FEB-23:00 |
March | 827.17 | 01-MAR-10:09 | 606.79 | 21-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1921.18 | 19-MAR-07:00 |
April | 827.17 | 03-APR-09:09 | 562.25 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1238.30 | 15-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.20 | 17-MAY-14:50 | 681.94 | 03-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.29 | 25-JUN-17:50 | 463.58 | 08-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.87 | 16-JUL-12:00 | 442.13 | 03-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 456.05 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.63 | 06-AUG-12:00 | 583.70 | 27-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 512.47 | 25-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.71 | 10-SEP-14:53 | 457.31 | 21-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 659.83 | 30-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 11-OCT-14:00 | 979.37 | 29-OCT-19:00 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 06-NOV-16:49 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1040.91 | 01-NOV-04:13 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:30 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1596.86 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.13 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 347.87 | 1921.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:49 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 583.79 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 1111.02 | 06-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 696.70 | 23-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 941.08 | 21-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 | 14-MAR-13:00 | 1543.41 | 19-MAR-06:52 |
April | 1306.65 | 03-APR-09:09 | 855.62 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1032.51 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 17-MAY-14:50 | 579.89 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.38 | 25-JUN-17:50 | 357.72 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 270.52 | 16-JUL-12:00 | 345.01 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.89 | 06-AUG-12:00 | 418.19 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 720.41 | 01-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.98 | 10-SEP-15:00 | 415.20 | 22-SEP-02:00 |
October | 1306.65 | 02-OCT-09:09 | 1035.65 | 30-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 | 11-OCT-14:00 | 915.84 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 877.12 | 01-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 | 02-DEC-15:00 | 1317.98 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.01 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 270.52 | 1543.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 739.79 | 02-JAN-16:49 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 396.78 | 13-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 703.82 | 06-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 486.15 | 23-FEB-24:00 |
March | 827.22 | 01-MAR-10:09 | 579.52 | 21-MAR-07:10 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14-MAR-13:00 | 1024.98 | 19-MAR-06:52 |
April | 827.22 | 03-APR-09:09 | 510.15 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 697.64 | 15-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.55 | 17-MAY-14:50 | 393.30 | 03-MAY-03:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.48 | 25-JUN-17:50 | 248.75 | 08-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.93 | 16-JUL-11:56 | 243.19 | 03-JUL-03:00 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.21 | 02-AUG-16:00 | 297.41 | 27-AUG-18:00 |
September | 827.22 | 01-SEP-09:09 | 456.08 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.60 | 10-SEP-14:50 | 278.84 | 22-SEP-02:00 |
October | 827.22 | 02-OCT-09:09 | 648.59 | 30-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 | 11-OCT-14:00 | 624.18 | 29-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 06-NOV-16:49 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 580.80 | 01-NOV-04:00 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-16:30 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 874.26 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.19 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 180.93 | 1024.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:49 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 41128.46 | 05-JAN-17:01 |
February | 1306.65 | 01-FEB-10:09 | 1109.72 | 06-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 32400.78 | 02-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 933.65 | 21-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 | 14-MAR-13:00 | 31182.71 | 02-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 850.75 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 30236.15 | 17-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3913.04 | 31-MAY-16:10 | 21100.70 | 02-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13620.70 | 26-JUN-16:02 | 12578.77 | 09-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10493.06 | 17-JUL-11:02 | 11546.25 | 03-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11983.34 | 16-AUG-16:02 | 10746.45 | 17-AUG-06:01 |
September | 1306.65 | 01-SEP-09:09 | 720.41 | 01-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6315.13 | 12-SEP-16:03 | 23272.09 | 22-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 1028.61 | 30-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1017.94 | 10-OCT-17:00 | 32954.89 | 30-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 35445.86 | 29-NOV-17:01 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 48686.88 | 21-DEC-17:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10746.45 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 13620.70 | 48686.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-16:49 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 400.05 | 13-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 701.68 | 06-FEB-16:00 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 487.36 | 23-FEB-24:00 |
March | 827.17 | 01-MAR-10:09 | 602.33 | 21-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 14-MAR-13:00 | 1021.94 | 19-MAR-06:52 |
April | 827.17 | 03-APR-09:09 | 556.30 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 686.61 | 15-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.55 | 17-MAY-14:50 | 402.77 | 03-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.75 | 25-JUN-17:45 | 260.64 | 08-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.56 | 16-JUL-12:00 | 251.80 | 03-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 456.05 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.81 | 06-AUG-12:00 | 323.52 | 27-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 503.78 | 25-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.01 | 10-SEP-14:44 | 276.12 | 22-SEP-02:00 |
October | 827.17 | 02-OCT-09:09 | 657.14 | 30-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 | 11-OCT-14:00 | 615.26 | 29-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 06-NOV-16:49 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 579.95 | 01-NOV-04:00 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:30 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 880.02 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.80 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 187.56 | 1021.94 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:49 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 910.16 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 1113.39 | 06-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1116.57 | 23-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 950.56 | 21-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2396.89 | 19-MAR-06:52 |
April | 1306.65 | 03-APR-09:09 | 868.69 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1584.97 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.56 | 17-MAY-14:50 | 917.44 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.14 | 25-JUN-17:45 | 568.31 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 404.92 | 16-JUL-11:52 | 556.83 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.22 | 02-AUG-16:00 | 684.45 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 720.41 | 01-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.61 | 10-SEP-15:00 | 624.05 | 22-SEP-02:00 |
October | 1306.65 | 02-OCT-09:09 | 1041.15 | 30-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.05 | 11-OCT-14:00 | 1358.84 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1329.68 | 01-NOV-04:08 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 02-DEC-15:00 | 2019.27 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.83 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 404.92 | 2396.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 739.79 | 02-JAN-16:49 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 605.93 | 13-JAN-05:00 |
February | 805.43 | 01-FEB-08:09 | 704.98 | 06-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 749.35 | 23-FEB-24:00 |
March | 805.43 | 01-MAR-08:09 | 585.01 | 21-MAR-07:10 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1597.93 | 19-MAR-06:52 |
April | 805.43 | 03-APR-07:10 | 518.56 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1049.98 | 15-APR-05:00 |
May | 805.43 | 01-MAY-07:10 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 | 17-MAY-14:50 | 609.07 | 03-MAY-03:00 |
June | 805.43 | 01-JUN-07:10 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.40 | 25-JUN-17:50 | 377.56 | 08-JUN-23:00 |
July | 805.43 | 03-JUL-07:10 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 270.15 | 16-JUL-11:52 | 378.42 | 02-JUL-08:40 |
August | 805.43 | 01-AUG-07:10 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.48 | 02-AUG-16:00 | 462.29 | 27-AUG-18:00 |
September | 805.43 | 01-SEP-07:10 | 456.08 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.94 | 10-SEP-14:50 | 413.63 | 22-SEP-02:00 |
October | 805.43 | 02-OCT-07:10 | 651.68 | 30-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.03 | 11-OCT-14:00 | 908.05 | 29-OCT-09:00 |
November | 805.43 | 01-NOV-07:10 | 739.79 | 06-NOV-16:49 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 901.92 | 01-NOV-04:04 |
December | 805.43 | 01-DEC-08:09 | 739.79 | 01-DEC-16:30 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 | 02-DEC-15:00 | 1338.24 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.56 | |||||
Maximum of Months | 805.43 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 270.15 | 1597.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:49 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 942.22 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 1112.16 | 06-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1174.81 | 23-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 943.52 | 21-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2396.89 | 19-MAR-06:52 |
April | 1306.65 | 03-APR-09:09 | 864.07 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1591.41 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.56 | 17-MAY-14:50 | 927.62 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.34 | 25-JUN-17:50 | 566.18 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 404.98 | 16-JUL-11:52 | 557.50 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.22 | 02-AUG-16:00 | 743.01 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 720.41 | 01-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.02 | 10-SEP-14:44 | 626.27 | 22-SEP-02:00 |
October | 1306.65 | 02-OCT-09:09 | 1034.51 | 30-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.58 | 11-OCT-14:00 | 1388.67 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1342.26 | 01-NOV-04:04 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2045.45 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.50 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 404.98 | 2396.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-16:49 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 610.62 | 13-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 702.94 | 06-FEB-16:00 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 760.33 | 23-FEB-24:00 |
March | 827.17 | 01-MAR-10:09 | 606.78 | 21-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1597.93 | 19-MAR-06:52 |
April | 827.17 | 03-APR-09:09 | 562.24 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1047.63 | 15-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 | 17-MAY-14:50 | 621.65 | 03-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.03 | 25-JUN-17:43 | 398.53 | 08-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.82 | 16-JUL-12:00 | 382.38 | 03-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 456.05 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.02 | 06-AUG-12:00 | 491.74 | 27-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 512.48 | 25-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.48 | 10-SEP-13:24 | 411.12 | 22-SEP-02:00 |
October | 827.17 | 02-OCT-09:09 | 659.82 | 30-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.04 | 11-OCT-14:00 | 902.06 | 29-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 06-NOV-16:49 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 901.31 | 01-NOV-04:04 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:30 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1346.54 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.38 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 282.82 | 1597.93 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1338.07 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1600.41 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3404.00 | 19-MAR-06:52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2301.10 | 15-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.47 | 17-MAY-14:40 | 1313.08 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.80 | 25-JUN-17:51 | 763.64 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.26 | 16-JUL-12:00 | 745.76 | 03-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.81 | 06-AUG-12:00 | 895.13 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.89 | 10-SEP-15:00 | 880.40 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.03 | 11-OCT-14:00 | 1982.30 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1906.94 | 01-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2807.87 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 745.76 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.26 | 3404.00 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1643.99 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1999.87 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4171.28 | 19-MAR-06:52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2853.02 | 15-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.15 | 17-MAY-14:40 | 1628.54 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.93 | 25-JUN-18:00 | 975.62 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 685.19 | 16-JUL-12:00 | 961.73 | 03-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.74 | 06-AUG-12:00 | 1131.86 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.38 | 10-SEP-15:00 | 1105.22 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.76 | 11-OCT-14:00 | 2395.01 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2293.63 | 01-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3512.48 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 961.73 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 685.19 | 4171.28 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1491.96 | 31-JAN-02:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1996.90 | 19-FEB-17:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4188.37 | 19-MAR-07:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2763.51 | 15-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.53 | 17-MAY-13:00 | 1479.76 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.12 | 25-JUN-17:50 | 966.47 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 627.81 | 16-JUL-12:00 | 946.01 | 03-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.44 | 02-AUG-16:00 | 1316.60 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.98 | 10-SEP-14:40 | 1042.06 | 21-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.80 | 11-OCT-14:00 | 2242.70 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2237.28 | 01-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3639.14 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 946.01 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 627.81 | 4188.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17838.09 | 23-JAN-08:04 | 42245.05 | 38802.21 | 129642.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18844.66 | 22-FEB-08:03 | 60350.08 | 55431.73 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34485.57 | 16-MAR-05:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22560.58 | 21-APR-05:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34956.41 | 19-MAY-05:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41611.56 | 26-JUN-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 43646.46 | 24-JUL-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43631.75 | 28-AUG-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 42873.04 | 11-SEP-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39974.92 | 06-OCT-05:02 | 3176.32 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28739.91 | 09-NOV-06:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18551.96 | 05-DEC-08:02 | 60350.08 | 55431.73 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17838.09 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43646.46 | 60350.08 | 55431.73 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3244.11 | 20-JAN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.94 |
February | 3313.61 | 18-FEB-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.77 |
March | 7197.28 | 14-MAR-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.73 |
April | 6290.70 | 21-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.49 |
May | 9193.79 | 31-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.06 | 0.00 |
June | 12636.91 | 26-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.20 | 0.00 |
July | 11185.24 | 17-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.68 | 0.00 |
August | 12626.69 | 16-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.48 | 0.00 |
September | 9531.90 | 12-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.42 | 0.00 |
October | 7368.39 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 0.00 |
November | 4127.68 | 09-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.35 |
December | 2237.28 | 01-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2237.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12636.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.68 | 147.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2386.86 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.25 |
February | 1954.89 | 28-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.50 |
March | 2625.29 | 15-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.70 |
April | 2203.65 | 15-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 663.60 |
May | 2893.49 | 18-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.25 |
June | 5572.92 | 26-JUN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.34 | 0.00 |
July | 5608.42 | 17-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.99 | 0.00 |
August | 5063.36 | 21-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 0.00 |
September | 4728.22 | 05-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 |
October | 3188.58 | 11-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.07 |
November | 1971.15 | 30-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1302.11 |
December | 2676.42 | 20-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1713.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1954.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5608.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.99 | 1713.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3029.34 | 27-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.65 |
February | 2647.42 | 28-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.37 |
March | 2932.98 | 15-MAR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.63 |
April | 2178.24 | 14-APR-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.59 |
May | 3124.57 | 18-MAY-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.68 |
June | 6886.07 | 26-JUN-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 | 0.00 |
July | 7103.80 | 17-JUL-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.49 | 0.00 |
August | 5261.70 | 21-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 |
September | 5084.64 | 05-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.06 |
October | 3910.04 | 11-OCT-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.28 |
November | 2341.35 | 29-NOV-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.74 |
December | 2808.04 | 21-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2178.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7103.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.49 | 405.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9626.54 | 25-JAN-16:20 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8964.06 | 27-FEB-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14432.24 | 15-MAR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12818.06 | 21-APR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19412.94 | 18-MAY-05:03 | 1905.79 | 1847.62 | 9524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31933.63 | 26-JUN-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32477.03 | 24-JUL-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32349.29 | 21-AUG-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32261.31 | 11-SEP-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22453.32 | 12-OCT-05:02 | 3811.58 | 3695.25 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12291.89 | 08-NOV-16:40 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7771.23 | 15-DEC-13:30 | 12070.02 | 11086.35 | 14286.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7771.23 | 0.00 | 1847.62 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32477.03 | 12070.02 | 11086.35 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8910.80 | 20-JAN-16:30 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7945.81 | 27-FEB-16:20 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15436.93 | 15-MAR-15:40 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14280.51 | 21-APR-14:00 | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16804.07 | 18-MAY-15:20 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28349.32 | 26-JUN-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35089.14 | 17-JUL-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34216.08 | 21-AUG-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30759.97 | 11-SEP-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16233.77 | 11-OCT-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11393.82 | 08-NOV-16:10 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7207.47 | 03-DEC-14:02 | 1270.53 | 1231.90 | 9524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7207.47 | 0.00 | 1231.90 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35089.14 | 6198.29 | 5543.17 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1738.72 | 20-JAN-14:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.56 |
February | 1356.29 | 27-FEB-13:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.61 |
March | 3611.99 | 14-MAR-14:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 |
April | 3585.70 | 20-APR-13:30 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 |
May | 5812.41 | 17-MAY-13:30 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 44.26 | 0.00 |
June | 11715.31 | 25-JUN-17:21 | 0.00 | 280.18 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 259.83 | 0.00 |
July | 11812.74 | 16-JUL-14:32 | 334.80 | 200.13 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 400.78 | 0.00 |
August | 6973.60 | 16-AUG-14:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 84.03 | 0.00 |
September | 6627.05 | 11-SEP-14:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 68.50 | 0.00 |
October | 4120.79 | 11-OCT-14:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 22.55 | 0.00 |
November | 2261.43 | 09-NOV-13:50 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 |
December | 1354.05 | 03-DEC-14:02 | 267.84 | 160.10 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1354.05 | 0.00 | 160.10 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11812.74 | 1306.65 | 720.41 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 400.78 | 208.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2273.34 | 20-JAN-10:10 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.51 |
February | 3095.03 | 27-FEB-09:30 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.21 |
March | 6222.24 | 15-MAR-09:10 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.26 |
April | 6721.26 | 21-APR-09:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.32 |
May | 7582.63 | 16-MAY-08:50 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.42 |
June | 10167.35 | 11-JUN-09:12 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.34 |
July | 13991.73 | 09-JUL-09:12 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.70 |
August | 13180.04 | 06-AUG-09:12 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.04 |
September | 10535.02 | 04-SEP-09:22 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.29 |
October | 5341.19 | 11-OCT-09:40 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.82 |
November | 3149.73 | 07-NOV-09:30 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.87 |
December | 1638.82 | 03-DEC-14:02 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1638.82 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.42 | |
Maximum of Months | 13991.73 | 827.22 | 456.08 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12943.39 | 20-JAN-13:30 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.86 |
February | 12152.00 | 26-FEB-13:13 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.28 |
March | 12899.07 | 15-MAR-13:20 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 |
April | 9182.46 | 21-APR-13:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.16 |
May | 8342.34 | 16-MAY-13:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 28.68 | 0.00 |
June | 15159.02 | 25-JUN-16:01 | 468.72 | 280.18 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 168.28 | 0.00 |
July | 16085.08 | 09-JUL-13:12 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 215.42 | 0.00 |
August | 15717.46 | 20-AUG-15:12 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 34.82 | 0.00 |
September | 17131.05 | 04-SEP-13:22 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 51.90 | 0.00 |
October | 18038.18 | 01-OCT-13:31 | 468.72 | 280.18 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.39 |
November | 18051.77 | 05-NOV-13:31 | 468.72 | 280.18 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.99 |
December | 16170.60 | 17-DEC-13:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8342.34 | 267.84 | 160.10 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18051.77 | 1306.65 | 720.41 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 215.42 | 373.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4665.83 | 20-JAN-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 |
February | 5004.34 | 17-FEB-16:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.59 |
March | 9958.39 | 12-MAR-17:12 | 0.00 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.18 |
April | 9131.63 | 08-APR-17:42 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.17 |
May | 8952.21 | 31-MAY-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 22.55 | 0.00 |
June | 16456.68 | 11-JUN-16:31 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 | 0.00 |
July | 16301.01 | 02-JUL-17:01 | 0.00 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 | 0.00 |
August | 15800.59 | 13-AUG-16:42 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.79 |
September | 16020.11 | 10-SEP-16:52 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 43.30 | 0.00 |
October | 10825.64 | 09-OCT-16:12 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.85 |
November | 5705.93 | 07-NOV-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.38 |
December | 3489.52 | 01-DEC-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3489.52 | 0.00 | 101.35 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16456.68 | 805.38 | 456.05 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 43.30 | 221.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1435.83 | 20-JAN-14:10 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.51 |
February | 1516.86 | 27-FEB-13:05 | 5088.93 | 2881.64 | 6023.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.94 |
March | 1768.82 | 14-MAR-13:10 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 0.00 |
April | 1432.48 | 20-APR-13:40 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.88 |
May | 3873.41 | 17-MAY-13:30 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 23.78 | 0.00 |
June | 5943.53 | 26-JUN-12:09 | 8905.63 | 5042.88 | 10541.25 | 0.00 | 0.00 | 0.00 | 0.00 | 28.32 | 0.00 |
July | 7130.61 | 17-JUL-06:03 | 803.52 | 720.40 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.92 |
August | 5524.14 | 18-AUG-14:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 27.57 | 0.00 |
September | 5953.32 | 11-SEP-14:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 36.81 | 0.00 |
October | 3366.89 | 11-OCT-14:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 | 0.00 |
November | 1963.30 | 09-NOV-13:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 |
December | 1464.33 | 03-DEC-15:13 | 267.84 | 187.54 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1432.48 | 267.84 | 187.54 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7130.61 | 8905.63 | 5042.88 | 10541.25 | 0.00 | 0.00 | 0.00 | 0.00 | 36.81 | 99.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1522.92 | 20-JAN-10:10 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.48 |
February | 2488.08 | 27-FEB-08:45 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.28 |
March | 4293.91 | 15-MAR-09:10 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 |
April | 4550.61 | 21-APR-09:10 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.52 |
May | 5325.70 | 16-MAY-09:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 |
June | 8263.82 | 08-JUN-06:02 | 1017.38 | 912.15 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.97 |
July | 10927.14 | 09-JUL-09:12 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.37 |
August | 11397.08 | 06-AUG-09:41 | 296.74 | 177.38 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.38 |
September | 10949.52 | 04-SEP-09:52 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 |
October | 4963.12 | 10-OCT-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.66 |
November | 3031.36 | 07-NOV-09:20 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.06 |
December | 1478.61 | 03-DEC-12:32 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1478.61 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 | |
Maximum of Months | 11397.08 | 1610.86 | 912.16 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9057.32 | 20-JAN-14:00 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.19 |
February | 11967.05 | 26-FEB-12:52 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.42 |
March | 9616.48 | 14-MAR-13:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.73 |
April | 5468.22 | 12-APR-12:08 | 5088.93 | 2881.64 | 6023.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 708.75 |
May | 7679.14 | 16-MAY-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 3061.25 | 0.00 |
June | 12530.52 | 26-JUN-16:20 | 1607.03 | 1600.90 | 3346.41 | 0.00 | 0.00 | 0.00 | 0.00 | 11487.58 | 0.00 |
July | 12319.71 | 17-JUL-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 9433.90 | 0.00 |
August | 12854.97 | 20-AUG-11:42 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 0.00 |
September | 13862.40 | 04-SEP-12:31 | 468.72 | 280.18 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 0.00 |
October | 14324.51 | 09-OCT-13:21 | 468.72 | 280.18 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.06 |
November | 12770.26 | 05-NOV-13:42 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.61 |
December | 12890.53 | 17-DEC-14:02 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5468.22 | 267.84 | 160.10 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14324.51 | 5088.93 | 2881.64 | 6023.53 | 0.00 | 0.00 | 0.00 | 0.00 | 11487.58 | 708.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3310.21 | 23-JAN-16:10 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 |
February | 3570.91 | 17-FEB-16:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.53 |
March | 5698.73 | 12-MAR-17:12 | 0.00 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.21 |
April | 6131.74 | 08-APR-17:42 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.22 |
May | 5856.52 | 31-MAY-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 12.15 | 0.00 |
June | 12322.59 | 25-JUN-16:41 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 72.67 | 0.00 |
July | 12490.59 | 02-JUL-17:31 | 0.00 | 228.04 | 2859.87 | 0.00 | 0.00 | 0.00 | 0.00 | 13.70 | 0.00 |
August | 13021.03 | 13-AUG-17:11 | 0.00 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 |
September | 13450.44 | 10-SEP-16:41 | 381.49 | 228.04 | 2859.87 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 0.00 |
October | 11927.03 | 09-OCT-15:22 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.63 |
November | 4983.03 | 07-NOV-15:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.36 |
December | 2714.80 | 04-DEC-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2714.80 | 0.00 | 101.35 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13450.44 | 805.38 | 456.05 | 2859.87 | 0.00 | 0.00 | 0.00 | 0.00 | 72.67 | 116.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1717.60 | 20-JAN-14:50 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.52 |
February | 1557.74 | 27-FEB-13:10 | 5088.93 | 2881.64 | 6023.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.00 |
March | 3456.45 | 14-MAR-15:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.14 |
April | 3224.68 | 20-APR-13:30 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 |
May | 5433.51 | 17-MAY-13:30 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 37.04 | 0.00 |
June | 9124.21 | 25-JUN-17:42 | 0.00 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 237.88 | 0.00 |
July | 10003.87 | 16-JUL-14:22 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 332.05 | 0.00 |
August | 6515.43 | 20-AUG-15:41 | 535.68 | 320.20 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 23.60 | 0.00 |
September | 7104.19 | 10-SEP-16:01 | 602.64 | 360.23 | 4517.68 | 0.00 | 0.00 | 0.00 | 0.00 | 68.57 | 0.00 |
October | 3951.64 | 11-OCT-14:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 18.98 | 0.00 |
November | 2484.46 | 09-NOV-13:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 |
December | 1448.73 | 14-DEC-13:30 | 2544.47 | 1440.82 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1448.73 | 0.00 | 240.15 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10003.87 | 5088.93 | 2881.64 | 6023.57 | 0.00 | 0.00 | 0.00 | 0.00 | 332.05 | 170.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2970.08 | 20-JAN-09:40 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.12 |
February | 4166.55 | 27-FEB-09:10 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.92 |
March | 6690.05 | 15-MAR-08:50 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.28 |
April | 7014.51 | 21-APR-08:40 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.50 |
May | 7704.87 | 16-MAY-08:30 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.27 |
June | 13500.54 | 11-JUN-09:02 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.34 |
July | 14077.34 | 16-JUL-08:21 | 296.74 | 177.38 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 66.99 | 0.00 |
August | 14328.74 | 06-AUG-09:01 | 296.74 | 177.38 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.10 |
September | 13543.47 | 04-SEP-09:12 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.70 |
October | 6603.10 | 09-OCT-09:53 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.62 |
November | 4124.41 | 07-NOV-09:10 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.71 |
December | 1680.13 | 17-DEC-11:53 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1680.13 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14328.74 | 805.43 | 456.08 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 66.99 | 176.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14458.10 | 22-JAN-12:13 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.09 |
February | 15208.96 | 26-FEB-12:22 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.76 |
March | 12579.78 | 12-MAR-12:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.01 |
April | 8665.77 | 21-APR-13:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.86 |
May | 7723.74 | 16-MAY-13:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 24.07 | 0.00 |
June | 14189.76 | 25-JUN-13:02 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 84.10 | 0.00 |
July | 13841.56 | 16-JUL-14:22 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 337.32 | 0.00 |
August | 14988.33 | 27-AUG-13:12 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.72 |
September | 16263.66 | 10-SEP-12:41 | 468.72 | 280.18 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 0.00 |
October | 16519.09 | 09-OCT-13:11 | 468.72 | 280.18 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.12 |
November | 14912.28 | 05-NOV-13:02 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.73 |
December | 14503.40 | 17-DEC-11:53 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7723.74 | 267.84 | 160.10 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16519.09 | 1306.65 | 720.41 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 337.32 | 562.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4507.08 | 20-JAN-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.57 |
February | 4910.77 | 17-FEB-16:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.37 |
March | 9635.51 | 12-MAR-17:12 | 0.00 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.03 |
April | 8782.24 | 08-APR-17:42 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.57 |
May | 8368.65 | 31-MAY-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 18.89 | 0.00 |
June | 15779.05 | 11-JUN-17:41 | 0.00 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.74 |
July | 14727.98 | 02-JUL-17:21 | 0.00 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 20.96 | 0.00 |
August | 15713.62 | 13-AUG-17:11 | 0.00 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.07 |
September | 15992.71 | 10-SEP-16:41 | 381.49 | 228.04 | 2859.87 | 0.00 | 0.00 | 0.00 | 0.00 | 18.22 | 0.00 |
October | 14495.77 | 09-OCT-16:32 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.37 |
November | 5661.88 | 07-NOV-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 |
December | 3372.94 | 01-DEC-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3372.94 | 0.00 | 101.35 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15992.71 | 805.38 | 456.05 | 2859.87 | 0.00 | 0.00 | 0.00 | 0.00 | 20.96 | 183.57 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.127945E+12 | 170078.32 | 05-JAN-07:10 | 0.335345E+11 | 93869.37 | 05-JAN-07:30 |
February | 0.121157E+12 | 209717.90 | 06-FEB-07:10 | 0.323947E+11 | 66846.74 | 06-FEB-07:40 |
March | 0.127132E+12 | 180364.37 | 20-MAR-06:10 | 0.246378E+11 | 62705.83 | 04-MAR-07:10 |
April | 0.110453E+12 | 171588.33 | 03-APR-06:10 | 0.174360E+11 | 61755.61 | 17-APR-06:19 |
May | 0.116521E+12 | 127290.56 | 31-MAY-15:00 | 0.996314E+10 | 32903.62 | 02-MAY-06:30 |
June | 0.155627E+12 | 184000.73 | 26-JUN-15:20 | 0.900991E+10 | 9210.58 | 01-JUN-11:50 |
July | 0.152186E+12 | 167748.89 | 17-JUL-10:50 | 0.861284E+10 | 9109.11 | 03-JUL-11:09 |
August | 0.157716E+12 | 170422.89 | 16-AUG-15:09 | 0.902473E+10 | 9053.46 | 16-AUG-11:20 |
September | 0.131524E+12 | 149655.45 | 12-SEP-15:50 | 0.894923E+10 | 31837.61 | 22-SEP-06:30 |
October | 0.119876E+12 | 169814.80 | 30-OCT-06:10 | 0.194585E+11 | 70219.79 | 30-OCT-06:00 |
November | 0.119221E+12 | 157049.63 | 30-NOV-07:10 | 0.267578E+11 | 79490.82 | 29-NOV-20:00 |
December | 0.140734E+12 | 201346.85 | 26-DEC-07:10 | 0.443150E+11 | 112156.86 | 23-DEC-07:19 |
Annual Sum or Average | 0.158009E+13 | 0.244094E+12 | ||||
Minimum of Months | 0.110453E+12 | 127290.56 | 0.861284E+10 | 9053.46 | ||
Maximum of Months | 0.157716E+12 | 209717.90 | 0.443150E+11 | 112156.86 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.239340E+11 | 0.765085E+10 | 0.641572E+11 | 0.109131E+10 | 0.536759E+10 | 1312252.65 | 0.250566E+11 | 0.685830E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.214479E+11 | 0.636102E+10 | 0.580684E+11 | 0.987394E+09 | 0.507697E+10 | 1186778.30 | 0.289773E+11 | 0.236555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251745E+11 | 0.626705E+10 | 0.666107E+11 | 0.114317E+10 | 0.667201E+10 | 1343621.24 | 0.189751E+11 | 0.228803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223634E+11 | 0.527914E+10 | 0.619407E+11 | 0.105056E+10 | 0.551717E+10 | 1267813.82 | 0.122505E+11 | 0.205038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.240022E+11 | 0.482744E+10 | 0.653840E+11 | 0.111685E+10 | 0.892412E+10 | 1327936.95 | 0.189640E+10 | 0.103689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.238287E+11 | 0.436489E+10 | 0.641577E+11 | 0.109954E+10 | 0.195162E+11 | 1296568.36 | 57333570.79 | 0.426011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.223447E+11 | 0.462091E+10 | 0.631525E+11 | 0.106757E+10 | 0.183600E+11 | 1299182.41 | 30765660.11 | 0.426081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.249659E+11 | 0.515335E+10 | 0.666107E+11 | 0.114306E+10 | 0.188534E+11 | 1343621.24 | 58314859.67 | 0.409304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.224121E+11 | 0.572263E+10 | 0.619118E+11 | 0.105017E+10 | 0.138860E+11 | 1267813.82 | 0.443454E+09 | 0.260962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.235184E+11 | 0.672388E+10 | 0.641717E+11 | 0.109110E+10 | 0.751196E+10 | 1312252.65 | 0.123780E+11 | 0.447922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.236070E+11 | 0.719979E+10 | 0.627379E+11 | 0.107133E+10 | 0.568157E+10 | 1278270.02 | 0.175401E+11 | 0.138169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232459E+11 | 0.784425E+10 | 0.631380E+11 | 0.106811E+10 | 0.550588E+10 | 1299182.41 | 0.392135E+11 | 0.716882E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280845E+12 | 0.720152E+11 | 0.762041E+12 | 0.129802E+11 | 0.120873E+12 | 15535293.87 | 0.156877E+12 | 0.174443E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.214479E+11 | 0.436489E+10 | 0.580684E+11 | 0.987394E+09 | 0.507697E+10 | 1186778.30 | 30765660.11 | 0.236555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.251745E+11 | 0.784425E+10 | 0.666107E+11 | 0.114317E+10 | 0.195162E+11 | 1343621.24 | 0.392135E+11 | 0.426081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.236536E+11 | 0.00 | 0.988086E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.233650E+11 | 0.00 | 0.902966E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.143278E+11 | 0.00 | 0.103100E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.811832E+10 | 0.00 | 0.931768E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.459857E+09 | 0.00 | 0.950328E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.900991E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.861284E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.902473E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.467719E+09 | 0.00 | 0.848151E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.104534E+11 | 0.00 | 0.900507E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.176439E+11 | 0.00 | 0.911388E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.348077E+11 | 0.00 | 0.950736E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.133297E+12 | 0.00 | 0.110797E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.848151E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.348077E+11 | 0.00 | 0.103100E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28079.40 | 02-JAN-16:49 | 5557.43 | 01-JAN-06:10 | 47562.27 | 02-JAN-08:09 | 926.74 | 02-JAN-16:00 | 8438.81 | 20-JAN-15:00 | 0.73 | 02-JAN-06:10 | 128147.92 | 05-JAN-07:10 |
February | 27522.72 | 06-FEB-16:00 | 5557.43 | 01-FEB-06:10 | 47562.27 | 01-FEB-08:09 | 925.66 | 06-FEB-16:00 | 7413.10 | 27-FEB-15:20 | 0.73 | 01-FEB-07:10 | 171881.05 | 06-FEB-07:10 |
March | 25857.89 | 21-MAR-07:10 | 5557.43 | 01-MAR-06:10 | 47562.27 | 01-MAR-08:09 | 925.01 | 21-MAR-07:19 | 19210.66 | 15-MAR-15:00 | 0.73 | 01-MAR-07:10 | 143763.79 | 20-MAR-06:10 |
April | 25029.52 | 03-APR-07:10 | 5557.43 | 01-APR-05:10 | 47562.27 | 03-APR-07:10 | 923.82 | 03-APR-07:19 | 11991.28 | 21-APR-13:30 | 0.73 | 03-APR-06:10 | 135475.00 | 03-APR-06:10 |
May | 23688.37 | 01-MAY-07:10 | 5557.43 | 01-MAY-18:49 | 47562.27 | 01-MAY-07:10 | 921.90 | 01-MAY-07:19 | 19659.99 | 31-MAY-15:00 | 0.73 | 02-MAY-06:10 | 61629.36 | 01-MAY-06:10 |
June | 23688.37 | 01-JUN-07:10 | 5557.43 | 01-JUN-19:19 | 47562.27 | 01-JUN-07:10 | 921.90 | 01-JUN-07:19 | 34179.81 | 27-JUN-15:09 | 0.73 | 11-JUN-16:30 | 9355.63 | 09-JUN-06:10 |
July | 23688.37 | 03-JUL-07:10 | 5557.43 | 01-JUL-19:30 | 47562.27 | 03-JUL-07:10 | 921.90 | 03-JUL-07:19 | 34957.46 | 24-JUL-15:30 | 0.73 | 01-JUL-05:10 | 7214.92 | 03-JUL-06:19 |
August | 23688.37 | 01-AUG-07:10 | 5557.43 | 01-AUG-19:10 | 47562.27 | 01-AUG-07:10 | 921.90 | 01-AUG-07:19 | 30979.44 | 11-AUG-15:09 | 0.73 | 01-AUG-05:10 | 5374.37 | 23-AUG-06:19 |
September | 23848.95 | 25-SEP-07:10 | 5557.43 | 01-SEP-05:10 | 47562.27 | 01-SEP-07:10 | 922.13 | 25-SEP-07:19 | 28108.91 | 05-SEP-15:39 | 0.73 | 22-SEP-07:10 | 34296.14 | 22-SEP-06:10 |
October | 26773.84 | 30-OCT-07:10 | 5557.43 | 01-OCT-05:10 | 47562.27 | 02-OCT-07:10 | 926.33 | 30-OCT-07:19 | 19313.30 | 11-OCT-15:00 | 0.73 | 23-OCT-06:10 | 127980.66 | 30-OCT-06:10 |
November | 28079.40 | 06-NOV-16:49 | 5557.43 | 01-NOV-05:10 | 47562.27 | 01-NOV-07:10 | 926.74 | 06-NOV-16:00 | 10862.20 | 08-NOV-15:20 | 0.73 | 01-NOV-06:10 | 120902.49 | 30-NOV-07:10 |
December | 28079.40 | 01-DEC-16:30 | 5557.43 | 01-DEC-06:10 | 47562.27 | 01-DEC-08:09 | 926.74 | 01-DEC-16:40 | 6346.57 | 14-DEC-14:00 | 0.73 | 01-DEC-17:10 | 158698.73 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 23688.37 | 5557.43 | 47562.27 | 921.90 | 6346.57 | 0.73 | 5374.37 | |||||||
Maximum of Months | 28079.40 | 5557.43 | 47562.27 | 926.74 | 34957.46 | 0.73 | 171881.05 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 16404.22 | 20-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11153.51 | 18-FEB-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26046.62 | 14-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17744.73 | 20-APR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39251.06 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84403.91 | 26-JUN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 70203.93 | 17-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 72487.75 | 16-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54585.28 | 12-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38534.34 | 11-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20452.68 | 07-NOV-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15386.39 | 01-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 11153.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84403.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 170078.32 | 05-JAN-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 4903.24 | 0.73 | 128147.92 | 0.00 | 0.00 |
February | 209717.90 | 06-FEB-07:10 | 9359.67 | 21853.28 | 0.00 | 256.05 | 6367.12 | 0.73 | 171881.05 | 0.00 | 0.00 |
March | 180364.37 | 20-MAR-06:10 | 9359.67 | 21853.28 | 0.00 | 256.05 | 5130.85 | 0.73 | 143763.79 | 0.00 | 0.00 |
April | 171588.33 | 03-APR-06:10 | 9002.08 | 21853.28 | 0.00 | 256.01 | 5001.23 | 0.73 | 135475.00 | 0.00 | 0.00 |
May | 127290.56 | 31-MAY-15:00 | 23688.37 | 43769.98 | 0.00 | 920.43 | 19659.99 | 0.73 | 0.00 | 39251.06 | 0.00 |
June | 184000.73 | 26-JUN-15:20 | 23688.37 | 43769.98 | 0.00 | 920.43 | 31433.43 | 0.73 | 0.00 | 84187.79 | 0.00 |
July | 167748.89 | 17-JUL-10:50 | 23688.37 | 43275.33 | 0.00 | 920.24 | 32254.23 | 0.73 | 0.00 | 67609.99 | 0.00 |
August | 170422.89 | 16-AUG-15:09 | 23688.37 | 43769.98 | 0.00 | 920.43 | 29728.76 | 0.73 | 0.00 | 72314.62 | 0.00 |
September | 149655.45 | 12-SEP-15:50 | 23688.37 | 43769.98 | 0.00 | 920.43 | 26690.67 | 0.73 | 0.00 | 54585.28 | 0.00 |
October | 169814.80 | 30-OCT-06:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 4806.97 | 0.73 | 127980.66 | 0.00 | 0.00 |
November | 157049.63 | 30-NOV-07:10 | 9359.67 | 21853.28 | 0.00 | 256.05 | 4677.41 | 0.73 | 120902.49 | 0.00 | 0.00 |
December | 201346.85 | 26-DEC-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 5620.96 | 0.73 | 158698.73 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 127290.56 | 9002.08 | 21853.28 | 0.00 | 256.01 | 4677.41 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 209717.90 | 23688.37 | 43769.98 | 5557.43 | 920.43 | 32254.23 | 0.73 | 171881.05 | 84187.79 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 85701.82 | 05-JAN-07:30 | 0.00 | 9707.17 | 31-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 60653.35 | 11-FEB-17:00 | 0.00 | 9796.16 | 07-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 56380.38 | 04-MAR-17:00 | 0.00 | 9638.20 | 03-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 53584.17 | 17-APR-06:19 | 0.00 | 9458.12 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 25372.12 | 02-MAY-06:19 | 0.00 | 9338.40 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9210.58 | 01-JUN-11:50 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9109.11 | 03-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9053.46 | 16-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 24888.24 | 22-SEP-06:10 | 0.00 | 9113.47 | 28-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 62747.72 | 30-OCT-06:30 | 0.00 | 9237.08 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 71421.19 | 29-NOV-20:00 | 0.00 | 9354.82 | 28-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 104241.97 | 23-DEC-07:30 | 0.00 | 9469.20 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9053.46 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 104241.97 | 0.00 | 9796.16 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.42 | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Annual Sum or Average | 0.17 | 19.42 | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.42 | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 18.54 | 0.33 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.33 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 17.39 | 0.17 | 17.84 | 0.00 | 17.84 | 0.00 | 17.84 |
Annual Sum or Average | 1.33 | 17.71 | 0.50 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 18.54 | 0.33 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.83 | 16.07 | 3.33 | 16.26 | 0.00 | 16.26 | 0.00 | 16.26 |
February | 19.67 | 15.87 | 8.33 | 16.19 | 0.00 | 16.19 | 0.00 | 16.19 |
March | 7.50 | 15.06 | 2.67 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
April | 5.50 | 16.39 | 1.33 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.65 | 1.33 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.59 | 4.17 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4.50 | 16.21 | 0.83 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
November | 3.50 | 17.00 | 1.00 | 17.54 | 0.00 | 17.54 | 0.00 | 17.54 |
December | 34.50 | 16.10 | 14.00 | 16.63 | 0.00 | 16.63 | 0.00 | 16.63 |
Annual Sum or Average | 84.00 | 16.01 | 31.50 | 16.40 | 7.67 | 17.10 | 5.50 | 17.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.50 | 17.00 | 14.00 | 17.54 | 5.67 | 27.65 | 4.17 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.33 | 15.54 | 1.00 | 15.45 | 0.00 | 15.45 | 0.00 | 15.45 |
February | 14.67 | 14.88 | 3.50 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
March | 8.00 | 14.98 | 2.33 | 14.85 | 0.00 | 14.85 | 0.00 | 14.85 |
April | 4.00 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
May | 0.17 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.84 | 6.67 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 28.03 | 13.83 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.08 | 5.50 | 28.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.68 | 4.33 | 27.68 |
October | 3.50 | 15.30 | 0.00 | 15.30 | 0.00 | 15.30 | 0.00 | 15.30 |
November | 2.50 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 |
December | 22.17 | 14.77 | 2.67 | 14.81 | 0.00 | 14.81 | 0.00 | 14.81 |
Annual Sum or Average | 61.33 | 15.02 | 9.50 | 14.98 | 31.50 | 18.97 | 30.33 | 21.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 | 0.00 | 14.81 |
Maximum of Months | 22.17 | 17.23 | 3.50 | 17.23 | 14.50 | 28.08 | 13.83 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 16.26 | 0.00 | 16.26 | 0.50 | 18.22 | 0.50 | 19.59 |
February | 12.50 | 15.08 | 4.00 | 15.10 | 1.17 | 15.93 | 1.17 | 16.67 |
March | 6.50 | 14.94 | 2.17 | 14.82 | 1.50 | 16.75 | 1.50 | 18.19 |
April | 3.67 | 15.46 | 0.17 | 15.63 | 0.00 | 15.63 | 0.00 | 15.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.68 | 4.50 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.80 | 8.17 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.89 | 5.00 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.38 | 9.00 | 27.37 |
October | 3.33 | 15.42 | 0.00 | 15.42 | 5.50 | 23.43 | 5.50 | 25.29 |
November | 2.33 | 16.37 | 0.17 | 16.57 | 2.33 | 22.11 | 2.33 | 24.04 |
December | 16.50 | 15.05 | 2.33 | 15.19 | 2.00 | 16.39 | 2.00 | 17.39 |
Annual Sum or Average | 47.17 | 15.23 | 8.83 | 15.25 | 41.83 | 20.61 | 39.83 | 22.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.63 | 0.00 | 15.63 |
Maximum of Months | 16.50 | 16.37 | 4.00 | 16.57 | 9.50 | 27.89 | 9.00 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.50 | 15.64 | 1.33 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
February | 14.83 | 14.88 | 4.33 | 14.83 | 0.00 | 14.83 | 0.00 | 14.83 |
March | 8.50 | 14.96 | 2.83 | 14.84 | 0.83 | 15.73 | 0.50 | 16.21 |
April | 5.00 | 15.14 | 0.00 | 15.14 | 0.17 | 15.55 | 0.17 | 15.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.43 | 0.83 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.65 | 3.83 | 28.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.20 | 6.33 | 28.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.43 | 2.17 | 28.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.23 | 3.83 | 28.27 |
October | 3.50 | 15.29 | 0.00 | 15.29 | 1.33 | 18.86 | 1.33 | 20.89 |
November | 2.50 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 |
December | 22.67 | 14.78 | 4.50 | 14.80 | 0.00 | 14.80 | 0.00 | 14.80 |
Annual Sum or Average | 62.50 | 15.01 | 13.00 | 14.96 | 28.83 | 18.65 | 19.00 | 20.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | 0.00 | 14.80 |
Maximum of Months | 22.67 | 15.85 | 4.50 | 15.85 | 8.83 | 28.65 | 6.33 | 28.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
February | 3.67 | 18.98 | 2.83 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
March | 0.17 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 |
April | 0.17 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.67 | 18.47 | 1.50 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
Annual Sum or Average | 7.00 | 18.62 | 4.33 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 18.98 | 2.83 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
February | 0.83 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
March | 0.17 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.59 | 2.50 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.71 | 9.50 | 27.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.77 | 4.67 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.56 | 3.50 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 |
Annual Sum or Average | 2.17 | 16.79 | 0.00 | 16.79 | 20.17 | 26.62 | 20.17 | 27.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 17.22 | 0.00 | 17.22 | 9.50 | 27.77 | 9.50 | 27.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 49.17 | 17.19 | 49.17 | 17.19 | 0.50 | 17.24 | 0.50 | 17.29 |
February | 51.83 | 17.12 | 51.17 | 17.12 | 1.00 | 17.22 | 1.00 | 17.32 |
March | 44.33 | 17.95 | 44.33 | 17.95 | 1.17 | 18.07 | 1.17 | 18.20 |
April | 34.17 | 18.15 | 34.17 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 |
May | 9.50 | 19.03 | 9.50 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 25.33 | 14.33 | 25.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 25.33 | 11.67 | 25.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 25.64 | 19.83 | 25.64 |
September | 2.00 | 18.07 | 2.00 | 18.07 | 20.00 | 24.71 | 19.17 | 25.27 |
October | 33.83 | 17.72 | 33.83 | 17.72 | 13.83 | 19.20 | 13.33 | 20.21 |
November | 40.33 | 17.34 | 40.33 | 17.34 | 3.17 | 17.74 | 3.17 | 18.10 |
December | 64.50 | 16.67 | 63.83 | 16.67 | 2.33 | 16.87 | 2.33 | 17.06 |
Annual Sum or Average | 329.67 | 17.41 | 328.33 | 17.41 | 87.83 | 18.42 | 86.50 | 19.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.87 | 0.00 | 17.06 |
Maximum of Months | 64.50 | 19.03 | 63.83 | 19.03 | 20.00 | 25.64 | 19.83 | 25.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
February | 0.83 | 16.52 | 0.00 | 16.52 | 0.00 | 16.52 | 0.00 | 16.52 |
March | 0.17 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 |
April | 0.17 | 17.14 | 0.00 | 17.14 | 0.17 | 22.27 | 0.17 | 23.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.08 | 3.00 | 28.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.93 | 3.00 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.04 | 1.67 | 28.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.91 | 3.33 | 27.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.79 | 1.33 | 27.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 |
Annual Sum or Average | 2.17 | 16.79 | 0.00 | 16.79 | 19.83 | 26.87 | 12.50 | 27.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 17.21 | 0.00 | 17.21 | 5.50 | 28.08 | 3.33 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
February | 2.67 | 18.15 | 1.50 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
March | 0.67 | 15.48 | 0.50 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
April | 0.33 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.43 | 0.50 | 27.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.52 | 2.33 | 27.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
November | 0.33 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
December | 7.83 | 16.49 | 3.00 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
Annual Sum or Average | 12.33 | 16.85 | 5.00 | 17.30 | 3.50 | 19.01 | 2.83 | 20.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.83 | 18.15 | 3.00 | 18.72 | 2.50 | 27.52 | 2.33 | 27.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 |
February | 2.00 | 15.99 | 0.17 | 16.25 | 0.00 | 16.25 | 0.00 | 16.25 |
March | 0.83 | 15.31 | 0.67 | 15.13 | 0.50 | 18.23 | 0.50 | 20.10 |
April | 0.50 | 17.02 | 0.00 | 17.02 | 0.17 | 19.59 | 0.17 | 21.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.44 | 0.67 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.79 | 5.67 | 27.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 28.05 | 11.17 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.12 | 4.83 | 28.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.81 | 3.67 | 27.81 |
October | 0.17 | 16.98 | 0.00 | 16.98 | 1.17 | 26.19 | 1.17 | 26.81 |
November | 0.33 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
December | 5.83 | 15.34 | 0.50 | 15.40 | 0.00 | 15.40 | 0.00 | 15.40 |
Annual Sum or Average | 10.00 | 15.69 | 1.33 | 15.71 | 28.00 | 24.41 | 27.83 | 25.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 | 0.00 | 15.40 |
Maximum of Months | 5.83 | 17.02 | 0.67 | 17.02 | 11.33 | 28.12 | 11.17 | 28.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.18 | 0.00 | 17.18 | 1.83 | 25.97 | 1.83 | 26.70 |
February | 1.33 | 16.55 | 0.17 | 16.84 | 2.00 | 23.08 | 2.00 | 24.78 |
March | 0.50 | 15.65 | 0.33 | 15.38 | 1.50 | 23.48 | 1.50 | 25.24 |
April | 0.33 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.56 | 2.67 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.61 | 7.33 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.76 | 5.00 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.04 | 10.33 | 27.03 |
October | 0.17 | 17.13 | 0.00 | 17.13 | 10.33 | 26.73 | 10.33 | 26.81 |
November | 0.33 | 17.09 | 0.00 | 17.09 | 5.17 | 26.76 | 5.17 | 27.06 |
December | 3.00 | 15.81 | 0.50 | 15.86 | 2.67 | 21.07 | 2.67 | 23.13 |
Annual Sum or Average | 6.00 | 16.21 | 1.00 | 16.22 | 49.67 | 25.98 | 48.83 | 26.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 17.18 | 0.50 | 17.18 | 10.83 | 27.76 | 10.33 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
February | 2.17 | 15.91 | 0.17 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 |
March | 1.00 | 15.24 | 0.83 | 15.09 | 0.83 | 19.05 | 0.50 | 20.44 |
April | 0.33 | 16.87 | 0.00 | 16.87 | 0.17 | 20.53 | 0.17 | 22.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.47 | 0.67 | 27.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.51 | 3.67 | 28.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.17 | 4.50 | 28.14 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.28 | 2.17 | 28.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.11 | 4.00 | 28.12 |
October | 0.17 | 16.99 | 0.00 | 16.99 | 1.83 | 27.06 | 1.50 | 27.50 |
November | 0.33 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 |
December | 5.17 | 15.39 | 1.00 | 15.40 | 0.00 | 15.40 | 0.00 | 15.40 |
Annual Sum or Average | 9.50 | 15.69 | 2.00 | 15.66 | 25.50 | 24.31 | 17.17 | 25.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 | 0.00 | 15.40 |
Maximum of Months | 5.17 | 17.07 | 1.00 | 17.07 | 6.50 | 28.51 | 4.50 | 28.59 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 471.67 | 23.58 | 12.00 | 23.54 | 12.00 | 23.51 |
February | 408.67 | 23.49 | 3.17 | 23.47 | 3.17 | 23.45 |
March | 458.00 | 23.74 | 5.50 | 23.75 | 0.00 | 23.75 |
April | 355.00 | 23.82 | 11.67 | 23.86 | 0.00 | 23.86 |
May | 112.33 | 23.96 | 143.83 | 24.64 | 0.00 | 24.64 |
June | 0.67 | 24.00 | 306.33 | 24.55 | 0.67 | 24.55 |
July | 20.00 | 24.55 | 366.83 | 24.53 | 17.67 | 24.54 |
August | 2.00 | 24.28 | 349.67 | 24.56 | 1.33 | 24.56 |
September | 32.17 | 24.01 | 170.83 | 24.81 | 0.00 | 24.81 |
October | 241.83 | 23.93 | 43.00 | 24.20 | 0.00 | 24.20 |
November | 342.67 | 23.84 | 4.50 | 23.86 | 0.00 | 23.86 |
December | 492.67 | 23.42 | 22.50 | 23.32 | 22.50 | 23.23 |
Annual Sum or Average | 2937.67 | 23.68 | 1439.83 | 23.99 | 57.33 | 23.97 |
Minimum of Months | 0.67 | 23.42 | 3.17 | 23.32 | 0.00 | 23.23 |
Maximum of Months | 492.67 | 24.55 | 366.83 | 24.81 | 22.50 | 24.81 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.83 | 22.25 | 74.83 | 22.05 | 74.83 | 21.89 |
February | 453.17 | 22.26 | 79.33 | 22.01 | 79.33 | 21.83 |
March | 496.83 | 22.72 | 34.83 | 22.57 | 34.83 | 22.44 |
April | 453.67 | 22.83 | 26.33 | 22.73 | 26.33 | 22.64 |
May | 214.83 | 23.55 | 39.17 | 23.72 | 0.00 | 23.72 |
June | 15.00 | 23.96 | 260.00 | 24.37 | 0.00 | 24.37 |
July | 33.83 | 24.26 | 309.33 | 24.39 | 23.33 | 24.39 |
August | 5.00 | 24.02 | 290.17 | 24.44 | 1.00 | 24.44 |
September | 127.50 | 23.80 | 115.17 | 24.29 | 0.00 | 24.29 |
October | 422.33 | 23.27 | 19.83 | 23.20 | 16.17 | 23.12 |
November | 471.33 | 22.72 | 11.17 | 22.67 | 11.17 | 22.63 |
December | 497.00 | 21.90 | 125.83 | 21.61 | 125.83 | 21.41 |
Annual Sum or Average | 3692.33 | 22.67 | 1386.00 | 22.88 | 392.83 | 22.74 |
Minimum of Months | 5.00 | 21.90 | 11.17 | 21.61 | 0.00 | 21.41 |
Maximum of Months | 501.83 | 24.26 | 309.33 | 24.44 | 125.83 | 24.44 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.37 | 192.33 | 21.05 | 192.33 | 20.87 |
February | 454.00 | 21.49 | 184.50 | 21.16 | 184.50 | 20.98 |
March | 508.33 | 22.11 | 107.33 | 21.76 | 107.33 | 21.52 |
April | 459.83 | 22.16 | 96.50 | 21.82 | 96.50 | 21.58 |
May | 289.67 | 23.30 | 31.83 | 23.33 | 6.17 | 23.28 |
June | 27.50 | 23.76 | 271.50 | 24.30 | 0.00 | 24.30 |
July | 39.33 | 24.12 | 315.67 | 24.35 | 27.00 | 24.34 |
August | 22.33 | 23.78 | 274.83 | 24.31 | 0.00 | 24.31 |
September | 173.83 | 23.47 | 92.17 | 23.87 | 0.00 | 23.87 |
October | 484.00 | 22.64 | 65.83 | 22.39 | 65.83 | 22.20 |
November | 488.67 | 21.87 | 122.50 | 21.64 | 122.50 | 21.48 |
December | 497.00 | 21.03 | 276.00 | 20.75 | 276.00 | 20.61 |
Annual Sum or Average | 3946.50 | 22.04 | 2031.00 | 22.12 | 1078.17 | 21.86 |
Minimum of Months | 22.33 | 21.03 | 31.83 | 20.75 | 0.00 | 20.61 |
Maximum of Months | 508.33 | 24.12 | 315.67 | 24.35 | 276.00 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.34 | 358.17 | 20.14 | 358.17 | 20.05 |
February | 454.00 | 20.46 | 332.33 | 20.28 | 332.33 | 20.21 |
March | 514.00 | 21.23 | 250.17 | 20.85 | 250.17 | 20.66 |
April | 464.00 | 21.21 | 190.83 | 20.75 | 189.83 | 20.49 |
May | 304.17 | 22.73 | 79.17 | 22.86 | 21.17 | 22.74 |
June | 41.00 | 23.79 | 332.33 | 24.30 | 7.00 | 24.31 |
July | 69.33 | 24.25 | 361.50 | 24.42 | 44.83 | 24.44 |
August | 71.50 | 23.40 | 292.50 | 24.13 | 9.33 | 24.13 |
September | 224.83 | 22.98 | 105.83 | 23.37 | 11.33 | 23.28 |
October | 494.00 | 21.63 | 166.50 | 21.25 | 166.50 | 21.02 |
November | 489.00 | 20.81 | 304.17 | 20.56 | 304.17 | 20.45 |
December | 497.00 | 20.12 | 434.33 | 20.02 | 434.33 | 19.98 |
Annual Sum or Average | 4124.83 | 21.22 | 3207.83 | 21.36 | 2129.17 | 21.08 |
Minimum of Months | 41.00 | 20.12 | 79.17 | 20.02 | 7.00 | 19.98 |
Maximum of Months | 514.00 | 24.25 | 434.33 | 24.42 | 434.33 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.73 | 289.33 | 20.44 | 289.33 | 20.31 |
February | 440.50 | 20.89 | 249.50 | 20.55 | 249.50 | 20.39 |
March | 450.00 | 21.40 | 200.67 | 21.01 | 194.00 | 20.77 |
April | 391.83 | 21.13 | 183.67 | 20.79 | 161.50 | 20.49 |
May | 220.17 | 22.57 | 157.83 | 23.20 | 14.00 | 23.10 |
June | 46.17 | 25.15 | 396.17 | 24.49 | 27.00 | 24.61 |
July | 99.17 | 25.22 | 420.00 | 24.68 | 80.33 | 24.82 |
August | 69.33 | 24.26 | 378.67 | 24.34 | 26.17 | 24.45 |
September | 161.83 | 23.07 | 202.17 | 23.81 | 15.67 | 23.81 |
October | 403.17 | 21.60 | 154.33 | 21.35 | 136.50 | 21.10 |
November | 475.67 | 21.13 | 228.00 | 20.84 | 228.00 | 20.69 |
December | 497.00 | 20.38 | 366.17 | 20.17 | 366.17 | 20.09 |
Annual Sum or Average | 3756.83 | 21.41 | 3226.50 | 21.76 | 1788.17 | 21.49 |
Minimum of Months | 46.17 | 20.38 | 154.33 | 20.17 | 14.00 | 20.09 |
Maximum of Months | 502.00 | 25.22 | 420.00 | 24.68 | 366.17 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 369.00 | 21.17 | 246.00 | 21.15 | 188.17 | 20.90 |
February | 334.50 | 21.05 | 234.83 | 21.01 | 183.17 | 20.75 |
March | 385.17 | 21.35 | 221.67 | 21.18 | 184.83 | 20.94 |
April | 382.67 | 21.03 | 189.50 | 20.72 | 165.83 | 20.44 |
May | 266.67 | 22.47 | 127.83 | 22.91 | 22.33 | 22.78 |
June | 84.67 | 23.74 | 320.33 | 24.24 | 15.50 | 24.31 |
July | 102.50 | 24.28 | 360.83 | 24.43 | 55.83 | 24.51 |
August | 90.00 | 23.85 | 347.83 | 24.27 | 24.00 | 24.35 |
September | 164.50 | 23.35 | 225.50 | 23.98 | 28.83 | 24.07 |
October | 337.67 | 21.76 | 237.33 | 21.98 | 144.50 | 21.77 |
November | 339.83 | 21.43 | 230.00 | 21.58 | 154.17 | 21.33 |
December | 407.33 | 20.89 | 283.83 | 20.71 | 255.83 | 20.50 |
Annual Sum or Average | 3264.50 | 21.67 | 3025.50 | 22.11 | 1423.00 | 21.83 |
Minimum of Months | 84.67 | 20.89 | 127.83 | 20.71 | 15.50 | 20.44 |
Maximum of Months | 407.33 | 24.28 | 360.83 | 24.43 | 255.83 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 481.00 | 20.61 | 310.00 | 20.36 | 310.00 | 20.25 |
February | 422.50 | 20.67 | 275.33 | 20.44 | 271.50 | 20.33 |
March | 446.00 | 21.02 | 248.17 | 20.81 | 230.67 | 20.64 |
April | 412.17 | 20.89 | 203.83 | 20.64 | 179.83 | 20.39 |
May | 295.17 | 22.33 | 142.00 | 22.83 | 23.83 | 22.73 |
June | 103.83 | 23.69 | 332.33 | 24.22 | 23.00 | 24.34 |
July | 124.83 | 23.95 | 358.50 | 24.29 | 57.00 | 24.37 |
August | 110.33 | 23.25 | 328.50 | 24.06 | 18.00 | 24.11 |
September | 233.50 | 22.87 | 174.00 | 23.48 | 25.50 | 23.52 |
October | 420.67 | 21.32 | 200.17 | 21.23 | 165.83 | 21.03 |
November | 454.17 | 20.94 | 245.33 | 20.68 | 244.17 | 20.56 |
December | 490.33 | 20.38 | 375.83 | 20.17 | 375.83 | 20.09 |
Annual Sum or Average | 3994.50 | 21.29 | 3194.00 | 21.57 | 1925.17 | 21.31 |
Minimum of Months | 103.83 | 20.38 | 142.00 | 20.17 | 18.00 | 20.09 |
Maximum of Months | 490.33 | 23.95 | 375.83 | 24.29 | 375.83 | 24.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.57 | 348.50 | 20.42 | 348.50 | 20.36 |
February | 454.00 | 20.57 | 346.67 | 20.46 | 346.67 | 20.42 |
March | 514.00 | 21.13 | 274.50 | 20.87 | 274.50 | 20.74 |
April | 485.00 | 21.36 | 163.33 | 21.08 | 163.33 | 20.91 |
May | 403.33 | 22.98 | 32.00 | 22.93 | 18.00 | 22.84 |
June | 43.33 | 23.76 | 248.67 | 24.20 | 3.67 | 24.20 |
July | 54.67 | 23.94 | 304.17 | 24.29 | 34.83 | 24.27 |
August | 50.50 | 23.70 | 252.17 | 24.19 | 6.00 | 24.18 |
September | 190.83 | 23.46 | 97.33 | 23.87 | 0.00 | 23.87 |
October | 498.17 | 22.36 | 69.33 | 22.13 | 69.33 | 21.95 |
November | 489.00 | 21.36 | 178.17 | 21.17 | 178.17 | 21.06 |
December | 497.00 | 20.50 | 387.00 | 20.39 | 387.00 | 20.34 |
Annual Sum or Average | 4181.83 | 21.51 | 2701.83 | 21.58 | 1830.00 | 21.33 |
Minimum of Months | 43.33 | 20.50 | 32.00 | 20.39 | 0.00 | 20.34 |
Maximum of Months | 514.00 | 23.94 | 387.00 | 24.29 | 387.00 | 24.27 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.13 | 234.67 | 20.89 | 234.67 | 20.76 |
February | 449.50 | 21.25 | 223.67 | 20.91 | 223.67 | 20.74 |
March | 483.17 | 21.81 | 167.83 | 21.43 | 164.00 | 21.19 |
April | 426.83 | 21.81 | 121.83 | 21.52 | 114.00 | 21.29 |
May | 238.17 | 23.00 | 106.83 | 23.40 | 9.33 | 23.33 |
June | 13.83 | 25.03 | 401.50 | 24.45 | 9.33 | 24.48 |
July | 55.00 | 25.17 | 429.83 | 24.63 | 52.17 | 24.69 |
August | 29.50 | 25.32 | 412.50 | 24.48 | 19.33 | 24.56 |
September | 82.50 | 23.69 | 230.17 | 24.40 | 5.67 | 24.45 |
October | 371.00 | 22.43 | 95.17 | 22.39 | 63.17 | 22.17 |
November | 467.33 | 21.88 | 112.33 | 21.63 | 112.33 | 21.47 |
December | 497.00 | 20.95 | 290.00 | 20.69 | 290.00 | 20.57 |
Annual Sum or Average | 3615.83 | 21.81 | 2826.33 | 22.21 | 1297.67 | 21.96 |
Minimum of Months | 13.83 | 20.95 | 95.17 | 20.69 | 5.67 | 20.57 |
Maximum of Months | 502.00 | 25.32 | 429.83 | 24.63 | 290.00 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 398.00 | 21.16 | 159.50 | 20.99 | 126.00 | 20.66 |
February | 373.33 | 20.79 | 189.33 | 20.51 | 167.50 | 20.21 |
March | 433.00 | 21.15 | 186.67 | 20.81 | 175.33 | 20.55 |
April | 451.33 | 21.21 | 146.50 | 20.86 | 143.50 | 20.62 |
May | 379.67 | 22.45 | 50.50 | 22.49 | 23.50 | 22.36 |
June | 82.17 | 22.98 | 259.67 | 24.07 | 7.33 | 24.07 |
July | 87.17 | 23.42 | 326.33 | 24.23 | 43.83 | 24.20 |
August | 62.83 | 23.29 | 364.67 | 24.32 | 18.17 | 24.35 |
September | 101.00 | 23.29 | 257.83 | 24.32 | 20.33 | 24.43 |
October | 303.67 | 21.93 | 176.33 | 22.26 | 88.50 | 22.04 |
November | 336.50 | 21.39 | 169.17 | 21.66 | 84.83 | 21.32 |
December | 417.50 | 20.68 | 217.17 | 20.38 | 197.83 | 20.09 |
Annual Sum or Average | 3426.17 | 21.50 | 2503.67 | 21.96 | 1096.67 | 21.64 |
Minimum of Months | 62.83 | 20.68 | 50.50 | 20.38 | 7.33 | 20.09 |
Maximum of Months | 451.33 | 23.42 | 364.67 | 24.32 | 197.83 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.67 | 21.08 | 246.50 | 20.83 | 246.50 | 20.70 |
February | 441.67 | 21.06 | 232.00 | 20.79 | 232.00 | 20.66 |
March | 478.50 | 21.46 | 201.17 | 21.14 | 198.00 | 20.95 |
April | 448.33 | 21.54 | 127.83 | 21.26 | 125.17 | 21.06 |
May | 314.17 | 22.81 | 82.17 | 23.09 | 11.33 | 23.03 |
June | 54.33 | 24.11 | 341.17 | 24.37 | 14.17 | 24.43 |
July | 67.83 | 24.10 | 363.50 | 24.36 | 40.83 | 24.38 |
August | 45.17 | 23.99 | 372.50 | 24.34 | 15.00 | 24.38 |
September | 123.17 | 23.55 | 192.50 | 24.25 | 9.50 | 24.33 |
October | 400.00 | 22.35 | 95.83 | 22.28 | 67.17 | 22.10 |
November | 455.67 | 21.72 | 117.33 | 21.51 | 116.67 | 21.37 |
December | 496.33 | 20.90 | 306.67 | 20.65 | 306.67 | 20.54 |
Annual Sum or Average | 3821.83 | 21.72 | 2679.17 | 22.02 | 1383.00 | 21.78 |
Minimum of Months | 45.17 | 20.90 | 82.17 | 20.65 | 9.50 | 20.54 |
Maximum of Months | 496.67 | 24.11 | 372.50 | 24.37 | 306.67 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.77 | 276.00 | 20.52 | 276.00 | 20.40 |
February | 454.00 | 20.79 | 271.00 | 20.57 | 271.00 | 20.46 |
March | 513.00 | 21.57 | 173.67 | 21.19 | 173.67 | 20.96 |
April | 467.50 | 21.74 | 125.33 | 21.37 | 124.50 | 21.13 |
May | 279.83 | 23.15 | 72.67 | 23.31 | 10.83 | 23.23 |
June | 14.33 | 24.07 | 340.17 | 24.37 | 4.17 | 24.37 |
July | 37.50 | 24.39 | 376.17 | 24.45 | 35.83 | 24.45 |
August | 33.33 | 23.78 | 306.00 | 24.29 | 6.17 | 24.29 |
September | 186.50 | 23.35 | 106.83 | 23.82 | 1.00 | 23.81 |
October | 490.83 | 22.22 | 84.67 | 21.94 | 84.67 | 21.73 |
November | 488.50 | 21.31 | 203.50 | 21.08 | 203.50 | 20.95 |
December | 497.00 | 20.46 | 362.50 | 20.29 | 362.50 | 20.22 |
Annual Sum or Average | 3964.33 | 21.56 | 2698.50 | 21.76 | 1553.83 | 21.48 |
Minimum of Months | 14.33 | 20.46 | 72.67 | 20.29 | 1.00 | 20.22 |
Maximum of Months | 513.00 | 24.39 | 376.17 | 24.45 | 362.50 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 421.33 | 21.00 | 199.00 | 20.74 | 199.00 | 20.60 |
February | 366.33 | 21.03 | 184.83 | 20.71 | 182.83 | 20.53 |
March | 377.50 | 21.52 | 138.17 | 21.21 | 128.33 | 20.96 |
April | 338.17 | 21.49 | 124.50 | 21.27 | 103.17 | 21.01 |
May | 183.83 | 22.88 | 131.17 | 23.52 | 8.33 | 23.47 |
June | 29.33 | 25.69 | 332.33 | 24.62 | 22.00 | 24.72 |
July | 73.00 | 25.52 | 354.83 | 24.82 | 66.50 | 24.94 |
August | 47.00 | 24.83 | 310.83 | 24.52 | 23.50 | 24.63 |
September | 131.67 | 23.39 | 159.50 | 24.12 | 9.67 | 24.20 |
October | 339.67 | 21.92 | 105.17 | 21.86 | 77.83 | 21.64 |
November | 397.67 | 21.43 | 140.00 | 21.21 | 137.17 | 21.06 |
December | 422.00 | 20.63 | 272.33 | 20.38 | 272.33 | 20.27 |
Annual Sum or Average | 3127.50 | 21.64 | 2452.67 | 22.05 | 1230.67 | 21.81 |
Minimum of Months | 29.33 | 20.63 | 105.17 | 20.38 | 8.33 | 20.27 |
Maximum of Months | 422.00 | 25.69 | 354.83 | 24.82 | 272.33 | 24.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 346.67 | 21.65 | 198.33 | 21.78 | 124.50 | 21.52 |
February | 315.50 | 21.41 | 199.83 | 21.42 | 140.83 | 21.13 |
March | 372.00 | 21.71 | 154.33 | 21.57 | 117.67 | 21.30 |
April | 380.00 | 21.64 | 121.00 | 21.40 | 101.00 | 21.14 |
May | 236.67 | 22.96 | 122.67 | 23.40 | 10.00 | 23.32 |
June | 36.83 | 24.13 | 335.17 | 24.37 | 8.83 | 24.40 |
July | 72.33 | 24.65 | 378.50 | 24.52 | 49.17 | 24.58 |
August | 51.33 | 24.63 | 376.50 | 24.44 | 21.50 | 24.52 |
September | 131.67 | 23.90 | 239.83 | 24.37 | 22.00 | 24.51 |
October | 319.33 | 22.35 | 189.67 | 22.65 | 89.50 | 22.51 |
November | 318.83 | 21.96 | 186.83 | 22.26 | 97.50 | 22.05 |
December | 394.83 | 21.39 | 238.33 | 21.24 | 202.00 | 21.01 |
Annual Sum or Average | 2976.00 | 22.06 | 2741.00 | 22.61 | 984.50 | 22.37 |
Minimum of Months | 36.83 | 21.39 | 121.00 | 21.24 | 8.83 | 21.01 |
Maximum of Months | 394.83 | 24.65 | 378.50 | 24.52 | 202.00 | 24.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 475.50 | 21.00 | 232.33 | 20.74 | 231.83 | 20.61 |
February | 419.83 | 20.98 | 221.33 | 20.73 | 216.50 | 20.58 |
March | 445.17 | 21.37 | 171.50 | 21.13 | 156.33 | 20.92 |
April | 412.67 | 21.42 | 136.67 | 21.23 | 115.00 | 21.00 |
May | 261.67 | 22.75 | 138.50 | 23.29 | 10.33 | 23.24 |
June | 67.83 | 24.27 | 346.83 | 24.38 | 20.83 | 24.49 |
July | 83.17 | 24.35 | 374.17 | 24.41 | 49.17 | 24.47 |
August | 70.50 | 23.77 | 351.50 | 24.28 | 17.67 | 24.32 |
September | 184.83 | 23.25 | 182.83 | 23.92 | 15.33 | 24.02 |
October | 413.33 | 21.87 | 125.50 | 21.86 | 87.67 | 21.69 |
November | 447.33 | 21.38 | 167.17 | 21.16 | 164.83 | 21.02 |
December | 487.83 | 20.71 | 320.17 | 20.46 | 320.17 | 20.36 |
Annual Sum or Average | 3769.67 | 21.61 | 2768.50 | 21.97 | 1405.67 | 21.72 |
Minimum of Months | 67.83 | 20.71 | 125.50 | 20.46 | 10.33 | 20.36 |
Maximum of Months | 487.83 | 24.35 | 374.17 | 24.41 | 320.17 | 24.49 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.63953 | 20.79383 | 0.06527 | 5.62967 |
February | 454.00000 | 23.59983 | 18.00381 | 0.03648 | 5.84771 |
March | 514.00000 | 23.84787 | 17.71212 | 0.11817 | 5.66196 |
April | 485.00000 | 23.98403 | 21.63833 | 0.17575 | 5.99149 |
May | 508.00000 | 24.37728 | 24.51764 | -0.5323 | 11.60476 |
June | 496.00000 | 24.36012 | 32.67401 | -0.4134 | 9.03278 |
July | 497.00000 | 24.41665 | 34.64639 | -0.3814 | 8.50043 |
August | 514.00000 | 24.39104 | 33.16961 | -0.3971 | 8.80475 |
September | 485.00000 | 24.40575 | 24.49749 | -0.4691 | 10.24509 |
October | 502.00000 | 24.24517 | 18.87406 | 0.25589 | 6.72166 |
November | 489.00000 | 24.02992 | 20.31809 | 0.18082 | 6.01032 |
December | 497.00000 | 23.42979 | 14.66566 | -0.0284 | 5.97255 |
Annual Sum or Average | 5943.00000 | 24.06409 | 23.51018 | -0.1175 | 7.51699 |
Minimum of Months | 454.00000 | 23.42979 | 14.66566 | -0.5323 | 5.62967 |
Maximum of Months | 514.00000 | 24.41665 | 34.64639 | 0.25589 | 11.60476 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.24818 | 22.67459 | -0.2545 | 7.74487 |
February | 454.00000 | 22.25992 | 19.82224 | -0.2727 | 8.29565 |
March | 514.00000 | 22.77766 | 19.44511 | -0.1335 | 6.98961 |
April | 485.00000 | 22.92238 | 23.81198 | -0.0715 | 6.54373 |
May | 508.00000 | 23.97226 | 25.82845 | -0.6841 | 15.78727 |
June | 496.00000 | 24.23863 | 33.61677 | -0.4723 | 9.97798 |
July | 497.00000 | 24.28486 | 35.53037 | -0.4426 | 9.41438 |
August | 514.00000 | 24.27672 | 34.09271 | -0.4589 | 9.74756 |
September | 485.00000 | 24.20197 | 25.45590 | -0.5655 | 12.40759 |
October | 502.00000 | 23.43814 | 20.72706 | 0.05009 | 6.23760 |
November | 489.00000 | 22.77195 | 22.77049 | -0.1170 | 6.35891 |
December | 497.00000 | 21.89678 | 16.41782 | -0.3836 | 9.92958 |
Annual Sum or Average | 5943.00000 | 23.28282 | 25.06278 | -0.3179 | 9.13212 |
Minimum of Months | 454.00000 | 21.89678 | 16.41782 | -0.6841 | 6.23760 |
Maximum of Months | 514.00000 | 24.28486 | 35.53037 | 0.05009 | 15.78727 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.37360 | 22.57295 | -0.4844 | 12.27491 |
February | 454.00000 | 21.49177 | 20.44272 | -0.4723 | 12.15119 |
March | 514.00000 | 22.13198 | 19.95186 | -0.2977 | 9.69605 |
April | 485.00000 | 22.25660 | 24.44168 | -0.2355 | 8.97175 |
May | 508.00000 | 23.67610 | 26.05884 | -0.7858 | 19.58603 |
June | 496.00000 | 24.20003 | 33.57045 | -0.4756 | 10.08407 |
July | 497.00000 | 24.26287 | 35.49638 | -0.4425 | 9.46046 |
August | 514.00000 | 24.20569 | 34.12267 | -0.4772 | 10.09547 |
September | 485.00000 | 23.98582 | 25.50647 | -0.6439 | 14.92997 |
October | 502.00000 | 22.68962 | 21.65264 | -0.1404 | 7.49490 |
November | 489.00000 | 21.87463 | 23.98870 | -0.3451 | 9.17364 |
December | 497.00000 | 21.03022 | 16.97379 | -0.6114 | 15.28832 |
Annual Sum or Average | 5943.00000 | 22.77640 | 25.44142 | -0.4510 | 11.60083 |
Minimum of Months | 454.00000 | 21.03022 | 16.97379 | -0.7858 | 7.49490 |
Maximum of Months | 514.00000 | 24.26287 | 35.49638 | -0.1404 | 19.58603 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.34081 | 24.56768 | -0.7737 | 20.40100 |
February | 454.00000 | 20.45555 | 22.10328 | -0.7634 | 19.84773 |
March | 514.00000 | 21.23374 | 21.30969 | -0.5372 | 14.74712 |
April | 485.00000 | 21.32900 | 25.84129 | -0.4597 | 14.19275 |
May | 508.00000 | 23.30403 | 27.41698 | -0.8930 | 24.78271 |
June | 496.00000 | 24.22632 | 33.60060 | -0.4205 | 9.58070 |
July | 497.00000 | 24.32328 | 35.66210 | -0.3780 | 9.13821 |
August | 514.00000 | 24.11008 | 35.05402 | -0.4792 | 10.76545 |
September | 485.00000 | 23.67613 | 26.50632 | -0.7383 | 19.55056 |
October | 502.00000 | 21.66806 | 23.83237 | -0.3975 | 11.67797 |
November | 489.00000 | 20.81124 | 25.79427 | -0.6341 | 15.79254 |
December | 497.00000 | 20.12033 | 17.91283 | -0.8893 | 24.34340 |
Annual Sum or Average | 5943.00000 | 22.14864 | 26.67426 | -0.6125 | 16.20361 |
Minimum of Months | 454.00000 | 20.12033 | 17.91283 | -0.8930 | 9.13821 |
Maximum of Months | 514.00000 | 24.32328 | 35.66210 | -0.3780 | 24.78271 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.72973 | 23.37750 | -0.6499 | 16.84058 |
February | 454.00000 | 20.98751 | 20.83466 | -0.5976 | 16.83063 |
March | 514.00000 | 21.74932 | 19.86193 | -0.3695 | 13.09760 |
April | 485.00000 | 21.70407 | 24.57613 | -0.3244 | 13.40241 |
May | 508.00000 | 23.51704 | 26.37759 | -0.7404 | 20.23574 |
June | 496.00000 | 24.30738 | 33.08829 | -0.2779 | 8.19958 |
July | 497.00000 | 24.43680 | 35.22170 | -0.2349 | 8.47391 |
August | 514.00000 | 24.19318 | 34.32537 | -0.3274 | 9.18933 |
September | 485.00000 | 23.86891 | 25.60658 | -0.5721 | 15.57526 |
October | 502.00000 | 22.14040 | 22.31011 | -0.2519 | 11.33596 |
November | 489.00000 | 21.20844 | 24.46750 | -0.5105 | 13.46677 |
December | 497.00000 | 20.37779 | 17.15658 | -0.7970 | 21.51725 |
Annual Sum or Average | 5943.00000 | 22.44882 | 25.64247 | -0.4700 | 13.98839 |
Minimum of Months | 454.00000 | 20.37779 | 17.15658 | -0.7970 | 8.19958 |
Maximum of Months | 514.00000 | 24.43680 | 35.22170 | -0.2349 | 21.51725 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.00049 | 21.19367 | -0.2904 | 13.42018 |
February | 454.00000 | 21.89610 | 19.28382 | -0.3305 | 14.96112 |
March | 514.00000 | 22.06850 | 19.16073 | -0.2729 | 13.05397 |
April | 485.00000 | 21.68116 | 24.41989 | -0.3385 | 13.79750 |
May | 508.00000 | 23.31674 | 26.79159 | -0.8467 | 24.10079 |
June | 496.00000 | 24.13301 | 33.63147 | -0.4213 | 10.38240 |
July | 497.00000 | 24.27518 | 35.57887 | -0.3569 | 9.67517 |
August | 514.00000 | 24.15119 | 34.53736 | -0.3819 | 10.06874 |
September | 485.00000 | 23.94650 | 25.32970 | -0.5292 | 15.61987 |
October | 502.00000 | 22.57777 | 21.21030 | -0.1018 | 12.38036 |
November | 489.00000 | 22.33875 | 22.28832 | -0.1864 | 12.12985 |
December | 497.00000 | 21.51471 | 15.71258 | -0.4678 | 17.01415 |
Annual Sum or Average | 5943.00000 | 22.83385 | 24.97950 | -0.3777 | 13.87947 |
Minimum of Months | 454.00000 | 21.51471 | 15.71258 | -0.8467 | 9.67517 |
Maximum of Months | 514.00000 | 24.27518 | 35.57887 | -0.1018 | 24.10079 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.75421 | 22.91883 | -0.6473 | 17.76530 |
February | 454.00000 | 20.91486 | 20.56127 | -0.6215 | 17.71795 |
March | 514.00000 | 21.44036 | 19.91698 | -0.4455 | 14.27998 |
April | 485.00000 | 21.37734 | 24.88360 | -0.4075 | 14.38237 |
May | 508.00000 | 23.14383 | 27.05796 | -0.8686 | 25.78798 |
June | 496.00000 | 24.06808 | 33.83435 | -0.3795 | 10.82236 |
July | 497.00000 | 24.13867 | 35.96014 | -0.3669 | 10.26141 |
August | 514.00000 | 23.98825 | 35.13467 | -0.4281 | 11.30741 |
September | 485.00000 | 23.56765 | 26.23953 | -0.6847 | 19.94661 |
October | 502.00000 | 21.79714 | 22.48524 | -0.3213 | 12.28474 |
November | 489.00000 | 21.16135 | 24.12533 | -0.5213 | 14.25295 |
December | 497.00000 | 20.43240 | 16.78964 | -0.7909 | 22.03377 |
Annual Sum or Average | 5943.00000 | 22.24454 | 25.87248 | -0.5396 | 15.88745 |
Minimum of Months | 454.00000 | 20.43240 | 16.78964 | -0.8686 | 10.26141 |
Maximum of Months | 514.00000 | 24.13867 | 35.96014 | -0.3213 | 25.78798 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.57039 | 24.45338 | -0.7052 | 16.97987 |
February | 454.00000 | 20.56849 | 22.12489 | -0.7295 | 17.72218 |
March | 514.00000 | 21.12834 | 21.63831 | -0.5627 | 13.55955 |
April | 485.00000 | 21.36137 | 26.20525 | -0.4560 | 11.23417 |
May | 508.00000 | 23.21060 | 28.25463 | -0.9619 | 26.40625 |
June | 496.00000 | 24.14841 | 33.85904 | -0.4993 | 10.55090 |
July | 497.00000 | 24.23680 | 35.76912 | -0.4541 | 9.75451 |
August | 514.00000 | 24.13998 | 34.88792 | -0.5016 | 10.64566 |
September | 485.00000 | 23.95089 | 26.24485 | -0.6499 | 15.33288 |
October | 502.00000 | 22.37170 | 23.02809 | -0.2081 | 7.76369 |
November | 489.00000 | 21.36194 | 25.12508 | -0.4675 | 10.79707 |
December | 497.00000 | 20.50314 | 17.91474 | -0.7563 | 18.78859 |
Annual Sum or Average | 5943.00000 | 22.31024 | 26.66796 | -0.5787 | 14.11862 |
Minimum of Months | 454.00000 | 20.50314 | 17.91474 | -0.9619 | 7.76369 |
Maximum of Months | 514.00000 | 24.23680 | 35.76912 | -0.2081 | 26.40625 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.12881 | 23.51949 | -0.5405 | 12.90406 |
February | 454.00000 | 21.28478 | 21.03701 | -0.5214 | 13.99903 |
March | 514.00000 | 21.95829 | 20.23333 | -0.3251 | 10.90332 |
April | 485.00000 | 22.09783 | 24.62953 | -0.2431 | 9.65615 |
May | 508.00000 | 23.68545 | 26.68910 | -0.7309 | 18.68610 |
June | 496.00000 | 24.35143 | 32.93977 | -0.3152 | 7.95017 |
July | 497.00000 | 24.48685 | 34.95628 | -0.2675 | 7.85885 |
August | 514.00000 | 24.34010 | 33.79739 | -0.3091 | 8.08525 |
September | 485.00000 | 24.24941 | 25.19837 | -0.4478 | 11.00066 |
October | 502.00000 | 22.95776 | 21.45555 | -0.0358 | 8.12640 |
November | 489.00000 | 21.97977 | 23.83137 | -0.2959 | 9.02627 |
December | 497.00000 | 20.95210 | 17.28102 | -0.6241 | 15.43007 |
Annual Sum or Average | 5943.00000 | 22.80200 | 25.50534 | -0.3874 | 11.12498 |
Minimum of Months | 454.00000 | 20.95210 | 17.28102 | -0.7309 | 7.85885 |
Maximum of Months | 514.00000 | 24.48685 | 34.95628 | -0.0358 | 18.68610 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.86303 | 20.30037 | -0.2609 | 11.94751 |
February | 454.00000 | 21.45426 | 18.51105 | -0.3783 | 14.86614 |
March | 514.00000 | 21.65796 | 18.77409 | -0.3391 | 12.53513 |
April | 485.00000 | 21.42142 | 24.11401 | -0.3819 | 11.46165 |
May | 508.00000 | 22.92189 | 27.17526 | -0.9958 | 28.71789 |
June | 496.00000 | 24.07861 | 33.11980 | -0.4982 | 11.42900 |
July | 497.00000 | 24.22647 | 35.34023 | -0.4233 | 10.06498 |
August | 514.00000 | 24.22217 | 33.58516 | -0.3893 | 9.76307 |
September | 485.00000 | 24.17799 | 24.49917 | -0.4404 | 12.38454 |
October | 502.00000 | 22.90615 | 20.07691 | 0.02843 | 11.10305 |
November | 489.00000 | 22.40622 | 21.06327 | -0.0965 | 11.15869 |
December | 497.00000 | 21.30731 | 14.59476 | -0.4348 | 15.87789 |
Annual Sum or Average | 5943.00000 | 22.73039 | 24.31660 | -0.3851 | 13.45364 |
Minimum of Months | 454.00000 | 21.30731 | 14.59476 | -0.9958 | 9.76307 |
Maximum of Months | 514.00000 | 24.22647 | 35.34023 | 0.02843 | 28.71789 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.10616 | 23.13661 | -0.5459 | 13.47989 |
February | 454.00000 | 21.14132 | 20.86698 | -0.5562 | 14.48801 |
March | 514.00000 | 21.64873 | 20.33112 | -0.4023 | 11.78355 |
April | 485.00000 | 21.74730 | 25.06755 | -0.3323 | 10.30240 |
May | 508.00000 | 23.38168 | 27.34595 | -0.8435 | 22.97491 |
June | 496.00000 | 24.22587 | 33.49967 | -0.3852 | 9.39076 |
July | 497.00000 | 24.26695 | 35.62760 | -0.3797 | 9.08129 |
August | 514.00000 | 24.24467 | 34.45259 | -0.3819 | 9.10874 |
September | 485.00000 | 24.13508 | 25.58988 | -0.5096 | 12.77044 |
October | 502.00000 | 22.75431 | 21.64868 | -0.0770 | 8.17425 |
November | 489.00000 | 21.88577 | 23.63575 | -0.3145 | 9.20820 |
December | 497.00000 | 20.90514 | 17.00134 | -0.6359 | 16.13873 |
Annual Sum or Average | 5943.00000 | 22.63249 | 25.72868 | -0.4467 | 12.24014 |
Minimum of Months | 454.00000 | 20.90514 | 17.00134 | -0.8435 | 8.17425 |
Maximum of Months | 514.00000 | 24.26695 | 35.62760 | -0.0770 | 22.97491 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.76646 | 24.15994 | -0.6335 | 15.54442 |
February | 454.00000 | 20.79138 | 21.79188 | -0.6441 | 16.03860 |
March | 514.00000 | 21.57596 | 21.11849 | -0.4272 | 11.87127 |
April | 485.00000 | 21.81730 | 25.28412 | -0.3275 | 10.34891 |
May | 508.00000 | 23.62102 | 27.01190 | -0.7839 | 19.96550 |
June | 496.00000 | 24.28316 | 33.55191 | -0.4120 | 9.05243 |
July | 497.00000 | 24.37368 | 35.52930 | -0.3709 | 8.59489 |
August | 514.00000 | 24.21329 | 34.85352 | -0.4519 | 9.79524 |
September | 485.00000 | 23.93170 | 26.31689 | -0.6491 | 15.78189 |
October | 502.00000 | 22.26149 | 23.20101 | -0.2344 | 8.57371 |
November | 489.00000 | 21.31588 | 25.19405 | -0.4784 | 11.44602 |
December | 497.00000 | 20.45938 | 17.82448 | -0.7611 | 19.50108 |
Annual Sum or Average | 5943.00000 | 22.46554 | 26.36132 | -0.5137 | 13.02240 |
Minimum of Months | 454.00000 | 20.45938 | 17.82448 | -0.7839 | 8.57371 |
Maximum of Months | 514.00000 | 24.37368 | 35.52930 | -0.2344 | 19.96550 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.03884 | 22.54497 | -0.5486 | 13.53863 |
February | 385.00000 | 21.18783 | 20.15448 | -0.5213 | 14.73413 |
March | 433.00000 | 21.88009 | 19.37499 | -0.3182 | 11.62218 |
April | 410.00000 | 21.96671 | 23.99873 | -0.2520 | 10.67179 |
May | 430.00000 | 23.71684 | 26.20384 | -0.6837 | 17.92060 |
June | 418.00000 | 24.40992 | 32.86696 | -0.2824 | 8.15586 |
July | 422.00000 | 24.56205 | 34.82365 | -0.2320 | 8.33379 |
August | 433.00000 | 24.31699 | 34.20686 | -0.3251 | 8.97301 |
September | 410.00000 | 24.05630 | 25.48930 | -0.5290 | 13.98442 |
October | 427.00000 | 22.45414 | 21.57575 | -0.1576 | 9.53854 |
November | 417.00000 | 21.56609 | 23.52858 | -0.3983 | 10.69988 |
December | 422.00000 | 20.63490 | 16.49919 | -0.7008 | 18.08053 |
Annual Sum or Average | 5034.00000 | 22.65978 | 25.14218 | -0.4117 | 12.17264 |
Minimum of Months | 385.00000 | 20.63490 | 16.49919 | -0.7008 | 8.15586 |
Maximum of Months | 433.00000 | 24.56205 | 34.82365 | -0.1576 | 18.08053 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.49224 | 20.65239 | -0.1435 | 10.71515 |
February | 454.00000 | 22.30324 | 18.81036 | -0.2039 | 12.54054 |
March | 514.00000 | 22.41471 | 18.91877 | -0.1666 | 10.90380 |
April | 485.00000 | 22.17589 | 23.83261 | -0.2078 | 10.16865 |
May | 508.00000 | 23.65741 | 26.42359 | -0.7334 | 19.05979 |
June | 496.00000 | 24.24351 | 33.48457 | -0.4001 | 9.33264 |
July | 497.00000 | 24.37459 | 35.36762 | -0.3385 | 8.71871 |
August | 514.00000 | 24.28446 | 34.28687 | -0.3502 | 8.87388 |
September | 485.00000 | 24.18290 | 25.20494 | -0.4505 | 12.45252 |
October | 502.00000 | 23.05621 | 20.65177 | 0.03387 | 10.38330 |
November | 489.00000 | 22.83037 | 21.65924 | -0.0395 | 10.10636 |
December | 497.00000 | 22.00882 | 15.40413 | -0.3170 | 13.38934 |
Annual Sum or Average | 5943.00000 | 23.17647 | 24.61080 | -0.2774 | 11.38531 |
Minimum of Months | 454.00000 | 22.00882 | 15.40413 | -0.7334 | 8.71871 |
Maximum of Months | 514.00000 | 24.37459 | 35.36762 | 0.03387 | 19.05979 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.16112 | 22.51539 | -0.5127 | 13.59546 |
February | 454.00000 | 21.22440 | 20.26212 | -0.5095 | 14.50246 |
March | 514.00000 | 21.75557 | 19.79751 | -0.3427 | 11.72919 |
April | 485.00000 | 21.82963 | 24.36635 | -0.2839 | 10.69841 |
May | 508.00000 | 23.50523 | 26.70668 | -0.7497 | 20.47959 |
June | 496.00000 | 24.19696 | 33.66434 | -0.3543 | 9.48262 |
July | 497.00000 | 24.25738 | 35.73330 | -0.3432 | 9.04141 |
August | 514.00000 | 24.15901 | 34.86616 | -0.3854 | 9.66620 |
September | 485.00000 | 23.87844 | 26.08562 | -0.5836 | 15.72403 |
October | 502.00000 | 22.30101 | 21.97584 | -0.1777 | 9.48649 |
November | 489.00000 | 21.61447 | 23.60441 | -0.3776 | 10.62676 |
December | 497.00000 | 20.76991 | 16.62817 | -0.6656 | 17.64786 |
Annual Sum or Average | 5943.00000 | 22.56651 | 25.56464 | -0.4401 | 12.71268 |
Minimum of Months | 454.00000 | 20.76991 | 16.62817 | -0.7497 | 9.04141 |
Maximum of Months | 514.00000 | 24.25738 | 35.73330 | -0.1777 | 20.47959 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.816085E+09 | 0.216619E+09 | 24.67 | 0.815857E+09 | 227526.42 | 0.00 | 0.72 | 20-JAN-14:00 | 0.00 | 01-JAN-00:05 | 22588.17 | 20-JAN-14:00 | 22588.17 | 20-JAN-14:00 | 96.86 | 19-JAN-12:30 | 5582.29 | 20-JAN-14:00 | 0.00 |
February | 0.234037E+09 | 65205417.06 | 12.71 | 0.233635E+09 | 401666.29 | 0.00 | 0.41 | 18-FEB-13:40 | 0.00 | 01-FEB-00:10 | 11686.73 | 18-FEB-13:40 | 11686.73 | 18-FEB-13:40 | 169.13 | 18-FEB-17:10 | 3139.12 | 18-FEB-13:40 | 0.00 |
March | 0.302106E+10 | 0.759935E+09 | 74.50 | 0.302063E+10 | 431718.14 | 0.00 | 1.00 | 13-MAR-14:00 | 0.00 | 01-MAR-00:10 | 39433.80 | 14-MAR-13:00 | 39433.80 | 14-MAR-13:00 | 219.68 | 31-MAR-17:40 | 9048.66 | 14-MAR-13:00 | 0.00 |
April | 0.259253E+10 | 0.692284E+09 | 84.53 | 0.255372E+10 | 38813922.94 | 0.00 | 0.74 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 23355.82 | 20-APR-13:00 | 23355.82 | 20-APR-13:00 | 2969.38 | 28-APR-14:00 | 5739.69 | 20-APR-13:00 | 0.00 |
May | 0.138293E+11 | 0.347377E+10 | 216.51 | 0.135099E+11 | 0.319469E+09 | 0.00 | 1.00 | 10-MAY-12:20 | 0.00 | 01-MAY-00:10 | 49868.09 | 17-MAY-13:00 | 49868.09 | 17-MAY-13:00 | 3307.65 | 31-MAY-07:40 | 12989.03 | 17-MAY-13:00 | 0.00 |
June | 0.543108E+11 | 0.143856E+11 | 436.36 | 0.517817E+11 | 0.252909E+10 | 0.00 | 1.00 | 01-JUN-10:20 | 0.00 | 01-JUN-00:10 | 77071.95 | 26-JUN-16:00 | 77071.95 | 26-JUN-16:00 | 22559.68 | 21-JUN-06:03 | 26926.65 | 26-JUN-15:50 | 0.00 |
July | 0.554180E+11 | 0.144554E+11 | 445.00 | 0.510783E+11 | 0.433965E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 75427.11 | 17-JUL-12:07 | 75427.11 | 17-JUL-12:07 | 32503.97 | 31-JUL-15:40 | 24128.23 | 17-JUL-12:07 | 0.00 |
August | 0.547536E+11 | 0.142191E+11 | 438.00 | 0.519367E+11 | 0.281693E+10 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 72403.09 | 16-AUG-16:00 | 72403.09 | 16-AUG-16:00 | 33705.60 | 04-AUG-06:03 | 23894.36 | 16-AUG-16:00 | 0.00 |
September | 0.376041E+11 | 0.946019E+10 | 362.87 | 0.370978E+11 | 0.506299E+09 | 0.00 | 1.00 | 01-SEP-10:00 | 0.00 | 01-SEP-00:10 | 65940.66 | 12-SEP-16:00 | 65940.66 | 12-SEP-16:00 | 9357.29 | 01-SEP-14:00 | 18213.40 | 12-SEP-16:00 | 0.00 |
October | 0.656032E+10 | 0.163358E+10 | 112.05 | 0.654200E+10 | 18323981.92 | 0.00 | 1.00 | 10-OCT-10:20 | 0.00 | 01-OCT-00:10 | 54783.53 | 11-OCT-15:20 | 54783.53 | 11-OCT-15:20 | 1594.36 | 09-OCT-10:02 | 13068.14 | 11-OCT-14:00 | 0.00 |
November | 0.198186E+10 | 0.503872E+09 | 40.92 | 0.198183E+10 | 31907.75 | 0.00 | 0.96 | 07-NOV-15:00 | 0.00 | 01-NOV-00:10 | 31950.67 | 07-NOV-15:00 | 31950.67 | 07-NOV-15:00 | 31.96 | 09-NOV-08:45 | 7388.79 | 07-NOV-15:00 | 0.00 |
December | 0.879480E+09 | 0.236497E+09 | 32.00 | 0.878970E+09 | 510428.77 | 0.00 | 0.68 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 | 20851.60 | 01-DEC-14:00 | 20851.60 | 01-DEC-14:00 | 121.44 | 03-DEC-15:15 | 5219.59 | 01-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.232001E+12 | 0.601021E+11 | 2280.13 | 0.221431E+12 | 0.105702E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.234037E+09 | 65205417.06 | 12.71 | 0.233635E+09 | 31907.75 | 0.00 | 0.41 | 0.00 | 11686.73 | 11686.73 | 31.96 | 3139.12 | 0.00 | ||||||
Maximum of Months | 0.554180E+11 | 0.144554E+11 | 445.00 | 0.519367E+11 | 0.433965E+10 | 0.00 | 1.00 | 0.00 | 77071.95 | 77071.95 | 33705.60 | 26926.65 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.958357E+09 | 0.251256E+09 | 28.33 | 0.958303E+09 | 54467.62 | 0.00 | 0.75 | 20-JAN-14:00 | 0.00 | 01-JAN-00:05 | 21124.30 | 20-JAN-14:00 | 21124.30 | 20-JAN-14:00 | 50.13 | 19-JAN-12:00 | 5186.68 | 20-JAN-14:00 | 0.00 |
February | 0.347257E+09 | 94917123.45 | 17.67 | 0.347139E+09 | 118112.79 | 0.00 | 0.60 | 18-FEB-13:20 | 0.00 | 01-FEB-00:10 | 16183.62 | 18-FEB-13:20 | 16183.62 | 18-FEB-13:20 | 76.88 | 18-FEB-17:05 | 4139.18 | 18-FEB-13:20 | 0.00 |
March | 0.308452E+10 | 0.772387E+09 | 77.67 | 0.308430E+10 | 224281.48 | 0.00 | 1.00 | 13-MAR-13:40 | 0.00 | 01-MAR-00:10 | 36528.68 | 13-MAR-16:00 | 36528.68 | 13-MAR-16:00 | 152.43 | 31-MAR-17:50 | 8339.27 | 13-MAR-16:00 | 0.00 |
April | 0.247977E+10 | 0.657893E+09 | 84.73 | 0.244544E+10 | 34332507.37 | 0.00 | 0.82 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 23663.25 | 20-APR-13:00 | 23663.25 | 20-APR-13:00 | 2742.46 | 28-APR-14:00 | 5693.03 | 20-APR-13:00 | 0.00 |
May | 0.133084E+11 | 0.332983E+10 | 227.54 | 0.130025E+11 | 0.305884E+09 | 0.00 | 1.00 | 04-MAY-14:30 | 0.00 | 01-MAY-00:10 | 48285.16 | 31-MAY-16:00 | 48285.16 | 31-MAY-16:00 | 2947.96 | 31-MAY-07:50 | 12358.77 | 17-MAY-13:30 | 0.00 |
June | 0.506590E+11 | 0.134098E+11 | 437.81 | 0.483836E+11 | 0.227543E+10 | 0.00 | 1.00 | 01-JUN-10:10 | 0.00 | 01-JUN-00:10 | 74917.47 | 26-JUN-15:20 | 74917.47 | 26-JUN-15:20 | 17084.44 | 22-JUN-13:20 | 26549.01 | 26-JUN-15:00 | 0.00 |
July | 0.515793E+11 | 0.134622E+11 | 443.11 | 0.476994E+11 | 0.387988E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 72698.77 | 31-JUL-14:40 | 70495.34 | 17-JUL-10:30 | 32209.18 | 31-JUL-15:50 | 22036.49 | 17-JUL-13:00 | 0.00 |
August | 0.490993E+11 | 0.127805E+11 | 433.15 | 0.466642E+11 | 0.243508E+10 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 70511.13 | 16-AUG-15:10 | 70511.13 | 16-AUG-15:10 | 18210.30 | 21-AUG-16:00 | 22668.85 | 16-AUG-15:10 | 0.00 |
September | 0.322604E+11 | 0.814747E+10 | 356.77 | 0.318355E+11 | 0.424904E+09 | 0.00 | 1.00 | 01-SEP-10:00 | 0.00 | 01-SEP-00:10 | 62828.51 | 12-SEP-15:50 | 62828.51 | 12-SEP-15:50 | 8812.09 | 01-SEP-14:00 | 17209.14 | 12-SEP-15:50 | 0.00 |
October | 0.584440E+10 | 0.145987E+10 | 111.66 | 0.583150E+10 | 12899757.12 | 0.00 | 1.00 | 09-OCT-14:31 | 0.00 | 01-OCT-00:10 | 50102.30 | 11-OCT-15:00 | 50102.30 | 11-OCT-15:00 | 795.29 | 01-OCT-10:23 | 12070.75 | 11-OCT-14:40 | 0.00 |
November | 0.180010E+10 | 0.462096E+09 | 43.17 | 0.179981E+10 | 291360.17 | 0.00 | 0.95 | 07-NOV-14:50 | 0.00 | 01-NOV-00:10 | 28375.42 | 07-NOV-14:50 | 28375.42 | 07-NOV-14:50 | 154.98 | 09-NOV-08:55 | 6580.67 | 07-NOV-14:50 | 0.00 |
December | 0.936471E+09 | 0.249337E+09 | 32.33 | 0.936397E+09 | 74421.23 | 0.00 | 0.73 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 | 20679.31 | 01-DEC-14:00 | 20679.31 | 01-DEC-14:00 | 61.11 | 03-DEC-15:53 | 5095.78 | 01-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.212357E+12 | 0.550776E+11 | 2293.93 | 0.202988E+12 | 0.936917E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.347257E+09 | 94917123.45 | 17.67 | 0.347139E+09 | 54467.62 | 0.00 | 0.60 | 0.00 | 16183.62 | 16183.62 | 50.13 | 4139.18 | 0.00 | ||||||
Maximum of Months | 0.515793E+11 | 0.134622E+11 | 443.11 | 0.483836E+11 | 0.387988E+10 | 0.00 | 1.00 | 0.00 | 74917.47 | 74917.47 | 32209.18 | 26549.01 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.815330E+09 | 0.217956E+09 | 25.17 | 0.815304E+09 | 25596.71 | 0.00 | 0.69 | 20-JAN-14:00 | 0.00 | 01-JAN-00:05 | 22604.83 | 20-JAN-14:00 | 22604.83 | 20-JAN-14:00 | 28.70 | 19-JAN-12:02 | 5635.25 | 20-JAN-14:00 | 0.00 |
February | 0.276175E+09 | 76432547.86 | 13.17 | 0.275781E+09 | 394035.29 | 0.00 | 0.48 | 18-FEB-13:30 | 0.00 | 01-FEB-00:10 | 14690.72 | 18-FEB-13:30 | 14690.72 | 18-FEB-13:30 | 155.90 | 18-FEB-17:10 | 3877.26 | 18-FEB-13:30 | 0.00 |
March | 0.297972E+10 | 0.755710E+09 | 72.92 | 0.297924E+10 | 478073.51 | 0.00 | 1.00 | 13-MAR-14:30 | 0.00 | 01-MAR-00:10 | 38095.42 | 14-MAR-13:10 | 38095.42 | 14-MAR-13:10 | 194.41 | 31-MAR-17:50 | 8709.75 | 14-MAR-13:10 | 0.00 |
April | 0.262171E+10 | 0.700207E+09 | 83.07 | 0.257705E+10 | 44655102.19 | 0.00 | 0.77 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 25904.82 | 20-APR-13:00 | 25904.82 | 20-APR-13:00 | 3025.45 | 28-APR-14:00 | 6312.01 | 20-APR-13:00 | 0.00 |
May | 0.141103E+11 | 0.356534E+10 | 225.28 | 0.136860E+11 | 0.424316E+09 | 0.00 | 1.00 | 04-MAY-14:30 | 0.00 | 01-MAY-00:10 | 57888.51 | 31-MAY-15:20 | 57888.51 | 31-MAY-15:20 | 3529.57 | 31-MAY-08:00 | 14669.50 | 31-MAY-15:20 | 0.00 |
June | 0.554428E+11 | 0.148056E+11 | 433.68 | 0.529720E+11 | 0.247084E+10 | 0.00 | 1.00 | 01-JUN-10:30 | 0.00 | 01-JUN-00:10 | 87607.57 | 26-JUN-15:10 | 87607.57 | 26-JUN-15:10 | 17758.55 | 22-JUN-13:20 | 31113.69 | 26-JUN-15:00 | 0.00 |
July | 0.557283E+11 | 0.146905E+11 | 441.50 | 0.517042E+11 | 0.402402E+10 | 0.00 | 1.00 | 01-JUL-08:50 | 0.00 | 01-JUL-00:10 | 80304.70 | 31-JUL-14:10 | 80195.02 | 17-JUL-14:00 | 33029.92 | 31-JUL-15:40 | 25126.39 | 17-JUL-13:30 | 0.00 |
August | 0.529644E+11 | 0.139308E+11 | 426.78 | 0.504413E+11 | 0.252311E+10 | 0.00 | 1.00 | 02-AUG-09:50 | 0.00 | 01-AUG-00:10 | 84068.93 | 16-AUG-15:10 | 84068.93 | 16-AUG-15:10 | 17823.60 | 21-AUG-16:00 | 27025.88 | 16-AUG-15:10 | 0.00 |
September | 0.332050E+11 | 0.848851E+10 | 353.41 | 0.326536E+11 | 0.551413E+09 | 0.00 | 1.00 | 01-SEP-10:50 | 0.00 | 01-SEP-00:10 | 70940.37 | 12-SEP-15:50 | 70940.37 | 12-SEP-15:50 | 8133.45 | 01-SEP-14:00 | 19433.54 | 12-SEP-15:50 | 0.00 |
October | 0.544889E+10 | 0.138577E+10 | 104.68 | 0.542783E+10 | 21054538.84 | 0.00 | 1.00 | 10-OCT-12:30 | 0.00 | 01-OCT-00:10 | 55732.29 | 11-OCT-15:00 | 55732.29 | 11-OCT-15:00 | 1012.16 | 01-OCT-11:32 | 13469.76 | 11-OCT-14:40 | 0.00 |
November | 0.158250E+10 | 0.415724E+09 | 40.37 | 0.158086E+10 | 1635573.08 | 0.00 | 0.81 | 07-NOV-14:30 | 0.00 | 01-NOV-00:10 | 27357.12 | 07-NOV-14:30 | 27357.12 | 07-NOV-14:30 | 412.89 | 09-NOV-09:15 | 6600.25 | 07-NOV-14:30 | 0.00 |
December | 0.852803E+09 | 0.231048E+09 | 30.83 | 0.852402E+09 | 401359.35 | 0.00 | 0.62 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 | 19965.40 | 01-DEC-14:00 | 19965.40 | 01-DEC-14:00 | 124.57 | 03-DEC-15:43 | 5071.02 | 01-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.226028E+12 | 0.592635E+11 | 2250.86 | 0.215966E+12 | 0.100623E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.276175E+09 | 76432547.86 | 13.17 | 0.275781E+09 | 25596.71 | 0.00 | 0.48 | 0.00 | 14690.72 | 14690.72 | 28.70 | 3877.26 | 0.00 | ||||||
Maximum of Months | 0.557283E+11 | 0.148056E+11 | 441.50 | 0.529720E+11 | 0.402402E+10 | 0.00 | 1.00 | 0.00 | 87607.57 | 87607.57 | 33029.92 | 31113.69 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 351.98 | 0.00 | 351.98 | 75.00 | 1664.18 | 0.00 | 0.00 | 0.00 |
February | 442.39 | 0.00 | 442.39 | 91.25 | 1695.53 | 0.00 | 0.00 | 0.00 |
March | 601.95 | 0.00 | 601.95 | 283.08 | 1282.14 | 0.00 | 0.00 | 0.00 |
April | 755.96 | 4.19 | 751.77 | 428.20 | 1083.93 | 0.00 | 0.00 | 0.00 |
May | 1032.69 | 34.14 | 998.56 | 940.01 | 666.67 | 0.00 | 0.00 | 0.00 |
June | 1132.42 | 125.55 | 1006.87 | 1504.99 | 381.09 | 0.00 | 0.00 | 0.00 |
July | 1070.96 | 69.33 | 1001.64 | 1440.53 | 361.60 | 0.00 | 0.00 | 0.00 |
August | 852.40 | 20.16 | 832.24 | 1095.95 | 412.08 | 0.00 | 0.00 | 0.00 |
September | 716.02 | 0.17 | 715.85 | 814.63 | 625.86 | 0.00 | 0.00 | 0.00 |
October | 512.84 | 0.00 | 512.84 | 291.78 | 1265.32 | 0.00 | 0.00 | 0.00 |
November | 389.31 | 0.00 | 389.31 | 119.61 | 1504.71 | 0.00 | 0.00 | 0.00 |
December | 329.32 | 0.00 | 329.32 | 64.16 | 1880.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 683.60 | 21.18 | 662.43 | 598.59 | 1065.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 329.32 | 0.00 | 329.32 | 64.16 | 361.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1132.42 | 125.55 | 1006.87 | 1504.99 | 1880.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 734.76 | 450.28 | 284.48 | 665.96 | 1036.88 | 0.00 | 0.00 | 0.00 |
February | 976.05 | 616.17 | 359.87 | 926.37 | 1078.54 | 0.00 | 0.00 | 0.00 |
March | 1178.06 | 687.15 | 490.91 | 1200.19 | 820.60 | 0.00 | 0.00 | 0.00 |
April | 1208.16 | 588.52 | 619.65 | 1206.33 | 702.94 | 0.00 | 0.00 | 0.00 |
May | 1412.33 | 589.93 | 822.39 | 1602.35 | 447.47 | 0.00 | 0.00 | 0.00 |
June | 1723.18 | 904.62 | 818.56 | 2312.43 | 254.31 | 0.00 | 0.00 | 0.00 |
July | 1566.51 | 745.93 | 820.58 | 2120.72 | 241.16 | 0.00 | 0.00 | 0.00 |
August | 1580.04 | 870.23 | 709.81 | 2126.15 | 274.27 | 0.00 | 0.00 | 0.00 |
September | 1314.67 | 714.17 | 600.51 | 1679.24 | 399.72 | 0.00 | 0.00 | 0.00 |
October | 952.09 | 521.69 | 430.40 | 1004.46 | 823.85 | 0.00 | 0.00 | 0.00 |
November | 741.08 | 418.42 | 322.66 | 706.18 | 965.38 | 0.00 | 0.00 | 0.00 |
December | 641.57 | 369.59 | 271.98 | 556.20 | 1184.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1169.78 | 622.75 | 547.03 | 1344.17 | 683.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 641.57 | 369.59 | 271.98 | 556.20 | 241.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1723.18 | 904.62 | 822.39 | 2312.43 | 1184.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3373.25 | 2774.86 | 598.39 | 3871.42 | 1512.30 | 0.00 | 0.00 | 0.00 |
February | 3235.57 | 2579.60 | 655.97 | 3671.07 | 1582.06 | 0.00 | 0.00 | 0.00 |
March | 2385.51 | 1569.53 | 815.98 | 2743.93 | 1259.50 | 0.00 | 0.00 | 0.00 |
April | 1545.04 | 621.26 | 923.77 | 1624.73 | 1116.25 | 0.00 | 0.00 | 0.00 |
May | 1415.86 | 259.52 | 1156.34 | 1620.09 | 728.40 | 0.00 | 0.00 | 0.00 |
June | 1305.38 | 238.58 | 1066.79 | 1883.31 | 415.38 | 0.00 | 0.00 | 0.00 |
July | 1358.86 | 243.33 | 1115.53 | 1964.93 | 385.96 | 0.00 | 0.00 | 0.00 |
August | 1730.11 | 723.25 | 1006.86 | 2514.22 | 433.78 | 0.00 | 0.00 | 0.00 |
September | 2225.95 | 1242.07 | 983.89 | 3033.66 | 643.51 | 0.00 | 0.00 | 0.00 |
October | 2661.59 | 1888.45 | 773.13 | 3230.63 | 1260.21 | 0.00 | 0.00 | 0.00 |
November | 3242.77 | 2584.96 | 657.81 | 3800.44 | 1442.53 | 0.00 | 0.00 | 0.00 |
December | 3100.93 | 2509.85 | 591.08 | 3486.07 | 1698.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2293.09 | 1429.77 | 863.32 | 2781.98 | 1036.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1305.38 | 238.58 | 591.08 | 1620.09 | 385.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3373.25 | 2774.86 | 1156.34 | 3871.42 | 1698.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 781.62 | 495.28 | 286.34 | 756.94 | 1064.94 | 0.00 | 0.00 | 0.00 |
February | 942.52 | 584.08 | 358.44 | 899.03 | 1094.47 | 0.00 | 0.00 | 0.00 |
March | 1103.63 | 608.90 | 494.74 | 1119.14 | 837.91 | 0.00 | 0.00 | 0.00 |
April | 1039.12 | 439.95 | 599.18 | 1009.51 | 721.85 | 0.00 | 0.00 | 0.00 |
May | 1270.08 | 447.75 | 822.33 | 1449.06 | 473.75 | 0.00 | 0.00 | 0.00 |
June | 1553.38 | 747.39 | 805.99 | 2118.09 | 285.25 | 0.00 | 0.00 | 0.00 |
July | 1265.64 | 463.58 | 802.06 | 1731.88 | 260.61 | 0.00 | 0.00 | 0.00 |
August | 1320.97 | 652.57 | 668.39 | 1782.18 | 290.26 | 0.00 | 0.00 | 0.00 |
September | 1171.30 | 561.72 | 609.59 | 1513.20 | 426.84 | 0.00 | 0.00 | 0.00 |
October | 985.37 | 563.21 | 422.16 | 1078.56 | 839.35 | 0.00 | 0.00 | 0.00 |
November | 808.55 | 490.89 | 317.66 | 803.87 | 979.17 | 0.00 | 0.00 | 0.00 |
December | 653.09 | 385.80 | 267.29 | 578.88 | 1190.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1074.94 | 536.12 | 538.83 | 1238.11 | 703.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 653.09 | 385.80 | 267.29 | 578.88 | 260.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1553.38 | 747.39 | 822.33 | 2118.09 | 1190.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.32 | 0.00 | 117.32 | 24.87 | 573.14 | 0.00 | 0.00 | 0.00 |
February | 147.46 | 0.00 | 147.46 | 32.02 | 576.99 | 0.00 | 0.00 | 0.00 |
March | 200.64 | 0.00 | 200.64 | 100.85 | 433.82 | 0.00 | 0.00 | 0.00 |
April | 251.98 | 1.40 | 250.58 | 149.77 | 374.13 | 0.00 | 0.00 | 0.00 |
May | 344.21 | 11.38 | 332.84 | 323.32 | 220.87 | 0.00 | 0.00 | 0.00 |
June | 377.46 | 41.85 | 335.61 | 511.38 | 124.43 | 0.00 | 0.00 | 0.00 |
July | 356.97 | 23.11 | 333.86 | 489.34 | 117.50 | 0.00 | 0.00 | 0.00 |
August | 284.12 | 6.72 | 277.40 | 369.86 | 138.53 | 0.00 | 0.00 | 0.00 |
September | 238.66 | 0.06 | 238.61 | 270.87 | 220.62 | 0.00 | 0.00 | 0.00 |
October | 170.94 | 0.00 | 170.94 | 93.15 | 455.28 | 0.00 | 0.00 | 0.00 |
November | 129.76 | 0.00 | 129.76 | 36.46 | 536.82 | 0.00 | 0.00 | 0.00 |
December | 109.77 | 0.00 | 109.77 | 20.12 | 656.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.86 | 7.06 | 220.80 | 202.79 | 367.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.77 | 0.00 | 109.77 | 20.12 | 117.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 377.46 | 41.85 | 335.61 | 511.38 | 656.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.33 | 0.00 | 117.33 | 24.87 | 573.18 | 0.00 | 0.00 | 0.00 |
February | 147.47 | 0.00 | 147.47 | 32.02 | 577.03 | 0.00 | 0.00 | 0.00 |
March | 200.65 | 0.00 | 200.65 | 100.85 | 433.84 | 0.00 | 0.00 | 0.00 |
April | 251.99 | 1.40 | 250.59 | 149.78 | 374.15 | 0.00 | 0.00 | 0.00 |
May | 344.24 | 11.38 | 332.86 | 323.34 | 220.89 | 0.00 | 0.00 | 0.00 |
June | 377.48 | 41.85 | 335.63 | 511.41 | 124.44 | 0.00 | 0.00 | 0.00 |
July | 356.99 | 23.11 | 333.88 | 489.37 | 117.51 | 0.00 | 0.00 | 0.00 |
August | 284.14 | 6.72 | 277.42 | 369.88 | 138.54 | 0.00 | 0.00 | 0.00 |
September | 238.68 | 0.06 | 238.62 | 270.89 | 220.63 | 0.00 | 0.00 | 0.00 |
October | 170.95 | 0.00 | 170.95 | 93.16 | 455.31 | 0.00 | 0.00 | 0.00 |
November | 129.77 | 0.00 | 129.77 | 36.47 | 536.85 | 0.00 | 0.00 | 0.00 |
December | 109.77 | 0.00 | 109.77 | 20.12 | 656.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.87 | 7.06 | 220.81 | 202.80 | 367.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.77 | 0.00 | 109.77 | 20.12 | 117.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 377.48 | 41.85 | 335.63 | 511.41 | 656.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.33 | 0.00 | 117.33 | 24.87 | 573.18 | 0.00 | 0.00 | 0.00 |
February | 147.47 | 0.00 | 147.47 | 32.02 | 577.03 | 0.00 | 0.00 | 0.00 |
March | 200.65 | 0.00 | 200.65 | 100.85 | 433.84 | 0.00 | 0.00 | 0.00 |
April | 251.99 | 1.40 | 250.59 | 149.78 | 374.15 | 0.00 | 0.00 | 0.00 |
May | 344.24 | 11.38 | 332.86 | 323.34 | 220.89 | 0.00 | 0.00 | 0.00 |
June | 377.48 | 41.85 | 335.63 | 511.41 | 124.44 | 0.00 | 0.00 | 0.00 |
July | 356.99 | 23.11 | 333.88 | 489.37 | 117.51 | 0.00 | 0.00 | 0.00 |
August | 284.14 | 6.72 | 277.42 | 369.88 | 138.54 | 0.00 | 0.00 | 0.00 |
September | 238.68 | 0.06 | 238.62 | 270.89 | 220.63 | 0.00 | 0.00 | 0.00 |
October | 170.95 | 0.00 | 170.95 | 93.16 | 455.31 | 0.00 | 0.00 | 0.00 |
November | 129.77 | 0.00 | 129.77 | 36.47 | 536.85 | 0.00 | 0.00 | 0.00 |
December | 109.77 | 0.00 | 109.77 | 20.12 | 656.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.87 | 7.06 | 220.81 | 202.80 | 367.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.77 | 0.00 | 109.77 | 20.12 | 117.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 377.48 | 41.85 | 335.63 | 511.41 | 656.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 706.81 | 433.15 | 273.66 | 637.88 | 1045.90 | 0.00 | 0.00 | 0.00 |
February | 938.91 | 592.73 | 346.18 | 895.31 | 1075.99 | 0.00 | 0.00 | 0.00 |
March | 1133.24 | 661.01 | 472.24 | 1165.48 | 822.01 | 0.00 | 0.00 | 0.00 |
April | 1162.20 | 566.13 | 596.08 | 1170.57 | 721.06 | 0.00 | 0.00 | 0.00 |
May | 1358.60 | 567.49 | 791.11 | 1555.43 | 441.83 | 0.00 | 0.00 | 0.00 |
June | 1657.63 | 870.21 | 787.42 | 2241.06 | 250.56 | 0.00 | 0.00 | 0.00 |
July | 1506.92 | 717.55 | 789.36 | 2055.21 | 237.44 | 0.00 | 0.00 | 0.00 |
August | 1519.93 | 837.12 | 682.81 | 2053.61 | 279.57 | 0.00 | 0.00 | 0.00 |
September | 1264.66 | 687.00 | 577.66 | 1613.79 | 419.95 | 0.00 | 0.00 | 0.00 |
October | 915.87 | 501.84 | 414.03 | 959.22 | 872.06 | 0.00 | 0.00 | 0.00 |
November | 712.88 | 402.50 | 310.38 | 668.56 | 1008.01 | 0.00 | 0.00 | 0.00 |
December | 617.17 | 355.53 | 261.64 | 528.87 | 1205.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1125.27 | 599.06 | 526.22 | 1297.30 | 696.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 617.17 | 355.53 | 261.64 | 528.87 | 237.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1657.63 | 870.21 | 791.11 | 2241.06 | 1205.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.95 | 17.13 | 10.82 | 25.22 | 41.35 | 0.00 | 0.00 | 0.00 |
February | 37.12 | 23.44 | 13.69 | 35.40 | 42.54 | 0.00 | 0.00 | 0.00 |
March | 44.81 | 26.14 | 18.67 | 46.08 | 32.50 | 0.00 | 0.00 | 0.00 |
April | 45.95 | 22.38 | 23.57 | 46.28 | 28.51 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 22.44 | 31.28 | 61.50 | 17.47 | 0.00 | 0.00 | 0.00 |
June | 65.54 | 34.41 | 31.13 | 88.61 | 9.91 | 0.00 | 0.00 | 0.00 |
July | 59.58 | 28.37 | 31.21 | 81.26 | 9.39 | 0.00 | 0.00 | 0.00 |
August | 60.10 | 33.10 | 27.00 | 81.20 | 11.05 | 0.00 | 0.00 | 0.00 |
September | 50.00 | 27.16 | 22.84 | 63.81 | 16.60 | 0.00 | 0.00 | 0.00 |
October | 36.21 | 19.84 | 16.37 | 37.93 | 34.48 | 0.00 | 0.00 | 0.00 |
November | 28.19 | 15.91 | 12.27 | 26.43 | 39.86 | 0.00 | 0.00 | 0.00 |
December | 24.40 | 14.06 | 10.34 | 20.91 | 47.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.49 | 23.69 | 20.81 | 51.29 | 27.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.40 | 14.06 | 10.34 | 20.91 | 9.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.54 | 34.41 | 31.28 | 88.61 | 47.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1124.45 | 924.98 | 199.47 | 1295.92 | 542.61 | 0.00 | 0.00 | 0.00 |
February | 1078.56 | 859.89 | 218.66 | 1236.92 | 555.98 | 0.00 | 0.00 | 0.00 |
March | 795.20 | 523.19 | 272.00 | 927.91 | 437.11 | 0.00 | 0.00 | 0.00 |
April | 515.03 | 207.09 | 307.93 | 553.28 | 389.94 | 0.00 | 0.00 | 0.00 |
May | 471.97 | 86.51 | 385.46 | 553.91 | 241.63 | 0.00 | 0.00 | 0.00 |
June | 435.14 | 79.53 | 355.61 | 637.22 | 137.25 | 0.00 | 0.00 | 0.00 |
July | 452.97 | 81.11 | 371.85 | 663.87 | 127.74 | 0.00 | 0.00 | 0.00 |
August | 576.72 | 241.09 | 335.63 | 843.53 | 151.25 | 0.00 | 0.00 | 0.00 |
September | 742.01 | 414.04 | 327.97 | 1013.19 | 234.81 | 0.00 | 0.00 | 0.00 |
October | 887.22 | 629.50 | 257.72 | 1078.15 | 463.61 | 0.00 | 0.00 | 0.00 |
November | 1080.96 | 861.68 | 219.28 | 1270.49 | 526.99 | 0.00 | 0.00 | 0.00 |
December | 1033.68 | 836.64 | 197.03 | 1168.25 | 605.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 764.39 | 476.61 | 287.78 | 935.17 | 366.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 435.14 | 79.53 | 197.03 | 553.28 | 127.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1124.45 | 924.98 | 385.46 | 1295.92 | 605.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1124.45 | 924.98 | 199.47 | 1295.92 | 542.61 | 0.00 | 0.00 | 0.00 |
February | 1078.56 | 859.89 | 218.66 | 1236.92 | 555.98 | 0.00 | 0.00 | 0.00 |
March | 795.20 | 523.19 | 272.00 | 927.91 | 437.11 | 0.00 | 0.00 | 0.00 |
April | 515.03 | 207.09 | 307.93 | 553.28 | 389.94 | 0.00 | 0.00 | 0.00 |
May | 471.97 | 86.51 | 385.46 | 553.91 | 241.63 | 0.00 | 0.00 | 0.00 |
June | 435.14 | 79.53 | 355.61 | 637.22 | 137.25 | 0.00 | 0.00 | 0.00 |
July | 452.97 | 81.11 | 371.85 | 663.87 | 127.74 | 0.00 | 0.00 | 0.00 |
August | 576.72 | 241.09 | 335.63 | 843.53 | 151.25 | 0.00 | 0.00 | 0.00 |
September | 742.01 | 414.04 | 327.97 | 1013.19 | 234.81 | 0.00 | 0.00 | 0.00 |
October | 887.22 | 629.50 | 257.72 | 1078.15 | 463.61 | 0.00 | 0.00 | 0.00 |
November | 1080.96 | 861.68 | 219.28 | 1270.49 | 526.99 | 0.00 | 0.00 | 0.00 |
December | 1033.68 | 836.64 | 197.03 | 1168.25 | 605.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 764.39 | 476.61 | 287.78 | 935.17 | 366.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 435.14 | 79.53 | 197.03 | 553.28 | 127.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1124.45 | 924.98 | 385.46 | 1295.92 | 605.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1124.38 | 924.92 | 199.46 | 1295.84 | 542.58 | 0.00 | 0.00 | 0.00 |
February | 1078.49 | 859.84 | 218.65 | 1236.84 | 555.95 | 0.00 | 0.00 | 0.00 |
March | 795.15 | 523.16 | 271.98 | 927.85 | 437.09 | 0.00 | 0.00 | 0.00 |
April | 515.00 | 207.08 | 307.91 | 553.25 | 389.91 | 0.00 | 0.00 | 0.00 |
May | 471.94 | 86.50 | 385.43 | 553.87 | 241.61 | 0.00 | 0.00 | 0.00 |
June | 435.11 | 79.53 | 355.58 | 637.18 | 137.25 | 0.00 | 0.00 | 0.00 |
July | 452.94 | 81.11 | 371.83 | 663.82 | 127.74 | 0.00 | 0.00 | 0.00 |
August | 576.68 | 241.08 | 335.61 | 843.48 | 151.24 | 0.00 | 0.00 | 0.00 |
September | 741.96 | 414.01 | 327.95 | 1013.13 | 234.80 | 0.00 | 0.00 | 0.00 |
October | 887.17 | 629.47 | 257.70 | 1078.08 | 463.58 | 0.00 | 0.00 | 0.00 |
November | 1080.89 | 861.63 | 219.26 | 1270.41 | 526.95 | 0.00 | 0.00 | 0.00 |
December | 1033.61 | 836.59 | 197.02 | 1168.18 | 605.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 764.34 | 476.58 | 287.76 | 935.11 | 366.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 435.11 | 79.53 | 197.02 | 553.25 | 127.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1124.38 | 924.92 | 385.43 | 1295.84 | 605.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 751.89 | 476.43 | 275.45 | 730.54 | 1076.60 | 0.00 | 0.00 | 0.00 |
February | 906.67 | 561.86 | 344.80 | 873.16 | 1094.20 | 0.00 | 0.00 | 0.00 |
March | 1061.65 | 585.73 | 475.92 | 1089.55 | 837.36 | 0.00 | 0.00 | 0.00 |
April | 999.59 | 423.21 | 576.38 | 981.85 | 736.02 | 0.00 | 0.00 | 0.00 |
May | 1221.76 | 430.71 | 791.05 | 1409.16 | 466.97 | 0.00 | 0.00 | 0.00 |
June | 1494.29 | 718.96 | 775.33 | 2050.98 | 281.35 | 0.00 | 0.00 | 0.00 |
July | 1217.49 | 445.94 | 771.55 | 1679.37 | 254.06 | 0.00 | 0.00 | 0.00 |
August | 1270.71 | 627.75 | 642.97 | 1720.30 | 293.21 | 0.00 | 0.00 | 0.00 |
September | 1126.74 | 540.35 | 586.40 | 1451.36 | 447.95 | 0.00 | 0.00 | 0.00 |
October | 947.89 | 541.79 | 406.10 | 1028.08 | 888.50 | 0.00 | 0.00 | 0.00 |
November | 777.79 | 472.21 | 305.58 | 766.09 | 1022.83 | 0.00 | 0.00 | 0.00 |
December | 628.24 | 371.12 | 257.12 | 555.30 | 1213.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1034.05 | 515.72 | 518.33 | 1195.99 | 715.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 628.24 | 371.12 | 257.12 | 555.30 | 254.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1494.29 | 718.96 | 791.05 | 2050.98 | 1213.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.73 | 18.84 | 10.89 | 28.88 | 42.57 | 0.00 | 0.00 | 0.00 |
February | 35.85 | 22.22 | 13.63 | 34.52 | 43.26 | 0.00 | 0.00 | 0.00 |
March | 41.98 | 23.16 | 18.82 | 43.08 | 33.11 | 0.00 | 0.00 | 0.00 |
April | 39.52 | 16.73 | 22.79 | 38.82 | 29.10 | 0.00 | 0.00 | 0.00 |
May | 48.31 | 17.03 | 31.28 | 55.72 | 18.46 | 0.00 | 0.00 | 0.00 |
June | 59.08 | 28.43 | 30.66 | 81.09 | 11.12 | 0.00 | 0.00 | 0.00 |
July | 48.14 | 17.63 | 30.51 | 66.40 | 10.05 | 0.00 | 0.00 | 0.00 |
August | 50.24 | 24.82 | 25.42 | 68.02 | 11.59 | 0.00 | 0.00 | 0.00 |
September | 44.55 | 21.36 | 23.19 | 57.39 | 17.71 | 0.00 | 0.00 | 0.00 |
October | 37.48 | 21.42 | 16.06 | 40.65 | 35.13 | 0.00 | 0.00 | 0.00 |
November | 30.75 | 18.67 | 12.08 | 30.29 | 40.44 | 0.00 | 0.00 | 0.00 |
December | 24.84 | 14.67 | 10.17 | 21.96 | 47.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.89 | 20.39 | 20.49 | 47.29 | 28.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.84 | 14.67 | 10.17 | 21.96 | 10.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.08 | 28.43 | 31.28 | 81.09 | 47.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 351.98 | 0.00 | 351.98 | 66.26 | 1761.73 | 0.00 | 0.00 | 0.00 |
February | 442.39 | 0.00 | 442.39 | 82.75 | 1780.34 | 0.00 | 0.00 | 0.00 |
March | 601.95 | 0.00 | 601.95 | 272.89 | 1354.79 | 0.00 | 0.00 | 0.00 |
April | 755.96 | 4.19 | 751.77 | 416.05 | 1164.76 | 0.00 | 0.00 | 0.00 |
May | 1032.69 | 34.14 | 998.56 | 925.30 | 700.27 | 0.00 | 0.00 | 0.00 |
June | 1132.42 | 125.55 | 1006.87 | 1506.97 | 391.65 | 0.00 | 0.00 | 0.00 |
July | 1070.96 | 69.33 | 1001.64 | 1443.39 | 371.37 | 0.00 | 0.00 | 0.00 |
August | 852.40 | 20.16 | 832.24 | 1095.74 | 427.65 | 0.00 | 0.00 | 0.00 |
September | 716.02 | 0.17 | 715.85 | 808.06 | 659.82 | 0.00 | 0.00 | 0.00 |
October | 512.84 | 0.00 | 512.84 | 276.32 | 1352.43 | 0.00 | 0.00 | 0.00 |
November | 389.31 | 0.00 | 389.31 | 107.05 | 1604.07 | 0.00 | 0.00 | 0.00 |
December | 329.32 | 0.00 | 329.32 | 58.04 | 1970.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 683.60 | 21.18 | 662.43 | 591.06 | 1124.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 329.32 | 0.00 | 329.32 | 58.04 | 371.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1132.42 | 125.55 | 1006.87 | 1506.97 | 1970.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 734.76 | 450.28 | 284.48 | 652.90 | 1094.66 | 0.00 | 0.00 | 0.00 |
February | 976.05 | 616.17 | 359.87 | 916.05 | 1129.21 | 0.00 | 0.00 | 0.00 |
March | 1178.06 | 687.15 | 490.91 | 1192.59 | 863.30 | 0.00 | 0.00 | 0.00 |
April | 1208.16 | 588.52 | 619.65 | 1198.43 | 751.87 | 0.00 | 0.00 | 0.00 |
May | 1412.33 | 589.93 | 822.39 | 1595.33 | 467.51 | 0.00 | 0.00 | 0.00 |
June | 1723.18 | 904.62 | 818.56 | 2316.20 | 261.03 | 0.00 | 0.00 | 0.00 |
July | 1566.51 | 745.93 | 820.58 | 2124.49 | 247.63 | 0.00 | 0.00 | 0.00 |
August | 1580.04 | 870.23 | 709.81 | 2128.42 | 283.86 | 0.00 | 0.00 | 0.00 |
September | 1314.67 | 714.17 | 600.51 | 1676.42 | 418.56 | 0.00 | 0.00 | 0.00 |
October | 952.09 | 521.69 | 430.40 | 995.87 | 874.72 | 0.00 | 0.00 | 0.00 |
November | 741.08 | 418.42 | 322.66 | 693.13 | 1023.66 | 0.00 | 0.00 | 0.00 |
December | 641.57 | 369.59 | 271.98 | 545.58 | 1239.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1169.78 | 622.75 | 547.03 | 1338.26 | 719.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 641.57 | 369.59 | 271.98 | 545.58 | 247.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1723.18 | 904.62 | 822.39 | 2316.20 | 1239.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3373.25 | 2774.86 | 598.39 | 3849.94 | 1599.19 | 0.00 | 0.00 | 0.00 |
February | 3235.57 | 2579.60 | 655.97 | 3656.73 | 1661.12 | 0.00 | 0.00 | 0.00 |
March | 2385.51 | 1569.53 | 815.98 | 2734.39 | 1328.84 | 0.00 | 0.00 | 0.00 |
April | 1545.04 | 621.26 | 923.77 | 1614.24 | 1196.57 | 0.00 | 0.00 | 0.00 |
May | 1415.86 | 259.52 | 1156.34 | 1610.32 | 767.25 | 0.00 | 0.00 | 0.00 |
June | 1305.38 | 238.58 | 1066.79 | 1886.54 | 429.76 | 0.00 | 0.00 | 0.00 |
July | 1358.86 | 243.33 | 1115.53 | 1968.63 | 399.00 | 0.00 | 0.00 | 0.00 |
August | 1730.11 | 723.25 | 1006.86 | 2516.46 | 451.15 | 0.00 | 0.00 | 0.00 |
September | 2225.95 | 1242.07 | 983.89 | 3030.85 | 676.23 | 0.00 | 0.00 | 0.00 |
October | 2661.59 | 1888.45 | 773.13 | 3218.95 | 1338.99 | 0.00 | 0.00 | 0.00 |
November | 3242.77 | 2584.96 | 657.81 | 3782.42 | 1529.52 | 0.00 | 0.00 | 0.00 |
December | 3100.93 | 2509.85 | 591.08 | 3467.29 | 1783.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2293.09 | 1429.77 | 863.32 | 2773.03 | 1093.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1305.38 | 238.58 | 591.08 | 1610.32 | 399.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3373.25 | 2774.86 | 1156.34 | 3849.94 | 1783.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 781.62 | 495.28 | 286.34 | 748.53 | 1126.38 | 0.00 | 0.00 | 0.00 |
February | 942.52 | 584.08 | 358.44 | 892.86 | 1148.67 | 0.00 | 0.00 | 0.00 |
March | 1103.63 | 608.90 | 494.74 | 1113.55 | 884.42 | 0.00 | 0.00 | 0.00 |
April | 1039.12 | 439.95 | 599.18 | 1002.49 | 773.68 | 0.00 | 0.00 | 0.00 |
May | 1270.08 | 447.75 | 822.33 | 1441.74 | 499.00 | 0.00 | 0.00 | 0.00 |
June | 1553.38 | 747.39 | 805.99 | 2120.19 | 294.62 | 0.00 | 0.00 | 0.00 |
July | 1265.64 | 463.58 | 802.06 | 1733.94 | 269.23 | 0.00 | 0.00 | 0.00 |
August | 1320.97 | 652.57 | 668.39 | 1782.07 | 301.55 | 0.00 | 0.00 | 0.00 |
September | 1171.30 | 561.72 | 609.59 | 1508.59 | 449.46 | 0.00 | 0.00 | 0.00 |
October | 985.37 | 563.21 | 422.16 | 1069.72 | 893.42 | 0.00 | 0.00 | 0.00 |
November | 808.55 | 490.89 | 317.66 | 794.35 | 1040.65 | 0.00 | 0.00 | 0.00 |
December | 653.09 | 385.80 | 267.29 | 572.42 | 1247.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1074.94 | 536.12 | 538.83 | 1233.12 | 741.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 653.09 | 385.80 | 267.29 | 572.42 | 269.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1553.38 | 747.39 | 822.33 | 2120.19 | 1247.99 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.942735E+09 | 0.00 | 0.942735E+09 | 0.200881E+09 | 0.445734E+10 |
February | 0.107024E+10 | 0.00 | 0.107024E+10 | 0.220755E+09 | 0.410182E+10 |
March | 0.161227E+10 | 0.00 | 0.161227E+10 | 0.758193E+09 | 0.343410E+10 |
April | 0.195946E+10 | 10870236.15 | 0.194859E+10 | 0.110990E+10 | 0.280955E+10 |
May | 0.276597E+10 | 91431654.91 | 0.267453E+10 | 0.251772E+10 | 0.178561E+10 |
June | 0.293523E+10 | 0.325418E+09 | 0.260981E+10 | 0.390093E+10 | 0.987794E+09 |
July | 0.286846E+10 | 0.185680E+09 | 0.268278E+10 | 0.385832E+10 | 0.968496E+09 |
August | 0.228308E+10 | 54009907.87 | 0.222907E+10 | 0.293540E+10 | 0.110372E+10 |
September | 0.185592E+10 | 435922.88 | 0.185548E+10 | 0.211152E+10 | 0.162224E+10 |
October | 0.137360E+10 | 0.00 | 0.137360E+10 | 0.781510E+09 | 0.338902E+10 |
November | 0.100910E+10 | 0.00 | 0.100910E+10 | 0.310034E+09 | 0.390022E+10 |
December | 0.882047E+09 | 0.00 | 0.882047E+09 | 0.171855E+09 | 0.503584E+10 |
Annual Sum or Average | 0.215581E+11 | 0.667846E+09 | 0.208902E+11 | 0.188770E+11 | 0.335957E+11 |
Minimum of Months | 0.882047E+09 | 0.00 | 0.882047E+09 | 0.171855E+09 | 0.968496E+09 |
Maximum of Months | 0.293523E+10 | 0.325418E+09 | 0.268278E+10 | 0.390093E+10 | 0.503584E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196798E+10 | 0.120603E+10 | 0.761944E+09 | 0.178372E+10 | 0.277718E+10 |
February | 0.236125E+10 | 0.149064E+10 | 0.870605E+09 | 0.224108E+10 | 0.260921E+10 |
March | 0.315532E+10 | 0.184046E+10 | 0.131485E+10 | 0.321458E+10 | 0.219789E+10 |
April | 0.313156E+10 | 0.152544E+10 | 0.160613E+10 | 0.312680E+10 | 0.182201E+10 |
May | 0.378277E+10 | 0.158007E+10 | 0.220270E+10 | 0.429173E+10 | 0.119850E+10 |
June | 0.446649E+10 | 0.234478E+10 | 0.212171E+10 | 0.599382E+10 | 0.659181E+09 |
July | 0.419574E+10 | 0.199790E+10 | 0.219784E+10 | 0.568013E+10 | 0.645922E+09 |
August | 0.423198E+10 | 0.233082E+10 | 0.190116E+10 | 0.569469E+10 | 0.734612E+09 |
September | 0.340763E+10 | 0.185112E+10 | 0.155652E+10 | 0.435260E+10 | 0.103609E+10 |
October | 0.255007E+10 | 0.139729E+10 | 0.115278E+10 | 0.269034E+10 | 0.220660E+10 |
November | 0.192087E+10 | 0.108454E+10 | 0.836331E+09 | 0.183041E+10 | 0.250227E+10 |
December | 0.171839E+10 | 0.989914E+09 | 0.728478E+09 | 0.148974E+10 | 0.317213E+10 |
Annual Sum or Average | 0.368900E+11 | 0.196390E+11 | 0.172510E+11 | 0.423896E+11 | 0.215616E+11 |
Minimum of Months | 0.171839E+10 | 0.989914E+09 | 0.728478E+09 | 0.148974E+10 | 0.645922E+09 |
Maximum of Months | 0.446649E+10 | 0.234478E+10 | 0.220270E+10 | 0.599382E+10 | 0.317213E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.903490E+10 | 0.743217E+10 | 0.160273E+10 | 0.103692E+11 | 0.405055E+10 |
February | 0.782749E+10 | 0.624056E+10 | 0.158693E+10 | 0.888105E+10 | 0.382731E+10 |
March | 0.638936E+10 | 0.420383E+10 | 0.218553E+10 | 0.734935E+10 | 0.337345E+10 |
April | 0.400474E+10 | 0.161032E+10 | 0.239442E+10 | 0.421131E+10 | 0.289333E+10 |
May | 0.379223E+10 | 0.695086E+09 | 0.309715E+10 | 0.433925E+10 | 0.195096E+10 |
June | 0.338353E+10 | 0.618411E+09 | 0.276512E+10 | 0.488154E+10 | 0.107667E+10 |
July | 0.363958E+10 | 0.651745E+09 | 0.298784E+10 | 0.526288E+10 | 0.103375E+10 |
August | 0.463392E+10 | 0.193715E+10 | 0.269678E+10 | 0.673409E+10 | 0.116185E+10 |
September | 0.576967E+10 | 0.321943E+10 | 0.255023E+10 | 0.786325E+10 | 0.166797E+10 |
October | 0.712879E+10 | 0.505803E+10 | 0.207076E+10 | 0.865291E+10 | 0.337534E+10 |
November | 0.840526E+10 | 0.670020E+10 | 0.170505E+10 | 0.985075E+10 | 0.373904E+10 |
December | 0.830554E+10 | 0.672238E+10 | 0.158315E+10 | 0.933709E+10 | 0.454869E+10 |
Annual Sum or Average | 0.723150E+11 | 0.450893E+11 | 0.272257E+11 | 0.877327E+11 | 0.326989E+11 |
Minimum of Months | 0.338353E+10 | 0.618411E+09 | 0.158315E+10 | 0.421131E+10 | 0.103375E+10 |
Maximum of Months | 0.903490E+10 | 0.743217E+10 | 0.309715E+10 | 0.103692E+11 | 0.454869E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209349E+10 | 0.132655E+10 | 0.766944E+09 | 0.202740E+10 | 0.285234E+10 |
February | 0.228015E+10 | 0.141302E+10 | 0.867136E+09 | 0.217494E+10 | 0.264775E+10 |
March | 0.295598E+10 | 0.163087E+10 | 0.132510E+10 | 0.299751E+10 | 0.224425E+10 |
April | 0.269341E+10 | 0.114034E+10 | 0.155307E+10 | 0.261664E+10 | 0.187103E+10 |
May | 0.340177E+10 | 0.119925E+10 | 0.220252E+10 | 0.388115E+10 | 0.126888E+10 |
June | 0.402636E+10 | 0.193723E+10 | 0.208913E+10 | 0.549009E+10 | 0.739362E+09 |
July | 0.338988E+10 | 0.124165E+10 | 0.214823E+10 | 0.463866E+10 | 0.698012E+09 |
August | 0.353807E+10 | 0.174785E+10 | 0.179022E+10 | 0.477339E+10 | 0.777426E+09 |
September | 0.303601E+10 | 0.145597E+10 | 0.158004E+10 | 0.392221E+10 | 0.110638E+10 |
October | 0.263923E+10 | 0.150851E+10 | 0.113071E+10 | 0.288883E+10 | 0.224811E+10 |
November | 0.209577E+10 | 0.127239E+10 | 0.823378E+09 | 0.208362E+10 | 0.253802E+10 |
December | 0.174923E+10 | 0.103332E+10 | 0.715916E+09 | 0.155046E+10 | 0.318854E+10 |
Annual Sum or Average | 0.338994E+11 | 0.169069E+11 | 0.169924E+11 | 0.390449E+11 | 0.221801E+11 |
Minimum of Months | 0.174923E+10 | 0.103332E+10 | 0.715916E+09 | 0.155046E+10 | 0.698012E+09 |
Maximum of Months | 0.402636E+10 | 0.193723E+10 | 0.220252E+10 | 0.549009E+10 | 0.318854E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314230E+09 | 0.00 | 0.314230E+09 | 66611213.33 | 0.153511E+10 |
February | 0.356729E+09 | 0.00 | 0.356729E+09 | 77463211.92 | 0.139585E+10 |
March | 0.537397E+09 | 0.00 | 0.537397E+09 | 0.270105E+09 | 0.116193E+10 |
April | 0.653122E+09 | 3623240.62 | 0.649499E+09 | 0.388216E+09 | 0.969734E+09 |
May | 0.921945E+09 | 30475776.36 | 0.891469E+09 | 0.865987E+09 | 0.591585E+09 |
June | 0.978364E+09 | 0.108467E+09 | 0.869896E+09 | 0.132549E+10 | 0.322530E+09 |
July | 0.956108E+09 | 61890569.91 | 0.894217E+09 | 0.131065E+10 | 0.314714E+09 |
August | 0.760990E+09 | 18002450.85 | 0.742987E+09 | 0.990623E+09 | 0.371034E+09 |
September | 0.618611E+09 | 145300.75 | 0.618466E+09 | 0.702101E+09 | 0.571845E+09 |
October | 0.457844E+09 | 0.00 | 0.457844E+09 | 0.249503E+09 | 0.121942E+10 |
November | 0.336350E+09 | 0.00 | 0.336350E+09 | 94515450.12 | 0.139144E+10 |
December | 0.294002E+09 | 0.00 | 0.294002E+09 | 53880550.13 | 0.175838E+10 |
Annual Sum or Average | 0.718569E+10 | 0.222605E+09 | 0.696308E+10 | 0.639515E+10 | 0.116036E+11 |
Minimum of Months | 0.294002E+09 | 0.00 | 0.294002E+09 | 53880550.13 | 0.314714E+09 |
Maximum of Months | 0.978364E+09 | 0.108467E+09 | 0.894217E+09 | 0.132549E+10 | 0.175838E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314250E+09 | 0.00 | 0.314250E+09 | 66615423.05 | 0.153520E+10 |
February | 0.356751E+09 | 0.00 | 0.356751E+09 | 77468107.46 | 0.139594E+10 |
March | 0.537431E+09 | 0.00 | 0.537431E+09 | 0.270122E+09 | 0.116201E+10 |
April | 0.653163E+09 | 3623469.60 | 0.649540E+09 | 0.388241E+09 | 0.969795E+09 |
May | 0.922003E+09 | 30477702.38 | 0.891525E+09 | 0.866042E+09 | 0.591623E+09 |
June | 0.978425E+09 | 0.108474E+09 | 0.869951E+09 | 0.132558E+10 | 0.322551E+09 |
July | 0.956168E+09 | 61894481.29 | 0.894274E+09 | 0.131074E+10 | 0.314734E+09 |
August | 0.761038E+09 | 18003588.58 | 0.743034E+09 | 0.990686E+09 | 0.371057E+09 |
September | 0.618650E+09 | 145309.93 | 0.618505E+09 | 0.702146E+09 | 0.571881E+09 |
October | 0.457873E+09 | 0.00 | 0.457873E+09 | 0.249519E+09 | 0.121949E+10 |
November | 0.336371E+09 | 0.00 | 0.336371E+09 | 94521423.34 | 0.139152E+10 |
December | 0.294020E+09 | 0.00 | 0.294020E+09 | 53883955.30 | 0.175849E+10 |
Annual Sum or Average | 0.718614E+10 | 0.222619E+09 | 0.696352E+10 | 0.639556E+10 | 0.116043E+11 |
Minimum of Months | 0.294020E+09 | 0.00 | 0.294020E+09 | 53883955.30 | 0.314734E+09 |
Maximum of Months | 0.978425E+09 | 0.108474E+09 | 0.894274E+09 | 0.132558E+10 | 0.175849E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314250E+09 | 0.00 | 0.314250E+09 | 66615423.05 | 0.153520E+10 |
February | 0.356751E+09 | 0.00 | 0.356751E+09 | 77468107.46 | 0.139594E+10 |
March | 0.537431E+09 | 0.00 | 0.537431E+09 | 0.270122E+09 | 0.116201E+10 |
April | 0.653163E+09 | 3623469.60 | 0.649540E+09 | 0.388241E+09 | 0.969795E+09 |
May | 0.922003E+09 | 30477702.38 | 0.891525E+09 | 0.866042E+09 | 0.591623E+09 |
June | 0.978425E+09 | 0.108474E+09 | 0.869951E+09 | 0.132558E+10 | 0.322551E+09 |
July | 0.956168E+09 | 61894481.29 | 0.894274E+09 | 0.131074E+10 | 0.314734E+09 |
August | 0.761038E+09 | 18003588.58 | 0.743034E+09 | 0.990686E+09 | 0.371057E+09 |
September | 0.618650E+09 | 145309.93 | 0.618505E+09 | 0.702146E+09 | 0.571881E+09 |
October | 0.457873E+09 | 0.00 | 0.457873E+09 | 0.249519E+09 | 0.121949E+10 |
November | 0.336371E+09 | 0.00 | 0.336371E+09 | 94521423.34 | 0.139152E+10 |
December | 0.294020E+09 | 0.00 | 0.294020E+09 | 53883955.30 | 0.175849E+10 |
Annual Sum or Average | 0.718614E+10 | 0.222619E+09 | 0.696352E+10 | 0.639556E+10 | 0.116043E+11 |
Minimum of Months | 0.294020E+09 | 0.00 | 0.294020E+09 | 53883955.30 | 0.314734E+09 |
Maximum of Months | 0.978425E+09 | 0.108474E+09 | 0.894274E+09 | 0.132558E+10 | 0.175849E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189311E+10 | 0.116015E+10 | 0.732960E+09 | 0.170849E+10 | 0.280134E+10 |
February | 0.227142E+10 | 0.143393E+10 | 0.837488E+09 | 0.216594E+10 | 0.260303E+10 |
March | 0.303528E+10 | 0.177044E+10 | 0.126484E+10 | 0.312163E+10 | 0.220167E+10 |
April | 0.301243E+10 | 0.146740E+10 | 0.154503E+10 | 0.303411E+10 | 0.186899E+10 |
May | 0.363887E+10 | 0.151996E+10 | 0.211891E+10 | 0.416607E+10 | 0.118339E+10 |
June | 0.429657E+10 | 0.225557E+10 | 0.204100E+10 | 0.580882E+10 | 0.649441E+09 |
July | 0.403612E+10 | 0.192189E+10 | 0.211423E+10 | 0.550466E+10 | 0.635971E+09 |
August | 0.407098E+10 | 0.224214E+10 | 0.182884E+10 | 0.550039E+10 | 0.748799E+09 |
September | 0.327800E+10 | 0.178069E+10 | 0.149730E+10 | 0.418293E+10 | 0.108851E+10 |
October | 0.245305E+10 | 0.134413E+10 | 0.110893E+10 | 0.256918E+10 | 0.233572E+10 |
November | 0.184780E+10 | 0.104328E+10 | 0.804517E+09 | 0.173292E+10 | 0.261275E+10 |
December | 0.165302E+10 | 0.952253E+09 | 0.700767E+09 | 0.141652E+10 | 0.322900E+10 |
Annual Sum or Average | 0.354866E+11 | 0.188918E+11 | 0.165948E+11 | 0.409117E+11 | 0.219586E+11 |
Minimum of Months | 0.165302E+10 | 0.952253E+09 | 0.700767E+09 | 0.141652E+10 | 0.635971E+09 |
Maximum of Months | 0.429657E+10 | 0.225557E+10 | 0.211891E+10 | 0.580882E+10 | 0.322900E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 74851854.85 | 45871280.28 | 28980574.57 | 67552120.07 | 0.110762E+09 |
February | 89809899.69 | 56696393.84 | 33113505.85 | 85639119.99 | 0.102922E+09 |
March | 0.120012E+09 | 70001719.01 | 50010440.30 | 0.123426E+09 | 87051891.40 |
April | 0.119109E+09 | 58019680.16 | 61089059.77 | 0.119966E+09 | 73898075.31 |
May | 0.143877E+09 | 60097872.24 | 83779611.65 | 0.164723E+09 | 46790268.55 |
June | 0.169883E+09 | 89183388.48 | 80699170.63 | 0.229676E+09 | 25678314.00 |
July | 0.159585E+09 | 75989889.06 | 83594729.67 | 0.217649E+09 | 25145732.80 |
August | 0.160963E+09 | 88652189.02 | 72310777.96 | 0.217481E+09 | 29606819.58 |
September | 0.129609E+09 | 70406958.28 | 59202089.61 | 0.165389E+09 | 43038719.97 |
October | 96991565.62 | 53145510.59 | 43846055.03 | 0.101583E+09 | 92352157.68 |
November | 73060170.97 | 41250305.34 | 31809865.63 | 68517933.91 | 0.103306E+09 |
December | 65358905.10 | 37651218.26 | 27707686.83 | 56007833.72 | 0.127672E+09 |
Annual Sum or Average | 0.140311E+10 | 0.746966E+09 | 0.656144E+09 | 0.161761E+10 | 0.868224E+09 |
Minimum of Months | 65358905.10 | 37651218.26 | 27707686.83 | 56007833.72 | 25145732.80 |
Maximum of Months | 0.169883E+09 | 89183388.48 | 83779611.65 | 0.229676E+09 | 0.127672E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.301173E+10 | 0.247747E+10 | 0.534257E+09 | 0.347099E+10 | 0.145333E+10 |
February | 0.260925E+10 | 0.208026E+10 | 0.528990E+09 | 0.299235E+10 | 0.134503E+10 |
March | 0.212985E+10 | 0.140132E+10 | 0.728530E+09 | 0.248531E+10 | 0.117076E+10 |
April | 0.133495E+10 | 0.536789E+09 | 0.798162E+09 | 0.143411E+10 | 0.101072E+10 |
May | 0.126411E+10 | 0.231703E+09 | 0.103241E+10 | 0.148359E+10 | 0.647172E+09 |
June | 0.112787E+10 | 0.206144E+09 | 0.921731E+09 | 0.165168E+10 | 0.355764E+09 |
July | 0.121323E+10 | 0.217255E+09 | 0.995973E+09 | 0.177810E+10 | 0.342151E+09 |
August | 0.154469E+10 | 0.645737E+09 | 0.898949E+09 | 0.225932E+10 | 0.405117E+09 |
September | 0.192328E+10 | 0.107318E+10 | 0.850101E+09 | 0.262619E+10 | 0.608634E+09 |
October | 0.237634E+10 | 0.168607E+10 | 0.690272E+09 | 0.288771E+10 | 0.124173E+10 |
November | 0.280184E+10 | 0.223347E+10 | 0.568367E+09 | 0.329311E+10 | 0.136595E+10 |
December | 0.276860E+10 | 0.224087E+10 | 0.527733E+09 | 0.312905E+10 | 0.162186E+10 |
Annual Sum or Average | 0.241057E+11 | 0.150303E+11 | 0.907548E+10 | 0.294915E+11 | 0.115682E+11 |
Minimum of Months | 0.112787E+10 | 0.206144E+09 | 0.527733E+09 | 0.143411E+10 | 0.342151E+09 |
Maximum of Months | 0.301173E+10 | 0.247747E+10 | 0.103241E+10 | 0.347099E+10 | 0.162186E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.301173E+10 | 0.247747E+10 | 0.534257E+09 | 0.347099E+10 | 0.145333E+10 |
February | 0.260925E+10 | 0.208026E+10 | 0.528990E+09 | 0.299235E+10 | 0.134503E+10 |
March | 0.212985E+10 | 0.140132E+10 | 0.728530E+09 | 0.248531E+10 | 0.117076E+10 |
April | 0.133495E+10 | 0.536789E+09 | 0.798162E+09 | 0.143411E+10 | 0.101072E+10 |
May | 0.126411E+10 | 0.231703E+09 | 0.103241E+10 | 0.148359E+10 | 0.647172E+09 |
June | 0.112787E+10 | 0.206144E+09 | 0.921731E+09 | 0.165168E+10 | 0.355764E+09 |
July | 0.121323E+10 | 0.217255E+09 | 0.995973E+09 | 0.177810E+10 | 0.342151E+09 |
August | 0.154469E+10 | 0.645737E+09 | 0.898949E+09 | 0.225932E+10 | 0.405117E+09 |
September | 0.192328E+10 | 0.107318E+10 | 0.850101E+09 | 0.262619E+10 | 0.608634E+09 |
October | 0.237634E+10 | 0.168607E+10 | 0.690272E+09 | 0.288771E+10 | 0.124173E+10 |
November | 0.280184E+10 | 0.223347E+10 | 0.568367E+09 | 0.329311E+10 | 0.136595E+10 |
December | 0.276860E+10 | 0.224087E+10 | 0.527733E+09 | 0.312905E+10 | 0.162186E+10 |
Annual Sum or Average | 0.241057E+11 | 0.150303E+11 | 0.907548E+10 | 0.294915E+11 | 0.115682E+11 |
Minimum of Months | 0.112787E+10 | 0.206144E+09 | 0.527733E+09 | 0.143411E+10 | 0.342151E+09 |
Maximum of Months | 0.301173E+10 | 0.247747E+10 | 0.103241E+10 | 0.347099E+10 | 0.162186E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.301154E+10 | 0.247732E+10 | 0.534224E+09 | 0.347078E+10 | 0.145324E+10 |
February | 0.260908E+10 | 0.208012E+10 | 0.528957E+09 | 0.299216E+10 | 0.134495E+10 |
March | 0.212972E+10 | 0.140123E+10 | 0.728484E+09 | 0.248516E+10 | 0.117069E+10 |
April | 0.133487E+10 | 0.536755E+09 | 0.798112E+09 | 0.143402E+10 | 0.101065E+10 |
May | 0.126403E+10 | 0.231688E+09 | 0.103235E+10 | 0.148349E+10 | 0.647131E+09 |
June | 0.112780E+10 | 0.206131E+09 | 0.921673E+09 | 0.165157E+10 | 0.355741E+09 |
July | 0.121315E+10 | 0.217242E+09 | 0.995910E+09 | 0.177799E+10 | 0.342130E+09 |
August | 0.154459E+10 | 0.645696E+09 | 0.898892E+09 | 0.225917E+10 | 0.405092E+09 |
September | 0.192316E+10 | 0.107311E+10 | 0.850047E+09 | 0.262603E+10 | 0.608596E+09 |
October | 0.237619E+10 | 0.168596E+10 | 0.690228E+09 | 0.288752E+10 | 0.124165E+10 |
November | 0.280166E+10 | 0.223333E+10 | 0.568331E+09 | 0.329290E+10 | 0.136586E+10 |
December | 0.276843E+10 | 0.224073E+10 | 0.527700E+09 | 0.312885E+10 | 0.162176E+10 |
Annual Sum or Average | 0.241042E+11 | 0.150293E+11 | 0.907490E+10 | 0.294896E+11 | 0.115675E+11 |
Minimum of Months | 0.112780E+10 | 0.206131E+09 | 0.527700E+09 | 0.143402E+10 | 0.342130E+09 |
Maximum of Months | 0.301154E+10 | 0.247732E+10 | 0.103235E+10 | 0.347078E+10 | 0.162176E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201385E+10 | 0.127608E+10 | 0.737770E+09 | 0.195668E+10 | 0.288357E+10 |
February | 0.219341E+10 | 0.135926E+10 | 0.834151E+09 | 0.211234E+10 | 0.264709E+10 |
March | 0.284352E+10 | 0.156883E+10 | 0.127469E+10 | 0.291826E+10 | 0.224278E+10 |
April | 0.259095E+10 | 0.109696E+10 | 0.149399E+10 | 0.254496E+10 | 0.190777E+10 |
May | 0.327236E+10 | 0.115362E+10 | 0.211874E+10 | 0.377429E+10 | 0.125074E+10 |
June | 0.387319E+10 | 0.186353E+10 | 0.200966E+10 | 0.531613E+10 | 0.729251E+09 |
July | 0.326092E+10 | 0.119441E+10 | 0.206651E+10 | 0.449803E+10 | 0.680481E+09 |
August | 0.340348E+10 | 0.168136E+10 | 0.172212E+10 | 0.460765E+10 | 0.785326E+09 |
September | 0.292051E+10 | 0.140058E+10 | 0.151994E+10 | 0.376192E+10 | 0.116108E+10 |
October | 0.253882E+10 | 0.145112E+10 | 0.108770E+10 | 0.275361E+10 | 0.237975E+10 |
November | 0.201604E+10 | 0.122398E+10 | 0.792057E+09 | 0.198570E+10 | 0.265117E+10 |
December | 0.168269E+10 | 0.994004E+09 | 0.688682E+09 | 0.148732E+10 | 0.325077E+10 |
Annual Sum or Average | 0.326097E+11 | 0.162637E+11 | 0.163460E+11 | 0.377169E+11 | 0.225698E+11 |
Minimum of Months | 0.168269E+10 | 0.994004E+09 | 0.688682E+09 | 0.148732E+10 | 0.680481E+09 |
Maximum of Months | 0.387319E+10 | 0.186353E+10 | 0.211874E+10 | 0.531613E+10 | 0.325077E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 79625608.84 | 50454911.82 | 29170697.02 | 77365213.32 | 0.114014E+09 |
February | 86725264.41 | 53743742.24 | 32981522.17 | 83519639.11 | 0.104664E+09 |
March | 0.112430E+09 | 62029845.27 | 50400160.88 | 0.115385E+09 | 88677636.61 |
April | 0.102443E+09 | 43372532.56 | 59070836.17 | 0.100625E+09 | 75431464.65 |
May | 0.129386E+09 | 45613048.18 | 83772740.38 | 0.149231E+09 | 49453080.71 |
June | 0.153142E+09 | 73682114.35 | 79459870.66 | 0.210195E+09 | 28833906.45 |
July | 0.128934E+09 | 47225734.30 | 81707949.58 | 0.177848E+09 | 26905598.54 |
August | 0.134570E+09 | 66479171.86 | 68090971.48 | 0.182182E+09 | 31051054.85 |
September | 0.115474E+09 | 55377309.50 | 60096906.40 | 0.148743E+09 | 45907836.90 |
October | 0.100383E+09 | 57375825.15 | 43006691.55 | 0.108875E+09 | 94093145.40 |
November | 79712061.33 | 48394890.12 | 31317171.21 | 78512326.46 | 0.104825E+09 |
December | 66531716.14 | 39301894.90 | 27229821.24 | 58806900.96 | 0.128532E+09 |
Annual Sum or Average | 0.128936E+10 | 0.643051E+09 | 0.646305E+09 | 0.149129E+10 | 0.892388E+09 |
Minimum of Months | 66531716.14 | 39301894.90 | 27229821.24 | 58806900.96 | 26905598.54 |
Maximum of Months | 0.153142E+09 | 73682114.35 | 83772740.38 | 0.210195E+09 | 0.128532E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.942735E+09 | 0.00 | 0.942735E+09 | 0.177475E+09 | 0.471862E+10 |
February | 0.107024E+10 | 0.00 | 0.107024E+10 | 0.200196E+09 | 0.430700E+10 |
March | 0.161227E+10 | 0.00 | 0.161227E+10 | 0.730915E+09 | 0.362868E+10 |
April | 0.195946E+10 | 10870236.15 | 0.194859E+10 | 0.107840E+10 | 0.301906E+10 |
May | 0.276597E+10 | 91431654.91 | 0.267453E+10 | 0.247834E+10 | 0.187561E+10 |
June | 0.293523E+10 | 0.325418E+09 | 0.260981E+10 | 0.390606E+10 | 0.101516E+10 |
July | 0.286846E+10 | 0.185680E+09 | 0.268278E+10 | 0.386597E+10 | 0.994677E+09 |
August | 0.228308E+10 | 54009907.87 | 0.222907E+10 | 0.293483E+10 | 0.114543E+10 |
September | 0.185592E+10 | 435922.88 | 0.185548E+10 | 0.209449E+10 | 0.171025E+10 |
October | 0.137360E+10 | 0.00 | 0.137360E+10 | 0.740091E+09 | 0.362234E+10 |
November | 0.100910E+10 | 0.00 | 0.100910E+10 | 0.277462E+09 | 0.415776E+10 |
December | 0.882047E+09 | 0.00 | 0.882047E+09 | 0.155448E+09 | 0.527824E+10 |
Annual Sum or Average | 0.215581E+11 | 0.667846E+09 | 0.208902E+11 | 0.186397E+11 | 0.354728E+11 |
Minimum of Months | 0.882047E+09 | 0.00 | 0.882047E+09 | 0.155448E+09 | 0.994677E+09 |
Maximum of Months | 0.293523E+10 | 0.325418E+09 | 0.268278E+10 | 0.390606E+10 | 0.527824E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196798E+10 | 0.120603E+10 | 0.761944E+09 | 0.174873E+10 | 0.293193E+10 |
February | 0.236125E+10 | 0.149064E+10 | 0.870605E+09 | 0.221611E+10 | 0.273180E+10 |
March | 0.315532E+10 | 0.184046E+10 | 0.131485E+10 | 0.319423E+10 | 0.231226E+10 |
April | 0.313156E+10 | 0.152544E+10 | 0.160613E+10 | 0.310634E+10 | 0.194886E+10 |
May | 0.378277E+10 | 0.158007E+10 | 0.220270E+10 | 0.427292E+10 | 0.125217E+10 |
June | 0.446649E+10 | 0.234478E+10 | 0.212171E+10 | 0.600358E+10 | 0.676595E+09 |
July | 0.419574E+10 | 0.199790E+10 | 0.219784E+10 | 0.569023E+10 | 0.663264E+09 |
August | 0.423198E+10 | 0.233082E+10 | 0.190116E+10 | 0.570076E+10 | 0.760286E+09 |
September | 0.340763E+10 | 0.185112E+10 | 0.155652E+10 | 0.434527E+10 | 0.108490E+10 |
October | 0.255007E+10 | 0.139729E+10 | 0.115278E+10 | 0.266733E+10 | 0.234285E+10 |
November | 0.192087E+10 | 0.108454E+10 | 0.836331E+09 | 0.179660E+10 | 0.265332E+10 |
December | 0.171839E+10 | 0.989914E+09 | 0.728478E+09 | 0.146127E+10 | 0.331961E+10 |
Annual Sum or Average | 0.368900E+11 | 0.196390E+11 | 0.172510E+11 | 0.422034E+11 | 0.226778E+11 |
Minimum of Months | 0.171839E+10 | 0.989914E+09 | 0.728478E+09 | 0.146127E+10 | 0.663264E+09 |
Maximum of Months | 0.446649E+10 | 0.234478E+10 | 0.220270E+10 | 0.600358E+10 | 0.331961E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.903490E+10 | 0.743217E+10 | 0.160273E+10 | 0.103117E+11 | 0.428328E+10 |
February | 0.782749E+10 | 0.624056E+10 | 0.158693E+10 | 0.884636E+10 | 0.401858E+10 |
March | 0.638936E+10 | 0.420383E+10 | 0.218553E+10 | 0.732379E+10 | 0.355918E+10 |
April | 0.400474E+10 | 0.161032E+10 | 0.239442E+10 | 0.418411E+10 | 0.310150E+10 |
May | 0.379223E+10 | 0.695086E+09 | 0.309715E+10 | 0.431307E+10 | 0.205500E+10 |
June | 0.338353E+10 | 0.618411E+09 | 0.276512E+10 | 0.488992E+10 | 0.111394E+10 |
July | 0.363958E+10 | 0.651745E+09 | 0.298784E+10 | 0.527279E+10 | 0.106868E+10 |
August | 0.463392E+10 | 0.193715E+10 | 0.269678E+10 | 0.674009E+10 | 0.120836E+10 |
September | 0.576967E+10 | 0.321943E+10 | 0.255023E+10 | 0.785596E+10 | 0.175280E+10 |
October | 0.712879E+10 | 0.505803E+10 | 0.207076E+10 | 0.862163E+10 | 0.358635E+10 |
November | 0.840526E+10 | 0.670020E+10 | 0.170505E+10 | 0.980403E+10 | 0.396453E+10 |
December | 0.830554E+10 | 0.672238E+10 | 0.158315E+10 | 0.928679E+10 | 0.477593E+10 |
Annual Sum or Average | 0.723150E+11 | 0.450893E+11 | 0.272257E+11 | 0.874502E+11 | 0.344881E+11 |
Minimum of Months | 0.338353E+10 | 0.618411E+09 | 0.158315E+10 | 0.418411E+10 | 0.106868E+10 |
Maximum of Months | 0.903490E+10 | 0.743217E+10 | 0.309715E+10 | 0.103117E+11 | 0.477593E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209349E+10 | 0.132655E+10 | 0.766944E+09 | 0.200485E+10 | 0.301688E+10 |
February | 0.228015E+10 | 0.141302E+10 | 0.867136E+09 | 0.216000E+10 | 0.277887E+10 |
March | 0.295598E+10 | 0.163087E+10 | 0.132510E+10 | 0.298254E+10 | 0.236884E+10 |
April | 0.269341E+10 | 0.114034E+10 | 0.155307E+10 | 0.259844E+10 | 0.200537E+10 |
May | 0.340177E+10 | 0.119925E+10 | 0.220252E+10 | 0.386155E+10 | 0.133651E+10 |
June | 0.402636E+10 | 0.193723E+10 | 0.208913E+10 | 0.549553E+10 | 0.763660E+09 |
July | 0.338988E+10 | 0.124165E+10 | 0.214823E+10 | 0.464419E+10 | 0.721113E+09 |
August | 0.353807E+10 | 0.174785E+10 | 0.179022E+10 | 0.477309E+10 | 0.807659E+09 |
September | 0.303601E+10 | 0.145597E+10 | 0.158004E+10 | 0.391027E+10 | 0.116499E+10 |
October | 0.263923E+10 | 0.150851E+10 | 0.113071E+10 | 0.286513E+10 | 0.239293E+10 |
November | 0.209577E+10 | 0.127239E+10 | 0.823378E+09 | 0.205895E+10 | 0.269737E+10 |
December | 0.174923E+10 | 0.103332E+10 | 0.715916E+09 | 0.153317E+10 | 0.334263E+10 |
Annual Sum or Average | 0.338994E+11 | 0.169069E+11 | 0.169924E+11 | 0.388877E+11 | 0.233968E+11 |
Minimum of Months | 0.174923E+10 | 0.103332E+10 | 0.715916E+09 | 0.153317E+10 | 0.721113E+09 |
Maximum of Months | 0.402636E+10 | 0.193723E+10 | 0.220252E+10 | 0.549553E+10 | 0.334263E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 75.00 | 1664.18 | 351.98 | 0.00 | 351.98 | 0.00 | 0.00 |
February | 91.25 | 1695.53 | 442.39 | 0.00 | 442.39 | 0.00 | 0.00 |
March | 283.08 | 1282.14 | 601.95 | 0.00 | 601.95 | 0.00 | 0.00 |
April | 428.20 | 1083.93 | 755.96 | 4.19 | 751.77 | 0.00 | 0.00 |
May | 940.01 | 666.67 | 1032.69 | 34.14 | 998.56 | 0.00 | 0.00 |
June | 1504.99 | 381.09 | 1132.42 | 125.55 | 1006.87 | 0.00 | 0.00 |
July | 1440.53 | 361.60 | 1070.96 | 69.33 | 1001.64 | 0.00 | 0.00 |
August | 1095.95 | 412.08 | 852.40 | 20.16 | 832.24 | 0.00 | 0.00 |
September | 814.63 | 625.86 | 716.02 | 0.17 | 715.85 | 0.00 | 0.00 |
October | 291.78 | 1265.32 | 512.84 | 0.00 | 512.84 | 0.00 | 0.00 |
November | 119.61 | 1504.71 | 389.31 | 0.00 | 389.31 | 0.00 | 0.00 |
December | 64.16 | 1880.17 | 329.32 | 0.00 | 329.32 | 0.00 | 0.00 |
Annual Sum or Average | 598.59 | 1065.31 | 683.60 | 21.18 | 662.43 | 0.00 | 0.00 |
Minimum of Months | 64.16 | 361.60 | 329.32 | 0.00 | 329.32 | 0.00 | 0.00 |
Maximum of Months | 1504.99 | 1880.17 | 1132.42 | 125.55 | 1006.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 665.96 | 1036.88 | 734.76 | 450.28 | 284.48 | 0.00 | 0.00 |
February | 926.37 | 1078.54 | 976.05 | 616.17 | 359.87 | 0.00 | 0.00 |
March | 1200.19 | 820.60 | 1178.06 | 687.15 | 490.91 | 0.00 | 0.00 |
April | 1206.33 | 702.94 | 1208.16 | 588.52 | 619.65 | 0.00 | 0.00 |
May | 1602.35 | 447.47 | 1412.33 | 589.93 | 822.39 | 0.00 | 0.00 |
June | 2312.43 | 254.31 | 1723.18 | 904.62 | 818.56 | 0.00 | 0.00 |
July | 2120.72 | 241.16 | 1566.51 | 745.93 | 820.58 | 0.00 | 0.00 |
August | 2126.15 | 274.27 | 1580.04 | 870.23 | 709.81 | 0.00 | 0.00 |
September | 1679.24 | 399.72 | 1314.67 | 714.17 | 600.51 | 0.00 | 0.00 |
October | 1004.46 | 823.85 | 952.09 | 521.69 | 430.40 | 0.00 | 0.00 |
November | 706.18 | 965.38 | 741.08 | 418.42 | 322.66 | 0.00 | 0.00 |
December | 556.20 | 1184.34 | 641.57 | 369.59 | 271.98 | 0.00 | 0.00 |
Annual Sum or Average | 1344.17 | 683.71 | 1169.78 | 622.75 | 547.03 | 0.00 | 0.00 |
Minimum of Months | 556.20 | 241.16 | 641.57 | 369.59 | 271.98 | 0.00 | 0.00 |
Maximum of Months | 2312.43 | 1184.34 | 1723.18 | 904.62 | 822.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3871.42 | 1512.30 | 3373.25 | 2774.86 | 598.39 | 0.00 | 0.00 |
February | 3671.07 | 1582.06 | 3235.57 | 2579.60 | 655.97 | 0.00 | 0.00 |
March | 2743.93 | 1259.50 | 2385.51 | 1569.53 | 815.98 | 0.00 | 0.00 |
April | 1624.73 | 1116.25 | 1545.04 | 621.26 | 923.77 | 0.00 | 0.00 |
May | 1620.09 | 728.40 | 1415.86 | 259.52 | 1156.34 | 0.00 | 0.00 |
June | 1883.31 | 415.38 | 1305.38 | 238.58 | 1066.79 | 0.00 | 0.00 |
July | 1964.93 | 385.96 | 1358.86 | 243.33 | 1115.53 | 0.00 | 0.00 |
August | 2514.22 | 433.78 | 1730.11 | 723.25 | 1006.86 | 0.00 | 0.00 |
September | 3033.66 | 643.51 | 2225.95 | 1242.07 | 983.89 | 0.00 | 0.00 |
October | 3230.63 | 1260.21 | 2661.59 | 1888.45 | 773.13 | 0.00 | 0.00 |
November | 3800.44 | 1442.53 | 3242.77 | 2584.96 | 657.81 | 0.00 | 0.00 |
December | 3486.07 | 1698.29 | 3100.93 | 2509.85 | 591.08 | 0.00 | 0.00 |
Annual Sum or Average | 2781.98 | 1036.88 | 2293.09 | 1429.77 | 863.32 | 0.00 | 0.00 |
Minimum of Months | 1620.09 | 385.96 | 1305.38 | 238.58 | 591.08 | 0.00 | 0.00 |
Maximum of Months | 3871.42 | 1698.29 | 3373.25 | 2774.86 | 1156.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 756.94 | 1064.94 | 781.62 | 495.28 | 286.34 | 0.00 | 0.00 |
February | 899.03 | 1094.47 | 942.52 | 584.08 | 358.44 | 0.00 | 0.00 |
March | 1119.14 | 837.91 | 1103.63 | 608.90 | 494.74 | 0.00 | 0.00 |
April | 1009.51 | 721.85 | 1039.12 | 439.95 | 599.18 | 0.00 | 0.00 |
May | 1449.06 | 473.75 | 1270.08 | 447.75 | 822.33 | 0.00 | 0.00 |
June | 2118.09 | 285.25 | 1553.38 | 747.39 | 805.99 | 0.00 | 0.00 |
July | 1731.88 | 260.61 | 1265.64 | 463.58 | 802.06 | 0.00 | 0.00 |
August | 1782.18 | 290.26 | 1320.97 | 652.57 | 668.39 | 0.00 | 0.00 |
September | 1513.20 | 426.84 | 1171.30 | 561.72 | 609.59 | 0.00 | 0.00 |
October | 1078.56 | 839.35 | 985.37 | 563.21 | 422.16 | 0.00 | 0.00 |
November | 803.87 | 979.17 | 808.55 | 490.89 | 317.66 | 0.00 | 0.00 |
December | 578.88 | 1190.47 | 653.09 | 385.80 | 267.29 | 0.00 | 0.00 |
Annual Sum or Average | 1238.11 | 703.33 | 1074.94 | 536.12 | 538.83 | 0.00 | 0.00 |
Minimum of Months | 578.88 | 260.61 | 653.09 | 385.80 | 267.29 | 0.00 | 0.00 |
Maximum of Months | 2118.09 | 1190.47 | 1553.38 | 747.39 | 822.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 74.61 | 1719.50 | 351.98 | 0.00 | 351.98 | 0.00 | 0.00 |
February | 96.06 | 1731.04 | 442.39 | 0.00 | 442.39 | 0.00 | 0.00 |
March | 302.55 | 1301.50 | 601.95 | 0.00 | 601.95 | 0.00 | 0.00 |
April | 449.34 | 1122.42 | 755.96 | 4.19 | 751.77 | 0.00 | 0.00 |
May | 970.01 | 662.65 | 1032.69 | 34.14 | 998.55 | 0.00 | 0.00 |
June | 1534.20 | 373.31 | 1132.41 | 125.55 | 1006.87 | 0.00 | 0.00 |
July | 1468.09 | 352.52 | 1070.95 | 69.32 | 1001.63 | 0.00 | 0.00 |
August | 1109.62 | 415.60 | 852.40 | 20.16 | 832.23 | 0.00 | 0.00 |
September | 812.65 | 661.89 | 716.01 | 0.17 | 715.85 | 0.00 | 0.00 |
October | 279.47 | 1365.89 | 512.84 | 0.00 | 512.84 | 0.00 | 0.00 |
November | 109.40 | 1610.53 | 389.31 | 0.00 | 389.31 | 0.00 | 0.00 |
December | 60.35 | 1969.59 | 329.32 | 0.00 | 329.32 | 0.00 | 0.00 |
Annual Sum or Average | 608.39 | 1103.89 | 683.60 | 21.18 | 662.42 | 0.00 | 0.00 |
Minimum of Months | 60.35 | 352.52 | 329.32 | 0.00 | 329.32 | 0.00 | 0.00 |
Maximum of Months | 1534.20 | 1969.59 | 1132.41 | 125.55 | 1006.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 663.10 | 1087.25 | 734.75 | 450.28 | 284.48 | 0.00 | 0.00 |
February | 930.71 | 1118.53 | 976.04 | 616.17 | 359.87 | 0.00 | 0.00 |
March | 1211.57 | 854.51 | 1178.05 | 687.14 | 490.91 | 0.00 | 0.00 |
April | 1216.85 | 749.57 | 1208.16 | 588.51 | 619.64 | 0.00 | 0.00 |
May | 1616.93 | 459.30 | 1412.31 | 589.93 | 822.39 | 0.00 | 0.00 |
June | 2329.67 | 260.46 | 1723.17 | 904.61 | 818.56 | 0.00 | 0.00 |
July | 2136.47 | 246.83 | 1566.50 | 745.92 | 820.57 | 0.00 | 0.00 |
August | 2134.81 | 290.62 | 1580.03 | 870.22 | 709.81 | 0.00 | 0.00 |
September | 1677.59 | 436.55 | 1314.66 | 714.16 | 600.50 | 0.00 | 0.00 |
October | 997.15 | 906.54 | 952.08 | 521.68 | 430.40 | 0.00 | 0.00 |
November | 695.00 | 1047.86 | 741.07 | 418.41 | 322.66 | 0.00 | 0.00 |
December | 549.78 | 1253.24 | 641.57 | 369.59 | 271.98 | 0.00 | 0.00 |
Annual Sum or Average | 1348.59 | 723.83 | 1169.77 | 622.74 | 547.02 | 0.00 | 0.00 |
Minimum of Months | 549.78 | 246.83 | 641.57 | 369.59 | 271.98 | 0.00 | 0.00 |
Maximum of Months | 2329.67 | 1253.24 | 1723.17 | 904.61 | 822.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3887.68 | 1627.80 | 3373.28 | 2774.89 | 598.39 | 0.00 | 0.00 |
February | 3710.68 | 1667.91 | 3235.60 | 2579.63 | 655.98 | 0.00 | 0.00 |
March | 2783.67 | 1311.31 | 2385.54 | 1569.55 | 815.99 | 0.00 | 0.00 |
April | 1659.81 | 1169.79 | 1545.05 | 621.27 | 923.78 | 0.00 | 0.00 |
May | 1661.69 | 724.86 | 1415.87 | 259.52 | 1156.35 | 0.00 | 0.00 |
June | 1911.62 | 411.76 | 1305.38 | 238.59 | 1066.80 | 0.00 | 0.00 |
July | 1991.56 | 383.23 | 1358.87 | 243.34 | 1115.54 | 0.00 | 0.00 |
August | 2530.54 | 453.75 | 1730.12 | 723.26 | 1006.87 | 0.00 | 0.00 |
September | 3039.51 | 704.42 | 2225.97 | 1242.08 | 983.89 | 0.00 | 0.00 |
October | 3234.37 | 1390.80 | 2661.61 | 1888.47 | 773.14 | 0.00 | 0.00 |
November | 3811.38 | 1580.93 | 3242.80 | 2584.99 | 657.82 | 0.00 | 0.00 |
December | 3504.68 | 1816.56 | 3100.97 | 2509.88 | 591.09 | 0.00 | 0.00 |
Annual Sum or Average | 2805.45 | 1100.46 | 2293.12 | 1429.79 | 863.33 | 0.00 | 0.00 |
Minimum of Months | 1659.81 | 383.23 | 1305.38 | 238.59 | 591.09 | 0.00 | 0.00 |
Maximum of Months | 3887.68 | 1816.56 | 3373.28 | 2774.89 | 1156.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 759.43 | 1119.17 | 781.61 | 495.27 | 286.34 | 0.00 | 0.00 |
February | 907.68 | 1137.46 | 942.52 | 584.08 | 358.44 | 0.00 | 0.00 |
March | 1132.63 | 870.47 | 1103.63 | 608.89 | 494.73 | 0.00 | 0.00 |
April | 1020.68 | 765.12 | 1039.12 | 439.94 | 599.17 | 0.00 | 0.00 |
May | 1464.87 | 485.44 | 1270.07 | 447.74 | 822.32 | 0.00 | 0.00 |
June | 2132.07 | 292.47 | 1553.37 | 747.38 | 805.99 | 0.00 | 0.00 |
July | 1745.77 | 264.11 | 1265.63 | 463.57 | 802.05 | 0.00 | 0.00 |
August | 1788.32 | 304.80 | 1320.96 | 652.57 | 668.39 | 0.00 | 0.00 |
September | 1508.75 | 465.66 | 1171.29 | 561.71 | 609.58 | 0.00 | 0.00 |
October | 1068.73 | 923.63 | 985.37 | 563.21 | 422.16 | 0.00 | 0.00 |
November | 796.38 | 1063.27 | 808.55 | 490.89 | 317.66 | 0.00 | 0.00 |
December | 577.26 | 1261.69 | 653.08 | 385.79 | 267.29 | 0.00 | 0.00 |
Annual Sum or Average | 1243.28 | 743.98 | 1074.93 | 536.11 | 538.82 | 0.00 | 0.00 |
Minimum of Months | 577.26 | 264.11 | 653.08 | 385.79 | 267.29 | 0.00 | 0.00 |
Maximum of Months | 2132.07 | 1261.69 | 1553.37 | 747.38 | 822.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 66.26 | 1761.73 | 351.98 | 0.00 | 351.98 | 0.00 | 0.00 |
February | 82.75 | 1780.34 | 442.39 | 0.00 | 442.39 | 0.00 | 0.00 |
March | 272.89 | 1354.79 | 601.95 | 0.00 | 601.95 | 0.00 | 0.00 |
April | 416.05 | 1164.76 | 755.96 | 4.19 | 751.77 | 0.00 | 0.00 |
May | 925.30 | 700.27 | 1032.69 | 34.14 | 998.56 | 0.00 | 0.00 |
June | 1506.97 | 391.65 | 1132.42 | 125.55 | 1006.87 | 0.00 | 0.00 |
July | 1443.39 | 371.37 | 1070.96 | 69.33 | 1001.64 | 0.00 | 0.00 |
August | 1095.74 | 427.65 | 852.40 | 20.16 | 832.24 | 0.00 | 0.00 |
September | 808.06 | 659.82 | 716.02 | 0.17 | 715.85 | 0.00 | 0.00 |
October | 276.32 | 1352.43 | 512.84 | 0.00 | 512.84 | 0.00 | 0.00 |
November | 107.05 | 1604.07 | 389.31 | 0.00 | 389.31 | 0.00 | 0.00 |
December | 58.04 | 1970.67 | 329.32 | 0.00 | 329.32 | 0.00 | 0.00 |
Annual Sum or Average | 591.06 | 1124.84 | 683.60 | 21.18 | 662.43 | 0.00 | 0.00 |
Minimum of Months | 58.04 | 371.37 | 329.32 | 0.00 | 329.32 | 0.00 | 0.00 |
Maximum of Months | 1506.97 | 1970.67 | 1132.42 | 125.55 | 1006.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 652.90 | 1094.66 | 734.76 | 450.28 | 284.48 | 0.00 | 0.00 |
February | 916.05 | 1129.21 | 976.05 | 616.17 | 359.87 | 0.00 | 0.00 |
March | 1192.59 | 863.30 | 1178.06 | 687.15 | 490.91 | 0.00 | 0.00 |
April | 1198.43 | 751.87 | 1208.16 | 588.52 | 619.65 | 0.00 | 0.00 |
May | 1595.33 | 467.51 | 1412.33 | 589.93 | 822.39 | 0.00 | 0.00 |
June | 2316.20 | 261.03 | 1723.18 | 904.62 | 818.56 | 0.00 | 0.00 |
July | 2124.49 | 247.63 | 1566.51 | 745.93 | 820.58 | 0.00 | 0.00 |
August | 2128.42 | 283.86 | 1580.04 | 870.23 | 709.81 | 0.00 | 0.00 |
September | 1676.42 | 418.56 | 1314.67 | 714.17 | 600.51 | 0.00 | 0.00 |
October | 995.87 | 874.72 | 952.09 | 521.69 | 430.40 | 0.00 | 0.00 |
November | 693.13 | 1023.66 | 741.08 | 418.42 | 322.66 | 0.00 | 0.00 |
December | 545.58 | 1239.40 | 641.57 | 369.59 | 271.98 | 0.00 | 0.00 |
Annual Sum or Average | 1338.26 | 719.11 | 1169.78 | 622.75 | 547.03 | 0.00 | 0.00 |
Minimum of Months | 545.58 | 247.63 | 641.57 | 369.59 | 271.98 | 0.00 | 0.00 |
Maximum of Months | 2316.20 | 1239.40 | 1723.18 | 904.62 | 822.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3849.94 | 1599.19 | 3373.25 | 2774.86 | 598.39 | 0.00 | 0.00 |
February | 3656.73 | 1661.12 | 3235.57 | 2579.60 | 655.97 | 0.00 | 0.00 |
March | 2734.39 | 1328.84 | 2385.51 | 1569.53 | 815.98 | 0.00 | 0.00 |
April | 1614.24 | 1196.57 | 1545.04 | 621.26 | 923.77 | 0.00 | 0.00 |
May | 1610.32 | 767.25 | 1415.86 | 259.52 | 1156.34 | 0.00 | 0.00 |
June | 1886.54 | 429.76 | 1305.38 | 238.58 | 1066.79 | 0.00 | 0.00 |
July | 1968.63 | 399.00 | 1358.86 | 243.33 | 1115.53 | 0.00 | 0.00 |
August | 2516.46 | 451.15 | 1730.11 | 723.25 | 1006.86 | 0.00 | 0.00 |
September | 3030.85 | 676.23 | 2225.95 | 1242.07 | 983.89 | 0.00 | 0.00 |
October | 3218.95 | 1338.99 | 2661.59 | 1888.45 | 773.13 | 0.00 | 0.00 |
November | 3782.42 | 1529.52 | 3242.77 | 2584.96 | 657.81 | 0.00 | 0.00 |
December | 3467.29 | 1783.13 | 3100.93 | 2509.85 | 591.08 | 0.00 | 0.00 |
Annual Sum or Average | 2773.03 | 1093.61 | 2293.09 | 1429.77 | 863.32 | 0.00 | 0.00 |
Minimum of Months | 1610.32 | 399.00 | 1305.38 | 238.58 | 591.08 | 0.00 | 0.00 |
Maximum of Months | 3849.94 | 1783.13 | 3373.25 | 2774.86 | 1156.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 748.53 | 1126.38 | 781.62 | 495.28 | 286.34 | 0.00 | 0.00 |
February | 892.86 | 1148.67 | 942.52 | 584.08 | 358.44 | 0.00 | 0.00 |
March | 1113.55 | 884.42 | 1103.63 | 608.90 | 494.74 | 0.00 | 0.00 |
April | 1002.49 | 773.68 | 1039.12 | 439.95 | 599.18 | 0.00 | 0.00 |
May | 1441.74 | 499.00 | 1270.08 | 447.75 | 822.33 | 0.00 | 0.00 |
June | 2120.19 | 294.62 | 1553.38 | 747.39 | 805.99 | 0.00 | 0.00 |
July | 1733.94 | 269.23 | 1265.64 | 463.58 | 802.06 | 0.00 | 0.00 |
August | 1782.07 | 301.55 | 1320.97 | 652.57 | 668.39 | 0.00 | 0.00 |
September | 1508.59 | 449.46 | 1171.30 | 561.72 | 609.59 | 0.00 | 0.00 |
October | 1069.72 | 893.42 | 985.37 | 563.21 | 422.16 | 0.00 | 0.00 |
November | 794.35 | 1040.65 | 808.55 | 490.89 | 317.66 | 0.00 | 0.00 |
December | 572.42 | 1247.99 | 653.09 | 385.80 | 267.29 | 0.00 | 0.00 |
Annual Sum or Average | 1233.12 | 741.91 | 1074.94 | 536.12 | 538.83 | 0.00 | 0.00 |
Minimum of Months | 572.42 | 269.23 | 653.09 | 385.80 | 267.29 | 0.00 | 0.00 |
Maximum of Months | 2120.19 | 1247.99 | 1553.38 | 747.39 | 822.33 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.200881E+09 | 0.445734E+10 | 0.942735E+09 | 0.00 | 0.942735E+09 | 0.00 | 0.00 |
February | 0.220755E+09 | 0.410182E+10 | 0.107024E+10 | 0.00 | 0.107024E+10 | 0.00 | 0.00 |
March | 0.758193E+09 | 0.343410E+10 | 0.161227E+10 | 0.00 | 0.161227E+10 | 0.00 | 0.00 |
April | 0.110990E+10 | 0.280955E+10 | 0.195946E+10 | 10870236.15 | 0.194859E+10 | 0.00 | 0.00 |
May | 0.251772E+10 | 0.178561E+10 | 0.276597E+10 | 91431654.91 | 0.267453E+10 | 0.00 | 0.00 |
June | 0.390093E+10 | 0.987794E+09 | 0.293523E+10 | 0.325418E+09 | 0.260981E+10 | 0.00 | 0.00 |
July | 0.385832E+10 | 0.968496E+09 | 0.286846E+10 | 0.185680E+09 | 0.268278E+10 | 0.00 | 0.00 |
August | 0.293540E+10 | 0.110372E+10 | 0.228308E+10 | 54009907.87 | 0.222907E+10 | 0.00 | 0.00 |
September | 0.211152E+10 | 0.162224E+10 | 0.185592E+10 | 435922.88 | 0.185548E+10 | 0.00 | 0.00 |
October | 0.781510E+09 | 0.338902E+10 | 0.137360E+10 | 0.00 | 0.137360E+10 | 0.00 | 0.00 |
November | 0.310034E+09 | 0.390022E+10 | 0.100910E+10 | 0.00 | 0.100910E+10 | 0.00 | 0.00 |
December | 0.171855E+09 | 0.503584E+10 | 0.882047E+09 | 0.00 | 0.882047E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.188770E+11 | 0.335957E+11 | 0.215581E+11 | 0.667846E+09 | 0.208902E+11 | 0.00 | 0.00 |
Minimum of Months | 0.171855E+09 | 0.968496E+09 | 0.882047E+09 | 0.00 | 0.882047E+09 | 0.00 | 0.00 |
Maximum of Months | 0.390093E+10 | 0.503584E+10 | 0.293523E+10 | 0.325418E+09 | 0.268278E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.178372E+10 | 0.277718E+10 | 0.196798E+10 | 0.120603E+10 | 0.761944E+09 | 0.00 | 0.00 |
February | 0.224108E+10 | 0.260921E+10 | 0.236125E+10 | 0.149064E+10 | 0.870605E+09 | 0.00 | 0.00 |
March | 0.321458E+10 | 0.219789E+10 | 0.315532E+10 | 0.184046E+10 | 0.131485E+10 | 0.00 | 0.00 |
April | 0.312680E+10 | 0.182201E+10 | 0.313156E+10 | 0.152544E+10 | 0.160613E+10 | 0.00 | 0.00 |
May | 0.429173E+10 | 0.119850E+10 | 0.378277E+10 | 0.158007E+10 | 0.220270E+10 | 0.00 | 0.00 |
June | 0.599382E+10 | 0.659181E+09 | 0.446649E+10 | 0.234478E+10 | 0.212171E+10 | 0.00 | 0.00 |
July | 0.568013E+10 | 0.645922E+09 | 0.419574E+10 | 0.199790E+10 | 0.219784E+10 | 0.00 | 0.00 |
August | 0.569469E+10 | 0.734612E+09 | 0.423198E+10 | 0.233082E+10 | 0.190116E+10 | 0.00 | 0.00 |
September | 0.435260E+10 | 0.103609E+10 | 0.340763E+10 | 0.185112E+10 | 0.155652E+10 | 0.00 | 0.00 |
October | 0.269034E+10 | 0.220660E+10 | 0.255007E+10 | 0.139729E+10 | 0.115278E+10 | 0.00 | 0.00 |
November | 0.183041E+10 | 0.250227E+10 | 0.192087E+10 | 0.108454E+10 | 0.836331E+09 | 0.00 | 0.00 |
December | 0.148974E+10 | 0.317213E+10 | 0.171839E+10 | 0.989914E+09 | 0.728478E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.423896E+11 | 0.215616E+11 | 0.368900E+11 | 0.196390E+11 | 0.172510E+11 | 0.00 | 0.00 |
Minimum of Months | 0.148974E+10 | 0.645922E+09 | 0.171839E+10 | 0.989914E+09 | 0.728478E+09 | 0.00 | 0.00 |
Maximum of Months | 0.599382E+10 | 0.317213E+10 | 0.446649E+10 | 0.234478E+10 | 0.220270E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.103692E+11 | 0.405055E+10 | 0.903490E+10 | 0.743217E+10 | 0.160273E+10 | 0.00 | 0.00 |
February | 0.888105E+10 | 0.382731E+10 | 0.782749E+10 | 0.624056E+10 | 0.158693E+10 | 0.00 | 0.00 |
March | 0.734935E+10 | 0.337345E+10 | 0.638936E+10 | 0.420383E+10 | 0.218553E+10 | 0.00 | 0.00 |
April | 0.421131E+10 | 0.289333E+10 | 0.400474E+10 | 0.161032E+10 | 0.239442E+10 | 0.00 | 0.00 |
May | 0.433925E+10 | 0.195096E+10 | 0.379223E+10 | 0.695086E+09 | 0.309715E+10 | 0.00 | 0.00 |
June | 0.488154E+10 | 0.107667E+10 | 0.338353E+10 | 0.618411E+09 | 0.276512E+10 | 0.00 | 0.00 |
July | 0.526288E+10 | 0.103375E+10 | 0.363958E+10 | 0.651745E+09 | 0.298784E+10 | 0.00 | 0.00 |
August | 0.673409E+10 | 0.116185E+10 | 0.463392E+10 | 0.193715E+10 | 0.269678E+10 | 0.00 | 0.00 |
September | 0.786325E+10 | 0.166797E+10 | 0.576967E+10 | 0.321943E+10 | 0.255023E+10 | 0.00 | 0.00 |
October | 0.865291E+10 | 0.337534E+10 | 0.712879E+10 | 0.505803E+10 | 0.207076E+10 | 0.00 | 0.00 |
November | 0.985075E+10 | 0.373904E+10 | 0.840526E+10 | 0.670020E+10 | 0.170505E+10 | 0.00 | 0.00 |
December | 0.933709E+10 | 0.454869E+10 | 0.830554E+10 | 0.672238E+10 | 0.158315E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.877327E+11 | 0.326989E+11 | 0.723150E+11 | 0.450893E+11 | 0.272257E+11 | 0.00 | 0.00 |
Minimum of Months | 0.421131E+10 | 0.103375E+10 | 0.338353E+10 | 0.618411E+09 | 0.158315E+10 | 0.00 | 0.00 |
Maximum of Months | 0.103692E+11 | 0.454869E+10 | 0.903490E+10 | 0.743217E+10 | 0.309715E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.202740E+10 | 0.285234E+10 | 0.209349E+10 | 0.132655E+10 | 0.766944E+09 | 0.00 | 0.00 |
February | 0.217494E+10 | 0.264775E+10 | 0.228015E+10 | 0.141302E+10 | 0.867136E+09 | 0.00 | 0.00 |
March | 0.299751E+10 | 0.224425E+10 | 0.295598E+10 | 0.163087E+10 | 0.132510E+10 | 0.00 | 0.00 |
April | 0.261664E+10 | 0.187103E+10 | 0.269341E+10 | 0.114034E+10 | 0.155307E+10 | 0.00 | 0.00 |
May | 0.388115E+10 | 0.126888E+10 | 0.340177E+10 | 0.119925E+10 | 0.220252E+10 | 0.00 | 0.00 |
June | 0.549009E+10 | 0.739362E+09 | 0.402636E+10 | 0.193723E+10 | 0.208913E+10 | 0.00 | 0.00 |
July | 0.463866E+10 | 0.698012E+09 | 0.338988E+10 | 0.124165E+10 | 0.214823E+10 | 0.00 | 0.00 |
August | 0.477339E+10 | 0.777426E+09 | 0.353807E+10 | 0.174785E+10 | 0.179022E+10 | 0.00 | 0.00 |
September | 0.392221E+10 | 0.110638E+10 | 0.303601E+10 | 0.145597E+10 | 0.158004E+10 | 0.00 | 0.00 |
October | 0.288883E+10 | 0.224811E+10 | 0.263923E+10 | 0.150851E+10 | 0.113071E+10 | 0.00 | 0.00 |
November | 0.208362E+10 | 0.253802E+10 | 0.209577E+10 | 0.127239E+10 | 0.823378E+09 | 0.00 | 0.00 |
December | 0.155046E+10 | 0.318854E+10 | 0.174923E+10 | 0.103332E+10 | 0.715916E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.390449E+11 | 0.221801E+11 | 0.338994E+11 | 0.169069E+11 | 0.169924E+11 | 0.00 | 0.00 |
Minimum of Months | 0.155046E+10 | 0.698012E+09 | 0.174923E+10 | 0.103332E+10 | 0.715916E+09 | 0.00 | 0.00 |
Maximum of Months | 0.549009E+10 | 0.318854E+10 | 0.402636E+10 | 0.193723E+10 | 0.220252E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.199842E+09 | 0.460552E+10 | 0.942730E+09 | 0.00 | 0.942730E+09 | 0.00 | 0.00 |
February | 0.232399E+09 | 0.418773E+10 | 0.107023E+10 | 0.00 | 0.107023E+10 | 0.00 | 0.00 |
March | 0.810348E+09 | 0.348595E+10 | 0.161226E+10 | 0.00 | 0.161226E+10 | 0.00 | 0.00 |
April | 0.116470E+10 | 0.290932E+10 | 0.195945E+10 | 10870179.82 | 0.194858E+10 | 0.00 | 0.00 |
May | 0.259807E+10 | 0.177483E+10 | 0.276595E+10 | 91431181.13 | 0.267452E+10 | 0.00 | 0.00 |
June | 0.397664E+10 | 0.967631E+09 | 0.293521E+10 | 0.325416E+09 | 0.260980E+10 | 0.00 | 0.00 |
July | 0.393213E+10 | 0.944181E+09 | 0.286845E+10 | 0.185680E+09 | 0.268277E+10 | 0.00 | 0.00 |
August | 0.297200E+10 | 0.111315E+10 | 0.228306E+10 | 54009628.00 | 0.222906E+10 | 0.00 | 0.00 |
September | 0.210639E+10 | 0.171561E+10 | 0.185591E+10 | 435920.62 | 0.185547E+10 | 0.00 | 0.00 |
October | 0.748540E+09 | 0.365841E+10 | 0.137359E+10 | 0.00 | 0.137359E+10 | 0.00 | 0.00 |
November | 0.283558E+09 | 0.417448E+10 | 0.100909E+10 | 0.00 | 0.100909E+10 | 0.00 | 0.00 |
December | 0.161648E+09 | 0.527535E+10 | 0.882042E+09 | 0.00 | 0.882042E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.191863E+11 | 0.348122E+11 | 0.215580E+11 | 0.667843E+09 | 0.208901E+11 | 0.00 | 0.00 |
Minimum of Months | 0.161648E+09 | 0.944181E+09 | 0.882042E+09 | 0.00 | 0.882042E+09 | 0.00 | 0.00 |
Maximum of Months | 0.397664E+10 | 0.527535E+10 | 0.293521E+10 | 0.325416E+09 | 0.268277E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.177604E+10 | 0.291210E+10 | 0.196796E+10 | 0.120602E+10 | 0.761940E+09 | 0.00 | 0.00 |
February | 0.225157E+10 | 0.270595E+10 | 0.236123E+10 | 0.149063E+10 | 0.870601E+09 | 0.00 | 0.00 |
March | 0.324506E+10 | 0.228872E+10 | 0.315529E+10 | 0.184044E+10 | 0.131485E+10 | 0.00 | 0.00 |
April | 0.315407E+10 | 0.194289E+10 | 0.313154E+10 | 0.152542E+10 | 0.160612E+10 | 0.00 | 0.00 |
May | 0.433080E+10 | 0.123018E+10 | 0.378274E+10 | 0.158006E+10 | 0.220269E+10 | 0.00 | 0.00 |
June | 0.603850E+10 | 0.675119E+09 | 0.446645E+10 | 0.234476E+10 | 0.212170E+10 | 0.00 | 0.00 |
July | 0.572231E+10 | 0.661117E+09 | 0.419571E+10 | 0.199788E+10 | 0.219782E+10 | 0.00 | 0.00 |
August | 0.571787E+10 | 0.778405E+09 | 0.423195E+10 | 0.233079E+10 | 0.190115E+10 | 0.00 | 0.00 |
September | 0.434832E+10 | 0.113155E+10 | 0.340761E+10 | 0.185110E+10 | 0.155651E+10 | 0.00 | 0.00 |
October | 0.267076E+10 | 0.242807E+10 | 0.255005E+10 | 0.139727E+10 | 0.115278E+10 | 0.00 | 0.00 |
November | 0.180143E+10 | 0.271606E+10 | 0.192086E+10 | 0.108453E+10 | 0.836327E+09 | 0.00 | 0.00 |
December | 0.147253E+10 | 0.335668E+10 | 0.171838E+10 | 0.989904E+09 | 0.728474E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.425293E+11 | 0.228268E+11 | 0.368898E+11 | 0.196388E+11 | 0.172509E+11 | 0.00 | 0.00 |
Minimum of Months | 0.147253E+10 | 0.661117E+09 | 0.171838E+10 | 0.989904E+09 | 0.728474E+09 | 0.00 | 0.00 |
Maximum of Months | 0.603850E+10 | 0.335668E+10 | 0.446645E+10 | 0.234476E+10 | 0.220269E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104128E+11 | 0.435990E+10 | 0.903500E+10 | 0.743226E+10 | 0.160274E+10 | 0.00 | 0.00 |
February | 0.897687E+10 | 0.403502E+10 | 0.782757E+10 | 0.624064E+10 | 0.158694E+10 | 0.00 | 0.00 |
March | 0.745578E+10 | 0.351222E+10 | 0.638942E+10 | 0.420388E+10 | 0.218554E+10 | 0.00 | 0.00 |
April | 0.430223E+10 | 0.303208E+10 | 0.400477E+10 | 0.161033E+10 | 0.239444E+10 | 0.00 | 0.00 |
May | 0.445067E+10 | 0.194148E+10 | 0.379226E+10 | 0.695095E+09 | 0.309717E+10 | 0.00 | 0.00 |
June | 0.495493E+10 | 0.106727E+10 | 0.338355E+10 | 0.618419E+09 | 0.276514E+10 | 0.00 | 0.00 |
July | 0.533419E+10 | 0.102643E+10 | 0.363961E+10 | 0.651752E+09 | 0.298786E+10 | 0.00 | 0.00 |
August | 0.677781E+10 | 0.121533E+10 | 0.463396E+10 | 0.193717E+10 | 0.269679E+10 | 0.00 | 0.00 |
September | 0.787842E+10 | 0.182586E+10 | 0.576972E+10 | 0.321947E+10 | 0.255025E+10 | 0.00 | 0.00 |
October | 0.866294E+10 | 0.372512E+10 | 0.712886E+10 | 0.505809E+10 | 0.207077E+10 | 0.00 | 0.00 |
November | 0.987911E+10 | 0.409776E+10 | 0.840535E+10 | 0.670028E+10 | 0.170507E+10 | 0.00 | 0.00 |
December | 0.938695E+10 | 0.486548E+10 | 0.830563E+10 | 0.672246E+10 | 0.158317E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.884727E+11 | 0.347040E+11 | 0.723157E+11 | 0.450899E+11 | 0.272259E+11 | 0.00 | 0.00 |
Minimum of Months | 0.430223E+10 | 0.102643E+10 | 0.338355E+10 | 0.618419E+09 | 0.158317E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104128E+11 | 0.486548E+10 | 0.903500E+10 | 0.743226E+10 | 0.309717E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.203405E+10 | 0.299758E+10 | 0.209348E+10 | 0.132654E+10 | 0.766941E+09 | 0.00 | 0.00 |
February | 0.219586E+10 | 0.275175E+10 | 0.228014E+10 | 0.141300E+10 | 0.867133E+09 | 0.00 | 0.00 |
March | 0.303364E+10 | 0.233146E+10 | 0.295595E+10 | 0.163086E+10 | 0.132509E+10 | 0.00 | 0.00 |
April | 0.264559E+10 | 0.198320E+10 | 0.269339E+10 | 0.114033E+10 | 0.155306E+10 | 0.00 | 0.00 |
May | 0.392352E+10 | 0.130019E+10 | 0.340174E+10 | 0.119924E+10 | 0.220251E+10 | 0.00 | 0.00 |
June | 0.552633E+10 | 0.758085E+09 | 0.402633E+10 | 0.193721E+10 | 0.208912E+10 | 0.00 | 0.00 |
July | 0.467588E+10 | 0.707387E+09 | 0.338986E+10 | 0.124164E+10 | 0.214822E+10 | 0.00 | 0.00 |
August | 0.478983E+10 | 0.816377E+09 | 0.353805E+10 | 0.174784E+10 | 0.179021E+10 | 0.00 | 0.00 |
September | 0.391067E+10 | 0.120698E+10 | 0.303599E+10 | 0.145595E+10 | 0.158004E+10 | 0.00 | 0.00 |
October | 0.286249E+10 | 0.247384E+10 | 0.263921E+10 | 0.150850E+10 | 0.113071E+10 | 0.00 | 0.00 |
November | 0.206421E+10 | 0.275599E+10 | 0.209575E+10 | 0.127237E+10 | 0.823375E+09 | 0.00 | 0.00 |
December | 0.154612E+10 | 0.337930E+10 | 0.174922E+10 | 0.103331E+10 | 0.715912E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.392082E+11 | 0.234622E+11 | 0.338991E+11 | 0.169068E+11 | 0.169923E+11 | 0.00 | 0.00 |
Minimum of Months | 0.154612E+10 | 0.707387E+09 | 0.174922E+10 | 0.103331E+10 | 0.715912E+09 | 0.00 | 0.00 |
Maximum of Months | 0.552633E+10 | 0.337930E+10 | 0.402633E+10 | 0.193721E+10 | 0.220251E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.177475E+09 | 0.471862E+10 | 0.942735E+09 | 0.00 | 0.942735E+09 | 0.00 | 0.00 |
February | 0.200196E+09 | 0.430700E+10 | 0.107024E+10 | 0.00 | 0.107024E+10 | 0.00 | 0.00 |
March | 0.730915E+09 | 0.362868E+10 | 0.161227E+10 | 0.00 | 0.161227E+10 | 0.00 | 0.00 |
April | 0.107840E+10 | 0.301906E+10 | 0.195946E+10 | 10870236.15 | 0.194859E+10 | 0.00 | 0.00 |
May | 0.247834E+10 | 0.187561E+10 | 0.276597E+10 | 91431654.91 | 0.267453E+10 | 0.00 | 0.00 |
June | 0.390606E+10 | 0.101516E+10 | 0.293523E+10 | 0.325418E+09 | 0.260981E+10 | 0.00 | 0.00 |
July | 0.386597E+10 | 0.994677E+09 | 0.286846E+10 | 0.185680E+09 | 0.268278E+10 | 0.00 | 0.00 |
August | 0.293483E+10 | 0.114543E+10 | 0.228308E+10 | 54009907.87 | 0.222907E+10 | 0.00 | 0.00 |
September | 0.209449E+10 | 0.171025E+10 | 0.185592E+10 | 435922.88 | 0.185548E+10 | 0.00 | 0.00 |
October | 0.740091E+09 | 0.362234E+10 | 0.137360E+10 | 0.00 | 0.137360E+10 | 0.00 | 0.00 |
November | 0.277462E+09 | 0.415776E+10 | 0.100910E+10 | 0.00 | 0.100910E+10 | 0.00 | 0.00 |
December | 0.155448E+09 | 0.527824E+10 | 0.882047E+09 | 0.00 | 0.882047E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.186397E+11 | 0.354728E+11 | 0.215581E+11 | 0.667846E+09 | 0.208902E+11 | 0.00 | 0.00 |
Minimum of Months | 0.155448E+09 | 0.994677E+09 | 0.882047E+09 | 0.00 | 0.882047E+09 | 0.00 | 0.00 |
Maximum of Months | 0.390606E+10 | 0.527824E+10 | 0.293523E+10 | 0.325418E+09 | 0.268278E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.174873E+10 | 0.293193E+10 | 0.196798E+10 | 0.120603E+10 | 0.761944E+09 | 0.00 | 0.00 |
February | 0.221611E+10 | 0.273180E+10 | 0.236125E+10 | 0.149064E+10 | 0.870605E+09 | 0.00 | 0.00 |
March | 0.319423E+10 | 0.231226E+10 | 0.315532E+10 | 0.184046E+10 | 0.131485E+10 | 0.00 | 0.00 |
April | 0.310634E+10 | 0.194886E+10 | 0.313156E+10 | 0.152544E+10 | 0.160613E+10 | 0.00 | 0.00 |
May | 0.427292E+10 | 0.125217E+10 | 0.378277E+10 | 0.158007E+10 | 0.220270E+10 | 0.00 | 0.00 |
June | 0.600358E+10 | 0.676595E+09 | 0.446649E+10 | 0.234478E+10 | 0.212171E+10 | 0.00 | 0.00 |
July | 0.569023E+10 | 0.663264E+09 | 0.419574E+10 | 0.199790E+10 | 0.219784E+10 | 0.00 | 0.00 |
August | 0.570076E+10 | 0.760286E+09 | 0.423198E+10 | 0.233082E+10 | 0.190116E+10 | 0.00 | 0.00 |
September | 0.434527E+10 | 0.108490E+10 | 0.340763E+10 | 0.185112E+10 | 0.155652E+10 | 0.00 | 0.00 |
October | 0.266733E+10 | 0.234285E+10 | 0.255007E+10 | 0.139729E+10 | 0.115278E+10 | 0.00 | 0.00 |
November | 0.179660E+10 | 0.265332E+10 | 0.192087E+10 | 0.108454E+10 | 0.836331E+09 | 0.00 | 0.00 |
December | 0.146127E+10 | 0.331961E+10 | 0.171839E+10 | 0.989914E+09 | 0.728478E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.422034E+11 | 0.226778E+11 | 0.368900E+11 | 0.196390E+11 | 0.172510E+11 | 0.00 | 0.00 |
Minimum of Months | 0.146127E+10 | 0.663264E+09 | 0.171839E+10 | 0.989914E+09 | 0.728478E+09 | 0.00 | 0.00 |
Maximum of Months | 0.600358E+10 | 0.331961E+10 | 0.446649E+10 | 0.234478E+10 | 0.220270E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.103117E+11 | 0.428328E+10 | 0.903490E+10 | 0.743217E+10 | 0.160273E+10 | 0.00 | 0.00 |
February | 0.884636E+10 | 0.401858E+10 | 0.782749E+10 | 0.624056E+10 | 0.158693E+10 | 0.00 | 0.00 |
March | 0.732379E+10 | 0.355918E+10 | 0.638936E+10 | 0.420383E+10 | 0.218553E+10 | 0.00 | 0.00 |
April | 0.418411E+10 | 0.310150E+10 | 0.400474E+10 | 0.161032E+10 | 0.239442E+10 | 0.00 | 0.00 |
May | 0.431307E+10 | 0.205500E+10 | 0.379223E+10 | 0.695086E+09 | 0.309715E+10 | 0.00 | 0.00 |
June | 0.488992E+10 | 0.111394E+10 | 0.338353E+10 | 0.618411E+09 | 0.276512E+10 | 0.00 | 0.00 |
July | 0.527279E+10 | 0.106868E+10 | 0.363958E+10 | 0.651745E+09 | 0.298784E+10 | 0.00 | 0.00 |
August | 0.674009E+10 | 0.120836E+10 | 0.463392E+10 | 0.193715E+10 | 0.269678E+10 | 0.00 | 0.00 |
September | 0.785596E+10 | 0.175280E+10 | 0.576967E+10 | 0.321943E+10 | 0.255023E+10 | 0.00 | 0.00 |
October | 0.862163E+10 | 0.358635E+10 | 0.712879E+10 | 0.505803E+10 | 0.207076E+10 | 0.00 | 0.00 |
November | 0.980403E+10 | 0.396453E+10 | 0.840526E+10 | 0.670020E+10 | 0.170505E+10 | 0.00 | 0.00 |
December | 0.928679E+10 | 0.477593E+10 | 0.830554E+10 | 0.672238E+10 | 0.158315E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.874502E+11 | 0.344881E+11 | 0.723150E+11 | 0.450893E+11 | 0.272257E+11 | 0.00 | 0.00 |
Minimum of Months | 0.418411E+10 | 0.106868E+10 | 0.338353E+10 | 0.618411E+09 | 0.158315E+10 | 0.00 | 0.00 |
Maximum of Months | 0.103117E+11 | 0.477593E+10 | 0.903490E+10 | 0.743217E+10 | 0.309715E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.200485E+10 | 0.301688E+10 | 0.209349E+10 | 0.132655E+10 | 0.766944E+09 | 0.00 | 0.00 |
February | 0.216000E+10 | 0.277887E+10 | 0.228015E+10 | 0.141302E+10 | 0.867136E+09 | 0.00 | 0.00 |
March | 0.298254E+10 | 0.236884E+10 | 0.295598E+10 | 0.163087E+10 | 0.132510E+10 | 0.00 | 0.00 |
April | 0.259844E+10 | 0.200537E+10 | 0.269341E+10 | 0.114034E+10 | 0.155307E+10 | 0.00 | 0.00 |
May | 0.386155E+10 | 0.133651E+10 | 0.340177E+10 | 0.119925E+10 | 0.220252E+10 | 0.00 | 0.00 |
June | 0.549553E+10 | 0.763660E+09 | 0.402636E+10 | 0.193723E+10 | 0.208913E+10 | 0.00 | 0.00 |
July | 0.464419E+10 | 0.721113E+09 | 0.338988E+10 | 0.124165E+10 | 0.214823E+10 | 0.00 | 0.00 |
August | 0.477309E+10 | 0.807659E+09 | 0.353807E+10 | 0.174785E+10 | 0.179022E+10 | 0.00 | 0.00 |
September | 0.391027E+10 | 0.116499E+10 | 0.303601E+10 | 0.145597E+10 | 0.158004E+10 | 0.00 | 0.00 |
October | 0.286513E+10 | 0.239293E+10 | 0.263923E+10 | 0.150851E+10 | 0.113071E+10 | 0.00 | 0.00 |
November | 0.205895E+10 | 0.269737E+10 | 0.209577E+10 | 0.127239E+10 | 0.823378E+09 | 0.00 | 0.00 |
December | 0.153317E+10 | 0.334263E+10 | 0.174923E+10 | 0.103332E+10 | 0.715916E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.388877E+11 | 0.233968E+11 | 0.338994E+11 | 0.169069E+11 | 0.169924E+11 | 0.00 | 0.00 |
Minimum of Months | 0.153317E+10 | 0.721113E+09 | 0.174923E+10 | 0.103332E+10 | 0.715916E+09 | 0.00 | 0.00 |
Maximum of Months | 0.549553E+10 | 0.334263E+10 | 0.402636E+10 | 0.193723E+10 | 0.220252E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.548429E+10 | -0.477000E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -714286556.4 | 58.98 | 0.00 | 0.00 |
February | 0.503446E+10 | -0.438886E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -645601615.6 | 58.98 | 0.00 | 0.00 |
March | 0.582645E+10 | -0.511858E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -707865363.9 | 58.98 | 0.00 | 0.00 |
April | 0.510716E+10 | -0.442519E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -681973265.0 | 58.98 | 0.00 | 0.00 |
May | 0.517700E+10 | -0.448521E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691784890.3 | 58.98 | 0.00 | 0.00 |
June | 0.485896E+10 | -0.419150E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667461857.0 | 58.98 | 0.00 | 0.00 |
July | 0.445663E+10 | -0.376945E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687177580.6 | 58.98 | 0.00 | 0.00 |
August | 0.479027E+10 | -0.410191E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688359819.4 | 58.98 | 0.00 | 0.00 |
September | 0.443124E+10 | -0.376489E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666342017.3 | 58.98 | 0.00 | 0.00 |
October | 0.477457E+10 | -0.407943E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -695141857.3 | 58.98 | 0.00 | 0.00 |
November | 0.494222E+10 | -0.426178E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -680443442.4 | 58.99 | 0.00 | 0.00 |
December | 0.517917E+10 | -0.446012E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -719051059.8 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.600624E+11 | -0.518169E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.824549E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.443124E+10 | -0.511858E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -719051059.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.582645E+10 | -0.376489E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -645601615.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.63 | 0.62 | 01-JAN-07:00 | 9399.41 | 37.37 | 256.83 | 263.33 | 5095.18 | 34.69 | 232.50 | 257.00 |
February | 245.50 | 0.62 | 0.62 | 01-FEB-10:39 | 12764.06 | 38.85 | 241.00 | 260.50 | 2051.05 | 24.43 | 108.17 | 234.00 |
March | 296.17 | 0.63 | 0.62 | 01-MAR-06:00 | 2447.71 | 17.99 | 10.33 | 323.33 | 1383.38 | 20.44 | 98.67 | 281.33 |
April | 296.67 | 0.64 | 0.62 | 03-APR-09:39 | 1829.97 | 17.71 | 0.00 | 334.17 | 1066.12 | 20.48 | 115.83 | 288.17 |
May | 415.33 | 0.63 | 0.62 | 01-MAY-05:49 | 1636.41 | 17.79 | 0.00 | 386.00 | 903.50 | 20.55 | 188.67 | 344.33 |
June | 421.50 | 0.64 | 0.62 | 01-JUN-05:40 | 1319.18 | 17.26 | 0.00 | 382.67 | 792.18 | 20.11 | 109.50 | 337.83 |
July | 430.33 | 0.64 | 0.62 | 01-JUL-05:49 | 1487.93 | 17.41 | 0.00 | 387.67 | 843.51 | 20.20 | 167.67 | 345.83 |
August | 394.50 | 0.64 | 0.62 | 01-AUG-05:00 | 1594.96 | 17.18 | 0.00 | 363.50 | 975.60 | 19.97 | 115.50 | 324.33 |
September | 354.00 | 0.63 | 0.62 | 01-SEP-06:10 | 2637.07 | 19.06 | 29.50 | 325.83 | 1216.93 | 20.41 | 132.33 | 296.17 |
October | 262.67 | 0.63 | 0.62 | 01-OCT-06:30 | 12422.75 | 36.13 | 239.67 | 297.50 | 1708.53 | 21.06 | 98.00 | 264.50 |
November | 257.67 | 0.63 | 0.62 | 01-NOV-08:39 | 10853.54 | 38.43 | 248.33 | 260.00 | 3226.78 | 29.54 | 174.50 | 238.67 |
December | 251.17 | 0.63 | 0.62 | 01-DEC-07:40 | 8778.64 | 37.56 | 233.50 | 251.33 | 7209.95 | 40.38 | 248.33 | 241.83 |
Annual Sum or Average | 3902.00 | 0.63 | 4793.34 | 24.34 | 1259.17 | 3835.83 | 1952.14 | 23.53 | 1789.67 | 3454.00 | ||
Minimum of Months | 245.50 | 0.62 | 0.62 | 1319.18 | 17.18 | 0.00 | 251.33 | 792.18 | 19.97 | 98.00 | 234.00 | |
Maximum of Months | 430.33 | 0.64 | 0.62 | 12764.06 | 38.85 | 256.83 | 387.67 | 7209.95 | 40.38 | 248.33 | 345.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.66 | 0.62 | 01-JAN-07:49 | 2178.26 | 19.86 | 82.50 | 224.00 | 1313.62 | 22.78 | 87.17 | 186.83 |
February | 245.50 | 0.64 | 0.62 | 01-FEB-10:39 | 3496.99 | 22.23 | 84.33 | 240.17 | 2076.51 | 23.18 | 67.83 | 190.83 |
March | 296.17 | 0.64 | 0.62 | 01-MAR-06:49 | 3169.89 | 19.61 | 68.83 | 309.17 | 1849.87 | 22.59 | 64.83 | 265.83 |
April | 296.67 | 0.63 | 0.62 | 03-APR-09:39 | 3619.83 | 20.82 | 84.83 | 334.17 | 1587.24 | 22.11 | 52.50 | 287.00 |
May | 415.33 | 0.63 | 0.62 | 01-MAY-05:40 | 2881.50 | 20.73 | 111.50 | 393.33 | 1563.77 | 22.39 | 83.50 | 356.00 |
June | 421.50 | 0.63 | 0.62 | 01-JUN-04:00 | 3442.76 | 20.34 | 109.00 | 394.50 | 1952.92 | 22.10 | 79.67 | 363.67 |
July | 430.33 | 0.63 | 0.62 | 01-JUL-04:00 | 3086.20 | 20.45 | 114.17 | 397.83 | 1663.79 | 22.10 | 84.83 | 362.33 |
August | 394.50 | 0.64 | 0.62 | 01-AUG-05:49 | 4219.63 | 20.77 | 116.50 | 362.67 | 1681.40 | 21.53 | 69.00 | 329.00 |
September | 354.00 | 0.64 | 0.62 | 01-SEP-05:49 | 3480.91 | 21.22 | 105.50 | 324.83 | 1344.60 | 21.13 | 57.50 | 297.33 |
October | 262.67 | 0.64 | 0.62 | 01-OCT-06:19 | 3059.38 | 20.28 | 67.67 | 278.83 | 1798.24 | 23.03 | 56.83 | 227.50 |
November | 257.67 | 0.65 | 0.62 | 01-NOV-08:39 | 2160.91 | 20.04 | 69.50 | 231.33 | 1126.31 | 21.07 | 70.33 | 188.67 |
December | 251.17 | 0.65 | 0.62 | 01-DEC-07:49 | 2175.57 | 20.68 | 78.00 | 219.83 | 1362.38 | 23.46 | 87.17 | 178.17 |
Annual Sum or Average | 3902.00 | 0.64 | 3140.24 | 20.58 | 1092.33 | 3710.67 | 1620.81 | 22.22 | 861.17 | 3233.17 | ||
Minimum of Months | 245.50 | 0.63 | 0.62 | 2160.91 | 19.61 | 67.67 | 219.83 | 1126.31 | 21.07 | 52.50 | 178.17 | |
Maximum of Months | 430.33 | 0.66 | 0.62 | 4219.63 | 22.23 | 116.50 | 397.83 | 2076.51 | 23.46 | 87.17 | 363.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.67 | 0.62 | 01-JAN-08:39 | 474.16 | 12.82 | 0.00 | 197.17 | 319.09 | 16.21 | 0.00 | 94.50 |
February | 245.50 | 0.64 | 0.62 | 01-FEB-10:39 | 563.90 | 14.41 | 0.00 | 228.33 | 392.67 | 17.73 | 0.00 | 148.17 |
March | 296.17 | 0.64 | 0.62 | 01-MAR-07:10 | 736.84 | 15.92 | 0.00 | 305.83 | 480.76 | 18.89 | 0.17 | 228.33 |
April | 296.67 | 0.63 | 0.62 | 03-APR-09:39 | 991.77 | 17.26 | 0.00 | 339.67 | 589.72 | 19.98 | 21.00 | 278.83 |
May | 415.33 | 0.63 | 0.62 | 01-MAY-05:40 | 1209.86 | 17.91 | 0.00 | 403.67 | 672.88 | 20.77 | 114.50 | 371.17 |
June | 421.50 | 0.63 | 0.62 | 01-JUN-04:00 | 1296.32 | 18.08 | 0.00 | 413.83 | 738.58 | 23.47 | 190.00 | 399.00 |
July | 430.33 | 0.63 | 0.62 | 01-JUL-05:10 | 1240.71 | 17.84 | 0.00 | 413.17 | 689.66 | 21.81 | 151.00 | 385.67 |
August | 394.50 | 0.63 | 0.62 | 01-AUG-05:49 | 962.19 | 17.14 | 0.00 | 373.83 | 597.74 | 19.90 | 47.50 | 335.67 |
September | 354.00 | 0.63 | 0.62 | 01-SEP-06:10 | 808.97 | 16.46 | 0.00 | 320.33 | 513.92 | 19.33 | 5.00 | 272.17 |
October | 262.67 | 0.64 | 0.62 | 01-OCT-06:49 | 684.52 | 15.63 | 0.00 | 271.17 | 465.78 | 18.77 | 0.00 | 199.33 |
November | 257.67 | 0.66 | 0.62 | 01-NOV-08:39 | 530.80 | 13.86 | 0.00 | 215.83 | 365.16 | 17.22 | 0.00 | 141.50 |
December | 251.17 | 0.66 | 0.62 | 01-DEC-08:20 | 489.23 | 13.44 | 0.00 | 203.00 | 328.00 | 16.86 | 0.00 | 105.50 |
Annual Sum or Average | 3902.00 | 0.64 | 889.34 | 16.22 | 0.00 | 3685.83 | 539.74 | 19.62 | 529.17 | 2959.83 | ||
Minimum of Months | 245.50 | 0.63 | 0.62 | 474.16 | 12.82 | 0.00 | 197.17 | 319.09 | 16.21 | 0.00 | 94.50 | |
Maximum of Months | 430.33 | 0.67 | 0.62 | 1296.32 | 18.08 | 0.00 | 413.83 | 738.58 | 23.47 | 190.00 | 399.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.65 | 0.62 | 01-JAN-08:39 | 2396.23 | 20.15 | 83.33 | 238.00 | 1562.06 | 23.73 | 93.00 | 186.50 |
February | 245.50 | 0.63 | 0.62 | 01-FEB-10:39 | 2660.22 | 20.54 | 68.50 | 248.50 | 1405.57 | 21.58 | 52.50 | 196.67 |
March | 296.17 | 0.63 | 0.62 | 01-MAR-07:19 | 2922.76 | 19.49 | 73.83 | 320.67 | 1776.50 | 23.12 | 74.50 | 275.17 |
April | 296.67 | 0.63 | 0.62 | 03-APR-09:39 | 2925.36 | 20.45 | 85.17 | 339.50 | 1265.93 | 20.81 | 38.33 | 292.50 |
May | 415.33 | 0.63 | 0.62 | 01-MAY-05:00 | 2469.81 | 17.13 | 53.17 | 388.83 | 1315.60 | 18.43 | 0.50 | 354.17 |
June | 421.50 | 0.63 | 0.62 | 01-JUN-05:40 | 2996.91 | 13.99 | 1.83 | 392.83 | 1668.23 | 18.08 | 0.17 | 366.33 |
July | 430.33 | 0.63 | 0.62 | 01-JUL-05:00 | 2516.58 | 16.72 | 54.83 | 398.00 | 1371.62 | 18.22 | 0.67 | 365.00 |
August | 394.50 | 0.63 | 0.62 | 01-AUG-06:10 | 2531.99 | 16.70 | 53.50 | 373.17 | 1483.07 | 18.19 | 7.83 | 345.00 |
September | 354.00 | 0.63 | 0.62 | 01-SEP-06:30 | 2928.79 | 21.27 | 109.83 | 325.83 | 1577.94 | 22.54 | 79.00 | 296.50 |
October | 262.67 | 0.63 | 0.62 | 01-OCT-06:49 | 3801.99 | 22.81 | 92.83 | 288.50 | 1413.46 | 21.93 | 48.17 | 240.67 |
November | 257.67 | 0.64 | 0.62 | 01-NOV-08:39 | 2492.20 | 20.85 | 77.17 | 242.50 | 1496.73 | 24.10 | 85.67 | 200.33 |
December | 251.17 | 0.64 | 0.62 | 01-DEC-08:20 | 2070.73 | 21.22 | 80.67 | 235.00 | 1157.56 | 22.42 | 71.83 | 185.50 |
Annual Sum or Average | 3902.00 | 0.63 | 2721.08 | 18.83 | 834.67 | 3791.33 | 1463.31 | 20.70 | 552.17 | 3304.33 | ||
Minimum of Months | 245.50 | 0.63 | 0.62 | 2070.73 | 13.99 | 1.83 | 235.00 | 1157.56 | 18.08 | 0.17 | 185.50 | |
Maximum of Months | 430.33 | 0.65 | 0.62 | 3801.99 | 22.81 | 109.83 | 398.00 | 1776.50 | 24.10 | 93.00 | 366.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.64 | 0.62 | 01-JAN-07:00 | 9184.67 | 36.94 | 256.50 | 261.83 | 4922.92 | 33.53 | 205.33 | 256.67 |
February | 245.50 | 0.63 | 0.62 | 01-FEB-10:39 | 12497.34 | 37.21 | 228.50 | 256.00 | 1879.90 | 21.78 | 69.33 | 232.67 |
March | 296.17 | 0.63 | 0.62 | 01-MAR-06:00 | 2339.05 | 14.25 | 9.83 | 323.33 | 1270.25 | 17.92 | 8.83 | 276.83 |
April | 296.67 | 0.64 | 0.62 | 03-APR-09:39 | 1729.74 | 14.17 | 0.00 | 331.67 | 998.02 | 18.13 | 3.67 | 283.83 |
May | 415.33 | 0.64 | 0.62 | 01-MAY-05:49 | 1558.88 | 14.23 | 0.00 | 382.83 | 856.35 | 18.15 | 0.00 | 340.67 |
June | 421.50 | 0.64 | 0.62 | 01-JUN-05:40 | 1258.21 | 13.93 | 0.00 | 379.00 | 755.55 | 17.97 | 0.00 | 333.67 |
July | 430.33 | 0.64 | 0.62 | 01-JUL-05:00 | 1418.24 | 13.91 | 0.00 | 384.00 | 801.34 | 17.86 | 0.00 | 340.50 |
August | 394.50 | 0.64 | 0.62 | 01-AUG-05:00 | 1507.71 | 13.74 | 0.00 | 362.33 | 915.97 | 17.73 | 3.33 | 320.33 |
September | 354.00 | 0.64 | 0.62 | 01-SEP-06:10 | 2514.72 | 15.69 | 29.50 | 323.00 | 1127.78 | 17.94 | 2.33 | 293.33 |
October | 262.67 | 0.63 | 0.62 | 01-OCT-06:30 | 12237.49 | 35.71 | 239.17 | 295.83 | 1557.37 | 18.19 | 8.33 | 258.83 |
November | 257.67 | 0.63 | 0.62 | 01-NOV-08:39 | 10616.41 | 38.02 | 247.17 | 258.50 | 3026.36 | 26.97 | 126.33 | 236.00 |
December | 251.17 | 0.63 | 0.62 | 01-DEC-07:49 | 8428.94 | 35.41 | 220.00 | 248.33 | 7032.47 | 40.14 | 247.00 | 240.33 |
Annual Sum or Average | 3902.00 | 0.64 | 4652.39 | 21.68 | 1230.67 | 3806.67 | 1852.83 | 21.34 | 674.50 | 3413.67 | ||
Minimum of Months | 245.50 | 0.63 | 0.62 | 1258.21 | 13.74 | 0.00 | 248.33 | 755.55 | 17.73 | 0.00 | 232.67 | |
Maximum of Months | 430.33 | 0.64 | 0.62 | 12497.34 | 38.02 | 256.50 | 384.00 | 7032.47 | 40.14 | 247.00 | 340.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.66 | 0.62 | 01-JAN-07:49 | 2118.66 | 19.44 | 82.50 | 221.83 | 1265.97 | 22.57 | 83.17 | 183.33 |
February | 245.50 | 0.64 | 0.62 | 01-FEB-10:39 | 3083.92 | 19.66 | 66.17 | 236.33 | 2012.75 | 22.98 | 65.17 | 188.67 |
March | 296.17 | 0.64 | 0.62 | 01-MAR-06:49 | 3061.10 | 19.08 | 67.83 | 305.50 | 1777.68 | 22.40 | 62.33 | 259.67 |
April | 296.67 | 0.64 | 0.62 | 03-APR-09:39 | 3518.28 | 20.42 | 84.83 | 332.00 | 1443.57 | 20.77 | 41.17 | 279.83 |
May | 415.33 | 0.63 | 0.62 | 01-MAY-05:40 | 2682.14 | 18.64 | 84.50 | 390.50 | 1498.58 | 22.22 | 83.50 | 352.50 |
June | 421.50 | 0.63 | 0.62 | 01-JUN-04:00 | 3331.82 | 19.88 | 108.00 | 392.00 | 1876.54 | 21.94 | 79.67 | 361.17 |
July | 430.33 | 0.63 | 0.62 | 01-JUL-05:10 | 2865.46 | 18.41 | 86.67 | 395.00 | 1594.39 | 21.94 | 84.83 | 358.67 |
August | 394.50 | 0.64 | 0.62 | 01-AUG-05:49 | 4114.69 | 20.38 | 116.50 | 360.50 | 1601.26 | 21.36 | 69.00 | 325.33 |
September | 354.00 | 0.64 | 0.62 | 01-SEP-05:49 | 3393.61 | 20.81 | 105.50 | 322.50 | 1274.95 | 20.94 | 56.00 | 294.50 |
October | 262.67 | 0.64 | 0.62 | 01-OCT-06:30 | 2970.53 | 19.85 | 67.67 | 276.50 | 1727.31 | 22.83 | 55.67 | 222.83 |
November | 257.67 | 0.65 | 0.62 | 01-NOV-08:39 | 2092.59 | 19.61 | 69.50 | 228.33 | 1072.81 | 20.85 | 63.00 | 185.17 |
December | 251.17 | 0.65 | 0.62 | 01-DEC-07:49 | 2115.87 | 20.25 | 78.00 | 217.00 | 1303.08 | 23.06 | 81.50 | 173.33 |
Annual Sum or Average | 3902.00 | 0.64 | 3003.63 | 19.66 | 1017.67 | 3678.00 | 1547.63 | 21.94 | 825.00 | 3185.00 | ||
Minimum of Months | 245.50 | 0.63 | 0.62 | 2092.59 | 18.41 | 66.17 | 217.00 | 1072.81 | 20.77 | 41.17 | 173.33 | |
Maximum of Months | 430.33 | 0.66 | 0.62 | 4114.69 | 20.81 | 116.50 | 395.00 | 2012.75 | 23.06 | 84.83 | 361.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.67 | 0.62 | 01-JAN-08:50 | 453.92 | 9.37 | 0.00 | 190.17 | 308.91 | 13.78 | 0.00 | 86.50 |
February | 245.50 | 0.64 | 0.62 | 01-FEB-10:39 | 541.29 | 11.10 | 0.00 | 224.00 | 381.65 | 15.53 | 0.00 | 142.17 |
March | 296.17 | 0.64 | 0.62 | 01-MAR-07:10 | 707.38 | 12.81 | 0.00 | 302.33 | 465.99 | 16.94 | 0.00 | 221.50 |
April | 296.67 | 0.63 | 0.62 | 03-APR-09:39 | 951.74 | 14.12 | 0.00 | 337.83 | 568.83 | 18.07 | 0.83 | 271.00 |
May | 415.33 | 0.63 | 0.62 | 01-MAY-05:40 | 1160.62 | 14.50 | 0.00 | 402.17 | 646.22 | 18.60 | 3.50 | 367.33 |
June | 421.50 | 0.63 | 0.62 | 01-JUN-05:10 | 1245.97 | 14.74 | 0.00 | 411.83 | 710.53 | 21.73 | 70.83 | 397.17 |
July | 430.33 | 0.63 | 0.62 | 01-JUL-05:10 | 1191.47 | 14.42 | 0.00 | 411.50 | 662.49 | 19.80 | 32.67 | 380.83 |
August | 394.50 | 0.63 | 0.62 | 01-AUG-05:49 | 946.89 | 14.00 | 0.00 | 377.00 | 577.90 | 18.05 | 3.00 | 333.00 |
September | 354.00 | 0.64 | 0.62 | 01-SEP-06:10 | 775.99 | 13.38 | 0.00 | 316.67 | 497.09 | 17.43 | 0.00 | 266.50 |
October | 262.67 | 0.64 | 0.62 | 01-OCT-06:49 | 655.66 | 12.53 | 0.00 | 267.67 | 451.34 | 16.78 | 0.00 | 193.50 |
November | 257.67 | 0.66 | 0.62 | 01-NOV-08:39 | 507.72 | 10.48 | 0.00 | 210.00 | 353.59 | 14.90 | 0.00 | 133.83 |
December | 251.17 | 0.66 | 0.62 | 01-DEC-08:20 | 466.97 | 9.96 | 0.00 | 198.50 | 316.61 | 14.41 | 0.00 | 95.67 |
Annual Sum or Average | 3902.00 | 0.64 | 855.66 | 12.94 | 0.00 | 3649.67 | 520.75 | 17.57 | 110.83 | 2889.00 | ||
Minimum of Months | 245.50 | 0.63 | 0.62 | 453.92 | 9.37 | 0.00 | 190.17 | 308.91 | 13.78 | 0.00 | 86.50 | |
Maximum of Months | 430.33 | 0.67 | 0.62 | 1245.97 | 14.74 | 0.00 | 411.83 | 710.53 | 21.73 | 70.83 | 397.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.65 | 0.62 | 01-JAN-08:50 | 2335.79 | 19.81 | 83.33 | 233.83 | 1513.26 | 23.65 | 92.17 | 182.00 |
February | 245.50 | 0.63 | 0.62 | 01-FEB-10:39 | 2580.62 | 20.19 | 68.50 | 245.83 | 1341.14 | 21.47 | 52.33 | 193.83 |
March | 296.17 | 0.63 | 0.62 | 01-MAR-07:19 | 2841.60 | 19.11 | 73.83 | 318.50 | 1712.27 | 23.00 | 74.17 | 269.00 |
April | 296.67 | 0.63 | 0.62 | 03-APR-09:39 | 2844.01 | 20.08 | 85.17 | 337.50 | 1205.18 | 20.66 | 38.33 | 288.17 |
May | 415.33 | 0.63 | 0.62 | 01-MAY-05:00 | 2385.11 | 16.70 | 53.17 | 387.17 | 1256.54 | 18.26 | 0.50 | 350.67 |
June | 421.50 | 0.63 | 0.62 | 01-JUN-05:49 | 2901.73 | 13.54 | 1.83 | 390.83 | 1600.22 | 17.90 | 0.00 | 363.50 |
July | 430.33 | 0.64 | 0.62 | 01-JUL-05:00 | 2433.98 | 16.29 | 54.83 | 394.83 | 1314.33 | 18.04 | 0.50 | 360.83 |
August | 394.50 | 0.63 | 0.62 | 01-AUG-06:10 | 2427.94 | 16.09 | 50.67 | 372.00 | 1420.88 | 18.02 | 7.83 | 339.67 |
September | 354.00 | 0.63 | 0.62 | 01-SEP-06:30 | 2710.57 | 18.96 | 84.67 | 322.67 | 1517.91 | 22.41 | 78.17 | 294.33 |
October | 262.67 | 0.63 | 0.62 | 01-OCT-06:49 | 3712.20 | 22.47 | 92.83 | 286.83 | 1343.43 | 21.82 | 48.00 | 235.50 |
November | 257.67 | 0.64 | 0.62 | 01-NOV-08:39 | 2425.62 | 20.51 | 77.17 | 240.00 | 1442.68 | 24.01 | 84.67 | 197.50 |
December | 251.17 | 0.64 | 0.62 | 01-DEC-08:20 | 2009.69 | 20.90 | 80.67 | 234.17 | 1109.55 | 22.33 | 71.33 | 182.83 |
Annual Sum or Average | 3902.00 | 0.64 | 2626.35 | 18.25 | 806.67 | 3764.17 | 1403.24 | 20.56 | 548.00 | 3257.83 | ||
Minimum of Months | 245.50 | 0.63 | 0.62 | 2009.69 | 13.54 | 1.83 | 233.83 | 1109.55 | 17.90 | 0.00 | 182.00 | |
Maximum of Months | 430.33 | 0.65 | 0.62 | 3712.20 | 22.47 | 92.83 | 394.83 | 1712.27 | 24.01 | 92.17 | 363.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.64 | 0.62 | 01-JAN-07:00 | 9186.15 | 36.98 | 256.83 | 262.00 | 4922.86 | 33.53 | 205.33 | 256.67 |
February | 245.50 | 0.63 | 0.62 | 01-FEB-10:39 | 12561.15 | 38.65 | 241.00 | 259.00 | 1879.83 | 21.78 | 69.33 | 232.67 |
March | 296.17 | 0.63 | 0.62 | 01-MAR-06:00 | 2339.53 | 14.30 | 10.33 | 323.33 | 1270.18 | 17.92 | 8.83 | 276.83 |
April | 296.67 | 0.64 | 0.62 | 03-APR-09:39 | 1729.67 | 14.17 | 0.00 | 331.67 | 997.96 | 18.13 | 3.67 | 283.83 |
May | 415.33 | 0.64 | 0.62 | 01-MAY-05:49 | 1558.81 | 14.23 | 0.00 | 382.83 | 856.28 | 18.15 | 0.00 | 340.67 |
June | 421.50 | 0.64 | 0.62 | 01-JUN-05:40 | 1258.17 | 13.93 | 0.00 | 379.00 | 755.51 | 17.97 | 0.00 | 333.67 |
July | 430.33 | 0.64 | 0.62 | 01-JUL-05:00 | 1418.19 | 13.92 | 0.00 | 384.00 | 801.28 | 17.87 | 0.00 | 340.50 |
August | 394.50 | 0.64 | 0.62 | 01-AUG-05:00 | 1507.66 | 13.74 | 0.00 | 362.17 | 915.92 | 17.73 | 3.33 | 320.33 |
September | 354.00 | 0.64 | 0.62 | 01-SEP-06:10 | 2514.66 | 15.69 | 29.50 | 323.00 | 1127.71 | 17.94 | 2.50 | 293.33 |
October | 262.67 | 0.63 | 0.62 | 01-OCT-06:30 | 12237.47 | 35.72 | 239.17 | 295.83 | 1557.29 | 18.19 | 8.33 | 258.83 |
November | 257.67 | 0.63 | 0.62 | 01-NOV-08:39 | 10616.45 | 38.02 | 247.17 | 258.50 | 3026.29 | 26.97 | 126.33 | 236.00 |
December | 251.17 | 0.63 | 0.62 | 01-DEC-07:49 | 8429.01 | 35.41 | 220.00 | 248.33 | 7032.40 | 40.14 | 247.00 | 240.33 |
Annual Sum or Average | 3902.00 | 0.63 | 4656.52 | 21.78 | 1244.00 | 3809.67 | 1852.77 | 21.34 | 674.67 | 3413.67 | ||
Minimum of Months | 245.50 | 0.63 | 0.62 | 1258.17 | 13.74 | 0.00 | 248.33 | 755.51 | 17.73 | 0.00 | 232.67 | |
Maximum of Months | 430.33 | 0.64 | 0.62 | 12561.15 | 38.65 | 256.83 | 384.00 | 7032.40 | 40.14 | 247.00 | 340.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.66 | 0.62 | 01-JAN-07:49 | 2118.67 | 19.44 | 82.50 | 221.83 | 1265.95 | 22.57 | 83.17 | 183.33 |
February | 245.50 | 0.64 | 0.62 | 01-FEB-10:39 | 3083.94 | 19.66 | 66.17 | 236.33 | 2012.73 | 22.98 | 65.17 | 188.67 |
March | 296.17 | 0.64 | 0.62 | 01-MAR-06:49 | 3061.11 | 19.08 | 67.83 | 305.50 | 1777.65 | 22.40 | 62.33 | 259.67 |
April | 296.67 | 0.64 | 0.62 | 03-APR-09:39 | 3518.27 | 20.42 | 84.83 | 332.00 | 1443.51 | 20.77 | 41.17 | 279.83 |
May | 415.33 | 0.63 | 0.62 | 01-MAY-05:40 | 2682.10 | 18.64 | 84.50 | 390.33 | 1498.52 | 22.23 | 83.50 | 352.50 |
June | 421.50 | 0.63 | 0.62 | 01-JUN-04:00 | 3331.81 | 19.88 | 108.00 | 392.00 | 1876.48 | 21.94 | 79.67 | 361.17 |
July | 430.33 | 0.63 | 0.62 | 01-JUL-05:10 | 2865.43 | 18.41 | 86.67 | 395.00 | 1594.33 | 21.94 | 84.83 | 358.67 |
August | 394.50 | 0.64 | 0.62 | 01-AUG-05:49 | 4114.69 | 20.38 | 116.50 | 360.50 | 1601.21 | 21.36 | 69.00 | 325.33 |
September | 354.00 | 0.64 | 0.62 | 01-SEP-05:49 | 3393.61 | 20.81 | 105.50 | 322.50 | 1274.90 | 20.94 | 56.00 | 294.50 |
October | 262.67 | 0.64 | 0.62 | 01-OCT-06:30 | 2970.55 | 19.85 | 67.67 | 276.50 | 1727.27 | 22.83 | 55.67 | 222.83 |
November | 257.67 | 0.65 | 0.62 | 01-NOV-08:39 | 2092.60 | 19.61 | 69.50 | 228.33 | 1072.78 | 20.85 | 63.00 | 185.17 |
December | 251.17 | 0.65 | 0.62 | 01-DEC-07:49 | 2115.89 | 20.25 | 78.00 | 217.00 | 1303.06 | 23.06 | 81.50 | 173.33 |
Annual Sum or Average | 3902.00 | 0.64 | 3003.63 | 19.66 | 1017.67 | 3677.83 | 1547.59 | 21.94 | 825.00 | 3185.00 | ||
Minimum of Months | 245.50 | 0.63 | 0.62 | 2092.60 | 18.41 | 66.17 | 217.00 | 1072.78 | 20.77 | 41.17 | 173.33 | |
Maximum of Months | 430.33 | 0.66 | 0.62 | 4114.69 | 20.81 | 116.50 | 395.00 | 2012.73 | 23.06 | 84.83 | 361.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.67 | 0.62 | 01-JAN-08:50 | 453.92 | 9.38 | 0.00 | 190.17 | 308.89 | 13.78 | 0.00 | 86.33 |
February | 245.50 | 0.64 | 0.62 | 01-FEB-10:39 | 541.30 | 11.10 | 0.00 | 224.00 | 381.64 | 15.54 | 0.00 | 142.00 |
March | 296.17 | 0.64 | 0.62 | 01-MAR-07:10 | 707.38 | 12.81 | 0.00 | 302.33 | 465.97 | 16.94 | 0.00 | 221.50 |
April | 296.67 | 0.63 | 0.62 | 03-APR-09:39 | 951.73 | 14.12 | 0.00 | 337.83 | 568.80 | 18.07 | 0.83 | 271.00 |
May | 415.33 | 0.63 | 0.62 | 01-MAY-05:40 | 1160.59 | 14.50 | 0.00 | 402.17 | 646.18 | 18.60 | 3.50 | 367.33 |
June | 421.50 | 0.63 | 0.62 | 01-JUN-05:10 | 1245.97 | 14.74 | 0.00 | 411.83 | 710.50 | 21.73 | 70.83 | 397.17 |
July | 430.33 | 0.63 | 0.62 | 01-JUL-05:10 | 1191.45 | 14.42 | 0.00 | 411.50 | 662.45 | 19.80 | 32.67 | 380.83 |
August | 394.50 | 0.63 | 0.62 | 01-AUG-05:49 | 946.89 | 14.01 | 0.00 | 377.00 | 577.87 | 18.05 | 3.00 | 333.00 |
September | 354.00 | 0.64 | 0.62 | 01-SEP-06:10 | 775.99 | 13.38 | 0.00 | 316.67 | 497.06 | 17.43 | 0.00 | 266.50 |
October | 262.67 | 0.64 | 0.62 | 01-OCT-06:49 | 655.67 | 12.53 | 0.00 | 267.67 | 451.33 | 16.78 | 0.00 | 193.50 |
November | 257.67 | 0.66 | 0.62 | 01-NOV-08:39 | 507.73 | 10.49 | 0.00 | 210.00 | 353.58 | 14.90 | 0.00 | 133.83 |
December | 251.17 | 0.66 | 0.62 | 01-DEC-08:20 | 466.98 | 9.96 | 0.00 | 198.50 | 316.60 | 14.41 | 0.00 | 95.67 |
Annual Sum or Average | 3902.00 | 0.64 | 855.65 | 12.94 | 0.00 | 3649.67 | 520.73 | 17.57 | 110.83 | 2888.67 | ||
Minimum of Months | 245.50 | 0.63 | 0.62 | 453.92 | 9.38 | 0.00 | 190.17 | 308.89 | 13.78 | 0.00 | 86.33 | |
Maximum of Months | 430.33 | 0.67 | 0.62 | 1245.97 | 14.74 | 0.00 | 411.83 | 710.50 | 21.73 | 70.83 | 397.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.65 | 0.62 | 01-JAN-08:50 | 2335.80 | 19.81 | 83.33 | 233.83 | 1513.23 | 23.65 | 92.17 | 182.00 |
February | 245.50 | 0.63 | 0.62 | 01-FEB-10:39 | 2580.63 | 20.19 | 68.50 | 245.83 | 1341.12 | 21.48 | 52.33 | 193.83 |
March | 296.17 | 0.63 | 0.62 | 01-MAR-07:19 | 2841.61 | 19.12 | 73.83 | 318.50 | 1712.23 | 23.00 | 74.17 | 269.00 |
April | 296.67 | 0.63 | 0.62 | 03-APR-09:39 | 2843.99 | 20.08 | 85.17 | 337.50 | 1205.12 | 20.66 | 38.33 | 288.17 |
May | 415.33 | 0.63 | 0.62 | 01-MAY-05:00 | 2385.07 | 16.70 | 53.17 | 387.17 | 1256.48 | 18.26 | 0.50 | 350.67 |
June | 421.50 | 0.63 | 0.62 | 01-JUN-05:49 | 2901.72 | 13.54 | 1.83 | 390.83 | 1600.16 | 17.90 | 0.00 | 363.50 |
July | 430.33 | 0.64 | 0.62 | 01-JUL-05:00 | 2433.94 | 16.29 | 54.83 | 394.83 | 1314.27 | 18.04 | 0.50 | 360.67 |
August | 394.50 | 0.63 | 0.62 | 01-AUG-06:10 | 2427.94 | 16.09 | 50.67 | 372.00 | 1420.83 | 18.02 | 7.83 | 339.67 |
September | 354.00 | 0.63 | 0.62 | 01-SEP-06:30 | 2710.57 | 18.96 | 84.67 | 322.67 | 1517.86 | 22.42 | 78.33 | 294.33 |
October | 262.67 | 0.63 | 0.62 | 01-OCT-06:49 | 3712.21 | 22.47 | 92.83 | 286.83 | 1343.39 | 21.82 | 48.00 | 235.50 |
November | 257.67 | 0.64 | 0.62 | 01-NOV-08:39 | 2425.63 | 20.51 | 77.17 | 240.00 | 1442.65 | 24.01 | 84.67 | 197.50 |
December | 251.17 | 0.64 | 0.62 | 01-DEC-08:20 | 2009.70 | 20.90 | 80.67 | 234.17 | 1109.52 | 22.33 | 71.33 | 182.83 |
Annual Sum or Average | 3902.00 | 0.64 | 2626.34 | 18.25 | 806.67 | 3764.17 | 1403.20 | 20.56 | 548.17 | 3257.67 | ||
Minimum of Months | 245.50 | 0.63 | 0.62 | 2009.70 | 13.54 | 1.83 | 233.83 | 1109.52 | 17.90 | 0.00 | 182.00 | |
Maximum of Months | 430.33 | 0.65 | 0.62 | 3712.21 | 22.47 | 92.83 | 394.83 | 1712.23 | 24.01 | 92.17 | 363.50 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1288731.62 | 21478.86 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11239253.88 | 22096.17 | 26-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 12527985.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11239253.88 | 22096.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.352301E+10 | 11016.25 | 10-JAN-17:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.397846E+10 | 10996.21 | 28-FEB-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.356906E+10 | 11090.35 | 17-MAR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.264050E+10 | 11037.26 | 14-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113189E+10 | 11233.69 | 11-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 57333570.79 | 11268.80 | 09-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30765660.11 | 10587.50 | 03-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 58314859.67 | 8181.86 | 23-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.256667E+09 | 11258.95 | 22-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.246003E+10 | 11975.91 | 12-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.287635E+10 | 11168.30 | 10-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.446089E+10 | 11040.96 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 30765660.11 | 8181.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.446089E+10 | 11975.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.996979E+09 | 9225.29 | 30-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119429E+10 | 9194.34 | 22-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.708192E+09 | 9224.17 | 21-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.367341E+09 | 9208.78 | 25-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18837313.71 | 9162.57 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304857E+09 | 9191.60 | 25-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.482618E+09 | 9200.99 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140359E+10 | 9183.57 | 29-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.547671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.140359E+10 | 9225.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.219286E+10 | 7965.15 | 30-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249055E+10 | 7958.94 | 22-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140100E+10 | 7965.56 | 21-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.732555E+09 | 7971.61 | 25-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45834247.66 | 7941.70 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.423351E+09 | 7956.73 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.900749E+09 | 7951.26 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261912E+10 | 7993.76 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.261912E+10 | 7993.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115987E+10 | 9597.33 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132379E+10 | 9597.33 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.863498E+09 | 9597.33 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.480087E+09 | 9597.33 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31813359.87 | 9597.33 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29966.51 | 399.55 | 22-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.333184E+09 | 9597.33 | 23-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.536508E+09 | 9597.33 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155351E+10 | 9597.33 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.628228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.155351E+10 | 9597.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.290653E+09 | 24598.21 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.657485E+09 | 24598.21 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.257844E+09 | 24598.21 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166883E+09 | 24598.21 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110886E+09 | 24598.21 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 77809058.52 | 24598.21 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.861451E+09 | 24598.21 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.861451E+09 | 24598.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.797982E+09 | 12646.92 | 17-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116392E+10 | 12642.41 | 06-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.783024E+09 | 12604.39 | 21-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.500365E+09 | 12624.77 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36773792.74 | 12469.06 | 03-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4038644.53 | 11435.83 | 22-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.614656E+09 | 12566.35 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.644249E+09 | 12614.33 | 29-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161909E+10 | 12619.79 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.616410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161909E+10 | 12646.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105838E+10 | 10069.91 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119991E+10 | 10069.91 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.709956E+09 | 10069.91 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.425432E+09 | 10069.91 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19756028.13 | 10069.91 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2990264.37 | 9304.77 | 22-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.548472E+09 | 10069.91 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.804812E+09 | 10069.91 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188150E+10 | 10069.91 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.665120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.188150E+10 | 10069.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.164825E+10 | 9091.18 | 18-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.190515E+10 | 9048.95 | 10-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.964861E+09 | 9082.72 | 22-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.545403E+09 | 9084.95 | 24-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28169016.33 | 8962.94 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3307011.68 | 8918.93 | 22-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.632755E+09 | 9046.45 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112108E+10 | 9081.74 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.288976E+10 | 9062.50 | 12-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.973874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.288976E+10 | 9091.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120030E+10 | 10069.81 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133487E+10 | 10069.81 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.828284E+09 | 10069.81 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.503587E+09 | 10069.81 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36032032.20 | 10069.81 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7245094.76 | 10069.81 | 22-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.563382E+09 | 10069.81 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.895517E+09 | 10069.81 | 01-NOV-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.202418E+10 | 10069.81 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.739339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.202418E+10 | 10069.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.233069E+10 | 33332.82 | 12-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275692E+10 | 33369.86 | 22-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148794E+10 | 33313.74 | 24-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110871E+10 | 33415.68 | 25-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 77924921.70 | 33216.38 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100410E+10 | 33258.65 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147275E+10 | 33307.87 | 20-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.380872E+10 | 33228.87 | 29-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.380872E+10 | 33415.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.193204E+10 | 14232.76 | 31-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.247851E+10 | 14203.65 | 01-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192059E+10 | 14248.00 | 25-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134909E+10 | 14191.07 | 24-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147091E+09 | 14099.64 | 02-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41446650.75 | 14030.39 | 22-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144497E+10 | 14239.87 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164117E+10 | 14219.77 | 22-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348154E+10 | 14185.43 | 07-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.348154E+10 | 14248.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.201717E+10 | 11355.57 | 14-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.215777E+10 | 11362.92 | 22-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141129E+10 | 11348.82 | 18-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.879758E+09 | 11366.64 | 03-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 63847835.22 | 11248.73 | 03-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27220995.70 | 11269.37 | 22-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110888E+10 | 11360.67 | 30-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158769E+10 | 11330.09 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.333025E+10 | 11332.96 | 23-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.333025E+10 | 11366.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.352537E+10 | 10576.19 | 11-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.378941E+10 | 10555.97 | 22-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.229836E+10 | 10566.49 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139163E+10 | 10572.55 | 25-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119213E+09 | 10573.62 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41668135.19 | 10416.98 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156128E+10 | 10557.60 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.260631E+10 | 10560.21 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.555062E+10 | 10532.26 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.555062E+10 | 10576.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.238304E+10 | 12941.81 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.254499E+10 | 12941.81 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177117E+10 | 12941.81 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115911E+10 | 12941.81 | 03-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139221E+09 | 12941.81 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 58840246.24 | 12791.07 | 22-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126724E+10 | 12941.81 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189248E+10 | 12941.81 | 01-NOV-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.371805E+10 | 12941.81 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.371805E+10 | 12941.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.538609E+10 | 21811.72 | 05-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.537696E+10 | 17362.12 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.306402E+10 | 13578.54 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162093E+10 | 14014.73 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 56114814.96 | 5613.95 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54162362.07 | 5476.48 | 22-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.199862E+10 | 15427.53 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.368010E+10 | 17466.61 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.795236E+10 | 27264.30 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.291894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.795236E+10 | 27264.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.638843E+10 | 22661.43 | 05-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.626659E+10 | 17509.35 | 06-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.395764E+10 | 14766.31 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.226178E+10 | 15524.56 | 17-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125334E+09 | 6800.16 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130231E+09 | 7109.54 | 22-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.285668E+10 | 17343.72 | 30-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.488389E+10 | 18867.69 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.919317E+10 | 27999.96 | 23-DEC-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.919317E+10 | 27999.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.714837E+10 | 26652.55 | 05-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.704846E+10 | 18956.64 | 02-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.444059E+10 | 17086.82 | 04-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.261194E+10 | 16417.87 | 17-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.186436E+09 | 8617.95 | 02-MAY-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189782E+09 | 9635.80 | 22-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.350742E+10 | 18925.95 | 30-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.555117E+10 | 21155.22 | 30-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107006E+11 | 31826.57 | 23-DEC-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.413848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107006E+11 | 31826.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.816085E+09 | 0.815857E+09 | 22588.17 | 20-JAN-14:00 | 22588.17 | 0.00 |
February | 0.00 | 0.00 | 0.234037E+09 | 0.233635E+09 | 11686.73 | 18-FEB-13:40 | 11686.73 | 0.00 |
March | 0.00 | 0.00 | 0.302106E+10 | 0.302063E+10 | 39433.80 | 14-MAR-13:00 | 39433.80 | 0.00 |
April | 0.00 | 0.00 | 0.259253E+10 | 0.255372E+10 | 23355.82 | 20-APR-13:00 | 23355.82 | 0.00 |
May | 0.00 | 0.00 | 0.138293E+11 | 0.135099E+11 | 49868.09 | 17-MAY-13:00 | 49868.09 | 0.00 |
June | 0.00 | 0.00 | 0.543108E+11 | 0.517817E+11 | 77071.95 | 26-JUN-16:00 | 77071.95 | 0.00 |
July | 0.00 | 0.00 | 0.554180E+11 | 0.510783E+11 | 75427.11 | 17-JUL-12:07 | 75427.11 | 0.00 |
August | 0.00 | 0.00 | 0.547536E+11 | 0.519367E+11 | 72403.09 | 16-AUG-16:00 | 72403.09 | 0.00 |
September | 0.00 | 0.00 | 0.376041E+11 | 0.370978E+11 | 65940.66 | 12-SEP-16:00 | 65940.66 | 0.00 |
October | 0.00 | 0.00 | 0.656032E+10 | 0.654200E+10 | 54783.53 | 11-OCT-15:20 | 54783.53 | 0.00 |
November | 0.00 | 0.00 | 0.198186E+10 | 0.198183E+10 | 31950.67 | 07-NOV-15:00 | 31950.67 | 0.00 |
December | 0.00 | 0.00 | 0.879480E+09 | 0.878970E+09 | 20851.60 | 01-DEC-14:00 | 20851.60 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.232001E+12 | 0.221431E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.234037E+09 | 0.233635E+09 | 11686.73 | 11686.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.554180E+11 | 0.519367E+11 | 77071.95 | 77071.95 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.958357E+09 | 0.958303E+09 | 21124.30 | 20-JAN-14:00 | 21124.30 | 0.00 |
February | 0.00 | 0.00 | 0.347257E+09 | 0.347139E+09 | 16183.62 | 18-FEB-13:20 | 16183.62 | 0.00 |
March | 0.00 | 0.00 | 0.308452E+10 | 0.308430E+10 | 36528.68 | 13-MAR-16:00 | 36528.68 | 0.00 |
April | 0.00 | 0.00 | 0.247977E+10 | 0.244544E+10 | 23663.25 | 20-APR-13:00 | 23663.25 | 0.00 |
May | 0.00 | 0.00 | 0.133084E+11 | 0.130025E+11 | 48285.16 | 31-MAY-16:00 | 48285.16 | 0.00 |
June | 0.00 | 0.00 | 0.506590E+11 | 0.483836E+11 | 74917.47 | 26-JUN-15:20 | 74917.47 | 0.00 |
July | 0.00 | 0.00 | 0.515793E+11 | 0.476994E+11 | 72698.77 | 31-JUL-14:40 | 52601.79 | 0.00 |
August | 0.00 | 0.00 | 0.490993E+11 | 0.466642E+11 | 70511.13 | 16-AUG-15:10 | 70511.13 | 0.00 |
September | 0.00 | 0.00 | 0.322604E+11 | 0.318355E+11 | 62828.51 | 12-SEP-15:50 | 62828.51 | 0.00 |
October | 0.00 | 0.00 | 0.584440E+10 | 0.583150E+10 | 50102.30 | 11-OCT-15:00 | 50102.30 | 0.00 |
November | 0.00 | 0.00 | 0.180010E+10 | 0.179981E+10 | 28375.42 | 07-NOV-14:50 | 28375.42 | 0.00 |
December | 0.00 | 0.00 | 0.936471E+09 | 0.936397E+09 | 20679.31 | 01-DEC-14:00 | 20679.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.212357E+12 | 0.202988E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.347257E+09 | 0.347139E+09 | 16183.62 | 16183.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.515793E+11 | 0.483836E+11 | 74917.47 | 74917.47 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.815330E+09 | 0.815304E+09 | 22604.83 | 20-JAN-14:00 | 22604.83 | 0.00 |
February | 0.00 | 0.00 | 0.276175E+09 | 0.275781E+09 | 14690.72 | 18-FEB-13:30 | 14690.72 | 0.00 |
March | 0.00 | 0.00 | 0.297972E+10 | 0.297924E+10 | 38095.42 | 14-MAR-13:10 | 38095.42 | 0.00 |
April | 0.00 | 0.00 | 0.262171E+10 | 0.257705E+10 | 25904.82 | 20-APR-13:00 | 25904.82 | 0.00 |
May | 0.00 | 0.00 | 0.141103E+11 | 0.136860E+11 | 57888.51 | 31-MAY-15:20 | 57888.51 | 0.00 |
June | 0.00 | 0.00 | 0.554428E+11 | 0.529720E+11 | 87607.57 | 26-JUN-15:10 | 87607.57 | 0.00 |
July | 0.00 | 0.00 | 0.557283E+11 | 0.517042E+11 | 80304.70 | 31-JUL-14:10 | 60557.92 | 0.00 |
August | 0.00 | 0.00 | 0.529644E+11 | 0.504413E+11 | 84068.93 | 16-AUG-15:10 | 84068.93 | 0.00 |
September | 0.00 | 0.00 | 0.332050E+11 | 0.326536E+11 | 70940.37 | 12-SEP-15:50 | 70940.37 | 0.00 |
October | 0.00 | 0.00 | 0.544889E+10 | 0.542783E+10 | 55732.29 | 11-OCT-15:00 | 55732.29 | 0.00 |
November | 0.00 | 0.00 | 0.158250E+10 | 0.158086E+10 | 27357.12 | 07-NOV-14:30 | 27357.12 | 0.00 |
December | 0.00 | 0.00 | 0.852803E+09 | 0.852402E+09 | 19965.40 | 01-DEC-14:00 | 19965.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.226028E+12 | 0.215966E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.276175E+09 | 0.275781E+09 | 14690.72 | 14690.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.557283E+11 | 0.529720E+11 | 87607.57 | 87607.57 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1933.78 | 6793.46 | 30-JAN-12:09 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1966.73 | 6806.41 | 08-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2067.05 | 6777.12 | 03-MAR-12:09 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1859.95 | 6573.11 | 03-APR-11:15 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1829.26 | 6239.61 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1773.41 | 5877.87 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1559.11 | 5569.00 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1688.09 | 5424.64 | 31-AUG-11:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1605.36 | 5589.23 | 28-SEP-11:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1676.25 | 5949.36 | 31-OCT-11:16 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1797.91 | 6302.35 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1816.16 | 6601.03 | 29-DEC-12:07 |
Annual Sum or Average | 0.00 | 1796.79 | ||||
Minimum of Months | 0.00 | 0.00 | 1559.11 | 5424.64 | ||
Maximum of Months | 0.00 | 0.00 | 2067.05 | 6806.41 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.176900E+10 | 0.35 | 3518.76 | 24-JAN-16:10 | 1.00 |
February | 0.161058E+10 | 0.36 | 2937.07 | 27-FEB-14:00 | 0.91 |
March | 0.228340E+10 | 0.40 | 6161.25 | 15-MAR-15:40 | 1.39 |
April | 0.190431E+10 | 0.36 | 3314.05 | 21-APR-12:08 | 0.96 |
May | 0.320942E+10 | 0.43 | 6215.70 | 17-MAY-13:00 | 1.39 |
June | 0.666397E+10 | 0.67 | 12895.92 | 26-JUN-12:07 | 2.18 |
July | 0.633002E+10 | 0.63 | 12895.92 | 24-JUL-12:10 | 2.18 |
August | 0.663119E+10 | 0.66 | 10737.89 | 18-AUG-12:08 | 1.95 |
September | 0.529747E+10 | 0.59 | 12365.62 | 06-SEP-12:10 | 2.13 |
October | 0.300491E+10 | 0.43 | 6441.48 | 11-OCT-16:30 | 1.43 |
November | 0.209834E+10 | 0.37 | 4696.46 | 07-NOV-16:30 | 1.18 |
December | 0.172893E+10 | 0.35 | 2980.86 | 26-DEC-07:02 | 0.91 |
Annual Sum or Average | 0.425316E+11 | 0.47 | |||
Minimum of Months | 0.161058E+10 | 0.35 | 2937.07 | 0.91 | |
Maximum of Months | 0.666397E+10 | 0.67 | 12895.92 | 2.18 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.174772E+10 | 0.37 | 3120.87 | 02-JAN-06:01 | 1.01 |
February | 0.169138E+10 | 0.39 | 3120.87 | 06-FEB-06:01 | 1.02 |
March | 0.220220E+10 | 0.42 | 7310.56 | 15-MAR-16:00 | 1.68 |
April | 0.180207E+10 | 0.38 | 4509.69 | 21-APR-13:30 | 1.25 |
May | 0.304975E+10 | 0.46 | 7272.69 | 18-MAY-14:30 | 1.67 |
June | 0.676057E+10 | 0.73 | 11887.19 | 30-JUN-15:10 | 2.27 |
July | 0.638109E+10 | 0.68 | 11908.31 | 24-JUL-15:10 | 2.26 |
August | 0.649799E+10 | 0.69 | 11908.26 | 11-AUG-15:10 | 2.28 |
September | 0.468972E+10 | 0.58 | 11517.54 | 05-SEP-15:40 | 2.22 |
October | 0.237815E+10 | 0.42 | 7267.65 | 11-OCT-16:00 | 1.67 |
November | 0.183375E+10 | 0.38 | 4116.38 | 07-NOV-15:50 | 1.19 |
December | 0.178543E+10 | 0.39 | 3120.87 | 11-DEC-06:01 | 1.02 |
Annual Sum or Average | 0.408198E+11 | 0.49 | |||
Minimum of Months | 0.169138E+10 | 0.37 | 3120.87 | 1.01 | |
Maximum of Months | 0.676057E+10 | 0.73 | 11908.31 | 2.28 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.185087E+10 | 0.38 | 2986.36 | 02-JAN-05:01 | 0.89 |
February | 0.177500E+10 | 0.40 | 2986.36 | 01-FEB-06:01 | 0.89 |
March | 0.218641E+10 | 0.42 | 6331.17 | 15-MAR-15:50 | 1.37 |
April | 0.181079E+10 | 0.37 | 4274.65 | 21-APR-13:30 | 1.08 |
May | 0.266496E+10 | 0.40 | 6774.48 | 31-MAY-15:40 | 1.41 |
June | 0.609163E+10 | 0.62 | 11967.87 | 26-JUN-15:10 | 2.01 |
July | 0.564886E+10 | 0.57 | 11955.03 | 24-JUL-15:30 | 2.00 |
August | 0.572425E+10 | 0.58 | 12169.23 | 11-AUG-15:10 | 2.04 |
September | 0.389883E+10 | 0.49 | 10246.86 | 12-SEP-15:50 | 1.82 |
October | 0.212890E+10 | 0.38 | 7021.34 | 11-OCT-16:00 | 1.45 |
November | 0.174948E+10 | 0.36 | 3300.18 | 07-NOV-15:40 | 0.94 |
December | 0.199152E+10 | 0.41 | 2986.36 | 05-DEC-07:01 | 0.89 |
Annual Sum or Average | 0.375215E+11 | 0.45 | |||
Minimum of Months | 0.174948E+10 | 0.36 | 2986.36 | 0.89 | |
Maximum of Months | 0.609163E+10 | 0.62 | 12169.23 | 2.04 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:05 | 0.22 | 0.22 | 56.59 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:01 | 0.22 | 0.22 | 55.32 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:01 | 0.22 | 0.22 | 56.10 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:05 | 0.22 | 0.22 | 55.56 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:01 | 0.22 | 0.22 | 55.81 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 55.67 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 56.46 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 56.59 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 57.00 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 57.76 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:01 | 0.22 | 0.22 | 56.47 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:01 | 0.22 | 0.22 | 55.76 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 55.32 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.76 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.45 | 57.45 | 1933.78 | 6793.46 | 30-JAN-12:09 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 55.77 | 55.77 | 1966.73 | 6806.41 | 08-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.53 | 56.53 | 2067.05 | 6777.12 | 03-MAR-12:09 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.21 | 56.21 | 1859.95 | 6573.11 | 03-APR-11:15 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.34 | 56.34 | 1829.26 | 6239.61 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.16 | 56.16 | 1773.41 | 5877.87 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.52 | 57.52 | 1559.11 | 5569.00 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.57 | 57.57 | 1688.09 | 5424.64 | 31-AUG-11:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.40 | 57.40 | 1605.36 | 5589.23 | 28-SEP-11:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.56 | 55.56 | 1676.25 | 5949.36 | 31-OCT-11:16 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.84 | 56.84 | 1797.91 | 6302.35 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.17 | 56.17 | 1816.16 | 6601.03 | 29-DEC-12:07 |
Annual Sum or Average | 0.00 | 1796.79 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.56 | 55.56 | 1559.11 | 5424.64 | ||
Maximum of Months | 0.00 | 0.00 | 57.57 | 57.57 | 2067.05 | 6806.41 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.985833E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.106642E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.958509E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.681708E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.791156E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.211069E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.208162E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.209086E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.150144E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.815991E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.739845E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.120138E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.150254E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.681708E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.211069E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.699454E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.804764E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.651856E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.460163E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.650031E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.201704E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.198433E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.192785E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.128548E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.630817E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.583931E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.113107E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.128268E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.460163E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.201704E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.142571E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.155790E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.118315E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.839930E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.677760E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.208972E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.203393E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.196550E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.125565E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.990114E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.113656E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.221117E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.173671E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.677760E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.221117E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.176900E+10 | 0.816085E+09 | 0.132588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161058E+10 | 0.234037E+09 | 0.143653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.228340E+10 | 0.302106E+10 | 0.960577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.190431E+10 | 0.259253E+10 | 0.584141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.320942E+10 | 0.138293E+11 | 0.128449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.666397E+10 | 0.543108E+11 | 57333570.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.633002E+10 | 0.554180E+11 | 30765660.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.663119E+10 | 0.547536E+11 | 58314859.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.529747E+10 | 0.376041E+11 | 0.310859E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.300491E+10 | 0.656032E+10 | 0.552004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209834E+10 | 0.198186E+10 | 0.847633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172893E+10 | 0.879480E+09 | 0.180007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.425316E+11 | 0.232001E+12 | 0.768102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.161058E+10 | 0.234037E+09 | 30765660.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.666397E+10 | 0.554180E+11 | 0.180007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.174772E+10 | 0.958357E+09 | 0.113840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169138E+10 | 0.347257E+09 | 0.125279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.220220E+10 | 0.308452E+10 | 0.750161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180207E+10 | 0.247977E+10 | 0.440345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.304975E+10 | 0.133084E+11 | 0.246065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.676057E+10 | 0.506590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.638109E+10 | 0.515793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.649799E+10 | 0.490993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.468972E+10 | 0.322604E+11 | 0.147812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.237815E+10 | 0.584440E+10 | 0.532683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183375E+10 | 0.180010E+10 | 0.842736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178543E+10 | 0.936471E+09 | 0.184691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.408198E+11 | 0.212357E+12 | 0.684342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.169138E+10 | 0.347257E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.676057E+10 | 0.515793E+11 | 0.184691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.185087E+10 | 0.815330E+09 | 0.193367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177500E+10 | 0.276175E+09 | 0.207761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218641E+10 | 0.297972E+10 | 0.133299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.181079E+10 | 0.262171E+10 | 0.850025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.266496E+10 | 0.141103E+11 | 0.733734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.609163E+10 | 0.554428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.564886E+10 | 0.557283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.572425E+10 | 0.529644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.389883E+10 | 0.332050E+11 | 0.358958E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.212890E+10 | 0.544889E+10 | 0.989389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174948E+10 | 0.158250E+10 | 0.147516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199152E+10 | 0.852803E+09 | 0.305898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.375215E+11 | 0.226028E+12 | 0.118271E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.174948E+10 | 0.276175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.609163E+10 | 0.557283E+11 | 0.305898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.176900E+10 | 0.00 | 0.00 | 0.00 | 0.216619E+09 | 0.787271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161058E+10 | 0.00 | 0.00 | 0.00 | 65205417.06 | 0.898838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.228340E+10 | 0.00 | 0.00 | 0.00 | 0.759935E+09 | 0.654175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.190431E+10 | 0.00 | 0.00 | 0.00 | 0.692284E+09 | 0.422048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.320942E+10 | 0.00 | 0.00 | 0.00 | 0.347377E+10 | 0.122837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.666397E+10 | 0.00 | 0.00 | 0.00 | 0.143856E+11 | 57333570.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.633002E+10 | 0.00 | 0.00 | 0.00 | 0.144554E+11 | 30765660.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.663119E+10 | 0.00 | 0.00 | 0.00 | 0.142191E+11 | 58314859.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.529747E+10 | 0.00 | 0.00 | 0.00 | 0.946019E+10 | 0.256697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.300491E+10 | 0.00 | 0.00 | 0.00 | 0.163358E+10 | 0.352142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209834E+10 | 0.00 | 0.00 | 0.00 | 0.503872E+09 | 0.479623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172893E+10 | 0.00 | 0.00 | 0.00 | 0.236497E+09 | 0.100483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.425316E+11 | 0.00 | 0.00 | 0.00 | 0.601021E+11 | 0.476208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.161058E+10 | 0.00 | 0.00 | 0.00 | 65205417.06 | 30765660.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.666397E+10 | 0.00 | 0.00 | 0.00 | 0.144554E+11 | 0.100483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.174772E+10 | 0.00 | 0.00 | 0.00 | 0.251256E+09 | 0.499556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169138E+10 | 0.00 | 0.00 | 0.00 | 94917123.45 | 0.626134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.220220E+10 | 0.00 | 0.00 | 0.00 | 0.772387E+09 | 0.354397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180207E+10 | 0.00 | 0.00 | 0.00 | 0.657893E+09 | 0.214167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.304975E+10 | 0.00 | 0.00 | 0.00 | 0.332983E+10 | 0.120731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.676057E+10 | 0.00 | 0.00 | 0.00 | 0.134098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.638109E+10 | 0.00 | 0.00 | 0.00 | 0.134622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.649799E+10 | 0.00 | 0.00 | 0.00 | 0.127805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.468972E+10 | 0.00 | 0.00 | 0.00 | 0.814747E+10 | 17581015.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.237815E+10 | 0.00 | 0.00 | 0.00 | 0.145987E+10 | 0.247015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183375E+10 | 0.00 | 0.00 | 0.00 | 0.462096E+09 | 0.354347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178543E+10 | 0.00 | 0.00 | 0.00 | 0.249337E+09 | 0.927597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.408198E+11 | 0.00 | 0.00 | 0.00 | 0.550776E+11 | 0.323704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.169138E+10 | 0.00 | 0.00 | 0.00 | 94917123.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.676057E+10 | 0.00 | 0.00 | 0.00 | 0.134622E+11 | 0.927597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.185087E+10 | 0.00 | 0.00 | 0.00 | 0.217956E+09 | 0.121883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177500E+10 | 0.00 | 0.00 | 0.00 | 76432547.86 | 0.137276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218641E+10 | 0.00 | 0.00 | 0.00 | 0.755710E+09 | 0.888934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.181079E+10 | 0.00 | 0.00 | 0.00 | 0.700207E+09 | 0.588831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.266496E+10 | 0.00 | 0.00 | 0.00 | 0.356534E+10 | 0.547298E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.609163E+10 | 0.00 | 0.00 | 0.00 | 0.148056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.564886E+10 | 0.00 | 0.00 | 0.00 | 0.146905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.572425E+10 | 0.00 | 0.00 | 0.00 | 0.139308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.389883E+10 | 0.00 | 0.00 | 0.00 | 0.848851E+10 | 0.169176E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.212890E+10 | 0.00 | 0.00 | 0.00 | 0.138577E+10 | 0.638647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174948E+10 | 0.00 | 0.00 | 0.00 | 0.415724E+09 | 0.920041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199152E+10 | 0.00 | 0.00 | 0.00 | 0.231048E+09 | 0.198892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.375215E+11 | 0.00 | 0.00 | 0.00 | 0.592635E+11 | 0.768861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.174948E+10 | 0.00 | 0.00 | 0.00 | 76432547.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.609163E+10 | 0.00 | 0.00 | 0.00 | 0.148056E+11 | 0.198892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.451750E+10 | 0.00 | 0.00 | 23748844.24 | 0.00 | 0.00 | 0.114737E+11 | 0.00 | 0.43 |
February | 0.496884E+10 | 0.00 | 0.00 | 20919115.45 | 0.00 | 570411.85 | 0.970084E+10 | 0.00 | 0.40 |
March | 0.315195E+10 | 0.00 | 0.00 | 30835445.06 | 0.00 | 0.00 | 0.148191E+11 | 0.00 | 0.65 |
April | 0.198531E+10 | 0.00 | 0.00 | 27428763.78 | 0.00 | 0.00 | 0.132482E+11 | 0.00 | 0.62 |
May | 0.706204E+09 | 5222192.96 | 0.00 | 40949113.78 | 2236517.77 | 0.00 | 0.168913E+11 | 0.00 | 1.02 |
June | 0.494124E+09 | 0.545423E+09 | 0.00 | 31744233.04 | 72711881.54 | 0.00 | 0.603723E+10 | 0.00 | 0.89 |
July | 0.418616E+09 | 0.700201E+09 | 0.00 | 28211159.71 | 0.120881E+09 | 0.00 | 0.436687E+10 | 0.00 | 0.83 |
August | 0.583994E+09 | 0.524886E+09 | 0.00 | 41375139.11 | 27495523.10 | 0.00 | 0.798927E+10 | 0.00 | 0.95 |
September | 0.699495E+09 | 73836878.37 | 0.00 | 44275462.06 | 18454336.33 | 0.00 | 0.113979E+11 | 0.00 | 1.03 |
October | 0.182731E+10 | 0.00 | 0.00 | 41272766.32 | 0.00 | 0.00 | 0.186982E+11 | 0.00 | 0.80 |
November | 0.278473E+10 | 0.00 | 0.00 | 32692182.69 | 0.00 | 0.00 | 0.148262E+11 | 0.00 | 0.55 |
December | 0.549781E+10 | 0.00 | 0.00 | 20456948.55 | 0.00 | 1923207.61 | 0.104119E+11 | 0.00 | 0.39 |
Annual Sum or Average | 0.276359E+11 | 0.184957E+10 | 0.00 | 0.383909E+09 | 0.241779E+09 | 2493619.46 | 0.139861E+12 | 0.00 | 0.72 |
Minimum of Months | 0.418616E+09 | 0.00 | 0.00 | 20456948.55 | 0.00 | 0.00 | 0.436687E+10 | 0.00 | 0.39 |
Maximum of Months | 0.549781E+10 | 0.700201E+09 | 0.00 | 44275462.06 | 0.120881E+09 | 1923207.61 | 0.186982E+11 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101943E+11 | 0.00 | 0.00 | 2034948.48 | 0.00 | 0.153556E+09 | 0.172032E+10 | 0.00 | 0.31 |
February | 0.920829E+10 | 0.00 | 0.00 | 1618198.84 | 0.00 | 0.496569E+09 | 0.151685E+10 | 0.00 | 0.30 |
March | 0.802082E+10 | 0.00 | 0.00 | 7367897.01 | 0.00 | 86114649.84 | 0.455518E+10 | 0.00 | 0.44 |
April | 0.651181E+10 | 0.00 | 0.00 | 6618385.17 | 0.00 | 89502039.81 | 0.400761E+10 | 0.00 | 0.42 |
May | 0.222105E+10 | 2982132.59 | 0.00 | 20325228.80 | 3129659.94 | 0.00 | 0.910486E+10 | 0.00 | 0.66 |
June | 0.686568E+09 | 0.365461E+09 | 0.00 | 22297676.57 | 59986337.07 | 0.00 | 0.394861E+10 | 0.00 | 0.64 |
July | 0.537152E+09 | 0.496142E+09 | 0.00 | 19881347.12 | 0.110206E+09 | 0.00 | 0.290572E+10 | 0.00 | 0.60 |
August | 0.691322E+09 | 0.359789E+09 | 0.00 | 28343449.81 | 22425180.67 | 0.00 | 0.519480E+10 | 0.00 | 0.67 |
September | 0.102139E+10 | 56479272.19 | 0.00 | 26485191.35 | 19930315.27 | 0.00 | 0.669721E+10 | 0.00 | 0.68 |
October | 0.594387E+10 | 0.00 | 0.00 | 12342628.48 | 0.00 | 75942948.11 | 0.646711E+10 | 0.00 | 0.48 |
November | 0.880746E+10 | 0.00 | 0.00 | 4627980.74 | 0.00 | 42750198.64 | 0.298001E+10 | 0.00 | 0.36 |
December | 0.110940E+11 | 0.00 | 0.00 | 767964.27 | 0.00 | 0.607368E+09 | 0.940263E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.649381E+11 | 0.128085E+10 | 0.00 | 0.152711E+09 | 0.215677E+09 | 0.155180E+10 | 0.500385E+11 | 0.00 | 0.49 |
Minimum of Months | 0.537152E+09 | 0.00 | 0.00 | 767964.27 | 0.00 | 0.00 | 0.940263E+09 | 0.00 | 0.30 |
Maximum of Months | 0.110940E+11 | 0.496142E+09 | 0.00 | 28343449.81 | 0.110206E+09 | 0.607368E+09 | 0.910486E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.904039E+10 | 0.00 | 0.00 | 774249.61 | 0.00 | 0.145831E+10 | 0.738636E+09 | 0.00 | 0.30 |
February | 0.802983E+10 | 0.00 | 0.00 | 649375.86 | 0.00 | 0.169513E+10 | 0.801879E+09 | 0.00 | 0.29 |
March | 0.798925E+10 | 0.00 | 0.00 | 5102948.79 | 0.00 | 0.673671E+09 | 0.346278E+10 | 0.00 | 0.43 |
April | 0.655556E+10 | 0.00 | 0.00 | 4889033.29 | 0.00 | 0.542738E+09 | 0.337266E+10 | 0.00 | 0.42 |
May | 0.308268E+10 | 60230.78 | 0.00 | 17484806.81 | 1478338.57 | 39947802.94 | 0.790823E+10 | 0.00 | 0.66 |
June | 0.845320E+09 | 0.272092E+09 | 0.00 | 23240876.89 | 55203041.70 | 0.00 | 0.347567E+10 | 0.00 | 0.68 |
July | 0.607559E+09 | 0.359086E+09 | 0.00 | 20306003.15 | 0.107504E+09 | 0.00 | 0.245349E+10 | 0.00 | 0.62 |
August | 0.888338E+09 | 0.288260E+09 | 0.00 | 26682914.05 | 23060998.25 | 0.00 | 0.436437E+10 | 0.00 | 0.66 |
September | 0.173960E+10 | 38380103.64 | 0.00 | 21482381.65 | 14134369.26 | 0.00 | 0.505708E+10 | 0.00 | 0.66 |
October | 0.633818E+10 | 0.00 | 0.00 | 6426797.82 | 0.00 | 0.791429E+09 | 0.414171E+10 | 0.00 | 0.46 |
November | 0.857328E+10 | 0.00 | 0.00 | 2044469.61 | 0.00 | 0.826748E+09 | 0.152245E+10 | 0.00 | 0.34 |
December | 0.849445E+10 | 0.00 | 0.00 | 182940.86 | 0.00 | 0.277176E+10 | 0.289745E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.621844E+11 | 0.957878E+09 | 0.00 | 0.129267E+09 | 0.201380E+09 | 0.879974E+10 | 0.375887E+11 | 0.00 | 0.48 |
Minimum of Months | 0.607559E+09 | 0.00 | 0.00 | 182940.86 | 0.00 | 0.00 | 0.289745E+09 | 0.00 | 0.29 |
Maximum of Months | 0.904039E+10 | 0.359086E+09 | 0.00 | 26682914.05 | 0.107504E+09 | 0.277176E+10 | 0.790823E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.911575E+09 | 0.00 | 0.00 | 3633.29 | 0.00 | 0.164900E+10 | 9366099.93 | 0.00 | 0.32 |
February | 0.866758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153251E+10 | 0.00 | 0.00 | 0.31 |
March | 0.123189E+10 | 0.00 | 0.00 | 588782.46 | 0.00 | 0.986282E+09 | 0.336989E+09 | 0.00 | 0.42 |
April | 0.113350E+10 | 0.00 | 0.00 | 857749.19 | 0.00 | 0.618594E+09 | 0.501180E+09 | 0.00 | 0.43 |
May | 0.828778E+09 | 144469.75 | 0.00 | 4136554.78 | 201223.26 | 42330422.61 | 0.157193E+10 | 0.00 | 0.75 |
June | 0.205159E+09 | 0.101916E+09 | 0.00 | 6869148.66 | 10872285.50 | 0.00 | 0.868940E+09 | 0.00 | 0.90 |
July | 0.159241E+09 | 0.130444E+09 | 0.00 | 5671576.51 | 20152379.84 | 0.00 | 0.580548E+09 | 0.00 | 0.80 |
August | 0.283659E+09 | 97435294.86 | 0.00 | 6712195.40 | 4771335.37 | 0.00 | 0.900271E+09 | 0.00 | 0.77 |
September | 0.530110E+09 | 14200028.41 | 0.00 | 4782530.23 | 2951794.98 | 17930634.92 | 0.892166E+09 | 0.00 | 0.70 |
October | 0.130573E+10 | 0.00 | 0.00 | 659931.96 | 0.00 | 0.724627E+09 | 0.356915E+09 | 0.00 | 0.45 |
November | 0.977577E+09 | 0.00 | 0.00 | 154830.61 | 0.00 | 0.132245E+10 | 97931649.42 | 0.00 | 0.34 |
December | 0.633044E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240348E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.906702E+10 | 0.344140E+09 | 0.00 | 30436933.08 | 38949018.95 | 0.929721E+10 | 0.611624E+10 | 0.00 | 0.54 |
Minimum of Months | 0.159241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.130573E+10 | 0.130444E+09 | 0.00 | 6869148.66 | 20152379.84 | 0.240348E+10 | 0.157193E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131126E+10 | 0.00 | 0.00 | 123094.22 | 0.00 | 0.115472E+10 | 0.107504E+09 | 0.00 | 0.52 |
February | 0.118998E+10 | 0.00 | 0.00 | 375905.86 | 0.00 | 0.100842E+10 | 0.242356E+09 | 0.00 | 0.51 |
March | 0.114964E+10 | 0.00 | 0.00 | 2089926.92 | 0.00 | 0.735413E+09 | 0.116677E+10 | 0.00 | 0.82 |
April | 0.956136E+09 | 0.00 | 0.00 | 2355195.21 | 0.00 | 0.500478E+09 | 0.133143E+10 | 0.00 | 0.86 |
May | 0.728004E+09 | 141074.69 | 0.00 | 5251029.42 | 216903.50 | 24846325.79 | 0.217140E+10 | 0.00 | 1.37 |
June | 0.157740E+09 | 82013064.32 | 0.00 | 8505128.02 | 9091711.41 | 0.00 | 0.134619E+10 | 0.00 | 1.70 |
July | 0.142013E+09 | 0.118714E+09 | 0.00 | 7067634.26 | 13649922.44 | 0.00 | 0.724605E+09 | 0.00 | 1.35 |
August | 0.216543E+09 | 83771725.36 | 0.00 | 9195545.53 | 4987702.83 | 0.00 | 0.159390E+10 | 0.00 | 1.60 |
September | 0.475374E+09 | 12865203.43 | 0.00 | 6481641.11 | 3209017.84 | 12900236.33 | 0.139448E+10 | 0.00 | 1.41 |
October | 0.105871E+10 | 0.00 | 0.00 | 1903986.72 | 0.00 | 0.631955E+09 | 0.100863E+10 | 0.00 | 0.83 |
November | 0.123053E+10 | 0.00 | 0.00 | 496018.49 | 0.00 | 0.938846E+09 | 0.322892E+09 | 0.00 | 0.58 |
December | 0.103902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168460E+10 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 0.965495E+10 | 0.297505E+09 | 0.00 | 43845105.77 | 31155258.02 | 0.669219E+10 | 0.114102E+11 | 0.00 | 1.01 |
Minimum of Months | 0.142013E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.131126E+10 | 0.118714E+09 | 0.00 | 9195545.53 | 13649922.44 | 0.168460E+10 | 0.217140E+10 | 0.00 | 1.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.102372E+10 | 0.00 | 0.00 | 6627844.52 | 0.00 | 0.101602E+10 | 0.329253E+10 | 0.00 | 0.80 |
February | 0.963439E+09 | 0.00 | 0.00 | 7174290.84 | 0.00 | 0.936415E+09 | 0.332021E+10 | 0.00 | 0.76 |
March | 0.106755E+10 | 0.00 | 0.00 | 7142900.79 | 0.00 | 0.876424E+09 | 0.365210E+10 | 0.00 | 1.06 |
April | 0.116564E+10 | 0.00 | 0.00 | 4101435.47 | 0.00 | 0.631640E+09 | 0.220033E+10 | 0.00 | 0.82 |
May | 0.105635E+10 | 193153.49 | 0.00 | 6204914.62 | 270052.29 | 53705396.76 | 0.243820E+10 | 0.00 | 1.08 |
June | 0.362253E+09 | 0.115014E+09 | 0.00 | 7449716.23 | 14811750.92 | 0.00 | 0.905990E+09 | 0.00 | 1.05 |
July | 0.259994E+09 | 0.180083E+09 | 0.00 | 6387649.82 | 14823572.84 | 0.00 | 0.627585E+09 | 0.00 | 0.95 |
August | 0.386231E+09 | 0.139230E+09 | 0.00 | 10886908.48 | 6109744.65 | 0.00 | 0.137109E+10 | 0.00 | 1.13 |
September | 0.524141E+09 | 27167941.37 | 0.00 | 11635539.36 | 3886299.33 | 20454230.59 | 0.216628E+10 | 0.00 | 1.37 |
October | 0.877907E+09 | 0.00 | 0.00 | 10834962.92 | 0.00 | 0.759737E+09 | 0.440994E+10 | 0.00 | 1.33 |
November | 0.969838E+09 | 0.00 | 0.00 | 7929815.95 | 0.00 | 0.880759E+09 | 0.360428E+10 | 0.00 | 0.95 |
December | 0.114779E+10 | 0.00 | 0.00 | 5149009.73 | 0.00 | 0.150958E+10 | 0.217969E+10 | 0.00 | 0.70 |
Annual Sum or Average | 0.980486E+10 | 0.461688E+09 | 0.00 | 91524988.72 | 39901420.03 | 0.668474E+10 | 0.301682E+11 | 0.00 | 1.00 |
Minimum of Months | 0.259994E+09 | 0.00 | 0.00 | 4101435.47 | 0.00 | 0.00 | 0.627585E+09 | 0.00 | 0.70 |
Maximum of Months | 0.116564E+10 | 0.180083E+09 | 0.00 | 11635539.36 | 14823572.84 | 0.150958E+10 | 0.440994E+10 | 0.00 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120438E+10 | 0.00 | 0.00 | 487856.53 | 0.00 | 0.151716E+10 | 0.389323E+09 | 0.00 | 0.64 |
February | 0.114458E+10 | 0.00 | 0.00 | 775364.26 | 0.00 | 0.136071E+10 | 0.501897E+09 | 0.00 | 0.63 |
March | 0.145430E+10 | 0.00 | 0.00 | 2226199.74 | 0.00 | 0.101525E+10 | 0.117812E+10 | 0.00 | 1.01 |
April | 0.135913E+10 | 0.00 | 0.00 | 1992895.36 | 0.00 | 0.642647E+09 | 0.111542E+10 | 0.00 | 0.96 |
May | 0.116971E+10 | 172775.41 | 0.00 | 4298579.06 | 257430.34 | 46878129.33 | 0.171271E+10 | 0.00 | 1.40 |
June | 0.364415E+09 | 0.118381E+09 | 0.00 | 6163700.35 | 7971368.79 | 0.00 | 0.644711E+09 | 0.00 | 1.35 |
July | 0.276230E+09 | 0.127257E+09 | 0.00 | 4352977.93 | 20463930.37 | 0.00 | 0.447011E+09 | 0.00 | 1.18 |
August | 0.432609E+09 | 0.103286E+09 | 0.00 | 6610918.23 | 5508667.15 | 0.00 | 0.720706E+09 | 0.00 | 1.22 |
September | 0.706337E+09 | 16909125.74 | 0.00 | 5242379.50 | 2467130.12 | 23376434.34 | 0.995927E+09 | 0.00 | 1.30 |
October | 0.144461E+10 | 0.00 | 0.00 | 2558625.74 | 0.00 | 0.772560E+09 | 0.116533E+10 | 0.00 | 1.07 |
November | 0.125779E+10 | 0.00 | 0.00 | 798873.08 | 0.00 | 0.126186E+10 | 0.525402E+09 | 0.00 | 0.73 |
December | 0.963693E+09 | 0.00 | 0.00 | 223543.81 | 0.00 | 0.206021E+10 | 0.166298E+09 | 0.00 | 0.61 |
Annual Sum or Average | 0.117778E+11 | 0.366007E+09 | 0.00 | 35731913.60 | 36668526.78 | 0.870066E+10 | 0.956286E+10 | 0.00 | 1.01 |
Minimum of Months | 0.276230E+09 | 0.00 | 0.00 | 223543.81 | 0.00 | 0.00 | 0.166298E+09 | 0.00 | 0.61 |
Maximum of Months | 0.145430E+10 | 0.127257E+09 | 0.00 | 6610918.23 | 20463930.37 | 0.206021E+10 | 0.171271E+10 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160582E+10 | 0.00 | 0.00 | 0.31 |
February | 0.850590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165237E+10 | 0.00 | 0.00 | 0.31 |
March | 0.143300E+10 | 0.00 | 0.00 | 90785.70 | 0.00 | 0.104909E+10 | 58145805.62 | 0.00 | 0.39 |
April | 0.156808E+10 | 0.00 | 0.00 | 70086.68 | 0.00 | 0.513556E+09 | 78894599.47 | 0.00 | 0.39 |
May | 0.110531E+10 | 639878.31 | 0.00 | 2036847.17 | 748239.13 | 30869015.51 | 0.804850E+09 | 0.00 | 0.55 |
June | 0.315564E+09 | 0.117197E+09 | 0.00 | 4005045.64 | 15348637.63 | 0.00 | 0.606103E+09 | 0.00 | 0.66 |
July | 0.244029E+09 | 0.146819E+09 | 0.00 | 3480390.55 | 25516628.51 | 0.00 | 0.440814E+09 | 0.00 | 0.63 |
August | 0.329252E+09 | 0.108519E+09 | 0.00 | 5012472.20 | 5837532.52 | 0.00 | 0.811761E+09 | 0.00 | 0.67 |
September | 0.581717E+09 | 17144200.57 | 0.00 | 4552183.19 | 3895497.07 | 0.00 | 0.966316E+09 | 0.00 | 0.69 |
October | 0.165421E+10 | 0.00 | 0.00 | 716144.44 | 0.00 | 0.387951E+09 | 0.395500E+09 | 0.00 | 0.43 |
November | 0.154785E+10 | 0.00 | 0.00 | 104093.66 | 0.00 | 0.814614E+09 | 76812100.56 | 0.00 | 0.34 |
December | 0.969537E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191949E+10 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.116649E+11 | 0.390319E+09 | 0.00 | 20068049.22 | 51346534.87 | 0.797375E+10 | 0.423920E+10 | 0.00 | 0.47 |
Minimum of Months | 0.244029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.165421E+10 | 0.146819E+09 | 0.00 | 5012472.20 | 25516628.51 | 0.191949E+10 | 0.966316E+09 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131063E+10 | 0.00 | 0.00 | 106076.36 | 0.00 | 0.922099E+09 | 82904799.14 | 0.00 | 0.44 |
February | 0.110804E+10 | 0.00 | 0.00 | 319590.98 | 0.00 | 0.865121E+09 | 0.203552E+09 | 0.00 | 0.43 |
March | 0.110490E+10 | 0.00 | 0.00 | 1512573.25 | 0.00 | 0.579139E+09 | 0.830413E+09 | 0.00 | 0.65 |
April | 0.111792E+10 | 0.00 | 0.00 | 1628511.77 | 0.00 | 0.252373E+09 | 0.860861E+09 | 0.00 | 0.67 |
May | 0.670108E+09 | 925011.02 | 0.00 | 3925939.36 | 418249.20 | 5538531.23 | 0.154873E+10 | 0.00 | 1.02 |
June | 0.187384E+09 | 0.106544E+09 | 0.00 | 5971899.78 | 11550333.56 | 0.00 | 0.107942E+10 | 0.00 | 1.33 |
July | 0.157853E+09 | 0.141541E+09 | 0.00 | 5007927.56 | 17108416.06 | 0.00 | 0.642928E+09 | 0.00 | 1.10 |
August | 0.227028E+09 | 0.110196E+09 | 0.00 | 7792112.16 | 4800646.49 | 0.00 | 0.143736E+10 | 0.00 | 1.40 |
September | 0.337771E+09 | 17193550.48 | 0.00 | 6830868.66 | 3451129.01 | 0.00 | 0.160208E+10 | 0.00 | 1.35 |
October | 0.100256E+10 | 0.00 | 0.00 | 2588256.82 | 0.00 | 0.331169E+09 | 0.128167E+10 | 0.00 | 0.78 |
November | 0.133410E+10 | 0.00 | 0.00 | 823765.19 | 0.00 | 0.487369E+09 | 0.427219E+09 | 0.00 | 0.51 |
December | 0.114658E+10 | 0.00 | 0.00 | 3948.37 | 0.00 | 0.126317E+10 | 16211797.30 | 0.00 | 0.43 |
Annual Sum or Average | 0.970487E+10 | 0.376399E+09 | 0.00 | 36511470.26 | 37328774.32 | 0.470598E+10 | 0.100133E+11 | 0.00 | 0.84 |
Minimum of Months | 0.157853E+09 | 0.00 | 0.00 | 3948.37 | 0.00 | 0.00 | 16211797.30 | 0.00 | 0.43 |
Maximum of Months | 0.133410E+10 | 0.141541E+09 | 0.00 | 7792112.16 | 17108416.06 | 0.126317E+10 | 0.160208E+10 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106020E+10 | 0.00 | 0.00 | 2138285.08 | 0.00 | 0.192934E+10 | 0.124411E+10 | 0.00 | 0.57 |
February | 0.909439E+09 | 0.00 | 0.00 | 1823898.87 | 0.00 | 0.201286E+10 | 0.959608E+09 | 0.00 | 0.52 |
March | 0.105336E+10 | 0.00 | 0.00 | 2423752.06 | 0.00 | 0.168580E+10 | 0.117318E+10 | 0.00 | 0.71 |
April | 0.121341E+10 | 0.00 | 0.00 | 844615.82 | 0.00 | 0.121345E+10 | 0.430348E+09 | 0.00 | 0.52 |
May | 0.126308E+10 | 1460919.85 | 0.00 | 2103010.23 | 534075.11 | 0.467994E+09 | 0.516875E+09 | 0.00 | 0.65 |
June | 0.434916E+09 | 0.166517E+09 | 0.00 | 4243970.41 | 16063257.25 | 35145003.37 | 0.434048E+09 | 0.00 | 0.73 |
July | 0.333395E+09 | 0.210465E+09 | 0.00 | 3540737.91 | 26903089.39 | 14090165.32 | 0.333085E+09 | 0.00 | 0.70 |
August | 0.416399E+09 | 0.193442E+09 | 0.00 | 8570883.70 | 3719329.82 | 43612879.69 | 0.901513E+09 | 0.00 | 0.92 |
September | 0.520319E+09 | 36058975.28 | 0.00 | 10075817.51 | 3865967.69 | 0.117797E+09 | 0.172537E+10 | 0.00 | 1.22 |
October | 0.772243E+09 | 0.00 | 0.00 | 8754719.43 | 0.00 | 0.122608E+10 | 0.301118E+10 | 0.00 | 1.05 |
November | 0.943188E+09 | 0.00 | 0.00 | 4474152.61 | 0.00 | 0.144876E+10 | 0.207183E+10 | 0.00 | 0.74 |
December | 0.100924E+10 | 0.00 | 0.00 | 2497684.74 | 0.00 | 0.259868E+10 | 0.101034E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.992918E+10 | 0.607943E+09 | 0.00 | 51491528.38 | 51085719.26 | 0.127936E+11 | 0.138115E+11 | 0.00 | 0.74 |
Minimum of Months | 0.333395E+09 | 0.00 | 0.00 | 844615.82 | 0.00 | 14090165.32 | 0.333085E+09 | 0.00 | 0.52 |
Maximum of Months | 0.126308E+10 | 0.210465E+09 | 0.00 | 10075817.51 | 26903089.39 | 0.259868E+10 | 0.301118E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129412E+10 | 0.00 | 0.00 | 275244.76 | 0.00 | 0.111890E+10 | 0.215098E+09 | 0.00 | 0.50 |
February | 0.116778E+10 | 0.00 | 0.00 | 375348.01 | 0.00 | 0.104223E+10 | 0.254224E+09 | 0.00 | 0.48 |
March | 0.136095E+10 | 0.00 | 0.00 | 1252465.50 | 0.00 | 0.761933E+09 | 0.609643E+09 | 0.00 | 0.73 |
April | 0.144843E+10 | 0.00 | 0.00 | 1011542.89 | 0.00 | 0.334766E+09 | 0.508968E+09 | 0.00 | 0.68 |
May | 0.990463E+09 | 1251407.90 | 0.00 | 2749793.14 | 468558.16 | 21244820.67 | 0.104606E+10 | 0.00 | 0.96 |
June | 0.325518E+09 | 0.141224E+09 | 0.00 | 3759518.82 | 9761982.71 | 0.00 | 0.527500E+09 | 0.00 | 1.01 |
July | 0.260009E+09 | 0.146999E+09 | 0.00 | 2794982.45 | 21274038.69 | 0.00 | 0.392289E+09 | 0.00 | 0.91 |
August | 0.329704E+09 | 0.124243E+09 | 0.00 | 5040522.77 | 5505229.43 | 0.00 | 0.722252E+09 | 0.00 | 1.03 |
September | 0.494593E+09 | 19758664.03 | 0.00 | 5092939.60 | 2534701.96 | 0.00 | 0.109931E+10 | 0.00 | 1.15 |
October | 0.131468E+10 | 0.00 | 0.00 | 2600805.20 | 0.00 | 0.364151E+09 | 0.117262E+10 | 0.00 | 0.88 |
November | 0.150959E+10 | 0.00 | 0.00 | 759973.88 | 0.00 | 0.574491E+09 | 0.448666E+09 | 0.00 | 0.58 |
December | 0.119429E+10 | 0.00 | 0.00 | 169858.12 | 0.00 | 0.139542E+10 | 0.132317E+09 | 0.00 | 0.49 |
Annual Sum or Average | 0.116901E+11 | 0.433476E+09 | 0.00 | 25882995.14 | 39544510.96 | 0.561313E+10 | 0.712895E+10 | 0.00 | 0.78 |
Minimum of Months | 0.260009E+09 | 0.00 | 0.00 | 169858.12 | 0.00 | 0.00 | 0.132317E+09 | 0.00 | 0.48 |
Maximum of Months | 0.150959E+10 | 0.146999E+09 | 0.00 | 5092939.60 | 21274038.69 | 0.139542E+10 | 0.117262E+10 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125959E+10 | 0.00 | 0.00 | 3407.40 | 0.00 | 0.131850E+10 | 6391173.88 | 0.00 | 0.31 |
February | 0.119718E+10 | 0.00 | 0.00 | 1246.13 | 0.00 | 0.122712E+10 | 7331494.64 | 0.00 | 0.31 |
March | 0.146871E+10 | 0.00 | 0.00 | 678585.34 | 0.00 | 0.738959E+09 | 0.372000E+09 | 0.00 | 0.42 |
April | 0.141433E+10 | 0.00 | 0.00 | 891672.40 | 0.00 | 0.320027E+09 | 0.476701E+09 | 0.00 | 0.42 |
May | 0.751613E+09 | 1403402.94 | 0.00 | 4499173.45 | 433071.17 | 18467369.22 | 0.166690E+10 | 0.00 | 0.73 |
June | 0.188086E+09 | 0.137887E+09 | 0.00 | 6063517.13 | 12541980.11 | 0.00 | 0.910308E+09 | 0.00 | 0.85 |
July | 0.162385E+09 | 0.185423E+09 | 0.00 | 5070381.96 | 22350758.94 | 0.00 | 0.628151E+09 | 0.00 | 0.78 |
August | 0.239111E+09 | 0.126815E+09 | 0.00 | 6611837.37 | 4757607.79 | 0.00 | 0.101245E+10 | 0.00 | 0.77 |
September | 0.485771E+09 | 22031472.97 | 0.00 | 5007269.82 | 4193525.21 | 2605802.90 | 0.103322E+10 | 0.00 | 0.70 |
October | 0.149389E+10 | 0.00 | 0.00 | 918759.85 | 0.00 | 0.459875E+09 | 0.455625E+09 | 0.00 | 0.44 |
November | 0.141033E+10 | 0.00 | 0.00 | 217259.61 | 0.00 | 0.908033E+09 | 0.134416E+09 | 0.00 | 0.35 |
December | 0.976943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195639E+10 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.110479E+11 | 0.473560E+09 | 0.00 | 29963110.46 | 44276943.23 | 0.694998E+10 | 0.670350E+10 | 0.00 | 0.53 |
Minimum of Months | 0.162385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.149389E+10 | 0.185423E+09 | 0.00 | 6611837.37 | 22350758.94 | 0.195639E+10 | 0.166690E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154399E+10 | 0.00 | 0.00 | 261910.08 | 0.00 | 0.105461E+10 | 0.200142E+09 | 0.00 | 0.54 |
February | 0.139306E+10 | 0.00 | 0.00 | 686905.38 | 0.00 | 0.934647E+09 | 0.366298E+09 | 0.00 | 0.54 |
March | 0.135307E+10 | 0.00 | 0.00 | 2506510.93 | 0.00 | 0.628309E+09 | 0.128940E+10 | 0.00 | 0.86 |
April | 0.125576E+10 | 0.00 | 0.00 | 2613391.70 | 0.00 | 0.262483E+09 | 0.134430E+10 | 0.00 | 0.87 |
May | 0.717804E+09 | 1177073.80 | 0.00 | 5479949.53 | 474123.97 | 7161210.75 | 0.222398E+10 | 0.00 | 1.34 |
June | 0.168980E+09 | 0.107346E+09 | 0.00 | 7626615.72 | 11350950.02 | 0.00 | 0.137368E+10 | 0.00 | 1.58 |
July | 0.144763E+09 | 0.158506E+09 | 0.00 | 6331469.58 | 16939531.09 | 0.00 | 0.784981E+09 | 0.00 | 1.29 |
August | 0.230161E+09 | 0.109225E+09 | 0.00 | 8813710.46 | 5139297.41 | 0.00 | 0.165546E+10 | 0.00 | 1.55 |
September | 0.449974E+09 | 19678564.86 | 0.00 | 6613205.81 | 4591048.67 | 474677.13 | 0.156136E+10 | 0.00 | 1.39 |
October | 0.124586E+10 | 0.00 | 0.00 | 2473121.92 | 0.00 | 0.509498E+09 | 0.121570E+10 | 0.00 | 0.86 |
November | 0.154505E+10 | 0.00 | 0.00 | 784194.17 | 0.00 | 0.775702E+09 | 0.405738E+09 | 0.00 | 0.61 |
December | 0.128442E+10 | 0.00 | 0.00 | 36413.23 | 0.00 | 0.162779E+10 | 36908159.55 | 0.00 | 0.53 |
Annual Sum or Average | 0.113329E+11 | 0.395933E+09 | 0.00 | 44227398.51 | 38494951.17 | 0.580067E+10 | 0.124580E+11 | 0.00 | 1.00 |
Minimum of Months | 0.144763E+09 | 0.00 | 0.00 | 36413.23 | 0.00 | 0.00 | 36908159.55 | 0.00 | 0.53 |
Maximum of Months | 0.154505E+10 | 0.158506E+09 | 0.00 | 8813710.46 | 16939531.09 | 0.162779E+10 | 0.222398E+10 | 0.00 | 1.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126059E+10 | 0.00 | 0.00 | 7947606.50 | 0.00 | 0.696698E+09 | 0.358844E+10 | 0.00 | 0.82 |
February | 0.105755E+10 | 0.00 | 0.00 | 8322899.67 | 0.00 | 0.739652E+09 | 0.355841E+10 | 0.00 | 0.78 |
March | 0.118858E+10 | 0.00 | 0.00 | 7754324.13 | 0.00 | 0.638616E+09 | 0.355631E+10 | 0.00 | 1.04 |
April | 0.140052E+10 | 0.00 | 0.00 | 4233401.75 | 0.00 | 0.299495E+09 | 0.198394E+10 | 0.00 | 0.79 |
May | 0.895777E+09 | 2137442.95 | 0.00 | 6499346.75 | 535591.39 | 26427251.68 | 0.240505E+10 | 0.00 | 1.01 |
June | 0.325117E+09 | 0.158177E+09 | 0.00 | 6356756.63 | 15317950.53 | 0.00 | 0.863187E+09 | 0.00 | 0.94 |
July | 0.236179E+09 | 0.246457E+09 | 0.00 | 5407509.60 | 19297676.27 | 0.00 | 0.635079E+09 | 0.00 | 0.88 |
August | 0.303757E+09 | 0.193955E+09 | 0.00 | 9923599.28 | 4292992.81 | 0.00 | 0.139906E+10 | 0.00 | 1.07 |
September | 0.474031E+09 | 44196128.67 | 0.00 | 11017485.64 | 5183565.01 | 3439945.36 | 0.213654E+10 | 0.00 | 1.30 |
October | 0.100144E+10 | 0.00 | 0.00 | 12148996.82 | 0.00 | 0.527588E+09 | 0.438931E+10 | 0.00 | 1.30 |
November | 0.119587E+10 | 0.00 | 0.00 | 9424366.26 | 0.00 | 0.548270E+09 | 0.388233E+10 | 0.00 | 0.98 |
December | 0.125223E+10 | 0.00 | 0.00 | 6348072.12 | 0.00 | 0.119882E+10 | 0.252685E+10 | 0.00 | 0.72 |
Annual Sum or Average | 0.105916E+11 | 0.644922E+09 | 0.00 | 95384365.13 | 44627776.01 | 0.467901E+10 | 0.309245E+11 | 0.00 | 0.97 |
Minimum of Months | 0.236179E+09 | 0.00 | 0.00 | 4233401.75 | 0.00 | 0.00 | 0.635079E+09 | 0.00 | 0.72 |
Maximum of Months | 0.140052E+10 | 0.246457E+09 | 0.00 | 12148996.82 | 19297676.27 | 0.119882E+10 | 0.438931E+10 | 0.00 | 1.30 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.159713E+10 | 0.00 | 0.00 | 587347.47 | 0.00 | 0.114317E+10 | 0.402695E+09 | 0.00 | 0.62 |
February | 0.141699E+10 | 0.00 | 0.00 | 854944.11 | 0.00 | 0.109970E+10 | 0.515958E+09 | 0.00 | 0.62 |
March | 0.165764E+10 | 0.00 | 0.00 | 2277530.96 | 0.00 | 0.743329E+09 | 0.109680E+10 | 0.00 | 0.97 |
April | 0.162053E+10 | 0.00 | 0.00 | 1963776.33 | 0.00 | 0.317382E+09 | 0.971922E+09 | 0.00 | 0.91 |
May | 0.963542E+09 | 1900308.90 | 0.00 | 4477013.86 | 521043.03 | 24546640.30 | 0.171864E+10 | 0.00 | 1.29 |
June | 0.360039E+09 | 0.160073E+09 | 0.00 | 4870554.58 | 8115898.50 | 0.00 | 0.596953E+09 | 0.00 | 1.20 |
July | 0.270613E+09 | 0.184857E+09 | 0.00 | 3464353.20 | 20084784.39 | 0.00 | 0.445890E+09 | 0.00 | 1.07 |
August | 0.384539E+09 | 0.138416E+09 | 0.00 | 5835504.34 | 5242982.19 | 0.00 | 0.743428E+09 | 0.00 | 1.14 |
September | 0.636309E+09 | 25983680.90 | 0.00 | 4959773.35 | 3436694.28 | 8683308.38 | 0.101749E+10 | 0.00 | 1.20 |
October | 0.163521E+10 | 0.00 | 0.00 | 2812843.87 | 0.00 | 0.532918E+09 | 0.114105E+10 | 0.00 | 1.01 |
November | 0.165590E+10 | 0.00 | 0.00 | 932570.78 | 0.00 | 0.872070E+09 | 0.536306E+09 | 0.00 | 0.71 |
December | 0.129570E+10 | 0.00 | 0.00 | 279496.68 | 0.00 | 0.177707E+10 | 0.194701E+09 | 0.00 | 0.60 |
Annual Sum or Average | 0.134941E+11 | 0.511230E+09 | 0.00 | 33315709.52 | 37401402.40 | 0.651886E+10 | 0.938184E+10 | 0.00 | 0.95 |
Minimum of Months | 0.270613E+09 | 0.00 | 0.00 | 279496.68 | 0.00 | 0.00 | 0.194701E+09 | 0.00 | 0.60 |
Maximum of Months | 0.165764E+10 | 0.184857E+09 | 0.00 | 5835504.34 | 20084784.39 | 0.177707E+10 | 0.171864E+10 | 0.00 | 1.29 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.253549E+12 | 0.138312E+11 | 0.00 | 0.169561E+12 | 0.800627E+10 |
February | 0.310891E+12 | 0.177432E+11 | 0.00 | 0.154253E+12 | 0.576703E+10 |
March | 0.374675E+12 | 0.177989E+11 | 0.00 | 0.181663E+12 | 0.142389E+11 |
April | 0.386577E+12 | 0.170386E+11 | 0.00 | 0.179113E+12 | 0.113681E+11 |
May | 0.449353E+12 | 0.934825E+10 | 0.00 | 0.212220E+12 | 0.517090E+11 |
June | 0.466036E+12 | 0.260562E+10 | 0.00 | 0.128099E+12 | 0.203014E+12 |
July | 0.435684E+12 | 0.193269E+10 | 0.00 | 0.102381E+12 | 0.205334E+12 |
August | 0.434055E+12 | 0.255971E+10 | 0.00 | 0.110549E+12 | 0.197748E+12 |
September | 0.331504E+12 | 0.553945E+10 | 0.00 | 0.165493E+12 | 0.129259E+12 |
October | 0.296792E+12 | 0.142897E+11 | 0.00 | 0.212018E+12 | 0.244235E+11 |
November | 0.265597E+12 | 0.145235E+11 | 0.00 | 0.186731E+12 | 0.102749E+11 |
December | 0.214398E+12 | 0.221567E+11 | 0.00 | 0.157233E+12 | 0.103472E+11 |
Annual Sum or Average | 0.421911E+13 | 0.139367E+12 | 0.00 | 0.195931E+13 | 0.871489E+12 |
Minimum of Months | 0.214398E+12 | 0.193269E+10 | 0.00 | 0.102381E+12 | 0.576703E+10 |
Maximum of Months | 0.466036E+12 | 0.221567E+11 | 0.00 | 0.212220E+12 | 0.205334E+12 |