Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 08:35:11
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2287.32 | 459.10 | 459.10 |
Net Site Energy | 2287.32 | 459.10 | 459.10 |
Total Source Energy | 7065.64 | 1418.18 | 1418.18 |
Net Source Energy | 7065.64 | 1418.18 | 1418.18 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 899.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 174.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 85.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2201.72 | 85.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 899.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 280.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 71.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 174.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 85.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 899.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 280.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 71.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 174.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 85.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 215.70 | 17.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 441.92 | 17.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 215.70 | 17.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 441.92 | 17.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2201.721 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2201.721 | 100.00 |
Total On-Site and Utility Electric Sources | 2201.721 | 100.00 |
Total Electricity End Uses | 2201.721 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.67 |
Time Setpoint Not Met During Occupied Cooling | 542.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1289.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.5763 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 7.5763 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 7.5763 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:39 | 10-JAN-12:20 | - | - | - | - | - | - | - | - | - | - | 24-APR-11:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 127061.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 23688.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 43769.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 920.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 23823.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8797.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 219264.18 | 8797.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 127061.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 23688.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 7527.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 920.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 23823.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8797.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 1.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2850.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 886.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 227.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2413.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 41.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 552.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 92.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6972.85 | 92.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 572.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 178.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 110.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1399.56 | 18.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 572.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 178.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 110.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1399.56 | 18.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.89 | 0.259273 | 0.277000 | 0.800698 | 0.691394 | 0.500000 | 0.001469 |
CORE_MID VAV BOX COMPONENT | 2.19 | 0.342965 | 0.354000 | 0.773569 | 0.914573 | 0.500000 | 0.001111 |
CORE_TOP VAV BOX COMPONENT | 2.51 | 0.299066 | 0.324000 | 0.811939 | 0.797510 | 0.500000 | 0.001274 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.929162 | 0.170037 | 0.200000 | 0.185832 | 0.453431 | 0.500000 | 0.002241 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.727437 | 0.137499 | 0.200000 | 0.145487 | 0.366664 | 0.500000 | 0.002771 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.03 | 0.153453 | 0.200000 | 0.205915 | 0.409209 | 0.500000 | 0.002483 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.827599 | 0.120850 | 0.200000 | 0.165520 | 0.322266 | 0.500000 | 0.003153 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.777016 | 0.203331 | 0.217000 | 0.168612 | 0.542217 | 0.500000 | 0.001874 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.648141 | 0.154321 | 0.200000 | 0.129628 | 0.411523 | 0.500000 | 0.002469 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.868225 | 0.181971 | 0.200000 | 0.173645 | 0.485256 | 0.500000 | 0.002094 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.683203 | 0.146392 | 0.200000 | 0.136641 | 0.390378 | 0.500000 | 0.002603 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.776987 | 0.203339 | 0.210000 | 0.163167 | 0.542237 | 0.500000 | 0.001874 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.667646 | 0.149813 | 0.200000 | 0.133529 | 0.399500 | 0.500000 | 0.002543 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.873112 | 0.180952 | 0.200000 | 0.174622 | 0.482540 | 0.500000 | 0.002106 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.716698 | 0.139550 | 0.200000 | 0.143340 | 0.372133 | 0.500000 | 0.002730 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 26729.76 |
CORE_MID VAV BOX REHEAT COIL | 25824.12 |
CORE_TOP VAV BOX REHEAT COIL | 27105.03 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 7043.54 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 4856.82 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 7012.60 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 5525.57 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5628.80 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4327.39 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 5796.81 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4561.49 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 5447.03 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 4457.62 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 5829.43 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 4785.12 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.93 | 1.41 | 5.87 | 1.41 | 5.49 | 5.49 | 0.300000 | 0.256598 | 5.49 |
PACU_VAV_MID | 2.61 | 1.39 | 5.22 | 1.39 | 4.79 | 4.79 | 0.300000 | 0.289711 | 4.79 |
PACU_VAV_TOP | 3.01 | 1.51 | 6.02 | 1.51 | 5.86 | 5.86 | 0.300000 | 0.258298 | 5.86 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.49 |
PACU_VAV_MID_OA_CONTROLLER | 4.79 |
PACU_VAV_TOP_OA_CONTROLLER | 5.86 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.49 | 131519.09 | 0.712138 | 1.83 | 43835.31 | 0.712138 |
PACU_VAV_MID COOLING COIL | 4.79 | 118894.78 | 0.701282 | 1.60 | 39627.63 | 0.701282 |
PACU_VAV_TOP COOLING COIL | 5.86 | 138597.12 | 0.716503 | 1.95 | 46194.42 | 0.716503 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 0.000000 |
PACU_VAV_MID HEATING COIL | 0.000000 |
PACU_VAV_TOP HEATING COIL | 0.000000 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.49 |
PACU_VAV_MID FAN | 4.79 |
PACU_VAV_TOP FAN | 5.86 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 32.411 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.029 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 1.013 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.375 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7377 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7531 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4931 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
39 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
40 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
41 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
42 | 7 | -0.27613173E-12 | 0.13648587E-14 | -0.80406974E-13 | 0.78369587E-16 |
43 | 6 | 0.25651297E-07 | 0.27955499E-09 | 0.59014154E-08 | -0.11905989E-12 |
44 | 5 | -0.17465063E-03 | 0.24416492E-05 | -0.90019538E-04 | 0.58421144E-08 |
45 | 4 | 0.27387862 | 0.12098825E-02 | 0.93122264E-01 | -0.31012301E-04 |
46 | 3 | -6.9041115 | 0.38080793E-01 | -2.2314619 | 0.27235146E-01 |
47 | 2 | 39.676056 | 0.13726811 | 14.823303 | -0.32003278 |
48 | 1 | -79.629469 | 0.62686726E-01 | -28.745292 | 1.0590931 |
49 | 0 | 46.824345 | 0.12759187E-02 | 16.300942 | |
50 | 7 | -0.27182421E-12 | 0.13107754E-14 | -0.81108189E-13 | 0.79120162E-16 |
51 | 6 | 0.25844325E-07 | 0.27588229E-09 | 0.59440225E-08 | -0.12008605E-12 |
52 | 5 | -0.17564658E-03 | 0.24062150E-05 | -0.90521036E-04 | 0.58837691E-08 |
53 | 4 | 0.27506755 | 0.11908598E-02 | 0.93548701E-01 | -0.31177608E-04 |
54 | 3 | -6.9277136 | 0.37441415E-01 | -2.2384615 | 0.27350651E-01 |
55 | 2 | 39.753961 | 0.13483533 | 14.852153 | -0.32090009 |
56 | 1 | -79.689237 | 0.61525268E-01 | -28.771196 | 1.0603666 |
57 | 0 | 46.824344 | 0.12512697E-02 | 16.300293 | |
58 | 6 | 0.21465343E-07 | 0.35044740E-09 | 0.49771822E-08 | -0.96989815E-13 |
59 | 5 | -0.15274237E-03 | 0.31655188E-05 | -0.78941554E-04 | 0.49363227E-08 |
60 | 4 | 0.24727258 | 0.16154212E-02 | 0.83601931E-01 | -0.27359285E-04 |
61 | 3 | -6.3748395 | 0.52179222E-01 | -2.0745682 | 0.24648141E-01 |
62 | 2 | 37.927790 | 0.19236366 | 14.173893 | -0.30057625 |
63 | 1 | -78.286849 | 0.89555956E-01 | -28.161423 | 1.0304865 |
64 | 0 | 46.824354 | 0.18576719E-02 | 16.316151 | |
65 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
66 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
67 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
68 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
69 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
70 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
71 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
72 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
73 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
74 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
75 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
76 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
77 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
78 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
79 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
80 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
81 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
82 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
83 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
84 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
85 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
86 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
87 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
88 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
89 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
90 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
91 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
92 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
93 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
94 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
95 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
96 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
97 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
98 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
99 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
100 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
101 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
102 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
103 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
104 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
105 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.1510E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1852E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3966E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4249E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.2201E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2416E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4264E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4410E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.4939E-002 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1733E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1678E-002 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2956E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2359E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3738E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8057E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0496E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.1523E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1932E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3981E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4336E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.2216E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2486E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4263E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4409E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0383E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2884E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7935E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.0916E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9296E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9301E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2668E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5265E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6271E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6401E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4307E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4401E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2715E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2750E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8320E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8371E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3456E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3774E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9954E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0209E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7391E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7570E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4263E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4409E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1375E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2262E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6779E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.4855E-003 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5623E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.6375E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8057E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0496E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3451E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3766E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9947E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0190E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7378E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7520E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4264E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4410E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2711E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9470E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8828E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6869E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1484E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5843E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2668E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5265E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1444E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1691E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8518E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8759E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8033E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8172E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8321E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8372E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.7775E-002 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.9660E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.3957E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.1263E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.6485E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.0467E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.1564E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.4627E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.8913E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2054E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6634E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.0182E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.8196E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.8696E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.1886E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.4843E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4454E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6120E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.9570E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2866E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8361E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 9.7410E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1564E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4627E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.1505E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8808E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.7840E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.6337E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.0645E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5402E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.1887E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.4843E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.7773E-002 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.9656E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.3954E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.1259E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.6481E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.0464E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.1562E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.4625E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.8913E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2053E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6633E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.0181E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.8194E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.8694E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.1884E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.4841E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4455E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6120E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.9570E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2866E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8360E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 9.7402E-003 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1562E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4625E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.1505E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8807E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.7840E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.6336E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.0644E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5400E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.1884E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4842E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 40097.67422 | 40097.67422 | 2.89060 | 2.89060 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 635.06439 | 635.06439 | 2.71587E-002 | 0.42469 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 30345.36931 | 30345.36931 | 2.18522 | 2.18522 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 6388.66197 | 6388.66197 | 0.26715 | 0.42469 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 34474.81355 | 34474.81355 | 2.50598 | 2.50598 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 42.60600 | 1.07815E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 11853.46026 | 11853.46026 | 0.50046 | 0.50046 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 12782.22290 | 12782.22290 | 0.92916 | 0.92916 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 4964.05484 | 4964.05484 | 0.21099 | 0.21099 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10007.15257 | 10007.15257 | 0.72744 | 0.72744 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 40.08400 | 1.07771E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 3237.10606 | 3237.10606 | 0.13762 | 0.13762 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 14163.58420 | 14163.58420 | 1.02957 | 1.02957 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 4942.39584 | 4942.39584 | 0.21006 | 0.21006 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11385.08854 | 11385.08854 | 0.82760 | 0.82760 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 3249.73460 | 3249.73460 | 0.13816 | 0.13816 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 10689.33319 | 10689.33319 | 0.77702 | 0.77702 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 2324.40804 | 2324.40804 | 9.96800E-002 | 9.96800E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8916.43999 | 8916.43999 | 0.64814 | 0.64814 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 40.08400 | 1.07771E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 1533.62212 | 1533.62212 | 6.57680E-002 | 6.57680E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 11944.10562 | 11944.10562 | 0.86822 | 0.86822 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 2315.72041 | 2315.72041 | 9.93075E-002 | 9.93075E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9398.79244 | 9398.79244 | 0.68320 | 0.68320 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 1539.47479 | 1539.47479 | 6.60190E-002 | 6.60190E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 10688.82120 | 10688.82120 | 0.77699 | 0.77699 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 3363.70309 | 3363.70309 | 0.14254 | 0.14254 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9184.66680 | 9184.66680 | 0.66765 | 0.66765 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 39.59900 | 1.07763E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 2219.37668 | 2219.37668 | 9.40772E-002 | 9.40772E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 12011.20479 | 12011.20479 | 0.87311 | 0.87311 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 3347.45974 | 3347.45974 | 0.14184 | 0.14184 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9859.47616 | 9859.47616 | 0.71670 | 0.71670 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 2228.38944 | 2228.38944 | 9.44619E-002 | 9.44619E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 101552.54 | 5.49195 | 5.49195 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 91.37 | 0.75547 | 0.75547 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 92007.71 | 4.79177 | 4.79177 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 108.56 | 0.89761 | 0.89761 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 106419.81 | 5.86414 | 5.86414 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 139.65 | 1.19729 | 1.19729 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.89060 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25927 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27700 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80070 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69139 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.46950E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26729.76498 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.18522 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34297 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35400 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77357 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91457 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11090E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25824.12130 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.50598 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29907 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32400 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81194 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79751 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.27397E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 27105.03005 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.92916 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17004 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18583 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45343 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.24069E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7043.53956 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72744 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13750 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14549 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36666 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.77093E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4856.81776 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.02957 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15345 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20591 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40921 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.48284E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7012.60163 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82760 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12085 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16552 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32227 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.15267E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5525.56662 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77702 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20333 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21700 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16861 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54222 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.87379E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5628.80325 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64814 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15432 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12963 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41152 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.46888E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4327.38923 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86822 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18197 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17364 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48526 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09374E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5796.80695 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68320 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14639 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13664 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39038 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.60261E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4561.48820 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77699 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20334 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16317 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54224 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.87372E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5447.02675 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66765 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14981 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13353 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39950 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54318E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4457.61660 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87311 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18095 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17462 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48254 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10553E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5829.43479 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71670 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13955 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14334 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37213 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.73020E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4785.11956 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.93359 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.40922 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.86719 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.40922 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.49195 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.49195 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.25660 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.60983 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.38823 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.21966 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.38823 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.79177 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.79177 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.28971 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.00988 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.51469 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.01976 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.51469 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.86414 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.86414 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.25830 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.49195 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.79177 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.86414 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.49195 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.49195 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 131519.09440 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.71214 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.83047 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 43835.31416 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.71214 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.49195 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.79177 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.79177 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 118894.77632 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70128 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.59710 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 39627.62895 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70128 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.79177 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.86414 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.86414 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 138597.11586 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.71650 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.95452 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 46194.41872 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.71650 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.86414 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 131152.98 | 447512.53 | 11.58 | 2.96 | 3.32 | 3.50 | 3.63 | 10.10 | 11.32 | 11.95 | 12.38 | 6.3490 | 5.0399 | 3.3875 | 1.4437 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 118697.59 | 405012.99 | 11.64 | 2.97 | 3.34 | 3.52 | 3.64 | 10.14 | 11.39 | 12.02 | 12.42 | 5.5396 | 4.3954 | 2.9567 | 1.2723 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 138152.04 | 471394.32 | 11.55 | 2.95 | 3.31 | 3.49 | 3.62 | 10.08 | 11.29 | 11.91 | 12.36 | 6.7793 | 5.3880 | 3.6240 | 1.5353 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1220514307 | 0.2346338834 | Pass | Pass | 9.3195849752E-002 | 0.2885163065 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.1242363387E-002 | 5.8847726793E-002 | Pass | Pass | 1.3124304491E-002 | 7.8436522872E-002 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.5957812414E-002 | 2.3986864367E-002 | Pass | Pass | 1.9061045325 | 21.8106401546 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.2302852006E-002 | 3.3409066365E-002 | Pass | Pass | 0.1418378225 | 0.5033349887 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.8891678370E-002 | 0.1503526566 | Pass | Pass | 4.3328311414E-002 | 0.2019815713 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.6046352589E-002 | 0.1269184217 | Pass | Pass | 1.5648455314E-002 | 0.1246235122 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.1590061759E-002 | 0.1139975263 | Pass | Pass | 1.5307140811E-002 | 0.1231232907 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.0380361406E-002 | 0.1348140393 | Pass | Pass | 1.5678737413E-002 | 0.1247199527 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1076341300 | 0.1536040208 | Pass | Pass | 1.7644229016E-002 | 0.1337958139 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.9648215036E-002 | 0.1641184855 | Pass | Pass | 1.5726312350E-002 | 0.1249384510 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1052035991 | 0.1787616376 | Pass | Pass | 9.2020948891E-002 | 0.2873453231 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1252486128 | 0.2142343411 | Pass | Pass | 9.2145612535E-002 | 0.2875563074 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1291092017 | 0.2161374238 | Pass | Pass | 9.1564498592E-002 | 0.2872798018 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1320726909 | 0.2293481437 | Pass | Pass | 9.1638821791E-002 | 0.2860485535 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.1002256790E-002 | 0.1265148125 | Pass | Pass | 4.2626531498E-002 | 0.2004933140 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.4723569482E-002 | 0.1580228734 | Pass | Pass | 4.2741701366E-002 | 0.2006454696 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 9.9015290083E-002 | 0.1610339324 | Pass | Pass | 4.1779062945E-002 | 0.1992675182 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.9496096241E-002 | 0.1752117521 | Pass | Pass | 4.2294612185E-002 | 0.1989338257 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2183.78 | -123.4 | 0.00 | -1075.4 | 4120.42 | 5105.45 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5047_SHGC_EAST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5047_SHGC_WEST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5047_SHGC_EAST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5047_SHGC_WEST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.869 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 177.99 | 2.869 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.869 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.06 | 0.0000 | Y | 9.16 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.08 | 0.0000 | Y | 5.80 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 30.95 | 0.0000 | Y | 9.13 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.03 | 0.0000 | Y | 5.79 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.03 | 0.0000 | Y | 9.15 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.05 | 0.0000 | Y | 5.80 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 30.93 | 0.0000 | Y | 9.12 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.00 | 0.0000 | Y | 5.79 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.06 | 0.0000 | Y | 9.16 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.08 | 0.0000 | Y | 5.80 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 30.95 | 0.0000 | Y | 9.13 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.03 | 0.0000 | Y | 5.79 |
Interior Lighting Total | 7.5763 | 4982.19 | 37746.71 | 280.06 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 41.85 | 41.85 | 3.34 | |
EXTERIOR_LIGHTS_B | 5132.60 | AstronomicalClock | - | 83.85 | 71.25 | 68.65 | |
Exterior Lighting Total | 5557.43 | 71.98 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 131519.09 | 93659.74 | 37859.35 | 0.71 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 118894.78 | 83378.75 | 35516.03 | 0.70 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 138597.12 | 99305.22 | 39291.90 | 0.72 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 131153.0 | 2.96 | 10.10 | N/A | N/A | 11.58 | |
PACU_VAV_MID COOLING COIL | 118697.6 | 2.97 | 10.14 | N/A | N/A | 11.64 | |
PACU_VAV_TOP COOLING COIL | 138152.0 | 2.95 | 10.08 | N/A | N/A | 11.55 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 26729.76 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 25824.12 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 27105.03 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7043.54 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4856.82 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7012.60 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5525.57 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5628.80 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4327.39 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5796.81 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4561.49 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5447.03 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4457.62 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5829.43 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4785.12 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 0.00 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 0.00 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 0.00 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.49 | 11944.37 | 2174.89 | 1.00 | 1.14 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.79 | 10489.24 | 2189.01 | 1.00 | 1.14 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.86 | 12753.85 | 2174.89 | 1.00 | 1.13 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 131152.98 | 2.96 | 10.10 | 11.58 | 6.3490 | 3.32 | 11.32 | 5.0399 | 3.50 | 11.95 | 3.3875 | 3.63 | 12.38 | 1.4437 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 118697.59 | 2.97 | 10.14 | 11.64 | 5.5396 | 3.34 | 11.39 | 4.3954 | 3.52 | 12.02 | 2.9567 | 3.64 | 12.42 | 1.2723 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 138152.04 | 2.95 | 10.08 | 11.55 | 6.7793 | 3.31 | 11.29 | 5.3880 | 3.49 | 11.91 | 3.6240 | 3.62 | 12.36 | 1.5353 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 40097.67 | 40097.67 | 40.77 | 2.891 | 2.891 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 35.62 | 0.01077 | 0.425 | 0.00 |
CORE_MID | 30345.37 | 30345.37 | 30.85 | 2.185 | 2.185 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 35.62 | 0.01077 | 0.425 | 0.00 |
CORE_TOP | 34474.81 | 34474.81 | 35.05 | 2.506 | 2.506 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00885 | 42.61 | 0.01078 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 12782.22 | 12782.22 | 61.65 | 0.929 | 0.929 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00877 | 42.70 | 0.01078 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10007.15 | 10007.15 | 76.24 | 0.727 | 0.727 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 24.00 | 24.00 | 0.00873 | 40.08 | 0.01078 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 14163.58 | 14163.58 | 68.31 | 1.030 | 1.030 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00875 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11385.09 | 11385.09 | 86.74 | 0.828 | 0.828 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00870 | 41.96 | 0.01078 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 10689.33 | 10689.33 | 51.56 | 0.777 | 0.777 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00878 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8916.44 | 8916.44 | 67.93 | 0.648 | 0.648 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 24.00 | 24.00 | 0.00872 | 40.08 | 0.01078 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11944.11 | 11944.11 | 57.61 | 0.868 | 0.868 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00875 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9398.79 | 9398.79 | 71.61 | 0.683 | 0.683 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00871 | 41.96 | 0.01078 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 10688.82 | 10688.82 | 51.55 | 0.777 | 0.777 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00881 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9184.67 | 9184.67 | 69.97 | 0.668 | 0.668 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 24.00 | 24.00 | 0.00873 | 39.60 | 0.01078 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12011.20 | 12011.20 | 57.93 | 0.873 | 0.873 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00878 | 42.72 | 0.01078 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9859.48 | 9859.48 | 75.12 | 0.717 | 0.717 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00872 | 41.96 | 0.01078 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 635.06 | 635.06 | 0.65 | 0.027 | 0.425 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00841 | 12.70 | 0.00915 | 0.425 | 0.00 |
CORE_MID | 6388.66 | 6388.66 | 6.50 | 0.267 | 0.425 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 0.425 | 0.00 |
CORE_TOP | 11853.46 | 11853.46 | 12.05 | 0.500 | 0.500 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 4964.05 | 4964.05 | 23.94 | 0.211 | 0.211 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00821 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 3237.11 | 3237.11 | 24.66 | 0.138 | 0.138 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00821 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 4942.40 | 4942.40 | 23.84 | 0.210 | 0.210 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00821 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 3249.73 | 3249.73 | 24.76 | 0.138 | 0.138 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00821 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 2324.41 | 2324.41 | 11.21 | 0.100 | 0.100 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00826 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 1533.62 | 1533.62 | 11.68 | 0.066 | 0.066 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00827 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 2315.72 | 2315.72 | 11.17 | 0.099 | 0.099 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00827 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 1539.47 | 1539.47 | 11.73 | 0.066 | 0.066 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00826 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 3363.70 | 3363.70 | 16.22 | 0.143 | 0.143 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00830 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 2219.38 | 2219.38 | 16.91 | 0.094 | 0.094 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00830 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 3347.46 | 3347.46 | 16.14 | 0.142 | 0.142 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00830 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 2228.39 | 2228.39 | 16.98 | 0.094 | 0.094 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00830 | 12.70 | 0.00915 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.49 | 5.49 | 0.76 | 0.76 | 5.4919 | 1.4092 | 5.4919 | 0.2566 | 0.3000 |
PACU_VAV_MID | 4.79 | 4.79 | 0.90 | 0.90 | 4.7918 | 1.3882 | 4.7918 | 0.2897 | 0.3000 |
PACU_VAV_TOP | 5.86 | 5.86 | 1.20 | 1.20 | 5.8641 | 1.5147 | 5.8641 | 0.2583 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 26729.765 | 26729.765 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26729.76 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00841026 | 54.3083 | 635.06 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 25824.121 | 25824.121 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25824.12 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 6388.66 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 27105.030 | 27105.030 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27105.03 | 16706.85 | 0.500458 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 11853.46 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 7043.540 | 7043.540 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7043.54 | 7043.54 | 0.210991 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00821151 | 53.0400 | 4964.05 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 4856.818 | 4856.818 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4856.82 | 4594.09 | 0.137617 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00821059 | 53.0341 | 3237.11 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 7012.602 | 7012.602 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7012.60 | 7012.60 | 0.210064 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00821326 | 53.0512 | 4942.40 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 5525.567 | 5525.567 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5525.57 | 4612.13 | 0.138157 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00820898 | 53.0239 | 3249.73 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 5628.803 | 5628.803 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5628.80 | 3327.63 | 0.099680 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00826418 | 53.3764 | 2324.41 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4327.389 | 4327.389 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 4327.39 | 2195.54 | 0.065768 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00826528 | 53.3834 | 1533.62 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 5796.807 | 5796.807 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5796.81 | 3315.19 | 0.099307 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00826520 | 53.3829 | 2315.72 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4561.488 | 4561.488 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 4561.49 | 2203.92 | 0.066019 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00826422 | 53.3766 | 1539.47 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 5447.027 | 5447.027 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5447.03 | 4758.27 | 0.142535 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00830316 | 53.6242 | 3363.70 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 4457.617 | 4457.617 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4457.62 | 3140.59 | 0.094077 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00830274 | 53.6215 | 2219.38 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 5829.435 | 5829.435 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5829.43 | 4735.10 | 0.141841 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00830470 | 53.6340 | 3347.46 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 4785.120 | 4785.120 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4785.12 | 3153.43 | 0.094462 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00830138 | 53.6128 | 2228.39 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 131519.094 | 93659.742 | 5.491948 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 122585.56 | 110459.85 | 5.491948 | 28.09 | 18.38 | 0.00922405 | 11.03 | 11.03 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 21.7622 | 24.00 | 0.00879069 | 47.2803 | 75543.66 | 0.00 | 135613.84 | 95239.44 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 0.00 | 0.00 | 1.647584 | 14.98 | 13.40 | 0.00893128 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 72.5407 | 21.00 | 0.00827401 | 53.4391 | 8255.16 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 118894.776 | 83378.749 | 4.791773 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 111714.26 | 99607.96 | 4.791773 | 28.69 | 18.66 | 0.00933055 | 11.02 | 11.02 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 24.9421 | 24.00 | 0.00884759 | 47.5824 | 65848.78 | 0.00 | 122596.47 | 84794.64 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 1.437532 | 14.05 | 13.08 | 0.00898591 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 83.1404 | 21.00 | 0.00819374 | 52.9273 | 17547.59 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 138597.116 | 99305.221 | 5.864138 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 128809.19 | 116308.79 | 5.864138 | 27.84 | 18.28 | 0.00919821 | 11.03 | 11.03 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 20.3810 | 24.00 | 0.00879167 | 47.2858 | 80487.24 | 0.00 | 142912.23 | 100944.95 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 1.759241 | 15.36 | 13.44 | 0.00881395 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 67.9367 | 21.00 | 0.00809461 | 52.2955 | 26924.47 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 26729.765 | 26729.765 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26729.76 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26729.76 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.96 | 0.00841026 | 21.00 | 0.00841026 | 54.3083 | 635.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 25824.121 | 25824.121 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25824.12 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25824.12 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.59 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 6388.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 27105.030 | 27105.030 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27105.03 | 16706.85 | 1.0000 | 0.60234899 | 0.500458 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27105.03 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 11853.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 7043.540 | 7043.540 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7043.54 | 7043.54 | 1.0000 | 0.25394794 | 0.210991 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7043.54 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00821151 | 21.00 | 0.00821151 | 53.0400 | 4964.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4856.818 | 4856.818 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4856.82 | 4594.09 | 1.0000 | 0.16563535 | 0.137617 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4856.82 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00821059 | 21.00 | 0.00821059 | 53.0341 | 3237.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 7012.602 | 7012.602 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7012.60 | 7012.60 | 1.0000 | 0.25283250 | 0.210064 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7012.60 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00821326 | 21.00 | 0.00821326 | 53.0512 | 4942.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5525.567 | 5525.567 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5525.57 | 4612.13 | 1.0000 | 0.16628567 | 0.138157 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5525.57 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00820898 | 21.00 | 0.00820898 | 53.0239 | 3249.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5628.803 | 5628.803 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 5628.80 | 3327.63 | 1.0000 | 0.11997437 | 0.099680 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5628.80 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00826418 | 21.00 | 0.00826418 | 53.3764 | 2324.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4327.389 | 4327.389 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 4327.39 | 2195.54 | 1.0000 | 0.07915801 | 0.065768 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4327.39 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00826528 | 21.00 | 0.00826528 | 53.3834 | 1533.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5796.807 | 5796.807 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 5796.81 | 3315.19 | 1.0000 | 0.11952596 | 0.099307 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5796.81 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00826520 | 21.00 | 0.00826520 | 53.3829 | 2315.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4561.488 | 4561.488 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 4561.49 | 2203.92 | 1.0000 | 0.07946010 | 0.066019 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4561.49 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00826422 | 21.00 | 0.00826422 | 53.3766 | 1539.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5447.027 | 5447.027 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5447.03 | 4758.27 | 1.0000 | 0.17155460 | 0.142535 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5447.03 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00830316 | 21.00 | 0.00830316 | 53.6242 | 3363.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4457.617 | 4457.617 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4457.62 | 3140.59 | 1.0000 | 0.11323090 | 0.094077 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4457.62 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00830274 | 21.00 | 0.00830274 | 53.6215 | 2219.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5829.435 | 5829.435 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5829.43 | 4735.10 | 1.0000 | 0.17071957 | 0.141841 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5829.43 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00830470 | 21.00 | 0.00830470 | 53.6340 | 3347.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4785.120 | 4785.120 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4785.12 | 3153.43 | 1.0000 | 0.11369391 | 0.094462 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4785.12 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00830138 | 21.00 | 0.00830138 | 53.6128 | 2228.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 131519.094 | 93659.742 | 5.491948 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9870 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.491948 | 6.61008125 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 122585.56 | 110459.85 | 0.9321 | 6.61008125 | 5.491948 | 28.09 | 18.38 | 0.00922405 | 51777.2 | 11.03 | 11.03 | 0.00850000 | 32517.6 | -999.0 | -999.00 | -999.00 | -999.00 | 11944.374 | 110641.19 | 42.80 | 0.01078182 | 23.86 | 1.19517000 | 21.7622 | 24.00 | 0.00879069 | 24.00 | 0.00879069 | 47.2803 | 75543.66 | 0.00 | 135613.84 | 95239.44 | 6.34903301 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.97 | 11.95 | 0.00869138 | 33962.6 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.491948 | 6.61008125 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 0.00 | 0.00 | 1.0000 | 1.98302437 | 1.647584 | 14.98 | 13.40 | 0.00893128 | 37638.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 1.19517000 | 72.5407 | 21.00 | 0.00834435 | 21.00 | 0.00827401 | 53.4391 | 8255.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 118894.776 | 83378.749 | 4.791773 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1850 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.791773 | 5.76735405 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 111714.26 | 99607.96 | 0.9396 | 5.76735405 | 4.791773 | 28.69 | 18.66 | 0.00933055 | 52664.9 | 11.02 | 11.02 | 0.00850000 | 32506.2 | -999.0 | -999.00 | -999.00 | -999.00 | 10489.244 | 101225.01 | 42.80 | 0.01078182 | 23.86 | 1.19517000 | 24.9421 | 24.00 | 0.00884759 | 24.00 | 0.00884759 | 47.5824 | 65848.78 | 0.00 | 122596.47 | 84794.64 | 5.53958717 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.67 | 11.64 | 0.00850914 | 33191.4 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.791773 | 5.76735405 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 1.73020622 | 1.437532 | 14.05 | 13.08 | 0.00898591 | 36830.8 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 1.19517000 | 83.1404 | 20.74 | 0.00815974 | 21.00 | 0.00819374 | 52.9273 | 17547.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 138597.116 | 99305.221 | 5.864138 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9390 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.864138 | 7.05804718 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | Sensible | 128809.19 | 116308.79 | 0.9294 | 7.05804718 | 5.864138 | 27.84 | 18.28 | 0.00919821 | 51454.3 | 11.03 | 11.03 | 0.00850000 | 32517.5 | -999.0 | -999.00 | -999.00 | -999.00 | 12753.846 | 116055.35 | 42.80 | 0.01078182 | 23.86 | 1.19517000 | 20.3810 | 24.00 | 0.00879167 | 24.00 | 0.00879167 | 47.2858 | 80487.24 | 0.00 | 142912.23 | 100944.95 | 6.77930767 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.08 | 12.06 | 0.00875751 | 34241.7 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.864138 | 7.05804718 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 2.11741416 | 1.759241 | 15.36 | 13.44 | 0.00881395 | 37730.5 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 1.19517000 | 67.9367 | 21.00 | 0.00809461 | 21.00 | 0.00809461 | 52.2955 | 26924.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 5493.67 | 0.00 | 0.00 |
CORE_MID | 4923.50 | 170.17 | 0.00 |
CORE_TOP | 4454.83 | 628.67 | 0.83 |
PERIMETER_TOP_ZN_3 | 4490.67 | 1324.33 | 431.50 |
PERIMETER_TOP_ZN_2 | 4727.67 | 1235.50 | 500.50 |
PERIMETER_TOP_ZN_1 | 4870.33 | 1134.67 | 503.17 |
PERIMETER_TOP_ZN_4 | 4552.17 | 1409.17 | 462.17 |
PERIMETER_BOT_ZN_3 | 4973.83 | 541.17 | 251.67 |
PERIMETER_BOT_ZN_2 | 5223.67 | 575.83 | 365.83 |
PERIMETER_BOT_ZN_1 | 5362.83 | 1212.17 | 1006.17 |
PERIMETER_BOT_ZN_4 | 5167.67 | 614.17 | 349.83 |
PERIMETER_MID_ZN_3 | 4785.00 | 867.67 | 392.00 |
PERIMETER_MID_ZN_2 | 4120.50 | 893.50 | 456.17 |
PERIMETER_MID_ZN_1 | 5151.83 | 751.50 | 472.00 |
PERIMETER_MID_ZN_4 | 4869.17 | 967.00 | 428.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5673.33 | 2337.17 | 1289.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 2.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 86.33 | 0.00 | 55.83 |
PERIMETER_TOP_ZN_2 | 0.00 | 106.17 | 0.00 | 80.33 |
PERIMETER_TOP_ZN_1 | 0.00 | 102.50 | 0.00 | 76.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 98.50 | 0.00 | 62.67 |
PERIMETER_BOT_ZN_3 | 0.00 | 51.83 | 0.00 | 36.50 |
PERIMETER_BOT_ZN_2 | 0.00 | 90.67 | 0.00 | 70.17 |
PERIMETER_BOT_ZN_1 | 0.67 | 429.67 | 0.67 | 404.83 |
PERIMETER_BOT_ZN_4 | 0.00 | 87.83 | 0.00 | 51.50 |
PERIMETER_MID_ZN_3 | 0.00 | 62.17 | 0.00 | 45.17 |
PERIMETER_MID_ZN_2 | 0.00 | 87.00 | 0.00 | 73.83 |
PERIMETER_MID_ZN_1 | 0.00 | 86.67 | 0.00 | 70.50 |
PERIMETER_MID_ZN_4 | 0.00 | 76.17 | 0.00 | 51.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.67 | 622.33 | 0.67 | 542.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.84 | 52.94 | 2698.04 | 0.483 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.84 | 52.94 | 2698.04 | 0.433 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.84 | 52.94 | 2698.04 | 0.425 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.608 | 0.072 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.761 | 0.076 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.740 | 0.072 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.774 | 0.076 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.517 | 0.038 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.649 | 0.040 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.726 | 1.258 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.647 | 0.040 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.605 | 0.060 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.717 | 0.066 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.736 | 0.060 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.764 | 0.063 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.56 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.30 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 8483342.82 | 0.00 | 8483342.82 | 0.00 | 8483342.82 | 13393058.27 | 7336.03 | 110.93 | 1313.03 | 655.57 |
CORE_MID | 7451629.65 | 0.00 | 7451629.65 | 0.00 | 7451629.65 | 13393058.27 | 8462.47 | 44.66 | 252.86 | 496.14 |
CORE_TOP | 7367705.38 | 0.00 | 7367705.38 | 0.00 | 7367705.38 | 13393058.27 | 8645.93 | 23.81 | 90.26 | 535.97 |
PERIMETER_TOP_ZN_3 | 2174829.71 | 0.00 | 2174829.71 | 413457.77 | 2588287.49 | 2823374.22 | 3696.36 | 126.91 | 4936.73 | 535.97 |
PERIMETER_TOP_ZN_2 | 1717430.41 | 0.00 | 1717430.41 | 275636.86 | 1993067.27 | 1787429.43 | 3162.79 | 8.64 | 5588.57 | 535.97 |
PERIMETER_TOP_ZN_1 | 2624850.19 | 0.00 | 2624850.19 | 413457.77 | 3038307.96 | 2823374.22 | 3180.11 | 13.36 | 5566.53 | 535.97 |
PERIMETER_TOP_ZN_4 | 1766880.66 | 0.00 | 1766880.66 | 275636.86 | 2042517.52 | 1787312.18 | 3243.63 | 32.71 | 5483.66 | 535.97 |
PERIMETER_BOT_ZN_3 | 1898769.20 | 0.00 | 1898769.20 | 219835.62 | 2118604.81 | 2823374.22 | 6397.12 | 127.24 | 2235.65 | 655.57 |
PERIMETER_BOT_ZN_2 | 1503515.91 | 0.00 | 1503515.91 | 146556.20 | 1650072.11 | 1787429.43 | 3413.41 | 118.77 | 5227.83 | 655.57 |
PERIMETER_BOT_ZN_1 | 2589992.36 | 0.00 | 2589992.36 | 4198137.27 | 6788129.63 | 2823374.22 | 3632.37 | 945.97 | 4181.66 | 655.57 |
PERIMETER_BOT_ZN_4 | 1512564.51 | 0.00 | 1512564.51 | 146556.20 | 1659120.71 | 1787312.18 | 3742.17 | 87.73 | 4930.10 | 655.57 |
PERIMETER_MID_ZN_3 | 2137093.52 | 0.00 | 2137093.52 | 344173.66 | 2481267.18 | 2823374.22 | 5275.93 | 94.58 | 3389.49 | 496.14 |
PERIMETER_MID_ZN_2 | 1681016.51 | 0.00 | 1681016.51 | 229447.73 | 1910464.24 | 1787429.43 | 3255.26 | 23.99 | 5480.75 | 1405.14 |
PERIMETER_MID_ZN_1 | 2578992.01 | 0.00 | 2578992.01 | 344173.66 | 2923165.67 | 2823374.22 | 3290.93 | 47.17 | 5421.90 | 496.14 |
PERIMETER_MID_ZN_4 | 1722940.77 | 0.00 | 1722940.77 | 229447.73 | 1952388.49 | 1787312.18 | 3417.49 | 38.79 | 5303.72 | 496.14 |
Total Facility | 47211553.62 | 0.00 | 47211553.62 | 7236517.31 | 54448070.93 | 67843644.98 | 8760.00 | 1660.54 | 6105.52 | 1774.21 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3506 | 0.0000 | 0.3506 | 0.0000 | 0.3506 | 0.4247 | 4540.44 | 110.49 | 1292.06 |
CORE_MID | 0.3144 | 0.0000 | 0.3144 | 0.0000 | 0.3144 | 0.4247 | 5651.89 | 44.40 | 246.70 |
CORE_TOP | 0.3087 | 0.0000 | 0.3087 | 0.0000 | 0.3087 | 0.4247 | 5831.68 | 23.69 | 87.62 |
PERIMETER_TOP_ZN_3 | 0.0928 | 0.0000 | 0.0928 | 0.0110 | 0.1038 | 0.0895 | 1410.53 | 123.12 | 4409.36 |
PERIMETER_TOP_ZN_2 | 0.0736 | 0.0000 | 0.0736 | 0.0073 | 0.0809 | 0.0567 | 880.08 | 8.53 | 5054.39 |
PERIMETER_TOP_ZN_1 | 0.1131 | 0.0000 | 0.1131 | 0.0110 | 0.1241 | 0.0895 | 897.36 | 12.87 | 5032.77 |
PERIMETER_TOP_ZN_4 | 0.0748 | 0.0000 | 0.0748 | 0.0073 | 0.0822 | 0.0567 | 961.93 | 32.47 | 4948.60 |
PERIMETER_BOT_ZN_3 | 0.0790 | 0.0000 | 0.0790 | 0.0058 | 0.0848 | 0.0895 | 3626.78 | 124.16 | 2192.06 |
PERIMETER_BOT_ZN_2 | 0.0628 | 0.0000 | 0.0628 | 0.0039 | 0.0667 | 0.0567 | 1239.33 | 116.40 | 4587.28 |
PERIMETER_BOT_ZN_1 | 0.1107 | 0.0000 | 0.1107 | 0.1918 | 0.3025 | 0.0895 | 1437.44 | 429.74 | 4075.81 |
PERIMETER_BOT_ZN_4 | 0.0626 | 0.0000 | 0.0626 | 0.0039 | 0.0664 | 0.0567 | 1572.73 | 86.53 | 4283.75 |
PERIMETER_MID_ZN_3 | 0.0923 | 0.0000 | 0.0923 | 0.0091 | 0.1014 | 0.0895 | 2521.41 | 92.32 | 3329.27 |
PERIMETER_MID_ZN_2 | 0.0692 | 0.0000 | 0.0692 | 0.0064 | 0.0757 | 0.0567 | 897.34 | 15.35 | 4121.31 |
PERIMETER_MID_ZN_1 | 0.1125 | 0.0000 | 0.1125 | 0.0091 | 0.1216 | 0.0895 | 961.86 | 40.87 | 4940.27 |
PERIMETER_MID_ZN_4 | 0.0739 | 0.0000 | 0.0739 | 0.0061 | 0.0800 | 0.0567 | 1094.22 | 38.51 | 4810.27 |
Total Facility | 1.9910 | 0.0000 | 1.9910 | 0.2728 | 2.2638 | 2.1513 | 5943.00 | 1129.43 | 5240.31 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 23161128.59 | 0.00 | 23161128.59 | 22614548.33 | 3001.59 | 0.00 | 5758.41 | 655.57 |
PACU_VAV_MID | 22557781.44 | 0.00 | 22557781.44 | 22614548.33 | 3189.53 | 0.00 | 5570.48 | 496.14 |
PACU_VAV_TOP | 22673680.34 | 0.00 | 22673680.34 | 22614548.33 | 3146.46 | 0.00 | 5613.54 | 535.97 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9643 | 0.0000 | 0.9643 | 0.7171 | 840.16 | 0.00 | 5102.84 |
PACU_VAV_MID | 0.9642 | 0.0000 | 0.9642 | 0.7171 | 868.66 | 0.00 | 5074.34 |
PACU_VAV_TOP | 0.9606 | 0.0000 | 0.9606 | 0.7171 | 865.44 | 0.00 | 5077.56 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5758.41 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5570.48 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5613.54 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1232 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1294 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1245 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 824 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2201.72 | 15539.06 | 30-APR-17:20 | 219264.18 | 10-AUG-15:40 |
Electricity:Building | 1042.10 | 15341.49 | 01-JAN-08:40 | 74697.72 | 15-MAR-07:10 |
Electricity:Zone:CORE_BOTTOM | 310.83 | 4652.71 | 01-JAN-00:10 | 24063.48 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1042.10 | 15341.49 | 01-JAN-08:40 | 74697.72 | 15-MAR-07:10 |
InteriorLights:Electricity | 280.06 | 1316.11 | 01-JAN-08:40 | 27135.45 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 280.06 | 1316.11 | 01-JAN-08:40 | 27135.45 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity | 280.06 | 1316.11 | 01-JAN-08:40 | 27135.45 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 280.06 | 1316.11 | 01-JAN-08:40 | 27135.45 | 15-MAR-07:10 |
Electricity:Zone:CORE_MID | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 35.85 | 541.99 | 01-JAN-08:30 | 2581.32 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.16 | 40.03 | 01-JAN-08:30 | 1075.43 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.16 | 40.03 | 01-JAN-08:30 | 1075.43 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 22.70 | 343.10 | 01-JAN-07:50 | 1626.66 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.80 | 25.34 | 01-JAN-07:50 | 673.37 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.80 | 25.34 | 01-JAN-07:50 | 673.37 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 35.81 | 541.99 | 01-JAN-07:50 | 2579.46 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.13 | 40.03 | 01-JAN-07:50 | 1073.58 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.13 | 40.03 | 01-JAN-07:50 | 1073.58 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 22.69 | 343.10 | 01-JAN-08:40 | 1637.23 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.79 | 25.34 | 01-JAN-08:40 | 683.94 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.79 | 25.34 | 01-JAN-08:40 | 683.94 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 35.84 | 541.99 | 01-JAN-08:20 | 2577.25 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.15 | 40.03 | 01-JAN-08:20 | 1071.36 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.15 | 40.03 | 01-JAN-08:20 | 1071.36 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 22.69 | 343.10 | 01-JAN-07:50 | 1624.26 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.80 | 25.34 | 01-JAN-07:50 | 670.97 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.80 | 25.34 | 01-JAN-07:50 | 670.97 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 35.81 | 541.99 | 01-JAN-07:50 | 2575.29 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.12 | 40.03 | 01-JAN-07:50 | 1069.41 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.12 | 40.03 | 01-JAN-07:50 | 1069.41 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 22.68 | 343.10 | 01-JAN-08:40 | 1635.35 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.79 | 25.34 | 01-JAN-08:40 | 682.06 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.79 | 25.34 | 01-JAN-08:40 | 682.06 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 35.85 | 541.99 | 01-JAN-08:30 | 2581.31 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.16 | 40.03 | 01-JAN-08:30 | 1075.42 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.16 | 40.03 | 01-JAN-08:30 | 1075.42 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 22.70 | 343.10 | 01-JAN-07:50 | 1626.66 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.80 | 25.34 | 01-JAN-07:50 | 673.37 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.80 | 25.34 | 01-JAN-07:50 | 673.37 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 35.81 | 541.99 | 01-JAN-07:50 | 2579.45 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.13 | 40.03 | 01-JAN-07:50 | 1073.57 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.13 | 40.03 | 01-JAN-07:50 | 1073.57 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 22.69 | 343.10 | 01-JAN-08:40 | 1637.23 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.79 | 25.34 | 01-JAN-08:40 | 683.94 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.79 | 25.34 | 01-JAN-08:40 | 683.94 | 14-MAR-07:10 |
InteriorEquipment:Electricity | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 247.34 | 4344.73 | 01-JAN-00:10 | 18520.31 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 1087.62 | 197.13 | 01-JAN-00:10 | 151805.11 | 10-AUG-15:40 |
ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 926.85 | 15-MAR-07:20 |
Transformer:ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 926.85 | 15-MAR-07:20 |
ElectricityPurchased:Facility | 2201.72 | 15539.06 | 02-JUL-17:30 | 219264.18 | 10-AUG-15:40 |
ElectricityPurchased:Plant | 2201.72 | 15539.06 | 02-JUL-17:30 | 219264.18 | 10-AUG-15:40 |
Cogeneration:ElectricityPurchased | 2201.72 | 15539.06 | 02-JUL-17:30 | 219264.18 | 10-AUG-15:40 |
General:Cogeneration:ElectricityPurchased | 2201.72 | 15539.06 | 02-JUL-17:30 | 219264.18 | 10-AUG-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2201.72 | 15539.06 | 02-JUL-17:30 | 219264.18 | 10-AUG-15:40 |
ElectricityNet:Plant | 2201.72 | 15539.06 | 02-JUL-17:30 | 219264.18 | 10-AUG-15:40 |
Cogeneration:ElectricityNet | 2201.72 | 15539.06 | 02-JUL-17:30 | 219264.18 | 10-AUG-15:40 |
General:Cogeneration:ElectricityNet | 2201.72 | 15539.06 | 02-JUL-17:30 | 219264.18 | 10-AUG-15:40 |
Heating:Electricity | 0.41 | 0.00 | 01-JAN-00:10 | 6233.84 | 20-JAN-07:30 |
General:Heating:Electricity | 0.41 | 0.00 | 01-JAN-00:10 | 6233.84 | 20-JAN-07:30 |
Fans:Electricity | 174.30 | 0.00 | 01-JAN-00:10 | 26138.50 | 05-SEP-15:30 |
General:Fans:Electricity | 174.30 | 0.00 | 01-JAN-00:10 | 26138.50 | 05-SEP-15:30 |
ExteriorLights:Electricity | 71.98 | 0.00 | 01-JAN-07:10 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 71.98 | 0.00 | 01-JAN-07:10 | 5557.43 | 01-JAN-06:10 |
Cooling:Electricity | 899.93 | 0.00 | 01-JAN-00:10 | 127061.43 | 10-AUG-15:40 |
General:Cooling:Electricity | 899.93 | 0.00 | 01-JAN-00:10 | 127061.43 | 10-AUG-15:40 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 28-APR-12:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 28-APR-12:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 28-APR-12:10 |
WIRED_LTG_ELECTRICITY | 7.87 | 0.00 | 01-JAN-00:10 | 762.51 | 15-MAR-07:20 |
WIRED_INT_EQUIP | 641.94 | 12061.80 | 01-JAN-00:10 | 36271.65 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 85.60 | 1156.00 | 26-APR-12:10 | 8797.37 | 10-JAN-12:20 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 85.60 | 1156.00 | 26-APR-12:10 | 8797.37 | 10-JAN-12:20 |
WaterSystems:NaturalGas | 85.60 | 1156.00 | 26-APR-12:10 | 8797.37 | 10-JAN-12:20 |
Water Heater:WaterSystems:NaturalGas | 85.60 | 1156.00 | 26-APR-12:10 | 8797.37 | 10-JAN-12:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 5233.62 | 0.00 | 01-JAN-00:10 | 555137.87 | 10-AUG-16:00 |
EnergyTransfer:Building | 1981.16 | 0.00 | 01-JAN-00:10 | 193750.36 | 05-SEP-14:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 341.34 | 0.00 | 01-JAN-00:10 | 27541.86 | 02-JAN-09:00 |
Heating:EnergyTransfer | 2.41 | 0.00 | 01-JAN-00:10 | 6008.49 | 03-JAN-07:50 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 2.41 | 0.00 | 01-JAN-00:10 | 6008.49 | 03-JAN-07:50 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1978.75 | 0.00 | 01-JAN-00:10 | 193750.36 | 05-SEP-14:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 341.34 | 0.00 | 01-JAN-00:10 | 27541.86 | 02-JAN-09:00 |
General:Cooling:EnergyTransfer | 1978.75 | 0.00 | 01-JAN-00:10 | 193750.36 | 05-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 341.34 | 0.00 | 01-JAN-00:10 | 27541.86 | 02-JAN-09:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 96.15 | 0.00 | 01-JAN-00:10 | 15714.88 | 16-AUG-13:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.42 | 0.00 | 01-JAN-00:10 | 3237.28 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.42 | 0.00 | 01-JAN-00:10 | 3237.28 | 03-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 94.73 | 0.00 | 01-JAN-00:10 | 15714.88 | 16-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 94.73 | 0.00 | 01-JAN-00:10 | 15714.88 | 16-AUG-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 53.85 | 0.00 | 01-JAN-00:10 | 6983.50 | 05-SEP-15:30 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.29 | 0.00 | 01-JAN-00:10 | 1479.91 | 01-JAN-13:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.29 | 0.00 | 01-JAN-00:10 | 1479.91 | 01-JAN-13:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 53.56 | 0.00 | 01-JAN-00:10 | 6983.50 | 05-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 53.56 | 0.00 | 01-JAN-00:10 | 6983.50 | 05-SEP-15:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 61.28 | 0.00 | 01-JAN-00:10 | 7318.66 | 05-SEP-07:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.45 | 0.00 | 01-JAN-00:10 | 1402.40 | 22-JAN-11:50 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.45 | 0.00 | 01-JAN-00:10 | 1402.40 | 22-JAN-11:50 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 60.83 | 0.00 | 01-JAN-00:10 | 7318.66 | 05-SEP-07:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 60.83 | 0.00 | 01-JAN-00:10 | 7318.66 | 05-SEP-07:10 |
EnergyTransfer:Zone:CORE_MID | 245.01 | 0.00 | 01-JAN-00:10 | 20587.13 | 05-SEP-07:40 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 245.01 | 0.00 | 01-JAN-00:10 | 20587.13 | 05-SEP-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 245.01 | 0.00 | 01-JAN-00:10 | 20587.13 | 05-SEP-07:40 |
EnergyTransfer:Zone:CORE_TOP | 256.83 | 0.00 | 01-JAN-00:10 | 23127.54 | 05-SEP-13:40 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 256.83 | 0.00 | 01-JAN-00:10 | 23127.54 | 05-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 256.83 | 0.00 | 01-JAN-00:10 | 23127.54 | 05-SEP-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 82.19 | 0.00 | 01-JAN-00:10 | 9451.13 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 82.19 | 0.00 | 01-JAN-00:10 | 9451.13 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 82.19 | 0.00 | 01-JAN-00:10 | 9451.13 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 64.65 | 0.00 | 01-JAN-00:10 | 8022.02 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 26.70 | 20-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 26.70 | 20-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 64.65 | 0.00 | 01-JAN-00:10 | 8022.02 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 64.65 | 0.00 | 01-JAN-00:10 | 8022.02 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 98.73 | 0.00 | 01-JAN-00:10 | 11298.12 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 98.73 | 0.00 | 01-JAN-00:10 | 11298.12 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 98.73 | 0.00 | 01-JAN-00:10 | 11298.12 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 64.87 | 0.00 | 01-JAN-00:10 | 8254.38 | 09-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 200.06 | 20-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 200.06 | 20-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 64.87 | 0.00 | 01-JAN-00:10 | 8254.38 | 09-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 64.87 | 0.00 | 01-JAN-00:10 | 8254.38 | 09-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 81.29 | 0.00 | 01-JAN-00:10 | 8878.83 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 81.29 | 0.00 | 01-JAN-00:10 | 8878.83 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 81.29 | 0.00 | 01-JAN-00:10 | 8878.83 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 64.45 | 0.00 | 01-JAN-00:10 | 7404.46 | 31-JUL-10:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 64.45 | 0.00 | 01-JAN-00:10 | 7404.46 | 31-JUL-10:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 64.45 | 0.00 | 01-JAN-00:10 | 7404.46 | 31-JUL-10:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 119.60 | 0.00 | 01-JAN-00:10 | 18294.62 | 16-AUG-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.26 | 0.00 | 01-JAN-00:10 | 4496.84 | 04-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.26 | 0.00 | 01-JAN-00:10 | 4496.84 | 04-JAN-07:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 119.34 | 0.00 | 01-JAN-00:10 | 18294.62 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 119.34 | 0.00 | 01-JAN-00:10 | 18294.62 | 16-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 63.75 | 0.00 | 01-JAN-00:10 | 7455.13 | 05-SEP-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 63.75 | 0.00 | 01-JAN-00:10 | 7455.13 | 05-SEP-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 63.75 | 0.00 | 01-JAN-00:10 | 7455.13 | 05-SEP-15:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 76.07 | 0.00 | 01-JAN-00:10 | 8264.55 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 76.07 | 0.00 | 01-JAN-00:10 | 8264.55 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 76.07 | 0.00 | 01-JAN-00:10 | 8264.55 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 59.40 | 0.00 | 01-JAN-00:10 | 7386.05 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 59.40 | 0.00 | 01-JAN-00:10 | 7386.05 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 59.40 | 0.00 | 01-JAN-00:10 | 7386.05 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 91.80 | 0.00 | 01-JAN-00:10 | 10350.57 | 13-NOV-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 91.80 | 0.00 | 01-JAN-00:10 | 10350.57 | 13-NOV-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 91.80 | 0.00 | 01-JAN-00:10 | 10350.57 | 13-NOV-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 59.90 | 0.00 | 01-JAN-00:10 | 7433.57 | 31-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 59.90 | 0.00 | 01-JAN-00:10 | 7433.57 | 31-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 59.90 | 0.00 | 01-JAN-00:10 | 7433.57 | 31-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 31.56 | 0.00 | 01-JAN-00:10 | 4393.38 | 12-JAN-12:40 |
PlantLoopHeatingDemand:Plant | 31.56 | 0.00 | 01-JAN-00:10 | 4393.38 | 12-JAN-12:40 |
WaterSystems:PlantLoopHeatingDemand | 31.56 | 0.00 | 01-JAN-00:10 | 4393.38 | 12-JAN-12:40 |
General:WaterSystems:PlantLoopHeatingDemand | 31.56 | 0.00 | 01-JAN-00:10 | 4393.38 | 12-JAN-12:40 |
EnergyTransfer:HVAC | 3220.91 | 0.00 | 01-JAN-00:10 | 370502.48 | 10-AUG-16:00 |
HeatingCoils:EnergyTransfer | 0.41 | 0.00 | 01-JAN-00:10 | 6233.84 | 20-JAN-07:30 |
CoolingCoils:EnergyTransfer | 3220.49 | 0.00 | 01-JAN-00:10 | 370502.48 | 10-AUG-16:00 |
EnergyTransfer:Plant | 31.56 | 0.00 | 01-JAN-00:10 | 4393.38 | 12-JAN-12:40 |
WaterSystems:EnergyTransfer | 31.56 | 0.00 | 01-JAN-00:10 | 4393.38 | 12-JAN-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 31.56 | 0.00 | 01-JAN-00:10 | 4393.38 | 12-JAN-12:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -341.347 | 0.000 | 0.000 | 32.669 | 63.485 | 247.342 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -2.149 |
CORE_MID | 0.000 | 0.000 | 0.000 | -245.008 | 0.000 | 0.000 | 32.721 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 22.201 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -256.836 | 0.000 | 0.000 | 32.805 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 33.946 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.000 | -82.190 | 0.000 | 0.000 | 6.939 | 9.160 | 26.688 | 36.391 | 0.000 | 2.201 | 8.684 | 0.000 | -7.254 | 0.000 | -0.618 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -64.653 | 0.000 | 0.000 | 4.381 | 5.801 | 16.895 | 37.271 | 0.000 | 1.462 | 3.869 | 0.000 | -4.601 | 0.000 | -0.425 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -98.725 | 0.000 | 0.000 | 6.917 | 9.125 | 26.688 | 58.287 | 0.000 | 2.179 | 3.483 | 0.000 | -7.267 | 0.000 | -0.688 | -0.000 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.000 | -64.866 | 0.000 | 0.000 | 4.409 | 5.792 | 16.895 | 37.872 | 0.000 | 1.466 | 3.772 | 0.000 | -4.913 | 0.000 | -0.426 | -0.001 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -81.293 | 0.000 | 0.000 | 6.895 | 9.150 | 26.688 | 36.208 | 0.000 | 1.190 | 9.655 | 0.000 | -8.112 | 0.000 | -0.382 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -64.453 | 0.000 | 0.000 | 4.361 | 5.796 | 16.895 | 37.139 | 0.000 | 0.783 | 4.951 | 0.000 | -5.208 | 0.000 | -0.265 | -0.001 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.260 | -119.338 | 0.000 | 0.000 | 6.834 | 9.119 | 26.688 | 57.940 | 0.000 | 26.865 | 4.453 | 0.000 | -8.267 | 0.000 | -4.555 | -0.002 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -63.752 | 0.000 | 0.000 | 4.365 | 5.786 | 16.895 | 37.735 | 0.000 | 0.779 | 4.073 | 0.000 | -5.613 | 0.000 | -0.269 | -0.001 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -76.066 | 0.000 | 0.000 | 6.903 | 9.160 | 26.688 | 36.499 | 0.000 | 1.839 | 3.389 | 0.000 | -7.836 | 0.000 | -0.575 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -59.395 | 0.000 | 0.000 | 3.222 | 5.801 | 16.895 | 37.358 | 0.000 | 1.223 | 0.209 | 0.000 | -4.922 | 0.000 | -0.390 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -91.804 | 0.000 | 0.000 | 6.891 | 9.125 | 26.688 | 58.432 | 0.000 | 1.817 | 0.002 | 0.000 | -7.782 | 0.000 | -0.629 | -2.739 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -59.894 | 0.000 | 0.000 | 4.377 | 5.792 | 16.895 | 37.946 | 0.000 | 1.218 | 0.000 | 0.000 | -5.300 | 0.000 | -0.395 | -0.638 |
TOPFLOOR_PLENUM | 1.417 | -94.734 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.987 | 91.230 | 0.000 | 0.000 | 0.000 | -0.899 | 0.000 |
MIDFLOOR_PLENUM | 0.287 | -53.558 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.911 | 51.352 | 0.000 | 0.000 | 0.000 | -0.993 | 0.000 |
FIRSTFLOOR_PLENUM | 0.446 | -60.834 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.257 | 58.957 | 0.000 | 0.000 | 0.000 | -0.827 | 0.000 |
Total Facility | 2.150 | -209.126 | 0.260 | -1769.621 | 0.000 | 0.000 | 164.689 | 280.063 | 762.041 | 509.077 | 0.000 | 51.177 | 304.228 | 0.000 | -77.073 | 0.000 | -12.336 | -5.534 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:02 | 0.00 | 0.00 | 0.00 | -46815.29 | 0.00 | 0.00 | 0.00 | 615.87 | 5138.45 | 0.00 | 0.00 | 0.00 | 41060.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 13-NOV-05:02 | 0.00 | 0.00 | 0.00 | -35483.42 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 31692.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 01-MAY-04:02 | 0.00 | 0.00 | 0.00 | -39297.70 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 35506.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 04-SEP-15:31 | 0.00 | 0.00 | 0.00 | -16204.16 | 0.00 | 0.00 | 23.58 | 40.03 | 501.96 | 3288.65 | 0.00 | 586.63 | 11763.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-SEP-10:12 | 0.00 | 0.00 | 0.00 | -13463.61 | 0.00 | 0.00 | 13.96 | 25.34 | 317.77 | 4710.39 | 0.00 | 255.89 | 8140.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 12-NOV-13:22 | 0.00 | 0.00 | 0.00 | -18521.38 | 0.00 | 0.00 | 24.28 | 40.03 | 501.96 | 7488.08 | 0.00 | 98.45 | 10368.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 04-SEP-15:31 | 0.00 | 0.00 | 0.00 | -14915.12 | 0.00 | 0.00 | 12.18 | 25.34 | 317.76 | 5827.65 | 0.00 | 377.28 | 8354.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 30-JUL-14:21 | 0.00 | 0.00 | 0.00 | -13403.09 | 0.00 | 0.00 | 25.74 | 40.03 | 501.96 | 4207.83 | 0.00 | 515.01 | 8112.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 23-JUL-10:02 | 0.00 | 0.00 | 0.00 | -11629.50 | 0.00 | 0.00 | 15.44 | 25.34 | 317.77 | 5392.01 | 0.00 | 178.08 | 5700.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 16-AUG-12:00 | 0.00 | 0.00 | 0.00 | -18294.26 | 0.00 | 0.00 | 222.07 | 720.41 | 1338.56 | 5822.30 | 0.00 | 18582.27 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8391.36 |
PERIMETER_BOT_ZN_4 | 06-AUG-16:11 | 0.00 | 0.00 | 0.00 | -12113.18 | 0.00 | 0.00 | 14.16 | 25.34 | 317.76 | 5572.63 | 0.00 | 174.62 | 6008.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-SEP-14:41 | 0.00 | 0.00 | 0.00 | -13402.15 | 0.00 | 0.00 | 25.39 | 40.03 | 501.96 | 3715.75 | 0.00 | 509.87 | 8609.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-SEP-10:02 | 0.00 | 0.00 | 0.00 | -12141.84 | 0.00 | 0.00 | 14.66 | 25.34 | 317.77 | 4947.09 | 0.00 | 218.07 | 6618.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 29-OCT-14:02 | 0.00 | 0.00 | 0.00 | -15897.58 | 0.00 | 0.00 | 23.61 | 40.03 | 501.96 | 7098.83 | 0.00 | 248.53 | 7984.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 04-SEP-16:01 | 0.00 | 0.00 | 0.00 | -12804.09 | 0.00 | 0.00 | 13.44 | 25.34 | 317.76 | 5528.44 | 0.00 | 321.77 | 6597.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-12:02 | 0.00 | -15737.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.66 | 15492.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 05-JUL-06:15 | 0.00 | -7417.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.43 | 7377.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 31-JUL-12:09 | 0.00 | -8931.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.34 | 8762.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-MAY-04:02 | 0.00 | 10194.36 | 0.00 | -238326.00 | 0.00 | 0.00 | 0.00 | 3119.77 | 18045.99 | 439.37 | 0.00 | 458.16 | 206068.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 20-JAN-07:03 | 0.00 | 0.00 | 106.82 | 0.00 | 0.00 | 0.00 | 118.08 | 238.87 | 423.69 | 182.15 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -21.26 | -1048.35 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 20-JAN-07:03 | 0.00 | 0.00 | 800.22 | 0.00 | 0.00 | 0.00 | 118.59 | 244.03 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -848.85 | 0.00 | -21.25 | -716.42 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 21-FEB-07:07 | 0.00 | 0.00 | 4518.74 | 0.00 | 0.00 | 0.00 | 168.93 | 305.59 | 669.28 | 0.00 | 0.00 | 0.00 | 4417.69 | 0.00 | -872.42 | 0.00 | -9207.81 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 13-NOV-05:02 | 6691.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -133.00 | -6558.19 |
MIDFLOOR_PLENUM | 27-JUL-04:02 | 3720.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.37 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3764.81 |
FIRSTFLOOR_PLENUM | 02-JAN-05:02 | 5378.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -117.83 | -5260.33 |
Total Facility | 22-SEP-04:02 | -187660.78 | 200411.19 | 0.00 | -200411.19 | 0.00 | 0.00 | 0.00 | 3119.77 | 18045.99 | 0.00 | 0.00 | 412.41 | 167471.02 | 0.00 | -1388.40 | 0.00 | 0.00 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.8672 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.4919 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.2197 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7918 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.0198 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.8641 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.9336 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4092 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.6098 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3882 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.0099 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5147 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8906 | 2.8906 | 0.8007 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1852 | 2.1852 | 0.7736 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5060 | 2.5060 | 0.8119 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9292 | 0.9292 | 0.1858 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7274 | 0.7274 | 0.1455 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0296 | 1.0296 | 0.2059 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8276 | 0.8276 | 0.1655 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7770 | 0.7770 | 0.1686 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6481 | 0.6481 | 0.1296 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8682 | 0.8682 | 0.1736 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6832 | 0.6832 | 0.1366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7770 | 0.7770 | 0.1632 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6676 | 0.6676 | 0.1335 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8731 | 0.8731 | 0.1746 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7167 | 0.7167 | 0.1433 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.8672 | 5.4919 | 5.8672 | 1.4092 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.2197 | 4.7918 | 5.2197 | 1.3882 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.0198 | 5.8641 | 6.0198 | 1.5147 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4453 | 1.4453 | 0.8007 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0926 | 1.0926 | 0.7736 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2530 | 1.2530 | 0.8119 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4646 | 0.4646 | 0.1858 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3637 | 0.3637 | 0.1455 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5148 | 0.5148 | 0.2059 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4138 | 0.4138 | 0.1655 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3885 | 0.3885 | 0.1686 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3241 | 0.3241 | 0.1296 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4341 | 0.4341 | 0.1736 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3416 | 0.3416 | 0.1366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3885 | 0.3885 | 0.1632 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3338 | 0.3338 | 0.1335 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4366 | 0.4366 | 0.1746 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3583 | 0.3583 | 0.1433 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.9336 | 1.4092 | 1.4092 | 1.4092 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.6098 | 1.3882 | 1.3882 | 1.3882 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.0099 | 1.5147 | 1.5147 | 1.5147 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 0.67 |
Number of hours cooling loads not met | 542.17 |
Number of hours not met | 542.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.41 | 6233.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 899.93 | 127061.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 280.06 | 27135.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 71.98 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 641.30 | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 12.98 | 926.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 174.30 | 26138.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 85.60 | 8797.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 762.04 | 2201.72 |
Natural Gas | 0.00 | 85.60 |
Additional | 0.00 | 0.00 |
Total | 762.04 | 2287.32 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 56.21 |
Space Heating | 0.08 |
Space Cooling | 180.63 |
Fans (All) | 34.98 |
Service Water Heating | 0.00 |
Receptacle Equipment | 152.95 |
Miscellaneous (All) | 441.92 |
Subtotal | 441.92 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 17.18 |
Miscellaneous (All) | 17.18 |
Subtotal | 17.18 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.24 |
Space Heating | 0.02 |
Space Cooling | 39.34 |
Fans (All) | 7.62 |
Service Water Heating | 3.74 |
Receptacle Equipment | 33.32 |
Miscellaneous | 3.72 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2429. | 8760. |
BLDG_EQUIP_SCH | 4487. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8233.67 | 526.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8706.00 | 54.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8702.67 | 57.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7843.50 | 916.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7794.50 | 965.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7758.33 | 1001.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7772.67 | 987.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8038.67 | 721.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7802.00 | 958.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7615.33 | 1144.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7733.33 | 1026.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7797.50 | 962.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7725.50 | 1034.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7660.00 | 1100.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7663.17 | 1096.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8006.83 | 753.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8408.17 | 351.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8579.50 | 180.50 | 0.00 | 0.00 | 0.00 |
Min | 7615.33 | 54.00 | 0.00 | 0.00 | 0.00 |
Max | 8706.00 | 1144.67 | 0.00 | 0.00 | 0.00 |
Average | 7991.19 | 768.81 | 0.00 | 0.00 | 0.00 |
Sum | 143841.33 | 13838.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128201.00 | 103.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128297.67 | 6.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128293.00 | 11.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24472.33 | 436.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128297.67 | 436.67 | 0.00 | 0.00 | 0.00 |
Average | 34112.39 | 30.94 | 0.00 | 0.00 | 0.00 |
Sum | 614023.00 | 557.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7144.83 | 1615.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7298.83 | 1461.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7380.67 | 1379.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6404.33 | 2355.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6368.00 | 2392.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6295.67 | 2464.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6406.67 | 2353.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6412.00 | 2348.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6326.17 | 2433.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 5535.33 | 3224.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6335.83 | 2424.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6255.33 | 2504.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6230.50 | 2529.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6124.50 | 2635.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6228.00 | 2532.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 4514.33 | 4245.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 5754.17 | 3005.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 6085.67 | 2674.33 | 0.00 | 0.00 | 0.00 |
Min | 4514.33 | 1379.33 | 0.00 | 0.00 | 0.00 |
Max | 7380.67 | 4245.67 | 0.00 | 0.00 | 0.00 |
Average | 6283.38 | 2476.62 | 0.00 | 0.00 | 0.00 |
Sum | 113100.83 | 44579.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127556.83 | 747.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 127662.33 | 641.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 127559.83 | 744.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24814.50 | 94.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14015.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24822.50 | 86.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24826.33 | 82.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 21492.33 | 3416.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24797.50 | 111.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24802.67 | 106.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 127662.33 | 3416.67 | 0.00 | 0.00 | 0.00 |
Average | 33808.26 | 335.07 | 0.00 | 0.00 | 0.00 |
Sum | 608548.67 | 6031.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244434E+11 | 46813.32 | 02-JAN-05:02 | 13.83 | 11.17 | 0.199446E+10 | 2606.69 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.224019E+11 | 46209.90 | 21-FEB-05:02 | 14.83 | 13.75 | 0.180957E+10 | 2606.76 | 15-FEB-14:09 | 14.83 | 13.75 |
March | 0.272313E+11 | 45251.81 | 27-MAR-04:02 | 22.57 | 14.00 | 0.216052E+10 | 2606.81 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.263373E+11 | 46079.57 | 10-APR-04:02 | 21.60 | 19.29 | 0.191807E+10 | 2606.87 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.307765E+11 | 45261.55 | 02-MAY-04:03 | 23.08 | 20.31 | 0.207775E+10 | 2606.77 | 04-MAY-13:00 | 36.00 | 22.99 |
June | 0.309289E+11 | 44152.01 | 07-JUN-04:02 | 24.83 | 21.13 | 0.207095E+10 | 2606.71 | 02-JUN-13:09 | 24.83 | 21.13 |
July | 0.316400E+11 | 39606.05 | 13-JUL-04:02 | 30.58 | 20.96 | 0.192310E+10 | 2606.85 | 03-JUL-09:20 | 30.58 | 20.96 |
August | 0.339545E+11 | 37162.53 | 31-AUG-04:02 | 28.83 | 25.83 | 0.215814E+10 | 2606.63 | 08-AUG-13:09 | 28.83 | 25.83 |
September | 0.305641E+11 | 42363.79 | 30-SEP-04:03 | 24.52 | 21.72 | 0.191774E+10 | 2606.64 | 26-SEP-09:30 | 24.52 | 21.72 |
October | 0.304197E+11 | 43902.40 | 20-OCT-04:03 | 22.50 | 16.21 | 0.199485E+10 | 2606.62 | 20-OCT-09:00 | 30.40 | 18.49 |
November | 0.278444E+11 | 45711.95 | 27-NOV-05:02 | 18.00 | 16.14 | 0.197546E+10 | 2606.66 | 22-NOV-10:09 | 18.00 | 16.14 |
December | 0.248019E+11 | 45810.49 | 26-DEC-05:02 | 15.83 | 15.83 | 0.192447E+10 | 2606.69 | 08-DEC-10:09 | 15.83 | 15.83 |
Annual Sum or Average | 0.341344E+12 | 0.239251E+11 | ||||||||
Minimum of Months | 0.224019E+11 | 37162.53 | 13.83 | 11.17 | 0.180957E+10 | 2606.62 | 14.83 | 13.75 | ||
Maximum of Months | 0.339545E+11 | 46813.32 | 30.58 | 25.83 | 0.216052E+10 | 2606.87 | 36.42 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242029E+10 | 5863.28 | 23-JAN-14:10 | 27.50 | 16.66 | 0.00 | 0.00 | 01-JAN-00:10 | 27.50 | 16.66 |
February | 0.319171E+10 | 8844.90 | 06-FEB-15:00 | 32.50 | 17.28 | 0.00 | 0.00 | 01-FEB-00:10 | 32.50 | 17.28 |
March | 0.519589E+10 | 12031.74 | 27-MAR-13:10 | 35.83 | 19.71 | 0.00 | 0.00 | 01-MAR-00:10 | 35.83 | 19.71 |
April | 0.694140E+10 | 13375.56 | 28-APR-12:40 | 38.47 | 22.15 | 0.00 | 0.00 | 01-APR-00:10 | 38.47 | 22.15 |
May | 0.108955E+11 | 13925.31 | 10-MAY-14:30 | 40.00 | 20.13 | 0.00 | 0.00 | 01-MAY-00:10 | 40.00 | 20.13 |
June | 0.118346E+11 | 14511.73 | 12-JUN-13:10 | 40.25 | 27.32 | 0.00 | 0.00 | 01-JUN-00:10 | 40.25 | 27.32 |
July | 0.131594E+11 | 15737.99 | 21-JUL-12:02 | 45.38 | 23.17 | 0.00 | 0.00 | 01-JUL-00:10 | 45.38 | 23.17 |
August | 0.137549E+11 | 15714.88 | 16-AUG-13:30 | 44.10 | 25.63 | 0.00 | 0.00 | 01-AUG-00:10 | 44.10 | 25.63 |
September | 0.106249E+11 | 14496.19 | 05-SEP-13:50 | 40.15 | 24.82 | 0.00 | 0.00 | 01-SEP-00:10 | 40.15 | 24.82 |
October | 0.833242E+10 | 12184.77 | 04-OCT-14:00 | 36.00 | 20.88 | 0.00 | 0.00 | 01-OCT-00:10 | 36.00 | 20.88 |
November | 0.537785E+10 | 9983.60 | 06-NOV-14:10 | 32.83 | 20.61 | 0.00 | 0.00 | 01-NOV-00:10 | 32.83 | 20.61 |
December | 0.300496E+10 | 7438.27 | 04-DEC-13:50 | 27.17 | 20.95 | 0.00 | 0.00 | 01-DEC-00:10 | 27.17 | 20.95 |
Annual Sum or Average | 0.947338E+11 | 0.00 | ||||||||
Minimum of Months | 0.242029E+10 | 5863.28 | 27.17 | 16.66 | 0.00 | 0.00 | 27.17 | 16.66 | ||
Maximum of Months | 0.137549E+11 | 15737.99 | 45.38 | 27.32 | 0.00 | 0.00 | 45.38 | 27.32 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154538E+10 | 2248.22 | 31-JAN-15:40 | 22.73 | 16.59 | 0.00 | 0.00 | 01-JAN-00:10 | 22.73 | 16.59 |
February | 0.188713E+10 | 3982.83 | 06-FEB-15:30 | 31.95 | 17.43 | 0.00 | 0.00 | 01-FEB-00:10 | 31.95 | 17.43 |
March | 0.301561E+10 | 5179.45 | 27-MAR-14:50 | 35.00 | 18.94 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 18.94 |
April | 0.383596E+10 | 5302.17 | 24-APR-14:30 | 35.00 | 18.42 | 0.00 | 0.00 | 01-APR-00:10 | 35.00 | 18.42 |
May | 0.594384E+10 | 6266.90 | 22-MAY-12:03 | 38.02 | 22.04 | 0.00 | 0.00 | 01-MAY-00:10 | 38.02 | 22.04 |
June | 0.635158E+10 | 6385.40 | 12-JUN-12:02 | 42.65 | 25.06 | 0.00 | 0.00 | 01-JUN-00:10 | 42.65 | 25.06 |
July | 0.678079E+10 | 7418.65 | 05-JUL-06:15 | 30.13 | 28.32 | 0.00 | 0.00 | 01-JUL-00:10 | 30.13 | 28.32 |
August | 0.722153E+10 | 6919.79 | 21-AUG-06:15 | 30.00 | 28.39 | 0.00 | 0.00 | 01-AUG-00:10 | 30.00 | 28.39 |
September | 0.602818E+10 | 6983.50 | 05-SEP-15:30 | 39.05 | 25.34 | 0.00 | 0.00 | 01-SEP-00:10 | 39.05 | 25.34 |
October | 0.523053E+10 | 6065.91 | 10-OCT-15:20 | 34.70 | 20.18 | 0.00 | 0.00 | 01-OCT-00:10 | 34.70 | 20.18 |
November | 0.366145E+10 | 5170.54 | 13-NOV-15:10 | 32.53 | 19.09 | 0.00 | 0.00 | 01-NOV-00:10 | 32.53 | 19.09 |
December | 0.205606E+10 | 3429.97 | 04-DEC-15:10 | 26.87 | 21.39 | 0.00 | 0.00 | 01-DEC-00:10 | 26.87 | 21.39 |
Annual Sum or Average | 0.535581E+11 | 0.00 | ||||||||
Minimum of Months | 0.154538E+10 | 2248.22 | 22.73 | 16.59 | 0.00 | 0.00 | 22.73 | 16.59 | ||
Maximum of Months | 0.722153E+10 | 7418.65 | 42.65 | 28.39 | 0.00 | 0.00 | 42.65 | 28.39 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.263061E+10 | 3592.20 | 02-JAN-07:07 | 13.00 | 10.98 | 0.00 | 0.00 | 01-JAN-00:10 | 13.00 | 10.98 |
February | 0.275576E+10 | 4818.24 | 06-FEB-13:10 | 30.25 | 18.19 | 0.00 | 0.00 | 01-FEB-00:10 | 30.25 | 18.19 |
March | 0.382891E+10 | 7230.02 | 27-MAR-12:09 | 37.08 | 19.46 | 0.00 | 0.00 | 01-MAR-00:10 | 37.08 | 19.46 |
April | 0.434211E+10 | 6850.63 | 26-APR-12:07 | 38.83 | 18.61 | 0.00 | 0.00 | 01-APR-00:10 | 38.83 | 18.61 |
May | 0.622977E+10 | 8601.02 | 22-MAY-12:06 | 38.02 | 22.04 | 0.00 | 0.00 | 01-MAY-00:10 | 38.02 | 22.04 |
June | 0.660587E+10 | 7972.10 | 15-JUN-12:07 | 39.97 | 20.94 | 0.00 | 0.00 | 01-JUN-00:10 | 39.97 | 20.94 |
July | 0.684429E+10 | 8931.74 | 31-JUL-12:09 | 40.98 | 25.84 | 0.00 | 0.00 | 01-JUL-00:10 | 40.98 | 25.84 |
August | 0.738227E+10 | 8564.94 | 07-AUG-12:09 | 36.98 | 28.67 | 0.00 | 0.00 | 01-AUG-00:10 | 36.98 | 28.67 |
September | 0.642113E+10 | 7930.74 | 12-SEP-12:09 | 38.87 | 25.21 | 0.00 | 0.00 | 01-SEP-00:10 | 38.87 | 25.21 |
October | 0.593650E+10 | 6651.96 | 10-OCT-06:10 | 25.97 | 23.91 | 0.00 | 0.00 | 01-OCT-00:10 | 25.97 | 23.91 |
November | 0.470476E+10 | 5650.19 | 13-NOV-16:10 | 30.00 | 21.15 | 0.00 | 0.00 | 01-NOV-00:10 | 30.00 | 21.15 |
December | 0.315150E+10 | 4845.52 | 04-DEC-13:10 | 27.83 | 21.18 | 0.00 | 0.00 | 01-DEC-00:10 | 27.83 | 21.18 |
Annual Sum or Average | 0.608335E+11 | 0.00 | ||||||||
Minimum of Months | 0.263061E+10 | 3592.20 | 13.00 | 10.98 | 0.00 | 0.00 | 13.00 | 10.98 | ||
Maximum of Months | 0.738227E+10 | 8931.74 | 40.98 | 28.67 | 0.00 | 0.00 | 40.98 | 28.67 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151209E+11 | 31869.53 | 31-JAN-06:03 | 15.90 | 14.14 | 0.198178E+10 | 2606.69 | 17-JAN-10:09 | 15.90 | 14.14 |
February | 0.145023E+11 | 32842.51 | 21-FEB-06:03 | 13.95 | 13.33 | 0.180103E+10 | 2606.73 | 15-FEB-14:09 | 13.95 | 13.33 |
March | 0.184087E+11 | 33928.31 | 27-MAR-04:02 | 22.57 | 14.00 | 0.215492E+10 | 2606.79 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.189535E+11 | 34742.92 | 10-APR-04:02 | 21.60 | 19.29 | 0.191473E+10 | 2606.82 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.233868E+11 | 33992.86 | 02-MAY-04:03 | 23.08 | 20.31 | 0.207560E+10 | 2606.76 | 04-MAY-13:00 | 36.00 | 22.99 |
June | 0.237040E+11 | 33138.87 | 07-JUN-04:02 | 24.83 | 21.13 | 0.206903E+10 | 2606.73 | 02-JUN-13:09 | 24.83 | 21.13 |
July | 0.248988E+11 | 29799.34 | 03-JUL-06:03 | 28.20 | 16.17 | 0.192149E+10 | 2606.83 | 03-JUL-09:09 | 34.37 | 23.66 |
August | 0.261432E+11 | 30330.32 | 07-AUG-06:03 | 31.98 | 22.90 | 0.215708E+10 | 2606.58 | 24-AUG-09:00 | 34.90 | 25.82 |
September | 0.228349E+11 | 32763.62 | 26-SEP-04:02 | 26.97 | 19.72 | 0.191664E+10 | 2606.64 | 26-SEP-09:39 | 35.93 | 21.30 |
October | 0.220683E+11 | 34145.49 | 30-OCT-04:02 | 22.25 | 18.14 | 0.199314E+10 | 2606.62 | 20-OCT-09:39 | 22.25 | 18.14 |
November | 0.190367E+11 | 35479.99 | 13-NOV-05:02 | 21.00 | 17.30 | 0.197211E+10 | 2606.69 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.159482E+11 | 34076.22 | 11-DEC-05:02 | 22.00 | 18.76 | 0.191532E+10 | 2606.66 | 08-DEC-10:09 | 22.00 | 18.76 |
Annual Sum or Average | 0.245006E+12 | 0.238729E+11 | ||||||||
Minimum of Months | 0.145023E+11 | 29799.34 | 13.95 | 13.33 | 0.180103E+10 | 2606.58 | 13.95 | 13.33 | ||
Maximum of Months | 0.261432E+11 | 35479.99 | 31.98 | 22.90 | 0.215708E+10 | 2606.83 | 36.42 | 25.82 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136546E+11 | 15252.69 | 30-JAN-14:50 | 22.17 | 20.62 | 0.195118E+10 | 2606.66 | 24-JAN-10:00 | 22.17 | 20.62 |
February | 0.137467E+11 | 28784.44 | 06-FEB-06:03 | 21.88 | 19.06 | 0.178232E+10 | 2606.74 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.181525E+11 | 35620.25 | 27-MAR-04:02 | 22.57 | 14.00 | 0.214414E+10 | 2606.80 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.196440E+11 | 39076.83 | 24-APR-04:02 | 23.25 | 14.59 | 0.191155E+10 | 2606.82 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.256598E+11 | 39301.60 | 01-MAY-04:02 | 22.02 | 21.72 | 0.207629E+10 | 2606.77 | 08-MAY-13:39 | 35.50 | 23.99 |
June | 0.264931E+11 | 38500.61 | 07-JUN-04:02 | 24.83 | 21.13 | 0.206985E+10 | 2606.81 | 02-JUN-13:09 | 24.83 | 21.13 |
July | 0.285012E+11 | 34260.54 | 31-JUL-06:03 | 30.15 | 26.27 | 0.192323E+10 | 2606.84 | 03-JUL-09:09 | 30.15 | 26.27 |
August | 0.297710E+11 | 34686.87 | 07-AUG-06:03 | 31.98 | 22.90 | 0.215817E+10 | 2606.57 | 24-AUG-09:00 | 34.90 | 25.82 |
September | 0.250327E+11 | 38218.76 | 26-SEP-04:02 | 26.97 | 19.72 | 0.191740E+10 | 2606.65 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.228913E+11 | 39238.57 | 30-OCT-04:02 | 22.25 | 18.14 | 0.199286E+10 | 2606.69 | 30-OCT-09:30 | 29.25 | 20.46 |
November | 0.185085E+11 | 39047.44 | 06-NOV-05:02 | 20.00 | 17.94 | 0.196749E+10 | 2606.68 | 28-NOV-10:00 | 26.00 | 20.50 |
December | 0.147790E+11 | 37198.00 | 11-DEC-06:03 | 21.90 | 19.23 | 0.189498E+10 | 2606.66 | 01-DEC-14:09 | 21.90 | 19.23 |
Annual Sum or Average | 0.256834E+12 | 0.237895E+11 | ||||||||
Minimum of Months | 0.136546E+11 | 15252.69 | 20.00 | 14.00 | 0.178232E+10 | 2606.57 | 21.90 | 18.27 | ||
Maximum of Months | 0.297710E+11 | 39301.60 | 31.98 | 26.27 | 0.215817E+10 | 2606.84 | 36.90 | 26.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.297332E+10 | 4334.72 | 23-JAN-14:10 | 27.50 | 16.66 | 0.399302E+09 | 549.50 | 23-JAN-14:00 | 25.00 | 16.89 |
February | 0.327422E+10 | 6058.61 | 06-FEB-15:00 | 32.50 | 17.28 | 0.369130E+09 | 549.52 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.486070E+10 | 7394.60 | 27-MAR-13:40 | 35.33 | 19.53 | 0.448158E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.599761E+10 | 13304.50 | 30-APR-12:43 | 37.08 | 20.98 | 0.402467E+09 | 549.54 | 28-APR-13:09 | 37.08 | 20.98 |
May | 0.904776E+10 | 16084.87 | 21-MAY-13:12 | 38.00 | 22.80 | 0.438745E+09 | 549.53 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.985019E+10 | 15134.71 | 11-JUN-15:32 | 36.60 | 27.14 | 0.437549E+09 | 549.53 | 02-JUN-13:09 | 36.60 | 27.14 |
July | 0.108228E+11 | 16185.15 | 30-JUL-14:32 | 42.00 | 26.25 | 0.407235E+09 | 549.55 | 03-JUL-09:09 | 42.00 | 26.25 |
August | 0.111584E+11 | 16175.51 | 06-AUG-15:01 | 40.85 | 24.99 | 0.456497E+09 | 549.48 | 04-AUG-13:00 | 40.85 | 24.99 |
September | 0.870091E+10 | 16208.07 | 04-SEP-15:31 | 40.80 | 24.09 | 0.405338E+09 | 549.50 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.710431E+10 | 13766.93 | 09-OCT-14:42 | 37.00 | 20.65 | 0.420755E+09 | 549.51 | 30-OCT-09:30 | 29.25 | 20.46 |
November | 0.501027E+10 | 6816.58 | 20-NOV-05:02 | 26.00 | 18.81 | 0.413703E+09 | 549.50 | 28-NOV-10:00 | 26.00 | 20.50 |
December | 0.339061E+10 | 4843.15 | 11-DEC-14:10 | 26.77 | 18.23 | 0.392756E+09 | 549.50 | 01-DEC-14:09 | 26.77 | 18.23 |
Annual Sum or Average | 0.821911E+11 | 0.499164E+10 | ||||||||
Minimum of Months | 0.297332E+10 | 4334.72 | 26.00 | 16.66 | 0.369130E+09 | 549.48 | 25.00 | 16.89 | ||
Maximum of Months | 0.111584E+11 | 16208.07 | 42.00 | 27.14 | 0.456497E+09 | 549.55 | 42.00 | 27.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244584E+10 | 3168.68 | 24-JAN-11:00 | 24.00 | 17.69 | 0.257502E+09 | 347.88 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.267960E+10 | 4477.60 | 05-FEB-10:48 | 28.72 | 18.70 | 0.236339E+09 | 347.89 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.391239E+10 | 8706.08 | 26-MAR-12:53 | 35.00 | 18.29 | 0.284667E+09 | 347.90 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.492316E+10 | 12421.75 | 23-APR-10:02 | 32.75 | 16.81 | 0.255121E+09 | 347.91 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.714648E+10 | 12623.05 | 21-MAY-09:52 | 37.70 | 19.93 | 0.277846E+09 | 348.01 | 22-MAY-09:39 | 35.80 | 22.83 |
June | 0.749290E+10 | 13010.97 | 18-JUN-09:12 | 35.53 | 24.85 | 0.277002E+09 | 347.90 | 02-JUN-13:09 | 35.53 | 24.85 |
July | 0.817324E+10 | 13427.33 | 23-JUL-10:02 | 40.33 | 23.40 | 0.257843E+09 | 348.08 | 21-JUL-09:39 | 40.33 | 23.40 |
August | 0.859471E+10 | 13453.34 | 13-AUG-10:22 | 38.80 | 25.02 | 0.289012E+09 | 348.00 | 02-AUG-09:30 | 38.80 | 25.02 |
September | 0.686236E+10 | 13471.38 | 04-SEP-10:12 | 38.00 | 23.07 | 0.256668E+09 | 347.88 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.568464E+10 | 10751.13 | 29-OCT-11:32 | 34.13 | 15.87 | 0.266553E+09 | 347.88 | 30-OCT-09:30 | 29.25 | 20.46 |
November | 0.403160E+10 | 7749.16 | 05-NOV-11:13 | 32.87 | 18.22 | 0.262535E+09 | 347.88 | 28-NOV-10:50 | 25.93 | 20.29 |
December | 0.270633E+10 | 3620.91 | 04-DEC-11:00 | 26.00 | 20.51 | 0.251024E+09 | 347.88 | 01-DEC-10:20 | 26.00 | 20.51 |
Annual Sum or Average | 0.646532E+11 | 0.317211E+10 | ||||||||
Minimum of Months | 0.244584E+10 | 3168.68 | 24.00 | 15.87 | 0.236339E+09 | 347.88 | 24.00 | 17.69 | ||
Maximum of Months | 0.859471E+10 | 13471.38 | 40.33 | 25.02 | 0.289012E+09 | 348.08 | 40.33 | 25.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.505899E+10 | 8062.91 | 23-JAN-13:30 | 27.70 | 16.54 | 0.408569E+09 | 549.51 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.517869E+10 | 17972.91 | 05-FEB-13:23 | 31.35 | 19.49 | 0.373295E+09 | 549.54 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.653888E+10 | 17801.92 | 26-MAR-12:53 | 35.00 | 18.29 | 0.449079E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.684295E+10 | 17578.52 | 30-APR-12:43 | 37.08 | 20.98 | 0.402284E+09 | 549.55 | 28-APR-13:09 | 37.08 | 20.98 |
May | 0.914834E+10 | 17766.46 | 21-MAY-13:12 | 38.00 | 22.80 | 0.438542E+09 | 549.53 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.954964E+10 | 14748.92 | 11-JUN-14:52 | 37.00 | 27.77 | 0.437358E+09 | 549.53 | 02-JUN-13:09 | 37.00 | 27.77 |
July | 0.108012E+11 | 17959.83 | 30-JUL-14:32 | 42.00 | 26.25 | 0.407086E+09 | 549.54 | 03-JUL-09:09 | 42.00 | 26.25 |
August | 0.118216E+11 | 17948.65 | 06-AUG-15:01 | 40.85 | 24.99 | 0.456450E+09 | 549.48 | 04-AUG-13:00 | 40.85 | 24.99 |
September | 0.103868E+11 | 18274.35 | 04-SEP-14:12 | 41.00 | 24.86 | 0.405447E+09 | 549.73 | 28-SEP-13:50 | 35.10 | 25.53 |
October | 0.981278E+10 | 18504.59 | 29-OCT-11:32 | 34.13 | 15.87 | 0.421260E+09 | 549.80 | 10-OCT-13:00 | 34.13 | 15.87 |
November | 0.788594E+10 | 18519.42 | 12-NOV-13:22 | 29.65 | 18.98 | 0.415381E+09 | 549.84 | 13-NOV-14:09 | 33.00 | 16.45 |
December | 0.570011E+10 | 18002.21 | 03-DEC-13:13 | 28.87 | 18.94 | 0.398726E+09 | 549.51 | 01-DEC-14:09 | 28.87 | 18.94 |
Annual Sum or Average | 0.987260E+11 | 0.501348E+10 | ||||||||
Minimum of Months | 0.505899E+10 | 8062.91 | 27.70 | 15.87 | 0.373295E+09 | 549.48 | 24.00 | 15.87 | ||
Maximum of Months | 0.118216E+11 | 18519.42 | 42.00 | 27.77 | 0.456450E+09 | 549.84 | 42.00 | 27.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259706E+10 | 3872.43 | 31-JAN-16:20 | 22.73 | 16.79 | 0.248476E+09 | 347.85 | 23-JAN-14:00 | 22.73 | 16.79 |
February | 0.283514E+10 | 8658.36 | 05-FEB-15:23 | 32.00 | 19.15 | 0.230654E+09 | 347.87 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.409407E+10 | 8255.11 | 26-MAR-15:32 | 32.07 | 18.56 | 0.281270E+09 | 347.87 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.482660E+10 | 11840.88 | 09-APR-15:53 | 29.60 | 23.46 | 0.253682E+09 | 347.88 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.696607E+10 | 14250.05 | 21-MAY-15:52 | 37.50 | 23.27 | 0.277513E+09 | 347.88 | 04-MAY-13:00 | 37.50 | 23.27 |
June | 0.743735E+10 | 13993.65 | 18-JUN-15:52 | 36.10 | 27.45 | 0.276870E+09 | 347.87 | 02-JUN-13:09 | 36.10 | 27.45 |
July | 0.813792E+10 | 14587.49 | 30-JUL-14:32 | 42.00 | 26.25 | 0.257663E+09 | 347.88 | 03-JUL-09:09 | 42.00 | 26.25 |
August | 0.852525E+10 | 14781.03 | 06-AUG-15:41 | 40.25 | 25.55 | 0.288878E+09 | 347.84 | 04-AUG-13:00 | 40.25 | 25.55 |
September | 0.681004E+10 | 14920.04 | 04-SEP-15:31 | 40.80 | 24.09 | 0.256499E+09 | 347.86 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.564262E+10 | 14193.93 | 29-OCT-15:32 | 32.00 | 19.85 | 0.265977E+09 | 347.86 | 30-OCT-09:30 | 29.25 | 20.46 |
November | 0.409415E+10 | 10837.10 | 12-NOV-15:23 | 29.05 | 17.71 | 0.260699E+09 | 347.86 | 28-NOV-10:00 | 26.00 | 20.50 |
December | 0.290059E+10 | 4554.77 | 06-DEC-15:30 | 26.85 | 20.67 | 0.245213E+09 | 347.85 | 01-DEC-14:09 | 26.85 | 20.67 |
Annual Sum or Average | 0.648669E+11 | 0.314339E+10 | ||||||||
Minimum of Months | 0.259706E+10 | 3872.43 | 22.73 | 16.79 | 0.230654E+09 | 347.84 | 22.73 | 16.79 | ||
Maximum of Months | 0.852525E+10 | 14920.04 | 42.00 | 27.45 | 0.288878E+09 | 347.88 | 42.00 | 27.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.349051E+10 | 4374.87 | 23-JAN-14:10 | 27.50 | 16.66 | 0.415787E+09 | 549.50 | 17-JAN-10:09 | 27.50 | 16.66 |
February | 0.342906E+10 | 5382.50 | 06-FEB-15:00 | 32.50 | 17.28 | 0.378014E+09 | 549.51 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.457540E+10 | 6185.26 | 27-MAR-13:10 | 35.83 | 19.71 | 0.452664E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.527888E+10 | 6527.79 | 28-APR-12:50 | 37.58 | 22.61 | 0.403376E+09 | 549.54 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.795671E+10 | 13246.04 | 21-MAY-13:32 | 38.00 | 22.80 | 0.438569E+09 | 549.53 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.884459E+10 | 11021.55 | 15-JUN-04:02 | 28.70 | 21.44 | 0.437436E+09 | 549.51 | 02-JUN-13:09 | 28.70 | 21.44 |
July | 0.986132E+10 | 13404.48 | 30-JUL-14:21 | 42.50 | 25.87 | 0.407070E+09 | 549.55 | 03-JUL-09:20 | 42.50 | 25.87 |
August | 0.108272E+11 | 13323.16 | 06-AUG-14:51 | 41.00 | 24.84 | 0.456403E+09 | 549.50 | 04-AUG-13:00 | 41.00 | 24.84 |
September | 0.889349E+10 | 13221.63 | 17-SEP-14:32 | 36.00 | 25.62 | 0.405411E+09 | 549.50 | 26-SEP-09:30 | 35.45 | 21.05 |
October | 0.791249E+10 | 10929.77 | 12-OCT-04:02 | 25.50 | 20.90 | 0.421294E+09 | 549.49 | 20-OCT-09:00 | 30.40 | 18.49 |
November | 0.606396E+10 | 9338.90 | 20-NOV-05:02 | 26.00 | 18.81 | 0.416209E+09 | 549.50 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.415932E+10 | 5647.86 | 11-DEC-07:03 | 21.50 | 18.56 | 0.403615E+09 | 549.50 | 08-DEC-10:09 | 21.50 | 18.56 |
Annual Sum or Average | 0.812930E+11 | 0.503585E+10 | ||||||||
Minimum of Months | 0.342906E+10 | 4374.87 | 21.50 | 16.66 | 0.378014E+09 | 549.49 | 21.50 | 16.66 | ||
Maximum of Months | 0.108272E+11 | 13404.48 | 42.50 | 25.87 | 0.456403E+09 | 549.55 | 42.50 | 25.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.290144E+10 | 3536.35 | 17-JAN-11:10 | 24.17 | 16.24 | 0.264272E+09 | 347.88 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.283026E+10 | 3907.28 | 06-FEB-14:10 | 32.08 | 17.23 | 0.240008E+09 | 347.89 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.372776E+10 | 5706.82 | 27-MAR-10:50 | 37.50 | 18.71 | 0.286931E+09 | 347.90 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.441868E+10 | 8290.72 | 30-APR-12:43 | 37.08 | 20.98 | 0.255740E+09 | 347.91 | 28-APR-13:09 | 37.08 | 20.98 |
May | 0.642402E+10 | 11157.73 | 29-MAY-10:32 | 37.30 | 22.20 | 0.277843E+09 | 348.01 | 22-MAY-09:50 | 37.30 | 22.20 |
June | 0.681160E+10 | 11265.33 | 18-JUN-10:02 | 36.50 | 24.82 | 0.277014E+09 | 347.88 | 27-JUN-13:09 | 38.33 | 27.70 |
July | 0.752839E+10 | 11636.39 | 23-JUL-10:02 | 40.33 | 23.40 | 0.257818E+09 | 347.96 | 03-JUL-09:50 | 40.33 | 23.40 |
August | 0.840985E+10 | 11186.58 | 13-AUG-10:51 | 40.00 | 25.04 | 0.289026E+09 | 347.88 | 04-AUG-13:00 | 40.00 | 25.04 |
September | 0.702547E+10 | 11205.43 | 04-SEP-08:23 | 34.55 | 21.42 | 0.256808E+09 | 347.88 | 26-SEP-09:30 | 35.45 | 21.05 |
October | 0.629374E+10 | 9272.03 | 08-OCT-09:13 | 31.33 | 26.94 | 0.266938E+09 | 347.88 | 20-OCT-09:00 | 30.40 | 18.49 |
November | 0.479524E+10 | 7734.77 | 05-NOV-11:13 | 32.87 | 18.22 | 0.263785E+09 | 347.88 | 22-NOV-10:09 | 23.42 | 16.99 |
December | 0.328647E+10 | 4120.83 | 04-DEC-10:40 | 25.47 | 20.60 | 0.255859E+09 | 347.88 | 08-DEC-10:09 | 22.75 | 18.50 |
Annual Sum or Average | 0.644529E+11 | 0.319204E+10 | ||||||||
Minimum of Months | 0.283026E+10 | 3536.35 | 24.17 | 16.24 | 0.240008E+09 | 347.88 | 22.75 | 16.99 | ||
Maximum of Months | 0.840985E+10 | 11636.39 | 40.33 | 26.94 | 0.289026E+09 | 348.01 | 40.33 | 27.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.509837E+10 | 11237.78 | 23-JAN-13:00 | 27.40 | 16.52 | 0.412911E+09 | 549.52 | 23-JAN-14:30 | 26.50 | 16.81 |
February | 0.519280E+10 | 13060.97 | 07-FEB-13:00 | 31.00 | 20.84 | 0.376471E+09 | 586.74 | 07-FEB-13:09 | 31.00 | 20.70 |
March | 0.676892E+10 | 15280.79 | 27-MAR-12:00 | 37.30 | 19.38 | 0.451047E+09 | 704.44 | 27-MAR-12:09 | 37.08 | 19.46 |
April | 0.746458E+10 | 16623.56 | 28-APR-12:00 | 42.00 | 19.18 | 0.404665E+09 | 780.74 | 28-APR-12:09 | 41.12 | 20.13 |
May | 0.109548E+11 | 16232.41 | 09-MAY-12:00 | 41.00 | 19.42 | 0.445987E+09 | 756.73 | 09-MAY-12:09 | 41.02 | 19.49 |
June | 0.119558E+11 | 17083.14 | 12-JUN-12:00 | 43.00 | 24.56 | 0.447111E+09 | 797.09 | 12-JUN-12:09 | 42.65 | 25.06 |
July | 0.133634E+11 | 17974.35 | 21-JUL-12:00 | 46.00 | 22.01 | 0.417991E+09 | 854.14 | 21-JUL-12:09 | 45.38 | 23.17 |
August | 0.155689E+11 | 18294.62 | 16-AUG-12:00 | 46.00 | 25.38 | 0.471744E+09 | 867.65 | 16-AUG-12:09 | 45.70 | 25.45 |
September | 0.134372E+11 | 16940.50 | 05-SEP-12:00 | 41.00 | 24.24 | 0.417029E+09 | 789.48 | 05-SEP-12:09 | 40.98 | 24.12 |
October | 0.128340E+11 | 15765.06 | 04-OCT-12:00 | 38.00 | 19.81 | 0.429942E+09 | 728.25 | 04-OCT-12:09 | 37.77 | 20.04 |
November | 0.102045E+11 | 15719.46 | 12-NOV-13:22 | 29.65 | 18.98 | 0.419108E+09 | 642.02 | 06-NOV-13:09 | 29.65 | 18.98 |
December | 0.649602E+10 | 15318.23 | 25-DEC-13:43 | 27.08 | 18.31 | 0.402042E+09 | 561.85 | 04-DEC-13:09 | 27.08 | 18.31 |
Annual Sum or Average | 0.119339E+12 | 0.509605E+10 | ||||||||
Minimum of Months | 0.509837E+10 | 11237.78 | 27.08 | 16.52 | 0.376471E+09 | 549.52 | 26.50 | 16.81 | ||
Maximum of Months | 0.155689E+11 | 18294.62 | 46.00 | 25.38 | 0.471744E+09 | 867.65 | 45.70 | 25.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286551E+10 | 3756.03 | 31-JAN-16:30 | 22.80 | 16.92 | 0.262797E+09 | 347.86 | 17-JAN-10:09 | 22.80 | 16.92 |
February | 0.284664E+10 | 4950.10 | 06-FEB-15:30 | 31.95 | 17.43 | 0.239070E+09 | 347.86 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.382547E+10 | 5940.05 | 27-MAR-16:00 | 35.00 | 18.85 | 0.286500E+09 | 347.87 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.427557E+10 | 7739.50 | 30-APR-18:03 | 29.95 | 25.20 | 0.255440E+09 | 347.88 | 28-APR-13:09 | 29.95 | 25.20 |
May | 0.620779E+10 | 11816.06 | 29-MAY-16:31 | 35.70 | 24.12 | 0.277724E+09 | 347.88 | 04-MAY-13:00 | 35.70 | 24.12 |
June | 0.673202E+10 | 10291.67 | 11-JUN-16:12 | 36.60 | 26.54 | 0.276994E+09 | 347.86 | 02-JUN-13:09 | 36.60 | 26.54 |
July | 0.744526E+10 | 12028.28 | 30-JUL-15:01 | 40.45 | 27.73 | 0.257754E+09 | 347.88 | 03-JUL-09:20 | 40.45 | 27.73 |
August | 0.829742E+10 | 12116.13 | 06-AUG-16:11 | 40.07 | 25.84 | 0.289008E+09 | 347.85 | 04-AUG-13:00 | 40.07 | 25.84 |
September | 0.695273E+10 | 12016.75 | 17-SEP-16:32 | 34.47 | 26.91 | 0.256773E+09 | 347.85 | 26-SEP-09:30 | 35.45 | 21.05 |
October | 0.620015E+10 | 11196.08 | 22-OCT-15:32 | 31.60 | 23.78 | 0.266844E+09 | 347.85 | 20-OCT-09:00 | 31.60 | 23.78 |
November | 0.477729E+10 | 9629.57 | 12-NOV-15:23 | 29.05 | 17.71 | 0.263649E+09 | 347.85 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.332591E+10 | 4487.04 | 04-DEC-15:30 | 26.60 | 21.10 | 0.255397E+09 | 347.86 | 08-DEC-10:09 | 22.75 | 18.50 |
Annual Sum or Average | 0.637517E+11 | 0.318795E+10 | ||||||||
Minimum of Months | 0.284664E+10 | 3756.03 | 22.80 | 16.92 | 0.239070E+09 | 347.85 | 22.75 | 16.92 | ||
Maximum of Months | 0.829742E+10 | 12116.13 | 40.45 | 27.73 | 0.289008E+09 | 347.88 | 40.45 | 27.73 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308310E+10 | 4216.07 | 23-JAN-14:10 | 27.50 | 16.66 | 0.412017E+09 | 549.50 | 17-JAN-10:09 | 27.50 | 16.66 |
February | 0.328909E+10 | 5563.12 | 06-FEB-14:50 | 32.42 | 17.27 | 0.376631E+09 | 549.52 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.475734E+10 | 7634.92 | 28-MAR-05:03 | 25.67 | 14.74 | 0.452747E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.563952E+10 | 9686.02 | 17-APR-04:02 | 24.33 | 19.27 | 0.403788E+09 | 549.54 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.819152E+10 | 13234.64 | 21-MAY-13:12 | 38.00 | 22.80 | 0.438818E+09 | 549.53 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.882939E+10 | 12264.16 | 04-JUN-14:32 | 36.67 | 28.36 | 0.437544E+09 | 549.51 | 02-JUN-13:09 | 36.67 | 28.36 |
July | 0.941746E+10 | 13320.27 | 30-JUL-14:32 | 42.00 | 26.25 | 0.407180E+09 | 549.60 | 31-JUL-13:30 | 40.45 | 27.06 |
August | 0.983567E+10 | 13156.10 | 13-AUG-13:13 | 40.47 | 25.37 | 0.456447E+09 | 549.53 | 04-AUG-13:20 | 40.47 | 25.37 |
September | 0.784729E+10 | 13404.63 | 04-SEP-14:41 | 41.00 | 24.39 | 0.405362E+09 | 549.50 | 26-SEP-09:39 | 35.93 | 21.30 |
October | 0.671634E+10 | 13211.19 | 09-OCT-16:32 | 36.27 | 20.22 | 0.421029E+09 | 549.49 | 20-OCT-09:00 | 30.40 | 18.49 |
November | 0.497959E+10 | 9593.68 | 20-NOV-05:02 | 26.00 | 18.81 | 0.415476E+09 | 549.51 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.348087E+10 | 4692.98 | 11-DEC-14:10 | 26.77 | 18.23 | 0.400784E+09 | 549.50 | 01-DEC-14:09 | 26.77 | 18.23 |
Annual Sum or Average | 0.760672E+11 | 0.502782E+10 | ||||||||
Minimum of Months | 0.308310E+10 | 4216.07 | 24.33 | 14.74 | 0.376631E+09 | 549.49 | 25.67 | 16.66 | ||
Maximum of Months | 0.983567E+10 | 13404.63 | 42.00 | 28.36 | 0.456447E+09 | 549.60 | 40.47 | 28.36 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251404E+10 | 3288.91 | 17-JAN-10:00 | 22.80 | 15.94 | 0.193146E+09 | 338.73 | 24-JAN-11:20 | 24.00 | 18.46 |
February | 0.265369E+10 | 3806.55 | 06-FEB-14:00 | 32.00 | 17.22 | 0.176303E+09 | 338.73 | 06-FEB-16:40 | 27.80 | 20.42 |
March | 0.375062E+10 | 6766.24 | 26-MAR-10:33 | 31.67 | 16.41 | 0.211224E+09 | 338.75 | 28-MAR-10:20 | 27.33 | 20.93 |
April | 0.456635E+10 | 11480.00 | 23-APR-10:02 | 32.75 | 16.81 | 0.189167E+09 | 338.74 | 28-APR-12:00 | 36.70 | 22.98 |
May | 0.644152E+10 | 11580.79 | 29-MAY-09:52 | 37.10 | 22.97 | 0.205626E+09 | 339.02 | 08-MAY-10:30 | 37.10 | 22.97 |
June | 0.668940E+10 | 11828.34 | 18-JUN-09:12 | 35.53 | 24.85 | 0.204746E+09 | 338.73 | 02-JUN-12:50 | 35.53 | 24.85 |
July | 0.710436E+10 | 11713.22 | 30-JUL-09:52 | 42.40 | 21.65 | 0.191246E+09 | 339.17 | 31-JUL-10:30 | 40.45 | 24.31 |
August | 0.756372E+10 | 11229.00 | 13-AUG-13:13 | 40.47 | 25.37 | 0.213585E+09 | 339.17 | 30-AUG-10:50 | 42.55 | 23.86 |
September | 0.615849E+10 | 12148.88 | 04-SEP-10:02 | 38.00 | 23.07 | 0.190103E+09 | 338.73 | 26-SEP-07:19 | 27.40 | 17.98 |
October | 0.531842E+10 | 11697.19 | 09-OCT-10:32 | 35.10 | 22.00 | 0.197589E+09 | 338.73 | 30-OCT-07:19 | 23.07 | 18.33 |
November | 0.390575E+10 | 6667.81 | 05-NOV-11:32 | 33.43 | 17.72 | 0.194806E+09 | 338.74 | 06-NOV-08:30 | 25.00 | 20.60 |
December | 0.272931E+10 | 3715.50 | 04-DEC-10:00 | 24.40 | 20.71 | 0.187655E+09 | 338.73 | 20-DEC-13:20 | 24.30 | 20.76 |
Annual Sum or Average | 0.593957E+11 | 0.235520E+10 | ||||||||
Minimum of Months | 0.251404E+10 | 3288.91 | 22.80 | 15.94 | 0.176303E+09 | 338.73 | 23.07 | 17.98 | ||
Maximum of Months | 0.756372E+10 | 12148.88 | 42.40 | 25.37 | 0.213585E+09 | 339.17 | 42.55 | 24.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.521347E+10 | 7907.10 | 23-JAN-13:30 | 27.70 | 16.54 | 0.416445E+09 | 549.51 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.515780E+10 | 15346.51 | 05-FEB-13:32 | 31.43 | 19.44 | 0.378636E+09 | 549.53 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.633488E+10 | 13854.52 | 26-MAR-15:53 | 31.80 | 18.54 | 0.453388E+09 | 549.67 | 27-MAR-13:00 | 35.00 | 19.40 |
April | 0.639047E+10 | 14801.98 | 30-APR-12:43 | 37.08 | 20.98 | 0.403919E+09 | 549.55 | 28-APR-13:09 | 37.08 | 20.98 |
May | 0.825321E+10 | 14825.88 | 21-MAY-13:12 | 38.00 | 22.80 | 0.438712E+09 | 549.54 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.852862E+10 | 13180.61 | 04-JUN-17:52 | 34.00 | 28.58 | 0.437399E+09 | 549.51 | 02-JUN-13:09 | 34.00 | 28.58 |
July | 0.936093E+10 | 14983.01 | 30-JUL-14:32 | 42.00 | 26.25 | 0.407075E+09 | 549.54 | 03-JUL-09:09 | 42.00 | 26.25 |
August | 0.104044E+11 | 14975.87 | 13-AUG-13:13 | 40.47 | 25.37 | 0.456453E+09 | 549.64 | 29-AUG-13:30 | 37.30 | 29.96 |
September | 0.938644E+10 | 15420.86 | 04-SEP-14:41 | 41.00 | 24.39 | 0.405538E+09 | 549.73 | 28-SEP-13:50 | 35.10 | 25.53 |
October | 0.927223E+10 | 15904.63 | 29-OCT-14:02 | 33.67 | 19.63 | 0.421566E+09 | 549.81 | 20-OCT-13:00 | 33.67 | 19.63 |
November | 0.770884E+10 | 15454.27 | 05-NOV-11:32 | 33.43 | 17.72 | 0.416586E+09 | 549.86 | 13-NOV-14:50 | 33.00 | 18.21 |
December | 0.579350E+10 | 15371.38 | 03-DEC-13:23 | 28.40 | 19.50 | 0.403638E+09 | 549.52 | 04-DEC-14:09 | 27.00 | 21.00 |
Annual Sum or Average | 0.918047E+11 | 0.503935E+10 | ||||||||
Minimum of Months | 0.515780E+10 | 7907.10 | 27.70 | 16.54 | 0.378636E+09 | 549.51 | 24.00 | 17.69 | ||
Maximum of Months | 0.104044E+11 | 15904.63 | 42.00 | 28.58 | 0.456453E+09 | 549.86 | 42.00 | 29.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.261083E+10 | 3778.68 | 31-JAN-16:20 | 22.73 | 16.79 | 0.258255E+09 | 347.85 | 17-JAN-10:20 | 22.73 | 16.79 |
February | 0.277847E+10 | 6117.51 | 05-FEB-16:13 | 31.67 | 18.76 | 0.236851E+09 | 347.87 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.393866E+10 | 11455.46 | 26-MAR-15:53 | 31.80 | 18.54 | 0.285640E+09 | 347.87 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.450822E+10 | 10003.15 | 02-APR-16:53 | 30.00 | 18.16 | 0.255272E+09 | 347.88 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.633218E+10 | 12395.73 | 29-MAY-16:31 | 35.70 | 24.12 | 0.277700E+09 | 347.88 | 04-MAY-13:00 | 35.70 | 24.12 |
June | 0.669735E+10 | 12053.77 | 18-JUN-15:52 | 36.10 | 27.45 | 0.276920E+09 | 347.86 | 02-JUN-13:09 | 36.10 | 27.45 |
July | 0.711743E+10 | 12468.94 | 30-JUL-14:32 | 42.00 | 26.25 | 0.257700E+09 | 347.88 | 03-JUL-09:09 | 42.00 | 26.25 |
August | 0.755330E+10 | 12358.96 | 06-AUG-15:52 | 40.10 | 25.68 | 0.288924E+09 | 347.84 | 04-AUG-13:50 | 40.10 | 25.68 |
September | 0.616445E+10 | 12807.36 | 04-SEP-16:01 | 40.58 | 23.84 | 0.256589E+09 | 347.85 | 26-SEP-09:39 | 35.93 | 21.30 |
October | 0.531734E+10 | 12758.40 | 09-OCT-16:32 | 36.27 | 20.22 | 0.266457E+09 | 347.85 | 20-OCT-09:00 | 30.40 | 18.49 |
November | 0.399131E+10 | 10914.07 | 05-NOV-15:32 | 31.60 | 21.44 | 0.262672E+09 | 347.86 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.288551E+10 | 4353.21 | 06-DEC-15:30 | 26.85 | 20.67 | 0.252079E+09 | 347.85 | 01-DEC-14:09 | 26.85 | 20.67 |
Annual Sum or Average | 0.598951E+11 | 0.317506E+10 | ||||||||
Minimum of Months | 0.261083E+10 | 3778.68 | 22.73 | 16.79 | 0.236851E+09 | 347.84 | 22.73 | 16.79 | ||
Maximum of Months | 0.755330E+10 | 12807.36 | 42.00 | 27.45 | 0.288924E+09 | 347.88 | 42.00 | 27.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.406224E+09 | 4159.16 | 03-JAN-06:03 | 12.93 |
February | 0.246816E+09 | 5288.66 | 06-FEB-06:03 | 21.88 |
March | 0.204270E+09 | 6039.33 | 27-MAR-04:02 | 22.57 |
April | 83504805.08 | 6365.33 | 24-APR-04:02 | 23.25 |
May | 34007173.49 | 6441.54 | 08-MAY-04:02 | 26.67 |
June | 21203305.16 | 5009.85 | 02-JUN-04:02 | 28.33 |
July | 10524617.37 | 3512.98 | 06-JUL-04:02 | 29.17 |
August | 8697969.49 | 4039.88 | 15-AUG-04:02 | 29.75 |
September | 21360983.46 | 6531.21 | 25-SEP-04:02 | 24.17 |
October | 37988999.14 | 6123.00 | 30-OCT-04:02 | 22.25 |
November | 76126826.98 | 6692.00 | 13-NOV-05:02 | 21.00 |
December | 0.265903E+09 | 4973.23 | 11-DEC-06:03 | 21.90 |
Annual Sum or Average | 0.141663E+10 | |||
Minimum of Months | 8697969.49 | 3512.98 | 12.93 | |
Maximum of Months | 0.406224E+09 | 6692.00 | 29.75 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26161725.11 | 3284.46 | 02-JAN-06:03 | 13.00 |
February | 21676449.80 | 3174.42 | 21-FEB-06:03 | 13.95 |
March | 18575440.45 | 3152.30 | 02-MAR-05:03 | 29.08 |
April | 17926637.75 | 2718.96 | 17-APR-04:02 | 24.33 |
May | 21586339.63 | 3591.83 | 12-MAY-04:02 | 28.67 |
June | 19644430.63 | 3497.20 | 23-JUN-04:02 | 28.17 |
July | 31745610.15 | 3720.29 | 27-JUL-04:02 | 30.33 |
August | 32242517.11 | 3473.31 | 25-AUG-04:02 | 31.17 |
September | 22999230.15 | 3569.51 | 14-SEP-04:02 | 29.67 |
October | 22402861.90 | 3243.16 | 05-OCT-04:02 | 27.83 |
November | 24773365.76 | 3043.91 | 20-NOV-05:02 | 26.00 |
December | 27411018.53 | 2797.00 | 18-DEC-06:03 | 13.17 |
Annual Sum or Average | 0.287146E+09 | |||
Minimum of Months | 17926637.75 | 2718.96 | 13.00 | |
Maximum of Months | 32242517.11 | 3720.29 | 31.17 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 41364970.01 | 5378.43 | 02-JAN-05:02 | 13.83 |
February | 29974463.81 | 5183.59 | 21-FEB-05:02 | 14.83 |
March | 28295131.68 | 4508.68 | 06-MAR-05:03 | 16.83 |
April | 23337880.22 | 3763.49 | 13-APR-04:03 | 19.08 |
May | 25403015.64 | 4342.60 | 12-MAY-04:02 | 28.67 |
June | 25817203.84 | 4417.35 | 16-JUN-04:02 | 28.83 |
July | 50867273.54 | 4593.36 | 27-JUL-04:02 | 30.33 |
August | 53972271.88 | 4406.73 | 31-AUG-04:02 | 28.83 |
September | 45215019.95 | 5021.96 | 22-SEP-04:02 | 27.82 |
October | 39314960.91 | 4914.82 | 13-OCT-04:02 | 25.75 |
November | 41653662.18 | 4382.84 | 24-NOV-05:02 | 20.00 |
December | 40908216.19 | 4627.50 | 26-DEC-05:02 | 15.83 |
Annual Sum or Average | 0.446124E+09 | |||
Minimum of Months | 23337880.22 | 3763.49 | 13.83 | |
Maximum of Months | 53972271.88 | 5378.43 | 30.33 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16022.41 | 106.82 | 20-JAN-07:03 | 12.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 16022.41 | |||
Minimum of Months | 0.00 | 0.00 | 12.17 | |
Maximum of Months | 16022.41 | 106.82 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 163228.74 | 800.22 | 20-JAN-07:03 | 12.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 163228.74 | |||
Minimum of Months | 0.00 | 0.00 | 12.17 | |
Maximum of Months | 163228.74 | 800.22 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138637E+09 | 4504.99 | 06-JAN-07:10 | 13.92 |
February | 83519761.64 | 4518.79 | 21-FEB-07:07 | 13.92 |
March | 21732987.13 | 4513.95 | 07-MAR-07:08 | 14.58 |
April | 29025.31 | 241.88 | 05-APR-06:10 | 17.02 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 15892137.67 | 4254.29 | 19-DEC-07:07 | 14.92 |
Annual Sum or Average | 0.259811E+09 | |||
Minimum of Months | 0.00 | 0.00 | 13.92 | |
Maximum of Months | 0.138637E+09 | 4518.79 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.208150E+11 | 18520.31 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.188385E+11 | 18520.31 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.216654E+11 | 18520.31 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.200796E+11 | 18520.31 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.212402E+11 | 18520.31 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.208620E+11 | 18520.31 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.204550E+11 | 18520.31 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.216654E+11 | 18520.31 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.200739E+11 | 18520.31 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.208179E+11 | 18520.31 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.203773E+11 | 18520.31 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.204522E+11 | 18520.31 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.247342E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.188385E+11 | 18520.31 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.216654E+11 | 18520.31 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.790847E+09 | 941.26 | 04-JAN-16:00 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.703580E+09 | 955.25 | 09-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.823877E+09 | 1075.43 | 15-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.727178E+09 | 929.41 | 18-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.772476E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.763551E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.722842E+09 | 804.28 | 20-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.806453E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.730184E+09 | 720.41 | 01-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.769240E+09 | 872.37 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.777514E+09 | 1019.29 | 29-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.772022E+09 | 1038.23 | 14-DEC-16:00 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.915976E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.703580E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.823877E+09 | 1075.43 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.499082E+09 | 618.08 | 04-JAN-16:00 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.445216E+09 | 614.74 | 09-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.521406E+09 | 673.37 | 15-MAR-07:10 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.461021E+09 | 552.74 | 18-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.490813E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.485687E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.458713E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.511282E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.462818E+09 | 456.08 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.486310E+09 | 456.08 | 02-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.491979E+09 | 658.69 | 29-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.486956E+09 | 663.86 | 14-DEC-16:00 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.580128E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.445216E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.521406E+09 | 673.37 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.779274E+09 | 857.05 | 23-JAN-16:00 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.697844E+09 | 916.97 | 09-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.821808E+09 | 1073.58 | 15-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.728068E+09 | 934.12 | 18-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.776316E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.768117E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.725686E+09 | 851.64 | 20-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.808065E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.729938E+09 | 720.41 | 01-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.765237E+09 | 720.41 | 02-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.766661E+09 | 946.45 | 29-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.758434E+09 | 1001.85 | 15-DEC-16:00 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.912545E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.697844E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.821808E+09 | 1073.58 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.496866E+09 | 589.78 | 09-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.443239E+09 | 567.46 | 09-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.522440E+09 | 683.94 | 14-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.461381E+09 | 608.99 | 18-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.491193E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.485181E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.459035E+09 | 564.89 | 20-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.511664E+09 | 530.52 | 29-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.462723E+09 | 544.96 | 26-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.487696E+09 | 584.50 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.487284E+09 | 586.50 | 03-NOV-07:10 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.482841E+09 | 639.58 | 15-DEC-08:09 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.579154E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.443239E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.522440E+09 | 683.94 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.789075E+09 | 930.40 | 04-JAN-16:00 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.702784E+09 | 945.86 | 09-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.823014E+09 | 1071.36 | 15-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.726789E+09 | 918.75 | 18-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.772143E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.763274E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.722378E+09 | 787.64 | 20-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.806026E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.729688E+09 | 720.41 | 01-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.768642E+09 | 857.42 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.776184E+09 | 1012.36 | 29-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.770391E+09 | 1032.39 | 15-DEC-16:00 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.915039E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.702784E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.823014E+09 | 1071.36 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.498292E+09 | 613.57 | 04-JAN-16:00 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.444737E+09 | 610.50 | 09-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.520932E+09 | 670.97 | 15-MAR-07:10 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.460458E+09 | 542.82 | 18-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.490627E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.485461E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.458433E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.511039E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.462537E+09 | 456.08 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.485988E+09 | 456.08 | 02-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.491313E+09 | 655.81 | 29-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.486164E+09 | 661.24 | 14-DEC-16:00 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.579598E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.444737E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.520932E+09 | 670.97 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.778837E+09 | 842.40 | 23-JAN-16:00 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.697305E+09 | 905.62 | 09-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.821188E+09 | 1069.41 | 15-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.727611E+09 | 923.72 | 18-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.775827E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.767389E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.725112E+09 | 837.56 | 20-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.807646E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.729498E+09 | 720.41 | 01-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.764905E+09 | 720.41 | 02-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.766180E+09 | 934.47 | 29-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.757706E+09 | 993.48 | 15-DEC-16:00 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.911920E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.697305E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.821188E+09 | 1069.41 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.496277E+09 | 584.62 | 09-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.442743E+09 | 561.59 | 09-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.521906E+09 | 682.06 | 14-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.460995E+09 | 604.58 | 18-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.490949E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.484894E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.458747E+09 | 558.98 | 20-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.511300E+09 | 523.38 | 29-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.462335E+09 | 537.61 | 26-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.487213E+09 | 578.32 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.486890E+09 | 580.27 | 03-NOV-07:10 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.482183E+09 | 636.19 | 15-DEC-08:09 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.578643E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.442743E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.521906E+09 | 682.06 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.790846E+09 | 941.25 | 04-JAN-16:00 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.703579E+09 | 955.23 | 09-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.823877E+09 | 1075.42 | 15-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.727178E+09 | 929.40 | 18-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.772476E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.763551E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.722842E+09 | 804.26 | 20-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.806452E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.730183E+09 | 720.41 | 01-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.769240E+09 | 872.36 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.777514E+09 | 1019.28 | 29-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.772022E+09 | 1038.23 | 14-DEC-16:00 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.915976E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.703579E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.823877E+09 | 1075.42 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.499082E+09 | 618.08 | 04-JAN-16:00 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.445216E+09 | 614.73 | 09-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.521406E+09 | 673.37 | 15-MAR-07:10 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.461021E+09 | 552.73 | 18-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.490813E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.485687E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.458713E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.511282E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.462818E+09 | 456.08 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.486310E+09 | 456.08 | 02-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.491979E+09 | 658.68 | 29-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.486955E+09 | 663.86 | 14-DEC-16:00 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.580128E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.445216E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.521406E+09 | 673.37 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.779274E+09 | 857.04 | 23-JAN-16:00 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.697844E+09 | 916.95 | 09-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.821808E+09 | 1073.57 | 15-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.728068E+09 | 934.10 | 18-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.776316E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.768117E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.725686E+09 | 851.62 | 20-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.808065E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.729938E+09 | 720.41 | 01-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.765237E+09 | 720.41 | 02-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.766661E+09 | 946.44 | 29-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.758434E+09 | 1001.84 | 15-DEC-16:00 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.912545E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.697844E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.821808E+09 | 1073.57 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.496866E+09 | 589.77 | 09-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.443239E+09 | 567.45 | 09-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.522440E+09 | 683.94 | 14-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.461380E+09 | 608.98 | 18-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.491193E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.485181E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.459035E+09 | 564.88 | 20-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.511664E+09 | 530.51 | 29-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.462723E+09 | 544.96 | 26-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.487696E+09 | 584.50 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.487284E+09 | 586.50 | 03-NOV-07:10 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.482841E+09 | 639.57 | 15-DEC-08:09 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.579154E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.443239E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.522440E+09 | 683.94 | 0.147531E+10 | 953.29 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.208150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.200796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.212402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.208620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.204550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.200739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.208179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.203773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.204522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.247342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.790847E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2762754.87 | 0.157257E+09 |
February | 0.901968E+09 | 0.703580E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18009038.38 | 0.159241E+09 |
March | 0.107774E+10 | 0.823877E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43406254.33 | 89114116.39 |
April | 0.956342E+09 | 0.727178E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103982E+09 | 41772657.31 |
May | 0.103597E+10 | 0.772476E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254965E+09 | 4752593.61 |
June | 0.103308E+10 | 0.763551E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317795E+09 | 531105.53 |
July | 0.959235E+09 | 0.722842E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456156E+09 | 0.00 |
August | 0.107774E+10 | 0.806453E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436801E+09 | 0.00 |
September | 0.956342E+09 | 0.730184E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305489E+09 | 740876.91 |
October | 0.994195E+09 | 0.769240E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175065E+09 | 6800579.62 |
November | 0.984487E+09 | 0.777514E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74265152.81 | 42762518.23 |
December | 0.959235E+09 | 0.772022E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12461736.88 | 0.115138E+09 |
Annual Sum or Average | 0.119305E+11 | 0.915976E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220116E+10 | 0.618111E+09 |
Minimum of Months | 0.901968E+09 | 0.703580E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2762754.87 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.823877E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456156E+09 | 0.159241E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.499082E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1263609.63 | 0.109212E+09 |
February | 0.571020E+09 | 0.445216E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10884567.92 | 0.109092E+09 |
March | 0.682301E+09 | 0.521406E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28386585.13 | 60898103.92 |
April | 0.605444E+09 | 0.461021E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67585638.64 | 28424456.59 |
May | 0.655854E+09 | 0.490813E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169606E+09 | 3231021.59 |
June | 0.654023E+09 | 0.485687E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212590E+09 | 364012.18 |
July | 0.607275E+09 | 0.458713E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305449E+09 | 0.00 |
August | 0.682301E+09 | 0.511282E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292064E+09 | 0.00 |
September | 0.605444E+09 | 0.462818E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203172E+09 | 506893.22 |
October | 0.629407E+09 | 0.486310E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115416E+09 | 4833141.40 |
November | 0.623262E+09 | 0.491979E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47487004.97 | 30009082.47 |
December | 0.607275E+09 | 0.486956E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7693001.55 | 78606279.81 |
Annual Sum or Average | 0.755301E+10 | 0.580128E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146160E+10 | 0.425178E+09 |
Minimum of Months | 0.571020E+09 | 0.445216E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1263609.63 | 0.00 |
Maximum of Months | 0.682301E+09 | 0.521406E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305449E+09 | 0.109212E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.779274E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 987015.18 | 0.180662E+09 |
February | 0.901968E+09 | 0.697844E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14917945.90 | 0.174611E+09 |
March | 0.107774E+10 | 0.821808E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41414090.87 | 95840249.65 |
April | 0.956342E+09 | 0.728068E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101925E+09 | 42601273.72 |
May | 0.103597E+10 | 0.776316E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256670E+09 | 4692068.25 |
June | 0.103308E+10 | 0.768117E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320560E+09 | 503659.76 |
July | 0.959235E+09 | 0.725686E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459595E+09 | 0.00 |
August | 0.107774E+10 | 0.808065E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438280E+09 | 0.00 |
September | 0.956342E+09 | 0.729938E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303457E+09 | 788199.55 |
October | 0.994195E+09 | 0.765237E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168766E+09 | 7898771.64 |
November | 0.984487E+09 | 0.766661E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64180458.00 | 48304465.81 |
December | 0.959235E+09 | 0.758434E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8696688.63 | 0.131917E+09 |
Annual Sum or Average | 0.119305E+11 | 0.912545E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217945E+10 | 0.687818E+09 |
Minimum of Months | 0.901968E+09 | 0.697844E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 987015.18 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.821808E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459595E+09 | 0.180662E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.496866E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1662313.52 | 0.108196E+09 |
February | 0.570983E+09 | 0.443239E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11780843.45 | 0.108872E+09 |
March | 0.682256E+09 | 0.522440E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28472886.77 | 62496134.29 |
April | 0.605404E+09 | 0.461381E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68009386.01 | 29179533.07 |
May | 0.655811E+09 | 0.491193E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169908E+09 | 3281797.55 |
June | 0.653980E+09 | 0.485181E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212175E+09 | 375190.60 |
July | 0.607235E+09 | 0.459035E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306736E+09 | 0.00 |
August | 0.682256E+09 | 0.511664E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292981E+09 | 0.00 |
September | 0.605404E+09 | 0.462723E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203012E+09 | 510457.08 |
October | 0.629366E+09 | 0.487696E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115280E+09 | 4830931.94 |
November | 0.623221E+09 | 0.487284E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47661591.63 | 29499418.79 |
December | 0.607235E+09 | 0.482841E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7879113.50 | 78791975.41 |
Annual Sum or Average | 0.755252E+10 | 0.579154E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146556E+10 | 0.426033E+09 |
Minimum of Months | 0.570983E+09 | 0.443239E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1662313.52 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.522440E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306736E+09 | 0.108872E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.789075E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1212120.48 | 0.100351E+09 |
February | 0.901968E+09 | 0.702784E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9893916.71 | 96695910.79 |
March | 0.107774E+10 | 0.823014E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23818988.73 | 51063188.25 |
April | 0.956342E+09 | 0.726789E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58559638.12 | 22319126.15 |
May | 0.103597E+10 | 0.772143E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138970E+09 | 2284390.14 |
June | 0.103308E+10 | 0.763274E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172070E+09 | 238160.64 |
July | 0.959235E+09 | 0.722378E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245720E+09 | 0.00 |
August | 0.107774E+10 | 0.806026E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234894E+09 | 0.00 |
September | 0.956342E+09 | 0.729688E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165282E+09 | 375583.22 |
October | 0.994195E+09 | 0.768642E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94022432.46 | 4514719.89 |
November | 0.984487E+09 | 0.776184E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39329253.44 | 28239754.51 |
December | 0.959235E+09 | 0.770391E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6253426.82 | 75749456.73 |
Annual Sum or Average | 0.119305E+11 | 0.915039E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119003E+10 | 0.381831E+09 |
Minimum of Months | 0.901968E+09 | 0.702784E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1212120.48 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.823014E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245720E+09 | 0.100351E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.498292E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 528743.52 | 69643790.48 |
February | 0.571020E+09 | 0.444737E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5963990.47 | 66849955.31 |
March | 0.682301E+09 | 0.520932E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15362508.44 | 35348375.76 |
April | 0.605444E+09 | 0.460458E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37066586.17 | 15739767.91 |
May | 0.655854E+09 | 0.490627E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91376405.40 | 1710493.09 |
June | 0.654023E+09 | 0.485461E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114114E+09 | 186157.52 |
July | 0.607275E+09 | 0.458433E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163404E+09 | 0.00 |
August | 0.682301E+09 | 0.511039E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156166E+09 | 0.00 |
September | 0.605444E+09 | 0.462537E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109072E+09 | 283036.19 |
October | 0.629407E+09 | 0.485988E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61438244.41 | 3373973.10 |
November | 0.623262E+09 | 0.491313E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24940434.39 | 20073749.72 |
December | 0.607275E+09 | 0.486164E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3900703.90 | 51923361.13 |
Annual Sum or Average | 0.755301E+10 | 0.579598E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783333E+09 | 0.265133E+09 |
Minimum of Months | 0.571020E+09 | 0.444737E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 528743.52 | 0.00 |
Maximum of Months | 0.682301E+09 | 0.520932E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163404E+09 | 69643790.48 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.778837E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21702632.12 | 0.152784E+10 |
February | 0.901968E+09 | 0.697305E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256278E+09 | 0.946161E+09 |
March | 0.107774E+10 | 0.821188E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.887853E+09 | 0.599342E+09 |
April | 0.956342E+09 | 0.727611E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165060E+10 | 0.213326E+09 |
May | 0.103597E+10 | 0.775827E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341784E+10 | 35011145.15 |
June | 0.103308E+10 | 0.767389E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402553E+10 | 1384045.34 |
July | 0.959235E+09 | 0.725112E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427724E+10 | 0.00 |
August | 0.107774E+10 | 0.807646E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491702E+10 | 0.00 |
September | 0.956342E+09 | 0.729498E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342021E+10 | 2958474.55 |
October | 0.994195E+09 | 0.764905E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246683E+10 | 27516530.39 |
November | 0.984487E+09 | 0.766180E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132016E+10 | 0.313570E+09 |
December | 0.959235E+09 | 0.757706E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203652E+09 | 0.887561E+09 |
Annual Sum or Average | 0.119305E+11 | 0.911920E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268649E+11 | 0.455467E+10 |
Minimum of Months | 0.901968E+09 | 0.697305E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21702632.12 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.821188E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491702E+10 | 0.152784E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.496277E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 691567.53 | 69779494.70 |
February | 0.570983E+09 | 0.442743E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6215849.05 | 67449470.57 |
March | 0.682256E+09 | 0.521906E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15130323.23 | 36808021.72 |
April | 0.605404E+09 | 0.460995E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36829073.40 | 16267711.70 |
May | 0.655811E+09 | 0.490949E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91013995.87 | 1788143.19 |
June | 0.653980E+09 | 0.484894E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112999E+09 | 204825.62 |
July | 0.607235E+09 | 0.458747E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162933E+09 | 0.00 |
August | 0.682256E+09 | 0.511300E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155721E+09 | 0.00 |
September | 0.605404E+09 | 0.462335E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108342E+09 | 296926.70 |
October | 0.629366E+09 | 0.487213E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60941640.13 | 3470883.70 |
November | 0.623221E+09 | 0.486890E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24695169.15 | 20104124.51 |
December | 0.607235E+09 | 0.482183E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3859640.53 | 52534469.18 |
Annual Sum or Average | 0.755252E+10 | 0.578643E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779373E+09 | 0.268704E+09 |
Minimum of Months | 0.570983E+09 | 0.442743E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 691567.53 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.521906E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162933E+09 | 69779494.70 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.790846E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2076949.45 | 0.148365E+09 |
February | 0.901968E+09 | 0.703579E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14972696.83 | 0.147177E+09 |
March | 0.107774E+10 | 0.823877E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36239882.00 | 81653806.33 |
April | 0.956342E+09 | 0.727178E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88035107.76 | 37374145.35 |
May | 0.103597E+10 | 0.772476E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213618E+09 | 4079424.61 |
June | 0.103308E+10 | 0.763551E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265621E+09 | 436065.66 |
July | 0.959235E+09 | 0.722842E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380296E+09 | 0.00 |
August | 0.107774E+10 | 0.806452E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364240E+09 | 0.00 |
September | 0.956342E+09 | 0.730183E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255404E+09 | 594984.67 |
October | 0.994195E+09 | 0.769240E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146373E+09 | 6354952.66 |
November | 0.984487E+09 | 0.777514E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61890933.51 | 40323270.73 |
December | 0.959235E+09 | 0.772022E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9933170.95 | 0.108680E+09 |
Annual Sum or Average | 0.119305E+11 | 0.915976E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183870E+10 | 0.575039E+09 |
Minimum of Months | 0.901968E+09 | 0.703579E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2076949.45 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.823877E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380296E+09 | 0.148365E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.499082E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 984225.73 | 0.101338E+09 |
February | 0.421807E+09 | 0.445216E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9127811.54 | 99709996.07 |
March | 0.502994E+09 | 0.521406E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23707665.48 | 55138988.53 |
April | 0.447140E+09 | 0.461021E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57289474.19 | 25247118.54 |
May | 0.484071E+09 | 0.490813E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142330E+09 | 2737803.39 |
June | 0.482240E+09 | 0.485687E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177888E+09 | 295728.98 |
July | 0.448971E+09 | 0.458713E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254777E+09 | 0.00 |
August | 0.502994E+09 | 0.511282E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243657E+09 | 0.00 |
September | 0.447140E+09 | 0.462818E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169986E+09 | 398031.55 |
October | 0.465148E+09 | 0.486310E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96788062.96 | 4424250.39 |
November | 0.460569E+09 | 0.491979E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39709518.06 | 27859030.62 |
December | 0.448971E+09 | 0.486955E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6299802.41 | 73280025.58 |
Annual Sum or Average | 0.557719E+10 | 0.580128E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122254E+10 | 0.390429E+09 |
Minimum of Months | 0.421807E+09 | 0.445216E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 984225.73 | 0.00 |
Maximum of Months | 0.502994E+09 | 0.521406E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254777E+09 | 0.101338E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.779274E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 797325.69 | 0.166023E+09 |
February | 0.901968E+09 | 0.697844E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12481521.71 | 0.159010E+09 |
March | 0.107774E+10 | 0.821808E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34421410.19 | 87064850.35 |
April | 0.956342E+09 | 0.728068E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85592706.15 | 38112751.94 |
May | 0.103597E+10 | 0.776316E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214675E+09 | 4048809.03 |
June | 0.103308E+10 | 0.768117E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267557E+09 | 417047.42 |
July | 0.959235E+09 | 0.725686E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382420E+09 | 0.00 |
August | 0.107774E+10 | 0.808065E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364634E+09 | 0.00 |
September | 0.956342E+09 | 0.729938E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253006E+09 | 633782.34 |
October | 0.994195E+09 | 0.765237E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140866E+09 | 7294037.22 |
November | 0.984487E+09 | 0.766661E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53420168.57 | 44762075.16 |
December | 0.959235E+09 | 0.758434E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7278540.83 | 0.121341E+09 |
Annual Sum or Average | 0.119305E+11 | 0.912545E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181715E+10 | 0.628707E+09 |
Minimum of Months | 0.901968E+09 | 0.697844E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 797325.69 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.821808E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382420E+09 | 0.166023E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.496866E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1260379.88 | 0.101550E+09 |
February | 0.570983E+09 | 0.443239E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9692968.38 | 0.100470E+09 |
March | 0.682256E+09 | 0.522440E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23498181.71 | 57039048.58 |
April | 0.605404E+09 | 0.461380E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56898109.03 | 26082925.15 |
May | 0.655811E+09 | 0.491193E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141823E+09 | 2826705.12 |
June | 0.653980E+09 | 0.485181E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176579E+09 | 308352.40 |
July | 0.607235E+09 | 0.459035E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254419E+09 | 0.00 |
August | 0.682256E+09 | 0.511664E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243169E+09 | 0.00 |
September | 0.605404E+09 | 0.462723E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168912E+09 | 407503.94 |
October | 0.629366E+09 | 0.487696E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95935315.32 | 4490885.13 |
November | 0.623221E+09 | 0.487284E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39343423.57 | 27720194.76 |
December | 0.607235E+09 | 0.482841E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6203604.70 | 74217006.15 |
Annual Sum or Average | 0.755252E+10 | 0.579154E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121773E+10 | 0.395113E+09 |
Minimum of Months | 0.570983E+09 | 0.443239E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1260379.88 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.522440E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254419E+09 | 0.101550E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1202064.94 | 0.220164E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16183360.48 | 0.211867E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39865837.87 | 0.114875E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103624E+09 | 48978202.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264928E+09 | 4710530.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332385E+09 | 459912.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478246E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453500E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316907E+09 | 712950.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175486E+09 | 8357217.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66247328.91 | 56090009.18 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8791886.46 | 0.160394E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225737E+10 | 0.826610E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1202064.94 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478246E+09 | 0.220164E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2613224.32 | 0.259220E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22241570.66 | 0.256266E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52624804.74 | 0.140533E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134052E+09 | 61960517.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339488E+09 | 6174846.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426019E+09 | 599946.25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613625E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583427E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407596E+09 | 946492.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227296E+09 | 10045746.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89158338.68 | 67505772.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13176914.86 | 0.189570E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291132E+10 | 0.992822E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2613224.32 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613625E+09 | 0.259220E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 764166.49 | 0.245613E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18128317.20 | 0.240581E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50393666.70 | 0.133066E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117727E+09 | 49792900.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343535E+09 | 4110997.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446346E+09 | 422120.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639379E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.615039E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424994E+09 | 620172.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236766E+09 | 5449577.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85294844.32 | 48733569.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8416337.09 | 0.171058E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298678E+10 | 0.899448E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 764166.49 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639379E+09 | 0.245613E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 18520.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 18520.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 18520.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 18520.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 18520.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 18520.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 18520.31 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 18520.31 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 18520.31 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 18520.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 18520.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 18520.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 941.26 | 04-JAN-16:00 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 166.54 | 29-JAN-11:50 | 407.83 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 955.25 | 09-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 399.23 | 05-FEB-15:00 | 347.15 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 1075.43 | 15-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 332.01 | 26-MAR-13:57 | 356.00 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 929.41 | 18-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 462.76 | 30-APR-12:55 | 236.86 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2658.74 | 21-MAY-13:00 | 77.24 | 01-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 656.18 | 11-JUN-14:54 | 64.66 | 07-JUN-04:55 |
July | 1306.65 | 03-JUL-09:09 | 804.28 | 20-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 995.66 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 930.64 | 13-AUG-13:53 | 0.00 | 01-AUG-00:03 |
September | 1306.65 | 01-SEP-09:09 | 720.41 | 01-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 725.00 | 03-SEP-15:44 | 51.97 | 25-SEP-04:45 |
October | 1306.65 | 02-OCT-09:09 | 872.37 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 616.09 | 09-OCT-15:26 | 115.27 | 20-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1019.29 | 29-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 394.60 | 19-NOV-13:52 | 191.84 | 22-NOV-05:55 |
December | 1306.65 | 01-DEC-10:09 | 1038.23 | 14-DEC-16:00 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.45 | 10-DEC-12:30 | 269.10 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 166.54 | 0.00 | |||||
Maximum of Months | 1306.65 | 1075.43 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 2658.74 | 407.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 618.08 | 04-JAN-16:00 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.22 | 29-JAN-11:50 | 271.19 | 18-JAN-04:00 |
February | 827.22 | 01-FEB-10:09 | 614.74 | 09-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 261.40 | 05-FEB-14:53 | 232.57 | 13-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 673.37 | 15-MAR-07:10 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 217.06 | 26-MAR-14:18 | 243.65 | 05-MAR-15:00 |
April | 827.22 | 03-APR-09:09 | 552.74 | 18-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 306.73 | 30-APR-12:55 | 157.92 | 05-APR-01:00 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1772.49 | 21-MAY-13:00 | 52.28 | 01-MAY-03:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 444.23 | 11-JUN-14:56 | 42.61 | 07-JUN-04:55 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 663.77 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 620.65 | 13-AUG-13:53 | 0.00 | 01-AUG-00:03 |
September | 827.22 | 01-SEP-09:09 | 456.08 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 487.69 | 03-SEP-15:46 | 34.22 | 25-SEP-04:45 |
October | 827.22 | 02-OCT-09:09 | 456.08 | 02-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 415.65 | 09-OCT-15:26 | 77.02 | 20-OCT-04:00 |
November | 827.22 | 01-NOV-09:09 | 658.69 | 29-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.03 | 19-NOV-13:50 | 126.91 | 22-NOV-05:55 |
December | 827.22 | 01-DEC-10:09 | 663.86 | 14-DEC-16:00 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 115.79 | 10-DEC-13:00 | 176.93 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 71.22 | 0.00 | |||||
Maximum of Months | 827.22 | 673.37 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 1772.49 | 271.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 857.05 | 23-JAN-16:00 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.91 | 29-JAN-11:50 | 423.70 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 916.97 | 09-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 372.91 | 05-FEB-15:28 | 360.39 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 1073.58 | 15-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 315.21 | 26-MAR-13:53 | 404.53 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 934.12 | 18-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 459.54 | 30-APR-12:55 | 239.51 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2658.74 | 21-MAY-13:00 | 78.44 | 01-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 662.89 | 11-JUN-14:56 | 64.02 | 07-JUN-04:55 |
July | 1306.65 | 03-JUL-09:09 | 851.64 | 20-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 995.66 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 930.47 | 13-AUG-13:53 | 0.00 | 01-AUG-00:03 |
September | 1306.65 | 01-SEP-09:09 | 720.41 | 01-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 717.38 | 03-SEP-15:44 | 52.48 | 25-SEP-04:45 |
October | 1306.65 | 02-OCT-09:09 | 720.41 | 02-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 598.85 | 09-OCT-15:00 | 118.55 | 20-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 946.45 | 29-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.39 | 19-NOV-14:05 | 195.21 | 22-NOV-05:55 |
December | 1306.65 | 01-DEC-10:09 | 1001.85 | 15-DEC-16:00 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 129.67 | 10-DEC-12:50 | 269.31 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 50.91 | 0.00 | |||||
Maximum of Months | 1306.65 | 1073.58 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2658.74 | 423.70 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 589.78 | 09-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 126.33 | 29-JAN-11:50 | 272.37 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 567.46 | 09-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 255.41 | 05-FEB-14:50 | 233.79 | 13-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 683.94 | 14-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 216.46 | 26-MAR-13:53 | 259.92 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 608.99 | 18-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 313.86 | 30-APR-12:55 | 161.46 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1772.48 | 21-MAY-12:53 | 53.36 | 01-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 440.33 | 11-JUN-12:58 | 43.16 | 07-JUN-04:55 |
July | 827.17 | 03-JUL-09:09 | 564.89 | 20-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 663.77 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 530.52 | 29-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 620.65 | 13-AUG-13:53 | 0.00 | 01-AUG-00:03 |
September | 827.17 | 01-SEP-09:09 | 544.96 | 26-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 474.96 | 03-SEP-15:44 | 33.88 | 25-SEP-04:45 |
October | 827.17 | 02-OCT-09:09 | 584.50 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 412.21 | 09-OCT-15:24 | 78.33 | 20-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 586.50 | 03-NOV-07:10 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 251.19 | 19-NOV-13:43 | 127.84 | 22-NOV-05:55 |
December | 827.17 | 01-DEC-10:09 | 639.58 | 15-DEC-08:09 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 133.77 | 10-DEC-12:10 | 176.23 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 126.33 | 0.00 | |||||
Maximum of Months | 827.17 | 683.94 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1772.48 | 272.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 930.40 | 04-JAN-16:00 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 79.87 | 29-JAN-12:00 | 269.03 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 945.86 | 09-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 229.89 | 05-FEB-14:50 | 214.58 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 1071.36 | 15-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 200.24 | 26-MAR-14:00 | 181.77 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 918.75 | 18-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.74 | 30-APR-13:00 | 135.45 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1444.15 | 21-MAY-12:55 | 37.94 | 15-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.41 | 11-JUN-13:10 | 29.36 | 07-JUN-04:45 |
July | 1306.65 | 03-JUL-09:09 | 787.64 | 20-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 531.89 | 30-JUL-14:24 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 496.65 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1306.65 | 01-SEP-09:09 | 720.41 | 01-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 384.99 | 03-SEP-16:06 | 25.14 | 25-SEP-04:53 |
October | 1306.65 | 02-OCT-09:09 | 857.42 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.63 | 09-OCT-15:00 | 72.46 | 20-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1012.36 | 29-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.57 | 19-NOV-14:00 | 118.39 | 22-NOV-05:55 |
December | 1306.65 | 01-DEC-10:09 | 1032.39 | 15-DEC-16:00 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 94.52 | 10-DEC-12:10 | 173.60 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 79.87 | 0.00 | |||||
Maximum of Months | 1306.65 | 1071.36 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1444.15 | 269.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 613.57 | 04-JAN-16:00 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.02 | 29-JAN-12:00 | 184.20 | 18-JAN-04:00 |
February | 827.22 | 01-FEB-10:09 | 610.50 | 09-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 144.20 | 05-FEB-15:10 | 146.13 | 13-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 670.97 | 15-MAR-07:10 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 124.82 | 26-MAR-14:00 | 124.56 | 05-MAR-15:00 |
April | 827.22 | 03-APR-09:09 | 542.82 | 18-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.20 | 30-APR-13:00 | 92.13 | 05-APR-01:00 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 962.58 | 21-MAY-12:55 | 27.43 | 01-MAY-03:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.08 | 11-JUN-14:56 | 20.29 | 07-JUN-04:45 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 354.16 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.83 | 13-AUG-14:14 | 0.00 | 01-AUG-00:03 |
September | 827.22 | 01-SEP-09:09 | 456.08 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.42 | 03-SEP-16:06 | 16.66 | 25-SEP-04:53 |
October | 827.22 | 02-OCT-09:09 | 456.08 | 02-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.19 | 09-OCT-15:26 | 50.12 | 20-OCT-04:00 |
November | 827.22 | 01-NOV-09:09 | 655.81 | 29-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.30 | 19-NOV-13:50 | 78.56 | 22-NOV-05:55 |
December | 827.22 | 01-DEC-10:09 | 661.24 | 14-DEC-16:00 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.78 | 10-DEC-13:00 | 115.01 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 36.02 | 0.00 | |||||
Maximum of Months | 827.22 | 670.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 962.58 | 184.20 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 842.40 | 23-JAN-16:00 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4217.06 | 23-JAN-13:00 | 12540.89 | 09-JAN-07:02 |
February | 1306.65 | 01-FEB-10:09 | 905.62 | 09-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7355.02 | 07-FEB-13:00 | 10964.95 | 13-FEB-07:02 |
March | 1306.65 | 01-MAR-10:09 | 1069.41 | 15-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15792.26 | 27-MAR-11:01 | 9092.57 | 07-MAR-07:02 |
April | 1306.65 | 03-APR-09:09 | 923.72 | 18-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18442.30 | 28-APR-11:01 | 6757.46 | 05-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18286.25 | 09-MAY-11:01 | 4166.24 | 01-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20291.39 | 12-JUN-11:01 | 541.50 | 22-JUN-08:00 |
July | 1306.65 | 03-JUL-09:09 | 837.56 | 20-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23319.22 | 21-JUL-11:01 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22635.97 | 16-AUG-11:01 | 0.00 | 01-AUG-00:03 |
September | 1306.65 | 01-SEP-09:09 | 720.41 | 01-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17862.87 | 12-SEP-11:01 | 1054.87 | 25-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 720.41 | 02-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14168.56 | 04-OCT-11:01 | 2698.13 | 30-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 934.47 | 29-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9227.30 | 01-NOV-11:02 | 7799.66 | 27-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 993.48 | 15-DEC-16:00 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4903.86 | 01-DEC-12:10 | 11685.76 | 26-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 4217.06 | 0.00 | |||||
Maximum of Months | 1306.65 | 1069.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 23319.22 | 12540.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 584.62 | 09-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 55.56 | 29-JAN-12:00 | 184.43 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 561.59 | 09-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 137.59 | 05-FEB-14:50 | 146.77 | 13-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 682.06 | 14-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 124.80 | 26-MAR-13:53 | 133.88 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 604.58 | 18-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.40 | 30-APR-13:00 | 94.36 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 963.95 | 21-MAY-12:55 | 28.20 | 01-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.15 | 11-JUN-13:10 | 21.19 | 07-JUN-04:45 |
July | 827.17 | 03-JUL-09:09 | 558.98 | 20-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 354.64 | 30-JUL-14:24 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 523.38 | 29-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.10 | 13-AUG-13:53 | 0.00 | 01-AUG-00:03 |
September | 827.17 | 01-SEP-09:09 | 537.61 | 26-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.06 | 03-SEP-16:04 | 16.60 | 25-SEP-04:53 |
October | 827.17 | 02-OCT-09:09 | 578.32 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.96 | 09-OCT-15:24 | 51.11 | 20-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 580.27 | 03-NOV-07:10 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.28 | 19-NOV-13:50 | 79.19 | 22-NOV-05:55 |
December | 827.17 | 01-DEC-10:09 | 636.19 | 15-DEC-08:09 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 66.41 | 10-DEC-12:10 | 114.96 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 55.56 | 0.00 | |||||
Maximum of Months | 827.17 | 682.06 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 963.95 | 184.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 941.25 | 04-JAN-16:00 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 129.86 | 29-JAN-11:50 | 387.57 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 955.23 | 09-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 335.27 | 05-FEB-14:40 | 322.34 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 1075.42 | 15-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 286.11 | 26-MAR-14:00 | 294.92 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 929.40 | 18-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 392.09 | 30-APR-13:00 | 211.99 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2218.27 | 21-MAY-13:00 | 64.39 | 01-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 548.47 | 11-JUN-14:54 | 55.73 | 07-JUN-04:55 |
July | 1306.65 | 03-JUL-09:09 | 804.26 | 20-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 830.27 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 788.53 | 13-AUG-13:55 | 0.00 | 01-AUG-00:03 |
September | 1306.65 | 01-SEP-09:09 | 720.41 | 01-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 598.23 | 03-SEP-16:04 | 38.76 | 25-SEP-04:53 |
October | 1306.65 | 02-OCT-09:09 | 872.36 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 510.37 | 09-OCT-15:14 | 103.68 | 20-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1019.28 | 29-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.18 | 19-NOV-14:00 | 179.65 | 22-NOV-05:55 |
December | 1306.65 | 01-DEC-10:09 | 1038.23 | 14-DEC-16:00 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.26 | 10-DEC-12:50 | 248.22 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 129.86 | 0.00 | |||||
Maximum of Months | 1306.65 | 1075.42 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 2218.27 | 387.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 618.08 | 04-JAN-16:00 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.38 | 29-JAN-12:00 | 257.11 | 18-JAN-04:00 |
February | 805.43 | 01-FEB-08:09 | 614.73 | 09-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 216.85 | 05-FEB-15:20 | 215.47 | 13-FEB-04:00 |
March | 805.43 | 01-MAR-08:09 | 673.37 | 15-MAR-07:10 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 187.48 | 26-MAR-14:00 | 201.38 | 05-MAR-15:00 |
April | 805.43 | 03-APR-07:10 | 552.73 | 18-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 257.68 | 30-APR-12:55 | 141.13 | 05-APR-01:00 |
May | 805.43 | 01-MAY-07:10 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1478.84 | 21-MAY-13:00 | 43.50 | 01-MAY-03:00 |
June | 805.43 | 01-JUN-07:10 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.43 | 11-JUN-14:56 | 36.55 | 07-JUN-04:55 |
July | 805.43 | 03-JUL-07:10 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 560.00 | 30-JUL-14:33 | 0.00 | 01-JUL-00:10 |
August | 805.43 | 01-AUG-07:10 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 527.52 | 13-AUG-13:55 | 0.00 | 01-AUG-00:03 |
September | 805.43 | 01-SEP-07:10 | 456.08 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 403.30 | 03-SEP-16:06 | 24.61 | 25-SEP-04:53 |
October | 805.43 | 02-OCT-07:10 | 456.08 | 02-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 349.33 | 09-OCT-15:14 | 68.93 | 20-OCT-04:00 |
November | 805.43 | 01-NOV-07:10 | 658.68 | 29-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.21 | 19-NOV-14:00 | 118.72 | 22-NOV-05:55 |
December | 805.43 | 01-DEC-08:09 | 663.86 | 14-DEC-16:00 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.53 | 10-DEC-12:50 | 163.21 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 59.38 | 0.00 | |||||
Maximum of Months | 805.43 | 673.37 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 1478.84 | 257.11 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 857.04 | 23-JAN-16:00 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.38 | 23-JAN-13:00 | 400.08 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 916.95 | 09-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 305.14 | 05-FEB-14:58 | 332.96 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 1073.57 | 15-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 269.38 | 26-MAR-13:57 | 331.93 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 934.10 | 18-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 383.36 | 30-APR-12:55 | 214.23 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2218.27 | 21-MAY-13:00 | 65.56 | 01-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 549.51 | 11-JUN-14:56 | 55.39 | 07-JUN-04:55 |
July | 1306.65 | 03-JUL-09:09 | 851.62 | 20-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 830.27 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 784.58 | 13-AUG-13:55 | 0.00 | 01-AUG-00:03 |
September | 1306.65 | 01-SEP-09:09 | 720.41 | 01-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 599.76 | 03-SEP-16:04 | 38.63 | 25-SEP-04:53 |
October | 1306.65 | 02-OCT-09:09 | 720.41 | 02-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 501.67 | 09-OCT-15:14 | 106.23 | 20-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 946.44 | 29-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 277.41 | 19-NOV-14:00 | 182.21 | 22-NOV-05:55 |
December | 1306.65 | 01-DEC-10:09 | 1001.84 | 15-DEC-16:00 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.87 | 10-DEC-12:30 | 248.47 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 39.38 | 0.00 | |||||
Maximum of Months | 1306.65 | 1073.57 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2218.27 | 400.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 589.77 | 09-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.97 | 29-JAN-11:50 | 258.69 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 567.45 | 09-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 212.15 | 05-FEB-14:58 | 216.65 | 13-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 683.94 | 14-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.60 | 26-MAR-14:00 | 214.93 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 608.98 | 18-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.95 | 30-APR-13:00 | 144.25 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1478.84 | 21-MAY-13:00 | 44.62 | 01-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.66 | 11-JUN-12:58 | 37.29 | 07-JUN-04:55 |
July | 827.17 | 03-JUL-09:09 | 564.88 | 20-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 553.51 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 530.51 | 29-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 525.23 | 13-AUG-13:55 | 0.00 | 01-AUG-00:03 |
September | 827.17 | 01-SEP-09:09 | 544.96 | 26-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 393.67 | 03-SEP-16:04 | 24.31 | 25-SEP-04:53 |
October | 827.17 | 02-OCT-09:09 | 584.50 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.16 | 09-OCT-15:00 | 70.13 | 20-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 586.50 | 03-NOV-07:10 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.25 | 19-NOV-13:52 | 119.65 | 22-NOV-05:55 |
December | 827.17 | 01-DEC-10:09 | 639.57 | 15-DEC-08:09 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 108.15 | 10-DEC-12:30 | 163.14 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 98.97 | 0.00 | |||||
Maximum of Months | 827.17 | 683.94 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1478.84 | 258.69 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.46 | 29-JAN-12:00 | 563.51 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.59 | 05-FEB-14:53 | 464.30 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.72 | 26-MAR-14:00 | 416.62 | 06-MAR-05:55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.46 | 30-APR-13:00 | 288.87 | 05-APR-04:07 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2736.19 | 21-MAY-13:00 | 87.10 | 01-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 684.00 | 11-JUN-13:20 | 68.21 | 07-JUN-04:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1041.57 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 984.91 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 738.17 | 03-SEP-15:52 | 65.18 | 25-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.74 | 09-OCT-15:10 | 143.32 | 20-OCT-04:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.42 | 19-NOV-14:00 | 255.43 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.35 | 10-DEC-12:30 | 355.52 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.46 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2736.19 | 563.51 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.84 | 29-JAN-12:00 | 670.20 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.62 | 05-FEB-14:43 | 567.21 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.27 | 26-MAR-14:00 | 513.36 | 06-MAR-05:55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 649.29 | 30-APR-13:00 | 365.00 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3540.20 | 21-MAY-12:53 | 116.07 | 01-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 871.97 | 11-JUN-13:20 | 87.19 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1330.79 | 30-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1245.65 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 938.59 | 03-SEP-15:52 | 86.47 | 25-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 790.05 | 09-OCT-15:00 | 168.80 | 20-OCT-04:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543.92 | 19-NOV-14:00 | 313.64 | 22-NOV-05:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.80 | 10-DEC-12:50 | 433.87 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.84 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3540.20 | 670.20 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.85 | 29-JAN-11:50 | 572.97 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.38 | 05-FEB-15:00 | 508.91 | 19-FEB-19:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.94 | 02-MAR-04:00 | 648.47 | 05-MAR-15:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.66 | 30-APR-13:00 | 315.28 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3169.65 | 21-MAY-13:00 | 113.27 | 01-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 791.99 | 09-JUN-03:00 | 70.95 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1270.11 | 30-JUL-14:20 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1150.40 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 905.24 | 02-SEP-17:02 | 80.97 | 25-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 728.27 | 09-OCT-15:10 | 151.02 | 20-OCT-04:08 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.81 | 19-NOV-13:52 | 253.58 | 22-NOV-05:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.92 | 10-DEC-11:53 | 387.05 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.85 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3169.65 | 648.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 46813.32 | 02-JAN-05:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 46209.90 | 21-FEB-05:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 45251.81 | 27-MAR-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46079.57 | 10-APR-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45261.55 | 02-MAY-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 44152.01 | 07-JUN-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 39606.05 | 13-JUL-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 37162.53 | 31-AUG-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 42363.79 | 30-SEP-04:03 | 0.00 | 1231.90 | 17378.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 43902.40 | 20-OCT-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 45711.95 | 27-NOV-05:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 45810.49 | 26-DEC-05:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 37162.53 | 0.00 | 1231.90 | 17378.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46813.32 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5863.28 | 23-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.44 | 0.00 |
February | 8844.90 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.82 | 0.00 |
March | 12031.74 | 27-MAR-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.71 | 0.00 |
April | 13375.56 | 28-APR-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.89 | 0.00 |
May | 13925.31 | 10-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.52 | 0.00 |
June | 14511.73 | 12-JUN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.64 | 0.00 |
July | 15737.99 | 21-JUL-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.66 | 0.00 |
August | 15714.88 | 16-AUG-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.38 | 0.00 |
September | 14496.19 | 05-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.30 | 0.00 |
October | 12184.77 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.27 | 0.00 |
November | 9983.60 | 06-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.54 | 0.00 |
December | 7438.27 | 04-DEC-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5863.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.57 | 0.00 | |
Maximum of Months | 15737.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.89 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2248.22 | 31-JAN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.29 |
February | 3982.83 | 06-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.22 | 0.00 |
March | 5179.45 | 27-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.42 | 0.00 |
April | 5302.17 | 24-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.59 | 0.00 |
May | 6266.90 | 22-MAY-12:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.10 | 0.00 |
June | 6385.40 | 12-JUN-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.49 | 0.00 |
July | 7418.65 | 05-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.43 | 0.00 |
August | 6919.79 | 21-AUG-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.56 | 0.00 |
September | 6983.50 | 05-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.81 | 0.00 |
October | 6065.91 | 10-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.19 | 0.00 |
November | 5170.54 | 13-NOV-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.13 | 0.00 |
December | 3429.97 | 04-DEC-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2248.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7418.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.81 | 33.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3592.20 | 02-JAN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.99 |
February | 4818.24 | 06-FEB-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.26 | 0.00 |
March | 7230.02 | 27-MAR-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.19 | 0.00 |
April | 6850.63 | 26-APR-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.03 | 0.00 |
May | 8601.02 | 22-MAY-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.19 | 0.00 |
June | 7972.10 | 15-JUN-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.51 | 0.00 |
July | 8931.74 | 31-JUL-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.34 | 0.00 |
August | 8564.94 | 07-AUG-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.43 | 0.00 |
September | 7930.74 | 12-SEP-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.73 | 0.00 |
October | 6651.96 | 10-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 | 0.00 |
November | 5650.19 | 13-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.90 | 0.00 |
December | 4845.52 | 04-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3592.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8931.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.19 | 31.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 31869.53 | 31-JAN-06:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 32842.51 | 21-FEB-06:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33928.31 | 27-MAR-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34742.92 | 10-APR-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33992.86 | 02-MAY-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33138.87 | 07-JUN-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29799.34 | 03-JUL-06:03 | 3811.58 | 5543.10 | 9524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30330.32 | 07-AUG-06:03 | 3811.58 | 5543.10 | 9524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32763.62 | 26-SEP-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34145.49 | 30-OCT-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35479.99 | 13-NOV-05:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 34076.22 | 11-DEC-05:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 29799.34 | 0.00 | 2463.50 | 9524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35479.99 | 3811.58 | 5543.10 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 15252.69 | 30-JAN-14:50 | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28784.44 | 06-FEB-06:03 | 1905.79 | 1847.62 | 9524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 35620.25 | 27-MAR-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39076.83 | 24-APR-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39301.60 | 01-MAY-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38500.61 | 07-JUN-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34260.54 | 31-JUL-06:03 | 3811.58 | 5543.10 | 9524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34686.87 | 07-AUG-06:03 | 3811.58 | 5543.10 | 9524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38218.76 | 26-SEP-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39238.57 | 30-OCT-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 39047.44 | 06-NOV-05:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 37198.00 | 11-DEC-06:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15252.69 | 0.00 | 1847.62 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39301.60 | 6198.29 | 5543.17 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4334.72 | 23-JAN-14:10 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 36.51 | 0.00 |
February | 6058.61 | 06-FEB-15:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 116.29 | 0.00 |
March | 7394.60 | 27-MAR-13:40 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 174.08 | 0.00 |
April | 13304.50 | 30-APR-12:43 | 267.84 | 160.10 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 410.19 | 0.00 |
May | 16084.87 | 21-MAY-13:12 | 334.80 | 200.13 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1906.77 | 0.00 |
June | 15134.71 | 11-JUN-15:32 | 334.80 | 200.13 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 577.36 | 0.00 |
July | 16185.15 | 30-JUL-14:32 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 951.68 | 0.00 |
August | 16175.51 | 06-AUG-15:01 | 468.72 | 280.18 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 578.05 | 0.00 |
September | 16208.07 | 04-SEP-15:31 | 468.72 | 280.18 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 586.63 | 0.00 |
October | 13766.93 | 09-OCT-14:42 | 334.80 | 200.13 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 578.08 | 0.00 |
November | 6816.58 | 20-NOV-05:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 | 0.00 |
December | 4843.15 | 11-DEC-14:10 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 32.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4334.72 | 0.00 | 160.10 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 | 0.00 | |
Maximum of Months | 16208.07 | 1306.65 | 720.41 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1906.77 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3168.68 | 24-JAN-11:00 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
February | 4477.60 | 05-FEB-10:48 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 73.89 | 0.00 |
March | 8706.08 | 26-MAR-12:53 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 100.53 | 0.00 |
April | 12421.75 | 23-APR-10:02 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 83.70 | 0.00 |
May | 12623.05 | 21-MAY-09:52 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 381.13 | 0.00 |
June | 13010.97 | 18-JUN-09:12 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 196.65 | 0.00 |
July | 13427.33 | 23-JUL-10:02 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 320.45 | 0.00 |
August | 13453.34 | 13-AUG-10:22 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 433.47 | 0.00 |
September | 13471.38 | 04-SEP-10:12 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 255.89 | 0.00 |
October | 10751.13 | 29-OCT-11:32 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 155.08 | 0.00 |
November | 7749.16 | 05-NOV-11:13 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 82.76 | 0.00 |
December | 3620.91 | 04-DEC-11:00 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3168.68 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13471.38 | 827.22 | 456.08 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 433.47 | 0.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8062.91 | 23-JAN-13:30 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | 0.00 |
February | 17972.91 | 05-FEB-13:23 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 258.68 | 0.00 |
March | 17801.92 | 26-MAR-12:53 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 145.90 | 0.00 |
April | 17578.52 | 30-APR-12:43 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 399.75 | 0.00 |
May | 17766.46 | 21-MAY-13:12 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 1914.69 | 0.00 |
June | 14748.92 | 11-JUN-14:52 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 629.60 | 0.00 |
July | 17959.83 | 30-JUL-14:32 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 950.41 | 0.00 |
August | 17948.65 | 06-AUG-15:01 | 468.72 | 280.18 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 577.17 | 0.00 |
September | 18274.35 | 04-SEP-14:12 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 631.29 | 0.00 |
October | 18504.59 | 29-OCT-11:32 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 206.41 | 0.00 |
November | 18519.42 | 12-NOV-13:22 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 98.45 | 0.00 |
December | 18002.21 | 03-DEC-13:13 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 40.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8062.91 | 267.84 | 160.10 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 40.22 | 0.00 | |
Maximum of Months | 18519.42 | 1272.23 | 720.41 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 1914.69 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3872.43 | 31-JAN-16:20 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.14 |
February | 8658.36 | 05-FEB-15:23 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 213.88 | 0.00 |
March | 8255.11 | 26-MAR-15:32 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 153.51 | 0.00 |
April | 11840.88 | 09-APR-15:53 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 89.31 | 0.00 |
May | 14250.05 | 21-MAY-15:52 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 430.91 | 0.00 |
June | 13993.65 | 18-JUN-15:52 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 323.90 | 0.00 |
July | 14587.49 | 30-JUL-14:32 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 627.22 | 0.00 |
August | 14781.03 | 06-AUG-15:41 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 332.18 | 0.00 |
September | 14920.04 | 04-SEP-15:31 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 377.28 | 0.00 |
October | 14193.93 | 29-OCT-15:32 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 169.72 | 0.00 |
November | 10837.10 | 12-NOV-15:23 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 59.64 | 0.00 |
December | 4554.77 | 06-DEC-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 23.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3872.43 | 169.55 | 101.35 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14920.04 | 805.38 | 456.05 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 627.22 | 11.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4374.87 | 23-JAN-14:10 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 | 0.00 |
February | 5382.50 | 06-FEB-15:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 62.21 | 0.00 |
March | 6185.26 | 27-MAR-13:10 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 114.15 | 0.00 |
April | 6527.79 | 28-APR-12:50 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 148.37 | 0.00 |
May | 13246.04 | 21-MAY-13:32 | 267.84 | 160.10 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 684.97 | 0.00 |
June | 11021.55 | 15-JUN-04:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 14.14 | 0.00 |
July | 13404.48 | 30-JUL-14:21 | 535.68 | 320.20 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 515.01 | 0.00 |
August | 13323.16 | 06-AUG-14:51 | 535.68 | 320.20 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 322.57 | 0.00 |
September | 13221.63 | 17-SEP-14:32 | 334.80 | 200.13 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 280.63 | 0.00 |
October | 10929.77 | 12-OCT-04:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 |
November | 9338.90 | 20-NOV-05:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 8.66 | 0.00 |
December | 5647.86 | 11-DEC-07:03 | 803.52 | 1088.13 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4374.87 | 0.00 | 160.10 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13404.48 | 1306.65 | 1088.13 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 684.97 | 8.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3536.35 | 17-JAN-11:10 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 | 0.00 |
February | 3907.28 | 06-FEB-14:10 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 39.53 | 0.00 |
March | 5706.82 | 27-MAR-10:50 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 77.63 | 0.00 |
April | 8290.72 | 30-APR-12:43 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 146.04 | 0.00 |
May | 11157.73 | 29-MAY-10:32 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 78.09 | 0.00 |
June | 11265.33 | 18-JUN-10:02 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 136.35 | 0.00 |
July | 11636.39 | 23-JUL-10:02 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 178.08 | 0.00 |
August | 11186.58 | 13-AUG-10:51 | 296.74 | 177.38 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 281.50 | 0.00 |
September | 11205.43 | 04-SEP-08:23 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 101.88 | 0.00 |
October | 9272.03 | 08-OCT-09:13 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 14.28 | 0.00 |
November | 7734.77 | 05-NOV-11:13 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 44.35 | 0.00 |
December | 4120.83 | 04-DEC-10:40 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3536.35 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 | 0.00 | |
Maximum of Months | 11636.39 | 827.22 | 456.08 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 281.50 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11237.78 | 23-JAN-13:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 4217.06 | 0.00 |
February | 13060.97 | 07-FEB-13:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 7355.02 | 0.00 |
March | 15280.79 | 27-MAR-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 12125.05 | 0.00 |
April | 16623.56 | 28-APR-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 15869.30 | 0.00 |
May | 16232.41 | 09-MAY-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 15197.18 | 0.00 |
June | 17083.14 | 12-JUN-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 16535.00 | 0.00 |
July | 17974.35 | 21-JUL-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 18666.32 | 0.00 |
August | 18294.62 | 16-AUG-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 18582.27 | 0.00 |
September | 16940.50 | 05-SEP-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 14525.39 | 0.00 |
October | 15765.06 | 04-OCT-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 12377.44 | 0.00 |
November | 15719.46 | 12-NOV-13:22 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 50.59 | 0.00 |
December | 15318.23 | 25-DEC-13:43 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11237.78 | 267.84 | 160.10 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18294.62 | 687.71 | 720.41 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 18666.32 | 1.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3756.03 | 31-JAN-16:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 |
February | 4950.10 | 06-FEB-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 38.86 | 0.00 |
March | 5940.05 | 27-MAR-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 61.65 | 0.00 |
April | 7739.50 | 30-APR-18:03 | 0.00 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 42.65 | 0.00 |
May | 11816.06 | 29-MAY-16:31 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 104.39 | 0.00 |
June | 10291.67 | 11-JUN-16:12 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 194.69 | 0.00 |
July | 12028.28 | 30-JUL-15:01 | 339.11 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.99 | 0.00 |
August | 12116.13 | 06-AUG-16:11 | 339.11 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.62 | 0.00 |
September | 12016.75 | 17-SEP-16:32 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 153.30 | 0.00 |
October | 11196.08 | 22-OCT-15:32 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 86.00 | 0.00 |
November | 9629.57 | 12-NOV-15:23 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 32.89 | 0.00 |
December | 4487.04 | 04-DEC-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 13.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3756.03 | 0.00 | 101.35 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12116.13 | 805.38 | 456.05 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.99 | 5.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4216.07 | 23-JAN-14:10 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 30.62 | 0.00 |
February | 5563.12 | 06-FEB-14:50 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 96.19 | 0.00 |
March | 7634.92 | 28-MAR-05:03 | 535.68 | 519.33 | 2677.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 | 0.00 |
April | 9686.02 | 17-APR-04:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.16 |
May | 13234.64 | 21-MAY-13:12 | 334.80 | 200.13 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1614.88 | 0.00 |
June | 12264.16 | 04-JUN-14:32 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 315.16 | 0.00 |
July | 13320.27 | 30-JUL-14:32 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 806.49 | 0.00 |
August | 13156.10 | 13-AUG-13:13 | 267.84 | 160.10 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 393.47 | 0.00 |
September | 13404.63 | 04-SEP-14:41 | 535.68 | 320.20 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 509.87 | 0.00 |
October | 13211.19 | 09-OCT-16:32 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 439.65 | 0.00 |
November | 9593.68 | 20-NOV-05:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 12.49 | 0.00 |
December | 4692.98 | 11-DEC-14:10 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 27.25 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4216.07 | 0.00 | 160.10 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13404.63 | 1306.65 | 720.41 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 1614.88 | 11.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3288.91 | 17-JAN-10:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.70 |
February | 3806.55 | 06-FEB-14:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 61.08 | 0.00 |
March | 6766.24 | 26-MAR-10:33 | 127.17 | 76.02 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 24.70 | 0.00 |
April | 11480.00 | 23-APR-10:02 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 69.99 | 0.00 |
May | 11580.79 | 29-MAY-09:52 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 24.26 | 0.00 |
June | 11828.34 | 18-JUN-09:12 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 166.14 | 0.00 |
July | 11713.22 | 30-JUL-09:52 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 257.06 | 0.00 |
August | 11229.00 | 13-AUG-13:13 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 264.06 | 0.00 |
September | 12148.88 | 04-SEP-10:02 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 218.07 | 0.00 |
October | 11697.19 | 09-OCT-10:32 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 44.11 | 0.00 |
November | 6667.81 | 05-NOV-11:32 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 72.38 | 0.00 |
December | 3715.50 | 04-DEC-10:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3288.91 | 127.17 | 76.02 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12148.88 | 805.43 | 456.08 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 264.06 | 9.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7907.10 | 23-JAN-13:30 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 37.31 | 0.00 |
February | 15346.51 | 05-FEB-13:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 217.22 | 0.00 |
March | 13854.52 | 26-MAR-15:53 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 180.36 | 0.00 |
April | 14801.98 | 30-APR-12:43 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 338.30 | 0.00 |
May | 14825.88 | 21-MAY-13:12 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 1621.21 | 0.00 |
June | 13180.61 | 04-JUN-17:52 | 0.00 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 266.95 | 0.00 |
July | 14983.01 | 30-JUL-14:32 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 805.77 | 0.00 |
August | 14975.87 | 13-AUG-13:13 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 388.16 | 0.00 |
September | 15420.86 | 04-SEP-14:41 | 535.68 | 320.20 | 4015.69 | 0.00 | 0.00 | 0.00 | 0.00 | 497.58 | 0.00 |
October | 15904.63 | 29-OCT-14:02 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 248.53 | 0.00 |
November | 15454.27 | 05-NOV-11:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 98.91 | 0.00 |
December | 15371.38 | 03-DEC-13:23 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 29.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7907.10 | 0.00 | 160.10 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 29.79 | 0.00 | |
Maximum of Months | 15904.63 | 1272.23 | 720.41 | 4015.69 | 0.00 | 0.00 | 0.00 | 0.00 | 1621.21 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3778.68 | 31-JAN-16:20 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 |
February | 6117.51 | 05-FEB-16:13 | 127.16 | 76.01 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 153.43 | 0.00 |
March | 11455.46 | 26-MAR-15:53 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 117.97 | 0.00 |
April | 10003.15 | 02-APR-16:53 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 87.70 | 0.00 |
May | 12395.73 | 29-MAY-16:31 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 158.62 | 0.00 |
June | 12053.77 | 18-JUN-15:52 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 272.93 | 0.00 |
July | 12468.94 | 30-JUL-14:32 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 530.26 | 0.00 |
August | 12358.96 | 06-AUG-15:52 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 281.93 | 0.00 |
September | 12807.36 | 04-SEP-16:01 | 339.11 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.77 | 0.00 |
October | 12758.40 | 09-OCT-16:32 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 271.87 | 0.00 |
November | 10914.07 | 05-NOV-15:32 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 157.68 | 0.00 |
December | 4353.21 | 06-DEC-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 20.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3778.68 | 127.16 | 76.01 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12807.36 | 805.38 | 456.05 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 530.26 | 9.09 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.130876E+12 | 115444.73 | 23-JAN-13:00 | 0.793350E+10 | 8797.37 | 10-JAN-12:20 |
February | 0.124278E+12 | 134762.66 | 06-FEB-14:00 | 0.708659E+10 | 8780.34 | 03-FEB-12:00 |
March | 0.152269E+12 | 158466.86 | 27-MAR-12:09 | 0.782588E+10 | 8726.18 | 01-MAR-12:20 |
April | 0.157376E+12 | 173274.34 | 28-APR-12:09 | 0.695202E+10 | 8598.13 | 03-APR-11:50 |
May | 0.202505E+12 | 192066.54 | 30-MAY-15:09 | 0.694463E+10 | 8485.19 | 02-MAY-11:50 |
June | 0.220857E+12 | 201927.62 | 12-JUN-12:00 | 0.652593E+10 | 8393.93 | 02-JUN-11:20 |
July | 0.243318E+12 | 206151.60 | 21-JUL-13:00 | 0.642344E+10 | 8351.77 | 31-JUL-11:20 |
August | 0.263319E+12 | 219264.18 | 10-AUG-15:39 | 0.681530E+10 | 8412.62 | 31-AUG-11:20 |
September | 0.216882E+12 | 196630.21 | 05-SEP-15:30 | 0.667185E+10 | 8509.60 | 29-SEP-11:20 |
October | 0.192433E+12 | 172129.36 | 06-OCT-15:20 | 0.725169E+10 | 8624.88 | 31-OCT-11:50 |
November | 0.160633E+12 | 159561.15 | 01-NOV-12:30 | 0.741922E+10 | 8731.61 | 30-NOV-12:39 |
December | 0.136975E+12 | 130269.10 | 04-DEC-13:09 | 0.775232E+10 | 8789.66 | 29-DEC-12:50 |
Annual Sum or Average | 0.220172E+13 | 0.856024E+11 | ||||
Minimum of Months | 0.124278E+12 | 115444.73 | 0.642344E+10 | 8351.77 | ||
Maximum of Months | 0.263319E+12 | 219264.18 | 0.793350E+10 | 8797.37 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.235858E+11 | 0.697063E+10 | 0.641572E+11 | 0.109092E+10 | 0.726101E+10 | 1312252.65 | 0.208154E+09 | 0.276010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212818E+11 | 0.600090E+10 | 0.580684E+11 | 0.987241E+09 | 0.756616E+10 | 1186778.30 | 0.122781E+09 | 0.302497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251945E+11 | 0.621370E+10 | 0.666107E+11 | 0.114321E+10 | 0.105390E+11 | 1343621.24 | 44250507.78 | 0.425222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.224303E+11 | 0.555590E+10 | 0.619407E+11 | 0.105060E+10 | 0.121295E+11 | 1267813.82 | 741884.20 | 0.542668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.241009E+11 | 0.537342E+10 | 0.653840E+11 | 0.111689E+10 | 0.185526E+11 | 1327936.95 | 0.00 | 0.879759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.239361E+11 | 0.502906E+10 | 0.641577E+11 | 0.109959E+10 | 0.200344E+11 | 1296568.36 | 0.00 | 0.106599E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.224762E+11 | 0.526005E+10 | 0.631525E+11 | 0.106763E+10 | 0.205350E+11 | 1299182.41 | 0.00 | 0.130825E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.250394E+11 | 0.557682E+10 | 0.666107E+11 | 0.114310E+10 | 0.224241E+11 | 1343621.24 | 0.00 | 0.142523E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.224546E+11 | 0.581266E+10 | 0.619118E+11 | 0.105020E+10 | 0.183613E+11 | 1267813.82 | 0.00 | 0.107291E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.234149E+11 | 0.646045E+10 | 0.641717E+11 | 0.109102E+10 | 0.160670E+11 | 1312252.65 | 0.00 | 0.812267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.232724E+11 | 0.664294E+10 | 0.627379E+11 | 0.107094E+10 | 0.124048E+11 | 1278270.02 | 0.00 | 0.545028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.228760E+11 | 0.708733E+10 | 0.631380E+11 | 0.106768E+10 | 0.842239E+10 | 1299182.41 | 37955415.08 | 0.343440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280063E+12 | 0.719839E+11 | 0.762041E+12 | 0.129790E+11 | 0.174297E+12 | 15535293.87 | 0.413884E+09 | 0.899927E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.212818E+11 | 0.502906E+10 | 0.580684E+11 | 0.987241E+09 | 0.726101E+10 | 1186778.30 | 0.00 | 0.276010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.251945E+11 | 0.708733E+10 | 0.666107E+11 | 0.114321E+10 | 0.224241E+11 | 1343621.24 | 0.208154E+09 | 0.142523E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.793350E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.708659E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.782588E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.695202E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.694463E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.652593E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.642344E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.681530E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.667185E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.725169E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.741922E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.775232E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.856024E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.642344E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.793350E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 25315.91 | 23-JAN-16:00 | 5557.43 | 01-JAN-06:10 | 47562.27 | 02-JAN-08:09 | 923.82 | 09-JAN-08:20 | 11593.37 | 23-JAN-13:30 | 0.73 | 01-JAN-06:10 | 6233.84 | 20-JAN-07:30 |
February | 25723.80 | 09-FEB-16:00 | 5557.43 | 01-FEB-06:10 | 47562.27 | 01-FEB-08:09 | 922.96 | 09-FEB-08:20 | 16159.44 | 06-FEB-15:30 | 0.73 | 01-FEB-06:30 | 5796.81 | 01-FEB-07:19 |
March | 27135.45 | 15-MAR-07:10 | 5557.43 | 01-MAR-06:10 | 47562.27 | 01-MAR-08:09 | 926.85 | 15-MAR-07:19 | 20589.84 | 27-MAR-15:30 | 0.73 | 01-MAR-06:30 | 4696.42 | 07-MAR-07:19 |
April | 25669.86 | 18-APR-07:10 | 5557.43 | 01-APR-05:10 | 47562.27 | 03-APR-07:10 | 924.74 | 18-APR-07:19 | 22507.51 | 24-APR-15:09 | 0.73 | 28-APR-12:09 | 409.13 | 05-APR-06:49 |
May | 23688.37 | 01-MAY-07:10 | 5557.43 | 01-MAY-05:10 | 47562.27 | 01-MAY-07:10 | 921.90 | 01-MAY-07:19 | 25328.97 | 30-MAY-15:30 | 0.73 | 09-MAY-12:09 | 0.00 | 01-MAY-00:10 |
June | 23688.37 | 01-JUN-07:10 | 5557.43 | 01-JUN-05:10 | 47562.27 | 01-JUN-07:10 | 921.90 | 01-JUN-07:19 | 24994.99 | 12-JUN-15:09 | 0.73 | 01-JUN-12:09 | 0.00 | 01-JUN-00:10 |
July | 24623.50 | 20-JUL-07:10 | 5557.43 | 01-JUL-05:10 | 47562.27 | 03-JUL-07:10 | 923.24 | 20-JUL-07:19 | 25734.36 | 31-JUL-15:20 | 0.73 | 03-JUL-17:10 | 0.00 | 01-JUL-00:10 |
August | 23904.63 | 29-AUG-07:10 | 5557.43 | 01-AUG-05:10 | 47562.27 | 01-AUG-07:10 | 922.21 | 29-AUG-07:19 | 24250.68 | 07-AUG-15:30 | 0.73 | 01-AUG-12:09 | 0.00 | 01-AUG-00:10 |
September | 23947.75 | 26-SEP-07:10 | 5557.43 | 01-SEP-05:10 | 47562.27 | 01-SEP-07:10 | 922.27 | 26-SEP-07:19 | 26138.50 | 05-SEP-15:30 | 0.73 | 05-SEP-12:09 | 0.00 | 01-SEP-00:10 |
October | 24508.45 | 31-OCT-07:10 | 5557.43 | 01-OCT-05:10 | 47562.27 | 02-OCT-07:10 | 923.07 | 31-OCT-07:19 | 21354.61 | 10-OCT-15:20 | 0.73 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 26179.43 | 29-NOV-16:00 | 5557.43 | 01-NOV-05:10 | 47562.27 | 01-NOV-07:10 | 923.22 | 29-NOV-16:00 | 17924.70 | 13-NOV-15:09 | 0.73 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 26574.54 | 15-DEC-16:00 | 5557.43 | 01-DEC-06:10 | 47562.27 | 01-DEC-08:09 | 925.70 | 15-DEC-08:20 | 14171.30 | 04-DEC-15:30 | 0.73 | 01-DEC-06:30 | 4011.34 | 18-DEC-07:19 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 23688.37 | 5557.43 | 47562.27 | 921.90 | 11593.37 | 0.73 | 0.00 | |||||||
Maximum of Months | 27135.45 | 5557.43 | 47562.27 | 926.85 | 26138.50 | 0.73 | 6233.84 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 35209.23 | 23-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 51958.02 | 06-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 71631.01 | 27-MAR-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 86235.10 | 28-APR-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 99057.65 | 31-MAY-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 109995.10 | 12-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 116454.55 | 21-JUL-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 127061.43 | 10-AUG-15:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 107253.83 | 07-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84631.05 | 05-OCT-12:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 76812.76 | 01-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 48385.48 | 04-DEC-13:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 35209.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 127061.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 115444.73 | 23-JAN-13:00 | 23688.37 | 44099.74 | 0.00 | 920.56 | 11526.09 | 0.73 | 0.00 | 35209.23 | 0.00 |
February | 134762.66 | 06-FEB-14:00 | 23688.37 | 42286.04 | 0.00 | 919.86 | 15909.64 | 0.73 | 0.00 | 51958.02 | 0.00 |
March | 158466.86 | 27-MAR-12:09 | 23688.37 | 44099.74 | 0.00 | 920.56 | 18390.76 | 0.73 | 0.00 | 71366.71 | 0.00 |
April | 173274.34 | 28-APR-12:09 | 23688.37 | 44099.74 | 0.00 | 920.56 | 18329.84 | 0.73 | 0.00 | 86235.10 | 0.00 |
May | 192066.54 | 30-MAY-15:09 | 23688.37 | 43769.98 | 0.00 | 920.43 | 25084.21 | 0.73 | 0.00 | 98602.83 | 0.00 |
June | 201927.62 | 12-JUN-12:00 | 23688.37 | 44099.74 | 0.00 | 920.56 | 23223.12 | 0.73 | 0.00 | 109995.10 | 0.00 |
July | 206151.60 | 21-JUL-13:00 | 23688.37 | 42286.04 | 0.00 | 919.86 | 22802.06 | 0.73 | 0.00 | 116454.55 | 0.00 |
August | 219264.18 | 10-AUG-15:39 | 23688.37 | 43769.98 | 0.00 | 920.43 | 23823.25 | 0.73 | 0.00 | 127061.43 | 0.00 |
September | 196630.21 | 05-SEP-15:30 | 23688.37 | 43769.98 | 0.00 | 920.43 | 26138.50 | 0.73 | 0.00 | 102112.21 | 0.00 |
October | 172129.36 | 06-OCT-15:20 | 23688.37 | 43769.98 | 0.00 | 920.43 | 19358.56 | 0.73 | 0.00 | 84391.29 | 0.00 |
November | 159561.15 | 01-NOV-12:30 | 23688.37 | 44099.74 | 0.00 | 920.56 | 14708.43 | 0.73 | 0.00 | 76143.33 | 0.00 |
December | 130269.10 | 04-DEC-13:09 | 23688.37 | 44099.74 | 0.00 | 920.56 | 13174.23 | 0.73 | 0.00 | 48385.48 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 115444.73 | 23688.37 | 42286.04 | 0.00 | 919.86 | 11526.09 | 0.73 | 0.00 | 35209.23 | 0.00 | |
Maximum of Months | 219264.18 | 23688.37 | 44099.74 | 0.00 | 920.56 | 26138.50 | 0.73 | 0.00 | 127061.43 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 8797.37 | 10-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 8780.34 | 03-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 8726.18 | 01-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 8598.13 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 8485.19 | 02-MAY-11:50 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 8393.93 | 02-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 8351.77 | 31-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 8412.62 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 8509.60 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 8624.88 | 31-OCT-11:50 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 8731.61 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 8789.66 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8351.77 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8797.37 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.20 | 0.00 | 26.20 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.20 | 0.00 | 26.20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.18 | 0.00 | 26.18 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.16 | 0.00 | 26.16 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.20 | 0.00 | 26.20 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.16 | 0.00 | 26.16 |
Annual Sum or Average | 0.00 | 0.00 | 2.00 | 26.18 | 0.00 | 26.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.20 | 0.00 | 26.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.48 | 2.83 | 27.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.72 | 8.50 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.68 | 8.17 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 27.68 | 12.67 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.60 | 8.33 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.74 | 8.83 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.53 | 6.50 | 27.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 86.33 | 27.66 | 55.83 | 27.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 27.74 | 12.67 | 27.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.51 | 1.50 | 27.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.67 | 7.83 | 27.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.98 | 11.67 | 28.04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 28.00 | 9.33 | 28.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 27.98 | 14.67 | 28.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.90 | 9.83 | 28.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.99 | 11.67 | 28.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.73 | 12.33 | 27.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.37 | 1.50 | 27.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 106.17 | 27.90 | 80.33 | 27.96 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 28.00 | 14.67 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.69 | 1.83 | 27.69 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.70 | 2.00 | 27.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.63 | 5.83 | 27.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.78 | 8.00 | 27.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.76 | 6.83 | 27.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 27.73 | 11.50 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.77 | 8.00 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 28.02 | 9.50 | 28.11 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 28.09 | 10.83 | 28.14 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.84 | 8.67 | 27.85 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.68 | 2.67 | 27.68 |
Annual Sum or Average | 0.00 | 0.00 | 102.50 | 27.83 | 76.00 | 27.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 28.09 | 11.50 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.47 | 0.50 | 27.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.92 | 0.83 | 27.96 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.79 | 5.00 | 27.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 28.07 | 8.17 | 28.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.97 | 7.67 | 28.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 28.00 | 12.50 | 28.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.98 | 9.00 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 28.05 | 9.00 | 28.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.02 | 6.83 | 28.05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.63 | 3.17 | 27.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 98.50 | 27.98 | 62.67 | 28.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 28.07 | 12.50 | 28.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.42 | 3.50 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.36 | 5.17 | 27.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.37 | 10.33 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.29 | 7.00 | 27.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.39 | 7.17 | 27.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.29 | 3.33 | 27.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 51.83 | 27.35 | 36.50 | 27.42 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.42 | 10.33 | 27.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.45 | 2.33 | 27.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.66 | 11.00 | 27.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.60 | 8.83 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 27.65 | 13.67 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.48 | 9.17 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.66 | 11.17 | 27.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.50 | 12.50 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.33 | 1.50 | 27.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 90.67 | 27.58 | 70.17 | 27.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 27.66 | 13.67 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.39 | 0.67 | 20.39 | 0.50 | 22.28 | 0.50 | 23.36 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.35 | 2.67 | 26.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 25.81 | 7.83 | 25.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 25.69 | 14.83 | 25.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 48.17 | 25.98 | 47.83 | 25.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 52.33 | 26.20 | 52.33 | 26.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 64.67 | 26.57 | 60.67 | 26.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 78.67 | 26.56 | 71.00 | 26.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 65.17 | 26.44 | 58.67 | 26.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 62.33 | 26.13 | 57.17 | 26.08 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 26.18 | 27.17 | 26.16 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.56 | 4.17 | 27.56 |
Annual Sum or Average | 0.67 | 20.39 | 0.67 | 20.39 | 429.67 | 26.29 | 404.83 | 26.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 22.28 | 0.50 | 23.36 |
Maximum of Months | 0.67 | 20.39 | 0.67 | 20.39 | 78.67 | 27.56 | 71.00 | 27.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.48 | 0.67 | 27.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.57 | 2.33 | 27.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.75 | 6.17 | 27.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.59 | 5.67 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 27.60 | 10.50 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.49 | 8.33 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.65 | 8.00 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.65 | 6.83 | 27.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.53 | 3.00 | 27.53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 87.83 | 27.60 | 51.50 | 27.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 27.75 | 10.50 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.32 | 0.67 | 27.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.50 | 7.67 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.51 | 7.00 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.49 | 11.33 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.44 | 7.17 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.50 | 7.67 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.42 | 3.67 | 27.42 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 62.17 | 27.48 | 45.17 | 27.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.51 | 11.33 | 27.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.36 | 1.00 | 27.36 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.51 | 6.67 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.77 | 12.00 | 27.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.77 | 9.33 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 27.81 | 14.00 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.73 | 9.17 | 27.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.82 | 11.17 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.60 | 10.17 | 27.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.33 | 0.33 | 27.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 87.00 | 27.73 | 73.83 | 27.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 27.82 | 14.00 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.32 | 0.50 | 27.32 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.65 | 1.50 | 27.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.63 | 1.50 | 27.63 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.49 | 3.67 | 27.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.54 | 7.33 | 27.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.49 | 6.33 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.50 | 10.50 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.53 | 7.33 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.77 | 9.17 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.84 | 11.00 | 27.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.73 | 8.83 | 27.73 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.62 | 2.83 | 27.62 |
Annual Sum or Average | 0.00 | 0.00 | 86.67 | 27.63 | 70.50 | 27.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.32 | 0.50 | 27.32 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.84 | 11.00 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.17 | 27.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.71 | 0.67 | 27.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.71 | 3.67 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.91 | 6.83 | 27.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.86 | 6.50 | 27.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.80 | 10.50 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.78 | 7.33 | 27.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.93 | 7.00 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.85 | 6.17 | 27.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.53 | 2.33 | 27.53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 76.17 | 27.83 | 51.17 | 27.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.93 | 10.50 | 27.98 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 353.33 | 24.60 | 0.00 | 24.60 |
February | 0.00 | 0.00 | 375.50 | 24.53 | 0.00 | 24.53 |
March | 0.00 | 0.00 | 412.17 | 24.48 | 0.00 | 24.48 |
April | 0.00 | 0.00 | 454.33 | 24.42 | 0.00 | 24.42 |
May | 0.00 | 0.00 | 499.33 | 24.42 | 0.00 | 24.42 |
June | 0.00 | 0.00 | 496.00 | 24.37 | 0.00 | 24.37 |
July | 0.00 | 0.00 | 497.00 | 24.36 | 0.00 | 24.36 |
August | 0.00 | 0.00 | 514.00 | 24.29 | 0.00 | 24.29 |
September | 0.00 | 0.00 | 485.00 | 24.38 | 0.00 | 24.38 |
October | 0.00 | 0.00 | 491.67 | 24.44 | 0.00 | 24.44 |
November | 0.00 | 0.00 | 481.33 | 24.46 | 0.00 | 24.46 |
December | 0.00 | 0.00 | 434.00 | 24.48 | 0.00 | 24.48 |
Annual Sum or Average | 0.00 | 5493.67 | 24.43 | 0.00 | 24.43 | |
Minimum of Months | 0.00 | 0.00 | 353.33 | 24.29 | 0.00 | 24.29 |
Maximum of Months | 0.00 | 0.00 | 514.00 | 24.60 | 0.00 | 24.60 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 79.67 | 23.54 | 201.83 | 24.17 | 0.00 | 24.17 |
February | 36.00 | 23.56 | 265.67 | 24.30 | 0.00 | 24.30 |
March | 13.33 | 23.60 | 331.17 | 24.34 | 0.00 | 24.34 |
April | 4.33 | 23.75 | 405.83 | 24.32 | 0.00 | 24.32 |
May | 0.00 | 0.00 | 489.67 | 24.34 | 0.00 | 24.34 |
June | 0.00 | 0.00 | 496.00 | 24.31 | 0.00 | 24.31 |
July | 0.00 | 0.00 | 497.00 | 24.30 | 0.00 | 24.30 |
August | 0.00 | 0.00 | 514.00 | 24.26 | 0.00 | 24.26 |
September | 0.00 | 0.00 | 485.00 | 24.34 | 0.00 | 24.34 |
October | 0.00 | 0.00 | 482.67 | 24.39 | 0.00 | 24.39 |
November | 0.50 | 23.76 | 456.33 | 24.34 | 0.00 | 24.34 |
December | 36.33 | 23.56 | 298.33 | 24.26 | 0.00 | 24.26 |
Annual Sum or Average | 170.17 | 23.56 | 4923.50 | 24.31 | 0.00 | 24.31 |
Minimum of Months | 0.00 | 0.00 | 201.83 | 24.17 | 0.00 | 24.17 |
Maximum of Months | 79.67 | 23.76 | 514.00 | 24.39 | 0.00 | 24.39 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 236.00 | 23.30 | 96.50 | 23.54 | 0.00 | 23.54 |
February | 138.83 | 23.33 | 174.00 | 23.83 | 0.00 | 23.83 |
March | 76.50 | 23.43 | 265.83 | 24.08 | 0.00 | 24.08 |
April | 13.33 | 23.45 | 381.00 | 24.31 | 0.00 | 24.31 |
May | 0.00 | 0.00 | 483.67 | 24.38 | 0.00 | 24.38 |
June | 0.00 | 0.00 | 496.00 | 24.35 | 0.00 | 24.35 |
July | 0.00 | 0.00 | 496.17 | 24.38 | 0.00 | 24.38 |
August | 0.00 | 0.00 | 514.00 | 24.30 | 0.00 | 24.30 |
September | 0.83 | 26.72 | 485.00 | 24.39 | 0.83 | 24.39 |
October | 0.00 | 0.00 | 479.17 | 24.39 | 0.00 | 24.39 |
November | 8.67 | 23.51 | 393.50 | 24.29 | 0.00 | 24.29 |
December | 154.50 | 23.31 | 190.00 | 23.79 | 0.00 | 23.79 |
Annual Sum or Average | 628.67 | 23.34 | 4454.83 | 24.21 | 0.83 | 24.21 |
Minimum of Months | 0.00 | 0.00 | 96.50 | 23.54 | 0.00 | 23.54 |
Maximum of Months | 236.00 | 26.72 | 514.00 | 24.39 | 0.83 | 24.39 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 304.83 | 22.82 | 94.00 | 23.12 | 0.00 | 23.12 |
February | 189.50 | 22.96 | 177.33 | 23.56 | 0.50 | 23.56 |
March | 118.67 | 23.15 | 280.17 | 23.93 | 0.50 | 23.94 |
April | 54.50 | 24.24 | 393.33 | 24.42 | 22.33 | 24.49 |
May | 42.67 | 26.73 | 500.50 | 24.74 | 42.67 | 24.88 |
June | 68.33 | 26.53 | 496.00 | 24.80 | 68.33 | 24.98 |
July | 92.33 | 26.64 | 497.00 | 24.99 | 92.33 | 25.21 |
August | 66.67 | 26.61 | 514.00 | 24.79 | 66.67 | 24.98 |
September | 73.17 | 26.47 | 485.00 | 24.84 | 73.17 | 25.03 |
October | 59.17 | 26.10 | 484.67 | 24.71 | 56.50 | 24.85 |
November | 40.00 | 23.39 | 379.83 | 24.27 | 2.17 | 24.27 |
December | 214.50 | 22.97 | 188.83 | 23.52 | 6.33 | 23.52 |
Annual Sum or Average | 1324.33 | 24.09 | 4490.67 | 24.40 | 431.50 | 24.54 |
Minimum of Months | 40.00 | 22.82 | 94.00 | 23.12 | 0.00 | 23.12 |
Maximum of Months | 304.83 | 26.73 | 514.00 | 24.99 | 92.33 | 25.21 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 243.50 | 22.78 | 148.83 | 23.35 | 0.17 | 23.35 |
February | 158.33 | 22.90 | 218.17 | 23.72 | 0.50 | 23.72 |
March | 108.50 | 23.14 | 319.50 | 24.02 | 2.33 | 24.04 |
April | 75.83 | 25.25 | 417.67 | 24.63 | 48.67 | 24.79 |
May | 55.00 | 26.88 | 504.00 | 24.82 | 55.00 | 25.00 |
June | 70.00 | 26.68 | 496.00 | 24.83 | 70.00 | 25.03 |
July | 93.67 | 26.76 | 497.00 | 25.02 | 93.67 | 25.26 |
August | 70.00 | 26.74 | 514.00 | 24.82 | 70.00 | 25.03 |
September | 78.17 | 26.70 | 485.00 | 24.90 | 78.17 | 25.12 |
October | 69.17 | 26.53 | 492.33 | 24.83 | 67.83 | 25.02 |
November | 34.67 | 23.88 | 404.00 | 24.40 | 7.33 | 24.43 |
December | 178.67 | 22.96 | 231.17 | 23.67 | 6.83 | 23.68 |
Annual Sum or Average | 1235.50 | 24.42 | 4727.67 | 24.50 | 500.50 | 24.67 |
Minimum of Months | 34.67 | 22.78 | 148.83 | 23.35 | 0.17 | 23.35 |
Maximum of Months | 243.50 | 26.88 | 514.00 | 25.02 | 93.67 | 25.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 208.83 | 22.95 | 222.33 | 23.75 | 2.17 | 23.77 |
February | 140.50 | 23.15 | 247.50 | 23.95 | 7.33 | 24.01 |
March | 106.50 | 23.32 | 319.33 | 24.10 | 6.67 | 24.15 |
April | 72.83 | 24.70 | 402.50 | 24.51 | 37.00 | 24.63 |
May | 39.83 | 26.74 | 494.83 | 24.71 | 39.83 | 24.86 |
June | 61.67 | 26.47 | 496.00 | 24.75 | 61.67 | 24.92 |
July | 85.50 | 26.61 | 497.00 | 24.95 | 85.50 | 25.16 |
August | 64.50 | 26.64 | 514.00 | 24.78 | 64.50 | 24.97 |
September | 74.67 | 26.60 | 485.00 | 24.88 | 74.67 | 25.08 |
October | 72.00 | 26.55 | 491.83 | 24.86 | 70.00 | 25.06 |
November | 56.67 | 25.53 | 422.67 | 24.65 | 35.83 | 24.80 |
December | 151.17 | 23.40 | 277.33 | 24.11 | 18.00 | 24.21 |
Annual Sum or Average | 1134.67 | 24.59 | 4870.33 | 24.55 | 503.17 | 24.71 |
Minimum of Months | 39.83 | 22.95 | 222.33 | 23.75 | 2.17 | 23.77 |
Maximum of Months | 208.83 | 26.74 | 514.00 | 24.95 | 85.50 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 298.83 | 22.60 | 132.33 | 23.12 | 0.00 | 23.12 |
February | 192.50 | 22.76 | 192.83 | 23.52 | 1.50 | 23.53 |
March | 137.17 | 23.04 | 296.17 | 23.91 | 4.00 | 23.94 |
April | 80.17 | 24.34 | 393.33 | 24.45 | 34.17 | 24.57 |
May | 44.50 | 26.78 | 491.67 | 24.75 | 43.33 | 24.91 |
June | 69.67 | 26.69 | 496.00 | 24.81 | 69.67 | 25.02 |
July | 87.33 | 26.72 | 497.00 | 24.97 | 87.33 | 25.20 |
August | 68.83 | 26.74 | 514.00 | 24.80 | 68.83 | 25.01 |
September | 78.50 | 26.58 | 484.00 | 24.87 | 78.50 | 25.08 |
October | 60.83 | 26.13 | 476.50 | 24.73 | 55.83 | 24.88 |
November | 66.67 | 23.73 | 375.83 | 24.30 | 12.33 | 24.36 |
December | 224.17 | 22.77 | 202.50 | 23.47 | 6.67 | 23.48 |
Annual Sum or Average | 1409.17 | 24.01 | 4552.17 | 24.39 | 462.17 | 24.54 |
Minimum of Months | 44.50 | 22.60 | 132.33 | 23.12 | 0.00 | 23.12 |
Maximum of Months | 298.83 | 26.78 | 514.00 | 24.97 | 87.33 | 25.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 117.83 | 23.47 | 186.83 | 23.92 | 0.00 | 23.92 |
February | 69.33 | 23.39 | 249.67 | 24.08 | 0.00 | 24.08 |
March | 56.50 | 23.43 | 315.83 | 24.15 | 0.00 | 24.15 |
April | 18.17 | 24.24 | 412.50 | 24.38 | 7.00 | 24.40 |
May | 17.67 | 26.78 | 506.83 | 24.60 | 17.67 | 24.67 |
June | 43.83 | 26.47 | 496.00 | 24.69 | 43.83 | 24.82 |
July | 59.83 | 26.71 | 497.00 | 24.88 | 59.83 | 25.06 |
August | 43.33 | 26.69 | 514.00 | 24.70 | 43.33 | 24.85 |
September | 49.50 | 26.61 | 485.00 | 24.78 | 49.50 | 24.93 |
October | 30.50 | 26.52 | 495.17 | 24.70 | 30.50 | 24.80 |
November | 0.00 | 0.00 | 475.50 | 24.44 | 0.00 | 24.44 |
December | 34.67 | 23.54 | 339.50 | 24.22 | 0.00 | 24.22 |
Annual Sum or Average | 541.17 | 24.91 | 4973.83 | 24.52 | 251.67 | 24.61 |
Minimum of Months | 0.00 | 0.00 | 186.83 | 23.92 | 0.00 | 23.92 |
Maximum of Months | 117.83 | 26.78 | 514.00 | 24.88 | 59.83 | 25.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 80.33 | 23.41 | 263.83 | 24.13 | 0.33 | 24.14 |
February | 47.83 | 23.31 | 292.00 | 24.23 | 0.00 | 24.23 |
March | 46.17 | 23.35 | 364.33 | 24.23 | 0.00 | 24.23 |
April | 26.17 | 25.40 | 441.83 | 24.53 | 16.83 | 24.60 |
May | 46.33 | 26.86 | 508.00 | 24.77 | 46.33 | 24.93 |
June | 51.67 | 26.68 | 496.00 | 24.76 | 51.67 | 24.92 |
July | 73.67 | 26.86 | 497.00 | 24.97 | 73.67 | 25.18 |
August | 57.33 | 26.84 | 514.00 | 24.78 | 57.33 | 24.97 |
September | 63.17 | 26.81 | 485.00 | 24.88 | 63.17 | 25.08 |
October | 51.50 | 26.81 | 501.67 | 24.85 | 51.50 | 25.01 |
November | 5.00 | 27.13 | 482.67 | 24.56 | 5.00 | 24.58 |
December | 26.67 | 23.46 | 377.33 | 24.31 | 0.00 | 24.31 |
Annual Sum or Average | 575.83 | 25.55 | 5223.67 | 24.63 | 365.83 | 24.76 |
Minimum of Months | 5.00 | 23.31 | 263.83 | 24.13 | 0.00 | 24.14 |
Maximum of Months | 80.33 | 27.13 | 514.00 | 24.97 | 73.67 | 25.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 68.83 | 22.60 | 329.50 | 24.23 | 2.67 | 24.24 |
February | 53.00 | 22.90 | 344.67 | 24.27 | 10.00 | 24.29 |
March | 62.33 | 22.97 | 375.17 | 24.21 | 13.17 | 24.21 |
April | 44.67 | 24.04 | 421.17 | 24.46 | 27.50 | 24.48 |
May | 55.00 | 25.47 | 504.33 | 24.77 | 55.00 | 24.83 |
June | 133.33 | 25.37 | 496.00 | 24.87 | 133.33 | 24.96 |
July | 190.00 | 25.52 | 497.00 | 25.07 | 190.00 | 25.17 |
August | 186.67 | 25.68 | 514.00 | 25.08 | 186.67 | 25.21 |
September | 163.67 | 25.82 | 485.00 | 25.11 | 163.67 | 25.26 |
October | 126.50 | 25.82 | 502.00 | 25.05 | 126.50 | 25.18 |
November | 72.00 | 25.67 | 483.67 | 24.80 | 70.17 | 24.91 |
December | 56.17 | 23.97 | 410.33 | 24.48 | 27.50 | 24.55 |
Annual Sum or Average | 1212.17 | 25.07 | 5362.83 | 24.76 | 1006.17 | 24.88 |
Minimum of Months | 44.67 | 22.60 | 329.50 | 24.21 | 2.67 | 24.21 |
Maximum of Months | 190.00 | 25.82 | 514.00 | 25.11 | 190.00 | 25.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 103.50 | 23.34 | 252.67 | 24.04 | 0.00 | 24.04 |
February | 59.33 | 23.26 | 294.50 | 24.17 | 0.00 | 24.17 |
March | 50.50 | 23.38 | 355.83 | 24.24 | 0.67 | 24.24 |
April | 27.83 | 25.06 | 422.67 | 24.50 | 15.67 | 24.56 |
May | 29.17 | 26.91 | 507.00 | 24.69 | 29.17 | 24.80 |
June | 55.83 | 26.71 | 496.00 | 24.78 | 55.83 | 24.96 |
July | 72.67 | 26.84 | 497.00 | 24.95 | 72.67 | 25.17 |
August | 60.33 | 26.85 | 514.00 | 24.80 | 60.33 | 24.99 |
September | 64.00 | 26.81 | 485.00 | 24.88 | 64.00 | 25.09 |
October | 41.67 | 26.74 | 499.33 | 24.79 | 41.67 | 24.93 |
November | 9.83 | 26.92 | 481.67 | 24.55 | 9.83 | 24.60 |
December | 39.50 | 23.42 | 362.00 | 24.28 | 0.00 | 24.28 |
Annual Sum or Average | 614.17 | 25.30 | 5167.67 | 24.60 | 349.83 | 24.73 |
Minimum of Months | 9.83 | 23.26 | 252.67 | 24.04 | 0.00 | 24.04 |
Maximum of Months | 103.50 | 26.92 | 514.00 | 24.95 | 72.67 | 25.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 199.67 | 23.30 | 135.83 | 23.64 | 0.00 | 23.64 |
February | 99.50 | 23.30 | 224.83 | 23.96 | 0.33 | 23.96 |
March | 54.67 | 23.43 | 319.00 | 24.17 | 0.00 | 24.17 |
April | 22.83 | 25.02 | 422.50 | 24.47 | 15.83 | 24.52 |
May | 38.83 | 26.69 | 507.00 | 24.71 | 38.83 | 24.84 |
June | 65.00 | 26.46 | 496.00 | 24.77 | 65.00 | 24.95 |
July | 88.17 | 26.57 | 497.00 | 24.96 | 88.17 | 25.17 |
August | 62.33 | 26.55 | 514.00 | 24.76 | 62.33 | 24.94 |
September | 69.67 | 26.41 | 485.00 | 24.82 | 69.67 | 24.99 |
October | 48.67 | 26.27 | 490.17 | 24.71 | 48.67 | 24.84 |
November | 5.00 | 23.86 | 436.33 | 24.37 | 1.33 | 24.37 |
December | 113.33 | 23.38 | 257.33 | 23.96 | 1.83 | 23.97 |
Annual Sum or Average | 867.67 | 24.74 | 4785.00 | 24.52 | 392.00 | 24.65 |
Minimum of Months | 5.00 | 23.30 | 135.83 | 23.64 | 0.00 | 23.64 |
Maximum of Months | 199.67 | 26.69 | 514.00 | 24.96 | 88.17 | 25.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 171.00 | 23.20 | 144.33 | 23.76 | 0.50 | 23.77 |
February | 94.33 | 23.20 | 197.17 | 24.05 | 0.67 | 24.06 |
March | 58.67 | 23.37 | 277.17 | 24.25 | 1.33 | 24.26 |
April | 43.17 | 25.78 | 365.50 | 24.73 | 32.83 | 24.86 |
May | 55.83 | 26.83 | 430.00 | 24.93 | 55.83 | 25.13 |
June | 66.33 | 26.60 | 418.00 | 24.92 | 66.33 | 25.13 |
July | 90.00 | 26.71 | 422.00 | 25.14 | 90.00 | 25.38 |
August | 64.83 | 26.69 | 433.00 | 24.92 | 64.83 | 25.12 |
September | 72.67 | 26.65 | 410.00 | 25.01 | 72.67 | 25.23 |
October | 62.83 | 26.61 | 422.17 | 24.95 | 62.83 | 25.14 |
November | 10.00 | 25.27 | 373.83 | 24.56 | 5.83 | 24.59 |
December | 103.83 | 23.29 | 227.33 | 24.04 | 2.50 | 24.05 |
Annual Sum or Average | 893.50 | 24.98 | 4120.50 | 24.69 | 456.17 | 24.85 |
Minimum of Months | 10.00 | 23.20 | 144.33 | 23.76 | 0.50 | 23.77 |
Maximum of Months | 171.00 | 26.83 | 433.00 | 25.14 | 90.00 | 25.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 114.67 | 23.40 | 265.00 | 24.18 | 2.17 | 24.20 |
February | 62.67 | 23.55 | 296.83 | 24.28 | 5.67 | 24.32 |
March | 48.17 | 23.76 | 363.33 | 24.31 | 4.83 | 24.34 |
April | 34.67 | 25.47 | 428.33 | 24.56 | 25.33 | 24.64 |
May | 38.50 | 26.69 | 505.83 | 24.70 | 38.50 | 24.83 |
June | 60.67 | 26.39 | 496.00 | 24.73 | 60.67 | 24.90 |
July | 83.50 | 26.53 | 497.00 | 24.93 | 83.50 | 25.13 |
August | 60.83 | 26.56 | 514.00 | 24.76 | 60.83 | 24.93 |
September | 69.33 | 26.58 | 485.00 | 24.86 | 69.33 | 25.05 |
October | 68.17 | 26.69 | 497.50 | 24.88 | 68.17 | 25.08 |
November | 37.83 | 26.74 | 463.00 | 24.72 | 36.33 | 24.86 |
December | 72.50 | 24.11 | 340.00 | 24.43 | 16.67 | 24.53 |
Annual Sum or Average | 751.50 | 25.37 | 5151.83 | 24.65 | 472.00 | 24.79 |
Minimum of Months | 34.67 | 23.40 | 265.00 | 24.18 | 2.17 | 24.20 |
Maximum of Months | 114.67 | 26.74 | 514.00 | 24.93 | 83.50 | 25.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 208.33 | 23.10 | 179.00 | 23.65 | 0.00 | 23.65 |
February | 109.33 | 23.10 | 244.33 | 23.94 | 0.67 | 23.94 |
March | 68.00 | 23.34 | 340.67 | 24.18 | 2.83 | 24.20 |
April | 45.00 | 25.20 | 418.33 | 24.55 | 28.83 | 24.65 |
May | 40.00 | 26.82 | 503.33 | 24.73 | 40.00 | 24.87 |
June | 66.33 | 26.58 | 496.00 | 24.79 | 66.33 | 24.98 |
July | 87.67 | 26.64 | 497.00 | 24.96 | 87.67 | 25.18 |
August | 66.83 | 26.67 | 514.00 | 24.79 | 66.83 | 24.99 |
September | 71.00 | 26.54 | 485.00 | 24.85 | 71.00 | 25.04 |
October | 54.17 | 26.38 | 491.00 | 24.74 | 53.33 | 24.89 |
November | 19.17 | 24.92 | 432.00 | 24.44 | 9.17 | 24.49 |
December | 131.17 | 23.17 | 268.50 | 23.93 | 2.17 | 23.94 |
Annual Sum or Average | 967.00 | 24.66 | 4869.17 | 24.53 | 428.83 | 24.67 |
Minimum of Months | 19.17 | 23.10 | 179.00 | 23.65 | 0.00 | 23.65 |
Maximum of Months | 208.33 | 26.82 | 514.00 | 24.96 | 87.67 | 25.18 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.43369 | 42.26180 | 0.50587 | 10.62241 |
February | 454.00000 | 24.43949 | 45.31273 | 0.53076 | 11.16731 |
March | 514.00000 | 24.38955 | 44.76141 | 0.52458 | 11.00613 |
April | 485.00000 | 24.39915 | 47.44390 | 0.55399 | 11.69204 |
May | 508.00000 | 24.40904 | 50.00012 | -0.2520 | 6.83759 |
June | 496.00000 | 24.37168 | 53.12626 | -0.2370 | 6.65836 |
July | 497.00000 | 24.35552 | 52.75030 | -0.2490 | 6.63673 |
August | 514.00000 | 24.28571 | 52.81721 | -0.2657 | 6.75348 |
September | 485.00000 | 24.37954 | 52.49677 | -0.2411 | 6.66735 |
October | 502.00000 | 24.43490 | 50.45024 | 0.59675 | 12.76965 |
November | 489.00000 | 24.45331 | 49.39823 | 0.58526 | 12.41384 |
December | 497.00000 | 24.42396 | 46.52701 | 0.53966 | 11.35400 |
Annual Sum or Average | 5943.00000 | 24.39736 | 48.96303 | 0.21275 | 9.52942 |
Minimum of Months | 454.00000 | 24.28571 | 42.26180 | -0.2657 | 6.63673 |
Maximum of Months | 514.00000 | 24.45331 | 53.12626 | 0.59675 | 12.76965 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.10861 | 42.94307 | 0.40306 | 8.61013 |
February | 454.00000 | 24.18053 | 45.99306 | 0.44834 | 9.41539 |
March | 514.00000 | 24.21756 | 45.38437 | 0.46560 | 9.71811 |
April | 485.00000 | 24.27385 | 48.67632 | 0.51449 | 10.74278 |
May | 508.00000 | 24.32776 | 51.64693 | -0.2887 | 7.15953 |
June | 496.00000 | 24.30767 | 54.85983 | -0.2672 | 6.88221 |
July | 497.00000 | 24.29737 | 55.15576 | -0.2662 | 6.77313 |
August | 514.00000 | 24.25508 | 55.85172 | -0.2723 | 6.80557 |
September | 485.00000 | 24.34308 | 55.24369 | -0.2546 | 6.78932 |
October | 502.00000 | 24.37068 | 52.59586 | 0.57913 | 12.30179 |
November | 489.00000 | 24.31934 | 50.61116 | 0.53874 | 11.23862 |
December | 497.00000 | 24.16807 | 46.85905 | 0.45312 | 9.51847 |
Annual Sum or Average | 5943.00000 | 24.26440 | 50.50905 | 0.16812 | 8.81909 |
Minimum of Months | 454.00000 | 24.10861 | 42.94307 | -0.2887 | 6.77313 |
Maximum of Months | 514.00000 | 24.37068 | 55.85172 | 0.57913 | 12.30179 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.72557 | 42.63201 | 0.29623 | 7.27060 |
February | 454.00000 | 23.90322 | 45.46876 | 0.37160 | 8.26608 |
March | 514.00000 | 24.07070 | 44.61953 | 0.42399 | 9.04955 |
April | 485.00000 | 24.24387 | 47.85709 | 0.50820 | 10.64836 |
May | 508.00000 | 24.36569 | 51.17137 | -0.2566 | 6.91374 |
June | 496.00000 | 24.34735 | 54.81239 | -0.2276 | 6.59128 |
July | 497.00000 | 24.37511 | 55.01705 | -0.2093 | 6.43088 |
August | 514.00000 | 24.30265 | 55.89577 | -0.2250 | 6.45509 |
September | 485.00000 | 24.38484 | 55.33712 | -0.2187 | 6.58868 |
October | 502.00000 | 24.37243 | 52.33872 | 0.58502 | 12.46407 |
November | 489.00000 | 24.22597 | 50.04511 | 0.51036 | 10.63030 |
December | 497.00000 | 23.86392 | 46.24808 | 0.36660 | 8.21455 |
Annual Sum or Average | 5943.00000 | 24.18332 | 50.14555 | 0.15788 | 8.28662 |
Minimum of Months | 454.00000 | 23.72557 | 42.63201 | -0.2566 | 6.43088 |
Maximum of Months | 514.00000 | 24.38484 | 55.89577 | 0.58502 | 12.46407 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.30330 | 45.37978 | 0.20539 | 6.96091 |
February | 454.00000 | 23.63387 | 48.32688 | 0.32490 | 8.15363 |
March | 514.00000 | 23.94662 | 46.22016 | 0.41416 | 9.29145 |
April | 485.00000 | 24.30324 | 49.30306 | 0.55821 | 12.21632 |
May | 508.00000 | 24.55725 | 51.43470 | -0.1132 | 6.73590 |
June | 496.00000 | 24.55820 | 55.57800 | -0.0556 | 6.56401 |
July | 497.00000 | 24.68458 | 55.31179 | 0.00088 | 6.81737 |
August | 514.00000 | 24.55330 | 56.36506 | -0.0363 | 6.45339 |
September | 485.00000 | 24.59060 | 56.64598 | -0.0664 | 6.76106 |
October | 502.00000 | 24.51451 | 53.87630 | 0.66159 | 14.92882 |
November | 489.00000 | 24.21274 | 51.76244 | 0.52866 | 11.30970 |
December | 497.00000 | 23.60372 | 49.13140 | 0.31802 | 8.03324 |
Annual Sum or Average | 5943.00000 | 24.20866 | 51.62320 | 0.22673 | 8.67845 |
Minimum of Months | 454.00000 | 23.30330 | 45.37978 | -0.1132 | 6.45339 |
Maximum of Months | 514.00000 | 24.68458 | 56.64598 | 0.66159 | 14.92882 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.48580 | 44.67937 | 0.26823 | 7.68434 |
February | 454.00000 | 23.75137 | 47.76483 | 0.37544 | 9.02431 |
March | 514.00000 | 23.99954 | 45.87330 | 0.45315 | 10.19483 |
April | 485.00000 | 24.37359 | 48.83941 | 0.60997 | 13.76880 |
May | 508.00000 | 24.58396 | 51.18899 | -0.0481 | 6.80731 |
June | 496.00000 | 24.56376 | 55.37831 | -0.0060 | 6.65395 |
July | 497.00000 | 24.69352 | 55.12606 | 0.05206 | 7.12343 |
August | 514.00000 | 24.55928 | 56.15724 | 0.02025 | 6.57109 |
September | 485.00000 | 24.61479 | 56.27392 | -0.0041 | 6.94681 |
October | 502.00000 | 24.57151 | 53.38066 | 0.70947 | 16.51188 |
November | 489.00000 | 24.29902 | 51.32744 | 0.57713 | 12.63231 |
December | 497.00000 | 23.70657 | 48.64849 | 0.36195 | 8.71355 |
Annual Sum or Average | 5943.00000 | 24.26987 | 51.23368 | 0.27914 | 9.37489 |
Minimum of Months | 454.00000 | 23.48580 | 44.67937 | -0.0481 | 6.57109 |
Maximum of Months | 514.00000 | 24.69352 | 56.27392 | 0.70947 | 16.51188 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.76964 | 43.31081 | 0.35613 | 9.37724 |
February | 454.00000 | 23.90822 | 46.86773 | 0.43156 | 10.32458 |
March | 514.00000 | 24.04648 | 45.49922 | 0.47064 | 10.65212 |
April | 485.00000 | 24.32210 | 49.01327 | 0.58001 | 12.91634 |
May | 508.00000 | 24.53414 | 51.43822 | -0.1195 | 6.75788 |
June | 496.00000 | 24.53111 | 55.65884 | -0.0748 | 6.54068 |
July | 497.00000 | 24.66062 | 55.34724 | -0.0097 | 6.75853 |
August | 514.00000 | 24.54749 | 56.25782 | -0.0228 | 6.47046 |
September | 485.00000 | 24.61266 | 56.24725 | -0.0132 | 6.92774 |
October | 502.00000 | 24.60019 | 53.11242 | 0.73428 | 17.36885 |
November | 489.00000 | 24.41560 | 50.56050 | 0.63561 | 14.46276 |
December | 497.00000 | 23.99331 | 47.23004 | 0.45570 | 10.88307 |
Annual Sum or Average | 5943.00000 | 24.33075 | 50.89673 | 0.28320 | 9.93718 |
Minimum of Months | 454.00000 | 23.76964 | 43.31081 | -0.1195 | 6.47046 |
Maximum of Months | 514.00000 | 24.66062 | 56.25782 | 0.73428 | 17.36885 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.23229 | 45.07897 | 0.21371 | 7.52197 |
February | 454.00000 | 23.56268 | 48.08095 | 0.33653 | 8.75216 |
March | 514.00000 | 23.89601 | 45.99735 | 0.43384 | 10.06129 |
April | 485.00000 | 24.26931 | 49.09267 | 0.58106 | 13.11115 |
May | 508.00000 | 24.53845 | 51.32550 | -0.0763 | 6.93821 |
June | 496.00000 | 24.54814 | 55.45010 | -0.0188 | 6.75434 |
July | 497.00000 | 24.66130 | 55.21441 | 0.03318 | 7.04396 |
August | 514.00000 | 24.54253 | 56.23718 | 0.00645 | 6.62444 |
September | 485.00000 | 24.59028 | 56.35336 | -0.0199 | 6.99136 |
October | 502.00000 | 24.49806 | 53.64471 | 0.68887 | 15.87847 |
November | 489.00000 | 24.17549 | 51.55253 | 0.54966 | 12.13232 |
December | 497.00000 | 23.52395 | 48.89576 | 0.32515 | 8.56001 |
Annual Sum or Average | 5943.00000 | 24.17360 | 51.42293 | 0.25293 | 9.18885 |
Minimum of Months | 454.00000 | 23.23229 | 45.07897 | -0.0763 | 6.62444 |
Maximum of Months | 514.00000 | 24.66130 | 56.35336 | 0.68887 | 15.87847 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.98616 | 45.15666 | 0.38608 | 8.41686 |
February | 454.00000 | 24.06006 | 48.37381 | 0.43383 | 9.26235 |
March | 514.00000 | 24.11995 | 46.93180 | 0.45326 | 9.58828 |
April | 485.00000 | 24.31129 | 49.26473 | 0.54125 | 11.45605 |
May | 508.00000 | 24.52713 | 50.62855 | -0.1620 | 6.54515 |
June | 496.00000 | 24.53335 | 53.87013 | -0.1038 | 6.32617 |
July | 497.00000 | 24.65801 | 52.84168 | -0.0506 | 6.42699 |
August | 514.00000 | 24.53412 | 52.90349 | -0.0749 | 6.25388 |
September | 485.00000 | 24.58896 | 53.11909 | -0.0876 | 6.45611 |
October | 502.00000 | 24.57881 | 51.26622 | 0.67274 | 15.10749 |
November | 489.00000 | 24.43016 | 50.51938 | 0.59620 | 12.70328 |
December | 497.00000 | 24.17379 | 48.83398 | 0.47651 | 10.01686 |
Annual Sum or Average | 5943.00000 | 24.37688 | 50.31350 | 0.25448 | 9.03446 |
Minimum of Months | 454.00000 | 23.98616 | 45.15666 | -0.1620 | 6.25388 |
Maximum of Months | 514.00000 | 24.65801 | 53.87013 | 0.67274 | 15.10749 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.10537 | 44.65177 | 0.43764 | 9.42413 |
February | 454.00000 | 24.16302 | 47.90656 | 0.48234 | 10.32578 |
March | 514.00000 | 24.18556 | 46.58345 | 0.49492 | 10.57224 |
April | 485.00000 | 24.41953 | 48.72663 | 0.60044 | 13.13491 |
May | 508.00000 | 24.58124 | 50.27806 | -0.0878 | 6.45879 |
June | 496.00000 | 24.55802 | 53.62220 | -0.0477 | 6.31806 |
July | 497.00000 | 24.68523 | 52.60435 | 0.00658 | 6.60805 |
August | 514.00000 | 24.55456 | 52.67080 | -0.0122 | 6.26851 |
September | 485.00000 | 24.63032 | 52.75394 | -0.0183 | 6.55548 |
October | 502.00000 | 24.64431 | 50.84269 | 0.72426 | 16.78423 |
November | 489.00000 | 24.52227 | 50.17713 | 0.64730 | 14.21646 |
December | 497.00000 | 24.24518 | 48.53643 | 0.51507 | 10.92381 |
Annual Sum or Average | 5943.00000 | 24.44250 | 49.95188 | 0.30964 | 9.78134 |
Minimum of Months | 454.00000 | 24.10537 | 44.65177 | -0.0878 | 6.26851 |
Maximum of Months | 514.00000 | 24.68523 | 53.62220 | 0.72426 | 16.78423 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.17347 | 44.26759 | 0.49311 | 11.13099 |
February | 454.00000 | 24.21062 | 48.12302 | 0.52736 | 11.70565 |
March | 514.00000 | 24.17975 | 46.85075 | 0.50875 | 11.13378 |
April | 485.00000 | 24.38346 | 49.92250 | 0.58104 | 12.65795 |
May | 508.00000 | 24.68251 | 52.01512 | -0.1077 | 6.43090 |
June | 496.00000 | 24.73737 | 56.98677 | -0.0366 | 6.31988 |
July | 497.00000 | 24.90368 | 57.51563 | 0.04792 | 6.69814 |
August | 514.00000 | 24.86580 | 58.35130 | 0.07532 | 6.87998 |
September | 485.00000 | 24.87627 | 56.96502 | 0.07512 | 6.89415 |
October | 502.00000 | 24.85623 | 53.34382 | 0.80919 | 19.61363 |
November | 489.00000 | 24.64861 | 51.94830 | 0.72890 | 16.85286 |
December | 497.00000 | 24.34277 | 48.74592 | 0.58421 | 13.10415 |
Annual Sum or Average | 5943.00000 | 24.57379 | 52.10616 | 0.35493 | 10.76466 |
Minimum of Months | 454.00000 | 24.17347 | 44.26759 | -0.1077 | 6.31988 |
Maximum of Months | 514.00000 | 24.90368 | 58.35130 | 0.80919 | 19.61363 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.04257 | 44.77081 | 0.42084 | 9.17158 |
February | 454.00000 | 24.12159 | 47.95939 | 0.47231 | 10.15367 |
March | 514.00000 | 24.18345 | 46.51671 | 0.49663 | 10.62338 |
April | 485.00000 | 24.37540 | 48.90434 | 0.58539 | 12.71877 |
May | 508.00000 | 24.55934 | 50.42469 | -0.1069 | 6.48841 |
June | 496.00000 | 24.56278 | 53.67196 | -0.0521 | 6.37737 |
July | 497.00000 | 24.67623 | 52.66845 | -0.0036 | 6.55353 |
August | 514.00000 | 24.55831 | 52.74438 | -0.0185 | 6.32838 |
September | 485.00000 | 24.63060 | 52.83501 | -0.0249 | 6.56703 |
October | 502.00000 | 24.62551 | 51.01408 | 0.71577 | 16.48314 |
November | 489.00000 | 24.49195 | 50.24545 | 0.63882 | 13.96665 |
December | 497.00000 | 24.21999 | 48.52129 | 0.50950 | 10.84820 |
Annual Sum or Average | 5943.00000 | 24.42218 | 50.02856 | 0.30056 | 9.67405 |
Minimum of Months | 454.00000 | 24.04257 | 44.77081 | -0.1069 | 6.32838 |
Maximum of Months | 514.00000 | 24.67623 | 53.67196 | 0.71577 | 16.48314 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.77446 | 45.37081 | 0.32583 | 7.67852 |
February | 454.00000 | 23.97082 | 48.42298 | 0.40953 | 8.93851 |
March | 514.00000 | 24.13199 | 46.67073 | 0.46036 | 9.76704 |
April | 485.00000 | 24.37153 | 49.73854 | 0.56850 | 12.22516 |
May | 508.00000 | 24.56019 | 51.70489 | -0.1372 | 6.65958 |
June | 496.00000 | 24.55274 | 55.41398 | -0.0893 | 6.50268 |
July | 497.00000 | 24.67694 | 55.17424 | -0.0404 | 6.63552 |
August | 514.00000 | 24.54457 | 56.10712 | -0.0760 | 6.39906 |
September | 485.00000 | 24.58668 | 56.33292 | -0.0952 | 6.67320 |
October | 502.00000 | 24.53984 | 53.86649 | 0.65755 | 14.74984 |
November | 489.00000 | 24.32963 | 51.89208 | 0.55711 | 11.76447 |
December | 497.00000 | 23.96484 | 49.27161 | 0.41127 | 8.96396 |
Annual Sum or Average | 5943.00000 | 24.33584 | 51.67590 | 0.24390 | 8.90230 |
Minimum of Months | 454.00000 | 23.77446 | 45.37081 | -0.1372 | 6.39906 |
Maximum of Months | 514.00000 | 24.67694 | 56.33292 | 0.65755 | 14.74984 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.82450 | 44.41360 | 0.34807 | 8.22900 |
February | 385.00000 | 24.02133 | 47.68837 | 0.43196 | 9.61074 |
March | 433.00000 | 24.17820 | 45.92638 | 0.48007 | 10.43460 |
April | 410.00000 | 24.50443 | 49.14527 | 0.61600 | 13.79569 |
May | 430.00000 | 24.68754 | 51.31959 | -0.0667 | 6.87318 |
June | 418.00000 | 24.65895 | 55.24957 | -0.0332 | 6.74057 |
July | 422.00000 | 24.80955 | 54.74551 | 0.02419 | 7.11926 |
August | 433.00000 | 24.65431 | 55.85345 | -0.0134 | 6.64134 |
September | 410.00000 | 24.72009 | 55.97665 | -0.0238 | 7.04110 |
October | 427.00000 | 24.68798 | 53.31440 | 0.70916 | 16.53198 |
November | 417.00000 | 24.46563 | 50.87192 | 0.59784 | 13.03529 |
December | 422.00000 | 23.99871 | 48.52387 | 0.42781 | 9.46752 |
Annual Sum or Average | 5034.00000 | 24.43622 | 51.09566 | 0.29005 | 9.61828 |
Minimum of Months | 385.00000 | 23.82450 | 44.41360 | -0.0667 | 6.64134 |
Maximum of Months | 433.00000 | 24.80955 | 55.97665 | 0.70916 | 16.53198 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.13902 | 43.56699 | 0.45413 | 10.28748 |
February | 454.00000 | 24.19353 | 47.10878 | 0.50374 | 11.12269 |
March | 514.00000 | 24.22723 | 45.97719 | 0.51387 | 11.09963 |
April | 485.00000 | 24.40651 | 49.44094 | 0.59234 | 12.94940 |
May | 508.00000 | 24.54488 | 51.71402 | -0.1413 | 6.65968 |
June | 496.00000 | 24.53037 | 55.51788 | -0.1063 | 6.49811 |
July | 497.00000 | 24.65807 | 55.21879 | -0.0492 | 6.58876 |
August | 514.00000 | 24.54468 | 55.98829 | -0.0616 | 6.38742 |
September | 485.00000 | 24.61516 | 55.91028 | -0.0424 | 6.72530 |
October | 502.00000 | 24.62793 | 53.07334 | 0.72814 | 17.06067 |
November | 489.00000 | 24.51694 | 50.77207 | 0.65795 | 14.82372 |
December | 497.00000 | 24.27022 | 47.60761 | 0.52987 | 11.83747 |
Annual Sum or Average | 5943.00000 | 24.44071 | 51.00897 | 0.29573 | 10.15007 |
Minimum of Months | 454.00000 | 24.13902 | 43.56699 | -0.1413 | 6.38742 |
Maximum of Months | 514.00000 | 24.65807 | 55.98829 | 0.72814 | 17.06067 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.72912 | 45.09412 | 0.33804 | 8.18921 |
February | 454.00000 | 23.93427 | 48.17059 | 0.42667 | 9.52882 |
March | 514.00000 | 24.11914 | 46.42413 | 0.48605 | 10.54325 |
April | 485.00000 | 24.37187 | 49.50159 | 0.59710 | 13.16655 |
May | 508.00000 | 24.55481 | 51.59398 | -0.0971 | 6.69531 |
June | 496.00000 | 24.55235 | 55.28854 | -0.0502 | 6.56688 |
July | 497.00000 | 24.66757 | 55.04262 | -0.0046 | 6.74409 |
August | 514.00000 | 24.54808 | 55.94753 | -0.0301 | 6.45940 |
September | 485.00000 | 24.59747 | 56.03737 | -0.0466 | 6.75331 |
October | 502.00000 | 24.54514 | 53.62756 | 0.68835 | 15.72694 |
November | 489.00000 | 24.33183 | 51.66767 | 0.58444 | 12.64756 |
December | 497.00000 | 23.92391 | 49.03145 | 0.42472 | 9.49369 |
Annual Sum or Average | 5943.00000 | 24.32525 | 51.46497 | 0.27438 | 9.36324 |
Minimum of Months | 454.00000 | 23.72912 | 45.09412 | -0.0971 | 6.45940 |
Maximum of Months | 514.00000 | 24.66757 | 56.03737 | 0.68835 | 15.72694 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.440946E+11 | 0.108569E+11 | 422.83 | 0.380820E+11 | 0.601263E+10 | 0.00 | 1.00 | 02-JAN-13:10 | 0.00 | 01-JAN-00:10 | 66592.69 | 30-JAN-05:03 | 53196.53 | 23-JAN-14:00 | 14667.83 | 30-JAN-14:50 | 15299.58 | 30-JAN-05:03 | 0.00 |
February | 0.461085E+11 | 0.114106E+11 | 381.39 | 0.390264E+11 | 0.708203E+10 | 0.00 | 1.00 | 01-FEB-13:30 | 0.00 | 01-FEB-00:10 | 83299.31 | 06-FEB-05:03 | 63203.07 | 06-FEB-15:00 | 26473.72 | 06-FEB-05:03 | 20304.54 | 07-FEB-13:03 | 0.00 |
March | 0.609332E+11 | 0.155479E+11 | 449.50 | 0.532815E+11 | 0.765164E+10 | 0.00 | 1.00 | 01-MAR-08:50 | 0.00 | 01-MAR-00:10 | 84796.24 | 28-MAR-11:40 | 76055.67 | 27-MAR-12:09 | 29487.71 | 29-MAR-04:03 | 25185.10 | 27-MAR-12:09 | 0.00 |
April | 0.716373E+11 | 0.191962E+11 | 438.75 | 0.609734E+11 | 0.106639E+11 | 0.00 | 1.00 | 03-APR-04:02 | 0.00 | 01-APR-00:10 | 92650.58 | 17-APR-04:02 | 78462.12 | 28-APR-12:02 | 32839.62 | 10-APR-11:50 | 29779.27 | 28-APR-12:00 | 0.00 |
May | 0.106072E+12 | 0.307825E+11 | 497.79 | 0.876381E+11 | 0.184344E+11 | 0.00 | 1.00 | 01-MAY-04:02 | 0.00 | 01-MAY-00:03 | 146509.67 | 24-MAY-04:03 | 97783.75 | 22-MAY-06:03 | 69895.26 | 24-MAY-04:03 | 37886.61 | 31-MAY-12:02 | 0.00 |
June | 0.127608E+12 | 0.372712E+11 | 500.44 | 0.938953E+11 | 0.337123E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:03 | 150975.24 | 14-JUN-04:02 | 96896.63 | 16-JUN-04:02 | 72315.72 | 08-JUN-04:03 | 39616.03 | 09-JUN-12:13 | 0.00 |
July | 0.153876E+12 | 0.456826E+11 | 566.15 | 0.103488E+12 | 0.503874E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 148358.61 | 06-JUL-04:02 | 97247.49 | 11-JUL-06:03 | 67112.93 | 30-JUL-16:21 | 42985.78 | 30-JUL-15:41 | 0.00 |
August | 0.171297E+12 | 0.510223E+11 | 594.04 | 0.113094E+12 | 0.582032E+11 | 0.00 | 1.00 | 01-AUG-00:23 | 0.00 | 01-AUG-00:03 | 146957.27 | 08-AUG-06:03 | 100387.37 | 07-AUG-06:03 | 67257.35 | 22-AUG-17:00 | 44041.41 | 10-AUG-15:50 | 0.00 |
September | 0.138076E+12 | 0.391420E+11 | 522.91 | 0.938285E+11 | 0.442477E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:25 | 149703.82 | 23-SEP-04:03 | 98597.17 | 05-SEP-06:03 | 70380.21 | 23-SEP-04:03 | 39909.12 | 10-SEP-15:31 | 0.00 |
October | 0.112514E+12 | 0.304959E+11 | 507.68 | 0.845700E+11 | 0.279436E+11 | 0.00 | 1.00 | 01-OCT-00:53 | 0.00 | 01-OCT-00:10 | 147724.49 | 18-OCT-04:02 | 94929.75 | 11-OCT-04:02 | 66679.66 | 07-OCT-04:03 | 35312.63 | 05-OCT-04:02 | 0.00 |
November | 0.824651E+11 | 0.211118E+11 | 451.89 | 0.662236E+11 | 0.162416E+11 | 0.00 | 1.00 | 01-NOV-04:03 | 0.00 | 01-NOV-00:10 | 132175.20 | 03-NOV-04:03 | 92842.47 | 20-NOV-05:02 | 54922.54 | 03-NOV-04:03 | 30272.30 | 03-NOV-04:03 | 0.00 |
December | 0.546881E+11 | 0.133853E+11 | 425.03 | 0.454073E+11 | 0.928081E+10 | 0.00 | 1.00 | 01-DEC-09:50 | 0.00 | 01-DEC-00:10 | 94439.09 | 11-DEC-05:02 | 66515.20 | 11-DEC-05:02 | 27923.89 | 11-DEC-05:02 | 21704.78 | 11-DEC-05:02 | 0.00 |
Annual Sum or Average | 0.116937E+13 | 0.325905E+12 | 5758.41 | 0.879508E+12 | 0.289861E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.440946E+11 | 0.108569E+11 | 381.39 | 0.380820E+11 | 0.601263E+10 | 0.00 | 1.00 | 0.00 | 66592.69 | 53196.53 | 14667.83 | 15299.58 | 0.00 | ||||||
Maximum of Months | 0.171297E+12 | 0.510223E+11 | 594.04 | 0.113094E+12 | 0.582032E+11 | 0.00 | 1.00 | 0.00 | 150975.24 | 100387.37 | 72315.72 | 44041.41 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.330536E+11 | 0.831304E+10 | 404.76 | 0.269125E+11 | 0.614113E+10 | 0.00 | 1.00 | 23-JAN-13:30 | 0.00 | 01-JAN-00:10 | 46122.82 | 30-JAN-14:00 | 41097.26 | 23-JAN-14:00 | 13289.77 | 30-JAN-14:40 | 10607.52 | 30-JAN-14:00 | 0.00 |
February | 0.366854E+11 | 0.921221E+10 | 370.85 | 0.297786E+11 | 0.690673E+10 | 0.00 | 1.00 | 05-FEB-13:32 | 0.00 | 01-FEB-00:10 | 74283.41 | 09-FEB-06:03 | 56041.14 | 06-FEB-15:10 | 27757.26 | 09-FEB-06:03 | 17059.22 | 09-FEB-06:03 | 0.00 |
March | 0.507090E+11 | 0.130516E+11 | 440.94 | 0.433534E+11 | 0.735562E+10 | 0.00 | 1.00 | 01-MAR-06:03 | 0.00 | 01-MAR-00:10 | 66832.31 | 27-MAR-11:00 | 66832.31 | 27-MAR-11:00 | 15543.37 | 31-MAR-18:00 | 22775.68 | 27-MAR-11:00 | 0.00 |
April | 0.625153E+11 | 0.167630E+11 | 437.54 | 0.526090E+11 | 0.990635E+10 | 0.00 | 1.00 | 02-APR-10:53 | 0.00 | 01-APR-00:10 | 95225.64 | 17-APR-04:02 | 74911.99 | 17-APR-04:02 | 27876.47 | 20-APR-05:03 | 26130.05 | 28-APR-12:02 | 0.00 |
May | 0.940214E+11 | 0.270983E+11 | 499.34 | 0.775725E+11 | 0.164490E+11 | 0.00 | 1.00 | 01-MAY-04:02 | 0.00 | 01-MAY-00:35 | 135005.82 | 24-MAY-05:03 | 87111.89 | 22-MAY-04:02 | 67911.61 | 24-MAY-04:03 | 36103.31 | 29-MAY-15:11 | 0.00 |
June | 0.113748E+12 | 0.328867E+11 | 500.61 | 0.827555E+11 | 0.309926E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:03 | 138417.62 | 14-JUN-04:02 | 84959.01 | 01-JUN-04:02 | 70753.47 | 08-JUN-04:03 | 37929.60 | 04-JUN-15:51 | 0.00 |
July | 0.136385E+12 | 0.401277E+11 | 555.11 | 0.916124E+11 | 0.447722E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 137145.42 | 06-JUL-04:02 | 93996.28 | 30-JUL-13:52 | 65360.17 | 06-JUL-04:02 | 41877.47 | 30-JUL-14:32 | 0.00 |
August | 0.146631E+12 | 0.433433E+11 | 566.36 | 0.974283E+11 | 0.492024E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:13 | 136559.90 | 26-AUG-04:02 | 89219.73 | 07-AUG-06:03 | 64455.33 | 26-AUG-04:02 | 40630.80 | 13-AUG-13:13 | 0.00 |
September | 0.115804E+12 | 0.325955E+11 | 488.99 | 0.786817E+11 | 0.371228E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:25 | 136997.52 | 28-SEP-04:02 | 90986.23 | 04-SEP-14:41 | 68762.22 | 23-SEP-05:03 | 40149.01 | 04-SEP-14:01 | 0.00 |
October | 0.910501E+11 | 0.245987E+11 | 473.61 | 0.684253E+11 | 0.226248E+11 | 0.00 | 1.00 | 01-OCT-07:07 | 0.00 | 01-OCT-00:10 | 134513.57 | 02-OCT-04:03 | 86313.71 | 10-OCT-04:02 | 61018.07 | 18-OCT-04:02 | 32138.56 | 05-OCT-04:02 | 0.00 |
November | 0.639420E+11 | 0.164314E+11 | 425.47 | 0.502745E+11 | 0.136674E+11 | 0.00 | 1.00 | 01-NOV-04:03 | 0.00 | 01-NOV-00:10 | 103568.99 | 03-NOV-05:03 | 77610.57 | 20-NOV-05:02 | 45833.10 | 03-NOV-05:03 | 23626.35 | 03-NOV-05:03 | 0.00 |
December | 0.415914E+11 | 0.103565E+11 | 406.89 | 0.326664E+11 | 0.892496E+10 | 0.00 | 1.00 | 01-DEC-11:30 | 0.00 | 01-DEC-00:10 | 67424.21 | 11-DEC-06:03 | 47699.97 | 04-DEC-13:50 | 23839.72 | 11-DEC-06:03 | 15503.72 | 11-DEC-06:03 | 0.00 |
Annual Sum or Average | 0.986136E+12 | 0.274778E+12 | 5570.48 | 0.732070E+12 | 0.254066E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.330536E+11 | 0.831304E+10 | 370.85 | 0.269125E+11 | 0.614113E+10 | 0.00 | 1.00 | 0.00 | 46122.82 | 41097.26 | 13289.77 | 10607.52 | 0.00 | ||||||
Maximum of Months | 0.146631E+12 | 0.433433E+11 | 566.36 | 0.974283E+11 | 0.492024E+11 | 0.00 | 1.00 | 0.00 | 138417.62 | 93996.28 | 70753.47 | 41877.47 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.329229E+11 | 0.843100E+10 | 401.53 | 0.257455E+11 | 0.717735E+10 | 0.00 | 0.95 | 23-JAN-14:00 | 0.00 | 01-JAN-00:10 | 46341.48 | 30-JAN-14:30 | 43974.26 | 23-JAN-14:00 | 13925.92 | 30-JAN-15:10 | 11318.75 | 23-JAN-14:00 | 0.00 |
February | 0.377334E+11 | 0.962687E+10 | 369.03 | 0.300054E+11 | 0.772800E+10 | 0.00 | 1.00 | 05-FEB-12:43 | 0.00 | 01-FEB-00:10 | 70615.07 | 07-FEB-15:30 | 63300.46 | 06-FEB-15:00 | 17308.50 | 07-FEB-16:00 | 17939.95 | 06-FEB-15:00 | 0.00 |
March | 0.533822E+11 | 0.139228E+11 | 437.56 | 0.451884E+11 | 0.819379E+10 | 0.00 | 1.00 | 01-MAR-11:00 | 0.00 | 01-MAR-00:10 | 76986.77 | 27-MAR-13:10 | 76986.77 | 27-MAR-13:10 | 16845.55 | 31-MAR-18:00 | 25043.85 | 27-MAR-12:03 | 0.00 |
April | 0.675436E+11 | 0.183075E+11 | 435.39 | 0.569157E+11 | 0.106279E+11 | 0.00 | 1.00 | 02-APR-13:43 | 0.00 | 01-APR-00:10 | 98527.86 | 30-APR-12:43 | 91153.94 | 30-APR-12:43 | 29917.15 | 30-APR-18:03 | 30990.63 | 28-APR-12:02 | 0.00 |
May | 0.103794E+12 | 0.300951E+11 | 504.81 | 0.865941E+11 | 0.171997E+11 | 0.00 | 1.00 | 01-MAY-04:02 | 0.00 | 01-MAY-00:03 | 155111.71 | 31-MAY-04:02 | 107381.60 | 21-MAY-13:12 | 74378.92 | 24-MAY-04:03 | 38472.30 | 21-MAY-13:12 | 0.00 |
June | 0.125562E+12 | 0.364408E+11 | 511.34 | 0.933834E+11 | 0.321781E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:15 | 161355.13 | 14-JUN-04:02 | 101273.24 | 01-JUN-04:02 | 82177.48 | 14-JUN-04:02 | 44215.01 | 11-JUN-14:52 | 0.00 |
July | 0.152590E+12 | 0.450152E+11 | 575.37 | 0.105515E+12 | 0.470750E+11 | 0.00 | 1.00 | 01-JUL-02:42 | 0.00 | 01-JUL-00:10 | 159045.44 | 06-JUL-04:02 | 116935.05 | 30-JUL-13:52 | 73292.15 | 06-JUL-04:02 | 48817.68 | 30-JUL-14:32 | 0.00 |
August | 0.162567E+12 | 0.481579E+11 | 586.92 | 0.111263E+12 | 0.513034E+11 | 0.00 | 1.00 | 01-AUG-00:27 | 0.00 | 01-AUG-00:03 | 158234.08 | 26-AUG-04:02 | 110938.05 | 06-AUG-15:01 | 71116.89 | 26-AUG-04:02 | 47619.76 | 06-AUG-15:01 | 0.00 |
September | 0.125863E+12 | 0.355530E+11 | 498.91 | 0.876139E+11 | 0.382489E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:03 | 159890.66 | 28-SEP-04:02 | 112009.59 | 04-SEP-14:12 | 77065.12 | 28-SEP-04:02 | 47063.77 | 04-SEP-14:12 | 0.00 |
October | 0.959689E+11 | 0.261321E+11 | 472.24 | 0.728603E+11 | 0.231085E+11 | 0.00 | 1.00 | 01-OCT-07:12 | 0.00 | 01-OCT-00:10 | 152482.42 | 05-OCT-04:02 | 97088.96 | 09-OCT-14:42 | 70033.98 | 06-OCT-04:02 | 36995.75 | 05-OCT-04:02 | 0.00 |
November | 0.652481E+11 | 0.169596E+11 | 417.17 | 0.511324E+11 | 0.141157E+11 | 0.00 | 1.00 | 01-NOV-05:03 | 0.00 | 01-NOV-00:10 | 94034.59 | 01-NOV-14:00 | 70084.26 | 06-NOV-14:10 | 29909.02 | 03-NOV-05:03 | 25820.38 | 01-NOV-14:00 | 0.00 |
December | 0.418164E+11 | 0.106022E+11 | 403.28 | 0.319034E+11 | 0.991303E+10 | 0.00 | 1.00 | 01-DEC-13:10 | 0.00 | 01-DEC-00:10 | 74212.55 | 11-DEC-06:03 | 51579.57 | 04-DEC-14:10 | 29570.04 | 11-DEC-06:03 | 17062.86 | 11-DEC-06:03 | 0.00 |
Annual Sum or Average | 0.106499E+13 | 0.299244E+12 | 5613.54 | 0.798120E+12 | 0.266869E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.329229E+11 | 0.843100E+10 | 369.03 | 0.257455E+11 | 0.717735E+10 | 0.00 | 0.95 | 0.00 | 46341.48 | 43974.26 | 13925.92 | 11318.75 | 0.00 | ||||||
Maximum of Months | 0.162567E+12 | 0.481579E+11 | 586.92 | 0.111263E+12 | 0.513034E+11 | 0.00 | 1.00 | 0.00 | 161355.13 | 116935.05 | 82177.48 | 48817.68 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 355.41 | 0.00 | 355.41 | 399.25 | 614.27 | 0.00 | 0.00 | 0.00 |
February | 407.41 | 0.00 | 407.41 | 535.53 | 515.81 | 0.00 | 0.00 | 0.00 |
March | 467.96 | 0.00 | 467.96 | 747.87 | 395.96 | 0.00 | 0.00 | 0.00 |
April | 527.24 | 1.09 | 526.15 | 1057.35 | 252.08 | 0.00 | 0.00 | 0.00 |
May | 593.46 | 17.41 | 576.05 | 1570.86 | 64.55 | 0.00 | 0.00 | 0.00 |
June | 635.41 | 35.28 | 600.13 | 1809.64 | 16.75 | 0.00 | 0.00 | 0.00 |
July | 583.05 | 16.80 | 566.25 | 1999.95 | 0.33 | 0.00 | 0.00 | 0.00 |
August | 542.77 | 4.49 | 538.28 | 1965.89 | 0.09 | 0.00 | 0.00 | 0.00 |
September | 494.41 | 0.06 | 494.35 | 1491.10 | 24.18 | 0.00 | 0.00 | 0.00 |
October | 438.28 | 0.00 | 438.28 | 1082.47 | 104.87 | 0.00 | 0.00 | 0.00 |
November | 376.26 | 0.00 | 376.26 | 704.19 | 285.62 | 0.00 | 0.00 | 0.00 |
December | 331.73 | 0.00 | 331.73 | 437.76 | 502.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 479.72 | 6.28 | 473.44 | 1153.94 | 230.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 331.73 | 0.00 | 331.73 | 399.25 | 0.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 635.41 | 35.28 | 600.13 | 1999.95 | 614.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 428.62 | 129.68 | 298.94 | 566.31 | 387.25 | 0.00 | 0.00 | 0.00 |
February | 467.10 | 126.59 | 340.51 | 673.79 | 327.67 | 0.00 | 0.00 | 0.00 |
March | 515.96 | 127.16 | 388.79 | 841.40 | 253.23 | 0.00 | 0.00 | 0.00 |
April | 628.20 | 183.04 | 445.16 | 1181.13 | 162.96 | 0.00 | 0.00 | 0.00 |
May | 702.03 | 223.67 | 478.36 | 1571.70 | 40.86 | 0.00 | 0.00 | 0.00 |
June | 687.53 | 210.25 | 477.28 | 1652.61 | 9.74 | 0.00 | 0.00 | 0.00 |
July | 641.71 | 185.00 | 456.70 | 1771.02 | 0.14 | 0.00 | 0.00 | 0.00 |
August | 657.10 | 201.67 | 455.42 | 1828.56 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 617.75 | 190.94 | 426.81 | 1494.57 | 14.30 | 0.00 | 0.00 | 0.00 |
October | 560.54 | 183.13 | 377.41 | 1182.22 | 64.19 | 0.00 | 0.00 | 0.00 |
November | 469.74 | 148.79 | 320.95 | 836.46 | 181.44 | 0.00 | 0.00 | 0.00 |
December | 380.21 | 104.31 | 275.89 | 547.41 | 319.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 563.41 | 168.02 | 395.39 | 1181.85 | 145.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 380.21 | 104.31 | 275.89 | 547.41 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 702.03 | 223.67 | 478.36 | 1828.56 | 387.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1148.64 | 540.03 | 608.62 | 1704.08 | 604.41 | 0.00 | 0.00 | 0.00 |
February | 1078.63 | 441.20 | 637.42 | 1689.51 | 516.60 | 0.00 | 0.00 | 0.00 |
March | 887.76 | 241.02 | 646.74 | 1539.20 | 404.42 | 0.00 | 0.00 | 0.00 |
April | 697.85 | 73.98 | 623.86 | 1413.29 | 257.09 | 0.00 | 0.00 | 0.00 |
May | 591.14 | 9.05 | 582.08 | 1567.57 | 64.11 | 0.00 | 0.00 | 0.00 |
June | 556.72 | 0.69 | 556.03 | 1655.25 | 13.19 | 0.00 | 0.00 | 0.00 |
July | 556.70 | 4.73 | 551.97 | 1940.80 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 645.73 | 45.75 | 599.98 | 2181.30 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 851.40 | 195.12 | 656.28 | 2191.58 | 23.93 | 0.00 | 0.00 | 0.00 |
October | 1114.64 | 443.13 | 671.51 | 2311.68 | 104.87 | 0.00 | 0.00 | 0.00 |
November | 1229.68 | 592.80 | 636.88 | 2178.77 | 289.07 | 0.00 | 0.00 | 0.00 |
December | 1141.51 | 563.87 | 577.64 | 1792.20 | 504.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 873.81 | 261.66 | 612.15 | 1848.26 | 230.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 556.70 | 0.69 | 551.97 | 1413.29 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1229.68 | 592.80 | 671.51 | 2311.68 | 604.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 420.34 | 120.73 | 299.62 | 578.44 | 409.31 | 0.00 | 0.00 | 0.00 |
February | 479.99 | 136.87 | 343.12 | 716.45 | 344.61 | 0.00 | 0.00 | 0.00 |
March | 568.56 | 168.32 | 400.24 | 942.44 | 268.91 | 0.00 | 0.00 | 0.00 |
April | 621.34 | 174.56 | 446.78 | 1173.78 | 175.93 | 0.00 | 0.00 | 0.00 |
May | 676.32 | 202.45 | 473.87 | 1533.83 | 46.82 | 0.00 | 0.00 | 0.00 |
June | 698.93 | 220.32 | 478.61 | 1678.53 | 10.91 | 0.00 | 0.00 | 0.00 |
July | 641.19 | 183.43 | 457.76 | 1769.04 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 657.79 | 200.00 | 457.79 | 1821.52 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 625.73 | 196.58 | 429.14 | 1507.93 | 17.44 | 0.00 | 0.00 | 0.00 |
October | 556.09 | 179.63 | 376.46 | 1181.73 | 73.81 | 0.00 | 0.00 | 0.00 |
November | 477.89 | 156.28 | 321.60 | 868.98 | 195.35 | 0.00 | 0.00 | 0.00 |
December | 400.07 | 120.93 | 279.13 | 605.08 | 337.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 569.01 | 171.79 | 397.21 | 1200.91 | 155.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 400.07 | 120.73 | 279.13 | 578.44 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 698.93 | 220.32 | 478.61 | 1821.52 | 409.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.47 | 0.00 | 118.47 | 125.76 | 236.04 | 0.00 | 0.00 | 0.00 |
February | 135.80 | 0.00 | 135.80 | 175.14 | 191.49 | 0.00 | 0.00 | 0.00 |
March | 155.98 | 0.00 | 155.98 | 250.62 | 139.95 | 0.00 | 0.00 | 0.00 |
April | 175.74 | 0.36 | 175.38 | 357.24 | 84.30 | 0.00 | 0.00 | 0.00 |
May | 197.81 | 5.80 | 192.01 | 528.41 | 20.54 | 0.00 | 0.00 | 0.00 |
June | 211.79 | 11.76 | 200.03 | 605.83 | 5.29 | 0.00 | 0.00 | 0.00 |
July | 194.34 | 5.60 | 188.74 | 667.93 | 0.13 | 0.00 | 0.00 | 0.00 |
August | 180.91 | 1.50 | 179.42 | 651.84 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 164.80 | 0.02 | 164.78 | 492.74 | 9.30 | 0.00 | 0.00 | 0.00 |
October | 146.09 | 0.00 | 146.09 | 355.04 | 40.84 | 0.00 | 0.00 | 0.00 |
November | 125.41 | 0.00 | 125.41 | 228.34 | 110.92 | 0.00 | 0.00 | 0.00 |
December | 110.57 | 0.00 | 110.57 | 138.39 | 195.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.90 | 2.09 | 157.81 | 382.70 | 85.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.57 | 0.00 | 110.57 | 125.76 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.79 | 11.76 | 200.03 | 667.93 | 236.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.47 | 0.00 | 118.47 | 125.77 | 236.05 | 0.00 | 0.00 | 0.00 |
February | 135.80 | 0.00 | 135.80 | 175.15 | 191.50 | 0.00 | 0.00 | 0.00 |
March | 155.99 | 0.00 | 155.99 | 250.63 | 139.96 | 0.00 | 0.00 | 0.00 |
April | 175.75 | 0.36 | 175.39 | 357.26 | 84.31 | 0.00 | 0.00 | 0.00 |
May | 197.82 | 5.80 | 192.02 | 528.44 | 20.54 | 0.00 | 0.00 | 0.00 |
June | 211.81 | 11.76 | 200.05 | 605.87 | 5.29 | 0.00 | 0.00 | 0.00 |
July | 194.35 | 5.60 | 188.75 | 667.97 | 0.13 | 0.00 | 0.00 | 0.00 |
August | 180.93 | 1.50 | 179.43 | 651.88 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 164.81 | 0.02 | 164.79 | 492.77 | 9.30 | 0.00 | 0.00 | 0.00 |
October | 146.10 | 0.00 | 146.10 | 355.06 | 40.84 | 0.00 | 0.00 | 0.00 |
November | 125.42 | 0.00 | 125.42 | 228.36 | 110.93 | 0.00 | 0.00 | 0.00 |
December | 110.58 | 0.00 | 110.58 | 138.40 | 195.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.91 | 2.09 | 157.82 | 382.73 | 85.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.58 | 0.00 | 110.58 | 125.77 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.81 | 11.76 | 200.05 | 667.97 | 236.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.47 | 0.00 | 118.47 | 125.77 | 236.05 | 0.00 | 0.00 | 0.00 |
February | 135.80 | 0.00 | 135.80 | 175.15 | 191.50 | 0.00 | 0.00 | 0.00 |
March | 155.99 | 0.00 | 155.99 | 250.63 | 139.96 | 0.00 | 0.00 | 0.00 |
April | 175.75 | 0.36 | 175.39 | 357.26 | 84.31 | 0.00 | 0.00 | 0.00 |
May | 197.82 | 5.80 | 192.02 | 528.44 | 20.54 | 0.00 | 0.00 | 0.00 |
June | 211.81 | 11.76 | 200.05 | 605.87 | 5.29 | 0.00 | 0.00 | 0.00 |
July | 194.35 | 5.60 | 188.75 | 667.97 | 0.13 | 0.00 | 0.00 | 0.00 |
August | 180.93 | 1.50 | 179.43 | 651.88 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 164.81 | 0.02 | 164.79 | 492.77 | 9.30 | 0.00 | 0.00 | 0.00 |
October | 146.10 | 0.00 | 146.10 | 355.06 | 40.84 | 0.00 | 0.00 | 0.00 |
November | 125.42 | 0.00 | 125.42 | 228.36 | 110.93 | 0.00 | 0.00 | 0.00 |
December | 110.58 | 0.00 | 110.58 | 138.40 | 195.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.91 | 2.09 | 157.82 | 382.73 | 85.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.58 | 0.00 | 110.58 | 125.77 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.81 | 11.76 | 200.05 | 667.97 | 236.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 412.32 | 124.75 | 287.57 | 527.84 | 429.46 | 0.00 | 0.00 | 0.00 |
February | 449.33 | 121.77 | 327.56 | 641.04 | 353.21 | 0.00 | 0.00 | 0.00 |
March | 496.33 | 122.33 | 374.00 | 812.40 | 261.27 | 0.00 | 0.00 | 0.00 |
April | 604.30 | 176.07 | 428.23 | 1146.44 | 161.87 | 0.00 | 0.00 | 0.00 |
May | 675.33 | 215.16 | 460.16 | 1521.23 | 40.29 | 0.00 | 0.00 | 0.00 |
June | 661.38 | 202.26 | 459.12 | 1594.59 | 10.02 | 0.00 | 0.00 | 0.00 |
July | 617.29 | 177.96 | 439.33 | 1704.72 | 0.24 | 0.00 | 0.00 | 0.00 |
August | 632.10 | 194.00 | 438.10 | 1751.10 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 594.25 | 183.67 | 410.57 | 1429.64 | 17.35 | 0.00 | 0.00 | 0.00 |
October | 539.22 | 176.16 | 363.06 | 1128.47 | 76.51 | 0.00 | 0.00 | 0.00 |
November | 451.87 | 143.13 | 308.74 | 793.31 | 206.90 | 0.00 | 0.00 | 0.00 |
December | 365.74 | 100.34 | 265.40 | 510.21 | 360.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 541.98 | 161.63 | 380.35 | 1132.89 | 158.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 365.74 | 100.34 | 265.40 | 510.21 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 675.33 | 215.16 | 460.16 | 1751.10 | 429.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.30 | 4.93 | 11.37 | 20.87 | 16.98 | 0.00 | 0.00 | 0.00 |
February | 17.77 | 4.81 | 12.95 | 25.35 | 13.97 | 0.00 | 0.00 | 0.00 |
March | 19.62 | 4.84 | 14.79 | 32.12 | 10.33 | 0.00 | 0.00 | 0.00 |
April | 23.89 | 6.96 | 16.93 | 45.33 | 6.40 | 0.00 | 0.00 | 0.00 |
May | 26.70 | 8.51 | 18.19 | 60.15 | 1.59 | 0.00 | 0.00 | 0.00 |
June | 26.15 | 8.00 | 18.15 | 63.05 | 0.40 | 0.00 | 0.00 | 0.00 |
July | 24.41 | 7.04 | 17.37 | 67.40 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 24.99 | 7.67 | 17.32 | 69.24 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23.50 | 7.26 | 16.23 | 56.53 | 0.69 | 0.00 | 0.00 | 0.00 |
October | 21.32 | 6.97 | 14.35 | 44.62 | 3.03 | 0.00 | 0.00 | 0.00 |
November | 17.87 | 5.66 | 12.21 | 31.37 | 8.18 | 0.00 | 0.00 | 0.00 |
December | 14.46 | 3.97 | 10.49 | 20.17 | 14.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.43 | 6.39 | 15.04 | 44.79 | 6.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.46 | 3.97 | 10.49 | 20.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.70 | 8.51 | 18.19 | 69.24 | 16.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 382.89 | 180.02 | 202.88 | 564.26 | 232.91 | 0.00 | 0.00 | 0.00 |
February | 359.55 | 147.07 | 212.48 | 563.33 | 194.43 | 0.00 | 0.00 | 0.00 |
March | 295.93 | 80.34 | 215.59 | 516.00 | 144.90 | 0.00 | 0.00 | 0.00 |
April | 232.62 | 24.66 | 207.96 | 475.53 | 87.58 | 0.00 | 0.00 | 0.00 |
May | 197.05 | 3.02 | 194.03 | 523.14 | 21.39 | 0.00 | 0.00 | 0.00 |
June | 185.58 | 0.23 | 185.35 | 547.90 | 4.67 | 0.00 | 0.00 | 0.00 |
July | 185.57 | 1.58 | 183.99 | 641.28 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 215.25 | 15.25 | 200.00 | 714.46 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 283.81 | 65.04 | 218.76 | 720.24 | 10.42 | 0.00 | 0.00 | 0.00 |
October | 371.56 | 147.72 | 223.84 | 763.16 | 45.10 | 0.00 | 0.00 | 0.00 |
November | 409.91 | 197.61 | 212.30 | 722.17 | 116.32 | 0.00 | 0.00 | 0.00 |
December | 380.52 | 187.96 | 192.55 | 593.51 | 196.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 291.28 | 87.22 | 204.05 | 612.43 | 87.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 185.57 | 0.23 | 183.99 | 475.53 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 409.91 | 197.61 | 223.84 | 763.16 | 232.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 382.89 | 180.02 | 202.88 | 564.26 | 232.91 | 0.00 | 0.00 | 0.00 |
February | 359.55 | 147.07 | 212.48 | 563.33 | 194.43 | 0.00 | 0.00 | 0.00 |
March | 295.93 | 80.34 | 215.59 | 516.00 | 144.90 | 0.00 | 0.00 | 0.00 |
April | 232.62 | 24.66 | 207.96 | 475.53 | 87.58 | 0.00 | 0.00 | 0.00 |
May | 197.05 | 3.02 | 194.03 | 523.14 | 21.39 | 0.00 | 0.00 | 0.00 |
June | 185.58 | 0.23 | 185.35 | 547.90 | 4.67 | 0.00 | 0.00 | 0.00 |
July | 185.57 | 1.58 | 183.99 | 641.28 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 215.25 | 15.25 | 200.00 | 714.46 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 283.81 | 65.04 | 218.76 | 720.24 | 10.42 | 0.00 | 0.00 | 0.00 |
October | 371.56 | 147.72 | 223.84 | 763.16 | 45.10 | 0.00 | 0.00 | 0.00 |
November | 409.91 | 197.61 | 212.30 | 722.17 | 116.32 | 0.00 | 0.00 | 0.00 |
December | 380.52 | 187.96 | 192.55 | 593.51 | 196.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 291.28 | 87.22 | 204.05 | 612.43 | 87.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 185.57 | 0.23 | 183.99 | 475.53 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 409.91 | 197.61 | 223.84 | 763.16 | 232.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 382.87 | 180.00 | 202.87 | 564.23 | 232.90 | 0.00 | 0.00 | 0.00 |
February | 359.53 | 147.06 | 212.47 | 563.29 | 194.42 | 0.00 | 0.00 | 0.00 |
March | 295.91 | 80.34 | 215.57 | 515.97 | 144.89 | 0.00 | 0.00 | 0.00 |
April | 232.61 | 24.66 | 207.95 | 475.50 | 87.57 | 0.00 | 0.00 | 0.00 |
May | 197.04 | 3.02 | 194.02 | 523.11 | 21.39 | 0.00 | 0.00 | 0.00 |
June | 185.56 | 0.23 | 185.34 | 547.86 | 4.67 | 0.00 | 0.00 | 0.00 |
July | 185.56 | 1.58 | 183.98 | 641.24 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 215.23 | 15.25 | 199.98 | 714.42 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 283.79 | 65.04 | 218.75 | 720.20 | 10.42 | 0.00 | 0.00 | 0.00 |
October | 371.54 | 147.71 | 223.83 | 763.11 | 45.10 | 0.00 | 0.00 | 0.00 |
November | 409.88 | 197.59 | 212.29 | 722.12 | 116.32 | 0.00 | 0.00 | 0.00 |
December | 380.49 | 187.95 | 192.54 | 593.47 | 196.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 291.26 | 87.22 | 204.04 | 612.40 | 87.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 185.56 | 0.23 | 183.98 | 475.50 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 409.88 | 197.59 | 223.83 | 763.11 | 232.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 404.35 | 116.13 | 288.22 | 542.55 | 459.54 | 0.00 | 0.00 | 0.00 |
February | 461.73 | 131.67 | 330.06 | 683.44 | 375.33 | 0.00 | 0.00 | 0.00 |
March | 546.93 | 161.92 | 385.01 | 910.82 | 280.50 | 0.00 | 0.00 | 0.00 |
April | 597.70 | 167.92 | 429.78 | 1139.57 | 175.74 | 0.00 | 0.00 | 0.00 |
May | 650.60 | 194.75 | 455.85 | 1483.64 | 46.70 | 0.00 | 0.00 | 0.00 |
June | 672.34 | 211.94 | 460.40 | 1616.23 | 11.79 | 0.00 | 0.00 | 0.00 |
July | 616.80 | 176.45 | 440.34 | 1699.87 | 0.29 | 0.00 | 0.00 | 0.00 |
August | 632.76 | 192.39 | 440.38 | 1742.68 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 601.92 | 189.11 | 412.82 | 1441.51 | 20.95 | 0.00 | 0.00 | 0.00 |
October | 534.93 | 172.80 | 362.13 | 1127.26 | 86.87 | 0.00 | 0.00 | 0.00 |
November | 459.71 | 150.34 | 309.37 | 825.44 | 224.18 | 0.00 | 0.00 | 0.00 |
December | 384.85 | 116.33 | 268.52 | 567.90 | 384.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 547.36 | 165.26 | 382.10 | 1151.06 | 171.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 384.85 | 116.13 | 268.52 | 542.55 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 672.34 | 211.94 | 460.40 | 1742.68 | 459.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.99 | 4.59 | 11.40 | 21.45 | 18.17 | 0.00 | 0.00 | 0.00 |
February | 18.26 | 5.21 | 13.05 | 27.02 | 14.84 | 0.00 | 0.00 | 0.00 |
March | 21.63 | 6.40 | 15.22 | 36.01 | 11.09 | 0.00 | 0.00 | 0.00 |
April | 23.63 | 6.64 | 16.99 | 45.06 | 6.95 | 0.00 | 0.00 | 0.00 |
May | 25.72 | 7.70 | 18.02 | 58.66 | 1.85 | 0.00 | 0.00 | 0.00 |
June | 26.58 | 8.38 | 18.20 | 63.90 | 0.47 | 0.00 | 0.00 | 0.00 |
July | 24.39 | 6.98 | 17.41 | 67.21 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 25.02 | 7.61 | 17.41 | 68.90 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23.80 | 7.48 | 16.32 | 57.00 | 0.83 | 0.00 | 0.00 | 0.00 |
October | 21.15 | 6.83 | 14.32 | 44.57 | 3.43 | 0.00 | 0.00 | 0.00 |
November | 18.18 | 5.94 | 12.23 | 32.64 | 8.86 | 0.00 | 0.00 | 0.00 |
December | 15.22 | 4.60 | 10.62 | 22.45 | 15.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.64 | 6.53 | 15.11 | 45.51 | 6.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.22 | 4.59 | 10.62 | 21.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.58 | 8.38 | 18.20 | 68.90 | 18.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 355.41 | 0.00 | 355.41 | 383.78 | 676.06 | 0.00 | 0.00 | 0.00 |
February | 407.41 | 0.00 | 407.41 | 525.70 | 561.04 | 0.00 | 0.00 | 0.00 |
March | 467.96 | 0.00 | 467.96 | 745.69 | 424.14 | 0.00 | 0.00 | 0.00 |
April | 527.24 | 1.09 | 526.15 | 1063.01 | 263.17 | 0.00 | 0.00 | 0.00 |
May | 593.46 | 17.41 | 576.05 | 1583.40 | 65.44 | 0.00 | 0.00 | 0.00 |
June | 635.41 | 35.28 | 600.13 | 1823.35 | 16.62 | 0.00 | 0.00 | 0.00 |
July | 583.05 | 16.80 | 566.25 | 2017.84 | 0.33 | 0.00 | 0.00 | 0.00 |
August | 542.77 | 4.49 | 538.28 | 1981.44 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 494.41 | 0.06 | 494.35 | 1502.01 | 24.62 | 0.00 | 0.00 | 0.00 |
October | 438.28 | 0.00 | 438.28 | 1087.88 | 110.45 | 0.00 | 0.00 | 0.00 |
November | 376.26 | 0.00 | 376.26 | 702.17 | 307.09 | 0.00 | 0.00 | 0.00 |
December | 331.73 | 0.00 | 331.73 | 425.83 | 550.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 479.72 | 6.28 | 473.44 | 1157.36 | 248.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 331.73 | 0.00 | 331.73 | 383.78 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 635.41 | 35.28 | 600.13 | 2017.84 | 676.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 428.62 | 129.68 | 298.94 | 553.90 | 420.53 | 0.00 | 0.00 | 0.00 |
February | 467.10 | 126.59 | 340.51 | 666.54 | 352.60 | 0.00 | 0.00 | 0.00 |
March | 515.96 | 127.16 | 388.79 | 839.83 | 269.05 | 0.00 | 0.00 | 0.00 |
April | 628.20 | 183.04 | 445.16 | 1185.68 | 169.11 | 0.00 | 0.00 | 0.00 |
May | 702.03 | 223.67 | 478.36 | 1581.66 | 41.39 | 0.00 | 0.00 | 0.00 |
June | 687.53 | 210.25 | 477.28 | 1663.06 | 9.64 | 0.00 | 0.00 | 0.00 |
July | 641.71 | 185.00 | 456.70 | 1784.01 | 0.14 | 0.00 | 0.00 | 0.00 |
August | 657.10 | 201.67 | 455.42 | 1840.19 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 617.75 | 190.94 | 426.81 | 1503.44 | 14.51 | 0.00 | 0.00 | 0.00 |
October | 560.54 | 183.13 | 377.41 | 1187.59 | 67.45 | 0.00 | 0.00 | 0.00 |
November | 469.74 | 148.79 | 320.95 | 835.54 | 193.65 | 0.00 | 0.00 | 0.00 |
December | 380.21 | 104.31 | 275.89 | 538.23 | 346.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 563.41 | 168.02 | 395.39 | 1184.61 | 156.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 380.21 | 104.31 | 275.89 | 538.23 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 702.03 | 223.67 | 478.36 | 1840.19 | 420.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1148.64 | 540.03 | 608.62 | 1690.12 | 656.00 | 0.00 | 0.00 | 0.00 |
February | 1078.63 | 441.20 | 637.42 | 1682.82 | 556.98 | 0.00 | 0.00 | 0.00 |
March | 887.76 | 241.02 | 646.74 | 1539.20 | 431.50 | 0.00 | 0.00 | 0.00 |
April | 697.85 | 73.98 | 623.86 | 1419.67 | 268.96 | 0.00 | 0.00 | 0.00 |
May | 591.14 | 9.05 | 582.08 | 1579.75 | 65.79 | 0.00 | 0.00 | 0.00 |
June | 556.72 | 0.69 | 556.03 | 1667.30 | 13.40 | 0.00 | 0.00 | 0.00 |
July | 556.70 | 4.73 | 551.97 | 1957.31 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 645.73 | 45.75 | 599.98 | 2196.16 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 851.40 | 195.12 | 656.28 | 2203.92 | 24.49 | 0.00 | 0.00 | 0.00 |
October | 1114.64 | 443.13 | 671.51 | 2320.72 | 110.32 | 0.00 | 0.00 | 0.00 |
November | 1229.68 | 592.80 | 636.88 | 2179.90 | 307.39 | 0.00 | 0.00 | 0.00 |
December | 1141.51 | 563.87 | 577.64 | 1782.89 | 544.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 873.81 | 261.66 | 612.15 | 1852.86 | 246.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 556.70 | 0.69 | 551.97 | 1419.67 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1229.68 | 592.80 | 671.51 | 2320.72 | 656.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 420.34 | 120.73 | 299.62 | 567.97 | 449.50 | 0.00 | 0.00 | 0.00 |
February | 479.99 | 136.87 | 343.12 | 710.00 | 374.35 | 0.00 | 0.00 | 0.00 |
March | 568.56 | 168.32 | 400.24 | 941.44 | 287.71 | 0.00 | 0.00 | 0.00 |
April | 621.34 | 174.56 | 446.78 | 1178.04 | 183.72 | 0.00 | 0.00 | 0.00 |
May | 676.32 | 202.45 | 473.87 | 1542.72 | 47.90 | 0.00 | 0.00 | 0.00 |
June | 698.93 | 220.32 | 478.61 | 1687.24 | 11.05 | 0.00 | 0.00 | 0.00 |
July | 641.19 | 183.43 | 457.76 | 1779.76 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 657.79 | 200.00 | 457.79 | 1831.29 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 625.73 | 196.58 | 429.14 | 1515.49 | 17.79 | 0.00 | 0.00 | 0.00 |
October | 556.09 | 179.63 | 376.46 | 1186.12 | 77.76 | 0.00 | 0.00 | 0.00 |
November | 477.89 | 156.28 | 321.60 | 868.25 | 209.90 | 0.00 | 0.00 | 0.00 |
December | 400.07 | 120.93 | 279.13 | 597.05 | 368.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 569.01 | 171.79 | 397.21 | 1203.25 | 168.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 400.07 | 120.73 | 279.13 | 567.97 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 698.93 | 220.32 | 478.61 | 1831.29 | 449.50 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.951942E+09 | 0.00 | 0.951942E+09 | 0.106934E+10 | 0.164525E+10 |
February | 0.985598E+09 | 0.00 | 0.985598E+09 | 0.129555E+10 | 0.124784E+10 |
March | 0.125339E+10 | 0.00 | 0.125339E+10 | 0.200309E+10 | 0.106054E+10 |
April | 0.136661E+10 | 2815821.33 | 0.136379E+10 | 0.274066E+10 | 0.653395E+09 |
May | 0.158951E+10 | 46619386.00 | 0.154289E+10 | 0.420740E+10 | 0.172894E+09 |
June | 0.164697E+10 | 91434997.90 | 0.155554E+10 | 0.469059E+10 | 43417362.21 |
July | 0.156163E+10 | 44994457.35 | 0.151664E+10 | 0.535668E+10 | 893738.84 |
August | 0.145375E+10 | 12023936.16 | 0.144172E+10 | 0.526543E+10 | 228227.13 |
September | 0.128151E+10 | 146849.74 | 0.128137E+10 | 0.386493E+10 | 62680764.02 |
October | 0.117390E+10 | 0.00 | 0.117390E+10 | 0.289928E+10 | 0.280883E+09 |
November | 0.975261E+09 | 0.00 | 0.975261E+09 | 0.182526E+10 | 0.740333E+09 |
December | 0.888515E+09 | 0.00 | 0.888515E+09 | 0.117251E+10 | 0.134577E+10 |
Annual Sum or Average | 0.151286E+11 | 0.198035E+09 | 0.149306E+11 | 0.363907E+11 | 0.725413E+10 |
Minimum of Months | 0.888515E+09 | 0.00 | 0.888515E+09 | 0.106934E+10 | 228227.13 |
Maximum of Months | 0.164697E+10 | 91434997.90 | 0.155554E+10 | 0.535668E+10 | 0.164525E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114802E+10 | 0.347331E+09 | 0.800689E+09 | 0.151679E+10 | 0.103721E+10 |
February | 0.113001E+10 | 0.306236E+09 | 0.823770E+09 | 0.163002E+10 | 0.792709E+09 |
March | 0.138195E+10 | 0.340598E+09 | 0.104135E+10 | 0.225362E+10 | 0.678252E+09 |
April | 0.162830E+10 | 0.474431E+09 | 0.115387E+10 | 0.306150E+10 | 0.422400E+09 |
May | 0.188032E+10 | 0.599079E+09 | 0.128124E+10 | 0.420964E+10 | 0.109452E+09 |
June | 0.178208E+10 | 0.544979E+09 | 0.123711E+10 | 0.428357E+10 | 25248183.77 |
July | 0.171874E+10 | 0.495509E+09 | 0.122323E+10 | 0.474351E+10 | 369717.13 |
August | 0.175996E+10 | 0.540155E+09 | 0.121981E+10 | 0.489763E+10 | 92210.47 |
September | 0.160120E+10 | 0.494910E+09 | 0.110629E+10 | 0.387392E+10 | 37068911.82 |
October | 0.150136E+10 | 0.490493E+09 | 0.101086E+10 | 0.316646E+10 | 0.171938E+09 |
November | 0.121756E+10 | 0.385659E+09 | 0.831898E+09 | 0.216811E+10 | 0.470290E+09 |
December | 0.101834E+10 | 0.279392E+09 | 0.738953E+09 | 0.146619E+10 | 0.855512E+09 |
Annual Sum or Average | 0.177678E+11 | 0.529877E+10 | 0.124691E+11 | 0.372710E+11 | 0.460054E+10 |
Minimum of Months | 0.101834E+10 | 0.279392E+09 | 0.738953E+09 | 0.146619E+10 | 92210.47 |
Maximum of Months | 0.188032E+10 | 0.599079E+09 | 0.128124E+10 | 0.489763E+10 | 0.103721E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307653E+10 | 0.144641E+10 | 0.163012E+10 | 0.456422E+10 | 0.161885E+10 |
February | 0.260941E+10 | 0.106736E+10 | 0.154205E+10 | 0.408727E+10 | 0.124976E+10 |
March | 0.237777E+10 | 0.645551E+09 | 0.173222E+10 | 0.412260E+10 | 0.108319E+10 |
April | 0.180882E+10 | 0.191768E+09 | 0.161705E+10 | 0.366326E+10 | 0.666372E+09 |
May | 0.158330E+10 | 24246543.42 | 0.155905E+10 | 0.419859E+10 | 0.171705E+09 |
June | 0.144301E+10 | 1785763.13 | 0.144122E+10 | 0.429040E+10 | 34181249.45 |
July | 0.149107E+10 | 12669433.04 | 0.147840E+10 | 0.519823E+10 | 408590.49 |
August | 0.172952E+10 | 0.122543E+09 | 0.160697E+10 | 0.584240E+10 | 135395.42 |
September | 0.220682E+10 | 0.505756E+09 | 0.170107E+10 | 0.568057E+10 | 62019656.48 |
October | 0.298546E+10 | 0.118689E+10 | 0.179858E+10 | 0.619160E+10 | 0.280895E+09 |
November | 0.318733E+10 | 0.153653E+10 | 0.165080E+10 | 0.564736E+10 | 0.749275E+09 |
December | 0.305743E+10 | 0.151028E+10 | 0.154716E+10 | 0.480023E+10 | 0.134995E+10 |
Annual Sum or Average | 0.275565E+11 | 0.825179E+10 | 0.193047E+11 | 0.582867E+11 | 0.726675E+10 |
Minimum of Months | 0.144301E+10 | 1785763.13 | 0.144122E+10 | 0.366326E+10 | 135395.42 |
Maximum of Months | 0.318733E+10 | 0.153653E+10 | 0.179858E+10 | 0.619160E+10 | 0.161885E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112585E+10 | 0.323352E+09 | 0.802494E+09 | 0.154928E+10 | 0.109628E+10 |
February | 0.116119E+10 | 0.331123E+09 | 0.830064E+09 | 0.173323E+10 | 0.833669E+09 |
March | 0.152283E+10 | 0.450837E+09 | 0.107200E+10 | 0.252422E+10 | 0.720251E+09 |
April | 0.161051E+10 | 0.452466E+09 | 0.115804E+10 | 0.304244E+10 | 0.456012E+09 |
May | 0.181147E+10 | 0.542244E+09 | 0.126922E+10 | 0.410821E+10 | 0.125415E+09 |
June | 0.181161E+10 | 0.571068E+09 | 0.124055E+10 | 0.435075E+10 | 28273618.11 |
July | 0.171736E+10 | 0.491301E+09 | 0.122606E+10 | 0.473820E+10 | 396107.26 |
August | 0.176182E+10 | 0.535667E+09 | 0.122615E+10 | 0.487876E+10 | 222492.71 |
September | 0.162188E+10 | 0.509547E+09 | 0.111233E+10 | 0.390856E+10 | 45211351.68 |
October | 0.148942E+10 | 0.481123E+09 | 0.100830E+10 | 0.316514E+10 | 0.197701E+09 |
November | 0.123868E+10 | 0.405089E+09 | 0.833596E+09 | 0.225241E+10 | 0.506356E+09 |
December | 0.107154E+10 | 0.323906E+09 | 0.747632E+09 | 0.162065E+10 | 0.903050E+09 |
Annual Sum or Average | 0.179442E+11 | 0.541772E+10 | 0.125264E+11 | 0.378718E+11 | 0.491284E+10 |
Minimum of Months | 0.107154E+10 | 0.323352E+09 | 0.747632E+09 | 0.154928E+10 | 222492.71 |
Maximum of Months | 0.181161E+10 | 0.571068E+09 | 0.126922E+10 | 0.487876E+10 | 0.109628E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.317299E+09 | 0.00 | 0.317299E+09 | 0.336841E+09 | 0.632207E+09 |
February | 0.328517E+09 | 0.00 | 0.328517E+09 | 0.423706E+09 | 0.463241E+09 |
March | 0.417776E+09 | 0.00 | 0.417776E+09 | 0.671255E+09 | 0.374837E+09 |
April | 0.455514E+09 | 938562.70 | 0.454575E+09 | 0.925970E+09 | 0.218518E+09 |
May | 0.529812E+09 | 15539060.11 | 0.514273E+09 | 0.141530E+10 | 55003727.31 |
June | 0.548965E+09 | 30476890.64 | 0.518488E+09 | 0.157032E+10 | 13713654.37 |
July | 0.520520E+09 | 14997442.86 | 0.505523E+09 | 0.178899E+10 | 339259.66 |
August | 0.484560E+09 | 4007789.10 | 0.480552E+09 | 0.174589E+10 | 55087.04 |
September | 0.427151E+09 | 48947.60 | 0.427102E+09 | 0.127718E+10 | 24101312.54 |
October | 0.391282E+09 | 0.00 | 0.391282E+09 | 0.950929E+09 | 0.109375E+09 |
November | 0.325072E+09 | 0.00 | 0.325072E+09 | 0.591861E+09 | 0.287506E+09 |
December | 0.296158E+09 | 0.00 | 0.296158E+09 | 0.370663E+09 | 0.524910E+09 |
Annual Sum or Average | 0.504263E+10 | 66008693.00 | 0.497662E+10 | 0.120689E+11 | 0.270381E+10 |
Minimum of Months | 0.296158E+09 | 0.00 | 0.296158E+09 | 0.336841E+09 | 55087.04 |
Maximum of Months | 0.548965E+09 | 30476890.64 | 0.518488E+09 | 0.178899E+10 | 0.632207E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.317319E+09 | 0.00 | 0.317319E+09 | 0.336863E+09 | 0.632247E+09 |
February | 0.328538E+09 | 0.00 | 0.328538E+09 | 0.423733E+09 | 0.463270E+09 |
March | 0.417803E+09 | 0.00 | 0.417803E+09 | 0.671298E+09 | 0.374861E+09 |
April | 0.455543E+09 | 938622.02 | 0.454604E+09 | 0.926029E+09 | 0.218532E+09 |
May | 0.529845E+09 | 15540042.16 | 0.514305E+09 | 0.141539E+10 | 55007203.45 |
June | 0.549000E+09 | 30478816.73 | 0.518521E+09 | 0.157042E+10 | 13714521.05 |
July | 0.520553E+09 | 14998390.67 | 0.505555E+09 | 0.178910E+10 | 339281.10 |
August | 0.484590E+09 | 4008042.38 | 0.480582E+09 | 0.174600E+10 | 55090.52 |
September | 0.427178E+09 | 48950.69 | 0.427129E+09 | 0.127726E+10 | 24102835.70 |
October | 0.391307E+09 | 0.00 | 0.391307E+09 | 0.950990E+09 | 0.109382E+09 |
November | 0.325092E+09 | 0.00 | 0.325092E+09 | 0.591898E+09 | 0.287525E+09 |
December | 0.296176E+09 | 0.00 | 0.296176E+09 | 0.370687E+09 | 0.524943E+09 |
Annual Sum or Average | 0.504294E+10 | 66012864.64 | 0.497693E+10 | 0.120697E+11 | 0.270398E+10 |
Minimum of Months | 0.296176E+09 | 0.00 | 0.296176E+09 | 0.336863E+09 | 55090.52 |
Maximum of Months | 0.549000E+09 | 30478816.73 | 0.518521E+09 | 0.178910E+10 | 0.632247E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.317319E+09 | 0.00 | 0.317319E+09 | 0.336863E+09 | 0.632247E+09 |
February | 0.328538E+09 | 0.00 | 0.328538E+09 | 0.423733E+09 | 0.463270E+09 |
March | 0.417803E+09 | 0.00 | 0.417803E+09 | 0.671298E+09 | 0.374861E+09 |
April | 0.455543E+09 | 938622.02 | 0.454604E+09 | 0.926029E+09 | 0.218532E+09 |
May | 0.529845E+09 | 15540042.16 | 0.514305E+09 | 0.141539E+10 | 55007203.45 |
June | 0.549000E+09 | 30478816.73 | 0.518521E+09 | 0.157042E+10 | 13714521.05 |
July | 0.520553E+09 | 14998390.67 | 0.505555E+09 | 0.178910E+10 | 339281.10 |
August | 0.484590E+09 | 4008042.38 | 0.480582E+09 | 0.174600E+10 | 55090.52 |
September | 0.427178E+09 | 48950.69 | 0.427129E+09 | 0.127726E+10 | 24102835.70 |
October | 0.391307E+09 | 0.00 | 0.391307E+09 | 0.950990E+09 | 0.109382E+09 |
November | 0.325092E+09 | 0.00 | 0.325092E+09 | 0.591898E+09 | 0.287525E+09 |
December | 0.296176E+09 | 0.00 | 0.296176E+09 | 0.370687E+09 | 0.524943E+09 |
Annual Sum or Average | 0.504294E+10 | 66012864.64 | 0.497693E+10 | 0.120697E+11 | 0.270398E+10 |
Minimum of Months | 0.296176E+09 | 0.00 | 0.296176E+09 | 0.336863E+09 | 55090.52 |
Maximum of Months | 0.549000E+09 | 30478816.73 | 0.518521E+09 | 0.178910E+10 | 0.632247E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110435E+10 | 0.334117E+09 | 0.770230E+09 | 0.141378E+10 | 0.115027E+10 |
February | 0.108702E+10 | 0.294586E+09 | 0.792433E+09 | 0.155081E+10 | 0.854496E+09 |
March | 0.132937E+10 | 0.327640E+09 | 0.100173E+10 | 0.217594E+10 | 0.699786E+09 |
April | 0.156635E+10 | 0.456381E+09 | 0.110997E+10 | 0.297157E+10 | 0.419570E+09 |
May | 0.180879E+10 | 0.576287E+09 | 0.123250E+10 | 0.407446E+10 | 0.107914E+09 |
June | 0.171429E+10 | 0.524246E+09 | 0.119004E+10 | 0.413317E+10 | 25966748.41 |
July | 0.165336E+10 | 0.476657E+09 | 0.117670E+10 | 0.456591E+10 | 632602.39 |
August | 0.169301E+10 | 0.519605E+09 | 0.117341E+10 | 0.469015E+10 | 107661.72 |
September | 0.154028E+10 | 0.476081E+09 | 0.106420E+10 | 0.370562E+10 | 44976158.67 |
October | 0.144424E+10 | 0.471832E+09 | 0.972410E+09 | 0.302248E+10 | 0.204933E+09 |
November | 0.117124E+10 | 0.370986E+09 | 0.800252E+09 | 0.205627E+10 | 0.536278E+09 |
December | 0.979605E+09 | 0.268762E+09 | 0.710842E+09 | 0.136656E+10 | 0.964835E+09 |
Annual Sum or Average | 0.170919E+11 | 0.509718E+10 | 0.119947E+11 | 0.357267E+11 | 0.500977E+10 |
Minimum of Months | 0.979605E+09 | 0.268762E+09 | 0.710842E+09 | 0.136656E+10 | 107661.72 |
Maximum of Months | 0.180879E+10 | 0.576287E+09 | 0.123250E+10 | 0.469015E+10 | 0.115027E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43664875.02 | 13210691.14 | 30454183.88 | 55899430.98 | 45480713.00 |
February | 42979723.25 | 11647653.04 | 31332070.21 | 61317758.50 | 33785998.19 |
March | 52562209.64 | 12954581.24 | 39607628.40 | 86034897.45 | 27668913.43 |
April | 61932229.81 | 18044909.31 | 43887320.50 | 0.117493E+09 | 16589439.04 |
May | 71517959.31 | 22785860.64 | 48732098.67 | 0.161100E+09 | 4266817.94 |
June | 67781505.58 | 20728205.07 | 47053300.51 | 0.163422E+09 | 1026701.85 |
July | 65372335.19 | 18846600.88 | 46525734.31 | 0.180532E+09 | 25012.53 |
August | 66940136.47 | 20544710.14 | 46395426.33 | 0.185444E+09 | 4256.85 |
September | 60901460.14 | 18823809.12 | 42077651.01 | 0.146517E+09 | 1778316.82 |
October | 57104047.85 | 18655820.55 | 38448227.30 | 0.119506E+09 | 8102876.14 |
November | 46309704.67 | 14668471.44 | 31641233.22 | 81303118.40 | 21203956.47 |
December | 38732683.64 | 10626625.94 | 28106057.70 | 54032369.19 | 38148717.67 |
Annual Sum or Average | 0.675799E+09 | 0.201538E+09 | 0.474261E+09 | 0.141260E+10 | 0.198082E+09 |
Minimum of Months | 38732683.64 | 10626625.94 | 28106057.70 | 54032369.19 | 4256.85 |
Maximum of Months | 71517959.31 | 22785860.64 | 48732098.67 | 0.185444E+09 | 45480713.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102554E+10 | 0.482154E+09 | 0.543388E+09 | 0.151132E+10 | 0.623832E+09 |
February | 0.869831E+09 | 0.355799E+09 | 0.514032E+09 | 0.136280E+10 | 0.470359E+09 |
March | 0.792615E+09 | 0.215191E+09 | 0.577424E+09 | 0.138205E+10 | 0.388087E+09 |
April | 0.602956E+09 | 63924773.92 | 0.539031E+09 | 0.123257E+10 | 0.227005E+09 |
May | 0.527781E+09 | 8082445.50 | 0.519699E+09 | 0.140118E+10 | 57282333.49 |
June | 0.481015E+09 | 595273.85 | 0.480419E+09 | 0.142015E+10 | 12112082.93 |
July | 0.497035E+09 | 4223282.48 | 0.492812E+09 | 0.171760E+10 | 185959.07 |
August | 0.576521E+09 | 40848858.69 | 0.535672E+09 | 0.191361E+10 | 78613.56 |
September | 0.735629E+09 | 0.168591E+09 | 0.567038E+09 | 0.186687E+10 | 27010732.44 |
October | 0.995185E+09 | 0.395642E+09 | 0.599543E+09 | 0.204405E+10 | 0.120804E+09 |
November | 0.106248E+10 | 0.512192E+09 | 0.550283E+09 | 0.187186E+10 | 0.301510E+09 |
December | 0.101918E+10 | 0.503442E+09 | 0.515734E+09 | 0.158966E+10 | 0.527452E+09 |
Annual Sum or Average | 0.918576E+10 | 0.275069E+10 | 0.643508E+10 | 0.193137E+11 | 0.275572E+10 |
Minimum of Months | 0.481015E+09 | 595273.85 | 0.480419E+09 | 0.123257E+10 | 78613.56 |
Maximum of Months | 0.106248E+10 | 0.512192E+09 | 0.599543E+09 | 0.204405E+10 | 0.623832E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102554E+10 | 0.482154E+09 | 0.543388E+09 | 0.151132E+10 | 0.623832E+09 |
February | 0.869831E+09 | 0.355799E+09 | 0.514032E+09 | 0.136280E+10 | 0.470359E+09 |
March | 0.792615E+09 | 0.215191E+09 | 0.577424E+09 | 0.138205E+10 | 0.388087E+09 |
April | 0.602956E+09 | 63924773.92 | 0.539031E+09 | 0.123257E+10 | 0.227005E+09 |
May | 0.527781E+09 | 8082445.50 | 0.519699E+09 | 0.140118E+10 | 57282333.49 |
June | 0.481015E+09 | 595273.85 | 0.480419E+09 | 0.142015E+10 | 12112082.93 |
July | 0.497035E+09 | 4223282.48 | 0.492812E+09 | 0.171760E+10 | 185959.07 |
August | 0.576521E+09 | 40848858.69 | 0.535672E+09 | 0.191361E+10 | 78613.56 |
September | 0.735629E+09 | 0.168591E+09 | 0.567038E+09 | 0.186687E+10 | 27010732.44 |
October | 0.995185E+09 | 0.395642E+09 | 0.599543E+09 | 0.204405E+10 | 0.120804E+09 |
November | 0.106248E+10 | 0.512192E+09 | 0.550283E+09 | 0.187186E+10 | 0.301510E+09 |
December | 0.101918E+10 | 0.503442E+09 | 0.515734E+09 | 0.158966E+10 | 0.527452E+09 |
Annual Sum or Average | 0.918576E+10 | 0.275069E+10 | 0.643508E+10 | 0.193137E+11 | 0.275572E+10 |
Minimum of Months | 0.481015E+09 | 595273.85 | 0.480419E+09 | 0.123257E+10 | 78613.56 |
Maximum of Months | 0.106248E+10 | 0.512192E+09 | 0.599543E+09 | 0.204405E+10 | 0.623832E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102548E+10 | 0.482123E+09 | 0.543354E+09 | 0.151122E+10 | 0.623793E+09 |
February | 0.869776E+09 | 0.355777E+09 | 0.514000E+09 | 0.136271E+10 | 0.470329E+09 |
March | 0.792565E+09 | 0.215177E+09 | 0.577388E+09 | 0.138196E+10 | 0.388062E+09 |
April | 0.602918E+09 | 63920734.23 | 0.538997E+09 | 0.123249E+10 | 0.226990E+09 |
May | 0.527748E+09 | 8081934.73 | 0.519666E+09 | 0.140109E+10 | 57278713.57 |
June | 0.480984E+09 | 595236.23 | 0.480389E+09 | 0.142006E+10 | 12111317.51 |
July | 0.497004E+09 | 4223015.59 | 0.492781E+09 | 0.171749E+10 | 185947.32 |
August | 0.576485E+09 | 40846277.28 | 0.535638E+09 | 0.191349E+10 | 78608.59 |
September | 0.735583E+09 | 0.168580E+09 | 0.567002E+09 | 0.186675E+10 | 27009025.51 |
October | 0.995122E+09 | 0.395617E+09 | 0.599505E+09 | 0.204392E+10 | 0.120796E+09 |
November | 0.106241E+10 | 0.512160E+09 | 0.550249E+09 | 0.187174E+10 | 0.301491E+09 |
December | 0.101911E+10 | 0.503410E+09 | 0.515701E+09 | 0.158956E+10 | 0.527419E+09 |
Annual Sum or Average | 0.918518E+10 | 0.275051E+10 | 0.643467E+10 | 0.193125E+11 | 0.275554E+10 |
Minimum of Months | 0.480984E+09 | 595236.23 | 0.480389E+09 | 0.123249E+10 | 78608.59 |
Maximum of Months | 0.106241E+10 | 0.512160E+09 | 0.599505E+09 | 0.204392E+10 | 0.623793E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108302E+10 | 0.311050E+09 | 0.771966E+09 | 0.145316E+10 | 0.123085E+10 |
February | 0.111701E+10 | 0.318526E+09 | 0.798488E+09 | 0.165337E+10 | 0.908001E+09 |
March | 0.146490E+10 | 0.433685E+09 | 0.103122E+10 | 0.243955E+10 | 0.751279E+09 |
April | 0.154924E+10 | 0.435252E+09 | 0.111399E+10 | 0.295376E+10 | 0.455513E+09 |
May | 0.174256E+10 | 0.521614E+09 | 0.122094E+10 | 0.397379E+10 | 0.125072E+09 |
June | 0.174270E+10 | 0.549342E+09 | 0.119336E+10 | 0.418928E+10 | 30568786.65 |
July | 0.165203E+10 | 0.472610E+09 | 0.117942E+10 | 0.455294E+10 | 780527.05 |
August | 0.169480E+10 | 0.515288E+09 | 0.117951E+10 | 0.466759E+10 | 225599.46 |
September | 0.156018E+10 | 0.490162E+09 | 0.107002E+10 | 0.373639E+10 | 54315034.24 |
October | 0.143276E+10 | 0.462819E+09 | 0.969942E+09 | 0.301924E+10 | 0.232679E+09 |
November | 0.119156E+10 | 0.389677E+09 | 0.801885E+09 | 0.213953E+10 | 0.581068E+09 |
December | 0.103077E+10 | 0.311583E+09 | 0.719191E+09 | 0.152107E+10 | 0.102888E+10 |
Annual Sum or Average | 0.172615E+11 | 0.521161E+10 | 0.120499E+11 | 0.362997E+11 | 0.539923E+10 |
Minimum of Months | 0.103077E+10 | 0.311050E+09 | 0.719191E+09 | 0.145316E+10 | 225599.46 |
Maximum of Months | 0.174270E+10 | 0.549342E+09 | 0.122094E+10 | 0.466759E+10 | 0.123085E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42821337.81 | 12298584.88 | 30522752.94 | 57456442.07 | 48666478.51 |
February | 44165574.81 | 12594172.82 | 31571401.99 | 65372648.01 | 35901492.95 |
March | 57920681.25 | 17147462.24 | 40773219.01 | 96457314.93 | 29704863.61 |
April | 61255548.92 | 17209428.69 | 44046120.23 | 0.116789E+09 | 18010559.70 |
May | 68898925.43 | 20624089.28 | 48274836.15 | 0.157120E+09 | 4945206.17 |
June | 68904478.54 | 21720398.66 | 47184079.88 | 0.165640E+09 | 1208653.90 |
July | 65319541.43 | 18686508.11 | 46633033.32 | 0.180019E+09 | 30860.50 |
August | 67010576.60 | 20373953.29 | 46636623.32 | 0.184552E+09 | 8919.79 |
September | 61688022.42 | 19380493.44 | 42307528.98 | 0.147733E+09 | 2147557.53 |
October | 56649931.81 | 18299394.08 | 38350537.73 | 0.119378E+09 | 9199899.48 |
November | 47113172.64 | 15407441.47 | 31705731.16 | 84594967.22 | 22974853.54 |
December | 40755782.91 | 12319687.55 | 28436095.36 | 60141477.82 | 40680887.16 |
Annual Sum or Average | 0.682504E+09 | 0.206062E+09 | 0.476442E+09 | 0.143525E+10 | 0.213480E+09 |
Minimum of Months | 40755782.91 | 12298584.88 | 28436095.36 | 57456442.07 | 8919.79 |
Maximum of Months | 68904478.54 | 21720398.66 | 48274836.15 | 0.184552E+09 | 48666478.51 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.951942E+09 | 0.00 | 0.951942E+09 | 0.102792E+10 | 0.181075E+10 |
February | 0.985598E+09 | 0.00 | 0.985598E+09 | 0.127178E+10 | 0.135726E+10 |
March | 0.125339E+10 | 0.00 | 0.125339E+10 | 0.199726E+10 | 0.113600E+10 |
April | 0.136661E+10 | 2815821.33 | 0.136379E+10 | 0.275532E+10 | 0.682132E+09 |
May | 0.158951E+10 | 46619386.00 | 0.154289E+10 | 0.424099E+10 | 0.175283E+09 |
June | 0.164697E+10 | 91434997.90 | 0.155554E+10 | 0.472612E+10 | 43069145.24 |
July | 0.156163E+10 | 44994457.35 | 0.151664E+10 | 0.540457E+10 | 888571.73 |
August | 0.145375E+10 | 12023936.16 | 0.144172E+10 | 0.530709E+10 | 185235.48 |
September | 0.128151E+10 | 146849.74 | 0.128137E+10 | 0.389322E+10 | 63820437.83 |
October | 0.117390E+10 | 0.00 | 0.117390E+10 | 0.291377E+10 | 0.295828E+09 |
November | 0.975261E+09 | 0.00 | 0.975261E+09 | 0.182002E+10 | 0.795986E+09 |
December | 0.888515E+09 | 0.00 | 0.888515E+09 | 0.114056E+10 | 0.147458E+10 |
Annual Sum or Average | 0.151286E+11 | 0.198035E+09 | 0.149306E+11 | 0.364986E+11 | 0.783579E+10 |
Minimum of Months | 0.888515E+09 | 0.00 | 0.888515E+09 | 0.102792E+10 | 185235.48 |
Maximum of Months | 0.164697E+10 | 91434997.90 | 0.155554E+10 | 0.540457E+10 | 0.181075E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114802E+10 | 0.347331E+09 | 0.800689E+09 | 0.148357E+10 | 0.112634E+10 |
February | 0.113001E+10 | 0.306236E+09 | 0.823770E+09 | 0.161249E+10 | 0.853011E+09 |
March | 0.138195E+10 | 0.340598E+09 | 0.104135E+10 | 0.224941E+10 | 0.720636E+09 |
April | 0.162830E+10 | 0.474431E+09 | 0.115387E+10 | 0.307328E+10 | 0.438340E+09 |
May | 0.188032E+10 | 0.599079E+09 | 0.128124E+10 | 0.423632E+10 | 0.110872E+09 |
June | 0.178208E+10 | 0.544979E+09 | 0.123711E+10 | 0.431065E+10 | 24990698.25 |
July | 0.171874E+10 | 0.495509E+09 | 0.122323E+10 | 0.477829E+10 | 368625.19 |
August | 0.175996E+10 | 0.540155E+09 | 0.121981E+10 | 0.492877E+10 | 73150.96 |
September | 0.160120E+10 | 0.494910E+09 | 0.110629E+10 | 0.389693E+10 | 37619859.23 |
October | 0.150136E+10 | 0.490493E+09 | 0.101086E+10 | 0.318084E+10 | 0.180664E+09 |
November | 0.121756E+10 | 0.385659E+09 | 0.831898E+09 | 0.216572E+10 | 0.501932E+09 |
December | 0.101834E+10 | 0.279392E+09 | 0.738953E+09 | 0.144160E+10 | 0.927111E+09 |
Annual Sum or Average | 0.177678E+11 | 0.529877E+10 | 0.124691E+11 | 0.373579E+11 | 0.492196E+10 |
Minimum of Months | 0.101834E+10 | 0.279392E+09 | 0.738953E+09 | 0.144160E+10 | 73150.96 |
Maximum of Months | 0.188032E+10 | 0.599079E+09 | 0.128124E+10 | 0.492877E+10 | 0.112634E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307653E+10 | 0.144641E+10 | 0.163012E+10 | 0.452682E+10 | 0.175703E+10 |
February | 0.260941E+10 | 0.106736E+10 | 0.154205E+10 | 0.407108E+10 | 0.134744E+10 |
March | 0.237777E+10 | 0.645551E+09 | 0.173222E+10 | 0.412260E+10 | 0.115573E+10 |
April | 0.180882E+10 | 0.191768E+09 | 0.161705E+10 | 0.367979E+10 | 0.697134E+09 |
May | 0.158330E+10 | 24246543.42 | 0.155905E+10 | 0.423120E+10 | 0.176214E+09 |
June | 0.144301E+10 | 1785763.13 | 0.144122E+10 | 0.432165E+10 | 34731390.76 |
July | 0.149107E+10 | 12669433.04 | 0.147840E+10 | 0.524247E+10 | 394581.34 |
August | 0.172952E+10 | 0.122543E+09 | 0.160697E+10 | 0.588220E+10 | 106414.86 |
September | 0.220682E+10 | 0.505756E+09 | 0.170107E+10 | 0.571257E+10 | 63475213.39 |
October | 0.298546E+10 | 0.118689E+10 | 0.179858E+10 | 0.621582E+10 | 0.295492E+09 |
November | 0.318733E+10 | 0.153653E+10 | 0.165080E+10 | 0.565029E+10 | 0.796762E+09 |
December | 0.305743E+10 | 0.151028E+10 | 0.154716E+10 | 0.477528E+10 | 0.145738E+10 |
Annual Sum or Average | 0.275565E+11 | 0.825179E+10 | 0.193047E+11 | 0.584318E+11 | 0.778189E+10 |
Minimum of Months | 0.144301E+10 | 1785763.13 | 0.144122E+10 | 0.367979E+10 | 106414.86 |
Maximum of Months | 0.318733E+10 | 0.153653E+10 | 0.179858E+10 | 0.621582E+10 | 0.175703E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112585E+10 | 0.323352E+09 | 0.802494E+09 | 0.152126E+10 | 0.120393E+10 |
February | 0.116119E+10 | 0.331123E+09 | 0.830064E+09 | 0.171762E+10 | 0.905625E+09 |
March | 0.152283E+10 | 0.450837E+09 | 0.107200E+10 | 0.252155E+10 | 0.770596E+09 |
April | 0.161051E+10 | 0.452466E+09 | 0.115804E+10 | 0.305349E+10 | 0.476205E+09 |
May | 0.181147E+10 | 0.542244E+09 | 0.126922E+10 | 0.413202E+10 | 0.128293E+09 |
June | 0.181161E+10 | 0.571068E+09 | 0.124055E+10 | 0.437333E+10 | 28649546.67 |
July | 0.171736E+10 | 0.491301E+09 | 0.122606E+10 | 0.476690E+10 | 396783.24 |
August | 0.176182E+10 | 0.535667E+09 | 0.122615E+10 | 0.490492E+10 | 207542.53 |
September | 0.162188E+10 | 0.509547E+09 | 0.111233E+10 | 0.392814E+10 | 46108325.69 |
October | 0.148942E+10 | 0.481123E+09 | 0.100830E+10 | 0.317692E+10 | 0.208282E+09 |
November | 0.123868E+10 | 0.405089E+09 | 0.833596E+09 | 0.225049E+10 | 0.544060E+09 |
December | 0.107154E+10 | 0.323906E+09 | 0.747632E+09 | 0.159913E+10 | 0.987307E+09 |
Annual Sum or Average | 0.179442E+11 | 0.541772E+10 | 0.125264E+11 | 0.379458E+11 | 0.529967E+10 |
Minimum of Months | 0.107154E+10 | 0.323352E+09 | 0.747632E+09 | 0.152126E+10 | 207542.53 |
Maximum of Months | 0.181161E+10 | 0.571068E+09 | 0.126922E+10 | 0.490492E+10 | 0.120393E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 399.25 | 614.27 | 355.41 | 0.00 | 355.41 | 0.00 | 0.00 |
February | 535.53 | 515.81 | 407.41 | 0.00 | 407.41 | 0.00 | 0.00 |
March | 747.87 | 395.96 | 467.96 | 0.00 | 467.96 | 0.00 | 0.00 |
April | 1057.35 | 252.08 | 527.24 | 1.09 | 526.15 | 0.00 | 0.00 |
May | 1570.86 | 64.55 | 593.46 | 17.41 | 576.05 | 0.00 | 0.00 |
June | 1809.64 | 16.75 | 635.41 | 35.28 | 600.13 | 0.00 | 0.00 |
July | 1999.95 | 0.33 | 583.05 | 16.80 | 566.25 | 0.00 | 0.00 |
August | 1965.89 | 0.09 | 542.77 | 4.49 | 538.28 | 0.00 | 0.00 |
September | 1491.10 | 24.18 | 494.41 | 0.06 | 494.35 | 0.00 | 0.00 |
October | 1082.47 | 104.87 | 438.28 | 0.00 | 438.28 | 0.00 | 0.00 |
November | 704.19 | 285.62 | 376.26 | 0.00 | 376.26 | 0.00 | 0.00 |
December | 437.76 | 502.45 | 331.73 | 0.00 | 331.73 | 0.00 | 0.00 |
Annual Sum or Average | 1153.94 | 230.03 | 479.72 | 6.28 | 473.44 | 0.00 | 0.00 |
Minimum of Months | 399.25 | 0.09 | 331.73 | 0.00 | 331.73 | 0.00 | 0.00 |
Maximum of Months | 1999.95 | 614.27 | 635.41 | 35.28 | 600.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 566.31 | 387.25 | 428.62 | 129.68 | 298.94 | 0.00 | 0.00 |
February | 673.79 | 327.67 | 467.10 | 126.59 | 340.51 | 0.00 | 0.00 |
March | 841.40 | 253.23 | 515.96 | 127.16 | 388.79 | 0.00 | 0.00 |
April | 1181.13 | 162.96 | 628.20 | 183.04 | 445.16 | 0.00 | 0.00 |
May | 1571.70 | 40.86 | 702.03 | 223.67 | 478.36 | 0.00 | 0.00 |
June | 1652.61 | 9.74 | 687.53 | 210.25 | 477.28 | 0.00 | 0.00 |
July | 1771.02 | 0.14 | 641.71 | 185.00 | 456.70 | 0.00 | 0.00 |
August | 1828.56 | 0.03 | 657.10 | 201.67 | 455.42 | 0.00 | 0.00 |
September | 1494.57 | 14.30 | 617.75 | 190.94 | 426.81 | 0.00 | 0.00 |
October | 1182.22 | 64.19 | 560.54 | 183.13 | 377.41 | 0.00 | 0.00 |
November | 836.46 | 181.44 | 469.74 | 148.79 | 320.95 | 0.00 | 0.00 |
December | 547.41 | 319.41 | 380.21 | 104.31 | 275.89 | 0.00 | 0.00 |
Annual Sum or Average | 1181.85 | 145.88 | 563.41 | 168.02 | 395.39 | 0.00 | 0.00 |
Minimum of Months | 547.41 | 0.03 | 380.21 | 104.31 | 275.89 | 0.00 | 0.00 |
Maximum of Months | 1828.56 | 387.25 | 702.03 | 223.67 | 478.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1704.08 | 604.41 | 1148.64 | 540.03 | 608.62 | 0.00 | 0.00 |
February | 1689.51 | 516.60 | 1078.63 | 441.20 | 637.42 | 0.00 | 0.00 |
March | 1539.20 | 404.42 | 887.76 | 241.02 | 646.74 | 0.00 | 0.00 |
April | 1413.29 | 257.09 | 697.85 | 73.98 | 623.86 | 0.00 | 0.00 |
May | 1567.57 | 64.11 | 591.14 | 9.05 | 582.08 | 0.00 | 0.00 |
June | 1655.25 | 13.19 | 556.72 | 0.69 | 556.03 | 0.00 | 0.00 |
July | 1940.80 | 0.15 | 556.70 | 4.73 | 551.97 | 0.00 | 0.00 |
August | 2181.30 | 0.05 | 645.73 | 45.75 | 599.98 | 0.00 | 0.00 |
September | 2191.58 | 23.93 | 851.40 | 195.12 | 656.28 | 0.00 | 0.00 |
October | 2311.68 | 104.87 | 1114.64 | 443.13 | 671.51 | 0.00 | 0.00 |
November | 2178.77 | 289.07 | 1229.68 | 592.80 | 636.88 | 0.00 | 0.00 |
December | 1792.20 | 504.01 | 1141.51 | 563.87 | 577.64 | 0.00 | 0.00 |
Annual Sum or Average | 1848.26 | 230.43 | 873.81 | 261.66 | 612.15 | 0.00 | 0.00 |
Minimum of Months | 1413.29 | 0.05 | 556.70 | 0.69 | 551.97 | 0.00 | 0.00 |
Maximum of Months | 2311.68 | 604.41 | 1229.68 | 592.80 | 671.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 578.44 | 409.31 | 420.34 | 120.73 | 299.62 | 0.00 | 0.00 |
February | 716.45 | 344.61 | 479.99 | 136.87 | 343.12 | 0.00 | 0.00 |
March | 942.44 | 268.91 | 568.56 | 168.32 | 400.24 | 0.00 | 0.00 |
April | 1173.78 | 175.93 | 621.34 | 174.56 | 446.78 | 0.00 | 0.00 |
May | 1533.83 | 46.82 | 676.32 | 202.45 | 473.87 | 0.00 | 0.00 |
June | 1678.53 | 10.91 | 698.93 | 220.32 | 478.61 | 0.00 | 0.00 |
July | 1769.04 | 0.15 | 641.19 | 183.43 | 457.76 | 0.00 | 0.00 |
August | 1821.52 | 0.08 | 657.79 | 200.00 | 457.79 | 0.00 | 0.00 |
September | 1507.93 | 17.44 | 625.73 | 196.58 | 429.14 | 0.00 | 0.00 |
October | 1181.73 | 73.81 | 556.09 | 179.63 | 376.46 | 0.00 | 0.00 |
November | 868.98 | 195.35 | 477.89 | 156.28 | 321.60 | 0.00 | 0.00 |
December | 605.08 | 337.16 | 400.07 | 120.93 | 279.13 | 0.00 | 0.00 |
Annual Sum or Average | 1200.91 | 155.79 | 569.01 | 171.79 | 397.21 | 0.00 | 0.00 |
Minimum of Months | 578.44 | 0.08 | 400.07 | 120.73 | 279.13 | 0.00 | 0.00 |
Maximum of Months | 1821.52 | 409.31 | 698.93 | 220.32 | 478.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 377.30 | 708.15 | 355.41 | 0.00 | 355.41 | 0.00 | 0.00 |
February | 525.45 | 574.48 | 407.40 | 0.00 | 407.40 | 0.00 | 0.00 |
March | 751.89 | 419.86 | 467.96 | 0.00 | 467.96 | 0.00 | 0.00 |
April | 1071.77 | 252.93 | 527.24 | 1.09 | 526.15 | 0.00 | 0.00 |
May | 1585.30 | 61.61 | 593.45 | 17.41 | 576.05 | 0.00 | 0.00 |
June | 1817.57 | 15.87 | 635.40 | 35.28 | 600.13 | 0.00 | 0.00 |
July | 2003.88 | 0.38 | 583.04 | 16.80 | 566.25 | 0.00 | 0.00 |
August | 1955.60 | 0.06 | 542.76 | 4.49 | 538.28 | 0.00 | 0.00 |
September | 1478.28 | 27.90 | 494.41 | 0.06 | 494.35 | 0.00 | 0.00 |
October | 1065.15 | 122.51 | 438.28 | 0.00 | 438.28 | 0.00 | 0.00 |
November | 685.05 | 332.78 | 376.26 | 0.00 | 376.26 | 0.00 | 0.00 |
December | 415.19 | 587.96 | 331.73 | 0.00 | 331.73 | 0.00 | 0.00 |
Annual Sum or Average | 1148.16 | 257.22 | 479.72 | 6.28 | 473.44 | 0.00 | 0.00 |
Minimum of Months | 377.30 | 0.06 | 331.73 | 0.00 | 331.73 | 0.00 | 0.00 |
Maximum of Months | 2003.88 | 708.15 | 635.40 | 35.28 | 600.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 548.71 | 446.44 | 428.62 | 129.68 | 298.94 | 0.00 | 0.00 |
February | 666.39 | 367.18 | 467.10 | 126.58 | 340.51 | 0.00 | 0.00 |
March | 844.53 | 271.60 | 515.96 | 127.16 | 388.79 | 0.00 | 0.00 |
April | 1191.77 | 168.27 | 628.20 | 183.03 | 445.16 | 0.00 | 0.00 |
May | 1581.38 | 41.88 | 702.03 | 223.67 | 478.36 | 0.00 | 0.00 |
June | 1657.64 | 10.41 | 687.53 | 210.25 | 477.28 | 0.00 | 0.00 |
July | 1772.12 | 0.25 | 641.70 | 185.00 | 456.70 | 0.00 | 0.00 |
August | 1820.34 | 0.04 | 657.09 | 201.67 | 455.42 | 0.00 | 0.00 |
September | 1486.16 | 18.04 | 617.74 | 190.94 | 426.81 | 0.00 | 0.00 |
October | 1173.08 | 79.54 | 560.54 | 183.13 | 377.41 | 0.00 | 0.00 |
November | 824.68 | 215.08 | 469.73 | 148.79 | 320.95 | 0.00 | 0.00 |
December | 530.39 | 374.47 | 380.20 | 104.31 | 275.89 | 0.00 | 0.00 |
Annual Sum or Average | 1177.68 | 165.14 | 563.41 | 168.02 | 395.39 | 0.00 | 0.00 |
Minimum of Months | 530.39 | 0.04 | 380.20 | 104.31 | 275.89 | 0.00 | 0.00 |
Maximum of Months | 1820.34 | 446.44 | 702.03 | 223.67 | 478.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1692.75 | 698.72 | 1148.66 | 540.04 | 608.62 | 0.00 | 0.00 |
February | 1689.95 | 583.27 | 1078.64 | 441.21 | 637.43 | 0.00 | 0.00 |
March | 1547.96 | 434.68 | 887.77 | 241.02 | 646.74 | 0.00 | 0.00 |
April | 1426.55 | 262.73 | 697.85 | 73.99 | 623.87 | 0.00 | 0.00 |
May | 1569.39 | 64.16 | 591.14 | 9.05 | 582.09 | 0.00 | 0.00 |
June | 1643.66 | 14.02 | 556.72 | 0.69 | 556.03 | 0.00 | 0.00 |
July | 1923.80 | 0.21 | 556.70 | 4.73 | 551.97 | 0.00 | 0.00 |
August | 2143.34 | 0.09 | 645.73 | 45.75 | 599.98 | 0.00 | 0.00 |
September | 2160.68 | 31.26 | 851.40 | 195.12 | 656.28 | 0.00 | 0.00 |
October | 2289.44 | 135.31 | 1114.66 | 443.14 | 671.52 | 0.00 | 0.00 |
November | 2166.46 | 348.96 | 1229.69 | 592.80 | 636.89 | 0.00 | 0.00 |
December | 1780.50 | 590.77 | 1141.53 | 563.88 | 577.65 | 0.00 | 0.00 |
Annual Sum or Average | 1837.26 | 262.14 | 873.82 | 261.67 | 612.15 | 0.00 | 0.00 |
Minimum of Months | 1426.55 | 0.09 | 556.70 | 0.69 | 551.97 | 0.00 | 0.00 |
Maximum of Months | 2289.44 | 698.72 | 1229.69 | 592.80 | 671.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 564.00 | 477.71 | 420.34 | 120.72 | 299.61 | 0.00 | 0.00 |
February | 710.46 | 390.17 | 479.98 | 136.87 | 343.11 | 0.00 | 0.00 |
March | 946.84 | 291.59 | 568.56 | 168.32 | 400.23 | 0.00 | 0.00 |
April | 1184.63 | 182.69 | 621.33 | 174.56 | 446.77 | 0.00 | 0.00 |
May | 1542.31 | 48.54 | 676.32 | 202.45 | 473.87 | 0.00 | 0.00 |
June | 1680.14 | 12.26 | 698.92 | 220.32 | 478.60 | 0.00 | 0.00 |
July | 1767.09 | 0.30 | 641.18 | 183.43 | 457.76 | 0.00 | 0.00 |
August | 1811.58 | 0.09 | 657.78 | 199.99 | 457.79 | 0.00 | 0.00 |
September | 1498.50 | 21.78 | 625.72 | 196.58 | 429.14 | 0.00 | 0.00 |
October | 1171.83 | 90.31 | 556.08 | 179.63 | 376.45 | 0.00 | 0.00 |
November | 858.07 | 233.04 | 477.88 | 156.28 | 321.60 | 0.00 | 0.00 |
December | 590.36 | 399.33 | 400.06 | 120.93 | 279.13 | 0.00 | 0.00 |
Annual Sum or Average | 1196.57 | 177.98 | 569.00 | 171.79 | 397.21 | 0.00 | 0.00 |
Minimum of Months | 564.00 | 0.09 | 400.06 | 120.72 | 279.13 | 0.00 | 0.00 |
Maximum of Months | 1811.58 | 477.71 | 698.92 | 220.32 | 478.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 383.78 | 676.06 | 355.41 | 0.00 | 355.41 | 0.00 | 0.00 |
February | 525.70 | 561.04 | 407.41 | 0.00 | 407.41 | 0.00 | 0.00 |
March | 745.69 | 424.14 | 467.96 | 0.00 | 467.96 | 0.00 | 0.00 |
April | 1063.01 | 263.17 | 527.24 | 1.09 | 526.15 | 0.00 | 0.00 |
May | 1583.40 | 65.44 | 593.46 | 17.41 | 576.05 | 0.00 | 0.00 |
June | 1823.35 | 16.62 | 635.41 | 35.28 | 600.13 | 0.00 | 0.00 |
July | 2017.84 | 0.33 | 583.05 | 16.80 | 566.25 | 0.00 | 0.00 |
August | 1981.44 | 0.07 | 542.77 | 4.49 | 538.28 | 0.00 | 0.00 |
September | 1502.01 | 24.62 | 494.41 | 0.06 | 494.35 | 0.00 | 0.00 |
October | 1087.88 | 110.45 | 438.28 | 0.00 | 438.28 | 0.00 | 0.00 |
November | 702.17 | 307.09 | 376.26 | 0.00 | 376.26 | 0.00 | 0.00 |
December | 425.83 | 550.55 | 331.73 | 0.00 | 331.73 | 0.00 | 0.00 |
Annual Sum or Average | 1157.36 | 248.47 | 479.72 | 6.28 | 473.44 | 0.00 | 0.00 |
Minimum of Months | 383.78 | 0.07 | 331.73 | 0.00 | 331.73 | 0.00 | 0.00 |
Maximum of Months | 2017.84 | 676.06 | 635.41 | 35.28 | 600.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 553.90 | 420.53 | 428.62 | 129.68 | 298.94 | 0.00 | 0.00 |
February | 666.54 | 352.60 | 467.10 | 126.59 | 340.51 | 0.00 | 0.00 |
March | 839.83 | 269.05 | 515.96 | 127.16 | 388.79 | 0.00 | 0.00 |
April | 1185.68 | 169.11 | 628.20 | 183.04 | 445.16 | 0.00 | 0.00 |
May | 1581.66 | 41.39 | 702.03 | 223.67 | 478.36 | 0.00 | 0.00 |
June | 1663.06 | 9.64 | 687.53 | 210.25 | 477.28 | 0.00 | 0.00 |
July | 1784.01 | 0.14 | 641.71 | 185.00 | 456.70 | 0.00 | 0.00 |
August | 1840.19 | 0.03 | 657.10 | 201.67 | 455.42 | 0.00 | 0.00 |
September | 1503.44 | 14.51 | 617.75 | 190.94 | 426.81 | 0.00 | 0.00 |
October | 1187.59 | 67.45 | 560.54 | 183.13 | 377.41 | 0.00 | 0.00 |
November | 835.54 | 193.65 | 469.74 | 148.79 | 320.95 | 0.00 | 0.00 |
December | 538.23 | 346.14 | 380.21 | 104.31 | 275.89 | 0.00 | 0.00 |
Annual Sum or Average | 1184.61 | 156.07 | 563.41 | 168.02 | 395.39 | 0.00 | 0.00 |
Minimum of Months | 538.23 | 0.03 | 380.21 | 104.31 | 275.89 | 0.00 | 0.00 |
Maximum of Months | 1840.19 | 420.53 | 702.03 | 223.67 | 478.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1690.12 | 656.00 | 1148.64 | 540.03 | 608.62 | 0.00 | 0.00 |
February | 1682.82 | 556.98 | 1078.63 | 441.20 | 637.42 | 0.00 | 0.00 |
March | 1539.20 | 431.50 | 887.76 | 241.02 | 646.74 | 0.00 | 0.00 |
April | 1419.67 | 268.96 | 697.85 | 73.98 | 623.86 | 0.00 | 0.00 |
May | 1579.75 | 65.79 | 591.14 | 9.05 | 582.08 | 0.00 | 0.00 |
June | 1667.30 | 13.40 | 556.72 | 0.69 | 556.03 | 0.00 | 0.00 |
July | 1957.31 | 0.15 | 556.70 | 4.73 | 551.97 | 0.00 | 0.00 |
August | 2196.16 | 0.04 | 645.73 | 45.75 | 599.98 | 0.00 | 0.00 |
September | 2203.92 | 24.49 | 851.40 | 195.12 | 656.28 | 0.00 | 0.00 |
October | 2320.72 | 110.32 | 1114.64 | 443.13 | 671.51 | 0.00 | 0.00 |
November | 2179.90 | 307.39 | 1229.68 | 592.80 | 636.88 | 0.00 | 0.00 |
December | 1782.89 | 544.12 | 1141.51 | 563.87 | 577.64 | 0.00 | 0.00 |
Annual Sum or Average | 1852.86 | 246.76 | 873.81 | 261.66 | 612.15 | 0.00 | 0.00 |
Minimum of Months | 1419.67 | 0.04 | 556.70 | 0.69 | 551.97 | 0.00 | 0.00 |
Maximum of Months | 2320.72 | 656.00 | 1229.68 | 592.80 | 671.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 567.97 | 449.50 | 420.34 | 120.73 | 299.62 | 0.00 | 0.00 |
February | 710.00 | 374.35 | 479.99 | 136.87 | 343.12 | 0.00 | 0.00 |
March | 941.44 | 287.71 | 568.56 | 168.32 | 400.24 | 0.00 | 0.00 |
April | 1178.04 | 183.72 | 621.34 | 174.56 | 446.78 | 0.00 | 0.00 |
May | 1542.72 | 47.90 | 676.32 | 202.45 | 473.87 | 0.00 | 0.00 |
June | 1687.24 | 11.05 | 698.93 | 220.32 | 478.61 | 0.00 | 0.00 |
July | 1779.76 | 0.15 | 641.19 | 183.43 | 457.76 | 0.00 | 0.00 |
August | 1831.29 | 0.08 | 657.79 | 200.00 | 457.79 | 0.00 | 0.00 |
September | 1515.49 | 17.79 | 625.73 | 196.58 | 429.14 | 0.00 | 0.00 |
October | 1186.12 | 77.76 | 556.09 | 179.63 | 376.46 | 0.00 | 0.00 |
November | 868.25 | 209.90 | 477.89 | 156.28 | 321.60 | 0.00 | 0.00 |
December | 597.05 | 368.62 | 400.07 | 120.93 | 279.13 | 0.00 | 0.00 |
Annual Sum or Average | 1203.25 | 168.05 | 569.01 | 171.79 | 397.21 | 0.00 | 0.00 |
Minimum of Months | 567.97 | 0.08 | 400.07 | 120.73 | 279.13 | 0.00 | 0.00 |
Maximum of Months | 1831.29 | 449.50 | 698.93 | 220.32 | 478.61 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.106934E+10 | 0.164525E+10 | 0.951942E+09 | 0.00 | 0.951942E+09 | 0.00 | 0.00 |
February | 0.129555E+10 | 0.124784E+10 | 0.985598E+09 | 0.00 | 0.985598E+09 | 0.00 | 0.00 |
March | 0.200309E+10 | 0.106054E+10 | 0.125339E+10 | 0.00 | 0.125339E+10 | 0.00 | 0.00 |
April | 0.274066E+10 | 0.653395E+09 | 0.136661E+10 | 2815821.33 | 0.136379E+10 | 0.00 | 0.00 |
May | 0.420740E+10 | 0.172894E+09 | 0.158951E+10 | 46619386.00 | 0.154289E+10 | 0.00 | 0.00 |
June | 0.469059E+10 | 43417362.21 | 0.164697E+10 | 91434997.90 | 0.155554E+10 | 0.00 | 0.00 |
July | 0.535668E+10 | 893738.84 | 0.156163E+10 | 44994457.35 | 0.151664E+10 | 0.00 | 0.00 |
August | 0.526543E+10 | 228227.13 | 0.145375E+10 | 12023936.16 | 0.144172E+10 | 0.00 | 0.00 |
September | 0.386493E+10 | 62680764.02 | 0.128151E+10 | 146849.74 | 0.128137E+10 | 0.00 | 0.00 |
October | 0.289928E+10 | 0.280883E+09 | 0.117390E+10 | 0.00 | 0.117390E+10 | 0.00 | 0.00 |
November | 0.182526E+10 | 0.740333E+09 | 0.975261E+09 | 0.00 | 0.975261E+09 | 0.00 | 0.00 |
December | 0.117251E+10 | 0.134577E+10 | 0.888515E+09 | 0.00 | 0.888515E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.363907E+11 | 0.725413E+10 | 0.151286E+11 | 0.198035E+09 | 0.149306E+11 | 0.00 | 0.00 |
Minimum of Months | 0.106934E+10 | 228227.13 | 0.888515E+09 | 0.00 | 0.888515E+09 | 0.00 | 0.00 |
Maximum of Months | 0.535668E+10 | 0.164525E+10 | 0.164697E+10 | 91434997.90 | 0.155554E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.151679E+10 | 0.103721E+10 | 0.114802E+10 | 0.347331E+09 | 0.800689E+09 | 0.00 | 0.00 |
February | 0.163002E+10 | 0.792709E+09 | 0.113001E+10 | 0.306236E+09 | 0.823770E+09 | 0.00 | 0.00 |
March | 0.225362E+10 | 0.678252E+09 | 0.138195E+10 | 0.340598E+09 | 0.104135E+10 | 0.00 | 0.00 |
April | 0.306150E+10 | 0.422400E+09 | 0.162830E+10 | 0.474431E+09 | 0.115387E+10 | 0.00 | 0.00 |
May | 0.420964E+10 | 0.109452E+09 | 0.188032E+10 | 0.599079E+09 | 0.128124E+10 | 0.00 | 0.00 |
June | 0.428357E+10 | 25248183.77 | 0.178208E+10 | 0.544979E+09 | 0.123711E+10 | 0.00 | 0.00 |
July | 0.474351E+10 | 369717.13 | 0.171874E+10 | 0.495509E+09 | 0.122323E+10 | 0.00 | 0.00 |
August | 0.489763E+10 | 92210.47 | 0.175996E+10 | 0.540155E+09 | 0.121981E+10 | 0.00 | 0.00 |
September | 0.387392E+10 | 37068911.82 | 0.160120E+10 | 0.494910E+09 | 0.110629E+10 | 0.00 | 0.00 |
October | 0.316646E+10 | 0.171938E+09 | 0.150136E+10 | 0.490493E+09 | 0.101086E+10 | 0.00 | 0.00 |
November | 0.216811E+10 | 0.470290E+09 | 0.121756E+10 | 0.385659E+09 | 0.831898E+09 | 0.00 | 0.00 |
December | 0.146619E+10 | 0.855512E+09 | 0.101834E+10 | 0.279392E+09 | 0.738953E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.372710E+11 | 0.460054E+10 | 0.177678E+11 | 0.529877E+10 | 0.124691E+11 | 0.00 | 0.00 |
Minimum of Months | 0.146619E+10 | 92210.47 | 0.101834E+10 | 0.279392E+09 | 0.738953E+09 | 0.00 | 0.00 |
Maximum of Months | 0.489763E+10 | 0.103721E+10 | 0.188032E+10 | 0.599079E+09 | 0.128124E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.456422E+10 | 0.161885E+10 | 0.307653E+10 | 0.144641E+10 | 0.163012E+10 | 0.00 | 0.00 |
February | 0.408727E+10 | 0.124976E+10 | 0.260941E+10 | 0.106736E+10 | 0.154205E+10 | 0.00 | 0.00 |
March | 0.412260E+10 | 0.108319E+10 | 0.237777E+10 | 0.645551E+09 | 0.173222E+10 | 0.00 | 0.00 |
April | 0.366326E+10 | 0.666372E+09 | 0.180882E+10 | 0.191768E+09 | 0.161705E+10 | 0.00 | 0.00 |
May | 0.419859E+10 | 0.171705E+09 | 0.158330E+10 | 24246543.42 | 0.155905E+10 | 0.00 | 0.00 |
June | 0.429040E+10 | 34181249.45 | 0.144301E+10 | 1785763.13 | 0.144122E+10 | 0.00 | 0.00 |
July | 0.519823E+10 | 408590.49 | 0.149107E+10 | 12669433.04 | 0.147840E+10 | 0.00 | 0.00 |
August | 0.584240E+10 | 135395.42 | 0.172952E+10 | 0.122543E+09 | 0.160697E+10 | 0.00 | 0.00 |
September | 0.568057E+10 | 62019656.48 | 0.220682E+10 | 0.505756E+09 | 0.170107E+10 | 0.00 | 0.00 |
October | 0.619160E+10 | 0.280895E+09 | 0.298546E+10 | 0.118689E+10 | 0.179858E+10 | 0.00 | 0.00 |
November | 0.564736E+10 | 0.749275E+09 | 0.318733E+10 | 0.153653E+10 | 0.165080E+10 | 0.00 | 0.00 |
December | 0.480023E+10 | 0.134995E+10 | 0.305743E+10 | 0.151028E+10 | 0.154716E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.582867E+11 | 0.726675E+10 | 0.275565E+11 | 0.825179E+10 | 0.193047E+11 | 0.00 | 0.00 |
Minimum of Months | 0.366326E+10 | 135395.42 | 0.144301E+10 | 1785763.13 | 0.144122E+10 | 0.00 | 0.00 |
Maximum of Months | 0.619160E+10 | 0.161885E+10 | 0.318733E+10 | 0.153653E+10 | 0.179858E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.154928E+10 | 0.109628E+10 | 0.112585E+10 | 0.323352E+09 | 0.802494E+09 | 0.00 | 0.00 |
February | 0.173323E+10 | 0.833669E+09 | 0.116119E+10 | 0.331123E+09 | 0.830064E+09 | 0.00 | 0.00 |
March | 0.252422E+10 | 0.720251E+09 | 0.152283E+10 | 0.450837E+09 | 0.107200E+10 | 0.00 | 0.00 |
April | 0.304244E+10 | 0.456012E+09 | 0.161051E+10 | 0.452466E+09 | 0.115804E+10 | 0.00 | 0.00 |
May | 0.410821E+10 | 0.125415E+09 | 0.181147E+10 | 0.542244E+09 | 0.126922E+10 | 0.00 | 0.00 |
June | 0.435075E+10 | 28273618.11 | 0.181161E+10 | 0.571068E+09 | 0.124055E+10 | 0.00 | 0.00 |
July | 0.473820E+10 | 396107.26 | 0.171736E+10 | 0.491301E+09 | 0.122606E+10 | 0.00 | 0.00 |
August | 0.487876E+10 | 222492.71 | 0.176182E+10 | 0.535667E+09 | 0.122615E+10 | 0.00 | 0.00 |
September | 0.390856E+10 | 45211351.68 | 0.162188E+10 | 0.509547E+09 | 0.111233E+10 | 0.00 | 0.00 |
October | 0.316514E+10 | 0.197701E+09 | 0.148942E+10 | 0.481123E+09 | 0.100830E+10 | 0.00 | 0.00 |
November | 0.225241E+10 | 0.506356E+09 | 0.123868E+10 | 0.405089E+09 | 0.833596E+09 | 0.00 | 0.00 |
December | 0.162065E+10 | 0.903050E+09 | 0.107154E+10 | 0.323906E+09 | 0.747632E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.378718E+11 | 0.491284E+10 | 0.179442E+11 | 0.541772E+10 | 0.125264E+11 | 0.00 | 0.00 |
Minimum of Months | 0.154928E+10 | 222492.71 | 0.107154E+10 | 0.323352E+09 | 0.747632E+09 | 0.00 | 0.00 |
Maximum of Months | 0.487876E+10 | 0.109628E+10 | 0.181161E+10 | 0.571068E+09 | 0.126922E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101057E+10 | 0.189670E+10 | 0.951937E+09 | 0.00 | 0.951937E+09 | 0.00 | 0.00 |
February | 0.127117E+10 | 0.138978E+10 | 0.985593E+09 | 0.00 | 0.985593E+09 | 0.00 | 0.00 |
March | 0.201385E+10 | 0.112456E+10 | 0.125338E+10 | 0.00 | 0.125338E+10 | 0.00 | 0.00 |
April | 0.277803E+10 | 0.655582E+09 | 0.136660E+10 | 2815806.74 | 0.136378E+10 | 0.00 | 0.00 |
May | 0.424607E+10 | 0.165018E+09 | 0.158950E+10 | 46619144.42 | 0.154288E+10 | 0.00 | 0.00 |
June | 0.471115E+10 | 41142696.47 | 0.164696E+10 | 91434524.10 | 0.155553E+10 | 0.00 | 0.00 |
July | 0.536718E+10 | 1017821.87 | 0.156163E+10 | 44994224.20 | 0.151663E+10 | 0.00 | 0.00 |
August | 0.523789E+10 | 165268.08 | 0.145374E+10 | 12023873.86 | 0.144172E+10 | 0.00 | 0.00 |
September | 0.383171E+10 | 72306983.95 | 0.128151E+10 | 146848.98 | 0.128136E+10 | 0.00 | 0.00 |
October | 0.285291E+10 | 0.328138E+09 | 0.117390E+10 | 0.00 | 0.117390E+10 | 0.00 | 0.00 |
November | 0.177566E+10 | 0.862556E+09 | 0.975256E+09 | 0.00 | 0.975256E+09 | 0.00 | 0.00 |
December | 0.111204E+10 | 0.157480E+10 | 0.888510E+09 | 0.00 | 0.888510E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.362082E+11 | 0.811176E+10 | 0.151285E+11 | 0.198034E+09 | 0.149305E+11 | 0.00 | 0.00 |
Minimum of Months | 0.101057E+10 | 165268.08 | 0.888510E+09 | 0.00 | 0.888510E+09 | 0.00 | 0.00 |
Maximum of Months | 0.536718E+10 | 0.189670E+10 | 0.164696E+10 | 91434524.10 | 0.155553E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.146968E+10 | 0.119575E+10 | 0.114801E+10 | 0.347328E+09 | 0.800684E+09 | 0.00 | 0.00 |
February | 0.161213E+10 | 0.888282E+09 | 0.113000E+10 | 0.306233E+09 | 0.823765E+09 | 0.00 | 0.00 |
March | 0.226198E+10 | 0.727455E+09 | 0.138194E+10 | 0.340594E+09 | 0.104134E+10 | 0.00 | 0.00 |
April | 0.308907E+10 | 0.436160E+09 | 0.162829E+10 | 0.474426E+09 | 0.115386E+10 | 0.00 | 0.00 |
May | 0.423556E+10 | 0.112181E+09 | 0.188031E+10 | 0.599073E+09 | 0.128124E+10 | 0.00 | 0.00 |
June | 0.429659E+10 | 26993450.27 | 0.178207E+10 | 0.544974E+09 | 0.123710E+10 | 0.00 | 0.00 |
July | 0.474645E+10 | 657614.92 | 0.171873E+10 | 0.495504E+09 | 0.122323E+10 | 0.00 | 0.00 |
August | 0.487560E+10 | 111918.56 | 0.175995E+10 | 0.540150E+09 | 0.121980E+10 | 0.00 | 0.00 |
September | 0.385213E+10 | 46754475.49 | 0.160119E+10 | 0.494905E+09 | 0.110628E+10 | 0.00 | 0.00 |
October | 0.314199E+10 | 0.213036E+09 | 0.150135E+10 | 0.490488E+09 | 0.101086E+10 | 0.00 | 0.00 |
November | 0.213757E+10 | 0.557482E+09 | 0.121755E+10 | 0.385655E+09 | 0.831893E+09 | 0.00 | 0.00 |
December | 0.142059E+10 | 0.100298E+10 | 0.101834E+10 | 0.279389E+09 | 0.738948E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.371393E+11 | 0.520785E+10 | 0.177677E+11 | 0.529872E+10 | 0.124690E+11 | 0.00 | 0.00 |
Minimum of Months | 0.142059E+10 | 111918.56 | 0.101834E+10 | 0.279389E+09 | 0.738948E+09 | 0.00 | 0.00 |
Maximum of Months | 0.487560E+10 | 0.119575E+10 | 0.188031E+10 | 0.599073E+09 | 0.128124E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.453387E+10 | 0.187146E+10 | 0.307656E+10 | 0.144643E+10 | 0.163013E+10 | 0.00 | 0.00 |
February | 0.408832E+10 | 0.141105E+10 | 0.260944E+10 | 0.106737E+10 | 0.154206E+10 | 0.00 | 0.00 |
March | 0.414606E+10 | 0.116424E+10 | 0.237779E+10 | 0.645558E+09 | 0.173224E+10 | 0.00 | 0.00 |
April | 0.369762E+10 | 0.680999E+09 | 0.180883E+10 | 0.191770E+09 | 0.161706E+10 | 0.00 | 0.00 |
May | 0.420345E+10 | 0.171843E+09 | 0.158331E+10 | 24246825.73 | 0.155906E+10 | 0.00 | 0.00 |
June | 0.426037E+10 | 36335483.37 | 0.144301E+10 | 1785783.93 | 0.144123E+10 | 0.00 | 0.00 |
July | 0.515270E+10 | 557865.46 | 0.149107E+10 | 12669580.55 | 0.147840E+10 | 0.00 | 0.00 |
August | 0.574071E+10 | 235835.71 | 0.172953E+10 | 0.122544E+09 | 0.160698E+10 | 0.00 | 0.00 |
September | 0.560049E+10 | 81030490.39 | 0.220684E+10 | 0.505762E+09 | 0.170108E+10 | 0.00 | 0.00 |
October | 0.613203E+10 | 0.362404E+09 | 0.298549E+10 | 0.118690E+10 | 0.179859E+10 | 0.00 | 0.00 |
November | 0.561547E+10 | 0.904510E+09 | 0.318736E+10 | 0.153654E+10 | 0.165082E+10 | 0.00 | 0.00 |
December | 0.476889E+10 | 0.158232E+10 | 0.305746E+10 | 0.151029E+10 | 0.154717E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.579400E+11 | 0.826698E+10 | 0.275567E+11 | 0.825188E+10 | 0.193048E+11 | 0.00 | 0.00 |
Minimum of Months | 0.369762E+10 | 235835.71 | 0.144301E+10 | 1785783.93 | 0.144123E+10 | 0.00 | 0.00 |
Maximum of Months | 0.613203E+10 | 0.187146E+10 | 0.318736E+10 | 0.153654E+10 | 0.179859E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.151062E+10 | 0.127951E+10 | 0.112584E+10 | 0.323348E+09 | 0.802488E+09 | 0.00 | 0.00 |
February | 0.171874E+10 | 0.943902E+09 | 0.116118E+10 | 0.331120E+09 | 0.830059E+09 | 0.00 | 0.00 |
March | 0.253601E+10 | 0.780984E+09 | 0.152282E+10 | 0.450833E+09 | 0.107199E+10 | 0.00 | 0.00 |
April | 0.307055E+10 | 0.473524E+09 | 0.161050E+10 | 0.452462E+09 | 0.115804E+10 | 0.00 | 0.00 |
May | 0.413091E+10 | 0.130017E+09 | 0.181146E+10 | 0.542238E+09 | 0.126922E+10 | 0.00 | 0.00 |
June | 0.435492E+10 | 31777440.55 | 0.181160E+10 | 0.571062E+09 | 0.124054E+10 | 0.00 | 0.00 |
July | 0.473296E+10 | 811387.55 | 0.171735E+10 | 0.491296E+09 | 0.122605E+10 | 0.00 | 0.00 |
August | 0.485214E+10 | 234519.25 | 0.176181E+10 | 0.535662E+09 | 0.122615E+10 | 0.00 | 0.00 |
September | 0.388412E+10 | 56462591.77 | 0.162187E+10 | 0.509542E+09 | 0.111233E+10 | 0.00 | 0.00 |
October | 0.313862E+10 | 0.241879E+09 | 0.148941E+10 | 0.481119E+09 | 0.100829E+10 | 0.00 | 0.00 |
November | 0.222413E+10 | 0.604042E+09 | 0.123868E+10 | 0.405085E+09 | 0.833591E+09 | 0.00 | 0.00 |
December | 0.158121E+10 | 0.106956E+10 | 0.107153E+10 | 0.323903E+09 | 0.747627E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.377349E+11 | 0.561271E+10 | 0.179440E+11 | 0.541767E+10 | 0.125264E+11 | 0.00 | 0.00 |
Minimum of Months | 0.151062E+10 | 234519.25 | 0.107153E+10 | 0.323348E+09 | 0.747627E+09 | 0.00 | 0.00 |
Maximum of Months | 0.485214E+10 | 0.127951E+10 | 0.181160E+10 | 0.571062E+09 | 0.126922E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.102792E+10 | 0.181075E+10 | 0.951942E+09 | 0.00 | 0.951942E+09 | 0.00 | 0.00 |
February | 0.127178E+10 | 0.135726E+10 | 0.985598E+09 | 0.00 | 0.985598E+09 | 0.00 | 0.00 |
March | 0.199726E+10 | 0.113600E+10 | 0.125339E+10 | 0.00 | 0.125339E+10 | 0.00 | 0.00 |
April | 0.275532E+10 | 0.682132E+09 | 0.136661E+10 | 2815821.33 | 0.136379E+10 | 0.00 | 0.00 |
May | 0.424099E+10 | 0.175283E+09 | 0.158951E+10 | 46619386.00 | 0.154289E+10 | 0.00 | 0.00 |
June | 0.472612E+10 | 43069145.24 | 0.164697E+10 | 91434997.90 | 0.155554E+10 | 0.00 | 0.00 |
July | 0.540457E+10 | 888571.73 | 0.156163E+10 | 44994457.35 | 0.151664E+10 | 0.00 | 0.00 |
August | 0.530709E+10 | 185235.48 | 0.145375E+10 | 12023936.16 | 0.144172E+10 | 0.00 | 0.00 |
September | 0.389322E+10 | 63820437.83 | 0.128151E+10 | 146849.74 | 0.128137E+10 | 0.00 | 0.00 |
October | 0.291377E+10 | 0.295828E+09 | 0.117390E+10 | 0.00 | 0.117390E+10 | 0.00 | 0.00 |
November | 0.182002E+10 | 0.795986E+09 | 0.975261E+09 | 0.00 | 0.975261E+09 | 0.00 | 0.00 |
December | 0.114056E+10 | 0.147458E+10 | 0.888515E+09 | 0.00 | 0.888515E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.364986E+11 | 0.783579E+10 | 0.151286E+11 | 0.198035E+09 | 0.149306E+11 | 0.00 | 0.00 |
Minimum of Months | 0.102792E+10 | 185235.48 | 0.888515E+09 | 0.00 | 0.888515E+09 | 0.00 | 0.00 |
Maximum of Months | 0.540457E+10 | 0.181075E+10 | 0.164697E+10 | 91434997.90 | 0.155554E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.148357E+10 | 0.112634E+10 | 0.114802E+10 | 0.347331E+09 | 0.800689E+09 | 0.00 | 0.00 |
February | 0.161249E+10 | 0.853011E+09 | 0.113001E+10 | 0.306236E+09 | 0.823770E+09 | 0.00 | 0.00 |
March | 0.224941E+10 | 0.720636E+09 | 0.138195E+10 | 0.340598E+09 | 0.104135E+10 | 0.00 | 0.00 |
April | 0.307328E+10 | 0.438340E+09 | 0.162830E+10 | 0.474431E+09 | 0.115387E+10 | 0.00 | 0.00 |
May | 0.423632E+10 | 0.110872E+09 | 0.188032E+10 | 0.599079E+09 | 0.128124E+10 | 0.00 | 0.00 |
June | 0.431065E+10 | 24990698.25 | 0.178208E+10 | 0.544979E+09 | 0.123711E+10 | 0.00 | 0.00 |
July | 0.477829E+10 | 368625.19 | 0.171874E+10 | 0.495509E+09 | 0.122323E+10 | 0.00 | 0.00 |
August | 0.492877E+10 | 73150.96 | 0.175996E+10 | 0.540155E+09 | 0.121981E+10 | 0.00 | 0.00 |
September | 0.389693E+10 | 37619859.23 | 0.160120E+10 | 0.494910E+09 | 0.110629E+10 | 0.00 | 0.00 |
October | 0.318084E+10 | 0.180664E+09 | 0.150136E+10 | 0.490493E+09 | 0.101086E+10 | 0.00 | 0.00 |
November | 0.216572E+10 | 0.501932E+09 | 0.121756E+10 | 0.385659E+09 | 0.831898E+09 | 0.00 | 0.00 |
December | 0.144160E+10 | 0.927111E+09 | 0.101834E+10 | 0.279392E+09 | 0.738953E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.373579E+11 | 0.492196E+10 | 0.177678E+11 | 0.529877E+10 | 0.124691E+11 | 0.00 | 0.00 |
Minimum of Months | 0.144160E+10 | 73150.96 | 0.101834E+10 | 0.279392E+09 | 0.738953E+09 | 0.00 | 0.00 |
Maximum of Months | 0.492877E+10 | 0.112634E+10 | 0.188032E+10 | 0.599079E+09 | 0.128124E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.452682E+10 | 0.175703E+10 | 0.307653E+10 | 0.144641E+10 | 0.163012E+10 | 0.00 | 0.00 |
February | 0.407108E+10 | 0.134744E+10 | 0.260941E+10 | 0.106736E+10 | 0.154205E+10 | 0.00 | 0.00 |
March | 0.412260E+10 | 0.115573E+10 | 0.237777E+10 | 0.645551E+09 | 0.173222E+10 | 0.00 | 0.00 |
April | 0.367979E+10 | 0.697134E+09 | 0.180882E+10 | 0.191768E+09 | 0.161705E+10 | 0.00 | 0.00 |
May | 0.423120E+10 | 0.176214E+09 | 0.158330E+10 | 24246543.42 | 0.155905E+10 | 0.00 | 0.00 |
June | 0.432165E+10 | 34731390.76 | 0.144301E+10 | 1785763.13 | 0.144122E+10 | 0.00 | 0.00 |
July | 0.524247E+10 | 394581.34 | 0.149107E+10 | 12669433.04 | 0.147840E+10 | 0.00 | 0.00 |
August | 0.588220E+10 | 106414.86 | 0.172952E+10 | 0.122543E+09 | 0.160697E+10 | 0.00 | 0.00 |
September | 0.571257E+10 | 63475213.39 | 0.220682E+10 | 0.505756E+09 | 0.170107E+10 | 0.00 | 0.00 |
October | 0.621582E+10 | 0.295492E+09 | 0.298546E+10 | 0.118689E+10 | 0.179858E+10 | 0.00 | 0.00 |
November | 0.565029E+10 | 0.796762E+09 | 0.318733E+10 | 0.153653E+10 | 0.165080E+10 | 0.00 | 0.00 |
December | 0.477528E+10 | 0.145738E+10 | 0.305743E+10 | 0.151028E+10 | 0.154716E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.584318E+11 | 0.778189E+10 | 0.275565E+11 | 0.825179E+10 | 0.193047E+11 | 0.00 | 0.00 |
Minimum of Months | 0.367979E+10 | 106414.86 | 0.144301E+10 | 1785763.13 | 0.144122E+10 | 0.00 | 0.00 |
Maximum of Months | 0.621582E+10 | 0.175703E+10 | 0.318733E+10 | 0.153653E+10 | 0.179858E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.152126E+10 | 0.120393E+10 | 0.112585E+10 | 0.323352E+09 | 0.802494E+09 | 0.00 | 0.00 |
February | 0.171762E+10 | 0.905625E+09 | 0.116119E+10 | 0.331123E+09 | 0.830064E+09 | 0.00 | 0.00 |
March | 0.252155E+10 | 0.770596E+09 | 0.152283E+10 | 0.450837E+09 | 0.107200E+10 | 0.00 | 0.00 |
April | 0.305349E+10 | 0.476205E+09 | 0.161051E+10 | 0.452466E+09 | 0.115804E+10 | 0.00 | 0.00 |
May | 0.413202E+10 | 0.128293E+09 | 0.181147E+10 | 0.542244E+09 | 0.126922E+10 | 0.00 | 0.00 |
June | 0.437333E+10 | 28649546.67 | 0.181161E+10 | 0.571068E+09 | 0.124055E+10 | 0.00 | 0.00 |
July | 0.476690E+10 | 396783.24 | 0.171736E+10 | 0.491301E+09 | 0.122606E+10 | 0.00 | 0.00 |
August | 0.490492E+10 | 207542.53 | 0.176182E+10 | 0.535667E+09 | 0.122615E+10 | 0.00 | 0.00 |
September | 0.392814E+10 | 46108325.69 | 0.162188E+10 | 0.509547E+09 | 0.111233E+10 | 0.00 | 0.00 |
October | 0.317692E+10 | 0.208282E+09 | 0.148942E+10 | 0.481123E+09 | 0.100830E+10 | 0.00 | 0.00 |
November | 0.225049E+10 | 0.544060E+09 | 0.123868E+10 | 0.405089E+09 | 0.833596E+09 | 0.00 | 0.00 |
December | 0.159913E+10 | 0.987307E+09 | 0.107154E+10 | 0.323906E+09 | 0.747632E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.379458E+11 | 0.529967E+10 | 0.179442E+11 | 0.541772E+10 | 0.125264E+11 | 0.00 | 0.00 |
Minimum of Months | 0.152126E+10 | 207542.53 | 0.107154E+10 | 0.323352E+09 | 0.747632E+09 | 0.00 | 0.00 |
Maximum of Months | 0.490492E+10 | 0.120393E+10 | 0.181161E+10 | 0.571068E+09 | 0.126922E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.390931E+10 | -0.322142E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687893117.3 | 58.98 | 0.00 | 0.00 |
February | 0.346709E+10 | -0.284590E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -621190269.0 | 58.98 | 0.00 | 0.00 |
March | 0.381910E+10 | -0.313028E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688819609.9 | 58.98 | 0.00 | 0.00 |
April | 0.319688E+10 | -0.253157E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -665313250.6 | 58.98 | 0.00 | 0.00 |
May | 0.310688E+10 | -0.241875E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688133536.7 | 58.97 | 0.00 | 0.00 |
June | 0.285245E+10 | -0.218496E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667480777.3 | 58.98 | 0.00 | 0.00 |
July | 0.268802E+10 | -0.199502E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -693002467.9 | 58.98 | 0.00 | 0.00 |
August | 0.300300E+10 | -0.230751E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -695487010.2 | 58.97 | 0.00 | 0.00 |
September | 0.296934E+10 | -0.230055E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668787816.3 | 58.98 | 0.00 | 0.00 |
October | 0.335945E+10 | -0.267081E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688631224.0 | 58.98 | 0.00 | 0.00 |
November | 0.357252E+10 | -0.290772E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -664803018.0 | 58.98 | 0.00 | 0.00 |
December | 0.376092E+10 | -0.307337E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687550226.6 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.397050E+11 | -0.315879E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.811709E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.268802E+10 | -0.322142E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -695487010.2 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.390931E+10 | -0.199502E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -621190269.0 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.64 | 0.62 | 01-JAN-07:49 | 4211.45 | 34.00 | 310.83 | 292.50 | 1068.93 | 24.88 | 267.67 | 280.17 |
February | 308.33 | 0.63 | 0.62 | 01-FEB-07:40 | 2119.37 | 24.55 | 142.00 | 273.33 | 948.52 | 20.56 | 147.50 | 243.50 |
March | 357.50 | 0.64 | 0.62 | 01-MAR-07:49 | 1544.04 | 17.60 | 5.00 | 312.33 | 804.90 | 20.11 | 110.00 | 275.00 |
April | 375.00 | 0.65 | 0.62 | 01-APR-07:10 | 1198.93 | 16.59 | 0.00 | 321.17 | 636.95 | 19.20 | 35.50 | 281.83 |
May | 405.33 | 0.64 | 0.62 | 01-MAY-06:40 | 1012.69 | 16.50 | 0.00 | 346.50 | 556.87 | 19.16 | 1.17 | 301.67 |
June | 403.50 | 0.65 | 0.62 | 01-JUN-06:30 | 966.95 | 16.37 | 0.00 | 343.17 | 540.87 | 19.10 | 0.00 | 294.50 |
July | 405.00 | 0.65 | 0.62 | 01-JUL-06:49 | 1018.25 | 16.32 | 0.00 | 343.17 | 562.43 | 19.03 | 2.17 | 299.67 |
August | 395.83 | 0.65 | 0.62 | 01-AUG-06:40 | 1200.39 | 16.83 | 0.00 | 342.17 | 646.45 | 19.51 | 70.00 | 301.17 |
September | 358.83 | 0.64 | 0.62 | 01-SEP-06:00 | 1510.49 | 17.58 | 0.00 | 317.67 | 800.15 | 20.27 | 146.33 | 283.50 |
October | 351.17 | 0.64 | 0.62 | 01-OCT-06:00 | 2043.31 | 19.63 | 34.50 | 316.50 | 971.62 | 21.20 | 199.83 | 286.67 |
November | 318.83 | 0.63 | 0.62 | 01-NOV-06:00 | 3516.56 | 31.40 | 255.00 | 296.67 | 1105.44 | 24.70 | 275.83 | 281.83 |
December | 319.00 | 0.63 | 0.62 | 01-DEC-07:19 | 4189.21 | 33.53 | 296.83 | 285.83 | 1145.23 | 26.08 | 269.00 | 275.17 |
Annual Sum or Average | 4323.33 | 0.64 | 1949.67 | 21.19 | 1044.17 | 3791.00 | 795.73 | 20.96 | 1525.00 | 3404.67 | ||
Minimum of Months | 308.33 | 0.63 | 0.62 | 966.95 | 16.32 | 0.00 | 273.33 | 540.87 | 19.03 | 0.00 | 243.50 | |
Maximum of Months | 405.33 | 0.65 | 0.62 | 4211.45 | 34.00 | 310.83 | 346.50 | 1145.23 | 26.08 | 275.83 | 301.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.65 | 0.62 | 01-JAN-07:49 | 1457.43 | 19.05 | 88.50 | 268.50 | 789.15 | 22.30 | 80.83 | 230.33 |
February | 308.33 | 0.64 | 0.62 | 01-FEB-07:40 | 1622.25 | 20.77 | 102.50 | 259.33 | 691.29 | 20.55 | 47.17 | 223.00 |
March | 357.50 | 0.64 | 0.62 | 01-MAR-07:49 | 1501.65 | 18.52 | 83.83 | 303.83 | 771.84 | 21.16 | 66.00 | 264.83 |
April | 375.00 | 0.65 | 0.62 | 01-APR-06:00 | 1777.57 | 19.77 | 109.33 | 316.67 | 905.34 | 21.18 | 79.83 | 277.83 |
May | 405.33 | 0.64 | 0.62 | 01-MAY-06:10 | 2012.23 | 19.63 | 118.83 | 354.67 | 838.71 | 19.84 | 56.83 | 312.50 |
June | 403.50 | 0.64 | 0.62 | 01-JUN-05:00 | 1929.52 | 19.34 | 114.33 | 347.50 | 827.35 | 19.81 | 54.50 | 310.33 |
July | 405.00 | 0.64 | 0.62 | 01-JUL-06:19 | 1818.12 | 19.29 | 114.17 | 345.83 | 792.69 | 19.62 | 52.50 | 306.83 |
August | 395.83 | 0.65 | 0.62 | 01-AUG-06:19 | 1868.69 | 19.69 | 111.50 | 338.67 | 827.94 | 20.17 | 56.17 | 304.00 |
September | 358.83 | 0.64 | 0.62 | 01-SEP-06:49 | 1832.44 | 18.74 | 85.00 | 308.67 | 959.89 | 22.15 | 77.50 | 280.67 |
October | 351.17 | 0.64 | 0.62 | 01-OCT-06:49 | 1709.60 | 19.13 | 87.83 | 301.83 | 894.26 | 21.94 | 74.00 | 269.00 |
November | 318.83 | 0.64 | 0.62 | 01-NOV-06:49 | 1483.55 | 19.82 | 84.33 | 273.50 | 759.90 | 21.21 | 54.33 | 235.50 |
December | 319.00 | 0.64 | 0.62 | 01-DEC-07:10 | 1218.58 | 19.33 | 81.33 | 264.17 | 614.75 | 20.69 | 50.83 | 219.00 |
Annual Sum or Average | 4323.33 | 0.64 | 1704.04 | 19.41 | 1181.50 | 3683.17 | 810.60 | 20.83 | 750.50 | 3233.83 | ||
Minimum of Months | 308.33 | 0.64 | 0.62 | 1218.58 | 18.52 | 81.33 | 259.33 | 614.75 | 19.62 | 47.17 | 219.00 | |
Maximum of Months | 405.33 | 0.65 | 0.62 | 2012.23 | 20.77 | 118.83 | 354.67 | 959.89 | 22.30 | 80.83 | 312.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.66 | 0.62 | 01-JAN-08:20 | 565.07 | 14.29 | 0.00 | 254.67 | 326.88 | 17.00 | 0.00 | 164.00 |
February | 308.33 | 0.65 | 0.62 | 01-FEB-08:09 | 642.98 | 15.13 | 0.00 | 250.67 | 370.70 | 17.84 | 0.00 | 184.83 |
March | 357.50 | 0.64 | 0.62 | 01-MAR-07:00 | 751.38 | 15.81 | 0.00 | 304.33 | 426.66 | 18.46 | 0.00 | 249.00 |
April | 375.00 | 0.65 | 0.62 | 01-APR-07:10 | 862.33 | 16.16 | 0.00 | 324.50 | 483.06 | 18.73 | 0.00 | 283.67 |
May | 405.33 | 0.64 | 0.62 | 01-MAY-06:19 | 1018.69 | 17.19 | 2.83 | 367.50 | 562.90 | 19.82 | 13.67 | 330.83 |
June | 403.50 | 0.63 | 0.62 | 01-JUN-06:10 | 1128.57 | 20.47 | 76.50 | 364.67 | 615.41 | 21.49 | 109.00 | 334.83 |
July | 405.00 | 0.64 | 0.62 | 01-JUL-06:40 | 1089.41 | 16.89 | 0.00 | 356.33 | 595.90 | 20.89 | 82.67 | 326.00 |
August | 395.83 | 0.64 | 0.62 | 01-AUG-06:40 | 984.66 | 16.84 | 0.00 | 348.17 | 551.34 | 19.51 | 6.83 | 312.33 |
September | 358.83 | 0.64 | 0.62 | 01-SEP-06:00 | 856.22 | 16.49 | 0.00 | 316.00 | 491.37 | 19.16 | 0.00 | 272.00 |
October | 351.17 | 0.65 | 0.62 | 01-OCT-06:00 | 706.09 | 15.57 | 0.00 | 296.33 | 415.11 | 18.29 | 0.00 | 242.00 |
November | 318.83 | 0.65 | 0.62 | 01-NOV-07:30 | 610.99 | 15.18 | 0.00 | 257.67 | 360.77 | 17.97 | 0.00 | 186.67 |
December | 319.00 | 0.65 | 0.62 | 01-DEC-07:00 | 547.65 | 14.36 | 0.00 | 244.33 | 317.59 | 17.12 | 0.00 | 138.50 |
Annual Sum or Average | 4323.33 | 0.64 | 832.19 | 16.32 | 79.33 | 3685.17 | 469.25 | 18.97 | 212.17 | 3024.67 | ||
Minimum of Months | 308.33 | 0.63 | 0.62 | 547.65 | 14.29 | 0.00 | 244.33 | 317.59 | 17.00 | 0.00 | 138.50 | |
Maximum of Months | 405.33 | 0.66 | 0.62 | 1128.57 | 20.47 | 76.50 | 367.50 | 615.41 | 21.49 | 109.00 | 334.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.65 | 0.62 | 01-JAN-08:39 | 1419.87 | 18.91 | 87.33 | 270.17 | 756.80 | 21.91 | 77.17 | 229.50 |
February | 308.33 | 0.64 | 0.62 | 01-FEB-08:20 | 1413.14 | 19.14 | 76.33 | 258.83 | 712.47 | 20.45 | 48.33 | 219.67 |
March | 357.50 | 0.64 | 0.62 | 01-MAR-08:09 | 1615.22 | 18.78 | 85.83 | 307.00 | 813.31 | 20.20 | 55.17 | 264.00 |
April | 375.00 | 0.65 | 0.62 | 01-APR-07:40 | 1623.57 | 16.07 | 55.00 | 320.17 | 851.54 | 17.00 | 0.00 | 282.83 |
May | 405.33 | 0.64 | 0.62 | 01-MAY-06:00 | 1703.76 | 13.60 | 0.00 | 347.00 | 888.18 | 17.29 | 0.00 | 309.33 |
June | 403.50 | 0.64 | 0.62 | 01-JUN-06:49 | 1837.12 | 13.78 | 0.00 | 344.00 | 806.70 | 17.50 | 0.00 | 307.00 |
July | 405.00 | 0.65 | 0.62 | 01-JUL-06:00 | 1756.26 | 13.83 | 3.67 | 345.33 | 789.44 | 17.29 | 0.00 | 305.67 |
August | 395.83 | 0.65 | 0.62 | 01-AUG-06:00 | 1771.34 | 16.53 | 59.83 | 338.83 | 922.79 | 17.69 | 5.50 | 304.67 |
September | 358.83 | 0.64 | 0.62 | 01-SEP-07:10 | 1715.02 | 18.89 | 84.33 | 314.50 | 883.33 | 20.61 | 57.50 | 279.50 |
October | 351.17 | 0.64 | 0.62 | 01-OCT-07:19 | 1764.37 | 19.03 | 87.83 | 298.83 | 931.82 | 22.26 | 79.33 | 269.17 |
November | 318.83 | 0.64 | 0.62 | 01-NOV-07:40 | 1542.22 | 19.77 | 85.00 | 273.17 | 804.95 | 22.22 | 67.33 | 239.50 |
December | 319.00 | 0.64 | 0.62 | 01-DEC-08:09 | 1347.73 | 19.34 | 87.33 | 265.00 | 693.38 | 20.91 | 59.67 | 221.33 |
Annual Sum or Average | 4323.33 | 0.64 | 1638.64 | 17.10 | 712.50 | 3682.83 | 825.35 | 19.44 | 450.00 | 3232.17 | ||
Minimum of Months | 308.33 | 0.64 | 0.62 | 1347.73 | 13.60 | 0.00 | 258.83 | 693.38 | 17.00 | 0.00 | 219.67 | |
Maximum of Months | 405.33 | 0.65 | 0.62 | 1837.12 | 19.77 | 87.83 | 347.00 | 931.82 | 22.26 | 79.33 | 309.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.64 | 0.62 | 01-JAN-07:49 | 4104.22 | 33.76 | 310.17 | 291.17 | 999.50 | 22.57 | 91.67 | 279.17 |
February | 308.33 | 0.64 | 0.62 | 01-FEB-07:40 | 2022.82 | 22.38 | 141.33 | 271.50 | 886.04 | 17.66 | 0.00 | 240.00 |
March | 357.50 | 0.64 | 0.62 | 01-MAR-07:49 | 1467.91 | 13.84 | 5.00 | 309.83 | 757.13 | 17.48 | 0.00 | 272.33 |
April | 375.00 | 0.65 | 0.62 | 01-APR-07:10 | 1144.47 | 13.06 | 0.00 | 319.50 | 604.77 | 16.79 | 0.00 | 277.50 |
May | 405.33 | 0.65 | 0.62 | 01-MAY-06:40 | 968.82 | 13.04 | 0.00 | 344.83 | 532.14 | 16.86 | 0.00 | 296.33 |
June | 403.50 | 0.65 | 0.62 | 01-JUN-06:40 | 925.17 | 12.86 | 0.00 | 339.33 | 517.60 | 16.75 | 0.00 | 290.50 |
July | 405.00 | 0.65 | 0.62 | 01-JUL-06:49 | 974.10 | 12.74 | 0.00 | 341.83 | 537.65 | 16.56 | 0.00 | 296.00 |
August | 395.83 | 0.65 | 0.62 | 01-AUG-06:49 | 1146.35 | 13.34 | 0.00 | 339.33 | 615.17 | 17.13 | 0.00 | 296.83 |
September | 358.83 | 0.64 | 0.62 | 01-SEP-06:00 | 1437.54 | 14.01 | 0.00 | 315.83 | 755.37 | 17.86 | 0.00 | 280.17 |
October | 351.17 | 0.64 | 0.62 | 01-OCT-06:00 | 1946.19 | 16.04 | 32.83 | 315.67 | 909.38 | 18.71 | 10.67 | 283.33 |
November | 318.83 | 0.63 | 0.62 | 01-NOV-06:00 | 3399.79 | 29.75 | 247.33 | 293.50 | 1032.07 | 22.32 | 76.67 | 279.67 |
December | 319.00 | 0.63 | 0.62 | 01-DEC-07:19 | 4076.98 | 32.94 | 293.50 | 284.67 | 1074.38 | 23.93 | 113.33 | 273.17 |
Annual Sum or Average | 4323.33 | 0.64 | 1875.78 | 18.34 | 1030.17 | 3767.00 | 750.23 | 18.54 | 292.33 | 3365.00 | ||
Minimum of Months | 308.33 | 0.63 | 0.62 | 925.17 | 12.74 | 0.00 | 271.50 | 517.60 | 16.56 | 0.00 | 240.00 | |
Maximum of Months | 405.33 | 0.65 | 0.62 | 4104.22 | 33.76 | 310.17 | 344.83 | 1074.38 | 23.93 | 113.33 | 296.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.65 | 0.62 | 01-JAN-07:49 | 1411.22 | 18.60 | 88.50 | 266.33 | 756.93 | 22.08 | 80.83 | 225.50 |
February | 308.33 | 0.64 | 0.62 | 01-FEB-07:40 | 1573.03 | 20.37 | 102.50 | 257.83 | 657.91 | 20.33 | 47.17 | 218.33 |
March | 357.50 | 0.64 | 0.62 | 01-MAR-07:49 | 1454.04 | 18.09 | 83.83 | 302.33 | 723.84 | 19.83 | 52.50 | 258.33 |
April | 375.00 | 0.65 | 0.62 | 01-APR-06:00 | 1680.27 | 17.28 | 84.33 | 313.67 | 866.83 | 21.01 | 79.83 | 273.67 |
May | 405.33 | 0.64 | 0.62 | 01-MAY-06:10 | 1952.27 | 19.26 | 118.83 | 352.33 | 797.27 | 19.68 | 56.83 | 307.83 |
June | 403.50 | 0.64 | 0.62 | 01-JUN-05:00 | 1878.16 | 18.96 | 114.33 | 345.50 | 787.10 | 19.65 | 54.50 | 306.67 |
July | 405.00 | 0.65 | 0.62 | 01-JUL-06:19 | 1763.76 | 18.92 | 114.17 | 343.33 | 753.61 | 19.46 | 52.50 | 303.17 |
August | 395.83 | 0.65 | 0.62 | 01-AUG-06:19 | 1801.94 | 19.32 | 111.33 | 336.83 | 787.04 | 20.01 | 56.33 | 301.17 |
September | 358.83 | 0.64 | 0.62 | 01-SEP-06:49 | 1776.74 | 18.32 | 85.00 | 306.67 | 918.47 | 21.97 | 77.50 | 276.83 |
October | 351.17 | 0.65 | 0.62 | 01-OCT-06:49 | 1652.29 | 18.71 | 87.83 | 299.33 | 854.58 | 21.74 | 74.00 | 264.83 |
November | 318.83 | 0.64 | 0.62 | 01-NOV-06:49 | 1431.74 | 19.38 | 84.33 | 272.00 | 723.89 | 20.97 | 54.33 | 230.50 |
December | 319.00 | 0.65 | 0.62 | 01-DEC-07:10 | 1176.10 | 18.88 | 81.17 | 261.83 | 585.45 | 20.44 | 50.83 | 214.17 |
Annual Sum or Average | 4323.33 | 0.64 | 1646.83 | 18.82 | 1156.17 | 3658.00 | 771.96 | 20.55 | 737.17 | 3181.00 | ||
Minimum of Months | 308.33 | 0.64 | 0.62 | 1176.10 | 17.28 | 81.17 | 257.83 | 585.45 | 19.46 | 47.17 | 214.17 | |
Maximum of Months | 405.33 | 0.65 | 0.62 | 1952.27 | 20.37 | 118.83 | 352.33 | 918.47 | 22.08 | 80.83 | 307.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.66 | 0.62 | 01-JAN-08:30 | 541.02 | 10.79 | 0.00 | 250.33 | 313.99 | 14.68 | 0.00 | 146.00 |
February | 308.33 | 0.65 | 0.62 | 01-FEB-08:09 | 615.85 | 11.53 | 0.00 | 248.50 | 356.13 | 15.48 | 0.00 | 176.67 |
March | 357.50 | 0.64 | 0.62 | 01-MAR-07:00 | 719.96 | 12.27 | 0.00 | 300.67 | 409.65 | 16.14 | 0.00 | 243.00 |
April | 375.00 | 0.65 | 0.62 | 01-APR-07:10 | 825.94 | 12.75 | 0.00 | 322.67 | 463.09 | 16.52 | 0.00 | 278.67 |
May | 405.33 | 0.64 | 0.62 | 01-MAY-06:30 | 974.99 | 13.67 | 2.83 | 365.50 | 538.41 | 17.54 | 1.17 | 326.00 |
June | 403.50 | 0.64 | 0.62 | 01-JUN-06:10 | 1079.31 | 17.71 | 76.17 | 361.67 | 587.34 | 19.30 | 34.17 | 331.83 |
July | 405.00 | 0.64 | 0.62 | 01-JUL-06:40 | 1042.10 | 13.23 | 0.00 | 355.33 | 569.17 | 18.62 | 27.50 | 321.33 |
August | 395.83 | 0.64 | 0.62 | 01-AUG-06:40 | 941.87 | 13.38 | 0.00 | 346.67 | 527.64 | 17.25 | 0.00 | 308.50 |
September | 358.83 | 0.64 | 0.62 | 01-SEP-06:00 | 819.37 | 13.20 | 0.00 | 313.50 | 471.31 | 17.04 | 0.00 | 266.83 |
October | 351.17 | 0.65 | 0.62 | 01-OCT-07:10 | 675.71 | 12.28 | 0.00 | 294.17 | 398.81 | 16.19 | 0.00 | 236.33 |
November | 318.83 | 0.65 | 0.62 | 01-NOV-07:30 | 584.49 | 11.72 | 0.00 | 254.00 | 346.60 | 15.76 | 0.00 | 175.67 |
December | 319.00 | 0.66 | 0.62 | 01-DEC-07:00 | 524.07 | 10.74 | 0.00 | 240.67 | 304.94 | 14.73 | 0.00 | 123.17 |
Annual Sum or Average | 4323.33 | 0.65 | 796.43 | 12.90 | 79.00 | 3653.67 | 449.54 | 16.72 | 62.83 | 2934.00 | ||
Minimum of Months | 308.33 | 0.64 | 0.62 | 524.07 | 10.74 | 0.00 | 240.67 | 304.94 | 14.68 | 0.00 | 123.17 | |
Maximum of Months | 405.33 | 0.66 | 0.62 | 1079.31 | 17.71 | 76.17 | 365.50 | 587.34 | 19.30 | 34.17 | 331.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.65 | 0.62 | 01-JAN-08:39 | 1374.25 | 18.55 | 87.33 | 267.00 | 725.09 | 21.81 | 77.17 | 223.67 |
February | 308.33 | 0.64 | 0.62 | 01-FEB-08:20 | 1362.31 | 18.77 | 76.33 | 256.67 | 677.89 | 20.34 | 48.50 | 215.67 |
March | 357.50 | 0.64 | 0.62 | 01-MAR-08:09 | 1563.30 | 18.41 | 85.83 | 304.83 | 774.15 | 20.06 | 55.17 | 259.50 |
April | 375.00 | 0.65 | 0.62 | 01-APR-07:40 | 1566.42 | 15.66 | 55.00 | 319.17 | 812.61 | 16.82 | 0.00 | 278.83 |
May | 405.33 | 0.65 | 0.62 | 01-MAY-06:00 | 1642.38 | 13.12 | 0.00 | 344.50 | 848.82 | 17.09 | 0.00 | 305.83 |
June | 403.50 | 0.64 | 0.62 | 01-JUN-06:49 | 1783.31 | 13.30 | 0.00 | 341.33 | 765.86 | 17.29 | 0.00 | 304.00 |
July | 405.00 | 0.65 | 0.62 | 01-JUL-06:00 | 1699.19 | 13.35 | 3.67 | 344.17 | 750.49 | 17.08 | 0.00 | 301.67 |
August | 395.83 | 0.65 | 0.62 | 01-AUG-07:10 | 1704.11 | 16.11 | 59.83 | 336.33 | 881.77 | 17.51 | 5.50 | 302.33 |
September | 358.83 | 0.64 | 0.62 | 01-SEP-07:19 | 1659.42 | 18.52 | 84.33 | 311.67 | 841.37 | 20.47 | 57.50 | 274.67 |
October | 351.17 | 0.65 | 0.62 | 01-OCT-07:19 | 1707.68 | 18.66 | 87.83 | 296.50 | 889.06 | 21.95 | 76.83 | 264.33 |
November | 318.83 | 0.64 | 0.62 | 01-NOV-07:40 | 1490.60 | 19.40 | 85.00 | 271.17 | 752.25 | 21.04 | 55.00 | 233.33 |
December | 319.00 | 0.65 | 0.62 | 01-DEC-08:09 | 1302.14 | 18.97 | 87.33 | 261.83 | 661.65 | 20.79 | 59.67 | 216.00 |
Annual Sum or Average | 4323.33 | 0.65 | 1583.67 | 16.70 | 712.50 | 3655.17 | 785.79 | 19.19 | 435.33 | 3179.83 | ||
Minimum of Months | 308.33 | 0.64 | 0.62 | 1302.14 | 13.12 | 0.00 | 256.67 | 661.65 | 16.82 | 0.00 | 215.67 | |
Maximum of Months | 405.33 | 0.65 | 0.62 | 1783.31 | 19.40 | 87.83 | 344.50 | 889.06 | 21.95 | 77.17 | 305.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.64 | 0.62 | 01-JAN-07:49 | 4104.17 | 33.76 | 310.17 | 291.17 | 999.42 | 22.57 | 91.67 | 279.17 |
February | 308.33 | 0.64 | 0.62 | 01-FEB-07:40 | 2022.73 | 22.39 | 141.33 | 271.50 | 885.97 | 17.66 | 0.00 | 240.00 |
March | 357.50 | 0.64 | 0.62 | 01-MAR-07:49 | 1467.83 | 13.84 | 5.00 | 309.83 | 757.07 | 17.48 | 0.00 | 272.33 |
April | 375.00 | 0.65 | 0.62 | 01-APR-07:10 | 1144.41 | 13.07 | 0.00 | 319.50 | 604.72 | 16.80 | 0.00 | 277.50 |
May | 405.33 | 0.65 | 0.62 | 01-MAY-06:40 | 968.78 | 13.04 | 0.00 | 344.83 | 532.10 | 16.86 | 0.00 | 296.33 |
June | 403.50 | 0.65 | 0.62 | 01-JUN-06:40 | 925.14 | 12.86 | 0.00 | 339.33 | 517.57 | 16.75 | 0.00 | 290.50 |
July | 405.00 | 0.65 | 0.62 | 01-JUL-06:49 | 974.06 | 12.74 | 0.00 | 341.83 | 537.61 | 16.56 | 0.00 | 296.00 |
August | 395.83 | 0.65 | 0.62 | 01-AUG-06:49 | 1146.30 | 13.34 | 0.00 | 339.33 | 615.12 | 17.13 | 0.00 | 296.83 |
September | 358.83 | 0.64 | 0.62 | 01-SEP-06:00 | 1437.47 | 14.02 | 0.00 | 315.83 | 755.31 | 17.86 | 0.00 | 280.17 |
October | 351.17 | 0.64 | 0.62 | 01-OCT-06:00 | 1946.11 | 16.04 | 32.83 | 315.67 | 909.30 | 18.71 | 10.67 | 283.33 |
November | 318.83 | 0.63 | 0.62 | 01-NOV-06:00 | 3399.73 | 29.75 | 247.33 | 293.50 | 1031.98 | 22.32 | 76.67 | 279.67 |
December | 319.00 | 0.63 | 0.62 | 01-DEC-07:19 | 4076.94 | 32.94 | 293.50 | 284.67 | 1074.30 | 23.94 | 113.33 | 273.17 |
Annual Sum or Average | 4323.33 | 0.64 | 1875.72 | 18.34 | 1030.17 | 3767.00 | 750.17 | 18.54 | 292.33 | 3365.00 | ||
Minimum of Months | 308.33 | 0.63 | 0.62 | 925.14 | 12.74 | 0.00 | 271.50 | 517.57 | 16.56 | 0.00 | 240.00 | |
Maximum of Months | 405.33 | 0.65 | 0.62 | 4104.17 | 33.76 | 310.17 | 344.83 | 1074.30 | 23.94 | 113.33 | 296.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.65 | 0.62 | 01-JAN-07:49 | 1411.20 | 18.60 | 88.50 | 266.33 | 756.89 | 22.08 | 80.83 | 225.50 |
February | 308.33 | 0.64 | 0.62 | 01-FEB-07:40 | 1573.00 | 20.37 | 102.50 | 257.83 | 657.86 | 20.33 | 47.17 | 218.33 |
March | 357.50 | 0.64 | 0.62 | 01-MAR-07:49 | 1454.00 | 18.10 | 83.83 | 302.33 | 723.79 | 19.83 | 52.50 | 258.33 |
April | 375.00 | 0.65 | 0.62 | 01-APR-06:00 | 1680.22 | 17.28 | 84.33 | 313.67 | 866.78 | 21.01 | 79.83 | 273.67 |
May | 405.33 | 0.64 | 0.62 | 01-MAY-06:10 | 1952.23 | 19.26 | 118.83 | 352.33 | 797.22 | 19.68 | 56.83 | 307.83 |
June | 403.50 | 0.64 | 0.62 | 01-JUN-05:00 | 1878.12 | 18.97 | 114.33 | 345.50 | 787.05 | 19.66 | 54.50 | 306.67 |
July | 405.00 | 0.65 | 0.62 | 01-JUL-06:19 | 1763.72 | 18.92 | 114.17 | 343.33 | 753.56 | 19.46 | 52.50 | 303.17 |
August | 395.83 | 0.65 | 0.62 | 01-AUG-06:19 | 1801.89 | 19.32 | 111.33 | 336.83 | 786.99 | 20.01 | 56.33 | 301.17 |
September | 358.83 | 0.64 | 0.62 | 01-SEP-06:49 | 1776.70 | 18.32 | 85.00 | 306.67 | 918.42 | 21.97 | 77.50 | 276.83 |
October | 351.17 | 0.65 | 0.62 | 01-OCT-06:49 | 1652.26 | 18.71 | 87.83 | 299.33 | 854.53 | 21.74 | 74.00 | 264.83 |
November | 318.83 | 0.64 | 0.62 | 01-NOV-06:49 | 1431.72 | 19.38 | 84.33 | 272.00 | 723.85 | 20.97 | 54.33 | 230.50 |
December | 319.00 | 0.65 | 0.62 | 01-DEC-07:10 | 1176.07 | 18.89 | 81.17 | 261.83 | 585.41 | 20.44 | 50.83 | 214.17 |
Annual Sum or Average | 4323.33 | 0.64 | 1646.79 | 18.83 | 1156.17 | 3658.00 | 771.91 | 20.55 | 737.17 | 3181.00 | ||
Minimum of Months | 308.33 | 0.64 | 0.62 | 1176.07 | 17.28 | 81.17 | 257.83 | 585.41 | 19.46 | 47.17 | 214.17 | |
Maximum of Months | 405.33 | 0.65 | 0.62 | 1952.23 | 20.37 | 118.83 | 352.33 | 918.42 | 22.08 | 80.83 | 307.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.66 | 0.62 | 01-JAN-08:30 | 541.01 | 10.79 | 0.00 | 250.33 | 313.97 | 14.68 | 0.00 | 146.00 |
February | 308.33 | 0.65 | 0.62 | 01-FEB-08:09 | 615.84 | 11.53 | 0.00 | 248.50 | 356.11 | 15.48 | 0.00 | 176.67 |
March | 357.50 | 0.64 | 0.62 | 01-MAR-07:00 | 719.94 | 12.28 | 0.00 | 300.67 | 409.62 | 16.14 | 0.00 | 243.00 |
April | 375.00 | 0.65 | 0.62 | 01-APR-07:10 | 825.92 | 12.75 | 0.00 | 322.67 | 463.06 | 16.52 | 0.00 | 278.67 |
May | 405.33 | 0.64 | 0.62 | 01-MAY-06:30 | 974.95 | 13.68 | 2.83 | 365.50 | 538.37 | 17.54 | 1.17 | 326.00 |
June | 403.50 | 0.64 | 0.62 | 01-JUN-06:10 | 1079.27 | 17.71 | 76.17 | 361.67 | 587.30 | 19.30 | 34.17 | 331.83 |
July | 405.00 | 0.64 | 0.62 | 01-JUL-06:40 | 1042.06 | 13.23 | 0.00 | 355.33 | 569.13 | 18.63 | 27.50 | 321.33 |
August | 395.83 | 0.64 | 0.62 | 01-AUG-06:40 | 941.84 | 13.38 | 0.00 | 346.67 | 527.61 | 17.25 | 0.00 | 308.50 |
September | 358.83 | 0.64 | 0.62 | 01-SEP-06:00 | 819.35 | 13.20 | 0.00 | 313.50 | 471.28 | 17.04 | 0.00 | 266.83 |
October | 351.17 | 0.65 | 0.62 | 01-OCT-07:10 | 675.70 | 12.29 | 0.00 | 294.17 | 398.78 | 16.19 | 0.00 | 236.33 |
November | 318.83 | 0.65 | 0.62 | 01-NOV-07:30 | 584.48 | 11.73 | 0.00 | 254.00 | 346.58 | 15.76 | 0.00 | 175.67 |
December | 319.00 | 0.66 | 0.62 | 01-DEC-07:00 | 524.06 | 10.74 | 0.00 | 240.67 | 304.92 | 14.73 | 0.00 | 123.17 |
Annual Sum or Average | 4323.33 | 0.65 | 796.41 | 12.91 | 79.00 | 3653.67 | 449.51 | 16.72 | 62.83 | 2934.00 | ||
Minimum of Months | 308.33 | 0.64 | 0.62 | 524.06 | 10.74 | 0.00 | 240.67 | 304.92 | 14.68 | 0.00 | 123.17 | |
Maximum of Months | 405.33 | 0.66 | 0.62 | 1079.27 | 17.71 | 76.17 | 365.50 | 587.30 | 19.30 | 34.17 | 331.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.65 | 0.62 | 01-JAN-08:39 | 1374.22 | 18.55 | 87.33 | 267.00 | 725.05 | 21.81 | 77.17 | 223.67 |
February | 308.33 | 0.64 | 0.62 | 01-FEB-08:20 | 1362.27 | 18.78 | 76.33 | 256.67 | 677.84 | 20.34 | 48.50 | 215.67 |
March | 357.50 | 0.64 | 0.62 | 01-MAR-08:09 | 1563.26 | 18.41 | 85.83 | 304.83 | 774.10 | 20.06 | 55.17 | 259.50 |
April | 375.00 | 0.65 | 0.62 | 01-APR-07:40 | 1566.37 | 15.66 | 55.00 | 319.17 | 812.56 | 16.82 | 0.00 | 278.83 |
May | 405.33 | 0.65 | 0.62 | 01-MAY-06:00 | 1642.34 | 13.12 | 0.00 | 344.50 | 848.77 | 17.09 | 0.00 | 305.83 |
June | 403.50 | 0.64 | 0.62 | 01-JUN-06:49 | 1783.27 | 13.30 | 0.00 | 341.33 | 765.81 | 17.29 | 0.00 | 304.00 |
July | 405.00 | 0.65 | 0.62 | 01-JUL-06:00 | 1699.14 | 13.36 | 3.67 | 344.17 | 750.44 | 17.08 | 0.00 | 301.67 |
August | 395.83 | 0.65 | 0.62 | 01-AUG-07:10 | 1704.07 | 16.11 | 59.83 | 336.33 | 881.72 | 17.51 | 5.50 | 302.33 |
September | 358.83 | 0.64 | 0.62 | 01-SEP-07:19 | 1659.38 | 18.52 | 84.33 | 311.67 | 841.31 | 20.47 | 57.50 | 274.67 |
October | 351.17 | 0.65 | 0.62 | 01-OCT-07:19 | 1707.65 | 18.66 | 87.83 | 296.50 | 889.01 | 21.95 | 76.83 | 264.33 |
November | 318.83 | 0.64 | 0.62 | 01-NOV-07:40 | 1490.58 | 19.41 | 85.00 | 271.17 | 752.20 | 21.04 | 55.00 | 233.33 |
December | 319.00 | 0.65 | 0.62 | 01-DEC-08:09 | 1302.13 | 18.97 | 87.33 | 261.83 | 661.61 | 20.79 | 59.67 | 216.00 |
Annual Sum or Average | 4323.33 | 0.65 | 1583.63 | 16.70 | 712.50 | 3655.17 | 785.74 | 19.19 | 435.33 | 3179.83 | ||
Minimum of Months | 308.33 | 0.64 | 0.62 | 1302.13 | 13.12 | 0.00 | 256.67 | 661.61 | 16.82 | 0.00 | 215.67 | |
Maximum of Months | 405.33 | 0.65 | 0.62 | 1783.27 | 19.41 | 87.83 | 344.50 | 889.01 | 21.95 | 77.17 | 305.83 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.204043E+09 | 5796.81 | 02-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122781E+09 | 5796.81 | 01-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 44250507.78 | 5796.81 | 07-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 741884.20 | 1399.97 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 37848431.23 | 5796.81 | 18-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.409665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.204043E+09 | 5796.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 235479.13 | 1066.81 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 235479.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 235479.13 | 1066.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 6458.83 | 43.06 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6458.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6458.83 | 43.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3869229.50 | 1891.44 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 106983.85 | 57.86 | 30-DEC-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3976213.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3869229.50 | 1891.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.440946E+11 | 0.380820E+11 | 66592.69 | 30-JAN-05:03 | 52442.34 | 0.00 |
February | 0.00 | 0.00 | 0.461085E+11 | 0.390264E+11 | 83299.31 | 06-FEB-05:03 | 56825.59 | 0.00 |
March | 0.00 | 0.00 | 0.609332E+11 | 0.532815E+11 | 84796.24 | 28-MAR-11:40 | 58353.25 | 0.00 |
April | 0.00 | 0.00 | 0.716373E+11 | 0.609734E+11 | 92650.58 | 17-APR-04:02 | 74486.17 | 0.00 |
May | 0.00 | 0.00 | 0.106072E+12 | 0.876381E+11 | 146509.67 | 24-MAY-04:03 | 76614.41 | 0.00 |
June | 0.00 | 0.00 | 0.127608E+12 | 0.938953E+11 | 150975.24 | 14-JUN-04:02 | 80463.73 | 0.00 |
July | 0.00 | 0.00 | 0.153876E+12 | 0.103488E+12 | 148358.61 | 06-JUL-04:02 | 84988.69 | 0.00 |
August | 0.00 | 0.00 | 0.171297E+12 | 0.113094E+12 | 146957.27 | 08-AUG-06:03 | 83267.86 | 0.00 |
September | 0.00 | 0.00 | 0.138076E+12 | 0.938285E+11 | 149703.82 | 23-SEP-04:03 | 79323.61 | 0.00 |
October | 0.00 | 0.00 | 0.112514E+12 | 0.845700E+11 | 147724.49 | 18-OCT-04:02 | 85679.11 | 0.00 |
November | 0.00 | 0.00 | 0.824651E+11 | 0.662236E+11 | 132175.20 | 03-NOV-04:03 | 77252.66 | 0.00 |
December | 0.00 | 0.00 | 0.546881E+11 | 0.454073E+11 | 94439.09 | 11-DEC-05:02 | 66515.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.116937E+13 | 0.879508E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.440946E+11 | 0.380820E+11 | 66592.69 | 52442.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.171297E+12 | 0.113094E+12 | 150975.24 | 85679.11 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.330536E+11 | 0.269125E+11 | 46122.82 | 30-JAN-14:00 | 33271.06 | 0.00 |
February | 0.00 | 0.00 | 0.366854E+11 | 0.297786E+11 | 74283.41 | 09-FEB-06:03 | 46526.15 | 0.00 |
March | 0.00 | 0.00 | 0.507090E+11 | 0.433534E+11 | 66832.31 | 27-MAR-11:00 | 66832.31 | 0.00 |
April | 0.00 | 0.00 | 0.625153E+11 | 0.526090E+11 | 95225.64 | 17-APR-04:02 | 74911.99 | 0.00 |
May | 0.00 | 0.00 | 0.940214E+11 | 0.775725E+11 | 135005.82 | 24-MAY-05:03 | 68980.96 | 0.00 |
June | 0.00 | 0.00 | 0.113748E+12 | 0.827555E+11 | 138417.62 | 14-JUN-04:02 | 68644.13 | 0.00 |
July | 0.00 | 0.00 | 0.136385E+12 | 0.916124E+11 | 137145.42 | 06-JUL-04:02 | 71785.24 | 0.00 |
August | 0.00 | 0.00 | 0.146631E+12 | 0.974283E+11 | 136559.90 | 26-AUG-04:02 | 72104.57 | 0.00 |
September | 0.00 | 0.00 | 0.115804E+12 | 0.786817E+11 | 136997.52 | 28-SEP-04:02 | 70645.33 | 0.00 |
October | 0.00 | 0.00 | 0.910501E+11 | 0.684253E+11 | 134513.57 | 02-OCT-04:03 | 77017.09 | 0.00 |
November | 0.00 | 0.00 | 0.639420E+11 | 0.502745E+11 | 103568.99 | 03-NOV-05:03 | 57735.90 | 0.00 |
December | 0.00 | 0.00 | 0.415914E+11 | 0.326664E+11 | 67424.21 | 11-DEC-06:03 | 43584.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.986136E+12 | 0.732070E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.330536E+11 | 0.269125E+11 | 46122.82 | 33271.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.146631E+12 | 0.974283E+11 | 138417.62 | 77017.09 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.329229E+11 | 0.257455E+11 | 46341.48 | 30-JAN-14:30 | 33288.77 | 0.00 |
February | 0.00 | 0.00 | 0.377334E+11 | 0.300054E+11 | 70615.07 | 07-FEB-15:30 | 54550.46 | 0.00 |
March | 0.00 | 0.00 | 0.533822E+11 | 0.451884E+11 | 76986.77 | 27-MAR-13:10 | 76986.77 | 0.00 |
April | 0.00 | 0.00 | 0.675436E+11 | 0.569157E+11 | 98527.86 | 30-APR-12:43 | 91153.94 | 0.00 |
May | 0.00 | 0.00 | 0.103794E+12 | 0.865941E+11 | 155111.71 | 31-MAY-04:02 | 91703.30 | 0.00 |
June | 0.00 | 0.00 | 0.125562E+12 | 0.933834E+11 | 161355.13 | 14-JUN-04:02 | 79177.66 | 0.00 |
July | 0.00 | 0.00 | 0.152590E+12 | 0.105515E+12 | 159045.44 | 06-JUL-04:02 | 85753.29 | 0.00 |
August | 0.00 | 0.00 | 0.162567E+12 | 0.111263E+12 | 158234.08 | 26-AUG-04:02 | 87117.19 | 0.00 |
September | 0.00 | 0.00 | 0.125863E+12 | 0.876139E+11 | 159890.66 | 28-SEP-04:02 | 82825.54 | 0.00 |
October | 0.00 | 0.00 | 0.959689E+11 | 0.728603E+11 | 152482.42 | 05-OCT-04:02 | 86603.40 | 0.00 |
November | 0.00 | 0.00 | 0.652481E+11 | 0.511324E+11 | 94034.59 | 01-NOV-14:00 | 68115.91 | 0.00 |
December | 0.00 | 0.00 | 0.418164E+11 | 0.319034E+11 | 74212.55 | 11-DEC-06:03 | 44642.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.106499E+13 | 0.798120E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.329229E+11 | 0.257455E+11 | 46341.48 | 33288.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.162567E+12 | 0.111263E+12 | 161355.13 | 91703.30 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1356.70 | 4612.48 | 13-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1330.75 | 4567.87 | 01-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1326.14 | 4377.07 | 01-MAR-12:13 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1130.92 | 3948.64 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 1059.67 | 3584.79 | 02-MAY-11:15 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 1002.00 | 3261.30 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 898.25 | 3089.78 | 31-JUL-11:18 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 1019.87 | 3309.64 | 31-AUG-11:13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 1042.35 | 3656.61 | 29-SEP-11:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1151.70 | 4072.65 | 31-OCT-11:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1276.89 | 4418.02 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1300.74 | 4587.23 | 28-DEC-12:40 |
Annual Sum or Average | 0.00 | 1157.07 | ||||
Minimum of Months | 0.00 | 0.00 | 898.25 | 3089.78 | ||
Maximum of Months | 0.00 | 0.00 | 1356.70 | 4612.48 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.325721E+10 | 0.37 | 5502.86 | 23-JAN-13:10 | 1.09 |
February | 0.319961E+10 | 0.39 | 6812.69 | 06-FEB-13:10 | 1.24 |
March | 0.419029E+10 | 0.43 | 9047.12 | 27-MAR-12:09 | 1.49 |
April | 0.459577E+10 | 0.46 | 9356.18 | 24-APR-12:20 | 1.52 |
May | 0.674246E+10 | 0.57 | 11939.60 | 08-MAY-04:02 | 1.77 |
June | 0.718477E+10 | 0.62 | 11939.60 | 01-JUN-04:02 | 1.77 |
July | 0.698801E+10 | 0.62 | 11939.60 | 01-JUL-04:02 | 1.76 |
August | 0.740457E+10 | 0.66 | 11939.60 | 01-AUG-06:03 | 1.77 |
September | 0.632145E+10 | 0.59 | 11939.60 | 01-SEP-04:02 | 1.77 |
October | 0.594062E+10 | 0.55 | 11939.60 | 02-OCT-06:03 | 1.77 |
November | 0.517725E+10 | 0.49 | 11593.23 | 20-NOV-05:02 | 1.74 |
December | 0.380407E+10 | 0.40 | 6354.24 | 05-DEC-13:10 | 1.19 |
Annual Sum or Average | 0.648061E+11 | 0.51 | |||
Minimum of Months | 0.319961E+10 | 0.37 | 5502.86 | 1.09 | |
Maximum of Months | 0.740457E+10 | 0.66 | 11939.60 | 1.77 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.216609E+10 | 0.32 | 3520.93 | 23-JAN-13:30 | 0.91 |
February | 0.233982E+10 | 0.35 | 5668.34 | 06-FEB-15:10 | 1.21 |
March | 0.336229E+10 | 0.41 | 8069.41 | 02-MAR-05:03 | 1.51 |
April | 0.391727E+10 | 0.45 | 8788.06 | 17-APR-04:02 | 1.59 |
May | 0.603686E+10 | 0.58 | 10485.05 | 08-MAY-04:02 | 1.78 |
June | 0.652309E+10 | 0.63 | 10485.05 | 01-JUN-04:02 | 1.78 |
July | 0.676943E+10 | 0.65 | 10485.05 | 01-JUL-04:02 | 1.78 |
August | 0.755259E+10 | 0.69 | 10485.05 | 03-AUG-06:03 | 1.78 |
September | 0.614855E+10 | 0.60 | 10485.05 | 02-SEP-04:02 | 1.78 |
October | 0.528792E+10 | 0.53 | 10485.05 | 10-OCT-04:02 | 1.78 |
November | 0.390833E+10 | 0.44 | 9151.85 | 20-NOV-05:02 | 1.63 |
December | 0.251035E+10 | 0.35 | 4901.64 | 04-DEC-14:00 | 1.10 |
Annual Sum or Average | 0.565226E+11 | 0.50 | |||
Minimum of Months | 0.216609E+10 | 0.32 | 3520.93 | 0.91 | |
Maximum of Months | 0.755259E+10 | 0.69 | 10485.05 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.183770E+10 | 0.29 | 2815.97 | 23-JAN-14:00 | 0.72 |
February | 0.202673E+10 | 0.31 | 5140.07 | 06-FEB-15:00 | 1.00 |
March | 0.298643E+10 | 0.36 | 7281.55 | 27-MAR-14:30 | 1.24 |
April | 0.361644E+10 | 0.40 | 7359.02 | 24-APR-14:00 | 1.25 |
May | 0.577331E+10 | 0.52 | 12673.32 | 12-MAY-04:02 | 1.76 |
June | 0.632650E+10 | 0.56 | 12748.74 | 14-JUN-04:02 | 1.76 |
July | 0.677761E+10 | 0.60 | 12748.74 | 06-JUL-04:02 | 1.76 |
August | 0.746692E+10 | 0.63 | 12748.74 | 11-AUG-04:02 | 1.76 |
September | 0.589127E+10 | 0.53 | 12748.74 | 15-SEP-04:02 | 1.76 |
October | 0.483851E+10 | 0.46 | 9964.85 | 16-OCT-04:02 | 1.51 |
November | 0.331919E+10 | 0.38 | 6391.80 | 06-NOV-14:20 | 1.14 |
December | 0.210797E+10 | 0.30 | 4008.84 | 04-DEC-14:10 | 0.87 |
Annual Sum or Average | 0.529686E+11 | 0.45 | |||
Minimum of Months | 0.183770E+10 | 0.29 | 2815.97 | 0.72 | |
Maximum of Months | 0.746692E+10 | 0.63 | 12748.74 | 1.76 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:10 | 0.22 | 0.22 | 57.19 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:03 | 0.22 | 0.22 | 57.22 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:03 | 0.22 | 0.22 | 56.51 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:03 | 0.22 | 0.22 | 56.68 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:05 | 0.22 | 0.22 | 57.57 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:10 | 0.22 | 0.22 | 57.37 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:05 | 0.22 | 0.22 | 57.30 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:05 | 0.22 | 0.22 | 58.26 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:10 | 0.22 | 0.22 | 57.07 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 57.68 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:03 | 0.22 | 0.22 | 57.06 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:03 | 0.22 | 0.22 | 56.66 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 56.51 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 58.26 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.10 | 57.10 | 1356.70 | 4612.48 | 13-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.52 | 57.52 | 1330.75 | 4567.87 | 01-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.76 | 56.76 | 1326.14 | 4377.07 | 01-MAR-12:13 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.14 | 57.14 | 1130.92 | 3948.64 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 57.54 | 57.54 | 1059.67 | 3584.79 | 02-MAY-11:15 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 57.46 | 57.46 | 1002.00 | 3261.30 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.58 | 58.58 | 898.25 | 3089.78 | 31-JUL-11:18 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 58.40 | 58.40 | 1019.87 | 3309.64 | 31-AUG-11:13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 57.20 | 57.20 | 1042.35 | 3656.61 | 29-SEP-11:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.34 | 57.34 | 1151.70 | 4072.65 | 31-OCT-11:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.27 | 57.27 | 1276.89 | 4418.02 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.93 | 56.93 | 1300.74 | 4587.23 | 28-DEC-12:40 |
Annual Sum or Average | 0.00 | 1157.07 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.76 | 56.76 | 898.25 | 3089.78 | ||
Maximum of Months | 0.00 | 0.00 | 58.58 | 58.58 | 1356.70 | 4612.48 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.143182E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.147330E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.197824E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.237927E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.375249E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.444560E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.526706E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.584268E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.454635E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.364365E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.262891E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.172272E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.391121E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.143182E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.584268E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.104791E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.115520E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.164139E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.206803E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.331352E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.394098E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.468971E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.508959E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.387440E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.298866E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.203398E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.128669E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.331301E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.104791E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.508959E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.102728E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.116536E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.169092E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.219240E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.358685E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.427673E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.517928E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.556248E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.414443E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.309706E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.202787E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.127103E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.352217E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.102728E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.556248E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.325721E+10 | 0.440946E+11 | 0.204043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.319961E+10 | 0.461085E+11 | 0.122781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.419029E+10 | 0.609332E+11 | 44250507.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.459577E+10 | 0.716373E+11 | 741884.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.674246E+10 | 0.106072E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.718477E+10 | 0.127608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.698801E+10 | 0.153876E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.740457E+10 | 0.171297E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.632145E+10 | 0.138076E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.594062E+10 | 0.112514E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.517725E+10 | 0.824651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.380407E+10 | 0.546881E+11 | 37848431.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.648061E+11 | 0.116937E+13 | 0.409665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.319961E+10 | 0.440946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.740457E+10 | 0.171297E+12 | 0.204043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.216609E+10 | 0.330536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.233982E+10 | 0.366854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.336229E+10 | 0.507090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.391727E+10 | 0.625153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.603686E+10 | 0.940214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.652309E+10 | 0.113748E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.676943E+10 | 0.136385E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.755259E+10 | 0.146631E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.614855E+10 | 0.115804E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.528792E+10 | 0.910501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.390833E+10 | 0.639420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.251035E+10 | 0.415914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565226E+11 | 0.986136E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.216609E+10 | 0.330536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.755259E+10 | 0.146631E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.183770E+10 | 0.329229E+11 | 4111167.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202673E+10 | 0.377334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.298643E+10 | 0.533822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.361644E+10 | 0.675436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.577331E+10 | 0.103794E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.632650E+10 | 0.125562E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.677761E+10 | 0.152590E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.746692E+10 | 0.162567E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.589127E+10 | 0.125863E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.483851E+10 | 0.959689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.331919E+10 | 0.652481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210797E+10 | 0.418164E+11 | 106983.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.529686E+11 | 0.106499E+13 | 4218151.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.183770E+10 | 0.329229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.746692E+10 | 0.162567E+12 | 4111167.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.325721E+10 | 0.00 | 0.00 | 0.00 | 0.108569E+11 | 0.204043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.319961E+10 | 0.00 | 0.00 | 0.00 | 0.114106E+11 | 0.122781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.419029E+10 | 0.00 | 0.00 | 0.00 | 0.155479E+11 | 44250507.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.459577E+10 | 0.00 | 0.00 | 0.00 | 0.191962E+11 | 741884.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.674246E+10 | 0.00 | 0.00 | 0.00 | 0.307825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.718477E+10 | 0.00 | 0.00 | 0.00 | 0.372712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.698801E+10 | 0.00 | 0.00 | 0.00 | 0.456826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.740457E+10 | 0.00 | 0.00 | 0.00 | 0.510223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.632145E+10 | 0.00 | 0.00 | 0.00 | 0.391420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.594062E+10 | 0.00 | 0.00 | 0.00 | 0.304959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.517725E+10 | 0.00 | 0.00 | 0.00 | 0.211118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.380407E+10 | 0.00 | 0.00 | 0.00 | 0.133853E+11 | 37848431.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.648061E+11 | 0.00 | 0.00 | 0.00 | 0.325905E+12 | 0.409665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.319961E+10 | 0.00 | 0.00 | 0.00 | 0.108569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.740457E+10 | 0.00 | 0.00 | 0.00 | 0.510223E+11 | 0.204043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.216609E+10 | 0.00 | 0.00 | 0.00 | 0.831304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.233982E+10 | 0.00 | 0.00 | 0.00 | 0.921221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.336229E+10 | 0.00 | 0.00 | 0.00 | 0.130516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.391727E+10 | 0.00 | 0.00 | 0.00 | 0.167630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.603686E+10 | 0.00 | 0.00 | 0.00 | 0.270983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.652309E+10 | 0.00 | 0.00 | 0.00 | 0.328867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.676943E+10 | 0.00 | 0.00 | 0.00 | 0.401277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.755259E+10 | 0.00 | 0.00 | 0.00 | 0.433433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.614855E+10 | 0.00 | 0.00 | 0.00 | 0.325955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.528792E+10 | 0.00 | 0.00 | 0.00 | 0.245987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.390833E+10 | 0.00 | 0.00 | 0.00 | 0.164314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.251035E+10 | 0.00 | 0.00 | 0.00 | 0.103565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565226E+11 | 0.00 | 0.00 | 0.00 | 0.274778E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.216609E+10 | 0.00 | 0.00 | 0.00 | 0.831304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.755259E+10 | 0.00 | 0.00 | 0.00 | 0.433433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.183770E+10 | 0.00 | 0.00 | 0.00 | 0.843100E+10 | 4111167.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202673E+10 | 0.00 | 0.00 | 0.00 | 0.962687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.298643E+10 | 0.00 | 0.00 | 0.00 | 0.139228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.361644E+10 | 0.00 | 0.00 | 0.00 | 0.183075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.577331E+10 | 0.00 | 0.00 | 0.00 | 0.300951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.632650E+10 | 0.00 | 0.00 | 0.00 | 0.364408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.677761E+10 | 0.00 | 0.00 | 0.00 | 0.450152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.746692E+10 | 0.00 | 0.00 | 0.00 | 0.481579E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.589127E+10 | 0.00 | 0.00 | 0.00 | 0.355530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.483851E+10 | 0.00 | 0.00 | 0.00 | 0.261321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.331919E+10 | 0.00 | 0.00 | 0.00 | 0.169596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210797E+10 | 0.00 | 0.00 | 0.00 | 0.106022E+11 | 106983.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.529686E+11 | 0.00 | 0.00 | 0.00 | 0.299244E+12 | 4218151.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.183770E+10 | 0.00 | 0.00 | 0.00 | 0.843100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.746692E+10 | 0.00 | 0.00 | 0.00 | 0.481579E+11 | 4111167.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.444362E+09 | 0.328510E+09 | 0.00 | 36588477.56 | 0.150000E+09 | 0.00 | 0.331901E+10 | 0.00 | 0.40 |
February | 0.270980E+09 | 0.108485E+10 | 0.00 | 24988668.65 | 0.162326E+09 | 0.00 | 0.167047E+10 | 0.00 | 0.38 |
March | 0.206584E+09 | 0.215528E+10 | 0.00 | 22507937.34 | 0.204531E+09 | 0.00 | 0.136779E+10 | 0.00 | 0.39 |
April | 89603693.35 | 0.452189E+10 | 0.00 | 6818966.91 | 0.101794E+10 | 0.00 | 0.393419E+09 | 0.00 | 0.36 |
May | 17006106.67 | 0.900090E+10 | 0.00 | 1720606.55 | 0.271971E+10 | 0.00 | 63382582.20 | 0.00 | 0.35 |
June | 3245480.20 | 0.141836E+11 | 0.00 | 418103.20 | 0.448791E+10 | 0.00 | 11817160.31 | 0.00 | 0.36 |
July | 2172051.32 | 0.180355E+11 | 0.00 | 8243.33 | 0.944759E+10 | 0.00 | 240799.09 | 0.00 | 0.39 |
August | 0.00 | 0.207231E+11 | 0.00 | 0.00 | 0.938763E+10 | 0.00 | 0.00 | 0.00 | 0.40 |
September | 54537.97 | 0.157348E+11 | 0.00 | 86548.12 | 0.650657E+10 | 0.00 | 753051.13 | 0.00 | 0.37 |
October | 32923046.74 | 0.996200E+10 | 0.00 | 1303572.64 | 0.388880E+10 | 0.00 | 50348967.98 | 0.00 | 0.35 |
November | 23843074.15 | 0.543533E+10 | 0.00 | 3981507.51 | 0.901805E+09 | 0.00 | 0.108334E+09 | 0.00 | 0.35 |
December | 0.205747E+09 | 0.155413E+10 | 0.00 | 25786223.22 | 0.396792E+09 | 0.00 | 0.153077E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.129652E+10 | 0.102720E+12 | 0.00 | 0.124209E+09 | 0.392716E+11 | 0.00 | 0.851634E+10 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.328510E+09 | 0.00 | 0.00 | 0.150000E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.444362E+09 | 0.207231E+11 | 0.00 | 36588477.56 | 0.944759E+10 | 0.00 | 0.331901E+10 | 0.00 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.609086E+09 | 0.310426E+09 | 0.00 | 16216702.58 | 0.210748E+09 | 0.00 | 0.192968E+10 | 0.00 | 0.31 |
February | 0.310652E+09 | 0.941567E+09 | 0.00 | 12318365.59 | 0.207898E+09 | 0.00 | 0.100460E+10 | 0.00 | 0.30 |
March | 0.271458E+09 | 0.186610E+10 | 0.00 | 12782866.71 | 0.217303E+09 | 0.00 | 0.866067E+09 | 0.00 | 0.32 |
April | 0.155927E+09 | 0.384695E+10 | 0.00 | 4717604.94 | 0.104985E+10 | 0.00 | 0.274093E+09 | 0.00 | 0.31 |
May | 33597575.30 | 0.800654E+10 | 0.00 | 1488509.79 | 0.262312E+10 | 0.00 | 63155417.10 | 0.00 | 0.33 |
June | 6127129.97 | 0.130233E+11 | 0.00 | 294377.49 | 0.431321E+10 | 0.00 | 13472143.57 | 0.00 | 0.34 |
July | 2808533.90 | 0.168773E+11 | 0.00 | 2890.05 | 0.863637E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.196320E+11 | 0.00 | 0.00 | 0.761038E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
September | 531471.26 | 0.147946E+11 | 0.00 | 97613.86 | 0.472060E+10 | 0.00 | 2559265.26 | 0.00 | 0.33 |
October | 46313381.70 | 0.917063E+10 | 0.00 | 1074121.40 | 0.271766E+10 | 0.00 | 32469330.81 | 0.00 | 0.32 |
November | 38626800.76 | 0.497107E+10 | 0.00 | 2533914.30 | 0.677766E+09 | 0.00 | 68994451.64 | 0.00 | 0.31 |
December | 0.296682E+09 | 0.147500E+10 | 0.00 | 12437560.16 | 0.361373E+09 | 0.00 | 0.840775E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.177181E+10 | 0.949155E+11 | 0.00 | 63964526.87 | 0.333463E+11 | 0.00 | 0.509587E+10 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.310426E+09 | 0.00 | 0.00 | 0.207898E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.609086E+09 | 0.196320E+11 | 0.00 | 16216702.58 | 0.863637E+10 | 0.00 | 0.192968E+10 | 0.00 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.835098E+09 | 0.328881E+09 | 0.00 | 9597520.19 | 0.322154E+09 | 0.00 | 0.995121E+09 | 0.00 | 0.29 |
February | 0.402732E+09 | 0.910256E+09 | 0.00 | 8209436.96 | 0.367357E+09 | 0.00 | 0.562433E+09 | 0.00 | 0.29 |
March | 0.327870E+09 | 0.187509E+10 | 0.00 | 7939363.80 | 0.252029E+09 | 0.00 | 0.474536E+09 | 0.00 | 0.31 |
April | 0.141574E+09 | 0.375959E+10 | 0.00 | 2831810.67 | 0.982469E+09 | 0.00 | 0.126234E+09 | 0.00 | 0.31 |
May | 27755528.02 | 0.767326E+10 | 0.00 | 1045045.13 | 0.271167E+10 | 0.00 | 34481557.26 | 0.00 | 0.33 |
June | 7538925.27 | 0.125246E+11 | 0.00 | 340271.37 | 0.464667E+10 | 0.00 | 9063419.45 | 0.00 | 0.35 |
July | 837227.97 | 0.164682E+11 | 0.00 | 0.00 | 0.911100E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.191083E+11 | 0.00 | 0.00 | 0.834629E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
September | 584276.73 | 0.142102E+11 | 0.00 | 54560.34 | 0.510047E+10 | 0.00 | 1144045.18 | 0.00 | 0.34 |
October | 43677264.93 | 0.868949E+10 | 0.00 | 940715.08 | 0.289313E+10 | 0.00 | 16139058.54 | 0.00 | 0.31 |
November | 20739538.87 | 0.494991E+10 | 0.00 | 1715183.40 | 0.677271E+09 | 0.00 | 41271158.87 | 0.00 | 0.30 |
December | 0.341916E+09 | 0.134190E+10 | 0.00 | 7101671.50 | 0.690846E+09 | 0.00 | 0.377558E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.215032E+10 | 0.918397E+11 | 0.00 | 39775578.44 | 0.361014E+11 | 0.00 | 0.263798E+10 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.328881E+09 | 0.00 | 0.00 | 0.252029E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.835098E+09 | 0.191083E+11 | 0.00 | 9597520.19 | 0.911100E+10 | 0.00 | 0.995121E+09 | 0.00 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.248618E+09 | 68646797.77 | 0.00 | 1696040.58 | 80068635.62 | 0.00 | 0.161144E+09 | 0.00 | 0.31 |
February | 0.109814E+09 | 0.197747E+09 | 0.00 | 1852979.68 | 0.110625E+09 | 0.00 | 0.115967E+09 | 0.00 | 0.33 |
March | 85687032.94 | 0.509586E+09 | 0.00 | 1832993.90 | 70720653.31 | 0.00 | 0.107243E+09 | 0.00 | 0.37 |
April | 40201019.35 | 0.124791E+10 | 0.00 | 631841.21 | 0.187352E+09 | 0.00 | 22105129.78 | 0.00 | 0.42 |
May | 5942796.46 | 0.315153E+10 | 0.00 | 293870.12 | 0.372791E+09 | 0.00 | 9238493.90 | 0.00 | 0.52 |
June | 1426317.34 | 0.549944E+10 | 0.00 | 114012.81 | 0.569597E+09 | 0.00 | 2670945.09 | 0.00 | 0.57 |
July | 162611.46 | 0.777915E+10 | 0.00 | 3497.31 | 0.117920E+10 | 0.00 | 37082.04 | 0.00 | 0.62 |
August | 0.00 | 0.845411E+10 | 0.00 | 0.00 | 0.115239E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
September | 133726.28 | 0.568102E+10 | 0.00 | 11700.76 | 0.734146E+09 | 0.00 | 263061.40 | 0.00 | 0.52 |
October | 10301081.57 | 0.290519E+10 | 0.00 | 264048.03 | 0.506912E+09 | 0.00 | 4180974.25 | 0.00 | 0.44 |
November | 5078658.17 | 0.131634E+10 | 0.00 | 445567.49 | 0.183791E+09 | 0.00 | 10807970.87 | 0.00 | 0.37 |
December | 89561319.74 | 0.318674E+09 | 0.00 | 1455911.94 | 0.158351E+09 | 0.00 | 74665104.72 | 0.00 | 0.32 |
Annual Sum or Average | 0.596926E+09 | 0.371293E+11 | 0.00 | 8602463.83 | 0.530594E+10 | 0.00 | 0.508323E+09 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 68646797.77 | 0.00 | 0.00 | 70720653.31 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.248618E+09 | 0.845411E+10 | 0.00 | 1852979.68 | 0.117920E+10 | 0.00 | 0.161144E+09 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.168909E+09 | 68025147.19 | 0.00 | 1637381.90 | 52159922.78 | 117645.33 | 0.157407E+09 | 0.00 | 0.40 |
February | 78949592.88 | 0.159221E+09 | 0.00 | 1624786.69 | 85283918.54 | 0.00 | 0.101632E+09 | 0.00 | 0.42 |
March | 63739594.11 | 0.423747E+09 | 0.00 | 1521017.21 | 47268883.42 | 0.00 | 86876393.44 | 0.00 | 0.48 |
April | 31790828.01 | 0.104286E+10 | 0.00 | 623772.43 | 0.109273E+09 | 0.00 | 18558973.88 | 0.00 | 0.55 |
May | 4566098.86 | 0.240956E+10 | 0.00 | 227771.94 | 0.281600E+09 | 0.00 | 7330820.48 | 0.00 | 0.65 |
June | 1150231.51 | 0.409576E+10 | 0.00 | 88899.74 | 0.459348E+09 | 0.00 | 2077902.64 | 0.00 | 0.69 |
July | 127307.76 | 0.568622E+10 | 0.00 | 3073.86 | 0.990831E+09 | 0.00 | 32150.81 | 0.00 | 0.74 |
August | 0.00 | 0.633466E+10 | 0.00 | 0.00 | 0.935481E+09 | 0.00 | 0.00 | 0.00 | 0.76 |
September | 184374.58 | 0.438073E+10 | 0.00 | 6561.17 | 0.571217E+09 | 0.00 | 124745.03 | 0.00 | 0.65 |
October | 4894943.58 | 0.236694E+10 | 0.00 | 356069.44 | 0.348725E+09 | 0.00 | 7522987.81 | 0.00 | 0.55 |
November | 3615577.59 | 0.107951E+10 | 0.00 | 343767.90 | 0.128152E+09 | 0.00 | 8078289.94 | 0.00 | 0.47 |
December | 62147207.35 | 0.266592E+09 | 0.00 | 1208591.94 | 0.115920E+09 | 0.00 | 66059616.88 | 0.00 | 0.40 |
Annual Sum or Average | 0.420075E+09 | 0.283138E+11 | 0.00 | 7641694.22 | 0.412526E+10 | 117645.33 | 0.455700E+09 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 68025147.19 | 0.00 | 0.00 | 47268883.42 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.168909E+09 | 0.633466E+10 | 0.00 | 1637381.90 | 0.990831E+09 | 117645.33 | 0.157407E+09 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.217327E+09 | 0.173267E+09 | 0.00 | 4358086.30 | 52317102.30 | 0.00 | 0.388222E+09 | 0.00 | 0.47 |
February | 0.107760E+09 | 0.345879E+09 | 0.00 | 3685926.97 | 73946719.10 | 0.00 | 0.222827E+09 | 0.00 | 0.48 |
March | 91569467.59 | 0.688924E+09 | 0.00 | 2773452.27 | 58927936.26 | 0.00 | 0.159581E+09 | 0.00 | 0.49 |
April | 45480411.75 | 0.145024E+10 | 0.00 | 709748.21 | 0.178935E+09 | 0.00 | 23586511.76 | 0.00 | 0.48 |
May | 6785541.33 | 0.311321E+10 | 0.00 | 279373.40 | 0.452751E+09 | 0.00 | 9494281.16 | 0.00 | 0.53 |
June | 1627975.55 | 0.520995E+10 | 0.00 | 105831.14 | 0.717305E+09 | 0.00 | 2749960.51 | 0.00 | 0.56 |
July | 180184.53 | 0.756891E+10 | 0.00 | 2998.17 | 0.144753E+10 | 0.00 | 31956.72 | 0.00 | 0.63 |
August | 0.00 | 0.882749E+10 | 0.00 | 0.00 | 0.133429E+10 | 0.00 | 0.00 | 0.00 | 0.66 |
September | 148177.79 | 0.676737E+10 | 0.00 | 11367.76 | 0.746865E+09 | 0.00 | 290665.91 | 0.00 | 0.61 |
October | 7660165.39 | 0.404745E+10 | 0.00 | 792581.29 | 0.429523E+09 | 0.00 | 12436128.36 | 0.00 | 0.59 |
November | 5367620.19 | 0.208909E+10 | 0.00 | 797368.72 | 0.108761E+09 | 0.00 | 18394632.54 | 0.00 | 0.55 |
December | 80071791.59 | 0.648459E+09 | 0.00 | 3373984.74 | 97095027.40 | 0.00 | 0.168045E+09 | 0.00 | 0.49 |
Annual Sum or Average | 0.563978E+09 | 0.409302E+11 | 0.00 | 16890718.96 | 0.569824E+10 | 0.00 | 0.100566E+10 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.173267E+09 | 0.00 | 0.00 | 52317102.30 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.217327E+09 | 0.882749E+10 | 0.00 | 4358086.30 | 0.144753E+10 | 0.00 | 0.388222E+09 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.225319E+09 | 59106284.40 | 0.00 | 1475986.96 | 69425723.37 | 227201.79 | 0.144539E+09 | 0.00 | 0.43 |
February | 97465043.81 | 0.164267E+09 | 0.00 | 1665404.63 | 98889020.61 | 0.00 | 0.108902E+09 | 0.00 | 0.45 |
March | 78313670.58 | 0.426361E+09 | 0.00 | 1560144.48 | 63201810.31 | 0.00 | 99138271.94 | 0.00 | 0.51 |
April | 37236069.98 | 0.104852E+10 | 0.00 | 431335.30 | 0.144416E+09 | 0.00 | 16168457.51 | 0.00 | 0.55 |
May | 6656822.18 | 0.246921E+10 | 0.00 | 180635.89 | 0.337754E+09 | 0.00 | 6085945.23 | 0.00 | 0.65 |
June | 1846241.75 | 0.416528E+10 | 0.00 | 69662.64 | 0.539243E+09 | 0.00 | 1534008.45 | 0.00 | 0.69 |
July | 144837.12 | 0.571562E+10 | 0.00 | 2305.75 | 0.117378E+10 | 0.00 | 24405.80 | 0.00 | 0.76 |
August | 0.00 | 0.642698E+10 | 0.00 | 0.00 | 0.110325E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
September | 209761.63 | 0.452527E+10 | 0.00 | 6173.14 | 0.642492E+09 | 0.00 | 141020.28 | 0.00 | 0.65 |
October | 9792766.90 | 0.229862E+10 | 0.00 | 157068.56 | 0.450293E+09 | 0.00 | 2558679.77 | 0.00 | 0.56 |
November | 4523532.71 | 0.104834E+10 | 0.00 | 386457.09 | 0.175411E+09 | 0.00 | 9926159.38 | 0.00 | 0.48 |
December | 78339737.77 | 0.258391E+09 | 0.00 | 1230701.18 | 0.160087E+09 | 0.00 | 70788565.93 | 0.00 | 0.44 |
Annual Sum or Average | 0.539848E+09 | 0.286060E+11 | 0.00 | 7165875.61 | 0.495825E+10 | 227201.79 | 0.459807E+09 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 59106284.40 | 0.00 | 0.00 | 63201810.31 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.225319E+09 | 0.642698E+10 | 0.00 | 1665404.63 | 0.117378E+10 | 227201.79 | 0.144539E+09 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.228705E+09 | 54171323.35 | 0.00 | 3347641.34 | 31989783.76 | 0.00 | 0.304813E+09 | 0.00 | 0.28 |
February | 0.131657E+09 | 0.180882E+09 | 0.00 | 2480780.41 | 41510790.93 | 0.00 | 0.156826E+09 | 0.00 | 0.28 |
March | 0.115638E+09 | 0.401304E+09 | 0.00 | 2142415.23 | 47804323.08 | 0.00 | 0.122484E+09 | 0.00 | 0.31 |
April | 53511264.95 | 0.968570E+09 | 0.00 | 578951.81 | 0.220282E+09 | 0.00 | 27170089.89 | 0.00 | 0.34 |
May | 6123517.93 | 0.263929E+10 | 0.00 | 256278.78 | 0.409300E+09 | 0.00 | 10376356.31 | 0.00 | 0.42 |
June | 723380.50 | 0.463336E+10 | 0.00 | 71712.59 | 0.601637E+09 | 0.00 | 2369064.88 | 0.00 | 0.47 |
July | 444582.13 | 0.678977E+10 | 0.00 | 6785.21 | 0.126173E+10 | 0.00 | 66211.48 | 0.00 | 0.53 |
August | 0.00 | 0.775544E+10 | 0.00 | 0.00 | 0.133862E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 11484.71 | 0.528723E+10 | 0.00 | 21973.67 | 0.989445E+09 | 0.00 | 168360.76 | 0.00 | 0.48 |
October | 7777765.30 | 0.283116E+10 | 0.00 | 238116.75 | 0.688579E+09 | 0.00 | 9475874.58 | 0.00 | 0.42 |
November | 12162276.66 | 0.122471E+10 | 0.00 | 527900.46 | 0.201310E+09 | 0.00 | 11563937.70 | 0.00 | 0.35 |
December | 0.107201E+09 | 0.288739E+09 | 0.00 | 3007199.12 | 85517574.98 | 0.00 | 0.166656E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.663956E+09 | 0.330546E+11 | 0.00 | 12679755.36 | 0.591772E+10 | 0.00 | 0.811968E+09 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 54171323.35 | 0.00 | 0.00 | 31989783.76 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.228705E+09 | 0.775544E+10 | 0.00 | 3347641.34 | 0.133862E+10 | 0.00 | 0.304813E+09 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.149747E+09 | 44934905.85 | 0.00 | 3148649.31 | 24279443.20 | 0.00 | 0.284057E+09 | 0.00 | 0.36 |
February | 91976335.84 | 0.141059E+09 | 0.00 | 2337569.97 | 29398830.92 | 0.00 | 0.144030E+09 | 0.00 | 0.36 |
March | 83131303.65 | 0.326376E+09 | 0.00 | 1881058.35 | 35869469.94 | 0.00 | 0.106113E+09 | 0.00 | 0.40 |
April | 39593164.96 | 0.836421E+09 | 0.00 | 578268.61 | 0.124783E+09 | 0.00 | 26017560.54 | 0.00 | 0.44 |
May | 3863104.01 | 0.211442E+10 | 0.00 | 231328.69 | 0.267578E+09 | 0.00 | 9131669.77 | 0.00 | 0.53 |
June | 556130.47 | 0.354766E+10 | 0.00 | 52067.36 | 0.437688E+09 | 0.00 | 1807740.88 | 0.00 | 0.57 |
July | 341792.00 | 0.516321E+10 | 0.00 | 7318.70 | 0.917693E+09 | 0.00 | 60138.21 | 0.00 | 0.64 |
August | 0.00 | 0.597085E+10 | 0.00 | 0.00 | 0.987657E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
September | 8829.37 | 0.418513E+10 | 0.00 | 15928.89 | 0.685579E+09 | 0.00 | 122511.75 | 0.00 | 0.60 |
October | 3756544.49 | 0.233965E+10 | 0.00 | 275172.82 | 0.434702E+09 | 0.00 | 10879901.60 | 0.00 | 0.52 |
November | 8785969.25 | 0.968934E+09 | 0.00 | 465723.99 | 0.134906E+09 | 0.00 | 10509985.11 | 0.00 | 0.44 |
December | 69898825.96 | 0.223691E+09 | 0.00 | 2553014.13 | 64982213.60 | 0.00 | 0.147808E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.451659E+09 | 0.258623E+11 | 0.00 | 11546100.81 | 0.414512E+10 | 0.00 | 0.740537E+09 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 44934905.85 | 0.00 | 0.00 | 24279443.20 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.149747E+09 | 0.597085E+10 | 0.00 | 3148649.31 | 0.987657E+09 | 0.00 | 0.284057E+09 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.209593E+09 | 0.109329E+09 | 0.00 | 5476384.55 | 24185429.61 | 47819767.58 | 0.413667E+09 | 0.00 | 0.39 |
February | 0.117411E+09 | 0.308074E+09 | 0.00 | 4106679.78 | 25968460.17 | 24366361.68 | 0.226935E+09 | 0.00 | 0.40 |
March | 0.114396E+09 | 0.652706E+09 | 0.00 | 2993528.55 | 38661078.42 | 9550791.46 | 0.156321E+09 | 0.00 | 0.43 |
April | 59261839.74 | 0.140668E+10 | 0.00 | 693529.12 | 0.189467E+09 | 43694.64 | 27135375.82 | 0.00 | 0.44 |
May | 5772622.63 | 0.343400E+10 | 0.00 | 351382.04 | 0.443358E+09 | 0.00 | 12929556.80 | 0.00 | 0.53 |
June | 755576.33 | 0.575929E+10 | 0.00 | 78960.01 | 0.684034E+09 | 0.00 | 2504361.59 | 0.00 | 0.58 |
July | 457851.63 | 0.871459E+10 | 0.00 | 7414.94 | 0.134553E+10 | 0.00 | 76288.55 | 0.00 | 0.66 |
August | 0.00 | 0.107395E+11 | 0.00 | 0.00 | 0.132148E+10 | 0.00 | 0.00 | 0.00 | 0.74 |
September | 0.00 | 0.795498E+10 | 0.00 | 31990.39 | 0.816081E+09 | 0.00 | 224577.21 | 0.00 | 0.67 |
October | 4624517.82 | 0.484422E+10 | 0.00 | 487399.89 | 0.439412E+09 | 0.00 | 15864033.60 | 0.00 | 0.63 |
November | 13344181.93 | 0.222799E+10 | 0.00 | 803719.30 | 96414436.09 | 0.00 | 16175381.84 | 0.00 | 0.55 |
December | 0.107266E+09 | 0.559224E+09 | 0.00 | 4721864.43 | 45382817.36 | 9104183.05 | 0.245161E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.632883E+09 | 0.467106E+11 | 0.00 | 19752853.01 | 0.546998E+10 | 90884798.41 | 0.111699E+10 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.109329E+09 | 0.00 | 0.00 | 24185429.61 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.209593E+09 | 0.107395E+11 | 0.00 | 5476384.55 | 0.134553E+10 | 47819767.58 | 0.413667E+09 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.185004E+09 | 46976683.10 | 0.00 | 2774847.27 | 25023778.15 | 0.00 | 0.252716E+09 | 0.00 | 0.36 |
February | 0.106798E+09 | 0.151809E+09 | 0.00 | 2138404.02 | 30252259.09 | 0.00 | 0.135585E+09 | 0.00 | 0.37 |
March | 91392825.25 | 0.353460E+09 | 0.00 | 1817786.61 | 29506652.11 | 0.00 | 0.109122E+09 | 0.00 | 0.41 |
April | 41563488.53 | 0.877489E+09 | 0.00 | 417241.63 | 0.120453E+09 | 0.00 | 21819994.52 | 0.00 | 0.43 |
May | 4777533.72 | 0.220097E+10 | 0.00 | 188088.40 | 0.272385E+09 | 0.00 | 8252820.37 | 0.00 | 0.53 |
June | 586215.48 | 0.369479E+10 | 0.00 | 54381.94 | 0.403916E+09 | 0.00 | 1902382.70 | 0.00 | 0.57 |
July | 360281.93 | 0.526864E+10 | 0.00 | 6446.76 | 0.938153E+09 | 0.00 | 64324.48 | 0.00 | 0.65 |
August | 0.00 | 0.613592E+10 | 0.00 | 0.00 | 0.990708E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
September | 9307.01 | 0.437565E+10 | 0.00 | 16542.87 | 0.671359E+09 | 0.00 | 128332.55 | 0.00 | 0.60 |
October | 6302971.17 | 0.234916E+10 | 0.00 | 172960.90 | 0.462086E+09 | 0.00 | 7104212.51 | 0.00 | 0.52 |
November | 9893411.78 | 0.997872E+09 | 0.00 | 423487.44 | 0.128922E+09 | 0.00 | 9164736.29 | 0.00 | 0.44 |
December | 88705530.23 | 0.238826E+09 | 0.00 | 2333214.86 | 68317857.89 | 0.00 | 0.134489E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.535393E+09 | 0.266916E+11 | 0.00 | 10343402.70 | 0.414108E+10 | 0.00 | 0.680349E+09 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 46976683.10 | 0.00 | 0.00 | 25023778.15 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.185004E+09 | 0.613592E+10 | 0.00 | 2774847.27 | 0.990708E+09 | 0.00 | 0.252716E+09 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.259768E+09 | 74256249.58 | 0.00 | 2376180.23 | 39158468.49 | 0.00 | 0.244127E+09 | 0.00 | 0.30 |
February | 0.129509E+09 | 0.223606E+09 | 0.00 | 2141444.66 | 49050522.38 | 0.00 | 0.147136E+09 | 0.00 | 0.32 |
March | 0.103864E+09 | 0.532506E+09 | 0.00 | 2265915.74 | 45918023.58 | 0.00 | 0.139259E+09 | 0.00 | 0.37 |
April | 46197999.89 | 0.129484E+10 | 0.00 | 788659.56 | 0.189546E+09 | 0.00 | 43922918.81 | 0.00 | 0.42 |
May | 6313869.11 | 0.330946E+10 | 0.00 | 378036.64 | 0.324232E+09 | 0.00 | 15655432.07 | 0.00 | 0.52 |
June | 1021538.56 | 0.571491E+10 | 0.00 | 86307.85 | 0.464386E+09 | 0.00 | 3417000.35 | 0.00 | 0.56 |
July | 512630.45 | 0.797127E+10 | 0.00 | 18803.60 | 0.948581E+09 | 0.00 | 103225.93 | 0.00 | 0.60 |
August | 0.00 | 0.869049E+10 | 0.00 | 0.00 | 0.938296E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
September | 112102.10 | 0.581159E+10 | 0.00 | 23529.18 | 0.642916E+09 | 0.00 | 542416.87 | 0.00 | 0.51 |
October | 10389087.67 | 0.299358E+10 | 0.00 | 260284.11 | 0.478773E+09 | 0.00 | 6330616.93 | 0.00 | 0.44 |
November | 11767999.43 | 0.134974E+10 | 0.00 | 386521.32 | 0.150750E+09 | 0.00 | 11323139.19 | 0.00 | 0.37 |
December | 0.114604E+09 | 0.341961E+09 | 0.00 | 1951662.15 | 78516527.69 | 0.00 | 0.119185E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.684061E+09 | 0.383082E+11 | 0.00 | 10677345.04 | 0.435012E+10 | 0.00 | 0.731003E+09 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 74256249.58 | 0.00 | 0.00 | 39158468.49 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.259768E+09 | 0.869049E+10 | 0.00 | 2376180.23 | 0.948581E+09 | 0.00 | 0.244127E+09 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.196655E+09 | 57872175.24 | 0.00 | 2118156.28 | 33206455.53 | 0.00 | 0.218227E+09 | 0.00 | 0.39 |
February | 99928126.69 | 0.164269E+09 | 0.00 | 1877328.17 | 46104984.98 | 0.00 | 0.128348E+09 | 0.00 | 0.41 |
March | 84806844.42 | 0.415859E+09 | 0.00 | 1825836.41 | 35809831.12 | 0.00 | 0.110431E+09 | 0.00 | 0.47 |
April | 41150609.77 | 0.104375E+10 | 0.00 | 712546.61 | 0.121964E+09 | 0.00 | 35119775.57 | 0.00 | 0.54 |
May | 4656233.23 | 0.248991E+10 | 0.00 | 295215.48 | 0.265453E+09 | 0.00 | 13145719.73 | 0.00 | 0.64 |
June | 1131996.13 | 0.419488E+10 | 0.00 | 53943.78 | 0.428362E+09 | 0.00 | 2372601.39 | 0.00 | 0.67 |
July | 419515.11 | 0.577246E+10 | 0.00 | 13860.70 | 0.873500E+09 | 0.00 | 82892.17 | 0.00 | 0.72 |
August | 0.00 | 0.645683E+10 | 0.00 | 0.00 | 0.821470E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
September | 73337.30 | 0.443503E+10 | 0.00 | 11929.29 | 0.527518E+09 | 0.00 | 447422.65 | 0.00 | 0.63 |
October | 6900204.03 | 0.238830E+10 | 0.00 | 296375.79 | 0.349306E+09 | 0.00 | 8358579.57 | 0.00 | 0.55 |
November | 8421219.65 | 0.103982E+10 | 0.00 | 336537.42 | 0.117242E+09 | 0.00 | 10102521.45 | 0.00 | 0.46 |
December | 86469575.53 | 0.262417E+09 | 0.00 | 1590555.28 | 67842293.01 | 0.00 | 0.101974E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.530613E+09 | 0.287214E+11 | 0.00 | 9132285.22 | 0.368778E+10 | 0.00 | 0.628610E+09 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 57872175.24 | 0.00 | 0.00 | 33206455.53 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.196655E+09 | 0.645683E+10 | 0.00 | 2118156.28 | 0.873500E+09 | 0.00 | 0.218227E+09 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.216629E+09 | 0.162118E+09 | 0.00 | 5360369.49 | 17896924.29 | 0.00 | 0.513694E+09 | 0.00 | 0.46 |
February | 0.122427E+09 | 0.365011E+09 | 0.00 | 4001837.49 | 20411506.95 | 0.00 | 0.264564E+09 | 0.00 | 0.47 |
March | 0.106405E+09 | 0.725833E+09 | 0.00 | 3228838.74 | 31376142.33 | 0.00 | 0.194847E+09 | 0.00 | 0.48 |
April | 50017554.87 | 0.152176E+10 | 0.00 | 834010.97 | 0.166498E+09 | 0.00 | 45813356.66 | 0.00 | 0.48 |
May | 7055320.69 | 0.328240E+10 | 0.00 | 360195.57 | 0.378582E+09 | 0.00 | 15672538.34 | 0.00 | 0.52 |
June | 1384009.55 | 0.539652E+10 | 0.00 | 79490.16 | 0.595340E+09 | 0.00 | 3209400.81 | 0.00 | 0.55 |
July | 548619.63 | 0.775882E+10 | 0.00 | 16583.87 | 0.114652E+10 | 0.00 | 96431.98 | 0.00 | 0.60 |
August | 0.00 | 0.911573E+10 | 0.00 | 0.00 | 0.103677E+10 | 0.00 | 0.00 | 0.00 | 0.64 |
September | 95906.63 | 0.701614E+10 | 0.00 | 23294.66 | 0.596084E+09 | 0.00 | 600706.77 | 0.00 | 0.60 |
October | 8942957.03 | 0.426387E+10 | 0.00 | 707969.63 | 0.353607E+09 | 0.00 | 11518741.69 | 0.00 | 0.59 |
November | 10682449.67 | 0.213028E+10 | 0.00 | 709373.63 | 80136295.37 | 0.00 | 19703996.42 | 0.00 | 0.55 |
December | 0.100589E+09 | 0.636205E+09 | 0.00 | 4145557.47 | 45065834.14 | 0.00 | 0.237813E+09 | 0.00 | 0.48 |
Annual Sum or Average | 0.624777E+09 | 0.423747E+11 | 0.00 | 19467521.69 | 0.446829E+10 | 0.00 | 0.130753E+10 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.162118E+09 | 0.00 | 0.00 | 17896924.29 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.216629E+09 | 0.911573E+10 | 0.00 | 5360369.49 | 0.114652E+10 | 0.00 | 0.513694E+09 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.237879E+09 | 58732459.32 | 0.00 | 1931685.20 | 38486991.86 | 0.00 | 0.202765E+09 | 0.00 | 0.41 |
February | 0.117854E+09 | 0.180487E+09 | 0.00 | 1799647.44 | 47611277.95 | 0.00 | 0.126717E+09 | 0.00 | 0.43 |
March | 97695731.98 | 0.453513E+09 | 0.00 | 1783706.41 | 33406506.25 | 0.00 | 0.116377E+09 | 0.00 | 0.50 |
April | 48835584.51 | 0.111940E+10 | 0.00 | 485755.84 | 0.126030E+09 | 0.00 | 24327321.47 | 0.00 | 0.55 |
May | 7613213.10 | 0.265499E+10 | 0.00 | 228066.85 | 0.277463E+09 | 0.00 | 10121046.89 | 0.00 | 0.65 |
June | 1136070.89 | 0.441386E+10 | 0.00 | 50111.78 | 0.416243E+09 | 0.00 | 2505477.61 | 0.00 | 0.69 |
July | 450337.06 | 0.596689E+10 | 0.00 | 11606.96 | 0.921446E+09 | 0.00 | 73177.04 | 0.00 | 0.73 |
August | 0.00 | 0.673286E+10 | 0.00 | 0.00 | 0.849051E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
September | 78725.42 | 0.473130E+10 | 0.00 | 11360.31 | 0.508091E+09 | 0.00 | 477145.75 | 0.00 | 0.64 |
October | 9713017.16 | 0.241895E+10 | 0.00 | 159893.50 | 0.383802E+09 | 0.00 | 4062200.17 | 0.00 | 0.56 |
November | 12001495.93 | 0.108543E+10 | 0.00 | 307665.24 | 0.115454E+09 | 0.00 | 8515830.35 | 0.00 | 0.47 |
December | 0.105910E+09 | 0.282291E+09 | 0.00 | 1546921.13 | 78815171.84 | 0.00 | 98472602.85 | 0.00 | 0.41 |
Annual Sum or Average | 0.639166E+09 | 0.300987E+11 | 0.00 | 8316420.68 | 0.379590E+10 | 0.00 | 0.594414E+09 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 58732459.32 | 0.00 | 0.00 | 33406506.25 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.237879E+09 | 0.673286E+10 | 0.00 | 1931685.20 | 0.921446E+09 | 0.00 | 0.202765E+09 | 0.00 | 0.75 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.151729E+12 | 0.269344E+10 | 0.00 | 0.219903E+11 | 0.137672E+12 |
February | 0.166158E+12 | 0.100600E+10 | 0.00 | 0.584793E+10 | 0.150777E+12 |
March | 0.203110E+12 | -889919660.8 | 0.00 | -0.594892E+10 | 0.207547E+12 |
April | 0.213081E+12 | -0.501934E+10 | 0.00 | -0.406695E+11 | 0.255963E+12 |
May | 0.221413E+12 | -0.115511E+11 | 0.00 | -0.967054E+11 | 0.391864E+12 |
June | 0.211164E+12 | -0.190179E+11 | 0.00 | -0.158455E+12 | 0.473516E+12 |
July | 0.208221E+12 | -0.256747E+11 | 0.00 | -0.219133E+12 | 0.573675E+12 |
August | 0.203207E+12 | -0.274927E+11 | 0.00 | -0.235434E+12 | 0.623018E+12 |
September | 0.182657E+12 | -0.202830E+11 | 0.00 | -0.182344E+12 | 0.487034E+12 |
October | 0.159976E+12 | -0.119297E+11 | 0.00 | -0.112907E+12 | 0.380759E+12 |
November | 0.131830E+12 | -0.536084E+10 | 0.00 | -0.478929E+11 | 0.266158E+12 |
December | 0.131233E+12 | 0.135229E+09 | 0.00 | -0.375084E+10 | 0.172440E+12 |
Annual Sum or Average | 0.218378E+13 | -0.123385E+12 | 0.00 | -0.107540E+13 | 0.412042E+13 |
Minimum of Months | 0.131233E+12 | -0.274927E+11 | 0.00 | -0.235434E+12 | 0.137672E+12 |
Maximum of Months | 0.221413E+12 | 0.269344E+10 | 0.00 | 0.219903E+11 | 0.623018E+12 |