Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 08:35:21
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2047.41 | 410.95 | 410.95 |
Net Site Energy | 2047.41 | 410.95 | 410.95 |
Total Source Energy | 6021.84 | 1208.67 | 1208.67 |
Net Source Energy | 6021.84 | 1208.67 | 1208.67 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 453.73 | 101.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 118.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 281.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 101.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 24.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 120.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1825.47 | 221.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 453.73 | 101.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 118.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 281.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 72.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 101.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 24.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 120.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 453.73 | 101.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 118.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 281.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 72.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 101.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 24.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 120.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 135.15 | 44.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 160.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 366.40 | 44.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 135.15 | 44.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 160.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 366.40 | 44.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1825.468 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1825.468 | 100.00 |
Total On-Site and Utility Electric Sources | 1825.468 | 100.00 |
Total Electricity End Uses | 1825.468 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 13.07 | 3.70 |
Air to Air Heat Recovery for Heating | 340.15 | 96.30 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 353.22 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 797.17 |
Time Setpoint Not Met During Occupied Cooling | 80.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3247.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.5763 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 7.5763 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 7.5763 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-08:09 | 06-JAN-07:00 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 191640.49 | 183268.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 28079.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 47562.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 901.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5642.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2722.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8233.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 282107.28 | 191502.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 191640.49 | 183268.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 28079.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 901.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 5642.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 2722.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8233.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 1436.97 | 110.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 374.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 890.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 228.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2413.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 41.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 320.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 76.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 130.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5781.26 | 240.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 288.42 | 22.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 75.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 178.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 64.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 15.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 26.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1160.39 | 48.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 288.42 | 22.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 75.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 178.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 64.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 15.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 26.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1160.39 | 48.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.95 | 0.254360 | 0.269000 | 0.792592 | 0.678292 | 0.500000 | 0.001498 |
CORE_MID VAV BOX COMPONENT | 2.16 | 0.347319 | 0.356000 | 0.768187 | 0.926184 | 0.500000 | 0.001097 |
CORE_TOP VAV BOX COMPONENT | 2.24 | 0.334737 | 0.354000 | 0.792583 | 0.892633 | 0.500000 | 0.001138 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.745375 | 0.211963 | 0.241000 | 0.179635 | 0.565234 | 0.500000 | 0.001797 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.877126 | 0.114034 | 0.200000 | 0.175425 | 0.304090 | 0.500000 | 0.003341 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.16 | 0.136726 | 0.200000 | 0.231108 | 0.364601 | 0.500000 | 0.002787 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.973441 | 0.102744 | 0.200000 | 0.194688 | 0.300000 | 0.500000 | 0.003708 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.556863 | 0.283717 | 0.300000 | 0.167059 | 0.756580 | 0.500000 | 0.001343 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.717916 | 0.139322 | 0.200000 | 0.143583 | 0.371527 | 0.500000 | 0.002735 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.932524 | 0.169424 | 0.200000 | 0.186505 | 0.451796 | 0.500000 | 0.002249 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.781896 | 0.127914 | 0.200000 | 0.156379 | 0.341103 | 0.500000 | 0.002979 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.613447 | 0.257547 | 0.264000 | 0.161950 | 0.686793 | 0.500000 | 0.001479 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.866515 | 0.115430 | 0.200000 | 0.173303 | 0.307813 | 0.500000 | 0.003301 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.07 | 0.148076 | 0.200000 | 0.213392 | 0.394870 | 0.500000 | 0.002573 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.906011 | 0.110391 | 0.200000 | 0.181202 | 0.300000 | 0.500000 | 0.003451 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25367.25 |
CORE_MID VAV BOX REHEAT COIL | 29436.03 |
CORE_TOP VAV BOX REHEAT COIL | 50504.72 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 23856.05 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 15603.44 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 24019.45 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 15725.25 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17822.64 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11759.72 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 17967.06 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11855.38 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 18372.54 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 12083.53 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 18497.68 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 12182.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.97 | 1.45 | 5.94 | 2.36 | 5.24 | 5.24 | 0.300000 | 0.450661 | 5.24 |
PACU_VAV_MID | 2.81 | 1.50 | 5.61 | 2.83 | 4.68 | 4.68 | 0.300000 | 0.604311 | 4.68 |
PACU_VAV_TOP | 3.00 | 1.57 | 5.99 | 4.05 | 5.29 | 5.29 | 0.300000 | 0.766601 | 5.29 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.24 |
PACU_VAV_MID_OA_CONTROLLER | 4.68 |
PACU_VAV_TOP_OA_CONTROLLER | 5.29 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT OA HEAT RECOVERY | 1.20 |
PACU_VAV_MID OA HEAT RECOVERY | 1.20 |
PACU_VAV_TOP OA HEAT RECOVERY | 1.20 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.24 | 103791.04 | 0.780335 | 1.75 | 34593.55 | 0.780335 |
PACU_VAV_MID COOLING COIL | 4.68 | 95340.51 | 0.768926 | 1.56 | 31776.99 | 0.768926 |
PACU_VAV_TOP COOLING COIL | 5.29 | 104951.84 | 0.779562 | 1.76 | 34980.45 | 0.779562 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 60569.86 |
PACU_VAV_MID HEATING COIL | 61914.73 |
PACU_VAV_TOP HEATING COIL | 61498.69 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.24 |
PACU_VAV_MID FAN | 4.68 |
PACU_VAV_TOP FAN | 5.29 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 32.411 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9320 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9163 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.269 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1711 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1804 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1711 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1804 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8390 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8573 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5538 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.768 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.466 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.768 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.465 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
39 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
40 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
41 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
42 | 7 | -0.27971961E-12 | 0.14534712E-14 | -0.84678956E-13 | 0.82684317E-16 |
43 | 6 | 0.26817376E-07 | 0.25687399E-09 | 0.61588016E-08 | -0.12527087E-12 |
44 | 5 | -0.18065003E-03 | 0.22251366E-05 | -0.93037841E-04 | 0.60936178E-08 |
45 | 4 | 0.28101542 | 0.10946024E-02 | 0.95683253E-01 | -0.32007147E-04 |
46 | 3 | -7.0457283 | 0.34231649E-01 | -2.2734647 | 0.27928366E-01 |
47 | 2 | 40.143429 | 0.12270019 | 14.996275 | -0.32523640 |
48 | 1 | -79.987958 | 0.55761501E-01 | -28.900564 | 1.0667320 |
49 | 0 | 46.824342 | 0.11295401E-02 | 16.297084 | |
50 | 7 | -0.28233695E-12 | 0.14433069E-14 | -0.85363548E-13 | 0.83491456E-16 |
51 | 6 | 0.27004714E-07 | 0.25312183E-09 | 0.62001510E-08 | -0.12627076E-12 |
52 | 5 | -0.18161011E-03 | 0.21898175E-05 | -0.93520278E-04 | 0.61339935E-08 |
53 | 4 | 0.28215201 | 0.10760039E-02 | 0.96091377E-01 | -0.32166146E-04 |
54 | 3 | -7.0682688 | 0.33616209E-01 | -2.2801509 | 0.28038740E-01 |
55 | 2 | 40.217804 | 0.12038787 | 15.023777 | -0.32606455 |
56 | 1 | -80.044990 | 0.54668782E-01 | -28.925243 | 1.0679473 |
57 | 0 | 46.824342 | 0.11065724E-02 | 16.296477 | |
58 | 6 | 0.22748378E-07 | 0.33059726E-09 | 0.52605359E-08 | -0.10371465E-12 |
59 | 5 | -0.15952455E-03 | 0.29533519E-05 | -0.82380770E-04 | 0.52144884E-08 |
60 | 4 | 0.25560578 | 0.14926938E-02 | 0.86578981E-01 | -0.28493712E-04 |
61 | 3 | -6.5408460 | 0.47808585E-01 | -2.1237636 | 0.25458881E-01 |
62 | 2 | 38.476406 | 0.17496760 | 14.378110 | -0.30668036 |
63 | 1 | -78.708466 | 0.80951212E-01 | -28.345189 | 1.0394692 |
64 | 0 | 46.824351 | 0.16689207E-02 | 16.311239 | |
65 | 7 | -0.24742660E-08 | -0.10943249E-14 | 0.58004390E-14 | -0.93636906E-16 |
66 | 6 | 0.48508293E-05 | 0.32725533E-08 | 0.31920885E-02 | -0.26777914E-04 |
67 | 5 | -0.34494329E-03 | 0.19369032E-05 | -0.22385068 | 0.19572633E-02 |
68 | 4 | 0.79096117E-02 | 0.88130937E-04 | 4.8316460 | -0.45285171E-01 |
69 | 3 | -0.69381330E-01 | 0.70057705E-03 | -38.033282 | 0.39878490 |
70 | 2 | 0.24625431 | 0.11650871E-02 | 116.50704 | -1.4182482 |
71 | 1 | -0.35536509 | 0.35482444E-03 | -143.92090 | 2.0492634 |
72 | 0 | 0.17324174 | 0.85915519E-05 | 60.838472 | |
73 | 7 | -0.23440898E-08 | -0.93321999E-15 | 0.55807564E-14 | -0.85509042E-16 |
74 | 6 | 0.50995884E-05 | 0.34521263E-08 | 0.31913593E-02 | -0.26771796E-04 |
75 | 5 | -0.36354987E-03 | 0.20433482E-05 | -0.22380923 | 0.19568975E-02 |
76 | 4 | 0.83423098E-02 | 0.92983792E-04 | 4.8309558 | -0.45278535E-01 |
77 | 3 | -0.73195838E-01 | 0.73920573E-03 | -38.029382 | 0.39874180 |
78 | 2 | 0.25981955 | 0.12294351E-02 | 116.49945 | -1.4181467 |
79 | 1 | -0.37495780 | 0.37443474E-03 | -143.91643 | 2.0491899 |
80 | 0 | 0.18279742 | 0.90747285E-05 | 60.838472 | |
81 | 7 | -0.24742660E-08 | -0.10943249E-14 | 0.58004393E-14 | -0.93636910E-16 |
82 | 6 | 0.48508293E-05 | 0.32725533E-08 | 0.31920885E-02 | -0.26777914E-04 |
83 | 5 | -0.34494329E-03 | 0.19369032E-05 | -0.22385068 | 0.19572633E-02 |
84 | 4 | 0.79096117E-02 | 0.88130937E-04 | 4.8316460 | -0.45285171E-01 |
85 | 3 | -0.69381330E-01 | 0.70057705E-03 | -38.033282 | 0.39878490 |
86 | 2 | 0.24625431 | 0.11650871E-02 | 116.50704 | -1.4182482 |
87 | 1 | -0.35536509 | 0.35482444E-03 | -143.92090 | 2.0492634 |
88 | 0 | 0.17324174 | 0.85915519E-05 | 60.838472 | |
89 | 7 | -0.23439288E-08 | -0.93347870E-15 | 0.55887675E-14 | -0.85663837E-16 |
90 | 6 | 0.50999137E-05 | 0.34523603E-08 | 0.31913583E-02 | -0.26771788E-04 |
91 | 5 | -0.36357417E-03 | 0.20434871E-05 | -0.22380918 | 0.19568970E-02 |
92 | 4 | 0.83428746E-02 | 0.92990125E-04 | 4.8309549 | -0.45278527E-01 |
93 | 3 | -0.73200817E-01 | 0.73925614E-03 | -38.029377 | 0.39874175 |
94 | 2 | 0.25983726 | 0.12295191E-02 | 116.49944 | -1.4181466 |
95 | 1 | -0.37498338 | 0.37446036E-03 | -143.91643 | 2.0491898 |
96 | 0 | 0.18280989 | 0.90753466E-05 | 60.838472 | |
97 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
98 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
99 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
100 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
101 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
102 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
103 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
104 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
105 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.2925_SHGC_EAST_0.45 | 35 | 1 | VerySmooth | 1.661 | 1.661 | 1.000 | 0.451 | ||
2 | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 36 | 1 | VerySmooth | 1.661 | 1.661 | 1.000 | 0.451 | ||
3 | WINDOW_U_0.2925_SHGC_WEST_0.45 | 37 | 1 | VerySmooth | 1.661 | 1.661 | 1.000 | 0.451 | ||
4 | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 38 | 1 | VerySmooth | 1.661 | 1.661 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 4.24435E-002 | 0.36619 | 0.44086 | 0.44086 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.92517E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 4.24435E-002 | 0.36619 | 0.44086 | 0.44086 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.92517E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 4.24435E-002 | 0.36619 | 0.44086 | 0.44086 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.92517E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 4.24435E-002 | 0.36619 | 0.44086 | 0.44086 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.92517E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2892E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2965E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4507E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4570E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.0773E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.1278E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3410E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3672E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1723 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1040 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1981 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1210 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1173 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2005E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0374E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8858E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2894E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2979E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4509E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4587E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.0792E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.1373E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3408E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3669E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.1573E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8269E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.9007E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5887E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.8016E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9462E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8621E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7388E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.1513E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.1818E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9037E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.9259E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2881E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.2958E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0663E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0753E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8459E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.9107E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0437E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0966E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4806E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.5198E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3408E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3669E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7183E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7761E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6564E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1246E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4703E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4599E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0374E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8858E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8456E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.9116E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0429E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0951E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4788E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.5129E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3410E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3672E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.8822E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1779E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2654E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7522E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.8716E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4978E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8621E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7389E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.3689E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.4652E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8956E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.0052E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7422E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7759E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0665E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0755E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1712 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1229 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1936 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1421 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1249 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.4690E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.6644E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.6249E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.8335E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.6458E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.5982E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.4201E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.5673E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.8193E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.7222E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6635E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.3135E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.5521E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.1881E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7924E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.9997E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0713E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.6644E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6249E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.6096E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0289E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.0290E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6253E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.6715E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3916E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.7222E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6636E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1712 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1228 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1936 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1420 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1248 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.4683E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.6639E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.6246E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.8337E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.6455E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.5983E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.4198E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.5670E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.8189E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.7217E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6632E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.3138E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.5519E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.1883E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7923E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.9995E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0711E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.6639E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6246E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.6098E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0287E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.0291E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6251E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.6712E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3912E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.7218E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6633E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 39183.54282 | 39183.54282 | 2.94644 | 2.94644 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 11487.38423 | 11487.38423 | 0.50597 | 0.50597 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 28729.88401 | 28729.88401 | 2.15783 | 2.15783 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 20759.06578 | 20759.06578 | 0.91972 | 0.91972 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 29529.77001 | 29529.77001 | 2.23893 | 2.23893 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 29.60400 | 1.27250E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 35518.44843 | 35518.44843 | 1.57800 | 1.57800 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9132.10213 | 9132.10213 | 0.69243 | 0.69243 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 29.85200 | 1.27254E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 16740.68894 | 16740.68894 | 0.74537 | 0.74537 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11568.09344 | 11568.09344 | 0.87713 | 0.87713 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 23.98267 | 1.27152E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 10948.94561 | 10948.94561 | 0.48752 | 0.48752 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 15239.96894 | 15239.96894 | 1.15554 | 1.15554 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 16855.14395 | 16855.14395 | 0.75048 | 0.75048 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12838.38443 | 12838.38443 | 0.97344 | 0.97344 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 11034.26720 | 11034.26720 | 0.49133 | 0.49133 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7341.14408 | 7341.14408 | 0.55662 | 0.55662 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.10000 | 1.27259E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 12513.03004 | 12513.03004 | 0.55686 | 0.55686 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9468.59204 | 9468.59204 | 0.71792 | 0.71792 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.68533 | 1.27164E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 8255.57100 | 8255.57100 | 0.36743 | 0.36743 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 12299.03662 | 12299.03662 | 0.93252 | 0.93252 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.10000 | 1.27259E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 12614.18398 | 12614.18398 | 0.56138 | 0.56138 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 10312.43663 | 10312.43663 | 0.78190 | 0.78190 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 26.50400 | 1.27196E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 8322.57574 | 8322.57574 | 0.37042 | 0.37042 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8090.53070 | 8090.53070 | 0.61345 | 0.61345 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.10000 | 1.27259E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 12899.11541 | 12899.11541 | 0.57404 | 0.57404 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 11428.28144 | 11428.28144 | 0.86652 | 0.86652 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.28000 | 1.27140E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 8482.97978 | 8482.97978 | 0.37755 | 0.37755 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 14071.87876 | 14071.87876 | 1.06696 | 1.06696 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 12986.77002 | 12986.77002 | 0.57795 | 0.57795 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11949.18323 | 11949.18323 | 0.90601 | 0.90601 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 8551.99206 | 8551.99206 | 0.38062 | 0.38062 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 76479.65 | 5.24131 | 5.24131 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 62944.74 | 2.36206 | 2.36206 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 69176.06 | 4.68283 | 4.68283 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 62972.37 | 2.82989 | 2.82989 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 76868.82 | 5.28660 | 5.28660 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 63027.45 | 4.05271 | 4.05271 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 01:30:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.94644 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25436 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79259 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67829 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49788E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25367.24906 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.15783 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34732 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35600 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76819 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92618 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09697E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 29436.02905 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.23893 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33474 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35400 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79258 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89263 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13821E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 50504.71790 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74537 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21196 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24100 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17964 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56523 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.79749E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23856.05401 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87713 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11403 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17543 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30409 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.34112E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15603.44135 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.15554 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13673 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23111 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36460 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.78660E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24019.44925 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.97344 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10274 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19469 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.70825E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15725.24520 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.55686 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28372 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16706 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75658 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34289E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17822.64007 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71792 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13932 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14358 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37153 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.73466E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11759.71544 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93252 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16942 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18650 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45180 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.24880E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17967.06163 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78190 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12791 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15638 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34110 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.97857E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11855.38223 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61345 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25755 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26400 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16195 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68679 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47934E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18372.53611 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86652 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11543 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17330 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30781 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.30070E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12083.52548 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.06696 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14808 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21339 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39487 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.57300E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18497.68060 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90601 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11039 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18120 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.45138E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12182.05393 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.96782 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.44612 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.93564 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.36206 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.24131 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.24131 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.45066 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.80538 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.49803 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.61076 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.82989 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.68283 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.68283 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.60431 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.99521 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.57344 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.99041 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 4.05271 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.28660 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.28660 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.76660 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.24131 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.68283 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.28660 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.24131 |
149 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_BOT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.19517 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.24131 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 103791.04402 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.78033 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.74693 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34593.55497 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.78033 |
156 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 60569.85827 |
157 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.24131 |
158 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.68283 |
159 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_MID OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.19517 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.68283 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 95340.50534 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.76893 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.56079 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31776.99043 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.76893 |
166 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 61914.73174 |
167 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.68283 |
168 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.28660 |
169 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_TOP OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.19517 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.28660 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 104951.84421 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.77956 |
173 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.76202 |
174 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34980.44967 |
175 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.77956 |
176 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 61498.68931 |
177 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.28660 |
178 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
179 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
180 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
181 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
182 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 102800.56 | 350770.06 | 11.27 | 2.88 | 3.23 | 3.40 | 3.57 | 9.83 | 11.01 | 11.59 | 12.19 | 5.8092 | 4.6447 | 3.1290 | 1.2516 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 94532.53 | 322558.39 | 11.33 | 2.89 | 3.24 | 3.42 | 3.58 | 9.87 | 11.07 | 11.66 | 12.23 | 5.1902 | 4.1432 | 2.7901 | 1.1296 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 103960.59 | 354728.25 | 11.28 | 2.88 | 3.23 | 3.40 | 3.57 | 9.83 | 11.01 | 11.59 | 12.20 | 5.8594 | 4.6854 | 3.1568 | 1.2633 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_EAST_0.45 | N/A | 1.661 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_WEST_0.45 | N/A | 1.661 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.171 | 0.164 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_EAST_0.45 | N/A | 1.661 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_EAST_0.45 | N/A | 1.661 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.180 | 0.173 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.171 | 0.164 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_WEST_0.45 | N/A | 1.661 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_WEST_0.45 | N/A | 1.661 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.180 | 0.173 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_EAST_0.45 | N/A | 1.661 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_WEST_0.45 | N/A | 1.661 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.2355268204E-002 | 2.2442130234E-002 | Pass | Pass | 0.4873468855 | 0.4972494190 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.3119323015 | 0.2526965747 | Pass | Pass | 0.5076511981 | 0.5113647284 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1500962129 | 9.7569017583E-002 | Pass | Pass | 0.5008339304 | 0.4952126678 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1270227891 | 8.2070802457E-002 | Pass | Pass | 0.4901236925 | 0.4946033733 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.2022460724E-002 | 5.3595617906E-002 | Pass | Pass | 0.6528796733 | 0.7076571231 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.2188398063 | 0.2312098197 | Pass | Pass | 0.6163623018 | 0.6254768352 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.0528658880 | 0.8894229972 | Pass | Pass | 0.5854584416 | 0.5473320733 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.9567556118 | 0.9589422121 | Pass | Pass | 0.5949366173 | 0.5596303069 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.6810124561 | 0.8147898985 | Pass | Pass | 0.6669136682 | 0.8131727051 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.9852209642 | 0.9996716326 | Pass | Pass | 0.5985485630 | 0.5609168753 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.7573494053 | 0.6566113682 | Pass | Pass | 0.6080614397 | 0.5665987197 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6403622455 | 0.6647758563 | Pass | Pass | 0.6125866765 | 0.5890713731 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3487344409 | 0.4301089207 | Pass | Pass | 0.9079590367 | 2.5316309697 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6677268562 | 0.6990253925 | Pass | Pass | 0.6234574136 | 0.5943082528 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.8014009265 | 0.6932677312 | Pass | Pass | 0.6369569585 | 0.5549343044 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.7077707249 | 0.7432133309 | Pass | Pass | 0.6236075377 | 0.5679293571 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4946995586 | 0.5901191865 | Pass | Pass | 0.7109497368 | 1.1972596731 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.7333940201 | 0.7670713820 | Pass | Pass | 0.6288761876 | 0.5689633036 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3414.57 | 232.65 | 0.00 | 2151.32 | 620.65 | 6419.19 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.159 | 0.163 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.166 | 0.171 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.175 | 0.180 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.166 | 0.171 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.175 | 0.180 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.661 | 0.451 | 0.452 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.2925_SHGC_EAST_0.45 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.661 | 0.451 | 0.452 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.661 | 0.451 | 0.452 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.2925_SHGC_WEST_0.45 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.661 | 0.451 | 0.452 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.2925_SHGC_EAST_0.45 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.2925_SHGC_EAST_0.45 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.2925_SHGC_WEST_0.45 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.2925_SHGC_WEST_0.45 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.661 | 0.451 | 0.452 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.2925_SHGC_EAST_0.45 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.661 | 0.451 | 0.452 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.661 | 0.451 | 0.452 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.2925_SHGC_WEST_0.45 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.661 | 0.451 | 0.452 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 1.661 | 0.451 | 0.452 | |||||||||||||||||
North Total or Average | 177.99 | 1.661 | 0.451 | 0.452 | |||||||||||||||||
Non-North Total or Average | 415.31 | 1.661 | 0.451 | 0.452 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.49 | 0.0000 | Y | 9.29 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.41 | 0.0000 | Y | 5.86 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.27 | 0.0000 | Y | 9.22 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.35 | 0.0000 | Y | 5.85 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.45 | 0.0000 | Y | 9.27 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.38 | 0.0000 | Y | 5.86 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.25 | 0.0000 | Y | 9.21 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.33 | 0.0000 | Y | 5.85 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.49 | 0.0000 | Y | 9.29 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.41 | 0.0000 | Y | 5.86 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.27 | 0.0000 | Y | 9.22 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.35 | 0.0000 | Y | 5.85 |
Interior Lighting Total | 7.5763 | 4982.19 | 37746.71 | 281.09 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 42.55 | 42.55 | 3.39 | |
EXTERIOR_LIGHTS_B | 5132.60 | AstronomicalClock | - | 83.52 | 71.23 | 68.63 | |
Exterior Lighting Total | 5557.43 | 72.02 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 103791.04 | 80991.78 | 22799.27 | 0.78 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 95340.51 | 73309.76 | 22030.74 | 0.77 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 104951.84 | 81816.47 | 23135.37 | 0.78 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 102800.6 | 2.88 | 9.83 | N/A | N/A | 11.27 | |
PACU_VAV_MID COOLING COIL | 94532.5 | 2.89 | 9.87 | N/A | N/A | 11.33 | |
PACU_VAV_TOP COOLING COIL | 103960.6 | 2.88 | 9.83 | N/A | N/A | 11.28 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25367.25 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 29436.03 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 50504.72 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 23856.05 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15603.44 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 24019.45 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15725.25 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17822.64 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11759.72 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17967.06 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11855.38 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18372.54 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12083.53 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18497.68 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12182.05 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 60569.86 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 61914.73 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 61498.69 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.24 | 12046.95 | 2298.46 | 1.00 | 1.13 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.68 | 10833.21 | 2313.39 | 1.00 | 1.13 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.29 | 12151.05 | 2298.46 | 1.00 | 1.13 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 102800.56 | 2.88 | 9.83 | 11.27 | 5.8092 | 3.23 | 11.01 | 4.6447 | 3.40 | 11.59 | 3.1290 | 3.57 | 12.19 | 1.2516 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 94532.53 | 2.89 | 9.87 | 11.33 | 5.1902 | 3.24 | 11.07 | 4.1432 | 3.42 | 11.66 | 2.7901 | 3.58 | 12.23 | 1.1296 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 103960.59 | 2.88 | 9.83 | 11.28 | 5.8594 | 3.23 | 11.01 | 4.6854 | 3.40 | 11.59 | 3.1568 | 3.57 | 12.20 | 1.2633 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 39183.54 | 39183.54 | 39.84 | 2.946 | 2.946 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00881 | 20.92 | 0.01271 | 0.425 | 0.00 |
CORE_MID | 28729.88 | 28729.88 | 29.21 | 2.158 | 2.158 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 20.92 | 0.01271 | 0.425 | 0.00 |
CORE_TOP | 29529.77 | 29529.77 | 30.02 | 2.239 | 2.239 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00891 | 29.60 | 0.01272 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9132.10 | 9132.10 | 44.04 | 0.692 | 0.692 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00896 | 29.85 | 0.01273 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11568.09 | 11568.09 | 88.13 | 0.877 | 0.877 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00874 | 23.98 | 0.01272 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15239.97 | 15239.97 | 73.50 | 1.156 | 1.156 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00878 | 29.89 | 0.01273 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12838.38 | 12838.38 | 97.81 | 0.973 | 0.973 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00872 | 27.95 | 0.01272 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7341.14 | 7341.14 | 35.41 | 0.557 | 0.557 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00897 | 30.10 | 0.01273 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9468.59 | 9468.59 | 72.13 | 0.718 | 0.718 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00874 | 24.69 | 0.01272 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12299.04 | 12299.04 | 59.32 | 0.933 | 0.933 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00878 | 30.10 | 0.01273 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 10312.44 | 10312.44 | 78.57 | 0.782 | 0.782 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00872 | 26.50 | 0.01272 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8090.53 | 8090.53 | 39.02 | 0.613 | 0.613 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00899 | 30.10 | 0.01273 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 11428.28 | 11428.28 | 87.06 | 0.867 | 0.867 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00873 | 23.28 | 0.01271 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 14071.88 | 14071.88 | 67.87 | 1.067 | 1.067 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00878 | 29.79 | 0.01273 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11949.18 | 11949.18 | 91.04 | 0.906 | 0.906 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00872 | 27.95 | 0.01272 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 11487.38 | 11487.38 | 11.68 | 0.506 | 0.506 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 0.425 | 0.00 |
CORE_MID | 20759.07 | 20759.07 | 21.11 | 0.920 | 0.920 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 0.425 | 0.00 |
CORE_TOP | 35518.45 | 35518.45 | 36.11 | 1.578 | 1.578 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 16740.69 | 16740.69 | 80.74 | 0.745 | 0.745 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10948.95 | 10948.95 | 83.41 | 0.488 | 0.488 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 16855.14 | 16855.14 | 81.29 | 0.750 | 0.750 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11034.27 | 11034.27 | 84.07 | 0.491 | 0.491 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 12513.03 | 12513.03 | 60.35 | 0.557 | 0.557 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8255.57 | 8255.57 | 62.89 | 0.367 | 0.367 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12614.18 | 12614.18 | 60.84 | 0.561 | 0.561 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8322.58 | 8322.58 | 63.41 | 0.370 | 0.370 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 12899.12 | 12899.12 | 62.21 | 0.574 | 0.574 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8482.98 | 8482.98 | 64.63 | 0.378 | 0.378 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12986.77 | 12986.77 | 62.64 | 0.578 | 0.578 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 8551.99 | 8551.99 | 65.16 | 0.381 | 0.381 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -32.70 | 0.00018 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.24 | 5.24 | 2.36 | 2.36 | 5.2413 | 2.3621 | 5.2413 | 0.4507 | 0.3000 |
PACU_VAV_MID | 4.68 | 4.68 | 2.83 | 2.83 | 4.6828 | 2.8299 | 4.6828 | 0.6043 | 0.3000 |
PACU_VAV_TOP | 5.29 | 5.29 | 4.05 | 4.05 | 5.2866 | 4.0527 | 5.2866 | 0.7666 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25367.249 | 25367.249 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25367.25 | 16193.86 | 0.505972 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 11487.38 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 29436.029 | 29436.029 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29436.03 | 29436.03 | 0.919720 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 20759.07 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 50504.718 | 50504.718 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 50504.72 | 50504.72 | 1.578004 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 35518.45 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 23856.054 | 23856.054 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23856.05 | 23856.05 | 0.745375 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00776946 | 48.1533 | 16740.69 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 15603.441 | 15603.441 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15603.44 | 15603.44 | 0.487525 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00776509 | 48.1268 | 10948.95 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 24019.449 | 24019.449 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24019.45 | 24019.45 | 0.750480 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00777098 | 48.1626 | 16855.14 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 15725.245 | 15725.245 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15725.25 | 15725.25 | 0.491330 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00776685 | 48.1376 | 11034.27 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 17822.640 | 17822.640 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17822.64 | 17822.64 | 0.556863 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00783321 | 48.5417 | 12513.03 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 11759.715 | 11759.715 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11759.72 | 11759.72 | 0.367429 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00783207 | 48.5348 | 8255.57 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 17967.062 | 17967.062 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17967.06 | 17967.06 | 0.561375 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00783465 | 48.5505 | 12614.18 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11855.382 | 11855.382 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11855.38 | 11855.38 | 0.370418 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00783350 | 48.5435 | 8322.58 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 18372.536 | 18372.536 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18372.54 | 18372.54 | 0.574044 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00775058 | 48.0372 | 12899.12 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 12083.525 | 12083.525 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12083.53 | 12083.53 | 0.377546 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00774764 | 48.0194 | 8482.98 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 18497.681 | 18497.681 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18497.68 | 18497.68 | 0.577954 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00775228 | 48.0477 | 12986.77 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 12182.054 | 12182.054 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12182.05 | 12182.05 | 0.380624 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00774968 | 48.0319 | 8551.99 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 103791.044 | 80991.777 | 5.241310 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 105437.70 | 87008.85 | 5.241310 | 25.39 | 17.44 | 0.00972460 | 10.85 | 10.85 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 22.8029 | 24.00 | 0.00883748 | 45.5674 | 69092.50 | 0.00 | 107022.50 | 80473.25 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 60569.858 | 60569.858 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 60569.86 | 60569.86 | 1.572393 | -20.42 | -20.42 | 0.00198746 | 12.80 | 11.22 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 76.0096 | 18.08 | 0.00771466 | 57.3212 | 21135.07 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 95340.505 | 73309.765 | 4.682834 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 97192.85 | 78614.66 | 4.682834 | 25.56 | 17.62 | 0.00988201 | 10.84 | 10.84 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 25.5224 | 24.00 | 0.00890561 | 45.9142 | 61673.98 | 0.00 | 98308.86 | 72892.07 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 61914.732 | 61914.732 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 61914.73 | 61914.73 | 1.404850 | -25.21 | -25.21 | 0.00128643 | 12.80 | 11.22 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 85.0746 | 17.61 | 0.00737307 | 56.4728 | 22252.74 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 104951.844 | 81816.471 | 5.286600 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 106649.46 | 87708.22 | 5.286600 | 25.38 | 17.46 | 0.00974792 | 10.85 | 10.85 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 22.6075 | 24.00 | 0.00887418 | 45.7546 | 69487.50 | 0.00 | 108219.44 | 81288.92 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 61498.689 | 61498.689 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 01:30:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 61498.69 | 61498.69 | 1.585980 | -20.64 | -20.64 | 0.00199717 | 12.80 | 11.22 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 75.3585 | 15.60 | 0.00732016 | 63.7239 | 23150.01 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25367.249 | 25367.249 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25367.25 | 16193.86 | 1.0000 | 0.58385363 | 0.505972 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25367.25 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 11487.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 29436.029 | 29436.029 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29436.03 | 29436.03 | 1.0000 | 1.06128728 | 0.919720 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29436.03 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 20759.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 50504.718 | 50504.718 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 50504.72 | 50504.72 | 1.0000 | 1.82089828 | 1.578004 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50504.72 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 35518.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 23856.054 | 23856.054 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23856.05 | 23856.05 | 1.0000 | 0.86010673 | 0.745375 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23856.05 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00776946 | 21.00 | 0.00776946 | 48.1533 | 16740.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 15603.441 | 15603.441 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15603.44 | 15603.44 | 1.0000 | 0.56256684 | 0.487525 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15603.44 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00776509 | 21.00 | 0.00776509 | 48.1268 | 10948.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 24019.449 | 24019.449 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24019.45 | 24019.45 | 1.0000 | 0.86599779 | 0.750480 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24019.45 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00777098 | 21.00 | 0.00777098 | 48.1626 | 16855.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 15725.245 | 15725.245 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15725.25 | 15725.25 | 1.0000 | 0.56695836 | 0.491330 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15725.25 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00776685 | 21.00 | 0.00776685 | 48.1376 | 11034.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 17822.640 | 17822.640 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17822.64 | 17822.64 | 1.0000 | 0.64257788 | 0.556863 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17822.64 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00783321 | 21.00 | 0.00783321 | 48.5417 | 12513.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 11759.715 | 11759.715 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11759.72 | 11759.72 | 1.0000 | 0.42398506 | 0.367429 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11759.72 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00783207 | 21.00 | 0.00783207 | 48.5348 | 8255.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 17967.062 | 17967.062 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17967.06 | 17967.06 | 1.0000 | 0.64778486 | 0.561375 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17967.06 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00783465 | 21.00 | 0.00783465 | 48.5505 | 12614.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 11855.382 | 11855.382 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11855.38 | 11855.38 | 1.0000 | 0.42743423 | 0.370418 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11855.38 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00783350 | 21.00 | 0.00783350 | 48.5435 | 8322.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 18372.536 | 18372.536 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18372.54 | 18372.54 | 1.0000 | 0.66240385 | 0.574044 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18372.54 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00775058 | 21.00 | 0.00775058 | 48.0372 | 12899.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 12083.525 | 12083.525 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12083.53 | 12083.53 | 1.0000 | 0.43565971 | 0.377546 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12083.53 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00774764 | 21.00 | 0.00774764 | 48.0194 | 8482.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 18497.681 | 18497.681 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18497.68 | 18497.68 | 1.0000 | 0.66691581 | 0.577954 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18497.68 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00775228 | 21.00 | 0.00775228 | 48.0477 | 12986.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 12182.054 | 12182.054 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12182.05 | 12182.05 | 1.0000 | 0.43921206 | 0.380624 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12182.05 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00774968 | 21.00 | 0.00774968 | 48.0319 | 8551.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 103791.044 | 80991.777 | 5.241310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.9175 | 1004.8586 | 1.1539 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.241310 | 6.04807789 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 105437.70 | 87008.85 | 1.0159 | 6.04807789 | 5.241310 | 25.39 | 17.44 | 0.00972460 | 50293.1 | 10.85 | 10.85 | 0.00850000 | 32334.8 | -999.0 | -999.00 | -999.00 | -999.00 | 12046.949 | 93390.75 | 30.10 | 0.01272586 | 21.13 | 1.19517000 | 22.8029 | 24.00 | 0.00883748 | 24.00 | 0.00883748 | 45.5674 | 69092.50 | 0.00 | 107022.50 | 80473.25 | 5.80922454 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.12 | 13.10 | 0.00939279 | 36899.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 60569.858 | 60569.858 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.241310 | 6.04807789 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 60569.86 | 60569.86 | 1.0000 | 1.81442337 | 1.572393 | -20.42 | -20.42 | 0.00198746 | -15624.8 | 12.80 | 11.22 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60569.86 | -32.70 | 0.00018338 | -32.70 | 1.19517000 | 76.0096 | 18.48 | 0.00770342 | 18.08 | 0.00771466 | 57.3212 | 21135.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 95340.505 | 73309.765 | 4.682834 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2102 | 1004.8586 | 1.1539 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.682834 | 5.40363846 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 97192.85 | 78614.66 | 1.0194 | 5.40363846 | 4.682834 | 25.56 | 17.62 | 0.00988201 | 50865.4 | 10.84 | 10.84 | 0.00850000 | 32322.4 | -999.0 | -999.00 | -999.00 | -999.00 | 10833.205 | 86359.65 | 30.10 | 0.01272586 | 21.13 | 1.19517000 | 25.5224 | 24.00 | 0.00890561 | 24.00 | 0.00890561 | 45.9142 | 61673.98 | 0.00 | 98308.86 | 72892.07 | 5.19023558 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.93 | 12.90 | 0.00926464 | 36381.3 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 61914.732 | 61914.732 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.682834 | 5.40363846 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 61914.73 | 61914.73 | 1.0000 | 1.62109154 | 1.404850 | -25.21 | -25.21 | 0.00128643 | -22173.6 | 12.80 | 11.22 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61914.73 | -32.70 | 0.00018338 | -32.70 | 1.19517000 | 85.0746 | 17.49 | 0.00757379 | 17.61 | 0.00737307 | 56.4728 | 22252.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 104951.844 | 81816.471 | 5.286600 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.9609 | 1004.8586 | 1.1539 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.286600 | 6.10033940 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 106649.46 | 87708.22 | 1.0162 | 6.10033940 | 5.286600 | 25.38 | 17.46 | 0.00974792 | 50344.3 | 10.85 | 10.85 | 0.00850000 | 32334.8 | -999.0 | -999.00 | -999.00 | -999.00 | 12151.047 | 94498.41 | 30.10 | 0.01272586 | 21.13 | 1.19517000 | 22.6075 | 24.00 | 0.00887418 | 24.00 | 0.00887418 | 45.7546 | 69487.50 | 0.00 | 108219.44 | 81288.92 | 5.85942211 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.10 | 13.09 | 0.00938263 | 36853.1 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 61498.689 | 61498.689 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.286600 | 6.10033940 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 01:30:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 61498.69 | 61498.69 | 1.0000 | 1.83010182 | 1.585980 | -20.64 | -20.64 | 0.00199717 | -15823.2 | 12.80 | 11.22 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61498.69 | -32.70 | 0.00018338 | -32.70 | 1.19517000 | 75.3585 | 16.24 | 0.00754408 | 15.60 | 0.00732016 | 63.7239 | 23150.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.24 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.68 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.29 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2262.00 | 3273.00 | 518.00 |
CORE_MID | 2930.17 | 3842.00 | 1534.00 |
CORE_TOP | 3416.17 | 4151.83 | 2199.83 |
PERIMETER_TOP_ZN_3 | 4021.00 | 4375.33 | 2866.17 |
PERIMETER_TOP_ZN_2 | 4056.67 | 4149.00 | 2676.33 |
PERIMETER_TOP_ZN_1 | 3713.50 | 4044.33 | 2319.50 |
PERIMETER_TOP_ZN_4 | 3975.67 | 4353.00 | 2726.17 |
PERIMETER_BOT_ZN_3 | 3876.83 | 4297.33 | 2715.50 |
PERIMETER_BOT_ZN_2 | 4018.83 | 3941.83 | 2470.50 |
PERIMETER_BOT_ZN_1 | 3803.17 | 4286.83 | 2542.67 |
PERIMETER_BOT_ZN_4 | 3962.67 | 4048.00 | 2519.33 |
PERIMETER_MID_ZN_3 | 3886.17 | 4101.33 | 2573.00 |
PERIMETER_MID_ZN_2 | 3357.17 | 3425.17 | 2123.50 |
PERIMETER_MID_ZN_1 | 3533.17 | 3749.83 | 1968.83 |
PERIMETER_MID_ZN_4 | 3825.83 | 4094.00 | 2415.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5170.00 | 4864.83 | 3247.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 1.00 | 1.83 | 0.83 | 1.33 |
CORE_MID | 3.33 | 0.67 | 2.50 | 0.67 |
CORE_TOP | 21.67 | 0.33 | 16.17 | 0.33 |
PERIMETER_TOP_ZN_3 | 339.67 | 1.33 | 167.00 | 1.17 |
PERIMETER_TOP_ZN_2 | 200.83 | 12.83 | 44.83 | 12.67 |
PERIMETER_TOP_ZN_1 | 168.33 | 19.33 | 35.33 | 19.00 |
PERIMETER_TOP_ZN_4 | 196.00 | 21.83 | 46.00 | 11.67 |
PERIMETER_BOT_ZN_3 | 181.33 | 1.67 | 136.00 | 1.67 |
PERIMETER_BOT_ZN_2 | 50.50 | 9.50 | 12.17 | 9.50 |
PERIMETER_BOT_ZN_1 | 729.00 | 17.67 | 698.00 | 17.67 |
PERIMETER_BOT_ZN_4 | 49.33 | 17.17 | 12.00 | 8.17 |
PERIMETER_MID_ZN_3 | 153.50 | 3.33 | 84.67 | 3.33 |
PERIMETER_MID_ZN_2 | 84.17 | 15.17 | 16.83 | 15.17 |
PERIMETER_MID_ZN_1 | 58.50 | 22.50 | 9.67 | 22.33 |
PERIMETER_MID_ZN_4 | 83.33 | 22.33 | 18.67 | 11.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1030.83 | 98.50 | 797.17 | 80.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.92 | 52.94 | 2698.04 | 0.906 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.92 | 52.94 | 2698.04 | 0.672 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.92 | 52.94 | 2698.04 | 0.654 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.62 | 11.16 | 568.77 | 0.809 | 0.086 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 1.324 | 0.091 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.62 | 11.16 | 568.77 | 1.218 | 0.086 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 1.348 | 0.091 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.62 | 11.16 | 568.77 | 0.695 | 0.046 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 1.124 | 0.048 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.62 | 11.16 | 568.77 | 1.011 | 1.356 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 1.104 | 0.048 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.62 | 11.16 | 568.77 | 0.777 | 0.072 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 1.227 | 0.080 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.62 | 11.16 | 568.77 | 1.196 | 0.072 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 1.304 | 0.076 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.92 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.92 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.92 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.92 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.92 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.92 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.57 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.67 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 14532320.98 | 0.00 | 14532320.98 | 0.00 | 14532320.98 | 13393058.27 | 6130.15 | 36.87 | 2592.98 | 332.81 |
CORE_MID | 10756641.94 | 0.00 | 10756641.94 | 0.00 | 10756641.94 | 13393058.27 | 6691.60 | 24.38 | 2044.01 | 340.30 |
CORE_TOP | 10435781.75 | 0.00 | 10435781.75 | 0.00 | 10435781.75 | 13393058.27 | 6728.65 | 19.24 | 2012.11 | 85.47 |
PERIMETER_TOP_ZN_3 | 2718204.08 | 0.00 | 2718204.08 | 554487.21 | 3272691.29 | 2823374.22 | 4598.40 | 1084.92 | 3076.68 | 85.47 |
PERIMETER_TOP_ZN_2 | 2811085.68 | 0.00 | 2811085.68 | 369655.91 | 3180741.59 | 1787429.43 | 4098.84 | 1.84 | 4659.32 | 85.47 |
PERIMETER_TOP_ZN_1 | 4078588.75 | 0.00 | 4078588.75 | 554487.21 | 4633075.96 | 2823374.22 | 4117.74 | 2.52 | 4639.74 | 85.47 |
PERIMETER_TOP_ZN_4 | 2876905.54 | 0.00 | 2876905.54 | 369655.91 | 3246561.46 | 1787312.18 | 4093.87 | 2.28 | 4663.86 | 85.47 |
PERIMETER_BOT_ZN_3 | 2368959.70 | 0.00 | 2368959.70 | 294816.05 | 2663775.75 | 2823374.22 | 6018.63 | 53.05 | 2688.31 | 332.81 |
PERIMETER_BOT_ZN_2 | 2411021.31 | 0.00 | 2411021.31 | 196542.85 | 2607564.17 | 1787429.43 | 4083.22 | 9.49 | 4667.29 | 332.81 |
PERIMETER_BOT_ZN_1 | 3438657.52 | 0.00 | 3438657.52 | 4714532.20 | 8153189.72 | 2823374.22 | 4245.16 | 59.31 | 4455.52 | 332.81 |
PERIMETER_BOT_ZN_4 | 2381745.11 | 0.00 | 2381745.11 | 196542.85 | 2578287.97 | 1787312.18 | 4087.86 | 8.91 | 4663.23 | 332.81 |
PERIMETER_MID_ZN_3 | 2616807.68 | 0.00 | 2616807.68 | 461566.56 | 3078374.25 | 2823374.22 | 5979.37 | 54.24 | 2726.38 | 340.30 |
PERIMETER_MID_ZN_2 | 2828005.75 | 0.00 | 2828005.75 | 307709.19 | 3135714.94 | 1787429.43 | 4069.41 | 1.24 | 4689.35 | 1249.30 |
PERIMETER_MID_ZN_1 | 4014872.16 | 0.00 | 4014872.16 | 461566.56 | 4476438.73 | 2823374.22 | 4084.16 | 1.54 | 4674.30 | 340.30 |
PERIMETER_MID_ZN_4 | 2792148.18 | 0.00 | 2792148.18 | 307709.19 | 3099857.37 | 1787312.18 | 4064.85 | 3.24 | 4691.91 | 340.30 |
Total Facility | 71061746.14 | 0.00 | 71061746.14 | 8789271.71 | 79851017.85 | 67843644.98 | 6873.65 | 1243.84 | 4801.59 | 1409.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6640 | 0.0000 | 0.6640 | 0.0000 | 0.6640 | 0.4247 | 3405.99 | 36.59 | 2500.42 |
CORE_MID | 0.4935 | 0.0000 | 0.4935 | 0.0000 | 0.4935 | 0.4247 | 3930.80 | 24.38 | 1987.82 |
CORE_TOP | 0.4808 | 0.0000 | 0.4808 | 0.0000 | 0.4808 | 0.4247 | 3962.55 | 19.24 | 1961.21 |
PERIMETER_TOP_ZN_3 | 0.1255 | 0.0000 | 0.1255 | 0.0135 | 0.1389 | 0.0895 | 1832.30 | 1084.92 | 3025.78 |
PERIMETER_TOP_ZN_2 | 0.1299 | 0.0000 | 0.1299 | 0.0090 | 0.1388 | 0.0567 | 1332.74 | 1.84 | 4608.42 |
PERIMETER_TOP_ZN_1 | 0.1886 | 0.0000 | 0.1886 | 0.0135 | 0.2021 | 0.0895 | 1351.64 | 2.52 | 4588.84 |
PERIMETER_TOP_ZN_4 | 0.1323 | 0.0000 | 0.1323 | 0.0090 | 0.1413 | 0.0567 | 1327.77 | 2.28 | 4612.96 |
PERIMETER_BOT_ZN_3 | 0.1078 | 0.0000 | 0.1078 | 0.0072 | 0.1149 | 0.0895 | 3294.05 | 52.78 | 2596.17 |
PERIMETER_BOT_ZN_2 | 0.1101 | 0.0000 | 0.1101 | 0.0048 | 0.1149 | 0.0567 | 1361.91 | 9.49 | 4571.60 |
PERIMETER_BOT_ZN_1 | 0.1574 | 0.0000 | 0.1574 | 0.2137 | 0.3711 | 0.0895 | 1522.89 | 58.65 | 4361.47 |
PERIMETER_BOT_ZN_4 | 0.1083 | 0.0000 | 0.1083 | 0.0048 | 0.1131 | 0.0567 | 1366.55 | 8.91 | 4567.54 |
PERIMETER_MID_ZN_3 | 0.1204 | 0.0000 | 0.1204 | 0.0112 | 0.1316 | 0.0895 | 3218.57 | 54.24 | 2670.19 |
PERIMETER_MID_ZN_2 | 0.1203 | 0.0000 | 0.1203 | 0.0079 | 0.1282 | 0.0567 | 1309.48 | 0.74 | 3723.78 |
PERIMETER_MID_ZN_1 | 0.1851 | 0.0000 | 0.1851 | 0.0112 | 0.1963 | 0.0895 | 1324.53 | 1.54 | 4616.94 |
PERIMETER_MID_ZN_4 | 0.1280 | 0.0000 | 0.1280 | 0.0075 | 0.1354 | 0.0567 | 1305.25 | 3.23 | 4634.53 |
Total Facility | 3.2520 | 0.0000 | 3.2520 | 0.3131 | 3.5650 | 2.1513 | 4088.02 | 1242.88 | 4686.20 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 33465259.92 | 0.00 | 33465259.92 | 22614548.33 | 4056.55 | 0.22 | 4703.22 | 332.81 |
PACU_VAV_MID | 30636789.55 | 0.00 | 30636789.55 | 22614548.33 | 4074.67 | 0.86 | 4684.47 | 339.59 |
PACU_VAV_TOP | 30519725.75 | 0.00 | 30519725.75 | 22614548.33 | 4105.22 | 2.01 | 4652.77 | 85.06 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.5281 | 0.0000 | 1.5281 | 0.7171 | 1335.22 | 0.22 | 4607.56 |
PACU_VAV_MID | 1.4075 | 0.0000 | 1.4075 | 0.7171 | 1315.03 | 0.86 | 4627.11 |
PACU_VAV_TOP | 1.4075 | 0.0000 | 1.4075 | 0.7171 | 1339.12 | 2.01 | 4601.87 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 2.33 | 2826.78 | 0.00 | 0.00 | 0.00 | 2319.03 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 1.00 | 2704.90 | 0.00 | 0.00 | 0.00 | 2498.15 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2349.67 | 0.00 | 0.00 | 0.00 | 2496.19 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 8.1422 | 2.6534 | 0.0000 | 0.0000 | 0.0000 | 1.0566 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.4203 | 0.0000 | 0.0000 | 0.0000 | 1.0547 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.5299 | 0.0000 | 0.0000 | 0.0000 | 1.0567 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 545 |
Fields with Defaults | 2289 |
Autosized Fields | 152 |
Autosizable Fields | 205 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1825.47 | 15539.06 | 19-MAR-17:10 | 282107.28 | 02-JAN-08:10 |
Electricity:Building | 1043.13 | 15341.49 | 01-JAN-09:30 | 75641.67 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 310.83 | 4652.71 | 01-JAN-00:10 | 24063.48 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1043.13 | 15341.49 | 01-JAN-09:30 | 75641.67 | 02-JAN-08:10 |
InteriorLights:Electricity | 281.09 | 1316.11 | 01-JAN-09:30 | 28079.40 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 281.09 | 1316.11 | 01-JAN-09:30 | 28079.40 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 281.09 | 1316.11 | 01-JAN-09:30 | 28079.40 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 281.09 | 1316.11 | 01-JAN-09:30 | 28079.40 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 35.97 | 541.99 | 01-JAN-09:30 | 2674.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.29 | 40.03 | 01-JAN-09:30 | 1168.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.29 | 40.03 | 01-JAN-09:30 | 1168.55 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 22.76 | 343.10 | 01-JAN-08:40 | 1693.08 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.86 | 25.34 | 01-JAN-08:40 | 739.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.86 | 25.34 | 01-JAN-08:40 | 739.79 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 35.91 | 541.99 | 01-JAN-08:40 | 2674.43 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.22 | 40.03 | 01-JAN-08:40 | 1168.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.22 | 40.03 | 01-JAN-08:40 | 1168.55 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 22.75 | 343.10 | 01-JAN-09:30 | 1693.03 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.85 | 25.34 | 01-JAN-09:30 | 739.74 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.85 | 25.34 | 01-JAN-09:30 | 739.74 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 35.96 | 541.99 | 01-JAN-09:20 | 2674.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.27 | 40.03 | 01-JAN-09:20 | 1168.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.27 | 40.03 | 01-JAN-09:20 | 1168.55 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 22.75 | 343.10 | 01-JAN-08:40 | 1693.08 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.86 | 25.34 | 01-JAN-08:40 | 739.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.86 | 25.34 | 01-JAN-08:40 | 739.79 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 35.90 | 541.99 | 01-JAN-08:40 | 2674.43 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.21 | 40.03 | 01-JAN-08:40 | 1168.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.21 | 40.03 | 01-JAN-08:40 | 1168.55 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 22.74 | 343.10 | 01-JAN-09:20 | 1693.03 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.85 | 25.34 | 01-JAN-09:20 | 739.74 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.85 | 25.34 | 01-JAN-09:20 | 739.74 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 35.97 | 541.99 | 01-JAN-09:30 | 2674.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.29 | 40.03 | 01-JAN-09:30 | 1168.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.29 | 40.03 | 01-JAN-09:30 | 1168.55 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 22.76 | 343.10 | 01-JAN-08:40 | 1693.08 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.86 | 25.34 | 01-JAN-08:40 | 739.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.86 | 25.34 | 01-JAN-08:40 | 739.79 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 35.91 | 541.99 | 01-JAN-08:40 | 2674.43 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.22 | 40.03 | 01-JAN-08:40 | 1168.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.22 | 40.03 | 01-JAN-08:40 | 1168.55 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 22.75 | 343.10 | 01-JAN-09:30 | 1693.03 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.85 | 25.34 | 01-JAN-09:30 | 739.74 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.85 | 25.34 | 01-JAN-09:30 | 739.74 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 247.34 | 4344.73 | 01-JAN-00:10 | 18520.31 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 710.30 | 197.57 | 20-FEB-08:20 | 236462.98 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 928.21 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 928.21 | 02-JAN-08:20 |
ElectricityPurchased:Facility | 1825.47 | 15539.06 | 17-JUN-18:20 | 282107.28 | 02-JAN-08:10 |
ElectricityPurchased:Plant | 1825.47 | 15539.06 | 17-JUN-18:20 | 282107.28 | 02-JAN-08:10 |
Cogeneration:ElectricityPurchased | 1825.47 | 15539.06 | 17-JUN-18:20 | 282107.28 | 02-JAN-08:10 |
General:Cogeneration:ElectricityPurchased | 1825.47 | 15539.06 | 17-JUN-18:20 | 282107.28 | 02-JAN-08:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1825.47 | 15539.06 | 17-JUN-18:20 | 282107.28 | 02-JAN-08:10 |
ElectricityNet:Plant | 1825.47 | 15539.06 | 17-JUN-18:20 | 282107.28 | 02-JAN-08:10 |
Cogeneration:ElectricityNet | 1825.47 | 15539.06 | 17-JUN-18:20 | 282107.28 | 02-JAN-08:10 |
General:Cogeneration:ElectricityNet | 1825.47 | 15539.06 | 17-JUN-18:20 | 282107.28 | 02-JAN-08:10 |
Heating:Electricity | 453.73 | 0.00 | 01-JAN-00:40 | 226564.56 | 02-JAN-06:20 |
General:Heating:Electricity | 453.73 | 0.00 | 01-JAN-00:40 | 226564.56 | 02-JAN-06:20 |
Fans:Electricity | 101.29 | 0.00 | 01-JAN-00:40 | 35017.19 | 05-JUL-10:40 |
General:Fans:Electricity | 101.29 | 0.00 | 01-JAN-00:40 | 35017.19 | 05-JUL-10:40 |
ExteriorLights:Electricity | 72.02 | 0.00 | 01-JAN-08:20 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 72.02 | 0.00 | 01-JAN-08:20 | 5557.43 | 01-JAN-06:10 |
HeatRecovery:Electricity | 24.00 | 0.00 | 01-JAN-00:10 | 2722.67 | 02-JAN-08:50 |
General:HeatRecovery:Electricity | 24.00 | 0.00 | 01-JAN-00:10 | 2722.67 | 02-JAN-08:50 |
Cooling:Electricity | 118.29 | 0.00 | 01-JAN-00:10 | 80445.31 | 05-JUL-11:50 |
General:Cooling:Electricity | 118.29 | 0.00 | 01-JAN-00:10 | 80445.31 | 05-JUL-11:50 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 7.90 | 0.00 | 01-JAN-00:10 | 789.03 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 641.94 | 12061.80 | 01-JAN-00:10 | 36271.65 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 221.94 | 1156.00 | 02-JAN-06:00 | 191502.39 | 06-JAN-08:00 |
NaturalGas:HVAC | 101.56 | 0.00 | 01-JAN-00:40 | 183919.64 | 06-JAN-07:40 |
Heating:NaturalGas | 101.56 | 0.00 | 01-JAN-00:40 | 183919.64 | 06-JAN-07:40 |
General:Heating:NaturalGas | 101.56 | 0.00 | 01-JAN-00:40 | 183919.64 | 06-JAN-07:40 |
NaturalGas:Plant | 120.38 | 1156.00 | 02-JAN-05:30 | 13170.07 | 24-FEB-12:30 |
WaterSystems:NaturalGas | 120.38 | 1156.00 | 02-JAN-05:30 | 13170.07 | 24-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 120.38 | 1156.00 | 02-JAN-05:30 | 13170.07 | 24-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2691.33 | 0.00 | 01-JAN-00:40 | 568108.69 | 09-JAN-07:10 |
EnergyTransfer:Building | 1261.77 | 0.00 | 01-JAN-00:40 | 231204.29 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 203.64 | 0.00 | 01-JAN-00:40 | 27454.58 | 05-JUL-08:00 |
Heating:EnergyTransfer | 413.02 | 0.00 | 01-JAN-00:40 | 231204.29 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.72 | 0.00 | 01-JAN-00:10 | 19933.90 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 413.02 | 0.00 | 01-JAN-00:40 | 231204.29 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.72 | 0.00 | 01-JAN-00:10 | 19933.90 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 848.74 | 0.00 | 01-JAN-00:40 | 174403.66 | 24-JUL-15:40 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 202.92 | 0.00 | 01-JAN-00:40 | 27454.58 | 05-JUL-08:00 |
General:Cooling:EnergyTransfer | 848.74 | 0.00 | 01-JAN-00:40 | 174403.66 | 24-JUL-15:40 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 202.92 | 0.00 | 01-JAN-00:40 | 27454.58 | 05-JUL-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 75.12 | 0.00 | 01-JAN-00:40 | 19457.11 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 53.77 | 0.00 | 01-JAN-00:40 | 19457.11 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 53.77 | 0.00 | 01-JAN-00:40 | 19457.11 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 21.35 | 0.00 | 01-JAN-00:10 | 11212.19 | 30-JUN-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 21.35 | 0.00 | 01-JAN-00:10 | 11212.19 | 30-JUN-14:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 35.99 | 0.00 | 01-JAN-00:40 | 11847.42 | 26-DEC-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 22.75 | 0.00 | 01-JAN-00:40 | 11847.42 | 26-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 22.75 | 0.00 | 01-JAN-00:40 | 11847.42 | 26-DEC-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.24 | 0.00 | 01-JAN-00:10 | 5701.76 | 24-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.24 | 0.00 | 01-JAN-00:10 | 5701.76 | 24-JUL-14:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 33.85 | 0.00 | 01-JAN-00:40 | 9544.07 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 15.71 | 0.00 | 01-JAN-00:40 | 9544.07 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 15.71 | 0.00 | 01-JAN-00:40 | 9544.07 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 18.14 | 0.00 | 01-JAN-00:10 | 6030.40 | 24-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 18.14 | 0.00 | 01-JAN-00:10 | 6030.40 | 24-JUL-16:00 |
EnergyTransfer:Zone:CORE_MID | 135.11 | 0.00 | 01-JAN-00:40 | 25746.24 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 6.05 | 0.00 | 01-JAN-00:40 | 25746.24 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 6.05 | 0.00 | 01-JAN-00:40 | 25746.24 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 129.05 | 0.00 | 01-JAN-00:20 | 19053.76 | 24-JUL-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 129.05 | 0.00 | 01-JAN-00:20 | 19053.76 | 24-JUL-07:40 |
EnergyTransfer:Zone:CORE_TOP | 136.71 | 0.00 | 01-JAN-00:40 | 28988.32 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 23.99 | 0.00 | 01-JAN-00:40 | 28988.32 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 23.99 | 0.00 | 01-JAN-00:40 | 28988.32 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 112.72 | 0.00 | 01-JAN-00:20 | 20604.71 | 24-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 112.72 | 0.00 | 01-JAN-00:20 | 20604.71 | 24-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 63.78 | 0.00 | 01-JAN-00:40 | 10801.53 | 13-FEB-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.83 | 0.00 | 01-JAN-00:40 | 10801.53 | 13-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.83 | 0.00 | 01-JAN-00:40 | 10801.53 | 13-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.95 | 0.00 | 01-JAN-00:10 | 7347.92 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.95 | 0.00 | 01-JAN-00:10 | 7347.92 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.92 | 0.00 | 01-JAN-00:40 | 10780.78 | 04-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 23.20 | 0.00 | 01-JAN-00:40 | 10780.78 | 04-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 23.20 | 0.00 | 01-JAN-00:40 | 10780.78 | 04-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 26.73 | 0.00 | 01-JAN-00:10 | 10122.95 | 24-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 26.73 | 0.00 | 01-JAN-00:10 | 10122.95 | 24-JUL-08:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 72.21 | 0.00 | 01-JAN-00:40 | 15314.88 | 01-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 27.96 | 0.00 | 01-JAN-00:40 | 15213.05 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 27.96 | 0.00 | 01-JAN-00:40 | 15213.05 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 44.25 | 0.00 | 01-JAN-00:10 | 15314.88 | 01-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 44.25 | 0.00 | 01-JAN-00:10 | 15314.88 | 01-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 51.60 | 0.00 | 01-JAN-00:40 | 11707.20 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 24.39 | 0.00 | 01-JAN-00:40 | 11707.20 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 24.39 | 0.00 | 01-JAN-00:40 | 11707.20 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 27.21 | 0.00 | 01-JAN-00:10 | 10731.91 | 30-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 27.21 | 0.00 | 01-JAN-00:10 | 10731.91 | 30-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 45.73 | 0.00 | 01-JAN-00:40 | 7818.24 | 09-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 24.18 | 0.00 | 01-JAN-00:40 | 7818.24 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 24.18 | 0.00 | 01-JAN-00:40 | 7818.24 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 21.55 | 0.00 | 01-JAN-00:10 | 5586.35 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 21.55 | 0.00 | 01-JAN-00:10 | 5586.35 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 37.86 | 0.00 | 01-JAN-00:40 | 8673.50 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 13.29 | 0.00 | 01-JAN-00:40 | 8673.50 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 13.29 | 0.00 | 01-JAN-00:40 | 8673.50 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 24.57 | 0.00 | 01-JAN-00:10 | 8098.47 | 24-JUL-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 24.57 | 0.00 | 01-JAN-00:10 | 8098.47 | 24-JUL-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 88.29 | 0.00 | 01-JAN-00:40 | 21682.93 | 06-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 58.56 | 0.00 | 01-JAN-00:40 | 21682.93 | 06-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 58.56 | 0.00 | 01-JAN-00:40 | 21682.93 | 06-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 29.72 | 0.00 | 01-JAN-00:20 | 13905.11 | 29-JUN-16:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 29.72 | 0.00 | 01-JAN-00:20 | 13905.11 | 29-JUN-16:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 38.16 | 0.00 | 01-JAN-00:40 | 9165.02 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 13.94 | 0.00 | 01-JAN-00:40 | 9165.02 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 13.94 | 0.00 | 01-JAN-00:40 | 9165.02 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 24.22 | 0.00 | 01-JAN-00:10 | 8281.61 | 30-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 24.22 | 0.00 | 01-JAN-00:10 | 8281.61 | 30-JUN-18:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 48.63 | 0.00 | 01-JAN-00:40 | 8577.08 | 09-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 23.08 | 0.00 | 01-JAN-00:40 | 8577.08 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 23.08 | 0.00 | 01-JAN-00:40 | 8577.08 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.55 | 0.00 | 01-JAN-00:10 | 6745.10 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.55 | 0.00 | 01-JAN-00:10 | 6745.10 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 41.55 | 0.00 | 01-JAN-00:40 | 10015.18 | 24-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 13.34 | 0.00 | 01-JAN-00:40 | 9696.15 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 13.34 | 0.00 | 01-JAN-00:40 | 9696.15 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 28.21 | 0.00 | 01-JAN-00:10 | 10015.18 | 24-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 28.21 | 0.00 | 01-JAN-00:10 | 10015.18 | 24-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 61.29 | 0.00 | 01-JAN-00:40 | 14346.35 | 01-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 14.42 | 0.00 | 01-JAN-00:40 | 13319.82 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 14.42 | 0.00 | 01-JAN-00:40 | 13319.82 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 46.87 | 0.00 | 01-JAN-00:10 | 14346.35 | 01-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 46.87 | 0.00 | 01-JAN-00:10 | 14346.35 | 01-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 42.31 | 0.00 | 01-JAN-00:40 | 10134.18 | 30-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 13.83 | 0.00 | 01-JAN-00:40 | 9732.42 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 13.83 | 0.00 | 01-JAN-00:40 | 9732.42 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 28.49 | 0.00 | 01-JAN-00:20 | 10134.18 | 30-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 28.49 | 0.00 | 01-JAN-00:20 | 10134.18 | 30-JUN-17:00 |
PlantLoopHeatingDemand:Facility | 59.32 | 0.00 | 01-JAN-00:10 | 7496.52 | 23-FEB-12:30 |
PlantLoopHeatingDemand:Plant | 59.32 | 0.00 | 01-JAN-00:10 | 7496.52 | 23-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 59.32 | 0.00 | 01-JAN-00:10 | 7496.52 | 23-FEB-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 59.32 | 0.00 | 01-JAN-00:10 | 7496.52 | 23-FEB-12:30 |
EnergyTransfer:HVAC | 1370.24 | 0.00 | 01-JAN-00:40 | 357319.84 | 05-JUL-10:40 |
HeatingCoils:EnergyTransfer | 534.98 | 0.00 | 01-JAN-00:40 | 347974.50 | 09-JAN-07:10 |
HeatRecoveryForHeating:EnergyTransfer | 340.15 | 0.00 | 01-JAN-00:10 | 95663.54 | 13-JAN-17:10 |
HeatRecoveryForCooling:EnergyTransfer | 13.07 | 0.00 | 01-JAN-00:10 | 56504.43 | 15-JUL-14:00 |
CoolingCoils:EnergyTransfer | 482.04 | 0.00 | 01-JAN-00:10 | 357319.84 | 05-JUL-10:40 |
EnergyTransfer:Plant | 59.32 | 0.00 | 01-JAN-00:10 | 7496.52 | 23-FEB-12:30 |
WaterSystems:EnergyTransfer | 59.32 | 0.00 | 01-JAN-00:10 | 7496.52 | 23-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 59.32 | 0.00 | 01-JAN-00:10 | 7496.52 | 23-FEB-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.722 | -202.918 | 0.000 | 0.000 | 33.744 | 63.485 | 247.342 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -142.375 |
CORE_MID | 0.000 | 0.000 | 6.055 | -129.055 | 0.000 | 0.000 | 35.282 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -102.367 |
CORE_TOP | 0.000 | 0.000 | 23.986 | -112.725 | 0.000 | 0.000 | 35.917 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -137.264 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 39.832 | -23.952 | 0.000 | 0.000 | 7.712 | 9.286 | 26.688 | 18.272 | 0.000 | 0.041 | 0.000 | 0.000 | -36.486 | 0.000 | -11.763 | -29.631 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 23.198 | -26.727 | 0.000 | 0.000 | 4.839 | 5.863 | 16.895 | 34.895 | 0.000 | 0.027 | 0.000 | 0.000 | -22.683 | 0.000 | -7.920 | -28.387 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 27.960 | -44.249 | 0.000 | 0.000 | 7.541 | 9.222 | 26.688 | 74.104 | 0.000 | 0.038 | 0.001 | 0.000 | -33.036 | 0.000 | -12.084 | -56.184 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 24.391 | -27.206 | 0.000 | 0.000 | 4.892 | 5.853 | 16.895 | 35.434 | 0.000 | 0.026 | 0.000 | 0.000 | -23.477 | 0.000 | -7.938 | -28.868 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 24.179 | -21.555 | 0.000 | 0.000 | 7.672 | 9.274 | 26.688 | 18.377 | 0.000 | 0.026 | 0.000 | 0.000 | -37.378 | 0.000 | -6.456 | -20.828 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 13.295 | -24.570 | 0.000 | 0.000 | 4.797 | 5.857 | 16.895 | 34.923 | 0.000 | 0.015 | 0.000 | 0.000 | -23.514 | 0.000 | -4.384 | -23.314 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 58.564 | -29.722 | 0.000 | 0.000 | 7.900 | 9.214 | 26.688 | 74.926 | 0.000 | 1.072 | 0.001 | 0.000 | -33.747 | 0.000 | -85.241 | -29.654 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 13.941 | -24.217 | 0.000 | 0.000 | 4.833 | 5.847 | 16.895 | 35.479 | 0.000 | 0.014 | 0.000 | 0.000 | -24.323 | 0.000 | -4.397 | -24.073 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 23.080 | -25.552 | 0.000 | 0.000 | 7.623 | 9.286 | 26.688 | 17.962 | 0.000 | 0.035 | 0.000 | 0.000 | -37.864 | 0.000 | -10.126 | -11.132 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 13.344 | -28.208 | 0.000 | 0.000 | 3.555 | 5.863 | 16.895 | 34.686 | 0.000 | 0.023 | 0.000 | 0.000 | -23.507 | 0.000 | -6.798 | -15.852 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 14.416 | -46.873 | 0.000 | 0.000 | 7.441 | 9.222 | 26.688 | 73.743 | 0.000 | 0.032 | 0.000 | 0.000 | -34.368 | 0.000 | -10.422 | -39.880 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 13.826 | -28.488 | 0.000 | 0.000 | 4.838 | 5.853 | 16.895 | 35.238 | 0.000 | 0.022 | 0.000 | 0.000 | -24.349 | 0.000 | -6.824 | -17.011 |
TOPFLOOR_PLENUM | 53.768 | -21.353 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.034 | 0.000 | 0.000 | 0.000 | 0.000 | -17.736 | -14.713 |
MIDFLOOR_PLENUM | 22.753 | -13.236 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.046 | 7.498 | 0.000 | 0.000 | 0.000 | -17.061 | -0.000 |
FIRSTFLOOR_PLENUM | 15.714 | -18.136 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.035 | 16.078 | 0.000 | 0.000 | 0.000 | -13.691 | -0.000 |
Total Facility | 92.236 | -52.724 | 320.788 | -796.017 | 0.000 | 0.000 | 178.586 | 281.093 | 762.041 | 488.040 | 0.000 | 1.486 | 23.581 | 0.000 | -354.731 | 0.000 | -222.841 | -721.534 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 05-JUL-04:02 | 0.00 | 0.00 | 0.00 | -45371.43 | 0.00 | 0.00 | 0.00 | 615.87 | 5138.45 | 0.00 | 0.00 | 0.00 | 39617.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-JUL-04:02 | 0.00 | 0.00 | 0.00 | -33009.50 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 29218.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-04:02 | 0.00 | 0.00 | 0.00 | -34004.09 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 30213.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 23-JUL-15:32 | 0.00 | 0.00 | 0.00 | -9741.80 | 0.00 | 0.00 | 27.39 | 40.03 | 501.96 | 3185.72 | 0.00 | 170.57 | 5816.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 25-JUN-08:12 | 0.00 | 0.00 | 0.00 | -15050.82 | 0.00 | 0.00 | 12.90 | 25.34 | 317.77 | 11963.77 | 0.00 | 0.00 | 2822.67 | 0.00 | -0.00 | 0.00 | -91.63 | 0.00 |
PERIMETER_TOP_ZN_1 | 22-OCT-13:21 | 0.00 | 0.00 | 0.00 | -21294.93 | 0.00 | 0.00 | 21.81 | 40.03 | 501.96 | 18457.45 | 0.00 | 0.00 | 2608.54 | 0.00 | -0.00 | 0.00 | -334.85 | 0.00 |
PERIMETER_TOP_ZN_4 | 27-AUG-17:22 | 0.00 | 0.00 | 0.00 | -16778.13 | 0.00 | 0.00 | 0.00 | 25.34 | 317.76 | 9345.50 | 0.00 | 0.00 | 7206.34 | 0.00 | -0.00 | 0.00 | -116.81 | 0.00 |
PERIMETER_BOT_ZN_3 | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | -7210.25 | 0.00 | 0.00 | 147.26 | 240.13 | 669.29 | 2745.81 | 0.00 | 0.00 | 3434.41 | 0.00 | -0.00 | 0.00 | -26.66 | 0.00 |
PERIMETER_BOT_ZN_2 | 18-JUN-10:42 | 0.00 | 0.00 | 0.00 | -11930.65 | 0.00 | 0.00 | 16.31 | 25.34 | 317.77 | 5825.56 | 0.00 | 0.00 | 5791.54 | 0.00 | -0.00 | 0.00 | -45.87 | 0.00 |
PERIMETER_BOT_ZN_1 | 22-OCT-13:21 | 0.00 | 0.00 | 0.00 | -17017.29 | 0.00 | 0.00 | 23.07 | 40.03 | 501.96 | 18516.84 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -173.92 | -1890.68 |
PERIMETER_BOT_ZN_4 | 03-SEP-17:11 | 0.00 | 0.00 | 0.00 | -14051.40 | 0.00 | 0.00 | 0.00 | 25.34 | 317.76 | 10520.68 | 0.00 | 0.00 | 3304.12 | 0.00 | -0.00 | 0.00 | -116.50 | 0.00 |
PERIMETER_MID_ZN_3 | 23-JUL-16:01 | 0.00 | 0.00 | 0.00 | -9612.59 | 0.00 | 0.00 | 28.29 | 40.03 | 501.96 | 3017.11 | 0.00 | 104.84 | 5920.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 23-JUL-09:21 | 0.00 | 0.00 | 0.00 | -15939.02 | 0.00 | 0.00 | 13.48 | 25.34 | 317.77 | 10591.06 | 0.00 | 0.00 | 5033.76 | 0.00 | -0.00 | 0.00 | -42.38 | 0.00 |
PERIMETER_MID_ZN_1 | 23-JUL-12:02 | 0.00 | 0.00 | 0.00 | -18689.61 | 0.00 | 0.00 | 23.43 | 40.03 | 501.96 | 12621.17 | 0.00 | 12.43 | 5490.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 16-JUL-16:41 | 0.00 | 0.00 | 0.00 | -16931.82 | 0.00 | 0.00 | 12.56 | 25.34 | 317.76 | 11628.12 | 0.00 | 0.00 | 5247.98 | 0.00 | -0.00 | 0.00 | -299.93 | 0.00 |
TOPFLOOR_PLENUM | 30-JUN-14:50 | 0.00 | -11212.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.52 | 11048.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 24-JUL-06:15 | 0.00 | -5794.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5872.66 | 0.00 | -0.00 | 0.00 | -77.84 | 0.00 |
FIRSTFLOOR_PLENUM | 30-JUN-12:08 | 0.00 | -6371.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.49 | 6288.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-06:03 | 0.00 | -7392.42 | 0.00 | -173323.56 | 0.00 | 0.00 | 3543.77 | 7896.02 | 21853.28 | 35113.15 | 0.00 | 0.00 | 119005.34 | 0.00 | 0.00 | 0.00 | -6695.58 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 23509.57 | 0.00 | 0.00 | 0.00 | 0.00 | 615.87 | 5138.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29263.90 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 29089.89 | 0.00 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -32880.62 |
CORE_TOP | 09-JAN-01:21 | 0.00 | 0.00 | 32012.43 | 0.00 | 0.00 | 0.00 | 0.00 | 307.97 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -35495.27 |
PERIMETER_TOP_ZN_3 | 09-JAN-01:21 | 0.00 | 0.00 | 11774.71 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3762.92 | 0.00 | -977.54 | -7768.46 |
PERIMETER_TOP_ZN_2 | 09-JAN-01:21 | 0.00 | 0.00 | 13587.62 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2507.60 | 0.00 | -659.51 | -10885.30 |
PERIMETER_TOP_ZN_1 | 09-JAN-01:21 | 0.00 | 0.00 | 17917.71 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3853.67 | 0.00 | -988.70 | -13809.55 |
PERIMETER_TOP_ZN_4 | 09-JAN-01:21 | 0.00 | 0.00 | 15009.83 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2559.27 | 0.00 | -661.34 | -12254.01 |
PERIMETER_BOT_ZN_3 | 01-JAN-08:61 | 0.00 | 0.00 | 8307.62 | 0.00 | 0.00 | 0.00 | 60.50 | 64.92 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3438.03 | 0.00 | -911.33 | -4585.65 |
PERIMETER_BOT_ZN_2 | 01-JAN-08:61 | 0.00 | 0.00 | 10495.62 | 0.00 | 0.00 | 0.00 | 38.30 | 41.10 | 317.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2297.34 | 0.00 | -615.19 | -7980.25 |
PERIMETER_BOT_ZN_1 | 06-JAN-07:10 | 0.00 | 0.00 | 23285.78 | 0.00 | 0.00 | 0.00 | 225.67 | 389.51 | 669.28 | 0.00 | 0.00 | 0.00 | 28173.76 | 0.00 | -4201.41 | 0.00 | -48542.59 | 0.00 |
PERIMETER_BOT_ZN_4 | 01-JAN-08:61 | 0.00 | 0.00 | 11397.54 | 0.00 | 0.00 | 0.00 | 38.31 | 41.10 | 317.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2344.06 | 0.00 | -616.28 | -8834.36 |
PERIMETER_MID_ZN_3 | 09-JAN-01:21 | 0.00 | 0.00 | 9338.71 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3854.38 | 0.00 | -831.56 | -5386.98 |
PERIMETER_MID_ZN_2 | 09-JAN-01:21 | 0.00 | 0.00 | 12789.84 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2568.15 | 0.00 | -561.72 | -10124.77 |
PERIMETER_MID_ZN_1 | 09-JAN-01:21 | 0.00 | 0.00 | 15908.54 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3945.62 | 0.00 | -841.56 | -11855.56 |
PERIMETER_MID_ZN_4 | 09-JAN-01:21 | 0.00 | 0.00 | 12918.15 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2618.72 | 0.00 | -561.77 | -10202.44 |
TOPFLOOR_PLENUM | 09-JAN-06:07 | 20609.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -396.39 | -20213.46 |
MIDFLOOR_PLENUM | 26-DEC-07:04 | 12257.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -335.43 | -11922.39 |
FIRSTFLOOR_PLENUM | 02-JAN-07:01 | 10524.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -194.74 | -10329.56 |
Total Facility | 09-JAN-06:01 | 29363.43 | 0.00 | 223823.08 | 0.00 | 0.00 | 0.00 | 2653.82 | 3119.77 | 18045.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -39972.63 | 0.00 | -13662.82 | -223370.63 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.9356 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.2413 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.6108 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6828 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.9904 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.2866 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.9678 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4461 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.8054 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4980 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.9952 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5734 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9464 | 2.9464 | 0.7926 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1578 | 2.1578 | 0.7682 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2389 | 2.2389 | 0.7926 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7454 | 0.7454 | 0.1796 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8771 | 0.8771 | 0.1754 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1555 | 1.1555 | 0.2311 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9734 | 0.9734 | 0.1947 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5569 | 0.5569 | 0.1671 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7179 | 0.7179 | 0.1436 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9325 | 0.9325 | 0.1865 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7819 | 0.7819 | 0.1564 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6134 | 0.6134 | 0.1620 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8665 | 0.8665 | 0.1733 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0670 | 1.0670 | 0.2134 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9060 | 0.9060 | 0.1812 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.9356 | 5.2413 | 5.9356 | 1.4461 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.6108 | 4.6828 | 5.6108 | 1.4980 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.9904 | 5.2866 | 5.9904 | 1.5734 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4732 | 1.4732 | 0.7926 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0789 | 1.0789 | 0.7682 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1195 | 1.1195 | 0.7926 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3727 | 0.3727 | 0.1796 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4386 | 0.4386 | 0.1754 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5778 | 0.5778 | 0.2311 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4867 | 0.4867 | 0.1947 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2784 | 0.2784 | 0.1671 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3590 | 0.3590 | 0.1436 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4663 | 0.4663 | 0.1865 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3909 | 0.3909 | 0.1564 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3067 | 0.3067 | 0.1620 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4333 | 0.4333 | 0.1733 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5335 | 0.5335 | 0.2134 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4530 | 0.4530 | 0.1812 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.9678 | 1.4461 | 1.4461 | 1.4461 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.8054 | 1.4980 | 1.4980 | 1.4980 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.9952 | 1.5734 | 1.5734 | 1.5734 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 797.17 |
Number of hours cooling loads not met | 80.67 |
Number of hours not met | 877.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 453.73 | 226564.56 | 101.56 | 183919.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 118.29 | 80445.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 281.09 | 28079.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 72.02 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 641.30 | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 12.98 | 928.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 101.29 | 35017.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 24.00 | 2722.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 120.38 | 13170.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 762.04 | 1825.47 |
Natural Gas | 0.00 | 221.94 |
Additional | 0.00 | 0.00 |
Total | 762.04 | 2047.41 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 56.42 |
Space Heating | 91.07 |
Space Cooling | 23.74 |
Fans (All) | 20.33 |
Service Water Heating | 0.00 |
Receptacle Equipment | 152.95 |
Miscellaneous (All) | 366.40 |
Subtotal | 366.40 |
Natural Gas [MJ/m2] | |
Space Heating | 20.38 |
Service Water Heating | 24.16 |
Miscellaneous (All) | 44.55 |
Subtotal | 44.55 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.73 |
Space Heating | 27.12 |
Space Cooling | 5.78 |
Fans (All) | 4.95 |
Service Water Heating | 5.88 |
Receptacle Equipment | 37.22 |
Miscellaneous | 5.32 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2429. | 8760. |
BLDG_EQUIP_SCH | 4487. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8684.83 | 75.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8747.00 | 13.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8747.50 | 12.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8716.67 | 43.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8718.33 | 41.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8699.67 | 60.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8729.00 | 31.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8734.83 | 25.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8698.00 | 62.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8748.33 | 11.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8713.33 | 46.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8712.83 | 47.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8692.50 | 67.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8717.50 | 42.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8684.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 75.17 | 0.00 | 0.00 | 0.00 |
Average | 8727.67 | 32.33 | 0.00 | 0.00 | 0.00 |
Sum | 157098.00 | 582.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128279.33 | 24.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 24.67 | 0.00 | 0.00 | 0.00 |
Average | 34141.96 | 1.37 | 0.00 | 0.00 | 0.00 |
Sum | 614555.33 | 24.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8288.83 | 471.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8403.67 | 356.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8495.83 | 264.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8490.00 | 270.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8503.50 | 256.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8463.33 | 296.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8447.67 | 312.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8533.00 | 227.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8451.17 | 308.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8376.50 | 383.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8395.67 | 364.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8438.83 | 321.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8453.33 | 306.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8414.67 | 345.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8401.33 | 358.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8267.33 | 492.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8462.17 | 297.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8448.33 | 311.67 | 0.00 | 0.00 | 0.00 |
Min | 8267.33 | 227.00 | 0.00 | 0.00 | 0.00 |
Max | 8533.00 | 492.67 | 0.00 | 0.00 | 0.00 |
Average | 8429.73 | 330.27 | 0.00 | 0.00 | 0.00 |
Sum | 151735.17 | 5944.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127932.67 | 371.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128073.33 | 230.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128111.33 | 192.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24889.50 | 19.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14011.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24896.50 | 12.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14011.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24883.17 | 25.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14009.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24583.17 | 325.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14009.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24877.50 | 31.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10131.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24885.00 | 24.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14010.00 | 6.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128111.33 | 371.33 | 0.00 | 0.00 | 0.00 |
Average | 34072.98 | 70.35 | 0.00 | 0.00 | 0.00 |
Sum | 613313.67 | 1266.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.839387E+10 | 7561.02 | 27-JAN-16:50 | -16.3 | -17.2 | 0.164418E+10 | 2493.85 | 27-JAN-14:09 | -16.3 | -17.2 |
February | 0.872021E+10 | 9662.80 | 10-FEB-17:00 | -12.8 | -14.1 | 0.161361E+10 | 2606.66 | 10-FEB-14:09 | -12.8 | -14.1 |
March | 0.115900E+11 | 16588.84 | 30-MAR-07:06 | -2.7 | -3.2 | 0.204587E+10 | 2608.73 | 30-MAR-09:20 | -1.5 | -2.2 |
April | 0.146174E+11 | 40458.43 | 24-APR-05:02 | 4.40 | 3.41 | 0.189508E+10 | 2608.95 | 26-APR-09:20 | 0.00 | -0.1 |
May | 0.226121E+11 | 45339.22 | 30-MAY-04:02 | 10.60 | 8.25 | 0.207626E+10 | 2608.10 | 01-MAY-09:20 | 10.60 | 8.25 |
June | 0.256200E+11 | 43433.91 | 26-JUN-04:03 | 16.78 | 15.67 | 0.206966E+10 | 2606.68 | 27-JUN-13:09 | 28.58 | 20.77 |
July | 0.265524E+11 | 45378.72 | 05-JUL-04:02 | 19.90 | 18.81 | 0.192693E+10 | 2745.39 | 05-JUL-10:00 | 24.40 | 23.25 |
August | 0.276330E+11 | 43989.65 | 28-AUG-04:03 | 13.90 | 12.90 | 0.215899E+10 | 2606.69 | 03-AUG-13:00 | 13.90 | 12.90 |
September | 0.217748E+11 | 43510.56 | 05-SEP-04:03 | 6.52 | 6.03 | 0.191649E+10 | 2606.68 | 11-SEP-13:09 | 18.90 | 14.33 |
October | 0.157640E+11 | 40962.38 | 23-OCT-05:02 | 5.60 | 4.10 | 0.197716E+10 | 2608.82 | 06-OCT-09:20 | 5.60 | 4.10 |
November | 0.104359E+11 | 15681.83 | 02-NOV-07:07 | 3.90 | 2.94 | 0.188377E+10 | 2608.53 | 02-NOV-09:20 | 2.80 | 2.41 |
December | 0.920408E+10 | 8602.58 | 01-DEC-16:20 | -19.0 | -19.7 | 0.164239E+10 | 2606.25 | 01-DEC-14:09 | -19.0 | -19.7 |
Annual Sum or Average | 0.202918E+12 | 0.228504E+11 | ||||||||
Minimum of Months | 0.839387E+10 | 7561.02 | -19.0 | -19.7 | 0.161361E+10 | 2493.85 | -19.0 | -19.7 | ||
Maximum of Months | 0.276330E+11 | 45378.72 | 19.90 | 18.81 | 0.215899E+10 | 2745.39 | 28.58 | 23.25 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 583590.01 | 537.51 | 04-FEB-17:25 | 6.10 | 1.54 | 0.00 | 0.00 | 01-FEB-00:10 | 6.10 | 1.54 |
March | 73311555.74 | 1539.02 | 31-MAR-16:10 | 8.90 | 3.69 | 0.00 | 0.00 | 01-MAR-00:10 | 8.90 | 3.69 |
April | 0.898820E+09 | 4804.42 | 13-APR-15:00 | 20.00 | 8.11 | 0.00 | 0.00 | 01-APR-00:10 | 20.00 | 8.11 |
May | 0.330703E+10 | 9848.55 | 18-MAY-14:30 | 28.70 | 16.68 | 0.00 | 0.00 | 01-MAY-00:10 | 28.70 | 16.68 |
June | 0.498925E+10 | 11212.19 | 30-JUN-14:50 | 32.02 | 24.38 | 0.00 | 0.00 | 01-JUN-00:10 | 32.02 | 24.38 |
July | 0.583744E+10 | 10586.36 | 24-JUL-14:50 | 29.40 | 19.36 | 0.00 | 0.00 | 01-JUL-00:10 | 29.40 | 19.36 |
August | 0.418360E+10 | 9703.25 | 08-AUG-15:10 | 30.60 | 23.30 | 0.00 | 0.00 | 01-AUG-00:10 | 30.60 | 23.30 |
September | 0.170775E+10 | 8270.28 | 01-SEP-15:50 | 26.10 | 17.67 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.67 |
October | 0.343826E+09 | 3475.96 | 20-OCT-14:30 | 18.90 | 10.07 | 0.00 | 0.00 | 01-OCT-00:10 | 18.90 | 10.07 |
November | 11195492.80 | 993.22 | 01-NOV-16:30 | 17.25 | 13.03 | 0.00 | 0.00 | 01-NOV-00:10 | 17.25 | 13.03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.213528E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -21.9 | -22.1 | 0.00 | 0.00 | -21.9 | -22.1 | ||
Maximum of Months | 0.583744E+10 | 11212.19 | 32.02 | 24.38 | 0.00 | 0.00 | 32.02 | 24.38 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7196721.73 | 2759.74 | 28-JAN-05:11 | -26.7 | -26.9 | 0.00 | 0.00 | 01-JAN-00:10 | -26.7 | -26.9 |
February | 3913484.39 | 3064.21 | 25-FEB-05:01 | -29.0 | -29.1 | 0.00 | 0.00 | 01-FEB-00:10 | -29.0 | -29.1 |
March | 28877704.62 | 2261.03 | 16-MAR-04:01 | -26.3 | -26.5 | 0.00 | 0.00 | 01-MAR-00:10 | -26.3 | -26.5 |
April | 0.287250E+09 | 2328.77 | 26-APR-06:01 | 1.10 | 0.37 | 0.00 | 0.00 | 01-APR-00:10 | 1.10 | 0.37 |
May | 0.179162E+10 | 4383.25 | 18-MAY-15:50 | 28.57 | 16.37 | 0.00 | 0.00 | 01-MAY-00:10 | 28.57 | 16.37 |
June | 0.307880E+10 | 5336.82 | 30-JUN-16:00 | 31.70 | 24.66 | 0.00 | 0.00 | 01-JUN-00:10 | 31.70 | 24.66 |
July | 0.379119E+10 | 5795.27 | 24-JUL-06:15 | 19.07 | 17.12 | 0.00 | 0.00 | 01-JUL-00:10 | 19.07 | 17.12 |
August | 0.288706E+10 | 4476.27 | 08-AUG-16:00 | 30.60 | 22.99 | 0.00 | 0.00 | 01-AUG-00:10 | 30.60 | 22.99 |
September | 0.113904E+10 | 4335.98 | 01-SEP-15:50 | 26.10 | 17.67 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.67 |
October | 0.206602E+09 | 2516.77 | 25-OCT-06:01 | -4.2 | -4.4 | 0.00 | 0.00 | 01-OCT-00:10 | -4.2 | -4.4 |
November | 7972709.42 | 2106.42 | 29-NOV-05:01 | -19.6 | -19.9 | 0.00 | 0.00 | 01-NOV-00:10 | -19.6 | -19.9 |
December | 6110451.11 | 2193.54 | 08-DEC-05:01 | -20.3 | -20.7 | 0.00 | 0.00 | 01-DEC-00:10 | -20.3 | -20.7 |
Annual Sum or Average | 0.132356E+11 | 0.00 | ||||||||
Minimum of Months | 3913484.39 | 2106.42 | -29.0 | -29.1 | 0.00 | 0.00 | -29.0 | -29.1 | ||
Maximum of Months | 0.379119E+10 | 5795.27 | 31.70 | 24.66 | 0.00 | 0.00 | 31.70 | 24.66 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202898E+09 | 5046.28 | 26-JAN-07:10 | -33.1 | -33.2 | 0.00 | 0.00 | 01-JAN-00:10 | -33.1 | -33.2 |
February | 0.191816E+09 | 4841.14 | 17-FEB-07:10 | -30.7 | -30.9 | 0.00 | 0.00 | 01-FEB-00:10 | -30.7 | -30.9 |
March | 0.254233E+09 | 3989.17 | 23-MAR-06:10 | -18.8 | -19.1 | 0.00 | 0.00 | 01-MAR-00:10 | -18.8 | -19.1 |
April | 0.671126E+09 | 3178.03 | 05-APR-06:10 | -13.5 | -14.0 | 0.00 | 0.00 | 01-APR-00:10 | -13.5 | -14.0 |
May | 0.240431E+10 | 4600.35 | 18-MAY-16:00 | 28.50 | 16.32 | 0.00 | 0.00 | 01-MAY-00:10 | 28.50 | 16.32 |
June | 0.358178E+10 | 6372.85 | 30-JUN-12:08 | 31.70 | 24.14 | 0.00 | 0.00 | 01-JUN-00:10 | 31.70 | 24.14 |
July | 0.439900E+10 | 6209.06 | 24-JUL-12:10 | 28.40 | 19.78 | 0.00 | 0.00 | 01-JUL-00:10 | 28.40 | 19.78 |
August | 0.372824E+10 | 4877.72 | 08-AUG-16:00 | 30.60 | 22.99 | 0.00 | 0.00 | 01-AUG-00:10 | 30.60 | 22.99 |
September | 0.192479E+10 | 4563.88 | 01-SEP-16:00 | 26.10 | 17.64 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.64 |
October | 0.512631E+09 | 3001.23 | 25-OCT-06:08 | -4.2 | -4.4 | 0.00 | 0.00 | 01-OCT-00:10 | -4.2 | -4.4 |
November | 0.102131E+09 | 2646.03 | 10-NOV-07:10 | -8.4 | -9.4 | 0.00 | 0.00 | 01-NOV-00:10 | -8.4 | -9.4 |
December | 0.163474E+09 | 4103.10 | 01-DEC-17:10 | -19.9 | -20.4 | 0.00 | 0.00 | 01-DEC-00:10 | -19.9 | -20.4 |
Annual Sum or Average | 0.181364E+11 | 0.00 | ||||||||
Minimum of Months | 0.102131E+09 | 2646.03 | -33.1 | -33.2 | 0.00 | 0.00 | -33.1 | -33.2 | ||
Maximum of Months | 0.439900E+10 | 6372.85 | 31.70 | 24.14 | 0.00 | 0.00 | 31.70 | 24.14 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.380185E+10 | 6005.75 | 27-JAN-16:47 | -16.3 | -17.2 | 0.147829E+10 | 2148.10 | 27-JAN-14:00 | -16.3 | -17.2 |
February | 0.470056E+10 | 6521.17 | 08-FEB-16:40 | 3.67 | -1.2 | 0.138132E+10 | 2261.93 | 08-FEB-16:00 | 3.30 | -1.3 |
March | 0.742373E+10 | 7371.38 | 29-MAR-16:00 | 5.00 | 1.34 | 0.176364E+10 | 2512.51 | 29-MAR-13:00 | 5.00 | 1.34 |
April | 0.943673E+10 | 12037.48 | 14-APR-16:00 | 15.00 | 6.77 | 0.175340E+10 | 2606.61 | 13-APR-09:39 | 15.00 | 6.77 |
May | 0.152066E+11 | 32302.81 | 30-MAY-04:02 | 10.60 | 8.25 | 0.205345E+10 | 2606.71 | 24-MAY-09:09 | 10.60 | 8.25 |
June | 0.178070E+11 | 32144.94 | 26-JUN-04:03 | 16.78 | 15.67 | 0.206279E+10 | 2606.65 | 06-JUN-09:09 | 16.78 | 15.67 |
July | 0.188690E+11 | 33014.05 | 05-JUL-04:02 | 19.90 | 18.81 | 0.192240E+10 | 2704.00 | 05-JUL-10:00 | 24.40 | 23.25 |
August | 0.185890E+11 | 31983.87 | 28-AUG-04:03 | 13.90 | 12.90 | 0.215296E+10 | 2606.66 | 10-AUG-13:00 | 13.90 | 12.90 |
September | 0.134058E+11 | 30990.68 | 01-SEP-05:03 | 15.68 | 15.63 | 0.189432E+10 | 2606.66 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.937292E+10 | 12098.32 | 20-OCT-16:00 | 18.30 | 9.93 | 0.181679E+10 | 2606.63 | 20-OCT-09:09 | 18.30 | 9.93 |
November | 0.625128E+10 | 7083.51 | 17-NOV-16:20 | 8.90 | 2.59 | 0.159532E+10 | 2449.13 | 17-NOV-14:00 | 8.90 | 2.59 |
December | 0.418986E+10 | 5960.53 | 01-DEC-16:20 | -19.0 | -19.7 | 0.143783E+10 | 2192.97 | 01-DEC-14:00 | -19.0 | -19.7 |
Annual Sum or Average | 0.129054E+12 | 0.213125E+11 | ||||||||
Minimum of Months | 0.380185E+10 | 5960.53 | -19.0 | -19.7 | 0.138132E+10 | 2148.10 | -19.0 | -19.7 | ||
Maximum of Months | 0.188690E+11 | 33014.05 | 19.90 | 18.81 | 0.215296E+10 | 2704.00 | 24.40 | 23.25 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206295E+10 | 5718.55 | 27-JAN-16:00 | -14.4 | -15.6 | 0.145458E+10 | 2036.44 | 27-JAN-14:00 | -14.4 | -15.6 |
February | 0.295996E+10 | 6476.92 | 08-FEB-17:00 | 3.30 | -1.3 | 0.133757E+10 | 2213.49 | 08-FEB-16:00 | 3.30 | -1.3 |
March | 0.528106E+10 | 7290.37 | 29-MAR-16:00 | 5.00 | 1.34 | 0.166680E+10 | 2424.38 | 29-MAR-13:00 | 5.00 | 1.34 |
April | 0.824549E+10 | 11650.82 | 14-APR-16:00 | 15.00 | 6.77 | 0.166004E+10 | 2606.60 | 19-APR-13:00 | 6.70 | 0.87 |
May | 0.143852E+11 | 31902.83 | 26-MAY-05:03 | 19.40 | 15.69 | 0.202167E+10 | 2606.72 | 24-MAY-09:09 | 19.40 | 15.69 |
June | 0.175541E+11 | 32134.78 | 19-JUN-05:03 | 17.80 | 16.77 | 0.205323E+10 | 2606.67 | 26-JUN-13:20 | 25.97 | 17.06 |
July | 0.185614E+11 | 34008.35 | 24-JUL-04:02 | 18.22 | 16.14 | 0.191630E+10 | 2649.90 | 05-JUL-10:00 | 18.22 | 16.14 |
August | 0.175722E+11 | 32091.69 | 09-AUG-05:03 | 18.40 | 17.30 | 0.214253E+10 | 2606.65 | 10-AUG-13:00 | 19.40 | 16.96 |
September | 0.118575E+11 | 21918.35 | 01-SEP-05:03 | 15.68 | 15.63 | 0.183789E+10 | 2606.62 | 11-SEP-13:09 | 18.90 | 14.33 |
October | 0.762394E+10 | 11367.86 | 20-OCT-16:00 | 18.30 | 9.93 | 0.167684E+10 | 2606.47 | 20-OCT-13:00 | 18.30 | 9.93 |
November | 0.440063E+10 | 6843.85 | 17-NOV-17:00 | 6.70 | 1.30 | 0.150671E+10 | 2327.32 | 17-NOV-14:00 | 6.70 | 1.30 |
December | 0.222038E+10 | 5547.90 | 28-DEC-15:50 | -2.0 | -3.9 | 0.140280E+10 | 2041.62 | 28-DEC-14:00 | -2.0 | -3.9 |
Annual Sum or Average | 0.112725E+12 | 0.206769E+11 | ||||||||
Minimum of Months | 0.206295E+10 | 5547.90 | -14.4 | -15.6 | 0.133757E+10 | 2036.44 | -14.4 | -15.6 | ||
Maximum of Months | 0.185614E+11 | 34008.35 | 19.40 | 17.30 | 0.214253E+10 | 2649.90 | 25.97 | 17.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7587157.47 | 1038.33 | 14-JAN-17:01 | -12.3 | -12.9 | 0.300650E+09 | 406.69 | 04-JAN-14:39 | -12.3 | -12.9 |
February | 35017493.22 | 1050.61 | 11-FEB-17:02 | -7.1 | -8.6 | 0.275254E+09 | 406.68 | 14-FEB-10:30 | -23.9 | -24.3 |
March | 0.260319E+09 | 1427.61 | 31-MAR-16:00 | 8.90 | 3.77 | 0.334397E+09 | 457.45 | 31-MAR-15:00 | 8.90 | 3.77 |
April | 0.116999E+10 | 2685.98 | 18-APR-14:50 | 15.47 | 9.11 | 0.323774E+09 | 549.48 | 18-APR-13:00 | 15.47 | 9.11 |
May | 0.365269E+10 | 5968.66 | 18-MAY-15:00 | 28.90 | 16.60 | 0.416033E+09 | 549.51 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.515972E+10 | 7347.92 | 29-JUN-15:00 | 34.40 | 24.01 | 0.431654E+09 | 549.52 | 26-JUN-13:20 | 34.40 | 24.01 |
July | 0.554271E+10 | 9743.43 | 23-JUL-15:32 | 30.00 | 22.71 | 0.403694E+09 | 559.01 | 05-JUL-13:09 | 30.00 | 22.71 |
August | 0.451851E+10 | 6197.09 | 08-AUG-15:40 | 30.60 | 23.11 | 0.447090E+09 | 549.50 | 10-AUG-13:00 | 19.40 | 16.96 |
September | 0.245121E+10 | 5178.66 | 01-SEP-15:40 | 26.10 | 17.70 | 0.367409E+09 | 549.49 | 11-SEP-13:00 | 18.90 | 14.76 |
October | 0.973749E+09 | 2085.24 | 22-OCT-14:42 | 19.40 | 12.77 | 0.324284E+09 | 538.45 | 20-OCT-13:00 | 19.40 | 12.77 |
November | 0.171549E+09 | 1427.13 | 01-NOV-15:40 | 17.97 | 13.32 | 0.302981E+09 | 460.53 | 01-NOV-13:00 | 17.97 | 13.32 |
December | 8820339.05 | 1048.03 | 30-DEC-17:02 | -3.3 | -3.3 | 0.291273E+09 | 406.68 | 21-DEC-10:00 | -3.3 | -3.3 |
Annual Sum or Average | 0.239519E+11 | 0.421849E+10 | ||||||||
Minimum of Months | 7587157.47 | 1038.33 | -12.3 | -12.9 | 0.275254E+09 | 406.68 | -23.9 | -24.3 | ||
Maximum of Months | 0.554271E+10 | 9743.43 | 34.40 | 24.01 | 0.447090E+09 | 559.01 | 34.40 | 24.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8822392.40 | 1005.29 | 14-JAN-17:01 | -12.3 | -12.9 | 0.192642E+09 | 257.48 | 04-JAN-14:30 | -12.3 | -12.9 |
February | 0.127472E+09 | 1336.44 | 28-FEB-10:25 | -4.4 | -6.4 | 0.175492E+09 | 289.49 | 28-FEB-10:39 | -3.9 | -5.9 |
March | 0.568584E+09 | 2332.28 | 31-MAR-09:45 | 1.42 | -1.1 | 0.220808E+09 | 347.88 | 20-MAR-09:30 | 1.42 | -1.1 |
April | 0.189210E+10 | 6484.88 | 18-APR-09:30 | 18.05 | 10.95 | 0.224109E+09 | 348.47 | 19-APR-09:50 | 2.88 | -2.5 |
May | 0.396909E+10 | 11436.22 | 21-MAY-09:02 | 12.52 | 7.56 | 0.268592E+09 | 348.37 | 01-MAY-09:30 | 12.52 | 7.56 |
June | 0.547625E+10 | 15057.57 | 25-JUN-08:12 | 24.27 | 20.87 | 0.273648E+09 | 348.52 | 27-JUN-09:00 | 26.10 | 19.03 |
July | 0.595040E+10 | 14725.19 | 23-JUL-09:32 | 26.13 | 22.79 | 0.255796E+09 | 348.51 | 31-JUL-09:00 | 19.40 | 13.46 |
August | 0.464659E+10 | 11652.45 | 20-AUG-09:32 | 22.07 | 15.84 | 0.281851E+09 | 347.89 | 04-AUG-09:00 | 22.07 | 15.84 |
September | 0.282096E+10 | 8339.84 | 01-SEP-09:10 | 20.28 | 17.76 | 0.233750E+09 | 347.88 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.101165E+10 | 3711.20 | 19-OCT-09:30 | 12.50 | 9.01 | 0.208619E+09 | 347.88 | 18-OCT-09:30 | 12.50 | 9.01 |
November | 0.241044E+09 | 1369.54 | 16-NOV-10:05 | 2.15 | -0.3 | 0.192509E+09 | 293.82 | 16-NOV-10:09 | 2.15 | -0.3 |
December | 13901363.46 | 1013.02 | 16-DEC-17:02 | -5.9 | -6.6 | 0.185822E+09 | 257.47 | 18-DEC-14:30 | -22.8 | -23.5 |
Annual Sum or Average | 0.267269E+11 | 0.271364E+10 | ||||||||
Minimum of Months | 8822392.40 | 1005.29 | -12.3 | -12.9 | 0.175492E+09 | 257.47 | -22.8 | -23.5 | ||
Maximum of Months | 0.595040E+10 | 15057.57 | 26.13 | 22.79 | 0.281851E+09 | 348.52 | 26.10 | 19.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.670938E+09 | 6080.13 | 27-JAN-14:00 | -14.4 | -15.6 | 0.321879E+09 | 549.49 | 25-JAN-14:00 | -14.4 | -15.6 |
February | 0.126457E+10 | 8823.17 | 28-FEB-14:20 | 4.63 | 0.62 | 0.304207E+09 | 549.96 | 28-FEB-14:20 | 4.63 | 0.62 |
March | 0.174307E+10 | 9580.21 | 31-MAR-14:00 | 8.30 | 3.10 | 0.370238E+09 | 550.25 | 20-MAR-13:09 | 8.30 | 3.10 |
April | 0.334820E+10 | 13148.07 | 23-APR-13:43 | 24.13 | 15.95 | 0.352486E+09 | 549.50 | 19-APR-13:00 | 24.13 | 15.95 |
May | 0.574260E+10 | 12479.53 | 18-MAY-13:10 | 28.25 | 16.75 | 0.418079E+09 | 550.33 | 17-MAY-13:00 | 28.25 | 16.75 |
June | 0.682327E+10 | 16648.94 | 18-JUN-14:13 | 26.50 | 18.78 | 0.428236E+09 | 550.02 | 28-JUN-13:00 | 30.00 | 21.52 |
July | 0.775512E+10 | 19296.89 | 23-JUL-12:52 | 30.00 | 22.84 | 0.401986E+09 | 569.95 | 05-JUL-13:09 | 30.00 | 22.84 |
August | 0.741456E+10 | 19255.96 | 27-AUG-14:42 | 23.12 | 18.42 | 0.445438E+09 | 550.29 | 22-AUG-13:50 | 23.12 | 18.42 |
September | 0.524982E+10 | 19149.49 | 04-SEP-12:52 | 16.10 | 9.74 | 0.373588E+09 | 552.01 | 01-SEP-13:20 | 16.10 | 9.74 |
October | 0.273053E+10 | 21292.35 | 22-OCT-13:21 | 18.85 | 12.94 | 0.344172E+09 | 549.72 | 20-OCT-13:50 | 18.85 | 12.94 |
November | 0.111959E+10 | 8030.54 | 17-NOV-13:15 | 10.20 | 3.29 | 0.326016E+09 | 550.01 | 07-NOV-14:09 | 10.20 | 3.29 |
December | 0.387353E+09 | 3247.63 | 02-DEC-13:30 | -18.6 | -19.3 | 0.302808E+09 | 549.49 | 20-DEC-14:00 | -18.9 | -19.7 |
Annual Sum or Average | 0.442496E+11 | 0.438913E+10 | ||||||||
Minimum of Months | 0.387353E+09 | 3247.63 | -18.6 | -19.3 | 0.302808E+09 | 549.49 | -18.9 | -19.7 | ||
Maximum of Months | 0.775512E+10 | 21292.35 | 30.00 | 22.84 | 0.445438E+09 | 569.95 | 30.00 | 22.84 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 69851491.71 | 1499.64 | 27-JAN-16:00 | -14.4 | -15.6 | 0.192950E+09 | 281.38 | 27-JAN-16:10 | -14.8 | -15.9 |
February | 0.234977E+09 | 2166.54 | 08-FEB-16:20 | 4.03 | -1.1 | 0.178032E+09 | 339.02 | 08-FEB-16:40 | 3.67 | -1.2 |
March | 0.652390E+09 | 4659.56 | 31-MAR-16:00 | 8.90 | 3.77 | 0.217170E+09 | 338.94 | 29-MAR-15:00 | 8.90 | 3.77 |
April | 0.190762E+10 | 16348.02 | 23-APR-16:22 | 26.40 | 16.81 | 0.206419E+09 | 347.84 | 18-APR-13:00 | 26.40 | 16.81 |
May | 0.432627E+10 | 14183.46 | 14-MAY-16:42 | 20.00 | 8.40 | 0.257809E+09 | 347.86 | 23-MAY-13:00 | 25.80 | 17.04 |
June | 0.517902E+10 | 16310.49 | 17-JUN-17:42 | 23.90 | 13.28 | 0.268431E+09 | 347.87 | 26-JUN-13:20 | 25.97 | 17.06 |
July | 0.567940E+10 | 16577.10 | 16-JUL-16:52 | 21.10 | 15.60 | 0.253139E+09 | 347.90 | 05-JUL-13:50 | 21.10 | 15.60 |
August | 0.481862E+10 | 16784.17 | 27-AUG-17:22 | 22.80 | 19.07 | 0.276972E+09 | 347.86 | 10-AUG-13:00 | 22.80 | 19.07 |
September | 0.289698E+10 | 13493.52 | 03-SEP-17:22 | 21.15 | 15.79 | 0.224363E+09 | 347.85 | 11-SEP-13:00 | 18.90 | 14.76 |
October | 0.116499E+10 | 5422.16 | 19-OCT-16:00 | 21.70 | 13.55 | 0.206209E+09 | 347.82 | 20-OCT-13:00 | 18.90 | 10.07 |
November | 0.253180E+09 | 1743.60 | 17-NOV-15:50 | 10.10 | 3.24 | 0.193377E+09 | 316.17 | 17-NOV-15:00 | 10.00 | 3.20 |
December | 23362049.28 | 1132.92 | 16-DEC-17:02 | -5.9 | -6.6 | 0.185815E+09 | 257.46 | 21-DEC-10:39 | -24.3 | -24.7 |
Annual Sum or Average | 0.272066E+11 | 0.266069E+10 | ||||||||
Minimum of Months | 23362049.28 | 1132.92 | -14.4 | -15.6 | 0.178032E+09 | 257.46 | -24.3 | -24.7 | ||
Maximum of Months | 0.567940E+10 | 16784.17 | 26.40 | 19.07 | 0.276972E+09 | 347.90 | 26.40 | 19.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8496953.84 | 976.66 | 28-JAN-17:02 | -7.8 | -9.1 | 0.298899E+09 | 406.70 | 04-JAN-14:30 | -7.8 | -9.1 |
February | 16266953.38 | 983.65 | 11-FEB-17:02 | -7.1 | -8.6 | 0.276149E+09 | 406.68 | 14-FEB-10:30 | -23.9 | -24.3 |
March | 0.185564E+09 | 1196.04 | 31-MAR-16:00 | 8.90 | 3.77 | 0.333237E+09 | 430.78 | 31-MAR-13:00 | 8.90 | 3.77 |
April | 0.993502E+09 | 2023.23 | 23-APR-18:32 | 24.07 | 15.29 | 0.314644E+09 | 511.16 | 14-APR-13:09 | 24.07 | 15.29 |
May | 0.270840E+10 | 4126.83 | 26-MAY-13:30 | 22.50 | 17.44 | 0.413425E+09 | 549.51 | 24-MAY-09:09 | 22.50 | 17.44 |
June | 0.400477E+10 | 5586.35 | 29-JUN-15:00 | 34.40 | 24.01 | 0.432197E+09 | 549.50 | 27-JUN-13:09 | 34.40 | 24.01 |
July | 0.477400E+10 | 7211.67 | 24-JUL-06:03 | 18.68 | 16.82 | 0.404558E+09 | 574.65 | 05-JUL-13:09 | 18.68 | 16.82 |
August | 0.430892E+10 | 5153.74 | 09-AUG-15:30 | 27.25 | 21.19 | 0.451862E+09 | 549.50 | 10-AUG-13:00 | 19.40 | 16.96 |
September | 0.261476E+10 | 4345.84 | 01-SEP-15:40 | 26.10 | 17.70 | 0.388381E+09 | 549.50 | 11-SEP-13:09 | 18.90 | 14.33 |
October | 0.152998E+10 | 2027.72 | 22-OCT-14:42 | 19.40 | 12.77 | 0.346464E+09 | 547.20 | 02-OCT-13:00 | 19.40 | 12.77 |
November | 0.398971E+09 | 1372.95 | 01-NOV-15:30 | 18.05 | 13.35 | 0.307404E+09 | 477.38 | 01-NOV-13:00 | 18.05 | 13.35 |
December | 11260899.35 | 987.04 | 30-DEC-17:02 | -3.3 | -3.3 | 0.291447E+09 | 406.69 | 18-DEC-14:30 | -3.3 | -3.3 |
Annual Sum or Average | 0.215549E+11 | 0.425867E+10 | ||||||||
Minimum of Months | 8496953.84 | 976.66 | -7.8 | -9.1 | 0.276149E+09 | 406.68 | -23.9 | -24.3 | ||
Maximum of Months | 0.477400E+10 | 7211.67 | 34.40 | 24.01 | 0.451862E+09 | 574.65 | 34.40 | 24.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8572839.59 | 838.16 | 21-JAN-17:02 | -5.0 | -7.1 | 0.192947E+09 | 257.49 | 04-JAN-14:30 | -5.0 | -7.1 |
February | 92233065.30 | 992.32 | 28-FEB-10:25 | -4.4 | -6.4 | 0.175801E+09 | 272.40 | 28-FEB-10:39 | -3.9 | -5.9 |
March | 0.449079E+09 | 1354.92 | 31-MAR-10:10 | 2.07 | -0.7 | 0.219453E+09 | 336.94 | 31-MAR-09:00 | 2.07 | -0.7 |
April | 0.156347E+10 | 4193.78 | 18-APR-09:40 | 18.13 | 11.06 | 0.224716E+09 | 347.88 | 18-APR-09:00 | 18.30 | 11.28 |
May | 0.315793E+10 | 6330.13 | 18-MAY-09:30 | 24.55 | 16.00 | 0.271476E+09 | 348.15 | 01-MAY-09:20 | 24.55 | 16.00 |
June | 0.461609E+10 | 11931.55 | 18-JUN-10:42 | 24.72 | 17.27 | 0.275021E+09 | 348.03 | 28-JUN-09:30 | 28.05 | 21.71 |
July | 0.538852E+10 | 9342.81 | 31-JUL-06:02 | 16.28 | 14.26 | 0.256646E+09 | 350.09 | 05-JUL-13:09 | 16.28 | 14.26 |
August | 0.449012E+10 | 11557.41 | 13-AUG-10:12 | 20.77 | 14.69 | 0.286845E+09 | 347.88 | 04-AUG-09:00 | 20.77 | 14.69 |
September | 0.291841E+10 | 6200.86 | 01-SEP-09:30 | 20.85 | 17.74 | 0.246652E+09 | 347.88 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.142897E+10 | 2897.53 | 19-OCT-08:35 | 10.37 | 7.57 | 0.223997E+09 | 347.88 | 18-OCT-09:09 | 10.37 | 7.57 |
November | 0.437835E+09 | 1183.84 | 17-NOV-10:10 | 3.87 | 0.38 | 0.196244E+09 | 306.47 | 17-NOV-10:30 | 5.00 | 1.00 |
December | 18916227.90 | 842.74 | 16-DEC-17:02 | -5.9 | -6.6 | 0.186245E+09 | 257.48 | 18-DEC-14:30 | -22.8 | -23.5 |
Annual Sum or Average | 0.245701E+11 | 0.275604E+10 | ||||||||
Minimum of Months | 8572839.59 | 838.16 | -5.9 | -7.1 | 0.175801E+09 | 257.48 | -22.8 | -23.5 | ||
Maximum of Months | 0.538852E+10 | 11931.55 | 24.72 | 17.74 | 0.286845E+09 | 350.09 | 28.05 | 21.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43484905.42 | 1342.14 | 21-JAN-12:00 | -10.0 | -10.7 | 0.251072E+09 | 406.63 | 05-JAN-14:00 | -10.0 | -10.7 |
February | 0.212769E+09 | 1629.47 | 04-FEB-14:40 | 7.60 | 2.46 | 0.248369E+09 | 499.95 | 28-FEB-14:00 | 6.10 | 1.55 |
March | 0.335191E+09 | 2262.40 | 18-MAR-13:30 | -2.0 | -5.7 | 0.313865E+09 | 533.30 | 31-MAR-13:00 | 8.30 | 3.10 |
April | 0.135762E+10 | 10026.85 | 23-APR-15:12 | 25.97 | 16.64 | 0.317706E+09 | 549.51 | 19-APR-13:00 | 25.97 | 16.64 |
May | 0.361385E+10 | 12316.16 | 18-MAY-12:00 | 27.80 | 16.87 | 0.395536E+09 | 549.73 | 18-MAY-13:00 | 28.50 | 16.75 |
June | 0.499964E+10 | 14102.15 | 29-JUN-16:10 | 34.90 | 24.48 | 0.418899E+09 | 599.46 | 30-JUN-12:09 | 31.70 | 24.14 |
July | 0.647583E+10 | 15442.89 | 16-JUL-14:02 | 24.32 | 18.29 | 0.399936E+09 | 569.04 | 05-JUL-13:09 | 24.32 | 18.29 |
August | 0.628336E+10 | 15300.60 | 13-AUG-13:32 | 23.13 | 14.35 | 0.440814E+09 | 549.94 | 22-AUG-13:50 | 24.32 | 16.45 |
September | 0.410249E+10 | 16608.45 | 04-SEP-13:22 | 16.10 | 9.67 | 0.365147E+09 | 549.91 | 07-SEP-13:00 | 23.90 | 14.48 |
October | 0.186209E+10 | 17015.53 | 22-OCT-13:21 | 18.85 | 12.94 | 0.332766E+09 | 549.60 | 20-OCT-13:00 | 18.85 | 12.94 |
November | 0.330589E+09 | 2870.29 | 17-NOV-13:50 | 10.50 | 3.40 | 0.296769E+09 | 549.50 | 17-NOV-14:09 | 10.60 | 3.43 |
December | 0.105460E+09 | 1975.62 | 02-DEC-13:50 | -18.3 | -19.0 | 0.249374E+09 | 406.62 | 05-DEC-10:09 | -0.9 | -0.9 |
Annual Sum or Average | 0.297224E+11 | 0.403026E+10 | ||||||||
Minimum of Months | 43484905.42 | 1342.14 | -18.3 | -19.0 | 0.248369E+09 | 406.62 | -10.0 | -10.7 | ||
Maximum of Months | 0.647583E+10 | 17015.53 | 34.90 | 24.48 | 0.440814E+09 | 599.46 | 31.70 | 24.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50208994.63 | 1151.42 | 27-JAN-16:00 | -14.4 | -15.6 | 0.193255E+09 | 276.50 | 27-JAN-16:10 | -14.8 | -15.9 |
February | 0.152724E+09 | 1463.80 | 08-FEB-16:40 | 3.67 | -1.2 | 0.177427E+09 | 327.06 | 08-FEB-16:49 | 3.48 | -1.2 |
March | 0.480398E+09 | 3039.00 | 28-MAR-17:00 | 7.20 | 3.52 | 0.215624E+09 | 338.67 | 31-MAR-15:00 | 8.90 | 3.77 |
April | 0.149226E+10 | 12998.84 | 23-APR-17:51 | 25.60 | 16.47 | 0.209074E+09 | 347.83 | 18-APR-13:00 | 25.60 | 16.47 |
May | 0.336422E+10 | 13014.10 | 21-MAY-17:32 | 21.83 | 11.10 | 0.264016E+09 | 347.85 | 25-MAY-09:00 | 21.50 | 16.78 |
June | 0.416177E+10 | 12935.66 | 17-JUN-18:22 | 23.05 | 13.03 | 0.272160E+09 | 347.85 | 27-JUN-13:09 | 28.58 | 20.77 |
July | 0.507696E+10 | 13797.57 | 16-JUL-16:41 | 21.38 | 15.74 | 0.256334E+09 | 350.33 | 05-JUL-13:50 | 21.38 | 15.74 |
August | 0.455459E+10 | 12296.10 | 05-AUG-17:04 | 22.70 | 14.24 | 0.285635E+09 | 347.86 | 10-AUG-13:00 | 19.40 | 16.96 |
September | 0.287506E+10 | 14050.51 | 03-SEP-17:11 | 21.33 | 15.90 | 0.243423E+09 | 347.85 | 11-SEP-13:09 | 18.90 | 14.33 |
October | 0.156547E+10 | 4564.90 | 19-OCT-16:00 | 21.70 | 13.55 | 0.220676E+09 | 347.83 | 20-OCT-13:00 | 18.90 | 10.07 |
November | 0.418319E+09 | 1449.70 | 17-NOV-15:50 | 10.10 | 3.24 | 0.195678E+09 | 324.47 | 17-NOV-15:00 | 10.00 | 3.20 |
December | 25235402.68 | 924.54 | 02-DEC-17:02 | -20.0 | -20.5 | 0.186251E+09 | 257.46 | 11-DEC-14:30 | -18.2 | -19.1 |
Annual Sum or Average | 0.242172E+11 | 0.271955E+10 | ||||||||
Minimum of Months | 25235402.68 | 924.54 | -20.0 | -20.5 | 0.177427E+09 | 257.46 | -18.2 | -19.1 | ||
Maximum of Months | 0.507696E+10 | 14050.51 | 25.60 | 16.47 | 0.285635E+09 | 350.33 | 28.58 | 20.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8354039.78 | 954.05 | 28-JAN-17:02 | -7.8 | -9.1 | 0.302418E+09 | 406.70 | 05-JAN-14:00 | -7.8 | -9.1 |
February | 61279085.36 | 1077.22 | 08-FEB-16:40 | 3.67 | -1.2 | 0.276761E+09 | 415.78 | 08-FEB-14:00 | 3.67 | -1.2 |
March | 0.445803E+09 | 1377.94 | 29-MAR-15:50 | 4.90 | 1.34 | 0.339160E+09 | 481.53 | 29-MAR-13:00 | 4.90 | 1.34 |
April | 0.144305E+10 | 2771.14 | 14-APR-15:30 | 15.00 | 6.90 | 0.338531E+09 | 549.48 | 18-APR-13:00 | 17.80 | 10.49 |
May | 0.377539E+10 | 5538.54 | 26-MAY-13:30 | 22.50 | 17.44 | 0.426479E+09 | 549.51 | 24-MAY-09:09 | 22.50 | 17.44 |
June | 0.517008E+10 | 8164.04 | 28-JUN-06:03 | 19.55 | 18.20 | 0.434651E+09 | 549.72 | 29-JUN-13:50 | 32.88 | 24.59 |
July | 0.554865E+10 | 9613.93 | 23-JUL-16:01 | 29.72 | 22.65 | 0.405532E+09 | 585.21 | 05-JUL-13:09 | 29.72 | 22.65 |
August | 0.466368E+10 | 5712.28 | 09-AUG-15:30 | 27.25 | 21.19 | 0.452257E+09 | 549.51 | 10-AUG-13:00 | 19.40 | 16.96 |
September | 0.267001E+10 | 4847.50 | 01-SEP-15:40 | 26.10 | 17.70 | 0.387058E+09 | 549.50 | 11-SEP-13:09 | 18.90 | 14.33 |
October | 0.139421E+10 | 2155.22 | 20-OCT-15:20 | 18.70 | 10.02 | 0.344931E+09 | 549.48 | 02-OCT-13:00 | 18.70 | 10.02 |
November | 0.361410E+09 | 1370.26 | 01-NOV-15:40 | 17.97 | 13.32 | 0.306903E+09 | 485.06 | 01-NOV-13:00 | 17.97 | 13.32 |
December | 10451099.77 | 961.38 | 30-DEC-17:02 | -3.3 | -3.3 | 0.292569E+09 | 406.68 | 21-DEC-10:00 | -3.3 | -3.3 |
Annual Sum or Average | 0.255524E+11 | 0.430725E+10 | ||||||||
Minimum of Months | 8354039.78 | 954.05 | -7.8 | -9.1 | 0.276761E+09 | 406.68 | -7.8 | -9.1 | ||
Maximum of Months | 0.554865E+10 | 9613.93 | 29.72 | 22.65 | 0.452257E+09 | 585.21 | 32.88 | 24.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15579895.43 | 1010.78 | 21-JAN-17:02 | -5.0 | -7.1 | 0.141746E+09 | 250.69 | 11-JAN-08:09 | -5.0 | -7.1 |
February | 0.182894E+09 | 1428.84 | 28-FEB-10:00 | -6.1 | -7.7 | 0.129638E+09 | 296.87 | 28-FEB-09:00 | -6.1 | -7.7 |
March | 0.765986E+09 | 3115.20 | 31-MAR-10:10 | 2.07 | -0.7 | 0.164236E+09 | 338.72 | 20-MAR-10:09 | 2.07 | -0.7 |
April | 0.222760E+10 | 6831.77 | 18-APR-09:00 | 17.80 | 10.61 | 0.168039E+09 | 338.96 | 05-APR-10:00 | 17.80 | 10.61 |
May | 0.408124E+10 | 11455.15 | 21-MAY-10:13 | 14.70 | 8.71 | 0.200578E+09 | 339.04 | 17-MAY-08:00 | 14.70 | 8.71 |
June | 0.541682E+10 | 14817.63 | 25-JUN-08:12 | 24.27 | 20.87 | 0.202776E+09 | 339.38 | 07-JUN-08:50 | 24.27 | 20.87 |
July | 0.587242E+10 | 15935.80 | 23-JUL-09:21 | 25.85 | 22.64 | 0.189873E+09 | 345.21 | 05-JUL-10:00 | 25.85 | 22.64 |
August | 0.468827E+10 | 12586.23 | 06-AUG-08:42 | 17.93 | 13.93 | 0.209696E+09 | 338.75 | 21-AUG-07:10 | 15.97 | 15.14 |
September | 0.308112E+10 | 10056.41 | 10-SEP-09:32 | 14.83 | 10.42 | 0.177155E+09 | 338.88 | 13-SEP-07:19 | 7.60 | 6.49 |
October | 0.144937E+10 | 4436.32 | 19-OCT-09:00 | 11.10 | 7.97 | 0.158612E+09 | 338.73 | 19-OCT-10:09 | 14.27 | 10.24 |
November | 0.401668E+09 | 1524.46 | 16-NOV-09:50 | 1.32 | -0.7 | 0.143215E+09 | 310.32 | 16-NOV-09:00 | 1.70 | -0.5 |
December | 25281041.77 | 1016.33 | 16-DEC-17:02 | -5.9 | -6.6 | 0.136832E+09 | 250.69 | 18-DEC-16:00 | -23.5 | -24.0 |
Annual Sum or Average | 0.282082E+11 | 0.202240E+10 | ||||||||
Minimum of Months | 15579895.43 | 1010.78 | -6.1 | -7.7 | 0.129638E+09 | 250.69 | -23.5 | -24.0 | ||
Maximum of Months | 0.587242E+10 | 15935.80 | 25.85 | 22.64 | 0.209696E+09 | 345.21 | 25.85 | 22.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.829662E+09 | 6789.25 | 27-JAN-13:40 | -14.8 | -15.9 | 0.327160E+09 | 549.49 | 05-JAN-14:09 | -14.8 | -15.9 |
February | 0.146740E+10 | 9024.91 | 28-FEB-13:40 | 3.33 | -0.5 | 0.310984E+09 | 550.09 | 28-FEB-10:00 | 3.33 | -0.5 |
March | 0.211779E+10 | 9959.98 | 31-MAR-13:50 | 8.03 | 2.94 | 0.379234E+09 | 550.30 | 20-MAR-13:09 | 8.03 | 2.94 |
April | 0.378988E+10 | 13455.87 | 23-APR-14:02 | 24.60 | 16.15 | 0.363201E+09 | 549.90 | 13-APR-13:00 | 24.60 | 16.15 |
May | 0.587614E+10 | 15405.41 | 21-MAY-12:53 | 19.50 | 10.66 | 0.427275E+09 | 550.41 | 24-MAY-13:00 | 27.10 | 17.69 |
June | 0.673283E+10 | 16642.15 | 18-JUN-13:53 | 26.70 | 18.65 | 0.432756E+09 | 549.99 | 30-JUN-13:00 | 31.10 | 23.76 |
July | 0.766397E+10 | 18693.03 | 23-JUL-12:02 | 28.58 | 22.50 | 0.404700E+09 | 584.49 | 05-JUL-13:09 | 28.58 | 22.50 |
August | 0.746284E+10 | 17682.12 | 13-AUG-13:22 | 23.05 | 14.31 | 0.451822E+09 | 550.47 | 01-AUG-13:50 | 23.05 | 14.31 |
September | 0.561551E+10 | 18521.26 | 03-SEP-13:52 | 21.10 | 15.89 | 0.388850E+09 | 560.05 | 01-SEP-13:20 | 21.10 | 15.89 |
October | 0.333292E+10 | 18176.27 | 22-OCT-12:52 | 18.30 | 13.08 | 0.361532E+09 | 549.76 | 20-OCT-13:00 | 18.30 | 13.08 |
November | 0.148281E+10 | 8833.58 | 17-NOV-13:03 | 10.10 | 3.25 | 0.334348E+09 | 549.50 | 07-NOV-14:39 | 10.10 | 3.25 |
December | 0.501391E+09 | 4214.07 | 02-DEC-13:30 | -18.6 | -19.3 | 0.307541E+09 | 549.49 | 20-DEC-14:00 | -18.9 | -19.7 |
Annual Sum or Average | 0.468731E+11 | 0.448940E+10 | ||||||||
Minimum of Months | 0.501391E+09 | 4214.07 | -18.6 | -19.3 | 0.307541E+09 | 549.49 | -18.9 | -19.7 | ||
Maximum of Months | 0.766397E+10 | 18693.03 | 28.58 | 22.50 | 0.451822E+09 | 584.49 | 31.10 | 23.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 93207279.68 | 1495.22 | 27-JAN-16:00 | -14.4 | -15.6 | 0.193642E+09 | 295.30 | 27-JAN-16:10 | -14.8 | -15.9 |
February | 0.284844E+09 | 2343.74 | 08-FEB-16:30 | 3.85 | -1.1 | 0.179368E+09 | 338.99 | 28-FEB-16:19 | 5.93 | 1.38 |
March | 0.839834E+09 | 4815.85 | 31-MAR-16:00 | 8.90 | 3.77 | 0.219828E+09 | 338.90 | 29-MAR-15:50 | 8.90 | 3.77 |
April | 0.220172E+10 | 14726.65 | 23-APR-16:42 | 26.20 | 16.72 | 0.213019E+09 | 347.84 | 19-APR-13:00 | 26.20 | 16.72 |
May | 0.437346E+10 | 15723.30 | 21-MAY-16:52 | 22.10 | 11.17 | 0.265444E+09 | 347.86 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.509589E+10 | 15159.78 | 17-JUN-17:42 | 23.90 | 13.28 | 0.272397E+09 | 347.85 | 07-JUN-13:00 | 23.90 | 13.28 |
July | 0.560468E+10 | 16928.06 | 16-JUL-16:41 | 21.38 | 15.74 | 0.255498E+09 | 351.00 | 05-JUL-13:00 | 21.38 | 15.74 |
August | 0.481331E+10 | 15032.44 | 13-AUG-17:22 | 22.20 | 15.24 | 0.282956E+09 | 347.86 | 10-AUG-13:00 | 22.20 | 15.24 |
September | 0.310150E+10 | 16302.05 | 03-SEP-17:11 | 21.33 | 15.90 | 0.236315E+09 | 347.85 | 11-SEP-13:00 | 18.90 | 14.76 |
October | 0.161280E+10 | 5388.21 | 19-OCT-16:00 | 21.70 | 13.55 | 0.214300E+09 | 347.83 | 20-OCT-13:00 | 18.90 | 10.07 |
November | 0.424829E+09 | 1730.54 | 17-NOV-15:50 | 10.10 | 3.24 | 0.195539E+09 | 331.74 | 17-NOV-15:00 | 10.00 | 3.20 |
December | 42515823.95 | 1167.47 | 20-DEC-15:40 | -19.8 | -20.5 | 0.186102E+09 | 257.45 | 26-DEC-10:30 | -23.4 | -23.7 |
Annual Sum or Average | 0.284886E+11 | 0.271441E+10 | ||||||||
Minimum of Months | 42515823.95 | 1167.47 | -19.8 | -20.5 | 0.179368E+09 | 257.45 | -23.4 | -23.7 | ||
Maximum of Months | 0.560468E+10 | 16928.06 | 26.20 | 16.72 | 0.282956E+09 | 351.00 | 26.20 | 16.72 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.552446E+09 | 23509.58 | 02-JAN-05:01 | -18.2 |
February | 16994918.60 | 18972.02 | 28-FEB-07:01 | -14.9 |
March | 4604104.20 | 17770.79 | 06-MAR-07:01 | -19.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 5042355.24 | 17781.60 | 27-NOV-07:01 | -6.7 |
December | 0.142502E+09 | 20915.84 | 26-DEC-06:01 | -26.7 |
Annual Sum or Average | 0.721590E+09 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.552446E+09 | 23509.58 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138843E+11 | 20609.84 | 09-JAN-06:07 | -31.8 |
February | 0.917831E+10 | 19514.79 | 14-FEB-06:13 | -32.2 |
March | 0.615826E+10 | 17433.52 | 06-MAR-06:12 | -19.1 |
April | 0.206369E+10 | 12263.73 | 05-APR-06:01 | -13.5 |
May | 0.478433E+09 | 7447.94 | 01-MAY-06:01 | -3.5 |
June | 0.169053E+09 | 7039.33 | 28-JUN-05:03 | 15.15 |
July | 0.123841E+09 | 6158.83 | 31-JUL-05:03 | 14.68 |
August | 0.189372E+09 | 5563.25 | 28-AUG-05:03 | 13.90 |
September | 0.588446E+09 | 4832.19 | 06-SEP-05:02 | 1.28 |
October | 0.212123E+10 | 14901.03 | 30-OCT-05:12 | -9.8 |
November | 0.592347E+10 | 16145.15 | 25-NOV-06:13 | -19.4 |
December | 0.128899E+11 | 19474.29 | 20-DEC-06:12 | -29.0 |
Annual Sum or Average | 0.537682E+11 | |||
Minimum of Months | 0.123841E+09 | 4832.19 | -32.2 | |
Maximum of Months | 0.138843E+11 | 20609.84 | 15.15 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.585753E+10 | 12230.94 | 02-JAN-07:03 | -18.1 |
February | 0.378148E+10 | 9679.68 | 13-FEB-06:11 | -24.1 |
March | 0.272187E+10 | 9307.08 | 06-MAR-06:12 | -19.1 |
April | 0.100270E+10 | 5556.85 | 23-APR-16:02 | 26.60 |
May | 0.155444E+09 | 5879.86 | 21-MAY-14:52 | 22.80 |
June | 29828773.36 | 4344.63 | 04-JUN-15:12 | 21.10 |
July | 34180735.73 | 4272.29 | 23-JUL-16:01 | 29.72 |
August | 36981714.14 | 3972.52 | 13-AUG-11:23 | 21.95 |
September | 0.152885E+09 | 5306.70 | 03-SEP-15:51 | 21.70 |
October | 0.101952E+10 | 6664.94 | 09-OCT-13:23 | 5.85 |
November | 0.269423E+10 | 9335.81 | 27-NOV-07:11 | -6.7 |
December | 0.526619E+10 | 12257.80 | 26-DEC-07:04 | -26.5 |
Annual Sum or Average | 0.227528E+11 | |||
Minimum of Months | 29828773.36 | 3972.52 | -26.5 | |
Maximum of Months | 0.585753E+10 | 12257.80 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.428292E+10 | 10524.29 | 02-JAN-07:01 | -18.1 |
February | 0.256705E+10 | 5440.64 | 13-FEB-07:01 | -24.4 |
March | 0.187388E+10 | 5224.42 | 06-MAR-07:01 | -19.3 |
April | 0.567495E+09 | 5413.37 | 21-APR-05:02 | -4.3 |
May | 65213168.98 | 5140.81 | 15-MAY-05:02 | 6.87 |
June | 30257779.27 | 4991.77 | 01-JUN-05:03 | 14.08 |
July | 35531582.14 | 4257.50 | 06-JUL-04:03 | 15.00 |
August | 40725146.40 | 5234.94 | 18-AUG-05:03 | 11.60 |
September | 46209211.82 | 6188.96 | 20-SEP-05:03 | 5.60 |
October | 0.569545E+09 | 5942.45 | 24-OCT-05:02 | 5.10 |
November | 0.184474E+10 | 5743.80 | 27-NOV-07:01 | -6.7 |
December | 0.379023E+10 | 8979.75 | 26-DEC-06:12 | -26.6 |
Annual Sum or Average | 0.157138E+11 | |||
Minimum of Months | 30257779.27 | 4257.50 | -26.6 | |
Maximum of Months | 0.428292E+10 | 10524.29 | 15.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.270984E+10 | 29089.89 | 02-JAN-05:01 | -18.2 |
February | 0.707760E+09 | 26478.69 | 21-FEB-06:01 | 2.80 |
March | 0.258844E+09 | 26522.03 | 06-MAR-06:01 | -19.0 |
April | 20699760.98 | 23975.69 | 03-APR-06:01 | -3.8 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 13729559.45 | 23954.96 | 30-OCT-06:01 | -9.4 |
November | 0.506310E+09 | 27165.33 | 27-NOV-05:01 | -7.2 |
December | 0.183750E+10 | 28860.03 | 26-DEC-05:01 | -25.9 |
Annual Sum or Average | 0.605468E+10 | |||
Minimum of Months | 0.00 | 0.00 | -25.9 | |
Maximum of Months | 0.270984E+10 | 29089.89 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.803673E+10 | 32012.29 | 09-JAN-01:21 | -31.1 |
February | 0.406724E+10 | 31417.81 | 27-FEB-05:01 | -17.4 |
March | 0.194994E+10 | 31210.57 | 06-MAR-05:01 | -18.4 |
April | 0.357315E+09 | 28487.41 | 10-APR-05:01 | -2.7 |
May | 6241067.21 | 25746.93 | 01-MAY-06:01 | -3.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.305964E+09 | 29101.59 | 30-OCT-04:01 | -10.0 |
November | 0.238170E+10 | 31356.93 | 27-NOV-05:01 | -7.2 |
December | 0.688135E+10 | 31996.32 | 25-DEC-23:32 | -19.4 |
Annual Sum or Average | 0.239865E+11 | |||
Minimum of Months | 0.00 | 0.00 | -31.1 | |
Maximum of Months | 0.803673E+10 | 32012.29 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115463E+11 | 11774.77 | 09-JAN-01:21 | -31.1 |
February | 0.733008E+10 | 11659.72 | 13-FEB-05:21 | -23.6 |
March | 0.441425E+10 | 11274.42 | 06-MAR-03:22 | -16.6 |
April | 0.911512E+09 | 10524.02 | 03-APR-04:01 | -5.4 |
May | 27610636.01 | 9308.33 | 01-MAY-05:01 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 398223.57 | 2654.82 | 19-AUG-06:03 | 6.23 |
September | 17856903.04 | 8323.39 | 23-SEP-06:03 | 4.32 |
October | 0.802489E+09 | 10377.48 | 30-OCT-04:01 | -10.0 |
November | 0.406823E+10 | 10947.84 | 23-NOV-22:12 | -10.8 |
December | 0.107129E+11 | 11573.14 | 10-DEC-12:12 | -23.7 |
Annual Sum or Average | 0.398317E+11 | |||
Minimum of Months | 0.00 | 0.00 | -31.1 | |
Maximum of Months | 0.115463E+11 | 11774.77 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.700994E+10 | 13587.70 | 09-JAN-01:21 | -31.1 |
February | 0.401031E+10 | 13307.93 | 13-FEB-05:21 | -23.6 |
March | 0.222232E+10 | 12884.93 | 06-MAR-03:22 | -16.6 |
April | 0.396817E+09 | 12141.67 | 03-APR-04:01 | -5.4 |
May | 6053528.73 | 10602.29 | 01-MAY-05:01 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 1340.14 | 8.93 | 19-AUG-06:03 | 6.23 |
September | 12132487.07 | 5356.80 | 28-SEP-06:03 | 6.70 |
October | 0.461802E+09 | 11951.58 | 30-OCT-04:01 | -10.0 |
November | 0.242260E+10 | 12613.74 | 25-NOV-05:01 | -19.0 |
December | 0.665555E+10 | 13254.39 | 10-DEC-06:12 | -26.2 |
Annual Sum or Average | 0.231975E+11 | |||
Minimum of Months | 0.00 | 0.00 | -31.1 | |
Maximum of Months | 0.700994E+10 | 13587.70 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.811782E+10 | 17917.82 | 09-JAN-01:21 | -31.1 |
February | 0.465439E+10 | 17530.11 | 13-FEB-02:42 | -22.0 |
March | 0.290014E+10 | 17021.10 | 06-MAR-03:22 | -16.6 |
April | 0.683600E+09 | 15973.56 | 03-APR-04:01 | -5.4 |
May | 30388378.78 | 13988.70 | 01-MAY-05:01 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 846523.91 | 5419.22 | 19-AUG-06:03 | 6.23 |
September | 17091392.27 | 8343.20 | 23-SEP-06:03 | 4.32 |
October | 0.611353E+09 | 15855.80 | 30-OCT-04:01 | -10.0 |
November | 0.297217E+10 | 16655.50 | 25-NOV-05:01 | -19.0 |
December | 0.797226E+10 | 17508.42 | 10-DEC-06:12 | -26.2 |
Annual Sum or Average | 0.279600E+11 | |||
Minimum of Months | 0.00 | 0.00 | -31.1 | |
Maximum of Months | 0.811782E+10 | 17917.82 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.720282E+10 | 15009.91 | 09-JAN-01:21 | -31.1 |
February | 0.432185E+10 | 14713.63 | 13-FEB-05:21 | -23.6 |
March | 0.249385E+10 | 14219.11 | 06-MAR-03:22 | -16.6 |
April | 0.528605E+09 | 13364.35 | 03-APR-04:01 | -5.4 |
May | 21469849.83 | 11703.32 | 01-MAY-05:01 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 1030353.01 | 4913.10 | 19-AUG-06:03 | 6.23 |
September | 15301203.23 | 5330.66 | 28-SEP-06:03 | 6.70 |
October | 0.509310E+09 | 13193.58 | 30-OCT-04:01 | -10.0 |
November | 0.251629E+10 | 13959.31 | 25-NOV-05:01 | -19.0 |
December | 0.677996E+10 | 14634.74 | 24-DEC-00:12 | -27.0 |
Annual Sum or Average | 0.243905E+11 | |||
Minimum of Months | 0.00 | 0.00 | -31.1 | |
Maximum of Months | 0.720282E+10 | 15009.91 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.791304E+10 | 8307.63 | 01-JAN-08:61 | -26.7 |
February | 0.464931E+10 | 8049.71 | 13-FEB-05:11 | -23.5 |
March | 0.319505E+10 | 8056.38 | 06-MAR-03:22 | -16.6 |
April | 0.497031E+09 | 7298.74 | 03-APR-04:01 | -5.4 |
May | 8581005.96 | 6624.87 | 01-MAY-05:01 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 75865561.08 | 6832.47 | 30-OCT-05:01 | -9.9 |
November | 0.151801E+10 | 7842.84 | 27-NOV-05:01 | -7.2 |
December | 0.632237E+10 | 8284.11 | 25-DEC-23:32 | -19.4 |
Annual Sum or Average | 0.241793E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.791304E+10 | 8307.63 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.473138E+10 | 10495.63 | 01-JAN-08:61 | -26.7 |
February | 0.230517E+10 | 10225.66 | 13-FEB-05:11 | -23.5 |
March | 0.134229E+10 | 9985.78 | 07-MAR-05:01 | -23.6 |
April | 0.138355E+09 | 9169.90 | 04-APR-05:01 | -9.0 |
May | 17613.04 | 205.49 | 01-MAY-05:01 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 43739686.54 | 8734.23 | 30-OCT-05:01 | -9.9 |
November | 0.885603E+09 | 10016.44 | 27-NOV-05:01 | -7.2 |
December | 0.384829E+10 | 10427.52 | 25-DEC-23:32 | -19.4 |
Annual Sum or Average | 0.132948E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.473138E+10 | 10495.63 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142214E+11 | 23286.22 | 06-JAN-07:10 | -35.0 |
February | 0.903860E+10 | 22466.91 | 14-FEB-07:10 | -33.0 |
March | 0.818367E+10 | 19140.59 | 16-MAR-06:10 | -22.9 |
April | 0.322299E+10 | 16554.91 | 05-APR-06:10 | -13.5 |
May | 0.103975E+10 | 13999.35 | 01-MAY-06:10 | -3.5 |
June | 0.277640E+09 | 10467.37 | 02-JUN-06:10 | 9.08 |
July | 64256453.35 | 10468.53 | 18-JUL-06:05 | 11.23 |
August | 0.193077E+09 | 10637.43 | 25-AUG-06:05 | 9.05 |
September | 0.104823E+10 | 11622.10 | 21-SEP-06:10 | 5.10 |
October | 0.287320E+10 | 15675.10 | 30-OCT-06:10 | -9.4 |
November | 0.573135E+10 | 17755.67 | 29-NOV-07:10 | -18.4 |
December | 0.126697E+11 | 21344.18 | 20-DEC-07:10 | -29.1 |
Annual Sum or Average | 0.585638E+11 | |||
Minimum of Months | 64256453.35 | 10467.37 | -35.0 | |
Maximum of Months | 0.142214E+11 | 23286.22 | 11.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.488317E+10 | 11397.55 | 01-JAN-08:61 | -26.7 |
February | 0.246758E+10 | 11091.50 | 13-FEB-05:11 | -23.5 |
March | 0.148704E+10 | 10803.51 | 07-MAR-05:01 | -23.6 |
April | 0.195001E+09 | 9903.61 | 04-APR-05:01 | -9.0 |
May | 4607800.43 | 8825.74 | 01-MAY-06:01 | -3.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 51749004.68 | 9468.72 | 30-OCT-05:01 | -9.9 |
November | 0.898574E+09 | 10848.03 | 27-NOV-05:01 | -7.2 |
December | 0.395304E+10 | 11331.32 | 25-DEC-23:32 | -19.4 |
Annual Sum or Average | 0.139408E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.488317E+10 | 11397.55 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.764051E+10 | 9338.76 | 09-JAN-01:21 | -31.1 |
February | 0.419291E+10 | 9228.84 | 12-FEB-23:02 | -17.4 |
March | 0.216172E+10 | 8885.38 | 06-MAR-05:11 | -18.5 |
April | 0.269546E+09 | 8067.49 | 03-APR-04:01 | -5.4 |
May | 2290890.75 | 7004.71 | 01-MAY-06:01 | -3.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.187454E+09 | 7970.03 | 30-OCT-04:01 | -10.0 |
November | 0.186182E+10 | 8741.06 | 26-NOV-23:42 | -6.6 |
December | 0.676409E+10 | 9171.81 | 10-DEC-18:52 | -25.0 |
Annual Sum or Average | 0.230803E+11 | |||
Minimum of Months | 0.00 | 0.00 | -31.1 | |
Maximum of Months | 0.764051E+10 | 9338.76 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.454640E+10 | 12789.88 | 09-JAN-01:21 | -31.1 |
February | 0.217287E+10 | 12547.67 | 12-FEB-23:02 | -17.4 |
March | 0.106691E+10 | 12142.56 | 06-MAR-05:11 | -18.5 |
April | 0.115016E+09 | 10649.85 | 04-APR-05:01 | -9.0 |
May | 39563.91 | 527.52 | 02-MAY-06:01 | 1.18 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 517873.22 | 1311.08 | 23-SEP-06:03 | 4.32 |
October | 0.117445E+09 | 10694.60 | 30-OCT-05:01 | -9.9 |
November | 0.115064E+10 | 12039.34 | 27-NOV-05:01 | -7.2 |
December | 0.417406E+10 | 12537.57 | 25-DEC-06:01 | -29.3 |
Annual Sum or Average | 0.133439E+11 | |||
Minimum of Months | 0.00 | 0.00 | -31.1 | |
Maximum of Months | 0.454640E+10 | 12789.88 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.477670E+10 | 15908.60 | 09-JAN-01:21 | -31.1 |
February | 0.226570E+10 | 15479.84 | 12-FEB-23:02 | -17.4 |
March | 0.124759E+10 | 15170.54 | 06-MAR-05:11 | -18.5 |
April | 0.188642E+09 | 13371.16 | 04-APR-05:01 | -9.0 |
May | 2872911.05 | 12076.47 | 01-MAY-06:01 | -3.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.136130E+09 | 13428.64 | 30-OCT-05:01 | -9.9 |
November | 0.128360E+10 | 14983.13 | 27-NOV-05:01 | -7.2 |
December | 0.451523E+10 | 15589.68 | 25-DEC-08:61 | -27.8 |
Annual Sum or Average | 0.144165E+11 | |||
Minimum of Months | 0.00 | 0.00 | -31.1 | |
Maximum of Months | 0.477670E+10 | 15908.60 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.464841E+10 | 12918.18 | 09-JAN-01:21 | -31.1 |
February | 0.236859E+10 | 12612.43 | 12-FEB-23:02 | -17.4 |
March | 0.117116E+10 | 12253.81 | 06-MAR-05:11 | -18.5 |
April | 0.154572E+09 | 10681.87 | 04-APR-05:01 | -9.0 |
May | 2423213.29 | 9550.90 | 01-MAY-06:01 | -3.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 454823.26 | 970.07 | 29-SEP-06:03 | 7.30 |
October | 0.131524E+09 | 10727.78 | 30-OCT-05:01 | -9.9 |
November | 0.115113E+10 | 12125.87 | 27-NOV-05:01 | -7.2 |
December | 0.419757E+10 | 12635.32 | 25-DEC-06:01 | -29.3 |
Annual Sum or Average | 0.138258E+11 | |||
Minimum of Months | 0.00 | 0.00 | -31.1 | |
Maximum of Months | 0.464841E+10 | 12918.18 | 17.07 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.208150E+11 | 18520.31 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.188385E+11 | 18520.31 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.216654E+11 | 18520.31 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.200796E+11 | 18520.31 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.212402E+11 | 18520.31 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.208620E+11 | 18520.31 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.204550E+11 | 18520.31 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.216654E+11 | 18520.31 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.200739E+11 | 18520.31 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.208179E+11 | 18520.31 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.203773E+11 | 18520.31 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.204522E+11 | 18520.31 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.247342E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.188385E+11 | 18520.31 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.216654E+11 | 18520.31 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.850593E+09 | 1168.55 | 02-JAN-08:09 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.721214E+09 | 1038.79 | 02-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.824156E+09 | 962.01 | 03-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.716865E+09 | 720.41 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.756092E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.746689E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.703073E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.794971E+09 | 869.70 | 31-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.725651E+09 | 886.83 | 19-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.784511E+09 | 1156.07 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.826338E+09 | 1168.55 | 06-NOV-16:49 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.836013E+09 | 1168.55 | 01-DEC-16:19 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.928616E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.703073E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.850593E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.531515E+09 | 739.79 | 02-JAN-08:09 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.454953E+09 | 668.53 | 02-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.520572E+09 | 616.86 | 03-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.454231E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.480175E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.474554E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.446638E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.504166E+09 | 522.00 | 31-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.459391E+09 | 521.10 | 19-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.493745E+09 | 729.41 | 31-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.519255E+09 | 739.79 | 06-NOV-16:49 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.523522E+09 | 739.79 | 01-DEC-16:19 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.586272E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.446638E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.531515E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.828743E+09 | 1168.55 | 02-JAN-08:09 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.712728E+09 | 998.91 | 02-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.820654E+09 | 945.15 | 03-MAR-16:00 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.717742E+09 | 720.41 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.758830E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.749982E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.705879E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.796338E+09 | 860.45 | 31-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.725318E+09 | 873.70 | 19-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.776588E+09 | 1153.17 | 31-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.811675E+09 | 1168.55 | 06-NOV-16:49 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.817145E+09 | 1168.55 | 01-DEC-16:19 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.922162E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.705879E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.828743E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.530878E+09 | 739.74 | 02-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.452923E+09 | 614.43 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.520597E+09 | 620.24 | 13-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.453683E+09 | 498.99 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.479060E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.473072E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.445245E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.503290E+09 | 560.69 | 31-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.459251E+09 | 576.68 | 19-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.495008E+09 | 732.10 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.517440E+09 | 739.74 | 06-NOV-16:49 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.522319E+09 | 739.74 | 01-DEC-16:19 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.585276E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.445245E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.530878E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.848150E+09 | 1168.55 | 02-JAN-08:09 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.720074E+09 | 1032.81 | 02-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.823074E+09 | 952.97 | 03-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.716517E+09 | 720.41 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.755861E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.746367E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.702739E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.794444E+09 | 856.67 | 31-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.725096E+09 | 874.42 | 19-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.782945E+09 | 1155.52 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.824252E+09 | 1168.55 | 06-NOV-16:49 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.833997E+09 | 1168.55 | 01-DEC-16:19 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.927352E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.702739E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.848150E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.530640E+09 | 739.79 | 02-JAN-08:09 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.454347E+09 | 666.04 | 02-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.520186E+09 | 612.72 | 03-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.454025E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.479922E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.474327E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.446437E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.503918E+09 | 514.09 | 31-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.459099E+09 | 512.84 | 19-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.493174E+09 | 729.01 | 31-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.518493E+09 | 739.79 | 06-NOV-16:49 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.522689E+09 | 739.79 | 01-DEC-16:19 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.585726E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.446437E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.530640E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.827684E+09 | 1168.55 | 02-JAN-08:09 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.712265E+09 | 990.57 | 02-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.819969E+09 | 935.17 | 03-MAR-16:00 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.717319E+09 | 720.41 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.758471E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.749547E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.705454E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.795854E+09 | 846.91 | 31-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.724788E+09 | 860.57 | 19-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.775906E+09 | 1152.44 | 31-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.810838E+09 | 1168.55 | 06-NOV-16:49 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.815866E+09 | 1168.55 | 01-DEC-16:19 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.921396E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.705454E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.827684E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.530012E+09 | 739.74 | 02-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.452503E+09 | 610.04 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.520012E+09 | 616.19 | 13-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.453398E+09 | 456.05 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.478932E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.472913E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.445089E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.503033E+09 | 554.69 | 31-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.458925E+09 | 571.19 | 19-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.494444E+09 | 731.84 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.516635E+09 | 739.74 | 06-NOV-16:49 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.521571E+09 | 739.74 | 01-DEC-16:19 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.584747E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.445089E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.530012E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.850594E+09 | 1168.55 | 02-JAN-08:09 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.721213E+09 | 1038.78 | 02-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.824155E+09 | 962.00 | 03-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.716865E+09 | 720.41 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.756092E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.746689E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.703073E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.794971E+09 | 869.68 | 31-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.725650E+09 | 886.82 | 19-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.784511E+09 | 1156.07 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.826338E+09 | 1168.55 | 06-NOV-16:49 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.836012E+09 | 1168.55 | 01-DEC-16:19 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.928616E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.703073E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.850594E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.531515E+09 | 739.79 | 02-JAN-08:09 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.454953E+09 | 668.53 | 02-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.520572E+09 | 616.85 | 03-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.454231E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.480175E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.474554E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.446638E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.504166E+09 | 521.99 | 31-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.459391E+09 | 521.09 | 19-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.493744E+09 | 729.41 | 31-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.519254E+09 | 739.79 | 06-NOV-16:49 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.523522E+09 | 739.79 | 01-DEC-16:19 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.586271E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.446638E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.531515E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.828743E+09 | 1168.55 | 02-JAN-08:09 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.712728E+09 | 998.91 | 02-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.820654E+09 | 945.14 | 03-MAR-16:00 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.717742E+09 | 720.41 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.758830E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.749982E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.705879E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.796337E+09 | 860.43 | 31-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.725318E+09 | 873.68 | 19-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.776588E+09 | 1153.16 | 31-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.811674E+09 | 1168.55 | 06-NOV-16:49 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.817145E+09 | 1168.55 | 01-DEC-16:19 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.922162E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.705879E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.828743E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.530878E+09 | 739.74 | 02-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.452923E+09 | 614.43 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.520597E+09 | 620.24 | 13-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.453683E+09 | 498.98 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.479060E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.473078E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.445245E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.503289E+09 | 560.68 | 31-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.459250E+09 | 576.67 | 19-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.495007E+09 | 732.10 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.517440E+09 | 739.74 | 06-NOV-16:49 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.522319E+09 | 739.74 | 01-DEC-16:19 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.585277E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.445245E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.530878E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.208150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.200796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.212402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.208620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.204550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.200739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.208179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.203773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.204522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.247342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.850593E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197328E+10 |
February | 0.901968E+09 | 0.721214E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168131E+10 |
March | 0.107774E+10 | 0.824156E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114422E+10 |
April | 0.956342E+09 | 0.716865E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2364824.15 | 0.103658E+10 |
May | 0.103597E+10 | 0.756092E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3495231.40 | 0.533910E+09 |
June | 0.103308E+10 | 0.746689E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13270660.19 | 0.293100E+09 |
July | 0.959235E+09 | 0.703073E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16269070.48 | 0.216386E+09 |
August | 0.107774E+10 | 0.794971E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5678992.51 | 0.293915E+09 |
September | 0.956342E+09 | 0.725651E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 172802.70 | 0.490490E+09 |
October | 0.994195E+09 | 0.784511E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711546E+09 |
November | 0.984487E+09 | 0.826338E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129413E+10 |
December | 0.959235E+09 | 0.836013E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209397E+10 |
Annual Sum or Average | 0.119305E+11 | 0.928616E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41251581.44 | 0.117628E+11 |
Minimum of Months | 0.901968E+09 | 0.703073E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216386E+09 |
Maximum of Months | 0.107774E+10 | 0.850593E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16269070.48 | 0.209397E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.531515E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131834E+10 |
February | 0.571020E+09 | 0.454953E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112469E+10 |
March | 0.682301E+09 | 0.520572E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772057E+09 |
April | 0.605444E+09 | 0.454231E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1596528.78 | 0.711989E+09 |
May | 0.655854E+09 | 0.480175E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2330818.22 | 0.365868E+09 |
June | 0.654023E+09 | 0.474554E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8839125.47 | 0.199216E+09 |
July | 0.607275E+09 | 0.446638E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10763192.34 | 0.144771E+09 |
August | 0.682301E+09 | 0.504166E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3602084.26 | 0.204046E+09 |
September | 0.605444E+09 | 0.459391E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115202.83 | 0.334003E+09 |
October | 0.629407E+09 | 0.493745E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481261E+09 |
November | 0.623262E+09 | 0.519255E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.865087E+09 |
December | 0.607275E+09 | 0.523522E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139832E+10 |
Annual Sum or Average | 0.755301E+10 | 0.586272E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27246951.91 | 0.791965E+10 |
Minimum of Months | 0.571020E+09 | 0.446638E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144771E+09 |
Maximum of Months | 0.682301E+09 | 0.531515E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10763192.34 | 0.139832E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.828743E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198949E+10 |
February | 0.901968E+09 | 0.712728E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172679E+10 |
March | 0.107774E+10 | 0.820654E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119136E+10 |
April | 0.956342E+09 | 0.717742E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38772.00 | 0.109397E+10 |
May | 0.103597E+10 | 0.758830E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3493952.35 | 0.547542E+09 |
June | 0.103308E+10 | 0.749982E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12977438.45 | 0.293489E+09 |
July | 0.959235E+09 | 0.705879E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15564414.03 | 0.218429E+09 |
August | 0.107774E+10 | 0.796338E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5333599.37 | 0.310158E+09 |
September | 0.956342E+09 | 0.725318E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 170959.40 | 0.523559E+09 |
October | 0.994195E+09 | 0.776588E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751050E+09 |
November | 0.984487E+09 | 0.811675E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132601E+10 |
December | 0.959235E+09 | 0.817145E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211167E+10 |
Annual Sum or Average | 0.119305E+11 | 0.922162E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37579135.60 | 0.120835E+11 |
Minimum of Months | 0.901968E+09 | 0.705879E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218429E+09 |
Maximum of Months | 0.107774E+10 | 0.828743E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15564414.03 | 0.211167E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.530878E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131876E+10 |
February | 0.570983E+09 | 0.452923E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112998E+10 |
March | 0.682256E+09 | 0.520597E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777811E+09 |
April | 0.605404E+09 | 0.453683E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.712095E+09 |
May | 0.655811E+09 | 0.479060E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2330238.94 | 0.368502E+09 |
June | 0.653980E+09 | 0.473072E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9145588.22 | 0.197549E+09 |
July | 0.607235E+09 | 0.445245E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10780437.34 | 0.150057E+09 |
August | 0.682256E+09 | 0.503290E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3815688.66 | 0.202837E+09 |
September | 0.605404E+09 | 0.459251E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115204.28 | 0.334273E+09 |
October | 0.629366E+09 | 0.495008E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482342E+09 |
November | 0.623221E+09 | 0.517440E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.865579E+09 |
December | 0.607235E+09 | 0.522319E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139847E+10 |
Annual Sum or Average | 0.755252E+10 | 0.585276E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26187157.45 | 0.793826E+10 |
Minimum of Months | 0.570983E+09 | 0.445245E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150057E+09 |
Maximum of Months | 0.682256E+09 | 0.530878E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10780437.34 | 0.139847E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.848150E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106050E+10 |
February | 0.901968E+09 | 0.720074E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911289E+09 |
March | 0.107774E+10 | 0.823074E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622180E+09 |
April | 0.956342E+09 | 0.716517E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2546026.58 | 0.569463E+09 |
May | 0.103597E+10 | 0.755861E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1924289.28 | 0.283914E+09 |
June | 0.103308E+10 | 0.746367E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8363951.01 | 0.154891E+09 |
July | 0.959235E+09 | 0.702739E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9698266.32 | 0.114881E+09 |
August | 0.107774E+10 | 0.794444E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3255753.20 | 0.161927E+09 |
September | 0.956342E+09 | 0.725096E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95978.43 | 0.284343E+09 |
October | 0.994195E+09 | 0.782945E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420300E+09 |
November | 0.984487E+09 | 0.824252E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736979E+09 |
December | 0.959235E+09 | 0.833997E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113497E+10 |
Annual Sum or Average | 0.119305E+11 | 0.927352E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25884264.82 | 0.645563E+10 |
Minimum of Months | 0.901968E+09 | 0.702739E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114881E+09 |
Maximum of Months | 0.107774E+10 | 0.848150E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9698266.32 | 0.113497E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.530640E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708763E+09 |
February | 0.571020E+09 | 0.454347E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612910E+09 |
March | 0.682301E+09 | 0.520186E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422429E+09 |
April | 0.605444E+09 | 0.454025E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1024590.93 | 0.399421E+09 |
May | 0.655854E+09 | 0.479922E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1278132.05 | 0.200990E+09 |
June | 0.654023E+09 | 0.474327E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4972802.68 | 0.109689E+09 |
July | 0.607275E+09 | 0.446437E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5979542.52 | 79865296.41 |
August | 0.682301E+09 | 0.503918E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1949026.42 | 0.116327E+09 |
September | 0.605444E+09 | 0.459099E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63985.53 | 0.196485E+09 |
October | 0.629407E+09 | 0.493174E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286187E+09 |
November | 0.623262E+09 | 0.518493E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493898E+09 |
December | 0.607275E+09 | 0.522689E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757184E+09 |
Annual Sum or Average | 0.755301E+10 | 0.585726E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15268080.13 | 0.438415E+10 |
Minimum of Months | 0.571020E+09 | 0.446437E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79865296.41 |
Maximum of Months | 0.682301E+09 | 0.530640E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5979542.52 | 0.757184E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.827684E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152561E+11 |
February | 0.901968E+09 | 0.712265E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118074E+11 |
March | 0.107774E+10 | 0.819969E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112812E+11 |
April | 0.956342E+09 | 0.717319E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58409.05 | 0.660321E+10 |
May | 0.103597E+10 | 0.758471E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164374E+09 | 0.333120E+10 |
June | 0.103308E+10 | 0.749547E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362268E+09 | 0.165385E+10 |
July | 0.959235E+09 | 0.705454E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347280E+09 | 0.112931E+10 |
August | 0.107774E+10 | 0.795854E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190082E+09 | 0.199158E+10 |
September | 0.956342E+09 | 0.724788E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8134962.28 | 0.387722E+10 |
October | 0.994195E+09 | 0.775906E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644184E+10 |
November | 0.984487E+09 | 0.810838E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850498E+10 |
December | 0.959235E+09 | 0.815866E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133633E+11 |
Annual Sum or Average | 0.119305E+11 | 0.921396E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107220E+10 | 0.852412E+11 |
Minimum of Months | 0.901968E+09 | 0.705454E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112931E+10 |
Maximum of Months | 0.107774E+10 | 0.827684E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362268E+09 | 0.152561E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.530012E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.709150E+09 |
February | 0.570983E+09 | 0.452503E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614911E+09 |
March | 0.682256E+09 | 0.520012E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424856E+09 |
April | 0.605404E+09 | 0.453398E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11047.20 | 0.398435E+09 |
May | 0.655811E+09 | 0.478932E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1270614.36 | 0.203528E+09 |
June | 0.653980E+09 | 0.472913E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4966763.80 | 0.108580E+09 |
July | 0.607235E+09 | 0.445089E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5878045.80 | 84330739.19 |
August | 0.682256E+09 | 0.503033E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1980941.01 | 0.117117E+09 |
September | 0.605404E+09 | 0.458925E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63986.70 | 0.197872E+09 |
October | 0.629366E+09 | 0.494444E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286479E+09 |
November | 0.623221E+09 | 0.516635E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493723E+09 |
December | 0.607235E+09 | 0.521571E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757832E+09 |
Annual Sum or Average | 0.755252E+10 | 0.584747E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14171398.88 | 0.439681E+10 |
Minimum of Months | 0.570983E+09 | 0.445089E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84330739.19 |
Maximum of Months | 0.682256E+09 | 0.530012E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5878045.80 | 0.757832E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.850594E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165728E+10 |
February | 0.901968E+09 | 0.721213E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142212E+10 |
March | 0.107774E+10 | 0.824155E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.984926E+09 |
April | 0.956342E+09 | 0.716865E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1868796.00 | 0.921493E+09 |
May | 0.103597E+10 | 0.756092E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2946568.02 | 0.468178E+09 |
June | 0.103308E+10 | 0.746689E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11313720.40 | 0.255843E+09 |
July | 0.959235E+09 | 0.703073E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13684676.37 | 0.187937E+09 |
August | 0.107774E+10 | 0.794971E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4738810.84 | 0.257490E+09 |
September | 0.956342E+09 | 0.725650E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 147048.25 | 0.439991E+09 |
October | 0.994195E+09 | 0.784511E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640891E+09 |
November | 0.984487E+09 | 0.826338E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112467E+10 |
December | 0.959235E+09 | 0.836012E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176545E+10 |
Annual Sum or Average | 0.119305E+11 | 0.928616E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34699619.88 | 0.101263E+11 |
Minimum of Months | 0.901968E+09 | 0.703073E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187937E+09 |
Maximum of Months | 0.107774E+10 | 0.850594E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13684676.37 | 0.176545E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.531515E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110555E+10 |
February | 0.421807E+09 | 0.454953E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.953039E+09 |
March | 0.502994E+09 | 0.520572E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664704E+09 |
April | 0.447140E+09 | 0.454231E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1349069.44 | 0.628853E+09 |
May | 0.484071E+09 | 0.480175E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1966129.28 | 0.318069E+09 |
June | 0.482240E+09 | 0.474554E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7522859.44 | 0.172574E+09 |
July | 0.448971E+09 | 0.446638E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9179100.11 | 0.124739E+09 |
August | 0.502994E+09 | 0.504166E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3044071.59 | 0.176476E+09 |
September | 0.447140E+09 | 0.459391E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98022.51 | 0.295754E+09 |
October | 0.465148E+09 | 0.493744E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430148E+09 |
November | 0.460569E+09 | 0.519254E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751375E+09 |
December | 0.448971E+09 | 0.523522E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117714E+10 |
Annual Sum or Average | 0.557719E+10 | 0.586271E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23159252.36 | 0.679842E+10 |
Minimum of Months | 0.421807E+09 | 0.446638E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124739E+09 |
Maximum of Months | 0.502994E+09 | 0.531515E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9179100.11 | 0.117714E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.828743E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167622E+10 |
February | 0.901968E+09 | 0.712728E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147542E+10 |
March | 0.107774E+10 | 0.820654E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102803E+10 |
April | 0.956342E+09 | 0.717742E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32243.08 | 0.966807E+09 |
May | 0.103597E+10 | 0.758830E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2944787.55 | 0.477895E+09 |
June | 0.103308E+10 | 0.749982E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10976587.30 | 0.256433E+09 |
July | 0.959235E+09 | 0.705879E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13143833.66 | 0.189738E+09 |
August | 0.107774E+10 | 0.796337E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4493515.96 | 0.270594E+09 |
September | 0.956342E+09 | 0.725318E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140464.56 | 0.463285E+09 |
October | 0.994195E+09 | 0.776588E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671840E+09 |
November | 0.984487E+09 | 0.811674E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115767E+10 |
December | 0.959235E+09 | 0.817145E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178789E+10 |
Annual Sum or Average | 0.119305E+11 | 0.922162E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31731432.11 | 0.104218E+11 |
Minimum of Months | 0.901968E+09 | 0.705879E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189738E+09 |
Maximum of Months | 0.107774E+10 | 0.828743E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13143833.66 | 0.178789E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.530878E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110614E+10 |
February | 0.570983E+09 | 0.452923E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957525E+09 |
March | 0.682256E+09 | 0.520597E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669376E+09 |
April | 0.605404E+09 | 0.453683E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 578.38 | 0.629687E+09 |
May | 0.655811E+09 | 0.479060E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1964413.57 | 0.321602E+09 |
June | 0.653980E+09 | 0.473078E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7720978.70 | 0.172567E+09 |
July | 0.607235E+09 | 0.445245E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8948879.55 | 0.130033E+09 |
August | 0.682256E+09 | 0.503289E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3139186.69 | 0.177483E+09 |
September | 0.605404E+09 | 0.459250E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97987.18 | 0.297851E+09 |
October | 0.629366E+09 | 0.495007E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431740E+09 |
November | 0.623221E+09 | 0.517440E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751946E+09 |
December | 0.607235E+09 | 0.522319E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117761E+10 |
Annual Sum or Average | 0.755252E+10 | 0.585277E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21872024.08 | 0.682356E+10 |
Minimum of Months | 0.570983E+09 | 0.445245E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130033E+09 |
Maximum of Months | 0.682256E+09 | 0.530878E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8948879.55 | 0.117761E+10 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217343E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192129E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133276E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1376073.36 | 0.127476E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2540525.08 | 0.628168E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12659369.12 | 0.340725E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14632096.57 | 0.249982E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3898452.01 | 0.353145E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79500.39 | 0.610906E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901830E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156000E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234428E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35186016.53 | 0.136913E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249982E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14632096.57 | 0.234428E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274371E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239480E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166746E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2187735.63 | 0.157931E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3311256.63 | 0.794828E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16303516.83 | 0.432040E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18683630.95 | 0.317159E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5139130.29 | 0.443606E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103277.04 | 0.754549E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108895E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190524E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293934E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45728547.37 | 0.170610E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317159E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18683630.95 | 0.293934E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290134E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250686E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173588E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62561.93 | 0.161606E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2255900.48 | 0.832918E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14616206.14 | 0.456528E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13099334.01 | 0.337266E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3817162.55 | 0.467399E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31079.99 | 0.774060E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109335E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193567E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307900E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33882245.10 | 0.177363E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337266E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14616206.14 | 0.307900E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 18520.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 18520.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 18520.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 18520.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 18520.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 18520.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 18520.31 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 18520.31 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 18520.31 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 18520.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 18520.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 18520.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-08:09 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3479.85 | 04-JAN-05:51 |
February | 1306.65 | 01-FEB-10:09 | 1038.79 | 02-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4283.37 | 12-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 962.01 | 03-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2150.10 | 15-MAR-04:51 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.27 | 23-APR-16:00 | 1646.93 | 01-APR-19:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.17 | 24-MAY-15:00 | 913.02 | 29-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.84 | 29-JUN-21:03 | 614.17 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.15 | 23-JUL-14:56 | 619.10 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 869.70 | 31-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.91 | 08-AUG-16:00 | 803.22 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 886.83 | 19-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.03 | 01-SEP-15:00 | 1026.53 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 1156.07 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1449.59 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2270.22 | 21-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:19 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3492.51 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 614.17 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 262.15 | 4283.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 739.79 | 02-JAN-08:09 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2371.96 | 04-JAN-05:51 |
February | 827.22 | 01-FEB-10:09 | 668.53 | 02-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2855.56 | 12-FEB-22:58 |
March | 827.22 | 01-MAR-10:09 | 616.86 | 03-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1433.41 | 15-MAR-04:51 |
April | 827.22 | 03-APR-09:09 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.74 | 23-APR-15:50 | 1095.41 | 01-APR-19:00 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.78 | 24-MAY-15:00 | 638.83 | 14-MAY-08:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.06 | 24-JUN-17:02 | 404.89 | 20-JUN-04:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.97 | 23-JUL-14:56 | 404.08 | 06-JUL-22:00 |
August | 827.22 | 01-AUG-09:09 | 522.00 | 31-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.94 | 08-AUG-16:00 | 540.50 | 27-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 521.10 | 19-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 01-SEP-15:00 | 676.45 | 20-SEP-01:00 |
October | 827.22 | 02-OCT-09:09 | 729.41 | 31-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 965.88 | 31-OCT-21:03 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 06-NOV-16:49 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1512.09 | 21-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-16:19 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2328.88 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.08 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 182.97 | 2855.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-08:09 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3560.30 | 04-JAN-05:51 |
February | 1306.65 | 01-FEB-10:09 | 998.91 | 02-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4283.37 | 12-FEB-22:58 |
March | 1306.65 | 01-MAR-10:09 | 945.15 | 03-MAR-16:00 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2153.01 | 15-MAR-04:51 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.55 | 23-APR-16:30 | 1832.32 | 16-APR-12:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.17 | 24-MAY-15:00 | 926.58 | 29-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.72 | 29-JUN-16:00 | 612.99 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.36 | 23-JUL-14:56 | 620.41 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 860.45 | 31-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.91 | 08-AUG-16:00 | 818.62 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 873.70 | 19-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.94 | 01-SEP-15:00 | 1027.90 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 1153.17 | 31-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1450.67 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2270.28 | 21-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:19 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3493.34 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 612.99 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 263.36 | 4283.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2371.75 | 04-JAN-05:51 |
February | 827.17 | 01-FEB-10:09 | 614.43 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2855.56 | 12-FEB-22:58 |
March | 827.17 | 01-MAR-10:09 | 620.24 | 13-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1433.58 | 15-MAR-04:51 |
April | 827.17 | 03-APR-09:09 | 498.99 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1104.46 | 01-APR-19:00 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.78 | 24-MAY-15:00 | 621.04 | 29-MAY-18:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.15 | 29-JUN-16:00 | 407.92 | 20-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.05 | 23-JUL-14:56 | 460.22 | 06-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 560.69 | 31-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.94 | 08-AUG-16:00 | 547.10 | 27-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 576.68 | 19-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 01-SEP-15:00 | 673.88 | 20-SEP-01:00 |
October | 827.17 | 02-OCT-09:09 | 732.10 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 965.63 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 06-NOV-16:49 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1511.74 | 21-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:19 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2328.88 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.92 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 175.05 | 2855.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-08:09 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1905.58 | 04-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1032.81 | 02-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2273.84 | 12-FEB-22:54 |
March | 1306.65 | 01-MAR-10:09 | 952.97 | 03-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1155.37 | 15-MAR-04:57 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.27 | 23-APR-16:00 | 924.52 | 01-APR-19:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.89 | 24-MAY-15:00 | 490.67 | 20-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.03 | 24-JUN-17:02 | 335.52 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.68 | 23-JUL-15:00 | 337.52 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 856.67 | 31-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.61 | 08-AUG-16:00 | 456.86 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 874.42 | 19-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 | 01-SEP-15:00 | 612.03 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 1155.52 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 776.85 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1336.37 | 22-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:19 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1854.52 | 16-DEC-05:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.52 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 206.27 | 2273.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 739.79 | 02-JAN-08:09 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1273.99 | 04-JAN-06:00 |
February | 827.22 | 01-FEB-10:09 | 666.04 | 02-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1515.89 | 12-FEB-22:52 |
March | 827.22 | 01-MAR-10:09 | 612.72 | 03-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 770.24 | 15-MAR-04:53 |
April | 827.22 | 03-APR-09:09 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.77 | 23-APR-16:00 | 625.28 | 01-APR-19:00 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.59 | 24-MAY-15:00 | 334.07 | 08-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.33 | 24-JUN-17:02 | 229.01 | 20-JUN-04:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.12 | 23-JUL-15:00 | 230.63 | 06-JUL-22:00 |
August | 827.22 | 01-AUG-09:09 | 514.09 | 31-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.41 | 08-AUG-16:00 | 319.79 | 27-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 512.84 | 19-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 01-SEP-15:00 | 404.75 | 20-SEP-01:00 |
October | 827.22 | 02-OCT-09:09 | 729.01 | 31-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 517.77 | 31-OCT-21:03 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 06-NOV-16:49 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 885.05 | 22-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-16:19 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1236.34 | 16-DEC-05:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.01 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 108.77 | 1515.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-08:09 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 72906.99 | 06-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 990.57 | 02-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 70453.94 | 14-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 935.17 | 03-MAR-16:00 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 56641.74 | 16-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.95 | 23-APR-15:56 | 43918.74 | 05-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6106.18 | 25-MAY-17:00 | 30127.52 | 01-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11982.75 | 29-JUN-16:03 | 15070.01 | 02-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6248.92 | 28-JUL-16:10 | 12441.60 | 18-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 846.91 | 31-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7167.16 | 08-AUG-16:05 | 15133.89 | 25-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 860.57 | 19-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2161.60 | 01-SEP-16:10 | 24022.60 | 06-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 1152.44 | 31-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 38408.02 | 30-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 50336.67 | 29-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:19 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 64866.82 | 20-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12441.60 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 11982.75 | 72906.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1273.99 | 04-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 610.04 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1515.89 | 12-FEB-22:52 |
March | 827.17 | 01-MAR-10:09 | 616.19 | 13-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 770.26 | 15-MAR-04:51 |
April | 827.17 | 03-APR-09:09 | 456.05 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.11 | 23-APR-15:54 | 631.94 | 01-APR-19:00 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.59 | 24-MAY-15:00 | 331.65 | 20-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.10 | 29-JUN-16:00 | 227.63 | 20-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.75 | 23-JUL-14:56 | 264.88 | 06-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 554.69 | 31-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.41 | 08-AUG-16:00 | 327.30 | 27-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 571.19 | 19-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 01-SEP-15:00 | 406.07 | 20-SEP-01:00 |
October | 827.17 | 02-OCT-09:09 | 731.84 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 517.53 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 06-NOV-16:49 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 884.40 | 22-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:19 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1236.34 | 16-DEC-05:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.63 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 94.75 | 1515.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-08:09 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2956.96 | 04-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1038.78 | 02-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3522.94 | 12-FEB-22:52 |
March | 1306.65 | 01-MAR-10:09 | 962.00 | 03-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1810.04 | 15-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.66 | 23-APR-15:51 | 1464.22 | 01-APR-19:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 24-MAY-15:00 | 781.32 | 08-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.13 | 24-JUN-17:02 | 541.57 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.45 | 23-JUL-14:46 | 531.46 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 869.68 | 31-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.17 | 08-AUG-16:00 | 711.91 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 886.82 | 19-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.51 | 01-SEP-15:00 | 921.11 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 1156.07 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1213.26 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1987.38 | 22-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:19 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2905.68 | 16-DEC-05:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 531.46 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 209.45 | 3522.94 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 739.79 | 02-JAN-08:09 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1995.69 | 04-JAN-06:00 |
February | 805.43 | 01-FEB-08:09 | 668.53 | 02-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2347.09 | 12-FEB-22:52 |
March | 805.43 | 01-MAR-08:09 | 616.85 | 03-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1206.68 | 15-MAR-04:53 |
April | 805.43 | 03-APR-07:10 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.28 | 23-APR-16:10 | 982.41 | 16-APR-12:00 |
May | 805.43 | 01-MAY-07:10 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 | 24-MAY-15:00 | 551.09 | 14-MAY-08:00 |
June | 805.43 | 01-JUN-07:10 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.26 | 24-JUN-17:02 | 357.42 | 20-JUN-04:00 |
July | 805.43 | 03-JUL-07:10 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.83 | 23-JUL-14:46 | 348.21 | 06-JUL-22:00 |
August | 805.43 | 01-AUG-07:10 | 521.99 | 31-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.78 | 08-AUG-16:00 | 478.51 | 27-AUG-06:00 |
September | 805.43 | 01-SEP-07:10 | 521.09 | 19-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.01 | 01-SEP-15:00 | 606.78 | 20-SEP-01:00 |
October | 805.43 | 02-OCT-07:10 | 729.41 | 31-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 808.42 | 31-OCT-21:03 |
November | 805.43 | 01-NOV-07:10 | 739.79 | 06-NOV-16:49 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1312.85 | 22-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 739.79 | 01-DEC-16:19 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1937.11 | 16-DEC-05:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.21 | |||||
Maximum of Months | 805.43 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 149.28 | 2347.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-08:09 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2993.55 | 04-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 998.91 | 02-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3528.63 | 12-FEB-22:52 |
March | 1306.65 | 01-MAR-10:09 | 945.14 | 03-MAR-16:00 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1810.04 | 15-MAR-04:53 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.31 | 23-APR-16:08 | 1648.45 | 16-APR-12:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 24-MAY-15:00 | 791.53 | 29-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.38 | 24-JUN-17:02 | 541.13 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.43 | 23-JUL-15:00 | 534.63 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 860.43 | 31-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.16 | 08-AUG-16:00 | 724.39 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 873.68 | 19-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.43 | 01-SEP-15:00 | 921.98 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 1153.16 | 31-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1213.99 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1987.10 | 22-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:19 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2905.69 | 16-DEC-05:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.63 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 191.43 | 3528.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1995.69 | 04-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 614.43 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2347.76 | 12-FEB-22:52 |
March | 827.17 | 01-MAR-10:09 | 620.24 | 13-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1206.68 | 15-MAR-04:53 |
April | 827.17 | 03-APR-09:09 | 498.98 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.82 | 23-APR-16:04 | 980.15 | 01-APR-19:00 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 | 24-MAY-15:00 | 530.70 | 29-MAY-18:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.06 | 29-JUN-16:00 | 360.12 | 20-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.76 | 23-JUL-14:44 | 392.26 | 06-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 560.68 | 31-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.78 | 08-AUG-16:00 | 484.32 | 27-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 576.67 | 19-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.01 | 01-SEP-15:00 | 606.27 | 20-SEP-01:00 |
October | 827.17 | 02-OCT-09:09 | 732.10 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 808.28 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 06-NOV-16:49 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1311.47 | 22-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:19 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1937.11 | 16-DEC-05:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.12 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 144.76 | 2347.76 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3739.60 | 04-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4807.78 | 12-FEB-22:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2372.83 | 15-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.68 | 23-APR-16:00 | 2064.82 | 01-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.37 | 24-MAY-15:00 | 1068.96 | 08-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.35 | 24-JUN-17:02 | 728.21 | 20-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.78 | 23-JUL-15:00 | 705.29 | 06-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.89 | 08-AUG-16:00 | 979.60 | 27-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.69 | 01-SEP-15:00 | 1278.57 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1596.36 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2866.39 | 22-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3762.84 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 705.29 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.78 | 4807.78 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4771.60 | 04-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5891.51 | 12-FEB-22:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2986.51 | 15-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.23 | 23-APR-16:00 | 2556.81 | 01-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.88 | 24-MAY-15:00 | 1350.53 | 20-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.04 | 24-JUN-17:02 | 926.47 | 20-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.50 | 23-JUL-15:00 | 896.48 | 06-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.84 | 08-AUG-16:00 | 1236.70 | 27-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.81 | 01-SEP-15:00 | 1597.68 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1971.40 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3506.39 | 22-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4703.38 | 16-DEC-05:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 896.48 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.50 | 5891.51 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5021.94 | 04-JAN-05:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6049.78 | 12-FEB-22:56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3066.18 | 15-MAR-04:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.98 | 23-APR-16:00 | 2562.77 | 01-APR-18:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.56 | 24-MAY-15:00 | 1440.05 | 29-MAY-18:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.20 | 29-JUN-16:00 | 905.46 | 20-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.66 | 15-JUL-17:03 | 884.76 | 06-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.69 | 08-AUG-16:00 | 1216.47 | 27-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.43 | 01-SEP-16:00 | 1545.06 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2116.15 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3327.15 | 21-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4837.15 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 884.76 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.66 | 6049.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7561.02 | 27-JAN-16:50 | 18105.02 | 16629.52 | 44184.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9662.80 | 10-FEB-17:00 | 6035.01 | 5543.17 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16588.84 | 30-MAR-07:06 | 60350.08 | 55431.73 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40458.43 | 24-APR-05:02 | 3176.32 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45339.22 | 30-MAY-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 43433.91 | 26-JUN-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 45378.72 | 05-JUL-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43989.65 | 28-AUG-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43510.56 | 05-SEP-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40962.38 | 23-OCT-05:02 | 3176.32 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15681.83 | 02-NOV-07:07 | 60350.08 | 55431.73 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8602.58 | 01-DEC-16:20 | 6035.01 | 5543.17 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7561.02 | 0.00 | 2463.50 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45378.72 | 60350.08 | 55431.73 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1732.73 |
February | 537.51 | 04-FEB-17:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.75 |
March | 1539.02 | 31-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 354.56 |
April | 4804.42 | 13-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.64 |
May | 9848.55 | 18-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 0.00 |
June | 11212.19 | 30-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.52 | 0.00 |
July | 10586.36 | 24-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.84 | 0.00 |
August | 9703.25 | 08-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.00 | 0.00 |
September | 8270.28 | 01-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 | 0.00 |
October | 3475.96 | 20-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.19 |
November | 993.22 | 01-NOV-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.61 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1813.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11212.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.52 | 1813.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2759.74 | 28-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1688.77 |
February | 3064.21 | 25-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2261.03 | 16-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1475.82 |
April | 2328.77 | 26-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 540.82 |
May | 4383.25 | 18-MAY-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.84 | 0.00 |
June | 5336.82 | 30-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.67 | 0.00 |
July | 5795.27 | 24-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.84 |
August | 4476.27 | 08-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.84 | 0.00 |
September | 4335.98 | 01-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.63 | 0.00 |
October | 2516.77 | 25-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2106.42 | 29-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 848.55 |
December | 2193.54 | 08-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1370.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2106.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.84 | 1688.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5046.28 | 26-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.65 |
February | 4841.14 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3989.17 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3178.03 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4600.35 | 18-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 | 0.00 |
June | 6372.85 | 30-JUN-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.49 | 0.00 |
July | 6209.06 | 24-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.21 | 0.00 |
August | 4877.72 | 08-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.89 | 0.00 |
September | 4563.88 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.51 | 0.00 |
October | 3001.23 | 25-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2646.03 | 10-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.43 |
December | 4103.10 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2646.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6372.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.89 | 456.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6005.75 | 27-JAN-16:47 | 18105.02 | 16629.52 | 21430.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6521.17 | 08-FEB-16:40 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7371.38 | 29-MAR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12037.48 | 14-APR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32302.81 | 30-MAY-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32144.94 | 26-JUN-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33014.05 | 05-JUL-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31983.87 | 28-AUG-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30990.68 | 01-SEP-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12098.32 | 20-OCT-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7083.51 | 17-NOV-16:20 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5960.53 | 01-DEC-16:20 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5960.53 | 0.00 | 2463.50 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33014.05 | 18105.02 | 16629.52 | 21430.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5718.55 | 27-JAN-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6476.92 | 08-FEB-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7290.37 | 29-MAR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11650.82 | 14-APR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31902.83 | 26-MAY-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32134.78 | 19-JUN-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34008.35 | 24-JUL-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32091.69 | 09-AUG-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21918.35 | 01-SEP-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11367.86 | 20-OCT-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6843.85 | 17-NOV-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5547.90 | 28-DEC-15:50 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5547.90 | 0.00 | 2463.50 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34008.35 | 6035.01 | 5543.17 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1038.33 | 14-JAN-17:01 | 468.72 | 454.47 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.60 |
February | 1050.61 | 11-FEB-17:02 | 334.80 | 297.52 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.22 |
March | 1427.61 | 31-MAR-16:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.53 |
April | 2685.98 | 18-APR-14:50 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.22 |
May | 5968.66 | 18-MAY-15:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 32.54 | 0.00 |
June | 7347.92 | 29-JUN-15:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 146.64 | 0.00 |
July | 9743.43 | 23-JUL-15:32 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 170.57 | 0.00 |
August | 6197.09 | 08-AUG-15:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 99.55 | 0.00 |
September | 5178.66 | 01-SEP-15:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 | 0.00 |
October | 2085.24 | 22-OCT-14:42 | 334.80 | 200.13 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.70 |
November | 1427.13 | 01-NOV-15:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.01 |
December | 1048.03 | 30-DEC-17:02 | 334.80 | 324.62 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1038.33 | 334.80 | 200.13 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9743.43 | 1272.23 | 720.41 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 170.57 | 328.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1005.29 | 14-JAN-17:01 | 296.74 | 287.71 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.78 |
February | 1336.44 | 28-FEB-10:25 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.91 |
March | 2332.28 | 31-MAR-09:45 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.75 |
April | 6484.88 | 18-APR-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.87 |
May | 11436.22 | 21-MAY-09:02 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.56 |
June | 15057.57 | 25-JUN-08:12 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.63 |
July | 14725.19 | 23-JUL-09:32 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 |
August | 11652.45 | 20-AUG-09:32 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.38 |
September | 8339.84 | 01-SEP-09:10 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 |
October | 3711.20 | 19-OCT-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.48 |
November | 1369.54 | 16-NOV-10:05 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.06 |
December | 1013.02 | 16-DEC-17:02 | 254.35 | 246.61 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1005.29 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | |
Maximum of Months | 15057.57 | 1654.44 | 912.16 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6080.13 | 27-JAN-14:00 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8823.17 | 28-FEB-14:20 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.98 |
March | 9580.21 | 31-MAR-14:00 | 2613.31 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.79 |
April | 13148.07 | 23-APR-13:43 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.89 |
May | 12479.53 | 18-MAY-13:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 | 0.00 |
June | 16648.94 | 18-JUN-14:13 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.48 |
July | 19296.89 | 23-JUL-12:52 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 88.58 | 0.00 |
August | 19255.96 | 27-AUG-14:42 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.83 |
September | 19149.49 | 04-SEP-12:52 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.72 |
October | 21292.35 | 22-OCT-13:21 | 468.72 | 280.18 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.85 |
November | 8030.54 | 17-NOV-13:15 | 5088.93 | 2881.64 | 6023.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.83 |
December | 3247.63 | 02-DEC-13:30 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3247.63 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21292.35 | 5088.93 | 2881.64 | 6023.53 | 0.00 | 0.00 | 0.00 | 0.00 | 88.58 | 616.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1499.64 | 27-JAN-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2166.54 | 08-FEB-16:20 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.63 |
March | 4659.56 | 31-MAR-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.23 |
April | 16348.02 | 23-APR-16:22 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.35 |
May | 14183.46 | 14-MAY-16:42 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.42 |
June | 16310.49 | 17-JUN-17:42 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.68 |
July | 16577.10 | 16-JUL-16:52 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.74 |
August | 16784.17 | 27-AUG-17:22 | 0.00 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.81 |
September | 13493.52 | 03-SEP-17:22 | 0.00 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.79 |
October | 5422.16 | 19-OCT-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 |
November | 1743.60 | 17-NOV-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.69 |
December | 1132.92 | 16-DEC-17:02 | 254.33 | 246.60 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1132.92 | 0.00 | 126.69 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16784.17 | 805.38 | 456.05 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 976.66 | 28-JAN-17:02 | 401.76 | 389.54 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.87 |
February | 983.65 | 11-FEB-17:02 | 334.80 | 296.29 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.57 |
March | 1196.04 | 31-MAR-16:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.52 |
April | 2023.23 | 23-APR-18:32 | 0.00 | 288.72 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 36.47 | 0.00 |
May | 4126.83 | 26-MAY-13:30 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.71 |
June | 5586.35 | 29-JUN-15:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 78.36 | 0.00 |
July | 7211.67 | 24-JUL-06:03 | 1071.35 | 960.53 | 2677.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.66 |
August | 5153.74 | 09-AUG-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 0.00 |
September | 4345.84 | 01-SEP-15:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 7.93 | 0.00 |
October | 2027.72 | 22-OCT-14:42 | 334.80 | 200.13 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.86 |
November | 1372.95 | 01-NOV-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.11 |
December | 987.04 | 30-DEC-17:02 | 334.80 | 324.62 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 976.66 | 0.00 | 200.13 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7211.67 | 1306.65 | 960.53 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 78.36 | 223.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 838.16 | 21-JAN-17:02 | 211.95 | 205.51 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.14 |
February | 992.32 | 28-FEB-10:25 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.72 |
March | 1354.92 | 31-MAR-10:10 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.79 |
April | 4193.78 | 18-APR-09:40 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.13 |
May | 6330.13 | 18-MAY-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 | 0.00 |
June | 11931.55 | 18-JUN-10:42 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.87 |
July | 9342.81 | 31-JUL-06:02 | 847.82 | 760.12 | 2118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.45 |
August | 11557.41 | 13-AUG-10:12 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.18 |
September | 6200.86 | 01-SEP-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.48 |
October | 2897.53 | 19-OCT-08:35 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.98 |
November | 1183.84 | 17-NOV-10:10 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.46 |
December | 842.74 | 16-DEC-17:02 | 254.35 | 246.61 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 838.16 | 211.95 | 126.70 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11931.55 | 1654.44 | 912.16 | 2118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 | 180.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1342.14 | 21-JAN-12:00 | 401.76 | 240.13 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.82 |
February | 1629.47 | 04-FEB-14:40 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.80 |
March | 2262.40 | 18-MAR-13:30 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.67 |
April | 10026.85 | 23-APR-15:12 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.90 |
May | 12316.16 | 18-MAY-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 4527.04 | 0.00 |
June | 14102.15 | 29-JUN-16:10 | 1607.03 | 1600.90 | 3346.41 | 0.00 | 0.00 | 0.00 | 0.00 | 10822.22 | 0.00 |
July | 15442.89 | 16-JUL-14:02 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.69 |
August | 15300.60 | 13-AUG-13:32 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.15 |
September | 16608.45 | 04-SEP-13:22 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.80 |
October | 17015.53 | 22-OCT-13:21 | 468.72 | 280.18 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.92 |
November | 2870.29 | 17-NOV-13:50 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2562.26 |
December | 1975.62 | 02-DEC-13:50 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1342.14 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17015.53 | 1607.03 | 1600.90 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 10822.22 | 2562.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1151.42 | 27-JAN-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1463.80 | 08-FEB-16:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.04 |
March | 3039.00 | 28-MAR-17:00 | 254.33 | 253.36 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.75 |
April | 12998.84 | 23-APR-17:51 | 0.00 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.89 |
May | 13014.10 | 21-MAY-17:32 | 0.00 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.71 |
June | 12935.66 | 17-JUN-18:22 | 0.00 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.66 |
July | 13797.57 | 16-JUL-16:41 | 339.11 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.76 |
August | 12296.10 | 05-AUG-17:04 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.89 |
September | 14050.51 | 03-SEP-17:11 | 0.00 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.50 |
October | 4564.90 | 19-OCT-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.42 |
November | 1449.70 | 17-NOV-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.64 |
December | 924.54 | 02-DEC-17:02 | 254.33 | 246.60 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 924.54 | 0.00 | 152.03 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14050.51 | 805.38 | 456.05 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 954.05 | 28-JAN-17:02 | 401.76 | 389.54 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.28 |
February | 1077.22 | 08-FEB-16:40 | 1272.23 | 898.59 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.94 |
March | 1377.94 | 29-MAR-15:50 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.03 |
April | 2771.14 | 14-APR-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.86 |
May | 5538.54 | 26-MAY-13:30 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.27 |
June | 8164.04 | 28-JUN-06:03 | 803.52 | 720.40 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9613.93 | 23-JUL-16:01 | 602.64 | 360.23 | 4517.68 | 0.00 | 0.00 | 0.00 | 0.00 | 104.84 | 0.00 |
August | 5712.28 | 09-AUG-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 0.00 |
September | 4847.50 | 01-SEP-15:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 | 0.00 |
October | 2155.22 | 20-OCT-15:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.79 |
November | 1370.26 | 01-NOV-15:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.56 |
December | 961.38 | 30-DEC-17:02 | 334.80 | 324.62 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 954.05 | 334.80 | 324.62 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9613.93 | 1306.65 | 898.59 | 4517.68 | 0.00 | 0.00 | 0.00 | 0.00 | 104.84 | 351.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1010.78 | 21-JAN-17:02 | 211.95 | 205.51 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.26 |
February | 1428.84 | 28-FEB-10:00 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.24 |
March | 3115.20 | 31-MAR-10:10 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.45 |
April | 6831.77 | 18-APR-09:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.58 |
May | 11455.15 | 21-MAY-10:13 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.52 |
June | 14817.63 | 25-JUN-08:12 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.82 |
July | 15935.80 | 23-JUL-09:21 | 296.74 | 177.38 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.38 |
August | 12586.23 | 06-AUG-08:42 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.03 |
September | 10056.41 | 10-SEP-09:32 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.02 |
October | 4436.32 | 19-OCT-09:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.10 |
November | 1524.46 | 16-NOV-09:50 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.53 |
December | 1016.33 | 16-DEC-17:02 | 254.35 | 246.61 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1010.78 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.38 | |
Maximum of Months | 15935.80 | 1610.86 | 912.16 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6789.25 | 27-JAN-13:40 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9024.91 | 28-FEB-13:40 | 2544.47 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.84 |
March | 9959.98 | 31-MAR-13:50 | 2613.31 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.05 |
April | 13455.87 | 23-APR-14:02 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.25 |
May | 15405.41 | 21-MAY-12:53 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.18 |
June | 16642.15 | 18-JUN-13:53 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 |
July | 18693.03 | 23-JUL-12:02 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 12.43 | 0.00 |
August | 17682.12 | 13-AUG-13:22 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.91 |
September | 18521.26 | 03-SEP-13:52 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.62 |
October | 18176.27 | 22-OCT-12:52 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.67 |
November | 8833.58 | 17-NOV-13:03 | 7633.40 | 4322.46 | 9035.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.41 |
December | 4214.07 | 02-DEC-13:30 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4214.07 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18693.03 | 7633.40 | 4322.46 | 9035.30 | 0.00 | 0.00 | 0.00 | 0.00 | 12.43 | 350.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1495.22 | 27-JAN-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2343.74 | 08-FEB-16:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.84 |
March | 4815.85 | 31-MAR-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 |
April | 14726.65 | 23-APR-16:42 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.46 |
May | 15723.30 | 21-MAY-16:52 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.32 |
June | 15159.78 | 17-JUN-17:42 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.87 |
July | 16928.06 | 16-JUL-16:41 | 339.11 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.93 |
August | 15032.44 | 13-AUG-17:22 | 0.00 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.90 |
September | 16302.05 | 03-SEP-17:11 | 0.00 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.23 |
October | 5388.21 | 19-OCT-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.92 |
November | 1730.54 | 17-NOV-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.74 |
December | 1167.47 | 20-DEC-15:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1167.47 | 0.00 | 126.69 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16928.06 | 805.38 | 456.05 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.93 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.236952E+12 | 282107.28 | 02-JAN-08:09 | 0.602728E+11 | 191502.39 | 06-JAN-07:00 |
February | 0.172393E+12 | 237169.13 | 13-FEB-07:10 | 0.275047E+11 | 178947.81 | 14-FEB-07:30 |
March | 0.161232E+12 | 221578.39 | 06-MAR-07:10 | 0.142290E+11 | 130302.93 | 15-MAR-06:00 |
April | 0.112864E+12 | 157197.81 | 03-APR-06:10 | 0.104218E+11 | 14517.81 | 05-APR-06:19 |
May | 0.119867E+12 | 146476.58 | 18-MAY-15:09 | 0.104815E+11 | 11610.98 | 02-MAY-11:50 |
June | 0.136845E+12 | 171640.67 | 29-JUN-15:50 | 0.990820E+10 | 9574.54 | 02-JUN-11:09 |
July | 0.146838E+12 | 183773.31 | 05-JUL-12:09 | 0.937720E+10 | 9417.64 | 03-JUL-11:30 |
August | 0.140920E+12 | 158417.88 | 08-AUG-15:39 | 0.978508E+10 | 9335.97 | 03-AUG-11:09 |
September | 0.107475E+12 | 141936.39 | 01-SEP-15:50 | 0.910685E+10 | 9351.21 | 26-SEP-11:09 |
October | 0.116913E+12 | 170201.77 | 30-OCT-06:10 | 0.977993E+10 | 13254.64 | 30-OCT-06:10 |
November | 0.150755E+12 | 225078.79 | 27-NOV-07:10 | 0.114302E+11 | 22713.19 | 29-NOV-07:30 |
December | 0.222415E+12 | 270618.78 | 26-DEC-08:09 | 0.396414E+11 | 169038.57 | 20-DEC-07:40 |
Annual Sum or Average | 0.182547E+13 | 0.221939E+12 | ||||
Minimum of Months | 0.107475E+12 | 141936.39 | 0.910685E+10 | 9335.97 | ||
Maximum of Months | 0.236952E+12 | 282107.28 | 0.602728E+11 | 191502.39 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.241111E+11 | 0.824439E+10 | 0.641572E+11 | 0.109154E+10 | 0.677880E+10 | 1312252.65 | 0.129047E+12 | 2044986.42 | 0.00 | 0.00 | 0.351878E+10 | 0.00 | 0.00 |
February | 0.214373E+11 | 0.666445E+10 | 0.580684E+11 | 0.987351E+09 | 0.525697E+10 | 1186778.30 | 0.767554E+11 | 7743926.68 | 0.00 | 0.00 | 0.321438E+10 | 0.00 | 0.00 |
March | 0.251836E+11 | 0.631707E+10 | 0.666107E+11 | 0.114318E+10 | 0.534226E+10 | 1343621.24 | 0.529369E+11 | 17413713.54 | 0.00 | 0.00 | 0.367907E+10 | 0.00 | 0.00 |
April | 0.223255E+11 | 0.504573E+10 | 0.619407E+11 | 0.105054E+10 | 0.544359E+10 | 1267813.82 | 0.139934E+11 | 0.109297E+10 | 0.00 | 0.00 | 0.196998E+10 | 0.00 | 0.00 |
May | 0.239313E+11 | 0.434616E+10 | 0.653840E+11 | 0.111681E+10 | 0.994595E+10 | 1327936.95 | 0.163525E+10 | 0.128678E+11 | 0.00 | 0.00 | 0.638820E+09 | 0.00 | 0.00 |
June | 0.237617E+11 | 0.376616E+10 | 0.641577E+11 | 0.109951E+10 | 0.139069E+11 | 1296568.36 | 0.373217E+09 | 0.291869E+11 | 0.00 | 0.00 | 0.591545E+09 | 0.00 | 0.00 |
July | 0.222804E+11 | 0.407041E+10 | 0.631525E+11 | 0.106754E+10 | 0.166897E+11 | 1299182.41 | 98077234.58 | 0.384372E+11 | 0.00 | 0.00 | 0.104060E+10 | 0.00 | 0.00 |
August | 0.249232E+11 | 0.479029E+10 | 0.666107E+11 | 0.114304E+10 | 0.135034E+11 | 1343621.24 | 0.290371E+09 | 0.291171E+11 | 0.00 | 0.00 | 0.540450E+09 | 0.00 | 0.00 |
September | 0.224063E+11 | 0.564593E+10 | 0.619118E+11 | 0.105017E+10 | 0.803067E+10 | 1267813.82 | 0.167592E+10 | 0.650430E+10 | 0.00 | 0.00 | 0.248244E+09 | 0.00 | 0.00 |
October | 0.235374E+11 | 0.694062E+10 | 0.641717E+11 | 0.109113E+10 | 0.521544E+10 | 1312252.65 | 0.130105E+11 | 0.905721E+09 | 0.00 | 0.00 | 0.203891E+10 | 0.00 | 0.00 |
November | 0.237246E+11 | 0.768662E+10 | 0.627379E+11 | 0.107145E+10 | 0.479752E+10 | 1278270.02 | 0.475462E+11 | 0.149628E+09 | 0.00 | 0.00 | 0.303966E+10 | 0.00 | 0.00 |
December | 0.234711E+11 | 0.850114E+10 | 0.631380E+11 | 0.106840E+10 | 0.638223E+10 | 1299182.41 | 0.116370E+12 | 3694503.09 | 0.00 | 0.00 | 0.347957E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.281093E+12 | 0.720190E+11 | 0.762041E+12 | 0.129807E+11 | 0.101293E+12 | 15535293.87 | 0.453731E+12 | 0.118293E+12 | 0.00 | 0.00 | 0.240000E+11 | 0.00 | 0.00 |
Minimum of Months | 0.214373E+11 | 0.376616E+10 | 0.580684E+11 | 0.987351E+09 | 0.479752E+10 | 1186778.30 | 98077234.58 | 2044986.42 | 0.00 | 0.00 | 0.248244E+09 | 0.00 | 0.00 |
Maximum of Months | 0.251836E+11 | 0.850114E+10 | 0.666107E+11 | 0.114318E+10 | 0.166897E+11 | 1343621.24 | 0.129047E+12 | 0.384372E+11 | 0.00 | 0.00 | 0.367907E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.495472E+11 | 0.00 | 0.107256E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.176624E+11 | 0.00 | 0.984226E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.290867E+10 | 0.00 | 0.113203E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.187185E+09 | 0.00 | 0.102346E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 19108774.51 | 0.00 | 0.104624E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.990820E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.937720E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 266071.11 | 0.00 | 0.978481E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 5724635.79 | 0.00 | 0.910113E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.149283E+09 | 0.00 | 0.963064E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.166410E+10 | 0.00 | 0.976612E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.294143E+11 | 0.00 | 0.102271E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.101558E+12 | 0.00 | 0.120380E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.910113E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.495472E+11 | 0.00 | 0.113203E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28079.40 | 02-JAN-08:09 | 5557.43 | 01-JAN-06:10 | 47562.27 | 02-JAN-08:09 | 928.21 | 02-JAN-08:20 | 8403.56 | 02-JAN-06:19 | 0.73 | 02-JAN-06:10 | 226564.56 | 02-JAN-06:19 |
February | 26566.18 | 02-FEB-16:00 | 5557.43 | 01-FEB-06:10 | 47562.27 | 01-FEB-08:09 | 924.67 | 15-FEB-08:20 | 6571.69 | 13-FEB-07:10 | 0.73 | 01-FEB-07:10 | 190847.61 | 13-FEB-07:10 |
March | 25914.23 | 03-MAR-16:00 | 5557.43 | 01-MAR-06:10 | 47562.27 | 01-MAR-08:09 | 924.96 | 13-MAR-07:19 | 5979.88 | 06-MAR-06:19 | 0.73 | 01-MAR-07:10 | 182456.32 | 06-MAR-07:10 |
April | 23774.24 | 03-APR-07:10 | 5557.43 | 01-APR-05:10 | 47562.27 | 03-APR-07:10 | 922.02 | 03-APR-07:19 | 9953.19 | 13-APR-15:30 | 0.73 | 03-APR-06:10 | 118988.30 | 03-APR-06:10 |
May | 23688.37 | 01-MAY-07:10 | 5557.43 | 01-MAY-19:30 | 47562.27 | 01-MAY-07:10 | 921.90 | 01-MAY-07:19 | 27298.90 | 18-MAY-15:09 | 0.73 | 01-MAY-06:10 | 53392.48 | 01-MAY-06:10 |
June | 23688.37 | 01-JUN-07:10 | 5557.43 | 01-JUN-19:00 | 47562.27 | 01-JUN-07:10 | 921.90 | 01-JUN-07:19 | 30624.70 | 30-JUN-15:39 | 0.73 | 01-JUN-05:10 | 13349.68 | 02-JUN-06:10 |
July | 23688.37 | 03-JUL-07:10 | 5557.43 | 01-JUL-20:19 | 47562.27 | 03-JUL-07:10 | 921.90 | 03-JUL-07:19 | 35017.19 | 05-JUL-10:39 | 0.73 | 01-JUL-05:19 | 8801.36 | 18-JUL-06:19 |
August | 25027.49 | 31-AUG-07:10 | 5557.43 | 01-AUG-19:49 | 47562.27 | 01-AUG-07:10 | 923.82 | 31-AUG-07:19 | 28114.13 | 08-AUG-15:00 | 0.73 | 01-AUG-05:30 | 11490.64 | 18-AUG-06:19 |
September | 25165.11 | 19-SEP-07:10 | 5557.43 | 01-SEP-05:10 | 47562.27 | 01-SEP-07:10 | 924.02 | 19-SEP-07:19 | 25571.65 | 01-SEP-15:50 | 0.73 | 01-SEP-05:10 | 26279.66 | 28-SEP-06:10 |
October | 27939.81 | 31-OCT-07:10 | 5557.43 | 01-OCT-05:10 | 47562.27 | 02-OCT-07:10 | 928.01 | 31-OCT-07:19 | 10590.02 | 20-OCT-14:50 | 0.73 | 04-OCT-07:10 | 125849.05 | 30-OCT-06:10 |
November | 28079.40 | 06-NOV-16:49 | 5557.43 | 01-NOV-05:10 | 47562.27 | 01-NOV-07:10 | 927.95 | 01-NOV-07:19 | 5780.13 | 27-NOV-07:10 | 0.73 | 02-NOV-07:10 | 179397.10 | 27-NOV-07:10 |
December | 28079.40 | 01-DEC-16:19 | 5557.43 | 01-DEC-06:10 | 47562.27 | 01-DEC-08:09 | 928.21 | 26-DEC-08:20 | 7830.32 | 26-DEC-07:10 | 0.73 | 01-DEC-06:10 | 222110.57 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 23688.37 | 5557.43 | 47562.27 | 921.90 | 5780.13 | 0.73 | 8801.36 | |||||||
Maximum of Months | 28079.40 | 5557.43 | 47562.27 | 928.21 | 35017.19 | 0.73 | 226564.56 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 404.15 | 19-JAN-07:10 | 0.00 | 0.00 | 2722.67 | 02-JAN-08:50 | 0.00 | 0.00 |
February | 384.70 | 18-FEB-07:10 | 0.00 | 0.00 | 2722.67 | 04-FEB-17:10 | 0.00 | 0.00 |
March | 552.76 | 04-MAR-07:10 | 0.00 | 0.00 | 2722.67 | 02-MAR-08:30 | 0.00 | 0.00 |
April | 17201.74 | 23-APR-16:10 | 0.00 | 0.00 | 2722.67 | 01-APR-16:10 | 0.00 | 0.00 |
May | 50370.77 | 25-MAY-15:00 | 0.00 | 0.00 | 2722.67 | 02-MAY-06:19 | 0.00 | 0.00 |
June | 72422.54 | 29-JUN-15:00 | 0.00 | 0.00 | 2722.67 | 30-JUN-06:10 | 0.00 | 0.00 |
July | 80445.31 | 05-JUL-11:50 | 0.00 | 0.00 | 2722.67 | 22-JUL-16:10 | 0.00 | 0.00 |
August | 61191.36 | 31-AUG-12:50 | 0.00 | 0.00 | 2722.67 | 08-AUG-10:30 | 0.00 | 0.00 |
September | 48207.27 | 01-SEP-13:20 | 0.00 | 0.00 | 2722.67 | 01-SEP-14:20 | 0.00 | 0.00 |
October | 18711.95 | 19-OCT-14:00 | 0.00 | 0.00 | 2722.67 | 04-OCT-06:19 | 0.00 | 0.00 |
November | 7384.19 | 01-NOV-14:00 | 0.00 | 0.00 | 2722.67 | 02-NOV-06:19 | 0.00 | 0.00 |
December | 461.94 | 30-DEC-07:10 | 0.00 | 0.00 | 2722.67 | 01-DEC-08:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 384.70 | 0.00 | 0.00 | 2722.67 | 0.00 | 0.00 | ||
Maximum of Months | 80445.31 | 0.00 | 0.00 | 2722.67 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 282107.28 | 02-JAN-08:09 | 28079.40 | 47562.27 | 5557.43 | 901.53 | 5642.76 | 0.73 | 191640.49 | 0.00 | 0.00 |
February | 237169.13 | 13-FEB-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 6571.69 | 0.73 | 190847.61 | 0.00 | 0.00 |
March | 221578.39 | 06-MAR-07:10 | 8293.42 | 21853.28 | 0.00 | 255.94 | 5973.54 | 0.73 | 182456.32 | 22.50 | 0.00 |
April | 157197.81 | 03-APR-06:10 | 8948.90 | 21853.28 | 0.00 | 256.01 | 4210.53 | 0.73 | 118988.30 | 217.40 | 0.00 |
May | 146476.58 | 18-MAY-15:09 | 23688.37 | 43769.98 | 0.00 | 920.43 | 27298.90 | 0.73 | 0.00 | 48075.51 | 0.00 |
June | 171640.67 | 29-JUN-15:50 | 23688.37 | 43769.98 | 0.00 | 920.43 | 28872.94 | 0.73 | 0.00 | 71665.55 | 0.00 |
July | 183773.31 | 05-JUL-12:09 | 23688.37 | 44099.74 | 0.00 | 920.56 | 35017.19 | 0.73 | 0.00 | 80046.72 | 0.00 |
August | 158417.88 | 08-AUG-15:39 | 23688.37 | 43769.98 | 0.00 | 920.43 | 27814.35 | 0.73 | 0.00 | 59501.35 | 0.00 |
September | 141936.39 | 01-SEP-15:50 | 23688.37 | 43769.98 | 0.00 | 920.43 | 25571.65 | 0.73 | 0.00 | 45262.56 | 0.00 |
October | 170201.77 | 30-OCT-06:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 4420.36 | 0.73 | 125849.05 | 182.53 | 0.00 |
November | 225078.79 | 27-NOV-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 5780.13 | 0.73 | 179397.10 | 151.72 | 0.00 |
December | 270618.78 | 26-DEC-08:09 | 28079.40 | 47562.27 | 5557.43 | 901.53 | 5594.64 | 0.73 | 180200.11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 141936.39 | 8293.42 | 21853.28 | 0.00 | 255.94 | 4210.53 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 282107.28 | 28079.40 | 47562.27 | 5557.43 | 920.56 | 35017.19 | 0.73 | 191640.49 | 80046.72 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 183919.64 | 06-JAN-07:40 | 0.00 | 12874.58 | 27-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 171905.67 | 14-FEB-07:19 | 0.00 | 13170.07 | 24-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 129146.93 | 15-MAR-06:00 | 0.00 | 13126.67 | 01-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 7395.55 | 05-APR-06:10 | 0.00 | 12615.66 | 04-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 1981.91 | 01-MAY-09:39 | 0.00 | 11610.98 | 02-MAY-11:50 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9574.54 | 02-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9417.64 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 443.45 | 19-AUG-06:10 | 0.00 | 9335.97 | 03-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 657.02 | 06-SEP-07:10 | 0.00 | 9351.21 | 26-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 5082.90 | 30-OCT-06:10 | 0.00 | 9478.45 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 15168.87 | 25-NOV-07:19 | 0.00 | 10513.78 | 28-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 161689.59 | 20-DEC-07:30 | 0.00 | 11989.44 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9335.97 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 183919.64 | 0.00 | 13170.07 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.34 | 0.83 | 19.53 | 0.00 | 19.53 | 0.00 | 19.53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.18 | 0.00 | 26.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.83 | 1.33 | 24.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.21 | 0.00 | 26.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 19.34 | 0.83 | 19.53 | 1.83 | 22.37 | 1.33 | 23.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.34 | 0.83 | 19.53 | 1.33 | 26.21 | 1.33 | 26.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 18.81 | 1.50 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.73 | 0.67 | 24.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.44 | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
December | 1.17 | 18.71 | 0.83 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
Annual Sum or Average | 3.33 | 18.81 | 2.50 | 19.08 | 0.67 | 19.66 | 0.67 | 20.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 19.44 | 1.50 | 19.44 | 0.67 | 24.73 | 0.67 | 24.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.17 | 18.33 | 7.67 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
February | 3.17 | 18.58 | 2.17 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
March | 1.33 | 18.49 | 0.83 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.65 | 0.33 | 24.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.44 | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
November | 1.17 | 18.63 | 0.83 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
December | 5.67 | 18.95 | 4.50 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
Annual Sum or Average | 21.67 | 18.56 | 16.17 | 18.85 | 0.33 | 18.90 | 0.33 | 18.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.17 | 19.44 | 7.67 | 19.44 | 0.33 | 24.65 | 0.33 | 24.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 121.67 | 16.42 | 66.33 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 |
February | 68.00 | 16.43 | 31.00 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
March | 25.17 | 16.64 | 11.33 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
April | 1.33 | 17.27 | 0.33 | 17.68 | 0.00 | 17.68 | 0.00 | 17.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 26.74 | 1.17 | 26.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.00 | 18.04 | 0.50 | 18.54 | 0.00 | 18.54 | 0.00 | 18.54 |
November | 26.17 | 15.95 | 10.50 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 |
December | 96.33 | 16.08 | 47.00 | 16.55 | 0.00 | 16.55 | 0.00 | 16.55 |
Annual Sum or Average | 339.67 | 16.32 | 167.00 | 16.81 | 1.33 | 16.84 | 1.17 | 16.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.67 | 18.04 | 66.33 | 18.54 | 1.33 | 26.74 | 1.17 | 26.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 68.67 | 14.60 | 19.50 | 14.67 | 0.00 | 14.67 | 0.00 | 14.67 |
February | 37.83 | 14.75 | 3.67 | 14.77 | 0.00 | 14.77 | 0.00 | 14.77 |
March | 14.17 | 15.14 | 1.50 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
April | 0.83 | 16.42 | 0.00 | 16.42 | 0.00 | 16.42 | 0.00 | 16.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.71 | 0.67 | 27.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.11 | 4.83 | 28.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.05 | 3.83 | 28.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.00 | 3.33 | 28.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 16.20 | 0.00 | 16.20 | 0.00 | 16.20 | 0.00 | 16.20 |
November | 20.50 | 15.00 | 4.83 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
December | 58.50 | 14.44 | 15.33 | 14.44 | 0.00 | 14.44 | 0.00 | 14.44 |
Annual Sum or Average | 200.83 | 14.67 | 44.83 | 14.69 | 12.83 | 15.35 | 12.67 | 15.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.67 | 16.42 | 19.50 | 16.42 | 4.83 | 28.11 | 4.83 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 59.33 | 14.93 | 15.33 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 |
February | 31.50 | 14.98 | 4.00 | 15.09 | 0.00 | 15.09 | 0.00 | 15.09 |
March | 10.67 | 15.25 | 1.67 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
April | 0.83 | 16.55 | 0.00 | 16.55 | 1.17 | 23.18 | 1.17 | 24.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.52 | 1.17 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.84 | 2.00 | 27.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.92 | 4.67 | 27.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.98 | 5.00 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.93 | 3.33 | 27.93 |
October | 0.50 | 17.33 | 0.17 | 17.85 | 1.67 | 25.15 | 1.67 | 26.37 |
November | 15.17 | 15.12 | 3.00 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 |
December | 50.33 | 14.71 | 11.17 | 14.80 | 0.00 | 14.80 | 0.00 | 14.80 |
Annual Sum or Average | 168.33 | 14.93 | 35.33 | 15.04 | 19.33 | 16.16 | 19.00 | 17.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | 0.00 | 14.80 |
Maximum of Months | 59.33 | 17.33 | 15.33 | 17.85 | 5.00 | 27.98 | 5.00 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 65.50 | 14.54 | 18.17 | 14.58 | 0.00 | 14.58 | 0.00 | 14.58 |
February | 37.67 | 14.71 | 5.83 | 14.72 | 0.00 | 14.72 | 0.00 | 14.72 |
March | 13.50 | 15.09 | 2.67 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
April | 1.00 | 16.61 | 0.00 | 16.61 | 1.33 | 23.37 | 0.83 | 24.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.17 | 1.67 | 28.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.11 | 1.00 | 28.09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.29 | 4.17 | 28.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.13 | 3.17 | 28.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.25 | 0.83 | 28.26 |
October | 0.33 | 16.22 | 0.00 | 16.22 | 0.00 | 16.22 | 0.00 | 16.22 |
November | 20.33 | 14.98 | 4.83 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
December | 57.67 | 14.40 | 14.50 | 14.38 | 0.00 | 14.38 | 0.00 | 14.38 |
Annual Sum or Average | 196.00 | 14.63 | 46.00 | 14.63 | 21.83 | 15.75 | 11.67 | 16.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.38 | 0.00 | 14.38 |
Maximum of Months | 65.50 | 16.61 | 18.17 | 16.61 | 7.83 | 28.29 | 4.17 | 28.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 87.83 | 18.26 | 67.67 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
February | 26.17 | 18.59 | 18.83 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
March | 10.83 | 18.67 | 8.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
April | 0.50 | 19.37 | 0.50 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.68 | 1.67 | 24.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.00 | 19.09 | 1.50 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
December | 54.00 | 17.66 | 39.50 | 18.03 | 0.00 | 18.03 | 0.00 | 18.03 |
Annual Sum or Average | 181.33 | 18.16 | 136.00 | 18.55 | 1.67 | 18.58 | 1.67 | 18.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.83 | 19.37 | 67.67 | 19.38 | 1.67 | 24.68 | 1.67 | 24.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.83 | 15.15 | 5.67 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
February | 5.00 | 15.97 | 0.33 | 15.91 | 0.00 | 15.91 | 0.00 | 15.91 |
March | 2.33 | 16.29 | 0.17 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.74 | 3.00 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.60 | 3.00 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.62 | 3.50 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
December | 19.50 | 15.08 | 6.00 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 |
Annual Sum or Average | 50.50 | 15.29 | 12.17 | 15.29 | 9.50 | 16.92 | 9.50 | 18.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.83 | 17.07 | 6.00 | 17.07 | 3.50 | 27.74 | 3.50 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 183.33 | 14.73 | 166.67 | 14.71 | 0.00 | 14.71 | 0.00 | 14.71 |
February | 111.50 | 15.12 | 108.83 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
March | 97.67 | 15.92 | 96.50 | 15.92 | 0.00 | 15.92 | 0.00 | 15.92 |
April | 42.33 | 17.17 | 42.33 | 17.17 | 0.83 | 17.27 | 0.83 | 17.37 |
May | 12.17 | 19.04 | 12.17 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 25.44 | 3.67 | 25.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.64 | 2.67 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.56 | 4.50 | 27.56 |
September | 11.00 | 19.73 | 11.00 | 19.73 | 4.00 | 20.96 | 4.00 | 21.86 |
October | 43.33 | 18.39 | 43.33 | 18.39 | 2.00 | 18.60 | 2.00 | 18.81 |
November | 69.50 | 16.74 | 68.83 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
December | 158.17 | 15.19 | 148.33 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
Annual Sum or Average | 729.00 | 15.75 | 698.00 | 15.75 | 17.67 | 15.89 | 17.67 | 16.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 | 0.00 | 14.71 |
Maximum of Months | 183.33 | 19.73 | 166.67 | 19.73 | 4.50 | 27.64 | 4.50 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.67 | 15.03 | 5.33 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 |
February | 4.17 | 16.11 | 0.00 | 16.11 | 0.00 | 16.11 | 0.00 | 16.11 |
March | 2.67 | 16.13 | 0.17 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.87 | 0.50 | 27.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.73 | 1.17 | 27.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.95 | 0.17 | 27.98 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.85 | 3.17 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.77 | 2.50 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.99 | 0.67 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
December | 20.00 | 14.99 | 6.50 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
Annual Sum or Average | 49.33 | 15.20 | 12.00 | 15.14 | 17.17 | 17.91 | 8.17 | 18.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 21.67 | 17.07 | 6.50 | 17.07 | 6.17 | 27.99 | 3.17 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 65.17 | 17.02 | 37.33 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 |
February | 25.67 | 17.16 | 13.00 | 17.72 | 0.00 | 17.72 | 0.00 | 17.72 |
March | 7.00 | 17.51 | 3.67 | 18.11 | 0.00 | 18.11 | 0.00 | 18.11 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 25.19 | 3.33 | 25.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.50 | 18.50 | 2.17 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
December | 52.17 | 16.49 | 28.50 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 |
Annual Sum or Average | 153.50 | 16.92 | 84.67 | 17.40 | 3.33 | 17.51 | 3.33 | 17.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.17 | 18.50 | 37.33 | 18.94 | 3.33 | 25.19 | 3.33 | 25.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.67 | 14.92 | 7.17 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
February | 12.33 | 15.28 | 0.83 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 |
March | 3.00 | 15.57 | 0.17 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.79 | 1.67 | 27.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.14 | 4.67 | 28.14 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.92 | 4.33 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.06 | 3.67 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.65 | 0.83 | 27.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.33 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 |
December | 33.83 | 14.82 | 8.67 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 |
Annual Sum or Average | 84.17 | 14.98 | 16.83 | 14.96 | 15.17 | 16.66 | 15.17 | 17.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.83 | 15.76 | 8.67 | 15.76 | 4.67 | 28.14 | 4.67 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.50 | 15.25 | 4.17 | 15.40 | 0.00 | 15.40 | 0.00 | 15.40 |
February | 8.00 | 15.59 | 0.67 | 15.62 | 0.00 | 15.62 | 0.00 | 15.62 |
March | 2.00 | 16.07 | 0.00 | 16.07 | 0.33 | 17.67 | 0.33 | 18.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.98 | 1.17 | 27.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.52 | 1.67 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.68 | 2.17 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.18 | 5.17 | 27.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.93 | 5.00 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.90 | 4.33 | 27.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.99 | 2.50 | 27.99 |
November | 1.17 | 16.63 | 0.00 | 16.63 | 0.00 | 16.63 | 0.00 | 16.63 |
December | 22.83 | 15.02 | 4.83 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 |
Annual Sum or Average | 58.50 | 15.26 | 9.67 | 15.32 | 22.50 | 18.39 | 22.33 | 20.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.04 | 0.00 | 15.04 |
Maximum of Months | 24.50 | 16.63 | 4.83 | 16.63 | 5.33 | 27.99 | 5.17 | 27.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 33.00 | 14.91 | 7.83 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
February | 13.00 | 15.27 | 2.17 | 15.26 | 0.00 | 15.26 | 0.00 | 15.26 |
March | 3.33 | 15.52 | 0.33 | 15.47 | 0.00 | 15.47 | 0.00 | 15.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.27 | 0.83 | 28.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.17 | 1.67 | 28.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.08 | 0.83 | 28.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.16 | 4.33 | 28.20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.98 | 3.33 | 27.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.19 | 0.83 | 28.21 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.67 | 16.06 | 0.00 | 16.06 | 0.00 | 16.06 | 0.00 | 16.06 |
December | 32.33 | 14.78 | 8.33 | 14.73 | 0.00 | 14.73 | 0.00 | 14.73 |
Annual Sum or Average | 83.33 | 14.97 | 18.67 | 14.94 | 22.33 | 17.30 | 11.83 | 18.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.00 | 16.06 | 8.33 | 16.06 | 8.00 | 28.27 | 4.33 | 28.27 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.43 | 254.83 | 21.17 | 254.83 | 21.04 |
February | 454.00 | 22.26 | 66.00 | 22.09 | 66.00 | 21.96 |
March | 514.00 | 23.03 | 13.00 | 22.98 | 13.00 | 22.93 |
April | 416.50 | 23.75 | 0.00 | 23.75 | 0.00 | 23.75 |
May | 87.33 | 23.95 | 189.67 | 24.54 | 0.00 | 24.54 |
June | 5.50 | 23.99 | 359.50 | 24.42 | 0.00 | 24.42 |
July | 2.50 | 24.66 | 491.50 | 24.47 | 2.50 | 24.47 |
August | 0.00 | 0.00 | 479.00 | 24.35 | 0.00 | 24.35 |
September | 15.33 | 23.92 | 203.67 | 24.69 | 0.00 | 24.69 |
October | 304.33 | 23.77 | 23.17 | 23.88 | 0.00 | 23.88 |
November | 474.50 | 23.14 | 20.17 | 23.05 | 20.17 | 22.98 |
December | 497.00 | 21.79 | 161.50 | 21.55 | 161.50 | 21.40 |
Annual Sum or Average | 3273.00 | 22.70 | 2262.00 | 23.09 | 518.00 | 22.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.17 | 0.00 | 21.04 |
Maximum of Months | 514.00 | 24.66 | 491.50 | 24.69 | 254.83 | 24.69 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.48 | 446.50 | 20.42 | 446.50 | 20.40 |
February | 454.00 | 20.89 | 313.33 | 20.75 | 313.33 | 20.69 |
March | 514.00 | 21.56 | 179.83 | 21.35 | 179.83 | 21.22 |
April | 468.50 | 22.75 | 11.17 | 22.70 | 11.17 | 22.66 |
May | 201.00 | 23.56 | 138.33 | 23.97 | 0.00 | 23.97 |
June | 41.33 | 23.56 | 294.50 | 24.20 | 0.00 | 24.20 |
July | 3.50 | 24.08 | 462.67 | 24.34 | 2.33 | 24.34 |
August | 22.67 | 23.34 | 417.17 | 24.19 | 0.00 | 24.19 |
September | 175.17 | 23.43 | 88.83 | 23.80 | 3.00 | 23.80 |
October | 473.83 | 22.65 | 4.17 | 22.63 | 4.17 | 22.62 |
November | 489.00 | 21.44 | 173.33 | 21.22 | 173.33 | 21.09 |
December | 497.00 | 20.59 | 400.33 | 20.50 | 400.33 | 20.47 |
Annual Sum or Average | 3842.00 | 21.70 | 2930.17 | 21.97 | 1534.00 | 21.70 |
Minimum of Months | 3.50 | 20.48 | 4.17 | 20.42 | 0.00 | 20.40 |
Maximum of Months | 514.00 | 24.08 | 462.67 | 24.34 | 446.50 | 24.34 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.10 | 487.17 | 20.08 | 487.17 | 20.07 |
February | 454.00 | 20.39 | 404.50 | 20.33 | 404.50 | 20.30 |
March | 514.00 | 20.95 | 317.17 | 20.77 | 317.17 | 20.68 |
April | 481.17 | 22.07 | 109.17 | 21.78 | 109.17 | 21.57 |
May | 251.50 | 23.21 | 127.33 | 23.61 | 3.83 | 23.58 |
June | 84.83 | 23.20 | 262.00 | 23.98 | 0.00 | 23.98 |
July | 26.67 | 23.33 | 423.50 | 24.24 | 2.33 | 24.24 |
August | 57.83 | 23.21 | 360.33 | 24.03 | 0.00 | 24.03 |
September | 298.33 | 23.01 | 55.17 | 23.20 | 5.83 | 23.21 |
October | 495.50 | 21.78 | 89.83 | 21.54 | 89.83 | 21.36 |
November | 489.00 | 20.66 | 306.67 | 20.46 | 306.67 | 20.37 |
December | 497.00 | 20.13 | 473.33 | 20.11 | 473.33 | 20.10 |
Annual Sum or Average | 4151.83 | 21.26 | 3416.17 | 21.44 | 2199.83 | 21.16 |
Minimum of Months | 26.67 | 20.10 | 55.17 | 20.08 | 0.00 | 20.07 |
Maximum of Months | 514.00 | 23.33 | 487.17 | 24.24 | 487.17 | 24.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.53 | 502.00 | 19.53 | 502.00 | 19.53 |
February | 454.00 | 19.75 | 454.00 | 19.75 | 454.00 | 19.75 |
March | 514.00 | 20.25 | 453.33 | 20.18 | 453.33 | 20.15 |
April | 478.17 | 21.13 | 232.67 | 20.80 | 232.00 | 20.63 |
May | 266.00 | 22.64 | 144.17 | 23.08 | 17.83 | 22.98 |
June | 112.00 | 23.23 | 283.50 | 23.96 | 8.50 | 24.00 |
July | 71.50 | 24.32 | 426.67 | 24.34 | 38.17 | 24.43 |
August | 120.33 | 22.95 | 324.67 | 23.82 | 5.00 | 23.82 |
September | 369.33 | 22.37 | 63.50 | 22.52 | 18.83 | 22.48 |
October | 502.00 | 20.85 | 208.33 | 20.57 | 208.33 | 20.41 |
November | 489.00 | 19.90 | 431.17 | 19.82 | 431.17 | 19.79 |
December | 497.00 | 19.59 | 497.00 | 19.59 | 497.00 | 19.59 |
Annual Sum or Average | 4375.33 | 20.71 | 4021.00 | 20.91 | 2866.17 | 20.65 |
Minimum of Months | 71.50 | 19.53 | 63.50 | 19.53 | 5.00 | 19.53 |
Maximum of Months | 514.00 | 24.32 | 502.00 | 24.34 | 502.00 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.68 | 502.00 | 19.68 | 502.00 | 19.68 |
February | 454.00 | 19.86 | 432.83 | 19.83 | 432.83 | 19.82 |
March | 512.50 | 20.59 | 392.17 | 20.42 | 392.17 | 20.35 |
April | 415.83 | 21.43 | 159.33 | 21.07 | 150.83 | 20.83 |
May | 203.83 | 22.65 | 202.50 | 23.54 | 6.17 | 23.50 |
June | 105.50 | 23.76 | 354.17 | 24.21 | 24.67 | 24.33 |
July | 72.33 | 24.81 | 434.83 | 24.47 | 43.50 | 24.62 |
August | 120.17 | 23.19 | 352.83 | 24.01 | 14.17 | 24.10 |
September | 303.50 | 22.12 | 124.50 | 22.65 | 18.00 | 22.60 |
October | 473.33 | 20.90 | 194.50 | 20.69 | 185.00 | 20.52 |
November | 489.00 | 19.97 | 410.00 | 19.86 | 410.00 | 19.82 |
December | 497.00 | 19.69 | 497.00 | 19.69 | 497.00 | 19.69 |
Annual Sum or Average | 4149.00 | 20.78 | 4056.67 | 21.12 | 2676.33 | 20.86 |
Minimum of Months | 72.33 | 19.68 | 124.50 | 19.68 | 6.17 | 19.68 |
Maximum of Months | 512.50 | 24.81 | 502.00 | 24.47 | 502.00 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.50 | 19.95 | 430.17 | 19.77 | 430.17 | 19.71 |
February | 429.50 | 20.40 | 325.83 | 20.13 | 324.33 | 20.01 |
March | 462.00 | 20.85 | 326.33 | 20.66 | 312.67 | 20.52 |
April | 393.17 | 21.48 | 196.33 | 21.27 | 168.00 | 21.04 |
May | 211.67 | 22.47 | 196.67 | 23.25 | 18.33 | 23.15 |
June | 140.00 | 23.07 | 305.67 | 23.91 | 14.50 | 23.98 |
July | 103.50 | 24.23 | 408.67 | 24.38 | 47.67 | 24.51 |
August | 136.00 | 23.39 | 350.83 | 24.06 | 21.33 | 24.18 |
September | 284.50 | 22.43 | 170.67 | 23.14 | 29.17 | 23.19 |
October | 429.33 | 21.09 | 215.50 | 21.12 | 166.50 | 20.93 |
November | 463.17 | 20.24 | 335.17 | 20.02 | 335.17 | 19.93 |
December | 497.00 | 19.94 | 451.67 | 19.82 | 451.67 | 19.77 |
Annual Sum or Average | 4044.33 | 21.04 | 3713.50 | 21.35 | 2319.50 | 21.06 |
Minimum of Months | 103.50 | 19.94 | 170.67 | 19.77 | 14.50 | 19.71 |
Maximum of Months | 497.00 | 24.23 | 451.67 | 24.38 | 451.67 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.69 | 492.33 | 19.68 | 492.33 | 19.67 |
February | 454.00 | 19.98 | 416.00 | 19.90 | 416.00 | 19.87 |
March | 494.67 | 20.46 | 390.83 | 20.33 | 388.00 | 20.27 |
April | 424.50 | 21.09 | 227.83 | 20.92 | 203.17 | 20.73 |
May | 247.33 | 22.41 | 201.50 | 23.17 | 25.33 | 23.13 |
June | 147.33 | 22.78 | 301.83 | 23.80 | 13.00 | 23.86 |
July | 109.33 | 24.05 | 404.50 | 24.35 | 45.67 | 24.49 |
August | 172.83 | 23.01 | 311.00 | 23.83 | 19.17 | 23.94 |
September | 346.83 | 22.08 | 116.67 | 22.54 | 22.33 | 22.53 |
October | 468.17 | 20.77 | 206.00 | 20.59 | 194.00 | 20.43 |
November | 489.00 | 19.99 | 410.83 | 19.88 | 410.83 | 19.84 |
December | 497.00 | 19.69 | 496.33 | 19.69 | 496.33 | 19.69 |
Annual Sum or Average | 4353.00 | 20.79 | 3975.67 | 21.06 | 2726.17 | 20.81 |
Minimum of Months | 109.33 | 19.69 | 116.67 | 19.68 | 13.00 | 19.67 |
Maximum of Months | 502.00 | 24.05 | 496.33 | 24.35 | 496.33 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.63 | 502.00 | 19.63 | 502.00 | 19.63 |
February | 454.00 | 19.98 | 454.00 | 19.98 | 454.00 | 19.98 |
March | 514.00 | 20.37 | 479.83 | 20.34 | 479.83 | 20.33 |
April | 485.00 | 21.09 | 255.50 | 20.89 | 255.50 | 20.79 |
May | 331.50 | 22.83 | 99.33 | 23.08 | 11.17 | 23.03 |
June | 123.00 | 23.40 | 234.50 | 23.92 | 2.17 | 23.92 |
July | 39.50 | 24.53 | 440.17 | 24.32 | 23.17 | 24.37 |
August | 58.17 | 23.31 | 361.00 | 24.03 | 0.00 | 24.03 |
September | 305.33 | 23.08 | 68.67 | 23.29 | 5.83 | 23.30 |
October | 498.83 | 21.69 | 91.33 | 21.50 | 91.33 | 21.37 |
November | 489.00 | 20.43 | 393.50 | 20.34 | 393.50 | 20.30 |
December | 497.00 | 19.80 | 497.00 | 19.80 | 497.00 | 19.80 |
Annual Sum or Average | 4297.33 | 20.96 | 3876.83 | 21.14 | 2715.50 | 20.88 |
Minimum of Months | 39.50 | 19.63 | 68.67 | 19.63 | 0.00 | 19.63 |
Maximum of Months | 514.00 | 24.53 | 502.00 | 24.32 | 502.00 | 24.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.82 | 502.00 | 19.82 | 502.00 | 19.82 |
February | 454.00 | 20.14 | 450.17 | 20.14 | 450.17 | 20.14 |
March | 514.00 | 20.74 | 392.33 | 20.60 | 392.33 | 20.55 |
April | 439.67 | 21.84 | 135.33 | 21.51 | 132.67 | 21.29 |
May | 209.67 | 23.07 | 174.33 | 23.78 | 1.50 | 23.76 |
June | 65.83 | 23.96 | 364.33 | 24.31 | 15.33 | 24.39 |
July | 48.67 | 25.46 | 471.67 | 24.54 | 36.33 | 24.65 |
August | 43.17 | 24.19 | 442.17 | 24.32 | 12.33 | 24.38 |
September | 222.33 | 22.93 | 153.50 | 23.57 | 6.83 | 23.57 |
October | 456.50 | 21.75 | 83.17 | 21.66 | 71.17 | 21.52 |
November | 489.00 | 20.53 | 352.83 | 20.40 | 352.83 | 20.35 |
December | 497.00 | 19.89 | 497.00 | 19.89 | 497.00 | 19.89 |
Annual Sum or Average | 3941.83 | 21.06 | 4018.83 | 21.46 | 2470.50 | 21.18 |
Minimum of Months | 43.17 | 19.82 | 83.17 | 19.82 | 1.50 | 19.82 |
Maximum of Months | 514.00 | 25.46 | 502.00 | 24.54 | 502.00 | 24.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 17.88 | 488.83 | 17.84 | 488.83 | 17.82 |
February | 454.00 | 19.11 | 386.50 | 18.91 | 386.50 | 18.83 |
March | 504.17 | 19.84 | 374.17 | 19.59 | 372.67 | 19.48 |
April | 435.17 | 21.02 | 191.17 | 20.70 | 183.50 | 20.48 |
May | 292.33 | 22.20 | 143.17 | 22.79 | 16.33 | 22.67 |
June | 211.67 | 22.88 | 256.67 | 23.64 | 51.83 | 23.66 |
July | 108.33 | 23.93 | 421.67 | 24.31 | 67.67 | 24.37 |
August | 130.67 | 23.18 | 393.67 | 24.06 | 47.00 | 24.13 |
September | 239.67 | 22.25 | 189.17 | 23.29 | 20.83 | 23.36 |
October | 425.33 | 21.27 | 155.67 | 21.38 | 105.00 | 21.19 |
November | 486.50 | 20.15 | 319.67 | 19.88 | 319.67 | 19.76 |
December | 497.00 | 18.38 | 482.83 | 18.33 | 482.83 | 18.31 |
Annual Sum or Average | 4286.83 | 20.31 | 3803.17 | 20.60 | 2542.67 | 20.26 |
Minimum of Months | 108.33 | 17.88 | 143.17 | 17.84 | 16.33 | 17.82 |
Maximum of Months | 504.17 | 23.93 | 488.83 | 24.31 | 488.83 | 24.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 496.50 | 19.82 | 496.50 | 19.82 |
February | 454.00 | 20.20 | 430.50 | 20.15 | 430.50 | 20.14 |
March | 509.50 | 20.68 | 397.33 | 20.54 | 397.33 | 20.49 |
April | 446.67 | 21.52 | 181.83 | 21.26 | 177.67 | 21.08 |
May | 234.67 | 22.88 | 169.67 | 23.49 | 8.00 | 23.46 |
June | 108.33 | 23.14 | 309.00 | 24.00 | 4.83 | 24.03 |
July | 43.17 | 25.76 | 459.67 | 24.57 | 36.50 | 24.68 |
August | 54.50 | 23.80 | 418.67 | 24.26 | 12.50 | 24.33 |
September | 248.00 | 22.94 | 143.83 | 23.52 | 9.33 | 23.55 |
October | 461.17 | 21.71 | 90.67 | 21.59 | 81.17 | 21.45 |
November | 489.00 | 20.51 | 368.00 | 20.40 | 368.00 | 20.36 |
December | 497.00 | 19.90 | 497.00 | 19.90 | 497.00 | 19.90 |
Annual Sum or Average | 4048.00 | 21.04 | 3962.67 | 21.39 | 2519.33 | 21.12 |
Minimum of Months | 43.17 | 19.83 | 90.67 | 19.82 | 4.83 | 19.82 |
Maximum of Months | 509.50 | 25.76 | 497.00 | 24.57 | 497.00 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.69 | 502.00 | 19.69 | 502.00 | 19.69 |
February | 454.00 | 19.99 | 449.17 | 19.98 | 449.17 | 19.98 |
March | 514.00 | 20.52 | 408.00 | 20.41 | 408.00 | 20.37 |
April | 476.00 | 21.68 | 151.50 | 21.35 | 151.17 | 21.15 |
May | 223.67 | 23.12 | 141.83 | 23.58 | 4.50 | 23.55 |
June | 62.83 | 23.70 | 302.17 | 24.18 | 5.17 | 24.20 |
July | 49.50 | 25.21 | 462.00 | 24.47 | 37.00 | 24.57 |
August | 47.33 | 23.23 | 390.33 | 24.07 | 0.33 | 24.07 |
September | 289.17 | 22.92 | 70.00 | 23.17 | 6.50 | 23.18 |
October | 496.83 | 21.52 | 121.17 | 21.26 | 121.17 | 21.08 |
November | 489.00 | 20.25 | 391.00 | 20.13 | 391.00 | 20.09 |
December | 497.00 | 19.77 | 497.00 | 19.77 | 497.00 | 19.77 |
Annual Sum or Average | 4101.33 | 20.94 | 3886.17 | 21.20 | 2573.00 | 20.93 |
Minimum of Months | 47.33 | 19.69 | 70.00 | 19.69 | 0.33 | 19.69 |
Maximum of Months | 514.00 | 25.21 | 502.00 | 24.47 | 502.00 | 24.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.57 | 427.00 | 19.57 | 427.00 | 19.57 |
February | 385.00 | 19.95 | 365.83 | 19.92 | 365.83 | 19.90 |
March | 429.00 | 20.74 | 298.50 | 20.56 | 298.50 | 20.48 |
April | 351.50 | 21.73 | 114.17 | 21.51 | 97.50 | 21.27 |
May | 164.17 | 23.03 | 179.50 | 23.90 | 4.33 | 23.91 |
June | 67.83 | 24.31 | 302.33 | 24.43 | 22.83 | 24.56 |
July | 50.00 | 25.68 | 388.33 | 24.65 | 39.33 | 24.80 |
August | 73.67 | 23.72 | 320.33 | 24.24 | 14.17 | 24.34 |
September | 239.83 | 22.58 | 102.83 | 23.17 | 6.67 | 23.21 |
October | 398.17 | 21.29 | 115.50 | 21.15 | 104.50 | 20.99 |
November | 417.00 | 20.16 | 321.33 | 20.03 | 321.33 | 19.97 |
December | 422.00 | 19.62 | 421.50 | 19.62 | 421.50 | 19.61 |
Annual Sum or Average | 3425.17 | 20.91 | 3357.17 | 21.29 | 2123.50 | 21.01 |
Minimum of Months | 50.00 | 19.57 | 102.83 | 19.57 | 4.33 | 19.57 |
Maximum of Months | 429.00 | 25.68 | 427.00 | 24.65 | 427.00 | 24.80 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.33 | 20.14 | 413.17 | 19.94 | 413.17 | 19.87 |
February | 426.17 | 20.79 | 292.17 | 20.47 | 290.50 | 20.34 |
March | 449.83 | 21.16 | 278.33 | 20.99 | 258.67 | 20.82 |
April | 375.33 | 21.94 | 129.33 | 21.81 | 100.17 | 21.60 |
May | 175.33 | 22.95 | 203.17 | 23.75 | 5.17 | 23.72 |
June | 94.17 | 23.55 | 324.67 | 24.14 | 11.83 | 24.20 |
July | 72.33 | 25.12 | 437.17 | 24.54 | 47.00 | 24.68 |
August | 73.67 | 24.19 | 405.83 | 24.31 | 21.33 | 24.42 |
September | 225.33 | 23.03 | 190.67 | 23.74 | 21.83 | 23.86 |
October | 411.33 | 21.70 | 148.00 | 21.85 | 90.67 | 21.70 |
November | 459.00 | 20.70 | 275.83 | 20.43 | 273.67 | 20.30 |
December | 497.00 | 20.22 | 434.83 | 20.06 | 434.83 | 20.00 |
Annual Sum or Average | 3749.83 | 21.33 | 3533.17 | 21.71 | 1968.83 | 21.42 |
Minimum of Months | 72.33 | 20.14 | 129.33 | 19.94 | 5.17 | 19.87 |
Maximum of Months | 497.00 | 25.12 | 437.17 | 24.54 | 434.83 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.81 | 487.33 | 19.78 | 487.33 | 19.77 |
February | 453.83 | 20.22 | 396.00 | 20.12 | 396.00 | 20.08 |
March | 492.50 | 20.72 | 342.17 | 20.56 | 338.17 | 20.48 |
April | 414.33 | 21.53 | 154.83 | 21.40 | 130.33 | 21.21 |
May | 211.17 | 22.88 | 205.50 | 23.64 | 12.33 | 23.67 |
June | 104.00 | 23.20 | 327.83 | 24.04 | 9.17 | 24.09 |
July | 75.67 | 24.88 | 435.50 | 24.51 | 44.00 | 24.65 |
August | 101.00 | 23.54 | 364.50 | 24.13 | 17.67 | 24.23 |
September | 291.83 | 22.58 | 127.00 | 23.13 | 10.83 | 23.17 |
October | 461.67 | 21.30 | 132.33 | 21.17 | 117.17 | 21.01 |
November | 489.00 | 20.32 | 359.33 | 20.18 | 359.33 | 20.12 |
December | 497.00 | 19.83 | 493.50 | 19.83 | 493.50 | 19.82 |
Annual Sum or Average | 4094.00 | 21.00 | 3825.83 | 21.34 | 2415.83 | 21.08 |
Minimum of Months | 75.67 | 19.81 | 127.00 | 19.78 | 9.17 | 19.77 |
Maximum of Months | 502.00 | 24.88 | 493.50 | 24.51 | 493.50 | 24.65 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.43267 | 14.34449 | -0.5494 | 12.90742 |
February | 454.00000 | 22.26399 | 16.00271 | -0.3248 | 8.14406 |
March | 514.00000 | 23.02908 | 18.99434 | -0.1087 | 6.18114 |
April | 485.00000 | 23.87303 | 18.92408 | 0.13480 | 5.78267 |
May | 508.00000 | 24.38974 | 31.41827 | -0.4640 | 10.48413 |
June | 496.00000 | 24.33182 | 43.75901 | -0.3589 | 8.19807 |
July | 497.00000 | 24.46310 | 50.13260 | -0.2591 | 7.00604 |
August | 514.00000 | 24.32317 | 49.58035 | -0.3117 | 7.42997 |
September | 485.00000 | 24.35068 | 36.95625 | -0.4310 | 9.46095 |
October | 502.00000 | 23.98323 | 29.54632 | 0.24054 | 6.56001 |
November | 489.00000 | 23.16352 | 22.08803 | -0.0562 | 6.07464 |
December | 497.00000 | 21.79178 | 16.14046 | -0.4396 | 10.28164 |
Annual Sum or Average | 5943.00000 | 23.45758 | 29.11854 | -0.2441 | 8.21369 |
Minimum of Months | 454.00000 | 21.43267 | 14.34449 | -0.5494 | 5.78267 |
Maximum of Months | 514.00000 | 24.46310 | 50.13260 | 0.24054 | 12.90742 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.48201 | 16.18513 | -0.7740 | 19.26781 |
February | 454.00000 | 20.88624 | 17.93734 | -0.6418 | 14.78534 |
March | 514.00000 | 21.56049 | 21.68177 | -0.4326 | 10.08750 |
April | 485.00000 | 22.79974 | 21.32785 | -0.1088 | 6.52958 |
May | 508.00000 | 24.02622 | 32.57911 | -0.5978 | 13.86153 |
June | 496.00000 | 24.13374 | 44.96606 | -0.4432 | 9.63394 |
July | 497.00000 | 24.31087 | 50.97559 | -0.3302 | 7.71397 |
August | 514.00000 | 24.15456 | 50.60649 | -0.3954 | 8.66434 |
September | 485.00000 | 23.91178 | 38.93815 | -0.6032 | 13.42148 |
October | 502.00000 | 22.73232 | 33.21277 | -0.0510 | 6.28967 |
November | 489.00000 | 21.43599 | 25.42900 | -0.4479 | 10.48392 |
December | 497.00000 | 20.59370 | 18.23115 | -0.7253 | 17.58274 |
Annual Sum or Average | 5943.00000 | 22.59869 | 31.13080 | -0.4616 | 11.50535 |
Minimum of Months | 454.00000 | 20.48201 | 16.18513 | -0.7740 | 6.28967 |
Maximum of Months | 514.00000 | 24.31087 | 50.97559 | -0.0510 | 19.26781 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.10064 | 16.52703 | -0.9017 | 24.39856 |
February | 454.00000 | 20.39238 | 18.23989 | -0.7958 | 20.25977 |
March | 514.00000 | 20.95377 | 22.19757 | -0.6057 | 14.39558 |
April | 485.00000 | 22.08911 | 22.03227 | -0.2867 | 8.85968 |
May | 508.00000 | 23.74791 | 32.85806 | -0.6967 | 17.39372 |
June | 496.00000 | 23.98628 | 45.52283 | -0.4902 | 10.97200 |
July | 497.00000 | 24.20776 | 51.39655 | -0.3628 | 8.34751 |
August | 514.00000 | 24.00635 | 51.20998 | -0.4508 | 9.84672 |
September | 485.00000 | 23.42490 | 40.22326 | -0.7779 | 19.27361 |
October | 502.00000 | 21.80463 | 35.21972 | -0.2828 | 8.45012 |
November | 489.00000 | 20.66044 | 25.84265 | -0.6614 | 16.40545 |
December | 497.00000 | 20.13393 | 18.69214 | -0.8737 | 23.35576 |
Annual Sum or Average | 5943.00000 | 22.14038 | 31.78959 | -0.5974 | 15.11864 |
Minimum of Months | 454.00000 | 20.10064 | 16.52703 | -0.9017 | 8.34751 |
Maximum of Months | 514.00000 | 24.20776 | 51.39655 | -0.2828 | 24.39856 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.53007 | 16.58744 | -1.1503 | 34.83185 |
February | 454.00000 | 19.74791 | 18.74681 | -1.0323 | 29.87517 |
March | 514.00000 | 20.24652 | 22.99965 | -0.8372 | 22.04057 |
April | 485.00000 | 21.17473 | 23.04334 | -0.5132 | 13.73847 |
May | 508.00000 | 23.38939 | 33.46922 | -0.7918 | 22.09432 |
June | 496.00000 | 23.94657 | 45.77192 | -0.4643 | 11.23610 |
July | 497.00000 | 24.21513 | 52.10891 | -0.3143 | 8.43738 |
August | 514.00000 | 23.82246 | 52.23804 | -0.4927 | 11.49068 |
September | 485.00000 | 22.76699 | 42.24356 | -0.9895 | 28.47143 |
October | 502.00000 | 20.85410 | 35.39437 | -0.5310 | 13.48760 |
November | 489.00000 | 19.89662 | 26.47302 | -0.8978 | 25.03899 |
December | 497.00000 | 19.58641 | 18.83908 | -1.1121 | 33.19357 |
Annual Sum or Average | 5943.00000 | 21.61530 | 32.45060 | -0.7581 | 21.07660 |
Minimum of Months | 454.00000 | 19.53007 | 16.58744 | -1.1503 | 8.43738 |
Maximum of Months | 514.00000 | 24.21513 | 52.23804 | -0.3143 | 34.83185 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.67637 | 16.57538 | -1.0985 | 32.61441 |
February | 454.00000 | 19.86319 | 18.49288 | -0.9697 | 27.43489 |
March | 514.00000 | 20.60049 | 22.22030 | -0.7155 | 18.68203 |
April | 485.00000 | 21.80495 | 21.68729 | -0.3140 | 11.67799 |
May | 508.00000 | 23.66574 | 32.71402 | -0.6202 | 17.29256 |
June | 496.00000 | 24.04685 | 45.20824 | -0.3293 | 10.05256 |
July | 497.00000 | 24.26973 | 51.47838 | -0.1875 | 8.06142 |
August | 514.00000 | 23.89279 | 51.70758 | -0.3866 | 10.88042 |
September | 485.00000 | 22.89348 | 41.38654 | -0.8807 | 25.72739 |
October | 502.00000 | 21.09352 | 34.41956 | -0.4588 | 12.73470 |
November | 489.00000 | 19.96570 | 26.05118 | -0.8677 | 23.91171 |
December | 497.00000 | 19.68556 | 18.74761 | -1.0775 | 31.71990 |
Annual Sum or Average | 5943.00000 | 21.80567 | 31.84727 | -0.6561 | 19.14727 |
Minimum of Months | 454.00000 | 19.67637 | 16.57538 | -1.0985 | 8.06142 |
Maximum of Months | 514.00000 | 24.26973 | 51.70758 | -0.1875 | 32.61441 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.00607 | 16.16457 | -0.9494 | 28.57133 |
February | 454.00000 | 20.59078 | 17.53232 | -0.7368 | 22.13187 |
March | 514.00000 | 21.21842 | 21.24986 | -0.5435 | 16.71143 |
April | 485.00000 | 21.98087 | 21.12628 | -0.2711 | 12.11859 |
May | 508.00000 | 23.53269 | 32.69332 | -0.6816 | 19.68928 |
June | 496.00000 | 23.84768 | 45.70543 | -0.4479 | 12.30220 |
July | 497.00000 | 24.17868 | 51.82791 | -0.2624 | 9.06402 |
August | 514.00000 | 23.91217 | 51.45880 | -0.3789 | 11.20621 |
September | 485.00000 | 23.19902 | 40.36957 | -0.7589 | 23.45346 |
October | 502.00000 | 21.57310 | 33.14805 | -0.3212 | 12.70743 |
November | 489.00000 | 20.44249 | 25.20275 | -0.7201 | 20.76969 |
December | 497.00000 | 19.94320 | 18.43622 | -0.9626 | 28.12196 |
Annual Sum or Average | 5943.00000 | 22.04919 | 31.37066 | -0.5848 | 18.02352 |
Minimum of Months | 454.00000 | 19.94320 | 16.16457 | -0.9626 | 9.06402 |
Maximum of Months | 514.00000 | 24.17868 | 51.82791 | -0.2624 | 28.57133 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.69486 | 16.34875 | -1.0977 | 32.63748 |
February | 454.00000 | 19.97969 | 18.15333 | -0.9504 | 27.13865 |
March | 514.00000 | 20.60557 | 21.95217 | -0.7235 | 19.81539 |
April | 485.00000 | 21.47357 | 21.93563 | -0.4004 | 13.47926 |
May | 508.00000 | 23.35450 | 33.08914 | -0.7120 | 21.75522 |
June | 496.00000 | 23.74986 | 46.14195 | -0.4439 | 12.94239 |
July | 497.00000 | 24.13790 | 52.12346 | -0.2470 | 9.47183 |
August | 514.00000 | 23.69635 | 52.30037 | -0.4466 | 12.86696 |
September | 485.00000 | 22.67232 | 41.79250 | -0.9504 | 28.99651 |
October | 502.00000 | 21.00398 | 34.33614 | -0.4764 | 13.31871 |
November | 489.00000 | 19.98736 | 25.82928 | -0.8669 | 23.96828 |
December | 497.00000 | 19.68925 | 18.55259 | -1.0802 | 31.82400 |
Annual Sum or Average | 5943.00000 | 21.68660 | 32.00599 | -0.6972 | 20.61350 |
Minimum of Months | 454.00000 | 19.68925 | 16.34875 | -1.0977 | 9.47183 |
Maximum of Months | 514.00000 | 24.13790 | 52.30037 | -0.2470 | 32.63748 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.62573 | 15.65260 | -1.1073 | 32.61661 |
February | 454.00000 | 19.98115 | 18.13289 | -0.9672 | 26.47945 |
March | 514.00000 | 20.36652 | 22.18687 | -0.8165 | 20.52780 |
April | 485.00000 | 21.09045 | 22.98299 | -0.5459 | 12.53910 |
May | 508.00000 | 23.30159 | 34.45729 | -0.8639 | 23.59691 |
June | 496.00000 | 23.93852 | 45.96062 | -0.5144 | 11.44876 |
July | 497.00000 | 24.23900 | 51.99720 | -0.3383 | 7.95010 |
August | 514.00000 | 24.00392 | 51.60990 | -0.4452 | 9.65805 |
September | 485.00000 | 23.45357 | 40.57157 | -0.7633 | 18.69907 |
October | 502.00000 | 21.69968 | 33.59321 | -0.3031 | 8.20573 |
November | 489.00000 | 20.42914 | 25.37864 | -0.7293 | 17.84501 |
December | 497.00000 | 19.79801 | 17.89284 | -1.0266 | 29.18488 |
Annual Sum or Average | 5943.00000 | 21.84318 | 31.82829 | -0.6999 | 18.17746 |
Minimum of Months | 454.00000 | 19.62573 | 15.65260 | -1.1073 | 7.95010 |
Maximum of Months | 514.00000 | 24.23900 | 51.99720 | -0.3031 | 32.61661 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.81673 | 15.82440 | -1.0488 | 30.09216 |
February | 454.00000 | 20.14232 | 18.02255 | -0.8984 | 23.62199 |
March | 514.00000 | 20.74250 | 21.64374 | -0.6867 | 16.71244 |
April | 485.00000 | 22.05201 | 21.45638 | -0.2707 | 9.53649 |
May | 508.00000 | 23.85018 | 33.07558 | -0.6055 | 15.49345 |
June | 496.00000 | 24.18062 | 44.80437 | -0.3325 | 8.88646 |
July | 497.00000 | 24.40571 | 50.96725 | -0.1741 | 6.79122 |
August | 514.00000 | 24.20953 | 50.67277 | -0.2955 | 8.14522 |
September | 485.00000 | 23.66774 | 39.52052 | -0.6266 | 15.68014 |
October | 502.00000 | 21.98466 | 32.71245 | -0.2184 | 8.17500 |
November | 489.00000 | 20.52658 | 25.13513 | -0.6933 | 16.76902 |
December | 497.00000 | 19.89302 | 17.92138 | -0.9950 | 27.81812 |
Annual Sum or Average | 5943.00000 | 22.13895 | 31.10320 | -0.5682 | 15.58483 |
Minimum of Months | 454.00000 | 19.81673 | 15.82440 | -1.0488 | 6.79122 |
Maximum of Months | 514.00000 | 24.40571 | 50.96725 | -0.1741 | 30.09216 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 17.88147 | 13.27547 | -1.3503 | 42.01015 |
February | 454.00000 | 19.11364 | 14.95508 | -1.0097 | 29.14311 |
March | 514.00000 | 19.94318 | 18.74872 | -0.7872 | 22.03038 |
April | 485.00000 | 21.37027 | 19.92042 | -0.3909 | 12.43844 |
May | 508.00000 | 23.12795 | 33.26016 | -0.8261 | 23.74958 |
June | 496.00000 | 23.65691 | 46.97900 | -0.5390 | 13.83628 |
July | 497.00000 | 24.18829 | 52.68083 | -0.2767 | 8.42304 |
August | 514.00000 | 23.93652 | 52.20039 | -0.3550 | 10.31055 |
September | 485.00000 | 23.32959 | 39.30617 | -0.6709 | 20.06001 |
October | 502.00000 | 21.77887 | 30.62477 | -0.2109 | 10.35770 |
November | 489.00000 | 20.17209 | 22.42221 | -0.7111 | 18.85937 |
December | 497.00000 | 18.38318 | 15.48434 | -1.2361 | 37.71983 |
Annual Sum or Average | 5943.00000 | 21.42448 | 30.12966 | -0.6951 | 20.69451 |
Minimum of Months | 454.00000 | 17.88147 | 13.27547 | -1.3503 | 8.42304 |
Maximum of Months | 514.00000 | 24.18829 | 52.68083 | -0.2109 | 42.01015 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83326 | 15.57924 | -1.0488 | 30.13004 |
February | 454.00000 | 20.19779 | 17.71448 | -0.8895 | 23.61397 |
March | 514.00000 | 20.70974 | 21.38357 | -0.6996 | 17.55092 |
April | 485.00000 | 21.73801 | 21.66261 | -0.3520 | 10.69819 |
May | 508.00000 | 23.66229 | 33.22265 | -0.6611 | 17.73728 |
June | 496.00000 | 23.96635 | 45.60363 | -0.4265 | 10.76351 |
July | 497.00000 | 24.39501 | 51.20707 | -0.1945 | 7.20733 |
August | 514.00000 | 24.13916 | 50.88827 | -0.3182 | 8.71646 |
September | 485.00000 | 23.58898 | 39.71366 | -0.6556 | 16.75715 |
October | 502.00000 | 21.91442 | 32.53560 | -0.2309 | 8.23145 |
November | 489.00000 | 20.51195 | 24.92786 | -0.6997 | 16.94436 |
December | 497.00000 | 19.90339 | 17.69882 | -0.9969 | 27.87445 |
Annual Sum or Average | 5943.00000 | 22.06250 | 31.13641 | -0.5956 | 16.29920 |
Minimum of Months | 454.00000 | 19.83326 | 15.57924 | -1.0488 | 7.20733 |
Maximum of Months | 514.00000 | 24.39501 | 51.20707 | -0.1945 | 30.13004 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.69402 | 16.84282 | -1.0609 | 30.89507 |
February | 454.00000 | 19.98894 | 18.95093 | -0.9274 | 25.22959 |
March | 514.00000 | 20.52008 | 22.85643 | -0.7263 | 17.98256 |
April | 485.00000 | 21.72213 | 22.58592 | -0.3619 | 10.16862 |
May | 508.00000 | 23.75270 | 33.09157 | -0.6680 | 16.93614 |
June | 496.00000 | 24.13150 | 45.11591 | -0.4063 | 9.31128 |
July | 497.00000 | 24.35162 | 51.55382 | -0.2725 | 7.43937 |
August | 514.00000 | 24.04476 | 51.36366 | -0.4172 | 9.26588 |
September | 485.00000 | 23.38577 | 40.79959 | -0.7778 | 19.60932 |
October | 502.00000 | 21.54725 | 34.32620 | -0.3387 | 9.35467 |
November | 489.00000 | 20.24854 | 26.17162 | -0.7661 | 19.74557 |
December | 497.00000 | 19.76547 | 18.96915 | -1.0162 | 29.07380 |
Annual Sum or Average | 5943.00000 | 21.94600 | 32.00698 | -0.6428 | 17.01703 |
Minimum of Months | 454.00000 | 19.69402 | 16.84282 | -1.0609 | 7.43937 |
Maximum of Months | 514.00000 | 24.35162 | 51.55382 | -0.2725 | 30.89507 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.56743 | 16.08306 | -1.0737 | 31.62359 |
February | 385.00000 | 19.94957 | 17.92630 | -0.9105 | 24.62254 |
March | 433.00000 | 20.77420 | 21.19217 | -0.6425 | 16.03368 |
April | 410.00000 | 22.09696 | 20.76515 | -0.2323 | 9.75546 |
May | 430.00000 | 23.90876 | 31.99571 | -0.5509 | 14.91089 |
June | 418.00000 | 24.21693 | 44.52446 | -0.2963 | 9.14248 |
July | 422.00000 | 24.43364 | 50.82059 | -0.1632 | 7.48933 |
August | 433.00000 | 24.06950 | 50.71503 | -0.3447 | 9.67914 |
September | 410.00000 | 23.26988 | 40.10815 | -0.7546 | 20.59461 |
October | 427.00000 | 21.51188 | 32.84931 | -0.3332 | 9.92852 |
November | 417.00000 | 20.16454 | 24.76525 | -0.7797 | 20.24749 |
December | 422.00000 | 19.61600 | 18.13138 | -1.0395 | 30.16768 |
Annual Sum or Average | 5034.00000 | 21.97858 | 30.92647 | -0.5913 | 16.95815 |
Minimum of Months | 385.00000 | 19.56743 | 16.08306 | -1.0737 | 7.48933 |
Maximum of Months | 433.00000 | 24.43364 | 50.82059 | -0.1632 | 31.62359 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.23421 | 16.07682 | -0.8503 | 24.82200 |
February | 454.00000 | 20.98407 | 17.33228 | -0.6070 | 17.73366 |
March | 514.00000 | 21.58450 | 20.78796 | -0.4190 | 13.50465 |
April | 485.00000 | 22.45196 | 20.51141 | -0.1386 | 9.58506 |
May | 508.00000 | 23.84651 | 32.35266 | -0.5733 | 15.24074 |
June | 496.00000 | 24.05878 | 44.98845 | -0.3844 | 9.87801 |
July | 497.00000 | 24.33771 | 51.17745 | -0.2171 | 7.69817 |
August | 514.00000 | 24.13450 | 50.63041 | -0.3060 | 8.95638 |
September | 485.00000 | 23.68434 | 39.16845 | -0.5865 | 16.59547 |
October | 502.00000 | 22.19693 | 32.03812 | -0.1457 | 9.75724 |
November | 489.00000 | 20.89931 | 24.58957 | -0.5715 | 15.99705 |
December | 497.00000 | 20.22005 | 18.24562 | -0.8503 | 23.78841 |
Annual Sum or Average | 5943.00000 | 22.39862 | 30.78467 | -0.4698 | 14.43136 |
Minimum of Months | 454.00000 | 20.22005 | 16.07682 | -0.8503 | 7.69817 |
Maximum of Months | 514.00000 | 24.33771 | 51.17745 | -0.1386 | 24.82200 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.80827 | 16.33875 | -1.0196 | 29.32897 |
February | 454.00000 | 20.22302 | 18.09828 | -0.8475 | 22.82396 |
March | 514.00000 | 20.87318 | 21.57880 | -0.6163 | 16.22376 |
April | 485.00000 | 21.91626 | 21.40788 | -0.2710 | 10.40134 |
May | 508.00000 | 23.70157 | 32.71848 | -0.5947 | 16.79030 |
June | 496.00000 | 23.97617 | 45.40956 | -0.3763 | 10.28373 |
July | 497.00000 | 24.30644 | 51.46392 | -0.1987 | 7.98795 |
August | 514.00000 | 23.95988 | 51.39266 | -0.3616 | 10.10229 |
September | 485.00000 | 23.21549 | 40.52141 | -0.7603 | 20.92928 |
October | 502.00000 | 21.53738 | 33.35295 | -0.3158 | 9.70070 |
November | 489.00000 | 20.32499 | 25.38501 | -0.7395 | 18.93881 |
December | 497.00000 | 19.83050 | 18.44565 | -0.9931 | 28.10780 |
Annual Sum or Average | 5943.00000 | 21.98846 | 31.46682 | -0.5890 | 16.74454 |
Minimum of Months | 454.00000 | 19.80827 | 16.33875 | -1.0196 | 7.98795 |
Maximum of Months | 514.00000 | 24.30644 | 51.46392 | -0.1987 | 29.32897 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 4766617.73 | 1386209.95 | 2.20 | 4670502.65 | 96115.08 | 0.00 | 0.23 | 19-JAN-07:01 | 0.00 | 01-JAN-00:01 | 6714.92 | 19-JAN-07:01 | 6714.92 | 19-JAN-07:01 | 55.90 | 19-JAN-13:17 | 1883.75 | 19-JAN-07:01 | 0.00 |
February | 11177062.45 | 3283037.05 | 6.56 | 11035159.23 | 141903.22 | 0.00 | 0.23 | 22-FEB-07:01 | 0.00 | 01-FEB-00:03 | 6689.68 | 22-FEB-07:01 | 6689.68 | 22-FEB-07:01 | 109.56 | 21-FEB-18:13 | 1877.04 | 22-FEB-07:01 | 0.00 |
March | 29222678.96 | 8591820.99 | 16.41 | 28257391.59 | 965287.38 | 0.00 | 0.15 | 30-MAR-07:06 | 0.00 | 01-MAR-00:10 | 4341.85 | 30-MAR-07:06 | 4341.85 | 30-MAR-07:06 | 126.18 | 20-MAR-17:13 | 1241.22 | 30-MAR-07:06 | 0.00 |
April | 0.124204E+10 | 0.339804E+09 | 59.70 | 0.120330E+10 | 38734380.92 | 0.00 | 0.90 | 23-APR-17:11 | 0.00 | 01-APR-00:10 | 30932.82 | 23-APR-17:51 | 30932.82 | 23-APR-17:51 | 4163.59 | 23-APR-13:54 | 7654.13 | 23-APR-17:11 | 0.00 |
May | 0.171446E+11 | 0.427276E+10 | 212.60 | 0.160795E+11 | 0.106517E+10 | 0.00 | 1.00 | 10-MAY-15:30 | 0.00 | 01-MAY-00:10 | 69134.14 | 25-MAY-16:10 | 59548.51 | 18-MAY-15:10 | 20586.88 | 26-MAY-11:20 | 17858.04 | 25-MAY-16:10 | 0.00 |
June | 0.402853E+11 | 0.996422E+10 | 352.15 | 0.313547E+11 | 0.893059E+10 | 0.00 | 1.00 | 01-JUN-12:00 | 0.00 | 01-JUN-00:10 | 116320.83 | 30-JUN-04:03 | 68464.60 | 29-JUN-16:00 | 55422.22 | 19-JUN-15:30 | 27364.59 | 30-JUN-04:03 | 0.00 |
July | 0.552453E+11 | 0.133601E+11 | 402.22 | 0.412860E+11 | 0.139593E+11 | 0.00 | 1.00 | 03-JUL-04:03 | 0.00 | 01-JUL-00:10 | 121984.70 | 05-JUL-10:30 | 70338.69 | 24-JUL-16:00 | 79724.44 | 05-JUL-11:00 | 27457.94 | 05-JUL-11:50 | 0.00 |
August | 0.433418E+11 | 0.104984E+11 | 394.02 | 0.310462E+11 | 0.122956E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 100512.30 | 31-AUG-12:50 | 64870.15 | 08-AUG-16:00 | 54922.31 | 31-AUG-12:50 | 22879.18 | 09-AUG-12:20 | 0.00 |
September | 0.931900E+10 | 0.234390E+10 | 162.31 | 0.777685E+10 | 0.154216E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 68837.41 | 01-SEP-13:20 | 60839.58 | 01-SEP-16:00 | 25294.63 | 01-SEP-06:02 | 16144.45 | 01-SEP-13:20 | 0.00 |
October | 0.119175E+10 | 0.314980E+09 | 45.44 | 0.113128E+10 | 60467523.04 | 0.00 | 0.84 | 19-OCT-15:10 | 0.00 | 01-OCT-00:10 | 28823.04 | 19-OCT-15:10 | 28823.04 | 19-OCT-15:10 | 4231.02 | 22-OCT-12:01 | 6886.77 | 19-OCT-15:10 | 0.00 |
November | 0.200191E+09 | 56178245.75 | 21.88 | 0.146404E+09 | 53786453.00 | 0.00 | 0.33 | 01-NOV-15:10 | 0.00 | 01-NOV-00:10 | 9777.79 | 01-NOV-15:10 | 7056.74 | 01-NOV-15:10 | 2776.74 | 01-NOV-15:00 | 2678.38 | 01-NOV-15:10 | 0.00 |
December | 7263309.94 | 2124450.75 | 4.02 | 7098515.18 | 164794.77 | 0.00 | 0.22 | 28-DEC-07:01 | 0.00 | 01-DEC-00:10 | 6301.58 | 28-DEC-07:01 | 6301.58 | 28-DEC-07:01 | 107.72 | 05-DEC-13:12 | 1773.57 | 28-DEC-07:01 | 0.00 |
Annual Sum or Average | 0.168022E+12 | 0.411657E+11 | 1679.52 | 0.130075E+12 | 0.379472E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 4766617.73 | 1386209.95 | 2.20 | 4670502.65 | 96115.08 | 0.00 | 0.15 | 0.00 | 4341.85 | 4341.85 | 55.90 | 1241.22 | 0.00 | ||||||
Maximum of Months | 0.552453E+11 | 0.133601E+11 | 402.22 | 0.412860E+11 | 0.139593E+11 | 0.00 | 1.00 | 0.00 | 121984.70 | 70338.69 | 79724.44 | 27457.94 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1765891.75 | 509946.66 | 0.31 | 1764134.72 | 1757.03 | 0.00 | 0.20 | 19-JAN-07:01 | 0.00 | 01-JAN-00:01 | 5306.64 | 19-JAN-07:01 | 5306.64 | 19-JAN-07:01 | 13.53 | 19-JAN-07:06 | 1499.76 | 19-JAN-07:01 | 0.00 |
February | 7585909.42 | 2199543.18 | 3.97 | 7582192.76 | 3716.66 | 0.00 | 0.26 | 09-FEB-07:01 | 0.00 | 01-FEB-00:03 | 6908.99 | 09-FEB-07:01 | 6908.99 | 09-FEB-07:01 | 7.29 | 08-FEB-10:50 | 1925.96 | 09-FEB-07:01 | 0.00 |
March | 13194886.31 | 3814461.49 | 6.45 | 13125636.74 | 69249.56 | 0.00 | 0.27 | 22-MAR-06:01 | 0.00 | 01-MAR-00:10 | 7254.30 | 22-MAR-06:01 | 7254.30 | 22-MAR-06:01 | 60.18 | 28-MAR-11:20 | 2016.29 | 22-MAR-06:01 | 0.00 |
April | 0.135866E+10 | 0.366951E+09 | 60.61 | 0.133107E+10 | 27588566.36 | 0.00 | 1.00 | 23-APR-16:02 | 0.00 | 01-APR-00:10 | 36880.22 | 23-APR-16:02 | 36880.22 | 23-APR-16:02 | 3415.73 | 23-APR-12:45 | 9015.77 | 23-APR-16:02 | 0.00 |
May | 0.168068E+11 | 0.417407E+10 | 218.12 | 0.157701E+11 | 0.103663E+10 | 0.00 | 1.00 | 10-MAY-15:20 | 0.00 | 01-MAY-00:10 | 62492.28 | 25-MAY-16:00 | 58732.69 | 18-MAY-15:00 | 20198.45 | 26-MAY-11:00 | 16165.79 | 25-MAY-16:00 | 0.00 |
June | 0.380906E+11 | 0.938876E+10 | 355.46 | 0.300044E+11 | 0.808624E+10 | 0.00 | 1.00 | 01-JUN-12:00 | 0.00 | 01-JUN-00:10 | 108041.56 | 30-JUN-04:03 | 64409.57 | 30-JUN-14:40 | 50228.59 | 29-JUN-06:03 | 25260.32 | 30-JUN-04:03 | 0.00 |
July | 0.507285E+11 | 0.122621E+11 | 401.19 | 0.379226E+11 | 0.128059E+11 | 0.00 | 1.00 | 03-JUL-04:03 | 0.00 | 01-JUL-00:10 | 112052.85 | 05-JUL-10:30 | 68893.40 | 23-JUL-16:01 | 73317.10 | 05-JUL-11:00 | 25222.35 | 05-JUL-11:50 | 0.00 |
August | 0.378422E+11 | 0.918753E+10 | 387.19 | 0.273515E+11 | 0.104907E+11 | 0.00 | 1.00 | 04-AUG-12:10 | 0.00 | 01-AUG-00:10 | 88629.36 | 31-AUG-12:50 | 61410.83 | 08-AUG-15:20 | 48417.09 | 31-AUG-12:50 | 20112.77 | 31-AUG-12:50 | 0.00 |
September | 0.837530E+10 | 0.211164E+10 | 162.58 | 0.696203E+10 | 0.141327E+10 | 0.00 | 1.00 | 01-SEP-08:30 | 0.00 | 01-SEP-00:10 | 66071.81 | 01-SEP-13:20 | 59121.76 | 01-SEP-15:50 | 19755.69 | 01-SEP-05:03 | 15493.75 | 01-SEP-13:20 | 0.00 |
October | 0.113406E+10 | 0.299667E+09 | 36.06 | 0.107891E+10 | 55146093.64 | 0.00 | 0.80 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 24702.94 | 19-OCT-15:00 | 24702.94 | 19-OCT-15:00 | 3592.23 | 22-OCT-12:12 | 5979.77 | 19-OCT-15:00 | 0.00 |
November | 0.161390E+09 | 45265437.40 | 14.17 | 0.113383E+09 | 48006466.81 | 0.00 | 0.31 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 | 8318.07 | 01-NOV-15:00 | 7070.46 | 15-NOV-07:01 | 2561.63 | 01-NOV-15:00 | 2291.25 | 01-NOV-15:00 | 0.00 |
December | 4546225.00 | 1308042.69 | 0.77 | 4535543.06 | 10681.93 | 0.00 | 0.22 | 06-DEC-07:01 | 0.00 | 01-DEC-00:10 | 5827.17 | 06-DEC-07:01 | 5827.17 | 06-DEC-07:01 | 55.76 | 06-DEC-07:11 | 1639.50 | 06-DEC-07:01 | 0.00 |
Annual Sum or Average | 0.154525E+12 | 0.378438E+11 | 1646.87 | 0.120561E+12 | 0.339636E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 1765891.75 | 509946.66 | 0.31 | 1764134.72 | 1757.03 | 0.00 | 0.20 | 0.00 | 5306.64 | 5306.64 | 7.29 | 1499.76 | 0.00 | ||||||
Maximum of Months | 0.507285E+11 | 0.122621E+11 | 401.19 | 0.379226E+11 | 0.128059E+11 | 0.00 | 1.00 | 0.00 | 112052.85 | 68893.40 | 73317.10 | 25260.32 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 506289.58 | 148829.82 | 0.22 | 506289.58 | -0.0 | 0.00 | 0.07 | 19-JAN-07:01 | 0.00 | 01-JAN-00:01 | 1892.11 | 19-JAN-07:01 | 1892.11 | 19-JAN-07:01 | 0.00 | 30-JAN-07:11 | 551.85 | 19-JAN-07:01 | 0.00 |
February | 7661415.45 | 2261346.45 | 6.17 | 7586053.34 | 75362.11 | 0.00 | 0.07 | 09-FEB-07:01 | 0.00 | 01-FEB-00:03 | 2066.43 | 09-FEB-07:01 | 2066.43 | 09-FEB-07:01 | 19.24 | 22-FEB-11:00 | 601.84 | 09-FEB-07:01 | 0.00 |
March | 17021724.78 | 5007431.05 | 12.88 | 16641120.35 | 380604.43 | 0.00 | 0.19 | 30-MAR-06:01 | 0.00 | 01-MAR-00:10 | 5453.42 | 30-MAR-06:01 | 5453.42 | 30-MAR-06:01 | 52.55 | 28-MAR-11:40 | 1545.95 | 30-MAR-06:01 | 0.00 |
April | 0.143053E+10 | 0.386216E+09 | 64.56 | 0.137795E+10 | 52581199.34 | 0.00 | 1.00 | 23-APR-15:42 | 0.00 | 01-APR-00:10 | 46262.72 | 23-APR-16:22 | 46262.72 | 23-APR-16:22 | 3913.42 | 23-APR-13:05 | 11254.75 | 23-APR-16:22 | 0.00 |
May | 0.177161E+11 | 0.442096E+10 | 218.81 | 0.166338E+11 | 0.108234E+10 | 0.00 | 1.00 | 10-MAY-15:30 | 0.00 | 01-MAY-00:10 | 70399.43 | 25-MAY-16:00 | 67812.47 | 18-MAY-14:30 | 18842.99 | 26-MAY-11:00 | 18150.46 | 25-MAY-16:00 | 0.00 |
June | 0.396667E+11 | 0.983388E+10 | 352.22 | 0.313735E+11 | 0.829326E+10 | 0.00 | 1.00 | 01-JUN-12:10 | 0.00 | 01-JUN-00:10 | 119644.99 | 30-JUN-04:03 | 77596.59 | 30-JUN-14:50 | 57774.17 | 30-JUN-04:03 | 27874.64 | 30-JUN-04:03 | 0.00 |
July | 0.527514E+11 | 0.128150E+11 | 398.15 | 0.396554E+11 | 0.130960E+11 | 0.00 | 1.00 | 03-JUL-12:02 | 0.00 | 01-JUL-00:10 | 123325.96 | 05-JUL-10:40 | 80095.23 | 23-JUL-15:32 | 80622.70 | 05-JUL-11:00 | 28827.69 | 23-JUL-16:52 | 0.00 |
August | 0.386107E+11 | 0.943122E+10 | 382.19 | 0.278113E+11 | 0.107994E+11 | 0.00 | 1.00 | 04-AUG-12:30 | 0.00 | 01-AUG-00:10 | 102242.54 | 29-AUG-15:20 | 70322.63 | 08-AUG-15:10 | 44103.26 | 09-AUG-12:40 | 23904.35 | 29-AUG-15:20 | 0.00 |
September | 0.803836E+10 | 0.204876E+10 | 159.91 | 0.661918E+10 | 0.141919E+10 | 0.00 | 1.00 | 01-SEP-09:00 | 0.00 | 01-SEP-00:10 | 73617.47 | 01-SEP-14:00 | 66181.90 | 01-SEP-15:50 | 18576.61 | 01-SEP-12:40 | 17551.86 | 01-SEP-14:00 | 0.00 |
October | 0.108656E+10 | 0.291073E+09 | 35.70 | 0.102330E+10 | 63250572.20 | 0.00 | 0.72 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 24110.18 | 19-OCT-15:00 | 24110.18 | 19-OCT-15:00 | 4005.48 | 22-OCT-12:01 | 5959.77 | 19-OCT-15:00 | 0.00 |
November | 0.171298E+09 | 48184309.61 | 15.23 | 0.118785E+09 | 52513217.60 | 0.00 | 0.30 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 | 8828.19 | 01-NOV-15:00 | 6032.64 | 01-NOV-15:00 | 2795.55 | 01-NOV-15:00 | 2437.89 | 01-NOV-15:00 | 0.00 |
December | 899206.62 | 262009.65 | 0.18 | 893564.06 | 5642.56 | 0.00 | 0.12 | 06-DEC-07:01 | 0.00 | 01-DEC-00:10 | 3342.07 | 06-DEC-07:01 | 3342.07 | 06-DEC-07:01 | 58.08 | 06-DEC-07:11 | 963.43 | 06-DEC-07:01 | 0.00 |
Annual Sum or Average | 0.159498E+12 | 0.392830E+11 | 1646.22 | 0.124639E+12 | 0.348590E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 506289.58 | 148829.82 | 0.18 | 506289.58 | -0.0 | 0.00 | 0.07 | 0.00 | 1892.11 | 1892.11 | 0.00 | 551.85 | 0.00 | ||||||
Maximum of Months | 0.527514E+11 | 0.128150E+11 | 398.15 | 0.396554E+11 | 0.130960E+11 | 0.00 | 1.00 | 0.00 | 123325.96 | 80095.23 | 80622.70 | 28827.69 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.85 | 0.00 | 353.85 | 10.41 | 2536.15 | 0.00 | 0.00 | 0.00 |
February | 543.54 | 0.00 | 543.54 | 76.26 | 1973.72 | 0.00 | 0.00 | 0.00 |
March | 668.73 | 0.00 | 668.73 | 166.40 | 1519.01 | 0.00 | 0.00 | 0.00 |
April | 876.85 | 7.03 | 869.82 | 498.57 | 904.61 | 0.00 | 0.00 | 0.00 |
May | 1234.05 | 67.45 | 1166.60 | 1146.94 | 507.33 | 0.00 | 0.00 | 0.00 |
June | 1377.80 | 153.02 | 1224.78 | 1513.28 | 356.19 | 0.00 | 0.00 | 0.00 |
July | 1315.80 | 114.26 | 1201.54 | 1502.84 | 339.05 | 0.00 | 0.00 | 0.00 |
August | 998.65 | 17.51 | 981.14 | 1047.10 | 393.33 | 0.00 | 0.00 | 0.00 |
September | 777.94 | 0.20 | 777.74 | 636.36 | 622.76 | 0.00 | 0.00 | 0.00 |
October | 540.16 | 0.00 | 540.16 | 264.10 | 921.89 | 0.00 | 0.00 | 0.00 |
November | 357.65 | 0.00 | 357.65 | 51.44 | 1422.95 | 0.00 | 0.00 | 0.00 |
December | 299.81 | 0.00 | 299.81 | 2.71 | 2423.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 779.92 | 30.09 | 749.82 | 579.40 | 1156.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 299.81 | 0.00 | 299.81 | 2.71 | 339.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1377.80 | 153.02 | 1224.78 | 1513.28 | 2536.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 517.97 | 216.68 | 301.30 | 228.64 | 1525.99 | 0.00 | 0.00 | 0.00 |
February | 813.30 | 347.25 | 466.05 | 526.38 | 1188.60 | 0.00 | 0.00 | 0.00 |
March | 1106.79 | 554.89 | 551.90 | 882.70 | 935.15 | 0.00 | 0.00 | 0.00 |
April | 1533.62 | 826.50 | 707.12 | 1509.41 | 579.01 | 0.00 | 0.00 | 0.00 |
May | 1660.24 | 729.16 | 931.07 | 1822.99 | 343.46 | 0.00 | 0.00 | 0.00 |
June | 1879.36 | 898.20 | 981.17 | 2224.52 | 242.91 | 0.00 | 0.00 | 0.00 |
July | 1840.97 | 863.54 | 977.43 | 2229.05 | 228.85 | 0.00 | 0.00 | 0.00 |
August | 1419.54 | 619.81 | 799.72 | 1661.16 | 262.22 | 0.00 | 0.00 | 0.00 |
September | 1137.08 | 508.61 | 628.47 | 1204.86 | 401.11 | 0.00 | 0.00 | 0.00 |
October | 688.96 | 261.29 | 427.67 | 573.18 | 587.30 | 0.00 | 0.00 | 0.00 |
November | 439.02 | 147.09 | 291.94 | 240.38 | 882.17 | 0.00 | 0.00 | 0.00 |
December | 400.78 | 148.51 | 252.27 | 143.16 | 1475.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1120.92 | 510.54 | 610.39 | 1106.52 | 719.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 400.78 | 147.09 | 252.27 | 143.16 | 228.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1879.36 | 898.20 | 981.17 | 2229.05 | 1525.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2430.41 | 1688.90 | 741.51 | 2130.66 | 2050.44 | 0.00 | 0.00 | 0.00 |
February | 3081.23 | 2079.84 | 1001.39 | 2996.88 | 1705.88 | 0.00 | 0.00 | 0.00 |
March | 2720.74 | 1722.65 | 998.08 | 2693.71 | 1410.53 | 0.00 | 0.00 | 0.00 |
April | 2469.18 | 1343.06 | 1126.11 | 2642.51 | 936.45 | 0.00 | 0.00 | 0.00 |
May | 2076.80 | 714.05 | 1362.75 | 2379.51 | 558.01 | 0.00 | 0.00 | 0.00 |
June | 1863.56 | 500.83 | 1362.74 | 2263.57 | 385.91 | 0.00 | 0.00 | 0.00 |
July | 2037.86 | 650.03 | 1387.83 | 2569.34 | 362.08 | 0.00 | 0.00 | 0.00 |
August | 2175.05 | 913.11 | 1261.94 | 2671.50 | 415.76 | 0.00 | 0.00 | 0.00 |
September | 2327.09 | 1240.93 | 1086.17 | 2673.02 | 638.19 | 0.00 | 0.00 | 0.00 |
October | 1983.87 | 1166.64 | 817.23 | 2058.85 | 898.13 | 0.00 | 0.00 | 0.00 |
November | 1763.94 | 1105.70 | 658.24 | 1644.80 | 1270.75 | 0.00 | 0.00 | 0.00 |
December | 1876.31 | 1228.59 | 647.72 | 1530.41 | 1971.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2228.27 | 1190.56 | 1037.71 | 2349.82 | 1047.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1763.94 | 500.83 | 647.72 | 1530.41 | 362.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3081.23 | 2079.84 | 1387.83 | 2996.88 | 2050.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 523.40 | 219.57 | 303.84 | 248.23 | 1559.97 | 0.00 | 0.00 | 0.00 |
February | 852.15 | 389.46 | 462.69 | 600.75 | 1236.71 | 0.00 | 0.00 | 0.00 |
March | 1120.03 | 572.76 | 547.26 | 927.67 | 973.24 | 0.00 | 0.00 | 0.00 |
April | 1430.26 | 723.72 | 706.55 | 1406.70 | 611.55 | 0.00 | 0.00 | 0.00 |
May | 1757.28 | 837.29 | 919.99 | 1977.16 | 368.28 | 0.00 | 0.00 | 0.00 |
June | 1696.29 | 732.79 | 963.50 | 2009.64 | 256.59 | 0.00 | 0.00 | 0.00 |
July | 1811.06 | 841.34 | 969.72 | 2203.51 | 245.45 | 0.00 | 0.00 | 0.00 |
August | 1490.30 | 676.63 | 813.68 | 1768.72 | 276.83 | 0.00 | 0.00 | 0.00 |
September | 1164.62 | 522.74 | 641.87 | 1253.68 | 418.33 | 0.00 | 0.00 | 0.00 |
October | 736.34 | 295.64 | 440.70 | 648.06 | 605.63 | 0.00 | 0.00 | 0.00 |
November | 447.62 | 151.22 | 296.41 | 258.42 | 903.23 | 0.00 | 0.00 | 0.00 |
December | 399.20 | 140.09 | 259.11 | 144.01 | 1499.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1120.52 | 509.32 | 611.20 | 1123.60 | 744.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 399.20 | 140.09 | 259.11 | 144.01 | 245.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1811.06 | 841.34 | 969.72 | 2203.51 | 1559.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.94 | 0.00 | 117.94 | 3.25 | 850.28 | 0.00 | 0.00 | 0.00 |
February | 181.17 | 0.00 | 181.17 | 25.32 | 666.55 | 0.00 | 0.00 | 0.00 |
March | 222.90 | 0.00 | 222.90 | 57.21 | 511.23 | 0.00 | 0.00 | 0.00 |
April | 292.27 | 2.34 | 289.93 | 172.39 | 305.21 | 0.00 | 0.00 | 0.00 |
May | 411.33 | 22.48 | 388.85 | 390.59 | 167.19 | 0.00 | 0.00 | 0.00 |
June | 459.25 | 51.01 | 408.24 | 511.05 | 118.05 | 0.00 | 0.00 | 0.00 |
July | 438.58 | 38.08 | 400.50 | 505.07 | 113.42 | 0.00 | 0.00 | 0.00 |
August | 332.87 | 5.84 | 327.03 | 349.55 | 135.68 | 0.00 | 0.00 | 0.00 |
September | 259.30 | 0.07 | 259.23 | 207.44 | 223.85 | 0.00 | 0.00 | 0.00 |
October | 180.04 | 0.00 | 180.04 | 81.09 | 337.07 | 0.00 | 0.00 | 0.00 |
November | 119.21 | 0.00 | 119.21 | 15.21 | 504.23 | 0.00 | 0.00 | 0.00 |
December | 99.93 | 0.00 | 99.93 | 0.53 | 820.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 259.96 | 10.03 | 249.93 | 194.24 | 395.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.93 | 0.00 | 99.93 | 0.53 | 113.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 459.25 | 51.01 | 408.24 | 511.05 | 850.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.95 | 0.00 | 117.95 | 3.25 | 850.33 | 0.00 | 0.00 | 0.00 |
February | 181.18 | 0.00 | 181.18 | 25.32 | 666.59 | 0.00 | 0.00 | 0.00 |
March | 222.91 | 0.00 | 222.91 | 57.21 | 511.26 | 0.00 | 0.00 | 0.00 |
April | 292.29 | 2.34 | 289.95 | 172.40 | 305.23 | 0.00 | 0.00 | 0.00 |
May | 411.36 | 22.48 | 388.87 | 390.62 | 167.20 | 0.00 | 0.00 | 0.00 |
June | 459.28 | 51.01 | 408.27 | 511.08 | 118.06 | 0.00 | 0.00 | 0.00 |
July | 438.61 | 38.09 | 400.52 | 505.10 | 113.43 | 0.00 | 0.00 | 0.00 |
August | 332.89 | 5.84 | 327.05 | 349.58 | 135.69 | 0.00 | 0.00 | 0.00 |
September | 259.32 | 0.07 | 259.25 | 207.45 | 223.87 | 0.00 | 0.00 | 0.00 |
October | 180.06 | 0.00 | 180.06 | 81.09 | 337.09 | 0.00 | 0.00 | 0.00 |
November | 119.22 | 0.00 | 119.22 | 15.21 | 504.26 | 0.00 | 0.00 | 0.00 |
December | 99.94 | 0.00 | 99.94 | 0.53 | 820.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 259.98 | 10.03 | 249.95 | 194.25 | 395.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.94 | 0.00 | 99.94 | 0.53 | 113.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 459.28 | 51.01 | 408.27 | 511.08 | 850.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.95 | 0.00 | 117.95 | 3.25 | 850.33 | 0.00 | 0.00 | 0.00 |
February | 181.18 | 0.00 | 181.18 | 25.32 | 666.59 | 0.00 | 0.00 | 0.00 |
March | 222.91 | 0.00 | 222.91 | 57.21 | 511.26 | 0.00 | 0.00 | 0.00 |
April | 292.29 | 2.34 | 289.95 | 172.40 | 305.23 | 0.00 | 0.00 | 0.00 |
May | 411.36 | 22.48 | 388.87 | 390.62 | 167.20 | 0.00 | 0.00 | 0.00 |
June | 459.28 | 51.01 | 408.27 | 511.08 | 118.06 | 0.00 | 0.00 | 0.00 |
July | 438.61 | 38.09 | 400.52 | 505.10 | 113.43 | 0.00 | 0.00 | 0.00 |
August | 332.89 | 5.84 | 327.05 | 349.58 | 135.69 | 0.00 | 0.00 | 0.00 |
September | 259.32 | 0.07 | 259.25 | 207.45 | 223.87 | 0.00 | 0.00 | 0.00 |
October | 180.06 | 0.00 | 180.06 | 81.09 | 337.09 | 0.00 | 0.00 | 0.00 |
November | 119.22 | 0.00 | 119.22 | 15.21 | 504.26 | 0.00 | 0.00 | 0.00 |
December | 99.94 | 0.00 | 99.94 | 0.53 | 820.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 259.98 | 10.03 | 249.95 | 194.25 | 395.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.94 | 0.00 | 99.94 | 0.53 | 113.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 459.28 | 51.01 | 408.27 | 511.08 | 850.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 498.27 | 208.43 | 289.84 | 221.31 | 1481.80 | 0.00 | 0.00 | 0.00 |
February | 782.36 | 334.04 | 448.32 | 507.91 | 1165.19 | 0.00 | 0.00 | 0.00 |
March | 1064.68 | 533.78 | 530.91 | 855.75 | 918.67 | 0.00 | 0.00 | 0.00 |
April | 1475.28 | 795.06 | 680.22 | 1459.17 | 581.38 | 0.00 | 0.00 | 0.00 |
May | 1597.08 | 701.42 | 895.65 | 1763.97 | 338.90 | 0.00 | 0.00 | 0.00 |
June | 1807.86 | 864.02 | 943.84 | 2150.14 | 241.54 | 0.00 | 0.00 | 0.00 |
July | 1770.94 | 830.69 | 940.25 | 2150.24 | 229.29 | 0.00 | 0.00 | 0.00 |
August | 1365.53 | 596.23 | 769.30 | 1598.26 | 270.64 | 0.00 | 0.00 | 0.00 |
September | 1093.83 | 489.26 | 604.56 | 1148.89 | 423.64 | 0.00 | 0.00 | 0.00 |
October | 662.75 | 251.35 | 411.40 | 535.26 | 625.10 | 0.00 | 0.00 | 0.00 |
November | 422.32 | 141.49 | 280.83 | 224.92 | 906.48 | 0.00 | 0.00 | 0.00 |
December | 385.53 | 142.86 | 242.67 | 137.02 | 1444.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1078.28 | 491.11 | 587.17 | 1065.29 | 717.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 385.53 | 141.49 | 242.67 | 137.02 | 229.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1807.86 | 864.02 | 943.84 | 2150.24 | 1481.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.70 | 8.24 | 11.46 | 8.75 | 58.59 | 0.00 | 0.00 | 0.00 |
February | 30.93 | 13.21 | 17.73 | 20.08 | 46.07 | 0.00 | 0.00 | 0.00 |
March | 42.10 | 21.10 | 20.99 | 33.84 | 36.32 | 0.00 | 0.00 | 0.00 |
April | 58.33 | 31.44 | 26.90 | 57.69 | 22.99 | 0.00 | 0.00 | 0.00 |
May | 63.15 | 27.73 | 35.41 | 69.75 | 13.40 | 0.00 | 0.00 | 0.00 |
June | 71.48 | 34.16 | 37.32 | 85.01 | 9.55 | 0.00 | 0.00 | 0.00 |
July | 70.02 | 32.84 | 37.18 | 85.02 | 9.07 | 0.00 | 0.00 | 0.00 |
August | 53.99 | 23.57 | 30.42 | 63.19 | 10.70 | 0.00 | 0.00 | 0.00 |
September | 43.25 | 19.34 | 23.90 | 45.43 | 16.75 | 0.00 | 0.00 | 0.00 |
October | 26.20 | 9.94 | 16.27 | 21.16 | 24.72 | 0.00 | 0.00 | 0.00 |
November | 16.70 | 5.59 | 11.10 | 8.89 | 35.84 | 0.00 | 0.00 | 0.00 |
December | 15.24 | 5.65 | 9.59 | 5.42 | 57.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.63 | 19.42 | 23.22 | 42.12 | 28.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.24 | 5.59 | 9.59 | 5.42 | 9.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.48 | 34.16 | 37.32 | 85.02 | 58.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 810.16 | 562.98 | 247.18 | 728.13 | 671.07 | 0.00 | 0.00 | 0.00 |
February | 1027.11 | 693.30 | 333.81 | 1016.63 | 573.01 | 0.00 | 0.00 | 0.00 |
March | 906.94 | 574.24 | 332.70 | 914.43 | 475.42 | 0.00 | 0.00 | 0.00 |
April | 823.08 | 447.70 | 375.38 | 892.64 | 321.89 | 0.00 | 0.00 | 0.00 |
May | 692.29 | 238.02 | 454.26 | 804.68 | 187.41 | 0.00 | 0.00 | 0.00 |
June | 621.21 | 166.95 | 454.26 | 763.59 | 128.78 | 0.00 | 0.00 | 0.00 |
July | 679.31 | 216.68 | 462.62 | 861.37 | 124.46 | 0.00 | 0.00 | 0.00 |
August | 725.04 | 304.38 | 420.66 | 894.22 | 147.66 | 0.00 | 0.00 | 0.00 |
September | 775.72 | 413.66 | 362.07 | 892.79 | 231.56 | 0.00 | 0.00 | 0.00 |
October | 661.31 | 388.89 | 272.42 | 684.00 | 329.91 | 0.00 | 0.00 | 0.00 |
November | 588.00 | 368.58 | 219.42 | 550.42 | 448.66 | 0.00 | 0.00 | 0.00 |
December | 625.46 | 409.54 | 215.91 | 520.43 | 652.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 742.78 | 396.87 | 345.91 | 791.98 | 356.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 588.00 | 166.95 | 215.91 | 520.43 | 124.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1027.11 | 693.30 | 462.62 | 1016.63 | 671.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 810.16 | 562.98 | 247.18 | 728.13 | 671.07 | 0.00 | 0.00 | 0.00 |
February | 1027.11 | 693.30 | 333.81 | 1016.63 | 573.01 | 0.00 | 0.00 | 0.00 |
March | 906.94 | 574.24 | 332.70 | 914.43 | 475.42 | 0.00 | 0.00 | 0.00 |
April | 823.08 | 447.70 | 375.38 | 892.64 | 321.89 | 0.00 | 0.00 | 0.00 |
May | 692.29 | 238.02 | 454.26 | 804.68 | 187.41 | 0.00 | 0.00 | 0.00 |
June | 621.21 | 166.95 | 454.26 | 763.59 | 128.78 | 0.00 | 0.00 | 0.00 |
July | 679.31 | 216.68 | 462.62 | 861.37 | 124.46 | 0.00 | 0.00 | 0.00 |
August | 725.04 | 304.38 | 420.66 | 894.22 | 147.66 | 0.00 | 0.00 | 0.00 |
September | 775.72 | 413.66 | 362.07 | 892.79 | 231.56 | 0.00 | 0.00 | 0.00 |
October | 661.31 | 388.89 | 272.42 | 684.00 | 329.91 | 0.00 | 0.00 | 0.00 |
November | 588.00 | 368.58 | 219.42 | 550.42 | 448.66 | 0.00 | 0.00 | 0.00 |
December | 625.46 | 409.54 | 215.91 | 520.43 | 652.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 742.78 | 396.87 | 345.91 | 791.98 | 356.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 588.00 | 166.95 | 215.91 | 520.43 | 124.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1027.11 | 693.30 | 462.62 | 1016.63 | 671.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 810.11 | 562.95 | 247.16 | 728.09 | 671.03 | 0.00 | 0.00 | 0.00 |
February | 1027.04 | 693.26 | 333.78 | 1016.57 | 572.98 | 0.00 | 0.00 | 0.00 |
March | 906.88 | 574.20 | 332.68 | 914.37 | 475.39 | 0.00 | 0.00 | 0.00 |
April | 823.03 | 447.67 | 375.36 | 892.58 | 321.87 | 0.00 | 0.00 | 0.00 |
May | 692.24 | 238.01 | 454.23 | 804.63 | 187.39 | 0.00 | 0.00 | 0.00 |
June | 621.17 | 166.94 | 454.23 | 763.54 | 128.77 | 0.00 | 0.00 | 0.00 |
July | 679.26 | 216.67 | 462.59 | 861.32 | 124.45 | 0.00 | 0.00 | 0.00 |
August | 724.99 | 304.36 | 420.63 | 894.16 | 147.65 | 0.00 | 0.00 | 0.00 |
September | 775.67 | 413.63 | 362.04 | 892.73 | 231.54 | 0.00 | 0.00 | 0.00 |
October | 661.27 | 388.87 | 272.40 | 683.96 | 329.89 | 0.00 | 0.00 | 0.00 |
November | 587.96 | 368.56 | 219.41 | 550.38 | 448.63 | 0.00 | 0.00 | 0.00 |
December | 625.42 | 409.52 | 215.90 | 520.40 | 652.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 742.73 | 396.84 | 345.89 | 791.93 | 356.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 587.96 | 166.94 | 215.90 | 520.40 | 124.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1027.04 | 693.26 | 462.59 | 1016.57 | 671.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 503.49 | 211.21 | 292.28 | 242.06 | 1513.67 | 0.00 | 0.00 | 0.00 |
February | 819.73 | 374.65 | 445.08 | 583.44 | 1212.41 | 0.00 | 0.00 | 0.00 |
March | 1077.42 | 550.97 | 526.44 | 901.76 | 956.29 | 0.00 | 0.00 | 0.00 |
April | 1375.85 | 696.18 | 679.67 | 1362.01 | 611.90 | 0.00 | 0.00 | 0.00 |
May | 1690.43 | 805.44 | 884.99 | 1910.50 | 365.11 | 0.00 | 0.00 | 0.00 |
June | 1631.76 | 704.91 | 926.84 | 1941.94 | 253.24 | 0.00 | 0.00 | 0.00 |
July | 1742.17 | 809.34 | 932.83 | 2123.55 | 247.39 | 0.00 | 0.00 | 0.00 |
August | 1433.61 | 650.88 | 782.72 | 1699.94 | 286.05 | 0.00 | 0.00 | 0.00 |
September | 1120.31 | 502.85 | 617.46 | 1194.90 | 441.86 | 0.00 | 0.00 | 0.00 |
October | 708.32 | 284.39 | 423.94 | 609.33 | 644.68 | 0.00 | 0.00 | 0.00 |
November | 430.60 | 145.47 | 285.13 | 243.78 | 925.59 | 0.00 | 0.00 | 0.00 |
December | 384.01 | 134.76 | 249.25 | 138.70 | 1466.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1077.89 | 489.94 | 587.95 | 1082.24 | 741.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 384.01 | 134.76 | 249.25 | 138.70 | 247.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1742.17 | 809.34 | 932.83 | 2123.55 | 1513.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.91 | 8.35 | 11.56 | 9.57 | 59.85 | 0.00 | 0.00 | 0.00 |
February | 32.41 | 14.81 | 17.60 | 23.07 | 47.94 | 0.00 | 0.00 | 0.00 |
March | 42.60 | 21.78 | 20.82 | 35.65 | 37.81 | 0.00 | 0.00 | 0.00 |
April | 54.40 | 27.53 | 26.87 | 53.85 | 24.19 | 0.00 | 0.00 | 0.00 |
May | 66.84 | 31.85 | 34.99 | 75.54 | 14.44 | 0.00 | 0.00 | 0.00 |
June | 64.52 | 27.87 | 36.65 | 76.78 | 10.01 | 0.00 | 0.00 | 0.00 |
July | 68.88 | 32.00 | 36.88 | 83.96 | 9.78 | 0.00 | 0.00 | 0.00 |
August | 56.68 | 25.74 | 30.95 | 67.21 | 11.31 | 0.00 | 0.00 | 0.00 |
September | 44.30 | 19.88 | 24.41 | 47.25 | 17.47 | 0.00 | 0.00 | 0.00 |
October | 28.01 | 11.24 | 16.76 | 24.09 | 25.49 | 0.00 | 0.00 | 0.00 |
November | 17.03 | 5.75 | 11.27 | 9.64 | 36.60 | 0.00 | 0.00 | 0.00 |
December | 15.18 | 5.33 | 9.86 | 5.48 | 58.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.62 | 19.37 | 23.25 | 42.79 | 29.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.18 | 5.33 | 9.86 | 5.48 | 9.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.88 | 32.00 | 36.88 | 83.96 | 59.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.85 | 0.00 | 353.85 | 9.28 | 2581.23 | 0.00 | 0.00 | 0.00 |
February | 543.54 | 0.00 | 543.54 | 71.48 | 2025.88 | 0.00 | 0.00 | 0.00 |
March | 668.73 | 0.00 | 668.73 | 157.57 | 1577.87 | 0.00 | 0.00 | 0.00 |
April | 876.85 | 7.03 | 869.82 | 478.55 | 962.78 | 0.00 | 0.00 | 0.00 |
May | 1234.05 | 67.45 | 1166.60 | 1130.84 | 531.68 | 0.00 | 0.00 | 0.00 |
June | 1377.80 | 153.02 | 1224.78 | 1505.21 | 371.03 | 0.00 | 0.00 | 0.00 |
July | 1315.80 | 114.26 | 1201.54 | 1497.71 | 350.80 | 0.00 | 0.00 | 0.00 |
August | 998.65 | 17.51 | 981.14 | 1039.64 | 412.12 | 0.00 | 0.00 | 0.00 |
September | 777.94 | 0.20 | 777.74 | 617.76 | 667.57 | 0.00 | 0.00 | 0.00 |
October | 540.16 | 0.00 | 540.16 | 243.25 | 995.08 | 0.00 | 0.00 | 0.00 |
November | 357.65 | 0.00 | 357.65 | 45.35 | 1494.90 | 0.00 | 0.00 | 0.00 |
December | 299.81 | 0.00 | 299.81 | 1.74 | 2474.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 779.92 | 30.09 | 749.82 | 569.56 | 1200.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 299.81 | 0.00 | 299.81 | 1.74 | 350.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1377.80 | 153.02 | 1224.78 | 1505.21 | 2581.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 517.97 | 216.68 | 301.30 | 225.99 | 1552.32 | 0.00 | 0.00 | 0.00 |
February | 813.30 | 347.25 | 466.05 | 519.60 | 1220.15 | 0.00 | 0.00 | 0.00 |
March | 1106.79 | 554.89 | 551.90 | 872.95 | 971.86 | 0.00 | 0.00 | 0.00 |
April | 1533.62 | 826.50 | 707.12 | 1496.60 | 612.62 | 0.00 | 0.00 | 0.00 |
May | 1660.24 | 729.16 | 931.07 | 1815.88 | 358.43 | 0.00 | 0.00 | 0.00 |
June | 1879.36 | 898.20 | 981.17 | 2222.13 | 252.54 | 0.00 | 0.00 | 0.00 |
July | 1840.97 | 863.54 | 977.43 | 2227.99 | 236.46 | 0.00 | 0.00 | 0.00 |
August | 1419.54 | 619.81 | 799.72 | 1658.45 | 273.63 | 0.00 | 0.00 | 0.00 |
September | 1137.08 | 508.61 | 628.47 | 1194.61 | 425.76 | 0.00 | 0.00 | 0.00 |
October | 688.96 | 261.29 | 427.67 | 559.06 | 629.41 | 0.00 | 0.00 | 0.00 |
November | 439.02 | 147.09 | 291.94 | 232.74 | 926.32 | 0.00 | 0.00 | 0.00 |
December | 400.78 | 148.51 | 252.27 | 140.60 | 1506.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1120.92 | 510.54 | 610.39 | 1099.89 | 745.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 400.78 | 147.09 | 252.27 | 140.60 | 236.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1879.36 | 898.20 | 981.17 | 2227.99 | 1552.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2430.41 | 1688.90 | 741.51 | 2121.59 | 2091.94 | 0.00 | 0.00 | 0.00 |
February | 3081.23 | 2079.84 | 1001.39 | 2983.17 | 1759.08 | 0.00 | 0.00 | 0.00 |
March | 2720.74 | 1722.65 | 998.08 | 2679.36 | 1468.88 | 0.00 | 0.00 | 0.00 |
April | 2469.18 | 1343.06 | 1126.11 | 2626.37 | 992.02 | 0.00 | 0.00 | 0.00 |
May | 2076.80 | 714.05 | 1362.75 | 2370.69 | 585.65 | 0.00 | 0.00 | 0.00 |
June | 1863.56 | 500.83 | 1362.74 | 2258.25 | 403.51 | 0.00 | 0.00 | 0.00 |
July | 2037.86 | 650.03 | 1387.83 | 2566.68 | 375.81 | 0.00 | 0.00 | 0.00 |
August | 2175.05 | 913.11 | 1261.94 | 2667.46 | 435.46 | 0.00 | 0.00 | 0.00 |
September | 2327.09 | 1240.93 | 1086.17 | 2659.78 | 678.92 | 0.00 | 0.00 | 0.00 |
October | 1983.87 | 1166.64 | 817.23 | 2036.39 | 963.98 | 0.00 | 0.00 | 0.00 |
November | 1763.94 | 1105.70 | 658.24 | 1627.89 | 1337.88 | 0.00 | 0.00 | 0.00 |
December | 1876.31 | 1228.59 | 647.72 | 1519.46 | 2018.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2228.27 | 1190.56 | 1037.71 | 2338.38 | 1089.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1763.94 | 500.83 | 647.72 | 1519.46 | 375.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3081.23 | 2079.84 | 1387.83 | 2983.17 | 2091.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 523.40 | 219.57 | 303.84 | 246.53 | 1586.67 | 0.00 | 0.00 | 0.00 |
February | 852.15 | 389.46 | 462.69 | 595.88 | 1269.77 | 0.00 | 0.00 | 0.00 |
March | 1120.03 | 572.76 | 547.26 | 921.21 | 1011.69 | 0.00 | 0.00 | 0.00 |
April | 1430.26 | 723.72 | 706.55 | 1395.51 | 647.72 | 0.00 | 0.00 | 0.00 |
May | 1757.28 | 837.29 | 919.99 | 1969.94 | 385.86 | 0.00 | 0.00 | 0.00 |
June | 1696.29 | 732.79 | 963.50 | 2005.49 | 267.74 | 0.00 | 0.00 | 0.00 |
July | 1811.06 | 841.34 | 969.72 | 2201.51 | 254.21 | 0.00 | 0.00 | 0.00 |
August | 1490.30 | 676.63 | 813.68 | 1764.48 | 289.75 | 0.00 | 0.00 | 0.00 |
September | 1164.62 | 522.74 | 641.87 | 1242.51 | 445.60 | 0.00 | 0.00 | 0.00 |
October | 736.34 | 295.64 | 440.70 | 635.17 | 649.99 | 0.00 | 0.00 | 0.00 |
November | 447.62 | 151.22 | 296.41 | 251.77 | 948.18 | 0.00 | 0.00 | 0.00 |
December | 399.20 | 140.09 | 259.11 | 141.96 | 1531.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1120.52 | 509.32 | 611.20 | 1117.39 | 772.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 399.20 | 140.09 | 259.11 | 141.96 | 254.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1811.06 | 841.34 | 969.72 | 2201.51 | 1586.67 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.947751E+09 | 0.00 | 0.947751E+09 | 27874511.57 | 0.679282E+10 |
February | 0.131493E+10 | 0.00 | 0.131493E+10 | 0.184481E+09 | 0.477483E+10 |
March | 0.179113E+10 | 0.00 | 0.179113E+10 | 0.445688E+09 | 0.406851E+10 |
April | 0.227280E+10 | 18219161.88 | 0.225458E+10 | 0.129229E+10 | 0.234474E+10 |
May | 0.330529E+10 | 0.180659E+09 | 0.312463E+10 | 0.307197E+10 | 0.135884E+10 |
June | 0.357127E+10 | 0.396639E+09 | 0.317463E+10 | 0.392243E+10 | 0.923251E+09 |
July | 0.352425E+10 | 0.306032E+09 | 0.321822E+10 | 0.402520E+10 | 0.908101E+09 |
August | 0.267478E+10 | 46901125.33 | 0.262788E+10 | 0.280456E+10 | 0.105349E+10 |
September | 0.201642E+10 | 514326.90 | 0.201591E+10 | 0.164945E+10 | 0.161420E+10 |
October | 0.144676E+10 | 0.00 | 0.144676E+10 | 0.707377E+09 | 0.246920E+10 |
November | 0.927034E+09 | 0.00 | 0.927034E+09 | 0.133330E+09 | 0.368828E+10 |
December | 0.803011E+09 | 0.00 | 0.803011E+09 | 7251125.96 | 0.648996E+10 |
Annual Sum or Average | 0.245954E+11 | 0.948964E+09 | 0.236465E+11 | 0.182719E+11 | 0.364862E+11 |
Minimum of Months | 0.803011E+09 | 0.00 | 0.803011E+09 | 7251125.96 | 0.908101E+09 |
Maximum of Months | 0.357127E+10 | 0.396639E+09 | 0.321822E+10 | 0.402520E+10 | 0.679282E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138734E+10 | 0.580346E+09 | 0.806996E+09 | 0.612385E+09 | 0.408721E+10 |
February | 0.196753E+10 | 0.840067E+09 | 0.112746E+10 | 0.127342E+10 | 0.287546E+10 |
March | 0.296442E+10 | 0.148621E+10 | 0.147821E+10 | 0.236423E+10 | 0.250470E+10 |
April | 0.397515E+10 | 0.214229E+10 | 0.183285E+10 | 0.391240E+10 | 0.150080E+10 |
May | 0.444678E+10 | 0.195299E+10 | 0.249379E+10 | 0.488269E+10 | 0.919917E+09 |
June | 0.487130E+10 | 0.232812E+10 | 0.254318E+10 | 0.576596E+10 | 0.629627E+09 |
July | 0.493087E+10 | 0.231292E+10 | 0.261795E+10 | 0.597028E+10 | 0.612956E+09 |
August | 0.380208E+10 | 0.166010E+10 | 0.214198E+10 | 0.444926E+10 | 0.702321E+09 |
September | 0.294732E+10 | 0.131832E+10 | 0.162900E+10 | 0.312300E+10 | 0.103968E+10 |
October | 0.184531E+10 | 0.699847E+09 | 0.114547E+10 | 0.153522E+10 | 0.157303E+10 |
November | 0.113795E+10 | 0.381250E+09 | 0.756701E+09 | 0.623074E+09 | 0.228659E+10 |
December | 0.107344E+10 | 0.397766E+09 | 0.675671E+09 | 0.383441E+09 | 0.395118E+10 |
Annual Sum or Average | 0.353495E+11 | 0.161002E+11 | 0.192493E+11 | 0.348953E+11 | 0.226835E+11 |
Minimum of Months | 0.107344E+10 | 0.381250E+09 | 0.675671E+09 | 0.383441E+09 | 0.612956E+09 |
Maximum of Months | 0.493087E+10 | 0.232812E+10 | 0.261795E+10 | 0.597028E+10 | 0.408721E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.650961E+10 | 0.452355E+10 | 0.198606E+10 | 0.570676E+10 | 0.549189E+10 |
February | 0.745411E+10 | 0.503156E+10 | 0.242255E+10 | 0.725004E+10 | 0.412686E+10 |
March | 0.728722E+10 | 0.461396E+10 | 0.267326E+10 | 0.721483E+10 | 0.377796E+10 |
April | 0.640010E+10 | 0.348122E+10 | 0.291888E+10 | 0.684939E+10 | 0.242727E+10 |
May | 0.556249E+10 | 0.191250E+10 | 0.364999E+10 | 0.637329E+10 | 0.149458E+10 |
June | 0.483036E+10 | 0.129815E+10 | 0.353221E+10 | 0.586718E+10 | 0.100027E+10 |
July | 0.545821E+10 | 0.174104E+10 | 0.371717E+10 | 0.688173E+10 | 0.969808E+09 |
August | 0.582566E+10 | 0.244568E+10 | 0.337998E+10 | 0.715536E+10 | 0.111357E+10 |
September | 0.603183E+10 | 0.321649E+10 | 0.281534E+10 | 0.692846E+10 | 0.165418E+10 |
October | 0.531360E+10 | 0.312473E+10 | 0.218887E+10 | 0.551443E+10 | 0.240554E+10 |
November | 0.457213E+10 | 0.286597E+10 | 0.170616E+10 | 0.426333E+10 | 0.329380E+10 |
December | 0.502552E+10 | 0.329066E+10 | 0.173486E+10 | 0.409905E+10 | 0.528017E+10 |
Annual Sum or Average | 0.702708E+11 | 0.375455E+11 | 0.327253E+11 | 0.741039E+11 | 0.330359E+11 |
Minimum of Months | 0.457213E+10 | 0.129815E+10 | 0.170616E+10 | 0.409905E+10 | 0.969808E+09 |
Maximum of Months | 0.745411E+10 | 0.503156E+10 | 0.371717E+10 | 0.725004E+10 | 0.549189E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140189E+10 | 0.588084E+09 | 0.813801E+09 | 0.664855E+09 | 0.417822E+10 |
February | 0.206152E+10 | 0.942189E+09 | 0.111933E+10 | 0.145334E+10 | 0.299186E+10 |
March | 0.299988E+10 | 0.153409E+10 | 0.146579E+10 | 0.248468E+10 | 0.260672E+10 |
April | 0.370724E+10 | 0.187587E+10 | 0.183137E+10 | 0.364617E+10 | 0.158513E+10 |
May | 0.470670E+10 | 0.224261E+10 | 0.246409E+10 | 0.529562E+10 | 0.986402E+09 |
June | 0.439677E+10 | 0.189939E+10 | 0.249738E+10 | 0.520898E+10 | 0.665072E+09 |
July | 0.485075E+10 | 0.225346E+10 | 0.259730E+10 | 0.590187E+10 | 0.657422E+09 |
August | 0.399163E+10 | 0.181228E+10 | 0.217935E+10 | 0.473733E+10 | 0.741474E+09 |
September | 0.301868E+10 | 0.135494E+10 | 0.166374E+10 | 0.324954E+10 | 0.108431E+10 |
October | 0.197220E+10 | 0.791831E+09 | 0.118037E+10 | 0.173577E+10 | 0.162213E+10 |
November | 0.116024E+10 | 0.391959E+09 | 0.768282E+09 | 0.669815E+09 | 0.234116E+10 |
December | 0.106921E+10 | 0.375211E+09 | 0.693995E+09 | 0.385730E+09 | 0.401741E+10 |
Annual Sum or Average | 0.353367E+11 | 0.160619E+11 | 0.192748E+11 | 0.354337E+11 | 0.234773E+11 |
Minimum of Months | 0.106921E+10 | 0.375211E+09 | 0.693995E+09 | 0.385730E+09 | 0.657422E+09 |
Maximum of Months | 0.485075E+10 | 0.225346E+10 | 0.259730E+10 | 0.590187E+10 | 0.417822E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315902E+09 | 0.00 | 0.315902E+09 | 8716182.47 | 0.227739E+10 |
February | 0.438290E+09 | 0.00 | 0.438290E+09 | 61245315.30 | 0.161252E+10 |
March | 0.597016E+09 | 0.00 | 0.597016E+09 | 0.153225E+09 | 0.136927E+10 |
April | 0.757565E+09 | 6072766.63 | 0.751492E+09 | 0.446840E+09 | 0.791105E+09 |
May | 0.110171E+10 | 60216724.37 | 0.104149E+10 | 0.104616E+10 | 0.447805E+09 |
June | 0.119037E+10 | 0.132207E+09 | 0.105816E+10 | 0.132464E+10 | 0.305982E+09 |
July | 0.117469E+10 | 0.102006E+09 | 0.107269E+10 | 0.135279E+10 | 0.303794E+09 |
August | 0.891552E+09 | 15632968.78 | 0.875919E+09 | 0.936248E+09 | 0.363405E+09 |
September | 0.672108E+09 | 171434.19 | 0.671937E+09 | 0.537673E+09 | 0.580224E+09 |
October | 0.482229E+09 | 0.00 | 0.482229E+09 | 0.217184E+09 | 0.902805E+09 |
November | 0.308997E+09 | 0.00 | 0.308997E+09 | 39423849.56 | 0.130695E+10 |
December | 0.267658E+09 | 0.00 | 0.267658E+09 | 1427331.53 | 0.219742E+10 |
Annual Sum or Average | 0.819809E+10 | 0.316307E+09 | 0.788178E+10 | 0.612557E+10 | 0.124587E+11 |
Minimum of Months | 0.267658E+09 | 0.00 | 0.267658E+09 | 1427331.53 | 0.303794E+09 |
Maximum of Months | 0.119037E+10 | 0.132207E+09 | 0.107269E+10 | 0.135279E+10 | 0.227739E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315922E+09 | 0.00 | 0.315922E+09 | 8716733.32 | 0.227753E+10 |
February | 0.438318E+09 | 0.00 | 0.438318E+09 | 61249185.90 | 0.161262E+10 |
March | 0.597053E+09 | 0.00 | 0.597053E+09 | 0.153235E+09 | 0.136936E+10 |
April | 0.757613E+09 | 6073150.42 | 0.751539E+09 | 0.446868E+09 | 0.791155E+09 |
May | 0.110178E+10 | 60220529.96 | 0.104156E+10 | 0.104623E+10 | 0.447834E+09 |
June | 0.119044E+10 | 0.132215E+09 | 0.105823E+10 | 0.132472E+10 | 0.306001E+09 |
July | 0.117477E+10 | 0.102012E+09 | 0.107276E+10 | 0.135287E+10 | 0.303813E+09 |
August | 0.891608E+09 | 15633956.76 | 0.875974E+09 | 0.936307E+09 | 0.363428E+09 |
September | 0.672151E+09 | 171445.02 | 0.671979E+09 | 0.537707E+09 | 0.580260E+09 |
October | 0.482259E+09 | 0.00 | 0.482259E+09 | 0.217198E+09 | 0.902862E+09 |
November | 0.309016E+09 | 0.00 | 0.309016E+09 | 39426341.08 | 0.130703E+10 |
December | 0.267674E+09 | 0.00 | 0.267674E+09 | 1427421.73 | 0.219756E+10 |
Annual Sum or Average | 0.819860E+10 | 0.316327E+09 | 0.788228E+10 | 0.612596E+10 | 0.124595E+11 |
Minimum of Months | 0.267674E+09 | 0.00 | 0.267674E+09 | 1427421.73 | 0.303813E+09 |
Maximum of Months | 0.119044E+10 | 0.132215E+09 | 0.107276E+10 | 0.135287E+10 | 0.227753E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315922E+09 | 0.00 | 0.315922E+09 | 8716733.32 | 0.227753E+10 |
February | 0.438318E+09 | 0.00 | 0.438318E+09 | 61249185.90 | 0.161262E+10 |
March | 0.597053E+09 | 0.00 | 0.597053E+09 | 0.153235E+09 | 0.136936E+10 |
April | 0.757613E+09 | 6073150.42 | 0.751539E+09 | 0.446868E+09 | 0.791155E+09 |
May | 0.110178E+10 | 60220529.96 | 0.104156E+10 | 0.104623E+10 | 0.447834E+09 |
June | 0.119044E+10 | 0.132215E+09 | 0.105823E+10 | 0.132472E+10 | 0.306001E+09 |
July | 0.117477E+10 | 0.102012E+09 | 0.107276E+10 | 0.135287E+10 | 0.303813E+09 |
August | 0.891608E+09 | 15633956.76 | 0.875974E+09 | 0.936307E+09 | 0.363428E+09 |
September | 0.672151E+09 | 171445.02 | 0.671979E+09 | 0.537707E+09 | 0.580260E+09 |
October | 0.482259E+09 | 0.00 | 0.482259E+09 | 0.217198E+09 | 0.902862E+09 |
November | 0.309016E+09 | 0.00 | 0.309016E+09 | 39426341.08 | 0.130703E+10 |
December | 0.267674E+09 | 0.00 | 0.267674E+09 | 1427421.73 | 0.219756E+10 |
Annual Sum or Average | 0.819860E+10 | 0.316327E+09 | 0.788228E+10 | 0.612596E+10 | 0.124595E+11 |
Minimum of Months | 0.267674E+09 | 0.00 | 0.267674E+09 | 1427421.73 | 0.303813E+09 |
Maximum of Months | 0.119044E+10 | 0.132215E+09 | 0.107276E+10 | 0.135287E+10 | 0.227753E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133456E+10 | 0.558267E+09 | 0.776296E+09 | 0.592768E+09 | 0.396885E+10 |
February | 0.189268E+10 | 0.808107E+09 | 0.108457E+10 | 0.122874E+10 | 0.281882E+10 |
March | 0.285164E+10 | 0.142966E+10 | 0.142198E+10 | 0.229204E+10 | 0.246057E+10 |
April | 0.382392E+10 | 0.206079E+10 | 0.176313E+10 | 0.378216E+10 | 0.150695E+10 |
May | 0.427761E+10 | 0.187869E+10 | 0.239892E+10 | 0.472462E+10 | 0.907707E+09 |
June | 0.468598E+10 | 0.223955E+10 | 0.244644E+10 | 0.557316E+10 | 0.626062E+09 |
July | 0.474328E+10 | 0.222492E+10 | 0.251836E+10 | 0.575920E+10 | 0.614130E+09 |
August | 0.365744E+10 | 0.159694E+10 | 0.206050E+10 | 0.428078E+10 | 0.724874E+09 |
September | 0.283520E+10 | 0.126817E+10 | 0.156703E+10 | 0.297793E+10 | 0.109807E+10 |
October | 0.177511E+10 | 0.673222E+09 | 0.110189E+10 | 0.143363E+10 | 0.167427E+10 |
November | 0.109466E+10 | 0.366745E+09 | 0.727915E+09 | 0.582982E+09 | 0.234960E+10 |
December | 0.103260E+10 | 0.382633E+09 | 0.649967E+09 | 0.366991E+09 | 0.386967E+10 |
Annual Sum or Average | 0.340047E+11 | 0.154877E+11 | 0.185170E+11 | 0.335950E+11 | 0.226196E+11 |
Minimum of Months | 0.103260E+10 | 0.366745E+09 | 0.649967E+09 | 0.366991E+09 | 0.614130E+09 |
Maximum of Months | 0.474328E+10 | 0.223955E+10 | 0.251836E+10 | 0.575920E+10 | 0.396885E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52767405.03 | 22073356.25 | 30694048.78 | 23437495.39 | 0.156925E+09 |
February | 74834782.09 | 31951812.17 | 42882969.93 | 48583117.03 | 0.111453E+09 |
March | 0.112751E+09 | 56527617.79 | 56223680.08 | 90625164.03 | 97288644.05 |
April | 0.151194E+09 | 81481836.83 | 69712563.44 | 0.149543E+09 | 59583320.85 |
May | 0.169133E+09 | 74281688.24 | 94851198.55 | 0.186807E+09 | 35889929.03 |
June | 0.185280E+09 | 88549735.81 | 96729880.53 | 0.220358E+09 | 24753925.24 |
July | 0.187545E+09 | 87971422.72 | 99573692.65 | 0.227714E+09 | 24282150.97 |
August | 0.144612E+09 | 63141746.79 | 81470254.19 | 0.169258E+09 | 28660853.23 |
September | 0.112101E+09 | 50142191.19 | 61958872.62 | 0.117745E+09 | 43416718.43 |
October | 70186384.95 | 26618576.40 | 43567808.55 | 56684541.06 | 66199074.24 |
November | 43281882.41 | 14500776.40 | 28781106.01 | 23050569.96 | 92901020.11 |
December | 40828081.51 | 15128974.28 | 25699107.23 | 14510502.80 | 0.153003E+09 |
Annual Sum or Average | 0.134451E+10 | 0.612370E+09 | 0.732145E+09 | 0.132832E+10 | 0.894357E+09 |
Minimum of Months | 40828081.51 | 14500776.40 | 25699107.23 | 14510502.80 | 24282150.97 |
Maximum of Months | 0.187545E+09 | 88549735.81 | 99573692.65 | 0.227714E+09 | 0.156925E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216994E+10 | 0.150790E+10 | 0.662040E+09 | 0.195023E+10 | 0.179740E+10 |
February | 0.248478E+10 | 0.167724E+10 | 0.807541E+09 | 0.245943E+10 | 0.138623E+10 |
March | 0.242915E+10 | 0.153804E+10 | 0.891113E+09 | 0.244921E+10 | 0.127336E+10 |
April | 0.213343E+10 | 0.116045E+10 | 0.972988E+09 | 0.231372E+10 | 0.834340E+09 |
May | 0.185422E+10 | 0.637520E+09 | 0.121670E+10 | 0.215525E+10 | 0.501950E+09 |
June | 0.161017E+10 | 0.432731E+09 | 0.117744E+10 | 0.197922E+10 | 0.333800E+09 |
July | 0.181946E+10 | 0.580365E+09 | 0.123909E+10 | 0.230711E+10 | 0.333347E+09 |
August | 0.194195E+10 | 0.815254E+09 | 0.112669E+10 | 0.239508E+10 | 0.395499E+09 |
September | 0.201067E+10 | 0.107220E+10 | 0.938474E+09 | 0.231410E+10 | 0.600197E+09 |
October | 0.177126E+10 | 0.104161E+10 | 0.729645E+09 | 0.183202E+10 | 0.883632E+09 |
November | 0.152409E+10 | 0.955356E+09 | 0.568736E+09 | 0.142668E+10 | 0.116294E+10 |
December | 0.167523E+10 | 0.109692E+10 | 0.578305E+09 | 0.139391E+10 | 0.174666E+10 |
Annual Sum or Average | 0.234243E+11 | 0.125156E+11 | 0.109088E+11 | 0.249760E+11 | 0.112494E+11 |
Minimum of Months | 0.152409E+10 | 0.432731E+09 | 0.568736E+09 | 0.139391E+10 | 0.333347E+09 |
Maximum of Months | 0.248478E+10 | 0.167724E+10 | 0.123909E+10 | 0.245943E+10 | 0.179740E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216994E+10 | 0.150790E+10 | 0.662040E+09 | 0.195023E+10 | 0.179740E+10 |
February | 0.248478E+10 | 0.167724E+10 | 0.807541E+09 | 0.245943E+10 | 0.138623E+10 |
March | 0.242915E+10 | 0.153804E+10 | 0.891113E+09 | 0.244921E+10 | 0.127336E+10 |
April | 0.213343E+10 | 0.116045E+10 | 0.972988E+09 | 0.231372E+10 | 0.834340E+09 |
May | 0.185422E+10 | 0.637520E+09 | 0.121670E+10 | 0.215525E+10 | 0.501950E+09 |
June | 0.161017E+10 | 0.432731E+09 | 0.117744E+10 | 0.197922E+10 | 0.333800E+09 |
July | 0.181946E+10 | 0.580365E+09 | 0.123909E+10 | 0.230711E+10 | 0.333347E+09 |
August | 0.194195E+10 | 0.815254E+09 | 0.112669E+10 | 0.239508E+10 | 0.395499E+09 |
September | 0.201067E+10 | 0.107220E+10 | 0.938474E+09 | 0.231410E+10 | 0.600197E+09 |
October | 0.177126E+10 | 0.104161E+10 | 0.729645E+09 | 0.183202E+10 | 0.883632E+09 |
November | 0.152409E+10 | 0.955356E+09 | 0.568736E+09 | 0.142668E+10 | 0.116294E+10 |
December | 0.167523E+10 | 0.109692E+10 | 0.578305E+09 | 0.139391E+10 | 0.174666E+10 |
Annual Sum or Average | 0.234243E+11 | 0.125156E+11 | 0.109088E+11 | 0.249760E+11 | 0.112494E+11 |
Minimum of Months | 0.152409E+10 | 0.432731E+09 | 0.568736E+09 | 0.139391E+10 | 0.333347E+09 |
Maximum of Months | 0.248478E+10 | 0.167724E+10 | 0.123909E+10 | 0.245943E+10 | 0.179740E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216980E+10 | 0.150780E+10 | 0.661998E+09 | 0.195011E+10 | 0.179729E+10 |
February | 0.248463E+10 | 0.167714E+10 | 0.807490E+09 | 0.245928E+10 | 0.138614E+10 |
March | 0.242900E+10 | 0.153794E+10 | 0.891056E+09 | 0.244906E+10 | 0.127328E+10 |
April | 0.213330E+10 | 0.116037E+10 | 0.972926E+09 | 0.231358E+10 | 0.834287E+09 |
May | 0.185410E+10 | 0.637480E+09 | 0.121662E+10 | 0.215512E+10 | 0.501918E+09 |
June | 0.161006E+10 | 0.432703E+09 | 0.117736E+10 | 0.197910E+10 | 0.333778E+09 |
July | 0.181934E+10 | 0.580328E+09 | 0.123901E+10 | 0.230696E+10 | 0.333326E+09 |
August | 0.194182E+10 | 0.815202E+09 | 0.112662E+10 | 0.239493E+10 | 0.395474E+09 |
September | 0.201054E+10 | 0.107213E+10 | 0.938414E+09 | 0.231396E+10 | 0.600159E+09 |
October | 0.177114E+10 | 0.104155E+10 | 0.729599E+09 | 0.183191E+10 | 0.883576E+09 |
November | 0.152400E+10 | 0.955295E+09 | 0.568700E+09 | 0.142659E+10 | 0.116286E+10 |
December | 0.167512E+10 | 0.109685E+10 | 0.578269E+09 | 0.139383E+10 | 0.174655E+10 |
Annual Sum or Average | 0.234229E+11 | 0.125148E+11 | 0.109081E+11 | 0.249744E+11 | 0.112486E+11 |
Minimum of Months | 0.152400E+10 | 0.432703E+09 | 0.568700E+09 | 0.139383E+10 | 0.333326E+09 |
Maximum of Months | 0.248463E+10 | 0.167714E+10 | 0.123901E+10 | 0.245928E+10 | 0.179729E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134855E+10 | 0.565711E+09 | 0.782843E+09 | 0.648344E+09 | 0.405420E+10 |
February | 0.198309E+10 | 0.906344E+09 | 0.107675E+10 | 0.141147E+10 | 0.293306E+10 |
March | 0.288575E+10 | 0.147572E+10 | 0.141003E+10 | 0.241526E+10 | 0.256134E+10 |
April | 0.356621E+10 | 0.180450E+10 | 0.176171E+10 | 0.353033E+10 | 0.158605E+10 |
May | 0.452765E+10 | 0.215729E+10 | 0.237036E+10 | 0.511710E+10 | 0.977912E+09 |
June | 0.422951E+10 | 0.182713E+10 | 0.240238E+10 | 0.503351E+10 | 0.656395E+09 |
July | 0.466622E+10 | 0.216772E+10 | 0.249850E+10 | 0.568771E+10 | 0.662611E+09 |
August | 0.383978E+10 | 0.174333E+10 | 0.209645E+10 | 0.455311E+10 | 0.766164E+09 |
September | 0.290384E+10 | 0.130340E+10 | 0.160045E+10 | 0.309719E+10 | 0.114531E+10 |
October | 0.189718E+10 | 0.761706E+09 | 0.113547E+10 | 0.163202E+10 | 0.172672E+10 |
November | 0.111610E+10 | 0.377047E+09 | 0.739055E+09 | 0.631882E+09 | 0.239913E+10 |
December | 0.102853E+10 | 0.360937E+09 | 0.667594E+09 | 0.371494E+09 | 0.392863E+10 |
Annual Sum or Average | 0.339924E+11 | 0.154508E+11 | 0.185416E+11 | 0.341294E+11 | 0.233975E+11 |
Minimum of Months | 0.102853E+10 | 0.360937E+09 | 0.667594E+09 | 0.371494E+09 | 0.656395E+09 |
Maximum of Months | 0.466622E+10 | 0.216772E+10 | 0.249850E+10 | 0.568771E+10 | 0.405420E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53320451.54 | 22367614.91 | 30952836.63 | 25634784.65 | 0.160300E+09 |
February | 78409448.73 | 35835891.29 | 42573557.44 | 55807814.85 | 0.115971E+09 |
March | 0.114100E+09 | 58348586.13 | 55751190.38 | 95496985.54 | 0.101273E+09 |
April | 0.141004E+09 | 71348222.50 | 69656140.97 | 0.139586E+09 | 62711045.10 |
May | 0.179019E+09 | 85297056.84 | 93721591.55 | 0.202325E+09 | 38665765.41 |
June | 0.167231E+09 | 72242870.52 | 94987658.13 | 0.199020E+09 | 25953252.65 |
July | 0.184498E+09 | 85709560.41 | 98788039.33 | 0.224886E+09 | 26199035.69 |
August | 0.151821E+09 | 68929423.72 | 82891514.82 | 0.180025E+09 | 30293438.89 |
September | 0.114815E+09 | 51534938.14 | 63280119.48 | 0.122460E+09 | 45284564.88 |
October | 75012384.12 | 30117063.08 | 44895321.04 | 64528368.80 | 68272820.88 |
November | 44129556.20 | 14908050.99 | 29221505.21 | 24983930.11 | 94859255.05 |
December | 40667065.90 | 14271058.24 | 26396007.65 | 14688432.85 | 0.155335E+09 |
Annual Sum or Average | 0.134403E+10 | 0.610910E+09 | 0.733115E+09 | 0.134944E+10 | 0.925117E+09 |
Minimum of Months | 40667065.90 | 14271058.24 | 26396007.65 | 14688432.85 | 25953252.65 |
Maximum of Months | 0.184498E+09 | 85709560.41 | 98788039.33 | 0.224886E+09 | 0.160300E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.947751E+09 | 0.00 | 0.947751E+09 | 24860975.00 | 0.691356E+10 |
February | 0.131493E+10 | 0.00 | 0.131493E+10 | 0.172929E+09 | 0.490100E+10 |
March | 0.179113E+10 | 0.00 | 0.179113E+10 | 0.422041E+09 | 0.422616E+10 |
April | 0.227280E+10 | 18219161.88 | 0.225458E+10 | 0.124040E+10 | 0.249554E+10 |
May | 0.330529E+10 | 0.180659E+09 | 0.312463E+10 | 0.302884E+10 | 0.142406E+10 |
June | 0.357127E+10 | 0.396639E+09 | 0.317463E+10 | 0.390150E+10 | 0.961722E+09 |
July | 0.352425E+10 | 0.306032E+09 | 0.321822E+10 | 0.401148E+10 | 0.939595E+09 |
August | 0.267478E+10 | 46901125.33 | 0.262788E+10 | 0.278457E+10 | 0.110383E+10 |
September | 0.201642E+10 | 514326.90 | 0.201591E+10 | 0.160124E+10 | 0.173035E+10 |
October | 0.144676E+10 | 0.00 | 0.144676E+10 | 0.651522E+09 | 0.266521E+10 |
November | 0.927034E+09 | 0.00 | 0.927034E+09 | 0.117536E+09 | 0.387478E+10 |
December | 0.803011E+09 | 0.00 | 0.803011E+09 | 4664377.13 | 0.662781E+10 |
Annual Sum or Average | 0.245954E+11 | 0.948964E+09 | 0.236465E+11 | 0.179616E+11 | 0.378636E+11 |
Minimum of Months | 0.803011E+09 | 0.00 | 0.803011E+09 | 4664377.13 | 0.939595E+09 |
Maximum of Months | 0.357127E+10 | 0.396639E+09 | 0.321822E+10 | 0.401148E+10 | 0.691356E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138734E+10 | 0.580346E+09 | 0.806996E+09 | 0.605293E+09 | 0.415774E+10 |
February | 0.196753E+10 | 0.840067E+09 | 0.112746E+10 | 0.125701E+10 | 0.295180E+10 |
March | 0.296442E+10 | 0.148621E+10 | 0.147821E+10 | 0.233811E+10 | 0.260304E+10 |
April | 0.397515E+10 | 0.214229E+10 | 0.183285E+10 | 0.387919E+10 | 0.158791E+10 |
May | 0.444678E+10 | 0.195299E+10 | 0.249379E+10 | 0.486366E+10 | 0.960023E+09 |
June | 0.487130E+10 | 0.232812E+10 | 0.254318E+10 | 0.575977E+10 | 0.654588E+09 |
July | 0.493087E+10 | 0.231292E+10 | 0.261795E+10 | 0.596746E+10 | 0.633334E+09 |
August | 0.380208E+10 | 0.166010E+10 | 0.214198E+10 | 0.444198E+10 | 0.732878E+09 |
September | 0.294732E+10 | 0.131832E+10 | 0.162900E+10 | 0.309642E+10 | 0.110358E+10 |
October | 0.184531E+10 | 0.699847E+09 | 0.114547E+10 | 0.149738E+10 | 0.168580E+10 |
November | 0.113795E+10 | 0.381250E+09 | 0.756701E+09 | 0.603267E+09 | 0.240101E+10 |
December | 0.107344E+10 | 0.397766E+09 | 0.675671E+09 | 0.376572E+09 | 0.403508E+10 |
Annual Sum or Average | 0.353495E+11 | 0.161002E+11 | 0.192493E+11 | 0.346861E+11 | 0.235068E+11 |
Minimum of Months | 0.107344E+10 | 0.381250E+09 | 0.675671E+09 | 0.376572E+09 | 0.633334E+09 |
Maximum of Months | 0.493087E+10 | 0.232812E+10 | 0.261795E+10 | 0.596746E+10 | 0.415774E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.650961E+10 | 0.452355E+10 | 0.198606E+10 | 0.568247E+10 | 0.560305E+10 |
February | 0.745411E+10 | 0.503156E+10 | 0.242255E+10 | 0.721689E+10 | 0.425558E+10 |
March | 0.728722E+10 | 0.461396E+10 | 0.267326E+10 | 0.717639E+10 | 0.393424E+10 |
April | 0.640010E+10 | 0.348122E+10 | 0.291888E+10 | 0.680755E+10 | 0.257130E+10 |
May | 0.556249E+10 | 0.191250E+10 | 0.364999E+10 | 0.634967E+10 | 0.156860E+10 |
June | 0.483036E+10 | 0.129815E+10 | 0.353221E+10 | 0.585339E+10 | 0.104589E+10 |
July | 0.545821E+10 | 0.174104E+10 | 0.371717E+10 | 0.687459E+10 | 0.100656E+10 |
August | 0.582566E+10 | 0.244568E+10 | 0.337998E+10 | 0.714453E+10 | 0.116634E+10 |
September | 0.603183E+10 | 0.321649E+10 | 0.281534E+10 | 0.689414E+10 | 0.175976E+10 |
October | 0.531360E+10 | 0.312473E+10 | 0.218887E+10 | 0.545425E+10 | 0.258193E+10 |
November | 0.457213E+10 | 0.286597E+10 | 0.170616E+10 | 0.421950E+10 | 0.346778E+10 |
December | 0.502552E+10 | 0.329066E+10 | 0.173486E+10 | 0.406971E+10 | 0.540656E+10 |
Annual Sum or Average | 0.702708E+11 | 0.375455E+11 | 0.327253E+11 | 0.737431E+11 | 0.343676E+11 |
Minimum of Months | 0.457213E+10 | 0.129815E+10 | 0.170616E+10 | 0.406971E+10 | 0.100656E+10 |
Maximum of Months | 0.745411E+10 | 0.503156E+10 | 0.371717E+10 | 0.721689E+10 | 0.560305E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140189E+10 | 0.588084E+09 | 0.813801E+09 | 0.660312E+09 | 0.424974E+10 |
February | 0.206152E+10 | 0.942189E+09 | 0.111933E+10 | 0.144156E+10 | 0.307184E+10 |
March | 0.299988E+10 | 0.153409E+10 | 0.146579E+10 | 0.246736E+10 | 0.270971E+10 |
April | 0.370724E+10 | 0.187587E+10 | 0.183137E+10 | 0.361717E+10 | 0.167889E+10 |
May | 0.470670E+10 | 0.224261E+10 | 0.246409E+10 | 0.527628E+10 | 0.103349E+10 |
June | 0.439677E+10 | 0.189939E+10 | 0.249738E+10 | 0.519824E+10 | 0.693976E+09 |
July | 0.485075E+10 | 0.225346E+10 | 0.259730E+10 | 0.589651E+10 | 0.680878E+09 |
August | 0.399163E+10 | 0.181228E+10 | 0.217935E+10 | 0.472600E+10 | 0.776069E+09 |
September | 0.301868E+10 | 0.135494E+10 | 0.166374E+10 | 0.322058E+10 | 0.115500E+10 |
October | 0.197220E+10 | 0.791831E+09 | 0.118037E+10 | 0.170124E+10 | 0.174093E+10 |
November | 0.116024E+10 | 0.391959E+09 | 0.768282E+09 | 0.652589E+09 | 0.245769E+10 |
December | 0.106921E+10 | 0.375211E+09 | 0.693995E+09 | 0.380233E+09 | 0.410070E+10 |
Annual Sum or Average | 0.353367E+11 | 0.160619E+11 | 0.192748E+11 | 0.352381E+11 | 0.243489E+11 |
Minimum of Months | 0.106921E+10 | 0.375211E+09 | 0.693995E+09 | 0.380233E+09 | 0.680878E+09 |
Maximum of Months | 0.485075E+10 | 0.225346E+10 | 0.259730E+10 | 0.589651E+10 | 0.424974E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.41 | 2536.15 | 353.85 | 0.00 | 353.85 | 0.00 | 0.00 |
February | 76.26 | 1973.72 | 543.54 | 0.00 | 543.54 | 0.00 | 0.00 |
March | 166.40 | 1519.01 | 668.73 | 0.00 | 668.73 | 0.00 | 0.00 |
April | 498.57 | 904.61 | 876.85 | 7.03 | 869.82 | 0.00 | 0.00 |
May | 1146.94 | 507.33 | 1234.05 | 67.45 | 1166.60 | 0.00 | 0.00 |
June | 1513.28 | 356.19 | 1377.80 | 153.02 | 1224.78 | 0.00 | 0.00 |
July | 1502.84 | 339.05 | 1315.80 | 114.26 | 1201.54 | 0.00 | 0.00 |
August | 1047.10 | 393.33 | 998.65 | 17.51 | 981.14 | 0.00 | 0.00 |
September | 636.36 | 622.76 | 777.94 | 0.20 | 777.74 | 0.00 | 0.00 |
October | 264.10 | 921.89 | 540.16 | 0.00 | 540.16 | 0.00 | 0.00 |
November | 51.44 | 1422.95 | 357.65 | 0.00 | 357.65 | 0.00 | 0.00 |
December | 2.71 | 2423.08 | 299.81 | 0.00 | 299.81 | 0.00 | 0.00 |
Annual Sum or Average | 579.40 | 1156.97 | 779.92 | 30.09 | 749.82 | 0.00 | 0.00 |
Minimum of Months | 2.71 | 339.05 | 299.81 | 0.00 | 299.81 | 0.00 | 0.00 |
Maximum of Months | 1513.28 | 2536.15 | 1377.80 | 153.02 | 1224.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 228.64 | 1525.99 | 517.97 | 216.68 | 301.30 | 0.00 | 0.00 |
February | 526.38 | 1188.60 | 813.30 | 347.25 | 466.05 | 0.00 | 0.00 |
March | 882.70 | 935.15 | 1106.79 | 554.89 | 551.90 | 0.00 | 0.00 |
April | 1509.41 | 579.01 | 1533.62 | 826.50 | 707.12 | 0.00 | 0.00 |
May | 1822.99 | 343.46 | 1660.24 | 729.16 | 931.07 | 0.00 | 0.00 |
June | 2224.52 | 242.91 | 1879.36 | 898.20 | 981.17 | 0.00 | 0.00 |
July | 2229.05 | 228.85 | 1840.97 | 863.54 | 977.43 | 0.00 | 0.00 |
August | 1661.16 | 262.22 | 1419.54 | 619.81 | 799.72 | 0.00 | 0.00 |
September | 1204.86 | 401.11 | 1137.08 | 508.61 | 628.47 | 0.00 | 0.00 |
October | 573.18 | 587.30 | 688.96 | 261.29 | 427.67 | 0.00 | 0.00 |
November | 240.38 | 882.17 | 439.02 | 147.09 | 291.94 | 0.00 | 0.00 |
December | 143.16 | 1475.20 | 400.78 | 148.51 | 252.27 | 0.00 | 0.00 |
Annual Sum or Average | 1106.52 | 719.29 | 1120.92 | 510.54 | 610.39 | 0.00 | 0.00 |
Minimum of Months | 143.16 | 228.85 | 400.78 | 147.09 | 252.27 | 0.00 | 0.00 |
Maximum of Months | 2229.05 | 1525.99 | 1879.36 | 898.20 | 981.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2130.66 | 2050.44 | 2430.41 | 1688.90 | 741.51 | 0.00 | 0.00 |
February | 2996.88 | 1705.88 | 3081.23 | 2079.84 | 1001.39 | 0.00 | 0.00 |
March | 2693.71 | 1410.53 | 2720.74 | 1722.65 | 998.08 | 0.00 | 0.00 |
April | 2642.51 | 936.45 | 2469.18 | 1343.06 | 1126.11 | 0.00 | 0.00 |
May | 2379.51 | 558.01 | 2076.80 | 714.05 | 1362.75 | 0.00 | 0.00 |
June | 2263.57 | 385.91 | 1863.56 | 500.83 | 1362.74 | 0.00 | 0.00 |
July | 2569.34 | 362.08 | 2037.86 | 650.03 | 1387.83 | 0.00 | 0.00 |
August | 2671.50 | 415.76 | 2175.05 | 913.11 | 1261.94 | 0.00 | 0.00 |
September | 2673.02 | 638.19 | 2327.09 | 1240.93 | 1086.17 | 0.00 | 0.00 |
October | 2058.85 | 898.13 | 1983.87 | 1166.64 | 817.23 | 0.00 | 0.00 |
November | 1644.80 | 1270.75 | 1763.94 | 1105.70 | 658.24 | 0.00 | 0.00 |
December | 1530.41 | 1971.39 | 1876.31 | 1228.59 | 647.72 | 0.00 | 0.00 |
Annual Sum or Average | 2349.82 | 1047.56 | 2228.27 | 1190.56 | 1037.71 | 0.00 | 0.00 |
Minimum of Months | 1530.41 | 362.08 | 1763.94 | 500.83 | 647.72 | 0.00 | 0.00 |
Maximum of Months | 2996.88 | 2050.44 | 3081.23 | 2079.84 | 1387.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 248.23 | 1559.97 | 523.40 | 219.57 | 303.84 | 0.00 | 0.00 |
February | 600.75 | 1236.71 | 852.15 | 389.46 | 462.69 | 0.00 | 0.00 |
March | 927.67 | 973.24 | 1120.03 | 572.76 | 547.26 | 0.00 | 0.00 |
April | 1406.70 | 611.55 | 1430.26 | 723.72 | 706.55 | 0.00 | 0.00 |
May | 1977.16 | 368.28 | 1757.28 | 837.29 | 919.99 | 0.00 | 0.00 |
June | 2009.64 | 256.59 | 1696.29 | 732.79 | 963.50 | 0.00 | 0.00 |
July | 2203.51 | 245.45 | 1811.06 | 841.34 | 969.72 | 0.00 | 0.00 |
August | 1768.72 | 276.83 | 1490.30 | 676.63 | 813.68 | 0.00 | 0.00 |
September | 1253.68 | 418.33 | 1164.62 | 522.74 | 641.87 | 0.00 | 0.00 |
October | 648.06 | 605.63 | 736.34 | 295.64 | 440.70 | 0.00 | 0.00 |
November | 258.42 | 903.23 | 447.62 | 151.22 | 296.41 | 0.00 | 0.00 |
December | 144.01 | 1499.93 | 399.20 | 140.09 | 259.11 | 0.00 | 0.00 |
Annual Sum or Average | 1123.60 | 744.46 | 1120.52 | 509.32 | 611.20 | 0.00 | 0.00 |
Minimum of Months | 144.01 | 245.45 | 399.20 | 140.09 | 259.11 | 0.00 | 0.00 |
Maximum of Months | 2203.51 | 1559.97 | 1811.06 | 841.34 | 969.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 9.76 | 2550.95 | 353.85 | 0.00 | 353.85 | 0.00 | 0.00 |
February | 75.95 | 1999.74 | 543.54 | 0.00 | 543.54 | 0.00 | 0.00 |
March | 171.63 | 1533.75 | 668.73 | 0.00 | 668.73 | 0.00 | 0.00 |
April | 517.20 | 915.67 | 876.85 | 7.03 | 869.82 | 0.00 | 0.00 |
May | 1171.83 | 501.60 | 1234.05 | 67.45 | 1166.60 | 0.00 | 0.00 |
June | 1533.21 | 354.16 | 1377.80 | 153.02 | 1224.77 | 0.00 | 0.00 |
July | 1515.28 | 340.29 | 1315.80 | 114.26 | 1201.54 | 0.00 | 0.00 |
August | 1048.71 | 407.06 | 998.64 | 17.51 | 981.13 | 0.00 | 0.00 |
September | 622.33 | 671.58 | 777.94 | 0.20 | 777.74 | 0.00 | 0.00 |
October | 243.27 | 1011.25 | 540.15 | 0.00 | 540.15 | 0.00 | 0.00 |
November | 45.63 | 1512.74 | 357.65 | 0.00 | 357.65 | 0.00 | 0.00 |
December | 1.60 | 2461.37 | 299.81 | 0.00 | 299.81 | 0.00 | 0.00 |
Annual Sum or Average | 582.75 | 1185.24 | 779.91 | 30.09 | 749.82 | 0.00 | 0.00 |
Minimum of Months | 1.60 | 340.29 | 299.81 | 0.00 | 299.81 | 0.00 | 0.00 |
Maximum of Months | 1533.21 | 2550.95 | 1377.80 | 153.02 | 1224.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 230.06 | 1540.39 | 517.97 | 216.67 | 301.30 | 0.00 | 0.00 |
February | 527.99 | 1211.26 | 813.29 | 347.25 | 466.04 | 0.00 | 0.00 |
March | 889.58 | 954.99 | 1106.78 | 554.88 | 551.90 | 0.00 | 0.00 |
April | 1516.86 | 604.37 | 1533.61 | 826.49 | 707.12 | 0.00 | 0.00 |
May | 1833.72 | 352.30 | 1660.22 | 729.16 | 931.07 | 0.00 | 0.00 |
June | 2235.16 | 251.09 | 1879.35 | 898.19 | 981.16 | 0.00 | 0.00 |
July | 2235.26 | 238.36 | 1840.96 | 863.54 | 977.42 | 0.00 | 0.00 |
August | 1661.45 | 281.34 | 1419.52 | 619.81 | 799.72 | 0.00 | 0.00 |
September | 1194.32 | 440.39 | 1137.07 | 508.61 | 628.47 | 0.00 | 0.00 |
October | 556.42 | 649.82 | 688.96 | 261.29 | 427.67 | 0.00 | 0.00 |
November | 233.81 | 942.32 | 439.02 | 147.09 | 291.94 | 0.00 | 0.00 |
December | 142.44 | 1501.89 | 400.77 | 148.51 | 252.26 | 0.00 | 0.00 |
Annual Sum or Average | 1107.41 | 745.62 | 1120.92 | 510.53 | 610.39 | 0.00 | 0.00 |
Minimum of Months | 142.44 | 238.36 | 400.77 | 147.09 | 252.26 | 0.00 | 0.00 |
Maximum of Months | 2235.26 | 1540.39 | 1879.35 | 898.19 | 981.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2184.35 | 2013.18 | 2430.44 | 1688.92 | 741.52 | 0.00 | 0.00 |
February | 3049.83 | 1719.00 | 3081.26 | 2079.87 | 1001.39 | 0.00 | 0.00 |
March | 2743.23 | 1426.23 | 2720.76 | 1722.67 | 998.09 | 0.00 | 0.00 |
April | 2677.86 | 965.65 | 2469.20 | 1343.08 | 1126.12 | 0.00 | 0.00 |
May | 2413.99 | 562.21 | 2076.81 | 714.05 | 1362.76 | 0.00 | 0.00 |
June | 2290.72 | 386.33 | 1863.58 | 500.84 | 1362.74 | 0.00 | 0.00 |
July | 2584.07 | 373.37 | 2037.88 | 650.04 | 1387.84 | 0.00 | 0.00 |
August | 2682.60 | 442.98 | 2175.07 | 913.12 | 1261.95 | 0.00 | 0.00 |
September | 2678.31 | 694.66 | 2327.12 | 1240.94 | 1086.17 | 0.00 | 0.00 |
October | 2051.95 | 989.71 | 1983.89 | 1166.66 | 817.24 | 0.00 | 0.00 |
November | 1651.22 | 1345.96 | 1763.96 | 1105.71 | 658.25 | 0.00 | 0.00 |
December | 1561.25 | 1956.34 | 1876.33 | 1228.60 | 647.73 | 0.00 | 0.00 |
Annual Sum or Average | 2375.90 | 1070.12 | 2228.30 | 1190.57 | 1037.72 | 0.00 | 0.00 |
Minimum of Months | 1561.25 | 373.37 | 1763.96 | 500.84 | 647.73 | 0.00 | 0.00 |
Maximum of Months | 3049.83 | 2013.18 | 3081.26 | 2079.87 | 1387.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 251.63 | 1573.51 | 523.40 | 219.56 | 303.84 | 0.00 | 0.00 |
February | 606.51 | 1260.35 | 852.14 | 389.46 | 462.68 | 0.00 | 0.00 |
March | 937.41 | 994.10 | 1120.02 | 572.76 | 547.26 | 0.00 | 0.00 |
April | 1415.86 | 636.10 | 1430.25 | 723.71 | 706.54 | 0.00 | 0.00 |
May | 1986.04 | 379.55 | 1757.27 | 837.29 | 919.98 | 0.00 | 0.00 |
June | 2018.72 | 263.25 | 1696.27 | 732.78 | 963.49 | 0.00 | 0.00 |
July | 2207.51 | 257.17 | 1811.05 | 841.34 | 969.71 | 0.00 | 0.00 |
August | 1767.15 | 297.36 | 1490.29 | 676.62 | 813.67 | 0.00 | 0.00 |
September | 1242.15 | 459.33 | 1164.61 | 522.74 | 641.87 | 0.00 | 0.00 |
October | 633.42 | 670.17 | 736.33 | 295.63 | 440.70 | 0.00 | 0.00 |
November | 253.42 | 962.19 | 447.62 | 151.22 | 296.40 | 0.00 | 0.00 |
December | 144.18 | 1524.78 | 399.19 | 140.09 | 259.11 | 0.00 | 0.00 |
Annual Sum or Average | 1125.03 | 771.27 | 1120.51 | 509.31 | 611.20 | 0.00 | 0.00 |
Minimum of Months | 144.18 | 257.17 | 399.19 | 140.09 | 259.11 | 0.00 | 0.00 |
Maximum of Months | 2207.51 | 1573.51 | 1811.05 | 841.34 | 969.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 9.28 | 2581.23 | 353.85 | 0.00 | 353.85 | 0.00 | 0.00 |
February | 71.48 | 2025.88 | 543.54 | 0.00 | 543.54 | 0.00 | 0.00 |
March | 157.57 | 1577.87 | 668.73 | 0.00 | 668.73 | 0.00 | 0.00 |
April | 478.55 | 962.78 | 876.85 | 7.03 | 869.82 | 0.00 | 0.00 |
May | 1130.84 | 531.68 | 1234.05 | 67.45 | 1166.60 | 0.00 | 0.00 |
June | 1505.21 | 371.03 | 1377.80 | 153.02 | 1224.78 | 0.00 | 0.00 |
July | 1497.71 | 350.80 | 1315.80 | 114.26 | 1201.54 | 0.00 | 0.00 |
August | 1039.64 | 412.12 | 998.65 | 17.51 | 981.14 | 0.00 | 0.00 |
September | 617.76 | 667.57 | 777.94 | 0.20 | 777.74 | 0.00 | 0.00 |
October | 243.25 | 995.08 | 540.16 | 0.00 | 540.16 | 0.00 | 0.00 |
November | 45.35 | 1494.90 | 357.65 | 0.00 | 357.65 | 0.00 | 0.00 |
December | 1.74 | 2474.54 | 299.81 | 0.00 | 299.81 | 0.00 | 0.00 |
Annual Sum or Average | 569.56 | 1200.65 | 779.92 | 30.09 | 749.82 | 0.00 | 0.00 |
Minimum of Months | 1.74 | 350.80 | 299.81 | 0.00 | 299.81 | 0.00 | 0.00 |
Maximum of Months | 1505.21 | 2581.23 | 1377.80 | 153.02 | 1224.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 225.99 | 1552.32 | 517.97 | 216.68 | 301.30 | 0.00 | 0.00 |
February | 519.60 | 1220.15 | 813.30 | 347.25 | 466.05 | 0.00 | 0.00 |
March | 872.95 | 971.86 | 1106.79 | 554.89 | 551.90 | 0.00 | 0.00 |
April | 1496.60 | 612.62 | 1533.62 | 826.50 | 707.12 | 0.00 | 0.00 |
May | 1815.88 | 358.43 | 1660.24 | 729.16 | 931.07 | 0.00 | 0.00 |
June | 2222.13 | 252.54 | 1879.36 | 898.20 | 981.17 | 0.00 | 0.00 |
July | 2227.99 | 236.46 | 1840.97 | 863.54 | 977.43 | 0.00 | 0.00 |
August | 1658.45 | 273.63 | 1419.54 | 619.81 | 799.72 | 0.00 | 0.00 |
September | 1194.61 | 425.76 | 1137.08 | 508.61 | 628.47 | 0.00 | 0.00 |
October | 559.06 | 629.41 | 688.96 | 261.29 | 427.67 | 0.00 | 0.00 |
November | 232.74 | 926.32 | 439.02 | 147.09 | 291.94 | 0.00 | 0.00 |
December | 140.60 | 1506.52 | 400.78 | 148.51 | 252.27 | 0.00 | 0.00 |
Annual Sum or Average | 1099.89 | 745.40 | 1120.92 | 510.54 | 610.39 | 0.00 | 0.00 |
Minimum of Months | 140.60 | 236.46 | 400.78 | 147.09 | 252.27 | 0.00 | 0.00 |
Maximum of Months | 2227.99 | 1552.32 | 1879.36 | 898.20 | 981.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2121.59 | 2091.94 | 2430.41 | 1688.90 | 741.51 | 0.00 | 0.00 |
February | 2983.17 | 1759.08 | 3081.23 | 2079.84 | 1001.39 | 0.00 | 0.00 |
March | 2679.36 | 1468.88 | 2720.74 | 1722.65 | 998.08 | 0.00 | 0.00 |
April | 2626.37 | 992.02 | 2469.18 | 1343.06 | 1126.11 | 0.00 | 0.00 |
May | 2370.69 | 585.65 | 2076.80 | 714.05 | 1362.75 | 0.00 | 0.00 |
June | 2258.25 | 403.51 | 1863.56 | 500.83 | 1362.74 | 0.00 | 0.00 |
July | 2566.68 | 375.81 | 2037.86 | 650.03 | 1387.83 | 0.00 | 0.00 |
August | 2667.46 | 435.46 | 2175.05 | 913.11 | 1261.94 | 0.00 | 0.00 |
September | 2659.78 | 678.92 | 2327.09 | 1240.93 | 1086.17 | 0.00 | 0.00 |
October | 2036.39 | 963.98 | 1983.87 | 1166.64 | 817.23 | 0.00 | 0.00 |
November | 1627.89 | 1337.88 | 1763.94 | 1105.70 | 658.24 | 0.00 | 0.00 |
December | 1519.46 | 2018.58 | 1876.31 | 1228.59 | 647.72 | 0.00 | 0.00 |
Annual Sum or Average | 2338.38 | 1089.79 | 2228.27 | 1190.56 | 1037.71 | 0.00 | 0.00 |
Minimum of Months | 1519.46 | 375.81 | 1763.94 | 500.83 | 647.72 | 0.00 | 0.00 |
Maximum of Months | 2983.17 | 2091.94 | 3081.23 | 2079.84 | 1387.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 246.53 | 1586.67 | 523.40 | 219.57 | 303.84 | 0.00 | 0.00 |
February | 595.88 | 1269.77 | 852.15 | 389.46 | 462.69 | 0.00 | 0.00 |
March | 921.21 | 1011.69 | 1120.03 | 572.76 | 547.26 | 0.00 | 0.00 |
April | 1395.51 | 647.72 | 1430.26 | 723.72 | 706.55 | 0.00 | 0.00 |
May | 1969.94 | 385.86 | 1757.28 | 837.29 | 919.99 | 0.00 | 0.00 |
June | 2005.49 | 267.74 | 1696.29 | 732.79 | 963.50 | 0.00 | 0.00 |
July | 2201.51 | 254.21 | 1811.06 | 841.34 | 969.72 | 0.00 | 0.00 |
August | 1764.48 | 289.75 | 1490.30 | 676.63 | 813.68 | 0.00 | 0.00 |
September | 1242.51 | 445.60 | 1164.62 | 522.74 | 641.87 | 0.00 | 0.00 |
October | 635.17 | 649.99 | 736.34 | 295.64 | 440.70 | 0.00 | 0.00 |
November | 251.77 | 948.18 | 447.62 | 151.22 | 296.41 | 0.00 | 0.00 |
December | 141.96 | 1531.03 | 399.20 | 140.09 | 259.11 | 0.00 | 0.00 |
Annual Sum or Average | 1117.39 | 772.10 | 1120.52 | 509.32 | 611.20 | 0.00 | 0.00 |
Minimum of Months | 141.96 | 254.21 | 399.20 | 140.09 | 259.11 | 0.00 | 0.00 |
Maximum of Months | 2201.51 | 1586.67 | 1811.06 | 841.34 | 969.72 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 27874511.57 | 0.679282E+10 | 0.947751E+09 | 0.00 | 0.947751E+09 | 0.00 | 0.00 |
February | 0.184481E+09 | 0.477483E+10 | 0.131493E+10 | 0.00 | 0.131493E+10 | 0.00 | 0.00 |
March | 0.445688E+09 | 0.406851E+10 | 0.179113E+10 | 0.00 | 0.179113E+10 | 0.00 | 0.00 |
April | 0.129229E+10 | 0.234474E+10 | 0.227280E+10 | 18219161.88 | 0.225458E+10 | 0.00 | 0.00 |
May | 0.307197E+10 | 0.135884E+10 | 0.330529E+10 | 0.180659E+09 | 0.312463E+10 | 0.00 | 0.00 |
June | 0.392243E+10 | 0.923251E+09 | 0.357127E+10 | 0.396639E+09 | 0.317463E+10 | 0.00 | 0.00 |
July | 0.402520E+10 | 0.908101E+09 | 0.352425E+10 | 0.306032E+09 | 0.321822E+10 | 0.00 | 0.00 |
August | 0.280456E+10 | 0.105349E+10 | 0.267478E+10 | 46901125.33 | 0.262788E+10 | 0.00 | 0.00 |
September | 0.164945E+10 | 0.161420E+10 | 0.201642E+10 | 514326.90 | 0.201591E+10 | 0.00 | 0.00 |
October | 0.707377E+09 | 0.246920E+10 | 0.144676E+10 | 0.00 | 0.144676E+10 | 0.00 | 0.00 |
November | 0.133330E+09 | 0.368828E+10 | 0.927034E+09 | 0.00 | 0.927034E+09 | 0.00 | 0.00 |
December | 7251125.96 | 0.648996E+10 | 0.803011E+09 | 0.00 | 0.803011E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.182719E+11 | 0.364862E+11 | 0.245954E+11 | 0.948964E+09 | 0.236465E+11 | 0.00 | 0.00 |
Minimum of Months | 7251125.96 | 0.908101E+09 | 0.803011E+09 | 0.00 | 0.803011E+09 | 0.00 | 0.00 |
Maximum of Months | 0.402520E+10 | 0.679282E+10 | 0.357127E+10 | 0.396639E+09 | 0.321822E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.612385E+09 | 0.408721E+10 | 0.138734E+10 | 0.580346E+09 | 0.806996E+09 | 0.00 | 0.00 |
February | 0.127342E+10 | 0.287546E+10 | 0.196753E+10 | 0.840067E+09 | 0.112746E+10 | 0.00 | 0.00 |
March | 0.236423E+10 | 0.250470E+10 | 0.296442E+10 | 0.148621E+10 | 0.147821E+10 | 0.00 | 0.00 |
April | 0.391240E+10 | 0.150080E+10 | 0.397515E+10 | 0.214229E+10 | 0.183285E+10 | 0.00 | 0.00 |
May | 0.488269E+10 | 0.919917E+09 | 0.444678E+10 | 0.195299E+10 | 0.249379E+10 | 0.00 | 0.00 |
June | 0.576596E+10 | 0.629627E+09 | 0.487130E+10 | 0.232812E+10 | 0.254318E+10 | 0.00 | 0.00 |
July | 0.597028E+10 | 0.612956E+09 | 0.493087E+10 | 0.231292E+10 | 0.261795E+10 | 0.00 | 0.00 |
August | 0.444926E+10 | 0.702321E+09 | 0.380208E+10 | 0.166010E+10 | 0.214198E+10 | 0.00 | 0.00 |
September | 0.312300E+10 | 0.103968E+10 | 0.294732E+10 | 0.131832E+10 | 0.162900E+10 | 0.00 | 0.00 |
October | 0.153522E+10 | 0.157303E+10 | 0.184531E+10 | 0.699847E+09 | 0.114547E+10 | 0.00 | 0.00 |
November | 0.623074E+09 | 0.228659E+10 | 0.113795E+10 | 0.381250E+09 | 0.756701E+09 | 0.00 | 0.00 |
December | 0.383441E+09 | 0.395118E+10 | 0.107344E+10 | 0.397766E+09 | 0.675671E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.348953E+11 | 0.226835E+11 | 0.353495E+11 | 0.161002E+11 | 0.192493E+11 | 0.00 | 0.00 |
Minimum of Months | 0.383441E+09 | 0.612956E+09 | 0.107344E+10 | 0.381250E+09 | 0.675671E+09 | 0.00 | 0.00 |
Maximum of Months | 0.597028E+10 | 0.408721E+10 | 0.493087E+10 | 0.232812E+10 | 0.261795E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.570676E+10 | 0.549189E+10 | 0.650961E+10 | 0.452355E+10 | 0.198606E+10 | 0.00 | 0.00 |
February | 0.725004E+10 | 0.412686E+10 | 0.745411E+10 | 0.503156E+10 | 0.242255E+10 | 0.00 | 0.00 |
March | 0.721483E+10 | 0.377796E+10 | 0.728722E+10 | 0.461396E+10 | 0.267326E+10 | 0.00 | 0.00 |
April | 0.684939E+10 | 0.242727E+10 | 0.640010E+10 | 0.348122E+10 | 0.291888E+10 | 0.00 | 0.00 |
May | 0.637329E+10 | 0.149458E+10 | 0.556249E+10 | 0.191250E+10 | 0.364999E+10 | 0.00 | 0.00 |
June | 0.586718E+10 | 0.100027E+10 | 0.483036E+10 | 0.129815E+10 | 0.353221E+10 | 0.00 | 0.00 |
July | 0.688173E+10 | 0.969808E+09 | 0.545821E+10 | 0.174104E+10 | 0.371717E+10 | 0.00 | 0.00 |
August | 0.715536E+10 | 0.111357E+10 | 0.582566E+10 | 0.244568E+10 | 0.337998E+10 | 0.00 | 0.00 |
September | 0.692846E+10 | 0.165418E+10 | 0.603183E+10 | 0.321649E+10 | 0.281534E+10 | 0.00 | 0.00 |
October | 0.551443E+10 | 0.240554E+10 | 0.531360E+10 | 0.312473E+10 | 0.218887E+10 | 0.00 | 0.00 |
November | 0.426333E+10 | 0.329380E+10 | 0.457213E+10 | 0.286597E+10 | 0.170616E+10 | 0.00 | 0.00 |
December | 0.409905E+10 | 0.528017E+10 | 0.502552E+10 | 0.329066E+10 | 0.173486E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.741039E+11 | 0.330359E+11 | 0.702708E+11 | 0.375455E+11 | 0.327253E+11 | 0.00 | 0.00 |
Minimum of Months | 0.409905E+10 | 0.969808E+09 | 0.457213E+10 | 0.129815E+10 | 0.170616E+10 | 0.00 | 0.00 |
Maximum of Months | 0.725004E+10 | 0.549189E+10 | 0.745411E+10 | 0.503156E+10 | 0.371717E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.664855E+09 | 0.417822E+10 | 0.140189E+10 | 0.588084E+09 | 0.813801E+09 | 0.00 | 0.00 |
February | 0.145334E+10 | 0.299186E+10 | 0.206152E+10 | 0.942189E+09 | 0.111933E+10 | 0.00 | 0.00 |
March | 0.248468E+10 | 0.260672E+10 | 0.299988E+10 | 0.153409E+10 | 0.146579E+10 | 0.00 | 0.00 |
April | 0.364617E+10 | 0.158513E+10 | 0.370724E+10 | 0.187587E+10 | 0.183137E+10 | 0.00 | 0.00 |
May | 0.529562E+10 | 0.986402E+09 | 0.470670E+10 | 0.224261E+10 | 0.246409E+10 | 0.00 | 0.00 |
June | 0.520898E+10 | 0.665072E+09 | 0.439677E+10 | 0.189939E+10 | 0.249738E+10 | 0.00 | 0.00 |
July | 0.590187E+10 | 0.657422E+09 | 0.485075E+10 | 0.225346E+10 | 0.259730E+10 | 0.00 | 0.00 |
August | 0.473733E+10 | 0.741474E+09 | 0.399163E+10 | 0.181228E+10 | 0.217935E+10 | 0.00 | 0.00 |
September | 0.324954E+10 | 0.108431E+10 | 0.301868E+10 | 0.135494E+10 | 0.166374E+10 | 0.00 | 0.00 |
October | 0.173577E+10 | 0.162213E+10 | 0.197220E+10 | 0.791831E+09 | 0.118037E+10 | 0.00 | 0.00 |
November | 0.669815E+09 | 0.234116E+10 | 0.116024E+10 | 0.391959E+09 | 0.768282E+09 | 0.00 | 0.00 |
December | 0.385730E+09 | 0.401741E+10 | 0.106921E+10 | 0.375211E+09 | 0.693995E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.354337E+11 | 0.234773E+11 | 0.353367E+11 | 0.160619E+11 | 0.192748E+11 | 0.00 | 0.00 |
Minimum of Months | 0.385730E+09 | 0.657422E+09 | 0.106921E+10 | 0.375211E+09 | 0.693995E+09 | 0.00 | 0.00 |
Maximum of Months | 0.590187E+10 | 0.417822E+10 | 0.485075E+10 | 0.225346E+10 | 0.259730E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 26149649.10 | 0.683246E+10 | 0.947746E+09 | 0.00 | 0.947746E+09 | 0.00 | 0.00 |
February | 0.183744E+09 | 0.483777E+10 | 0.131493E+10 | 0.00 | 0.131493E+10 | 0.00 | 0.00 |
March | 0.459694E+09 | 0.410799E+10 | 0.179112E+10 | 0.00 | 0.179112E+10 | 0.00 | 0.00 |
April | 0.134058E+10 | 0.237341E+10 | 0.227279E+10 | 18219067.47 | 0.225457E+10 | 0.00 | 0.00 |
May | 0.313862E+10 | 0.134347E+10 | 0.330527E+10 | 0.180658E+09 | 0.312461E+10 | 0.00 | 0.00 |
June | 0.397409E+10 | 0.917984E+09 | 0.357125E+10 | 0.396637E+09 | 0.317462E+10 | 0.00 | 0.00 |
July | 0.405853E+10 | 0.911420E+09 | 0.352423E+10 | 0.306031E+09 | 0.321820E+10 | 0.00 | 0.00 |
August | 0.280886E+10 | 0.109026E+10 | 0.267477E+10 | 46900882.30 | 0.262787E+10 | 0.00 | 0.00 |
September | 0.161309E+10 | 0.174074E+10 | 0.201641E+10 | 514324.24 | 0.201589E+10 | 0.00 | 0.00 |
October | 0.651579E+09 | 0.270853E+10 | 0.144675E+10 | 0.00 | 0.144675E+10 | 0.00 | 0.00 |
November | 0.118277E+09 | 0.392102E+10 | 0.927030E+09 | 0.00 | 0.927030E+09 | 0.00 | 0.00 |
December | 4282174.99 | 0.659253E+10 | 0.803006E+09 | 0.00 | 0.803006E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.183775E+11 | 0.373776E+11 | 0.245953E+11 | 0.948960E+09 | 0.236463E+11 | 0.00 | 0.00 |
Minimum of Months | 4282174.99 | 0.911420E+09 | 0.803006E+09 | 0.00 | 0.803006E+09 | 0.00 | 0.00 |
Maximum of Months | 0.405853E+10 | 0.683246E+10 | 0.357125E+10 | 0.396637E+09 | 0.321820E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.616205E+09 | 0.412577E+10 | 0.138733E+10 | 0.580340E+09 | 0.806990E+09 | 0.00 | 0.00 |
February | 0.127732E+10 | 0.293027E+10 | 0.196751E+10 | 0.840059E+09 | 0.112745E+10 | 0.00 | 0.00 |
March | 0.238266E+10 | 0.255786E+10 | 0.296439E+10 | 0.148619E+10 | 0.147820E+10 | 0.00 | 0.00 |
April | 0.393170E+10 | 0.156653E+10 | 0.397512E+10 | 0.214227E+10 | 0.183284E+10 | 0.00 | 0.00 |
May | 0.491143E+10 | 0.943597E+09 | 0.444674E+10 | 0.195297E+10 | 0.249377E+10 | 0.00 | 0.00 |
June | 0.579352E+10 | 0.650816E+09 | 0.487126E+10 | 0.232810E+10 | 0.254317E+10 | 0.00 | 0.00 |
July | 0.598692E+10 | 0.638412E+09 | 0.493083E+10 | 0.231289E+10 | 0.261793E+10 | 0.00 | 0.00 |
August | 0.445004E+10 | 0.753535E+09 | 0.380205E+10 | 0.166009E+10 | 0.214197E+10 | 0.00 | 0.00 |
September | 0.309567E+10 | 0.114149E+10 | 0.294730E+10 | 0.131831E+10 | 0.162899E+10 | 0.00 | 0.00 |
October | 0.149032E+10 | 0.174047E+10 | 0.184530E+10 | 0.699840E+09 | 0.114546E+10 | 0.00 | 0.00 |
November | 0.606032E+09 | 0.244250E+10 | 0.113794E+10 | 0.381246E+09 | 0.756696E+09 | 0.00 | 0.00 |
December | 0.381502E+09 | 0.402267E+10 | 0.107343E+10 | 0.397762E+09 | 0.675666E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.349233E+11 | 0.235139E+11 | 0.353492E+11 | 0.161001E+11 | 0.192491E+11 | 0.00 | 0.00 |
Minimum of Months | 0.381502E+09 | 0.638412E+09 | 0.107343E+10 | 0.381246E+09 | 0.675666E+09 | 0.00 | 0.00 |
Maximum of Months | 0.598692E+10 | 0.412577E+10 | 0.493083E+10 | 0.232810E+10 | 0.261793E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.585057E+10 | 0.539209E+10 | 0.650968E+10 | 0.452360E+10 | 0.198608E+10 | 0.00 | 0.00 |
February | 0.737815E+10 | 0.415861E+10 | 0.745419E+10 | 0.503162E+10 | 0.242257E+10 | 0.00 | 0.00 |
March | 0.734748E+10 | 0.382001E+10 | 0.728729E+10 | 0.461401E+10 | 0.267328E+10 | 0.00 | 0.00 |
April | 0.694102E+10 | 0.250297E+10 | 0.640016E+10 | 0.348126E+10 | 0.291890E+10 | 0.00 | 0.00 |
May | 0.646562E+10 | 0.150582E+10 | 0.556254E+10 | 0.191252E+10 | 0.365002E+10 | 0.00 | 0.00 |
June | 0.593754E+10 | 0.100138E+10 | 0.483040E+10 | 0.129816E+10 | 0.353223E+10 | 0.00 | 0.00 |
July | 0.692117E+10 | 0.100002E+10 | 0.545825E+10 | 0.174106E+10 | 0.371719E+10 | 0.00 | 0.00 |
August | 0.718509E+10 | 0.118647E+10 | 0.582571E+10 | 0.244571E+10 | 0.338000E+10 | 0.00 | 0.00 |
September | 0.694217E+10 | 0.180055E+10 | 0.603189E+10 | 0.321653E+10 | 0.281536E+10 | 0.00 | 0.00 |
October | 0.549595E+10 | 0.265084E+10 | 0.531366E+10 | 0.312477E+10 | 0.218889E+10 | 0.00 | 0.00 |
November | 0.427995E+10 | 0.348873E+10 | 0.457218E+10 | 0.286601E+10 | 0.170617E+10 | 0.00 | 0.00 |
December | 0.418166E+10 | 0.523987E+10 | 0.502557E+10 | 0.329069E+10 | 0.173488E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.749264E+11 | 0.337474E+11 | 0.702715E+11 | 0.375459E+11 | 0.327256E+11 | 0.00 | 0.00 |
Minimum of Months | 0.418166E+10 | 0.100002E+10 | 0.457218E+10 | 0.129816E+10 | 0.170617E+10 | 0.00 | 0.00 |
Maximum of Months | 0.737815E+10 | 0.539209E+10 | 0.745419E+10 | 0.503162E+10 | 0.371719E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.673979E+09 | 0.421450E+10 | 0.140187E+10 | 0.588078E+09 | 0.813796E+09 | 0.00 | 0.00 |
February | 0.146727E+10 | 0.304903E+10 | 0.206150E+10 | 0.942179E+09 | 0.111932E+10 | 0.00 | 0.00 |
March | 0.251076E+10 | 0.266261E+10 | 0.299985E+10 | 0.153407E+10 | 0.146578E+10 | 0.00 | 0.00 |
April | 0.366992E+10 | 0.164876E+10 | 0.370721E+10 | 0.187585E+10 | 0.183136E+10 | 0.00 | 0.00 |
May | 0.531942E+10 | 0.101658E+10 | 0.470667E+10 | 0.224259E+10 | 0.246408E+10 | 0.00 | 0.00 |
June | 0.523253E+10 | 0.682348E+09 | 0.439674E+10 | 0.189937E+10 | 0.249737E+10 | 0.00 | 0.00 |
July | 0.591259E+10 | 0.688810E+09 | 0.485072E+10 | 0.225343E+10 | 0.259728E+10 | 0.00 | 0.00 |
August | 0.473314E+10 | 0.796458E+09 | 0.399160E+10 | 0.181226E+10 | 0.217934E+10 | 0.00 | 0.00 |
September | 0.321964E+10 | 0.119060E+10 | 0.301866E+10 | 0.135493E+10 | 0.166373E+10 | 0.00 | 0.00 |
October | 0.169655E+10 | 0.179499E+10 | 0.197219E+10 | 0.791823E+09 | 0.118036E+10 | 0.00 | 0.00 |
November | 0.656866E+09 | 0.249398E+10 | 0.116023E+10 | 0.391955E+09 | 0.768277E+09 | 0.00 | 0.00 |
December | 0.386182E+09 | 0.408397E+10 | 0.106920E+10 | 0.375208E+09 | 0.693990E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.354789E+11 | 0.243226E+11 | 0.353364E+11 | 0.160618E+11 | 0.192747E+11 | 0.00 | 0.00 |
Minimum of Months | 0.386182E+09 | 0.682348E+09 | 0.106920E+10 | 0.375208E+09 | 0.693990E+09 | 0.00 | 0.00 |
Maximum of Months | 0.591259E+10 | 0.421450E+10 | 0.485072E+10 | 0.225343E+10 | 0.259728E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 24860975.00 | 0.691356E+10 | 0.947751E+09 | 0.00 | 0.947751E+09 | 0.00 | 0.00 |
February | 0.172929E+09 | 0.490100E+10 | 0.131493E+10 | 0.00 | 0.131493E+10 | 0.00 | 0.00 |
March | 0.422041E+09 | 0.422616E+10 | 0.179113E+10 | 0.00 | 0.179113E+10 | 0.00 | 0.00 |
April | 0.124040E+10 | 0.249554E+10 | 0.227280E+10 | 18219161.88 | 0.225458E+10 | 0.00 | 0.00 |
May | 0.302884E+10 | 0.142406E+10 | 0.330529E+10 | 0.180659E+09 | 0.312463E+10 | 0.00 | 0.00 |
June | 0.390150E+10 | 0.961722E+09 | 0.357127E+10 | 0.396639E+09 | 0.317463E+10 | 0.00 | 0.00 |
July | 0.401148E+10 | 0.939595E+09 | 0.352425E+10 | 0.306032E+09 | 0.321822E+10 | 0.00 | 0.00 |
August | 0.278457E+10 | 0.110383E+10 | 0.267478E+10 | 46901125.33 | 0.262788E+10 | 0.00 | 0.00 |
September | 0.160124E+10 | 0.173035E+10 | 0.201642E+10 | 514326.90 | 0.201591E+10 | 0.00 | 0.00 |
October | 0.651522E+09 | 0.266521E+10 | 0.144676E+10 | 0.00 | 0.144676E+10 | 0.00 | 0.00 |
November | 0.117536E+09 | 0.387478E+10 | 0.927034E+09 | 0.00 | 0.927034E+09 | 0.00 | 0.00 |
December | 4664377.13 | 0.662781E+10 | 0.803011E+09 | 0.00 | 0.803011E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.179616E+11 | 0.378636E+11 | 0.245954E+11 | 0.948964E+09 | 0.236465E+11 | 0.00 | 0.00 |
Minimum of Months | 4664377.13 | 0.939595E+09 | 0.803011E+09 | 0.00 | 0.803011E+09 | 0.00 | 0.00 |
Maximum of Months | 0.401148E+10 | 0.691356E+10 | 0.357127E+10 | 0.396639E+09 | 0.321822E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.605293E+09 | 0.415774E+10 | 0.138734E+10 | 0.580346E+09 | 0.806996E+09 | 0.00 | 0.00 |
February | 0.125701E+10 | 0.295180E+10 | 0.196753E+10 | 0.840067E+09 | 0.112746E+10 | 0.00 | 0.00 |
March | 0.233811E+10 | 0.260304E+10 | 0.296442E+10 | 0.148621E+10 | 0.147821E+10 | 0.00 | 0.00 |
April | 0.387919E+10 | 0.158791E+10 | 0.397515E+10 | 0.214229E+10 | 0.183285E+10 | 0.00 | 0.00 |
May | 0.486366E+10 | 0.960023E+09 | 0.444678E+10 | 0.195299E+10 | 0.249379E+10 | 0.00 | 0.00 |
June | 0.575977E+10 | 0.654588E+09 | 0.487130E+10 | 0.232812E+10 | 0.254318E+10 | 0.00 | 0.00 |
July | 0.596746E+10 | 0.633334E+09 | 0.493087E+10 | 0.231292E+10 | 0.261795E+10 | 0.00 | 0.00 |
August | 0.444198E+10 | 0.732878E+09 | 0.380208E+10 | 0.166010E+10 | 0.214198E+10 | 0.00 | 0.00 |
September | 0.309642E+10 | 0.110358E+10 | 0.294732E+10 | 0.131832E+10 | 0.162900E+10 | 0.00 | 0.00 |
October | 0.149738E+10 | 0.168580E+10 | 0.184531E+10 | 0.699847E+09 | 0.114547E+10 | 0.00 | 0.00 |
November | 0.603267E+09 | 0.240101E+10 | 0.113795E+10 | 0.381250E+09 | 0.756701E+09 | 0.00 | 0.00 |
December | 0.376572E+09 | 0.403508E+10 | 0.107344E+10 | 0.397766E+09 | 0.675671E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.346861E+11 | 0.235068E+11 | 0.353495E+11 | 0.161002E+11 | 0.192493E+11 | 0.00 | 0.00 |
Minimum of Months | 0.376572E+09 | 0.633334E+09 | 0.107344E+10 | 0.381250E+09 | 0.675671E+09 | 0.00 | 0.00 |
Maximum of Months | 0.596746E+10 | 0.415774E+10 | 0.493087E+10 | 0.232812E+10 | 0.261795E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.568247E+10 | 0.560305E+10 | 0.650961E+10 | 0.452355E+10 | 0.198606E+10 | 0.00 | 0.00 |
February | 0.721689E+10 | 0.425558E+10 | 0.745411E+10 | 0.503156E+10 | 0.242255E+10 | 0.00 | 0.00 |
March | 0.717639E+10 | 0.393424E+10 | 0.728722E+10 | 0.461396E+10 | 0.267326E+10 | 0.00 | 0.00 |
April | 0.680755E+10 | 0.257130E+10 | 0.640010E+10 | 0.348122E+10 | 0.291888E+10 | 0.00 | 0.00 |
May | 0.634967E+10 | 0.156860E+10 | 0.556249E+10 | 0.191250E+10 | 0.364999E+10 | 0.00 | 0.00 |
June | 0.585339E+10 | 0.104589E+10 | 0.483036E+10 | 0.129815E+10 | 0.353221E+10 | 0.00 | 0.00 |
July | 0.687459E+10 | 0.100656E+10 | 0.545821E+10 | 0.174104E+10 | 0.371717E+10 | 0.00 | 0.00 |
August | 0.714453E+10 | 0.116634E+10 | 0.582566E+10 | 0.244568E+10 | 0.337998E+10 | 0.00 | 0.00 |
September | 0.689414E+10 | 0.175976E+10 | 0.603183E+10 | 0.321649E+10 | 0.281534E+10 | 0.00 | 0.00 |
October | 0.545425E+10 | 0.258193E+10 | 0.531360E+10 | 0.312473E+10 | 0.218887E+10 | 0.00 | 0.00 |
November | 0.421950E+10 | 0.346778E+10 | 0.457213E+10 | 0.286597E+10 | 0.170616E+10 | 0.00 | 0.00 |
December | 0.406971E+10 | 0.540656E+10 | 0.502552E+10 | 0.329066E+10 | 0.173486E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.737431E+11 | 0.343676E+11 | 0.702708E+11 | 0.375455E+11 | 0.327253E+11 | 0.00 | 0.00 |
Minimum of Months | 0.406971E+10 | 0.100656E+10 | 0.457213E+10 | 0.129815E+10 | 0.170616E+10 | 0.00 | 0.00 |
Maximum of Months | 0.721689E+10 | 0.560305E+10 | 0.745411E+10 | 0.503156E+10 | 0.371717E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.660312E+09 | 0.424974E+10 | 0.140189E+10 | 0.588084E+09 | 0.813801E+09 | 0.00 | 0.00 |
February | 0.144156E+10 | 0.307184E+10 | 0.206152E+10 | 0.942189E+09 | 0.111933E+10 | 0.00 | 0.00 |
March | 0.246736E+10 | 0.270971E+10 | 0.299988E+10 | 0.153409E+10 | 0.146579E+10 | 0.00 | 0.00 |
April | 0.361717E+10 | 0.167889E+10 | 0.370724E+10 | 0.187587E+10 | 0.183137E+10 | 0.00 | 0.00 |
May | 0.527628E+10 | 0.103349E+10 | 0.470670E+10 | 0.224261E+10 | 0.246409E+10 | 0.00 | 0.00 |
June | 0.519824E+10 | 0.693976E+09 | 0.439677E+10 | 0.189939E+10 | 0.249738E+10 | 0.00 | 0.00 |
July | 0.589651E+10 | 0.680878E+09 | 0.485075E+10 | 0.225346E+10 | 0.259730E+10 | 0.00 | 0.00 |
August | 0.472600E+10 | 0.776069E+09 | 0.399163E+10 | 0.181228E+10 | 0.217935E+10 | 0.00 | 0.00 |
September | 0.322058E+10 | 0.115500E+10 | 0.301868E+10 | 0.135494E+10 | 0.166374E+10 | 0.00 | 0.00 |
October | 0.170124E+10 | 0.174093E+10 | 0.197220E+10 | 0.791831E+09 | 0.118037E+10 | 0.00 | 0.00 |
November | 0.652589E+09 | 0.245769E+10 | 0.116024E+10 | 0.391959E+09 | 0.768282E+09 | 0.00 | 0.00 |
December | 0.380233E+09 | 0.410070E+10 | 0.106921E+10 | 0.375211E+09 | 0.693995E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.352381E+11 | 0.243489E+11 | 0.353367E+11 | 0.160619E+11 | 0.192748E+11 | 0.00 | 0.00 |
Minimum of Months | 0.380233E+09 | 0.680878E+09 | 0.106921E+10 | 0.375211E+09 | 0.693995E+09 | 0.00 | 0.00 |
Maximum of Months | 0.589651E+10 | 0.424974E+10 | 0.485075E+10 | 0.225346E+10 | 0.259730E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.616480E+10 | -0.539720E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -767601939.5 | 58.99 | 0.00 | 0.00 |
February | 0.569169E+10 | -0.501702E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -674676814.5 | 58.99 | 0.00 | 0.00 |
March | 0.664505E+10 | -0.591628E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -728771938.1 | 58.99 | 0.00 | 0.00 |
April | 0.584740E+10 | -0.516353E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -683873016.8 | 58.98 | 0.00 | 0.00 |
May | 0.595327E+10 | -0.526231E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690957164.5 | 58.98 | 0.00 | 0.00 |
June | 0.558395E+10 | -0.491540E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668557389.3 | 58.98 | 0.00 | 0.00 |
July | 0.507395E+10 | -0.438685E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687109407.7 | 58.98 | 0.00 | 0.00 |
August | 0.540319E+10 | -0.471252E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690665290.4 | 58.98 | 0.00 | 0.00 |
September | 0.493312E+10 | -0.426453E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668591397.7 | 58.98 | 0.00 | 0.00 |
October | 0.527956E+10 | -0.457629E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -703267103.0 | 58.98 | 0.00 | 0.00 |
November | 0.546800E+10 | -0.476581E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -702187564.8 | 58.98 | 0.00 | 0.00 |
December | 0.576126E+10 | -0.500369E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -757574275.6 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.678052E+11 | -0.593814E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.842383E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.493312E+10 | -0.591628E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -767601939.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.664505E+10 | -0.426453E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -668557389.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.63 | 0.62 | 01-JAN-08:39 | 4890.49 | 32.14 | 200.50 | 233.00 | 4260.65 | 36.55 | 241.50 | 223.33 |
February | 265.33 | 0.63 | 0.62 | 01-FEB-08:39 | 7790.54 | 33.92 | 234.50 | 253.17 | 3408.27 | 31.34 | 235.50 | 241.50 |
March | 254.17 | 0.63 | 0.62 | 02-MAR-10:39 | 11196.84 | 34.70 | 215.00 | 317.50 | 1766.40 | 21.30 | 155.83 | 281.50 |
April | 296.33 | 0.64 | 0.62 | 01-APR-07:19 | 2231.85 | 17.52 | 0.17 | 343.67 | 1379.65 | 20.34 | 136.00 | 309.33 |
May | 437.50 | 0.63 | 0.62 | 01-MAY-05:49 | 1956.63 | 18.07 | 0.00 | 404.00 | 1095.48 | 20.82 | 209.17 | 360.33 |
June | 401.83 | 0.63 | 0.62 | 01-JUN-04:00 | 1855.76 | 18.15 | 0.00 | 405.33 | 1052.81 | 20.91 | 202.00 | 361.17 |
July | 409.17 | 0.63 | 0.62 | 01-JUL-05:10 | 2012.18 | 18.43 | 0.00 | 412.17 | 1151.27 | 21.20 | 218.83 | 371.33 |
August | 352.83 | 0.63 | 0.62 | 01-AUG-07:40 | 2542.76 | 19.02 | 8.67 | 372.17 | 1344.50 | 21.44 | 201.83 | 333.50 |
September | 344.17 | 0.63 | 0.62 | 01-SEP-06:10 | 4382.80 | 22.29 | 95.83 | 326.50 | 1384.14 | 21.33 | 194.83 | 293.33 |
October | 299.00 | 0.62 | 0.62 | 01-OCT-06:40 | 5550.88 | 31.16 | 262.67 | 293.33 | 1422.60 | 23.62 | 192.33 | 267.67 |
November | 255.50 | 0.63 | 0.62 | 01-NOV-07:00 | 3914.02 | 31.22 | 214.50 | 235.00 | 3329.85 | 35.35 | 246.83 | 215.67 |
December | 226.33 | 0.63 | 0.62 | 01-DEC-08:30 | 3526.14 | 29.47 | 168.83 | 218.00 | 3137.08 | 34.89 | 216.17 | 201.50 |
Annual Sum or Average | 3785.50 | 0.63 | 3976.44 | 24.28 | 1400.67 | 3813.83 | 1878.01 | 24.76 | 2450.83 | 3460.17 | ||
Minimum of Months | 226.33 | 0.62 | 0.62 | 1855.76 | 17.52 | 0.00 | 218.00 | 1052.81 | 20.34 | 136.00 | 201.50 | |
Maximum of Months | 437.50 | 0.64 | 0.62 | 11196.84 | 34.70 | 262.67 | 412.17 | 4260.65 | 36.55 | 246.83 | 371.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.64 | 0.62 | 01-JAN-08:39 | 1557.72 | 20.22 | 76.67 | 213.50 | 972.31 | 23.41 | 90.50 | 179.50 |
February | 265.33 | 0.63 | 0.62 | 01-FEB-08:39 | 2118.49 | 20.69 | 73.67 | 241.00 | 1109.81 | 22.02 | 97.83 | 211.17 |
March | 254.17 | 0.63 | 0.62 | 02-MAR-10:39 | 3672.44 | 22.36 | 80.83 | 309.83 | 2204.29 | 23.74 | 88.17 | 267.17 |
April | 296.33 | 0.64 | 0.62 | 01-APR-06:49 | 3937.10 | 21.32 | 84.33 | 351.00 | 2290.30 | 22.77 | 72.00 | 313.50 |
May | 437.50 | 0.63 | 0.62 | 01-MAY-05:10 | 3595.91 | 21.37 | 134.50 | 412.50 | 1586.18 | 22.05 | 85.50 | 377.17 |
June | 401.83 | 0.63 | 0.62 | 01-JUN-04:49 | 4360.53 | 21.82 | 120.00 | 411.67 | 2038.18 | 23.35 | 84.50 | 377.17 |
July | 409.17 | 0.63 | 0.62 | 01-JUL-04:40 | 4161.44 | 22.15 | 125.00 | 418.00 | 1903.99 | 22.73 | 76.67 | 386.50 |
August | 352.83 | 0.63 | 0.62 | 01-AUG-07:40 | 3436.48 | 20.80 | 86.67 | 374.83 | 1543.00 | 22.41 | 82.17 | 336.67 |
September | 344.17 | 0.63 | 0.62 | 01-SEP-05:00 | 2625.91 | 19.38 | 76.33 | 323.83 | 1451.29 | 22.20 | 85.67 | 286.17 |
October | 299.00 | 0.63 | 0.62 | 01-OCT-06:40 | 2019.06 | 20.48 | 95.50 | 278.83 | 875.56 | 21.07 | 61.00 | 234.50 |
November | 255.50 | 0.64 | 0.62 | 01-NOV-07:00 | 1309.58 | 19.20 | 73.50 | 217.83 | 739.63 | 22.22 | 74.67 | 173.00 |
December | 226.33 | 0.64 | 0.62 | 01-DEC-08:30 | 1101.64 | 18.10 | 46.50 | 196.33 | 802.88 | 22.98 | 78.50 | 159.67 |
Annual Sum or Average | 3785.50 | 0.63 | 3004.43 | 20.80 | 1073.50 | 3749.17 | 1515.90 | 22.55 | 977.17 | 3302.17 | ||
Minimum of Months | 226.33 | 0.63 | 0.62 | 1101.64 | 18.10 | 46.50 | 196.33 | 739.63 | 21.07 | 61.00 | 159.67 | |
Maximum of Months | 437.50 | 0.64 | 0.62 | 4360.53 | 22.36 | 134.50 | 418.00 | 2290.30 | 23.74 | 97.83 | 386.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.65 | 0.62 | 01-JAN-09:20 | 587.26 | 14.44 | 0.00 | 195.17 | 341.08 | 17.47 | 0.00 | 115.67 |
February | 265.33 | 0.64 | 0.62 | 01-FEB-08:39 | 741.20 | 15.76 | 0.00 | 230.33 | 445.45 | 18.73 | 0.00 | 180.33 |
March | 254.17 | 0.64 | 0.62 | 02-MAR-10:39 | 799.30 | 16.44 | 0.00 | 301.50 | 512.46 | 19.38 | 2.33 | 234.50 |
April | 296.33 | 0.64 | 0.62 | 01-APR-07:40 | 910.94 | 16.94 | 0.00 | 349.50 | 578.68 | 19.70 | 19.67 | 304.50 |
May | 437.50 | 0.62 | 0.62 | 01-MAY-05:19 | 1255.51 | 19.37 | 30.17 | 427.67 | 730.13 | 22.87 | 157.33 | 405.50 |
June | 401.83 | 0.62 | 0.62 | 01-JUN-04:49 | 1498.44 | 21.70 | 76.83 | 433.50 | 865.21 | 24.22 | 223.83 | 404.00 |
July | 409.17 | 0.62 | 0.62 | 01-JUL-04:49 | 1416.23 | 20.13 | 38.50 | 434.33 | 844.96 | 23.78 | 228.83 | 411.67 |
August | 352.83 | 0.62 | 0.62 | 01-AUG-07:40 | 1187.98 | 18.25 | 0.00 | 382.00 | 707.60 | 20.95 | 106.50 | 340.33 |
September | 344.17 | 0.63 | 0.62 | 01-SEP-06:10 | 900.34 | 16.96 | 0.00 | 322.17 | 530.81 | 19.69 | 1.00 | 268.33 |
October | 299.00 | 0.63 | 0.62 | 01-OCT-06:00 | 741.30 | 15.73 | 0.00 | 267.33 | 416.86 | 18.50 | 0.00 | 194.00 |
November | 255.50 | 0.65 | 0.62 | 01-NOV-07:00 | 573.09 | 14.29 | 0.00 | 200.17 | 320.50 | 17.07 | 0.00 | 106.00 |
December | 226.33 | 0.65 | 0.62 | 01-DEC-08:00 | 546.44 | 14.17 | 0.00 | 179.50 | 306.52 | 17.08 | 0.00 | 72.33 |
Annual Sum or Average | 3785.50 | 0.63 | 994.41 | 17.48 | 145.50 | 3723.17 | 587.51 | 20.44 | 739.50 | 3037.17 | ||
Minimum of Months | 226.33 | 0.62 | 0.62 | 546.44 | 14.17 | 0.00 | 179.50 | 306.52 | 17.07 | 0.00 | 72.33 | |
Maximum of Months | 437.50 | 0.65 | 0.62 | 1498.44 | 21.70 | 76.83 | 434.33 | 865.21 | 24.22 | 228.83 | 411.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.64 | 0.62 | 01-JAN-09:20 | 1536.69 | 20.39 | 75.67 | 216.33 | 914.10 | 23.03 | 82.33 | 181.50 |
February | 265.33 | 0.63 | 0.62 | 01-FEB-08:50 | 2138.94 | 20.91 | 75.00 | 243.33 | 1135.00 | 22.14 | 89.67 | 213.67 |
March | 254.17 | 0.63 | 0.62 | 02-MAR-10:39 | 3413.43 | 22.35 | 78.83 | 310.33 | 1985.83 | 23.61 | 80.17 | 266.33 |
April | 296.33 | 0.64 | 0.62 | 01-APR-07:49 | 3952.77 | 20.82 | 84.50 | 346.17 | 1757.64 | 20.85 | 48.17 | 311.50 |
May | 437.50 | 0.63 | 0.62 | 01-MAY-06:10 | 3258.91 | 18.62 | 80.67 | 414.50 | 1899.74 | 20.77 | 55.83 | 381.33 |
June | 401.83 | 0.63 | 0.62 | 01-JUN-05:10 | 3465.43 | 17.46 | 46.67 | 424.67 | 1539.16 | 19.12 | 1.17 | 386.83 |
July | 409.17 | 0.62 | 0.62 | 01-JUL-05:10 | 3743.58 | 17.93 | 53.67 | 425.83 | 1677.55 | 19.35 | 5.17 | 388.67 |
August | 352.83 | 0.63 | 0.62 | 01-AUG-07:40 | 3421.31 | 20.11 | 79.17 | 377.50 | 1916.96 | 21.82 | 64.33 | 335.83 |
September | 344.17 | 0.63 | 0.62 | 01-SEP-06:40 | 2898.14 | 20.97 | 99.17 | 325.50 | 1640.46 | 22.54 | 86.83 | 289.67 |
October | 299.00 | 0.63 | 0.62 | 01-OCT-06:00 | 2184.02 | 21.03 | 99.83 | 280.00 | 913.66 | 21.02 | 59.17 | 236.83 |
November | 255.50 | 0.64 | 0.62 | 01-NOV-08:09 | 1304.07 | 19.34 | 75.33 | 220.33 | 680.20 | 20.53 | 59.67 | 176.00 |
December | 226.33 | 0.64 | 0.62 | 01-DEC-08:00 | 1212.73 | 19.72 | 64.33 | 203.83 | 637.05 | 20.90 | 55.83 | 157.50 |
Annual Sum or Average | 3785.50 | 0.63 | 2851.86 | 19.78 | 912.83 | 3788.33 | 1457.48 | 21.15 | 688.33 | 3325.67 | ||
Minimum of Months | 226.33 | 0.62 | 0.62 | 1212.73 | 17.46 | 46.67 | 203.83 | 637.05 | 19.12 | 1.17 | 157.50 | |
Maximum of Months | 437.50 | 0.64 | 0.62 | 3952.77 | 22.35 | 99.83 | 425.83 | 1985.83 | 23.61 | 89.67 | 388.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.63 | 0.62 | 01-JAN-08:39 | 4714.68 | 31.29 | 198.00 | 231.17 | 4132.05 | 36.23 | 233.17 | 221.17 |
February | 265.33 | 0.63 | 0.62 | 01-FEB-08:39 | 7580.88 | 33.34 | 233.33 | 252.00 | 3252.96 | 29.93 | 172.67 | 240.00 |
March | 254.17 | 0.63 | 0.62 | 02-MAR-10:39 | 10997.54 | 34.16 | 215.00 | 316.17 | 1619.87 | 18.65 | 12.00 | 278.17 |
April | 296.33 | 0.64 | 0.62 | 01-APR-07:19 | 2090.92 | 14.00 | 0.00 | 341.67 | 1276.25 | 18.03 | 11.00 | 304.33 |
May | 437.50 | 0.63 | 0.62 | 01-MAY-05:00 | 1855.98 | 14.56 | 0.00 | 401.00 | 1030.13 | 18.46 | 3.17 | 354.67 |
June | 401.83 | 0.64 | 0.62 | 01-JUN-05:10 | 1763.36 | 14.79 | 0.00 | 403.33 | 994.51 | 18.68 | 1.50 | 357.17 |
July | 409.17 | 0.63 | 0.62 | 01-JUL-05:10 | 1908.84 | 15.08 | 0.00 | 408.83 | 1084.69 | 19.00 | 13.00 | 366.83 |
August | 352.83 | 0.63 | 0.62 | 01-AUG-07:40 | 2412.23 | 15.60 | 8.00 | 370.00 | 1257.30 | 19.07 | 22.17 | 329.17 |
September | 344.17 | 0.63 | 0.62 | 01-SEP-06:19 | 4239.96 | 19.62 | 90.33 | 323.83 | 1284.56 | 18.69 | 14.83 | 288.67 |
October | 299.00 | 0.63 | 0.62 | 01-OCT-06:49 | 5413.45 | 30.62 | 257.67 | 291.50 | 1326.96 | 21.21 | 69.83 | 265.00 |
November | 255.50 | 0.63 | 0.62 | 01-NOV-07:00 | 3778.85 | 30.45 | 213.67 | 233.83 | 3236.00 | 35.10 | 245.33 | 213.83 |
December | 226.33 | 0.63 | 0.62 | 01-DEC-08:30 | 3380.74 | 28.27 | 167.00 | 216.50 | 3034.19 | 34.50 | 211.00 | 199.33 |
Annual Sum or Average | 3785.50 | 0.63 | 3839.59 | 22.02 | 1383.00 | 3789.83 | 1782.76 | 22.84 | 1009.67 | 3418.33 | ||
Minimum of Months | 226.33 | 0.63 | 0.62 | 1763.36 | 14.00 | 0.00 | 216.50 | 994.51 | 18.03 | 1.50 | 199.33 | |
Maximum of Months | 437.50 | 0.64 | 0.62 | 10997.54 | 34.16 | 257.67 | 408.83 | 4132.05 | 36.23 | 245.33 | 366.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.64 | 0.62 | 01-JAN-08:39 | 1507.70 | 19.80 | 76.00 | 211.83 | 936.25 | 23.19 | 85.50 | 175.17 |
February | 265.33 | 0.63 | 0.62 | 01-FEB-08:39 | 2047.10 | 20.26 | 73.67 | 238.83 | 1056.16 | 21.79 | 88.33 | 207.33 |
March | 254.17 | 0.63 | 0.62 | 02-MAR-10:39 | 3574.00 | 21.95 | 80.83 | 307.00 | 2128.59 | 23.53 | 80.50 | 263.00 |
April | 296.33 | 0.64 | 0.62 | 01-APR-06:49 | 3827.69 | 20.92 | 84.33 | 348.50 | 2202.98 | 22.59 | 67.33 | 309.33 |
May | 437.50 | 0.63 | 0.62 | 01-MAY-05:10 | 3405.61 | 19.61 | 110.17 | 410.67 | 1515.20 | 21.87 | 81.67 | 374.00 |
June | 401.83 | 0.63 | 0.62 | 01-JUN-04:49 | 4247.75 | 21.43 | 119.83 | 409.67 | 1923.18 | 22.29 | 69.83 | 372.17 |
July | 409.17 | 0.63 | 0.62 | 01-JUL-04:49 | 3922.83 | 20.38 | 102.50 | 415.50 | 1822.69 | 22.56 | 73.00 | 383.00 |
August | 352.83 | 0.63 | 0.62 | 01-AUG-07:40 | 3334.68 | 20.39 | 86.67 | 372.50 | 1469.04 | 22.23 | 72.17 | 331.67 |
September | 344.17 | 0.63 | 0.62 | 01-SEP-05:00 | 2545.85 | 18.95 | 75.83 | 321.50 | 1391.23 | 22.00 | 78.17 | 281.50 |
October | 299.00 | 0.63 | 0.62 | 01-OCT-06:40 | 1960.56 | 20.07 | 95.00 | 276.00 | 827.09 | 20.62 | 54.00 | 229.17 |
November | 255.50 | 0.64 | 0.62 | 01-NOV-07:00 | 1265.25 | 18.76 | 73.17 | 216.17 | 682.66 | 20.64 | 58.00 | 167.83 |
December | 226.33 | 0.64 | 0.62 | 01-DEC-08:30 | 1059.85 | 17.61 | 46.17 | 194.33 | 773.39 | 22.75 | 77.17 | 154.50 |
Annual Sum or Average | 3785.50 | 0.63 | 2894.41 | 20.08 | 1024.17 | 3722.50 | 1446.91 | 22.15 | 885.67 | 3248.67 | ||
Minimum of Months | 226.33 | 0.63 | 0.62 | 1059.85 | 17.61 | 46.17 | 194.33 | 682.66 | 20.62 | 54.00 | 154.50 | |
Maximum of Months | 437.50 | 0.64 | 0.62 | 4247.75 | 21.95 | 119.83 | 415.50 | 2202.98 | 23.53 | 88.33 | 383.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.65 | 0.62 | 01-JAN-09:30 | 560.93 | 10.84 | 0.00 | 191.17 | 326.96 | 14.98 | 0.00 | 103.33 |
February | 265.33 | 0.64 | 0.62 | 01-FEB-08:39 | 708.47 | 12.39 | 0.00 | 226.50 | 428.16 | 16.46 | 0.00 | 173.67 |
March | 254.17 | 0.64 | 0.62 | 02-MAR-10:39 | 765.38 | 13.42 | 0.00 | 298.33 | 495.09 | 17.48 | 0.00 | 225.83 |
April | 296.33 | 0.64 | 0.62 | 01-APR-07:40 | 874.39 | 14.03 | 0.00 | 348.17 | 560.13 | 18.00 | 0.17 | 296.33 |
May | 437.50 | 0.62 | 0.62 | 01-MAY-05:19 | 1204.18 | 16.35 | 30.00 | 426.67 | 695.63 | 20.08 | 38.83 | 398.33 |
June | 401.83 | 0.62 | 0.62 | 01-JUN-04:49 | 1413.19 | 17.43 | 43.83 | 430.50 | 831.75 | 22.54 | 115.83 | 399.33 |
July | 409.17 | 0.62 | 0.62 | 01-JUL-04:49 | 1357.32 | 17.29 | 38.33 | 432.50 | 812.93 | 22.13 | 110.00 | 407.83 |
August | 352.83 | 0.63 | 0.62 | 01-AUG-07:40 | 1128.47 | 15.13 | 0.00 | 379.33 | 681.19 | 19.06 | 16.83 | 334.17 |
September | 344.17 | 0.63 | 0.62 | 01-SEP-06:10 | 862.61 | 13.73 | 0.00 | 318.83 | 510.95 | 17.62 | 0.00 | 262.00 |
October | 299.00 | 0.64 | 0.62 | 01-OCT-06:00 | 709.99 | 12.17 | 0.00 | 262.83 | 400.09 | 16.11 | 0.00 | 184.00 |
November | 255.50 | 0.65 | 0.62 | 01-NOV-08:09 | 548.14 | 10.53 | 0.00 | 196.33 | 307.04 | 14.50 | 0.00 | 93.67 |
December | 226.33 | 0.65 | 0.62 | 01-DEC-08:00 | 522.20 | 10.40 | 0.00 | 175.50 | 293.41 | 14.48 | 0.00 | 55.67 |
Annual Sum or Average | 3785.50 | 0.63 | 949.35 | 14.12 | 112.17 | 3686.67 | 564.48 | 18.30 | 281.67 | 2934.17 | ||
Minimum of Months | 226.33 | 0.62 | 0.62 | 522.20 | 10.40 | 0.00 | 175.50 | 293.41 | 14.48 | 0.00 | 55.67 | |
Maximum of Months | 437.50 | 0.65 | 0.62 | 1413.19 | 17.43 | 43.83 | 432.50 | 831.75 | 22.54 | 115.83 | 407.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.64 | 0.62 | 01-JAN-09:30 | 1485.59 | 20.06 | 75.50 | 214.17 | 812.39 | 21.47 | 66.50 | 175.00 |
February | 265.33 | 0.63 | 0.62 | 01-FEB-08:50 | 2065.85 | 20.58 | 75.00 | 241.67 | 1079.97 | 22.04 | 88.33 | 210.50 |
March | 254.17 | 0.63 | 0.62 | 02-MAR-10:39 | 3053.11 | 19.86 | 59.67 | 307.00 | 1914.08 | 23.50 | 78.67 | 261.00 |
April | 296.33 | 0.64 | 0.62 | 01-APR-07:49 | 3855.88 | 20.46 | 84.50 | 344.17 | 1681.30 | 20.72 | 45.33 | 306.67 |
May | 437.50 | 0.63 | 0.62 | 01-MAY-06:10 | 3161.28 | 18.23 | 80.50 | 411.17 | 1789.18 | 20.63 | 54.67 | 376.83 |
June | 401.83 | 0.63 | 0.62 | 01-JUN-05:10 | 3362.94 | 17.04 | 46.50 | 421.17 | 1465.00 | 18.95 | 0.83 | 381.83 |
July | 409.17 | 0.63 | 0.62 | 01-JUL-05:10 | 3628.50 | 17.52 | 53.67 | 422.83 | 1596.46 | 19.19 | 3.50 | 383.83 |
August | 352.83 | 0.63 | 0.62 | 01-AUG-07:40 | 3163.00 | 19.74 | 79.17 | 375.33 | 1837.44 | 21.69 | 62.17 | 331.67 |
September | 344.17 | 0.63 | 0.62 | 01-SEP-06:40 | 2813.58 | 20.62 | 99.00 | 323.67 | 1576.67 | 22.42 | 83.67 | 286.00 |
October | 299.00 | 0.63 | 0.62 | 01-OCT-07:10 | 2121.27 | 20.69 | 99.33 | 277.50 | 868.18 | 20.90 | 58.83 | 232.50 |
November | 255.50 | 0.64 | 0.62 | 01-NOV-08:09 | 1240.42 | 18.67 | 71.33 | 217.67 | 649.09 | 20.41 | 59.83 | 171.83 |
December | 226.33 | 0.64 | 0.62 | 01-DEC-08:00 | 1064.87 | 17.43 | 44.33 | 200.50 | 608.21 | 20.80 | 55.17 | 151.67 |
Annual Sum or Average | 3785.50 | 0.63 | 2727.22 | 19.13 | 868.50 | 3756.83 | 1386.25 | 20.93 | 657.50 | 3269.33 | ||
Minimum of Months | 226.33 | 0.63 | 0.62 | 1064.87 | 17.04 | 44.33 | 200.50 | 608.21 | 18.95 | 0.83 | 151.67 | |
Maximum of Months | 437.50 | 0.64 | 0.62 | 3855.88 | 20.69 | 99.33 | 422.83 | 1914.08 | 23.50 | 88.33 | 383.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.63 | 0.62 | 01-JAN-08:39 | 4714.72 | 31.29 | 198.00 | 231.33 | 4131.98 | 36.23 | 233.17 | 221.17 |
February | 265.33 | 0.63 | 0.62 | 01-FEB-08:39 | 7580.91 | 33.34 | 233.33 | 252.00 | 3252.86 | 29.93 | 172.67 | 240.00 |
March | 254.17 | 0.63 | 0.62 | 02-MAR-10:39 | 10997.51 | 34.16 | 215.00 | 316.17 | 1619.77 | 18.65 | 12.17 | 278.17 |
April | 296.33 | 0.64 | 0.62 | 01-APR-07:19 | 2090.85 | 14.00 | 0.00 | 341.67 | 1276.17 | 18.03 | 11.00 | 304.17 |
May | 437.50 | 0.63 | 0.62 | 01-MAY-05:00 | 1855.89 | 14.56 | 0.00 | 401.00 | 1030.05 | 18.46 | 3.17 | 354.67 |
June | 401.83 | 0.64 | 0.62 | 01-JUN-05:10 | 1763.29 | 14.79 | 0.00 | 403.33 | 994.44 | 18.69 | 1.50 | 357.17 |
July | 409.17 | 0.63 | 0.62 | 01-JUL-05:10 | 1908.77 | 15.08 | 0.00 | 408.83 | 1084.62 | 19.00 | 13.00 | 366.83 |
August | 352.83 | 0.63 | 0.62 | 01-AUG-07:40 | 2412.13 | 15.60 | 8.00 | 370.00 | 1257.21 | 19.07 | 22.17 | 329.17 |
September | 344.17 | 0.63 | 0.62 | 01-SEP-06:19 | 4239.88 | 19.62 | 90.33 | 323.83 | 1284.47 | 18.69 | 14.83 | 288.67 |
October | 299.00 | 0.63 | 0.62 | 01-OCT-06:49 | 5413.42 | 30.62 | 257.67 | 291.50 | 1326.87 | 21.21 | 69.83 | 265.00 |
November | 255.50 | 0.63 | 0.62 | 01-NOV-07:00 | 3778.87 | 30.45 | 213.67 | 233.83 | 3235.93 | 35.10 | 245.33 | 213.83 |
December | 226.33 | 0.63 | 0.62 | 01-DEC-08:30 | 3380.77 | 28.27 | 167.00 | 216.50 | 3034.13 | 34.50 | 211.00 | 199.33 |
Annual Sum or Average | 3785.50 | 0.63 | 3839.55 | 22.02 | 1383.00 | 3790.00 | 1782.68 | 22.84 | 1009.83 | 3418.17 | ||
Minimum of Months | 226.33 | 0.63 | 0.62 | 1763.29 | 14.00 | 0.00 | 216.50 | 994.44 | 18.03 | 1.50 | 199.33 | |
Maximum of Months | 437.50 | 0.64 | 0.62 | 10997.51 | 34.16 | 257.67 | 408.83 | 4131.98 | 36.23 | 245.33 | 366.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.64 | 0.62 | 01-JAN-08:39 | 1507.70 | 19.80 | 76.00 | 211.83 | 936.21 | 23.19 | 85.50 | 175.17 |
February | 265.33 | 0.63 | 0.62 | 01-FEB-08:39 | 2047.10 | 20.27 | 73.67 | 238.83 | 1056.11 | 21.79 | 88.33 | 207.33 |
March | 254.17 | 0.63 | 0.62 | 02-MAR-10:39 | 3574.01 | 21.95 | 80.83 | 307.00 | 2128.54 | 23.53 | 80.50 | 263.00 |
April | 296.33 | 0.64 | 0.62 | 01-APR-06:49 | 3827.70 | 20.92 | 84.33 | 348.50 | 2202.93 | 22.59 | 67.33 | 309.33 |
May | 437.50 | 0.63 | 0.62 | 01-MAY-05:10 | 3405.57 | 19.61 | 110.17 | 410.67 | 1515.13 | 21.87 | 81.83 | 374.00 |
June | 401.83 | 0.63 | 0.62 | 01-JUN-04:49 | 4247.73 | 21.43 | 119.83 | 409.67 | 1923.11 | 22.30 | 69.83 | 372.17 |
July | 409.17 | 0.63 | 0.62 | 01-JUL-04:49 | 3922.82 | 20.38 | 102.50 | 415.50 | 1822.62 | 22.56 | 73.00 | 383.00 |
August | 352.83 | 0.63 | 0.62 | 01-AUG-07:40 | 3334.66 | 20.39 | 86.67 | 372.50 | 1468.97 | 22.23 | 72.17 | 331.67 |
September | 344.17 | 0.63 | 0.62 | 01-SEP-05:00 | 2545.83 | 18.96 | 75.83 | 321.33 | 1391.17 | 22.01 | 78.17 | 281.50 |
October | 299.00 | 0.63 | 0.62 | 01-OCT-06:40 | 1960.53 | 20.07 | 95.17 | 276.00 | 827.04 | 20.62 | 54.00 | 229.17 |
November | 255.50 | 0.64 | 0.62 | 01-NOV-07:00 | 1265.23 | 18.76 | 73.17 | 216.17 | 682.63 | 20.64 | 58.17 | 167.83 |
December | 226.33 | 0.64 | 0.62 | 01-DEC-08:30 | 1059.84 | 17.61 | 46.17 | 194.33 | 773.36 | 22.75 | 77.17 | 154.50 |
Annual Sum or Average | 3785.50 | 0.63 | 2894.39 | 20.08 | 1024.33 | 3722.33 | 1446.85 | 22.15 | 886.00 | 3248.67 | ||
Minimum of Months | 226.33 | 0.63 | 0.62 | 1059.84 | 17.61 | 46.17 | 194.33 | 682.63 | 20.62 | 54.00 | 154.50 | |
Maximum of Months | 437.50 | 0.64 | 0.62 | 4247.73 | 21.95 | 119.83 | 415.50 | 2202.93 | 23.53 | 88.33 | 383.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.65 | 0.62 | 01-JAN-09:30 | 560.92 | 10.84 | 0.00 | 191.17 | 326.94 | 14.98 | 0.00 | 103.33 |
February | 265.33 | 0.64 | 0.62 | 01-FEB-08:39 | 708.46 | 12.39 | 0.00 | 226.50 | 428.13 | 16.46 | 0.00 | 173.67 |
March | 254.17 | 0.64 | 0.62 | 02-MAR-10:39 | 765.38 | 13.42 | 0.00 | 298.33 | 495.06 | 17.48 | 0.00 | 225.83 |
April | 296.33 | 0.64 | 0.62 | 01-APR-07:40 | 874.39 | 14.03 | 0.00 | 348.17 | 560.10 | 18.00 | 0.17 | 296.33 |
May | 437.50 | 0.62 | 0.62 | 01-MAY-05:19 | 1204.16 | 16.35 | 30.00 | 426.67 | 695.58 | 20.08 | 38.83 | 398.33 |
June | 401.83 | 0.62 | 0.62 | 01-JUN-04:49 | 1413.17 | 17.43 | 43.83 | 430.50 | 831.70 | 22.54 | 115.83 | 399.33 |
July | 409.17 | 0.62 | 0.62 | 01-JUL-04:49 | 1357.30 | 17.29 | 38.33 | 432.50 | 812.89 | 22.13 | 110.00 | 407.83 |
August | 352.83 | 0.63 | 0.62 | 01-AUG-07:40 | 1128.46 | 15.13 | 0.00 | 379.33 | 681.15 | 19.06 | 17.00 | 334.17 |
September | 344.17 | 0.63 | 0.62 | 01-SEP-06:10 | 862.59 | 13.73 | 0.00 | 318.83 | 510.92 | 17.62 | 0.00 | 262.00 |
October | 299.00 | 0.64 | 0.62 | 01-OCT-06:00 | 709.97 | 12.17 | 0.00 | 262.83 | 400.06 | 16.11 | 0.00 | 184.00 |
November | 255.50 | 0.65 | 0.62 | 01-NOV-08:09 | 548.12 | 10.53 | 0.00 | 196.33 | 307.02 | 14.50 | 0.00 | 93.67 |
December | 226.33 | 0.65 | 0.62 | 01-DEC-08:00 | 522.18 | 10.40 | 0.00 | 175.50 | 293.39 | 14.48 | 0.00 | 55.67 |
Annual Sum or Average | 3785.50 | 0.63 | 949.33 | 14.13 | 112.17 | 3686.67 | 564.45 | 18.30 | 281.83 | 2934.17 | ||
Minimum of Months | 226.33 | 0.62 | 0.62 | 522.18 | 10.40 | 0.00 | 175.50 | 293.39 | 14.48 | 0.00 | 55.67 | |
Maximum of Months | 437.50 | 0.65 | 0.62 | 1413.17 | 17.43 | 43.83 | 432.50 | 831.70 | 22.54 | 115.83 | 407.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.64 | 0.62 | 01-JAN-09:30 | 1485.58 | 20.06 | 75.50 | 214.17 | 812.35 | 21.47 | 66.50 | 175.00 |
February | 265.33 | 0.63 | 0.62 | 01-FEB-08:50 | 2065.84 | 20.58 | 75.00 | 241.67 | 1079.92 | 22.04 | 88.33 | 210.50 |
March | 254.17 | 0.63 | 0.62 | 02-MAR-10:39 | 3053.12 | 19.86 | 59.67 | 307.00 | 1914.03 | 23.50 | 78.67 | 261.00 |
April | 296.33 | 0.64 | 0.62 | 01-APR-07:49 | 3855.87 | 20.46 | 84.50 | 344.17 | 1681.25 | 20.72 | 45.33 | 306.50 |
May | 437.50 | 0.63 | 0.62 | 01-MAY-06:10 | 3161.25 | 18.23 | 80.50 | 411.17 | 1789.11 | 20.63 | 54.67 | 376.83 |
June | 401.83 | 0.63 | 0.62 | 01-JUN-05:10 | 3362.91 | 17.04 | 46.50 | 421.17 | 1464.93 | 18.95 | 0.83 | 381.83 |
July | 409.17 | 0.63 | 0.62 | 01-JUL-05:10 | 3628.48 | 17.52 | 53.67 | 422.83 | 1596.39 | 19.19 | 3.50 | 383.83 |
August | 352.83 | 0.63 | 0.62 | 01-AUG-07:40 | 3162.98 | 19.74 | 79.17 | 375.33 | 1837.36 | 21.69 | 62.17 | 331.67 |
September | 344.17 | 0.63 | 0.62 | 01-SEP-06:40 | 2813.57 | 20.62 | 99.00 | 323.67 | 1576.61 | 22.42 | 83.83 | 286.00 |
October | 299.00 | 0.63 | 0.62 | 01-OCT-07:10 | 2121.24 | 20.69 | 99.33 | 277.50 | 868.12 | 20.90 | 58.83 | 232.33 |
November | 255.50 | 0.64 | 0.62 | 01-NOV-08:09 | 1240.40 | 18.67 | 71.33 | 217.67 | 649.05 | 20.41 | 59.83 | 171.83 |
December | 226.33 | 0.64 | 0.62 | 01-DEC-08:00 | 1064.86 | 17.43 | 44.33 | 200.50 | 608.17 | 20.80 | 55.17 | 151.67 |
Annual Sum or Average | 3785.50 | 0.63 | 2727.20 | 19.13 | 868.50 | 3756.83 | 1386.19 | 20.93 | 657.67 | 3269.00 | ||
Minimum of Months | 226.33 | 0.63 | 0.62 | 1064.86 | 17.04 | 44.33 | 200.50 | 608.17 | 18.95 | 0.83 | 151.67 | |
Maximum of Months | 437.50 | 0.64 | 0.62 | 3855.87 | 20.69 | 99.33 | 422.83 | 1914.03 | 23.50 | 88.33 | 383.83 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.159925E+10 | 25367.25 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 78097276.17 | 25367.25 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18335065.21 | 25367.25 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28143343.33 | 25367.25 | 27-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.557894E+09 | 25367.25 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.159925E+10 | 25367.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.154098E+11 | 13392.23 | 19-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101296E+11 | 13383.91 | 21-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.954965E+10 | 13347.84 | 22-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.402378E+10 | 13385.63 | 24-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131188E+10 | 13690.77 | 17-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.373217E+09 | 13661.26 | 16-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 98077234.58 | 13745.15 | 18-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.277251E+09 | 13651.27 | 25-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133748E+10 | 14615.22 | 06-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.367264E+10 | 13389.93 | 20-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.703286E+10 | 13394.63 | 21-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140231E+11 | 13393.15 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.672394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 98077234.58 | 13347.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.154098E+11 | 14615.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.612332E+10 | 10275.04 | 31-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.340785E+10 | 10272.77 | 06-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231300E+10 | 10264.41 | 07-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.395176E+09 | 10218.33 | 10-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176057.44 | 941.19 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.204217E+09 | 10223.72 | 11-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168337E+10 | 10212.46 | 15-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.515499E+10 | 10269.20 | 18-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.612332E+10 | 10275.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.974082E+10 | 7999.32 | 19-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.612482E+10 | 7994.51 | 22-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.465887E+10 | 7968.40 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106922E+10 | 7961.63 | 26-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27141336.57 | 7929.42 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.281137E+09 | 7955.49 | 12-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.256123E+10 | 7986.61 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.798231E+10 | 7997.81 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.324456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.974082E+10 | 7999.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.634220E+10 | 11173.99 | 12-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.362145E+10 | 11188.29 | 06-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.257141E+10 | 11188.53 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.571651E+09 | 11128.98 | 10-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16976761.33 | 11103.32 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.257429E+09 | 11134.71 | 11-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181902E+10 | 11122.39 | 15-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.535804E+10 | 11175.56 | 14-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.634220E+10 | 11188.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.667471E+10 | 29436.03 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.305103E+10 | 29436.03 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129091E+10 | 29436.03 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109352E+09 | 29436.03 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 73790451.24 | 29436.03 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171159E+10 | 29436.03 | 06-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.545084E+10 | 29436.03 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.667471E+10 | 29436.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.628658E+10 | 15283.36 | 17-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.327879E+10 | 15316.51 | 07-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.219812E+10 | 15265.87 | 08-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.456196E+09 | 15225.65 | 10-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11801002.22 | 15093.98 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 284757.66 | 205.16 | 23-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.428644E+09 | 15176.76 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222811E+10 | 15271.26 | 06-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.613232E+10 | 15339.86 | 28-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.628658E+10 | 15339.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.611006E+10 | 12083.53 | 01-JAN-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.341538E+10 | 12083.53 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209092E+10 | 12083.53 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.366464E+09 | 12083.53 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 239898.96 | 1610.25 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4244697.55 | 2397.70 | 23-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.500712E+09 | 12083.53 | 04-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223161E+10 | 12083.53 | 03-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.568984E+10 | 12083.53 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.611006E+10 | 12083.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.939151E+10 | 8833.16 | 17-JAN-05:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.556252E+10 | 8833.17 | 09-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.332817E+10 | 8846.78 | 22-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.570974E+09 | 8810.57 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7525312.15 | 8764.61 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.483902E+09 | 8815.38 | 16-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.292242E+10 | 8864.22 | 15-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.839547E+10 | 8831.78 | 06-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.306625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.939151E+10 | 8864.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.620847E+10 | 12182.05 | 01-JAN-00:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.359764E+10 | 12182.05 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227811E+10 | 12182.05 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.502291E+09 | 12182.05 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13183990.81 | 12182.05 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7705233.61 | 2111.34 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.532457E+09 | 12182.05 | 04-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.228184E+10 | 12182.05 | 03-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.576459E+10 | 12182.05 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.620847E+10 | 12182.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137723E+11 | 32102.13 | 20-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.833062E+10 | 32132.48 | 22-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.503821E+10 | 32213.26 | 21-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103109E+10 | 32200.40 | 17-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24318526.19 | 32138.23 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114646E+10 | 32288.42 | 11-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.551049E+10 | 32214.44 | 15-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123809E+11 | 32193.72 | 23-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.472345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137723E+11 | 32288.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.998998E+10 | 16539.47 | 19-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.598726E+10 | 16543.16 | 03-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.424596E+10 | 16524.56 | 06-MAR-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129696E+10 | 16544.18 | 10-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74327245.43 | 16321.84 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4212125.08 | 6926.70 | 19-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74797513.17 | 10672.81 | 23-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134129E+10 | 16561.15 | 30-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.433062E+10 | 16548.98 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.991818E+10 | 16562.61 | 06-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.372636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.998998E+10 | 16562.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.870781E+10 | 12527.16 | 18-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.537479E+10 | 12516.03 | 15-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.344434E+10 | 12522.70 | 11-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.836665E+09 | 12496.17 | 28-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17577274.06 | 12389.43 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 165774.82 | 1105.17 | 19-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 68353028.69 | 6852.58 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118813E+10 | 12504.98 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.370739E+10 | 12561.79 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.828264E+10 | 12512.53 | 14-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.316279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.870781E+10 | 12561.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136984E+11 | 10726.43 | 18-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.903448E+10 | 10713.74 | 21-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.601350E+10 | 10725.35 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156829E+10 | 10704.32 | 17-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 55661410.74 | 10696.14 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1433561.83 | 3775.35 | 19-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 66855178.01 | 10634.81 | 23-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155068E+10 | 10742.94 | 11-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.554305E+10 | 10732.15 | 15-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127292E+11 | 10715.03 | 23-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.502615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136984E+11 | 10742.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.899141E+10 | 13902.89 | 18-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.576101E+10 | 13880.92 | 17-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.389737E+10 | 13878.78 | 07-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119528E+10 | 13859.49 | 10-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74436508.35 | 13749.75 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7308807.36 | 6274.29 | 19-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116203E+09 | 6819.29 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134901E+10 | 13865.25 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.395446E+10 | 13883.47 | 25-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.854927E+10 | 13868.79 | 18-DEC-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.338958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.899141E+10 | 13902.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114070E+11 | 49541.95 | 06-JAN-07:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.349052E+10 | 46645.17 | 14-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.272707E+09 | 34554.04 | 15-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43169144.97 | 2940.41 | 27-APR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9778122.04 | 2166.57 | 06-MAY-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 212856.89 | 801.23 | 19-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 711089.53 | 2700.79 | 06-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 55927316.54 | 6180.98 | 05-OCT-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 91566393.83 | 6676.76 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.596535E+10 | 43228.83 | 20-DEC-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114070E+11 | 49541.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117377E+11 | 47845.67 | 06-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.391143E+10 | 45359.02 | 14-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.437212E+09 | 32599.85 | 15-MAR-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21364664.03 | 6680.89 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4042862.84 | 2107.49 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2615453.19 | 1169.14 | 06-SEP-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10750095.10 | 4390.96 | 16-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200270E+09 | 7161.75 | 15-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.654945E+10 | 41947.22 | 20-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117377E+11 | 47845.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.164930E+11 | 52502.70 | 06-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.672799E+10 | 49394.29 | 14-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161702E+10 | 36239.31 | 15-MAR-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 85214576.66 | 5357.89 | 05-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1466034.73 | 2711.44 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1253165.91 | 1306.88 | 28-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 52749126.35 | 5315.47 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103945E+10 | 7669.10 | 25-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110166E+11 | 45299.32 | 20-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.164930E+11 | 52502.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4766617.73 | 4670502.65 | 6714.92 | 19-JAN-07:01 | 6714.92 | 0.00 |
February | 0.00 | 0.00 | 11177062.45 | 11035159.23 | 6689.68 | 22-FEB-07:01 | 6689.68 | 0.00 |
March | 0.00 | 0.00 | 29222678.96 | 28257391.59 | 4341.85 | 30-MAR-07:06 | 4341.85 | 0.00 |
April | 0.00 | 0.00 | 0.124204E+10 | 0.120330E+10 | 30932.82 | 23-APR-17:51 | 30932.82 | 0.00 |
May | 0.00 | 0.00 | 0.171446E+11 | 0.160795E+11 | 69134.14 | 25-MAY-16:10 | 51636.33 | 0.00 |
June | 0.00 | 0.00 | 0.402853E+11 | 0.313547E+11 | 116320.83 | 30-JUN-04:03 | 64280.76 | 0.00 |
July | 0.00 | 0.00 | 0.552453E+11 | 0.412860E+11 | 121984.70 | 05-JUL-10:30 | 43749.13 | 0.00 |
August | 0.00 | 0.00 | 0.433418E+11 | 0.310462E+11 | 100512.30 | 31-AUG-12:50 | 45589.99 | 0.00 |
September | 0.00 | 0.00 | 0.931900E+10 | 0.777685E+10 | 68837.41 | 01-SEP-13:20 | 53078.98 | 0.00 |
October | 0.00 | 0.00 | 0.119175E+10 | 0.113128E+10 | 28823.04 | 19-OCT-15:10 | 28823.04 | 0.00 |
November | 0.00 | 0.00 | 0.200191E+09 | 0.146404E+09 | 9777.79 | 01-NOV-15:10 | 7056.74 | 0.00 |
December | 0.00 | 0.00 | 7263309.94 | 7098515.18 | 6301.58 | 28-DEC-07:01 | 6301.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.168022E+12 | 0.130075E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4766617.73 | 4670502.65 | 4341.85 | 4341.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.552453E+11 | 0.412860E+11 | 121984.70 | 64280.76 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1765891.75 | 1764134.72 | 5306.64 | 19-JAN-07:01 | 5306.64 | 0.00 |
February | 0.00 | 0.00 | 7585909.42 | 7582192.76 | 6908.99 | 09-FEB-07:01 | 6908.99 | 0.00 |
March | 0.00 | 0.00 | 13194886.31 | 13125636.74 | 7254.30 | 22-MAR-06:01 | 7254.30 | 0.00 |
April | 0.00 | 0.00 | 0.135866E+10 | 0.133107E+10 | 36880.22 | 23-APR-16:02 | 36880.22 | 0.00 |
May | 0.00 | 0.00 | 0.168068E+11 | 0.157701E+11 | 62492.28 | 25-MAY-16:00 | 54741.42 | 0.00 |
June | 0.00 | 0.00 | 0.380906E+11 | 0.300044E+11 | 108041.56 | 30-JUN-04:03 | 60454.68 | 0.00 |
July | 0.00 | 0.00 | 0.507285E+11 | 0.379226E+11 | 112052.85 | 05-JUL-10:30 | 40104.78 | 0.00 |
August | 0.00 | 0.00 | 0.378422E+11 | 0.273515E+11 | 88629.36 | 31-AUG-12:50 | 40212.27 | 0.00 |
September | 0.00 | 0.00 | 0.837530E+10 | 0.696203E+10 | 66071.81 | 01-SEP-13:20 | 49593.87 | 0.00 |
October | 0.00 | 0.00 | 0.113406E+10 | 0.107891E+10 | 24702.94 | 19-OCT-15:00 | 24702.94 | 0.00 |
November | 0.00 | 0.00 | 0.161390E+09 | 0.113383E+09 | 8318.07 | 01-NOV-15:00 | 5756.44 | 0.00 |
December | 0.00 | 0.00 | 4546225.00 | 4535543.06 | 5827.17 | 06-DEC-07:01 | 5827.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.154525E+12 | 0.120561E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1765891.75 | 1764134.72 | 5306.64 | 5306.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.507285E+11 | 0.379226E+11 | 112052.85 | 60454.68 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 506289.58 | 506289.58 | 1892.11 | 19-JAN-07:01 | 1892.11 | 0.00 |
February | 0.00 | 0.00 | 7661415.45 | 7586053.34 | 2066.43 | 09-FEB-07:01 | 2066.43 | 0.00 |
March | 0.00 | 0.00 | 17021724.78 | 16641120.35 | 5453.42 | 30-MAR-06:01 | 5453.42 | 0.00 |
April | 0.00 | 0.00 | 0.143053E+10 | 0.137795E+10 | 46262.72 | 23-APR-16:22 | 46262.72 | 0.00 |
May | 0.00 | 0.00 | 0.177161E+11 | 0.166338E+11 | 70399.43 | 25-MAY-16:00 | 63099.92 | 0.00 |
June | 0.00 | 0.00 | 0.396667E+11 | 0.313735E+11 | 119644.99 | 30-JUN-04:03 | 61870.82 | 0.00 |
July | 0.00 | 0.00 | 0.527514E+11 | 0.396554E+11 | 123325.96 | 05-JUL-10:40 | 43681.68 | 0.00 |
August | 0.00 | 0.00 | 0.386107E+11 | 0.278113E+11 | 102242.54 | 29-AUG-15:20 | 61849.42 | 0.00 |
September | 0.00 | 0.00 | 0.803836E+10 | 0.661918E+10 | 73617.47 | 01-SEP-14:00 | 59197.26 | 0.00 |
October | 0.00 | 0.00 | 0.108656E+10 | 0.102330E+10 | 24110.18 | 19-OCT-15:00 | 24110.18 | 0.00 |
November | 0.00 | 0.00 | 0.171298E+09 | 0.118785E+09 | 8828.19 | 01-NOV-15:00 | 6032.64 | 0.00 |
December | 0.00 | 0.00 | 899206.62 | 893564.06 | 3342.07 | 06-DEC-07:01 | 3342.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.159498E+12 | 0.124639E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 506289.58 | 506289.58 | 1892.11 | 1892.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.527514E+11 | 0.396554E+11 | 123325.96 | 63099.92 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 2166.92 | 7679.29 | 31-JAN-12:06 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 2226.04 | 7756.38 | 23-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2364.35 | 7753.11 | 03-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2144.31 | 7603.13 | 03-APR-11:09 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 2118.70 | 7287.30 | 01-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 2051.64 | 6887.69 | 02-JUN-11:09 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1789.42 | 6456.11 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1915.97 | 6230.29 | 03-AUG-11:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1798.04 | 6276.31 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1861.21 | 6625.93 | 31-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1992.09 | 7021.09 | 30-NOV-12:07 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2018.97 | 7393.71 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 2036.20 | ||||
Minimum of Months | 0.00 | 0.00 | 1789.42 | 6230.29 | ||
Maximum of Months | 0.00 | 0.00 | 2364.35 | 7756.38 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.208277E+10 | 0.40 | 2874.19 | 02-JAN-05:01 | 0.83 |
February | 0.153561E+10 | 0.34 | 2874.19 | 06-FEB-07:01 | 0.83 |
March | 0.169416E+10 | 0.34 | 2874.19 | 06-MAR-07:01 | 0.83 |
April | 0.185790E+10 | 0.33 | 4489.07 | 21-APR-05:02 | 1.07 |
May | 0.347030E+10 | 0.42 | 8558.04 | 18-MAY-15:10 | 1.57 |
June | 0.477403E+10 | 0.51 | 10997.69 | 30-JUN-12:08 | 1.83 |
July | 0.604285E+10 | 0.56 | 12042.13 | 05-JUL-10:20 | 1.94 |
August | 0.521916E+10 | 0.54 | 9356.51 | 25-AUG-16:00 | 1.66 |
September | 0.328898E+10 | 0.42 | 8580.36 | 05-SEP-15:30 | 1.58 |
October | 0.196833E+10 | 0.32 | 4489.07 | 02-OCT-05:02 | 1.06 |
November | 0.144724E+10 | 0.30 | 2874.19 | 27-NOV-07:01 | 0.83 |
December | 0.191132E+10 | 0.37 | 2874.19 | 04-DEC-07:01 | 0.83 |
Annual Sum or Average | 0.352926E+11 | 0.40 | |||
Minimum of Months | 0.144724E+10 | 0.30 | 2874.19 | 0.83 | |
Maximum of Months | 0.604285E+10 | 0.56 | 12042.13 | 1.94 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.209701E+10 | 0.42 | 2927.74 | 02-JAN-05:01 | 0.90 |
February | 0.163456E+10 | 0.37 | 2927.74 | 01-FEB-06:01 | 0.90 |
March | 0.169799E+10 | 0.35 | 2927.74 | 01-MAR-07:01 | 0.90 |
April | 0.180904E+10 | 0.33 | 3683.55 | 13-APR-15:20 | 1.02 |
May | 0.340419E+10 | 0.44 | 9388.26 | 18-MAY-15:00 | 1.79 |
June | 0.474811E+10 | 0.54 | 9761.13 | 30-JUN-10:50 | 1.83 |
July | 0.560393E+10 | 0.57 | 10828.87 | 05-JUL-10:20 | 1.95 |
August | 0.442052E+10 | 0.51 | 10193.30 | 08-AUG-15:20 | 1.88 |
September | 0.254164E+10 | 0.39 | 9322.60 | 01-SEP-15:50 | 1.78 |
October | 0.162592E+10 | 0.32 | 3691.60 | 20-OCT-14:50 | 1.02 |
November | 0.149993E+10 | 0.32 | 2927.74 | 06-NOV-06:01 | 0.90 |
December | 0.199806E+10 | 0.41 | 2927.74 | 01-DEC-07:01 | 0.90 |
Annual Sum or Average | 0.330809E+11 | 0.41 | |||
Minimum of Months | 0.149993E+10 | 0.32 | 2927.74 | 0.90 | |
Maximum of Months | 0.560393E+10 | 0.57 | 10828.87 | 1.95 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.259902E+10 | 0.48 | 2902.69 | 01-JAN-01:22 | 0.83 |
February | 0.208681E+10 | 0.44 | 2902.69 | 01-FEB-05:01 | 0.83 |
March | 0.195011E+10 | 0.38 | 2902.69 | 01-MAR-06:01 | 0.83 |
April | 0.177664E+10 | 0.33 | 3386.47 | 13-APR-15:30 | 0.91 |
May | 0.307146E+10 | 0.40 | 9496.51 | 18-MAY-14:30 | 1.66 |
June | 0.438480E+10 | 0.48 | 12146.19 | 30-JUN-14:50 | 1.94 |
July | 0.504291E+10 | 0.50 | 12146.19 | 05-JUL-10:40 | 1.94 |
August | 0.386370E+10 | 0.45 | 10268.25 | 08-AUG-15:10 | 1.75 |
September | 0.220006E+10 | 0.35 | 9484.10 | 01-SEP-15:50 | 1.66 |
October | 0.162118E+10 | 0.31 | 2935.83 | 20-OCT-14:30 | 0.83 |
November | 0.185036E+10 | 0.37 | 2902.69 | 03-NOV-06:01 | 0.83 |
December | 0.247286E+10 | 0.46 | 2902.69 | 01-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.329199E+11 | 0.41 | |||
Minimum of Months | 0.162118E+10 | 0.31 | 2902.69 | 0.83 | |
Maximum of Months | 0.504291E+10 | 0.50 | 12146.19 | 1.94 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:01 | 0.22 | 0.22 | 56.95 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:01 | 0.22 | 0.22 | 56.06 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:01 | 0.22 | 0.22 | 55.28 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:02 | 0.22 | 0.22 | 54.79 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:01 | 0.22 | 0.22 | 55.46 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 56.17 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 56.50 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 55.97 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 55.50 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 57.46 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:02 | 0.22 | 0.22 | 56.37 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:01 | 0.22 | 0.22 | 56.54 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 54.79 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.46 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 56.87 | 56.87 | 2166.92 | 7679.29 | 31-JAN-12:06 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 56.61 | 56.61 | 2226.04 | 7756.38 | 23-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 55.99 | 55.99 | 2364.35 | 7753.11 | 03-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 55.39 | 55.39 | 2144.31 | 7603.13 | 03-APR-11:09 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.14 | 56.14 | 2118.70 | 7287.30 | 01-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.70 | 56.70 | 2051.64 | 6887.69 | 02-JUN-11:09 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.02 | 57.02 | 1789.42 | 6456.11 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.30 | 57.30 | 1915.97 | 6230.29 | 03-AUG-11:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 55.94 | 55.94 | 1798.04 | 6276.31 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.16 | 55.16 | 1861.21 | 6625.93 | 31-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.85 | 56.85 | 1992.09 | 7021.09 | 30-NOV-12:07 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.91 | 56.91 | 2018.97 | 7393.71 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 2036.20 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.16 | 55.16 | 1789.42 | 6230.29 | ||
Maximum of Months | 0.00 | 0.00 | 57.30 | 57.30 | 2364.35 | 7756.38 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.412996E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.249008E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.208140E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.825753E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.909924E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.151115E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.195011E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.159948E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.697036E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.669874E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.146280E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.349898E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.218265E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.669874E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.412996E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.367689E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.205421E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.128880E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.418127E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.761101E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.141369E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.178660E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.136080E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.466551E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.394510E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.129208E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.334324E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.182566E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.394510E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.367689E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.577591E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.365772E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.245945E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.809114E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.773874E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.142187E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.178579E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.133080E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.457503E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.848783E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.249445E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.543333E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.272486E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.457503E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.577591E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.208277E+10 | 4766617.73 | 0.506225E+11 | 0.248185E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153561E+10 | 11177062.45 | 0.268524E+11 | 0.210231E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169416E+10 | 29222678.96 | 0.193840E+11 | 0.185022E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185790E+10 | 0.124204E+10 | 0.610299E+10 | 0.410763E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.347030E+10 | 0.171446E+11 | 0.136596E+10 | 0.265805E+09 | 77381075.37 | 0.00 | 0.00 | 0.00 |
June | 0.477403E+10 | 0.402853E+11 | 0.373217E+09 | 15122192.68 | 0.156874E+10 | 0.00 | 0.00 | 0.00 |
July | 0.604285E+10 | 0.552453E+11 | 98077234.58 | 30574028.35 | 0.181218E+10 | 0.00 | 0.00 | 0.00 |
August | 0.521916E+10 | 0.433418E+11 | 0.277464E+09 | 3069288.75 | 0.893029E+09 | 0.00 | 0.00 | 0.00 |
September | 0.328898E+10 | 0.931900E+10 | 0.133819E+10 | 19193949.96 | 12584015.55 | 0.00 | 0.00 | 0.00 |
October | 0.196833E+10 | 0.119175E+10 | 0.447135E+10 | 0.251588E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144724E+10 | 0.200191E+09 | 0.132162E+11 | 0.115747E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191132E+10 | 7263309.94 | 0.390417E+11 | 0.251936E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.352926E+11 | 0.168022E+12 | 0.163144E+12 | 0.108069E+12 | 0.436391E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144724E+10 | 4766617.73 | 98077234.58 | 3069288.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.604285E+10 | 0.552453E+11 | 0.506225E+11 | 0.251936E+11 | 0.181218E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.209701E+10 | 1765891.75 | 0.464090E+11 | 0.248247E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163456E+10 | 7585909.42 | 0.228168E+11 | 0.215251E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169799E+10 | 13194886.31 | 0.116234E+11 | 0.200823E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180904E+10 | 0.135866E+10 | 0.202664E+10 | 0.546868E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.340419E+10 | 0.168068E+11 | 36793066.98 | 0.411259E+09 | 82359585.60 | 0.00 | 0.00 | 0.00 |
June | 0.474811E+10 | 0.380906E+11 | 0.00 | 16893292.40 | 0.167893E+10 | 0.00 | 0.00 | 0.00 |
July | 0.560393E+10 | 0.507285E+11 | 0.00 | 35308597.09 | 0.203059E+10 | 0.00 | 0.00 | 0.00 |
August | 0.442052E+10 | 0.378422E+11 | 0.00 | 3752845.79 | 0.973974E+09 | 0.00 | 0.00 | 0.00 |
September | 0.254164E+10 | 0.837530E+10 | 14850142.01 | 0.133182E+09 | 14260690.88 | 0.00 | 0.00 | 0.00 |
October | 0.162592E+10 | 0.113406E+10 | 0.203026E+10 | 0.439677E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149993E+10 | 0.161390E+09 | 0.115758E+11 | 0.133304E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199806E+10 | 4546225.00 | 0.379825E+11 | 0.254652E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.330809E+11 | 0.154525E+12 | 0.134516E+12 | 0.115694E+12 | 0.478011E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149993E+10 | 1765891.75 | 0.00 | 3752845.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.560393E+10 | 0.507285E+11 | 0.464090E+11 | 0.254652E+11 | 0.203059E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.259902E+10 | 506289.58 | 0.716529E+11 | 0.245102E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.208681E+10 | 7661415.45 | 0.412161E+11 | 0.210010E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195011E+10 | 17021724.78 | 0.242564E+11 | 0.201191E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177664E+10 | 0.143053E+10 | 0.601350E+10 | 0.594321E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.307146E+10 | 0.177161E+11 | 0.247787E+09 | 0.533177E+09 | 53359512.02 | 0.00 | 0.00 | 0.00 |
June | 0.438480E+10 | 0.396667E+11 | 0.00 | 10650833.76 | 0.148432E+10 | 0.00 | 0.00 | 0.00 |
July | 0.504291E+10 | 0.527514E+11 | 0.00 | 30036236.02 | 0.168312E+10 | 0.00 | 0.00 | 0.00 |
August | 0.386370E+10 | 0.386107E+11 | 13120269.09 | 15122143.14 | 0.702420E+09 | 0.00 | 0.00 | 0.00 |
September | 0.220006E+10 | 0.803836E+10 | 0.327461E+09 | 0.333310E+09 | 2624240.53 | 0.00 | 0.00 | 0.00 |
October | 0.162118E+10 | 0.108656E+10 | 0.662833E+10 | 0.501757E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185036E+10 | 0.171298E+09 | 0.240854E+11 | 0.136661E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.247286E+10 | 899206.62 | 0.628768E+11 | 0.252091E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.329199E+11 | 0.159498E+12 | 0.237318E+12 | 0.116388E+12 | 0.392585E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.162118E+10 | 506289.58 | 0.00 | 10650833.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.504291E+10 | 0.527514E+11 | 0.716529E+11 | 0.252091E+11 | 0.168312E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.208277E+10 | 0.00 | 0.00 | 0.00 | 1386209.95 | 0.392154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153561E+10 | 0.00 | 0.00 | 0.00 | 3283037.05 | 0.233619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169416E+10 | 0.00 | 0.00 | 0.00 | 8591820.99 | 0.191113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185790E+10 | 0.00 | 0.00 | 0.00 | 0.339804E+09 | 0.605982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.347030E+10 | 0.00 | 0.00 | 0.00 | 0.427276E+10 | 0.135618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.477403E+10 | 0.00 | 0.00 | 0.00 | 0.996422E+10 | 0.373217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.604285E+10 | 0.00 | 0.00 | 0.00 | 0.133601E+11 | 98077234.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.521916E+10 | 0.00 | 0.00 | 0.00 | 0.104984E+11 | 0.277251E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.328898E+10 | 0.00 | 0.00 | 0.00 | 0.234390E+10 | 0.133748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.196833E+10 | 0.00 | 0.00 | 0.00 | 0.314980E+09 | 0.441542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144724E+10 | 0.00 | 0.00 | 0.00 | 56178245.75 | 0.131246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191132E+10 | 0.00 | 0.00 | 0.00 | 2124450.75 | 0.330764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.352926E+11 | 0.00 | 0.00 | 0.00 | 0.411657E+11 | 0.141807E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144724E+10 | 0.00 | 0.00 | 0.00 | 1386209.95 | 98077234.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.604285E+10 | 0.00 | 0.00 | 0.00 | 0.133601E+11 | 0.392154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.209701E+10 | 0.00 | 0.00 | 0.00 | 509946.66 | 0.346713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163456E+10 | 0.00 | 0.00 | 0.00 | 2199543.18 | 0.189054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169799E+10 | 0.00 | 0.00 | 0.00 | 3814461.49 | 0.111862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180904E+10 | 0.00 | 0.00 | 0.00 | 0.366951E+09 | 0.200528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.340419E+10 | 0.00 | 0.00 | 0.00 | 0.417407E+10 | 32750204.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.474811E+10 | 0.00 | 0.00 | 0.00 | 0.938876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.560393E+10 | 0.00 | 0.00 | 0.00 | 0.122621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.442052E+10 | 0.00 | 0.00 | 0.00 | 0.918753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.254164E+10 | 0.00 | 0.00 | 0.00 | 0.211164E+10 | 12234688.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162592E+10 | 0.00 | 0.00 | 0.00 | 0.299667E+09 | 0.201951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149993E+10 | 0.00 | 0.00 | 0.00 | 45265437.40 | 0.113756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199806E+10 | 0.00 | 0.00 | 0.00 | 1308042.69 | 0.314331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.330809E+11 | 0.00 | 0.00 | 0.00 | 0.378438E+11 | 0.111641E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149993E+10 | 0.00 | 0.00 | 0.00 | 509946.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.560393E+10 | 0.00 | 0.00 | 0.00 | 0.122621E+11 | 0.346713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.259902E+10 | 0.00 | 0.00 | 0.00 | 148829.82 | 0.551599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.208681E+10 | 0.00 | 0.00 | 0.00 | 2261346.45 | 0.344882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195011E+10 | 0.00 | 0.00 | 0.00 | 5007431.05 | 0.226394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177664E+10 | 0.00 | 0.00 | 0.00 | 0.386216E+09 | 0.592829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.307146E+10 | 0.00 | 0.00 | 0.00 | 0.442096E+10 | 0.246321E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.438480E+10 | 0.00 | 0.00 | 0.00 | 0.983388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.504291E+10 | 0.00 | 0.00 | 0.00 | 0.128150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.386370E+10 | 0.00 | 0.00 | 0.00 | 0.943122E+10 | 13120269.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.220006E+10 | 0.00 | 0.00 | 0.00 | 0.204876E+10 | 0.326208E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162118E+10 | 0.00 | 0.00 | 0.00 | 0.291073E+09 | 0.657558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185036E+10 | 0.00 | 0.00 | 0.00 | 48184309.61 | 0.230460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.247286E+10 | 0.00 | 0.00 | 0.00 | 262009.65 | 0.518602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.329199E+11 | 0.00 | 0.00 | 0.00 | 0.392830E+11 | 0.200283E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.162118E+10 | 0.00 | 0.00 | 0.00 | 148829.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.504291E+10 | 0.00 | 0.00 | 0.00 | 0.128150E+11 | 0.551599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117841E+11 | 0.00 | 0.00 | 38195.56 | 0.00 | 0.556075E+09 | 0.101416E+09 | 0.00 | 0.26 |
February | 0.826977E+10 | 0.00 | 0.00 | 1613391.60 | 0.00 | 13161969.03 | 0.102266E+10 | 0.00 | 0.27 |
March | 0.612957E+10 | 0.00 | 0.00 | 11528999.49 | 0.00 | 2040542.27 | 0.526661E+10 | 0.00 | 0.31 |
April | 0.267745E+10 | 0.00 | 0.00 | 28770284.05 | 43657794.00 | 0.00 | 0.129498E+11 | 0.00 | 0.47 |
May | 0.131407E+10 | 44780613.40 | 0.00 | 42035734.48 | 0.00 | 0.00 | 0.168238E+11 | 0.00 | 0.88 |
June | 0.905642E+09 | 0.180636E+10 | 0.00 | 35393247.97 | 0.222205E+09 | 0.00 | 0.115776E+11 | 0.00 | 1.12 |
July | 0.758630E+09 | 0.289399E+10 | 0.00 | 29585943.81 | 0.395335E+09 | 0.00 | 0.794452E+10 | 0.00 | 1.02 |
August | 0.100676E+10 | 0.159155E+10 | 0.00 | 39197059.04 | 54817952.15 | 0.00 | 0.123058E+11 | 0.00 | 1.21 |
September | 0.150752E+10 | 13752952.51 | 0.00 | 42116143.77 | 0.00 | 0.00 | 0.201231E+11 | 0.00 | 0.94 |
October | 0.272566E+10 | 0.00 | 0.00 | 30297503.92 | 0.00 | 0.00 | 0.142797E+11 | 0.00 | 0.48 |
November | 0.477451E+10 | 0.00 | 0.00 | 11827355.02 | 0.00 | 2325878.37 | 0.542140E+10 | 0.00 | 0.31 |
December | 0.973654E+10 | 0.00 | 0.00 | 461331.11 | 0.00 | 0.225877E+09 | 0.450460E+09 | 0.00 | 0.26 |
Annual Sum or Average | 0.515902E+11 | 0.635043E+10 | 0.00 | 0.272865E+09 | 0.716016E+09 | 0.799481E+09 | 0.108267E+12 | 0.00 | 0.63 |
Minimum of Months | 0.758630E+09 | 0.00 | 0.00 | 38195.56 | 0.00 | 0.00 | 0.101416E+09 | 0.00 | 0.26 |
Maximum of Months | 0.117841E+11 | 0.289399E+10 | 0.00 | 42116143.77 | 0.395335E+09 | 0.556075E+09 | 0.201231E+11 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.823972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421510E+10 | 0.00 | 0.00 | 0.26 |
February | 0.740287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144238E+10 | 0.00 | 0.00 | 0.27 |
March | 0.900145E+10 | 0.00 | 0.00 | 86575.29 | 0.00 | 0.331297E+09 | 0.223991E+09 | 0.00 | 0.29 |
April | 0.683739E+10 | 0.00 | 0.00 | 5755416.53 | 33864932.94 | 30553473.29 | 0.391273E+10 | 0.00 | 0.35 |
May | 0.311042E+10 | 38107379.05 | 0.00 | 21490418.50 | 0.00 | 0.00 | 0.920228E+10 | 0.00 | 0.60 |
June | 0.116335E+10 | 0.133074E+10 | 0.00 | 21497828.67 | 0.222623E+09 | 0.00 | 0.727370E+10 | 0.00 | 0.78 |
July | 0.103330E+10 | 0.220324E+10 | 0.00 | 18891953.33 | 0.353058E+09 | 0.00 | 0.494940E+10 | 0.00 | 0.73 |
August | 0.144886E+10 | 0.116558E+10 | 0.00 | 22793165.90 | 45529418.43 | 0.00 | 0.723404E+10 | 0.00 | 0.82 |
September | 0.349834E+10 | 25667223.57 | 0.00 | 17854906.99 | 487103.51 | 0.00 | 0.969711E+10 | 0.00 | 0.59 |
October | 0.730952E+10 | 0.00 | 0.00 | 4254250.50 | 0.00 | 12583654.62 | 0.330025E+10 | 0.00 | 0.33 |
November | 0.736261E+10 | 0.00 | 0.00 | 4860.70 | 0.00 | 0.608701E+09 | 35150896.84 | 0.00 | 0.28 |
December | 0.659966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346339E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.630075E+11 | 0.476333E+10 | 0.00 | 0.112629E+09 | 0.655562E+09 | 0.101040E+11 | 0.458286E+11 | 0.00 | 0.46 |
Minimum of Months | 0.103330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.900145E+10 | 0.220324E+10 | 0.00 | 22793165.90 | 0.353058E+09 | 0.421510E+10 | 0.969711E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.295020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784355E+10 | 0.00 | 0.00 | 0.24 |
February | 0.363777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412034E+10 | 0.00 | 0.00 | 0.25 |
March | 0.689958E+10 | 0.00 | 0.00 | 2429.16 | 0.00 | 0.150669E+10 | 35411366.41 | 0.00 | 0.28 |
April | 0.712800E+10 | 0.00 | 0.00 | 2868881.36 | 47668063.63 | 0.184438E+09 | 0.254598E+10 | 0.00 | 0.34 |
May | 0.408144E+10 | 33273692.78 | 0.00 | 17553534.94 | 0.00 | 5244509.96 | 0.723687E+10 | 0.00 | 0.59 |
June | 0.166404E+10 | 0.129931E+10 | 0.00 | 18243122.06 | 0.294720E+09 | 0.00 | 0.646719E+10 | 0.00 | 0.78 |
July | 0.124970E+10 | 0.220965E+10 | 0.00 | 15535750.68 | 0.402495E+09 | 0.00 | 0.426686E+10 | 0.00 | 0.74 |
August | 0.203641E+10 | 0.123586E+10 | 0.00 | 16905597.33 | 29207198.82 | 0.00 | 0.561180E+10 | 0.00 | 0.80 |
September | 0.531189E+10 | 13784951.82 | 0.00 | 10322064.49 | 0.00 | 0.00 | 0.614291E+10 | 0.00 | 0.54 |
October | 0.794870E+10 | 0.00 | 0.00 | 918094.53 | 0.00 | 0.242325E+09 | 0.104570E+10 | 0.00 | 0.32 |
November | 0.548854E+10 | 0.00 | 0.00 | 0.00 | 159325.89 | 0.150574E+10 | 0.00 | 0.00 | 0.27 |
December | 0.242158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607419E+10 | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.508179E+11 | 0.479189E+10 | 0.00 | 82349474.56 | 0.774249E+09 | 0.214825E+11 | 0.333527E+11 | 0.00 | 0.45 |
Minimum of Months | 0.124970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.794870E+10 | 0.220965E+10 | 0.00 | 18243122.06 | 0.402495E+09 | 0.784355E+10 | 0.723687E+10 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 14011473.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380718E+10 | 0.00 | 0.00 | 0.37 |
February | 0.122864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215809E+10 | 0.00 | 0.00 | 0.32 |
March | 0.552955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148000E+10 | 0.00 | 0.00 | 0.32 |
April | 0.151977E+10 | 0.00 | 0.00 | 267854.48 | 10803754.43 | 0.458023E+09 | 0.237556E+09 | 0.00 | 0.37 |
May | 0.114588E+10 | 11029238.89 | 0.00 | 4461299.53 | 0.00 | 15443467.50 | 0.153468E+10 | 0.00 | 0.72 |
June | 0.430962E+09 | 0.442655E+09 | 0.00 | 5174757.30 | 62066841.64 | 0.00 | 0.171112E+10 | 0.00 | 1.05 |
July | 0.294174E+09 | 0.711408E+09 | 0.00 | 4315584.47 | 88804027.90 | 0.00 | 0.116891E+10 | 0.00 | 0.99 |
August | 0.615483E+09 | 0.367980E+09 | 0.00 | 3509654.98 | 6816524.44 | 220119.18 | 0.114420E+10 | 0.00 | 0.95 |
September | 0.165495E+10 | 3814021.17 | 0.00 | 1607755.48 | 0.00 | 22534825.13 | 0.847106E+09 | 0.00 | 0.57 |
October | 0.152483E+10 | 0.00 | 0.00 | 38691.57 | 0.00 | 0.541605E+09 | 30807466.42 | 0.00 | 0.34 |
November | 0.377265E+09 | 0.00 | 13852.63 | 0.00 | 4467.14 | 0.128789E+10 | 0.00 | 32267.76 | 0.31 |
December | 19703870.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278388E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.827284E+10 | 0.153689E+10 | 13852.63 | 19375597.81 | 0.168496E+09 | 0.125549E+11 | 0.667438E+10 | 32267.76 | 0.56 |
Minimum of Months | 14011473.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.165495E+10 | 0.711408E+09 | 13852.63 | 5174757.30 | 88804027.90 | 0.380718E+10 | 0.171112E+10 | 32267.76 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 13725140.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262780E+10 | 0.00 | 0.00 | 0.43 |
February | 0.271589E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152647E+10 | 0.00 | 0.00 | 0.43 |
March | 0.821315E+09 | 0.00 | 0.00 | 153948.29 | 0.00 | 0.991502E+09 | 72618553.14 | 0.00 | 0.46 |
April | 0.114505E+10 | 0.00 | 0.00 | 2314203.52 | 10550540.08 | 0.267655E+09 | 0.116592E+10 | 0.00 | 0.68 |
May | 0.905170E+09 | 8500848.75 | 0.00 | 5636507.02 | 0.00 | 3328383.37 | 0.208569E+10 | 0.00 | 1.24 |
June | 0.314772E+09 | 0.409298E+09 | 0.00 | 6649885.54 | 37929807.05 | 0.00 | 0.236272E+10 | 0.00 | 1.80 |
July | 0.225997E+09 | 0.692624E+09 | 0.00 | 5945900.83 | 69778047.99 | 0.00 | 0.160251E+10 | 0.00 | 1.79 |
August | 0.616572E+09 | 0.316897E+09 | 0.00 | 5104498.53 | 12207856.00 | 214960.11 | 0.133327E+10 | 0.00 | 1.59 |
September | 0.145851E+10 | 3349952.44 | 0.00 | 2766256.68 | 0.00 | 19007431.02 | 0.140227E+10 | 0.00 | 1.03 |
October | 0.146481E+10 | 0.00 | 0.00 | 325348.77 | 0.00 | 0.436906E+09 | 0.173156E+09 | 0.00 | 0.53 |
November | 0.535567E+09 | 0.00 | 17092.97 | 0.00 | 4362.44 | 0.102497E+10 | 0.00 | 23701.93 | 0.45 |
December | 37281199.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201356E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.781035E+10 | 0.143067E+10 | 17092.97 | 28896549.18 | 0.130471E+09 | 0.891142E+10 | 0.101982E+11 | 23701.93 | 0.91 |
Minimum of Months | 13725140.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.146481E+10 | 0.692624E+09 | 17092.97 | 6649885.54 | 69778047.99 | 0.262780E+10 | 0.236272E+10 | 23701.93 | 1.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.711709E+09 | 0.00 | 0.00 | 979457.79 | 0.00 | 0.264996E+10 | 0.255707E+09 | 0.00 | 0.38 |
February | 0.609881E+09 | 0.00 | 0.00 | 1921806.27 | 0.00 | 0.150786E+10 | 0.635940E+09 | 0.00 | 0.40 |
March | 0.880774E+09 | 0.00 | 0.00 | 2765953.57 | 0.00 | 0.105445E+10 | 0.114318E+10 | 0.00 | 0.45 |
April | 0.126608E+10 | 18061766.04 | 0.00 | 5515819.05 | 3078411.07 | 0.335727E+09 | 0.287078E+10 | 0.00 | 0.76 |
May | 0.117428E+10 | 13713901.30 | 0.00 | 8237071.73 | 0.00 | 21522223.54 | 0.297314E+10 | 0.00 | 1.12 |
June | 0.684002E+09 | 0.524078E+09 | 0.00 | 6536581.87 | 71543339.31 | 0.00 | 0.217775E+10 | 0.00 | 1.38 |
July | 0.444952E+09 | 0.908616E+09 | 0.00 | 5983203.77 | 0.113372E+09 | 0.00 | 0.157539E+10 | 0.00 | 1.35 |
August | 0.831543E+09 | 0.583957E+09 | 0.00 | 7401877.52 | 6442564.88 | 1145873.36 | 0.183651E+10 | 0.00 | 1.52 |
September | 0.157641E+10 | 11824929.96 | 0.00 | 7434457.63 | 0.00 | 26000095.22 | 0.328408E+10 | 0.00 | 1.20 |
October | 0.162433E+10 | 0.00 | 0.00 | 3973638.70 | 0.00 | 0.456946E+09 | 0.163889E+10 | 0.00 | 0.66 |
November | 0.801297E+09 | 0.00 | 18929.16 | 1653433.77 | 5747.14 | 0.977159E+09 | 0.587757E+09 | 34814.65 | 0.42 |
December | 0.377382E+09 | 0.00 | 0.00 | 243950.60 | 0.00 | 0.232796E+10 | 75011246.54 | 0.00 | 0.36 |
Annual Sum or Average | 0.109826E+11 | 0.206025E+10 | 18929.16 | 52647252.28 | 0.194442E+09 | 0.935873E+10 | 0.190541E+11 | 34814.65 | 0.84 |
Minimum of Months | 0.377382E+09 | 0.00 | 0.00 | 243950.60 | 0.00 | 0.00 | 75011246.54 | 0.00 | 0.36 |
Maximum of Months | 0.162433E+10 | 0.908616E+09 | 18929.16 | 8237071.73 | 0.113372E+09 | 0.264996E+10 | 0.328408E+10 | 34814.65 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278524E+10 | 0.00 | 0.00 | 0.47 |
February | 0.346895E+09 | 0.00 | 0.00 | 50021.66 | 0.00 | 0.161796E+10 | 47637524.10 | 0.00 | 0.48 |
March | 0.772985E+09 | 0.00 | 0.00 | 619268.39 | 0.00 | 0.114213E+10 | 0.270935E+09 | 0.00 | 0.53 |
April | 0.131857E+10 | 6116091.49 | 0.00 | 2520691.89 | 8449069.78 | 0.397427E+09 | 0.128916E+10 | 0.00 | 0.80 |
May | 0.116009E+10 | 9486101.11 | 0.00 | 6064690.98 | 0.00 | 22180454.15 | 0.200151E+10 | 0.00 | 1.33 |
June | 0.596218E+09 | 0.383551E+09 | 0.00 | 5118165.49 | 59738676.46 | 0.00 | 0.156226E+10 | 0.00 | 1.68 |
July | 0.368185E+09 | 0.674752E+09 | 0.00 | 4520775.17 | 85632217.14 | 0.00 | 0.109026E+10 | 0.00 | 1.57 |
August | 0.829318E+09 | 0.366127E+09 | 0.00 | 3996705.81 | 8765131.90 | 1446928.58 | 0.105141E+10 | 0.00 | 1.58 |
September | 0.179400E+10 | 4088892.58 | 0.00 | 2705418.12 | 0.00 | 30577134.41 | 0.122164E+10 | 0.00 | 1.11 |
October | 0.152709E+10 | 0.00 | 0.00 | 664570.83 | 0.00 | 0.510380E+09 | 0.342843E+09 | 0.00 | 0.62 |
November | 0.592387E+09 | 0.00 | 19293.94 | 550.18 | 6823.35 | 0.112943E+10 | 5275715.05 | 23998.67 | 0.50 |
December | 65833802.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218970E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.948853E+10 | 0.144412E+10 | 19293.94 | 26260858.53 | 0.162592E+09 | 0.982647E+10 | 0.888293E+10 | 23998.67 | 0.93 |
Minimum of Months | 65833802.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.179400E+10 | 0.674752E+09 | 19293.94 | 6064690.98 | 85632217.14 | 0.278524E+10 | 0.200151E+10 | 23998.67 | 1.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 37937439.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359773E+10 | 0.00 | 0.00 | 0.34 |
February | 52765583.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226280E+10 | 0.00 | 0.00 | 0.30 |
March | 0.483343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183448E+10 | 0.00 | 0.00 | 0.30 |
April | 0.173055E+10 | 0.00 | 0.00 | 0.00 | 9201988.92 | 0.589920E+09 | 0.00 | 0.00 | 0.33 |
May | 0.144765E+10 | 7594127.28 | 0.00 | 2337309.45 | 0.00 | 14717254.18 | 0.814640E+09 | 0.00 | 0.53 |
June | 0.542812E+09 | 0.319325E+09 | 0.00 | 3767373.48 | 50263247.63 | 0.00 | 0.117892E+10 | 0.00 | 0.80 |
July | 0.378281E+09 | 0.548564E+09 | 0.00 | 3854625.52 | 85835846.06 | 0.00 | 0.102122E+10 | 0.00 | 0.83 |
August | 0.569179E+09 | 0.281674E+09 | 0.00 | 3920056.37 | 12287026.46 | 0.00 | 0.126870E+10 | 0.00 | 0.87 |
September | 0.143934E+10 | 2434913.67 | 0.00 | 2220786.10 | 0.00 | 0.00 | 0.125324E+10 | 0.00 | 0.57 |
October | 0.222418E+10 | 0.00 | 0.00 | 53227.82 | 0.00 | 0.137390E+09 | 73429160.56 | 0.00 | 0.33 |
November | 0.848397E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111495E+10 | 0.00 | 0.00 | 0.28 |
December | 37547961.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271046E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.979198E+10 | 0.115959E+10 | 0.00 | 16153378.74 | 0.157588E+09 | 0.122624E+11 | 0.561014E+10 | 0.00 | 0.48 |
Minimum of Months | 37547961.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.222418E+10 | 0.548564E+09 | 0.00 | 3920056.37 | 85835846.06 | 0.359773E+10 | 0.126870E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 35226205.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250836E+10 | 0.00 | 0.00 | 0.38 |
February | 0.223962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154414E+10 | 0.00 | 0.00 | 0.38 |
March | 0.789141E+09 | 0.00 | 0.00 | 6766.09 | 0.00 | 0.111218E+10 | 19620805.44 | 0.00 | 0.39 |
April | 0.125051E+10 | 0.00 | 0.00 | 1645344.60 | 7908891.98 | 0.204308E+09 | 0.838519E+09 | 0.00 | 0.53 |
May | 0.813806E+09 | 6505210.08 | 0.00 | 4370712.46 | 0.00 | 111630.60 | 0.162621E+10 | 0.00 | 0.95 |
June | 0.273383E+09 | 0.315202E+09 | 0.00 | 5770264.89 | 24980825.58 | 0.00 | 0.195533E+10 | 0.00 | 1.49 |
July | 0.258840E+09 | 0.580995E+09 | 0.00 | 5495410.20 | 57896225.07 | 0.00 | 0.144685E+10 | 0.00 | 1.53 |
August | 0.394102E+09 | 0.268517E+09 | 0.00 | 5447485.59 | 10442214.99 | 0.00 | 0.153971E+10 | 0.00 | 1.46 |
September | 0.992958E+09 | 2301710.43 | 0.00 | 3665171.71 | 0.00 | 0.00 | 0.194298E+10 | 0.00 | 1.01 |
October | 0.172375E+10 | 0.00 | 0.00 | 449857.78 | 0.00 | 99054483.14 | 0.326778E+09 | 0.00 | 0.46 |
November | 0.869764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803502E+09 | 0.00 | 0.00 | 0.38 |
December | 61769928.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200361E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.768721E+10 | 0.117352E+10 | 0.00 | 26851013.32 | 0.101228E+09 | 0.827527E+10 | 0.969600E+10 | 0.00 | 0.78 |
Minimum of Months | 35226205.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.172375E+10 | 0.580995E+09 | 0.00 | 5770264.89 | 57896225.07 | 0.250836E+10 | 0.195533E+10 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 74685079.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579185E+10 | 0.00 | 0.00 | 0.55 |
February | 0.315984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336182E+10 | 0.00 | 0.00 | 0.48 |
March | 0.498127E+09 | 0.00 | 0.00 | 50031.53 | 0.00 | 0.300182E+10 | 41663131.37 | 0.00 | 0.46 |
April | 0.122914E+10 | 6045897.03 | 0.00 | 955412.78 | 5528328.75 | 0.155030E+10 | 0.584373E+09 | 0.00 | 0.50 |
May | 0.153444E+10 | 12200991.55 | 0.00 | 3546479.06 | 0.00 | 0.529143E+09 | 0.846090E+09 | 0.00 | 0.72 |
June | 0.891375E+09 | 0.399923E+09 | 0.00 | 3385341.86 | 63960600.53 | 0.163628E+09 | 0.872705E+09 | 0.00 | 0.95 |
July | 0.502122E+09 | 0.734835E+09 | 0.00 | 3950301.19 | 0.103012E+09 | 48482658.84 | 0.100673E+10 | 0.00 | 1.02 |
August | 0.858616E+09 | 0.462183E+09 | 0.00 | 5032649.92 | 10262075.04 | 0.140014E+09 | 0.117671E+10 | 0.00 | 1.20 |
September | 0.154871E+10 | 6703030.97 | 0.00 | 5439408.09 | 0.00 | 0.547710E+09 | 0.220525E+10 | 0.00 | 1.01 |
October | 0.137861E+10 | 0.00 | 0.00 | 2217807.31 | 0.00 | 0.153471E+10 | 0.864118E+09 | 0.00 | 0.56 |
November | 0.503595E+09 | 0.00 | 0.00 | 34334.61 | 0.00 | 0.237107E+10 | 29455893.86 | 0.00 | 0.42 |
December | 0.135575E+09 | 0.00 | 0.00 | 25223.89 | 0.00 | 0.445974E+10 | 15747777.47 | 0.00 | 0.53 |
Annual Sum or Average | 0.947098E+10 | 0.162189E+10 | 0.00 | 24636990.25 | 0.182763E+09 | 0.235003E+11 | 0.764284E+10 | 0.00 | 0.70 |
Minimum of Months | 74685079.40 | 0.00 | 0.00 | 0.00 | 0.00 | 48482658.84 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.154871E+10 | 0.734835E+09 | 0.00 | 5439408.09 | 0.103012E+09 | 0.579185E+10 | 0.220525E+10 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264537E+10 | 0.00 | 0.00 | 0.41 |
February | 0.304609E+09 | 0.00 | 0.00 | 2941.77 | 0.00 | 0.161757E+10 | 6081324.18 | 0.00 | 0.41 |
March | 0.796936E+09 | 0.00 | 0.00 | 186106.32 | 0.00 | 0.121131E+10 | 0.104686E+09 | 0.00 | 0.43 |
April | 0.145407E+10 | 1221851.18 | 0.00 | 1297180.55 | 7860014.86 | 0.301970E+09 | 0.684901E+09 | 0.00 | 0.57 |
May | 0.995616E+09 | 8731274.44 | 0.00 | 4419942.77 | 0.00 | 10011918.16 | 0.143852E+10 | 0.00 | 0.98 |
June | 0.517326E+09 | 0.300751E+09 | 0.00 | 4073589.78 | 41420957.94 | 0.00 | 0.118003E+10 | 0.00 | 1.30 |
July | 0.280660E+09 | 0.593217E+09 | 0.00 | 4322497.43 | 62642554.84 | 0.00 | 0.112147E+10 | 0.00 | 1.36 |
August | 0.514392E+09 | 0.294327E+09 | 0.00 | 4572149.31 | 4984994.56 | 0.00 | 0.130218E+10 | 0.00 | 1.41 |
September | 0.121037E+10 | 3580719.15 | 0.00 | 3288044.44 | 0.00 | 0.00 | 0.163043E+10 | 0.00 | 1.00 |
October | 0.187879E+10 | 0.00 | 0.00 | 658594.35 | 0.00 | 0.123693E+09 | 0.375899E+09 | 0.00 | 0.52 |
November | 0.921709E+09 | 0.00 | 0.00 | 2009.25 | 0.00 | 0.891156E+09 | 6547800.63 | 0.00 | 0.42 |
December | 83749439.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214814E+10 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.906793E+10 | 0.120183E+10 | 0.00 | 22823055.96 | 0.116909E+09 | 0.894922E+10 | 0.785074E+10 | 0.00 | 0.77 |
Minimum of Months | 83749439.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.187879E+10 | 0.593217E+09 | 0.00 | 4572149.31 | 62642554.84 | 0.264537E+10 | 0.163043E+10 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 29262812.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353341E+10 | 0.00 | 0.00 | 0.33 |
February | 0.177604E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201478E+10 | 0.00 | 0.00 | 0.29 |
March | 0.835782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124181E+10 | 0.00 | 0.00 | 0.29 |
April | 0.162107E+10 | 0.00 | 0.00 | 453534.65 | 7139443.72 | 0.252593E+09 | 0.334223E+09 | 0.00 | 0.34 |
May | 0.881445E+09 | 12653402.44 | 0.00 | 5194523.01 | 0.00 | 4775571.36 | 0.189171E+10 | 0.00 | 0.71 |
June | 0.251075E+09 | 0.452230E+09 | 0.00 | 5888447.32 | 44686336.41 | 0.00 | 0.189170E+10 | 0.00 | 1.04 |
July | 0.280731E+09 | 0.693158E+09 | 0.00 | 4840441.15 | 72684686.02 | 0.00 | 0.124351E+10 | 0.00 | 0.97 |
August | 0.440611E+09 | 0.342870E+09 | 0.00 | 4474671.33 | 9714100.87 | 0.00 | 0.142216E+10 | 0.00 | 0.94 |
September | 0.126201E+10 | 7094030.80 | 0.00 | 2615070.69 | 102691.72 | 0.00 | 0.137447E+10 | 0.00 | 0.58 |
October | 0.182892E+10 | 0.00 | 0.00 | 121572.03 | 0.00 | 0.233953E+09 | 0.129561E+09 | 0.00 | 0.32 |
November | 0.690812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104127E+10 | 0.00 | 0.00 | 0.29 |
December | 26614928.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267977E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.832594E+10 | 0.150800E+10 | 0.00 | 23588260.17 | 0.134327E+09 | 0.110024E+11 | 0.828735E+10 | 0.00 | 0.54 |
Minimum of Months | 26614928.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.182892E+10 | 0.693158E+09 | 0.00 | 5888447.32 | 72684686.02 | 0.353341E+10 | 0.189171E+10 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 95155409.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283233E+10 | 0.00 | 0.00 | 0.45 |
February | 0.428184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161136E+10 | 0.00 | 0.00 | 0.45 |
March | 0.108681E+10 | 0.00 | 0.00 | 321806.16 | 0.00 | 0.977276E+09 | 0.127245E+09 | 0.00 | 0.49 |
April | 0.138895E+10 | 0.00 | 0.00 | 2778516.61 | 7639934.69 | 0.161743E+09 | 0.134975E+10 | 0.00 | 0.71 |
May | 0.825838E+09 | 9619026.03 | 0.00 | 6176514.52 | 0.00 | 90105.60 | 0.235393E+10 | 0.00 | 1.23 |
June | 0.278475E+09 | 0.397228E+09 | 0.00 | 6997633.15 | 29940314.18 | 0.00 | 0.242786E+10 | 0.00 | 1.77 |
July | 0.256031E+09 | 0.685132E+09 | 0.00 | 6100759.77 | 56244064.40 | 0.00 | 0.163842E+10 | 0.00 | 1.72 |
August | 0.518356E+09 | 0.299832E+09 | 0.00 | 5479851.32 | 10584373.74 | 0.00 | 0.155275E+10 | 0.00 | 1.56 |
September | 0.145731E+10 | 6995133.21 | 0.00 | 3307136.88 | 109890.64 | 1178965.87 | 0.170333E+10 | 0.00 | 1.08 |
October | 0.189387E+10 | 0.00 | 0.00 | 467779.41 | 0.00 | 0.230646E+09 | 0.279753E+09 | 0.00 | 0.56 |
November | 0.864006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.950883E+09 | 0.00 | 0.00 | 0.47 |
December | 72532277.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227788E+10 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.916551E+10 | 0.139881E+10 | 0.00 | 31629997.81 | 0.104519E+09 | 0.904339E+10 | 0.114330E+11 | 0.00 | 0.91 |
Minimum of Months | 72532277.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.189387E+10 | 0.685132E+09 | 0.00 | 6997633.15 | 56244064.40 | 0.283233E+10 | 0.242786E+10 | 0.00 | 1.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.834807E+09 | 0.00 | 0.00 | 1536402.55 | 0.00 | 0.259652E+10 | 0.424036E+09 | 0.00 | 0.38 |
February | 0.767935E+09 | 0.00 | 0.00 | 2476756.74 | 0.00 | 0.144666E+10 | 0.727068E+09 | 0.00 | 0.42 |
March | 0.113262E+10 | 0.00 | 0.00 | 3603000.96 | 0.00 | 0.927434E+09 | 0.130967E+10 | 0.00 | 0.46 |
April | 0.141184E+10 | 15485916.48 | 0.00 | 6201970.32 | 563859.48 | 0.202722E+09 | 0.297106E+10 | 0.00 | 0.76 |
May | 0.102114E+10 | 16511200.43 | 0.00 | 8925187.63 | 0.00 | 6512705.38 | 0.315262E+10 | 0.00 | 1.08 |
June | 0.533366E+09 | 0.522256E+09 | 0.00 | 6985273.41 | 58248216.67 | 0.00 | 0.217154E+10 | 0.00 | 1.34 |
July | 0.440350E+09 | 0.906775E+09 | 0.00 | 5983985.82 | 92391448.72 | 0.00 | 0.153444E+10 | 0.00 | 1.28 |
August | 0.615763E+09 | 0.535643E+09 | 0.00 | 7617601.35 | 7509954.39 | 0.00 | 0.202019E+10 | 0.00 | 1.44 |
September | 0.130111E+10 | 22323098.06 | 0.00 | 8718693.46 | 135310.96 | 0.00 | 0.375914E+10 | 0.00 | 1.23 |
October | 0.189530E+10 | 0.00 | 0.00 | 4732036.98 | 0.00 | 0.207246E+09 | 0.192758E+10 | 0.00 | 0.67 |
November | 0.107864E+10 | 0.00 | 0.00 | 2076608.49 | 0.00 | 0.855825E+09 | 0.731966E+09 | 0.00 | 0.42 |
December | 0.519970E+09 | 0.00 | 0.00 | 436283.20 | 0.00 | 0.234845E+10 | 0.144830E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.115528E+11 | 0.201899E+10 | 0.00 | 59293800.89 | 0.158849E+09 | 0.859137E+10 | 0.208741E+11 | 0.00 | 0.82 |
Minimum of Months | 0.440350E+09 | 0.00 | 0.00 | 436283.20 | 0.00 | 0.00 | 0.144830E+09 | 0.00 | 0.36 |
Maximum of Months | 0.189530E+10 | 0.906775E+09 | 0.00 | 8925187.63 | 92391448.72 | 0.259652E+10 | 0.375914E+10 | 0.00 | 1.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.189768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287561E+10 | 0.00 | 0.00 | 0.47 |
February | 0.431374E+09 | 0.00 | 0.00 | 66210.58 | 0.00 | 0.166293E+10 | 46797368.73 | 0.00 | 0.48 |
March | 0.100521E+10 | 0.00 | 0.00 | 707467.46 | 0.00 | 0.107361E+10 | 0.300740E+09 | 0.00 | 0.53 |
April | 0.154732E+10 | 377104.05 | 0.00 | 2674175.73 | 7763225.51 | 0.231485E+09 | 0.127981E+10 | 0.00 | 0.77 |
May | 0.100002E+10 | 11908103.98 | 0.00 | 6528391.11 | 0.00 | 5423136.79 | 0.212658E+10 | 0.00 | 1.27 |
June | 0.510278E+09 | 0.388114E+09 | 0.00 | 5321644.87 | 44909628.18 | 0.00 | 0.153415E+10 | 0.00 | 1.61 |
July | 0.382930E+09 | 0.670814E+09 | 0.00 | 4649163.79 | 68114826.01 | 0.00 | 0.106878E+10 | 0.00 | 1.50 |
August | 0.647014E+09 | 0.334064E+09 | 0.00 | 4269148.96 | 3491447.54 | 0.00 | 0.120742E+10 | 0.00 | 1.49 |
September | 0.155681E+10 | 6304459.58 | 0.00 | 3219395.10 | 108341.23 | 1232702.94 | 0.153351E+10 | 0.00 | 1.10 |
October | 0.192283E+10 | 0.00 | 0.00 | 801096.39 | 0.00 | 0.254922E+09 | 0.411950E+09 | 0.00 | 0.62 |
November | 0.876811E+09 | 0.00 | 0.00 | 9629.56 | 0.00 | 0.100281E+10 | 16479180.70 | 0.00 | 0.49 |
December | 0.123503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233616E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.101939E+11 | 0.141158E+10 | 0.00 | 28246323.56 | 0.124387E+09 | 0.944419E+10 | 0.952621E+10 | 0.00 | 0.90 |
Minimum of Months | 0.123503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.192283E+10 | 0.670814E+09 | 0.00 | 6528391.11 | 68114826.01 | 0.287561E+10 | 0.212658E+10 | 0.00 | 1.61 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.174306E+12 | 0.399029E+11 | 0.00 | 0.174153E+12 | 0.991852E+10 |
February | 0.231856E+12 | 0.333969E+11 | 0.00 | 0.154877E+12 | 0.356665E+10 |
March | 0.312664E+12 | 0.269490E+11 | 0.00 | 0.185673E+12 | 0.658587E+09 |
April | 0.372463E+12 | 0.204225E+11 | 0.00 | 0.194485E+12 | 0.516163E+10 |
May | 0.421431E+12 | 0.103179E+11 | 0.00 | 0.241076E+12 | 0.645391E+11 |
June | 0.426655E+12 | 0.335649E+10 | 0.00 | 0.156755E+12 | 0.147229E+12 |
July | 0.434136E+12 | 0.134726E+10 | 0.00 | 0.113317E+12 | 0.197162E+12 |
August | 0.366455E+12 | 0.429361E+10 | 0.00 | 0.167051E+12 | 0.148912E+12 |
September | 0.277116E+12 | 0.103891E+11 | 0.00 | 0.235482E+12 | 0.322381E+11 |
October | 0.168899E+12 | 0.166180E+11 | 0.00 | 0.208664E+12 | 0.434793E+10 |
November | 0.995389E+11 | 0.258338E+11 | 0.00 | 0.152737E+12 | 0.101533E+10 |
December | 0.129047E+12 | 0.398227E+11 | 0.00 | 0.167051E+12 | 0.589926E+10 |
Annual Sum or Average | 0.341457E+13 | 0.232650E+12 | 0.00 | 0.215132E+13 | 0.620649E+12 |
Minimum of Months | 0.995389E+11 | 0.134726E+10 | 0.00 | 0.113317E+12 | 0.658587E+09 |
Maximum of Months | 0.434136E+12 | 0.399029E+11 | 0.00 | 0.241076E+12 | 0.197162E+12 |