Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2023-10-16 08:35:16
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2372.54 | 476.20 | 476.20 |
Net Site Energy | 2372.54 | 476.20 | 476.20 |
Total Source Energy | 7335.06 | 1472.26 | 1472.26 |
Net Source Energy | 7335.06 | 1472.26 | 1472.26 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 971.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 279.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 188.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 85.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2286.72 | 85.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 971.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 279.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 72.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 188.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 85.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 971.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 279.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 72.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 188.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 85.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 232.79 | 17.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 458.98 | 17.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 232.79 | 17.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 458.98 | 17.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2286.716 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2286.716 | 100.00 |
Total On-Site and Utility Electric Sources | 2286.716 | 100.00 |
Total Electricity End Uses | 2286.716 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 896.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2790.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.5763 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 7.5763 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 7.5763 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 13-JUN-15:09 | 12-JAN-12:09 | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 98545.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 23688.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 43769.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 920.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 17065.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8618.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 183990.18 | 8618.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 98545.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 23688.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 7527.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 920.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 17065.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8618.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3076.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 886.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 228.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2413.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 41.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 596.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 93.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7242.03 | 93.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 617.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 177.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 119.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1453.58 | 18.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 617.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 177.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 119.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1453.58 | 18.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.81 | 0.266483 | 0.276000 | 0.776219 | 0.710623 | 0.500000 | 0.001430 |
CORE_MID VAV BOX COMPONENT | 2.06 | 0.363520 | 0.359000 | 0.740135 | 0.969388 | 0.500000 | 0.001048 |
CORE_TOP VAV BOX COMPONENT | 2.26 | 0.331013 | 0.344000 | 0.778859 | 0.882702 | 0.500000 | 0.001151 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.743741 | 0.212428 | 0.221000 | 0.164367 | 0.566476 | 0.500000 | 0.001794 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.658581 | 0.151875 | 0.200000 | 0.131716 | 0.404999 | 0.500000 | 0.002509 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.724955 | 0.217933 | 0.227000 | 0.164565 | 0.581154 | 0.500000 | 0.001748 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.766449 | 0.130492 | 0.200000 | 0.153290 | 0.347978 | 0.500000 | 0.002920 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.621248 | 0.254313 | 0.263000 | 0.163388 | 0.678169 | 0.500000 | 0.001498 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.586810 | 0.170450 | 0.200000 | 0.117362 | 0.454533 | 0.500000 | 0.002235 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.604199 | 0.261489 | 0.270000 | 0.163134 | 0.697305 | 0.500000 | 0.001457 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.629085 | 0.158985 | 0.200000 | 0.125817 | 0.423961 | 0.500000 | 0.002396 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.627565 | 0.251753 | 0.249000 | 0.156264 | 0.671342 | 0.500000 | 0.001513 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.625580 | 0.159886 | 0.200000 | 0.125116 | 0.426364 | 0.500000 | 0.002383 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.611657 | 0.258301 | 0.255000 | 0.155973 | 0.688803 | 0.500000 | 0.001475 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.677791 | 0.147561 | 0.200000 | 0.135558 | 0.393495 | 0.500000 | 0.002582 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25912.60 |
CORE_MID VAV BOX REHEAT COIL | 24708.01 |
CORE_TOP VAV BOX REHEAT COIL | 26000.72 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 5487.07 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 4397.10 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 5493.69 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 5117.29 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5454.40 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3917.91 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 5445.91 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4200.16 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 5216.57 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 4176.76 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 5206.85 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 4525.35 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.63 | 1.35 | 5.25 | 1.35 | 4.84 | 4.84 | 0.300000 | 0.277999 | 4.84 |
PACU_VAV_MID | 2.30 | 1.31 | 4.60 | 1.31 | 4.14 | 4.14 | 0.300000 | 0.317424 | 4.14 |
PACU_VAV_TOP | 2.58 | 1.39 | 5.16 | 1.39 | 4.96 | 4.96 | 0.300000 | 0.280924 | 4.96 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.84 |
PACU_VAV_MID_OA_CONTROLLER | 4.14 |
PACU_VAV_TOP_OA_CONTROLLER | 4.96 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.84 | 120225.07 | 0.701083 | 1.61 | 40071.02 | 0.701083 |
PACU_VAV_MID COOLING COIL | 4.14 | 102720.83 | 0.701083 | 1.38 | 34236.85 | 0.701083 |
PACU_VAV_TOP COOLING COIL | 4.96 | 123116.84 | 0.701083 | 1.65 | 41034.84 | 0.701083 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 22485.02 |
PACU_VAV_MID HEATING COIL | 19211.30 |
PACU_VAV_TOP HEATING COIL | 23025.85 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.84 |
PACU_VAV_MID FAN | 4.14 |
PACU_VAV_TOP FAN | 4.96 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 32.411 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.029 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 1.013 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.375 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7377 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7531 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4931 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
39 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
40 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
41 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
42 | 7 | -0.27613173E-12 | 0.13648587E-14 | -0.80406974E-13 | 0.78369587E-16 |
43 | 6 | 0.25651297E-07 | 0.27955499E-09 | 0.59014154E-08 | -0.11905989E-12 |
44 | 5 | -0.17465063E-03 | 0.24416492E-05 | -0.90019538E-04 | 0.58421144E-08 |
45 | 4 | 0.27387862 | 0.12098825E-02 | 0.93122264E-01 | -0.31012301E-04 |
46 | 3 | -6.9041115 | 0.38080793E-01 | -2.2314619 | 0.27235146E-01 |
47 | 2 | 39.676056 | 0.13726811 | 14.823303 | -0.32003278 |
48 | 1 | -79.629469 | 0.62686726E-01 | -28.745292 | 1.0590931 |
49 | 0 | 46.824345 | 0.12759187E-02 | 16.300942 | |
50 | 7 | -0.27182421E-12 | 0.13107754E-14 | -0.81108189E-13 | 0.79120162E-16 |
51 | 6 | 0.25844325E-07 | 0.27588229E-09 | 0.59440225E-08 | -0.12008605E-12 |
52 | 5 | -0.17564658E-03 | 0.24062150E-05 | -0.90521036E-04 | 0.58837691E-08 |
53 | 4 | 0.27506755 | 0.11908598E-02 | 0.93548701E-01 | -0.31177608E-04 |
54 | 3 | -6.9277136 | 0.37441415E-01 | -2.2384615 | 0.27350651E-01 |
55 | 2 | 39.753961 | 0.13483533 | 14.852153 | -0.32090009 |
56 | 1 | -79.689237 | 0.61525268E-01 | -28.771196 | 1.0603666 |
57 | 0 | 46.824344 | 0.12512697E-02 | 16.300293 | |
58 | 6 | 0.21465343E-07 | 0.35044740E-09 | 0.49771822E-08 | -0.96989815E-13 |
59 | 5 | -0.15274237E-03 | 0.31655188E-05 | -0.78941554E-04 | 0.49363227E-08 |
60 | 4 | 0.24727258 | 0.16154212E-02 | 0.83601931E-01 | -0.27359285E-04 |
61 | 3 | -6.3748395 | 0.52179222E-01 | -2.0745682 | 0.24648141E-01 |
62 | 2 | 37.927790 | 0.19236366 | 14.173893 | -0.30057625 |
63 | 1 | -78.286849 | 0.89555956E-01 | -28.161423 | 1.0304865 |
64 | 0 | 46.824354 | 0.18576719E-02 | 16.316151 | |
65 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
66 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
67 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
68 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
69 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
70 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
71 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
72 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
73 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
74 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
75 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
76 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
77 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
78 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
79 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
80 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
81 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
82 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
83 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
84 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
85 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
86 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
87 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
88 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
89 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
90 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
91 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
92 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
93 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
94 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
95 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
96 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
97 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
98 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
99 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
100 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
101 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
102 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
103 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
104 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
105 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.2642E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2996E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3112E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3409E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6650E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6856E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4264E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4410E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.6054E-002 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3771E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.8021E-002 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3270E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9758E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8436E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8057E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0496E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.2635E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2972E-003 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3104E-003 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3383E-003 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6642E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6833E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4263E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4409E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2999E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9175E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9376E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.6729E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9445E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4655E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2668E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5265E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1508E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1626E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8818E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8905E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.7046E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7078E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8320E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8371E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2764E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3065E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9641E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9876E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6734E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6866E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4263E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4409E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0637E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1490E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6480E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.0349E-003 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4256E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.0343E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8057E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0496E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2768E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3071E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9645E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9885E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6739E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6882E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4264E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4410E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5110E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0083E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1810E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7770E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1753E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5644E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2668E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5265E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2894E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3089E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0441E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0622E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8511E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8623E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8321E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8372E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.9945E-002 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.0468E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.1702E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.0062E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.3893E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.4368E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.1564E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.4627E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.1821E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.8520E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 2.8403E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.6194E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 2.8691E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.4251E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.1886E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.4843E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3693E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5268E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.9274E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2384E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.6931E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 9.0378E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1564E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4627E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3863E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9386E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.0757E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7186E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.0926E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5194E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.1887E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.4843E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.9942E-002 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.0465E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.1699E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.0059E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.3889E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.4365E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.1562E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.4625E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.1821E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.8519E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 2.8402E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.6193E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 2.8689E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.4249E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.1884E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.4841E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3693E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5267E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.9274E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2383E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.6930E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 9.0371E-003 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1562E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4625E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3863E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9385E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.0756E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7185E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.0924E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5193E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.1884E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4842E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 39015.51573 | 39015.51573 | 2.81239 | 2.81239 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 0.42469 | 00:10:00 | 20.10000 | 1.47983E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 | |
3 | CORE_MID | Cooling | 28635.95196 | 28635.95196 | 2.06166 | 2.06166 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 1233.91418 | 1233.91418 | 5.25010E-002 | 0.42469 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 31147.50931 | 31147.50931 | 2.26412 | 2.26412 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 5004.21517 | 5004.21517 | 0.21016 | 0.42469 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 10230.50914 | 10230.50914 | 0.74374 | 0.74374 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 35.03000 | 1.71578E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 1615.33035 | 1615.33035 | 6.78110E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9059.09671 | 9059.09671 | 0.65858 | 0.65858 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 31.72917 | 1.71515E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 1048.18583 | 1048.18583 | 4.40072E-002 | 5.66790E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 9972.09884 | 9972.09884 | 0.72496 | 0.72496 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 1654.83977 | 1654.83977 | 6.94671E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10542.90878 | 10542.90878 | 0.76645 | 0.76645 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 1048.14912 | 1048.14912 | 4.40057E-002 | 5.66753E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 8546.00890 | 8546.00890 | 0.62125 | 0.62125 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 35.03000 | 1.71578E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 112.82255 | 112.82255 | 4.82747E-003 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8072.30047 | 8072.30047 | 0.58681 | 0.58681 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:40:00 | 31.48833 | 1.71511E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 83.58093 | 83.58093 | 3.57532E-003 | 5.66790E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 8311.47759 | 8311.47759 | 0.60420 | 0.60420 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 35.20000 | 1.71581E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 144.31170 | 144.31170 | 6.17157E-003 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8653.85877 | 8653.85877 | 0.62908 | 0.62908 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:30:00 | 34.35000 | 1.71565E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 83.57873 | 83.57873 | 3.57522E-003 | 5.66753E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8632.59791 | 8632.59791 | 0.62757 | 0.62757 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 34.94500 | 1.71577E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 799.53713 | 799.53713 | 3.38269E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8605.32044 | 8605.32044 | 0.62558 | 0.62558 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:30:00 | 31.24750 | 1.71506E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 529.02247 | 529.02247 | 2.23800E-002 | 5.66790E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 8413.76096 | 8413.76096 | 0.61166 | 0.61166 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 35.20000 | 1.71581E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 839.09803 | 839.09803 | 3.54834E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9323.52468 | 9323.52468 | 0.67779 | 0.67779 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 529.01235 | 529.01235 | 2.23796E-002 | 5.66753E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 81582.50 | 4.84146 | 4.84146 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
3 | PACU_VAV_MID | Cooling | Sensible | 71877.86 | 4.13657 | 4.13657 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
5 | PACU_VAV_TOP | Cooling | Sensible | 83067.87 | 4.95792 | 4.95792 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.81239 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26648 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27600 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77622 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71062 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.42973E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25912.59522 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.06166 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36352 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35900 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.74014 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96939 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04808E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24708.01313 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.26412 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33101 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34400 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77886 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88270 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.15101E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26000.72099 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74374 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21243 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22100 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16437 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56648 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.79355E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5487.07090 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65858 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15187 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13172 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40500 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.50865E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4397.09561 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72496 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21793 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22700 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16456 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58115 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.74824E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5493.68560 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76645 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13049 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15329 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34798 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.91973E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5117.28690 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62125 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25431 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16339 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67817 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49815E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5454.40317 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.58681 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17045 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11736 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45453 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.23526E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 3917.90793 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.60420 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26149 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16313 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69731 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45704E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5445.91035 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62908 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15899 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12582 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42396 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.39645E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4200.15893 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62757 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25175 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24900 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15626 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67134 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.51339E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5216.56881 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62558 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15989 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12512 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42636 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.38294E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4176.76208 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61166 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25830 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25500 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15597 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68880 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47502E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5206.84637 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67779 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14756 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13556 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39350 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.58199E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4525.35100 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.62686 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.34592 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.25373 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.34592 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.84146 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.84146 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.27800 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.30213 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.31305 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.60425 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.31305 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.13657 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.13657 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.31742 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.57893 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39280 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.15785 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.39280 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.95792 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.95792 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.28092 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.84146 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.13657 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.95792 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.84146 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.84146 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 120225.07398 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.61366 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 40071.01716 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 22485.01722 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.84146 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.13657 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.13657 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 102720.83070 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.37872 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34236.85287 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 19211.29736 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.13657 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.95792 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.95792 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 123116.84107 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.65247 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 41034.84313 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 23025.84810 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.95792 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 120028.72 | 409554.98 | 11.65 | 2.97 | 3.34 | 3.52 | 3.64 | 10.14 | 11.39 | 12.03 | 12.43 | 5.5970 | 4.4307 | 2.9816 | 1.2852 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 102553.06 | 349925.57 | 11.65 | 2.97 | 3.34 | 3.52 | 3.64 | 10.14 | 11.39 | 12.03 | 12.43 | 4.7821 | 3.7856 | 2.5475 | 1.0981 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 122915.76 | 419405.98 | 11.65 | 2.97 | 3.34 | 3.52 | 3.64 | 10.14 | 11.39 | 12.03 | 12.43 | 5.7317 | 4.5373 | 3.0533 | 1.3161 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.4022339702 | 0.2783513470 | Pass | Pass | 0.2828007286 | 0.5021654328 | Pass | Fail |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.2468074241E-002 | 7.2564114307E-002 | Pass | Pass | 0.2731925955 | 0.5834087917 | Fail | Fail |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.6864406215E-002 | 5.6462422294E-002 | Pass | Pass | 0.3644945672 | 1.2785611711 | Fail | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.4352540728E-002 | 5.4279804246E-002 | Pass | Pass | 0.3149821294 | 0.6899624635 | Fail | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.2701301487 | 0.2601089224 | Pass | Pass | 0.2276169140 | 0.4163678217 | Pass | Fail |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.2254650545 | 0.2448890569 | Pass | Pass | 0.2325106518 | 0.4246712872 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2410947428 | 0.2753327583 | Pass | Pass | 0.2438184448 | 0.4347132763 | Pass | Fail |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2834409078 | 0.3231049697 | Pass | Fail | 0.2416921250 | 0.4357334867 | Pass | Fail |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2747905472 | 0.3203938113 | Pass | Fail | 0.2781079312 | 0.4994498459 | Pass | Fail |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3003998535 | 0.3426802154 | Pass | Pass | 0.2283725449 | 0.4166832787 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3448165763 | 0.2551931567 | Pass | Pass | 0.2382325216 | 0.4266741542 | Pass | Fail |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3814534120 | 0.2860898245 | Pass | Pass | 0.2461905645 | 0.4373555963 | Pass | Fail |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3537916474 | 0.2737101509 | Pass | Pass | 0.2585728579 | 0.4704707699 | Pass | Fail |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3981544402 | 0.2992031391 | Pass | Pass | 0.2367761147 | 0.4235506534 | Pass | Fail |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2621395697 | 0.2465751139 | Pass | Pass | 0.2361143029 | 0.4283372103 | Pass | Fail |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3106120267 | 0.2921907842 | Pass | Pass | 0.2489336547 | 0.4474687713 | Pass | Fail |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2741688465 | 0.2869218044 | Pass | Pass | 0.2714530818 | 0.5001281411 | Pass | Fail |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3256848755 | 0.3041368728 | Pass | Pass | 0.2283605034 | 0.4172722603 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3232.10 | -168.0 | 0.00 | -1811.7 | 4797.30 | 6049.77 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5047_SHGC_EAST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5047_SHGC_WEST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5047_SHGC_EAST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5047_SHGC_WEST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.869 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 177.99 | 2.869 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.869 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 30.98 | 0.0000 | Y | 9.14 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.05 | 0.0000 | Y | 5.80 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 30.94 | 0.0000 | Y | 9.12 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 30.91 | 0.0000 | Y | 5.77 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 30.96 | 0.0000 | Y | 9.13 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.03 | 0.0000 | Y | 5.79 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 30.92 | 0.0000 | Y | 9.12 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 30.89 | 0.0000 | Y | 5.77 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 30.98 | 0.0000 | Y | 9.14 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.05 | 0.0000 | Y | 5.80 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 30.94 | 0.0000 | Y | 9.12 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 30.91 | 0.0000 | Y | 5.77 |
Interior Lighting Total | 7.5763 | 4982.19 | 37746.71 | 279.90 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 41.93 | 41.93 | 3.34 | |
EXTERIOR_LIGHTS_B | 5132.60 | AstronomicalClock | - | 83.83 | 71.26 | 68.66 | |
Exterior Lighting Total | 5557.43 | 72.00 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 120225.07 | 84287.78 | 35937.29 | 0.70 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 102720.83 | 72015.85 | 30704.98 | 0.70 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 123116.84 | 86315.15 | 36801.69 | 0.70 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 120028.7 | 2.97 | 10.14 | N/A | N/A | 11.65 | |
PACU_VAV_MID COOLING COIL | 102553.1 | 2.97 | 10.14 | N/A | N/A | 11.65 | |
PACU_VAV_TOP COOLING COIL | 122915.8 | 2.97 | 10.14 | N/A | N/A | 11.65 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25912.60 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 24708.01 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 26000.72 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5487.07 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4397.10 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5493.69 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5117.29 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5454.40 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3917.91 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5445.91 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4200.16 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5216.57 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4176.76 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5206.85 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4525.35 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 22485.02 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 19211.30 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 23025.85 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.84 | 10598.02 | 2189.01 | 1.00 | 1.13 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.14 | 9054.99 | 2189.01 | 1.00 | 1.14 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.96 | 10852.93 | 2189.01 | 1.00 | 1.13 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 120028.72 | 2.97 | 10.14 | 11.65 | 5.5970 | 3.34 | 11.39 | 4.4307 | 3.52 | 12.03 | 2.9816 | 3.64 | 12.43 | 1.2852 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 102553.06 | 2.97 | 10.14 | 11.65 | 4.7821 | 3.34 | 11.39 | 3.7856 | 3.52 | 12.03 | 2.5475 | 3.64 | 12.43 | 1.0981 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 122915.76 | 2.97 | 10.14 | 11.65 | 5.7317 | 3.34 | 11.39 | 4.5373 | 3.52 | 12.03 | 3.0533 | 3.64 | 12.43 | 1.3161 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 39015.52 | 39015.52 | 39.67 | 2.812 | 2.812 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00881 | 28.91 | 0.01715 | 0.425 | 0.00 |
CORE_MID | 28635.95 | 28635.95 | 29.12 | 2.062 | 2.062 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 28.91 | 0.01715 | 0.425 | 0.00 |
CORE_TOP | 31147.51 | 31147.51 | 31.67 | 2.264 | 2.264 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 24.00 | 24.00 | 0.00889 | 35.20 | 0.01716 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10230.51 | 10230.51 | 49.34 | 0.744 | 0.744 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 24.00 | 24.00 | 0.00906 | 35.03 | 0.01716 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9059.10 | 9059.10 | 69.02 | 0.659 | 0.659 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 24.00 | 24.00 | 0.00892 | 31.73 | 0.01715 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9972.10 | 9972.10 | 48.10 | 0.725 | 0.725 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 24.00 | 24.00 | 0.00908 | 35.20 | 0.01716 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10542.91 | 10542.91 | 80.32 | 0.766 | 0.766 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 24.00 | 24.00 | 0.00886 | 34.58 | 0.01716 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8546.01 | 8546.01 | 41.22 | 0.621 | 0.621 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 24.00 | 24.00 | 0.00900 | 35.03 | 0.01716 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8072.30 | 8072.30 | 61.50 | 0.587 | 0.587 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:40:00 | 24.00 | 24.00 | 0.00885 | 31.49 | 0.01715 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 8311.48 | 8311.48 | 40.09 | 0.604 | 0.604 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 24.00 | 24.00 | 0.00901 | 35.20 | 0.01716 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8653.86 | 8653.86 | 65.93 | 0.629 | 0.629 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:30:00 | 24.00 | 24.00 | 0.00882 | 34.35 | 0.01716 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8632.60 | 8632.60 | 41.64 | 0.628 | 0.628 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 24.00 | 24.00 | 0.00910 | 34.95 | 0.01716 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8605.32 | 8605.32 | 65.56 | 0.626 | 0.626 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:30:00 | 24.00 | 24.00 | 0.00890 | 31.25 | 0.01715 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 8413.76 | 8413.76 | 40.58 | 0.612 | 0.612 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 24.00 | 24.00 | 0.00912 | 35.20 | 0.01716 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9323.52 | 9323.52 | 71.03 | 0.678 | 0.678 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 24.00 | 24.00 | 0.00887 | 34.58 | 0.01716 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 0.425 | 00:10:00 | 15.60 | 22.03 | 0.01480 | 20.10 | 0.01480 | 0.425 | 0.00 | |
CORE_MID | 1233.91 | 1233.91 | 1.25 | 0.053 | 0.425 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 20.10 | 0.01480 | 0.425 | 0.00 |
CORE_TOP | 5004.22 | 5004.22 | 5.09 | 0.210 | 0.425 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 20.10 | 0.01480 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 1615.33 | 1615.33 | 7.79 | 0.068 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01137 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 1048.19 | 1048.19 | 7.99 | 0.044 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01143 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 1654.84 | 1654.84 | 7.98 | 0.069 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01133 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 1048.15 | 1048.15 | 7.99 | 0.044 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01143 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 112.82 | 112.82 | 0.54 | 0.005 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01343 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 83.58 | 83.58 | 0.64 | 0.004 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01333 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 144.31 | 144.31 | 0.70 | 0.006 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01316 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 83.58 | 83.58 | 0.64 | 0.004 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01333 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 799.54 | 799.54 | 3.86 | 0.034 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01190 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 529.02 | 529.02 | 4.03 | 0.022 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01195 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 839.10 | 839.10 | 4.05 | 0.035 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01184 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 529.01 | 529.01 | 4.03 | 0.022 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01195 | 20.10 | 0.01480 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.84 | 4.84 | 0.00 | 0.00 | 4.8415 | 1.3459 | 4.8415 | 0.2780 | 0.3000 |
PACU_VAV_MID | 4.14 | 4.14 | 0.00 | 0.00 | 4.1366 | 1.3130 | 4.1366 | 0.3174 | 0.3000 |
PACU_VAV_TOP | 4.96 | 4.96 | 0.00 | 0.00 | 4.9579 | 1.3928 | 4.9579 | 0.2809 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25912.595 | 25912.595 | -999.0 | -999.0 | -999.000 | 12/21 00:10:00 | 12/21 00:10:00 | 25912.60 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 24708.013 | 24708.013 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24708.01 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800426 | 51.7200 | 1233.91 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 26000.721 | 26000.721 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 26000.72 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 5004.22 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 5487.071 | 5487.071 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5487.07 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01137211 | 73.0794 | 1615.33 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 4397.096 | 4397.096 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4397.10 | 1892.12 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01142985 | 73.4431 | 1048.19 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 5493.686 | 5493.686 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5493.69 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01133015 | 72.8143 | 1654.84 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 5117.287 | 5117.287 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5117.29 | 1892.00 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01142992 | 73.4436 | 1048.15 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 5454.403 | 5454.403 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5454.40 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01343279 | 86.0537 | 112.82 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 3917.908 | 3917.908 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3917.91 | 1892.12 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01333080 | 85.4138 | 83.58 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 5445.910 | 5445.910 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5445.91 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01315530 | 84.3126 | 144.31 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4200.159 | 4200.159 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4200.16 | 1892.00 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01333084 | 85.4141 | 83.58 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 5216.569 | 5216.569 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5216.57 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01190476 | 76.4438 | 799.54 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 4176.762 | 4176.762 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4176.76 | 1892.12 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01194823 | 76.7173 | 529.02 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 5206.846 | 5206.846 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5206.85 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01184162 | 76.0457 | 839.10 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 4525.351 | 4525.351 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4525.35 | 1892.00 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01194829 | 76.7176 | 529.01 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 120225.074 | 84287.782 | 4.841464 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 123224.99 | 87931.03 | 4.841464 | 26.77 | 19.30 | 0.01093806 | 11.03 | 11.03 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 24.6861 | 24.00 | 0.00889174 | 47.8170 | 66417.82 | 0.00 | 123968.19 | 85757.05 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 22485.017 | 22485.017 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 22485.02 | 22485.02 | 1.452439 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 82.2871 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 102720.831 | 72015.851 | 4.136568 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | 106735.91 | 73105.05 | 4.136568 | 27.22 | 19.77 | 0.01137643 | 11.03 | 11.03 | 0.00850000 | 35.12 | 0.01715799 | 25.81 | 28.8928 | 24.00 | 0.00901447 | 48.4684 | 56685.11 | 0.00 | 105918.96 | 73271.20 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 19211.297 | 19211.297 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 19211.30 | 19211.30 | 1.240970 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 96.3093 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 123116.841 | 86315.151 | 4.957915 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 126170.49 | 89893.35 | 4.957915 | 26.68 | 19.27 | 0.01093731 | 11.03 | 11.03 | 0.00850000 | 35.12 | 0.01715799 | 25.81 | 24.1063 | 24.00 | 0.00895564 | 48.1568 | 68050.76 | 0.00 | 126949.99 | 87819.76 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 23025.848 | 23025.848 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 23025.85 | 23025.85 | 1.487375 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 80.3543 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25912.595 | 25912.595 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 25912.60 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25912.60 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 24708.013 | 24708.013 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 24708.01 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24708.01 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.87 | 0.00800426 | 21.00 | 0.00800426 | 51.7200 | 1233.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 26000.721 | 26000.721 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 26000.72 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26000.72 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.68 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 5004.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5487.071 | 5487.071 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5487.07 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5487.07 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.56 | 0.01137211 | 21.00 | 0.01137211 | 73.0794 | 1615.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4397.096 | 4397.096 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4397.10 | 1892.12 | 1.0000 | 0.06821858 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4397.10 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.56 | 0.01142985 | 21.00 | 0.01142985 | 73.4431 | 1048.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5493.686 | 5493.686 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5493.69 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5493.69 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.56 | 0.01133015 | 21.00 | 0.01133015 | 72.8143 | 1654.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5117.287 | 5117.287 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5117.29 | 1892.00 | 1.0000 | 0.06821410 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5117.29 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.56 | 0.01142992 | 21.00 | 0.01142992 | 73.4436 | 1048.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5454.403 | 5454.403 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5454.40 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5454.40 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.97 | 0.01343279 | 21.00 | 0.01343279 | 86.0537 | 112.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 3917.908 | 3917.908 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 3917.91 | 1892.12 | 1.0000 | 0.06821858 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3917.91 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.96 | 0.01333080 | 21.00 | 0.01333080 | 85.4138 | 83.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5445.910 | 5445.910 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5445.91 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5445.91 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.96 | 0.01315530 | 21.00 | 0.01315530 | 84.3126 | 144.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4200.159 | 4200.159 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4200.16 | 1892.00 | 1.0000 | 0.06821410 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4200.16 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.96 | 0.01333084 | 21.00 | 0.01333084 | 85.4141 | 83.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5216.569 | 5216.569 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5216.57 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5216.57 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.77 | 0.01190476 | 21.00 | 0.01190476 | 76.4438 | 799.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4176.762 | 4176.762 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4176.76 | 1892.12 | 1.0000 | 0.06821858 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4176.76 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.76 | 0.01194823 | 21.00 | 0.01194823 | 76.7173 | 529.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5206.846 | 5206.846 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5206.85 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5206.85 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.76 | 0.01184162 | 21.00 | 0.01184162 | 76.0457 | 839.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4525.351 | 4525.351 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4525.35 | 1892.00 | 1.0000 | 0.06821410 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4525.35 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.76 | 0.01194829 | 21.00 | 0.01194829 | 76.7176 | 529.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 120225.074 | 84287.782 | 4.841464 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.98406 | 1025.1733 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.841464 | 5.82716145 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | Sensible | 123224.99 | 87931.03 | 1.0250 | 5.82716145 | 4.841464 | 26.77 | 19.30 | 0.01093806 | 54800.7 | 11.03 | 11.03 | 0.00850000 | 32511.5 | -999.0 | -999.00 | -999.00 | -999.00 | 10598.017 | 112626.97 | 35.20 | 0.01715815 | 25.83 | 1.19517000 | 24.6861 | 24.00 | 0.00889174 | 24.00 | 0.00889174 | 47.8170 | 66417.82 | 0.00 | 123968.19 | 85757.05 | 5.59703262 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.65 | 11.63 | 0.00850793 | 33173.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22485.017 | 22485.017 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.841464 | 5.82716145 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 22485.02 | 22485.02 | 1.0000 | 1.74814843 | 1.452439 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22485.02 | 0.00 | 0.00000000 | -6.26 | 1.19517000 | 82.2871 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | ||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 102720.831 | 72015.851 | 4.136568 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.93366 | 1025.9882 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.136568 | 4.97875231 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | Sensible | 106735.91 | 73105.05 | 1.0391 | 4.97875231 | 4.136568 | 27.22 | 19.77 | 0.01137643 | 56381.7 | 11.03 | 11.03 | 0.00850000 | 32512.9 | -999.0 | -999.00 | -999.00 | -999.00 | 9054.992 | 97680.92 | 35.12 | 0.01715799 | 25.81 | 1.19517000 | 28.8928 | 24.00 | 0.00901447 | 24.00 | 0.00901447 | 48.4684 | 56685.11 | 0.00 | 105918.96 | 73271.20 | 4.78212923 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.65 | 11.63 | 0.00850793 | 33173.5 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19211.297 | 19211.297 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.136568 | 4.97875231 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 19211.30 | 19211.30 | 1.0000 | 1.49362569 | 1.240970 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19211.30 | 0.00 | 0.00000000 | -6.26 | 1.19517000 | 96.3093 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | ||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 123116.841 | 86315.151 | 4.957915 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.98769 | 1025.1719 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.957915 | 5.96732184 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | Sensible | 126170.49 | 89893.35 | 1.0248 | 5.96732184 | 4.957915 | 26.68 | 19.27 | 0.01093731 | 54709.1 | 11.03 | 11.03 | 0.00850000 | 32511.5 | -999.0 | -999.00 | -999.00 | -999.00 | 10852.931 | 115317.56 | 35.12 | 0.01715799 | 25.81 | 1.19517000 | 24.1063 | 24.00 | 0.00895564 | 24.00 | 0.00895564 | 48.1568 | 68050.76 | 0.00 | 126949.99 | 87819.76 | 5.73165774 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.65 | 11.63 | 0.00850793 | 33173.5 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23025.848 | 23025.848 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.957915 | 5.96732184 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 23025.85 | 23025.85 | 1.0000 | 1.79019655 | 1.487375 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23025.85 | 0.00 | 0.00000000 | -6.26 | 1.19517000 | 80.3543 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 5943.00 | 0.00 | 0.00 |
CORE_MID | 5940.33 | 0.50 | 0.50 |
CORE_TOP | 5932.00 | 0.17 | 0.17 |
PERIMETER_TOP_ZN_3 | 5925.00 | 978.83 | 976.83 |
PERIMETER_TOP_ZN_2 | 5936.33 | 1000.33 | 1000.33 |
PERIMETER_TOP_ZN_1 | 5939.67 | 1041.00 | 1041.00 |
PERIMETER_TOP_ZN_4 | 5882.50 | 910.17 | 901.17 |
PERIMETER_BOT_ZN_3 | 5942.33 | 520.00 | 520.00 |
PERIMETER_BOT_ZN_2 | 5943.00 | 738.67 | 738.67 |
PERIMETER_BOT_ZN_1 | 5943.00 | 2448.33 | 2448.33 |
PERIMETER_BOT_ZN_4 | 5942.17 | 638.83 | 638.83 |
PERIMETER_MID_ZN_3 | 5940.33 | 863.17 | 863.17 |
PERIMETER_MID_ZN_2 | 5033.00 | 934.83 | 934.83 |
PERIMETER_MID_ZN_1 | 5943.00 | 986.17 | 986.17 |
PERIMETER_MID_ZN_4 | 5936.00 | 851.67 | 850.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 2798.00 | 2790.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 5.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.33 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 74.00 | 0.00 | 65.67 |
PERIMETER_TOP_ZN_2 | 0.00 | 117.00 | 0.00 | 111.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 103.33 | 0.00 | 95.67 |
PERIMETER_TOP_ZN_4 | 0.00 | 85.83 | 0.00 | 68.33 |
PERIMETER_BOT_ZN_3 | 0.00 | 21.00 | 0.00 | 18.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 84.83 | 0.00 | 82.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 736.00 | 0.00 | 733.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 68.67 | 0.00 | 54.17 |
PERIMETER_MID_ZN_3 | 0.00 | 31.33 | 0.00 | 28.00 |
PERIMETER_MID_ZN_2 | 0.00 | 86.17 | 0.00 | 85.50 |
PERIMETER_MID_ZN_1 | 0.00 | 99.50 | 0.00 | 98.33 |
PERIMETER_MID_ZN_4 | 0.00 | 63.00 | 0.00 | 53.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 931.17 | 0.00 | 896.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.462 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.435 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.431 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.633 | 0.055 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.777 | 0.058 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.693 | 0.055 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.778 | 0.058 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.540 | 0.029 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.657 | 0.031 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.674 | 1.244 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.654 | 0.031 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.640 | 0.046 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.736 | 0.051 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.699 | 0.046 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.782 | 0.048 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.51 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 108.48 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 7932966.34 | 0.00 | 7932966.34 | 0.00 | 7932966.34 | 13393058.27 | 8276.11 | 125.64 | 358.25 | 495.81 |
CORE_MID | 7271487.61 | 0.00 | 7271487.61 | 0.00 | 7271487.61 | 13393058.27 | 8711.09 | 6.07 | 42.84 | 353.08 |
CORE_TOP | 7211450.57 | 0.00 | 7211450.57 | 0.00 | 7211450.57 | 13393058.27 | 8724.85 | 5.53 | 29.62 | 355.07 |
PERIMETER_TOP_ZN_3 | 2183924.58 | 0.00 | 2183924.58 | 330276.95 | 2514201.53 | 2823374.22 | 4422.60 | 42.67 | 4294.73 | 355.07 |
PERIMETER_TOP_ZN_2 | 1695531.71 | 0.00 | 1695531.71 | 220183.31 | 1915715.02 | 1787429.43 | 3299.52 | 2.38 | 5458.09 | 355.07 |
PERIMETER_TOP_ZN_1 | 2377552.13 | 0.00 | 2377552.13 | 330276.95 | 2707829.08 | 2823374.22 | 4271.34 | 17.26 | 4471.39 | 355.07 |
PERIMETER_TOP_ZN_4 | 1715890.69 | 0.00 | 1715890.69 | 220183.31 | 1936074.00 | 1787312.18 | 3339.00 | 15.51 | 5405.50 | 355.07 |
PERIMETER_BOT_ZN_3 | 1920832.51 | 0.00 | 1920832.51 | 175608.30 | 2096440.81 | 2823374.22 | 5685.97 | 260.82 | 2813.21 | 495.81 |
PERIMETER_BOT_ZN_2 | 1472412.81 | 0.00 | 1472412.81 | 117071.50 | 1589484.31 | 1787429.43 | 3282.62 | 63.69 | 5413.69 | 495.81 |
PERIMETER_BOT_ZN_1 | 2355984.63 | 0.00 | 2355984.63 | 4121307.75 | 6477292.39 | 2823374.22 | 4355.60 | 47.00 | 4357.40 | 495.81 |
PERIMETER_BOT_ZN_4 | 1479353.88 | 0.00 | 1479353.88 | 117071.50 | 1596425.38 | 1787312.18 | 3605.97 | 100.13 | 5053.90 | 495.81 |
PERIMETER_MID_ZN_3 | 2204117.88 | 0.00 | 2204117.88 | 274931.61 | 2479049.49 | 2823374.22 | 4444.84 | 34.87 | 4280.29 | 353.08 |
PERIMETER_MID_ZN_2 | 1681733.11 | 0.00 | 1681733.11 | 183286.64 | 1865019.75 | 1787429.43 | 3307.43 | 2.63 | 5449.94 | 1262.08 |
PERIMETER_MID_ZN_1 | 2397617.83 | 0.00 | 2397617.83 | 274931.61 | 2672549.44 | 2823374.22 | 4284.54 | 12.88 | 4462.57 | 353.08 |
PERIMETER_MID_ZN_4 | 1717438.32 | 0.00 | 1717438.32 | 183286.64 | 1900724.96 | 1787312.18 | 3351.57 | 19.79 | 5388.64 | 353.08 |
Total Facility | 45618294.60 | 0.00 | 45618294.60 | 6548416.08 | 52166710.68 | 67843644.98 | 8760.00 | 660.13 | 5839.27 | 1515.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3351 | 0.0000 | 0.3351 | 0.0000 | 0.3351 | 0.4247 | 5497.76 | 123.77 | 321.47 |
CORE_MID | 0.3150 | 0.0000 | 0.3150 | 0.0000 | 0.3150 | 0.4247 | 5911.26 | 5.35 | 26.39 |
CORE_TOP | 0.3125 | 0.0000 | 0.3125 | 0.0000 | 0.3125 | 0.4247 | 5919.39 | 4.58 | 19.03 |
PERIMETER_TOP_ZN_3 | 0.0967 | 0.0000 | 0.0967 | 0.0084 | 0.1051 | 0.0895 | 1642.87 | 40.31 | 4259.82 |
PERIMETER_TOP_ZN_2 | 0.0751 | 0.0000 | 0.0751 | 0.0056 | 0.0807 | 0.0567 | 829.35 | 1.28 | 5112.37 |
PERIMETER_TOP_ZN_1 | 0.1058 | 0.0000 | 0.1058 | 0.0084 | 0.1141 | 0.0895 | 1490.66 | 15.10 | 4437.24 |
PERIMETER_TOP_ZN_4 | 0.0752 | 0.0000 | 0.0752 | 0.0056 | 0.0807 | 0.0567 | 873.54 | 14.50 | 5054.96 |
PERIMETER_BOT_ZN_3 | 0.0825 | 0.0000 | 0.0825 | 0.0044 | 0.0869 | 0.0895 | 2887.74 | 259.28 | 2795.98 |
PERIMETER_BOT_ZN_2 | 0.0636 | 0.0000 | 0.0636 | 0.0030 | 0.0665 | 0.0567 | 935.75 | 60.65 | 4946.61 |
PERIMETER_BOT_ZN_1 | 0.1027 | 0.0000 | 0.1027 | 0.1889 | 0.2916 | 0.0895 | 1567.88 | 45.00 | 4330.13 |
PERIMETER_BOT_ZN_4 | 0.0633 | 0.0000 | 0.0633 | 0.0030 | 0.0663 | 0.0567 | 1268.22 | 97.93 | 4576.85 |
PERIMETER_MID_ZN_3 | 0.0977 | 0.0000 | 0.0977 | 0.0070 | 0.1047 | 0.0895 | 1653.67 | 33.16 | 4256.17 |
PERIMETER_MID_ZN_2 | 0.0711 | 0.0000 | 0.0711 | 0.0049 | 0.0760 | 0.0567 | 831.09 | 1.57 | 4201.35 |
PERIMETER_MID_ZN_1 | 0.1068 | 0.0000 | 0.1068 | 0.0070 | 0.1138 | 0.0895 | 1496.02 | 11.30 | 4435.68 |
PERIMETER_MID_ZN_4 | 0.0756 | 0.0000 | 0.0756 | 0.0046 | 0.0803 | 0.0567 | 879.40 | 18.87 | 5044.73 |
Total Facility | 1.9786 | 0.0000 | 1.9786 | 0.2507 | 2.2292 | 2.1513 | 5943.00 | 640.55 | 5233.10 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 21963649.85 | 0.00 | 21963649.85 | 22614548.33 | 3139.04 | 0.00 | 5620.96 | 495.81 |
PACU_VAV_MID | 22124231.86 | 0.00 | 22124231.86 | 22614548.33 | 3285.37 | 0.00 | 5474.63 | 353.08 |
PACU_VAV_TOP | 21996677.80 | 0.00 | 21996677.80 | 22614548.33 | 3281.23 | 0.00 | 5478.77 | 355.07 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9374 | 0.0000 | 0.9374 | 0.7171 | 817.84 | 0.00 | 5125.16 |
PACU_VAV_MID | 0.9702 | 0.0000 | 0.9702 | 0.7171 | 821.45 | 0.00 | 5121.55 |
PACU_VAV_TOP | 0.9636 | 0.0000 | 0.9636 | 0.7171 | 819.30 | 0.00 | 5123.70 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5620.96 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5474.63 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5478.77 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0870 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1259 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1178 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 824 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2286.72 | 15539.06 | 28-MAY-17:10 | 183990.18 | 13-JUN-15:10 |
Electricity:Building | 1041.95 | 15341.49 | 01-JAN-07:40 | 71349.54 | 23-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 310.83 | 4652.71 | 01-JAN-00:10 | 24063.48 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1041.95 | 15341.49 | 01-JAN-07:40 | 71349.54 | 23-OCT-07:10 |
InteriorLights:Electricity | 279.91 | 1316.11 | 01-JAN-07:40 | 26362.23 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 279.91 | 1316.11 | 01-JAN-07:40 | 26362.23 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity | 279.91 | 1316.11 | 01-JAN-07:40 | 26362.23 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 279.91 | 1316.11 | 01-JAN-07:40 | 26362.23 | 18-DEC-17:00 |
Electricity:Zone:CORE_MID | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 35.82 | 541.99 | 01-JAN-07:30 | 2522.79 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.14 | 40.03 | 01-JAN-07:30 | 1016.90 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.14 | 40.03 | 01-JAN-07:30 | 1016.90 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 22.69 | 343.10 | 01-JAN-07:00 | 1604.32 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.80 | 25.34 | 01-JAN-07:00 | 651.02 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.80 | 25.34 | 01-JAN-07:00 | 651.02 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 35.81 | 541.99 | 01-JAN-07:10 | 2482.68 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.12 | 40.03 | 01-JAN-07:10 | 976.80 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.12 | 40.03 | 01-JAN-07:10 | 976.80 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 22.66 | 343.10 | 01-JAN-07:40 | 1560.88 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.77 | 25.34 | 01-JAN-07:40 | 607.59 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.77 | 25.34 | 01-JAN-07:40 | 607.59 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 35.82 | 541.99 | 01-JAN-07:30 | 2516.04 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.13 | 40.03 | 01-JAN-07:30 | 1010.15 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.13 | 40.03 | 01-JAN-07:30 | 1010.15 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 22.69 | 343.10 | 01-JAN-07:00 | 1601.28 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.79 | 25.34 | 01-JAN-07:00 | 647.99 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.79 | 25.34 | 01-JAN-07:00 | 647.99 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 35.80 | 541.99 | 01-JAN-07:00 | 2473.95 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.12 | 40.03 | 01-JAN-07:00 | 968.07 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.12 | 40.03 | 01-JAN-07:00 | 968.07 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 22.66 | 343.10 | 01-JAN-07:40 | 1555.21 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.77 | 25.34 | 01-JAN-07:40 | 601.92 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.77 | 25.34 | 01-JAN-07:40 | 601.92 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 35.82 | 541.99 | 01-JAN-07:30 | 2522.78 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.14 | 40.03 | 01-JAN-07:30 | 1016.89 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.14 | 40.03 | 01-JAN-07:30 | 1016.89 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 22.69 | 343.10 | 01-JAN-07:00 | 1604.31 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.80 | 25.34 | 01-JAN-07:00 | 651.02 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.80 | 25.34 | 01-JAN-07:00 | 651.02 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 35.81 | 541.99 | 01-JAN-07:10 | 2482.67 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.12 | 40.03 | 01-JAN-07:10 | 976.79 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.12 | 40.03 | 01-JAN-07:10 | 976.79 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 22.66 | 343.10 | 01-JAN-07:40 | 1560.87 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.77 | 25.34 | 01-JAN-07:40 | 607.59 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.77 | 25.34 | 01-JAN-07:40 | 607.59 | 18-DEC-17:00 |
InteriorEquipment:Electricity | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 247.34 | 4344.73 | 01-JAN-00:10 | 18520.31 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 1172.75 | 197.13 | 01-JAN-00:10 | 116531.10 | 13-JUN-15:10 |
ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 923.95 | 18-DEC-17:00 |
Transformer:ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 923.95 | 18-DEC-17:00 |
ElectricityPurchased:Facility | 2286.72 | 15539.06 | 11-JUN-17:10 | 183990.18 | 13-JUN-15:10 |
ElectricityPurchased:Plant | 2286.72 | 15539.06 | 11-JUN-17:10 | 183990.18 | 13-JUN-15:10 |
Cogeneration:ElectricityPurchased | 2286.72 | 15539.06 | 11-JUN-17:10 | 183990.18 | 13-JUN-15:10 |
General:Cogeneration:ElectricityPurchased | 2286.72 | 15539.06 | 11-JUN-17:10 | 183990.18 | 13-JUN-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2286.72 | 15539.06 | 11-JUN-17:10 | 183990.18 | 13-JUN-15:10 |
ElectricityNet:Plant | 2286.72 | 15539.06 | 11-JUN-17:10 | 183990.18 | 13-JUN-15:10 |
Cogeneration:ElectricityNet | 2286.72 | 15539.06 | 11-JUN-17:10 | 183990.18 | 13-JUN-15:10 |
General:Cogeneration:ElectricityNet | 2286.72 | 15539.06 | 11-JUN-17:10 | 183990.18 | 13-JUN-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity | 188.26 | 0.00 | 01-JAN-00:10 | 24960.75 | 19-JUN-07:10 |
General:Fans:Electricity | 188.26 | 0.00 | 01-JAN-00:10 | 24960.75 | 19-JUN-07:10 |
ExteriorLights:Electricity | 72.00 | 0.00 | 01-JAN-06:20 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 72.00 | 0.00 | 01-JAN-06:20 | 5557.43 | 01-JAN-06:10 |
Cooling:Electricity | 971.51 | 0.00 | 01-JAN-00:10 | 98545.37 | 13-JUN-15:10 |
General:Cooling:Electricity | 971.51 | 0.00 | 01-JAN-00:10 | 98545.37 | 13-JUN-15:10 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 01-JAN-06:20 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 01-JAN-06:20 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 01-JAN-06:20 |
WIRED_LTG_ELECTRICITY | 7.87 | 0.00 | 01-JAN-00:10 | 740.78 | 18-DEC-17:10 |
WIRED_INT_EQUIP | 641.94 | 12061.80 | 01-JAN-00:10 | 36271.65 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 85.82 | 1156.00 | 01-JAN-00:10 | 8618.51 | 12-JAN-12:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 85.82 | 1156.00 | 01-JAN-00:10 | 8618.51 | 12-JAN-12:10 |
WaterSystems:NaturalGas | 85.82 | 1156.00 | 01-JAN-00:10 | 8618.51 | 12-JAN-12:10 |
Water Heater:WaterSystems:NaturalGas | 85.82 | 1156.00 | 01-JAN-00:10 | 8618.51 | 12-JAN-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 5881.55 | 0.00 | 01-JAN-00:10 | 508897.87 | 13-JUN-15:20 |
EnergyTransfer:Building | 2024.00 | 0.00 | 01-JAN-00:10 | 177342.63 | 21-FEB-14:50 |
EnergyTransfer:Zone:CORE_BOTTOM | 347.84 | 0.00 | 01-JAN-00:10 | 30547.19 | 02-JAN-08:20 |
Heating:EnergyTransfer | 0.90 | 0.00 | 01-JAN-00:10 | 2868.09 | 23-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 0.90 | 0.00 | 01-JAN-00:10 | 2868.09 | 23-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 2023.09 | 0.00 | 01-JAN-00:10 | 177342.63 | 21-FEB-14:50 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 347.84 | 0.00 | 01-JAN-00:10 | 30547.19 | 02-JAN-08:20 |
General:Cooling:EnergyTransfer | 2023.09 | 0.00 | 01-JAN-00:10 | 177342.63 | 21-FEB-14:50 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 347.84 | 0.00 | 01-JAN-00:10 | 30547.19 | 02-JAN-08:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 99.07 | 0.00 | 01-JAN-00:10 | 12645.77 | 05-MAY-13:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 0.33 | 0.00 | 01-JAN-00:10 | 2264.18 | 23-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 0.33 | 0.00 | 01-JAN-00:10 | 2264.18 | 23-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 98.73 | 0.00 | 01-JAN-00:10 | 12645.77 | 05-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 98.73 | 0.00 | 01-JAN-00:10 | 12645.77 | 05-MAY-13:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 56.40 | 0.00 | 01-JAN-00:10 | 5833.99 | 21-FEB-08:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.22 | 0.00 | 01-JAN-00:10 | 723.27 | 20-AUG-15:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.22 | 0.00 | 01-JAN-00:10 | 723.27 | 20-AUG-15:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 56.18 | 0.00 | 01-JAN-00:10 | 5833.99 | 21-FEB-08:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 56.18 | 0.00 | 01-JAN-00:10 | 5833.99 | 21-FEB-08:10 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 62.73 | 0.00 | 01-JAN-00:10 | 6338.47 | 05-SEP-07:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.35 | 0.00 | 01-JAN-00:10 | 1060.99 | 29-JUN-04:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.35 | 0.00 | 01-JAN-00:10 | 1060.99 | 29-JUN-04:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 62.38 | 0.00 | 01-JAN-00:10 | 6338.47 | 05-SEP-07:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 62.38 | 0.00 | 01-JAN-00:10 | 6338.47 | 05-SEP-07:10 |
EnergyTransfer:Zone:CORE_MID | 252.41 | 0.00 | 01-JAN-00:10 | 20532.86 | 21-FEB-08:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 252.41 | 0.00 | 01-JAN-00:10 | 20532.86 | 21-FEB-08:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 252.41 | 0.00 | 01-JAN-00:10 | 20532.86 | 21-FEB-08:20 |
EnergyTransfer:Zone:CORE_TOP | 268.63 | 0.00 | 01-JAN-00:10 | 22812.46 | 21-FEB-14:40 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 268.63 | 0.00 | 01-JAN-00:10 | 22812.46 | 21-FEB-14:40 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 268.63 | 0.00 | 01-JAN-00:10 | 22812.46 | 21-FEB-14:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 86.42 | 0.00 | 01-JAN-00:10 | 9690.25 | 12-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 86.42 | 0.00 | 01-JAN-00:10 | 9690.25 | 12-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 86.42 | 0.00 | 01-JAN-00:10 | 9690.25 | 12-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 66.64 | 0.00 | 01-JAN-00:10 | 7682.39 | 05-MAY-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 66.64 | 0.00 | 01-JAN-00:10 | 7682.39 | 05-MAY-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 66.64 | 0.00 | 01-JAN-00:10 | 7682.39 | 05-MAY-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 94.87 | 0.00 | 01-JAN-00:10 | 10586.84 | 26-DEC-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 94.87 | 0.00 | 01-JAN-00:10 | 10586.84 | 26-DEC-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 94.87 | 0.00 | 01-JAN-00:10 | 10586.84 | 26-DEC-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 66.45 | 0.00 | 01-JAN-00:10 | 8370.84 | 11-APR-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 66.45 | 0.00 | 01-JAN-00:10 | 8370.84 | 11-APR-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 66.45 | 0.00 | 01-JAN-00:10 | 8370.84 | 11-APR-15:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.34 | 0.00 | 01-JAN-00:10 | 8713.48 | 12-JUN-15:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.34 | 0.00 | 01-JAN-00:10 | 8713.48 | 12-JUN-15:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.34 | 0.00 | 01-JAN-00:10 | 8713.48 | 12-JUN-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 66.67 | 0.00 | 01-JAN-00:10 | 7062.14 | 20-MAR-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 66.67 | 0.00 | 01-JAN-00:10 | 7062.14 | 20-MAR-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 66.67 | 0.00 | 01-JAN-00:10 | 7062.14 | 20-MAR-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 111.77 | 0.00 | 01-JAN-00:10 | 11396.38 | 05-MAY-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 111.77 | 0.00 | 01-JAN-00:10 | 11396.38 | 05-MAY-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 111.77 | 0.00 | 01-JAN-00:10 | 11396.38 | 05-MAY-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 65.84 | 0.00 | 01-JAN-00:10 | 7354.15 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 65.84 | 0.00 | 01-JAN-00:10 | 7354.15 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 65.84 | 0.00 | 01-JAN-00:10 | 7354.15 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 80.56 | 0.00 | 01-JAN-00:10 | 8647.76 | 12-JUN-15:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 80.56 | 0.00 | 01-JAN-00:10 | 8647.76 | 12-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 80.56 | 0.00 | 01-JAN-00:10 | 8647.76 | 12-JUN-15:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 61.31 | 0.00 | 01-JAN-00:10 | 7197.39 | 05-MAY-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 61.31 | 0.00 | 01-JAN-00:10 | 7197.39 | 05-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 61.31 | 0.00 | 01-JAN-00:10 | 7197.39 | 05-MAY-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 88.36 | 0.00 | 01-JAN-00:10 | 9171.35 | 26-DEC-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 88.36 | 0.00 | 01-JAN-00:10 | 9171.35 | 26-DEC-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 88.36 | 0.00 | 01-JAN-00:10 | 9171.35 | 26-DEC-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 61.68 | 0.00 | 01-JAN-00:10 | 7622.40 | 18-APR-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 61.68 | 0.00 | 01-JAN-00:10 | 7622.40 | 18-APR-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 61.68 | 0.00 | 01-JAN-00:10 | 7622.40 | 18-APR-15:30 |
PlantLoopHeatingDemand:Facility | 31.77 | 0.00 | 01-JAN-00:10 | 3782.91 | 13-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 31.77 | 0.00 | 01-JAN-00:10 | 3782.91 | 13-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 31.77 | 0.00 | 01-JAN-00:10 | 3782.91 | 13-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 31.77 | 0.00 | 01-JAN-00:10 | 3782.91 | 13-JAN-12:10 |
EnergyTransfer:HVAC | 3825.79 | 0.00 | 01-JAN-00:10 | 342009.00 | 15-JUN-10:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 3825.79 | 0.00 | 01-JAN-00:10 | 342009.00 | 15-JUN-10:00 |
EnergyTransfer:Plant | 31.77 | 0.00 | 01-JAN-00:10 | 3782.91 | 13-JAN-12:10 |
WaterSystems:EnergyTransfer | 31.77 | 0.00 | 01-JAN-00:10 | 3782.91 | 13-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 31.77 | 0.00 | 01-JAN-00:10 | 3782.91 | 13-JAN-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -347.837 | 0.000 | 0.000 | 32.660 | 63.485 | 247.342 | 0.000 | 0.000 | 0.000 | 4.350 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 0.000 | -252.406 | 0.000 | 0.000 | 32.688 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 29.633 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -268.630 | 0.000 | 0.000 | 32.687 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 45.858 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.000 | -86.421 | 0.000 | 0.000 | 6.882 | 9.135 | 26.688 | 37.791 | 0.000 | 0.987 | 8.605 | 0.000 | -3.485 | 0.000 | -0.183 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -66.640 | 0.000 | 0.000 | 4.356 | 5.797 | 16.895 | 37.926 | 0.000 | 0.655 | 3.387 | 0.000 | -2.249 | 0.000 | -0.126 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -94.867 | 0.000 | 0.000 | 6.876 | 9.122 | 26.688 | 48.757 | 0.000 | 0.979 | 6.101 | 0.000 | -3.461 | 0.000 | -0.195 | -0.000 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.000 | -66.443 | 0.000 | 0.000 | 4.360 | 5.770 | 16.895 | 38.007 | 0.000 | 0.655 | 3.318 | 0.000 | -2.432 | 0.000 | -0.130 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -86.342 | 0.000 | 0.000 | 6.881 | 9.128 | 26.688 | 38.002 | 0.000 | 0.544 | 8.904 | 0.000 | -3.704 | 0.000 | -0.101 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -66.670 | 0.000 | 0.000 | 4.354 | 5.792 | 16.895 | 38.058 | 0.000 | 0.351 | 3.817 | 0.000 | -2.522 | 0.000 | -0.074 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -111.762 | 0.000 | 0.000 | 6.748 | 9.117 | 26.688 | 48.573 | 0.000 | 21.278 | 3.728 | 0.000 | -3.916 | 0.000 | -0.453 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -65.841 | 0.000 | 0.000 | 4.355 | 5.766 | 16.895 | 38.120 | 0.000 | 0.347 | 3.174 | 0.000 | -2.738 | 0.000 | -0.078 | -0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -80.561 | 0.000 | 0.000 | 6.882 | 9.135 | 26.688 | 38.129 | 0.000 | 0.838 | 2.619 | 0.000 | -3.571 | 0.000 | -0.159 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -61.309 | 0.000 | 0.000 | 3.210 | 5.797 | 16.895 | 38.174 | 0.000 | 0.555 | 0.001 | 0.000 | -2.304 | 0.000 | -0.109 | -0.910 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -88.358 | 0.000 | 0.000 | 6.867 | 9.122 | 26.688 | 49.094 | 0.000 | 0.830 | 0.000 | 0.000 | -3.547 | 0.000 | -0.169 | -0.527 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -61.683 | 0.000 | 0.000 | 4.357 | 5.770 | 16.895 | 38.229 | 0.000 | 0.549 | 0.000 | 0.000 | -2.505 | 0.000 | -0.113 | -1.499 |
TOPFLOOR_PLENUM | 0.332 | -98.733 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.220 | 97.386 | 0.000 | 0.000 | 0.000 | -0.204 | 0.000 |
MIDFLOOR_PLENUM | 0.220 | -56.176 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.284 | 54.904 | 0.000 | 0.000 | 0.000 | -0.232 | 0.000 |
FIRSTFLOOR_PLENUM | 0.351 | -62.379 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.993 | 61.221 | 0.000 | 0.000 | 0.000 | -0.186 | -0.000 |
Total Facility | 0.903 | -217.288 | 0.000 | -1805.773 | 0.000 | 0.000 | 164.162 | 279.906 | 762.041 | 488.862 | 0.000 | 32.065 | 337.004 | 0.000 | -36.433 | 0.000 | -2.512 | -2.940 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 23-JAN-05:02 | 0.00 | 0.00 | 0.00 | -44278.51 | 0.00 | 0.00 | 0.00 | 615.87 | 5138.45 | 0.00 | 0.00 | 0.00 | 38524.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 10-APR-04:04 | 0.00 | 0.00 | 0.00 | -35135.01 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 31344.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 22-MAY-04:04 | 0.00 | 0.00 | 0.00 | -36264.13 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 32473.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 18-JUN-16:32 | 0.00 | 0.00 | 0.00 | -12856.49 | 0.00 | 0.00 | 24.38 | 40.03 | 501.96 | 2897.60 | 0.00 | 124.17 | 9268.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 18-JUN-08:32 | 0.00 | 0.00 | 0.00 | -11924.54 | 0.00 | 0.00 | 15.33 | 25.34 | 317.77 | 5451.31 | 0.00 | 83.98 | 6030.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 16-JAN-11:32 | 0.00 | 0.00 | 0.00 | -13584.53 | 0.00 | 0.00 | 23.85 | 40.03 | 501.96 | 8286.27 | 0.00 | 19.55 | 4712.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 19-MAR-15:32 | 0.00 | 0.00 | 0.00 | -13809.68 | 0.00 | 0.00 | 12.09 | 25.34 | 317.76 | 6582.53 | 0.00 | 341.26 | 6530.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 18-JUN-14:32 | 0.00 | 0.00 | 0.00 | -10767.45 | 0.00 | 0.00 | 25.74 | 40.03 | 501.96 | 4597.60 | 0.00 | 204.68 | 5397.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 18-JUN-08:32 | 0.00 | 0.00 | 0.00 | -10427.76 | 0.00 | 0.00 | 16.30 | 25.34 | 317.77 | 5526.26 | 0.00 | 50.05 | 4492.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 05-MAY-12:00 | 0.00 | 0.00 | 0.00 | -11395.66 | 0.00 | 0.00 | 284.26 | 720.41 | 1338.56 | 3279.32 | 0.00 | 10752.13 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4979.02 |
PERIMETER_BOT_ZN_4 | 04-SEP-16:22 | 0.00 | 0.00 | 0.00 | -11662.91 | 0.00 | 0.00 | 14.63 | 25.34 | 317.76 | 6590.97 | 0.00 | 54.15 | 4660.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-JUN-12:53 | 0.00 | 0.00 | 0.00 | -10854.40 | 0.00 | 0.00 | 27.10 | 40.03 | 501.96 | 4404.45 | 0.00 | 116.37 | 5764.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-SEP-09:52 | 0.00 | 0.00 | 0.00 | -11142.54 | 0.00 | 0.00 | 15.72 | 25.34 | 317.77 | 4305.43 | 0.00 | 40.40 | 6437.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 03-DEC-11:42 | 0.00 | 0.00 | 0.00 | -11349.73 | 0.00 | 0.00 | 25.07 | 40.03 | 501.96 | 8038.77 | 0.00 | 44.78 | 2699.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 10-SEP-17:12 | 0.00 | 0.00 | 0.00 | -12005.05 | 0.00 | 0.00 | 0.00 | 25.34 | 317.76 | 3603.36 | 0.00 | 7.92 | 8050.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 05-MAY-13:10 | 0.00 | -12644.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.90 | 12497.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 19-JUN-06:15 | 0.00 | -7023.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.13 | 7007.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 11-APR-12:10 | 0.00 | -6539.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.89 | 6484.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-JUL-04:02 | 0.00 | 9958.45 | 0.00 | -210252.50 | 0.00 | 0.00 | 0.00 | 3119.77 | 18045.99 | 0.00 | 0.00 | 0.00 | 182610.05 | 0.00 | -3431.06 | 0.00 | -50.69 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 23-JAN-05:02 | 6254.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -95.05 | -6159.47 |
MIDFLOOR_PLENUM | 02-AUG-04:02 | 3044.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.20 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3148.98 |
FIRSTFLOOR_PLENUM | 02-AUG-04:02 | 4548.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.07 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4626.53 |
Total Facility | 18-SEP-04:02 | -180088.77 | 191381.23 | 0.00 | -191381.23 | 0.00 | 0.00 | 0.00 | 3119.77 | 18045.99 | 0.00 | 0.00 | 0.00 | 161411.48 | 0.00 | -2421.69 | 0.00 | -66.77 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.2537 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.8415 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.6043 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.1366 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.1579 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9579 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.6269 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3459 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.3021 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3130 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.5789 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3928 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8124 | 2.8124 | 0.7762 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0617 | 2.0617 | 0.7401 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2641 | 2.2641 | 0.7789 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7437 | 0.7437 | 0.1644 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6586 | 0.6586 | 0.1317 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7250 | 0.7250 | 0.1646 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7664 | 0.7664 | 0.1533 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6212 | 0.6212 | 0.1634 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5868 | 0.5868 | 0.1174 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6042 | 0.6042 | 0.1631 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6291 | 0.6291 | 0.1258 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6276 | 0.6276 | 0.1563 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6256 | 0.6256 | 0.1251 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6117 | 0.6117 | 0.1560 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6778 | 0.6778 | 0.1356 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.2537 | 4.8415 | 5.2537 | 1.3459 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.6043 | 4.1366 | 4.6043 | 1.3130 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.1579 | 4.9579 | 5.1579 | 1.3928 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4062 | 1.4062 | 0.7762 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0308 | 1.0308 | 0.7401 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1321 | 1.1321 | 0.7789 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3719 | 0.3719 | 0.1644 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3293 | 0.3293 | 0.1317 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3625 | 0.3625 | 0.1646 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3832 | 0.3832 | 0.1533 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3106 | 0.3106 | 0.1634 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2934 | 0.2934 | 0.1174 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3021 | 0.3021 | 0.1631 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3145 | 0.3145 | 0.1258 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3138 | 0.3138 | 0.1563 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3128 | 0.3128 | 0.1251 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3058 | 0.3058 | 0.1560 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3389 | 0.3389 | 0.1356 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.6269 | 1.3459 | 1.3459 | 1.3459 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.3021 | 1.3130 | 1.3130 | 1.3130 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.5789 | 1.3928 | 1.3928 | 1.3928 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 4982.19 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 896.50 |
Number of hours not met | 896.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 971.51 | 98545.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 279.91 | 26362.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 72.00 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 641.30 | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 12.98 | 923.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 188.26 | 24960.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 85.82 | 8618.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 762.04 | 2286.72 |
Natural Gas | 0.00 | 85.82 |
Additional | 0.00 | 0.00 |
Total | 762.04 | 2372.54 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 56.18 |
Space Heating | 0.00 |
Space Cooling | 195.00 |
Fans (All) | 37.79 |
Service Water Heating | 0.00 |
Receptacle Equipment | 152.95 |
Miscellaneous (All) | 458.98 |
Subtotal | 458.98 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 17.23 |
Miscellaneous (All) | 17.23 |
Subtotal | 17.23 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.80 |
Space Heating | 0.00 |
Space Cooling | 40.95 |
Fans (All) | 7.93 |
Service Water Heating | 3.62 |
Receptacle Equipment | 32.12 |
Miscellaneous | 3.58 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2429. | 8760. |
BLDG_EQUIP_SCH | 4487. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 7414.83 | 1345.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8484.67 | 275.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8480.00 | 280.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7488.33 | 1271.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7364.33 | 1395.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7295.00 | 1465.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7248.17 | 1511.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7853.33 | 906.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7398.67 | 1361.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7272.83 | 1487.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7154.17 | 1605.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7569.67 | 1190.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7411.67 | 1348.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7380.00 | 1380.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7213.00 | 1547.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8014.00 | 746.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8499.00 | 261.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8674.00 | 86.00 | 0.00 | 0.00 | 0.00 |
Min | 7154.17 | 86.00 | 0.00 | 0.00 | 0.00 |
Max | 8674.00 | 1605.83 | 0.00 | 0.00 | 0.00 |
Average | 7678.65 | 1081.35 | 0.00 | 0.00 | 0.00 |
Sum | 138215.67 | 19464.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128030.67 | 273.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128286.33 | 17.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128283.33 | 20.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24570.83 | 338.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128286.33 | 338.17 | 0.00 | 0.00 | 0.00 |
Average | 34107.23 | 36.10 | 0.00 | 0.00 | 0.00 |
Sum | 613930.17 | 649.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 5388.17 | 3371.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 5373.67 | 3386.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 5373.17 | 3386.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 4436.33 | 4323.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 4474.00 | 4286.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 4410.17 | 4349.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 4524.00 | 4236.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 4532.67 | 4227.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 4499.83 | 4260.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 2616.17 | 6143.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 4498.50 | 4261.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 4406.50 | 4353.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 4435.50 | 4324.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 4387.17 | 4372.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 4446.00 | 4314.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 1696.00 | 7064.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3385.83 | 5374.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 3910.50 | 4849.50 | 0.00 | 0.00 | 0.00 |
Min | 1696.00 | 3371.83 | 0.00 | 0.00 | 0.00 |
Max | 5388.17 | 7064.00 | 0.00 | 0.00 | 0.00 |
Average | 4266.34 | 4493.66 | 0.00 | 0.00 | 0.00 |
Sum | 76794.17 | 80885.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 126586.67 | 1717.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 126729.00 | 1575.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 126625.67 | 1678.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24618.83 | 290.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14009.83 | 6.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24608.00 | 301.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14010.67 | 5.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24702.83 | 206.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 14141.00 | 10768.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24626.50 | 282.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10131.17 | 2.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24617.50 | 291.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14012.83 | 3.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 126729.00 | 10768.00 | 0.00 | 0.00 | 0.00 |
Average | 33191.81 | 951.53 | 0.00 | 0.00 | 0.00 |
Sum | 597452.50 | 17127.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294116E+11 | 44281.66 | 23-JAN-05:02 | 18.95 | 17.06 | 0.199562E+10 | 2606.58 | 24-JAN-10:20 | 22.27 | 18.67 |
February | 0.266594E+11 | 43125.97 | 03-FEB-05:03 | 21.82 | 20.81 | 0.180977E+10 | 2606.66 | 21-FEB-10:09 | 21.92 | 19.78 |
March | 0.307475E+11 | 43250.24 | 02-MAR-05:03 | 23.00 | 22.27 | 0.216037E+10 | 2606.69 | 03-MAR-14:09 | 32.17 | 22.91 |
April | 0.284541E+11 | 41782.04 | 21-APR-04:03 | 26.00 | 24.56 | 0.191815E+10 | 2606.71 | 14-APR-13:09 | 26.00 | 24.56 |
May | 0.304533E+11 | 43046.73 | 26-MAY-04:03 | 24.00 | 23.90 | 0.207745E+10 | 2606.67 | 03-MAY-13:00 | 24.00 | 23.90 |
June | 0.302095E+11 | 42369.36 | 21-JUN-04:03 | 23.33 | 23.13 | 0.207132E+10 | 2606.62 | 30-JUN-13:09 | 24.00 | 23.77 |
July | 0.286344E+11 | 42736.41 | 19-JUL-04:03 | 24.42 | 23.71 | 0.192549E+10 | 2606.66 | 03-JUL-13:09 | 24.42 | 23.71 |
August | 0.302351E+11 | 43041.61 | 22-AUG-04:03 | 24.08 | 23.67 | 0.216108E+10 | 2606.81 | 17-AUG-13:09 | 24.08 | 23.67 |
September | 0.280190E+11 | 42549.50 | 29-SEP-04:03 | 24.00 | 23.47 | 0.191855E+10 | 2606.63 | 20-SEP-13:09 | 24.00 | 23.47 |
October | 0.286871E+11 | 43663.81 | 23-OCT-04:02 | 22.58 | 22.48 | 0.199559E+10 | 2606.72 | 30-OCT-13:09 | 24.42 | 24.31 |
November | 0.282812E+11 | 43669.52 | 28-NOV-05:03 | 23.00 | 22.27 | 0.197590E+10 | 2606.69 | 08-NOV-14:50 | 23.00 | 22.27 |
December | 0.280461E+11 | 44146.62 | 27-DEC-05:02 | 19.00 | 18.34 | 0.192508E+10 | 2606.62 | 18-DEC-14:00 | 19.00 | 18.34 |
Annual Sum or Average | 0.347838E+12 | 0.239344E+11 | ||||||||
Minimum of Months | 0.266594E+11 | 41782.04 | 18.95 | 17.06 | 0.180977E+10 | 2606.58 | 19.00 | 18.34 | ||
Maximum of Months | 0.307475E+11 | 44281.66 | 26.00 | 24.56 | 0.216108E+10 | 2606.81 | 32.17 | 24.56 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.768206E+10 | 10645.71 | 04-JAN-13:02 | 34.08 | 23.62 | 0.00 | 0.00 | 01-JAN-00:10 | 34.08 | 23.62 |
February | 0.772477E+10 | 11948.30 | 21-FEB-14:30 | 34.50 | 21.90 | 0.00 | 0.00 | 01-FEB-00:10 | 34.50 | 21.90 |
March | 0.966955E+10 | 12440.73 | 29-MAR-14:10 | 35.67 | 23.72 | 0.00 | 0.00 | 01-MAR-00:10 | 35.67 | 23.72 |
April | 0.940809E+10 | 12442.04 | 11-APR-14:00 | 34.90 | 26.25 | 0.00 | 0.00 | 01-APR-00:10 | 34.90 | 26.25 |
May | 0.932120E+10 | 12645.77 | 05-MAY-13:10 | 36.33 | 27.23 | 0.00 | 0.00 | 01-MAY-00:10 | 36.33 | 27.23 |
June | 0.969296E+10 | 12029.38 | 16-JUN-14:10 | 35.33 | 27.51 | 0.00 | 0.00 | 01-JUN-00:10 | 35.33 | 27.51 |
July | 0.800578E+10 | 11144.70 | 14-JUL-14:00 | 32.00 | 24.80 | 0.00 | 0.00 | 01-JUL-00:10 | 32.00 | 24.80 |
August | 0.813659E+10 | 11946.56 | 14-AUG-13:40 | 33.27 | 27.64 | 0.00 | 0.00 | 01-AUG-00:10 | 33.27 | 27.64 |
September | 0.781458E+10 | 11988.03 | 06-SEP-14:10 | 33.83 | 26.60 | 0.00 | 0.00 | 01-SEP-00:10 | 33.83 | 26.60 |
October | 0.705927E+10 | 10826.47 | 02-OCT-13:30 | 31.00 | 26.24 | 0.00 | 0.00 | 01-OCT-00:10 | 31.00 | 26.24 |
November | 0.712662E+10 | 10140.12 | 22-NOV-13:02 | 31.50 | 24.57 | 0.00 | 0.00 | 01-NOV-00:10 | 31.50 | 24.57 |
December | 0.709292E+10 | 10560.34 | 26-DEC-13:02 | 32.00 | 23.12 | 0.00 | 0.00 | 01-DEC-00:10 | 32.00 | 23.12 |
Annual Sum or Average | 0.987344E+11 | 0.00 | ||||||||
Minimum of Months | 0.705927E+10 | 10140.12 | 31.00 | 21.90 | 0.00 | 0.00 | 31.00 | 21.90 | ||
Maximum of Months | 0.969296E+10 | 12645.77 | 36.33 | 27.64 | 0.00 | 0.00 | 36.33 | 27.64 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.450433E+10 | 5300.00 | 17-JAN-07:10 | 20.78 | 19.94 | 0.00 | 0.00 | 01-JAN-00:10 | 20.78 | 19.94 |
February | 0.430620E+10 | 5833.99 | 21-FEB-08:70 | 26.33 | 21.23 | 0.00 | 0.00 | 01-FEB-00:10 | 26.33 | 21.23 |
March | 0.517302E+10 | 5429.51 | 20-MAR-16:00 | 34.30 | 24.91 | 0.00 | 0.00 | 01-MAR-00:10 | 34.30 | 24.91 |
April | 0.499432E+10 | 6522.74 | 03-APR-06:15 | 27.20 | 25.21 | 0.00 | 0.00 | 01-APR-00:10 | 27.20 | 25.21 |
May | 0.527463E+10 | 6796.39 | 08-MAY-06:15 | 27.37 | 26.11 | 0.00 | 0.00 | 01-MAY-00:10 | 27.37 | 26.11 |
June | 0.537736E+10 | 7024.82 | 19-JUN-06:15 | 27.13 | 26.29 | 0.00 | 0.00 | 01-JUN-00:10 | 27.13 | 26.29 |
July | 0.462046E+10 | 5046.22 | 17-JUL-15:30 | 27.60 | 25.62 | 0.00 | 0.00 | 01-JUL-00:10 | 27.60 | 25.62 |
August | 0.476953E+10 | 5284.23 | 28-AUG-10:10 | 31.08 | 26.90 | 0.00 | 0.00 | 01-AUG-00:10 | 31.08 | 26.90 |
September | 0.443784E+10 | 5688.49 | 05-SEP-07:10 | 26.83 | 25.82 | 0.00 | 0.00 | 01-SEP-00:10 | 26.83 | 25.82 |
October | 0.435517E+10 | 5199.41 | 10-OCT-07:10 | 23.92 | 23.32 | 0.00 | 0.00 | 01-OCT-00:10 | 23.92 | 23.32 |
November | 0.428155E+10 | 5243.01 | 13-NOV-08:65 | 27.58 | 25.39 | 0.00 | 0.00 | 01-NOV-00:10 | 27.58 | 25.39 |
December | 0.408216E+10 | 5214.89 | 26-DEC-08:70 | 24.17 | 21.80 | 0.00 | 0.00 | 01-DEC-00:10 | 24.17 | 21.80 |
Annual Sum or Average | 0.561766E+11 | 0.00 | ||||||||
Minimum of Months | 0.408216E+10 | 5046.22 | 20.78 | 19.94 | 0.00 | 0.00 | 20.78 | 19.94 | ||
Maximum of Months | 0.537736E+10 | 7024.82 | 34.30 | 26.90 | 0.00 | 0.00 | 34.30 | 26.90 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.508590E+10 | 5872.74 | 02-JAN-08:70 | 24.83 | 23.54 | 0.00 | 0.00 | 01-JAN-00:10 | 24.83 | 23.54 |
February | 0.478253E+10 | 6153.27 | 21-FEB-07:10 | 24.33 | 20.72 | 0.00 | 0.00 | 01-FEB-00:10 | 24.33 | 20.72 |
March | 0.560037E+10 | 5833.65 | 27-MAR-07:10 | 27.33 | 24.91 | 0.00 | 0.00 | 01-MAR-00:10 | 27.33 | 24.91 |
April | 0.531455E+10 | 6540.31 | 11-APR-12:10 | 33.67 | 26.49 | 0.00 | 0.00 | 01-APR-00:10 | 33.67 | 26.49 |
May | 0.569171E+10 | 6516.39 | 30-MAY-07:10 | 29.42 | 27.87 | 0.00 | 0.00 | 01-MAY-00:10 | 29.42 | 27.87 |
June | 0.587770E+10 | 6216.94 | 19-JUN-07:10 | 27.83 | 26.68 | 0.00 | 0.00 | 01-JUN-00:10 | 27.83 | 26.68 |
July | 0.521424E+10 | 5810.05 | 03-JUL-12:10 | 27.78 | 25.34 | 0.00 | 0.00 | 01-JUL-00:10 | 27.78 | 25.34 |
August | 0.539510E+10 | 6013.39 | 07-AUG-12:10 | 31.90 | 28.04 | 0.00 | 0.00 | 01-AUG-00:10 | 31.90 | 28.04 |
September | 0.495751E+10 | 6338.47 | 05-SEP-07:10 | 26.83 | 25.82 | 0.00 | 0.00 | 01-SEP-00:10 | 26.83 | 25.82 |
October | 0.490482E+10 | 5886.13 | 10-OCT-07:10 | 23.92 | 23.32 | 0.00 | 0.00 | 01-OCT-00:10 | 23.92 | 23.32 |
November | 0.484294E+10 | 5551.07 | 13-NOV-08:10 | 27.58 | 25.39 | 0.00 | 0.00 | 01-NOV-00:10 | 27.58 | 25.39 |
December | 0.471315E+10 | 5520.86 | 26-DEC-07:10 | 23.17 | 21.69 | 0.00 | 0.00 | 01-DEC-00:10 | 23.17 | 21.69 |
Annual Sum or Average | 0.623805E+11 | 0.00 | ||||||||
Minimum of Months | 0.471315E+10 | 5520.86 | 23.17 | 20.72 | 0.00 | 0.00 | 23.17 | 20.72 | ||
Maximum of Months | 0.587770E+10 | 6540.31 | 33.67 | 28.04 | 0.00 | 0.00 | 33.67 | 28.04 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211675E+11 | 34143.80 | 09-JAN-05:04 | 23.92 | 23.24 | 0.199289E+10 | 2606.59 | 11-JAN-14:00 | 33.00 | 24.27 |
February | 0.194022E+11 | 35082.06 | 06-FEB-05:04 | 23.17 | 21.81 | 0.180757E+10 | 2606.58 | 07-FEB-14:00 | 32.00 | 26.09 |
March | 0.224353E+11 | 34494.36 | 13-MAR-04:04 | 26.17 | 24.04 | 0.215824E+10 | 2606.57 | 03-MAR-10:09 | 26.17 | 24.04 |
April | 0.210003E+11 | 35144.65 | 10-APR-04:04 | 25.17 | 23.75 | 0.191589E+10 | 2606.60 | 10-APR-09:20 | 30.50 | 26.44 |
May | 0.224610E+11 | 31444.38 | 09-MAY-04:03 | 24.17 | 24.17 | 0.207557E+10 | 2606.60 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.222681E+11 | 35104.13 | 26-JUN-04:04 | 24.00 | 23.59 | 0.206938E+10 | 2606.62 | 28-JUN-13:30 | 34.10 | 26.99 |
July | 0.208039E+11 | 34814.94 | 24-JUL-04:04 | 25.67 | 24.17 | 0.192310E+10 | 2606.58 | 10-JUL-13:00 | 25.67 | 24.17 |
August | 0.216491E+11 | 35042.43 | 21-AUG-04:04 | 24.17 | 23.75 | 0.215860E+10 | 2606.60 | 28-AUG-09:20 | 30.97 | 27.04 |
September | 0.202459E+11 | 34782.14 | 25-SEP-04:04 | 26.00 | 25.36 | 0.191619E+10 | 2608.62 | 05-SEP-09:20 | 26.00 | 25.36 |
October | 0.206313E+11 | 35122.56 | 23-OCT-04:04 | 22.58 | 22.48 | 0.199308E+10 | 2606.64 | 13-OCT-13:30 | 22.58 | 22.48 |
November | 0.202968E+11 | 33253.61 | 20-NOV-05:04 | 24.00 | 22.62 | 0.197319E+10 | 2606.66 | 16-NOV-14:20 | 24.00 | 22.62 |
December | 0.200454E+11 | 34965.16 | 26-DEC-05:04 | 22.00 | 21.88 | 0.192218E+10 | 2606.60 | 04-DEC-14:00 | 22.00 | 21.88 |
Annual Sum or Average | 0.252407E+12 | 0.239059E+11 | ||||||||
Minimum of Months | 0.194022E+11 | 31444.38 | 22.00 | 21.81 | 0.180757E+10 | 2606.57 | 22.00 | 21.88 | ||
Maximum of Months | 0.224610E+11 | 35144.65 | 26.17 | 25.36 | 0.215860E+10 | 2608.62 | 34.10 | 27.04 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.219782E+11 | 35881.05 | 17-JAN-05:02 | 21.33 | 20.02 | 0.199243E+10 | 2606.66 | 24-JAN-10:30 | 23.70 | 19.15 |
February | 0.204485E+11 | 35225.39 | 21-FEB-05:02 | 25.00 | 21.63 | 0.180729E+10 | 2606.59 | 15-FEB-14:00 | 25.00 | 21.63 |
March | 0.241565E+11 | 34572.14 | 06-MAR-05:02 | 24.00 | 21.84 | 0.215831E+10 | 2606.59 | 03-MAR-10:09 | 24.00 | 21.84 |
April | 0.230535E+11 | 34231.58 | 13-APR-04:03 | 25.83 | 23.88 | 0.191676E+10 | 2606.59 | 20-APR-13:39 | 34.10 | 26.60 |
May | 0.243742E+11 | 36270.61 | 22-MAY-04:04 | 27.00 | 26.56 | 0.207622E+10 | 2606.62 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.242708E+11 | 34913.04 | 27-JUN-04:02 | 23.17 | 23.17 | 0.207007E+10 | 2606.61 | 28-JUN-13:09 | 34.17 | 26.79 |
July | 0.222818E+11 | 35049.75 | 17-JUL-04:02 | 24.42 | 23.35 | 0.192357E+10 | 2606.57 | 03-JUL-13:20 | 24.42 | 23.35 |
August | 0.229745E+11 | 34220.79 | 29-AUG-04:02 | 25.33 | 24.59 | 0.215844E+10 | 2606.59 | 17-AUG-13:00 | 25.33 | 24.59 |
September | 0.217184E+11 | 34217.17 | 26-SEP-04:02 | 26.00 | 25.44 | 0.191644E+10 | 2606.59 | 11-SEP-13:00 | 26.00 | 25.44 |
October | 0.216233E+11 | 35742.53 | 23-OCT-04:02 | 22.58 | 22.48 | 0.199330E+10 | 2606.62 | 13-OCT-13:09 | 22.58 | 22.48 |
November | 0.211432E+11 | 35355.14 | 27-NOV-05:03 | 22.00 | 20.87 | 0.197295E+10 | 2606.67 | 16-NOV-14:09 | 22.00 | 20.87 |
December | 0.206074E+11 | 35255.52 | 26-DEC-05:02 | 22.00 | 21.88 | 0.192123E+10 | 2606.65 | 21-DEC-10:09 | 22.00 | 21.88 |
Annual Sum or Average | 0.268630E+12 | 0.239070E+11 | ||||||||
Minimum of Months | 0.204485E+11 | 34217.17 | 21.33 | 20.02 | 0.180729E+10 | 2606.57 | 22.00 | 19.15 | ||
Maximum of Months | 0.243742E+11 | 36270.61 | 27.00 | 26.56 | 0.215844E+10 | 2606.67 | 34.17 | 26.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.639411E+10 | 10111.43 | 09-JAN-05:02 | 23.92 | 23.24 | 0.420333E+09 | 549.50 | 24-JAN-10:30 | 23.70 | 19.15 |
February | 0.617746E+10 | 11244.37 | 26-FEB-15:32 | 34.40 | 24.93 | 0.381535E+09 | 549.49 | 15-FEB-14:00 | 34.40 | 24.93 |
March | 0.756958E+10 | 12687.88 | 19-MAR-15:32 | 34.80 | 24.95 | 0.455561E+09 | 549.49 | 01-MAR-14:00 | 34.80 | 24.95 |
April | 0.754194E+10 | 12537.62 | 02-APR-16:12 | 33.00 | 27.09 | 0.405004E+09 | 549.49 | 20-APR-13:00 | 34.50 | 26.74 |
May | 0.867780E+10 | 12755.25 | 07-MAY-13:52 | 34.00 | 26.51 | 0.438742E+09 | 549.67 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.935677E+10 | 12860.71 | 18-JUN-16:32 | 30.73 | 26.82 | 0.437367E+09 | 549.65 | 19-JUN-13:39 | 29.50 | 26.97 |
July | 0.776217E+10 | 12698.20 | 04-JUL-15:32 | 31.67 | 25.13 | 0.406538E+09 | 549.56 | 28-JUL-13:20 | 32.17 | 26.06 |
August | 0.754188E+10 | 12280.11 | 13-AUG-15:32 | 31.53 | 27.39 | 0.455650E+09 | 549.57 | 01-AUG-13:00 | 31.53 | 27.39 |
September | 0.679198E+10 | 12636.28 | 04-SEP-12:43 | 32.42 | 27.44 | 0.404720E+09 | 549.48 | 11-SEP-13:00 | 27.00 | 24.83 |
October | 0.644067E+10 | 12569.76 | 09-OCT-13:23 | 29.25 | 26.07 | 0.420872E+09 | 549.49 | 13-OCT-13:09 | 31.75 | 26.46 |
November | 0.622644E+10 | 10953.32 | 20-NOV-05:02 | 24.00 | 22.62 | 0.416496E+09 | 549.50 | 16-NOV-14:09 | 24.00 | 22.62 |
December | 0.594299E+10 | 10128.56 | 26-DEC-05:02 | 22.00 | 21.88 | 0.405337E+09 | 549.49 | 21-DEC-10:09 | 22.00 | 21.88 |
Annual Sum or Average | 0.864238E+11 | 0.504815E+10 | ||||||||
Minimum of Months | 0.594299E+10 | 10111.43 | 22.00 | 21.88 | 0.381535E+09 | 549.48 | 22.00 | 19.15 | ||
Maximum of Months | 0.935677E+10 | 12860.71 | 34.80 | 27.44 | 0.455650E+09 | 549.67 | 34.80 | 27.39 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.521526E+10 | 11352.68 | 16-JAN-11:32 | 30.03 | 21.52 | 0.266430E+09 | 347.88 | 24-JAN-10:30 | 23.70 | 19.15 |
February | 0.515998E+10 | 9486.13 | 05-FEB-12:23 | 31.15 | 24.54 | 0.241815E+09 | 347.87 | 15-FEB-14:00 | 29.00 | 24.59 |
March | 0.636961E+10 | 11498.69 | 19-MAR-10:12 | 32.80 | 23.42 | 0.288580E+09 | 348.05 | 17-MAR-09:00 | 32.80 | 23.42 |
April | 0.622914E+10 | 11552.52 | 23-APR-09:02 | 27.78 | 23.87 | 0.256541E+09 | 348.13 | 12-APR-09:00 | 27.78 | 23.87 |
May | 0.619674E+10 | 9478.14 | 07-MAY-09:53 | 33.20 | 27.88 | 0.277731E+09 | 348.08 | 05-MAY-09:00 | 33.20 | 27.88 |
June | 0.635474E+10 | 11926.82 | 18-JUN-08:32 | 30.67 | 27.14 | 0.276799E+09 | 347.87 | 28-JUN-13:09 | 34.17 | 26.79 |
July | 0.535530E+10 | 9778.55 | 02-JUL-10:53 | 30.60 | 26.21 | 0.257272E+09 | 347.87 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.572363E+10 | 11545.35 | 27-AUG-08:43 | 30.67 | 28.46 | 0.288465E+09 | 348.14 | 09-AUG-09:00 | 30.67 | 28.46 |
September | 0.534685E+10 | 11491.73 | 04-SEP-08:43 | 29.67 | 26.75 | 0.256347E+09 | 348.14 | 05-SEP-09:00 | 31.20 | 26.93 |
October | 0.503888E+10 | 11250.72 | 08-OCT-11:13 | 31.00 | 26.41 | 0.266497E+09 | 347.87 | 13-OCT-13:09 | 31.75 | 26.46 |
November | 0.486603E+10 | 8669.76 | 11-NOV-11:43 | 30.75 | 25.39 | 0.263882E+09 | 347.88 | 09-NOV-14:50 | 30.75 | 25.39 |
December | 0.478627E+10 | 6693.63 | 26-DEC-07:03 | 23.17 | 21.69 | 0.256989E+09 | 347.88 | 21-DEC-10:09 | 23.17 | 21.69 |
Annual Sum or Average | 0.666424E+11 | 0.319735E+10 | ||||||||
Minimum of Months | 0.478627E+10 | 6693.63 | 23.17 | 21.52 | 0.241815E+09 | 347.87 | 23.17 | 19.15 | ||
Maximum of Months | 0.636961E+10 | 11926.82 | 33.20 | 28.46 | 0.288580E+09 | 348.14 | 34.17 | 28.46 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.929713E+10 | 13588.31 | 16-JAN-11:32 | 30.03 | 21.52 | 0.422702E+09 | 578.99 | 04-JAN-14:09 | 30.03 | 21.52 |
February | 0.830825E+10 | 12919.65 | 20-FEB-13:12 | 32.73 | 24.46 | 0.382716E+09 | 576.58 | 21-FEB-14:20 | 34.67 | 21.94 |
March | 0.863298E+10 | 12670.93 | 19-MAR-14:52 | 35.00 | 24.37 | 0.455790E+09 | 549.65 | 06-MAR-14:00 | 35.00 | 24.37 |
April | 0.742242E+10 | 12221.12 | 02-APR-16:12 | 33.00 | 27.09 | 0.404958E+09 | 549.86 | 03-APR-13:00 | 32.10 | 25.45 |
May | 0.784967E+10 | 12244.68 | 07-MAY-13:52 | 34.00 | 26.51 | 0.438504E+09 | 549.49 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.779150E+10 | 12170.28 | 18-JUN-16:32 | 30.73 | 26.82 | 0.437076E+09 | 549.49 | 28-JUN-13:09 | 34.17 | 26.79 |
July | 0.687942E+10 | 10833.80 | 03-JUL-04:02 | 25.00 | 22.79 | 0.406298E+09 | 549.48 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.713406E+10 | 11666.60 | 13-AUG-12:13 | 33.33 | 28.47 | 0.455528E+09 | 549.48 | 25-AUG-13:00 | 29.00 | 26.74 |
September | 0.708984E+10 | 12458.48 | 04-SEP-12:43 | 32.42 | 27.44 | 0.404778E+09 | 549.71 | 11-SEP-13:39 | 28.90 | 25.49 |
October | 0.752585E+10 | 12842.93 | 08-OCT-12:32 | 31.87 | 26.74 | 0.421151E+09 | 549.69 | 31-OCT-13:20 | 27.90 | 25.30 |
November | 0.819082E+10 | 13025.05 | 11-NOV-11:43 | 30.75 | 25.39 | 0.417090E+09 | 551.28 | 20-NOV-14:09 | 31.00 | 24.79 |
December | 0.874826E+10 | 12970.82 | 31-DEC-13:32 | 32.00 | 24.36 | 0.408223E+09 | 582.77 | 26-DEC-14:09 | 32.00 | 24.36 |
Annual Sum or Average | 0.948702E+11 | 0.505481E+10 | ||||||||
Minimum of Months | 0.687942E+10 | 10833.80 | 25.00 | 21.52 | 0.382716E+09 | 549.48 | 25.00 | 21.52 | ||
Maximum of Months | 0.929713E+10 | 13588.31 | 35.00 | 28.47 | 0.455790E+09 | 582.77 | 35.00 | 26.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.528825E+10 | 13195.53 | 16-JAN-15:32 | 31.53 | 21.99 | 0.265791E+09 | 347.85 | 24-JAN-10:30 | 23.70 | 19.15 |
February | 0.517889E+10 | 13293.28 | 26-FEB-15:32 | 34.40 | 24.93 | 0.241305E+09 | 347.85 | 15-FEB-14:00 | 34.40 | 24.93 |
March | 0.641451E+10 | 13815.56 | 19-MAR-15:32 | 34.80 | 24.95 | 0.288297E+09 | 347.85 | 01-MAR-14:00 | 34.80 | 24.95 |
April | 0.619018E+10 | 13628.04 | 02-APR-16:12 | 33.00 | 27.09 | 0.256294E+09 | 347.85 | 20-APR-13:00 | 34.50 | 26.74 |
May | 0.613181E+10 | 13213.16 | 14-MAY-15:32 | 34.87 | 27.32 | 0.277428E+09 | 347.85 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.623895E+10 | 13310.70 | 18-JUN-16:32 | 30.73 | 26.82 | 0.276597E+09 | 347.85 | 19-JUN-13:00 | 29.00 | 26.74 |
July | 0.531499E+10 | 13217.42 | 04-JUL-16:12 | 30.83 | 25.29 | 0.256953E+09 | 347.84 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.560880E+10 | 13223.07 | 27-AUG-16:02 | 32.83 | 25.70 | 0.288182E+09 | 347.84 | 25-AUG-13:00 | 32.83 | 25.70 |
September | 0.527628E+10 | 13309.82 | 04-SEP-16:42 | 32.17 | 26.80 | 0.255985E+09 | 347.84 | 11-SEP-13:00 | 27.00 | 24.83 |
October | 0.503459E+10 | 13433.63 | 15-OCT-15:42 | 29.42 | 25.55 | 0.266100E+09 | 347.85 | 13-OCT-13:09 | 29.42 | 25.55 |
November | 0.490541E+10 | 12029.39 | 19-NOV-14:52 | 31.50 | 24.93 | 0.263405E+09 | 347.85 | 09-NOV-14:50 | 31.50 | 24.93 |
December | 0.486269E+10 | 12308.16 | 25-DEC-15:52 | 31.00 | 22.24 | 0.256146E+09 | 347.85 | 21-DEC-10:09 | 31.00 | 22.24 |
Annual Sum or Average | 0.664454E+11 | 0.319248E+10 | ||||||||
Minimum of Months | 0.486269E+10 | 12029.39 | 29.42 | 21.99 | 0.241305E+09 | 347.84 | 23.70 | 19.15 | ||
Maximum of Months | 0.641451E+10 | 13815.56 | 34.87 | 27.32 | 0.288297E+09 | 347.85 | 34.80 | 26.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.644229E+10 | 8564.74 | 03-JAN-05:02 | 24.93 | 22.82 | 0.420463E+09 | 549.48 | 24-JAN-10:09 | 20.83 | 18.11 |
February | 0.610350E+10 | 8695.11 | 06-FEB-05:02 | 23.17 | 21.81 | 0.381604E+09 | 549.50 | 21-FEB-10:09 | 21.92 | 19.78 |
March | 0.727292E+10 | 9549.26 | 26-MAR-15:11 | 33.80 | 25.34 | 0.455525E+09 | 549.50 | 03-MAR-14:09 | 33.80 | 25.34 |
April | 0.721601E+10 | 8315.84 | 24-APR-04:02 | 25.00 | 24.18 | 0.404864E+09 | 549.51 | 14-APR-13:09 | 25.00 | 24.18 |
May | 0.853282E+10 | 10321.82 | 29-MAY-14:22 | 33.50 | 27.78 | 0.438765E+09 | 549.50 | 03-MAY-13:00 | 33.50 | 27.78 |
June | 0.923823E+10 | 10770.19 | 18-JUN-14:32 | 34.00 | 27.03 | 0.437653E+09 | 557.59 | 12-JUN-13:00 | 34.00 | 27.03 |
July | 0.795017E+10 | 10680.31 | 04-JUL-18:02 | 27.18 | 24.74 | 0.406707E+09 | 549.61 | 03-JUL-13:30 | 27.18 | 24.74 |
August | 0.774428E+10 | 10412.98 | 13-AUG-14:42 | 34.00 | 28.60 | 0.455875E+09 | 549.53 | 17-AUG-13:09 | 27.50 | 25.43 |
September | 0.689257E+10 | 10582.59 | 04-SEP-16:22 | 32.50 | 26.80 | 0.404803E+09 | 549.49 | 11-SEP-13:00 | 27.00 | 24.83 |
October | 0.652209E+10 | 8622.02 | 10-OCT-04:02 | 24.00 | 23.63 | 0.420861E+09 | 549.50 | 30-OCT-13:09 | 24.42 | 24.31 |
November | 0.634157E+10 | 8621.75 | 06-NOV-05:02 | 23.00 | 22.27 | 0.416560E+09 | 549.50 | 08-NOV-14:00 | 28.50 | 25.22 |
December | 0.608715E+10 | 8463.05 | 04-DEC-05:02 | 23.00 | 23.00 | 0.405632E+09 | 549.49 | 18-DEC-14:00 | 28.00 | 25.05 |
Annual Sum or Average | 0.863436E+11 | 0.504931E+10 | ||||||||
Minimum of Months | 0.608715E+10 | 8315.84 | 23.00 | 21.81 | 0.381604E+09 | 549.48 | 20.83 | 18.11 | ||
Maximum of Months | 0.923823E+10 | 10770.19 | 34.00 | 28.60 | 0.455875E+09 | 557.59 | 34.00 | 27.78 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.526783E+10 | 9681.07 | 16-JAN-10:23 | 28.70 | 21.38 | 0.266621E+09 | 347.87 | 31-JAN-10:09 | 24.17 | 21.37 |
February | 0.516659E+10 | 8802.99 | 19-FEB-10:23 | 29.45 | 24.10 | 0.241976E+09 | 347.88 | 21-FEB-10:09 | 21.92 | 19.78 |
March | 0.622068E+10 | 10208.93 | 26-MAR-09:52 | 32.80 | 25.30 | 0.288746E+09 | 347.88 | 03-MAR-14:09 | 32.80 | 25.30 |
April | 0.601063E+10 | 10015.59 | 02-APR-08:53 | 29.00 | 25.22 | 0.256630E+09 | 347.88 | 14-APR-13:09 | 29.00 | 26.30 |
May | 0.609119E+10 | 7647.61 | 07-MAY-09:53 | 33.20 | 27.88 | 0.277847E+09 | 347.88 | 03-MAY-13:00 | 33.20 | 27.88 |
June | 0.625712E+10 | 10430.14 | 18-JUN-08:32 | 30.67 | 27.14 | 0.276921E+09 | 347.87 | 28-JUN-13:50 | 34.03 | 27.19 |
July | 0.544319E+10 | 8061.56 | 03-JUL-04:02 | 25.00 | 22.79 | 0.257462E+09 | 347.87 | 03-JUL-13:09 | 23.40 | 22.58 |
August | 0.585394E+10 | 10160.86 | 27-AUG-08:43 | 30.67 | 28.46 | 0.288727E+09 | 347.90 | 17-AUG-13:09 | 30.67 | 28.46 |
September | 0.541802E+10 | 10262.30 | 04-SEP-09:02 | 30.03 | 26.99 | 0.256537E+09 | 347.87 | 11-SEP-13:00 | 27.00 | 24.83 |
October | 0.507170E+10 | 10152.64 | 08-OCT-09:32 | 30.17 | 26.36 | 0.266692E+09 | 347.88 | 30-OCT-13:09 | 24.42 | 24.31 |
November | 0.495773E+10 | 8039.03 | 24-NOV-05:02 | 24.42 | 21.44 | 0.264068E+09 | 347.88 | 08-NOV-14:00 | 24.42 | 21.44 |
December | 0.491313E+10 | 9272.68 | 31-DEC-10:02 | 30.83 | 24.89 | 0.257271E+09 | 347.87 | 18-DEC-14:00 | 30.83 | 24.89 |
Annual Sum or Average | 0.666718E+11 | 0.319950E+10 | ||||||||
Minimum of Months | 0.491313E+10 | 7647.61 | 24.42 | 21.38 | 0.241976E+09 | 347.87 | 21.92 | 19.78 | ||
Maximum of Months | 0.625712E+10 | 10430.14 | 33.20 | 28.46 | 0.288746E+09 | 347.90 | 34.03 | 28.46 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102544E+11 | 11262.57 | 16-JAN-11:42 | 30.17 | 21.60 | 0.442159E+09 | 740.78 | 04-JAN-13:09 | 30.17 | 21.60 |
February | 0.924477E+10 | 11099.51 | 21-FEB-13:00 | 34.10 | 22.08 | 0.402332E+09 | 734.94 | 21-FEB-13:09 | 34.25 | 22.07 |
March | 0.101547E+11 | 10988.54 | 21-MAR-12:00 | 35.00 | 23.21 | 0.469544E+09 | 724.52 | 21-MAR-12:09 | 35.23 | 23.19 |
April | 0.896623E+10 | 10501.30 | 18-APR-12:00 | 34.00 | 26.52 | 0.412034E+09 | 682.39 | 18-APR-12:09 | 34.03 | 26.51 |
May | 0.961909E+10 | 11396.38 | 05-MAY-12:00 | 37.00 | 25.95 | 0.447153E+09 | 753.10 | 05-MAY-12:09 | 36.90 | 26.19 |
June | 0.964226E+10 | 10876.32 | 16-JUN-12:00 | 35.00 | 28.16 | 0.446083E+09 | 708.56 | 16-JUN-12:09 | 35.17 | 28.24 |
July | 0.829750E+10 | 10002.67 | 26-JUL-17:00 | 33.00 | 26.23 | 0.410083E+09 | 629.97 | 27-JUL-12:09 | 31.48 | 25.75 |
August | 0.899921E+10 | 10510.91 | 15-AUG-12:00 | 33.70 | 27.96 | 0.460976E+09 | 680.51 | 15-AUG-12:09 | 33.32 | 27.86 |
September | 0.857011E+10 | 10370.84 | 05-SEP-12:00 | 33.00 | 26.98 | 0.410439E+09 | 671.70 | 05-SEP-12:09 | 33.02 | 26.93 |
October | 0.881941E+10 | 10607.34 | 08-OCT-13:32 | 32.43 | 26.42 | 0.427367E+09 | 669.37 | 04-OCT-12:09 | 32.43 | 26.42 |
November | 0.945407E+10 | 10728.08 | 23-NOV-14:13 | 28.83 | 25.69 | 0.429932E+09 | 673.94 | 13-NOV-13:09 | 28.83 | 25.69 |
December | 0.974589E+10 | 11205.78 | 25-DEC-12:22 | 30.00 | 24.33 | 0.424523E+09 | 710.14 | 26-DEC-13:09 | 32.00 | 23.12 |
Annual Sum or Average | 0.111768E+12 | 0.518262E+10 | ||||||||
Minimum of Months | 0.829750E+10 | 10002.67 | 28.83 | 21.60 | 0.402332E+09 | 629.97 | 28.83 | 21.60 | ||
Maximum of Months | 0.102544E+11 | 11396.38 | 37.00 | 28.16 | 0.469544E+09 | 753.10 | 36.90 | 28.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.526121E+10 | 11419.01 | 16-JAN-17:02 | 28.77 | 22.01 | 0.266448E+09 | 347.84 | 24-JAN-10:09 | 20.83 | 18.11 |
February | 0.510637E+10 | 10993.36 | 20-FEB-15:41 | 33.08 | 24.34 | 0.241795E+09 | 347.85 | 21-FEB-10:09 | 21.92 | 19.78 |
March | 0.620086E+10 | 11145.44 | 26-MAR-15:51 | 33.40 | 25.40 | 0.288660E+09 | 347.85 | 03-MAR-14:09 | 33.40 | 25.40 |
April | 0.591955E+10 | 11121.71 | 02-APR-16:12 | 33.00 | 27.09 | 0.256539E+09 | 347.86 | 14-APR-13:09 | 29.00 | 26.30 |
May | 0.598441E+10 | 10722.38 | 29-MAY-16:22 | 34.30 | 26.96 | 0.277727E+09 | 347.85 | 03-MAY-13:00 | 34.30 | 26.96 |
June | 0.613337E+10 | 10931.96 | 18-JUN-15:52 | 34.20 | 28.22 | 0.276861E+09 | 347.85 | 30-JUN-13:09 | 24.00 | 23.77 |
July | 0.536870E+10 | 11197.53 | 04-JUL-18:02 | 27.18 | 24.74 | 0.257387E+09 | 347.85 | 03-JUL-13:09 | 27.18 | 24.74 |
August | 0.571306E+10 | 10795.97 | 27-AUG-16:02 | 32.83 | 25.70 | 0.288659E+09 | 347.87 | 17-AUG-13:09 | 32.83 | 25.70 |
September | 0.529809E+10 | 11667.41 | 04-SEP-16:22 | 32.50 | 26.80 | 0.256400E+09 | 347.85 | 11-SEP-13:00 | 27.00 | 24.83 |
October | 0.502018E+10 | 10864.79 | 15-OCT-16:33 | 28.80 | 25.70 | 0.266592E+09 | 347.86 | 30-OCT-13:09 | 24.42 | 24.31 |
November | 0.492829E+10 | 8903.12 | 19-NOV-14:52 | 31.50 | 24.93 | 0.263881E+09 | 347.86 | 08-NOV-14:00 | 31.50 | 24.93 |
December | 0.490743E+10 | 11162.81 | 25-DEC-17:02 | 28.67 | 24.13 | 0.257029E+09 | 347.85 | 18-DEC-14:00 | 28.67 | 24.13 |
Annual Sum or Average | 0.658415E+11 | 0.319798E+10 | ||||||||
Minimum of Months | 0.490743E+10 | 8903.12 | 27.18 | 22.01 | 0.241795E+09 | 347.84 | 20.83 | 18.11 | ||
Maximum of Months | 0.620086E+10 | 11667.41 | 34.30 | 28.22 | 0.288660E+09 | 347.87 | 34.30 | 26.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.608299E+10 | 8822.72 | 30-JAN-05:02 | 22.92 | 21.68 | 0.420505E+09 | 549.49 | 11-JAN-14:00 | 22.92 | 21.68 |
February | 0.580692E+10 | 9075.47 | 21-FEB-05:02 | 25.00 | 21.63 | 0.381645E+09 | 549.49 | 15-FEB-14:00 | 25.00 | 21.63 |
March | 0.700398E+10 | 10509.01 | 19-MAR-15:32 | 34.80 | 24.95 | 0.455606E+09 | 549.48 | 01-MAR-14:00 | 34.80 | 24.95 |
April | 0.687136E+10 | 8996.86 | 02-APR-15:32 | 34.00 | 27.22 | 0.404905E+09 | 549.49 | 10-APR-09:20 | 30.50 | 26.44 |
May | 0.797216E+10 | 10638.47 | 07-MAY-14:32 | 34.00 | 27.03 | 0.438726E+09 | 550.32 | 05-MAY-09:20 | 34.00 | 27.03 |
June | 0.855364E+10 | 10857.05 | 04-JUN-12:53 | 32.40 | 28.53 | 0.437360E+09 | 549.67 | 28-JUN-13:30 | 34.10 | 26.99 |
July | 0.719408E+10 | 10673.14 | 04-JUL-15:32 | 31.67 | 25.13 | 0.406545E+09 | 549.57 | 10-JUL-13:30 | 28.50 | 25.89 |
August | 0.706326E+10 | 10358.90 | 13-AUG-12:13 | 33.33 | 28.47 | 0.455718E+09 | 549.70 | 15-AUG-13:50 | 27.73 | 27.13 |
September | 0.630439E+10 | 10370.32 | 04-SEP-12:32 | 32.33 | 27.45 | 0.404721E+09 | 550.01 | 05-SEP-09:20 | 30.40 | 26.94 |
October | 0.608914E+10 | 9972.63 | 09-OCT-13:23 | 29.25 | 26.07 | 0.420884E+09 | 549.50 | 13-OCT-13:09 | 31.75 | 26.46 |
November | 0.592105E+10 | 8739.83 | 06-NOV-05:02 | 23.00 | 22.27 | 0.416573E+09 | 549.50 | 09-NOV-14:00 | 27.50 | 24.88 |
December | 0.570041E+10 | 8719.62 | 26-DEC-05:02 | 22.00 | 21.88 | 0.405612E+09 | 549.49 | 04-DEC-14:00 | 22.00 | 21.88 |
Annual Sum or Average | 0.805634E+11 | 0.504880E+10 | ||||||||
Minimum of Months | 0.570041E+10 | 8719.62 | 22.00 | 21.63 | 0.381645E+09 | 549.48 | 22.00 | 21.63 | ||
Maximum of Months | 0.855364E+10 | 10857.05 | 34.80 | 28.53 | 0.455718E+09 | 550.32 | 34.80 | 27.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.487660E+10 | 7664.76 | 17-JAN-07:03 | 20.78 | 19.94 | 0.197419E+09 | 338.73 | 11-JAN-15:20 | 20.78 | 19.94 |
February | 0.479404E+10 | 9860.84 | 19-FEB-10:23 | 29.45 | 24.10 | 0.179134E+09 | 340.82 | 21-FEB-08:20 | 26.67 | 21.34 |
March | 0.584746E+10 | 10916.86 | 19-MAR-08:13 | 28.83 | 22.56 | 0.213214E+09 | 338.87 | 09-MAR-09:50 | 28.83 | 22.56 |
April | 0.563559E+10 | 10916.76 | 23-APR-09:02 | 27.78 | 23.87 | 0.189924E+09 | 339.49 | 17-APR-10:30 | 27.78 | 23.87 |
May | 0.562904E+10 | 8456.65 | 07-MAY-09:53 | 33.20 | 27.88 | 0.205482E+09 | 338.85 | 01-MAY-07:49 | 33.20 | 27.88 |
June | 0.574564E+10 | 8974.23 | 04-JUN-10:13 | 31.27 | 28.13 | 0.204542E+09 | 338.72 | 19-JUN-14:09 | 29.33 | 26.83 |
July | 0.489550E+10 | 8109.54 | 03-JUL-04:02 | 25.00 | 22.79 | 0.190704E+09 | 338.72 | 03-JUL-07:10 | 26.83 | 24.70 |
August | 0.527737E+10 | 10921.62 | 27-AUG-08:43 | 30.67 | 28.46 | 0.213112E+09 | 338.74 | 28-AUG-08:20 | 30.33 | 27.04 |
September | 0.488621E+10 | 11147.15 | 04-SEP-09:52 | 30.20 | 27.28 | 0.189795E+09 | 338.72 | 11-SEP-14:09 | 26.67 | 24.75 |
October | 0.466801E+10 | 10518.48 | 08-OCT-08:23 | 28.75 | 25.76 | 0.197478E+09 | 338.72 | 20-OCT-14:20 | 30.83 | 25.00 |
November | 0.454069E+10 | 7645.37 | 24-NOV-05:02 | 24.42 | 21.44 | 0.195533E+09 | 338.73 | 09-NOV-15:09 | 24.42 | 21.44 |
December | 0.451498E+10 | 10351.65 | 31-DEC-10:02 | 30.83 | 24.89 | 0.190546E+09 | 338.73 | 21-DEC-08:30 | 30.83 | 24.89 |
Annual Sum or Average | 0.613111E+11 | 0.236688E+10 | ||||||||
Minimum of Months | 0.451498E+10 | 7645.37 | 20.78 | 19.94 | 0.179134E+09 | 338.72 | 20.78 | 19.94 | ||
Maximum of Months | 0.584746E+10 | 11147.15 | 33.20 | 28.46 | 0.213214E+09 | 340.82 | 33.20 | 27.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.871467E+10 | 11194.54 | 29-JAN-12:23 | 30.25 | 23.13 | 0.425824E+09 | 595.24 | 17-JAN-14:09 | 30.25 | 23.13 |
February | 0.775889E+10 | 11016.87 | 26-FEB-13:13 | 34.67 | 24.42 | 0.384614E+09 | 590.19 | 21-FEB-14:09 | 34.67 | 24.42 |
March | 0.798848E+10 | 10483.82 | 19-MAR-14:52 | 35.00 | 24.37 | 0.455866E+09 | 549.63 | 08-MAR-14:50 | 35.00 | 24.37 |
April | 0.676663E+10 | 9037.41 | 02-APR-15:32 | 34.00 | 27.22 | 0.404872E+09 | 549.79 | 03-APR-13:00 | 32.10 | 25.45 |
May | 0.722246E+10 | 8792.13 | 07-MAY-14:32 | 34.00 | 27.03 | 0.438455E+09 | 549.49 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.713626E+10 | 8528.00 | 11-JUN-14:32 | 35.00 | 28.16 | 0.437024E+09 | 549.49 | 28-JUN-13:30 | 34.10 | 26.99 |
July | 0.639358E+10 | 8454.32 | 06-JUL-04:02 | 25.17 | 23.75 | 0.406264E+09 | 549.48 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.669442E+10 | 8542.32 | 13-AUG-12:13 | 33.33 | 28.47 | 0.455587E+09 | 549.49 | 28-AUG-09:20 | 30.97 | 27.04 |
September | 0.657364E+10 | 10258.35 | 10-SEP-14:31 | 32.67 | 26.74 | 0.404802E+09 | 550.02 | 05-SEP-09:20 | 32.67 | 26.74 |
October | 0.708198E+10 | 10693.04 | 09-OCT-12:02 | 31.57 | 26.98 | 0.421223E+09 | 549.84 | 13-OCT-13:09 | 31.75 | 26.46 |
November | 0.773393E+10 | 10894.69 | 11-NOV-11:32 | 30.50 | 25.40 | 0.418067E+09 | 565.70 | 20-NOV-14:09 | 31.00 | 24.79 |
December | 0.829598E+10 | 11352.91 | 03-DEC-11:42 | 31.00 | 22.63 | 0.411215E+09 | 599.03 | 26-DEC-14:09 | 31.17 | 22.67 |
Annual Sum or Average | 0.883609E+11 | 0.506381E+10 | ||||||||
Minimum of Months | 0.639358E+10 | 8454.32 | 25.17 | 22.63 | 0.384614E+09 | 549.48 | 25.00 | 22.67 | ||
Maximum of Months | 0.871467E+10 | 11352.91 | 35.00 | 28.47 | 0.455866E+09 | 599.03 | 35.00 | 27.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.497879E+10 | 11708.61 | 22-JAN-15:43 | 30.00 | 22.15 | 0.266201E+09 | 347.85 | 11-JAN-14:00 | 30.00 | 22.15 |
February | 0.484473E+10 | 11663.77 | 20-FEB-15:52 | 33.10 | 24.35 | 0.241591E+09 | 347.85 | 15-FEB-14:00 | 33.10 | 24.35 |
March | 0.593360E+10 | 12009.06 | 19-MAR-15:32 | 34.80 | 24.95 | 0.288460E+09 | 347.85 | 01-MAR-14:00 | 34.80 | 24.95 |
April | 0.564067E+10 | 11968.37 | 02-APR-16:12 | 33.00 | 27.09 | 0.256321E+09 | 347.84 | 10-APR-09:20 | 30.50 | 26.44 |
May | 0.562218E+10 | 11602.73 | 14-MAY-15:32 | 34.87 | 27.32 | 0.277535E+09 | 347.85 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.571056E+10 | 11659.19 | 11-JUN-16:32 | 33.50 | 27.84 | 0.276655E+09 | 347.85 | 28-JUN-13:30 | 34.10 | 26.99 |
July | 0.490219E+10 | 11707.29 | 04-JUL-16:12 | 30.83 | 25.29 | 0.257133E+09 | 347.84 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.523706E+10 | 11687.57 | 27-AUG-16:02 | 32.83 | 25.70 | 0.288392E+09 | 347.85 | 28-AUG-09:20 | 30.97 | 27.04 |
September | 0.487148E+10 | 12010.80 | 10-SEP-17:12 | 28.00 | 25.79 | 0.256158E+09 | 348.18 | 05-SEP-09:20 | 28.00 | 25.79 |
October | 0.470513E+10 | 11645.38 | 15-OCT-16:33 | 28.80 | 25.70 | 0.266371E+09 | 347.85 | 13-OCT-13:30 | 28.80 | 25.70 |
November | 0.461844E+10 | 10147.38 | 19-NOV-14:52 | 31.50 | 24.93 | 0.263675E+09 | 347.86 | 09-NOV-14:00 | 31.50 | 24.93 |
December | 0.462006E+10 | 11966.67 | 24-DEC-16:32 | 29.67 | 23.46 | 0.256713E+09 | 347.85 | 04-DEC-14:00 | 29.67 | 23.46 |
Annual Sum or Average | 0.616849E+11 | 0.319521E+10 | ||||||||
Minimum of Months | 0.461844E+10 | 10147.38 | 28.00 | 22.15 | 0.241591E+09 | 347.84 | 25.00 | 22.15 | ||
Maximum of Months | 0.593360E+10 | 12010.80 | 34.87 | 27.84 | 0.288460E+09 | 348.18 | 34.80 | 27.04 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39366123.56 | 6255.33 | 23-JAN-05:02 | 18.95 |
February | 31309631.41 | 6092.52 | 21-FEB-05:02 | 25.00 |
March | 27752584.78 | 4991.60 | 06-MAR-05:02 | 24.00 |
April | 24657560.10 | 5413.78 | 10-APR-04:02 | 25.17 |
May | 24353996.72 | 4414.28 | 15-MAY-04:02 | 26.33 |
June | 22271407.51 | 5018.66 | 26-JUN-04:02 | 24.00 |
July | 24583559.30 | 5400.02 | 17-JUL-04:02 | 24.42 |
August | 24478295.27 | 5235.45 | 28-AUG-04:02 | 25.33 |
September | 24959531.23 | 5094.63 | 25-SEP-04:02 | 26.00 |
October | 25361832.54 | 5654.86 | 02-OCT-04:02 | 24.00 |
November | 27962315.77 | 5680.34 | 13-NOV-05:02 | 25.00 |
December | 34888852.70 | 5746.69 | 27-DEC-06:03 | 19.17 |
Annual Sum or Average | 0.331946E+09 | |||
Minimum of Months | 22271407.51 | 4414.28 | 18.95 | |
Maximum of Months | 39366123.56 | 6255.33 | 26.33 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20533456.41 | 2289.37 | 03-JAN-05:02 | 24.93 |
February | 16852182.19 | 2222.39 | 13-FEB-05:02 | 23.92 |
March | 19990997.78 | 2644.11 | 28-MAR-04:02 | 27.25 |
April | 17391056.86 | 2778.08 | 12-APR-04:02 | 27.08 |
May | 18673267.28 | 2999.66 | 10-MAY-04:02 | 28.33 |
June | 16905525.97 | 2797.22 | 16-JUN-04:02 | 27.33 |
July | 16414682.69 | 2466.41 | 24-JUL-04:02 | 25.67 |
August | 16744217.35 | 3044.74 | 02-AUG-04:02 | 29.25 |
September | 17093405.58 | 2786.60 | 18-SEP-04:02 | 25.42 |
October | 17851356.68 | 2461.84 | 03-OCT-04:02 | 25.58 |
November | 19618936.13 | 2511.59 | 14-NOV-05:02 | 26.00 |
December | 21853071.05 | 2394.59 | 18-DEC-05:03 | 23.00 |
Annual Sum or Average | 0.219922E+09 | |||
Minimum of Months | 16414682.69 | 2222.39 | 23.00 | |
Maximum of Months | 21853071.05 | 3044.74 | 29.25 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33004272.27 | 4074.27 | 03-JAN-05:02 | 24.93 |
February | 25698773.49 | 3942.39 | 23-FEB-05:02 | 24.08 |
March | 27531399.82 | 4037.05 | 28-MAR-04:02 | 27.25 |
April | 27526443.12 | 4155.31 | 12-APR-04:02 | 27.08 |
May | 29329045.24 | 4333.30 | 10-MAY-04:02 | 28.33 |
June | 26459121.42 | 4246.06 | 16-JUN-04:02 | 27.33 |
July | 31582562.91 | 4118.13 | 06-JUL-04:02 | 25.17 |
August | 28534508.63 | 4549.02 | 02-AUG-04:02 | 29.25 |
September | 27592088.03 | 4240.77 | 07-SEP-04:02 | 26.25 |
October | 30373432.95 | 3986.00 | 03-OCT-04:02 | 25.58 |
November | 31886461.60 | 4086.94 | 14-NOV-05:02 | 26.00 |
December | 31614854.77 | 3922.07 | 21-DEC-05:03 | 18.00 |
Annual Sum or Average | 0.351133E+09 | |||
Minimum of Months | 25698773.49 | 3922.07 | 18.00 | |
Maximum of Months | 33004272.27 | 4549.02 | 29.25 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.208150E+11 | 18520.31 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.188385E+11 | 18520.31 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.216654E+11 | 18520.31 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.200796E+11 | 18520.31 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.212402E+11 | 18520.31 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.208620E+11 | 18520.31 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.204550E+11 | 18520.31 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.216654E+11 | 18520.31 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.200739E+11 | 18520.31 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.208179E+11 | 18520.31 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.203773E+11 | 18520.31 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.204522E+11 | 18520.31 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.247342E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.188385E+11 | 18520.31 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.216654E+11 | 18520.31 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.777562E+09 | 956.56 | 02-JAN-16:00 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.701308E+09 | 720.41 | 01-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.818810E+09 | 813.91 | 01-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.724336E+09 | 720.41 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.780398E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.772621E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.727106E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.809216E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.731444E+09 | 720.41 | 01-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.763128E+09 | 720.41 | 02-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.770731E+09 | 1002.10 | 27-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.758571E+09 | 1016.90 | 18-DEC-16:00 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.913523E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.701308E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.818810E+09 | 1016.90 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.492744E+09 | 623.96 | 02-JAN-16:00 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.444352E+09 | 551.63 | 07-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.518908E+09 | 549.28 | 01-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.459844E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.495824E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.491376E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.462195E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.513660E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.463574E+09 | 456.08 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.483756E+09 | 502.01 | 30-OCT-15:00 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.489440E+09 | 649.34 | 27-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.480982E+09 | 651.02 | 18-DEC-16:00 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.579665E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.444352E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.518908E+09 | 651.02 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.770953E+09 | 851.26 | 02-JAN-16:00 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.697540E+09 | 720.41 | 01-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.817971E+09 | 720.41 | 01-MAR-08:09 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.726145E+09 | 720.41 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.783737E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.776814E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.731101E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.811754E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.731532E+09 | 720.41 | 01-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.760346E+09 | 720.41 | 02-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.763796E+09 | 946.31 | 09-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.750315E+09 | 976.80 | 18-DEC-16:00 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.912201E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.697540E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.817971E+09 | 976.80 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.488702E+09 | 518.33 | 02-JAN-16:00 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.441188E+09 | 456.05 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.516910E+09 | 456.05 | 01-MAR-08:09 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.459004E+09 | 456.05 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.494969E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.490189E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.461589E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.513189E+09 | 456.05 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.463123E+09 | 456.05 | 01-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.482277E+09 | 505.51 | 23-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.483430E+09 | 571.93 | 09-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.475349E+09 | 607.59 | 18-DEC-16:00 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.576992E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.441188E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.516910E+09 | 607.59 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.776862E+09 | 946.95 | 02-JAN-16:00 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.700897E+09 | 720.41 | 01-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.818331E+09 | 797.96 | 01-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.723879E+09 | 720.41 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.780001E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.772303E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.726704E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.808544E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.730966E+09 | 720.41 | 01-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.762388E+09 | 720.41 | 02-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.769907E+09 | 994.45 | 27-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.757443E+09 | 1010.15 | 18-DEC-16:00 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.912823E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.700897E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.818331E+09 | 1010.15 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.492352E+09 | 619.97 | 02-JAN-16:00 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.444127E+09 | 545.08 | 07-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.518462E+09 | 542.82 | 01-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.459579E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.495479E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.491058E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.461859E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.513365E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.463302E+09 | 456.08 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.483409E+09 | 456.08 | 02-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.488790E+09 | 646.19 | 27-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.480341E+09 | 647.99 | 18-DEC-16:00 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.579212E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.444127E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.518462E+09 | 647.99 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.770718E+09 | 837.19 | 02-JAN-16:00 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.697298E+09 | 720.41 | 01-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.817550E+09 | 720.41 | 01-MAR-08:09 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.725719E+09 | 720.41 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.783119E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.776226E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.730474E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.811152E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.731194E+09 | 720.41 | 01-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.759967E+09 | 720.41 | 02-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.763322E+09 | 936.00 | 09-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.749973E+09 | 968.07 | 18-DEC-16:00 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.911671E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.697298E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.817550E+09 | 968.07 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.488418E+09 | 508.05 | 02-JAN-16:00 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.441024E+09 | 456.05 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.516716E+09 | 456.05 | 01-MAR-08:09 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.458738E+09 | 456.05 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.494650E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.489926E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.461290E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.512801E+09 | 456.05 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.462672E+09 | 456.05 | 01-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.481942E+09 | 456.05 | 02-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.483153E+09 | 564.09 | 09-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.475051E+09 | 601.92 | 18-DEC-16:00 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.576638E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.441024E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.516716E+09 | 601.92 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.777562E+09 | 956.55 | 02-JAN-16:00 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.701308E+09 | 720.41 | 01-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.818810E+09 | 813.89 | 01-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.724336E+09 | 720.41 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.780398E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.772621E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.727106E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.809216E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.731444E+09 | 720.41 | 01-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.763128E+09 | 720.41 | 02-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.770731E+09 | 1002.09 | 27-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.758571E+09 | 1016.89 | 18-DEC-16:00 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.913523E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.701308E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.818810E+09 | 1016.89 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.492744E+09 | 623.96 | 02-JAN-16:00 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.444352E+09 | 551.62 | 07-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.518908E+09 | 549.27 | 01-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.459844E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.495823E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.491375E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.462195E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.513660E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.463574E+09 | 456.08 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.483755E+09 | 502.00 | 30-OCT-15:00 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.489440E+09 | 649.34 | 27-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.480982E+09 | 651.02 | 18-DEC-16:00 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.579665E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.444352E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.518908E+09 | 651.02 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.770953E+09 | 851.24 | 02-JAN-16:00 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.697540E+09 | 720.41 | 01-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.817971E+09 | 720.41 | 01-MAR-08:09 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.726145E+09 | 720.41 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.783737E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.776814E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.731101E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.811754E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.731532E+09 | 720.41 | 01-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.760346E+09 | 720.41 | 02-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.763796E+09 | 946.30 | 09-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.750315E+09 | 976.79 | 18-DEC-16:00 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.912200E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.697540E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.817971E+09 | 976.79 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.488702E+09 | 518.32 | 02-JAN-16:00 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.441188E+09 | 456.05 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.516910E+09 | 456.05 | 01-MAR-08:09 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.459004E+09 | 456.05 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.494969E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.490189E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.461589E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.513189E+09 | 456.05 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.463123E+09 | 456.05 | 01-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.482277E+09 | 505.49 | 23-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.483430E+09 | 571.92 | 09-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.475349E+09 | 607.59 | 18-DEC-16:00 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.576992E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.441188E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.516910E+09 | 607.59 | 0.147531E+10 | 953.29 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.208150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.200796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.212402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.208620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.204550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.200739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.208179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.203773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.204522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.247342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.777562E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49748755.93 | 34998238.35 |
February | 0.901968E+09 | 0.701308E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71299749.05 | 9514547.59 |
March | 0.107774E+10 | 0.818810E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122583E+09 | 14051902.14 |
April | 0.956342E+09 | 0.724336E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121915E+09 | 2683352.45 |
May | 0.103597E+10 | 0.780398E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134387E+09 | 7532432.23 |
June | 0.103308E+10 | 0.772621E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119247E+09 | 9101441.35 |
July | 0.959235E+09 | 0.727106E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73981660.53 | 8048907.82 |
August | 0.107774E+10 | 0.809216E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89495880.76 | 15350167.25 |
September | 0.956342E+09 | 0.731444E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67317802.57 | 9007956.90 |
October | 0.994195E+09 | 0.763128E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53844154.87 | 16470301.72 |
November | 0.984487E+09 | 0.770731E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42797001.78 | 19525236.14 |
December | 0.959235E+09 | 0.758571E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40183875.60 | 36830067.62 |
Annual Sum or Average | 0.119305E+11 | 0.913523E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.986801E+09 | 0.183115E+09 |
Minimum of Months | 0.901968E+09 | 0.701308E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40183875.60 | 2683352.45 |
Maximum of Months | 0.107774E+10 | 0.818810E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134387E+09 | 36830067.62 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.492744E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32603618.81 | 24260914.19 |
February | 0.571020E+09 | 0.444352E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46596558.05 | 7106119.76 |
March | 0.682301E+09 | 0.518908E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79877571.68 | 10194162.52 |
April | 0.605444E+09 | 0.459844E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80447243.65 | 1998047.44 |
May | 0.655854E+09 | 0.495824E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90761545.43 | 4845350.89 |
June | 0.654023E+09 | 0.491376E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81515479.25 | 5721700.29 |
July | 0.607275E+09 | 0.462195E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50402514.42 | 5054951.55 |
August | 0.682301E+09 | 0.513660E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59523551.82 | 10234666.08 |
September | 0.605444E+09 | 0.463574E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44130386.37 | 6207003.78 |
October | 0.629407E+09 | 0.483756E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35220139.04 | 11152562.80 |
November | 0.623262E+09 | 0.489440E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27582729.91 | 13461670.60 |
December | 0.607275E+09 | 0.480982E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26113431.48 | 25334842.99 |
Annual Sum or Average | 0.755301E+10 | 0.579665E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654775E+09 | 0.125572E+09 |
Minimum of Months | 0.571020E+09 | 0.444352E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26113431.48 | 1998047.44 |
Maximum of Months | 0.682301E+09 | 0.518908E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90761545.43 | 25334842.99 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.770953E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46268662.41 | 39300707.81 |
February | 0.901968E+09 | 0.697540E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67829712.09 | 11243891.60 |
March | 0.107774E+10 | 0.817971E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119674E+09 | 15443949.58 |
April | 0.956342E+09 | 0.726145E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122549E+09 | 2640398.14 |
May | 0.103597E+10 | 0.783737E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137096E+09 | 7192519.55 |
June | 0.103308E+10 | 0.776814E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123488E+09 | 8410401.38 |
July | 0.959235E+09 | 0.731101E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76380939.19 | 7356458.91 |
August | 0.107774E+10 | 0.811754E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91206024.32 | 14777505.66 |
September | 0.956342E+09 | 0.731532E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66830103.60 | 9187114.55 |
October | 0.994195E+09 | 0.760346E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51676330.94 | 17686574.19 |
November | 0.984487E+09 | 0.763796E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39966116.61 | 21488595.69 |
December | 0.959235E+09 | 0.750315E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36499887.91 | 40380585.24 |
Annual Sum or Average | 0.119305E+11 | 0.912201E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.979465E+09 | 0.195109E+09 |
Minimum of Months | 0.901968E+09 | 0.697540E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36499887.91 | 2640398.14 |
Maximum of Months | 0.107774E+10 | 0.817971E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137096E+09 | 40380585.24 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.488702E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32578461.25 | 24592828.58 |
February | 0.570983E+09 | 0.441188E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47020935.34 | 7260938.23 |
March | 0.682256E+09 | 0.516910E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79552134.75 | 11470328.85 |
April | 0.605404E+09 | 0.459004E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79028781.90 | 2082757.11 |
May | 0.655811E+09 | 0.494969E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90477004.53 | 5136561.94 |
June | 0.653980E+09 | 0.490189E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80385017.47 | 6063730.35 |
July | 0.607235E+09 | 0.461589E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50723538.78 | 5400114.16 |
August | 0.682256E+09 | 0.513189E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59937410.38 | 11014763.20 |
September | 0.605404E+09 | 0.463123E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44538589.40 | 6492672.43 |
October | 0.629366E+09 | 0.482277E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35914277.13 | 11589663.02 |
November | 0.623221E+09 | 0.483430E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28504313.26 | 13534067.14 |
December | 0.607235E+09 | 0.475349E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26507635.13 | 25359657.87 |
Annual Sum or Average | 0.755252E+10 | 0.576992E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655168E+09 | 0.129998E+09 |
Minimum of Months | 0.570983E+09 | 0.441188E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26507635.13 | 2082757.11 |
Maximum of Months | 0.682256E+09 | 0.516910E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90477004.53 | 25359657.87 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.776862E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27885166.86 | 18520287.67 |
February | 0.901968E+09 | 0.700897E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39244773.43 | 5168718.05 |
March | 0.107774E+10 | 0.818331E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68064531.80 | 7540209.00 |
April | 0.956342E+09 | 0.723879E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67937137.61 | 1369136.36 |
May | 0.103597E+10 | 0.780001E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73533784.98 | 4502540.93 |
June | 0.103308E+10 | 0.772303E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64511015.10 | 5129769.40 |
July | 0.959235E+09 | 0.726704E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40367272.56 | 4587049.07 |
August | 0.107774E+10 | 0.808544E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48566873.42 | 9408478.49 |
September | 0.956342E+09 | 0.730966E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36854138.60 | 5086560.24 |
October | 0.994195E+09 | 0.762388E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30297056.28 | 8298579.71 |
November | 0.984487E+09 | 0.769907E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23831566.93 | 10730757.46 |
December | 0.959235E+09 | 0.757443E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22571336.38 | 20876731.45 |
Annual Sum or Average | 0.119305E+11 | 0.912823E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543665E+09 | 0.101219E+09 |
Minimum of Months | 0.901968E+09 | 0.700897E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22571336.38 | 1369136.36 |
Maximum of Months | 0.107774E+10 | 0.818331E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73533784.98 | 20876731.45 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.492352E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17664792.34 | 13523672.79 |
February | 0.571020E+09 | 0.444127E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24884483.71 | 4301124.87 |
March | 0.682301E+09 | 0.518462E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42618822.57 | 6387579.06 |
April | 0.605444E+09 | 0.459579E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42982051.51 | 1166482.51 |
May | 0.655854E+09 | 0.495479E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48729905.15 | 3033527.66 |
June | 0.654023E+09 | 0.491058E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43724055.78 | 3341473.18 |
July | 0.607275E+09 | 0.461859E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27116545.49 | 3015222.51 |
August | 0.682301E+09 | 0.513365E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31738105.91 | 6689050.90 |
September | 0.605444E+09 | 0.463302E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23502827.25 | 3829307.12 |
October | 0.629407E+09 | 0.483409E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19182303.01 | 6180594.54 |
November | 0.623262E+09 | 0.488790E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14917127.35 | 7867344.21 |
December | 0.607275E+09 | 0.480341E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14120982.16 | 14867284.45 |
Annual Sum or Average | 0.755301E+10 | 0.579212E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351182E+09 | 74202663.80 |
Minimum of Months | 0.571020E+09 | 0.444127E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14120982.16 | 1166482.51 |
Maximum of Months | 0.682301E+09 | 0.518462E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48729905.15 | 14867284.45 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.770718E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147035E+10 | 0.135387E+09 |
February | 0.901968E+09 | 0.697298E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154596E+10 | 75655069.40 |
March | 0.107774E+10 | 0.817550E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224982E+10 | 16247600.18 |
April | 0.956342E+09 | 0.725719E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219812E+10 | 1743485.39 |
May | 0.103597E+10 | 0.783119E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231066E+10 | 6637123.06 |
June | 0.103308E+10 | 0.776226E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239222E+10 | 9917517.56 |
July | 0.959235E+09 | 0.730474E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146347E+10 | 8406514.51 |
August | 0.107774E+10 | 0.811152E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192763E+10 | 12756840.39 |
September | 0.956342E+09 | 0.731194E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161515E+10 | 8925252.66 |
October | 0.994195E+09 | 0.759967E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142941E+10 | 22892537.03 |
November | 0.984487E+09 | 0.763322E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145012E+10 | 32398143.87 |
December | 0.959235E+09 | 0.749973E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122549E+10 | 0.122396E+09 |
Annual Sum or Average | 0.119305E+11 | 0.911671E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212784E+11 | 0.453363E+09 |
Minimum of Months | 0.901968E+09 | 0.697298E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122549E+10 | 1743485.39 |
Maximum of Months | 0.107774E+10 | 0.817550E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239222E+10 | 0.135387E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.488418E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17382228.88 | 13831421.66 |
February | 0.570983E+09 | 0.441024E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24793101.07 | 4502064.75 |
March | 0.682256E+09 | 0.516716E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41984374.49 | 7225085.11 |
April | 0.605404E+09 | 0.458738E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41751627.89 | 1290320.36 |
May | 0.655811E+09 | 0.494650E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48140192.12 | 3246323.27 |
June | 0.653980E+09 | 0.489926E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42638502.87 | 3569354.96 |
July | 0.607235E+09 | 0.461290E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26864112.02 | 3246526.39 |
August | 0.682256E+09 | 0.512801E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31426368.85 | 7140309.03 |
September | 0.605404E+09 | 0.462672E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23388893.57 | 4050135.85 |
October | 0.629366E+09 | 0.481942E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19190587.72 | 6494787.03 |
November | 0.623221E+09 | 0.483153E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15076220.98 | 7967416.93 |
December | 0.607235E+09 | 0.475051E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14040983.16 | 15053518.68 |
Annual Sum or Average | 0.755252E+10 | 0.576638E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346677E+09 | 77617264.01 |
Minimum of Months | 0.570983E+09 | 0.441024E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14040983.16 | 1290320.36 |
Maximum of Months | 0.682256E+09 | 0.516716E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48140192.12 | 15053518.68 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.777562E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42525456.03 | 30450461.21 |
February | 0.901968E+09 | 0.701308E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60004743.04 | 8494258.94 |
March | 0.107774E+10 | 0.818810E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103666E+09 | 12350246.81 |
April | 0.956342E+09 | 0.724336E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104148E+09 | 2338119.40 |
May | 0.103597E+10 | 0.780398E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113585E+09 | 6395944.37 |
June | 0.103308E+10 | 0.772621E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101303E+09 | 7577257.31 |
July | 0.959235E+09 | 0.727106E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62753849.67 | 6754122.28 |
August | 0.107774E+10 | 0.809216E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75856076.47 | 13342602.06 |
September | 0.956342E+09 | 0.731444E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57133656.47 | 7639526.07 |
October | 0.994195E+09 | 0.763128E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46264062.65 | 13835938.80 |
November | 0.984487E+09 | 0.770731E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36488326.90 | 17136856.82 |
December | 0.959235E+09 | 0.758571E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34288879.59 | 32441513.48 |
Annual Sum or Average | 0.119305E+11 | 0.913523E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838018E+09 | 0.158757E+09 |
Minimum of Months | 0.901968E+09 | 0.701308E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34288879.59 | 2338119.40 |
Maximum of Months | 0.107774E+10 | 0.818810E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113585E+09 | 32441513.48 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.492744E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27725437.29 | 20961094.27 |
February | 0.421807E+09 | 0.444352E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39080876.79 | 6289680.41 |
March | 0.502994E+09 | 0.518908E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67355224.59 | 8897472.29 |
April | 0.447140E+09 | 0.459844E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68482400.05 | 1730678.11 |
May | 0.484071E+09 | 0.495823E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76764172.16 | 4117328.70 |
June | 0.482240E+09 | 0.491375E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69452443.96 | 4762392.94 |
July | 0.448971E+09 | 0.462195E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42892300.36 | 4230105.94 |
August | 0.502994E+09 | 0.513660E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50401467.26 | 8895664.60 |
September | 0.447140E+09 | 0.463574E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37252632.43 | 5281183.98 |
October | 0.465148E+09 | 0.483755E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30076364.14 | 9425776.48 |
November | 0.460569E+09 | 0.489440E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23423141.10 | 11777412.26 |
December | 0.448971E+09 | 0.480982E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22153668.21 | 22190850.95 |
Annual Sum or Average | 0.557719E+10 | 0.579665E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555060E+09 | 0.108560E+09 |
Minimum of Months | 0.421807E+09 | 0.444352E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22153668.21 | 1730678.11 |
Maximum of Months | 0.502994E+09 | 0.518908E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76764172.16 | 22190850.95 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.770953E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38672441.18 | 34039175.11 |
February | 0.901968E+09 | 0.697540E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56608200.94 | 10009728.80 |
March | 0.107774E+10 | 0.817971E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100825E+09 | 13506596.35 |
April | 0.956342E+09 | 0.726145E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104739E+09 | 2302099.15 |
May | 0.103597E+10 | 0.783737E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116370E+09 | 6125678.33 |
June | 0.103308E+10 | 0.776814E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105552E+09 | 6978734.55 |
July | 0.959235E+09 | 0.731101E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65383233.67 | 6129132.45 |
August | 0.107774E+10 | 0.811754E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77471535.94 | 12878619.73 |
September | 0.956342E+09 | 0.731532E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56527487.81 | 7785340.49 |
October | 0.994195E+09 | 0.760346E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43914922.96 | 14911743.98 |
November | 0.984487E+09 | 0.763796E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33602982.47 | 18801688.40 |
December | 0.959235E+09 | 0.750315E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30587726.94 | 35358089.08 |
Annual Sum or Average | 0.119305E+11 | 0.912200E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830254E+09 | 0.168827E+09 |
Minimum of Months | 0.901968E+09 | 0.697540E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30587726.94 | 2302099.15 |
Maximum of Months | 0.107774E+10 | 0.817971E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116370E+09 | 35358089.08 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.488702E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27268141.91 | 21439793.84 |
February | 0.570983E+09 | 0.441188E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39013714.50 | 6512447.39 |
March | 0.682256E+09 | 0.516910E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66430363.46 | 10036348.21 |
April | 0.605404E+09 | 0.459004E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66565843.29 | 1839383.50 |
May | 0.655811E+09 | 0.494969E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75758756.60 | 4380312.70 |
June | 0.653980E+09 | 0.490189E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67912263.37 | 5104882.89 |
July | 0.607235E+09 | 0.461589E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42549654.10 | 4578325.87 |
August | 0.682256E+09 | 0.513189E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50120301.05 | 9614619.21 |
September | 0.605404E+09 | 0.463123E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37195584.74 | 5631259.65 |
October | 0.629366E+09 | 0.482277E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30304303.26 | 9937315.82 |
November | 0.623221E+09 | 0.483430E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23816161.96 | 11953912.28 |
December | 0.607235E+09 | 0.475349E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22071084.42 | 22378113.91 |
Annual Sum or Average | 0.755252E+10 | 0.576992E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549006E+09 | 0.113407E+09 |
Minimum of Months | 0.570983E+09 | 0.441188E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22071084.42 | 1839383.50 |
Maximum of Months | 0.682256E+09 | 0.516910E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75758756.60 | 22378113.91 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44538641.10 | 39723792.38 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67606169.53 | 9392560.17 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121341E+09 | 13472357.10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129081E+09 | 2094295.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141611E+09 | 6662896.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127376E+09 | 7971076.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77096716.07 | 6406817.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89724637.18 | 13080700.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66794425.27 | 7701200.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52427414.38 | 15456129.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39295986.06 | 20635899.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35931024.96 | 43082402.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992824E+09 | 0.185680E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35931024.96 | 2094295.27 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141611E+09 | 43082402.03 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58155117.59 | 50344718.80 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87807528.69 | 11665842.77 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156710E+09 | 16834197.05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166030E+09 | 2674149.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181437E+09 | 8226663.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163462E+09 | 10229289.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99982539.37 | 8213711.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116855E+09 | 15614840.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86831880.02 | 9538096.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68041990.56 | 19878810.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51395100.95 | 25428322.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47000786.03 | 53804671.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128371E+10 | 0.232453E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47000786.03 | 2674149.27 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181437E+09 | 53804671.10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52836452.08 | 43585710.17 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82865986.19 | 7046526.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155828E+09 | 11201107.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164542E+09 | 1729288.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183367E+09 | 7333570.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160086E+09 | 10952527.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85242234.14 | 9009861.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113695E+09 | 14280521.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78853444.06 | 10578689.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57260463.04 | 20167827.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45522419.55 | 22411176.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39620668.07 | 45908400.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121972E+10 | 0.204205E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39620668.07 | 1729288.28 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183367E+09 | 45908400.44 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 18520.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 18520.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 18520.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 18520.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 18520.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 18520.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 18520.31 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 18520.31 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 18520.31 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 18520.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 18520.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 18520.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 956.56 | 02-JAN-16:00 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.45 | 15-JAN-13:00 | 444.79 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 720.41 | 01-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 360.50 | 20-FEB-15:56 | 55.36 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 813.91 | 01-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 628.51 | 19-MAR-16:00 | 97.48 | 03-MAR-05:35 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.03 | 30-APR-15:36 | 37.65 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 447.21 | 07-MAY-14:55 | 179.53 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 411.76 | 18-JUN-14:35 | 210.39 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 348.08 | 04-JUL-14:15 | 109.51 | 02-JUL-13:30 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 391.53 | 06-AUG-13:00 | 205.37 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 720.41 | 01-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 420.28 | 10-SEP-14:52 | 114.17 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 720.41 | 02-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 388.33 | 29-OCT-12:58 | 97.92 | 22-OCT-18:00 |
November | 1306.65 | 01-NOV-09:09 | 1002.10 | 27-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.67 | 11-NOV-15:50 | 98.98 | 26-NOV-10:00 |
December | 1306.65 | 01-DEC-10:09 | 1016.90 | 18-DEC-16:00 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 150.11 | 31-DEC-09:53 | 177.25 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 150.11 | 37.65 | |||||
Maximum of Months | 1306.65 | 1016.90 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 628.51 | 444.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 623.96 | 02-JAN-16:00 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 121.50 | 15-JAN-13:00 | 296.76 | 07-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 551.63 | 07-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 245.21 | 20-FEB-15:56 | 57.17 | 19-FEB-07:00 |
March | 827.22 | 01-MAR-10:09 | 549.28 | 01-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 420.48 | 19-MAR-15:35 | 65.14 | 03-MAR-05:35 |
April | 827.22 | 03-APR-09:09 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.24 | 02-APR-15:35 | 36.21 | 23-APR-07:07 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 306.01 | 07-MAY-14:36 | 119.75 | 08-MAY-22:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.99 | 18-JUN-14:35 | 137.71 | 20-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.86 | 04-JUL-14:18 | 70.84 | 02-JUL-13:30 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.42 | 06-AUG-12:55 | 145.97 | 20-AUG-10:50 |
September | 827.22 | 01-SEP-09:09 | 456.08 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 286.67 | 10-SEP-14:52 | 75.72 | 15-SEP-22:00 |
October | 827.22 | 02-OCT-09:09 | 502.01 | 30-OCT-15:00 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.61 | 29-OCT-12:58 | 65.05 | 22-OCT-18:00 |
November | 827.22 | 01-NOV-09:09 | 649.34 | 27-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.83 | 11-NOV-15:50 | 72.31 | 26-NOV-10:00 |
December | 827.22 | 01-DEC-10:09 | 651.02 | 18-DEC-16:00 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 102.21 | 31-DEC-12:58 | 117.93 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 102.21 | 36.21 | |||||
Maximum of Months | 827.22 | 651.02 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 420.48 | 296.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 851.26 | 02-JAN-16:00 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.73 | 15-JAN-13:00 | 459.30 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 720.41 | 01-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.30 | 19-FEB-15:00 | 63.45 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 720.41 | 01-MAR-08:09 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 628.51 | 19-MAR-16:00 | 98.70 | 03-MAR-05:35 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.36 | 30-APR-15:36 | 37.16 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 447.35 | 07-MAY-14:55 | 177.63 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 415.52 | 18-JUN-13:56 | 203.69 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.79 | 04-JUL-14:18 | 93.51 | 02-JUL-13:30 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 410.83 | 06-AUG-13:00 | 203.61 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 720.41 | 01-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 420.39 | 10-SEP-14:52 | 115.32 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 720.41 | 02-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 376.02 | 29-OCT-12:55 | 99.80 | 22-OCT-18:00 |
November | 1306.65 | 01-NOV-09:09 | 946.31 | 09-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.08 | 11-NOV-15:48 | 108.50 | 26-NOV-10:00 |
December | 1306.65 | 01-DEC-10:09 | 976.80 | 18-DEC-16:00 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 140.41 | 31-DEC-13:00 | 180.75 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 140.41 | 37.16 | |||||
Maximum of Months | 1306.65 | 976.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 628.51 | 459.30 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 518.33 | 02-JAN-16:00 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 135.84 | 15-JAN-13:00 | 298.30 | 07-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 456.05 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 234.02 | 20-FEB-15:54 | 39.00 | 19-FEB-07:00 |
March | 827.17 | 01-MAR-10:09 | 456.05 | 01-MAR-08:09 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 418.98 | 19-MAR-16:00 | 66.13 | 03-MAR-05:35 |
April | 827.17 | 03-APR-09:09 | 456.05 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.99 | 30-APR-15:34 | 37.11 | 09-APR-16:03 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 299.63 | 21-MAY-11:53 | 120.91 | 08-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 281.74 | 18-JUN-13:54 | 141.39 | 20-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.10 | 04-JUL-14:15 | 72.98 | 02-JUL-14:10 |
August | 827.17 | 01-AUG-09:09 | 456.05 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.72 | 06-AUG-12:55 | 136.22 | 20-AUG-11:00 |
September | 827.17 | 01-SEP-09:09 | 456.05 | 01-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 280.04 | 10-SEP-14:52 | 76.79 | 15-SEP-22:00 |
October | 827.17 | 02-OCT-09:09 | 505.51 | 23-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.81 | 29-OCT-12:58 | 66.29 | 22-OCT-18:00 |
November | 827.17 | 01-NOV-09:09 | 571.93 | 09-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.22 | 11-NOV-15:48 | 66.84 | 26-NOV-10:00 |
December | 827.17 | 01-DEC-10:09 | 607.59 | 18-DEC-16:00 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 108.33 | 31-DEC-09:53 | 118.61 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 108.33 | 37.11 | |||||
Maximum of Months | 827.17 | 607.59 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 418.98 | 298.30 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 946.95 | 02-JAN-16:00 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 108.38 | 15-JAN-13:00 | 288.39 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 720.41 | 01-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 187.70 | 20-FEB-15:52 | 32.36 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 797.96 | 01-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 341.31 | 19-MAR-16:00 | 56.13 | 03-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.04 | 30-APR-15:50 | 23.61 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.75 | 07-MAY-14:50 | 107.14 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.65 | 18-JUN-14:20 | 119.63 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.05 | 04-JUL-14:06 | 44.78 | 02-JUL-13:30 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.93 | 06-AUG-12:55 | 114.26 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 720.41 | 01-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.20 | 10-SEP-14:52 | 71.07 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 720.41 | 02-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.97 | 29-OCT-13:10 | 51.24 | 22-OCT-18:00 |
November | 1306.65 | 01-NOV-09:09 | 994.45 | 27-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.59 | 11-NOV-16:00 | 56.38 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1010.15 | 18-DEC-16:00 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.87 | 24-DEC-15:00 | 106.59 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 86.87 | 23.61 | |||||
Maximum of Months | 1306.65 | 1010.15 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 341.31 | 288.39 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 619.97 | 02-JAN-16:00 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.38 | 15-JAN-13:00 | 200.46 | 07-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 545.08 | 07-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 124.01 | 26-FEB-15:58 | 33.29 | 20-FEB-07:00 |
March | 827.22 | 01-MAR-10:09 | 542.82 | 01-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 224.22 | 19-MAR-16:00 | 38.88 | 03-MAR-05:00 |
April | 827.22 | 03-APR-09:09 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.27 | 30-APR-15:50 | 20.17 | 23-APR-07:00 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.85 | 07-MAY-14:50 | 73.36 | 08-MAY-22:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.89 | 18-JUN-14:35 | 79.00 | 20-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.17 | 04-JUL-14:08 | 29.25 | 02-JUL-13:30 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.99 | 06-AUG-12:55 | 81.30 | 20-AUG-10:50 |
September | 827.22 | 01-SEP-09:09 | 456.08 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.82 | 10-SEP-14:52 | 49.61 | 15-SEP-22:00 |
October | 827.22 | 02-OCT-09:09 | 456.08 | 02-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.66 | 29-OCT-13:00 | 34.82 | 22-OCT-18:00 |
November | 827.22 | 01-NOV-09:09 | 646.19 | 27-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.46 | 11-NOV-15:43 | 40.71 | 26-NOV-10:00 |
December | 827.22 | 01-DEC-10:09 | 647.99 | 18-DEC-16:00 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 55.31 | 24-DEC-15:00 | 72.08 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 55.31 | 20.17 | |||||
Maximum of Months | 827.22 | 647.99 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 224.22 | 200.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 837.19 | 02-JAN-16:00 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9264.44 | 04-JAN-12:02 | 5361.86 | 24-JAN-07:03 |
February | 1306.65 | 01-FEB-10:09 | 720.41 | 01-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8988.04 | 24-FEB-17:03 | 3486.62 | 02-FEB-07:03 |
March | 1306.65 | 01-MAR-10:09 | 720.41 | 01-MAR-08:09 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11173.48 | 21-MAR-11:02 | 980.17 | 15-MAR-06:03 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11643.69 | 11-APR-16:02 | 201.20 | 14-APR-16:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13660.88 | 05-MAY-11:01 | 184.60 | 17-MAY-05:03 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12249.55 | 12-JUN-16:02 | 783.63 | 21-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9859.91 | 20-JUL-16:02 | 333.33 | 13-JUL-05:03 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10948.84 | 15-AUG-11:02 | 413.04 | 21-AUG-11:10 |
September | 1306.65 | 01-SEP-09:09 | 720.41 | 01-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9552.88 | 13-SEP-16:02 | 1253.58 | 15-SEP-17:00 |
October | 1306.65 | 02-OCT-09:09 | 720.41 | 02-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8967.07 | 04-OCT-11:02 | 1247.31 | 30-OCT-17:00 |
November | 1306.65 | 01-NOV-09:09 | 936.00 | 09-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8565.44 | 10-NOV-12:02 | 2445.58 | 27-NOV-07:03 |
December | 1306.65 | 01-DEC-10:09 | 968.07 | 18-DEC-16:00 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7670.29 | 08-DEC-12:02 | 5904.38 | 21-DEC-07:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 7670.29 | 184.60 | |||||
Maximum of Months | 1306.65 | 968.07 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 13660.88 | 5904.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 508.05 | 02-JAN-16:00 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 68.24 | 15-JAN-13:00 | 201.33 | 07-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 456.05 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 121.38 | 26-FEB-15:54 | 24.48 | 19-FEB-07:00 |
March | 827.17 | 01-MAR-10:09 | 456.05 | 01-MAR-08:09 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 224.21 | 19-MAR-16:00 | 39.92 | 03-MAR-05:00 |
April | 827.17 | 03-APR-09:09 | 456.05 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.86 | 30-APR-15:34 | 18.25 | 09-APR-16:07 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.64 | 07-MAY-15:00 | 73.80 | 08-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.55 | 18-JUN-13:54 | 80.89 | 20-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.59 | 04-JUL-14:06 | 28.17 | 02-JUL-14:10 |
August | 827.17 | 01-AUG-09:09 | 456.05 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.78 | 06-AUG-12:40 | 76.58 | 20-AUG-11:00 |
September | 827.17 | 01-SEP-09:09 | 456.05 | 01-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.88 | 10-SEP-14:50 | 50.95 | 15-SEP-22:00 |
October | 827.17 | 02-OCT-09:09 | 456.05 | 02-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.47 | 29-OCT-13:10 | 35.52 | 22-OCT-18:00 |
November | 827.17 | 01-NOV-09:09 | 564.09 | 09-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.33 | 11-NOV-15:38 | 38.50 | 25-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 601.92 | 18-DEC-16:00 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.02 | 31-DEC-12:50 | 72.39 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 54.02 | 18.25 | |||||
Maximum of Months | 827.17 | 601.92 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 224.21 | 201.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 956.55 | 02-JAN-16:00 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.33 | 15-JAN-13:00 | 417.69 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 720.41 | 01-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 298.51 | 20-FEB-15:58 | 50.43 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 813.89 | 01-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 524.88 | 19-MAR-16:00 | 85.44 | 03-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.33 | 30-APR-15:50 | 34.89 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.77 | 07-MAY-14:55 | 151.00 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.09 | 18-JUN-14:05 | 171.02 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.05 | 04-JUL-14:15 | 74.30 | 02-JUL-13:40 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.46 | 06-AUG-13:00 | 175.64 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 720.41 | 01-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 353.70 | 10-SEP-15:00 | 100.56 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 720.41 | 02-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.23 | 29-OCT-13:10 | 82.70 | 23-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1002.09 | 27-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.99 | 11-NOV-16:00 | 85.56 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1016.89 | 18-DEC-16:00 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 129.67 | 24-DEC-15:00 | 159.80 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 129.67 | 34.89 | |||||
Maximum of Months | 1306.65 | 1016.89 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 524.88 | 417.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 623.96 | 02-JAN-16:00 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.10 | 15-JAN-13:00 | 278.25 | 07-JAN-05:00 |
February | 805.43 | 01-FEB-08:09 | 551.62 | 07-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 202.30 | 20-FEB-15:56 | 50.42 | 19-FEB-07:00 |
March | 805.43 | 01-MAR-08:09 | 549.27 | 01-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 349.92 | 19-MAR-16:00 | 57.13 | 03-MAR-05:00 |
April | 805.43 | 03-APR-07:10 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.78 | 30-APR-15:50 | 31.84 | 23-APR-07:00 |
May | 805.43 | 01-MAY-07:10 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 257.98 | 07-MAY-14:50 | 100.61 | 08-MAY-22:00 |
June | 805.43 | 01-JUN-07:10 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.05 | 18-JUN-14:08 | 111.85 | 20-JUN-23:00 |
July | 805.43 | 03-JUL-07:10 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.76 | 04-JUL-13:53 | 44.70 | 02-JUL-13:40 |
August | 805.43 | 01-AUG-07:10 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.25 | 06-AUG-12:55 | 125.30 | 20-AUG-10:50 |
September | 805.43 | 01-SEP-07:10 | 456.08 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.32 | 10-SEP-14:52 | 66.96 | 15-SEP-22:00 |
October | 805.43 | 02-OCT-07:10 | 502.00 | 30-OCT-15:00 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.11 | 29-OCT-13:00 | 54.68 | 23-OCT-03:00 |
November | 805.43 | 01-NOV-07:10 | 649.34 | 27-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.54 | 11-NOV-16:00 | 61.11 | 26-NOV-10:00 |
December | 805.43 | 01-DEC-08:09 | 651.02 | 18-DEC-16:00 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.40 | 24-DEC-15:00 | 106.26 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 85.40 | 31.84 | |||||
Maximum of Months | 805.43 | 651.02 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 349.92 | 278.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 851.24 | 02-JAN-16:00 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 133.08 | 15-JAN-13:00 | 430.58 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 720.41 | 01-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 282.74 | 20-FEB-15:56 | 57.12 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 720.41 | 01-MAR-08:09 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 524.88 | 19-MAR-16:00 | 86.79 | 03-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.35 | 30-APR-15:50 | 34.49 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 381.51 | 07-MAY-14:50 | 149.45 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 356.02 | 18-JUN-14:20 | 165.64 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.47 | 04-JUL-13:53 | 54.96 | 02-JUL-13:40 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 348.33 | 06-AUG-13:00 | 174.11 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 720.41 | 01-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.25 | 10-SEP-14:52 | 101.30 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 720.41 | 02-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.36 | 29-OCT-12:55 | 83.36 | 23-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 946.30 | 09-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.16 | 11-NOV-15:38 | 91.68 | 26-NOV-10:00 |
December | 1306.65 | 01-DEC-10:09 | 976.79 | 18-DEC-16:00 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 117.46 | 31-DEC-13:00 | 162.62 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 117.46 | 34.49 | |||||
Maximum of Months | 1306.65 | 976.79 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 524.88 | 430.58 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 518.32 | 02-JAN-16:00 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 108.64 | 15-JAN-13:00 | 280.06 | 07-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 456.05 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 195.05 | 20-FEB-15:54 | 35.41 | 19-FEB-07:00 |
March | 827.17 | 01-MAR-10:09 | 456.05 | 01-MAR-08:09 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 349.91 | 19-MAR-16:00 | 58.29 | 03-MAR-05:00 |
April | 827.17 | 03-APR-09:09 | 456.05 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.29 | 30-APR-15:34 | 26.48 | 09-APR-16:03 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.05 | 07-MAY-15:00 | 101.66 | 08-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.94 | 18-JUN-14:05 | 115.03 | 20-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.10 | 04-JUL-13:50 | 43.06 | 02-JUL-13:40 |
August | 827.17 | 01-AUG-09:09 | 456.05 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.96 | 06-AUG-12:55 | 116.56 | 20-AUG-11:00 |
September | 827.17 | 01-SEP-09:09 | 456.05 | 01-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.17 | 10-SEP-14:52 | 68.65 | 15-SEP-22:00 |
October | 827.17 | 02-OCT-09:09 | 505.49 | 23-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.67 | 29-OCT-12:58 | 55.07 | 23-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 571.92 | 09-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.37 | 11-NOV-15:38 | 57.27 | 25-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 607.59 | 18-DEC-16:00 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.41 | 31-DEC-12:50 | 106.91 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 85.41 | 26.48 | |||||
Maximum of Months | 827.17 | 607.59 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 349.91 | 280.06 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.52 | 15-JAN-13:00 | 599.87 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.33 | 19-FEB-14:52 | 72.59 | 20-FEB-07:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 673.05 | 19-MAR-16:00 | 113.30 | 03-MAR-05:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.71 | 30-APR-16:00 | 41.79 | 22-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.83 | 07-MAY-15:00 | 179.58 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.69 | 18-JUN-14:20 | 176.62 | 20-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.58 | 04-JUL-13:53 | 59.43 | 19-JUL-21:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.46 | 06-AUG-13:00 | 185.97 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.50 | 10-SEP-14:52 | 124.36 | 15-SEP-22:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.85 | 29-OCT-13:00 | 96.52 | 23-OCT-04:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.96 | 11-NOV-16:00 | 114.77 | 25-NOV-05:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.87 | 31-DEC-13:00 | 219.11 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.87 | 41.79 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 673.05 | 599.87 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.40 | 15-JAN-13:00 | 727.40 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.45 | 19-FEB-14:52 | 93.94 | 20-FEB-06:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 855.15 | 19-MAR-16:00 | 136.32 | 03-MAR-05:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.38 | 02-APR-16:00 | 50.87 | 22-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 611.84 | 07-MAY-15:00 | 230.89 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.14 | 18-JUN-14:30 | 220.44 | 20-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.52 | 04-JUL-14:00 | 75.24 | 19-JUL-21:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 581.67 | 06-AUG-13:00 | 227.55 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.31 | 10-SEP-15:00 | 153.43 | 15-SEP-22:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.65 | 29-OCT-13:00 | 128.30 | 23-OCT-04:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.69 | 11-NOV-16:00 | 142.54 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.58 | 24-DEC-15:00 | 274.01 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.58 | 50.87 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 855.15 | 727.40 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.92 | 15-JAN-13:00 | 560.90 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.11 | 19-FEB-15:00 | 81.96 | 20-FEB-06:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 690.03 | 19-MAR-16:00 | 120.61 | 03-MAR-05:55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.55 | 09-APR-15:00 | 36.65 | 13-APR-04:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.11 | 21-MAY-12:00 | 219.28 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.23 | 18-JUN-14:00 | 268.02 | 20-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.62 | 04-JUL-13:58 | 226.50 | 02-JUL-13:30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 604.95 | 06-AUG-12:32 | 280.77 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.57 | 10-SEP-15:00 | 203.25 | 03-SEP-16:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.83 | 29-OCT-13:00 | 179.70 | 29-OCT-16:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.37 | 11-NOV-16:00 | 146.67 | 26-NOV-10:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.21 | 31-DEC-09:53 | 244.60 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.92 | 36.65 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 690.03 | 560.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 44281.66 | 23-JAN-05:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 43125.97 | 03-FEB-05:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 43250.24 | 02-MAR-05:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41782.04 | 21-APR-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43046.73 | 26-MAY-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42369.36 | 21-JUN-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 42736.41 | 19-JUL-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43041.61 | 22-AUG-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 42549.50 | 29-SEP-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 43663.81 | 23-OCT-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 43669.52 | 28-NOV-05:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 44146.62 | 27-DEC-05:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 41782.04 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44281.66 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10645.71 | 04-JAN-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.54 | 0.00 |
February | 11948.30 | 21-FEB-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.23 | 0.00 |
March | 12440.73 | 29-MAR-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.68 | 0.00 |
April | 12442.04 | 11-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.02 | 0.00 |
May | 12645.77 | 05-MAY-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.90 | 0.00 |
June | 12029.38 | 16-JUN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.46 | 0.00 |
July | 11144.70 | 14-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.52 | 0.00 |
August | 11946.56 | 14-AUG-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.40 | 0.00 |
September | 11988.03 | 06-SEP-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.63 | 0.00 |
October | 10826.47 | 02-OCT-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.03 | 0.00 |
November | 10140.12 | 22-NOV-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 | 0.00 |
December | 10560.34 | 26-DEC-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10140.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 | 0.00 | |
Maximum of Months | 12645.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.46 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5300.00 | 17-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.11 |
February | 5833.99 | 21-FEB-08:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 | 0.00 |
March | 5429.51 | 20-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.35 | 0.00 |
April | 6522.74 | 03-APR-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.79 | 0.00 |
May | 6796.39 | 08-MAY-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.49 | 0.00 |
June | 7024.82 | 19-JUN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.13 | 0.00 |
July | 5046.22 | 17-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.85 | 0.00 |
August | 5284.23 | 28-AUG-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.22 | 0.00 |
September | 5688.49 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 | 0.00 |
October | 5199.41 | 10-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.30 |
November | 5243.01 | 13-NOV-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.99 | 0.00 |
December | 5214.89 | 26-DEC-08:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5046.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7024.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.35 | 28.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5872.74 | 02-JAN-08:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
February | 6153.27 | 21-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
March | 5833.65 | 27-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 | 0.00 |
April | 6540.31 | 11-APR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.89 | 0.00 |
May | 6516.39 | 30-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6216.94 | 19-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.54 | 0.00 |
July | 5810.05 | 03-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.43 | 0.00 |
August | 6013.39 | 07-AUG-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.39 | 0.00 |
September | 6338.47 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.94 | 0.00 |
October | 5886.13 | 10-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 |
November | 5551.07 | 13-NOV-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 0.00 |
December | 5520.86 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5520.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6540.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.39 | 12.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 34143.80 | 09-JAN-05:04 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35082.06 | 06-FEB-05:04 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34494.36 | 13-MAR-04:04 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35144.65 | 10-APR-04:04 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31444.38 | 09-MAY-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35104.13 | 26-JUN-04:04 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34814.94 | 24-JUL-04:04 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35042.43 | 21-AUG-04:04 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34782.14 | 25-SEP-04:04 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35122.56 | 23-OCT-04:04 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33253.61 | 20-NOV-05:04 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 34965.16 | 26-DEC-05:04 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 31444.38 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35144.65 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 35881.05 | 17-JAN-05:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35225.39 | 21-FEB-05:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34572.14 | 06-MAR-05:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34231.58 | 13-APR-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36270.61 | 22-MAY-04:04 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34913.04 | 27-JUN-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35049.75 | 17-JUL-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34220.79 | 29-AUG-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34217.17 | 26-SEP-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35742.53 | 23-OCT-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35355.14 | 27-NOV-05:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 35255.52 | 26-DEC-05:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 34217.17 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36270.61 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10111.43 | 09-JAN-05:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.10 |
February | 11244.37 | 26-FEB-15:32 | 334.80 | 200.13 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 314.67 | 0.00 |
March | 12687.88 | 19-MAR-15:32 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 569.46 | 0.00 |
April | 12537.62 | 02-APR-16:12 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 278.45 | 0.00 |
May | 12755.25 | 07-MAY-13:52 | 334.80 | 200.13 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 365.53 | 0.00 |
June | 12860.71 | 18-JUN-16:32 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 124.17 | 0.00 |
July | 12698.20 | 04-JUL-15:32 | 334.80 | 200.13 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 267.06 | 0.00 |
August | 12280.11 | 13-AUG-15:32 | 334.80 | 200.13 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 220.97 | 0.00 |
September | 12636.28 | 04-SEP-12:43 | 267.84 | 160.10 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 141.91 | 0.00 |
October | 12569.76 | 09-OCT-13:23 | 267.84 | 160.10 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 116.16 | 0.00 |
November | 10953.32 | 20-NOV-05:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.63 |
December | 10128.56 | 26-DEC-05:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10111.43 | 0.00 | 160.10 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12860.71 | 401.76 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 569.46 | 68.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11352.68 | 16-JAN-11:32 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 21.77 | 0.00 |
February | 9486.13 | 05-FEB-12:23 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 38.41 | 0.00 |
March | 11498.69 | 19-MAR-10:12 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 180.40 | 0.00 |
April | 11552.52 | 23-APR-09:02 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 15.51 | 0.00 |
May | 9478.14 | 07-MAY-09:53 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 110.41 | 0.00 |
June | 11926.82 | 18-JUN-08:32 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 83.98 | 0.00 |
July | 9778.55 | 02-JUL-10:53 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 91.42 | 0.00 |
August | 11545.35 | 27-AUG-08:43 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 43.24 | 0.00 |
September | 11491.73 | 04-SEP-08:43 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 26.49 | 0.00 |
October | 11250.72 | 08-OCT-11:13 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 60.79 | 0.00 |
November | 8669.76 | 11-NOV-11:43 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 54.47 | 0.00 |
December | 6693.63 | 26-DEC-07:03 | 508.69 | 456.07 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6693.63 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11926.82 | 508.69 | 456.07 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 180.40 | 3.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13588.31 | 16-JAN-11:32 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 19.55 | 0.00 |
February | 12919.65 | 20-FEB-13:12 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 110.19 | 0.00 |
March | 12670.93 | 19-MAR-14:52 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 468.63 | 0.00 |
April | 12221.12 | 02-APR-16:12 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 278.44 | 0.00 |
May | 12244.68 | 07-MAY-13:52 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 376.86 | 0.00 |
June | 12170.28 | 18-JUN-16:32 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 139.01 | 0.00 |
July | 10833.80 | 03-JUL-04:02 | 0.00 | 649.16 | 3346.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 |
August | 11666.60 | 13-AUG-12:13 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 205.37 | 0.00 |
September | 12458.48 | 04-SEP-12:43 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 137.65 | 0.00 |
October | 12842.93 | 08-OCT-12:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 83.23 | 0.00 |
November | 13025.05 | 11-NOV-11:43 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 67.24 | 0.00 |
December | 12970.82 | 31-DEC-13:32 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 93.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10833.80 | 0.00 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13588.31 | 401.76 | 649.16 | 3346.41 | 0.00 | 0.00 | 0.00 | 0.00 | 468.63 | 3.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13195.53 | 16-JAN-15:32 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 44.29 | 0.00 |
February | 13293.28 | 26-FEB-15:32 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 199.41 | 0.00 |
March | 13815.56 | 19-MAR-15:32 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 341.26 | 0.00 |
April | 13628.04 | 02-APR-16:12 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 162.63 | 0.00 |
May | 13213.16 | 14-MAY-15:32 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 90.22 | 0.00 |
June | 13310.70 | 18-JUN-16:32 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 81.21 | 0.00 |
July | 13217.42 | 04-JUL-16:12 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 138.40 | 0.00 |
August | 13223.07 | 27-AUG-16:02 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 157.10 | 0.00 |
September | 13309.82 | 04-SEP-16:42 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 117.67 | 0.00 |
October | 13433.63 | 15-OCT-15:42 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 33.96 | 0.00 |
November | 12029.39 | 19-NOV-14:52 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 67.51 | 0.00 |
December | 12308.16 | 25-DEC-15:52 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 48.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12029.39 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 33.96 | 0.00 | |
Maximum of Months | 13815.56 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 341.26 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8564.74 | 03-JAN-05:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 |
February | 8695.11 | 06-FEB-05:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9549.26 | 26-MAR-15:11 | 535.68 | 320.20 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 199.05 | 0.00 |
April | 8315.84 | 24-APR-04:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.11 |
May | 10321.82 | 29-MAY-14:22 | 334.80 | 200.13 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 31.59 | 0.00 |
June | 10770.19 | 18-JUN-14:32 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 204.68 | 0.00 |
July | 10680.31 | 04-JUL-18:02 | 0.00 | 267.20 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 6.03 | 0.00 |
August | 10412.98 | 13-AUG-14:42 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 136.04 | 0.00 |
September | 10582.59 | 04-SEP-16:22 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 104.53 | 0.00 |
October | 8622.02 | 10-OCT-04:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 |
November | 8621.75 | 06-NOV-05:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.43 |
December | 8463.05 | 04-DEC-05:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8315.84 | 0.00 | 200.13 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10770.19 | 535.68 | 649.16 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 204.68 | 15.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9681.07 | 16-JAN-10:23 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 9.08 | 0.00 |
February | 8802.99 | 19-FEB-10:23 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 25.92 | 0.00 |
March | 10208.93 | 26-MAR-09:52 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 74.06 | 0.00 |
April | 10015.59 | 02-APR-08:53 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 10.48 | 0.00 |
May | 7647.61 | 07-MAY-09:53 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 60.01 | 0.00 |
June | 10430.14 | 18-JUN-08:32 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 50.05 | 0.00 |
July | 8061.56 | 03-JUL-04:02 | 0.00 | 410.97 | 2118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
August | 10160.86 | 27-AUG-08:43 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 24.38 | 0.00 |
September | 10262.30 | 04-SEP-09:02 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 | 0.00 |
October | 10152.64 | 08-OCT-09:32 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 19.16 | 0.00 |
November | 8039.03 | 24-NOV-05:02 | 0.00 | 410.97 | 2118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.44 |
December | 9272.68 | 31-DEC-10:02 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 36.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7647.61 | 0.00 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10430.14 | 254.35 | 410.97 | 2118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 74.06 | 4.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11262.57 | 16-JAN-11:42 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 12.71 | 0.00 |
February | 11099.51 | 21-FEB-13:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 7748.39 | 0.00 |
March | 10988.54 | 21-MAR-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 8987.45 | 0.00 |
April | 10501.30 | 18-APR-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 8723.25 | 0.00 |
May | 11396.38 | 05-MAY-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 10752.13 | 0.00 |
June | 10876.32 | 16-JUN-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 9329.55 | 0.00 |
July | 10002.67 | 26-JUL-17:00 | 401.76 | 400.23 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 8328.73 | 0.00 |
August | 10510.91 | 15-AUG-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 8381.56 | 0.00 |
September | 10370.84 | 05-SEP-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 7773.41 | 0.00 |
October | 10607.34 | 08-OCT-13:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 57.27 | 0.00 |
November | 10728.08 | 23-NOV-14:13 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 28.04 | 0.00 |
December | 11205.78 | 25-DEC-12:22 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10002.67 | 267.84 | 160.10 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 12.71 | 0.00 | |
Maximum of Months | 11396.38 | 687.71 | 720.41 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 10752.13 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11419.01 | 16-JAN-17:02 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 16.80 | 0.00 |
February | 10993.36 | 20-FEB-15:41 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 98.27 | 0.00 |
March | 11145.44 | 26-MAR-15:51 | 339.11 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.62 | 0.00 |
April | 11121.71 | 02-APR-16:12 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 93.40 | 0.00 |
May | 10722.38 | 29-MAY-16:22 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 34.75 | 0.00 |
June | 10931.96 | 18-JUN-15:52 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 88.41 | 0.00 |
July | 11197.53 | 04-JUL-18:02 | 0.00 | 144.91 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 |
August | 10795.97 | 27-AUG-16:02 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 87.50 | 0.00 |
September | 11667.41 | 04-SEP-16:22 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 54.15 | 0.00 |
October | 10864.79 | 15-OCT-16:33 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 0.00 |
November | 8903.12 | 19-NOV-14:52 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 37.02 | 0.00 |
December | 11162.81 | 25-DEC-17:02 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 9.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8903.12 | 0.00 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11667.41 | 339.11 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.62 | 2.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8822.72 | 30-JAN-05:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.89 |
February | 9075.47 | 21-FEB-05:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10509.01 | 19-MAR-15:32 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 489.20 | 0.00 |
April | 8996.86 | 02-APR-15:32 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 247.60 | 0.00 |
May | 10638.47 | 07-MAY-14:32 | 334.80 | 200.13 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 347.76 | 0.00 |
June | 10857.05 | 04-JUN-12:53 | 267.84 | 160.10 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 116.37 | 0.00 |
July | 10673.14 | 04-JUL-15:32 | 334.80 | 200.13 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 229.63 | 0.00 |
August | 10358.90 | 13-AUG-12:13 | 267.84 | 160.10 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 174.79 | 0.00 |
September | 10370.32 | 04-SEP-12:32 | 267.84 | 160.10 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 121.94 | 0.00 |
October | 9972.63 | 09-OCT-13:23 | 267.84 | 160.10 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 104.66 | 0.00 |
November | 8739.83 | 06-NOV-05:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.26 |
December | 8719.62 | 26-DEC-05:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8719.62 | 0.00 | 160.10 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10857.05 | 401.76 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 489.20 | 60.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7664.76 | 17-JAN-07:03 | 678.26 | 608.10 | 1694.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.11 |
February | 9860.84 | 19-FEB-10:23 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 39.90 | 0.00 |
March | 10916.86 | 19-MAR-08:13 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 33.56 | 0.00 |
April | 10916.76 | 23-APR-09:02 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 14.23 | 0.00 |
May | 8456.65 | 07-MAY-09:53 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 93.11 | 0.00 |
June | 8974.23 | 04-JUN-10:13 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 51.25 | 0.00 |
July | 8109.54 | 03-JUL-04:02 | 0.00 | 410.97 | 2118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 |
August | 10921.62 | 27-AUG-08:43 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 36.55 | 0.00 |
September | 11147.15 | 04-SEP-09:52 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 40.40 | 0.00 |
October | 10518.48 | 08-OCT-08:23 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 14.24 | 0.00 |
November | 7645.37 | 24-NOV-05:02 | 0.00 | 410.97 | 2118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.10 |
December | 10351.65 | 31-DEC-10:02 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 56.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7645.37 | 0.00 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11147.15 | 678.26 | 608.10 | 2118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 93.11 | 8.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11194.54 | 29-JAN-12:23 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 46.98 | 0.00 |
February | 11016.87 | 26-FEB-13:13 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 69.69 | 0.00 |
March | 10483.82 | 19-MAR-14:52 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 404.00 | 0.00 |
April | 9037.41 | 02-APR-15:32 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 247.59 | 0.00 |
May | 8792.13 | 07-MAY-14:32 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 353.82 | 0.00 |
June | 8528.00 | 11-JUN-14:32 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 300.92 | 0.00 |
July | 8454.32 | 06-JUL-04:02 | 0.00 | 649.16 | 3346.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 8542.32 | 13-AUG-12:13 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 177.77 | 0.00 |
September | 10258.35 | 10-SEP-14:31 | 468.72 | 280.18 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 286.88 | 0.00 |
October | 10693.04 | 09-OCT-12:02 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 83.49 | 0.00 |
November | 10894.69 | 11-NOV-11:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 50.89 | 0.00 |
December | 11352.91 | 03-DEC-11:42 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 44.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8454.32 | 0.00 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11352.91 | 468.72 | 649.16 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 404.00 | 0.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11708.61 | 22-JAN-15:43 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 16.44 | 0.00 |
February | 11663.77 | 20-FEB-15:52 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 179.10 | 0.00 |
March | 12009.06 | 19-MAR-15:32 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 293.86 | 0.00 |
April | 11968.37 | 02-APR-16:12 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 141.37 | 0.00 |
May | 11602.73 | 14-MAY-15:32 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 76.85 | 0.00 |
June | 11659.19 | 11-JUN-16:32 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 126.72 | 0.00 |
July | 11707.29 | 04-JUL-16:12 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 118.10 | 0.00 |
August | 11687.57 | 27-AUG-16:02 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 134.16 | 0.00 |
September | 12010.80 | 10-SEP-17:12 | 0.00 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 | 0.00 |
October | 11645.38 | 15-OCT-16:33 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 27.45 | 0.00 |
November | 10147.38 | 19-NOV-14:52 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 57.26 | 0.00 |
December | 11966.67 | 24-DEC-16:32 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10147.38 | 0.00 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 | 0.00 | |
Maximum of Months | 12010.80 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 293.86 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.179102E+12 | 155288.99 | 04-JAN-13:00 | 0.736839E+10 | 8618.51 | 12-JAN-12:09 |
February | 0.167106E+12 | 165430.26 | 13-FEB-14:00 | 0.665564E+10 | 8614.04 | 07-FEB-12:09 |
March | 0.200212E+12 | 170110.81 | 27-MAR-12:00 | 0.755286E+10 | 8600.95 | 01-MAR-12:09 |
April | 0.195894E+12 | 176096.39 | 10-APR-12:00 | 0.699240E+10 | 8580.51 | 04-APR-11:09 |
May | 0.213283E+12 | 183326.33 | 04-MAY-12:00 | 0.727500E+10 | 8559.68 | 01-MAY-11:09 |
June | 0.212505E+12 | 183990.18 | 13-JUN-15:09 | 0.708052E+10 | 8535.25 | 06-JUN-11:09 |
July | 0.185118E+12 | 165515.76 | 17-JUL-12:00 | 0.700109E+10 | 8527.33 | 24-JUL-11:09 |
August | 0.205121E+12 | 176526.19 | 14-AUG-12:00 | 0.734500E+10 | 8536.75 | 30-AUG-11:09 |
September | 0.188089E+12 | 173437.71 | 05-SEP-12:20 | 0.693635E+10 | 8558.91 | 29-SEP-11:09 |
October | 0.187030E+12 | 164618.02 | 16-OCT-15:09 | 0.723273E+10 | 8580.68 | 30-OCT-11:20 |
November | 0.179622E+12 | 162743.25 | 13-NOV-13:00 | 0.712286E+10 | 8601.70 | 22-NOV-12:09 |
December | 0.173633E+12 | 158537.91 | 11-DEC-13:09 | 0.726179E+10 | 8612.83 | 29-DEC-12:09 |
Annual Sum or Average | 0.228672E+13 | 0.858246E+11 | ||||
Minimum of Months | 0.167106E+12 | 155288.99 | 0.665564E+10 | 8527.33 | ||
Maximum of Months | 0.213283E+12 | 183990.18 | 0.755286E+10 | 8618.51 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.234795E+11 | 0.647379E+10 | 0.641572E+11 | 0.109085E+10 | 0.135042E+11 | 1312252.65 | 0.00 | 0.703957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212666E+11 | 0.573747E+10 | 0.580684E+11 | 0.987234E+09 | 0.131181E+11 | 1186778.30 | 0.00 | 0.679272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251447E+11 | 0.611700E+10 | 0.666107E+11 | 0.114315E+10 | 0.174643E+11 | 1343621.24 | 0.00 | 0.837309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.224057E+11 | 0.574930E+10 | 0.619407E+11 | 0.105058E+10 | 0.176622E+11 | 1267813.82 | 0.00 | 0.870842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.241729E+11 | 0.581690E+10 | 0.653840E+11 | 0.111692E+10 | 0.181128E+11 | 1327936.95 | 0.00 | 0.986785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.240215E+11 | 0.554923E+10 | 0.641577E+11 | 0.109963E+10 | 0.181632E+11 | 1296568.36 | 0.00 | 0.995126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.225233E+11 | 0.579023E+10 | 0.631525E+11 | 0.106765E+10 | 0.163420E+11 | 1299182.41 | 0.00 | 0.762409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.250699E+11 | 0.588026E+10 | 0.666107E+11 | 0.114311E+10 | 0.176058E+11 | 1343621.24 | 0.00 | 0.888097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.224667E+11 | 0.586934E+10 | 0.619118E+11 | 0.105020E+10 | 0.156068E+11 | 1267813.82 | 0.00 | 0.811834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.233579E+11 | 0.625705E+10 | 0.641717E+11 | 0.109098E+10 | 0.146968E+11 | 1312252.65 | 0.00 | 0.774543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.232249E+11 | 0.623579E+10 | 0.627379E+11 | 0.107092E+10 | 0.135143E+11 | 1278270.02 | 0.00 | 0.728364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227722E+11 | 0.652499E+10 | 0.631380E+11 | 0.106760E+10 | 0.124684E+11 | 1299182.41 | 0.00 | 0.676605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279906E+12 | 0.720014E+11 | 0.762041E+12 | 0.129788E+11 | 0.188259E+12 | 15535293.87 | 0.00 | 0.971514E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.212666E+11 | 0.554923E+10 | 0.580684E+11 | 0.987234E+09 | 0.124684E+11 | 1186778.30 | 0.00 | 0.676605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.251447E+11 | 0.652499E+10 | 0.666107E+11 | 0.114315E+10 | 0.181632E+11 | 1343621.24 | 0.00 | 0.995126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.736839E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.665564E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.755286E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.699240E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.727500E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.708052E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.700109E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.734500E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.693635E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.723273E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.712286E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.726179E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.858246E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.665564E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.755286E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 25441.87 | 02-JAN-16:00 | 5557.43 | 01-JAN-06:10 | 47562.27 | 02-JAN-08:09 | 921.90 | 02-JAN-08:20 | 20724.15 | 17-JAN-08:09 | 0.73 | 01-JAN-06:19 | 0.00 | 01-JAN-00:10 |
February | 23968.45 | 07-FEB-16:00 | 5557.43 | 01-FEB-06:10 | 47562.27 | 01-FEB-08:09 | 921.90 | 01-FEB-08:20 | 22671.63 | 21-FEB-08:09 | 0.73 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 24226.03 | 01-MAR-16:00 | 5557.43 | 01-MAR-06:10 | 47562.27 | 01-MAR-08:09 | 921.90 | 01-MAR-08:20 | 23052.37 | 06-MAR-08:09 | 0.73 | 01-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 23688.37 | 03-APR-07:10 | 5557.43 | 01-APR-05:10 | 47562.27 | 03-APR-07:10 | 921.90 | 03-APR-07:19 | 23475.89 | 17-APR-15:09 | 0.73 | 01-APR-05:10 | 0.00 | 01-APR-00:10 |
May | 23688.37 | 01-MAY-07:10 | 5557.43 | 01-MAY-05:10 | 47562.27 | 01-MAY-07:10 | 921.90 | 01-MAY-07:19 | 24848.78 | 22-MAY-07:10 | 0.73 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 23688.37 | 01-JUN-07:10 | 5557.43 | 01-JUN-05:10 | 47562.27 | 01-JUN-07:10 | 921.90 | 01-JUN-07:19 | 24960.75 | 19-JUN-07:10 | 0.73 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 23688.37 | 03-JUL-07:10 | 5557.43 | 01-JUL-05:10 | 47562.27 | 03-JUL-07:10 | 921.90 | 03-JUL-07:19 | 21711.53 | 05-JUL-07:10 | 0.73 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 23688.37 | 01-AUG-07:10 | 5557.43 | 01-AUG-05:10 | 47562.27 | 01-AUG-07:10 | 921.90 | 01-AUG-07:19 | 22872.27 | 14-AUG-15:00 | 0.73 | 01-AUG-05:30 | 0.00 | 01-AUG-00:10 |
September | 23688.37 | 01-SEP-07:10 | 5557.43 | 01-SEP-05:10 | 47562.27 | 01-SEP-07:10 | 921.90 | 01-SEP-07:19 | 23865.16 | 05-SEP-07:10 | 0.73 | 01-SEP-05:30 | 0.00 | 01-SEP-00:10 |
October | 23787.27 | 23-OCT-07:10 | 5557.43 | 01-OCT-05:10 | 47562.27 | 02-OCT-07:10 | 922.04 | 23-OCT-07:19 | 21424.22 | 16-OCT-07:10 | 0.73 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 26092.56 | 09-NOV-16:00 | 5557.43 | 01-NOV-05:10 | 47562.27 | 01-NOV-07:10 | 923.07 | 09-NOV-16:00 | 20260.84 | 06-NOV-08:09 | 0.73 | 01-NOV-05:19 | 0.00 | 01-NOV-00:10 |
December | 26362.23 | 18-DEC-16:00 | 5557.43 | 01-DEC-17:30 | 47562.27 | 01-DEC-08:09 | 923.95 | 18-DEC-16:00 | 19059.70 | 26-DEC-08:09 | 0.73 | 01-DEC-06:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 23688.37 | 5557.43 | 47562.27 | 921.90 | 19059.70 | 0.73 | 0.00 | |||||||
Maximum of Months | 26362.23 | 5557.43 | 47562.27 | 923.95 | 24960.75 | 0.73 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 73375.16 | 04-JAN-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83542.03 | 13-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 84974.42 | 27-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 86363.47 | 10-APR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 96863.04 | 04-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 98545.37 | 13-JUN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 78220.01 | 17-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87590.13 | 14-AUG-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84831.05 | 05-SEP-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 80645.70 | 16-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 78495.50 | 13-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 74221.67 | 11-DEC-13:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 73375.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 98545.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 155288.99 | 04-JAN-13:00 | 23688.37 | 44099.74 | 0.00 | 920.56 | 13396.60 | 0.73 | 0.00 | 73182.99 | 0.00 |
February | 165430.26 | 13-FEB-14:00 | 23688.37 | 42286.04 | 0.00 | 919.86 | 14993.24 | 0.73 | 0.00 | 83542.03 | 0.00 |
March | 170110.81 | 27-MAR-12:00 | 23688.37 | 44099.74 | 0.00 | 920.56 | 16426.99 | 0.73 | 0.00 | 84974.42 | 0.00 |
April | 176096.39 | 10-APR-12:00 | 23688.37 | 44099.74 | 0.00 | 920.56 | 21023.51 | 0.73 | 0.00 | 86363.47 | 0.00 |
May | 183326.33 | 04-MAY-12:00 | 23688.37 | 44099.74 | 0.00 | 920.56 | 17753.89 | 0.73 | 0.00 | 96863.04 | 0.00 |
June | 183990.18 | 13-JUN-15:09 | 23688.37 | 43769.98 | 0.00 | 920.43 | 17065.30 | 0.73 | 0.00 | 98545.37 | 0.00 |
July | 165515.76 | 17-JUL-12:00 | 23688.37 | 44099.74 | 0.00 | 920.56 | 18586.35 | 0.73 | 0.00 | 78220.01 | 0.00 |
August | 176526.19 | 14-AUG-12:00 | 23688.37 | 44099.74 | 0.00 | 920.56 | 20226.66 | 0.73 | 0.00 | 87590.13 | 0.00 |
September | 173437.71 | 05-SEP-12:20 | 23688.37 | 44099.74 | 0.00 | 920.56 | 19897.26 | 0.73 | 0.00 | 84831.05 | 0.00 |
October | 164618.02 | 16-OCT-15:09 | 23688.37 | 43769.98 | 0.00 | 920.43 | 17493.37 | 0.73 | 0.00 | 78745.15 | 0.00 |
November | 162743.25 | 13-NOV-13:00 | 23688.37 | 44099.74 | 0.00 | 920.56 | 15538.36 | 0.73 | 0.00 | 78495.50 | 0.00 |
December | 158537.91 | 11-DEC-13:09 | 23688.37 | 44099.74 | 0.00 | 920.56 | 15606.84 | 0.73 | 0.00 | 74221.67 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 155288.99 | 23688.37 | 42286.04 | 0.00 | 919.86 | 13396.60 | 0.73 | 0.00 | 73182.99 | 0.00 | |
Maximum of Months | 183990.18 | 23688.37 | 44099.74 | 0.00 | 920.56 | 21023.51 | 0.73 | 0.00 | 98545.37 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 8618.51 | 12-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 8614.04 | 07-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 8600.95 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 8580.51 | 04-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 8559.68 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 8535.25 | 06-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 8527.33 | 24-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 8536.75 | 30-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 8558.91 | 29-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 8580.68 | 30-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 8601.70 | 22-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 8612.83 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8527.33 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8618.51 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.63 | 0.00 | 26.63 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.17 | 0.00 | 26.17 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.20 | 0.00 | 26.20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.20 | 0.00 | 26.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.20 | 0.00 | 26.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.18 | 0.00 | 26.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.19 | 0.00 | 26.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.19 | 0.00 | 26.19 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.19 | 0.00 | 26.19 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.20 | 0.00 | 26.20 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.17 | 0.00 | 26.17 |
Annual Sum or Average | 0.00 | 0.00 | 5.00 | 26.26 | 0.00 | 26.26 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.63 | 0.00 | 26.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.16 | 0.00 | 26.16 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 26.16 | 0.00 | 26.16 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.16 | 0.00 | 26.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.17 | 0.00 | 26.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 26.17 | 0.00 | 26.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.17 | 0.00 | 26.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.35 | 2.50 | 27.35 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.48 | 5.50 | 27.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.56 | 4.83 | 27.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.55 | 6.50 | 27.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.73 | 8.17 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.83 | 8.00 | 27.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.56 | 9.50 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.59 | 4.00 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.52 | 5.33 | 27.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.44 | 6.17 | 27.44 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.37 | 3.33 | 27.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.30 | 1.83 | 27.30 |
Annual Sum or Average | 0.00 | 0.00 | 74.00 | 27.58 | 65.67 | 27.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.30 | 1.83 | 27.30 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.83 | 9.50 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.52 | 7.17 | 27.52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.68 | 10.67 | 27.68 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.89 | 9.17 | 27.91 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.87 | 11.67 | 27.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.90 | 10.17 | 27.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.84 | 9.17 | 27.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.57 | 10.17 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.82 | 5.83 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.78 | 9.83 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.65 | 10.00 | 27.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.54 | 8.33 | 27.54 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.52 | 8.83 | 27.52 |
Annual Sum or Average | 0.00 | 0.00 | 117.00 | 27.73 | 111.00 | 27.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.52 | 5.83 | 27.52 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.90 | 11.67 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.73 | 11.83 | 27.74 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.87 | 9.67 | 27.89 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.79 | 6.83 | 27.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.55 | 6.17 | 27.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.60 | 5.67 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.56 | 6.33 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.42 | 6.50 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.56 | 2.83 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.58 | 6.00 | 27.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.71 | 9.00 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.82 | 9.33 | 27.83 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.01 | 15.50 | 27.01 |
Annual Sum or Average | 0.00 | 0.00 | 103.33 | 27.58 | 95.67 | 27.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.01 | 2.83 | 27.01 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.87 | 15.50 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.04 | 6.00 | 28.08 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.97 | 6.17 | 28.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.20 | 5.33 | 28.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.04 | 6.33 | 28.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.98 | 6.00 | 28.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.05 | 6.00 | 28.09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.79 | 6.33 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.02 | 3.83 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.96 | 5.00 | 27.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.80 | 5.83 | 27.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.76 | 5.33 | 27.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.00 | 6.17 | 28.00 |
Annual Sum or Average | 0.00 | 0.00 | 85.83 | 27.97 | 68.33 | 28.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.76 | 3.83 | 27.77 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.20 | 6.33 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.39 | 5.00 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.52 | 6.33 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.38 | 4.33 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.38 | 1.33 | 27.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.32 | 0.83 | 27.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 21.00 | 27.43 | 18.00 | 27.46 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.52 | 6.33 | 27.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.40 | 2.83 | 27.40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.47 | 8.50 | 27.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.56 | 8.50 | 27.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.59 | 9.83 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.55 | 9.33 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.54 | 7.67 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.37 | 5.83 | 27.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.57 | 5.50 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.51 | 8.50 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.49 | 5.83 | 27.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.37 | 4.50 | 27.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.40 | 5.17 | 27.40 |
Annual Sum or Average | 0.00 | 0.00 | 84.83 | 27.50 | 82.00 | 27.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.37 | 2.83 | 27.37 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.59 | 9.83 | 27.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 118.83 | 25.42 | 118.17 | 25.42 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 110.00 | 25.49 | 109.67 | 25.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 71.67 | 25.54 | 71.67 | 25.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 40.33 | 25.65 | 40.33 | 25.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 46.83 | 25.64 | 46.67 | 25.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 43.50 | 25.80 | 43.50 | 25.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 25.28 | 29.83 | 25.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 32.67 | 25.49 | 32.67 | 25.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 25.53 | 32.83 | 25.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 41.50 | 25.49 | 41.33 | 25.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 71.33 | 25.46 | 71.17 | 25.45 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 96.33 | 25.51 | 95.83 | 25.51 |
Annual Sum or Average | 0.00 | 0.00 | 736.00 | 25.51 | 733.67 | 25.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 25.28 | 29.83 | 25.28 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 118.83 | 25.80 | 118.17 | 25.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.77 | 5.33 | 27.77 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.74 | 5.33 | 27.74 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.78 | 4.33 | 27.86 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.78 | 5.00 | 27.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.59 | 4.33 | 27.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.73 | 4.83 | 27.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.57 | 4.50 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.62 | 3.33 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.61 | 4.17 | 27.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.59 | 4.00 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.52 | 3.83 | 27.53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.72 | 5.17 | 27.72 |
Annual Sum or Average | 0.00 | 0.00 | 68.67 | 27.67 | 54.17 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.52 | 3.33 | 27.53 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.78 | 5.33 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.30 | 1.50 | 27.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.38 | 1.67 | 27.38 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.26 | 2.17 | 27.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.52 | 6.17 | 27.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.61 | 7.17 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.39 | 4.83 | 27.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.30 | 2.17 | 27.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.38 | 1.67 | 27.38 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.30 | 0.67 | 27.30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 31.33 | 27.45 | 28.00 | 27.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.61 | 7.17 | 27.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.48 | 2.83 | 27.48 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.51 | 9.67 | 27.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.69 | 9.00 | 27.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.65 | 10.83 | 27.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.70 | 9.50 | 27.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.67 | 7.33 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.39 | 5.17 | 27.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.64 | 5.17 | 27.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.59 | 8.83 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.54 | 6.33 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.44 | 4.67 | 27.44 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.45 | 6.17 | 27.45 |
Annual Sum or Average | 0.00 | 0.00 | 86.17 | 27.58 | 85.50 | 27.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.39 | 2.83 | 27.39 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.70 | 10.83 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 | 25.96 | 23.83 | 25.96 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.99 | 12.00 | 26.98 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.54 | 6.33 | 27.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.22 | 1.67 | 27.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.33 | 2.83 | 27.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.37 | 2.50 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.40 | 3.00 | 27.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.53 | 7.17 | 27.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.65 | 8.50 | 27.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 25.78 | 30.17 | 25.78 |
Annual Sum or Average | 0.00 | 0.00 | 99.50 | 26.55 | 98.33 | 26.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 27.65 | 30.17 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.90 | 5.33 | 27.91 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.83 | 5.50 | 27.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.05 | 4.67 | 28.08 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.91 | 5.00 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.84 | 4.50 | 27.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.95 | 4.67 | 27.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.66 | 3.83 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.87 | 3.17 | 27.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.92 | 3.33 | 27.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.68 | 4.17 | 27.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.64 | 3.83 | 27.64 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.84 | 5.33 | 27.84 |
Annual Sum or Average | 0.00 | 0.00 | 63.00 | 27.85 | 53.33 | 27.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.64 | 3.17 | 27.64 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.05 | 5.50 | 28.08 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 24.47 | 0.00 | 24.47 |
February | 0.00 | 0.00 | 454.00 | 24.43 | 0.00 | 24.43 |
March | 0.00 | 0.00 | 514.00 | 24.37 | 0.00 | 24.37 |
April | 0.00 | 0.00 | 485.00 | 24.39 | 0.00 | 24.39 |
May | 0.00 | 0.00 | 508.00 | 24.39 | 0.00 | 24.39 |
June | 0.00 | 0.00 | 496.00 | 24.39 | 0.00 | 24.39 |
July | 0.00 | 0.00 | 497.00 | 24.45 | 0.00 | 24.45 |
August | 0.00 | 0.00 | 514.00 | 24.40 | 0.00 | 24.40 |
September | 0.00 | 0.00 | 485.00 | 24.42 | 0.00 | 24.42 |
October | 0.00 | 0.00 | 502.00 | 24.47 | 0.00 | 24.47 |
November | 0.00 | 0.00 | 489.00 | 24.47 | 0.00 | 24.47 |
December | 0.00 | 0.00 | 497.00 | 24.44 | 0.00 | 24.44 |
Annual Sum or Average | 0.00 | 5943.00 | 24.42 | 0.00 | 24.42 | |
Minimum of Months | 0.00 | 0.00 | 454.00 | 24.37 | 0.00 | 24.37 |
Maximum of Months | 0.00 | 0.00 | 514.00 | 24.47 | 0.00 | 24.47 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 27.18 | 499.33 | 24.37 | 0.50 | 24.37 |
February | 0.00 | 0.00 | 454.00 | 24.34 | 0.00 | 24.34 |
March | 0.00 | 0.00 | 514.00 | 24.29 | 0.00 | 24.29 |
April | 0.00 | 0.00 | 485.00 | 24.31 | 0.00 | 24.31 |
May | 0.00 | 0.00 | 508.00 | 24.32 | 0.00 | 24.32 |
June | 0.00 | 0.00 | 496.00 | 24.31 | 0.00 | 24.31 |
July | 0.00 | 0.00 | 497.00 | 24.35 | 0.00 | 24.35 |
August | 0.00 | 0.00 | 514.00 | 24.31 | 0.00 | 24.31 |
September | 0.00 | 0.00 | 485.00 | 24.32 | 0.00 | 24.32 |
October | 0.00 | 0.00 | 502.00 | 24.37 | 0.00 | 24.37 |
November | 0.00 | 0.00 | 489.00 | 24.36 | 0.00 | 24.36 |
December | 0.00 | 0.00 | 497.00 | 24.33 | 0.00 | 24.33 |
Annual Sum or Average | 0.50 | 27.18 | 5940.33 | 24.33 | 0.50 | 24.33 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 24.29 | 0.00 | 24.29 |
Maximum of Months | 0.50 | 27.18 | 514.00 | 24.37 | 0.50 | 24.37 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 27.20 | 498.83 | 24.36 | 0.17 | 24.36 |
February | 0.00 | 0.00 | 454.00 | 24.34 | 0.00 | 24.34 |
March | 0.00 | 0.00 | 512.67 | 24.31 | 0.00 | 24.31 |
April | 0.00 | 0.00 | 485.00 | 24.35 | 0.00 | 24.35 |
May | 0.00 | 0.00 | 508.00 | 24.36 | 0.00 | 24.36 |
June | 0.00 | 0.00 | 496.00 | 24.35 | 0.00 | 24.35 |
July | 0.00 | 0.00 | 497.00 | 24.39 | 0.00 | 24.39 |
August | 0.00 | 0.00 | 513.83 | 24.31 | 0.00 | 24.31 |
September | 0.00 | 0.00 | 485.00 | 24.34 | 0.00 | 24.34 |
October | 0.00 | 0.00 | 502.00 | 24.39 | 0.00 | 24.39 |
November | 0.00 | 0.00 | 489.00 | 24.36 | 0.00 | 24.36 |
December | 0.00 | 0.00 | 490.67 | 24.32 | 0.00 | 24.32 |
Annual Sum or Average | 0.17 | 27.20 | 5932.00 | 24.35 | 0.17 | 24.35 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 24.31 | 0.00 | 24.31 |
Maximum of Months | 0.17 | 27.20 | 513.83 | 24.39 | 0.17 | 24.39 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 52.00 | 25.95 | 494.67 | 24.60 | 51.83 | 24.72 |
February | 56.67 | 26.12 | 454.00 | 24.64 | 56.67 | 24.79 |
March | 73.50 | 25.78 | 514.00 | 24.58 | 73.50 | 24.72 |
April | 99.33 | 25.99 | 485.00 | 24.78 | 99.33 | 24.95 |
May | 109.83 | 26.09 | 508.00 | 24.82 | 109.83 | 25.01 |
June | 96.67 | 26.16 | 496.00 | 24.79 | 96.67 | 24.98 |
July | 85.67 | 26.37 | 497.00 | 24.85 | 85.67 | 25.04 |
August | 92.33 | 25.73 | 514.00 | 24.62 | 92.33 | 24.77 |
September | 86.83 | 25.88 | 485.00 | 24.69 | 86.83 | 24.85 |
October | 94.83 | 25.99 | 502.00 | 24.75 | 94.83 | 24.92 |
November | 72.67 | 25.92 | 489.00 | 24.66 | 72.67 | 24.81 |
December | 58.50 | 25.68 | 486.33 | 24.56 | 56.67 | 24.67 |
Annual Sum or Average | 978.83 | 25.98 | 5925.00 | 24.70 | 976.83 | 24.86 |
Minimum of Months | 52.00 | 25.68 | 454.00 | 24.56 | 51.83 | 24.67 |
Maximum of Months | 109.83 | 26.37 | 514.00 | 24.85 | 109.83 | 25.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 70.17 | 26.41 | 501.00 | 24.76 | 70.17 | 24.94 |
February | 65.83 | 26.54 | 454.00 | 24.79 | 65.83 | 24.99 |
March | 74.83 | 26.20 | 513.83 | 24.68 | 74.83 | 24.85 |
April | 96.00 | 26.31 | 485.00 | 24.86 | 96.00 | 25.06 |
May | 102.33 | 26.19 | 508.00 | 24.82 | 102.33 | 25.02 |
June | 90.67 | 26.20 | 496.00 | 24.77 | 90.67 | 24.96 |
July | 84.00 | 26.43 | 497.00 | 24.84 | 84.00 | 25.04 |
August | 88.83 | 25.91 | 514.00 | 24.65 | 88.83 | 24.81 |
September | 85.83 | 26.22 | 485.00 | 24.78 | 85.83 | 24.97 |
October | 95.83 | 26.22 | 501.83 | 24.81 | 95.83 | 25.01 |
November | 76.50 | 26.29 | 488.00 | 24.77 | 76.50 | 24.95 |
December | 69.50 | 26.33 | 492.67 | 24.73 | 69.50 | 24.90 |
Annual Sum or Average | 1000.33 | 26.26 | 5936.33 | 24.77 | 1000.33 | 24.96 |
Minimum of Months | 65.83 | 25.91 | 454.00 | 24.65 | 65.83 | 24.81 |
Maximum of Months | 102.33 | 26.54 | 514.00 | 24.86 | 102.33 | 25.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 75.50 | 26.53 | 500.83 | 24.84 | 75.50 | 25.04 |
February | 64.17 | 26.49 | 454.00 | 24.79 | 64.17 | 24.98 |
March | 76.83 | 25.95 | 514.00 | 24.64 | 76.83 | 24.79 |
April | 98.83 | 25.97 | 485.00 | 24.76 | 98.83 | 24.94 |
May | 107.00 | 25.92 | 508.00 | 24.75 | 107.00 | 24.93 |
June | 96.17 | 25.92 | 496.00 | 24.71 | 96.17 | 24.88 |
July | 83.83 | 26.21 | 497.00 | 24.79 | 83.83 | 24.97 |
August | 93.17 | 25.63 | 514.00 | 24.59 | 93.17 | 24.73 |
September | 87.50 | 25.91 | 485.00 | 24.71 | 87.50 | 24.87 |
October | 96.83 | 26.17 | 502.00 | 24.82 | 96.83 | 25.01 |
November | 83.00 | 26.34 | 489.00 | 24.83 | 83.00 | 25.02 |
December | 78.17 | 26.49 | 494.83 | 24.84 | 78.17 | 25.04 |
Annual Sum or Average | 1041.00 | 26.10 | 5939.67 | 24.76 | 1041.00 | 24.93 |
Minimum of Months | 64.17 | 25.63 | 454.00 | 24.59 | 64.17 | 24.73 |
Maximum of Months | 107.00 | 26.53 | 514.00 | 24.84 | 107.00 | 25.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 55.00 | 25.99 | 486.67 | 24.62 | 51.33 | 24.75 |
February | 48.67 | 26.26 | 448.17 | 24.63 | 48.67 | 24.78 |
March | 66.17 | 26.03 | 512.67 | 24.61 | 66.17 | 24.75 |
April | 93.17 | 26.13 | 485.00 | 24.78 | 93.17 | 24.97 |
May | 98.33 | 26.02 | 507.17 | 24.74 | 98.33 | 24.92 |
June | 91.33 | 26.07 | 496.00 | 24.72 | 91.33 | 24.90 |
July | 77.17 | 26.26 | 496.50 | 24.76 | 77.17 | 24.93 |
August | 90.67 | 25.74 | 514.00 | 24.60 | 90.67 | 24.75 |
September | 78.33 | 25.91 | 485.00 | 24.66 | 78.33 | 24.81 |
October | 87.67 | 26.05 | 498.33 | 24.72 | 87.67 | 24.90 |
November | 64.83 | 26.04 | 484.33 | 24.64 | 64.83 | 24.79 |
December | 58.83 | 25.72 | 468.67 | 24.58 | 53.50 | 24.71 |
Annual Sum or Average | 910.17 | 26.02 | 5882.50 | 24.67 | 901.17 | 24.83 |
Minimum of Months | 48.67 | 25.72 | 448.17 | 24.58 | 48.67 | 24.71 |
Maximum of Months | 98.33 | 26.26 | 514.00 | 24.78 | 98.33 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.67 | 25.77 | 502.00 | 24.48 | 11.67 | 24.51 |
February | 19.17 | 26.14 | 454.00 | 24.54 | 19.17 | 24.60 |
March | 31.17 | 25.80 | 514.00 | 24.49 | 31.17 | 24.56 |
April | 48.17 | 25.94 | 485.00 | 24.63 | 48.17 | 24.74 |
May | 74.00 | 26.25 | 508.00 | 24.76 | 74.00 | 24.93 |
June | 71.67 | 26.37 | 496.00 | 24.77 | 71.67 | 24.95 |
July | 64.17 | 26.56 | 497.00 | 24.83 | 64.17 | 25.01 |
August | 64.17 | 26.08 | 514.00 | 24.64 | 64.17 | 24.78 |
September | 46.83 | 26.10 | 485.00 | 24.64 | 46.83 | 24.75 |
October | 49.00 | 26.14 | 502.00 | 24.66 | 49.00 | 24.78 |
November | 24.83 | 26.04 | 489.00 | 24.56 | 24.83 | 24.63 |
December | 15.17 | 25.73 | 496.33 | 24.47 | 15.17 | 24.51 |
Annual Sum or Average | 520.00 | 26.16 | 5942.33 | 24.63 | 520.00 | 24.74 |
Minimum of Months | 11.67 | 25.73 | 454.00 | 24.47 | 11.67 | 24.51 |
Maximum of Months | 74.00 | 26.56 | 514.00 | 24.83 | 74.00 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 35.67 | 26.67 | 502.00 | 24.71 | 35.67 | 24.83 |
February | 54.50 | 26.72 | 454.00 | 24.81 | 54.50 | 25.00 |
March | 54.67 | 26.54 | 514.00 | 24.69 | 54.67 | 24.86 |
April | 72.33 | 26.52 | 485.00 | 24.84 | 72.33 | 25.03 |
May | 78.50 | 26.44 | 508.00 | 24.82 | 78.50 | 25.01 |
June | 71.33 | 26.41 | 496.00 | 24.77 | 71.33 | 24.95 |
July | 68.33 | 26.61 | 497.00 | 24.85 | 68.33 | 25.04 |
August | 66.50 | 26.33 | 514.00 | 24.70 | 66.50 | 24.87 |
September | 61.50 | 26.60 | 485.00 | 24.80 | 61.50 | 24.98 |
October | 72.50 | 26.52 | 502.00 | 24.83 | 72.50 | 25.02 |
November | 54.17 | 26.58 | 489.00 | 24.78 | 54.17 | 24.95 |
December | 48.67 | 26.65 | 497.00 | 24.74 | 48.67 | 24.90 |
Annual Sum or Average | 738.67 | 26.54 | 5943.00 | 24.78 | 738.67 | 24.95 |
Minimum of Months | 35.67 | 26.33 | 454.00 | 24.69 | 35.67 | 24.83 |
Maximum of Months | 78.50 | 26.72 | 514.00 | 24.85 | 78.50 | 25.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 142.50 | 25.71 | 502.00 | 25.10 | 142.50 | 25.21 |
February | 126.00 | 25.73 | 454.00 | 25.11 | 126.00 | 25.22 |
March | 156.17 | 25.23 | 514.00 | 24.82 | 156.17 | 24.90 |
April | 190.17 | 24.91 | 485.00 | 24.73 | 190.17 | 24.77 |
May | 256.67 | 24.82 | 508.00 | 24.72 | 256.67 | 24.74 |
June | 256.17 | 24.88 | 496.00 | 24.73 | 256.17 | 24.77 |
July | 191.67 | 24.81 | 497.00 | 24.69 | 191.67 | 24.71 |
August | 294.50 | 24.63 | 514.00 | 24.57 | 294.50 | 24.59 |
September | 237.83 | 24.74 | 485.00 | 24.66 | 237.83 | 24.68 |
October | 248.00 | 24.94 | 502.00 | 24.78 | 248.00 | 24.82 |
November | 196.00 | 25.25 | 489.00 | 24.94 | 196.00 | 25.01 |
December | 152.67 | 25.58 | 497.00 | 25.04 | 152.67 | 25.14 |
Annual Sum or Average | 2448.33 | 25.02 | 5943.00 | 24.81 | 2448.33 | 24.86 |
Minimum of Months | 126.00 | 24.63 | 454.00 | 24.57 | 126.00 | 24.59 |
Maximum of Months | 294.50 | 25.73 | 514.00 | 25.11 | 294.50 | 25.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.00 | 26.60 | 502.00 | 24.66 | 34.00 | 24.78 |
February | 36.00 | 26.63 | 454.00 | 24.70 | 36.00 | 24.83 |
March | 43.50 | 26.43 | 514.00 | 24.64 | 43.50 | 24.77 |
April | 61.17 | 26.40 | 485.00 | 24.78 | 61.17 | 24.94 |
May | 71.33 | 26.31 | 508.00 | 24.76 | 71.33 | 24.93 |
June | 71.00 | 26.32 | 496.00 | 24.75 | 71.00 | 24.92 |
July | 56.33 | 26.56 | 497.00 | 24.80 | 56.33 | 24.96 |
August | 66.50 | 26.22 | 514.00 | 24.69 | 66.50 | 24.84 |
September | 51.67 | 26.40 | 485.00 | 24.72 | 51.67 | 24.87 |
October | 62.67 | 26.44 | 502.00 | 24.77 | 62.67 | 24.94 |
November | 45.83 | 26.48 | 489.00 | 24.71 | 45.83 | 24.85 |
December | 38.83 | 26.52 | 496.17 | 24.66 | 38.83 | 24.78 |
Annual Sum or Average | 638.83 | 26.42 | 5942.17 | 24.72 | 638.83 | 24.87 |
Minimum of Months | 34.00 | 26.22 | 454.00 | 24.64 | 34.00 | 24.77 |
Maximum of Months | 71.33 | 26.63 | 514.00 | 24.80 | 71.33 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.17 | 25.73 | 501.83 | 24.53 | 30.17 | 24.59 |
February | 47.17 | 26.11 | 454.00 | 24.63 | 47.17 | 24.76 |
March | 68.50 | 25.78 | 514.00 | 24.57 | 68.50 | 24.70 |
April | 90.50 | 25.91 | 485.00 | 24.73 | 90.50 | 24.89 |
May | 100.83 | 26.11 | 508.00 | 24.80 | 100.83 | 24.98 |
June | 89.33 | 26.19 | 496.00 | 24.77 | 89.33 | 24.96 |
July | 83.17 | 26.34 | 497.00 | 24.83 | 83.17 | 25.02 |
August | 85.83 | 25.81 | 514.00 | 24.63 | 85.83 | 24.77 |
September | 83.50 | 25.87 | 485.00 | 24.68 | 83.50 | 24.83 |
October | 88.00 | 25.96 | 502.00 | 24.73 | 88.00 | 24.89 |
November | 58.17 | 25.87 | 489.00 | 24.63 | 58.17 | 24.75 |
December | 38.00 | 25.67 | 494.50 | 24.52 | 38.00 | 24.60 |
Annual Sum or Average | 863.17 | 25.98 | 5940.33 | 24.67 | 863.17 | 24.82 |
Minimum of Months | 30.17 | 25.67 | 454.00 | 24.52 | 30.17 | 24.59 |
Maximum of Months | 100.83 | 26.34 | 514.00 | 24.83 | 100.83 | 25.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 55.83 | 26.42 | 426.83 | 24.83 | 55.83 | 25.00 |
February | 62.33 | 26.59 | 385.00 | 24.92 | 62.33 | 25.12 |
March | 73.50 | 26.24 | 433.00 | 24.80 | 73.50 | 24.98 |
April | 93.00 | 26.27 | 410.00 | 24.96 | 93.00 | 25.16 |
May | 97.00 | 26.21 | 430.00 | 24.92 | 97.00 | 25.12 |
June | 87.50 | 26.19 | 418.00 | 24.87 | 87.50 | 25.06 |
July | 80.50 | 26.37 | 422.00 | 24.93 | 80.50 | 25.13 |
August | 84.17 | 25.98 | 433.00 | 24.76 | 84.17 | 24.93 |
September | 81.17 | 26.25 | 410.00 | 24.89 | 81.17 | 25.08 |
October | 90.83 | 26.22 | 427.00 | 24.92 | 90.83 | 25.12 |
November | 69.50 | 26.33 | 417.00 | 24.88 | 69.50 | 25.06 |
December | 59.50 | 26.45 | 421.17 | 24.84 | 59.50 | 25.01 |
Annual Sum or Average | 934.83 | 26.27 | 5033.00 | 24.88 | 934.83 | 25.07 |
Minimum of Months | 55.83 | 25.98 | 385.00 | 24.76 | 55.83 | 24.93 |
Maximum of Months | 97.00 | 26.59 | 433.00 | 24.96 | 97.00 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 72.50 | 26.58 | 502.00 | 24.89 | 72.50 | 25.08 |
February | 62.50 | 26.55 | 454.00 | 24.83 | 62.50 | 25.02 |
March | 75.83 | 26.02 | 514.00 | 24.65 | 75.83 | 24.81 |
April | 89.83 | 25.87 | 485.00 | 24.71 | 89.83 | 24.87 |
May | 97.33 | 25.90 | 508.00 | 24.72 | 97.33 | 24.88 |
June | 90.00 | 25.91 | 496.00 | 24.68 | 90.00 | 24.85 |
July | 80.33 | 26.13 | 497.00 | 24.75 | 80.33 | 24.92 |
August | 87.17 | 25.69 | 514.00 | 24.59 | 87.17 | 24.73 |
September | 84.17 | 25.94 | 485.00 | 24.70 | 84.17 | 24.86 |
October | 92.67 | 26.20 | 502.00 | 24.82 | 92.67 | 25.01 |
November | 79.83 | 26.43 | 489.00 | 24.86 | 79.83 | 25.05 |
December | 74.00 | 26.60 | 497.00 | 24.89 | 74.00 | 25.08 |
Annual Sum or Average | 986.17 | 26.13 | 5943.00 | 24.76 | 986.17 | 24.93 |
Minimum of Months | 62.50 | 25.69 | 454.00 | 24.59 | 62.50 | 24.73 |
Maximum of Months | 97.33 | 26.60 | 514.00 | 24.89 | 97.33 | 25.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 46.17 | 26.31 | 498.67 | 24.63 | 46.17 | 24.76 |
February | 46.17 | 26.31 | 454.00 | 24.66 | 46.17 | 24.80 |
March | 64.33 | 26.04 | 514.00 | 24.62 | 64.33 | 24.76 |
April | 86.33 | 26.05 | 485.00 | 24.75 | 86.33 | 24.92 |
May | 91.17 | 26.02 | 508.00 | 24.73 | 91.17 | 24.90 |
June | 88.00 | 26.05 | 496.00 | 24.71 | 88.00 | 24.89 |
July | 73.67 | 26.19 | 497.00 | 24.75 | 73.67 | 24.91 |
August | 86.17 | 25.80 | 514.00 | 24.62 | 86.17 | 24.77 |
September | 74.17 | 25.94 | 485.00 | 24.67 | 74.17 | 24.82 |
October | 83.50 | 26.03 | 502.00 | 24.73 | 83.50 | 24.89 |
November | 60.50 | 26.12 | 489.00 | 24.67 | 60.50 | 24.81 |
December | 51.50 | 26.11 | 493.33 | 24.61 | 50.67 | 24.74 |
Annual Sum or Average | 851.67 | 26.06 | 5936.00 | 24.68 | 850.83 | 24.83 |
Minimum of Months | 46.17 | 25.80 | 454.00 | 24.61 | 46.17 | 24.74 |
Maximum of Months | 91.17 | 26.31 | 514.00 | 24.75 | 91.17 | 24.92 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.46777 | 50.65336 | 0.60530 | 13.02753 |
February | 454.00000 | 24.43493 | 51.19826 | 0.60309 | 12.93536 |
March | 514.00000 | 24.37158 | 51.82879 | 0.59318 | 12.64250 |
April | 485.00000 | 24.39391 | 52.71342 | 0.60301 | 12.90705 |
May | 508.00000 | 24.39400 | 52.71747 | -0.2383 | 6.71068 |
June | 496.00000 | 24.38659 | 52.42453 | -0.2387 | 6.73052 |
July | 497.00000 | 24.45422 | 52.91862 | -0.2245 | 6.64932 |
August | 514.00000 | 24.40094 | 53.37701 | -0.2368 | 6.75205 |
September | 485.00000 | 24.41714 | 53.24133 | -0.2331 | 6.68956 |
October | 502.00000 | 24.46505 | 52.92849 | 0.61710 | 13.34323 |
November | 489.00000 | 24.46773 | 51.80575 | 0.61170 | 13.19999 |
December | 497.00000 | 24.44299 | 51.50622 | 0.60100 | 12.88030 |
Annual Sum or Average | 5943.00000 | 24.42448 | 52.28355 | 0.25186 | 10.34701 |
Minimum of Months | 454.00000 | 24.37158 | 50.65336 | -0.2387 | 6.64932 |
Maximum of Months | 514.00000 | 24.46777 | 53.37701 | 0.61710 | 13.34323 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.36078 | 52.98527 | 0.57750 | 12.24601 |
February | 454.00000 | 24.33802 | 53.40570 | 0.57711 | 12.20194 |
March | 514.00000 | 24.29051 | 54.70463 | 0.57507 | 12.11039 |
April | 485.00000 | 24.30737 | 55.63690 | 0.58579 | 12.38283 |
May | 508.00000 | 24.32342 | 55.30600 | -0.2682 | 6.90626 |
June | 496.00000 | 24.31199 | 54.68670 | -0.2728 | 6.94897 |
July | 497.00000 | 24.35481 | 55.36906 | -0.2650 | 6.90972 |
August | 514.00000 | 24.30607 | 55.97609 | -0.2783 | 7.00130 |
September | 485.00000 | 24.32019 | 55.95075 | -0.2731 | 6.95383 |
October | 502.00000 | 24.36541 | 55.41508 | 0.59222 | 12.60707 |
November | 489.00000 | 24.35789 | 54.32683 | 0.58415 | 12.39398 |
December | 497.00000 | 24.33009 | 53.77001 | 0.57072 | 12.03733 |
Annual Sum or Average | 5943.00000 | 24.33038 | 54.80415 | 0.22202 | 10.03702 |
Minimum of Months | 454.00000 | 24.29051 | 52.98527 | -0.2783 | 6.90626 |
Maximum of Months | 514.00000 | 24.36541 | 55.97609 | 0.59222 | 12.60707 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.35990 | 52.82869 | 0.58398 | 12.39097 |
February | 454.00000 | 24.33702 | 53.21578 | 0.58662 | 12.44239 |
March | 514.00000 | 24.30399 | 54.54800 | 0.59072 | 12.50880 |
April | 485.00000 | 24.35224 | 55.58275 | 0.61173 | 13.08816 |
May | 508.00000 | 24.35788 | 55.58940 | -0.2357 | 6.66591 |
June | 496.00000 | 24.35072 | 55.15965 | -0.2359 | 6.67349 |
July | 497.00000 | 24.38724 | 55.17948 | -0.2403 | 6.70818 |
August | 514.00000 | 24.31194 | 56.14132 | -0.2613 | 6.82167 |
September | 485.00000 | 24.33806 | 56.02773 | -0.2498 | 6.77291 |
October | 502.00000 | 24.38841 | 55.59739 | 0.60688 | 13.02031 |
November | 489.00000 | 24.35983 | 54.54801 | 0.59453 | 12.65046 |
December | 497.00000 | 24.31426 | 53.68042 | 0.57414 | 12.11289 |
Annual Sum or Average | 5943.00000 | 24.34669 | 54.85297 | 0.24043 | 10.13129 |
Minimum of Months | 454.00000 | 24.30399 | 52.82869 | -0.2613 | 6.66591 |
Maximum of Months | 514.00000 | 24.38841 | 56.14132 | 0.61173 | 13.08816 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.44452 | 54.62647 | 0.63932 | 14.14225 |
February | 454.00000 | 24.46059 | 54.84666 | 0.65640 | 14.68990 |
March | 514.00000 | 24.41102 | 56.74007 | 0.66669 | 14.87944 |
April | 485.00000 | 24.52829 | 57.83450 | 0.71358 | 16.43377 |
May | 508.00000 | 24.54520 | 57.86459 | -0.0741 | 6.76599 |
June | 496.00000 | 24.52280 | 57.27452 | -0.0588 | 6.67587 |
July | 497.00000 | 24.58443 | 56.72137 | -0.0885 | 6.80888 |
August | 514.00000 | 24.42635 | 59.37044 | -0.1401 | 6.61501 |
September | 485.00000 | 24.47916 | 58.20057 | -0.1383 | 6.67460 |
October | 502.00000 | 24.51799 | 58.11452 | 0.68326 | 15.60984 |
November | 489.00000 | 24.47801 | 56.61869 | 0.66267 | 14.87287 |
December | 497.00000 | 24.40904 | 55.63409 | 0.63093 | 13.94635 |
Annual Sum or Average | 5943.00000 | 24.48378 | 57.00568 | 0.34300 | 11.47518 |
Minimum of Months | 454.00000 | 24.40904 | 54.62647 | -0.1401 | 6.61501 |
Maximum of Months | 514.00000 | 24.58443 | 59.37044 | 0.71358 | 16.43377 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.52434 | 53.99205 | 0.69260 | 15.79776 |
February | 454.00000 | 24.53742 | 54.18202 | 0.71552 | 16.60216 |
March | 514.00000 | 24.46025 | 56.08045 | 0.72243 | 16.71630 |
April | 485.00000 | 24.57057 | 57.18741 | 0.76533 | 18.23478 |
May | 508.00000 | 24.54278 | 57.66460 | -0.0497 | 6.90069 |
June | 496.00000 | 24.50604 | 57.23495 | -0.0510 | 6.65918 |
July | 497.00000 | 24.56890 | 56.72645 | -0.0779 | 6.79680 |
August | 514.00000 | 24.43579 | 59.00159 | -0.1006 | 6.65368 |
September | 485.00000 | 24.52368 | 57.68398 | -0.0794 | 6.88380 |
October | 502.00000 | 24.54441 | 57.68731 | 0.71709 | 16.75509 |
November | 489.00000 | 24.53256 | 56.11090 | 0.70323 | 16.20444 |
December | 497.00000 | 24.49358 | 54.93084 | 0.68195 | 15.58048 |
Annual Sum or Average | 5943.00000 | 24.51943 | 56.56075 | 0.38336 | 12.43944 |
Minimum of Months | 454.00000 | 24.43579 | 53.99205 | -0.1006 | 6.65368 |
Maximum of Months | 514.00000 | 24.57057 | 59.00159 | 0.76533 | 18.23478 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.58797 | 53.54936 | 0.73036 | 17.11482 |
February | 454.00000 | 24.55191 | 54.05361 | 0.72434 | 16.89725 |
March | 514.00000 | 24.44386 | 56.39048 | 0.69480 | 15.78985 |
April | 485.00000 | 24.51953 | 57.90199 | 0.70903 | 16.28193 |
May | 508.00000 | 24.50601 | 58.23924 | -0.1100 | 6.65192 |
June | 496.00000 | 24.47644 | 57.87673 | -0.1177 | 6.62733 |
July | 497.00000 | 24.54413 | 57.09929 | -0.1277 | 6.79421 |
August | 514.00000 | 24.40585 | 59.58645 | -0.1584 | 6.61780 |
September | 485.00000 | 24.48865 | 58.08680 | -0.1265 | 6.66835 |
October | 502.00000 | 24.56342 | 57.62837 | 0.71516 | 16.68693 |
November | 489.00000 | 24.57040 | 55.75788 | 0.72411 | 16.92046 |
December | 497.00000 | 24.57606 | 54.36763 | 0.72652 | 17.09660 |
Annual Sum or Average | 5943.00000 | 24.51881 | 56.73487 | 0.36180 | 12.46886 |
Minimum of Months | 454.00000 | 24.40585 | 53.54936 | -0.1584 | 6.61780 |
Maximum of Months | 514.00000 | 24.58797 | 59.58645 | 0.73036 | 17.11482 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.42806 | 54.32494 | 0.67134 | 15.23543 |
February | 454.00000 | 24.44309 | 54.54332 | 0.69219 | 15.84986 |
March | 514.00000 | 24.42064 | 56.29133 | 0.71199 | 16.39779 |
April | 485.00000 | 24.52615 | 57.44260 | 0.75075 | 17.71243 |
May | 508.00000 | 24.49239 | 57.88046 | -0.0728 | 6.78408 |
June | 496.00000 | 24.47644 | 57.47688 | -0.0686 | 6.71938 |
July | 497.00000 | 24.51974 | 56.90209 | -0.0988 | 6.81695 |
August | 514.00000 | 24.39824 | 59.20779 | -0.1198 | 6.69638 |
September | 485.00000 | 24.45357 | 57.95862 | -0.1085 | 6.75814 |
October | 502.00000 | 24.48225 | 57.88773 | 0.70094 | 16.20992 |
November | 489.00000 | 24.44814 | 56.37465 | 0.68390 | 15.57359 |
December | 497.00000 | 24.37371 | 55.34342 | 0.65596 | 14.83450 |
Annual Sum or Average | 5943.00000 | 24.45496 | 56.82224 | 0.36334 | 12.09413 |
Minimum of Months | 454.00000 | 24.37371 | 54.32494 | -0.1198 | 6.69638 |
Maximum of Months | 514.00000 | 24.52615 | 59.20779 | 0.75075 | 17.71243 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.45087 | 52.24602 | 0.62111 | 13.48478 |
February | 454.00000 | 24.47427 | 52.62846 | 0.63730 | 14.01531 |
March | 514.00000 | 24.40563 | 53.68439 | 0.63446 | 13.85705 |
April | 485.00000 | 24.49914 | 54.45733 | 0.67233 | 15.03393 |
May | 508.00000 | 24.54684 | 54.20178 | -0.1064 | 6.51233 |
June | 496.00000 | 24.53937 | 53.72224 | -0.0846 | 6.44048 |
July | 497.00000 | 24.60916 | 53.95309 | -0.0985 | 6.50790 |
August | 514.00000 | 24.45990 | 55.73669 | -0.1511 | 6.50462 |
September | 485.00000 | 24.49463 | 54.83543 | -0.1574 | 6.50196 |
October | 502.00000 | 24.51348 | 54.89349 | 0.65828 | 14.69680 |
November | 489.00000 | 24.48704 | 53.53460 | 0.64172 | 14.13625 |
December | 497.00000 | 24.43546 | 53.17265 | 0.61866 | 13.44251 |
Annual Sum or Average | 5943.00000 | 24.49284 | 53.93361 | 0.32072 | 10.89544 |
Minimum of Months | 454.00000 | 24.40563 | 52.24602 | -0.1574 | 6.44048 |
Maximum of Months | 514.00000 | 24.60916 | 55.73669 | 0.67233 | 15.03393 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.56595 | 51.64910 | 0.68362 | 15.41788 |
February | 454.00000 | 24.58405 | 51.95230 | 0.70583 | 16.19478 |
March | 514.00000 | 24.49772 | 52.97896 | 0.70216 | 16.00327 |
April | 485.00000 | 24.59043 | 53.78105 | 0.73637 | 17.18011 |
May | 508.00000 | 24.56875 | 54.06476 | -0.0734 | 6.63830 |
June | 496.00000 | 24.53220 | 53.77962 | -0.0733 | 6.43261 |
July | 497.00000 | 24.61009 | 54.00230 | -0.0833 | 6.50446 |
August | 514.00000 | 24.49354 | 55.43234 | -0.1029 | 6.47619 |
September | 485.00000 | 24.56927 | 54.34360 | -0.0880 | 6.61979 |
October | 502.00000 | 24.58521 | 54.46909 | 0.70286 | 16.16838 |
November | 489.00000 | 24.58263 | 53.05190 | 0.69244 | 15.78399 |
December | 497.00000 | 24.55841 | 52.54032 | 0.67915 | 15.36752 |
Annual Sum or Average | 5943.00000 | 24.56092 | 53.51762 | 0.37018 | 12.02384 |
Minimum of Months | 454.00000 | 24.49354 | 51.64910 | -0.1029 | 6.43261 |
Maximum of Months | 514.00000 | 24.61009 | 55.43234 | 0.73637 | 17.18011 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.93123 | 55.57372 | 0.81943 | 19.93184 |
February | 454.00000 | 24.93247 | 56.06676 | 0.81778 | 19.87755 |
March | 514.00000 | 24.69643 | 58.71154 | 0.75770 | 17.68329 |
April | 485.00000 | 24.65343 | 61.51602 | 0.75205 | 17.46670 |
May | 508.00000 | 24.66907 | 64.09502 | -0.0296 | 6.14458 |
June | 496.00000 | 24.65951 | 64.05563 | -0.0286 | 6.18453 |
July | 497.00000 | 24.63726 | 61.23966 | -0.0706 | 6.11299 |
August | 514.00000 | 24.54234 | 65.89881 | -0.0700 | 6.09388 |
September | 485.00000 | 24.62664 | 63.33856 | -0.0487 | 6.11764 |
October | 502.00000 | 24.69994 | 62.87187 | 0.78164 | 18.56189 |
November | 489.00000 | 24.82127 | 59.79374 | 0.80837 | 19.50980 |
December | 497.00000 | 24.87216 | 56.62464 | 0.80915 | 19.64283 |
Annual Sum or Average | 5943.00000 | 24.72666 | 60.85609 | 0.43795 | 13.55175 |
Minimum of Months | 454.00000 | 24.54234 | 55.57372 | -0.0706 | 6.09388 |
Maximum of Months | 514.00000 | 24.93247 | 65.89881 | 0.81943 | 19.93184 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.52997 | 51.84847 | 0.67443 | 15.14391 |
February | 454.00000 | 24.54422 | 52.19833 | 0.69383 | 15.76978 |
March | 514.00000 | 24.48711 | 53.16320 | 0.69837 | 15.86322 |
April | 485.00000 | 24.57419 | 53.99977 | 0.72872 | 16.89210 |
May | 508.00000 | 24.54737 | 54.24293 | -0.0866 | 6.52323 |
June | 496.00000 | 24.52538 | 53.97872 | -0.0821 | 6.46781 |
July | 497.00000 | 24.59866 | 54.12404 | -0.0918 | 6.50364 |
August | 514.00000 | 24.48747 | 55.60902 | -0.1115 | 6.47781 |
September | 485.00000 | 24.54240 | 54.57907 | -0.1034 | 6.50796 |
October | 502.00000 | 24.56711 | 54.62128 | 0.69670 | 15.93254 |
November | 489.00000 | 24.54614 | 53.23262 | 0.68291 | 15.43861 |
December | 497.00000 | 24.50879 | 52.77318 | 0.66720 | 14.96738 |
Annual Sum or Average | 5943.00000 | 24.53784 | 53.71076 | 0.36067 | 11.83486 |
Minimum of Months | 454.00000 | 24.48711 | 51.84847 | -0.1115 | 6.46781 |
Maximum of Months | 514.00000 | 24.59866 | 55.60902 | 0.72872 | 16.89210 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.45390 | 54.36735 | 0.63076 | 13.82647 |
February | 454.00000 | 24.47639 | 54.64017 | 0.64613 | 14.35067 |
March | 514.00000 | 24.41351 | 56.46800 | 0.65044 | 14.37103 |
April | 485.00000 | 24.50677 | 57.52324 | 0.68868 | 15.59058 |
May | 508.00000 | 24.53823 | 57.23085 | -0.1037 | 6.67133 |
June | 496.00000 | 24.51671 | 56.43753 | -0.0925 | 6.58467 |
July | 497.00000 | 24.57882 | 56.55191 | -0.1108 | 6.68762 |
August | 514.00000 | 24.43007 | 58.77610 | -0.1593 | 6.60634 |
September | 485.00000 | 24.47657 | 57.81461 | -0.1606 | 6.63055 |
October | 502.00000 | 24.51224 | 57.56247 | 0.66850 | 15.08507 |
November | 489.00000 | 24.48477 | 56.01471 | 0.65036 | 14.46499 |
December | 497.00000 | 24.43172 | 55.30360 | 0.62529 | 13.71011 |
Annual Sum or Average | 5943.00000 | 24.48474 | 56.57402 | 0.32463 | 11.18198 |
Minimum of Months | 454.00000 | 24.41351 | 54.36735 | -0.1606 | 6.58467 |
Maximum of Months | 514.00000 | 24.57882 | 58.77610 | 0.68868 | 15.59058 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 24.62401 | 54.18738 | 0.69255 | 15.83068 |
February | 385.00000 | 24.65177 | 54.36444 | 0.71492 | 16.65987 |
March | 433.00000 | 24.55261 | 56.07898 | 0.71141 | 16.44967 |
April | 410.00000 | 24.65861 | 57.05632 | 0.74977 | 17.78376 |
May | 430.00000 | 24.63373 | 57.33858 | -0.0670 | 7.00367 |
June | 418.00000 | 24.58932 | 56.86654 | -0.0747 | 6.76967 |
July | 422.00000 | 24.66016 | 56.69219 | -0.0886 | 6.84120 |
August | 433.00000 | 24.52416 | 58.76059 | -0.1135 | 6.80212 |
September | 410.00000 | 24.62169 | 57.44531 | -0.0908 | 6.98978 |
October | 427.00000 | 24.64487 | 57.43059 | 0.71376 | 16.68434 |
November | 417.00000 | 24.63885 | 55.98063 | 0.70275 | 16.24415 |
December | 422.00000 | 24.60816 | 55.03390 | 0.68601 | 15.74881 |
Annual Sum or Average | 5034.00000 | 24.61668 | 56.45223 | 0.37543 | 12.44959 |
Minimum of Months | 385.00000 | 24.52416 | 54.18738 | -0.1135 | 6.76967 |
Maximum of Months | 433.00000 | 24.66016 | 58.76059 | 0.74977 | 17.78376 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.64200 | 53.15850 | 0.72728 | 16.93836 |
February | 454.00000 | 24.59543 | 53.72725 | 0.71679 | 16.59266 |
March | 514.00000 | 24.45082 | 56.08212 | 0.67832 | 15.25225 |
April | 485.00000 | 24.49807 | 57.58974 | 0.68446 | 15.45199 |
May | 508.00000 | 24.49341 | 57.62834 | -0.1397 | 6.60425 |
June | 496.00000 | 24.46190 | 57.08234 | -0.1509 | 6.60102 |
July | 497.00000 | 24.53010 | 56.94464 | -0.1507 | 6.68671 |
August | 514.00000 | 24.40841 | 58.99085 | -0.1770 | 6.62653 |
September | 485.00000 | 24.48947 | 57.69240 | -0.1484 | 6.61664 |
October | 502.00000 | 24.56774 | 57.03982 | 0.70114 | 16.17689 |
November | 489.00000 | 24.59802 | 55.07461 | 0.71343 | 16.53596 |
December | 497.00000 | 24.63469 | 53.94299 | 0.72468 | 16.95624 |
Annual Sum or Average | 5943.00000 | 24.52992 | 56.26817 | 0.34468 | 12.21127 |
Minimum of Months | 454.00000 | 24.40841 | 53.15850 | -0.1770 | 6.60102 |
Maximum of Months | 514.00000 | 24.64200 | 58.99085 | 0.72728 | 16.95624 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.47383 | 54.07752 | 0.66894 | 15.04745 |
February | 454.00000 | 24.48850 | 54.33897 | 0.68663 | 15.59504 |
March | 514.00000 | 24.44141 | 56.05843 | 0.69844 | 15.89997 |
April | 485.00000 | 24.52355 | 57.14633 | 0.72910 | 16.92504 |
May | 508.00000 | 24.50198 | 57.27849 | -0.0970 | 6.63498 |
June | 496.00000 | 24.47776 | 56.69744 | -0.0983 | 6.58333 |
July | 497.00000 | 24.53324 | 56.76306 | -0.1149 | 6.62538 |
August | 514.00000 | 24.42374 | 58.63756 | -0.1329 | 6.58103 |
September | 485.00000 | 24.47936 | 57.57672 | -0.1237 | 6.61468 |
October | 502.00000 | 24.51264 | 57.34780 | 0.69296 | 15.84693 |
November | 489.00000 | 24.49212 | 55.77294 | 0.67814 | 15.32776 |
December | 497.00000 | 24.44153 | 54.99423 | 0.65796 | 14.76489 |
Annual Sum or Average | 5943.00000 | 24.48211 | 56.40847 | 0.35053 | 11.83296 |
Minimum of Months | 454.00000 | 24.42374 | 54.07752 | -0.1329 | 6.58103 |
Maximum of Months | 514.00000 | 24.53324 | 58.63756 | 0.72910 | 16.92504 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.100668E+12 | 0.257100E+11 | 471.92 | 0.704789E+11 | 0.301893E+11 | 0.00 | 1.00 | 01-JAN-02:00 | 0.00 | 01-JAN-00:10 | 134279.56 | 09-JAN-05:02 | 84317.48 | 02-JAN-07:03 | 57497.11 | 10-JAN-05:03 | 30657.85 | 09-JAN-05:02 | 0.00 |
February | 0.946139E+11 | 0.245213E+11 | 426.58 | 0.665834E+11 | 0.280305E+11 | 0.00 | 1.00 | 01-FEB-05:03 | 0.00 | 01-FEB-00:10 | 132864.26 | 16-FEB-07:03 | 85616.95 | 21-FEB-07:03 | 56851.37 | 16-FEB-05:03 | 31175.77 | 16-FEB-07:03 | 0.00 |
March | 0.114996E+12 | 0.301234E+11 | 489.71 | 0.791031E+11 | 0.358927E+11 | 0.00 | 1.00 | 01-MAR-05:03 | 0.00 | 01-MAR-00:10 | 136855.51 | 28-MAR-04:02 | 85375.14 | 06-MAR-07:03 | 63788.93 | 24-MAR-04:03 | 32442.85 | 28-MAR-04:02 | 0.00 |
April | 0.119330E+12 | 0.310741E+11 | 468.59 | 0.753616E+11 | 0.439684E+11 | 0.00 | 1.00 | 01-APR-04:03 | 0.00 | 01-APR-00:10 | 138579.06 | 01-APR-04:03 | 82130.91 | 17-APR-04:02 | 69662.53 | 01-APR-04:03 | 32519.61 | 01-APR-04:03 | 0.00 |
May | 0.137398E+12 | 0.354176E+11 | 496.81 | 0.804487E+11 | 0.569494E+11 | 0.00 | 1.00 | 01-MAY-00:23 | 0.00 | 01-MAY-00:03 | 140260.34 | 24-MAY-04:03 | 79288.47 | 08-MAY-06:03 | 73901.14 | 20-MAY-04:03 | 33644.54 | 04-MAY-13:00 | 0.00 |
June | 0.138163E+12 | 0.357776E+11 | 479.06 | 0.814718E+11 | 0.566917E+11 | 0.00 | 1.00 | 01-JUN-04:03 | 0.00 | 01-JUN-00:10 | 140078.74 | 15-JUN-04:02 | 80872.35 | 26-JUN-06:03 | 76025.26 | 10-JUN-04:03 | 34222.84 | 15-JUN-12:13 | 0.00 |
July | 0.110969E+12 | 0.278437E+11 | 473.71 | 0.713940E+11 | 0.395748E+11 | 0.00 | 1.00 | 01-JUL-04:03 | 0.00 | 01-JUL-00:10 | 135609.39 | 21-JUL-04:03 | 85285.89 | 31-JUL-06:03 | 61373.01 | 21-JUL-04:03 | 31248.69 | 24-JUL-04:02 | 0.00 |
August | 0.129879E+12 | 0.325189E+11 | 480.40 | 0.757411E+11 | 0.541379E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 139619.33 | 12-AUG-04:03 | 81757.09 | 28-AUG-06:03 | 71890.05 | 12-AUG-04:03 | 33450.09 | 02-AUG-04:02 | 0.00 |
September | 0.117737E+12 | 0.295104E+11 | 459.45 | 0.697278E+11 | 0.480090E+11 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 136275.09 | 01-SEP-04:03 | 81717.60 | 05-SEP-05:03 | 64170.13 | 01-SEP-04:03 | 32096.87 | 04-SEP-13:43 | 0.00 |
October | 0.114404E+12 | 0.283035E+11 | 463.50 | 0.682821E+11 | 0.461214E+11 | 0.00 | 1.00 | 02-OCT-05:03 | 0.00 | 01-OCT-00:10 | 136607.71 | 05-OCT-04:03 | 83871.23 | 10-OCT-04:02 | 63136.24 | 05-OCT-04:03 | 31848.18 | 05-OCT-06:03 | 0.00 |
November | 0.107047E+12 | 0.267295E+11 | 449.93 | 0.674038E+11 | 0.396434E+11 | 0.00 | 1.00 | 01-NOV-04:03 | 0.00 | 01-NOV-00:10 | 134863.40 | 03-NOV-04:03 | 84814.21 | 24-NOV-07:03 | 59775.34 | 03-NOV-04:03 | 31670.78 | 14-NOV-07:03 | 0.00 |
December | 0.983719E+11 | 0.247648E+11 | 461.31 | 0.663840E+11 | 0.319879E+11 | 0.00 | 1.00 | 01-DEC-05:03 | 0.00 | 01-DEC-00:10 | 134609.89 | 11-DEC-05:02 | 85197.65 | 26-DEC-07:03 | 55675.07 | 11-DEC-05:02 | 30651.18 | 11-DEC-05:02 | 0.00 |
Annual Sum or Average | 0.138358E+13 | 0.352295E+12 | 5620.96 | 0.872380E+12 | 0.511196E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.946139E+11 | 0.245213E+11 | 426.58 | 0.663840E+11 | 0.280305E+11 | 0.00 | 1.00 | 0.00 | 132864.26 | 79288.47 | 55675.07 | 30651.18 | 0.00 | ||||||
Maximum of Months | 0.138163E+12 | 0.357776E+11 | 496.81 | 0.814718E+11 | 0.569494E+11 | 0.00 | 1.00 | 0.00 | 140260.34 | 85616.95 | 76025.26 | 34222.84 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.851469E+11 | 0.216340E+11 | 454.50 | 0.590278E+11 | 0.261191E+11 | 0.00 | 1.00 | 01-JAN-01:53 | 0.00 | 01-JAN-00:10 | 117684.46 | 09-JAN-05:02 | 69542.83 | 02-JAN-07:03 | 54533.16 | 09-JAN-05:02 | 26600.81 | 09-JAN-05:02 | 0.00 |
February | 0.811582E+11 | 0.209136E+11 | 416.42 | 0.563845E+11 | 0.247737E+11 | 0.00 | 1.00 | 01-FEB-05:03 | 0.00 | 01-FEB-00:10 | 116749.83 | 06-FEB-05:02 | 74128.72 | 21-FEB-07:03 | 53707.74 | 16-FEB-06:03 | 26751.19 | 16-FEB-06:03 | 0.00 |
March | 0.988847E+11 | 0.257094E+11 | 480.61 | 0.676852E+11 | 0.311996E+11 | 0.00 | 1.00 | 01-MAR-05:03 | 0.00 | 01-MAR-00:10 | 118727.32 | 28-MAR-04:02 | 70081.53 | 20-MAR-06:03 | 60693.49 | 24-MAR-04:03 | 29501.56 | 19-MAR-15:32 | 0.00 |
April | 0.104168E+12 | 0.268626E+11 | 459.74 | 0.650456E+11 | 0.391224E+11 | 0.00 | 1.00 | 01-APR-04:03 | 0.00 | 01-APR-00:10 | 119199.82 | 12-APR-04:02 | 68304.61 | 03-APR-06:03 | 60075.89 | 01-APR-05:03 | 29913.82 | 02-APR-15:32 | 0.00 |
May | 0.119355E+12 | 0.305486E+11 | 485.55 | 0.684727E+11 | 0.508820E+11 | 0.00 | 1.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:13 | 120072.15 | 20-MAY-05:03 | 67619.99 | 08-MAY-06:03 | 68126.77 | 20-MAY-04:03 | 30869.07 | 29-MAY-15:02 | 0.00 |
June | 0.119713E+12 | 0.307415E+11 | 468.38 | 0.686390E+11 | 0.510739E+11 | 0.00 | 1.00 | 01-JUN-04:03 | 0.00 | 01-JUN-00:10 | 120015.37 | 07-JUN-04:02 | 67642.17 | 12-JUN-15:00 | 69780.62 | 10-JUN-04:03 | 31556.07 | 11-JUN-14:32 | 0.00 |
July | 0.937491E+11 | 0.233182E+11 | 458.58 | 0.588848E+11 | 0.348642E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 116576.00 | 28-JUL-05:03 | 70852.29 | 03-JUL-06:03 | 55457.79 | 28-JUL-05:03 | 27135.84 | 01-JUL-05:03 | 0.00 |
August | 0.110346E+12 | 0.274008E+11 | 468.40 | 0.622537E+11 | 0.480921E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 120626.06 | 21-AUG-04:02 | 68156.07 | 28-AUG-04:02 | 70399.00 | 21-AUG-04:04 | 30620.46 | 13-AUG-12:13 | 0.00 |
September | 0.100668E+12 | 0.250058E+11 | 447.95 | 0.579371E+11 | 0.427311E+11 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 119375.60 | 25-SEP-04:04 | 67955.29 | 05-SEP-04:02 | 65406.99 | 25-SEP-04:04 | 30442.29 | 04-SEP-15:51 | 0.00 |
October | 0.976308E+11 | 0.239566E+11 | 451.24 | 0.566834E+11 | 0.409474E+11 | 0.00 | 1.00 | 01-OCT-06:20 | 0.00 | 01-OCT-00:10 | 119980.93 | 23-OCT-04:02 | 69502.15 | 10-OCT-06:03 | 62359.37 | 23-OCT-04:02 | 27379.02 | 05-OCT-04:03 | 0.00 |
November | 0.905992E+11 | 0.224648E+11 | 436.18 | 0.558808E+11 | 0.347184E+11 | 0.00 | 1.00 | 01-NOV-04:03 | 0.00 | 01-NOV-00:10 | 115908.14 | 03-NOV-05:03 | 70690.91 | 24-NOV-07:03 | 52547.66 | 03-NOV-04:03 | 27145.13 | 14-NOV-07:03 | 0.00 |
December | 0.834079E+11 | 0.208765E+11 | 447.08 | 0.551312E+11 | 0.282767E+11 | 0.00 | 1.00 | 01-DEC-05:03 | 0.00 | 01-DEC-00:10 | 117193.12 | 11-DEC-05:02 | 71363.34 | 26-DEC-07:03 | 54264.23 | 11-DEC-05:02 | 26496.28 | 11-DEC-05:02 | 0.00 |
Annual Sum or Average | 0.118483E+13 | 0.299432E+12 | 5474.63 | 0.732026E+12 | 0.452801E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.811582E+11 | 0.208765E+11 | 416.42 | 0.551312E+11 | 0.247737E+11 | 0.00 | 1.00 | 0.00 | 115908.14 | 67619.99 | 52547.66 | 26496.28 | 0.00 | ||||||
Maximum of Months | 0.119713E+12 | 0.307415E+11 | 485.55 | 0.686390E+11 | 0.510739E+11 | 0.00 | 1.00 | 0.00 | 120626.06 | 74128.72 | 70399.00 | 31556.07 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.899425E+11 | 0.230516E+11 | 450.54 | 0.638520E+11 | 0.260905E+11 | 0.00 | 1.00 | 01-JAN-03:02 | 0.00 | 01-JAN-00:10 | 140213.95 | 09-JAN-05:02 | 73199.83 | 09-JAN-05:02 | 67014.12 | 09-JAN-05:02 | 31776.90 | 09-JAN-05:02 | 0.00 |
February | 0.865101E+11 | 0.224923E+11 | 413.57 | 0.617619E+11 | 0.247482E+11 | 0.00 | 1.00 | 01-FEB-05:03 | 0.00 | 01-FEB-00:10 | 136520.94 | 06-FEB-05:02 | 82873.68 | 21-FEB-05:02 | 63201.69 | 06-FEB-05:02 | 32130.15 | 26-FEB-15:32 | 0.00 |
March | 0.106552E+12 | 0.278980E+11 | 479.71 | 0.751871E+11 | 0.313645E+11 | 0.00 | 1.00 | 01-MAR-05:03 | 0.00 | 01-MAR-00:10 | 142478.92 | 28-MAR-04:02 | 87830.72 | 19-MAR-14:52 | 75586.74 | 25-MAR-05:03 | 35247.11 | 19-MAR-15:32 | 0.00 |
April | 0.112466E+12 | 0.291475E+11 | 463.31 | 0.728718E+11 | 0.395939E+11 | 0.00 | 1.00 | 01-APR-04:03 | 0.00 | 01-APR-00:10 | 143228.23 | 12-APR-04:02 | 83024.90 | 02-APR-15:32 | 76316.01 | 01-APR-05:03 | 37453.81 | 02-APR-14:52 | 0.00 |
May | 0.127233E+12 | 0.327123E+11 | 489.66 | 0.759633E+11 | 0.512693E+11 | 0.00 | 1.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:23 | 143913.40 | 20-MAY-05:03 | 83001.48 | 07-MAY-14:32 | 85141.57 | 22-MAY-04:04 | 37138.41 | 07-MAY-14:32 | 0.00 |
June | 0.127916E+12 | 0.329936E+11 | 471.61 | 0.767823E+11 | 0.511335E+11 | 0.00 | 1.00 | 01-JUN-04:03 | 0.00 | 01-JUN-00:10 | 144013.08 | 08-JUN-04:02 | 84545.67 | 18-JUN-13:52 | 85815.16 | 10-JUN-04:03 | 38535.12 | 18-JUN-13:52 | 0.00 |
July | 0.100126E+12 | 0.250791E+11 | 463.50 | 0.647078E+11 | 0.354186E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 137951.17 | 10-JUL-04:02 | 84675.37 | 03-JUL-04:02 | 63338.68 | 21-JUL-05:03 | 32189.55 | 24-JUL-04:02 | 0.00 |
August | 0.115862E+12 | 0.288900E+11 | 468.93 | 0.676121E+11 | 0.482502E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 144577.30 | 21-AUG-04:02 | 80958.91 | 28-AUG-04:02 | 88820.39 | 21-AUG-04:02 | 37138.41 | 13-AUG-14:52 | 0.00 |
September | 0.106797E+12 | 0.266672E+11 | 452.21 | 0.636763E+11 | 0.431209E+11 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 142972.67 | 02-SEP-05:03 | 79122.75 | 11-SEP-04:02 | 76826.59 | 02-SEP-05:03 | 36122.13 | 04-SEP-12:43 | 0.00 |
October | 0.102054E+12 | 0.251943E+11 | 452.36 | 0.610536E+11 | 0.410003E+11 | 0.00 | 1.00 | 01-OCT-08:50 | 0.00 | 01-OCT-00:10 | 143795.54 | 23-OCT-04:02 | 80225.71 | 16-OCT-04:02 | 78446.45 | 23-OCT-04:02 | 32594.66 | 09-OCT-12:02 | 0.00 |
November | 0.947222E+11 | 0.236422E+11 | 433.46 | 0.602898E+11 | 0.344324E+11 | 0.00 | 1.00 | 01-NOV-06:03 | 0.00 | 01-NOV-00:10 | 139925.09 | 13-NOV-05:02 | 78594.81 | 24-NOV-05:02 | 64219.11 | 13-NOV-05:02 | 32208.94 | 13-NOV-07:03 | 0.00 |
December | 0.872038E+11 | 0.220192E+11 | 439.90 | 0.592283E+11 | 0.279755E+11 | 0.00 | 1.00 | 01-DEC-06:03 | 0.00 | 01-DEC-00:10 | 128096.03 | 11-DEC-05:02 | 74399.75 | 26-DEC-05:02 | 63402.85 | 11-DEC-05:02 | 29023.90 | 11-DEC-05:02 | 0.00 |
Annual Sum or Average | 0.125738E+13 | 0.319787E+12 | 5478.77 | 0.802986E+12 | 0.454398E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.865101E+11 | 0.220192E+11 | 413.57 | 0.592283E+11 | 0.247482E+11 | 0.00 | 1.00 | 0.00 | 128096.03 | 73199.83 | 63201.69 | 29023.90 | 0.00 | ||||||
Maximum of Months | 0.127916E+12 | 0.329936E+11 | 489.66 | 0.767823E+11 | 0.512693E+11 | 0.00 | 1.00 | 0.00 | 144577.30 | 87830.72 | 88820.39 | 38535.12 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 449.46 | 0.00 | 449.46 | 913.11 | 192.04 | 0.00 | 0.00 | 0.00 |
February | 479.45 | 0.00 | 479.45 | 1019.82 | 147.20 | 0.00 | 0.00 | 0.00 |
March | 492.06 | 0.00 | 492.06 | 1107.54 | 99.41 | 0.00 | 0.00 | 0.00 |
April | 535.49 | 7.59 | 527.91 | 1238.76 | 45.90 | 0.00 | 0.00 | 0.00 |
May | 686.44 | 73.13 | 613.31 | 1586.69 | 54.02 | 0.00 | 0.00 | 0.00 |
June | 838.51 | 169.46 | 669.05 | 1892.91 | 62.28 | 0.00 | 0.00 | 0.00 |
July | 721.04 | 75.58 | 645.46 | 1493.11 | 107.35 | 0.00 | 0.00 | 0.00 |
August | 593.65 | 25.31 | 568.34 | 1246.50 | 82.67 | 0.00 | 0.00 | 0.00 |
September | 505.43 | 0.24 | 505.19 | 1089.17 | 83.01 | 0.00 | 0.00 | 0.00 |
October | 487.00 | 0.00 | 487.00 | 975.88 | 109.94 | 0.00 | 0.00 | 0.00 |
November | 460.81 | 0.00 | 460.81 | 931.28 | 131.38 | 0.00 | 0.00 | 0.00 |
December | 436.64 | 0.00 | 436.64 | 879.64 | 210.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 557.50 | 29.35 | 528.15 | 1198.34 | 110.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 436.64 | 0.00 | 436.64 | 879.64 | 45.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 838.51 | 169.46 | 669.05 | 1892.91 | 210.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 577.78 | 194.73 | 383.05 | 1092.28 | 122.24 | 0.00 | 0.00 | 0.00 |
February | 655.20 | 240.23 | 414.97 | 1265.85 | 92.35 | 0.00 | 0.00 | 0.00 |
March | 714.30 | 279.71 | 434.58 | 1412.54 | 61.06 | 0.00 | 0.00 | 0.00 |
April | 721.91 | 275.80 | 446.11 | 1461.86 | 28.52 | 0.00 | 0.00 | 0.00 |
May | 620.54 | 187.84 | 432.71 | 1304.98 | 34.89 | 0.00 | 0.00 | 0.00 |
June | 660.93 | 217.67 | 443.26 | 1373.67 | 39.33 | 0.00 | 0.00 | 0.00 |
July | 564.53 | 126.47 | 438.06 | 1107.81 | 69.37 | 0.00 | 0.00 | 0.00 |
August | 621.27 | 182.63 | 438.64 | 1203.71 | 54.53 | 0.00 | 0.00 | 0.00 |
September | 583.45 | 158.99 | 424.46 | 1157.88 | 55.77 | 0.00 | 0.00 | 0.00 |
October | 546.82 | 139.90 | 406.93 | 1036.09 | 73.59 | 0.00 | 0.00 | 0.00 |
November | 529.21 | 146.25 | 382.97 | 1007.75 | 87.60 | 0.00 | 0.00 | 0.00 |
December | 541.57 | 173.79 | 367.77 | 1019.45 | 136.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 610.96 | 193.22 | 417.75 | 1202.63 | 71.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 529.21 | 126.47 | 367.77 | 1007.75 | 28.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 721.91 | 279.71 | 446.11 | 1461.86 | 136.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1189.99 | 496.48 | 693.51 | 2278.13 | 195.29 | 0.00 | 0.00 | 0.00 |
February | 1010.48 | 329.45 | 681.03 | 2073.19 | 145.91 | 0.00 | 0.00 | 0.00 |
March | 689.60 | 92.61 | 596.98 | 1553.77 | 94.44 | 0.00 | 0.00 | 0.00 |
April | 514.13 | 0.23 | 513.90 | 1203.10 | 41.17 | 0.00 | 0.00 | 0.00 |
May | 514.48 | 0.00 | 514.48 | 1233.22 | 49.74 | 0.00 | 0.00 | 0.00 |
June | 512.63 | 0.00 | 512.63 | 1225.73 | 55.32 | 0.00 | 0.00 | 0.00 |
July | 528.08 | 0.00 | 528.08 | 1103.21 | 102.07 | 0.00 | 0.00 | 0.00 |
August | 514.09 | 0.79 | 513.30 | 1083.22 | 76.87 | 0.00 | 0.00 | 0.00 |
September | 569.14 | 18.59 | 550.55 | 1222.29 | 83.13 | 0.00 | 0.00 | 0.00 |
October | 744.60 | 118.72 | 625.88 | 1481.62 | 115.10 | 0.00 | 0.00 | 0.00 |
November | 968.22 | 295.39 | 672.83 | 1881.03 | 139.46 | 0.00 | 0.00 | 0.00 |
December | 1189.38 | 506.03 | 683.35 | 2244.35 | 218.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 744.37 | 154.26 | 590.11 | 1546.07 | 109.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 512.63 | 0.00 | 512.63 | 1083.22 | 41.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1189.99 | 506.03 | 693.51 | 2278.13 | 218.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 585.42 | 205.85 | 379.57 | 1120.26 | 134.98 | 0.00 | 0.00 | 0.00 |
February | 642.96 | 227.53 | 415.43 | 1256.23 | 103.52 | 0.00 | 0.00 | 0.00 |
March | 720.71 | 284.67 | 436.04 | 1432.76 | 74.52 | 0.00 | 0.00 | 0.00 |
April | 724.27 | 277.41 | 446.87 | 1457.83 | 34.88 | 0.00 | 0.00 | 0.00 |
May | 616.28 | 182.57 | 433.70 | 1289.41 | 35.39 | 0.00 | 0.00 | 0.00 |
June | 667.81 | 230.18 | 437.63 | 1377.28 | 40.21 | 0.00 | 0.00 | 0.00 |
July | 569.35 | 134.26 | 435.08 | 1115.24 | 71.54 | 0.00 | 0.00 | 0.00 |
August | 618.99 | 183.31 | 435.68 | 1192.67 | 55.82 | 0.00 | 0.00 | 0.00 |
September | 579.78 | 160.80 | 418.97 | 1146.00 | 58.39 | 0.00 | 0.00 | 0.00 |
October | 544.52 | 140.37 | 404.16 | 1031.29 | 77.06 | 0.00 | 0.00 | 0.00 |
November | 531.02 | 144.83 | 386.20 | 1014.91 | 92.04 | 0.00 | 0.00 | 0.00 |
December | 543.46 | 177.77 | 365.68 | 1039.09 | 146.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 611.64 | 195.45 | 416.19 | 1205.20 | 77.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 531.02 | 134.26 | 365.68 | 1014.91 | 34.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 724.27 | 284.67 | 446.87 | 1457.83 | 146.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 149.81 | 0.00 | 149.81 | 306.35 | 66.35 | 0.00 | 0.00 | 0.00 |
February | 159.81 | 0.00 | 159.81 | 342.26 | 51.66 | 0.00 | 0.00 | 0.00 |
March | 164.01 | 0.00 | 164.01 | 371.77 | 34.42 | 0.00 | 0.00 | 0.00 |
April | 178.49 | 2.53 | 175.96 | 416.64 | 15.55 | 0.00 | 0.00 | 0.00 |
May | 228.80 | 24.37 | 204.43 | 531.95 | 19.73 | 0.00 | 0.00 | 0.00 |
June | 279.49 | 56.48 | 223.01 | 633.41 | 22.84 | 0.00 | 0.00 | 0.00 |
July | 240.34 | 25.19 | 215.14 | 500.36 | 39.21 | 0.00 | 0.00 | 0.00 |
August | 197.87 | 8.44 | 189.44 | 416.15 | 31.00 | 0.00 | 0.00 | 0.00 |
September | 168.47 | 0.08 | 168.39 | 364.50 | 30.14 | 0.00 | 0.00 | 0.00 |
October | 162.33 | 0.00 | 162.33 | 327.62 | 38.07 | 0.00 | 0.00 | 0.00 |
November | 153.60 | 0.00 | 153.60 | 312.40 | 46.44 | 0.00 | 0.00 | 0.00 |
December | 145.54 | 0.00 | 145.54 | 294.63 | 74.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 185.82 | 9.78 | 176.04 | 401.66 | 39.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 145.54 | 0.00 | 145.54 | 294.63 | 15.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 279.49 | 56.48 | 223.01 | 633.41 | 74.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 149.82 | 0.00 | 149.82 | 306.37 | 66.35 | 0.00 | 0.00 | 0.00 |
February | 159.82 | 0.00 | 159.82 | 342.28 | 51.66 | 0.00 | 0.00 | 0.00 |
March | 164.02 | 0.00 | 164.02 | 371.80 | 34.43 | 0.00 | 0.00 | 0.00 |
April | 178.50 | 2.53 | 175.97 | 416.67 | 15.55 | 0.00 | 0.00 | 0.00 |
May | 228.82 | 24.38 | 204.44 | 531.99 | 19.73 | 0.00 | 0.00 | 0.00 |
June | 279.51 | 56.49 | 223.02 | 633.45 | 22.84 | 0.00 | 0.00 | 0.00 |
July | 240.35 | 25.19 | 215.16 | 500.39 | 39.21 | 0.00 | 0.00 | 0.00 |
August | 197.89 | 8.44 | 189.45 | 416.17 | 31.00 | 0.00 | 0.00 | 0.00 |
September | 168.48 | 0.08 | 168.40 | 364.53 | 30.14 | 0.00 | 0.00 | 0.00 |
October | 162.34 | 0.00 | 162.34 | 327.64 | 38.08 | 0.00 | 0.00 | 0.00 |
November | 153.61 | 0.00 | 153.61 | 312.42 | 46.44 | 0.00 | 0.00 | 0.00 |
December | 145.55 | 0.00 | 145.55 | 294.65 | 74.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 185.84 | 9.78 | 176.05 | 401.68 | 39.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 145.55 | 0.00 | 145.55 | 294.65 | 15.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 279.51 | 56.49 | 223.02 | 633.45 | 74.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 149.82 | 0.00 | 149.82 | 306.37 | 66.35 | 0.00 | 0.00 | 0.00 |
February | 159.82 | 0.00 | 159.82 | 342.28 | 51.66 | 0.00 | 0.00 | 0.00 |
March | 164.02 | 0.00 | 164.02 | 371.80 | 34.43 | 0.00 | 0.00 | 0.00 |
April | 178.50 | 2.53 | 175.97 | 416.67 | 15.55 | 0.00 | 0.00 | 0.00 |
May | 228.82 | 24.38 | 204.44 | 531.99 | 19.73 | 0.00 | 0.00 | 0.00 |
June | 279.51 | 56.49 | 223.02 | 633.45 | 22.84 | 0.00 | 0.00 | 0.00 |
July | 240.35 | 25.19 | 215.16 | 500.39 | 39.21 | 0.00 | 0.00 | 0.00 |
August | 197.89 | 8.44 | 189.45 | 416.17 | 31.00 | 0.00 | 0.00 | 0.00 |
September | 168.48 | 0.08 | 168.40 | 364.53 | 30.14 | 0.00 | 0.00 | 0.00 |
October | 162.34 | 0.00 | 162.34 | 327.64 | 38.08 | 0.00 | 0.00 | 0.00 |
November | 153.61 | 0.00 | 153.61 | 312.42 | 46.44 | 0.00 | 0.00 | 0.00 |
December | 145.55 | 0.00 | 145.55 | 294.65 | 74.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 185.84 | 9.78 | 176.05 | 401.68 | 39.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 145.55 | 0.00 | 145.55 | 294.65 | 15.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 279.51 | 56.49 | 223.02 | 633.45 | 74.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 555.80 | 187.32 | 368.48 | 1054.55 | 126.96 | 0.00 | 0.00 | 0.00 |
February | 630.28 | 231.09 | 399.19 | 1222.14 | 99.58 | 0.00 | 0.00 | 0.00 |
March | 687.12 | 269.07 | 418.05 | 1365.36 | 68.32 | 0.00 | 0.00 | 0.00 |
April | 694.44 | 265.30 | 429.14 | 1412.33 | 32.61 | 0.00 | 0.00 | 0.00 |
May | 596.94 | 180.69 | 416.25 | 1259.08 | 38.50 | 0.00 | 0.00 | 0.00 |
June | 635.79 | 209.39 | 426.39 | 1325.30 | 43.01 | 0.00 | 0.00 | 0.00 |
July | 543.05 | 121.66 | 421.39 | 1069.51 | 74.84 | 0.00 | 0.00 | 0.00 |
August | 597.64 | 175.68 | 421.96 | 1159.44 | 62.30 | 0.00 | 0.00 | 0.00 |
September | 561.25 | 152.94 | 408.31 | 1116.56 | 62.44 | 0.00 | 0.00 | 0.00 |
October | 526.02 | 134.57 | 391.45 | 1001.27 | 77.82 | 0.00 | 0.00 | 0.00 |
November | 509.08 | 140.68 | 368.40 | 973.48 | 93.57 | 0.00 | 0.00 | 0.00 |
December | 520.96 | 167.18 | 353.78 | 983.87 | 143.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 587.72 | 185.87 | 401.85 | 1160.92 | 76.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 509.08 | 121.66 | 353.78 | 973.48 | 32.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 694.44 | 269.07 | 429.14 | 1412.33 | 143.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.98 | 7.41 | 14.57 | 41.70 | 5.02 | 0.00 | 0.00 | 0.00 |
February | 24.92 | 9.14 | 15.78 | 48.32 | 3.94 | 0.00 | 0.00 | 0.00 |
March | 27.17 | 10.64 | 16.53 | 53.99 | 2.70 | 0.00 | 0.00 | 0.00 |
April | 27.46 | 10.49 | 16.97 | 55.84 | 1.29 | 0.00 | 0.00 | 0.00 |
May | 23.60 | 7.14 | 16.46 | 49.78 | 1.52 | 0.00 | 0.00 | 0.00 |
June | 25.14 | 8.28 | 16.86 | 52.40 | 1.70 | 0.00 | 0.00 | 0.00 |
July | 21.47 | 4.81 | 16.66 | 42.29 | 2.96 | 0.00 | 0.00 | 0.00 |
August | 23.63 | 6.95 | 16.68 | 45.84 | 2.46 | 0.00 | 0.00 | 0.00 |
September | 22.19 | 6.05 | 16.14 | 44.15 | 2.47 | 0.00 | 0.00 | 0.00 |
October | 20.80 | 5.32 | 15.48 | 39.59 | 3.08 | 0.00 | 0.00 | 0.00 |
November | 20.13 | 5.56 | 14.57 | 38.49 | 3.70 | 0.00 | 0.00 | 0.00 |
December | 20.60 | 6.61 | 13.99 | 38.90 | 5.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.24 | 7.35 | 15.89 | 45.90 | 3.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.13 | 4.81 | 13.99 | 38.49 | 1.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 27.46 | 10.64 | 16.97 | 55.84 | 5.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 396.67 | 165.50 | 231.18 | 755.60 | 73.82 | 0.00 | 0.00 | 0.00 |
February | 336.84 | 109.82 | 227.02 | 686.51 | 57.02 | 0.00 | 0.00 | 0.00 |
March | 229.87 | 30.87 | 199.00 | 515.31 | 36.30 | 0.00 | 0.00 | 0.00 |
April | 171.38 | 0.08 | 171.30 | 400.32 | 14.96 | 0.00 | 0.00 | 0.00 |
May | 171.50 | 0.00 | 171.50 | 409.54 | 18.46 | 0.00 | 0.00 | 0.00 |
June | 170.88 | 0.00 | 170.88 | 405.67 | 20.05 | 0.00 | 0.00 | 0.00 |
July | 176.03 | 0.00 | 176.03 | 368.15 | 37.23 | 0.00 | 0.00 | 0.00 |
August | 171.37 | 0.26 | 171.10 | 358.97 | 29.57 | 0.00 | 0.00 | 0.00 |
September | 189.72 | 6.20 | 183.52 | 406.49 | 31.24 | 0.00 | 0.00 | 0.00 |
October | 248.21 | 39.57 | 208.63 | 494.05 | 42.21 | 0.00 | 0.00 | 0.00 |
November | 322.75 | 98.47 | 224.28 | 624.71 | 53.34 | 0.00 | 0.00 | 0.00 |
December | 396.47 | 168.68 | 227.79 | 745.56 | 82.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 248.13 | 51.42 | 196.71 | 513.43 | 41.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 170.88 | 0.00 | 170.88 | 358.97 | 14.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 396.67 | 168.68 | 231.18 | 755.60 | 82.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 396.67 | 165.50 | 231.18 | 755.60 | 73.82 | 0.00 | 0.00 | 0.00 |
February | 336.84 | 109.82 | 227.02 | 686.51 | 57.02 | 0.00 | 0.00 | 0.00 |
March | 229.87 | 30.87 | 199.00 | 515.31 | 36.30 | 0.00 | 0.00 | 0.00 |
April | 171.38 | 0.08 | 171.30 | 400.32 | 14.96 | 0.00 | 0.00 | 0.00 |
May | 171.50 | 0.00 | 171.50 | 409.54 | 18.46 | 0.00 | 0.00 | 0.00 |
June | 170.88 | 0.00 | 170.88 | 405.67 | 20.05 | 0.00 | 0.00 | 0.00 |
July | 176.03 | 0.00 | 176.03 | 368.15 | 37.23 | 0.00 | 0.00 | 0.00 |
August | 171.37 | 0.26 | 171.10 | 358.97 | 29.57 | 0.00 | 0.00 | 0.00 |
September | 189.72 | 6.20 | 183.52 | 406.49 | 31.24 | 0.00 | 0.00 | 0.00 |
October | 248.21 | 39.57 | 208.63 | 494.05 | 42.21 | 0.00 | 0.00 | 0.00 |
November | 322.75 | 98.47 | 224.28 | 624.71 | 53.34 | 0.00 | 0.00 | 0.00 |
December | 396.47 | 168.68 | 227.79 | 745.56 | 82.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 248.13 | 51.42 | 196.71 | 513.43 | 41.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 170.88 | 0.00 | 170.88 | 358.97 | 14.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 396.67 | 168.68 | 231.18 | 755.60 | 82.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 396.65 | 165.49 | 231.16 | 755.55 | 73.81 | 0.00 | 0.00 | 0.00 |
February | 336.82 | 109.81 | 227.00 | 686.46 | 57.01 | 0.00 | 0.00 | 0.00 |
March | 229.86 | 30.87 | 198.99 | 515.27 | 36.30 | 0.00 | 0.00 | 0.00 |
April | 171.37 | 0.08 | 171.29 | 400.30 | 14.96 | 0.00 | 0.00 | 0.00 |
May | 171.49 | 0.00 | 171.49 | 409.52 | 18.45 | 0.00 | 0.00 | 0.00 |
June | 170.87 | 0.00 | 170.87 | 405.65 | 20.05 | 0.00 | 0.00 | 0.00 |
July | 176.02 | 0.00 | 176.02 | 368.13 | 37.22 | 0.00 | 0.00 | 0.00 |
August | 171.36 | 0.26 | 171.09 | 358.94 | 29.57 | 0.00 | 0.00 | 0.00 |
September | 189.71 | 6.20 | 183.51 | 406.47 | 31.24 | 0.00 | 0.00 | 0.00 |
October | 248.19 | 39.57 | 208.62 | 494.02 | 42.20 | 0.00 | 0.00 | 0.00 |
November | 322.73 | 98.46 | 224.27 | 624.67 | 53.33 | 0.00 | 0.00 | 0.00 |
December | 396.45 | 168.67 | 227.77 | 745.51 | 82.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 248.11 | 51.42 | 196.70 | 513.39 | 41.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 170.87 | 0.00 | 170.87 | 358.94 | 14.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 396.65 | 168.67 | 231.16 | 755.55 | 82.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 563.15 | 198.02 | 365.13 | 1080.79 | 140.13 | 0.00 | 0.00 | 0.00 |
February | 618.50 | 218.87 | 399.63 | 1212.67 | 111.36 | 0.00 | 0.00 | 0.00 |
March | 693.29 | 273.84 | 419.46 | 1383.84 | 81.37 | 0.00 | 0.00 | 0.00 |
April | 696.72 | 266.85 | 429.87 | 1407.87 | 39.50 | 0.00 | 0.00 | 0.00 |
May | 592.83 | 175.63 | 417.20 | 1243.46 | 40.14 | 0.00 | 0.00 | 0.00 |
June | 642.41 | 221.42 | 420.99 | 1328.26 | 45.14 | 0.00 | 0.00 | 0.00 |
July | 547.69 | 129.16 | 418.53 | 1076.83 | 78.30 | 0.00 | 0.00 | 0.00 |
August | 595.44 | 176.34 | 419.11 | 1148.96 | 64.95 | 0.00 | 0.00 | 0.00 |
September | 557.72 | 154.69 | 403.03 | 1104.93 | 65.74 | 0.00 | 0.00 | 0.00 |
October | 523.81 | 135.03 | 388.78 | 995.79 | 82.34 | 0.00 | 0.00 | 0.00 |
November | 510.82 | 139.32 | 371.50 | 978.95 | 98.42 | 0.00 | 0.00 | 0.00 |
December | 522.78 | 171.01 | 351.77 | 1001.48 | 154.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 588.38 | 188.02 | 400.36 | 1162.80 | 83.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 510.82 | 129.16 | 351.77 | 978.95 | 39.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 696.72 | 273.84 | 429.87 | 1407.87 | 154.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.27 | 7.83 | 14.44 | 42.73 | 5.54 | 0.00 | 0.00 | 0.00 |
February | 24.45 | 8.65 | 15.80 | 47.95 | 4.40 | 0.00 | 0.00 | 0.00 |
March | 27.41 | 10.83 | 16.58 | 54.72 | 3.22 | 0.00 | 0.00 | 0.00 |
April | 27.55 | 10.55 | 17.00 | 55.67 | 1.56 | 0.00 | 0.00 | 0.00 |
May | 23.44 | 6.94 | 16.50 | 49.17 | 1.59 | 0.00 | 0.00 | 0.00 |
June | 25.40 | 8.75 | 16.65 | 52.52 | 1.78 | 0.00 | 0.00 | 0.00 |
July | 21.65 | 5.11 | 16.55 | 42.58 | 3.10 | 0.00 | 0.00 | 0.00 |
August | 23.54 | 6.97 | 16.57 | 45.43 | 2.57 | 0.00 | 0.00 | 0.00 |
September | 22.05 | 6.12 | 15.94 | 43.69 | 2.60 | 0.00 | 0.00 | 0.00 |
October | 20.71 | 5.34 | 15.37 | 39.37 | 3.26 | 0.00 | 0.00 | 0.00 |
November | 20.20 | 5.51 | 14.69 | 38.71 | 3.89 | 0.00 | 0.00 | 0.00 |
December | 20.67 | 6.76 | 13.91 | 39.60 | 6.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.26 | 7.43 | 15.83 | 45.98 | 3.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.20 | 5.11 | 13.91 | 38.71 | 1.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 27.55 | 10.83 | 17.00 | 55.67 | 6.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 449.46 | 0.00 | 449.46 | 920.68 | 198.65 | 0.00 | 0.00 | 0.00 |
February | 479.45 | 0.00 | 479.45 | 1028.90 | 153.09 | 0.00 | 0.00 | 0.00 |
March | 492.06 | 0.00 | 492.06 | 1118.13 | 101.88 | 0.00 | 0.00 | 0.00 |
April | 535.49 | 7.59 | 527.91 | 1253.81 | 45.69 | 0.00 | 0.00 | 0.00 |
May | 686.44 | 73.13 | 613.31 | 1601.22 | 54.47 | 0.00 | 0.00 | 0.00 |
June | 838.51 | 169.46 | 669.05 | 1908.00 | 61.44 | 0.00 | 0.00 | 0.00 |
July | 721.04 | 75.58 | 645.46 | 1505.96 | 108.67 | 0.00 | 0.00 | 0.00 |
August | 593.65 | 25.31 | 568.34 | 1255.92 | 84.45 | 0.00 | 0.00 | 0.00 |
September | 505.43 | 0.24 | 505.19 | 1100.21 | 84.21 | 0.00 | 0.00 | 0.00 |
October | 487.00 | 0.00 | 487.00 | 985.02 | 111.61 | 0.00 | 0.00 | 0.00 |
November | 460.81 | 0.00 | 460.81 | 939.36 | 136.03 | 0.00 | 0.00 | 0.00 |
December | 436.64 | 0.00 | 436.64 | 886.03 | 218.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 557.50 | 29.35 | 528.15 | 1209.07 | 113.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 436.64 | 0.00 | 436.64 | 886.03 | 45.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 838.51 | 169.46 | 669.05 | 1908.00 | 218.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 577.78 | 194.73 | 383.05 | 1098.03 | 125.95 | 0.00 | 0.00 | 0.00 |
February | 655.20 | 240.23 | 414.97 | 1272.87 | 95.96 | 0.00 | 0.00 | 0.00 |
March | 714.30 | 279.71 | 434.58 | 1421.42 | 62.94 | 0.00 | 0.00 | 0.00 |
April | 721.91 | 275.80 | 446.11 | 1473.16 | 28.64 | 0.00 | 0.00 | 0.00 |
May | 620.54 | 187.84 | 432.71 | 1315.03 | 35.27 | 0.00 | 0.00 | 0.00 |
June | 660.93 | 217.67 | 443.26 | 1383.98 | 38.86 | 0.00 | 0.00 | 0.00 |
July | 564.53 | 126.47 | 438.06 | 1116.22 | 70.29 | 0.00 | 0.00 | 0.00 |
August | 621.27 | 182.63 | 438.64 | 1210.57 | 55.69 | 0.00 | 0.00 | 0.00 |
September | 583.45 | 158.99 | 424.46 | 1165.90 | 56.58 | 0.00 | 0.00 | 0.00 |
October | 546.82 | 139.90 | 406.93 | 1042.82 | 74.75 | 0.00 | 0.00 | 0.00 |
November | 529.21 | 146.25 | 382.97 | 1013.88 | 90.47 | 0.00 | 0.00 | 0.00 |
December | 541.57 | 173.79 | 367.77 | 1024.38 | 140.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 610.96 | 193.22 | 417.75 | 1210.50 | 73.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 529.21 | 126.47 | 367.77 | 1013.88 | 28.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 721.91 | 279.71 | 446.11 | 1473.16 | 140.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1189.99 | 496.48 | 693.51 | 2284.91 | 201.16 | 0.00 | 0.00 | 0.00 |
February | 1010.48 | 329.45 | 681.03 | 2082.50 | 151.55 | 0.00 | 0.00 | 0.00 |
March | 689.60 | 92.61 | 596.98 | 1565.60 | 97.34 | 0.00 | 0.00 | 0.00 |
April | 514.13 | 0.23 | 513.90 | 1217.90 | 41.38 | 0.00 | 0.00 | 0.00 |
May | 514.48 | 0.00 | 514.48 | 1247.08 | 50.50 | 0.00 | 0.00 | 0.00 |
June | 512.63 | 0.00 | 512.63 | 1239.69 | 54.97 | 0.00 | 0.00 | 0.00 |
July | 528.08 | 0.00 | 528.08 | 1115.43 | 103.68 | 0.00 | 0.00 | 0.00 |
August | 514.09 | 0.79 | 513.30 | 1092.35 | 79.07 | 0.00 | 0.00 | 0.00 |
September | 569.14 | 18.59 | 550.55 | 1233.80 | 84.46 | 0.00 | 0.00 | 0.00 |
October | 744.60 | 118.72 | 625.88 | 1491.76 | 116.60 | 0.00 | 0.00 | 0.00 |
November | 968.22 | 295.39 | 672.83 | 1889.78 | 143.60 | 0.00 | 0.00 | 0.00 |
December | 1189.38 | 506.03 | 683.35 | 2250.50 | 225.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 744.37 | 154.26 | 590.11 | 1556.77 | 112.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 512.63 | 0.00 | 512.63 | 1092.35 | 41.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1189.99 | 506.03 | 693.51 | 2284.91 | 225.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 585.42 | 205.85 | 379.57 | 1125.10 | 139.56 | 0.00 | 0.00 | 0.00 |
February | 642.96 | 227.53 | 415.43 | 1262.53 | 107.68 | 0.00 | 0.00 | 0.00 |
March | 720.71 | 284.67 | 436.04 | 1440.49 | 76.28 | 0.00 | 0.00 | 0.00 |
April | 724.27 | 277.41 | 446.87 | 1467.82 | 35.02 | 0.00 | 0.00 | 0.00 |
May | 616.28 | 182.57 | 433.70 | 1298.34 | 36.24 | 0.00 | 0.00 | 0.00 |
June | 667.81 | 230.18 | 437.63 | 1387.07 | 40.35 | 0.00 | 0.00 | 0.00 |
July | 569.35 | 134.26 | 435.08 | 1123.26 | 73.28 | 0.00 | 0.00 | 0.00 |
August | 618.99 | 183.31 | 435.68 | 1199.20 | 57.75 | 0.00 | 0.00 | 0.00 |
September | 579.78 | 160.80 | 418.97 | 1153.41 | 59.79 | 0.00 | 0.00 | 0.00 |
October | 544.52 | 140.37 | 404.16 | 1037.31 | 79.01 | 0.00 | 0.00 | 0.00 |
November | 531.02 | 144.83 | 386.20 | 1020.05 | 95.55 | 0.00 | 0.00 | 0.00 |
December | 543.46 | 177.77 | 365.68 | 1042.99 | 152.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 611.64 | 195.45 | 416.19 | 1212.24 | 79.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 531.02 | 134.26 | 365.68 | 1020.05 | 35.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 724.27 | 284.67 | 446.87 | 1467.82 | 152.47 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120383E+10 | 0.00 | 0.120383E+10 | 0.244568E+10 | 0.514364E+09 |
February | 0.115989E+10 | 0.00 | 0.115989E+10 | 0.246715E+10 | 0.356115E+09 |
March | 0.131794E+10 | 0.00 | 0.131794E+10 | 0.296644E+10 | 0.266265E+09 |
April | 0.138800E+10 | 19670596.96 | 0.136833E+10 | 0.321086E+10 | 0.118983E+09 |
May | 0.183856E+10 | 0.195862E+09 | 0.164270E+10 | 0.424980E+10 | 0.144699E+09 |
June | 0.217342E+10 | 0.439231E+09 | 0.173419E+10 | 0.490641E+10 | 0.161440E+09 |
July | 0.193123E+10 | 0.202428E+09 | 0.172881E+10 | 0.399914E+10 | 0.287529E+09 |
August | 0.159003E+10 | 67800312.32 | 0.152223E+10 | 0.333862E+10 | 0.221410E+09 |
September | 0.131007E+10 | 627332.92 | 0.130944E+10 | 0.282312E+10 | 0.215156E+09 |
October | 0.130438E+10 | 0.00 | 0.130438E+10 | 0.261380E+10 | 0.294462E+09 |
November | 0.119442E+10 | 0.00 | 0.119442E+10 | 0.241389E+10 | 0.340546E+09 |
December | 0.116951E+10 | 0.00 | 0.116951E+10 | 0.235602E+10 | 0.563827E+09 |
Annual Sum or Average | 0.175813E+11 | 0.925619E+09 | 0.166557E+11 | 0.377909E+11 | 0.348479E+10 |
Minimum of Months | 0.115989E+10 | 0.00 | 0.115989E+10 | 0.235602E+10 | 0.118983E+09 |
Maximum of Months | 0.217342E+10 | 0.439231E+09 | 0.173419E+10 | 0.490641E+10 | 0.563827E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.154754E+10 | 0.521563E+09 | 0.102597E+10 | 0.292556E+10 | 0.327419E+09 |
February | 0.158507E+10 | 0.581163E+09 | 0.100391E+10 | 0.306234E+10 | 0.223411E+09 |
March | 0.191317E+10 | 0.749187E+09 | 0.116399E+10 | 0.378336E+10 | 0.163550E+09 |
April | 0.187118E+10 | 0.714868E+09 | 0.115631E+10 | 0.378914E+10 | 73920736.34 |
May | 0.166206E+10 | 0.503101E+09 | 0.115896E+10 | 0.349526E+10 | 93437143.59 |
June | 0.171313E+10 | 0.564213E+09 | 0.114892E+10 | 0.356055E+10 | 0.101944E+09 |
July | 0.151203E+10 | 0.338730E+09 | 0.117330E+10 | 0.296716E+10 | 0.185799E+09 |
August | 0.166401E+10 | 0.489148E+09 | 0.117486E+10 | 0.322402E+10 | 0.146041E+09 |
September | 0.151230E+10 | 0.412107E+09 | 0.110019E+10 | 0.300124E+10 | 0.144548E+09 |
October | 0.146461E+10 | 0.374698E+09 | 0.108991E+10 | 0.277505E+10 | 0.197104E+09 |
November | 0.137172E+10 | 0.379069E+09 | 0.992654E+09 | 0.261209E+10 | 0.227061E+09 |
December | 0.145053E+10 | 0.465487E+09 | 0.985042E+09 | 0.273050E+10 | 0.364768E+09 |
Annual Sum or Average | 0.192674E+11 | 0.609333E+10 | 0.131740E+11 | 0.379263E+11 | 0.224900E+10 |
Minimum of Months | 0.137172E+10 | 0.338730E+09 | 0.985042E+09 | 0.261209E+10 | 73920736.34 |
Maximum of Months | 0.191317E+10 | 0.749187E+09 | 0.117486E+10 | 0.378914E+10 | 0.364768E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.318727E+10 | 0.132976E+10 | 0.185750E+10 | 0.610173E+10 | 0.523064E+09 |
February | 0.244455E+10 | 0.797014E+09 | 0.164754E+10 | 0.501546E+10 | 0.352993E+09 |
March | 0.184702E+10 | 0.248054E+09 | 0.159896E+10 | 0.416163E+10 | 0.252939E+09 |
April | 0.133262E+10 | 598219.61 | 0.133202E+10 | 0.311843E+10 | 0.106724E+09 |
May | 0.137798E+10 | 0.00 | 0.137798E+10 | 0.330306E+10 | 0.133230E+09 |
June | 0.132873E+10 | 0.00 | 0.132873E+10 | 0.317709E+10 | 0.143383E+09 |
July | 0.141442E+10 | 0.00 | 0.141442E+10 | 0.295484E+10 | 0.273380E+09 |
August | 0.137695E+10 | 2128087.11 | 0.137482E+10 | 0.290130E+10 | 0.205880E+09 |
September | 0.147520E+10 | 48180982.48 | 0.142702E+10 | 0.316818E+10 | 0.215466E+09 |
October | 0.199433E+10 | 0.317979E+09 | 0.167635E+10 | 0.396837E+10 | 0.308292E+09 |
November | 0.250962E+10 | 0.765651E+09 | 0.174397E+10 | 0.487563E+10 | 0.361488E+09 |
December | 0.318563E+10 | 0.135535E+10 | 0.183028E+10 | 0.601128E+10 | 0.584352E+09 |
Annual Sum or Average | 0.234743E+11 | 0.486472E+10 | 0.186096E+11 | 0.487570E+11 | 0.346119E+10 |
Minimum of Months | 0.132873E+10 | 0.00 | 0.132873E+10 | 0.290130E+10 | 0.106724E+09 |
Maximum of Months | 0.318727E+10 | 0.135535E+10 | 0.185750E+10 | 0.610173E+10 | 0.584352E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156799E+10 | 0.551354E+09 | 0.101663E+10 | 0.300052E+10 | 0.361533E+09 |
February | 0.155545E+10 | 0.550435E+09 | 0.100501E+10 | 0.303906E+10 | 0.250430E+09 |
March | 0.193035E+10 | 0.762449E+09 | 0.116790E+10 | 0.383749E+10 | 0.199582E+09 |
April | 0.187732E+10 | 0.719039E+09 | 0.115828E+10 | 0.377870E+10 | 90412055.97 |
May | 0.165064E+10 | 0.489006E+09 | 0.116163E+10 | 0.345356E+10 | 94783950.47 |
June | 0.173097E+10 | 0.596624E+09 | 0.113435E+10 | 0.356991E+10 | 0.104227E+09 |
July | 0.152493E+10 | 0.359614E+09 | 0.116532E+10 | 0.298707E+10 | 0.191605E+09 |
August | 0.165791E+10 | 0.490977E+09 | 0.116693E+10 | 0.319445E+10 | 0.149508E+09 |
September | 0.150278E+10 | 0.416805E+09 | 0.108598E+10 | 0.297044E+10 | 0.151353E+09 |
October | 0.145845E+10 | 0.375957E+09 | 0.108250E+10 | 0.276221E+10 | 0.206406E+09 |
November | 0.137641E+10 | 0.375387E+09 | 0.100102E+10 | 0.263063E+10 | 0.238559E+09 |
December | 0.145560E+10 | 0.476152E+09 | 0.979448E+09 | 0.278310E+10 | 0.393279E+09 |
Annual Sum or Average | 0.192888E+11 | 0.616380E+10 | 0.131250E+11 | 0.380071E+11 | 0.243168E+10 |
Minimum of Months | 0.137641E+10 | 0.359614E+09 | 0.979448E+09 | 0.263063E+10 | 90412055.97 |
Maximum of Months | 0.193035E+10 | 0.762449E+09 | 0.116790E+10 | 0.383749E+10 | 0.393279E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.401259E+09 | 0.00 | 0.401259E+09 | 0.820526E+09 | 0.177701E+09 |
February | 0.386610E+09 | 0.00 | 0.386610E+09 | 0.828000E+09 | 0.124978E+09 |
March | 0.439293E+09 | 0.00 | 0.439293E+09 | 0.995753E+09 | 92201321.24 |
April | 0.462646E+09 | 6556555.43 | 0.456089E+09 | 0.107993E+10 | 40299366.77 |
May | 0.612825E+09 | 65284254.04 | 0.547541E+09 | 0.142478E+10 | 52836215.51 |
June | 0.724439E+09 | 0.146403E+09 | 0.578036E+09 | 0.164180E+10 | 59192857.38 |
July | 0.643714E+09 | 67472734.67 | 0.576241E+09 | 0.134015E+10 | 0.105025E+09 |
August | 0.529986E+09 | 22599034.85 | 0.507387E+09 | 0.111461E+10 | 83034433.40 |
September | 0.436670E+09 | 209101.08 | 0.436461E+09 | 0.944791E+09 | 78124621.30 |
October | 0.434774E+09 | 0.00 | 0.434774E+09 | 0.877503E+09 | 0.101979E+09 |
November | 0.398121E+09 | 0.00 | 0.398121E+09 | 0.809736E+09 | 0.120377E+09 |
December | 0.389817E+09 | 0.00 | 0.389817E+09 | 0.789135E+09 | 0.198717E+09 |
Annual Sum or Average | 0.586015E+10 | 0.308525E+09 | 0.555163E+10 | 0.126667E+11 | 0.123446E+10 |
Minimum of Months | 0.386610E+09 | 0.00 | 0.386610E+09 | 0.789135E+09 | 40299366.77 |
Maximum of Months | 0.724439E+09 | 0.146403E+09 | 0.578036E+09 | 0.164180E+10 | 0.198717E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.401284E+09 | 0.00 | 0.401284E+09 | 0.820578E+09 | 0.177712E+09 |
February | 0.386635E+09 | 0.00 | 0.386635E+09 | 0.828052E+09 | 0.124986E+09 |
March | 0.439320E+09 | 0.00 | 0.439320E+09 | 0.995816E+09 | 92207148.21 |
April | 0.462675E+09 | 6556969.80 | 0.456118E+09 | 0.108000E+10 | 40301913.62 |
May | 0.612864E+09 | 65288379.90 | 0.547575E+09 | 0.142487E+10 | 52839554.67 |
June | 0.724485E+09 | 0.146413E+09 | 0.578072E+09 | 0.164191E+10 | 59196598.27 |
July | 0.643755E+09 | 67476998.84 | 0.576278E+09 | 0.134024E+10 | 0.105031E+09 |
August | 0.530020E+09 | 22600463.07 | 0.507419E+09 | 0.111468E+10 | 83039681.04 |
September | 0.436697E+09 | 209114.29 | 0.436488E+09 | 0.944851E+09 | 78129558.64 |
October | 0.434801E+09 | 0.00 | 0.434801E+09 | 0.877559E+09 | 0.101985E+09 |
November | 0.398146E+09 | 0.00 | 0.398146E+09 | 0.809787E+09 | 0.120384E+09 |
December | 0.389842E+09 | 0.00 | 0.389842E+09 | 0.789185E+09 | 0.198730E+09 |
Annual Sum or Average | 0.586052E+10 | 0.308545E+09 | 0.555198E+10 | 0.126675E+11 | 0.123454E+10 |
Minimum of Months | 0.386635E+09 | 0.00 | 0.386635E+09 | 0.789185E+09 | 40301913.62 |
Maximum of Months | 0.724485E+09 | 0.146413E+09 | 0.578072E+09 | 0.164191E+10 | 0.198730E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.401284E+09 | 0.00 | 0.401284E+09 | 0.820578E+09 | 0.177712E+09 |
February | 0.386635E+09 | 0.00 | 0.386635E+09 | 0.828052E+09 | 0.124986E+09 |
March | 0.439320E+09 | 0.00 | 0.439320E+09 | 0.995816E+09 | 92207148.21 |
April | 0.462675E+09 | 6556969.80 | 0.456118E+09 | 0.108000E+10 | 40301913.62 |
May | 0.612864E+09 | 65288379.90 | 0.547575E+09 | 0.142487E+10 | 52839554.67 |
June | 0.724485E+09 | 0.146413E+09 | 0.578072E+09 | 0.164191E+10 | 59196598.27 |
July | 0.643755E+09 | 67476998.84 | 0.576278E+09 | 0.134024E+10 | 0.105031E+09 |
August | 0.530020E+09 | 22600463.07 | 0.507419E+09 | 0.111468E+10 | 83039681.04 |
September | 0.436697E+09 | 209114.29 | 0.436488E+09 | 0.944851E+09 | 78129558.64 |
October | 0.434801E+09 | 0.00 | 0.434801E+09 | 0.877559E+09 | 0.101985E+09 |
November | 0.398146E+09 | 0.00 | 0.398146E+09 | 0.809787E+09 | 0.120384E+09 |
December | 0.389842E+09 | 0.00 | 0.389842E+09 | 0.789185E+09 | 0.198730E+09 |
Annual Sum or Average | 0.586052E+10 | 0.308545E+09 | 0.555198E+10 | 0.126675E+11 | 0.123454E+10 |
Minimum of Months | 0.386635E+09 | 0.00 | 0.386635E+09 | 0.789185E+09 | 40301913.62 |
Maximum of Months | 0.724485E+09 | 0.146413E+09 | 0.578072E+09 | 0.164191E+10 | 0.198730E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148866E+10 | 0.501720E+09 | 0.986945E+09 | 0.282450E+10 | 0.340044E+09 |
February | 0.152477E+10 | 0.559053E+09 | 0.965717E+09 | 0.295661E+10 | 0.240897E+09 |
March | 0.184039E+10 | 0.720684E+09 | 0.111971E+10 | 0.365699E+10 | 0.182978E+09 |
April | 0.180000E+10 | 0.687670E+09 | 0.111233E+10 | 0.366076E+10 | 84534344.27 |
May | 0.159883E+10 | 0.483961E+09 | 0.111487E+10 | 0.337231E+10 | 0.103113E+09 |
June | 0.164796E+10 | 0.542748E+09 | 0.110521E+10 | 0.343517E+10 | 0.111486E+09 |
July | 0.145450E+10 | 0.325843E+09 | 0.112866E+10 | 0.286457E+10 | 0.200443E+09 |
August | 0.160071E+10 | 0.470538E+09 | 0.113017E+10 | 0.310544E+10 | 0.166855E+09 |
September | 0.145477E+10 | 0.396429E+09 | 0.105834E+10 | 0.289414E+10 | 0.161839E+09 |
October | 0.140889E+10 | 0.360443E+09 | 0.104845E+10 | 0.268180E+10 | 0.208433E+09 |
November | 0.131954E+10 | 0.364647E+09 | 0.954892E+09 | 0.252326E+10 | 0.242529E+09 |
December | 0.139535E+10 | 0.447778E+09 | 0.947569E+09 | 0.263518E+10 | 0.383256E+09 |
Annual Sum or Average | 0.185344E+11 | 0.586151E+10 | 0.126729E+11 | 0.366107E+11 | 0.242641E+10 |
Minimum of Months | 0.131954E+10 | 0.325843E+09 | 0.947569E+09 | 0.252326E+10 | 84534344.27 |
Maximum of Months | 0.184039E+10 | 0.720684E+09 | 0.113017E+10 | 0.366076E+10 | 0.383256E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58860454.71 | 19837552.93 | 39022901.78 | 0.111678E+09 | 13445035.78 |
February | 60288043.78 | 22104449.25 | 38183594.54 | 0.116902E+09 | 9524870.24 |
March | 72767423.61 | 28495208.98 | 44272214.64 | 0.144594E+09 | 7234781.76 |
April | 71170252.06 | 27189871.70 | 43980380.37 | 0.144743E+09 | 3342411.86 |
May | 63216390.81 | 19135377.40 | 44081013.40 | 0.133338E+09 | 4076977.21 |
June | 65158853.77 | 21459752.18 | 43699101.59 | 0.135824E+09 | 4408055.92 |
July | 57509798.99 | 12883536.21 | 44626262.78 | 0.113263E+09 | 7925321.53 |
August | 63290600.77 | 18604649.65 | 44685951.12 | 0.122786E+09 | 6597304.11 |
September | 57520325.23 | 15674440.17 | 41845885.06 | 0.114432E+09 | 6398950.54 |
October | 55706316.36 | 14251576.98 | 41454739.38 | 0.106036E+09 | 8241270.86 |
November | 52173399.51 | 14417829.72 | 37755569.79 | 99767377.10 | 9589367.57 |
December | 55170764.99 | 17704721.76 | 37466043.23 | 0.104193E+09 | 15153606.66 |
Annual Sum or Average | 0.732833E+09 | 0.231759E+09 | 0.501074E+09 | 0.144756E+10 | 95937954.03 |
Minimum of Months | 52173399.51 | 12883536.21 | 37466043.23 | 99767377.10 | 3342411.86 |
Maximum of Months | 72767423.61 | 28495208.98 | 44685951.12 | 0.144743E+09 | 15153606.66 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106245E+10 | 0.443268E+09 | 0.619186E+09 | 0.202379E+10 | 0.197716E+09 |
February | 0.814876E+09 | 0.265680E+09 | 0.549196E+09 | 0.166080E+10 | 0.137931E+09 |
March | 0.615689E+09 | 82687478.87 | 0.533002E+09 | 0.138020E+10 | 97238150.73 |
April | 0.444219E+09 | 199413.06 | 0.444019E+09 | 0.103763E+10 | 38783713.17 |
May | 0.459339E+09 | 0.00 | 0.459339E+09 | 0.109692E+10 | 49431421.13 |
June | 0.442922E+09 | 0.00 | 0.442922E+09 | 0.105150E+10 | 51970440.67 |
July | 0.471485E+09 | 0.00 | 0.471485E+09 | 0.986059E+09 | 99704267.88 |
August | 0.458994E+09 | 709385.57 | 0.458285E+09 | 0.961453E+09 | 79193352.01 |
September | 0.491748E+09 | 16060852.81 | 0.475687E+09 | 0.105362E+10 | 80973109.15 |
October | 0.664795E+09 | 0.105996E+09 | 0.558799E+09 | 0.132327E+10 | 0.113046E+09 |
November | 0.836567E+09 | 0.255225E+09 | 0.581341E+09 | 0.161925E+10 | 0.138244E+09 |
December | 0.106191E+10 | 0.451800E+09 | 0.610111E+09 | 0.199690E+10 | 0.221291E+09 |
Annual Sum or Average | 0.782500E+10 | 0.162163E+10 | 0.620337E+10 | 0.161914E+11 | 0.130552E+10 |
Minimum of Months | 0.442922E+09 | 0.00 | 0.442922E+09 | 0.961453E+09 | 38783713.17 |
Maximum of Months | 0.106245E+10 | 0.451800E+09 | 0.619186E+09 | 0.202379E+10 | 0.221291E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106245E+10 | 0.443268E+09 | 0.619186E+09 | 0.202379E+10 | 0.197716E+09 |
February | 0.814876E+09 | 0.265680E+09 | 0.549196E+09 | 0.166080E+10 | 0.137931E+09 |
March | 0.615689E+09 | 82687478.87 | 0.533002E+09 | 0.138020E+10 | 97238150.73 |
April | 0.444219E+09 | 199413.06 | 0.444019E+09 | 0.103763E+10 | 38783713.17 |
May | 0.459339E+09 | 0.00 | 0.459339E+09 | 0.109692E+10 | 49431421.13 |
June | 0.442922E+09 | 0.00 | 0.442922E+09 | 0.105150E+10 | 51970440.67 |
July | 0.471485E+09 | 0.00 | 0.471485E+09 | 0.986059E+09 | 99704267.88 |
August | 0.458994E+09 | 709385.57 | 0.458285E+09 | 0.961453E+09 | 79193352.01 |
September | 0.491748E+09 | 16060852.81 | 0.475687E+09 | 0.105362E+10 | 80973109.15 |
October | 0.664795E+09 | 0.105996E+09 | 0.558799E+09 | 0.132327E+10 | 0.113046E+09 |
November | 0.836567E+09 | 0.255225E+09 | 0.581341E+09 | 0.161925E+10 | 0.138244E+09 |
December | 0.106191E+10 | 0.451800E+09 | 0.610111E+09 | 0.199690E+10 | 0.221291E+09 |
Annual Sum or Average | 0.782500E+10 | 0.162163E+10 | 0.620337E+10 | 0.161914E+11 | 0.130552E+10 |
Minimum of Months | 0.442922E+09 | 0.00 | 0.442922E+09 | 0.961453E+09 | 38783713.17 |
Maximum of Months | 0.106245E+10 | 0.451800E+09 | 0.619186E+09 | 0.202379E+10 | 0.221291E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106239E+10 | 0.443240E+09 | 0.619147E+09 | 0.202366E+10 | 0.197704E+09 |
February | 0.814824E+09 | 0.265663E+09 | 0.549161E+09 | 0.166069E+10 | 0.137922E+09 |
March | 0.615650E+09 | 82682253.49 | 0.532968E+09 | 0.138011E+10 | 97232005.83 |
April | 0.444190E+09 | 199400.46 | 0.443991E+09 | 0.103757E+10 | 38781262.26 |
May | 0.459310E+09 | 0.00 | 0.459310E+09 | 0.109685E+10 | 49428297.34 |
June | 0.442894E+09 | 0.00 | 0.442894E+09 | 0.105144E+10 | 51967156.43 |
July | 0.471455E+09 | 0.00 | 0.471455E+09 | 0.985997E+09 | 99697967.13 |
August | 0.458965E+09 | 709340.74 | 0.458256E+09 | 0.961392E+09 | 79188347.44 |
September | 0.491717E+09 | 16059837.85 | 0.475657E+09 | 0.105356E+10 | 80967992.11 |
October | 0.664753E+09 | 0.105990E+09 | 0.558763E+09 | 0.132319E+10 | 0.113039E+09 |
November | 0.836514E+09 | 0.255209E+09 | 0.581305E+09 | 0.161915E+10 | 0.138236E+09 |
December | 0.106184E+10 | 0.451771E+09 | 0.610073E+09 | 0.199677E+10 | 0.221277E+09 |
Annual Sum or Average | 0.782450E+10 | 0.162152E+10 | 0.620298E+10 | 0.161904E+11 | 0.130544E+10 |
Minimum of Months | 0.442894E+09 | 0.00 | 0.442894E+09 | 0.961392E+09 | 38781262.26 |
Maximum of Months | 0.106239E+10 | 0.451771E+09 | 0.619147E+09 | 0.202366E+10 | 0.221277E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150834E+10 | 0.530378E+09 | 0.977961E+09 | 0.289478E+10 | 0.375331E+09 |
February | 0.149628E+10 | 0.529494E+09 | 0.966781E+09 | 0.293370E+10 | 0.269407E+09 |
March | 0.185691E+10 | 0.733442E+09 | 0.112347E+10 | 0.370647E+10 | 0.217929E+09 |
April | 0.180590E+10 | 0.691683E+09 | 0.111422E+10 | 0.364920E+10 | 0.102374E+09 |
May | 0.158784E+10 | 0.470402E+09 | 0.111744E+10 | 0.333049E+10 | 0.107508E+09 |
June | 0.166512E+10 | 0.573926E+09 | 0.109120E+10 | 0.344284E+10 | 0.117005E+09 |
July | 0.146692E+10 | 0.345932E+09 | 0.112099E+10 | 0.288418E+10 | 0.209707E+09 |
August | 0.159484E+10 | 0.472298E+09 | 0.112254E+10 | 0.307738E+10 | 0.173974E+09 |
September | 0.144561E+10 | 0.400947E+09 | 0.104467E+10 | 0.286397E+10 | 0.170393E+09 |
October | 0.140297E+10 | 0.361654E+09 | 0.104132E+10 | 0.266713E+10 | 0.220528E+09 |
November | 0.132405E+10 | 0.361106E+09 | 0.962940E+09 | 0.253744E+10 | 0.255114E+09 |
December | 0.140023E+10 | 0.458037E+09 | 0.942189E+09 | 0.268236E+10 | 0.414361E+09 |
Annual Sum or Average | 0.185550E+11 | 0.592930E+10 | 0.126257E+11 | 0.366699E+11 | 0.263363E+10 |
Minimum of Months | 0.132405E+10 | 0.345932E+09 | 0.942189E+09 | 0.253744E+10 | 0.102374E+09 |
Maximum of Months | 0.185691E+10 | 0.733442E+09 | 0.112347E+10 | 0.370647E+10 | 0.414361E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59638216.87 | 20970609.69 | 38667607.18 | 0.114457E+09 | 14840222.30 |
February | 59161226.99 | 20935661.30 | 38225565.68 | 0.115995E+09 | 10652079.14 |
March | 73420511.10 | 28999525.64 | 44420985.46 | 0.146550E+09 | 8616684.64 |
April | 71403478.84 | 27348431.25 | 44055047.59 | 0.144286E+09 | 4047773.43 |
May | 62781709.20 | 18599222.66 | 44182486.54 | 0.131684E+09 | 4250745.70 |
June | 65837258.37 | 22692425.22 | 43144833.15 | 0.136127E+09 | 4626278.16 |
July | 58000624.42 | 13677804.31 | 44322820.10 | 0.114038E+09 | 8291615.96 |
August | 63058278.31 | 18674190.21 | 44384088.10 | 0.121676E+09 | 6878754.43 |
September | 57158083.22 | 15853046.26 | 41305036.96 | 0.113239E+09 | 6737165.97 |
October | 55472078.68 | 14299420.67 | 41172658.01 | 0.105456E+09 | 8719468.49 |
November | 52351426.88 | 14277746.46 | 38073680.42 | 0.100328E+09 | 10086951.42 |
December | 55363538.88 | 18110314.41 | 37253224.47 | 0.106058E+09 | 16383420.07 |
Annual Sum or Average | 0.733646E+09 | 0.234438E+09 | 0.499208E+09 | 0.144989E+10 | 0.104131E+09 |
Minimum of Months | 52351426.88 | 13677804.31 | 37253224.47 | 0.100328E+09 | 4047773.43 |
Maximum of Months | 73420511.10 | 28999525.64 | 44420985.46 | 0.146550E+09 | 16383420.07 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120383E+10 | 0.00 | 0.120383E+10 | 0.246594E+10 | 0.532064E+09 |
February | 0.115989E+10 | 0.00 | 0.115989E+10 | 0.248911E+10 | 0.370366E+09 |
March | 0.131794E+10 | 0.00 | 0.131794E+10 | 0.299481E+10 | 0.272885E+09 |
April | 0.138800E+10 | 19670596.96 | 0.136833E+10 | 0.324988E+10 | 0.118417E+09 |
May | 0.183856E+10 | 0.195862E+09 | 0.164270E+10 | 0.428870E+10 | 0.145883E+09 |
June | 0.217342E+10 | 0.439231E+09 | 0.173419E+10 | 0.494554E+10 | 0.159263E+09 |
July | 0.193123E+10 | 0.202428E+09 | 0.172881E+10 | 0.403357E+10 | 0.291067E+09 |
August | 0.159003E+10 | 67800312.32 | 0.152223E+10 | 0.336385E+10 | 0.226193E+09 |
September | 0.131007E+10 | 627332.92 | 0.130944E+10 | 0.285174E+10 | 0.218265E+09 |
October | 0.130438E+10 | 0.00 | 0.130438E+10 | 0.263828E+10 | 0.298940E+09 |
November | 0.119442E+10 | 0.00 | 0.119442E+10 | 0.243483E+10 | 0.352590E+09 |
December | 0.116951E+10 | 0.00 | 0.116951E+10 | 0.237313E+10 | 0.585526E+09 |
Annual Sum or Average | 0.175813E+11 | 0.925619E+09 | 0.166557E+11 | 0.381294E+11 | 0.357146E+10 |
Minimum of Months | 0.115989E+10 | 0.00 | 0.115989E+10 | 0.237313E+10 | 0.118417E+09 |
Maximum of Months | 0.217342E+10 | 0.439231E+09 | 0.173419E+10 | 0.494554E+10 | 0.585526E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.154754E+10 | 0.521563E+09 | 0.102597E+10 | 0.294097E+10 | 0.337348E+09 |
February | 0.158507E+10 | 0.581163E+09 | 0.100391E+10 | 0.307933E+10 | 0.232155E+09 |
March | 0.191317E+10 | 0.749187E+09 | 0.116399E+10 | 0.380714E+10 | 0.168578E+09 |
April | 0.187118E+10 | 0.714868E+09 | 0.115631E+10 | 0.381843E+10 | 74246361.87 |
May | 0.166206E+10 | 0.503101E+09 | 0.115896E+10 | 0.352218E+10 | 94463540.99 |
June | 0.171313E+10 | 0.564213E+09 | 0.114892E+10 | 0.358726E+10 | 0.100724E+09 |
July | 0.151203E+10 | 0.338730E+09 | 0.117330E+10 | 0.298968E+10 | 0.188273E+09 |
August | 0.166401E+10 | 0.489148E+09 | 0.117486E+10 | 0.324238E+10 | 0.149171E+09 |
September | 0.151230E+10 | 0.412107E+09 | 0.110019E+10 | 0.302201E+10 | 0.146664E+09 |
October | 0.146461E+10 | 0.374698E+09 | 0.108991E+10 | 0.279310E+10 | 0.200219E+09 |
November | 0.137172E+10 | 0.379069E+09 | 0.992654E+09 | 0.262799E+10 | 0.234506E+09 |
December | 0.145053E+10 | 0.465487E+09 | 0.985042E+09 | 0.274371E+10 | 0.377246E+09 |
Annual Sum or Average | 0.192674E+11 | 0.609333E+10 | 0.131740E+11 | 0.381742E+11 | 0.230359E+10 |
Minimum of Months | 0.137172E+10 | 0.338730E+09 | 0.985042E+09 | 0.262799E+10 | 74246361.87 |
Maximum of Months | 0.191317E+10 | 0.749187E+09 | 0.117486E+10 | 0.381843E+10 | 0.377246E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.318727E+10 | 0.132976E+10 | 0.185750E+10 | 0.611991E+10 | 0.538795E+09 |
February | 0.244455E+10 | 0.797014E+09 | 0.164754E+10 | 0.503799E+10 | 0.366632E+09 |
March | 0.184702E+10 | 0.248054E+09 | 0.159896E+10 | 0.419331E+10 | 0.260719E+09 |
April | 0.133262E+10 | 598219.61 | 0.133202E+10 | 0.315680E+10 | 0.107252E+09 |
May | 0.137798E+10 | 0.00 | 0.137798E+10 | 0.334018E+10 | 0.135270E+09 |
June | 0.132873E+10 | 0.00 | 0.132873E+10 | 0.321327E+10 | 0.142495E+09 |
July | 0.141442E+10 | 0.00 | 0.141442E+10 | 0.298757E+10 | 0.277685E+09 |
August | 0.137695E+10 | 2128087.11 | 0.137482E+10 | 0.292574E+10 | 0.211783E+09 |
September | 0.147520E+10 | 48180982.48 | 0.142702E+10 | 0.319801E+10 | 0.218914E+09 |
October | 0.199433E+10 | 0.317979E+09 | 0.167635E+10 | 0.399552E+10 | 0.312307E+09 |
November | 0.250962E+10 | 0.765651E+09 | 0.174397E+10 | 0.489831E+10 | 0.372220E+09 |
December | 0.318563E+10 | 0.135535E+10 | 0.183028E+10 | 0.602775E+10 | 0.602796E+09 |
Annual Sum or Average | 0.234743E+11 | 0.486472E+10 | 0.186096E+11 | 0.490944E+11 | 0.354687E+10 |
Minimum of Months | 0.132873E+10 | 0.00 | 0.132873E+10 | 0.292574E+10 | 0.107252E+09 |
Maximum of Months | 0.318727E+10 | 0.135535E+10 | 0.185750E+10 | 0.611991E+10 | 0.602796E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156799E+10 | 0.551354E+09 | 0.101663E+10 | 0.301346E+10 | 0.373790E+09 |
February | 0.155545E+10 | 0.550435E+09 | 0.100501E+10 | 0.305432E+10 | 0.260508E+09 |
March | 0.193035E+10 | 0.762449E+09 | 0.116790E+10 | 0.385820E+10 | 0.204300E+09 |
April | 0.187732E+10 | 0.719039E+09 | 0.115828E+10 | 0.380459E+10 | 90762841.61 |
May | 0.165064E+10 | 0.489006E+09 | 0.116163E+10 | 0.347747E+10 | 97068396.67 |
June | 0.173097E+10 | 0.596624E+09 | 0.113435E+10 | 0.359530E+10 | 0.104595E+09 |
July | 0.152493E+10 | 0.359614E+09 | 0.116532E+10 | 0.300855E+10 | 0.196266E+09 |
August | 0.165791E+10 | 0.490977E+09 | 0.116693E+10 | 0.321195E+10 | 0.154682E+09 |
September | 0.150278E+10 | 0.416805E+09 | 0.108598E+10 | 0.298964E+10 | 0.154978E+09 |
October | 0.145845E+10 | 0.375957E+09 | 0.108250E+10 | 0.277833E+10 | 0.211621E+09 |
November | 0.137641E+10 | 0.375387E+09 | 0.100102E+10 | 0.264396E+10 | 0.247668E+09 |
December | 0.145560E+10 | 0.476152E+09 | 0.979448E+09 | 0.279355E+10 | 0.408372E+09 |
Annual Sum or Average | 0.192888E+11 | 0.616380E+10 | 0.131250E+11 | 0.382293E+11 | 0.250461E+10 |
Minimum of Months | 0.137641E+10 | 0.359614E+09 | 0.979448E+09 | 0.264396E+10 | 90762841.61 |
Maximum of Months | 0.193035E+10 | 0.762449E+09 | 0.116790E+10 | 0.385820E+10 | 0.408372E+09 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 913.11 | 192.04 | 449.46 | 0.00 | 449.46 | 0.00 | 0.00 |
February | 1019.82 | 147.20 | 479.45 | 0.00 | 479.45 | 0.00 | 0.00 |
March | 1107.54 | 99.41 | 492.06 | 0.00 | 492.06 | 0.00 | 0.00 |
April | 1238.76 | 45.90 | 535.49 | 7.59 | 527.91 | 0.00 | 0.00 |
May | 1586.69 | 54.02 | 686.44 | 73.13 | 613.31 | 0.00 | 0.00 |
June | 1892.91 | 62.28 | 838.51 | 169.46 | 669.05 | 0.00 | 0.00 |
July | 1493.11 | 107.35 | 721.04 | 75.58 | 645.46 | 0.00 | 0.00 |
August | 1246.50 | 82.67 | 593.65 | 25.31 | 568.34 | 0.00 | 0.00 |
September | 1089.17 | 83.01 | 505.43 | 0.24 | 505.19 | 0.00 | 0.00 |
October | 975.88 | 109.94 | 487.00 | 0.00 | 487.00 | 0.00 | 0.00 |
November | 931.28 | 131.38 | 460.81 | 0.00 | 460.81 | 0.00 | 0.00 |
December | 879.64 | 210.51 | 436.64 | 0.00 | 436.64 | 0.00 | 0.00 |
Annual Sum or Average | 1198.34 | 110.50 | 557.50 | 29.35 | 528.15 | 0.00 | 0.00 |
Minimum of Months | 879.64 | 45.90 | 436.64 | 0.00 | 436.64 | 0.00 | 0.00 |
Maximum of Months | 1892.91 | 210.51 | 838.51 | 169.46 | 669.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1092.28 | 122.24 | 577.78 | 194.73 | 383.05 | 0.00 | 0.00 |
February | 1265.85 | 92.35 | 655.20 | 240.23 | 414.97 | 0.00 | 0.00 |
March | 1412.54 | 61.06 | 714.30 | 279.71 | 434.58 | 0.00 | 0.00 |
April | 1461.86 | 28.52 | 721.91 | 275.80 | 446.11 | 0.00 | 0.00 |
May | 1304.98 | 34.89 | 620.54 | 187.84 | 432.71 | 0.00 | 0.00 |
June | 1373.67 | 39.33 | 660.93 | 217.67 | 443.26 | 0.00 | 0.00 |
July | 1107.81 | 69.37 | 564.53 | 126.47 | 438.06 | 0.00 | 0.00 |
August | 1203.71 | 54.53 | 621.27 | 182.63 | 438.64 | 0.00 | 0.00 |
September | 1157.88 | 55.77 | 583.45 | 158.99 | 424.46 | 0.00 | 0.00 |
October | 1036.09 | 73.59 | 546.82 | 139.90 | 406.93 | 0.00 | 0.00 |
November | 1007.75 | 87.60 | 529.21 | 146.25 | 382.97 | 0.00 | 0.00 |
December | 1019.45 | 136.19 | 541.57 | 173.79 | 367.77 | 0.00 | 0.00 |
Annual Sum or Average | 1202.63 | 71.32 | 610.96 | 193.22 | 417.75 | 0.00 | 0.00 |
Minimum of Months | 1007.75 | 28.52 | 529.21 | 126.47 | 367.77 | 0.00 | 0.00 |
Maximum of Months | 1461.86 | 136.19 | 721.91 | 279.71 | 446.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2278.13 | 195.29 | 1189.99 | 496.48 | 693.51 | 0.00 | 0.00 |
February | 2073.19 | 145.91 | 1010.48 | 329.45 | 681.03 | 0.00 | 0.00 |
March | 1553.77 | 94.44 | 689.60 | 92.61 | 596.98 | 0.00 | 0.00 |
April | 1203.10 | 41.17 | 514.13 | 0.23 | 513.90 | 0.00 | 0.00 |
May | 1233.22 | 49.74 | 514.48 | 0.00 | 514.48 | 0.00 | 0.00 |
June | 1225.73 | 55.32 | 512.63 | 0.00 | 512.63 | 0.00 | 0.00 |
July | 1103.21 | 102.07 | 528.08 | 0.00 | 528.08 | 0.00 | 0.00 |
August | 1083.22 | 76.87 | 514.09 | 0.79 | 513.30 | 0.00 | 0.00 |
September | 1222.29 | 83.13 | 569.14 | 18.59 | 550.55 | 0.00 | 0.00 |
October | 1481.62 | 115.10 | 744.60 | 118.72 | 625.88 | 0.00 | 0.00 |
November | 1881.03 | 139.46 | 968.22 | 295.39 | 672.83 | 0.00 | 0.00 |
December | 2244.35 | 218.17 | 1189.38 | 506.03 | 683.35 | 0.00 | 0.00 |
Annual Sum or Average | 1546.07 | 109.75 | 744.37 | 154.26 | 590.11 | 0.00 | 0.00 |
Minimum of Months | 1083.22 | 41.17 | 512.63 | 0.00 | 512.63 | 0.00 | 0.00 |
Maximum of Months | 2278.13 | 218.17 | 1189.99 | 506.03 | 693.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1120.26 | 134.98 | 585.42 | 205.85 | 379.57 | 0.00 | 0.00 |
February | 1256.23 | 103.52 | 642.96 | 227.53 | 415.43 | 0.00 | 0.00 |
March | 1432.76 | 74.52 | 720.71 | 284.67 | 436.04 | 0.00 | 0.00 |
April | 1457.83 | 34.88 | 724.27 | 277.41 | 446.87 | 0.00 | 0.00 |
May | 1289.41 | 35.39 | 616.28 | 182.57 | 433.70 | 0.00 | 0.00 |
June | 1377.28 | 40.21 | 667.81 | 230.18 | 437.63 | 0.00 | 0.00 |
July | 1115.24 | 71.54 | 569.35 | 134.26 | 435.08 | 0.00 | 0.00 |
August | 1192.67 | 55.82 | 618.99 | 183.31 | 435.68 | 0.00 | 0.00 |
September | 1146.00 | 58.39 | 579.78 | 160.80 | 418.97 | 0.00 | 0.00 |
October | 1031.29 | 77.06 | 544.52 | 140.37 | 404.16 | 0.00 | 0.00 |
November | 1014.91 | 92.04 | 531.02 | 144.83 | 386.20 | 0.00 | 0.00 |
December | 1039.09 | 146.83 | 543.46 | 177.77 | 365.68 | 0.00 | 0.00 |
Annual Sum or Average | 1205.20 | 77.11 | 611.64 | 195.45 | 416.19 | 0.00 | 0.00 |
Minimum of Months | 1014.91 | 34.88 | 531.02 | 134.26 | 365.68 | 0.00 | 0.00 |
Maximum of Months | 1457.83 | 146.83 | 724.27 | 284.67 | 446.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 919.09 | 199.05 | 449.46 | 0.00 | 449.46 | 0.00 | 0.00 |
February | 1026.83 | 154.99 | 479.45 | 0.00 | 479.45 | 0.00 | 0.00 |
March | 1115.36 | 103.28 | 492.06 | 0.00 | 492.06 | 0.00 | 0.00 |
April | 1249.98 | 46.64 | 535.49 | 7.59 | 527.90 | 0.00 | 0.00 |
May | 1595.93 | 59.18 | 686.44 | 73.13 | 613.31 | 0.00 | 0.00 |
June | 1900.32 | 68.51 | 838.51 | 169.46 | 669.05 | 0.00 | 0.00 |
July | 1501.13 | 117.64 | 721.04 | 75.58 | 645.46 | 0.00 | 0.00 |
August | 1248.49 | 93.01 | 593.65 | 25.31 | 568.33 | 0.00 | 0.00 |
September | 1093.55 | 90.43 | 505.43 | 0.24 | 505.18 | 0.00 | 0.00 |
October | 982.91 | 114.23 | 487.00 | 0.00 | 487.00 | 0.00 | 0.00 |
November | 937.23 | 139.33 | 460.81 | 0.00 | 460.81 | 0.00 | 0.00 |
December | 883.93 | 222.59 | 436.64 | 0.00 | 436.64 | 0.00 | 0.00 |
Annual Sum or Average | 1205.03 | 117.44 | 557.50 | 29.35 | 528.15 | 0.00 | 0.00 |
Minimum of Months | 883.93 | 46.64 | 436.64 | 0.00 | 436.64 | 0.00 | 0.00 |
Maximum of Months | 1900.32 | 222.59 | 838.51 | 169.46 | 669.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1096.24 | 131.98 | 577.78 | 194.73 | 383.05 | 0.00 | 0.00 |
February | 1270.47 | 103.51 | 655.20 | 240.23 | 414.97 | 0.00 | 0.00 |
March | 1419.35 | 71.02 | 714.29 | 279.71 | 434.58 | 0.00 | 0.00 |
April | 1468.17 | 33.90 | 721.90 | 275.79 | 446.11 | 0.00 | 0.00 |
May | 1308.86 | 40.02 | 620.54 | 187.83 | 432.70 | 0.00 | 0.00 |
June | 1377.70 | 44.71 | 660.93 | 217.67 | 443.25 | 0.00 | 0.00 |
July | 1111.80 | 77.80 | 564.52 | 126.47 | 438.06 | 0.00 | 0.00 |
August | 1205.28 | 64.76 | 621.27 | 182.62 | 438.64 | 0.00 | 0.00 |
September | 1160.71 | 64.91 | 583.45 | 158.99 | 424.46 | 0.00 | 0.00 |
October | 1040.86 | 80.90 | 546.82 | 139.89 | 406.92 | 0.00 | 0.00 |
November | 1011.97 | 97.27 | 529.21 | 146.24 | 382.97 | 0.00 | 0.00 |
December | 1022.77 | 148.75 | 541.56 | 173.79 | 367.77 | 0.00 | 0.00 |
Annual Sum or Average | 1206.82 | 79.98 | 610.96 | 193.22 | 417.74 | 0.00 | 0.00 |
Minimum of Months | 1011.97 | 33.90 | 529.21 | 126.47 | 367.77 | 0.00 | 0.00 |
Maximum of Months | 1468.17 | 148.75 | 721.90 | 279.71 | 446.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2266.74 | 221.45 | 1190.00 | 496.48 | 693.52 | 0.00 | 0.00 |
February | 2059.47 | 171.04 | 1010.49 | 329.46 | 681.03 | 0.00 | 0.00 |
March | 1545.89 | 108.91 | 689.60 | 92.61 | 596.99 | 0.00 | 0.00 |
April | 1200.94 | 44.89 | 514.13 | 0.23 | 513.90 | 0.00 | 0.00 |
May | 1228.60 | 55.37 | 514.48 | 0.00 | 514.48 | 0.00 | 0.00 |
June | 1216.99 | 60.15 | 512.63 | 0.00 | 512.63 | 0.00 | 0.00 |
July | 1104.43 | 111.67 | 528.09 | 0.00 | 528.09 | 0.00 | 0.00 |
August | 1076.87 | 88.70 | 514.10 | 0.79 | 513.30 | 0.00 | 0.00 |
September | 1219.45 | 93.72 | 569.14 | 18.59 | 550.55 | 0.00 | 0.00 |
October | 1482.13 | 126.62 | 744.60 | 118.72 | 625.88 | 0.00 | 0.00 |
November | 1874.10 | 160.00 | 968.23 | 295.39 | 672.83 | 0.00 | 0.00 |
December | 2236.62 | 247.86 | 1189.39 | 506.04 | 683.35 | 0.00 | 0.00 |
Annual Sum or Average | 1540.25 | 124.19 | 744.37 | 154.26 | 590.11 | 0.00 | 0.00 |
Minimum of Months | 1076.87 | 44.89 | 512.63 | 0.00 | 512.63 | 0.00 | 0.00 |
Maximum of Months | 2266.74 | 247.86 | 1190.00 | 506.04 | 693.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1123.52 | 145.67 | 585.42 | 205.85 | 379.57 | 0.00 | 0.00 |
February | 1260.62 | 115.77 | 642.95 | 227.53 | 415.43 | 0.00 | 0.00 |
March | 1438.55 | 84.58 | 720.70 | 284.66 | 436.04 | 0.00 | 0.00 |
April | 1463.53 | 41.06 | 724.27 | 277.40 | 446.86 | 0.00 | 0.00 |
May | 1292.63 | 41.73 | 616.27 | 182.57 | 433.70 | 0.00 | 0.00 |
June | 1380.78 | 46.93 | 667.81 | 230.18 | 437.63 | 0.00 | 0.00 |
July | 1119.41 | 81.39 | 569.34 | 134.26 | 435.08 | 0.00 | 0.00 |
August | 1194.39 | 67.52 | 618.99 | 183.31 | 435.68 | 0.00 | 0.00 |
September | 1148.62 | 68.34 | 579.77 | 160.80 | 418.97 | 0.00 | 0.00 |
October | 1035.16 | 85.59 | 544.52 | 140.36 | 404.16 | 0.00 | 0.00 |
November | 1017.66 | 102.32 | 531.02 | 144.82 | 386.19 | 0.00 | 0.00 |
December | 1041.08 | 160.82 | 543.45 | 177.77 | 365.68 | 0.00 | 0.00 |
Annual Sum or Average | 1208.77 | 86.81 | 611.64 | 195.45 | 416.19 | 0.00 | 0.00 |
Minimum of Months | 1017.66 | 41.06 | 531.02 | 134.26 | 365.68 | 0.00 | 0.00 |
Maximum of Months | 1463.53 | 160.82 | 724.27 | 284.66 | 446.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 920.68 | 198.65 | 449.46 | 0.00 | 449.46 | 0.00 | 0.00 |
February | 1028.90 | 153.09 | 479.45 | 0.00 | 479.45 | 0.00 | 0.00 |
March | 1118.13 | 101.88 | 492.06 | 0.00 | 492.06 | 0.00 | 0.00 |
April | 1253.81 | 45.69 | 535.49 | 7.59 | 527.91 | 0.00 | 0.00 |
May | 1601.22 | 54.47 | 686.44 | 73.13 | 613.31 | 0.00 | 0.00 |
June | 1908.00 | 61.44 | 838.51 | 169.46 | 669.05 | 0.00 | 0.00 |
July | 1505.96 | 108.67 | 721.04 | 75.58 | 645.46 | 0.00 | 0.00 |
August | 1255.92 | 84.45 | 593.65 | 25.31 | 568.34 | 0.00 | 0.00 |
September | 1100.21 | 84.21 | 505.43 | 0.24 | 505.19 | 0.00 | 0.00 |
October | 985.02 | 111.61 | 487.00 | 0.00 | 487.00 | 0.00 | 0.00 |
November | 939.36 | 136.03 | 460.81 | 0.00 | 460.81 | 0.00 | 0.00 |
December | 886.03 | 218.61 | 436.64 | 0.00 | 436.64 | 0.00 | 0.00 |
Annual Sum or Average | 1209.07 | 113.25 | 557.50 | 29.35 | 528.15 | 0.00 | 0.00 |
Minimum of Months | 886.03 | 45.69 | 436.64 | 0.00 | 436.64 | 0.00 | 0.00 |
Maximum of Months | 1908.00 | 218.61 | 838.51 | 169.46 | 669.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1098.03 | 125.95 | 577.78 | 194.73 | 383.05 | 0.00 | 0.00 |
February | 1272.87 | 95.96 | 655.20 | 240.23 | 414.97 | 0.00 | 0.00 |
March | 1421.42 | 62.94 | 714.30 | 279.71 | 434.58 | 0.00 | 0.00 |
April | 1473.16 | 28.64 | 721.91 | 275.80 | 446.11 | 0.00 | 0.00 |
May | 1315.03 | 35.27 | 620.54 | 187.84 | 432.71 | 0.00 | 0.00 |
June | 1383.98 | 38.86 | 660.93 | 217.67 | 443.26 | 0.00 | 0.00 |
July | 1116.22 | 70.29 | 564.53 | 126.47 | 438.06 | 0.00 | 0.00 |
August | 1210.57 | 55.69 | 621.27 | 182.63 | 438.64 | 0.00 | 0.00 |
September | 1165.90 | 56.58 | 583.45 | 158.99 | 424.46 | 0.00 | 0.00 |
October | 1042.82 | 74.75 | 546.82 | 139.90 | 406.93 | 0.00 | 0.00 |
November | 1013.88 | 90.47 | 529.21 | 146.25 | 382.97 | 0.00 | 0.00 |
December | 1024.38 | 140.85 | 541.57 | 173.79 | 367.77 | 0.00 | 0.00 |
Annual Sum or Average | 1210.50 | 73.05 | 610.96 | 193.22 | 417.75 | 0.00 | 0.00 |
Minimum of Months | 1013.88 | 28.64 | 529.21 | 126.47 | 367.77 | 0.00 | 0.00 |
Maximum of Months | 1473.16 | 140.85 | 721.91 | 279.71 | 446.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2284.91 | 201.16 | 1189.99 | 496.48 | 693.51 | 0.00 | 0.00 |
February | 2082.50 | 151.55 | 1010.48 | 329.45 | 681.03 | 0.00 | 0.00 |
March | 1565.60 | 97.34 | 689.60 | 92.61 | 596.98 | 0.00 | 0.00 |
April | 1217.90 | 41.38 | 514.13 | 0.23 | 513.90 | 0.00 | 0.00 |
May | 1247.08 | 50.50 | 514.48 | 0.00 | 514.48 | 0.00 | 0.00 |
June | 1239.69 | 54.97 | 512.63 | 0.00 | 512.63 | 0.00 | 0.00 |
July | 1115.43 | 103.68 | 528.08 | 0.00 | 528.08 | 0.00 | 0.00 |
August | 1092.35 | 79.07 | 514.09 | 0.79 | 513.30 | 0.00 | 0.00 |
September | 1233.80 | 84.46 | 569.14 | 18.59 | 550.55 | 0.00 | 0.00 |
October | 1491.76 | 116.60 | 744.60 | 118.72 | 625.88 | 0.00 | 0.00 |
November | 1889.78 | 143.60 | 968.22 | 295.39 | 672.83 | 0.00 | 0.00 |
December | 2250.50 | 225.06 | 1189.38 | 506.03 | 683.35 | 0.00 | 0.00 |
Annual Sum or Average | 1556.77 | 112.47 | 744.37 | 154.26 | 590.11 | 0.00 | 0.00 |
Minimum of Months | 1092.35 | 41.38 | 512.63 | 0.00 | 512.63 | 0.00 | 0.00 |
Maximum of Months | 2284.91 | 225.06 | 1189.99 | 506.03 | 693.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1125.10 | 139.56 | 585.42 | 205.85 | 379.57 | 0.00 | 0.00 |
February | 1262.53 | 107.68 | 642.96 | 227.53 | 415.43 | 0.00 | 0.00 |
March | 1440.49 | 76.28 | 720.71 | 284.67 | 436.04 | 0.00 | 0.00 |
April | 1467.82 | 35.02 | 724.27 | 277.41 | 446.87 | 0.00 | 0.00 |
May | 1298.34 | 36.24 | 616.28 | 182.57 | 433.70 | 0.00 | 0.00 |
June | 1387.07 | 40.35 | 667.81 | 230.18 | 437.63 | 0.00 | 0.00 |
July | 1123.26 | 73.28 | 569.35 | 134.26 | 435.08 | 0.00 | 0.00 |
August | 1199.20 | 57.75 | 618.99 | 183.31 | 435.68 | 0.00 | 0.00 |
September | 1153.41 | 59.79 | 579.78 | 160.80 | 418.97 | 0.00 | 0.00 |
October | 1037.31 | 79.01 | 544.52 | 140.37 | 404.16 | 0.00 | 0.00 |
November | 1020.05 | 95.55 | 531.02 | 144.83 | 386.20 | 0.00 | 0.00 |
December | 1042.99 | 152.47 | 543.46 | 177.77 | 365.68 | 0.00 | 0.00 |
Annual Sum or Average | 1212.24 | 79.42 | 611.64 | 195.45 | 416.19 | 0.00 | 0.00 |
Minimum of Months | 1020.05 | 35.02 | 531.02 | 134.26 | 365.68 | 0.00 | 0.00 |
Maximum of Months | 1467.82 | 152.47 | 724.27 | 284.67 | 446.87 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.244568E+10 | 0.514364E+09 | 0.120383E+10 | 0.00 | 0.120383E+10 | 0.00 | 0.00 |
February | 0.246715E+10 | 0.356115E+09 | 0.115989E+10 | 0.00 | 0.115989E+10 | 0.00 | 0.00 |
March | 0.296644E+10 | 0.266265E+09 | 0.131794E+10 | 0.00 | 0.131794E+10 | 0.00 | 0.00 |
April | 0.321086E+10 | 0.118983E+09 | 0.138800E+10 | 19670596.96 | 0.136833E+10 | 0.00 | 0.00 |
May | 0.424980E+10 | 0.144699E+09 | 0.183856E+10 | 0.195862E+09 | 0.164270E+10 | 0.00 | 0.00 |
June | 0.490641E+10 | 0.161440E+09 | 0.217342E+10 | 0.439231E+09 | 0.173419E+10 | 0.00 | 0.00 |
July | 0.399914E+10 | 0.287529E+09 | 0.193123E+10 | 0.202428E+09 | 0.172881E+10 | 0.00 | 0.00 |
August | 0.333862E+10 | 0.221410E+09 | 0.159003E+10 | 67800312.32 | 0.152223E+10 | 0.00 | 0.00 |
September | 0.282312E+10 | 0.215156E+09 | 0.131007E+10 | 627332.92 | 0.130944E+10 | 0.00 | 0.00 |
October | 0.261380E+10 | 0.294462E+09 | 0.130438E+10 | 0.00 | 0.130438E+10 | 0.00 | 0.00 |
November | 0.241389E+10 | 0.340546E+09 | 0.119442E+10 | 0.00 | 0.119442E+10 | 0.00 | 0.00 |
December | 0.235602E+10 | 0.563827E+09 | 0.116951E+10 | 0.00 | 0.116951E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.377909E+11 | 0.348479E+10 | 0.175813E+11 | 0.925619E+09 | 0.166557E+11 | 0.00 | 0.00 |
Minimum of Months | 0.235602E+10 | 0.118983E+09 | 0.115989E+10 | 0.00 | 0.115989E+10 | 0.00 | 0.00 |
Maximum of Months | 0.490641E+10 | 0.563827E+09 | 0.217342E+10 | 0.439231E+09 | 0.173419E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.292556E+10 | 0.327419E+09 | 0.154754E+10 | 0.521563E+09 | 0.102597E+10 | 0.00 | 0.00 |
February | 0.306234E+10 | 0.223411E+09 | 0.158507E+10 | 0.581163E+09 | 0.100391E+10 | 0.00 | 0.00 |
March | 0.378336E+10 | 0.163550E+09 | 0.191317E+10 | 0.749187E+09 | 0.116399E+10 | 0.00 | 0.00 |
April | 0.378914E+10 | 73920736.34 | 0.187118E+10 | 0.714868E+09 | 0.115631E+10 | 0.00 | 0.00 |
May | 0.349526E+10 | 93437143.59 | 0.166206E+10 | 0.503101E+09 | 0.115896E+10 | 0.00 | 0.00 |
June | 0.356055E+10 | 0.101944E+09 | 0.171313E+10 | 0.564213E+09 | 0.114892E+10 | 0.00 | 0.00 |
July | 0.296716E+10 | 0.185799E+09 | 0.151203E+10 | 0.338730E+09 | 0.117330E+10 | 0.00 | 0.00 |
August | 0.322402E+10 | 0.146041E+09 | 0.166401E+10 | 0.489148E+09 | 0.117486E+10 | 0.00 | 0.00 |
September | 0.300124E+10 | 0.144548E+09 | 0.151230E+10 | 0.412107E+09 | 0.110019E+10 | 0.00 | 0.00 |
October | 0.277505E+10 | 0.197104E+09 | 0.146461E+10 | 0.374698E+09 | 0.108991E+10 | 0.00 | 0.00 |
November | 0.261209E+10 | 0.227061E+09 | 0.137172E+10 | 0.379069E+09 | 0.992654E+09 | 0.00 | 0.00 |
December | 0.273050E+10 | 0.364768E+09 | 0.145053E+10 | 0.465487E+09 | 0.985042E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.379263E+11 | 0.224900E+10 | 0.192674E+11 | 0.609333E+10 | 0.131740E+11 | 0.00 | 0.00 |
Minimum of Months | 0.261209E+10 | 73920736.34 | 0.137172E+10 | 0.338730E+09 | 0.985042E+09 | 0.00 | 0.00 |
Maximum of Months | 0.378914E+10 | 0.364768E+09 | 0.191317E+10 | 0.749187E+09 | 0.117486E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.610173E+10 | 0.523064E+09 | 0.318727E+10 | 0.132976E+10 | 0.185750E+10 | 0.00 | 0.00 |
February | 0.501546E+10 | 0.352993E+09 | 0.244455E+10 | 0.797014E+09 | 0.164754E+10 | 0.00 | 0.00 |
March | 0.416163E+10 | 0.252939E+09 | 0.184702E+10 | 0.248054E+09 | 0.159896E+10 | 0.00 | 0.00 |
April | 0.311843E+10 | 0.106724E+09 | 0.133262E+10 | 598219.61 | 0.133202E+10 | 0.00 | 0.00 |
May | 0.330306E+10 | 0.133230E+09 | 0.137798E+10 | 0.00 | 0.137798E+10 | 0.00 | 0.00 |
June | 0.317709E+10 | 0.143383E+09 | 0.132873E+10 | 0.00 | 0.132873E+10 | 0.00 | 0.00 |
July | 0.295484E+10 | 0.273380E+09 | 0.141442E+10 | 0.00 | 0.141442E+10 | 0.00 | 0.00 |
August | 0.290130E+10 | 0.205880E+09 | 0.137695E+10 | 2128087.11 | 0.137482E+10 | 0.00 | 0.00 |
September | 0.316818E+10 | 0.215466E+09 | 0.147520E+10 | 48180982.48 | 0.142702E+10 | 0.00 | 0.00 |
October | 0.396837E+10 | 0.308292E+09 | 0.199433E+10 | 0.317979E+09 | 0.167635E+10 | 0.00 | 0.00 |
November | 0.487563E+10 | 0.361488E+09 | 0.250962E+10 | 0.765651E+09 | 0.174397E+10 | 0.00 | 0.00 |
December | 0.601128E+10 | 0.584352E+09 | 0.318563E+10 | 0.135535E+10 | 0.183028E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.487570E+11 | 0.346119E+10 | 0.234743E+11 | 0.486472E+10 | 0.186096E+11 | 0.00 | 0.00 |
Minimum of Months | 0.290130E+10 | 0.106724E+09 | 0.132873E+10 | 0.00 | 0.132873E+10 | 0.00 | 0.00 |
Maximum of Months | 0.610173E+10 | 0.584352E+09 | 0.318727E+10 | 0.135535E+10 | 0.185750E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.300052E+10 | 0.361533E+09 | 0.156799E+10 | 0.551354E+09 | 0.101663E+10 | 0.00 | 0.00 |
February | 0.303906E+10 | 0.250430E+09 | 0.155545E+10 | 0.550435E+09 | 0.100501E+10 | 0.00 | 0.00 |
March | 0.383749E+10 | 0.199582E+09 | 0.193035E+10 | 0.762449E+09 | 0.116790E+10 | 0.00 | 0.00 |
April | 0.377870E+10 | 90412055.97 | 0.187732E+10 | 0.719039E+09 | 0.115828E+10 | 0.00 | 0.00 |
May | 0.345356E+10 | 94783950.47 | 0.165064E+10 | 0.489006E+09 | 0.116163E+10 | 0.00 | 0.00 |
June | 0.356991E+10 | 0.104227E+09 | 0.173097E+10 | 0.596624E+09 | 0.113435E+10 | 0.00 | 0.00 |
July | 0.298707E+10 | 0.191605E+09 | 0.152493E+10 | 0.359614E+09 | 0.116532E+10 | 0.00 | 0.00 |
August | 0.319445E+10 | 0.149508E+09 | 0.165791E+10 | 0.490977E+09 | 0.116693E+10 | 0.00 | 0.00 |
September | 0.297044E+10 | 0.151353E+09 | 0.150278E+10 | 0.416805E+09 | 0.108598E+10 | 0.00 | 0.00 |
October | 0.276221E+10 | 0.206406E+09 | 0.145845E+10 | 0.375957E+09 | 0.108250E+10 | 0.00 | 0.00 |
November | 0.263063E+10 | 0.238559E+09 | 0.137641E+10 | 0.375387E+09 | 0.100102E+10 | 0.00 | 0.00 |
December | 0.278310E+10 | 0.393279E+09 | 0.145560E+10 | 0.476152E+09 | 0.979448E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.380071E+11 | 0.243168E+10 | 0.192888E+11 | 0.616380E+10 | 0.131250E+11 | 0.00 | 0.00 |
Minimum of Months | 0.263063E+10 | 90412055.97 | 0.137641E+10 | 0.359614E+09 | 0.979448E+09 | 0.00 | 0.00 |
Maximum of Months | 0.383749E+10 | 0.393279E+09 | 0.193035E+10 | 0.762449E+09 | 0.116790E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.246168E+10 | 0.533125E+09 | 0.120383E+10 | 0.00 | 0.120383E+10 | 0.00 | 0.00 |
February | 0.248410E+10 | 0.374951E+09 | 0.115988E+10 | 0.00 | 0.115988E+10 | 0.00 | 0.00 |
March | 0.298739E+10 | 0.276616E+09 | 0.131793E+10 | 0.00 | 0.131793E+10 | 0.00 | 0.00 |
April | 0.323994E+10 | 0.120903E+09 | 0.138800E+10 | 19670495.03 | 0.136832E+10 | 0.00 | 0.00 |
May | 0.427453E+10 | 0.158515E+09 | 0.183855E+10 | 0.195861E+09 | 0.164269E+10 | 0.00 | 0.00 |
June | 0.492562E+10 | 0.177586E+09 | 0.217341E+10 | 0.439228E+09 | 0.173418E+10 | 0.00 | 0.00 |
July | 0.402063E+10 | 0.315087E+09 | 0.193122E+10 | 0.202427E+09 | 0.172880E+10 | 0.00 | 0.00 |
August | 0.334396E+10 | 0.249114E+09 | 0.159003E+10 | 67799960.99 | 0.152223E+10 | 0.00 | 0.00 |
September | 0.283449E+10 | 0.234384E+09 | 0.131006E+10 | 627329.67 | 0.130944E+10 | 0.00 | 0.00 |
October | 0.263262E+10 | 0.305949E+09 | 0.130438E+10 | 0.00 | 0.130438E+10 | 0.00 | 0.00 |
November | 0.242931E+10 | 0.361145E+09 | 0.119441E+10 | 0.00 | 0.119441E+10 | 0.00 | 0.00 |
December | 0.236751E+10 | 0.596176E+09 | 0.116950E+10 | 0.00 | 0.116950E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.380018E+11 | 0.370355E+10 | 0.175812E+11 | 0.925614E+09 | 0.166556E+11 | 0.00 | 0.00 |
Minimum of Months | 0.236751E+10 | 0.120903E+09 | 0.115988E+10 | 0.00 | 0.115988E+10 | 0.00 | 0.00 |
Maximum of Months | 0.492562E+10 | 0.596176E+09 | 0.217341E+10 | 0.439228E+09 | 0.173418E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.293618E+10 | 0.353489E+09 | 0.154752E+10 | 0.521557E+09 | 0.102597E+10 | 0.00 | 0.00 |
February | 0.307351E+10 | 0.250422E+09 | 0.158506E+10 | 0.581157E+09 | 0.100390E+10 | 0.00 | 0.00 |
March | 0.380159E+10 | 0.190213E+09 | 0.191316E+10 | 0.749180E+09 | 0.116398E+10 | 0.00 | 0.00 |
April | 0.380551E+10 | 87876756.14 | 0.187117E+10 | 0.714860E+09 | 0.115631E+10 | 0.00 | 0.00 |
May | 0.350565E+10 | 0.107190E+09 | 0.166205E+10 | 0.503096E+09 | 0.115895E+10 | 0.00 | 0.00 |
June | 0.357099E+10 | 0.115894E+09 | 0.171312E+10 | 0.564207E+09 | 0.114891E+10 | 0.00 | 0.00 |
July | 0.297784E+10 | 0.208368E+09 | 0.151201E+10 | 0.338726E+09 | 0.117329E+10 | 0.00 | 0.00 |
August | 0.322822E+10 | 0.173452E+09 | 0.166400E+10 | 0.489143E+09 | 0.117486E+10 | 0.00 | 0.00 |
September | 0.300857E+10 | 0.168238E+09 | 0.151229E+10 | 0.412103E+09 | 0.110019E+10 | 0.00 | 0.00 |
October | 0.278783E+10 | 0.216675E+09 | 0.146460E+10 | 0.374694E+09 | 0.108990E+10 | 0.00 | 0.00 |
November | 0.262303E+10 | 0.252118E+09 | 0.137171E+10 | 0.379065E+09 | 0.992648E+09 | 0.00 | 0.00 |
December | 0.273938E+10 | 0.398410E+09 | 0.145052E+10 | 0.465482E+09 | 0.985036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.380583E+11 | 0.252235E+10 | 0.192672E+11 | 0.609327E+10 | 0.131739E+11 | 0.00 | 0.00 |
Minimum of Months | 0.262303E+10 | 87876756.14 | 0.137171E+10 | 0.338726E+09 | 0.985036E+09 | 0.00 | 0.00 |
Maximum of Months | 0.380551E+10 | 0.398410E+09 | 0.191316E+10 | 0.749180E+09 | 0.117486E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.607124E+10 | 0.593136E+09 | 0.318730E+10 | 0.132978E+10 | 0.185752E+10 | 0.00 | 0.00 |
February | 0.498228E+10 | 0.413784E+09 | 0.244458E+10 | 0.797024E+09 | 0.164755E+10 | 0.00 | 0.00 |
March | 0.414051E+10 | 0.291708E+09 | 0.184703E+10 | 0.248057E+09 | 0.159897E+10 | 0.00 | 0.00 |
April | 0.311283E+10 | 0.116349E+09 | 0.133263E+10 | 598226.57 | 0.133203E+10 | 0.00 | 0.00 |
May | 0.329069E+10 | 0.148291E+09 | 0.137799E+10 | 0.00 | 0.137799E+10 | 0.00 | 0.00 |
June | 0.315445E+10 | 0.155908E+09 | 0.132874E+10 | 0.00 | 0.132874E+10 | 0.00 | 0.00 |
July | 0.295812E+10 | 0.299107E+09 | 0.141443E+10 | 0.00 | 0.141443E+10 | 0.00 | 0.00 |
August | 0.288430E+10 | 0.237575E+09 | 0.137695E+10 | 2128111.89 | 0.137483E+10 | 0.00 | 0.00 |
September | 0.316081E+10 | 0.242914E+09 | 0.147521E+10 | 48181543.46 | 0.142703E+10 | 0.00 | 0.00 |
October | 0.396973E+10 | 0.339132E+09 | 0.199434E+10 | 0.317982E+09 | 0.167636E+10 | 0.00 | 0.00 |
November | 0.485766E+10 | 0.414725E+09 | 0.250965E+10 | 0.765660E+09 | 0.174399E+10 | 0.00 | 0.00 |
December | 0.599057E+10 | 0.663858E+09 | 0.318566E+10 | 0.135537E+10 | 0.183029E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.485732E+11 | 0.391649E+10 | 0.234745E+11 | 0.486478E+10 | 0.186097E+11 | 0.00 | 0.00 |
Minimum of Months | 0.288430E+10 | 0.116349E+09 | 0.132874E+10 | 0.00 | 0.132874E+10 | 0.00 | 0.00 |
Maximum of Months | 0.607124E+10 | 0.663858E+09 | 0.318730E+10 | 0.135537E+10 | 0.185752E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.300924E+10 | 0.390171E+09 | 0.156798E+10 | 0.551349E+09 | 0.101663E+10 | 0.00 | 0.00 |
February | 0.304969E+10 | 0.280059E+09 | 0.155544E+10 | 0.550430E+09 | 0.100501E+10 | 0.00 | 0.00 |
March | 0.385302E+10 | 0.226545E+09 | 0.193033E+10 | 0.762441E+09 | 0.116789E+10 | 0.00 | 0.00 |
April | 0.379348E+10 | 0.106422E+09 | 0.187730E+10 | 0.719031E+09 | 0.115827E+10 | 0.00 | 0.00 |
May | 0.346217E+10 | 0.111758E+09 | 0.165062E+10 | 0.489002E+09 | 0.116162E+10 | 0.00 | 0.00 |
June | 0.357897E+10 | 0.121632E+09 | 0.173096E+10 | 0.596618E+09 | 0.113434E+10 | 0.00 | 0.00 |
July | 0.299822E+10 | 0.217999E+09 | 0.152492E+10 | 0.359610E+09 | 0.116531E+10 | 0.00 | 0.00 |
August | 0.319905E+10 | 0.180853E+09 | 0.165790E+10 | 0.490973E+09 | 0.116692E+10 | 0.00 | 0.00 |
September | 0.297721E+10 | 0.177130E+09 | 0.150277E+10 | 0.416800E+09 | 0.108597E+10 | 0.00 | 0.00 |
October | 0.277258E+10 | 0.229248E+09 | 0.145844E+10 | 0.375953E+09 | 0.108249E+10 | 0.00 | 0.00 |
November | 0.263777E+10 | 0.265201E+09 | 0.137640E+10 | 0.375383E+09 | 0.100101E+10 | 0.00 | 0.00 |
December | 0.278842E+10 | 0.430744E+09 | 0.145559E+10 | 0.476147E+09 | 0.979442E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.381198E+11 | 0.273776E+10 | 0.192887E+11 | 0.616374E+10 | 0.131249E+11 | 0.00 | 0.00 |
Minimum of Months | 0.263777E+10 | 0.106422E+09 | 0.137640E+10 | 0.359610E+09 | 0.979442E+09 | 0.00 | 0.00 |
Maximum of Months | 0.385302E+10 | 0.430744E+09 | 0.193033E+10 | 0.762441E+09 | 0.116789E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.246594E+10 | 0.532064E+09 | 0.120383E+10 | 0.00 | 0.120383E+10 | 0.00 | 0.00 |
February | 0.248911E+10 | 0.370366E+09 | 0.115989E+10 | 0.00 | 0.115989E+10 | 0.00 | 0.00 |
March | 0.299481E+10 | 0.272885E+09 | 0.131794E+10 | 0.00 | 0.131794E+10 | 0.00 | 0.00 |
April | 0.324988E+10 | 0.118417E+09 | 0.138800E+10 | 19670596.96 | 0.136833E+10 | 0.00 | 0.00 |
May | 0.428870E+10 | 0.145883E+09 | 0.183856E+10 | 0.195862E+09 | 0.164270E+10 | 0.00 | 0.00 |
June | 0.494554E+10 | 0.159263E+09 | 0.217342E+10 | 0.439231E+09 | 0.173419E+10 | 0.00 | 0.00 |
July | 0.403357E+10 | 0.291067E+09 | 0.193123E+10 | 0.202428E+09 | 0.172881E+10 | 0.00 | 0.00 |
August | 0.336385E+10 | 0.226193E+09 | 0.159003E+10 | 67800312.32 | 0.152223E+10 | 0.00 | 0.00 |
September | 0.285174E+10 | 0.218265E+09 | 0.131007E+10 | 627332.92 | 0.130944E+10 | 0.00 | 0.00 |
October | 0.263828E+10 | 0.298940E+09 | 0.130438E+10 | 0.00 | 0.130438E+10 | 0.00 | 0.00 |
November | 0.243483E+10 | 0.352590E+09 | 0.119442E+10 | 0.00 | 0.119442E+10 | 0.00 | 0.00 |
December | 0.237313E+10 | 0.585526E+09 | 0.116951E+10 | 0.00 | 0.116951E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.381294E+11 | 0.357146E+10 | 0.175813E+11 | 0.925619E+09 | 0.166557E+11 | 0.00 | 0.00 |
Minimum of Months | 0.237313E+10 | 0.118417E+09 | 0.115989E+10 | 0.00 | 0.115989E+10 | 0.00 | 0.00 |
Maximum of Months | 0.494554E+10 | 0.585526E+09 | 0.217342E+10 | 0.439231E+09 | 0.173419E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.294097E+10 | 0.337348E+09 | 0.154754E+10 | 0.521563E+09 | 0.102597E+10 | 0.00 | 0.00 |
February | 0.307933E+10 | 0.232155E+09 | 0.158507E+10 | 0.581163E+09 | 0.100391E+10 | 0.00 | 0.00 |
March | 0.380714E+10 | 0.168578E+09 | 0.191317E+10 | 0.749187E+09 | 0.116399E+10 | 0.00 | 0.00 |
April | 0.381843E+10 | 74246361.87 | 0.187118E+10 | 0.714868E+09 | 0.115631E+10 | 0.00 | 0.00 |
May | 0.352218E+10 | 94463540.99 | 0.166206E+10 | 0.503101E+09 | 0.115896E+10 | 0.00 | 0.00 |
June | 0.358726E+10 | 0.100724E+09 | 0.171313E+10 | 0.564213E+09 | 0.114892E+10 | 0.00 | 0.00 |
July | 0.298968E+10 | 0.188273E+09 | 0.151203E+10 | 0.338730E+09 | 0.117330E+10 | 0.00 | 0.00 |
August | 0.324238E+10 | 0.149171E+09 | 0.166401E+10 | 0.489148E+09 | 0.117486E+10 | 0.00 | 0.00 |
September | 0.302201E+10 | 0.146664E+09 | 0.151230E+10 | 0.412107E+09 | 0.110019E+10 | 0.00 | 0.00 |
October | 0.279310E+10 | 0.200219E+09 | 0.146461E+10 | 0.374698E+09 | 0.108991E+10 | 0.00 | 0.00 |
November | 0.262799E+10 | 0.234506E+09 | 0.137172E+10 | 0.379069E+09 | 0.992654E+09 | 0.00 | 0.00 |
December | 0.274371E+10 | 0.377246E+09 | 0.145053E+10 | 0.465487E+09 | 0.985042E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.381742E+11 | 0.230359E+10 | 0.192674E+11 | 0.609333E+10 | 0.131740E+11 | 0.00 | 0.00 |
Minimum of Months | 0.262799E+10 | 74246361.87 | 0.137172E+10 | 0.338730E+09 | 0.985042E+09 | 0.00 | 0.00 |
Maximum of Months | 0.381843E+10 | 0.377246E+09 | 0.191317E+10 | 0.749187E+09 | 0.117486E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.611991E+10 | 0.538795E+09 | 0.318727E+10 | 0.132976E+10 | 0.185750E+10 | 0.00 | 0.00 |
February | 0.503799E+10 | 0.366632E+09 | 0.244455E+10 | 0.797014E+09 | 0.164754E+10 | 0.00 | 0.00 |
March | 0.419331E+10 | 0.260719E+09 | 0.184702E+10 | 0.248054E+09 | 0.159896E+10 | 0.00 | 0.00 |
April | 0.315680E+10 | 0.107252E+09 | 0.133262E+10 | 598219.61 | 0.133202E+10 | 0.00 | 0.00 |
May | 0.334018E+10 | 0.135270E+09 | 0.137798E+10 | 0.00 | 0.137798E+10 | 0.00 | 0.00 |
June | 0.321327E+10 | 0.142495E+09 | 0.132873E+10 | 0.00 | 0.132873E+10 | 0.00 | 0.00 |
July | 0.298757E+10 | 0.277685E+09 | 0.141442E+10 | 0.00 | 0.141442E+10 | 0.00 | 0.00 |
August | 0.292574E+10 | 0.211783E+09 | 0.137695E+10 | 2128087.11 | 0.137482E+10 | 0.00 | 0.00 |
September | 0.319801E+10 | 0.218914E+09 | 0.147520E+10 | 48180982.48 | 0.142702E+10 | 0.00 | 0.00 |
October | 0.399552E+10 | 0.312307E+09 | 0.199433E+10 | 0.317979E+09 | 0.167635E+10 | 0.00 | 0.00 |
November | 0.489831E+10 | 0.372220E+09 | 0.250962E+10 | 0.765651E+09 | 0.174397E+10 | 0.00 | 0.00 |
December | 0.602775E+10 | 0.602796E+09 | 0.318563E+10 | 0.135535E+10 | 0.183028E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.490944E+11 | 0.354687E+10 | 0.234743E+11 | 0.486472E+10 | 0.186096E+11 | 0.00 | 0.00 |
Minimum of Months | 0.292574E+10 | 0.107252E+09 | 0.132873E+10 | 0.00 | 0.132873E+10 | 0.00 | 0.00 |
Maximum of Months | 0.611991E+10 | 0.602796E+09 | 0.318727E+10 | 0.135535E+10 | 0.185750E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.301346E+10 | 0.373790E+09 | 0.156799E+10 | 0.551354E+09 | 0.101663E+10 | 0.00 | 0.00 |
February | 0.305432E+10 | 0.260508E+09 | 0.155545E+10 | 0.550435E+09 | 0.100501E+10 | 0.00 | 0.00 |
March | 0.385820E+10 | 0.204300E+09 | 0.193035E+10 | 0.762449E+09 | 0.116790E+10 | 0.00 | 0.00 |
April | 0.380459E+10 | 90762841.61 | 0.187732E+10 | 0.719039E+09 | 0.115828E+10 | 0.00 | 0.00 |
May | 0.347747E+10 | 97068396.67 | 0.165064E+10 | 0.489006E+09 | 0.116163E+10 | 0.00 | 0.00 |
June | 0.359530E+10 | 0.104595E+09 | 0.173097E+10 | 0.596624E+09 | 0.113435E+10 | 0.00 | 0.00 |
July | 0.300855E+10 | 0.196266E+09 | 0.152493E+10 | 0.359614E+09 | 0.116532E+10 | 0.00 | 0.00 |
August | 0.321195E+10 | 0.154682E+09 | 0.165791E+10 | 0.490977E+09 | 0.116693E+10 | 0.00 | 0.00 |
September | 0.298964E+10 | 0.154978E+09 | 0.150278E+10 | 0.416805E+09 | 0.108598E+10 | 0.00 | 0.00 |
October | 0.277833E+10 | 0.211621E+09 | 0.145845E+10 | 0.375957E+09 | 0.108250E+10 | 0.00 | 0.00 |
November | 0.264396E+10 | 0.247668E+09 | 0.137641E+10 | 0.375387E+09 | 0.100102E+10 | 0.00 | 0.00 |
December | 0.279355E+10 | 0.408372E+09 | 0.145560E+10 | 0.476152E+09 | 0.979448E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.382293E+11 | 0.250461E+10 | 0.192888E+11 | 0.616380E+10 | 0.131250E+11 | 0.00 | 0.00 |
Minimum of Months | 0.264396E+10 | 90762841.61 | 0.137641E+10 | 0.359614E+09 | 0.979448E+09 | 0.00 | 0.00 |
Maximum of Months | 0.385820E+10 | 0.408372E+09 | 0.193035E+10 | 0.762449E+09 | 0.116790E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.345271E+10 | -0.276652E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -686189588.4 | 58.98 | 0.00 | 0.00 |
February | 0.311823E+10 | -0.249831E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -619916864.8 | 58.98 | 0.00 | 0.00 |
March | 0.359936E+10 | -0.291085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688508589.3 | 58.98 | 0.00 | 0.00 |
April | 0.322827E+10 | -0.256258E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -665694242.9 | 58.98 | 0.00 | 0.00 |
May | 0.337742E+10 | -0.268890E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688511957.4 | 58.98 | 0.00 | 0.00 |
June | 0.329770E+10 | -0.263163E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666071313.5 | 58.98 | 0.00 | 0.00 |
July | 0.315317E+10 | -0.246652E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -686651397.0 | 58.98 | 0.00 | 0.00 |
August | 0.343499E+10 | -0.274692E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688073686.0 | 58.98 | 0.00 | 0.00 |
September | 0.318080E+10 | -0.251589E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -664909779.5 | 58.98 | 0.00 | 0.00 |
October | 0.334295E+10 | -0.265688E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -686079671.6 | 58.98 | 0.00 | 0.00 |
November | 0.333302E+10 | -0.266913E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -663883240.6 | 58.98 | 0.00 | 0.00 |
December | 0.336645E+10 | -0.267998E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -686470949.9 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.398851E+11 | -0.317941E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.809096E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.311823E+10 | -0.291085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -688511957.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.359936E+10 | -0.246652E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -619916864.8 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.63 | 0.62 | 01-JAN-06:00 | 2178.33 | 24.68 | 147.67 | 322.50 | 1065.06 | 24.70 | 279.50 | 311.50 |
February | 321.17 | 0.64 | 0.62 | 01-FEB-06:49 | 1706.21 | 18.19 | 0.00 | 293.83 | 896.88 | 20.93 | 158.67 | 271.50 |
March | 361.17 | 0.63 | 0.62 | 01-MAR-06:00 | 1282.81 | 17.96 | 0.00 | 326.17 | 713.59 | 20.62 | 115.67 | 298.50 |
April | 358.33 | 0.63 | 0.62 | 01-APR-06:30 | 1049.48 | 17.58 | 0.00 | 320.50 | 595.97 | 20.28 | 6.33 | 284.67 |
May | 376.33 | 0.64 | 0.62 | 01-MAY-06:19 | 900.93 | 16.48 | 0.00 | 328.00 | 500.31 | 19.14 | 0.00 | 278.33 |
June | 370.50 | 0.64 | 0.62 | 01-JUN-06:49 | 876.70 | 16.64 | 0.00 | 320.67 | 503.96 | 19.37 | 0.00 | 273.83 |
July | 383.17 | 0.64 | 0.62 | 01-JUL-06:40 | 854.92 | 16.04 | 0.00 | 325.00 | 462.72 | 18.66 | 0.00 | 272.17 |
August | 369.33 | 0.63 | 0.62 | 01-AUG-06:19 | 1009.07 | 17.01 | 0.00 | 326.17 | 551.00 | 19.66 | 8.17 | 282.67 |
September | 357.83 | 0.64 | 0.62 | 01-SEP-06:19 | 1144.53 | 16.90 | 0.00 | 312.17 | 600.02 | 19.49 | 53.83 | 274.17 |
October | 356.83 | 0.63 | 0.62 | 01-OCT-06:10 | 1487.05 | 18.40 | 15.00 | 323.50 | 752.42 | 20.48 | 116.33 | 283.83 |
November | 337.67 | 0.63 | 0.62 | 01-NOV-06:30 | 1884.23 | 23.04 | 114.67 | 312.50 | 916.53 | 21.49 | 197.17 | 280.33 |
December | 349.33 | 0.63 | 0.62 | 01-DEC-06:40 | 2188.12 | 24.73 | 148.67 | 319.17 | 1065.57 | 24.65 | 273.67 | 303.33 |
Annual Sum or Average | 4292.33 | 0.63 | 1364.33 | 18.90 | 426.00 | 3830.17 | 711.39 | 20.75 | 1209.33 | 3414.83 | ||
Minimum of Months | 321.17 | 0.63 | 0.62 | 854.92 | 16.04 | 0.00 | 293.83 | 462.72 | 18.66 | 0.00 | 271.50 | |
Maximum of Months | 383.17 | 0.64 | 0.62 | 2188.12 | 24.73 | 148.67 | 328.00 | 1065.57 | 24.70 | 279.50 | 311.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.64 | 0.62 | 01-JAN-06:00 | 1797.82 | 19.23 | 87.83 | 305.00 | 959.52 | 22.31 | 77.50 | 270.17 |
February | 321.17 | 0.64 | 0.62 | 01-FEB-06:40 | 1991.19 | 19.16 | 79.33 | 284.17 | 1069.12 | 22.42 | 71.17 | 256.17 |
March | 361.17 | 0.63 | 0.62 | 01-MAR-06:00 | 2320.13 | 21.05 | 111.50 | 320.50 | 946.45 | 21.02 | 52.17 | 291.17 |
April | 358.33 | 0.63 | 0.62 | 01-APR-06:10 | 1894.68 | 19.29 | 84.17 | 325.50 | 987.09 | 20.99 | 54.33 | 293.83 |
May | 376.33 | 0.63 | 0.62 | 01-MAY-05:49 | 1626.43 | 18.53 | 87.33 | 336.17 | 835.48 | 20.24 | 56.83 | 294.50 |
June | 370.50 | 0.63 | 0.62 | 01-JUN-06:19 | 1743.32 | 18.93 | 84.50 | 331.00 | 901.55 | 20.68 | 54.50 | 295.67 |
July | 383.17 | 0.64 | 0.62 | 01-JUL-05:00 | 1451.58 | 18.22 | 86.67 | 333.67 | 735.34 | 19.91 | 56.33 | 288.33 |
August | 369.33 | 0.63 | 0.62 | 01-AUG-05:00 | 1652.97 | 18.88 | 86.00 | 334.17 | 851.30 | 20.55 | 55.00 | 296.17 |
September | 357.83 | 0.64 | 0.62 | 01-SEP-06:10 | 1561.67 | 18.32 | 83.67 | 312.33 | 794.53 | 19.91 | 54.50 | 272.33 |
October | 356.83 | 0.64 | 0.62 | 01-OCT-05:00 | 1560.35 | 18.86 | 86.17 | 314.00 | 791.75 | 20.43 | 55.17 | 272.67 |
November | 337.67 | 0.64 | 0.62 | 01-NOV-06:19 | 1574.22 | 19.51 | 84.50 | 295.33 | 785.79 | 20.80 | 51.50 | 257.00 |
December | 349.33 | 0.64 | 0.62 | 01-DEC-06:30 | 1776.85 | 20.73 | 108.83 | 299.67 | 810.93 | 21.18 | 56.17 | 265.50 |
Annual Sum or Average | 4292.33 | 0.64 | 1742.49 | 19.21 | 1070.50 | 3791.50 | 870.26 | 20.85 | 695.17 | 3353.50 | ||
Minimum of Months | 321.17 | 0.63 | 0.62 | 1451.58 | 18.22 | 79.33 | 284.17 | 735.34 | 19.91 | 51.50 | 256.17 | |
Maximum of Months | 383.17 | 0.64 | 0.62 | 2320.13 | 21.05 | 111.50 | 336.17 | 1069.12 | 22.42 | 77.50 | 296.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.65 | 0.62 | 01-JAN-07:30 | 714.86 | 15.57 | 0.00 | 296.17 | 422.58 | 18.32 | 0.00 | 237.17 |
February | 321.17 | 0.65 | 0.62 | 01-FEB-07:10 | 786.58 | 16.11 | 0.00 | 278.17 | 466.75 | 18.83 | 0.00 | 238.00 |
March | 361.17 | 0.64 | 0.62 | 01-MAR-07:10 | 898.11 | 17.06 | 0.00 | 320.17 | 532.37 | 19.75 | 0.00 | 287.67 |
April | 358.33 | 0.63 | 0.62 | 01-APR-06:19 | 1102.41 | 18.07 | 0.00 | 330.83 | 624.32 | 20.74 | 68.33 | 301.17 |
May | 376.33 | 0.63 | 0.62 | 01-MAY-05:00 | 1290.13 | 17.92 | 3.83 | 348.17 | 674.46 | 20.53 | 113.17 | 315.83 |
June | 370.50 | 0.63 | 0.62 | 01-JUN-06:30 | 1547.31 | 22.49 | 111.67 | 348.00 | 785.12 | 22.43 | 193.83 | 322.00 |
July | 383.17 | 0.63 | 0.62 | 01-JUL-06:19 | 1335.14 | 20.77 | 93.50 | 347.83 | 669.14 | 22.63 | 136.33 | 317.83 |
August | 369.33 | 0.63 | 0.62 | 01-AUG-06:10 | 1195.32 | 17.81 | 0.00 | 341.50 | 639.11 | 20.46 | 87.00 | 306.50 |
September | 357.83 | 0.64 | 0.62 | 01-SEP-06:19 | 969.86 | 16.60 | 0.00 | 313.83 | 523.15 | 19.17 | 1.33 | 272.67 |
October | 356.83 | 0.64 | 0.62 | 01-OCT-06:19 | 856.56 | 16.35 | 0.00 | 310.50 | 469.05 | 18.95 | 0.00 | 258.00 |
November | 337.67 | 0.64 | 0.62 | 01-NOV-06:49 | 764.90 | 15.95 | 0.00 | 286.83 | 430.20 | 18.60 | 0.00 | 230.67 |
December | 349.33 | 0.65 | 0.62 | 01-DEC-06:00 | 696.98 | 15.34 | 0.00 | 289.17 | 406.73 | 18.07 | 0.00 | 229.00 |
Annual Sum or Average | 4292.33 | 0.64 | 1022.52 | 17.57 | 209.00 | 3811.17 | 557.54 | 19.92 | 600.00 | 3316.50 | ||
Minimum of Months | 321.17 | 0.63 | 0.62 | 696.98 | 15.34 | 0.00 | 278.17 | 406.73 | 18.07 | 0.00 | 229.00 | |
Maximum of Months | 383.17 | 0.65 | 0.62 | 1547.31 | 22.49 | 111.67 | 348.17 | 785.12 | 22.63 | 193.83 | 322.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.64 | 0.62 | 01-JAN-07:40 | 1848.12 | 19.21 | 88.17 | 304.17 | 989.59 | 22.39 | 77.67 | 272.17 |
February | 321.17 | 0.64 | 0.62 | 01-FEB-07:19 | 2132.79 | 21.06 | 102.33 | 281.50 | 882.38 | 20.82 | 46.67 | 253.00 |
March | 361.17 | 0.64 | 0.62 | 01-MAR-07:30 | 2368.49 | 20.87 | 112.67 | 328.83 | 964.10 | 20.70 | 51.50 | 294.17 |
April | 358.33 | 0.63 | 0.62 | 01-APR-06:49 | 2305.70 | 14.36 | 0.00 | 325.67 | 952.91 | 18.28 | 0.00 | 293.67 |
May | 376.33 | 0.63 | 0.62 | 01-MAY-06:30 | 1809.92 | 14.12 | 0.00 | 335.67 | 802.95 | 17.79 | 0.00 | 294.17 |
June | 370.50 | 0.63 | 0.62 | 01-JUN-06:00 | 1693.71 | 14.55 | 0.00 | 330.83 | 881.88 | 18.34 | 0.00 | 295.67 |
July | 383.17 | 0.64 | 0.62 | 01-JUL-06:49 | 1451.97 | 13.93 | 0.00 | 334.17 | 735.40 | 17.50 | 0.00 | 290.17 |
August | 369.33 | 0.63 | 0.62 | 01-AUG-06:40 | 1662.37 | 14.73 | 8.50 | 332.17 | 833.85 | 17.98 | 0.00 | 292.50 |
September | 357.83 | 0.64 | 0.62 | 01-SEP-06:40 | 1719.27 | 17.91 | 85.00 | 310.83 | 772.38 | 17.74 | 7.67 | 271.83 |
October | 356.83 | 0.63 | 0.62 | 01-OCT-06:40 | 1615.53 | 18.71 | 87.50 | 313.17 | 835.62 | 21.50 | 70.83 | 275.17 |
November | 337.67 | 0.63 | 0.62 | 01-NOV-06:00 | 1610.65 | 19.26 | 85.00 | 298.17 | 818.82 | 20.91 | 56.67 | 259.67 |
December | 349.33 | 0.64 | 0.62 | 01-DEC-06:00 | 1669.19 | 19.14 | 87.33 | 303.67 | 883.74 | 21.85 | 71.83 | 267.83 |
Annual Sum or Average | 4292.33 | 0.64 | 1820.06 | 17.23 | 656.50 | 3798.83 | 861.65 | 19.60 | 382.83 | 3360.00 | ||
Minimum of Months | 321.17 | 0.63 | 0.62 | 1451.97 | 13.93 | 0.00 | 281.50 | 735.40 | 17.50 | 0.00 | 253.00 | |
Maximum of Months | 383.17 | 0.64 | 0.62 | 2368.49 | 21.06 | 112.67 | 335.67 | 989.59 | 22.39 | 77.67 | 295.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.63 | 0.62 | 01-JAN-07:10 | 2078.20 | 22.35 | 147.67 | 322.00 | 999.68 | 22.52 | 88.83 | 308.67 |
February | 321.17 | 0.64 | 0.62 | 01-FEB-06:49 | 1622.05 | 14.48 | 0.00 | 293.17 | 843.18 | 18.49 | 0.00 | 269.50 |
March | 361.17 | 0.64 | 0.62 | 01-MAR-06:00 | 1223.07 | 14.65 | 0.00 | 325.17 | 678.34 | 18.53 | 0.00 | 294.83 |
April | 358.33 | 0.63 | 0.62 | 01-APR-06:40 | 1003.33 | 14.34 | 0.00 | 318.83 | 570.38 | 18.24 | 0.00 | 279.00 |
May | 376.33 | 0.64 | 0.62 | 01-MAY-06:19 | 862.45 | 12.96 | 0.00 | 325.17 | 479.00 | 16.79 | 0.00 | 274.67 |
June | 370.50 | 0.64 | 0.62 | 01-JUN-06:49 | 838.62 | 13.26 | 0.00 | 317.83 | 483.07 | 17.18 | 0.00 | 268.83 |
July | 383.17 | 0.64 | 0.62 | 01-JUL-06:40 | 819.33 | 12.34 | 0.00 | 322.00 | 442.89 | 16.17 | 0.00 | 265.83 |
August | 369.33 | 0.63 | 0.62 | 01-AUG-06:30 | 965.46 | 13.54 | 0.00 | 325.00 | 526.61 | 17.36 | 0.00 | 278.33 |
September | 357.83 | 0.64 | 0.62 | 01-SEP-06:19 | 1094.19 | 13.31 | 0.00 | 309.50 | 571.18 | 17.06 | 0.00 | 269.50 |
October | 356.83 | 0.63 | 0.62 | 01-OCT-06:10 | 1418.55 | 14.78 | 15.00 | 321.83 | 712.49 | 18.10 | 4.50 | 280.17 |
November | 337.67 | 0.63 | 0.62 | 01-NOV-06:30 | 1795.98 | 20.45 | 114.33 | 310.50 | 868.00 | 20.20 | 39.83 | 280.83 |
December | 349.33 | 0.63 | 0.62 | 01-DEC-06:40 | 2086.76 | 22.41 | 148.50 | 318.17 | 999.57 | 22.42 | 88.17 | 301.67 |
Annual Sum or Average | 4292.33 | 0.64 | 1302.30 | 15.66 | 425.50 | 3809.17 | 674.47 | 18.54 | 221.33 | 3371.83 | ||
Minimum of Months | 321.17 | 0.63 | 0.62 | 819.33 | 12.34 | 0.00 | 293.17 | 442.89 | 16.17 | 0.00 | 265.83 | |
Maximum of Months | 383.17 | 0.64 | 0.62 | 2086.76 | 22.41 | 148.50 | 325.17 | 999.68 | 22.52 | 88.83 | 308.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.64 | 0.62 | 01-JAN-06:00 | 1736.79 | 18.80 | 87.83 | 303.00 | 918.76 | 22.11 | 77.50 | 267.67 |
February | 321.17 | 0.64 | 0.62 | 01-FEB-06:40 | 1931.80 | 18.75 | 79.33 | 282.67 | 1023.72 | 22.23 | 71.17 | 254.17 |
March | 361.17 | 0.64 | 0.62 | 01-MAR-06:00 | 2180.23 | 18.60 | 87.83 | 317.67 | 898.89 | 20.85 | 52.17 | 288.33 |
April | 358.33 | 0.63 | 0.62 | 01-APR-06:10 | 1818.74 | 18.89 | 84.17 | 323.33 | 938.90 | 20.82 | 54.33 | 289.67 |
May | 376.33 | 0.63 | 0.62 | 01-MAY-05:49 | 1581.58 | 18.13 | 87.33 | 332.50 | 795.67 | 20.08 | 56.83 | 291.00 |
June | 370.50 | 0.63 | 0.62 | 01-JUN-06:30 | 1686.22 | 18.54 | 84.50 | 329.33 | 859.08 | 20.53 | 54.50 | 292.50 |
July | 383.17 | 0.64 | 0.62 | 01-JUL-06:10 | 1406.01 | 17.83 | 86.67 | 331.17 | 700.58 | 19.76 | 56.33 | 284.17 |
August | 369.33 | 0.63 | 0.62 | 01-AUG-05:00 | 1598.93 | 18.49 | 86.00 | 332.50 | 810.09 | 20.39 | 55.00 | 291.00 |
September | 357.83 | 0.64 | 0.62 | 01-SEP-06:10 | 1497.09 | 17.92 | 83.67 | 310.50 | 756.05 | 19.73 | 54.50 | 268.17 |
October | 356.83 | 0.64 | 0.62 | 01-OCT-05:00 | 1511.77 | 18.44 | 86.17 | 312.17 | 754.07 | 20.23 | 55.17 | 269.00 |
November | 337.67 | 0.64 | 0.62 | 01-NOV-06:19 | 1512.82 | 18.84 | 81.50 | 293.17 | 748.58 | 20.59 | 51.50 | 253.33 |
December | 349.33 | 0.64 | 0.62 | 01-DEC-06:40 | 1678.64 | 18.52 | 87.83 | 295.67 | 772.78 | 20.96 | 56.17 | 261.67 |
Annual Sum or Average | 4292.33 | 0.64 | 1675.13 | 18.47 | 1022.83 | 3763.67 | 829.33 | 20.67 | 695.17 | 3310.67 | ||
Minimum of Months | 321.17 | 0.63 | 0.62 | 1406.01 | 17.83 | 79.33 | 282.67 | 700.58 | 19.73 | 51.50 | 253.33 | |
Maximum of Months | 383.17 | 0.64 | 0.62 | 2180.23 | 18.89 | 87.83 | 332.50 | 1023.72 | 22.23 | 77.50 | 292.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.65 | 0.62 | 01-JAN-07:30 | 684.11 | 12.25 | 0.00 | 292.50 | 406.08 | 16.17 | 0.00 | 229.33 |
February | 321.17 | 0.65 | 0.62 | 01-FEB-07:10 | 752.89 | 12.88 | 0.00 | 276.50 | 448.64 | 16.78 | 0.00 | 231.83 |
March | 361.17 | 0.64 | 0.62 | 01-MAR-07:19 | 859.11 | 13.93 | 0.00 | 319.33 | 511.30 | 17.82 | 0.00 | 282.17 |
April | 358.33 | 0.63 | 0.62 | 01-APR-06:19 | 1053.61 | 14.81 | 0.00 | 329.17 | 597.18 | 18.75 | 0.00 | 297.00 |
May | 376.33 | 0.63 | 0.62 | 01-MAY-05:00 | 1232.77 | 14.23 | 3.83 | 346.00 | 640.93 | 18.02 | 1.17 | 311.83 |
June | 370.50 | 0.63 | 0.62 | 01-JUN-06:30 | 1478.23 | 19.95 | 111.17 | 347.00 | 743.57 | 20.14 | 33.17 | 317.83 |
July | 383.17 | 0.63 | 0.62 | 01-JUL-06:19 | 1276.91 | 17.94 | 93.00 | 345.67 | 634.79 | 20.36 | 59.33 | 313.33 |
August | 369.33 | 0.63 | 0.62 | 01-AUG-06:10 | 1140.15 | 14.24 | 0.00 | 337.67 | 608.86 | 18.12 | 0.00 | 301.50 |
September | 357.83 | 0.64 | 0.62 | 01-SEP-06:19 | 928.35 | 13.07 | 0.00 | 310.00 | 499.98 | 16.82 | 0.00 | 268.00 |
October | 356.83 | 0.64 | 0.62 | 01-OCT-06:30 | 820.51 | 12.75 | 0.00 | 305.83 | 449.17 | 16.58 | 0.00 | 252.50 |
November | 337.67 | 0.64 | 0.62 | 01-NOV-06:49 | 732.69 | 12.41 | 0.00 | 284.17 | 412.67 | 16.28 | 0.00 | 225.17 |
December | 349.33 | 0.65 | 0.62 | 01-DEC-06:00 | 667.06 | 11.94 | 0.00 | 287.00 | 390.64 | 15.83 | 0.00 | 221.33 |
Annual Sum or Average | 4292.33 | 0.64 | 977.77 | 14.27 | 208.00 | 3780.83 | 532.33 | 17.69 | 93.67 | 3251.83 | ||
Minimum of Months | 321.17 | 0.63 | 0.62 | 667.06 | 11.94 | 0.00 | 276.50 | 390.64 | 15.83 | 0.00 | 221.33 | |
Maximum of Months | 383.17 | 0.65 | 0.62 | 1478.23 | 19.95 | 111.17 | 347.00 | 743.57 | 20.36 | 59.33 | 317.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.64 | 0.62 | 01-JAN-07:40 | 1787.53 | 18.84 | 88.17 | 302.67 | 948.47 | 22.27 | 77.83 | 269.17 |
February | 321.17 | 0.64 | 0.62 | 01-FEB-07:19 | 2071.55 | 20.72 | 102.33 | 279.17 | 838.39 | 20.69 | 46.83 | 250.50 |
March | 361.17 | 0.64 | 0.62 | 01-MAR-07:30 | 2307.05 | 20.51 | 112.67 | 326.00 | 916.34 | 20.55 | 51.50 | 290.17 |
April | 358.33 | 0.63 | 0.62 | 01-APR-06:49 | 2221.76 | 13.87 | 0.00 | 323.50 | 905.75 | 18.08 | 0.00 | 289.83 |
May | 376.33 | 0.64 | 0.62 | 01-MAY-06:40 | 1765.29 | 13.62 | 0.00 | 332.67 | 763.71 | 17.56 | 0.00 | 289.83 |
June | 370.50 | 0.63 | 0.62 | 01-JUN-06:00 | 1641.10 | 14.05 | 0.00 | 328.83 | 839.48 | 18.11 | 0.00 | 291.50 |
July | 383.17 | 0.64 | 0.62 | 01-JUL-06:49 | 1407.66 | 13.42 | 0.00 | 331.67 | 700.30 | 17.26 | 0.00 | 284.83 |
August | 369.33 | 0.63 | 0.62 | 01-AUG-06:49 | 1600.24 | 14.25 | 8.50 | 329.33 | 793.47 | 17.76 | 0.00 | 287.50 |
September | 357.83 | 0.64 | 0.62 | 01-SEP-06:49 | 1624.15 | 17.51 | 85.00 | 307.17 | 734.28 | 17.55 | 7.67 | 268.33 |
October | 356.83 | 0.64 | 0.62 | 01-OCT-06:49 | 1567.45 | 18.33 | 87.50 | 310.50 | 797.90 | 21.36 | 70.83 | 271.00 |
November | 337.67 | 0.64 | 0.62 | 01-NOV-06:00 | 1553.14 | 18.89 | 85.00 | 295.50 | 779.82 | 20.64 | 55.00 | 254.67 |
December | 349.33 | 0.64 | 0.62 | 01-DEC-06:00 | 1612.00 | 18.78 | 87.33 | 301.50 | 825.12 | 20.70 | 59.17 | 262.33 |
Annual Sum or Average | 4292.33 | 0.64 | 1759.49 | 16.80 | 656.50 | 3768.50 | 819.19 | 19.33 | 368.83 | 3309.67 | ||
Minimum of Months | 321.17 | 0.63 | 0.62 | 1407.66 | 13.42 | 0.00 | 279.17 | 700.30 | 17.26 | 0.00 | 250.50 | |
Maximum of Months | 383.17 | 0.64 | 0.62 | 2307.05 | 20.72 | 112.67 | 332.67 | 948.47 | 22.27 | 77.83 | 291.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.63 | 0.62 | 01-JAN-07:10 | 2078.11 | 22.35 | 147.67 | 322.00 | 999.60 | 22.52 | 88.83 | 308.67 |
February | 321.17 | 0.64 | 0.62 | 01-FEB-06:49 | 1621.98 | 14.48 | 0.00 | 293.17 | 843.11 | 18.50 | 0.00 | 269.50 |
March | 361.17 | 0.64 | 0.62 | 01-MAR-06:00 | 1223.02 | 14.65 | 0.00 | 325.17 | 678.29 | 18.53 | 0.00 | 294.83 |
April | 358.33 | 0.63 | 0.62 | 01-APR-06:40 | 1003.30 | 14.35 | 0.00 | 318.83 | 570.34 | 18.24 | 0.00 | 279.00 |
May | 376.33 | 0.64 | 0.62 | 01-MAY-06:19 | 862.42 | 12.96 | 0.00 | 325.17 | 478.96 | 16.79 | 0.00 | 274.67 |
June | 370.50 | 0.64 | 0.62 | 01-JUN-06:49 | 838.59 | 13.26 | 0.00 | 317.83 | 483.04 | 17.18 | 0.00 | 268.83 |
July | 383.17 | 0.64 | 0.62 | 01-JUL-06:40 | 819.29 | 12.34 | 0.00 | 322.00 | 442.85 | 16.17 | 0.00 | 265.83 |
August | 369.33 | 0.63 | 0.62 | 01-AUG-06:30 | 965.42 | 13.54 | 0.00 | 325.00 | 526.57 | 17.36 | 0.00 | 278.33 |
September | 357.83 | 0.64 | 0.62 | 01-SEP-06:19 | 1094.13 | 13.31 | 0.00 | 309.50 | 571.14 | 17.06 | 0.00 | 269.50 |
October | 356.83 | 0.63 | 0.62 | 01-OCT-06:10 | 1418.47 | 14.78 | 15.00 | 321.83 | 712.43 | 18.10 | 4.50 | 280.17 |
November | 337.67 | 0.63 | 0.62 | 01-NOV-06:30 | 1795.89 | 20.45 | 114.33 | 310.50 | 867.92 | 20.20 | 39.83 | 280.83 |
December | 349.33 | 0.63 | 0.62 | 01-DEC-06:40 | 2086.67 | 22.41 | 148.50 | 318.17 | 999.49 | 22.42 | 88.17 | 301.67 |
Annual Sum or Average | 4292.33 | 0.64 | 1302.24 | 15.66 | 425.50 | 3809.17 | 674.42 | 18.54 | 221.33 | 3371.83 | ||
Minimum of Months | 321.17 | 0.63 | 0.62 | 819.29 | 12.34 | 0.00 | 293.17 | 442.85 | 16.17 | 0.00 | 265.83 | |
Maximum of Months | 383.17 | 0.64 | 0.62 | 2086.67 | 22.41 | 148.50 | 325.17 | 999.60 | 22.52 | 88.83 | 308.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.64 | 0.62 | 01-JAN-06:00 | 1736.76 | 18.80 | 87.83 | 303.00 | 918.71 | 22.11 | 77.50 | 267.67 |
February | 321.17 | 0.64 | 0.62 | 01-FEB-06:40 | 1931.77 | 18.75 | 79.33 | 282.67 | 1023.67 | 22.23 | 71.17 | 254.17 |
March | 361.17 | 0.64 | 0.62 | 01-MAR-06:00 | 2180.20 | 18.60 | 87.83 | 317.67 | 898.84 | 20.85 | 52.17 | 288.33 |
April | 358.33 | 0.63 | 0.62 | 01-APR-06:10 | 1818.71 | 18.89 | 84.17 | 323.33 | 938.85 | 20.82 | 54.33 | 289.67 |
May | 376.33 | 0.63 | 0.62 | 01-MAY-05:49 | 1581.53 | 18.13 | 87.33 | 332.50 | 795.61 | 20.08 | 56.83 | 291.00 |
June | 370.50 | 0.63 | 0.62 | 01-JUN-06:30 | 1686.18 | 18.54 | 84.50 | 329.33 | 859.03 | 20.53 | 54.50 | 292.50 |
July | 383.17 | 0.64 | 0.62 | 01-JUL-06:10 | 1405.96 | 17.83 | 86.67 | 331.17 | 700.52 | 19.76 | 56.33 | 284.17 |
August | 369.33 | 0.63 | 0.62 | 01-AUG-05:00 | 1598.88 | 18.49 | 86.00 | 332.50 | 810.03 | 20.39 | 55.00 | 291.00 |
September | 357.83 | 0.64 | 0.62 | 01-SEP-06:10 | 1497.04 | 17.92 | 83.67 | 310.50 | 756.00 | 19.73 | 54.50 | 268.17 |
October | 356.83 | 0.64 | 0.62 | 01-OCT-05:00 | 1511.72 | 18.45 | 86.17 | 312.17 | 754.01 | 20.23 | 55.17 | 269.00 |
November | 337.67 | 0.64 | 0.62 | 01-NOV-06:19 | 1512.78 | 18.84 | 81.50 | 293.17 | 748.52 | 20.59 | 51.50 | 253.33 |
December | 349.33 | 0.64 | 0.62 | 01-DEC-06:40 | 1678.61 | 18.52 | 87.83 | 295.67 | 772.73 | 20.96 | 56.17 | 261.67 |
Annual Sum or Average | 4292.33 | 0.64 | 1675.09 | 18.47 | 1022.83 | 3763.67 | 829.28 | 20.67 | 695.17 | 3310.67 | ||
Minimum of Months | 321.17 | 0.63 | 0.62 | 1405.96 | 17.83 | 79.33 | 282.67 | 700.52 | 19.73 | 51.50 | 253.33 | |
Maximum of Months | 383.17 | 0.64 | 0.62 | 2180.20 | 18.89 | 87.83 | 332.50 | 1023.67 | 22.23 | 77.50 | 292.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.65 | 0.62 | 01-JAN-07:30 | 684.10 | 12.25 | 0.00 | 292.50 | 406.06 | 16.17 | 0.00 | 229.33 |
February | 321.17 | 0.65 | 0.62 | 01-FEB-07:10 | 752.88 | 12.88 | 0.00 | 276.50 | 448.62 | 16.78 | 0.00 | 231.83 |
March | 361.17 | 0.64 | 0.62 | 01-MAR-07:19 | 859.09 | 13.93 | 0.00 | 319.33 | 511.27 | 17.82 | 0.00 | 282.17 |
April | 358.33 | 0.63 | 0.62 | 01-APR-06:19 | 1053.58 | 14.81 | 0.00 | 329.17 | 597.14 | 18.75 | 0.00 | 297.00 |
May | 376.33 | 0.63 | 0.62 | 01-MAY-05:00 | 1232.71 | 14.23 | 3.83 | 346.00 | 640.88 | 18.03 | 1.17 | 311.83 |
June | 370.50 | 0.63 | 0.62 | 01-JUN-06:30 | 1478.17 | 19.95 | 111.17 | 347.00 | 743.51 | 20.14 | 33.17 | 317.83 |
July | 383.17 | 0.63 | 0.62 | 01-JUL-06:19 | 1276.84 | 17.94 | 93.00 | 345.67 | 634.73 | 20.36 | 59.33 | 313.33 |
August | 369.33 | 0.63 | 0.62 | 01-AUG-06:10 | 1140.10 | 14.24 | 0.00 | 337.67 | 608.81 | 18.12 | 0.00 | 301.50 |
September | 357.83 | 0.64 | 0.62 | 01-SEP-06:19 | 928.31 | 13.08 | 0.00 | 310.00 | 499.94 | 16.82 | 0.00 | 268.00 |
October | 356.83 | 0.64 | 0.62 | 01-OCT-06:30 | 820.48 | 12.76 | 0.00 | 305.83 | 449.14 | 16.58 | 0.00 | 252.50 |
November | 337.67 | 0.64 | 0.62 | 01-NOV-06:49 | 732.67 | 12.41 | 0.00 | 284.17 | 412.64 | 16.28 | 0.00 | 225.17 |
December | 349.33 | 0.65 | 0.62 | 01-DEC-06:00 | 667.05 | 11.94 | 0.00 | 287.00 | 390.62 | 15.83 | 0.00 | 221.33 |
Annual Sum or Average | 4292.33 | 0.64 | 977.73 | 14.27 | 208.00 | 3780.83 | 532.29 | 17.69 | 93.67 | 3251.83 | ||
Minimum of Months | 321.17 | 0.63 | 0.62 | 667.05 | 11.94 | 0.00 | 276.50 | 390.62 | 15.83 | 0.00 | 221.33 | |
Maximum of Months | 383.17 | 0.65 | 0.62 | 1478.17 | 19.95 | 111.17 | 347.00 | 743.51 | 20.36 | 59.33 | 317.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.64 | 0.62 | 01-JAN-07:40 | 1787.50 | 18.84 | 88.17 | 302.67 | 948.42 | 22.27 | 77.83 | 269.17 |
February | 321.17 | 0.64 | 0.62 | 01-FEB-07:19 | 2071.52 | 20.72 | 102.33 | 279.17 | 838.34 | 20.69 | 46.83 | 250.50 |
March | 361.17 | 0.64 | 0.62 | 01-MAR-07:30 | 2307.02 | 20.51 | 112.67 | 326.00 | 916.29 | 20.55 | 51.50 | 290.17 |
April | 358.33 | 0.63 | 0.62 | 01-APR-06:49 | 2221.73 | 13.87 | 0.00 | 323.50 | 905.70 | 18.08 | 0.00 | 289.83 |
May | 376.33 | 0.64 | 0.62 | 01-MAY-06:40 | 1765.24 | 13.62 | 0.00 | 332.67 | 763.66 | 17.56 | 0.00 | 289.83 |
June | 370.50 | 0.63 | 0.62 | 01-JUN-06:00 | 1641.07 | 14.05 | 0.00 | 328.83 | 839.42 | 18.11 | 0.00 | 291.50 |
July | 383.17 | 0.64 | 0.62 | 01-JUL-06:49 | 1407.60 | 13.42 | 0.00 | 331.67 | 700.25 | 17.26 | 0.00 | 284.83 |
August | 369.33 | 0.63 | 0.62 | 01-AUG-06:49 | 1600.19 | 14.25 | 8.50 | 329.33 | 793.42 | 17.76 | 0.00 | 287.50 |
September | 357.83 | 0.64 | 0.62 | 01-SEP-06:49 | 1624.10 | 17.51 | 85.00 | 307.17 | 734.23 | 17.55 | 7.67 | 268.33 |
October | 356.83 | 0.64 | 0.62 | 01-OCT-06:49 | 1567.40 | 18.33 | 87.50 | 310.50 | 797.84 | 21.36 | 70.83 | 271.00 |
November | 337.67 | 0.64 | 0.62 | 01-NOV-06:00 | 1553.10 | 18.89 | 85.00 | 295.50 | 779.77 | 20.64 | 55.00 | 254.67 |
December | 349.33 | 0.64 | 0.62 | 01-DEC-06:00 | 1611.97 | 18.78 | 87.33 | 301.50 | 825.07 | 20.70 | 59.17 | 262.33 |
Annual Sum or Average | 4292.33 | 0.64 | 1759.45 | 16.80 | 656.50 | 3768.50 | 819.13 | 19.33 | 368.83 | 3309.67 | ||
Minimum of Months | 321.17 | 0.63 | 0.62 | 1407.60 | 13.42 | 0.00 | 279.17 | 700.25 | 17.26 | 0.00 | 250.50 | |
Maximum of Months | 383.17 | 0.64 | 0.62 | 2307.02 | 20.72 | 112.67 | 332.67 | 948.42 | 22.27 | 77.83 | 291.50 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.100668E+12 | 0.704789E+11 | 134279.56 | 09-JAN-05:02 | 80430.58 | 0.00 |
February | 0.00 | 0.00 | 0.946139E+11 | 0.665834E+11 | 132864.26 | 16-FEB-07:03 | 76901.73 | 0.00 |
March | 0.00 | 0.00 | 0.114996E+12 | 0.791031E+11 | 136855.51 | 28-MAR-04:02 | 74558.41 | 0.00 |
April | 0.00 | 0.00 | 0.119330E+12 | 0.753616E+11 | 138579.06 | 01-APR-04:03 | 68916.53 | 0.00 |
May | 0.00 | 0.00 | 0.137398E+12 | 0.804487E+11 | 140260.34 | 24-MAY-04:03 | 68346.80 | 0.00 |
June | 0.00 | 0.00 | 0.138163E+12 | 0.814718E+11 | 140078.74 | 15-JUN-04:02 | 69223.03 | 0.00 |
July | 0.00 | 0.00 | 0.110969E+12 | 0.713940E+11 | 135609.39 | 21-JUL-04:03 | 74236.37 | 0.00 |
August | 0.00 | 0.00 | 0.129879E+12 | 0.757411E+11 | 139619.33 | 12-AUG-04:03 | 67729.28 | 0.00 |
September | 0.00 | 0.00 | 0.117737E+12 | 0.697278E+11 | 136275.09 | 01-SEP-04:03 | 72104.96 | 0.00 |
October | 0.00 | 0.00 | 0.114404E+12 | 0.682821E+11 | 136607.71 | 05-OCT-04:03 | 73471.48 | 0.00 |
November | 0.00 | 0.00 | 0.107047E+12 | 0.674038E+11 | 134863.40 | 03-NOV-04:03 | 75088.07 | 0.00 |
December | 0.00 | 0.00 | 0.983719E+11 | 0.663840E+11 | 134609.89 | 11-DEC-05:02 | 78934.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.138358E+13 | 0.872380E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.946139E+11 | 0.663840E+11 | 132864.26 | 67729.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.138163E+12 | 0.814718E+11 | 140260.34 | 80430.58 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.851469E+11 | 0.590278E+11 | 117684.46 | 09-JAN-05:02 | 63151.30 | 0.00 |
February | 0.00 | 0.00 | 0.811582E+11 | 0.563845E+11 | 116749.83 | 06-FEB-05:02 | 64754.40 | 0.00 |
March | 0.00 | 0.00 | 0.988847E+11 | 0.676852E+11 | 118727.32 | 28-MAR-04:02 | 60818.60 | 0.00 |
April | 0.00 | 0.00 | 0.104168E+12 | 0.650456E+11 | 119199.82 | 12-APR-04:02 | 59846.76 | 0.00 |
May | 0.00 | 0.00 | 0.119355E+12 | 0.684727E+11 | 120072.15 | 20-MAY-05:03 | 54258.69 | 0.00 |
June | 0.00 | 0.00 | 0.119713E+12 | 0.686390E+11 | 120015.37 | 07-JUN-04:02 | 56087.49 | 0.00 |
July | 0.00 | 0.00 | 0.937491E+11 | 0.588848E+11 | 116576.00 | 28-JUL-05:03 | 61118.21 | 0.00 |
August | 0.00 | 0.00 | 0.110346E+12 | 0.622537E+11 | 120626.06 | 21-AUG-04:02 | 52063.60 | 0.00 |
September | 0.00 | 0.00 | 0.100668E+12 | 0.579371E+11 | 119375.60 | 25-SEP-04:04 | 53968.62 | 0.00 |
October | 0.00 | 0.00 | 0.976308E+11 | 0.566834E+11 | 119980.93 | 23-OCT-04:02 | 57621.56 | 0.00 |
November | 0.00 | 0.00 | 0.905992E+11 | 0.558808E+11 | 115908.14 | 03-NOV-05:03 | 63449.20 | 0.00 |
December | 0.00 | 0.00 | 0.834079E+11 | 0.551312E+11 | 117193.12 | 11-DEC-05:02 | 62928.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.118483E+13 | 0.732026E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.811582E+11 | 0.551312E+11 | 115908.14 | 52063.60 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.119713E+12 | 0.686390E+11 | 120626.06 | 64754.40 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.899425E+11 | 0.638520E+11 | 140213.95 | 09-JAN-05:02 | 73199.83 | 0.00 |
February | 0.00 | 0.00 | 0.865101E+11 | 0.617619E+11 | 136520.94 | 06-FEB-05:02 | 73319.25 | 0.00 |
March | 0.00 | 0.00 | 0.106552E+12 | 0.751871E+11 | 142478.92 | 28-MAR-04:02 | 71020.70 | 0.00 |
April | 0.00 | 0.00 | 0.112466E+12 | 0.728718E+11 | 143228.23 | 12-APR-04:02 | 70686.68 | 0.00 |
May | 0.00 | 0.00 | 0.127233E+12 | 0.759633E+11 | 143913.40 | 20-MAY-05:03 | 63183.69 | 0.00 |
June | 0.00 | 0.00 | 0.127916E+12 | 0.767823E+11 | 144013.08 | 08-JUN-04:02 | 67050.34 | 0.00 |
July | 0.00 | 0.00 | 0.100126E+12 | 0.647078E+11 | 137951.17 | 10-JUL-04:02 | 80288.33 | 0.00 |
August | 0.00 | 0.00 | 0.115862E+12 | 0.676121E+11 | 144577.30 | 21-AUG-04:02 | 55756.91 | 0.00 |
September | 0.00 | 0.00 | 0.106797E+12 | 0.636763E+11 | 142972.67 | 02-SEP-05:03 | 66146.08 | 0.00 |
October | 0.00 | 0.00 | 0.102054E+12 | 0.610536E+11 | 143795.54 | 23-OCT-04:02 | 65349.09 | 0.00 |
November | 0.00 | 0.00 | 0.947222E+11 | 0.602898E+11 | 139925.09 | 13-NOV-05:02 | 75705.98 | 0.00 |
December | 0.00 | 0.00 | 0.872038E+11 | 0.592283E+11 | 128096.03 | 11-DEC-05:02 | 64693.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.125738E+13 | 0.802986E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.865101E+11 | 0.592283E+11 | 128096.03 | 55756.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.127916E+12 | 0.767823E+11 | 144577.30 | 80288.33 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1187.37 | 4021.95 | 12-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1187.48 | 4006.47 | 06-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1244.92 | 3967.73 | 02-MAR-12:06 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1143.19 | 3886.49 | 04-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 1160.65 | 3822.04 | 01-MAY-11:06 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1173.40 | 3737.87 | 05-JUN-11:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1074.21 | 3705.64 | 25-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1183.91 | 3752.51 | 28-AUG-11:13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1125.08 | 3825.80 | 29-SEP-11:06 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1146.45 | 3899.41 | 31-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1185.05 | 3975.74 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1153.89 | 4015.31 | 26-DEC-12:08 |
Annual Sum or Average | 0.00 | 1163.68 | ||||
Minimum of Months | 0.00 | 0.00 | 1074.21 | 3705.64 | ||
Maximum of Months | 0.00 | 0.00 | 1244.92 | 4021.95 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.485026E+10 | 0.51 | 10593.78 | 02-JAN-07:03 | 1.78 |
February | 0.465970E+10 | 0.52 | 10593.78 | 06-FEB-05:02 | 1.78 |
March | 0.580042E+10 | 0.57 | 10593.78 | 06-MAR-07:03 | 1.78 |
April | 0.570218E+10 | 0.57 | 10593.78 | 03-APR-04:02 | 1.78 |
May | 0.610098E+10 | 0.58 | 10593.78 | 01-MAY-06:03 | 1.78 |
June | 0.639215E+10 | 0.61 | 10593.78 | 02-JUN-06:03 | 1.78 |
July | 0.594491E+10 | 0.56 | 10593.78 | 03-JUL-04:02 | 1.78 |
August | 0.632870E+10 | 0.58 | 10593.78 | 01-AUG-06:03 | 1.78 |
September | 0.542935E+10 | 0.55 | 10593.78 | 01-SEP-06:03 | 1.78 |
October | 0.523105E+10 | 0.52 | 10593.78 | 02-OCT-06:03 | 1.78 |
November | 0.480544E+10 | 0.51 | 10593.78 | 06-NOV-05:02 | 1.78 |
December | 0.454377E+10 | 0.48 | 10593.78 | 04-DEC-05:02 | 1.78 |
Annual Sum or Average | 0.657889E+11 | 0.55 | |||
Minimum of Months | 0.454377E+10 | 0.48 | 10593.78 | 1.78 | |
Maximum of Months | 0.639215E+10 | 0.61 | 10593.78 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.433118E+10 | 0.50 | 9051.37 | 09-JAN-05:02 | 1.78 |
February | 0.419643E+10 | 0.53 | 9051.37 | 13-FEB-05:02 | 1.78 |
March | 0.578271E+10 | 0.60 | 9051.37 | 06-MAR-05:02 | 1.78 |
April | 0.600575E+10 | 0.62 | 9051.37 | 03-APR-04:02 | 1.78 |
May | 0.598043E+10 | 0.62 | 9051.37 | 01-MAY-06:03 | 1.78 |
June | 0.577034E+10 | 0.62 | 9051.37 | 02-JUN-05:03 | 1.78 |
July | 0.526888E+10 | 0.56 | 9051.37 | 01-JUL-05:03 | 1.78 |
August | 0.579991E+10 | 0.60 | 9051.37 | 02-AUG-04:02 | 1.77 |
September | 0.517125E+10 | 0.57 | 9051.37 | 05-SEP-06:03 | 1.78 |
October | 0.481457E+10 | 0.53 | 9051.37 | 02-OCT-04:02 | 1.78 |
November | 0.436230E+10 | 0.51 | 9051.37 | 03-NOV-05:03 | 1.78 |
December | 0.399004E+10 | 0.48 | 9051.37 | 04-DEC-05:02 | 1.78 |
Annual Sum or Average | 0.614738E+11 | 0.56 | |||
Minimum of Months | 0.399004E+10 | 0.48 | 9051.37 | 1.77 | |
Maximum of Months | 0.600575E+10 | 0.62 | 9051.37 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.432272E+10 | 0.46 | 9348.21 | 09-JAN-05:02 | 1.62 |
February | 0.426195E+10 | 0.48 | 10693.23 | 21-FEB-05:02 | 1.76 |
March | 0.588117E+10 | 0.55 | 10848.59 | 13-MAR-04:02 | 1.78 |
April | 0.595429E+10 | 0.56 | 10848.59 | 03-APR-04:02 | 1.78 |
May | 0.603143E+10 | 0.56 | 10848.59 | 01-MAY-04:02 | 1.78 |
June | 0.600074E+10 | 0.57 | 10848.59 | 05-JUN-04:02 | 1.78 |
July | 0.512820E+10 | 0.51 | 10848.59 | 03-JUL-04:02 | 1.78 |
August | 0.547714E+10 | 0.53 | 10848.59 | 02-AUG-04:02 | 1.77 |
September | 0.500623E+10 | 0.51 | 10848.59 | 11-SEP-04:02 | 1.78 |
October | 0.465117E+10 | 0.48 | 10848.59 | 16-OCT-04:02 | 1.78 |
November | 0.434658E+10 | 0.47 | 10644.44 | 13-NOV-05:02 | 1.76 |
December | 0.393455E+10 | 0.43 | 8892.50 | 26-DEC-05:02 | 1.57 |
Annual Sum or Average | 0.609962E+11 | 0.51 | |||
Minimum of Months | 0.393455E+10 | 0.43 | 8892.50 | 1.57 | |
Maximum of Months | 0.603143E+10 | 0.57 | 10848.59 | 1.78 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:03 | 0.22 | 0.22 | 57.32 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:03 | 0.22 | 0.22 | 57.52 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:03 | 0.22 | 0.22 | 57.10 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:03 | 0.22 | 0.22 | 57.41 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:03 | 0.22 | 0.22 | 57.20 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 57.23 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 57.46 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 57.15 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 57.42 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 57.58 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:03 | 0.22 | 0.22 | 57.81 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:03 | 0.22 | 0.22 | 57.58 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 57.10 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.81 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.25 | 57.25 | 1187.37 | 4021.95 | 12-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.71 | 57.71 | 1187.48 | 4006.47 | 06-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.29 | 57.29 | 1244.92 | 3967.73 | 02-MAR-12:06 |
April | 0.00 | 0.00 | 01-APR-00:10 | 58.26 | 58.26 | 1143.19 | 3886.49 | 04-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 58.12 | 58.12 | 1160.65 | 3822.04 | 01-MAY-11:06 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.39 | 57.39 | 1173.40 | 3737.87 | 05-JUN-11:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.32 | 58.32 | 1074.21 | 3705.64 | 25-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.31 | 57.31 | 1183.91 | 3752.51 | 28-AUG-11:13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.59 | 57.59 | 1125.08 | 3825.80 | 29-SEP-11:06 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.10 | 57.10 | 1146.45 | 3899.41 | 31-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.01 | 58.01 | 1185.05 | 3975.74 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.78 | 57.78 | 1153.89 | 4015.31 | 26-DEC-12:08 |
Annual Sum or Average | 0.00 | 1163.68 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.10 | 57.10 | 1074.21 | 3705.64 | ||
Maximum of Months | 0.00 | 0.00 | 58.32 | 58.32 | 1244.92 | 4021.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.305602E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.291810E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.359238E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.367763E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.415186E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.421698E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.337886E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.388476E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.349398E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.335345E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.315350E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.293085E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.418084E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.291810E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.421698E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.259652E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.251100E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.314922E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.328683E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.365291E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.365118E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.285870E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.332007E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.301770E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.287711E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.268271E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.248666E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.360906E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.248666E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.365291E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.273744E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.267542E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.337792E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.351018E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.387438E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.389943E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.302073E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.343672E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.316734E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.298454E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.279887E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.259537E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.380783E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.259537E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.389943E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.485026E+10 | 0.100668E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.465970E+10 | 0.946139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.580042E+10 | 0.114996E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.570218E+10 | 0.119330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.610098E+10 | 0.137398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.639215E+10 | 0.138163E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.594491E+10 | 0.110969E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.632870E+10 | 0.129879E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.542935E+10 | 0.117737E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.523105E+10 | 0.114404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.480544E+10 | 0.107047E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.454377E+10 | 0.983719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.657889E+11 | 0.138358E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.454377E+10 | 0.946139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.639215E+10 | 0.138163E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.433118E+10 | 0.851469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.419643E+10 | 0.811582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.578271E+10 | 0.988847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.600575E+10 | 0.104168E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.598043E+10 | 0.119355E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.577034E+10 | 0.119713E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.526888E+10 | 0.937491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.579991E+10 | 0.110346E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.517125E+10 | 0.100668E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.481457E+10 | 0.976308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.436230E+10 | 0.905992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.399004E+10 | 0.834079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.614738E+11 | 0.118483E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.399004E+10 | 0.811582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.600575E+10 | 0.119713E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.432272E+10 | 0.899425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.426195E+10 | 0.865101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.588117E+10 | 0.106552E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.595429E+10 | 0.112466E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.603143E+10 | 0.127233E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.600074E+10 | 0.127916E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.512820E+10 | 0.100126E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.547714E+10 | 0.115862E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.500623E+10 | 0.106797E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.465117E+10 | 0.102054E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.434658E+10 | 0.947222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.393455E+10 | 0.872038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.609962E+11 | 0.125738E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.393455E+10 | 0.865101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.603143E+10 | 0.127916E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.485026E+10 | 0.00 | 0.00 | 0.00 | 0.257100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.465970E+10 | 0.00 | 0.00 | 0.00 | 0.245213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.580042E+10 | 0.00 | 0.00 | 0.00 | 0.301234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.570218E+10 | 0.00 | 0.00 | 0.00 | 0.310741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.610098E+10 | 0.00 | 0.00 | 0.00 | 0.354176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.639215E+10 | 0.00 | 0.00 | 0.00 | 0.357776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.594491E+10 | 0.00 | 0.00 | 0.00 | 0.278437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.632870E+10 | 0.00 | 0.00 | 0.00 | 0.325189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.542935E+10 | 0.00 | 0.00 | 0.00 | 0.295104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.523105E+10 | 0.00 | 0.00 | 0.00 | 0.283035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.480544E+10 | 0.00 | 0.00 | 0.00 | 0.267295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.454377E+10 | 0.00 | 0.00 | 0.00 | 0.247648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.657889E+11 | 0.00 | 0.00 | 0.00 | 0.352295E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.454377E+10 | 0.00 | 0.00 | 0.00 | 0.245213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.639215E+10 | 0.00 | 0.00 | 0.00 | 0.357776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.433118E+10 | 0.00 | 0.00 | 0.00 | 0.216340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.419643E+10 | 0.00 | 0.00 | 0.00 | 0.209136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.578271E+10 | 0.00 | 0.00 | 0.00 | 0.257094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.600575E+10 | 0.00 | 0.00 | 0.00 | 0.268626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.598043E+10 | 0.00 | 0.00 | 0.00 | 0.305486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.577034E+10 | 0.00 | 0.00 | 0.00 | 0.307415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.526888E+10 | 0.00 | 0.00 | 0.00 | 0.233182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.579991E+10 | 0.00 | 0.00 | 0.00 | 0.274008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.517125E+10 | 0.00 | 0.00 | 0.00 | 0.250058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.481457E+10 | 0.00 | 0.00 | 0.00 | 0.239566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.436230E+10 | 0.00 | 0.00 | 0.00 | 0.224648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.399004E+10 | 0.00 | 0.00 | 0.00 | 0.208765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.614738E+11 | 0.00 | 0.00 | 0.00 | 0.299432E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.399004E+10 | 0.00 | 0.00 | 0.00 | 0.208765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.600575E+10 | 0.00 | 0.00 | 0.00 | 0.307415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.432272E+10 | 0.00 | 0.00 | 0.00 | 0.230516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.426195E+10 | 0.00 | 0.00 | 0.00 | 0.224923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.588117E+10 | 0.00 | 0.00 | 0.00 | 0.278980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.595429E+10 | 0.00 | 0.00 | 0.00 | 0.291475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.603143E+10 | 0.00 | 0.00 | 0.00 | 0.327123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.600074E+10 | 0.00 | 0.00 | 0.00 | 0.329936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.512820E+10 | 0.00 | 0.00 | 0.00 | 0.250791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.547714E+10 | 0.00 | 0.00 | 0.00 | 0.288900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.500623E+10 | 0.00 | 0.00 | 0.00 | 0.266672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.465117E+10 | 0.00 | 0.00 | 0.00 | 0.251943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.434658E+10 | 0.00 | 0.00 | 0.00 | 0.236422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.393455E+10 | 0.00 | 0.00 | 0.00 | 0.220192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.609962E+11 | 0.00 | 0.00 | 0.00 | 0.319787E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.393455E+10 | 0.00 | 0.00 | 0.00 | 0.220192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.603143E+10 | 0.00 | 0.00 | 0.00 | 0.329936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 6439153.19 | 0.111663E+11 | 0.00 | 856441.99 | 0.195371E+10 | 0.00 | 17526968.42 | 0.00 | 0.35 |
February | 0.00 | 0.106597E+11 | 0.00 | 79609.79 | 0.198452E+10 | 0.00 | 938647.26 | 0.00 | 0.34 |
March | 0.00 | 0.141652E+11 | 0.00 | 0.00 | 0.209814E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
April | 0.00 | 0.169113E+11 | 0.00 | 0.00 | 0.359282E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
May | 0.00 | 0.210617E+11 | 0.00 | 0.00 | 0.471878E+10 | 0.00 | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.212846E+11 | 0.00 | 0.00 | 0.360572E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.143249E+11 | 0.00 | 0.00 | 0.322458E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
August | 0.00 | 0.208414E+11 | 0.00 | 0.00 | 0.272561E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.180822E+11 | 0.00 | 0.00 | 0.350973E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
October | 0.00 | 0.173941E+11 | 0.00 | 0.00 | 0.306806E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
November | 283179.80 | 0.147955E+11 | 0.00 | 46643.57 | 0.257014E+10 | 0.00 | 95242.25 | 0.00 | 0.34 |
December | 2903834.52 | 0.115264E+11 | 0.00 | 297377.75 | 0.242832E+10 | 0.00 | 2335236.16 | 0.00 | 0.34 |
Annual Sum or Average | 9626167.51 | 0.192213E+12 | 0.00 | 1280073.09 | 0.354801E+11 | 0.00 | 20896094.09 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.106597E+11 | 0.00 | 0.00 | 0.195371E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 6439153.19 | 0.212846E+11 | 0.00 | 856441.99 | 0.471878E+10 | 0.00 | 17526968.42 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 9293266.71 | 0.982026E+10 | 0.00 | 724441.58 | 0.160826E+10 | 0.00 | 20724376.19 | 0.00 | 0.31 |
February | 632729.16 | 0.946749E+10 | 0.00 | 75802.03 | 0.179504E+10 | 0.00 | 1196349.30 | 0.00 | 0.31 |
March | 0.00 | 0.123880E+11 | 0.00 | 0.00 | 0.189654E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
April | 0.00 | 0.151315E+11 | 0.00 | 0.00 | 0.331139E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
May | 0.00 | 0.192531E+11 | 0.00 | 0.00 | 0.425385E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.197399E+11 | 0.00 | 0.00 | 0.323560E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.129344E+11 | 0.00 | 0.00 | 0.283050E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.189186E+11 | 0.00 | 0.00 | 0.257432E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.163261E+11 | 0.00 | 0.00 | 0.329358E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.154852E+11 | 0.00 | 0.00 | 0.292066E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
November | 637693.02 | 0.131799E+11 | 0.00 | 52040.43 | 0.236434E+10 | 0.00 | 158971.67 | 0.00 | 0.31 |
December | 5030217.08 | 0.101546E+11 | 0.00 | 166773.60 | 0.217484E+10 | 0.00 | 882878.87 | 0.00 | 0.31 |
Annual Sum or Average | 15593905.97 | 0.172799E+12 | 0.00 | 1019057.64 | 0.322589E+11 | 0.00 | 22962576.02 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.946749E+10 | 0.00 | 0.00 | 0.160826E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 9293266.71 | 0.197399E+11 | 0.00 | 724441.58 | 0.425385E+10 | 0.00 | 20724376.19 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4347216.78 | 0.923659E+10 | 0.00 | 201919.67 | 0.168140E+10 | 0.00 | 3107943.24 | 0.00 | 0.31 |
February | 47723.59 | 0.890540E+10 | 0.00 | 0.00 | 0.189547E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
March | 0.00 | 0.117265E+11 | 0.00 | 0.00 | 0.200541E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
April | 0.00 | 0.144824E+11 | 0.00 | 0.00 | 0.345586E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
May | 0.00 | 0.185478E+11 | 0.00 | 0.00 | 0.439721E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.189189E+11 | 0.00 | 0.00 | 0.330040E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.123696E+11 | 0.00 | 0.00 | 0.305490E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.181923E+11 | 0.00 | 0.00 | 0.275220E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.157359E+11 | 0.00 | 0.00 | 0.347470E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.148617E+11 | 0.00 | 0.00 | 0.298252E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
November | 0.00 | 0.124847E+11 | 0.00 | 0.00 | 0.240596E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
December | 39045.04 | 0.960790E+10 | 0.00 | 26660.79 | 0.218715E+10 | 0.00 | 5297.14 | 0.00 | 0.30 |
Annual Sum or Average | 4433985.41 | 0.165070E+12 | 0.00 | 228580.46 | 0.335932E+11 | 0.00 | 3113240.38 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.890540E+10 | 0.00 | 0.00 | 0.168140E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 4347216.78 | 0.189189E+11 | 0.00 | 201919.67 | 0.439721E+10 | 0.00 | 3107943.24 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1241360.59 | 0.281298E+10 | 0.00 | 19236.48 | 0.313450E+09 | 0.00 | 210888.91 | 0.00 | 0.40 |
February | 10071.36 | 0.290801E+10 | 0.00 | 0.00 | 0.285936E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
March | 0.00 | 0.386923E+10 | 0.00 | 0.00 | 0.310315E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
April | 0.00 | 0.520947E+10 | 0.00 | 0.00 | 0.454675E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
May | 0.00 | 0.729798E+10 | 0.00 | 0.00 | 0.507262E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
June | 0.00 | 0.798066E+10 | 0.00 | 0.00 | 0.325176E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.477410E+10 | 0.00 | 0.00 | 0.384954E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.630095E+10 | 0.00 | 0.00 | 0.415355E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.528637E+10 | 0.00 | 0.00 | 0.549618E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.00 | 0.470976E+10 | 0.00 | 0.00 | 0.462922E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
November | 0.00 | 0.387209E+10 | 0.00 | 0.00 | 0.388219E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
December | 12083.74 | 0.291453E+10 | 0.00 | 0.00 | 0.410152E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 1263515.69 | 0.579361E+11 | 0.00 | 19236.48 | 0.480803E+10 | 0.00 | 210888.91 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.281298E+10 | 0.00 | 0.00 | 0.285936E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 1241360.59 | 0.798066E+10 | 0.00 | 19236.48 | 0.549618E+09 | 0.00 | 210888.91 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 972953.70 | 0.230045E+10 | 0.00 | 25485.19 | 0.195919E+09 | 0.00 | 278682.62 | 0.00 | 0.52 |
February | 0.00 | 0.242756E+10 | 0.00 | 1073.67 | 0.157986E+09 | 0.00 | 6997.07 | 0.00 | 0.55 |
March | 0.00 | 0.326860E+10 | 0.00 | 0.00 | 0.214434E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.00 | 0.433032E+10 | 0.00 | 0.00 | 0.328411E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
May | 0.00 | 0.518176E+10 | 0.00 | 0.00 | 0.432079E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.534864E+10 | 0.00 | 0.00 | 0.324406E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.325728E+10 | 0.00 | 0.00 | 0.326798E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.478717E+10 | 0.00 | 0.00 | 0.314994E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.423306E+10 | 0.00 | 0.00 | 0.370821E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
October | 0.00 | 0.372391E+10 | 0.00 | 0.00 | 0.327201E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
November | 0.00 | 0.306246E+10 | 0.00 | 0.00 | 0.226848E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
December | 9683.37 | 0.239625E+10 | 0.00 | 0.00 | 0.240285E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 982637.07 | 0.443175E+11 | 0.00 | 26558.86 | 0.346018E+10 | 0.00 | 285679.70 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.230045E+10 | 0.00 | 0.00 | 0.157986E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 972953.70 | 0.534864E+10 | 0.00 | 25485.19 | 0.432079E+09 | 0.00 | 278682.62 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1235207.12 | 0.419785E+10 | 0.00 | 35427.21 | 0.181114E+09 | 0.00 | 351918.53 | 0.00 | 0.56 |
February | 10083.51 | 0.399396E+10 | 0.00 | 0.00 | 0.197306E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
March | 0.00 | 0.444777E+10 | 0.00 | 0.00 | 0.264980E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
April | 0.00 | 0.510079E+10 | 0.00 | 0.00 | 0.469687E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 0.00 | 0.646731E+10 | 0.00 | 0.00 | 0.623099E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.650421E+10 | 0.00 | 0.00 | 0.443161E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.414300E+10 | 0.00 | 0.00 | 0.455689E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.589804E+10 | 0.00 | 0.00 | 0.456367E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.553816E+10 | 0.00 | 0.00 | 0.538503E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.562769E+10 | 0.00 | 0.00 | 0.370881E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
November | 0.00 | 0.522055E+10 | 0.00 | 0.00 | 0.247458E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
December | 12098.31 | 0.448932E+10 | 0.00 | 0.00 | 0.211999E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 1257388.93 | 0.616287E+11 | 0.00 | 35427.21 | 0.446025E+10 | 0.00 | 351918.53 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.399396E+10 | 0.00 | 0.00 | 0.181114E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 1235207.12 | 0.650421E+10 | 0.00 | 35427.21 | 0.623099E+09 | 0.00 | 351918.53 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1157702.97 | 0.230573E+10 | 0.00 | 12536.97 | 0.277789E+09 | 0.00 | 145800.67 | 0.00 | 0.53 |
February | 9392.64 | 0.243522E+10 | 0.00 | 0.00 | 0.276321E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
March | 0.00 | 0.332153E+10 | 0.00 | 0.00 | 0.269343E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
April | 0.00 | 0.429132E+10 | 0.00 | 0.00 | 0.418265E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
May | 0.00 | 0.504769E+10 | 0.00 | 0.00 | 0.581069E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
June | 0.00 | 0.521761E+10 | 0.00 | 0.00 | 0.417465E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.316920E+10 | 0.00 | 0.00 | 0.449702E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.466358E+10 | 0.00 | 0.00 | 0.396839E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.408499E+10 | 0.00 | 0.00 | 0.517721E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
October | 0.00 | 0.366047E+10 | 0.00 | 0.00 | 0.457763E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
November | 0.00 | 0.304512E+10 | 0.00 | 0.00 | 0.364164E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
December | 11269.39 | 0.236665E+10 | 0.00 | 0.00 | 0.373766E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 1178365.00 | 0.436091E+11 | 0.00 | 12536.97 | 0.480021E+10 | 0.00 | 145800.67 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.230573E+10 | 0.00 | 0.00 | 0.269343E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 1157702.97 | 0.521761E+10 | 0.00 | 12536.97 | 0.581069E+09 | 0.00 | 145800.67 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3249004.91 | 0.245763E+10 | 0.00 | 48236.85 | 0.459843E+09 | 0.00 | 1019256.16 | 0.00 | 0.36 |
February | 169998.23 | 0.251299E+10 | 0.00 | 7011.83 | 0.413367E+09 | 0.00 | 31107.45 | 0.00 | 0.37 |
March | 0.00 | 0.342041E+10 | 0.00 | 0.00 | 0.440532E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
April | 0.00 | 0.450479E+10 | 0.00 | 0.00 | 0.655526E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
May | 0.00 | 0.643813E+10 | 0.00 | 0.00 | 0.647936E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
June | 0.00 | 0.713454E+10 | 0.00 | 0.00 | 0.398684E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.437369E+10 | 0.00 | 0.00 | 0.440129E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.557327E+10 | 0.00 | 0.00 | 0.479147E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.464306E+10 | 0.00 | 0.00 | 0.671403E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
October | 0.00 | 0.403762E+10 | 0.00 | 0.00 | 0.636744E+09 | 0.00 | 0.00 | 0.00 | 0.37 |
November | 59607.18 | 0.334919E+10 | 0.00 | 278.16 | 0.550706E+09 | 0.00 | 7964.82 | 0.00 | 0.36 |
December | 974066.06 | 0.252213E+10 | 0.00 | 273.80 | 0.569170E+09 | 0.00 | 7045.76 | 0.00 | 0.35 |
Annual Sum or Average | 4452676.39 | 0.509674E+11 | 0.00 | 55800.64 | 0.636319E+10 | 0.00 | 1065374.20 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.245763E+10 | 0.00 | 0.00 | 0.398684E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 3249004.91 | 0.713454E+10 | 0.00 | 48236.85 | 0.671403E+09 | 0.00 | 1019256.16 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1754767.28 | 0.204324E+10 | 0.00 | 66820.30 | 0.265698E+09 | 0.00 | 1693292.40 | 0.00 | 0.46 |
February | 0.00 | 0.220459E+10 | 0.00 | 17089.74 | 0.181554E+09 | 0.00 | 191792.03 | 0.00 | 0.48 |
March | 0.00 | 0.302594E+10 | 0.00 | 0.00 | 0.204747E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
April | 0.00 | 0.391316E+10 | 0.00 | 0.00 | 0.312157E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
May | 0.00 | 0.464984E+10 | 0.00 | 0.00 | 0.414331E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
June | 0.00 | 0.477564E+10 | 0.00 | 0.00 | 0.318261E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.297352E+10 | 0.00 | 0.00 | 0.315992E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.426520E+10 | 0.00 | 0.00 | 0.282426E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.381514E+10 | 0.00 | 0.00 | 0.340604E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.327443E+10 | 0.00 | 0.00 | 0.327316E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
November | 42815.95 | 0.272482E+10 | 0.00 | 948.67 | 0.266634E+09 | 0.00 | 4972.28 | 0.00 | 0.44 |
December | 695602.89 | 0.213514E+10 | 0.00 | 1405.65 | 0.291888E+09 | 0.00 | 7922.57 | 0.00 | 0.44 |
Annual Sum or Average | 2493186.12 | 0.398007E+11 | 0.00 | 86264.36 | 0.352161E+10 | 0.00 | 1897979.28 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.204324E+10 | 0.00 | 0.00 | 0.181554E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 1754767.28 | 0.477564E+10 | 0.00 | 66820.30 | 0.414331E+09 | 0.00 | 1693292.40 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2325736.86 | 0.416101E+10 | 0.00 | 95434.33 | 0.216944E+09 | 0.00 | 2374236.24 | 0.00 | 0.53 |
February | 8282.22 | 0.398023E+10 | 0.00 | 8491.98 | 0.215552E+09 | 0.00 | 189681.27 | 0.00 | 0.52 |
March | 0.00 | 0.479212E+10 | 0.00 | 0.00 | 0.317711E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
April | 0.00 | 0.542151E+10 | 0.00 | 0.00 | 0.657178E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
May | 0.00 | 0.681214E+10 | 0.00 | 0.00 | 0.827984E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.688294E+10 | 0.00 | 0.00 | 0.625726E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.429529E+10 | 0.00 | 0.00 | 0.587224E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.623939E+10 | 0.00 | 0.00 | 0.525365E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.573467E+10 | 0.00 | 0.00 | 0.603839E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.565824E+10 | 0.00 | 0.00 | 0.427003E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
November | 59514.37 | 0.524719E+10 | 0.00 | 3434.88 | 0.309529E+09 | 0.00 | 8008.49 | 0.00 | 0.51 |
December | 899456.41 | 0.441814E+10 | 0.00 | 13502.01 | 0.263854E+09 | 0.00 | 86296.21 | 0.00 | 0.52 |
Annual Sum or Average | 3292989.87 | 0.636429E+11 | 0.00 | 120863.20 | 0.557791E+10 | 0.00 | 2658222.21 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.398023E+10 | 0.00 | 0.00 | 0.215552E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 2325736.86 | 0.688294E+10 | 0.00 | 95434.33 | 0.827984E+09 | 0.00 | 2374236.24 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1745194.58 | 0.210741E+10 | 0.00 | 45368.86 | 0.270113E+09 | 0.00 | 1481512.50 | 0.00 | 0.46 |
February | 0.00 | 0.223184E+10 | 0.00 | 6637.11 | 0.239192E+09 | 0.00 | 153169.70 | 0.00 | 0.48 |
March | 0.00 | 0.311710E+10 | 0.00 | 0.00 | 0.220582E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
April | 0.00 | 0.391652E+10 | 0.00 | 0.00 | 0.363361E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
May | 0.00 | 0.456322E+10 | 0.00 | 0.00 | 0.491799E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
June | 0.00 | 0.474336E+10 | 0.00 | 0.00 | 0.341479E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.295450E+10 | 0.00 | 0.00 | 0.364492E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.422219E+10 | 0.00 | 0.00 | 0.299734E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.373150E+10 | 0.00 | 0.00 | 0.405995E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.323536E+10 | 0.00 | 0.00 | 0.403036E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
November | 45900.47 | 0.272638E+10 | 0.00 | 966.25 | 0.331696E+09 | 0.00 | 5381.26 | 0.00 | 0.44 |
December | 739093.00 | 0.215197E+10 | 0.00 | 2314.42 | 0.342532E+09 | 0.00 | 15059.09 | 0.00 | 0.44 |
Annual Sum or Average | 2530188.05 | 0.397014E+11 | 0.00 | 55286.64 | 0.407401E+10 | 0.00 | 1655122.55 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.210741E+10 | 0.00 | 0.00 | 0.220582E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 1745194.58 | 0.474336E+10 | 0.00 | 45368.86 | 0.491799E+09 | 0.00 | 1481512.50 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4844756.51 | 0.295686E+10 | 0.00 | 55869.87 | 0.344457E+09 | 0.00 | 1010165.38 | 0.00 | 0.41 |
February | 341457.05 | 0.305474E+10 | 0.00 | 12557.08 | 0.310635E+09 | 0.00 | 43916.59 | 0.00 | 0.42 |
March | 0.00 | 0.408129E+10 | 0.00 | 0.00 | 0.325907E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
April | 0.00 | 0.536576E+10 | 0.00 | 0.00 | 0.514188E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
May | 0.00 | 0.754867E+10 | 0.00 | 0.00 | 0.518922E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
June | 0.00 | 0.831835E+10 | 0.00 | 0.00 | 0.322512E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.497060E+10 | 0.00 | 0.00 | 0.361096E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.652250E+10 | 0.00 | 0.00 | 0.416314E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.544982E+10 | 0.00 | 0.00 | 0.565226E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.00 | 0.483479E+10 | 0.00 | 0.00 | 0.528938E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
November | 149381.00 | 0.402594E+10 | 0.00 | 1615.35 | 0.435855E+09 | 0.00 | 1171.67 | 0.00 | 0.41 |
December | 1156292.50 | 0.306682E+10 | 0.00 | 1235.18 | 0.439035E+09 | 0.00 | 2556.54 | 0.00 | 0.40 |
Annual Sum or Average | 6491887.05 | 0.601962E+11 | 0.00 | 71277.47 | 0.508308E+10 | 0.00 | 1057810.19 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.295686E+10 | 0.00 | 0.00 | 0.310635E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 4844756.51 | 0.831835E+10 | 0.00 | 55869.87 | 0.565226E+09 | 0.00 | 1010165.38 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3284947.03 | 0.234388E+10 | 0.00 | 72437.25 | 0.220487E+09 | 0.00 | 1761891.06 | 0.00 | 0.52 |
February | 0.00 | 0.249228E+10 | 0.00 | 28043.68 | 0.172446E+09 | 0.00 | 359372.90 | 0.00 | 0.55 |
March | 0.00 | 0.339589E+10 | 0.00 | 0.00 | 0.215148E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.00 | 0.444739E+10 | 0.00 | 0.00 | 0.327678E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
May | 0.00 | 0.529586E+10 | 0.00 | 0.00 | 0.423696E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.547793E+10 | 0.00 | 0.00 | 0.322539E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.331196E+10 | 0.00 | 0.00 | 0.321136E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.485905E+10 | 0.00 | 0.00 | 0.310250E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.430693E+10 | 0.00 | 0.00 | 0.352700E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.00 | 0.376645E+10 | 0.00 | 0.00 | 0.336102E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 119605.22 | 0.310699E+10 | 0.00 | 1662.25 | 0.261131E+09 | 0.00 | 674.71 | 0.00 | 0.50 |
December | 925811.36 | 0.244872E+10 | 0.00 | 494.96 | 0.264234E+09 | 0.00 | 2540.97 | 0.00 | 0.50 |
Annual Sum or Average | 4330363.62 | 0.452533E+11 | 0.00 | 102638.14 | 0.352754E+10 | 0.00 | 2124479.63 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.234388E+10 | 0.00 | 0.00 | 0.172446E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 3284947.03 | 0.547793E+10 | 0.00 | 72437.25 | 0.423696E+09 | 0.00 | 1761891.06 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3482696.20 | 0.442550E+10 | 0.00 | 105637.15 | 0.170529E+09 | 0.00 | 2973866.79 | 0.00 | 0.57 |
February | 25020.09 | 0.425823E+10 | 0.00 | 19603.38 | 0.177697E+09 | 0.00 | 369982.54 | 0.00 | 0.55 |
March | 0.00 | 0.474710E+10 | 0.00 | 0.00 | 0.252626E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
April | 0.00 | 0.526360E+10 | 0.00 | 0.00 | 0.527826E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
May | 0.00 | 0.667367E+10 | 0.00 | 0.00 | 0.655531E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
June | 0.00 | 0.674358E+10 | 0.00 | 0.00 | 0.486542E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.427238E+10 | 0.00 | 0.00 | 0.485309E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.611295E+10 | 0.00 | 0.00 | 0.461659E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.574264E+10 | 0.00 | 0.00 | 0.529643E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.586011E+10 | 0.00 | 0.00 | 0.370746E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
November | 149102.59 | 0.549775E+10 | 0.00 | 2481.69 | 0.239255E+09 | 0.00 | 1000.99 | 0.00 | 0.53 |
December | 1134818.33 | 0.475011E+10 | 0.00 | 2909.60 | 0.215804E+09 | 0.00 | 20831.90 | 0.00 | 0.56 |
Annual Sum or Average | 4791637.21 | 0.643476E+11 | 0.00 | 130631.82 | 0.457317E+10 | 0.00 | 3365682.22 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.425823E+10 | 0.00 | 0.00 | 0.170529E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 3482696.20 | 0.674358E+10 | 0.00 | 105637.15 | 0.655531E+09 | 0.00 | 2973866.79 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4209252.27 | 0.246622E+10 | 0.00 | 34540.32 | 0.247717E+09 | 0.00 | 690159.44 | 0.00 | 0.53 |
February | 296212.52 | 0.261211E+10 | 0.00 | 7492.18 | 0.251535E+09 | 0.00 | 27525.86 | 0.00 | 0.56 |
March | 0.00 | 0.357594E+10 | 0.00 | 0.00 | 0.240312E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
April | 0.00 | 0.453267E+10 | 0.00 | 0.00 | 0.379429E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
May | 0.00 | 0.527479E+10 | 0.00 | 0.00 | 0.525672E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
June | 0.00 | 0.548153E+10 | 0.00 | 0.00 | 0.392326E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.330612E+10 | 0.00 | 0.00 | 0.409876E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.485914E+10 | 0.00 | 0.00 | 0.362876E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.426936E+10 | 0.00 | 0.00 | 0.461439E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
October | 0.00 | 0.378272E+10 | 0.00 | 0.00 | 0.443058E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
November | 129587.37 | 0.318439E+10 | 0.00 | 889.52 | 0.351832E+09 | 0.00 | 1528.21 | 0.00 | 0.51 |
December | 1003078.77 | 0.253602E+10 | 0.00 | 805.27 | 0.326372E+09 | 0.00 | 2484.04 | 0.00 | 0.52 |
Annual Sum or Average | 5638130.93 | 0.458810E+11 | 0.00 | 43727.28 | 0.439244E+10 | 0.00 | 721697.55 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.246622E+10 | 0.00 | 0.00 | 0.240312E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 4209252.27 | 0.548153E+10 | 0.00 | 34540.32 | 0.525672E+09 | 0.00 | 690159.44 | 0.00 | 0.62 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.240816E+12 | -0.881024E+10 | 0.00 | -0.999732E+11 | 0.346153E+12 |
February | 0.234451E+12 | -0.909112E+10 | 0.00 | -0.100929E+12 | 0.330209E+12 |
March | 0.298986E+12 | -0.146005E+11 | 0.00 | -0.125603E+12 | 0.404163E+12 |
April | 0.294091E+12 | -0.163366E+11 | 0.00 | -0.164736E+12 | 0.423048E+12 |
May | 0.296261E+12 | -0.208318E+11 | 0.00 | -0.206314E+12 | 0.482664E+12 |
June | 0.307162E+12 | -0.202894E+11 | 0.00 | -0.201193E+12 | 0.485305E+12 |
July | 0.255866E+12 | -0.120995E+11 | 0.00 | -0.143493E+12 | 0.381085E+12 |
August | 0.317026E+12 | -0.185425E+11 | 0.00 | -0.183479E+12 | 0.444897E+12 |
September | 0.251204E+12 | -0.142883E+11 | 0.00 | -0.173418E+12 | 0.406386E+12 |
October | 0.277733E+12 | -0.136133E+11 | 0.00 | -0.163790E+12 | 0.391542E+12 |
November | 0.230967E+12 | -0.111149E+11 | 0.00 | -0.137877E+12 | 0.365205E+12 |
December | 0.227540E+12 | -0.835966E+10 | 0.00 | -0.110831E+12 | 0.336644E+12 |
Annual Sum or Average | 0.323210E+13 | -0.167978E+12 | 0.00 | -0.181164E+13 | 0.479730E+13 |
Minimum of Months | 0.227540E+12 | -0.208318E+11 | 0.00 | -0.206314E+12 | 0.330209E+12 |