Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2023-10-16 08:35:17
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2314.58 | 464.57 | 464.57 |
Net Site Energy | 2314.58 | 464.57 | 464.57 |
Total Source Energy | 6304.78 | 1265.46 | 1265.46 |
Net Source Energy | 6304.78 | 1265.46 | 1265.46 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 437.78 | 376.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 156.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 100.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 116.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1822.26 | 492.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 437.78 | 376.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 156.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 280.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 71.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 100.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 116.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 437.78 | 376.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 156.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 280.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 71.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 100.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 116.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 139.36 | 98.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 365.76 | 98.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 139.36 | 98.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 365.76 | 98.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1822.261 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1822.261 | 100.00 |
Total On-Site and Utility Electric Sources | 1822.261 | 100.00 |
Total Electricity End Uses | 1822.261 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 783.67 |
Time Setpoint Not Met During Occupied Cooling | 103.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3288.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.5763 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 7.5763 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 7.5763 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 02-FEB-07:40 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 215582.80 | 191400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 9359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21853.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 256.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7741.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8239.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 260351.92 | 199639.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 215582.80 | 191400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 9359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 16082.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 256.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7741.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8239.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 1386.45 | 407.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 494.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 227.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2413.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 41.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 125.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5771.10 | 533.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 278.28 | 81.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 99.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 178.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 63.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 25.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1158.35 | 107.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 278.28 | 81.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 99.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 178.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 63.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 25.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1158.35 | 107.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.95 | 0.254289 | 0.266000 | 0.783972 | 0.678103 | 0.500000 | 0.001498 |
CORE_MID VAV BOX COMPONENT | 2.16 | 0.346695 | 0.353000 | 0.763085 | 0.924519 | 0.500000 | 0.001099 |
CORE_TOP VAV BOX COMPONENT | 2.29 | 0.326738 | 0.346000 | 0.793637 | 0.871302 | 0.500000 | 0.001166 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.817423 | 0.193280 | 0.232000 | 0.189642 | 0.515414 | 0.500000 | 0.001971 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.846801 | 0.118117 | 0.200000 | 0.169360 | 0.314979 | 0.500000 | 0.003226 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.05 | 0.150191 | 0.200000 | 0.210388 | 0.400509 | 0.500000 | 0.002537 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.940485 | 0.106344 | 0.200000 | 0.188097 | 0.300000 | 0.500000 | 0.003583 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.599795 | 0.263409 | 0.298000 | 0.178739 | 0.702425 | 0.500000 | 0.001446 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.684169 | 0.146195 | 0.200000 | 0.136834 | 0.389852 | 0.500000 | 0.002606 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.826363 | 0.191189 | 0.200000 | 0.165273 | 0.509838 | 0.500000 | 0.001993 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.738443 | 0.135441 | 0.200000 | 0.147689 | 0.361175 | 0.500000 | 0.002813 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.638467 | 0.247455 | 0.257000 | 0.164086 | 0.659879 | 0.500000 | 0.001540 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.826062 | 0.121083 | 0.200000 | 0.165212 | 0.322887 | 0.500000 | 0.003147 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.950355 | 0.166245 | 0.200000 | 0.190071 | 0.443320 | 0.500000 | 0.002292 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.864264 | 0.115723 | 0.200000 | 0.172853 | 0.308595 | 0.500000 | 0.003292 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 24974.61 |
CORE_MID VAV BOX REHEAT COIL | 30086.82 |
CORE_TOP VAV BOX REHEAT COIL | 50916.31 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 26040.25 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 16891.98 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 25774.30 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 17057.30 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 19107.39 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12478.91 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 18900.42 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 12616.15 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 20339.34 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 13250.40 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 20107.76 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 13391.09 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.90 | 1.41 | 5.80 | 2.50 | 5.10 | 5.10 | 0.300000 | 0.490029 | 5.10 |
PACU_VAV_MID | 2.72 | 1.46 | 5.44 | 3.05 | 4.57 | 4.57 | 0.300000 | 0.666803 | 4.57 |
PACU_VAV_TOP | 2.98 | 1.55 | 5.95 | 4.29 | 5.29 | 5.29 | 0.300000 | 0.811306 | 5.29 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.10 |
PACU_VAV_MID_OA_CONTROLLER | 4.57 |
PACU_VAV_TOP_OA_CONTROLLER | 5.29 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.10 | 111284.41 | 0.743650 | 1.70 | 37091.09 | 0.743650 |
PACU_VAV_MID COOLING COIL | 4.57 | 103540.48 | 0.730895 | 1.52 | 34510.04 | 0.730895 |
PACU_VAV_TOP COOLING COIL | 5.29 | 115317.88 | 0.744099 | 1.76 | 38435.45 | 0.744099 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 51694.37 |
PACU_VAV_MID HEATING COIL | 52850.20 |
PACU_VAV_TOP HEATING COIL | 51674.47 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.10 |
PACU_VAV_MID FAN | 4.57 |
PACU_VAV_TOP FAN | 5.29 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 32.411 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9320 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9163 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.269 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8390 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8573 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5538 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.27971961E-12 | 0.14534712E-14 | -0.84678956E-13 | 0.82684317E-16 |
43 | 6 | 0.26817376E-07 | 0.25687399E-09 | 0.61588016E-08 | -0.12527087E-12 |
44 | 5 | -0.18065003E-03 | 0.22251366E-05 | -0.93037841E-04 | 0.60936178E-08 |
45 | 4 | 0.28101542 | 0.10946024E-02 | 0.95683253E-01 | -0.32007147E-04 |
46 | 3 | -7.0457283 | 0.34231649E-01 | -2.2734647 | 0.27928366E-01 |
47 | 2 | 40.143429 | 0.12270019 | 14.996275 | -0.32523640 |
48 | 1 | -79.987958 | 0.55761501E-01 | -28.900564 | 1.0667320 |
49 | 0 | 46.824342 | 0.11295401E-02 | 16.297084 | |
50 | 7 | -0.28233695E-12 | 0.14433069E-14 | -0.85363548E-13 | 0.83491456E-16 |
51 | 6 | 0.27004714E-07 | 0.25312183E-09 | 0.62001510E-08 | -0.12627076E-12 |
52 | 5 | -0.18161011E-03 | 0.21898175E-05 | -0.93520278E-04 | 0.61339935E-08 |
53 | 4 | 0.28215201 | 0.10760039E-02 | 0.96091377E-01 | -0.32166146E-04 |
54 | 3 | -7.0682688 | 0.33616209E-01 | -2.2801509 | 0.28038740E-01 |
55 | 2 | 40.217804 | 0.12038787 | 15.023777 | -0.32606455 |
56 | 1 | -80.044990 | 0.54668782E-01 | -28.925243 | 1.0679473 |
57 | 0 | 46.824342 | 0.11065724E-02 | 16.296477 | |
58 | 6 | 0.22748378E-07 | 0.33059726E-09 | 0.52605359E-08 | -0.10371465E-12 |
59 | 5 | -0.15952455E-03 | 0.29533519E-05 | -0.82380770E-04 | 0.52144884E-08 |
60 | 4 | 0.25560578 | 0.14926938E-02 | 0.86578981E-01 | -0.28493712E-04 |
61 | 3 | -6.5408460 | 0.47808585E-01 | -2.1237636 | 0.25458881E-01 |
62 | 2 | 38.476406 | 0.17496760 | 14.378110 | -0.30668036 |
63 | 1 | -78.708466 | 0.80951212E-01 | -28.345189 | 1.0394692 |
64 | 0 | 46.824351 | 0.16689207E-02 | 16.311239 | |
65 | 7 | -0.18042418E-08 | -0.42925973E-15 | 0.63337540E-14 | -0.83764910E-16 |
66 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
67 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
68 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
69 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
70 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
71 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
72 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
73 | 7 | -0.17078159E-08 | -0.36552483E-15 | 0.71259391E-14 | -0.98899249E-16 |
74 | 6 | 0.68798867E-05 | 0.47165251E-08 | 0.31862110E-02 | -0.26728608E-04 |
75 | 5 | -0.49558197E-03 | 0.27953368E-05 | -0.22351660 | 0.19543146E-02 |
76 | 4 | 0.11404824E-01 | 0.12725100E-03 | 4.8260817 | -0.45231683E-01 |
77 | 3 | -0.10016651 | 0.10121065E-02 | -38.001848 | 0.39843745 |
78 | 2 | 0.35569192 | 0.16837830E-02 | 116.44586 | -1.4174299 |
79 | 1 | -0.51340120 | 0.51323984E-03 | -143.88489 | 2.0486714 |
80 | 0 | 0.25031121 | 0.12359947E-04 | 60.838472 | |
81 | 7 | -0.18042418E-08 | -0.42925997E-15 | 0.63337541E-14 | -0.83764912E-16 |
82 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
83 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
84 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
85 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
86 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
87 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
88 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
89 | 7 | -0.17076967E-08 | -0.36446083E-15 | 0.71390403E-14 | -0.94439575E-16 |
90 | 6 | 0.68803475E-05 | 0.47168467E-08 | 0.31862096E-02 | -0.26728597E-04 |
91 | 5 | -0.49561596E-03 | 0.27955299E-05 | -0.22351653 | 0.19543140E-02 |
92 | 4 | 0.11405612E-01 | 0.12725979E-03 | 4.8260805 | -0.45231671E-01 |
93 | 3 | -0.10017344 | 0.10121766E-02 | -38.001841 | 0.39843738 |
94 | 2 | 0.35571654 | 0.16838995E-02 | 116.44585 | -1.4174297 |
95 | 1 | -0.51343675 | 0.51327568E-03 | -143.88488 | 2.0486713 |
96 | 0 | 0.25032854 | 0.12360692E-04 | 60.838472 | |
97 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
98 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
99 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
100 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
101 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
102 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
103 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
104 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
105 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0881E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0943E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2086E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2139E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2351E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2780E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8297E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8525E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1522 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.4286E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1739 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.6227E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1070 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6235E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4494E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6685E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0883E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0953E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2087E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2150E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2365E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2853E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8295E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8523E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8778E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0429E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5716E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7831E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7406E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3985E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1768E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4209E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0827E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.1076E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8122E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8301E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4562E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.4624E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4698E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4776E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1172E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1713E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4393E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4830E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9846E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0171E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8295E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.8523E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9359E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3191E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0435E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7699E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9146E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2332E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4494E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6685E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1169E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1718E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4387E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4819E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9833E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0119E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8297E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.8525E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9302E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5769E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3802E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1946E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9839E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0398E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1769E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4210E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5022E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5745E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0783E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.1583E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0133E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0419E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4700E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.4778E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1498 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.9954E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1682 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1135 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1131 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.7556E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.0018E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.3204E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.6100E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.8931E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.3266E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.6466E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.5405E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.2902E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.0531E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3544E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.4483E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.9818E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.5022E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3411E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3717E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7595E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.0018E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3204E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.6990E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4503E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.1814E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0877E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.8111E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9482E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.0532E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3545E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1498 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.9945E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1682 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1134 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1131 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.7549E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.0015E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.3201E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.6101E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.8929E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.3266E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.6463E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.5402E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.2899E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.0527E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3542E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.4486E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.9817E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.5023E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3410E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3716E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7593E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.0015E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3201E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.6991E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4502E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.1815E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0875E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.8109E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9479E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.0528E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3542E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 39011.94234 | 39011.94234 | 2.94726 | 2.94726 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 11655.87776 | 11655.87776 | 0.51595 | 0.51595 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 28647.36643 | 28647.36643 | 2.16171 | 2.16171 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 21213.65982 | 21213.65982 | 0.94445 | 0.94445 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 30111.94508 | 30111.94508 | 2.29375 | 2.29375 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 30.98800 | 1.53647E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 35806.03040 | 35806.03040 | 1.59830 | 1.59830 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9456.32773 | 9456.32773 | 0.72043 | 0.72043 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 18271.88131 | 18271.88131 | 0.81742 | 0.81742 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11115.19436 | 11115.19436 | 0.84680 | 0.84680 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.97067 | 1.53554E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 11852.36611 | 11852.36611 | 0.53025 | 0.53025 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13807.87106 | 13807.87106 | 1.05194 | 1.05194 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53648E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 18085.57266 | 18085.57266 | 0.80907 | 0.80907 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12344.94475 | 12344.94475 | 0.94049 | 0.94049 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 11968.18000 | 11968.18000 | 0.53544 | 0.53544 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7290.94473 | 7290.94473 | 0.55542 | 0.55542 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 13413.31552 | 13413.31552 | 0.59980 | 0.59980 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8981.06126 | 8981.06126 | 0.68417 | 0.68417 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.57133 | 1.53565E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 8759.60707 | 8759.60707 | 0.39172 | 0.39172 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10847.61380 | 10847.61380 | 0.82636 | 0.82636 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 31.11167 | 1.53649E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 13268.34574 | 13268.34574 | 0.59330 | 0.59330 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9693.54001 | 9693.54001 | 0.73844 | 0.73844 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 28.39100 | 1.53599E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 8855.73122 | 8855.73122 | 0.39603 | 0.39603 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8210.70118 | 8210.70118 | 0.62552 | 0.62552 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 14277.49428 | 14277.49428 | 0.63847 | 0.63847 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10843.22940 | 10843.22940 | 0.82606 | 0.82606 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.37000 | 1.53543E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 9300.83003 | 9300.83003 | 0.41594 | 0.41594 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 12474.72833 | 12474.72833 | 0.95035 | 0.95035 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53646E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 14115.28038 | 14115.28038 | 0.63120 | 0.63120 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11344.71362 | 11344.71362 | 0.86426 | 0.86426 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53617E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 9399.38095 | 9399.38095 | 0.42036 | 0.42036 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 75756.45 | 5.09520 | 5.09520 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 53601.05 | 2.49680 | 2.49680 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 68935.86 | 4.57468 | 4.57468 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 53618.54 | 3.05041 | 3.05041 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 78044.41 | 5.28838 | 5.28838 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 53732.34 | 4.29049 | 4.29049 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.94726 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25429 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26600 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78397 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67810 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49830E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24974.61219 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.16171 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34669 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35300 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76308 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92452 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09895E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 30086.81979 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.29375 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32674 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34600 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79364 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87130 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16607E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 50916.30806 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81742 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19328 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23200 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18964 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51541 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97123E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26040.25060 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84680 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11812 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16936 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31498 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.22561E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16891.97718 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05194 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15019 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21039 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40051 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.53677E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25774.30241 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94049 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10634 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18810 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.58270E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17057.29714 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59980 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26341 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29800 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17874 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70242 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44642E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19107.39089 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68417 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14619 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13683 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38985 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.60611E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12478.91252 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82636 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19119 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16527 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50984 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.99279E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18900.42081 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73844 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13544 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14769 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36118 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.81304E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12616.14666 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63847 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24745 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25700 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16409 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65988 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.53968E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20339.33558 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82606 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12108 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16521 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32289 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.14661E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13250.40155 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95035 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16624 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19007 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44332 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.29180E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20107.76386 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86426 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11572 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17285 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30859 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.29234E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13391.09052 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.89802 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.41251 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.79603 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.49680 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.09520 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.09520 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.49003 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.72043 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.45531 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.44086 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 3.05041 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.57468 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.57468 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.66680 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.97520 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.55112 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.95040 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 4.29049 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.28838 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.28838 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.81131 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.09520 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.57468 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.28838 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.09520 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.09520 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 111284.41118 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74365 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.69823 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37091.09425 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74365 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 51694.36656 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.09520 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.57468 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.57468 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 103540.47715 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73089 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.52474 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34510.04103 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73089 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 52850.19509 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.57468 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.28838 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.28838 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 115317.88125 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74410 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.76262 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 38435.44982 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74410 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 51674.46624 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.28838 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 110628.02 | 377478.47 | 11.48 | 2.92 | 3.29 | 3.47 | 3.61 | 9.97 | 11.23 | 11.83 | 12.33 | 5.6210 | 4.4801 | 3.0162 | 1.2491 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 103058.11 | 351648.85 | 11.55 | 2.94 | 3.31 | 3.49 | 3.63 | 10.02 | 11.30 | 11.91 | 12.38 | 5.0468 | 4.0158 | 2.7029 | 1.1339 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 114631.13 | 391137.64 | 11.48 | 2.92 | 3.29 | 3.47 | 3.61 | 9.97 | 11.22 | 11.83 | 12.33 | 5.8341 | 4.6498 | 3.1304 | 1.2959 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.246 | 0.232 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.246 | 0.232 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.1797244238E-002 | 2.6789875020E-002 | Pass | Pass | 0.4826917264 | 0.4902117310 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1731129566 | 0.1139431260 | Pass | Pass | 0.4904431494 | 0.4780050818 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.5355435348E-002 | 5.0331015381E-002 | Pass | Pass | 0.4932442439 | 0.4697691355 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.1214607255E-002 | 4.9137492044E-002 | Pass | Pass | 0.4965904507 | 0.4683632314 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.3442833785E-003 | 3.5345133628E-003 | Pass | Pass | 0.5044469228 | 0.5022133549 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1107219271 | 0.1040272828 | Pass | Pass | 10.6763720657 | 37.7906216150 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4864430351 | 0.4444678089 | Pass | Pass | 16.7601723492 | 88.8808949828 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5361065631 | 0.5100483104 | Pass | Pass | 15.3501481873 | 115.7553109261 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4594779208 | 0.4661738730 | Pass | Pass | 10.6890767386 | 55.1324806904 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5415865830 | 0.5092946565 | Pass | Pass | 7.5237635934 | 33.7315750597 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3356007288 | 0.3088907976 | Pass | Pass | 8.6815842974 | 31.2859631625 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3894582851 | 0.3582411163 | Pass | Pass | 8.1512857681 | 26.9265331789 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3379091735 | 0.3238468114 | Pass | Pass | 7.9715156982 | 25.3873488224 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3963798136 | 0.3603779673 | Pass | Pass | 8.3005473214 | 27.4419743628 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3472808733 | 0.3227071869 | Pass | Pass | 11.9526753369 | 50.9846751601 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3892855477 | 0.3708420547 | Pass | Pass | 24.9059447696 | 135.5822809362 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3471980902 | 0.3463420127 | Pass | Pass | 12.7001457246 | 58.0672424064 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3957906816 | 0.3695717551 | Pass | Pass | 10.6113579633 | 45.9030868598 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3693.17 | 250.31 | 0.00 | 1711.39 | 865.28 | 6520.15 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3622_SHGC_EAST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3622_SHGC_WEST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3622_SHGC_EAST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3622_SHGC_WEST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.058 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 177.99 | 2.058 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.058 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.44 | 0.0000 | Y | 9.27 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.38 | 0.0000 | Y | 5.86 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.22 | 0.0000 | Y | 9.21 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.30 | 0.0000 | Y | 5.84 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.40 | 0.0000 | Y | 9.26 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.34 | 0.0000 | Y | 5.85 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.19 | 0.0000 | Y | 9.20 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.27 | 0.0000 | Y | 5.84 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.44 | 0.0000 | Y | 9.27 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.38 | 0.0000 | Y | 5.86 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.22 | 0.0000 | Y | 9.21 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.30 | 0.0000 | Y | 5.84 |
Interior Lighting Total | 7.5763 | 4982.19 | 37746.71 | 280.95 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 42.24 | 42.24 | 3.37 | |
EXTERIOR_LIGHTS_B | 5132.60 | AstronomicalClock | - | 83.63 | 71.21 | 68.61 | |
Exterior Lighting Total | 5557.43 | 71.98 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 111284.41 | 82756.65 | 28527.76 | 0.74 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 103540.48 | 75677.17 | 27863.30 | 0.73 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 115317.88 | 85807.87 | 29510.01 | 0.74 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 110628.0 | 2.92 | 9.97 | N/A | N/A | 11.48 | |
PACU_VAV_MID COOLING COIL | 103058.1 | 2.94 | 10.02 | N/A | N/A | 11.55 | |
PACU_VAV_TOP COOLING COIL | 114631.1 | 2.92 | 9.97 | N/A | N/A | 11.48 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 24974.61 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 30086.82 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 50916.31 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 26040.25 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16891.98 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 25774.30 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17057.30 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19107.39 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12478.91 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18900.42 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12616.15 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20339.34 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13250.40 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20107.76 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13391.09 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 51694.37 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 52850.20 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 51674.47 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.10 | 11711.13 | 2298.46 | 1.00 | 1.13 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.57 | 10582.99 | 2313.39 | 1.00 | 1.13 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.29 | 12155.13 | 2298.46 | 1.00 | 1.13 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 110628.02 | 2.92 | 9.97 | 11.48 | 5.6210 | 3.29 | 11.23 | 4.4801 | 3.47 | 11.83 | 3.0162 | 3.61 | 12.33 | 1.2491 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 103058.11 | 2.94 | 10.02 | 11.55 | 5.0468 | 3.31 | 11.30 | 4.0158 | 3.49 | 11.91 | 2.7029 | 3.63 | 12.38 | 1.1339 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 114631.13 | 2.92 | 9.97 | 11.48 | 5.8341 | 3.29 | 11.22 | 4.6498 | 3.47 | 11.83 | 3.1304 | 3.61 | 12.33 | 1.2959 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 39011.94 | 39011.94 | 39.66 | 2.947 | 2.947 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00881 | 23.36 | 0.01535 | 0.425 | 0.00 |
CORE_MID | 28647.37 | 28647.37 | 29.13 | 2.162 | 2.162 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 23.36 | 0.01535 | 0.425 | 0.00 |
CORE_TOP | 30111.95 | 30111.95 | 30.62 | 2.294 | 2.294 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00890 | 30.99 | 0.01536 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9456.33 | 9456.33 | 45.61 | 0.720 | 0.720 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00918 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11115.19 | 11115.19 | 84.68 | 0.847 | 0.847 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00889 | 25.97 | 0.01536 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13807.87 | 13807.87 | 66.60 | 1.052 | 1.052 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00898 | 31.02 | 0.01536 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12344.94 | 12344.94 | 94.05 | 0.940 | 0.940 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00885 | 29.54 | 0.01536 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7290.94 | 7290.94 | 35.16 | 0.555 | 0.555 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00913 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8981.06 | 8981.06 | 68.42 | 0.684 | 0.684 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00884 | 26.57 | 0.01536 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10847.61 | 10847.61 | 52.32 | 0.826 | 0.826 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00893 | 31.11 | 0.01536 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9693.54 | 9693.54 | 73.85 | 0.738 | 0.738 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00882 | 28.39 | 0.01536 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8210.70 | 8210.70 | 39.60 | 0.626 | 0.626 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00920 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10843.23 | 10843.23 | 82.61 | 0.826 | 0.826 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00886 | 25.37 | 0.01535 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12474.73 | 12474.73 | 60.17 | 0.950 | 0.950 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00897 | 30.93 | 0.01536 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11344.71 | 11344.71 | 86.43 | 0.864 | 0.864 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00884 | 29.36 | 0.01536 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 11655.88 | 11655.88 | 11.85 | 0.516 | 0.516 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
CORE_MID | 21213.66 | 21213.66 | 21.57 | 0.944 | 0.944 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
CORE_TOP | 35806.03 | 35806.03 | 36.41 | 1.598 | 1.598 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 18271.88 | 18271.88 | 88.13 | 0.817 | 0.817 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11852.37 | 11852.37 | 90.30 | 0.530 | 0.530 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 18085.57 | 18085.57 | 87.23 | 0.809 | 0.809 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11968.18 | 11968.18 | 91.18 | 0.535 | 0.535 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 13413.32 | 13413.32 | 64.69 | 0.600 | 0.600 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8759.61 | 8759.61 | 66.73 | 0.392 | 0.392 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 13268.35 | 13268.35 | 63.99 | 0.593 | 0.593 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8855.73 | 8855.73 | 67.47 | 0.396 | 0.396 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 14277.49 | 14277.49 | 68.86 | 0.638 | 0.638 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9300.83 | 9300.83 | 70.86 | 0.416 | 0.416 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 14115.28 | 14115.28 | 68.08 | 0.631 | 0.631 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9399.38 | 9399.38 | 71.61 | 0.420 | 0.420 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -26.20 | 0.00036 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.10 | 5.10 | 2.50 | 2.50 | 5.0952 | 2.4968 | 5.0952 | 0.4900 | 0.3000 |
PACU_VAV_MID | 4.57 | 4.57 | 3.05 | 3.05 | 4.5747 | 3.0504 | 4.5747 | 0.6668 | 0.3000 |
PACU_VAV_TOP | 5.29 | 5.29 | 4.29 | 4.29 | 5.2884 | 4.2905 | 5.2884 | 0.8113 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 24974.612 | 24974.612 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24974.61 | 16436.34 | 0.515949 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 11655.88 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 30086.820 | 30086.820 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30086.82 | 30086.82 | 0.944448 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 21213.66 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 50916.308 | 50916.308 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 50916.31 | 50916.31 | 1.598301 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3290 | 35806.03 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 26040.251 | 26040.251 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26040.25 | 26040.25 | 0.817423 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00753990 | 46.5351 | 18271.88 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 16891.977 | 16891.977 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16891.98 | 16891.98 | 0.530252 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00752778 | 46.4615 | 11852.37 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 25774.302 | 25774.302 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25774.30 | 25774.30 | 0.809075 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00753547 | 46.5081 | 18085.57 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 17057.297 | 17057.297 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17057.30 | 17057.30 | 0.535441 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00753205 | 46.4875 | 11968.18 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 19107.391 | 19107.391 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19107.39 | 19107.39 | 0.599795 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00766078 | 47.2681 | 13413.32 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 12478.913 | 12478.913 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12478.91 | 12478.91 | 0.391722 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00765449 | 47.2300 | 8759.61 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 18900.421 | 18900.421 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18900.42 | 18900.42 | 0.593298 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00765705 | 47.2454 | 13268.35 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 12616.147 | 12616.147 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12616.15 | 12616.15 | 0.396030 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00765821 | 47.2527 | 8855.73 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 20339.336 | 20339.336 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20339.34 | 20339.34 | 0.638467 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00751202 | 46.3639 | 14277.49 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 13250.402 | 13250.402 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13250.40 | 13250.40 | 0.415940 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00750152 | 46.3001 | 9300.83 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 20107.764 | 20107.764 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20107.76 | 20107.76 | 0.631198 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00750668 | 46.3313 | 14115.28 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 13391.091 | 13391.091 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13391.09 | 13391.09 | 0.420356 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00750646 | 46.3303 | 9399.38 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 111284.411 | 82756.654 | 5.095203 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 113672.74 | 85816.92 | 5.095203 | 25.69 | 18.04 | 0.01042415 | 10.85 | 10.85 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 23.4568 | 24.00 | 0.00890909 | 45.7185 | 66856.38 | 0.00 | 114749.17 | 82278.82 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 51694.367 | 51694.367 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 51694.37 | 51694.37 | 1.528561 | -16.50 | -16.50 | 0.00190279 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 78.1892 | 18.09 | 0.00746153 | 55.1937 | 21635.40 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 103540.477 | 75677.175 | 4.574675 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 106370.33 | 78021.43 | 4.574675 | 25.88 | 18.30 | 0.01068193 | 10.83 | 10.83 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 26.1258 | 24.00 | 0.00902110 | 46.2861 | 59928.12 | 0.00 | 106764.13 | 75326.71 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 52850.195 | 52850.195 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 52850.20 | 52850.20 | 1.372403 | -20.57 | -20.57 | 0.00124923 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 87.0860 | 17.60 | 0.00688953 | 52.5976 | 23423.90 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 115317.881 | 85807.869 | 5.288376 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 117759.55 | 88741.70 | 5.288376 | 25.63 | 18.03 | 0.01043094 | 10.85 | 10.85 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 22.5999 | 24.00 | 0.00898376 | 46.0976 | 69179.58 | 0.00 | 118908.21 | 85314.45 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 51674.466 | 51674.466 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 51674.47 | 51674.47 | 1.586513 | -15.42 | -15.42 | 0.00202936 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 75.3332 | 15.86 | 0.00735509 | 62.6841 | 22358.22 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 24974.612 | 24974.612 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24974.61 | 16436.34 | 1.0000 | 0.59259608 | 0.515949 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24974.61 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 11655.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 30086.820 | 30086.820 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30086.82 | 30086.82 | 1.0000 | 1.08475090 | 0.944448 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30086.82 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 21213.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 50916.308 | 50916.308 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 50916.31 | 50916.31 | 1.0000 | 1.83573776 | 1.598301 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50916.31 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 49.3290 | 35806.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 26040.251 | 26040.251 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26040.25 | 26040.25 | 1.0000 | 0.93885580 | 0.817423 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26040.25 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00753990 | 21.00 | 0.00753990 | 46.5351 | 18271.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 16891.977 | 16891.977 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16891.98 | 16891.98 | 1.0000 | 0.60902374 | 0.530252 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16891.98 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00752778 | 21.00 | 0.00752778 | 46.4615 | 11852.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 25774.302 | 25774.302 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25774.30 | 25774.30 | 1.0000 | 0.92926730 | 0.809075 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25774.30 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00753547 | 21.00 | 0.00753547 | 46.5081 | 18085.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 17057.297 | 17057.297 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17057.30 | 17057.30 | 1.0000 | 0.61498419 | 0.535441 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17057.30 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00753205 | 21.00 | 0.00753205 | 46.4875 | 11968.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 19107.391 | 19107.391 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19107.39 | 19107.39 | 1.0000 | 0.68889832 | 0.599795 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19107.39 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00766078 | 21.00 | 0.00766078 | 47.2681 | 13413.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 12478.913 | 12478.913 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12478.91 | 12478.91 | 1.0000 | 0.44991500 | 0.391722 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12478.91 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00765449 | 21.00 | 0.00765449 | 47.2300 | 8759.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 18900.421 | 18900.421 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18900.42 | 18900.42 | 1.0000 | 0.68143621 | 0.593298 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18900.42 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00765705 | 21.00 | 0.00765705 | 47.2454 | 13268.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 12616.147 | 12616.147 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12616.15 | 12616.15 | 1.0000 | 0.45486285 | 0.396030 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12616.15 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00765821 | 21.00 | 0.00765821 | 47.2527 | 8855.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 20339.336 | 20339.336 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20339.34 | 20339.34 | 1.0000 | 0.73331488 | 0.638467 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20339.34 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00751202 | 21.00 | 0.00751202 | 46.3639 | 14277.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 13250.402 | 13250.402 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13250.40 | 13250.40 | 1.0000 | 0.47773029 | 0.415940 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13250.40 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00750152 | 21.00 | 0.00750152 | 46.3001 | 9300.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 20107.764 | 20107.764 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20107.76 | 20107.76 | 1.0000 | 0.72496579 | 0.631198 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20107.76 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00750668 | 21.00 | 0.00750668 | 46.3313 | 14115.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 13391.091 | 13391.091 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13391.09 | 13391.09 | 1.0000 | 0.48280269 | 0.420356 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13391.09 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00750646 | 21.00 | 0.00750646 | 46.3303 | 9399.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 111284.411 | 82756.654 | 5.095203 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2180 | 1004.8586 | 1.1486 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.095203 | 5.85212457 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 113672.74 | 85816.92 | 1.0215 | 5.85212457 | 5.095203 | 25.69 | 18.04 | 0.01042415 | 52380.7 | 10.85 | 10.85 | 0.00850000 | 32328.0 | -999.0 | -999.00 | -999.00 | -999.00 | 11711.127 | 101961.62 | 31.20 | 0.01536508 | 23.13 | 1.19517000 | 23.4568 | 24.00 | 0.00890909 | 24.00 | 0.00890909 | 45.7185 | 66856.38 | 0.00 | 114749.17 | 82278.82 | 5.62100988 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.34 | 12.33 | 0.00891978 | 34908.1 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 51694.367 | 51694.367 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.095203 | 5.85212457 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 51694.37 | 51694.37 | 1.0000 | 1.75563737 | 1.528561 | -16.50 | -16.50 | 0.00190279 | -11881.9 | 12.80 | 11.18 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51694.37 | -26.20 | 0.00036134 | -26.20 | 1.19517000 | 78.1892 | 18.26 | 0.00742873 | 18.09 | 0.00746153 | 55.1937 | 21635.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 103540.477 | 75677.175 | 4.574675 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6972 | 1004.8586 | 1.1486 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.574675 | 5.25427004 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 106370.33 | 78021.43 | 1.0273 | 5.25427004 | 4.574675 | 25.88 | 18.30 | 0.01068193 | 53237.5 | 10.83 | 10.83 | 0.00850000 | 32316.0 | -999.0 | -999.00 | -999.00 | -999.00 | 10582.993 | 95787.34 | 31.20 | 0.01536508 | 23.13 | 1.19517000 | 26.1258 | 24.00 | 0.00902110 | 24.00 | 0.00902110 | 46.2861 | 59928.12 | 0.00 | 106764.13 | 75326.71 | 5.04676609 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.05 | 12.03 | 0.00874232 | 34167.4 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 52850.195 | 52850.195 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.574675 | 5.25427004 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 52850.20 | 52850.20 | 1.0000 | 1.57628101 | 1.372403 | -20.57 | -20.57 | 0.00124923 | -17589.4 | 12.80 | 11.18 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52850.20 | -26.20 | 0.00036134 | -26.20 | 1.19517000 | 87.0860 | 17.42 | 0.00723668 | 17.60 | 0.00688953 | 52.5976 | 23423.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 115317.881 | 85807.869 | 5.288376 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2306 | 1004.8586 | 1.1486 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.288376 | 6.07399466 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 117759.55 | 88741.70 | 1.0212 | 6.07399466 | 5.288376 | 25.63 | 18.03 | 0.01043094 | 52339.4 | 10.85 | 10.85 | 0.00850000 | 32328.0 | -999.0 | -999.00 | -999.00 | -999.00 | 12155.128 | 105604.42 | 31.20 | 0.01536508 | 23.13 | 1.19517000 | 22.5999 | 24.00 | 0.00898376 | 24.00 | 0.00898376 | 46.0976 | 69179.58 | 0.00 | 118908.21 | 85314.45 | 5.83411778 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.35 | 12.34 | 0.00892702 | 34940.9 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 51674.466 | 51674.466 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.288376 | 6.07399466 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 51674.47 | 51674.47 | 1.0000 | 1.82219840 | 1.586513 | -15.42 | -15.42 | 0.00202936 | -10478.7 | 12.80 | 11.18 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51674.47 | -26.20 | 0.00036134 | -26.20 | 1.19517000 | 75.3332 | 17.50 | 0.00712351 | 15.86 | 0.00735509 | 62.6841 | 22358.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.10 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.57 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.29 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2585.17 | 3148.67 | 517.17 |
CORE_MID | 3203.67 | 3725.17 | 1507.33 |
CORE_TOP | 3575.33 | 3959.33 | 2054.17 |
PERIMETER_TOP_ZN_3 | 4151.17 | 4268.33 | 2782.83 |
PERIMETER_TOP_ZN_2 | 4113.33 | 4141.00 | 2600.67 |
PERIMETER_TOP_ZN_1 | 3803.50 | 3961.33 | 2266.83 |
PERIMETER_TOP_ZN_4 | 4055.33 | 4250.83 | 2659.17 |
PERIMETER_BOT_ZN_3 | 3841.50 | 4315.17 | 2559.17 |
PERIMETER_BOT_ZN_2 | 3961.83 | 4037.17 | 2356.67 |
PERIMETER_BOT_ZN_1 | 3765.17 | 4358.67 | 2506.67 |
PERIMETER_BOT_ZN_4 | 3899.17 | 4096.00 | 2352.50 |
PERIMETER_MID_ZN_3 | 3989.17 | 4017.67 | 2421.83 |
PERIMETER_MID_ZN_2 | 3353.67 | 3434.50 | 2040.67 |
PERIMETER_MID_ZN_1 | 3651.67 | 3692.00 | 1910.83 |
PERIMETER_MID_ZN_4 | 3902.83 | 4019.17 | 2332.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5150.67 | 4928.33 | 3288.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.50 | 1.83 | 0.50 | 0.67 |
CORE_MID | 2.83 | 0.17 | 1.83 | 0.17 |
CORE_TOP | 15.83 | 0.00 | 11.50 | 0.00 |
PERIMETER_TOP_ZN_3 | 297.00 | 4.17 | 133.67 | 2.50 |
PERIMETER_TOP_ZN_2 | 196.17 | 20.50 | 46.67 | 19.83 |
PERIMETER_TOP_ZN_1 | 171.50 | 22.67 | 43.83 | 20.83 |
PERIMETER_TOP_ZN_4 | 190.00 | 27.00 | 46.67 | 15.67 |
PERIMETER_BOT_ZN_3 | 180.00 | 0.00 | 123.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 59.67 | 12.33 | 11.00 | 12.33 |
PERIMETER_BOT_ZN_1 | 728.83 | 29.50 | 686.33 | 29.50 |
PERIMETER_BOT_ZN_4 | 60.50 | 18.33 | 12.67 | 9.67 |
PERIMETER_MID_ZN_3 | 178.50 | 0.67 | 91.33 | 0.00 |
PERIMETER_MID_ZN_2 | 99.33 | 19.50 | 17.83 | 19.50 |
PERIMETER_MID_ZN_1 | 78.00 | 21.33 | 14.17 | 20.67 |
PERIMETER_MID_ZN_4 | 100.33 | 25.83 | 20.17 | 14.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1027.50 | 125.67 | 783.67 | 103.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.885 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.657 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.657 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.819 | 0.123 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 1.254 | 0.129 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 1.083 | 0.123 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 1.283 | 0.129 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.693 | 0.065 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 1.017 | 0.069 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.880 | 1.363 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 1.010 | 0.069 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.757 | 0.102 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 1.145 | 0.114 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 1.037 | 0.103 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 1.207 | 0.108 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.55 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.93 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 14209039.02 | 0.00 | 14209039.02 | 0.00 | 14209039.02 | 13393058.27 | 6208.84 | 36.37 | 2514.79 | 368.74 |
CORE_MID | 10549897.12 | 0.00 | 10549897.12 | 0.00 | 10549897.12 | 13393058.27 | 6672.30 | 22.40 | 2065.30 | 342.91 |
CORE_TOP | 10495912.99 | 0.00 | 10495912.99 | 0.00 | 10495912.99 | 13393058.27 | 6614.43 | 26.63 | 2118.95 | 109.26 |
PERIMETER_TOP_ZN_3 | 2758574.21 | 0.00 | 2758574.21 | 834711.09 | 3593285.31 | 2823374.22 | 4145.48 | 27.34 | 4587.18 | 109.26 |
PERIMETER_TOP_ZN_2 | 2667296.54 | 0.00 | 2667296.54 | 556470.72 | 3223767.26 | 1787429.43 | 4089.19 | 2.16 | 4668.65 | 109.26 |
PERIMETER_TOP_ZN_1 | 3633849.67 | 0.00 | 3633849.67 | 834711.09 | 4468560.77 | 2823374.22 | 4104.94 | 0.91 | 4654.15 | 109.26 |
PERIMETER_TOP_ZN_4 | 2743394.85 | 0.00 | 2743394.85 | 556470.72 | 3299865.57 | 1787312.18 | 4087.56 | 3.14 | 4669.30 | 109.26 |
PERIMETER_BOT_ZN_3 | 2371845.05 | 0.00 | 2371845.05 | 443809.51 | 2815654.56 | 2823374.22 | 5045.19 | 118.28 | 3596.53 | 368.74 |
PERIMETER_BOT_ZN_2 | 2186435.82 | 0.00 | 2186435.82 | 295871.23 | 2482307.05 | 1787429.43 | 4137.20 | 15.70 | 4607.10 | 368.74 |
PERIMETER_BOT_ZN_1 | 2996790.92 | 0.00 | 2996790.92 | 4810592.74 | 7807383.67 | 2823374.22 | 5068.80 | 37.53 | 3653.67 | 368.74 |
PERIMETER_BOT_ZN_4 | 2182226.92 | 0.00 | 2182226.92 | 295871.23 | 2478098.15 | 1787312.18 | 4156.50 | 18.11 | 4585.39 | 368.74 |
PERIMETER_MID_ZN_3 | 2555520.46 | 0.00 | 2555520.46 | 694831.36 | 3250351.82 | 2823374.22 | 5783.30 | 42.03 | 2934.68 | 342.88 |
PERIMETER_MID_ZN_2 | 2623405.48 | 0.00 | 2623405.48 | 463218.12 | 3086623.61 | 1787429.43 | 4075.79 | 0.90 | 4683.31 | 1251.88 |
PERIMETER_MID_ZN_1 | 3486250.23 | 0.00 | 3486250.23 | 694831.36 | 4181081.59 | 2823374.22 | 4104.28 | 4.31 | 4651.42 | 342.88 |
PERIMETER_MID_ZN_4 | 2587675.52 | 0.00 | 2587675.52 | 463218.12 | 3050893.64 | 1787312.18 | 4077.31 | 3.94 | 4678.75 | 342.88 |
Total Facility | 68048114.82 | 0.00 | 68048114.82 | 10944607.30 | 78992722.12 | 67843644.98 | 6827.73 | 328.17 | 4811.13 | 1449.54 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6486 | 0.0000 | 0.6486 | 0.0000 | 0.6486 | 0.4247 | 3479.81 | 36.04 | 2427.15 |
CORE_MID | 0.4828 | 0.0000 | 0.4828 | 0.0000 | 0.4828 | 0.4247 | 3917.23 | 22.40 | 2003.37 |
CORE_TOP | 0.4824 | 0.0000 | 0.4824 | 0.0000 | 0.4824 | 0.4247 | 3855.33 | 26.63 | 2061.04 |
PERIMETER_TOP_ZN_3 | 0.1270 | 0.0000 | 0.1270 | 0.0192 | 0.1462 | 0.0895 | 1386.38 | 27.34 | 4529.28 |
PERIMETER_TOP_ZN_2 | 0.1230 | 0.0000 | 0.1230 | 0.0128 | 0.1357 | 0.0567 | 1330.09 | 2.16 | 4610.75 |
PERIMETER_TOP_ZN_1 | 0.1677 | 0.0000 | 0.1677 | 0.0192 | 0.1869 | 0.0895 | 1345.84 | 0.91 | 4596.25 |
PERIMETER_TOP_ZN_4 | 0.1259 | 0.0000 | 0.1259 | 0.0128 | 0.1387 | 0.0567 | 1328.46 | 3.14 | 4611.40 |
PERIMETER_BOT_ZN_3 | 0.1076 | 0.0000 | 0.1076 | 0.0102 | 0.1178 | 0.0895 | 2317.78 | 117.89 | 3507.33 |
PERIMETER_BOT_ZN_2 | 0.0997 | 0.0000 | 0.0997 | 0.0068 | 0.1065 | 0.0567 | 1410.03 | 15.68 | 4517.29 |
PERIMETER_BOT_ZN_1 | 0.1370 | 0.0000 | 0.1370 | 0.2143 | 0.3513 | 0.0895 | 2339.52 | 37.14 | 3566.34 |
PERIMETER_BOT_ZN_4 | 0.0991 | 0.0000 | 0.0991 | 0.0068 | 0.1059 | 0.0567 | 1429.38 | 18.11 | 4495.52 |
PERIMETER_MID_ZN_3 | 0.1172 | 0.0000 | 0.1172 | 0.0160 | 0.1332 | 0.0895 | 3028.23 | 42.03 | 2872.75 |
PERIMETER_MID_ZN_2 | 0.1124 | 0.0000 | 0.1124 | 0.0113 | 0.1236 | 0.0567 | 1321.03 | 0.87 | 3712.10 |
PERIMETER_MID_ZN_1 | 0.1604 | 0.0000 | 0.1604 | 0.0160 | 0.1764 | 0.0895 | 1349.23 | 4.31 | 4589.46 |
PERIMETER_MID_ZN_4 | 0.1184 | 0.0000 | 0.1184 | 0.0106 | 0.1290 | 0.0567 | 1322.62 | 3.92 | 4616.46 |
Total Facility | 3.1092 | 0.0000 | 3.1092 | 0.3559 | 3.4651 | 2.1513 | 4039.89 | 327.32 | 4691.34 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 31589501.10 | 0.00 | 31589501.10 | 22614548.33 | 4085.42 | 0.49 | 4674.09 | 368.66 |
PACU_VAV_MID | 28761779.04 | 0.00 | 28761779.04 | 22614548.33 | 4081.84 | 0.95 | 4677.21 | 342.58 |
PACU_VAV_TOP | 29416446.47 | 0.00 | 29416446.47 | 22614548.33 | 4091.91 | 0.90 | 4667.19 | 108.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.4406 | 0.0000 | 1.4406 | 0.7171 | 1358.00 | 0.49 | 4584.50 |
PACU_VAV_MID | 1.3182 | 0.0000 | 1.3182 | 0.7171 | 1326.77 | 0.95 | 4615.28 |
PACU_VAV_TOP | 1.3535 | 0.0000 | 1.3535 | 0.7171 | 1332.81 | 0.90 | 4609.29 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.17 | 2885.97 | 0.00 | 0.00 | 0.00 | 2283.87 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.33 | 2727.29 | 0.00 | 0.00 | 0.00 | 2478.17 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2468.23 | 0.00 | 0.00 | 0.00 | 2416.30 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.4599 | 0.0000 | 0.0000 | 0.0000 | 1.0376 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.2076 | 0.0000 | 0.0000 | 0.0000 | 1.0367 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.3443 | 0.0000 | 0.0000 | 0.0000 | 1.0403 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 824 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1822.26 | 15539.06 | 12-MAR-17:10 | 260351.92 | 02-JAN-07:10 |
Electricity:Building | 1043.00 | 15341.49 | 01-JAN-09:40 | 75356.56 | 03-NOV-07:10 |
Electricity:Zone:CORE_BOTTOM | 310.83 | 4652.71 | 01-JAN-00:10 | 24063.48 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1043.00 | 15341.49 | 01-JAN-09:40 | 75356.56 | 03-NOV-07:10 |
InteriorLights:Electricity | 280.96 | 1316.11 | 01-JAN-09:40 | 28079.40 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 280.96 | 1316.11 | 01-JAN-09:40 | 28079.40 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 280.96 | 1316.11 | 01-JAN-09:40 | 28079.40 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 280.96 | 1316.11 | 01-JAN-09:40 | 28079.40 | 02-JAN-16:40 |
Electricity:Zone:CORE_MID | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 35.96 | 541.99 | 01-JAN-09:40 | 2674.44 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.27 | 40.03 | 01-JAN-09:40 | 1168.55 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.27 | 40.03 | 01-JAN-09:40 | 1168.55 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 22.75 | 343.10 | 01-JAN-09:10 | 1693.08 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.86 | 25.34 | 01-JAN-09:10 | 739.79 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.86 | 25.34 | 01-JAN-09:10 | 739.79 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 35.90 | 541.99 | 01-JAN-09:20 | 2674.43 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.21 | 40.03 | 01-JAN-09:20 | 1168.55 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.21 | 40.03 | 01-JAN-09:20 | 1168.55 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 22.74 | 343.10 | 01-JAN-09:40 | 1693.03 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.84 | 25.34 | 01-JAN-09:40 | 739.74 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.84 | 25.34 | 01-JAN-09:40 | 739.74 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 35.95 | 541.99 | 01-JAN-09:40 | 2674.44 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.26 | 40.03 | 01-JAN-09:40 | 1168.55 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.26 | 40.03 | 01-JAN-09:40 | 1168.55 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 22.75 | 343.10 | 01-JAN-09:10 | 1693.08 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.85 | 25.34 | 01-JAN-09:10 | 739.79 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.85 | 25.34 | 01-JAN-09:10 | 739.79 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 35.89 | 541.99 | 01-JAN-09:10 | 2674.43 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.20 | 40.03 | 01-JAN-09:10 | 1168.55 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.20 | 40.03 | 01-JAN-09:10 | 1168.55 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 22.73 | 343.10 | 01-JAN-09:30 | 1693.03 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.84 | 25.34 | 01-JAN-09:30 | 739.74 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.84 | 25.34 | 01-JAN-09:30 | 739.74 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 35.96 | 541.99 | 01-JAN-09:40 | 2674.44 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.27 | 40.03 | 01-JAN-09:40 | 1168.55 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.27 | 40.03 | 01-JAN-09:40 | 1168.55 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 22.75 | 343.10 | 01-JAN-09:10 | 1693.08 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.86 | 25.34 | 01-JAN-09:10 | 739.79 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.86 | 25.34 | 01-JAN-09:10 | 739.79 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 35.90 | 541.99 | 01-JAN-09:20 | 2674.43 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.21 | 40.03 | 01-JAN-09:20 | 1168.55 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.21 | 40.03 | 01-JAN-09:20 | 1168.55 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 22.74 | 343.10 | 01-JAN-09:40 | 1693.03 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.84 | 25.34 | 01-JAN-09:40 | 739.74 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.84 | 25.34 | 01-JAN-09:40 | 739.74 | 02-JAN-16:40 |
InteriorEquipment:Electricity | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 247.34 | 4344.73 | 01-JAN-00:10 | 18520.31 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 707.27 | 197.57 | 08-JUL-18:20 | 223580.81 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 927.80 | 03-NOV-07:20 |
Transformer:ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 927.80 | 03-NOV-07:20 |
ElectricityPurchased:Facility | 1822.26 | 15539.06 | 10-JUN-18:20 | 260351.92 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1822.26 | 15539.06 | 10-JUN-18:20 | 260351.92 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1822.26 | 15539.06 | 10-JUN-18:20 | 260351.92 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1822.26 | 15539.06 | 10-JUN-18:20 | 260351.92 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1822.26 | 15539.06 | 10-JUN-18:20 | 260351.92 | 02-JAN-07:10 |
ElectricityNet:Plant | 1822.26 | 15539.06 | 10-JUN-18:20 | 260351.92 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1822.26 | 15539.06 | 10-JUN-18:20 | 260351.92 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1822.26 | 15539.06 | 10-JUN-18:20 | 260351.92 | 02-JAN-07:10 |
Heating:Electricity | 437.78 | 0.00 | 01-JAN-00:40 | 215582.80 | 02-JAN-07:10 |
General:Heating:Electricity | 437.78 | 0.00 | 01-JAN-00:40 | 215582.80 | 02-JAN-07:10 |
Fans:Electricity | 100.37 | 0.00 | 01-JAN-00:40 | 32062.24 | 26-JUN-15:50 |
General:Fans:Electricity | 100.37 | 0.00 | 01-JAN-00:40 | 32062.24 | 26-JUN-15:50 |
ExteriorLights:Electricity | 71.98 | 0.00 | 01-JAN-08:00 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 71.98 | 0.00 | 01-JAN-08:00 | 5557.43 | 01-JAN-06:10 |
Cooling:Electricity | 156.14 | 0.00 | 01-JAN-00:10 | 84477.23 | 04-AUG-15:30 |
General:Cooling:Electricity | 156.14 | 0.00 | 01-JAN-00:10 | 84477.23 | 04-AUG-15:30 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 7.89 | 0.00 | 01-JAN-00:10 | 789.03 | 02-JAN-16:50 |
WIRED_INT_EQUIP | 641.94 | 12061.80 | 01-JAN-00:10 | 36271.65 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 492.32 | 1156.00 | 06-JAN-05:20 | 199639.57 | 02-FEB-07:40 |
NaturalGas:HVAC | 376.29 | 0.00 | 01-JAN-00:40 | 191716.84 | 02-FEB-07:30 |
Heating:NaturalGas | 376.29 | 0.00 | 01-JAN-00:40 | 191716.84 | 02-FEB-07:30 |
General:Heating:NaturalGas | 376.29 | 0.00 | 01-JAN-00:40 | 191716.84 | 02-FEB-07:30 |
NaturalGas:Plant | 116.03 | 1156.00 | 02-JAN-07:20 | 12054.05 | 21-FEB-12:40 |
WaterSystems:NaturalGas | 116.03 | 1156.00 | 02-JAN-07:20 | 12054.05 | 21-FEB-12:40 |
Water Heater:WaterSystems:NaturalGas | 116.03 | 1156.00 | 02-JAN-07:20 | 12054.05 | 21-FEB-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2677.30 | 0.00 | 01-JAN-00:40 | 545049.18 | 30-JAN-07:10 |
EnergyTransfer:Building | 1248.79 | 0.00 | 01-JAN-00:40 | 216483.44 | 30-JAN-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 203.75 | 0.00 | 01-JAN-00:40 | 27432.50 | 04-AUG-08:00 |
Heating:EnergyTransfer | 397.98 | 0.00 | 01-JAN-00:40 | 215795.66 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.62 | 0.00 | 01-JAN-00:10 | 19302.65 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 397.98 | 0.00 | 01-JAN-00:40 | 215795.66 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.62 | 0.00 | 01-JAN-00:10 | 19302.65 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 850.81 | 0.00 | 01-JAN-00:40 | 169926.72 | 04-AUG-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 203.14 | 0.00 | 01-JAN-00:40 | 27432.50 | 04-AUG-08:00 |
General:Cooling:EnergyTransfer | 850.81 | 0.00 | 01-JAN-00:40 | 169926.72 | 04-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 203.14 | 0.00 | 01-JAN-00:40 | 27432.50 | 04-AUG-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 74.07 | 0.00 | 01-JAN-00:40 | 20042.60 | 02-FEB-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 48.97 | 0.00 | 01-JAN-00:40 | 20042.60 | 02-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 48.97 | 0.00 | 01-JAN-00:40 | 20042.60 | 02-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 25.10 | 0.00 | 01-JAN-00:10 | 11473.06 | 26-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 25.10 | 0.00 | 01-JAN-00:10 | 11473.06 | 26-JUN-14:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 35.06 | 0.00 | 01-JAN-00:40 | 11041.84 | 11-DEC-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 21.27 | 0.00 | 01-JAN-00:40 | 11041.84 | 11-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 21.27 | 0.00 | 01-JAN-00:40 | 11041.84 | 11-DEC-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.79 | 0.00 | 01-JAN-00:10 | 5524.46 | 26-JUN-15:40 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.79 | 0.00 | 01-JAN-00:10 | 5524.46 | 26-JUN-15:40 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 32.32 | 0.00 | 01-JAN-00:40 | 8778.38 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 14.91 | 0.00 | 01-JAN-00:40 | 8778.38 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 14.91 | 0.00 | 01-JAN-00:40 | 8778.38 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.41 | 0.00 | 01-JAN-00:10 | 5699.86 | 26-JUN-15:50 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.41 | 0.00 | 01-JAN-00:10 | 5699.86 | 26-JUN-15:50 |
EnergyTransfer:Zone:CORE_MID | 136.63 | 0.00 | 01-JAN-00:40 | 26074.70 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 6.09 | 0.00 | 01-JAN-00:20 | 26074.70 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 6.09 | 0.00 | 01-JAN-00:20 | 26074.70 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 130.55 | 0.00 | 01-JAN-00:40 | 18620.08 | 05-JUL-09:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 130.55 | 0.00 | 01-JAN-00:40 | 18620.08 | 05-JUL-09:20 |
EnergyTransfer:Zone:CORE_TOP | 140.12 | 0.00 | 01-JAN-00:40 | 29375.74 | 11-DEC-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 21.71 | 0.00 | 01-JAN-00:40 | 29375.74 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 21.71 | 0.00 | 01-JAN-00:40 | 29375.74 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 118.41 | 0.00 | 01-JAN-00:20 | 21001.68 | 26-JUN-13:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 118.41 | 0.00 | 01-JAN-00:20 | 21001.68 | 26-JUN-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 64.72 | 0.00 | 01-JAN-00:40 | 11983.29 | 30-JAN-05:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.27 | 0.00 | 01-JAN-00:40 | 11983.29 | 30-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.27 | 0.00 | 01-JAN-00:40 | 11983.29 | 30-JAN-05:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 25.45 | 0.00 | 01-JAN-00:10 | 7626.84 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 25.45 | 0.00 | 01-JAN-00:10 | 7626.84 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.75 | 0.00 | 01-JAN-00:40 | 11217.70 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 23.17 | 0.00 | 01-JAN-00:40 | 11217.70 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 23.17 | 0.00 | 01-JAN-00:40 | 11217.70 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 26.58 | 0.00 | 01-JAN-00:20 | 9310.94 | 26-JUN-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 26.58 | 0.00 | 01-JAN-00:20 | 9310.94 | 26-JUN-08:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 70.04 | 0.00 | 01-JAN-00:40 | 14510.36 | 09-DEC-05:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 28.30 | 0.00 | 01-JAN-00:40 | 14510.36 | 09-DEC-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 28.30 | 0.00 | 01-JAN-00:40 | 14510.36 | 09-DEC-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 41.74 | 0.00 | 01-JAN-00:20 | 14043.81 | 07-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 41.74 | 0.00 | 01-JAN-00:20 | 14043.81 | 07-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 51.38 | 0.00 | 01-JAN-00:40 | 11758.33 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 24.12 | 0.00 | 01-JAN-00:40 | 11758.33 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 24.12 | 0.00 | 01-JAN-00:40 | 11758.33 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 27.26 | 0.00 | 01-JAN-00:20 | 9802.82 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 27.26 | 0.00 | 01-JAN-00:20 | 9802.82 | 05-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 46.10 | 0.00 | 01-JAN-00:40 | 8451.69 | 30-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 24.22 | 0.00 | 01-JAN-00:40 | 8451.69 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 24.22 | 0.00 | 01-JAN-00:40 | 8451.69 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 21.88 | 0.00 | 01-JAN-00:10 | 5768.19 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 21.88 | 0.00 | 01-JAN-00:10 | 5768.19 | 04-AUG-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 36.90 | 0.00 | 01-JAN-00:40 | 8371.06 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 13.68 | 0.00 | 01-JAN-00:40 | 8371.06 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 13.68 | 0.00 | 01-JAN-00:40 | 8371.06 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 23.22 | 0.00 | 01-JAN-00:20 | 7340.30 | 05-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 23.22 | 0.00 | 01-JAN-00:20 | 7340.30 | 05-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 79.65 | 0.00 | 01-JAN-00:40 | 19757.91 | 02-FEB-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 50.90 | 0.00 | 01-JAN-00:40 | 19757.91 | 02-FEB-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 50.90 | 0.00 | 01-JAN-00:40 | 19757.91 | 02-FEB-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 28.75 | 0.00 | 01-JAN-00:20 | 12670.16 | 07-SEP-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 28.75 | 0.00 | 01-JAN-00:20 | 12670.16 | 07-SEP-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 37.47 | 0.00 | 01-JAN-00:40 | 8911.58 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 14.17 | 0.00 | 01-JAN-00:40 | 8911.58 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 14.17 | 0.00 | 01-JAN-00:40 | 8911.58 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 23.31 | 0.00 | 01-JAN-00:20 | 7557.42 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 23.31 | 0.00 | 01-JAN-00:20 | 7557.42 | 05-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 49.35 | 0.00 | 01-JAN-00:40 | 9075.95 | 30-JAN-05:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 23.30 | 0.00 | 01-JAN-00:40 | 9075.95 | 30-JAN-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 23.30 | 0.00 | 01-JAN-00:40 | 9075.95 | 30-JAN-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.05 | 0.00 | 01-JAN-00:10 | 6916.75 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.05 | 0.00 | 01-JAN-00:10 | 6916.75 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 41.10 | 0.00 | 01-JAN-00:40 | 9457.17 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 13.80 | 0.00 | 01-JAN-00:40 | 9457.17 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 13.80 | 0.00 | 01-JAN-00:40 | 9457.17 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 27.29 | 0.00 | 01-JAN-00:20 | 9162.12 | 26-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 27.29 | 0.00 | 01-JAN-00:20 | 9162.12 | 26-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 58.41 | 0.00 | 01-JAN-00:40 | 12865.07 | 07-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 15.38 | 0.00 | 01-JAN-00:40 | 12183.19 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 15.38 | 0.00 | 01-JAN-00:40 | 12183.19 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 43.03 | 0.00 | 01-JAN-00:20 | 12865.07 | 07-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 43.03 | 0.00 | 01-JAN-00:20 | 12865.07 | 07-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 41.98 | 0.00 | 01-JAN-00:40 | 9576.98 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 14.12 | 0.00 | 01-JAN-00:40 | 9576.98 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 14.12 | 0.00 | 01-JAN-00:40 | 9576.98 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 27.86 | 0.00 | 01-JAN-00:20 | 9251.70 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 27.86 | 0.00 | 01-JAN-00:20 | 9251.70 | 05-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 55.82 | 0.00 | 01-JAN-00:10 | 7152.22 | 16-FEB-12:30 |
PlantLoopHeatingDemand:Plant | 55.82 | 0.00 | 01-JAN-00:10 | 7152.22 | 16-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 55.82 | 0.00 | 01-JAN-00:10 | 7152.22 | 16-FEB-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 55.82 | 0.00 | 01-JAN-00:10 | 7152.22 | 16-FEB-12:30 |
EnergyTransfer:HVAC | 1372.69 | 0.00 | 01-JAN-00:40 | 365365.87 | 26-JUN-07:50 |
HeatingCoils:EnergyTransfer | 738.81 | 0.00 | 01-JAN-00:40 | 337264.97 | 02-FEB-07:10 |
CoolingCoils:EnergyTransfer | 633.87 | 0.00 | 01-JAN-00:10 | 365365.87 | 26-JUN-07:50 |
EnergyTransfer:Plant | 55.82 | 0.00 | 01-JAN-00:10 | 7152.22 | 16-FEB-12:30 |
WaterSystems:EnergyTransfer | 55.82 | 0.00 | 01-JAN-00:10 | 7152.22 | 16-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 55.82 | 0.00 | 01-JAN-00:10 | 7152.22 | 16-FEB-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.615 | -203.135 | 0.000 | 0.000 | 33.704 | 63.485 | 247.342 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -142.012 |
CORE_MID | 0.000 | 0.000 | 6.087 | -130.545 | 0.000 | 0.000 | 35.170 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -100.797 |
CORE_TOP | 0.000 | 0.000 | 21.708 | -118.414 | 0.000 | 0.000 | 35.815 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -129.195 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 39.268 | -25.454 | 0.000 | 0.000 | 7.709 | 9.272 | 26.688 | 16.821 | 0.000 | 0.110 | 0.001 | 0.000 | -38.398 | 0.000 | -15.124 | -20.892 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 23.169 | -26.577 | 0.000 | 0.000 | 4.838 | 5.857 | 16.895 | 31.483 | 0.000 | 0.071 | 0.000 | 0.000 | -23.820 | 0.000 | -10.192 | -21.724 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 28.295 | -41.743 | 0.000 | 0.000 | 7.529 | 9.207 | 26.688 | 64.786 | 0.000 | 0.100 | 0.001 | 0.000 | -34.841 | 0.000 | -15.588 | -44.434 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 24.122 | -27.261 | 0.000 | 0.000 | 4.884 | 5.842 | 16.895 | 32.882 | 0.000 | 0.069 | 0.000 | 0.000 | -24.694 | 0.000 | -10.229 | -22.511 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 24.218 | -21.881 | 0.000 | 0.000 | 7.691 | 9.258 | 26.688 | 17.156 | 0.000 | 0.074 | 0.000 | 0.000 | -39.144 | 0.000 | -8.306 | -15.754 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 13.682 | -23.221 | 0.000 | 0.000 | 4.802 | 5.851 | 16.895 | 31.664 | 0.000 | 0.041 | 0.000 | 0.000 | -24.607 | 0.000 | -5.652 | -19.455 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 50.903 | -28.745 | 0.000 | 0.000 | 7.875 | 9.198 | 26.688 | 65.885 | 0.000 | 1.678 | 0.000 | 0.000 | -35.408 | 0.000 | -74.069 | -24.006 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 14.165 | -23.306 | 0.000 | 0.000 | 4.837 | 5.836 | 16.895 | 33.111 | 0.000 | 0.039 | 0.000 | 0.000 | -25.509 | 0.000 | -5.676 | -20.392 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 23.295 | -26.050 | 0.000 | 0.000 | 7.620 | 9.272 | 26.688 | 16.562 | 0.000 | 0.095 | 0.000 | 0.000 | -39.931 | 0.000 | -13.060 | -4.491 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 13.804 | -27.293 | 0.000 | 0.000 | 3.554 | 5.857 | 16.895 | 31.307 | 0.000 | 0.063 | 0.000 | 0.000 | -24.734 | 0.000 | -8.777 | -10.676 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 15.381 | -43.028 | 0.000 | 0.000 | 7.428 | 9.207 | 26.688 | 64.481 | 0.000 | 0.085 | 0.000 | 0.000 | -36.352 | 0.000 | -13.490 | -30.401 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 14.120 | -27.857 | 0.000 | 0.000 | 4.832 | 5.842 | 16.895 | 32.733 | 0.000 | 0.059 | 0.000 | 0.000 | -25.675 | 0.000 | -8.818 | -12.131 |
TOPFLOOR_PLENUM | 48.968 | -25.100 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.086 | 0.002 | 0.000 | 0.000 | 0.000 | -22.712 | -1.243 |
MIDFLOOR_PLENUM | 21.272 | -13.787 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.136 | 14.544 | 0.000 | 0.000 | 0.000 | -22.165 | -0.000 |
FIRSTFLOOR_PLENUM | 14.909 | -17.407 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.106 | 20.260 | 0.000 | 0.000 | 0.000 | -17.868 | -0.000 |
Total Facility | 85.149 | -56.294 | 312.832 | -794.510 | 0.000 | 0.000 | 178.287 | 280.956 | 762.041 | 438.871 | 0.000 | 2.813 | 34.810 | 0.000 | -373.112 | 0.000 | -251.725 | -620.112 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 05-JUL-04:02 | 0.00 | 0.00 | 0.00 | -44159.54 | 0.00 | 0.00 | 0.00 | 615.87 | 5138.45 | 0.00 | 0.00 | 0.00 | 38405.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 11-SEP-04:02 | 0.00 | 0.00 | 0.00 | -32749.88 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 28959.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 03-JUL-04:02 | 0.00 | 0.00 | 0.00 | -34740.04 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 30949.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 11-JUN-14:22 | 0.00 | 0.00 | 0.00 | -13070.36 | 0.00 | 0.00 | 27.26 | 40.03 | 501.96 | 3776.25 | 0.00 | 347.50 | 8377.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 11-JUN-09:01 | 0.00 | 0.00 | 0.00 | -15470.06 | 0.00 | 0.00 | 13.69 | 25.34 | 317.77 | 9507.49 | 0.00 | 0.00 | 5649.52 | 0.00 | -0.00 | 0.00 | -43.75 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-13:42 | 0.00 | 0.00 | 0.00 | -19001.57 | 0.00 | 0.00 | 22.47 | 40.03 | 501.96 | 12967.85 | 0.00 | 0.00 | 5675.06 | 0.00 | -0.00 | 0.00 | -205.79 | 0.00 |
PERIMETER_TOP_ZN_4 | 25-JUN-17:21 | 0.00 | 0.00 | 0.00 | -16366.24 | 0.00 | 0.00 | 0.00 | 25.34 | 317.76 | 11010.66 | 0.00 | 183.85 | 4828.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 05-JUL-06:03 | 0.00 | 0.00 | 0.00 | -5916.72 | 0.00 | 0.00 | 149.13 | 240.13 | 669.29 | 2792.50 | 0.00 | 0.00 | 2084.50 | 0.00 | -0.00 | 0.00 | -18.83 | 0.00 |
PERIMETER_BOT_ZN_2 | 02-JUL-09:21 | 0.00 | 0.00 | 0.00 | -12072.73 | 0.00 | 0.00 | 15.44 | 25.34 | 317.77 | 9610.87 | 0.00 | 0.00 | 2134.00 | 0.00 | -0.00 | 0.00 | -30.68 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-13:42 | 0.00 | 0.00 | 0.00 | -14583.60 | 0.00 | 0.00 | 24.54 | 40.03 | 501.96 | 13071.05 | 0.00 | 0.00 | 1048.78 | 0.00 | -0.00 | 0.00 | -102.75 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JUL-18:01 | 0.00 | 0.00 | 0.00 | -13497.31 | 0.00 | 0.00 | 0.00 | 25.34 | 317.76 | 8633.89 | 0.00 | 0.00 | 4527.80 | 0.00 | -0.00 | 0.00 | -7.48 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-19:12 | 0.00 | 0.00 | 0.00 | -10361.26 | 0.00 | 0.00 | 0.00 | 40.03 | 501.96 | 2454.82 | 0.00 | 97.58 | 7266.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-08:41 | 0.00 | 0.00 | 0.00 | -15277.47 | 0.00 | 0.00 | 13.35 | 25.34 | 317.77 | 10743.19 | 0.00 | 0.00 | 4271.72 | 0.00 | -0.00 | 0.00 | -93.90 | 0.00 |
PERIMETER_MID_ZN_1 | 30-JUL-11:52 | 0.00 | 0.00 | 0.00 | -16221.78 | 0.00 | 0.00 | 24.79 | 40.03 | 501.96 | 11417.55 | 0.00 | 0.00 | 4254.19 | 0.00 | -0.00 | 0.00 | -16.73 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JUL-16:41 | 0.00 | 0.00 | 0.00 | -16034.94 | 0.00 | 0.00 | 11.96 | 25.34 | 317.76 | 11193.36 | 0.00 | 0.00 | 4501.64 | 0.00 | -0.00 | 0.00 | -15.12 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-14:00 | 0.00 | -11473.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.72 | 11371.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 26-JUN-15:40 | 0.00 | -5524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.04 | 5426.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 26-JUN-12:10 | 0.00 | -5876.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.17 | 5794.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-JUL-06:03 | 0.00 | -8384.68 | 0.00 | -162591.04 | 0.00 | 0.00 | 3553.34 | 7896.02 | 21853.28 | 7983.04 | 0.00 | 0.00 | 136064.48 | 0.00 | 0.00 | 0.00 | -6374.44 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 22688.52 | 0.00 | 0.00 | 0.00 | 0.00 | 615.87 | 5138.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -28442.84 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 29612.60 | 0.00 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -33403.34 |
CORE_TOP | 30-JAN-04:51 | 0.00 | 0.00 | 32389.70 | 0.00 | 0.00 | 0.00 | 0.00 | 307.97 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -35872.54 |
PERIMETER_TOP_ZN_3 | 11-DEC-05:21 | 0.00 | 0.00 | 12801.19 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3770.39 | 0.00 | -1508.16 | -8321.76 |
PERIMETER_TOP_ZN_2 | 03-FEB-05:11 | 0.00 | 0.00 | 13070.24 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3183.79 | 0.00 | -728.23 | -9664.11 |
PERIMETER_TOP_ZN_1 | 03-FEB-05:11 | 0.00 | 0.00 | 16206.08 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4803.07 | 0.00 | -1093.51 | -11108.61 |
PERIMETER_TOP_ZN_4 | 03-FEB-05:11 | 0.00 | 0.00 | 14476.35 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3269.96 | 0.00 | -729.36 | -10982.90 |
PERIMETER_BOT_ZN_3 | 30-JAN-03:52 | 0.00 | 0.00 | 9118.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4371.52 | 0.00 | -1435.20 | -4045.48 |
PERIMETER_BOT_ZN_2 | 30-JAN-03:52 | 0.00 | 0.00 | 10165.80 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2839.11 | 0.00 | -970.70 | -6820.78 |
PERIMETER_BOT_ZN_1 | 03-FEB-07:10 | 0.00 | 0.00 | 20940.09 | 0.00 | 0.00 | 0.00 | 233.43 | 389.51 | 669.28 | 0.00 | 0.00 | 0.00 | 27855.84 | 0.00 | -4886.55 | 0.00 | -45201.61 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-JAN-03:52 | 0.00 | 0.00 | 10914.33 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2928.87 | 0.00 | -973.88 | -7476.35 |
PERIMETER_MID_ZN_3 | 19-JAN-05:21 | 0.00 | 0.00 | 9685.30 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4599.80 | 0.00 | -3253.97 | -2630.65 |
PERIMETER_MID_ZN_2 | 19-JAN-05:21 | 0.00 | 0.00 | 12191.48 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2974.93 | 0.00 | -2206.75 | -7515.68 |
PERIMETER_MID_ZN_1 | 19-JAN-05:21 | 0.00 | 0.00 | 14056.34 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4476.51 | 0.00 | -3305.73 | -7073.22 |
PERIMETER_MID_ZN_4 | 19-JAN-05:21 | 0.00 | 0.00 | 12765.10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3080.19 | 0.00 | -2205.72 | -7985.06 |
TOPFLOOR_PLENUM | 02-FEB-06:07 | 21122.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -678.22 | -20444.56 |
MIDFLOOR_PLENUM | 11-DEC-07:04 | 11257.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -630.25 | -10626.76 |
FIRSTFLOOR_PLENUM | 02-JAN-07:01 | 9567.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -425.44 | -9142.18 |
Total Facility | 11-DEC-06:01 | 27596.21 | 0.00 | 217581.74 | 0.00 | 0.00 | 0.00 | 2639.39 | 3119.77 | 18045.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -38833.22 | 0.00 | -12947.21 | -217202.65 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.7960 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0952 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.4409 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.5747 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.9504 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.2884 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.8980 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4125 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.7204 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4553 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.9752 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5511 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9473 | 2.9473 | 0.7840 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1617 | 2.1617 | 0.7631 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2937 | 2.2937 | 0.7936 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8174 | 0.8174 | 0.1896 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8468 | 0.8468 | 0.1694 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0519 | 1.0519 | 0.2104 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9405 | 0.9405 | 0.1881 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5998 | 0.5998 | 0.1787 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6842 | 0.6842 | 0.1368 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8264 | 0.8264 | 0.1653 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7384 | 0.7384 | 0.1477 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6385 | 0.6385 | 0.1641 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8261 | 0.8261 | 0.1652 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9504 | 0.9504 | 0.1901 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8643 | 0.8643 | 0.1729 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.7960 | 5.0952 | 5.7960 | 1.4125 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.4409 | 4.5747 | 5.4409 | 1.4553 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.9504 | 5.2884 | 5.9504 | 1.5511 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4736 | 1.4736 | 0.7840 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0809 | 1.0809 | 0.7631 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1469 | 1.1469 | 0.7936 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4087 | 0.4087 | 0.1896 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4234 | 0.4234 | 0.1694 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5260 | 0.5260 | 0.2104 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4702 | 0.4702 | 0.1881 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2999 | 0.2999 | 0.1787 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3421 | 0.3421 | 0.1368 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4132 | 0.4132 | 0.1653 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3692 | 0.3692 | 0.1477 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3192 | 0.3192 | 0.1641 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4130 | 0.4130 | 0.1652 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4752 | 0.4752 | 0.1901 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4321 | 0.4321 | 0.1729 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.8980 | 1.4125 | 1.4125 | 1.4125 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.7204 | 1.4553 | 1.4553 | 1.4553 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.9752 | 1.5511 | 1.5511 | 1.5511 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 783.67 |
Number of hours cooling loads not met | 103.00 |
Number of hours not met | 886.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 437.78 | 215582.80 | 376.29 | 191716.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 156.14 | 84477.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 280.96 | 28079.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 71.98 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 641.30 | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 12.98 | 927.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 100.37 | 32062.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 116.03 | 12054.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 762.04 | 1822.26 |
Natural Gas | 0.00 | 492.32 |
Additional | 0.00 | 0.00 |
Total | 762.04 | 2314.58 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 56.39 |
Space Heating | 87.87 |
Space Cooling | 31.34 |
Fans (All) | 20.15 |
Service Water Heating | 0.00 |
Receptacle Equipment | 152.95 |
Miscellaneous (All) | 365.76 |
Subtotal | 365.76 |
Natural Gas [MJ/m2] | |
Space Heating | 75.53 |
Service Water Heating | 23.29 |
Miscellaneous (All) | 98.82 |
Subtotal | 98.82 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.14 |
Space Heating | 35.17 |
Space Cooling | 6.75 |
Fans (All) | 4.34 |
Service Water Heating | 5.01 |
Receptacle Equipment | 32.92 |
Miscellaneous | 3.67 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2429. | 8760. |
BLDG_EQUIP_SCH | 4487. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8681.83 | 78.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8750.00 | 10.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8742.17 | 17.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8685.50 | 74.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8695.33 | 64.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8659.17 | 100.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8704.00 | 56.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8714.67 | 45.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8678.83 | 81.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8747.00 | 13.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8686.83 | 73.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8692.50 | 67.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8647.00 | 113.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8649.83 | 110.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8647.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 113.00 | 0.00 | 0.00 | 0.00 |
Average | 8709.31 | 50.69 | 0.00 | 0.00 | 0.00 |
Sum | 156767.67 | 912.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128295.67 | 8.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 8.33 | 0.00 | 0.00 | 0.00 |
Average | 34142.87 | 0.46 | 0.00 | 0.00 | 0.00 |
Sum | 614571.67 | 8.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8233.83 | 526.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8391.83 | 368.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8458.83 | 301.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8305.83 | 454.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8268.50 | 491.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8269.67 | 490.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8245.33 | 514.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8454.17 | 305.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8293.17 | 466.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8173.17 | 586.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8244.00 | 516.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8254.67 | 505.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8243.67 | 516.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8220.83 | 539.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8201.50 | 558.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7905.17 | 854.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8285.50 | 474.50 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8323.33 | 436.67 | 0.00 | 0.00 | 0.00 |
Min | 7905.17 | 301.17 | 0.00 | 0.00 | 0.00 |
Max | 8458.83 | 854.83 | 0.00 | 0.00 | 0.00 |
Average | 8265.17 | 494.83 | 0.00 | 0.00 | 0.00 |
Sum | 148773.00 | 8907.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127993.00 | 311.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128145.00 | 159.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128205.67 | 98.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24884.67 | 24.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24898.67 | 10.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24894.50 | 14.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14011.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24103.33 | 805.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14010.00 | 6.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24887.83 | 21.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10131.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24892.33 | 16.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14013.00 | 3.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128205.67 | 805.67 | 0.00 | 0.00 | 0.00 |
Average | 34061.22 | 82.11 | 0.00 | 0.00 | 0.00 |
Sum | 613102.00 | 1478.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.871632E+10 | 9210.60 | 13-JAN-17:00 | 2.20 | 0.77 | 0.164441E+10 | 2606.57 | 13-JAN-14:09 | 2.20 | 0.77 |
February | 0.846097E+10 | 10185.81 | 24-FEB-17:00 | 7.20 | 5.13 | 0.160143E+10 | 2606.61 | 24-FEB-14:20 | 7.20 | 5.13 |
March | 0.120068E+11 | 16825.94 | 29-MAR-07:06 | 7.80 | 6.92 | 0.205534E+10 | 2606.64 | 28-MAR-09:30 | 7.80 | 6.92 |
April | 0.142455E+11 | 29763.45 | 20-APR-05:03 | 2.62 | 0.36 | 0.188202E+10 | 2608.66 | 28-APR-13:09 | 5.00 | 3.48 |
May | 0.205842E+11 | 43105.44 | 30-MAY-04:03 | 14.40 | 14.40 | 0.207428E+10 | 2606.73 | 09-MAY-13:09 | 14.40 | 14.40 |
June | 0.252641E+11 | 43433.80 | 27-JUN-04:03 | 20.50 | 19.04 | 0.206969E+10 | 2606.69 | 01-JUN-09:00 | 20.50 | 19.04 |
July | 0.262953E+11 | 44165.66 | 05-JUL-04:02 | 18.72 | 18.00 | 0.192493E+10 | 2606.66 | 19-JUL-09:09 | 21.28 | 16.97 |
August | 0.277696E+11 | 43427.47 | 14-AUG-04:03 | 16.02 | 15.64 | 0.216080E+10 | 2846.52 | 04-AUG-07:49 | 16.02 | 15.64 |
September | 0.227635E+11 | 43859.91 | 11-SEP-04:02 | 20.50 | 17.33 | 0.191618E+10 | 2606.66 | 06-SEP-09:20 | 20.50 | 17.33 |
October | 0.156372E+11 | 19069.71 | 24-OCT-07:03 | 3.50 | 1.10 | 0.198064E+10 | 2606.65 | 20-OCT-09:09 | 3.50 | 1.10 |
November | 0.120162E+11 | 19252.02 | 02-NOV-07:03 | 6.78 | 5.70 | 0.187573E+10 | 2606.65 | 01-NOV-09:09 | 6.78 | 5.70 |
December | 0.937579E+10 | 9819.79 | 07-DEC-16:15 | -5.7 | -8.8 | 0.170423E+10 | 2606.57 | 06-DEC-14:20 | -5.7 | -8.8 |
Annual Sum or Average | 0.203135E+12 | 0.228897E+11 | ||||||||
Minimum of Months | 0.846097E+10 | 9210.60 | -5.7 | -8.8 | 0.160143E+10 | 2606.57 | -5.7 | -8.8 | ||
Maximum of Months | 0.277696E+11 | 44165.66 | 20.50 | 19.04 | 0.216080E+10 | 2846.52 | 21.28 | 19.04 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 | -3.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 9489667.41 | 619.68 | 24-FEB-14:50 | 8.22 | 5.55 | 0.00 | 0.00 | 01-FEB-00:10 | 8.22 | 5.55 |
March | 0.189431E+09 | 1986.84 | 25-MAR-15:20 | 18.53 | 10.46 | 0.00 | 0.00 | 01-MAR-00:10 | 18.53 | 10.46 |
April | 0.127682E+10 | 8837.61 | 18-APR-14:40 | 28.30 | 20.65 | 0.00 | 0.00 | 01-APR-00:10 | 28.30 | 20.65 |
May | 0.291447E+10 | 9994.70 | 31-MAY-14:00 | 29.40 | 19.44 | 0.00 | 0.00 | 01-MAY-00:10 | 29.40 | 19.44 |
June | 0.550476E+10 | 11473.06 | 26-JUN-14:00 | 31.70 | 22.11 | 0.00 | 0.00 | 01-JUN-00:10 | 31.70 | 22.11 |
July | 0.608660E+10 | 10764.43 | 05-JUL-14:00 | 27.20 | 19.77 | 0.00 | 0.00 | 01-JUL-00:10 | 27.20 | 19.77 |
August | 0.560241E+10 | 11342.45 | 04-AUG-15:20 | 33.90 | 25.66 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 25.66 |
September | 0.299064E+10 | 10209.81 | 07-SEP-15:10 | 31.70 | 18.53 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 18.53 |
October | 0.451833E+09 | 3772.62 | 20-OCT-14:50 | 23.18 | 13.31 | 0.00 | 0.00 | 01-OCT-00:10 | 23.18 | 13.31 |
November | 73557411.34 | 1888.11 | 03-NOV-14:30 | 16.10 | 10.04 | 0.00 | 0.00 | 01-NOV-00:10 | 16.10 | 10.04 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 |
Annual Sum or Average | 0.251000E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.8 | -3.2 | 0.00 | 0.00 | -2.8 | -3.2 | ||
Maximum of Months | 0.608660E+10 | 11473.06 | 33.90 | 25.66 | 0.00 | 0.00 | 33.90 | 25.66 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8607723.13 | 2736.94 | 05-JAN-05:01 | -21.2 | -21.5 | 0.00 | 0.00 | 01-JAN-00:10 | -21.2 | -21.5 |
February | 8606215.20 | 2386.76 | 16-FEB-05:01 | -17.3 | -17.7 | 0.00 | 0.00 | 01-FEB-00:10 | -17.3 | -17.7 |
March | 49588123.46 | 1723.59 | 04-MAR-05:01 | -8.8 | -9.5 | 0.00 | 0.00 | 01-MAR-00:10 | -8.8 | -9.5 |
April | 0.490266E+09 | 3559.95 | 18-APR-15:20 | 27.20 | 20.26 | 0.00 | 0.00 | 01-APR-00:10 | 27.20 | 20.26 |
May | 0.124060E+10 | 4164.60 | 30-MAY-16:00 | 27.80 | 19.90 | 0.00 | 0.00 | 01-MAY-00:10 | 27.80 | 19.90 |
June | 0.310423E+10 | 5524.46 | 26-JUN-15:40 | 31.50 | 22.02 | 0.00 | 0.00 | 01-JUN-00:10 | 31.50 | 22.02 |
July | 0.357539E+10 | 5466.74 | 05-JUL-06:15 | 19.80 | 18.77 | 0.00 | 0.00 | 01-JUL-00:10 | 19.80 | 18.77 |
August | 0.329563E+10 | 4982.37 | 04-AUG-15:20 | 33.90 | 25.66 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 25.66 |
September | 0.176633E+10 | 4654.62 | 08-SEP-16:00 | 29.40 | 18.44 | 0.00 | 0.00 | 01-SEP-00:10 | 29.40 | 18.44 |
October | 0.177538E+09 | 2177.47 | 13-OCT-06:01 | 0.75 | -0.4 | 0.00 | 0.00 | 01-OCT-00:10 | 0.75 | -0.4 |
November | 64902568.02 | 1739.38 | 25-NOV-05:11 | -15.6 | -16.0 | 0.00 | 0.00 | 01-NOV-00:10 | -15.6 | -16.0 |
December | 5661871.14 | 2380.63 | 28-DEC-05:01 | -17.2 | -17.5 | 0.00 | 0.00 | 01-DEC-00:10 | -17.2 | -17.5 |
Annual Sum or Average | 0.137873E+11 | 0.00 | ||||||||
Minimum of Months | 5661871.14 | 1723.59 | -21.2 | -21.5 | 0.00 | 0.00 | -21.2 | -21.5 | ||
Maximum of Months | 0.357539E+10 | 5524.46 | 33.90 | 25.66 | 0.00 | 0.00 | 33.90 | 25.66 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 88712086.71 | 3258.42 | 05-JAN-17:10 | -20.7 | -21.2 | 0.00 | 0.00 | 01-JAN-00:10 | -20.7 | -21.2 |
February | 0.100090E+09 | 4316.50 | 02-FEB-17:10 | -29.6 | -29.9 | 0.00 | 0.00 | 01-FEB-00:10 | -29.6 | -29.9 |
March | 0.176723E+09 | 2460.95 | 22-MAR-06:10 | -6.8 | -7.6 | 0.00 | 0.00 | 01-MAR-00:10 | -6.8 | -7.6 |
April | 0.690070E+09 | 3568.02 | 18-APR-15:10 | 27.75 | 20.46 | 0.00 | 0.00 | 01-APR-00:10 | 27.75 | 20.46 |
May | 0.173885E+10 | 4248.05 | 31-MAY-15:10 | 29.72 | 19.55 | 0.00 | 0.00 | 01-MAY-00:10 | 29.72 | 19.55 |
June | 0.346616E+10 | 5877.00 | 26-JUN-12:10 | 30.68 | 21.60 | 0.00 | 0.00 | 01-JUN-00:10 | 30.68 | 21.60 |
July | 0.405941E+10 | 5755.13 | 05-JUL-06:15 | 19.80 | 18.77 | 0.00 | 0.00 | 01-JUL-00:10 | 19.80 | 18.77 |
August | 0.403441E+10 | 5041.43 | 04-AUG-16:00 | 33.90 | 26.33 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 26.33 |
September | 0.244612E+10 | 5023.36 | 11-SEP-15:30 | 28.05 | 20.01 | 0.00 | 0.00 | 01-SEP-00:10 | 28.05 | 20.01 |
October | 0.372170E+09 | 2422.63 | 31-OCT-06:01 | 0.18 | -0.9 | 0.00 | 0.00 | 01-OCT-00:10 | 0.18 | -0.9 |
November | 0.159590E+09 | 2318.01 | 09-NOV-18:01 | 1.10 | 0.21 | 0.00 | 0.00 | 01-NOV-00:10 | 1.10 | 0.21 |
December | 75303910.70 | 2940.85 | 08-DEC-17:10 | -19.2 | -19.4 | 0.00 | 0.00 | 01-DEC-00:10 | -19.2 | -19.4 |
Annual Sum or Average | 0.174076E+11 | 0.00 | ||||||||
Minimum of Months | 75303910.70 | 2318.01 | -29.6 | -29.9 | 0.00 | 0.00 | -29.6 | -29.9 | ||
Maximum of Months | 0.405941E+10 | 5877.00 | 33.90 | 26.33 | 0.00 | 0.00 | 33.90 | 26.33 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408324E+10 | 6345.89 | 13-JAN-17:00 | 2.20 | 0.77 | 0.148057E+10 | 2270.83 | 13-JAN-14:00 | 2.20 | 0.77 |
February | 0.472326E+10 | 6584.77 | 24-FEB-17:00 | 7.20 | 5.13 | 0.138652E+10 | 2297.84 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.758099E+10 | 7463.68 | 24-MAR-16:00 | 10.60 | 5.50 | 0.179181E+10 | 2557.81 | 24-MAR-13:00 | 10.60 | 5.50 |
April | 0.963458E+10 | 26152.12 | 17-APR-05:03 | 11.42 | 9.68 | 0.173720E+10 | 2606.60 | 18-APR-09:09 | 23.27 | 18.95 |
May | 0.140703E+11 | 26477.21 | 30-MAY-05:03 | 14.50 | 14.50 | 0.204604E+10 | 2606.69 | 09-MAY-13:09 | 14.50 | 14.50 |
June | 0.176684E+11 | 32356.54 | 12-JUN-04:03 | 18.22 | 17.50 | 0.206062E+10 | 2606.66 | 01-JUN-09:00 | 18.22 | 17.50 |
July | 0.188059E+11 | 32292.02 | 03-JUL-04:02 | 18.80 | 17.39 | 0.192092E+10 | 2606.65 | 05-JUL-09:20 | 23.33 | 20.37 |
August | 0.189265E+11 | 31059.54 | 15-AUG-05:03 | 14.82 | 13.87 | 0.215586E+10 | 2694.22 | 04-AUG-07:30 | 14.82 | 13.87 |
September | 0.145470E+11 | 32747.35 | 11-SEP-04:02 | 20.50 | 17.33 | 0.189130E+10 | 2606.68 | 06-SEP-09:09 | 20.50 | 17.33 |
October | 0.912185E+10 | 9502.30 | 20-OCT-16:00 | 21.30 | 12.72 | 0.184161E+10 | 2606.54 | 12-OCT-13:30 | 21.30 | 12.72 |
November | 0.664833E+10 | 9135.16 | 03-NOV-16:00 | 15.00 | 9.33 | 0.164726E+10 | 2582.72 | 03-NOV-13:00 | 15.00 | 9.33 |
December | 0.473468E+10 | 6163.76 | 01-DEC-16:20 | -2.4 | -4.5 | 0.146463E+10 | 2227.95 | 07-DEC-14:00 | -3.3 | -7.2 |
Annual Sum or Average | 0.130545E+12 | 0.214243E+11 | ||||||||
Minimum of Months | 0.408324E+10 | 6163.76 | -2.4 | -4.5 | 0.138652E+10 | 2227.95 | -3.3 | -7.2 | ||
Maximum of Months | 0.189265E+11 | 32747.35 | 21.30 | 17.50 | 0.215586E+10 | 2694.22 | 23.33 | 20.37 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215963E+10 | 6157.85 | 13-JAN-16:50 | 2.48 | 0.97 | 0.145820E+10 | 2176.39 | 13-JAN-14:00 | 2.48 | 0.97 |
February | 0.315541E+10 | 6698.17 | 24-FEB-17:00 | 7.20 | 5.13 | 0.134492E+10 | 2263.75 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.595730E+10 | 7652.17 | 24-MAR-16:00 | 10.60 | 5.50 | 0.170121E+10 | 2510.22 | 24-MAR-13:00 | 10.60 | 5.50 |
April | 0.873332E+10 | 17335.30 | 17-APR-15:30 | 19.40 | 11.54 | 0.165981E+10 | 2607.98 | 19-APR-09:30 | 5.60 | 4.05 |
May | 0.137133E+11 | 20568.26 | 30-MAY-05:03 | 14.50 | 14.50 | 0.201294E+10 | 2606.69 | 09-MAY-13:09 | 14.50 | 14.50 |
June | 0.178935E+11 | 34197.53 | 26-JUN-04:03 | 21.60 | 20.40 | 0.204392E+10 | 2606.67 | 09-JUN-09:30 | 21.60 | 20.40 |
July | 0.189452E+11 | 34743.44 | 03-JUL-04:02 | 18.80 | 17.39 | 0.191628E+10 | 2606.69 | 25-JUL-09:09 | 23.68 | 19.04 |
August | 0.186229E+11 | 32929.47 | 28-AUG-05:03 | 18.40 | 18.00 | 0.214760E+10 | 2606.71 | 08-AUG-09:09 | 18.40 | 18.00 |
September | 0.134362E+11 | 33829.26 | 11-SEP-04:02 | 20.50 | 17.33 | 0.183568E+10 | 2606.72 | 06-SEP-09:39 | 20.50 | 17.33 |
October | 0.790905E+10 | 9097.63 | 20-OCT-16:00 | 21.30 | 12.72 | 0.169584E+10 | 2546.36 | 20-OCT-13:00 | 21.30 | 12.72 |
November | 0.512507E+10 | 8067.81 | 03-NOV-15:50 | 15.18 | 9.38 | 0.154795E+10 | 2537.81 | 03-NOV-15:00 | 15.00 | 9.33 |
December | 0.276303E+10 | 6019.42 | 01-DEC-16:10 | -2.1 | -4.3 | 0.141474E+10 | 2136.09 | 01-DEC-14:00 | -2.1 | -4.3 |
Annual Sum or Average | 0.118414E+12 | 0.207791E+11 | ||||||||
Minimum of Months | 0.215963E+10 | 6019.42 | -2.1 | -4.3 | 0.134492E+10 | 2136.09 | -2.1 | -4.3 | ||
Maximum of Months | 0.189452E+11 | 34743.44 | 21.60 | 20.40 | 0.214760E+10 | 2607.98 | 23.68 | 20.40 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12237976.50 | 1090.91 | 21-JAN-17:02 | -3.9 | -4.9 | 0.301802E+09 | 406.71 | 18-JAN-14:00 | -3.9 | -4.9 |
February | 37791789.90 | 1251.53 | 24-FEB-16:20 | 7.93 | 5.63 | 0.274767E+09 | 411.98 | 24-FEB-14:00 | 7.93 | 5.63 |
March | 0.430294E+09 | 1643.13 | 28-MAR-15:30 | 16.40 | 10.50 | 0.338075E+09 | 487.04 | 28-MAR-15:39 | 16.13 | 10.43 |
April | 0.138680E+10 | 5843.35 | 18-APR-15:00 | 28.30 | 20.65 | 0.323635E+09 | 549.50 | 18-APR-09:09 | 28.30 | 20.65 |
May | 0.327679E+10 | 6387.18 | 31-MAY-15:00 | 30.00 | 19.70 | 0.409681E+09 | 549.50 | 09-MAY-13:09 | 30.00 | 19.70 |
June | 0.518849E+10 | 13072.67 | 11-JUN-14:22 | 32.50 | 24.45 | 0.425919E+09 | 549.50 | 09-JUN-09:30 | 32.50 | 24.45 |
July | 0.545461E+10 | 8738.58 | 02-JUL-18:12 | 27.93 | 21.01 | 0.403312E+09 | 549.50 | 25-JUL-09:09 | 23.68 | 19.04 |
August | 0.512313E+10 | 7108.96 | 04-AUG-15:30 | 33.90 | 25.83 | 0.448831E+09 | 549.51 | 30-AUG-13:00 | 23.90 | 18.14 |
September | 0.305196E+10 | 6319.43 | 11-SEP-14:00 | 28.90 | 20.23 | 0.368401E+09 | 549.51 | 06-SEP-09:39 | 28.90 | 20.23 |
October | 0.104066E+10 | 1841.50 | 20-OCT-13:40 | 22.33 | 12.89 | 0.325608E+09 | 522.75 | 20-OCT-15:00 | 21.30 | 12.72 |
November | 0.441466E+09 | 1656.28 | 03-NOV-15:30 | 15.55 | 9.47 | 0.308872E+09 | 493.65 | 03-NOV-13:00 | 15.55 | 9.47 |
December | 10182819.51 | 1109.08 | 02-DEC-17:03 | 1.70 | 0.90 | 0.292730E+09 | 406.74 | 08-DEC-14:00 | -15.6 | -15.9 |
Annual Sum or Average | 0.254544E+11 | 0.422163E+10 | ||||||||
Minimum of Months | 10182819.51 | 1090.91 | -3.9 | -4.9 | 0.274767E+09 | 406.71 | -15.6 | -15.9 | ||
Maximum of Months | 0.545461E+10 | 13072.67 | 33.90 | 25.83 | 0.448831E+09 | 549.51 | 32.50 | 24.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36446922.84 | 967.02 | 21-JAN-17:02 | -3.9 | -4.9 | 0.192651E+09 | 257.48 | 30-JAN-14:39 | -24.1 | -24.4 |
February | 0.131063E+09 | 1458.42 | 24-FEB-10:15 | 4.80 | 1.70 | 0.176263E+09 | 316.26 | 24-FEB-10:30 | 5.00 | 1.88 |
March | 0.655387E+09 | 2313.61 | 28-MAR-09:35 | 9.07 | 5.68 | 0.221348E+09 | 347.88 | 28-MAR-09:50 | 9.53 | 5.99 |
April | 0.160658E+10 | 7791.57 | 18-APR-09:30 | 24.20 | 19.59 | 0.213666E+09 | 347.89 | 18-APR-09:09 | 24.20 | 19.59 |
May | 0.345862E+10 | 10734.81 | 29-MAY-08:53 | 22.20 | 18.24 | 0.266929E+09 | 348.40 | 31-MAY-09:00 | 27.20 | 19.40 |
June | 0.523035E+10 | 15465.54 | 11-JUN-09:01 | 26.88 | 21.15 | 0.269130E+09 | 348.42 | 26-JUN-09:00 | 28.30 | 22.44 |
July | 0.553322E+10 | 14191.78 | 02-JUL-09:32 | 26.33 | 21.34 | 0.255959E+09 | 348.61 | 05-JUL-09:39 | 23.87 | 20.31 |
August | 0.505418E+10 | 11767.02 | 27-AUG-09:02 | 23.07 | 19.49 | 0.285464E+09 | 348.46 | 02-AUG-09:00 | 23.07 | 19.49 |
September | 0.331364E+10 | 11095.58 | 03-SEP-09:32 | 17.93 | 13.10 | 0.239886E+09 | 347.90 | 06-SEP-09:39 | 24.67 | 18.11 |
October | 0.113370E+10 | 2786.94 | 20-OCT-09:50 | 14.70 | 9.97 | 0.213013E+09 | 347.88 | 20-OCT-09:09 | 14.70 | 9.97 |
November | 0.404577E+09 | 1456.83 | 03-NOV-14:50 | 16.10 | 9.74 | 0.195046E+09 | 313.85 | 03-NOV-13:00 | 16.10 | 9.74 |
December | 19568489.44 | 985.05 | 02-DEC-17:03 | 1.70 | 0.90 | 0.185945E+09 | 257.49 | 08-DEC-14:00 | -15.6 | -15.9 |
Annual Sum or Average | 0.265773E+11 | 0.271530E+10 | ||||||||
Minimum of Months | 19568489.44 | 967.02 | -3.9 | -4.9 | 0.176263E+09 | 257.48 | -24.1 | -24.4 | ||
Maximum of Months | 0.553322E+10 | 15465.54 | 26.88 | 21.34 | 0.285464E+09 | 348.61 | 28.30 | 22.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.562225E+09 | 4362.51 | 12-JAN-12:40 | 2.03 | 0.42 | 0.321746E+09 | 549.49 | 12-JAN-14:00 | 2.80 | 1.13 |
February | 0.848584E+09 | 7802.29 | 24-FEB-13:50 | 7.62 | 4.99 | 0.296964E+09 | 549.50 | 24-FEB-14:09 | 7.88 | 5.25 |
March | 0.156334E+10 | 8105.03 | 24-MAR-13:40 | 12.93 | 6.50 | 0.368492E+09 | 549.50 | 28-MAR-13:09 | 15.78 | 9.88 |
April | 0.285727E+10 | 17950.13 | 16-APR-13:02 | 26.88 | 19.97 | 0.342642E+09 | 549.90 | 18-APR-13:39 | 27.93 | 20.65 |
May | 0.451306E+10 | 10407.26 | 30-MAY-13:30 | 26.70 | 19.86 | 0.414235E+09 | 549.75 | 30-MAY-13:39 | 26.70 | 19.86 |
June | 0.635776E+10 | 17736.03 | 11-JUN-14:22 | 32.50 | 24.45 | 0.424309E+09 | 550.07 | 26-JUN-13:00 | 31.70 | 22.11 |
July | 0.700454E+10 | 17372.58 | 30-JUL-13:22 | 26.95 | 19.99 | 0.402561E+09 | 549.95 | 31-JUL-13:00 | 26.10 | 21.45 |
August | 0.748332E+10 | 17417.24 | 13-AUG-13:02 | 25.18 | 19.76 | 0.449071E+09 | 550.09 | 21-AUG-13:50 | 29.32 | 21.76 |
September | 0.589620E+10 | 19001.31 | 04-SEP-13:42 | 21.60 | 14.14 | 0.379103E+09 | 559.25 | 07-SEP-13:39 | 32.03 | 18.28 |
October | 0.285475E+10 | 12543.24 | 01-OCT-14:13 | 19.13 | 12.31 | 0.364935E+09 | 549.57 | 20-OCT-13:50 | 22.47 | 12.96 |
November | 0.115014E+10 | 10057.95 | 03-NOV-13:30 | 15.85 | 10.76 | 0.323897E+09 | 549.49 | 21-NOV-14:20 | -6.3 | -8.1 |
December | 0.652238E+09 | 5615.79 | 01-DEC-13:30 | -0.9 | -3.3 | 0.313489E+09 | 549.49 | 14-DEC-14:00 | 1.70 | 0.50 |
Annual Sum or Average | 0.417434E+11 | 0.440144E+10 | ||||||||
Minimum of Months | 0.562225E+09 | 4362.51 | -0.9 | -3.3 | 0.296964E+09 | 549.49 | -6.3 | -8.1 | ||
Maximum of Months | 0.748332E+10 | 19001.31 | 32.50 | 24.45 | 0.449071E+09 | 559.25 | 32.03 | 22.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63649952.11 | 1458.27 | 12-JAN-16:00 | 2.80 | 1.13 | 0.192995E+09 | 285.91 | 12-JAN-16:10 | 2.62 | 1.03 |
February | 0.185206E+09 | 2652.83 | 24-FEB-16:30 | 7.75 | 5.51 | 0.177258E+09 | 338.68 | 24-FEB-16:10 | 7.75 | 5.51 |
March | 0.630445E+09 | 2954.15 | 23-MAR-16:00 | 17.20 | 10.15 | 0.217883E+09 | 338.69 | 24-MAR-15:30 | 11.70 | 6.01 |
April | 0.187274E+10 | 15947.10 | 16-APR-16:21 | 28.60 | 20.44 | 0.207790E+09 | 347.84 | 14-APR-13:00 | 28.60 | 20.44 |
May | 0.345960E+10 | 16197.41 | 21-MAY-16:32 | 18.17 | 10.08 | 0.253197E+09 | 347.85 | 08-MAY-13:00 | 18.17 | 10.08 |
June | 0.512606E+10 | 16370.28 | 25-JUN-17:21 | 31.40 | 21.75 | 0.265223E+09 | 347.86 | 16-JUN-13:00 | 31.40 | 21.75 |
July | 0.554116E+10 | 16305.11 | 02-JUL-16:52 | 28.90 | 21.17 | 0.253284E+09 | 347.86 | 25-JUL-09:09 | 23.68 | 19.04 |
August | 0.523480E+10 | 13485.73 | 13-AUG-16:22 | 25.30 | 20.50 | 0.281048E+09 | 347.86 | 30-AUG-13:00 | 23.90 | 18.14 |
September | 0.335617E+10 | 16127.01 | 04-SEP-15:42 | 22.20 | 14.41 | 0.228555E+09 | 347.86 | 06-SEP-09:50 | 25.13 | 18.36 |
October | 0.123611E+10 | 5397.61 | 20-OCT-15:30 | 22.30 | 13.06 | 0.210660E+09 | 347.79 | 20-OCT-13:00 | 22.30 | 13.06 |
November | 0.458262E+09 | 3418.70 | 03-NOV-15:30 | 15.55 | 9.47 | 0.194658E+09 | 343.20 | 03-NOV-13:00 | 15.55 | 9.47 |
December | 96852043.42 | 1457.02 | 01-DEC-15:50 | -1.6 | -4.0 | 0.186324E+09 | 286.19 | 01-DEC-15:00 | -1.7 | -4.1 |
Annual Sum or Average | 0.272610E+11 | 0.266887E+10 | ||||||||
Minimum of Months | 63649952.11 | 1457.02 | -1.6 | -4.0 | 0.177258E+09 | 285.91 | -1.7 | -4.1 | ||
Maximum of Months | 0.554116E+10 | 16370.28 | 31.40 | 21.75 | 0.281048E+09 | 347.86 | 31.40 | 21.75 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12651368.66 | 1044.51 | 14-JAN-17:02 | -7.4 | -8.6 | 0.300090E+09 | 406.72 | 18-JAN-14:00 | -17.2 | -17.5 |
February | 19816623.18 | 1058.25 | 25-FEB-17:03 | 4.63 | 1.87 | 0.273842E+09 | 406.70 | 01-FEB-14:39 | 4.63 | 1.87 |
March | 0.310348E+09 | 1335.24 | 28-MAR-15:30 | 16.40 | 10.50 | 0.335156E+09 | 444.89 | 28-MAR-13:00 | 16.40 | 10.50 |
April | 0.927381E+09 | 3073.50 | 18-APR-15:00 | 28.30 | 20.65 | 0.313538E+09 | 549.47 | 18-APR-13:09 | 28.30 | 20.65 |
May | 0.229300E+10 | 4017.17 | 31-MAY-15:00 | 30.00 | 19.70 | 0.396134E+09 | 549.50 | 31-MAY-13:09 | 30.00 | 19.70 |
June | 0.388327E+10 | 5549.64 | 26-JUN-14:30 | 31.40 | 21.97 | 0.425823E+09 | 549.50 | 20-JUN-13:00 | 31.40 | 21.97 |
July | 0.443015E+10 | 5918.87 | 05-JUL-06:03 | 19.60 | 18.69 | 0.403427E+09 | 549.50 | 19-JUL-09:09 | 21.28 | 16.97 |
August | 0.455036E+10 | 5768.19 | 04-AUG-15:30 | 33.90 | 25.83 | 0.452091E+09 | 562.05 | 04-AUG-07:49 | 33.90 | 25.83 |
September | 0.314564E+10 | 5583.04 | 11-SEP-14:00 | 28.90 | 20.23 | 0.383405E+09 | 549.50 | 06-SEP-09:20 | 28.90 | 20.23 |
October | 0.158839E+10 | 1700.31 | 20-OCT-14:00 | 22.60 | 13.03 | 0.344772E+09 | 520.47 | 02-OCT-13:00 | 22.60 | 13.03 |
November | 0.707684E+09 | 1575.86 | 03-NOV-15:20 | 15.73 | 9.52 | 0.318309E+09 | 503.57 | 03-NOV-13:00 | 15.73 | 9.52 |
December | 12596096.32 | 1058.79 | 02-DEC-17:03 | 1.70 | 0.90 | 0.293376E+09 | 406.71 | 08-DEC-14:00 | -15.6 | -15.9 |
Annual Sum or Average | 0.218813E+11 | 0.423996E+10 | ||||||||
Minimum of Months | 12596096.32 | 1044.51 | -7.4 | -8.6 | 0.273842E+09 | 406.70 | -17.2 | -17.5 | ||
Maximum of Months | 0.455036E+10 | 5918.87 | 33.90 | 25.83 | 0.452091E+09 | 562.05 | 33.90 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34959740.41 | 862.35 | 13-JAN-11:00 | 2.20 | 0.51 | 0.192879E+09 | 257.64 | 13-JAN-10:00 | 2.20 | 0.51 |
February | 84938674.34 | 1076.31 | 24-FEB-10:20 | 4.80 | 1.70 | 0.176212E+09 | 296.73 | 24-FEB-10:30 | 5.00 | 1.88 |
March | 0.505471E+09 | 1281.08 | 28-MAR-10:00 | 10.00 | 6.30 | 0.219701E+09 | 335.70 | 28-MAR-09:00 | 10.00 | 6.30 |
April | 0.111557E+10 | 5113.08 | 18-APR-09:40 | 24.67 | 19.90 | 0.210298E+09 | 347.88 | 13-APR-09:09 | 24.67 | 19.90 |
May | 0.242165E+10 | 6128.97 | 31-MAY-09:30 | 26.65 | 19.56 | 0.266667E+09 | 347.88 | 09-MAY-09:09 | 26.65 | 19.56 |
June | 0.419779E+10 | 11810.39 | 11-JUN-09:01 | 26.88 | 21.15 | 0.271095E+09 | 348.10 | 26-JUN-09:50 | 28.12 | 22.45 |
July | 0.477345E+10 | 12068.80 | 02-JUL-09:21 | 26.15 | 21.26 | 0.256531E+09 | 348.24 | 05-JUL-09:30 | 23.60 | 20.34 |
August | 0.468654E+10 | 8491.44 | 20-AUG-09:43 | 22.43 | 18.94 | 0.287317E+09 | 366.35 | 04-AUG-07:49 | 22.43 | 18.94 |
September | 0.336202E+10 | 8911.72 | 04-SEP-10:23 | 18.85 | 13.15 | 0.248706E+09 | 347.88 | 06-SEP-09:20 | 23.73 | 17.58 |
October | 0.142546E+10 | 2425.67 | 20-OCT-10:00 | 15.20 | 10.20 | 0.232764E+09 | 347.88 | 20-OCT-09:09 | 15.20 | 10.20 |
November | 0.574096E+09 | 1268.92 | 03-NOV-10:40 | 13.87 | 11.30 | 0.202533E+09 | 326.58 | 03-NOV-13:00 | 16.10 | 10.47 |
December | 39053462.88 | 872.76 | 05-DEC-09:30 | -6.4 | -8.4 | 0.186531E+09 | 257.49 | 11-DEC-14:30 | -19.4 | -20.0 |
Annual Sum or Average | 0.232210E+11 | 0.275123E+10 | ||||||||
Minimum of Months | 34959740.41 | 862.35 | -6.4 | -8.4 | 0.176212E+09 | 257.49 | -19.4 | -20.0 | ||
Maximum of Months | 0.477345E+10 | 12068.80 | 26.88 | 21.26 | 0.287317E+09 | 366.35 | 28.12 | 22.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52657547.11 | 1152.07 | 13-JAN-14:40 | 3.90 | 1.72 | 0.246133E+09 | 433.03 | 13-JAN-14:50 | 3.90 | 1.72 |
February | 0.118685E+09 | 1482.47 | 25-FEB-15:30 | 5.60 | 2.75 | 0.244144E+09 | 506.36 | 24-FEB-14:00 | 5.60 | 2.75 |
March | 0.377566E+09 | 2581.90 | 24-MAR-14:00 | 13.30 | 6.51 | 0.322202E+09 | 549.50 | 24-MAR-13:20 | 13.30 | 6.51 |
April | 0.111431E+10 | 10811.33 | 18-APR-12:00 | 27.80 | 20.94 | 0.311003E+09 | 549.58 | 18-APR-13:30 | 27.75 | 20.64 |
May | 0.233541E+10 | 11179.97 | 31-MAY-12:00 | 29.40 | 19.85 | 0.382007E+09 | 550.04 | 31-MAY-12:09 | 29.50 | 19.82 |
June | 0.453247E+10 | 13456.00 | 11-JUN-13:02 | 31.20 | 23.33 | 0.412192E+09 | 590.73 | 26-JUN-12:09 | 30.68 | 21.60 |
July | 0.570826E+10 | 13661.19 | 02-JUL-13:22 | 28.60 | 22.17 | 0.399742E+09 | 549.68 | 05-JUL-13:09 | 26.78 | 20.42 |
August | 0.672971E+10 | 12499.50 | 04-AUG-16:10 | 33.15 | 26.05 | 0.448726E+09 | 605.29 | 04-AUG-12:09 | 33.15 | 26.05 |
September | 0.514843E+10 | 14583.17 | 04-SEP-13:42 | 21.60 | 14.14 | 0.376290E+09 | 631.68 | 07-SEP-12:09 | 30.78 | 18.58 |
October | 0.179509E+10 | 8627.69 | 20-OCT-14:00 | 22.60 | 13.03 | 0.352869E+09 | 549.55 | 20-OCT-13:00 | 22.60 | 13.03 |
November | 0.693556E+09 | 7178.69 | 04-NOV-13:30 | 14.15 | 6.81 | 0.300516E+09 | 549.49 | 03-NOV-13:09 | 14.15 | 6.81 |
December | 0.139574E+09 | 1440.49 | 02-DEC-12:40 | 5.40 | 2.84 | 0.259363E+09 | 443.30 | 01-DEC-14:39 | 5.40 | 2.84 |
Annual Sum or Average | 0.287457E+11 | 0.405519E+10 | ||||||||
Minimum of Months | 52657547.11 | 1152.07 | 3.90 | 1.72 | 0.244144E+09 | 433.03 | 3.90 | 1.72 | ||
Maximum of Months | 0.672971E+10 | 14583.17 | 33.15 | 26.05 | 0.448726E+09 | 631.68 | 33.15 | 26.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40797587.17 | 1114.38 | 12-JAN-16:00 | 2.80 | 1.13 | 0.193135E+09 | 280.72 | 12-JAN-16:10 | 2.62 | 1.03 |
February | 0.115237E+09 | 1435.99 | 24-FEB-16:40 | 7.57 | 5.38 | 0.176894E+09 | 336.34 | 24-FEB-16:49 | 7.38 | 5.26 |
March | 0.467631E+09 | 1412.47 | 23-MAR-16:50 | 16.28 | 9.98 | 0.215906E+09 | 326.70 | 23-MAR-15:00 | 16.28 | 9.98 |
April | 0.128756E+10 | 8865.99 | 15-APR-17:06 | 29.72 | 18.80 | 0.206672E+09 | 347.84 | 18-APR-09:00 | 25.60 | 20.52 |
May | 0.231546E+10 | 10627.20 | 21-MAY-17:52 | 17.20 | 9.22 | 0.253695E+09 | 347.85 | 31-MAY-13:09 | 29.90 | 19.66 |
June | 0.401412E+10 | 12219.74 | 25-JUN-17:32 | 31.30 | 21.77 | 0.268617E+09 | 347.86 | 20-JUN-13:00 | 31.30 | 21.77 |
July | 0.471141E+10 | 13495.15 | 02-JUL-18:01 | 28.12 | 21.02 | 0.256032E+09 | 347.85 | 19-JUL-09:09 | 21.28 | 16.97 |
August | 0.477215E+10 | 9837.08 | 05-AUG-17:05 | 25.32 | 17.94 | 0.286956E+09 | 347.87 | 08-AUG-09:09 | 20.28 | 15.58 |
September | 0.328087E+10 | 12223.75 | 04-SEP-15:42 | 22.20 | 14.41 | 0.243052E+09 | 347.85 | 06-SEP-09:20 | 23.73 | 17.58 |
October | 0.157023E+10 | 4474.01 | 11-OCT-16:00 | 17.80 | 11.96 | 0.225377E+09 | 347.83 | 20-OCT-13:00 | 22.60 | 13.03 |
November | 0.637445E+09 | 2877.46 | 03-NOV-15:40 | 15.37 | 9.43 | 0.202464E+09 | 345.12 | 03-NOV-13:00 | 15.37 | 9.43 |
December | 93606042.11 | 1171.71 | 01-DEC-15:50 | -1.6 | -4.0 | 0.187104E+09 | 290.86 | 01-DEC-15:00 | -1.7 | -4.1 |
Annual Sum or Average | 0.233065E+11 | 0.271590E+10 | ||||||||
Minimum of Months | 40797587.17 | 1114.38 | -1.6 | -4.0 | 0.176894E+09 | 280.72 | -1.7 | -4.1 | ||
Maximum of Months | 0.477215E+10 | 13495.15 | 31.30 | 21.77 | 0.286956E+09 | 347.87 | 31.30 | 21.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24633652.53 | 963.61 | 14-JAN-17:02 | -7.4 | -8.6 | 0.302286E+09 | 406.71 | 18-JAN-14:00 | -17.2 | -17.5 |
February | 61797193.75 | 1134.83 | 24-FEB-16:30 | 7.75 | 5.51 | 0.275918E+09 | 423.46 | 24-FEB-14:00 | 7.75 | 5.51 |
March | 0.599223E+09 | 1468.74 | 28-MAR-15:30 | 16.40 | 10.50 | 0.344149E+09 | 502.94 | 24-MAR-13:00 | 16.40 | 10.50 |
April | 0.153890E+10 | 5370.43 | 18-APR-15:00 | 28.30 | 20.65 | 0.335351E+09 | 549.48 | 18-APR-09:09 | 28.30 | 20.65 |
May | 0.322986E+10 | 5761.06 | 31-MAY-15:00 | 30.00 | 19.70 | 0.421992E+09 | 549.51 | 09-MAY-13:09 | 30.00 | 19.70 |
June | 0.500553E+10 | 10360.61 | 25-JUN-19:12 | 28.87 | 21.34 | 0.431463E+09 | 549.90 | 27-JUN-13:20 | 29.60 | 22.39 |
July | 0.532513E+10 | 10281.17 | 02-JUL-18:41 | 27.38 | 20.97 | 0.404829E+09 | 549.78 | 03-JUL-13:00 | 29.40 | 24.07 |
August | 0.507052E+10 | 6374.76 | 04-AUG-15:10 | 33.90 | 25.49 | 0.452956E+09 | 556.52 | 04-AUG-07:30 | 33.90 | 25.49 |
September | 0.318054E+10 | 6064.05 | 11-SEP-14:00 | 28.90 | 20.23 | 0.383802E+09 | 549.50 | 06-SEP-09:09 | 28.90 | 20.23 |
October | 0.139274E+10 | 1814.18 | 20-OCT-13:30 | 22.20 | 12.82 | 0.345607E+09 | 541.87 | 02-OCT-13:00 | 22.20 | 12.82 |
November | 0.610664E+09 | 1621.77 | 03-NOV-13:30 | 15.85 | 10.76 | 0.318731E+09 | 513.48 | 03-NOV-13:00 | 16.10 | 10.47 |
December | 10754379.86 | 977.26 | 02-DEC-17:03 | 1.70 | 0.90 | 0.293335E+09 | 406.71 | 08-DEC-14:00 | -15.6 | -15.9 |
Annual Sum or Average | 0.260503E+11 | 0.431042E+10 | ||||||||
Minimum of Months | 10754379.86 | 963.61 | -7.4 | -8.6 | 0.275918E+09 | 406.71 | -17.2 | -17.5 | ||
Maximum of Months | 0.532513E+10 | 10360.61 | 33.90 | 25.49 | 0.452956E+09 | 556.52 | 33.90 | 25.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52583536.11 | 1116.36 | 12-JAN-10:00 | -2.8 | -3.3 | 0.141722E+09 | 260.12 | 12-JAN-09:00 | -2.8 | -3.3 |
February | 0.171645E+09 | 1539.78 | 24-FEB-10:00 | 4.40 | 1.36 | 0.130147E+09 | 326.21 | 24-FEB-09:00 | 4.40 | 1.36 |
March | 0.822428E+09 | 2928.30 | 28-MAR-09:00 | 7.20 | 4.38 | 0.164924E+09 | 338.72 | 28-MAR-10:09 | 10.47 | 6.54 |
April | 0.180367E+10 | 7736.55 | 18-APR-09:00 | 22.80 | 18.62 | 0.159774E+09 | 338.72 | 18-APR-07:10 | 22.80 | 18.62 |
May | 0.350507E+10 | 10874.83 | 28-MAY-08:22 | 18.85 | 16.51 | 0.198874E+09 | 338.94 | 31-MAY-08:00 | 26.10 | 19.69 |
June | 0.502991E+10 | 15213.96 | 25-JUN-08:31 | 25.37 | 20.95 | 0.200202E+09 | 359.22 | 26-JUN-07:00 | 25.00 | 21.93 |
July | 0.540595E+10 | 15284.60 | 02-JUL-08:41 | 25.32 | 20.92 | 0.189878E+09 | 339.21 | 05-JUL-08:00 | 22.80 | 20.41 |
August | 0.495636E+10 | 10685.35 | 20-AUG-10:13 | 22.80 | 18.82 | 0.211286E+09 | 351.81 | 04-AUG-07:30 | 22.80 | 18.82 |
September | 0.348048E+10 | 11542.36 | 03-SEP-08:32 | 16.83 | 12.49 | 0.180096E+09 | 339.00 | 25-SEP-08:50 | 7.52 | 4.79 |
October | 0.145782E+10 | 3473.87 | 20-OCT-08:55 | 12.20 | 8.72 | 0.163408E+09 | 338.72 | 20-OCT-10:09 | 15.68 | 10.42 |
November | 0.562617E+09 | 1579.23 | 03-NOV-13:00 | 15.60 | 11.02 | 0.146291E+09 | 322.03 | 03-NOV-10:50 | 15.60 | 11.02 |
December | 44433508.19 | 1082.81 | 05-DEC-09:50 | -6.2 | -8.3 | 0.137069E+09 | 257.50 | 05-DEC-09:00 | -6.1 | -8.3 |
Annual Sum or Average | 0.272930E+11 | 0.202367E+10 | ||||||||
Minimum of Months | 44433508.19 | 1082.81 | -6.2 | -8.3 | 0.130147E+09 | 257.50 | -6.1 | -8.3 | ||
Maximum of Months | 0.540595E+10 | 15284.60 | 25.37 | 20.95 | 0.211286E+09 | 359.22 | 26.10 | 21.93 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.675963E+09 | 5027.57 | 12-JAN-12:30 | 1.95 | 0.38 | 0.327451E+09 | 549.49 | 12-JAN-14:00 | 2.80 | 1.13 |
February | 0.966656E+09 | 7895.86 | 24-FEB-13:35 | 7.43 | 4.81 | 0.304060E+09 | 549.50 | 24-FEB-14:09 | 7.88 | 5.25 |
March | 0.184824E+10 | 8179.03 | 24-MAR-13:10 | 12.38 | 6.48 | 0.377894E+09 | 549.50 | 28-MAR-13:09 | 15.78 | 9.88 |
April | 0.305719E+10 | 12714.02 | 16-APR-13:53 | 27.80 | 20.59 | 0.352886E+09 | 549.86 | 18-APR-13:39 | 27.93 | 20.65 |
May | 0.450921E+10 | 10466.46 | 29-MAY-12:33 | 24.63 | 19.18 | 0.424365E+09 | 550.10 | 30-MAY-13:00 | 26.70 | 19.86 |
June | 0.610583E+10 | 15886.50 | 25-JUN-13:12 | 31.87 | 22.64 | 0.430231E+09 | 549.98 | 30-JUN-13:50 | 29.40 | 21.96 |
July | 0.681419E+10 | 16220.68 | 30-JUL-11:52 | 26.70 | 21.51 | 0.404626E+09 | 550.07 | 05-JUL-13:00 | 26.70 | 21.51 |
August | 0.736240E+10 | 15725.79 | 13-AUG-12:53 | 25.00 | 19.70 | 0.453066E+09 | 550.57 | 21-AUG-13:00 | 29.40 | 21.95 |
September | 0.608578E+10 | 15975.64 | 04-SEP-13:12 | 21.30 | 14.06 | 0.390901E+09 | 566.95 | 07-SEP-13:20 | 31.87 | 18.17 |
October | 0.340953E+10 | 11224.33 | 20-OCT-13:10 | 21.93 | 12.68 | 0.381078E+09 | 549.60 | 20-OCT-13:50 | 22.47 | 12.96 |
November | 0.140558E+10 | 10220.03 | 03-NOV-13:10 | 15.68 | 10.94 | 0.337661E+09 | 549.54 | 03-NOV-13:00 | 16.10 | 10.47 |
December | 0.787542E+09 | 6106.03 | 01-DEC-13:30 | -0.9 | -3.3 | 0.318433E+09 | 549.49 | 06-DEC-14:00 | -3.3 | -7.1 |
Annual Sum or Average | 0.430281E+11 | 0.450265E+10 | ||||||||
Minimum of Months | 0.675963E+09 | 5027.57 | -0.9 | -3.3 | 0.304060E+09 | 549.49 | -3.3 | -7.1 | ||
Maximum of Months | 0.736240E+10 | 16220.68 | 31.87 | 22.64 | 0.453066E+09 | 566.95 | 31.87 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 86888568.89 | 1416.61 | 12-JAN-16:00 | 2.80 | 1.13 | 0.193447E+09 | 296.94 | 12-JAN-16:10 | 2.62 | 1.03 |
February | 0.227416E+09 | 2683.35 | 24-FEB-16:30 | 7.75 | 5.51 | 0.178314E+09 | 339.03 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.805399E+09 | 3032.90 | 23-MAR-16:00 | 17.20 | 10.15 | 0.220823E+09 | 338.69 | 24-MAR-15:39 | 11.33 | 5.84 |
April | 0.203571E+10 | 13594.13 | 15-APR-17:04 | 29.72 | 18.80 | 0.212763E+09 | 347.84 | 18-APR-09:09 | 23.27 | 18.95 |
May | 0.341551E+10 | 14847.92 | 14-MAY-17:22 | 20.85 | 15.99 | 0.261208E+09 | 347.86 | 08-MAY-13:00 | 20.85 | 15.99 |
June | 0.492972E+10 | 15208.05 | 25-JUN-17:11 | 31.50 | 21.73 | 0.269835E+09 | 347.86 | 20-JUN-13:00 | 31.50 | 21.73 |
July | 0.537547E+10 | 16035.81 | 02-JUL-16:41 | 28.98 | 21.21 | 0.255420E+09 | 347.85 | 05-JUL-09:20 | 23.33 | 20.37 |
August | 0.512257E+10 | 14438.19 | 13-AUG-16:11 | 25.40 | 20.51 | 0.285153E+09 | 347.86 | 30-AUG-13:50 | 23.62 | 17.87 |
September | 0.346322E+10 | 12296.50 | 04-SEP-17:12 | 21.67 | 14.30 | 0.237345E+09 | 347.86 | 06-SEP-09:09 | 23.27 | 17.32 |
October | 0.161791E+10 | 5331.37 | 20-OCT-15:30 | 22.30 | 13.06 | 0.218909E+09 | 347.83 | 11-OCT-13:00 | 22.30 | 13.06 |
November | 0.647565E+09 | 3575.15 | 03-NOV-15:30 | 15.55 | 9.47 | 0.199689E+09 | 347.53 | 03-NOV-13:00 | 15.55 | 9.47 |
December | 0.130041E+09 | 1428.12 | 01-DEC-15:50 | -1.6 | -4.0 | 0.187295E+09 | 299.10 | 01-DEC-15:00 | -1.7 | -4.1 |
Annual Sum or Average | 0.278574E+11 | 0.272020E+10 | ||||||||
Minimum of Months | 86888568.89 | 1416.61 | -1.6 | -4.0 | 0.178314E+09 | 296.94 | -1.7 | -4.1 | ||
Maximum of Months | 0.537547E+10 | 16035.81 | 31.50 | 21.73 | 0.285153E+09 | 347.86 | 31.50 | 21.73 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.466048E+09 | 22688.57 | 02-JAN-05:01 | -4.5 |
February | 63409756.67 | 19108.42 | 06-FEB-06:03 | -15.0 |
March | 4831352.24 | 18043.53 | 06-MAR-07:03 | -12.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 19741708.52 | 20268.94 | 27-NOV-06:02 | -9.4 |
December | 61456123.97 | 19831.76 | 26-DEC-06:03 | -5.8 |
Annual Sum or Average | 0.615487E+09 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.466048E+09 | 22688.57 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134089E+11 | 20004.93 | 31-JAN-06:06 | -30.6 |
February | 0.877595E+10 | 21122.76 | 02-FEB-06:07 | -36.7 |
March | 0.472272E+10 | 17699.64 | 06-MAR-06:13 | -13.9 |
April | 0.205246E+10 | 14234.19 | 03-APR-05:13 | -7.2 |
May | 0.408272E+09 | 5511.22 | 30-MAY-05:03 | 14.50 |
June | 0.196226E+09 | 7648.16 | 19-JUN-05:03 | 11.78 |
July | 95958738.71 | 6633.81 | 31-JUL-05:03 | 16.88 |
August | 0.165006E+09 | 5397.02 | 14-AUG-05:03 | 15.68 |
September | 0.683964E+09 | 7017.68 | 30-SEP-06:03 | 0.60 |
October | 0.174448E+10 | 9118.50 | 23-OCT-06:01 | -3.0 |
November | 0.601897E+10 | 17294.25 | 28-NOV-06:13 | -18.1 |
December | 0.106950E+11 | 19425.31 | 09-DEC-06:11 | -22.8 |
Annual Sum or Average | 0.489679E+11 | |||
Minimum of Months | 95958738.71 | 5397.02 | -36.7 | |
Maximum of Months | 0.134089E+11 | 21122.76 | 16.88 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.576378E+10 | 11212.76 | 30-JAN-07:07 | -29.0 |
February | 0.362994E+10 | 10541.40 | 06-FEB-07:03 | -15.0 |
March | 0.238751E+10 | 8882.51 | 06-MAR-06:13 | -13.9 |
April | 0.950805E+09 | 7552.97 | 03-APR-06:11 | -7.0 |
May | 0.140979E+09 | 3683.42 | 21-MAY-16:42 | 17.98 |
June | 50814551.57 | 3546.35 | 25-JUN-15:11 | 32.20 |
July | 36579103.32 | 3416.75 | 02-JUL-15:21 | 29.40 |
August | 26005171.53 | 3579.13 | 13-AUG-15:31 | 25.77 |
September | 0.200794E+09 | 4259.17 | 04-SEP-10:32 | 19.03 |
October | 0.102910E+10 | 4825.77 | 01-OCT-12:23 | 18.50 |
November | 0.258580E+10 | 10517.62 | 27-NOV-07:05 | -9.4 |
December | 0.446953E+10 | 11256.99 | 11-DEC-07:04 | -21.7 |
Annual Sum or Average | 0.212716E+11 | |||
Minimum of Months | 26005171.53 | 3416.75 | -29.0 | |
Maximum of Months | 0.576378E+10 | 11256.99 | 32.20 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.421193E+10 | 9567.61 | 02-JAN-07:01 | -5.9 |
February | 0.261693E+10 | 7397.00 | 06-FEB-07:01 | -15.0 |
March | 0.173230E+10 | 5304.12 | 06-MAR-07:01 | -12.7 |
April | 0.637953E+09 | 5381.12 | 20-APR-05:03 | 2.62 |
May | 59596933.28 | 5161.38 | 08-MAY-05:03 | 12.02 |
June | 25281316.33 | 5677.13 | 02-JUN-05:03 | 7.20 |
July | 31985107.53 | 4100.30 | 10-JUL-04:03 | 17.20 |
August | 33662899.03 | 4666.83 | 07-AUG-04:03 | 8.40 |
September | 73776536.94 | 6471.27 | 25-SEP-05:02 | 2.80 |
October | 0.475202E+09 | 3925.34 | 16-OCT-07:17 | 1.13 |
November | 0.179717E+10 | 7058.91 | 27-NOV-07:01 | -9.4 |
December | 0.321330E+10 | 7320.25 | 11-DEC-07:01 | -21.7 |
Annual Sum or Average | 0.149091E+11 | |||
Minimum of Months | 25281316.33 | 3925.34 | -21.7 | |
Maximum of Months | 0.421193E+10 | 9567.61 | 17.20 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267481E+10 | 29612.64 | 02-JAN-05:01 | -4.5 |
February | 0.109021E+10 | 28559.33 | 06-FEB-05:01 | -14.5 |
March | 0.278061E+09 | 26923.73 | 06-MAR-06:01 | -14.1 |
April | 68004375.56 | 26292.40 | 03-APR-05:01 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 1426123.09 | 23768.72 | 16-OCT-06:01 | -0.4 |
November | 0.623415E+09 | 28556.10 | 27-NOV-05:01 | -9.4 |
December | 0.135104E+10 | 28884.18 | 11-DEC-05:01 | -22.2 |
Annual Sum or Average | 0.608696E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.2 | |
Maximum of Months | 0.267481E+10 | 29612.64 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.749116E+10 | 32389.76 | 30-JAN-04:51 | -27.8 |
February | 0.419530E+10 | 31835.53 | 06-FEB-05:01 | -14.5 |
March | 0.165286E+10 | 32005.69 | 06-MAR-05:01 | -15.4 |
April | 0.401427E+09 | 30826.67 | 03-APR-04:01 | -6.8 |
May | 1693036.75 | 25395.55 | 02-MAY-06:01 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 9412424.58 | 25831.10 | 29-SEP-06:01 | 0.10 |
October | 0.156533E+09 | 27986.36 | 16-OCT-05:01 | 0.48 |
November | 0.256037E+10 | 31820.99 | 27-NOV-05:01 | -9.4 |
December | 0.523938E+10 | 32139.47 | 26-DEC-05:01 | -4.2 |
Annual Sum or Average | 0.217081E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.8 | |
Maximum of Months | 0.749116E+10 | 32389.76 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121079E+11 | 12750.12 | 19-JAN-00:11 | -21.0 |
February | 0.755000E+10 | 12761.49 | 03-FEB-05:11 | -33.9 |
March | 0.366208E+10 | 12546.96 | 06-MAR-03:42 | -16.2 |
April | 0.107651E+10 | 11990.27 | 03-APR-01:53 | -6.1 |
May | 29688524.51 | 10010.14 | 02-MAY-05:02 | 2.20 |
June | 1946957.68 | 5047.37 | 05-JUN-06:03 | 8.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.116443E+09 | 10241.81 | 30-SEP-05:01 | 0.10 |
October | 0.757139E+09 | 10843.19 | 16-OCT-04:02 | 1.78 |
November | 0.471453E+10 | 12564.30 | 25-NOV-22:42 | -24.0 |
December | 0.925134E+10 | 12801.22 | 11-DEC-05:21 | -22.2 |
Annual Sum or Average | 0.392676E+11 | |||
Minimum of Months | 0.00 | 0.00 | -33.9 | |
Maximum of Months | 0.121079E+11 | 12801.22 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.735160E+10 | 13058.56 | 19-JAN-00:11 | -21.0 |
February | 0.430308E+10 | 13070.39 | 03-FEB-05:11 | -33.9 |
March | 0.193638E+10 | 12756.73 | 06-MAR-03:42 | -16.2 |
April | 0.587110E+09 | 12099.26 | 03-APR-01:53 | -6.1 |
May | 8124861.87 | 10154.17 | 02-MAY-05:02 | 2.20 |
June | 1656351.52 | 3987.55 | 05-JUN-06:03 | 8.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 55735335.70 | 10417.93 | 30-SEP-05:01 | 0.10 |
October | 0.380545E+09 | 10719.33 | 19-OCT-05:01 | 1.62 |
November | 0.286177E+10 | 12764.46 | 25-NOV-22:42 | -24.0 |
December | 0.568276E+10 | 12903.38 | 11-DEC-05:21 | -22.2 |
Annual Sum or Average | 0.231687E+11 | |||
Minimum of Months | 0.00 | 0.00 | -33.9 | |
Maximum of Months | 0.735160E+10 | 13070.39 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.868297E+10 | 16191.47 | 19-JAN-00:11 | -21.0 |
February | 0.498435E+10 | 16206.23 | 03-FEB-05:11 | -33.9 |
March | 0.265482E+10 | 15867.28 | 06-MAR-03:42 | -16.2 |
April | 0.888140E+09 | 15180.93 | 03-APR-01:53 | -6.1 |
May | 29895168.82 | 12650.50 | 02-MAY-05:02 | 2.20 |
June | 2710916.44 | 6104.99 | 03-JUN-06:03 | 6.78 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 83588745.12 | 13056.34 | 30-SEP-05:01 | 0.10 |
October | 0.474037E+09 | 13595.30 | 16-OCT-04:02 | 1.78 |
November | 0.345066E+10 | 15946.55 | 27-NOV-04:42 | -9.6 |
December | 0.704414E+10 | 16048.04 | 11-DEC-05:21 | -22.2 |
Annual Sum or Average | 0.282953E+11 | |||
Minimum of Months | 0.00 | 0.00 | -33.9 | |
Maximum of Months | 0.868297E+10 | 16206.23 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.753883E+10 | 14467.09 | 19-JAN-00:11 | -21.0 |
February | 0.450046E+10 | 14476.51 | 03-FEB-05:11 | -33.9 |
March | 0.215607E+10 | 14050.40 | 06-MAR-03:42 | -16.2 |
April | 0.623833E+09 | 13250.63 | 03-APR-01:53 | -6.1 |
May | 22925727.61 | 11237.13 | 02-MAY-05:02 | 2.20 |
June | 3171633.07 | 4912.17 | 03-JUN-06:03 | 6.78 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 80826519.94 | 11524.89 | 30-SEP-05:01 | 0.10 |
October | 0.443787E+09 | 11758.06 | 19-OCT-05:01 | 1.62 |
November | 0.293954E+10 | 14092.06 | 25-NOV-22:42 | -24.0 |
December | 0.581282E+10 | 14291.64 | 11-DEC-05:21 | -22.2 |
Annual Sum or Average | 0.241223E+11 | |||
Minimum of Months | 0.00 | 0.00 | -33.9 | |
Maximum of Months | 0.753883E+10 | 14476.51 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.819369E+10 | 9118.07 | 30-JAN-03:52 | -27.2 |
February | 0.523501E+10 | 8878.21 | 05-FEB-21:22 | -21.4 |
March | 0.265346E+10 | 8810.87 | 06-MAR-03:42 | -16.2 |
April | 0.790224E+09 | 8350.62 | 03-APR-04:01 | -6.8 |
May | 15625969.90 | 7043.41 | 02-MAY-05:02 | 2.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 4091144.87 | 6760.66 | 29-SEP-06:01 | 0.10 |
October | 53019114.21 | 6866.25 | 16-OCT-06:01 | -0.4 |
November | 0.204548E+10 | 8699.77 | 27-NOV-04:42 | -9.6 |
December | 0.522700E+10 | 8879.54 | 11-DEC-02:23 | -21.7 |
Annual Sum or Average | 0.242176E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.819369E+10 | 9118.07 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.491856E+10 | 10165.88 | 30-JAN-03:52 | -27.2 |
February | 0.283103E+10 | 9886.00 | 05-FEB-21:22 | -21.4 |
March | 0.125556E+10 | 9805.04 | 06-MAR-03:42 | -16.2 |
April | 0.354843E+09 | 9389.58 | 03-APR-04:01 | -6.8 |
May | 726632.53 | 7669.57 | 02-MAY-06:01 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 1567193.35 | 7566.74 | 29-SEP-06:01 | 0.10 |
October | 18545942.44 | 7723.84 | 16-OCT-06:01 | -0.4 |
November | 0.117452E+10 | 9744.24 | 27-NOV-04:42 | -9.6 |
December | 0.312620E+10 | 9862.50 | 11-DEC-02:23 | -21.7 |
Annual Sum or Average | 0.136815E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.491856E+10 | 10165.88 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128054E+11 | 19728.02 | 31-JAN-07:10 | -30.5 |
February | 0.867844E+10 | 20940.42 | 03-FEB-07:10 | -33.9 |
March | 0.675994E+10 | 14955.29 | 06-MAR-07:10 | -12.7 |
April | 0.340523E+10 | 13942.77 | 03-APR-06:50 | -6.8 |
May | 0.102601E+10 | 11506.62 | 02-MAY-06:10 | 2.30 |
June | 0.397667E+09 | 9958.03 | 02-JUN-06:10 | 7.30 |
July | 31401729.21 | 8322.16 | 24-JUL-06:05 | 12.35 |
August | 0.126704E+09 | 9423.99 | 07-AUG-06:05 | 8.87 |
September | 0.732413E+09 | 11605.70 | 29-SEP-06:10 | 0.10 |
October | 0.184251E+10 | 12153.22 | 23-OCT-06:10 | -3.0 |
November | 0.538370E+10 | 16150.61 | 28-NOV-07:10 | -17.6 |
December | 0.971334E+10 | 17318.91 | 11-DEC-07:10 | -21.7 |
Annual Sum or Average | 0.509028E+11 | |||
Minimum of Months | 31401729.21 | 8322.16 | -33.9 | |
Maximum of Months | 0.128054E+11 | 20940.42 | 12.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.506068E+10 | 10914.40 | 30-JAN-03:52 | -27.2 |
February | 0.290935E+10 | 10618.74 | 02-FEB-04:01 | -35.2 |
March | 0.140440E+10 | 10491.52 | 06-MAR-03:42 | -16.2 |
April | 0.327547E+09 | 10115.54 | 03-APR-04:01 | -6.8 |
May | 6477432.46 | 8290.81 | 02-MAY-06:01 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 4165199.10 | 8290.61 | 29-SEP-06:01 | 0.10 |
October | 22624804.63 | 8327.22 | 16-OCT-06:01 | -0.4 |
November | 0.122085E+10 | 10488.02 | 27-NOV-04:42 | -9.6 |
December | 0.320904E+10 | 10618.18 | 11-DEC-02:23 | -21.7 |
Annual Sum or Average | 0.141651E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.506068E+10 | 10914.40 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.815493E+10 | 9685.46 | 19-JAN-05:21 | -27.5 |
February | 0.457750E+10 | 9459.09 | 02-FEB-04:01 | -35.2 |
March | 0.188035E+10 | 9252.25 | 06-MAR-04:51 | -15.6 |
April | 0.395260E+09 | 8859.55 | 03-APR-04:01 | -6.8 |
May | 3289307.37 | 7263.92 | 02-MAY-06:01 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 13519611.59 | 7451.45 | 30-SEP-05:01 | 0.10 |
October | 0.130735E+09 | 7793.47 | 16-OCT-05:01 | 0.48 |
November | 0.248707E+10 | 9237.06 | 26-NOV-04:12 | -25.0 |
December | 0.565255E+10 | 9605.85 | 11-DEC-05:21 | -22.2 |
Annual Sum or Average | 0.232952E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.815493E+10 | 9685.46 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.491655E+10 | 12191.86 | 19-JAN-05:21 | -27.5 |
February | 0.255657E+10 | 12042.55 | 02-FEB-04:01 | -35.2 |
March | 0.994795E+09 | 11712.12 | 06-MAR-04:51 | -15.6 |
April | 0.224915E+09 | 11226.56 | 03-APR-04:01 | -6.8 |
May | 836311.00 | 9189.64 | 02-MAY-06:01 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 8030697.56 | 9272.30 | 29-SEP-06:01 | 0.10 |
October | 75923552.49 | 9805.34 | 16-OCT-05:01 | 0.48 |
November | 0.152283E+10 | 11567.53 | 25-NOV-05:11 | -15.6 |
December | 0.350368E+10 | 12116.64 | 09-DEC-02:61 | -22.7 |
Annual Sum or Average | 0.138041E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.491655E+10 | 12191.86 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.531591E+10 | 14056.68 | 19-JAN-05:21 | -27.5 |
February | 0.265578E+10 | 13865.64 | 02-FEB-04:01 | -35.2 |
March | 0.124509E+10 | 13530.91 | 06-MAR-04:51 | -15.6 |
April | 0.303036E+09 | 13056.05 | 03-APR-04:01 | -6.8 |
May | 3278239.24 | 10716.57 | 02-MAY-06:01 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 9466851.06 | 10760.38 | 29-SEP-06:01 | 0.10 |
October | 81331818.97 | 11312.93 | 16-OCT-05:01 | 0.48 |
November | 0.165620E+10 | 13479.82 | 26-NOV-04:12 | -25.0 |
December | 0.411069E+10 | 13961.92 | 09-DEC-02:61 | -22.7 |
Annual Sum or Average | 0.153808E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.531591E+10 | 14056.68 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.500005E+10 | 12765.50 | 19-JAN-05:21 | -27.5 |
February | 0.264770E+10 | 12593.15 | 02-FEB-04:01 | -35.2 |
March | 0.107894E+10 | 11877.75 | 06-MAR-05:01 | -15.4 |
April | 0.217364E+09 | 11723.86 | 03-APR-04:01 | -6.8 |
May | 3448997.90 | 9638.36 | 02-MAY-06:01 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 12359278.47 | 9688.14 | 29-SEP-06:01 | 0.10 |
October | 85514515.97 | 10320.95 | 16-OCT-05:01 | 0.48 |
November | 0.153560E+10 | 12095.06 | 25-NOV-05:11 | -15.6 |
December | 0.353872E+10 | 12683.34 | 09-DEC-02:61 | -22.7 |
Annual Sum or Average | 0.141197E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.500005E+10 | 12765.50 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.208150E+11 | 18520.31 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.188385E+11 | 18520.31 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.216654E+11 | 18520.31 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.200796E+11 | 18520.31 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.212402E+11 | 18520.31 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.208620E+11 | 18520.31 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.204550E+11 | 18520.31 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.216654E+11 | 18520.31 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.200739E+11 | 18520.31 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.208179E+11 | 18520.31 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.203773E+11 | 18520.31 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.204522E+11 | 18520.31 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.247342E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.188385E+11 | 18520.31 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.216654E+11 | 18520.31 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.836295E+09 | 1168.55 | 02-JAN-16:40 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.724389E+09 | 1023.90 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.820201E+09 | 885.21 | 01-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.719726E+09 | 823.84 | 10-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.760308E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.752799E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.708271E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.792613E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.727145E+09 | 828.57 | 21-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.779286E+09 | 1134.77 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.815971E+09 | 1168.55 | 06-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.834927E+09 | 1168.55 | 01-DEC-16:30 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.927193E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.708271E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.836295E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.524285E+09 | 739.79 | 02-JAN-16:40 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.456067E+09 | 656.04 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.518978E+09 | 572.85 | 01-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.456222E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.482989E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.478147E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.449504E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.503314E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.461014E+09 | 456.08 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.490888E+09 | 683.81 | 31-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.514311E+09 | 739.79 | 06-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.521422E+09 | 739.79 | 01-DEC-16:30 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.585714E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.449504E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.524285E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.818595E+09 | 1168.55 | 02-JAN-16:40 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.713400E+09 | 987.94 | 14-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.817639E+09 | 840.07 | 01-MAR-16:00 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.720279E+09 | 816.80 | 10-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.762893E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.755719E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.710351E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.794765E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.726437E+09 | 807.58 | 21-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.770816E+09 | 1085.68 | 31-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.804701E+09 | 1168.55 | 06-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.811798E+09 | 1168.55 | 01-DEC-16:30 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.920739E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.710351E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.818595E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522923E+09 | 739.74 | 02-JAN-16:40 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.454223E+09 | 613.49 | 14-FEB-16:00 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.518399E+09 | 572.64 | 14-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.455163E+09 | 544.28 | 10-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.481668E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.476832E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.448837E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.501910E+09 | 456.05 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.459402E+09 | 551.29 | 21-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.491662E+09 | 719.99 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.511695E+09 | 739.74 | 06-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.519263E+09 | 739.74 | 01-DEC-16:30 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.584198E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.448837E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.522923E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.833948E+09 | 1168.55 | 02-JAN-16:40 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.722412E+09 | 1015.06 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.819465E+09 | 872.59 | 01-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.719352E+09 | 808.60 | 10-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.759993E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.752476E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.708082E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.792288E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.726635E+09 | 813.38 | 21-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.777823E+09 | 1132.98 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.814268E+09 | 1168.55 | 06-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.831558E+09 | 1168.55 | 01-DEC-16:30 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.925830E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.708082E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.833948E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.523528E+09 | 739.79 | 02-JAN-16:40 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.455278E+09 | 651.71 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.518622E+09 | 567.15 | 01-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.456014E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.482752E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.477927E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.449329E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.503071E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.460739E+09 | 456.08 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.490396E+09 | 680.16 | 31-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.513643E+09 | 739.79 | 06-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.520180E+09 | 739.79 | 01-DEC-16:30 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.585148E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.449329E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.523528E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.816610E+09 | 1168.55 | 02-JAN-16:40 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.712292E+09 | 979.62 | 14-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.817153E+09 | 824.80 | 01-MAR-16:00 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.719908E+09 | 801.19 | 10-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.762472E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.755255E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.709944E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.794190E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.726006E+09 | 791.26 | 21-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.770248E+09 | 1080.85 | 31-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.803613E+09 | 1168.55 | 06-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.810279E+09 | 1168.55 | 01-DEC-16:30 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.919797E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.709944E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.817153E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522008E+09 | 739.74 | 02-JAN-16:40 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.453557E+09 | 608.69 | 14-FEB-16:00 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.517888E+09 | 564.26 | 14-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.454907E+09 | 537.71 | 10-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.481434E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.476629E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.448698E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.501689E+09 | 456.05 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.459110E+09 | 544.93 | 21-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.491160E+09 | 719.14 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.511066E+09 | 739.74 | 06-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.518082E+09 | 739.74 | 01-DEC-16:30 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.583623E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.448698E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.522008E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.836295E+09 | 1168.55 | 02-JAN-16:40 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.724388E+09 | 1023.90 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.820201E+09 | 885.19 | 01-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.719726E+09 | 823.82 | 10-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.760307E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.752798E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.708271E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.792613E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.727145E+09 | 828.55 | 21-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.779286E+09 | 1134.77 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.815970E+09 | 1168.55 | 06-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.834926E+09 | 1168.55 | 01-DEC-16:30 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.927193E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.708271E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.836295E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.524284E+09 | 739.79 | 02-JAN-16:40 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.456067E+09 | 656.05 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.518978E+09 | 572.84 | 01-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.456222E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.482989E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.478147E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.449504E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.503314E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.461013E+09 | 456.08 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.490888E+09 | 683.81 | 31-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.514311E+09 | 739.79 | 06-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.521422E+09 | 739.79 | 01-DEC-16:30 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.585714E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.449504E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.524284E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.818594E+09 | 1168.55 | 02-JAN-16:40 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.713400E+09 | 987.93 | 14-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.817639E+09 | 840.06 | 01-MAR-16:00 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.720279E+09 | 816.78 | 10-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.762893E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.755719E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.710351E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.794765E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.726437E+09 | 807.56 | 21-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.770816E+09 | 1085.68 | 31-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.804701E+09 | 1168.55 | 06-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.811797E+09 | 1168.55 | 01-DEC-16:30 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.920739E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.710351E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.818594E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522923E+09 | 739.74 | 02-JAN-16:40 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.454223E+09 | 613.48 | 14-FEB-16:00 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.518399E+09 | 572.65 | 14-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.455163E+09 | 544.27 | 10-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.481668E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.476829E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.448837E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.501910E+09 | 456.05 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.459402E+09 | 551.28 | 21-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.491662E+09 | 719.99 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.511695E+09 | 739.74 | 06-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.519262E+09 | 739.74 | 01-DEC-16:30 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.584197E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.448837E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.522923E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.208150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.200796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.212402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.208620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.204550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.200739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.208179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.203773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.204522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.247342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.836295E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285211E+10 |
February | 0.901968E+09 | 0.724389E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207752E+10 |
March | 0.107774E+10 | 0.820201E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176059E+10 |
April | 0.956342E+09 | 0.719726E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10812938.66 | 0.109299E+10 |
May | 0.103597E+10 | 0.760308E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3525199.57 | 0.624676E+09 |
June | 0.103308E+10 | 0.752799E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46478256.17 | 0.370342E+09 |
July | 0.959235E+09 | 0.708271E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16473519.74 | 0.272922E+09 |
August | 0.107774E+10 | 0.792613E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17959583.23 | 0.365333E+09 |
September | 0.956342E+09 | 0.727145E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15169947.12 | 0.556604E+09 |
October | 0.994195E+09 | 0.779286E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101981E+10 |
November | 0.984487E+09 | 0.815971E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175337E+10 |
December | 0.959235E+09 | 0.834927E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237813E+10 |
Annual Sum or Average | 0.119305E+11 | 0.927193E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110419E+09 | 0.151244E+11 |
Minimum of Months | 0.901968E+09 | 0.708271E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272922E+09 |
Maximum of Months | 0.107774E+10 | 0.836295E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46478256.17 | 0.285211E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.524285E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190618E+10 |
February | 0.571020E+09 | 0.456067E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138917E+10 |
March | 0.682301E+09 | 0.518978E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118458E+10 |
April | 0.605444E+09 | 0.456222E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7136814.53 | 0.750755E+09 |
May | 0.655854E+09 | 0.482989E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2349458.75 | 0.428730E+09 |
June | 0.654023E+09 | 0.478147E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30594654.75 | 0.249866E+09 |
July | 0.607275E+09 | 0.449504E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10349171.24 | 0.185490E+09 |
August | 0.682301E+09 | 0.503314E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11752638.02 | 0.246399E+09 |
September | 0.605444E+09 | 0.461014E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9144221.22 | 0.384872E+09 |
October | 0.629407E+09 | 0.490888E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701630E+09 |
November | 0.623262E+09 | 0.514311E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117375E+10 |
December | 0.607275E+09 | 0.521422E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159028E+10 |
Annual Sum or Average | 0.755301E+10 | 0.585714E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71326958.52 | 0.101917E+11 |
Minimum of Months | 0.571020E+09 | 0.449504E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185490E+09 |
Maximum of Months | 0.682301E+09 | 0.524285E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30594654.75 | 0.190618E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.818595E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287891E+10 |
February | 0.901968E+09 | 0.713400E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212181E+10 |
March | 0.107774E+10 | 0.817639E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182353E+10 |
April | 0.956342E+09 | 0.720279E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8474160.69 | 0.114798E+10 |
May | 0.103597E+10 | 0.762893E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3524622.98 | 0.642645E+09 |
June | 0.103308E+10 | 0.755719E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45136454.50 | 0.370626E+09 |
July | 0.959235E+09 | 0.710351E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15072739.51 | 0.276040E+09 |
August | 0.107774E+10 | 0.794765E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17038871.55 | 0.380592E+09 |
September | 0.956342E+09 | 0.726437E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11158338.80 | 0.599480E+09 |
October | 0.994195E+09 | 0.770816E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111880E+10 |
November | 0.984487E+09 | 0.804701E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180221E+10 |
December | 0.959235E+09 | 0.811798E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242565E+10 |
Annual Sum or Average | 0.119305E+11 | 0.920739E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100405E+09 | 0.155883E+11 |
Minimum of Months | 0.901968E+09 | 0.710351E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276040E+09 |
Maximum of Months | 0.107774E+10 | 0.818595E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45136454.50 | 0.287891E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.522923E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190699E+10 |
February | 0.570983E+09 | 0.454223E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139542E+10 |
March | 0.682256E+09 | 0.518399E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118818E+10 |
April | 0.605404E+09 | 0.455163E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5471503.14 | 0.760670E+09 |
May | 0.655811E+09 | 0.481668E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2383639.76 | 0.428065E+09 |
June | 0.653980E+09 | 0.476832E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30403544.62 | 0.251177E+09 |
July | 0.607235E+09 | 0.448837E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10607272.24 | 0.191396E+09 |
August | 0.682256E+09 | 0.501910E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11844922.80 | 0.254825E+09 |
September | 0.605404E+09 | 0.459402E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8752883.42 | 0.386923E+09 |
October | 0.629366E+09 | 0.491662E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699351E+09 |
November | 0.623221E+09 | 0.511695E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117542E+10 |
December | 0.607235E+09 | 0.519263E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159072E+10 |
Annual Sum or Average | 0.755252E+10 | 0.584198E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69463765.98 | 0.102291E+11 |
Minimum of Months | 0.570983E+09 | 0.448837E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191396E+09 |
Maximum of Months | 0.682256E+09 | 0.522923E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30403544.62 | 0.190699E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.833948E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153282E+10 |
February | 0.901968E+09 | 0.722412E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113071E+10 |
March | 0.107774E+10 | 0.819465E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.958170E+09 |
April | 0.956342E+09 | 0.719352E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10322048.32 | 0.581972E+09 |
May | 0.103597E+10 | 0.759993E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2125400.41 | 0.320877E+09 |
June | 0.103308E+10 | 0.752476E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30770954.78 | 0.194138E+09 |
July | 0.959235E+09 | 0.708082E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10812258.45 | 0.141982E+09 |
August | 0.107774E+10 | 0.792288E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10257264.25 | 0.200243E+09 |
September | 0.956342E+09 | 0.726635E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9366097.14 | 0.321729E+09 |
October | 0.994195E+09 | 0.777823E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616126E+09 |
November | 0.984487E+09 | 0.814268E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999824E+09 |
December | 0.959235E+09 | 0.831558E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130694E+10 |
Annual Sum or Average | 0.119305E+11 | 0.925830E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73654023.35 | 0.830553E+10 |
Minimum of Months | 0.901968E+09 | 0.708082E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141982E+09 |
Maximum of Months | 0.107774E+10 | 0.833948E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30770954.78 | 0.153282E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.523528E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102467E+10 |
February | 0.571020E+09 | 0.455278E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758863E+09 |
March | 0.682301E+09 | 0.518622E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648926E+09 |
April | 0.605444E+09 | 0.456014E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5526987.29 | 0.405910E+09 |
May | 0.655854E+09 | 0.482752E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1279445.92 | 0.232272E+09 |
June | 0.654023E+09 | 0.477927E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17587884.91 | 0.136590E+09 |
July | 0.607275E+09 | 0.449329E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5802435.43 | 0.101716E+09 |
August | 0.682301E+09 | 0.503071E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6456068.09 | 0.139977E+09 |
September | 0.605444E+09 | 0.460739E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4840484.01 | 0.228305E+09 |
October | 0.629407E+09 | 0.490396E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430121E+09 |
November | 0.623262E+09 | 0.513643E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670717E+09 |
December | 0.607275E+09 | 0.520180E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.873911E+09 |
Annual Sum or Average | 0.755301E+10 | 0.585148E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41493305.65 | 0.565198E+10 |
Minimum of Months | 0.571020E+09 | 0.449329E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101716E+09 |
Maximum of Months | 0.682301E+09 | 0.523528E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17587884.91 | 0.102467E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.816610E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138040E+11 |
February | 0.901968E+09 | 0.712292E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105110E+11 |
March | 0.107774E+10 | 0.817153E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.915792E+10 |
April | 0.956342E+09 | 0.719908E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35716432.33 | 0.570477E+10 |
May | 0.103597E+10 | 0.762472E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106597E+09 | 0.319018E+10 |
June | 0.103308E+10 | 0.755255E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412590E+09 | 0.175893E+10 |
July | 0.959235E+09 | 0.709944E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364332E+09 | 0.847032E+09 |
August | 0.107774E+10 | 0.794190E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502877E+09 | 0.129726E+10 |
September | 0.956342E+09 | 0.726006E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256264E+09 | 0.293567E+10 |
October | 0.994195E+09 | 0.770248E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576252E+10 |
November | 0.984487E+09 | 0.803613E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803574E+10 |
December | 0.959235E+09 | 0.810279E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110635E+11 |
Annual Sum or Average | 0.119305E+11 | 0.919797E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167838E+10 | 0.740685E+11 |
Minimum of Months | 0.901968E+09 | 0.709944E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.847032E+09 |
Maximum of Months | 0.107774E+10 | 0.817153E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502877E+09 | 0.138040E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.522008E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102502E+10 |
February | 0.570983E+09 | 0.453557E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761770E+09 |
March | 0.682256E+09 | 0.517888E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650167E+09 |
April | 0.605404E+09 | 0.454907E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3588362.70 | 0.414189E+09 |
May | 0.655811E+09 | 0.481434E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1327017.65 | 0.230882E+09 |
June | 0.653980E+09 | 0.476629E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17179576.76 | 0.137266E+09 |
July | 0.607235E+09 | 0.448698E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5752331.82 | 0.107169E+09 |
August | 0.682256E+09 | 0.501689E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6378202.80 | 0.146197E+09 |
September | 0.605404E+09 | 0.459110E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4466943.81 | 0.229676E+09 |
October | 0.629366E+09 | 0.491160E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426958E+09 |
November | 0.623221E+09 | 0.511066E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671859E+09 |
December | 0.607235E+09 | 0.518082E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874416E+09 |
Annual Sum or Average | 0.755252E+10 | 0.583623E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38692435.55 | 0.567557E+10 |
Minimum of Months | 0.570983E+09 | 0.448698E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107169E+09 |
Maximum of Months | 0.682256E+09 | 0.522008E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17179576.76 | 0.102502E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.836295E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239470E+10 |
February | 0.901968E+09 | 0.724388E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176754E+10 |
March | 0.107774E+10 | 0.820201E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152547E+10 |
April | 0.956342E+09 | 0.719726E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10082314.03 | 0.962806E+09 |
May | 0.103597E+10 | 0.760307E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2964576.51 | 0.549270E+09 |
June | 0.103308E+10 | 0.752798E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39968408.93 | 0.324928E+09 |
July | 0.959235E+09 | 0.708271E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13986127.09 | 0.237698E+09 |
August | 0.107774E+10 | 0.792613E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15114051.40 | 0.320731E+09 |
September | 0.956342E+09 | 0.727145E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12616554.25 | 0.500266E+09 |
October | 0.994195E+09 | 0.779286E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934331E+09 |
November | 0.984487E+09 | 0.815970E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152193E+10 |
December | 0.959235E+09 | 0.834926E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202049E+10 |
Annual Sum or Average | 0.119305E+11 | 0.927193E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94732032.21 | 0.130602E+11 |
Minimum of Months | 0.901968E+09 | 0.708271E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237698E+09 |
Maximum of Months | 0.107774E+10 | 0.836295E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39968408.93 | 0.239470E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.524284E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159868E+10 |
February | 0.421807E+09 | 0.456067E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118286E+10 |
March | 0.502994E+09 | 0.518978E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102650E+10 |
April | 0.447140E+09 | 0.456222E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6800107.51 | 0.656882E+09 |
May | 0.484071E+09 | 0.482989E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1976687.93 | 0.372723E+09 |
June | 0.482240E+09 | 0.478147E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26859074.53 | 0.218018E+09 |
July | 0.448971E+09 | 0.449504E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9050577.57 | 0.159837E+09 |
August | 0.502994E+09 | 0.503314E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10082611.90 | 0.214574E+09 |
September | 0.447140E+09 | 0.461013E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7979760.83 | 0.341235E+09 |
October | 0.465148E+09 | 0.490888E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638007E+09 |
November | 0.460569E+09 | 0.514311E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101745E+10 |
December | 0.448971E+09 | 0.521422E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135029E+10 |
Annual Sum or Average | 0.557719E+10 | 0.585714E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62748820.26 | 0.877707E+10 |
Minimum of Months | 0.421807E+09 | 0.449504E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159837E+09 |
Maximum of Months | 0.502994E+09 | 0.524284E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26859074.53 | 0.159868E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.818594E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242791E+10 |
February | 0.901968E+09 | 0.713400E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181767E+10 |
March | 0.107774E+10 | 0.817639E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158483E+10 |
April | 0.956342E+09 | 0.720279E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7363922.06 | 0.100771E+10 |
May | 0.103597E+10 | 0.762893E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2964169.39 | 0.562175E+09 |
June | 0.103308E+10 | 0.755719E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38531023.32 | 0.325141E+09 |
July | 0.959235E+09 | 0.710351E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12690898.07 | 0.240058E+09 |
August | 0.107774E+10 | 0.794765E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14320852.36 | 0.332628E+09 |
September | 0.956342E+09 | 0.726437E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9360036.33 | 0.532794E+09 |
October | 0.994195E+09 | 0.770816E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101382E+10 |
November | 0.984487E+09 | 0.804701E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157214E+10 |
December | 0.959235E+09 | 0.811797E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207341E+10 |
Annual Sum or Average | 0.119305E+11 | 0.920739E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85230901.54 | 0.134903E+11 |
Minimum of Months | 0.901968E+09 | 0.710351E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240058E+09 |
Maximum of Months | 0.107774E+10 | 0.818594E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38531023.32 | 0.242791E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.522923E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159982E+10 |
February | 0.570983E+09 | 0.454223E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118803E+10 |
March | 0.682256E+09 | 0.518399E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102892E+10 |
April | 0.605404E+09 | 0.455163E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4810989.89 | 0.666211E+09 |
May | 0.655811E+09 | 0.481668E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1990751.62 | 0.375095E+09 |
June | 0.653980E+09 | 0.476829E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25929636.65 | 0.220111E+09 |
July | 0.607235E+09 | 0.448837E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8771635.73 | 0.166277E+09 |
August | 0.682256E+09 | 0.501910E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9906911.21 | 0.222968E+09 |
September | 0.605404E+09 | 0.459402E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7147042.36 | 0.344761E+09 |
October | 0.629366E+09 | 0.491662E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635852E+09 |
November | 0.623221E+09 | 0.511695E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101906E+10 |
December | 0.607235E+09 | 0.519262E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135082E+10 |
Annual Sum or Average | 0.755252E+10 | 0.584197E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58556967.46 | 0.881793E+10 |
Minimum of Months | 0.570983E+09 | 0.448837E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166277E+09 |
Maximum of Months | 0.682256E+09 | 0.522923E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25929636.65 | 0.159982E+10 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316745E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239382E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210235E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12788453.47 | 0.134450E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2808270.42 | 0.748025E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50541113.42 | 0.434558E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14162982.55 | 0.318619E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14012030.09 | 0.440830E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11495032.02 | 0.706565E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135400E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212164E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273533E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105808E+09 | 0.178677E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318619E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50541113.42 | 0.316745E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397613E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298303E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260566E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15666310.91 | 0.166723E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3599303.18 | 0.949614E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63737758.74 | 0.552675E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17856416.55 | 0.406345E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18545707.44 | 0.555971E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16406304.89 | 0.870681E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161835E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258445E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339483E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135812E+09 | 0.221650E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406345E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63737758.74 | 0.397613E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415752E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308386E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266988E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7266087.76 | 0.169997E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2577512.73 | 0.985747E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43245973.16 | 0.563392E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9006792.66 | 0.422732E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14086936.98 | 0.569699E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9959935.07 | 0.868463E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158596E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261176E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349306E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86143238.36 | 0.227120E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422732E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43245973.16 | 0.415752E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 18520.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 18520.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 18520.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 18520.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 18520.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 18520.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 18520.31 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 18520.31 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 18520.31 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 18520.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 18520.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 18520.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:40 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5587.34 | 29-JAN-11:00 |
February | 1306.65 | 01-FEB-10:09 | 1023.90 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3920.80 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 885.21 | 01-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2971.08 | 20-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 823.84 | 10-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 524.32 | 15-APR-17:01 | 2238.37 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.65 | 31-MAY-13:00 | 1441.92 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 600.53 | 11-JUN-15:05 | 1213.57 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.69 | 02-JUL-15:00 | 569.62 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.60 | 04-AUG-16:40 | 736.36 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 828.57 | 21-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.95 | 17-SEP-14:42 | 1092.21 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1134.77 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1580.77 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4293.95 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6589.90 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 569.62 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 600.53 | 6589.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 739.79 | 02-JAN-16:40 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3745.93 | 29-JAN-10:58 |
February | 827.22 | 01-FEB-10:09 | 656.04 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2612.16 | 10-FEB-22:01 |
March | 827.22 | 01-MAR-10:09 | 572.85 | 01-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2007.63 | 06-MAR-06:00 |
April | 827.22 | 03-APR-09:09 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 356.39 | 15-APR-17:01 | 1518.05 | 02-APR-23:55 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.43 | 31-MAY-13:00 | 966.78 | 01-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 418.02 | 11-JUN-15:05 | 808.80 | 02-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.65 | 02-JUL-15:37 | 378.95 | 09-JUL-10:00 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.07 | 04-AUG-16:40 | 501.79 | 06-AUG-09:00 |
September | 827.22 | 01-SEP-09:09 | 456.08 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.77 | 17-SEP-14:42 | 724.30 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 683.81 | 31-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1053.83 | 24-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 06-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2860.82 | 20-NOV-22:01 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-16:30 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4393.24 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.95 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 418.02 | 4393.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:40 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5646.60 | 29-JAN-10:53 |
February | 1306.65 | 01-FEB-10:09 | 987.94 | 14-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3922.87 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 840.07 | 01-MAR-16:00 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 3134.75 | 05-MAR-14:20 |
April | 1306.65 | 03-APR-09:09 | 816.80 | 10-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 401.39 | 15-APR-17:01 | 2238.38 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.65 | 31-MAY-13:00 | 1465.77 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 587.16 | 11-JUN-15:05 | 1218.35 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.53 | 02-JUL-15:35 | 573.86 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.60 | 04-AUG-16:40 | 803.05 | 06-AUG-14:00 |
September | 1306.65 | 01-SEP-09:09 | 807.58 | 21-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.32 | 10-SEP-15:18 | 1100.85 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1085.68 | 31-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1580.77 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4296.57 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6589.90 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.86 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 587.16 | 6589.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-16:40 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3745.93 | 29-JAN-11:00 |
February | 827.17 | 01-FEB-10:09 | 613.49 | 14-FEB-16:00 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2611.49 | 10-FEB-22:01 |
March | 827.17 | 01-MAR-10:09 | 572.64 | 14-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2007.63 | 06-MAR-06:00 |
April | 827.17 | 03-APR-09:09 | 544.28 | 10-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.60 | 15-APR-17:06 | 1524.42 | 02-APR-23:55 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.43 | 31-MAY-13:00 | 963.62 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 393.02 | 11-JUN-15:03 | 799.09 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.17 | 02-JUL-11:00 | 396.43 | 09-JUL-21:00 |
August | 827.17 | 01-AUG-09:09 | 456.05 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.07 | 04-AUG-16:40 | 504.32 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 551.29 | 21-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.79 | 17-SEP-12:00 | 790.08 | 24-SEP-16:30 |
October | 827.17 | 02-OCT-09:09 | 719.99 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1053.83 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 06-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2860.47 | 20-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:30 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4393.24 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.43 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 393.02 | 4393.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:40 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2983.42 | 29-JAN-10:53 |
February | 1306.65 | 01-FEB-10:09 | 1015.06 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2094.42 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 872.59 | 01-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1598.58 | 06-MAR-06:00 |
April | 1306.65 | 03-APR-09:09 | 808.60 | 10-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 389.97 | 15-APR-17:01 | 1179.79 | 02-APR-23:53 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.18 | 31-MAY-13:00 | 790.23 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 360.66 | 18-JUN-15:51 | 708.34 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.76 | 02-JUL-15:30 | 297.00 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.15 | 04-AUG-16:40 | 415.69 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 813.38 | 21-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.03 | 17-SEP-15:00 | 647.47 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1132.98 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 948.24 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2295.96 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3507.27 | 09-DEC-01:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.00 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 389.97 | 3507.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 739.79 | 02-JAN-16:40 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1988.94 | 29-JAN-11:00 |
February | 827.22 | 01-FEB-10:09 | 651.71 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1396.06 | 10-FEB-22:01 |
March | 827.22 | 01-MAR-10:09 | 567.15 | 01-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1065.72 | 06-MAR-06:00 |
April | 827.22 | 03-APR-09:09 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.44 | 15-APR-17:01 | 783.77 | 02-APR-23:53 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.12 | 31-MAY-13:00 | 551.22 | 01-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.82 | 18-JUN-16:10 | 487.50 | 02-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.85 | 02-JUL-15:30 | 204.00 | 09-JUL-10:00 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.43 | 04-AUG-16:40 | 286.19 | 06-AUG-09:00 |
September | 827.22 | 01-SEP-09:09 | 456.08 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.50 | 17-SEP-15:00 | 441.57 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 680.16 | 31-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 646.86 | 24-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 06-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1530.09 | 20-NOV-22:01 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-16:30 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2339.83 | 09-DEC-01:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.00 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 237.44 | 2339.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:40 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 63866.66 | 31-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 979.62 | 14-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 73449.75 | 02-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 824.80 | 01-MAR-16:00 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 40560.64 | 06-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 801.19 | 10-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4489.61 | 18-APR-12:00 | 34099.06 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5978.60 | 31-MAY-12:00 | 22391.21 | 02-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8372.64 | 26-JUN-16:05 | 15866.66 | 02-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6769.70 | 26-JUL-16:10 | 11142.09 | 24-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9902.76 | 04-AUG-16:03 | 15397.47 | 07-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 791.26 | 21-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7826.34 | 07-SEP-16:03 | 25187.41 | 29-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 1080.85 | 31-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 29598.11 | 23-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 46783.92 | 28-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 52584.06 | 08-DEC-17:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11142.09 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 9902.76 | 73449.75 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-16:40 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1988.94 | 29-JAN-11:00 |
February | 827.17 | 01-FEB-10:09 | 608.69 | 14-FEB-16:00 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1395.76 | 10-FEB-22:01 |
March | 827.17 | 01-MAR-10:09 | 564.26 | 14-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1065.72 | 06-MAR-06:00 |
April | 827.17 | 03-APR-09:09 | 537.71 | 10-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.50 | 15-APR-17:09 | 778.90 | 02-APR-23:53 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.12 | 31-MAY-13:00 | 539.07 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.16 | 11-JUN-15:05 | 473.87 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.60 | 02-JUL-11:30 | 217.78 | 09-JUL-21:00 |
August | 827.17 | 01-AUG-09:09 | 456.05 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.43 | 04-AUG-16:40 | 296.84 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 544.93 | 21-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.74 | 10-SEP-15:08 | 441.13 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 719.14 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 646.50 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 06-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1530.09 | 20-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:30 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2340.04 | 09-DEC-01:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.78 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 211.16 | 2340.04 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:40 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4674.09 | 29-JAN-11:00 |
February | 1306.65 | 01-FEB-10:09 | 1023.90 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3277.20 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 885.19 | 01-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2504.78 | 06-MAR-06:00 |
April | 1306.65 | 03-APR-09:09 | 823.82 | 10-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 458.00 | 15-APR-17:01 | 1874.98 | 02-APR-23:55 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.75 | 31-MAY-13:00 | 1289.67 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 498.00 | 11-JUN-14:51 | 1108.53 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.22 | 02-JUL-15:30 | 488.34 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.60 | 04-AUG-16:40 | 650.77 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 828.55 | 21-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.64 | 17-SEP-15:00 | 978.36 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1134.77 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1397.67 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3586.06 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5421.32 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.34 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 498.00 | 5421.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 739.79 | 02-JAN-16:40 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3135.40 | 29-JAN-10:53 |
February | 805.43 | 01-FEB-08:09 | 656.05 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2183.58 | 10-FEB-22:01 |
March | 805.43 | 01-MAR-08:09 | 572.84 | 01-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1711.89 | 05-MAR-10:00 |
April | 805.43 | 03-APR-07:10 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.52 | 15-APR-17:01 | 1250.97 | 02-APR-23:55 |
May | 805.43 | 01-MAY-07:10 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.84 | 31-MAY-13:00 | 861.98 | 01-MAY-24:00 |
June | 805.43 | 01-JUN-07:10 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 349.13 | 18-JUN-16:10 | 737.87 | 02-JUN-05:00 |
July | 805.43 | 03-JUL-07:10 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.07 | 02-JUL-15:30 | 340.02 | 09-JUL-10:00 |
August | 805.43 | 01-AUG-07:10 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.74 | 04-AUG-16:40 | 442.60 | 06-AUG-09:00 |
September | 805.43 | 01-SEP-07:10 | 456.08 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.25 | 17-SEP-15:00 | 647.64 | 18-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 683.81 | 31-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 931.84 | 24-OCT-05:00 |
November | 805.43 | 01-NOV-07:10 | 739.79 | 06-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2389.41 | 20-NOV-22:01 |
December | 805.43 | 01-DEC-08:09 | 739.79 | 01-DEC-16:30 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3611.49 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.02 | |||||
Maximum of Months | 805.43 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 349.13 | 3611.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:40 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4745.45 | 29-JAN-12:51 |
February | 1306.65 | 01-FEB-10:09 | 987.93 | 14-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3278.83 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 840.06 | 01-MAR-16:00 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2731.34 | 05-MAR-14:18 |
April | 1306.65 | 03-APR-09:09 | 816.78 | 10-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 363.04 | 15-APR-17:01 | 1872.82 | 02-APR-23:55 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.75 | 31-MAY-13:00 | 1309.04 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 488.94 | 11-JUN-15:16 | 1112.39 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.74 | 02-JUL-15:24 | 492.59 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.60 | 04-AUG-16:40 | 665.13 | 06-AUG-13:50 |
September | 1306.65 | 01-SEP-09:09 | 807.56 | 21-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.10 | 10-SEP-15:08 | 984.71 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1085.68 | 31-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1440.93 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3588.56 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5423.68 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.59 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 488.94 | 5423.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-16:40 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3116.04 | 29-JAN-10:58 |
February | 827.17 | 01-FEB-10:09 | 613.48 | 14-FEB-16:00 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2183.15 | 10-FEB-22:01 |
March | 827.17 | 01-MAR-10:09 | 572.65 | 14-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1669.85 | 06-MAR-05:55 |
April | 827.17 | 03-APR-09:09 | 544.27 | 10-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.35 | 15-APR-17:06 | 1251.71 | 02-APR-23:55 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.84 | 31-MAY-13:00 | 860.77 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.84 | 11-JUN-15:14 | 731.55 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.86 | 02-JUL-11:30 | 339.20 | 09-JUL-21:00 |
August | 827.17 | 01-AUG-09:09 | 456.05 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.74 | 04-AUG-16:40 | 445.14 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 551.28 | 21-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.59 | 17-SEP-11:40 | 668.98 | 24-SEP-16:03 |
October | 827.17 | 02-OCT-09:09 | 719.99 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 935.66 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 06-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2389.26 | 20-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:30 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3610.37 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.20 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 322.84 | 3610.37 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 6086.97 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4263.83 | 04-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 3447.22 | 21-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 578.07 | 15-APR-17:01 | 2681.68 | 02-APR-23:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.58 | 31-MAY-13:00 | 1817.65 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 660.58 | 11-JUN-14:51 | 1572.03 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.11 | 02-JUL-15:10 | 638.75 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.77 | 04-AUG-16:25 | 873.29 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.10 | 17-SEP-14:42 | 1376.89 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2093.31 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4535.46 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7400.13 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 638.75 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 660.58 | 7400.13 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 7573.60 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5368.11 | 04-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 4334.67 | 21-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727.32 | 15-APR-17:01 | 3217.07 | 02-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.30 | 31-MAY-13:00 | 2292.04 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 837.57 | 11-JUN-15:00 | 1968.72 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.03 | 02-JUL-15:10 | 803.95 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.37 | 04-AUG-16:25 | 1101.21 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.66 | 17-SEP-14:42 | 1733.48 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2508.18 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5653.72 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9231.46 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.95 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 837.57 | 9231.46 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 7958.87 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5655.28 | 10-FEB-22:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 4435.30 | 20-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 560.26 | 15-APR-17:01 | 3202.10 | 02-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.99 | 31-MAY-13:00 | 2182.66 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 627.57 | 18-JUN-16:00 | 1844.00 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.27 | 25-JUL-16:00 | 863.00 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.07 | 04-AUG-16:30 | 1124.31 | 06-AUG-09:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.65 | 06-SEP-16:00 | 1639.68 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2341.17 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6151.06 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9349.03 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 863.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 627.57 | 9349.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9210.60 | 13-JAN-17:00 | 12070.02 | 11086.35 | 29456.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10185.81 | 24-FEB-17:00 | 6035.01 | 5543.17 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16825.94 | 29-MAR-07:06 | 42245.05 | 38802.21 | 129642.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29763.45 | 20-APR-05:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43105.44 | 30-MAY-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 43433.80 | 27-JUN-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 44165.66 | 05-JUL-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43427.47 | 14-AUG-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43859.91 | 11-SEP-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19069.71 | 24-OCT-07:03 | 60350.08 | 55431.73 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19252.02 | 02-NOV-07:03 | 42245.05 | 38802.21 | 129642.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9819.79 | 07-DEC-16:15 | 12070.02 | 11086.35 | 29456.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 9210.60 | 0.00 | 2463.50 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44165.66 | 60350.08 | 55431.73 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1329.26 |
February | 619.68 | 24-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.32 |
March | 1986.84 | 25-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.79 |
April | 8837.61 | 18-APR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.92 | 0.00 |
May | 9994.70 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.16 | 0.00 |
June | 11473.06 | 26-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.72 | 0.00 |
July | 10764.43 | 05-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.31 | 0.00 |
August | 11342.45 | 04-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.27 | 0.00 |
September | 10209.81 | 07-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.66 | 0.00 |
October | 3772.62 | 20-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.31 |
November | 1888.11 | 03-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.38 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1744.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11473.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.27 | 1744.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2736.94 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1767.89 |
February | 2386.76 | 16-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1982.95 |
March | 1723.59 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1570.13 |
April | 3559.95 | 18-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.53 | 0.00 |
May | 4164.60 | 30-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.98 | 0.00 |
June | 5524.46 | 26-JUN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.04 | 0.00 |
July | 5466.74 | 05-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.84 |
August | 4982.37 | 04-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.94 | 0.00 |
September | 4654.62 | 08-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.72 | 0.00 |
October | 2177.47 | 13-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.86 |
November | 1739.38 | 25-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3085.62 |
December | 2380.63 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1559.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1723.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5524.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.94 | 3085.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3258.42 | 05-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.67 |
February | 4316.50 | 02-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.38 |
March | 2460.95 | 22-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.77 |
April | 3568.02 | 18-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.83 | 0.00 |
May | 4248.05 | 31-MAY-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.58 | 0.00 |
June | 5877.00 | 26-JUN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.17 | 0.00 |
July | 5755.13 | 05-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.88 |
August | 5041.43 | 04-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.65 | 0.00 |
September | 5023.36 | 11-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.05 | 0.00 |
October | 2422.63 | 31-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.41 |
November | 2318.01 | 09-NOV-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.81 |
December | 2940.85 | 08-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2318.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5877.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.65 | 1437.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6345.89 | 13-JAN-17:00 | 12070.02 | 11086.35 | 14286.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6584.77 | 24-FEB-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7463.68 | 24-MAR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26152.12 | 17-APR-05:03 | 1905.79 | 1847.62 | 9524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26477.21 | 30-MAY-05:03 | 1905.79 | 1847.62 | 9524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32356.54 | 12-JUN-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32292.02 | 03-JUL-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31059.54 | 15-AUG-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32747.35 | 11-SEP-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9502.30 | 20-OCT-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9135.16 | 03-NOV-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6163.76 | 01-DEC-16:20 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6163.76 | 0.00 | 1847.62 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32747.35 | 12070.02 | 11086.35 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6157.85 | 13-JAN-16:50 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6698.17 | 24-FEB-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7652.17 | 24-MAR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17335.30 | 17-APR-15:30 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20568.26 | 30-MAY-05:03 | 1905.79 | 1847.62 | 9524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34197.53 | 26-JUN-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34743.44 | 03-JUL-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32929.47 | 28-AUG-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33829.26 | 11-SEP-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9097.63 | 20-OCT-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8067.81 | 03-NOV-15:50 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6019.42 | 01-DEC-16:10 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6019.42 | 0.00 | 1847.62 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34743.44 | 6035.01 | 5543.17 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1090.91 | 21-JAN-17:02 | 401.76 | 389.54 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 683.17 |
February | 1251.53 | 24-FEB-16:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.78 |
March | 1643.13 | 28-MAR-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.24 |
April | 5843.35 | 18-APR-15:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 116.87 | 0.00 |
May | 6387.18 | 31-MAY-15:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 72.23 | 0.00 |
June | 13072.67 | 11-JUN-14:22 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 347.50 | 0.00 |
July | 8738.58 | 02-JUL-18:12 | 0.00 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 61.16 | 0.00 |
August | 7108.96 | 04-AUG-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 95.01 | 0.00 |
September | 6319.43 | 11-SEP-14:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 96.84 | 0.00 |
October | 1841.50 | 20-OCT-13:40 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.19 |
November | 1656.28 | 03-NOV-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.01 |
December | 1109.08 | 02-DEC-17:03 | 267.84 | 259.70 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1090.91 | 0.00 | 240.15 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13072.67 | 1306.65 | 720.41 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 347.50 | 683.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 967.02 | 21-JAN-17:02 | 254.35 | 246.61 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.76 |
February | 1458.42 | 24-FEB-10:15 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.42 |
March | 2313.61 | 28-MAR-09:35 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.39 |
April | 7791.57 | 18-APR-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 2.96 | 0.00 |
May | 10734.81 | 29-MAY-08:53 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.61 |
June | 15465.54 | 11-JUN-09:01 | 296.74 | 177.38 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.75 |
July | 14191.78 | 02-JUL-09:32 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.92 |
August | 11767.02 | 27-AUG-09:02 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.56 |
September | 11095.58 | 03-SEP-09:32 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.60 |
October | 2786.94 | 20-OCT-09:50 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.20 |
November | 1456.83 | 03-NOV-14:50 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.51 |
December | 985.05 | 02-DEC-17:03 | 169.56 | 164.41 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 967.02 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15465.54 | 1654.44 | 912.16 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 2.96 | 454.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4362.51 | 12-JAN-12:40 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.34 |
February | 7802.29 | 24-FEB-13:50 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.43 |
March | 8105.03 | 24-MAR-13:40 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.78 |
April | 17950.13 | 16-APR-13:02 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.52 |
May | 10407.26 | 30-MAY-13:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 23.77 | 0.00 |
June | 17736.03 | 11-JUN-14:22 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 298.62 | 0.00 |
July | 17372.58 | 30-JUL-13:22 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
August | 17417.24 | 13-AUG-13:02 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.68 |
September | 19001.31 | 04-SEP-13:42 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.79 |
October | 12543.24 | 01-OCT-14:13 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.45 |
November | 10057.95 | 03-NOV-13:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.37 |
December | 5615.79 | 01-DEC-13:30 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4362.51 | 267.84 | 160.10 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19001.31 | 1306.65 | 720.41 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 298.62 | 536.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1458.27 | 12-JAN-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.40 |
February | 2652.83 | 24-FEB-16:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.66 |
March | 2954.15 | 23-MAR-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.36 |
April | 15947.10 | 16-APR-16:21 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 85.39 | 0.00 |
May | 16197.41 | 21-MAY-16:32 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.03 |
June | 16370.28 | 25-JUN-17:21 | 0.00 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 183.85 | 0.00 |
July | 16305.11 | 02-JUL-16:52 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 37.26 | 0.00 |
August | 13485.73 | 13-AUG-16:22 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.64 |
September | 16127.01 | 04-SEP-15:42 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.35 |
October | 5397.61 | 20-OCT-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.71 |
November | 3418.70 | 03-NOV-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.32 |
December | 1457.02 | 01-DEC-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1457.02 | 0.00 | 126.69 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16370.28 | 805.38 | 456.05 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 183.85 | 272.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1044.51 | 14-JAN-17:02 | 334.80 | 324.62 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.43 |
February | 1058.25 | 25-FEB-17:03 | 200.88 | 143.29 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.12 |
March | 1335.24 | 28-MAR-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.01 |
April | 3073.50 | 18-APR-15:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 62.90 | 0.00 |
May | 4017.17 | 31-MAY-15:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 38.74 | 0.00 |
June | 5549.64 | 26-JUN-14:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 44.04 | 0.00 |
July | 5918.87 | 05-JUL-06:03 | 803.52 | 720.40 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 |
August | 5768.19 | 04-AUG-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 50.78 | 0.00 |
September | 5583.04 | 11-SEP-14:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 52.04 | 0.00 |
October | 1700.31 | 20-OCT-14:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.94 |
November | 1575.86 | 03-NOV-15:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.61 |
December | 1058.79 | 02-DEC-17:03 | 267.84 | 259.70 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1044.51 | 200.88 | 143.29 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5918.87 | 1306.65 | 720.41 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 62.90 | 235.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 862.35 | 13-JAN-11:00 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.58 |
February | 1076.31 | 24-FEB-10:20 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.82 |
March | 1281.08 | 28-MAR-10:00 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.54 |
April | 5113.08 | 18-APR-09:40 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 | 0.00 |
May | 6128.97 | 31-MAY-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 0.00 |
June | 11810.39 | 11-JUN-09:01 | 296.74 | 177.38 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.64 |
July | 12068.80 | 02-JUL-09:21 | 296.74 | 177.38 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.68 |
August | 8491.44 | 20-AUG-09:43 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.21 |
September | 8911.72 | 04-SEP-10:23 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.06 |
October | 2425.67 | 20-OCT-10:00 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.72 |
November | 1268.92 | 03-NOV-10:40 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.58 |
December | 872.76 | 05-DEC-09:30 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 862.35 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12068.80 | 1654.44 | 912.16 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 351.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1152.07 | 13-JAN-14:40 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3350.77 |
February | 1482.47 | 25-FEB-15:30 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.56 |
March | 2581.90 | 24-MAR-14:00 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2039.07 |
April | 10811.33 | 18-APR-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 4489.61 | 0.00 |
May | 11179.97 | 31-MAY-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 5978.60 | 0.00 |
June | 13456.00 | 11-JUN-13:02 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 137.34 | 0.00 |
July | 13661.19 | 02-JUL-13:22 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 37.57 | 0.00 |
August | 12499.50 | 04-AUG-16:10 | 1607.03 | 1600.90 | 3346.41 | 0.00 | 0.00 | 0.00 | 0.00 | 8721.60 | 0.00 |
September | 14583.17 | 04-SEP-13:42 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.75 |
October | 8627.69 | 20-OCT-14:00 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.77 |
November | 7178.69 | 04-NOV-13:30 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.35 |
December | 1440.49 | 02-DEC-12:40 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1152.07 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14583.17 | 1607.03 | 1600.90 | 3346.41 | 0.00 | 0.00 | 0.00 | 0.00 | 8721.60 | 3350.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1114.38 | 12-JAN-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.63 |
February | 1435.99 | 24-FEB-16:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.26 |
March | 1412.47 | 23-MAR-16:50 | 254.33 | 253.36 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.05 |
April | 8865.99 | 15-APR-17:06 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 111.47 | 0.00 |
May | 10627.20 | 21-MAY-17:52 | 0.00 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.50 |
June | 12219.74 | 25-JUN-17:32 | 0.00 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 129.86 | 0.00 |
July | 13495.15 | 02-JUL-18:01 | 0.00 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 |
August | 9837.08 | 05-AUG-17:05 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.91 |
September | 12223.75 | 04-SEP-15:42 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.31 |
October | 4474.01 | 11-OCT-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.20 |
November | 2877.46 | 03-NOV-15:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.71 |
December | 1171.71 | 01-DEC-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1114.38 | 0.00 | 126.69 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13495.15 | 805.38 | 456.05 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.86 | 122.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 963.61 | 14-JAN-17:02 | 334.80 | 324.62 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.26 |
February | 1134.83 | 24-FEB-16:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.94 |
March | 1468.74 | 28-MAR-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.99 |
April | 5370.43 | 18-APR-15:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 97.88 | 0.00 |
May | 5761.06 | 31-MAY-15:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 60.39 | 0.00 |
June | 10360.61 | 25-JUN-19:12 | 0.00 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 97.58 | 0.00 |
July | 10281.17 | 02-JUL-18:41 | 0.00 | 280.18 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 18.52 | 0.00 |
August | 6374.76 | 04-AUG-15:10 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 79.31 | 0.00 |
September | 6064.05 | 11-SEP-14:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 81.04 | 0.00 |
October | 1814.18 | 20-OCT-13:30 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.86 |
November | 1621.77 | 03-NOV-13:30 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.51 |
December | 977.26 | 02-DEC-17:03 | 267.84 | 259.70 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 963.61 | 0.00 | 240.15 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10360.61 | 1306.65 | 720.41 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 97.88 | 369.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1116.36 | 12-JAN-10:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.66 |
February | 1539.78 | 24-FEB-10:00 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.26 |
March | 2928.30 | 28-MAR-09:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.39 |
April | 7736.55 | 18-APR-09:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.07 |
May | 10874.83 | 28-MAY-08:22 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.81 |
June | 15213.96 | 25-JUN-08:31 | 296.74 | 177.38 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.75 |
July | 15284.60 | 02-JUL-08:41 | 296.74 | 177.38 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.90 |
August | 10685.35 | 20-AUG-10:13 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.61 |
September | 11542.36 | 03-SEP-08:32 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.46 |
October | 3473.87 | 20-OCT-08:55 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.12 |
November | 1579.23 | 03-NOV-13:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.92 |
December | 1082.81 | 05-DEC-09:50 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1082.81 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.07 | |
Maximum of Months | 15284.60 | 1610.86 | 912.16 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5027.57 | 12-JAN-12:30 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.95 |
February | 7895.86 | 24-FEB-13:35 | 2544.47 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.48 |
March | 8179.03 | 24-MAR-13:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.04 |
April | 12714.02 | 16-APR-13:53 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 79.57 | 0.00 |
May | 10466.46 | 29-MAY-12:33 | 200.88 | 120.08 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.67 |
June | 15886.50 | 25-JUN-13:12 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 259.33 | 0.00 |
July | 16220.68 | 30-JUL-11:52 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.73 |
August | 15725.79 | 13-AUG-12:53 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.63 |
September | 15975.64 | 04-SEP-13:12 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.09 |
October | 11224.33 | 20-OCT-13:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.44 |
November | 10220.03 | 03-NOV-13:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.37 |
December | 6106.03 | 01-DEC-13:30 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5027.57 | 200.88 | 120.08 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16220.68 | 2544.47 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 259.33 | 268.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1416.61 | 12-JAN-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.79 |
February | 2683.35 | 24-FEB-16:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.93 |
March | 3032.90 | 23-MAR-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.96 |
April | 13594.13 | 15-APR-17:04 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 165.58 | 0.00 |
May | 14847.92 | 14-MAY-17:22 | 0.00 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.77 |
June | 15208.05 | 25-JUN-17:11 | 0.00 | 253.38 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 150.70 | 0.00 |
July | 16035.81 | 02-JUL-16:41 | 381.49 | 228.04 | 2859.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.12 |
August | 14438.19 | 13-AUG-16:11 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.63 |
September | 12296.50 | 04-SEP-17:12 | 0.00 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.80 |
October | 5331.37 | 20-OCT-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.53 |
November | 3575.15 | 03-NOV-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.83 |
December | 1428.12 | 01-DEC-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1416.61 | 0.00 | 126.69 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16035.81 | 805.38 | 456.05 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 165.58 | 197.79 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.234758E+12 | 260351.92 | 02-JAN-07:10 | 0.123005E+12 | 170488.10 | 31-JAN-07:00 |
February | 0.173348E+12 | 254288.60 | 06-FEB-07:10 | 0.851585E+11 | 199639.57 | 02-FEB-07:40 |
March | 0.150812E+12 | 226603.12 | 06-MAR-07:10 | 0.532057E+11 | 96908.59 | 06-MAR-08:09 |
April | 0.117816E+12 | 193670.67 | 03-APR-06:10 | 0.253618E+11 | 74419.31 | 03-APR-06:30 |
May | 0.115855E+12 | 144894.67 | 31-MAY-15:09 | 0.105666E+11 | 32608.70 | 02-MAY-06:19 |
June | 0.140911E+12 | 182118.45 | 26-JUN-07:49 | 0.948413E+10 | 11852.56 | 03-JUN-06:00 |
July | 0.151259E+12 | 171819.39 | 05-JUL-10:50 | 0.894876E+10 | 9242.58 | 03-JUL-11:20 |
August | 0.155900E+12 | 181476.35 | 04-AUG-15:30 | 0.933430E+10 | 9162.07 | 01-AUG-11:00 |
September | 0.120662E+12 | 151553.18 | 07-SEP-15:00 | 0.990361E+10 | 39358.91 | 29-SEP-06:40 |
October | 0.110751E+12 | 125513.31 | 16-OCT-06:10 | 0.173161E+11 | 50366.97 | 23-OCT-06:10 |
November | 0.149959E+12 | 244597.17 | 27-NOV-07:10 | 0.486204E+11 | 116650.20 | 25-NOV-07:30 |
December | 0.200230E+12 | 255810.39 | 11-DEC-07:10 | 0.914183E+11 | 139831.06 | 09-DEC-07:40 |
Annual Sum or Average | 0.182226E+13 | 0.492323E+12 | ||||
Minimum of Months | 0.110751E+12 | 125513.31 | 0.894876E+10 | 9162.07 | ||
Maximum of Months | 0.234758E+12 | 260351.92 | 0.123005E+12 | 199639.57 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.239915E+11 | 0.790094E+10 | 0.641572E+11 | 0.109138E+10 | 0.692757E+10 | 1312252.65 | 0.130688E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.214542E+11 | 0.649106E+10 | 0.580684E+11 | 0.987374E+09 | 0.524553E+10 | 1186778.30 | 0.811003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251520E+11 | 0.629373E+10 | 0.666107E+11 | 0.114316E+10 | 0.515471E+10 | 1343621.24 | 0.463262E+11 | 0.129674E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223521E+11 | 0.517577E+10 | 0.619407E+11 | 0.105056E+10 | 0.566483E+10 | 1267813.82 | 0.173206E+11 | 0.431060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.239722E+11 | 0.460403E+10 | 0.653840E+11 | 0.111683E+10 | 0.778236E+10 | 1327936.95 | 0.173637E+10 | 0.112581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.238193E+11 | 0.410813E+10 | 0.641577E+11 | 0.109954E+10 | 0.136781E+11 | 1296568.36 | 0.573032E+09 | 0.334743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.223290E+11 | 0.437123E+10 | 0.631525E+11 | 0.106756E+10 | 0.151650E+11 | 1299182.41 | 48050461.97 | 0.451239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.249049E+11 | 0.499663E+10 | 0.666107E+11 | 0.114303E+10 | 0.151929E+11 | 1343621.24 | 0.176790E+09 | 0.428740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.224197E+11 | 0.568261E+10 | 0.619118E+11 | 0.105018E+10 | 0.967852E+10 | 1267813.82 | 0.209473E+10 | 0.178231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.234861E+11 | 0.681724E+10 | 0.641717E+11 | 0.109108E+10 | 0.494802E+10 | 1312252.65 | 0.912989E+10 | 0.110514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.236409E+11 | 0.741320E+10 | 0.627379E+11 | 0.107134E+10 | 0.508763E+10 | 1278270.02 | 0.499638E+11 | 43382059.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.234339E+11 | 0.812435E+10 | 0.631380E+11 | 0.106835E+10 | 0.584151E+10 | 1299182.41 | 0.986224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280956E+12 | 0.719789E+11 | 0.762041E+12 | 0.129804E+11 | 0.100367E+12 | 15535293.87 | 0.437780E+12 | 0.156142E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.214542E+11 | 0.410813E+10 | 0.580684E+11 | 0.987374E+09 | 0.494802E+10 | 1186778.30 | 48050461.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.251520E+11 | 0.812435E+10 | 0.666107E+11 | 0.114316E+10 | 0.151929E+11 | 1343621.24 | 0.130688E+12 | 0.451239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.112562E+12 | 0.00 | 0.104430E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.755941E+11 | 0.00 | 0.956444E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.422567E+11 | 0.00 | 0.109489E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.154970E+11 | 0.00 | 0.986476E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.540051E+09 | 0.00 | 0.100265E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 32949952.77 | 0.00 | 0.945118E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.894876E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.933430E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.116604E+10 | 0.00 | 0.873757E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.801965E+10 | 0.00 | 0.929640E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.391506E+11 | 0.00 | 0.946989E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.814729E+11 | 0.00 | 0.994538E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.376292E+12 | 0.00 | 0.116031E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.873757E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.112562E+12 | 0.00 | 0.109489E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28079.40 | 02-JAN-16:40 | 5557.43 | 01-JAN-06:10 | 47562.27 | 02-JAN-08:09 | 926.74 | 02-JAN-16:49 | 7743.91 | 02-JAN-06:19 | 0.73 | 02-JAN-06:10 | 215582.80 | 02-JAN-07:10 |
February | 26373.66 | 14-FEB-16:00 | 5557.43 | 01-FEB-06:10 | 47562.27 | 01-FEB-08:09 | 924.69 | 22-FEB-08:20 | 7271.77 | 06-FEB-07:10 | 0.73 | 01-FEB-06:10 | 209989.67 | 06-FEB-07:10 |
March | 24960.72 | 01-MAR-16:00 | 5557.43 | 01-MAR-06:10 | 47562.27 | 01-MAR-08:09 | 923.00 | 14-MAR-07:19 | 6432.98 | 06-MAR-07:10 | 0.73 | 01-MAR-07:10 | 189571.42 | 06-MAR-07:10 |
April | 24515.06 | 10-APR-07:10 | 5557.43 | 01-APR-05:10 | 47562.27 | 03-APR-07:10 | 923.08 | 10-APR-07:19 | 22230.06 | 18-APR-15:09 | 0.73 | 03-APR-06:10 | 157918.80 | 03-APR-06:10 |
May | 23688.37 | 01-MAY-07:10 | 5557.43 | 01-MAY-19:10 | 47562.27 | 01-MAY-07:10 | 921.90 | 01-MAY-07:19 | 24267.29 | 31-MAY-15:09 | 0.73 | 02-MAY-07:10 | 48757.92 | 02-MAY-06:10 |
June | 23688.37 | 01-JUN-07:10 | 5557.43 | 01-JUN-19:40 | 47562.27 | 01-JUN-07:10 | 921.90 | 01-JUN-07:19 | 32062.24 | 26-JUN-15:50 | 0.73 | 25-JUN-16:40 | 19500.23 | 05-JUN-06:10 |
July | 23688.37 | 03-JUL-07:10 | 5557.43 | 01-JUL-19:00 | 47562.27 | 03-JUL-07:10 | 921.90 | 03-JUL-07:19 | 31975.66 | 03-JUL-15:30 | 0.73 | 01-JUL-05:10 | 6135.22 | 24-JUL-06:10 |
August | 23688.37 | 01-AUG-07:10 | 5557.43 | 01-AUG-19:40 | 47562.27 | 01-AUG-07:10 | 921.90 | 01-AUG-07:19 | 28619.61 | 04-AUG-15:30 | 0.73 | 01-AUG-05:30 | 10727.61 | 07-AUG-06:19 |
September | 24522.16 | 21-SEP-07:10 | 5557.43 | 01-SEP-05:10 | 47562.27 | 01-SEP-07:10 | 923.09 | 21-SEP-07:19 | 24721.51 | 07-SEP-15:00 | 0.73 | 18-SEP-16:10 | 58181.73 | 30-SEP-06:10 |
October | 27491.14 | 31-OCT-07:10 | 5557.43 | 01-OCT-05:10 | 47562.27 | 02-OCT-07:10 | 927.36 | 31-OCT-07:19 | 8978.85 | 20-OCT-15:09 | 0.73 | 06-OCT-07:10 | 84708.66 | 16-OCT-06:10 |
November | 28079.40 | 06-NOV-16:00 | 5557.43 | 01-NOV-05:10 | 47562.27 | 01-NOV-07:10 | 927.80 | 03-NOV-07:19 | 6872.82 | 27-NOV-07:10 | 0.73 | 09-NOV-18:10 | 200697.19 | 27-NOV-07:10 |
December | 28079.40 | 01-DEC-16:30 | 5557.43 | 01-DEC-06:10 | 47562.27 | 01-DEC-08:09 | 927.16 | 22-DEC-08:20 | 7515.78 | 11-DEC-07:10 | 0.73 | 01-DEC-07:10 | 211267.45 | 11-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 23688.37 | 5557.43 | 47562.27 | 921.90 | 6432.98 | 0.73 | 6135.22 | |||||||
Maximum of Months | 28079.40 | 5557.43 | 47562.27 | 927.80 | 32062.24 | 0.73 | 215582.80 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6608.81 | 25-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 50505.17 | 18-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 52612.08 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82666.11 | 26-JUN-07:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76851.65 | 05-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84477.23 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 63860.27 | 06-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20800.93 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3710.79 | 03-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84477.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 260351.92 | 02-JAN-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 7741.95 | 0.73 | 215582.80 | 0.00 | 0.00 |
February | 254288.60 | 06-FEB-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 7271.77 | 0.73 | 209989.67 | 0.00 | 0.00 |
March | 226603.12 | 06-MAR-07:10 | 8488.76 | 21853.28 | 0.00 | 255.95 | 6432.98 | 0.73 | 189571.42 | 0.00 | 0.00 |
April | 193670.67 | 03-APR-06:10 | 8397.12 | 21853.28 | 0.00 | 255.95 | 5244.80 | 0.73 | 157918.80 | 0.00 | 0.00 |
May | 144894.67 | 31-MAY-15:09 | 23688.37 | 43769.98 | 0.00 | 920.43 | 24267.29 | 0.73 | 0.00 | 52247.87 | 0.00 |
June | 182118.45 | 26-JUN-07:49 | 23688.37 | 47562.27 | 0.00 | 921.90 | 27279.07 | 0.73 | 0.00 | 82666.11 | 0.00 |
July | 171819.39 | 05-JUL-10:50 | 23688.37 | 43275.33 | 0.00 | 920.24 | 27083.07 | 0.73 | 0.00 | 76851.65 | 0.00 |
August | 181476.35 | 04-AUG-15:30 | 23688.37 | 43769.98 | 0.00 | 920.43 | 28619.61 | 0.73 | 0.00 | 84477.23 | 0.00 |
September | 151553.18 | 07-SEP-15:00 | 23688.37 | 43769.98 | 0.00 | 920.43 | 24721.51 | 0.73 | 0.00 | 58452.17 | 0.00 |
October | 125513.31 | 16-OCT-06:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 3777.49 | 0.73 | 84708.66 | 0.00 | 0.00 |
November | 244597.17 | 27-NOV-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 6872.82 | 0.73 | 200697.19 | 0.00 | 0.00 |
December | 255810.39 | 11-DEC-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 7515.78 | 0.73 | 211267.45 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 125513.31 | 8397.12 | 21853.28 | 0.00 | 255.95 | 3777.49 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 260351.92 | 23688.37 | 47562.27 | 5557.43 | 921.90 | 28619.61 | 0.73 | 215582.80 | 84477.23 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 162258.20 | 31-JAN-07:00 | 0.00 | 11920.91 | 30-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 191716.84 | 02-FEB-07:30 | 0.00 | 12054.05 | 21-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 88120.98 | 06-MAR-07:30 | 0.00 | 12013.39 | 01-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 66604.24 | 03-APR-06:40 | 0.00 | 11253.39 | 04-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 24413.20 | 02-MAY-06:19 | 0.00 | 9834.22 | 04-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 5421.94 | 03-JUN-06:10 | 0.00 | 9401.94 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9242.58 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9162.07 | 01-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 31901.70 | 30-SEP-06:19 | 0.00 | 9219.80 | 28-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 44421.47 | 23-OCT-06:19 | 0.00 | 9353.54 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 109772.21 | 25-NOV-17:00 | 0.00 | 9511.35 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 132619.56 | 09-DEC-07:30 | 0.00 | 10820.94 | 26-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9162.07 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 191716.84 | 0.00 | 12054.05 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.51 | 0.50 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.69 | 0.67 | 25.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.18 | 0.00 | 26.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 19.51 | 0.50 | 19.51 | 1.83 | 23.56 | 0.67 | 23.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.51 | 0.50 | 19.51 | 1.50 | 26.18 | 0.67 | 26.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 18.50 | 1.17 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
February | 0.17 | 19.30 | 0.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.61 | 0.17 | 24.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.32 | 0.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
December | 0.67 | 18.10 | 0.33 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 |
Annual Sum or Average | 2.83 | 18.50 | 1.83 | 18.83 | 0.17 | 19.03 | 0.17 | 19.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.32 | 1.17 | 19.32 | 0.17 | 24.61 | 0.17 | 24.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.33 | 18.80 | 4.83 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
February | 3.33 | 18.27 | 2.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
March | 0.67 | 18.71 | 0.50 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
April | 0.17 | 19.32 | 0.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.67 | 18.81 | 1.33 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
December | 3.67 | 18.76 | 2.67 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
Annual Sum or Average | 15.83 | 18.68 | 11.50 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.33 | 19.32 | 4.83 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 119.17 | 16.01 | 58.17 | 16.47 | 0.00 | 16.47 | 0.00 | 16.47 |
February | 60.83 | 16.30 | 29.50 | 16.83 | 0.00 | 16.83 | 0.00 | 16.83 |
March | 19.17 | 15.84 | 6.67 | 16.18 | 0.00 | 16.18 | 0.00 | 16.18 |
April | 3.33 | 15.64 | 0.50 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.54 | 2.50 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.40 | 0.00 | 27.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
November | 30.33 | 15.76 | 11.17 | 16.21 | 0.00 | 16.21 | 0.00 | 16.21 |
December | 64.00 | 15.81 | 27.67 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
Annual Sum or Average | 297.00 | 15.98 | 133.67 | 16.45 | 4.17 | 16.56 | 2.50 | 16.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.17 | 17.18 | 58.17 | 17.18 | 3.83 | 27.54 | 2.50 | 27.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 74.33 | 14.54 | 22.33 | 14.61 | 0.00 | 14.61 | 0.00 | 14.61 |
February | 34.83 | 14.71 | 6.83 | 14.82 | 0.00 | 14.82 | 0.00 | 14.82 |
March | 13.33 | 15.00 | 1.33 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
April | 2.83 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.60 | 2.67 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.05 | 6.00 | 28.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.06 | 7.00 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.80 | 1.83 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.68 | 2.33 | 27.68 |
October | 0.33 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
November | 24.33 | 14.60 | 4.83 | 14.59 | 0.00 | 14.59 | 0.00 | 14.59 |
December | 46.17 | 14.64 | 11.33 | 14.66 | 0.00 | 14.66 | 0.00 | 14.66 |
Annual Sum or Average | 196.17 | 14.64 | 46.67 | 14.69 | 20.50 | 15.72 | 19.83 | 16.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.59 | 0.00 | 14.59 |
Maximum of Months | 74.33 | 17.22 | 22.33 | 17.22 | 7.00 | 28.06 | 7.00 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 66.33 | 14.99 | 17.83 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
February | 33.50 | 15.55 | 9.33 | 16.04 | 0.00 | 16.04 | 0.00 | 16.04 |
March | 12.17 | 15.39 | 1.33 | 15.55 | 0.00 | 15.55 | 0.00 | 15.55 |
April | 2.67 | 14.85 | 0.00 | 14.85 | 1.67 | 19.89 | 1.67 | 22.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.46 | 0.83 | 27.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.88 | 4.33 | 27.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.81 | 5.00 | 27.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.64 | 3.83 | 27.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.01 | 4.67 | 28.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.44 | 0.50 | 27.44 |
November | 18.33 | 14.86 | 4.50 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
December | 38.50 | 15.14 | 10.83 | 15.38 | 0.00 | 15.38 | 0.00 | 15.38 |
Annual Sum or Average | 171.50 | 15.15 | 43.83 | 15.42 | 22.67 | 16.60 | 20.83 | 17.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.98 | 0.00 | 14.98 |
Maximum of Months | 66.33 | 15.55 | 17.83 | 16.04 | 5.83 | 28.01 | 5.00 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 70.50 | 14.43 | 19.67 | 14.45 | 0.00 | 14.45 | 0.00 | 14.45 |
February | 34.50 | 14.65 | 8.17 | 14.74 | 0.00 | 14.74 | 0.00 | 14.74 |
March | 13.17 | 15.00 | 1.83 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
April | 3.83 | 14.94 | 0.83 | 14.96 | 1.50 | 18.26 | 1.00 | 19.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.01 | 1.67 | 28.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.59 | 3.33 | 28.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.34 | 4.83 | 28.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.99 | 2.33 | 27.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.00 | 2.50 | 28.04 |
October | 0.33 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
November | 23.17 | 14.56 | 5.17 | 14.54 | 0.00 | 14.54 | 0.00 | 14.54 |
December | 44.50 | 14.58 | 11.00 | 14.58 | 0.00 | 14.58 | 0.00 | 14.58 |
Annual Sum or Average | 190.00 | 14.58 | 46.67 | 14.59 | 27.00 | 15.99 | 15.67 | 16.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 | 0.00 | 14.45 |
Maximum of Months | 70.50 | 17.19 | 19.67 | 17.19 | 10.00 | 28.59 | 4.83 | 28.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 78.50 | 17.92 | 55.33 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 |
February | 57.50 | 18.16 | 42.67 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
March | 8.00 | 17.53 | 4.17 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
April | 0.67 | 19.14 | 0.50 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10.50 | 16.86 | 5.00 | 17.39 | 0.00 | 17.39 | 0.00 | 17.39 |
December | 24.83 | 17.29 | 15.33 | 17.74 | 0.00 | 17.74 | 0.00 | 17.74 |
Annual Sum or Average | 180.00 | 17.84 | 123.00 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.50 | 19.14 | 55.33 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.17 | 15.28 | 6.17 | 15.43 | 0.00 | 15.43 | 0.00 | 15.43 |
February | 14.00 | 15.33 | 1.83 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 |
March | 2.67 | 15.72 | 0.00 | 15.72 | 0.00 | 15.72 | 0.00 | 15.72 |
April | 0.17 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.67 | 3.50 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.70 | 5.00 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.56 | 1.50 | 26.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.51 | 2.17 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.00 | 15.36 | 1.00 | 15.41 | 0.00 | 15.41 | 0.00 | 15.41 |
December | 10.67 | 15.29 | 2.00 | 15.34 | 0.00 | 15.34 | 0.00 | 15.34 |
Annual Sum or Average | 59.67 | 15.33 | 11.00 | 15.45 | 12.33 | 17.24 | 12.33 | 18.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.17 | 16.64 | 6.17 | 16.64 | 5.00 | 27.70 | 5.00 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 211.17 | 15.47 | 191.33 | 15.49 | 0.00 | 15.49 | 0.00 | 15.49 |
February | 129.50 | 15.48 | 120.67 | 15.49 | 0.00 | 15.49 | 0.00 | 15.49 |
March | 84.17 | 16.50 | 83.33 | 16.50 | 0.00 | 16.50 | 0.00 | 16.50 |
April | 49.33 | 17.71 | 49.17 | 17.71 | 0.67 | 17.78 | 0.67 | 17.84 |
May | 10.33 | 19.11 | 10.33 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
June | 2.00 | 19.64 | 2.00 | 19.64 | 3.50 | 22.58 | 3.50 | 23.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.54 | 2.50 | 27.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 25.91 | 3.50 | 25.91 |
September | 8.17 | 18.91 | 8.17 | 18.91 | 19.00 | 22.52 | 19.00 | 23.60 |
October | 29.00 | 18.62 | 29.00 | 18.62 | 0.33 | 18.67 | 0.33 | 18.72 |
November | 70.00 | 16.46 | 67.33 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 |
December | 135.17 | 15.71 | 125.00 | 15.73 | 0.00 | 15.73 | 0.00 | 15.73 |
Annual Sum or Average | 728.83 | 16.11 | 686.33 | 16.14 | 29.50 | 16.34 | 29.50 | 16.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.49 | 0.00 | 15.49 |
Maximum of Months | 211.17 | 19.64 | 191.33 | 19.64 | 19.00 | 27.54 | 19.00 | 27.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.67 | 15.19 | 5.67 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
February | 14.17 | 15.34 | 2.50 | 15.47 | 0.00 | 15.47 | 0.00 | 15.47 |
March | 2.50 | 15.84 | 0.00 | 15.84 | 0.00 | 15.84 | 0.00 | 15.84 |
April | 0.17 | 16.59 | 0.00 | 16.59 | 0.83 | 25.89 | 0.50 | 26.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.43 | 0.00 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.06 | 2.17 | 28.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.92 | 3.33 | 27.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.67 | 1.33 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.67 | 2.33 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.33 | 15.33 | 1.33 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 |
December | 11.67 | 15.10 | 3.17 | 15.09 | 0.00 | 15.09 | 0.00 | 15.09 |
Annual Sum or Average | 60.50 | 15.26 | 12.67 | 15.31 | 18.33 | 17.83 | 9.67 | 18.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.67 | 16.59 | 5.67 | 16.59 | 7.67 | 28.06 | 3.33 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 76.17 | 16.75 | 39.50 | 17.29 | 0.00 | 17.29 | 0.00 | 17.29 |
February | 38.67 | 17.04 | 21.17 | 17.60 | 0.00 | 17.60 | 0.00 | 17.60 |
March | 7.17 | 16.88 | 2.67 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 |
April | 0.33 | 17.87 | 0.17 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.37 | 0.00 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17.00 | 16.36 | 8.17 | 16.80 | 0.00 | 16.80 | 0.00 | 16.80 |
December | 39.17 | 16.41 | 19.67 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 |
Annual Sum or Average | 178.50 | 16.71 | 91.33 | 17.23 | 0.67 | 17.25 | 0.00 | 17.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 76.17 | 17.87 | 39.50 | 18.32 | 0.67 | 27.37 | 0.00 | 27.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.83 | 14.87 | 8.50 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
February | 17.33 | 14.88 | 1.83 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
March | 4.00 | 15.41 | 0.00 | 15.41 | 0.00 | 15.41 | 0.00 | 15.41 |
April | 0.17 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.72 | 3.00 | 27.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.86 | 5.50 | 27.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.01 | 6.67 | 28.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.82 | 2.00 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.88 | 2.33 | 27.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.33 | 14.94 | 2.83 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
December | 23.67 | 15.01 | 4.67 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 |
Annual Sum or Average | 99.33 | 14.94 | 17.83 | 14.96 | 19.50 | 16.81 | 19.50 | 18.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.83 | 16.48 | 8.50 | 16.48 | 6.67 | 28.01 | 6.67 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.50 | 15.30 | 6.67 | 15.52 | 0.00 | 15.52 | 0.00 | 15.52 |
February | 13.33 | 15.32 | 1.50 | 15.46 | 0.00 | 15.46 | 0.00 | 15.46 |
March | 2.17 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 |
April | 0.17 | 16.56 | 0.00 | 16.56 | 1.67 | 26.74 | 1.67 | 27.23 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.45 | 0.50 | 27.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.69 | 4.00 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.72 | 4.50 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.57 | 3.67 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.90 | 5.17 | 27.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.53 | 1.17 | 27.53 |
November | 9.33 | 15.26 | 2.50 | 15.41 | 0.00 | 15.41 | 0.00 | 15.41 |
December | 18.50 | 15.30 | 3.50 | 15.47 | 0.00 | 15.47 | 0.00 | 15.47 |
Annual Sum or Average | 78.00 | 15.31 | 14.17 | 15.49 | 21.33 | 17.79 | 20.67 | 19.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.41 | 0.00 | 15.41 |
Maximum of Months | 34.50 | 16.56 | 6.67 | 16.56 | 5.17 | 27.90 | 5.17 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.67 | 14.85 | 8.67 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
February | 17.83 | 14.88 | 2.33 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
March | 3.33 | 15.57 | 0.00 | 15.57 | 0.00 | 15.57 | 0.00 | 15.57 |
April | 0.17 | 16.45 | 0.00 | 16.45 | 1.67 | 27.12 | 1.00 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.95 | 1.50 | 27.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.41 | 2.83 | 28.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.21 | 4.33 | 28.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.97 | 2.00 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.84 | 2.83 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12.00 | 14.92 | 3.33 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 |
December | 24.33 | 14.98 | 5.83 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
Annual Sum or Average | 100.33 | 14.92 | 20.17 | 14.93 | 25.83 | 17.26 | 14.50 | 18.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.67 | 16.45 | 8.67 | 16.45 | 9.50 | 28.41 | 4.33 | 28.43 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.45 | 277.17 | 21.18 | 277.17 | 21.06 |
February | 454.00 | 22.23 | 88.67 | 22.00 | 88.67 | 21.83 |
March | 500.50 | 23.11 | 13.17 | 23.06 | 13.17 | 23.00 |
April | 362.50 | 23.56 | 43.83 | 23.67 | 0.00 | 23.67 |
May | 60.83 | 23.89 | 284.50 | 24.42 | 0.00 | 24.42 |
June | 0.33 | 23.73 | 436.83 | 24.38 | 0.00 | 24.38 |
July | 0.00 | 0.00 | 491.00 | 24.44 | 0.00 | 24.44 |
August | 1.00 | 24.69 | 504.17 | 24.38 | 1.00 | 24.38 |
September | 50.00 | 23.87 | 269.17 | 24.49 | 0.00 | 24.49 |
October | 333.33 | 23.92 | 25.33 | 24.00 | 0.00 | 24.00 |
November | 387.17 | 22.98 | 52.83 | 22.84 | 38.67 | 22.67 |
December | 497.00 | 22.17 | 98.50 | 21.95 | 98.50 | 21.79 |
Annual Sum or Average | 3148.67 | 22.72 | 2585.17 | 23.17 | 517.17 | 22.97 |
Minimum of Months | 0.00 | 0.00 | 13.17 | 21.18 | 0.00 | 21.06 |
Maximum of Months | 502.00 | 24.69 | 504.17 | 24.49 | 277.17 | 24.49 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.48 | 455.00 | 20.42 | 455.00 | 20.40 |
February | 454.00 | 20.92 | 298.00 | 20.77 | 298.00 | 20.70 |
March | 514.00 | 21.77 | 149.00 | 21.53 | 149.00 | 21.39 |
April | 410.67 | 22.40 | 64.17 | 22.39 | 36.50 | 22.27 |
May | 174.67 | 23.40 | 177.50 | 23.81 | 0.00 | 23.81 |
June | 41.67 | 23.32 | 364.50 | 24.15 | 0.00 | 24.15 |
July | 0.00 | 0.00 | 468.83 | 24.31 | 0.00 | 24.31 |
August | 0.67 | 24.16 | 476.17 | 24.24 | 0.67 | 24.24 |
September | 155.50 | 23.36 | 182.33 | 23.92 | 0.00 | 23.92 |
October | 490.67 | 22.84 | 0.17 | 22.84 | 0.17 | 22.84 |
November | 484.33 | 21.71 | 186.83 | 21.41 | 186.83 | 21.24 |
December | 497.00 | 20.78 | 381.17 | 20.66 | 381.17 | 20.61 |
Annual Sum or Average | 3725.17 | 21.72 | 3203.67 | 22.08 | 1507.33 | 21.80 |
Minimum of Months | 0.00 | 0.00 | 0.17 | 20.42 | 0.00 | 20.40 |
Maximum of Months | 514.00 | 24.16 | 476.17 | 24.31 | 455.00 | 24.31 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.11 | 480.50 | 20.08 | 480.50 | 20.07 |
February | 454.00 | 20.43 | 372.17 | 20.33 | 372.17 | 20.29 |
March | 514.00 | 21.21 | 265.67 | 20.99 | 265.67 | 20.89 |
April | 416.83 | 21.79 | 127.17 | 21.65 | 99.00 | 21.44 |
May | 245.67 | 23.11 | 148.33 | 23.49 | 0.33 | 23.49 |
June | 83.50 | 23.03 | 338.00 | 24.01 | 0.00 | 24.01 |
July | 12.50 | 23.39 | 441.83 | 24.25 | 0.00 | 24.25 |
August | 21.33 | 23.31 | 420.00 | 24.16 | 0.67 | 24.16 |
September | 224.17 | 22.79 | 151.00 | 23.35 | 5.17 | 23.31 |
October | 499.33 | 21.89 | 81.00 | 21.69 | 81.00 | 21.54 |
November | 489.00 | 20.92 | 279.83 | 20.64 | 279.83 | 20.50 |
December | 497.00 | 20.26 | 469.83 | 20.22 | 469.83 | 20.21 |
Annual Sum or Average | 3959.33 | 21.24 | 3575.33 | 21.56 | 2054.17 | 21.28 |
Minimum of Months | 12.50 | 20.11 | 81.00 | 20.08 | 0.00 | 20.07 |
Maximum of Months | 514.00 | 23.39 | 480.50 | 24.25 | 480.50 | 24.25 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.56 | 502.00 | 19.56 | 502.00 | 19.56 |
February | 454.00 | 19.74 | 442.17 | 19.72 | 442.17 | 19.71 |
March | 514.00 | 20.47 | 394.83 | 20.35 | 394.83 | 20.30 |
April | 432.00 | 20.95 | 237.50 | 20.83 | 206.17 | 20.64 |
May | 291.33 | 22.47 | 156.50 | 22.94 | 14.83 | 22.86 |
June | 133.00 | 23.15 | 335.50 | 23.98 | 30.33 | 24.07 |
July | 65.17 | 24.14 | 433.67 | 24.28 | 34.67 | 24.33 |
August | 100.17 | 23.35 | 377.00 | 23.97 | 29.00 | 23.99 |
September | 288.67 | 22.06 | 177.83 | 22.63 | 34.67 | 22.49 |
October | 502.00 | 20.86 | 235.67 | 20.60 | 235.67 | 20.47 |
November | 489.00 | 20.05 | 361.50 | 19.86 | 361.50 | 19.78 |
December | 497.00 | 19.67 | 497.00 | 19.67 | 497.00 | 19.67 |
Annual Sum or Average | 4268.33 | 20.69 | 4151.17 | 21.02 | 2782.83 | 20.76 |
Minimum of Months | 65.17 | 19.56 | 156.50 | 19.56 | 14.83 | 19.56 |
Maximum of Months | 514.00 | 24.14 | 502.00 | 24.28 | 502.00 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.67 | 494.67 | 19.66 | 494.67 | 19.66 |
February | 454.00 | 19.87 | 415.67 | 19.80 | 415.67 | 19.78 |
March | 511.67 | 20.67 | 326.83 | 20.45 | 326.83 | 20.36 |
April | 401.00 | 21.23 | 215.17 | 21.23 | 162.67 | 21.02 |
May | 235.67 | 22.74 | 217.17 | 23.51 | 22.00 | 23.57 |
June | 136.67 | 23.44 | 356.83 | 24.11 | 39.17 | 24.27 |
July | 83.00 | 25.26 | 452.33 | 24.56 | 62.17 | 24.71 |
August | 92.83 | 23.79 | 408.83 | 24.12 | 36.00 | 24.20 |
September | 243.83 | 22.21 | 217.83 | 23.08 | 33.50 | 23.03 |
October | 494.33 | 21.13 | 164.50 | 20.87 | 164.50 | 20.72 |
November | 489.00 | 20.14 | 346.50 | 19.94 | 346.50 | 19.86 |
December | 497.00 | 19.75 | 497.00 | 19.75 | 497.00 | 19.75 |
Annual Sum or Average | 4141.00 | 20.86 | 4113.33 | 21.27 | 2600.67 | 21.01 |
Minimum of Months | 83.00 | 19.67 | 164.50 | 19.66 | 22.00 | 19.66 |
Maximum of Months | 511.67 | 25.26 | 497.00 | 24.56 | 497.00 | 24.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 495.33 | 19.92 | 430.00 | 19.74 | 430.00 | 19.68 |
February | 439.67 | 20.25 | 350.00 | 20.05 | 344.83 | 19.95 |
March | 466.50 | 20.84 | 302.50 | 20.64 | 290.83 | 20.51 |
April | 368.50 | 21.19 | 225.83 | 21.27 | 162.83 | 21.04 |
May | 247.17 | 22.47 | 201.00 | 23.20 | 20.50 | 23.16 |
June | 146.33 | 23.17 | 329.33 | 23.96 | 34.00 | 24.07 |
July | 92.00 | 24.44 | 427.00 | 24.39 | 49.83 | 24.51 |
August | 109.83 | 23.87 | 396.33 | 24.18 | 44.83 | 24.28 |
September | 239.50 | 22.51 | 232.83 | 23.32 | 42.00 | 23.33 |
October | 398.67 | 21.31 | 188.00 | 21.32 | 138.17 | 21.10 |
November | 470.00 | 20.51 | 301.17 | 20.26 | 289.50 | 20.11 |
December | 487.83 | 20.16 | 419.50 | 19.96 | 419.50 | 19.89 |
Annual Sum or Average | 3961.33 | 21.07 | 3803.50 | 21.45 | 2266.83 | 21.17 |
Minimum of Months | 92.00 | 19.92 | 188.00 | 19.74 | 20.50 | 19.68 |
Maximum of Months | 495.33 | 24.44 | 430.00 | 24.39 | 430.00 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.69 | 492.67 | 19.67 | 492.67 | 19.66 |
February | 452.00 | 19.95 | 414.00 | 19.88 | 414.00 | 19.85 |
March | 500.67 | 20.60 | 355.33 | 20.43 | 354.00 | 20.36 |
April | 389.50 | 21.02 | 233.33 | 21.06 | 179.67 | 20.86 |
May | 294.00 | 22.32 | 173.67 | 22.96 | 23.67 | 22.95 |
June | 154.67 | 22.91 | 338.00 | 23.87 | 31.50 | 23.98 |
July | 101.67 | 24.31 | 415.83 | 24.37 | 50.83 | 24.51 |
August | 118.33 | 23.38 | 387.50 | 24.02 | 36.67 | 24.10 |
September | 290.33 | 22.10 | 202.67 | 22.82 | 46.83 | 22.78 |
October | 467.33 | 20.91 | 216.17 | 20.71 | 203.33 | 20.56 |
November | 483.33 | 20.10 | 342.33 | 19.91 | 342.17 | 19.83 |
December | 497.00 | 19.75 | 483.83 | 19.73 | 483.83 | 19.73 |
Annual Sum or Average | 4250.83 | 20.81 | 4055.33 | 21.17 | 2659.17 | 20.93 |
Minimum of Months | 101.67 | 19.69 | 173.67 | 19.67 | 23.67 | 19.66 |
Maximum of Months | 502.00 | 24.31 | 492.67 | 24.37 | 492.67 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.61 | 502.00 | 19.61 | 502.00 | 19.61 |
February | 454.00 | 19.89 | 450.17 | 19.88 | 450.17 | 19.88 |
March | 514.00 | 20.51 | 412.83 | 20.44 | 412.83 | 20.41 |
April | 470.50 | 21.00 | 249.50 | 20.82 | 241.33 | 20.71 |
May | 416.33 | 22.47 | 71.33 | 22.63 | 17.17 | 22.58 |
June | 140.67 | 22.95 | 282.83 | 23.79 | 14.83 | 23.81 |
July | 35.50 | 24.08 | 426.83 | 24.22 | 15.67 | 24.24 |
August | 48.67 | 23.71 | 409.83 | 24.09 | 17.83 | 24.11 |
September | 245.50 | 22.65 | 153.33 | 23.22 | 4.50 | 23.19 |
October | 502.00 | 21.61 | 84.33 | 21.46 | 84.33 | 21.34 |
November | 489.00 | 20.67 | 301.50 | 20.43 | 301.50 | 20.33 |
December | 497.00 | 19.95 | 497.00 | 19.95 | 497.00 | 19.95 |
Annual Sum or Average | 4315.17 | 20.93 | 3841.50 | 21.18 | 2559.17 | 20.92 |
Minimum of Months | 35.50 | 19.61 | 71.33 | 19.61 | 4.50 | 19.61 |
Maximum of Months | 514.00 | 24.08 | 502.00 | 24.22 | 502.00 | 24.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.78 | 496.17 | 19.77 | 496.17 | 19.77 |
February | 454.00 | 20.09 | 426.00 | 20.06 | 426.00 | 20.04 |
March | 514.00 | 20.76 | 345.33 | 20.60 | 345.33 | 20.53 |
April | 432.00 | 21.35 | 189.67 | 21.24 | 159.67 | 21.05 |
May | 268.50 | 22.77 | 158.67 | 23.46 | 5.67 | 23.47 |
June | 123.33 | 23.53 | 357.17 | 24.15 | 30.83 | 24.26 |
July | 45.50 | 25.94 | 473.00 | 24.58 | 38.67 | 24.71 |
August | 35.00 | 24.76 | 469.50 | 24.30 | 23.33 | 24.35 |
September | 189.17 | 22.99 | 226.33 | 23.82 | 11.00 | 23.86 |
October | 487.67 | 22.12 | 32.17 | 22.02 | 32.17 | 21.93 |
November | 489.00 | 20.82 | 290.83 | 20.57 | 290.83 | 20.45 |
December | 497.00 | 20.03 | 497.00 | 20.03 | 497.00 | 20.03 |
Annual Sum or Average | 4037.17 | 21.13 | 3961.83 | 21.53 | 2356.67 | 21.26 |
Minimum of Months | 35.00 | 19.78 | 32.17 | 19.77 | 5.67 | 19.77 |
Maximum of Months | 514.00 | 25.94 | 497.00 | 24.58 | 497.00 | 24.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 17.87 | 487.67 | 17.82 | 487.67 | 17.81 |
February | 454.00 | 18.93 | 398.33 | 18.77 | 398.33 | 18.70 |
March | 504.50 | 20.07 | 343.33 | 19.79 | 343.33 | 19.68 |
April | 430.33 | 20.80 | 235.83 | 20.67 | 203.33 | 20.46 |
May | 374.83 | 22.06 | 101.17 | 22.46 | 19.00 | 22.39 |
June | 222.50 | 22.79 | 282.17 | 23.60 | 74.00 | 23.66 |
July | 143.67 | 23.84 | 432.83 | 24.21 | 109.00 | 24.22 |
August | 132.50 | 23.64 | 454.00 | 24.14 | 96.83 | 24.15 |
September | 221.50 | 22.53 | 235.83 | 23.56 | 30.00 | 23.62 |
October | 413.67 | 21.74 | 79.50 | 21.80 | 40.67 | 21.61 |
November | 465.00 | 20.20 | 275.17 | 19.87 | 265.17 | 19.67 |
December | 494.17 | 18.97 | 439.33 | 18.82 | 439.33 | 18.77 |
Annual Sum or Average | 4358.67 | 20.49 | 3765.17 | 20.77 | 2506.67 | 20.45 |
Minimum of Months | 132.50 | 17.87 | 79.50 | 17.82 | 19.00 | 17.81 |
Maximum of Months | 504.50 | 23.84 | 487.67 | 24.21 | 487.67 | 24.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.79 | 494.17 | 19.77 | 494.17 | 19.77 |
February | 454.00 | 20.15 | 425.50 | 20.11 | 425.50 | 20.09 |
March | 514.00 | 20.74 | 358.00 | 20.59 | 358.00 | 20.53 |
April | 425.00 | 21.29 | 194.33 | 21.20 | 164.17 | 21.02 |
May | 335.50 | 22.51 | 115.67 | 22.95 | 8.50 | 22.91 |
June | 132.00 | 23.14 | 342.50 | 24.00 | 22.33 | 24.09 |
July | 42.17 | 25.70 | 455.33 | 24.55 | 32.17 | 24.67 |
August | 35.67 | 24.55 | 466.33 | 24.30 | 19.33 | 24.35 |
September | 211.33 | 22.81 | 221.67 | 23.63 | 16.00 | 23.67 |
October | 464.33 | 21.86 | 60.17 | 21.80 | 47.50 | 21.69 |
November | 483.00 | 20.77 | 281.67 | 20.52 | 281.00 | 20.41 |
December | 497.00 | 20.04 | 483.83 | 20.02 | 483.83 | 20.01 |
Annual Sum or Average | 4096.00 | 21.07 | 3899.17 | 21.46 | 2352.50 | 21.20 |
Minimum of Months | 35.67 | 19.79 | 60.17 | 19.77 | 8.50 | 19.77 |
Maximum of Months | 514.00 | 25.70 | 494.17 | 24.55 | 494.17 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.66 | 497.33 | 19.65 | 497.33 | 19.65 |
February | 454.00 | 19.94 | 429.33 | 19.90 | 429.33 | 19.89 |
March | 514.00 | 20.73 | 339.00 | 20.57 | 339.00 | 20.50 |
April | 421.50 | 21.32 | 178.17 | 21.22 | 143.00 | 21.02 |
May | 242.33 | 22.90 | 172.17 | 23.40 | 3.83 | 23.37 |
June | 89.83 | 23.51 | 368.33 | 24.15 | 22.33 | 24.21 |
July | 28.00 | 24.96 | 465.33 | 24.38 | 24.17 | 24.42 |
August | 45.50 | 23.96 | 434.50 | 24.15 | 22.50 | 24.18 |
September | 235.83 | 22.55 | 172.83 | 23.21 | 8.17 | 23.16 |
October | 498.67 | 21.49 | 123.17 | 21.26 | 123.17 | 21.11 |
November | 489.00 | 20.52 | 312.00 | 20.24 | 312.00 | 20.12 |
December | 497.00 | 19.85 | 497.00 | 19.85 | 497.00 | 19.85 |
Annual Sum or Average | 4017.67 | 20.89 | 3989.17 | 21.30 | 2421.83 | 21.01 |
Minimum of Months | 28.00 | 19.66 | 123.17 | 19.65 | 3.83 | 19.65 |
Maximum of Months | 514.00 | 24.96 | 497.33 | 24.38 | 497.33 | 24.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.54 | 417.00 | 19.52 | 417.00 | 19.51 |
February | 385.00 | 19.90 | 351.83 | 19.83 | 351.83 | 19.81 |
March | 428.50 | 20.80 | 252.33 | 20.57 | 252.33 | 20.46 |
April | 329.50 | 21.35 | 147.83 | 21.41 | 102.17 | 21.19 |
May | 197.33 | 23.05 | 175.83 | 23.77 | 16.33 | 23.87 |
June | 100.67 | 23.87 | 306.83 | 24.32 | 34.83 | 24.48 |
July | 57.17 | 26.00 | 395.50 | 24.71 | 49.50 | 24.88 |
August | 54.17 | 24.34 | 356.83 | 24.28 | 27.33 | 24.37 |
September | 197.17 | 22.60 | 176.33 | 23.49 | 17.50 | 23.53 |
October | 419.00 | 21.56 | 79.17 | 21.39 | 77.67 | 21.25 |
November | 417.00 | 20.40 | 274.00 | 20.17 | 274.00 | 20.07 |
December | 422.00 | 19.74 | 420.17 | 19.74 | 420.17 | 19.74 |
Annual Sum or Average | 3434.50 | 20.97 | 3353.67 | 21.40 | 2040.67 | 21.13 |
Minimum of Months | 54.17 | 19.54 | 79.17 | 19.52 | 16.33 | 19.51 |
Maximum of Months | 428.50 | 26.00 | 420.17 | 24.71 | 420.17 | 24.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.00 | 20.15 | 412.00 | 19.93 | 412.00 | 19.85 |
February | 437.83 | 20.61 | 314.67 | 20.35 | 309.83 | 20.23 |
March | 459.33 | 21.18 | 253.67 | 20.96 | 241.33 | 20.80 |
April | 356.33 | 21.57 | 181.67 | 21.72 | 111.67 | 21.51 |
May | 203.00 | 22.88 | 210.67 | 23.62 | 7.33 | 23.63 |
June | 110.67 | 23.72 | 354.00 | 24.18 | 31.33 | 24.30 |
July | 55.83 | 25.37 | 460.33 | 24.51 | 41.83 | 24.63 |
August | 63.00 | 24.70 | 454.67 | 24.33 | 37.67 | 24.43 |
September | 199.17 | 23.06 | 237.00 | 23.84 | 24.83 | 23.94 |
October | 376.50 | 21.96 | 118.17 | 22.15 | 56.17 | 21.99 |
November | 457.50 | 20.97 | 254.33 | 20.70 | 238.50 | 20.50 |
December | 478.83 | 20.40 | 400.50 | 20.21 | 398.33 | 20.13 |
Annual Sum or Average | 3692.00 | 21.36 | 3651.67 | 21.80 | 1910.83 | 21.52 |
Minimum of Months | 55.83 | 20.15 | 118.17 | 19.93 | 7.33 | 19.85 |
Maximum of Months | 494.00 | 25.37 | 460.33 | 24.51 | 412.00 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.77 | 489.17 | 19.75 | 489.17 | 19.74 |
February | 452.00 | 20.15 | 397.50 | 20.06 | 397.50 | 20.03 |
March | 497.00 | 20.84 | 305.33 | 20.65 | 303.83 | 20.56 |
April | 381.33 | 21.35 | 180.00 | 21.45 | 123.00 | 21.26 |
May | 248.17 | 22.69 | 187.50 | 23.37 | 11.50 | 23.40 |
June | 117.33 | 23.37 | 360.83 | 24.10 | 27.00 | 24.21 |
July | 65.17 | 25.20 | 447.00 | 24.52 | 42.67 | 24.66 |
August | 69.50 | 24.05 | 435.17 | 24.22 | 31.17 | 24.29 |
September | 252.50 | 22.54 | 200.50 | 23.32 | 23.17 | 23.36 |
October | 455.50 | 21.40 | 121.00 | 21.27 | 106.17 | 21.13 |
November | 481.67 | 20.50 | 304.17 | 20.27 | 303.00 | 20.16 |
December | 497.00 | 19.94 | 474.67 | 19.91 | 474.67 | 19.89 |
Annual Sum or Average | 4019.17 | 21.01 | 3902.83 | 21.43 | 2332.83 | 21.18 |
Minimum of Months | 65.17 | 19.77 | 121.00 | 19.75 | 11.50 | 19.74 |
Maximum of Months | 502.00 | 25.20 | 489.17 | 24.52 | 489.17 | 24.66 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.44654 | 13.81437 | -0.5488 | 12.80007 |
February | 454.00000 | 22.22675 | 17.56465 | -0.3271 | 8.60116 |
March | 514.00000 | 23.14187 | 22.12980 | -0.0564 | 6.19094 |
April | 485.00000 | 23.73947 | 28.46991 | 0.16433 | 6.44097 |
May | 508.00000 | 24.32468 | 40.71896 | -0.4386 | 9.71205 |
June | 496.00000 | 24.33291 | 47.63898 | -0.3354 | 7.78731 |
July | 497.00000 | 24.43367 | 51.86967 | -0.2605 | 6.92165 |
August | 514.00000 | 24.36902 | 50.88393 | -0.2856 | 7.14131 |
September | 485.00000 | 24.35222 | 37.38796 | -0.4182 | 9.43762 |
October | 502.00000 | 24.05458 | 27.23884 | 0.24251 | 6.44808 |
November | 489.00000 | 23.22591 | 23.88081 | -0.0144 | 7.14685 |
December | 497.00000 | 22.17196 | 15.95519 | -0.3488 | 8.74119 |
Annual Sum or Average | 5943.00000 | 23.49388 | 31.59247 | -0.2188 | 8.10985 |
Minimum of Months | 454.00000 | 21.44654 | 13.81437 | -0.5488 | 6.19094 |
Maximum of Months | 514.00000 | 24.43367 | 51.86967 | 0.24251 | 12.80007 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.48198 | 14.40908 | -0.7830 | 19.53939 |
February | 454.00000 | 20.91652 | 18.68266 | -0.6315 | 14.70486 |
March | 514.00000 | 21.76556 | 23.96738 | -0.3683 | 9.33537 |
April | 485.00000 | 22.66388 | 30.96815 | -0.0763 | 7.25008 |
May | 508.00000 | 23.86205 | 42.55555 | -0.5955 | 13.35254 |
June | 496.00000 | 24.12781 | 49.03479 | -0.4200 | 9.27575 |
July | 497.00000 | 24.28556 | 52.86075 | -0.3275 | 7.58613 |
August | 514.00000 | 24.21931 | 51.96530 | -0.3604 | 7.99890 |
September | 485.00000 | 23.94851 | 39.13640 | -0.5773 | 13.48104 |
October | 502.00000 | 22.86725 | 30.32464 | -0.0383 | 5.81640 |
November | 489.00000 | 21.73535 | 26.21499 | -0.3656 | 10.65768 |
December | 497.00000 | 20.77808 | 17.03033 | -0.6782 | 15.94554 |
Annual Sum or Average | 5943.00000 | 22.65105 | 33.22612 | -0.4341 | 11.21651 |
Minimum of Months | 454.00000 | 20.48198 | 14.40908 | -0.7830 | 5.81640 |
Maximum of Months | 514.00000 | 24.28556 | 52.86075 | -0.0383 | 19.53939 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.11026 | 14.72119 | -0.9068 | 24.58711 |
February | 454.00000 | 20.42771 | 19.22407 | -0.7796 | 19.85825 |
March | 514.00000 | 21.21305 | 24.56697 | -0.5214 | 12.43673 |
April | 485.00000 | 22.11052 | 31.75343 | -0.2148 | 9.30401 |
May | 508.00000 | 23.59830 | 43.12891 | -0.6836 | 16.45991 |
June | 496.00000 | 23.99438 | 49.56761 | -0.4589 | 10.65587 |
July | 497.00000 | 24.20765 | 53.25513 | -0.3461 | 7.91641 |
August | 514.00000 | 24.10400 | 52.43655 | -0.3973 | 8.67454 |
September | 485.00000 | 23.52448 | 40.03525 | -0.7273 | 18.95156 |
October | 502.00000 | 21.89706 | 31.60730 | -0.2769 | 8.03705 |
November | 489.00000 | 20.91804 | 26.73782 | -0.5852 | 15.58907 |
December | 497.00000 | 20.26327 | 17.27581 | -0.8398 | 21.81667 |
Annual Sum or Average | 5943.00000 | 22.21234 | 33.82225 | -0.5599 | 14.47004 |
Minimum of Months | 454.00000 | 20.11026 | 14.72119 | -0.9068 | 7.91641 |
Maximum of Months | 514.00000 | 24.20765 | 53.25513 | -0.2148 | 24.58711 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.56391 | 14.68732 | -1.1502 | 34.78611 |
February | 454.00000 | 19.73674 | 19.66342 | -1.0277 | 29.84249 |
March | 514.00000 | 20.46705 | 25.65294 | -0.7415 | 18.86696 |
April | 485.00000 | 21.30201 | 33.04752 | -0.4183 | 13.79755 |
May | 508.00000 | 23.14555 | 44.28828 | -0.8155 | 22.58429 |
June | 496.00000 | 23.86812 | 50.63917 | -0.4589 | 12.61799 |
July | 497.00000 | 24.19023 | 54.59946 | -0.3088 | 8.09445 |
August | 514.00000 | 23.92743 | 53.85747 | -0.4218 | 9.90272 |
September | 485.00000 | 22.92245 | 41.84629 | -0.9173 | 27.72975 |
October | 502.00000 | 20.85953 | 33.62846 | -0.5312 | 13.03976 |
November | 489.00000 | 20.05289 | 28.26173 | -0.8351 | 23.73741 |
December | 497.00000 | 19.66762 | 17.76604 | -1.0788 | 31.65131 |
Annual Sum or Average | 5943.00000 | 21.65917 | 34.96124 | -0.7229 | 20.45735 |
Minimum of Months | 454.00000 | 19.56391 | 14.68732 | -1.1502 | 8.09445 |
Maximum of Months | 514.00000 | 24.19023 | 54.59946 | -0.3088 | 34.78611 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.67155 | 14.78224 | -1.1042 | 32.85926 |
February | 454.00000 | 19.86594 | 19.55633 | -0.9667 | 27.56594 |
March | 514.00000 | 20.68372 | 25.10070 | -0.6559 | 17.12341 |
April | 485.00000 | 21.76265 | 31.95858 | -0.2792 | 12.81406 |
May | 508.00000 | 23.50685 | 43.15248 | -0.6274 | 17.87316 |
June | 496.00000 | 23.91309 | 50.03724 | -0.3553 | 12.17790 |
July | 497.00000 | 24.32340 | 53.76640 | -0.1706 | 7.84035 |
August | 514.00000 | 24.00313 | 53.16276 | -0.3153 | 8.91199 |
September | 485.00000 | 23.23426 | 40.72080 | -0.7420 | 23.55520 |
October | 502.00000 | 21.17473 | 32.81844 | -0.4319 | 10.97040 |
November | 489.00000 | 20.13768 | 28.02041 | -0.8024 | 22.34007 |
December | 497.00000 | 19.74772 | 17.61426 | -1.0467 | 30.28819 |
Annual Sum or Average | 5943.00000 | 21.85252 | 34.35456 | -0.6220 | 18.59881 |
Minimum of Months | 454.00000 | 19.67155 | 14.78224 | -1.1042 | 7.84035 |
Maximum of Months | 514.00000 | 24.32340 | 53.76640 | -0.1706 | 32.85926 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.97507 | 14.50623 | -0.9632 | 29.05865 |
February | 454.00000 | 20.37135 | 18.83410 | -0.7938 | 23.30429 |
March | 514.00000 | 21.14991 | 24.27444 | -0.5294 | 15.66430 |
April | 485.00000 | 21.92902 | 31.41285 | -0.2343 | 13.35953 |
May | 508.00000 | 23.35642 | 43.44546 | -0.7081 | 20.30668 |
June | 496.00000 | 23.82778 | 50.47341 | -0.4379 | 13.00867 |
July | 497.00000 | 24.21418 | 54.24696 | -0.2552 | 8.46817 |
August | 514.00000 | 24.02581 | 53.08866 | -0.3223 | 9.44337 |
September | 485.00000 | 23.38748 | 40.22586 | -0.6744 | 22.24174 |
October | 502.00000 | 21.93370 | 31.04530 | -0.2316 | 10.76800 |
November | 489.00000 | 20.66705 | 27.18341 | -0.6469 | 19.35885 |
December | 497.00000 | 20.22691 | 17.05156 | -0.8829 | 26.02290 |
Annual Sum or Average | 5943.00000 | 22.10377 | 33.94920 | -0.5549 | 17.52006 |
Minimum of Months | 454.00000 | 19.97507 | 14.50623 | -0.9632 | 8.46817 |
Maximum of Months | 514.00000 | 24.21418 | 54.24696 | -0.2316 | 29.05865 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.68572 | 14.55966 | -1.1054 | 32.97019 |
February | 454.00000 | 19.96347 | 19.16986 | -0.9507 | 27.16994 |
March | 514.00000 | 20.68809 | 24.88364 | -0.6673 | 17.63633 |
April | 485.00000 | 21.64483 | 31.95879 | -0.2998 | 13.77745 |
May | 508.00000 | 23.06052 | 44.19137 | -0.7767 | 23.10210 |
June | 496.00000 | 23.74587 | 50.66326 | -0.4196 | 13.82384 |
July | 497.00000 | 24.15538 | 54.43531 | -0.2323 | 9.05383 |
August | 514.00000 | 23.88976 | 53.67008 | -0.3472 | 10.12818 |
September | 485.00000 | 22.93305 | 41.42279 | -0.8439 | 27.50622 |
October | 502.00000 | 21.12449 | 32.61479 | -0.4452 | 12.42780 |
November | 489.00000 | 20.15067 | 27.78836 | -0.8008 | 22.60723 |
December | 497.00000 | 19.75495 | 17.41600 | -1.0457 | 30.35971 |
Annual Sum or Average | 5943.00000 | 21.74882 | 34.53276 | -0.6589 | 19.96541 |
Minimum of Months | 454.00000 | 19.68572 | 14.55966 | -1.1054 | 9.05383 |
Maximum of Months | 514.00000 | 24.15538 | 54.43531 | -0.2323 | 32.97019 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.61499 | 14.87635 | -1.1125 | 32.92905 |
February | 454.00000 | 19.88646 | 19.82546 | -0.9834 | 27.40697 |
March | 514.00000 | 20.50552 | 26.03191 | -0.7422 | 18.03288 |
April | 485.00000 | 21.08585 | 33.94837 | -0.4948 | 12.89070 |
May | 508.00000 | 22.75449 | 46.03789 | -0.9943 | 28.26079 |
June | 496.00000 | 23.79187 | 50.85425 | -0.5383 | 12.91721 |
July | 497.00000 | 24.15128 | 54.42060 | -0.3664 | 8.29910 |
August | 514.00000 | 24.04010 | 53.24497 | -0.4119 | 8.97829 |
September | 485.00000 | 23.38481 | 40.81070 | -0.7618 | 20.29778 |
October | 502.00000 | 21.60694 | 32.28538 | -0.3265 | 8.31757 |
November | 489.00000 | 20.67282 | 27.62138 | -0.6485 | 17.02383 |
December | 497.00000 | 19.94634 | 17.85127 | -0.9709 | 26.59165 |
Annual Sum or Average | 5943.00000 | 21.80248 | 34.95194 | -0.6941 | 18.43471 |
Minimum of Months | 454.00000 | 19.61499 | 14.87635 | -1.1125 | 8.29910 |
Maximum of Months | 514.00000 | 24.15128 | 54.42060 | -0.3265 | 32.92905 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.78114 | 15.22238 | -1.0576 | 30.55444 |
February | 454.00000 | 20.09253 | 19.97940 | -0.9087 | 24.36278 |
March | 514.00000 | 20.76468 | 25.76777 | -0.6469 | 15.73549 |
April | 485.00000 | 21.67375 | 32.81417 | -0.3259 | 11.32688 |
May | 508.00000 | 23.52966 | 43.95486 | -0.6834 | 18.21984 |
June | 496.00000 | 24.01001 | 49.63313 | -0.3806 | 10.89086 |
July | 497.00000 | 24.40638 | 53.15112 | -0.1893 | 7.14637 |
August | 514.00000 | 24.20379 | 52.22723 | -0.2749 | 7.39022 |
September | 485.00000 | 23.80631 | 39.48390 | -0.5533 | 15.59325 |
October | 502.00000 | 22.18269 | 31.40079 | -0.1735 | 6.97814 |
November | 489.00000 | 20.81616 | 27.61237 | -0.6028 | 15.81389 |
December | 497.00000 | 20.02945 | 17.98015 | -0.9388 | 25.30461 |
Annual Sum or Average | 5943.00000 | 22.12439 | 34.23040 | -0.5590 | 15.70985 |
Minimum of Months | 454.00000 | 19.78114 | 15.22238 | -1.0576 | 6.97814 |
Maximum of Months | 514.00000 | 24.40638 | 53.15112 | -0.1735 | 30.55444 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 17.87128 | 13.64309 | -1.3494 | 42.52744 |
February | 454.00000 | 18.93476 | 18.03957 | -1.0546 | 30.70531 |
March | 514.00000 | 20.14353 | 23.75218 | -0.7279 | 20.02062 |
April | 485.00000 | 21.19746 | 31.44673 | -0.4021 | 13.99818 |
May | 508.00000 | 22.67486 | 45.41000 | -0.9531 | 27.96725 |
June | 496.00000 | 23.55747 | 52.05573 | -0.5587 | 15.32626 |
July | 497.00000 | 24.16144 | 56.16861 | -0.2983 | 8.42626 |
August | 514.00000 | 24.09616 | 54.33907 | -0.3009 | 8.51081 |
September | 485.00000 | 23.55321 | 39.28050 | -0.5880 | 19.01198 |
October | 502.00000 | 22.22369 | 29.24187 | -0.1057 | 8.21754 |
November | 489.00000 | 20.42769 | 25.64806 | -0.6213 | 18.91405 |
December | 497.00000 | 19.00354 | 16.14860 | -1.0684 | 31.89081 |
Annual Sum or Average | 5943.00000 | 21.50644 | 33.91070 | -0.6668 | 20.39122 |
Minimum of Months | 454.00000 | 17.87128 | 13.64309 | -1.3494 | 8.21754 |
Maximum of Months | 514.00000 | 24.16144 | 56.16861 | -0.1057 | 42.52744 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.78597 | 15.01171 | -1.0613 | 30.75226 |
February | 454.00000 | 20.15348 | 19.65098 | -0.8980 | 24.15465 |
March | 514.00000 | 20.73754 | 25.58275 | -0.6627 | 16.21503 |
April | 485.00000 | 21.65596 | 32.59685 | -0.3207 | 11.57665 |
May | 508.00000 | 23.11089 | 44.91411 | -0.8279 | 22.96878 |
June | 496.00000 | 23.89479 | 50.13157 | -0.4298 | 12.00476 |
July | 497.00000 | 24.36680 | 53.38259 | -0.2096 | 7.35491 |
August | 514.00000 | 24.20899 | 52.34372 | -0.2714 | 7.43308 |
September | 485.00000 | 23.63495 | 39.90074 | -0.6163 | 17.68575 |
October | 502.00000 | 22.03255 | 31.26010 | -0.2042 | 7.63718 |
November | 489.00000 | 20.80997 | 27.38262 | -0.6036 | 16.04583 |
December | 497.00000 | 20.03677 | 17.78382 | -0.9381 | 25.37755 |
Annual Sum or Average | 5943.00000 | 22.05081 | 34.29362 | -0.5850 | 16.54418 |
Minimum of Months | 454.00000 | 19.78597 | 15.01171 | -1.0613 | 7.35491 |
Maximum of Months | 514.00000 | 24.36680 | 53.38259 | -0.2042 | 30.75226 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.65957 | 14.99488 | -1.0764 | 31.59233 |
February | 454.00000 | 19.93502 | 19.79954 | -0.9340 | 25.74605 |
March | 514.00000 | 20.73307 | 25.60592 | -0.6407 | 15.69332 |
April | 485.00000 | 21.68865 | 32.69772 | -0.3061 | 10.98216 |
May | 508.00000 | 23.52050 | 43.56909 | -0.6949 | 17.53889 |
June | 496.00000 | 24.07008 | 49.94772 | -0.4009 | 10.16368 |
July | 497.00000 | 24.31010 | 53.94290 | -0.2790 | 7.32436 |
August | 514.00000 | 24.10491 | 53.11994 | -0.3686 | 8.33745 |
September | 485.00000 | 23.38783 | 40.94979 | -0.7546 | 20.67329 |
October | 502.00000 | 21.50463 | 32.84798 | -0.3511 | 9.21398 |
November | 489.00000 | 20.51515 | 27.83674 | -0.6860 | 18.90226 |
December | 497.00000 | 19.84819 | 17.94270 | -0.9836 | 27.48109 |
Annual Sum or Average | 5943.00000 | 21.95684 | 34.56785 | -0.6207 | 16.88888 |
Minimum of Months | 454.00000 | 19.65957 | 14.99488 | -1.0764 | 7.32436 |
Maximum of Months | 514.00000 | 24.31010 | 53.94290 | -0.2790 | 31.59233 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.53612 | 14.39665 | -1.0863 | 32.20252 |
February | 385.00000 | 19.90006 | 18.93418 | -0.9181 | 25.30660 |
March | 433.00000 | 20.82828 | 24.43608 | -0.5958 | 15.09493 |
April | 410.00000 | 21.96061 | 30.99116 | -0.2175 | 11.23525 |
May | 430.00000 | 23.68768 | 42.41834 | -0.5779 | 15.95129 |
June | 418.00000 | 24.09096 | 49.22709 | -0.3264 | 10.78163 |
July | 422.00000 | 24.45543 | 52.93805 | -0.1596 | 7.63106 |
August | 433.00000 | 24.13635 | 52.40692 | -0.2985 | 8.24780 |
September | 410.00000 | 23.49157 | 39.79249 | -0.6589 | 20.00355 |
October | 427.00000 | 21.61615 | 31.37212 | -0.3084 | 8.59123 |
November | 417.00000 | 20.40077 | 26.67455 | -0.7058 | 18.94113 |
December | 422.00000 | 19.73963 | 17.05879 | -0.9974 | 28.10839 |
Annual Sum or Average | 5034.00000 | 22.00075 | 33.49345 | -0.5687 | 16.77067 |
Minimum of Months | 385.00000 | 19.53612 | 14.39665 | -1.0863 | 7.63106 |
Maximum of Months | 433.00000 | 24.45543 | 52.93805 | -0.1596 | 32.20252 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.20722 | 14.55143 | -0.8667 | 25.33271 |
February | 454.00000 | 20.73125 | 18.64860 | -0.6729 | 19.02698 |
March | 514.00000 | 21.49967 | 23.92538 | -0.4171 | 12.74447 |
April | 485.00000 | 22.29241 | 30.90821 | -0.1299 | 10.95649 |
May | 508.00000 | 23.67287 | 42.74931 | -0.6050 | 15.90468 |
June | 496.00000 | 24.03631 | 49.71730 | -0.3795 | 10.42793 |
July | 497.00000 | 24.34125 | 53.51297 | -0.2256 | 7.46812 |
August | 514.00000 | 24.19041 | 52.36728 | -0.2753 | 7.91513 |
September | 485.00000 | 23.76348 | 39.37722 | -0.5403 | 16.61419 |
October | 502.00000 | 22.55422 | 30.02634 | -0.0621 | 8.48416 |
November | 489.00000 | 21.21364 | 26.52855 | -0.4841 | 15.39221 |
December | 497.00000 | 20.53917 | 16.88707 | -0.7657 | 21.78521 |
Annual Sum or Average | 5943.00000 | 22.43428 | 33.39813 | -0.4506 | 14.28953 |
Minimum of Months | 454.00000 | 20.20722 | 14.55143 | -0.8667 | 7.46812 |
Maximum of Months | 514.00000 | 24.34125 | 53.51297 | -0.0621 | 25.33271 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.77476 | 14.60412 | -1.0348 | 29.97995 |
February | 454.00000 | 20.16690 | 19.07176 | -0.8580 | 23.36246 |
March | 514.00000 | 20.94345 | 24.61712 | -0.5710 | 14.65953 |
April | 485.00000 | 21.96206 | 31.50051 | -0.2031 | 11.28928 |
May | 508.00000 | 23.41083 | 43.46081 | -0.6641 | 18.20112 |
June | 496.00000 | 23.95709 | 49.90984 | -0.3607 | 11.07952 |
July | 497.00000 | 24.30382 | 53.67055 | -0.1971 | 7.82459 |
August | 514.00000 | 24.08569 | 52.88343 | -0.2914 | 8.29791 |
September | 485.00000 | 23.33374 | 40.56349 | -0.7007 | 21.17337 |
October | 502.00000 | 21.65037 | 31.75694 | -0.2902 | 9.13887 |
November | 489.00000 | 20.55379 | 27.25991 | -0.6644 | 18.09256 |
December | 497.00000 | 19.94102 | 17.34134 | -0.9515 | 26.33399 |
Annual Sum or Average | 5943.00000 | 22.02264 | 34.01894 | -0.5634 | 16.54962 |
Minimum of Months | 454.00000 | 19.77476 | 14.60412 | -1.0348 | 7.82459 |
Maximum of Months | 514.00000 | 24.30382 | 53.67055 | -0.1971 | 29.97995 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.149260E+09 | 42680195.01 | 11.00 | 0.126167E+09 | 23093671.78 | 0.00 | 0.24 | 25-MAR-15:00 | 0.00 | 01-MAR-00:03 | 7443.76 | 25-MAR-15:00 | 6469.28 | 25-MAR-15:00 | 1055.90 | 25-MAR-15:40 | 2084.48 | 25-MAR-15:00 | 0.00 |
April | 0.507762E+10 | 0.131095E+10 | 73.82 | 0.387223E+10 | 0.120539E+10 | 0.00 | 1.00 | 18-APR-08:50 | 0.00 | 01-APR-00:10 | 72622.65 | 18-APR-12:00 | 52939.46 | 18-APR-15:10 | 24669.25 | 18-APR-12:00 | 18023.30 | 18-APR-12:00 | 0.00 |
May | 0.139932E+11 | 0.356641E+10 | 216.69 | 0.104905E+11 | 0.350263E+10 | 0.00 | 1.00 | 05-MAY-13:00 | 0.00 | 01-MAY-00:10 | 73604.34 | 31-MAY-11:20 | 58839.42 | 31-MAY-15:10 | 26339.87 | 30-MAY-10:10 | 18740.88 | 31-MAY-11:20 | 0.00 |
June | 0.451318E+11 | 0.112098E+11 | 349.10 | 0.331956E+11 | 0.119362E+11 | 0.00 | 1.00 | 09-JUN-09:20 | 0.00 | 01-JUN-00:10 | 129516.62 | 26-JUN-07:50 | 71856.99 | 26-JUN-16:00 | 75355.06 | 26-JUN-06:03 | 29297.65 | 26-JUN-07:50 | 0.00 |
July | 0.645046E+11 | 0.155614E+11 | 439.93 | 0.433002E+11 | 0.212044E+11 | 0.00 | 1.00 | 02-JUL-08:61 | 0.00 | 01-JUL-00:10 | 114357.51 | 05-JUL-10:50 | 69390.27 | 03-JUL-15:30 | 65268.14 | 05-JUL-06:03 | 26397.72 | 05-JUL-10:50 | 0.00 |
August | 0.634003E+11 | 0.153862E+11 | 430.87 | 0.435092E+11 | 0.198912E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 130791.59 | 03-AUG-06:03 | 70735.97 | 04-AUG-15:30 | 93146.85 | 04-AUG-07:05 | 29479.04 | 04-AUG-07:40 | 0.00 |
September | 0.251571E+11 | 0.636850E+10 | 240.23 | 0.221437E+11 | 0.301338E+10 | 0.00 | 1.00 | 01-SEP-11:40 | 0.00 | 01-SEP-00:10 | 98556.05 | 11-SEP-09:50 | 67417.77 | 07-SEP-16:00 | 39474.55 | 11-SEP-09:50 | 22899.04 | 11-SEP-09:50 | 0.00 |
October | 0.147437E+10 | 0.395034E+09 | 48.25 | 0.125894E+10 | 0.215426E+09 | 0.00 | 0.88 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 32322.99 | 20-OCT-15:00 | 32322.99 | 20-OCT-15:00 | 5120.42 | 02-OCT-15:00 | 7655.07 | 20-OCT-15:00 | 0.00 |
November | 51298360.69 | 14826343.88 | 5.44 | 45965840.94 | 5332519.75 | 0.00 | 0.14 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4235.24 | 03-NOV-14:00 | 4107.45 | 03-NOV-15:00 | 566.55 | 03-NOV-12:15 | 1214.57 | 03-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.218939E+12 | 0.538558E+11 | 1815.33 | 0.157942E+12 | 0.609970E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.645046E+11 | 0.155614E+11 | 439.93 | 0.435092E+11 | 0.212044E+11 | 0.00 | 1.00 | 0.00 | 130791.59 | 71856.99 | 93146.85 | 29479.04 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.149291E+09 | 42563867.68 | 11.00 | 0.130195E+09 | 19095750.18 | 0.00 | 0.27 | 25-MAR-15:00 | 0.00 | 01-MAR-00:03 | 7920.94 | 25-MAR-15:00 | 7427.35 | 25-MAR-15:00 | 885.78 | 25-MAR-16:00 | 2200.84 | 25-MAR-15:00 | 0.00 |
April | 0.559129E+10 | 0.142603E+10 | 79.56 | 0.438400E+10 | 0.120729E+10 | 0.00 | 1.00 | 15-APR-14:00 | 0.00 | 01-APR-00:10 | 67087.08 | 18-APR-12:40 | 56065.95 | 18-APR-15:00 | 24017.69 | 18-APR-09:30 | 16570.01 | 18-APR-12:40 | 0.00 |
May | 0.146568E+11 | 0.371881E+10 | 236.75 | 0.109024E+11 | 0.375438E+10 | 0.00 | 1.00 | 04-MAY-15:00 | 0.00 | 01-MAY-00:10 | 68608.32 | 30-MAY-11:00 | 58384.46 | 31-MAY-15:00 | 28925.11 | 30-MAY-10:10 | 16876.98 | 31-MAY-15:00 | 0.00 |
June | 0.433614E+11 | 0.107342E+11 | 350.59 | 0.321487E+11 | 0.112127E+11 | 0.00 | 1.00 | 08-JUN-15:30 | 0.00 | 01-JUN-00:10 | 120694.07 | 26-JUN-08:00 | 67785.64 | 26-JUN-15:30 | 69955.51 | 26-JUN-06:03 | 27362.25 | 26-JUN-08:00 | 0.00 |
July | 0.595358E+11 | 0.143546E+11 | 439.70 | 0.400056E+11 | 0.195302E+11 | 0.00 | 1.00 | 02-JUL-07:22 | 0.00 | 01-JUL-00:10 | 108885.86 | 03-JUL-08:50 | 66412.30 | 02-JUL-16:41 | 61320.69 | 05-JUL-06:03 | 25045.39 | 05-JUL-10:50 | 0.00 |
August | 0.554431E+11 | 0.134868E+11 | 427.18 | 0.382194E+11 | 0.172237E+11 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 121690.21 | 03-AUG-05:03 | 69931.82 | 04-AUG-15:20 | 86547.03 | 04-AUG-07:05 | 27279.04 | 04-AUG-07:15 | 0.00 |
September | 0.220952E+11 | 0.560976E+10 | 238.01 | 0.194747E+11 | 0.262055E+10 | 0.00 | 1.00 | 01-SEP-12:00 | 0.00 | 01-SEP-00:10 | 83777.33 | 11-SEP-09:40 | 64929.26 | 07-SEP-16:00 | 33909.49 | 11-SEP-09:40 | 20437.50 | 06-SEP-14:30 | 0.00 |
October | 0.131000E+10 | 0.353224E+09 | 48.33 | 0.110759E+10 | 0.202409E+09 | 0.00 | 0.80 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 27022.16 | 20-OCT-15:00 | 27022.16 | 20-OCT-15:00 | 4373.01 | 02-OCT-15:00 | 6532.52 | 20-OCT-15:00 | 0.00 |
November | 59347746.84 | 17012273.01 | 5.39 | 50650828.46 | 8696918.38 | 0.00 | 0.19 | 03-NOV-13:30 | 0.00 | 01-NOV-00:10 | 5502.15 | 03-NOV-13:30 | 4604.08 | 03-NOV-13:40 | 1020.61 | 03-NOV-13:00 | 1558.25 | 03-NOV-13:30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.202202E+12 | 0.497430E+11 | 1836.52 | 0.146423E+12 | 0.557791E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.595358E+11 | 0.143546E+11 | 439.70 | 0.400056E+11 | 0.195302E+11 | 0.00 | 1.00 | 0.00 | 121690.21 | 69931.82 | 86547.03 | 27362.25 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.155519E+09 | 44430081.27 | 11.00 | 0.132193E+09 | 23325990.03 | 0.00 | 0.26 | 25-MAR-15:00 | 0.00 | 01-MAR-00:03 | 8333.71 | 25-MAR-15:00 | 7575.02 | 25-MAR-15:00 | 1032.94 | 25-MAR-15:50 | 2323.49 | 25-MAR-15:00 | 0.00 |
April | 0.617937E+10 | 0.157362E+10 | 78.92 | 0.482900E+10 | 0.135037E+10 | 0.00 | 1.00 | 15-APR-13:50 | 0.00 | 01-APR-00:10 | 80678.83 | 18-APR-15:50 | 63667.20 | 18-APR-15:00 | 26311.58 | 16-APR-13:42 | 19060.71 | 18-APR-15:50 | 0.00 |
May | 0.156133E+11 | 0.397284E+10 | 236.66 | 0.116827E+11 | 0.393058E+10 | 0.00 | 1.00 | 04-MAY-14:30 | 0.00 | 01-MAY-00:10 | 76673.42 | 30-MAY-12:10 | 67990.11 | 31-MAY-15:00 | 26933.12 | 30-MAY-10:00 | 19253.61 | 31-MAY-15:00 | 0.00 |
June | 0.464221E+11 | 0.115303E+11 | 349.47 | 0.348597E+11 | 0.115624E+11 | 0.00 | 1.00 | 08-JUN-15:40 | 0.00 | 01-JUN-00:10 | 130412.35 | 26-JUN-06:03 | 89171.59 | 11-JUN-14:22 | 78237.71 | 26-JUN-06:03 | 29954.25 | 11-JUN-15:42 | 0.00 |
July | 0.628937E+11 | 0.152080E+11 | 435.23 | 0.423061E+11 | 0.205876E+11 | 0.00 | 1.00 | 01-JUL-13:00 | 0.00 | 01-JUL-00:10 | 114729.88 | 06-JUL-15:10 | 73768.08 | 03-JUL-15:20 | 56972.32 | 17-JUL-16:10 | 26552.97 | 06-JUL-15:10 | 0.00 |
August | 0.572493E+11 | 0.140010E+11 | 423.31 | 0.399334E+11 | 0.173159E+11 | 0.00 | 1.00 | 01-AUG-07:30 | 0.00 | 01-AUG-00:10 | 110952.22 | 04-AUG-07:15 | 81756.48 | 04-AUG-15:30 | 76958.58 | 04-AUG-07:15 | 29603.53 | 04-AUG-15:30 | 0.00 |
September | 0.228681E+11 | 0.584480E+10 | 233.38 | 0.200861E+11 | 0.278203E+10 | 0.00 | 1.00 | 01-SEP-12:10 | 0.00 | 01-SEP-00:10 | 83259.41 | 11-SEP-10:00 | 73962.03 | 07-SEP-16:00 | 31603.41 | 11-SEP-10:00 | 22306.06 | 06-SEP-14:00 | 0.00 |
October | 0.131192E+10 | 0.356886E+09 | 47.17 | 0.108750E+10 | 0.224418E+09 | 0.00 | 0.73 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 26806.93 | 20-OCT-15:00 | 26806.93 | 20-OCT-15:00 | 4509.84 | 02-OCT-15:00 | 6613.34 | 20-OCT-15:00 | 0.00 |
November | 39806746.75 | 11543442.36 | 4.33 | 33677110.01 | 6129636.73 | 0.00 | 0.12 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3695.11 | 03-NOV-14:00 | 3220.51 | 03-NOV-14:30 | 548.81 | 03-NOV-13:30 | 1065.02 | 03-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.212733E+12 | 0.525434E+11 | 1819.47 | 0.154950E+12 | 0.577827E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.628937E+11 | 0.152080E+11 | 435.23 | 0.423061E+11 | 0.205876E+11 | 0.00 | 1.00 | 0.00 | 130412.35 | 89171.59 | 78237.71 | 29954.25 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 354.55 | 0.00 | 354.55 | 2.04 | 2746.82 | 0.00 | 0.00 | 0.00 |
February | 449.50 | 0.00 | 449.50 | 31.77 | 2189.42 | 0.00 | 0.00 | 0.00 |
March | 673.66 | 0.00 | 673.66 | 227.48 | 1377.60 | 0.00 | 0.00 | 0.00 |
April | 777.69 | 3.83 | 773.86 | 448.70 | 939.87 | 0.00 | 0.00 | 0.00 |
May | 1014.13 | 38.12 | 976.01 | 898.97 | 558.78 | 0.00 | 0.00 | 0.00 |
June | 1185.28 | 107.58 | 1077.70 | 1339.76 | 390.82 | 0.00 | 0.00 | 0.00 |
July | 1111.61 | 74.35 | 1037.25 | 1309.10 | 345.02 | 0.00 | 0.00 | 0.00 |
August | 930.74 | 16.50 | 914.25 | 1092.40 | 402.44 | 0.00 | 0.00 | 0.00 |
September | 713.61 | 0.18 | 713.44 | 669.83 | 684.38 | 0.00 | 0.00 | 0.00 |
October | 530.58 | 0.00 | 530.58 | 273.56 | 1016.45 | 0.00 | 0.00 | 0.00 |
November | 371.15 | 0.00 | 371.15 | 70.50 | 1608.76 | 0.00 | 0.00 | 0.00 |
December | 240.75 | 0.00 | 240.75 | 0.81 | 2404.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 697.41 | 20.13 | 677.28 | 533.39 | 1217.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 240.75 | 0.00 | 240.75 | 0.81 | 345.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1185.28 | 107.58 | 1077.70 | 1339.76 | 2746.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.48 | 208.42 | 298.06 | 222.38 | 1652.27 | 0.00 | 0.00 | 0.00 |
February | 671.34 | 295.20 | 376.14 | 391.53 | 1295.49 | 0.00 | 0.00 | 0.00 |
March | 912.14 | 362.06 | 550.09 | 709.16 | 844.45 | 0.00 | 0.00 | 0.00 |
April | 1120.03 | 490.49 | 629.53 | 1072.38 | 604.87 | 0.00 | 0.00 | 0.00 |
May | 1406.66 | 614.65 | 792.02 | 1559.59 | 376.71 | 0.00 | 0.00 | 0.00 |
June | 1547.99 | 674.13 | 873.87 | 1902.50 | 262.19 | 0.00 | 0.00 | 0.00 |
July | 1564.63 | 721.95 | 842.67 | 1966.11 | 231.24 | 0.00 | 0.00 | 0.00 |
August | 1318.95 | 568.63 | 750.32 | 1661.91 | 268.06 | 0.00 | 0.00 | 0.00 |
September | 1176.38 | 555.90 | 620.48 | 1375.32 | 441.23 | 0.00 | 0.00 | 0.00 |
October | 749.67 | 313.13 | 436.54 | 679.76 | 637.96 | 0.00 | 0.00 | 0.00 |
November | 442.31 | 143.67 | 298.64 | 243.83 | 997.06 | 0.00 | 0.00 | 0.00 |
December | 342.62 | 147.13 | 195.49 | 156.08 | 1481.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 981.47 | 425.22 | 556.24 | 998.32 | 755.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 342.62 | 143.67 | 195.49 | 156.08 | 231.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1564.63 | 721.95 | 873.87 | 1966.11 | 1652.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2204.89 | 1508.85 | 696.04 | 1946.14 | 2239.97 | 0.00 | 0.00 | 0.00 |
February | 2362.50 | 1596.12 | 766.38 | 2175.72 | 1791.12 | 0.00 | 0.00 | 0.00 |
March | 2055.91 | 1082.57 | 973.34 | 1988.84 | 1287.87 | 0.00 | 0.00 | 0.00 |
April | 1852.24 | 865.96 | 986.28 | 1989.64 | 963.19 | 0.00 | 0.00 | 0.00 |
May | 1534.52 | 416.03 | 1118.49 | 1745.20 | 610.49 | 0.00 | 0.00 | 0.00 |
June | 1489.78 | 303.33 | 1186.46 | 1879.83 | 418.68 | 0.00 | 0.00 | 0.00 |
July | 1577.04 | 397.37 | 1179.67 | 2074.63 | 367.98 | 0.00 | 0.00 | 0.00 |
August | 1776.80 | 637.20 | 1139.60 | 2374.86 | 431.96 | 0.00 | 0.00 | 0.00 |
September | 2153.11 | 1134.51 | 1018.60 | 2692.44 | 698.46 | 0.00 | 0.00 | 0.00 |
October | 2248.29 | 1410.49 | 837.81 | 2481.08 | 986.36 | 0.00 | 0.00 | 0.00 |
November | 1696.33 | 1061.94 | 634.40 | 1598.97 | 1432.45 | 0.00 | 0.00 | 0.00 |
December | 1808.89 | 1370.21 | 438.68 | 1714.60 | 2066.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1893.95 | 978.54 | 915.41 | 2054.34 | 1104.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1489.78 | 303.33 | 438.68 | 1598.97 | 367.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2362.50 | 1596.12 | 1186.46 | 2692.44 | 2239.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 502.31 | 203.24 | 299.07 | 230.06 | 1692.81 | 0.00 | 0.00 | 0.00 |
February | 736.54 | 362.95 | 373.60 | 481.96 | 1344.79 | 0.00 | 0.00 | 0.00 |
March | 879.28 | 327.14 | 552.14 | 670.97 | 873.41 | 0.00 | 0.00 | 0.00 |
April | 1282.61 | 634.23 | 648.38 | 1305.76 | 630.41 | 0.00 | 0.00 | 0.00 |
May | 1286.32 | 513.85 | 772.47 | 1436.19 | 397.33 | 0.00 | 0.00 | 0.00 |
June | 1509.34 | 654.11 | 855.23 | 1868.02 | 281.71 | 0.00 | 0.00 | 0.00 |
July | 1620.58 | 769.80 | 850.78 | 2060.29 | 253.53 | 0.00 | 0.00 | 0.00 |
August | 1416.79 | 650.21 | 766.58 | 1812.93 | 288.92 | 0.00 | 0.00 | 0.00 |
September | 1146.85 | 544.35 | 602.50 | 1350.10 | 461.27 | 0.00 | 0.00 | 0.00 |
October | 799.17 | 355.30 | 443.87 | 756.91 | 667.28 | 0.00 | 0.00 | 0.00 |
November | 478.36 | 176.90 | 301.46 | 304.20 | 1021.26 | 0.00 | 0.00 | 0.00 |
December | 367.88 | 173.42 | 194.46 | 201.69 | 1514.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1003.23 | 447.21 | 556.02 | 1042.68 | 783.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 367.88 | 173.42 | 194.46 | 201.69 | 253.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1620.58 | 769.80 | 855.23 | 2060.29 | 1692.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.18 | 0.00 | 118.18 | 0.74 | 916.55 | 0.00 | 0.00 | 0.00 |
February | 149.83 | 0.00 | 149.83 | 10.76 | 733.55 | 0.00 | 0.00 | 0.00 |
March | 224.54 | 0.00 | 224.54 | 80.90 | 461.49 | 0.00 | 0.00 | 0.00 |
April | 259.22 | 1.28 | 257.94 | 160.72 | 308.44 | 0.00 | 0.00 | 0.00 |
May | 338.03 | 12.71 | 325.32 | 316.65 | 177.89 | 0.00 | 0.00 | 0.00 |
June | 395.08 | 35.86 | 359.22 | 457.31 | 127.33 | 0.00 | 0.00 | 0.00 |
July | 370.52 | 24.78 | 345.73 | 444.42 | 113.36 | 0.00 | 0.00 | 0.00 |
August | 310.23 | 5.50 | 304.73 | 367.05 | 137.18 | 0.00 | 0.00 | 0.00 |
September | 237.86 | 0.06 | 237.80 | 220.71 | 244.57 | 0.00 | 0.00 | 0.00 |
October | 176.85 | 0.00 | 176.85 | 84.00 | 372.30 | 0.00 | 0.00 | 0.00 |
November | 123.71 | 0.00 | 123.71 | 20.48 | 569.16 | 0.00 | 0.00 | 0.00 |
December | 80.25 | 0.00 | 80.25 | 0.09 | 820.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.46 | 6.71 | 225.75 | 181.33 | 413.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.25 | 0.00 | 80.25 | 0.09 | 113.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 395.08 | 35.86 | 359.22 | 457.31 | 916.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.18 | 0.00 | 118.18 | 0.74 | 916.61 | 0.00 | 0.00 | 0.00 |
February | 149.83 | 0.00 | 149.83 | 10.76 | 733.59 | 0.00 | 0.00 | 0.00 |
March | 224.56 | 0.00 | 224.56 | 80.91 | 461.52 | 0.00 | 0.00 | 0.00 |
April | 259.24 | 1.28 | 257.96 | 160.73 | 308.46 | 0.00 | 0.00 | 0.00 |
May | 338.05 | 12.71 | 325.34 | 316.67 | 177.91 | 0.00 | 0.00 | 0.00 |
June | 395.10 | 35.86 | 359.24 | 457.33 | 127.34 | 0.00 | 0.00 | 0.00 |
July | 370.54 | 24.79 | 345.76 | 444.45 | 113.36 | 0.00 | 0.00 | 0.00 |
August | 310.25 | 5.50 | 304.75 | 367.07 | 137.19 | 0.00 | 0.00 | 0.00 |
September | 237.87 | 0.06 | 237.82 | 220.72 | 244.58 | 0.00 | 0.00 | 0.00 |
October | 176.86 | 0.00 | 176.86 | 84.00 | 372.32 | 0.00 | 0.00 | 0.00 |
November | 123.72 | 0.00 | 123.72 | 20.48 | 569.19 | 0.00 | 0.00 | 0.00 |
December | 80.25 | 0.00 | 80.25 | 0.09 | 820.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.47 | 6.71 | 225.77 | 181.35 | 413.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.25 | 0.00 | 80.25 | 0.09 | 113.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 395.10 | 35.86 | 359.24 | 457.33 | 916.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.18 | 0.00 | 118.18 | 0.74 | 916.61 | 0.00 | 0.00 | 0.00 |
February | 149.83 | 0.00 | 149.83 | 10.76 | 733.59 | 0.00 | 0.00 | 0.00 |
March | 224.56 | 0.00 | 224.56 | 80.91 | 461.52 | 0.00 | 0.00 | 0.00 |
April | 259.24 | 1.28 | 257.96 | 160.73 | 308.46 | 0.00 | 0.00 | 0.00 |
May | 338.05 | 12.71 | 325.34 | 316.67 | 177.91 | 0.00 | 0.00 | 0.00 |
June | 395.10 | 35.86 | 359.24 | 457.33 | 127.34 | 0.00 | 0.00 | 0.00 |
July | 370.54 | 24.79 | 345.76 | 444.45 | 113.36 | 0.00 | 0.00 | 0.00 |
August | 310.25 | 5.50 | 304.75 | 367.07 | 137.19 | 0.00 | 0.00 | 0.00 |
September | 237.87 | 0.06 | 237.82 | 220.72 | 244.58 | 0.00 | 0.00 | 0.00 |
October | 176.86 | 0.00 | 176.86 | 84.00 | 372.32 | 0.00 | 0.00 | 0.00 |
November | 123.72 | 0.00 | 123.72 | 20.48 | 569.19 | 0.00 | 0.00 | 0.00 |
December | 80.25 | 0.00 | 80.25 | 0.09 | 820.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.47 | 6.71 | 225.77 | 181.35 | 413.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.25 | 0.00 | 80.25 | 0.09 | 113.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 395.10 | 35.86 | 359.24 | 457.33 | 916.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 487.21 | 200.49 | 286.72 | 217.20 | 1598.61 | 0.00 | 0.00 | 0.00 |
February | 645.80 | 283.97 | 361.83 | 380.82 | 1264.81 | 0.00 | 0.00 | 0.00 |
March | 877.44 | 348.28 | 529.16 | 695.79 | 825.29 | 0.00 | 0.00 | 0.00 |
April | 1077.42 | 471.83 | 605.58 | 1054.47 | 584.84 | 0.00 | 0.00 | 0.00 |
May | 1353.15 | 591.26 | 761.89 | 1524.17 | 362.65 | 0.00 | 0.00 | 0.00 |
June | 1489.10 | 648.48 | 840.63 | 1847.02 | 256.86 | 0.00 | 0.00 | 0.00 |
July | 1505.10 | 694.49 | 810.62 | 1904.32 | 229.13 | 0.00 | 0.00 | 0.00 |
August | 1268.77 | 546.99 | 721.78 | 1604.77 | 272.33 | 0.00 | 0.00 | 0.00 |
September | 1131.63 | 534.75 | 596.88 | 1317.51 | 466.77 | 0.00 | 0.00 | 0.00 |
October | 721.15 | 301.22 | 419.93 | 632.70 | 686.66 | 0.00 | 0.00 | 0.00 |
November | 425.49 | 138.21 | 287.28 | 224.45 | 1023.04 | 0.00 | 0.00 | 0.00 |
December | 329.59 | 141.53 | 188.05 | 149.17 | 1464.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 944.13 | 409.04 | 535.08 | 965.86 | 750.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 329.59 | 138.21 | 188.05 | 149.17 | 229.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1505.10 | 694.49 | 840.63 | 1904.32 | 1598.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.26 | 7.93 | 11.34 | 8.59 | 63.21 | 0.00 | 0.00 | 0.00 |
February | 25.53 | 11.23 | 14.31 | 15.06 | 50.01 | 0.00 | 0.00 | 0.00 |
March | 34.69 | 13.77 | 20.92 | 27.51 | 32.63 | 0.00 | 0.00 | 0.00 |
April | 42.60 | 18.66 | 23.94 | 41.69 | 23.12 | 0.00 | 0.00 | 0.00 |
May | 53.50 | 23.38 | 30.12 | 60.26 | 14.34 | 0.00 | 0.00 | 0.00 |
June | 58.88 | 25.64 | 33.24 | 73.03 | 10.16 | 0.00 | 0.00 | 0.00 |
July | 59.51 | 27.46 | 32.05 | 75.30 | 9.06 | 0.00 | 0.00 | 0.00 |
August | 50.17 | 21.63 | 28.54 | 63.45 | 10.77 | 0.00 | 0.00 | 0.00 |
September | 44.74 | 21.14 | 23.60 | 52.09 | 18.46 | 0.00 | 0.00 | 0.00 |
October | 28.51 | 11.91 | 16.60 | 25.02 | 27.15 | 0.00 | 0.00 | 0.00 |
November | 16.82 | 5.46 | 11.36 | 8.87 | 40.45 | 0.00 | 0.00 | 0.00 |
December | 13.03 | 5.60 | 7.44 | 5.90 | 57.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.33 | 16.17 | 21.16 | 38.19 | 29.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.03 | 5.46 | 7.44 | 5.90 | 9.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.51 | 27.46 | 33.24 | 75.30 | 63.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 734.99 | 502.97 | 232.02 | 670.33 | 727.82 | 0.00 | 0.00 | 0.00 |
February | 787.53 | 532.06 | 255.47 | 746.42 | 597.28 | 0.00 | 0.00 | 0.00 |
March | 685.32 | 360.87 | 324.46 | 682.09 | 429.73 | 0.00 | 0.00 | 0.00 |
April | 617.43 | 288.66 | 328.77 | 681.21 | 318.71 | 0.00 | 0.00 | 0.00 |
May | 511.52 | 138.68 | 372.84 | 601.72 | 197.03 | 0.00 | 0.00 | 0.00 |
June | 496.61 | 101.11 | 395.50 | 639.77 | 137.11 | 0.00 | 0.00 | 0.00 |
July | 525.70 | 132.46 | 393.23 | 700.26 | 123.70 | 0.00 | 0.00 | 0.00 |
August | 592.28 | 212.41 | 379.88 | 797.06 | 151.69 | 0.00 | 0.00 | 0.00 |
September | 717.72 | 378.18 | 339.54 | 899.74 | 254.14 | 0.00 | 0.00 | 0.00 |
October | 749.45 | 470.18 | 279.28 | 826.45 | 368.44 | 0.00 | 0.00 | 0.00 |
November | 565.46 | 353.99 | 211.47 | 535.07 | 505.64 | 0.00 | 0.00 | 0.00 |
December | 602.98 | 456.75 | 146.23 | 580.75 | 692.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 631.34 | 326.19 | 305.14 | 696.42 | 374.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 496.61 | 101.11 | 146.23 | 535.07 | 123.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 787.53 | 532.06 | 395.50 | 899.74 | 727.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 734.99 | 502.97 | 232.02 | 670.33 | 727.82 | 0.00 | 0.00 | 0.00 |
February | 787.53 | 532.06 | 255.47 | 746.42 | 597.28 | 0.00 | 0.00 | 0.00 |
March | 685.32 | 360.87 | 324.46 | 682.09 | 429.73 | 0.00 | 0.00 | 0.00 |
April | 617.43 | 288.66 | 328.77 | 681.21 | 318.71 | 0.00 | 0.00 | 0.00 |
May | 511.52 | 138.68 | 372.84 | 601.72 | 197.03 | 0.00 | 0.00 | 0.00 |
June | 496.61 | 101.11 | 395.50 | 639.77 | 137.11 | 0.00 | 0.00 | 0.00 |
July | 525.70 | 132.46 | 393.23 | 700.26 | 123.70 | 0.00 | 0.00 | 0.00 |
August | 592.28 | 212.41 | 379.88 | 797.06 | 151.69 | 0.00 | 0.00 | 0.00 |
September | 717.72 | 378.18 | 339.54 | 899.74 | 254.14 | 0.00 | 0.00 | 0.00 |
October | 749.45 | 470.18 | 279.28 | 826.45 | 368.44 | 0.00 | 0.00 | 0.00 |
November | 565.46 | 353.99 | 211.47 | 535.07 | 505.64 | 0.00 | 0.00 | 0.00 |
December | 602.98 | 456.75 | 146.23 | 580.75 | 692.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 631.34 | 326.19 | 305.14 | 696.42 | 374.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 496.61 | 101.11 | 146.23 | 535.07 | 123.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 787.53 | 532.06 | 395.50 | 899.74 | 727.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 734.94 | 502.94 | 232.00 | 670.28 | 727.78 | 0.00 | 0.00 | 0.00 |
February | 787.48 | 532.03 | 255.45 | 746.38 | 597.25 | 0.00 | 0.00 | 0.00 |
March | 685.28 | 360.85 | 324.43 | 682.05 | 429.70 | 0.00 | 0.00 | 0.00 |
April | 617.39 | 288.64 | 328.75 | 681.17 | 318.69 | 0.00 | 0.00 | 0.00 |
May | 511.49 | 138.67 | 372.82 | 601.68 | 197.02 | 0.00 | 0.00 | 0.00 |
June | 496.58 | 101.11 | 395.47 | 639.73 | 137.10 | 0.00 | 0.00 | 0.00 |
July | 525.66 | 132.45 | 393.21 | 700.22 | 123.69 | 0.00 | 0.00 | 0.00 |
August | 592.25 | 212.39 | 379.85 | 797.01 | 151.68 | 0.00 | 0.00 | 0.00 |
September | 717.68 | 378.16 | 339.52 | 899.68 | 254.12 | 0.00 | 0.00 | 0.00 |
October | 749.41 | 470.15 | 279.26 | 826.40 | 368.42 | 0.00 | 0.00 | 0.00 |
November | 565.43 | 353.97 | 211.46 | 535.04 | 505.61 | 0.00 | 0.00 | 0.00 |
December | 602.95 | 456.72 | 146.22 | 580.72 | 692.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 631.30 | 326.17 | 305.12 | 696.37 | 374.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 496.58 | 101.11 | 146.22 | 535.04 | 123.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 787.48 | 532.03 | 395.47 | 899.68 | 727.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 483.20 | 195.51 | 287.69 | 226.92 | 1636.39 | 0.00 | 0.00 | 0.00 |
February | 708.52 | 349.14 | 359.39 | 472.50 | 1310.94 | 0.00 | 0.00 | 0.00 |
March | 845.83 | 314.69 | 531.14 | 662.60 | 852.85 | 0.00 | 0.00 | 0.00 |
April | 1233.81 | 610.10 | 623.72 | 1279.64 | 614.34 | 0.00 | 0.00 | 0.00 |
May | 1237.39 | 494.30 | 743.08 | 1405.77 | 380.92 | 0.00 | 0.00 | 0.00 |
June | 1451.92 | 629.23 | 822.70 | 1812.71 | 275.48 | 0.00 | 0.00 | 0.00 |
July | 1558.93 | 740.51 | 818.41 | 1992.51 | 253.37 | 0.00 | 0.00 | 0.00 |
August | 1362.89 | 625.48 | 737.42 | 1748.84 | 295.77 | 0.00 | 0.00 | 0.00 |
September | 1103.22 | 523.64 | 579.58 | 1291.80 | 487.05 | 0.00 | 0.00 | 0.00 |
October | 768.77 | 341.79 | 426.99 | 714.13 | 716.34 | 0.00 | 0.00 | 0.00 |
November | 460.16 | 170.17 | 289.99 | 285.49 | 1047.54 | 0.00 | 0.00 | 0.00 |
December | 353.89 | 166.83 | 187.06 | 195.37 | 1495.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 965.07 | 430.20 | 534.87 | 1010.00 | 778.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.89 | 166.83 | 187.06 | 195.37 | 253.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1558.93 | 740.51 | 822.70 | 1992.51 | 1636.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.11 | 7.73 | 11.37 | 8.97 | 64.70 | 0.00 | 0.00 | 0.00 |
February | 28.01 | 13.80 | 14.21 | 18.68 | 51.83 | 0.00 | 0.00 | 0.00 |
March | 33.44 | 12.44 | 21.00 | 26.20 | 33.72 | 0.00 | 0.00 | 0.00 |
April | 48.78 | 24.12 | 24.66 | 50.60 | 24.29 | 0.00 | 0.00 | 0.00 |
May | 48.92 | 19.54 | 29.38 | 55.58 | 15.06 | 0.00 | 0.00 | 0.00 |
June | 57.41 | 24.88 | 32.53 | 71.67 | 10.89 | 0.00 | 0.00 | 0.00 |
July | 61.64 | 29.28 | 32.36 | 78.78 | 10.02 | 0.00 | 0.00 | 0.00 |
August | 53.89 | 24.73 | 29.16 | 69.15 | 11.69 | 0.00 | 0.00 | 0.00 |
September | 43.62 | 20.70 | 22.92 | 51.08 | 19.26 | 0.00 | 0.00 | 0.00 |
October | 30.40 | 13.51 | 16.88 | 28.24 | 28.32 | 0.00 | 0.00 | 0.00 |
November | 18.19 | 6.73 | 11.47 | 11.29 | 41.42 | 0.00 | 0.00 | 0.00 |
December | 13.99 | 6.60 | 7.40 | 7.72 | 59.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.16 | 17.01 | 21.15 | 39.93 | 30.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.99 | 6.60 | 7.40 | 7.72 | 10.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.64 | 29.28 | 32.53 | 78.78 | 64.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 354.55 | 0.00 | 354.55 | 1.72 | 2792.71 | 0.00 | 0.00 | 0.00 |
February | 449.50 | 0.00 | 449.50 | 28.80 | 2249.98 | 0.00 | 0.00 | 0.00 |
March | 673.66 | 0.00 | 673.66 | 218.04 | 1439.03 | 0.00 | 0.00 | 0.00 |
April | 777.69 | 3.83 | 773.86 | 437.97 | 998.10 | 0.00 | 0.00 | 0.00 |
May | 1014.13 | 38.12 | 976.01 | 884.91 | 588.98 | 0.00 | 0.00 | 0.00 |
June | 1185.28 | 107.58 | 1077.70 | 1334.29 | 408.88 | 0.00 | 0.00 | 0.00 |
July | 1111.61 | 74.35 | 1037.25 | 1307.33 | 357.35 | 0.00 | 0.00 | 0.00 |
August | 930.74 | 16.50 | 914.25 | 1087.57 | 420.77 | 0.00 | 0.00 | 0.00 |
September | 713.61 | 0.18 | 713.44 | 655.13 | 732.20 | 0.00 | 0.00 | 0.00 |
October | 530.58 | 0.00 | 530.58 | 250.11 | 1101.10 | 0.00 | 0.00 | 0.00 |
November | 371.15 | 0.00 | 371.15 | 60.50 | 1690.35 | 0.00 | 0.00 | 0.00 |
December | 240.75 | 0.00 | 240.75 | 0.23 | 2470.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 697.41 | 20.13 | 677.28 | 525.18 | 1266.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 240.75 | 0.00 | 240.75 | 0.23 | 357.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1185.28 | 107.58 | 1077.70 | 1334.29 | 2792.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.48 | 208.42 | 298.06 | 220.19 | 1680.59 | 0.00 | 0.00 | 0.00 |
February | 671.34 | 295.20 | 376.14 | 386.20 | 1333.24 | 0.00 | 0.00 | 0.00 |
March | 912.14 | 362.06 | 550.09 | 700.00 | 882.06 | 0.00 | 0.00 | 0.00 |
April | 1120.03 | 490.49 | 629.53 | 1065.66 | 638.31 | 0.00 | 0.00 | 0.00 |
May | 1406.66 | 614.65 | 792.02 | 1554.99 | 393.95 | 0.00 | 0.00 | 0.00 |
June | 1547.99 | 674.13 | 873.87 | 1901.64 | 273.22 | 0.00 | 0.00 | 0.00 |
July | 1564.63 | 721.95 | 842.67 | 1967.74 | 238.54 | 0.00 | 0.00 | 0.00 |
August | 1318.95 | 568.63 | 750.32 | 1661.22 | 278.73 | 0.00 | 0.00 | 0.00 |
September | 1176.38 | 555.90 | 620.48 | 1368.14 | 467.45 | 0.00 | 0.00 | 0.00 |
October | 749.67 | 313.13 | 436.54 | 661.09 | 686.82 | 0.00 | 0.00 | 0.00 |
November | 442.31 | 143.67 | 298.64 | 233.63 | 1045.84 | 0.00 | 0.00 | 0.00 |
December | 342.62 | 147.13 | 195.49 | 153.00 | 1522.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 981.47 | 425.22 | 556.24 | 992.74 | 784.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 342.62 | 143.67 | 195.49 | 153.00 | 238.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1564.63 | 721.95 | 873.87 | 1967.74 | 1680.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2204.89 | 1508.85 | 696.04 | 1938.17 | 2286.52 | 0.00 | 0.00 | 0.00 |
February | 2362.50 | 1596.12 | 766.38 | 2162.91 | 1852.58 | 0.00 | 0.00 | 0.00 |
March | 2055.91 | 1082.57 | 973.34 | 1976.29 | 1348.36 | 0.00 | 0.00 | 0.00 |
April | 1852.24 | 865.96 | 986.28 | 1981.44 | 1019.93 | 0.00 | 0.00 | 0.00 |
May | 1534.52 | 416.03 | 1118.49 | 1738.35 | 642.85 | 0.00 | 0.00 | 0.00 |
June | 1489.78 | 303.33 | 1186.46 | 1877.72 | 439.49 | 0.00 | 0.00 | 0.00 |
July | 1577.04 | 397.37 | 1179.67 | 2075.69 | 381.96 | 0.00 | 0.00 | 0.00 |
August | 1776.80 | 637.20 | 1139.60 | 2374.65 | 451.62 | 0.00 | 0.00 | 0.00 |
September | 2153.11 | 1134.51 | 1018.60 | 2682.70 | 742.52 | 0.00 | 0.00 | 0.00 |
October | 2248.29 | 1410.49 | 837.81 | 2456.43 | 1064.24 | 0.00 | 0.00 | 0.00 |
November | 1696.33 | 1061.94 | 634.40 | 1577.64 | 1508.95 | 0.00 | 0.00 | 0.00 |
December | 1808.89 | 1370.21 | 438.68 | 1703.74 | 2132.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1893.95 | 978.54 | 915.41 | 2044.68 | 1152.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1489.78 | 303.33 | 438.68 | 1577.64 | 381.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2362.50 | 1596.12 | 1186.46 | 2682.70 | 2286.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 502.31 | 203.24 | 299.07 | 229.25 | 1721.98 | 0.00 | 0.00 | 0.00 |
February | 736.54 | 362.95 | 373.60 | 478.83 | 1383.49 | 0.00 | 0.00 | 0.00 |
March | 879.28 | 327.14 | 552.14 | 664.92 | 913.05 | 0.00 | 0.00 | 0.00 |
April | 1282.61 | 634.23 | 648.38 | 1300.93 | 667.14 | 0.00 | 0.00 | 0.00 |
May | 1286.32 | 513.85 | 772.47 | 1430.16 | 418.51 | 0.00 | 0.00 | 0.00 |
June | 1509.34 | 654.11 | 855.23 | 1866.43 | 294.96 | 0.00 | 0.00 | 0.00 |
July | 1620.58 | 769.80 | 850.78 | 2060.80 | 262.64 | 0.00 | 0.00 | 0.00 |
August | 1416.79 | 650.21 | 766.58 | 1811.57 | 301.68 | 0.00 | 0.00 | 0.00 |
September | 1146.85 | 544.35 | 602.50 | 1341.70 | 490.53 | 0.00 | 0.00 | 0.00 |
October | 799.17 | 355.30 | 443.87 | 742.64 | 719.87 | 0.00 | 0.00 | 0.00 |
November | 478.36 | 176.90 | 301.46 | 295.75 | 1071.38 | 0.00 | 0.00 | 0.00 |
December | 367.88 | 173.42 | 194.46 | 199.50 | 1556.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1003.23 | 447.21 | 556.02 | 1037.96 | 814.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 367.88 | 173.42 | 194.46 | 199.50 | 262.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1620.58 | 769.80 | 855.23 | 2060.80 | 1721.98 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.949622E+09 | 0.00 | 0.949622E+09 | 5476430.84 | 0.735710E+10 |
February | 0.108742E+10 | 0.00 | 0.108742E+10 | 76858189.38 | 0.529665E+10 |
March | 0.180433E+10 | 0.00 | 0.180433E+10 | 0.609292E+09 | 0.368977E+10 |
April | 0.201578E+10 | 9931654.83 | 0.200585E+10 | 0.116304E+10 | 0.243613E+10 |
May | 0.271624E+10 | 0.102097E+09 | 0.261414E+10 | 0.240780E+10 | 0.149665E+10 |
June | 0.307225E+10 | 0.278847E+09 | 0.279340E+10 | 0.347266E+10 | 0.101301E+10 |
July | 0.297733E+10 | 0.199151E+09 | 0.277818E+10 | 0.350629E+10 | 0.924092E+09 |
August | 0.249290E+10 | 44181142.49 | 0.244872E+10 | 0.292589E+10 | 0.107790E+10 |
September | 0.184968E+10 | 458638.62 | 0.184922E+10 | 0.173621E+10 | 0.177392E+10 |
October | 0.142112E+10 | 0.00 | 0.142112E+10 | 0.732706E+09 | 0.272245E+10 |
November | 0.962018E+09 | 0.00 | 0.962018E+09 | 0.182738E+09 | 0.416992E+10 |
December | 0.644823E+09 | 0.00 | 0.644823E+09 | 2178288.33 | 0.644044E+10 |
Annual Sum or Average | 0.219935E+11 | 0.634666E+09 | 0.213588E+11 | 0.168211E+11 | 0.383980E+11 |
Minimum of Months | 0.644823E+09 | 0.00 | 0.644823E+09 | 2178288.33 | 0.924092E+09 |
Maximum of Months | 0.307225E+10 | 0.278847E+09 | 0.279340E+10 | 0.350629E+10 | 0.735710E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135656E+10 | 0.558227E+09 | 0.798332E+09 | 0.595624E+09 | 0.442543E+10 |
February | 0.162410E+10 | 0.714148E+09 | 0.909953E+09 | 0.947192E+09 | 0.313406E+10 |
March | 0.244309E+10 | 0.969731E+09 | 0.147335E+10 | 0.189940E+10 | 0.226176E+10 |
April | 0.290310E+10 | 0.127136E+10 | 0.163175E+10 | 0.277961E+10 | 0.156781E+10 |
May | 0.376760E+10 | 0.164627E+10 | 0.212134E+10 | 0.417721E+10 | 0.100899E+10 |
June | 0.401240E+10 | 0.174733E+10 | 0.226507E+10 | 0.493128E+10 | 0.679593E+09 |
July | 0.419069E+10 | 0.193368E+10 | 0.225702E+10 | 0.526603E+10 | 0.619361E+09 |
August | 0.353267E+10 | 0.152301E+10 | 0.200966E+10 | 0.445126E+10 | 0.717982E+09 |
September | 0.304919E+10 | 0.144090E+10 | 0.160829E+10 | 0.356484E+10 | 0.114368E+10 |
October | 0.200792E+10 | 0.838692E+09 | 0.116923E+10 | 0.182066E+10 | 0.170871E+10 |
November | 0.114648E+10 | 0.372396E+09 | 0.774081E+09 | 0.632003E+09 | 0.258437E+10 |
December | 0.917674E+09 | 0.394071E+09 | 0.523603E+09 | 0.418053E+09 | 0.396853E+10 |
Annual Sum or Average | 0.309515E+11 | 0.134098E+11 | 0.175417E+11 | 0.314832E+11 | 0.238203E+11 |
Minimum of Months | 0.917674E+09 | 0.372396E+09 | 0.523603E+09 | 0.418053E+09 | 0.619361E+09 |
Maximum of Months | 0.419069E+10 | 0.193368E+10 | 0.226507E+10 | 0.526603E+10 | 0.442543E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.590558E+10 | 0.404132E+10 | 0.186427E+10 | 0.521255E+10 | 0.599953E+10 |
February | 0.571537E+10 | 0.386134E+10 | 0.185402E+10 | 0.526350E+10 | 0.433307E+10 |
March | 0.550655E+10 | 0.289956E+10 | 0.260699E+10 | 0.532691E+10 | 0.344944E+10 |
April | 0.480100E+10 | 0.224456E+10 | 0.255645E+10 | 0.515716E+10 | 0.249658E+10 |
May | 0.411005E+10 | 0.111429E+10 | 0.299577E+10 | 0.467435E+10 | 0.163514E+10 |
June | 0.386152E+10 | 0.786225E+09 | 0.307530E+10 | 0.487252E+10 | 0.108522E+10 |
July | 0.422395E+10 | 0.106432E+10 | 0.315963E+10 | 0.555670E+10 | 0.985606E+09 |
August | 0.475899E+10 | 0.170668E+10 | 0.305230E+10 | 0.636082E+10 | 0.115696E+10 |
September | 0.558085E+10 | 0.294064E+10 | 0.264021E+10 | 0.697881E+10 | 0.181041E+10 |
October | 0.602183E+10 | 0.377785E+10 | 0.224398E+10 | 0.664532E+10 | 0.264186E+10 |
November | 0.439690E+10 | 0.275254E+10 | 0.164436E+10 | 0.414453E+10 | 0.371290E+10 |
December | 0.484494E+10 | 0.366998E+10 | 0.117496E+10 | 0.459239E+10 | 0.553441E+10 |
Annual Sum or Average | 0.597275E+11 | 0.308593E+11 | 0.288682E+11 | 0.647856E+11 | 0.348411E+11 |
Minimum of Months | 0.386152E+10 | 0.786225E+09 | 0.117496E+10 | 0.414453E+10 | 0.985606E+09 |
Maximum of Months | 0.602183E+10 | 0.404132E+10 | 0.315963E+10 | 0.697881E+10 | 0.599953E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134538E+10 | 0.544355E+09 | 0.801022E+09 | 0.616199E+09 | 0.453403E+10 |
February | 0.178185E+10 | 0.878038E+09 | 0.903807E+09 | 0.116597E+10 | 0.325332E+10 |
March | 0.235507E+10 | 0.876212E+09 | 0.147885E+10 | 0.179712E+10 | 0.233935E+10 |
April | 0.332452E+10 | 0.164391E+10 | 0.168061E+10 | 0.338453E+10 | 0.163402E+10 |
May | 0.344528E+10 | 0.137630E+10 | 0.206897E+10 | 0.384669E+10 | 0.106420E+10 |
June | 0.391222E+10 | 0.169546E+10 | 0.221676E+10 | 0.484190E+10 | 0.730199E+09 |
July | 0.434055E+10 | 0.206183E+10 | 0.227872E+10 | 0.551829E+10 | 0.679064E+09 |
August | 0.379473E+10 | 0.174153E+10 | 0.205320E+10 | 0.485575E+10 | 0.773836E+09 |
September | 0.297264E+10 | 0.141097E+10 | 0.156168E+10 | 0.349947E+10 | 0.119562E+10 |
October | 0.214051E+10 | 0.951644E+09 | 0.118886E+10 | 0.202731E+10 | 0.178724E+10 |
November | 0.123990E+10 | 0.458515E+09 | 0.781390E+09 | 0.788484E+09 | 0.264711E+10 |
December | 0.985336E+09 | 0.464501E+09 | 0.520835E+09 | 0.540202E+09 | 0.405578E+10 |
Annual Sum or Average | 0.316380E+11 | 0.141033E+11 | 0.175347E+11 | 0.328819E+11 | 0.246938E+11 |
Minimum of Months | 0.985336E+09 | 0.458515E+09 | 0.520835E+09 | 0.540202E+09 | 0.679064E+09 |
Maximum of Months | 0.434055E+10 | 0.206183E+10 | 0.227872E+10 | 0.551829E+10 | 0.453403E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316526E+09 | 0.00 | 0.316526E+09 | 1978208.43 | 0.245488E+10 |
February | 0.362458E+09 | 0.00 | 0.362458E+09 | 26020481.77 | 0.177460E+10 |
March | 0.601414E+09 | 0.00 | 0.601414E+09 | 0.216686E+09 | 0.123606E+10 |
April | 0.671895E+09 | 3310394.98 | 0.668584E+09 | 0.416593E+09 | 0.799489E+09 |
May | 0.905369E+09 | 34030729.52 | 0.871338E+09 | 0.848115E+09 | 0.476473E+09 |
June | 0.102403E+10 | 92944440.68 | 0.931090E+09 | 0.118534E+10 | 0.330041E+09 |
July | 0.992397E+09 | 66380465.61 | 0.926016E+09 | 0.119034E+10 | 0.303617E+09 |
August | 0.830927E+09 | 14726350.73 | 0.816201E+09 | 0.983110E+09 | 0.367416E+09 |
September | 0.616532E+09 | 152872.31 | 0.616379E+09 | 0.572076E+09 | 0.633915E+09 |
October | 0.473683E+09 | 0.00 | 0.473683E+09 | 0.224979E+09 | 0.997156E+09 |
November | 0.320658E+09 | 0.00 | 0.320658E+09 | 53088507.36 | 0.147526E+10 |
December | 0.214931E+09 | 0.00 | 0.214931E+09 | 246766.79 | 0.219852E+10 |
Annual Sum or Average | 0.733082E+10 | 0.211545E+09 | 0.711928E+10 | 0.571857E+10 | 0.130474E+11 |
Minimum of Months | 0.214931E+09 | 0.00 | 0.214931E+09 | 246766.79 | 0.303617E+09 |
Maximum of Months | 0.102403E+10 | 92944440.68 | 0.931090E+09 | 0.119034E+10 | 0.245488E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316546E+09 | 0.00 | 0.316546E+09 | 1978333.44 | 0.245504E+10 |
February | 0.362481E+09 | 0.00 | 0.362481E+09 | 26022126.22 | 0.177471E+10 |
March | 0.601452E+09 | 0.00 | 0.601452E+09 | 0.216700E+09 | 0.123614E+10 |
April | 0.671937E+09 | 3310604.19 | 0.668627E+09 | 0.416619E+09 | 0.799540E+09 |
May | 0.905426E+09 | 34032880.20 | 0.871393E+09 | 0.848169E+09 | 0.476503E+09 |
June | 0.102410E+10 | 92950314.62 | 0.931149E+09 | 0.118541E+10 | 0.330061E+09 |
July | 0.992460E+09 | 66384660.75 | 0.926075E+09 | 0.119041E+10 | 0.303636E+09 |
August | 0.830980E+09 | 14727281.41 | 0.816252E+09 | 0.983172E+09 | 0.367439E+09 |
September | 0.616571E+09 | 152881.97 | 0.616418E+09 | 0.572113E+09 | 0.633955E+09 |
October | 0.473713E+09 | 0.00 | 0.473713E+09 | 0.224993E+09 | 0.997219E+09 |
November | 0.320678E+09 | 0.00 | 0.320678E+09 | 53091862.46 | 0.147535E+10 |
December | 0.214945E+09 | 0.00 | 0.214945E+09 | 246782.38 | 0.219866E+10 |
Annual Sum or Average | 0.733129E+10 | 0.211559E+09 | 0.711973E+10 | 0.571893E+10 | 0.130483E+11 |
Minimum of Months | 0.214945E+09 | 0.00 | 0.214945E+09 | 246782.38 | 0.303636E+09 |
Maximum of Months | 0.102410E+10 | 92950314.62 | 0.931149E+09 | 0.119041E+10 | 0.245504E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316546E+09 | 0.00 | 0.316546E+09 | 1978333.44 | 0.245504E+10 |
February | 0.362481E+09 | 0.00 | 0.362481E+09 | 26022126.22 | 0.177471E+10 |
March | 0.601452E+09 | 0.00 | 0.601452E+09 | 0.216700E+09 | 0.123614E+10 |
April | 0.671937E+09 | 3310604.19 | 0.668627E+09 | 0.416619E+09 | 0.799540E+09 |
May | 0.905426E+09 | 34032880.20 | 0.871393E+09 | 0.848169E+09 | 0.476503E+09 |
June | 0.102410E+10 | 92950314.62 | 0.931149E+09 | 0.118541E+10 | 0.330061E+09 |
July | 0.992460E+09 | 66384660.75 | 0.926075E+09 | 0.119041E+10 | 0.303636E+09 |
August | 0.830980E+09 | 14727281.41 | 0.816252E+09 | 0.983172E+09 | 0.367439E+09 |
September | 0.616571E+09 | 152881.97 | 0.616418E+09 | 0.572113E+09 | 0.633955E+09 |
October | 0.473713E+09 | 0.00 | 0.473713E+09 | 0.224993E+09 | 0.997219E+09 |
November | 0.320678E+09 | 0.00 | 0.320678E+09 | 53091862.46 | 0.147535E+10 |
December | 0.214945E+09 | 0.00 | 0.214945E+09 | 246782.38 | 0.219866E+10 |
Annual Sum or Average | 0.733129E+10 | 0.211559E+09 | 0.711973E+10 | 0.571893E+10 | 0.130483E+11 |
Minimum of Months | 0.214945E+09 | 0.00 | 0.214945E+09 | 246782.38 | 0.303636E+09 |
Maximum of Months | 0.102410E+10 | 92950314.62 | 0.931149E+09 | 0.119041E+10 | 0.245504E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130495E+10 | 0.536989E+09 | 0.767963E+09 | 0.581750E+09 | 0.428172E+10 |
February | 0.156232E+10 | 0.686978E+09 | 0.875337E+09 | 0.921277E+09 | 0.305983E+10 |
March | 0.235014E+10 | 0.932837E+09 | 0.141731E+10 | 0.186360E+10 | 0.221045E+10 |
April | 0.279266E+10 | 0.122299E+10 | 0.156967E+10 | 0.273320E+10 | 0.151591E+10 |
May | 0.362427E+10 | 0.158364E+10 | 0.204064E+10 | 0.408234E+10 | 0.971317E+09 |
June | 0.385976E+10 | 0.168086E+10 | 0.217890E+10 | 0.478748E+10 | 0.665790E+09 |
July | 0.403127E+10 | 0.186011E+10 | 0.217116E+10 | 0.510054E+10 | 0.613701E+09 |
August | 0.339828E+10 | 0.146507E+10 | 0.193321E+10 | 0.429821E+10 | 0.729396E+09 |
September | 0.293319E+10 | 0.138608E+10 | 0.154711E+10 | 0.341498E+10 | 0.120986E+10 |
October | 0.193154E+10 | 0.806784E+09 | 0.112475E+10 | 0.169461E+10 | 0.183915E+10 |
November | 0.110286E+10 | 0.358228E+09 | 0.744634E+09 | 0.581763E+09 | 0.265171E+10 |
December | 0.882763E+09 | 0.379078E+09 | 0.503685E+09 | 0.399528E+09 | 0.392188E+10 |
Annual Sum or Average | 0.297740E+11 | 0.128996E+11 | 0.168744E+11 | 0.304593E+11 | 0.236707E+11 |
Minimum of Months | 0.882763E+09 | 0.358228E+09 | 0.503685E+09 | 0.399528E+09 | 0.613701E+09 |
Maximum of Months | 0.403127E+10 | 0.186011E+10 | 0.217890E+10 | 0.510054E+10 | 0.428172E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51596621.93 | 21232073.00 | 30364548.93 | 23001879.92 | 0.169295E+09 |
February | 61772548.54 | 27162502.69 | 34610045.85 | 36426453.10 | 0.120983E+09 |
March | 92922567.74 | 36883552.92 | 56039014.82 | 73685188.76 | 87399294.48 |
April | 0.110419E+09 | 48355943.15 | 62063460.04 | 0.108068E+09 | 59937757.64 |
May | 0.143301E+09 | 62615530.52 | 80685009.18 | 0.161412E+09 | 38405011.89 |
June | 0.152611E+09 | 66459530.08 | 86151818.62 | 0.189293E+09 | 26324723.00 |
July | 0.159393E+09 | 73547039.82 | 85845646.08 | 0.201671E+09 | 24265168.63 |
August | 0.134365E+09 | 57927429.67 | 76437569.58 | 0.169947E+09 | 28839680.89 |
September | 0.115976E+09 | 54804259.11 | 61171327.77 | 0.135025E+09 | 47836614.22 |
October | 76371238.38 | 31899528.86 | 44471709.52 | 67003427.83 | 72718329.34 |
November | 43606186.80 | 14164032.29 | 29442154.51 | 23002367.23 | 0.104846E+09 |
December | 34903658.97 | 14988410.26 | 19915248.71 | 15796969.67 | 0.155068E+09 |
Annual Sum or Average | 0.117724E+10 | 0.510040E+09 | 0.667198E+09 | 0.120433E+10 | 0.935919E+09 |
Minimum of Months | 34903658.97 | 14164032.29 | 19915248.71 | 15796969.67 | 24265168.63 |
Maximum of Months | 0.159393E+09 | 73547039.82 | 86151818.62 | 0.201671E+09 | 0.169295E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196859E+10 | 0.134715E+10 | 0.621441E+09 | 0.179540E+10 | 0.194940E+10 |
February | 0.190518E+10 | 0.128716E+10 | 0.618026E+09 | 0.180575E+10 | 0.144495E+10 |
March | 0.183557E+10 | 0.966552E+09 | 0.869020E+09 | 0.182691E+10 | 0.115098E+10 |
April | 0.160038E+10 | 0.748210E+09 | 0.852172E+09 | 0.176570E+10 | 0.826108E+09 |
May | 0.137006E+10 | 0.371441E+09 | 0.998616E+09 | 0.161164E+10 | 0.527725E+09 |
June | 0.128721E+10 | 0.262083E+09 | 0.102513E+10 | 0.165828E+10 | 0.355393E+09 |
July | 0.140802E+10 | 0.354785E+09 | 0.105324E+10 | 0.187557E+10 | 0.331319E+09 |
August | 0.158638E+10 | 0.568912E+09 | 0.101746E+10 | 0.213485E+10 | 0.406284E+09 |
September | 0.186034E+10 | 0.980247E+09 | 0.880094E+09 | 0.233213E+10 | 0.658729E+09 |
October | 0.200734E+10 | 0.125932E+10 | 0.748016E+09 | 0.221358E+10 | 0.986835E+09 |
November | 0.146568E+10 | 0.917542E+09 | 0.548136E+09 | 0.138691E+10 | 0.131062E+10 |
December | 0.161503E+10 | 0.122337E+10 | 0.391664E+09 | 0.155549E+10 | 0.185461E+10 |
Annual Sum or Average | 0.199098E+11 | 0.102868E+11 | 0.962302E+10 | 0.219622E+11 | 0.118030E+11 |
Minimum of Months | 0.128721E+10 | 0.262083E+09 | 0.391664E+09 | 0.138691E+10 | 0.331319E+09 |
Maximum of Months | 0.200734E+10 | 0.134715E+10 | 0.105324E+10 | 0.233213E+10 | 0.194940E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196859E+10 | 0.134715E+10 | 0.621441E+09 | 0.179540E+10 | 0.194940E+10 |
February | 0.190518E+10 | 0.128716E+10 | 0.618026E+09 | 0.180575E+10 | 0.144495E+10 |
March | 0.183557E+10 | 0.966552E+09 | 0.869020E+09 | 0.182691E+10 | 0.115098E+10 |
April | 0.160038E+10 | 0.748210E+09 | 0.852172E+09 | 0.176570E+10 | 0.826108E+09 |
May | 0.137006E+10 | 0.371441E+09 | 0.998616E+09 | 0.161164E+10 | 0.527725E+09 |
June | 0.128721E+10 | 0.262083E+09 | 0.102513E+10 | 0.165828E+10 | 0.355393E+09 |
July | 0.140802E+10 | 0.354785E+09 | 0.105324E+10 | 0.187557E+10 | 0.331319E+09 |
August | 0.158638E+10 | 0.568912E+09 | 0.101746E+10 | 0.213485E+10 | 0.406284E+09 |
September | 0.186034E+10 | 0.980247E+09 | 0.880094E+09 | 0.233213E+10 | 0.658729E+09 |
October | 0.200734E+10 | 0.125932E+10 | 0.748016E+09 | 0.221358E+10 | 0.986835E+09 |
November | 0.146568E+10 | 0.917542E+09 | 0.548136E+09 | 0.138691E+10 | 0.131062E+10 |
December | 0.161503E+10 | 0.122337E+10 | 0.391664E+09 | 0.155549E+10 | 0.185461E+10 |
Annual Sum or Average | 0.199098E+11 | 0.102868E+11 | 0.962302E+10 | 0.219622E+11 | 0.118030E+11 |
Minimum of Months | 0.128721E+10 | 0.262083E+09 | 0.391664E+09 | 0.138691E+10 | 0.331319E+09 |
Maximum of Months | 0.200734E+10 | 0.134715E+10 | 0.105324E+10 | 0.233213E+10 | 0.194940E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196847E+10 | 0.134706E+10 | 0.621402E+09 | 0.179529E+10 | 0.194928E+10 |
February | 0.190506E+10 | 0.128708E+10 | 0.617987E+09 | 0.180564E+10 | 0.144486E+10 |
March | 0.183546E+10 | 0.966491E+09 | 0.868965E+09 | 0.182679E+10 | 0.115091E+10 |
April | 0.160028E+10 | 0.748163E+09 | 0.852118E+09 | 0.176558E+10 | 0.826056E+09 |
May | 0.136997E+10 | 0.371418E+09 | 0.998553E+09 | 0.161154E+10 | 0.527692E+09 |
June | 0.128713E+10 | 0.262067E+09 | 0.102506E+10 | 0.165817E+10 | 0.355371E+09 |
July | 0.140793E+10 | 0.354763E+09 | 0.105317E+10 | 0.187546E+10 | 0.331298E+09 |
August | 0.158628E+10 | 0.568876E+09 | 0.101740E+10 | 0.213472E+10 | 0.406259E+09 |
September | 0.186022E+10 | 0.980185E+09 | 0.880038E+09 | 0.233198E+10 | 0.658688E+09 |
October | 0.200721E+10 | 0.125924E+10 | 0.747969E+09 | 0.221344E+10 | 0.986773E+09 |
November | 0.146559E+10 | 0.917484E+09 | 0.548101E+09 | 0.138682E+10 | 0.131054E+10 |
December | 0.161493E+10 | 0.122329E+10 | 0.391640E+09 | 0.155539E+10 | 0.185449E+10 |
Annual Sum or Average | 0.199085E+11 | 0.102861E+11 | 0.962241E+10 | 0.219608E+11 | 0.118022E+11 |
Minimum of Months | 0.128713E+10 | 0.262067E+09 | 0.391640E+09 | 0.138682E+10 | 0.331298E+09 |
Maximum of Months | 0.200721E+10 | 0.134706E+10 | 0.105317E+10 | 0.233198E+10 | 0.194928E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129420E+10 | 0.523645E+09 | 0.770550E+09 | 0.607793E+09 | 0.438290E+10 |
February | 0.171406E+10 | 0.844634E+09 | 0.869425E+09 | 0.114307E+10 | 0.317142E+10 |
March | 0.226547E+10 | 0.842876E+09 | 0.142260E+10 | 0.177470E+10 | 0.228427E+10 |
April | 0.319805E+10 | 0.158137E+10 | 0.161668E+10 | 0.331683E+10 | 0.159238E+10 |
May | 0.331421E+10 | 0.132394E+10 | 0.199027E+10 | 0.376523E+10 | 0.102025E+10 |
June | 0.376339E+10 | 0.163095E+10 | 0.213244E+10 | 0.469855E+10 | 0.714051E+09 |
July | 0.417543E+10 | 0.198338E+10 | 0.219204E+10 | 0.533675E+10 | 0.678619E+09 |
August | 0.365037E+10 | 0.167528E+10 | 0.197510E+10 | 0.468409E+10 | 0.792203E+09 |
September | 0.285955E+10 | 0.135729E+10 | 0.150227E+10 | 0.334835E+10 | 0.126243E+10 |
October | 0.205908E+10 | 0.915439E+09 | 0.114364E+10 | 0.191273E+10 | 0.191864E+10 |
November | 0.119274E+10 | 0.441071E+09 | 0.751664E+09 | 0.739992E+09 | 0.271524E+10 |
December | 0.947851E+09 | 0.446829E+09 | 0.501022E+09 | 0.523292E+09 | 0.400609E+10 |
Annual Sum or Average | 0.304344E+11 | 0.135667E+11 | 0.168677E+11 | 0.318514E+11 | 0.245385E+11 |
Minimum of Months | 0.947851E+09 | 0.441071E+09 | 0.501022E+09 | 0.523292E+09 | 0.678619E+09 |
Maximum of Months | 0.417543E+10 | 0.198338E+10 | 0.219204E+10 | 0.533675E+10 | 0.438290E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51171174.57 | 20704391.81 | 30466782.76 | 24031435.43 | 0.173296E+09 |
February | 67772152.36 | 33395940.93 | 34376211.43 | 45195712.54 | 0.125395E+09 |
March | 89574520.26 | 33326463.27 | 56248056.99 | 70169855.29 | 90318095.32 |
April | 0.126448E+09 | 62525836.95 | 63921762.13 | 0.131144E+09 | 62961160.42 |
May | 0.131041E+09 | 52347344.96 | 78693297.11 | 0.148873E+09 | 40339683.06 |
June | 0.148801E+09 | 64486185.81 | 84314374.07 | 0.185776E+09 | 28232937.47 |
July | 0.165092E+09 | 78420958.81 | 86671142.14 | 0.211010E+09 | 26831966.29 |
August | 0.144332E+09 | 66238656.53 | 78093356.14 | 0.185204E+09 | 31322988.88 |
September | 0.113064E+09 | 53665679.25 | 59398210.88 | 0.132390E+09 | 49915370.20 |
October | 81413805.37 | 36195505.22 | 45218300.15 | 75627223.60 | 75861149.13 |
November | 47159554.11 | 17439491.87 | 29720062.24 | 29258487.08 | 0.107358E+09 |
December | 37477073.33 | 17667157.90 | 19809915.43 | 20690390.20 | 0.158397E+09 |
Annual Sum or Average | 0.120335E+10 | 0.536414E+09 | 0.666931E+09 | 0.125937E+10 | 0.970230E+09 |
Minimum of Months | 37477073.33 | 17439491.87 | 19809915.43 | 20690390.20 | 26831966.29 |
Maximum of Months | 0.165092E+09 | 78420958.81 | 86671142.14 | 0.211010E+09 | 0.173296E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.949622E+09 | 0.00 | 0.949622E+09 | 4603378.60 | 0.747999E+10 |
February | 0.108742E+10 | 0.00 | 0.108742E+10 | 69676662.04 | 0.544316E+10 |
March | 0.180433E+10 | 0.00 | 0.180433E+10 | 0.583990E+09 | 0.385429E+10 |
April | 0.201578E+10 | 9931654.83 | 0.200585E+10 | 0.113522E+10 | 0.258706E+10 |
May | 0.271624E+10 | 0.102097E+09 | 0.261414E+10 | 0.237014E+10 | 0.157752E+10 |
June | 0.307225E+10 | 0.278847E+09 | 0.279340E+10 | 0.345847E+10 | 0.105983E+10 |
July | 0.297733E+10 | 0.199151E+09 | 0.277818E+10 | 0.350154E+10 | 0.957134E+09 |
August | 0.249290E+10 | 44181142.49 | 0.244872E+10 | 0.291295E+10 | 0.112700E+10 |
September | 0.184968E+10 | 458638.62 | 0.184922E+10 | 0.169810E+10 | 0.189786E+10 |
October | 0.142112E+10 | 0.00 | 0.142112E+10 | 0.669898E+09 | 0.294918E+10 |
November | 0.962018E+09 | 0.00 | 0.962018E+09 | 0.156813E+09 | 0.438139E+10 |
December | 0.644823E+09 | 0.00 | 0.644823E+09 | 609098.35 | 0.661654E+10 |
Annual Sum or Average | 0.219935E+11 | 0.634666E+09 | 0.213588E+11 | 0.165620E+11 | 0.399310E+11 |
Minimum of Months | 0.644823E+09 | 0.00 | 0.644823E+09 | 609098.35 | 0.957134E+09 |
Maximum of Months | 0.307225E+10 | 0.278847E+09 | 0.279340E+10 | 0.350154E+10 | 0.747999E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135656E+10 | 0.558227E+09 | 0.798332E+09 | 0.589750E+09 | 0.450129E+10 |
February | 0.162410E+10 | 0.714148E+09 | 0.909953E+09 | 0.934297E+09 | 0.322537E+10 |
March | 0.244309E+10 | 0.969731E+09 | 0.147335E+10 | 0.187487E+10 | 0.236251E+10 |
April | 0.290310E+10 | 0.127136E+10 | 0.163175E+10 | 0.276219E+10 | 0.165449E+10 |
May | 0.376760E+10 | 0.164627E+10 | 0.212134E+10 | 0.416488E+10 | 0.105514E+10 |
June | 0.401240E+10 | 0.174733E+10 | 0.226507E+10 | 0.492905E+10 | 0.708191E+09 |
July | 0.419069E+10 | 0.193368E+10 | 0.225702E+10 | 0.527041E+10 | 0.638900E+09 |
August | 0.353267E+10 | 0.152301E+10 | 0.200966E+10 | 0.444940E+10 | 0.746560E+09 |
September | 0.304919E+10 | 0.144090E+10 | 0.160829E+10 | 0.354623E+10 | 0.121162E+10 |
October | 0.200792E+10 | 0.838692E+09 | 0.116923E+10 | 0.177065E+10 | 0.183957E+10 |
November | 0.114648E+10 | 0.372396E+09 | 0.774081E+09 | 0.605564E+09 | 0.271083E+10 |
December | 0.917674E+09 | 0.394071E+09 | 0.523603E+09 | 0.409791E+09 | 0.407908E+10 |
Annual Sum or Average | 0.309515E+11 | 0.134098E+11 | 0.175417E+11 | 0.313071E+11 | 0.247336E+11 |
Minimum of Months | 0.917674E+09 | 0.372396E+09 | 0.523603E+09 | 0.409791E+09 | 0.638900E+09 |
Maximum of Months | 0.419069E+10 | 0.193368E+10 | 0.226507E+10 | 0.527041E+10 | 0.450129E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.590558E+10 | 0.404132E+10 | 0.186427E+10 | 0.519120E+10 | 0.612421E+10 |
February | 0.571537E+10 | 0.386134E+10 | 0.185402E+10 | 0.523250E+10 | 0.448177E+10 |
March | 0.550655E+10 | 0.289956E+10 | 0.260699E+10 | 0.529329E+10 | 0.361144E+10 |
April | 0.480100E+10 | 0.224456E+10 | 0.255645E+10 | 0.513590E+10 | 0.264366E+10 |
May | 0.411005E+10 | 0.111429E+10 | 0.299577E+10 | 0.465601E+10 | 0.172180E+10 |
June | 0.386152E+10 | 0.786225E+09 | 0.307530E+10 | 0.486705E+10 | 0.113915E+10 |
July | 0.422395E+10 | 0.106432E+10 | 0.315963E+10 | 0.555953E+10 | 0.102304E+10 |
August | 0.475899E+10 | 0.170668E+10 | 0.305230E+10 | 0.636026E+10 | 0.120962E+10 |
September | 0.558085E+10 | 0.294064E+10 | 0.264021E+10 | 0.695356E+10 | 0.192462E+10 |
October | 0.602183E+10 | 0.377785E+10 | 0.224398E+10 | 0.657931E+10 | 0.285046E+10 |
November | 0.439690E+10 | 0.275254E+10 | 0.164436E+10 | 0.408924E+10 | 0.391120E+10 |
December | 0.484494E+10 | 0.366998E+10 | 0.117496E+10 | 0.456330E+10 | 0.571092E+10 |
Annual Sum or Average | 0.597275E+11 | 0.308593E+11 | 0.288682E+11 | 0.644811E+11 | 0.363519E+11 |
Minimum of Months | 0.386152E+10 | 0.786225E+09 | 0.117496E+10 | 0.408924E+10 | 0.102304E+10 |
Maximum of Months | 0.602183E+10 | 0.404132E+10 | 0.315963E+10 | 0.695356E+10 | 0.612421E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134538E+10 | 0.544355E+09 | 0.801022E+09 | 0.614028E+09 | 0.461215E+10 |
February | 0.178185E+10 | 0.878038E+09 | 0.903807E+09 | 0.115837E+10 | 0.334694E+10 |
March | 0.235507E+10 | 0.876212E+09 | 0.147885E+10 | 0.178093E+10 | 0.244552E+10 |
April | 0.332452E+10 | 0.164391E+10 | 0.168061E+10 | 0.337201E+10 | 0.172922E+10 |
May | 0.344528E+10 | 0.137630E+10 | 0.206897E+10 | 0.383055E+10 | 0.112092E+10 |
June | 0.391222E+10 | 0.169546E+10 | 0.221676E+10 | 0.483779E+10 | 0.764547E+09 |
July | 0.434055E+10 | 0.206183E+10 | 0.227872E+10 | 0.551965E+10 | 0.703455E+09 |
August | 0.379473E+10 | 0.174153E+10 | 0.205320E+10 | 0.485211E+10 | 0.808007E+09 |
September | 0.297264E+10 | 0.141097E+10 | 0.156168E+10 | 0.347769E+10 | 0.127145E+10 |
October | 0.214051E+10 | 0.951644E+09 | 0.118886E+10 | 0.198908E+10 | 0.192811E+10 |
November | 0.123990E+10 | 0.458515E+09 | 0.781390E+09 | 0.766573E+09 | 0.277702E+10 |
December | 0.985336E+09 | 0.464501E+09 | 0.520835E+09 | 0.534330E+09 | 0.416766E+10 |
Annual Sum or Average | 0.316380E+11 | 0.141033E+11 | 0.175347E+11 | 0.327331E+11 | 0.256750E+11 |
Minimum of Months | 0.985336E+09 | 0.458515E+09 | 0.520835E+09 | 0.534330E+09 | 0.703455E+09 |
Maximum of Months | 0.434055E+10 | 0.206183E+10 | 0.227872E+10 | 0.551965E+10 | 0.461215E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.04 | 2746.82 | 354.55 | 0.00 | 354.55 | 0.00 | 0.00 |
February | 31.77 | 2189.42 | 449.50 | 0.00 | 449.50 | 0.00 | 0.00 |
March | 227.48 | 1377.60 | 673.66 | 0.00 | 673.66 | 0.00 | 0.00 |
April | 448.70 | 939.87 | 777.69 | 3.83 | 773.86 | 0.00 | 0.00 |
May | 898.97 | 558.78 | 1014.13 | 38.12 | 976.01 | 0.00 | 0.00 |
June | 1339.76 | 390.82 | 1185.28 | 107.58 | 1077.70 | 0.00 | 0.00 |
July | 1309.10 | 345.02 | 1111.61 | 74.35 | 1037.25 | 0.00 | 0.00 |
August | 1092.40 | 402.44 | 930.74 | 16.50 | 914.25 | 0.00 | 0.00 |
September | 669.83 | 684.38 | 713.61 | 0.18 | 713.44 | 0.00 | 0.00 |
October | 273.56 | 1016.45 | 530.58 | 0.00 | 530.58 | 0.00 | 0.00 |
November | 70.50 | 1608.76 | 371.15 | 0.00 | 371.15 | 0.00 | 0.00 |
December | 0.81 | 2404.59 | 240.75 | 0.00 | 240.75 | 0.00 | 0.00 |
Annual Sum or Average | 533.39 | 1217.59 | 697.41 | 20.13 | 677.28 | 0.00 | 0.00 |
Minimum of Months | 0.81 | 345.02 | 240.75 | 0.00 | 240.75 | 0.00 | 0.00 |
Maximum of Months | 1339.76 | 2746.82 | 1185.28 | 107.58 | 1077.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 222.38 | 1652.27 | 506.48 | 208.42 | 298.06 | 0.00 | 0.00 |
February | 391.53 | 1295.49 | 671.34 | 295.20 | 376.14 | 0.00 | 0.00 |
March | 709.16 | 844.45 | 912.14 | 362.06 | 550.09 | 0.00 | 0.00 |
April | 1072.38 | 604.87 | 1120.03 | 490.49 | 629.53 | 0.00 | 0.00 |
May | 1559.59 | 376.71 | 1406.66 | 614.65 | 792.02 | 0.00 | 0.00 |
June | 1902.50 | 262.19 | 1547.99 | 674.13 | 873.87 | 0.00 | 0.00 |
July | 1966.11 | 231.24 | 1564.63 | 721.95 | 842.67 | 0.00 | 0.00 |
August | 1661.91 | 268.06 | 1318.95 | 568.63 | 750.32 | 0.00 | 0.00 |
September | 1375.32 | 441.23 | 1176.38 | 555.90 | 620.48 | 0.00 | 0.00 |
October | 679.76 | 637.96 | 749.67 | 313.13 | 436.54 | 0.00 | 0.00 |
November | 243.83 | 997.06 | 442.31 | 143.67 | 298.64 | 0.00 | 0.00 |
December | 156.08 | 1481.68 | 342.62 | 147.13 | 195.49 | 0.00 | 0.00 |
Annual Sum or Average | 998.32 | 755.34 | 981.47 | 425.22 | 556.24 | 0.00 | 0.00 |
Minimum of Months | 156.08 | 231.24 | 342.62 | 143.67 | 195.49 | 0.00 | 0.00 |
Maximum of Months | 1966.11 | 1652.27 | 1564.63 | 721.95 | 873.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1946.14 | 2239.97 | 2204.89 | 1508.85 | 696.04 | 0.00 | 0.00 |
February | 2175.72 | 1791.12 | 2362.50 | 1596.12 | 766.38 | 0.00 | 0.00 |
March | 1988.84 | 1287.87 | 2055.91 | 1082.57 | 973.34 | 0.00 | 0.00 |
April | 1989.64 | 963.19 | 1852.24 | 865.96 | 986.28 | 0.00 | 0.00 |
May | 1745.20 | 610.49 | 1534.52 | 416.03 | 1118.49 | 0.00 | 0.00 |
June | 1879.83 | 418.68 | 1489.78 | 303.33 | 1186.46 | 0.00 | 0.00 |
July | 2074.63 | 367.98 | 1577.04 | 397.37 | 1179.67 | 0.00 | 0.00 |
August | 2374.86 | 431.96 | 1776.80 | 637.20 | 1139.60 | 0.00 | 0.00 |
September | 2692.44 | 698.46 | 2153.11 | 1134.51 | 1018.60 | 0.00 | 0.00 |
October | 2481.08 | 986.36 | 2248.29 | 1410.49 | 837.81 | 0.00 | 0.00 |
November | 1598.97 | 1432.45 | 1696.33 | 1061.94 | 634.40 | 0.00 | 0.00 |
December | 1714.60 | 2066.31 | 1808.89 | 1370.21 | 438.68 | 0.00 | 0.00 |
Annual Sum or Average | 2054.34 | 1104.80 | 1893.95 | 978.54 | 915.41 | 0.00 | 0.00 |
Minimum of Months | 1598.97 | 367.98 | 1489.78 | 303.33 | 438.68 | 0.00 | 0.00 |
Maximum of Months | 2692.44 | 2239.97 | 2362.50 | 1596.12 | 1186.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 230.06 | 1692.81 | 502.31 | 203.24 | 299.07 | 0.00 | 0.00 |
February | 481.96 | 1344.79 | 736.54 | 362.95 | 373.60 | 0.00 | 0.00 |
March | 670.97 | 873.41 | 879.28 | 327.14 | 552.14 | 0.00 | 0.00 |
April | 1305.76 | 630.41 | 1282.61 | 634.23 | 648.38 | 0.00 | 0.00 |
May | 1436.19 | 397.33 | 1286.32 | 513.85 | 772.47 | 0.00 | 0.00 |
June | 1868.02 | 281.71 | 1509.34 | 654.11 | 855.23 | 0.00 | 0.00 |
July | 2060.29 | 253.53 | 1620.58 | 769.80 | 850.78 | 0.00 | 0.00 |
August | 1812.93 | 288.92 | 1416.79 | 650.21 | 766.58 | 0.00 | 0.00 |
September | 1350.10 | 461.27 | 1146.85 | 544.35 | 602.50 | 0.00 | 0.00 |
October | 756.91 | 667.28 | 799.17 | 355.30 | 443.87 | 0.00 | 0.00 |
November | 304.20 | 1021.26 | 478.36 | 176.90 | 301.46 | 0.00 | 0.00 |
December | 201.69 | 1514.26 | 367.88 | 173.42 | 194.46 | 0.00 | 0.00 |
Annual Sum or Average | 1042.68 | 783.03 | 1003.23 | 447.21 | 556.02 | 0.00 | 0.00 |
Minimum of Months | 201.69 | 253.53 | 367.88 | 173.42 | 194.46 | 0.00 | 0.00 |
Maximum of Months | 2060.29 | 1692.81 | 1620.58 | 769.80 | 855.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.22 | 2749.76 | 354.55 | 0.00 | 354.55 | 0.00 | 0.00 |
February | 32.27 | 2200.74 | 449.50 | 0.00 | 449.50 | 0.00 | 0.00 |
March | 242.71 | 1384.54 | 673.66 | 0.00 | 673.66 | 0.00 | 0.00 |
April | 482.19 | 925.37 | 777.69 | 3.83 | 773.86 | 0.00 | 0.00 |
May | 949.99 | 533.71 | 1014.12 | 38.12 | 976.00 | 0.00 | 0.00 |
June | 1371.97 | 382.01 | 1185.28 | 107.58 | 1077.70 | 0.00 | 0.00 |
July | 1333.32 | 340.09 | 1111.60 | 74.35 | 1037.25 | 0.00 | 0.00 |
August | 1101.20 | 411.55 | 930.74 | 16.50 | 914.24 | 0.00 | 0.00 |
September | 662.15 | 733.73 | 713.61 | 0.18 | 713.43 | 0.00 | 0.00 |
October | 252.00 | 1116.93 | 530.58 | 0.00 | 530.58 | 0.00 | 0.00 |
November | 61.45 | 1707.54 | 371.15 | 0.00 | 371.15 | 0.00 | 0.00 |
December | 0.28 | 2462.61 | 240.75 | 0.00 | 240.75 | 0.00 | 0.00 |
Annual Sum or Average | 544.03 | 1241.25 | 697.41 | 20.13 | 677.28 | 0.00 | 0.00 |
Minimum of Months | 0.28 | 340.09 | 240.75 | 0.00 | 240.75 | 0.00 | 0.00 |
Maximum of Months | 1371.97 | 2749.76 | 1185.28 | 107.58 | 1077.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 225.79 | 1661.82 | 506.48 | 208.42 | 298.06 | 0.00 | 0.00 |
February | 395.88 | 1314.82 | 671.33 | 295.20 | 376.14 | 0.00 | 0.00 |
March | 723.30 | 857.92 | 912.14 | 362.05 | 550.08 | 0.00 | 0.00 |
April | 1096.17 | 607.97 | 1120.02 | 490.49 | 629.53 | 0.00 | 0.00 |
May | 1584.43 | 376.99 | 1406.65 | 614.64 | 792.01 | 0.00 | 0.00 |
June | 1920.05 | 267.02 | 1547.98 | 674.12 | 873.86 | 0.00 | 0.00 |
July | 1979.62 | 238.19 | 1564.61 | 721.94 | 842.67 | 0.00 | 0.00 |
August | 1668.22 | 283.09 | 1318.94 | 568.62 | 750.32 | 0.00 | 0.00 |
September | 1369.60 | 485.22 | 1176.37 | 555.90 | 620.48 | 0.00 | 0.00 |
October | 657.71 | 713.81 | 749.67 | 313.13 | 436.54 | 0.00 | 0.00 |
November | 233.32 | 1063.49 | 442.31 | 143.67 | 298.64 | 0.00 | 0.00 |
December | 155.06 | 1522.16 | 342.62 | 147.13 | 195.49 | 0.00 | 0.00 |
Annual Sum or Average | 1004.05 | 780.27 | 981.46 | 425.22 | 556.24 | 0.00 | 0.00 |
Minimum of Months | 155.06 | 238.19 | 342.62 | 143.67 | 195.49 | 0.00 | 0.00 |
Maximum of Months | 1979.62 | 1661.82 | 1564.61 | 721.94 | 873.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2010.94 | 2183.42 | 2204.92 | 1508.87 | 696.04 | 0.00 | 0.00 |
February | 2239.23 | 1791.81 | 2362.53 | 1596.14 | 766.39 | 0.00 | 0.00 |
March | 2046.22 | 1289.15 | 2055.93 | 1082.58 | 973.34 | 0.00 | 0.00 |
April | 2043.59 | 956.12 | 1852.26 | 865.97 | 986.29 | 0.00 | 0.00 |
May | 1805.12 | 591.08 | 1534.53 | 416.03 | 1118.50 | 0.00 | 0.00 |
June | 1919.26 | 411.33 | 1489.80 | 303.33 | 1186.46 | 0.00 | 0.00 |
July | 2100.73 | 371.09 | 1577.05 | 397.38 | 1179.68 | 0.00 | 0.00 |
August | 2391.14 | 455.06 | 1776.82 | 637.21 | 1139.61 | 0.00 | 0.00 |
September | 2699.16 | 762.40 | 2153.13 | 1134.52 | 1018.61 | 0.00 | 0.00 |
October | 2479.31 | 1105.30 | 2248.32 | 1410.50 | 837.81 | 0.00 | 0.00 |
November | 1605.19 | 1516.89 | 1696.35 | 1061.95 | 634.40 | 0.00 | 0.00 |
December | 1742.23 | 2077.25 | 1808.91 | 1370.23 | 438.68 | 0.00 | 0.00 |
Annual Sum or Average | 2089.21 | 1122.78 | 1893.97 | 978.55 | 915.41 | 0.00 | 0.00 |
Minimum of Months | 1605.19 | 371.09 | 1489.80 | 303.33 | 438.68 | 0.00 | 0.00 |
Maximum of Months | 2699.16 | 2183.42 | 2362.53 | 1596.14 | 1186.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 235.90 | 1701.09 | 502.30 | 203.24 | 299.07 | 0.00 | 0.00 |
February | 491.18 | 1362.77 | 736.54 | 362.94 | 373.60 | 0.00 | 0.00 |
March | 688.80 | 886.57 | 879.27 | 327.14 | 552.14 | 0.00 | 0.00 |
April | 1330.24 | 638.63 | 1282.60 | 634.22 | 648.38 | 0.00 | 0.00 |
May | 1461.36 | 395.98 | 1286.31 | 513.85 | 772.46 | 0.00 | 0.00 |
June | 1884.38 | 286.38 | 1509.33 | 654.10 | 855.23 | 0.00 | 0.00 |
July | 2071.30 | 263.39 | 1620.56 | 769.79 | 850.77 | 0.00 | 0.00 |
August | 1817.99 | 307.47 | 1416.78 | 650.21 | 766.57 | 0.00 | 0.00 |
September | 1342.88 | 506.31 | 1146.84 | 544.35 | 602.49 | 0.00 | 0.00 |
October | 742.37 | 744.66 | 799.17 | 355.30 | 443.87 | 0.00 | 0.00 |
November | 296.78 | 1088.96 | 478.35 | 176.89 | 301.46 | 0.00 | 0.00 |
December | 203.10 | 1554.84 | 367.88 | 173.42 | 194.46 | 0.00 | 0.00 |
Annual Sum or Average | 1049.93 | 808.88 | 1003.23 | 447.21 | 556.02 | 0.00 | 0.00 |
Minimum of Months | 203.10 | 263.39 | 367.88 | 173.42 | 194.46 | 0.00 | 0.00 |
Maximum of Months | 2071.30 | 1701.09 | 1620.56 | 769.79 | 855.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.72 | 2792.71 | 354.55 | 0.00 | 354.55 | 0.00 | 0.00 |
February | 28.80 | 2249.98 | 449.50 | 0.00 | 449.50 | 0.00 | 0.00 |
March | 218.04 | 1439.03 | 673.66 | 0.00 | 673.66 | 0.00 | 0.00 |
April | 437.97 | 998.10 | 777.69 | 3.83 | 773.86 | 0.00 | 0.00 |
May | 884.91 | 588.98 | 1014.13 | 38.12 | 976.01 | 0.00 | 0.00 |
June | 1334.29 | 408.88 | 1185.28 | 107.58 | 1077.70 | 0.00 | 0.00 |
July | 1307.33 | 357.35 | 1111.61 | 74.35 | 1037.25 | 0.00 | 0.00 |
August | 1087.57 | 420.77 | 930.74 | 16.50 | 914.25 | 0.00 | 0.00 |
September | 655.13 | 732.20 | 713.61 | 0.18 | 713.44 | 0.00 | 0.00 |
October | 250.11 | 1101.10 | 530.58 | 0.00 | 530.58 | 0.00 | 0.00 |
November | 60.50 | 1690.35 | 371.15 | 0.00 | 371.15 | 0.00 | 0.00 |
December | 0.23 | 2470.33 | 240.75 | 0.00 | 240.75 | 0.00 | 0.00 |
Annual Sum or Average | 525.18 | 1266.20 | 697.41 | 20.13 | 677.28 | 0.00 | 0.00 |
Minimum of Months | 0.23 | 357.35 | 240.75 | 0.00 | 240.75 | 0.00 | 0.00 |
Maximum of Months | 1334.29 | 2792.71 | 1185.28 | 107.58 | 1077.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 220.19 | 1680.59 | 506.48 | 208.42 | 298.06 | 0.00 | 0.00 |
February | 386.20 | 1333.24 | 671.34 | 295.20 | 376.14 | 0.00 | 0.00 |
March | 700.00 | 882.06 | 912.14 | 362.06 | 550.09 | 0.00 | 0.00 |
April | 1065.66 | 638.31 | 1120.03 | 490.49 | 629.53 | 0.00 | 0.00 |
May | 1554.99 | 393.95 | 1406.66 | 614.65 | 792.02 | 0.00 | 0.00 |
June | 1901.64 | 273.22 | 1547.99 | 674.13 | 873.87 | 0.00 | 0.00 |
July | 1967.74 | 238.54 | 1564.63 | 721.95 | 842.67 | 0.00 | 0.00 |
August | 1661.22 | 278.73 | 1318.95 | 568.63 | 750.32 | 0.00 | 0.00 |
September | 1368.14 | 467.45 | 1176.38 | 555.90 | 620.48 | 0.00 | 0.00 |
October | 661.09 | 686.82 | 749.67 | 313.13 | 436.54 | 0.00 | 0.00 |
November | 233.63 | 1045.84 | 442.31 | 143.67 | 298.64 | 0.00 | 0.00 |
December | 153.00 | 1522.96 | 342.62 | 147.13 | 195.49 | 0.00 | 0.00 |
Annual Sum or Average | 992.74 | 784.30 | 981.47 | 425.22 | 556.24 | 0.00 | 0.00 |
Minimum of Months | 153.00 | 238.54 | 342.62 | 143.67 | 195.49 | 0.00 | 0.00 |
Maximum of Months | 1967.74 | 1680.59 | 1564.63 | 721.95 | 873.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1938.17 | 2286.52 | 2204.89 | 1508.85 | 696.04 | 0.00 | 0.00 |
February | 2162.91 | 1852.58 | 2362.50 | 1596.12 | 766.38 | 0.00 | 0.00 |
March | 1976.29 | 1348.36 | 2055.91 | 1082.57 | 973.34 | 0.00 | 0.00 |
April | 1981.44 | 1019.93 | 1852.24 | 865.96 | 986.28 | 0.00 | 0.00 |
May | 1738.35 | 642.85 | 1534.52 | 416.03 | 1118.49 | 0.00 | 0.00 |
June | 1877.72 | 439.49 | 1489.78 | 303.33 | 1186.46 | 0.00 | 0.00 |
July | 2075.69 | 381.96 | 1577.04 | 397.37 | 1179.67 | 0.00 | 0.00 |
August | 2374.65 | 451.62 | 1776.80 | 637.20 | 1139.60 | 0.00 | 0.00 |
September | 2682.70 | 742.52 | 2153.11 | 1134.51 | 1018.60 | 0.00 | 0.00 |
October | 2456.43 | 1064.24 | 2248.29 | 1410.49 | 837.81 | 0.00 | 0.00 |
November | 1577.64 | 1508.95 | 1696.33 | 1061.94 | 634.40 | 0.00 | 0.00 |
December | 1703.74 | 2132.21 | 1808.89 | 1370.21 | 438.68 | 0.00 | 0.00 |
Annual Sum or Average | 2044.68 | 1152.71 | 1893.95 | 978.54 | 915.41 | 0.00 | 0.00 |
Minimum of Months | 1577.64 | 381.96 | 1489.78 | 303.33 | 438.68 | 0.00 | 0.00 |
Maximum of Months | 2682.70 | 2286.52 | 2362.50 | 1596.12 | 1186.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 229.25 | 1721.98 | 502.31 | 203.24 | 299.07 | 0.00 | 0.00 |
February | 478.83 | 1383.49 | 736.54 | 362.95 | 373.60 | 0.00 | 0.00 |
March | 664.92 | 913.05 | 879.28 | 327.14 | 552.14 | 0.00 | 0.00 |
April | 1300.93 | 667.14 | 1282.61 | 634.23 | 648.38 | 0.00 | 0.00 |
May | 1430.16 | 418.51 | 1286.32 | 513.85 | 772.47 | 0.00 | 0.00 |
June | 1866.43 | 294.96 | 1509.34 | 654.11 | 855.23 | 0.00 | 0.00 |
July | 2060.80 | 262.64 | 1620.58 | 769.80 | 850.78 | 0.00 | 0.00 |
August | 1811.57 | 301.68 | 1416.79 | 650.21 | 766.58 | 0.00 | 0.00 |
September | 1341.70 | 490.53 | 1146.85 | 544.35 | 602.50 | 0.00 | 0.00 |
October | 742.64 | 719.87 | 799.17 | 355.30 | 443.87 | 0.00 | 0.00 |
November | 295.75 | 1071.38 | 478.36 | 176.90 | 301.46 | 0.00 | 0.00 |
December | 199.50 | 1556.03 | 367.88 | 173.42 | 194.46 | 0.00 | 0.00 |
Annual Sum or Average | 1037.96 | 814.15 | 1003.23 | 447.21 | 556.02 | 0.00 | 0.00 |
Minimum of Months | 199.50 | 262.64 | 367.88 | 173.42 | 194.46 | 0.00 | 0.00 |
Maximum of Months | 2060.80 | 1721.98 | 1620.58 | 769.80 | 855.23 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5476430.84 | 0.735710E+10 | 0.949622E+09 | 0.00 | 0.949622E+09 | 0.00 | 0.00 |
February | 76858189.38 | 0.529665E+10 | 0.108742E+10 | 0.00 | 0.108742E+10 | 0.00 | 0.00 |
March | 0.609292E+09 | 0.368977E+10 | 0.180433E+10 | 0.00 | 0.180433E+10 | 0.00 | 0.00 |
April | 0.116304E+10 | 0.243613E+10 | 0.201578E+10 | 9931654.83 | 0.200585E+10 | 0.00 | 0.00 |
May | 0.240780E+10 | 0.149665E+10 | 0.271624E+10 | 0.102097E+09 | 0.261414E+10 | 0.00 | 0.00 |
June | 0.347266E+10 | 0.101301E+10 | 0.307225E+10 | 0.278847E+09 | 0.279340E+10 | 0.00 | 0.00 |
July | 0.350629E+10 | 0.924092E+09 | 0.297733E+10 | 0.199151E+09 | 0.277818E+10 | 0.00 | 0.00 |
August | 0.292589E+10 | 0.107790E+10 | 0.249290E+10 | 44181142.49 | 0.244872E+10 | 0.00 | 0.00 |
September | 0.173621E+10 | 0.177392E+10 | 0.184968E+10 | 458638.62 | 0.184922E+10 | 0.00 | 0.00 |
October | 0.732706E+09 | 0.272245E+10 | 0.142112E+10 | 0.00 | 0.142112E+10 | 0.00 | 0.00 |
November | 0.182738E+09 | 0.416992E+10 | 0.962018E+09 | 0.00 | 0.962018E+09 | 0.00 | 0.00 |
December | 2178288.33 | 0.644044E+10 | 0.644823E+09 | 0.00 | 0.644823E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.168211E+11 | 0.383980E+11 | 0.219935E+11 | 0.634666E+09 | 0.213588E+11 | 0.00 | 0.00 |
Minimum of Months | 2178288.33 | 0.924092E+09 | 0.644823E+09 | 0.00 | 0.644823E+09 | 0.00 | 0.00 |
Maximum of Months | 0.350629E+10 | 0.735710E+10 | 0.307225E+10 | 0.278847E+09 | 0.279340E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.595624E+09 | 0.442543E+10 | 0.135656E+10 | 0.558227E+09 | 0.798332E+09 | 0.00 | 0.00 |
February | 0.947192E+09 | 0.313406E+10 | 0.162410E+10 | 0.714148E+09 | 0.909953E+09 | 0.00 | 0.00 |
March | 0.189940E+10 | 0.226176E+10 | 0.244309E+10 | 0.969731E+09 | 0.147335E+10 | 0.00 | 0.00 |
April | 0.277961E+10 | 0.156781E+10 | 0.290310E+10 | 0.127136E+10 | 0.163175E+10 | 0.00 | 0.00 |
May | 0.417721E+10 | 0.100899E+10 | 0.376760E+10 | 0.164627E+10 | 0.212134E+10 | 0.00 | 0.00 |
June | 0.493128E+10 | 0.679593E+09 | 0.401240E+10 | 0.174733E+10 | 0.226507E+10 | 0.00 | 0.00 |
July | 0.526603E+10 | 0.619361E+09 | 0.419069E+10 | 0.193368E+10 | 0.225702E+10 | 0.00 | 0.00 |
August | 0.445126E+10 | 0.717982E+09 | 0.353267E+10 | 0.152301E+10 | 0.200966E+10 | 0.00 | 0.00 |
September | 0.356484E+10 | 0.114368E+10 | 0.304919E+10 | 0.144090E+10 | 0.160829E+10 | 0.00 | 0.00 |
October | 0.182066E+10 | 0.170871E+10 | 0.200792E+10 | 0.838692E+09 | 0.116923E+10 | 0.00 | 0.00 |
November | 0.632003E+09 | 0.258437E+10 | 0.114648E+10 | 0.372396E+09 | 0.774081E+09 | 0.00 | 0.00 |
December | 0.418053E+09 | 0.396853E+10 | 0.917674E+09 | 0.394071E+09 | 0.523603E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.314832E+11 | 0.238203E+11 | 0.309515E+11 | 0.134098E+11 | 0.175417E+11 | 0.00 | 0.00 |
Minimum of Months | 0.418053E+09 | 0.619361E+09 | 0.917674E+09 | 0.372396E+09 | 0.523603E+09 | 0.00 | 0.00 |
Maximum of Months | 0.526603E+10 | 0.442543E+10 | 0.419069E+10 | 0.193368E+10 | 0.226507E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.521255E+10 | 0.599953E+10 | 0.590558E+10 | 0.404132E+10 | 0.186427E+10 | 0.00 | 0.00 |
February | 0.526350E+10 | 0.433307E+10 | 0.571537E+10 | 0.386134E+10 | 0.185402E+10 | 0.00 | 0.00 |
March | 0.532691E+10 | 0.344944E+10 | 0.550655E+10 | 0.289956E+10 | 0.260699E+10 | 0.00 | 0.00 |
April | 0.515716E+10 | 0.249658E+10 | 0.480100E+10 | 0.224456E+10 | 0.255645E+10 | 0.00 | 0.00 |
May | 0.467435E+10 | 0.163514E+10 | 0.411005E+10 | 0.111429E+10 | 0.299577E+10 | 0.00 | 0.00 |
June | 0.487252E+10 | 0.108522E+10 | 0.386152E+10 | 0.786225E+09 | 0.307530E+10 | 0.00 | 0.00 |
July | 0.555670E+10 | 0.985606E+09 | 0.422395E+10 | 0.106432E+10 | 0.315963E+10 | 0.00 | 0.00 |
August | 0.636082E+10 | 0.115696E+10 | 0.475899E+10 | 0.170668E+10 | 0.305230E+10 | 0.00 | 0.00 |
September | 0.697881E+10 | 0.181041E+10 | 0.558085E+10 | 0.294064E+10 | 0.264021E+10 | 0.00 | 0.00 |
October | 0.664532E+10 | 0.264186E+10 | 0.602183E+10 | 0.377785E+10 | 0.224398E+10 | 0.00 | 0.00 |
November | 0.414453E+10 | 0.371290E+10 | 0.439690E+10 | 0.275254E+10 | 0.164436E+10 | 0.00 | 0.00 |
December | 0.459239E+10 | 0.553441E+10 | 0.484494E+10 | 0.366998E+10 | 0.117496E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.647856E+11 | 0.348411E+11 | 0.597275E+11 | 0.308593E+11 | 0.288682E+11 | 0.00 | 0.00 |
Minimum of Months | 0.414453E+10 | 0.985606E+09 | 0.386152E+10 | 0.786225E+09 | 0.117496E+10 | 0.00 | 0.00 |
Maximum of Months | 0.697881E+10 | 0.599953E+10 | 0.602183E+10 | 0.404132E+10 | 0.315963E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.616199E+09 | 0.453403E+10 | 0.134538E+10 | 0.544355E+09 | 0.801022E+09 | 0.00 | 0.00 |
February | 0.116597E+10 | 0.325332E+10 | 0.178185E+10 | 0.878038E+09 | 0.903807E+09 | 0.00 | 0.00 |
March | 0.179712E+10 | 0.233935E+10 | 0.235507E+10 | 0.876212E+09 | 0.147885E+10 | 0.00 | 0.00 |
April | 0.338453E+10 | 0.163402E+10 | 0.332452E+10 | 0.164391E+10 | 0.168061E+10 | 0.00 | 0.00 |
May | 0.384669E+10 | 0.106420E+10 | 0.344528E+10 | 0.137630E+10 | 0.206897E+10 | 0.00 | 0.00 |
June | 0.484190E+10 | 0.730199E+09 | 0.391222E+10 | 0.169546E+10 | 0.221676E+10 | 0.00 | 0.00 |
July | 0.551829E+10 | 0.679064E+09 | 0.434055E+10 | 0.206183E+10 | 0.227872E+10 | 0.00 | 0.00 |
August | 0.485575E+10 | 0.773836E+09 | 0.379473E+10 | 0.174153E+10 | 0.205320E+10 | 0.00 | 0.00 |
September | 0.349947E+10 | 0.119562E+10 | 0.297264E+10 | 0.141097E+10 | 0.156168E+10 | 0.00 | 0.00 |
October | 0.202731E+10 | 0.178724E+10 | 0.214051E+10 | 0.951644E+09 | 0.118886E+10 | 0.00 | 0.00 |
November | 0.788484E+09 | 0.264711E+10 | 0.123990E+10 | 0.458515E+09 | 0.781390E+09 | 0.00 | 0.00 |
December | 0.540202E+09 | 0.405578E+10 | 0.985336E+09 | 0.464501E+09 | 0.520835E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.328819E+11 | 0.246938E+11 | 0.316380E+11 | 0.141033E+11 | 0.175347E+11 | 0.00 | 0.00 |
Minimum of Months | 0.540202E+09 | 0.679064E+09 | 0.985336E+09 | 0.458515E+09 | 0.520835E+09 | 0.00 | 0.00 |
Maximum of Months | 0.551829E+10 | 0.453403E+10 | 0.434055E+10 | 0.206183E+10 | 0.227872E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5934875.32 | 0.736496E+10 | 0.949617E+09 | 0.00 | 0.949617E+09 | 0.00 | 0.00 |
February | 78064734.21 | 0.532402E+10 | 0.108742E+10 | 0.00 | 0.108742E+10 | 0.00 | 0.00 |
March | 0.650085E+09 | 0.370834E+10 | 0.180432E+10 | 0.00 | 0.180432E+10 | 0.00 | 0.00 |
April | 0.124983E+10 | 0.239857E+10 | 0.201577E+10 | 9931603.37 | 0.200584E+10 | 0.00 | 0.00 |
May | 0.254445E+10 | 0.142948E+10 | 0.271622E+10 | 0.102096E+09 | 0.261412E+10 | 0.00 | 0.00 |
June | 0.355616E+10 | 0.990163E+09 | 0.307223E+10 | 0.278845E+09 | 0.279339E+10 | 0.00 | 0.00 |
July | 0.357117E+10 | 0.910889E+09 | 0.297732E+10 | 0.199150E+09 | 0.277817E+10 | 0.00 | 0.00 |
August | 0.294945E+10 | 0.110229E+10 | 0.249289E+10 | 44180913.56 | 0.244871E+10 | 0.00 | 0.00 |
September | 0.171630E+10 | 0.190183E+10 | 0.184967E+10 | 458636.24 | 0.184921E+10 | 0.00 | 0.00 |
October | 0.674966E+09 | 0.299160E+10 | 0.142111E+10 | 0.00 | 0.142111E+10 | 0.00 | 0.00 |
November | 0.159272E+09 | 0.442596E+10 | 0.962013E+09 | 0.00 | 0.962013E+09 | 0.00 | 0.00 |
December | 740331.55 | 0.659584E+10 | 0.644820E+09 | 0.00 | 0.644820E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.171564E+11 | 0.391439E+11 | 0.219934E+11 | 0.634663E+09 | 0.213587E+11 | 0.00 | 0.00 |
Minimum of Months | 740331.55 | 0.910889E+09 | 0.644820E+09 | 0.00 | 0.644820E+09 | 0.00 | 0.00 |
Maximum of Months | 0.357117E+10 | 0.736496E+10 | 0.307223E+10 | 0.278845E+09 | 0.279339E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.604752E+09 | 0.445102E+10 | 0.135655E+10 | 0.558221E+09 | 0.798327E+09 | 0.00 | 0.00 |
February | 0.957703E+09 | 0.318081E+10 | 0.162409E+10 | 0.714141E+09 | 0.909947E+09 | 0.00 | 0.00 |
March | 0.193729E+10 | 0.229785E+10 | 0.244307E+10 | 0.969721E+09 | 0.147335E+10 | 0.00 | 0.00 |
April | 0.284126E+10 | 0.157585E+10 | 0.290308E+10 | 0.127135E+10 | 0.163174E+10 | 0.00 | 0.00 |
May | 0.424375E+10 | 0.100972E+10 | 0.376757E+10 | 0.164625E+10 | 0.212132E+10 | 0.00 | 0.00 |
June | 0.497678E+10 | 0.692114E+09 | 0.401237E+10 | 0.174732E+10 | 0.226505E+10 | 0.00 | 0.00 |
July | 0.530221E+10 | 0.637966E+09 | 0.419066E+10 | 0.193366E+10 | 0.225700E+10 | 0.00 | 0.00 |
August | 0.446816E+10 | 0.758236E+09 | 0.353265E+10 | 0.152299E+10 | 0.200965E+10 | 0.00 | 0.00 |
September | 0.355000E+10 | 0.125769E+10 | 0.304916E+10 | 0.144088E+10 | 0.160828E+10 | 0.00 | 0.00 |
October | 0.176162E+10 | 0.191187E+10 | 0.200791E+10 | 0.838684E+09 | 0.116922E+10 | 0.00 | 0.00 |
November | 0.604765E+09 | 0.275656E+10 | 0.114647E+10 | 0.372393E+09 | 0.774076E+09 | 0.00 | 0.00 |
December | 0.415325E+09 | 0.407695E+10 | 0.917667E+09 | 0.394067E+09 | 0.523600E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.316636E+11 | 0.246066E+11 | 0.309512E+11 | 0.134097E+11 | 0.175416E+11 | 0.00 | 0.00 |
Minimum of Months | 0.415325E+09 | 0.637966E+09 | 0.917667E+09 | 0.372393E+09 | 0.523600E+09 | 0.00 | 0.00 |
Maximum of Months | 0.530221E+10 | 0.445102E+10 | 0.419066E+10 | 0.193366E+10 | 0.226505E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.538610E+10 | 0.584808E+10 | 0.590565E+10 | 0.404136E+10 | 0.186428E+10 | 0.00 | 0.00 |
February | 0.541714E+10 | 0.433475E+10 | 0.571543E+10 | 0.386139E+10 | 0.185404E+10 | 0.00 | 0.00 |
March | 0.548060E+10 | 0.345287E+10 | 0.550660E+10 | 0.289959E+10 | 0.260701E+10 | 0.00 | 0.00 |
April | 0.529698E+10 | 0.247827E+10 | 0.480105E+10 | 0.224458E+10 | 0.255646E+10 | 0.00 | 0.00 |
May | 0.483482E+10 | 0.158314E+10 | 0.411009E+10 | 0.111430E+10 | 0.299579E+10 | 0.00 | 0.00 |
June | 0.497473E+10 | 0.106616E+10 | 0.386155E+10 | 0.786234E+09 | 0.307532E+10 | 0.00 | 0.00 |
July | 0.562661E+10 | 0.993935E+09 | 0.422398E+10 | 0.106433E+10 | 0.315965E+10 | 0.00 | 0.00 |
August | 0.640442E+10 | 0.121883E+10 | 0.475903E+10 | 0.170670E+10 | 0.305232E+10 | 0.00 | 0.00 |
September | 0.699623E+10 | 0.197615E+10 | 0.558090E+10 | 0.294068E+10 | 0.264023E+10 | 0.00 | 0.00 |
October | 0.664059E+10 | 0.296044E+10 | 0.602189E+10 | 0.377789E+10 | 0.224400E+10 | 0.00 | 0.00 |
November | 0.416065E+10 | 0.393179E+10 | 0.439694E+10 | 0.275257E+10 | 0.164437E+10 | 0.00 | 0.00 |
December | 0.466638E+10 | 0.556370E+10 | 0.484499E+10 | 0.367002E+10 | 0.117497E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.658852E+11 | 0.354081E+11 | 0.597281E+11 | 0.308597E+11 | 0.288684E+11 | 0.00 | 0.00 |
Minimum of Months | 0.416065E+10 | 0.993935E+09 | 0.386155E+10 | 0.786234E+09 | 0.117497E+10 | 0.00 | 0.00 |
Maximum of Months | 0.699623E+10 | 0.584808E+10 | 0.602189E+10 | 0.404136E+10 | 0.315965E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.631824E+09 | 0.455620E+10 | 0.134537E+10 | 0.544350E+09 | 0.801017E+09 | 0.00 | 0.00 |
February | 0.118826E+10 | 0.329682E+10 | 0.178183E+10 | 0.878029E+09 | 0.903801E+09 | 0.00 | 0.00 |
March | 0.184487E+10 | 0.237459E+10 | 0.235505E+10 | 0.876203E+09 | 0.147884E+10 | 0.00 | 0.00 |
April | 0.344798E+10 | 0.165534E+10 | 0.332450E+10 | 0.164390E+10 | 0.168060E+10 | 0.00 | 0.00 |
May | 0.391410E+10 | 0.106059E+10 | 0.344525E+10 | 0.137629E+10 | 0.206896E+10 | 0.00 | 0.00 |
June | 0.488432E+10 | 0.742284E+09 | 0.391219E+10 | 0.169544E+10 | 0.221675E+10 | 0.00 | 0.00 |
July | 0.554776E+10 | 0.705451E+09 | 0.434052E+10 | 0.206180E+10 | 0.227871E+10 | 0.00 | 0.00 |
August | 0.486929E+10 | 0.823526E+09 | 0.379470E+10 | 0.174151E+10 | 0.205319E+10 | 0.00 | 0.00 |
September | 0.348074E+10 | 0.131235E+10 | 0.297262E+10 | 0.141095E+10 | 0.156167E+10 | 0.00 | 0.00 |
October | 0.198835E+10 | 0.199450E+10 | 0.214049E+10 | 0.951634E+09 | 0.118886E+10 | 0.00 | 0.00 |
November | 0.769251E+09 | 0.282259E+10 | 0.123989E+10 | 0.458510E+09 | 0.781385E+09 | 0.00 | 0.00 |
December | 0.543982E+09 | 0.416448E+10 | 0.985328E+09 | 0.464496E+09 | 0.520832E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.331107E+11 | 0.255087E+11 | 0.316377E+11 | 0.141031E+11 | 0.175346E+11 | 0.00 | 0.00 |
Minimum of Months | 0.543982E+09 | 0.705451E+09 | 0.985328E+09 | 0.458510E+09 | 0.520832E+09 | 0.00 | 0.00 |
Maximum of Months | 0.554776E+10 | 0.455620E+10 | 0.434052E+10 | 0.206180E+10 | 0.227871E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 4603378.60 | 0.747999E+10 | 0.949622E+09 | 0.00 | 0.949622E+09 | 0.00 | 0.00 |
February | 69676662.04 | 0.544316E+10 | 0.108742E+10 | 0.00 | 0.108742E+10 | 0.00 | 0.00 |
March | 0.583990E+09 | 0.385429E+10 | 0.180433E+10 | 0.00 | 0.180433E+10 | 0.00 | 0.00 |
April | 0.113522E+10 | 0.258706E+10 | 0.201578E+10 | 9931654.83 | 0.200585E+10 | 0.00 | 0.00 |
May | 0.237014E+10 | 0.157752E+10 | 0.271624E+10 | 0.102097E+09 | 0.261414E+10 | 0.00 | 0.00 |
June | 0.345847E+10 | 0.105983E+10 | 0.307225E+10 | 0.278847E+09 | 0.279340E+10 | 0.00 | 0.00 |
July | 0.350154E+10 | 0.957134E+09 | 0.297733E+10 | 0.199151E+09 | 0.277818E+10 | 0.00 | 0.00 |
August | 0.291295E+10 | 0.112700E+10 | 0.249290E+10 | 44181142.49 | 0.244872E+10 | 0.00 | 0.00 |
September | 0.169810E+10 | 0.189786E+10 | 0.184968E+10 | 458638.62 | 0.184922E+10 | 0.00 | 0.00 |
October | 0.669898E+09 | 0.294918E+10 | 0.142112E+10 | 0.00 | 0.142112E+10 | 0.00 | 0.00 |
November | 0.156813E+09 | 0.438139E+10 | 0.962018E+09 | 0.00 | 0.962018E+09 | 0.00 | 0.00 |
December | 609098.35 | 0.661654E+10 | 0.644823E+09 | 0.00 | 0.644823E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.165620E+11 | 0.399310E+11 | 0.219935E+11 | 0.634666E+09 | 0.213588E+11 | 0.00 | 0.00 |
Minimum of Months | 609098.35 | 0.957134E+09 | 0.644823E+09 | 0.00 | 0.644823E+09 | 0.00 | 0.00 |
Maximum of Months | 0.350154E+10 | 0.747999E+10 | 0.307225E+10 | 0.278847E+09 | 0.279340E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.589750E+09 | 0.450129E+10 | 0.135656E+10 | 0.558227E+09 | 0.798332E+09 | 0.00 | 0.00 |
February | 0.934297E+09 | 0.322537E+10 | 0.162410E+10 | 0.714148E+09 | 0.909953E+09 | 0.00 | 0.00 |
March | 0.187487E+10 | 0.236251E+10 | 0.244309E+10 | 0.969731E+09 | 0.147335E+10 | 0.00 | 0.00 |
April | 0.276219E+10 | 0.165449E+10 | 0.290310E+10 | 0.127136E+10 | 0.163175E+10 | 0.00 | 0.00 |
May | 0.416488E+10 | 0.105514E+10 | 0.376760E+10 | 0.164627E+10 | 0.212134E+10 | 0.00 | 0.00 |
June | 0.492905E+10 | 0.708191E+09 | 0.401240E+10 | 0.174733E+10 | 0.226507E+10 | 0.00 | 0.00 |
July | 0.527041E+10 | 0.638900E+09 | 0.419069E+10 | 0.193368E+10 | 0.225702E+10 | 0.00 | 0.00 |
August | 0.444940E+10 | 0.746560E+09 | 0.353267E+10 | 0.152301E+10 | 0.200966E+10 | 0.00 | 0.00 |
September | 0.354623E+10 | 0.121162E+10 | 0.304919E+10 | 0.144090E+10 | 0.160829E+10 | 0.00 | 0.00 |
October | 0.177065E+10 | 0.183957E+10 | 0.200792E+10 | 0.838692E+09 | 0.116923E+10 | 0.00 | 0.00 |
November | 0.605564E+09 | 0.271083E+10 | 0.114648E+10 | 0.372396E+09 | 0.774081E+09 | 0.00 | 0.00 |
December | 0.409791E+09 | 0.407908E+10 | 0.917674E+09 | 0.394071E+09 | 0.523603E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.313071E+11 | 0.247336E+11 | 0.309515E+11 | 0.134098E+11 | 0.175417E+11 | 0.00 | 0.00 |
Minimum of Months | 0.409791E+09 | 0.638900E+09 | 0.917674E+09 | 0.372396E+09 | 0.523603E+09 | 0.00 | 0.00 |
Maximum of Months | 0.527041E+10 | 0.450129E+10 | 0.419069E+10 | 0.193368E+10 | 0.226507E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.519120E+10 | 0.612421E+10 | 0.590558E+10 | 0.404132E+10 | 0.186427E+10 | 0.00 | 0.00 |
February | 0.523250E+10 | 0.448177E+10 | 0.571537E+10 | 0.386134E+10 | 0.185402E+10 | 0.00 | 0.00 |
March | 0.529329E+10 | 0.361144E+10 | 0.550655E+10 | 0.289956E+10 | 0.260699E+10 | 0.00 | 0.00 |
April | 0.513590E+10 | 0.264366E+10 | 0.480100E+10 | 0.224456E+10 | 0.255645E+10 | 0.00 | 0.00 |
May | 0.465601E+10 | 0.172180E+10 | 0.411005E+10 | 0.111429E+10 | 0.299577E+10 | 0.00 | 0.00 |
June | 0.486705E+10 | 0.113915E+10 | 0.386152E+10 | 0.786225E+09 | 0.307530E+10 | 0.00 | 0.00 |
July | 0.555953E+10 | 0.102304E+10 | 0.422395E+10 | 0.106432E+10 | 0.315963E+10 | 0.00 | 0.00 |
August | 0.636026E+10 | 0.120962E+10 | 0.475899E+10 | 0.170668E+10 | 0.305230E+10 | 0.00 | 0.00 |
September | 0.695356E+10 | 0.192462E+10 | 0.558085E+10 | 0.294064E+10 | 0.264021E+10 | 0.00 | 0.00 |
October | 0.657931E+10 | 0.285046E+10 | 0.602183E+10 | 0.377785E+10 | 0.224398E+10 | 0.00 | 0.00 |
November | 0.408924E+10 | 0.391120E+10 | 0.439690E+10 | 0.275254E+10 | 0.164436E+10 | 0.00 | 0.00 |
December | 0.456330E+10 | 0.571092E+10 | 0.484494E+10 | 0.366998E+10 | 0.117496E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.644811E+11 | 0.363519E+11 | 0.597275E+11 | 0.308593E+11 | 0.288682E+11 | 0.00 | 0.00 |
Minimum of Months | 0.408924E+10 | 0.102304E+10 | 0.386152E+10 | 0.786225E+09 | 0.117496E+10 | 0.00 | 0.00 |
Maximum of Months | 0.695356E+10 | 0.612421E+10 | 0.602183E+10 | 0.404132E+10 | 0.315963E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.614028E+09 | 0.461215E+10 | 0.134538E+10 | 0.544355E+09 | 0.801022E+09 | 0.00 | 0.00 |
February | 0.115837E+10 | 0.334694E+10 | 0.178185E+10 | 0.878038E+09 | 0.903807E+09 | 0.00 | 0.00 |
March | 0.178093E+10 | 0.244552E+10 | 0.235507E+10 | 0.876212E+09 | 0.147885E+10 | 0.00 | 0.00 |
April | 0.337201E+10 | 0.172922E+10 | 0.332452E+10 | 0.164391E+10 | 0.168061E+10 | 0.00 | 0.00 |
May | 0.383055E+10 | 0.112092E+10 | 0.344528E+10 | 0.137630E+10 | 0.206897E+10 | 0.00 | 0.00 |
June | 0.483779E+10 | 0.764547E+09 | 0.391222E+10 | 0.169546E+10 | 0.221676E+10 | 0.00 | 0.00 |
July | 0.551965E+10 | 0.703455E+09 | 0.434055E+10 | 0.206183E+10 | 0.227872E+10 | 0.00 | 0.00 |
August | 0.485211E+10 | 0.808007E+09 | 0.379473E+10 | 0.174153E+10 | 0.205320E+10 | 0.00 | 0.00 |
September | 0.347769E+10 | 0.127145E+10 | 0.297264E+10 | 0.141097E+10 | 0.156168E+10 | 0.00 | 0.00 |
October | 0.198908E+10 | 0.192811E+10 | 0.214051E+10 | 0.951644E+09 | 0.118886E+10 | 0.00 | 0.00 |
November | 0.766573E+09 | 0.277702E+10 | 0.123990E+10 | 0.458515E+09 | 0.781390E+09 | 0.00 | 0.00 |
December | 0.534330E+09 | 0.416766E+10 | 0.985336E+09 | 0.464501E+09 | 0.520835E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.327331E+11 | 0.256750E+11 | 0.316380E+11 | 0.141033E+11 | 0.175347E+11 | 0.00 | 0.00 |
Minimum of Months | 0.534330E+09 | 0.703455E+09 | 0.985336E+09 | 0.458515E+09 | 0.520835E+09 | 0.00 | 0.00 |
Maximum of Months | 0.551965E+10 | 0.461215E+10 | 0.434055E+10 | 0.206183E+10 | 0.227872E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.593752E+10 | -0.517005E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -767477144.2 | 58.99 | 0.00 | 0.00 |
February | 0.546902E+10 | -0.479336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -675661473.5 | 58.98 | 0.00 | 0.00 |
March | 0.634363E+10 | -0.561757E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -726065485.5 | 58.99 | 0.00 | 0.00 |
April | 0.554769E+10 | -0.486066E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -687035899.3 | 58.98 | 0.00 | 0.00 |
May | 0.560035E+10 | -0.490720E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -693149253.3 | 58.99 | 0.00 | 0.00 |
June | 0.521354E+10 | -0.454472E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668814753.0 | 58.98 | 0.00 | 0.00 |
July | 0.472792E+10 | -0.403988E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688034484.5 | 58.98 | 0.00 | 0.00 |
August | 0.503974E+10 | -0.435041E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689329626.6 | 58.98 | 0.00 | 0.00 |
September | 0.463843E+10 | -0.397021E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668218688.9 | 58.98 | 0.00 | 0.00 |
October | 0.500933E+10 | -0.430723E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -702103030.0 | 58.99 | 0.00 | 0.00 |
November | 0.522994E+10 | -0.452982E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -700114206.5 | 58.98 | 0.00 | 0.00 |
December | 0.553440E+10 | -0.478532E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -749080341.7 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.642915E+11 | -0.558764E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.841508E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.463843E+10 | -0.561757E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -767477144.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.634363E+10 | -0.397021E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -668218688.9 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.63 | 0.62 | 01-JAN-09:39 | 6687.30 | 36.99 | 205.17 | 240.33 | 5558.63 | 37.99 | 202.17 | 218.33 |
February | 226.83 | 0.63 | 0.62 | 01-FEB-07:49 | 7968.16 | 37.24 | 222.33 | 253.33 | 2270.95 | 28.64 | 180.00 | 234.33 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:40 | 7279.81 | 29.91 | 261.50 | 323.67 | 1336.51 | 21.21 | 183.00 | 287.17 |
April | 285.17 | 0.63 | 0.62 | 01-APR-06:40 | 2098.73 | 18.08 | 0.00 | 342.33 | 1250.45 | 20.86 | 142.33 | 291.33 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-05:00 | 1622.07 | 17.66 | 0.00 | 389.00 | 904.18 | 20.42 | 166.17 | 341.83 |
June | 400.67 | 0.64 | 0.62 | 01-JUN-05:19 | 1649.24 | 17.89 | 0.00 | 390.00 | 934.35 | 20.67 | 184.50 | 345.83 |
July | 414.00 | 0.63 | 0.62 | 01-JUL-05:40 | 1711.61 | 18.20 | 0.00 | 401.33 | 979.35 | 20.98 | 202.67 | 355.83 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:00 | 1905.05 | 18.12 | 0.00 | 373.83 | 1068.11 | 20.88 | 213.50 | 337.00 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-06:10 | 2792.20 | 19.94 | 26.00 | 328.67 | 1357.23 | 21.41 | 186.33 | 297.00 |
October | 325.17 | 0.63 | 0.62 | 01-OCT-06:40 | 6861.56 | 32.86 | 292.00 | 301.83 | 1793.21 | 22.66 | 179.33 | 279.83 |
November | 254.83 | 0.63 | 0.62 | 01-NOV-07:40 | 4771.68 | 32.30 | 231.33 | 244.67 | 2589.89 | 30.66 | 221.50 | 221.83 |
December | 186.17 | 0.63 | 0.62 | 01-DEC-07:00 | 5814.22 | 35.63 | 167.50 | 215.33 | 5367.23 | 38.59 | 177.33 | 175.33 |
Annual Sum or Average | 3807.33 | 0.63 | 3824.36 | 24.51 | 1405.83 | 3804.33 | 1786.20 | 23.99 | 2238.83 | 3385.67 | ||
Minimum of Months | 186.17 | 0.63 | 0.62 | 1622.07 | 17.66 | 0.00 | 215.33 | 904.18 | 20.42 | 142.33 | 175.33 | |
Maximum of Months | 428.67 | 0.64 | 0.62 | 7968.16 | 37.24 | 292.00 | 401.33 | 5558.63 | 38.59 | 221.50 | 355.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.64 | 0.62 | 01-JAN-09:39 | 1722.75 | 21.28 | 65.67 | 224.17 | 876.99 | 22.22 | 81.83 | 173.00 |
February | 226.83 | 0.64 | 0.62 | 01-FEB-07:49 | 2068.07 | 20.37 | 62.83 | 233.67 | 1182.25 | 23.48 | 82.67 | 195.50 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:40 | 2732.11 | 20.84 | 100.33 | 314.83 | 1116.23 | 21.13 | 67.33 | 272.17 |
April | 285.17 | 0.63 | 0.62 | 01-APR-06:40 | 3203.61 | 20.53 | 77.17 | 342.67 | 1882.34 | 22.36 | 60.00 | 299.83 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-05:10 | 3292.10 | 20.01 | 112.00 | 396.67 | 1428.73 | 21.73 | 77.50 | 352.83 |
June | 400.67 | 0.63 | 0.62 | 01-JUN-04:00 | 3009.59 | 20.04 | 95.67 | 398.83 | 1636.35 | 21.89 | 68.33 | 362.00 |
July | 414.00 | 0.63 | 0.62 | 01-JUL-05:40 | 3834.91 | 21.58 | 123.33 | 408.17 | 1651.06 | 22.18 | 70.00 | 371.00 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:40 | 3035.26 | 20.34 | 110.50 | 376.00 | 1364.74 | 22.13 | 73.33 | 348.50 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-05:00 | 3061.69 | 21.36 | 95.17 | 324.00 | 1727.41 | 23.04 | 83.33 | 285.50 |
October | 325.17 | 0.64 | 0.62 | 01-OCT-06:40 | 1885.59 | 19.67 | 84.00 | 285.50 | 1048.21 | 22.57 | 90.67 | 251.00 |
November | 254.83 | 0.64 | 0.62 | 01-NOV-07:40 | 1460.52 | 18.93 | 64.50 | 226.83 | 802.04 | 21.74 | 74.00 | 179.17 |
December | 186.17 | 0.65 | 0.62 | 01-DEC-07:00 | 1354.35 | 20.88 | 63.83 | 186.83 | 697.90 | 21.51 | 60.50 | 113.17 |
Annual Sum or Average | 3807.33 | 0.63 | 2719.45 | 20.48 | 1055.00 | 3718.17 | 1344.10 | 22.14 | 889.50 | 3203.67 | ||
Minimum of Months | 186.17 | 0.63 | 0.62 | 1354.35 | 18.93 | 62.83 | 186.83 | 697.90 | 21.13 | 60.00 | 113.17 | |
Maximum of Months | 428.67 | 0.65 | 0.62 | 3834.91 | 21.58 | 123.33 | 408.17 | 1882.34 | 23.48 | 90.67 | 371.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.65 | 0.62 | 01-JAN-09:39 | 588.69 | 14.46 | 0.00 | 203.83 | 362.64 | 17.56 | 0.00 | 114.50 |
February | 226.83 | 0.65 | 0.62 | 01-FEB-08:30 | 620.28 | 14.83 | 0.00 | 218.50 | 389.01 | 17.90 | 0.00 | 144.33 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:49 | 847.69 | 16.47 | 0.00 | 311.50 | 494.41 | 19.25 | 0.00 | 249.67 |
April | 285.17 | 0.63 | 0.62 | 01-APR-06:40 | 992.27 | 17.47 | 0.00 | 345.00 | 614.94 | 20.22 | 27.33 | 278.00 |
May | 428.67 | 0.62 | 0.62 | 01-MAY-05:30 | 1128.73 | 17.87 | 3.17 | 408.67 | 644.63 | 21.54 | 112.17 | 370.00 |
June | 400.67 | 0.63 | 0.62 | 01-JUN-04:00 | 1360.62 | 21.21 | 75.50 | 409.67 | 801.90 | 23.65 | 203.17 | 387.50 |
July | 414.00 | 0.62 | 0.62 | 01-JUL-05:40 | 1284.53 | 19.77 | 30.67 | 419.33 | 760.71 | 22.46 | 181.50 | 391.00 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:40 | 1062.50 | 17.80 | 0.00 | 385.50 | 623.31 | 20.51 | 60.17 | 352.33 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-05:00 | 877.40 | 17.14 | 0.00 | 325.83 | 542.97 | 19.91 | 1.17 | 266.00 |
October | 325.17 | 0.64 | 0.62 | 01-OCT-06:00 | 693.29 | 15.41 | 0.00 | 274.00 | 412.60 | 18.30 | 0.00 | 207.17 |
November | 254.83 | 0.65 | 0.62 | 01-NOV-07:00 | 590.29 | 14.40 | 0.00 | 213.17 | 336.79 | 17.24 | 0.00 | 119.50 |
December | 186.17 | 0.67 | 0.62 | 01-DEC-08:20 | 427.70 | 12.96 | 0.00 | 156.17 | 272.30 | 16.24 | 0.00 | 40.33 |
Annual Sum or Average | 3807.33 | 0.63 | 938.30 | 17.15 | 109.33 | 3671.17 | 557.65 | 20.05 | 585.50 | 2920.33 | ||
Minimum of Months | 186.17 | 0.62 | 0.62 | 427.70 | 12.96 | 0.00 | 156.17 | 272.30 | 16.24 | 0.00 | 40.33 | |
Maximum of Months | 428.67 | 0.67 | 0.62 | 1360.62 | 21.21 | 75.50 | 419.33 | 801.90 | 23.65 | 203.17 | 391.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.64 | 0.62 | 01-JAN-09:39 | 1780.90 | 20.66 | 67.17 | 220.17 | 1089.40 | 23.83 | 84.83 | 172.00 |
February | 226.83 | 0.64 | 0.62 | 01-FEB-08:39 | 2141.97 | 20.54 | 63.33 | 234.17 | 1137.58 | 21.67 | 58.67 | 197.67 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:00 | 2326.29 | 20.54 | 93.67 | 316.33 | 1255.10 | 22.12 | 86.67 | 275.50 |
April | 285.17 | 0.63 | 0.62 | 01-APR-06:49 | 4120.30 | 21.51 | 84.50 | 344.17 | 1726.28 | 21.32 | 39.50 | 288.50 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-06:40 | 2490.39 | 16.72 | 49.67 | 396.67 | 1349.77 | 18.34 | 0.00 | 357.50 |
June | 400.67 | 0.63 | 0.62 | 01-JUN-05:19 | 3153.06 | 17.20 | 50.33 | 398.50 | 1444.36 | 18.78 | 0.00 | 362.17 |
July | 414.00 | 0.63 | 0.62 | 01-JUL-05:40 | 3553.69 | 17.70 | 56.00 | 407.50 | 1552.50 | 19.01 | 2.17 | 372.50 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:00 | 2973.82 | 19.17 | 84.33 | 380.00 | 1666.04 | 21.07 | 55.83 | 344.83 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-06:19 | 3103.90 | 21.58 | 96.67 | 328.17 | 1789.83 | 23.16 | 73.50 | 292.33 |
October | 325.17 | 0.64 | 0.62 | 01-OCT-07:10 | 1945.43 | 19.75 | 82.17 | 286.50 | 1040.89 | 21.44 | 72.00 | 249.17 |
November | 254.83 | 0.64 | 0.62 | 01-NOV-07:00 | 1508.34 | 18.97 | 68.83 | 230.50 | 843.26 | 21.46 | 68.33 | 184.17 |
December | 186.17 | 0.65 | 0.62 | 01-DEC-08:20 | 1428.56 | 19.81 | 55.00 | 191.50 | 769.32 | 20.90 | 44.00 | 110.00 |
Annual Sum or Average | 3807.33 | 0.63 | 2663.33 | 19.26 | 851.67 | 3734.17 | 1357.57 | 20.83 | 585.50 | 3206.33 | ||
Minimum of Months | 186.17 | 0.63 | 0.62 | 1428.56 | 16.72 | 49.67 | 191.50 | 769.32 | 18.34 | 0.00 | 110.00 | |
Maximum of Months | 428.67 | 0.65 | 0.62 | 4120.30 | 21.58 | 96.67 | 407.50 | 1789.83 | 23.83 | 86.67 | 372.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.63 | 0.62 | 01-JAN-09:39 | 6391.49 | 34.41 | 188.00 | 236.33 | 5412.56 | 37.61 | 200.00 | 216.17 |
February | 226.83 | 0.63 | 0.62 | 01-FEB-07:49 | 7739.07 | 35.81 | 211.50 | 249.67 | 2135.56 | 26.63 | 105.67 | 232.17 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:49 | 7136.34 | 29.13 | 248.00 | 322.50 | 1239.89 | 18.40 | 5.33 | 283.50 |
April | 285.17 | 0.64 | 0.62 | 01-APR-06:40 | 1976.40 | 14.56 | 0.00 | 340.00 | 1164.75 | 18.54 | 10.00 | 285.33 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-05:00 | 1542.31 | 14.04 | 0.00 | 386.67 | 853.94 | 17.95 | 0.00 | 336.67 |
June | 400.67 | 0.64 | 0.62 | 01-JUN-05:19 | 1570.34 | 14.50 | 0.00 | 388.00 | 886.15 | 18.41 | 0.00 | 341.00 |
July | 414.00 | 0.63 | 0.62 | 01-JUL-05:40 | 1627.31 | 14.82 | 0.00 | 397.50 | 926.88 | 18.75 | 1.17 | 350.83 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:00 | 1805.29 | 14.58 | 0.00 | 371.33 | 1003.19 | 18.50 | 1.33 | 333.83 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-06:10 | 2654.42 | 16.59 | 26.00 | 326.67 | 1260.13 | 18.97 | 22.83 | 293.17 |
October | 325.17 | 0.63 | 0.62 | 01-OCT-06:40 | 6698.25 | 32.11 | 287.00 | 301.17 | 1685.33 | 19.90 | 30.83 | 277.33 |
November | 254.83 | 0.63 | 0.62 | 01-NOV-07:40 | 4592.29 | 30.85 | 216.83 | 241.50 | 2490.49 | 29.44 | 181.00 | 218.50 |
December | 186.17 | 0.63 | 0.62 | 01-DEC-07:00 | 5628.86 | 34.66 | 164.67 | 213.00 | 5190.01 | 37.07 | 169.00 | 170.17 |
Annual Sum or Average | 3807.33 | 0.63 | 3688.26 | 21.93 | 1342.00 | 3774.33 | 1698.72 | 21.81 | 727.17 | 3338.67 | ||
Minimum of Months | 186.17 | 0.63 | 0.62 | 1542.31 | 14.04 | 0.00 | 213.00 | 853.94 | 17.95 | 0.00 | 170.17 | |
Maximum of Months | 428.67 | 0.64 | 0.62 | 7739.07 | 35.81 | 287.00 | 397.50 | 5412.56 | 37.61 | 200.00 | 350.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.64 | 0.62 | 01-JAN-09:39 | 1666.43 | 20.85 | 65.67 | 220.67 | 836.31 | 21.98 | 75.00 | 166.67 |
February | 226.83 | 0.64 | 0.62 | 01-FEB-07:49 | 2005.25 | 19.93 | 62.83 | 230.67 | 1134.45 | 23.27 | 75.17 | 191.83 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:40 | 2658.20 | 20.44 | 99.67 | 312.33 | 1062.22 | 20.91 | 56.33 | 268.00 |
April | 285.17 | 0.64 | 0.62 | 01-APR-06:40 | 3109.29 | 20.13 | 77.00 | 341.00 | 1811.83 | 22.17 | 57.17 | 290.83 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-05:19 | 3204.48 | 19.61 | 111.83 | 395.17 | 1365.28 | 21.55 | 77.67 | 347.83 |
June | 400.67 | 0.63 | 0.62 | 01-JUN-04:00 | 2903.81 | 19.59 | 94.67 | 397.17 | 1565.41 | 21.72 | 68.33 | 359.00 |
July | 414.00 | 0.63 | 0.62 | 01-JUL-05:40 | 3646.92 | 19.95 | 101.83 | 406.17 | 1579.88 | 22.01 | 70.00 | 367.83 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:40 | 2937.12 | 19.79 | 108.17 | 373.33 | 1300.90 | 21.95 | 72.17 | 345.33 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-05:00 | 2832.89 | 19.34 | 74.67 | 321.83 | 1645.54 | 22.70 | 76.00 | 280.33 |
October | 325.17 | 0.64 | 0.62 | 01-OCT-06:40 | 1823.15 | 19.23 | 84.00 | 283.00 | 975.36 | 21.30 | 66.67 | 244.83 |
November | 254.83 | 0.64 | 0.62 | 01-NOV-07:40 | 1414.77 | 18.49 | 64.17 | 224.00 | 770.20 | 21.51 | 71.33 | 173.00 |
December | 186.17 | 0.65 | 0.62 | 01-DEC-07:00 | 1310.16 | 20.45 | 63.83 | 183.33 | 665.16 | 21.26 | 55.50 | 109.50 |
Annual Sum or Average | 3807.33 | 0.63 | 2616.78 | 19.77 | 1008.33 | 3688.67 | 1282.72 | 21.84 | 821.33 | 3145.00 | ||
Minimum of Months | 186.17 | 0.63 | 0.62 | 1310.16 | 18.49 | 62.83 | 183.33 | 665.16 | 20.91 | 55.50 | 109.50 | |
Maximum of Months | 428.67 | 0.65 | 0.62 | 3646.92 | 20.85 | 111.83 | 406.17 | 1811.83 | 23.27 | 77.67 | 367.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.66 | 0.62 | 01-JAN-09:39 | 561.63 | 10.97 | 0.00 | 199.00 | 348.35 | 15.16 | 0.00 | 107.67 |
February | 226.83 | 0.65 | 0.62 | 01-FEB-08:39 | 592.84 | 11.47 | 0.00 | 213.00 | 374.70 | 15.65 | 0.00 | 134.00 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:49 | 812.04 | 13.05 | 0.00 | 307.33 | 475.54 | 16.99 | 0.00 | 241.33 |
April | 285.17 | 0.63 | 0.62 | 01-APR-06:40 | 950.84 | 14.45 | 0.00 | 343.33 | 593.53 | 18.41 | 1.33 | 270.00 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-05:30 | 1081.95 | 14.42 | 3.17 | 406.50 | 619.39 | 19.47 | 31.00 | 365.50 |
June | 400.67 | 0.63 | 0.62 | 01-JUN-04:00 | 1303.23 | 18.52 | 75.17 | 408.50 | 770.15 | 21.86 | 86.00 | 384.17 |
July | 414.00 | 0.62 | 0.62 | 01-JUL-05:40 | 1230.62 | 16.79 | 30.67 | 417.67 | 731.50 | 20.59 | 55.00 | 387.17 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:40 | 1017.65 | 14.58 | 0.00 | 384.67 | 599.53 | 18.53 | 1.00 | 346.17 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-05:00 | 839.57 | 14.12 | 0.00 | 322.83 | 523.29 | 18.07 | 0.00 | 260.17 |
October | 325.17 | 0.64 | 0.62 | 01-OCT-06:00 | 663.37 | 11.93 | 0.00 | 269.33 | 396.81 | 15.98 | 0.00 | 199.17 |
November | 254.83 | 0.65 | 0.62 | 01-NOV-07:00 | 564.67 | 10.65 | 0.00 | 209.17 | 323.08 | 14.65 | 0.00 | 109.33 |
December | 186.17 | 0.67 | 0.62 | 01-DEC-08:20 | 407.64 | 9.22 | 0.00 | 146.33 | 261.79 | 13.61 | 0.00 | 33.50 |
Annual Sum or Average | 3807.33 | 0.64 | 898.40 | 13.89 | 109.00 | 3627.67 | 536.34 | 17.95 | 174.33 | 2838.17 | ||
Minimum of Months | 186.17 | 0.62 | 0.62 | 407.64 | 9.22 | 0.00 | 146.33 | 261.79 | 13.61 | 0.00 | 33.50 | |
Maximum of Months | 428.67 | 0.67 | 0.62 | 1303.23 | 18.52 | 75.17 | 417.67 | 770.15 | 21.86 | 86.00 | 387.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.65 | 0.62 | 01-JAN-09:39 | 1725.44 | 20.32 | 67.17 | 218.17 | 1048.89 | 23.75 | 84.50 | 166.83 |
February | 226.83 | 0.64 | 0.62 | 01-FEB-08:39 | 2072.83 | 20.20 | 63.33 | 232.33 | 1084.95 | 21.56 | 57.67 | 192.83 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:00 | 2153.97 | 18.60 | 70.83 | 314.50 | 1205.07 | 22.00 | 83.50 | 271.83 |
April | 285.17 | 0.63 | 0.62 | 01-APR-06:00 | 4018.64 | 21.14 | 84.50 | 342.00 | 1646.50 | 21.18 | 39.17 | 282.50 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-06:40 | 2410.03 | 16.29 | 49.50 | 394.33 | 1291.79 | 18.16 | 0.00 | 354.17 |
June | 400.67 | 0.63 | 0.62 | 01-JUN-05:30 | 3055.89 | 16.79 | 50.33 | 397.17 | 1373.90 | 18.61 | 0.00 | 359.33 |
July | 414.00 | 0.63 | 0.62 | 01-JUL-05:49 | 3440.30 | 17.28 | 56.00 | 404.83 | 1474.67 | 18.85 | 2.17 | 369.17 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:00 | 2775.59 | 18.78 | 84.00 | 377.83 | 1597.50 | 20.93 | 55.17 | 341.00 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-06:19 | 3016.05 | 21.22 | 96.67 | 326.33 | 1722.41 | 23.02 | 72.50 | 287.17 |
October | 325.17 | 0.64 | 0.62 | 01-OCT-07:19 | 1878.97 | 19.39 | 82.17 | 284.50 | 992.24 | 21.32 | 70.17 | 244.83 |
November | 254.83 | 0.64 | 0.62 | 01-NOV-07:00 | 1459.82 | 18.62 | 68.50 | 227.00 | 808.73 | 21.35 | 67.33 | 178.83 |
December | 186.17 | 0.65 | 0.62 | 01-DEC-08:30 | 1383.70 | 19.47 | 55.00 | 187.33 | 735.39 | 20.80 | 43.50 | 104.50 |
Annual Sum or Average | 3807.33 | 0.63 | 2561.70 | 18.74 | 828.00 | 3706.33 | 1298.08 | 20.69 | 575.67 | 3153.00 | ||
Minimum of Months | 186.17 | 0.63 | 0.62 | 1383.70 | 16.29 | 49.50 | 187.33 | 735.39 | 18.16 | 0.00 | 104.50 | |
Maximum of Months | 428.67 | 0.65 | 0.62 | 4018.64 | 21.22 | 96.67 | 404.83 | 1722.41 | 23.75 | 84.50 | 369.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.63 | 0.62 | 01-JAN-09:39 | 6391.55 | 34.41 | 188.00 | 236.33 | 5412.48 | 37.61 | 200.00 | 216.17 |
February | 226.83 | 0.63 | 0.62 | 01-FEB-07:49 | 7739.08 | 35.81 | 211.50 | 249.67 | 2135.47 | 26.63 | 105.67 | 232.17 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:49 | 7136.26 | 29.13 | 248.00 | 322.50 | 1239.80 | 18.40 | 5.33 | 283.50 |
April | 285.17 | 0.64 | 0.62 | 01-APR-06:40 | 1976.33 | 14.56 | 0.00 | 340.00 | 1164.67 | 18.54 | 10.17 | 285.33 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-05:00 | 1542.24 | 14.04 | 0.00 | 386.67 | 853.88 | 17.95 | 0.00 | 336.67 |
June | 400.67 | 0.64 | 0.62 | 01-JUN-05:19 | 1570.28 | 14.50 | 0.00 | 388.00 | 886.09 | 18.41 | 0.00 | 341.00 |
July | 414.00 | 0.63 | 0.62 | 01-JUL-05:40 | 1627.24 | 14.82 | 0.00 | 397.50 | 926.82 | 18.75 | 1.17 | 350.83 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:00 | 1805.21 | 14.59 | 0.00 | 371.33 | 1003.11 | 18.50 | 1.33 | 333.67 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-06:10 | 2654.35 | 16.59 | 26.00 | 326.67 | 1260.04 | 18.97 | 22.83 | 293.17 |
October | 325.17 | 0.63 | 0.62 | 01-OCT-06:40 | 6698.23 | 32.11 | 287.00 | 301.17 | 1685.25 | 19.90 | 30.83 | 277.33 |
November | 254.83 | 0.63 | 0.62 | 01-NOV-07:40 | 4592.30 | 30.85 | 216.83 | 241.50 | 2490.41 | 29.44 | 181.00 | 218.50 |
December | 186.17 | 0.63 | 0.62 | 01-DEC-07:00 | 5628.92 | 34.66 | 164.67 | 213.00 | 5189.96 | 37.07 | 169.00 | 170.17 |
Annual Sum or Average | 3807.33 | 0.63 | 3688.22 | 21.93 | 1342.00 | 3774.33 | 1698.64 | 21.81 | 727.33 | 3338.50 | ||
Minimum of Months | 186.17 | 0.63 | 0.62 | 1542.24 | 14.04 | 0.00 | 213.00 | 853.88 | 17.95 | 0.00 | 170.17 | |
Maximum of Months | 428.67 | 0.64 | 0.62 | 7739.08 | 35.81 | 287.00 | 397.50 | 5412.48 | 37.61 | 200.00 | 350.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.64 | 0.62 | 01-JAN-09:39 | 1666.44 | 20.85 | 65.67 | 220.67 | 836.27 | 21.98 | 75.00 | 166.67 |
February | 226.83 | 0.64 | 0.62 | 01-FEB-07:49 | 2005.25 | 19.93 | 62.83 | 230.67 | 1134.40 | 23.27 | 75.17 | 191.83 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:40 | 2658.18 | 20.44 | 99.67 | 312.33 | 1062.16 | 20.91 | 56.33 | 268.00 |
April | 285.17 | 0.64 | 0.62 | 01-APR-06:40 | 3109.29 | 20.13 | 77.00 | 341.00 | 1811.78 | 22.17 | 57.17 | 290.67 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-05:19 | 3204.45 | 19.61 | 111.83 | 395.17 | 1365.22 | 21.55 | 77.67 | 347.83 |
June | 400.67 | 0.63 | 0.62 | 01-JUN-04:00 | 2903.78 | 19.59 | 94.67 | 397.17 | 1565.34 | 21.72 | 68.33 | 359.00 |
July | 414.00 | 0.63 | 0.62 | 01-JUL-05:40 | 3646.90 | 19.95 | 101.83 | 406.17 | 1579.81 | 22.01 | 70.00 | 367.83 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:40 | 2937.09 | 19.79 | 108.17 | 373.33 | 1300.84 | 21.95 | 72.17 | 345.33 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-05:00 | 2832.89 | 19.34 | 74.67 | 321.83 | 1645.48 | 22.70 | 76.17 | 280.33 |
October | 325.17 | 0.64 | 0.62 | 01-OCT-06:40 | 1823.13 | 19.23 | 84.00 | 283.00 | 975.32 | 21.30 | 66.67 | 244.83 |
November | 254.83 | 0.64 | 0.62 | 01-NOV-07:40 | 1414.76 | 18.49 | 64.17 | 224.00 | 770.16 | 21.51 | 71.33 | 173.00 |
December | 186.17 | 0.65 | 0.62 | 01-DEC-07:00 | 1310.17 | 20.45 | 63.83 | 183.33 | 665.14 | 21.26 | 55.67 | 109.50 |
Annual Sum or Average | 3807.33 | 0.63 | 2616.77 | 19.78 | 1008.33 | 3688.67 | 1282.67 | 21.84 | 821.67 | 3144.83 | ||
Minimum of Months | 186.17 | 0.63 | 0.62 | 1310.17 | 18.49 | 62.83 | 183.33 | 665.14 | 20.91 | 55.67 | 109.50 | |
Maximum of Months | 428.67 | 0.65 | 0.62 | 3646.90 | 20.85 | 111.83 | 406.17 | 1811.78 | 23.27 | 77.67 | 367.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.66 | 0.62 | 01-JAN-09:39 | 561.63 | 10.97 | 0.00 | 199.00 | 348.33 | 15.16 | 0.00 | 107.67 |
February | 226.83 | 0.65 | 0.62 | 01-FEB-08:39 | 592.84 | 11.47 | 0.00 | 213.00 | 374.68 | 15.65 | 0.00 | 134.00 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:49 | 812.02 | 13.06 | 0.00 | 307.33 | 475.51 | 16.99 | 0.00 | 241.33 |
April | 285.17 | 0.63 | 0.62 | 01-APR-06:40 | 950.83 | 14.45 | 0.00 | 343.33 | 593.50 | 18.41 | 1.33 | 270.00 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-05:30 | 1081.92 | 14.43 | 3.17 | 406.50 | 619.35 | 19.47 | 31.00 | 365.50 |
June | 400.67 | 0.63 | 0.62 | 01-JUN-04:00 | 1303.21 | 18.53 | 75.17 | 408.50 | 770.10 | 21.86 | 86.00 | 384.17 |
July | 414.00 | 0.62 | 0.62 | 01-JUL-05:40 | 1230.60 | 16.79 | 30.67 | 417.67 | 731.46 | 20.59 | 55.33 | 387.17 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:40 | 1017.63 | 14.58 | 0.00 | 384.67 | 599.50 | 18.53 | 1.00 | 346.00 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-05:00 | 839.57 | 14.13 | 0.00 | 322.83 | 523.27 | 18.07 | 0.00 | 260.17 |
October | 325.17 | 0.64 | 0.62 | 01-OCT-06:00 | 663.36 | 11.94 | 0.00 | 269.33 | 396.79 | 15.98 | 0.00 | 199.17 |
November | 254.83 | 0.65 | 0.62 | 01-NOV-07:00 | 564.66 | 10.65 | 0.00 | 209.17 | 323.06 | 14.65 | 0.00 | 109.17 |
December | 186.17 | 0.67 | 0.62 | 01-DEC-08:20 | 407.65 | 9.22 | 0.00 | 146.33 | 261.78 | 13.61 | 0.00 | 33.50 |
Annual Sum or Average | 3807.33 | 0.64 | 898.39 | 13.90 | 109.00 | 3627.67 | 536.31 | 17.95 | 174.67 | 2837.83 | ||
Minimum of Months | 186.17 | 0.62 | 0.62 | 407.65 | 9.22 | 0.00 | 146.33 | 261.78 | 13.61 | 0.00 | 33.50 | |
Maximum of Months | 428.67 | 0.67 | 0.62 | 1303.21 | 18.53 | 75.17 | 417.67 | 770.10 | 21.86 | 86.00 | 387.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.65 | 0.62 | 01-JAN-09:39 | 1725.44 | 20.32 | 67.17 | 218.17 | 1048.85 | 23.75 | 84.50 | 166.83 |
February | 226.83 | 0.64 | 0.62 | 01-FEB-08:39 | 2072.83 | 20.20 | 63.33 | 232.33 | 1084.91 | 21.56 | 57.83 | 192.83 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:00 | 2153.95 | 18.60 | 70.83 | 314.50 | 1205.02 | 22.00 | 83.50 | 271.83 |
April | 285.17 | 0.63 | 0.62 | 01-APR-06:00 | 4018.63 | 21.15 | 84.50 | 342.00 | 1646.44 | 21.18 | 39.17 | 282.33 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-06:40 | 2409.99 | 16.29 | 49.50 | 394.33 | 1291.73 | 18.16 | 0.00 | 354.17 |
June | 400.67 | 0.63 | 0.62 | 01-JUN-05:30 | 3055.87 | 16.79 | 50.33 | 397.17 | 1373.83 | 18.61 | 0.00 | 359.33 |
July | 414.00 | 0.63 | 0.62 | 01-JUL-05:49 | 3440.28 | 17.29 | 56.00 | 404.83 | 1474.60 | 18.85 | 2.17 | 369.00 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:00 | 2775.57 | 18.78 | 84.00 | 377.83 | 1597.43 | 20.93 | 55.17 | 341.00 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-06:19 | 3016.06 | 21.22 | 96.67 | 326.33 | 1722.35 | 23.03 | 72.50 | 287.17 |
October | 325.17 | 0.64 | 0.62 | 01-OCT-07:19 | 1878.96 | 19.39 | 82.17 | 284.50 | 992.20 | 21.32 | 70.17 | 244.83 |
November | 254.83 | 0.64 | 0.62 | 01-NOV-07:00 | 1459.80 | 18.62 | 68.50 | 227.00 | 808.69 | 21.35 | 67.50 | 178.83 |
December | 186.17 | 0.65 | 0.62 | 01-DEC-08:30 | 1383.70 | 19.47 | 55.00 | 187.33 | 735.37 | 20.80 | 43.50 | 104.50 |
Annual Sum or Average | 3807.33 | 0.63 | 2561.69 | 18.74 | 828.00 | 3706.33 | 1298.02 | 20.69 | 576.00 | 3152.67 | ||
Minimum of Months | 186.17 | 0.63 | 0.62 | 1383.70 | 16.29 | 49.50 | 187.33 | 735.37 | 18.16 | 0.00 | 104.50 | |
Maximum of Months | 428.67 | 0.65 | 0.62 | 4018.63 | 21.22 | 96.67 | 404.83 | 1722.35 | 23.75 | 84.50 | 369.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.146690E+10 | 24974.61 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.367278E+09 | 24974.61 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20520767.89 | 24974.61 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122107E+09 | 24974.61 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.333792E+09 | 24974.61 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.146690E+10 | 24974.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139321E+11 | 11816.10 | 18-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.970754E+10 | 11819.77 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.807146E+10 | 11798.66 | 29-MAR-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.432565E+10 | 12036.33 | 19-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133581E+10 | 11861.19 | 09-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.517583E+09 | 12083.63 | 22-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 48050461.97 | 10951.48 | 24-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176790E+09 | 12063.29 | 17-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.929677E+09 | 12033.45 | 19-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.231556E+10 | 11804.47 | 10-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.639697E+10 | 11817.57 | 08-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110117E+11 | 11809.65 | 14-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.587689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 48050461.97 | 10951.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139321E+11 | 12083.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.626677E+10 | 9761.33 | 17-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.393010E+10 | 9717.03 | 04-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210552E+10 | 9729.04 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.788301E+09 | 9713.14 | 12-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5615401.73 | 9669.40 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5298142.18 | 9674.06 | 29-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84330375.82 | 9674.85 | 23-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185164E+10 | 9747.84 | 29-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.434450E+10 | 9756.34 | 18-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.626677E+10 | 9761.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101276E+11 | 8583.48 | 18-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.680413E+10 | 8579.55 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.407094E+10 | 8550.58 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157617E+10 | 8560.12 | 24-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 58354117.81 | 8525.57 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19280668.67 | 8492.73 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.253828E+09 | 8530.21 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.298149E+10 | 8555.27 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.688944E+10 | 8571.71 | 14-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.101276E+11 | 8583.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.649652E+10 | 10535.69 | 17-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.408019E+10 | 10487.87 | 04-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.239051E+10 | 10500.84 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.748877E+09 | 10483.63 | 12-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30345635.89 | 10453.51 | 03-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 319001.32 | 581.05 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 24291218.79 | 10441.41 | 29-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116034E+09 | 10442.57 | 23-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194237E+10 | 10500.86 | 20-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.446055E+10 | 10530.29 | 18-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.649652E+10 | 10535.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.657341E+10 | 30086.82 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.335137E+10 | 30086.82 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128844E+10 | 30086.82 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.253281E+09 | 30086.82 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6402928.80 | 30086.82 | 16-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192255E+10 | 30086.82 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.415216E+10 | 30086.82 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.657341E+10 | 30086.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.672291E+10 | 13598.34 | 17-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.368637E+10 | 13604.89 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202558E+10 | 13569.53 | 13-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.647700E+09 | 13573.28 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12281521.14 | 13362.26 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29362986.87 | 13370.08 | 29-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.216338E+09 | 13419.28 | 06-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.243336E+10 | 13569.35 | 27-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.545805E+10 | 13572.13 | 14-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.672291E+10 | 13604.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.638432E+10 | 11748.23 | 11-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.375653E+10 | 11723.02 | 21-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186071E+10 | 11742.58 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.595984E+09 | 11681.65 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4203197.63 | 11615.13 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33919961.48 | 11621.66 | 29-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.317615E+09 | 11661.80 | 19-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.242802E+10 | 11748.10 | 20-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.492948E+10 | 11742.79 | 04-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.638432E+10 | 11748.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.993489E+10 | 9155.04 | 18-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.602223E+10 | 9160.30 | 10-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.291239E+10 | 9149.33 | 10-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.785665E+09 | 9136.86 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10859978.06 | 8976.92 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43391972.18 | 9123.32 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.394312E+09 | 9160.58 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.342410E+10 | 9188.19 | 15-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.723204E+10 | 9127.94 | 23-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.993489E+10 | 9188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.650938E+10 | 12291.56 | 11-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.387885E+10 | 12251.25 | 06-FEB-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.205007E+10 | 12285.64 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.600438E+09 | 12221.92 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17275692.42 | 12152.34 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 64325277.15 | 12159.12 | 29-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.374654E+09 | 12160.27 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.244947E+10 | 12291.38 | 20-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.494884E+10 | 12261.01 | 28-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.650938E+10 | 12291.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131443E+11 | 32708.73 | 18-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.824228E+10 | 32819.21 | 10-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.415536E+10 | 32785.53 | 27-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124905E+10 | 32792.12 | 28-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6896001.90 | 32190.70 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 61391972.88 | 32266.53 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.627796E+09 | 32759.72 | 17-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.527843E+10 | 32872.83 | 20-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102103E+11 | 32736.32 | 01-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.429758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131443E+11 | 32872.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104753E+11 | 15004.36 | 11-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.632054E+10 | 15350.31 | 02-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.379736E+10 | 15036.58 | 18-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152373E+10 | 15045.44 | 29-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75882203.77 | 14841.24 | 03-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13245647.24 | 7826.74 | 03-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.199640E+09 | 14961.81 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.910119E+09 | 15024.45 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.456697E+10 | 15031.74 | 16-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.872863E+10 | 15012.44 | 02-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.366114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104753E+11 | 15350.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.899565E+10 | 12022.93 | 10-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.563985E+10 | 12266.00 | 02-FEB-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.299650E+10 | 12025.01 | 21-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115084E+10 | 12008.56 | 22-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24011946.36 | 11921.52 | 02-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11390031.70 | 5129.09 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153208E+09 | 11931.91 | 29-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.887429E+09 | 11993.77 | 19-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.395985E+10 | 12034.26 | 20-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.725388E+10 | 12021.18 | 01-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.310726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.899565E+10 | 12266.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.143527E+11 | 11688.78 | 17-JAN-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.935308E+10 | 11928.33 | 02-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.514705E+10 | 11735.99 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180088E+10 | 11691.24 | 29-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71054955.35 | 11532.61 | 03-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9881739.19 | 6496.15 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.274355E+09 | 11706.52 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149867E+10 | 11679.52 | 16-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.605883E+10 | 11714.11 | 15-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112255E+11 | 11675.69 | 02-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.497920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.143527E+11 | 11928.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.930535E+10 | 13353.17 | 10-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.595995E+10 | 13325.90 | 28-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.343382E+10 | 13355.66 | 21-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127404E+10 | 13337.15 | 22-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 83776830.30 | 13268.95 | 03-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20613241.24 | 6292.46 | 03-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.256592E+09 | 13251.92 | 29-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112680E+10 | 13320.77 | 19-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.414760E+10 | 13365.50 | 20-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.744347E+10 | 13330.25 | 13-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.330520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.930535E+10 | 13365.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.287705E+11 | 44933.77 | 31-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191926E+11 | 51694.37 | 02-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103008E+11 | 24711.47 | 06-MAR-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.334784E+10 | 17723.69 | 03-APR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82700381.99 | 5330.88 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1316713.74 | 652.85 | 03-JUN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165403E+09 | 7042.31 | 30-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137169E+10 | 10517.21 | 23-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.922492E+10 | 29485.17 | 28-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203242E+11 | 36194.27 | 11-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.927820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.287705E+11 | 51694.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.285348E+11 | 44709.32 | 31-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195186E+11 | 51094.74 | 02-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114541E+11 | 24550.17 | 06-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.438389E+10 | 18246.45 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148209E+09 | 6454.58 | 02-MAY-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4923074.97 | 1160.66 | 03-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.312684E+09 | 8387.24 | 29-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.231622E+10 | 11931.33 | 23-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103532E+11 | 29156.22 | 25-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210380E+11 | 35752.40 | 09-DEC-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.980646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.285348E+11 | 51094.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.327440E+11 | 45231.56 | 31-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217640E+11 | 51674.47 | 02-FEB-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120505E+11 | 24244.46 | 08-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.466591E+10 | 18841.19 | 03-APR-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201132E+09 | 8220.03 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20120173.51 | 2806.56 | 03-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.454749E+09 | 10619.01 | 29-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.272781E+10 | 14618.63 | 23-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117423E+11 | 31984.12 | 25-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.238162E+11 | 38911.50 | 09-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110187E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.327440E+11 | 51674.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.149260E+09 | 0.126167E+09 | 7443.76 | 25-MAR-15:00 | 6469.28 | 0.00 |
April | 0.00 | 0.00 | 0.507762E+10 | 0.387223E+10 | 72622.65 | 18-APR-12:00 | 47953.40 | 0.00 |
May | 0.00 | 0.00 | 0.139932E+11 | 0.104905E+11 | 73604.34 | 31-MAY-11:20 | 53692.03 | 0.00 |
June | 0.00 | 0.00 | 0.451318E+11 | 0.331956E+11 | 129516.62 | 26-JUN-07:50 | 57426.31 | 0.00 |
July | 0.00 | 0.00 | 0.645046E+11 | 0.433002E+11 | 114357.51 | 05-JUL-10:50 | 60705.14 | 0.00 |
August | 0.00 | 0.00 | 0.634003E+11 | 0.435092E+11 | 130791.59 | 03-AUG-06:03 | 44069.41 | 0.00 |
September | 0.00 | 0.00 | 0.251571E+11 | 0.221437E+11 | 98556.05 | 11-SEP-09:50 | 59081.50 | 0.00 |
October | 0.00 | 0.00 | 0.147437E+10 | 0.125894E+10 | 32322.99 | 20-OCT-15:00 | 32322.99 | 0.00 |
November | 0.00 | 0.00 | 51298360.69 | 45965840.94 | 4235.24 | 03-NOV-14:00 | 3900.78 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.218939E+12 | 0.157942E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.645046E+11 | 0.435092E+11 | 130791.59 | 60705.14 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.149291E+09 | 0.130195E+09 | 7920.94 | 25-MAR-15:00 | 7427.35 | 0.00 |
April | 0.00 | 0.00 | 0.559129E+10 | 0.438400E+10 | 67087.08 | 18-APR-12:40 | 48810.37 | 0.00 |
May | 0.00 | 0.00 | 0.146568E+11 | 0.109024E+11 | 68608.32 | 30-MAY-11:00 | 43121.36 | 0.00 |
June | 0.00 | 0.00 | 0.433614E+11 | 0.321487E+11 | 120694.07 | 26-JUN-08:00 | 54346.32 | 0.00 |
July | 0.00 | 0.00 | 0.595358E+11 | 0.400056E+11 | 108885.86 | 03-JUL-08:50 | 50614.38 | 0.00 |
August | 0.00 | 0.00 | 0.554431E+11 | 0.382194E+11 | 121690.21 | 03-AUG-05:03 | 41462.25 | 0.00 |
September | 0.00 | 0.00 | 0.220952E+11 | 0.194747E+11 | 83777.33 | 11-SEP-09:40 | 49867.84 | 0.00 |
October | 0.00 | 0.00 | 0.131000E+10 | 0.110759E+10 | 27022.16 | 20-OCT-15:00 | 27022.16 | 0.00 |
November | 0.00 | 0.00 | 59347746.84 | 50650828.46 | 5502.15 | 03-NOV-13:30 | 4569.34 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.202202E+12 | 0.146423E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.595358E+11 | 0.400056E+11 | 121690.21 | 54346.32 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.155519E+09 | 0.132193E+09 | 8333.71 | 25-MAR-15:00 | 7575.02 | 0.00 |
April | 0.00 | 0.00 | 0.617937E+10 | 0.482900E+10 | 80678.83 | 18-APR-15:50 | 56070.06 | 0.00 |
May | 0.00 | 0.00 | 0.156133E+11 | 0.116827E+11 | 76673.42 | 30-MAY-12:10 | 55670.37 | 0.00 |
June | 0.00 | 0.00 | 0.464221E+11 | 0.348597E+11 | 130412.35 | 26-JUN-06:03 | 52174.64 | 0.00 |
July | 0.00 | 0.00 | 0.628937E+11 | 0.423061E+11 | 114729.88 | 06-JUL-15:10 | 59106.04 | 0.00 |
August | 0.00 | 0.00 | 0.572493E+11 | 0.399334E+11 | 110952.22 | 04-AUG-07:15 | 33993.64 | 0.00 |
September | 0.00 | 0.00 | 0.228681E+11 | 0.200861E+11 | 83259.41 | 11-SEP-10:00 | 51656.00 | 0.00 |
October | 0.00 | 0.00 | 0.131192E+10 | 0.108750E+10 | 26806.93 | 20-OCT-15:00 | 26806.93 | 0.00 |
November | 0.00 | 0.00 | 39806746.75 | 33677110.01 | 3695.11 | 03-NOV-14:00 | 3183.01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.212733E+12 | 0.154950E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.628937E+11 | 0.423061E+11 | 130412.35 | 59106.04 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 2082.31 | 7369.40 | 31-JAN-12:19 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 2133.72 | 7414.63 | 16-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2253.24 | 7404.59 | 01-MAR-12:12 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2027.62 | 7200.27 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1986.61 | 6830.09 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1909.33 | 6418.12 | 01-JUN-11:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1659.98 | 5961.48 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1780.31 | 5732.80 | 02-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1684.97 | 5902.15 | 28-SEP-11:09 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1761.22 | 6282.51 | 31-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1901.48 | 6708.34 | 30-NOV-12:14 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1937.31 | 7092.95 | 29-DEC-12:13 |
Annual Sum or Average | 0.00 | 1925.31 | ||||
Minimum of Months | 0.00 | 0.00 | 1659.98 | 5732.80 | ||
Maximum of Months | 0.00 | 0.00 | 2253.24 | 7414.63 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.213038E+10 | 0.42 | 2821.32 | 02-JAN-05:01 | 0.84 |
February | 0.157865E+10 | 0.36 | 2821.32 | 01-FEB-07:01 | 0.84 |
March | 0.167817E+10 | 0.34 | 2821.32 | 06-MAR-07:01 | 0.84 |
April | 0.187643E+10 | 0.33 | 6423.13 | 18-APR-15:10 | 1.34 |
May | 0.270343E+10 | 0.38 | 8048.50 | 31-MAY-12:10 | 1.54 |
June | 0.465232E+10 | 0.51 | 11004.33 | 26-JUN-16:00 | 1.88 |
July | 0.545286E+10 | 0.55 | 11344.76 | 05-JUL-12:10 | 1.91 |
August | 0.572421E+10 | 0.57 | 11706.44 | 03-AUG-07:20 | 1.95 |
September | 0.379753E+10 | 0.46 | 9606.19 | 11-SEP-15:50 | 1.72 |
October | 0.187237E+10 | 0.32 | 3821.95 | 20-OCT-15:10 | 0.99 |
November | 0.167075E+10 | 0.33 | 2838.60 | 02-NOV-07:03 | 0.84 |
December | 0.173011E+10 | 0.36 | 2821.32 | 11-DEC-06:01 | 0.84 |
Annual Sum or Average | 0.348672E+11 | 0.41 | |||
Minimum of Months | 0.157865E+10 | 0.32 | 2821.32 | 0.84 | |
Maximum of Months | 0.572421E+10 | 0.57 | 11706.44 | 1.95 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.217571E+10 | 0.45 | 2813.04 | 09-JAN-07:02 | 0.89 |
February | 0.160797E+10 | 0.37 | 2813.04 | 03-FEB-06:02 | 0.90 |
March | 0.163794E+10 | 0.35 | 2813.04 | 01-MAR-07:01 | 0.89 |
April | 0.186686E+10 | 0.35 | 8203.76 | 18-APR-15:00 | 1.67 |
May | 0.260271E+10 | 0.40 | 8455.30 | 30-MAY-15:30 | 1.71 |
June | 0.466474E+10 | 0.54 | 10578.76 | 26-JUN-06:03 | 1.97 |
July | 0.508055E+10 | 0.55 | 10578.76 | 03-JUL-15:30 | 1.97 |
August | 0.499952E+10 | 0.55 | 10578.76 | 04-AUG-07:05 | 1.96 |
September | 0.311137E+10 | 0.43 | 10079.23 | 08-SEP-16:00 | 1.91 |
October | 0.152595E+10 | 0.31 | 2813.04 | 16-OCT-06:01 | 0.89 |
November | 0.153340E+10 | 0.34 | 2813.04 | 22-NOV-07:01 | 0.89 |
December | 0.179635E+10 | 0.38 | 2813.04 | 01-DEC-07:01 | 0.89 |
Annual Sum or Average | 0.326031E+11 | 0.42 | |||
Minimum of Months | 0.152595E+10 | 0.31 | 2813.04 | 0.89 | |
Maximum of Months | 0.508055E+10 | 0.55 | 10578.76 | 1.97 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.262148E+10 | 0.48 | 2859.80 | 02-JAN-05:01 | 0.83 |
February | 0.205892E+10 | 0.44 | 2859.80 | 01-FEB-05:01 | 0.83 |
March | 0.183860E+10 | 0.37 | 2859.80 | 01-MAR-06:01 | 0.83 |
April | 0.192154E+10 | 0.35 | 7888.47 | 18-APR-15:00 | 1.49 |
May | 0.247621E+10 | 0.37 | 8512.00 | 31-MAY-15:00 | 1.56 |
June | 0.436101E+10 | 0.49 | 11704.53 | 26-JUN-15:30 | 1.91 |
July | 0.463160E+10 | 0.49 | 10464.36 | 03-JUL-15:20 | 1.78 |
August | 0.446918E+10 | 0.48 | 11645.00 | 04-AUG-15:30 | 1.90 |
September | 0.276962E+10 | 0.39 | 9710.13 | 08-SEP-15:50 | 1.69 |
October | 0.154969E+10 | 0.30 | 2859.80 | 13-OCT-06:01 | 0.83 |
November | 0.188348E+10 | 0.38 | 2859.80 | 10-NOV-07:01 | 0.83 |
December | 0.231505E+10 | 0.44 | 2859.80 | 01-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.328964E+11 | 0.41 | |||
Minimum of Months | 0.154969E+10 | 0.30 | 2859.80 | 0.83 | |
Maximum of Months | 0.463160E+10 | 0.49 | 11704.53 | 1.91 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:03 | 0.22 | 0.22 | 57.04 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:01 | 0.22 | 0.22 | 55.66 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:01 | 0.22 | 0.22 | 54.96 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:01 | 0.22 | 0.22 | 56.11 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:03 | 0.22 | 0.22 | 55.88 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 56.50 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 55.65 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 55.96 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 56.02 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 56.91 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:02 | 0.22 | 0.22 | 55.57 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:01 | 0.22 | 0.22 | 56.74 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 54.96 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.04 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 56.77 | 56.77 | 2082.31 | 7369.40 | 31-JAN-12:19 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 56.09 | 56.09 | 2133.72 | 7414.63 | 16-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 55.49 | 55.49 | 2253.24 | 7404.59 | 01-MAR-12:12 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.59 | 56.59 | 2027.62 | 7200.27 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.56 | 57.56 | 1986.61 | 6830.09 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.97 | 56.97 | 1909.33 | 6418.12 | 01-JUN-11:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.07 | 56.07 | 1659.98 | 5961.48 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.39 | 56.39 | 1780.31 | 5732.80 | 02-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.42 | 56.42 | 1684.97 | 5902.15 | 28-SEP-11:09 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.38 | 56.38 | 1761.22 | 6282.51 | 31-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.04 | 56.04 | 1901.48 | 6708.34 | 30-NOV-12:14 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.11 | 57.11 | 1937.31 | 7092.95 | 29-DEC-12:13 |
Annual Sum or Average | 0.00 | 1925.31 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.49 | 55.49 | 1659.98 | 5732.80 | ||
Maximum of Months | 0.00 | 0.00 | 57.56 | 57.56 | 2253.24 | 7414.63 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.404202E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.264679E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.183798E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.106264E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.769997E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.163800E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.210623E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.212872E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.111446E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.503716E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.149802E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.287701E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.222256E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.503716E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.404202E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.383006E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.223033E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.118177E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.617596E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.636615E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.153990E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.194351E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.184863E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.889213E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.318850E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.142079E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.285169E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.193090E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.318850E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.383006E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.588947E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.375746E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.214131E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.104937E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.671067E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.159464E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.198396E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.184702E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.955960E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.695739E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.259067E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.471769E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.278944E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.671067E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.588947E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.213038E+10 | 0.00 | 0.670604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157865E+10 | 0.00 | 0.440819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167817E+10 | 0.149260E+09 | 0.269597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187643E+10 | 0.507762E+10 | 0.107868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.270343E+10 | 0.139932E+11 | 0.151283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.465232E+10 | 0.451318E+11 | 0.519219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.545286E+10 | 0.645046E+11 | 48050461.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.572421E+10 | 0.634003E+11 | 0.176790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.379753E+10 | 0.251571E+11 | 0.114395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187237E+10 | 0.147437E+10 | 0.414144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167075E+10 | 51298360.69 | 0.225195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173011E+10 | 0.00 | 0.473642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.348672E+11 | 0.218939E+12 | 0.226315E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157865E+10 | 0.00 | 48050461.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.572421E+10 | 0.645046E+11 | 0.670604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.217571E+10 | 0.00 | 0.646597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160797E+10 | 0.00 | 0.402140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163794E+10 | 0.149291E+09 | 0.215913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186686E+10 | 0.559129E+10 | 0.726696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.260271E+10 | 0.146568E+11 | 0.192829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.466474E+10 | 0.433614E+11 | 4923074.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.508055E+10 | 0.595358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.499952E+10 | 0.554431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.311137E+10 | 0.220952E+11 | 0.483684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152595E+10 | 0.131000E+10 | 0.362555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153340E+10 | 59347746.84 | 0.230107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179635E+10 | 0.00 | 0.477585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.326031E+11 | 0.202202E+12 | 0.208808E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.508055E+10 | 0.595358E+11 | 0.646597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.262148E+10 | 0.00 | 0.890172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.205892E+10 | 0.00 | 0.572797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183860E+10 | 0.155519E+09 | 0.315806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192154E+10 | 0.617937E+10 | 0.116644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.247621E+10 | 0.156133E+11 | 0.462754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.436101E+10 | 0.464221E+11 | 75250832.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.463160E+10 | 0.628937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.446918E+10 | 0.572493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.276962E+10 | 0.228681E+11 | 0.139994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154969E+10 | 0.131192E+10 | 0.777862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188348E+10 | 39806746.75 | 0.357540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231505E+10 | 0.00 | 0.686780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.328964E+11 | 0.212733E+12 | 0.303691E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.463160E+10 | 0.628937E+11 | 0.890172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.213038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167817E+10 | 0.00 | 0.00 | 0.00 | 42680195.01 | 0.166590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187643E+10 | 0.00 | 0.00 | 0.00 | 0.131095E+10 | 0.743899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.270343E+10 | 0.00 | 0.00 | 0.00 | 0.356641E+10 | 0.143013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.465232E+10 | 0.00 | 0.00 | 0.00 | 0.112098E+11 | 0.517902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.545286E+10 | 0.00 | 0.00 | 0.00 | 0.155614E+11 | 48050461.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.572421E+10 | 0.00 | 0.00 | 0.00 | 0.153862E+11 | 0.176790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.379753E+10 | 0.00 | 0.00 | 0.00 | 0.636850E+10 | 0.978547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187237E+10 | 0.00 | 0.00 | 0.00 | 0.395034E+09 | 0.276975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167075E+10 | 0.00 | 0.00 | 0.00 | 14826343.88 | 0.132946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.348672E+11 | 0.00 | 0.00 | 0.00 | 0.538558E+11 | 0.133533E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48050461.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.572421E+10 | 0.00 | 0.00 | 0.00 | 0.155614E+11 | 0.382899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.217571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163794E+10 | 0.00 | 0.00 | 0.00 | 42563867.68 | 0.101372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186686E+10 | 0.00 | 0.00 | 0.00 | 0.142603E+10 | 0.288307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.260271E+10 | 0.00 | 0.00 | 0.00 | 0.371881E+10 | 44620389.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.466474E+10 | 0.00 | 0.00 | 0.00 | 0.107342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.508055E+10 | 0.00 | 0.00 | 0.00 | 0.143546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.499952E+10 | 0.00 | 0.00 | 0.00 | 0.134868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.311137E+10 | 0.00 | 0.00 | 0.00 | 0.560976E+10 | 0.171000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152595E+10 | 0.00 | 0.00 | 0.00 | 0.353224E+09 | 0.130932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153340E+10 | 0.00 | 0.00 | 0.00 | 17012273.01 | 0.126575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.326031E+11 | 0.00 | 0.00 | 0.00 | 0.497430E+11 | 0.110744E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.508055E+10 | 0.00 | 0.00 | 0.00 | 0.143546E+11 | 0.361249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.262148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.205892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183860E+10 | 0.00 | 0.00 | 0.00 | 44430081.27 | 0.195301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192154E+10 | 0.00 | 0.00 | 0.00 | 0.157362E+10 | 0.699853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.247621E+10 | 0.00 | 0.00 | 0.00 | 0.397284E+10 | 0.261622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.436101E+10 | 0.00 | 0.00 | 0.00 | 0.115303E+11 | 55130659.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.463160E+10 | 0.00 | 0.00 | 0.00 | 0.152080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.446918E+10 | 0.00 | 0.00 | 0.00 | 0.140010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.276962E+10 | 0.00 | 0.00 | 0.00 | 0.584480E+10 | 0.945187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154969E+10 | 0.00 | 0.00 | 0.00 | 0.356886E+09 | 0.505081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188348E+10 | 0.00 | 0.00 | 0.00 | 11543442.36 | 0.240117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.328964E+11 | 0.00 | 0.00 | 0.00 | 0.525434E+11 | 0.193504E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.463160E+10 | 0.00 | 0.00 | 0.00 | 0.152080E+11 | 0.562732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.198128E+11 | 0.00 | 0.00 | 416188.08 | 0.00 | 0.868556E+09 | 0.444943E+09 | 0.00 | 0.27 |
February | 0.150569E+11 | 0.00 | 0.00 | 1674314.75 | 0.00 | 0.103551E+09 | 0.185875E+10 | 0.00 | 0.27 |
March | 0.968481E+10 | 0.00 | 0.00 | 12962897.26 | 0.00 | 3729799.89 | 0.763963E+10 | 0.00 | 0.35 |
April | 0.460442E+10 | 0.234453E+09 | 0.00 | 22124730.87 | 17400080.72 | 0.00 | 0.105914E+11 | 0.00 | 0.47 |
May | 0.118613E+10 | 0.278774E+09 | 0.00 | 35185554.41 | 24802474.13 | 0.00 | 0.155152E+11 | 0.00 | 0.89 |
June | 0.507079E+09 | 0.312429E+10 | 0.00 | 29159660.91 | 0.152474E+09 | 0.00 | 0.101309E+11 | 0.00 | 0.99 |
July | 0.483761E+09 | 0.542607E+10 | 0.00 | 20313296.77 | 0.547011E+09 | 0.00 | 0.424447E+10 | 0.00 | 0.99 |
August | 0.664771E+09 | 0.552577E+10 | 0.00 | 28625997.69 | 0.246585E+09 | 0.00 | 0.646407E+10 | 0.00 | 1.06 |
September | 0.120322E+10 | 0.535334E+09 | 0.00 | 36859628.54 | 61058769.17 | 0.00 | 0.148387E+11 | 0.00 | 0.88 |
October | 0.192533E+10 | 0.00 | 0.00 | 30753154.87 | 575246.50 | 0.00 | 0.156174E+11 | 0.00 | 0.53 |
November | 0.760393E+10 | 0.00 | 0.00 | 15363379.29 | 0.00 | 46105500.29 | 0.943667E+10 | 0.00 | 0.39 |
December | 0.152691E+11 | 0.00 | 0.00 | 2508100.51 | 0.00 | 0.159462E+09 | 0.304807E+10 | 0.00 | 0.27 |
Annual Sum or Average | 0.780023E+11 | 0.151247E+11 | 0.00 | 0.235947E+09 | 0.104991E+10 | 0.118140E+10 | 0.998303E+11 | 0.00 | 0.61 |
Minimum of Months | 0.483761E+09 | 0.00 | 0.00 | 416188.08 | 0.00 | 0.00 | 0.444943E+09 | 0.00 | 0.27 |
Maximum of Months | 0.198128E+11 | 0.552577E+10 | 0.00 | 36859628.54 | 0.547011E+09 | 0.868556E+09 | 0.156174E+11 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818712E+10 | 0.00 | 0.00 | 0.26 |
February | 0.133483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333922E+10 | 0.00 | 0.00 | 0.27 |
March | 0.143220E+11 | 0.00 | 0.00 | 185977.06 | 0.00 | 0.679362E+09 | 0.398538E+09 | 0.00 | 0.31 |
April | 0.856250E+10 | 0.100375E+09 | 0.00 | 4763946.70 | 0.117997E+09 | 97281853.54 | 0.337362E+10 | 0.00 | 0.37 |
May | 0.358713E+10 | 0.213766E+09 | 0.00 | 14898351.65 | 0.110182E+09 | 0.00 | 0.791959E+10 | 0.00 | 0.62 |
June | 0.127692E+10 | 0.240699E+10 | 0.00 | 17051176.93 | 0.174987E+09 | 0.00 | 0.582689E+10 | 0.00 | 0.69 |
July | 0.589685E+09 | 0.419444E+10 | 0.00 | 12723590.57 | 0.479757E+09 | 0.00 | 0.259024E+10 | 0.00 | 0.71 |
August | 0.827988E+09 | 0.405496E+10 | 0.00 | 17539400.08 | 0.235725E+09 | 0.00 | 0.376730E+10 | 0.00 | 0.73 |
September | 0.300471E+10 | 0.403841E+09 | 0.00 | 16195919.89 | 53187088.11 | 0.00 | 0.685910E+10 | 0.00 | 0.57 |
October | 0.863155E+10 | 0.00 | 0.00 | 2504662.24 | 2065895.09 | 497769.90 | 0.278257E+10 | 0.00 | 0.34 |
November | 0.108069E+11 | 0.00 | 0.00 | 838631.16 | 0.00 | 0.180837E+10 | 0.125172E+10 | 0.00 | 0.31 |
December | 0.137028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411323E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.916492E+11 | 0.113744E+11 | 0.00 | 86701656.28 | 0.117390E+10 | 0.182251E+11 | 0.347696E+11 | 0.00 | 0.46 |
Minimum of Months | 0.589685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.143220E+11 | 0.419444E+10 | 0.00 | 17539400.08 | 0.479757E+09 | 0.818712E+10 | 0.791959E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.626783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126682E+11 | 0.00 | 0.00 | 0.24 |
February | 0.756614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758678E+10 | 0.00 | 0.00 | 0.26 |
March | 0.115456E+11 | 0.00 | 0.00 | 78718.04 | 0.00 | 0.270621E+10 | 0.162559E+09 | 0.00 | 0.30 |
April | 0.871204E+10 | 0.112122E+09 | 0.00 | 3126995.23 | 0.135599E+09 | 0.617133E+09 | 0.212153E+10 | 0.00 | 0.37 |
May | 0.451089E+10 | 0.168725E+09 | 0.00 | 12639280.57 | 69071562.31 | 439418.87 | 0.660970E+10 | 0.00 | 0.62 |
June | 0.184245E+10 | 0.228313E+10 | 0.00 | 14091580.66 | 0.267773E+09 | 0.00 | 0.497516E+10 | 0.00 | 0.71 |
July | 0.763963E+09 | 0.433152E+10 | 0.00 | 10067271.76 | 0.606176E+09 | 0.00 | 0.229402E+10 | 0.00 | 0.76 |
August | 0.107620E+10 | 0.373714E+10 | 0.00 | 14430377.70 | 0.424491E+09 | 0.00 | 0.309033E+10 | 0.00 | 0.74 |
September | 0.444549E+10 | 0.333549E+09 | 0.00 | 9863919.79 | 85297132.14 | 27477107.37 | 0.412017E+10 | 0.00 | 0.55 |
October | 0.979973E+10 | 0.00 | 0.00 | 440771.41 | 1335025.28 | 0.250907E+09 | 0.624918E+09 | 0.00 | 0.34 |
November | 0.838041E+10 | 0.00 | 0.00 | 102964.76 | 0.00 | 0.416831E+10 | 0.128676E+09 | 0.00 | 0.29 |
December | 0.716892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.885329E+10 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.720797E+11 | 0.109662E+11 | 0.00 | 64841879.92 | 0.158974E+10 | 0.368787E+11 | 0.241271E+11 | 0.00 | 0.45 |
Minimum of Months | 0.763963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.115456E+11 | 0.433152E+10 | 0.00 | 14430377.70 | 0.606176E+09 | 0.126682E+11 | 0.660970E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 79400896.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640014E+10 | 0.00 | 0.00 | 0.38 |
February | 0.160936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460701E+10 | 0.00 | 0.00 | 0.35 |
March | 0.967665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262122E+10 | 0.00 | 0.00 | 0.35 |
April | 0.148779E+10 | 45061022.50 | 0.00 | 422095.20 | 22528002.00 | 0.972386E+09 | 0.246188E+09 | 0.00 | 0.42 |
May | 0.143284E+10 | 52743481.12 | 0.00 | 2582817.86 | 16035387.02 | 32305323.33 | 0.117469E+10 | 0.00 | 0.72 |
June | 0.540718E+09 | 0.746908E+09 | 0.00 | 3513840.00 | 64518710.31 | 1892496.99 | 0.115336E+10 | 0.00 | 0.93 |
July | 0.227719E+09 | 0.133890E+10 | 0.00 | 2497744.89 | 0.136516E+09 | 0.00 | 0.540811E+09 | 0.00 | 0.99 |
August | 0.355030E+09 | 0.112299E+10 | 0.00 | 3187131.66 | 0.104773E+09 | 0.00 | 0.647503E+09 | 0.00 | 0.92 |
September | 0.127632E+10 | 0.100385E+09 | 0.00 | 1641090.48 | 18421540.52 | 0.131235E+09 | 0.581565E+09 | 0.00 | 0.61 |
October | 0.172445E+10 | 0.00 | 0.00 | 12317.24 | 319008.74 | 0.817960E+09 | 21513782.70 | 0.00 | 0.38 |
November | 0.808997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255399E+10 | 0.00 | 0.00 | 0.36 |
December | 44356903.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468344E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.910623E+10 | 0.340698E+10 | 0.00 | 13857037.32 | 0.363112E+09 | 0.228216E+11 | 0.436563E+10 | 0.00 | 0.56 |
Minimum of Months | 44356903.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.172445E+10 | 0.133890E+10 | 0.00 | 3513840.00 | 0.136516E+09 | 0.640014E+10 | 0.117469E+10 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.156424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430651E+10 | 0.00 | 0.00 | 0.43 |
February | 0.370472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308993E+10 | 0.00 | 0.00 | 0.43 |
March | 0.135509E+10 | 0.00 | 0.00 | 84262.29 | 0.00 | 0.166890E+10 | 81423191.62 | 0.00 | 0.49 |
April | 0.127544E+10 | 68098649.58 | 0.00 | 988312.68 | 13801270.07 | 0.680735E+09 | 0.613836E+09 | 0.00 | 0.65 |
May | 0.983987E+09 | 64088893.56 | 0.00 | 3681606.74 | 7924362.30 | 7605669.04 | 0.170187E+10 | 0.00 | 1.17 |
June | 0.487715E+09 | 0.711320E+09 | 0.00 | 4183130.93 | 42990706.04 | 1844843.93 | 0.138905E+10 | 0.00 | 1.54 |
July | 0.156470E+09 | 0.121445E+10 | 0.00 | 3543480.47 | 0.100033E+09 | 0.00 | 0.727069E+09 | 0.00 | 1.68 |
August | 0.271742E+09 | 0.102293E+10 | 0.00 | 4055524.45 | 82335025.18 | 0.00 | 0.844098E+09 | 0.00 | 1.48 |
September | 0.922446E+09 | 0.107153E+09 | 0.00 | 2872487.78 | 12511862.15 | 70145432.57 | 0.929507E+09 | 0.00 | 1.03 |
October | 0.175596E+10 | 0.00 | 0.00 | 106836.17 | 284891.31 | 0.484728E+09 | 47509351.55 | 0.00 | 0.54 |
November | 0.780820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197706E+10 | 0.00 | 0.00 | 0.48 |
December | 0.123470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355448E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.864003E+10 | 0.318804E+10 | 0.00 | 19515641.51 | 0.259881E+09 | 0.158419E+11 | 0.633436E+10 | 0.00 | 0.86 |
Minimum of Months | 0.123470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.175596E+10 | 0.121445E+10 | 0.00 | 4183130.93 | 0.100033E+09 | 0.430651E+10 | 0.170187E+10 | 0.00 | 1.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.123846E+10 | 0.00 | 0.00 | 465111.62 | 0.00 | 0.434659E+10 | 0.268464E+09 | 0.00 | 0.35 |
February | 0.128264E+10 | 0.00 | 0.00 | 896941.06 | 0.00 | 0.286503E+10 | 0.449614E+09 | 0.00 | 0.37 |
March | 0.148600E+10 | 0.00 | 0.00 | 1825742.20 | 0.00 | 0.184364E+10 | 0.103622E+10 | 0.00 | 0.45 |
April | 0.136808E+10 | 0.123075E+09 | 0.00 | 3074616.32 | 14610571.87 | 0.816724E+09 | 0.161809E+10 | 0.00 | 0.63 |
May | 0.129933E+10 | 81505846.61 | 0.00 | 4827109.25 | 10306864.50 | 33969215.80 | 0.212997E+10 | 0.00 | 0.97 |
June | 0.650204E+09 | 0.875580E+09 | 0.00 | 4257084.10 | 73686940.34 | 3576811.77 | 0.141171E+10 | 0.00 | 1.13 |
July | 0.274122E+09 | 0.163986E+10 | 0.00 | 3333793.26 | 0.128433E+09 | 0.00 | 0.676800E+09 | 0.00 | 1.24 |
August | 0.350784E+09 | 0.146997E+10 | 0.00 | 5503042.87 | 89138333.46 | 0.00 | 0.112315E+10 | 0.00 | 1.29 |
September | 0.111583E+10 | 0.217257E+09 | 0.00 | 5835163.78 | 7689424.54 | 83771649.92 | 0.178715E+10 | 0.00 | 1.05 |
October | 0.155867E+10 | 0.00 | 0.00 | 4064122.15 | 353906.37 | 0.422417E+09 | 0.189582E+10 | 0.00 | 0.63 |
November | 0.132199E+10 | 0.00 | 0.00 | 875241.69 | 0.00 | 0.194783E+10 | 0.506209E+09 | 0.00 | 0.43 |
December | 0.711509E+09 | 0.00 | 0.00 | 1027752.03 | 0.00 | 0.371894E+10 | 0.536626E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.126576E+11 | 0.440725E+10 | 0.00 | 35985720.33 | 0.324219E+09 | 0.160825E+11 | 0.134398E+11 | 0.00 | 0.74 |
Minimum of Months | 0.274122E+09 | 0.00 | 0.00 | 465111.62 | 0.00 | 0.00 | 0.268464E+09 | 0.00 | 0.35 |
Maximum of Months | 0.155867E+10 | 0.163986E+10 | 0.00 | 5835163.78 | 0.128433E+09 | 0.434659E+10 | 0.212997E+10 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.269624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461724E+10 | 0.00 | 0.00 | 0.47 |
February | 0.464033E+09 | 0.00 | 0.00 | 41734.42 | 0.00 | 0.336620E+10 | 38805337.85 | 0.00 | 0.48 |
March | 0.116328E+10 | 0.00 | 0.00 | 310613.74 | 0.00 | 0.208199E+10 | 0.211929E+09 | 0.00 | 0.54 |
April | 0.131189E+10 | 49616708.01 | 0.00 | 1652393.23 | 21443269.16 | 0.761765E+09 | 0.908767E+09 | 0.00 | 0.75 |
May | 0.138825E+10 | 52608367.96 | 0.00 | 3327859.25 | 16394918.23 | 33977684.20 | 0.137086E+10 | 0.00 | 1.20 |
June | 0.615983E+09 | 0.632901E+09 | 0.00 | 3506030.25 | 56710698.08 | 4410182.10 | 0.111037E+10 | 0.00 | 1.45 |
July | 0.245126E+09 | 0.135413E+10 | 0.00 | 3103474.62 | 81305872.43 | 0.00 | 0.521753E+09 | 0.00 | 1.55 |
August | 0.348510E+09 | 0.994222E+09 | 0.00 | 3894021.45 | 98411379.49 | 0.00 | 0.734671E+09 | 0.00 | 1.49 |
September | 0.123722E+10 | 0.114412E+09 | 0.00 | 2384264.38 | 12692146.82 | 0.130594E+09 | 0.704253E+09 | 0.00 | 1.06 |
October | 0.157211E+10 | 0.00 | 0.00 | 729252.30 | 316409.74 | 0.634041E+09 | 0.415046E+09 | 0.00 | 0.63 |
November | 0.908545E+09 | 0.00 | 0.00 | 88359.57 | 0.00 | 0.210933E+10 | 55896162.67 | 0.00 | 0.53 |
December | 0.340982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366109E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.986555E+10 | 0.319789E+10 | 0.00 | 19038003.21 | 0.287275E+09 | 0.174006E+11 | 0.607235E+10 | 0.00 | 0.89 |
Minimum of Months | 0.245126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.157211E+10 | 0.135413E+10 | 0.00 | 3894021.45 | 98411379.49 | 0.461724E+10 | 0.137086E+10 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624445E+10 | 0.00 | 0.00 | 0.37 |
February | 0.100141E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461870E+10 | 0.00 | 0.00 | 0.34 |
March | 0.818564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289107E+10 | 0.00 | 0.00 | 0.34 |
April | 0.138643E+10 | 15092930.37 | 0.00 | 29657.12 | 26499216.28 | 0.121242E+10 | 25432892.73 | 0.00 | 0.36 |
May | 0.190288E+10 | 36535512.53 | 0.00 | 390075.06 | 8074742.21 | 41720428.99 | 0.283714E+09 | 0.00 | 0.55 |
June | 0.713651E+09 | 0.544544E+09 | 0.00 | 2263561.38 | 44797313.75 | 0.00 | 0.709942E+09 | 0.00 | 0.68 |
July | 0.287780E+09 | 0.954185E+09 | 0.00 | 1950240.51 | 0.129181E+09 | 0.00 | 0.413368E+09 | 0.00 | 0.75 |
August | 0.418657E+09 | 0.974286E+09 | 0.00 | 2736055.68 | 79740757.97 | 0.00 | 0.607904E+09 | 0.00 | 0.78 |
September | 0.139416E+10 | 0.101814E+09 | 0.00 | 1882476.99 | 14089109.79 | 15624507.20 | 0.751414E+09 | 0.00 | 0.59 |
October | 0.253565E+10 | 0.00 | 0.00 | 5521.59 | 131151.39 | 0.160061E+09 | 31428078.06 | 0.00 | 0.38 |
November | 0.130078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213920E+10 | 0.00 | 0.00 | 0.35 |
December | 68598674.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462651E+10 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.110377E+11 | 0.262646E+10 | 0.00 | 9257588.32 | 0.302514E+09 | 0.219498E+11 | 0.282320E+10 | 0.00 | 0.48 |
Minimum of Months | 68598674.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.253565E+10 | 0.974286E+09 | 0.00 | 2736055.68 | 0.129181E+09 | 0.624445E+10 | 0.751414E+09 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.170582E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407388E+10 | 0.00 | 0.00 | 0.39 |
February | 0.316750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295304E+10 | 0.00 | 0.00 | 0.38 |
March | 0.115006E+10 | 0.00 | 0.00 | 4613.07 | 0.00 | 0.163136E+10 | 10364188.20 | 0.00 | 0.41 |
April | 0.113833E+10 | 43453345.75 | 0.00 | 475425.54 | 3036994.72 | 0.666913E+09 | 0.281774E+09 | 0.00 | 0.48 |
May | 0.974768E+09 | 47318714.00 | 0.00 | 2090761.99 | 5570682.13 | 981703.15 | 0.100923E+10 | 0.00 | 0.82 |
June | 0.464752E+09 | 0.583665E+09 | 0.00 | 3359278.49 | 21487594.41 | 0.00 | 0.105219E+10 | 0.00 | 1.18 |
July | 0.168255E+09 | 0.963402E+09 | 0.00 | 3085245.01 | 83564521.12 | 0.00 | 0.615279E+09 | 0.00 | 1.32 |
August | 0.232983E+09 | 0.936423E+09 | 0.00 | 3984383.88 | 48296998.03 | 0.00 | 0.875613E+09 | 0.00 | 1.28 |
September | 0.780271E+09 | 0.110940E+09 | 0.00 | 3509143.96 | 9243305.53 | 3763099.64 | 0.122147E+10 | 0.00 | 0.96 |
October | 0.183028E+10 | 0.00 | 0.00 | 229778.64 | 100403.02 | 46945482.60 | 0.223878E+09 | 0.00 | 0.46 |
November | 0.105265E+10 | 0.00 | 0.00 | 1146.08 | 0.00 | 0.150344E+10 | 5501132.91 | 0.00 | 0.41 |
December | 0.249637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319813E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.852932E+10 | 0.268520E+10 | 0.00 | 16739776.65 | 0.171300E+09 | 0.140784E+11 | 0.529530E+10 | 0.00 | 0.71 |
Minimum of Months | 0.168255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.183028E+10 | 0.963402E+09 | 0.00 | 3984383.88 | 83564521.12 | 0.407388E+10 | 0.122147E+10 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.176624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.886898E+10 | 0.00 | 0.00 | 0.51 |
February | 0.252731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605648E+10 | 0.00 | 0.00 | 0.45 |
March | 0.594815E+09 | 0.00 | 0.00 | 107458.03 | 0.00 | 0.424572E+10 | 74104242.85 | 0.00 | 0.44 |
April | 0.744974E+09 | 94028573.51 | 0.00 | 400379.14 | 5039555.51 | 0.222344E+10 | 0.222044E+09 | 0.00 | 0.45 |
May | 0.151586E+10 | 68529454.48 | 0.00 | 740531.69 | 5503135.57 | 0.551219E+09 | 0.270192E+09 | 0.00 | 0.59 |
June | 0.766106E+09 | 0.726373E+09 | 0.00 | 1763483.09 | 51922259.47 | 0.211313E+09 | 0.453548E+09 | 0.00 | 0.74 |
July | 0.313443E+09 | 0.127166E+10 | 0.00 | 1888866.41 | 0.131931E+09 | 20659416.66 | 0.353945E+09 | 0.00 | 0.86 |
August | 0.347251E+09 | 0.142781E+10 | 0.00 | 4068029.46 | 70670254.79 | 81794502.60 | 0.778956E+09 | 0.00 | 1.02 |
September | 0.106967E+10 | 0.238233E+09 | 0.00 | 4098466.93 | 8472601.59 | 0.391690E+09 | 0.110944E+10 | 0.00 | 0.87 |
October | 0.155847E+10 | 54838.79 | 0.00 | 1356252.08 | 92430.12 | 0.991409E+09 | 0.735270E+09 | 0.00 | 0.48 |
November | 0.863498E+09 | 0.00 | 0.00 | 408245.23 | 0.00 | 0.344739E+10 | 0.256826E+09 | 0.00 | 0.46 |
December | 0.334872E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648029E+10 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.853831E+10 | 0.382669E+10 | 0.00 | 14831712.08 | 0.273632E+09 | 0.335704E+11 | 0.425433E+10 | 0.00 | 0.61 |
Minimum of Months | 0.176624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20659416.66 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.155847E+10 | 0.142781E+10 | 0.00 | 4098466.93 | 0.131931E+09 | 0.886898E+10 | 0.110944E+10 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.174701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436991E+10 | 0.00 | 0.00 | 0.42 |
February | 0.348088E+09 | 0.00 | 0.00 | 6232.73 | 0.00 | 0.318909E+10 | 6524479.61 | 0.00 | 0.41 |
March | 0.107570E+10 | 0.00 | 0.00 | 9656.63 | 0.00 | 0.190936E+10 | 26078563.45 | 0.00 | 0.44 |
April | 0.124058E+10 | 30443082.67 | 0.00 | 683332.56 | 13511194.81 | 0.648441E+09 | 0.389102E+09 | 0.00 | 0.53 |
May | 0.132922E+10 | 44153152.85 | 0.00 | 1378394.86 | 6502664.18 | 16871156.40 | 0.617500E+09 | 0.00 | 0.80 |
June | 0.556616E+09 | 0.527920E+09 | 0.00 | 2818370.33 | 26587119.36 | 0.00 | 0.797765E+09 | 0.00 | 1.09 |
July | 0.207113E+09 | 0.105630E+10 | 0.00 | 2525603.12 | 63287861.32 | 0.00 | 0.442432E+09 | 0.00 | 1.19 |
August | 0.287339E+09 | 0.950751E+09 | 0.00 | 3607948.27 | 42505055.50 | 0.00 | 0.736301E+09 | 0.00 | 1.27 |
September | 0.998420E+09 | 0.122683E+09 | 0.00 | 2638958.24 | 7874802.22 | 17655965.44 | 0.914854E+09 | 0.00 | 0.92 |
October | 0.187150E+10 | 0.00 | 0.00 | 763846.67 | 108367.89 | 71822442.85 | 0.397157E+09 | 0.00 | 0.53 |
November | 0.115619E+10 | 0.00 | 0.00 | 73469.59 | 0.00 | 0.157292E+10 | 45426787.67 | 0.00 | 0.45 |
December | 0.343661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333084E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.958913E+10 | 0.273225E+10 | 0.00 | 14505813.01 | 0.160377E+09 | 0.151269E+11 | 0.437314E+10 | 0.00 | 0.71 |
Minimum of Months | 0.174701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.187150E+10 | 0.105630E+10 | 0.00 | 3607948.27 | 63287861.32 | 0.436991E+10 | 0.914854E+09 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588322E+10 | 0.00 | 0.00 | 0.35 |
February | 0.253311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420437E+10 | 0.00 | 0.00 | 0.32 |
March | 0.128448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210651E+10 | 0.00 | 0.00 | 0.32 |
April | 0.165829E+10 | 47571712.37 | 0.00 | 567402.93 | 11190343.11 | 0.588692E+09 | 0.298632E+09 | 0.00 | 0.38 |
May | 0.108640E+10 | 69459058.14 | 0.00 | 3162145.50 | 22150322.62 | 7701755.57 | 0.140534E+10 | 0.00 | 0.68 |
June | 0.398240E+09 | 0.796539E+09 | 0.00 | 4017317.50 | 36986124.45 | 0.00 | 0.125093E+10 | 0.00 | 0.88 |
July | 0.168826E+09 | 0.130118E+10 | 0.00 | 2897893.84 | 0.101116E+09 | 0.00 | 0.573331E+09 | 0.00 | 0.90 |
August | 0.282076E+09 | 0.122800E+10 | 0.00 | 3343240.23 | 53218810.06 | 0.00 | 0.702888E+09 | 0.00 | 0.87 |
September | 0.114757E+10 | 0.123921E+09 | 0.00 | 2181259.78 | 9962322.86 | 30575977.94 | 0.823436E+09 | 0.00 | 0.59 |
October | 0.208398E+10 | 0.00 | 0.00 | 81537.90 | 444228.97 | 0.275394E+09 | 87628333.54 | 0.00 | 0.35 |
November | 0.106602E+10 | 0.00 | 0.00 | 99.33 | 0.00 | 0.213061E+10 | 4982315.45 | 0.00 | 0.33 |
December | 51135947.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437599E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.960989E+10 | 0.356667E+10 | 0.00 | 16250897.00 | 0.235068E+09 | 0.196031E+11 | 0.514717E+10 | 0.00 | 0.52 |
Minimum of Months | 51135947.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.208398E+10 | 0.130118E+10 | 0.00 | 4017317.50 | 0.101116E+09 | 0.588322E+10 | 0.140534E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.211082E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457805E+10 | 0.00 | 0.00 | 0.45 |
February | 0.594508E+09 | 0.00 | 0.00 | 979.96 | 0.00 | 0.314257E+10 | 2815085.56 | 0.00 | 0.45 |
March | 0.166817E+10 | 0.00 | 0.00 | 178587.20 | 0.00 | 0.157753E+10 | 0.122170E+09 | 0.00 | 0.51 |
April | 0.156546E+10 | 61510036.37 | 0.00 | 1197063.91 | 9390485.00 | 0.478759E+09 | 0.692700E+09 | 0.00 | 0.66 |
May | 0.931662E+09 | 78228791.45 | 0.00 | 4014676.92 | 15336921.43 | 867325.48 | 0.182453E+10 | 0.00 | 1.16 |
June | 0.476770E+09 | 0.723743E+09 | 0.00 | 4284663.03 | 28994740.28 | 0.00 | 0.140332E+10 | 0.00 | 1.45 |
July | 0.159796E+09 | 0.115285E+10 | 0.00 | 3748018.62 | 88371350.87 | 0.00 | 0.739214E+09 | 0.00 | 1.55 |
August | 0.265408E+09 | 0.105005E+10 | 0.00 | 4062806.33 | 58212941.66 | 0.00 | 0.912512E+09 | 0.00 | 1.40 |
September | 0.101781E+10 | 0.118363E+09 | 0.00 | 3374302.65 | 8598358.55 | 20879652.12 | 0.112761E+10 | 0.00 | 1.04 |
October | 0.215106E+10 | 0.00 | 0.00 | 199534.61 | 447278.23 | 0.183453E+09 | 0.142696E+09 | 0.00 | 0.56 |
November | 0.106957E+10 | 0.00 | 0.00 | 12672.97 | 0.00 | 0.194296E+10 | 13872969.69 | 0.00 | 0.50 |
December | 0.274501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370274E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.103858E+11 | 0.318475E+10 | 0.00 | 21073306.20 | 0.209352E+09 | 0.156278E+11 | 0.698144E+10 | 0.00 | 0.85 |
Minimum of Months | 0.159796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.215106E+10 | 0.115285E+10 | 0.00 | 4284663.03 | 88371350.87 | 0.457805E+10 | 0.182453E+10 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.137587E+10 | 0.00 | 0.00 | 693504.37 | 0.00 | 0.409751E+10 | 0.423118E+09 | 0.00 | 0.35 |
February | 0.150600E+10 | 0.00 | 0.00 | 1105427.78 | 0.00 | 0.260117E+10 | 0.552252E+09 | 0.00 | 0.36 |
March | 0.176486E+10 | 0.00 | 0.00 | 2320521.12 | 0.00 | 0.150383E+10 | 0.121014E+10 | 0.00 | 0.46 |
April | 0.168021E+10 | 0.125450E+09 | 0.00 | 3313292.51 | 8897467.64 | 0.484094E+09 | 0.158536E+10 | 0.00 | 0.61 |
May | 0.108703E+10 | 0.110485E+09 | 0.00 | 5146665.60 | 17357198.82 | 9346611.07 | 0.222665E+10 | 0.00 | 0.94 |
June | 0.526598E+09 | 0.933756E+09 | 0.00 | 4571758.23 | 45130893.05 | 0.00 | 0.143237E+10 | 0.00 | 1.05 |
July | 0.235381E+09 | 0.157504E+10 | 0.00 | 3334200.57 | 0.108541E+09 | 0.00 | 0.635575E+09 | 0.00 | 1.10 |
August | 0.328473E+09 | 0.158346E+10 | 0.00 | 5155015.59 | 56237126.65 | 0.00 | 0.105520E+10 | 0.00 | 1.20 |
September | 0.101360E+10 | 0.254179E+09 | 0.00 | 6225635.14 | 8471135.89 | 23873785.12 | 0.206620E+10 | 0.00 | 1.03 |
October | 0.174742E+10 | 359748.77 | 0.00 | 5187525.59 | 288081.71 | 0.148527E+09 | 0.223923E+10 | 0.00 | 0.66 |
November | 0.164095E+10 | 0.00 | 0.00 | 1288744.41 | 0.00 | 0.156818E+10 | 0.688677E+09 | 0.00 | 0.43 |
December | 0.825260E+09 | 0.00 | 0.00 | 1438120.17 | 0.00 | 0.352198E+10 | 0.771153E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.137316E+11 | 0.458273E+10 | 0.00 | 39780411.08 | 0.244923E+09 | 0.139585E+11 | 0.148859E+11 | 0.00 | 0.71 |
Minimum of Months | 0.235381E+09 | 0.00 | 0.00 | 693504.37 | 0.00 | 0.00 | 0.423118E+09 | 0.00 | 0.35 |
Maximum of Months | 0.176486E+10 | 0.158346E+10 | 0.00 | 6225635.14 | 0.108541E+09 | 0.409751E+10 | 0.223923E+10 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.441891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458919E+10 | 0.00 | 0.00 | 0.47 |
February | 0.721518E+09 | 0.00 | 0.00 | 53844.92 | 0.00 | 0.317511E+10 | 46547923.51 | 0.00 | 0.47 |
March | 0.151254E+10 | 0.00 | 0.00 | 395295.17 | 0.00 | 0.179608E+10 | 0.233634E+09 | 0.00 | 0.54 |
April | 0.158860E+10 | 51224052.84 | 0.00 | 1721955.96 | 12692479.26 | 0.482357E+09 | 0.894503E+09 | 0.00 | 0.72 |
May | 0.121277E+10 | 72806241.88 | 0.00 | 3366367.80 | 22294001.28 | 10586172.15 | 0.140010E+10 | 0.00 | 1.13 |
June | 0.554300E+09 | 0.681165E+09 | 0.00 | 3662824.83 | 32759845.05 | 0.00 | 0.107724E+10 | 0.00 | 1.34 |
July | 0.244870E+09 | 0.127330E+10 | 0.00 | 2904731.76 | 57210812.93 | 0.00 | 0.456660E+09 | 0.00 | 1.36 |
August | 0.333607E+09 | 0.107769E+10 | 0.00 | 3576584.82 | 54911673.62 | 0.00 | 0.699427E+09 | 0.00 | 1.36 |
September | 0.126107E+10 | 0.140838E+09 | 0.00 | 2464447.64 | 7243179.41 | 39429018.90 | 0.800415E+09 | 0.00 | 1.01 |
October | 0.200683E+10 | 0.00 | 0.00 | 947239.10 | 467963.29 | 0.229728E+09 | 0.466346E+09 | 0.00 | 0.63 |
November | 0.122897E+10 | 0.00 | 0.00 | 104097.06 | 0.00 | 0.189845E+10 | 61450285.63 | 0.00 | 0.53 |
December | 0.446318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369931E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.115533E+11 | 0.329702E+10 | 0.00 | 19197389.06 | 0.187580E+09 | 0.159202E+11 | 0.613632E+10 | 0.00 | 0.84 |
Minimum of Months | 0.244870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.200683E+10 | 0.127330E+10 | 0.00 | 3662824.83 | 57210812.93 | 0.458919E+10 | 0.140010E+10 | 0.00 | 1.36 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.221098E+12 | 0.478857E+11 | 0.00 | 0.148612E+12 | 0.225123E+11 |
February | 0.236759E+12 | 0.360783E+11 | 0.00 | 0.136694E+12 | 0.151188E+11 |
March | 0.334450E+12 | 0.319061E+11 | 0.00 | 0.159900E+12 | 0.903509E+10 |
April | 0.385490E+12 | 0.194431E+11 | 0.00 | 0.171604E+12 | 0.242583E+11 |
May | 0.434404E+12 | 0.109728E+11 | 0.00 | 0.208865E+12 | 0.556294E+11 |
June | 0.447133E+12 | 0.254486E+10 | 0.00 | 0.106762E+12 | 0.168396E+12 |
July | 0.449199E+12 | -23201136.0 | 0.00 | 0.408011E+11 | 0.232058E+12 |
August | 0.393698E+12 | 0.207982E+10 | 0.00 | 0.828917E+11 | 0.218967E+12 |
September | 0.284471E+12 | 0.947659E+10 | 0.00 | 0.173534E+12 | 0.881767E+11 |
October | 0.226995E+12 | 0.196874E+11 | 0.00 | 0.189130E+12 | 0.680536E+10 |
November | 0.149529E+12 | 0.301140E+11 | 0.00 | 0.150078E+12 | 0.802395E+10 |
December | 0.129948E+12 | 0.401461E+11 | 0.00 | 0.142516E+12 | 0.162946E+11 |
Annual Sum or Average | 0.369317E+13 | 0.250312E+12 | 0.00 | 0.171139E+13 | 0.865275E+12 |
Minimum of Months | 0.129948E+12 | -23201136.0 | 0.00 | 0.408011E+11 | 0.680536E+10 |
Maximum of Months | 0.449199E+12 | 0.478857E+11 | 0.00 | 0.208865E+12 | 0.232058E+12 |