Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 08:35:11
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1721.53 | 345.54 | 345.54 |
Net Site Energy | 1721.53 | 345.54 | 345.54 |
Total Source Energy | 5205.27 | 1044.78 | 1044.78 |
Net Source Energy | 5205.27 | 1044.78 | 1044.78 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 30.76 | 19.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 314.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 130.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 99.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1603.04 | 118.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 30.76 | 19.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 314.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 280.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 71.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 130.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 99.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 30.76 | 19.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 314.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 280.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 71.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 130.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 99.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 95.42 | 23.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 321.75 | 23.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 95.42 | 23.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 321.75 | 23.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1603.039 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1603.039 | 100.00 |
Total On-Site and Utility Electric Sources | 1603.039 | 100.00 |
Total Electricity End Uses | 1603.039 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 117.83 |
Time Setpoint Not Met During Occupied Cooling | 297.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1570.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.5763 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 7.5763 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 7.5763 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 20-JUL-15:09 | 27-DEC-07:30 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 45605.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 77389.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 23688.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 43769.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 920.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 35506.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8083.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 181276.11 | 53689.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 45605.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 77389.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 23688.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 7527.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 920.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 35506.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8083.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 97.42 | 20.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 995.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 889.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 227.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2413.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 41.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 412.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 107.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5076.82 | 128.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 19.55 | 4.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 199.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 178.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 82.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 21.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1019.00 | 25.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 19.55 | 4.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 199.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 178.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 82.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 21.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1019.00 | 25.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.23 | 0.231935 | 0.249000 | 0.804596 | 0.618494 | 0.500000 | 0.001643 |
CORE_MID VAV BOX COMPONENT | 2.37 | 0.315601 | 0.327000 | 0.776525 | 0.841602 | 0.500000 | 0.001207 |
CORE_TOP VAV BOX COMPONENT | 2.59 | 0.289336 | 0.313000 | 0.810750 | 0.771563 | 0.500000 | 0.001317 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.871840 | 0.181216 | 0.200000 | 0.174368 | 0.483244 | 0.500000 | 0.002102 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.752455 | 0.132927 | 0.200000 | 0.150491 | 0.354473 | 0.500000 | 0.002866 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.959672 | 0.164631 | 0.200000 | 0.191934 | 0.439016 | 0.500000 | 0.002314 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.865682 | 0.115533 | 0.200000 | 0.173136 | 0.308089 | 0.500000 | 0.003298 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.700348 | 0.225590 | 0.242000 | 0.169484 | 0.601574 | 0.500000 | 0.001689 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.650007 | 0.153878 | 0.200000 | 0.130001 | 0.410341 | 0.500000 | 0.002476 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.778504 | 0.202943 | 0.218000 | 0.169714 | 0.541181 | 0.500000 | 0.001877 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.692802 | 0.144363 | 0.200000 | 0.138560 | 0.384969 | 0.500000 | 0.002639 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.743837 | 0.212401 | 0.220000 | 0.163644 | 0.566403 | 0.500000 | 0.001794 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.711274 | 0.140623 | 0.200000 | 0.142255 | 0.374996 | 0.500000 | 0.002709 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.829319 | 0.190508 | 0.200000 | 0.165864 | 0.508020 | 0.500000 | 0.002000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.767585 | 0.130299 | 0.200000 | 0.153517 | 0.347463 | 0.500000 | 0.002924 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 23305.73 |
CORE_MID VAV BOX REHEAT COIL | 22492.62 |
CORE_TOP VAV BOX REHEAT COIL | 34764.69 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 15594.16 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 10193.44 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 15488.29 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10130.62 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 10899.06 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7212.13 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 10802.80 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7148.83 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 11973.89 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 7880.84 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 11876.37 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 7825.18 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.03 | 1.41 | 6.05 | 1.67 | 5.59 | 5.59 | 0.300000 | 0.298633 | 5.59 |
PACU_VAV_MID | 2.71 | 1.40 | 5.43 | 2.03 | 4.90 | 4.90 | 0.300000 | 0.415418 | 4.90 |
PACU_VAV_TOP | 3.02 | 1.50 | 6.04 | 2.97 | 5.81 | 5.81 | 0.300000 | 0.511677 | 5.81 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.59 |
PACU_VAV_MID_OA_CONTROLLER | 4.90 |
PACU_VAV_TOP_OA_CONTROLLER | 5.81 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.59 | 99976.57 | 0.800358 | 1.86 | 33322.19 | 0.800358 |
PACU_VAV_MID COOLING COIL | 4.90 | 89833.43 | 0.800650 | 1.63 | 29941.48 | 0.800650 |
PACU_VAV_TOP COOLING COIL | 5.81 | 103334.65 | 0.800427 | 1.94 | 34441.44 | 0.800427 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 18426.87 |
PACU_VAV_MID HEATING COIL | 20223.05 |
PACU_VAV_TOP HEATING COIL | 19894.49 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.59 |
PACU_VAV_MID FAN | 4.90 |
PACU_VAV_TOP FAN | 5.81 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 32.411 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9320 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9163 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.269 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8390 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8573 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5538 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27971961E-12 | 0.14534712E-14 | -0.84678956E-13 | 0.82684317E-16 |
43 | 6 | 0.26817376E-07 | 0.25687399E-09 | 0.61588016E-08 | -0.12527087E-12 |
44 | 5 | -0.18065003E-03 | 0.22251366E-05 | -0.93037841E-04 | 0.60936178E-08 |
45 | 4 | 0.28101542 | 0.10946024E-02 | 0.95683253E-01 | -0.32007147E-04 |
46 | 3 | -7.0457283 | 0.34231649E-01 | -2.2734647 | 0.27928366E-01 |
47 | 2 | 40.143429 | 0.12270019 | 14.996275 | -0.32523640 |
48 | 1 | -79.987958 | 0.55761501E-01 | -28.900564 | 1.0667320 |
49 | 0 | 46.824342 | 0.11295401E-02 | 16.297084 | |
50 | 7 | -0.28233695E-12 | 0.14433069E-14 | -0.85363548E-13 | 0.83491456E-16 |
51 | 6 | 0.27004714E-07 | 0.25312183E-09 | 0.62001510E-08 | -0.12627076E-12 |
52 | 5 | -0.18161011E-03 | 0.21898175E-05 | -0.93520278E-04 | 0.61339935E-08 |
53 | 4 | 0.28215201 | 0.10760039E-02 | 0.96091377E-01 | -0.32166146E-04 |
54 | 3 | -7.0682688 | 0.33616209E-01 | -2.2801509 | 0.28038740E-01 |
55 | 2 | 40.217804 | 0.12038787 | 15.023777 | -0.32606455 |
56 | 1 | -80.044990 | 0.54668782E-01 | -28.925243 | 1.0679473 |
57 | 0 | 46.824342 | 0.11065724E-02 | 16.296477 | |
58 | 6 | 0.22748378E-07 | 0.33059726E-09 | 0.52605359E-08 | -0.10371465E-12 |
59 | 5 | -0.15952455E-03 | 0.29533519E-05 | -0.82380770E-04 | 0.52144884E-08 |
60 | 4 | 0.25560578 | 0.14926938E-02 | 0.86578981E-01 | -0.28493712E-04 |
61 | 3 | -6.5408460 | 0.47808585E-01 | -2.1237636 | 0.25458881E-01 |
62 | 2 | 38.476406 | 0.17496760 | 14.378110 | -0.30668036 |
63 | 1 | -78.708466 | 0.80951212E-01 | -28.345189 | 1.0394692 |
64 | 0 | 46.824351 | 0.16689207E-02 | 16.311239 | |
65 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
66 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
67 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
68 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
69 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
70 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
71 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
72 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
73 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
74 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
75 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
76 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
77 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
78 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
79 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
80 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
81 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
82 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
83 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
84 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
85 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
86 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
87 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
88 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
89 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
90 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
91 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
92 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
93 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
94 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
95 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
96 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
97 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
98 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
99 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
100 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
101 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
102 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
103 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
104 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
105 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.4644_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.640 | 2.640 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.640 | 2.640 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.4644_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.640 | 2.640 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.640 | 2.640 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.48111E-002 | 0.16139 | 0.61554 | 0.61554 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11929 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.48111E-002 | 0.16139 | 0.61554 | 0.61554 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11929 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.48111E-002 | 0.16139 | 0.61554 | 0.61554 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11929 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.48111E-002 | 0.16139 | 0.61554 | 0.61554 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11929 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.9748E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.0136E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4344E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.4676E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5081E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5349E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4264E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4410E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.8825E-002 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1631E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.9549E-002 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5454E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.7940E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7412E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8057E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0496E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.9746E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.0143E-003 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4342E-003 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.4683E-003 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5080E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5354E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4263E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4409E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8344E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2455E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5360E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.0268E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8445E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9254E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2668E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5265E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5074E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5219E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2707E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2812E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2101E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2137E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8320E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8371E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4475E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4803E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0579E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0837E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7986E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8165E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4263E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4409E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2669E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3239E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7575E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0121E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6766E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.1147E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8057E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0496E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4476E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4804E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0579E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0837E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7985E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8161E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4264E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4410E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7407E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2015E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4220E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9730E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7581E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8857E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2668E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5265E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4564E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4930E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2084E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2471E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1632E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1804E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8321E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8372E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.7312E-002 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.0475E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.6119E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.4917E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.1358E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.4507E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.1564E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.4627E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6900E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1650E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.4103E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9571E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.7348E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.8661E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.1886E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.4843E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.5806E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7225E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0397E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3580E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.9567E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.0311E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1564E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4627E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.5999E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1238E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3006E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9069E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6516E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8286E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.1887E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.4843E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.7313E-002 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.0471E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.6119E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.4911E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.1355E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.4503E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.1562E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.4625E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6900E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1649E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.4103E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9570E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.7346E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.8660E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.1884E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.4841E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.5807E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7225E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0398E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3579E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.9566E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.0310E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1562E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4625E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6000E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1236E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3006E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9067E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6514E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8284E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.1884E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4842E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 38880.31254 | 38880.31254 | 3.23131 | 3.23131 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 6236.20772 | 6236.20772 | 0.30292 | 0.42469 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 28603.26159 | 28603.26159 | 2.37469 | 2.37469 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 13680.78387 | 13680.78387 | 0.66801 | 0.66801 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 30918.61031 | 30918.61031 | 2.59026 | 2.59026 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 37.71000 | 6.87086E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 24476.28114 | 24476.28114 | 1.20020 | 1.20020 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 10407.15309 | 10407.15309 | 0.87184 | 0.87184 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 37.84000 | 6.87107E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 10950.14587 | 10950.14587 | 0.53837 | 0.53837 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 8982.09639 | 8982.09639 | 0.75245 | 0.75245 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 33.48500 | 6.86412E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 7157.23745 | 7157.23745 | 0.35191 | 0.35191 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 11455.61092 | 11455.61092 | 0.95967 | 0.95967 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 10875.99695 | 10875.99695 | 0.53471 | 0.53471 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10333.70238 | 10333.70238 | 0.86568 | 0.86568 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 7113.24098 | 7113.24098 | 0.34974 | 0.34974 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 8359.93273 | 8359.93273 | 0.70035 | 0.70035 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 7660.70942 | 7660.70942 | 0.37627 | 0.37627 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 7759.06540 | 7759.06540 | 0.65001 | 0.65001 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 33.48500 | 6.86412E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 5068.48655 | 5068.48655 | 0.24899 | 0.24899 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 9292.87316 | 9292.87316 | 0.77850 | 0.77850 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10000 | 6.87148E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 7593.29614 | 7593.29614 | 0.37295 | 0.37295 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8269.91296 | 8269.91296 | 0.69280 | 0.69280 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 36.45333 | 6.86884E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 5024.15130 | 5024.15130 | 0.24680 | 0.24680 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8879.12474 | 8879.12474 | 0.74384 | 0.74384 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 8414.14202 | 8414.14202 | 0.41338 | 0.41338 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8490.47762 | 8490.47762 | 0.71127 | 0.71127 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 32.79167 | 6.86302E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5537.24707 | 5537.24707 | 0.27207 | 0.27207 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 9899.53729 | 9899.53729 | 0.82932 | 0.82932 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 8345.85356 | 8345.85356 | 0.41001 | 0.41001 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9162.66628 | 9162.66628 | 0.76759 | 0.76759 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 5498.26281 | 5498.26281 | 0.27015 | 0.27015 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 83332.79 | 5.59117 | 5.59117 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 22528.59 | 1.66971 | 1.66971 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 75036.64 | 4.89538 | 4.89538 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 22265.13 | 2.03363 | 2.03363 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 85668.27 | 5.81409 | 5.81409 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 22564.00 | 2.97493 | 2.97493 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.23131 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23194 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80460 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61849 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.64270E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23305.72682 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.37469 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31560 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32700 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77652 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84160 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.20722E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22492.62378 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.59026 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28934 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31300 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81075 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77156 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.31681E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 34764.68866 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87184 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18122 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17437 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48324 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10246E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15594.15888 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75245 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13293 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15049 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35447 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.86623E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10193.43622 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95967 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16463 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19193 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43902 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.31427E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15488.29081 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86568 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11553 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17314 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30809 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.29775E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10130.61962 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70035 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22559 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16948 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60157 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.68890E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10899.05587 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65001 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15388 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13000 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41034 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.47599E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7212.13108 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77850 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20294 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21800 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16971 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54118 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.87738E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10802.79843 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69280 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14436 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13856 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38497 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.63918E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7148.82788 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74384 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21240 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16364 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56640 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.79378E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11973.88530 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71127 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14062 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14225 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37500 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.70936E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7880.84302 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82932 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19051 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16586 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50802 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.99992E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11876.37371 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76759 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13030 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15352 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34746 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.92405E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7825.17743 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.02649 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.41236 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.05297 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.66971 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.59117 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.59117 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.29863 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.71335 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.40180 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.42671 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.03363 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.89538 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.89538 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.41542 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.01995 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.50068 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.03990 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.97493 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.81409 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.81409 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.51168 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.59117 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.89538 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.81409 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.59117 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.59117 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 99976.57017 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80036 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.86354 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 33322.19084 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80036 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 18426.87210 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.59117 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.89538 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.89538 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 89833.43138 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80065 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.63163 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 29941.48268 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80065 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 20223.05263 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.89538 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.81409 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.81409 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 103334.65476 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80043 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.93784 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34441.44043 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80043 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 19894.49193 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.81409 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 98602.98 | 336447.35 | 11.26 | 2.83 | 3.23 | 3.40 | 3.56 | 9.67 | 11.00 | 11.60 | 12.15 | 5.6084 | 4.4513 | 2.9886 | 1.2259 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 88698.60 | 302652.18 | 11.32 | 2.85 | 3.24 | 3.41 | 3.58 | 9.71 | 11.06 | 11.65 | 12.22 | 4.9105 | 3.9074 | 2.6264 | 1.0642 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 101887.77 | 347655.50 | 11.25 | 2.83 | 3.22 | 3.40 | 3.56 | 9.66 | 10.99 | 11.58 | 12.14 | 5.8320 | 4.6265 | 3.1059 | 1.2768 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_NORTH_0.25 | N/A | 2.640 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_EAST_0.25 | N/A | 2.640 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | N/A | 2.640 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_WEST_0.25 | N/A | 2.640 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_NORTH_0.25 | N/A | 2.640 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_NORTH_0.25 | N/A | 2.640 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_NORTH_0.25 | N/A | 2.640 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_EAST_0.25 | N/A | 2.640 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_EAST_0.25 | N/A | 2.640 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | N/A | 2.640 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | N/A | 2.640 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | N/A | 2.640 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_WEST_0.25 | N/A | 2.640 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_WEST_0.25 | N/A | 2.640 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_NORTH_0.25 | N/A | 2.640 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_EAST_0.25 | N/A | 2.640 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | N/A | 2.640 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_WEST_0.25 | N/A | 2.640 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.2256835274E-002 | 0.1393188407 | Pass | Pass | 7.7810387306E-002 | 0.2664087706 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.9311702775E-002 | 7.6416762797E-002 | Pass | Pass | 7.1416713368E-003 | 8.4332213954E-002 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.1741851851E-002 | 2.7018365639E-002 | Pass | Pass | 8.2127927766E-002 | 0.3712362828 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.9584432318E-002 | 2.4326120564E-002 | Pass | Pass | 0.5713950056 | 3.3055169976 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.9523080378E-002 | 9.6752313627E-002 | Pass | Pass | 4.9459190306E-002 | 0.2155841852 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.2306114712E-002 | 6.4211811881E-002 | Pass | Pass | 7.2720821035E-003 | 8.4967232619E-002 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.9590275679E-002 | 4.5627568689E-002 | Pass | Pass | 7.0612671765E-003 | 8.3732308146E-002 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.6524154652E-002 | 9.4285394999E-002 | Pass | Pass | 7.1087614343E-003 | 8.4008029506E-002 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1329226536 | 0.1350064661 | Pass | Pass | 6.9448920765E-003 | 8.2751978618E-002 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.5827106136E-002 | 0.1131464810 | Pass | Pass | 6.9439987945E-003 | 8.2417443280E-002 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.6673202458E-002 | 7.8446242253E-002 | Pass | Pass | 7.7761767999E-002 | 0.2655708836 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.3169734910E-002 | 0.1183078144 | Pass | Pass | 7.8188505382E-002 | 0.2675276417 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1270364810 | 0.1673339646 | Pass | Pass | 9.2353447534E-002 | 0.3182807493 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.5832607510E-002 | 0.1515306051 | Pass | Pass | 7.5794215437E-002 | 0.2602116033 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.8463774173E-002 | 6.4741009863E-002 | Pass | Pass | 4.8919002246E-002 | 0.2146858042 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.0397853626E-002 | 0.1165015517 | Pass | Pass | 4.9520474795E-002 | 0.2167474890 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1333316847 | 0.1512688703 | Pass | Pass | 4.9065188994E-002 | 0.2159285068 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.8741070682E-002 | 0.1369963904 | Pass | Pass | 4.7544907224E-002 | 0.2084399409 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3332.23 | 56.51 | 0.00 | 1317.25 | 1498.53 | 6204.53 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.640 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.4644_SHGC_EAST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.640 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.640 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.4644_SHGC_WEST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.640 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.4644_SHGC_EAST_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.4644_SHGC_EAST_0.25 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.4644_SHGC_WEST_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.4644_SHGC_WEST_0.25 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.640 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.4644_SHGC_EAST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.640 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.640 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.4644_SHGC_WEST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.640 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.640 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 177.99 | 2.640 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.640 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.40 | 0.0000 | Y | 9.26 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.39 | 0.0000 | Y | 5.86 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.10 | 0.0000 | Y | 9.17 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.15 | 0.0000 | Y | 5.81 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.35 | 0.0000 | Y | 9.24 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.35 | 0.0000 | Y | 5.85 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.08 | 0.0000 | Y | 9.16 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.10 | 0.0000 | Y | 5.81 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.40 | 0.0000 | Y | 9.26 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.39 | 0.0000 | Y | 5.86 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.10 | 0.0000 | Y | 9.17 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.15 | 0.0000 | Y | 5.82 |
Interior Lighting Total | 7.5763 | 4982.19 | 37746.71 | 280.73 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 41.77 | 41.77 | 3.33 | |
EXTERIOR_LIGHTS_B | 5132.60 | AstronomicalClock | - | 83.77 | 71.17 | 68.57 | |
Exterior Lighting Total | 5557.43 | 71.90 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 99976.57 | 80017.06 | 19959.51 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 89833.43 | 71925.16 | 17908.28 | 0.80 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 103334.65 | 82711.83 | 20622.82 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 98603.0 | 2.83 | 9.67 | N/A | N/A | 11.26 | |
PACU_VAV_MID COOLING COIL | 88698.6 | 2.85 | 9.71 | N/A | N/A | 11.32 | |
PACU_VAV_TOP COOLING COIL | 101887.8 | 2.83 | 9.66 | N/A | N/A | 11.25 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 23305.73 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 22492.62 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 34764.69 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15594.16 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10193.44 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15488.29 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10130.62 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10899.06 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7212.13 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10802.80 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7148.83 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11973.89 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7880.84 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11876.37 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7825.18 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 18426.87 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 20223.05 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 19894.49 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.59 | 12160.16 | 2174.89 | 1.00 | 1.13 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.90 | 10716.04 | 2189.01 | 1.00 | 1.13 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.81 | 12645.00 | 2174.89 | 1.00 | 1.13 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 98602.98 | 2.83 | 9.67 | 11.26 | 5.6084 | 3.23 | 11.00 | 4.4513 | 3.40 | 11.60 | 2.9886 | 3.56 | 12.15 | 1.2259 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 88698.60 | 2.85 | 9.71 | 11.32 | 4.9105 | 3.24 | 11.06 | 3.9074 | 3.41 | 11.65 | 2.6264 | 3.58 | 12.22 | 1.0642 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 101887.77 | 2.83 | 9.66 | 11.25 | 5.8320 | 3.22 | 10.99 | 4.6265 | 3.40 | 11.58 | 3.1059 | 3.56 | 12.14 | 1.2768 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 38880.31 | 38880.31 | 39.53 | 3.231 | 3.231 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00881 | 28.48 | 0.00686 | 0.425 | 0.00 |
CORE_MID | 28603.26 | 28603.26 | 29.08 | 2.375 | 2.375 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 28.48 | 0.00686 | 0.425 | 0.00 |
CORE_TOP | 30918.61 | 30918.61 | 31.44 | 2.590 | 2.590 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00889 | 37.71 | 0.00687 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10407.15 | 10407.15 | 50.19 | 0.872 | 0.872 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00869 | 37.84 | 0.00687 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8982.10 | 8982.10 | 68.43 | 0.752 | 0.752 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00863 | 33.48 | 0.00686 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 11455.61 | 11455.61 | 55.25 | 0.960 | 0.960 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00867 | 38.10 | 0.00687 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10333.70 | 10333.70 | 78.73 | 0.866 | 0.866 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00862 | 36.63 | 0.00687 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8359.93 | 8359.93 | 40.32 | 0.700 | 0.700 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00876 | 37.97 | 0.00687 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7759.07 | 7759.07 | 59.11 | 0.650 | 0.650 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00868 | 33.48 | 0.00686 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9292.87 | 9292.87 | 44.82 | 0.779 | 0.779 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00874 | 38.10 | 0.00687 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8269.91 | 8269.91 | 63.01 | 0.693 | 0.693 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00867 | 36.45 | 0.00687 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8879.12 | 8879.12 | 42.82 | 0.744 | 0.744 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00873 | 37.97 | 0.00687 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8490.48 | 8490.48 | 64.68 | 0.711 | 0.711 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00865 | 32.79 | 0.00686 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9899.54 | 9899.54 | 47.75 | 0.829 | 0.829 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00870 | 37.99 | 0.00687 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9162.67 | 9162.67 | 69.81 | 0.768 | 0.768 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00864 | 36.63 | 0.00687 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 6236.21 | 6236.21 | 6.34 | 0.303 | 0.425 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 0.425 | 0.00 |
CORE_MID | 13680.78 | 13680.78 | 13.91 | 0.668 | 0.668 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 0.425 | 0.00 |
CORE_TOP | 24476.28 | 24476.28 | 24.89 | 1.200 | 1.200 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10950.15 | 10950.15 | 52.81 | 0.538 | 0.538 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 7157.24 | 7157.24 | 54.53 | 0.352 | 0.352 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10876.00 | 10876.00 | 52.46 | 0.535 | 0.535 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 7113.24 | 7113.24 | 54.19 | 0.350 | 0.350 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7660.71 | 7660.71 | 36.95 | 0.376 | 0.376 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 5068.49 | 5068.49 | 38.61 | 0.249 | 0.249 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 7593.30 | 7593.30 | 36.62 | 0.373 | 0.373 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 5024.15 | 5024.15 | 38.28 | 0.247 | 0.247 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8414.14 | 8414.14 | 40.58 | 0.413 | 0.413 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 5537.25 | 5537.25 | 42.18 | 0.272 | 0.272 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 8345.85 | 8345.85 | 40.25 | 0.410 | 0.410 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 5498.26 | 5498.26 | 41.89 | 0.270 | 0.270 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -5.20 | 0.00281 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.59 | 5.59 | 1.67 | 1.67 | 5.5912 | 1.6697 | 5.5912 | 0.2986 | 0.3000 |
PACU_VAV_MID | 4.90 | 4.90 | 2.03 | 2.03 | 4.8954 | 2.0336 | 4.8954 | 0.4154 | 0.3000 |
PACU_VAV_TOP | 5.81 | 5.81 | 2.97 | 2.97 | 5.8141 | 2.9749 | 5.8141 | 0.5117 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 23305.727 | 23305.727 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 23305.73 | 12301.49 | 0.424691 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 6236.21 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 22492.624 | 22492.624 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22492.62 | 19349.34 | 0.668008 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 13680.78 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 34764.689 | 34764.689 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 34764.69 | 34764.69 | 1.200200 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 24476.28 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 15594.159 | 15594.159 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15594.16 | 15594.16 | 0.538365 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00782366 | 43.8785 | 10950.15 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 10193.436 | 10193.436 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10193.44 | 10193.44 | 0.351913 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00782096 | 43.8636 | 7157.24 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 15488.291 | 15488.291 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15488.29 | 15488.29 | 0.534711 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00782233 | 43.8712 | 10876.00 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 10130.620 | 10130.620 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10130.62 | 10130.62 | 0.349745 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00781976 | 43.8570 | 7113.24 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 10899.056 | 10899.056 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10899.06 | 10899.06 | 0.376274 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00781264 | 43.8173 | 7660.71 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 7212.131 | 7212.131 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7212.13 | 7212.13 | 0.248988 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00781964 | 43.8561 | 5068.49 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 10802.798 | 10802.798 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10802.80 | 10802.80 | 0.372951 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00780920 | 43.7983 | 7593.30 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 7148.828 | 7148.828 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7148.83 | 7148.83 | 0.246803 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00781650 | 43.8387 | 5024.15 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 11973.885 | 11973.885 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11973.89 | 11973.89 | 0.413381 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00778352 | 43.6563 | 8414.14 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 7880.843 | 7880.843 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7880.84 | 7880.84 | 0.272075 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00778733 | 43.6774 | 5537.25 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 11876.374 | 11876.374 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11876.37 | 11876.37 | 0.410014 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00778013 | 43.6376 | 8345.85 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 7825.177 | 7825.177 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7825.18 | 7825.18 | 0.270153 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00778469 | 43.6628 | 5498.26 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 99976.570 | 80017.056 | 5.591166 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 93783.76 | 93783.76 | 5.591166 | 27.02 | 15.84 | 0.00837727 | 10.76 | 9.88 | 0.00837727 | 38.10 | 0.00687148 | 18.17 | 21.3760 | 24.00 | 0.00878715 | 41.0076 | 66677.86 | 0.00 | 103089.26 | 75649.03 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 18426.872 | 18426.872 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18426.87 | 18426.87 | 1.677350 | 2.33 | 1.16 | 0.00426474 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 71.2535 | 19.86 | 0.00783787 | 47.1481 | 18798.11 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 89833.431 | 71925.156 | 4.895379 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 84268.92 | 84268.92 | 4.895379 | 27.45 | 15.96 | 0.00834159 | 10.75 | 9.83 | 0.00834159 | 38.10 | 0.00687148 | 18.17 | 24.4142 | 24.00 | 0.00881841 | 41.1513 | 58251.51 | 0.00 | 92630.33 | 67990.79 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 20223.053 | 20223.053 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20223.05 | 20223.05 | 1.468614 | -0.32 | -1.04 | 0.00373983 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 81.3808 | 19.90 | 0.00779501 | 46.7836 | 22978.01 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 103334.655 | 82711.831 | 5.814091 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 96933.84 | 96933.84 | 5.814091 | 26.91 | 15.80 | 0.00837324 | 10.76 | 9.87 | 0.00837324 | 38.10 | 0.00687148 | 18.17 | 20.5564 | 24.00 | 0.00876433 | 40.9023 | 69050.17 | 0.00 | 106551.90 | 78201.73 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 19894.492 | 19894.492 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19894.49 | 19894.49 | 1.744227 | 1.93 | 1.05 | 0.00434317 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 68.5215 | 17.60 | 0.00762709 | 52.8828 | 24572.36 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 23305.727 | 23305.727 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 23305.73 | 12301.49 | 1.0000 | 0.44351838 | 0.424691 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23305.73 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.62 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 6236.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 22492.624 | 22492.624 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 22492.62 | 19349.34 | 1.0000 | 0.69762161 | 0.668008 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22492.62 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 13680.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 34764.689 | 34764.689 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 34764.69 | 34764.69 | 1.0000 | 1.25340690 | 1.200200 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34764.69 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 24476.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 15594.159 | 15594.159 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15594.16 | 15594.16 | 1.0000 | 0.56223217 | 0.538365 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15594.16 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00782366 | 21.00 | 0.00782366 | 43.8785 | 10950.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10193.436 | 10193.436 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10193.44 | 10193.44 | 1.0000 | 0.36751439 | 0.351913 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10193.44 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00782096 | 21.00 | 0.00782096 | 43.8636 | 7157.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 15488.291 | 15488.291 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15488.29 | 15488.29 | 1.0000 | 0.55841520 | 0.534711 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15488.29 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00782233 | 21.00 | 0.00782233 | 43.8712 | 10876.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10130.620 | 10130.620 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10130.62 | 10130.62 | 1.0000 | 0.36524960 | 0.349745 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10130.62 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00781976 | 21.00 | 0.00781976 | 43.8570 | 7113.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10899.056 | 10899.056 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10899.06 | 10899.06 | 1.0000 | 0.39295482 | 0.376274 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10899.06 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00781264 | 21.00 | 0.00781264 | 43.8173 | 7660.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7212.131 | 7212.131 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7212.13 | 7212.13 | 1.0000 | 0.26002634 | 0.248988 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7212.13 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00781964 | 21.00 | 0.00781964 | 43.8561 | 5068.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10802.798 | 10802.798 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10802.80 | 10802.80 | 1.0000 | 0.38948435 | 0.372951 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10802.80 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00780920 | 21.00 | 0.00780920 | 43.7983 | 7593.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7148.828 | 7148.828 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7148.83 | 7148.83 | 1.0000 | 0.25774401 | 0.246803 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7148.83 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00781650 | 21.00 | 0.00781650 | 43.8387 | 5024.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 11973.885 | 11973.885 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11973.89 | 11973.89 | 1.0000 | 0.43170674 | 0.413381 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11973.89 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00778352 | 21.00 | 0.00778352 | 43.6563 | 8414.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7880.843 | 7880.843 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7880.84 | 7880.84 | 1.0000 | 0.28413610 | 0.272075 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7880.84 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00778733 | 21.00 | 0.00778733 | 43.6774 | 5537.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 11876.374 | 11876.374 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11876.37 | 11876.37 | 1.0000 | 0.42819106 | 0.410014 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11876.37 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00778013 | 21.00 | 0.00778013 | 43.6376 | 8345.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7825.177 | 7825.177 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7825.18 | 7825.18 | 1.0000 | 0.28212913 | 0.270153 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7825.18 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00778469 | 21.00 | 0.00778469 | 43.6628 | 5498.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 99976.570 | 80017.056 | 5.591166 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4129 | 1004.8586 | 1.0443 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.591166 | 5.83903168 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 93783.76 | 93783.76 | 0.9381 | 5.83903168 | 5.591166 | 27.02 | 15.84 | 0.00837727 | 48518.4 | 10.76 | 9.88 | 0.00837727 | 31929.8 | -999.0 | -999.00 | -999.00 | -999.00 | 12160.161 | 81623.60 | 38.10 | 0.00687148 | 18.17 | 1.19517000 | 21.3760 | 24.00 | 0.00878715 | 24.00 | 0.00878715 | 41.0076 | 66677.86 | 0.00 | 103089.26 | 75649.03 | 5.60843407 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.47 | 13.12 | 0.00926635 | 36941.3 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18426.872 | 18426.872 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.591166 | 5.83903168 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 18426.87 | 18426.87 | 1.0000 | 1.75170950 | 1.677350 | 2.33 | 1.16 | 0.00426474 | 13027.1 | 12.80 | 10.33 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18426.87 | -5.20 | 0.00280840 | -5.20 | 1.19517000 | 71.2535 | 21.00 | 0.00787455 | 19.86 | 0.00783787 | 47.1481 | 18798.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 89833.431 | 71925.156 | 4.895379 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3466 | 1004.8586 | 1.0443 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.895379 | 5.11239959 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 84268.92 | 84268.92 | 0.9381 | 5.11239959 | 4.895379 | 27.45 | 15.96 | 0.00834159 | 48872.8 | 10.75 | 9.83 | 0.00834159 | 31826.2 | -999.0 | -999.00 | -999.00 | -999.00 | 10716.038 | 73552.88 | 38.10 | 0.00687148 | 18.17 | 1.19517000 | 24.4142 | 24.00 | 0.00881841 | 24.00 | 0.00881841 | 41.1513 | 58251.51 | 0.00 | 92630.33 | 67990.79 | 4.91049845 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.12 | 12.94 | 0.00921732 | 36458.7 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20223.053 | 20223.053 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.895379 | 5.11239959 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 20223.05 | 20223.05 | 1.0000 | 1.53371988 | 1.468614 | -0.32 | -1.04 | 0.00373983 | 9027.4 | 12.80 | 10.33 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20223.05 | -5.20 | 0.00280840 | -5.20 | 1.19517000 | 81.3808 | 21.00 | 0.00781094 | 19.90 | 0.00779501 | 46.7836 | 22978.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 103334.655 | 82711.831 | 5.814091 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4054 | 1004.8586 | 1.0443 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.814091 | 6.07184002 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 96933.84 | 96933.84 | 0.9381 | 6.07184002 | 5.814091 | 26.91 | 15.80 | 0.00837324 | 48402.5 | 10.76 | 9.87 | 0.00837324 | 31919.6 | -999.0 | -999.00 | -999.00 | -999.00 | 12644.999 | 84288.84 | 38.10 | 0.00687148 | 18.17 | 1.19517000 | 20.5564 | 24.00 | 0.00876433 | 24.00 | 0.00876433 | 40.9023 | 69050.17 | 0.00 | 106551.90 | 78201.73 | 5.83204823 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.55 | 13.17 | 0.00927873 | 37052.3 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19894.492 | 19894.492 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.814091 | 6.07184002 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19894.49 | 19894.49 | 1.0000 | 1.82155200 | 1.744227 | 1.93 | 1.05 | 0.00434317 | 12818.0 | 12.80 | 10.33 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19894.49 | -5.20 | 0.00280840 | -5.20 | 1.19517000 | 68.5215 | 17.45 | 0.00768401 | 17.60 | 0.00762709 | 52.8828 | 24572.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.59 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.90 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.81 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2443.17 | 1930.00 | 34.83 |
CORE_MID | 2112.67 | 2781.17 | 68.50 |
CORE_TOP | 2312.17 | 3059.50 | 326.17 |
PERIMETER_TOP_ZN_3 | 3163.17 | 3377.00 | 1219.33 |
PERIMETER_TOP_ZN_2 | 3157.17 | 3066.33 | 982.50 |
PERIMETER_TOP_ZN_1 | 3038.17 | 2563.83 | 762.00 |
PERIMETER_TOP_ZN_4 | 3230.00 | 3187.00 | 1142.17 |
PERIMETER_BOT_ZN_3 | 2549.83 | 3297.00 | 612.00 |
PERIMETER_BOT_ZN_2 | 2725.33 | 2881.00 | 410.17 |
PERIMETER_BOT_ZN_1 | 2635.50 | 2706.83 | 423.50 |
PERIMETER_BOT_ZN_4 | 2724.83 | 2921.33 | 454.33 |
PERIMETER_MID_ZN_3 | 2658.00 | 3191.00 | 643.00 |
PERIMETER_MID_ZN_2 | 2417.17 | 2552.33 | 557.83 |
PERIMETER_MID_ZN_1 | 2801.83 | 2258.17 | 407.17 |
PERIMETER_MID_ZN_4 | 2844.67 | 2971.83 | 656.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4256.00 | 3912.00 | 1570.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.83 | 0.00 | 0.17 |
CORE_MID | 0.00 | 0.50 | 0.00 | 0.17 |
CORE_TOP | 0.00 | 1.17 | 0.00 | 0.67 |
PERIMETER_TOP_ZN_3 | 0.67 | 24.17 | 0.00 | 15.33 |
PERIMETER_TOP_ZN_2 | 1.33 | 63.17 | 0.00 | 56.67 |
PERIMETER_TOP_ZN_1 | 0.50 | 49.17 | 0.00 | 42.00 |
PERIMETER_TOP_ZN_4 | 0.50 | 54.33 | 0.00 | 31.17 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.17 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 34.33 | 0.00 | 33.50 |
PERIMETER_BOT_ZN_1 | 117.83 | 161.17 | 117.83 | 160.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 38.83 | 0.00 | 24.50 |
PERIMETER_MID_ZN_3 | 0.00 | 4.00 | 0.00 | 2.33 |
PERIMETER_MID_ZN_2 | 0.00 | 46.17 | 0.00 | 44.83 |
PERIMETER_MID_ZN_1 | 0.00 | 36.83 | 0.00 | 35.00 |
PERIMETER_MID_ZN_4 | 0.00 | 45.67 | 0.00 | 28.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 119.17 | 336.83 | 117.83 | 297.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.81 | 52.94 | 2698.04 | 1.083 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.81 | 52.94 | 2698.04 | 0.734 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.81 | 52.94 | 2698.04 | 0.716 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.60 | 11.16 | 568.77 | 0.786 | 0.077 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 1.271 | 0.082 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.60 | 11.16 | 568.77 | 1.218 | 0.078 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 1.238 | 0.082 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.60 | 11.16 | 568.77 | 0.709 | 0.041 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 1.116 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.60 | 11.16 | 568.77 | 0.988 | 1.299 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 1.035 | 0.043 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.60 | 11.16 | 568.77 | 0.775 | 0.065 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 1.179 | 0.072 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.60 | 11.16 | 568.77 | 1.208 | 0.065 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 1.177 | 0.068 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.55 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.11 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 17470436.61 | 0.00 | 17470436.61 | 0.00 | 17470436.61 | 13393058.27 | 5279.11 | 121.64 | 3359.25 | 123.78 |
CORE_MID | 11774328.72 | 0.00 | 11774328.72 | 0.00 | 11774328.72 | 13393058.27 | 6068.16 | 26.77 | 2665.07 | 70.00 |
CORE_TOP | 11457774.84 | 0.00 | 11457774.84 | 0.00 | 11457774.84 | 13393058.27 | 6090.50 | 24.21 | 2645.29 | 68.82 |
PERIMETER_TOP_ZN_3 | 2648043.41 | 0.00 | 2648043.41 | 511255.28 | 3159298.69 | 2823374.22 | 4638.84 | 46.48 | 4074.68 | 68.82 |
PERIMETER_TOP_ZN_2 | 2703297.00 | 0.00 | 2703297.00 | 340834.81 | 3044131.80 | 1787429.43 | 4024.07 | 2.62 | 4733.30 | 68.82 |
PERIMETER_TOP_ZN_1 | 4085606.79 | 0.00 | 4085606.79 | 511255.28 | 4596862.07 | 2823374.22 | 4072.13 | 14.88 | 4672.99 | 68.82 |
PERIMETER_TOP_ZN_4 | 2642459.85 | 0.00 | 2642459.85 | 340834.81 | 2983294.66 | 1787312.18 | 4058.03 | 18.01 | 4683.96 | 68.82 |
PERIMETER_BOT_ZN_3 | 2429405.51 | 0.00 | 2429405.51 | 271832.90 | 2701238.41 | 2823374.22 | 5524.77 | 130.97 | 3104.25 | 123.78 |
PERIMETER_BOT_ZN_2 | 2402828.94 | 0.00 | 2402828.94 | 181220.85 | 2584049.78 | 1787429.43 | 4126.92 | 48.52 | 4584.55 | 123.78 |
PERIMETER_BOT_ZN_1 | 3358156.44 | 0.00 | 3358156.44 | 4464493.17 | 7822649.61 | 2823374.22 | 4462.26 | 96.54 | 4201.20 | 123.78 |
PERIMETER_BOT_ZN_4 | 2237860.70 | 0.00 | 2237860.70 | 181220.85 | 2419081.54 | 1787312.18 | 4263.64 | 64.34 | 4432.02 | 123.78 |
PERIMETER_MID_ZN_3 | 2617347.92 | 0.00 | 2617347.92 | 425581.69 | 3042929.60 | 2823374.22 | 4648.13 | 50.46 | 4061.41 | 70.00 |
PERIMETER_MID_ZN_2 | 2665808.32 | 0.00 | 2665808.32 | 283719.42 | 2949527.74 | 1787429.43 | 3982.79 | 4.15 | 4773.06 | 979.00 |
PERIMETER_MID_ZN_1 | 4054546.67 | 0.00 | 4054546.67 | 425581.69 | 4480128.36 | 2823374.22 | 4257.47 | 246.11 | 4256.41 | 70.00 |
PERIMETER_MID_ZN_4 | 2515464.53 | 0.00 | 2515464.53 | 283719.42 | 2799183.94 | 1787312.18 | 3997.72 | 18.12 | 4744.17 | 70.00 |
Total Facility | 75063366.25 | 0.00 | 75063366.25 | 8221550.15 | 83284916.39 | 67843644.98 | 6284.92 | 637.95 | 4936.66 | 1069.46 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7969 | 0.0000 | 0.7969 | 0.0000 | 0.7969 | 0.4247 | 2585.44 | 121.64 | 3235.91 |
CORE_MID | 0.5399 | 0.0000 | 0.5399 | 0.0000 | 0.5399 | 0.4247 | 3321.16 | 26.77 | 2595.07 |
CORE_TOP | 0.5273 | 0.0000 | 0.5273 | 0.0000 | 0.5273 | 0.4247 | 3328.29 | 24.21 | 2590.50 |
PERIMETER_TOP_ZN_3 | 0.1221 | 0.0000 | 0.1221 | 0.0120 | 0.1341 | 0.0895 | 1876.63 | 46.48 | 4019.89 |
PERIMETER_TOP_ZN_2 | 0.1249 | 0.0000 | 0.1249 | 0.0080 | 0.1329 | 0.0567 | 1261.87 | 2.62 | 4678.51 |
PERIMETER_TOP_ZN_1 | 0.1891 | 0.0000 | 0.1891 | 0.0120 | 0.2012 | 0.0895 | 1309.92 | 14.88 | 4618.20 |
PERIMETER_TOP_ZN_4 | 0.1218 | 0.0000 | 0.1218 | 0.0080 | 0.1298 | 0.0567 | 1295.82 | 18.01 | 4629.17 |
PERIMETER_BOT_ZN_3 | 0.1101 | 0.0000 | 0.1101 | 0.0064 | 0.1165 | 0.0895 | 2831.05 | 130.97 | 2980.97 |
PERIMETER_BOT_ZN_2 | 0.1096 | 0.0000 | 0.1096 | 0.0043 | 0.1139 | 0.0567 | 1433.31 | 48.41 | 4461.27 |
PERIMETER_BOT_ZN_1 | 0.1535 | 0.0000 | 0.1535 | 0.2024 | 0.3558 | 0.0895 | 1768.53 | 96.54 | 4077.93 |
PERIMETER_BOT_ZN_4 | 0.1017 | 0.0000 | 0.1017 | 0.0043 | 0.1060 | 0.0567 | 1570.42 | 64.34 | 4308.24 |
PERIMETER_MID_ZN_3 | 0.1203 | 0.0000 | 0.1203 | 0.0100 | 0.1304 | 0.0895 | 1901.13 | 50.46 | 3991.41 |
PERIMETER_MID_ZN_2 | 0.1158 | 0.0000 | 0.1158 | 0.0071 | 0.1229 | 0.0567 | 1235.29 | 3.98 | 3794.73 |
PERIMETER_MID_ZN_1 | 0.1875 | 0.0000 | 0.1875 | 0.0100 | 0.1975 | 0.0895 | 1510.47 | 246.11 | 4186.41 |
PERIMETER_MID_ZN_4 | 0.1157 | 0.0000 | 0.1157 | 0.0067 | 0.1224 | 0.0567 | 1250.72 | 18.12 | 4674.17 |
Total Facility | 3.4362 | 0.0000 | 3.4362 | 0.2913 | 3.7275 | 2.1513 | 3501.02 | 637.84 | 4790.23 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 30427109.29 | 0.00 | 30427109.29 | 22614548.33 | 3961.49 | 3.23 | 4795.28 | 123.78 |
PACU_VAV_MID | 25768840.60 | 0.00 | 25768840.60 | 22614548.33 | 4002.09 | 1.35 | 4756.56 | 70.00 |
PACU_VAV_TOP | 25670326.54 | 0.00 | 25670326.54 | 22614548.33 | 4035.64 | 1.14 | 4723.22 | 68.82 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.3871 | 0.0000 | 1.3871 | 0.7171 | 1267.82 | 3.23 | 4671.95 |
PACU_VAV_MID | 1.1847 | 0.0000 | 1.1847 | 0.7171 | 1255.09 | 1.35 | 4686.56 |
PACU_VAV_TOP | 1.1835 | 0.0000 | 1.1835 | 0.7171 | 1273.43 | 1.14 | 4668.42 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.06 | 3116.70 | 0.00 | 0.00 | 0.00 | 1762.39 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.12 | 2852.23 | 0.00 | 0.00 | 0.00 | 1995.14 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.06 | 2845.28 | 0.00 | 0.00 | 0.00 | 2002.26 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.2618 | 0.0000 | 0.0000 | 0.0000 | 0.8376 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 1.9195 | 0.0000 | 0.0000 | 0.0000 | 0.8524 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 1.9247 | 0.0000 | 0.0000 | 0.0000 | 0.8444 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 824 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1603.04 | 15539.06 | 16-JUL-17:30 | 181276.11 | 20-JUL-15:10 |
Electricity:Building | 1042.77 | 15341.49 | 01-JAN-08:40 | 74391.06 | 13-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 310.83 | 4652.71 | 01-JAN-00:10 | 24063.48 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1042.77 | 15341.49 | 01-JAN-08:40 | 74391.06 | 13-OCT-07:10 |
InteriorLights:Electricity | 280.73 | 1316.11 | 01-JAN-08:40 | 28079.40 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 280.73 | 1316.11 | 01-JAN-08:40 | 28079.40 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity | 280.73 | 1316.11 | 01-JAN-08:40 | 28079.40 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 280.73 | 1316.11 | 01-JAN-08:40 | 28079.40 | 22-NOV-17:00 |
Electricity:Zone:CORE_MID | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 35.95 | 541.99 | 01-JAN-08:30 | 2674.44 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.26 | 40.03 | 01-JAN-08:30 | 1168.55 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.26 | 40.03 | 01-JAN-08:30 | 1168.55 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 22.76 | 343.10 | 01-JAN-08:10 | 1693.08 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.86 | 25.34 | 01-JAN-08:10 | 739.79 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.86 | 25.34 | 01-JAN-08:10 | 739.79 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 35.86 | 541.99 | 01-JAN-08:00 | 2674.43 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.17 | 40.03 | 01-JAN-08:00 | 1168.55 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.17 | 40.03 | 01-JAN-08:00 | 1168.55 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 22.71 | 343.10 | 01-JAN-08:40 | 1693.03 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.82 | 25.34 | 01-JAN-08:40 | 739.74 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.82 | 25.34 | 01-JAN-08:40 | 739.74 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 35.93 | 541.99 | 01-JAN-08:30 | 2674.44 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.24 | 40.03 | 01-JAN-08:30 | 1168.55 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.24 | 40.03 | 01-JAN-08:30 | 1168.55 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 22.75 | 343.10 | 01-JAN-08:00 | 1693.08 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.85 | 25.34 | 01-JAN-08:00 | 739.79 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.85 | 25.34 | 01-JAN-08:00 | 739.79 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 35.85 | 541.99 | 01-JAN-08:00 | 2674.43 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.16 | 40.03 | 01-JAN-08:00 | 1168.55 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.16 | 40.03 | 01-JAN-08:00 | 1168.55 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 22.70 | 343.10 | 01-JAN-08:30 | 1693.03 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.81 | 25.34 | 01-JAN-08:30 | 739.74 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.81 | 25.34 | 01-JAN-08:30 | 739.74 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 35.95 | 541.99 | 01-JAN-08:30 | 2674.44 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.26 | 40.03 | 01-JAN-08:30 | 1168.55 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.26 | 40.03 | 01-JAN-08:30 | 1168.55 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 22.76 | 343.10 | 01-JAN-08:10 | 1693.08 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.86 | 25.34 | 01-JAN-08:10 | 739.79 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.86 | 25.34 | 01-JAN-08:10 | 739.79 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 35.86 | 541.99 | 01-JAN-08:00 | 2674.43 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.17 | 40.03 | 01-JAN-08:00 | 1168.55 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.17 | 40.03 | 01-JAN-08:00 | 1168.55 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 22.71 | 343.10 | 01-JAN-08:40 | 1693.03 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.82 | 25.34 | 01-JAN-08:40 | 739.74 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.82 | 25.34 | 01-JAN-08:40 | 739.74 | 22-NOV-17:00 |
InteriorEquipment:Electricity | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 247.34 | 4344.73 | 01-JAN-00:10 | 18520.31 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 488.35 | 197.13 | 01-JAN-00:10 | 113817.03 | 20-JUL-15:10 |
ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 926.57 | 11-DEC-17:00 |
Transformer:ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 926.57 | 11-DEC-17:00 |
ElectricityPurchased:Facility | 1603.04 | 15539.06 | 06-AUG-17:30 | 181276.11 | 20-JUL-15:10 |
ElectricityPurchased:Plant | 1603.04 | 15539.06 | 06-AUG-17:30 | 181276.11 | 20-JUL-15:10 |
Cogeneration:ElectricityPurchased | 1603.04 | 15539.06 | 06-AUG-17:30 | 181276.11 | 20-JUL-15:10 |
General:Cogeneration:ElectricityPurchased | 1603.04 | 15539.06 | 06-AUG-17:30 | 181276.11 | 20-JUL-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1603.04 | 15539.06 | 06-AUG-17:30 | 181276.11 | 20-JUL-15:10 |
ElectricityNet:Plant | 1603.04 | 15539.06 | 06-AUG-17:30 | 181276.11 | 20-JUL-15:10 |
Cogeneration:ElectricityNet | 1603.04 | 15539.06 | 06-AUG-17:30 | 181276.11 | 20-JUL-15:10 |
General:Cogeneration:ElectricityNet | 1603.04 | 15539.06 | 06-AUG-17:30 | 181276.11 | 20-JUL-15:10 |
Heating:Electricity | 30.76 | 0.00 | 01-JAN-00:10 | 86722.52 | 27-DEC-07:10 |
General:Heating:Electricity | 30.76 | 0.00 | 01-JAN-00:10 | 86722.52 | 27-DEC-07:10 |
Fans:Electricity | 130.31 | 0.00 | 01-JAN-00:10 | 35506.99 | 20-JUL-15:00 |
General:Fans:Electricity | 130.31 | 0.00 | 01-JAN-00:10 | 35506.99 | 20-JUL-15:00 |
ExteriorLights:Electricity | 71.90 | 0.00 | 01-JAN-07:20 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 71.90 | 0.00 | 01-JAN-07:20 | 5557.43 | 01-JAN-06:10 |
Cooling:Electricity | 314.31 | 0.00 | 01-JAN-00:10 | 77389.61 | 20-JUL-15:10 |
General:Cooling:Electricity | 314.31 | 0.00 | 01-JAN-00:10 | 77389.61 | 20-JUL-15:10 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-08:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-08:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-08:10 |
WIRED_LTG_ELECTRICITY | 7.89 | 0.00 | 01-JAN-00:10 | 789.03 | 22-NOV-17:10 |
WIRED_INT_EQUIP | 641.94 | 12061.80 | 01-JAN-00:10 | 36271.65 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 118.50 | 1156.00 | 06-JAN-17:10 | 53689.64 | 27-DEC-07:30 |
NaturalGas:HVAC | 19.05 | 0.00 | 01-JAN-00:10 | 46154.01 | 27-DEC-07:20 |
Heating:NaturalGas | 19.05 | 0.00 | 01-JAN-00:10 | 46154.01 | 27-DEC-07:20 |
General:Heating:NaturalGas | 19.05 | 0.00 | 01-JAN-00:10 | 46154.01 | 27-DEC-07:20 |
NaturalGas:Plant | 99.44 | 1156.00 | 06-JAN-07:10 | 9222.10 | 27-JAN-12:10 |
WaterSystems:NaturalGas | 99.44 | 1156.00 | 06-JAN-07:10 | 9222.10 | 27-JAN-12:10 |
Water Heater:WaterSystems:NaturalGas | 99.44 | 1156.00 | 06-JAN-07:10 | 9222.10 | 27-JAN-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2594.64 | 0.00 | 01-JAN-00:10 | 443619.11 | 20-JUL-15:00 |
EnergyTransfer:Building | 1325.54 | 0.00 | 01-JAN-00:10 | 169343.32 | 03-JUL-14:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 270.16 | 0.00 | 01-JAN-00:10 | 27973.29 | 05-SEP-08:00 |
Heating:EnergyTransfer | 30.59 | 0.00 | 01-JAN-00:10 | 77718.90 | 27-DEC-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 30.59 | 0.00 | 01-JAN-00:10 | 77718.90 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1294.95 | 0.00 | 01-JAN-00:10 | 169343.32 | 03-JUL-14:30 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 270.16 | 0.00 | 01-JAN-00:10 | 27973.29 | 05-SEP-08:00 |
General:Cooling:EnergyTransfer | 1294.95 | 0.00 | 01-JAN-00:10 | 169343.32 | 03-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 270.16 | 0.00 | 01-JAN-00:10 | 27973.29 | 05-SEP-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 58.43 | 0.00 | 01-JAN-00:10 | 12123.50 | 03-JUL-13:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 8.68 | 0.00 | 01-JAN-00:10 | 8255.15 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 8.68 | 0.00 | 01-JAN-00:10 | 8255.15 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 49.75 | 0.00 | 01-JAN-00:10 | 12123.50 | 03-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 49.75 | 0.00 | 01-JAN-00:10 | 12123.50 | 03-JUL-13:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 29.92 | 0.00 | 01-JAN-00:10 | 5711.82 | 03-JUL-11:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 3.63 | 0.00 | 01-JAN-00:10 | 2740.23 | 04-DEC-11:40 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 3.63 | 0.00 | 01-JAN-00:10 | 2740.23 | 04-DEC-11:40 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 26.29 | 0.00 | 01-JAN-00:10 | 5711.82 | 03-JUL-11:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 26.29 | 0.00 | 01-JAN-00:10 | 5711.82 | 03-JUL-11:00 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 33.59 | 0.00 | 01-JAN-00:10 | 5720.05 | 19-JUN-12:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 1.62 | 0.00 | 01-JAN-00:10 | 2750.60 | 27-DEC-08:30 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 1.62 | 0.00 | 01-JAN-00:10 | 2750.60 | 27-DEC-08:30 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 31.97 | 0.00 | 01-JAN-00:10 | 5720.05 | 19-JUN-12:20 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 31.97 | 0.00 | 01-JAN-00:10 | 5720.05 | 19-JUN-12:20 |
EnergyTransfer:Zone:CORE_MID | 179.87 | 0.00 | 01-JAN-00:10 | 19447.62 | 19-JUN-08:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 1743.33 | 17-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 1743.33 | 17-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 179.86 | 0.00 | 01-JAN-00:10 | 19447.62 | 19-JUN-08:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 179.86 | 0.00 | 01-JAN-00:10 | 19447.62 | 19-JUN-08:00 |
EnergyTransfer:Zone:CORE_TOP | 177.36 | 0.00 | 01-JAN-00:10 | 21679.11 | 03-JUL-13:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.52 | 0.00 | 01-JAN-00:10 | 13357.75 | 04-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.52 | 0.00 | 01-JAN-00:10 | 13357.75 | 04-DEC-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 176.83 | 0.00 | 01-JAN-00:10 | 21679.11 | 03-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 176.83 | 0.00 | 01-JAN-00:10 | 21679.11 | 03-JUL-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 46.06 | 0.00 | 01-JAN-00:10 | 7963.64 | 03-JUL-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 3.01 | 0.00 | 01-JAN-00:10 | 7553.61 | 04-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 3.01 | 0.00 | 01-JAN-00:10 | 7553.61 | 04-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 43.05 | 0.00 | 01-JAN-00:10 | 7963.64 | 03-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 43.05 | 0.00 | 01-JAN-00:10 | 7963.64 | 03-JUL-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 43.98 | 0.00 | 01-JAN-00:10 | 8211.20 | 03-JUL-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.33 | 0.00 | 01-JAN-00:10 | 5022.02 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.33 | 0.00 | 01-JAN-00:10 | 5022.02 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 42.65 | 0.00 | 01-JAN-00:10 | 8211.20 | 03-JUL-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 42.65 | 0.00 | 01-JAN-00:10 | 8211.20 | 03-JUL-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 65.83 | 0.00 | 01-JAN-00:10 | 11565.33 | 03-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.58 | 0.00 | 01-JAN-00:10 | 7214.18 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.58 | 0.00 | 01-JAN-00:10 | 7214.18 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 64.25 | 0.00 | 01-JAN-00:10 | 11565.33 | 03-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 64.25 | 0.00 | 01-JAN-00:10 | 11565.33 | 03-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 44.59 | 0.00 | 01-JAN-00:10 | 9199.53 | 15-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.73 | 0.00 | 01-JAN-00:10 | 4859.77 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.73 | 0.00 | 01-JAN-00:10 | 4859.77 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 42.86 | 0.00 | 01-JAN-00:10 | 9199.53 | 15-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 42.86 | 0.00 | 01-JAN-00:10 | 9199.53 | 15-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 40.15 | 0.00 | 01-JAN-00:10 | 6838.38 | 03-JUL-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.40 | 0.00 | 01-JAN-00:10 | 2972.48 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.40 | 0.00 | 01-JAN-00:10 | 2972.48 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 39.75 | 0.00 | 01-JAN-00:10 | 6838.38 | 03-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 39.75 | 0.00 | 01-JAN-00:10 | 6838.38 | 03-JUL-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 39.97 | 0.00 | 01-JAN-00:10 | 7218.72 | 03-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.12 | 0.00 | 01-JAN-00:10 | 2032.18 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.12 | 0.00 | 01-JAN-00:10 | 2032.18 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 39.85 | 0.00 | 01-JAN-00:10 | 7218.72 | 03-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 39.85 | 0.00 | 01-JAN-00:10 | 7218.72 | 03-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 64.71 | 0.00 | 01-JAN-00:10 | 12050.27 | 03-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 6.47 | 0.00 | 01-JAN-00:10 | 10682.87 | 27-DEC-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 6.47 | 0.00 | 01-JAN-00:10 | 10682.87 | 27-DEC-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 58.24 | 0.00 | 01-JAN-00:10 | 12050.27 | 03-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 58.24 | 0.00 | 01-JAN-00:10 | 12050.27 | 03-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 39.19 | 0.00 | 01-JAN-00:10 | 7586.14 | 07-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.15 | 0.00 | 01-JAN-00:10 | 2002.73 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.15 | 0.00 | 01-JAN-00:10 | 2002.73 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 39.05 | 0.00 | 01-JAN-00:10 | 7586.14 | 07-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 39.05 | 0.00 | 01-JAN-00:10 | 7586.14 | 07-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 43.41 | 0.00 | 01-JAN-00:10 | 7134.00 | 03-JUL-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.54 | 0.00 | 01-JAN-00:10 | 4134.90 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.54 | 0.00 | 01-JAN-00:10 | 4134.90 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 42.87 | 0.00 | 01-JAN-00:10 | 7134.00 | 03-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 42.87 | 0.00 | 01-JAN-00:10 | 7134.00 | 03-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 41.98 | 0.00 | 01-JAN-00:10 | 7750.98 | 03-JUL-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.26 | 0.00 | 01-JAN-00:10 | 2918.93 | 27-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.26 | 0.00 | 01-JAN-00:10 | 2918.93 | 27-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 41.72 | 0.00 | 01-JAN-00:10 | 7750.98 | 03-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 41.72 | 0.00 | 01-JAN-00:10 | 7750.98 | 03-JUL-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 64.07 | 0.00 | 01-JAN-00:10 | 10231.62 | 03-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.24 | 0.00 | 01-JAN-00:10 | 3958.85 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.24 | 0.00 | 01-JAN-00:10 | 3958.85 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 63.83 | 0.00 | 01-JAN-00:10 | 10231.62 | 03-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 63.83 | 0.00 | 01-JAN-00:10 | 10231.62 | 03-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 42.26 | 0.00 | 01-JAN-00:10 | 8434.09 | 15-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.32 | 0.00 | 01-JAN-00:10 | 2840.16 | 27-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.32 | 0.00 | 01-JAN-00:10 | 2840.16 | 27-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 41.94 | 0.00 | 01-JAN-00:10 | 8434.09 | 15-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 41.94 | 0.00 | 01-JAN-00:10 | 8434.09 | 15-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 42.69 | 0.00 | 01-JAN-00:10 | 5648.28 | 26-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 42.69 | 0.00 | 01-JAN-00:10 | 5648.28 | 26-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 42.69 | 0.00 | 01-JAN-00:10 | 5648.28 | 26-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 42.69 | 0.00 | 01-JAN-00:10 | 5648.28 | 26-JAN-12:10 |
EnergyTransfer:HVAC | 1226.42 | 0.00 | 01-JAN-00:10 | 344061.97 | 20-JUL-15:00 |
HeatingCoils:EnergyTransfer | 46.00 | 0.00 | 01-JAN-00:10 | 122889.97 | 27-DEC-07:10 |
CoolingCoils:EnergyTransfer | 1180.41 | 0.00 | 01-JAN-00:10 | 344061.97 | 20-JUL-15:00 |
EnergyTransfer:Plant | 42.69 | 0.00 | 01-JAN-00:10 | 5648.28 | 26-JAN-12:10 |
WaterSystems:EnergyTransfer | 42.69 | 0.00 | 01-JAN-00:10 | 5648.28 | 26-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 42.69 | 0.00 | 01-JAN-00:10 | 5648.28 | 26-JAN-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -270.161 | 0.000 | 0.000 | 32.710 | 63.485 | 247.342 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -73.377 |
CORE_MID | 0.000 | 0.000 | 0.004 | -179.864 | 0.000 | 0.000 | 33.154 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -43.379 |
CORE_TOP | 0.000 | 0.000 | 0.524 | -176.831 | 0.000 | 0.000 | 33.791 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -47.569 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 3.008 | -43.052 | 0.000 | 0.000 | 7.314 | 9.260 | 26.688 | 17.398 | 0.000 | 0.489 | 5.670 | 0.000 | -23.454 | 0.000 | -3.321 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 1.333 | -42.648 | 0.000 | 0.000 | 4.548 | 5.860 | 16.895 | 34.816 | 0.000 | 0.321 | 0.001 | 0.000 | -14.602 | 0.000 | -2.289 | -4.234 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 1.577 | -64.253 | 0.000 | 0.000 | 7.084 | 9.171 | 26.688 | 59.474 | 0.000 | 0.480 | 0.002 | 0.000 | -22.453 | 0.000 | -3.612 | -14.156 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 1.728 | -42.859 | 0.000 | 0.000 | 4.622 | 5.815 | 16.895 | 35.218 | 0.000 | 0.314 | 0.001 | 0.000 | -15.643 | 0.000 | -2.307 | -3.782 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.399 | -39.748 | 0.000 | 0.000 | 7.262 | 9.244 | 26.688 | 17.687 | 0.000 | 0.286 | 4.715 | 0.000 | -24.654 | 0.000 | -1.879 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.116 | -39.854 | 0.000 | 0.000 | 4.487 | 5.853 | 16.895 | 34.925 | 0.000 | 0.176 | 0.000 | 0.000 | -15.725 | 0.000 | -1.331 | -5.542 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 6.470 | -58.240 | 0.000 | 0.000 | 7.155 | 9.163 | 26.688 | 60.004 | 0.000 | 7.843 | 0.001 | 0.000 | -24.088 | 0.000 | -25.824 | -9.172 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.146 | -39.046 | 0.000 | 0.000 | 4.547 | 5.806 | 16.895 | 35.398 | 0.000 | 0.170 | 0.000 | 0.000 | -16.874 | 0.000 | -1.341 | -5.700 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.540 | -42.874 | 0.000 | 0.000 | 7.209 | 9.260 | 26.688 | 17.272 | 0.000 | 0.418 | 9.637 | 0.000 | -25.155 | 0.000 | -2.994 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.261 | -41.719 | 0.000 | 0.000 | 3.325 | 5.860 | 16.895 | 34.671 | 0.000 | 0.274 | 0.002 | 0.000 | -15.541 | 0.000 | -2.049 | -1.976 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.238 | -63.833 | 0.000 | 0.000 | 7.002 | 9.171 | 26.688 | 59.270 | 0.000 | 0.405 | 0.003 | 0.000 | -23.901 | 0.000 | -3.227 | -11.812 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.316 | -41.944 | 0.000 | 0.000 | 4.556 | 5.815 | 16.895 | 35.139 | 0.000 | 0.263 | 0.000 | 0.000 | -16.705 | 0.000 | -2.070 | -2.265 |
TOPFLOOR_PLENUM | 8.679 | -49.750 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.585 | 45.610 | 0.000 | 0.000 | 0.000 | -5.123 | -0.001 |
MIDFLOOR_PLENUM | 3.632 | -26.290 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.638 | 27.307 | 0.000 | 0.000 | 0.000 | -5.287 | -0.000 |
FIRSTFLOOR_PLENUM | 1.615 | -31.973 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.497 | 34.168 | 0.000 | 0.000 | 0.000 | -4.307 | 0.000 |
Total Facility | 13.926 | -108.013 | 16.661 | -1186.927 | 0.000 | 0.000 | 168.766 | 280.733 | 762.041 | 441.270 | 0.000 | 13.158 | 127.118 | 0.000 | -238.795 | 0.000 | -66.962 | -222.966 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 14-AUG-04:02 | 0.00 | 0.00 | 0.00 | -43791.60 | 0.00 | 0.00 | 0.00 | 615.87 | 5138.45 | 0.00 | 0.00 | 0.00 | 38037.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-SEP-04:02 | 0.00 | 0.00 | 0.00 | -33477.83 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 29687.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 14-AUG-04:02 | 0.00 | 0.00 | 0.00 | -35330.35 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 31539.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 02-JUL-15:42 | 0.00 | 0.00 | 0.00 | -12668.60 | 0.00 | 0.00 | 25.66 | 40.03 | 501.96 | 2971.74 | 0.00 | 373.49 | 8755.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 21-MAY-10:02 | 0.00 | 0.00 | 0.00 | -11586.90 | 0.00 | 0.00 | 15.42 | 25.34 | 317.77 | 4960.16 | 0.00 | 0.60 | 6267.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-OCT-13:02 | 0.00 | 0.00 | 0.00 | -15906.55 | 0.00 | 0.00 | 22.38 | 40.03 | 501.96 | 10258.33 | 0.00 | 36.12 | 5047.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 16-APR-15:42 | 0.00 | 0.00 | 0.00 | -13699.14 | 0.00 | 0.00 | 14.30 | 25.34 | 317.76 | 8508.06 | 0.00 | 19.90 | 4813.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 07-AUG-06:03 | 0.00 | 0.00 | 0.00 | -8052.69 | 0.00 | 0.00 | 144.48 | 240.13 | 669.29 | 301.62 | 0.00 | 1.79 | 6695.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUL-09:32 | 0.00 | 0.00 | 0.00 | -10282.11 | 0.00 | 0.00 | 15.75 | 25.34 | 317.77 | 5909.86 | 0.00 | 0.00 | 4013.79 | 0.00 | -0.00 | 0.00 | -0.39 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-OCT-13:02 | 0.00 | 0.00 | 0.00 | -12719.11 | 0.00 | 0.00 | 23.95 | 40.03 | 501.96 | 10364.60 | 0.00 | 21.32 | 1767.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 17-SEP-16:42 | 0.00 | 0.00 | 0.00 | -11030.15 | 0.00 | 0.00 | 14.95 | 25.34 | 317.76 | 5926.68 | 0.00 | 30.07 | 4715.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-JUN-17:01 | 0.00 | 0.00 | 0.00 | -10726.65 | 0.00 | 0.00 | 0.00 | 40.03 | 501.96 | 2652.97 | 0.00 | 0.00 | 7531.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-08:52 | 0.00 | 0.00 | 0.00 | -11525.01 | 0.00 | 0.00 | 14.72 | 25.34 | 317.77 | 6838.87 | 0.00 | 0.00 | 4340.85 | 0.00 | -0.00 | 0.00 | -12.54 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-13:52 | 0.00 | 0.00 | 0.00 | -12893.76 | 0.00 | 0.00 | 25.23 | 40.03 | 501.96 | 5899.40 | 0.00 | 50.22 | 6376.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 30-APR-16:41 | 0.00 | 0.00 | 0.00 | -12563.97 | 0.00 | 0.00 | 14.01 | 25.34 | 317.76 | 7906.77 | 0.00 | 28.02 | 4272.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 03-JUL-13:10 | 0.00 | -12123.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.94 | 12058.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 03-JUL-11:00 | 0.00 | -5712.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.21 | 5645.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 03-JUL-12:09 | 0.00 | -7246.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 | 7238.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 19-JUN-04:02 | 0.00 | 8927.24 | 0.00 | -198067.02 | 0.00 | 0.00 | 0.00 | 3119.77 | 18045.99 | 0.00 | 0.00 | 0.00 | 175950.81 | 0.00 | -6931.85 | 0.00 | -1044.93 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 27-DEC-07:01 | 0.00 | 0.00 | 16611.38 | 0.00 | 0.00 | 0.00 | 885.28 | 1847.70 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22519.22 |
CORE_TOP | 04-DEC-06:01 | 0.00 | 0.00 | 28996.09 | 0.00 | 0.00 | 0.00 | 490.86 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -33277.69 |
PERIMETER_TOP_ZN_3 | 04-DEC-05:02 | 0.00 | 0.00 | 10715.25 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2295.71 | 0.00 | -38.33 | -9180.34 |
PERIMETER_TOP_ZN_2 | 04-DEC-05:02 | 0.00 | 0.00 | 9170.01 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1524.84 | 0.00 | -25.85 | -8125.19 |
PERIMETER_TOP_ZN_1 | 26-DEC-05:02 | 0.00 | 0.00 | 11559.72 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2230.38 | 0.00 | -648.86 | -9479.60 |
PERIMETER_TOP_ZN_4 | 26-DEC-05:02 | 0.00 | 0.00 | 9470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1457.77 | 0.00 | -430.55 | -8088.46 |
PERIMETER_BOT_ZN_3 | 02-MAR-06:01 | 0.00 | 0.00 | 7542.26 | 0.00 | 0.00 | 0.00 | 100.53 | 129.83 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3085.92 | 0.00 | -59.31 | -5296.68 |
PERIMETER_BOT_ZN_2 | 02-MAR-06:01 | 0.00 | 0.00 | 5868.49 | 0.00 | 0.00 | 0.00 | 62.90 | 82.19 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2086.91 | 0.00 | -40.22 | -4310.14 |
PERIMETER_BOT_ZN_1 | 27-DEC-07:10 | 0.00 | 0.00 | 11231.53 | 0.00 | 0.00 | 0.00 | 193.30 | 389.51 | 669.28 | 0.00 | 0.00 | 0.00 | 11126.20 | 0.00 | -3163.05 | 0.00 | -20446.77 | 0.00 |
PERIMETER_BOT_ZN_4 | 27-DEC-06:01 | 0.00 | 0.00 | 5641.97 | 0.00 | 0.00 | 0.00 | 63.49 | 82.19 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2039.89 | 0.00 | -45.60 | -4125.85 |
PERIMETER_MID_ZN_3 | 27-DEC-06:01 | 0.00 | 0.00 | 8356.14 | 0.00 | 0.00 | 0.00 | 104.27 | 129.83 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2947.68 | 0.00 | -102.41 | -6209.44 |
PERIMETER_MID_ZN_2 | 27-DEC-06:01 | 0.00 | 0.00 | 6757.46 | 0.00 | 0.00 | 0.00 | 66.44 | 82.19 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1997.69 | 0.00 | -68.22 | -5263.86 |
PERIMETER_MID_ZN_1 | 27-DEC-06:01 | 0.00 | 0.00 | 9247.11 | 0.00 | 0.00 | 0.00 | 103.90 | 129.83 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3029.63 | 0.00 | -103.14 | -7017.36 |
PERIMETER_MID_ZN_4 | 27-DEC-06:01 | 0.00 | 0.00 | 6596.17 | 0.00 | 0.00 | 0.00 | 66.30 | 82.19 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1957.72 | 0.00 | -68.35 | -5142.27 |
TOPFLOOR_PLENUM | 27-DEC-07:02 | 10715.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -161.94 | -10553.92 |
MIDFLOOR_PLENUM | 08-OCT-15:43 | 4234.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.04 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4309.21 |
FIRSTFLOOR_PLENUM | 07-NOV-06:02 | 6020.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -159.66 | -5860.80 |
Total Facility | 04-DEC-07:01 | 5130.74 | 6162.04 | 133341.44 | -6162.04 | 0.00 | 0.00 | 4491.43 | 8293.24 | 21853.28 | 8966.35 | 0.00 | 0.00 | 0.00 | 0.00 | -11730.20 | 0.00 | -25089.02 | -145257.24 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.0530 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.5912 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.4267 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.8954 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.0399 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.8141 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.0265 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4124 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.7134 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4018 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.0200 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5007 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2313 | 3.2313 | 0.8046 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3747 | 2.3747 | 0.7765 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5903 | 2.5903 | 0.8108 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8718 | 0.8718 | 0.1744 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7525 | 0.7525 | 0.1505 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9597 | 0.9597 | 0.1919 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8657 | 0.8657 | 0.1731 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7003 | 0.7003 | 0.1695 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6500 | 0.6500 | 0.1300 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7785 | 0.7785 | 0.1697 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6928 | 0.6928 | 0.1386 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7438 | 0.7438 | 0.1636 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7113 | 0.7113 | 0.1423 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8293 | 0.8293 | 0.1659 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7676 | 0.7676 | 0.1535 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.0530 | 5.5912 | 6.0530 | 1.4124 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.4267 | 4.8954 | 5.4267 | 1.4018 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.0399 | 5.8141 | 6.0399 | 1.5007 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6157 | 1.6157 | 0.8046 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1873 | 1.1873 | 0.7765 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2951 | 1.2951 | 0.8108 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4359 | 0.4359 | 0.1744 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3762 | 0.3762 | 0.1505 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4798 | 0.4798 | 0.1919 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4328 | 0.4328 | 0.1731 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3502 | 0.3502 | 0.1695 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3250 | 0.3250 | 0.1300 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3893 | 0.3893 | 0.1697 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3464 | 0.3464 | 0.1386 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3719 | 0.3719 | 0.1636 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3556 | 0.3556 | 0.1423 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4147 | 0.4147 | 0.1659 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3838 | 0.3838 | 0.1535 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.0265 | 1.4124 | 1.4124 | 1.4124 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.7134 | 1.4018 | 1.4018 | 1.4018 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.0200 | 1.5007 | 1.5007 | 1.5007 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 117.83 |
Number of hours cooling loads not met | 297.83 |
Number of hours not met | 415.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 30.76 | 86722.52 | 19.05 | 46154.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 314.31 | 77389.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 280.73 | 28079.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 71.90 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 641.30 | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 12.98 | 926.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 130.31 | 35506.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 99.44 | 9222.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 762.04 | 1603.04 |
Natural Gas | 0.00 | 118.50 |
Additional | 0.00 | 0.00 |
Total | 762.04 | 1721.53 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 56.35 |
Space Heating | 6.17 |
Space Cooling | 63.09 |
Fans (All) | 26.15 |
Service Water Heating | 0.00 |
Receptacle Equipment | 152.95 |
Miscellaneous (All) | 321.75 |
Subtotal | 321.75 |
Natural Gas [MJ/m2] | |
Space Heating | 3.82 |
Service Water Heating | 19.96 |
Miscellaneous (All) | 23.78 |
Subtotal | 23.78 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 16.31 |
Space Heating | 2.89 |
Space Cooling | 18.26 |
Fans (All) | 7.57 |
Service Water Heating | 5.78 |
Receptacle Equipment | 44.27 |
Miscellaneous | 4.93 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2429. | 8760. |
BLDG_EQUIP_SCH | 4487. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8666.67 | 93.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8751.00 | 9.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8730.50 | 29.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8679.33 | 80.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8712.67 | 47.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8665.50 | 94.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8705.50 | 54.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8730.67 | 29.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8690.83 | 69.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8697.67 | 62.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8718.83 | 41.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8667.83 | 92.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8540.50 | 219.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8540.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 219.50 | 0.00 | 0.00 | 0.00 |
Average | 8708.32 | 51.68 | 0.00 | 0.00 | 0.00 |
Sum | 156749.83 | 930.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128296.33 | 7.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24908.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 7.67 | 0.00 | 0.00 | 0.00 |
Average | 34142.85 | 0.48 | 0.00 | 0.00 | 0.00 |
Sum | 614571.33 | 8.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8477.00 | 283.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8569.00 | 191.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8646.17 | 113.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8506.67 | 253.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8445.00 | 315.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8474.83 | 285.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8468.83 | 291.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8562.00 | 198.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8452.67 | 307.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8456.83 | 303.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8444.67 | 315.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8493.67 | 266.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8424.00 | 336.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8443.50 | 316.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8421.83 | 338.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8420.50 | 339.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8597.33 | 162.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8633.00 | 127.00 | 0.00 | 0.00 | 0.00 |
Min | 8420.50 | 113.83 | 0.00 | 0.00 | 0.00 |
Max | 8646.17 | 339.50 | 0.00 | 0.00 | 0.00 |
Average | 8496.53 | 263.47 | 0.00 | 0.00 | 0.00 |
Sum | 152937.50 | 4742.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128175.83 | 128.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128222.33 | 81.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128230.00 | 74.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24896.00 | 13.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14011.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24897.33 | 11.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14011.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24906.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14014.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24730.00 | 179.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14015.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24902.67 | 6.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10133.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24903.33 | 5.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14015.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128230.00 | 179.00 | 0.00 | 0.00 | 0.00 |
Average | 34114.60 | 28.73 | 0.00 | 0.00 | 0.00 |
Sum | 614062.83 | 517.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150662E+11 | 19681.61 | 26-JAN-08:03 | 0.87 | -3.2 | 0.198122E+10 | 2606.64 | 02-JAN-10:09 | 0.87 | -3.2 |
February | 0.149936E+11 | 27830.01 | 22-FEB-06:02 | 2.52 | -2.0 | 0.180121E+10 | 2606.78 | 13-FEB-10:09 | 2.52 | -2.0 |
March | 0.193670E+11 | 30479.40 | 17-MAR-05:03 | 3.72 | -1.9 | 0.215536E+10 | 2606.62 | 22-MAR-09:09 | 15.15 | 5.68 |
April | 0.220039E+11 | 36680.62 | 18-APR-05:03 | 7.88 | 5.14 | 0.191729E+10 | 2606.69 | 27-APR-09:09 | 20.87 | 11.97 |
May | 0.268258E+11 | 43444.82 | 30-MAY-04:02 | 25.00 | 11.58 | 0.207690E+10 | 2606.70 | 08-MAY-09:09 | 25.00 | 11.58 |
June | 0.284919E+11 | 43564.63 | 12-JUN-04:02 | 17.93 | 6.78 | 0.207098E+10 | 2606.66 | 12-JUN-09:00 | 30.00 | 13.95 |
July | 0.279555E+11 | 43251.66 | 06-JUL-04:02 | 22.70 | 16.87 | 0.192506E+10 | 2738.60 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.298439E+11 | 43777.66 | 14-AUG-04:02 | 17.70 | 16.58 | 0.216049E+10 | 2606.66 | 30-AUG-09:00 | 25.00 | 16.34 |
September | 0.267284E+11 | 43350.07 | 05-SEP-04:02 | 16.60 | 15.64 | 0.191882E+10 | 2606.66 | 12-SEP-09:20 | 25.17 | 14.97 |
October | 0.248350E+11 | 40833.05 | 07-OCT-05:03 | 10.10 | 8.79 | 0.199395E+10 | 2606.73 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.194520E+11 | 40464.10 | 15-NOV-06:02 | 4.40 | 0.63 | 0.197112E+10 | 2606.62 | 09-NOV-10:00 | 4.40 | 0.63 |
December | 0.145982E+11 | 18360.28 | 22-DEC-08:02 | -1.3 | -3.8 | 0.191132E+10 | 2606.71 | 12-DEC-10:30 | -1.3 | -3.8 |
Annual Sum or Average | 0.270161E+12 | 0.238837E+11 | ||||||||
Minimum of Months | 0.145982E+11 | 18360.28 | -1.3 | -3.8 | 0.180121E+10 | 2606.62 | -1.3 | -3.8 | ||
Maximum of Months | 0.298439E+11 | 43777.66 | 25.00 | 16.87 | 0.216049E+10 | 2738.60 | 30.00 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.420501E+09 | 2910.45 | 12-JAN-15:20 | 18.90 | 10.07 | 0.00 | 0.00 | 01-JAN-00:10 | 18.90 | 10.07 |
February | 0.822940E+09 | 4486.23 | 22-FEB-14:30 | 21.95 | 7.96 | 0.00 | 0.00 | 01-FEB-00:10 | 21.95 | 7.96 |
March | 0.180242E+10 | 5719.34 | 16-MAR-14:20 | 22.80 | 9.14 | 0.00 | 0.00 | 01-MAR-00:10 | 22.80 | 9.14 |
April | 0.402925E+10 | 9202.05 | 19-APR-14:30 | 31.10 | 14.32 | 0.00 | 0.00 | 01-APR-00:10 | 31.10 | 14.32 |
May | 0.656936E+10 | 11160.12 | 30-MAY-14:20 | 34.40 | 17.58 | 0.00 | 0.00 | 01-MAY-00:10 | 34.40 | 17.58 |
June | 0.893770E+10 | 11824.65 | 15-JUN-14:40 | 38.13 | 15.82 | 0.00 | 0.00 | 01-JUN-00:10 | 38.13 | 15.82 |
July | 0.833386E+10 | 12123.50 | 03-JUL-13:10 | 36.88 | 18.64 | 0.00 | 0.00 | 01-JUL-00:10 | 36.88 | 18.64 |
August | 0.773596E+10 | 11625.31 | 07-AUG-14:50 | 35.00 | 18.73 | 0.00 | 0.00 | 01-AUG-00:10 | 35.00 | 18.73 |
September | 0.619482E+10 | 10265.88 | 19-SEP-15:00 | 33.30 | 16.48 | 0.00 | 0.00 | 01-SEP-00:10 | 33.30 | 16.48 |
October | 0.341500E+10 | 9355.57 | 03-OCT-14:30 | 32.25 | 19.38 | 0.00 | 0.00 | 01-OCT-00:10 | 32.25 | 19.38 |
November | 0.120593E+10 | 5162.82 | 03-NOV-15:20 | 23.50 | 13.53 | 0.00 | 0.00 | 01-NOV-00:10 | 23.50 | 13.53 |
December | 0.283251E+09 | 1695.50 | 09-DEC-13:30 | 17.50 | 7.28 | 0.00 | 0.00 | 01-DEC-00:10 | 17.50 | 7.28 |
Annual Sum or Average | 0.497510E+11 | 0.00 | ||||||||
Minimum of Months | 0.283251E+09 | 1695.50 | 17.50 | 7.28 | 0.00 | 0.00 | 17.50 | 7.28 | ||
Maximum of Months | 0.893770E+10 | 12123.50 | 38.13 | 19.38 | 0.00 | 0.00 | 38.13 | 19.38 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148557E+09 | 1985.42 | 05-JAN-07:01 | -0.9 | -5.5 | 0.00 | 0.00 | 01-JAN-00:10 | -0.9 | -5.5 |
February | 0.229482E+09 | 2245.00 | 09-FEB-07:01 | 0.78 | -2.4 | 0.00 | 0.00 | 01-FEB-00:10 | 0.78 | -2.4 |
March | 0.525942E+09 | 2559.45 | 30-MAR-06:01 | -0.1 | -3.7 | 0.00 | 0.00 | 01-MAR-00:10 | -0.1 | -3.7 |
April | 0.180442E+10 | 3497.58 | 21-APR-15:40 | 31.47 | 15.05 | 0.00 | 0.00 | 01-APR-00:10 | 31.47 | 15.05 |
May | 0.353140E+10 | 5205.64 | 30-MAY-16:00 | 33.90 | 17.46 | 0.00 | 0.00 | 01-MAY-00:10 | 33.90 | 17.46 |
June | 0.487278E+10 | 5411.27 | 19-JUN-14:30 | 34.70 | 18.56 | 0.00 | 0.00 | 01-JUN-00:10 | 34.70 | 18.56 |
July | 0.468772E+10 | 5711.82 | 03-JUL-11:00 | 35.00 | 19.01 | 0.00 | 0.00 | 01-JUL-00:10 | 35.00 | 19.01 |
August | 0.450240E+10 | 5474.75 | 07-AUG-15:00 | 35.00 | 18.74 | 0.00 | 0.00 | 01-AUG-00:10 | 35.00 | 18.74 |
September | 0.350101E+10 | 4883.14 | 05-SEP-15:30 | 31.10 | 19.25 | 0.00 | 0.00 | 01-SEP-00:10 | 31.10 | 19.25 |
October | 0.194010E+10 | 4101.82 | 05-OCT-16:00 | 31.10 | 17.21 | 0.00 | 0.00 | 01-OCT-00:10 | 31.10 | 17.21 |
November | 0.441659E+09 | 2047.13 | 10-NOV-15:50 | 15.10 | 9.99 | 0.00 | 0.00 | 01-NOV-00:10 | 15.10 | 9.99 |
December | 0.104511E+09 | 1867.09 | 14-DEC-07:01 | 2.30 | 1.51 | 0.00 | 0.00 | 01-DEC-00:10 | 2.30 | 1.51 |
Annual Sum or Average | 0.262900E+11 | 0.00 | ||||||||
Minimum of Months | 0.104511E+09 | 1867.09 | -0.9 | -5.5 | 0.00 | 0.00 | -0.9 | -5.5 | ||
Maximum of Months | 0.487278E+10 | 5711.82 | 35.00 | 19.25 | 0.00 | 0.00 | 35.00 | 19.25 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.369779E+09 | 2792.43 | 05-JAN-07:01 | -0.9 | -5.5 | 0.00 | 0.00 | 01-JAN-00:10 | -0.9 | -5.5 |
February | 0.573423E+09 | 2793.49 | 09-FEB-07:01 | 0.78 | -2.4 | 0.00 | 0.00 | 01-FEB-00:10 | 0.78 | -2.4 |
March | 0.110543E+10 | 3220.21 | 30-MAR-06:01 | -0.1 | -3.7 | 0.00 | 0.00 | 01-MAR-00:10 | -0.1 | -3.7 |
April | 0.233398E+10 | 3686.19 | 21-APR-15:10 | 32.02 | 15.38 | 0.00 | 0.00 | 01-APR-00:10 | 32.02 | 15.38 |
May | 0.390437E+10 | 5773.95 | 30-MAY-12:07 | 31.20 | 15.49 | 0.00 | 0.00 | 01-MAY-00:10 | 31.20 | 15.49 |
June | 0.506168E+10 | 6421.91 | 05-JUN-12:07 | 34.68 | 16.27 | 0.00 | 0.00 | 01-JUN-00:10 | 34.68 | 16.27 |
July | 0.498445E+10 | 7246.43 | 03-JUL-12:09 | 35.78 | 18.54 | 0.00 | 0.00 | 01-JUL-00:10 | 35.78 | 18.54 |
August | 0.505017E+10 | 5926.62 | 01-AUG-12:08 | 30.92 | 20.18 | 0.00 | 0.00 | 01-AUG-00:10 | 30.92 | 20.18 |
September | 0.427308E+10 | 5498.45 | 05-SEP-06:15 | 17.43 | 15.20 | 0.00 | 0.00 | 01-SEP-00:10 | 17.43 | 15.20 |
October | 0.289645E+10 | 4375.58 | 05-OCT-17:10 | 28.22 | 17.73 | 0.00 | 0.00 | 01-OCT-00:10 | 28.22 | 17.73 |
November | 0.114003E+10 | 2870.03 | 10-NOV-15:30 | 15.30 | 10.08 | 0.00 | 0.00 | 01-NOV-00:10 | 15.30 | 10.08 |
December | 0.280218E+09 | 2394.98 | 07-DEC-07:01 | -1.5 | -3.4 | 0.00 | 0.00 | 01-DEC-00:10 | -1.5 | -3.4 |
Annual Sum or Average | 0.319731E+11 | 0.00 | ||||||||
Minimum of Months | 0.280218E+09 | 2394.98 | -1.5 | -5.5 | 0.00 | 0.00 | -1.5 | -5.5 | ||
Maximum of Months | 0.506168E+10 | 7246.43 | 35.78 | 20.18 | 0.00 | 0.00 | 35.78 | 20.18 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.858468E+10 | 9853.90 | 13-JAN-17:00 | 17.20 | 8.47 | 0.186299E+10 | 2606.60 | 13-JAN-10:30 | 17.20 | 8.47 |
February | 0.884620E+10 | 11646.89 | 22-FEB-17:00 | 21.70 | 8.09 | 0.173721E+10 | 2606.60 | 23-FEB-10:09 | 13.48 | 7.26 |
March | 0.117365E+11 | 13292.10 | 16-MAR-16:00 | 22.20 | 8.37 | 0.211720E+10 | 2606.62 | 22-MAR-09:09 | 15.15 | 5.68 |
April | 0.148038E+11 | 30427.01 | 20-APR-05:03 | 20.10 | 9.51 | 0.190761E+10 | 2606.67 | 27-APR-09:09 | 20.87 | 11.97 |
May | 0.190897E+11 | 31973.91 | 22-MAY-04:03 | 18.22 | 13.83 | 0.207342E+10 | 2606.68 | 08-MAY-09:09 | 18.22 | 13.83 |
June | 0.211291E+11 | 32531.00 | 12-JUN-04:02 | 17.93 | 6.78 | 0.206896E+10 | 2606.65 | 12-JUN-09:39 | 28.70 | 13.17 |
July | 0.208487E+11 | 32890.99 | 05-JUL-04:03 | 19.08 | 16.04 | 0.192262E+10 | 2690.61 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.214253E+11 | 32874.21 | 14-AUG-04:02 | 17.70 | 16.58 | 0.215814E+10 | 2606.65 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.184389E+11 | 33475.29 | 05-SEP-04:02 | 16.60 | 15.64 | 0.191566E+10 | 2606.65 | 12-SEP-09:20 | 25.17 | 14.97 |
October | 0.158334E+11 | 30976.02 | 04-OCT-05:03 | 17.80 | 15.98 | 0.198474E+10 | 2606.69 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.109110E+11 | 15647.02 | 01-NOV-05:03 | 11.10 | 9.84 | 0.191749E+10 | 2606.60 | 01-NOV-09:09 | 12.38 | 10.67 |
December | 0.821600E+10 | 8580.80 | 15-DEC-17:00 | 15.00 | 5.87 | 0.177418E+10 | 2606.56 | 01-DEC-14:09 | 15.00 | 5.87 |
Annual Sum or Average | 0.179863E+12 | 0.234402E+11 | ||||||||
Minimum of Months | 0.821600E+10 | 8580.80 | 11.10 | 5.87 | 0.173721E+10 | 2606.56 | 12.38 | 5.68 | ||
Maximum of Months | 0.214253E+11 | 33475.29 | 22.20 | 16.58 | 0.215814E+10 | 2690.61 | 28.70 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.740612E+10 | 8906.53 | 12-JAN-16:50 | 17.98 | 9.87 | 0.171682E+10 | 2606.48 | 12-JAN-14:00 | 17.98 | 9.87 |
February | 0.791859E+10 | 11116.23 | 22-FEB-15:40 | 22.60 | 8.36 | 0.163011E+10 | 2606.53 | 07-FEB-14:09 | 22.60 | 8.36 |
March | 0.108327E+11 | 14369.03 | 16-MAR-16:00 | 22.20 | 8.37 | 0.203498E+10 | 2606.57 | 09-MAR-14:09 | 22.20 | 8.37 |
April | 0.145775E+11 | 22289.87 | 20-APR-05:03 | 20.10 | 9.51 | 0.188951E+10 | 2606.67 | 27-APR-09:09 | 20.87 | 11.97 |
May | 0.196450E+11 | 34380.54 | 30-MAY-04:02 | 25.00 | 11.58 | 0.206954E+10 | 2606.67 | 08-MAY-09:09 | 25.00 | 11.58 |
June | 0.227125E+11 | 34736.20 | 05-JUN-04:02 | 22.93 | 14.00 | 0.206884E+10 | 2606.65 | 12-JUN-09:00 | 30.00 | 13.95 |
July | 0.223342E+11 | 35231.17 | 17-JUL-04:02 | 20.60 | 20.13 | 0.192332E+10 | 2697.65 | 20-JUL-15:30 | 25.25 | 22.87 |
August | 0.222956E+11 | 35324.79 | 14-AUG-04:02 | 17.70 | 16.58 | 0.215732E+10 | 2606.65 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.183035E+11 | 35075.15 | 05-SEP-04:02 | 16.60 | 15.64 | 0.191155E+10 | 2606.64 | 11-SEP-09:50 | 25.32 | 12.16 |
October | 0.145869E+11 | 33069.45 | 02-OCT-04:02 | 24.82 | 15.04 | 0.196297E+10 | 2606.66 | 02-OCT-09:09 | 22.35 | 16.60 |
November | 0.934877E+10 | 14363.06 | 10-NOV-15:00 | 15.60 | 10.20 | 0.182001E+10 | 2606.58 | 09-NOV-10:00 | 15.60 | 10.20 |
December | 0.686952E+10 | 7115.80 | 15-DEC-17:00 | 15.00 | 5.87 | 0.161856E+10 | 2552.86 | 01-DEC-14:00 | 15.00 | 5.87 |
Annual Sum or Average | 0.176831E+12 | 0.228035E+11 | ||||||||
Minimum of Months | 0.686952E+10 | 7115.80 | 15.00 | 5.87 | 0.161856E+10 | 2552.86 | 15.00 | 5.87 | ||
Maximum of Months | 0.227125E+11 | 35324.79 | 25.00 | 20.13 | 0.215732E+10 | 2697.65 | 30.00 | 22.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.793709E+09 | 1476.57 | 12-JAN-14:30 | 18.60 | 9.87 | 0.325320E+09 | 517.43 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.109377E+10 | 2119.75 | 22-FEB-15:00 | 22.20 | 8.00 | 0.311266E+09 | 549.47 | 07-FEB-14:20 | 22.20 | 8.00 |
March | 0.186780E+10 | 3360.82 | 22-MAR-14:40 | 24.07 | 8.96 | 0.398133E+09 | 549.48 | 16-MAR-13:00 | 24.07 | 8.96 |
April | 0.332724E+10 | 5875.74 | 21-APR-15:00 | 32.20 | 15.49 | 0.388005E+09 | 549.50 | 27-APR-09:09 | 20.87 | 11.97 |
May | 0.549330E+10 | 12503.42 | 21-MAY-14:42 | 34.50 | 17.78 | 0.435031E+09 | 549.50 | 03-MAY-13:00 | 34.50 | 17.78 |
June | 0.731845E+10 | 12586.61 | 18-JUN-15:42 | 37.12 | 16.83 | 0.436572E+09 | 549.50 | 27-JUN-09:50 | 25.50 | 15.70 |
July | 0.697783E+10 | 12668.61 | 02-JUL-15:42 | 38.22 | 18.83 | 0.406183E+09 | 561.23 | 20-JUL-14:00 | 24.40 | 22.82 |
August | 0.634991E+10 | 11798.76 | 06-AUG-16:52 | 36.10 | 18.82 | 0.454647E+09 | 549.50 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.472286E+10 | 6179.43 | 20-SEP-14:30 | 33.30 | 17.76 | 0.400465E+09 | 549.50 | 26-SEP-13:20 | 25.97 | 15.08 |
October | 0.303165E+10 | 7956.54 | 02-OCT-04:02 | 24.82 | 15.04 | 0.400606E+09 | 549.50 | 02-OCT-09:09 | 22.35 | 16.60 |
November | 0.143768E+10 | 2787.53 | 09-NOV-15:40 | 23.30 | 12.89 | 0.352712E+09 | 549.48 | 09-NOV-14:00 | 23.30 | 12.89 |
December | 0.638562E+09 | 1335.23 | 08-DEC-15:20 | 17.20 | 7.54 | 0.307695E+09 | 490.13 | 08-DEC-14:00 | 17.20 | 7.54 |
Annual Sum or Average | 0.430527E+11 | 0.461663E+10 | ||||||||
Minimum of Months | 0.638562E+09 | 1335.23 | 17.20 | 7.54 | 0.307695E+09 | 490.13 | 17.20 | 7.54 | ||
Maximum of Months | 0.731845E+10 | 12668.61 | 38.22 | 18.83 | 0.454647E+09 | 561.23 | 34.50 | 22.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.949092E+09 | 1336.27 | 12-JAN-14:30 | 18.60 | 9.87 | 0.217983E+09 | 345.00 | 04-JAN-10:39 | 18.60 | 9.87 |
February | 0.123884E+10 | 2758.42 | 21-FEB-10:30 | 18.35 | 7.04 | 0.212829E+09 | 347.87 | 24-FEB-10:09 | 7.48 | 2.32 |
March | 0.214498E+10 | 3964.10 | 16-MAR-10:10 | 19.18 | 7.83 | 0.269286E+09 | 347.87 | 06-MAR-10:09 | 19.18 | 7.83 |
April | 0.374872E+10 | 11159.40 | 30-APR-08:13 | 18.87 | 12.48 | 0.252758E+09 | 347.90 | 19-APR-09:09 | 18.87 | 12.48 |
May | 0.546506E+10 | 11587.12 | 21-MAY-10:02 | 27.77 | 13.68 | 0.276589E+09 | 348.25 | 09-MAY-09:00 | 27.77 | 13.68 |
June | 0.666007E+10 | 11359.78 | 18-JUN-09:42 | 31.13 | 16.72 | 0.276601E+09 | 348.21 | 27-JUN-09:00 | 25.60 | 15.68 |
July | 0.622931E+10 | 11423.77 | 02-JUL-09:42 | 30.73 | 19.96 | 0.257407E+09 | 348.30 | 28-JUL-09:00 | 30.60 | 19.45 |
August | 0.596916E+10 | 11399.57 | 06-AUG-09:32 | 29.83 | 17.77 | 0.287969E+09 | 348.20 | 09-AUG-09:39 | 29.43 | 19.02 |
September | 0.482330E+10 | 11048.87 | 17-SEP-08:32 | 22.97 | 16.21 | 0.255017E+09 | 348.28 | 05-SEP-09:00 | 22.97 | 16.21 |
October | 0.307001E+10 | 8038.05 | 01-OCT-09:43 | 24.03 | 13.49 | 0.258649E+09 | 347.89 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.153187E+10 | 4360.49 | 10-NOV-09:30 | 18.85 | 11.99 | 0.237128E+09 | 347.87 | 09-NOV-10:00 | 18.85 | 11.99 |
December | 0.818003E+09 | 1213.20 | 01-DEC-10:30 | 13.05 | 5.08 | 0.203220E+09 | 322.94 | 01-DEC-10:39 | 13.33 | 5.28 |
Annual Sum or Average | 0.426484E+11 | 0.300544E+10 | ||||||||
Minimum of Months | 0.818003E+09 | 1213.20 | 13.05 | 5.08 | 0.203220E+09 | 322.94 | 7.48 | 2.32 | ||
Maximum of Months | 0.666007E+10 | 11587.12 | 31.13 | 19.96 | 0.287969E+09 | 348.30 | 30.60 | 19.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296309E+10 | 8975.27 | 12-JAN-14:30 | 18.60 | 9.87 | 0.382501E+09 | 549.60 | 12-JAN-14:00 | 18.90 | 10.02 |
February | 0.305600E+10 | 14168.09 | 20-FEB-14:32 | 22.93 | 8.74 | 0.351090E+09 | 549.80 | 22-FEB-14:09 | 21.78 | 7.94 |
March | 0.390135E+10 | 8461.21 | 16-MAR-13:30 | 22.50 | 9.16 | 0.423297E+09 | 549.49 | 14-MAR-13:00 | 22.50 | 9.16 |
April | 0.488337E+10 | 13563.05 | 16-APR-15:42 | 29.90 | 11.70 | 0.391260E+09 | 549.51 | 26-APR-13:50 | 26.32 | 13.73 |
May | 0.604294E+10 | 14112.18 | 21-MAY-14:42 | 34.50 | 17.78 | 0.434046E+09 | 549.51 | 05-MAY-13:00 | 34.50 | 17.78 |
June | 0.727895E+10 | 13429.79 | 18-JUN-15:42 | 37.12 | 16.83 | 0.436224E+09 | 549.50 | 12-JUN-09:00 | 37.12 | 16.83 |
July | 0.720332E+10 | 14265.48 | 30-JUL-13:32 | 31.33 | 19.86 | 0.405955E+09 | 558.38 | 20-JUL-14:00 | 31.33 | 19.86 |
August | 0.770168E+10 | 14010.76 | 06-AUG-15:32 | 36.10 | 18.34 | 0.454623E+09 | 550.23 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.756375E+10 | 14588.72 | 10-SEP-12:43 | 28.80 | 18.97 | 0.401881E+09 | 549.90 | 15-SEP-13:00 | 32.20 | 17.96 |
October | 0.656589E+10 | 15906.30 | 01-OCT-13:02 | 31.28 | 14.52 | 0.410092E+09 | 554.50 | 03-OCT-13:39 | 32.07 | 19.44 |
November | 0.443633E+10 | 14441.82 | 11-NOV-13:23 | 18.30 | 8.05 | 0.388615E+09 | 549.91 | 08-NOV-14:50 | 18.30 | 8.05 |
December | 0.265764E+10 | 7017.93 | 07-DEC-14:10 | 15.68 | 6.76 | 0.366612E+09 | 549.49 | 01-DEC-14:09 | 15.68 | 6.76 |
Annual Sum or Average | 0.642543E+11 | 0.484620E+10 | ||||||||
Minimum of Months | 0.265764E+10 | 7017.93 | 15.68 | 6.76 | 0.351090E+09 | 549.49 | 15.68 | 6.76 | ||
Maximum of Months | 0.770168E+10 | 15906.30 | 37.12 | 19.86 | 0.454623E+09 | 558.38 | 37.12 | 19.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.996294E+09 | 3388.76 | 12-JAN-15:30 | 18.90 | 10.10 | 0.214368E+09 | 347.83 | 12-JAN-14:00 | 18.90 | 10.10 |
February | 0.126459E+10 | 4650.83 | 21-FEB-16:50 | 22.30 | 7.87 | 0.200085E+09 | 347.84 | 23-FEB-14:00 | 21.10 | 7.10 |
March | 0.230933E+10 | 7184.87 | 26-MAR-16:33 | 22.60 | 9.13 | 0.250219E+09 | 347.84 | 09-MAR-14:09 | 22.60 | 9.13 |
April | 0.373429E+10 | 13698.99 | 16-APR-15:42 | 29.90 | 11.70 | 0.242101E+09 | 347.86 | 26-APR-13:50 | 26.32 | 13.73 |
May | 0.537680E+10 | 13531.32 | 29-MAY-16:42 | 32.88 | 16.50 | 0.273398E+09 | 347.86 | 03-MAY-13:00 | 32.88 | 16.50 |
June | 0.644455E+10 | 13533.86 | 25-JUN-17:12 | 31.50 | 16.72 | 0.275946E+09 | 347.85 | 12-JUN-09:00 | 31.50 | 16.72 |
July | 0.605678E+10 | 13454.74 | 09-JUL-16:32 | 32.97 | 19.28 | 0.256728E+09 | 347.85 | 03-JUL-09:09 | 32.97 | 19.28 |
August | 0.580970E+10 | 13520.80 | 06-AUG-16:52 | 36.10 | 18.82 | 0.286950E+09 | 347.85 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.484403E+10 | 13271.05 | 17-SEP-15:52 | 32.80 | 15.88 | 0.252066E+09 | 347.85 | 26-SEP-13:20 | 25.97 | 15.08 |
October | 0.338967E+10 | 13046.50 | 01-OCT-14:22 | 32.50 | 15.71 | 0.250003E+09 | 347.85 | 02-OCT-09:09 | 22.35 | 16.60 |
November | 0.181362E+10 | 5415.99 | 09-NOV-15:30 | 23.30 | 12.82 | 0.224895E+09 | 347.84 | 08-NOV-14:00 | 23.30 | 12.82 |
December | 0.820897E+09 | 2478.41 | 15-DEC-16:00 | 15.60 | 6.14 | 0.204192E+09 | 347.78 | 15-DEC-14:00 | 15.60 | 6.14 |
Annual Sum or Average | 0.428605E+11 | 0.293095E+10 | ||||||||
Minimum of Months | 0.820897E+09 | 2478.41 | 15.60 | 6.14 | 0.200085E+09 | 347.78 | 15.60 | 6.14 | ||
Maximum of Months | 0.644455E+10 | 13698.99 | 36.10 | 19.28 | 0.286950E+09 | 347.86 | 32.97 | 19.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115473E+10 | 1371.58 | 13-JAN-15:00 | 18.30 | 8.81 | 0.333934E+09 | 510.65 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.117670E+10 | 1697.73 | 20-FEB-14:32 | 22.93 | 8.74 | 0.310918E+09 | 536.56 | 23-FEB-14:50 | 21.28 | 7.21 |
March | 0.164362E+10 | 1567.36 | 22-MAR-14:30 | 24.15 | 9.01 | 0.389950E+09 | 549.36 | 15-MAR-13:00 | 24.15 | 9.01 |
April | 0.241240E+10 | 3895.73 | 21-APR-15:20 | 31.83 | 15.27 | 0.386644E+09 | 549.50 | 27-APR-09:39 | 21.67 | 12.66 |
May | 0.412344E+10 | 5114.63 | 30-MAY-15:20 | 34.23 | 17.67 | 0.434618E+09 | 549.50 | 08-MAY-09:09 | 34.23 | 17.67 |
June | 0.578920E+10 | 6302.96 | 19-JUN-06:03 | 23.07 | 16.06 | 0.435892E+09 | 549.50 | 12-JUN-09:00 | 23.07 | 16.06 |
July | 0.609595E+10 | 7861.39 | 03-JUL-06:03 | 26.88 | 16.13 | 0.405670E+09 | 560.22 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.605376E+10 | 8052.02 | 07-AUG-06:03 | 25.18 | 16.26 | 0.455006E+09 | 549.50 | 30-AUG-09:00 | 25.00 | 16.34 |
September | 0.493601E+10 | 5573.30 | 05-SEP-06:02 | 17.07 | 15.07 | 0.403275E+09 | 549.49 | 12-SEP-09:20 | 25.17 | 14.97 |
October | 0.335249E+10 | 5314.03 | 03-OCT-14:30 | 32.25 | 19.38 | 0.413955E+09 | 549.50 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.185530E+10 | 2490.97 | 09-NOV-16:00 | 23.30 | 13.01 | 0.376636E+09 | 549.48 | 09-NOV-10:00 | 23.30 | 13.01 |
December | 0.115518E+10 | 1344.76 | 01-DEC-14:10 | 14.22 | 6.46 | 0.322406E+09 | 503.58 | 01-DEC-14:39 | 13.67 | 6.12 |
Annual Sum or Average | 0.397488E+11 | 0.466890E+10 | ||||||||
Minimum of Months | 0.115473E+10 | 1344.76 | 14.22 | 6.46 | 0.310918E+09 | 503.58 | 13.67 | 6.12 | ||
Maximum of Months | 0.609595E+10 | 8052.02 | 34.23 | 19.38 | 0.455006E+09 | 560.22 | 34.23 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112547E+10 | 1391.79 | 04-JAN-10:10 | 9.60 | 3.11 | 0.230613E+09 | 347.86 | 31-JAN-10:09 | 11.88 | 4.56 |
February | 0.121454E+10 | 2414.65 | 21-FEB-10:30 | 18.35 | 7.04 | 0.218059E+09 | 347.87 | 17-FEB-10:09 | 18.35 | 7.04 |
March | 0.175193E+10 | 2857.14 | 31-MAR-09:50 | 18.25 | 6.32 | 0.271617E+09 | 347.87 | 06-MAR-10:09 | 18.25 | 6.32 |
April | 0.290645E+10 | 7041.54 | 30-APR-08:13 | 18.87 | 12.48 | 0.253716E+09 | 347.88 | 27-APR-09:09 | 18.87 | 12.48 |
May | 0.446899E+10 | 9690.74 | 21-MAY-10:02 | 27.77 | 13.68 | 0.276740E+09 | 348.11 | 30-MAY-09:00 | 28.90 | 14.30 |
June | 0.559245E+10 | 9833.59 | 11-JUN-09:12 | 26.47 | 11.74 | 0.276497E+09 | 348.11 | 09-JUN-09:00 | 26.47 | 11.74 |
July | 0.560435E+10 | 10281.09 | 04-JUL-09:32 | 27.57 | 18.80 | 0.257441E+09 | 348.99 | 21-JUL-10:30 | 24.75 | 21.90 |
August | 0.577324E+10 | 9899.39 | 27-AUG-08:32 | 28.50 | 13.96 | 0.288522E+09 | 348.09 | 04-AUG-09:00 | 28.50 | 13.96 |
September | 0.504641E+10 | 10128.47 | 04-SEP-09:42 | 25.63 | 18.58 | 0.256034E+09 | 348.24 | 15-SEP-09:50 | 27.43 | 19.66 |
October | 0.338970E+10 | 7819.36 | 01-OCT-09:43 | 24.03 | 13.49 | 0.264089E+09 | 347.89 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.186994E+10 | 4177.96 | 10-NOV-09:20 | 18.67 | 11.91 | 0.251346E+09 | 347.87 | 09-NOV-10:00 | 18.67 | 11.91 |
December | 0.111104E+10 | 1219.45 | 01-DEC-10:10 | 12.48 | 4.67 | 0.221250E+09 | 347.86 | 01-DEC-10:50 | 13.62 | 5.49 |
Annual Sum or Average | 0.398545E+11 | 0.306592E+10 | ||||||||
Minimum of Months | 0.111104E+10 | 1219.45 | 9.60 | 3.11 | 0.218059E+09 | 347.86 | 11.88 | 4.56 | ||
Maximum of Months | 0.577324E+10 | 10281.09 | 28.50 | 18.80 | 0.288522E+09 | 348.99 | 28.90 | 21.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185233E+10 | 6483.12 | 12-JAN-13:08 | 16.97 | 8.98 | 0.365243E+09 | 549.50 | 23-JAN-14:20 | 10.60 | 6.35 |
February | 0.178392E+10 | 11428.13 | 20-FEB-14:32 | 22.93 | 8.74 | 0.332713E+09 | 549.50 | 14-FEB-14:50 | 22.93 | 8.74 |
March | 0.217916E+10 | 5616.50 | 22-MAR-13:10 | 24.90 | 9.24 | 0.401681E+09 | 549.51 | 22-MAR-13:00 | 24.40 | 9.14 |
April | 0.349242E+10 | 9831.08 | 19-APR-12:00 | 30.60 | 14.04 | 0.381582E+09 | 571.33 | 19-APR-12:09 | 30.60 | 14.03 |
May | 0.531192E+10 | 10722.81 | 19-MAY-16:10 | 34.90 | 16.83 | 0.430255E+09 | 616.89 | 19-MAY-12:09 | 34.90 | 16.83 |
June | 0.733057E+10 | 11997.24 | 02-JUN-17:00 | 38.90 | 16.17 | 0.439311E+09 | 680.91 | 15-JUN-12:09 | 36.10 | 14.46 |
July | 0.757191E+10 | 12050.27 | 03-JUL-17:00 | 38.30 | 18.83 | 0.408869E+09 | 681.21 | 03-JUL-12:09 | 38.30 | 18.83 |
August | 0.832676E+10 | 11752.23 | 07-AUG-16:50 | 36.78 | 17.90 | 0.457476E+09 | 662.02 | 07-AUG-12:09 | 36.78 | 17.90 |
September | 0.834077E+10 | 12031.96 | 04-SEP-13:02 | 30.60 | 18.77 | 0.406585E+09 | 636.82 | 19-SEP-12:09 | 31.88 | 16.39 |
October | 0.649681E+10 | 12718.89 | 01-OCT-13:02 | 31.28 | 14.52 | 0.414316E+09 | 614.11 | 03-OCT-12:09 | 30.10 | 18.63 |
November | 0.381635E+10 | 11849.60 | 11-NOV-13:43 | 18.30 | 8.00 | 0.386627E+09 | 553.29 | 09-NOV-14:09 | 18.30 | 8.00 |
December | 0.173824E+10 | 5229.79 | 07-DEC-13:20 | 14.80 | 6.44 | 0.350567E+09 | 549.50 | 29-DEC-14:09 | 9.50 | 2.92 |
Annual Sum or Average | 0.582411E+11 | 0.477522E+10 | ||||||||
Minimum of Months | 0.173824E+10 | 5229.79 | 14.80 | 6.44 | 0.332713E+09 | 549.50 | 9.50 | 2.92 | ||
Maximum of Months | 0.834077E+10 | 12718.89 | 38.90 | 18.83 | 0.457476E+09 | 681.21 | 38.30 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120450E+10 | 2484.61 | 30-JAN-16:30 | 15.60 | 6.05 | 0.222701E+09 | 347.83 | 13-JAN-14:00 | 15.60 | 6.05 |
February | 0.118851E+10 | 3651.28 | 21-FEB-16:50 | 22.30 | 7.87 | 0.204947E+09 | 347.83 | 22-FEB-14:00 | 22.20 | 8.00 |
March | 0.177753E+10 | 3718.58 | 14-MAR-16:00 | 24.40 | 10.33 | 0.255668E+09 | 347.84 | 09-MAR-14:09 | 24.40 | 10.33 |
April | 0.274340E+10 | 10470.49 | 16-APR-15:42 | 29.90 | 11.70 | 0.247260E+09 | 347.85 | 27-APR-09:00 | 22.20 | 13.12 |
May | 0.428015E+10 | 10790.99 | 29-MAY-16:31 | 32.97 | 16.56 | 0.275556E+09 | 347.86 | 08-MAY-09:09 | 32.97 | 16.56 |
June | 0.530406E+10 | 10630.94 | 11-JUN-17:11 | 32.03 | 14.84 | 0.276239E+09 | 347.85 | 12-JUN-09:00 | 30.00 | 13.95 |
July | 0.534450E+10 | 10587.03 | 04-JUL-15:31 | 34.23 | 18.80 | 0.257088E+09 | 347.86 | 03-JUL-09:09 | 34.23 | 18.80 |
August | 0.553176E+10 | 10766.61 | 06-AUG-17:32 | 35.77 | 18.42 | 0.288376E+09 | 347.85 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.494461E+10 | 11030.92 | 17-SEP-16:42 | 31.88 | 15.56 | 0.255818E+09 | 347.85 | 11-SEP-09:50 | 31.88 | 15.56 |
October | 0.353379E+10 | 10444.38 | 01-OCT-14:22 | 32.50 | 15.71 | 0.263524E+09 | 347.86 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.202932E+10 | 4905.02 | 03-NOV-16:00 | 23.90 | 13.45 | 0.244020E+09 | 347.84 | 09-NOV-10:50 | 19.72 | 9.76 |
December | 0.116488E+10 | 2315.64 | 15-DEC-16:10 | 15.50 | 6.10 | 0.214718E+09 | 347.84 | 01-DEC-14:00 | 15.50 | 6.10 |
Annual Sum or Average | 0.390470E+11 | 0.300591E+10 | ||||||||
Minimum of Months | 0.116488E+10 | 2315.64 | 15.50 | 6.05 | 0.204947E+09 | 347.83 | 15.50 | 6.05 | ||
Maximum of Months | 0.553176E+10 | 11030.92 | 35.77 | 18.80 | 0.288376E+09 | 347.86 | 34.23 | 18.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118864E+10 | 1592.14 | 12-JAN-14:30 | 18.60 | 9.87 | 0.340501E+09 | 538.02 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.139092E+10 | 2273.99 | 23-FEB-14:30 | 21.65 | 7.41 | 0.326598E+09 | 549.47 | 23-FEB-14:00 | 21.10 | 7.10 |
March | 0.204185E+10 | 3191.96 | 22-MAR-14:40 | 24.07 | 8.96 | 0.415916E+09 | 549.49 | 22-MAR-13:00 | 24.07 | 8.96 |
April | 0.326958E+10 | 5247.74 | 21-APR-15:00 | 32.20 | 15.49 | 0.395682E+09 | 549.50 | 27-APR-09:09 | 20.87 | 11.97 |
May | 0.522738E+10 | 8166.21 | 30-MAY-06:03 | 25.10 | 11.90 | 0.436617E+09 | 549.50 | 08-MAY-09:09 | 25.10 | 11.90 |
June | 0.675537E+10 | 10726.67 | 04-JUN-17:01 | 34.90 | 16.85 | 0.436684E+09 | 549.50 | 12-JUN-09:39 | 28.70 | 13.17 |
July | 0.645192E+10 | 10723.44 | 02-JUL-18:11 | 35.93 | 17.69 | 0.406146E+09 | 561.69 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.600545E+10 | 8891.20 | 07-AUG-04:02 | 26.10 | 16.24 | 0.455132E+09 | 549.50 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.462279E+10 | 5540.50 | 20-SEP-14:30 | 33.30 | 17.76 | 0.402789E+09 | 549.50 | 11-SEP-09:50 | 33.30 | 17.76 |
October | 0.315094E+10 | 7915.13 | 02-OCT-04:02 | 24.82 | 15.04 | 0.411337E+09 | 549.50 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.173114E+10 | 2798.04 | 09-NOV-16:00 | 23.30 | 13.01 | 0.372040E+09 | 549.48 | 09-NOV-10:20 | 23.30 | 13.01 |
December | 0.103822E+10 | 1342.14 | 08-DEC-15:00 | 17.20 | 7.54 | 0.321696E+09 | 516.19 | 08-DEC-14:00 | 17.20 | 7.54 |
Annual Sum or Average | 0.428742E+11 | 0.472114E+10 | ||||||||
Minimum of Months | 0.103822E+10 | 1342.14 | 17.20 | 7.41 | 0.321696E+09 | 516.19 | 17.20 | 7.10 | ||
Maximum of Months | 0.675537E+10 | 10726.67 | 35.93 | 17.76 | 0.455132E+09 | 561.69 | 33.30 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116649E+10 | 1962.00 | 04-JAN-09:50 | 9.32 | 3.11 | 0.167948E+09 | 338.71 | 12-JAN-09:39 | 9.83 | 5.16 |
February | 0.144295E+10 | 3217.23 | 21-FEB-10:00 | 16.70 | 6.62 | 0.161983E+09 | 338.72 | 21-FEB-08:20 | 16.70 | 6.62 |
March | 0.229227E+10 | 4249.32 | 31-MAR-09:00 | 15.00 | 4.82 | 0.201455E+09 | 338.72 | 21-MAR-14:30 | 15.00 | 4.82 |
April | 0.366434E+10 | 11102.12 | 30-APR-08:42 | 19.72 | 12.65 | 0.187547E+09 | 338.85 | 27-APR-08:00 | 19.72 | 12.65 |
May | 0.513701E+10 | 10945.85 | 14-MAY-09:12 | 25.57 | 12.30 | 0.204725E+09 | 343.15 | 30-MAY-07:19 | 25.97 | 12.58 |
June | 0.614207E+10 | 11514.70 | 18-JUN-09:32 | 30.57 | 16.80 | 0.204421E+09 | 344.00 | 05-JUN-07:19 | 30.57 | 16.80 |
July | 0.574212E+10 | 11523.61 | 04-JUL-08:52 | 26.10 | 18.11 | 0.190847E+09 | 346.13 | 21-JUL-10:30 | 24.75 | 21.90 |
August | 0.555908E+10 | 11008.23 | 27-AUG-08:32 | 28.50 | 13.96 | 0.212879E+09 | 339.63 | 07-AUG-10:50 | 28.50 | 13.96 |
September | 0.462521E+10 | 11256.72 | 04-SEP-08:32 | 22.57 | 17.97 | 0.188994E+09 | 338.88 | 15-SEP-08:00 | 25.60 | 19.42 |
October | 0.312115E+10 | 6354.24 | 05-OCT-08:40 | 24.27 | 17.57 | 0.193168E+09 | 338.74 | 17-OCT-10:09 | 21.47 | 16.47 |
November | 0.177087E+10 | 4735.34 | 10-NOV-09:00 | 18.30 | 11.76 | 0.180106E+09 | 338.72 | 09-NOV-11:20 | 18.30 | 11.76 |
December | 0.105508E+10 | 1357.64 | 07-DEC-09:25 | 5.30 | 0.63 | 0.157843E+09 | 338.71 | 07-DEC-09:39 | 5.77 | 0.97 |
Annual Sum or Average | 0.417186E+11 | 0.225192E+10 | ||||||||
Minimum of Months | 0.105508E+10 | 1357.64 | 5.30 | 0.63 | 0.157843E+09 | 338.71 | 5.77 | 0.97 | ||
Maximum of Months | 0.614207E+10 | 11523.61 | 30.57 | 18.11 | 0.212879E+09 | 346.13 | 30.57 | 21.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.347299E+10 | 8759.68 | 12-JAN-14:10 | 18.40 | 9.78 | 0.395505E+09 | 549.62 | 04-JAN-14:00 | 18.40 | 9.78 |
February | 0.341300E+10 | 10368.72 | 20-FEB-12:43 | 21.10 | 8.39 | 0.362584E+09 | 549.96 | 22-FEB-14:30 | 21.95 | 7.96 |
March | 0.408412E+10 | 7967.75 | 16-MAR-13:10 | 22.30 | 9.05 | 0.436734E+09 | 549.78 | 22-MAR-13:39 | 24.60 | 9.18 |
April | 0.471458E+10 | 12272.58 | 30-APR-13:23 | 29.40 | 12.42 | 0.398238E+09 | 549.77 | 21-APR-13:30 | 29.40 | 12.42 |
May | 0.567597E+10 | 9277.49 | 29-MAY-13:43 | 32.43 | 16.80 | 0.436464E+09 | 549.51 | 05-MAY-13:00 | 32.43 | 16.80 |
June | 0.668129E+10 | 11806.98 | 18-JUN-15:31 | 37.03 | 16.78 | 0.436563E+09 | 549.50 | 12-JUN-09:00 | 37.03 | 16.78 |
July | 0.661113E+10 | 12225.22 | 30-JUL-13:32 | 31.33 | 19.86 | 0.406120E+09 | 557.04 | 20-JUL-15:20 | 31.33 | 19.86 |
August | 0.720857E+10 | 12214.60 | 27-AUG-11:12 | 32.57 | 15.48 | 0.455390E+09 | 550.20 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.725794E+10 | 12894.78 | 04-SEP-13:52 | 30.60 | 18.77 | 0.403945E+09 | 554.20 | 29-SEP-13:39 | 28.13 | 14.71 |
October | 0.658959E+10 | 12740.57 | 01-OCT-13:12 | 31.47 | 14.72 | 0.416901E+09 | 568.43 | 30-OCT-13:20 | 23.30 | 11.27 |
November | 0.489110E+10 | 12742.28 | 11-NOV-12:32 | 17.93 | 8.04 | 0.400464E+09 | 556.52 | 09-NOV-14:09 | 17.93 | 8.04 |
December | 0.323360E+10 | 7406.16 | 07-DEC-13:40 | 15.20 | 6.59 | 0.379956E+09 | 549.49 | 01-DEC-14:09 | 15.20 | 6.59 |
Annual Sum or Average | 0.638339E+11 | 0.492886E+10 | ||||||||
Minimum of Months | 0.323360E+10 | 7406.16 | 15.20 | 6.59 | 0.362584E+09 | 549.49 | 15.20 | 6.59 | ||
Maximum of Months | 0.725794E+10 | 12894.78 | 37.03 | 19.86 | 0.455390E+09 | 568.43 | 37.03 | 19.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129495E+10 | 3405.91 | 12-JAN-15:30 | 18.90 | 10.10 | 0.221776E+09 | 347.83 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.149670E+10 | 4592.13 | 21-FEB-16:40 | 22.40 | 7.93 | 0.207954E+09 | 347.84 | 23-FEB-14:00 | 21.10 | 7.10 |
March | 0.240653E+10 | 6172.64 | 26-MAR-17:23 | 21.95 | 8.81 | 0.261044E+09 | 347.84 | 22-MAR-13:00 | 21.95 | 8.81 |
April | 0.356338E+10 | 12564.29 | 30-APR-16:41 | 30.10 | 12.63 | 0.248509E+09 | 347.85 | 27-APR-09:09 | 30.10 | 12.63 |
May | 0.504783E+10 | 12125.45 | 07-MAY-17:12 | 28.70 | 13.88 | 0.275723E+09 | 347.86 | 05-MAY-13:00 | 28.70 | 13.88 |
June | 0.595941E+10 | 12294.99 | 04-JUN-17:01 | 34.90 | 16.85 | 0.276329E+09 | 347.85 | 12-JUN-09:39 | 28.70 | 13.17 |
July | 0.558049E+10 | 12097.93 | 09-JUL-16:21 | 33.05 | 19.34 | 0.256986E+09 | 347.85 | 03-JUL-09:09 | 33.05 | 19.34 |
August | 0.543405E+10 | 11920.89 | 27-AUG-16:31 | 35.00 | 16.38 | 0.287924E+09 | 347.85 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.462812E+10 | 11681.39 | 10-SEP-15:51 | 31.10 | 16.68 | 0.254644E+09 | 347.85 | 11-SEP-09:50 | 25.32 | 12.16 |
October | 0.336381E+10 | 10788.67 | 08-OCT-16:23 | 25.25 | 17.49 | 0.258542E+09 | 347.85 | 03-OCT-09:39 | 25.25 | 17.49 |
November | 0.203681E+10 | 5292.29 | 09-NOV-15:30 | 23.30 | 12.82 | 0.235215E+09 | 347.84 | 08-NOV-14:00 | 23.30 | 12.82 |
December | 0.113269E+10 | 2727.78 | 15-DEC-16:00 | 15.60 | 6.14 | 0.211478E+09 | 347.84 | 01-DEC-14:00 | 15.60 | 6.14 |
Annual Sum or Average | 0.419448E+11 | 0.299612E+10 | ||||||||
Minimum of Months | 0.113269E+10 | 2727.78 | 15.60 | 6.14 | 0.207954E+09 | 347.83 | 15.60 | 6.14 | ||
Maximum of Months | 0.595941E+10 | 12564.29 | 35.00 | 19.34 | 0.287924E+09 | 347.86 | 33.05 | 19.34 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177323E+10 | 8957.71 | 28-JAN-07:03 | -2.9 |
February | 0.127204E+10 | 9534.90 | 03-FEB-07:02 | -5.1 |
March | 0.106907E+10 | 8847.22 | 02-MAR-07:01 | -1.6 |
April | 0.428794E+09 | 4639.27 | 20-APR-05:03 | 20.10 |
May | 0.176012E+09 | 7098.37 | 01-MAY-05:03 | 14.40 |
June | 54796581.31 | 6295.80 | 12-JUN-04:02 | 17.93 |
July | 35928386.81 | 5943.20 | 05-JUL-04:03 | 19.08 |
August | 51537370.25 | 5314.16 | 14-AUG-04:02 | 17.70 |
September | 0.185712E+09 | 6306.68 | 05-SEP-04:02 | 16.60 |
October | 0.444718E+09 | 4121.44 | 05-OCT-05:03 | 21.32 |
November | 0.109600E+10 | 8462.20 | 28-NOV-07:01 | 0.87 |
December | 0.209058E+10 | 10715.86 | 27-DEC-07:02 | -4.3 |
Annual Sum or Average | 0.867842E+10 | |||
Minimum of Months | 35928386.81 | 4121.44 | -5.1 | |
Maximum of Months | 0.209058E+10 | 10715.86 | 21.32 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.987418E+09 | 2608.10 | 29-JAN-14:00 | 13.30 |
February | 0.572703E+09 | 3306.27 | 20-FEB-12:43 | 21.10 |
March | 0.315763E+09 | 2596.63 | 19-MAR-12:23 | 21.95 |
April | 34664649.54 | 2263.92 | 17-APR-05:03 | 13.72 |
May | 22301429.33 | 2145.19 | 24-MAY-05:03 | 17.20 |
June | 18786465.03 | 2883.44 | 15-JUN-04:02 | 29.53 |
July | 21226434.61 | 2366.04 | 26-JUL-04:03 | 25.82 |
August | 21371138.31 | 2351.99 | 27-AUG-15:11 | 35.00 |
September | 22334394.50 | 2378.67 | 25-SEP-05:03 | 9.08 |
October | 39683166.66 | 4233.93 | 08-OCT-15:43 | 26.20 |
November | 0.460681E+09 | 3747.26 | 05-NOV-13:03 | 16.20 |
December | 0.111461E+10 | 2740.23 | 04-DEC-11:40 | 8.67 |
Annual Sum or Average | 0.363155E+10 | |||
Minimum of Months | 18786465.03 | 2145.19 | 8.67 | |
Maximum of Months | 0.111461E+10 | 4233.93 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.445316E+09 | 3421.38 | 19-JAN-08:04 | 4.18 |
February | 0.189651E+09 | 4602.45 | 22-FEB-06:02 | 2.52 |
March | 79377061.67 | 4969.75 | 17-MAR-05:03 | 3.72 |
April | 22384482.23 | 5411.86 | 11-APR-05:03 | 4.90 |
May | 23227262.69 | 3649.48 | 06-MAY-05:03 | 10.50 |
June | 20828075.71 | 3841.05 | 28-JUN-04:03 | 17.38 |
July | 24680360.67 | 3632.05 | 19-JUL-04:03 | 20.00 |
August | 29047688.13 | 3818.72 | 16-AUG-04:03 | 19.90 |
September | 33291799.79 | 4395.31 | 25-SEP-04:03 | 10.32 |
October | 49704837.23 | 4738.61 | 10-OCT-04:03 | 12.98 |
November | 0.177746E+09 | 6020.22 | 07-NOV-06:02 | 3.98 |
December | 0.520073E+09 | 4319.19 | 04-DEC-08:07 | 0.28 |
Annual Sum or Average | 0.161533E+10 | |||
Minimum of Months | 20828075.71 | 3421.38 | 0.28 | |
Maximum of Months | 0.520073E+09 | 6020.22 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1045997.23 | 10459.97 | 17-JAN-07:02 | 5.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 2833066.72 | 16611.41 | 27-DEC-07:01 | -4.3 |
Annual Sum or Average | 3879063.95 | |||
Minimum of Months | 0.00 | 0.00 | -4.3 | |
Maximum of Months | 2833066.72 | 16611.41 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145746E+09 | 27780.49 | 17-JAN-06:01 | 4.50 |
February | 35816189.96 | 26848.86 | 02-FEB-07:01 | -4.0 |
March | 8739999.38 | 26804.02 | 02-MAR-07:01 | -1.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 52915044.11 | 27804.59 | 27-NOV-06:01 | 3.30 |
December | 0.280825E+09 | 28995.87 | 04-DEC-06:01 | -1.0 |
Annual Sum or Average | 0.524041E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.280825E+09 | 28995.87 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.858361E+09 | 10204.32 | 17-JAN-06:01 | 4.50 |
February | 0.446023E+09 | 10150.15 | 03-FEB-06:01 | -3.7 |
March | 0.201028E+09 | 10058.64 | 02-MAR-06:01 | -3.5 |
April | 6721061.98 | 8826.37 | 12-APR-06:02 | 3.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 1176291.04 | 4980.34 | 25-OCT-06:03 | 6.88 |
November | 0.315495E+09 | 10341.22 | 28-NOV-05:02 | -0.3 |
December | 0.117911E+10 | 10716.04 | 04-DEC-05:02 | -0.7 |
Annual Sum or Average | 0.300791E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.117911E+10 | 10716.04 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.406653E+09 | 8747.89 | 17-JAN-06:01 | 4.50 |
February | 0.165241E+09 | 8694.83 | 03-FEB-06:01 | -3.7 |
March | 83394625.16 | 8605.78 | 02-MAR-06:01 | -3.5 |
April | 1704864.31 | 4859.05 | 12-APR-06:02 | 3.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 1244122.95 | 4531.46 | 25-OCT-06:03 | 6.88 |
November | 0.132579E+09 | 8717.16 | 28-NOV-05:02 | -0.3 |
December | 0.542378E+09 | 9171.09 | 04-DEC-05:02 | -0.7 |
Annual Sum or Average | 0.133319E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.542378E+09 | 9171.09 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.460882E+09 | 11052.18 | 17-JAN-06:01 | 4.50 |
February | 0.225595E+09 | 10914.75 | 03-FEB-06:01 | -3.7 |
March | 0.125547E+09 | 10934.85 | 02-MAR-06:01 | -3.5 |
April | 6634473.87 | 9680.86 | 12-APR-06:02 | 3.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 491932.17 | 3279.55 | 25-OCT-06:03 | 6.88 |
November | 0.158348E+09 | 10897.60 | 28-NOV-06:01 | 1.02 |
December | 0.599483E+09 | 11559.63 | 26-DEC-05:02 | -0.6 |
Annual Sum or Average | 0.157698E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.599483E+09 | 11559.63 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.494707E+09 | 9042.39 | 17-JAN-06:01 | 4.50 |
February | 0.262609E+09 | 8947.23 | 03-FEB-06:01 | -3.7 |
March | 0.111935E+09 | 8885.53 | 02-MAR-06:01 | -3.5 |
April | 5421595.24 | 6908.48 | 12-APR-06:02 | 3.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 1035266.22 | 3754.28 | 25-OCT-06:03 | 6.88 |
November | 0.185428E+09 | 8796.29 | 28-NOV-06:01 | 1.02 |
December | 0.667269E+09 | 9470.77 | 26-DEC-05:02 | -0.6 |
Annual Sum or Average | 0.172841E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.667269E+09 | 9470.77 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119570E+09 | 7523.35 | 28-JAN-06:01 | -3.3 |
February | 86538435.13 | 7504.60 | 03-FEB-06:01 | -3.7 |
March | 46985907.71 | 7542.29 | 02-MAR-06:01 | -3.5 |
April | 51743.76 | 517.44 | 12-APR-06:02 | 3.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 6919282.03 | 7248.54 | 28-NOV-07:01 | 0.87 |
December | 0.139249E+09 | 7527.96 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.399315E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.139249E+09 | 7542.29 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39247330.86 | 5578.82 | 27-JAN-07:01 | -4.3 |
February | 17923440.82 | 5581.08 | 03-FEB-07:01 | -5.1 |
March | 11403705.56 | 5868.53 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 1213275.32 | 5496.63 | 28-NOV-07:01 | 0.87 |
December | 46274649.09 | 5803.85 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.116062E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 46274649.09 | 5868.53 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131563E+10 | 10701.39 | 27-JAN-07:10 | -4.3 |
February | 0.117669E+10 | 10934.81 | 03-FEB-07:10 | -5.1 |
March | 0.105010E+10 | 10440.77 | 02-MAR-07:10 | -1.6 |
April | 0.346290E+09 | 9147.70 | 12-APR-06:10 | 3.87 |
May | 64198770.68 | 7938.28 | 02-MAY-06:10 | 9.87 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 26436888.06 | 7909.07 | 25-SEP-06:05 | 10.55 |
October | 0.230191E+09 | 8347.09 | 25-OCT-06:10 | 6.88 |
November | 0.749574E+09 | 9812.66 | 28-NOV-07:10 | 0.87 |
December | 0.151151E+10 | 11231.91 | 27-DEC-07:10 | -4.3 |
Annual Sum or Average | 0.647062E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.151151E+10 | 11231.91 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44476477.86 | 5570.43 | 20-JAN-07:02 | 2.98 |
February | 32383119.34 | 5588.98 | 28-FEB-07:02 | 5.18 |
March | 13032114.76 | 5410.05 | 02-MAR-07:01 | -1.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 2932359.75 | 5366.05 | 28-NOV-07:01 | 0.87 |
December | 53521701.33 | 5642.04 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.146346E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 53521701.33 | 5642.04 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156162E+09 | 8145.22 | 28-JAN-06:01 | -3.3 |
February | 65691752.25 | 7990.88 | 02-FEB-06:01 | -3.5 |
March | 20381190.00 | 7955.43 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 36492351.67 | 8113.72 | 28-NOV-06:01 | 1.02 |
December | 0.260777E+09 | 8356.12 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.539504E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.260777E+09 | 8356.12 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 81439635.62 | 6542.34 | 28-JAN-06:01 | -3.3 |
February | 25892446.02 | 6385.46 | 10-FEB-06:01 | -2.8 |
March | 11484979.70 | 6346.59 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 14202056.23 | 6517.27 | 28-NOV-06:01 | 1.02 |
December | 0.127988E+09 | 6757.43 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.261008E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.127988E+09 | 6757.43 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 71478740.66 | 8777.57 | 28-JAN-06:01 | -3.3 |
February | 26554144.69 | 8556.39 | 02-FEB-07:01 | -4.0 |
March | 9270353.95 | 8547.81 | 02-MAR-07:01 | -1.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 13725608.91 | 8907.25 | 28-NOV-06:01 | 1.02 |
December | 0.117209E+09 | 9247.09 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.238238E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.117209E+09 | 9247.09 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 91331263.88 | 6389.80 | 26-JAN-06:01 | 1.52 |
February | 41781888.23 | 6328.27 | 02-FEB-06:01 | -3.5 |
March | 12800087.08 | 6377.77 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 21953182.81 | 6335.84 | 27-NOV-06:01 | 3.30 |
December | 0.148086E+09 | 6596.13 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.315952E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.148086E+09 | 6596.13 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.208150E+11 | 18520.31 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.188385E+11 | 18520.31 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.216654E+11 | 18520.31 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.200796E+11 | 18520.31 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.212402E+11 | 18520.31 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.208620E+11 | 18520.31 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.204550E+11 | 18520.31 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.216654E+11 | 18520.31 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.200739E+11 | 18520.31 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.208179E+11 | 18520.31 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.203773E+11 | 18520.31 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.204522E+11 | 18520.31 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.247342E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.188385E+11 | 18520.31 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.216654E+11 | 18520.31 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.819479E+09 | 1112.83 | 17-JAN-16:00 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.722399E+09 | 1030.29 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.826520E+09 | 992.94 | 10-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.720841E+09 | 822.23 | 20-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.770747E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.761430E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.716019E+09 | 797.12 | 07-JUL-07:30 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.804979E+09 | 789.39 | 17-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.731044E+09 | 871.41 | 29-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.781378E+09 | 1046.15 | 13-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.804051E+09 | 1168.55 | 22-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.800893E+09 | 1168.55 | 01-DEC-16:00 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.925978E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.716019E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.826520E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.513580E+09 | 705.03 | 17-JAN-16:00 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.455265E+09 | 657.58 | 13-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.522516E+09 | 635.10 | 10-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.458413E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.491071E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.485583E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.457072E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.511833E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.462047E+09 | 503.54 | 29-SEP-15:00 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.493094E+09 | 653.72 | 13-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.506274E+09 | 739.79 | 22-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.503496E+09 | 739.79 | 01-DEC-16:00 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.586024E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.455265E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.522516E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.792045E+09 | 1109.08 | 17-JAN-16:00 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.707169E+09 | 985.81 | 23-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.820568E+09 | 984.54 | 10-MAR-16:00 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.723463E+09 | 821.59 | 20-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.775546E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.767022E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.722005E+09 | 815.68 | 07-JUL-07:30 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.808064E+09 | 804.72 | 17-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.728660E+09 | 791.22 | 18-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.770357E+09 | 1041.27 | 13-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.779680E+09 | 1168.55 | 22-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.776317E+09 | 1168.55 | 01-DEC-16:00 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.917090E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.707169E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.820568E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.505927E+09 | 700.38 | 17-JAN-16:00 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.450709E+09 | 627.02 | 03-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.520585E+09 | 609.14 | 27-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.456853E+09 | 552.08 | 20-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.488543E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.482667E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.454040E+09 | 544.73 | 07-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.510601E+09 | 558.70 | 24-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.462422E+09 | 562.63 | 18-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.490422E+09 | 664.10 | 13-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.495752E+09 | 739.74 | 22-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.496504E+09 | 739.74 | 01-DEC-16:00 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.581502E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.450709E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.520585E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.816581E+09 | 1110.41 | 17-JAN-16:00 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.720398E+09 | 1022.50 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.825139E+09 | 985.27 | 10-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.720519E+09 | 806.80 | 20-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.770558E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.761170E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.715548E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.804521E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.729684E+09 | 856.48 | 29-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.779906E+09 | 1040.86 | 13-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.800870E+09 | 1168.55 | 22-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.798741E+09 | 1168.55 | 01-DEC-16:00 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.924363E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.715548E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.825139E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.512568E+09 | 703.86 | 17-JAN-16:00 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.454528E+09 | 654.74 | 13-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.521801E+09 | 631.58 | 10-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.458057E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.490776E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.485288E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.456738E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.511418E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.461522E+09 | 456.08 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.492435E+09 | 650.70 | 13-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.505250E+09 | 739.79 | 22-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.502547E+09 | 739.79 | 01-DEC-16:00 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.585293E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.454528E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.521801E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.791471E+09 | 1106.44 | 17-JAN-16:00 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.706659E+09 | 977.59 | 23-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.819845E+09 | 976.41 | 10-MAR-16:00 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.722830E+09 | 806.14 | 20-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.774997E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.766420E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.721202E+09 | 800.33 | 07-JUL-07:30 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.807228E+09 | 788.54 | 17-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.727834E+09 | 720.41 | 01-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.769923E+09 | 1035.71 | 13-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.778907E+09 | 1168.55 | 22-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.775926E+09 | 1168.55 | 01-DEC-16:00 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.916324E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.706659E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.819845E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.504913E+09 | 698.97 | 17-JAN-16:00 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.449860E+09 | 622.59 | 03-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.519949E+09 | 604.23 | 27-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.456485E+09 | 545.76 | 20-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.488276E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.482333E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.453659E+09 | 538.25 | 07-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.510052E+09 | 552.69 | 24-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.461792E+09 | 555.69 | 18-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.489952E+09 | 661.56 | 13-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.494736E+09 | 739.74 | 22-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.494158E+09 | 739.74 | 01-DEC-16:00 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.580616E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.449860E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.519949E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.819480E+09 | 1112.83 | 17-JAN-16:00 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.722399E+09 | 1030.30 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.826520E+09 | 992.93 | 10-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.720840E+09 | 822.21 | 20-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.770747E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.761430E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.716019E+09 | 797.09 | 07-JUL-07:30 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.804979E+09 | 789.37 | 17-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.731044E+09 | 871.42 | 29-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.781378E+09 | 1046.14 | 13-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.804051E+09 | 1168.55 | 22-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.800894E+09 | 1168.55 | 01-DEC-16:00 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.925978E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.716019E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.826520E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.513580E+09 | 705.03 | 17-JAN-16:00 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.455265E+09 | 657.57 | 13-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.522516E+09 | 635.10 | 10-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.458413E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.491071E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.485583E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.457072E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.511833E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.462047E+09 | 503.55 | 29-SEP-15:00 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.493094E+09 | 653.72 | 13-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.506274E+09 | 739.79 | 22-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.503497E+09 | 739.79 | 01-DEC-16:00 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.586025E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.455265E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.522516E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.792045E+09 | 1109.08 | 17-JAN-16:00 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.707168E+09 | 985.80 | 23-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.820568E+09 | 984.53 | 10-MAR-16:00 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.723463E+09 | 821.57 | 20-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.775546E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.767022E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.722005E+09 | 815.66 | 07-JUL-07:30 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.808063E+09 | 804.70 | 17-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.728660E+09 | 791.22 | 18-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.770357E+09 | 1041.26 | 13-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.779680E+09 | 1168.55 | 22-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.776317E+09 | 1168.55 | 01-DEC-16:00 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.917090E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.707168E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.820568E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.505927E+09 | 700.37 | 17-JAN-16:00 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.450709E+09 | 627.02 | 03-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.520586E+09 | 609.14 | 27-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.456853E+09 | 552.07 | 20-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.488543E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.482667E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.454040E+09 | 544.72 | 07-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.510601E+09 | 558.69 | 24-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.462423E+09 | 562.64 | 18-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.490422E+09 | 664.09 | 13-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.495753E+09 | 739.74 | 22-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.496504E+09 | 739.74 | 01-DEC-16:00 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.581503E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.450709E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.520586E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.208150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.200796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.212402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.208620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.204550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.200739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.208179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.203773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.204522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.247342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.819479E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536079E+09 |
February | 0.901968E+09 | 0.722399E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 197683.02 | 0.462071E+09 |
March | 0.107774E+10 | 0.826520E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 270498.55 | 0.490552E+09 |
April | 0.956342E+09 | 0.720841E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31282255.69 | 0.275049E+09 |
May | 0.103597E+10 | 0.770747E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85684000.23 | 0.159035E+09 |
June | 0.103308E+10 | 0.761430E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132533E+09 | 61588575.39 |
July | 0.959235E+09 | 0.716019E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109678E+09 | 47488090.71 |
August | 0.107774E+10 | 0.804979E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88876159.60 | 60753336.86 |
September | 0.956342E+09 | 0.731044E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29281089.63 | 79239601.39 |
October | 0.994195E+09 | 0.781378E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11160867.20 | 0.241049E+09 |
November | 0.984487E+09 | 0.804051E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442632E+09 |
December | 0.959235E+09 | 0.800893E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464996E+09 |
Annual Sum or Average | 0.119305E+11 | 0.925978E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488963E+09 | 0.332053E+10 |
Minimum of Months | 0.901968E+09 | 0.716019E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47488090.71 |
Maximum of Months | 0.107774E+10 | 0.826520E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132533E+09 | 0.536079E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.513580E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365293E+09 |
February | 0.571020E+09 | 0.455265E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316998E+09 |
March | 0.682301E+09 | 0.522516E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109496.46 | 0.344011E+09 |
April | 0.605444E+09 | 0.458413E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19228695.77 | 0.191568E+09 |
May | 0.655854E+09 | 0.491071E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56645291.37 | 0.109767E+09 |
June | 0.654023E+09 | 0.485583E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88245672.65 | 41651595.50 |
July | 0.607275E+09 | 0.457072E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73120242.29 | 32423539.71 |
August | 0.682301E+09 | 0.511833E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58515009.46 | 41717185.19 |
September | 0.605444E+09 | 0.462047E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18526899.28 | 55999328.85 |
October | 0.629407E+09 | 0.493094E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6655089.25 | 0.166869E+09 |
November | 0.623262E+09 | 0.506274E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306035E+09 |
December | 0.607275E+09 | 0.503496E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316620E+09 |
Annual Sum or Average | 0.755301E+10 | 0.586024E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321046E+09 | 0.228895E+10 |
Minimum of Months | 0.571020E+09 | 0.455265E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32423539.71 |
Maximum of Months | 0.682301E+09 | 0.522516E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88245672.65 | 0.365293E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.792045E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593361E+09 |
February | 0.901968E+09 | 0.707169E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506596E+09 |
March | 0.107774E+10 | 0.820568E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 162220.16 | 0.539392E+09 |
April | 0.956342E+09 | 0.723463E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26203929.58 | 0.286307E+09 |
May | 0.103597E+10 | 0.775546E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85443424.18 | 0.158097E+09 |
June | 0.103308E+10 | 0.767022E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134521E+09 | 60331391.13 |
July | 0.959235E+09 | 0.722005E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111284E+09 | 46341483.00 |
August | 0.107774E+10 | 0.808064E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87443316.80 | 61767524.79 |
September | 0.956342E+09 | 0.728660E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26407634.84 | 85621325.30 |
October | 0.994195E+09 | 0.770357E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8249068.62 | 0.268191E+09 |
November | 0.984487E+09 | 0.779680E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493282E+09 |
December | 0.959235E+09 | 0.776317E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512425E+09 |
Annual Sum or Average | 0.119305E+11 | 0.917090E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479714E+09 | 0.361171E+10 |
Minimum of Months | 0.901968E+09 | 0.707169E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46341483.00 |
Maximum of Months | 0.107774E+10 | 0.820568E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134521E+09 | 0.593361E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.505927E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368786E+09 |
February | 0.570983E+09 | 0.450709E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318725E+09 |
March | 0.682256E+09 | 0.520585E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 127458.24 | 0.345300E+09 |
April | 0.605404E+09 | 0.456853E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17467376.33 | 0.192676E+09 |
May | 0.655811E+09 | 0.488543E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54158906.81 | 0.110422E+09 |
June | 0.653980E+09 | 0.482667E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86827627.23 | 43239528.70 |
July | 0.607235E+09 | 0.454040E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72545141.92 | 33734331.10 |
August | 0.682256E+09 | 0.510601E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57581689.94 | 42190947.20 |
September | 0.605404E+09 | 0.462422E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18709655.75 | 56508025.18 |
October | 0.629366E+09 | 0.490422E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6083578.76 | 0.169402E+09 |
November | 0.623221E+09 | 0.495752E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306259E+09 |
December | 0.607235E+09 | 0.496504E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319375E+09 |
Annual Sum or Average | 0.755252E+10 | 0.581502E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313501E+09 | 0.230662E+10 |
Minimum of Months | 0.570983E+09 | 0.450709E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33734331.10 |
Maximum of Months | 0.682256E+09 | 0.520585E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86827627.23 | 0.368786E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.816581E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313685E+09 |
February | 0.901968E+09 | 0.720398E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 301240.52 | 0.257995E+09 |
March | 0.107774E+10 | 0.825139E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 276027.30 | 0.262299E+09 |
April | 0.956342E+09 | 0.720519E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19979902.79 | 0.142583E+09 |
May | 0.103597E+10 | 0.770558E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52460857.06 | 79553921.06 |
June | 0.103308E+10 | 0.761170E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76701889.03 | 28839698.09 |
July | 0.959235E+09 | 0.715548E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63287984.33 | 23583239.42 |
August | 0.107774E+10 | 0.804521E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50122347.82 | 32909601.51 |
September | 0.956342E+09 | 0.729684E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16488561.29 | 45243621.15 |
October | 0.994195E+09 | 0.779906E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6655556.70 | 0.142631E+09 |
November | 0.984487E+09 | 0.800870E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270200E+09 |
December | 0.959235E+09 | 0.798741E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279206E+09 |
Annual Sum or Average | 0.119305E+11 | 0.924363E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286274E+09 | 0.187873E+10 |
Minimum of Months | 0.901968E+09 | 0.715548E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23583239.42 |
Maximum of Months | 0.107774E+10 | 0.825139E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76701889.03 | 0.313685E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.512568E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217109E+09 |
February | 0.571020E+09 | 0.454528E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1750.21 | 0.181745E+09 |
March | 0.682301E+09 | 0.521801E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75521.69 | 0.190063E+09 |
April | 0.605444E+09 | 0.458057E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10626767.70 | 0.104920E+09 |
May | 0.655854E+09 | 0.490776E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32024103.84 | 58382876.20 |
June | 0.654023E+09 | 0.485288E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48690363.55 | 21134822.16 |
July | 0.607275E+09 | 0.456738E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39888031.59 | 17499532.68 |
August | 0.682301E+09 | 0.511418E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31409411.36 | 23973620.75 |
September | 0.605444E+09 | 0.461522E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9979947.31 | 33057459.59 |
October | 0.629407E+09 | 0.492435E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3796305.05 | 0.100447E+09 |
November | 0.623262E+09 | 0.505250E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189724E+09 |
December | 0.607275E+09 | 0.502547E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193234E+09 |
Annual Sum or Average | 0.755301E+10 | 0.585293E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176492E+09 | 0.133129E+10 |
Minimum of Months | 0.571020E+09 | 0.454528E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17499532.68 |
Maximum of Months | 0.682301E+09 | 0.521801E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48690363.55 | 0.217109E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.791471E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473018E+10 |
February | 0.901968E+09 | 0.706659E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382435E+10 |
March | 0.107774E+10 | 0.819845E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6119010.17 | 0.350697E+10 |
April | 0.956342E+09 | 0.722830E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392589E+09 | 0.152656E+10 |
May | 0.103597E+10 | 0.774997E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107895E+10 | 0.612003E+09 |
June | 0.103308E+10 | 0.766420E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204481E+10 | 0.214724E+09 |
July | 0.959235E+09 | 0.721202E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167851E+10 | 0.150051E+09 |
August | 0.107774E+10 | 0.807228E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142928E+10 | 0.366695E+09 |
September | 0.956342E+09 | 0.727834E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995376E+09 | 0.571402E+09 |
October | 0.994195E+09 | 0.769923E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216975E+09 | 0.171673E+10 |
November | 0.984487E+09 | 0.778907E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360623E+10 |
December | 0.959235E+09 | 0.775926E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499855E+10 |
Annual Sum or Average | 0.119305E+11 | 0.916324E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784261E+10 | 0.258244E+11 |
Minimum of Months | 0.901968E+09 | 0.706659E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150051E+09 |
Maximum of Months | 0.107774E+10 | 0.819845E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204481E+10 | 0.499855E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.504913E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218381E+09 |
February | 0.570983E+09 | 0.449860E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181532E+09 |
March | 0.682256E+09 | 0.519949E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77036.26 | 0.191072E+09 |
April | 0.605404E+09 | 0.456485E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9362562.38 | 0.105595E+09 |
May | 0.655811E+09 | 0.488276E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30078738.97 | 59464707.19 |
June | 0.653980E+09 | 0.482333E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47489761.63 | 22160610.76 |
July | 0.607235E+09 | 0.453659E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39076940.92 | 18402168.13 |
August | 0.682256E+09 | 0.510052E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30585235.00 | 24585954.03 |
September | 0.605404E+09 | 0.461792E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9877109.55 | 33578649.54 |
October | 0.629366E+09 | 0.489952E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3506535.32 | 0.103079E+09 |
November | 0.623221E+09 | 0.494736E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190303E+09 |
December | 0.607235E+09 | 0.494158E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193317E+09 |
Annual Sum or Average | 0.755252E+10 | 0.580616E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170054E+09 | 0.134147E+10 |
Minimum of Months | 0.570983E+09 | 0.449860E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18402168.13 |
Maximum of Months | 0.682256E+09 | 0.519949E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47489761.63 | 0.218381E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.819480E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488679E+09 |
February | 0.901968E+09 | 0.722399E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 147111.25 | 0.417513E+09 |
March | 0.107774E+10 | 0.826520E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 193312.93 | 0.440313E+09 |
April | 0.956342E+09 | 0.720840E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27225921.37 | 0.243404E+09 |
May | 0.103597E+10 | 0.770747E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73888168.20 | 0.139304E+09 |
June | 0.103308E+10 | 0.761430E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112560E+09 | 52003395.83 |
July | 0.959235E+09 | 0.716019E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93758654.33 | 39823605.95 |
August | 0.107774E+10 | 0.804979E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75602431.17 | 52487797.61 |
September | 0.956342E+09 | 0.731044E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25306184.62 | 69635601.88 |
October | 0.994195E+09 | 0.781378E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9501183.27 | 0.217198E+09 |
November | 0.984487E+09 | 0.804051E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408620E+09 |
December | 0.959235E+09 | 0.800894E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425500E+09 |
Annual Sum or Average | 0.119305E+11 | 0.925978E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418183E+09 | 0.299448E+10 |
Minimum of Months | 0.901968E+09 | 0.716019E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39823605.95 |
Maximum of Months | 0.107774E+10 | 0.826520E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112560E+09 | 0.488679E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.513580E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331848E+09 |
February | 0.421807E+09 | 0.455265E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.02 | 0.284597E+09 |
March | 0.502994E+09 | 0.522516E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97199.07 | 0.305673E+09 |
April | 0.447140E+09 | 0.458413E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16762193.05 | 0.167621E+09 |
May | 0.484071E+09 | 0.491071E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48524035.44 | 95550041.33 |
June | 0.482240E+09 | 0.485583E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74878979.11 | 35023866.17 |
July | 0.448971E+09 | 0.457072E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62195694.47 | 27122073.73 |
August | 0.502994E+09 | 0.511833E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49539255.01 | 35937692.14 |
September | 0.447140E+09 | 0.462047E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15986897.28 | 48670267.32 |
October | 0.465148E+09 | 0.493094E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5705562.42 | 0.148696E+09 |
November | 0.460569E+09 | 0.506274E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279880E+09 |
December | 0.448971E+09 | 0.503497E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288822E+09 |
Annual Sum or Average | 0.557719E+10 | 0.586025E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273690E+09 | 0.204944E+10 |
Minimum of Months | 0.421807E+09 | 0.455265E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27122073.73 |
Maximum of Months | 0.502994E+09 | 0.522516E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74878979.11 | 0.331848E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.792045E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535211E+09 |
February | 0.901968E+09 | 0.707168E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453226E+09 |
March | 0.107774E+10 | 0.820568E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 142438.08 | 0.478701E+09 |
April | 0.956342E+09 | 0.723463E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22334252.51 | 0.252715E+09 |
May | 0.103597E+10 | 0.775546E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72461398.60 | 0.139308E+09 |
June | 0.103308E+10 | 0.767022E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113566E+09 | 51204477.80 |
July | 0.959235E+09 | 0.722005E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94053263.35 | 39150308.88 |
August | 0.107774E+10 | 0.808063E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73522287.08 | 53563627.84 |
September | 0.956342E+09 | 0.728660E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22267153.82 | 75070472.16 |
October | 0.994195E+09 | 0.770357E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6889550.69 | 0.238046E+09 |
November | 0.984487E+09 | 0.779680E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447033E+09 |
December | 0.959235E+09 | 0.776317E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464079E+09 |
Annual Sum or Average | 0.119305E+11 | 0.917090E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405236E+09 | 0.322731E+10 |
Minimum of Months | 0.901968E+09 | 0.707168E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39150308.88 |
Maximum of Months | 0.107774E+10 | 0.820568E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113566E+09 | 0.535211E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.505927E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334265E+09 |
February | 0.570983E+09 | 0.450709E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286284E+09 |
March | 0.682256E+09 | 0.520586E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96972.78 | 0.308139E+09 |
April | 0.605404E+09 | 0.456853E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14624830.33 | 0.170237E+09 |
May | 0.655811E+09 | 0.488543E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45560486.96 | 97104450.57 |
June | 0.653980E+09 | 0.482667E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72936851.06 | 36522244.97 |
July | 0.607235E+09 | 0.454040E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60824876.25 | 28459043.53 |
August | 0.682256E+09 | 0.510601E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48128885.28 | 36563193.98 |
September | 0.605404E+09 | 0.462423E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15646658.73 | 49586559.23 |
October | 0.629366E+09 | 0.490422E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5053313.62 | 0.151887E+09 |
November | 0.623221E+09 | 0.495753E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280587E+09 |
December | 0.607235E+09 | 0.496504E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290558E+09 |
Annual Sum or Average | 0.755252E+10 | 0.581503E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262873E+09 | 0.207019E+10 |
Minimum of Months | 0.570983E+09 | 0.450709E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28459043.53 |
Maximum of Months | 0.682256E+09 | 0.520586E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72936851.06 | 0.334265E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714402E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605484E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71898.59 | 0.631538E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28503061.89 | 0.340700E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87368156.61 | 0.188320E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138946E+09 | 65862939.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115275E+09 | 49117590.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90354720.91 | 69534797.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26371292.81 | 97419222.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9615838.88 | 0.315097E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.603524E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626118E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496505E+09 | 0.430712E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49117590.35 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138946E+09 | 0.714402E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.859923E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742592E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132171.51 | 0.783482E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38482773.20 | 0.432008E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111245E+09 | 0.242274E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176848E+09 | 86238185.98 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146576E+09 | 63504587.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116376E+09 | 88562568.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35033870.00 | 0.121837E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13361961.79 | 0.387009E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729637E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750053E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638056E+09 | 0.528712E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63504587.16 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176848E+09 | 0.859923E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.832311E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722676E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.786092E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25603804.05 | 0.424238E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94966942.09 | 0.226226E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175073E+09 | 81677009.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139414E+09 | 62265712.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111843E+09 | 83344061.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27453599.06 | 0.118809E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10331718.66 | 0.379609E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691250E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714173E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584686E+09 | 0.512267E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62265712.88 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175073E+09 | 0.832311E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 18520.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 18520.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 18520.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 18520.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 18520.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 18520.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 18520.31 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 18520.31 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 18520.31 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 18520.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 18520.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 18520.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1112.83 | 17-JAN-16:00 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1461.34 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 1030.29 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.95 | 20-FEB-15:40 | 1866.13 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 992.94 | 10-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.65 | 19-MAR-14:10 | 1363.04 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 822.23 | 20-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 304.09 | 01-APR-17:03 | 1523.96 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 507.61 | 14-MAY-15:26 | 697.48 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 483.36 | 04-JUN-18:53 | 575.69 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 797.12 | 07-JUL-07:30 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 607.95 | 02-JUL-21:10 | 288.67 | 04-JUL-19:13 |
August | 1306.65 | 01-AUG-09:09 | 789.39 | 17-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.32 | 26-AUG-17:02 | 501.76 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 871.41 | 29-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.77 | 10-SEP-14:53 | 279.32 | 23-SEP-17:10 |
October | 1306.65 | 02-OCT-09:09 | 1046.15 | 13-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.51 | 01-OCT-14:52 | 712.61 | 23-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 22-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 832.57 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:00 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1162.82 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.32 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 607.95 | 1866.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 705.03 | 17-JAN-16:00 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 970.32 | 25-JAN-23:00 |
February | 827.22 | 01-FEB-10:09 | 657.58 | 13-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1243.81 | 09-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 635.10 | 10-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.16 | 22-MAR-13:00 | 938.90 | 19-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.31 | 01-APR-17:20 | 1013.60 | 10-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 349.93 | 14-MAY-15:26 | 458.56 | 04-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.55 | 04-JUN-18:53 | 382.18 | 28-JUN-02:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.88 | 02-JUL-21:10 | 195.08 | 04-JUL-19:20 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.40 | 26-AUG-18:00 | 336.64 | 14-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 503.54 | 29-SEP-15:00 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.30 | 10-SEP-14:53 | 224.13 | 24-SEP-10:30 |
October | 827.22 | 02-OCT-09:09 | 653.72 | 13-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.44 | 01-OCT-14:52 | 474.88 | 23-OCT-21:10 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 22-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 644.18 | 26-NOV-09:00 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-16:00 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 775.21 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.08 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 421.88 | 1243.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1109.08 | 17-JAN-16:00 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1483.28 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 985.81 | 23-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1907.90 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 984.54 | 10-MAR-16:00 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 | 22-MAR-13:00 | 1458.56 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 821.59 | 20-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.35 | 01-APR-17:20 | 1537.20 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 511.04 | 14-MAY-16:05 | 700.34 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 494.00 | 04-JUN-18:53 | 572.41 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 815.68 | 07-JUL-07:30 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 616.82 | 02-JUL-21:10 | 288.71 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 804.72 | 17-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 376.69 | 26-AUG-18:00 | 508.67 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 791.22 | 18-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.54 | 10-SEP-15:24 | 314.52 | 24-SEP-10:40 |
October | 1306.65 | 02-OCT-09:09 | 1041.27 | 13-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.81 | 01-OCT-15:10 | 750.56 | 23-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 22-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 969.25 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:00 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1173.58 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.71 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 616.82 | 1907.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 700.38 | 17-JAN-16:00 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 969.16 | 25-JAN-23:00 |
February | 827.17 | 01-FEB-10:09 | 627.02 | 03-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1247.80 | 09-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 609.14 | 27-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 22-MAR-13:00 | 941.01 | 19-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 552.08 | 20-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.69 | 21-APR-15:00 | 1016.87 | 10-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.12 | 14-MAY-15:24 | 470.35 | 04-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.26 | 04-JUN-18:53 | 395.29 | 28-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 544.73 | 07-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 426.59 | 02-JUL-21:10 | 227.23 | 04-JUL-19:07 |
August | 827.17 | 01-AUG-09:09 | 558.70 | 24-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 257.99 | 27-AUG-13:00 | 343.80 | 14-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 562.63 | 18-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.81 | 10-SEP-14:45 | 200.93 | 04-SEP-19:40 |
October | 827.17 | 02-OCT-09:09 | 664.10 | 13-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.17 | 01-OCT-15:04 | 489.19 | 23-OCT-21:10 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 22-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 578.72 | 26-NOV-16:55 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:00 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 775.21 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.93 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 426.59 | 1247.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1110.41 | 17-JAN-16:00 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 860.84 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 1022.50 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 20-FEB-16:00 | 1081.54 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 985.27 | 10-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.43 | 22-MAR-12:00 | 780.98 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 806.80 | 20-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.34 | 01-APR-17:03 | 871.87 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 334.95 | 14-MAY-16:00 | 383.30 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.62 | 04-JUN-19:00 | 303.57 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.38 | 02-JUL-21:10 | 153.99 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.59 | 26-AUG-18:00 | 262.16 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 856.48 | 29-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.71 | 10-SEP-15:10 | 160.35 | 24-SEP-07:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.86 | 13-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.34 | 01-OCT-14:52 | 422.92 | 24-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 22-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 547.99 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:00 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 711.76 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.99 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 347.38 | 1081.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 703.86 | 17-JAN-16:00 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 578.19 | 25-JAN-23:00 |
February | 827.22 | 01-FEB-10:09 | 654.74 | 13-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 | 20-FEB-16:00 | 737.48 | 09-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 631.58 | 10-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 22-MAR-13:00 | 560.84 | 19-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.31 | 01-APR-17:03 | 597.00 | 10-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.76 | 14-MAY-16:00 | 259.60 | 04-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.28 | 04-JUN-19:00 | 208.05 | 28-JUN-02:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.89 | 02-JUL-21:10 | 109.80 | 04-JUL-19:13 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.60 | 26-AUG-18:00 | 185.79 | 14-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 456.08 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.74 | 10-SEP-15:10 | 125.98 | 24-SEP-10:20 |
October | 827.22 | 02-OCT-09:09 | 650.70 | 13-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.65 | 01-OCT-14:52 | 289.86 | 24-OCT-02:00 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 22-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 408.80 | 26-NOV-09:00 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-16:00 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 488.34 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.80 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 230.89 | 737.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1106.44 | 17-JAN-16:00 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 28114.43 | 27-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 977.59 | 23-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 29011.03 | 03-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 976.41 | 10-MAR-16:00 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 973.09 | 21-MAR-16:10 | 24986.58 | 02-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 806.14 | 20-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7243.39 | 19-APR-16:05 | 18044.34 | 12-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10842.29 | 19-MAY-16:03 | 12636.38 | 02-MAY-06:05 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14745.95 | 02-JUN-16:01 | 6027.34 | 13-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 800.33 | 07-JUL-07:30 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14123.38 | 03-JUL-16:01 | 5775.05 | 05-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 788.54 | 17-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12886.26 | 07-AUG-16:01 | 6726.96 | 31-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 720.41 | 01-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9505.25 | 19-SEP-16:02 | 12833.39 | 25-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 1035.71 | 13-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6313.40 | 04-OCT-16:03 | 16261.00 | 25-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 22-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 22483.92 | 17-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:00 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 28081.27 | 27-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5775.05 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 14745.95 | 29011.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 698.97 | 17-JAN-16:00 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 575.13 | 25-JAN-23:00 |
February | 827.17 | 01-FEB-10:09 | 622.59 | 03-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 737.40 | 09-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 604.23 | 27-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 | 22-MAR-12:00 | 560.07 | 19-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 545.76 | 20-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.72 | 29-APR-17:03 | 597.31 | 10-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.31 | 14-MAY-15:35 | 268.35 | 04-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.78 | 04-JUN-19:00 | 216.38 | 28-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 538.25 | 07-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.70 | 02-JUL-21:10 | 123.01 | 04-JUL-19:00 |
August | 827.17 | 01-AUG-09:09 | 552.69 | 24-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.69 | 27-AUG-13:00 | 191.68 | 14-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 555.69 | 18-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.90 | 10-SEP-15:04 | 108.33 | 24-SEP-07:00 |
October | 827.17 | 02-OCT-09:09 | 661.56 | 13-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.68 | 01-OCT-15:04 | 295.03 | 24-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 22-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 378.27 | 26-NOV-09:00 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:00 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 493.04 | 18-DEC-05:35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.33 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 225.70 | 737.40 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1112.83 | 17-JAN-16:00 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1316.62 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 1030.30 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.49 | 20-FEB-15:43 | 1687.36 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 992.93 | 10-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.12 | 19-MAR-14:10 | 1258.35 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 822.21 | 20-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.30 | 01-APR-17:03 | 1370.18 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 443.56 | 14-MAY-16:00 | 632.36 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 410.04 | 10-JUN-17:02 | 489.01 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 797.09 | 07-JUL-07:30 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 514.99 | 02-JUL-21:00 | 239.48 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 789.37 | 17-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 336.60 | 26-AUG-17:02 | 415.97 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 871.42 | 29-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.72 | 10-SEP-15:00 | 237.52 | 24-SEP-07:00 |
October | 1306.65 | 02-OCT-09:09 | 1046.14 | 13-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 281.60 | 01-OCT-14:52 | 634.67 | 24-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 22-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 805.64 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:00 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1057.47 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.52 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 514.99 | 1687.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 705.03 | 17-JAN-16:00 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 872.94 | 25-JAN-23:00 |
February | 805.43 | 01-FEB-08:09 | 657.57 | 13-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 | 20-FEB-15:40 | 1121.91 | 09-FEB-01:00 |
March | 805.43 | 01-MAR-08:09 | 635.10 | 10-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 22-MAR-13:00 | 863.04 | 19-MAR-24:00 |
April | 805.43 | 03-APR-07:10 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.98 | 01-APR-17:20 | 910.78 | 10-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 306.35 | 14-MAY-16:00 | 416.15 | 04-MAY-02:00 |
June | 805.43 | 01-JUN-07:10 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.96 | 10-JUN-17:02 | 324.72 | 28-JUN-02:00 |
July | 805.43 | 03-JUL-07:10 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.67 | 02-JUL-21:00 | 159.33 | 18-JUL-21:10 |
August | 805.43 | 01-AUG-07:10 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.66 | 26-AUG-18:00 | 280.19 | 14-AUG-01:00 |
September | 805.43 | 01-SEP-07:10 | 503.55 | 29-SEP-15:00 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.29 | 10-SEP-15:20 | 195.64 | 24-SEP-10:27 |
October | 805.43 | 02-OCT-07:10 | 653.72 | 13-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.65 | 01-OCT-14:52 | 422.46 | 24-OCT-02:00 |
November | 805.43 | 01-NOV-07:10 | 739.79 | 22-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 610.17 | 26-NOV-09:00 |
December | 805.43 | 01-DEC-08:09 | 739.79 | 01-DEC-16:00 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 707.63 | 18-DEC-05:35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.33 | |||||
Maximum of Months | 805.43 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 359.67 | 1121.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1109.08 | 17-JAN-16:00 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1337.71 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 985.80 | 23-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1722.08 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 984.53 | 10-MAR-16:00 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.99 | 22-MAR-13:00 | 1335.77 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 821.57 | 20-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.79 | 01-APR-17:03 | 1381.42 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 440.95 | 14-MAY-15:54 | 635.25 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 423.61 | 10-JUN-17:02 | 486.39 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 815.66 | 07-JUL-07:30 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 517.96 | 02-JUL-21:00 | 239.95 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 804.70 | 17-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.16 | 26-AUG-18:00 | 424.40 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 791.22 | 18-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.95 | 10-SEP-15:13 | 271.39 | 24-SEP-10:27 |
October | 1306.65 | 02-OCT-09:09 | 1041.26 | 13-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.09 | 01-OCT-14:52 | 658.09 | 23-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 22-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 916.85 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:00 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1111.60 | 18-DEC-05:35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.95 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 517.96 | 1722.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 700.37 | 17-JAN-16:00 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 872.38 | 25-JAN-23:00 |
February | 827.17 | 01-FEB-10:09 | 627.02 | 03-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1126.98 | 09-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 609.14 | 27-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 22-MAR-13:00 | 865.12 | 19-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 552.07 | 20-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.01 | 21-APR-15:00 | 914.46 | 10-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 281.39 | 14-MAY-15:54 | 426.42 | 04-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 251.44 | 04-JUN-18:53 | 335.41 | 28-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 544.72 | 07-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.75 | 02-JUL-21:00 | 197.89 | 04-JUL-19:00 |
August | 827.17 | 01-AUG-09:09 | 558.69 | 24-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.61 | 27-AUG-13:00 | 287.76 | 14-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 562.64 | 18-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.30 | 10-SEP-15:13 | 166.01 | 04-SEP-19:53 |
October | 827.17 | 02-OCT-09:09 | 664.09 | 13-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.75 | 01-OCT-14:52 | 429.88 | 24-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 22-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 542.72 | 26-NOV-16:55 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:00 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 713.58 | 18-DEC-05:35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.01 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 357.75 | 1126.98 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1914.81 | 25-JAN-23:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2449.79 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.53 | 22-MAR-13:00 | 1877.86 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.25 | 01-APR-17:03 | 1962.05 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.96 | 14-MAY-16:00 | 887.50 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.48 | 04-JUN-19:00 | 661.77 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 638.53 | 02-JUL-20:53 | 326.96 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.32 | 26-AUG-17:02 | 549.86 | 14-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.31 | 10-SEP-14:53 | 333.92 | 24-SEP-07:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.41 | 01-OCT-14:52 | 908.63 | 24-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1198.83 | 26-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1597.65 | 18-DEC-05:45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.96 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 638.53 | 2449.79 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2331.52 | 25-JAN-23:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3077.81 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 | 22-MAR-13:00 | 2304.59 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.04 | 01-APR-17:03 | 2487.39 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 738.55 | 14-MAY-16:00 | 1113.85 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 685.33 | 10-JUN-17:02 | 853.37 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 792.31 | 02-JUL-21:10 | 423.03 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543.01 | 26-AUG-17:02 | 719.08 | 14-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.86 | 10-SEP-15:00 | 414.48 | 24-SEP-07:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.23 | 01-OCT-15:00 | 1135.29 | 24-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1420.73 | 26-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1897.19 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.48 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 792.31 | 3077.81 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2228.11 | 25-JAN-23:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2824.03 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2034.85 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.05 | 01-APR-17:03 | 2250.07 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.50 | 14-MAY-15:50 | 988.87 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 629.80 | 10-JUN-17:02 | 886.46 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 824.81 | 02-JUL-21:30 | 457.48 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.24 | 26-AUG-17:02 | 773.17 | 14-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.39 | 10-SEP-15:00 | 469.02 | 23-SEP-17:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.19 | 01-OCT-14:52 | 1122.34 | 23-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1334.92 | 26-NOV-14:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1759.54 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.48 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 824.81 | 2824.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19681.61 | 26-JAN-08:03 | 60350.08 | 55431.73 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27830.01 | 22-FEB-06:02 | 3176.32 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 30479.40 | 17-MAR-05:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36680.62 | 18-APR-05:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43444.82 | 30-MAY-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 43564.63 | 12-JUN-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 43251.66 | 06-JUL-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43777.66 | 14-AUG-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43350.07 | 05-SEP-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40833.05 | 07-OCT-05:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 40464.10 | 15-NOV-06:02 | 3176.32 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18360.28 | 22-DEC-08:02 | 60350.08 | 55431.73 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 18360.28 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43777.66 | 60350.08 | 55431.73 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2910.45 | 12-JAN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.88 |
February | 4486.23 | 22-FEB-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5719.34 | 16-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.65 |
April | 9202.05 | 19-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.54 | 0.00 |
May | 11160.12 | 30-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.05 | 0.00 |
June | 11824.65 | 15-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.10 | 0.00 |
July | 12123.50 | 03-JUL-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.94 | 0.00 |
August | 11625.31 | 07-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.96 | 0.00 |
September | 10265.88 | 19-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.93 | 0.00 |
October | 9355.57 | 03-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.09 | 0.00 |
November | 5162.82 | 03-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.19 |
December | 1695.50 | 09-DEC-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1695.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12123.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.10 | 121.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1985.42 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.30 |
February | 2245.00 | 09-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.27 |
March | 2559.45 | 30-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.94 |
April | 3497.58 | 21-APR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.43 | 0.00 |
May | 5205.64 | 30-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.40 | 0.00 |
June | 5411.27 | 19-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.82 | 0.00 |
July | 5711.82 | 03-JUL-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.21 | 0.00 |
August | 5474.75 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.58 | 0.00 |
September | 4883.14 | 05-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 | 0.00 |
October | 4101.82 | 05-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.53 | 0.00 |
November | 2047.13 | 10-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.61 |
December | 1867.09 | 14-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1867.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5711.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.43 | 295.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2792.43 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.89 |
February | 2793.49 | 09-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.81 |
March | 3220.21 | 30-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.55 |
April | 3686.19 | 21-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.89 | 0.00 |
May | 5773.95 | 30-MAY-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.16 | 0.00 |
June | 6421.91 | 05-JUN-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.15 | 0.00 |
July | 7246.43 | 03-JUL-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 | 0.00 |
August | 5926.62 | 01-AUG-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.72 | 0.00 |
September | 5498.45 | 05-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.80 |
October | 4375.58 | 05-OCT-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 | 0.00 |
November | 2870.03 | 10-NOV-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.91 |
December | 2394.98 | 07-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2394.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7246.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.89 | 236.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9853.90 | 13-JAN-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11646.89 | 22-FEB-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13292.10 | 16-MAR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 30427.01 | 20-APR-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31973.91 | 22-MAY-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32531.00 | 12-JUN-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32890.99 | 05-JUL-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32874.21 | 14-AUG-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33475.29 | 05-SEP-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30976.02 | 04-OCT-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15647.02 | 01-NOV-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8580.80 | 15-DEC-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 8580.80 | 0.00 | 2463.50 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33475.29 | 6035.01 | 5543.17 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8906.53 | 12-JAN-16:50 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11116.23 | 22-FEB-15:40 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14369.03 | 16-MAR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22289.87 | 20-APR-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34380.54 | 30-MAY-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34736.20 | 05-JUN-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35231.17 | 17-JUL-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35324.79 | 14-AUG-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35075.15 | 05-SEP-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33069.45 | 02-OCT-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14363.06 | 10-NOV-15:00 | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7115.80 | 15-DEC-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7115.80 | 0.00 | 2463.50 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35324.79 | 6198.29 | 5543.17 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1476.57 | 12-JAN-14:30 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 |
February | 2119.75 | 22-FEB-15:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3360.82 | 22-MAR-14:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 | 0.00 |
April | 5875.74 | 21-APR-15:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 233.53 | 0.00 |
May | 12503.42 | 21-MAY-14:42 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 272.51 | 0.00 |
June | 12586.61 | 18-JUN-15:42 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 189.66 | 0.00 |
July | 12668.61 | 02-JUL-15:42 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 373.49 | 0.00 |
August | 11798.76 | 06-AUG-16:52 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 290.44 | 0.00 |
September | 6179.43 | 20-SEP-14:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 41.92 | 0.00 |
October | 7956.54 | 02-OCT-04:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.61 |
November | 2787.53 | 09-NOV-15:40 | 1272.23 | 848.06 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 |
December | 1335.23 | 08-DEC-15:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1335.23 | 0.00 | 240.15 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12668.61 | 1306.65 | 848.06 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 373.49 | 43.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1336.27 | 12-JAN-14:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.09 |
February | 2758.42 | 21-FEB-10:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 |
March | 3964.10 | 16-MAR-10:10 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.45 |
April | 11159.40 | 30-APR-08:13 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.45 |
May | 11587.12 | 21-MAY-10:02 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 | 0.00 |
June | 11359.78 | 18-JUN-09:42 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 64.58 | 0.00 |
July | 11423.77 | 02-JUL-09:42 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11399.57 | 06-AUG-09:32 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 41.83 | 0.00 |
September | 11048.87 | 17-SEP-08:32 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.38 |
October | 8038.05 | 01-OCT-09:43 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4360.49 | 10-NOV-09:30 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.23 |
December | 1213.20 | 01-DEC-10:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1213.20 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11587.12 | 827.22 | 456.08 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 64.58 | 65.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8975.27 | 12-JAN-14:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.34 |
February | 14168.09 | 20-FEB-14:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.07 |
March | 8461.21 | 16-MAR-13:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.90 |
April | 13563.05 | 16-APR-15:42 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 48.49 | 0.00 |
May | 14112.18 | 21-MAY-14:42 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 260.04 | 0.00 |
June | 13429.79 | 18-JUN-15:42 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 190.32 | 0.00 |
July | 14265.48 | 30-JUL-13:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 86.07 | 0.00 |
August | 14010.76 | 06-AUG-15:32 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 154.40 | 0.00 |
September | 14588.72 | 10-SEP-12:43 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 69.98 | 0.00 |
October | 15906.30 | 01-OCT-13:02 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 | 0.00 |
November | 14441.82 | 11-NOV-13:23 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.22 |
December | 7017.93 | 07-DEC-14:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7017.93 | 267.84 | 160.10 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15906.30 | 1306.65 | 720.41 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 260.04 | 333.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3388.76 | 12-JAN-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.60 |
February | 4650.83 | 21-FEB-16:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.26 |
March | 7184.87 | 26-MAR-16:33 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.23 |
April | 13698.99 | 16-APR-15:42 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 19.90 | 0.00 |
May | 13531.32 | 29-MAY-16:42 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 186.06 | 0.00 |
June | 13533.86 | 25-JUN-17:12 | 0.00 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 73.88 | 0.00 |
July | 13454.74 | 09-JUL-16:32 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 71.47 | 0.00 |
August | 13520.80 | 06-AUG-16:52 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 170.88 | 0.00 |
September | 13271.05 | 17-SEP-15:52 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 99.09 | 0.00 |
October | 13046.50 | 01-OCT-14:22 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 112.24 | 0.00 |
November | 5415.99 | 09-NOV-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.46 |
December | 2478.41 | 15-DEC-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2478.41 | 0.00 | 101.35 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13698.99 | 805.38 | 456.05 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 186.06 | 130.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1371.58 | 13-JAN-15:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.26 |
February | 1697.73 | 20-FEB-14:32 | 267.84 | 160.10 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 11.22 | 0.00 |
March | 1567.36 | 22-MAR-14:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 | 0.00 |
April | 3895.73 | 21-APR-15:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 115.45 | 0.00 |
May | 5114.63 | 30-MAY-15:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 44.78 | 0.00 |
June | 6302.96 | 19-JUN-06:03 | 803.52 | 720.40 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.57 |
July | 7861.39 | 03-JUL-06:03 | 803.52 | 720.40 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 | 0.00 |
August | 8052.02 | 07-AUG-06:03 | 803.52 | 720.40 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 | 0.00 |
September | 5573.30 | 05-SEP-06:02 | 1339.19 | 1621.75 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 |
October | 5314.03 | 03-OCT-14:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 19.96 | 0.00 |
November | 2490.97 | 09-NOV-16:00 | 1272.23 | 905.45 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 |
December | 1344.76 | 01-DEC-14:10 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1344.76 | 267.84 | 160.10 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8052.02 | 1339.19 | 1621.75 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 115.45 | 63.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1391.79 | 04-JAN-10:10 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.51 |
February | 2414.65 | 21-FEB-10:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.72 |
March | 2857.14 | 31-MAR-09:50 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.65 |
April | 7041.54 | 30-APR-08:13 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.18 |
May | 9690.74 | 21-MAY-10:02 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 | 0.00 |
June | 9833.59 | 11-JUN-09:12 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.40 |
July | 10281.09 | 04-JUL-09:32 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 9899.39 | 27-AUG-08:32 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 | 0.00 |
September | 10128.47 | 04-SEP-09:42 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.19 |
October | 7819.36 | 01-OCT-09:43 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4177.96 | 10-NOV-09:20 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.74 |
December | 1219.45 | 01-DEC-10:10 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1219.45 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10281.09 | 827.22 | 456.08 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 | 70.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6483.12 | 12-JAN-13:08 | 5088.93 | 2881.64 | 6023.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1134.77 |
February | 11428.13 | 20-FEB-14:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.08 |
March | 5616.50 | 22-MAR-13:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 146.09 | 0.00 |
April | 9831.08 | 19-APR-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 6306.92 | 0.00 |
May | 10722.81 | 19-MAY-16:10 | 1607.03 | 1600.90 | 3346.41 | 0.00 | 0.00 | 0.00 | 0.00 | 9631.74 | 0.00 |
June | 11997.24 | 02-JUN-17:00 | 401.76 | 400.23 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 11897.45 | 0.00 |
July | 12050.27 | 03-JUL-17:00 | 401.76 | 484.76 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 11373.01 | 0.00 |
August | 11752.23 | 07-AUG-16:50 | 401.76 | 400.23 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 10206.46 | 0.00 |
September | 12031.96 | 04-SEP-13:02 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 22.65 | 0.00 |
October | 12718.89 | 01-OCT-13:02 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 21.32 | 0.00 |
November | 11849.60 | 11-NOV-13:43 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.26 |
December | 5229.79 | 07-DEC-13:20 | 2544.47 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1541.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5229.79 | 267.84 | 160.10 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12718.89 | 5088.93 | 2881.64 | 6023.53 | 0.00 | 0.00 | 0.00 | 0.00 | 11897.45 | 1541.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2484.61 | 30-JAN-16:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.55 |
February | 3651.28 | 21-FEB-16:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.26 |
March | 3718.58 | 14-MAR-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 | 0.00 |
April | 10470.49 | 16-APR-15:42 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 0.00 |
May | 10790.99 | 29-MAY-16:31 | 381.49 | 228.04 | 2859.87 | 0.00 | 0.00 | 0.00 | 0.00 | 105.94 | 0.00 |
June | 10630.94 | 11-JUN-17:11 | 0.00 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.50 | 0.00 |
July | 10587.03 | 04-JUL-15:31 | 339.11 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.54 | 0.00 |
August | 10766.61 | 06-AUG-17:32 | 0.00 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 92.34 | 0.00 |
September | 11030.92 | 17-SEP-16:42 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 30.07 | 0.00 |
October | 10444.38 | 01-OCT-14:22 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 61.22 | 0.00 |
November | 4905.02 | 03-NOV-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
December | 2315.64 | 15-DEC-16:10 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2315.64 | 0.00 | 152.03 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11030.92 | 805.38 | 456.05 | 2859.87 | 0.00 | 0.00 | 0.00 | 0.00 | 105.94 | 35.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1592.14 | 12-JAN-14:30 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 |
February | 2273.99 | 23-FEB-14:30 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.20 |
March | 3191.96 | 22-MAR-14:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 0.00 |
April | 5247.74 | 21-APR-15:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 195.01 | 0.00 |
May | 8166.21 | 30-MAY-06:03 | 803.52 | 720.40 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 0.00 |
June | 10726.67 | 04-JUN-17:01 | 0.00 | 280.18 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10723.44 | 02-JUL-18:11 | 0.00 | 280.18 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 328.81 | 0.00 |
August | 8891.20 | 07-AUG-04:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 | 0.00 |
September | 5540.50 | 20-SEP-14:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 34.99 | 0.00 |
October | 7915.13 | 02-OCT-04:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.20 |
November | 2798.04 | 09-NOV-16:00 | 1272.23 | 918.04 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.75 |
December | 1342.14 | 08-DEC-15:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1342.14 | 0.00 | 280.18 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10726.67 | 1306.65 | 918.04 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 328.81 | 37.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1962.00 | 04-JAN-09:50 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.97 |
February | 3217.23 | 21-FEB-10:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 |
March | 4249.32 | 31-MAR-09:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.39 |
April | 11102.12 | 30-APR-08:42 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.85 |
May | 10945.85 | 14-MAY-09:12 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.19 |
June | 11514.70 | 18-JUN-09:32 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 37.78 | 0.00 |
July | 11523.61 | 04-JUL-08:52 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.54 |
August | 11008.23 | 27-AUG-08:32 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 11.28 | 0.00 |
September | 11256.72 | 04-SEP-08:32 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.54 |
October | 6354.24 | 05-OCT-08:40 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 | 0.00 |
November | 4735.34 | 10-NOV-09:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.96 |
December | 1357.64 | 07-DEC-09:25 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1357.64 | 211.95 | 126.70 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11523.61 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 37.78 | 109.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8759.68 | 12-JAN-14:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.95 |
February | 10368.72 | 20-FEB-12:43 | 200.88 | 120.08 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.94 |
March | 7967.75 | 16-MAR-13:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.36 |
April | 12272.58 | 30-APR-13:23 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 34.26 | 0.00 |
May | 9277.49 | 29-MAY-13:43 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 223.38 | 0.00 |
June | 11806.98 | 18-JUN-15:31 | 535.68 | 320.20 | 4015.69 | 0.00 | 0.00 | 0.00 | 0.00 | 145.88 | 0.00 |
July | 12225.22 | 30-JUL-13:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 75.92 | 0.00 |
August | 12214.60 | 27-AUG-11:12 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 183.15 | 0.00 |
September | 12894.78 | 04-SEP-13:52 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 50.22 | 0.00 |
October | 12740.57 | 01-OCT-13:12 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 50.06 | 0.00 |
November | 12742.28 | 11-NOV-12:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.23 |
December | 7406.16 | 07-DEC-13:40 | 2544.47 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7406.16 | 200.88 | 120.08 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12894.78 | 2544.47 | 1440.82 | 4015.69 | 0.00 | 0.00 | 0.00 | 0.00 | 223.38 | 241.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3405.91 | 12-JAN-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.44 |
February | 4592.13 | 21-FEB-16:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.16 |
March | 6172.64 | 26-MAR-17:23 | 0.00 | 76.01 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.94 |
April | 12564.29 | 30-APR-16:41 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 28.02 | 0.00 |
May | 12125.45 | 07-MAY-17:12 | 0.00 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 13.14 | 0.00 |
June | 12294.99 | 04-JUN-17:01 | 0.00 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12097.93 | 09-JUL-16:21 | 339.11 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.67 | 0.00 |
August | 11920.89 | 27-AUG-16:31 | 339.11 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.80 | 0.00 |
September | 11681.39 | 10-SEP-15:51 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 85.29 | 0.00 |
October | 10788.67 | 08-OCT-16:23 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.63 |
November | 5292.29 | 09-NOV-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.99 |
December | 2727.78 | 15-DEC-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2727.78 | 0.00 | 76.01 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12564.29 | 805.38 | 456.05 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.80 | 76.94 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.109865E+12 | 108150.73 | 17-JAN-07:10 | 0.138653E+11 | 51555.86 | 27-JAN-07:19 |
February | 0.985384E+11 | 102864.56 | 03-FEB-07:10 | 0.113617E+11 | 53256.37 | 03-FEB-07:10 |
March | 0.114352E+12 | 103025.81 | 02-MAR-08:09 | 0.111202E+11 | 42049.49 | 02-MAR-07:10 |
April | 0.120376E+12 | 138960.96 | 21-APR-15:09 | 0.839587E+10 | 19052.82 | 12-APR-06:10 |
May | 0.149430E+12 | 159184.02 | 30-MAY-15:00 | 0.834553E+10 | 8940.88 | 01-MAY-11:20 |
June | 0.171379E+12 | 168125.76 | 15-JUN-14:30 | 0.783639E+10 | 8812.51 | 02-JUN-11:20 |
July | 0.172677E+12 | 181276.11 | 20-JUL-15:09 | 0.754671E+10 | 8713.86 | 03-JUL-11:39 |
August | 0.172065E+12 | 162737.06 | 07-AUG-15:00 | 0.793558E+10 | 8720.97 | 31-AUG-11:20 |
September | 0.149195E+12 | 150068.62 | 05-SEP-15:30 | 0.759634E+10 | 8804.42 | 29-SEP-11:50 |
October | 0.127052E+12 | 138789.19 | 05-OCT-15:00 | 0.820076E+10 | 11204.91 | 25-OCT-06:30 |
November | 0.108161E+12 | 106379.20 | 09-NOV-16:10 | 0.993291E+10 | 34356.68 | 28-NOV-07:30 |
December | 0.109949E+12 | 121811.11 | 27-DEC-07:10 | 0.163589E+11 | 53689.64 | 27-DEC-07:30 |
Annual Sum or Average | 0.160304E+13 | 0.118496E+12 | ||||
Minimum of Months | 0.985384E+11 | 102864.56 | 0.754671E+10 | 8713.86 | ||
Maximum of Months | 0.172677E+12 | 181276.11 | 0.163589E+11 | 53689.64 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.237788E+11 | 0.726739E+10 | 0.641572E+11 | 0.109112E+10 | 0.461951E+10 | 1312252.65 | 0.830363E+10 | 0.646021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.214170E+11 | 0.615428E+10 | 0.580684E+11 | 0.987366E+09 | 0.458991E+10 | 1186778.30 | 0.485689E+10 | 0.246335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251955E+11 | 0.623038E+10 | 0.666107E+11 | 0.114319E+10 | 0.613776E+10 | 1343621.24 | 0.293344E+10 | 0.609991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223762E+11 | 0.544253E+10 | 0.619407E+11 | 0.105057E+10 | 0.926355E+10 | 1267813.82 | 0.521300E+09 | 0.197795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.240862E+11 | 0.512000E+10 | 0.653840E+11 | 0.111688E+10 | 0.146769E+11 | 1327936.95 | 92927467.02 | 0.389517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.239186E+11 | 0.470228E+10 | 0.641577E+11 | 0.109959E+10 | 0.193474E+11 | 1296568.36 | 0.00 | 0.581523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.224244E+11 | 0.496995E+10 | 0.631525E+11 | 0.106761E+10 | 0.183455E+11 | 1299182.41 | 0.00 | 0.627156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.250326E+11 | 0.540010E+10 | 0.666107E+11 | 0.114310E+10 | 0.182176E+11 | 1343621.24 | 0.00 | 0.556592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.224484E+11 | 0.576931E+10 | 0.619118E+11 | 0.105020E+10 | 0.143988E+11 | 1267813.82 | 38052548.35 | 0.435777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.234939E+11 | 0.657382E+10 | 0.641717E+11 | 0.109108E+10 | 0.100404E+11 | 1312252.65 | 0.328685E+09 | 0.213516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.234562E+11 | 0.687301E+10 | 0.627379E+11 | 0.107115E+10 | 0.617612E+10 | 1278270.02 | 0.317178E+10 | 0.467318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231048E+11 | 0.739410E+10 | 0.631380E+11 | 0.106793E+10 | 0.449241E+10 | 1299182.41 | 0.105148E+11 | 0.235135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280733E+12 | 0.718972E+11 | 0.762041E+12 | 0.129798E+11 | 0.130306E+12 | 15535293.87 | 0.307615E+11 | 0.314305E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.214170E+11 | 0.470228E+10 | 0.580684E+11 | 0.987366E+09 | 0.449241E+10 | 1186778.30 | 0.00 | 0.235135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.251955E+11 | 0.739410E+10 | 0.666107E+11 | 0.114319E+10 | 0.193474E+11 | 1343621.24 | 0.105148E+11 | 0.627156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.477307E+10 | 0.00 | 0.909219E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.312934E+10 | 0.00 | 0.823234E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.185237E+10 | 0.00 | 0.926780E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.115927E+09 | 0.00 | 0.827995E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.834553E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.783639E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.754671E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.793558E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.759634E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 19834174.01 | 0.00 | 0.818093E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.156903E+10 | 0.00 | 0.836388E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.759161E+10 | 0.00 | 0.876727E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.190512E+11 | 0.00 | 0.994449E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.754671E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.759161E+10 | 0.00 | 0.926780E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 27503.82 | 17-JAN-16:00 | 5557.43 | 01-JAN-06:10 | 47562.27 | 02-JAN-08:09 | 925.62 | 17-JAN-16:00 | 6480.06 | 12-JAN-15:39 | 0.73 | 02-JAN-08:09 | 67758.39 | 17-JAN-07:10 |
February | 26326.59 | 23-FEB-16:00 | 5557.43 | 01-FEB-06:10 | 47562.27 | 01-FEB-08:09 | 925.18 | 13-FEB-08:20 | 8627.89 | 21-FEB-16:30 | 0.73 | 01-FEB-07:10 | 67989.64 | 03-FEB-07:10 |
March | 26267.55 | 10-MAR-16:00 | 5557.43 | 01-MAR-06:10 | 47562.27 | 01-MAR-08:09 | 924.35 | 22-MAR-07:19 | 12160.19 | 16-MAR-15:30 | 0.73 | 01-MAR-08:09 | 63548.96 | 02-MAR-07:10 |
April | 24548.23 | 20-APR-07:10 | 5557.43 | 01-APR-05:10 | 47562.27 | 03-APR-07:10 | 923.13 | 20-APR-07:19 | 21207.99 | 21-APR-15:09 | 0.73 | 01-APR-05:10 | 20073.07 | 11-APR-06:10 |
May | 23688.37 | 01-MAY-07:10 | 5557.43 | 01-MAY-05:10 | 47562.27 | 01-MAY-07:10 | 921.90 | 01-MAY-07:19 | 28922.15 | 30-MAY-15:00 | 0.73 | 01-MAY-05:10 | 10063.37 | 02-MAY-06:10 |
June | 23688.37 | 01-JUN-07:10 | 5557.43 | 01-JUN-19:10 | 47562.27 | 01-JUN-07:10 | 921.90 | 01-JUN-07:19 | 28619.37 | 19-JUN-14:30 | 0.73 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 24341.65 | 07-JUL-07:30 | 5557.43 | 01-JUL-19:19 | 47562.27 | 03-JUL-07:10 | 922.83 | 07-JUL-07:40 | 35506.99 | 20-JUL-14:00 | 0.73 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 24322.87 | 17-AUG-07:10 | 5557.43 | 01-AUG-05:10 | 47562.27 | 01-AUG-07:10 | 922.81 | 17-AUG-07:19 | 26388.61 | 07-AUG-14:00 | 0.73 | 01-AUG-05:19 | 0.00 | 01-AUG-00:10 |
September | 24499.05 | 18-SEP-07:10 | 5557.43 | 01-SEP-05:10 | 47562.27 | 01-SEP-07:10 | 923.06 | 18-SEP-07:19 | 22636.81 | 05-SEP-15:30 | 0.73 | 01-SEP-05:30 | 5758.69 | 25-SEP-06:10 |
October | 26828.79 | 13-OCT-07:10 | 5557.43 | 01-OCT-05:10 | 47562.27 | 02-OCT-07:10 | 926.41 | 13-OCT-07:19 | 18716.51 | 02-OCT-12:09 | 0.73 | 01-OCT-05:10 | 16873.96 | 25-OCT-06:10 |
November | 28079.40 | 22-NOV-16:00 | 5557.43 | 01-NOV-05:10 | 47562.27 | 01-NOV-07:10 | 926.51 | 28-NOV-16:00 | 12911.56 | 09-NOV-16:30 | 0.73 | 27-NOV-08:09 | 63014.45 | 28-NOV-07:10 |
December | 28079.40 | 01-DEC-16:00 | 5557.43 | 01-DEC-06:10 | 47562.27 | 01-DEC-08:09 | 926.57 | 11-DEC-16:00 | 5048.62 | 07-DEC-14:00 | 0.73 | 04-DEC-07:10 | 86722.52 | 27-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 23688.37 | 5557.43 | 47562.27 | 921.90 | 5048.62 | 0.73 | 0.00 | |||||||
Maximum of Months | 28079.40 | 5557.43 | 47562.27 | 926.57 | 35506.99 | 0.73 | 86722.52 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 10966.06 | 03-JAN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18354.96 | 21-FEB-16:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23790.02 | 21-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 49490.79 | 21-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 63148.73 | 30-MAY-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 74289.26 | 15-JUN-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 77389.61 | 20-JUL-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 72412.29 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 59052.31 | 05-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 58382.89 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25117.96 | 03-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5330.74 | 20-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5330.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 77389.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 108150.73 | 17-JAN-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 3365.18 | 0.73 | 67758.39 | 0.00 | 0.00 |
February | 102864.56 | 03-FEB-07:10 | 9359.67 | 21853.28 | 0.00 | 256.05 | 3405.18 | 0.73 | 67989.64 | 0.00 | 0.00 |
March | 103025.81 | 02-MAR-08:09 | 23688.37 | 47562.27 | 0.00 | 899.47 | 3447.34 | 0.73 | 27427.63 | 0.00 | 0.00 |
April | 138960.96 | 21-APR-15:09 | 23688.37 | 43769.98 | 0.00 | 920.43 | 21207.99 | 0.73 | 0.00 | 49373.46 | 0.00 |
May | 159184.02 | 30-MAY-15:00 | 23688.37 | 43769.98 | 0.00 | 920.43 | 28922.15 | 0.73 | 0.00 | 61882.37 | 0.00 |
June | 168125.76 | 15-JUN-14:30 | 23688.37 | 42286.04 | 0.00 | 919.86 | 27101.42 | 0.73 | 0.00 | 74129.35 | 0.00 |
July | 181276.11 | 20-JUL-15:09 | 23688.37 | 43769.98 | 0.00 | 920.43 | 35506.99 | 0.73 | 0.00 | 77389.61 | 0.00 |
August | 162737.06 | 07-AUG-15:00 | 23688.37 | 43769.98 | 0.00 | 920.43 | 21945.27 | 0.73 | 0.00 | 72412.29 | 0.00 |
September | 150068.62 | 05-SEP-15:30 | 23688.37 | 43769.98 | 0.00 | 920.43 | 22636.81 | 0.73 | 0.00 | 59052.31 | 0.00 |
October | 138789.19 | 05-OCT-15:00 | 23688.37 | 43769.98 | 0.00 | 920.43 | 18486.59 | 0.73 | 0.00 | 51923.09 | 0.00 |
November | 106379.20 | 09-NOV-16:10 | 24836.87 | 43769.98 | 0.00 | 921.80 | 12789.41 | 0.73 | 0.00 | 24060.41 | 0.00 |
December | 121811.11 | 27-DEC-07:10 | 9359.67 | 21853.28 | 0.00 | 256.05 | 3618.86 | 0.73 | 86722.52 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 102864.56 | 9359.67 | 21853.28 | 0.00 | 256.05 | 3365.18 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 181276.11 | 24836.87 | 47562.27 | 5557.43 | 921.80 | 35506.99 | 0.73 | 86722.52 | 77389.61 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 43437.91 | 27-JAN-07:19 | 0.00 | 9222.10 | 27-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 45131.73 | 03-FEB-07:10 | 0.00 | 9219.53 | 03-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 34947.64 | 02-MAR-07:19 | 0.00 | 9178.89 | 02-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 10979.98 | 12-APR-06:10 | 0.00 | 9060.43 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 8940.88 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 8812.51 | 02-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 8713.86 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 8720.97 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 8804.42 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 3782.64 | 25-OCT-06:10 | 0.00 | 8939.88 | 31-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 27279.49 | 28-NOV-07:19 | 0.00 | 9082.73 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 46154.01 | 27-DEC-07:19 | 0.00 | 9172.92 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8713.86 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 46154.01 | 0.00 | 9222.10 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.16 | 0.00 | 26.16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.28 | 0.00 | 26.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.80 | 0.17 | 24.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.25 | 0.00 | 26.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 25.95 | 0.17 | 25.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.28 | 0.17 | 26.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.61 | 0.17 | 24.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 25.65 | 0.17 | 25.39 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.17 | 26.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.93 | 0.67 | 24.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.17 | 25.29 | 0.67 | 25.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.17 | 0.67 | 26.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.42 | 2.33 | 27.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.52 | 3.50 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.47 | 5.50 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.45 | 4.00 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
Annual Sum or Average | 0.67 | 17.04 | 0.00 | 17.04 | 24.17 | 27.19 | 15.33 | 27.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 17.20 | 0.00 | 17.20 | 8.83 | 27.52 | 5.50 | 27.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.68 | 2.50 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.78 | 10.17 | 27.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.88 | 10.17 | 27.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 27.83 | 15.33 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.91 | 9.50 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.66 | 8.50 | 27.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.48 | 0.50 | 27.48 |
November | 0.17 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 |
December | 0.67 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
Annual Sum or Average | 1.33 | 17.11 | 0.00 | 17.11 | 63.17 | 27.59 | 56.67 | 27.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 17.23 | 0.00 | 17.23 | 17.83 | 27.91 | 15.33 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.55 | 1.17 | 27.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.54 | 2.67 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.54 | 4.67 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.54 | 4.00 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.57 | 7.17 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.76 | 6.00 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.85 | 7.00 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.98 | 6.50 | 27.98 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.53 | 2.83 | 27.53 |
December | 0.50 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
Annual Sum or Average | 0.50 | 17.11 | 0.00 | 17.11 | 49.17 | 27.58 | 42.00 | 27.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 17.11 | 0.00 | 17.11 | 9.50 | 27.98 | 7.17 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.40 | 0.33 | 27.38 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.07 | 3.67 | 28.07 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.27 | 5.00 | 28.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.30 | 4.33 | 28.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 28.15 | 6.50 | 28.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.32 | 4.67 | 28.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.07 | 4.33 | 28.11 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.90 | 2.33 | 27.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
Annual Sum or Average | 0.50 | 16.99 | 0.00 | 16.99 | 54.33 | 28.08 | 31.17 | 28.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 16.99 | 0.00 | 16.99 | 13.17 | 28.32 | 6.50 | 28.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.49 | 0.83 | 27.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.58 | 3.50 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.62 | 5.67 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.63 | 9.00 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.66 | 7.67 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.59 | 6.17 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.44 | 0.67 | 27.44 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 34.33 | 27.62 | 33.50 | 27.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.66 | 9.00 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.67 | 18.10 | 25.67 | 18.10 | 0.00 | 18.10 | 0.00 | 18.10 |
February | 18.17 | 17.96 | 18.17 | 17.96 | 0.83 | 18.17 | 0.83 | 18.37 |
March | 23.00 | 18.61 | 23.00 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
April | 5.00 | 18.96 | 5.00 | 18.96 | 0.83 | 19.39 | 0.83 | 19.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.93 | 8.33 | 24.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 25.73 | 32.50 | 25.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 25.47 | 29.83 | 25.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 25.52 | 34.00 | 25.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | 25.64 | 33.17 | 25.63 |
October | 1.50 | 20.16 | 1.50 | 20.16 | 15.33 | 25.31 | 14.83 | 25.75 |
November | 17.00 | 19.21 | 17.00 | 19.21 | 5.50 | 20.36 | 5.50 | 21.24 |
December | 27.50 | 17.88 | 27.50 | 17.88 | 0.17 | 17.91 | 0.17 | 17.93 |
Annual Sum or Average | 117.83 | 18.35 | 117.83 | 18.35 | 161.17 | 21.33 | 160.00 | 22.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.91 | 0.00 | 17.93 |
Maximum of Months | 27.50 | 20.16 | 27.50 | 20.16 | 34.17 | 25.73 | 34.00 | 25.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.75 | 1.50 | 27.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.82 | 4.00 | 27.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.94 | 3.33 | 27.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.82 | 4.83 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.95 | 4.00 | 28.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.79 | 4.33 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.66 | 2.50 | 27.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 38.83 | 27.84 | 24.50 | 27.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.95 | 4.83 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.38 | 1.17 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.26 | 0.83 | 27.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.33 | 0.33 | 27.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.00 | 27.32 | 2.33 | 27.35 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.38 | 1.17 | 27.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.76 | 2.50 | 27.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.71 | 7.50 | 27.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.78 | 9.17 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.74 | 12.67 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.81 | 7.67 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.76 | 4.67 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.56 | 0.67 | 27.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 46.17 | 27.76 | 44.83 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.81 | 12.67 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.50 | 1.83 | 27.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.43 | 1.67 | 27.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.33 | 1.50 | 27.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.46 | 1.33 | 27.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.43 | 3.83 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.53 | 5.67 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.71 | 6.83 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.87 | 7.00 | 27.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.59 | 4.83 | 27.59 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 36.83 | 27.60 | 35.00 | 27.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.87 | 7.00 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.43 | 0.33 | 27.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.93 | 3.00 | 27.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.09 | 4.83 | 28.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.16 | 4.17 | 28.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.00 | 5.33 | 28.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.20 | 4.00 | 28.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.97 | 4.00 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.71 | 2.83 | 27.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 45.67 | 28.04 | 28.50 | 28.07 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.20 | 5.33 | 28.26 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 413.33 | 23.95 | 0.00 | 23.95 | 0.00 | 23.95 |
February | 344.67 | 24.03 | 7.17 | 24.04 | 0.00 | 24.04 |
March | 357.17 | 24.00 | 6.17 | 24.03 | 0.00 | 24.03 |
April | 120.50 | 24.01 | 78.67 | 24.56 | 0.00 | 24.56 |
May | 15.00 | 24.00 | 218.50 | 24.70 | 0.00 | 24.70 |
June | 0.00 | 0.00 | 343.17 | 24.50 | 0.00 | 24.50 |
July | 27.33 | 24.48 | 496.33 | 24.42 | 27.33 | 24.43 |
August | 0.00 | 0.00 | 502.50 | 24.38 | 0.00 | 24.38 |
September | 7.50 | 26.09 | 436.17 | 24.50 | 7.50 | 24.52 |
October | 4.00 | 24.00 | 288.83 | 24.66 | 0.00 | 24.66 |
November | 191.00 | 23.99 | 65.67 | 24.23 | 0.00 | 24.23 |
December | 449.50 | 23.99 | 0.00 | 23.99 | 0.00 | 23.99 |
Annual Sum or Average | 1930.00 | 24.01 | 2443.17 | 24.30 | 34.83 | 24.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.95 | 0.00 | 23.95 |
Maximum of Months | 449.50 | 26.09 | 502.50 | 24.70 | 27.33 | 24.70 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.67 | 22.97 | 0.00 | 22.97 | 0.00 | 22.97 |
February | 449.17 | 23.31 | 0.00 | 23.31 | 0.00 | 23.31 |
March | 502.67 | 23.65 | 0.00 | 23.65 | 0.00 | 23.65 |
April | 230.33 | 23.88 | 23.83 | 23.99 | 0.00 | 23.99 |
May | 44.50 | 23.96 | 171.67 | 24.42 | 0.00 | 24.42 |
June | 1.50 | 24.00 | 316.33 | 24.41 | 0.00 | 24.41 |
July | 43.00 | 24.27 | 493.67 | 24.33 | 43.00 | 24.32 |
August | 5.83 | 24.00 | 488.17 | 24.30 | 5.83 | 24.29 |
September | 21.67 | 24.52 | 406.67 | 24.36 | 16.50 | 24.37 |
October | 88.83 | 23.73 | 200.00 | 24.17 | 2.33 | 24.17 |
November | 395.00 | 23.48 | 11.50 | 23.51 | 0.00 | 23.51 |
December | 497.00 | 22.83 | 0.83 | 22.82 | 0.83 | 22.82 |
Annual Sum or Average | 2781.17 | 23.35 | 2112.67 | 23.79 | 68.50 | 23.79 |
Minimum of Months | 1.50 | 22.83 | 0.00 | 22.82 | 0.00 | 22.82 |
Maximum of Months | 502.67 | 24.52 | 493.67 | 24.42 | 43.00 | 24.42 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.98 | 77.33 | 21.79 | 77.33 | 21.65 |
February | 454.00 | 22.50 | 39.50 | 22.37 | 39.50 | 22.26 |
March | 513.17 | 23.13 | 5.17 | 23.11 | 5.17 | 23.08 |
April | 273.33 | 23.66 | 23.17 | 23.73 | 0.00 | 23.73 |
May | 77.67 | 23.81 | 180.50 | 24.29 | 0.00 | 24.29 |
June | 5.33 | 24.00 | 337.83 | 24.41 | 0.00 | 24.41 |
July | 36.17 | 24.14 | 495.33 | 24.34 | 36.17 | 24.33 |
August | 4.67 | 24.00 | 483.83 | 24.30 | 4.67 | 24.30 |
September | 36.83 | 23.96 | 385.67 | 24.27 | 15.17 | 24.28 |
October | 214.50 | 23.46 | 137.50 | 23.73 | 1.83 | 23.73 |
November | 444.83 | 22.70 | 18.67 | 22.63 | 18.67 | 22.56 |
December | 497.00 | 21.72 | 127.67 | 21.49 | 127.67 | 21.33 |
Annual Sum or Average | 3059.50 | 22.67 | 2312.17 | 23.21 | 326.17 | 23.09 |
Minimum of Months | 4.67 | 21.72 | 5.17 | 21.49 | 0.00 | 21.33 |
Maximum of Months | 513.17 | 24.14 | 495.33 | 24.41 | 127.67 | 24.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.87 | 282.33 | 20.66 | 282.33 | 20.56 |
February | 454.00 | 21.44 | 177.33 | 21.18 | 177.33 | 21.03 |
March | 512.67 | 22.23 | 104.83 | 21.95 | 104.83 | 21.75 |
April | 298.33 | 23.12 | 53.17 | 23.21 | 10.83 | 23.13 |
May | 107.00 | 23.67 | 222.83 | 24.27 | 3.33 | 24.30 |
June | 17.83 | 25.68 | 403.33 | 24.55 | 10.17 | 24.60 |
July | 89.00 | 25.18 | 496.67 | 24.62 | 89.00 | 24.69 |
August | 35.33 | 24.70 | 478.50 | 24.40 | 25.33 | 24.44 |
September | 91.67 | 23.65 | 354.33 | 24.18 | 34.33 | 24.19 |
October | 304.50 | 22.84 | 115.50 | 23.20 | 7.50 | 23.21 |
November | 467.67 | 21.62 | 134.67 | 21.33 | 134.67 | 21.14 |
December | 497.00 | 20.65 | 339.67 | 20.49 | 339.67 | 20.42 |
Annual Sum or Average | 3377.00 | 21.94 | 3163.17 | 22.49 | 1219.33 | 22.26 |
Minimum of Months | 17.83 | 20.65 | 53.17 | 20.49 | 3.33 | 20.42 |
Maximum of Months | 512.67 | 25.68 | 496.67 | 24.62 | 339.67 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.24 | 187.50 | 20.96 | 187.50 | 20.79 |
February | 435.67 | 21.94 | 102.00 | 21.64 | 102.00 | 21.43 |
March | 411.50 | 22.45 | 64.33 | 22.23 | 60.00 | 22.03 |
April | 172.67 | 23.21 | 133.00 | 23.86 | 10.33 | 23.86 |
May | 81.33 | 24.68 | 322.33 | 24.62 | 28.50 | 24.78 |
June | 41.00 | 26.49 | 441.67 | 24.70 | 34.33 | 24.85 |
July | 117.83 | 25.74 | 496.67 | 24.82 | 117.83 | 24.97 |
August | 61.00 | 25.72 | 487.00 | 24.58 | 51.50 | 24.72 |
September | 92.00 | 24.93 | 402.67 | 24.52 | 57.50 | 24.68 |
October | 208.83 | 22.63 | 179.83 | 23.46 | 5.17 | 23.47 |
November | 445.50 | 22.06 | 95.33 | 21.83 | 83.00 | 21.63 |
December | 497.00 | 21.01 | 244.83 | 20.75 | 244.83 | 20.63 |
Annual Sum or Average | 3066.33 | 22.32 | 3157.17 | 22.98 | 982.50 | 22.85 |
Minimum of Months | 41.00 | 21.01 | 64.33 | 20.75 | 5.17 | 20.63 |
Maximum of Months | 502.00 | 26.49 | 496.67 | 24.82 | 244.83 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 383.00 | 21.67 | 157.67 | 21.47 | 133.50 | 21.21 |
February | 323.33 | 21.95 | 111.83 | 21.91 | 85.00 | 21.67 |
March | 352.00 | 22.38 | 93.17 | 22.29 | 70.83 | 22.05 |
April | 228.33 | 23.09 | 110.83 | 23.53 | 13.50 | 23.48 |
May | 117.00 | 23.74 | 239.17 | 24.29 | 10.83 | 24.37 |
June | 26.67 | 25.17 | 388.33 | 24.52 | 11.00 | 24.59 |
July | 93.17 | 25.23 | 495.50 | 24.61 | 93.17 | 24.69 |
August | 49.33 | 25.28 | 475.33 | 24.49 | 37.33 | 24.59 |
September | 96.17 | 24.63 | 395.00 | 24.48 | 57.83 | 24.61 |
October | 198.83 | 23.33 | 258.00 | 24.02 | 27.83 | 24.17 |
November | 302.33 | 22.03 | 150.67 | 22.34 | 68.00 | 22.09 |
December | 393.67 | 21.63 | 162.67 | 21.31 | 153.17 | 21.08 |
Annual Sum or Average | 2563.83 | 22.54 | 3038.17 | 23.24 | 762.00 | 23.10 |
Minimum of Months | 26.67 | 21.63 | 93.17 | 21.31 | 10.83 | 21.08 |
Maximum of Months | 393.67 | 25.28 | 495.50 | 24.61 | 153.17 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 485.83 | 21.16 | 233.00 | 20.87 | 233.00 | 20.72 |
February | 421.00 | 21.53 | 162.17 | 21.31 | 155.17 | 21.14 |
March | 413.50 | 21.97 | 114.83 | 21.82 | 99.83 | 21.62 |
April | 252.33 | 22.88 | 116.67 | 23.35 | 19.17 | 23.35 |
May | 131.67 | 23.87 | 275.67 | 24.34 | 23.17 | 24.49 |
June | 40.33 | 25.38 | 397.33 | 24.58 | 20.67 | 24.70 |
July | 93.83 | 25.25 | 493.00 | 24.60 | 93.83 | 24.69 |
August | 62.17 | 24.78 | 467.00 | 24.45 | 40.17 | 24.54 |
September | 110.17 | 23.94 | 373.50 | 24.27 | 51.67 | 24.36 |
October | 268.83 | 22.73 | 182.67 | 23.41 | 12.83 | 23.47 |
November | 413.50 | 21.60 | 137.67 | 21.44 | 116.17 | 21.25 |
December | 493.83 | 21.03 | 276.50 | 20.75 | 276.50 | 20.62 |
Annual Sum or Average | 3187.00 | 22.07 | 3230.00 | 22.71 | 1142.17 | 22.53 |
Minimum of Months | 40.33 | 21.03 | 114.83 | 20.75 | 12.83 | 20.62 |
Maximum of Months | 493.83 | 25.38 | 493.00 | 24.60 | 276.50 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.31 | 147.33 | 21.17 | 147.33 | 21.08 |
February | 454.00 | 21.55 | 130.00 | 21.37 | 130.00 | 21.25 |
March | 514.00 | 22.04 | 68.67 | 21.88 | 68.67 | 21.76 |
April | 403.67 | 23.25 | 4.67 | 23.23 | 3.83 | 23.21 |
May | 149.00 | 23.69 | 146.17 | 24.03 | 0.00 | 24.03 |
June | 9.17 | 23.97 | 333.50 | 24.41 | 0.00 | 24.41 |
July | 47.50 | 24.45 | 495.00 | 24.43 | 47.50 | 24.43 |
August | 10.00 | 24.29 | 497.17 | 24.35 | 10.00 | 24.35 |
September | 36.50 | 24.09 | 396.00 | 24.32 | 19.67 | 24.33 |
October | 217.00 | 23.54 | 149.67 | 23.80 | 3.33 | 23.81 |
November | 457.17 | 22.51 | 13.83 | 22.46 | 13.83 | 22.41 |
December | 497.00 | 21.34 | 167.83 | 21.17 | 167.83 | 21.07 |
Annual Sum or Average | 3297.00 | 22.21 | 2549.83 | 22.82 | 612.00 | 22.67 |
Minimum of Months | 9.17 | 21.31 | 4.67 | 21.17 | 0.00 | 21.07 |
Maximum of Months | 514.00 | 24.45 | 497.17 | 24.43 | 167.83 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.92 | 71.67 | 21.76 | 71.67 | 21.63 |
February | 442.83 | 22.35 | 46.83 | 22.18 | 46.83 | 22.05 |
March | 486.50 | 22.83 | 30.67 | 22.70 | 30.67 | 22.59 |
April | 211.33 | 23.52 | 89.83 | 24.02 | 0.67 | 24.02 |
May | 59.50 | 24.19 | 274.83 | 24.57 | 8.50 | 24.62 |
June | 16.83 | 26.42 | 427.33 | 24.58 | 13.50 | 24.66 |
July | 81.67 | 25.64 | 496.33 | 24.74 | 81.67 | 24.85 |
August | 30.00 | 26.49 | 507.33 | 24.58 | 30.00 | 24.68 |
September | 48.33 | 25.92 | 441.83 | 24.64 | 42.33 | 24.77 |
October | 118.50 | 23.49 | 236.67 | 24.15 | 2.83 | 24.16 |
November | 386.50 | 22.98 | 24.67 | 23.04 | 4.17 | 23.02 |
December | 497.00 | 21.97 | 77.33 | 21.79 | 77.33 | 21.65 |
Annual Sum or Average | 2881.00 | 22.76 | 2725.33 | 23.47 | 410.17 | 23.44 |
Minimum of Months | 16.83 | 21.92 | 24.67 | 21.76 | 0.67 | 21.63 |
Maximum of Months | 502.00 | 26.49 | 507.33 | 24.74 | 81.67 | 24.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 405.33 | 21.84 | 67.67 | 21.81 | 42.50 | 21.58 |
February | 378.83 | 22.04 | 60.17 | 22.08 | 34.33 | 21.86 |
March | 447.00 | 22.29 | 62.67 | 22.18 | 44.83 | 21.97 |
April | 307.00 | 22.99 | 57.00 | 23.23 | 7.33 | 23.15 |
May | 152.33 | 23.28 | 151.33 | 23.92 | 0.00 | 23.92 |
June | 26.17 | 23.25 | 325.00 | 24.50 | 2.00 | 24.50 |
July | 90.83 | 24.20 | 494.17 | 24.47 | 90.83 | 24.43 |
August | 45.67 | 24.13 | 497.33 | 24.44 | 41.33 | 24.43 |
September | 74.83 | 24.74 | 432.33 | 24.63 | 56.17 | 24.72 |
October | 108.67 | 23.70 | 305.83 | 24.41 | 32.17 | 24.55 |
November | 263.67 | 22.46 | 109.17 | 23.05 | 16.17 | 22.93 |
December | 406.50 | 21.89 | 72.83 | 21.74 | 55.83 | 21.47 |
Annual Sum or Average | 2706.83 | 22.51 | 2635.50 | 23.37 | 423.50 | 23.29 |
Minimum of Months | 26.17 | 21.84 | 57.00 | 21.74 | 0.00 | 21.47 |
Maximum of Months | 447.00 | 24.74 | 497.33 | 24.63 | 90.83 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.67 | 21.80 | 82.33 | 21.64 | 82.33 | 21.52 |
February | 443.67 | 22.00 | 70.33 | 21.86 | 67.50 | 21.73 |
March | 464.17 | 22.44 | 38.67 | 22.38 | 32.50 | 22.28 |
April | 271.17 | 23.31 | 75.83 | 23.67 | 1.33 | 23.68 |
May | 105.83 | 23.91 | 252.33 | 24.37 | 8.17 | 24.43 |
June | 19.33 | 25.85 | 393.50 | 24.54 | 11.83 | 24.61 |
July | 71.17 | 25.30 | 495.67 | 24.62 | 71.17 | 24.69 |
August | 28.67 | 26.01 | 504.50 | 24.53 | 28.67 | 24.60 |
September | 45.33 | 25.17 | 435.33 | 24.54 | 35.33 | 24.62 |
October | 105.67 | 23.68 | 240.00 | 24.21 | 9.67 | 24.27 |
November | 375.67 | 22.75 | 35.83 | 22.85 | 5.33 | 22.82 |
December | 497.00 | 21.83 | 100.50 | 21.64 | 100.50 | 21.50 |
Annual Sum or Average | 2921.33 | 22.55 | 2724.83 | 23.30 | 454.33 | 23.24 |
Minimum of Months | 19.33 | 21.80 | 35.83 | 21.64 | 1.33 | 21.50 |
Maximum of Months | 497.00 | 26.01 | 504.50 | 24.62 | 100.50 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.41 | 145.33 | 21.22 | 145.33 | 21.11 |
February | 454.00 | 21.98 | 79.50 | 21.78 | 79.50 | 21.64 |
March | 514.00 | 22.71 | 33.33 | 22.60 | 33.33 | 22.49 |
April | 280.50 | 23.49 | 31.50 | 23.59 | 0.00 | 23.59 |
May | 77.17 | 23.83 | 215.17 | 24.37 | 0.00 | 24.37 |
June | 3.83 | 25.49 | 388.83 | 24.53 | 1.67 | 24.54 |
July | 73.17 | 24.69 | 496.83 | 24.53 | 73.17 | 24.55 |
August | 17.67 | 24.42 | 491.50 | 24.38 | 17.67 | 24.38 |
September | 58.00 | 24.00 | 385.33 | 24.28 | 33.33 | 24.29 |
October | 256.50 | 23.35 | 137.50 | 23.63 | 5.83 | 23.64 |
November | 457.17 | 22.28 | 44.67 | 22.13 | 44.67 | 22.01 |
December | 497.00 | 21.22 | 208.50 | 21.02 | 208.50 | 20.91 |
Annual Sum or Average | 3191.00 | 22.34 | 2658.00 | 22.95 | 643.00 | 22.80 |
Minimum of Months | 3.83 | 21.22 | 31.50 | 21.02 | 0.00 | 20.91 |
Maximum of Months | 514.00 | 25.49 | 496.83 | 24.53 | 208.50 | 24.55 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 426.50 | 21.68 | 92.33 | 21.46 | 92.33 | 21.31 |
February | 363.00 | 22.27 | 51.00 | 22.14 | 45.17 | 21.98 |
March | 358.33 | 22.76 | 36.50 | 22.75 | 23.33 | 22.63 |
April | 155.00 | 23.51 | 103.17 | 24.14 | 4.33 | 24.19 |
May | 57.67 | 24.78 | 252.33 | 24.78 | 18.83 | 24.91 |
June | 28.67 | 26.79 | 361.83 | 24.81 | 26.50 | 24.95 |
July | 106.67 | 25.67 | 421.67 | 24.90 | 106.67 | 25.03 |
August | 42.17 | 26.05 | 417.83 | 24.66 | 40.50 | 24.78 |
September | 60.50 | 25.29 | 345.50 | 24.64 | 44.33 | 24.77 |
October | 171.67 | 23.16 | 168.50 | 23.85 | 4.50 | 23.87 |
November | 360.17 | 22.46 | 41.67 | 22.42 | 26.50 | 22.30 |
December | 422.00 | 21.52 | 124.83 | 21.27 | 124.83 | 21.12 |
Annual Sum or Average | 2552.33 | 22.66 | 2417.17 | 23.37 | 557.83 | 23.33 |
Minimum of Months | 28.67 | 21.52 | 36.50 | 21.27 | 4.33 | 21.12 |
Maximum of Months | 426.50 | 26.79 | 421.67 | 24.90 | 124.83 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 357.50 | 22.22 | 89.33 | 22.24 | 55.83 | 22.04 |
February | 303.83 | 22.54 | 61.33 | 22.69 | 30.33 | 22.54 |
March | 335.50 | 22.93 | 37.83 | 23.07 | 13.83 | 22.99 |
April | 197.00 | 23.48 | 95.17 | 23.94 | 1.00 | 23.95 |
May | 81.33 | 23.84 | 232.17 | 24.40 | 1.67 | 24.41 |
June | 9.33 | 24.97 | 379.67 | 24.51 | 2.67 | 24.53 |
July | 86.67 | 24.98 | 496.17 | 24.58 | 86.67 | 24.63 |
August | 33.33 | 25.74 | 494.67 | 24.50 | 33.33 | 24.57 |
September | 72.50 | 25.30 | 423.00 | 24.58 | 58.17 | 24.71 |
October | 150.67 | 23.97 | 288.83 | 24.35 | 29.17 | 24.49 |
November | 269.17 | 22.71 | 111.00 | 23.23 | 19.00 | 23.15 |
December | 361.33 | 22.19 | 92.67 | 22.04 | 75.50 | 21.81 |
Annual Sum or Average | 2258.17 | 22.97 | 2801.83 | 23.71 | 407.17 | 23.68 |
Minimum of Months | 9.33 | 22.19 | 37.83 | 22.04 | 1.00 | 21.81 |
Maximum of Months | 361.33 | 25.74 | 496.17 | 24.58 | 86.67 | 24.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 476.83 | 21.62 | 124.17 | 21.41 | 122.67 | 21.26 |
February | 416.00 | 22.02 | 74.17 | 21.89 | 67.17 | 21.74 |
March | 411.50 | 22.53 | 41.83 | 22.56 | 25.33 | 22.46 |
April | 227.83 | 23.34 | 102.50 | 23.79 | 5.67 | 23.84 |
May | 100.83 | 24.21 | 279.00 | 24.48 | 19.00 | 24.60 |
June | 25.67 | 26.16 | 402.17 | 24.61 | 18.17 | 24.71 |
July | 97.50 | 25.14 | 495.83 | 24.61 | 97.50 | 24.68 |
August | 42.33 | 25.45 | 490.83 | 24.49 | 38.83 | 24.57 |
September | 75.00 | 24.53 | 400.83 | 24.41 | 50.00 | 24.49 |
October | 213.33 | 23.30 | 208.33 | 23.84 | 13.17 | 23.90 |
November | 392.33 | 22.20 | 64.50 | 22.20 | 38.83 | 22.08 |
December | 492.67 | 21.56 | 160.50 | 21.30 | 160.50 | 21.14 |
Annual Sum or Average | 2971.83 | 22.49 | 2844.67 | 23.19 | 656.83 | 23.11 |
Minimum of Months | 25.67 | 21.56 | 41.83 | 21.30 | 5.67 | 21.14 |
Maximum of Months | 492.67 | 26.16 | 495.83 | 24.61 | 160.50 | 24.71 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.06323 | 20.09618 | 0.18978 | 5.88750 |
February | 454.00000 | 24.15969 | 16.89619 | 0.20313 | 5.99287 |
March | 514.00000 | 24.23530 | 16.37820 | 0.23412 | 6.28658 |
April | 485.00000 | 24.37575 | 20.39641 | 0.32642 | 7.47553 |
May | 508.00000 | 24.37597 | 29.23576 | -0.4400 | 9.55224 |
June | 496.00000 | 24.37271 | 35.41828 | -0.3771 | 8.43637 |
July | 497.00000 | 24.41862 | 47.43267 | -0.2795 | 7.05874 |
August | 514.00000 | 24.37360 | 45.14526 | -0.3080 | 7.37508 |
September | 485.00000 | 24.42644 | 42.60092 | -0.3160 | 7.66201 |
October | 502.00000 | 24.40593 | 34.38555 | 0.44589 | 9.48770 |
November | 489.00000 | 24.30641 | 21.54865 | 0.29710 | 7.08404 |
December | 497.00000 | 24.06090 | 17.43355 | 0.16925 | 5.73449 |
Annual Sum or Average | 5943.00000 | 24.29851 | 29.00766 | 0.00981 | 7.34683 |
Minimum of Months | 454.00000 | 24.06090 | 16.37820 | -0.4400 | 5.73449 |
Maximum of Months | 514.00000 | 24.42644 | 47.43267 | 0.44589 | 9.55224 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.96836 | 22.85218 | -0.0695 | 5.60952 |
February | 454.00000 | 23.31577 | 18.86764 | 0.00060 | 5.48612 |
March | 514.00000 | 23.68366 | 17.81357 | 0.09459 | 5.48516 |
April | 485.00000 | 24.09293 | 21.32756 | 0.25098 | 6.56533 |
May | 508.00000 | 24.24847 | 30.35247 | -0.4981 | 10.61062 |
June | 496.00000 | 24.29641 | 36.72538 | -0.4164 | 9.00663 |
July | 497.00000 | 24.33018 | 50.02395 | -0.3135 | 7.36396 |
August | 514.00000 | 24.28530 | 47.38728 | -0.3496 | 7.83227 |
September | 485.00000 | 24.30175 | 44.54085 | -0.3760 | 8.36788 |
October | 502.00000 | 24.13241 | 35.79312 | 0.36401 | 8.01708 |
November | 489.00000 | 23.62546 | 23.49917 | 0.11815 | 5.87863 |
December | 497.00000 | 22.82652 | 19.95561 | -0.1232 | 5.92279 |
Annual Sum or Average | 5943.00000 | 23.84593 | 30.85496 | -0.1115 | 7.19412 |
Minimum of Months | 454.00000 | 22.82652 | 17.81357 | -0.4981 | 5.48516 |
Maximum of Months | 514.00000 | 24.33018 | 50.02395 | 0.36401 | 10.61062 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.97518 | 24.08657 | -0.3113 | 8.16213 |
February | 454.00000 | 22.49762 | 19.65989 | -0.1978 | 6.98371 |
March | 514.00000 | 23.13073 | 18.38017 | -0.0397 | 5.92148 |
April | 485.00000 | 23.89989 | 21.26393 | 0.20368 | 6.37096 |
May | 508.00000 | 24.20538 | 30.07236 | -0.5063 | 10.94771 |
June | 496.00000 | 24.30087 | 36.28436 | -0.3982 | 8.73224 |
July | 497.00000 | 24.35810 | 48.98738 | -0.2935 | 7.16522 |
August | 514.00000 | 24.28454 | 46.43804 | -0.3461 | 7.82949 |
September | 485.00000 | 24.23528 | 43.96353 | -0.4006 | 8.84863 |
October | 502.00000 | 23.83813 | 36.11657 | 0.28544 | 7.18770 |
November | 489.00000 | 22.81986 | 24.59584 | -0.0811 | 6.60187 |
December | 497.00000 | 21.72211 | 20.90998 | -0.3948 | 9.53864 |
Annual Sum or Average | 5943.00000 | 23.44600 | 30.98428 | -0.2075 | 7.86614 |
Minimum of Months | 454.00000 | 21.72211 | 18.38017 | -0.5063 | 5.92148 |
Maximum of Months | 514.00000 | 24.35810 | 48.98738 | 0.28544 | 10.94771 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.87057 | 25.59820 | -0.5973 | 13.89600 |
February | 454.00000 | 21.44372 | 21.72726 | -0.4593 | 11.22046 |
March | 514.00000 | 22.23182 | 19.69192 | -0.2584 | 8.37569 |
April | 485.00000 | 23.54522 | 21.91301 | 0.12053 | 6.82617 |
May | 508.00000 | 24.19215 | 29.82278 | -0.4902 | 11.59661 |
June | 496.00000 | 24.41351 | 35.96884 | -0.3094 | 7.92452 |
July | 497.00000 | 24.51808 | 49.52154 | -0.1886 | 6.75742 |
August | 514.00000 | 24.33551 | 46.78109 | -0.3001 | 7.76830 |
September | 485.00000 | 24.13982 | 44.94630 | -0.4188 | 10.06969 |
October | 502.00000 | 23.33012 | 38.33513 | 0.16632 | 6.97365 |
November | 489.00000 | 21.72076 | 26.55182 | -0.3512 | 10.02659 |
December | 497.00000 | 20.65495 | 22.91567 | -0.6766 | 16.24915 |
Annual Sum or Average | 5943.00000 | 22.96117 | 32.05927 | -0.3131 | 9.79675 |
Minimum of Months | 454.00000 | 20.65495 | 19.69192 | -0.6766 | 6.75742 |
Maximum of Months | 514.00000 | 24.51808 | 49.52154 | 0.16632 | 16.24915 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.24430 | 24.89089 | -0.4833 | 11.75285 |
February | 454.00000 | 22.03672 | 20.75849 | -0.2908 | 9.24159 |
March | 514.00000 | 22.79869 | 18.42298 | -0.0892 | 7.60762 |
April | 485.00000 | 23.95449 | 20.88654 | 0.27402 | 8.29987 |
May | 508.00000 | 24.35089 | 29.33419 | -0.3463 | 9.74240 |
June | 496.00000 | 24.47544 | 35.68820 | -0.1995 | 7.36966 |
July | 497.00000 | 24.59996 | 49.00065 | -0.0822 | 6.94391 |
August | 514.00000 | 24.39189 | 46.42733 | -0.1956 | 7.37708 |
September | 485.00000 | 24.29995 | 44.08346 | -0.2765 | 8.74967 |
October | 502.00000 | 23.57876 | 37.23131 | 0.26411 | 8.35927 |
November | 489.00000 | 22.23718 | 25.54167 | -0.2027 | 8.58305 |
December | 497.00000 | 21.00558 | 22.32274 | -0.5663 | 13.56934 |
Annual Sum or Average | 5943.00000 | 23.25681 | 31.29630 | -0.1827 | 8.96177 |
Minimum of Months | 454.00000 | 21.00558 | 18.42298 | -0.5663 | 6.94391 |
Maximum of Months | 514.00000 | 24.59996 | 49.00065 | 0.27402 | 13.56934 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.30207 | 22.70908 | -0.2051 | 10.38628 |
February | 454.00000 | 22.69042 | 19.27968 | -0.1166 | 9.41722 |
March | 514.00000 | 23.00194 | 17.76621 | -0.0350 | 8.16824 |
April | 485.00000 | 23.75945 | 21.15062 | 0.20513 | 7.90303 |
May | 508.00000 | 24.17003 | 29.76525 | -0.4812 | 11.85413 |
June | 496.00000 | 24.37566 | 36.03737 | -0.3244 | 8.23672 |
July | 497.00000 | 24.48942 | 49.53511 | -0.1925 | 6.91598 |
August | 514.00000 | 24.35220 | 46.52837 | -0.2559 | 7.61488 |
September | 485.00000 | 24.28946 | 44.01295 | -0.2820 | 8.95316 |
October | 502.00000 | 23.86551 | 36.08169 | 0.36322 | 10.15304 |
November | 489.00000 | 22.96720 | 23.61354 | 0.00730 | 9.42924 |
December | 497.00000 | 22.17386 | 20.23952 | -0.2618 | 11.08949 |
Annual Sum or Average | 5943.00000 | 23.54243 | 30.64748 | -0.1326 | 9.17733 |
Minimum of Months | 454.00000 | 22.17386 | 17.76621 | -0.4812 | 6.91598 |
Maximum of Months | 514.00000 | 24.48942 | 49.53511 | 0.36322 | 11.85413 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.25292 | 24.49924 | -0.4865 | 12.65796 |
February | 454.00000 | 21.75518 | 20.74690 | -0.3624 | 10.67680 |
March | 514.00000 | 22.43017 | 18.67654 | -0.1719 | 8.68675 |
April | 485.00000 | 23.56771 | 21.49026 | 0.18153 | 8.27465 |
May | 508.00000 | 24.14506 | 29.78302 | -0.4235 | 11.85072 |
June | 496.00000 | 24.38317 | 35.96832 | -0.2469 | 8.07711 |
July | 497.00000 | 24.47556 | 49.47964 | -0.1384 | 7.10850 |
August | 514.00000 | 24.30792 | 46.74312 | -0.2364 | 8.00339 |
September | 485.00000 | 24.13287 | 44.70777 | -0.3347 | 9.92066 |
October | 502.00000 | 23.40431 | 37.60976 | 0.23316 | 8.43630 |
November | 489.00000 | 21.99899 | 25.31954 | -0.2523 | 9.78556 |
December | 497.00000 | 21.04751 | 21.94456 | -0.5650 | 14.48353 |
Annual Sum or Average | 5943.00000 | 23.08517 | 31.49566 | -0.2333 | 9.82380 |
Minimum of Months | 454.00000 | 21.04751 | 18.67654 | -0.5650 | 7.10850 |
Maximum of Months | 514.00000 | 24.47556 | 49.47964 | 0.23316 | 14.48353 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.30989 | 24.97383 | -0.4666 | 10.13850 |
February | 454.00000 | 21.54761 | 21.64145 | -0.4273 | 9.66169 |
March | 514.00000 | 22.04048 | 20.39108 | -0.3104 | 7.94480 |
April | 485.00000 | 23.39134 | 22.98620 | 0.05720 | 5.96703 |
May | 508.00000 | 24.07747 | 30.42872 | -0.5784 | 12.79824 |
June | 496.00000 | 24.30254 | 36.02163 | -0.4002 | 8.76516 |
July | 497.00000 | 24.42984 | 48.43343 | -0.2575 | 6.85522 |
August | 514.00000 | 24.33681 | 45.91296 | -0.3174 | 7.52658 |
September | 485.00000 | 24.28054 | 43.81251 | -0.3741 | 8.51719 |
October | 502.00000 | 23.85533 | 37.03974 | 0.29348 | 7.25556 |
November | 489.00000 | 22.60353 | 25.45175 | -0.1246 | 6.50195 |
December | 497.00000 | 21.33825 | 22.02859 | -0.4748 | 10.40633 |
Annual Sum or Average | 5943.00000 | 23.13640 | 31.67150 | -0.2818 | 8.53152 |
Minimum of Months | 454.00000 | 21.30989 | 20.39108 | -0.5784 | 5.96703 |
Maximum of Months | 514.00000 | 24.42984 | 48.43343 | 0.29348 | 12.79824 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.92079 | 24.34196 | -0.3040 | 8.03635 |
February | 454.00000 | 22.40837 | 20.75232 | -0.2023 | 7.33885 |
March | 514.00000 | 22.91879 | 19.06096 | -0.0769 | 6.61011 |
April | 485.00000 | 24.04276 | 21.45405 | 0.26156 | 7.46760 |
May | 508.00000 | 24.35068 | 29.53713 | -0.3985 | 9.71270 |
June | 496.00000 | 24.44723 | 35.48201 | -0.2641 | 7.48529 |
July | 497.00000 | 24.59521 | 47.71402 | -0.1260 | 6.58592 |
August | 514.00000 | 24.45677 | 45.38418 | -0.1924 | 6.80853 |
September | 485.00000 | 24.46116 | 42.92695 | -0.2228 | 7.37444 |
October | 502.00000 | 24.11616 | 35.96192 | 0.39589 | 9.02670 |
November | 489.00000 | 23.24160 | 24.28682 | 0.05040 | 6.37037 |
December | 497.00000 | 21.96654 | 21.48428 | -0.3093 | 8.16227 |
Annual Sum or Average | 5943.00000 | 23.58433 | 30.77830 | -0.1162 | 7.58620 |
Minimum of Months | 454.00000 | 21.92079 | 19.06096 | -0.3985 | 6.37037 |
Maximum of Months | 514.00000 | 24.59521 | 47.71402 | 0.39589 | 9.71270 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.38319 | 21.31038 | -0.1286 | 8.41735 |
February | 454.00000 | 22.53392 | 18.66404 | -0.1188 | 8.27820 |
March | 514.00000 | 22.60382 | 17.70332 | -0.1170 | 7.66667 |
April | 485.00000 | 23.53668 | 21.20560 | 0.12897 | 6.99977 |
May | 508.00000 | 24.00823 | 29.55927 | -0.5858 | 13.68906 |
June | 496.00000 | 24.36503 | 35.06973 | -0.3968 | 9.10540 |
July | 497.00000 | 24.51641 | 49.40050 | -0.2235 | 6.74075 |
August | 514.00000 | 24.43715 | 45.91615 | -0.2455 | 7.20200 |
September | 485.00000 | 24.47362 | 42.91473 | -0.2187 | 7.74402 |
October | 502.00000 | 24.20478 | 35.21040 | 0.46456 | 10.98959 |
November | 489.00000 | 23.41108 | 22.37130 | 0.16148 | 8.41863 |
December | 497.00000 | 22.38792 | 18.67786 | -0.1434 | 8.52508 |
Annual Sum or Average | 5943.00000 | 23.57771 | 29.92274 | -0.1200 | 8.66027 |
Minimum of Months | 454.00000 | 22.38319 | 17.70332 | -0.5858 | 6.74075 |
Maximum of Months | 514.00000 | 24.51641 | 49.40050 | 0.46456 | 13.68906 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.84333 | 24.11168 | -0.3206 | 8.53241 |
February | 454.00000 | 22.08135 | 20.89491 | -0.2813 | 8.24337 |
March | 514.00000 | 22.63897 | 19.27873 | -0.1420 | 7.06805 |
April | 485.00000 | 23.79737 | 21.96518 | 0.19685 | 7.12204 |
May | 508.00000 | 24.24045 | 29.84721 | -0.4472 | 10.77340 |
June | 496.00000 | 24.39177 | 35.70043 | -0.2995 | 7.90115 |
July | 497.00000 | 24.51632 | 48.07786 | -0.1668 | 6.61282 |
August | 514.00000 | 24.43473 | 45.55054 | -0.2142 | 6.97739 |
September | 485.00000 | 24.42110 | 43.19754 | -0.2447 | 7.39337 |
October | 502.00000 | 24.13947 | 36.00925 | 0.40499 | 9.18436 |
November | 489.00000 | 23.08659 | 24.19774 | 0.01884 | 6.55958 |
December | 497.00000 | 21.83427 | 21.36047 | -0.3397 | 8.77504 |
Annual Sum or Average | 5943.00000 | 23.46091 | 30.92824 | -0.1531 | 7.93251 |
Minimum of Months | 454.00000 | 21.83427 | 19.27873 | -0.4472 | 6.55958 |
Maximum of Months | 514.00000 | 24.51632 | 48.07786 | 0.40499 | 10.77340 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.40997 | 25.08355 | -0.4374 | 9.93809 |
February | 454.00000 | 21.97527 | 21.32978 | -0.3117 | 8.29567 |
March | 514.00000 | 22.71361 | 19.41815 | -0.1347 | 6.59413 |
April | 485.00000 | 23.79311 | 21.93384 | 0.17874 | 6.42220 |
May | 508.00000 | 24.26052 | 30.05900 | -0.4760 | 10.63719 |
June | 496.00000 | 24.42014 | 36.31089 | -0.3263 | 7.94634 |
July | 497.00000 | 24.50818 | 50.30076 | -0.2065 | 6.66218 |
August | 514.00000 | 24.35673 | 47.50304 | -0.3004 | 7.47066 |
September | 485.00000 | 24.24290 | 45.26375 | -0.3863 | 8.87260 |
October | 502.00000 | 23.70868 | 37.73484 | 0.25960 | 7.05610 |
November | 489.00000 | 22.39467 | 25.82364 | -0.1753 | 7.23156 |
December | 497.00000 | 21.22431 | 22.47996 | -0.5044 | 11.33629 |
Annual Sum or Average | 5943.00000 | 23.26009 | 32.01865 | -0.2352 | 8.20649 |
Minimum of Months | 454.00000 | 21.22431 | 19.41815 | -0.5044 | 6.42220 |
Maximum of Months | 514.00000 | 24.50818 | 50.30076 | 0.25960 | 11.33629 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.68490 | 23.89504 | -0.3588 | 9.06463 |
February | 385.00000 | 22.41160 | 19.63853 | -0.1912 | 7.68348 |
March | 433.00000 | 23.06263 | 17.76948 | -0.0259 | 6.83364 |
April | 410.00000 | 24.10968 | 20.70571 | 0.29580 | 8.14727 |
May | 430.00000 | 24.46564 | 29.19736 | -0.3445 | 9.48224 |
June | 418.00000 | 24.56907 | 35.39955 | -0.2197 | 7.58644 |
July | 422.00000 | 24.70106 | 49.21009 | -0.0921 | 6.99407 |
August | 433.00000 | 24.49213 | 46.47330 | -0.2015 | 7.30952 |
September | 410.00000 | 24.43018 | 43.99537 | -0.2650 | 8.33816 |
October | 427.00000 | 23.85437 | 36.62566 | 0.32185 | 8.43866 |
November | 417.00000 | 22.71434 | 24.26159 | -0.0795 | 7.09278 |
December | 422.00000 | 21.51845 | 21.25354 | -0.4219 | 10.10870 |
Annual Sum or Average | 5034.00000 | 23.50673 | 30.78116 | -0.1321 | 8.09269 |
Minimum of Months | 385.00000 | 21.51845 | 17.76948 | -0.4219 | 6.83364 |
Maximum of Months | 433.00000 | 24.70106 | 49.21009 | 0.32185 | 10.10870 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.84343 | 22.01897 | -0.0528 | 8.22546 |
February | 454.00000 | 23.18869 | 18.71824 | 0.01757 | 7.72189 |
March | 514.00000 | 23.42665 | 17.41672 | 0.07309 | 7.03560 |
April | 485.00000 | 24.01220 | 21.14287 | 0.26132 | 7.55155 |
May | 508.00000 | 24.27554 | 29.94789 | -0.4580 | 10.59955 |
June | 496.00000 | 24.40211 | 36.35081 | -0.3358 | 8.14417 |
July | 497.00000 | 24.50512 | 50.28006 | -0.2036 | 6.77026 |
August | 514.00000 | 24.39540 | 47.20291 | -0.2526 | 7.21499 |
September | 485.00000 | 24.40133 | 44.28966 | -0.2526 | 7.86986 |
October | 502.00000 | 24.16611 | 35.64183 | 0.43666 | 10.41596 |
November | 489.00000 | 23.50077 | 22.94400 | 0.14941 | 8.33972 |
December | 497.00000 | 22.76963 | 19.58581 | -0.0931 | 8.43908 |
Annual Sum or Average | 5943.00000 | 23.82810 | 30.55352 | -0.0607 | 8.19942 |
Minimum of Months | 454.00000 | 22.76963 | 17.41672 | -0.4580 | 6.77026 |
Maximum of Months | 514.00000 | 24.50512 | 50.28006 | 0.43666 | 10.59955 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.74831 | 24.01821 | -0.3375 | 9.29954 |
February | 454.00000 | 22.22720 | 20.41586 | -0.2281 | 8.15465 |
March | 514.00000 | 22.89296 | 18.44630 | -0.0543 | 7.08382 |
April | 485.00000 | 23.86072 | 21.49538 | 0.24592 | 7.82822 |
May | 508.00000 | 24.26804 | 29.93048 | -0.3974 | 10.34992 |
June | 496.00000 | 24.42173 | 36.23501 | -0.2574 | 7.77964 |
July | 497.00000 | 24.50170 | 50.17943 | -0.1484 | 6.79708 |
August | 514.00000 | 24.36884 | 47.37984 | -0.2288 | 7.39167 |
September | 485.00000 | 24.28092 | 44.93521 | -0.2945 | 8.40579 |
October | 502.00000 | 23.80669 | 37.09667 | 0.32858 | 8.53278 |
November | 489.00000 | 22.60164 | 24.68003 | -0.0928 | 7.50476 |
December | 497.00000 | 21.57895 | 21.54350 | -0.4026 | 10.33454 |
Annual Sum or Average | 5943.00000 | 23.38830 | 31.44776 | -0.1558 | 8.29019 |
Minimum of Months | 454.00000 | 21.57895 | 18.44630 | -0.4026 | 6.79708 |
Maximum of Months | 514.00000 | 24.50170 | 50.17943 | 0.32858 | 10.34992 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.923983E+09 | 0.253961E+09 | 48.28 | 0.917586E+09 | 6396527.43 | 0.00 | 0.55 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 | 16845.57 | 03-JAN-15:00 | 16845.57 | 03-JAN-15:00 | 475.72 | 01-JAN-15:00 | 4356.14 | 03-JAN-15:00 | 0.00 |
February | 0.330910E+10 | 0.869549E+09 | 99.39 | 0.329359E+10 | 15508088.29 | 0.00 | 0.86 | 21-FEB-16:20 | 0.00 | 01-FEB-00:10 | 28428.43 | 21-FEB-16:20 | 28428.43 | 21-FEB-16:20 | 743.97 | 27-FEB-16:20 | 6761.19 | 21-FEB-16:20 | 0.00 |
March | 0.834563E+10 | 0.214935E+10 | 197.50 | 0.832886E+10 | 16773670.72 | 0.00 | 1.00 | 21-MAR-15:30 | 0.00 | 01-MAR-00:10 | 35050.63 | 21-MAR-16:00 | 35050.63 | 21-MAR-16:00 | 460.07 | 25-MAR-11:30 | 8235.88 | 21-MAR-16:00 | 0.00 |
April | 0.258519E+11 | 0.664908E+10 | 327.88 | 0.256911E+11 | 0.160802E+09 | 0.00 | 1.00 | 03-APR-11:40 | 0.00 | 01-APR-00:10 | 56592.67 | 21-APR-15:10 | 56592.67 | 21-APR-15:10 | 3323.40 | 18-APR-21:00 | 16063.66 | 21-APR-15:10 | 0.00 |
May | 0.507966E+11 | 0.133169E+11 | 450.40 | 0.495404E+11 | 0.125627E+10 | 0.00 | 1.00 | 02-MAY-14:20 | 0.00 | 01-MAY-00:10 | 68796.77 | 30-MAY-15:30 | 68796.77 | 30-MAY-15:30 | 13812.72 | 22-MAY-11:10 | 20802.57 | 30-MAY-15:30 | 0.00 |
June | 0.698736E+11 | 0.197705E+11 | 467.77 | 0.674525E+11 | 0.242105E+10 | 0.00 | 1.00 | 01-JUN-07:15 | 0.00 | 01-JUN-00:10 | 76456.57 | 19-JUN-06:03 | 76408.91 | 15-JUN-06:03 | 21025.30 | 28-JUN-06:03 | 24602.98 | 05-JUN-16:00 | 0.00 |
July | 0.822728E+11 | 0.221054E+11 | 478.63 | 0.667648E+11 | 0.155080E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 117341.85 | 20-JUL-14:55 | 87822.65 | 03-JUL-06:03 | 76641.96 | 17-JUL-06:03 | 26466.14 | 20-JUL-15:20 | 0.00 |
August | 0.761776E+11 | 0.201321E+11 | 493.55 | 0.660113E+11 | 0.101662E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 110788.97 | 03-AUG-06:03 | 84201.40 | 07-AUG-06:03 | 63893.24 | 03-AUG-06:03 | 25304.99 | 03-AUG-06:03 | 0.00 |
September | 0.630229E+11 | 0.161681E+11 | 435.15 | 0.550358E+11 | 0.798706E+10 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 97242.94 | 14-SEP-09:50 | 68371.84 | 18-SEP-16:00 | 54816.70 | 22-SEP-06:03 | 22447.39 | 14-SEP-09:50 | 0.00 |
October | 0.326102E+11 | 0.808720E+10 | 346.55 | 0.292740E+11 | 0.333617E+10 | 0.00 | 1.00 | 01-OCT-14:22 | 0.00 | 01-OCT-00:10 | 74433.29 | 04-OCT-10:40 | 70424.39 | 02-OCT-04:02 | 26708.81 | 04-OCT-10:30 | 19930.36 | 03-OCT-14:00 | 0.00 |
November | 0.716611E+10 | 0.182427E+10 | 158.39 | 0.703251E+10 | 0.133606E+09 | 0.00 | 1.00 | 03-NOV-14:10 | 0.00 | 01-NOV-00:10 | 41795.47 | 03-NOV-16:00 | 41795.47 | 03-NOV-16:00 | 3024.35 | 03-NOV-11:10 | 9567.97 | 03-NOV-16:00 | 0.00 |
December | 0.318776E+09 | 91080071.32 | 27.83 | 0.317690E+09 | 1085821.32 | 0.00 | 0.28 | 08-DEC-14:00 | 0.00 | 01-DEC-00:10 | 7904.85 | 08-DEC-14:00 | 7904.85 | 08-DEC-14:00 | 406.18 | 10-DEC-12:55 | 2191.82 | 08-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.420669E+12 | 0.111418E+12 | 3531.33 | 0.379660E+12 | 0.410090E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.318776E+09 | 91080071.32 | 27.83 | 0.317690E+09 | 1085821.32 | 0.00 | 0.28 | 0.00 | 7904.85 | 7904.85 | 406.18 | 2191.82 | 0.00 | ||||||
Maximum of Months | 0.822728E+11 | 0.221054E+11 | 493.55 | 0.674525E+11 | 0.155080E+11 | 0.00 | 1.00 | 0.00 | 117341.85 | 87822.65 | 76641.96 | 26466.14 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.720285E+09 | 0.199673E+09 | 47.33 | 0.713037E+09 | 7247524.78 | 0.00 | 0.47 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 | 12690.02 | 03-JAN-15:00 | 12690.02 | 03-JAN-15:00 | 482.46 | 12-JAN-17:13 | 3350.29 | 03-JAN-15:00 | 0.00 |
February | 0.302278E+10 | 0.802497E+09 | 106.78 | 0.300752E+10 | 15267437.89 | 0.00 | 0.82 | 21-FEB-16:00 | 0.00 | 01-FEB-00:10 | 24126.91 | 21-FEB-16:00 | 24126.91 | 21-FEB-16:00 | 784.05 | 27-FEB-16:00 | 5801.58 | 21-FEB-16:00 | 0.00 |
March | 0.754883E+10 | 0.195131E+10 | 205.96 | 0.754218E+10 | 6650426.18 | 0.00 | 1.00 | 21-MAR-15:30 | 0.00 | 01-MAR-00:10 | 31369.96 | 21-MAR-16:00 | 31369.96 | 21-MAR-16:00 | 317.50 | 11-MAR-16:00 | 7371.08 | 21-MAR-16:00 | 0.00 |
April | 0.242080E+11 | 0.622938E+10 | 341.71 | 0.240859E+11 | 0.122142E+09 | 0.00 | 1.00 | 03-APR-11:40 | 0.00 | 01-APR-00:10 | 54482.13 | 21-APR-15:00 | 54482.13 | 21-APR-15:00 | 3047.79 | 18-APR-21:00 | 15545.39 | 21-APR-15:00 | 0.00 |
May | 0.461985E+11 | 0.121099E+11 | 451.47 | 0.453327E+11 | 0.865847E+09 | 0.00 | 1.00 | 01-MAY-14:20 | 0.00 | 01-MAY-00:10 | 67402.28 | 30-MAY-06:03 | 67402.28 | 30-MAY-06:03 | 8698.94 | 28-MAY-07:53 | 19852.41 | 30-MAY-14:40 | 0.00 |
June | 0.635638E+11 | 0.180027E+11 | 469.25 | 0.618977E+11 | 0.166606E+10 | 0.00 | 1.00 | 01-JUN-07:30 | 0.00 | 01-JUN-00:10 | 73133.16 | 19-JUN-06:03 | 72284.96 | 15-JUN-04:02 | 18039.17 | 19-JUN-18:00 | 23265.21 | 15-JUN-14:30 | 0.00 |
July | 0.715056E+11 | 0.191895E+11 | 478.50 | 0.593301E+11 | 0.121755E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 105436.91 | 20-JUL-14:55 | 80071.33 | 03-JUL-06:03 | 69011.82 | 17-JUL-06:03 | 23715.85 | 20-JUL-15:05 | 0.00 |
August | 0.634172E+11 | 0.168260E+11 | 485.19 | 0.563683E+11 | 0.704884E+10 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 90811.84 | 03-AUG-05:03 | 73619.17 | 07-AUG-04:02 | 50113.42 | 03-AUG-05:03 | 22208.67 | 07-AUG-16:00 | 0.00 |
September | 0.507899E+11 | 0.131004E+11 | 423.87 | 0.452671E+11 | 0.552280E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 | 78848.65 | 14-SEP-09:50 | 61631.07 | 18-SEP-15:30 | 47969.14 | 22-SEP-05:03 | 18208.69 | 14-SEP-09:50 | 0.00 |
October | 0.259039E+11 | 0.647518E+10 | 336.06 | 0.234486E+11 | 0.245526E+10 | 0.00 | 1.00 | 01-OCT-14:32 | 0.00 | 01-OCT-00:10 | 65602.08 | 02-OCT-04:02 | 65602.08 | 02-OCT-04:02 | 19723.60 | 04-OCT-10:30 | 17877.98 | 03-OCT-14:00 | 0.00 |
November | 0.567970E+10 | 0.146550E+10 | 157.33 | 0.554025E+10 | 0.139450E+09 | 0.00 | 1.00 | 03-NOV-14:50 | 0.00 | 01-NOV-00:10 | 33643.96 | 03-NOV-16:00 | 33643.96 | 03-NOV-16:00 | 3214.54 | 03-NOV-11:00 | 7703.44 | 03-NOV-16:00 | 0.00 |
December | 0.257877E+09 | 73903728.86 | 27.00 | 0.257254E+09 | 622928.43 | 0.00 | 0.23 | 23-DEC-15:00 | 0.00 | 01-DEC-00:10 | 5762.80 | 23-DEC-15:00 | 5762.80 | 23-DEC-15:00 | 266.80 | 10-DEC-12:55 | 1617.37 | 23-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.362816E+12 | 0.964259E+11 | 3530.46 | 0.332791E+12 | 0.300257E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.257877E+09 | 73903728.86 | 27.00 | 0.257254E+09 | 622928.43 | 0.00 | 0.23 | 0.00 | 5762.80 | 5762.80 | 266.80 | 1617.37 | 0.00 | ||||||
Maximum of Months | 0.715056E+11 | 0.191895E+11 | 485.19 | 0.618977E+11 | 0.121755E+11 | 0.00 | 1.00 | 0.00 | 105436.91 | 80071.33 | 69011.82 | 23715.85 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.685892E+09 | 0.192388E+09 | 45.83 | 0.668913E+09 | 16978717.64 | 0.00 | 0.40 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 | 12118.83 | 03-JAN-15:00 | 12118.83 | 03-JAN-15:00 | 708.24 | 12-JAN-17:02 | 3259.63 | 03-JAN-15:00 | 0.00 |
February | 0.293737E+10 | 0.791304E+09 | 103.61 | 0.291142E+10 | 25958244.15 | 0.00 | 0.77 | 20-FEB-14:32 | 0.00 | 01-FEB-00:10 | 25639.89 | 20-FEB-14:32 | 25639.89 | 20-FEB-14:32 | 961.49 | 27-FEB-15:00 | 6255.01 | 20-FEB-14:32 | 0.00 |
March | 0.763200E+10 | 0.199925E+10 | 205.28 | 0.761090E+10 | 21101660.80 | 0.00 | 0.98 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 | 34660.07 | 21-MAR-16:00 | 34660.07 | 21-MAR-16:00 | 487.20 | 15-MAR-09:40 | 8183.07 | 21-MAR-16:00 | 0.00 |
April | 0.266224E+11 | 0.690100E+10 | 342.23 | 0.264252E+11 | 0.197133E+09 | 0.00 | 1.00 | 03-APR-11:50 | 0.00 | 01-APR-00:10 | 63580.07 | 21-APR-14:40 | 63580.07 | 21-APR-14:40 | 3851.23 | 30-APR-08:13 | 18140.54 | 21-APR-14:40 | 0.00 |
May | 0.512109E+11 | 0.135249E+11 | 447.61 | 0.500156E+11 | 0.119522E+10 | 0.00 | 1.00 | 02-MAY-14:40 | 0.00 | 01-MAY-00:10 | 77319.40 | 21-MAY-14:42 | 77319.40 | 21-MAY-14:42 | 12316.89 | 24-MAY-11:00 | 23622.81 | 21-MAY-14:42 | 0.00 |
June | 0.714198E+11 | 0.203791E+11 | 466.47 | 0.692821E+11 | 0.213771E+10 | 0.00 | 1.00 | 01-JUN-08:00 | 0.00 | 01-JUN-00:10 | 81693.86 | 15-JUN-04:02 | 81693.86 | 15-JUN-04:02 | 20378.60 | 19-JUN-18:00 | 27684.69 | 15-JUN-14:40 | 0.00 |
July | 0.792052E+11 | 0.214207E+11 | 478.61 | 0.660903E+11 | 0.131149E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 121283.21 | 20-JUL-14:55 | 82811.25 | 03-JUL-14:30 | 78823.59 | 20-JUL-14:55 | 27458.76 | 03-JUL-14:00 | 0.00 |
August | 0.698478E+11 | 0.187011E+11 | 484.12 | 0.617975E+11 | 0.805026E+10 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 82058.10 | 02-AUG-05:03 | 79538.15 | 07-AUG-15:00 | 49381.87 | 02-AUG-05:03 | 25680.40 | 07-AUG-16:00 | 0.00 |
September | 0.550140E+11 | 0.143092E+11 | 418.67 | 0.488296E+11 | 0.618432E+10 | 0.00 | 1.00 | 01-SEP-07:20 | 0.00 | 01-SEP-00:10 | 84102.84 | 14-SEP-10:00 | 71121.80 | 18-SEP-15:20 | 49174.86 | 22-SEP-05:03 | 20813.96 | 19-SEP-15:20 | 0.00 |
October | 0.268524E+11 | 0.678918E+10 | 329.64 | 0.240021E+11 | 0.285027E+10 | 0.00 | 1.00 | 01-OCT-11:42 | 0.00 | 01-OCT-00:10 | 72523.08 | 03-OCT-13:50 | 68602.58 | 02-OCT-04:02 | 19004.43 | 04-OCT-10:40 | 20636.92 | 03-OCT-13:50 | 0.00 |
November | 0.525726E+10 | 0.138341E+10 | 151.83 | 0.506060E+10 | 0.196663E+09 | 0.00 | 0.97 | 09-NOV-15:00 | 0.00 | 01-NOV-00:10 | 34220.39 | 09-NOV-15:00 | 34220.39 | 09-NOV-15:00 | 3107.73 | 02-NOV-15:00 | 7883.00 | 09-NOV-15:00 | 0.00 |
December | 0.243756E+09 | 70151216.77 | 25.33 | 0.241105E+09 | 2651320.58 | 0.00 | 0.20 | 23-DEC-15:00 | 0.00 | 01-DEC-00:10 | 5823.16 | 23-DEC-15:00 | 5823.16 | 23-DEC-15:00 | 206.02 | 08-DEC-16:20 | 1644.80 | 23-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.396929E+12 | 0.106462E+12 | 3499.23 | 0.362936E+12 | 0.339932E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.243756E+09 | 70151216.77 | 25.33 | 0.241105E+09 | 2651320.58 | 0.00 | 0.20 | 0.00 | 5823.16 | 5823.16 | 206.02 | 1644.80 | 0.00 | ||||||
Maximum of Months | 0.792052E+11 | 0.214207E+11 | 484.12 | 0.692821E+11 | 0.131149E+11 | 0.00 | 1.00 | 0.00 | 121283.21 | 82811.25 | 78823.59 | 27684.69 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 263.16 | 0.00 | 263.16 | 60.79 | 1343.53 | 0.00 | 0.00 | 0.00 |
February | 321.34 | 0.00 | 321.34 | 148.07 | 1216.26 | 0.00 | 0.00 | 0.00 |
March | 420.53 | 0.00 | 420.53 | 290.19 | 1040.12 | 0.00 | 0.00 | 0.00 |
April | 485.55 | 3.83 | 481.72 | 552.19 | 621.98 | 0.00 | 0.00 | 0.00 |
May | 575.88 | 41.64 | 534.24 | 925.38 | 370.70 | 0.00 | 0.00 | 0.00 |
June | 612.35 | 75.39 | 536.96 | 1296.72 | 203.91 | 0.00 | 0.00 | 0.00 |
July | 565.93 | 55.09 | 510.84 | 1190.16 | 163.89 | 0.00 | 0.00 | 0.00 |
August | 477.20 | 9.76 | 467.44 | 924.95 | 219.35 | 0.00 | 0.00 | 0.00 |
September | 416.40 | 0.17 | 416.24 | 700.67 | 436.78 | 0.00 | 0.00 | 0.00 |
October | 345.73 | 0.00 | 345.73 | 363.30 | 691.22 | 0.00 | 0.00 | 0.00 |
November | 279.10 | 0.00 | 279.10 | 99.72 | 1161.10 | 0.00 | 0.00 | 0.00 |
December | 261.12 | 0.00 | 261.12 | 43.21 | 1483.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 419.17 | 15.57 | 403.60 | 551.68 | 743.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 261.12 | 0.00 | 261.12 | 43.21 | 163.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 612.35 | 75.39 | 536.96 | 1296.72 | 1483.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 469.23 | 254.54 | 214.69 | 460.02 | 824.61 | 0.00 | 0.00 | 0.00 |
February | 627.78 | 357.83 | 269.95 | 709.69 | 745.49 | 0.00 | 0.00 | 0.00 |
March | 775.10 | 427.06 | 348.05 | 950.10 | 642.12 | 0.00 | 0.00 | 0.00 |
April | 933.96 | 518.14 | 415.82 | 1355.80 | 394.15 | 0.00 | 0.00 | 0.00 |
May | 963.80 | 523.79 | 440.01 | 1578.29 | 246.80 | 0.00 | 0.00 | 0.00 |
June | 964.34 | 536.48 | 427.86 | 1788.60 | 133.24 | 0.00 | 0.00 | 0.00 |
July | 864.80 | 452.10 | 412.70 | 1609.01 | 108.75 | 0.00 | 0.00 | 0.00 |
August | 822.91 | 421.16 | 401.75 | 1475.22 | 144.85 | 0.00 | 0.00 | 0.00 |
September | 815.28 | 465.17 | 350.10 | 1363.20 | 274.85 | 0.00 | 0.00 | 0.00 |
October | 627.00 | 338.38 | 288.62 | 882.53 | 439.93 | 0.00 | 0.00 | 0.00 |
November | 562.05 | 327.21 | 234.84 | 623.88 | 713.67 | 0.00 | 0.00 | 0.00 |
December | 468.82 | 248.39 | 220.43 | 436.72 | 904.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 741.34 | 405.64 | 335.70 | 1104.01 | 463.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 468.82 | 248.39 | 214.69 | 436.72 | 108.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 964.34 | 536.48 | 440.01 | 1788.60 | 904.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1800.20 | 1363.84 | 436.36 | 2404.17 | 1234.47 | 0.00 | 0.00 | 0.00 |
February | 1669.89 | 1177.25 | 492.65 | 2265.62 | 1129.02 | 0.00 | 0.00 | 0.00 |
March | 1357.13 | 782.52 | 574.62 | 1892.91 | 1013.90 | 0.00 | 0.00 | 0.00 |
April | 920.13 | 343.32 | 576.81 | 1450.17 | 647.19 | 0.00 | 0.00 | 0.00 |
May | 650.25 | 91.01 | 559.24 | 1143.34 | 394.88 | 0.00 | 0.00 | 0.00 |
June | 561.00 | 35.60 | 525.41 | 1228.46 | 207.88 | 0.00 | 0.00 | 0.00 |
July | 571.88 | 53.01 | 518.87 | 1239.61 | 169.21 | 0.00 | 0.00 | 0.00 |
August | 728.99 | 192.97 | 536.02 | 1482.73 | 230.93 | 0.00 | 0.00 | 0.00 |
September | 1137.86 | 591.16 | 546.71 | 2097.51 | 446.42 | 0.00 | 0.00 | 0.00 |
October | 1546.02 | 1045.21 | 500.81 | 2432.01 | 688.62 | 0.00 | 0.00 | 0.00 |
November | 1860.49 | 1418.40 | 442.10 | 2605.36 | 1076.71 | 0.00 | 0.00 | 0.00 |
December | 1843.82 | 1384.05 | 459.77 | 2420.36 | 1329.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1218.05 | 703.86 | 514.19 | 1885.89 | 711.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 561.00 | 35.60 | 436.36 | 1143.34 | 169.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1860.49 | 1418.40 | 576.81 | 2605.36 | 1329.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 494.28 | 278.36 | 215.92 | 542.17 | 869.95 | 0.00 | 0.00 | 0.00 |
February | 557.74 | 296.45 | 261.29 | 652.45 | 796.61 | 0.00 | 0.00 | 0.00 |
March | 760.04 | 407.36 | 352.69 | 976.65 | 688.86 | 0.00 | 0.00 | 0.00 |
April | 873.61 | 471.85 | 401.76 | 1307.32 | 432.34 | 0.00 | 0.00 | 0.00 |
May | 940.96 | 503.45 | 437.50 | 1570.66 | 273.69 | 0.00 | 0.00 | 0.00 |
June | 915.95 | 491.97 | 423.99 | 1727.43 | 149.34 | 0.00 | 0.00 | 0.00 |
July | 812.84 | 403.92 | 408.93 | 1536.95 | 120.09 | 0.00 | 0.00 | 0.00 |
August | 787.20 | 401.18 | 386.01 | 1430.85 | 158.47 | 0.00 | 0.00 | 0.00 |
September | 805.03 | 448.48 | 356.55 | 1386.53 | 304.82 | 0.00 | 0.00 | 0.00 |
October | 693.00 | 404.46 | 288.54 | 1036.95 | 468.10 | 0.00 | 0.00 | 0.00 |
November | 581.67 | 354.17 | 227.50 | 720.07 | 757.59 | 0.00 | 0.00 | 0.00 |
December | 468.74 | 254.63 | 214.11 | 489.69 | 950.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 724.86 | 393.29 | 331.57 | 1116.74 | 496.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 468.74 | 254.63 | 214.11 | 489.69 | 120.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 940.96 | 503.45 | 437.50 | 1727.43 | 950.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.71 | 0.00 | 87.71 | 17.58 | 479.92 | 0.00 | 0.00 | 0.00 |
February | 107.11 | 0.00 | 107.11 | 50.71 | 417.30 | 0.00 | 0.00 | 0.00 |
March | 140.17 | 0.00 | 140.17 | 104.70 | 345.57 | 0.00 | 0.00 | 0.00 |
April | 161.84 | 1.28 | 160.57 | 195.00 | 201.05 | 0.00 | 0.00 | 0.00 |
May | 191.95 | 13.88 | 178.07 | 319.45 | 117.87 | 0.00 | 0.00 | 0.00 |
June | 204.11 | 25.13 | 178.98 | 442.95 | 62.54 | 0.00 | 0.00 | 0.00 |
July | 188.63 | 18.36 | 170.27 | 404.79 | 52.11 | 0.00 | 0.00 | 0.00 |
August | 159.06 | 3.25 | 155.81 | 311.50 | 74.79 | 0.00 | 0.00 | 0.00 |
September | 138.79 | 0.06 | 138.74 | 233.22 | 154.58 | 0.00 | 0.00 | 0.00 |
October | 115.24 | 0.00 | 115.24 | 117.13 | 253.05 | 0.00 | 0.00 | 0.00 |
November | 93.03 | 0.00 | 93.03 | 27.71 | 433.67 | 0.00 | 0.00 | 0.00 |
December | 87.03 | 0.00 | 87.03 | 10.25 | 543.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.72 | 5.19 | 134.53 | 186.94 | 260.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.03 | 0.00 | 87.03 | 10.25 | 52.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.11 | 25.13 | 178.98 | 442.95 | 543.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.72 | 0.00 | 87.72 | 17.58 | 479.95 | 0.00 | 0.00 | 0.00 |
February | 107.12 | 0.00 | 107.12 | 50.71 | 417.33 | 0.00 | 0.00 | 0.00 |
March | 140.18 | 0.00 | 140.18 | 104.71 | 345.59 | 0.00 | 0.00 | 0.00 |
April | 161.85 | 1.28 | 160.58 | 195.02 | 201.06 | 0.00 | 0.00 | 0.00 |
May | 191.96 | 13.88 | 178.08 | 319.47 | 117.88 | 0.00 | 0.00 | 0.00 |
June | 204.12 | 25.13 | 178.99 | 442.97 | 62.54 | 0.00 | 0.00 | 0.00 |
July | 188.65 | 18.36 | 170.28 | 404.81 | 52.11 | 0.00 | 0.00 | 0.00 |
August | 159.07 | 3.25 | 155.82 | 311.52 | 74.80 | 0.00 | 0.00 | 0.00 |
September | 138.80 | 0.06 | 138.75 | 233.23 | 154.59 | 0.00 | 0.00 | 0.00 |
October | 115.24 | 0.00 | 115.24 | 117.14 | 253.06 | 0.00 | 0.00 | 0.00 |
November | 93.04 | 0.00 | 93.04 | 27.71 | 433.70 | 0.00 | 0.00 | 0.00 |
December | 87.04 | 0.00 | 87.04 | 10.25 | 543.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.72 | 5.19 | 134.53 | 186.95 | 260.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.04 | 0.00 | 87.04 | 10.25 | 52.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.12 | 25.13 | 178.99 | 442.97 | 543.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.72 | 0.00 | 87.72 | 17.58 | 479.95 | 0.00 | 0.00 | 0.00 |
February | 107.12 | 0.00 | 107.12 | 50.71 | 417.33 | 0.00 | 0.00 | 0.00 |
March | 140.18 | 0.00 | 140.18 | 104.71 | 345.59 | 0.00 | 0.00 | 0.00 |
April | 161.85 | 1.28 | 160.58 | 195.02 | 201.06 | 0.00 | 0.00 | 0.00 |
May | 191.96 | 13.88 | 178.08 | 319.47 | 117.88 | 0.00 | 0.00 | 0.00 |
June | 204.12 | 25.13 | 178.99 | 442.97 | 62.54 | 0.00 | 0.00 | 0.00 |
July | 188.65 | 18.36 | 170.28 | 404.81 | 52.11 | 0.00 | 0.00 | 0.00 |
August | 159.07 | 3.25 | 155.82 | 311.52 | 74.80 | 0.00 | 0.00 | 0.00 |
September | 138.80 | 0.06 | 138.75 | 233.23 | 154.59 | 0.00 | 0.00 | 0.00 |
October | 115.24 | 0.00 | 115.24 | 117.14 | 253.06 | 0.00 | 0.00 | 0.00 |
November | 93.04 | 0.00 | 93.04 | 27.71 | 433.70 | 0.00 | 0.00 | 0.00 |
December | 87.04 | 0.00 | 87.04 | 10.25 | 543.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.72 | 5.19 | 134.53 | 186.95 | 260.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.04 | 0.00 | 87.04 | 10.25 | 52.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.12 | 25.13 | 178.99 | 442.97 | 543.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 451.38 | 244.85 | 206.52 | 432.42 | 865.69 | 0.00 | 0.00 | 0.00 |
February | 603.90 | 344.22 | 259.68 | 682.15 | 757.21 | 0.00 | 0.00 | 0.00 |
March | 745.62 | 410.81 | 334.81 | 927.40 | 633.87 | 0.00 | 0.00 | 0.00 |
April | 898.43 | 498.43 | 400.01 | 1323.31 | 384.81 | 0.00 | 0.00 | 0.00 |
May | 927.13 | 503.86 | 423.27 | 1539.27 | 237.78 | 0.00 | 0.00 | 0.00 |
June | 927.65 | 516.07 | 411.59 | 1740.76 | 125.23 | 0.00 | 0.00 | 0.00 |
July | 831.90 | 434.90 | 397.00 | 1562.17 | 106.49 | 0.00 | 0.00 | 0.00 |
August | 791.60 | 405.13 | 386.47 | 1425.77 | 149.59 | 0.00 | 0.00 | 0.00 |
September | 784.26 | 447.48 | 336.79 | 1312.17 | 288.45 | 0.00 | 0.00 | 0.00 |
October | 603.15 | 325.51 | 277.64 | 842.53 | 472.21 | 0.00 | 0.00 | 0.00 |
November | 540.67 | 314.76 | 225.91 | 580.81 | 780.40 | 0.00 | 0.00 | 0.00 |
December | 450.99 | 238.94 | 212.05 | 400.64 | 970.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 713.14 | 390.20 | 322.93 | 1065.34 | 479.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 450.99 | 238.94 | 206.52 | 400.64 | 106.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 927.65 | 516.07 | 423.27 | 1740.76 | 970.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.85 | 9.68 | 8.17 | 17.10 | 34.23 | 0.00 | 0.00 | 0.00 |
February | 23.88 | 13.61 | 10.27 | 26.97 | 29.94 | 0.00 | 0.00 | 0.00 |
March | 29.48 | 16.24 | 13.24 | 36.67 | 25.06 | 0.00 | 0.00 | 0.00 |
April | 35.52 | 19.71 | 15.82 | 52.32 | 15.22 | 0.00 | 0.00 | 0.00 |
May | 36.66 | 19.92 | 16.74 | 60.86 | 9.40 | 0.00 | 0.00 | 0.00 |
June | 36.68 | 20.40 | 16.27 | 68.83 | 4.95 | 0.00 | 0.00 | 0.00 |
July | 32.89 | 17.20 | 15.70 | 61.77 | 4.21 | 0.00 | 0.00 | 0.00 |
August | 31.30 | 16.02 | 15.28 | 56.37 | 5.91 | 0.00 | 0.00 | 0.00 |
September | 31.01 | 17.69 | 13.32 | 51.88 | 11.41 | 0.00 | 0.00 | 0.00 |
October | 23.85 | 12.87 | 10.98 | 33.31 | 18.67 | 0.00 | 0.00 | 0.00 |
November | 21.38 | 12.45 | 8.93 | 22.96 | 30.86 | 0.00 | 0.00 | 0.00 |
December | 17.83 | 9.45 | 8.38 | 15.84 | 38.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.20 | 15.43 | 12.77 | 42.12 | 18.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.83 | 9.45 | 8.17 | 15.84 | 4.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 36.68 | 20.40 | 16.74 | 68.83 | 38.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 600.09 | 454.63 | 145.46 | 805.91 | 454.60 | 0.00 | 0.00 | 0.00 |
February | 556.65 | 392.43 | 164.22 | 764.84 | 401.65 | 0.00 | 0.00 | 0.00 |
March | 452.39 | 260.85 | 191.54 | 646.86 | 345.31 | 0.00 | 0.00 | 0.00 |
April | 306.72 | 114.44 | 192.27 | 496.92 | 213.64 | 0.00 | 0.00 | 0.00 |
May | 216.76 | 30.34 | 186.42 | 392.93 | 126.75 | 0.00 | 0.00 | 0.00 |
June | 187.01 | 11.87 | 175.14 | 417.38 | 64.30 | 0.00 | 0.00 | 0.00 |
July | 190.63 | 17.67 | 172.96 | 419.03 | 54.84 | 0.00 | 0.00 | 0.00 |
August | 243.00 | 64.32 | 178.68 | 496.42 | 80.91 | 0.00 | 0.00 | 0.00 |
September | 379.30 | 197.06 | 182.24 | 700.07 | 162.64 | 0.00 | 0.00 | 0.00 |
October | 515.36 | 348.42 | 166.94 | 810.52 | 256.63 | 0.00 | 0.00 | 0.00 |
November | 620.18 | 472.81 | 147.37 | 865.34 | 407.91 | 0.00 | 0.00 | 0.00 |
December | 614.63 | 461.37 | 153.26 | 805.61 | 494.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 406.03 | 234.63 | 171.40 | 634.25 | 254.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 187.01 | 11.87 | 145.46 | 392.93 | 54.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.18 | 472.81 | 192.27 | 865.34 | 494.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 600.09 | 454.63 | 145.46 | 805.91 | 454.60 | 0.00 | 0.00 | 0.00 |
February | 556.65 | 392.43 | 164.22 | 764.84 | 401.65 | 0.00 | 0.00 | 0.00 |
March | 452.39 | 260.85 | 191.54 | 646.86 | 345.31 | 0.00 | 0.00 | 0.00 |
April | 306.72 | 114.44 | 192.27 | 496.92 | 213.64 | 0.00 | 0.00 | 0.00 |
May | 216.76 | 30.34 | 186.42 | 392.93 | 126.75 | 0.00 | 0.00 | 0.00 |
June | 187.01 | 11.87 | 175.14 | 417.38 | 64.30 | 0.00 | 0.00 | 0.00 |
July | 190.63 | 17.67 | 172.96 | 419.03 | 54.84 | 0.00 | 0.00 | 0.00 |
August | 243.00 | 64.32 | 178.68 | 496.42 | 80.91 | 0.00 | 0.00 | 0.00 |
September | 379.30 | 197.06 | 182.24 | 700.07 | 162.64 | 0.00 | 0.00 | 0.00 |
October | 515.36 | 348.42 | 166.94 | 810.52 | 256.63 | 0.00 | 0.00 | 0.00 |
November | 620.18 | 472.81 | 147.37 | 865.34 | 407.91 | 0.00 | 0.00 | 0.00 |
December | 614.63 | 461.37 | 153.26 | 805.61 | 494.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 406.03 | 234.63 | 171.40 | 634.25 | 254.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 187.01 | 11.87 | 145.46 | 392.93 | 54.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.18 | 472.81 | 192.27 | 865.34 | 494.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 600.05 | 454.60 | 145.45 | 805.86 | 454.57 | 0.00 | 0.00 | 0.00 |
February | 556.61 | 392.40 | 164.21 | 764.79 | 401.63 | 0.00 | 0.00 | 0.00 |
March | 452.36 | 260.83 | 191.53 | 646.82 | 345.29 | 0.00 | 0.00 | 0.00 |
April | 306.70 | 114.44 | 192.26 | 496.89 | 213.62 | 0.00 | 0.00 | 0.00 |
May | 216.74 | 30.34 | 186.41 | 392.91 | 126.74 | 0.00 | 0.00 | 0.00 |
June | 186.99 | 11.86 | 175.13 | 417.35 | 64.30 | 0.00 | 0.00 | 0.00 |
July | 190.62 | 17.67 | 172.95 | 419.01 | 54.83 | 0.00 | 0.00 | 0.00 |
August | 242.99 | 64.32 | 178.67 | 496.39 | 80.90 | 0.00 | 0.00 | 0.00 |
September | 379.28 | 197.05 | 182.23 | 700.03 | 162.63 | 0.00 | 0.00 | 0.00 |
October | 515.32 | 348.39 | 166.93 | 810.47 | 256.61 | 0.00 | 0.00 | 0.00 |
November | 620.14 | 472.78 | 147.36 | 865.29 | 407.88 | 0.00 | 0.00 | 0.00 |
December | 614.59 | 461.34 | 153.25 | 805.56 | 494.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 406.00 | 234.61 | 171.39 | 634.21 | 254.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.99 | 11.86 | 145.45 | 392.91 | 54.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.14 | 472.78 | 192.26 | 865.29 | 494.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 475.48 | 267.77 | 207.70 | 518.83 | 913.17 | 0.00 | 0.00 | 0.00 |
February | 536.53 | 285.17 | 251.35 | 634.27 | 807.68 | 0.00 | 0.00 | 0.00 |
March | 731.13 | 391.86 | 339.27 | 957.47 | 683.31 | 0.00 | 0.00 | 0.00 |
April | 840.37 | 453.90 | 386.48 | 1276.15 | 424.03 | 0.00 | 0.00 | 0.00 |
May | 905.16 | 484.30 | 420.86 | 1531.19 | 265.65 | 0.00 | 0.00 | 0.00 |
June | 881.11 | 473.25 | 407.86 | 1679.43 | 140.78 | 0.00 | 0.00 | 0.00 |
July | 781.92 | 388.55 | 393.37 | 1490.43 | 117.92 | 0.00 | 0.00 | 0.00 |
August | 757.25 | 385.92 | 371.33 | 1382.06 | 164.76 | 0.00 | 0.00 | 0.00 |
September | 774.40 | 431.42 | 342.98 | 1334.31 | 321.10 | 0.00 | 0.00 | 0.00 |
October | 666.64 | 389.07 | 277.57 | 989.49 | 506.53 | 0.00 | 0.00 | 0.00 |
November | 559.54 | 340.70 | 218.84 | 680.17 | 832.15 | 0.00 | 0.00 | 0.00 |
December | 450.91 | 244.95 | 205.96 | 461.28 | 1016.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 697.28 | 378.32 | 318.96 | 1079.77 | 514.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 450.91 | 244.95 | 205.96 | 461.28 | 117.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 905.16 | 484.30 | 420.86 | 1679.43 | 1016.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.80 | 10.59 | 8.21 | 20.51 | 36.11 | 0.00 | 0.00 | 0.00 |
February | 21.21 | 11.28 | 9.94 | 25.08 | 31.94 | 0.00 | 0.00 | 0.00 |
March | 28.91 | 15.49 | 13.41 | 37.86 | 27.02 | 0.00 | 0.00 | 0.00 |
April | 33.23 | 17.95 | 15.28 | 50.46 | 16.77 | 0.00 | 0.00 | 0.00 |
May | 35.79 | 19.15 | 16.64 | 60.54 | 10.50 | 0.00 | 0.00 | 0.00 |
June | 34.84 | 18.71 | 16.13 | 66.40 | 5.57 | 0.00 | 0.00 | 0.00 |
July | 30.92 | 15.36 | 15.55 | 58.93 | 4.66 | 0.00 | 0.00 | 0.00 |
August | 29.94 | 15.26 | 14.68 | 54.65 | 6.51 | 0.00 | 0.00 | 0.00 |
September | 30.62 | 17.06 | 13.56 | 52.76 | 12.70 | 0.00 | 0.00 | 0.00 |
October | 26.36 | 15.38 | 10.97 | 39.12 | 20.03 | 0.00 | 0.00 | 0.00 |
November | 22.12 | 13.47 | 8.65 | 26.89 | 32.90 | 0.00 | 0.00 | 0.00 |
December | 17.83 | 9.68 | 8.14 | 18.24 | 40.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 27.57 | 14.96 | 12.61 | 42.69 | 20.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.83 | 9.68 | 8.14 | 18.24 | 4.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 35.79 | 19.15 | 16.64 | 66.40 | 40.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 263.16 | 0.00 | 263.16 | 47.91 | 1457.58 | 0.00 | 0.00 | 0.00 |
February | 321.34 | 0.00 | 321.34 | 133.10 | 1310.62 | 0.00 | 0.00 | 0.00 |
March | 420.53 | 0.00 | 420.53 | 275.38 | 1112.67 | 0.00 | 0.00 | 0.00 |
April | 485.55 | 3.83 | 481.72 | 548.51 | 657.99 | 0.00 | 0.00 | 0.00 |
May | 575.88 | 41.64 | 534.24 | 928.25 | 383.11 | 0.00 | 0.00 | 0.00 |
June | 612.35 | 75.39 | 536.96 | 1306.74 | 205.89 | 0.00 | 0.00 | 0.00 |
July | 565.93 | 55.09 | 510.84 | 1202.10 | 164.94 | 0.00 | 0.00 | 0.00 |
August | 477.20 | 9.76 | 467.44 | 932.53 | 225.88 | 0.00 | 0.00 | 0.00 |
September | 416.40 | 0.17 | 416.24 | 702.62 | 456.01 | 0.00 | 0.00 | 0.00 |
October | 345.73 | 0.00 | 345.73 | 353.56 | 742.97 | 0.00 | 0.00 | 0.00 |
November | 279.10 | 0.00 | 279.10 | 84.61 | 1273.31 | 0.00 | 0.00 | 0.00 |
December | 261.12 | 0.00 | 261.12 | 31.31 | 1611.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 419.17 | 15.57 | 403.60 | 547.68 | 797.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 261.12 | 0.00 | 261.12 | 31.31 | 164.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 612.35 | 75.39 | 536.96 | 1306.74 | 1611.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 469.23 | 254.54 | 214.69 | 442.95 | 890.95 | 0.00 | 0.00 | 0.00 |
February | 627.78 | 357.83 | 269.95 | 693.23 | 798.07 | 0.00 | 0.00 | 0.00 |
March | 775.10 | 427.06 | 348.05 | 938.31 | 679.88 | 0.00 | 0.00 | 0.00 |
April | 933.96 | 518.14 | 415.82 | 1354.90 | 411.68 | 0.00 | 0.00 | 0.00 |
May | 963.80 | 523.79 | 440.01 | 1583.29 | 254.19 | 0.00 | 0.00 | 0.00 |
June | 964.34 | 536.48 | 427.86 | 1797.62 | 134.56 | 0.00 | 0.00 | 0.00 |
July | 864.80 | 452.10 | 412.70 | 1618.76 | 109.61 | 0.00 | 0.00 | 0.00 |
August | 822.91 | 421.16 | 401.75 | 1482.12 | 148.83 | 0.00 | 0.00 | 0.00 |
September | 815.28 | 465.17 | 350.10 | 1365.91 | 284.63 | 0.00 | 0.00 | 0.00 |
October | 627.00 | 338.38 | 288.62 | 876.76 | 468.00 | 0.00 | 0.00 | 0.00 |
November | 562.05 | 327.21 | 234.84 | 606.26 | 773.33 | 0.00 | 0.00 | 0.00 |
December | 468.82 | 248.39 | 220.43 | 416.83 | 977.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 741.34 | 405.64 | 335.70 | 1099.40 | 492.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 468.82 | 248.39 | 214.69 | 416.83 | 109.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 964.34 | 536.48 | 440.01 | 1797.62 | 977.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1800.20 | 1363.84 | 436.36 | 2382.03 | 1330.76 | 0.00 | 0.00 | 0.00 |
February | 1669.89 | 1177.25 | 492.65 | 2246.51 | 1209.71 | 0.00 | 0.00 | 0.00 |
March | 1357.13 | 782.52 | 574.62 | 1879.20 | 1076.64 | 0.00 | 0.00 | 0.00 |
April | 920.13 | 343.32 | 576.81 | 1449.21 | 682.34 | 0.00 | 0.00 | 0.00 |
May | 650.25 | 91.01 | 559.24 | 1147.90 | 410.82 | 0.00 | 0.00 | 0.00 |
June | 561.00 | 35.60 | 525.41 | 1237.52 | 211.34 | 0.00 | 0.00 | 0.00 |
July | 571.88 | 53.01 | 518.87 | 1250.69 | 171.62 | 0.00 | 0.00 | 0.00 |
August | 728.99 | 192.97 | 536.02 | 1491.37 | 238.61 | 0.00 | 0.00 | 0.00 |
September | 1137.86 | 591.16 | 546.71 | 2102.23 | 464.67 | 0.00 | 0.00 | 0.00 |
October | 1546.02 | 1045.21 | 500.81 | 2425.80 | 731.08 | 0.00 | 0.00 | 0.00 |
November | 1860.49 | 1418.40 | 442.10 | 2581.95 | 1161.44 | 0.00 | 0.00 | 0.00 |
December | 1843.82 | 1384.05 | 459.77 | 2389.64 | 1433.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1218.05 | 703.86 | 514.19 | 1879.44 | 757.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 561.00 | 35.60 | 436.36 | 1147.90 | 171.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1860.49 | 1418.40 | 576.81 | 2581.95 | 1433.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 494.28 | 278.36 | 215.92 | 532.09 | 939.87 | 0.00 | 0.00 | 0.00 |
February | 557.74 | 296.45 | 261.29 | 643.27 | 854.97 | 0.00 | 0.00 | 0.00 |
March | 760.04 | 407.36 | 352.69 | 968.73 | 734.47 | 0.00 | 0.00 | 0.00 |
April | 873.61 | 471.85 | 401.76 | 1305.93 | 456.09 | 0.00 | 0.00 | 0.00 |
May | 940.96 | 503.45 | 437.50 | 1574.81 | 284.06 | 0.00 | 0.00 | 0.00 |
June | 915.95 | 491.97 | 423.99 | 1734.77 | 151.15 | 0.00 | 0.00 | 0.00 |
July | 812.84 | 403.92 | 408.93 | 1544.82 | 121.56 | 0.00 | 0.00 | 0.00 |
August | 787.20 | 401.18 | 386.01 | 1436.53 | 163.50 | 0.00 | 0.00 | 0.00 |
September | 805.03 | 448.48 | 356.55 | 1388.41 | 317.28 | 0.00 | 0.00 | 0.00 |
October | 693.00 | 404.46 | 288.54 | 1031.13 | 500.58 | 0.00 | 0.00 | 0.00 |
November | 581.67 | 354.17 | 227.50 | 708.94 | 824.52 | 0.00 | 0.00 | 0.00 |
December | 468.74 | 254.63 | 214.11 | 477.98 | 1028.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 724.86 | 393.29 | 331.57 | 1114.25 | 529.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 468.74 | 254.63 | 214.11 | 477.98 | 121.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 940.96 | 503.45 | 437.50 | 1734.77 | 1028.11 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.704835E+09 | 0.00 | 0.704835E+09 | 0.162815E+09 | 0.359850E+10 |
February | 0.777386E+09 | 0.00 | 0.777386E+09 | 0.358221E+09 | 0.294238E+10 |
March | 0.112635E+10 | 0.00 | 0.112635E+10 | 0.777243E+09 | 0.278587E+10 |
April | 0.125854E+10 | 9915510.00 | 0.124863E+10 | 0.143129E+10 | 0.161216E+10 |
May | 0.154244E+10 | 0.111540E+09 | 0.143090E+10 | 0.247853E+10 | 0.992896E+09 |
June | 0.158721E+10 | 0.195404E+09 | 0.139181E+10 | 0.336109E+10 | 0.528542E+09 |
July | 0.151579E+10 | 0.147550E+09 | 0.136824E+10 | 0.318772E+10 | 0.438959E+09 |
August | 0.127814E+10 | 26134601.93 | 0.125200E+10 | 0.247739E+10 | 0.587513E+09 |
September | 0.107931E+10 | 430684.71 | 0.107888E+10 | 0.181613E+10 | 0.113214E+10 |
October | 0.925999E+09 | 0.00 | 0.925999E+09 | 0.973062E+09 | 0.185136E+10 |
November | 0.723440E+09 | 0.00 | 0.723440E+09 | 0.258475E+09 | 0.300957E+10 |
December | 0.699376E+09 | 0.00 | 0.699376E+09 | 0.115724E+09 | 0.397422E+10 |
Annual Sum or Average | 0.132188E+11 | 0.490975E+09 | 0.127278E+11 | 0.173977E+11 | 0.234541E+11 |
Minimum of Months | 0.699376E+09 | 0.00 | 0.699376E+09 | 0.115724E+09 | 0.438959E+09 |
Maximum of Months | 0.158721E+10 | 0.195404E+09 | 0.143090E+10 | 0.336109E+10 | 0.397422E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.125678E+10 | 0.681755E+09 | 0.575023E+09 | 0.123212E+10 | 0.220865E+10 |
February | 0.151873E+10 | 0.865663E+09 | 0.653065E+09 | 0.171688E+10 | 0.180348E+10 |
March | 0.207604E+10 | 0.114383E+10 | 0.932211E+09 | 0.254475E+10 | 0.171984E+10 |
April | 0.242083E+10 | 0.134302E+10 | 0.107781E+10 | 0.351423E+10 | 0.102164E+10 |
May | 0.258144E+10 | 0.140291E+10 | 0.117853E+10 | 0.422728E+10 | 0.661017E+09 |
June | 0.249957E+10 | 0.139056E+10 | 0.110902E+10 | 0.463606E+10 | 0.345360E+09 |
July | 0.231629E+10 | 0.121091E+10 | 0.110538E+10 | 0.430958E+10 | 0.291270E+09 |
August | 0.220407E+10 | 0.112802E+10 | 0.107605E+10 | 0.395124E+10 | 0.387957E+09 |
September | 0.211320E+10 | 0.120573E+10 | 0.907468E+09 | 0.353340E+10 | 0.712418E+09 |
October | 0.167936E+10 | 0.906330E+09 | 0.773027E+09 | 0.236377E+10 | 0.117832E+10 |
November | 0.145683E+10 | 0.848120E+09 | 0.608714E+09 | 0.161710E+10 | 0.184982E+10 |
December | 0.125570E+10 | 0.665296E+09 | 0.590403E+09 | 0.116970E+10 | 0.242203E+10 |
Annual Sum or Average | 0.233788E+11 | 0.127921E+11 | 0.105867E+11 | 0.348161E+11 | 0.146018E+11 |
Minimum of Months | 0.125570E+10 | 0.665296E+09 | 0.575023E+09 | 0.116970E+10 | 0.291270E+09 |
Maximum of Months | 0.258144E+10 | 0.140291E+10 | 0.117853E+10 | 0.463606E+10 | 0.242203E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.482167E+10 | 0.365291E+10 | 0.116875E+10 | 0.643932E+10 | 0.330640E+10 |
February | 0.403980E+10 | 0.284799E+10 | 0.119181E+10 | 0.548098E+10 | 0.273132E+10 |
March | 0.363495E+10 | 0.209589E+10 | 0.153905E+10 | 0.506996E+10 | 0.271562E+10 |
April | 0.238498E+10 | 0.889894E+09 | 0.149509E+10 | 0.375883E+10 | 0.167751E+10 |
May | 0.174163E+10 | 0.243769E+09 | 0.149786E+10 | 0.306232E+10 | 0.105766E+10 |
June | 0.145412E+10 | 92263465.73 | 0.136185E+10 | 0.318418E+10 | 0.538819E+09 |
July | 0.153172E+10 | 0.141992E+09 | 0.138973E+10 | 0.332017E+10 | 0.453211E+09 |
August | 0.195252E+10 | 0.516841E+09 | 0.143568E+10 | 0.397133E+10 | 0.618511E+09 |
September | 0.294934E+10 | 0.153228E+10 | 0.141706E+10 | 0.543674E+10 | 0.115712E+10 |
October | 0.414086E+10 | 0.279949E+10 | 0.134137E+10 | 0.651390E+10 | 0.184440E+10 |
November | 0.482240E+10 | 0.367648E+10 | 0.114592E+10 | 0.675309E+10 | 0.279084E+10 |
December | 0.493849E+10 | 0.370705E+10 | 0.123144E+10 | 0.648269E+10 | 0.356159E+10 |
Annual Sum or Average | 0.384125E+11 | 0.221969E+11 | 0.162156E+11 | 0.594735E+11 | 0.224530E+11 |
Minimum of Months | 0.145412E+10 | 92263465.73 | 0.114592E+10 | 0.306232E+10 | 0.453211E+09 |
Maximum of Months | 0.493849E+10 | 0.370705E+10 | 0.153905E+10 | 0.675309E+10 | 0.356159E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132388E+10 | 0.745569E+09 | 0.578309E+09 | 0.145215E+10 | 0.233007E+10 |
February | 0.134929E+10 | 0.717176E+09 | 0.632116E+09 | 0.157840E+10 | 0.192715E+10 |
March | 0.203570E+10 | 0.109106E+10 | 0.944638E+09 | 0.261587E+10 | 0.184505E+10 |
April | 0.226439E+10 | 0.122304E+10 | 0.104136E+10 | 0.338857E+10 | 0.112062E+10 |
May | 0.252027E+10 | 0.134845E+10 | 0.117181E+10 | 0.420685E+10 | 0.733055E+09 |
June | 0.237414E+10 | 0.127517E+10 | 0.109897E+10 | 0.447750E+10 | 0.387092E+09 |
July | 0.217712E+10 | 0.108185E+10 | 0.109527E+10 | 0.411657E+10 | 0.321644E+09 |
August | 0.210842E+10 | 0.107453E+10 | 0.103389E+10 | 0.383238E+10 | 0.424452E+09 |
September | 0.208664E+10 | 0.116247E+10 | 0.924172E+09 | 0.359388E+10 | 0.790092E+09 |
October | 0.185613E+10 | 0.108329E+10 | 0.772833E+09 | 0.277736E+10 | 0.125375E+10 |
November | 0.150769E+10 | 0.918021E+09 | 0.589669E+09 | 0.186643E+10 | 0.196366E+10 |
December | 0.125548E+10 | 0.682014E+09 | 0.573463E+09 | 0.131157E+10 | 0.254658E+10 |
Annual Sum or Average | 0.228591E+11 | 0.124026E+11 | 0.104565E+11 | 0.352175E+11 | 0.156432E+11 |
Minimum of Months | 0.125548E+10 | 0.682014E+09 | 0.573463E+09 | 0.131157E+10 | 0.321644E+09 |
Maximum of Months | 0.252027E+10 | 0.134845E+10 | 0.117181E+10 | 0.447750E+10 | 0.254658E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234934E+09 | 0.00 | 0.234934E+09 | 47088930.05 | 0.128541E+10 |
February | 0.259117E+09 | 0.00 | 0.259117E+09 | 0.122670E+09 | 0.100954E+10 |
March | 0.375432E+09 | 0.00 | 0.375432E+09 | 0.280436E+09 | 0.925570E+09 |
April | 0.419495E+09 | 3305013.62 | 0.416190E+09 | 0.505450E+09 | 0.521112E+09 |
May | 0.514121E+09 | 37178117.66 | 0.476943E+09 | 0.855613E+09 | 0.315707E+09 |
June | 0.529045E+09 | 65131603.43 | 0.463913E+09 | 0.114812E+10 | 0.162097E+09 |
July | 0.505238E+09 | 49181063.32 | 0.456057E+09 | 0.108418E+10 | 0.139573E+09 |
August | 0.426026E+09 | 8711121.82 | 0.417315E+09 | 0.834325E+09 | 0.200330E+09 |
September | 0.359754E+09 | 143554.78 | 0.359610E+09 | 0.604503E+09 | 0.400680E+09 |
October | 0.308652E+09 | 0.00 | 0.308652E+09 | 0.313723E+09 | 0.677762E+09 |
November | 0.241135E+09 | 0.00 | 0.241135E+09 | 71832467.02 | 0.112408E+10 |
December | 0.233114E+09 | 0.00 | 0.233114E+09 | 27455975.88 | 0.145571E+10 |
Annual Sum or Average | 0.440606E+10 | 0.163650E+09 | 0.424241E+10 | 0.589539E+10 | 0.821757E+10 |
Minimum of Months | 0.233114E+09 | 0.00 | 0.233114E+09 | 27455975.88 | 0.139573E+09 |
Maximum of Months | 0.529045E+09 | 65131603.43 | 0.476943E+09 | 0.114812E+10 | 0.145571E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234949E+09 | 0.00 | 0.234949E+09 | 47091905.99 | 0.128549E+10 |
February | 0.259133E+09 | 0.00 | 0.259133E+09 | 0.122678E+09 | 0.100960E+10 |
March | 0.375456E+09 | 0.00 | 0.375456E+09 | 0.280454E+09 | 0.925629E+09 |
April | 0.419522E+09 | 3305222.50 | 0.416216E+09 | 0.505482E+09 | 0.521145E+09 |
May | 0.514153E+09 | 37180467.25 | 0.476973E+09 | 0.855667E+09 | 0.315727E+09 |
June | 0.529078E+09 | 65135719.64 | 0.463943E+09 | 0.114819E+10 | 0.162107E+09 |
July | 0.505270E+09 | 49184171.48 | 0.456086E+09 | 0.108425E+10 | 0.139582E+09 |
August | 0.426053E+09 | 8711672.35 | 0.417341E+09 | 0.834377E+09 | 0.200343E+09 |
September | 0.359777E+09 | 143563.85 | 0.359633E+09 | 0.604542E+09 | 0.400705E+09 |
October | 0.308671E+09 | 0.00 | 0.308671E+09 | 0.313743E+09 | 0.677805E+09 |
November | 0.241150E+09 | 0.00 | 0.241150E+09 | 71837006.72 | 0.112415E+10 |
December | 0.233129E+09 | 0.00 | 0.233129E+09 | 27457711.05 | 0.145581E+10 |
Annual Sum or Average | 0.440634E+10 | 0.163661E+09 | 0.424268E+10 | 0.589577E+10 | 0.821809E+10 |
Minimum of Months | 0.233129E+09 | 0.00 | 0.233129E+09 | 27457711.05 | 0.139582E+09 |
Maximum of Months | 0.529078E+09 | 65135719.64 | 0.476973E+09 | 0.114819E+10 | 0.145581E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234949E+09 | 0.00 | 0.234949E+09 | 47091905.99 | 0.128549E+10 |
February | 0.259133E+09 | 0.00 | 0.259133E+09 | 0.122678E+09 | 0.100960E+10 |
March | 0.375456E+09 | 0.00 | 0.375456E+09 | 0.280454E+09 | 0.925629E+09 |
April | 0.419522E+09 | 3305222.50 | 0.416216E+09 | 0.505482E+09 | 0.521145E+09 |
May | 0.514153E+09 | 37180467.25 | 0.476973E+09 | 0.855667E+09 | 0.315727E+09 |
June | 0.529078E+09 | 65135719.64 | 0.463943E+09 | 0.114819E+10 | 0.162107E+09 |
July | 0.505270E+09 | 49184171.48 | 0.456086E+09 | 0.108425E+10 | 0.139582E+09 |
August | 0.426053E+09 | 8711672.35 | 0.417341E+09 | 0.834377E+09 | 0.200343E+09 |
September | 0.359777E+09 | 143563.85 | 0.359633E+09 | 0.604542E+09 | 0.400705E+09 |
October | 0.308671E+09 | 0.00 | 0.308671E+09 | 0.313743E+09 | 0.677805E+09 |
November | 0.241150E+09 | 0.00 | 0.241150E+09 | 71837006.72 | 0.112415E+10 |
December | 0.233129E+09 | 0.00 | 0.233129E+09 | 27457711.05 | 0.145581E+10 |
Annual Sum or Average | 0.440634E+10 | 0.163661E+09 | 0.424268E+10 | 0.589577E+10 | 0.821809E+10 |
Minimum of Months | 0.233129E+09 | 0.00 | 0.233129E+09 | 27457711.05 | 0.139582E+09 |
Maximum of Months | 0.529078E+09 | 65135719.64 | 0.476973E+09 | 0.114819E+10 | 0.145581E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120897E+10 | 0.655818E+09 | 0.553149E+09 | 0.115821E+10 | 0.231868E+10 |
February | 0.146095E+10 | 0.832729E+09 | 0.628222E+09 | 0.165026E+10 | 0.183185E+10 |
March | 0.199706E+10 | 0.110031E+10 | 0.896750E+09 | 0.248395E+10 | 0.169777E+10 |
April | 0.232873E+10 | 0.129192E+10 | 0.103681E+10 | 0.343002E+10 | 0.997428E+09 |
May | 0.248323E+10 | 0.134954E+10 | 0.113369E+10 | 0.412279E+10 | 0.636857E+09 |
June | 0.240448E+10 | 0.133765E+10 | 0.106683E+10 | 0.451205E+10 | 0.324583E+09 |
July | 0.222817E+10 | 0.116484E+10 | 0.106333E+10 | 0.418411E+10 | 0.285213E+09 |
August | 0.212023E+10 | 0.108511E+10 | 0.103512E+10 | 0.381879E+10 | 0.400659E+09 |
September | 0.203281E+10 | 0.115986E+10 | 0.872948E+09 | 0.340115E+10 | 0.747671E+09 |
October | 0.161547E+10 | 0.871849E+09 | 0.743621E+09 | 0.225662E+10 | 0.126478E+10 |
November | 0.140141E+10 | 0.815853E+09 | 0.585558E+09 | 0.150545E+10 | 0.202279E+10 |
December | 0.120793E+10 | 0.639985E+09 | 0.567944E+09 | 0.107306E+10 | 0.259846E+10 |
Annual Sum or Average | 0.224894E+11 | 0.123055E+11 | 0.101840E+11 | 0.335965E+11 | 0.151267E+11 |
Minimum of Months | 0.120793E+10 | 0.639985E+09 | 0.553149E+09 | 0.107306E+10 | 0.285213E+09 |
Maximum of Months | 0.248323E+10 | 0.134954E+10 | 0.113369E+10 | 0.451205E+10 | 0.259846E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 47801471.59 | 25930449.85 | 21871021.73 | 45794449.69 | 91678333.88 |
February | 57764691.50 | 32925360.09 | 24839331.41 | 65249985.15 | 72429623.78 |
March | 78961971.89 | 43505299.87 | 35456672.03 | 98213219.24 | 67128165.31 |
April | 92076062.01 | 51081373.88 | 40994688.13 | 0.135620E+09 | 39437403.65 |
May | 98184733.25 | 53359468.25 | 44825265.00 | 0.163011E+09 | 25180738.66 |
June | 95071012.79 | 52889535.46 | 42181477.34 | 0.178402E+09 | 12833737.15 |
July | 88099906.73 | 46056860.12 | 42043046.61 | 0.165436E+09 | 11277084.71 |
August | 83831823.54 | 42904122.79 | 40927700.75 | 0.150992E+09 | 15841686.34 |
September | 80375369.77 | 45859786.93 | 34515582.84 | 0.134478E+09 | 29562240.99 |
October | 63874206.72 | 34472109.83 | 29402096.89 | 89224865.05 | 50008164.86 |
November | 55410538.44 | 32258088.28 | 23152450.16 | 59524291.48 | 79979224.04 |
December | 47760413.06 | 25304415.41 | 22455997.65 | 42427880.41 | 0.102741E+09 |
Annual Sum or Average | 0.889212E+09 | 0.486547E+09 | 0.402665E+09 | 0.132837E+10 | 0.598097E+09 |
Minimum of Months | 47760413.06 | 25304415.41 | 21871021.73 | 42427880.41 | 11277084.71 |
Maximum of Months | 98184733.25 | 53359468.25 | 44825265.00 | 0.178402E+09 | 0.102741E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160727E+10 | 0.121768E+10 | 0.389596E+09 | 0.215855E+10 | 0.121759E+10 |
February | 0.134664E+10 | 0.949361E+09 | 0.397280E+09 | 0.185029E+10 | 0.971679E+09 |
March | 0.121169E+10 | 0.698654E+09 | 0.513031E+09 | 0.173256E+10 | 0.924879E+09 |
April | 0.795018E+09 | 0.296641E+09 | 0.498376E+09 | 0.128801E+10 | 0.553750E+09 |
May | 0.580558E+09 | 81259067.57 | 0.499299E+09 | 0.105242E+10 | 0.339474E+09 |
June | 0.484718E+09 | 30755494.51 | 0.453962E+09 | 0.108184E+10 | 0.166666E+09 |
July | 0.510587E+09 | 47332300.02 | 0.463255E+09 | 0.112234E+10 | 0.146875E+09 |
August | 0.650858E+09 | 0.172286E+09 | 0.478572E+09 | 0.132961E+10 | 0.216700E+09 |
September | 0.983144E+09 | 0.510777E+09 | 0.472366E+09 | 0.181458E+10 | 0.421570E+09 |
October | 0.138033E+10 | 0.933195E+09 | 0.447135E+09 | 0.217091E+10 | 0.687346E+09 |
November | 0.160752E+10 | 0.122553E+10 | 0.381983E+09 | 0.224296E+10 | 0.105730E+10 |
December | 0.164621E+10 | 0.123572E+10 | 0.410491E+09 | 0.215775E+10 | 0.132569E+10 |
Annual Sum or Average | 0.128045E+11 | 0.739920E+10 | 0.540535E+10 | 0.200018E+11 | 0.802951E+10 |
Minimum of Months | 0.484718E+09 | 30755494.51 | 0.381983E+09 | 0.105242E+10 | 0.146875E+09 |
Maximum of Months | 0.164621E+10 | 0.123572E+10 | 0.513031E+09 | 0.224296E+10 | 0.132569E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160727E+10 | 0.121768E+10 | 0.389596E+09 | 0.215855E+10 | 0.121759E+10 |
February | 0.134664E+10 | 0.949361E+09 | 0.397280E+09 | 0.185029E+10 | 0.971679E+09 |
March | 0.121169E+10 | 0.698654E+09 | 0.513031E+09 | 0.173256E+10 | 0.924879E+09 |
April | 0.795018E+09 | 0.296641E+09 | 0.498376E+09 | 0.128801E+10 | 0.553750E+09 |
May | 0.580558E+09 | 81259067.57 | 0.499299E+09 | 0.105242E+10 | 0.339474E+09 |
June | 0.484718E+09 | 30755494.51 | 0.453962E+09 | 0.108184E+10 | 0.166666E+09 |
July | 0.510587E+09 | 47332300.02 | 0.463255E+09 | 0.112234E+10 | 0.146875E+09 |
August | 0.650858E+09 | 0.172286E+09 | 0.478572E+09 | 0.132961E+10 | 0.216700E+09 |
September | 0.983144E+09 | 0.510777E+09 | 0.472366E+09 | 0.181458E+10 | 0.421570E+09 |
October | 0.138033E+10 | 0.933195E+09 | 0.447135E+09 | 0.217091E+10 | 0.687346E+09 |
November | 0.160752E+10 | 0.122553E+10 | 0.381983E+09 | 0.224296E+10 | 0.105730E+10 |
December | 0.164621E+10 | 0.123572E+10 | 0.410491E+09 | 0.215775E+10 | 0.132569E+10 |
Annual Sum or Average | 0.128045E+11 | 0.739920E+10 | 0.540535E+10 | 0.200018E+11 | 0.802951E+10 |
Minimum of Months | 0.484718E+09 | 30755494.51 | 0.381983E+09 | 0.105242E+10 | 0.146875E+09 |
Maximum of Months | 0.164621E+10 | 0.123572E+10 | 0.513031E+09 | 0.224296E+10 | 0.132569E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160717E+10 | 0.121760E+10 | 0.389571E+09 | 0.215842E+10 | 0.121751E+10 |
February | 0.134656E+10 | 0.949301E+09 | 0.397255E+09 | 0.185017E+10 | 0.971618E+09 |
March | 0.121161E+10 | 0.698610E+09 | 0.512999E+09 | 0.173245E+10 | 0.924821E+09 |
April | 0.794967E+09 | 0.296622E+09 | 0.498345E+09 | 0.128793E+10 | 0.553715E+09 |
May | 0.580521E+09 | 81253932.45 | 0.499267E+09 | 0.105236E+10 | 0.339452E+09 |
June | 0.484687E+09 | 30753550.94 | 0.453934E+09 | 0.108177E+10 | 0.166656E+09 |
July | 0.510555E+09 | 47329308.88 | 0.463226E+09 | 0.112227E+10 | 0.146865E+09 |
August | 0.650817E+09 | 0.172275E+09 | 0.478542E+09 | 0.132953E+10 | 0.216686E+09 |
September | 0.983082E+09 | 0.510745E+09 | 0.472337E+09 | 0.181447E+10 | 0.421544E+09 |
October | 0.138024E+10 | 0.933136E+09 | 0.447107E+09 | 0.217077E+10 | 0.687303E+09 |
November | 0.160742E+10 | 0.122546E+10 | 0.381958E+09 | 0.224282E+10 | 0.105723E+10 |
December | 0.164611E+10 | 0.123565E+10 | 0.410465E+09 | 0.215762E+10 | 0.132560E+10 |
Annual Sum or Average | 0.128037E+11 | 0.739873E+10 | 0.540500E+10 | 0.200006E+11 | 0.802900E+10 |
Minimum of Months | 0.484687E+09 | 30753550.94 | 0.381958E+09 | 0.105236E+10 | 0.146865E+09 |
Maximum of Months | 0.164611E+10 | 0.123565E+10 | 0.512999E+09 | 0.224282E+10 | 0.132560E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127351E+10 | 0.717204E+09 | 0.556310E+09 | 0.138965E+10 | 0.244583E+10 |
February | 0.129796E+10 | 0.689892E+09 | 0.608071E+09 | 0.153443E+10 | 0.195395E+10 |
March | 0.195826E+10 | 0.104955E+10 | 0.908704E+09 | 0.256448E+10 | 0.183018E+10 |
April | 0.217825E+10 | 0.117651E+10 | 0.100174E+10 | 0.330779E+10 | 0.109908E+10 |
May | 0.242439E+10 | 0.129715E+10 | 0.112724E+10 | 0.410114E+10 | 0.711522E+09 |
June | 0.228383E+10 | 0.122666E+10 | 0.105717E+10 | 0.435308E+10 | 0.364913E+09 |
July | 0.209429E+10 | 0.104069E+10 | 0.105360E+10 | 0.399197E+10 | 0.315849E+09 |
August | 0.202822E+10 | 0.103365E+10 | 0.994564E+09 | 0.370172E+10 | 0.441282E+09 |
September | 0.200726E+10 | 0.111824E+10 | 0.889017E+09 | 0.345852E+10 | 0.832303E+09 |
October | 0.178552E+10 | 0.104208E+10 | 0.743435E+09 | 0.265024E+10 | 0.135668E+10 |
November | 0.145033E+10 | 0.883095E+09 | 0.567238E+09 | 0.176301E+10 | 0.215694E+10 |
December | 0.120771E+10 | 0.656067E+09 | 0.551648E+09 | 0.123549E+10 | 0.272334E+10 |
Annual Sum or Average | 0.219895E+11 | 0.119308E+11 | 0.100587E+11 | 0.340515E+11 | 0.162319E+11 |
Minimum of Months | 0.120771E+10 | 0.656067E+09 | 0.551648E+09 | 0.123549E+10 | 0.315849E+09 |
Maximum of Months | 0.242439E+10 | 0.129715E+10 | 0.112724E+10 | 0.435308E+10 | 0.272334E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 50353474.72 | 28357519.06 | 21995955.65 | 54945118.59 | 96705943.19 |
February | 51320122.74 | 27277605.28 | 24042517.46 | 60669730.50 | 77257407.28 |
March | 77427552.34 | 41498280.99 | 35929271.35 | 0.101397E+09 | 72363551.44 |
April | 86125788.90 | 46517830.12 | 39607958.78 | 0.130787E+09 | 43456519.72 |
May | 95857884.47 | 51288026.21 | 44569858.26 | 0.162155E+09 | 28132891.58 |
June | 90300239.98 | 48500875.85 | 41799364.12 | 0.172117E+09 | 14428319.95 |
July | 82806258.38 | 41147827.36 | 41658431.02 | 0.157839E+09 | 12488357.64 |
August | 80193612.79 | 40869511.51 | 39324101.27 | 0.146362E+09 | 17447857.46 |
September | 79364893.30 | 44214037.10 | 35150856.20 | 0.136747E+09 | 32908482.90 |
October | 70597487.04 | 41202815.88 | 29394671.17 | 0.104788E+09 | 53641771.74 |
November | 57344702.50 | 34916661.65 | 22428040.86 | 69707708.08 | 85283249.19 |
December | 47751822.04 | 25940203.11 | 21811618.93 | 48849914.59 | 0.107678E+09 |
Annual Sum or Average | 0.869444E+09 | 0.471731E+09 | 0.397713E+09 | 0.134636E+10 | 0.641793E+09 |
Minimum of Months | 47751822.04 | 25940203.11 | 21811618.93 | 48849914.59 | 12488357.64 |
Maximum of Months | 95857884.47 | 51288026.21 | 44569858.26 | 0.172117E+09 | 0.107678E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.704835E+09 | 0.00 | 0.704835E+09 | 0.128316E+09 | 0.390398E+10 |
February | 0.777386E+09 | 0.00 | 0.777386E+09 | 0.322005E+09 | 0.317065E+10 |
March | 0.112635E+10 | 0.00 | 0.112635E+10 | 0.737572E+09 | 0.298019E+10 |
April | 0.125854E+10 | 9915510.00 | 0.124863E+10 | 0.142173E+10 | 0.170552E+10 |
May | 0.154244E+10 | 0.111540E+09 | 0.143090E+10 | 0.248624E+10 | 0.102611E+10 |
June | 0.158721E+10 | 0.195404E+09 | 0.139181E+10 | 0.338708E+10 | 0.533663E+09 |
July | 0.151579E+10 | 0.147550E+09 | 0.136824E+10 | 0.321970E+10 | 0.441776E+09 |
August | 0.127814E+10 | 26134601.93 | 0.125200E+10 | 0.249770E+10 | 0.604985E+09 |
September | 0.107931E+10 | 430684.71 | 0.107888E+10 | 0.182119E+10 | 0.118199E+10 |
October | 0.925999E+09 | 0.00 | 0.925999E+09 | 0.946972E+09 | 0.198998E+10 |
November | 0.723440E+09 | 0.00 | 0.723440E+09 | 0.219311E+09 | 0.330041E+10 |
December | 0.699376E+09 | 0.00 | 0.699376E+09 | 83864169.72 | 0.431612E+10 |
Annual Sum or Average | 0.132188E+11 | 0.490975E+09 | 0.127278E+11 | 0.172717E+11 | 0.251554E+11 |
Minimum of Months | 0.699376E+09 | 0.00 | 0.699376E+09 | 83864169.72 | 0.441776E+09 |
Maximum of Months | 0.158721E+10 | 0.195404E+09 | 0.143090E+10 | 0.338708E+10 | 0.431612E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.125678E+10 | 0.681755E+09 | 0.575023E+09 | 0.118640E+10 | 0.238632E+10 |
February | 0.151873E+10 | 0.865663E+09 | 0.653065E+09 | 0.167707E+10 | 0.193070E+10 |
March | 0.207604E+10 | 0.114383E+10 | 0.932211E+09 | 0.251318E+10 | 0.182099E+10 |
April | 0.242083E+10 | 0.134302E+10 | 0.107781E+10 | 0.351190E+10 | 0.106709E+10 |
May | 0.258144E+10 | 0.140291E+10 | 0.117853E+10 | 0.424069E+10 | 0.680819E+09 |
June | 0.249957E+10 | 0.139056E+10 | 0.110902E+10 | 0.465944E+10 | 0.348780E+09 |
July | 0.231629E+10 | 0.121091E+10 | 0.110538E+10 | 0.433569E+10 | 0.293581E+09 |
August | 0.220407E+10 | 0.112802E+10 | 0.107605E+10 | 0.396971E+10 | 0.398636E+09 |
September | 0.211320E+10 | 0.120573E+10 | 0.907468E+09 | 0.354043E+10 | 0.737750E+09 |
October | 0.167936E+10 | 0.906330E+09 | 0.773027E+09 | 0.234831E+10 | 0.125350E+10 |
November | 0.145683E+10 | 0.848120E+09 | 0.608714E+09 | 0.157142E+10 | 0.200447E+10 |
December | 0.125570E+10 | 0.665296E+09 | 0.590403E+09 | 0.111643E+10 | 0.261842E+10 |
Annual Sum or Average | 0.233788E+11 | 0.127921E+11 | 0.105867E+11 | 0.346707E+11 | 0.155411E+11 |
Minimum of Months | 0.125570E+10 | 0.665296E+09 | 0.575023E+09 | 0.111643E+10 | 0.293581E+09 |
Maximum of Months | 0.258144E+10 | 0.140291E+10 | 0.117853E+10 | 0.465944E+10 | 0.261842E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.482167E+10 | 0.365291E+10 | 0.116875E+10 | 0.638002E+10 | 0.356432E+10 |
February | 0.403980E+10 | 0.284799E+10 | 0.119181E+10 | 0.543476E+10 | 0.292652E+10 |
March | 0.363495E+10 | 0.209589E+10 | 0.153905E+10 | 0.503324E+10 | 0.288369E+10 |
April | 0.238498E+10 | 0.889894E+09 | 0.149509E+10 | 0.375636E+10 | 0.176864E+10 |
May | 0.174163E+10 | 0.243769E+09 | 0.149786E+10 | 0.307453E+10 | 0.110033E+10 |
June | 0.145412E+10 | 92263465.73 | 0.136185E+10 | 0.320765E+10 | 0.547803E+09 |
July | 0.153172E+10 | 0.141992E+09 | 0.138973E+10 | 0.334984E+10 | 0.459662E+09 |
August | 0.195252E+10 | 0.516841E+09 | 0.143568E+10 | 0.399448E+10 | 0.639093E+09 |
September | 0.294934E+10 | 0.153228E+10 | 0.141706E+10 | 0.544897E+10 | 0.120443E+10 |
October | 0.414086E+10 | 0.279949E+10 | 0.134137E+10 | 0.649727E+10 | 0.195813E+10 |
November | 0.482240E+10 | 0.367648E+10 | 0.114592E+10 | 0.669241E+10 | 0.301046E+10 |
December | 0.493849E+10 | 0.370705E+10 | 0.123144E+10 | 0.640042E+10 | 0.383837E+10 |
Annual Sum or Average | 0.384125E+11 | 0.221969E+11 | 0.162156E+11 | 0.592699E+11 | 0.239014E+11 |
Minimum of Months | 0.145412E+10 | 92263465.73 | 0.114592E+10 | 0.307453E+10 | 0.459662E+09 |
Maximum of Months | 0.493849E+10 | 0.370705E+10 | 0.153905E+10 | 0.669241E+10 | 0.383837E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132388E+10 | 0.745569E+09 | 0.578309E+09 | 0.142514E+10 | 0.251736E+10 |
February | 0.134929E+10 | 0.717176E+09 | 0.632116E+09 | 0.155619E+10 | 0.206835E+10 |
March | 0.203570E+10 | 0.109106E+10 | 0.944638E+09 | 0.259463E+10 | 0.196720E+10 |
April | 0.226439E+10 | 0.122304E+10 | 0.104136E+10 | 0.338497E+10 | 0.118219E+10 |
May | 0.252027E+10 | 0.134845E+10 | 0.117181E+10 | 0.421798E+10 | 0.760833E+09 |
June | 0.237414E+10 | 0.127517E+10 | 0.109897E+10 | 0.449652E+10 | 0.391793E+09 |
July | 0.217712E+10 | 0.108185E+10 | 0.109527E+10 | 0.413766E+10 | 0.325577E+09 |
August | 0.210842E+10 | 0.107453E+10 | 0.103389E+10 | 0.384760E+10 | 0.437919E+09 |
September | 0.208664E+10 | 0.116247E+10 | 0.924172E+09 | 0.359876E+10 | 0.822388E+09 |
October | 0.185613E+10 | 0.108329E+10 | 0.772833E+09 | 0.276177E+10 | 0.134074E+10 |
November | 0.150769E+10 | 0.918021E+09 | 0.589669E+09 | 0.183756E+10 | 0.213715E+10 |
December | 0.125548E+10 | 0.682014E+09 | 0.573463E+09 | 0.128022E+10 | 0.275368E+10 |
Annual Sum or Average | 0.228591E+11 | 0.124026E+11 | 0.104565E+11 | 0.351390E+11 | 0.167052E+11 |
Minimum of Months | 0.125548E+10 | 0.682014E+09 | 0.573463E+09 | 0.128022E+10 | 0.325577E+09 |
Maximum of Months | 0.252027E+10 | 0.134845E+10 | 0.117181E+10 | 0.449652E+10 | 0.275368E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 60.79 | 1343.53 | 263.16 | 0.00 | 263.16 | 0.00 | 0.00 |
February | 148.07 | 1216.26 | 321.34 | 0.00 | 321.34 | 0.00 | 0.00 |
March | 290.19 | 1040.12 | 420.53 | 0.00 | 420.53 | 0.00 | 0.00 |
April | 552.19 | 621.98 | 485.55 | 3.83 | 481.72 | 0.00 | 0.00 |
May | 925.38 | 370.70 | 575.88 | 41.64 | 534.24 | 0.00 | 0.00 |
June | 1296.72 | 203.91 | 612.35 | 75.39 | 536.96 | 0.00 | 0.00 |
July | 1190.16 | 163.89 | 565.93 | 55.09 | 510.84 | 0.00 | 0.00 |
August | 924.95 | 219.35 | 477.20 | 9.76 | 467.44 | 0.00 | 0.00 |
September | 700.67 | 436.78 | 416.40 | 0.17 | 416.24 | 0.00 | 0.00 |
October | 363.30 | 691.22 | 345.73 | 0.00 | 345.73 | 0.00 | 0.00 |
November | 99.72 | 1161.10 | 279.10 | 0.00 | 279.10 | 0.00 | 0.00 |
December | 43.21 | 1483.81 | 261.12 | 0.00 | 261.12 | 0.00 | 0.00 |
Annual Sum or Average | 551.68 | 743.72 | 419.17 | 15.57 | 403.60 | 0.00 | 0.00 |
Minimum of Months | 43.21 | 163.89 | 261.12 | 0.00 | 261.12 | 0.00 | 0.00 |
Maximum of Months | 1296.72 | 1483.81 | 612.35 | 75.39 | 536.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 460.02 | 824.61 | 469.23 | 254.54 | 214.69 | 0.00 | 0.00 |
February | 709.69 | 745.49 | 627.78 | 357.83 | 269.95 | 0.00 | 0.00 |
March | 950.10 | 642.12 | 775.10 | 427.06 | 348.05 | 0.00 | 0.00 |
April | 1355.80 | 394.15 | 933.96 | 518.14 | 415.82 | 0.00 | 0.00 |
May | 1578.29 | 246.80 | 963.80 | 523.79 | 440.01 | 0.00 | 0.00 |
June | 1788.60 | 133.24 | 964.34 | 536.48 | 427.86 | 0.00 | 0.00 |
July | 1609.01 | 108.75 | 864.80 | 452.10 | 412.70 | 0.00 | 0.00 |
August | 1475.22 | 144.85 | 822.91 | 421.16 | 401.75 | 0.00 | 0.00 |
September | 1363.20 | 274.85 | 815.28 | 465.17 | 350.10 | 0.00 | 0.00 |
October | 882.53 | 439.93 | 627.00 | 338.38 | 288.62 | 0.00 | 0.00 |
November | 623.88 | 713.67 | 562.05 | 327.21 | 234.84 | 0.00 | 0.00 |
December | 436.72 | 904.28 | 468.82 | 248.39 | 220.43 | 0.00 | 0.00 |
Annual Sum or Average | 1104.01 | 463.02 | 741.34 | 405.64 | 335.70 | 0.00 | 0.00 |
Minimum of Months | 436.72 | 108.75 | 468.82 | 248.39 | 214.69 | 0.00 | 0.00 |
Maximum of Months | 1788.60 | 904.28 | 964.34 | 536.48 | 440.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2404.17 | 1234.47 | 1800.20 | 1363.84 | 436.36 | 0.00 | 0.00 |
February | 2265.62 | 1129.02 | 1669.89 | 1177.25 | 492.65 | 0.00 | 0.00 |
March | 1892.91 | 1013.90 | 1357.13 | 782.52 | 574.62 | 0.00 | 0.00 |
April | 1450.17 | 647.19 | 920.13 | 343.32 | 576.81 | 0.00 | 0.00 |
May | 1143.34 | 394.88 | 650.25 | 91.01 | 559.24 | 0.00 | 0.00 |
June | 1228.46 | 207.88 | 561.00 | 35.60 | 525.41 | 0.00 | 0.00 |
July | 1239.61 | 169.21 | 571.88 | 53.01 | 518.87 | 0.00 | 0.00 |
August | 1482.73 | 230.93 | 728.99 | 192.97 | 536.02 | 0.00 | 0.00 |
September | 2097.51 | 446.42 | 1137.86 | 591.16 | 546.71 | 0.00 | 0.00 |
October | 2432.01 | 688.62 | 1546.02 | 1045.21 | 500.81 | 0.00 | 0.00 |
November | 2605.36 | 1076.71 | 1860.49 | 1418.40 | 442.10 | 0.00 | 0.00 |
December | 2420.36 | 1329.74 | 1843.82 | 1384.05 | 459.77 | 0.00 | 0.00 |
Annual Sum or Average | 1885.89 | 711.98 | 1218.05 | 703.86 | 514.19 | 0.00 | 0.00 |
Minimum of Months | 1143.34 | 169.21 | 561.00 | 35.60 | 436.36 | 0.00 | 0.00 |
Maximum of Months | 2605.36 | 1329.74 | 1860.49 | 1418.40 | 576.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 542.17 | 869.95 | 494.28 | 278.36 | 215.92 | 0.00 | 0.00 |
February | 652.45 | 796.61 | 557.74 | 296.45 | 261.29 | 0.00 | 0.00 |
March | 976.65 | 688.86 | 760.04 | 407.36 | 352.69 | 0.00 | 0.00 |
April | 1307.32 | 432.34 | 873.61 | 471.85 | 401.76 | 0.00 | 0.00 |
May | 1570.66 | 273.69 | 940.96 | 503.45 | 437.50 | 0.00 | 0.00 |
June | 1727.43 | 149.34 | 915.95 | 491.97 | 423.99 | 0.00 | 0.00 |
July | 1536.95 | 120.09 | 812.84 | 403.92 | 408.93 | 0.00 | 0.00 |
August | 1430.85 | 158.47 | 787.20 | 401.18 | 386.01 | 0.00 | 0.00 |
September | 1386.53 | 304.82 | 805.03 | 448.48 | 356.55 | 0.00 | 0.00 |
October | 1036.95 | 468.10 | 693.00 | 404.46 | 288.54 | 0.00 | 0.00 |
November | 720.07 | 757.59 | 581.67 | 354.17 | 227.50 | 0.00 | 0.00 |
December | 489.69 | 950.78 | 468.74 | 254.63 | 214.11 | 0.00 | 0.00 |
Annual Sum or Average | 1116.74 | 496.04 | 724.86 | 393.29 | 331.57 | 0.00 | 0.00 |
Minimum of Months | 489.69 | 120.09 | 468.74 | 254.63 | 214.11 | 0.00 | 0.00 |
Maximum of Months | 1727.43 | 950.78 | 940.96 | 503.45 | 437.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 52.75 | 1439.81 | 263.15 | 0.00 | 263.15 | 0.00 | 0.00 |
February | 152.13 | 1251.96 | 321.34 | 0.00 | 321.34 | 0.00 | 0.00 |
March | 314.12 | 1036.75 | 420.53 | 0.00 | 420.53 | 0.00 | 0.00 |
April | 585.04 | 603.16 | 485.55 | 3.83 | 481.72 | 0.00 | 0.00 |
May | 958.39 | 353.63 | 575.88 | 41.64 | 534.23 | 0.00 | 0.00 |
June | 1328.90 | 187.62 | 612.35 | 75.39 | 536.96 | 0.00 | 0.00 |
July | 1214.41 | 156.34 | 565.93 | 55.09 | 510.84 | 0.00 | 0.00 |
August | 934.54 | 224.39 | 477.20 | 9.76 | 467.44 | 0.00 | 0.00 |
September | 699.69 | 463.77 | 416.40 | 0.17 | 416.23 | 0.00 | 0.00 |
October | 351.41 | 759.17 | 345.73 | 0.00 | 345.73 | 0.00 | 0.00 |
November | 83.14 | 1301.07 | 279.10 | 0.00 | 279.10 | 0.00 | 0.00 |
December | 30.75 | 1630.57 | 261.12 | 0.00 | 261.12 | 0.00 | 0.00 |
Annual Sum or Average | 560.85 | 781.77 | 419.16 | 15.57 | 403.59 | 0.00 | 0.00 |
Minimum of Months | 30.75 | 156.34 | 261.12 | 0.00 | 261.12 | 0.00 | 0.00 |
Maximum of Months | 1328.90 | 1630.57 | 612.35 | 75.39 | 536.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 449.52 | 899.92 | 469.22 | 254.54 | 214.69 | 0.00 | 0.00 |
February | 709.12 | 787.15 | 627.78 | 357.83 | 269.95 | 0.00 | 0.00 |
March | 964.07 | 658.94 | 775.10 | 427.05 | 348.05 | 0.00 | 0.00 |
April | 1375.63 | 400.03 | 933.95 | 518.13 | 415.82 | 0.00 | 0.00 |
May | 1600.13 | 247.18 | 963.79 | 523.78 | 440.01 | 0.00 | 0.00 |
June | 1809.59 | 130.18 | 964.33 | 536.47 | 427.86 | 0.00 | 0.00 |
July | 1623.93 | 110.70 | 864.80 | 452.10 | 412.70 | 0.00 | 0.00 |
August | 1482.15 | 155.50 | 822.90 | 421.15 | 401.75 | 0.00 | 0.00 |
September | 1364.06 | 299.86 | 815.27 | 465.17 | 350.10 | 0.00 | 0.00 |
October | 875.84 | 490.88 | 627.00 | 338.38 | 288.61 | 0.00 | 0.00 |
November | 603.77 | 811.25 | 562.05 | 327.20 | 234.84 | 0.00 | 0.00 |
December | 416.48 | 1008.51 | 468.82 | 248.39 | 220.43 | 0.00 | 0.00 |
Annual Sum or Average | 1107.46 | 498.63 | 741.33 | 405.63 | 335.70 | 0.00 | 0.00 |
Minimum of Months | 416.48 | 110.70 | 468.82 | 248.39 | 214.69 | 0.00 | 0.00 |
Maximum of Months | 1809.59 | 1008.51 | 964.33 | 536.47 | 440.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2417.68 | 1363.76 | 1800.22 | 1363.86 | 436.37 | 0.00 | 0.00 |
February | 2294.46 | 1204.93 | 1669.91 | 1177.26 | 492.65 | 0.00 | 0.00 |
March | 1940.55 | 1035.91 | 1357.15 | 782.53 | 574.62 | 0.00 | 0.00 |
April | 1490.72 | 640.90 | 920.14 | 343.33 | 576.81 | 0.00 | 0.00 |
May | 1178.77 | 380.23 | 650.25 | 91.01 | 559.24 | 0.00 | 0.00 |
June | 1252.10 | 192.90 | 561.00 | 35.60 | 525.41 | 0.00 | 0.00 |
July | 1257.07 | 164.51 | 571.88 | 53.01 | 518.87 | 0.00 | 0.00 |
August | 1489.23 | 242.71 | 728.99 | 192.97 | 536.02 | 0.00 | 0.00 |
September | 2100.17 | 487.92 | 1137.87 | 591.17 | 546.71 | 0.00 | 0.00 |
October | 2431.52 | 769.86 | 1546.04 | 1045.22 | 500.81 | 0.00 | 0.00 |
November | 2595.97 | 1223.70 | 1860.51 | 1418.41 | 442.10 | 0.00 | 0.00 |
December | 2416.79 | 1484.83 | 1843.84 | 1384.07 | 459.77 | 0.00 | 0.00 |
Annual Sum or Average | 1902.72 | 763.83 | 1218.06 | 703.87 | 514.20 | 0.00 | 0.00 |
Minimum of Months | 1178.77 | 164.51 | 561.00 | 35.60 | 436.37 | 0.00 | 0.00 |
Maximum of Months | 2595.97 | 1484.83 | 1860.51 | 1418.41 | 576.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 539.35 | 949.27 | 494.28 | 278.36 | 215.91 | 0.00 | 0.00 |
February | 659.35 | 839.62 | 557.74 | 296.45 | 261.29 | 0.00 | 0.00 |
March | 995.33 | 710.33 | 760.04 | 407.35 | 352.69 | 0.00 | 0.00 |
April | 1326.61 | 440.79 | 873.60 | 471.85 | 401.76 | 0.00 | 0.00 |
May | 1591.73 | 276.16 | 940.95 | 503.45 | 437.50 | 0.00 | 0.00 |
June | 1745.83 | 146.35 | 915.94 | 491.96 | 423.98 | 0.00 | 0.00 |
July | 1549.36 | 122.59 | 812.84 | 403.91 | 408.92 | 0.00 | 0.00 |
August | 1436.71 | 171.27 | 787.19 | 401.18 | 386.01 | 0.00 | 0.00 |
September | 1387.06 | 333.80 | 805.02 | 448.48 | 356.55 | 0.00 | 0.00 |
October | 1028.61 | 526.55 | 692.99 | 404.45 | 288.54 | 0.00 | 0.00 |
November | 707.07 | 865.05 | 581.67 | 354.17 | 227.49 | 0.00 | 0.00 |
December | 479.52 | 1056.98 | 468.74 | 254.63 | 214.11 | 0.00 | 0.00 |
Annual Sum or Average | 1122.46 | 535.06 | 724.85 | 393.28 | 331.57 | 0.00 | 0.00 |
Minimum of Months | 479.52 | 122.59 | 468.74 | 254.63 | 214.11 | 0.00 | 0.00 |
Maximum of Months | 1745.83 | 1056.98 | 940.95 | 503.45 | 437.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 47.91 | 1457.58 | 263.16 | 0.00 | 263.16 | 0.00 | 0.00 |
February | 133.10 | 1310.62 | 321.34 | 0.00 | 321.34 | 0.00 | 0.00 |
March | 275.38 | 1112.67 | 420.53 | 0.00 | 420.53 | 0.00 | 0.00 |
April | 548.51 | 657.99 | 485.55 | 3.83 | 481.72 | 0.00 | 0.00 |
May | 928.25 | 383.11 | 575.88 | 41.64 | 534.24 | 0.00 | 0.00 |
June | 1306.74 | 205.89 | 612.35 | 75.39 | 536.96 | 0.00 | 0.00 |
July | 1202.10 | 164.94 | 565.93 | 55.09 | 510.84 | 0.00 | 0.00 |
August | 932.53 | 225.88 | 477.20 | 9.76 | 467.44 | 0.00 | 0.00 |
September | 702.62 | 456.01 | 416.40 | 0.17 | 416.24 | 0.00 | 0.00 |
October | 353.56 | 742.97 | 345.73 | 0.00 | 345.73 | 0.00 | 0.00 |
November | 84.61 | 1273.31 | 279.10 | 0.00 | 279.10 | 0.00 | 0.00 |
December | 31.31 | 1611.45 | 261.12 | 0.00 | 261.12 | 0.00 | 0.00 |
Annual Sum or Average | 547.68 | 797.67 | 419.17 | 15.57 | 403.60 | 0.00 | 0.00 |
Minimum of Months | 31.31 | 164.94 | 261.12 | 0.00 | 261.12 | 0.00 | 0.00 |
Maximum of Months | 1306.74 | 1611.45 | 612.35 | 75.39 | 536.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 442.95 | 890.95 | 469.23 | 254.54 | 214.69 | 0.00 | 0.00 |
February | 693.23 | 798.07 | 627.78 | 357.83 | 269.95 | 0.00 | 0.00 |
March | 938.31 | 679.88 | 775.10 | 427.06 | 348.05 | 0.00 | 0.00 |
April | 1354.90 | 411.68 | 933.96 | 518.14 | 415.82 | 0.00 | 0.00 |
May | 1583.29 | 254.19 | 963.80 | 523.79 | 440.01 | 0.00 | 0.00 |
June | 1797.62 | 134.56 | 964.34 | 536.48 | 427.86 | 0.00 | 0.00 |
July | 1618.76 | 109.61 | 864.80 | 452.10 | 412.70 | 0.00 | 0.00 |
August | 1482.12 | 148.83 | 822.91 | 421.16 | 401.75 | 0.00 | 0.00 |
September | 1365.91 | 284.63 | 815.28 | 465.17 | 350.10 | 0.00 | 0.00 |
October | 876.76 | 468.00 | 627.00 | 338.38 | 288.62 | 0.00 | 0.00 |
November | 606.26 | 773.33 | 562.05 | 327.21 | 234.84 | 0.00 | 0.00 |
December | 416.83 | 977.61 | 468.82 | 248.39 | 220.43 | 0.00 | 0.00 |
Annual Sum or Average | 1099.40 | 492.80 | 741.34 | 405.64 | 335.70 | 0.00 | 0.00 |
Minimum of Months | 416.83 | 109.61 | 468.82 | 248.39 | 214.69 | 0.00 | 0.00 |
Maximum of Months | 1797.62 | 977.61 | 964.34 | 536.48 | 440.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2382.03 | 1330.76 | 1800.20 | 1363.84 | 436.36 | 0.00 | 0.00 |
February | 2246.51 | 1209.71 | 1669.89 | 1177.25 | 492.65 | 0.00 | 0.00 |
March | 1879.20 | 1076.64 | 1357.13 | 782.52 | 574.62 | 0.00 | 0.00 |
April | 1449.21 | 682.34 | 920.13 | 343.32 | 576.81 | 0.00 | 0.00 |
May | 1147.90 | 410.82 | 650.25 | 91.01 | 559.24 | 0.00 | 0.00 |
June | 1237.52 | 211.34 | 561.00 | 35.60 | 525.41 | 0.00 | 0.00 |
July | 1250.69 | 171.62 | 571.88 | 53.01 | 518.87 | 0.00 | 0.00 |
August | 1491.37 | 238.61 | 728.99 | 192.97 | 536.02 | 0.00 | 0.00 |
September | 2102.23 | 464.67 | 1137.86 | 591.16 | 546.71 | 0.00 | 0.00 |
October | 2425.80 | 731.08 | 1546.02 | 1045.21 | 500.81 | 0.00 | 0.00 |
November | 2581.95 | 1161.44 | 1860.49 | 1418.40 | 442.10 | 0.00 | 0.00 |
December | 2389.64 | 1433.08 | 1843.82 | 1384.05 | 459.77 | 0.00 | 0.00 |
Annual Sum or Average | 1879.44 | 757.91 | 1218.05 | 703.86 | 514.19 | 0.00 | 0.00 |
Minimum of Months | 1147.90 | 171.62 | 561.00 | 35.60 | 436.36 | 0.00 | 0.00 |
Maximum of Months | 2581.95 | 1433.08 | 1860.49 | 1418.40 | 576.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 532.09 | 939.87 | 494.28 | 278.36 | 215.92 | 0.00 | 0.00 |
February | 643.27 | 854.97 | 557.74 | 296.45 | 261.29 | 0.00 | 0.00 |
March | 968.73 | 734.47 | 760.04 | 407.36 | 352.69 | 0.00 | 0.00 |
April | 1305.93 | 456.09 | 873.61 | 471.85 | 401.76 | 0.00 | 0.00 |
May | 1574.81 | 284.06 | 940.96 | 503.45 | 437.50 | 0.00 | 0.00 |
June | 1734.77 | 151.15 | 915.95 | 491.97 | 423.99 | 0.00 | 0.00 |
July | 1544.82 | 121.56 | 812.84 | 403.92 | 408.93 | 0.00 | 0.00 |
August | 1436.53 | 163.50 | 787.20 | 401.18 | 386.01 | 0.00 | 0.00 |
September | 1388.41 | 317.28 | 805.03 | 448.48 | 356.55 | 0.00 | 0.00 |
October | 1031.13 | 500.58 | 693.00 | 404.46 | 288.54 | 0.00 | 0.00 |
November | 708.94 | 824.52 | 581.67 | 354.17 | 227.50 | 0.00 | 0.00 |
December | 477.98 | 1028.11 | 468.74 | 254.63 | 214.11 | 0.00 | 0.00 |
Annual Sum or Average | 1114.25 | 529.72 | 724.86 | 393.29 | 331.57 | 0.00 | 0.00 |
Minimum of Months | 477.98 | 121.56 | 468.74 | 254.63 | 214.11 | 0.00 | 0.00 |
Maximum of Months | 1734.77 | 1028.11 | 940.96 | 503.45 | 437.50 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.162815E+09 | 0.359850E+10 | 0.704835E+09 | 0.00 | 0.704835E+09 | 0.00 | 0.00 |
February | 0.358221E+09 | 0.294238E+10 | 0.777386E+09 | 0.00 | 0.777386E+09 | 0.00 | 0.00 |
March | 0.777243E+09 | 0.278587E+10 | 0.112635E+10 | 0.00 | 0.112635E+10 | 0.00 | 0.00 |
April | 0.143129E+10 | 0.161216E+10 | 0.125854E+10 | 9915510.00 | 0.124863E+10 | 0.00 | 0.00 |
May | 0.247853E+10 | 0.992896E+09 | 0.154244E+10 | 0.111540E+09 | 0.143090E+10 | 0.00 | 0.00 |
June | 0.336109E+10 | 0.528542E+09 | 0.158721E+10 | 0.195404E+09 | 0.139181E+10 | 0.00 | 0.00 |
July | 0.318772E+10 | 0.438959E+09 | 0.151579E+10 | 0.147550E+09 | 0.136824E+10 | 0.00 | 0.00 |
August | 0.247739E+10 | 0.587513E+09 | 0.127814E+10 | 26134601.93 | 0.125200E+10 | 0.00 | 0.00 |
September | 0.181613E+10 | 0.113214E+10 | 0.107931E+10 | 430684.71 | 0.107888E+10 | 0.00 | 0.00 |
October | 0.973062E+09 | 0.185136E+10 | 0.925999E+09 | 0.00 | 0.925999E+09 | 0.00 | 0.00 |
November | 0.258475E+09 | 0.300957E+10 | 0.723440E+09 | 0.00 | 0.723440E+09 | 0.00 | 0.00 |
December | 0.115724E+09 | 0.397422E+10 | 0.699376E+09 | 0.00 | 0.699376E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.173977E+11 | 0.234541E+11 | 0.132188E+11 | 0.490975E+09 | 0.127278E+11 | 0.00 | 0.00 |
Minimum of Months | 0.115724E+09 | 0.438959E+09 | 0.699376E+09 | 0.00 | 0.699376E+09 | 0.00 | 0.00 |
Maximum of Months | 0.336109E+10 | 0.397422E+10 | 0.158721E+10 | 0.195404E+09 | 0.143090E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.123212E+10 | 0.220865E+10 | 0.125678E+10 | 0.681755E+09 | 0.575023E+09 | 0.00 | 0.00 |
February | 0.171688E+10 | 0.180348E+10 | 0.151873E+10 | 0.865663E+09 | 0.653065E+09 | 0.00 | 0.00 |
March | 0.254475E+10 | 0.171984E+10 | 0.207604E+10 | 0.114383E+10 | 0.932211E+09 | 0.00 | 0.00 |
April | 0.351423E+10 | 0.102164E+10 | 0.242083E+10 | 0.134302E+10 | 0.107781E+10 | 0.00 | 0.00 |
May | 0.422728E+10 | 0.661017E+09 | 0.258144E+10 | 0.140291E+10 | 0.117853E+10 | 0.00 | 0.00 |
June | 0.463606E+10 | 0.345360E+09 | 0.249957E+10 | 0.139056E+10 | 0.110902E+10 | 0.00 | 0.00 |
July | 0.430958E+10 | 0.291270E+09 | 0.231629E+10 | 0.121091E+10 | 0.110538E+10 | 0.00 | 0.00 |
August | 0.395124E+10 | 0.387957E+09 | 0.220407E+10 | 0.112802E+10 | 0.107605E+10 | 0.00 | 0.00 |
September | 0.353340E+10 | 0.712418E+09 | 0.211320E+10 | 0.120573E+10 | 0.907468E+09 | 0.00 | 0.00 |
October | 0.236377E+10 | 0.117832E+10 | 0.167936E+10 | 0.906330E+09 | 0.773027E+09 | 0.00 | 0.00 |
November | 0.161710E+10 | 0.184982E+10 | 0.145683E+10 | 0.848120E+09 | 0.608714E+09 | 0.00 | 0.00 |
December | 0.116970E+10 | 0.242203E+10 | 0.125570E+10 | 0.665296E+09 | 0.590403E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.348161E+11 | 0.146018E+11 | 0.233788E+11 | 0.127921E+11 | 0.105867E+11 | 0.00 | 0.00 |
Minimum of Months | 0.116970E+10 | 0.291270E+09 | 0.125570E+10 | 0.665296E+09 | 0.575023E+09 | 0.00 | 0.00 |
Maximum of Months | 0.463606E+10 | 0.242203E+10 | 0.258144E+10 | 0.140291E+10 | 0.117853E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.643932E+10 | 0.330640E+10 | 0.482167E+10 | 0.365291E+10 | 0.116875E+10 | 0.00 | 0.00 |
February | 0.548098E+10 | 0.273132E+10 | 0.403980E+10 | 0.284799E+10 | 0.119181E+10 | 0.00 | 0.00 |
March | 0.506996E+10 | 0.271562E+10 | 0.363495E+10 | 0.209589E+10 | 0.153905E+10 | 0.00 | 0.00 |
April | 0.375883E+10 | 0.167751E+10 | 0.238498E+10 | 0.889894E+09 | 0.149509E+10 | 0.00 | 0.00 |
May | 0.306232E+10 | 0.105766E+10 | 0.174163E+10 | 0.243769E+09 | 0.149786E+10 | 0.00 | 0.00 |
June | 0.318418E+10 | 0.538819E+09 | 0.145412E+10 | 92263465.73 | 0.136185E+10 | 0.00 | 0.00 |
July | 0.332017E+10 | 0.453211E+09 | 0.153172E+10 | 0.141992E+09 | 0.138973E+10 | 0.00 | 0.00 |
August | 0.397133E+10 | 0.618511E+09 | 0.195252E+10 | 0.516841E+09 | 0.143568E+10 | 0.00 | 0.00 |
September | 0.543674E+10 | 0.115712E+10 | 0.294934E+10 | 0.153228E+10 | 0.141706E+10 | 0.00 | 0.00 |
October | 0.651390E+10 | 0.184440E+10 | 0.414086E+10 | 0.279949E+10 | 0.134137E+10 | 0.00 | 0.00 |
November | 0.675309E+10 | 0.279084E+10 | 0.482240E+10 | 0.367648E+10 | 0.114592E+10 | 0.00 | 0.00 |
December | 0.648269E+10 | 0.356159E+10 | 0.493849E+10 | 0.370705E+10 | 0.123144E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.594735E+11 | 0.224530E+11 | 0.384125E+11 | 0.221969E+11 | 0.162156E+11 | 0.00 | 0.00 |
Minimum of Months | 0.306232E+10 | 0.453211E+09 | 0.145412E+10 | 92263465.73 | 0.114592E+10 | 0.00 | 0.00 |
Maximum of Months | 0.675309E+10 | 0.356159E+10 | 0.493849E+10 | 0.370705E+10 | 0.153905E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.145215E+10 | 0.233007E+10 | 0.132388E+10 | 0.745569E+09 | 0.578309E+09 | 0.00 | 0.00 |
February | 0.157840E+10 | 0.192715E+10 | 0.134929E+10 | 0.717176E+09 | 0.632116E+09 | 0.00 | 0.00 |
March | 0.261587E+10 | 0.184505E+10 | 0.203570E+10 | 0.109106E+10 | 0.944638E+09 | 0.00 | 0.00 |
April | 0.338857E+10 | 0.112062E+10 | 0.226439E+10 | 0.122304E+10 | 0.104136E+10 | 0.00 | 0.00 |
May | 0.420685E+10 | 0.733055E+09 | 0.252027E+10 | 0.134845E+10 | 0.117181E+10 | 0.00 | 0.00 |
June | 0.447750E+10 | 0.387092E+09 | 0.237414E+10 | 0.127517E+10 | 0.109897E+10 | 0.00 | 0.00 |
July | 0.411657E+10 | 0.321644E+09 | 0.217712E+10 | 0.108185E+10 | 0.109527E+10 | 0.00 | 0.00 |
August | 0.383238E+10 | 0.424452E+09 | 0.210842E+10 | 0.107453E+10 | 0.103389E+10 | 0.00 | 0.00 |
September | 0.359388E+10 | 0.790092E+09 | 0.208664E+10 | 0.116247E+10 | 0.924172E+09 | 0.00 | 0.00 |
October | 0.277736E+10 | 0.125375E+10 | 0.185613E+10 | 0.108329E+10 | 0.772833E+09 | 0.00 | 0.00 |
November | 0.186643E+10 | 0.196366E+10 | 0.150769E+10 | 0.918021E+09 | 0.589669E+09 | 0.00 | 0.00 |
December | 0.131157E+10 | 0.254658E+10 | 0.125548E+10 | 0.682014E+09 | 0.573463E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.352175E+11 | 0.156432E+11 | 0.228591E+11 | 0.124026E+11 | 0.104565E+11 | 0.00 | 0.00 |
Minimum of Months | 0.131157E+10 | 0.321644E+09 | 0.125548E+10 | 0.682014E+09 | 0.573463E+09 | 0.00 | 0.00 |
Maximum of Months | 0.447750E+10 | 0.254658E+10 | 0.252027E+10 | 0.134845E+10 | 0.117181E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.141273E+09 | 0.385639E+10 | 0.704831E+09 | 0.00 | 0.704831E+09 | 0.00 | 0.00 |
February | 0.368025E+09 | 0.302875E+10 | 0.777382E+09 | 0.00 | 0.777382E+09 | 0.00 | 0.00 |
March | 0.841343E+09 | 0.277683E+10 | 0.112634E+10 | 0.00 | 0.112634E+10 | 0.00 | 0.00 |
April | 0.151641E+10 | 0.156340E+10 | 0.125854E+10 | 9915458.62 | 0.124862E+10 | 0.00 | 0.00 |
May | 0.256695E+10 | 0.947162E+09 | 0.154243E+10 | 0.111539E+09 | 0.143089E+10 | 0.00 | 0.00 |
June | 0.344450E+10 | 0.486311E+09 | 0.158720E+10 | 0.195403E+09 | 0.139180E+10 | 0.00 | 0.00 |
July | 0.325267E+10 | 0.418738E+09 | 0.151578E+10 | 0.147549E+09 | 0.136823E+10 | 0.00 | 0.00 |
August | 0.250308E+10 | 0.601015E+09 | 0.127813E+10 | 26134466.51 | 0.125200E+10 | 0.00 | 0.00 |
September | 0.181359E+10 | 0.120209E+10 | 0.107931E+10 | 430682.48 | 0.107888E+10 | 0.00 | 0.00 |
October | 0.941210E+09 | 0.203337E+10 | 0.925994E+09 | 0.00 | 0.925994E+09 | 0.00 | 0.00 |
November | 0.215506E+09 | 0.337238E+10 | 0.723436E+09 | 0.00 | 0.723436E+09 | 0.00 | 0.00 |
December | 82371397.99 | 0.436732E+10 | 0.699373E+09 | 0.00 | 0.699373E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.176869E+11 | 0.246538E+11 | 0.132187E+11 | 0.490972E+09 | 0.127278E+11 | 0.00 | 0.00 |
Minimum of Months | 82371397.99 | 0.418738E+09 | 0.699373E+09 | 0.00 | 0.699373E+09 | 0.00 | 0.00 |
Maximum of Months | 0.344450E+10 | 0.436732E+10 | 0.158720E+10 | 0.195403E+09 | 0.143089E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.120400E+10 | 0.241035E+10 | 0.125677E+10 | 0.681748E+09 | 0.575020E+09 | 0.00 | 0.00 |
February | 0.171551E+10 | 0.190428E+10 | 0.151872E+10 | 0.865654E+09 | 0.653061E+09 | 0.00 | 0.00 |
March | 0.258217E+10 | 0.176489E+10 | 0.207602E+10 | 0.114382E+10 | 0.932206E+09 | 0.00 | 0.00 |
April | 0.356564E+10 | 0.103687E+10 | 0.242081E+10 | 0.134300E+10 | 0.107781E+10 | 0.00 | 0.00 |
May | 0.428580E+10 | 0.662037E+09 | 0.258142E+10 | 0.140290E+10 | 0.117852E+10 | 0.00 | 0.00 |
June | 0.469045E+10 | 0.337417E+09 | 0.249955E+10 | 0.139054E+10 | 0.110901E+10 | 0.00 | 0.00 |
July | 0.434954E+10 | 0.296491E+09 | 0.231627E+10 | 0.121090E+10 | 0.110537E+10 | 0.00 | 0.00 |
August | 0.396978E+10 | 0.416500E+09 | 0.220406E+10 | 0.112801E+10 | 0.107605E+10 | 0.00 | 0.00 |
September | 0.353563E+10 | 0.777233E+09 | 0.211318E+10 | 0.120572E+10 | 0.907464E+09 | 0.00 | 0.00 |
October | 0.234585E+10 | 0.131479E+10 | 0.167934E+10 | 0.906321E+09 | 0.773023E+09 | 0.00 | 0.00 |
November | 0.156498E+10 | 0.210277E+10 | 0.145682E+10 | 0.848111E+09 | 0.608711E+09 | 0.00 | 0.00 |
December | 0.111549E+10 | 0.270120E+10 | 0.125569E+10 | 0.665289E+09 | 0.590400E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.349248E+11 | 0.157248E+11 | 0.233787E+11 | 0.127920E+11 | 0.105866E+11 | 0.00 | 0.00 |
Minimum of Months | 0.111549E+10 | 0.296491E+09 | 0.125569E+10 | 0.665289E+09 | 0.575020E+09 | 0.00 | 0.00 |
Maximum of Months | 0.469045E+10 | 0.270120E+10 | 0.258142E+10 | 0.140290E+10 | 0.117852E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.647553E+10 | 0.365269E+10 | 0.482172E+10 | 0.365295E+10 | 0.116876E+10 | 0.00 | 0.00 |
February | 0.555076E+10 | 0.291498E+10 | 0.403984E+10 | 0.284802E+10 | 0.119182E+10 | 0.00 | 0.00 |
March | 0.519757E+10 | 0.277458E+10 | 0.363498E+10 | 0.209592E+10 | 0.153906E+10 | 0.00 | 0.00 |
April | 0.386395E+10 | 0.166121E+10 | 0.238500E+10 | 0.889904E+09 | 0.149510E+10 | 0.00 | 0.00 |
May | 0.315721E+10 | 0.101840E+10 | 0.174164E+10 | 0.243772E+09 | 0.149786E+10 | 0.00 | 0.00 |
June | 0.324545E+10 | 0.499988E+09 | 0.145412E+10 | 92264539.97 | 0.136186E+10 | 0.00 | 0.00 |
July | 0.336695E+10 | 0.440615E+09 | 0.153173E+10 | 0.141994E+09 | 0.138974E+10 | 0.00 | 0.00 |
August | 0.398875E+10 | 0.650086E+09 | 0.195253E+10 | 0.516847E+09 | 0.143569E+10 | 0.00 | 0.00 |
September | 0.544363E+10 | 0.126468E+10 | 0.294937E+10 | 0.153230E+10 | 0.141707E+10 | 0.00 | 0.00 |
October | 0.651258E+10 | 0.206200E+10 | 0.414090E+10 | 0.279953E+10 | 0.134138E+10 | 0.00 | 0.00 |
November | 0.672874E+10 | 0.317183E+10 | 0.482245E+10 | 0.367653E+10 | 0.114592E+10 | 0.00 | 0.00 |
December | 0.647312E+10 | 0.397698E+10 | 0.493854E+10 | 0.370709E+10 | 0.123145E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.600042E+11 | 0.240880E+11 | 0.384128E+11 | 0.221971E+11 | 0.162157E+11 | 0.00 | 0.00 |
Minimum of Months | 0.315721E+10 | 0.440615E+09 | 0.145412E+10 | 92264539.97 | 0.114592E+10 | 0.00 | 0.00 |
Maximum of Months | 0.672874E+10 | 0.397698E+10 | 0.493854E+10 | 0.370709E+10 | 0.153906E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.144459E+10 | 0.254254E+10 | 0.132387E+10 | 0.745562E+09 | 0.578306E+09 | 0.00 | 0.00 |
February | 0.159510E+10 | 0.203121E+10 | 0.134928E+10 | 0.717169E+09 | 0.632113E+09 | 0.00 | 0.00 |
March | 0.266588E+10 | 0.190254E+10 | 0.203569E+10 | 0.109105E+10 | 0.944633E+09 | 0.00 | 0.00 |
April | 0.343857E+10 | 0.114253E+10 | 0.226438E+10 | 0.122302E+10 | 0.104135E+10 | 0.00 | 0.00 |
May | 0.426329E+10 | 0.739655E+09 | 0.252025E+10 | 0.134844E+10 | 0.117181E+10 | 0.00 | 0.00 |
June | 0.452520E+10 | 0.379342E+09 | 0.237413E+10 | 0.127516E+10 | 0.109897E+10 | 0.00 | 0.00 |
July | 0.414981E+10 | 0.328337E+09 | 0.217710E+10 | 0.108184E+10 | 0.109526E+10 | 0.00 | 0.00 |
August | 0.384808E+10 | 0.458730E+09 | 0.210841E+10 | 0.107452E+10 | 0.103389E+10 | 0.00 | 0.00 |
September | 0.359527E+10 | 0.865212E+09 | 0.208662E+10 | 0.116245E+10 | 0.924168E+09 | 0.00 | 0.00 |
October | 0.275503E+10 | 0.141032E+10 | 0.185611E+10 | 0.108328E+10 | 0.772829E+09 | 0.00 | 0.00 |
November | 0.183272E+10 | 0.224222E+10 | 0.150768E+10 | 0.918012E+09 | 0.589666E+09 | 0.00 | 0.00 |
December | 0.128434E+10 | 0.283102E+10 | 0.125547E+10 | 0.682007E+09 | 0.573460E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.353979E+11 | 0.168737E+11 | 0.228590E+11 | 0.124025E+11 | 0.104565E+11 | 0.00 | 0.00 |
Minimum of Months | 0.128434E+10 | 0.328337E+09 | 0.125547E+10 | 0.682007E+09 | 0.573460E+09 | 0.00 | 0.00 |
Maximum of Months | 0.452520E+10 | 0.283102E+10 | 0.252025E+10 | 0.134844E+10 | 0.117181E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.128316E+09 | 0.390398E+10 | 0.704835E+09 | 0.00 | 0.704835E+09 | 0.00 | 0.00 |
February | 0.322005E+09 | 0.317065E+10 | 0.777386E+09 | 0.00 | 0.777386E+09 | 0.00 | 0.00 |
March | 0.737572E+09 | 0.298019E+10 | 0.112635E+10 | 0.00 | 0.112635E+10 | 0.00 | 0.00 |
April | 0.142173E+10 | 0.170552E+10 | 0.125854E+10 | 9915510.00 | 0.124863E+10 | 0.00 | 0.00 |
May | 0.248624E+10 | 0.102611E+10 | 0.154244E+10 | 0.111540E+09 | 0.143090E+10 | 0.00 | 0.00 |
June | 0.338708E+10 | 0.533663E+09 | 0.158721E+10 | 0.195404E+09 | 0.139181E+10 | 0.00 | 0.00 |
July | 0.321970E+10 | 0.441776E+09 | 0.151579E+10 | 0.147550E+09 | 0.136824E+10 | 0.00 | 0.00 |
August | 0.249770E+10 | 0.604985E+09 | 0.127814E+10 | 26134601.93 | 0.125200E+10 | 0.00 | 0.00 |
September | 0.182119E+10 | 0.118199E+10 | 0.107931E+10 | 430684.71 | 0.107888E+10 | 0.00 | 0.00 |
October | 0.946972E+09 | 0.198998E+10 | 0.925999E+09 | 0.00 | 0.925999E+09 | 0.00 | 0.00 |
November | 0.219311E+09 | 0.330041E+10 | 0.723440E+09 | 0.00 | 0.723440E+09 | 0.00 | 0.00 |
December | 83864169.72 | 0.431612E+10 | 0.699376E+09 | 0.00 | 0.699376E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.172717E+11 | 0.251554E+11 | 0.132188E+11 | 0.490975E+09 | 0.127278E+11 | 0.00 | 0.00 |
Minimum of Months | 83864169.72 | 0.441776E+09 | 0.699376E+09 | 0.00 | 0.699376E+09 | 0.00 | 0.00 |
Maximum of Months | 0.338708E+10 | 0.431612E+10 | 0.158721E+10 | 0.195404E+09 | 0.143090E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118640E+10 | 0.238632E+10 | 0.125678E+10 | 0.681755E+09 | 0.575023E+09 | 0.00 | 0.00 |
February | 0.167707E+10 | 0.193070E+10 | 0.151873E+10 | 0.865663E+09 | 0.653065E+09 | 0.00 | 0.00 |
March | 0.251318E+10 | 0.182099E+10 | 0.207604E+10 | 0.114383E+10 | 0.932211E+09 | 0.00 | 0.00 |
April | 0.351190E+10 | 0.106709E+10 | 0.242083E+10 | 0.134302E+10 | 0.107781E+10 | 0.00 | 0.00 |
May | 0.424069E+10 | 0.680819E+09 | 0.258144E+10 | 0.140291E+10 | 0.117853E+10 | 0.00 | 0.00 |
June | 0.465944E+10 | 0.348780E+09 | 0.249957E+10 | 0.139056E+10 | 0.110902E+10 | 0.00 | 0.00 |
July | 0.433569E+10 | 0.293581E+09 | 0.231629E+10 | 0.121091E+10 | 0.110538E+10 | 0.00 | 0.00 |
August | 0.396971E+10 | 0.398636E+09 | 0.220407E+10 | 0.112802E+10 | 0.107605E+10 | 0.00 | 0.00 |
September | 0.354043E+10 | 0.737750E+09 | 0.211320E+10 | 0.120573E+10 | 0.907468E+09 | 0.00 | 0.00 |
October | 0.234831E+10 | 0.125350E+10 | 0.167936E+10 | 0.906330E+09 | 0.773027E+09 | 0.00 | 0.00 |
November | 0.157142E+10 | 0.200447E+10 | 0.145683E+10 | 0.848120E+09 | 0.608714E+09 | 0.00 | 0.00 |
December | 0.111643E+10 | 0.261842E+10 | 0.125570E+10 | 0.665296E+09 | 0.590403E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.346707E+11 | 0.155411E+11 | 0.233788E+11 | 0.127921E+11 | 0.105867E+11 | 0.00 | 0.00 |
Minimum of Months | 0.111643E+10 | 0.293581E+09 | 0.125570E+10 | 0.665296E+09 | 0.575023E+09 | 0.00 | 0.00 |
Maximum of Months | 0.465944E+10 | 0.261842E+10 | 0.258144E+10 | 0.140291E+10 | 0.117853E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.638002E+10 | 0.356432E+10 | 0.482167E+10 | 0.365291E+10 | 0.116875E+10 | 0.00 | 0.00 |
February | 0.543476E+10 | 0.292652E+10 | 0.403980E+10 | 0.284799E+10 | 0.119181E+10 | 0.00 | 0.00 |
March | 0.503324E+10 | 0.288369E+10 | 0.363495E+10 | 0.209589E+10 | 0.153905E+10 | 0.00 | 0.00 |
April | 0.375636E+10 | 0.176864E+10 | 0.238498E+10 | 0.889894E+09 | 0.149509E+10 | 0.00 | 0.00 |
May | 0.307453E+10 | 0.110033E+10 | 0.174163E+10 | 0.243769E+09 | 0.149786E+10 | 0.00 | 0.00 |
June | 0.320765E+10 | 0.547803E+09 | 0.145412E+10 | 92263465.73 | 0.136185E+10 | 0.00 | 0.00 |
July | 0.334984E+10 | 0.459662E+09 | 0.153172E+10 | 0.141992E+09 | 0.138973E+10 | 0.00 | 0.00 |
August | 0.399448E+10 | 0.639093E+09 | 0.195252E+10 | 0.516841E+09 | 0.143568E+10 | 0.00 | 0.00 |
September | 0.544897E+10 | 0.120443E+10 | 0.294934E+10 | 0.153228E+10 | 0.141706E+10 | 0.00 | 0.00 |
October | 0.649727E+10 | 0.195813E+10 | 0.414086E+10 | 0.279949E+10 | 0.134137E+10 | 0.00 | 0.00 |
November | 0.669241E+10 | 0.301046E+10 | 0.482240E+10 | 0.367648E+10 | 0.114592E+10 | 0.00 | 0.00 |
December | 0.640042E+10 | 0.383837E+10 | 0.493849E+10 | 0.370705E+10 | 0.123144E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.592699E+11 | 0.239014E+11 | 0.384125E+11 | 0.221969E+11 | 0.162156E+11 | 0.00 | 0.00 |
Minimum of Months | 0.307453E+10 | 0.459662E+09 | 0.145412E+10 | 92263465.73 | 0.114592E+10 | 0.00 | 0.00 |
Maximum of Months | 0.669241E+10 | 0.383837E+10 | 0.493849E+10 | 0.370705E+10 | 0.153905E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.142514E+10 | 0.251736E+10 | 0.132388E+10 | 0.745569E+09 | 0.578309E+09 | 0.00 | 0.00 |
February | 0.155619E+10 | 0.206835E+10 | 0.134929E+10 | 0.717176E+09 | 0.632116E+09 | 0.00 | 0.00 |
March | 0.259463E+10 | 0.196720E+10 | 0.203570E+10 | 0.109106E+10 | 0.944638E+09 | 0.00 | 0.00 |
April | 0.338497E+10 | 0.118219E+10 | 0.226439E+10 | 0.122304E+10 | 0.104136E+10 | 0.00 | 0.00 |
May | 0.421798E+10 | 0.760833E+09 | 0.252027E+10 | 0.134845E+10 | 0.117181E+10 | 0.00 | 0.00 |
June | 0.449652E+10 | 0.391793E+09 | 0.237414E+10 | 0.127517E+10 | 0.109897E+10 | 0.00 | 0.00 |
July | 0.413766E+10 | 0.325577E+09 | 0.217712E+10 | 0.108185E+10 | 0.109527E+10 | 0.00 | 0.00 |
August | 0.384760E+10 | 0.437919E+09 | 0.210842E+10 | 0.107453E+10 | 0.103389E+10 | 0.00 | 0.00 |
September | 0.359876E+10 | 0.822388E+09 | 0.208664E+10 | 0.116247E+10 | 0.924172E+09 | 0.00 | 0.00 |
October | 0.276177E+10 | 0.134074E+10 | 0.185613E+10 | 0.108329E+10 | 0.772833E+09 | 0.00 | 0.00 |
November | 0.183756E+10 | 0.213715E+10 | 0.150769E+10 | 0.918021E+09 | 0.589669E+09 | 0.00 | 0.00 |
December | 0.128022E+10 | 0.275368E+10 | 0.125548E+10 | 0.682014E+09 | 0.573463E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.351390E+11 | 0.167052E+11 | 0.228591E+11 | 0.124026E+11 | 0.104565E+11 | 0.00 | 0.00 |
Minimum of Months | 0.128022E+10 | 0.325577E+09 | 0.125548E+10 | 0.682014E+09 | 0.573463E+09 | 0.00 | 0.00 |
Maximum of Months | 0.449652E+10 | 0.275368E+10 | 0.252027E+10 | 0.134845E+10 | 0.117181E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.484438E+10 | -0.414205E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -702327340.0 | 58.98 | 0.00 | 0.00 |
February | 0.439277E+10 | -0.376147E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -631297557.3 | 58.98 | 0.00 | 0.00 |
March | 0.498442E+10 | -0.428822E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -696202806.7 | 58.98 | 0.00 | 0.00 |
April | 0.427107E+10 | -0.360296E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668115136.3 | 58.98 | 0.00 | 0.00 |
May | 0.423888E+10 | -0.354969E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689189240.5 | 58.98 | 0.00 | 0.00 |
June | 0.391182E+10 | -0.324557E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666247356.6 | 58.98 | 0.00 | 0.00 |
July | 0.359510E+10 | -0.290765E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687443269.0 | 58.98 | 0.00 | 0.00 |
August | 0.390809E+10 | -0.321915E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688941121.3 | 58.98 | 0.00 | 0.00 |
September | 0.371722E+10 | -0.305245E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -664775864.1 | 58.98 | 0.00 | 0.00 |
October | 0.410891E+10 | -0.341993E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688981524.7 | 58.98 | 0.00 | 0.00 |
November | 0.433442E+10 | -0.366329E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -671123996.7 | 58.98 | 0.00 | 0.00 |
December | 0.458223E+10 | -0.388019E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -702045107.6 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.508893E+11 | -0.427326E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.815669E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.359510E+10 | -0.428822E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -702327340.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.498442E+10 | -0.290765E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -631297557.3 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.63 | 0.62 | 01-JAN-07:00 | 7847.03 | 36.94 | 265.17 | 274.50 | 1642.64 | 25.90 | 129.67 | 259.17 |
February | 268.33 | 0.63 | 0.62 | 01-FEB-07:49 | 8500.85 | 36.41 | 261.50 | 265.50 | 1187.43 | 21.87 | 86.83 | 238.83 |
March | 351.83 | 0.64 | 0.62 | 01-MAR-07:10 | 1711.27 | 17.06 | 10.67 | 313.33 | 886.70 | 19.32 | 62.17 | 281.33 |
April | 373.83 | 0.64 | 0.62 | 01-APR-06:30 | 1057.36 | 16.43 | 0.00 | 326.50 | 655.02 | 19.17 | 20.67 | 280.00 |
May | 408.83 | 0.65 | 0.62 | 01-MAY-06:19 | 860.48 | 16.11 | 0.00 | 352.17 | 529.64 | 18.85 | 0.00 | 298.83 |
June | 398.00 | 0.64 | 0.62 | 01-JUN-06:19 | 767.33 | 15.95 | 0.00 | 342.50 | 484.49 | 18.81 | 0.00 | 284.50 |
July | 400.17 | 0.65 | 0.62 | 01-JUL-06:19 | 821.49 | 16.00 | 0.00 | 348.17 | 499.20 | 18.78 | 0.67 | 273.00 |
August | 377.83 | 0.64 | 0.62 | 01-AUG-06:19 | 976.29 | 16.40 | 0.00 | 336.67 | 592.58 | 19.13 | 11.83 | 279.17 |
September | 365.83 | 0.64 | 0.62 | 01-SEP-06:49 | 1261.73 | 16.82 | 11.00 | 308.83 | 745.91 | 19.10 | 38.50 | 268.50 |
October | 318.83 | 0.63 | 0.62 | 01-OCT-06:49 | 3171.11 | 23.88 | 131.00 | 308.50 | 1055.13 | 20.22 | 67.00 | 276.50 |
November | 295.83 | 0.63 | 0.62 | 01-NOV-12:39 | 8052.28 | 36.92 | 288.33 | 283.83 | 1335.63 | 24.25 | 112.50 | 270.67 |
December | 289.50 | 0.63 | 0.62 | 01-DEC-07:10 | 7120.31 | 37.32 | 284.00 | 273.83 | 1617.86 | 25.93 | 135.00 | 266.67 |
Annual Sum or Average | 4125.67 | 0.64 | 3083.54 | 22.58 | 1251.67 | 3734.33 | 881.31 | 20.62 | 664.83 | 3277.17 | ||
Minimum of Months | 268.33 | 0.63 | 0.62 | 767.33 | 15.95 | 0.00 | 265.50 | 484.49 | 18.78 | 0.00 | 238.83 | |
Maximum of Months | 408.83 | 0.65 | 0.62 | 8500.85 | 37.32 | 288.33 | 352.17 | 1642.64 | 25.93 | 135.00 | 298.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.65 | 0.62 | 01-JAN-07:00 | 2002.92 | 19.52 | 79.83 | 232.67 | 1158.22 | 21.99 | 63.33 | 168.83 |
February | 268.33 | 0.64 | 0.62 | 01-FEB-07:40 | 2548.26 | 21.05 | 89.67 | 236.33 | 929.87 | 20.17 | 41.00 | 180.67 |
March | 351.83 | 0.64 | 0.62 | 01-MAR-06:00 | 2210.57 | 18.11 | 82.50 | 293.33 | 1229.23 | 21.12 | 70.83 | 253.50 |
April | 373.83 | 0.64 | 0.62 | 01-APR-06:10 | 2931.20 | 19.79 | 109.83 | 325.83 | 1101.76 | 19.48 | 50.83 | 290.33 |
May | 408.83 | 0.64 | 0.62 | 01-MAY-05:49 | 2252.45 | 17.63 | 87.00 | 354.50 | 1272.46 | 20.58 | 72.67 | 315.67 |
June | 398.00 | 0.64 | 0.62 | 01-JUN-05:49 | 2288.22 | 17.70 | 85.00 | 348.67 | 1305.48 | 20.64 | 70.00 | 308.00 |
July | 400.17 | 0.64 | 0.62 | 01-JUL-05:49 | 2040.22 | 17.56 | 84.17 | 354.17 | 1125.94 | 20.49 | 69.00 | 301.50 |
August | 377.83 | 0.64 | 0.62 | 01-AUG-05:49 | 2641.13 | 19.49 | 109.50 | 336.33 | 1016.80 | 19.53 | 52.33 | 293.33 |
September | 365.83 | 0.64 | 0.62 | 01-SEP-05:00 | 2534.12 | 19.95 | 111.50 | 302.17 | 974.02 | 19.88 | 57.67 | 263.67 |
October | 318.83 | 0.65 | 0.62 | 01-OCT-06:49 | 2120.10 | 18.41 | 77.67 | 274.00 | 1189.47 | 20.98 | 60.67 | 218.33 |
November | 295.83 | 0.65 | 0.62 | 01-NOV-12:39 | 1757.64 | 18.67 | 77.50 | 238.00 | 911.58 | 20.00 | 50.67 | 175.83 |
December | 289.50 | 0.65 | 0.62 | 01-DEC-07:10 | 1563.22 | 19.64 | 78.83 | 236.17 | 814.31 | 20.78 | 50.33 | 181.50 |
Annual Sum or Average | 4125.67 | 0.64 | 2262.24 | 18.87 | 1073.00 | 3532.17 | 1098.02 | 20.44 | 709.33 | 2951.17 | ||
Minimum of Months | 268.33 | 0.64 | 0.62 | 1563.22 | 17.56 | 77.50 | 232.67 | 814.31 | 19.48 | 41.00 | 168.83 | |
Maximum of Months | 408.83 | 0.65 | 0.62 | 2931.20 | 21.05 | 111.50 | 354.50 | 1305.48 | 21.99 | 72.67 | 315.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.66 | 0.62 | 01-JAN-08:30 | 424.57 | 12.97 | 0.00 | 197.00 | 285.61 | 16.28 | 0.00 | 61.17 |
February | 268.33 | 0.65 | 0.62 | 01-FEB-08:30 | 483.83 | 13.80 | 0.00 | 208.83 | 324.64 | 16.93 | 0.00 | 104.33 |
March | 351.83 | 0.65 | 0.62 | 01-MAR-07:30 | 573.05 | 14.73 | 0.00 | 281.83 | 369.95 | 17.62 | 0.00 | 193.33 |
April | 373.83 | 0.63 | 0.62 | 01-APR-06:19 | 680.33 | 16.06 | 0.00 | 343.67 | 437.31 | 18.80 | 0.00 | 281.67 |
May | 408.83 | 0.63 | 0.62 | 01-MAY-05:49 | 844.14 | 16.91 | 3.00 | 381.00 | 489.67 | 19.52 | 8.33 | 348.83 |
June | 398.00 | 0.62 | 0.62 | 01-JUN-05:49 | 908.17 | 20.23 | 83.17 | 378.17 | 513.83 | 19.87 | 27.67 | 348.00 |
July | 400.17 | 0.63 | 0.62 | 01-JUL-05:49 | 860.32 | 18.38 | 37.17 | 384.00 | 492.33 | 19.71 | 16.17 | 332.83 |
August | 377.83 | 0.63 | 0.62 | 01-AUG-05:00 | 730.07 | 16.37 | 0.00 | 355.00 | 456.26 | 19.08 | 0.00 | 301.50 |
September | 365.83 | 0.64 | 0.62 | 01-SEP-06:00 | 568.60 | 15.14 | 0.00 | 289.33 | 374.66 | 17.99 | 0.00 | 201.83 |
October | 318.83 | 0.65 | 0.62 | 01-OCT-07:19 | 509.40 | 14.17 | 0.00 | 262.83 | 338.58 | 17.20 | 0.00 | 146.50 |
November | 295.83 | 0.66 | 0.62 | 01-NOV-12:39 | 411.45 | 12.97 | 0.00 | 196.50 | 279.85 | 16.24 | 0.00 | 57.00 |
December | 289.50 | 0.66 | 0.62 | 01-DEC-07:00 | 425.34 | 12.99 | 0.00 | 205.33 | 281.14 | 16.23 | 0.00 | 52.50 |
Annual Sum or Average | 4125.67 | 0.64 | 641.17 | 15.67 | 123.33 | 3483.50 | 398.27 | 18.14 | 52.17 | 2429.50 | ||
Minimum of Months | 268.33 | 0.62 | 0.62 | 411.45 | 12.97 | 0.00 | 196.50 | 279.85 | 16.23 | 0.00 | 52.50 | |
Maximum of Months | 408.83 | 0.66 | 0.62 | 908.17 | 20.23 | 83.17 | 384.00 | 513.83 | 19.87 | 27.67 | 348.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.64 | 0.62 | 01-JAN-08:30 | 1718.70 | 19.91 | 81.17 | 242.33 | 904.33 | 20.90 | 52.33 | 180.67 |
February | 268.33 | 0.64 | 0.62 | 01-FEB-08:30 | 1936.00 | 18.91 | 70.83 | 236.67 | 1097.36 | 22.11 | 61.33 | 188.67 |
March | 351.83 | 0.64 | 0.62 | 01-MAR-07:40 | 2575.25 | 20.29 | 110.33 | 305.67 | 965.73 | 19.76 | 52.50 | 258.50 |
April | 373.83 | 0.63 | 0.62 | 01-APR-07:10 | 2870.05 | 19.78 | 111.83 | 329.33 | 1124.18 | 19.61 | 51.83 | 290.50 |
May | 408.83 | 0.64 | 0.62 | 01-MAY-06:30 | 2146.36 | 12.42 | 0.00 | 364.50 | 1238.15 | 16.68 | 0.00 | 326.67 |
June | 398.00 | 0.63 | 0.62 | 01-JUN-06:19 | 2322.33 | 12.50 | 0.00 | 363.33 | 1272.21 | 16.80 | 0.00 | 316.50 |
July | 400.17 | 0.63 | 0.62 | 01-JUL-06:30 | 2066.22 | 12.84 | 3.67 | 366.67 | 1135.64 | 16.84 | 0.00 | 306.33 |
August | 377.83 | 0.64 | 0.62 | 01-AUG-06:30 | 2069.47 | 16.11 | 57.17 | 337.17 | 1095.26 | 16.93 | 3.67 | 292.00 |
September | 365.83 | 0.64 | 0.62 | 01-SEP-07:30 | 2522.99 | 19.76 | 110.17 | 300.67 | 980.89 | 19.75 | 55.83 | 257.33 |
October | 318.83 | 0.64 | 0.62 | 01-OCT-07:19 | 2122.75 | 19.42 | 86.17 | 289.00 | 1159.62 | 21.91 | 69.00 | 235.17 |
November | 295.83 | 0.64 | 0.62 | 01-NOV-12:39 | 1627.78 | 19.77 | 86.17 | 244.33 | 808.61 | 20.50 | 54.00 | 187.17 |
December | 289.50 | 0.64 | 0.62 | 01-DEC-08:09 | 1795.43 | 21.86 | 105.67 | 245.33 | 722.13 | 21.14 | 51.83 | 183.50 |
Annual Sum or Average | 4125.67 | 0.64 | 2178.06 | 17.45 | 823.17 | 3625.00 | 1057.40 | 19.16 | 452.33 | 3023.00 | ||
Minimum of Months | 268.33 | 0.63 | 0.62 | 1627.78 | 12.42 | 0.00 | 236.67 | 722.13 | 16.68 | 0.00 | 180.67 | |
Maximum of Months | 408.83 | 0.64 | 0.62 | 2870.05 | 21.86 | 111.83 | 366.67 | 1272.21 | 22.11 | 69.00 | 326.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.63 | 0.62 | 01-JAN-07:00 | 7701.95 | 36.63 | 265.17 | 273.67 | 1526.14 | 23.45 | 97.17 | 257.67 |
February | 268.33 | 0.63 | 0.62 | 01-FEB-07:49 | 8374.99 | 36.20 | 261.33 | 264.33 | 1089.80 | 19.19 | 34.67 | 237.50 |
March | 351.83 | 0.64 | 0.62 | 01-MAR-07:10 | 1622.43 | 13.40 | 10.67 | 310.67 | 820.64 | 16.87 | 1.83 | 276.00 |
April | 373.83 | 0.64 | 0.62 | 01-APR-06:30 | 1001.94 | 13.06 | 0.00 | 323.50 | 617.96 | 17.08 | 0.00 | 275.17 |
May | 408.83 | 0.65 | 0.62 | 01-MAY-06:19 | 822.46 | 12.90 | 0.00 | 347.33 | 507.58 | 16.86 | 0.00 | 293.00 |
June | 398.00 | 0.64 | 0.62 | 01-JUN-06:19 | 735.77 | 12.64 | 0.00 | 339.67 | 467.32 | 16.74 | 0.00 | 277.17 |
July | 400.17 | 0.65 | 0.62 | 01-JUL-06:19 | 785.86 | 12.70 | 0.00 | 344.00 | 479.04 | 16.72 | 0.00 | 265.17 |
August | 377.83 | 0.64 | 0.62 | 01-AUG-06:19 | 928.61 | 13.07 | 0.00 | 333.50 | 562.59 | 17.04 | 0.00 | 274.33 |
September | 365.83 | 0.64 | 0.62 | 01-SEP-06:00 | 1191.26 | 13.34 | 11.00 | 305.50 | 694.99 | 16.86 | 0.00 | 263.00 |
October | 318.83 | 0.63 | 0.62 | 01-OCT-06:49 | 3053.87 | 21.12 | 128.00 | 306.83 | 970.26 | 17.62 | 13.33 | 273.00 |
November | 295.83 | 0.63 | 0.62 | 01-NOV-12:39 | 7890.63 | 35.70 | 278.33 | 279.83 | 1231.66 | 21.77 | 90.00 | 269.33 |
December | 289.50 | 0.63 | 0.62 | 01-DEC-07:19 | 6972.88 | 37.13 | 284.00 | 272.67 | 1504.12 | 23.48 | 101.33 | 265.17 |
Annual Sum or Average | 4125.67 | 0.64 | 3001.14 | 20.04 | 1238.50 | 3701.50 | 823.10 | 18.34 | 338.33 | 3226.50 | ||
Minimum of Months | 268.33 | 0.63 | 0.62 | 735.77 | 12.64 | 0.00 | 264.33 | 467.32 | 16.72 | 0.00 | 237.50 | |
Maximum of Months | 408.83 | 0.65 | 0.62 | 8374.99 | 37.13 | 284.00 | 347.33 | 1526.14 | 23.48 | 101.33 | 293.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.65 | 0.62 | 01-JAN-08:09 | 1954.29 | 19.07 | 79.83 | 228.33 | 1119.39 | 21.77 | 63.33 | 165.33 |
February | 268.33 | 0.65 | 0.62 | 01-FEB-07:40 | 2488.41 | 20.64 | 89.67 | 233.33 | 884.99 | 19.96 | 41.00 | 178.17 |
March | 351.83 | 0.64 | 0.62 | 01-MAR-06:00 | 2149.27 | 17.67 | 82.33 | 289.50 | 1178.26 | 20.93 | 70.83 | 249.83 |
April | 373.83 | 0.64 | 0.62 | 01-APR-06:10 | 2855.13 | 19.39 | 109.83 | 323.00 | 1043.80 | 19.30 | 50.83 | 285.17 |
May | 408.83 | 0.64 | 0.62 | 01-MAY-05:49 | 2176.52 | 17.22 | 87.00 | 351.50 | 1217.90 | 20.42 | 72.67 | 311.17 |
June | 398.00 | 0.64 | 0.62 | 01-JUN-05:49 | 2223.27 | 17.28 | 85.00 | 346.00 | 1250.17 | 20.48 | 70.00 | 305.33 |
July | 400.17 | 0.64 | 0.62 | 01-JUL-05:49 | 1975.91 | 17.14 | 84.17 | 350.67 | 1074.65 | 20.32 | 69.00 | 296.83 |
August | 377.83 | 0.64 | 0.62 | 01-AUG-05:49 | 2566.77 | 19.10 | 109.50 | 332.50 | 965.84 | 19.35 | 52.33 | 288.83 |
September | 365.83 | 0.64 | 0.62 | 01-SEP-06:10 | 2475.02 | 19.55 | 111.50 | 298.17 | 925.71 | 19.70 | 57.67 | 260.83 |
October | 318.83 | 0.65 | 0.62 | 01-OCT-06:49 | 2061.60 | 17.97 | 77.67 | 271.83 | 1143.67 | 20.78 | 60.67 | 213.33 |
November | 295.83 | 0.65 | 0.62 | 01-NOV-12:39 | 1694.89 | 17.89 | 73.50 | 233.67 | 870.55 | 19.78 | 50.67 | 169.33 |
December | 289.50 | 0.65 | 0.62 | 01-DEC-07:10 | 1389.55 | 17.48 | 61.83 | 230.50 | 777.40 | 20.55 | 50.33 | 175.50 |
Annual Sum or Average | 4125.67 | 0.65 | 2189.68 | 18.30 | 1051.83 | 3489.00 | 1049.15 | 20.25 | 709.33 | 2899.67 | ||
Minimum of Months | 268.33 | 0.64 | 0.62 | 1389.55 | 17.14 | 61.83 | 228.33 | 777.40 | 19.30 | 41.00 | 165.33 | |
Maximum of Months | 408.83 | 0.65 | 0.62 | 2855.13 | 20.64 | 111.50 | 351.50 | 1250.17 | 21.77 | 72.67 | 311.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.67 | 0.62 | 01-JAN-08:30 | 406.44 | 9.50 | 0.00 | 184.83 | 276.44 | 13.93 | 0.00 | 50.83 |
February | 268.33 | 0.66 | 0.62 | 01-FEB-08:30 | 463.79 | 10.50 | 0.00 | 201.33 | 314.56 | 14.79 | 0.00 | 96.00 |
March | 351.83 | 0.65 | 0.62 | 01-MAR-07:30 | 550.66 | 11.48 | 0.00 | 276.83 | 358.66 | 15.62 | 0.00 | 185.17 |
April | 373.83 | 0.63 | 0.62 | 01-APR-06:19 | 653.69 | 12.95 | 0.00 | 342.67 | 423.74 | 17.04 | 0.00 | 274.67 |
May | 408.83 | 0.63 | 0.62 | 01-MAY-05:00 | 811.42 | 13.61 | 3.00 | 380.00 | 472.19 | 17.59 | 0.00 | 344.50 |
June | 398.00 | 0.63 | 0.62 | 01-JUN-05:49 | 873.39 | 17.49 | 83.17 | 377.33 | 496.36 | 17.77 | 1.33 | 345.83 |
July | 400.17 | 0.63 | 0.62 | 01-JUL-05:49 | 826.05 | 15.24 | 37.17 | 382.17 | 502.07 | 19.15 | 37.50 | 333.67 |
August | 377.83 | 0.63 | 0.62 | 01-AUG-05:00 | 700.59 | 13.14 | 0.00 | 353.00 | 440.90 | 17.22 | 0.00 | 293.50 |
September | 365.83 | 0.65 | 0.62 | 01-SEP-07:10 | 545.86 | 12.03 | 0.00 | 283.50 | 363.23 | 16.16 | 0.00 | 194.00 |
October | 318.83 | 0.65 | 0.62 | 01-OCT-07:19 | 488.71 | 10.94 | 0.00 | 255.67 | 328.17 | 15.16 | 0.00 | 134.33 |
November | 295.83 | 0.67 | 0.62 | 01-NOV-12:39 | 394.33 | 9.54 | 0.00 | 183.50 | 271.28 | 13.97 | 0.00 | 45.50 |
December | 289.50 | 0.67 | 0.62 | 01-DEC-08:09 | 406.60 | 9.54 | 0.00 | 193.67 | 271.53 | 13.89 | 0.00 | 38.83 |
Annual Sum or Average | 4125.67 | 0.64 | 615.55 | 12.46 | 123.33 | 3414.50 | 387.82 | 16.25 | 38.83 | 2336.83 | ||
Minimum of Months | 268.33 | 0.63 | 0.62 | 394.33 | 9.50 | 0.00 | 183.50 | 271.28 | 13.89 | 0.00 | 38.83 | |
Maximum of Months | 408.83 | 0.67 | 0.62 | 873.39 | 17.49 | 83.17 | 382.17 | 502.07 | 19.15 | 37.50 | 345.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.64 | 0.62 | 01-JAN-08:39 | 1666.41 | 19.57 | 81.17 | 237.33 | 862.52 | 20.79 | 52.33 | 175.00 |
February | 268.33 | 0.64 | 0.62 | 01-FEB-08:39 | 1882.67 | 18.53 | 70.83 | 232.83 | 1056.89 | 21.99 | 61.33 | 184.50 |
March | 351.83 | 0.64 | 0.62 | 01-MAR-07:49 | 2516.77 | 19.93 | 110.33 | 301.17 | 919.01 | 19.63 | 52.50 | 254.50 |
April | 373.83 | 0.64 | 0.62 | 01-APR-07:10 | 2803.48 | 19.40 | 111.83 | 325.00 | 1023.78 | 19.45 | 51.83 | 285.67 |
May | 408.83 | 0.64 | 0.62 | 01-MAY-06:30 | 2070.82 | 11.97 | 0.00 | 361.17 | 1187.05 | 16.50 | 0.00 | 322.50 |
June | 398.00 | 0.63 | 0.62 | 01-JUN-06:30 | 2156.27 | 12.04 | 0.00 | 358.33 | 1222.61 | 16.62 | 0.00 | 312.67 |
July | 400.17 | 0.64 | 0.62 | 01-JUL-06:30 | 2002.91 | 12.37 | 3.67 | 361.50 | 1090.13 | 16.64 | 0.00 | 300.83 |
August | 377.83 | 0.64 | 0.62 | 01-AUG-06:30 | 2001.28 | 15.68 | 57.17 | 332.17 | 1046.79 | 16.75 | 3.67 | 287.00 |
September | 365.83 | 0.64 | 0.62 | 01-SEP-07:30 | 2463.84 | 19.38 | 110.17 | 296.83 | 932.97 | 19.61 | 55.83 | 254.17 |
October | 318.83 | 0.64 | 0.62 | 01-OCT-07:30 | 2060.53 | 19.05 | 86.17 | 283.33 | 1110.93 | 21.80 | 69.00 | 232.00 |
November | 295.83 | 0.65 | 0.62 | 01-NOV-12:39 | 1570.23 | 19.05 | 82.33 | 239.00 | 769.60 | 20.39 | 54.00 | 183.67 |
December | 289.50 | 0.65 | 0.62 | 01-DEC-08:09 | 1626.80 | 19.03 | 82.83 | 237.33 | 687.70 | 21.04 | 52.00 | 176.17 |
Annual Sum or Average | 4125.67 | 0.64 | 2098.15 | 16.85 | 796.50 | 3566.00 | 1006.95 | 19.01 | 452.50 | 2968.67 | ||
Minimum of Months | 268.33 | 0.63 | 0.62 | 1570.23 | 11.97 | 0.00 | 232.83 | 687.70 | 16.50 | 0.00 | 175.00 | |
Maximum of Months | 408.83 | 0.65 | 0.62 | 2803.48 | 19.93 | 111.83 | 361.50 | 1222.61 | 21.99 | 69.00 | 322.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.63 | 0.62 | 01-JAN-07:00 | 7701.96 | 36.63 | 265.17 | 273.67 | 1526.09 | 23.45 | 97.17 | 257.67 |
February | 268.33 | 0.63 | 0.62 | 01-FEB-07:49 | 8374.97 | 36.21 | 261.33 | 264.33 | 1089.75 | 19.19 | 34.67 | 237.50 |
March | 351.83 | 0.64 | 0.62 | 01-MAR-07:10 | 1622.39 | 13.41 | 10.67 | 310.67 | 820.60 | 16.87 | 1.83 | 276.00 |
April | 373.83 | 0.64 | 0.62 | 01-APR-06:30 | 1001.92 | 13.06 | 0.00 | 323.50 | 617.93 | 17.08 | 0.00 | 275.17 |
May | 408.83 | 0.65 | 0.62 | 01-MAY-06:19 | 822.44 | 12.90 | 0.00 | 347.33 | 507.56 | 16.86 | 0.00 | 293.00 |
June | 398.00 | 0.64 | 0.62 | 01-JUN-06:19 | 735.76 | 12.64 | 0.00 | 339.67 | 467.30 | 16.74 | 0.00 | 276.83 |
July | 400.17 | 0.65 | 0.62 | 01-JUL-06:19 | 785.84 | 12.70 | 0.00 | 344.00 | 479.02 | 16.72 | 0.00 | 265.17 |
August | 377.83 | 0.64 | 0.62 | 01-AUG-06:19 | 928.58 | 13.07 | 0.00 | 333.50 | 562.56 | 17.04 | 0.00 | 274.33 |
September | 365.83 | 0.64 | 0.62 | 01-SEP-06:00 | 1191.23 | 13.35 | 11.00 | 305.50 | 694.96 | 16.86 | 0.00 | 263.00 |
October | 318.83 | 0.63 | 0.62 | 01-OCT-06:49 | 3053.84 | 21.12 | 128.00 | 306.83 | 970.21 | 17.62 | 13.33 | 273.00 |
November | 295.83 | 0.63 | 0.62 | 01-NOV-12:39 | 7890.63 | 35.70 | 278.33 | 279.83 | 1231.61 | 21.77 | 90.00 | 269.33 |
December | 289.50 | 0.63 | 0.62 | 01-DEC-07:19 | 6972.90 | 37.13 | 284.00 | 272.67 | 1504.06 | 23.48 | 101.33 | 265.17 |
Annual Sum or Average | 4125.67 | 0.64 | 3001.12 | 20.04 | 1238.50 | 3701.50 | 823.06 | 18.34 | 338.33 | 3226.17 | ||
Minimum of Months | 268.33 | 0.63 | 0.62 | 735.76 | 12.64 | 0.00 | 264.33 | 467.30 | 16.72 | 0.00 | 237.50 | |
Maximum of Months | 408.83 | 0.65 | 0.62 | 8374.97 | 37.13 | 284.00 | 347.33 | 1526.09 | 23.48 | 101.33 | 293.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.65 | 0.62 | 01-JAN-08:09 | 1954.30 | 19.07 | 79.83 | 228.33 | 1119.36 | 21.77 | 63.33 | 165.33 |
February | 268.33 | 0.65 | 0.62 | 01-FEB-07:40 | 2488.42 | 20.65 | 89.67 | 233.33 | 884.96 | 19.96 | 41.00 | 178.17 |
March | 351.83 | 0.64 | 0.62 | 01-MAR-06:00 | 2149.26 | 17.67 | 82.33 | 289.50 | 1178.22 | 20.94 | 70.83 | 249.83 |
April | 373.83 | 0.64 | 0.62 | 01-APR-06:10 | 2855.13 | 19.39 | 109.83 | 323.00 | 1043.76 | 19.30 | 50.83 | 285.17 |
May | 408.83 | 0.64 | 0.62 | 01-MAY-05:49 | 2176.52 | 17.22 | 87.00 | 351.50 | 1217.86 | 20.42 | 72.67 | 311.17 |
June | 398.00 | 0.64 | 0.62 | 01-JUN-05:49 | 2223.27 | 17.28 | 85.00 | 346.00 | 1250.14 | 20.48 | 70.00 | 305.33 |
July | 400.17 | 0.64 | 0.62 | 01-JUL-05:49 | 1975.91 | 17.14 | 84.17 | 350.67 | 1074.61 | 20.32 | 69.00 | 296.83 |
August | 377.83 | 0.64 | 0.62 | 01-AUG-05:49 | 2566.77 | 19.10 | 109.50 | 332.50 | 965.80 | 19.35 | 52.33 | 288.83 |
September | 365.83 | 0.64 | 0.62 | 01-SEP-06:10 | 2475.02 | 19.55 | 111.50 | 298.33 | 925.68 | 19.70 | 57.67 | 260.67 |
October | 318.83 | 0.65 | 0.62 | 01-OCT-06:49 | 2061.60 | 17.97 | 77.67 | 271.83 | 1143.64 | 20.78 | 60.67 | 213.33 |
November | 295.83 | 0.65 | 0.62 | 01-NOV-12:39 | 1694.90 | 17.89 | 73.50 | 233.67 | 870.53 | 19.78 | 50.67 | 169.33 |
December | 289.50 | 0.65 | 0.62 | 01-DEC-07:10 | 1389.56 | 17.48 | 61.83 | 230.50 | 777.37 | 20.55 | 50.33 | 175.50 |
Annual Sum or Average | 4125.67 | 0.65 | 2189.68 | 18.31 | 1051.83 | 3489.17 | 1049.12 | 20.25 | 709.33 | 2899.50 | ||
Minimum of Months | 268.33 | 0.64 | 0.62 | 1389.56 | 17.14 | 61.83 | 228.33 | 777.37 | 19.30 | 41.00 | 165.33 | |
Maximum of Months | 408.83 | 0.65 | 0.62 | 2855.13 | 20.65 | 111.50 | 351.50 | 1250.14 | 21.77 | 72.67 | 311.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.67 | 0.62 | 01-JAN-08:30 | 406.45 | 9.50 | 0.00 | 185.00 | 276.43 | 13.93 | 0.00 | 50.67 |
February | 268.33 | 0.66 | 0.62 | 01-FEB-08:30 | 463.80 | 10.50 | 0.00 | 201.33 | 314.54 | 14.79 | 0.00 | 96.00 |
March | 351.83 | 0.65 | 0.62 | 01-MAR-07:30 | 550.66 | 11.48 | 0.00 | 276.83 | 358.64 | 15.62 | 0.00 | 185.17 |
April | 373.83 | 0.63 | 0.62 | 01-APR-06:19 | 653.69 | 12.95 | 0.00 | 342.67 | 423.73 | 17.04 | 0.00 | 274.67 |
May | 408.83 | 0.63 | 0.62 | 01-MAY-05:00 | 811.41 | 13.61 | 3.00 | 380.00 | 472.17 | 17.59 | 0.00 | 344.50 |
June | 398.00 | 0.63 | 0.62 | 01-JUN-05:49 | 873.38 | 17.49 | 83.17 | 377.33 | 496.34 | 17.77 | 1.33 | 345.83 |
July | 400.17 | 0.63 | 0.62 | 01-JUL-05:49 | 826.04 | 15.24 | 37.17 | 382.17 | 502.04 | 19.15 | 37.50 | 333.67 |
August | 377.83 | 0.63 | 0.62 | 01-AUG-05:00 | 700.58 | 13.14 | 0.00 | 353.00 | 440.88 | 17.22 | 0.00 | 293.50 |
September | 365.83 | 0.65 | 0.62 | 01-SEP-07:10 | 545.86 | 12.03 | 0.00 | 283.50 | 363.21 | 16.16 | 0.00 | 194.00 |
October | 318.83 | 0.65 | 0.62 | 01-OCT-07:19 | 488.71 | 10.94 | 0.00 | 255.67 | 328.16 | 15.16 | 0.00 | 134.33 |
November | 295.83 | 0.67 | 0.62 | 01-NOV-12:39 | 394.34 | 9.54 | 0.00 | 183.50 | 271.27 | 13.97 | 0.00 | 45.50 |
December | 289.50 | 0.67 | 0.62 | 01-DEC-08:09 | 406.61 | 9.55 | 0.00 | 193.67 | 271.51 | 13.89 | 0.00 | 38.83 |
Annual Sum or Average | 4125.67 | 0.64 | 615.55 | 12.46 | 123.33 | 3414.67 | 387.80 | 16.25 | 38.83 | 2336.67 | ||
Minimum of Months | 268.33 | 0.63 | 0.62 | 394.34 | 9.50 | 0.00 | 183.50 | 271.27 | 13.89 | 0.00 | 38.83 | |
Maximum of Months | 408.83 | 0.67 | 0.62 | 873.38 | 17.49 | 83.17 | 382.17 | 502.04 | 19.15 | 37.50 | 345.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.64 | 0.62 | 01-JAN-08:39 | 1666.42 | 19.57 | 81.17 | 237.33 | 862.49 | 20.80 | 52.33 | 175.00 |
February | 268.33 | 0.64 | 0.62 | 01-FEB-08:39 | 1882.67 | 18.54 | 70.83 | 232.83 | 1056.86 | 21.99 | 61.33 | 184.50 |
March | 351.83 | 0.64 | 0.62 | 01-MAR-07:49 | 2516.76 | 19.93 | 110.33 | 301.17 | 918.98 | 19.63 | 52.50 | 254.50 |
April | 373.83 | 0.64 | 0.62 | 01-APR-07:10 | 2803.48 | 19.40 | 111.83 | 325.00 | 1023.75 | 19.45 | 51.83 | 285.67 |
May | 408.83 | 0.64 | 0.62 | 01-MAY-06:30 | 2070.81 | 11.97 | 0.00 | 361.17 | 1187.02 | 16.50 | 0.00 | 322.50 |
June | 398.00 | 0.63 | 0.62 | 01-JUN-06:30 | 2156.27 | 12.04 | 0.00 | 358.33 | 1222.57 | 16.62 | 0.00 | 312.67 |
July | 400.17 | 0.64 | 0.62 | 01-JUL-06:30 | 2002.90 | 12.37 | 3.67 | 361.50 | 1090.09 | 16.65 | 0.00 | 300.83 |
August | 377.83 | 0.64 | 0.62 | 01-AUG-06:30 | 2001.28 | 15.68 | 57.17 | 332.17 | 1046.75 | 16.75 | 3.67 | 287.00 |
September | 365.83 | 0.64 | 0.62 | 01-SEP-07:30 | 2463.84 | 19.38 | 110.17 | 296.83 | 932.94 | 19.61 | 55.83 | 254.17 |
October | 318.83 | 0.64 | 0.62 | 01-OCT-07:30 | 2060.54 | 19.06 | 86.17 | 283.33 | 1110.90 | 21.80 | 69.00 | 232.00 |
November | 295.83 | 0.65 | 0.62 | 01-NOV-12:39 | 1570.24 | 19.06 | 82.33 | 239.17 | 769.58 | 20.40 | 54.00 | 183.67 |
December | 289.50 | 0.65 | 0.62 | 01-DEC-08:09 | 1626.80 | 19.03 | 82.83 | 237.33 | 687.68 | 21.04 | 52.00 | 176.17 |
Annual Sum or Average | 4125.67 | 0.64 | 2098.15 | 16.85 | 796.50 | 3566.17 | 1006.92 | 19.01 | 452.50 | 2968.67 | ||
Minimum of Months | 268.33 | 0.63 | 0.62 | 1570.24 | 11.97 | 0.00 | 232.83 | 687.68 | 16.50 | 0.00 | 175.00 | |
Maximum of Months | 408.83 | 0.65 | 0.62 | 2803.48 | 19.93 | 111.83 | 361.50 | 1222.57 | 21.99 | 69.00 | 322.50 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.162982E+10 | 10103.19 | 26-JAN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146026E+10 | 10132.64 | 13-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130109E+10 | 10136.52 | 17-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.442722E+09 | 10297.78 | 17-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 92927467.02 | 10158.24 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38052548.35 | 10147.84 | 25-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304146E+09 | 10303.56 | 11-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.939120E+09 | 10287.59 | 13-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186412E+10 | 10075.35 | 27-DEC-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.807226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.186412E+10 | 10303.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.148304E+09 | 7212.13 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 64609588.70 | 7212.13 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 39730623.29 | 7212.13 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11630461.55 | 7212.13 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153895E+09 | 7212.13 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.418170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.153895E+09 | 7212.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.423681E+09 | 9054.42 | 17-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.304832E+09 | 9074.80 | 28-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148845E+09 | 9023.53 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 590249.64 | 1449.21 | 12-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32349707.42 | 9016.61 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.431385E+09 | 9050.82 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.431385E+09 | 9074.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.180816E+09 | 7148.83 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131707E+09 | 7148.83 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 57880250.39 | 7148.83 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15000517.40 | 7148.83 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195858E+09 | 7148.83 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.581262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.195858E+09 | 7148.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 4629085.90 | 14785.10 | 17-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12667649.56 | 22492.62 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17296735.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12667649.56 | 22492.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.168679E+09 | 10687.19 | 24-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 61604976.63 | 10634.26 | 15-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27056333.62 | 10629.75 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 41505771.71 | 10671.70 | 30-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.234001E+09 | 10708.85 | 26-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.532847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.234001E+09 | 10708.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.262070E+09 | 7880.84 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 79008382.24 | 7880.84 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 35958763.06 | 7880.84 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 63361245.95 | 7880.84 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.353534E+09 | 7880.84 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.793932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.353534E+09 | 7880.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.421743E+09 | 9621.56 | 26-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177898E+09 | 9610.08 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 63936812.65 | 9596.72 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107574E+09 | 9641.44 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.618826E+09 | 9678.59 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.618826E+09 | 9678.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.328980E+09 | 7825.18 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150871E+09 | 7825.18 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 53037334.56 | 7825.18 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 101847.67 | 742.61 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 95303096.42 | 7825.18 | 17-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.447639E+09 | 7825.18 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.447639E+09 | 7825.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.535776E+09 | 33499.53 | 26-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156781E+09 | 33357.90 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 35633174.17 | 33378.52 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188405E+09 | 33560.37 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.882605E+09 | 33647.91 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.882605E+09 | 33647.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.785089E+09 | 12472.70 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.420033E+09 | 12390.94 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.265217E+09 | 12364.99 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23919393.40 | 12312.91 | 12-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2572110.93 | 4376.33 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324689E+09 | 12440.75 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.977432E+09 | 12435.97 | 05-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.977432E+09 | 12472.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.790321E+09 | 9779.44 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.366276E+09 | 9680.77 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189066E+09 | 9668.99 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4315867.26 | 6219.29 | 12-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6418212.32 | 5805.27 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.298981E+09 | 9754.67 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100371E+10 | 9745.07 | 28-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100371E+10 | 9779.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.153966E+10 | 11331.11 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.842738E+09 | 11322.85 | 17-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.398191E+09 | 11263.77 | 01-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22972676.37 | 11203.48 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5119555.89 | 6386.71 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.593930E+09 | 11302.15 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.198438E+10 | 11336.82 | 04-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.538699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.198438E+10 | 11336.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108405E+10 | 10130.62 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.640273E+09 | 10130.62 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.317803E+09 | 10130.62 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26677911.34 | 8833.90 | 12-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10429300.34 | 4812.64 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.459927E+09 | 10130.62 | 13-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135477E+10 | 10130.62 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135477E+10 | 10130.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.641996E+09 | 10160.96 | 27-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.439456E+09 | 10818.18 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226182E+09 | 7866.80 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 515707.04 | 1426.35 | 12-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119625E+09 | 5879.07 | 28-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125630E+10 | 10869.63 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.268408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.125630E+10 | 10869.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.134176E+10 | 11189.87 | 27-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.858959E+09 | 11745.79 | 03-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.492631E+09 | 8999.29 | 02-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25134298.17 | 3336.50 | 12-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1680474.89 | 739.90 | 25-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.450142E+09 | 7472.50 | 28-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.215057E+10 | 12222.16 | 27-DEC-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.532088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.215057E+10 | 12222.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.183470E+10 | 13864.71 | 27-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120506E+10 | 14748.98 | 03-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.763080E+09 | 11767.28 | 02-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 67091889.21 | 5227.58 | 12-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14186864.32 | 2406.07 | 25-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.685458E+09 | 9436.94 | 28-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.266641E+10 | 14838.92 | 27-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.723598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.266641E+10 | 14838.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.923983E+09 | 0.917586E+09 | 16845.57 | 03-JAN-15:00 | 16845.57 | 0.00 |
February | 0.00 | 0.00 | 0.330910E+10 | 0.329359E+10 | 28428.43 | 21-FEB-16:20 | 28428.43 | 0.00 |
March | 0.00 | 0.00 | 0.834563E+10 | 0.832886E+10 | 35050.63 | 21-MAR-16:00 | 35050.63 | 0.00 |
April | 0.00 | 0.00 | 0.258519E+11 | 0.256911E+11 | 56592.67 | 21-APR-15:10 | 56592.67 | 0.00 |
May | 0.00 | 0.00 | 0.507966E+11 | 0.495404E+11 | 68796.77 | 30-MAY-15:30 | 68796.77 | 0.00 |
June | 0.00 | 0.00 | 0.698736E+11 | 0.674525E+11 | 76456.57 | 19-JUN-06:03 | 61504.59 | 0.00 |
July | 0.00 | 0.00 | 0.822728E+11 | 0.667648E+11 | 117341.85 | 20-JUL-14:55 | 41080.65 | 0.00 |
August | 0.00 | 0.00 | 0.761776E+11 | 0.660113E+11 | 110788.97 | 03-AUG-06:03 | 46895.73 | 0.00 |
September | 0.00 | 0.00 | 0.630229E+11 | 0.550358E+11 | 97242.94 | 14-SEP-09:50 | 49912.58 | 0.00 |
October | 0.00 | 0.00 | 0.326102E+11 | 0.292740E+11 | 74433.29 | 04-OCT-10:40 | 47766.31 | 0.00 |
November | 0.00 | 0.00 | 0.716611E+10 | 0.703251E+10 | 41795.47 | 03-NOV-16:00 | 41795.47 | 0.00 |
December | 0.00 | 0.00 | 0.318776E+09 | 0.317690E+09 | 7904.85 | 08-DEC-14:00 | 7904.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.420669E+12 | 0.379660E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.318776E+09 | 0.317690E+09 | 7904.85 | 7904.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.822728E+11 | 0.674525E+11 | 117341.85 | 68796.77 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.720285E+09 | 0.713037E+09 | 12690.02 | 03-JAN-15:00 | 12690.02 | 0.00 |
February | 0.00 | 0.00 | 0.302278E+10 | 0.300752E+10 | 24126.91 | 21-FEB-16:00 | 24126.91 | 0.00 |
March | 0.00 | 0.00 | 0.754883E+10 | 0.754218E+10 | 31369.96 | 21-MAR-16:00 | 31369.96 | 0.00 |
April | 0.00 | 0.00 | 0.242080E+11 | 0.240859E+11 | 54482.13 | 21-APR-15:00 | 54482.13 | 0.00 |
May | 0.00 | 0.00 | 0.461985E+11 | 0.453327E+11 | 67402.28 | 30-MAY-06:03 | 67402.28 | 0.00 |
June | 0.00 | 0.00 | 0.635638E+11 | 0.618977E+11 | 73133.16 | 19-JUN-06:03 | 59253.60 | 0.00 |
July | 0.00 | 0.00 | 0.715056E+11 | 0.593301E+11 | 105436.91 | 20-JUL-14:55 | 36927.65 | 0.00 |
August | 0.00 | 0.00 | 0.634172E+11 | 0.563683E+11 | 90811.84 | 03-AUG-05:03 | 40698.42 | 0.00 |
September | 0.00 | 0.00 | 0.507899E+11 | 0.452671E+11 | 78848.65 | 14-SEP-09:50 | 41049.52 | 0.00 |
October | 0.00 | 0.00 | 0.259039E+11 | 0.234486E+11 | 65602.08 | 02-OCT-04:02 | 65602.08 | 0.00 |
November | 0.00 | 0.00 | 0.567970E+10 | 0.554025E+10 | 33643.96 | 03-NOV-16:00 | 33643.96 | 0.00 |
December | 0.00 | 0.00 | 0.257877E+09 | 0.257254E+09 | 5762.80 | 23-DEC-15:00 | 5762.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.362816E+12 | 0.332791E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.257877E+09 | 0.257254E+09 | 5762.80 | 5762.80 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.715056E+11 | 0.618977E+11 | 105436.91 | 67402.28 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.685892E+09 | 0.668913E+09 | 12118.83 | 03-JAN-15:00 | 12118.83 | 0.00 |
February | 0.00 | 0.00 | 0.293737E+10 | 0.291142E+10 | 25639.89 | 20-FEB-14:32 | 25639.89 | 0.00 |
March | 0.00 | 0.00 | 0.763200E+10 | 0.761090E+10 | 34660.07 | 21-MAR-16:00 | 34660.07 | 0.00 |
April | 0.00 | 0.00 | 0.266224E+11 | 0.264252E+11 | 63580.07 | 21-APR-14:40 | 63580.07 | 0.00 |
May | 0.00 | 0.00 | 0.512109E+11 | 0.500156E+11 | 77319.40 | 21-MAY-14:42 | 77319.40 | 0.00 |
June | 0.00 | 0.00 | 0.714198E+11 | 0.692821E+11 | 81693.86 | 15-JUN-04:02 | 81693.86 | 0.00 |
July | 0.00 | 0.00 | 0.792052E+11 | 0.660903E+11 | 121283.21 | 20-JUL-14:55 | 42459.62 | 0.00 |
August | 0.00 | 0.00 | 0.698478E+11 | 0.617975E+11 | 82058.10 | 02-AUG-05:03 | 32676.24 | 0.00 |
September | 0.00 | 0.00 | 0.550140E+11 | 0.488296E+11 | 84102.84 | 14-SEP-10:00 | 42732.33 | 0.00 |
October | 0.00 | 0.00 | 0.268524E+11 | 0.240021E+11 | 72523.08 | 03-OCT-13:50 | 63921.09 | 0.00 |
November | 0.00 | 0.00 | 0.525726E+10 | 0.506060E+10 | 34220.39 | 09-NOV-15:00 | 34220.39 | 0.00 |
December | 0.00 | 0.00 | 0.243756E+09 | 0.241105E+09 | 5823.16 | 23-DEC-15:00 | 5823.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.396929E+12 | 0.362936E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.243756E+09 | 0.241105E+09 | 5823.16 | 5823.16 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.792052E+11 | 0.692821E+11 | 121283.21 | 81693.86 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1699.73 | 5909.58 | 31-JAN-12:09 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1708.17 | 5900.47 | 02-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1757.70 | 5776.57 | 01-MAR-12:25 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1542.99 | 5432.25 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1480.74 | 5074.46 | 01-MAY-11:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1409.17 | 4656.39 | 02-JUN-11:17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1237.87 | 4381.49 | 03-JUL-11:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1359.53 | 4364.38 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1331.21 | 4645.76 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1430.08 | 5067.03 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1567.81 | 5500.10 | 30-NOV-12:07 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1600.39 | 5780.30 | 28-DEC-12:10 |
Annual Sum or Average | 0.00 | 1509.35 | ||||
Minimum of Months | 0.00 | 0.00 | 1237.87 | 4364.38 | ||
Maximum of Months | 0.00 | 0.00 | 1757.70 | 5909.58 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.177749E+10 | 0.33 | 2754.92 | 26-JAN-08:03 | 0.84 |
February | 0.178641E+10 | 0.34 | 3707.59 | 22-FEB-06:02 | 1.00 |
March | 0.236893E+10 | 0.38 | 4527.83 | 10-MAR-06:03 | 1.12 |
April | 0.335270E+10 | 0.44 | 6920.18 | 21-APR-15:10 | 1.44 |
May | 0.519906E+10 | 0.56 | 10082.52 | 30-MAY-12:07 | 1.82 |
June | 0.662970E+10 | 0.66 | 12155.30 | 05-JUN-12:20 | 2.04 |
July | 0.644587E+10 | 0.63 | 12155.30 | 03-JUL-06:03 | 2.04 |
August | 0.653971E+10 | 0.64 | 12155.30 | 07-AUG-04:02 | 2.04 |
September | 0.544017E+10 | 0.58 | 9328.57 | 05-SEP-07:08 | 1.72 |
October | 0.419252E+10 | 0.49 | 10584.77 | 02-OCT-06:03 | 1.87 |
November | 0.268993E+10 | 0.39 | 5653.63 | 09-NOV-16:40 | 1.27 |
December | 0.171696E+10 | 0.32 | 2502.86 | 22-DEC-08:02 | 0.80 |
Annual Sum or Average | 0.481394E+11 | 0.48 | |||
Minimum of Months | 0.171696E+10 | 0.32 | 2502.86 | 0.80 | |
Maximum of Months | 0.662970E+10 | 0.66 | 12155.30 | 2.04 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141213E+10 | 0.32 | 2105.79 | 12-JAN-15:40 | 0.79 |
February | 0.141553E+10 | 0.34 | 2850.13 | 21-FEB-16:30 | 0.93 |
March | 0.193852E+10 | 0.37 | 4346.10 | 16-MAR-15:30 | 1.18 |
April | 0.307530E+10 | 0.46 | 7233.03 | 21-APR-14:40 | 1.61 |
May | 0.489389E+10 | 0.58 | 9928.29 | 30-MAY-16:00 | 1.96 |
June | 0.643214E+10 | 0.69 | 10711.75 | 15-JUN-04:02 | 2.07 |
July | 0.604565E+10 | 0.65 | 10711.75 | 03-JUL-06:03 | 2.06 |
August | 0.600845E+10 | 0.65 | 10711.75 | 07-AUG-04:02 | 2.05 |
September | 0.463508E+10 | 0.56 | 8184.57 | 21-SEP-15:40 | 1.72 |
October | 0.309690E+10 | 0.44 | 10525.35 | 02-OCT-04:02 | 2.03 |
November | 0.181397E+10 | 0.36 | 4399.99 | 09-NOV-16:10 | 1.18 |
December | 0.136447E+10 | 0.31 | 2441.88 | 04-DEC-07:01 | 0.85 |
Annual Sum or Average | 0.421320E+11 | 0.48 | |||
Minimum of Months | 0.136447E+10 | 0.31 | 2105.79 | 0.79 | |
Maximum of Months | 0.643214E+10 | 0.69 | 10711.75 | 2.07 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142990E+10 | 0.31 | 2517.48 | 02-JAN-07:01 | 0.79 |
February | 0.138798E+10 | 0.33 | 2517.48 | 01-FEB-07:01 | 0.79 |
March | 0.183031E+10 | 0.35 | 4032.36 | 16-MAR-15:30 | 1.02 |
April | 0.283554E+10 | 0.42 | 7212.38 | 21-APR-15:00 | 1.44 |
May | 0.458392E+10 | 0.51 | 10229.32 | 30-MAY-14:50 | 1.78 |
June | 0.628553E+10 | 0.62 | 11529.13 | 15-JUN-04:02 | 1.94 |
July | 0.585397E+10 | 0.58 | 12639.94 | 20-JUL-14:50 | 2.02 |
August | 0.566944E+10 | 0.58 | 10900.29 | 07-AUG-15:00 | 1.85 |
September | 0.432351E+10 | 0.49 | 8661.50 | 05-SEP-15:30 | 1.60 |
October | 0.275099E+10 | 0.39 | 8862.01 | 02-OCT-04:02 | 1.63 |
November | 0.167222E+10 | 0.33 | 3811.85 | 09-NOV-15:50 | 0.98 |
December | 0.141099E+10 | 0.31 | 2517.48 | 22-DEC-07:01 | 0.79 |
Annual Sum or Average | 0.400343E+11 | 0.44 | |||
Minimum of Months | 0.138798E+10 | 0.31 | 2517.48 | 0.79 | |
Maximum of Months | 0.628553E+10 | 0.62 | 12639.94 | 2.02 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:10 | 0.22 | 0.22 | 56.65 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:01 | 0.22 | 0.22 | 56.38 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:01 | 0.22 | 0.22 | 56.63 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:05 | 0.22 | 0.22 | 56.18 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:03 | 0.22 | 0.22 | 56.62 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 56.31 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 57.30 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 57.50 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 56.40 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 57.54 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:03 | 0.22 | 0.22 | 56.64 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:02 | 0.22 | 0.22 | 57.08 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 56.18 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.54 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 56.97 | 56.97 | 1699.73 | 5909.58 | 31-JAN-12:09 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.88 | 56.88 | 1708.17 | 5900.47 | 02-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.98 | 56.98 | 1757.70 | 5776.57 | 01-MAR-12:25 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.66 | 56.66 | 1542.99 | 5432.25 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.92 | 56.92 | 1480.74 | 5074.46 | 01-MAY-11:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.58 | 56.58 | 1409.17 | 4656.39 | 02-JUN-11:17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.55 | 57.55 | 1237.87 | 4381.49 | 03-JUL-11:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.73 | 57.73 | 1359.53 | 4364.38 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.65 | 56.65 | 1331.21 | 4645.76 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.99 | 55.99 | 1430.08 | 5067.03 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.98 | 56.98 | 1567.81 | 5500.10 | 30-NOV-12:07 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.47 | 57.47 | 1600.39 | 5780.30 | 28-DEC-12:10 |
Annual Sum or Average | 0.00 | 1509.35 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.99 | 55.99 | 1237.87 | 4364.38 | ||
Maximum of Months | 0.00 | 0.00 | 57.73 | 57.73 | 1757.70 | 5909.58 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.441408E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.461736E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.606582E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.104451E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.186089E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.264002E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.285512E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.266718E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.216463E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.125839E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.551231E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.445330E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.169970E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.441408E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.285512E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.279790E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.268741E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.406983E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.930479E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.170037E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.244348E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.252352E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.228345E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.177355E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.957208E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.358721E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.310504E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.142368E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.268741E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.252352E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.635718E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.460538E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.503547E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.981442E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.181089E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.266646E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.272746E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.243705E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.186327E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.956470E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.492156E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.768403E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.163034E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.460538E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.272746E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.177749E+10 | 0.923983E+09 | 0.302462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178641E+10 | 0.330910E+10 | 0.240086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.236893E+10 | 0.834563E+10 | 0.177372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.335270E+10 | 0.258519E+11 | 0.443828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.519906E+10 | 0.507966E+11 | 92927467.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.662970E+10 | 0.698736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.644587E+10 | 0.822728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.653971E+10 | 0.761776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.544017E+10 | 0.630229E+11 | 38052548.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.419252E+10 | 0.326102E+11 | 0.304146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.268993E+10 | 0.716611E+10 | 0.111773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171696E+10 | 0.318776E+09 | 0.390156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.481394E+11 | 0.420669E+12 | 0.130974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.171696E+10 | 0.318776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.662970E+10 | 0.822728E+11 | 0.390156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141213E+10 | 0.720285E+09 | 0.252786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141553E+10 | 0.302278E+10 | 0.132834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193852E+10 | 0.754883E+10 | 0.672620E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.307530E+10 | 0.242080E+11 | 25236145.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.489389E+10 | 0.461985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.643214E+10 | 0.635638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.604565E+10 | 0.715056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.600845E+10 | 0.634172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.463508E+10 | 0.507899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.309690E+10 | 0.259039E+11 | 1680474.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181397E+10 | 0.567970E+10 | 0.757887E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136447E+10 | 0.257877E+09 | 0.381724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421320E+11 | 0.362816E+12 | 0.913087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136447E+10 | 0.257877E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.643214E+10 | 0.715056E+11 | 0.381724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142990E+10 | 0.685892E+09 | 0.656960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138798E+10 | 0.293737E+10 | 0.363116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183031E+10 | 0.763200E+10 | 0.196899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.283554E+10 | 0.266224E+11 | 0.144978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.458392E+10 | 0.512109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.628553E+10 | 0.714198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.585397E+10 | 0.792052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.566944E+10 | 0.698478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.432351E+10 | 0.550140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.275099E+10 | 0.268524E+11 | 38726043.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167222E+10 | 0.525726E+10 | 0.255139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141099E+10 | 0.243756E+09 | 0.886930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.400343E+11 | 0.396929E+12 | 0.237741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138798E+10 | 0.243756E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.628553E+10 | 0.792052E+11 | 0.886930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.177749E+10 | 0.00 | 0.00 | 0.00 | 0.253961E+09 | 0.238263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178641E+10 | 0.00 | 0.00 | 0.00 | 0.869549E+09 | 0.196140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.236893E+10 | 0.00 | 0.00 | 0.00 | 0.214935E+10 | 0.154754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.335270E+10 | 0.00 | 0.00 | 0.00 | 0.664908E+10 | 0.443313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.519906E+10 | 0.00 | 0.00 | 0.00 | 0.133169E+11 | 92927467.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.662970E+10 | 0.00 | 0.00 | 0.00 | 0.197705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.644587E+10 | 0.00 | 0.00 | 0.00 | 0.221054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.653971E+10 | 0.00 | 0.00 | 0.00 | 0.201321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.544017E+10 | 0.00 | 0.00 | 0.00 | 0.161681E+11 | 38052548.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.419252E+10 | 0.00 | 0.00 | 0.00 | 0.808720E+10 | 0.304146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.268993E+10 | 0.00 | 0.00 | 0.00 | 0.182427E+10 | 0.998101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171696E+10 | 0.00 | 0.00 | 0.00 | 91080071.32 | 0.264526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.481394E+11 | 0.00 | 0.00 | 0.00 | 0.111418E+12 | 0.104134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.171696E+10 | 0.00 | 0.00 | 0.00 | 91080071.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.662970E+10 | 0.00 | 0.00 | 0.00 | 0.221054E+11 | 0.264526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.141213E+10 | 0.00 | 0.00 | 0.00 | 0.199673E+09 | 0.118610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141553E+10 | 0.00 | 0.00 | 0.00 | 0.802497E+09 | 0.469382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193852E+10 | 0.00 | 0.00 | 0.00 | 0.195131E+10 | 0.179989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.307530E+10 | 0.00 | 0.00 | 0.00 | 0.622938E+10 | 101847.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.489389E+10 | 0.00 | 0.00 | 0.00 | 0.121099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.643214E+10 | 0.00 | 0.00 | 0.00 | 0.180027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.604565E+10 | 0.00 | 0.00 | 0.00 | 0.191895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.600845E+10 | 0.00 | 0.00 | 0.00 | 0.168260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.463508E+10 | 0.00 | 0.00 | 0.00 | 0.131004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.309690E+10 | 0.00 | 0.00 | 0.00 | 0.647518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181397E+10 | 0.00 | 0.00 | 0.00 | 0.146550E+10 | 0.307744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136447E+10 | 0.00 | 0.00 | 0.00 | 73903728.86 | 0.166667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421320E+11 | 0.00 | 0.00 | 0.00 | 0.964259E+11 | 0.380999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136447E+10 | 0.00 | 0.00 | 0.00 | 73903728.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.643214E+10 | 0.00 | 0.00 | 0.00 | 0.191895E+11 | 0.166667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.142990E+10 | 0.00 | 0.00 | 0.00 | 0.192388E+09 | 0.473490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138798E+10 | 0.00 | 0.00 | 0.00 | 0.791304E+09 | 0.242610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183031E+10 | 0.00 | 0.00 | 0.00 | 0.199925E+10 | 0.120591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.283554E+10 | 0.00 | 0.00 | 0.00 | 0.690100E+10 | 77885848.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.458392E+10 | 0.00 | 0.00 | 0.00 | 0.135249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.628553E+10 | 0.00 | 0.00 | 0.00 | 0.203791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.585397E+10 | 0.00 | 0.00 | 0.00 | 0.214207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.566944E+10 | 0.00 | 0.00 | 0.00 | 0.187011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.432351E+10 | 0.00 | 0.00 | 0.00 | 0.143092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.275099E+10 | 0.00 | 0.00 | 0.00 | 0.678918E+10 | 24539179.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167222E+10 | 0.00 | 0.00 | 0.00 | 0.138341E+10 | 0.186593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141099E+10 | 0.00 | 0.00 | 0.00 | 70151216.77 | 0.620289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.400343E+11 | 0.00 | 0.00 | 0.00 | 0.106462E+12 | 0.165382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138798E+10 | 0.00 | 0.00 | 0.00 | 70151216.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.628553E+10 | 0.00 | 0.00 | 0.00 | 0.214207E+11 | 0.620289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129908E+10 | 0.00 | 0.00 | 31803711.91 | 0.00 | 0.00 | 0.158309E+11 | 0.00 | 0.59 |
February | 0.903926E+09 | 0.00 | 0.00 | 31116332.31 | 0.00 | 0.00 | 0.148951E+11 | 0.00 | 0.72 |
March | 0.799626E+09 | 0.00 | 0.00 | 40786273.42 | 0.00 | 0.00 | 0.171066E+11 | 0.00 | 0.92 |
April | 0.692404E+09 | 0.160675E+09 | 0.00 | 37052533.68 | 14116866.94 | 0.00 | 0.110476E+11 | 0.00 | 0.91 |
May | 0.459095E+09 | 0.631858E+09 | 0.00 | 27007089.98 | 62473009.29 | 0.00 | 0.501712E+10 | 0.00 | 0.76 |
June | 0.173148E+09 | 0.195288E+10 | 0.00 | 14878884.54 | 65949226.64 | 0.00 | 0.126073E+10 | 0.00 | 0.56 |
July | 12096261.94 | 0.679524E+10 | 0.00 | 1039491.03 | 0.313336E+09 | 0.00 | 60527642.77 | 0.00 | 0.52 |
August | 93798438.90 | 0.306579E+10 | 0.00 | 13253482.87 | 0.124024E+09 | 0.00 | 0.134909E+10 | 0.00 | 0.72 |
September | 0.342686E+09 | 0.201400E+10 | 0.00 | 21114787.27 | 0.165611E+09 | 0.00 | 0.305856E+10 | 0.00 | 0.74 |
October | 0.733485E+09 | 0.473021E+09 | 0.00 | 39348509.93 | 43043942.22 | 0.00 | 0.131445E+11 | 0.00 | 1.11 |
November | 0.127847E+10 | 0.00 | 0.00 | 40258226.48 | 0.00 | 0.00 | 0.179944E+11 | 0.00 | 0.94 |
December | 0.183455E+10 | 0.00 | 0.00 | 31050249.21 | 0.00 | 0.00 | 0.153312E+11 | 0.00 | 0.55 |
Annual Sum or Average | 0.862237E+10 | 0.150935E+11 | 0.00 | 0.328710E+09 | 0.788554E+09 | 0.00 | 0.116096E+12 | 0.00 | 0.75 |
Minimum of Months | 12096261.94 | 0.00 | 0.00 | 1039491.03 | 0.00 | 0.00 | 60527642.77 | 0.00 | 0.52 |
Maximum of Months | 0.183455E+10 | 0.679524E+10 | 0.00 | 40786273.42 | 0.313336E+09 | 0.00 | 0.179944E+11 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.726474E+10 | 0.00 | 0.00 | 3571952.44 | 0.00 | 598602.35 | 0.349602E+10 | 0.00 | 0.37 |
February | 0.511952E+10 | 0.00 | 0.00 | 6773383.10 | 0.00 | 0.00 | 0.475455E+10 | 0.00 | 0.45 |
March | 0.404047E+10 | 0.00 | 0.00 | 14007795.74 | 0.00 | 0.00 | 0.732237E+10 | 0.00 | 0.58 |
April | 0.113281E+10 | 80221966.90 | 0.00 | 21139323.09 | 48883689.13 | 0.00 | 0.662069E+10 | 0.00 | 0.61 |
May | 0.635060E+09 | 0.403639E+09 | 0.00 | 19656593.28 | 54151524.99 | 0.00 | 0.331891E+10 | 0.00 | 0.55 |
June | 0.237503E+09 | 0.143747E+10 | 0.00 | 12461453.79 | 65543035.27 | 0.00 | 0.101442E+10 | 0.00 | 0.44 |
July | 15396178.36 | 0.473592E+10 | 0.00 | 1292643.21 | 0.327710E+09 | 0.00 | 70849688.13 | 0.00 | 0.42 |
August | 0.160578E+09 | 0.195576E+10 | 0.00 | 11669294.09 | 0.112805E+09 | 0.00 | 0.102160E+10 | 0.00 | 0.54 |
September | 0.375594E+09 | 0.122315E+10 | 0.00 | 15455939.64 | 0.128229E+09 | 0.00 | 0.195747E+10 | 0.00 | 0.53 |
October | 0.115638E+10 | 0.291120E+09 | 0.00 | 21610762.97 | 35314502.31 | 0.00 | 0.740132E+10 | 0.00 | 0.71 |
November | 0.466063E+10 | 0.00 | 0.00 | 12219943.10 | 0.00 | 0.00 | 0.638453E+10 | 0.00 | 0.54 |
December | 0.816598E+10 | 0.00 | 0.00 | 2411592.42 | 0.00 | 1417510.38 | 0.273656E+10 | 0.00 | 0.34 |
Annual Sum or Average | 0.329647E+11 | 0.101273E+11 | 0.00 | 0.142271E+09 | 0.772637E+09 | 2016112.72 | 0.460993E+11 | 0.00 | 0.51 |
Minimum of Months | 15396178.36 | 0.00 | 0.00 | 1292643.21 | 0.00 | 0.00 | 70849688.13 | 0.00 | 0.34 |
Maximum of Months | 0.816598E+10 | 0.473592E+10 | 0.00 | 21610762.97 | 0.327710E+09 | 1417510.38 | 0.740132E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.852503E+10 | 0.00 | 0.00 | 922321.09 | 0.00 | 0.290406E+09 | 0.123199E+10 | 0.00 | 0.36 |
February | 0.655070E+10 | 0.00 | 0.00 | 3080333.74 | 0.00 | 73712601.63 | 0.258458E+10 | 0.00 | 0.44 |
March | 0.544099E+10 | 0.00 | 0.00 | 8638587.19 | 0.00 | 13722358.60 | 0.521117E+10 | 0.00 | 0.57 |
April | 0.178734E+10 | 52878534.79 | 0.00 | 18254682.84 | 19659210.95 | 0.00 | 0.533392E+10 | 0.00 | 0.62 |
May | 0.806779E+09 | 0.329627E+09 | 0.00 | 18445342.19 | 74547710.10 | 0.00 | 0.257112E+10 | 0.00 | 0.56 |
June | 0.236834E+09 | 0.130566E+10 | 0.00 | 12235218.11 | 67251342.77 | 0.00 | 0.684686E+09 | 0.00 | 0.43 |
July | 16480448.02 | 0.481949E+10 | 0.00 | 1446911.00 | 0.437846E+09 | 0.00 | 35767277.73 | 0.00 | 0.41 |
August | 0.122073E+09 | 0.204070E+10 | 0.00 | 10285627.46 | 0.166374E+09 | 0.00 | 0.673015E+09 | 0.00 | 0.52 |
September | 0.515377E+09 | 0.128814E+10 | 0.00 | 12260275.70 | 0.238222E+09 | 0.00 | 0.120414E+10 | 0.00 | 0.51 |
October | 0.198143E+10 | 0.319798E+09 | 0.00 | 14623989.70 | 50039582.90 | 0.00 | 0.526618E+10 | 0.00 | 0.67 |
November | 0.592782E+10 | 0.00 | 0.00 | 6099855.82 | 0.00 | 69923563.10 | 0.383730E+10 | 0.00 | 0.50 |
December | 0.893352E+10 | 0.00 | 0.00 | 394447.37 | 0.00 | 0.364751E+09 | 0.816479E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.408444E+11 | 0.101563E+11 | 0.00 | 0.106688E+09 | 0.105394E+10 | 0.812515E+09 | 0.294503E+11 | 0.00 | 0.49 |
Minimum of Months | 16480448.02 | 0.00 | 0.00 | 394447.37 | 0.00 | 0.00 | 35767277.73 | 0.00 | 0.34 |
Maximum of Months | 0.893352E+10 | 0.481949E+10 | 0.00 | 18445342.19 | 0.437846E+09 | 0.364751E+09 | 0.533392E+10 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145987E+10 | 0.00 | 0.00 | 2193.13 | 0.00 | 0.714135E+09 | 8974707.01 | 0.00 | 0.37 |
February | 0.148835E+10 | 0.00 | 0.00 | 181250.40 | 0.00 | 0.381233E+09 | 87551894.94 | 0.00 | 0.44 |
March | 0.148645E+10 | 0.00 | 0.00 | 1007059.08 | 0.00 | 0.202992E+09 | 0.525431E+09 | 0.00 | 0.56 |
April | 0.675162E+09 | 18447545.43 | 0.00 | 3575248.98 | 2638784.98 | 10052851.46 | 0.764663E+09 | 0.00 | 0.64 |
May | 0.220031E+09 | 0.108998E+09 | 0.00 | 4573309.34 | 16015265.02 | 0.00 | 0.514528E+09 | 0.00 | 0.66 |
June | 65739927.65 | 0.472429E+09 | 0.00 | 3319849.97 | 13482653.79 | 0.00 | 0.154352E+09 | 0.00 | 0.60 |
July | 5468424.91 | 0.145639E+10 | 0.00 | 382240.15 | 98947563.37 | 0.00 | 5654558.31 | 0.00 | 0.55 |
August | 41510811.47 | 0.570488E+09 | 0.00 | 2403061.69 | 41663971.77 | 0.00 | 0.137608E+09 | 0.00 | 0.63 |
September | 0.151887E+09 | 0.321437E+09 | 0.00 | 2606894.76 | 59011787.02 | 0.00 | 0.205823E+09 | 0.00 | 0.56 |
October | 0.763671E+09 | 80932356.32 | 0.00 | 2162653.82 | 10889521.95 | 2336977.10 | 0.647653E+09 | 0.00 | 0.65 |
November | 0.154166E+10 | 0.00 | 0.00 | 425025.89 | 0.00 | 0.259357E+09 | 0.222594E+09 | 0.00 | 0.48 |
December | 0.124839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.971532E+09 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.914820E+10 | 0.302912E+10 | 0.00 | 20638787.22 | 0.242650E+09 | 0.254164E+10 | 0.327483E+10 | 0.00 | 0.54 |
Minimum of Months | 5468424.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.154166E+10 | 0.145639E+10 | 0.00 | 4573309.34 | 98947563.37 | 0.971532E+09 | 0.764663E+09 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143546E+10 | 0.00 | 0.00 | 42694.81 | 0.00 | 0.361316E+09 | 69777763.26 | 0.00 | 0.50 |
February | 0.117841E+10 | 0.00 | 0.00 | 563950.61 | 0.00 | 0.152574E+09 | 0.399331E+09 | 0.00 | 0.62 |
March | 0.939373E+09 | 0.00 | 0.00 | 2438262.04 | 0.00 | 97911114.81 | 0.123176E+10 | 0.00 | 0.90 |
April | 0.332756E+09 | 17015740.83 | 0.00 | 5455430.53 | 1592959.75 | 889240.99 | 0.147821E+10 | 0.00 | 1.21 |
May | 0.121036E+09 | 0.101325E+09 | 0.00 | 5829063.51 | 10678288.67 | 0.00 | 0.867615E+09 | 0.00 | 1.22 |
June | 54672752.55 | 0.384671E+09 | 0.00 | 3466510.69 | 10474360.67 | 0.00 | 0.172167E+09 | 0.00 | 0.92 |
July | 4939675.52 | 0.133160E+10 | 0.00 | 330983.49 | 76941487.85 | 0.00 | 5363984.65 | 0.00 | 0.82 |
August | 33284895.30 | 0.577103E+09 | 0.00 | 2295014.06 | 30061421.07 | 0.00 | 0.139157E+09 | 0.00 | 0.99 |
September | 99176002.55 | 0.406377E+09 | 0.00 | 3214776.11 | 34092274.86 | 0.00 | 0.336404E+09 | 0.00 | 1.03 |
October | 0.500364E+09 | 67587846.91 | 0.00 | 2964293.12 | 9210487.54 | 1918821.69 | 0.104613E+10 | 0.00 | 1.08 |
November | 0.110094E+10 | 0.00 | 0.00 | 1068651.04 | 0.00 | 0.138600E+09 | 0.606512E+09 | 0.00 | 0.71 |
December | 0.137828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508944E+09 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.717869E+10 | 0.288567E+10 | 0.00 | 27669630.00 | 0.173051E+09 | 0.126215E+10 | 0.635243E+10 | 0.00 | 0.87 |
Minimum of Months | 4939675.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.143546E+10 | 0.133160E+10 | 0.00 | 5829063.51 | 76941487.85 | 0.508944E+09 | 0.147821E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.956456E+09 | 0.00 | 0.00 | 5215468.13 | 0.00 | 0.312703E+09 | 0.267389E+10 | 0.00 | 0.69 |
February | 0.882749E+09 | 0.00 | 0.00 | 4978643.05 | 0.00 | 0.168777E+09 | 0.248909E+10 | 0.00 | 0.83 |
March | 0.964632E+09 | 0.00 | 0.00 | 5962031.48 | 0.00 | 0.134350E+09 | 0.276481E+10 | 0.00 | 1.03 |
April | 0.578829E+09 | 32784832.06 | 0.00 | 6292204.41 | 1956865.25 | 11023767.66 | 0.147355E+10 | 0.00 | 0.92 |
May | 0.267571E+09 | 0.123467E+09 | 0.00 | 4841455.57 | 17537821.18 | 0.00 | 0.550901E+09 | 0.00 | 0.72 |
June | 83486768.52 | 0.461277E+09 | 0.00 | 3135609.72 | 18643300.71 | 0.00 | 0.136720E+09 | 0.00 | 0.58 |
July | 6810901.32 | 0.143995E+10 | 0.00 | 393543.10 | 0.118380E+09 | 0.00 | 4809197.57 | 0.00 | 0.55 |
August | 47377034.08 | 0.659284E+09 | 0.00 | 2876880.09 | 46169987.57 | 0.00 | 0.160379E+09 | 0.00 | 0.73 |
September | 0.125951E+09 | 0.499981E+09 | 0.00 | 4793663.22 | 53832881.39 | 0.00 | 0.401568E+09 | 0.00 | 0.83 |
October | 0.512910E+09 | 0.144123E+09 | 0.00 | 8138707.78 | 5214211.75 | 224373.02 | 0.236744E+10 | 0.00 | 1.38 |
November | 0.881070E+09 | 0.00 | 0.00 | 7208083.88 | 0.00 | 0.154419E+09 | 0.340255E+10 | 0.00 | 1.16 |
December | 0.951377E+09 | 0.00 | 0.00 | 4666954.79 | 0.00 | 0.402802E+09 | 0.238712E+10 | 0.00 | 0.61 |
Annual Sum or Average | 0.625922E+10 | 0.336086E+10 | 0.00 | 58503245.23 | 0.261735E+09 | 0.118430E+10 | 0.188128E+11 | 0.00 | 0.83 |
Minimum of Months | 6810901.32 | 0.00 | 0.00 | 393543.10 | 0.00 | 0.00 | 4809197.57 | 0.00 | 0.55 |
Maximum of Months | 0.964632E+09 | 0.143995E+10 | 0.00 | 8138707.78 | 0.118380E+09 | 0.402802E+09 | 0.340255E+10 | 0.00 | 1.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126711E+10 | 0.00 | 0.00 | 475554.99 | 0.00 | 0.560444E+09 | 0.387034E+09 | 0.00 | 0.59 |
February | 0.126997E+10 | 0.00 | 0.00 | 819852.24 | 0.00 | 0.297932E+09 | 0.477619E+09 | 0.00 | 0.73 |
March | 0.129076E+10 | 0.00 | 0.00 | 2440615.35 | 0.00 | 0.167262E+09 | 0.110899E+10 | 0.00 | 1.06 |
April | 0.641935E+09 | 22250832.06 | 0.00 | 4435623.32 | 1241333.11 | 11871295.57 | 0.959445E+09 | 0.00 | 1.10 |
May | 0.259323E+09 | 0.107511E+09 | 0.00 | 4032834.64 | 10709718.46 | 0.00 | 0.400726E+09 | 0.00 | 0.96 |
June | 79558195.97 | 0.426298E+09 | 0.00 | 2527803.84 | 12884044.35 | 0.00 | 0.101093E+09 | 0.00 | 0.77 |
July | 6473661.72 | 0.114234E+10 | 0.00 | 310277.44 | 0.115009E+09 | 0.00 | 3277227.09 | 0.00 | 0.70 |
August | 48912994.42 | 0.469053E+09 | 0.00 | 2002640.47 | 49462192.87 | 0.00 | 99180448.05 | 0.00 | 0.85 |
September | 0.148629E+09 | 0.279361E+09 | 0.00 | 2977579.80 | 62260925.76 | 0.00 | 0.218707E+09 | 0.00 | 0.84 |
October | 0.729937E+09 | 80316695.73 | 0.00 | 3020140.95 | 9195146.13 | 1993702.01 | 0.848233E+09 | 0.00 | 1.17 |
November | 0.129563E+10 | 0.00 | 0.00 | 1433508.52 | 0.00 | 0.228363E+09 | 0.774680E+09 | 0.00 | 0.90 |
December | 0.116622E+10 | 0.00 | 0.00 | 274249.15 | 0.00 | 0.726636E+09 | 0.300283E+09 | 0.00 | 0.55 |
Annual Sum or Average | 0.820446E+10 | 0.252713E+10 | 0.00 | 24750680.69 | 0.260762E+09 | 0.199450E+10 | 0.567927E+10 | 0.00 | 0.85 |
Minimum of Months | 6473661.72 | 0.00 | 0.00 | 274249.15 | 0.00 | 0.00 | 3277227.09 | 0.00 | 0.55 |
Maximum of Months | 0.129563E+10 | 0.114234E+10 | 0.00 | 4435623.32 | 0.115009E+09 | 0.726636E+09 | 0.110899E+10 | 0.00 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.207846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260370E+09 | 0.00 | 0.00 | 0.37 |
February | 0.181775E+10 | 0.00 | 0.00 | 15757.18 | 0.00 | 0.184509E+09 | 19990672.06 | 0.00 | 0.43 |
March | 0.191306E+10 | 0.00 | 0.00 | 152115.55 | 0.00 | 0.114011E+09 | 91714658.70 | 0.00 | 0.50 |
April | 0.902176E+09 | 17088709.17 | 0.00 | 1550723.86 | 12478180.23 | 154163.02 | 0.361099E+09 | 0.00 | 0.48 |
May | 0.335580E+09 | 0.119177E+09 | 0.00 | 2399014.10 | 13228924.78 | 0.00 | 0.337445E+09 | 0.00 | 0.49 |
June | 0.109464E+09 | 0.445820E+09 | 0.00 | 1885032.59 | 19011617.18 | 0.00 | 0.116092E+09 | 0.00 | 0.48 |
July | 6395826.13 | 0.134101E+10 | 0.00 | 83167.03 | 0.110001E+09 | 0.00 | 5838879.09 | 0.00 | 0.49 |
August | 61050685.96 | 0.618313E+09 | 0.00 | 1721600.89 | 43111375.42 | 0.00 | 0.155875E+09 | 0.00 | 0.61 |
September | 0.193537E+09 | 0.383312E+09 | 0.00 | 2346573.69 | 46592194.90 | 0.00 | 0.279590E+09 | 0.00 | 0.57 |
October | 0.695558E+09 | 86973237.27 | 0.00 | 2905113.27 | 10839199.76 | 0.00 | 0.950523E+09 | 0.00 | 0.68 |
November | 0.179730E+10 | 0.00 | 0.00 | 642226.65 | 0.00 | 15546637.19 | 0.413551E+09 | 0.00 | 0.49 |
December | 0.204451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350424E+09 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.119548E+11 | 0.301169E+10 | 0.00 | 13701324.81 | 0.255262E+09 | 0.925014E+09 | 0.273172E+10 | 0.00 | 0.50 |
Minimum of Months | 6395826.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.207846E+10 | 0.134101E+10 | 0.00 | 2905113.27 | 0.110001E+09 | 0.350424E+09 | 0.950523E+09 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155844E+10 | 0.00 | 0.00 | 102812.52 | 0.00 | 86425707.31 | 0.150561E+09 | 0.00 | 0.45 |
February | 0.121759E+10 | 0.00 | 0.00 | 505281.54 | 0.00 | 31458291.92 | 0.349185E+09 | 0.00 | 0.54 |
March | 0.983258E+09 | 0.00 | 0.00 | 1755496.18 | 0.00 | 25584194.31 | 0.869744E+09 | 0.00 | 0.71 |
April | 0.350503E+09 | 24828427.71 | 0.00 | 3914496.28 | 2280911.41 | 0.00 | 0.114746E+10 | 0.00 | 0.91 |
May | 0.170400E+09 | 0.118547E+09 | 0.00 | 4038610.79 | 7272961.73 | 0.00 | 0.708923E+09 | 0.00 | 0.95 |
June | 74956901.17 | 0.393841E+09 | 0.00 | 2317281.90 | 10273362.21 | 0.00 | 0.151184E+09 | 0.00 | 0.78 |
July | 3945060.52 | 0.125012E+10 | 0.00 | 118715.22 | 63944388.93 | 0.00 | 7755654.70 | 0.00 | 0.72 |
August | 42949342.36 | 0.611544E+09 | 0.00 | 1816716.30 | 20440906.62 | 0.00 | 0.167815E+09 | 0.00 | 0.94 |
September | 0.114119E+09 | 0.414277E+09 | 0.00 | 3208641.90 | 24975205.44 | 0.00 | 0.453991E+09 | 0.00 | 1.02 |
October | 0.387385E+09 | 74520076.40 | 0.00 | 4056490.06 | 6771364.89 | 0.00 | 0.138642E+10 | 0.00 | 1.11 |
November | 0.962795E+09 | 0.00 | 0.00 | 2141489.52 | 0.00 | 1119618.74 | 0.104313E+10 | 0.00 | 0.73 |
December | 0.158571E+10 | 0.00 | 0.00 | 73542.98 | 0.00 | 0.121299E+09 | 0.129438E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.745205E+10 | 0.288768E+10 | 0.00 | 24049575.18 | 0.135959E+09 | 0.265886E+09 | 0.656560E+10 | 0.00 | 0.78 |
Minimum of Months | 3945060.52 | 0.00 | 0.00 | 73542.98 | 0.00 | 0.00 | 7755654.70 | 0.00 | 0.43 |
Maximum of Months | 0.158571E+10 | 0.125012E+10 | 0.00 | 4056490.06 | 63944388.93 | 0.121299E+09 | 0.138642E+10 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131312E+10 | 0.00 | 0.00 | 1602609.06 | 0.00 | 0.730921E+09 | 0.103820E+10 | 0.00 | 0.51 |
February | 0.122564E+10 | 0.00 | 0.00 | 1532881.59 | 0.00 | 0.610685E+09 | 0.724286E+09 | 0.00 | 0.59 |
March | 0.139516E+10 | 0.00 | 0.00 | 1822785.28 | 0.00 | 0.540350E+09 | 0.669932E+09 | 0.00 | 0.66 |
April | 0.786414E+09 | 53561524.81 | 0.00 | 2997316.62 | 2977676.61 | 0.175678E+09 | 0.470503E+09 | 0.00 | 0.61 |
May | 0.390640E+09 | 0.174553E+09 | 0.00 | 2414035.48 | 13249012.83 | 47834472.83 | 0.234233E+09 | 0.00 | 0.55 |
June | 0.137106E+09 | 0.571617E+09 | 0.00 | 1686086.58 | 20891078.00 | 0.00 | 67899207.90 | 0.00 | 0.52 |
July | 9330794.76 | 0.147296E+10 | 0.00 | 24546.41 | 0.150337E+09 | 0.00 | 1021126.15 | 0.00 | 0.52 |
August | 84774620.17 | 0.842198E+09 | 0.00 | 1690856.27 | 46103000.83 | 0.00 | 0.123304E+09 | 0.00 | 0.70 |
September | 0.193678E+09 | 0.632944E+09 | 0.00 | 3958242.25 | 44519142.38 | 17933702.98 | 0.376594E+09 | 0.00 | 0.82 |
October | 0.499406E+09 | 0.173866E+09 | 0.00 | 7700568.73 | 4520969.68 | 0.131160E+09 | 0.200394E+10 | 0.00 | 1.26 |
November | 0.950423E+09 | 0.00 | 0.00 | 5847618.79 | 0.00 | 0.382825E+09 | 0.259528E+10 | 0.00 | 1.01 |
December | 0.124849E+10 | 0.00 | 0.00 | 1511406.64 | 0.00 | 0.871689E+09 | 0.104066E+10 | 0.00 | 0.48 |
Annual Sum or Average | 0.823419E+10 | 0.392170E+10 | 0.00 | 32788953.72 | 0.282597E+09 | 0.350908E+10 | 0.934585E+10 | 0.00 | 0.69 |
Minimum of Months | 9330794.76 | 0.00 | 0.00 | 24546.41 | 0.00 | 0.00 | 1021126.15 | 0.00 | 0.48 |
Maximum of Months | 0.139516E+10 | 0.147296E+10 | 0.00 | 7700568.73 | 0.150337E+09 | 0.871689E+09 | 0.259528E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.152405E+10 | 0.00 | 0.00 | 411386.68 | 0.00 | 0.127623E+09 | 0.318321E+09 | 0.00 | 0.50 |
February | 0.135752E+10 | 0.00 | 0.00 | 486981.73 | 0.00 | 76093512.17 | 0.271102E+09 | 0.00 | 0.58 |
March | 0.134236E+10 | 0.00 | 0.00 | 1406232.64 | 0.00 | 27623408.62 | 0.549485E+09 | 0.00 | 0.76 |
April | 0.575945E+09 | 30350742.32 | 0.00 | 2836700.63 | 3540892.25 | 0.00 | 0.644554E+09 | 0.00 | 0.78 |
May | 0.253610E+09 | 0.135467E+09 | 0.00 | 2418683.04 | 7567109.38 | 0.00 | 0.329003E+09 | 0.00 | 0.74 |
June | 83397501.13 | 0.441753E+09 | 0.00 | 1494163.93 | 9734920.67 | 0.00 | 91473189.04 | 0.00 | 0.65 |
July | 4460773.35 | 0.114048E+10 | 0.00 | 67706.59 | 74899318.49 | 0.00 | 4888482.41 | 0.00 | 0.62 |
August | 45350560.78 | 0.562409E+09 | 0.00 | 1385858.02 | 26041087.52 | 0.00 | 0.121409E+09 | 0.00 | 0.82 |
September | 0.120331E+09 | 0.369653E+09 | 0.00 | 2582322.65 | 28259879.93 | 0.00 | 0.306489E+09 | 0.00 | 0.83 |
October | 0.419099E+09 | 88865607.65 | 0.00 | 3910993.06 | 5437748.85 | 0.00 | 0.116834E+10 | 0.00 | 1.11 |
November | 0.116705E+10 | 0.00 | 0.00 | 1908003.46 | 0.00 | 8873706.47 | 0.966508E+09 | 0.00 | 0.82 |
December | 0.153658E+10 | 0.00 | 0.00 | 347917.68 | 0.00 | 0.155519E+09 | 0.310006E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.842975E+10 | 0.276898E+10 | 0.00 | 19256950.11 | 0.155481E+09 | 0.395733E+09 | 0.508158E+10 | 0.00 | 0.72 |
Minimum of Months | 4460773.35 | 0.00 | 0.00 | 67706.59 | 0.00 | 0.00 | 4888482.41 | 0.00 | 0.47 |
Maximum of Months | 0.153658E+10 | 0.114048E+10 | 0.00 | 3910993.06 | 74899318.49 | 0.155519E+09 | 0.116834E+10 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.193132E+10 | 0.00 | 0.00 | 20375.50 | 0.00 | 0.280948E+09 | 31428971.38 | 0.00 | 0.36 |
February | 0.169064E+10 | 0.00 | 0.00 | 253901.45 | 0.00 | 0.123895E+09 | 0.167496E+09 | 0.00 | 0.43 |
March | 0.158037E+10 | 0.00 | 0.00 | 1256769.97 | 0.00 | 44257621.12 | 0.563380E+09 | 0.00 | 0.54 |
April | 0.603521E+09 | 32433629.90 | 0.00 | 3548649.72 | 4383798.79 | 0.00 | 0.855479E+09 | 0.00 | 0.59 |
May | 0.220269E+09 | 0.142561E+09 | 0.00 | 4368136.07 | 11470200.35 | 0.00 | 0.591607E+09 | 0.00 | 0.64 |
June | 86647786.20 | 0.538909E+09 | 0.00 | 3143677.43 | 13790866.03 | 0.00 | 0.201791E+09 | 0.00 | 0.62 |
July | 6645916.86 | 0.143921E+10 | 0.00 | 249727.18 | 78130306.24 | 0.00 | 11343976.17 | 0.00 | 0.57 |
August | 51881578.08 | 0.566011E+09 | 0.00 | 2561892.28 | 27863193.64 | 0.00 | 0.195843E+09 | 0.00 | 0.65 |
September | 0.163475E+09 | 0.321174E+09 | 0.00 | 2712931.17 | 31785732.88 | 0.00 | 0.271477E+09 | 0.00 | 0.56 |
October | 0.670096E+09 | 76498199.99 | 0.00 | 2805952.05 | 7625062.84 | 0.00 | 0.845882E+09 | 0.00 | 0.65 |
November | 0.162337E+10 | 0.00 | 0.00 | 675694.05 | 0.00 | 69135095.44 | 0.389899E+09 | 0.00 | 0.47 |
December | 0.183262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459646E+09 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.104609E+11 | 0.311680E+10 | 0.00 | 21597706.87 | 0.175049E+09 | 0.977883E+09 | 0.412563E+10 | 0.00 | 0.53 |
Minimum of Months | 6645916.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.193132E+10 | 0.143921E+10 | 0.00 | 4368136.07 | 78130306.24 | 0.459646E+09 | 0.855479E+09 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.160670E+10 | 0.00 | 0.00 | 158628.02 | 0.00 | 0.172133E+09 | 0.178390E+09 | 0.00 | 0.49 |
February | 0.120832E+10 | 0.00 | 0.00 | 881143.08 | 0.00 | 45713632.47 | 0.570877E+09 | 0.00 | 0.63 |
March | 0.999971E+09 | 0.00 | 0.00 | 2774016.83 | 0.00 | 21439745.84 | 0.134538E+10 | 0.00 | 0.90 |
April | 0.307822E+09 | 29349250.06 | 0.00 | 5454145.20 | 2759028.45 | 0.00 | 0.159705E+10 | 0.00 | 1.14 |
May | 0.138880E+09 | 0.124226E+09 | 0.00 | 5520313.15 | 7896811.87 | 0.00 | 0.943221E+09 | 0.00 | 1.16 |
June | 70906887.31 | 0.424701E+09 | 0.00 | 3476418.19 | 10234905.15 | 0.00 | 0.226024E+09 | 0.00 | 0.94 |
July | 7042995.32 | 0.127382E+10 | 0.00 | 257955.25 | 59313930.71 | 0.00 | 10221393.83 | 0.00 | 0.82 |
August | 47887601.30 | 0.537439E+09 | 0.00 | 2364416.12 | 21123618.81 | 0.00 | 0.191202E+09 | 0.00 | 0.99 |
September | 0.114030E+09 | 0.352991E+09 | 0.00 | 3384329.66 | 22900660.48 | 0.00 | 0.431019E+09 | 0.00 | 1.01 |
October | 0.503028E+09 | 60020675.61 | 0.00 | 3427191.28 | 6240899.62 | 0.00 | 0.118524E+10 | 0.00 | 1.05 |
November | 0.112805E+10 | 0.00 | 0.00 | 1606910.19 | 0.00 | 39297180.77 | 0.826935E+09 | 0.00 | 0.72 |
December | 0.163712E+10 | 0.00 | 0.00 | 54604.44 | 0.00 | 0.281215E+09 | 72478614.93 | 0.00 | 0.47 |
Annual Sum or Average | 0.776975E+10 | 0.280254E+10 | 0.00 | 29360071.41 | 0.130470E+09 | 0.559798E+09 | 0.757803E+10 | 0.00 | 0.86 |
Minimum of Months | 7042995.32 | 0.00 | 0.00 | 54604.44 | 0.00 | 0.00 | 10221393.83 | 0.00 | 0.47 |
Maximum of Months | 0.163712E+10 | 0.127382E+10 | 0.00 | 5520313.15 | 59313930.71 | 0.281215E+09 | 0.159705E+10 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100824E+10 | 0.00 | 0.00 | 6367903.62 | 0.00 | 0.127671E+09 | 0.312250E+10 | 0.00 | 0.74 |
February | 0.909163E+09 | 0.00 | 0.00 | 5829119.03 | 0.00 | 47430754.87 | 0.272421E+10 | 0.00 | 0.86 |
March | 0.927507E+09 | 0.00 | 0.00 | 6579568.09 | 0.00 | 16685323.08 | 0.278282E+10 | 0.00 | 1.00 |
April | 0.489794E+09 | 60213016.07 | 0.00 | 5915773.85 | 3216926.59 | 0.00 | 0.148015E+10 | 0.00 | 0.84 |
May | 0.245971E+09 | 0.165854E+09 | 0.00 | 4535291.91 | 11625794.60 | 0.00 | 0.600998E+09 | 0.00 | 0.67 |
June | 89989114.97 | 0.537251E+09 | 0.00 | 2932442.55 | 14731214.90 | 0.00 | 0.181771E+09 | 0.00 | 0.59 |
July | 8588847.65 | 0.143802E+10 | 0.00 | 245538.01 | 80785669.23 | 0.00 | 8612675.00 | 0.00 | 0.56 |
August | 52226657.84 | 0.667574E+09 | 0.00 | 2986599.09 | 27817753.37 | 0.00 | 0.217137E+09 | 0.00 | 0.73 |
September | 0.128999E+09 | 0.503157E+09 | 0.00 | 4574709.26 | 30753820.51 | 0.00 | 0.454450E+09 | 0.00 | 0.80 |
October | 0.436958E+09 | 0.141057E+09 | 0.00 | 8697499.52 | 4165078.08 | 0.00 | 0.241547E+10 | 0.00 | 1.31 |
November | 0.829273E+09 | 0.00 | 0.00 | 8676510.34 | 0.00 | 26932484.92 | 0.365908E+10 | 0.00 | 1.18 |
December | 0.108282E+10 | 0.00 | 0.00 | 5909720.31 | 0.00 | 0.175102E+09 | 0.289151E+10 | 0.00 | 0.67 |
Annual Sum or Average | 0.620953E+10 | 0.351313E+10 | 0.00 | 63250675.57 | 0.173096E+09 | 0.393821E+09 | 0.205387E+11 | 0.00 | 0.83 |
Minimum of Months | 8588847.65 | 0.00 | 0.00 | 245538.01 | 0.00 | 0.00 | 8612675.00 | 0.00 | 0.56 |
Maximum of Months | 0.108282E+10 | 0.143802E+10 | 0.00 | 8697499.52 | 80785669.23 | 0.175102E+09 | 0.365908E+10 | 0.00 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155232E+10 | 0.00 | 0.00 | 661054.54 | 0.00 | 0.213460E+09 | 0.457831E+09 | 0.00 | 0.57 |
February | 0.139937E+10 | 0.00 | 0.00 | 955162.57 | 0.00 | 0.103310E+09 | 0.506250E+09 | 0.00 | 0.70 |
March | 0.129387E+10 | 0.00 | 0.00 | 2618927.26 | 0.00 | 31261888.13 | 0.107880E+10 | 0.00 | 0.98 |
April | 0.554979E+09 | 41833177.02 | 0.00 | 4081702.75 | 2736500.49 | 0.00 | 0.957682E+09 | 0.00 | 0.98 |
May | 0.243693E+09 | 0.149227E+09 | 0.00 | 3557668.40 | 5904327.70 | 0.00 | 0.434112E+09 | 0.00 | 0.89 |
June | 87538035.49 | 0.509005E+09 | 0.00 | 2262265.23 | 9294548.25 | 0.00 | 0.132357E+09 | 0.00 | 0.78 |
July | 8932857.94 | 0.115647E+10 | 0.00 | 167564.89 | 72894843.18 | 0.00 | 5095928.34 | 0.00 | 0.71 |
August | 58117349.23 | 0.481604E+09 | 0.00 | 2038221.36 | 25664876.66 | 0.00 | 0.134530E+09 | 0.00 | 0.85 |
September | 0.159145E+09 | 0.285468E+09 | 0.00 | 2770692.46 | 27948404.70 | 0.00 | 0.245698E+09 | 0.00 | 0.81 |
October | 0.588326E+09 | 77313820.06 | 0.00 | 3317997.13 | 5190433.95 | 0.00 | 0.950664E+09 | 0.00 | 1.08 |
November | 0.138342E+10 | 0.00 | 0.00 | 1703891.13 | 0.00 | 45835838.10 | 0.826869E+09 | 0.00 | 0.86 |
December | 0.152013E+10 | 0.00 | 0.00 | 442781.96 | 0.00 | 0.329092E+09 | 0.366125E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.884985E+10 | 0.270092E+10 | 0.00 | 24577929.69 | 0.149634E+09 | 0.722961E+09 | 0.609601E+10 | 0.00 | 0.81 |
Minimum of Months | 8932857.94 | 0.00 | 0.00 | 167564.89 | 0.00 | 0.00 | 5095928.34 | 0.00 | 0.53 |
Maximum of Months | 0.155232E+10 | 0.115647E+10 | 0.00 | 4081702.75 | 72894843.18 | 0.329092E+09 | 0.107880E+10 | 0.00 | 1.08 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.220524E+12 | 0.124625E+11 | 0.00 | 0.191090E+12 | 0.393079E+10 |
February | 0.222903E+12 | 0.101195E+11 | 0.00 | 0.168023E+12 | 0.123585E+11 |
March | 0.317482E+12 | 0.104696E+11 | 0.00 | 0.204195E+12 | 0.299968E+11 |
April | 0.324182E+12 | 0.510808E+10 | 0.00 | 0.154728E+12 | 0.964850E+11 |
May | 0.335547E+12 | 0.167821E+10 | 0.00 | 0.105582E+12 | 0.187158E+12 |
June | 0.323476E+12 | -0.189806E+10 | 0.00 | 0.187647E+11 | 0.263009E+12 |
July | 0.321708E+12 | -0.486601E+10 | 0.00 | -0.766447E+11 | 0.295699E+12 |
August | 0.300884E+12 | -0.220202E+10 | 0.00 | -0.141000E+11 | 0.265102E+12 |
September | 0.285266E+12 | -362011831.8 | 0.00 | 0.191091E+11 | 0.212404E+12 |
October | 0.266761E+12 | 0.434711E+10 | 0.00 | 0.157437E+12 | 0.106722E+12 |
November | 0.222083E+12 | 0.999275E+10 | 0.00 | 0.209011E+12 | 0.230901E+11 |
December | 0.191413E+12 | 0.116571E+11 | 0.00 | 0.179986E+12 | 0.257387E+10 |
Annual Sum or Average | 0.333223E+13 | 0.565069E+11 | 0.00 | 0.131718E+13 | 0.149853E+13 |
Minimum of Months | 0.191413E+12 | -0.486601E+10 | 0.00 | -0.766447E+11 | 0.257387E+10 |