Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2023-10-16 08:35:16
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1863.01 | 373.94 | 373.94 |
Net Site Energy | 1863.01 | 373.94 | 373.94 |
Total Source Energy | 5395.27 | 1082.91 | 1082.91 |
Net Source Energy | 5395.27 | 1082.91 | 1082.91 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 170.02 | 135.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 221.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 281.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 100.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 107.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1620.63 | 242.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 170.02 | 135.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 221.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 281.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 72.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 100.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 107.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 170.02 | 135.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 221.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 281.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 72.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 100.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 107.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 98.83 | 48.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 325.28 | 48.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 98.83 | 48.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 325.28 | 48.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1620.626 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1620.626 | 100.00 |
Total On-Site and Utility Electric Sources | 1620.626 | 100.00 |
Total Electricity End Uses | 1620.626 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 363.17 |
Time Setpoint Not Met During Occupied Cooling | 118.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2695.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.5763 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 7.5763 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 7.5763 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 06-FEB-07:30 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 210984.87 | 93430.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 9359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21853.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 256.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7200.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8160.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 255212.18 | 101591.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 210984.87 | 93430.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 9359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 16082.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 256.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7200.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8160.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 538.44 | 146.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 701.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 890.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 228.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2413.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 41.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 319.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 116.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5132.52 | 262.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 108.07 | 29.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 140.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 178.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 64.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1030.17 | 52.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 108.07 | 29.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 140.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 178.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 64.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1030.17 | 52.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.82 | 0.265889 | 0.275000 | 0.775137 | 0.709037 | 0.500000 | 0.001433 |
CORE_MID VAV BOX COMPONENT | 2.08 | 0.360756 | 0.361000 | 0.749961 | 0.962017 | 0.500000 | 0.001056 |
CORE_TOP VAV BOX COMPONENT | 2.22 | 0.337124 | 0.352000 | 0.782526 | 0.898997 | 0.500000 | 0.001130 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.710779 | 0.222280 | 0.232000 | 0.164901 | 0.592746 | 0.500000 | 0.001714 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.750584 | 0.133259 | 0.200000 | 0.150117 | 0.355356 | 0.500000 | 0.002859 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.950100 | 0.166290 | 0.200000 | 0.190020 | 0.443439 | 0.500000 | 0.002291 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.818079 | 0.122256 | 0.200000 | 0.163616 | 0.326017 | 0.500000 | 0.003116 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.559967 | 0.282145 | 0.292000 | 0.163510 | 0.752385 | 0.500000 | 0.001350 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.620659 | 0.161154 | 0.200000 | 0.124132 | 0.429745 | 0.500000 | 0.002364 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.763457 | 0.206943 | 0.214000 | 0.163380 | 0.551847 | 0.500000 | 0.001841 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.639958 | 0.156284 | 0.200000 | 0.127992 | 0.416757 | 0.500000 | 0.002438 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.613913 | 0.257352 | 0.258000 | 0.158390 | 0.686272 | 0.500000 | 0.001480 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.719627 | 0.138991 | 0.200000 | 0.143925 | 0.370643 | 0.500000 | 0.002741 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.848699 | 0.186157 | 0.200000 | 0.169740 | 0.496420 | 0.500000 | 0.002047 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.743077 | 0.134596 | 0.200000 | 0.148615 | 0.358923 | 0.500000 | 0.002831 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25876.46 |
CORE_MID VAV BOX REHEAT COIL | 25036.03 |
CORE_TOP VAV BOX REHEAT COIL | 40288.06 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 20291.90 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13192.77 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 20132.53 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13289.59 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 14728.97 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9621.10 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 14600.10 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9705.38 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 15928.35 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10400.95 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 15787.75 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10484.39 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.70 | 1.35 | 5.40 | 1.88 | 4.87 | 4.87 | 0.300000 | 0.386172 | 4.87 |
PACU_VAV_MID | 2.50 | 1.37 | 5.00 | 2.29 | 4.33 | 4.33 | 0.300000 | 0.530216 | 4.33 |
PACU_VAV_TOP | 2.73 | 1.45 | 5.45 | 3.21 | 5.04 | 5.04 | 0.300000 | 0.636955 | 5.04 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.87 |
PACU_VAV_MID_OA_CONTROLLER | 4.33 |
PACU_VAV_TOP_OA_CONTROLLER | 5.04 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.87 | 108105.41 | 0.737388 | 1.62 | 36031.53 | 0.737388 |
PACU_VAV_MID COOLING COIL | 4.33 | 99937.13 | 0.724583 | 1.44 | 33309.04 | 0.724583 |
PACU_VAV_TOP COOLING COIL | 5.04 | 111402.06 | 0.739409 | 1.68 | 37130.31 | 0.739409 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 31934.96 |
PACU_VAV_MID HEATING COIL | 33224.61 |
PACU_VAV_TOP HEATING COIL | 32205.21 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.87 |
PACU_VAV_MID FAN | 4.33 |
PACU_VAV_TOP FAN | 5.04 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 32.411 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9320 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9163 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.269 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8390 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8573 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5538 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.27971961E-12 | 0.14534712E-14 | -0.84678956E-13 | 0.82684317E-16 |
43 | 6 | 0.26817376E-07 | 0.25687399E-09 | 0.61588016E-08 | -0.12527087E-12 |
44 | 5 | -0.18065003E-03 | 0.22251366E-05 | -0.93037841E-04 | 0.60936178E-08 |
45 | 4 | 0.28101542 | 0.10946024E-02 | 0.95683253E-01 | -0.32007147E-04 |
46 | 3 | -7.0457283 | 0.34231649E-01 | -2.2734647 | 0.27928366E-01 |
47 | 2 | 40.143429 | 0.12270019 | 14.996275 | -0.32523640 |
48 | 1 | -79.987958 | 0.55761501E-01 | -28.900564 | 1.0667320 |
49 | 0 | 46.824342 | 0.11295401E-02 | 16.297084 | |
50 | 7 | -0.28233695E-12 | 0.14433069E-14 | -0.85363548E-13 | 0.83491456E-16 |
51 | 6 | 0.27004714E-07 | 0.25312183E-09 | 0.62001510E-08 | -0.12627076E-12 |
52 | 5 | -0.18161011E-03 | 0.21898175E-05 | -0.93520278E-04 | 0.61339935E-08 |
53 | 4 | 0.28215201 | 0.10760039E-02 | 0.96091377E-01 | -0.32166146E-04 |
54 | 3 | -7.0682688 | 0.33616209E-01 | -2.2801509 | 0.28038740E-01 |
55 | 2 | 40.217804 | 0.12038787 | 15.023777 | -0.32606455 |
56 | 1 | -80.044990 | 0.54668782E-01 | -28.925243 | 1.0679473 |
57 | 0 | 46.824342 | 0.11065724E-02 | 16.296477 | |
58 | 6 | 0.22748378E-07 | 0.33059726E-09 | 0.52605359E-08 | -0.10371465E-12 |
59 | 5 | -0.15952455E-03 | 0.29533519E-05 | -0.82380770E-04 | 0.52144884E-08 |
60 | 4 | 0.25560578 | 0.14926938E-02 | 0.86578981E-01 | -0.28493712E-04 |
61 | 3 | -6.5408460 | 0.47808585E-01 | -2.1237636 | 0.25458881E-01 |
62 | 2 | 38.476406 | 0.17496760 | 14.378110 | -0.30668036 |
63 | 1 | -78.708466 | 0.80951212E-01 | -28.345189 | 1.0394692 |
64 | 0 | 46.824351 | 0.16689207E-02 | 16.311239 | |
65 | 7 | -0.18042418E-08 | -0.42925973E-15 | 0.63337540E-14 | -0.83764910E-16 |
66 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
67 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
68 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
69 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
70 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
71 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
72 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
73 | 7 | -0.17078159E-08 | -0.36552483E-15 | 0.71259391E-14 | -0.98899249E-16 |
74 | 6 | 0.68798867E-05 | 0.47165251E-08 | 0.31862110E-02 | -0.26728608E-04 |
75 | 5 | -0.49558197E-03 | 0.27953368E-05 | -0.22351660 | 0.19543146E-02 |
76 | 4 | 0.11404824E-01 | 0.12725100E-03 | 4.8260817 | -0.45231683E-01 |
77 | 3 | -0.10016651 | 0.10121065E-02 | -38.001848 | 0.39843745 |
78 | 2 | 0.35569192 | 0.16837830E-02 | 116.44586 | -1.4174299 |
79 | 1 | -0.51340120 | 0.51323984E-03 | -143.88489 | 2.0486714 |
80 | 0 | 0.25031121 | 0.12359947E-04 | 60.838472 | |
81 | 7 | -0.18042418E-08 | -0.42925997E-15 | 0.63337541E-14 | -0.83764912E-16 |
82 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
83 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
84 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
85 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
86 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
87 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
88 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
89 | 7 | -0.17076967E-08 | -0.36446083E-15 | 0.71390403E-14 | -0.94439575E-16 |
90 | 6 | 0.68803475E-05 | 0.47168467E-08 | 0.31862096E-02 | -0.26728597E-04 |
91 | 5 | -0.49561596E-03 | 0.27955299E-05 | -0.22351653 | 0.19543140E-02 |
92 | 4 | 0.11405612E-01 | 0.12725979E-03 | 4.8260805 | -0.45231671E-01 |
93 | 3 | -0.10017344 | 0.10121766E-02 | -38.001841 | 0.39843738 |
94 | 2 | 0.35571654 | 0.16838995E-02 | 116.44585 | -1.4174297 |
95 | 1 | -0.51343675 | 0.51327568E-03 | -143.88488 | 2.0486713 |
96 | 0 | 0.25032854 | 0.12360692E-04 | 60.838472 | |
97 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
98 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
99 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
100 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
101 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
102 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
103 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
104 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
105 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3822_SHGC_EAST_0.36 | 35 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.361 | ||
2 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 36 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.361 | ||
3 | WINDOW_U_0.3822_SHGC_WEST_0.36 | 37 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.361 | ||
4 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 38 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.43662E-002 | 0.27318 | 0.51756 | 0.51756 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.43662E-002 | 0.27318 | 0.51756 | 0.51756 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.43662E-002 | 0.27318 | 0.51756 | 0.51756 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.43662E-002 | 0.27318 | 0.51756 | 0.51756 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.2828E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.3386E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0175E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0224E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.5182E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5574E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4493E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4697E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1333 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9495E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1510 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7972E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.7367E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1131E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.0047E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5019E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.2827E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.3409E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0175E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0226E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.5183E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5592E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4490E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4695E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6904E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3586E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2991E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0648E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.7194E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8825E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6599E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1796E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1464E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.1678E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8288E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8442E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7054E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7107E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0258E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0328E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6021E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6494E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0121E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0497E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6306E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6576E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4490E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4695E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3948E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9984E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6206E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5220E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5234E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0704E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0047E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5019E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6022E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6496E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0121E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0495E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6304E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6563E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4493E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4697E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4403E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2375E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9893E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9143E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5058E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7822E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6599E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1796E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0033E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0647E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6509E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7181E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.5852E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.6108E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0259E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0329E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1303 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 8.2511E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1449 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.2006E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1025 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.1280E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.5023E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.0890E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.4717E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.2368E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1056E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9578E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.5527E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7926E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.5485E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1197E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8483E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.5809E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0272E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0248E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.9290E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5358E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.5023E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0890E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.2314E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.1227E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8079E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.8160E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.3469E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6974E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.5485E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1197E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1303 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 8.2503E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1449 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.1997E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1025 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.1274E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.5020E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.0887E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.4718E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.2366E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1056E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9576E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.5524E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7923E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.5481E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1194E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8485E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.5808E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0273E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0248E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.9289E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5356E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.5020E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0887E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.2314E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.1225E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8079E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.8159E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.3467E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6972E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.5482E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1195E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 39102.74015 | 39102.74015 | 2.81868 | 2.81868 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 8567.46809 | 8567.46809 | 0.36074 | 0.42469 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 28854.65668 | 28854.65668 | 2.07745 | 2.07745 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 16967.11151 | 16967.11151 | 0.71921 | 0.71921 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 30582.91409 | 30582.91409 | 2.22308 | 2.22308 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 32.10000 | 1.41196E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 28364.62500 | 28364.62500 | 1.20684 | 1.20684 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9777.25595 | 9777.25595 | 0.71078 | 0.71078 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 14246.41588 | 14246.41588 | 0.60785 | 0.60785 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10324.85208 | 10324.85208 | 0.75058 | 0.75058 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.65900 | 1.41134E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 9261.83000 | 9261.83000 | 0.39519 | 0.39519 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13069.33575 | 13069.33575 | 0.95010 | 0.95010 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 14134.77583 | 14134.77583 | 0.60308 | 0.60308 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11253.31757 | 11253.31757 | 0.81808 | 0.81808 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 9329.64810 | 9329.64810 | 0.39809 | 0.39809 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7703.07397 | 7703.07397 | 0.55997 | 0.55997 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 10348.13240 | 10348.13240 | 0.44121 | 0.44121 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8538.02279 | 8538.02279 | 0.62066 | 0.62066 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 28.86867 | 1.41138E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 6758.89056 | 6758.89056 | 0.28820 | 0.28820 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10502.38382 | 10502.38382 | 0.76346 | 0.76346 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.91500 | 1.41193E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 10257.87736 | 10257.87736 | 0.43735 | 0.43735 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8803.52313 | 8803.52313 | 0.63996 | 0.63996 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.06400 | 1.41178E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 6817.91355 | 6817.91355 | 0.29073 | 0.29073 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8444.91871 | 8444.91871 | 0.61391 | 0.61391 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 11189.19479 | 11189.19479 | 0.47714 | 0.47714 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9899.17293 | 9899.17293 | 0.71963 | 0.71963 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 28.23967 | 1.41127E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 7305.77613 | 7305.77613 | 0.31156 | 0.31156 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11674.66213 | 11674.66213 | 0.84870 | 0.84870 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 31.79167 | 1.41191E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 11090.71975 | 11090.71975 | 0.47293 | 0.47293 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10221.76378 | 10221.76378 | 0.74308 | 0.74308 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 7364.22334 | 7364.22334 | 0.31406 | 0.31406 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 77723.04 | 4.87394 | 4.87394 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 33658.70 | 1.88218 | 1.88218 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 70324.57 | 4.32824 | 4.32824 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 33736.56 | 2.29490 | 2.29490 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 79961.36 | 5.04126 | 5.04126 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 33926.16 | 3.21105 | 3.21105 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.81868 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26589 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27500 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77514 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70904 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.43293E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25876.46345 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.07745 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36076 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36100 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.74996 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96202 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05611E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25036.02947 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.22308 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33712 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35200 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78253 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89900 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13015E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 40288.06240 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71078 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22228 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23200 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16490 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59275 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.71406E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20291.90214 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75058 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13326 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15012 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35536 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.85910E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13192.76892 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95010 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16629 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19002 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44344 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.29118E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20132.52742 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81808 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12226 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16362 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32602 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.11641E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13289.58585 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.55997 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28214 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16351 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75239 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.35037E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14728.97029 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62066 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16115 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12413 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42974 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.36419E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9621.09923 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76346 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20694 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21400 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16338 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55185 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.84109E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14600.09616 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63996 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15628 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12799 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41676 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.43787E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9705.37717 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61391 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25735 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25800 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15839 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68627 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.48046E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15928.34657 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71963 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13899 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14393 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37064 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.74118E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10400.94822 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84870 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18616 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16974 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49642 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.04665E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15787.75417 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74308 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13460 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14862 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35892 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.83069E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10484.39446 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.70136 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.35415 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.40272 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.88218 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.87394 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.87394 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.38617 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.50139 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.37063 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.00277 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.29490 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.32824 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.32824 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.53022 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.72631 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.45118 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.45263 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.21105 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.04126 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.04126 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.63695 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.87394 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.32824 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.04126 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.87394 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.87394 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 108105.40952 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73739 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.62448 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 36031.53299 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73739 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 31934.96145 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.87394 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.32824 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.32824 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 99937.12596 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.72458 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.44260 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 33309.04408 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.72458 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 33224.61451 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.32824 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.04126 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.04126 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 111402.05902 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73941 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.68025 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37130.30627 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73941 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 32205.20515 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.04126 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 107526.32 | 366895.02 | 11.43 | 2.93 | 3.27 | 3.45 | 3.60 | 9.99 | 11.17 | 11.77 | 12.27 | 5.6346 | 4.4755 | 3.0175 | 1.2537 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 99538.99 | 339641.15 | 11.51 | 2.94 | 3.30 | 3.48 | 3.61 | 10.05 | 11.25 | 11.86 | 12.33 | 5.0037 | 3.9785 | 2.6749 | 1.1247 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 110790.86 | 378034.09 | 11.42 | 2.93 | 3.27 | 3.45 | 3.60 | 9.99 | 11.16 | 11.76 | 12.27 | 5.8280 | 4.6380 | 3.1236 | 1.2930 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.36 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.36 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.36 | N/A | 2.171 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.36 | N/A | 2.171 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.246 | 0.232 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.36 | N/A | 2.171 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.36 | N/A | 2.171 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.246 | 0.232 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.36 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.36 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.2902786116E-002 | 2.6281252981E-002 | Pass | Pass | 0.4866636000 | 0.4936273197 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1961310855 | 0.1429369892 | Pass | Pass | 0.4936044604 | 0.4897531172 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1042114905 | 6.6821381879E-002 | Pass | Pass | 0.4851766042 | 0.4850737926 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.7861805311E-002 | 6.1561946395E-002 | Pass | Pass | 0.4849038175 | 0.4822242735 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 8.2983816580E-003 | 7.8313812581E-003 | Pass | Pass | 1.3397072760 | 7.8341359203 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1300326403 | 0.1377472630 | Pass | Pass | 1.4650713525 | 7.2517070468 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6902405857 | 0.5972621962 | Pass | Pass | 0.6885417052 | 0.5976982119 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6308350190 | 0.6437317245 | Pass | Pass | 0.7648785245 | 0.7962808671 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5144898571 | 0.5825328739 | Pass | Pass | 0.8703880832 | 1.3148180522 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6912835263 | 0.6781334173 | Pass | Pass | 0.7495876051 | 0.7822881784 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4325749688 | 0.3987132669 | Pass | Pass | 1.5394846326 | 9.6521862164 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3550074772 | 0.4033294083 | Pass | Pass | 0.8420818853 | 1.0572871081 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2586382344 | 0.3014619694 | Pass | Pass | 0.7083420327 | 0.7556386984 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4251957268 | 0.4320498584 | Pass | Pass | 1.1904330811 | 5.3630918078 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5189614388 | 0.4649531185 | Pass | Pass | 0.7273284720 | 0.6411768558 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4639762499 | 0.5039392561 | Pass | Pass | 17.9230439750 | 204.7028100040 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3800869641 | 0.4299806874 | Pass | Pass | 0.9566395752 | 2.3044352553 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5210990704 | 0.5203283674 | Pass | Pass | 0.7966964882 | 0.8516652657 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3628.51 | 141.81 | 0.00 | 1487.39 | 1142.71 | 6400.43 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.36 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.36 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3822_SHGC_EAST_0.36 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3822_SHGC_EAST_0.36 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3822_SHGC_WEST_0.36 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3822_SHGC_WEST_0.36 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.36 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.36 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.171 | 0.361 | 0.361 | |||||||||||||||||
North Total or Average | 177.99 | 2.171 | 0.361 | 0.361 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.171 | 0.361 | 0.361 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.50 | 0.0000 | Y | 9.29 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.48 | 0.0000 | Y | 5.88 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.30 | 0.0000 | Y | 9.23 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.33 | 0.0000 | Y | 5.85 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.46 | 0.0000 | Y | 9.28 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.45 | 0.0000 | Y | 5.87 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.27 | 0.0000 | Y | 9.22 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.30 | 0.0000 | Y | 5.84 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.50 | 0.0000 | Y | 9.29 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.48 | 0.0000 | Y | 5.88 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.30 | 0.0000 | Y | 9.23 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.33 | 0.0000 | Y | 5.85 |
Interior Lighting Total | 7.5763 | 4982.19 | 37746.71 | 281.15 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 42.43 | 42.43 | 3.38 | |
EXTERIOR_LIGHTS_B | 5132.60 | AstronomicalClock | - | 83.64 | 71.28 | 68.68 | |
Exterior Lighting Total | 5557.43 | 72.06 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 108105.41 | 79715.61 | 28389.80 | 0.74 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 99937.13 | 72412.70 | 27524.42 | 0.72 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 111402.06 | 82371.65 | 29030.41 | 0.74 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 107526.3 | 2.93 | 9.99 | N/A | N/A | 11.43 | |
PACU_VAV_MID COOLING COIL | 99539.0 | 2.94 | 10.05 | N/A | N/A | 11.51 | |
PACU_VAV_TOP COOLING COIL | 110790.9 | 2.93 | 9.99 | N/A | N/A | 11.42 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25876.46 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 25036.03 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 40288.06 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20291.90 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13192.77 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20132.53 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13289.59 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14728.97 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9621.10 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14600.10 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9705.38 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15928.35 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10400.95 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15787.75 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10484.39 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 31934.96 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 33224.61 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 32205.21 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.87 | 10669.11 | 2189.01 | 1.00 | 1.13 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.33 | 10012.90 | 2313.39 | 1.00 | 1.14 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.04 | 10964.17 | 2174.89 | 1.00 | 1.14 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 107526.32 | 2.93 | 9.99 | 11.43 | 5.6346 | 3.27 | 11.17 | 4.4755 | 3.45 | 11.77 | 3.0175 | 3.60 | 12.27 | 1.2537 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 99538.99 | 2.94 | 10.05 | 11.51 | 5.0037 | 3.30 | 11.25 | 3.9785 | 3.48 | 11.86 | 2.6749 | 3.61 | 12.33 | 1.1247 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 110790.86 | 2.93 | 9.99 | 11.42 | 5.8280 | 3.27 | 11.16 | 4.6380 | 3.45 | 11.76 | 3.1236 | 3.60 | 12.27 | 1.2930 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 39102.74 | 39102.74 | 39.76 | 2.819 | 2.819 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00881 | 26.62 | 0.01411 | 0.425 | 0.00 |
CORE_MID | 28854.66 | 28854.66 | 29.34 | 2.077 | 2.077 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 26.62 | 0.01411 | 0.425 | 0.00 |
CORE_TOP | 30582.91 | 30582.91 | 31.09 | 2.223 | 2.223 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00889 | 32.10 | 0.01412 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9777.26 | 9777.26 | 47.16 | 0.711 | 0.711 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00905 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10324.85 | 10324.85 | 78.66 | 0.751 | 0.751 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00885 | 28.66 | 0.01411 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13069.34 | 13069.34 | 63.03 | 0.950 | 0.950 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00891 | 31.85 | 0.01412 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11253.32 | 11253.32 | 85.74 | 0.818 | 0.818 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00882 | 31.26 | 0.01412 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7703.07 | 7703.07 | 37.15 | 0.560 | 0.560 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00902 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8538.02 | 8538.02 | 65.05 | 0.621 | 0.621 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00881 | 28.87 | 0.01411 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10502.38 | 10502.38 | 50.65 | 0.763 | 0.763 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00889 | 31.92 | 0.01412 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8803.52 | 8803.52 | 67.07 | 0.640 | 0.640 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00880 | 31.06 | 0.01412 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8444.92 | 8444.92 | 40.73 | 0.614 | 0.614 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00907 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9899.17 | 9899.17 | 75.42 | 0.720 | 0.720 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00883 | 28.24 | 0.01411 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11674.66 | 11674.66 | 56.31 | 0.849 | 0.849 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00892 | 31.79 | 0.01412 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10221.76 | 10221.76 | 77.88 | 0.743 | 0.743 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00882 | 31.26 | 0.01412 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 8567.47 | 8567.47 | 8.71 | 0.361 | 0.425 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
CORE_MID | 16967.11 | 16967.11 | 17.25 | 0.719 | 0.719 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
CORE_TOP | 28364.62 | 28364.62 | 28.84 | 1.207 | 1.207 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 14246.42 | 14246.42 | 68.71 | 0.608 | 0.608 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00737 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9261.83 | 9261.83 | 70.56 | 0.395 | 0.395 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00736 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 14134.78 | 14134.78 | 68.17 | 0.603 | 0.603 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00737 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9329.65 | 9329.65 | 71.08 | 0.398 | 0.398 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00736 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 10348.13 | 10348.13 | 49.91 | 0.441 | 0.441 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 6758.89 | 6758.89 | 51.49 | 0.288 | 0.288 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00749 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10257.88 | 10257.88 | 49.47 | 0.437 | 0.437 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00749 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 6817.91 | 6817.91 | 51.94 | 0.291 | 0.291 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 11189.19 | 11189.19 | 53.97 | 0.477 | 0.477 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00733 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 7305.78 | 7305.78 | 55.66 | 0.312 | 0.312 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00732 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11090.72 | 11090.72 | 53.49 | 0.473 | 0.473 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00732 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 7364.22 | 7364.22 | 56.11 | 0.314 | 0.314 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00732 | -10.70 | 0.00150 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.87 | 4.87 | 1.88 | 1.88 | 4.8739 | 1.8822 | 4.8739 | 0.3862 | 0.3000 |
PACU_VAV_MID | 4.33 | 4.33 | 2.29 | 2.29 | 4.3282 | 2.2949 | 4.3282 | 0.5302 | 0.3000 |
PACU_VAV_TOP | 5.04 | 5.04 | 3.21 | 3.21 | 5.0413 | 3.2111 | 5.0413 | 0.6370 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25876.463 | 25876.463 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25876.46 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 8567.47 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 25036.029 | 25036.029 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25036.03 | 24009.56 | 0.719213 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 16967.11 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 40288.062 | 40288.062 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40288.06 | 40288.06 | 1.206840 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 28364.62 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 20291.902 | 20291.902 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20291.90 | 20291.90 | 0.607850 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00737291 | 47.6984 | 14246.42 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 13192.769 | 13192.769 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13192.77 | 13192.77 | 0.395193 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00735896 | 47.6096 | 9261.83 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 20132.527 | 20132.527 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20132.53 | 20132.53 | 0.603075 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00736832 | 47.6691 | 14134.78 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 13289.586 | 13289.586 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13289.59 | 13289.59 | 0.398093 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00736325 | 47.6370 | 9329.65 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 14728.970 | 14728.970 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14728.97 | 14728.97 | 0.441210 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00749805 | 48.4948 | 10348.13 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 9621.099 | 9621.099 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9621.10 | 9621.10 | 0.288203 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00749443 | 48.4718 | 6758.89 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 14600.096 | 14600.096 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14600.10 | 14600.10 | 0.437350 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00749208 | 48.4567 | 10257.88 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 9705.377 | 9705.377 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9705.38 | 9705.38 | 0.290727 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00749995 | 48.5070 | 6817.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 15928.347 | 15928.347 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15928.35 | 15928.35 | 0.477138 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00732644 | 47.4003 | 11189.19 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 10400.948 | 10400.948 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10400.95 | 10400.95 | 0.311563 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00731663 | 47.3378 | 7305.78 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 15787.754 | 15787.754 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15787.75 | 15787.75 | 0.472927 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00732029 | 47.3609 | 11090.72 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 10484.394 | 10484.394 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10484.39 | 10484.39 | 0.314063 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00732209 | 47.3727 | 7364.22 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 108105.410 | 79715.606 | 4.873940 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 110771.47 | 85964.25 | 4.873940 | 25.99 | 18.44 | 0.01016302 | 11.02 | 11.02 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 24.5216 | 24.00 | 0.00887759 | 47.7418 | 67049.22 | 0.00 | 111471.19 | 80966.08 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 31934.961 | 31934.961 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 31934.96 | 31934.96 | 1.462182 | -5.26 | -5.26 | 0.00255337 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 81.7388 | 19.60 | 0.00689520 | 48.6694 | 21922.99 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 99937.126 | 72412.702 | 4.328243 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 103035.95 | 77880.11 | 4.328243 | 26.24 | 18.70 | 0.01039350 | 10.92 | 10.92 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 27.6133 | 24.00 | 0.00897188 | 48.2424 | 59534.16 | 0.00 | 103048.59 | 73597.23 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 33224.615 | 33224.615 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33224.61 | 33224.61 | 1.298473 | -8.36 | -8.36 | 0.00194995 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 92.0443 | 19.39 | 0.00683056 | 48.8624 | 25294.38 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 111402.059 | 82371.647 | 5.041257 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 114086.34 | 88485.45 | 5.041257 | 25.92 | 18.41 | 0.01015983 | 11.03 | 11.03 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 23.7078 | 24.00 | 0.00892870 | 48.0137 | 69322.20 | 0.00 | 114870.48 | 83672.50 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 32205.205 | 32205.205 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 32205.21 | 32205.21 | 1.512377 | -4.81 | -4.81 | 0.00267684 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 79.0259 | 17.60 | 0.00681777 | 54.5505 | 26821.03 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25876.463 | 25876.463 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25876.46 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25876.46 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.90 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 8567.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 25036.029 | 25036.029 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25036.03 | 24009.56 | 1.0000 | 0.86564125 | 0.719213 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25036.03 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 16967.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 40288.062 | 40288.062 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 40288.06 | 40288.06 | 1.0000 | 1.45254674 | 1.206840 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40288.06 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 28364.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 20291.902 | 20291.902 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20291.90 | 20291.90 | 1.0000 | 0.73160471 | 0.607850 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20291.90 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00737291 | 21.00 | 0.00737291 | 47.6984 | 14246.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 13192.769 | 13192.769 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13192.77 | 13192.77 | 1.0000 | 0.47565240 | 0.395193 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13192.77 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00735896 | 21.00 | 0.00735896 | 47.6096 | 9261.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 20132.527 | 20132.527 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20132.53 | 20132.53 | 1.0000 | 0.72585861 | 0.603075 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20132.53 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00736832 | 21.00 | 0.00736832 | 47.6691 | 14134.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 13289.586 | 13289.586 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13289.59 | 13289.59 | 1.0000 | 0.47914304 | 0.398093 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13289.59 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00736325 | 21.00 | 0.00736325 | 47.6370 | 9329.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 14728.970 | 14728.970 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14728.97 | 14728.97 | 1.0000 | 0.53103864 | 0.441210 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14728.97 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00749805 | 21.00 | 0.00749805 | 48.4948 | 10348.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9621.099 | 9621.099 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9621.10 | 9621.10 | 1.0000 | 0.34687934 | 0.288203 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9621.10 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00749443 | 21.00 | 0.00749443 | 48.4718 | 6758.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 14600.096 | 14600.096 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14600.10 | 14600.10 | 1.0000 | 0.52639221 | 0.437350 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14600.10 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00749208 | 21.00 | 0.00749208 | 48.4567 | 10257.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9705.377 | 9705.377 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9705.38 | 9705.38 | 1.0000 | 0.34991790 | 0.290727 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9705.38 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00749995 | 21.00 | 0.00749995 | 48.5070 | 6817.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 15928.347 | 15928.347 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15928.35 | 15928.35 | 1.0000 | 0.57428098 | 0.477138 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15928.35 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00732644 | 21.00 | 0.00732644 | 47.4003 | 11189.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10400.948 | 10400.948 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10400.95 | 10400.95 | 1.0000 | 0.37499603 | 0.311563 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10400.95 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00731663 | 21.00 | 0.00731663 | 47.3378 | 7305.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 15787.754 | 15787.754 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15787.75 | 15787.75 | 1.0000 | 0.56921206 | 0.472927 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15787.75 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00732029 | 21.00 | 0.00732029 | 47.3609 | 11090.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10484.394 | 10484.394 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10484.39 | 10484.39 | 1.0000 | 0.37800460 | 0.314063 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10484.39 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00732209 | 21.00 | 0.00732209 | 47.3727 | 7364.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 108105.410 | 79715.606 | 4.873940 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7326 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.873940 | 5.86625021 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 110771.47 | 85964.25 | 1.0247 | 5.86625021 | 4.873940 | 25.99 | 18.44 | 0.01016302 | 52018.9 | 11.02 | 11.02 | 0.00850000 | 32509.0 | -999.0 | -999.00 | -999.00 | -999.00 | 10669.109 | 100102.36 | 32.10 | 0.01411964 | 23.13 | 1.19517000 | 24.5216 | 24.00 | 0.00887759 | 24.00 | 0.00887759 | 47.7418 | 67049.22 | 0.00 | 111471.19 | 80966.08 | 5.63457767 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.60 | 12.58 | 0.00906199 | 35539.0 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31934.961 | 31934.961 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.873940 | 5.86625021 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 31934.96 | 31934.96 | 1.0000 | 1.75987506 | 1.462182 | -5.26 | -5.26 | 0.00255337 | 1077.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31934.96 | -10.70 | 0.00150390 | -10.70 | 1.19517000 | 81.7388 | 19.10 | 0.00725092 | 19.60 | 0.00689520 | 48.6694 | 21922.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 99937.126 | 72412.702 | 4.328243 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1610 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.328243 | 5.20945151 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 103035.95 | 77880.11 | 1.0310 | 5.20945151 | 4.328243 | 26.24 | 18.70 | 0.01039350 | 52863.1 | 10.92 | 10.92 | 0.00850000 | 32406.7 | -999.0 | -999.00 | -999.00 | -999.00 | 10012.899 | 93023.05 | 32.10 | 0.01411964 | 23.13 | 1.19517000 | 27.6133 | 24.00 | 0.00897188 | 24.00 | 0.00897188 | 48.2424 | 59534.16 | 0.00 | 103048.59 | 73597.23 | 5.00371755 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.27 | 12.26 | 0.00887693 | 34728.0 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33224.615 | 33224.615 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.328243 | 5.20945151 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 33224.61 | 33224.61 | 1.0000 | 1.56283545 | 1.298473 | -8.36 | -8.36 | 0.00194995 | -3550.4 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33224.61 | -10.70 | 0.00150390 | -10.70 | 1.19517000 | 92.0443 | 18.76 | 0.00711055 | 19.39 | 0.00683056 | 48.8624 | 25294.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 111402.059 | 82371.647 | 5.041257 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7266 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.041257 | 6.06763186 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 114086.34 | 88485.45 | 1.0241 | 6.06763186 | 5.041257 | 25.92 | 18.41 | 0.01015983 | 51943.8 | 11.03 | 11.03 | 0.00850000 | 32520.6 | -999.0 | -999.00 | -999.00 | -999.00 | 10964.171 | 103122.17 | 32.10 | 0.01411964 | 23.13 | 1.19517000 | 23.7078 | 24.00 | 0.00892870 | 24.00 | 0.00892870 | 48.0137 | 69322.20 | 0.00 | 114870.48 | 83672.50 | 5.82800627 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.62 | 12.60 | 0.00908583 | 35612.3 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32205.205 | 32205.205 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.041257 | 6.06763186 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 32205.21 | 32205.21 | 1.0000 | 1.82028956 | 1.512377 | -4.81 | -4.81 | 0.00267684 | 1840.6 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32205.21 | -10.70 | 0.00150390 | -10.70 | 1.19517000 | 79.0259 | 17.40 | 0.00709624 | 17.60 | 0.00681777 | 54.5505 | 26821.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.87 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.33 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 5.04 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2495.67 | 2527.83 | 61.83 |
CORE_MID | 2504.50 | 3217.83 | 485.17 |
CORE_TOP | 2997.67 | 3498.17 | 1186.33 |
PERIMETER_TOP_ZN_3 | 3849.67 | 3827.00 | 2176.50 |
PERIMETER_TOP_ZN_2 | 3844.67 | 3698.50 | 1975.67 |
PERIMETER_TOP_ZN_1 | 3581.83 | 3429.17 | 1620.67 |
PERIMETER_TOP_ZN_4 | 3776.83 | 3771.00 | 2016.50 |
PERIMETER_BOT_ZN_3 | 3529.83 | 3776.67 | 1840.17 |
PERIMETER_BOT_ZN_2 | 3510.50 | 3430.00 | 1489.33 |
PERIMETER_BOT_ZN_1 | 3456.17 | 3795.50 | 1737.17 |
PERIMETER_BOT_ZN_4 | 3579.67 | 3492.67 | 1583.00 |
PERIMETER_MID_ZN_3 | 3551.67 | 3598.00 | 1724.17 |
PERIMETER_MID_ZN_2 | 3029.00 | 3054.17 | 1425.50 |
PERIMETER_MID_ZN_1 | 3357.50 | 3141.33 | 1197.67 |
PERIMETER_MID_ZN_4 | 3553.33 | 3518.83 | 1594.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4992.00 | 4514.50 | 2695.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.50 | 1.33 | 0.50 | 0.00 |
CORE_MID | 2.50 | 0.17 | 2.00 | 0.00 |
CORE_TOP | 3.17 | 0.00 | 2.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 55.50 | 4.17 | 22.33 | 3.50 |
PERIMETER_TOP_ZN_2 | 41.17 | 26.50 | 7.83 | 26.00 |
PERIMETER_TOP_ZN_1 | 30.00 | 26.17 | 5.67 | 25.33 |
PERIMETER_TOP_ZN_4 | 42.83 | 24.00 | 10.83 | 17.00 |
PERIMETER_BOT_ZN_3 | 18.50 | 0.00 | 10.83 | 0.00 |
PERIMETER_BOT_ZN_2 | 7.17 | 13.33 | 1.50 | 13.33 |
PERIMETER_BOT_ZN_1 | 353.67 | 49.17 | 348.50 | 48.67 |
PERIMETER_BOT_ZN_4 | 8.67 | 13.67 | 2.67 | 10.17 |
PERIMETER_MID_ZN_3 | 20.50 | 0.33 | 8.83 | 0.33 |
PERIMETER_MID_ZN_2 | 13.17 | 20.67 | 2.33 | 20.67 |
PERIMETER_MID_ZN_1 | 10.83 | 21.00 | 2.00 | 20.67 |
PERIMETER_MID_ZN_4 | 14.00 | 20.67 | 3.33 | 15.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 405.17 | 131.17 | 363.17 | 118.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.74 | 52.94 | 2698.04 | 0.810 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.74 | 52.94 | 2698.04 | 0.597 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.74 | 52.94 | 2698.04 | 0.594 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.58 | 11.16 | 568.77 | 0.671 | 0.106 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 1.016 | 0.112 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.58 | 11.16 | 568.77 | 0.988 | 0.106 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 1.068 | 0.112 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.58 | 11.16 | 568.77 | 0.592 | 0.057 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 0.851 | 0.060 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.58 | 11.16 | 568.77 | 0.808 | 1.332 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 0.851 | 0.060 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.58 | 11.16 | 568.77 | 0.662 | 0.089 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 0.923 | 0.099 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.58 | 11.16 | 568.77 | 0.966 | 0.089 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 1.022 | 0.093 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.74 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.74 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.74 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.74 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.74 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.74 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.54 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.75 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 12885462.36 | 0.00 | 12885462.36 | 0.00 | 12885462.36 | 13393058.27 | 5543.61 | 424.88 | 2791.51 | 66.51 |
CORE_MID | 9470935.98 | 0.00 | 9470935.98 | 0.00 | 9470935.98 | 13393058.27 | 6945.84 | 38.92 | 1775.24 | 67.20 |
CORE_TOP | 9408601.77 | 0.00 | 9408601.77 | 0.00 | 9408601.77 | 13393058.27 | 6955.74 | 31.89 | 1772.37 | 68.33 |
PERIMETER_TOP_ZN_3 | 2238870.92 | 0.00 | 2238870.92 | 696839.46 | 2935710.39 | 2823374.22 | 5895.51 | 55.18 | 2809.31 | 68.33 |
PERIMETER_TOP_ZN_2 | 2146947.82 | 0.00 | 2146947.82 | 464556.85 | 2611504.67 | 1787429.43 | 4220.86 | 4.40 | 4534.74 | 68.28 |
PERIMETER_TOP_ZN_1 | 3293301.73 | 0.00 | 3293301.73 | 696839.46 | 3990141.20 | 2823374.22 | 4250.27 | 13.00 | 4496.73 | 68.33 |
PERIMETER_TOP_ZN_4 | 2258444.14 | 0.00 | 2258444.14 | 464556.85 | 2723000.99 | 1787312.18 | 4239.37 | 10.12 | 4510.51 | 68.33 |
PERIMETER_BOT_ZN_3 | 1996369.58 | 0.00 | 1996369.58 | 370505.73 | 2366875.31 | 2823374.22 | 6271.44 | 457.21 | 2031.35 | 66.51 |
PERIMETER_BOT_ZN_2 | 1811167.43 | 0.00 | 1811167.43 | 247002.33 | 2058169.76 | 1787429.43 | 4324.57 | 52.97 | 4382.46 | 66.51 |
PERIMETER_BOT_ZN_1 | 2717417.07 | 0.00 | 2717417.07 | 4635841.98 | 7353259.05 | 2823374.22 | 5247.40 | 382.21 | 3130.39 | 66.51 |
PERIMETER_BOT_ZN_4 | 1810628.71 | 0.00 | 1810628.71 | 247002.33 | 2057631.05 | 1787312.18 | 4401.62 | 47.66 | 4310.71 | 66.51 |
PERIMETER_MID_ZN_3 | 2212757.93 | 0.00 | 2212757.93 | 580065.25 | 2792823.18 | 2823374.22 | 5955.35 | 56.12 | 2748.53 | 67.20 |
PERIMETER_MID_ZN_2 | 2114130.85 | 0.00 | 2114130.85 | 386707.84 | 2500838.69 | 1787429.43 | 4200.45 | 6.87 | 4552.68 | 976.20 |
PERIMETER_MID_ZN_1 | 3222309.70 | 0.00 | 3222309.70 | 580065.25 | 3802374.94 | 2823374.22 | 4247.38 | 20.69 | 4491.93 | 67.20 |
PERIMETER_MID_ZN_4 | 2162806.43 | 0.00 | 2162806.43 | 386707.84 | 2549514.27 | 1787312.18 | 4211.89 | 12.65 | 4535.46 | 67.20 |
Total Facility | 59750152.44 | 0.00 | 59750152.44 | 9756691.16 | 69506843.61 | 67843644.98 | 7127.06 | 770.22 | 4652.29 | 1062.38 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.5950 | 0.0000 | 0.5950 | 0.0000 | 0.5950 | 0.4247 | 2773.26 | 424.88 | 2744.86 |
CORE_MID | 0.4391 | 0.0000 | 0.4391 | 0.0000 | 0.4391 | 0.4247 | 4150.66 | 38.92 | 1753.42 |
CORE_TOP | 0.4372 | 0.0000 | 0.4372 | 0.0000 | 0.4372 | 0.4247 | 4154.08 | 31.89 | 1757.03 |
PERIMETER_TOP_ZN_3 | 0.1041 | 0.0000 | 0.1041 | 0.0166 | 0.1207 | 0.0895 | 3093.84 | 55.18 | 2793.98 |
PERIMETER_TOP_ZN_2 | 0.0999 | 0.0000 | 0.0999 | 0.0111 | 0.1109 | 0.0567 | 1419.19 | 4.40 | 4519.41 |
PERIMETER_TOP_ZN_1 | 0.1533 | 0.0000 | 0.1533 | 0.0166 | 0.1699 | 0.0895 | 1448.60 | 13.00 | 4481.40 |
PERIMETER_TOP_ZN_4 | 0.1050 | 0.0000 | 0.1050 | 0.0111 | 0.1161 | 0.0567 | 1437.71 | 10.12 | 4495.18 |
PERIMETER_BOT_ZN_3 | 0.0920 | 0.0000 | 0.0920 | 0.0088 | 0.1008 | 0.0895 | 3501.10 | 457.21 | 1984.70 |
PERIMETER_BOT_ZN_2 | 0.0837 | 0.0000 | 0.0837 | 0.0059 | 0.0895 | 0.0567 | 1554.30 | 52.95 | 4335.75 |
PERIMETER_BOT_ZN_1 | 0.1257 | 0.0000 | 0.1257 | 0.2082 | 0.3339 | 0.0895 | 2477.05 | 382.21 | 3083.74 |
PERIMETER_BOT_ZN_4 | 0.0836 | 0.0000 | 0.0836 | 0.0059 | 0.0895 | 0.0567 | 1631.30 | 47.66 | 4264.03 |
PERIMETER_MID_ZN_3 | 0.1027 | 0.0000 | 0.1027 | 0.0138 | 0.1165 | 0.0895 | 3160.17 | 56.12 | 2726.71 |
PERIMETER_MID_ZN_2 | 0.0907 | 0.0000 | 0.0907 | 0.0098 | 0.1005 | 0.0567 | 1396.81 | 5.52 | 3631.67 |
PERIMETER_MID_ZN_1 | 0.1499 | 0.0000 | 0.1499 | 0.0138 | 0.1637 | 0.0895 | 1452.20 | 20.69 | 4470.11 |
PERIMETER_MID_ZN_4 | 0.1004 | 0.0000 | 0.1004 | 0.0092 | 0.1096 | 0.0567 | 1416.77 | 12.63 | 4513.60 |
Total Facility | 2.7623 | 0.0000 | 2.7623 | 0.3308 | 3.0931 | 2.1513 | 4317.64 | 770.15 | 4596.37 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 30741666.09 | 0.00 | 30741666.09 | 22614548.33 | 4155.81 | 5.36 | 4598.83 | 66.51 |
PACU_VAV_MID | 27789204.64 | 0.00 | 27789204.64 | 22614548.33 | 4176.50 | 2.33 | 4581.17 | 67.20 |
PACU_VAV_TOP | 28025648.02 | 0.00 | 28025648.02 | 22614548.33 | 4209.87 | 1.83 | 4548.30 | 67.90 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.4196 | 0.0000 | 1.4196 | 0.7171 | 1385.46 | 5.36 | 4552.18 |
PACU_VAV_MID | 1.2897 | 0.0000 | 1.2897 | 0.7171 | 1381.32 | 2.33 | 4559.35 |
PACU_VAV_TOP | 1.3032 | 0.0000 | 1.3032 | 0.7171 | 1408.20 | 1.83 | 4532.96 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 2227.95 | 0.00 | 0.00 | 0.00 | 2486.04 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 2021.86 | 0.00 | 0.00 | 0.00 | 2711.27 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2048.90 | 0.00 | 0.00 | 0.00 | 2697.72 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.6170 | 0.0000 | 0.0000 | 0.0000 | 1.1188 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.3714 | 0.0000 | 0.0000 | 0.0000 | 1.1179 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.3923 | 0.0000 | 0.0000 | 0.0000 | 1.1145 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 824 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1620.63 | 15539.06 | 02-APR-17:10 | 255212.18 | 02-JAN-07:10 |
Electricity:Building | 1043.20 | 15341.49 | 01-JAN-08:30 | 74468.47 | 03-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 310.83 | 4652.71 | 01-JAN-00:10 | 24063.48 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1043.20 | 15341.49 | 01-JAN-08:30 | 74468.47 | 03-JAN-08:10 |
InteriorLights:Electricity | 281.16 | 1316.11 | 01-JAN-08:30 | 28079.40 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 281.16 | 1316.11 | 01-JAN-08:30 | 28079.40 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 281.16 | 1316.11 | 01-JAN-08:30 | 28079.40 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 281.16 | 1316.11 | 01-JAN-08:30 | 28079.40 | 02-JAN-16:40 |
Electricity:Zone:CORE_MID | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 35.98 | 541.99 | 01-JAN-08:20 | 2674.44 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.29 | 40.03 | 01-JAN-08:20 | 1168.55 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.29 | 40.03 | 01-JAN-08:20 | 1168.55 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 22.77 | 343.10 | 01-JAN-07:50 | 1693.08 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.88 | 25.34 | 01-JAN-07:50 | 739.79 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.88 | 25.34 | 01-JAN-07:50 | 739.79 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 35.92 | 541.99 | 01-JAN-07:50 | 2674.43 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.23 | 40.03 | 01-JAN-07:50 | 1168.55 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.23 | 40.03 | 01-JAN-07:50 | 1168.55 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 22.74 | 343.10 | 01-JAN-08:30 | 1693.03 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.85 | 25.34 | 01-JAN-08:30 | 739.74 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.85 | 25.34 | 01-JAN-08:30 | 739.74 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 35.97 | 541.99 | 01-JAN-08:20 | 2674.44 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.28 | 40.03 | 01-JAN-08:20 | 1168.55 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.28 | 40.03 | 01-JAN-08:20 | 1168.55 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 22.77 | 343.10 | 01-JAN-07:50 | 1693.08 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.87 | 25.34 | 01-JAN-07:50 | 739.79 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.87 | 25.34 | 01-JAN-07:50 | 739.79 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 35.91 | 541.99 | 01-JAN-07:50 | 2674.43 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.22 | 40.03 | 01-JAN-07:50 | 1168.55 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.22 | 40.03 | 01-JAN-07:50 | 1168.55 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 22.74 | 343.10 | 01-JAN-08:20 | 1693.03 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.84 | 25.34 | 01-JAN-08:20 | 739.74 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.84 | 25.34 | 01-JAN-08:20 | 739.74 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 35.98 | 541.99 | 01-JAN-08:20 | 2674.44 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.29 | 40.03 | 01-JAN-08:20 | 1168.55 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.29 | 40.03 | 01-JAN-08:20 | 1168.55 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 22.77 | 343.10 | 01-JAN-07:50 | 1693.08 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.88 | 25.34 | 01-JAN-07:50 | 739.79 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.88 | 25.34 | 01-JAN-07:50 | 739.79 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 35.92 | 541.99 | 01-JAN-07:50 | 2674.43 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.23 | 40.03 | 01-JAN-07:50 | 1168.55 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.23 | 40.03 | 01-JAN-07:50 | 1168.55 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 22.74 | 343.10 | 01-JAN-08:30 | 1693.03 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.85 | 25.34 | 01-JAN-08:30 | 739.74 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.85 | 25.34 | 01-JAN-08:30 | 739.74 | 02-JAN-16:40 |
InteriorEquipment:Electricity | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 247.34 | 4344.73 | 01-JAN-00:10 | 18520.31 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 505.35 | 197.57 | 01-JAN-08:40 | 219043.14 | 02-JAN-06:20 |
ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 926.74 | 02-JAN-16:50 |
Transformer:ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 926.74 | 02-JAN-16:50 |
ElectricityPurchased:Facility | 1620.63 | 15539.06 | 02-APR-17:10 | 255212.18 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1620.63 | 15539.06 | 02-APR-17:10 | 255212.18 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1620.63 | 15539.06 | 02-APR-17:10 | 255212.18 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1620.63 | 15539.06 | 02-APR-17:10 | 255212.18 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1620.63 | 15539.06 | 02-APR-17:10 | 255212.18 | 02-JAN-07:10 |
ElectricityNet:Plant | 1620.63 | 15539.06 | 02-APR-17:10 | 255212.18 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1620.63 | 15539.06 | 02-APR-17:10 | 255212.18 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1620.63 | 15539.06 | 02-APR-17:10 | 255212.18 | 02-JAN-07:10 |
Heating:Electricity | 170.02 | 0.00 | 01-JAN-00:40 | 211546.62 | 02-JAN-06:20 |
General:Heating:Electricity | 170.02 | 0.00 | 01-JAN-00:40 | 211546.62 | 02-JAN-06:20 |
Fans:Electricity | 100.85 | 0.00 | 01-JAN-00:40 | 26703.95 | 30-MAY-14:40 |
General:Fans:Electricity | 100.85 | 0.00 | 01-JAN-00:40 | 26703.95 | 30-MAY-14:40 |
ExteriorLights:Electricity | 72.06 | 0.00 | 01-JAN-07:30 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 72.06 | 0.00 | 01-JAN-07:30 | 5557.43 | 01-JAN-06:10 |
Cooling:Electricity | 221.50 | 0.00 | 01-JAN-00:10 | 83063.31 | 19-JUN-12:20 |
General:Cooling:Electricity | 221.50 | 0.00 | 01-JAN-00:10 | 83063.31 | 19-JUN-12:20 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 7.90 | 0.00 | 01-JAN-00:10 | 789.03 | 02-JAN-16:50 |
WIRED_INT_EQUIP | 641.94 | 12061.80 | 01-JAN-00:10 | 36271.65 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 242.39 | 1156.00 | 06-FEB-05:50 | 101591.00 | 06-FEB-07:30 |
NaturalGas:HVAC | 135.09 | 0.00 | 01-JAN-00:40 | 93603.49 | 06-FEB-07:40 |
Heating:NaturalGas | 135.09 | 0.00 | 01-JAN-00:40 | 93603.49 | 06-FEB-07:40 |
General:Heating:NaturalGas | 135.09 | 0.00 | 01-JAN-00:40 | 93603.49 | 06-FEB-07:40 |
NaturalGas:Plant | 107.30 | 1156.00 | 03-JAN-07:10 | 9473.14 | 07-FEB-12:10 |
WaterSystems:NaturalGas | 107.30 | 1156.00 | 03-JAN-07:10 | 9473.14 | 07-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 107.30 | 1156.00 | 03-JAN-07:10 | 9473.14 | 07-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2386.62 | 0.00 | 01-JAN-00:40 | 481920.15 | 02-JAN-07:10 |
EnergyTransfer:Building | 1165.44 | 0.00 | 01-JAN-00:40 | 213992.51 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 229.59 | 0.00 | 01-JAN-00:40 | 27792.75 | 07-AUG-08:00 |
Heating:EnergyTransfer | 138.47 | 0.00 | 01-JAN-00:40 | 213992.51 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.35 | 0.00 | 01-JAN-00:10 | 20232.14 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 138.47 | 0.00 | 01-JAN-00:40 | 213992.51 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.35 | 0.00 | 01-JAN-00:10 | 20232.14 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 1026.98 | 0.00 | 01-JAN-00:40 | 171652.91 | 10-JUL-14:00 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 229.23 | 0.00 | 01-JAN-00:40 | 27792.75 | 07-AUG-08:00 |
General:Cooling:EnergyTransfer | 1026.98 | 0.00 | 01-JAN-00:40 | 171652.91 | 10-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 229.23 | 0.00 | 01-JAN-00:40 | 27792.75 | 07-AUG-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 54.25 | 0.00 | 01-JAN-00:40 | 16028.51 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 20.82 | 0.00 | 01-JAN-00:40 | 16028.51 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 20.82 | 0.00 | 01-JAN-00:40 | 16028.51 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 33.43 | 0.00 | 01-JAN-00:10 | 12571.92 | 19-JUN-13:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 33.43 | 0.00 | 01-JAN-00:10 | 12571.92 | 19-JUN-13:40 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 29.09 | 0.00 | 01-JAN-00:40 | 10216.88 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.15 | 0.00 | 01-JAN-00:40 | 10216.88 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.15 | 0.00 | 01-JAN-00:40 | 10216.88 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 18.94 | 0.00 | 01-JAN-00:10 | 5666.76 | 14-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 18.94 | 0.00 | 01-JAN-00:10 | 5666.76 | 14-AUG-14:50 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 30.27 | 0.00 | 01-JAN-00:40 | 8619.48 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 7.13 | 0.00 | 01-JAN-00:40 | 8619.48 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 7.13 | 0.00 | 01-JAN-00:40 | 8619.48 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 23.14 | 0.00 | 01-JAN-00:10 | 5743.55 | 10-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 23.14 | 0.00 | 01-JAN-00:10 | 5743.55 | 10-JUL-16:00 |
EnergyTransfer:Zone:CORE_MID | 154.96 | 0.00 | 01-JAN-00:40 | 21578.20 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 1.23 | 0.00 | 01-JAN-00:40 | 21578.20 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 1.23 | 0.00 | 01-JAN-00:40 | 21578.20 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 153.73 | 0.00 | 01-JAN-00:20 | 19358.61 | 14-AUG-09:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 153.73 | 0.00 | 01-JAN-00:20 | 19358.61 | 14-AUG-09:20 |
EnergyTransfer:Zone:CORE_TOP | 151.31 | 0.00 | 01-JAN-00:40 | 29192.98 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 6.20 | 0.00 | 01-JAN-00:40 | 29192.98 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 6.20 | 0.00 | 01-JAN-00:40 | 29192.98 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 145.11 | 0.00 | 01-JAN-00:20 | 21360.25 | 10-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 145.11 | 0.00 | 01-JAN-00:20 | 21360.25 | 10-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 46.19 | 0.00 | 01-JAN-00:40 | 10454.64 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 14.07 | 0.00 | 01-JAN-00:40 | 10454.64 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 14.07 | 0.00 | 01-JAN-00:40 | 10454.64 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.13 | 0.00 | 01-JAN-00:10 | 8027.02 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.13 | 0.00 | 01-JAN-00:10 | 8027.02 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 38.76 | 0.00 | 01-JAN-00:40 | 9527.16 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 7.47 | 0.00 | 01-JAN-00:40 | 9527.16 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 7.47 | 0.00 | 01-JAN-00:40 | 9527.16 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 31.29 | 0.00 | 01-JAN-00:10 | 9065.28 | 26-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 31.29 | 0.00 | 01-JAN-00:10 | 9065.28 | 26-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 60.52 | 0.00 | 01-JAN-00:40 | 13125.53 | 28-SEP-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 9.24 | 0.00 | 01-JAN-00:40 | 12772.75 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 9.24 | 0.00 | 01-JAN-00:40 | 12772.75 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 51.28 | 0.00 | 01-JAN-00:10 | 13125.53 | 28-SEP-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 51.28 | 0.00 | 01-JAN-00:10 | 13125.53 | 28-SEP-12:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 40.45 | 0.00 | 01-JAN-00:40 | 10089.53 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 8.49 | 0.00 | 01-JAN-00:40 | 10089.53 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 8.49 | 0.00 | 01-JAN-00:40 | 10089.53 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 31.96 | 0.00 | 01-JAN-00:10 | 9605.49 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 31.96 | 0.00 | 01-JAN-00:10 | 9605.49 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 35.64 | 0.00 | 01-JAN-00:40 | 7880.06 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 6.26 | 0.00 | 01-JAN-00:40 | 7880.06 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 6.26 | 0.00 | 01-JAN-00:40 | 7880.06 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 29.38 | 0.00 | 01-JAN-00:10 | 6222.63 | 10-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 29.38 | 0.00 | 01-JAN-00:10 | 6222.63 | 10-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 31.72 | 0.00 | 01-JAN-00:40 | 7740.19 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.91 | 0.00 | 01-JAN-00:40 | 7740.19 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.91 | 0.00 | 01-JAN-00:40 | 7740.19 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 28.82 | 0.00 | 01-JAN-00:20 | 7303.97 | 22-AUG-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 28.82 | 0.00 | 01-JAN-00:20 | 7303.97 | 22-AUG-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 64.48 | 0.00 | 01-JAN-00:40 | 14770.37 | 02-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 23.55 | 0.00 | 01-JAN-00:40 | 14770.37 | 02-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 23.55 | 0.00 | 01-JAN-00:40 | 14770.37 | 02-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 40.93 | 0.00 | 01-JAN-00:20 | 13650.30 | 19-JUN-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 40.93 | 0.00 | 01-JAN-00:20 | 13650.30 | 19-JUN-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 31.99 | 0.00 | 01-JAN-00:40 | 7975.48 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 3.34 | 0.00 | 01-JAN-00:40 | 7975.48 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 3.34 | 0.00 | 01-JAN-00:40 | 7975.48 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 28.65 | 0.00 | 01-JAN-00:20 | 7562.81 | 21-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 28.65 | 0.00 | 01-JAN-00:20 | 7562.81 | 21-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 39.40 | 0.00 | 01-JAN-00:40 | 8761.02 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 6.33 | 0.00 | 01-JAN-00:40 | 8761.02 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 6.33 | 0.00 | 01-JAN-00:40 | 8761.02 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 33.07 | 0.00 | 01-JAN-00:10 | 7130.76 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 33.07 | 0.00 | 01-JAN-00:10 | 7130.76 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 34.92 | 0.00 | 01-JAN-00:40 | 8775.94 | 26-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 3.39 | 0.00 | 01-JAN-00:40 | 8472.14 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 3.39 | 0.00 | 01-JAN-00:40 | 8472.14 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 31.53 | 0.00 | 01-JAN-00:10 | 8775.94 | 26-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 31.53 | 0.00 | 01-JAN-00:10 | 8775.94 | 26-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 55.94 | 0.00 | 01-JAN-00:40 | 12000.19 | 28-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 3.74 | 0.00 | 01-JAN-00:40 | 10767.30 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 3.74 | 0.00 | 01-JAN-00:40 | 10767.30 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 52.20 | 0.00 | 01-JAN-00:10 | 12000.19 | 28-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 52.20 | 0.00 | 01-JAN-00:10 | 12000.19 | 28-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 35.95 | 0.00 | 01-JAN-00:40 | 9021.39 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 3.79 | 0.00 | 01-JAN-00:40 | 8533.24 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 3.79 | 0.00 | 01-JAN-00:40 | 8533.24 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.17 | 0.00 | 01-JAN-00:10 | 9021.39 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.17 | 0.00 | 01-JAN-00:10 | 9021.39 | 15-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 48.91 | 0.00 | 01-JAN-00:10 | 6340.66 | 10-FEB-12:10 |
PlantLoopHeatingDemand:Plant | 48.91 | 0.00 | 01-JAN-00:10 | 6340.66 | 10-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 48.91 | 0.00 | 01-JAN-00:10 | 6340.66 | 10-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 48.91 | 0.00 | 01-JAN-00:10 | 6340.66 | 10-FEB-12:10 |
EnergyTransfer:HVAC | 1172.27 | 0.00 | 01-JAN-00:40 | 289226.17 | 16-AUG-12:20 |
HeatingCoils:EnergyTransfer | 278.09 | 0.00 | 01-JAN-00:40 | 276158.19 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 894.18 | 0.00 | 01-JAN-00:10 | 289226.17 | 16-AUG-12:20 |
EnergyTransfer:Plant | 48.91 | 0.00 | 01-JAN-00:10 | 6340.66 | 10-FEB-12:10 |
WaterSystems:EnergyTransfer | 48.91 | 0.00 | 01-JAN-00:10 | 6340.66 | 10-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 48.91 | 0.00 | 01-JAN-00:10 | 6340.66 | 10-FEB-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.353 | -229.233 | 0.000 | 0.000 | 33.041 | 63.485 | 247.342 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -114.988 |
CORE_MID | 0.000 | 0.000 | 1.232 | -153.732 | 0.000 | 0.000 | 34.399 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -71.985 |
CORE_TOP | 0.000 | 0.000 | 6.204 | -145.107 | 0.000 | 0.000 | 35.067 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -86.249 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 14.065 | -32.126 | 0.000 | 0.000 | 7.542 | 9.290 | 26.688 | 17.069 | 0.000 | 0.139 | 0.000 | 0.000 | -26.232 | 0.000 | -9.073 | -7.363 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 7.469 | -31.292 | 0.000 | 0.000 | 4.733 | 5.877 | 16.895 | 30.421 | 0.000 | 0.090 | 0.001 | 0.000 | -16.542 | 0.000 | -6.122 | -11.529 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 9.240 | -51.284 | 0.000 | 0.000 | 7.347 | 9.230 | 26.688 | 61.931 | 0.000 | 0.135 | 0.001 | 0.000 | -24.856 | 0.000 | -9.477 | -28.955 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 8.494 | -31.960 | 0.000 | 0.000 | 4.776 | 5.848 | 16.895 | 31.033 | 0.000 | 0.094 | 0.001 | 0.000 | -17.067 | 0.000 | -6.156 | -11.956 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 6.259 | -29.376 | 0.000 | 0.000 | 7.512 | 9.277 | 26.688 | 17.321 | 0.000 | 0.084 | 0.000 | 0.000 | -27.523 | 0.000 | -5.148 | -5.095 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 2.907 | -28.816 | 0.000 | 0.000 | 4.690 | 5.871 | 16.895 | 30.531 | 0.000 | 0.050 | 0.000 | 0.000 | -17.664 | 0.000 | -3.525 | -10.939 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 23.553 | -40.925 | 0.000 | 0.000 | 7.570 | 9.221 | 26.688 | 62.715 | 0.000 | 3.061 | 0.000 | 0.000 | -26.320 | 0.000 | -49.048 | -16.514 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 3.341 | -28.653 | 0.000 | 0.000 | 4.721 | 5.843 | 16.895 | 31.182 | 0.000 | 0.051 | 0.001 | 0.000 | -18.232 | 0.000 | -3.545 | -11.602 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 6.329 | -33.070 | 0.000 | 0.000 | 7.470 | 9.290 | 26.688 | 16.885 | 0.000 | 0.119 | 2.149 | 0.000 | -27.850 | 0.000 | -8.010 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 3.391 | -31.528 | 0.000 | 0.000 | 3.474 | 5.877 | 16.895 | 30.266 | 0.000 | 0.077 | 0.000 | 0.000 | -17.521 | 0.000 | -5.397 | -5.535 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 3.739 | -52.199 | 0.000 | 0.000 | 7.253 | 9.230 | 26.688 | 61.682 | 0.000 | 0.113 | 0.000 | 0.000 | -26.403 | 0.000 | -8.383 | -21.720 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 3.786 | -32.165 | 0.000 | 0.000 | 4.724 | 5.848 | 16.895 | 30.903 | 0.000 | 0.079 | 0.000 | 0.000 | -18.112 | 0.000 | -5.434 | -6.523 |
TOPFLOOR_PLENUM | 20.817 | -33.430 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.135 | 26.369 | 0.000 | 0.000 | 0.000 | -13.891 | -0.005 |
MIDFLOOR_PLENUM | 10.155 | -18.939 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.159 | 22.446 | 0.000 | 0.000 | 0.000 | -13.821 | -0.000 |
FIRSTFLOOR_PLENUM | 7.133 | -23.141 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.125 | 27.185 | 0.000 | 0.000 | 0.000 | -11.302 | -0.000 |
Total Facility | 38.105 | -75.509 | 100.361 | -951.464 | 0.000 | 0.000 | 174.319 | 281.156 | 762.041 | 421.937 | 0.000 | 4.509 | 78.152 | 0.000 | -264.321 | 0.000 | -158.331 | -410.959 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 07-AUG-04:02 | 0.00 | 0.00 | 0.00 | -45858.46 | 0.00 | 0.00 | 0.00 | 615.87 | 5138.45 | 0.00 | 0.00 | 0.00 | 40104.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 07-AUG-04:02 | 0.00 | 0.00 | 0.00 | -34241.81 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 30451.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 07-AUG-04:02 | 0.00 | 0.00 | 0.00 | -35821.96 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 32031.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-AUG-15:52 | 0.00 | 0.00 | 0.00 | -10650.93 | 0.00 | 0.00 | 27.27 | 40.03 | 501.96 | 2265.52 | 0.00 | 117.59 | 7698.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-08:42 | 0.00 | 0.00 | 0.00 | -13132.42 | 0.00 | 0.00 | 13.78 | 25.34 | 317.77 | 9574.75 | 0.00 | 0.00 | 3236.83 | 0.00 | -0.00 | 0.00 | -36.05 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-13:12 | 0.00 | 0.00 | 0.00 | -16875.90 | 0.00 | 0.00 | 21.58 | 40.03 | 501.96 | 10957.32 | 0.00 | 0.00 | 5407.55 | 0.00 | -0.00 | 0.00 | -52.55 | 0.00 |
PERIMETER_TOP_ZN_4 | 18-JUN-16:02 | 0.00 | 0.00 | 0.00 | -14279.98 | 0.00 | 0.00 | 13.28 | 25.34 | 317.76 | 9415.69 | 0.00 | 0.00 | 4572.08 | 0.00 | -0.00 | 0.00 | -64.18 | 0.00 |
PERIMETER_BOT_ZN_3 | 10-JUL-04:02 | 0.00 | 0.00 | 0.00 | -7541.48 | 0.00 | 0.00 | 0.00 | 129.83 | 669.29 | 0.00 | 0.00 | 6.61 | 6804.42 | 0.00 | -68.66 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-SEP-10:12 | 0.00 | 0.00 | 0.00 | -11084.49 | 0.00 | 0.00 | 15.67 | 25.34 | 317.77 | 5461.67 | 0.00 | 0.00 | 5280.10 | 0.00 | -0.00 | 0.00 | -16.05 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-14:52 | 0.00 | 0.00 | 0.00 | -13858.33 | 0.00 | 0.00 | 24.70 | 40.03 | 501.96 | 5583.11 | 0.00 | 0.00 | 7793.55 | 0.00 | -0.00 | 0.00 | -85.01 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-SEP-16:52 | 0.00 | 0.00 | 0.00 | -11318.40 | 0.00 | 0.00 | 15.76 | 25.34 | 317.76 | 5504.14 | 0.00 | 0.00 | 5516.15 | 0.00 | -0.00 | 0.00 | -60.75 | 0.00 |
PERIMETER_MID_ZN_3 | 09-JUL-15:22 | 0.00 | 0.00 | 0.00 | -10122.87 | 0.00 | 0.00 | 28.57 | 40.03 | 501.96 | 3249.34 | 0.00 | 9.32 | 6293.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-08:31 | 0.00 | 0.00 | 0.00 | -13821.09 | 0.00 | 0.00 | 13.99 | 25.34 | 317.77 | 9843.45 | 0.00 | 0.00 | 3675.30 | 0.00 | -0.00 | 0.00 | -54.75 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-11:42 | 0.00 | 0.00 | 0.00 | -16090.64 | 0.00 | 0.00 | 22.87 | 40.03 | 501.96 | 12420.62 | 0.00 | 0.00 | 3172.94 | 0.00 | -0.00 | 0.00 | -67.78 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JUL-16:31 | 0.00 | 0.00 | 0.00 | -14204.92 | 0.00 | 0.00 | 13.95 | 25.34 | 317.76 | 8718.64 | 0.00 | 0.00 | 5276.27 | 0.00 | -0.00 | 0.00 | -147.04 | 0.00 |
TOPFLOOR_PLENUM | 19-JUN-13:40 | 0.00 | -12571.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.82 | 12435.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 14-AUG-14:50 | 0.00 | -5667.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.82 | 5602.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 19-JUN-12:09 | 0.00 | -7072.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.65 | 6934.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-AUG-04:02 | 0.00 | 10418.87 | 0.00 | -202179.55 | 0.00 | 0.00 | 0.00 | 3119.77 | 18045.99 | 0.00 | 0.00 | 0.00 | 178273.47 | 0.00 | -6628.55 | 0.00 | -1049.98 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 23578.86 | 0.00 | 0.00 | 0.00 | 0.00 | 615.87 | 5138.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29333.18 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 24679.81 | 0.00 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -28470.54 |
CORE_TOP | 02-JAN-01:22 | 0.00 | 0.00 | 32978.36 | 0.00 | 0.00 | 0.00 | 0.00 | 307.97 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -36461.20 |
PERIMETER_TOP_ZN_3 | 01-JAN-22:42 | 0.00 | 0.00 | 11500.52 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2780.33 | 0.00 | -2186.84 | -7100.24 |
PERIMETER_TOP_ZN_2 | 06-FEB-01:52 | 0.00 | 0.00 | 11927.27 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2058.14 | 0.00 | -1647.41 | -8686.50 |
PERIMETER_TOP_ZN_1 | 02-JAN-01:22 | 0.00 | 0.00 | 15111.96 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2830.13 | 0.00 | -1720.20 | -11295.84 |
PERIMETER_TOP_ZN_4 | 06-FEB-01:52 | 0.00 | 0.00 | 12968.27 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2117.19 | 0.00 | -1651.29 | -9664.57 |
PERIMETER_BOT_ZN_3 | 01-JAN-22:42 | 0.00 | 0.00 | 8758.93 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2834.95 | 0.00 | -1205.05 | -5285.82 |
PERIMETER_BOT_ZN_2 | 01-JAN-22:42 | 0.00 | 0.00 | 9511.56 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 317.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1859.09 | 0.00 | -820.83 | -7190.51 |
PERIMETER_BOT_ZN_1 | 06-FEB-07:10 | 0.00 | 0.00 | 14776.44 | 0.00 | 0.00 | 0.00 | 205.17 | 315.80 | 669.28 | 0.00 | 0.00 | 0.00 | 16814.94 | 0.00 | -2480.92 | 0.00 | -30300.71 | 0.00 |
PERIMETER_BOT_ZN_4 | 01-JAN-22:42 | 0.00 | 0.00 | 9834.24 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 317.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1894.85 | 0.00 | -818.52 | -7479.73 |
PERIMETER_MID_ZN_3 | 01-JAN-20:42 | 0.00 | 0.00 | 9724.62 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2665.32 | 0.00 | -2068.69 | -5557.49 |
PERIMETER_MID_ZN_2 | 01-JAN-22:42 | 0.00 | 0.00 | 10991.45 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 317.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1848.23 | 0.00 | -1268.50 | -8233.59 |
PERIMETER_MID_ZN_1 | 01-JAN-22:42 | 0.00 | 0.00 | 13206.71 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2798.01 | 0.00 | -1898.59 | -9076.99 |
PERIMETER_MID_ZN_4 | 01-JAN-22:42 | 0.00 | 0.00 | 11109.45 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 317.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1894.33 | 0.00 | -1266.73 | -8307.25 |
TOPFLOOR_PLENUM | 06-FEB-06:08 | 16768.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -799.27 | -15969.62 |
MIDFLOOR_PLENUM | 02-JAN-07:06 | 10522.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -232.36 | -10289.74 |
FIRSTFLOOR_PLENUM | 02-JAN-07:01 | 9329.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -179.52 | -9149.66 |
Total Facility | 02-JAN-05:01 | 18745.57 | 0.00 | 206364.47 | 0.00 | 0.00 | 0.00 | 0.00 | 3119.77 | 18045.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -30213.14 | 0.00 | -9587.93 | -206474.71 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.4027 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.8739 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.0028 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.3282 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.4526 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0413 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.7014 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3542 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.5014 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3706 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.7263 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4512 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8187 | 2.8187 | 0.7751 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0775 | 2.0775 | 0.7500 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2231 | 2.2231 | 0.7825 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7108 | 0.7108 | 0.1649 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7506 | 0.7506 | 0.1501 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9501 | 0.9501 | 0.1900 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8181 | 0.8181 | 0.1636 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5600 | 0.5600 | 0.1635 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6207 | 0.6207 | 0.1241 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7635 | 0.7635 | 0.1634 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6400 | 0.6400 | 0.1280 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6139 | 0.6139 | 0.1584 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7196 | 0.7196 | 0.1439 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8487 | 0.8487 | 0.1697 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7431 | 0.7431 | 0.1486 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.4027 | 4.8739 | 5.4027 | 1.3542 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.0028 | 4.3282 | 5.0028 | 1.3706 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.4526 | 5.0413 | 5.4526 | 1.4512 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4093 | 1.4093 | 0.7751 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0387 | 1.0387 | 0.7500 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1115 | 1.1115 | 0.7825 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3554 | 0.3554 | 0.1649 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3753 | 0.3753 | 0.1501 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4750 | 0.4750 | 0.1900 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4090 | 0.4090 | 0.1636 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2800 | 0.2800 | 0.1635 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3103 | 0.3103 | 0.1241 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3817 | 0.3817 | 0.1634 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3200 | 0.3200 | 0.1280 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3070 | 0.3070 | 0.1584 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3598 | 0.3598 | 0.1439 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4243 | 0.4243 | 0.1697 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3715 | 0.3715 | 0.1486 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.7014 | 1.3542 | 1.3542 | 1.3542 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.5014 | 1.3706 | 1.3706 | 1.3706 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.7263 | 1.4512 | 1.4512 | 1.4512 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 363.17 |
Number of hours cooling loads not met | 118.17 |
Number of hours not met | 481.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 170.02 | 211546.62 | 135.09 | 93603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 221.50 | 83063.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 281.16 | 28079.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 72.06 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 641.30 | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 12.98 | 926.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 100.85 | 26703.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 107.30 | 9473.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 762.04 | 1620.63 |
Natural Gas | 0.00 | 242.39 |
Additional | 0.00 | 0.00 |
Total | 762.04 | 1863.01 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 56.43 |
Space Heating | 34.12 |
Space Cooling | 44.46 |
Fans (All) | 20.24 |
Service Water Heating | 0.00 |
Receptacle Equipment | 152.95 |
Miscellaneous (All) | 325.28 |
Subtotal | 325.28 |
Natural Gas [MJ/m2] | |
Space Heating | 27.12 |
Service Water Heating | 21.54 |
Miscellaneous (All) | 48.65 |
Subtotal | 48.65 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.09 |
Space Heating | 16.38 |
Space Cooling | 11.89 |
Fans (All) | 5.41 |
Service Water Heating | 5.76 |
Receptacle Equipment | 40.90 |
Miscellaneous | 4.57 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2429. | 8760. |
BLDG_EQUIP_SCH | 4487. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8596.17 | 163.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8734.00 | 26.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8731.83 | 28.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8671.67 | 88.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8618.50 | 141.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8613.00 | 147.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8562.50 | 197.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8745.00 | 15.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8675.50 | 84.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8671.67 | 88.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8594.17 | 165.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8674.50 | 85.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8615.00 | 145.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8612.00 | 148.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8544.33 | 215.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8628.17 | 131.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
Min | 8544.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 215.67 | 0.00 | 0.00 | 0.00 |
Average | 8655.97 | 104.03 | 0.00 | 0.00 | 0.00 |
Sum | 155807.50 | 1872.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128257.67 | 46.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128298.33 | 5.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128294.33 | 9.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24905.67 | 3.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128298.33 | 46.33 | 0.00 | 0.00 | 0.00 |
Average | 34139.72 | 3.61 | 0.00 | 0.00 | 0.00 |
Sum | 614515.00 | 65.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8031.17 | 728.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8238.50 | 521.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8344.83 | 415.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7959.00 | 801.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7971.83 | 788.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7946.83 | 813.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7952.67 | 807.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8087.33 | 672.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8003.67 | 756.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7637.50 | 1122.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7940.67 | 819.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7929.83 | 830.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7940.17 | 819.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7894.00 | 866.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7903.33 | 856.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7403.67 | 1356.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 7880.50 | 879.50 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 7947.00 | 813.00 | 0.00 | 0.00 | 0.00 |
Min | 7403.67 | 415.17 | 0.00 | 0.00 | 0.00 |
Max | 8344.83 | 1356.33 | 0.00 | 0.00 | 0.00 |
Average | 7945.14 | 814.86 | 0.00 | 0.00 | 0.00 |
Sum | 143012.50 | 14667.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127943.33 | 360.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128071.17 | 232.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128126.00 | 178.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24816.00 | 93.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14003.00 | 13.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24855.67 | 53.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24857.00 | 52.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14001.00 | 15.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 23016.50 | 1892.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14014.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24865.83 | 43.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24876.67 | 32.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14008.00 | 8.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128126.00 | 1892.50 | 0.00 | 0.00 | 0.00 |
Average | 33978.01 | 165.32 | 0.00 | 0.00 | 0.00 |
Sum | 611604.17 | 2975.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:16
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.947959E+10 | 12140.49 | 27-JAN-08:40 | 2.57 | 0.54 | 0.182643E+10 | 2606.63 | 20-JAN-10:09 | 2.57 | 0.54 |
February | 0.972689E+10 | 12836.03 | 03-FEB-08:30 | -6.7 | -8.7 | 0.172221E+10 | 2606.64 | 01-FEB-10:39 | -6.7 | -8.7 |
March | 0.142679E+11 | 18488.64 | 28-MAR-07:06 | 10.00 | 7.46 | 0.212980E+10 | 2606.66 | 27-MAR-09:09 | 10.00 | 7.46 |
April | 0.162360E+11 | 40365.58 | 11-APR-05:03 | 6.10 | 1.72 | 0.190444E+10 | 2606.67 | 26-APR-09:00 | 16.10 | 12.59 |
May | 0.222407E+11 | 43540.22 | 30-MAY-04:03 | 17.80 | 14.10 | 0.207460E+10 | 2606.78 | 15-MAY-13:00 | 17.80 | 14.10 |
June | 0.265706E+11 | 43994.62 | 26-JUN-04:03 | 20.60 | 16.77 | 0.207091E+10 | 2606.65 | 08-JUN-09:00 | 20.60 | 16.77 |
July | 0.273037E+11 | 45065.77 | 24-JUL-04:02 | 21.02 | 20.27 | 0.192510E+10 | 2606.67 | 12-JUL-13:00 | 21.02 | 20.27 |
August | 0.297733E+11 | 45866.04 | 07-AUG-04:02 | 18.48 | 17.13 | 0.216115E+10 | 2606.69 | 08-AUG-13:30 | 26.40 | 17.05 |
September | 0.249502E+11 | 43591.49 | 06-SEP-04:03 | 21.20 | 18.83 | 0.191813E+10 | 2606.72 | 19-SEP-09:09 | 18.58 | 14.06 |
October | 0.226048E+11 | 41275.01 | 11-OCT-05:03 | 12.70 | 12.70 | 0.199268E+10 | 2606.74 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.146390E+11 | 30267.99 | 03-NOV-05:03 | 9.22 | 6.42 | 0.195192E+10 | 2606.71 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.114399E+11 | 15179.53 | 21-DEC-08:16 | -0.4 | -3.1 | 0.187549E+10 | 2606.63 | 15-DEC-10:20 | -0.4 | -3.1 |
Annual Sum or Average | 0.229233E+12 | 0.235528E+11 | ||||||||
Minimum of Months | 0.947959E+10 | 12140.49 | -6.7 | -8.7 | 0.172221E+10 | 2606.63 | -6.7 | -8.7 | ||
Maximum of Months | 0.297733E+11 | 45866.04 | 21.20 | 20.27 | 0.216115E+10 | 2606.78 | 26.40 | 20.27 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4508612.64 | 445.01 | 17-JAN-14:30 | 10.85 | 5.11 | 0.00 | 0.00 | 01-JAN-00:10 | 10.85 | 5.11 |
February | 23146118.14 | 761.37 | 17-FEB-13:00 | 6.70 | 1.56 | 0.00 | 0.00 | 01-FEB-00:10 | 6.70 | 1.56 |
March | 0.530360E+09 | 2746.41 | 03-MAR-14:30 | 15.00 | 8.51 | 0.00 | 0.00 | 01-MAR-00:10 | 15.00 | 8.51 |
April | 0.147174E+10 | 7380.10 | 07-APR-14:30 | 25.85 | 15.95 | 0.00 | 0.00 | 01-APR-00:10 | 25.85 | 15.95 |
May | 0.345408E+10 | 11114.72 | 30-MAY-14:00 | 29.40 | 16.93 | 0.00 | 0.00 | 01-MAY-00:10 | 29.40 | 16.93 |
June | 0.602330E+10 | 12571.92 | 19-JUN-13:40 | 34.60 | 23.77 | 0.00 | 0.00 | 01-JUN-00:10 | 34.60 | 23.77 |
July | 0.748397E+10 | 11684.96 | 07-JUL-13:50 | 32.80 | 23.64 | 0.00 | 0.00 | 01-JUL-00:10 | 32.80 | 23.64 |
August | 0.804222E+10 | 11171.20 | 01-AUG-14:40 | 30.97 | 22.94 | 0.00 | 0.00 | 01-AUG-00:10 | 30.97 | 22.94 |
September | 0.401972E+10 | 9933.27 | 01-SEP-14:50 | 30.68 | 17.45 | 0.00 | 0.00 | 01-SEP-00:10 | 30.68 | 17.45 |
October | 0.214854E+10 | 6999.08 | 04-OCT-14:50 | 23.98 | 19.09 | 0.00 | 0.00 | 01-OCT-00:10 | 23.98 | 19.09 |
November | 0.225864E+09 | 2436.45 | 04-NOV-13:10 | 17.62 | 12.77 | 0.00 | 0.00 | 01-NOV-00:10 | 17.62 | 12.77 |
December | 2406634.11 | 401.41 | 20-DEC-13:03 | 9.50 | 5.64 | 0.00 | 0.00 | 01-DEC-00:10 | 9.50 | 5.64 |
Annual Sum or Average | 0.334299E+11 | 0.00 | ||||||||
Minimum of Months | 2406634.11 | 401.41 | 6.70 | 1.56 | 0.00 | 0.00 | 6.70 | 1.56 | ||
Maximum of Months | 0.804222E+10 | 12571.92 | 34.60 | 23.77 | 0.00 | 0.00 | 34.60 | 23.77 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5283569.19 | 1647.57 | 05-JAN-05:02 | -7.8 | -9.6 | 0.00 | 0.00 | 01-JAN-00:10 | -7.8 | -9.6 |
February | 6724575.72 | 1499.16 | 09-FEB-05:01 | -8.3 | -9.9 | 0.00 | 0.00 | 01-FEB-00:10 | -8.3 | -9.9 |
March | 0.137284E+09 | 2568.12 | 29-MAR-06:01 | 1.88 | 0.26 | 0.00 | 0.00 | 01-MAR-00:10 | 1.88 | 0.26 |
April | 0.555536E+09 | 2263.01 | 14-APR-06:01 | 5.00 | 4.24 | 0.00 | 0.00 | 01-APR-00:10 | 5.00 | 4.24 |
May | 0.159270E+10 | 4937.03 | 30-MAY-14:40 | 28.67 | 17.12 | 0.00 | 0.00 | 01-MAY-00:10 | 28.67 | 17.12 |
June | 0.345843E+10 | 5199.08 | 19-JUN-15:10 | 32.93 | 23.30 | 0.00 | 0.00 | 01-JUN-00:10 | 32.93 | 23.30 |
July | 0.442888E+10 | 5592.72 | 10-JUL-14:10 | 32.88 | 20.91 | 0.00 | 0.00 | 01-JUL-00:10 | 32.88 | 20.91 |
August | 0.482622E+10 | 5666.76 | 14-AUG-14:50 | 28.58 | 23.14 | 0.00 | 0.00 | 01-AUG-00:10 | 28.58 | 23.14 |
September | 0.261102E+10 | 5203.09 | 05-SEP-15:20 | 25.93 | 21.57 | 0.00 | 0.00 | 01-SEP-00:10 | 25.93 | 21.57 |
October | 0.118385E+10 | 3185.69 | 04-OCT-15:40 | 23.17 | 19.12 | 0.00 | 0.00 | 01-OCT-00:10 | 23.17 | 19.12 |
November | 0.127242E+09 | 906.20 | 04-NOV-06:03 | 9.90 | 8.72 | 0.00 | 0.00 | 01-NOV-00:10 | 9.90 | 8.72 |
December | 5544880.28 | 927.47 | 02-DEC-06:01 | 1.10 | -2.5 | 0.00 | 0.00 | 01-DEC-00:10 | 1.10 | -2.5 |
Annual Sum or Average | 0.189387E+11 | 0.00 | ||||||||
Minimum of Months | 5283569.19 | 906.20 | -8.3 | -9.9 | 0.00 | 0.00 | -8.3 | -9.9 | ||
Maximum of Months | 0.482622E+10 | 5666.76 | 32.93 | 23.30 | 0.00 | 0.00 | 32.93 | 23.30 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55346960.01 | 1879.95 | 11-JAN-17:10 | -5.1 | -8.2 | 0.00 | 0.00 | 01-JAN-00:10 | -5.1 | -8.2 |
February | 66597183.98 | 2482.51 | 03-FEB-07:10 | -7.7 | -9.4 | 0.00 | 0.00 | 01-FEB-00:10 | -7.7 | -9.4 |
March | 0.299498E+09 | 2931.05 | 29-MAR-06:01 | 1.88 | 0.26 | 0.00 | 0.00 | 01-MAR-00:10 | 1.88 | 0.26 |
April | 0.864099E+09 | 2761.14 | 14-APR-06:01 | 5.00 | 4.24 | 0.00 | 0.00 | 01-APR-00:10 | 5.00 | 4.24 |
May | 0.207320E+10 | 5337.09 | 30-MAY-12:07 | 29.50 | 17.65 | 0.00 | 0.00 | 01-MAY-00:10 | 29.50 | 17.65 |
June | 0.385527E+10 | 7072.63 | 19-JUN-12:09 | 36.42 | 24.23 | 0.00 | 0.00 | 01-JUN-00:10 | 36.42 | 24.23 |
July | 0.475446E+10 | 6071.44 | 10-JUL-12:10 | 31.28 | 20.14 | 0.00 | 0.00 | 01-JUL-00:10 | 31.28 | 20.14 |
August | 0.534178E+10 | 5704.07 | 14-AUG-15:50 | 27.88 | 22.79 | 0.00 | 0.00 | 01-AUG-00:10 | 27.88 | 22.79 |
September | 0.336087E+10 | 5356.65 | 05-SEP-16:00 | 25.60 | 21.66 | 0.00 | 0.00 | 01-SEP-00:10 | 25.60 | 21.66 |
October | 0.206637E+10 | 3889.18 | 04-OCT-16:00 | 22.80 | 19.11 | 0.00 | 0.00 | 01-OCT-00:10 | 22.80 | 19.11 |
November | 0.325617E+09 | 1806.91 | 15-NOV-07:01 | 2.98 | 1.06 | 0.00 | 0.00 | 01-NOV-00:10 | 2.98 | 1.06 |
December | 77595197.97 | 2212.61 | 22-DEC-07:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-DEC-00:10 | -4.9 | -6.9 |
Annual Sum or Average | 0.231407E+11 | 0.00 | ||||||||
Minimum of Months | 55346960.01 | 1806.91 | -7.7 | -9.4 | 0.00 | 0.00 | -7.7 | -9.4 | ||
Maximum of Months | 0.534178E+10 | 7072.63 | 36.42 | 24.23 | 0.00 | 0.00 | 36.42 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.597789E+10 | 6954.03 | 20-JAN-17:00 | 5.60 | 3.19 | 0.157084E+10 | 2356.30 | 20-JAN-14:00 | 5.60 | 3.19 |
February | 0.622691E+10 | 6970.10 | 24-FEB-17:00 | 6.70 | 1.42 | 0.145202E+10 | 2373.50 | 24-FEB-14:00 | 6.70 | 1.42 |
March | 0.929479E+10 | 9236.96 | 29-MAR-16:00 | 7.20 | 4.88 | 0.190902E+10 | 2606.58 | 29-MAR-13:30 | 7.20 | 4.88 |
April | 0.104790E+11 | 15193.20 | 10-APR-05:03 | 15.10 | 13.73 | 0.181804E+10 | 2608.07 | 13-APR-09:30 | 8.05 | 3.78 |
May | 0.150077E+11 | 32378.92 | 30-MAY-04:03 | 17.80 | 14.10 | 0.205476E+10 | 2606.73 | 15-MAY-13:00 | 17.80 | 14.10 |
June | 0.187308E+11 | 32633.62 | 26-JUN-04:03 | 20.60 | 16.77 | 0.206708E+10 | 2606.65 | 26-JUN-09:39 | 25.73 | 19.90 |
July | 0.201770E+11 | 32842.85 | 24-JUL-04:02 | 21.02 | 20.27 | 0.192187E+10 | 2606.66 | 17-JUL-09:20 | 21.02 | 20.27 |
August | 0.214267E+11 | 34248.44 | 07-AUG-04:02 | 18.48 | 17.13 | 0.215841E+10 | 2606.66 | 23-AUG-13:09 | 25.60 | 17.07 |
September | 0.167813E+11 | 33027.56 | 05-SEP-04:02 | 20.52 | 17.93 | 0.191093E+10 | 2606.69 | 19-SEP-09:09 | 18.58 | 14.06 |
October | 0.138058E+11 | 25550.21 | 06-OCT-05:03 | 19.40 | 18.22 | 0.197108E+10 | 2606.71 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.846963E+10 | 11456.47 | 03-NOV-16:00 | 15.00 | 10.26 | 0.176759E+10 | 2606.66 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.735400E+10 | 7121.03 | 21-DEC-16:20 | 2.43 | -2.4 | 0.159305E+10 | 2431.92 | 21-DEC-14:00 | 2.43 | -2.4 |
Annual Sum or Average | 0.153732E+12 | 0.221947E+11 | ||||||||
Minimum of Months | 0.597789E+10 | 6954.03 | 2.43 | -2.4 | 0.145202E+10 | 2356.30 | 2.43 | -2.4 | ||
Maximum of Months | 0.214267E+11 | 34248.44 | 21.02 | 20.27 | 0.215841E+10 | 2608.07 | 25.73 | 20.27 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.435329E+10 | 6832.24 | 20-JAN-16:40 | 6.13 | 3.40 | 0.150169E+10 | 2251.69 | 20-JAN-16:49 | 5.87 | 3.30 |
February | 0.440990E+10 | 6905.12 | 24-FEB-16:50 | 6.88 | 1.49 | 0.137992E+10 | 2288.80 | 02-FEB-14:00 | 6.88 | 1.49 |
March | 0.815433E+10 | 8821.41 | 29-MAR-16:00 | 7.20 | 4.88 | 0.179618E+10 | 2596.18 | 28-MAR-13:00 | 7.20 | 4.88 |
April | 0.985833E+10 | 15280.37 | 10-APR-15:50 | 20.00 | 11.21 | 0.174434E+10 | 2606.64 | 07-APR-13:09 | 20.00 | 11.21 |
May | 0.148974E+11 | 26672.11 | 30-MAY-04:03 | 17.80 | 14.10 | 0.202564E+10 | 2606.74 | 15-MAY-13:00 | 17.80 | 14.10 |
June | 0.193042E+11 | 34778.49 | 26-JUN-04:03 | 20.60 | 16.77 | 0.206383E+10 | 2606.67 | 23-JUN-09:09 | 20.60 | 16.77 |
July | 0.212352E+11 | 35613.77 | 24-JUL-04:02 | 21.02 | 20.27 | 0.192191E+10 | 2606.65 | 14-JUL-09:00 | 21.02 | 20.27 |
August | 0.221850E+11 | 35828.11 | 07-AUG-04:02 | 18.48 | 17.13 | 0.215698E+10 | 2606.70 | 29-AUG-09:09 | 23.77 | 18.41 |
September | 0.162105E+11 | 35001.20 | 05-SEP-04:02 | 20.52 | 17.93 | 0.189864E+10 | 2606.69 | 11-SEP-13:09 | 20.60 | 12.01 |
October | 0.124539E+11 | 16285.56 | 04-OCT-15:50 | 22.98 | 19.12 | 0.191570E+10 | 2606.70 | 06-OCT-09:20 | 18.50 | 17.26 |
November | 0.699286E+10 | 10056.19 | 03-NOV-16:00 | 15.00 | 10.26 | 0.164146E+10 | 2606.55 | 03-NOV-13:50 | 15.00 | 10.26 |
December | 0.505195E+10 | 6811.92 | 21-DEC-16:10 | 2.62 | -2.3 | 0.148112E+10 | 2285.30 | 20-DEC-14:00 | 2.62 | -2.3 |
Annual Sum or Average | 0.145107E+12 | 0.215274E+11 | ||||||||
Minimum of Months | 0.435329E+10 | 6811.92 | 2.62 | -2.3 | 0.137992E+10 | 2251.69 | 2.62 | -2.3 | ||
Maximum of Months | 0.221850E+11 | 35828.11 | 22.98 | 20.27 | 0.215698E+10 | 2606.74 | 23.77 | 20.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109249E+09 | 1120.43 | 20-JAN-15:20 | 7.60 | 3.92 | 0.304942E+09 | 413.11 | 20-JAN-14:00 | 7.60 | 3.92 |
February | 0.133561E+09 | 1159.21 | 17-FEB-14:50 | 6.20 | 1.83 | 0.277270E+09 | 418.71 | 17-FEB-14:00 | 6.10 | 1.74 |
March | 0.807062E+09 | 1642.64 | 27-MAR-16:00 | 22.20 | 16.34 | 0.348975E+09 | 533.16 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.169808E+10 | 4103.02 | 07-APR-15:20 | 25.60 | 16.01 | 0.346448E+09 | 549.50 | 07-APR-13:09 | 25.60 | 16.01 |
May | 0.351510E+10 | 7306.85 | 29-MAY-14:23 | 25.85 | 17.23 | 0.419628E+09 | 549.52 | 15-MAY-13:00 | 25.85 | 17.23 |
June | 0.556300E+10 | 8970.69 | 26-JUN-06:03 | 21.97 | 17.81 | 0.434872E+09 | 549.77 | 19-JUN-13:50 | 21.97 | 17.81 |
July | 0.658411E+10 | 10036.59 | 31-JUL-04:02 | 23.80 | 22.58 | 0.405885E+09 | 549.51 | 11-JUL-13:50 | 23.80 | 22.58 |
August | 0.657364E+10 | 10651.03 | 13-AUG-15:52 | 30.00 | 20.46 | 0.454592E+09 | 549.51 | 08-AUG-13:39 | 30.00 | 20.46 |
September | 0.389300E+10 | 6265.51 | 01-SEP-14:30 | 30.85 | 17.41 | 0.395618E+09 | 549.51 | 11-SEP-13:09 | 20.60 | 12.01 |
October | 0.239463E+10 | 4264.73 | 04-OCT-14:00 | 24.40 | 18.95 | 0.385155E+09 | 549.50 | 12-OCT-13:00 | 20.60 | 17.37 |
November | 0.748989E+09 | 1650.02 | 03-NOV-14:50 | 17.30 | 10.93 | 0.319975E+09 | 534.18 | 03-NOV-13:00 | 17.30 | 10.93 |
December | 0.106137E+09 | 1154.20 | 20-DEC-14:00 | 10.00 | 5.91 | 0.294904E+09 | 421.16 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.321266E+11 | 0.438826E+10 | ||||||||
Minimum of Months | 0.106137E+09 | 1120.43 | 6.20 | 1.83 | 0.277270E+09 | 413.11 | 6.10 | 1.74 | ||
Maximum of Months | 0.658411E+10 | 10651.03 | 30.85 | 22.58 | 0.454592E+09 | 549.77 | 30.00 | 22.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182343E+09 | 1195.50 | 19-JAN-10:20 | 7.80 | 4.36 | 0.194116E+09 | 289.66 | 19-JAN-10:30 | 7.80 | 4.48 |
February | 0.274324E+09 | 1230.14 | 22-FEB-10:10 | 0.87 | -3.0 | 0.177149E+09 | 296.10 | 22-FEB-10:20 | 1.13 | -2.8 |
March | 0.102398E+10 | 2985.40 | 29-MAR-09:40 | 6.33 | 3.26 | 0.233535E+09 | 347.87 | 29-MAR-09:00 | 6.70 | 3.39 |
April | 0.191919E+10 | 5826.25 | 28-APR-09:00 | 16.10 | 8.85 | 0.229301E+09 | 347.89 | 26-APR-09:00 | 16.10 | 8.85 |
May | 0.368986E+10 | 13015.53 | 29-MAY-09:02 | 26.20 | 16.88 | 0.266984E+09 | 348.35 | 30-MAY-09:00 | 27.80 | 17.82 |
June | 0.488130E+10 | 12644.47 | 04-JUN-09:43 | 24.22 | 12.91 | 0.275240E+09 | 348.34 | 26-JUN-09:00 | 26.10 | 20.11 |
July | 0.568374E+10 | 13132.31 | 02-JUL-08:42 | 25.40 | 21.60 | 0.257042E+09 | 348.82 | 14-JUL-09:00 | 30.60 | 21.74 |
August | 0.626519E+10 | 12146.64 | 27-AUG-10:02 | 26.28 | 21.80 | 0.288048E+09 | 348.48 | 18-AUG-09:39 | 26.28 | 21.80 |
September | 0.377293E+10 | 12977.49 | 04-SEP-09:12 | 24.47 | 18.42 | 0.251348E+09 | 348.49 | 06-SEP-09:50 | 26.52 | 19.55 |
October | 0.252482E+10 | 5263.50 | 25-OCT-09:30 | 22.20 | 19.22 | 0.252201E+09 | 347.88 | 16-OCT-09:09 | 22.20 | 19.22 |
November | 0.812018E+09 | 1679.29 | 03-NOV-09:30 | 13.05 | 8.24 | 0.207234E+09 | 347.87 | 03-NOV-09:00 | 13.30 | 8.39 |
December | 0.262901E+09 | 1241.36 | 20-DEC-09:50 | 7.93 | 4.87 | 0.187562E+09 | 297.00 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.312926E+11 | 0.281976E+10 | ||||||||
Minimum of Months | 0.182343E+09 | 1195.50 | 0.87 | -3.0 | 0.177149E+09 | 289.66 | 1.13 | -2.8 | ||
Maximum of Months | 0.626519E+10 | 13132.31 | 26.28 | 21.80 | 0.288048E+09 | 348.82 | 30.60 | 21.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.821304E+09 | 5317.95 | 19-JAN-13:30 | 9.40 | 3.94 | 0.332842E+09 | 549.49 | 30-JAN-14:20 | 2.80 | -1.2 |
February | 0.108273E+10 | 5762.01 | 02-FEB-14:10 | 5.50 | -1.1 | 0.307378E+09 | 549.49 | 03-FEB-14:00 | -1.7 | -5.1 |
March | 0.235490E+10 | 8353.84 | 03-MAR-13:25 | 14.70 | 8.33 | 0.387538E+09 | 549.50 | 01-MAR-14:00 | 14.70 | 8.33 |
April | 0.305653E+10 | 9716.69 | 07-APR-12:30 | 26.15 | 15.90 | 0.359750E+09 | 549.51 | 10-APR-13:09 | 20.10 | 10.10 |
May | 0.465536E+10 | 16254.71 | 29-MAY-13:43 | 26.28 | 17.36 | 0.418392E+09 | 550.02 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.641353E+10 | 14076.46 | 25-JUN-13:32 | 26.70 | 23.10 | 0.434143E+09 | 549.87 | 19-JUN-13:50 | 26.70 | 23.10 |
July | 0.768029E+10 | 16337.02 | 04-JUL-12:53 | 27.80 | 18.77 | 0.405823E+09 | 549.96 | 10-JUL-13:00 | 32.80 | 20.89 |
August | 0.929602E+10 | 16604.51 | 13-AUG-12:32 | 30.93 | 19.36 | 0.454772E+09 | 549.98 | 17-AUG-13:50 | 31.10 | 24.82 |
September | 0.680724E+10 | 16876.02 | 04-SEP-13:12 | 26.10 | 18.36 | 0.397953E+09 | 554.65 | 28-SEP-13:20 | 23.17 | 13.55 |
October | 0.597633E+10 | 16617.80 | 22-OCT-12:43 | 22.02 | 16.80 | 0.402846E+09 | 549.93 | 13-OCT-13:39 | 22.02 | 16.80 |
November | 0.207361E+10 | 10086.66 | 02-NOV-13:10 | 15.68 | 8.29 | 0.355073E+09 | 549.52 | 02-NOV-13:50 | 16.02 | 8.62 |
December | 0.106674E+10 | 5349.03 | 21-DEC-13:30 | 3.05 | -1.7 | 0.326718E+09 | 549.49 | 14-DEC-14:09 | 3.05 | -1.7 |
Annual Sum or Average | 0.512846E+11 | 0.458323E+10 | ||||||||
Minimum of Months | 0.821304E+09 | 5317.95 | 3.05 | -1.7 | 0.307378E+09 | 549.49 | -1.7 | -5.1 | ||
Maximum of Months | 0.929602E+10 | 16876.02 | 30.93 | 23.10 | 0.454772E+09 | 554.65 | 32.80 | 24.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218245E+09 | 1505.54 | 19-JAN-15:50 | 8.40 | 3.05 | 0.195521E+09 | 312.34 | 19-JAN-15:00 | 8.30 | 2.94 |
February | 0.295268E+09 | 1654.53 | 22-FEB-16:30 | 3.85 | -0.7 | 0.179813E+09 | 335.88 | 22-FEB-16:40 | 3.67 | -0.7 |
March | 0.111018E+10 | 4850.77 | 29-MAR-16:00 | 7.20 | 4.88 | 0.227506E+09 | 347.84 | 02-MAR-14:00 | 7.20 | 4.88 |
April | 0.204343E+10 | 7649.48 | 07-APR-15:40 | 25.60 | 16.07 | 0.216986E+09 | 347.85 | 26-APR-13:00 | 18.30 | 12.92 |
May | 0.363396E+10 | 11662.35 | 29-MAY-14:23 | 25.85 | 17.23 | 0.259564E+09 | 347.87 | 15-MAY-13:00 | 25.85 | 17.23 |
June | 0.509869E+10 | 14282.93 | 18-JUN-16:02 | 25.50 | 22.07 | 0.273954E+09 | 347.86 | 22-JUN-13:30 | 29.15 | 17.46 |
July | 0.568774E+10 | 14269.77 | 02-JUL-16:02 | 24.90 | 20.78 | 0.256534E+09 | 347.87 | 11-JUL-13:50 | 28.72 | 17.86 |
August | 0.629143E+10 | 14261.59 | 13-AUG-15:52 | 30.00 | 20.46 | 0.287220E+09 | 347.86 | 08-AUG-13:39 | 30.00 | 20.46 |
September | 0.382069E+10 | 13203.74 | 10-SEP-15:32 | 23.67 | 13.25 | 0.247385E+09 | 347.86 | 11-SEP-13:09 | 20.60 | 12.01 |
October | 0.275009E+10 | 7209.84 | 04-OCT-15:30 | 23.35 | 19.12 | 0.240525E+09 | 347.86 | 12-OCT-13:00 | 20.60 | 17.37 |
November | 0.768843E+09 | 3354.54 | 03-NOV-15:30 | 16.10 | 10.65 | 0.203104E+09 | 347.83 | 03-NOV-13:00 | 16.10 | 10.65 |
December | 0.241641E+09 | 1458.33 | 08-DEC-15:40 | 6.30 | 2.04 | 0.188840E+09 | 305.20 | 08-DEC-15:50 | 6.20 | 1.96 |
Annual Sum or Average | 0.319602E+11 | 0.277695E+10 | ||||||||
Minimum of Months | 0.218245E+09 | 1458.33 | 3.85 | -0.7 | 0.179813E+09 | 305.20 | 3.67 | -0.7 | ||
Maximum of Months | 0.629143E+10 | 14282.93 | 30.00 | 22.07 | 0.287220E+09 | 347.87 | 30.00 | 20.46 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190584E+09 | 1130.63 | 20-JAN-15:00 | 7.80 | 3.97 | 0.305734E+09 | 418.36 | 20-JAN-14:00 | 7.80 | 3.97 |
February | 0.161650E+09 | 1136.20 | 24-FEB-14:10 | 9.22 | 3.12 | 0.278197E+09 | 419.38 | 24-FEB-14:20 | 9.03 | 2.95 |
March | 0.853952E+09 | 1453.42 | 28-MAR-14:00 | 13.30 | 8.41 | 0.345129E+09 | 492.85 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.150281E+10 | 2178.47 | 10-APR-14:00 | 20.60 | 10.45 | 0.339936E+09 | 549.48 | 07-APR-13:50 | 20.60 | 10.45 |
May | 0.266700E+10 | 4481.49 | 30-MAY-14:00 | 29.40 | 16.93 | 0.414989E+09 | 549.51 | 15-MAY-13:00 | 29.40 | 16.93 |
June | 0.437250E+10 | 6096.28 | 26-JUN-06:03 | 21.97 | 17.81 | 0.434302E+09 | 549.50 | 23-JUN-13:30 | 21.97 | 17.81 |
July | 0.550055E+10 | 7543.53 | 10-JUL-04:02 | 26.10 | 21.38 | 0.405236E+09 | 549.50 | 12-JUL-13:00 | 28.30 | 19.52 |
August | 0.583091E+10 | 6987.11 | 14-AUG-06:03 | 23.48 | 21.76 | 0.454668E+09 | 549.50 | 08-AUG-13:30 | 23.48 | 21.76 |
September | 0.390163E+10 | 5131.96 | 01-SEP-14:30 | 30.85 | 17.41 | 0.400527E+09 | 549.51 | 19-SEP-09:09 | 18.58 | 14.06 |
October | 0.271080E+10 | 3818.07 | 05-OCT-14:00 | 23.30 | 18.86 | 0.403495E+09 | 549.50 | 16-OCT-09:20 | 17.07 | 14.18 |
November | 0.127674E+10 | 1659.43 | 03-NOV-14:10 | 17.70 | 10.72 | 0.339077E+09 | 543.36 | 03-NOV-13:00 | 17.70 | 10.72 |
December | 0.407252E+09 | 1225.76 | 20-DEC-14:10 | 9.72 | 5.77 | 0.297667E+09 | 439.53 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.293764E+11 | 0.441895E+10 | ||||||||
Minimum of Months | 0.161650E+09 | 1130.63 | 7.80 | 3.12 | 0.278197E+09 | 418.36 | 7.80 | 2.95 | ||
Maximum of Months | 0.583091E+10 | 7543.53 | 30.85 | 21.76 | 0.454668E+09 | 549.51 | 29.40 | 21.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234532E+09 | 1016.77 | 27-JAN-10:20 | 4.60 | 1.51 | 0.195901E+09 | 295.49 | 27-JAN-10:30 | 4.70 | 1.53 |
February | 0.303764E+09 | 1014.48 | 22-FEB-10:10 | 0.87 | -3.0 | 0.178745E+09 | 295.49 | 22-FEB-10:20 | 1.13 | -2.8 |
March | 0.995714E+09 | 1929.67 | 29-MAR-09:40 | 6.33 | 3.26 | 0.234545E+09 | 347.87 | 29-MAR-09:09 | 6.33 | 3.26 |
April | 0.158723E+10 | 3936.81 | 28-APR-09:20 | 16.47 | 9.08 | 0.231377E+09 | 347.88 | 26-APR-09:00 | 16.47 | 9.08 |
May | 0.281801E+10 | 8562.40 | 29-MAY-09:02 | 26.20 | 16.88 | 0.267893E+09 | 348.12 | 30-MAY-09:00 | 27.80 | 17.82 |
June | 0.400892E+10 | 8225.17 | 05-JUN-06:02 | 16.47 | 13.09 | 0.275545E+09 | 348.12 | 26-JUN-09:00 | 26.10 | 20.11 |
July | 0.488729E+10 | 9443.91 | 09-JUL-09:32 | 29.43 | 25.37 | 0.257073E+09 | 348.44 | 14-JUL-09:00 | 30.60 | 21.74 |
August | 0.578088E+10 | 8792.71 | 20-AUG-10:02 | 24.27 | 15.52 | 0.288367E+09 | 348.27 | 18-AUG-09:30 | 24.27 | 15.52 |
September | 0.377137E+10 | 11084.80 | 04-SEP-10:12 | 25.60 | 17.90 | 0.254723E+09 | 348.08 | 06-SEP-09:30 | 26.15 | 19.35 |
October | 0.277824E+10 | 4818.97 | 05-OCT-09:30 | 19.45 | 17.11 | 0.261461E+09 | 347.89 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.113638E+10 | 2167.91 | 03-NOV-09:30 | 13.05 | 8.24 | 0.224196E+09 | 347.87 | 02-NOV-09:09 | 13.05 | 8.24 |
December | 0.513521E+09 | 1128.10 | 20-DEC-09:50 | 7.93 | 4.87 | 0.193466E+09 | 317.35 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.288158E+11 | 0.286329E+10 | ||||||||
Minimum of Months | 0.234532E+09 | 1014.48 | 0.87 | -3.0 | 0.178745E+09 | 295.49 | 1.13 | -2.8 | ||
Maximum of Months | 0.578088E+10 | 11084.80 | 29.43 | 25.37 | 0.288367E+09 | 348.44 | 30.60 | 21.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214761E+09 | 1487.10 | 07-JAN-14:10 | 0.60 | -4.3 | 0.292726E+09 | 495.88 | 19-JAN-14:39 | 9.07 | 3.63 |
February | 0.277308E+09 | 1664.66 | 25-FEB-13:30 | 3.05 | -1.7 | 0.267211E+09 | 481.88 | 02-FEB-14:39 | 3.05 | -1.7 |
March | 0.843957E+09 | 3328.82 | 03-MAR-13:35 | 14.80 | 8.43 | 0.346136E+09 | 549.50 | 28-MAR-13:09 | 13.80 | 8.65 |
April | 0.150889E+10 | 7218.76 | 07-APR-12:00 | 25.60 | 15.40 | 0.332800E+09 | 549.51 | 10-APR-13:09 | 20.10 | 10.10 |
May | 0.271431E+10 | 11259.85 | 30-MAY-12:00 | 29.40 | 17.58 | 0.394356E+09 | 576.52 | 30-MAY-12:09 | 29.50 | 17.65 |
June | 0.510556E+10 | 13650.30 | 19-JUN-12:00 | 36.70 | 24.28 | 0.430139E+09 | 710.41 | 19-JUN-12:09 | 36.42 | 24.23 |
July | 0.743153E+10 | 12769.73 | 07-JUL-12:00 | 33.90 | 23.31 | 0.406708E+09 | 658.05 | 07-JUL-12:09 | 33.72 | 23.31 |
August | 0.951931E+10 | 13127.49 | 13-AUG-13:12 | 31.30 | 19.70 | 0.457250E+09 | 653.24 | 18-AUG-12:09 | 32.88 | 20.21 |
September | 0.635708E+10 | 13858.69 | 04-SEP-14:52 | 25.00 | 18.55 | 0.399268E+09 | 618.68 | 01-SEP-12:09 | 25.00 | 18.55 |
October | 0.510287E+10 | 13441.63 | 22-OCT-12:43 | 22.02 | 16.80 | 0.404217E+09 | 563.02 | 04-OCT-13:20 | 22.02 | 16.80 |
November | 0.133971E+10 | 6964.96 | 02-NOV-12:20 | 15.20 | 8.07 | 0.334235E+09 | 549.51 | 08-NOV-14:50 | 13.68 | 11.16 |
December | 0.509884E+09 | 2696.36 | 02-DEC-14:00 | 6.70 | 1.42 | 0.295380E+09 | 525.95 | 18-DEC-14:50 | 6.38 | 2.66 |
Annual Sum or Average | 0.409252E+11 | 0.436043E+10 | ||||||||
Minimum of Months | 0.214761E+09 | 1487.10 | 0.60 | -4.3 | 0.267211E+09 | 481.88 | 3.05 | -1.7 | ||
Maximum of Months | 0.951931E+10 | 13858.69 | 36.70 | 24.28 | 0.457250E+09 | 710.41 | 36.42 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241098E+09 | 1197.93 | 20-JAN-16:00 | 7.20 | 3.80 | 0.196324E+09 | 315.98 | 20-JAN-16:10 | 6.93 | 3.71 |
February | 0.276229E+09 | 1248.33 | 22-FEB-16:30 | 3.85 | -0.7 | 0.179819E+09 | 326.62 | 22-FEB-16:40 | 3.67 | -0.7 |
March | 0.102132E+10 | 3009.23 | 27-MAR-16:50 | 21.28 | 15.57 | 0.228695E+09 | 347.83 | 03-MAR-14:00 | 21.28 | 15.57 |
April | 0.160292E+10 | 5272.01 | 10-APR-16:00 | 20.00 | 11.13 | 0.221910E+09 | 347.84 | 07-APR-13:09 | 20.00 | 11.13 |
May | 0.265326E+10 | 6596.97 | 30-MAY-16:00 | 28.30 | 17.60 | 0.263062E+09 | 347.87 | 15-MAY-13:00 | 28.30 | 17.60 |
June | 0.418438E+10 | 10915.25 | 04-JUN-16:12 | 21.83 | 14.55 | 0.275394E+09 | 347.85 | 22-JUN-09:09 | 25.68 | 16.96 |
July | 0.486863E+10 | 8968.03 | 02-JUL-16:02 | 24.90 | 20.78 | 0.256908E+09 | 347.86 | 12-JUL-13:00 | 28.30 | 19.52 |
August | 0.576241E+10 | 11022.52 | 13-AUG-15:52 | 30.00 | 20.46 | 0.288312E+09 | 347.86 | 08-AUG-13:30 | 30.00 | 20.46 |
September | 0.370881E+10 | 11318.04 | 04-SEP-16:52 | 24.40 | 18.66 | 0.253882E+09 | 347.86 | 19-SEP-09:09 | 18.58 | 14.06 |
October | 0.284806E+10 | 6261.91 | 04-OCT-15:50 | 22.98 | 19.12 | 0.258370E+09 | 347.86 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.106158E+10 | 3202.90 | 03-NOV-15:30 | 16.10 | 10.65 | 0.216649E+09 | 347.85 | 08-NOV-14:00 | 13.30 | 11.09 |
December | 0.424326E+09 | 1203.29 | 08-DEC-15:40 | 6.30 | 2.04 | 0.192336E+09 | 317.23 | 08-DEC-15:50 | 6.20 | 1.96 |
Annual Sum or Average | 0.286530E+11 | 0.283166E+10 | ||||||||
Minimum of Months | 0.241098E+09 | 1197.93 | 3.85 | -0.7 | 0.179819E+09 | 315.98 | 3.67 | -0.7 | ||
Maximum of Months | 0.576241E+10 | 11318.04 | 30.00 | 20.78 | 0.288312E+09 | 347.87 | 30.00 | 20.46 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227988E+09 | 1168.36 | 20-JAN-15:10 | 7.70 | 3.95 | 0.306499E+09 | 435.04 | 20-JAN-14:00 | 7.70 | 3.95 |
February | 0.256318E+09 | 1190.43 | 24-FEB-15:10 | 8.22 | 2.19 | 0.279462E+09 | 438.23 | 24-FEB-14:00 | 8.22 | 2.19 |
March | 0.116502E+10 | 1592.18 | 27-MAR-16:00 | 22.20 | 16.34 | 0.358529E+09 | 539.11 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.191552E+10 | 3597.28 | 07-APR-15:20 | 25.60 | 16.01 | 0.359356E+09 | 549.50 | 07-APR-13:09 | 25.60 | 16.01 |
May | 0.352554E+10 | 7492.02 | 30-MAY-06:03 | 20.47 | 15.45 | 0.427741E+09 | 549.52 | 15-MAY-13:00 | 20.47 | 15.45 |
June | 0.538272E+10 | 8559.07 | 26-JUN-06:03 | 21.97 | 17.81 | 0.435666E+09 | 549.56 | 19-JUN-13:30 | 21.97 | 17.81 |
July | 0.623925E+10 | 10123.09 | 09-JUL-15:22 | 27.20 | 24.16 | 0.405921E+09 | 549.68 | 07-JUL-13:50 | 27.20 | 24.16 |
August | 0.629816E+10 | 8651.43 | 14-AUG-04:02 | 22.20 | 19.79 | 0.455081E+09 | 549.51 | 08-AUG-13:20 | 22.20 | 19.79 |
September | 0.397861E+10 | 5636.78 | 01-SEP-14:30 | 30.85 | 17.41 | 0.400139E+09 | 549.51 | 19-SEP-09:09 | 18.58 | 14.06 |
October | 0.265208E+10 | 4092.68 | 05-OCT-14:00 | 23.30 | 18.86 | 0.400501E+09 | 549.50 | 16-OCT-09:20 | 17.07 | 14.18 |
November | 0.108017E+10 | 1786.75 | 03-NOV-14:00 | 17.80 | 10.67 | 0.334169E+09 | 549.48 | 03-NOV-13:39 | 17.80 | 10.67 |
December | 0.348853E+09 | 1215.45 | 20-DEC-14:00 | 10.00 | 5.91 | 0.297220E+09 | 446.23 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.330702E+11 | 0.446028E+10 | ||||||||
Minimum of Months | 0.227988E+09 | 1168.36 | 7.70 | 2.19 | 0.279462E+09 | 435.04 | 7.70 | 2.19 | ||
Maximum of Months | 0.629816E+10 | 10123.09 | 30.85 | 24.16 | 0.455081E+09 | 549.68 | 27.20 | 24.16 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.271991E+09 | 1253.21 | 19-JAN-10:00 | 7.80 | 4.14 | 0.143989E+09 | 299.36 | 19-JAN-09:00 | 7.80 | 4.14 |
February | 0.394414E+09 | 1312.61 | 22-FEB-09:55 | 0.60 | -3.2 | 0.132154E+09 | 310.64 | 22-FEB-09:00 | 0.60 | -3.2 |
March | 0.127364E+10 | 3623.11 | 29-MAR-09:00 | 5.60 | 2.98 | 0.174940E+09 | 338.72 | 29-MAR-10:20 | 7.43 | 3.94 |
April | 0.208045E+10 | 6137.98 | 28-APR-08:40 | 15.53 | 8.75 | 0.171547E+09 | 338.73 | 26-APR-10:09 | 15.53 | 8.75 |
May | 0.363036E+10 | 12707.32 | 28-MAY-08:32 | 20.20 | 12.71 | 0.199165E+09 | 338.94 | 31-MAY-08:00 | 25.00 | 19.48 |
June | 0.463413E+10 | 12332.91 | 04-JUN-09:32 | 24.03 | 12.91 | 0.203491E+09 | 341.53 | 26-JUN-07:19 | 23.50 | 18.22 |
July | 0.532964E+10 | 13820.15 | 02-JUL-08:31 | 25.20 | 21.54 | 0.190557E+09 | 343.24 | 17-JUL-07:19 | 24.63 | 20.35 |
August | 0.592196E+10 | 11817.31 | 27-AUG-09:53 | 26.10 | 21.81 | 0.212827E+09 | 340.14 | 22-AUG-07:19 | 26.10 | 21.81 |
September | 0.375881E+10 | 13465.49 | 04-SEP-08:22 | 23.35 | 18.64 | 0.186909E+09 | 338.98 | 06-SEP-08:00 | 25.60 | 19.05 |
October | 0.272226E+10 | 5557.02 | 05-OCT-09:00 | 18.90 | 16.77 | 0.189047E+09 | 338.73 | 16-OCT-08:39 | 15.77 | 13.14 |
November | 0.106015E+10 | 2353.00 | 03-NOV-09:00 | 12.80 | 8.09 | 0.157891E+09 | 338.72 | 03-NOV-12:20 | 16.47 | 10.10 |
December | 0.450391E+09 | 1348.03 | 20-DEC-09:40 | 7.57 | 4.72 | 0.140535E+09 | 316.15 | 20-DEC-09:50 | 7.93 | 4.87 |
Annual Sum or Average | 0.315282E+11 | 0.210305E+10 | ||||||||
Minimum of Months | 0.271991E+09 | 1253.21 | 0.60 | -3.2 | 0.132154E+09 | 299.36 | 0.60 | -3.2 | ||
Maximum of Months | 0.592196E+10 | 13820.15 | 26.10 | 21.81 | 0.212827E+09 | 343.24 | 26.10 | 21.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104441E+10 | 5556.29 | 19-JAN-13:30 | 9.40 | 3.94 | 0.340313E+09 | 549.50 | 30-JAN-14:30 | 2.80 | -1.1 |
February | 0.131241E+10 | 6114.39 | 02-FEB-13:50 | 5.78 | -0.8 | 0.315683E+09 | 549.49 | 03-FEB-14:00 | -1.7 | -5.1 |
March | 0.276545E+10 | 8090.44 | 03-MAR-13:25 | 14.70 | 8.33 | 0.399768E+09 | 549.50 | 23-MAR-13:00 | 5.00 | 1.08 |
April | 0.322831E+10 | 9020.46 | 07-APR-12:40 | 26.33 | 16.06 | 0.372175E+09 | 549.80 | 07-APR-13:09 | 26.60 | 16.32 |
May | 0.454620E+10 | 11029.94 | 28-MAY-13:53 | 25.60 | 14.65 | 0.427684E+09 | 550.17 | 30-MAY-13:50 | 29.50 | 17.11 |
June | 0.613748E+10 | 11327.58 | 25-JUN-13:32 | 26.70 | 23.10 | 0.435519E+09 | 549.83 | 19-JUN-13:30 | 26.70 | 23.10 |
July | 0.723616E+10 | 14491.31 | 04-JUL-12:53 | 27.80 | 18.77 | 0.406080E+09 | 550.01 | 10-JUL-13:50 | 32.70 | 20.82 |
August | 0.885378E+10 | 14925.43 | 20-AUG-12:32 | 27.43 | 15.69 | 0.455490E+09 | 553.75 | 30-AUG-13:09 | 27.48 | 15.59 |
September | 0.678486E+10 | 16090.63 | 04-SEP-11:42 | 26.02 | 17.75 | 0.402090E+09 | 568.22 | 28-SEP-13:09 | 22.98 | 13.55 |
October | 0.634551E+10 | 14919.15 | 15-OCT-13:13 | 20.77 | 13.05 | 0.412116E+09 | 560.21 | 04-OCT-13:09 | 20.77 | 13.05 |
November | 0.252585E+10 | 10349.52 | 02-NOV-12:50 | 15.50 | 8.17 | 0.371599E+09 | 549.66 | 02-NOV-13:00 | 16.10 | 8.71 |
December | 0.141882E+10 | 6297.39 | 21-DEC-13:30 | 3.05 | -1.7 | 0.339150E+09 | 549.49 | 18-DEC-10:09 | 3.05 | -1.7 |
Annual Sum or Average | 0.521992E+11 | 0.467767E+10 | ||||||||
Minimum of Months | 0.104441E+10 | 5556.29 | 3.05 | -1.7 | 0.315683E+09 | 549.49 | -1.7 | -5.1 | ||
Maximum of Months | 0.885378E+10 | 16090.63 | 27.80 | 23.10 | 0.455490E+09 | 568.22 | 32.70 | 23.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.312147E+09 | 1456.39 | 20-JAN-16:00 | 7.20 | 3.80 | 0.197327E+09 | 327.05 | 20-JAN-16:10 | 6.93 | 3.71 |
February | 0.394174E+09 | 1973.04 | 24-FEB-15:30 | 8.05 | 2.04 | 0.181940E+09 | 338.68 | 22-FEB-16:00 | 8.05 | 2.04 |
March | 0.137951E+10 | 4873.79 | 29-MAR-16:00 | 7.20 | 4.88 | 0.232827E+09 | 347.84 | 02-MAR-14:00 | 7.20 | 4.88 |
April | 0.217923E+10 | 7263.33 | 10-APR-16:00 | 20.00 | 11.13 | 0.224764E+09 | 347.85 | 10-APR-13:09 | 20.00 | 11.13 |
May | 0.352972E+10 | 9227.57 | 28-MAY-15:53 | 23.90 | 15.53 | 0.266628E+09 | 347.87 | 15-MAY-13:00 | 23.90 | 15.53 |
June | 0.488303E+10 | 13784.02 | 18-JUN-17:12 | 24.43 | 21.80 | 0.275302E+09 | 347.85 | 23-JUN-09:09 | 27.25 | 18.76 |
July | 0.536822E+10 | 14202.59 | 02-JUL-16:31 | 24.60 | 20.65 | 0.256849E+09 | 347.86 | 17-JUL-09:20 | 27.97 | 21.33 |
August | 0.599870E+10 | 12929.00 | 13-AUG-15:52 | 30.00 | 20.46 | 0.287954E+09 | 347.86 | 25-AUG-13:00 | 26.70 | 15.26 |
September | 0.378080E+10 | 13210.14 | 04-SEP-14:22 | 25.55 | 18.53 | 0.251789E+09 | 347.86 | 15-SEP-13:00 | 22.80 | 15.50 |
October | 0.290129E+10 | 6947.33 | 04-OCT-15:30 | 23.35 | 19.12 | 0.250748E+09 | 347.85 | 12-OCT-13:00 | 20.60 | 17.37 |
November | 0.103257E+10 | 3539.13 | 03-NOV-15:30 | 16.10 | 10.65 | 0.210800E+09 | 347.85 | 08-NOV-14:00 | 13.30 | 11.09 |
December | 0.406405E+09 | 1419.31 | 08-DEC-15:40 | 6.30 | 2.04 | 0.191701E+09 | 320.92 | 08-DEC-15:50 | 6.20 | 1.96 |
Annual Sum or Average | 0.321658E+11 | 0.282863E+10 | ||||||||
Minimum of Months | 0.312147E+09 | 1419.31 | 6.30 | 2.04 | 0.181940E+09 | 320.92 | 6.20 | 1.96 | ||
Maximum of Months | 0.599870E+10 | 14202.59 | 30.00 | 21.80 | 0.287954E+09 | 347.87 | 27.97 | 21.33 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351577E+09 | 23578.87 | 02-JAN-05:01 | -12.1 |
February | 1120521.60 | 18675.36 | 06-FEB-07:01 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.352697E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.351577E+09 | 23578.87 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.576441E+10 | 16145.79 | 02-JAN-06:12 | -11.7 |
February | 0.471103E+10 | 16768.86 | 06-FEB-06:08 | -12.9 |
March | 0.208990E+10 | 10287.24 | 20-MAR-06:02 | -0.6 |
April | 0.971369E+09 | 8015.86 | 03-APR-06:01 | 2.38 |
May | 0.230207E+09 | 5350.96 | 30-MAY-04:03 | 17.80 |
June | 48060316.83 | 4852.24 | 05-JUN-05:03 | 14.68 |
July | 26422124.56 | 4833.08 | 05-JUL-04:02 | 20.60 |
August | 41265423.45 | 5614.35 | 14-AUG-04:02 | 22.20 |
September | 0.154529E+09 | 5314.59 | 05-SEP-04:02 | 20.52 |
October | 0.557781E+09 | 4528.61 | 19-OCT-05:02 | 5.37 |
November | 0.226732E+10 | 12301.29 | 24-NOV-06:13 | -4.4 |
December | 0.395419E+10 | 10390.65 | 11-DEC-06:13 | 1.70 |
Annual Sum or Average | 0.208165E+11 | |||
Minimum of Months | 26422124.56 | 4528.61 | -12.9 | |
Maximum of Months | 0.576441E+10 | 16768.86 | 22.20 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.287550E+10 | 10522.09 | 02-JAN-07:06 | -11.6 |
February | 0.219228E+10 | 8807.78 | 06-FEB-07:11 | -13.1 |
March | 0.125598E+10 | 3120.39 | 20-MAR-06:03 | -0.6 |
April | 0.450476E+09 | 3441.84 | 16-APR-15:30 | 21.40 |
May | 99889419.78 | 2331.36 | 14-MAY-14:17 | 14.23 |
June | 19273956.23 | 2458.81 | 02-JUN-05:03 | 13.90 |
July | 24896414.49 | 2536.51 | 09-JUL-14:02 | 30.95 |
August | 23391915.30 | 2493.06 | 15-AUG-04:02 | 24.40 |
September | 29028885.99 | 3065.19 | 03-SEP-09:42 | 24.13 |
October | 0.153013E+09 | 3495.36 | 09-OCT-11:10 | 12.98 |
November | 0.120770E+10 | 4506.02 | 24-NOV-07:02 | -4.3 |
December | 0.182343E+10 | 4515.72 | 26-DEC-07:02 | 6.70 |
Annual Sum or Average | 0.101549E+11 | |||
Minimum of Months | 19273956.23 | 2331.36 | -13.1 | |
Maximum of Months | 0.287550E+10 | 10522.09 | 30.95 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224963E+10 | 9329.17 | 02-JAN-07:01 | -11.6 |
February | 0.158720E+10 | 4667.51 | 06-FEB-08:55 | -12.2 |
March | 0.836316E+09 | 3566.70 | 22-MAR-07:19 | -2.6 |
April | 0.238281E+09 | 6018.43 | 12-APR-05:03 | 4.32 |
May | 27886153.00 | 4988.97 | 15-MAY-05:03 | 8.07 |
June | 25813547.92 | 4000.55 | 12-JUN-04:03 | 18.80 |
July | 25281899.99 | 3616.20 | 27-JUL-04:03 | 21.78 |
August | 28154878.67 | 4091.45 | 08-AUG-04:03 | 15.50 |
September | 33219753.88 | 4477.44 | 18-SEP-04:03 | 16.88 |
October | 53534678.59 | 6339.78 | 27-OCT-05:03 | 6.02 |
November | 0.708854E+09 | 7497.73 | 06-NOV-06:01 | 5.00 |
December | 0.131841E+10 | 3635.52 | 21-DEC-08:16 | -0.4 |
Annual Sum or Average | 0.713258E+10 | |||
Minimum of Months | 25281899.99 | 3566.70 | -12.2 | |
Maximum of Months | 0.224963E+10 | 9329.17 | 21.78 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.850713E+09 | 24679.81 | 02-JAN-05:01 | -12.1 |
February | 0.258902E+09 | 21764.76 | 06-FEB-06:01 | -12.9 |
March | 14155549.24 | 19532.96 | 20-MAR-06:01 | -0.6 |
April | 1796792.29 | 18937.10 | 03-APR-06:01 | 2.38 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 37663201.50 | 19936.54 | 24-NOV-06:01 | -4.4 |
December | 68779506.28 | 20010.00 | 26-DEC-06:01 | 6.20 |
Annual Sum or Average | 0.123201E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 0.850713E+09 | 24679.81 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265343E+10 | 32978.15 | 02-JAN-01:22 | -11.4 |
February | 0.169844E+10 | 32396.34 | 06-FEB-05:11 | -13.1 |
March | 0.326269E+09 | 29230.56 | 20-MAR-05:01 | -1.5 |
April | 58549333.46 | 28055.19 | 03-APR-05:01 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.561792E+09 | 30032.05 | 24-NOV-05:01 | -4.0 |
December | 0.905224E+09 | 30146.09 | 26-DEC-05:01 | 5.68 |
Annual Sum or Average | 0.620370E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.1 | |
Maximum of Months | 0.265343E+10 | 32978.15 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.461573E+10 | 11500.69 | 01-JAN-22:42 | -9.9 |
February | 0.387786E+10 | 11496.88 | 06-FEB-01:52 | -13.3 |
March | 0.115030E+10 | 10391.65 | 13-MAR-04:01 | -0.1 |
April | 0.262404E+09 | 9665.85 | 03-APR-04:03 | 2.80 |
May | 2936082.94 | 8304.82 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 39270393.46 | 8347.90 | 31-OCT-06:02 | 5.68 |
November | 0.130128E+10 | 10539.66 | 20-NOV-05:01 | 0.50 |
December | 0.281543E+10 | 11269.93 | 31-DEC-22:02 | -7.3 |
Annual Sum or Average | 0.140652E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.461573E+10 | 11500.69 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.260351E+10 | 11924.49 | 01-JAN-22:42 | -9.9 |
February | 0.196566E+10 | 11927.48 | 06-FEB-01:52 | -13.3 |
March | 0.549273E+09 | 10815.29 | 13-MAR-04:01 | -0.1 |
April | 0.140643E+09 | 9726.50 | 03-APR-05:01 | 2.70 |
May | 1142999.89 | 3974.06 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 20063001.37 | 7312.10 | 31-OCT-06:02 | 5.68 |
November | 0.674043E+09 | 10989.58 | 20-NOV-05:01 | 0.50 |
December | 0.151458E+10 | 11649.64 | 31-DEC-22:02 | -7.3 |
Annual Sum or Average | 0.746892E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.260351E+10 | 11927.48 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319475E+10 | 15112.12 | 02-JAN-01:22 | -11.4 |
February | 0.240630E+10 | 15101.19 | 06-FEB-04:32 | -13.3 |
March | 0.757852E+09 | 13716.88 | 13-MAR-04:01 | -0.1 |
April | 0.227772E+09 | 12398.42 | 03-APR-05:01 | 2.70 |
May | 4522481.03 | 8804.52 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 20692261.19 | 11008.53 | 31-OCT-06:02 | 5.68 |
November | 0.791389E+09 | 13856.03 | 20-NOV-05:01 | 0.50 |
December | 0.183662E+10 | 14667.71 | 31-DEC-22:02 | -7.3 |
Annual Sum or Average | 0.923989E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.319475E+10 | 15112.12 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.283177E+10 | 12966.12 | 01-JAN-22:42 | -9.9 |
February | 0.230085E+10 | 12968.48 | 06-FEB-01:52 | -13.3 |
March | 0.640096E+09 | 11747.17 | 13-MAR-04:01 | -0.1 |
April | 0.165518E+09 | 10549.47 | 03-APR-05:01 | 2.70 |
May | 3680206.23 | 5551.15 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 25355441.19 | 7261.77 | 31-OCT-06:02 | 5.68 |
November | 0.810338E+09 | 11975.33 | 20-NOV-05:01 | 0.50 |
December | 0.171587E+10 | 12606.84 | 31-DEC-22:02 | -7.3 |
Annual Sum or Average | 0.849349E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.283177E+10 | 12968.48 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259851E+10 | 8759.00 | 01-JAN-22:42 | -9.9 |
February | 0.212754E+10 | 8338.31 | 06-FEB-04:53 | -13.3 |
March | 0.486451E+09 | 7433.86 | 13-MAR-05:01 | -0.6 |
April | 69420463.15 | 7107.99 | 03-APR-05:01 | 2.70 |
May | 222682.15 | 1484.55 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.239221E+09 | 7359.10 | 24-NOV-06:01 | -4.4 |
December | 0.738086E+09 | 7264.12 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.625945E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.259851E+10 | 8759.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135164E+10 | 9511.58 | 01-JAN-22:42 | -9.9 |
February | 0.903936E+09 | 8892.88 | 06-FEB-05:01 | -13.2 |
March | 0.166656E+09 | 8027.39 | 20-MAR-05:01 | -1.5 |
April | 25536904.26 | 7672.59 | 03-APR-05:01 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 99853545.55 | 7926.80 | 24-NOV-06:01 | -4.4 |
December | 0.359142E+09 | 7936.80 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.290676E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.135164E+10 | 9511.58 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.587909E+10 | 14770.37 | 02-JAN-08:00 | -11.1 |
February | 0.511927E+10 | 14776.97 | 06-FEB-07:10 | -13.2 |
March | 0.347779E+10 | 12980.24 | 23-MAR-06:10 | -4.7 |
April | 0.172702E+10 | 11571.43 | 03-APR-06:10 | 2.38 |
May | 0.643359E+09 | 9957.29 | 01-MAY-06:10 | 7.67 |
June | 16641187.77 | 6656.61 | 02-JUN-06:06 | 13.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 79992915.70 | 8406.71 | 20-SEP-06:05 | 12.48 |
October | 0.481274E+09 | 9776.22 | 27-OCT-06:10 | 5.68 |
November | 0.223392E+10 | 12931.39 | 24-NOV-07:10 | -4.3 |
December | 0.389459E+10 | 12703.59 | 15-DEC-07:10 | -3.6 |
Annual Sum or Average | 0.235529E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.587909E+10 | 14776.97 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150644E+10 | 9834.27 | 01-JAN-22:42 | -9.9 |
February | 0.109271E+10 | 9165.31 | 06-FEB-05:01 | -13.2 |
March | 0.170656E+09 | 8217.01 | 13-MAR-05:01 | -0.6 |
April | 32648074.34 | 7791.81 | 03-APR-05:01 | 2.70 |
May | 203966.33 | 1359.78 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.131252E+09 | 8157.98 | 24-NOV-06:01 | -4.4 |
December | 0.406681E+09 | 8175.69 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.334059E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.150644E+10 | 9834.27 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.254526E+10 | 9724.72 | 01-JAN-20:42 | -8.0 |
February | 0.189954E+10 | 9538.47 | 06-FEB-00:32 | -13.3 |
March | 0.344180E+09 | 8293.20 | 13-MAR-04:02 | -0.1 |
April | 42647904.75 | 7809.69 | 03-APR-05:01 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 626599.86 | 3264.26 | 28-OCT-06:03 | 3.90 |
November | 0.435085E+09 | 8645.52 | 24-NOV-05:01 | -4.0 |
December | 0.106129E+10 | 8451.32 | 11-DEC-05:01 | 1.70 |
Annual Sum or Average | 0.632863E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.254526E+10 | 9724.72 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143087E+10 | 10991.52 | 01-JAN-22:42 | -9.9 |
February | 0.942378E+09 | 10798.85 | 06-FEB-00:32 | -13.3 |
March | 0.165587E+09 | 9139.26 | 20-MAR-05:01 | -1.5 |
April | 21574329.37 | 8770.42 | 03-APR-05:01 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 1032940.18 | 3350.71 | 28-OCT-06:03 | 3.90 |
November | 0.229842E+09 | 9777.10 | 24-NOV-05:01 | -4.0 |
December | 0.600180E+09 | 9600.06 | 11-DEC-05:01 | 1.70 |
Annual Sum or Average | 0.339147E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.143087E+10 | 10991.52 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163073E+10 | 13206.85 | 01-JAN-22:42 | -9.9 |
February | 0.101422E+10 | 12929.74 | 06-FEB-04:32 | -13.3 |
March | 0.202592E+09 | 11070.39 | 13-MAR-05:01 | -0.6 |
April | 36064058.87 | 10529.71 | 03-APR-05:01 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 64748.23 | 431.65 | 28-OCT-06:03 | 3.90 |
November | 0.223362E+09 | 11474.46 | 24-NOV-05:01 | -4.0 |
December | 0.632123E+09 | 11555.81 | 11-DEC-05:01 | 1.70 |
Annual Sum or Average | 0.373915E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.163073E+10 | 13206.85 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155285E+10 | 11109.52 | 01-JAN-22:42 | -9.9 |
February | 0.109807E+10 | 10912.06 | 06-FEB-00:32 | -13.3 |
March | 0.184896E+09 | 9145.36 | 13-MAR-05:01 | -0.6 |
April | 29952102.68 | 8693.89 | 03-APR-05:01 | 2.70 |
May | 133148.82 | 887.66 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 920234.01 | 3171.41 | 28-OCT-06:03 | 3.90 |
November | 0.273653E+09 | 9806.75 | 24-NOV-05:01 | -4.0 |
December | 0.645700E+09 | 9641.15 | 11-DEC-05:01 | 1.70 |
Annual Sum or Average | 0.378617E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.155285E+10 | 11109.52 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.208150E+11 | 18520.31 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.188385E+11 | 18520.31 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.216654E+11 | 18520.31 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.200796E+11 | 18520.31 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.212402E+11 | 18520.31 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.208620E+11 | 18520.31 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.204550E+11 | 18520.31 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.216654E+11 | 18520.31 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.200739E+11 | 18520.31 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.208179E+11 | 18520.31 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.203773E+11 | 18520.31 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.204522E+11 | 18520.31 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.247342E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.188385E+11 | 18520.31 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.216654E+11 | 18520.31 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.838844E+09 | 1168.55 | 02-JAN-16:40 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.726054E+09 | 1089.43 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.828143E+09 | 934.17 | 02-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.721015E+09 | 720.41 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.766461E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.755767E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.711101E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.798991E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.729455E+09 | 860.00 | 27-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.777988E+09 | 991.17 | 31-OCT-15:00 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.812987E+09 | 1168.55 | 06-NOV-16:49 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.823105E+09 | 1168.55 | 01-DEC-16:30 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.928991E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.711101E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.838844E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.527539E+09 | 739.79 | 02-JAN-16:40 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.458158E+09 | 695.14 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.524345E+09 | 636.69 | 02-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.457248E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.486906E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.480452E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.451845E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.507245E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.462074E+09 | 456.08 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.492047E+09 | 631.15 | 31-OCT-15:00 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.513739E+09 | 739.79 | 06-NOV-16:49 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.515168E+09 | 739.79 | 01-DEC-16:30 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.587677E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.451845E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.527539E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.821902E+09 | 1168.55 | 02-JAN-16:40 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.715651E+09 | 1083.98 | 15-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.824289E+09 | 867.64 | 16-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.721884E+09 | 720.41 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.768908E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.758804E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.713664E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.800772E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.728536E+09 | 838.10 | 27-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.771842E+09 | 966.12 | 31-OCT-15:00 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.803501E+09 | 1168.55 | 06-NOV-16:49 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.800499E+09 | 1168.55 | 01-DEC-16:30 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.923025E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.713664E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.824289E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522822E+09 | 739.74 | 02-JAN-16:40 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.454484E+09 | 682.60 | 15-FEB-16:00 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.521806E+09 | 583.92 | 16-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.456667E+09 | 515.57 | 14-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.485245E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.478718E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.450525E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.505830E+09 | 502.50 | 16-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.461414E+09 | 566.00 | 27-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.489375E+09 | 614.85 | 06-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.509579E+09 | 739.74 | 06-NOV-16:49 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.511646E+09 | 739.74 | 01-DEC-16:30 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.584811E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.450525E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.522822E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.836333E+09 | 1168.55 | 02-JAN-16:40 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.724258E+09 | 1085.84 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.827502E+09 | 923.03 | 02-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.720582E+09 | 720.41 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.766145E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.755377E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.710739E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.798775E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.728810E+09 | 846.32 | 27-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.776940E+09 | 983.39 | 31-OCT-15:00 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.811567E+09 | 1168.55 | 06-NOV-16:49 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.819820E+09 | 1168.55 | 01-DEC-16:30 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.927685E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.710739E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.836333E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.526533E+09 | 739.79 | 02-JAN-16:40 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.457382E+09 | 693.60 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.523977E+09 | 633.14 | 02-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.456983E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.486713E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.480164E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.451605E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.506998E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.461785E+09 | 456.08 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.491511E+09 | 627.46 | 31-OCT-15:00 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.513148E+09 | 739.79 | 06-NOV-16:49 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.513917E+09 | 739.79 | 01-DEC-16:30 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.587071E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.451605E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.526533E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.819225E+09 | 1168.55 | 02-JAN-16:40 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.714694E+09 | 1080.21 | 15-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.823918E+09 | 853.92 | 16-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.721461E+09 | 720.41 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.768528E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.758267E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.713230E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.800394E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.727981E+09 | 823.25 | 27-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.771321E+09 | 956.86 | 31-OCT-15:00 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.802187E+09 | 1168.55 | 06-NOV-16:49 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.799392E+09 | 1168.55 | 01-DEC-16:30 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.922060E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.713230E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.823918E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.521777E+09 | 739.74 | 02-JAN-16:40 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.453870E+09 | 680.54 | 15-FEB-16:00 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.521458E+09 | 578.64 | 16-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.456372E+09 | 508.12 | 14-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.485060E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.478515E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.450321E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.505576E+09 | 456.05 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.461017E+09 | 560.14 | 27-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.489094E+09 | 610.64 | 06-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.508988E+09 | 739.74 | 06-NOV-16:49 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.510516E+09 | 739.74 | 01-DEC-16:30 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.584256E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.450321E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.521777E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.838843E+09 | 1168.55 | 02-JAN-16:40 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.726054E+09 | 1089.43 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.828143E+09 | 934.16 | 02-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.721015E+09 | 720.41 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.766460E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.755766E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.711101E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.798991E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.729455E+09 | 859.98 | 27-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.777987E+09 | 991.16 | 31-OCT-15:00 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.812986E+09 | 1168.55 | 06-NOV-16:49 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.823105E+09 | 1168.55 | 01-DEC-16:30 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.928991E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.711101E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.838843E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.527538E+09 | 739.79 | 02-JAN-16:40 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.458158E+09 | 695.13 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.524345E+09 | 636.69 | 02-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.457247E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.486906E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.480452E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.451845E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.507245E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.462074E+09 | 456.08 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.492047E+09 | 631.14 | 31-OCT-15:00 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.513739E+09 | 739.79 | 06-NOV-16:49 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.515168E+09 | 739.79 | 01-DEC-16:30 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.587676E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.451845E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.527538E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.821901E+09 | 1168.55 | 02-JAN-16:40 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.715651E+09 | 1083.98 | 15-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.824289E+09 | 867.62 | 16-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.721884E+09 | 720.41 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.768908E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.758803E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.713664E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.800772E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.728535E+09 | 838.08 | 27-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.771842E+09 | 966.11 | 31-OCT-15:00 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.803500E+09 | 1168.55 | 06-NOV-16:49 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.800499E+09 | 1168.55 | 01-DEC-16:30 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.923025E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.713664E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.824289E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522821E+09 | 739.74 | 02-JAN-16:40 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.454483E+09 | 682.60 | 15-FEB-16:00 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.521806E+09 | 583.91 | 16-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.456667E+09 | 515.55 | 14-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.485245E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.478718E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.450525E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.505830E+09 | 502.48 | 16-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.461414E+09 | 565.98 | 27-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.489375E+09 | 614.84 | 06-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.509578E+09 | 739.74 | 06-NOV-16:49 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.511646E+09 | 739.74 | 01-DEC-16:30 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.584811E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.450525E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.522821E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.208150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.200796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.212402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.208620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.204550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.200739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.208179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.203773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.204522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.247342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.838844E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159043E+10 |
February | 0.901968E+09 | 0.726054E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141662E+10 |
March | 0.107774E+10 | 0.828143E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112708E+10 |
April | 0.956342E+09 | 0.721015E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 638148.39 | 0.753136E+09 |
May | 0.103597E+10 | 0.766461E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3131192.04 | 0.464212E+09 |
June | 0.103308E+10 | 0.755767E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20645665.92 | 0.250427E+09 |
July | 0.959235E+09 | 0.711101E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48286108.40 | 92401523.31 |
August | 0.107774E+10 | 0.798991E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58552707.61 | 0.114443E+09 |
September | 0.956342E+09 | 0.729455E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7355406.75 | 0.253292E+09 |
October | 0.994195E+09 | 0.777988E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108579.99 | 0.608097E+09 |
November | 0.984487E+09 | 0.812987E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108438E+10 |
December | 0.959235E+09 | 0.823105E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131859E+10 |
Annual Sum or Average | 0.119305E+11 | 0.928991E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138718E+09 | 0.907312E+10 |
Minimum of Months | 0.901968E+09 | 0.711101E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92401523.31 |
Maximum of Months | 0.107774E+10 | 0.838844E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58552707.61 | 0.159043E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.527539E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106083E+10 |
February | 0.571020E+09 | 0.458158E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.950188E+09 |
March | 0.682301E+09 | 0.524345E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760519E+09 |
April | 0.605444E+09 | 0.457248E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 418121.09 | 0.519529E+09 |
May | 0.655854E+09 | 0.486906E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1590450.53 | 0.315103E+09 |
June | 0.654023E+09 | 0.480452E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13665083.90 | 0.167670E+09 |
July | 0.607275E+09 | 0.451845E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31828200.83 | 61799133.66 |
August | 0.682301E+09 | 0.507245E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38116053.87 | 78410357.95 |
September | 0.605444E+09 | 0.462074E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4807764.76 | 0.175668E+09 |
October | 0.629407E+09 | 0.492047E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72385.26 | 0.418193E+09 |
November | 0.623262E+09 | 0.513739E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731692E+09 |
December | 0.607275E+09 | 0.515168E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882251E+09 |
Annual Sum or Average | 0.755301E+10 | 0.587677E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90498060.23 | 0.612185E+10 |
Minimum of Months | 0.571020E+09 | 0.451845E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61799133.66 |
Maximum of Months | 0.682301E+09 | 0.527539E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38116053.87 | 0.106083E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.821902E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162588E+10 |
February | 0.901968E+09 | 0.715651E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147360E+10 |
March | 0.107774E+10 | 0.824289E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118133E+10 |
April | 0.956342E+09 | 0.721884E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 626134.07 | 0.788326E+09 |
May | 0.103597E+10 | 0.768908E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2505490.30 | 0.470842E+09 |
June | 0.103308E+10 | 0.758804E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20204888.19 | 0.250712E+09 |
July | 0.959235E+09 | 0.713664E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47459803.01 | 93915104.95 |
August | 0.107774E+10 | 0.800772E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56487136.00 | 0.119804E+09 |
September | 0.956342E+09 | 0.728536E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7163051.60 | 0.274236E+09 |
October | 0.994195E+09 | 0.771842E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108204.25 | 0.674711E+09 |
November | 0.984487E+09 | 0.803501E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114314E+10 |
December | 0.959235E+09 | 0.800499E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138019E+10 |
Annual Sum or Average | 0.119305E+11 | 0.923025E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134555E+09 | 0.947668E+10 |
Minimum of Months | 0.901968E+09 | 0.713664E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93915104.95 |
Maximum of Months | 0.107774E+10 | 0.824289E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56487136.00 | 0.162588E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.522822E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106439E+10 |
February | 0.570983E+09 | 0.454484E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.953773E+09 |
March | 0.682256E+09 | 0.521806E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772254E+09 |
April | 0.605404E+09 | 0.456667E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 445846.79 | 0.518967E+09 |
May | 0.655811E+09 | 0.485245E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2341751.95 | 0.316755E+09 |
June | 0.653980E+09 | 0.478718E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13950988.65 | 0.174043E+09 |
July | 0.607235E+09 | 0.450525E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33033032.36 | 67511272.28 |
August | 0.682256E+09 | 0.505830E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38713438.24 | 81772923.33 |
September | 0.605404E+09 | 0.461414E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5030706.42 | 0.175192E+09 |
October | 0.629366E+09 | 0.489375E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72425.30 | 0.421244E+09 |
November | 0.623221E+09 | 0.509579E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725003E+09 |
December | 0.607235E+09 | 0.511646E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.885528E+09 |
Annual Sum or Average | 0.755252E+10 | 0.584811E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93588189.71 | 0.615644E+10 |
Minimum of Months | 0.570983E+09 | 0.450525E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67511272.28 |
Maximum of Months | 0.682256E+09 | 0.522822E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38713438.24 | 0.106439E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.836333E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895336E+09 |
February | 0.901968E+09 | 0.724258E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790385E+09 |
March | 0.107774E+10 | 0.827502E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629896E+09 |
April | 0.956342E+09 | 0.720582E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 449072.65 | 0.414052E+09 |
May | 0.103597E+10 | 0.766145E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2782786.59 | 0.243270E+09 |
June | 0.103308E+10 | 0.755377E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12833469.38 | 0.127109E+09 |
July | 0.959235E+09 | 0.710739E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29966232.36 | 43382038.10 |
August | 0.107774E+10 | 0.798775E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33467153.04 | 59251371.45 |
September | 0.956342E+09 | 0.728810E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4149317.61 | 0.144194E+09 |
October | 0.994195E+09 | 0.776940E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65147.55 | 0.364777E+09 |
November | 0.984487E+09 | 0.811567E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.660654E+09 |
December | 0.959235E+09 | 0.819820E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.775286E+09 |
Annual Sum or Average | 0.119305E+11 | 0.927685E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83713179.18 | 0.514759E+10 |
Minimum of Months | 0.901968E+09 | 0.710739E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43382038.10 |
Maximum of Months | 0.107774E+10 | 0.836333E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33467153.04 | 0.895336E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.526533E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598440E+09 |
February | 0.571020E+09 | 0.457382E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535740E+09 |
March | 0.682301E+09 | 0.523977E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430966E+09 |
April | 0.605444E+09 | 0.456983E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 232010.64 | 0.291075E+09 |
May | 0.655854E+09 | 0.486713E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 933521.48 | 0.171436E+09 |
June | 0.654023E+09 | 0.480164E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7763405.72 | 89187907.80 |
July | 0.607275E+09 | 0.451605E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17764427.60 | 31937718.98 |
August | 0.682301E+09 | 0.506998E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20682189.63 | 43663479.81 |
September | 0.605444E+09 | 0.461785E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2592774.38 | 0.103418E+09 |
October | 0.629407E+09 | 0.491511E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43431.12 | 0.255103E+09 |
November | 0.623262E+09 | 0.513148E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451148E+09 |
December | 0.607275E+09 | 0.513917E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522594E+09 |
Annual Sum or Average | 0.755301E+10 | 0.587071E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50011760.58 | 0.352471E+10 |
Minimum of Months | 0.571020E+09 | 0.451605E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31937718.98 |
Maximum of Months | 0.682301E+09 | 0.526533E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20682189.63 | 0.598440E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.819225E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802861E+10 |
February | 0.901968E+09 | 0.714694E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794524E+10 |
March | 0.107774E+10 | 0.823918E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716047E+10 |
April | 0.956342E+09 | 0.721461E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17319599.85 | 0.427210E+10 |
May | 0.103597E+10 | 0.768528E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69581910.02 | 0.255745E+10 |
June | 0.103308E+10 | 0.758267E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490955E+09 | 0.847602E+09 |
July | 0.959235E+09 | 0.713230E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103614E+10 | 0.123813E+09 |
August | 0.107774E+10 | 0.800394E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123823E+10 | 0.284404E+09 |
September | 0.956342E+09 | 0.727981E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205408E+09 | 0.124128E+10 |
October | 0.994195E+09 | 0.771321E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3034013.55 | 0.333815E+10 |
November | 0.984487E+09 | 0.802187E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601797E+10 |
December | 0.959235E+09 | 0.799392E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723140E+10 |
Annual Sum or Average | 0.119305E+11 | 0.922060E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306068E+10 | 0.490485E+11 |
Minimum of Months | 0.901968E+09 | 0.713230E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123813E+09 |
Maximum of Months | 0.107774E+10 | 0.823918E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123823E+10 | 0.802861E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.521777E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600486E+09 |
February | 0.570983E+09 | 0.453870E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535401E+09 |
March | 0.682256E+09 | 0.521458E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437675E+09 |
April | 0.605404E+09 | 0.456372E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 254210.11 | 0.291648E+09 |
May | 0.655811E+09 | 0.485060E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1437288.93 | 0.173183E+09 |
June | 0.653980E+09 | 0.478515E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7541071.22 | 94392346.55 |
July | 0.607235E+09 | 0.450321E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18066061.35 | 36214643.11 |
August | 0.682256E+09 | 0.505576E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20815975.54 | 46036450.85 |
September | 0.605404E+09 | 0.461017E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2634184.26 | 0.103663E+09 |
October | 0.629366E+09 | 0.489094E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43453.52 | 0.258523E+09 |
November | 0.623221E+09 | 0.508988E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444519E+09 |
December | 0.607235E+09 | 0.510516E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522916E+09 |
Annual Sum or Average | 0.755252E+10 | 0.584256E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50792244.93 | 0.354466E+10 |
Minimum of Months | 0.570983E+09 | 0.450321E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36214643.11 |
Maximum of Months | 0.682256E+09 | 0.521777E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20815975.54 | 0.600486E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.838843E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137639E+10 |
February | 0.901968E+09 | 0.726054E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122602E+10 |
March | 0.107774E+10 | 0.828143E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999797E+09 |
April | 0.956342E+09 | 0.721015E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 531520.75 | 0.672448E+09 |
May | 0.103597E+10 | 0.766460E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2888127.91 | 0.407166E+09 |
June | 0.103308E+10 | 0.755766E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18017535.69 | 0.215245E+09 |
July | 0.959235E+09 | 0.711101E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41832984.37 | 77687950.88 |
August | 0.107774E+10 | 0.798991E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49662667.28 | 98808274.69 |
September | 0.956342E+09 | 0.729455E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6169838.46 | 0.225063E+09 |
October | 0.994195E+09 | 0.777987E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95982.04 | 0.552416E+09 |
November | 0.984487E+09 | 0.812986E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.986787E+09 |
December | 0.959235E+09 | 0.823105E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117222E+10 |
Annual Sum or Average | 0.119305E+11 | 0.928991E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119199E+09 | 0.801004E+10 |
Minimum of Months | 0.901968E+09 | 0.711101E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77687950.88 |
Maximum of Months | 0.107774E+10 | 0.838843E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49662667.28 | 0.137639E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.527538E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917579E+09 |
February | 0.421807E+09 | 0.458158E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825963E+09 |
March | 0.502994E+09 | 0.524345E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673683E+09 |
April | 0.447140E+09 | 0.457247E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 354103.78 | 0.460585E+09 |
May | 0.484071E+09 | 0.486906E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1360234.90 | 0.275140E+09 |
June | 0.482240E+09 | 0.480452E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11832598.13 | 0.144016E+09 |
July | 0.448971E+09 | 0.451845E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27314765.68 | 52092775.70 |
August | 0.502994E+09 | 0.507245E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32209024.44 | 67455185.77 |
September | 0.447140E+09 | 0.462074E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4034811.79 | 0.154840E+09 |
October | 0.465148E+09 | 0.492047E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63948.72 | 0.376042E+09 |
November | 0.460569E+09 | 0.513739E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664120E+09 |
December | 0.448971E+09 | 0.515168E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785281E+09 |
Annual Sum or Average | 0.557719E+10 | 0.587676E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77169487.44 | 0.539680E+10 |
Minimum of Months | 0.421807E+09 | 0.451845E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52092775.70 |
Maximum of Months | 0.502994E+09 | 0.527538E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32209024.44 | 0.917579E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.821901E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141546E+10 |
February | 0.901968E+09 | 0.715651E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128872E+10 |
March | 0.107774E+10 | 0.824289E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104668E+10 |
April | 0.956342E+09 | 0.721884E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 529374.82 | 0.701502E+09 |
May | 0.103597E+10 | 0.768908E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2086708.69 | 0.414031E+09 |
June | 0.103308E+10 | 0.758803E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17046186.93 | 0.216654E+09 |
July | 0.959235E+09 | 0.713664E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39943557.84 | 80034153.56 |
August | 0.107774E+10 | 0.800772E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47403955.72 | 0.103710E+09 |
September | 0.956342E+09 | 0.728535E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6005504.60 | 0.242680E+09 |
October | 0.994195E+09 | 0.771842E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83489.76 | 0.602115E+09 |
November | 0.984487E+09 | 0.803500E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103865E+10 |
December | 0.959235E+09 | 0.800499E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123283E+10 |
Annual Sum or Average | 0.119305E+11 | 0.923025E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113099E+09 | 0.838306E+10 |
Minimum of Months | 0.901968E+09 | 0.713664E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80034153.56 |
Maximum of Months | 0.107774E+10 | 0.824289E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47403955.72 | 0.141546E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.522821E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921524E+09 |
February | 0.570983E+09 | 0.454483E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826458E+09 |
March | 0.682256E+09 | 0.521806E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683712E+09 |
April | 0.605404E+09 | 0.456667E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 364579.80 | 0.461797E+09 |
May | 0.655811E+09 | 0.485245E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1980358.65 | 0.278650E+09 |
June | 0.653980E+09 | 0.478718E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11791510.75 | 0.150463E+09 |
July | 0.607235E+09 | 0.450525E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27793750.23 | 57722478.12 |
August | 0.682256E+09 | 0.505830E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32473482.50 | 70685135.15 |
September | 0.605404E+09 | 0.461414E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4140213.42 | 0.155941E+09 |
October | 0.629366E+09 | 0.489375E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64030.25 | 0.380310E+09 |
November | 0.623221E+09 | 0.509578E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658901E+09 |
December | 0.607235E+09 | 0.511646E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787472E+09 |
Annual Sum or Average | 0.755252E+10 | 0.584811E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78607925.60 | 0.543364E+10 |
Minimum of Months | 0.570983E+09 | 0.450525E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57722478.12 |
Maximum of Months | 0.682256E+09 | 0.522821E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32473482.50 | 0.921524E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190498E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172366E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141378E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500162.50 | 0.945962E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3125648.11 | 0.556963E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18191575.45 | 0.288668E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44870121.12 | 96809577.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52710035.89 | 0.130963E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5109779.70 | 0.319350E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8341.77 | 0.801038E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143207E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168770E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124516E+09 | 0.113019E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96809577.33 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52710035.89 | 0.190498E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233330E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211292E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173578E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 657990.98 | 0.116486E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3902023.50 | 0.702624E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23224771.47 | 0.369680E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56812142.47 | 0.125042E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68112667.30 | 0.166649E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6661819.52 | 0.395037E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17619.47 | 0.977604E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171058E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202738E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159389E+09 | 0.138215E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125042E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68112667.30 | 0.233330E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235637E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213470E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174674E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143521.33 | 0.118645E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1423600.28 | 0.739754E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18782310.28 | 0.395022E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46586343.96 | 0.140364E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61996956.19 | 0.167221E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5642777.02 | 0.403017E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.971827E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165921E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198991E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134576E+09 | 0.138906E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140364E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61996956.19 | 0.235637E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 18520.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 18520.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 18520.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 18520.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 18520.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 18520.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 18520.31 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 18520.31 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 18520.31 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 18520.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 18520.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 18520.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:40 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2699.17 | 01-JAN-21:00 |
February | 1306.65 | 01-FEB-10:09 | 1089.43 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2938.64 | 06-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 934.17 | 02-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2214.47 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.18 | 07-APR-13:00 | 1649.88 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.69 | 29-MAY-12:00 | 959.52 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.49 | 19-JUN-21:03 | 603.35 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.84 | 09-JUL-13:52 | 282.71 | 11-JUL-05:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.73 | 12-AUG-19:00 | 384.09 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 860.00 | 27-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.07 | 14-SEP-14:00 | 505.83 | 23-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 991.17 | 31-OCT-15:00 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 | 25-OCT-11:00 | 1366.26 | 17-OCT-24:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2168.95 | 22-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2863.30 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.71 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 347.73 | 2938.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 739.79 | 02-JAN-16:40 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1799.46 | 01-JAN-21:00 |
February | 827.22 | 01-FEB-10:09 | 695.14 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1959.09 | 06-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 636.69 | 02-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1476.87 | 21-MAR-21:03 |
April | 827.22 | 03-APR-09:09 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.79 | 07-APR-13:00 | 1094.49 | 11-APR-04:00 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 29-MAY-11:50 | 638.77 | 03-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.19 | 19-JUN-21:03 | 397.68 | 02-JUN-22:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.66 | 09-JUL-13:52 | 191.31 | 02-JUL-18:40 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.69 | 12-AUG-19:00 | 267.35 | 20-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 456.08 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.38 | 14-SEP-14:00 | 364.28 | 10-SEP-08:10 |
October | 827.22 | 02-OCT-09:09 | 631.15 | 31-OCT-15:00 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.99 | 25-OCT-11:00 | 978.36 | 08-OCT-08:00 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 06-NOV-16:49 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1445.74 | 22-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-16:30 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1908.17 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.31 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 247.69 | 1959.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:40 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2699.20 | 01-JAN-21:00 |
February | 1306.65 | 01-FEB-10:09 | 1083.98 | 15-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2938.66 | 06-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 867.64 | 16-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2223.50 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.18 | 07-APR-13:00 | 1673.72 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.09 | 29-MAY-11:53 | 971.89 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.36 | 19-JUN-21:03 | 601.35 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.28 | 09-JUL-13:52 | 285.78 | 02-JUL-18:40 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.68 | 12-AUG-19:00 | 386.74 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 838.10 | 27-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.95 | 14-SEP-14:00 | 530.26 | 30-SEP-24:00 |
October | 1306.65 | 02-OCT-09:09 | 966.12 | 31-OCT-15:00 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 | 25-OCT-11:00 | 1420.36 | 17-OCT-24:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2175.11 | 22-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2873.42 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.78 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 352.68 | 2938.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-16:40 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1804.37 | 01-JAN-20:45 |
February | 827.17 | 01-FEB-10:09 | 682.60 | 15-FEB-16:00 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1959.09 | 06-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 583.92 | 16-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1480.65 | 21-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 515.57 | 14-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.79 | 07-APR-13:00 | 1111.80 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.67 | 29-MAY-11:50 | 652.56 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.57 | 19-JUN-21:03 | 455.70 | 03-JUN-17:40 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.26 | 09-JUL-13:52 | 271.47 | 02-JUL-18:00 |
August | 827.17 | 01-AUG-09:09 | 502.50 | 16-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.15 | 12-AUG-19:00 | 261.51 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 566.00 | 27-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.38 | 14-SEP-14:00 | 361.93 | 10-SEP-20:00 |
October | 827.17 | 02-OCT-09:09 | 614.85 | 06-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.99 | 25-OCT-11:00 | 922.22 | 17-OCT-24:00 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 06-NOV-16:49 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1445.56 | 22-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:30 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1908.95 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.51 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 236.15 | 1959.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:40 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1538.78 | 31-JAN-00:55 |
February | 1306.65 | 01-FEB-10:09 | 1085.84 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1559.63 | 06-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 923.03 | 02-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1182.66 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.91 | 07-APR-17:00 | 951.36 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.16 | 29-MAY-12:00 | 533.16 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.02 | 19-JUN-21:03 | 327.82 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.18 | 09-JUL-13:52 | 140.83 | 11-JUL-04:45 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.07 | 04-AUG-21:03 | 221.69 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 846.32 | 27-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.56 | 14-SEP-14:00 | 301.19 | 23-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 983.39 | 31-OCT-15:00 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.24 | 25-OCT-11:00 | 855.58 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1289.61 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1576.41 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.83 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 187.07 | 1576.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 739.79 | 02-JAN-16:40 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1033.74 | 31-JAN-00:55 |
February | 827.22 | 01-FEB-10:09 | 693.60 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1048.85 | 05-FEB-08:40 |
March | 827.22 | 01-MAR-10:09 | 633.14 | 02-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 799.97 | 12-MAR-10:00 |
April | 827.22 | 03-APR-09:09 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 07-APR-13:00 | 649.14 | 11-APR-04:00 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.54 | 29-MAY-11:50 | 373.95 | 03-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.72 | 19-JUN-21:03 | 226.56 | 02-JUN-22:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.22 | 09-JUL-13:52 | 108.18 | 02-JUL-18:55 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.48 | 04-AUG-21:03 | 159.11 | 20-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 456.08 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.04 | 14-SEP-14:00 | 202.08 | 30-SEP-24:00 |
October | 827.22 | 02-OCT-09:09 | 627.46 | 31-OCT-15:00 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 25-OCT-11:00 | 628.86 | 08-OCT-08:00 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 06-NOV-16:49 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 871.62 | 23-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-16:30 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1058.63 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.18 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 123.48 | 1058.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:40 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 39864.75 | 02-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1080.21 | 15-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 43066.77 | 06-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 853.92 | 16-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 33194.99 | 23-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2610.61 | 07-APR-17:00 | 23308.07 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5824.24 | 30-MAY-11:05 | 15968.88 | 01-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13907.53 | 19-JUN-11:02 | 9940.51 | 02-JUN-06:02 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10772.89 | 07-JUL-11:02 | 3502.21 | 11-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11108.06 | 24-AUG-16:03 | 6707.18 | 25-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 823.25 | 27-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6371.66 | 14-SEP-16:05 | 13720.62 | 11-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 956.86 | 31-OCT-15:00 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1012.22 | 25-OCT-11:10 | 20230.43 | 31-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 32632.24 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 33512.37 | 22-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3502.21 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 13907.53 | 43066.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-16:40 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1035.81 | 31-JAN-00:55 |
February | 827.17 | 01-FEB-10:09 | 680.54 | 15-FEB-16:00 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1039.74 | 06-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 578.64 | 16-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 792.76 | 21-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 508.12 | 14-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 07-APR-13:00 | 669.68 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.58 | 29-MAY-12:00 | 377.02 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.66 | 19-JUN-21:03 | 239.19 | 02-JUN-22:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.06 | 09-JUL-13:52 | 131.96 | 02-JUL-18:55 |
August | 827.17 | 01-AUG-09:09 | 456.05 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.96 | 04-AUG-21:03 | 159.14 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 560.14 | 27-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.04 | 14-SEP-14:00 | 210.62 | 30-SEP-24:00 |
October | 827.17 | 02-OCT-09:09 | 610.64 | 06-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 25-OCT-11:00 | 584.95 | 08-OCT-08:00 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 06-NOV-16:49 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 863.23 | 23-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:30 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1062.16 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.96 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 122.96 | 1062.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:40 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2329.51 | 31-JAN-00:55 |
February | 1306.65 | 01-FEB-10:09 | 1089.43 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2444.01 | 06-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 934.16 | 02-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1853.47 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.25 | 07-APR-13:00 | 1495.19 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.92 | 29-MAY-12:10 | 873.62 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.98 | 19-JUN-21:03 | 525.24 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.94 | 09-JUL-13:52 | 246.03 | 11-JUL-04:55 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.19 | 04-AUG-21:03 | 347.43 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 859.98 | 27-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.96 | 14-SEP-14:00 | 454.33 | 23-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 991.16 | 31-OCT-15:00 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.09 | 25-OCT-11:00 | 1247.31 | 17-OCT-24:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1905.07 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2427.13 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.03 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 291.19 | 2444.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 739.79 | 02-JAN-16:40 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1550.47 | 31-JAN-00:55 |
February | 805.43 | 01-FEB-08:09 | 695.13 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1629.33 | 06-FEB-01:00 |
March | 805.43 | 01-MAR-08:09 | 636.69 | 02-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1266.15 | 12-MAR-10:00 |
April | 805.43 | 03-APR-07:10 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 07-APR-13:00 | 991.81 | 11-APR-04:00 |
May | 805.43 | 01-MAY-07:10 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.93 | 29-MAY-12:10 | 581.08 | 03-MAY-04:00 |
June | 805.43 | 01-JUN-07:10 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.93 | 19-JUN-21:03 | 346.42 | 02-JUN-22:00 |
July | 805.43 | 03-JUL-07:10 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.86 | 09-JUL-14:05 | 164.88 | 11-JUL-04:55 |
August | 805.43 | 01-AUG-07:10 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.53 | 04-AUG-21:03 | 241.19 | 20-AUG-06:00 |
September | 805.43 | 01-SEP-07:10 | 456.08 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.64 | 14-SEP-14:00 | 304.57 | 10-SEP-07:50 |
October | 805.43 | 02-OCT-07:10 | 631.14 | 31-OCT-15:00 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 | 25-OCT-11:00 | 924.98 | 08-OCT-08:00 |
November | 805.43 | 01-NOV-07:10 | 739.79 | 06-NOV-16:49 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1268.44 | 23-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 739.79 | 01-DEC-16:30 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1618.08 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.88 | |||||
Maximum of Months | 805.43 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 193.53 | 1629.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:40 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2406.84 | 31-JAN-00:55 |
February | 1306.65 | 01-FEB-10:09 | 1083.98 | 15-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2444.01 | 06-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 867.62 | 16-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1909.94 | 12-MAR-10:00 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.18 | 07-APR-13:00 | 1514.71 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.34 | 29-MAY-12:07 | 884.08 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.84 | 19-JUN-21:03 | 524.88 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.25 | 09-JUL-13:50 | 242.69 | 11-JUL-04:55 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.31 | 04-AUG-21:03 | 349.77 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 838.08 | 27-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.85 | 14-SEP-14:00 | 474.49 | 30-SEP-24:00 |
October | 1306.65 | 02-OCT-09:09 | 966.11 | 31-OCT-15:00 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.05 | 25-OCT-11:00 | 1335.03 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1951.82 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2427.14 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.69 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 290.31 | 2444.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-16:40 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1553.99 | 31-JAN-00:55 |
February | 827.17 | 01-FEB-10:09 | 682.60 | 15-FEB-16:00 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1629.33 | 06-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 583.91 | 16-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1240.11 | 21-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 515.55 | 14-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 | 07-APR-13:00 | 1006.71 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.85 | 29-MAY-12:10 | 593.02 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.91 | 19-JUN-21:03 | 374.27 | 03-JUN-17:40 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.86 | 09-JUL-14:05 | 209.71 | 02-JUL-17:50 |
August | 827.17 | 01-AUG-09:09 | 502.48 | 16-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.62 | 04-AUG-21:03 | 236.31 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 565.98 | 27-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.64 | 14-SEP-14:00 | 311.50 | 30-SEP-24:00 |
October | 827.17 | 02-OCT-09:09 | 614.84 | 06-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.40 | 25-OCT-11:00 | 840.33 | 17-OCT-24:00 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 06-NOV-16:49 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1266.89 | 23-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:30 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1618.08 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.71 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 192.62 | 1629.33 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3399.84 | 31-JAN-00:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3355.27 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2506.46 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.02 | 07-APR-13:00 | 2150.44 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.91 | 29-MAY-12:00 | 1241.98 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.02 | 19-JUN-21:03 | 713.15 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.55 | 09-JUL-13:58 | 323.63 | 11-JUL-04:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.08 | 12-AUG-18:53 | 475.29 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.86 | 14-SEP-14:00 | 636.38 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 | 25-OCT-11:00 | 1836.63 | 08-OCT-07:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2827.20 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3465.61 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.63 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.08 | 3465.61 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4174.29 | 31-JAN-00:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4073.29 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3135.25 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.78 | 07-APR-13:00 | 2704.80 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.77 | 29-MAY-11:53 | 1550.79 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.88 | 19-JUN-21:03 | 911.80 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.78 | 09-JUL-13:52 | 414.80 | 11-JUL-05:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.63 | 12-AUG-18:53 | 600.76 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.91 | 14-SEP-14:00 | 792.77 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.52 | 25-OCT-11:00 | 2245.80 | 17-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3443.42 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4164.18 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.80 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.63 | 4174.29 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4057.36 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4079.92 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3289.51 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.66 | 08-APR-10:00 | 2491.56 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.66 | 30-MAY-13:00 | 1444.32 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.85 | 19-JUN-21:03 | 865.70 | 03-JUN-18:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.59 | 07-JUL-22:00 | 505.81 | 02-JUL-18:03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.57 | 04-AUG-21:03 | 532.82 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.15 | 14-SEP-14:00 | 757.50 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2066.59 | 17-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3156.90 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4097.81 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.81 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.57 | 4097.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12140.49 | 27-JAN-08:40 | 12070.02 | 11086.35 | 37040.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12836.03 | 03-FEB-08:30 | 12070.02 | 11086.35 | 37040.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18488.64 | 28-MAR-07:06 | 30175.04 | 27715.86 | 92601.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40365.58 | 11-APR-05:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43540.22 | 30-MAY-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 43994.62 | 26-JUN-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 45065.77 | 24-JUL-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 45866.04 | 07-AUG-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43591.49 | 06-SEP-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41275.01 | 11-OCT-05:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 30267.99 | 03-NOV-05:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15179.53 | 21-DEC-08:16 | 30175.04 | 27715.86 | 92601.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12140.49 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45866.04 | 30175.04 | 27715.86 | 92601.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 445.01 | 17-JAN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.06 |
February | 761.37 | 17-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.06 |
March | 2746.41 | 03-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.46 |
April | 7380.10 | 07-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.35 | 0.00 |
May | 11114.72 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.20 | 0.00 |
June | 12571.92 | 19-JUN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.82 | 0.00 |
July | 11684.96 | 07-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.14 | 0.00 |
August | 11171.20 | 01-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.65 | 0.00 |
September | 9933.27 | 01-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.01 | 0.00 |
October | 6999.08 | 04-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.60 |
November | 2436.45 | 04-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.14 |
December | 401.41 | 20-DEC-13:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 401.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12571.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.82 | 317.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1647.57 | 05-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1944.36 |
February | 1499.16 | 09-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2321.32 |
March | 2568.12 | 29-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.51 |
April | 2263.01 | 14-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.02 |
May | 4937.03 | 30-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.13 | 0.00 |
June | 5199.08 | 19-JUN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.47 | 0.00 |
July | 5592.72 | 10-JUL-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.73 | 0.00 |
August | 5666.76 | 14-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.82 | 0.00 |
September | 5203.09 | 05-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 0.00 |
October | 3185.69 | 04-OCT-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.95 |
November | 906.20 | 04-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.63 |
December | 927.47 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 664.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 906.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5666.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.73 | 2321.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1879.95 | 11-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.88 |
February | 2482.51 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.21 |
March | 2931.05 | 29-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.52 |
April | 2761.14 | 14-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.66 |
May | 5337.09 | 30-MAY-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.08 | 0.00 |
June | 7072.63 | 19-JUN-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.65 | 0.00 |
July | 6071.44 | 10-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.80 | 0.00 |
August | 5704.07 | 14-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.24 | 0.00 |
September | 5356.65 | 05-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.68 | 0.00 |
October | 3889.18 | 04-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 |
November | 1806.91 | 15-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.18 |
December | 2212.61 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1806.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7072.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.65 | 534.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6954.03 | 20-JAN-17:00 | 12070.02 | 11086.35 | 14286.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6970.10 | 24-FEB-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9236.96 | 29-MAR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15193.20 | 10-APR-05:03 | 1905.79 | 1847.62 | 9524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32378.92 | 30-MAY-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32633.62 | 26-JUN-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32842.85 | 24-JUL-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34248.44 | 07-AUG-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33027.56 | 05-SEP-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25550.21 | 06-OCT-05:03 | 1905.79 | 1847.62 | 9524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11456.47 | 03-NOV-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7121.03 | 21-DEC-16:20 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6954.03 | 0.00 | 1847.62 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34248.44 | 12070.02 | 11086.35 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6832.24 | 20-JAN-16:40 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6905.12 | 24-FEB-16:50 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8821.41 | 29-MAR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15280.37 | 10-APR-15:50 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26672.11 | 30-MAY-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34778.49 | 26-JUN-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35613.77 | 24-JUL-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35828.11 | 07-AUG-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35001.20 | 05-SEP-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16285.56 | 04-OCT-15:50 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10056.19 | 03-NOV-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6811.92 | 21-DEC-16:10 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6811.92 | 0.00 | 2463.50 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35828.11 | 6035.01 | 5543.17 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1120.43 | 20-JAN-15:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.65 |
February | 1159.21 | 17-FEB-14:50 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.26 |
March | 1642.64 | 27-MAR-16:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.91 |
April | 4103.02 | 07-APR-15:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 23.56 | 0.00 |
May | 7306.85 | 29-MAY-14:23 | 267.84 | 160.10 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.98 |
June | 8970.69 | 26-JUN-06:03 | 803.52 | 720.40 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.27 |
July | 10036.59 | 31-JUL-04:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.42 |
August | 10651.03 | 13-AUG-15:52 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 117.59 | 0.00 |
September | 6265.51 | 01-SEP-14:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 77.78 | 0.00 |
October | 4264.73 | 04-OCT-14:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 | 0.00 |
November | 1650.02 | 03-NOV-14:50 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.94 |
December | 1154.20 | 20-DEC-14:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1120.43 | 0.00 | 160.10 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10651.03 | 1306.65 | 720.41 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 117.59 | 165.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1195.50 | 19-JAN-10:20 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.37 |
February | 1230.14 | 22-FEB-10:10 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.10 |
March | 2985.40 | 29-MAR-09:40 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.80 |
April | 5826.25 | 28-APR-09:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.61 |
May | 13015.53 | 29-MAY-09:02 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.20 |
June | 12644.47 | 04-JUN-09:43 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.54 |
July | 13132.31 | 02-JUL-08:42 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.05 |
August | 12146.64 | 27-AUG-10:02 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.81 |
September | 12977.49 | 04-SEP-09:12 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.64 |
October | 5263.50 | 25-OCT-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 |
November | 1679.29 | 03-NOV-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.43 |
December | 1241.36 | 20-DEC-09:50 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1195.50 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 | |
Maximum of Months | 13132.31 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5317.95 | 19-JAN-13:30 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.56 |
February | 5762.01 | 02-FEB-14:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.13 |
March | 8353.84 | 03-MAR-13:25 | 2544.47 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.68 |
April | 9716.69 | 07-APR-12:30 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 29.51 | 0.00 |
May | 16254.71 | 29-MAY-13:43 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.54 |
June | 14076.46 | 25-JUN-13:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 |
July | 16337.02 | 04-JUL-12:53 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 34.15 | 0.00 |
August | 16604.51 | 13-AUG-12:32 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 140.74 | 0.00 |
September | 16876.02 | 04-SEP-13:12 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.55 |
October | 16617.80 | 22-OCT-12:43 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.40 |
November | 10086.66 | 02-NOV-13:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.03 |
December | 5349.03 | 21-DEC-13:30 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5317.95 | 267.84 | 160.10 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16876.02 | 2544.47 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 140.74 | 307.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1505.54 | 19-JAN-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.10 |
February | 1654.53 | 22-FEB-16:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.50 |
March | 4850.77 | 29-MAR-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.31 |
April | 7649.48 | 07-APR-15:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 | 0.00 |
May | 11662.35 | 29-MAY-14:23 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.27 |
June | 14282.93 | 18-JUN-16:02 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.18 |
July | 14269.77 | 02-JUL-16:02 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.98 |
August | 14261.59 | 13-AUG-15:52 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 62.03 | 0.00 |
September | 13203.74 | 10-SEP-15:32 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.29 |
October | 7209.84 | 04-OCT-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 |
November | 3354.54 | 03-NOV-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.71 |
December | 1458.33 | 08-DEC-15:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1458.33 | 169.55 | 101.35 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14282.93 | 805.38 | 456.05 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 62.03 | 219.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1130.63 | 20-JAN-15:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.95 |
February | 1136.20 | 24-FEB-14:10 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.98 |
March | 1453.42 | 28-MAR-14:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.19 |
April | 2178.47 | 10-APR-14:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.90 |
May | 4481.49 | 30-MAY-14:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 29.90 | 0.00 |
June | 6096.28 | 26-JUN-06:03 | 803.52 | 720.40 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.56 |
July | 7543.53 | 10-JUL-04:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 6.61 | 0.00 |
August | 6987.11 | 14-AUG-06:03 | 803.52 | 720.40 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 |
September | 5131.96 | 01-SEP-14:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 41.67 | 0.00 |
October | 3818.07 | 05-OCT-14:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 |
November | 1659.43 | 03-NOV-14:10 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.48 |
December | 1225.76 | 20-DEC-14:10 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1130.63 | 0.00 | 649.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7543.53 | 1306.65 | 720.41 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 41.67 | 148.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1016.77 | 27-JAN-10:20 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.88 |
February | 1014.48 | 22-FEB-10:10 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.16 |
March | 1929.67 | 29-MAR-09:40 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.51 |
April | 3936.81 | 28-APR-09:20 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.84 |
May | 8562.40 | 29-MAY-09:02 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.98 |
June | 8225.17 | 05-JUN-06:02 | 847.82 | 760.12 | 2118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.97 |
July | 9443.91 | 09-JUL-09:32 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 28.64 | 0.00 |
August | 8792.71 | 20-AUG-10:02 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.46 |
September | 11084.80 | 04-SEP-10:12 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.05 |
October | 4818.97 | 05-OCT-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 |
November | 2167.91 | 03-NOV-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.69 |
December | 1128.10 | 20-DEC-09:50 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1014.48 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11084.80 | 1654.44 | 912.16 | 2118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 28.64 | 117.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1487.10 | 07-JAN-14:10 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.56 |
February | 1664.66 | 25-FEB-13:30 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.79 |
March | 3328.82 | 03-MAR-13:35 | 2544.47 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1817.46 |
April | 7218.76 | 07-APR-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1995.22 | 0.00 |
May | 11259.85 | 30-MAY-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 5683.34 | 0.00 |
June | 13650.30 | 19-JUN-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 11345.57 | 0.00 |
July | 12769.73 | 07-JUL-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 9182.49 | 0.00 |
August | 13127.49 | 13-AUG-13:12 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 79.30 | 0.00 |
September | 13858.69 | 04-SEP-14:52 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.01 |
October | 13441.63 | 22-OCT-12:43 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.16 |
November | 6964.96 | 02-NOV-12:20 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1710.39 |
December | 2696.36 | 02-DEC-14:00 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1487.10 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13858.69 | 2544.47 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 11345.57 | 1817.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1197.93 | 20-JAN-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 |
February | 1248.33 | 22-FEB-16:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.16 |
March | 3009.23 | 27-MAR-16:50 | 254.33 | 253.36 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 |
April | 5272.01 | 10-APR-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.54 |
May | 6596.97 | 30-MAY-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 | 0.00 |
June | 10915.25 | 04-JUN-16:12 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.89 |
July | 8968.03 | 02-JUL-16:02 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.43 |
August | 11022.52 | 13-AUG-15:52 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 39.52 | 0.00 |
September | 11318.04 | 04-SEP-16:52 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.75 |
October | 6261.91 | 04-OCT-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 |
November | 3202.90 | 03-NOV-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.45 |
December | 1203.29 | 08-DEC-15:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1197.93 | 211.94 | 126.69 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11318.04 | 805.38 | 456.05 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 39.52 | 89.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1168.36 | 20-JAN-15:10 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.84 |
February | 1190.43 | 24-FEB-15:10 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.29 |
March | 1592.18 | 27-MAR-16:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 |
April | 3597.28 | 07-APR-15:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 | 0.00 |
May | 7492.02 | 30-MAY-06:03 | 803.52 | 720.40 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.97 |
June | 8559.07 | 26-JUN-06:03 | 803.52 | 720.40 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.53 |
July | 10123.09 | 09-JUL-15:22 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 | 0.00 |
August | 8651.43 | 14-AUG-04:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.99 |
September | 5636.78 | 01-SEP-14:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 65.00 | 0.00 |
October | 4092.68 | 05-OCT-14:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 |
November | 1786.75 | 03-NOV-14:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.49 |
December | 1215.45 | 20-DEC-14:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1168.36 | 0.00 | 240.15 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10123.09 | 1306.65 | 720.41 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 65.00 | 251.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1253.21 | 19-JAN-10:00 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.34 |
February | 1312.61 | 22-FEB-09:55 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.79 |
March | 3623.11 | 29-MAR-09:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.98 |
April | 6137.98 | 28-APR-08:40 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.25 |
May | 12707.32 | 28-MAY-08:32 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.19 |
June | 12332.91 | 04-JUN-09:32 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.97 |
July | 13820.15 | 02-JUL-08:31 | 296.74 | 177.38 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.75 |
August | 11817.31 | 27-AUG-09:53 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 |
September | 13465.49 | 04-SEP-08:22 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.00 |
October | 5557.02 | 05-OCT-09:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.54 |
November | 2353.00 | 03-NOV-09:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.05 |
December | 1348.03 | 20-DEC-09:40 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1253.21 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | |
Maximum of Months | 13820.15 | 1610.86 | 912.16 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5556.29 | 19-JAN-13:30 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.57 |
February | 6114.39 | 02-FEB-13:50 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.87 |
March | 8090.44 | 03-MAR-13:25 | 2544.47 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.74 |
April | 9020.46 | 07-APR-12:40 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 26.96 | 0.00 |
May | 11029.94 | 28-MAY-13:53 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.02 |
June | 11327.58 | 25-JUN-13:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.56 |
July | 14491.31 | 04-JUL-12:53 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 38.12 | 0.00 |
August | 14925.43 | 20-AUG-12:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 | 0.00 |
September | 16090.63 | 04-SEP-11:42 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.78 |
October | 14919.15 | 15-OCT-13:13 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.26 |
November | 10349.52 | 02-NOV-12:50 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.67 |
December | 6297.39 | 21-DEC-13:30 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5556.29 | 267.84 | 160.10 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16090.63 | 2544.47 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 38.12 | 458.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1456.39 | 20-JAN-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.86 |
February | 1973.04 | 24-FEB-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.01 |
March | 4873.79 | 29-MAR-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.38 |
April | 7263.33 | 10-APR-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.85 |
May | 9227.57 | 28-MAY-15:53 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.93 |
June | 13784.02 | 18-JUN-17:12 | 0.00 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.44 |
July | 14202.59 | 02-JUL-16:31 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.04 |
August | 12929.00 | 13-AUG-15:52 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 54.82 | 0.00 |
September | 13210.14 | 04-SEP-14:22 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.59 |
October | 6947.33 | 04-OCT-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 |
November | 3539.13 | 03-NOV-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.12 |
December | 1419.31 | 08-DEC-15:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1419.31 | 0.00 | 101.35 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14202.59 | 805.38 | 456.05 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 54.82 | 198.01 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.156735E+12 | 255212.18 | 02-JAN-07:10 | 0.477338E+11 | 97655.84 | 02-JAN-08:30 |
February | 0.133264E+12 | 212177.04 | 06-FEB-07:10 | 0.467236E+11 | 101591.00 | 06-FEB-07:30 |
March | 0.120837E+12 | 146261.67 | 13-MAR-06:10 | 0.279073E+11 | 61351.17 | 23-MAR-06:30 |
April | 0.105100E+12 | 112252.59 | 07-APR-15:39 | 0.122000E+11 | 37582.15 | 03-APR-06:19 |
May | 0.116928E+12 | 156711.84 | 30-MAY-13:00 | 0.915076E+10 | 9311.53 | 01-MAY-06:49 |
June | 0.148403E+12 | 173028.93 | 19-JUN-12:09 | 0.860093E+10 | 9074.37 | 02-JUN-11:09 |
July | 0.167620E+12 | 163099.60 | 07-JUL-14:30 | 0.820903E+10 | 8955.12 | 03-JUL-11:50 |
August | 0.177025E+12 | 167283.13 | 16-AUG-15:09 | 0.859978E+10 | 8919.40 | 31-AUG-11:20 |
September | 0.131779E+12 | 145520.69 | 07-SEP-15:20 | 0.813798E+10 | 8992.50 | 29-SEP-11:39 |
October | 0.116699E+12 | 122500.23 | 04-OCT-15:39 | 0.914066E+10 | 27500.68 | 28-OCT-06:19 |
November | 0.114700E+12 | 156128.90 | 24-NOV-07:10 | 0.199898E+11 | 64711.13 | 24-NOV-07:30 |
December | 0.131537E+12 | 159524.07 | 11-DEC-07:10 | 0.359948E+11 | 63702.44 | 22-DEC-07:10 |
Annual Sum or Average | 0.162063E+13 | 0.242388E+12 | ||||
Minimum of Months | 0.105100E+12 | 112252.59 | 0.813798E+10 | 8919.40 | ||
Maximum of Months | 0.177025E+12 | 255212.18 | 0.477338E+11 | 101591.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.240173E+11 | 0.771421E+10 | 0.641572E+11 | 0.109142E+10 | 0.453167E+10 | 1312252.65 | 0.552221E+11 | 51908.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.214734E+11 | 0.638436E+10 | 0.580684E+11 | 0.987415E+09 | 0.396395E+10 | 1186778.30 | 0.423849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252224E+11 | 0.626705E+10 | 0.666107E+11 | 0.114320E+10 | 0.448699E+10 | 1343621.24 | 0.167528E+11 | 0.352089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223682E+11 | 0.526247E+10 | 0.619407E+11 | 0.105056E+10 | 0.510657E+10 | 1267813.82 | 0.609147E+10 | 0.327828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.240313E+11 | 0.480315E+10 | 0.653840E+11 | 0.111686E+10 | 0.802336E+10 | 1327936.95 | 0.904546E+09 | 0.126632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.238498E+11 | 0.432726E+10 | 0.641577E+11 | 0.109955E+10 | 0.132072E+11 | 1296568.36 | 28556917.50 | 0.417317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.223592E+11 | 0.458780E+10 | 0.631525E+11 | 0.106758E+10 | 0.164916E+11 | 1299182.41 | 0.00 | 0.599598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.249658E+11 | 0.511923E+10 | 0.666107E+11 | 0.114306E+10 | 0.182777E+11 | 1343621.24 | 0.00 | 0.609070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.224417E+11 | 0.571262E+10 | 0.619118E+11 | 0.105019E+10 | 0.107217E+11 | 1267813.82 | 0.108768E+09 | 0.298314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.234826E+11 | 0.673721E+10 | 0.641717E+11 | 0.109106E+10 | 0.775946E+10 | 1312252.65 | 0.991902E+09 | 0.124640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.236204E+11 | 0.725314E+10 | 0.627379E+11 | 0.107135E+10 | 0.426765E+10 | 1278270.02 | 0.154308E+11 | 0.317544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.233235E+11 | 0.789094E+10 | 0.631380E+11 | 0.106822E+10 | 0.401439E+10 | 1299182.41 | 0.321007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281156E+12 | 0.720594E+11 | 0.762041E+12 | 0.129805E+11 | 0.100852E+12 | 15535293.87 | 0.170016E+12 | 0.221505E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.214734E+11 | 0.432726E+10 | 0.580684E+11 | 0.987415E+09 | 0.396395E+10 | 1186778.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.252224E+11 | 0.789094E+10 | 0.666107E+11 | 0.114320E+10 | 0.182777E+11 | 1343621.24 | 0.552221E+11 | 0.609070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.379943E+11 | 0.00 | 0.973948E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.378602E+11 | 0.00 | 0.886345E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.178472E+11 | 0.00 | 0.100600E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.317009E+10 | 0.00 | 0.902989E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 11588287.24 | 0.00 | 0.913917E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.860093E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.820903E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.859978E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.813798E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.432298E+09 | 0.00 | 0.870836E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.111034E+11 | 0.00 | 0.888638E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.266740E+11 | 0.00 | 0.932082E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.135093E+12 | 0.00 | 0.107295E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.813798E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.379943E+11 | 0.00 | 0.100600E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28079.40 | 02-JAN-16:40 | 5557.43 | 01-JAN-06:10 | 47562.27 | 02-JAN-08:09 | 926.74 | 02-JAN-16:49 | 7241.18 | 02-JAN-06:19 | 0.73 | 02-JAN-06:10 | 211546.62 | 02-JAN-06:19 |
February | 27257.45 | 15-FEB-16:00 | 5557.43 | 01-FEB-06:10 | 47562.27 | 01-FEB-08:09 | 925.21 | 15-FEB-16:00 | 5727.66 | 06-FEB-06:10 | 0.73 | 01-FEB-07:10 | 175721.51 | 06-FEB-07:10 |
March | 25234.19 | 02-MAR-16:00 | 5557.43 | 01-MAR-06:10 | 47562.27 | 01-MAR-08:09 | 924.01 | 16-MAR-07:19 | 5227.38 | 29-MAR-15:30 | 0.73 | 01-MAR-08:09 | 108969.23 | 20-MAR-06:10 |
April | 23859.46 | 14-APR-07:10 | 5557.43 | 01-APR-05:10 | 47562.27 | 03-APR-07:10 | 922.14 | 14-APR-07:19 | 13350.24 | 10-APR-15:09 | 0.73 | 03-APR-06:10 | 77948.54 | 03-APR-06:10 |
May | 23688.37 | 01-MAY-07:10 | 5557.43 | 01-MAY-18:49 | 47562.27 | 01-MAY-07:10 | 921.90 | 01-MAY-07:19 | 26703.95 | 30-MAY-14:39 | 0.73 | 01-MAY-05:10 | 23679.52 | 01-MAY-06:10 |
June | 23688.37 | 01-JUN-07:10 | 5557.43 | 01-JUN-19:19 | 47562.27 | 01-JUN-07:10 | 921.90 | 01-JUN-07:19 | 26621.53 | 19-JUN-15:50 | 0.73 | 01-JUN-05:30 | 5566.25 | 02-JUN-06:19 |
July | 23688.37 | 03-JUL-07:10 | 5557.43 | 01-JUL-19:30 | 47562.27 | 03-JUL-07:10 | 921.90 | 03-JUL-07:19 | 26668.01 | 17-JUL-15:09 | 0.73 | 01-JUL-05:30 | 0.00 | 01-JUL-00:10 |
August | 23781.25 | 16-AUG-07:10 | 5557.43 | 01-AUG-19:10 | 47562.27 | 01-AUG-07:10 | 922.03 | 16-AUG-07:19 | 26511.75 | 14-AUG-15:09 | 0.73 | 01-AUG-05:30 | 0.00 | 01-AUG-00:10 |
September | 24755.60 | 27-SEP-07:10 | 5557.43 | 01-SEP-05:10 | 47562.27 | 01-SEP-07:10 | 923.43 | 27-SEP-07:19 | 22410.70 | 05-SEP-15:20 | 0.73 | 01-SEP-05:10 | 6727.88 | 19-SEP-06:19 |
October | 26176.33 | 31-OCT-15:00 | 5557.43 | 01-OCT-05:10 | 47562.27 | 02-OCT-07:10 | 925.12 | 06-OCT-07:19 | 16828.24 | 04-OCT-15:50 | 0.73 | 27-OCT-16:10 | 26830.70 | 31-OCT-06:10 |
November | 28079.40 | 06-NOV-16:49 | 5557.43 | 01-NOV-05:10 | 47562.27 | 01-NOV-07:10 | 926.74 | 06-NOV-16:00 | 6760.13 | 03-NOV-15:09 | 0.73 | 15-NOV-08:09 | 121696.98 | 24-NOV-07:10 |
December | 28079.40 | 01-DEC-16:30 | 5557.43 | 01-DEC-06:10 | 47562.27 | 01-DEC-08:09 | 926.74 | 01-DEC-16:40 | 3909.78 | 11-DEC-06:10 | 0.73 | 01-DEC-08:09 | 118614.74 | 11-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 23688.37 | 5557.43 | 47562.27 | 921.90 | 3909.78 | 0.73 | 0.00 | |||||||
Maximum of Months | 28079.40 | 5557.43 | 47562.27 | 926.74 | 26703.95 | 0.73 | 211546.62 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 86.51 | 15-JAN-10:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16822.73 | 27-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32209.77 | 07-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 65103.58 | 30-MAY-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 83063.31 | 19-JUN-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 72469.90 | 07-JUL-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 76920.06 | 16-AUG-12:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 59960.64 | 07-SEP-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41687.26 | 04-OCT-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7365.07 | 03-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83063.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 255212.18 | 02-JAN-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 7200.15 | 0.73 | 210984.87 | 0.00 | 0.00 |
February | 212177.04 | 06-FEB-07:10 | 8742.04 | 21853.28 | 0.00 | 256.05 | 5603.43 | 0.73 | 175721.51 | 0.00 | 0.00 |
March | 146261.67 | 13-MAR-06:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 3730.17 | 0.73 | 105504.34 | 0.00 | 0.00 |
April | 112252.59 | 07-APR-15:39 | 23688.37 | 43769.98 | 0.00 | 920.43 | 12124.84 | 0.73 | 0.00 | 31748.25 | 0.00 |
May | 156711.84 | 30-MAY-13:00 | 23688.37 | 42286.04 | 0.00 | 919.86 | 24713.27 | 0.73 | 0.00 | 65103.58 | 0.00 |
June | 173028.93 | 19-JUN-12:09 | 23688.37 | 44099.74 | 0.00 | 920.56 | 21679.76 | 0.73 | 0.00 | 82639.77 | 0.00 |
July | 163099.60 | 07-JUL-14:30 | 23688.37 | 42286.04 | 0.00 | 919.86 | 24411.54 | 0.73 | 0.00 | 71793.07 | 0.00 |
August | 167283.13 | 16-AUG-15:09 | 23688.37 | 43769.98 | 0.00 | 920.43 | 24191.39 | 0.73 | 0.00 | 74712.24 | 0.00 |
September | 145520.69 | 07-SEP-15:20 | 23688.37 | 43769.98 | 0.00 | 920.43 | 21374.31 | 0.73 | 0.00 | 55766.87 | 0.00 |
October | 122500.23 | 04-OCT-15:39 | 23688.37 | 43769.98 | 0.00 | 920.43 | 16643.90 | 0.73 | 0.00 | 37476.82 | 0.00 |
November | 156128.90 | 24-NOV-07:10 | 8375.44 | 21853.28 | 0.00 | 255.95 | 3946.53 | 0.73 | 121696.98 | 0.00 | 0.00 |
December | 159524.07 | 11-DEC-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 3882.17 | 0.73 | 118614.74 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 112252.59 | 8375.44 | 21853.28 | 0.00 | 255.95 | 3730.17 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 255212.18 | 23688.37 | 44099.74 | 5557.43 | 920.56 | 24713.27 | 0.73 | 210984.87 | 82639.77 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 89011.53 | 02-JAN-08:30 | 0.00 | 9467.88 | 31-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 93603.49 | 06-FEB-07:40 | 0.00 | 9473.14 | 07-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 54797.36 | 23-MAR-06:10 | 0.00 | 9450.98 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 29427.30 | 03-APR-06:19 | 0.00 | 9342.04 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 5429.86 | 01-MAY-06:10 | 0.00 | 9216.53 | 02-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9074.37 | 02-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 8955.12 | 03-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 8919.40 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 8992.50 | 29-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 19683.55 | 28-OCT-06:00 | 0.00 | 9129.24 | 30-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 56617.06 | 24-NOV-07:30 | 0.00 | 9271.78 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 55859.52 | 22-DEC-07:19 | 0.00 | 9388.21 | 27-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8919.40 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 93603.49 | 0.00 | 9473.14 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.52 | 0.50 | 19.52 | 0.00 | 19.52 | 0.00 | 19.52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.19 | 0.00 | 26.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 19.52 | 0.50 | 19.52 | 1.33 | 23.33 | 0.00 | 23.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.52 | 0.50 | 19.52 | 1.17 | 26.19 | 0.00 | 26.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 18.96 | 1.83 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
February | 0.17 | 19.44 | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.16 | 0.00 | 26.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 18.99 | 2.00 | 19.22 | 0.17 | 19.47 | 0.00 | 19.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.44 | 1.83 | 19.44 | 0.17 | 26.16 | 0.00 | 26.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 18.57 | 1.50 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
February | 1.00 | 17.90 | 0.50 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.17 | 18.36 | 2.00 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 18.57 | 1.50 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.00 | 15.79 | 9.50 | 16.10 | 0.00 | 16.10 | 0.00 | 16.10 |
February | 23.17 | 16.05 | 10.33 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 |
March | 1.00 | 17.79 | 0.33 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.33 | 2.33 | 27.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.46 | 1.17 | 27.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.00 | 16.43 | 0.33 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 |
December | 5.33 | 15.61 | 1.83 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 |
Annual Sum or Average | 55.50 | 15.94 | 22.33 | 16.24 | 4.17 | 16.81 | 3.50 | 17.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.00 | 17.79 | 10.33 | 18.20 | 2.67 | 27.46 | 2.33 | 27.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.50 | 15.04 | 4.50 | 15.10 | 0.00 | 15.10 | 0.00 | 15.10 |
February | 13.50 | 15.10 | 2.50 | 15.15 | 0.00 | 15.15 | 0.00 | 15.15 |
March | 0.67 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.88 | 4.00 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.71 | 3.00 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.80 | 10.17 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.79 | 5.00 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.92 | 3.83 | 27.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.50 | 15.95 | 0.00 | 15.95 | 0.00 | 15.95 | 0.00 | 15.95 |
December | 6.00 | 15.60 | 0.83 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 |
Annual Sum or Average | 41.17 | 15.21 | 7.83 | 15.22 | 26.50 | 19.64 | 26.00 | 21.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 19.50 | 16.93 | 4.50 | 16.93 | 10.33 | 27.92 | 10.17 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.83 | 15.39 | 3.50 | 15.63 | 0.00 | 15.63 | 0.00 | 15.63 |
February | 10.33 | 15.40 | 1.67 | 15.56 | 0.00 | 15.56 | 0.00 | 15.56 |
March | 0.67 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.66 | 2.50 | 27.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.48 | 2.50 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.72 | 7.67 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.90 | 5.00 | 27.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.09 | 5.50 | 28.10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.73 | 2.17 | 27.73 |
November | 0.83 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 |
December | 3.33 | 15.74 | 0.50 | 15.63 | 0.00 | 15.63 | 0.00 | 15.63 |
Annual Sum or Average | 30.00 | 15.51 | 5.67 | 15.67 | 26.17 | 20.81 | 25.33 | 22.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.83 | 17.07 | 3.50 | 17.07 | 7.83 | 28.09 | 7.67 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.50 | 14.93 | 5.67 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
February | 14.50 | 15.03 | 3.83 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 |
March | 0.67 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.86 | 0.33 | 27.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.61 | 3.50 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.02 | 3.00 | 28.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.10 | 5.00 | 28.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.21 | 2.33 | 28.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.11 | 2.67 | 28.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.38 | 0.17 | 27.38 |
November | 1.83 | 15.79 | 0.00 | 15.79 | 0.00 | 15.79 | 0.00 | 15.79 |
December | 6.33 | 15.63 | 1.33 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
Annual Sum or Average | 42.83 | 15.14 | 10.83 | 15.10 | 24.00 | 19.09 | 17.00 | 20.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.92 | 0.00 | 14.92 |
Maximum of Months | 19.50 | 17.00 | 5.67 | 17.00 | 7.83 | 28.21 | 5.00 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.33 | 16.50 | 7.83 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 |
February | 5.17 | 18.17 | 3.00 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.50 | 16.97 | 10.83 | 17.39 | 0.00 | 17.39 | 0.00 | 17.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.33 | 18.17 | 7.83 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 15.28 | 1.50 | 15.49 | 0.00 | 15.49 | 0.00 | 15.49 |
February | 0.67 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.62 | 1.50 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.52 | 1.00 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.65 | 4.00 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.53 | 3.17 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.67 | 3.67 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7.17 | 15.43 | 1.50 | 15.60 | 13.33 | 22.88 | 13.33 | 24.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.50 | 16.88 | 1.50 | 16.88 | 4.00 | 27.67 | 4.00 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 83.17 | 16.77 | 78.33 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
February | 72.67 | 16.67 | 72.33 | 16.67 | 0.00 | 16.67 | 0.00 | 16.67 |
March | 57.00 | 17.79 | 57.00 | 17.79 | 0.00 | 17.79 | 0.00 | 17.79 |
April | 27.00 | 18.88 | 27.00 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
May | 3.17 | 19.72 | 3.17 | 19.72 | 0.83 | 20.30 | 0.83 | 20.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.70 | 2.67 | 25.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 25.65 | 10.00 | 25.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 25.55 | 21.00 | 25.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 26.15 | 11.50 | 26.14 |
October | 4.17 | 19.45 | 4.17 | 19.45 | 2.67 | 21.41 | 2.67 | 22.62 |
November | 42.83 | 18.50 | 42.83 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 |
December | 63.67 | 17.64 | 63.67 | 17.64 | 0.00 | 17.64 | 0.00 | 17.64 |
Annual Sum or Average | 353.67 | 17.50 | 348.50 | 17.52 | 49.17 | 18.06 | 48.67 | 18.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 0.00 | 16.67 |
Maximum of Months | 83.17 | 19.72 | 78.33 | 19.72 | 21.17 | 26.15 | 21.00 | 26.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.67 | 15.18 | 2.67 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 |
February | 1.00 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.61 | 2.17 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.70 | 3.50 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.77 | 1.83 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.81 | 2.17 | 27.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8.67 | 15.26 | 2.67 | 15.37 | 13.67 | 22.11 | 10.17 | 23.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.67 | 15.85 | 2.67 | 15.85 | 4.83 | 27.81 | 3.50 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.17 | 16.04 | 6.17 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 |
February | 6.67 | 16.93 | 2.67 | 17.65 | 0.00 | 17.65 | 0.00 | 17.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
Annual Sum or Average | 20.50 | 16.29 | 8.83 | 16.72 | 0.33 | 16.84 | 0.33 | 16.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.17 | 16.93 | 6.17 | 17.65 | 0.33 | 27.27 | 0.33 | 27.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.83 | 15.08 | 2.17 | 15.08 | 0.00 | 15.08 | 0.00 | 15.08 |
February | 3.67 | 15.53 | 0.17 | 15.70 | 0.00 | 15.70 | 0.00 | 15.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.81 | 4.00 | 27.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.73 | 2.33 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.85 | 6.67 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.78 | 3.83 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.93 | 3.67 | 27.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
Annual Sum or Average | 13.17 | 15.20 | 2.33 | 15.23 | 20.67 | 22.43 | 20.67 | 24.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.83 | 15.53 | 2.17 | 15.70 | 6.67 | 27.93 | 6.67 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.67 | 15.43 | 1.67 | 15.66 | 0.00 | 15.66 | 0.00 | 15.66 |
February | 3.17 | 15.91 | 0.33 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.57 | 1.67 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.36 | 0.83 | 27.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.58 | 5.83 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.82 | 4.00 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.97 | 5.67 | 27.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.72 | 2.50 | 27.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
Annual Sum or Average | 10.83 | 15.57 | 2.00 | 15.81 | 21.00 | 23.22 | 20.67 | 24.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.67 | 15.91 | 1.67 | 16.23 | 5.83 | 27.97 | 5.83 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.83 | 15.03 | 3.17 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
February | 3.67 | 15.40 | 0.17 | 15.58 | 0.00 | 15.58 | 0.00 | 15.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.80 | 0.33 | 27.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.61 | 2.33 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.90 | 2.67 | 27.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.90 | 4.50 | 27.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.98 | 2.33 | 28.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.08 | 2.50 | 28.10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.38 | 0.33 | 27.38 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
Annual Sum or Average | 14.00 | 15.13 | 3.33 | 15.14 | 20.67 | 22.07 | 15.00 | 23.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.83 | 15.40 | 3.17 | 15.58 | 7.17 | 28.08 | 4.50 | 28.10 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.56 | 56.67 | 22.31 | 56.67 | 22.10 |
February | 454.00 | 23.13 | 4.83 | 23.11 | 4.83 | 23.09 |
March | 462.67 | 23.67 | 0.00 | 23.67 | 0.00 | 23.67 |
April | 229.00 | 23.74 | 49.50 | 23.99 | 0.00 | 23.99 |
May | 31.33 | 23.98 | 233.33 | 24.52 | 0.00 | 24.52 |
June | 0.00 | 0.00 | 435.17 | 24.42 | 0.00 | 24.42 |
July | 0.00 | 0.00 | 497.00 | 24.44 | 0.00 | 24.44 |
August | 0.33 | 27.19 | 483.67 | 24.43 | 0.33 | 24.44 |
September | 1.83 | 23.99 | 393.17 | 24.49 | 0.00 | 24.49 |
October | 56.83 | 24.02 | 278.33 | 24.39 | 0.00 | 24.39 |
November | 292.83 | 23.59 | 64.00 | 23.86 | 0.00 | 23.86 |
December | 497.00 | 23.42 | 0.00 | 23.42 | 0.00 | 23.42 |
Annual Sum or Average | 2527.83 | 23.31 | 2495.67 | 23.85 | 61.83 | 23.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.31 | 0.00 | 22.10 |
Maximum of Months | 502.00 | 27.19 | 497.00 | 24.52 | 56.67 | 24.52 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.09 | 198.67 | 20.85 | 198.67 | 20.72 |
February | 454.00 | 21.46 | 151.83 | 21.30 | 151.83 | 21.20 |
March | 514.00 | 22.42 | 6.83 | 22.40 | 6.83 | 22.37 |
April | 392.50 | 23.00 | 18.17 | 23.07 | 0.50 | 23.06 |
May | 157.67 | 23.51 | 135.33 | 23.85 | 0.00 | 23.85 |
June | 6.17 | 23.77 | 411.83 | 24.28 | 0.00 | 24.28 |
July | 0.00 | 0.00 | 497.00 | 24.31 | 0.00 | 24.31 |
August | 0.00 | 0.00 | 459.50 | 24.34 | 0.00 | 24.34 |
September | 36.00 | 23.66 | 310.17 | 24.28 | 0.00 | 24.28 |
October | 197.00 | 23.58 | 185.00 | 23.88 | 0.00 | 23.88 |
November | 461.50 | 22.50 | 49.17 | 22.36 | 46.33 | 22.23 |
December | 497.00 | 21.64 | 81.00 | 21.50 | 81.00 | 21.39 |
Annual Sum or Average | 3217.83 | 22.18 | 2504.50 | 22.79 | 485.17 | 22.62 |
Minimum of Months | 0.00 | 0.00 | 6.83 | 20.85 | 0.00 | 20.72 |
Maximum of Months | 514.00 | 23.77 | 497.00 | 24.34 | 198.67 | 24.34 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.54 | 326.17 | 20.36 | 326.17 | 20.29 |
February | 454.00 | 20.81 | 313.33 | 20.66 | 313.33 | 20.60 |
March | 514.00 | 21.71 | 96.17 | 21.53 | 96.17 | 21.40 |
April | 412.50 | 22.43 | 30.67 | 22.38 | 20.67 | 22.28 |
May | 226.83 | 23.25 | 105.50 | 23.56 | 0.00 | 23.56 |
June | 15.83 | 23.55 | 387.00 | 24.24 | 0.00 | 24.24 |
July | 0.00 | 0.00 | 491.00 | 24.33 | 0.00 | 24.33 |
August | 2.00 | 23.59 | 441.00 | 24.34 | 0.00 | 24.34 |
September | 89.33 | 23.28 | 255.00 | 24.01 | 0.00 | 24.01 |
October | 299.50 | 22.97 | 126.00 | 23.27 | 4.17 | 23.25 |
November | 485.17 | 21.68 | 119.50 | 21.41 | 119.50 | 21.23 |
December | 497.00 | 20.85 | 306.33 | 20.67 | 306.33 | 20.59 |
Annual Sum or Average | 3498.17 | 21.64 | 2997.67 | 22.14 | 1186.33 | 21.86 |
Minimum of Months | 0.00 | 0.00 | 30.67 | 20.36 | 0.00 | 20.29 |
Maximum of Months | 514.00 | 23.59 | 491.00 | 24.34 | 326.17 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.90 | 447.17 | 19.84 | 447.17 | 19.82 |
February | 454.00 | 20.04 | 427.83 | 20.01 | 427.83 | 20.00 |
March | 514.00 | 20.80 | 282.67 | 20.58 | 282.67 | 20.48 |
April | 421.00 | 21.61 | 117.50 | 21.44 | 97.50 | 21.24 |
May | 264.83 | 22.84 | 117.67 | 23.27 | 6.17 | 23.26 |
June | 46.50 | 24.34 | 400.83 | 24.30 | 22.00 | 24.35 |
July | 66.83 | 25.93 | 496.50 | 24.64 | 66.83 | 24.78 |
August | 48.83 | 25.19 | 446.50 | 24.46 | 34.00 | 24.55 |
September | 155.33 | 23.06 | 247.17 | 23.78 | 10.50 | 23.80 |
October | 367.67 | 22.13 | 131.33 | 22.26 | 47.33 | 22.08 |
November | 489.00 | 20.72 | 264.33 | 20.46 | 264.33 | 20.33 |
December | 497.00 | 20.06 | 470.17 | 20.03 | 470.17 | 20.03 |
Annual Sum or Average | 3827.00 | 21.13 | 3849.67 | 21.58 | 2176.50 | 21.31 |
Minimum of Months | 46.50 | 19.90 | 117.50 | 19.84 | 6.17 | 19.82 |
Maximum of Months | 514.00 | 25.93 | 496.50 | 24.64 | 470.17 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.95 | 427.33 | 19.85 | 427.33 | 19.82 |
February | 454.00 | 20.19 | 389.33 | 20.11 | 389.33 | 20.08 |
March | 504.83 | 21.06 | 204.50 | 20.74 | 204.50 | 20.57 |
April | 369.67 | 21.71 | 147.00 | 21.88 | 76.33 | 21.67 |
May | 235.33 | 22.86 | 196.67 | 23.61 | 15.67 | 23.70 |
June | 56.17 | 24.72 | 412.83 | 24.39 | 28.83 | 24.49 |
July | 81.00 | 26.34 | 490.67 | 24.78 | 81.00 | 24.98 |
August | 54.67 | 25.91 | 471.67 | 24.56 | 46.33 | 24.71 |
September | 148.67 | 23.35 | 300.83 | 24.05 | 25.83 | 24.15 |
October | 307.50 | 22.23 | 150.50 | 22.62 | 27.17 | 22.49 |
November | 487.67 | 20.89 | 220.83 | 20.58 | 220.83 | 20.42 |
December | 497.00 | 20.16 | 432.50 | 20.09 | 432.50 | 20.07 |
Annual Sum or Average | 3698.50 | 21.27 | 3844.67 | 21.82 | 1975.67 | 21.56 |
Minimum of Months | 54.67 | 19.95 | 147.00 | 19.85 | 15.67 | 19.82 |
Maximum of Months | 504.83 | 26.34 | 490.67 | 24.78 | 432.50 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.33 | 20.42 | 338.83 | 20.10 | 338.83 | 19.96 |
February | 435.83 | 20.78 | 302.33 | 20.47 | 302.33 | 20.33 |
March | 436.50 | 21.14 | 205.17 | 20.91 | 187.33 | 20.72 |
April | 358.17 | 21.66 | 146.83 | 21.83 | 77.83 | 21.62 |
May | 255.50 | 22.79 | 165.17 | 23.41 | 12.00 | 23.46 |
June | 62.33 | 24.32 | 396.33 | 24.32 | 27.50 | 24.40 |
July | 75.33 | 26.12 | 490.50 | 24.70 | 75.00 | 24.87 |
August | 62.00 | 25.64 | 463.17 | 24.57 | 47.33 | 24.72 |
September | 132.00 | 23.67 | 321.00 | 24.19 | 30.83 | 24.32 |
October | 220.83 | 22.44 | 239.17 | 23.25 | 32.17 | 23.17 |
November | 424.17 | 21.16 | 189.50 | 20.91 | 168.83 | 20.69 |
December | 472.17 | 20.71 | 323.83 | 20.43 | 320.67 | 20.29 |
Annual Sum or Average | 3429.17 | 21.54 | 3581.83 | 22.10 | 1620.67 | 21.83 |
Minimum of Months | 62.00 | 20.42 | 146.83 | 20.10 | 12.00 | 19.96 |
Maximum of Months | 494.33 | 26.12 | 490.50 | 24.70 | 338.83 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.01 | 423.33 | 19.90 | 423.33 | 19.86 |
February | 454.00 | 20.26 | 383.33 | 20.13 | 383.33 | 20.09 |
March | 482.83 | 20.95 | 235.67 | 20.72 | 229.00 | 20.58 |
April | 385.33 | 21.47 | 140.33 | 21.55 | 89.33 | 21.36 |
May | 275.50 | 22.70 | 165.33 | 23.32 | 15.50 | 23.41 |
June | 74.33 | 24.16 | 396.50 | 24.31 | 28.50 | 24.40 |
July | 67.17 | 26.04 | 475.67 | 24.67 | 65.00 | 24.83 |
August | 62.83 | 25.09 | 458.50 | 24.49 | 39.17 | 24.61 |
September | 169.00 | 23.05 | 255.67 | 23.81 | 20.67 | 23.90 |
October | 322.83 | 21.98 | 160.33 | 22.36 | 40.50 | 22.19 |
November | 478.17 | 20.69 | 251.00 | 20.44 | 251.00 | 20.32 |
December | 497.00 | 20.19 | 431.17 | 20.10 | 431.17 | 20.07 |
Annual Sum or Average | 3771.00 | 21.19 | 3776.83 | 21.71 | 2016.50 | 21.45 |
Minimum of Months | 62.83 | 20.01 | 140.33 | 19.90 | 15.50 | 19.86 |
Maximum of Months | 502.00 | 26.04 | 475.67 | 24.67 | 431.17 | 24.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.21 | 435.50 | 20.15 | 435.50 | 20.13 |
February | 454.00 | 20.34 | 428.67 | 20.32 | 428.67 | 20.32 |
March | 514.00 | 20.90 | 273.83 | 20.77 | 273.83 | 20.70 |
April | 471.33 | 21.79 | 68.17 | 21.63 | 66.17 | 21.50 |
May | 360.67 | 22.93 | 58.33 | 23.09 | 3.17 | 23.10 |
June | 43.83 | 23.97 | 356.50 | 24.19 | 11.83 | 24.22 |
July | 33.33 | 25.69 | 495.50 | 24.45 | 33.33 | 24.52 |
August | 22.33 | 25.76 | 453.33 | 24.40 | 20.50 | 24.46 |
September | 97.00 | 23.50 | 280.00 | 24.05 | 5.83 | 24.07 |
October | 292.67 | 22.91 | 118.67 | 23.23 | 0.00 | 23.23 |
November | 488.50 | 21.55 | 137.33 | 21.29 | 137.33 | 21.12 |
December | 497.00 | 20.55 | 424.00 | 20.51 | 424.00 | 20.49 |
Annual Sum or Average | 3776.67 | 21.41 | 3529.83 | 21.84 | 1840.17 | 21.58 |
Minimum of Months | 22.33 | 20.21 | 58.33 | 20.15 | 0.00 | 20.13 |
Maximum of Months | 514.00 | 25.76 | 495.50 | 24.45 | 435.50 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.30 | 403.00 | 20.20 | 403.00 | 20.16 |
February | 454.00 | 20.57 | 361.17 | 20.48 | 361.17 | 20.45 |
March | 514.00 | 21.34 | 153.83 | 21.10 | 153.83 | 20.96 |
April | 382.67 | 22.06 | 62.17 | 22.11 | 32.33 | 21.99 |
May | 243.00 | 22.89 | 142.83 | 23.57 | 5.33 | 23.59 |
June | 27.17 | 24.70 | 413.50 | 24.36 | 13.00 | 24.41 |
July | 51.50 | 26.37 | 496.50 | 24.69 | 51.50 | 24.83 |
August | 30.83 | 26.53 | 494.33 | 24.56 | 30.83 | 24.67 |
September | 68.50 | 24.16 | 358.17 | 24.40 | 18.50 | 24.49 |
October | 197.83 | 23.21 | 203.67 | 23.71 | 0.50 | 23.71 |
November | 461.50 | 21.79 | 106.50 | 21.53 | 104.50 | 21.35 |
December | 497.00 | 20.76 | 314.83 | 20.62 | 314.83 | 20.56 |
Annual Sum or Average | 3430.00 | 21.56 | 3510.50 | 22.20 | 1489.33 | 21.95 |
Minimum of Months | 27.17 | 20.30 | 62.17 | 20.20 | 0.50 | 20.16 |
Maximum of Months | 514.00 | 26.53 | 496.50 | 24.69 | 403.00 | 24.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.85 | 366.00 | 19.62 | 366.00 | 19.53 |
February | 448.67 | 20.19 | 319.67 | 19.94 | 319.67 | 19.84 |
March | 499.50 | 20.85 | 182.17 | 20.54 | 180.83 | 20.35 |
April | 416.33 | 21.46 | 92.00 | 21.44 | 61.67 | 21.25 |
May | 361.33 | 22.37 | 75.67 | 22.70 | 17.83 | 22.68 |
June | 145.00 | 23.62 | 369.83 | 24.05 | 99.83 | 24.03 |
July | 143.33 | 24.64 | 491.67 | 24.51 | 142.83 | 24.53 |
August | 87.67 | 24.94 | 484.67 | 24.56 | 80.83 | 24.63 |
September | 120.83 | 23.85 | 372.33 | 24.34 | 59.33 | 24.41 |
October | 157.33 | 22.81 | 282.17 | 23.86 | 18.00 | 23.88 |
November | 428.17 | 21.30 | 125.67 | 21.11 | 104.33 | 20.88 |
December | 485.33 | 20.57 | 294.33 | 20.37 | 286.00 | 20.23 |
Annual Sum or Average | 3795.50 | 21.39 | 3456.17 | 21.96 | 1737.17 | 21.73 |
Minimum of Months | 87.67 | 19.85 | 75.67 | 19.62 | 17.83 | 19.53 |
Maximum of Months | 502.00 | 24.94 | 491.67 | 24.56 | 366.00 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.33 | 400.33 | 20.22 | 400.33 | 20.18 |
February | 454.00 | 20.57 | 371.83 | 20.47 | 371.83 | 20.43 |
March | 504.00 | 21.32 | 180.00 | 21.13 | 177.50 | 21.00 |
April | 406.50 | 21.93 | 71.17 | 21.98 | 39.67 | 21.85 |
May | 269.50 | 22.84 | 129.00 | 23.37 | 0.50 | 23.37 |
June | 34.33 | 24.88 | 413.17 | 24.40 | 19.33 | 24.47 |
July | 48.50 | 26.34 | 493.33 | 24.66 | 48.17 | 24.79 |
August | 27.67 | 26.49 | 491.33 | 24.55 | 27.67 | 24.65 |
September | 74.83 | 23.87 | 334.00 | 24.29 | 14.67 | 24.36 |
October | 200.17 | 23.09 | 212.50 | 23.67 | 0.33 | 23.67 |
November | 474.17 | 21.59 | 127.50 | 21.34 | 127.50 | 21.17 |
December | 497.00 | 20.73 | 355.50 | 20.62 | 355.50 | 20.57 |
Annual Sum or Average | 3492.67 | 21.52 | 3579.67 | 22.14 | 1583.00 | 21.88 |
Minimum of Months | 27.67 | 20.33 | 71.17 | 20.22 | 0.33 | 20.18 |
Maximum of Months | 504.00 | 26.49 | 493.33 | 24.66 | 400.33 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.13 | 404.50 | 20.03 | 404.50 | 19.99 |
February | 454.00 | 20.31 | 389.67 | 20.25 | 389.67 | 20.22 |
March | 513.83 | 21.16 | 193.33 | 20.94 | 193.33 | 20.82 |
April | 417.50 | 22.08 | 59.17 | 22.00 | 42.00 | 21.86 |
May | 212.33 | 23.18 | 127.50 | 23.59 | 0.00 | 23.59 |
June | 24.67 | 24.70 | 423.00 | 24.32 | 15.00 | 24.35 |
July | 49.00 | 25.83 | 497.00 | 24.59 | 49.00 | 24.69 |
August | 29.00 | 25.89 | 467.83 | 24.47 | 27.67 | 24.55 |
September | 106.50 | 23.42 | 282.33 | 24.03 | 8.17 | 24.05 |
October | 303.17 | 22.68 | 122.00 | 22.99 | 9.50 | 22.95 |
November | 489.00 | 21.29 | 163.83 | 21.00 | 163.83 | 20.82 |
December | 497.00 | 20.40 | 421.50 | 20.34 | 421.50 | 20.31 |
Annual Sum or Average | 3598.00 | 21.37 | 3551.67 | 21.89 | 1724.17 | 21.62 |
Minimum of Months | 24.67 | 20.13 | 59.17 | 20.03 | 0.00 | 19.99 |
Maximum of Months | 513.83 | 25.89 | 497.00 | 24.59 | 421.50 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.03 | 346.00 | 19.91 | 346.00 | 19.87 |
February | 385.00 | 20.41 | 299.67 | 20.29 | 299.67 | 20.24 |
March | 423.17 | 21.26 | 130.17 | 21.00 | 129.67 | 20.84 |
April | 315.33 | 22.01 | 78.33 | 22.27 | 25.67 | 22.16 |
May | 189.50 | 23.17 | 157.83 | 23.85 | 11.33 | 23.95 |
June | 29.67 | 25.37 | 354.33 | 24.50 | 20.67 | 24.58 |
July | 65.17 | 26.42 | 421.17 | 24.86 | 65.17 | 25.04 |
August | 42.00 | 26.32 | 401.67 | 24.67 | 40.33 | 24.82 |
September | 107.50 | 23.73 | 263.33 | 24.28 | 21.67 | 24.39 |
October | 242.17 | 22.67 | 117.50 | 23.13 | 7.00 | 23.10 |
November | 405.67 | 21.24 | 139.00 | 20.95 | 138.33 | 20.77 |
December | 422.00 | 20.43 | 320.00 | 20.31 | 320.00 | 20.26 |
Annual Sum or Average | 3054.17 | 21.48 | 3029.00 | 22.06 | 1425.50 | 21.81 |
Minimum of Months | 29.67 | 20.03 | 78.33 | 19.91 | 7.00 | 19.87 |
Maximum of Months | 427.00 | 26.42 | 421.17 | 24.86 | 346.00 | 25.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.67 | 20.72 | 290.50 | 20.37 | 290.50 | 20.22 |
February | 424.00 | 21.16 | 242.83 | 20.85 | 239.33 | 20.69 |
March | 427.83 | 21.59 | 131.83 | 21.43 | 111.67 | 21.24 |
April | 340.67 | 22.15 | 95.83 | 22.41 | 27.17 | 22.29 |
May | 199.00 | 23.16 | 176.17 | 23.75 | 4.67 | 23.79 |
June | 37.67 | 24.93 | 429.00 | 24.37 | 22.50 | 24.44 |
July | 68.17 | 26.19 | 497.00 | 24.71 | 68.17 | 24.87 |
August | 46.67 | 26.26 | 480.17 | 24.60 | 44.17 | 24.74 |
September | 86.67 | 24.34 | 360.50 | 24.41 | 28.83 | 24.54 |
October | 171.33 | 23.11 | 263.33 | 23.91 | 9.83 | 23.96 |
November | 396.17 | 21.70 | 129.83 | 21.54 | 99.00 | 21.32 |
December | 455.50 | 21.12 | 260.50 | 20.88 | 251.83 | 20.72 |
Annual Sum or Average | 3141.33 | 21.87 | 3357.50 | 22.52 | 1197.67 | 22.29 |
Minimum of Months | 37.67 | 20.72 | 95.83 | 20.37 | 4.67 | 20.22 |
Maximum of Months | 487.67 | 26.26 | 497.00 | 24.71 | 290.50 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.26 | 373.67 | 20.10 | 373.67 | 20.04 |
February | 454.00 | 20.56 | 338.50 | 20.39 | 338.50 | 20.33 |
March | 476.50 | 21.29 | 166.00 | 21.10 | 158.33 | 20.96 |
April | 375.17 | 21.92 | 90.00 | 22.09 | 37.17 | 21.97 |
May | 220.33 | 23.03 | 185.17 | 23.65 | 7.50 | 23.71 |
June | 41.83 | 24.98 | 422.50 | 24.40 | 25.50 | 24.49 |
July | 57.00 | 26.26 | 494.00 | 24.66 | 57.00 | 24.81 |
August | 42.50 | 25.87 | 474.00 | 24.54 | 35.67 | 24.65 |
September | 116.50 | 23.47 | 306.33 | 24.09 | 17.67 | 24.18 |
October | 262.83 | 22.54 | 167.50 | 23.11 | 8.17 | 23.08 |
November | 473.17 | 21.20 | 161.83 | 20.93 | 161.33 | 20.78 |
December | 497.00 | 20.55 | 373.83 | 20.43 | 373.83 | 20.38 |
Annual Sum or Average | 3518.83 | 21.45 | 3553.33 | 22.06 | 1594.33 | 21.81 |
Minimum of Months | 41.83 | 20.26 | 90.00 | 20.10 | 7.50 | 20.04 |
Maximum of Months | 502.00 | 26.26 | 494.00 | 24.66 | 373.83 | 24.81 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.56255 | 23.83022 | -0.2019 | 8.23067 |
February | 454.00000 | 23.12944 | 19.77227 | -0.0808 | 5.75389 |
March | 514.00000 | 23.72219 | 27.13119 | 0.14202 | 5.77283 |
April | 485.00000 | 24.05922 | 32.56262 | 0.28996 | 7.16457 |
May | 508.00000 | 24.30912 | 39.87886 | -0.4306 | 9.30177 |
June | 496.00000 | 24.38095 | 49.04897 | -0.2969 | 7.32845 |
July | 497.00000 | 24.43707 | 52.35086 | -0.2435 | 6.74433 |
August | 514.00000 | 24.40665 | 49.07264 | -0.2677 | 7.10119 |
September | 485.00000 | 24.40870 | 44.88695 | -0.3240 | 7.71517 |
October | 502.00000 | 24.36682 | 38.64605 | 0.45226 | 9.73168 |
November | 489.00000 | 23.93019 | 29.85253 | 0.22192 | 6.89074 |
December | 497.00000 | 23.41935 | 22.73159 | 0.02055 | 5.36454 |
Annual Sum or Average | 5943.00000 | 23.93286 | 35.93675 | -0.0606 | 7.27094 |
Minimum of Months | 454.00000 | 22.56255 | 19.77227 | -0.4306 | 5.36454 |
Maximum of Months | 514.00000 | 24.43707 | 52.35086 | 0.45226 | 9.73168 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.09013 | 25.67128 | -0.5331 | 12.88889 |
February | 454.00000 | 21.45692 | 21.43107 | -0.4608 | 10.17240 |
March | 514.00000 | 22.41744 | 29.86417 | -0.1536 | 6.31602 |
April | 485.00000 | 23.22099 | 35.20998 | 0.09545 | 6.26972 |
May | 508.00000 | 23.94680 | 41.61846 | -0.5633 | 12.24264 |
June | 496.00000 | 24.24130 | 50.28360 | -0.3600 | 8.06738 |
July | 497.00000 | 24.31461 | 54.00704 | -0.2946 | 7.15274 |
August | 514.00000 | 24.30538 | 50.59725 | -0.3177 | 7.56381 |
September | 485.00000 | 24.19294 | 46.14250 | -0.4197 | 9.17786 |
October | 502.00000 | 23.91972 | 40.18425 | 0.32723 | 7.94460 |
November | 489.00000 | 22.58681 | 33.05129 | -0.0938 | 6.99632 |
December | 497.00000 | 21.64059 | 25.26472 | -0.3834 | 8.73496 |
Annual Sum or Average | 5943.00000 | 23.12317 | 37.90094 | -0.2624 | 8.62209 |
Minimum of Months | 454.00000 | 21.09013 | 21.43107 | -0.5633 | 6.26972 |
Maximum of Months | 514.00000 | 24.31461 | 54.00704 | 0.32723 | 12.88889 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.54190 | 26.46605 | -0.6892 | 17.30005 |
February | 454.00000 | 20.80685 | 21.38612 | -0.6458 | 15.18339 |
March | 514.00000 | 21.70624 | 30.82373 | -0.3321 | 8.61952 |
April | 485.00000 | 22.67421 | 36.13069 | -0.0372 | 6.88081 |
May | 508.00000 | 23.72085 | 42.23941 | -0.6358 | 14.59157 |
June | 496.00000 | 24.19678 | 50.13590 | -0.3677 | 8.25037 |
July | 497.00000 | 24.32831 | 53.93329 | -0.2767 | 6.95887 |
August | 514.00000 | 24.28605 | 50.48615 | -0.3147 | 7.55609 |
September | 485.00000 | 24.01500 | 46.35912 | -0.4823 | 10.69268 |
October | 502.00000 | 23.38432 | 41.46527 | 0.19562 | 7.33420 |
November | 489.00000 | 21.69942 | 34.44763 | -0.3198 | 9.39579 |
December | 497.00000 | 20.84613 | 25.86762 | -0.6015 | 13.86279 |
Annual Sum or Average | 5943.00000 | 22.69831 | 38.43894 | -0.3742 | 10.52409 |
Minimum of Months | 454.00000 | 20.54190 | 21.38612 | -0.6892 | 6.88081 |
Maximum of Months | 514.00000 | 24.32831 | 53.93329 | 0.19562 | 17.30005 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.90306 | 27.64819 | -0.8987 | 24.81097 |
February | 454.00000 | 20.04382 | 22.28723 | -0.8855 | 23.80453 |
March | 514.00000 | 20.79846 | 32.48505 | -0.5699 | 13.84287 |
April | 485.00000 | 21.93516 | 37.81839 | -0.2142 | 9.10157 |
May | 508.00000 | 23.46009 | 43.44822 | -0.7084 | 18.08995 |
June | 496.00000 | 24.19516 | 52.06595 | -0.3211 | 8.08556 |
July | 497.00000 | 24.47085 | 56.75918 | -0.1603 | 6.63718 |
August | 514.00000 | 24.30885 | 52.36928 | -0.2563 | 7.41882 |
September | 485.00000 | 23.79550 | 48.68568 | -0.5384 | 13.00112 |
October | 502.00000 | 22.61170 | 43.80905 | 0.01798 | 8.23073 |
November | 489.00000 | 20.72083 | 36.25292 | -0.5725 | 14.74447 |
December | 497.00000 | 20.06206 | 27.59375 | -0.8378 | 21.83171 |
Annual Sum or Average | 5943.00000 | 22.20944 | 40.23339 | -0.4929 | 14.06726 |
Minimum of Months | 454.00000 | 19.90306 | 22.28723 | -0.8987 | 6.63718 |
Maximum of Months | 514.00000 | 24.47085 | 56.75918 | 0.01798 | 24.81097 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.94795 | 27.29800 | -0.8681 | 23.81177 |
February | 454.00000 | 20.18604 | 21.87203 | -0.8189 | 21.46677 |
March | 514.00000 | 21.10822 | 31.71166 | -0.4669 | 12.40631 |
April | 485.00000 | 22.32562 | 36.50645 | -0.0909 | 8.98154 |
May | 508.00000 | 23.57670 | 42.78229 | -0.5986 | 16.62219 |
June | 496.00000 | 24.22042 | 51.65527 | -0.2528 | 7.87938 |
July | 497.00000 | 24.51595 | 56.00161 | -0.0824 | 6.92973 |
August | 514.00000 | 24.35470 | 51.72774 | -0.1523 | 6.94422 |
September | 485.00000 | 23.91665 | 47.92855 | -0.4336 | 11.99309 |
October | 502.00000 | 22.92704 | 42.63999 | 0.12740 | 8.47372 |
November | 489.00000 | 20.89922 | 35.62902 | -0.5084 | 13.60182 |
December | 497.00000 | 20.15708 | 27.18350 | -0.7938 | 20.30902 |
Annual Sum or Average | 5943.00000 | 22.36171 | 39.54192 | -0.4089 | 13.22788 |
Minimum of Months | 454.00000 | 19.94795 | 21.87203 | -0.8681 | 6.92973 |
Maximum of Months | 514.00000 | 24.51595 | 56.00161 | 0.12740 | 23.81177 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.47204 | 26.58783 | -0.7131 | 20.58504 |
February | 454.00000 | 20.91628 | 20.93934 | -0.6168 | 17.70704 |
March | 514.00000 | 21.57904 | 30.50459 | -0.3418 | 11.66102 |
April | 485.00000 | 22.34369 | 36.27145 | -0.0885 | 9.35167 |
May | 508.00000 | 23.47916 | 43.00760 | -0.6669 | 17.98437 |
June | 496.00000 | 24.17529 | 51.87034 | -0.3035 | 8.36974 |
July | 497.00000 | 24.47535 | 56.35845 | -0.1286 | 6.85999 |
August | 514.00000 | 24.35532 | 51.70402 | -0.1663 | 7.14724 |
September | 485.00000 | 24.01891 | 47.37447 | -0.3756 | 11.17956 |
October | 502.00000 | 23.42837 | 40.87944 | 0.28060 | 10.31147 |
November | 489.00000 | 21.53531 | 34.15149 | -0.3368 | 11.89879 |
December | 497.00000 | 20.89842 | 26.07614 | -0.5913 | 16.78757 |
Annual Sum or Average | 5943.00000 | 22.65354 | 38.94399 | -0.3357 | 12.45716 |
Minimum of Months | 454.00000 | 20.47204 | 20.93934 | -0.7131 | 6.85999 |
Maximum of Months | 514.00000 | 24.47535 | 56.35845 | 0.28060 | 20.58504 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.01391 | 26.99223 | -0.8610 | 23.61816 |
February | 454.00000 | 20.26040 | 21.61051 | -0.8160 | 21.96711 |
March | 514.00000 | 21.13603 | 31.32397 | -0.4644 | 12.78032 |
April | 485.00000 | 22.02687 | 37.04219 | -0.1576 | 9.67184 |
May | 508.00000 | 23.34541 | 43.42891 | -0.6778 | 18.99722 |
June | 496.00000 | 24.15372 | 51.77237 | -0.2661 | 8.46216 |
July | 497.00000 | 24.43635 | 56.25395 | -0.1112 | 7.05361 |
August | 514.00000 | 24.30849 | 51.91884 | -0.1693 | 7.29155 |
September | 485.00000 | 23.72534 | 48.40498 | -0.4952 | 13.51284 |
October | 502.00000 | 22.71350 | 43.00634 | 0.08420 | 8.87985 |
November | 489.00000 | 20.76310 | 35.67111 | -0.5495 | 14.38515 |
December | 497.00000 | 20.18663 | 26.92739 | -0.7971 | 20.58100 |
Annual Sum or Average | 5943.00000 | 22.27262 | 39.66085 | -0.4373 | 13.87601 |
Minimum of Months | 454.00000 | 20.01391 | 21.61051 | -0.8610 | 7.05361 |
Maximum of Months | 514.00000 | 24.43635 | 56.25395 | 0.08420 | 23.61816 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.20899 | 27.44349 | -0.8016 | 20.47809 |
February | 454.00000 | 20.34230 | 22.32390 | -0.7962 | 19.65636 |
March | 514.00000 | 20.89987 | 32.62262 | -0.5410 | 12.01120 |
April | 485.00000 | 21.85826 | 38.35615 | -0.2404 | 7.88354 |
May | 508.00000 | 23.25588 | 44.37161 | -0.8169 | 20.63816 |
June | 496.00000 | 24.11459 | 52.08588 | -0.3979 | 8.81441 |
July | 497.00000 | 24.36318 | 55.48870 | -0.2479 | 6.82325 |
August | 514.00000 | 24.28944 | 51.37475 | -0.2981 | 7.45865 |
September | 485.00000 | 24.02760 | 47.74465 | -0.4695 | 10.38490 |
October | 502.00000 | 23.33923 | 42.27974 | 0.19284 | 7.17952 |
November | 489.00000 | 21.55422 | 34.67215 | -0.3394 | 9.41797 |
December | 497.00000 | 20.55442 | 27.00745 | -0.6710 | 15.14780 |
Annual Sum or Average | 5943.00000 | 22.41586 | 39.77794 | -0.4506 | 12.12467 |
Minimum of Months | 454.00000 | 20.20899 | 22.32390 | -0.8169 | 6.82325 |
Maximum of Months | 514.00000 | 24.36318 | 55.48870 | 0.19284 | 20.63816 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.29626 | 27.56083 | -0.7609 | 19.19593 |
February | 454.00000 | 20.56626 | 22.29978 | -0.7107 | 16.83451 |
March | 514.00000 | 21.33701 | 32.13147 | -0.4069 | 9.93342 |
April | 485.00000 | 22.51594 | 36.73717 | -0.0588 | 7.59024 |
May | 508.00000 | 23.64307 | 43.03643 | -0.6294 | 16.21929 |
June | 496.00000 | 24.24629 | 51.41644 | -0.2962 | 7.78316 |
July | 497.00000 | 24.51070 | 54.61756 | -0.1372 | 6.54947 |
August | 514.00000 | 24.41734 | 50.53869 | -0.1646 | 6.53857 |
September | 485.00000 | 24.25284 | 46.82340 | -0.3322 | 8.82943 |
October | 502.00000 | 23.75501 | 40.83833 | 0.32558 | 8.45977 |
November | 489.00000 | 21.91194 | 34.12795 | -0.2371 | 8.66177 |
December | 497.00000 | 20.75810 | 26.94443 | -0.6027 | 13.46969 |
Annual Sum or Average | 5943.00000 | 22.69927 | 39.04926 | -0.3323 | 10.80955 |
Minimum of Months | 454.00000 | 20.29626 | 22.29978 | -0.7609 | 6.53857 |
Maximum of Months | 514.00000 | 24.51070 | 54.61756 | 0.32558 | 19.19593 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.84893 | 25.20562 | -0.7937 | 21.27972 |
February | 454.00000 | 20.24260 | 19.78293 | -0.7067 | 18.61871 |
March | 514.00000 | 20.94046 | 30.03383 | -0.4448 | 11.62032 |
April | 485.00000 | 21.87137 | 36.25391 | -0.1846 | 8.68917 |
May | 508.00000 | 22.94201 | 44.43690 | -0.8608 | 23.62527 |
June | 496.00000 | 24.03999 | 54.87387 | -0.3728 | 9.13885 |
July | 497.00000 | 24.46086 | 59.33514 | -0.1562 | 6.41681 |
August | 514.00000 | 24.43476 | 53.40184 | -0.1516 | 6.67970 |
September | 485.00000 | 24.20941 | 48.32365 | -0.2946 | 9.03253 |
October | 502.00000 | 23.86646 | 40.33779 | 0.42074 | 10.74313 |
November | 489.00000 | 21.66027 | 32.07212 | -0.2365 | 9.53948 |
December | 497.00000 | 20.69777 | 24.26997 | -0.5566 | 14.28751 |
Annual Sum or Average | 5943.00000 | 22.45018 | 39.17494 | -0.3599 | 12.45481 |
Minimum of Months | 454.00000 | 19.84893 | 19.78293 | -0.8608 | 6.41681 |
Maximum of Months | 514.00000 | 24.46086 | 59.33514 | 0.42074 | 23.62527 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.32883 | 27.39781 | -0.7598 | 19.21727 |
February | 454.00000 | 20.57403 | 22.17844 | -0.7188 | 17.45193 |
March | 514.00000 | 21.37788 | 31.80917 | -0.3990 | 10.02287 |
April | 485.00000 | 22.30404 | 37.20277 | -0.1079 | 7.82041 |
May | 508.00000 | 23.50567 | 43.52568 | -0.6830 | 17.41508 |
June | 496.00000 | 24.26465 | 51.28127 | -0.2821 | 7.70872 |
July | 497.00000 | 24.48369 | 54.76091 | -0.1475 | 6.60778 |
August | 514.00000 | 24.41684 | 50.65639 | -0.1667 | 6.56004 |
September | 485.00000 | 24.16952 | 47.09870 | -0.3632 | 9.16749 |
October | 502.00000 | 23.71490 | 40.98594 | 0.31867 | 8.54456 |
November | 489.00000 | 21.66672 | 34.44419 | -0.3003 | 9.15149 |
December | 497.00000 | 20.73133 | 26.85545 | -0.6168 | 13.89035 |
Annual Sum or Average | 5943.00000 | 22.64374 | 39.14256 | -0.3501 | 11.09800 |
Minimum of Months | 454.00000 | 20.32883 | 22.17844 | -0.7598 | 6.56004 |
Maximum of Months | 514.00000 | 24.48369 | 54.76091 | 0.31867 | 19.21727 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.13053 | 27.46798 | -0.8041 | 20.99010 |
February | 454.00000 | 20.31210 | 22.02082 | -0.7779 | 19.50237 |
March | 514.00000 | 21.15717 | 32.02409 | -0.4536 | 10.73249 |
April | 485.00000 | 22.36067 | 37.13243 | -0.1010 | 7.50551 |
May | 508.00000 | 23.72220 | 42.72348 | -0.6240 | 14.56230 |
June | 496.00000 | 24.25091 | 51.88234 | -0.3115 | 7.61789 |
July | 497.00000 | 24.46854 | 56.41156 | -0.1781 | 6.55595 |
August | 514.00000 | 24.34141 | 52.17832 | -0.2577 | 7.19236 |
September | 485.00000 | 24.00283 | 48.14183 | -0.4690 | 10.65361 |
October | 502.00000 | 23.17656 | 42.43612 | 0.15597 | 7.41288 |
November | 489.00000 | 21.28904 | 35.21826 | -0.4073 | 10.93082 |
December | 497.00000 | 20.39536 | 27.07222 | -0.7108 | 16.83743 |
Annual Sum or Average | 5943.00000 | 22.48384 | 39.69000 | -0.4094 | 11.65753 |
Minimum of Months | 454.00000 | 20.13053 | 22.02082 | -0.8041 | 6.55595 |
Maximum of Months | 514.00000 | 24.46854 | 56.41156 | 0.15597 | 20.99010 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.03488 | 26.40951 | -0.8141 | 21.55232 |
February | 385.00000 | 20.40883 | 20.82375 | -0.7349 | 18.24051 |
March | 433.00000 | 21.32128 | 30.80021 | -0.3955 | 10.29113 |
April | 410.00000 | 22.57205 | 35.82079 | -0.0258 | 8.04704 |
May | 430.00000 | 23.78758 | 41.93823 | -0.5459 | 14.43719 |
June | 418.00000 | 24.32379 | 51.15794 | -0.2512 | 7.68162 |
July | 422.00000 | 24.61558 | 55.53875 | -0.0921 | 6.97369 |
August | 433.00000 | 24.45584 | 51.50692 | -0.1610 | 6.96804 |
September | 410.00000 | 24.11020 | 47.40715 | -0.3876 | 10.54325 |
October | 427.00000 | 23.28155 | 41.18064 | 0.20614 | 7.94735 |
November | 417.00000 | 21.31669 | 34.23548 | -0.3858 | 10.76167 |
December | 422.00000 | 20.42983 | 26.05792 | -0.6909 | 16.39716 |
Annual Sum or Average | 5034.00000 | 22.56833 | 38.69051 | -0.3544 | 11.61764 |
Minimum of Months | 385.00000 | 20.03488 | 20.82375 | -0.8141 | 6.96804 |
Maximum of Months | 433.00000 | 24.61558 | 55.53875 | 0.20614 | 21.55232 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.81549 | 26.37401 | -0.5980 | 16.89447 |
February | 454.00000 | 21.36816 | 20.58429 | -0.4785 | 13.70181 |
March | 514.00000 | 22.00412 | 29.96450 | -0.2170 | 9.09102 |
April | 485.00000 | 22.77521 | 35.57309 | 0.02371 | 8.02006 |
May | 508.00000 | 23.78235 | 42.21634 | -0.5732 | 14.06155 |
June | 496.00000 | 24.26385 | 51.65083 | -0.2857 | 7.64783 |
July | 497.00000 | 24.50218 | 55.99188 | -0.1391 | 6.68604 |
August | 514.00000 | 24.40425 | 51.49150 | -0.1660 | 6.79654 |
September | 485.00000 | 24.22363 | 46.88886 | -0.3108 | 9.10131 |
October | 502.00000 | 23.86230 | 39.77307 | 0.38959 | 10.34485 |
November | 489.00000 | 22.14475 | 33.08357 | -0.1676 | 9.22515 |
December | 497.00000 | 21.41087 | 25.44264 | -0.4341 | 12.62800 |
Annual Sum or Average | 5943.00000 | 22.97520 | 38.38618 | -0.2453 | 10.33343 |
Minimum of Months | 454.00000 | 20.81549 | 20.58429 | -0.5980 | 6.68604 |
Maximum of Months | 514.00000 | 24.50218 | 55.99188 | 0.38959 | 16.89447 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.25573 | 26.91999 | -0.7639 | 19.88837 |
February | 454.00000 | 20.56050 | 21.37929 | -0.7036 | 17.81821 |
March | 514.00000 | 21.49174 | 30.92708 | -0.3505 | 10.01748 |
April | 485.00000 | 22.43470 | 36.40876 | -0.0488 | 8.17125 |
May | 508.00000 | 23.66450 | 42.63922 | -0.5800 | 14.82628 |
June | 496.00000 | 24.25300 | 51.53767 | -0.2461 | 7.62442 |
July | 497.00000 | 24.47427 | 55.88641 | -0.1190 | 6.76031 |
August | 514.00000 | 24.36575 | 51.74248 | -0.1664 | 6.85398 |
September | 485.00000 | 23.98502 | 47.84950 | -0.4139 | 10.69371 |
October | 502.00000 | 23.26121 | 41.73635 | 0.21762 | 8.30107 |
November | 489.00000 | 21.28888 | 34.77238 | -0.3928 | 10.76470 |
December | 497.00000 | 20.55408 | 26.45594 | -0.6647 | 15.73758 |
Annual Sum or Average | 5943.00000 | 22.56515 | 39.15200 | -0.3503 | 11.41189 |
Minimum of Months | 454.00000 | 20.25573 | 21.37929 | -0.7639 | 6.76031 |
Maximum of Months | 514.00000 | 24.47427 | 55.88641 | 0.21762 | 19.88837 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.458260E+09 | 0.120648E+09 | 13.17 | 0.304961E+09 | 0.153299E+09 | 0.00 | 0.69 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 23425.82 | 27-MAR-16:00 | 18704.07 | 27-MAR-16:00 | 8238.81 | 27-MAR-12:55 | 5845.46 | 27-MAR-16:00 | 0.00 |
April | 0.413474E+10 | 0.107315E+10 | 87.83 | 0.366396E+10 | 0.470777E+09 | 0.00 | 1.00 | 07-APR-12:40 | 0.00 | 01-APR-00:10 | 42212.81 | 07-APR-15:40 | 42212.81 | 07-APR-15:40 | 6004.70 | 10-APR-08:20 | 10085.24 | 07-APR-13:50 | 0.00 |
May | 0.166086E+11 | 0.426071E+10 | 285.86 | 0.138232E+11 | 0.278533E+10 | 0.00 | 1.00 | 30-MAY-06:03 | 0.00 | 01-MAY-00:10 | 79221.41 | 30-MAY-14:00 | 79221.41 | 30-MAY-14:00 | 24086.80 | 31-MAY-06:03 | 20835.47 | 30-MAY-13:40 | 0.00 |
June | 0.591475E+11 | 0.144653E+11 | 434.75 | 0.452686E+11 | 0.138789E+11 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 110372.56 | 19-JUN-06:03 | 76920.04 | 19-JUN-06:03 | 36442.15 | 28-JUN-04:03 | 28956.29 | 19-JUN-12:03 | 0.00 |
July | 0.844502E+11 | 0.208368E+11 | 451.45 | 0.621814E+11 | 0.222688E+11 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 116646.99 | 31-JUL-04:02 | 88059.41 | 10-JUL-06:03 | 52266.59 | 22-JUL-05:03 | 26716.90 | 31-JUL-04:02 | 0.00 |
August | 0.862993E+11 | 0.215805E+11 | 466.42 | 0.682703E+11 | 0.180290E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 121048.63 | 17-AUG-04:03 | 86438.93 | 22-AUG-15:50 | 51363.63 | 17-AUG-04:03 | 28271.57 | 03-AUG-04:03 | 0.00 |
September | 0.451515E+11 | 0.109744E+11 | 396.81 | 0.361125E+11 | 0.903900E+10 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 95104.05 | 08-SEP-04:03 | 70113.44 | 05-SEP-06:03 | 43239.22 | 06-SEP-04:03 | 21837.67 | 01-SEP-06:03 | 0.00 |
October | 0.192906E+11 | 0.467791E+10 | 228.34 | 0.135119E+11 | 0.577863E+10 | 0.00 | 1.00 | 02-OCT-13:00 | 0.00 | 01-OCT-00:10 | 67046.44 | 05-OCT-12:30 | 51879.88 | 04-OCT-15:30 | 28207.14 | 06-OCT-06:03 | 15417.53 | 05-OCT-12:30 | 0.00 |
November | 0.415396E+09 | 0.117401E+09 | 25.00 | 0.332024E+09 | 83372100.83 | 0.00 | 0.34 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 10584.71 | 03-NOV-14:00 | 10584.71 | 03-NOV-14:00 | 4328.27 | 10-NOV-10:00 | 2890.87 | 03-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.315956E+12 | 0.781068E+11 | 2389.63 | 0.243469E+12 | 0.724871E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.862993E+11 | 0.215805E+11 | 466.42 | 0.682703E+11 | 0.222688E+11 | 0.00 | 1.00 | 0.00 | 121048.63 | 88059.41 | 52266.59 | 28956.29 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.429498E+09 | 0.113066E+09 | 13.17 | 0.287777E+09 | 0.141721E+09 | 0.00 | 0.68 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 21261.24 | 27-MAR-16:00 | 16785.08 | 27-MAR-16:00 | 7614.93 | 27-MAR-13:00 | 5320.61 | 27-MAR-16:00 | 0.00 |
April | 0.413579E+10 | 0.107136E+10 | 92.82 | 0.368418E+10 | 0.451610E+09 | 0.00 | 1.00 | 07-APR-12:20 | 0.00 | 01-APR-00:10 | 43916.22 | 07-APR-14:30 | 43916.22 | 07-APR-14:30 | 6851.58 | 09-APR-12:02 | 10531.63 | 07-APR-14:30 | 0.00 |
May | 0.160290E+11 | 0.410316E+10 | 293.69 | 0.135938E+11 | 0.243520E+10 | 0.00 | 1.00 | 30-MAY-06:03 | 0.00 | 01-MAY-00:10 | 79520.82 | 30-MAY-14:00 | 79520.82 | 30-MAY-14:00 | 16220.30 | 18-MAY-15:00 | 20882.93 | 30-MAY-14:00 | 0.00 |
June | 0.540965E+11 | 0.132294E+11 | 433.35 | 0.415684E+11 | 0.125282E+11 | 0.00 | 1.00 | 01-JUN-09:40 | 0.00 | 01-JUN-00:10 | 108700.94 | 19-JUN-06:03 | 71249.37 | 01-JUN-15:00 | 40671.47 | 24-JUN-05:03 | 25715.02 | 19-JUN-12:04 | 0.00 |
July | 0.770409E+11 | 0.189629E+11 | 452.63 | 0.563058E+11 | 0.207351E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 115113.27 | 22-JUL-05:03 | 76227.64 | 10-JUL-06:03 | 64966.36 | 24-JUL-04:02 | 26125.46 | 22-JUL-05:03 | 0.00 |
August | 0.764358E+11 | 0.190941E+11 | 461.08 | 0.604399E+11 | 0.159959E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 112472.42 | 17-AUG-05:03 | 85400.39 | 22-AUG-14:50 | 50921.33 | 17-AUG-04:03 | 26261.62 | 05-AUG-05:03 | 0.00 |
September | 0.382197E+11 | 0.933855E+10 | 388.75 | 0.303137E+11 | 0.790596E+10 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 78602.52 | 01-SEP-05:03 | 61529.91 | 05-SEP-04:02 | 32965.02 | 06-SEP-05:03 | 18727.38 | 14-SEP-12:30 | 0.00 |
October | 0.160886E+11 | 0.393645E+10 | 226.14 | 0.112303E+11 | 0.485836E+10 | 0.00 | 1.00 | 03-OCT-10:20 | 0.00 | 01-OCT-00:10 | 57196.40 | 04-OCT-14:10 | 46427.76 | 04-OCT-15:00 | 21873.19 | 24-OCT-09:00 | 13285.55 | 04-OCT-14:10 | 0.00 |
November | 0.374870E+09 | 0.105997E+09 | 24.83 | 0.307588E+09 | 67281998.47 | 0.00 | 0.30 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 8599.28 | 03-NOV-14:00 | 8599.28 | 03-NOV-14:00 | 2857.54 | 10-NOV-10:00 | 2371.00 | 03-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.282851E+12 | 0.699550E+11 | 2386.46 | 0.217731E+12 | 0.651193E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.770409E+11 | 0.190941E+11 | 461.08 | 0.604399E+11 | 0.207351E+11 | 0.00 | 1.00 | 0.00 | 115113.27 | 85400.39 | 64966.36 | 26261.62 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 175648.00 | 51908.34 | 0.17 | 158303.63 | 17344.37 | 0.00 | 0.01 | 15-JAN-10:40 | 0.00 | 01-JAN-00:01 | 292.75 | 15-JAN-10:40 | 263.84 | 15-JAN-10:40 | 28.91 | 15-JAN-10:40 | 86.51 | 15-JAN-10:40 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.446582E+09 | 0.118375E+09 | 13.17 | 0.293320E+09 | 0.153262E+09 | 0.00 | 0.65 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 22413.79 | 27-MAR-16:00 | 17090.90 | 27-MAR-16:00 | 8087.61 | 27-MAR-13:00 | 5656.66 | 27-MAR-16:00 | 0.00 |
April | 0.435760E+10 | 0.113377E+10 | 91.90 | 0.384324E+10 | 0.514360E+09 | 0.00 | 1.00 | 07-APR-12:10 | 0.00 | 01-APR-00:10 | 48961.65 | 07-APR-14:30 | 48961.65 | 07-APR-14:30 | 6818.55 | 09-APR-12:10 | 11741.58 | 07-APR-14:30 | 0.00 |
May | 0.166977E+11 | 0.429931E+10 | 290.50 | 0.141952E+11 | 0.250251E+10 | 0.00 | 1.00 | 29-MAY-12:23 | 0.00 | 01-MAY-00:10 | 89145.15 | 30-MAY-14:00 | 89145.15 | 30-MAY-14:00 | 15066.95 | 18-MAY-15:00 | 23410.09 | 30-MAY-14:00 | 0.00 |
June | 0.570525E+11 | 0.140370E+11 | 430.02 | 0.444020E+11 | 0.126505E+11 | 0.00 | 1.00 | 01-JUN-09:50 | 0.00 | 01-JUN-00:10 | 97828.05 | 19-JUN-13:50 | 81959.61 | 19-JUN-13:40 | 38486.36 | 24-JUN-05:03 | 29154.31 | 19-JUN-12:04 | 0.00 |
July | 0.816496E+11 | 0.201601E+11 | 450.63 | 0.608259E+11 | 0.208237E+11 | 0.00 | 1.00 | 01-JUL-09:40 | 0.00 | 01-JUL-00:10 | 130721.75 | 22-JUL-05:03 | 79677.52 | 10-JUL-14:00 | 70972.45 | 22-JUL-05:03 | 29359.32 | 22-JUL-05:03 | 0.00 |
August | 0.807089E+11 | 0.202324E+11 | 456.54 | 0.647838E+11 | 0.159251E+11 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 125986.07 | 17-AUG-05:03 | 93861.79 | 22-AUG-14:40 | 59030.73 | 17-AUG-05:03 | 29091.35 | 05-AUG-05:03 | 0.00 |
September | 0.386054E+11 | 0.951842E+10 | 383.25 | 0.304592E+11 | 0.814619E+10 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 87888.50 | 01-SEP-14:00 | 87888.50 | 01-SEP-14:00 | 39520.21 | 14-SEP-05:03 | 24114.40 | 01-SEP-14:00 | 0.00 |
October | 0.155259E+11 | 0.384961E+10 | 222.72 | 0.106679E+11 | 0.485807E+10 | 0.00 | 1.00 | 03-OCT-12:00 | 0.00 | 01-OCT-00:10 | 60459.74 | 04-OCT-13:50 | 51817.42 | 04-OCT-15:00 | 21843.30 | 24-OCT-10:00 | 14109.53 | 04-OCT-13:40 | 0.00 |
November | 0.330843E+09 | 94146036.56 | 23.67 | 0.257189E+09 | 73654227.72 | 0.00 | 0.27 | 04-NOV-12:30 | 0.00 | 01-NOV-00:10 | 8494.40 | 04-NOV-12:30 | 7336.94 | 03-NOV-14:00 | 2641.29 | 10-NOV-08:00 | 2360.66 | 04-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.295375E+12 | 0.734432E+11 | 2362.56 | 0.229728E+12 | 0.656474E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.816496E+11 | 0.202324E+11 | 456.54 | 0.647838E+11 | 0.208237E+11 | 0.00 | 1.00 | 0.00 | 130721.75 | 93861.79 | 70972.45 | 29359.32 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 299.04 | 0.00 | 299.04 | 21.53 | 1604.02 | 0.00 | 0.00 | 0.00 |
February | 409.23 | 0.00 | 409.23 | 42.21 | 1665.79 | 0.00 | 0.00 | 0.00 |
March | 567.49 | 0.00 | 567.49 | 215.18 | 1095.63 | 0.00 | 0.00 | 0.00 |
April | 681.64 | 1.94 | 679.70 | 443.37 | 784.23 | 0.00 | 0.00 | 0.00 |
May | 904.31 | 30.13 | 874.18 | 854.73 | 496.42 | 0.00 | 0.00 | 0.00 |
June | 959.01 | 51.53 | 907.48 | 1189.67 | 277.66 | 0.00 | 0.00 | 0.00 |
July | 926.79 | 33.52 | 893.28 | 1322.86 | 158.03 | 0.00 | 0.00 | 0.00 |
August | 821.09 | 9.77 | 811.32 | 1159.86 | 212.70 | 0.00 | 0.00 | 0.00 |
September | 618.97 | 0.12 | 618.85 | 666.95 | 416.15 | 0.00 | 0.00 | 0.00 |
October | 535.67 | 0.00 | 535.67 | 406.12 | 745.10 | 0.00 | 0.00 | 0.00 |
November | 375.72 | 0.00 | 375.72 | 117.06 | 1108.24 | 0.00 | 0.00 | 0.00 |
December | 260.84 | 0.00 | 260.84 | 15.30 | 1474.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 614.50 | 10.64 | 603.86 | 541.25 | 831.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 260.84 | 0.00 | 260.84 | 15.30 | 158.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 959.01 | 51.53 | 907.48 | 1322.86 | 1665.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 416.44 | 166.96 | 249.48 | 262.22 | 992.54 | 0.00 | 0.00 | 0.00 |
February | 645.81 | 301.27 | 344.54 | 462.04 | 997.28 | 0.00 | 0.00 | 0.00 |
March | 823.85 | 350.39 | 473.46 | 731.96 | 704.21 | 0.00 | 0.00 | 0.00 |
April | 988.68 | 433.07 | 555.61 | 1013.83 | 508.58 | 0.00 | 0.00 | 0.00 |
May | 1199.06 | 479.21 | 719.84 | 1396.28 | 336.46 | 0.00 | 0.00 | 0.00 |
June | 1111.27 | 402.27 | 709.00 | 1455.64 | 188.35 | 0.00 | 0.00 | 0.00 |
July | 1116.14 | 402.78 | 713.35 | 1586.20 | 106.09 | 0.00 | 0.00 | 0.00 |
August | 1256.80 | 566.69 | 690.11 | 1777.96 | 142.21 | 0.00 | 0.00 | 0.00 |
September | 937.33 | 420.54 | 516.79 | 1174.99 | 268.68 | 0.00 | 0.00 | 0.00 |
October | 849.76 | 385.14 | 464.62 | 952.50 | 482.18 | 0.00 | 0.00 | 0.00 |
November | 525.51 | 201.80 | 323.71 | 436.00 | 694.83 | 0.00 | 0.00 | 0.00 |
December | 409.40 | 192.23 | 217.17 | 284.51 | 904.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 858.03 | 358.94 | 499.09 | 964.63 | 524.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 409.40 | 166.96 | 217.17 | 262.22 | 106.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1256.80 | 566.69 | 719.84 | 1777.96 | 997.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1546.98 | 1012.97 | 534.01 | 1538.47 | 1429.39 | 0.00 | 0.00 | 0.00 |
February | 2040.41 | 1350.59 | 689.83 | 2063.55 | 1448.70 | 0.00 | 0.00 | 0.00 |
March | 1840.84 | 1021.70 | 819.14 | 1969.77 | 1068.94 | 0.00 | 0.00 | 0.00 |
April | 1428.43 | 564.84 | 863.59 | 1580.28 | 810.81 | 0.00 | 0.00 | 0.00 |
May | 1251.81 | 261.11 | 990.70 | 1464.74 | 532.73 | 0.00 | 0.00 | 0.00 |
June | 1174.78 | 179.58 | 995.21 | 1585.87 | 296.69 | 0.00 | 0.00 | 0.00 |
July | 1231.41 | 213.89 | 1017.51 | 1846.94 | 161.97 | 0.00 | 0.00 | 0.00 |
August | 1644.41 | 609.94 | 1034.47 | 2488.41 | 225.31 | 0.00 | 0.00 | 0.00 |
September | 1784.21 | 922.87 | 861.35 | 2392.50 | 428.12 | 0.00 | 0.00 | 0.00 |
October | 2444.22 | 1532.70 | 911.52 | 3057.29 | 752.48 | 0.00 | 0.00 | 0.00 |
November | 1694.86 | 1017.84 | 677.02 | 1831.11 | 1043.68 | 0.00 | 0.00 | 0.00 |
December | 1676.69 | 1190.34 | 486.35 | 1741.47 | 1304.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1644.73 | 820.53 | 824.21 | 1963.81 | 788.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1174.78 | 179.58 | 486.35 | 1464.74 | 161.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2444.22 | 1532.70 | 1034.47 | 3057.29 | 1448.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 411.12 | 168.40 | 242.72 | 259.70 | 1015.80 | 0.00 | 0.00 | 0.00 |
February | 606.25 | 266.27 | 339.99 | 424.32 | 1043.31 | 0.00 | 0.00 | 0.00 |
March | 895.21 | 413.29 | 481.92 | 820.81 | 703.18 | 0.00 | 0.00 | 0.00 |
April | 978.42 | 418.64 | 559.78 | 1015.85 | 524.05 | 0.00 | 0.00 | 0.00 |
May | 1139.76 | 432.84 | 706.93 | 1335.83 | 348.73 | 0.00 | 0.00 | 0.00 |
June | 1247.44 | 503.13 | 744.31 | 1647.46 | 200.00 | 0.00 | 0.00 | 0.00 |
July | 1168.29 | 439.94 | 728.35 | 1659.32 | 113.19 | 0.00 | 0.00 | 0.00 |
August | 1292.45 | 598.32 | 694.13 | 1838.75 | 153.57 | 0.00 | 0.00 | 0.00 |
September | 917.53 | 400.96 | 516.57 | 1165.98 | 281.68 | 0.00 | 0.00 | 0.00 |
October | 909.67 | 442.35 | 467.32 | 1041.33 | 497.70 | 0.00 | 0.00 | 0.00 |
November | 427.18 | 123.46 | 303.72 | 303.02 | 714.96 | 0.00 | 0.00 | 0.00 |
December | 379.96 | 164.41 | 215.55 | 248.20 | 932.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 866.25 | 365.17 | 501.08 | 984.03 | 541.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 379.96 | 123.46 | 215.55 | 248.20 | 113.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1292.45 | 598.32 | 744.31 | 1838.75 | 1043.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.68 | 0.00 | 99.68 | 6.71 | 556.86 | 0.00 | 0.00 | 0.00 |
February | 136.40 | 0.00 | 136.40 | 13.81 | 574.59 | 0.00 | 0.00 | 0.00 |
March | 189.16 | 0.00 | 189.16 | 74.91 | 376.17 | 0.00 | 0.00 | 0.00 |
April | 227.20 | 0.65 | 226.55 | 154.38 | 264.97 | 0.00 | 0.00 | 0.00 |
May | 301.42 | 10.04 | 291.38 | 297.57 | 161.12 | 0.00 | 0.00 | 0.00 |
June | 319.66 | 17.18 | 302.48 | 406.30 | 89.13 | 0.00 | 0.00 | 0.00 |
July | 308.92 | 11.17 | 297.75 | 449.96 | 49.27 | 0.00 | 0.00 | 0.00 |
August | 273.69 | 3.26 | 270.43 | 391.26 | 70.42 | 0.00 | 0.00 | 0.00 |
September | 206.31 | 0.04 | 206.27 | 222.13 | 147.73 | 0.00 | 0.00 | 0.00 |
October | 178.55 | 0.00 | 178.55 | 129.34 | 274.67 | 0.00 | 0.00 | 0.00 |
November | 125.24 | 0.00 | 125.24 | 33.10 | 413.51 | 0.00 | 0.00 | 0.00 |
December | 86.94 | 0.00 | 86.94 | 3.76 | 531.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.82 | 3.55 | 201.28 | 183.08 | 290.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.94 | 0.00 | 86.94 | 3.76 | 49.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 319.66 | 17.18 | 302.48 | 449.96 | 574.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.68 | 0.00 | 99.68 | 6.71 | 556.90 | 0.00 | 0.00 | 0.00 |
February | 136.41 | 0.00 | 136.41 | 13.81 | 574.63 | 0.00 | 0.00 | 0.00 |
March | 189.17 | 0.00 | 189.17 | 74.92 | 376.19 | 0.00 | 0.00 | 0.00 |
April | 227.22 | 0.65 | 226.57 | 154.39 | 264.99 | 0.00 | 0.00 | 0.00 |
May | 301.44 | 10.04 | 291.40 | 297.59 | 161.13 | 0.00 | 0.00 | 0.00 |
June | 319.68 | 17.18 | 302.50 | 406.33 | 89.14 | 0.00 | 0.00 | 0.00 |
July | 308.94 | 11.17 | 297.76 | 449.99 | 49.27 | 0.00 | 0.00 | 0.00 |
August | 273.70 | 3.26 | 270.45 | 391.28 | 70.43 | 0.00 | 0.00 | 0.00 |
September | 206.33 | 0.04 | 206.29 | 222.14 | 147.74 | 0.00 | 0.00 | 0.00 |
October | 178.56 | 0.00 | 178.56 | 129.34 | 274.69 | 0.00 | 0.00 | 0.00 |
November | 125.24 | 0.00 | 125.24 | 33.10 | 413.54 | 0.00 | 0.00 | 0.00 |
December | 86.95 | 0.00 | 86.95 | 3.76 | 531.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.84 | 3.55 | 201.29 | 183.09 | 290.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.95 | 0.00 | 86.95 | 3.76 | 49.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 319.68 | 17.18 | 302.50 | 449.99 | 574.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.68 | 0.00 | 99.68 | 6.71 | 556.90 | 0.00 | 0.00 | 0.00 |
February | 136.41 | 0.00 | 136.41 | 13.81 | 574.63 | 0.00 | 0.00 | 0.00 |
March | 189.17 | 0.00 | 189.17 | 74.92 | 376.19 | 0.00 | 0.00 | 0.00 |
April | 227.22 | 0.65 | 226.57 | 154.39 | 264.99 | 0.00 | 0.00 | 0.00 |
May | 301.44 | 10.04 | 291.40 | 297.59 | 161.13 | 0.00 | 0.00 | 0.00 |
June | 319.68 | 17.18 | 302.50 | 406.33 | 89.14 | 0.00 | 0.00 | 0.00 |
July | 308.94 | 11.17 | 297.76 | 449.99 | 49.27 | 0.00 | 0.00 | 0.00 |
August | 273.70 | 3.26 | 270.45 | 391.28 | 70.43 | 0.00 | 0.00 | 0.00 |
September | 206.33 | 0.04 | 206.29 | 222.14 | 147.74 | 0.00 | 0.00 | 0.00 |
October | 178.56 | 0.00 | 178.56 | 129.34 | 274.69 | 0.00 | 0.00 | 0.00 |
November | 125.24 | 0.00 | 125.24 | 33.10 | 413.54 | 0.00 | 0.00 | 0.00 |
December | 86.95 | 0.00 | 86.95 | 3.76 | 531.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.84 | 3.55 | 201.29 | 183.09 | 290.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.95 | 0.00 | 86.95 | 3.76 | 49.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 319.68 | 17.18 | 302.50 | 449.99 | 574.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 400.60 | 160.61 | 239.99 | 251.56 | 1001.43 | 0.00 | 0.00 | 0.00 |
February | 621.24 | 289.81 | 331.43 | 443.43 | 1005.43 | 0.00 | 0.00 | 0.00 |
March | 792.51 | 337.06 | 455.45 | 711.43 | 709.74 | 0.00 | 0.00 | 0.00 |
April | 951.06 | 416.59 | 534.47 | 985.50 | 509.72 | 0.00 | 0.00 | 0.00 |
May | 1153.44 | 460.98 | 692.46 | 1362.90 | 326.58 | 0.00 | 0.00 | 0.00 |
June | 1069.00 | 386.97 | 682.03 | 1417.45 | 181.18 | 0.00 | 0.00 | 0.00 |
July | 1073.68 | 387.46 | 686.22 | 1541.12 | 101.79 | 0.00 | 0.00 | 0.00 |
August | 1208.99 | 545.13 | 663.86 | 1719.88 | 143.84 | 0.00 | 0.00 | 0.00 |
September | 901.67 | 404.54 | 497.13 | 1130.54 | 284.08 | 0.00 | 0.00 | 0.00 |
October | 817.43 | 370.48 | 446.94 | 904.58 | 525.15 | 0.00 | 0.00 | 0.00 |
November | 505.52 | 194.12 | 311.39 | 400.91 | 757.51 | 0.00 | 0.00 | 0.00 |
December | 393.83 | 184.92 | 208.91 | 265.88 | 950.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 825.39 | 345.28 | 480.11 | 931.30 | 538.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 393.83 | 160.61 | 208.91 | 251.56 | 101.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1208.99 | 545.13 | 692.46 | 1719.88 | 1005.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.84 | 6.35 | 9.49 | 9.95 | 39.60 | 0.00 | 0.00 | 0.00 |
February | 24.56 | 11.46 | 13.10 | 17.53 | 39.75 | 0.00 | 0.00 | 0.00 |
March | 31.34 | 13.33 | 18.01 | 28.13 | 28.06 | 0.00 | 0.00 | 0.00 |
April | 37.60 | 16.47 | 21.13 | 38.97 | 20.15 | 0.00 | 0.00 | 0.00 |
May | 45.61 | 18.23 | 27.38 | 53.89 | 12.91 | 0.00 | 0.00 | 0.00 |
June | 42.27 | 15.30 | 26.97 | 56.04 | 7.16 | 0.00 | 0.00 | 0.00 |
July | 42.45 | 15.32 | 27.13 | 60.93 | 4.02 | 0.00 | 0.00 | 0.00 |
August | 47.80 | 21.55 | 26.25 | 68.00 | 5.69 | 0.00 | 0.00 | 0.00 |
September | 35.65 | 16.00 | 19.66 | 44.70 | 11.23 | 0.00 | 0.00 | 0.00 |
October | 32.32 | 14.65 | 17.67 | 35.77 | 20.76 | 0.00 | 0.00 | 0.00 |
November | 19.99 | 7.68 | 12.31 | 15.85 | 29.95 | 0.00 | 0.00 | 0.00 |
December | 15.57 | 7.31 | 8.26 | 10.51 | 37.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.64 | 13.65 | 18.98 | 36.82 | 21.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.57 | 6.35 | 8.26 | 9.95 | 4.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.80 | 21.55 | 27.38 | 68.00 | 39.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.68 | 337.67 | 178.01 | 523.85 | 496.49 | 0.00 | 0.00 | 0.00 |
February | 680.16 | 450.21 | 229.95 | 700.70 | 506.03 | 0.00 | 0.00 | 0.00 |
March | 613.63 | 340.58 | 273.06 | 671.83 | 370.51 | 0.00 | 0.00 | 0.00 |
April | 476.16 | 188.29 | 287.87 | 539.61 | 275.10 | 0.00 | 0.00 | 0.00 |
May | 417.28 | 87.04 | 330.24 | 505.40 | 172.73 | 0.00 | 0.00 | 0.00 |
June | 391.61 | 59.86 | 331.74 | 539.97 | 96.29 | 0.00 | 0.00 | 0.00 |
July | 410.48 | 71.30 | 339.18 | 623.98 | 52.53 | 0.00 | 0.00 | 0.00 |
August | 548.15 | 203.32 | 344.83 | 834.34 | 79.07 | 0.00 | 0.00 | 0.00 |
September | 594.76 | 307.63 | 287.12 | 799.96 | 157.17 | 0.00 | 0.00 | 0.00 |
October | 814.77 | 510.92 | 303.85 | 1019.49 | 285.90 | 0.00 | 0.00 | 0.00 |
November | 564.97 | 339.29 | 225.68 | 610.23 | 389.57 | 0.00 | 0.00 | 0.00 |
December | 558.92 | 396.79 | 162.12 | 583.97 | 472.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 548.26 | 273.52 | 274.74 | 662.91 | 278.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 391.61 | 59.86 | 162.12 | 505.40 | 52.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 814.77 | 510.92 | 344.83 | 1019.49 | 506.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.68 | 337.67 | 178.01 | 523.85 | 496.49 | 0.00 | 0.00 | 0.00 |
February | 680.16 | 450.21 | 229.95 | 700.70 | 506.03 | 0.00 | 0.00 | 0.00 |
March | 613.63 | 340.58 | 273.06 | 671.83 | 370.51 | 0.00 | 0.00 | 0.00 |
April | 476.16 | 188.29 | 287.87 | 539.61 | 275.10 | 0.00 | 0.00 | 0.00 |
May | 417.28 | 87.04 | 330.24 | 505.40 | 172.73 | 0.00 | 0.00 | 0.00 |
June | 391.61 | 59.86 | 331.74 | 539.97 | 96.29 | 0.00 | 0.00 | 0.00 |
July | 410.48 | 71.30 | 339.18 | 623.98 | 52.53 | 0.00 | 0.00 | 0.00 |
August | 548.15 | 203.32 | 344.83 | 834.34 | 79.07 | 0.00 | 0.00 | 0.00 |
September | 594.76 | 307.63 | 287.12 | 799.96 | 157.17 | 0.00 | 0.00 | 0.00 |
October | 814.77 | 510.92 | 303.85 | 1019.49 | 285.90 | 0.00 | 0.00 | 0.00 |
November | 564.97 | 339.29 | 225.68 | 610.23 | 389.57 | 0.00 | 0.00 | 0.00 |
December | 558.92 | 396.79 | 162.12 | 583.97 | 472.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 548.26 | 273.52 | 274.74 | 662.91 | 278.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 391.61 | 59.86 | 162.12 | 505.40 | 52.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 814.77 | 510.92 | 344.83 | 1019.49 | 506.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.64 | 337.65 | 178.00 | 523.82 | 496.46 | 0.00 | 0.00 | 0.00 |
February | 680.12 | 450.18 | 229.93 | 700.65 | 506.00 | 0.00 | 0.00 | 0.00 |
March | 613.59 | 340.55 | 273.04 | 671.79 | 370.48 | 0.00 | 0.00 | 0.00 |
April | 476.13 | 188.27 | 287.85 | 539.57 | 275.08 | 0.00 | 0.00 | 0.00 |
May | 417.25 | 87.03 | 330.22 | 505.36 | 172.72 | 0.00 | 0.00 | 0.00 |
June | 391.58 | 59.86 | 331.72 | 539.94 | 96.28 | 0.00 | 0.00 | 0.00 |
July | 410.46 | 71.30 | 339.16 | 623.94 | 52.53 | 0.00 | 0.00 | 0.00 |
August | 548.12 | 203.31 | 344.81 | 834.28 | 79.07 | 0.00 | 0.00 | 0.00 |
September | 594.72 | 307.61 | 287.11 | 799.91 | 157.16 | 0.00 | 0.00 | 0.00 |
October | 814.71 | 510.88 | 303.83 | 1019.42 | 285.88 | 0.00 | 0.00 | 0.00 |
November | 564.93 | 339.27 | 225.66 | 610.19 | 389.54 | 0.00 | 0.00 | 0.00 |
December | 558.88 | 396.77 | 162.11 | 583.93 | 472.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 548.23 | 273.50 | 274.73 | 662.86 | 278.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 391.58 | 59.86 | 162.11 | 505.36 | 52.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 814.71 | 510.88 | 344.81 | 1019.42 | 506.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 395.48 | 161.99 | 233.49 | 251.76 | 1023.34 | 0.00 | 0.00 | 0.00 |
February | 583.19 | 256.14 | 327.05 | 413.19 | 1049.89 | 0.00 | 0.00 | 0.00 |
March | 861.15 | 397.57 | 463.58 | 799.42 | 711.99 | 0.00 | 0.00 | 0.00 |
April | 941.20 | 402.71 | 538.49 | 988.52 | 526.90 | 0.00 | 0.00 | 0.00 |
May | 1096.40 | 416.37 | 680.03 | 1302.88 | 339.93 | 0.00 | 0.00 | 0.00 |
June | 1199.98 | 483.98 | 716.00 | 1601.47 | 195.28 | 0.00 | 0.00 | 0.00 |
July | 1123.85 | 423.20 | 700.64 | 1611.15 | 110.18 | 0.00 | 0.00 | 0.00 |
August | 1243.28 | 575.55 | 667.73 | 1777.46 | 156.20 | 0.00 | 0.00 | 0.00 |
September | 882.63 | 385.71 | 496.92 | 1119.90 | 297.77 | 0.00 | 0.00 | 0.00 |
October | 875.06 | 425.52 | 449.54 | 988.83 | 544.11 | 0.00 | 0.00 | 0.00 |
November | 410.93 | 118.76 | 292.17 | 278.03 | 774.56 | 0.00 | 0.00 | 0.00 |
December | 365.51 | 158.16 | 207.35 | 235.20 | 977.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 833.30 | 351.28 | 482.02 | 951.16 | 556.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 365.51 | 118.76 | 207.35 | 235.20 | 110.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1243.28 | 575.55 | 716.00 | 1777.46 | 1049.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.64 | 6.40 | 9.23 | 9.95 | 40.46 | 0.00 | 0.00 | 0.00 |
February | 23.06 | 10.13 | 12.93 | 16.34 | 41.51 | 0.00 | 0.00 | 0.00 |
March | 34.05 | 15.72 | 18.33 | 31.61 | 28.15 | 0.00 | 0.00 | 0.00 |
April | 37.21 | 15.92 | 21.29 | 39.09 | 20.83 | 0.00 | 0.00 | 0.00 |
May | 43.35 | 16.46 | 26.89 | 51.51 | 13.44 | 0.00 | 0.00 | 0.00 |
June | 47.45 | 19.14 | 28.31 | 63.32 | 7.72 | 0.00 | 0.00 | 0.00 |
July | 44.44 | 16.73 | 27.70 | 63.70 | 4.36 | 0.00 | 0.00 | 0.00 |
August | 49.16 | 22.76 | 26.40 | 70.28 | 6.18 | 0.00 | 0.00 | 0.00 |
September | 34.90 | 15.25 | 19.65 | 44.28 | 11.77 | 0.00 | 0.00 | 0.00 |
October | 34.60 | 16.82 | 17.77 | 39.10 | 21.51 | 0.00 | 0.00 | 0.00 |
November | 16.25 | 4.70 | 11.55 | 10.99 | 30.63 | 0.00 | 0.00 | 0.00 |
December | 14.45 | 6.25 | 8.20 | 9.30 | 38.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.95 | 13.89 | 19.06 | 37.61 | 21.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.45 | 4.70 | 8.20 | 9.30 | 4.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.16 | 22.76 | 28.31 | 70.28 | 41.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 299.04 | 0.00 | 299.04 | 18.60 | 1676.02 | 0.00 | 0.00 | 0.00 |
February | 409.23 | 0.00 | 409.23 | 37.39 | 1748.71 | 0.00 | 0.00 | 0.00 |
March | 567.49 | 0.00 | 567.49 | 204.26 | 1170.21 | 0.00 | 0.00 | 0.00 |
April | 681.64 | 1.94 | 679.70 | 428.97 | 841.57 | 0.00 | 0.00 | 0.00 |
May | 904.31 | 30.13 | 874.18 | 845.35 | 522.96 | 0.00 | 0.00 | 0.00 |
June | 959.01 | 51.53 | 907.48 | 1192.59 | 287.45 | 0.00 | 0.00 | 0.00 |
July | 926.79 | 33.52 | 893.28 | 1330.70 | 161.28 | 0.00 | 0.00 | 0.00 |
August | 821.09 | 9.77 | 811.32 | 1164.00 | 219.62 | 0.00 | 0.00 | 0.00 |
September | 618.97 | 0.12 | 618.85 | 662.13 | 442.39 | 0.00 | 0.00 | 0.00 |
October | 535.67 | 0.00 | 535.67 | 388.04 | 808.04 | 0.00 | 0.00 | 0.00 |
November | 375.72 | 0.00 | 375.72 | 101.33 | 1204.06 | 0.00 | 0.00 | 0.00 |
December | 260.84 | 0.00 | 260.84 | 11.39 | 1574.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 614.50 | 10.64 | 603.86 | 535.42 | 883.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 260.84 | 0.00 | 260.84 | 11.39 | 161.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 959.01 | 51.53 | 907.48 | 1330.70 | 1748.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 416.44 | 166.96 | 249.48 | 257.19 | 1037.72 | 0.00 | 0.00 | 0.00 |
February | 645.81 | 301.27 | 344.54 | 452.65 | 1048.32 | 0.00 | 0.00 | 0.00 |
March | 823.85 | 350.39 | 473.46 | 722.71 | 750.11 | 0.00 | 0.00 | 0.00 |
April | 988.68 | 433.07 | 555.61 | 1004.72 | 541.51 | 0.00 | 0.00 | 0.00 |
May | 1199.06 | 479.21 | 719.84 | 1392.54 | 352.94 | 0.00 | 0.00 | 0.00 |
June | 1111.27 | 402.27 | 709.00 | 1458.61 | 194.68 | 0.00 | 0.00 | 0.00 |
July | 1116.14 | 402.78 | 713.35 | 1592.04 | 108.31 | 0.00 | 0.00 | 0.00 |
August | 1256.80 | 566.69 | 690.11 | 1782.39 | 146.48 | 0.00 | 0.00 | 0.00 |
September | 937.33 | 420.54 | 516.79 | 1172.93 | 283.90 | 0.00 | 0.00 | 0.00 |
October | 849.76 | 385.14 | 464.62 | 941.83 | 518.72 | 0.00 | 0.00 | 0.00 |
November | 525.51 | 201.80 | 323.71 | 421.14 | 751.08 | 0.00 | 0.00 | 0.00 |
December | 409.40 | 192.23 | 217.17 | 275.87 | 966.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 858.03 | 358.94 | 499.09 | 959.72 | 555.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 409.40 | 166.96 | 217.17 | 257.19 | 108.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1256.80 | 566.69 | 719.84 | 1782.39 | 1048.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1546.98 | 1012.97 | 534.01 | 1527.72 | 1500.63 | 0.00 | 0.00 | 0.00 |
February | 2040.41 | 1350.59 | 689.83 | 2046.33 | 1528.16 | 0.00 | 0.00 | 0.00 |
March | 1840.84 | 1021.70 | 819.14 | 1957.57 | 1141.32 | 0.00 | 0.00 | 0.00 |
April | 1428.43 | 564.84 | 863.59 | 1568.45 | 867.73 | 0.00 | 0.00 | 0.00 |
May | 1251.81 | 261.11 | 990.70 | 1458.57 | 562.78 | 0.00 | 0.00 | 0.00 |
June | 1174.78 | 179.58 | 995.21 | 1589.93 | 308.20 | 0.00 | 0.00 | 0.00 |
July | 1231.41 | 213.89 | 1017.51 | 1855.11 | 166.18 | 0.00 | 0.00 | 0.00 |
August | 1644.41 | 609.94 | 1034.47 | 2495.15 | 232.81 | 0.00 | 0.00 | 0.00 |
September | 1784.21 | 922.87 | 861.35 | 2390.82 | 452.93 | 0.00 | 0.00 | 0.00 |
October | 2444.22 | 1532.70 | 911.52 | 3046.05 | 807.85 | 0.00 | 0.00 | 0.00 |
November | 1694.86 | 1017.84 | 677.02 | 1807.41 | 1129.94 | 0.00 | 0.00 | 0.00 |
December | 1676.69 | 1190.34 | 486.35 | 1721.54 | 1396.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1644.73 | 820.53 | 824.21 | 1955.91 | 837.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1174.78 | 179.58 | 486.35 | 1458.57 | 166.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2444.22 | 1532.70 | 1034.47 | 3046.05 | 1528.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 411.12 | 168.40 | 242.72 | 256.35 | 1062.31 | 0.00 | 0.00 | 0.00 |
February | 606.25 | 266.27 | 339.99 | 419.19 | 1096.56 | 0.00 | 0.00 | 0.00 |
March | 895.21 | 413.29 | 481.92 | 813.15 | 750.40 | 0.00 | 0.00 | 0.00 |
April | 978.42 | 418.64 | 559.78 | 1007.32 | 560.74 | 0.00 | 0.00 | 0.00 |
May | 1139.76 | 432.84 | 706.93 | 1330.70 | 368.10 | 0.00 | 0.00 | 0.00 |
June | 1247.44 | 503.13 | 744.31 | 1650.48 | 207.61 | 0.00 | 0.00 | 0.00 |
July | 1168.29 | 439.94 | 728.35 | 1664.95 | 116.14 | 0.00 | 0.00 | 0.00 |
August | 1292.45 | 598.32 | 694.13 | 1842.71 | 158.36 | 0.00 | 0.00 | 0.00 |
September | 917.53 | 400.96 | 516.57 | 1162.78 | 298.98 | 0.00 | 0.00 | 0.00 |
October | 909.67 | 442.35 | 467.32 | 1030.11 | 537.60 | 0.00 | 0.00 | 0.00 |
November | 427.18 | 123.46 | 303.72 | 290.84 | 774.82 | 0.00 | 0.00 | 0.00 |
December | 379.96 | 164.41 | 215.55 | 242.36 | 996.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 866.25 | 365.17 | 501.08 | 979.92 | 574.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 379.96 | 123.46 | 215.55 | 242.36 | 116.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1292.45 | 598.32 | 744.31 | 1842.71 | 1096.56 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.800952E+09 | 0.00 | 0.800952E+09 | 57665195.85 | 0.429621E+10 |
February | 0.989997E+09 | 0.00 | 0.989997E+09 | 0.102111E+09 | 0.402989E+10 |
March | 0.151997E+10 | 0.00 | 0.151997E+10 | 0.576328E+09 | 0.293454E+10 |
April | 0.176680E+10 | 5025323.02 | 0.176177E+10 | 0.114921E+10 | 0.203272E+10 |
May | 0.242211E+10 | 80706178.30 | 0.234141E+10 | 0.228930E+10 | 0.132962E+10 |
June | 0.248576E+10 | 0.133570E+09 | 0.235219E+10 | 0.308362E+10 | 0.719685E+09 |
July | 0.248232E+10 | 89769122.78 | 0.239255E+10 | 0.354315E+10 | 0.423267E+09 |
August | 0.219922E+10 | 26173819.73 | 0.217305E+10 | 0.310656E+10 | 0.569692E+09 |
September | 0.160437E+10 | 300432.95 | 0.160407E+10 | 0.172872E+10 | 0.107867E+10 |
October | 0.143475E+10 | 0.00 | 0.143475E+10 | 0.108775E+10 | 0.199568E+10 |
November | 0.973875E+09 | 0.00 | 0.973875E+09 | 0.303429E+09 | 0.287255E+10 |
December | 0.698643E+09 | 0.00 | 0.698643E+09 | 40979382.47 | 0.394902E+10 |
Annual Sum or Average | 0.193788E+11 | 0.335545E+09 | 0.190432E+11 | 0.170688E+11 | 0.262316E+11 |
Minimum of Months | 0.698643E+09 | 0.00 | 0.698643E+09 | 40979382.47 | 0.423267E+09 |
Maximum of Months | 0.248576E+10 | 0.133570E+09 | 0.239255E+10 | 0.354315E+10 | 0.429621E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111539E+10 | 0.447180E+09 | 0.668210E+09 | 0.702331E+09 | 0.265843E+10 |
February | 0.156234E+10 | 0.728829E+09 | 0.833507E+09 | 0.111777E+10 | 0.241263E+10 |
March | 0.220660E+10 | 0.938479E+09 | 0.126812E+10 | 0.196047E+10 | 0.188615E+10 |
April | 0.256265E+10 | 0.112252E+10 | 0.144013E+10 | 0.262784E+10 | 0.131824E+10 |
May | 0.321155E+10 | 0.128353E+10 | 0.192803E+10 | 0.373980E+10 | 0.901164E+09 |
June | 0.288042E+10 | 0.104269E+10 | 0.183773E+10 | 0.377301E+10 | 0.488196E+09 |
July | 0.298946E+10 | 0.107882E+10 | 0.191064E+10 | 0.424848E+10 | 0.284139E+09 |
August | 0.336621E+10 | 0.151782E+10 | 0.184839E+10 | 0.476210E+10 | 0.380907E+09 |
September | 0.242955E+10 | 0.109004E+10 | 0.133951E+10 | 0.304557E+10 | 0.696423E+09 |
October | 0.227598E+10 | 0.103155E+10 | 0.124443E+10 | 0.255118E+10 | 0.129147E+10 |
November | 0.136212E+10 | 0.523065E+09 | 0.839051E+09 | 0.113012E+10 | 0.180100E+10 |
December | 0.109654E+10 | 0.514866E+09 | 0.581672E+09 | 0.762019E+09 | 0.242320E+10 |
Annual Sum or Average | 0.270588E+11 | 0.113194E+11 | 0.157394E+11 | 0.304207E+11 | 0.165420E+11 |
Minimum of Months | 0.109654E+10 | 0.447180E+09 | 0.581672E+09 | 0.702331E+09 | 0.284139E+09 |
Maximum of Months | 0.336621E+10 | 0.151782E+10 | 0.192803E+10 | 0.476210E+10 | 0.265843E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.414343E+10 | 0.271314E+10 | 0.143029E+10 | 0.412064E+10 | 0.382847E+10 |
February | 0.493617E+10 | 0.326734E+10 | 0.166883E+10 | 0.499213E+10 | 0.350469E+10 |
March | 0.493050E+10 | 0.273651E+10 | 0.219399E+10 | 0.527584E+10 | 0.286305E+10 |
April | 0.370248E+10 | 0.146407E+10 | 0.223842E+10 | 0.409609E+10 | 0.210163E+10 |
May | 0.335284E+10 | 0.699346E+09 | 0.265349E+10 | 0.392316E+10 | 0.142685E+10 |
June | 0.304504E+10 | 0.465464E+09 | 0.257958E+10 | 0.411057E+10 | 0.769018E+09 |
July | 0.329820E+10 | 0.572895E+09 | 0.272531E+10 | 0.494683E+10 | 0.433822E+09 |
August | 0.440438E+10 | 0.163365E+10 | 0.277073E+10 | 0.666495E+10 | 0.603459E+09 |
September | 0.462468E+10 | 0.239207E+10 | 0.223261E+10 | 0.620137E+10 | 0.110970E+10 |
October | 0.654660E+10 | 0.410518E+10 | 0.244142E+10 | 0.818865E+10 | 0.201543E+10 |
November | 0.439307E+10 | 0.263825E+10 | 0.175482E+10 | 0.474624E+10 | 0.270523E+10 |
December | 0.449086E+10 | 0.318821E+10 | 0.130265E+10 | 0.466436E+10 | 0.349450E+10 |
Annual Sum or Average | 0.518683E+11 | 0.258761E+11 | 0.259921E+11 | 0.619308E+11 | 0.248559E+11 |
Minimum of Months | 0.304504E+10 | 0.465464E+09 | 0.130265E+10 | 0.392316E+10 | 0.433822E+09 |
Maximum of Months | 0.654660E+10 | 0.410518E+10 | 0.277073E+10 | 0.818865E+10 | 0.382847E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110114E+10 | 0.451030E+09 | 0.650111E+09 | 0.695593E+09 | 0.272071E+10 |
February | 0.146665E+10 | 0.644157E+09 | 0.822493E+09 | 0.102650E+10 | 0.252399E+10 |
March | 0.239773E+10 | 0.110696E+10 | 0.129076E+10 | 0.219847E+10 | 0.188340E+10 |
April | 0.253607E+10 | 0.108512E+10 | 0.145095E+10 | 0.263310E+10 | 0.135833E+10 |
May | 0.305274E+10 | 0.115931E+10 | 0.189343E+10 | 0.357789E+10 | 0.934037E+09 |
June | 0.323335E+10 | 0.130410E+10 | 0.192925E+10 | 0.427020E+10 | 0.518398E+09 |
July | 0.312915E+10 | 0.117834E+10 | 0.195081E+10 | 0.444434E+10 | 0.303176E+09 |
August | 0.346169E+10 | 0.160253E+10 | 0.185916E+10 | 0.492491E+10 | 0.411309E+09 |
September | 0.237825E+10 | 0.103929E+10 | 0.133896E+10 | 0.302222E+10 | 0.730125E+09 |
October | 0.243645E+10 | 0.118478E+10 | 0.125167E+10 | 0.278909E+10 | 0.133303E+10 |
November | 0.110724E+10 | 0.320000E+09 | 0.787241E+09 | 0.785432E+09 | 0.185318E+10 |
December | 0.101770E+10 | 0.440359E+09 | 0.577337E+09 | 0.664784E+09 | 0.249684E+10 |
Annual Sum or Average | 0.273181E+11 | 0.115160E+11 | 0.158022E+11 | 0.310325E+11 | 0.170665E+11 |
Minimum of Months | 0.101770E+10 | 0.320000E+09 | 0.577337E+09 | 0.664784E+09 | 0.303176E+09 |
Maximum of Months | 0.346169E+10 | 0.160253E+10 | 0.195081E+10 | 0.492491E+10 | 0.272071E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.266971E+09 | 0.00 | 0.266971E+09 | 17980008.23 | 0.149150E+10 |
February | 0.329983E+09 | 0.00 | 0.329983E+09 | 33412323.14 | 0.139005E+10 |
March | 0.506633E+09 | 0.00 | 0.506633E+09 | 0.200645E+09 | 0.100753E+10 |
April | 0.588905E+09 | 1675028.42 | 0.587230E+09 | 0.400156E+09 | 0.686814E+09 |
May | 0.807333E+09 | 26900786.64 | 0.780432E+09 | 0.797022E+09 | 0.431556E+09 |
June | 0.828548E+09 | 44521364.70 | 0.784027E+09 | 0.105314E+10 | 0.231025E+09 |
July | 0.827402E+09 | 29921625.21 | 0.797480E+09 | 0.120517E+10 | 0.131953E+09 |
August | 0.733039E+09 | 8724193.80 | 0.724315E+09 | 0.104794E+10 | 0.188625E+09 |
September | 0.534764E+09 | 100139.58 | 0.534664E+09 | 0.575757E+09 | 0.382907E+09 |
October | 0.478227E+09 | 0.00 | 0.478227E+09 | 0.346414E+09 | 0.735679E+09 |
November | 0.324610E+09 | 0.00 | 0.324610E+09 | 85783494.92 | 0.107183E+10 |
December | 0.232870E+09 | 0.00 | 0.232870E+09 | 10062135.91 | 0.142433E+10 |
Annual Sum or Average | 0.645929E+10 | 0.111843E+09 | 0.634744E+10 | 0.577348E+10 | 0.917379E+10 |
Minimum of Months | 0.232870E+09 | 0.00 | 0.232870E+09 | 10062135.91 | 0.131953E+09 |
Maximum of Months | 0.828548E+09 | 44521364.70 | 0.797480E+09 | 0.120517E+10 | 0.149150E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.266988E+09 | 0.00 | 0.266988E+09 | 17981144.53 | 0.149160E+10 |
February | 0.330004E+09 | 0.00 | 0.330004E+09 | 33414434.74 | 0.139013E+10 |
March | 0.506665E+09 | 0.00 | 0.506665E+09 | 0.200658E+09 | 0.100759E+10 |
April | 0.588943E+09 | 1675134.28 | 0.587267E+09 | 0.400182E+09 | 0.686857E+09 |
May | 0.807384E+09 | 26902486.73 | 0.780481E+09 | 0.797073E+09 | 0.431583E+09 |
June | 0.828600E+09 | 44524178.37 | 0.784076E+09 | 0.105320E+10 | 0.231039E+09 |
July | 0.827454E+09 | 29923516.20 | 0.797531E+09 | 0.120525E+10 | 0.131961E+09 |
August | 0.733085E+09 | 8724745.15 | 0.724360E+09 | 0.104801E+10 | 0.188637E+09 |
September | 0.534798E+09 | 100145.91 | 0.534698E+09 | 0.575793E+09 | 0.382931E+09 |
October | 0.478257E+09 | 0.00 | 0.478257E+09 | 0.346436E+09 | 0.735726E+09 |
November | 0.324630E+09 | 0.00 | 0.324630E+09 | 85788916.29 | 0.107190E+10 |
December | 0.232885E+09 | 0.00 | 0.232885E+09 | 10062771.82 | 0.142442E+10 |
Annual Sum or Average | 0.645969E+10 | 0.111850E+09 | 0.634784E+10 | 0.577385E+10 | 0.917437E+10 |
Minimum of Months | 0.232885E+09 | 0.00 | 0.232885E+09 | 10062771.82 | 0.131961E+09 |
Maximum of Months | 0.828600E+09 | 44524178.37 | 0.797531E+09 | 0.120525E+10 | 0.149160E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.266988E+09 | 0.00 | 0.266988E+09 | 17981144.53 | 0.149160E+10 |
February | 0.330004E+09 | 0.00 | 0.330004E+09 | 33414434.74 | 0.139013E+10 |
March | 0.506665E+09 | 0.00 | 0.506665E+09 | 0.200658E+09 | 0.100759E+10 |
April | 0.588943E+09 | 1675134.28 | 0.587267E+09 | 0.400182E+09 | 0.686857E+09 |
May | 0.807384E+09 | 26902486.73 | 0.780481E+09 | 0.797073E+09 | 0.431583E+09 |
June | 0.828600E+09 | 44524178.37 | 0.784076E+09 | 0.105320E+10 | 0.231039E+09 |
July | 0.827454E+09 | 29923516.20 | 0.797531E+09 | 0.120525E+10 | 0.131961E+09 |
August | 0.733085E+09 | 8724745.15 | 0.724360E+09 | 0.104801E+10 | 0.188637E+09 |
September | 0.534798E+09 | 100145.91 | 0.534698E+09 | 0.575793E+09 | 0.382931E+09 |
October | 0.478257E+09 | 0.00 | 0.478257E+09 | 0.346436E+09 | 0.735726E+09 |
November | 0.324630E+09 | 0.00 | 0.324630E+09 | 85788916.29 | 0.107190E+10 |
December | 0.232885E+09 | 0.00 | 0.232885E+09 | 10062771.82 | 0.142442E+10 |
Annual Sum or Average | 0.645969E+10 | 0.111850E+09 | 0.634784E+10 | 0.577385E+10 | 0.917437E+10 |
Minimum of Months | 0.232885E+09 | 0.00 | 0.232885E+09 | 10062771.82 | 0.131961E+09 |
Maximum of Months | 0.828600E+09 | 44524178.37 | 0.797531E+09 | 0.120525E+10 | 0.149160E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107296E+10 | 0.430167E+09 | 0.642790E+09 | 0.673779E+09 | 0.268222E+10 |
February | 0.150290E+10 | 0.701101E+09 | 0.801800E+09 | 0.107275E+10 | 0.243233E+10 |
March | 0.212265E+10 | 0.902774E+09 | 0.121988E+10 | 0.190550E+10 | 0.190098E+10 |
April | 0.246516E+10 | 0.107981E+10 | 0.138535E+10 | 0.255443E+10 | 0.132121E+10 |
May | 0.308938E+10 | 0.123469E+10 | 0.185468E+10 | 0.365040E+10 | 0.874708E+09 |
June | 0.277084E+10 | 0.100302E+10 | 0.176782E+10 | 0.367403E+10 | 0.469614E+09 |
July | 0.287574E+10 | 0.103778E+10 | 0.183796E+10 | 0.412773E+10 | 0.272630E+09 |
August | 0.323815E+10 | 0.146007E+10 | 0.177807E+10 | 0.460653E+10 | 0.385272E+09 |
September | 0.233712E+10 | 0.104857E+10 | 0.128855E+10 | 0.293036E+10 | 0.736348E+09 |
October | 0.218940E+10 | 0.992306E+09 | 0.119709E+10 | 0.242282E+10 | 0.140656E+10 |
November | 0.131030E+10 | 0.503165E+09 | 0.807132E+09 | 0.103917E+10 | 0.196346E+10 |
December | 0.105482E+10 | 0.495278E+09 | 0.559545E+09 | 0.712135E+09 | 0.254681E+10 |
Annual Sum or Average | 0.260294E+11 | 0.108887E+11 | 0.151407E+11 | 0.293696E+11 | 0.169921E+11 |
Minimum of Months | 0.105482E+10 | 0.430167E+09 | 0.559545E+09 | 0.673779E+09 | 0.272630E+09 |
Maximum of Months | 0.323815E+10 | 0.146007E+10 | 0.185468E+10 | 0.460653E+10 | 0.268222E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42423779.60 | 17008434.29 | 25415345.31 | 26640625.00 | 0.106053E+09 |
February | 59423351.52 | 27720902.05 | 31702449.46 | 42415553.12 | 96172047.68 |
March | 83927777.31 | 35694885.87 | 48232891.44 | 75341662.93 | 75162945.52 |
April | 97470154.82 | 42694718.37 | 54775436.45 | 0.101000E+09 | 52239286.21 |
May | 0.122151E+09 | 48818725.42 | 73332505.75 | 0.144334E+09 | 34585152.62 |
June | 0.109557E+09 | 39658437.19 | 69898088.15 | 0.145268E+09 | 18568124.06 |
July | 0.113704E+09 | 41032713.71 | 72671289.02 | 0.163207E+09 | 10779557.39 |
August | 0.128033E+09 | 57729954.46 | 70303454.55 | 0.182138E+09 | 15233298.00 |
September | 92407707.83 | 41459503.73 | 50948204.10 | 0.115864E+09 | 29114537.20 |
October | 86566907.50 | 39234872.02 | 47332035.48 | 95795927.15 | 55614279.24 |
November | 51807968.92 | 19894701.90 | 31913267.02 | 41087730.02 | 77633535.01 |
December | 41706729.51 | 19582843.72 | 22123885.79 | 28157190.84 | 0.100699E+09 |
Annual Sum or Average | 0.102918E+10 | 0.430531E+09 | 0.598649E+09 | 0.116125E+10 | 0.671854E+09 |
Minimum of Months | 41706729.51 | 17008434.29 | 22123885.79 | 26640625.00 | 10779557.39 |
Maximum of Months | 0.128033E+09 | 57729954.46 | 73332505.75 | 0.182138E+09 | 0.106053E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138119E+10 | 0.904410E+09 | 0.476777E+09 | 0.140309E+10 | 0.132981E+10 |
February | 0.164544E+10 | 0.108915E+10 | 0.556293E+09 | 0.169513E+10 | 0.122419E+10 |
March | 0.164355E+10 | 0.912200E+09 | 0.731352E+09 | 0.179942E+10 | 0.992367E+09 |
April | 0.123420E+10 | 0.488039E+09 | 0.746159E+09 | 0.139866E+10 | 0.713060E+09 |
May | 0.111765E+10 | 0.233123E+09 | 0.884522E+09 | 0.135365E+10 | 0.462646E+09 |
June | 0.101504E+10 | 0.155160E+09 | 0.859882E+09 | 0.139961E+10 | 0.249585E+09 |
July | 0.109943E+10 | 0.190971E+09 | 0.908462E+09 | 0.167126E+10 | 0.140695E+09 |
August | 0.146817E+10 | 0.544569E+09 | 0.923602E+09 | 0.223469E+10 | 0.211789E+09 |
September | 0.154161E+10 | 0.797383E+09 | 0.744225E+09 | 0.207350E+10 | 0.407397E+09 |
October | 0.218227E+10 | 0.136844E+10 | 0.813829E+09 | 0.273059E+10 | 0.765757E+09 |
November | 0.146440E+10 | 0.879444E+09 | 0.584959E+09 | 0.158171E+10 | 0.100975E+10 |
December | 0.149700E+10 | 0.106277E+10 | 0.434230E+09 | 0.156410E+10 | 0.126645E+10 |
Annual Sum or Average | 0.172899E+11 | 0.862566E+10 | 0.866429E+10 | 0.209054E+11 | 0.877350E+10 |
Minimum of Months | 0.101504E+10 | 0.155160E+09 | 0.434230E+09 | 0.135365E+10 | 0.140695E+09 |
Maximum of Months | 0.218227E+10 | 0.136844E+10 | 0.923602E+09 | 0.273059E+10 | 0.132981E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138119E+10 | 0.904410E+09 | 0.476777E+09 | 0.140309E+10 | 0.132981E+10 |
February | 0.164544E+10 | 0.108915E+10 | 0.556293E+09 | 0.169513E+10 | 0.122419E+10 |
March | 0.164355E+10 | 0.912200E+09 | 0.731352E+09 | 0.179942E+10 | 0.992367E+09 |
April | 0.123420E+10 | 0.488039E+09 | 0.746159E+09 | 0.139866E+10 | 0.713060E+09 |
May | 0.111765E+10 | 0.233123E+09 | 0.884522E+09 | 0.135365E+10 | 0.462646E+09 |
June | 0.101504E+10 | 0.155160E+09 | 0.859882E+09 | 0.139961E+10 | 0.249585E+09 |
July | 0.109943E+10 | 0.190971E+09 | 0.908462E+09 | 0.167126E+10 | 0.140695E+09 |
August | 0.146817E+10 | 0.544569E+09 | 0.923602E+09 | 0.223469E+10 | 0.211789E+09 |
September | 0.154161E+10 | 0.797383E+09 | 0.744225E+09 | 0.207350E+10 | 0.407397E+09 |
October | 0.218227E+10 | 0.136844E+10 | 0.813829E+09 | 0.273059E+10 | 0.765757E+09 |
November | 0.146440E+10 | 0.879444E+09 | 0.584959E+09 | 0.158171E+10 | 0.100975E+10 |
December | 0.149700E+10 | 0.106277E+10 | 0.434230E+09 | 0.156410E+10 | 0.126645E+10 |
Annual Sum or Average | 0.172899E+11 | 0.862566E+10 | 0.866429E+10 | 0.209054E+11 | 0.877350E+10 |
Minimum of Months | 0.101504E+10 | 0.155160E+09 | 0.434230E+09 | 0.135365E+10 | 0.140695E+09 |
Maximum of Months | 0.218227E+10 | 0.136844E+10 | 0.923602E+09 | 0.273059E+10 | 0.132981E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138110E+10 | 0.904353E+09 | 0.476747E+09 | 0.140300E+10 | 0.132972E+10 |
February | 0.164534E+10 | 0.108908E+10 | 0.556258E+09 | 0.169502E+10 | 0.122411E+10 |
March | 0.164345E+10 | 0.912142E+09 | 0.731306E+09 | 0.179931E+10 | 0.992304E+09 |
April | 0.123412E+10 | 0.488008E+09 | 0.746112E+09 | 0.139857E+10 | 0.713015E+09 |
May | 0.111757E+10 | 0.233108E+09 | 0.884466E+09 | 0.135357E+10 | 0.462617E+09 |
June | 0.101498E+10 | 0.155150E+09 | 0.859828E+09 | 0.139953E+10 | 0.249569E+09 |
July | 0.109936E+10 | 0.190959E+09 | 0.908404E+09 | 0.167115E+10 | 0.140686E+09 |
August | 0.146808E+10 | 0.544535E+09 | 0.923544E+09 | 0.223455E+10 | 0.211776E+09 |
September | 0.154151E+10 | 0.797333E+09 | 0.744178E+09 | 0.207337E+10 | 0.407372E+09 |
October | 0.218213E+10 | 0.136835E+10 | 0.813778E+09 | 0.273042E+10 | 0.765708E+09 |
November | 0.146431E+10 | 0.879388E+09 | 0.584922E+09 | 0.158161E+10 | 0.100969E+10 |
December | 0.149691E+10 | 0.106270E+10 | 0.434203E+09 | 0.156400E+10 | 0.126637E+10 |
Annual Sum or Average | 0.172889E+11 | 0.862511E+10 | 0.866374E+10 | 0.209041E+11 | 0.877294E+10 |
Minimum of Months | 0.101498E+10 | 0.155150E+09 | 0.434203E+09 | 0.135357E+10 | 0.140686E+09 |
Maximum of Months | 0.218213E+10 | 0.136835E+10 | 0.923544E+09 | 0.273042E+10 | 0.132972E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.105925E+10 | 0.433871E+09 | 0.625380E+09 | 0.674313E+09 | 0.274091E+10 |
February | 0.141085E+10 | 0.619650E+09 | 0.791205E+09 | 0.999579E+09 | 0.253989E+10 |
March | 0.230651E+10 | 0.106485E+10 | 0.124166E+10 | 0.214116E+10 | 0.190698E+10 |
April | 0.243959E+10 | 0.104383E+10 | 0.139576E+10 | 0.256224E+10 | 0.136573E+10 |
May | 0.293660E+10 | 0.111520E+10 | 0.182140E+10 | 0.348962E+10 | 0.910469E+09 |
June | 0.311035E+10 | 0.125449E+10 | 0.185586E+10 | 0.415100E+10 | 0.506160E+09 |
July | 0.301011E+10 | 0.113351E+10 | 0.187660E+10 | 0.431531E+10 | 0.295100E+09 |
August | 0.333000E+10 | 0.154156E+10 | 0.178843E+10 | 0.476074E+10 | 0.418369E+09 |
September | 0.228777E+10 | 0.999747E+09 | 0.128803E+10 | 0.290277E+10 | 0.771823E+09 |
October | 0.234376E+10 | 0.113971E+10 | 0.120405E+10 | 0.264849E+10 | 0.145733E+10 |
November | 0.106512E+10 | 0.307825E+09 | 0.757293E+09 | 0.720651E+09 | 0.200767E+10 |
December | 0.978981E+09 | 0.423606E+09 | 0.555375E+09 | 0.629952E+09 | 0.261781E+10 |
Annual Sum or Average | 0.262789E+11 | 0.110779E+11 | 0.152010E+11 | 0.299958E+11 | 0.175383E+11 |
Minimum of Months | 0.978981E+09 | 0.307825E+09 | 0.555375E+09 | 0.629952E+09 | 0.295100E+09 |
Maximum of Months | 0.333000E+10 | 0.154156E+10 | 0.187660E+10 | 0.476074E+10 | 0.274091E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41881722.35 | 17154805.50 | 24726916.85 | 26661599.62 | 0.108373E+09 |
February | 55783778.15 | 24500333.57 | 31283444.58 | 39522273.39 | 0.100425E+09 |
March | 91197099.77 | 42103006.45 | 49094093.32 | 84659133.85 | 75400423.23 |
April | 96458942.92 | 41272093.29 | 55186849.63 | 0.101308E+09 | 53999911.07 |
May | 0.116110E+09 | 44093983.43 | 72016417.29 | 0.137976E+09 | 35999132.92 |
June | 0.122980E+09 | 49601099.07 | 73378927.75 | 0.164126E+09 | 20013115.08 |
July | 0.119017E+09 | 44817757.63 | 74198901.55 | 0.170623E+09 | 11667986.89 |
August | 0.131665E+09 | 60951800.67 | 70712945.73 | 0.188235E+09 | 16541916.27 |
September | 90456295.00 | 39528985.56 | 50927309.44 | 0.114773E+09 | 30517158.09 |
October | 92669939.05 | 45062924.06 | 47607014.99 | 0.104719E+09 | 57621619.49 |
November | 42113711.60 | 12171094.35 | 29942617.25 | 28493770.60 | 79381385.19 |
December | 38707902.22 | 16748947.55 | 21958954.68 | 24907600.02 | 0.103506E+09 |
Annual Sum or Average | 0.103904E+10 | 0.438007E+09 | 0.601034E+09 | 0.118600E+10 | 0.693447E+09 |
Minimum of Months | 38707902.22 | 12171094.35 | 21958954.68 | 24907600.02 | 11667986.89 |
Maximum of Months | 0.131665E+09 | 60951800.67 | 74198901.55 | 0.188235E+09 | 0.108373E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.800952E+09 | 0.00 | 0.800952E+09 | 49815166.95 | 0.448904E+10 |
February | 0.989997E+09 | 0.00 | 0.989997E+09 | 90462746.22 | 0.423048E+10 |
March | 0.151997E+10 | 0.00 | 0.151997E+10 | 0.547089E+09 | 0.313430E+10 |
April | 0.176680E+10 | 5025323.02 | 0.176177E+10 | 0.111190E+10 | 0.218134E+10 |
May | 0.242211E+10 | 80706178.30 | 0.234141E+10 | 0.226417E+10 | 0.140071E+10 |
June | 0.248576E+10 | 0.133570E+09 | 0.235219E+10 | 0.309118E+10 | 0.745075E+09 |
July | 0.248232E+10 | 89769122.78 | 0.239255E+10 | 0.356414E+10 | 0.431974E+09 |
August | 0.219922E+10 | 26173819.73 | 0.217305E+10 | 0.311767E+10 | 0.588239E+09 |
September | 0.160437E+10 | 300432.95 | 0.160407E+10 | 0.171625E+10 | 0.114667E+10 |
October | 0.143475E+10 | 0.00 | 0.143475E+10 | 0.103933E+10 | 0.216425E+10 |
November | 0.973875E+09 | 0.00 | 0.973875E+09 | 0.262651E+09 | 0.312093E+10 |
December | 0.698643E+09 | 0.00 | 0.698643E+09 | 30494874.71 | 0.421734E+10 |
Annual Sum or Average | 0.193788E+11 | 0.335545E+09 | 0.190432E+11 | 0.168852E+11 | 0.278504E+11 |
Minimum of Months | 0.698643E+09 | 0.00 | 0.698643E+09 | 30494874.71 | 0.431974E+09 |
Maximum of Months | 0.248576E+10 | 0.133570E+09 | 0.239255E+10 | 0.356414E+10 | 0.448904E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111539E+10 | 0.447180E+09 | 0.668210E+09 | 0.688858E+09 | 0.277943E+10 |
February | 0.156234E+10 | 0.728829E+09 | 0.833507E+09 | 0.109505E+10 | 0.253610E+10 |
March | 0.220660E+10 | 0.938479E+09 | 0.126812E+10 | 0.193571E+10 | 0.200908E+10 |
April | 0.256265E+10 | 0.112252E+10 | 0.144013E+10 | 0.260423E+10 | 0.140358E+10 |
May | 0.321155E+10 | 0.128353E+10 | 0.192803E+10 | 0.372977E+10 | 0.945317E+09 |
June | 0.288042E+10 | 0.104269E+10 | 0.183773E+10 | 0.378071E+10 | 0.504599E+09 |
July | 0.298946E+10 | 0.107882E+10 | 0.191064E+10 | 0.426412E+10 | 0.290106E+09 |
August | 0.336621E+10 | 0.151782E+10 | 0.184839E+10 | 0.477395E+10 | 0.392329E+09 |
September | 0.242955E+10 | 0.109004E+10 | 0.133951E+10 | 0.304023E+10 | 0.735856E+09 |
October | 0.227598E+10 | 0.103155E+10 | 0.124443E+10 | 0.252260E+10 | 0.138934E+10 |
November | 0.136212E+10 | 0.523065E+09 | 0.839051E+09 | 0.109160E+10 | 0.194679E+10 |
December | 0.109654E+10 | 0.514866E+09 | 0.581672E+09 | 0.738880E+09 | 0.258816E+10 |
Annual Sum or Average | 0.270588E+11 | 0.113194E+11 | 0.157394E+11 | 0.302657E+11 | 0.175207E+11 |
Minimum of Months | 0.109654E+10 | 0.447180E+09 | 0.581672E+09 | 0.688858E+09 | 0.290106E+09 |
Maximum of Months | 0.336621E+10 | 0.151782E+10 | 0.192803E+10 | 0.477395E+10 | 0.277943E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.414343E+10 | 0.271314E+10 | 0.143029E+10 | 0.409185E+10 | 0.401930E+10 |
February | 0.493617E+10 | 0.326734E+10 | 0.166883E+10 | 0.495049E+10 | 0.369693E+10 |
March | 0.493050E+10 | 0.273651E+10 | 0.219399E+10 | 0.524316E+10 | 0.305690E+10 |
April | 0.370248E+10 | 0.146407E+10 | 0.223842E+10 | 0.406541E+10 | 0.224916E+10 |
May | 0.335284E+10 | 0.699346E+09 | 0.265349E+10 | 0.390663E+10 | 0.150734E+10 |
June | 0.304504E+10 | 0.465464E+09 | 0.257958E+10 | 0.412109E+10 | 0.798844E+09 |
July | 0.329820E+10 | 0.572895E+09 | 0.272531E+10 | 0.496873E+10 | 0.445084E+09 |
August | 0.440438E+10 | 0.163365E+10 | 0.277073E+10 | 0.668302E+10 | 0.623552E+09 |
September | 0.462468E+10 | 0.239207E+10 | 0.223261E+10 | 0.619700E+10 | 0.117401E+10 |
October | 0.654660E+10 | 0.410518E+10 | 0.244142E+10 | 0.815853E+10 | 0.216374E+10 |
November | 0.439307E+10 | 0.263825E+10 | 0.175482E+10 | 0.468481E+10 | 0.292880E+10 |
December | 0.449086E+10 | 0.318821E+10 | 0.130265E+10 | 0.461098E+10 | 0.373958E+10 |
Annual Sum or Average | 0.518683E+11 | 0.258761E+11 | 0.259921E+11 | 0.616817E+11 | 0.264032E+11 |
Minimum of Months | 0.304504E+10 | 0.465464E+09 | 0.130265E+10 | 0.390663E+10 | 0.445084E+09 |
Maximum of Months | 0.654660E+10 | 0.410518E+10 | 0.277073E+10 | 0.815853E+10 | 0.401930E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110114E+10 | 0.451030E+09 | 0.650111E+09 | 0.686621E+09 | 0.284530E+10 |
February | 0.146665E+10 | 0.644157E+09 | 0.822493E+09 | 0.101409E+10 | 0.265279E+10 |
March | 0.239773E+10 | 0.110696E+10 | 0.129076E+10 | 0.217795E+10 | 0.200986E+10 |
April | 0.253607E+10 | 0.108512E+10 | 0.145095E+10 | 0.261097E+10 | 0.145344E+10 |
May | 0.305274E+10 | 0.115931E+10 | 0.189343E+10 | 0.356415E+10 | 0.985919E+09 |
June | 0.323335E+10 | 0.130410E+10 | 0.192925E+10 | 0.427805E+10 | 0.538113E+09 |
July | 0.312915E+10 | 0.117834E+10 | 0.195081E+10 | 0.445941E+10 | 0.311077E+09 |
August | 0.346169E+10 | 0.160253E+10 | 0.185916E+10 | 0.493551E+10 | 0.424157E+09 |
September | 0.237825E+10 | 0.103929E+10 | 0.133896E+10 | 0.301392E+10 | 0.774946E+09 |
October | 0.243645E+10 | 0.118478E+10 | 0.125167E+10 | 0.275904E+10 | 0.143991E+10 |
November | 0.110724E+10 | 0.320000E+09 | 0.787241E+09 | 0.753870E+09 | 0.200834E+10 |
December | 0.101770E+10 | 0.440359E+09 | 0.577337E+09 | 0.649134E+09 | 0.266850E+10 |
Annual Sum or Average | 0.273181E+11 | 0.115160E+11 | 0.158022E+11 | 0.309027E+11 | 0.181124E+11 |
Minimum of Months | 0.101770E+10 | 0.320000E+09 | 0.577337E+09 | 0.649134E+09 | 0.311077E+09 |
Maximum of Months | 0.346169E+10 | 0.160253E+10 | 0.195081E+10 | 0.493551E+10 | 0.284530E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 21.53 | 1604.02 | 299.04 | 0.00 | 299.04 | 0.00 | 0.00 |
February | 42.21 | 1665.79 | 409.23 | 0.00 | 409.23 | 0.00 | 0.00 |
March | 215.18 | 1095.63 | 567.49 | 0.00 | 567.49 | 0.00 | 0.00 |
April | 443.37 | 784.23 | 681.64 | 1.94 | 679.70 | 0.00 | 0.00 |
May | 854.73 | 496.42 | 904.31 | 30.13 | 874.18 | 0.00 | 0.00 |
June | 1189.67 | 277.66 | 959.01 | 51.53 | 907.48 | 0.00 | 0.00 |
July | 1322.86 | 158.03 | 926.79 | 33.52 | 893.28 | 0.00 | 0.00 |
August | 1159.86 | 212.70 | 821.09 | 9.77 | 811.32 | 0.00 | 0.00 |
September | 666.95 | 416.15 | 618.97 | 0.12 | 618.85 | 0.00 | 0.00 |
October | 406.12 | 745.10 | 535.67 | 0.00 | 535.67 | 0.00 | 0.00 |
November | 117.06 | 1108.24 | 375.72 | 0.00 | 375.72 | 0.00 | 0.00 |
December | 15.30 | 1474.40 | 260.84 | 0.00 | 260.84 | 0.00 | 0.00 |
Annual Sum or Average | 541.25 | 831.80 | 614.50 | 10.64 | 603.86 | 0.00 | 0.00 |
Minimum of Months | 15.30 | 158.03 | 260.84 | 0.00 | 260.84 | 0.00 | 0.00 |
Maximum of Months | 1322.86 | 1665.79 | 959.01 | 51.53 | 907.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 262.22 | 992.54 | 416.44 | 166.96 | 249.48 | 0.00 | 0.00 |
February | 462.04 | 997.28 | 645.81 | 301.27 | 344.54 | 0.00 | 0.00 |
March | 731.96 | 704.21 | 823.85 | 350.39 | 473.46 | 0.00 | 0.00 |
April | 1013.83 | 508.58 | 988.68 | 433.07 | 555.61 | 0.00 | 0.00 |
May | 1396.28 | 336.46 | 1199.06 | 479.21 | 719.84 | 0.00 | 0.00 |
June | 1455.64 | 188.35 | 1111.27 | 402.27 | 709.00 | 0.00 | 0.00 |
July | 1586.20 | 106.09 | 1116.14 | 402.78 | 713.35 | 0.00 | 0.00 |
August | 1777.96 | 142.21 | 1256.80 | 566.69 | 690.11 | 0.00 | 0.00 |
September | 1174.99 | 268.68 | 937.33 | 420.54 | 516.79 | 0.00 | 0.00 |
October | 952.50 | 482.18 | 849.76 | 385.14 | 464.62 | 0.00 | 0.00 |
November | 436.00 | 694.83 | 525.51 | 201.80 | 323.71 | 0.00 | 0.00 |
December | 284.51 | 904.72 | 409.40 | 192.23 | 217.17 | 0.00 | 0.00 |
Annual Sum or Average | 964.63 | 524.54 | 858.03 | 358.94 | 499.09 | 0.00 | 0.00 |
Minimum of Months | 262.22 | 106.09 | 409.40 | 166.96 | 217.17 | 0.00 | 0.00 |
Maximum of Months | 1777.96 | 997.28 | 1256.80 | 566.69 | 719.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1538.47 | 1429.39 | 1546.98 | 1012.97 | 534.01 | 0.00 | 0.00 |
February | 2063.55 | 1448.70 | 2040.41 | 1350.59 | 689.83 | 0.00 | 0.00 |
March | 1969.77 | 1068.94 | 1840.84 | 1021.70 | 819.14 | 0.00 | 0.00 |
April | 1580.28 | 810.81 | 1428.43 | 564.84 | 863.59 | 0.00 | 0.00 |
May | 1464.74 | 532.73 | 1251.81 | 261.11 | 990.70 | 0.00 | 0.00 |
June | 1585.87 | 296.69 | 1174.78 | 179.58 | 995.21 | 0.00 | 0.00 |
July | 1846.94 | 161.97 | 1231.41 | 213.89 | 1017.51 | 0.00 | 0.00 |
August | 2488.41 | 225.31 | 1644.41 | 609.94 | 1034.47 | 0.00 | 0.00 |
September | 2392.50 | 428.12 | 1784.21 | 922.87 | 861.35 | 0.00 | 0.00 |
October | 3057.29 | 752.48 | 2444.22 | 1532.70 | 911.52 | 0.00 | 0.00 |
November | 1831.11 | 1043.68 | 1694.86 | 1017.84 | 677.02 | 0.00 | 0.00 |
December | 1741.47 | 1304.70 | 1676.69 | 1190.34 | 486.35 | 0.00 | 0.00 |
Annual Sum or Average | 1963.81 | 788.17 | 1644.73 | 820.53 | 824.21 | 0.00 | 0.00 |
Minimum of Months | 1464.74 | 161.97 | 1174.78 | 179.58 | 486.35 | 0.00 | 0.00 |
Maximum of Months | 3057.29 | 1448.70 | 2444.22 | 1532.70 | 1034.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 259.70 | 1015.80 | 411.12 | 168.40 | 242.72 | 0.00 | 0.00 |
February | 424.32 | 1043.31 | 606.25 | 266.27 | 339.99 | 0.00 | 0.00 |
March | 820.81 | 703.18 | 895.21 | 413.29 | 481.92 | 0.00 | 0.00 |
April | 1015.85 | 524.05 | 978.42 | 418.64 | 559.78 | 0.00 | 0.00 |
May | 1335.83 | 348.73 | 1139.76 | 432.84 | 706.93 | 0.00 | 0.00 |
June | 1647.46 | 200.00 | 1247.44 | 503.13 | 744.31 | 0.00 | 0.00 |
July | 1659.32 | 113.19 | 1168.29 | 439.94 | 728.35 | 0.00 | 0.00 |
August | 1838.75 | 153.57 | 1292.45 | 598.32 | 694.13 | 0.00 | 0.00 |
September | 1165.98 | 281.68 | 917.53 | 400.96 | 516.57 | 0.00 | 0.00 |
October | 1041.33 | 497.70 | 909.67 | 442.35 | 467.32 | 0.00 | 0.00 |
November | 303.02 | 714.96 | 427.18 | 123.46 | 303.72 | 0.00 | 0.00 |
December | 248.20 | 932.22 | 379.96 | 164.41 | 215.55 | 0.00 | 0.00 |
Annual Sum or Average | 984.03 | 541.18 | 866.25 | 365.17 | 501.08 | 0.00 | 0.00 |
Minimum of Months | 248.20 | 113.19 | 379.96 | 123.46 | 215.55 | 0.00 | 0.00 |
Maximum of Months | 1838.75 | 1043.31 | 1292.45 | 598.32 | 744.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 20.14 | 1670.66 | 299.04 | 0.00 | 299.04 | 0.00 | 0.00 |
February | 41.44 | 1723.84 | 409.22 | 0.00 | 409.22 | 0.00 | 0.00 |
March | 224.75 | 1128.55 | 567.49 | 0.00 | 567.49 | 0.00 | 0.00 |
April | 463.16 | 794.96 | 681.63 | 1.94 | 679.69 | 0.00 | 0.00 |
May | 892.76 | 483.39 | 904.31 | 30.13 | 874.18 | 0.00 | 0.00 |
June | 1218.96 | 267.40 | 959.01 | 51.53 | 907.48 | 0.00 | 0.00 |
July | 1349.94 | 147.80 | 926.79 | 33.52 | 893.27 | 0.00 | 0.00 |
August | 1173.82 | 211.28 | 821.09 | 9.77 | 811.32 | 0.00 | 0.00 |
September | 666.41 | 443.20 | 618.97 | 0.12 | 618.85 | 0.00 | 0.00 |
October | 388.03 | 824.05 | 535.67 | 0.00 | 535.67 | 0.00 | 0.00 |
November | 99.29 | 1240.60 | 375.72 | 0.00 | 375.72 | 0.00 | 0.00 |
December | 11.27 | 1595.42 | 260.84 | 0.00 | 260.84 | 0.00 | 0.00 |
Annual Sum or Average | 549.25 | 872.73 | 614.49 | 10.64 | 603.85 | 0.00 | 0.00 |
Minimum of Months | 11.27 | 147.80 | 260.84 | 0.00 | 260.84 | 0.00 | 0.00 |
Maximum of Months | 1349.94 | 1723.84 | 959.01 | 51.53 | 907.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 261.51 | 1041.02 | 416.44 | 166.96 | 249.48 | 0.00 | 0.00 |
February | 460.96 | 1045.18 | 645.80 | 301.27 | 344.54 | 0.00 | 0.00 |
March | 739.56 | 737.81 | 823.84 | 350.38 | 473.46 | 0.00 | 0.00 |
April | 1024.47 | 529.88 | 988.67 | 433.07 | 555.60 | 0.00 | 0.00 |
May | 1416.79 | 339.49 | 1199.05 | 479.21 | 719.84 | 0.00 | 0.00 |
June | 1473.49 | 188.34 | 1111.26 | 402.27 | 709.00 | 0.00 | 0.00 |
July | 1602.05 | 105.81 | 1116.13 | 402.78 | 713.35 | 0.00 | 0.00 |
August | 1787.88 | 149.53 | 1256.79 | 566.68 | 690.11 | 0.00 | 0.00 |
September | 1175.24 | 295.32 | 937.32 | 420.54 | 516.78 | 0.00 | 0.00 |
October | 940.34 | 545.91 | 849.75 | 385.13 | 464.62 | 0.00 | 0.00 |
November | 416.76 | 787.46 | 525.50 | 201.80 | 323.71 | 0.00 | 0.00 |
December | 276.39 | 988.47 | 409.40 | 192.23 | 217.17 | 0.00 | 0.00 |
Annual Sum or Average | 968.13 | 560.12 | 858.02 | 358.93 | 499.09 | 0.00 | 0.00 |
Minimum of Months | 261.51 | 105.81 | 409.40 | 166.96 | 217.17 | 0.00 | 0.00 |
Maximum of Months | 1787.88 | 1045.18 | 1256.79 | 566.68 | 719.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1571.52 | 1489.45 | 1547.00 | 1012.98 | 534.01 | 0.00 | 0.00 |
February | 2102.05 | 1518.06 | 2040.43 | 1350.60 | 689.83 | 0.00 | 0.00 |
March | 2015.44 | 1111.50 | 1840.86 | 1021.71 | 819.15 | 0.00 | 0.00 |
April | 1618.79 | 825.28 | 1428.44 | 564.85 | 863.59 | 0.00 | 0.00 |
May | 1516.16 | 518.19 | 1251.82 | 261.11 | 990.71 | 0.00 | 0.00 |
June | 1619.89 | 288.87 | 1174.79 | 179.58 | 995.21 | 0.00 | 0.00 |
July | 1871.89 | 157.58 | 1231.42 | 213.90 | 1017.52 | 0.00 | 0.00 |
August | 2502.96 | 237.21 | 1644.42 | 609.94 | 1034.48 | 0.00 | 0.00 |
September | 2399.84 | 471.51 | 1784.23 | 922.88 | 861.35 | 0.00 | 0.00 |
October | 3058.39 | 857.68 | 2444.25 | 1532.72 | 911.53 | 0.00 | 0.00 |
November | 1830.65 | 1168.67 | 1694.88 | 1017.85 | 677.02 | 0.00 | 0.00 |
December | 1751.87 | 1418.48 | 1676.71 | 1190.35 | 486.36 | 0.00 | 0.00 |
Annual Sum or Average | 1988.68 | 834.60 | 1644.75 | 820.54 | 824.21 | 0.00 | 0.00 |
Minimum of Months | 1516.16 | 157.58 | 1174.79 | 179.58 | 486.36 | 0.00 | 0.00 |
Maximum of Months | 3058.39 | 1518.06 | 2444.25 | 1532.72 | 1034.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 261.71 | 1063.80 | 411.12 | 168.39 | 242.72 | 0.00 | 0.00 |
February | 429.52 | 1091.40 | 606.25 | 266.27 | 339.98 | 0.00 | 0.00 |
March | 831.02 | 740.14 | 895.20 | 413.29 | 481.91 | 0.00 | 0.00 |
April | 1027.61 | 547.74 | 978.41 | 418.64 | 559.78 | 0.00 | 0.00 |
May | 1354.39 | 353.37 | 1139.75 | 432.83 | 706.92 | 0.00 | 0.00 |
June | 1664.79 | 203.00 | 1247.43 | 503.12 | 744.31 | 0.00 | 0.00 |
July | 1674.86 | 114.53 | 1168.28 | 439.94 | 728.34 | 0.00 | 0.00 |
August | 1847.74 | 162.38 | 1292.44 | 598.31 | 694.13 | 0.00 | 0.00 |
September | 1164.17 | 309.54 | 917.53 | 400.96 | 516.57 | 0.00 | 0.00 |
October | 1027.93 | 565.62 | 909.66 | 442.34 | 467.32 | 0.00 | 0.00 |
November | 289.02 | 805.19 | 427.17 | 123.46 | 303.72 | 0.00 | 0.00 |
December | 244.50 | 1016.02 | 379.96 | 164.41 | 215.55 | 0.00 | 0.00 |
Annual Sum or Average | 988.77 | 578.12 | 866.25 | 365.17 | 501.08 | 0.00 | 0.00 |
Minimum of Months | 244.50 | 114.53 | 379.96 | 123.46 | 215.55 | 0.00 | 0.00 |
Maximum of Months | 1847.74 | 1091.40 | 1292.44 | 598.31 | 744.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 18.60 | 1676.02 | 299.04 | 0.00 | 299.04 | 0.00 | 0.00 |
February | 37.39 | 1748.71 | 409.23 | 0.00 | 409.23 | 0.00 | 0.00 |
March | 204.26 | 1170.21 | 567.49 | 0.00 | 567.49 | 0.00 | 0.00 |
April | 428.97 | 841.57 | 681.64 | 1.94 | 679.70 | 0.00 | 0.00 |
May | 845.35 | 522.96 | 904.31 | 30.13 | 874.18 | 0.00 | 0.00 |
June | 1192.59 | 287.45 | 959.01 | 51.53 | 907.48 | 0.00 | 0.00 |
July | 1330.70 | 161.28 | 926.79 | 33.52 | 893.28 | 0.00 | 0.00 |
August | 1164.00 | 219.62 | 821.09 | 9.77 | 811.32 | 0.00 | 0.00 |
September | 662.13 | 442.39 | 618.97 | 0.12 | 618.85 | 0.00 | 0.00 |
October | 388.04 | 808.04 | 535.67 | 0.00 | 535.67 | 0.00 | 0.00 |
November | 101.33 | 1204.06 | 375.72 | 0.00 | 375.72 | 0.00 | 0.00 |
December | 11.39 | 1574.58 | 260.84 | 0.00 | 260.84 | 0.00 | 0.00 |
Annual Sum or Average | 535.42 | 883.13 | 614.50 | 10.64 | 603.86 | 0.00 | 0.00 |
Minimum of Months | 11.39 | 161.28 | 260.84 | 0.00 | 260.84 | 0.00 | 0.00 |
Maximum of Months | 1330.70 | 1748.71 | 959.01 | 51.53 | 907.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 257.19 | 1037.72 | 416.44 | 166.96 | 249.48 | 0.00 | 0.00 |
February | 452.65 | 1048.32 | 645.81 | 301.27 | 344.54 | 0.00 | 0.00 |
March | 722.71 | 750.11 | 823.85 | 350.39 | 473.46 | 0.00 | 0.00 |
April | 1004.72 | 541.51 | 988.68 | 433.07 | 555.61 | 0.00 | 0.00 |
May | 1392.54 | 352.94 | 1199.06 | 479.21 | 719.84 | 0.00 | 0.00 |
June | 1458.61 | 194.68 | 1111.27 | 402.27 | 709.00 | 0.00 | 0.00 |
July | 1592.04 | 108.31 | 1116.14 | 402.78 | 713.35 | 0.00 | 0.00 |
August | 1782.39 | 146.48 | 1256.80 | 566.69 | 690.11 | 0.00 | 0.00 |
September | 1172.93 | 283.90 | 937.33 | 420.54 | 516.79 | 0.00 | 0.00 |
October | 941.83 | 518.72 | 849.76 | 385.14 | 464.62 | 0.00 | 0.00 |
November | 421.14 | 751.08 | 525.51 | 201.80 | 323.71 | 0.00 | 0.00 |
December | 275.87 | 966.31 | 409.40 | 192.23 | 217.17 | 0.00 | 0.00 |
Annual Sum or Average | 959.72 | 555.58 | 858.03 | 358.94 | 499.09 | 0.00 | 0.00 |
Minimum of Months | 257.19 | 108.31 | 409.40 | 166.96 | 217.17 | 0.00 | 0.00 |
Maximum of Months | 1782.39 | 1048.32 | 1256.80 | 566.69 | 719.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1527.72 | 1500.63 | 1546.98 | 1012.97 | 534.01 | 0.00 | 0.00 |
February | 2046.33 | 1528.16 | 2040.41 | 1350.59 | 689.83 | 0.00 | 0.00 |
March | 1957.57 | 1141.32 | 1840.84 | 1021.70 | 819.14 | 0.00 | 0.00 |
April | 1568.45 | 867.73 | 1428.43 | 564.84 | 863.59 | 0.00 | 0.00 |
May | 1458.57 | 562.78 | 1251.81 | 261.11 | 990.70 | 0.00 | 0.00 |
June | 1589.93 | 308.20 | 1174.78 | 179.58 | 995.21 | 0.00 | 0.00 |
July | 1855.11 | 166.18 | 1231.41 | 213.89 | 1017.51 | 0.00 | 0.00 |
August | 2495.15 | 232.81 | 1644.41 | 609.94 | 1034.47 | 0.00 | 0.00 |
September | 2390.82 | 452.93 | 1784.21 | 922.87 | 861.35 | 0.00 | 0.00 |
October | 3046.05 | 807.85 | 2444.22 | 1532.70 | 911.52 | 0.00 | 0.00 |
November | 1807.41 | 1129.94 | 1694.86 | 1017.84 | 677.02 | 0.00 | 0.00 |
December | 1721.54 | 1396.20 | 1676.69 | 1190.34 | 486.35 | 0.00 | 0.00 |
Annual Sum or Average | 1955.91 | 837.24 | 1644.73 | 820.53 | 824.21 | 0.00 | 0.00 |
Minimum of Months | 1458.57 | 166.18 | 1174.78 | 179.58 | 486.35 | 0.00 | 0.00 |
Maximum of Months | 3046.05 | 1528.16 | 2444.22 | 1532.70 | 1034.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 256.35 | 1062.31 | 411.12 | 168.40 | 242.72 | 0.00 | 0.00 |
February | 419.19 | 1096.56 | 606.25 | 266.27 | 339.99 | 0.00 | 0.00 |
March | 813.15 | 750.40 | 895.21 | 413.29 | 481.92 | 0.00 | 0.00 |
April | 1007.32 | 560.74 | 978.42 | 418.64 | 559.78 | 0.00 | 0.00 |
May | 1330.70 | 368.10 | 1139.76 | 432.84 | 706.93 | 0.00 | 0.00 |
June | 1650.48 | 207.61 | 1247.44 | 503.13 | 744.31 | 0.00 | 0.00 |
July | 1664.95 | 116.14 | 1168.29 | 439.94 | 728.35 | 0.00 | 0.00 |
August | 1842.71 | 158.36 | 1292.45 | 598.32 | 694.13 | 0.00 | 0.00 |
September | 1162.78 | 298.98 | 917.53 | 400.96 | 516.57 | 0.00 | 0.00 |
October | 1030.11 | 537.60 | 909.67 | 442.35 | 467.32 | 0.00 | 0.00 |
November | 290.84 | 774.82 | 427.18 | 123.46 | 303.72 | 0.00 | 0.00 |
December | 242.36 | 996.30 | 379.96 | 164.41 | 215.55 | 0.00 | 0.00 |
Annual Sum or Average | 979.92 | 574.34 | 866.25 | 365.17 | 501.08 | 0.00 | 0.00 |
Minimum of Months | 242.36 | 116.14 | 379.96 | 123.46 | 215.55 | 0.00 | 0.00 |
Maximum of Months | 1842.71 | 1096.56 | 1292.45 | 598.32 | 744.31 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 57665195.85 | 0.429621E+10 | 0.800952E+09 | 0.00 | 0.800952E+09 | 0.00 | 0.00 |
February | 0.102111E+09 | 0.402989E+10 | 0.989997E+09 | 0.00 | 0.989997E+09 | 0.00 | 0.00 |
March | 0.576328E+09 | 0.293454E+10 | 0.151997E+10 | 0.00 | 0.151997E+10 | 0.00 | 0.00 |
April | 0.114921E+10 | 0.203272E+10 | 0.176680E+10 | 5025323.02 | 0.176177E+10 | 0.00 | 0.00 |
May | 0.228930E+10 | 0.132962E+10 | 0.242211E+10 | 80706178.30 | 0.234141E+10 | 0.00 | 0.00 |
June | 0.308362E+10 | 0.719685E+09 | 0.248576E+10 | 0.133570E+09 | 0.235219E+10 | 0.00 | 0.00 |
July | 0.354315E+10 | 0.423267E+09 | 0.248232E+10 | 89769122.78 | 0.239255E+10 | 0.00 | 0.00 |
August | 0.310656E+10 | 0.569692E+09 | 0.219922E+10 | 26173819.73 | 0.217305E+10 | 0.00 | 0.00 |
September | 0.172872E+10 | 0.107867E+10 | 0.160437E+10 | 300432.95 | 0.160407E+10 | 0.00 | 0.00 |
October | 0.108775E+10 | 0.199568E+10 | 0.143475E+10 | 0.00 | 0.143475E+10 | 0.00 | 0.00 |
November | 0.303429E+09 | 0.287255E+10 | 0.973875E+09 | 0.00 | 0.973875E+09 | 0.00 | 0.00 |
December | 40979382.47 | 0.394902E+10 | 0.698643E+09 | 0.00 | 0.698643E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.170688E+11 | 0.262316E+11 | 0.193788E+11 | 0.335545E+09 | 0.190432E+11 | 0.00 | 0.00 |
Minimum of Months | 40979382.47 | 0.423267E+09 | 0.698643E+09 | 0.00 | 0.698643E+09 | 0.00 | 0.00 |
Maximum of Months | 0.354315E+10 | 0.429621E+10 | 0.248576E+10 | 0.133570E+09 | 0.239255E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.702331E+09 | 0.265843E+10 | 0.111539E+10 | 0.447180E+09 | 0.668210E+09 | 0.00 | 0.00 |
February | 0.111777E+10 | 0.241263E+10 | 0.156234E+10 | 0.728829E+09 | 0.833507E+09 | 0.00 | 0.00 |
March | 0.196047E+10 | 0.188615E+10 | 0.220660E+10 | 0.938479E+09 | 0.126812E+10 | 0.00 | 0.00 |
April | 0.262784E+10 | 0.131824E+10 | 0.256265E+10 | 0.112252E+10 | 0.144013E+10 | 0.00 | 0.00 |
May | 0.373980E+10 | 0.901164E+09 | 0.321155E+10 | 0.128353E+10 | 0.192803E+10 | 0.00 | 0.00 |
June | 0.377301E+10 | 0.488196E+09 | 0.288042E+10 | 0.104269E+10 | 0.183773E+10 | 0.00 | 0.00 |
July | 0.424848E+10 | 0.284139E+09 | 0.298946E+10 | 0.107882E+10 | 0.191064E+10 | 0.00 | 0.00 |
August | 0.476210E+10 | 0.380907E+09 | 0.336621E+10 | 0.151782E+10 | 0.184839E+10 | 0.00 | 0.00 |
September | 0.304557E+10 | 0.696423E+09 | 0.242955E+10 | 0.109004E+10 | 0.133951E+10 | 0.00 | 0.00 |
October | 0.255118E+10 | 0.129147E+10 | 0.227598E+10 | 0.103155E+10 | 0.124443E+10 | 0.00 | 0.00 |
November | 0.113012E+10 | 0.180100E+10 | 0.136212E+10 | 0.523065E+09 | 0.839051E+09 | 0.00 | 0.00 |
December | 0.762019E+09 | 0.242320E+10 | 0.109654E+10 | 0.514866E+09 | 0.581672E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.304207E+11 | 0.165420E+11 | 0.270588E+11 | 0.113194E+11 | 0.157394E+11 | 0.00 | 0.00 |
Minimum of Months | 0.702331E+09 | 0.284139E+09 | 0.109654E+10 | 0.447180E+09 | 0.581672E+09 | 0.00 | 0.00 |
Maximum of Months | 0.476210E+10 | 0.265843E+10 | 0.336621E+10 | 0.151782E+10 | 0.192803E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.412064E+10 | 0.382847E+10 | 0.414343E+10 | 0.271314E+10 | 0.143029E+10 | 0.00 | 0.00 |
February | 0.499213E+10 | 0.350469E+10 | 0.493617E+10 | 0.326734E+10 | 0.166883E+10 | 0.00 | 0.00 |
March | 0.527584E+10 | 0.286305E+10 | 0.493050E+10 | 0.273651E+10 | 0.219399E+10 | 0.00 | 0.00 |
April | 0.409609E+10 | 0.210163E+10 | 0.370248E+10 | 0.146407E+10 | 0.223842E+10 | 0.00 | 0.00 |
May | 0.392316E+10 | 0.142685E+10 | 0.335284E+10 | 0.699346E+09 | 0.265349E+10 | 0.00 | 0.00 |
June | 0.411057E+10 | 0.769018E+09 | 0.304504E+10 | 0.465464E+09 | 0.257958E+10 | 0.00 | 0.00 |
July | 0.494683E+10 | 0.433822E+09 | 0.329820E+10 | 0.572895E+09 | 0.272531E+10 | 0.00 | 0.00 |
August | 0.666495E+10 | 0.603459E+09 | 0.440438E+10 | 0.163365E+10 | 0.277073E+10 | 0.00 | 0.00 |
September | 0.620137E+10 | 0.110970E+10 | 0.462468E+10 | 0.239207E+10 | 0.223261E+10 | 0.00 | 0.00 |
October | 0.818865E+10 | 0.201543E+10 | 0.654660E+10 | 0.410518E+10 | 0.244142E+10 | 0.00 | 0.00 |
November | 0.474624E+10 | 0.270523E+10 | 0.439307E+10 | 0.263825E+10 | 0.175482E+10 | 0.00 | 0.00 |
December | 0.466436E+10 | 0.349450E+10 | 0.449086E+10 | 0.318821E+10 | 0.130265E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.619308E+11 | 0.248559E+11 | 0.518683E+11 | 0.258761E+11 | 0.259921E+11 | 0.00 | 0.00 |
Minimum of Months | 0.392316E+10 | 0.433822E+09 | 0.304504E+10 | 0.465464E+09 | 0.130265E+10 | 0.00 | 0.00 |
Maximum of Months | 0.818865E+10 | 0.382847E+10 | 0.654660E+10 | 0.410518E+10 | 0.277073E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.695593E+09 | 0.272071E+10 | 0.110114E+10 | 0.451030E+09 | 0.650111E+09 | 0.00 | 0.00 |
February | 0.102650E+10 | 0.252399E+10 | 0.146665E+10 | 0.644157E+09 | 0.822493E+09 | 0.00 | 0.00 |
March | 0.219847E+10 | 0.188340E+10 | 0.239773E+10 | 0.110696E+10 | 0.129076E+10 | 0.00 | 0.00 |
April | 0.263310E+10 | 0.135833E+10 | 0.253607E+10 | 0.108512E+10 | 0.145095E+10 | 0.00 | 0.00 |
May | 0.357789E+10 | 0.934037E+09 | 0.305274E+10 | 0.115931E+10 | 0.189343E+10 | 0.00 | 0.00 |
June | 0.427020E+10 | 0.518398E+09 | 0.323335E+10 | 0.130410E+10 | 0.192925E+10 | 0.00 | 0.00 |
July | 0.444434E+10 | 0.303176E+09 | 0.312915E+10 | 0.117834E+10 | 0.195081E+10 | 0.00 | 0.00 |
August | 0.492491E+10 | 0.411309E+09 | 0.346169E+10 | 0.160253E+10 | 0.185916E+10 | 0.00 | 0.00 |
September | 0.302222E+10 | 0.730125E+09 | 0.237825E+10 | 0.103929E+10 | 0.133896E+10 | 0.00 | 0.00 |
October | 0.278909E+10 | 0.133303E+10 | 0.243645E+10 | 0.118478E+10 | 0.125167E+10 | 0.00 | 0.00 |
November | 0.785432E+09 | 0.185318E+10 | 0.110724E+10 | 0.320000E+09 | 0.787241E+09 | 0.00 | 0.00 |
December | 0.664784E+09 | 0.249684E+10 | 0.101770E+10 | 0.440359E+09 | 0.577337E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.310325E+11 | 0.170665E+11 | 0.273181E+11 | 0.115160E+11 | 0.158022E+11 | 0.00 | 0.00 |
Minimum of Months | 0.664784E+09 | 0.303176E+09 | 0.101770E+10 | 0.320000E+09 | 0.577337E+09 | 0.00 | 0.00 |
Maximum of Months | 0.492491E+10 | 0.272071E+10 | 0.346169E+10 | 0.160253E+10 | 0.195081E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 53942297.29 | 0.447469E+10 | 0.800948E+09 | 0.00 | 0.800948E+09 | 0.00 | 0.00 |
February | 0.100241E+09 | 0.417031E+10 | 0.989992E+09 | 0.00 | 0.989992E+09 | 0.00 | 0.00 |
March | 0.601961E+09 | 0.302271E+10 | 0.151996E+10 | 0.00 | 0.151996E+10 | 0.00 | 0.00 |
April | 0.120052E+10 | 0.206053E+10 | 0.176679E+10 | 5025296.98 | 0.176176E+10 | 0.00 | 0.00 |
May | 0.239117E+10 | 0.129472E+10 | 0.242210E+10 | 80705760.09 | 0.234139E+10 | 0.00 | 0.00 |
June | 0.315955E+10 | 0.693104E+09 | 0.248575E+10 | 0.133570E+09 | 0.235218E+10 | 0.00 | 0.00 |
July | 0.361567E+10 | 0.395874E+09 | 0.248231E+10 | 89768657.61 | 0.239254E+10 | 0.00 | 0.00 |
August | 0.314396E+10 | 0.565898E+09 | 0.219921E+10 | 26173684.10 | 0.217304E+10 | 0.00 | 0.00 |
September | 0.172734E+10 | 0.114877E+10 | 0.160436E+10 | 300431.40 | 0.160406E+10 | 0.00 | 0.00 |
October | 0.103929E+10 | 0.220713E+10 | 0.143474E+10 | 0.00 | 0.143474E+10 | 0.00 | 0.00 |
November | 0.257361E+09 | 0.321562E+10 | 0.973870E+09 | 0.00 | 0.973870E+09 | 0.00 | 0.00 |
December | 30187679.55 | 0.427317E+10 | 0.698639E+09 | 0.00 | 0.698639E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.173212E+11 | 0.275225E+11 | 0.193787E+11 | 0.335544E+09 | 0.190431E+11 | 0.00 | 0.00 |
Minimum of Months | 30187679.55 | 0.395874E+09 | 0.698639E+09 | 0.00 | 0.698639E+09 | 0.00 | 0.00 |
Maximum of Months | 0.361567E+10 | 0.447469E+10 | 0.248575E+10 | 0.133570E+09 | 0.239254E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.700420E+09 | 0.278827E+10 | 0.111538E+10 | 0.447176E+09 | 0.668206E+09 | 0.00 | 0.00 |
February | 0.111517E+10 | 0.252850E+10 | 0.156232E+10 | 0.728822E+09 | 0.833502E+09 | 0.00 | 0.00 |
March | 0.198084E+10 | 0.197614E+10 | 0.220658E+10 | 0.938469E+09 | 0.126811E+10 | 0.00 | 0.00 |
April | 0.265543E+10 | 0.137345E+10 | 0.256263E+10 | 0.112250E+10 | 0.144012E+10 | 0.00 | 0.00 |
May | 0.379474E+10 | 0.909293E+09 | 0.321153E+10 | 0.128351E+10 | 0.192802E+10 | 0.00 | 0.00 |
June | 0.381930E+10 | 0.488182E+09 | 0.288040E+10 | 0.104268E+10 | 0.183772E+10 | 0.00 | 0.00 |
July | 0.429094E+10 | 0.283410E+09 | 0.298944E+10 | 0.107881E+10 | 0.191063E+10 | 0.00 | 0.00 |
August | 0.478866E+10 | 0.400505E+09 | 0.336618E+10 | 0.151780E+10 | 0.184838E+10 | 0.00 | 0.00 |
September | 0.304622E+10 | 0.765463E+09 | 0.242953E+10 | 0.109003E+10 | 0.133950E+10 | 0.00 | 0.00 |
October | 0.251861E+10 | 0.146218E+10 | 0.227597E+10 | 0.103154E+10 | 0.124443E+10 | 0.00 | 0.00 |
November | 0.108025E+10 | 0.204110E+10 | 0.136211E+10 | 0.523060E+09 | 0.839045E+09 | 0.00 | 0.00 |
December | 0.740293E+09 | 0.264751E+10 | 0.109653E+10 | 0.514861E+09 | 0.581668E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.305309E+11 | 0.176640E+11 | 0.270586E+11 | 0.113193E+11 | 0.157393E+11 | 0.00 | 0.00 |
Minimum of Months | 0.700420E+09 | 0.283410E+09 | 0.109653E+10 | 0.447176E+09 | 0.581668E+09 | 0.00 | 0.00 |
Maximum of Months | 0.478866E+10 | 0.278827E+10 | 0.336618E+10 | 0.151780E+10 | 0.192802E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.420917E+10 | 0.398934E+10 | 0.414347E+10 | 0.271317E+10 | 0.143030E+10 | 0.00 | 0.00 |
February | 0.508527E+10 | 0.367249E+10 | 0.493622E+10 | 0.326738E+10 | 0.166884E+10 | 0.00 | 0.00 |
March | 0.539816E+10 | 0.297704E+10 | 0.493055E+10 | 0.273654E+10 | 0.219401E+10 | 0.00 | 0.00 |
April | 0.419590E+10 | 0.213914E+10 | 0.370252E+10 | 0.146409E+10 | 0.223843E+10 | 0.00 | 0.00 |
May | 0.406087E+10 | 0.138791E+10 | 0.335286E+10 | 0.699355E+09 | 0.265351E+10 | 0.00 | 0.00 |
June | 0.419875E+10 | 0.748740E+09 | 0.304506E+10 | 0.465469E+09 | 0.257959E+10 | 0.00 | 0.00 |
July | 0.501367E+10 | 0.422075E+09 | 0.329823E+10 | 0.572901E+09 | 0.272533E+10 | 0.00 | 0.00 |
August | 0.670392E+10 | 0.635354E+09 | 0.440442E+10 | 0.163367E+10 | 0.277075E+10 | 0.00 | 0.00 |
September | 0.622038E+10 | 0.122217E+10 | 0.462473E+10 | 0.239210E+10 | 0.223263E+10 | 0.00 | 0.00 |
October | 0.819160E+10 | 0.229722E+10 | 0.654667E+10 | 0.410523E+10 | 0.244144E+10 | 0.00 | 0.00 |
November | 0.474504E+10 | 0.302920E+10 | 0.439312E+10 | 0.263828E+10 | 0.175484E+10 | 0.00 | 0.00 |
December | 0.469220E+10 | 0.379927E+10 | 0.449091E+10 | 0.318824E+10 | 0.130266E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.627149E+11 | 0.263199E+11 | 0.518688E+11 | 0.258764E+11 | 0.259923E+11 | 0.00 | 0.00 |
Minimum of Months | 0.406087E+10 | 0.422075E+09 | 0.304506E+10 | 0.465469E+09 | 0.130266E+10 | 0.00 | 0.00 |
Maximum of Months | 0.819160E+10 | 0.398934E+10 | 0.654667E+10 | 0.410523E+10 | 0.277075E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.700974E+09 | 0.284929E+10 | 0.110113E+10 | 0.451026E+09 | 0.650107E+09 | 0.00 | 0.00 |
February | 0.103910E+10 | 0.264032E+10 | 0.146664E+10 | 0.644151E+09 | 0.822488E+09 | 0.00 | 0.00 |
March | 0.222582E+10 | 0.198238E+10 | 0.239771E+10 | 0.110695E+10 | 0.129076E+10 | 0.00 | 0.00 |
April | 0.266355E+10 | 0.141973E+10 | 0.253605E+10 | 0.108511E+10 | 0.145094E+10 | 0.00 | 0.00 |
May | 0.362760E+10 | 0.946469E+09 | 0.305272E+10 | 0.115930E+10 | 0.189342E+10 | 0.00 | 0.00 |
June | 0.431513E+10 | 0.526174E+09 | 0.323333E+10 | 0.130409E+10 | 0.192924E+10 | 0.00 | 0.00 |
July | 0.448594E+10 | 0.306768E+09 | 0.312913E+10 | 0.117833E+10 | 0.195080E+10 | 0.00 | 0.00 |
August | 0.494897E+10 | 0.434911E+09 | 0.346166E+10 | 0.160251E+10 | 0.185915E+10 | 0.00 | 0.00 |
September | 0.301754E+10 | 0.802340E+09 | 0.237823E+10 | 0.103928E+10 | 0.133895E+10 | 0.00 | 0.00 |
October | 0.275321E+10 | 0.151495E+10 | 0.243643E+10 | 0.118477E+10 | 0.125166E+10 | 0.00 | 0.00 |
November | 0.749145E+09 | 0.208705E+10 | 0.110723E+10 | 0.319996E+09 | 0.787236E+09 | 0.00 | 0.00 |
December | 0.654859E+09 | 0.272132E+10 | 0.101769E+10 | 0.440355E+09 | 0.577333E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.311818E+11 | 0.182317E+11 | 0.273179E+11 | 0.115159E+11 | 0.158021E+11 | 0.00 | 0.00 |
Minimum of Months | 0.654859E+09 | 0.306768E+09 | 0.101769E+10 | 0.319996E+09 | 0.577333E+09 | 0.00 | 0.00 |
Maximum of Months | 0.494897E+10 | 0.284929E+10 | 0.346166E+10 | 0.160251E+10 | 0.195080E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 49815166.95 | 0.448904E+10 | 0.800952E+09 | 0.00 | 0.800952E+09 | 0.00 | 0.00 |
February | 90462746.22 | 0.423048E+10 | 0.989997E+09 | 0.00 | 0.989997E+09 | 0.00 | 0.00 |
March | 0.547089E+09 | 0.313430E+10 | 0.151997E+10 | 0.00 | 0.151997E+10 | 0.00 | 0.00 |
April | 0.111190E+10 | 0.218134E+10 | 0.176680E+10 | 5025323.02 | 0.176177E+10 | 0.00 | 0.00 |
May | 0.226417E+10 | 0.140071E+10 | 0.242211E+10 | 80706178.30 | 0.234141E+10 | 0.00 | 0.00 |
June | 0.309118E+10 | 0.745075E+09 | 0.248576E+10 | 0.133570E+09 | 0.235219E+10 | 0.00 | 0.00 |
July | 0.356414E+10 | 0.431974E+09 | 0.248232E+10 | 89769122.78 | 0.239255E+10 | 0.00 | 0.00 |
August | 0.311767E+10 | 0.588239E+09 | 0.219922E+10 | 26173819.73 | 0.217305E+10 | 0.00 | 0.00 |
September | 0.171625E+10 | 0.114667E+10 | 0.160437E+10 | 300432.95 | 0.160407E+10 | 0.00 | 0.00 |
October | 0.103933E+10 | 0.216425E+10 | 0.143475E+10 | 0.00 | 0.143475E+10 | 0.00 | 0.00 |
November | 0.262651E+09 | 0.312093E+10 | 0.973875E+09 | 0.00 | 0.973875E+09 | 0.00 | 0.00 |
December | 30494874.71 | 0.421734E+10 | 0.698643E+09 | 0.00 | 0.698643E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.168852E+11 | 0.278504E+11 | 0.193788E+11 | 0.335545E+09 | 0.190432E+11 | 0.00 | 0.00 |
Minimum of Months | 30494874.71 | 0.431974E+09 | 0.698643E+09 | 0.00 | 0.698643E+09 | 0.00 | 0.00 |
Maximum of Months | 0.356414E+10 | 0.448904E+10 | 0.248576E+10 | 0.133570E+09 | 0.239255E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.688858E+09 | 0.277943E+10 | 0.111539E+10 | 0.447180E+09 | 0.668210E+09 | 0.00 | 0.00 |
February | 0.109505E+10 | 0.253610E+10 | 0.156234E+10 | 0.728829E+09 | 0.833507E+09 | 0.00 | 0.00 |
March | 0.193571E+10 | 0.200908E+10 | 0.220660E+10 | 0.938479E+09 | 0.126812E+10 | 0.00 | 0.00 |
April | 0.260423E+10 | 0.140358E+10 | 0.256265E+10 | 0.112252E+10 | 0.144013E+10 | 0.00 | 0.00 |
May | 0.372977E+10 | 0.945317E+09 | 0.321155E+10 | 0.128353E+10 | 0.192803E+10 | 0.00 | 0.00 |
June | 0.378071E+10 | 0.504599E+09 | 0.288042E+10 | 0.104269E+10 | 0.183773E+10 | 0.00 | 0.00 |
July | 0.426412E+10 | 0.290106E+09 | 0.298946E+10 | 0.107882E+10 | 0.191064E+10 | 0.00 | 0.00 |
August | 0.477395E+10 | 0.392329E+09 | 0.336621E+10 | 0.151782E+10 | 0.184839E+10 | 0.00 | 0.00 |
September | 0.304023E+10 | 0.735856E+09 | 0.242955E+10 | 0.109004E+10 | 0.133951E+10 | 0.00 | 0.00 |
October | 0.252260E+10 | 0.138934E+10 | 0.227598E+10 | 0.103155E+10 | 0.124443E+10 | 0.00 | 0.00 |
November | 0.109160E+10 | 0.194679E+10 | 0.136212E+10 | 0.523065E+09 | 0.839051E+09 | 0.00 | 0.00 |
December | 0.738880E+09 | 0.258816E+10 | 0.109654E+10 | 0.514866E+09 | 0.581672E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.302657E+11 | 0.175207E+11 | 0.270588E+11 | 0.113194E+11 | 0.157394E+11 | 0.00 | 0.00 |
Minimum of Months | 0.688858E+09 | 0.290106E+09 | 0.109654E+10 | 0.447180E+09 | 0.581672E+09 | 0.00 | 0.00 |
Maximum of Months | 0.477395E+10 | 0.277943E+10 | 0.336621E+10 | 0.151782E+10 | 0.192803E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.409185E+10 | 0.401930E+10 | 0.414343E+10 | 0.271314E+10 | 0.143029E+10 | 0.00 | 0.00 |
February | 0.495049E+10 | 0.369693E+10 | 0.493617E+10 | 0.326734E+10 | 0.166883E+10 | 0.00 | 0.00 |
March | 0.524316E+10 | 0.305690E+10 | 0.493050E+10 | 0.273651E+10 | 0.219399E+10 | 0.00 | 0.00 |
April | 0.406541E+10 | 0.224916E+10 | 0.370248E+10 | 0.146407E+10 | 0.223842E+10 | 0.00 | 0.00 |
May | 0.390663E+10 | 0.150734E+10 | 0.335284E+10 | 0.699346E+09 | 0.265349E+10 | 0.00 | 0.00 |
June | 0.412109E+10 | 0.798844E+09 | 0.304504E+10 | 0.465464E+09 | 0.257958E+10 | 0.00 | 0.00 |
July | 0.496873E+10 | 0.445084E+09 | 0.329820E+10 | 0.572895E+09 | 0.272531E+10 | 0.00 | 0.00 |
August | 0.668302E+10 | 0.623552E+09 | 0.440438E+10 | 0.163365E+10 | 0.277073E+10 | 0.00 | 0.00 |
September | 0.619700E+10 | 0.117401E+10 | 0.462468E+10 | 0.239207E+10 | 0.223261E+10 | 0.00 | 0.00 |
October | 0.815853E+10 | 0.216374E+10 | 0.654660E+10 | 0.410518E+10 | 0.244142E+10 | 0.00 | 0.00 |
November | 0.468481E+10 | 0.292880E+10 | 0.439307E+10 | 0.263825E+10 | 0.175482E+10 | 0.00 | 0.00 |
December | 0.461098E+10 | 0.373958E+10 | 0.449086E+10 | 0.318821E+10 | 0.130265E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.616817E+11 | 0.264032E+11 | 0.518683E+11 | 0.258761E+11 | 0.259921E+11 | 0.00 | 0.00 |
Minimum of Months | 0.390663E+10 | 0.445084E+09 | 0.304504E+10 | 0.465464E+09 | 0.130265E+10 | 0.00 | 0.00 |
Maximum of Months | 0.815853E+10 | 0.401930E+10 | 0.654660E+10 | 0.410518E+10 | 0.277073E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.686621E+09 | 0.284530E+10 | 0.110114E+10 | 0.451030E+09 | 0.650111E+09 | 0.00 | 0.00 |
February | 0.101409E+10 | 0.265279E+10 | 0.146665E+10 | 0.644157E+09 | 0.822493E+09 | 0.00 | 0.00 |
March | 0.217795E+10 | 0.200986E+10 | 0.239773E+10 | 0.110696E+10 | 0.129076E+10 | 0.00 | 0.00 |
April | 0.261097E+10 | 0.145344E+10 | 0.253607E+10 | 0.108512E+10 | 0.145095E+10 | 0.00 | 0.00 |
May | 0.356415E+10 | 0.985919E+09 | 0.305274E+10 | 0.115931E+10 | 0.189343E+10 | 0.00 | 0.00 |
June | 0.427805E+10 | 0.538113E+09 | 0.323335E+10 | 0.130410E+10 | 0.192925E+10 | 0.00 | 0.00 |
July | 0.445941E+10 | 0.311077E+09 | 0.312915E+10 | 0.117834E+10 | 0.195081E+10 | 0.00 | 0.00 |
August | 0.493551E+10 | 0.424157E+09 | 0.346169E+10 | 0.160253E+10 | 0.185916E+10 | 0.00 | 0.00 |
September | 0.301392E+10 | 0.774946E+09 | 0.237825E+10 | 0.103929E+10 | 0.133896E+10 | 0.00 | 0.00 |
October | 0.275904E+10 | 0.143991E+10 | 0.243645E+10 | 0.118478E+10 | 0.125167E+10 | 0.00 | 0.00 |
November | 0.753870E+09 | 0.200834E+10 | 0.110724E+10 | 0.320000E+09 | 0.787241E+09 | 0.00 | 0.00 |
December | 0.649134E+09 | 0.266850E+10 | 0.101770E+10 | 0.440359E+09 | 0.577337E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.309027E+11 | 0.181124E+11 | 0.273181E+11 | 0.115160E+11 | 0.158022E+11 | 0.00 | 0.00 |
Minimum of Months | 0.649134E+09 | 0.311077E+09 | 0.101770E+10 | 0.320000E+09 | 0.577337E+09 | 0.00 | 0.00 |
Maximum of Months | 0.493551E+10 | 0.284530E+10 | 0.346169E+10 | 0.160253E+10 | 0.195081E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.536784E+10 | -0.462765E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -740192314.5 | 58.98 | 0.00 | 0.00 |
February | 0.490375E+10 | -0.424798E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -655766676.3 | 58.98 | 0.00 | 0.00 |
March | 0.562568E+10 | -0.491458E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -711105080.9 | 58.98 | 0.00 | 0.00 |
April | 0.487419E+10 | -0.419567E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -678520181.0 | 58.98 | 0.00 | 0.00 |
May | 0.488278E+10 | -0.419029E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692488191.5 | 58.98 | 0.00 | 0.00 |
June | 0.452704E+10 | -0.385997E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667066468.3 | 58.99 | 0.00 | 0.00 |
July | 0.413129E+10 | -0.344445E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -686843865.4 | 58.98 | 0.00 | 0.00 |
August | 0.444445E+10 | -0.375689E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687562555.3 | 58.98 | 0.00 | 0.00 |
September | 0.415553E+10 | -0.348954E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -665994846.2 | 58.98 | 0.00 | 0.00 |
October | 0.453324E+10 | -0.384251E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690725338.2 | 58.98 | 0.00 | 0.00 |
November | 0.475791E+10 | -0.407521E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -682696696.9 | 58.98 | 0.00 | 0.00 |
December | 0.502807E+10 | -0.430904E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -719024764.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.572318E+11 | -0.489538E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.827799E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.413129E+10 | -0.491458E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -740192314.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.562568E+10 | -0.344445E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -655766676.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.64 | 0.62 | 01-JAN-07:49 | 5719.27 | 34.81 | 184.50 | 232.00 | 2991.37 | 32.96 | 174.67 | 189.17 |
February | 216.00 | 0.63 | 0.62 | 01-FEB-07:40 | 8255.58 | 36.30 | 203.17 | 252.67 | 1832.08 | 26.07 | 150.50 | 226.83 |
March | 275.00 | 0.64 | 0.62 | 01-MAR-06:00 | 2839.50 | 20.43 | 45.17 | 314.17 | 1359.02 | 21.06 | 144.50 | 267.50 |
April | 261.17 | 0.63 | 0.62 | 01-APR-06:19 | 1774.32 | 17.69 | 0.00 | 331.17 | 1046.77 | 20.48 | 101.83 | 285.17 |
May | 372.00 | 0.64 | 0.62 | 01-MAY-05:40 | 1546.71 | 17.59 | 0.00 | 383.83 | 866.91 | 20.31 | 151.00 | 331.50 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-05:19 | 1470.79 | 17.55 | 0.00 | 372.83 | 836.00 | 20.34 | 135.67 | 326.67 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-05:30 | 1625.91 | 17.82 | 0.00 | 380.83 | 904.24 | 20.60 | 168.67 | 331.33 |
August | 389.17 | 0.64 | 0.62 | 01-AUG-05:49 | 1803.41 | 17.82 | 0.00 | 363.67 | 1043.81 | 20.58 | 181.83 | 328.50 |
September | 285.33 | 0.63 | 0.62 | 01-SEP-06:10 | 3332.57 | 20.14 | 29.50 | 316.33 | 1250.72 | 20.81 | 140.67 | 279.17 |
October | 305.50 | 0.63 | 0.62 | 01-OCT-14:39 | 9044.28 | 35.39 | 281.00 | 302.50 | 1758.24 | 22.99 | 235.83 | 281.50 |
November | 240.83 | 0.63 | 0.62 | 01-NOV-06:49 | 5705.62 | 35.04 | 227.17 | 253.17 | 1980.35 | 29.04 | 213.67 | 227.83 |
December | 211.17 | 0.64 | 0.62 | 01-DEC-07:40 | 5291.30 | 33.80 | 178.83 | 233.67 | 4837.57 | 38.79 | 207.83 | 206.67 |
Annual Sum or Average | 3472.67 | 0.63 | 3675.05 | 23.99 | 1149.33 | 3736.83 | 1550.72 | 23.54 | 2006.67 | 3281.83 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 1470.79 | 17.55 | 0.00 | 232.00 | 836.00 | 20.31 | 101.83 | 189.17 | |
Maximum of Months | 389.17 | 0.64 | 0.62 | 9044.28 | 36.30 | 281.00 | 383.83 | 4837.57 | 38.79 | 235.83 | 331.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.62 | 01-JAN-07:49 | 1724.32 | 20.20 | 60.83 | 209.17 | 980.12 | 23.01 | 72.00 | 146.17 |
February | 216.00 | 0.64 | 0.62 | 01-FEB-07:40 | 2471.33 | 22.95 | 80.67 | 236.17 | 1426.28 | 23.98 | 69.50 | 189.83 |
March | 275.00 | 0.65 | 0.62 | 01-MAR-06:49 | 2460.06 | 18.92 | 58.67 | 305.83 | 1423.12 | 21.91 | 54.67 | 237.17 |
April | 261.17 | 0.63 | 0.62 | 01-APR-05:00 | 3365.83 | 21.21 | 80.67 | 332.17 | 1343.86 | 22.28 | 50.17 | 285.00 |
May | 372.00 | 0.64 | 0.62 | 01-MAY-05:40 | 2773.47 | 20.09 | 98.83 | 387.67 | 1498.06 | 21.78 | 72.33 | 336.67 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-04:00 | 2466.97 | 19.34 | 80.50 | 378.83 | 1365.52 | 21.46 | 60.83 | 340.67 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-04:49 | 2546.80 | 19.95 | 89.00 | 387.33 | 1374.85 | 21.85 | 64.50 | 343.50 |
August | 389.17 | 0.64 | 0.62 | 01-AUG-05:30 | 3391.46 | 20.79 | 111.67 | 365.17 | 1405.01 | 22.09 | 68.50 | 335.00 |
September | 285.33 | 0.64 | 0.62 | 01-SEP-05:49 | 2954.42 | 20.75 | 79.67 | 312.83 | 1267.40 | 21.22 | 43.83 | 269.33 |
October | 305.50 | 0.64 | 0.62 | 01-OCT-14:39 | 2572.12 | 20.68 | 78.33 | 285.50 | 1388.01 | 23.21 | 91.67 | 250.17 |
November | 240.83 | 0.64 | 0.62 | 01-NOV-06:49 | 1771.83 | 20.76 | 71.67 | 235.00 | 907.77 | 21.86 | 81.83 | 183.83 |
December | 211.17 | 0.66 | 0.62 | 01-DEC-07:40 | 1580.61 | 19.72 | 64.00 | 204.67 | 966.25 | 23.38 | 80.83 | 136.00 |
Annual Sum or Average | 3472.67 | 0.64 | 2583.66 | 20.38 | 954.50 | 3640.33 | 1307.59 | 22.23 | 810.67 | 3053.33 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 1580.61 | 18.92 | 58.67 | 204.67 | 907.77 | 21.22 | 43.83 | 136.00 | |
Maximum of Months | 389.17 | 0.66 | 0.62 | 3391.46 | 22.95 | 111.67 | 387.67 | 1498.06 | 23.98 | 91.67 | 343.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.66 | 0.62 | 01-JAN-08:20 | 538.53 | 14.03 | 0.00 | 188.00 | 328.99 | 17.01 | 0.00 | 88.67 |
February | 216.00 | 0.65 | 0.62 | 01-FEB-08:20 | 580.87 | 14.92 | 0.00 | 216.50 | 376.73 | 18.05 | 0.00 | 134.67 |
March | 275.00 | 0.65 | 0.62 | 01-MAR-07:10 | 772.74 | 15.99 | 0.00 | 300.83 | 480.81 | 18.80 | 0.33 | 211.67 |
April | 261.17 | 0.63 | 0.62 | 01-APR-06:19 | 869.54 | 17.02 | 0.00 | 336.00 | 542.98 | 19.79 | 6.83 | 273.83 |
May | 372.00 | 0.63 | 0.62 | 01-MAY-05:40 | 1128.48 | 17.81 | 1.83 | 397.33 | 648.40 | 20.56 | 99.33 | 344.83 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-04:00 | 1264.33 | 19.60 | 41.00 | 393.83 | 715.29 | 23.05 | 162.00 | 365.17 |
July | 365.17 | 0.62 | 0.62 | 01-JUL-04:00 | 1252.10 | 18.01 | 0.00 | 399.33 | 708.18 | 22.59 | 159.33 | 360.17 |
August | 389.17 | 0.63 | 0.62 | 01-AUG-05:40 | 1027.02 | 17.48 | 0.00 | 373.83 | 618.86 | 20.22 | 54.17 | 339.67 |
September | 285.33 | 0.64 | 0.62 | 01-SEP-05:00 | 796.42 | 16.54 | 0.00 | 310.83 | 502.44 | 19.39 | 0.83 | 247.00 |
October | 305.50 | 0.64 | 0.62 | 01-OCT-14:39 | 720.64 | 16.11 | 0.00 | 281.00 | 465.84 | 19.11 | 0.00 | 220.83 |
November | 240.83 | 0.65 | 0.62 | 01-NOV-07:10 | 602.02 | 14.74 | 0.00 | 220.83 | 359.86 | 17.64 | 0.00 | 124.83 |
December | 211.17 | 0.67 | 0.62 | 01-DEC-08:20 | 433.20 | 12.94 | 0.00 | 171.17 | 273.34 | 16.12 | 0.00 | 55.17 |
Annual Sum or Average | 3472.67 | 0.64 | 886.32 | 16.61 | 42.83 | 3589.50 | 530.84 | 19.74 | 482.83 | 2766.50 | ||
Minimum of Months | 199.50 | 0.62 | 0.62 | 433.20 | 12.94 | 0.00 | 171.17 | 273.34 | 16.12 | 0.00 | 55.17 | |
Maximum of Months | 389.17 | 0.67 | 0.62 | 1264.33 | 19.60 | 41.00 | 399.33 | 715.29 | 23.05 | 162.00 | 365.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.62 | 01-JAN-08:20 | 1643.95 | 19.84 | 57.17 | 213.83 | 969.79 | 23.12 | 64.83 | 146.83 |
February | 216.00 | 0.64 | 0.62 | 01-FEB-08:30 | 1910.38 | 20.24 | 57.00 | 235.17 | 995.46 | 21.55 | 40.33 | 185.67 |
March | 275.00 | 0.64 | 0.62 | 01-MAR-07:10 | 2634.34 | 19.90 | 70.83 | 308.83 | 1567.61 | 23.90 | 75.83 | 247.67 |
April | 261.17 | 0.63 | 0.62 | 01-APR-06:49 | 3174.74 | 20.87 | 76.83 | 330.83 | 1267.75 | 20.83 | 37.00 | 285.33 |
May | 372.00 | 0.63 | 0.62 | 01-MAY-05:49 | 2937.14 | 18.07 | 69.00 | 387.67 | 1310.93 | 18.28 | 0.00 | 339.67 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-05:30 | 2877.16 | 14.59 | 1.83 | 383.33 | 1549.59 | 18.47 | 0.00 | 333.00 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-05:30 | 2700.41 | 17.34 | 49.00 | 387.33 | 1441.86 | 18.59 | 0.00 | 340.17 |
August | 389.17 | 0.64 | 0.62 | 01-AUG-05:00 | 3458.70 | 19.20 | 86.33 | 364.33 | 1505.67 | 18.74 | 8.50 | 334.00 |
September | 285.33 | 0.63 | 0.62 | 01-SEP-06:19 | 2817.56 | 21.33 | 85.17 | 313.00 | 1462.58 | 22.49 | 61.17 | 270.83 |
October | 305.50 | 0.63 | 0.62 | 01-OCT-14:39 | 3023.30 | 23.08 | 109.33 | 296.50 | 1263.05 | 22.79 | 68.83 | 264.33 |
November | 240.83 | 0.64 | 0.62 | 01-NOV-07:19 | 1445.98 | 19.91 | 68.50 | 238.17 | 788.21 | 22.53 | 70.67 | 183.33 |
December | 211.17 | 0.66 | 0.62 | 01-DEC-08:20 | 1358.35 | 20.01 | 67.50 | 206.83 | 737.35 | 20.97 | 54.83 | 139.50 |
Annual Sum or Average | 3472.67 | 0.64 | 2618.69 | 19.31 | 798.50 | 3665.83 | 1285.68 | 20.70 | 482.00 | 3070.33 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 1358.35 | 14.59 | 1.83 | 206.83 | 737.35 | 18.28 | 0.00 | 139.50 | |
Maximum of Months | 389.17 | 0.66 | 0.62 | 3458.70 | 23.08 | 109.33 | 387.67 | 1567.61 | 23.90 | 75.83 | 340.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.64 | 0.62 | 01-JAN-07:49 | 5485.31 | 32.27 | 169.00 | 227.33 | 2874.91 | 31.86 | 144.00 | 186.83 |
February | 216.00 | 0.63 | 0.62 | 01-FEB-07:40 | 8084.23 | 35.95 | 202.83 | 251.00 | 1721.40 | 24.52 | 80.00 | 226.33 |
March | 275.00 | 0.64 | 0.62 | 01-MAR-06:00 | 2722.90 | 17.14 | 44.83 | 313.67 | 1257.97 | 18.55 | 18.50 | 259.00 |
April | 261.17 | 0.64 | 0.62 | 01-APR-06:19 | 1674.98 | 14.12 | 0.00 | 329.17 | 978.36 | 18.13 | 0.00 | 281.00 |
May | 372.00 | 0.64 | 0.62 | 01-MAY-05:40 | 1471.89 | 14.09 | 0.00 | 381.17 | 820.86 | 17.95 | 0.00 | 326.67 |
June | 351.83 | 0.64 | 0.62 | 01-JUN-05:19 | 1401.99 | 14.07 | 0.00 | 370.17 | 794.81 | 18.01 | 0.00 | 323.17 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-05:30 | 1548.73 | 14.28 | 0.00 | 377.50 | 857.66 | 18.20 | 0.00 | 326.50 |
August | 389.17 | 0.64 | 0.62 | 01-AUG-05:49 | 1707.59 | 14.42 | 0.00 | 362.17 | 980.59 | 18.33 | 1.83 | 323.17 |
September | 285.33 | 0.64 | 0.62 | 01-SEP-06:10 | 3205.04 | 16.84 | 29.50 | 313.33 | 1159.67 | 18.32 | 1.50 | 275.50 |
October | 305.50 | 0.63 | 0.62 | 01-OCT-14:39 | 8852.70 | 34.74 | 278.33 | 301.00 | 1628.41 | 20.27 | 24.00 | 278.67 |
November | 240.83 | 0.63 | 0.62 | 01-NOV-06:00 | 5528.29 | 33.43 | 217.00 | 249.50 | 1868.30 | 27.01 | 119.67 | 225.33 |
December | 211.17 | 0.64 | 0.62 | 01-DEC-07:40 | 5133.04 | 32.98 | 178.83 | 231.67 | 4693.38 | 37.35 | 198.50 | 200.33 |
Annual Sum or Average | 3472.67 | 0.64 | 3551.16 | 21.32 | 1120.33 | 3707.67 | 1467.47 | 21.34 | 588.00 | 3232.50 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 1401.99 | 14.07 | 0.00 | 227.33 | 794.81 | 17.95 | 0.00 | 186.83 | |
Maximum of Months | 389.17 | 0.64 | 0.62 | 8852.70 | 35.95 | 278.33 | 381.17 | 4693.38 | 37.35 | 198.50 | 326.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.62 | 01-JAN-07:49 | 1662.75 | 19.69 | 60.33 | 205.67 | 940.58 | 22.78 | 66.00 | 141.67 |
February | 216.00 | 0.64 | 0.62 | 01-FEB-07:40 | 2242.81 | 20.11 | 61.33 | 233.00 | 1376.98 | 23.77 | 60.50 | 184.33 |
March | 275.00 | 0.65 | 0.62 | 01-MAR-06:49 | 2370.95 | 18.40 | 57.50 | 303.00 | 1366.53 | 21.71 | 52.00 | 233.17 |
April | 261.17 | 0.63 | 0.62 | 01-APR-05:00 | 3279.92 | 20.81 | 80.67 | 329.17 | 1278.83 | 22.10 | 50.17 | 279.67 |
May | 372.00 | 0.64 | 0.62 | 01-MAY-05:40 | 2591.49 | 18.18 | 75.00 | 385.83 | 1435.43 | 21.61 | 72.33 | 331.17 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-04:00 | 2386.33 | 18.93 | 80.50 | 375.83 | 1309.60 | 21.28 | 60.83 | 337.50 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-04:49 | 2458.96 | 19.56 | 88.83 | 384.67 | 1316.10 | 21.68 | 64.50 | 339.50 |
August | 389.17 | 0.64 | 0.62 | 01-AUG-05:40 | 3300.83 | 20.40 | 111.67 | 362.67 | 1338.80 | 21.92 | 68.50 | 331.17 |
September | 285.33 | 0.64 | 0.62 | 01-SEP-05:49 | 2873.84 | 20.33 | 79.67 | 310.83 | 1205.80 | 21.02 | 41.50 | 265.17 |
October | 305.50 | 0.64 | 0.62 | 01-OCT-14:39 | 2491.59 | 20.25 | 78.33 | 282.83 | 1328.82 | 23.00 | 75.67 | 244.83 |
November | 240.83 | 0.64 | 0.62 | 01-NOV-06:49 | 1711.09 | 20.33 | 71.67 | 232.33 | 864.08 | 21.62 | 71.83 | 179.33 |
December | 211.17 | 0.66 | 0.62 | 01-DEC-07:40 | 1533.49 | 19.27 | 64.00 | 201.83 | 931.16 | 23.16 | 76.67 | 130.50 |
Annual Sum or Average | 3472.67 | 0.64 | 2484.55 | 19.65 | 909.50 | 3607.67 | 1251.47 | 22.04 | 760.50 | 2998.00 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 1533.49 | 18.18 | 57.50 | 201.83 | 864.08 | 21.02 | 41.50 | 130.50 | |
Maximum of Months | 389.17 | 0.66 | 0.62 | 3300.83 | 20.81 | 111.67 | 385.83 | 1435.43 | 23.77 | 76.67 | 339.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.66 | 0.62 | 01-JAN-08:20 | 513.96 | 10.56 | 0.00 | 179.83 | 315.99 | 14.64 | 0.00 | 80.00 |
February | 216.00 | 0.65 | 0.62 | 01-FEB-08:30 | 554.83 | 11.60 | 0.00 | 211.83 | 363.26 | 15.87 | 0.00 | 126.00 |
March | 275.00 | 0.65 | 0.62 | 01-MAR-07:10 | 739.75 | 12.87 | 0.00 | 298.00 | 463.68 | 16.81 | 0.00 | 204.33 |
April | 261.17 | 0.63 | 0.62 | 01-APR-06:19 | 833.17 | 13.92 | 0.00 | 334.33 | 524.14 | 17.93 | 0.00 | 265.83 |
May | 372.00 | 0.63 | 0.62 | 01-MAY-05:40 | 1080.74 | 14.45 | 1.67 | 395.33 | 622.69 | 18.43 | 3.33 | 337.50 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-04:00 | 1212.24 | 16.62 | 40.67 | 392.33 | 686.64 | 21.23 | 50.17 | 362.00 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-04:00 | 1199.79 | 14.59 | 0.00 | 397.17 | 679.53 | 20.70 | 42.50 | 356.00 |
August | 389.17 | 0.63 | 0.62 | 01-AUG-05:40 | 983.89 | 14.43 | 0.00 | 372.67 | 596.17 | 18.37 | 0.00 | 334.83 |
September | 285.33 | 0.64 | 0.62 | 01-SEP-06:10 | 762.56 | 13.48 | 0.00 | 307.00 | 484.92 | 17.50 | 0.00 | 237.17 |
October | 305.50 | 0.64 | 0.62 | 01-OCT-14:39 | 687.79 | 13.03 | 0.00 | 277.67 | 448.76 | 17.13 | 0.00 | 213.83 |
November | 240.83 | 0.65 | 0.62 | 01-NOV-07:10 | 575.08 | 11.16 | 0.00 | 216.67 | 345.55 | 15.22 | 0.00 | 115.50 |
December | 211.17 | 0.68 | 0.62 | 01-DEC-08:20 | 412.92 | 9.39 | 0.00 | 161.33 | 262.67 | 13.65 | 0.00 | 47.67 |
Annual Sum or Average | 3472.67 | 0.64 | 848.44 | 13.38 | 42.33 | 3544.17 | 510.68 | 17.70 | 96.00 | 2680.67 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 412.92 | 9.39 | 0.00 | 161.33 | 262.67 | 13.65 | 0.00 | 47.67 | |
Maximum of Months | 389.17 | 0.68 | 0.62 | 1212.24 | 16.62 | 40.67 | 397.17 | 686.64 | 21.23 | 50.17 | 362.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.62 | 01-JAN-08:30 | 1592.00 | 19.50 | 57.17 | 210.00 | 932.20 | 23.02 | 64.33 | 143.33 |
February | 216.00 | 0.64 | 0.62 | 01-FEB-08:30 | 1845.48 | 19.88 | 57.00 | 232.17 | 947.58 | 21.44 | 39.83 | 179.50 |
March | 275.00 | 0.64 | 0.62 | 01-MAR-07:19 | 2553.37 | 19.54 | 70.83 | 306.50 | 1506.74 | 23.80 | 75.33 | 242.00 |
April | 261.17 | 0.64 | 0.62 | 01-APR-07:10 | 3090.09 | 20.50 | 76.83 | 327.83 | 1203.02 | 20.69 | 37.00 | 280.50 |
May | 372.00 | 0.63 | 0.62 | 01-MAY-05:00 | 2853.70 | 17.66 | 69.00 | 385.00 | 1252.57 | 18.10 | 0.00 | 332.33 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-05:30 | 2778.63 | 14.15 | 1.83 | 380.50 | 1483.59 | 18.30 | 0.00 | 328.00 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-05:40 | 2608.83 | 16.92 | 49.00 | 384.50 | 1379.32 | 18.42 | 0.00 | 335.50 |
August | 389.17 | 0.64 | 0.62 | 01-AUG-05:00 | 3337.95 | 18.59 | 83.33 | 363.33 | 1437.24 | 18.59 | 8.50 | 331.50 |
September | 285.33 | 0.64 | 0.62 | 01-SEP-06:30 | 2640.54 | 19.27 | 67.50 | 310.67 | 1401.29 | 22.36 | 60.67 | 266.33 |
October | 305.50 | 0.63 | 0.62 | 01-OCT-14:39 | 2936.59 | 22.76 | 109.33 | 295.50 | 1200.36 | 22.68 | 66.67 | 260.67 |
November | 240.83 | 0.64 | 0.62 | 01-NOV-07:19 | 1398.08 | 19.56 | 68.50 | 236.00 | 754.13 | 22.42 | 70.00 | 178.00 |
December | 211.17 | 0.66 | 0.62 | 01-DEC-08:20 | 1312.59 | 19.68 | 67.50 | 203.33 | 703.98 | 20.87 | 54.33 | 131.67 |
Annual Sum or Average | 3472.67 | 0.64 | 2528.53 | 18.77 | 777.83 | 3635.33 | 1228.73 | 20.57 | 476.67 | 3009.33 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 1312.59 | 14.15 | 1.83 | 203.33 | 703.98 | 18.10 | 0.00 | 131.67 | |
Maximum of Months | 389.17 | 0.66 | 0.62 | 3337.95 | 22.76 | 109.33 | 385.00 | 1506.74 | 23.80 | 75.33 | 335.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.64 | 0.62 | 01-JAN-07:49 | 5485.35 | 32.27 | 169.00 | 227.33 | 2874.83 | 31.86 | 144.00 | 186.83 |
February | 216.00 | 0.63 | 0.62 | 01-FEB-07:40 | 8084.23 | 35.95 | 202.83 | 251.00 | 1721.31 | 24.52 | 80.00 | 226.33 |
March | 275.00 | 0.64 | 0.62 | 01-MAR-06:00 | 2722.83 | 17.14 | 44.83 | 313.67 | 1257.89 | 18.55 | 18.67 | 259.00 |
April | 261.17 | 0.64 | 0.62 | 01-APR-06:19 | 1674.92 | 14.12 | 0.00 | 329.17 | 978.30 | 18.13 | 0.00 | 281.00 |
May | 372.00 | 0.64 | 0.62 | 01-MAY-05:40 | 1471.83 | 14.09 | 0.00 | 381.17 | 820.80 | 17.95 | 0.00 | 326.67 |
June | 351.83 | 0.64 | 0.62 | 01-JUN-05:19 | 1401.93 | 14.08 | 0.00 | 370.17 | 794.76 | 18.01 | 0.00 | 323.17 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-05:30 | 1548.67 | 14.28 | 0.00 | 377.50 | 857.60 | 18.20 | 0.00 | 326.50 |
August | 389.17 | 0.64 | 0.62 | 01-AUG-05:49 | 1707.52 | 14.42 | 0.00 | 362.17 | 980.53 | 18.33 | 1.83 | 323.17 |
September | 285.33 | 0.64 | 0.62 | 01-SEP-06:10 | 3204.97 | 16.84 | 29.50 | 313.33 | 1159.59 | 18.32 | 1.50 | 275.50 |
October | 305.50 | 0.63 | 0.62 | 01-OCT-14:39 | 8852.67 | 34.74 | 278.33 | 301.00 | 1628.31 | 20.27 | 24.00 | 278.67 |
November | 240.83 | 0.63 | 0.62 | 01-NOV-06:00 | 5528.30 | 33.43 | 217.00 | 249.50 | 1868.20 | 27.01 | 119.67 | 225.33 |
December | 211.17 | 0.64 | 0.62 | 01-DEC-07:40 | 5133.09 | 32.99 | 178.83 | 231.67 | 4693.32 | 37.35 | 198.50 | 200.33 |
Annual Sum or Average | 3472.67 | 0.64 | 3551.12 | 21.33 | 1120.33 | 3707.67 | 1467.40 | 21.34 | 588.17 | 3232.50 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 1401.93 | 14.08 | 0.00 | 227.33 | 794.76 | 17.95 | 0.00 | 186.83 | |
Maximum of Months | 389.17 | 0.64 | 0.62 | 8852.67 | 35.95 | 278.33 | 381.17 | 4693.32 | 37.35 | 198.50 | 326.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.62 | 01-JAN-07:49 | 1662.75 | 19.69 | 60.33 | 205.67 | 940.55 | 22.78 | 66.00 | 141.67 |
February | 216.00 | 0.64 | 0.62 | 01-FEB-07:40 | 2242.82 | 20.11 | 61.33 | 233.00 | 1376.95 | 23.77 | 60.50 | 184.33 |
March | 275.00 | 0.65 | 0.62 | 01-MAR-06:49 | 2370.95 | 18.40 | 57.50 | 303.00 | 1366.48 | 21.71 | 52.00 | 233.17 |
April | 261.17 | 0.63 | 0.62 | 01-APR-05:00 | 3279.91 | 20.81 | 80.67 | 329.17 | 1278.77 | 22.10 | 50.17 | 279.67 |
May | 372.00 | 0.64 | 0.62 | 01-MAY-05:40 | 2591.46 | 18.18 | 75.00 | 385.83 | 1435.36 | 21.61 | 72.33 | 331.17 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-04:00 | 2386.31 | 18.94 | 80.50 | 375.83 | 1309.54 | 21.28 | 60.83 | 337.50 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-04:49 | 2458.92 | 19.56 | 88.83 | 384.67 | 1316.04 | 21.69 | 64.50 | 339.50 |
August | 389.17 | 0.64 | 0.62 | 01-AUG-05:40 | 3300.81 | 20.41 | 111.67 | 362.67 | 1338.74 | 21.92 | 68.50 | 331.17 |
September | 285.33 | 0.64 | 0.62 | 01-SEP-05:49 | 2873.84 | 20.33 | 79.67 | 310.83 | 1205.75 | 21.02 | 41.50 | 265.17 |
October | 305.50 | 0.64 | 0.62 | 01-OCT-14:39 | 2491.60 | 20.25 | 78.33 | 282.83 | 1328.78 | 23.00 | 75.67 | 244.83 |
November | 240.83 | 0.64 | 0.62 | 01-NOV-06:49 | 1711.08 | 20.33 | 71.67 | 232.33 | 864.04 | 21.62 | 71.83 | 179.33 |
December | 211.17 | 0.66 | 0.62 | 01-DEC-07:40 | 1533.50 | 19.27 | 64.00 | 201.83 | 931.13 | 23.16 | 76.67 | 130.50 |
Annual Sum or Average | 3472.67 | 0.64 | 2484.54 | 19.65 | 909.50 | 3607.67 | 1251.42 | 22.04 | 760.50 | 2998.00 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 1533.50 | 18.18 | 57.50 | 201.83 | 864.04 | 21.02 | 41.50 | 130.50 | |
Maximum of Months | 389.17 | 0.66 | 0.62 | 3300.81 | 20.81 | 111.67 | 385.83 | 1435.36 | 23.77 | 76.67 | 339.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.66 | 0.62 | 01-JAN-08:20 | 513.95 | 10.56 | 0.00 | 179.83 | 315.97 | 14.64 | 0.00 | 80.00 |
February | 216.00 | 0.65 | 0.62 | 01-FEB-08:30 | 554.83 | 11.60 | 0.00 | 211.83 | 363.24 | 15.87 | 0.00 | 126.00 |
March | 275.00 | 0.65 | 0.62 | 01-MAR-07:10 | 739.74 | 12.87 | 0.00 | 298.00 | 463.65 | 16.81 | 0.00 | 204.33 |
April | 261.17 | 0.63 | 0.62 | 01-APR-06:19 | 833.17 | 13.93 | 0.00 | 334.33 | 524.11 | 17.93 | 0.00 | 265.83 |
May | 372.00 | 0.63 | 0.62 | 01-MAY-05:40 | 1080.72 | 14.45 | 1.67 | 395.33 | 622.65 | 18.43 | 3.33 | 337.50 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-04:00 | 1212.22 | 16.63 | 40.67 | 392.33 | 686.60 | 21.23 | 50.17 | 362.00 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-04:00 | 1199.77 | 14.59 | 0.00 | 397.17 | 679.49 | 20.70 | 42.50 | 356.00 |
August | 389.17 | 0.63 | 0.62 | 01-AUG-05:40 | 983.88 | 14.43 | 0.00 | 372.67 | 596.13 | 18.37 | 0.00 | 334.83 |
September | 285.33 | 0.64 | 0.62 | 01-SEP-06:10 | 762.55 | 13.48 | 0.00 | 307.00 | 484.90 | 17.50 | 0.00 | 237.17 |
October | 305.50 | 0.64 | 0.62 | 01-OCT-14:39 | 687.80 | 13.03 | 0.00 | 277.67 | 448.74 | 17.13 | 0.00 | 213.83 |
November | 240.83 | 0.65 | 0.62 | 01-NOV-07:10 | 575.07 | 11.16 | 0.00 | 216.67 | 345.53 | 15.22 | 0.00 | 115.50 |
December | 211.17 | 0.68 | 0.62 | 01-DEC-08:20 | 412.93 | 9.39 | 0.00 | 161.33 | 262.65 | 13.65 | 0.00 | 47.67 |
Annual Sum or Average | 3472.67 | 0.64 | 848.44 | 13.38 | 42.33 | 3544.17 | 510.65 | 17.70 | 96.00 | 2680.67 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 412.93 | 9.39 | 0.00 | 161.33 | 262.65 | 13.65 | 0.00 | 47.67 | |
Maximum of Months | 389.17 | 0.68 | 0.62 | 1212.22 | 16.63 | 40.67 | 397.17 | 686.60 | 21.23 | 50.17 | 362.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.62 | 01-JAN-08:30 | 1592.00 | 19.50 | 57.17 | 210.00 | 932.16 | 23.02 | 64.33 | 143.33 |
February | 216.00 | 0.64 | 0.62 | 01-FEB-08:30 | 1845.48 | 19.88 | 57.00 | 232.17 | 947.54 | 21.44 | 39.83 | 179.50 |
March | 275.00 | 0.64 | 0.62 | 01-MAR-07:19 | 2553.37 | 19.54 | 70.83 | 306.50 | 1506.69 | 23.80 | 75.33 | 242.00 |
April | 261.17 | 0.64 | 0.62 | 01-APR-07:10 | 3090.08 | 20.50 | 76.83 | 327.83 | 1202.96 | 20.69 | 37.00 | 280.50 |
May | 372.00 | 0.63 | 0.62 | 01-MAY-05:00 | 2853.67 | 17.66 | 69.00 | 385.00 | 1252.51 | 18.10 | 0.00 | 332.33 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-05:30 | 2778.59 | 14.15 | 1.83 | 380.50 | 1483.53 | 18.30 | 0.00 | 328.00 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-05:40 | 2608.79 | 16.92 | 49.00 | 384.50 | 1379.25 | 18.42 | 0.00 | 335.50 |
August | 389.17 | 0.64 | 0.62 | 01-AUG-05:00 | 3337.94 | 18.59 | 83.33 | 363.33 | 1437.18 | 18.59 | 8.50 | 331.50 |
September | 285.33 | 0.64 | 0.62 | 01-SEP-06:30 | 2640.53 | 19.27 | 67.50 | 310.67 | 1401.24 | 22.37 | 60.67 | 266.33 |
October | 305.50 | 0.63 | 0.62 | 01-OCT-14:39 | 2936.60 | 22.76 | 109.33 | 295.50 | 1200.31 | 22.68 | 66.67 | 260.50 |
November | 240.83 | 0.64 | 0.62 | 01-NOV-07:19 | 1398.07 | 19.56 | 68.50 | 236.00 | 754.09 | 22.42 | 70.00 | 178.00 |
December | 211.17 | 0.66 | 0.62 | 01-DEC-08:20 | 1312.59 | 19.68 | 67.50 | 203.33 | 703.95 | 20.87 | 54.33 | 131.67 |
Annual Sum or Average | 3472.67 | 0.64 | 2528.52 | 18.77 | 777.83 | 3635.33 | 1228.67 | 20.57 | 476.67 | 3009.17 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 1312.59 | 14.15 | 1.83 | 203.33 | 703.95 | 18.10 | 0.00 | 131.67 | |
Maximum of Months | 389.17 | 0.66 | 0.62 | 3337.94 | 22.76 | 109.33 | 385.00 | 1506.69 | 23.80 | 75.33 | 335.50 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.742279E+09 | 25876.46 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1826707.93 | 25876.46 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.744106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.742279E+09 | 25876.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.717723E+10 | 11463.26 | 03-JAN-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.620964E+10 | 11404.04 | 16-FEB-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.442428E+10 | 11465.78 | 06-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.234925E+10 | 11449.59 | 11-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.847866E+09 | 11461.04 | 08-MAY-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28556917.50 | 8544.55 | 02-JUN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108544E+09 | 11011.72 | 20-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.622636E+09 | 11621.87 | 17-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.290561E+10 | 11454.14 | 14-NOV-17:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.493358E+10 | 11449.35 | 04-DEC-17:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.717723E+10 | 11621.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.227300E+10 | 9273.77 | 09-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165033E+10 | 9229.64 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.532348E+09 | 9253.17 | 31-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162084E+09 | 9241.79 | 21-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.301672E+09 | 9248.74 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.981106E+09 | 9233.22 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.590054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.227300E+10 | 9273.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.393410E+10 | 8386.28 | 17-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.335250E+10 | 8360.04 | 24-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128738E+10 | 8358.31 | 27-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.318656E+09 | 8364.10 | 25-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 648148.02 | 2560.01 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.600367E+09 | 8353.22 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178919E+10 | 8362.35 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.393410E+10 | 8386.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.246495E+10 | 9562.10 | 09-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191466E+10 | 9516.59 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.583564E+09 | 9540.89 | 31-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171340E+09 | 9529.17 | 21-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 969475.47 | 2200.95 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.408630E+09 | 9536.34 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114735E+10 | 9520.25 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.669146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.246495E+10 | 9562.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.241881E+10 | 25036.03 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114262E+10 | 25036.03 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 68208720.42 | 25036.03 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9561647.84 | 25036.03 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.280655E+09 | 25036.03 | 20-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.479564E+09 | 25036.03 | 04-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.439942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.241881E+10 | 25036.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.252868E+10 | 12677.41 | 17-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169196E+10 | 12668.87 | 28-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.484261E+09 | 12650.36 | 20-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145569E+09 | 12565.42 | 21-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 136150.11 | 907.67 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 915968.11 | 1546.19 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.502883E+09 | 12718.79 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130588E+10 | 12697.54 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.666029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.252868E+10 | 12718.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.249065E+10 | 10400.95 | 01-JAN-01:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177313E+10 | 10400.95 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.551826E+09 | 10400.95 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155356E+09 | 10400.95 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5451100.03 | 4298.02 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.620616E+09 | 10400.95 | 15-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145526E+10 | 10400.95 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.705229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.249065E+10 | 10400.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.380101E+10 | 9227.35 | 13-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.299741E+10 | 9198.67 | 21-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.863373E+09 | 9226.60 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170604E+09 | 9197.18 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4633992.53 | 4302.82 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.922503E+09 | 9234.77 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.213497E+10 | 9222.68 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.380101E+10 | 9234.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.262706E+10 | 10484.39 | 01-JAN-00:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.199470E+10 | 10484.39 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.620172E+09 | 10484.39 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167304E+09 | 10484.39 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 676401.24 | 1865.61 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8606086.84 | 4144.05 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.741206E+09 | 10484.39 | 15-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159512E+10 | 10484.39 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.775485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.262706E+10 | 10484.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.618363E+10 | 33327.48 | 23-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.458721E+10 | 33328.61 | 24-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115750E+10 | 33314.29 | 15-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.327754E+09 | 33236.87 | 04-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174211E+10 | 33358.92 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.354880E+10 | 33285.61 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.618363E+10 | 33358.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.445848E+10 | 14262.43 | 24-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.340432E+10 | 14192.53 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146281E+10 | 14167.54 | 18-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.565989E+09 | 14197.88 | 22-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17864031.46 | 11248.89 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 61594411.69 | 14046.67 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137301E+10 | 14195.04 | 29-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.288157E+10 | 14226.56 | 30-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.445848E+10 | 14262.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.382957E+10 | 11193.26 | 13-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298564E+10 | 11180.15 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119684E+10 | 11192.52 | 18-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.429458E+09 | 11155.45 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5938539.56 | 5082.54 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 70703181.35 | 9331.50 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130378E+10 | 11211.29 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.262393E+10 | 11225.43 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.382957E+10 | 11225.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.613676E+10 | 10669.86 | 24-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.523551E+10 | 10656.29 | 24-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207535E+10 | 10658.49 | 08-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.600712E+09 | 10636.02 | 21-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11920902.37 | 10597.44 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107873E+09 | 10580.54 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.212545E+10 | 10671.33 | 27-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.424785E+10 | 10673.71 | 26-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.613676E+10 | 10673.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.415586E+10 | 12199.76 | 13-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.344346E+10 | 12164.17 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144491E+10 | 12169.45 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.517833E+09 | 12135.19 | 22-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18526087.99 | 7093.55 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 224631.02 | 124.18 | 30-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109488E+09 | 9267.59 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160227E+10 | 12157.36 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.297648E+10 | 12187.06 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.415586E+10 | 12199.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.913572E+10 | 25544.49 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.913731E+10 | 25905.95 | 06-FEB-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.385049E+10 | 13590.63 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.463936E+09 | 6861.29 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26319826.52 | 3974.33 | 28-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222224E+10 | 14170.56 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.586865E+10 | 13669.18 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.913731E+10 | 25905.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102180E+11 | 23683.20 | 02-JAN-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102782E+11 | 26180.75 | 06-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.510833E+10 | 14888.20 | 23-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.910898E+09 | 8096.47 | 03-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2202163.64 | 1552.10 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108514E+09 | 5003.89 | 28-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.318499E+10 | 15659.63 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.749360E+10 | 15308.67 | 22-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.373047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102782E+11 | 26180.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110418E+11 | 24220.96 | 02-JAN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108727E+11 | 25328.23 | 06-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.531896E+10 | 17565.89 | 23-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116124E+10 | 9687.89 | 03-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7068466.16 | 3042.47 | 01-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.211004E+09 | 6900.55 | 28-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.347554E+10 | 17381.24 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.797691E+10 | 18055.63 | 22-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.400652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110418E+11 | 25328.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.458260E+09 | 0.304961E+09 | 23425.82 | 27-MAR-16:00 | 18704.07 | 0.00 |
April | 0.00 | 0.00 | 0.413474E+10 | 0.366396E+10 | 42212.81 | 07-APR-15:40 | 42212.81 | 0.00 |
May | 0.00 | 0.00 | 0.166086E+11 | 0.138232E+11 | 79221.41 | 30-MAY-14:00 | 79221.41 | 0.00 |
June | 0.00 | 0.00 | 0.591475E+11 | 0.452686E+11 | 110372.56 | 19-JUN-06:03 | 76920.04 | 0.00 |
July | 0.00 | 0.00 | 0.844502E+11 | 0.621814E+11 | 116646.99 | 31-JUL-04:02 | 80260.65 | 0.00 |
August | 0.00 | 0.00 | 0.862993E+11 | 0.682703E+11 | 121048.63 | 17-AUG-04:03 | 69685.00 | 0.00 |
September | 0.00 | 0.00 | 0.451515E+11 | 0.361125E+11 | 95104.05 | 08-SEP-04:03 | 59903.74 | 0.00 |
October | 0.00 | 0.00 | 0.192906E+11 | 0.135119E+11 | 67046.44 | 05-OCT-12:30 | 47692.74 | 0.00 |
November | 0.00 | 0.00 | 0.415396E+09 | 0.332024E+09 | 10584.71 | 03-NOV-14:00 | 10584.71 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.315956E+12 | 0.243469E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.862993E+11 | 0.682703E+11 | 121048.63 | 80260.65 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.429498E+09 | 0.287777E+09 | 21261.24 | 27-MAR-16:00 | 16785.08 | 0.00 |
April | 0.00 | 0.00 | 0.413579E+10 | 0.368418E+10 | 43916.22 | 07-APR-14:30 | 43916.22 | 0.00 |
May | 0.00 | 0.00 | 0.160290E+11 | 0.135938E+11 | 79520.82 | 30-MAY-14:00 | 79520.82 | 0.00 |
June | 0.00 | 0.00 | 0.540965E+11 | 0.415684E+11 | 108700.94 | 19-JUN-06:03 | 70705.43 | 0.00 |
July | 0.00 | 0.00 | 0.770409E+11 | 0.563058E+11 | 115113.27 | 22-JUL-05:03 | 57049.62 | 0.00 |
August | 0.00 | 0.00 | 0.764358E+11 | 0.604399E+11 | 112472.42 | 17-AUG-05:03 | 64653.37 | 0.00 |
September | 0.00 | 0.00 | 0.382197E+11 | 0.303137E+11 | 78602.52 | 01-SEP-05:03 | 52252.97 | 0.00 |
October | 0.00 | 0.00 | 0.160886E+11 | 0.112303E+11 | 57196.40 | 04-OCT-14:10 | 45645.61 | 0.00 |
November | 0.00 | 0.00 | 0.374870E+09 | 0.307588E+09 | 8599.28 | 03-NOV-14:00 | 8599.28 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.282851E+12 | 0.217731E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.770409E+11 | 0.604399E+11 | 115113.27 | 79520.82 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 175648.00 | 158303.63 | 292.75 | 15-JAN-10:40 | 263.84 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.446582E+09 | 0.293320E+09 | 22413.79 | 27-MAR-16:00 | 17090.90 | 0.00 |
April | 0.00 | 0.00 | 0.435760E+10 | 0.384324E+10 | 48961.65 | 07-APR-14:30 | 48961.65 | 0.00 |
May | 0.00 | 0.00 | 0.166977E+11 | 0.141952E+11 | 89145.15 | 30-MAY-14:00 | 89145.15 | 0.00 |
June | 0.00 | 0.00 | 0.570525E+11 | 0.444020E+11 | 97828.05 | 19-JUN-13:50 | 81607.00 | 0.00 |
July | 0.00 | 0.00 | 0.816496E+11 | 0.608259E+11 | 130721.75 | 22-JUL-05:03 | 59749.30 | 0.00 |
August | 0.00 | 0.00 | 0.807089E+11 | 0.647838E+11 | 125986.07 | 17-AUG-05:03 | 66955.34 | 0.00 |
September | 0.00 | 0.00 | 0.386054E+11 | 0.304592E+11 | 87888.50 | 01-SEP-14:00 | 87888.50 | 0.00 |
October | 0.00 | 0.00 | 0.155259E+11 | 0.106679E+11 | 60459.74 | 04-OCT-13:50 | 50574.72 | 0.00 |
November | 0.00 | 0.00 | 0.330843E+09 | 0.257189E+09 | 8494.40 | 04-NOV-12:30 | 6594.55 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.295375E+12 | 0.229728E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.816496E+11 | 0.647838E+11 | 130721.75 | 89145.15 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 1880.68 | 6598.02 | 31-JAN-12:09 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1908.84 | 6609.89 | 09-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1991.05 | 6554.59 | 01-MAR-12:06 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1771.46 | 6260.41 | 03-APR-11:07 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1719.67 | 5925.36 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1646.16 | 5482.71 | 02-JUN-11:08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1438.46 | 5116.29 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1560.12 | 4999.05 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1499.55 | 5227.02 | 27-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1587.93 | 5631.91 | 30-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1726.40 | 6062.41 | 30-NOV-12:13 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1760.56 | 6409.17 | 29-DEC-12:09 |
Annual Sum or Average | 0.00 | 1706.43 | ||||
Minimum of Months | 0.00 | 0.00 | 1438.46 | 4999.05 | ||
Maximum of Months | 0.00 | 0.00 | 1991.05 | 6609.89 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136882E+10 | 0.29 | 2430.98 | 02-JAN-05:01 | 0.74 |
February | 0.121090E+10 | 0.28 | 1957.79 | 06-FEB-07:01 | 0.66 |
March | 0.153669E+10 | 0.30 | 2072.89 | 29-MAR-07:03 | 0.68 |
April | 0.181587E+10 | 0.30 | 4220.27 | 10-APR-15:10 | 1.01 |
May | 0.280658E+10 | 0.37 | 8420.39 | 30-MAY-15:10 | 1.53 |
June | 0.458783E+10 | 0.49 | 10414.18 | 19-JUN-12:09 | 1.75 |
July | 0.572908E+10 | 0.53 | 10664.84 | 10-JUL-06:03 | 1.78 |
August | 0.631004E+10 | 0.58 | 10664.84 | 02-AUG-06:03 | 1.78 |
September | 0.416878E+10 | 0.46 | 9339.93 | 05-SEP-07:10 | 1.63 |
October | 0.323532E+10 | 0.39 | 6767.58 | 05-OCT-15:50 | 1.33 |
November | 0.159160E+10 | 0.29 | 3951.49 | 03-NOV-05:03 | 0.97 |
December | 0.130110E+10 | 0.27 | 1613.31 | 22-DEC-08:08 | 0.61 |
Annual Sum or Average | 0.356626E+11 | 0.38 | |||
Minimum of Months | 0.121090E+10 | 0.27 | 1613.31 | 0.61 | |
Maximum of Months | 0.631004E+10 | 0.58 | 10664.84 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.145365E+10 | 0.32 | 2497.86 | 02-JAN-05:01 | 0.82 |
February | 0.128484E+10 | 0.31 | 2497.86 | 01-FEB-07:01 | 0.82 |
March | 0.148795E+10 | 0.31 | 2497.86 | 01-MAR-07:01 | 0.82 |
April | 0.170601E+10 | 0.32 | 4930.79 | 10-APR-15:20 | 1.22 |
May | 0.275813E+10 | 0.40 | 9613.76 | 30-MAY-14:20 | 1.84 |
June | 0.456522E+10 | 0.53 | 9343.36 | 19-JUN-06:03 | 1.80 |
July | 0.565640E+10 | 0.58 | 10008.89 | 31-JUL-04:02 | 1.88 |
August | 0.629590E+10 | 0.62 | 10008.89 | 05-AUG-05:03 | 1.88 |
September | 0.355465E+10 | 0.45 | 9159.18 | 05-SEP-09:10 | 1.77 |
October | 0.249579E+10 | 0.37 | 6242.35 | 04-OCT-15:50 | 1.39 |
November | 0.134369E+10 | 0.29 | 2497.86 | 20-NOV-07:01 | 0.82 |
December | 0.130764E+10 | 0.29 | 2497.86 | 06-DEC-07:01 | 0.82 |
Annual Sum or Average | 0.339099E+11 | 0.40 | |||
Minimum of Months | 0.128484E+10 | 0.29 | 2497.86 | 0.82 | |
Maximum of Months | 0.629590E+10 | 0.62 | 10008.89 | 1.88 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.170919E+10 | 0.35 | 2371.88 | 02-JAN-07:02 | 0.72 |
February | 0.146822E+10 | 0.33 | 2371.88 | 06-FEB-07:02 | 0.72 |
March | 0.146235E+10 | 0.29 | 2371.88 | 08-MAR-07:01 | 0.71 |
April | 0.158469E+10 | 0.29 | 4458.15 | 07-APR-15:20 | 1.01 |
May | 0.245865E+10 | 0.35 | 9223.73 | 30-MAY-14:10 | 1.59 |
June | 0.405419E+10 | 0.44 | 9409.04 | 19-JUN-13:40 | 1.60 |
July | 0.510609E+10 | 0.49 | 10118.83 | 22-JUL-05:03 | 1.67 |
August | 0.567174E+10 | 0.52 | 9983.61 | 14-AUG-14:50 | 1.66 |
September | 0.299828E+10 | 0.38 | 8194.74 | 05-SEP-15:10 | 1.47 |
October | 0.202834E+10 | 0.31 | 5569.93 | 04-OCT-15:30 | 1.15 |
November | 0.133237E+10 | 0.28 | 2371.88 | 15-NOV-07:01 | 0.71 |
December | 0.140565E+10 | 0.29 | 2371.88 | 12-DEC-06:02 | 0.71 |
Annual Sum or Average | 0.312798E+11 | 0.36 | |||
Minimum of Months | 0.133237E+10 | 0.28 | 2371.88 | 0.71 | |
Maximum of Months | 0.567174E+10 | 0.52 | 10118.83 | 1.67 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:02 | 0.22 | 0.22 | 57.66 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:01 | 0.22 | 0.22 | 56.71 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:01 | 0.22 | 0.22 | 55.45 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:02 | 0.22 | 0.22 | 56.33 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:03 | 0.22 | 0.22 | 56.50 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 56.39 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 57.07 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 56.70 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 56.40 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 57.63 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:03 | 0.22 | 0.22 | 56.87 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:01 | 0.22 | 0.22 | 56.56 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 55.45 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.66 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 57.68 | 57.68 | 1880.68 | 6598.02 | 31-JAN-12:09 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.11 | 57.11 | 1908.84 | 6609.89 | 09-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 55.86 | 55.86 | 1991.05 | 6554.59 | 01-MAR-12:06 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.77 | 56.77 | 1771.46 | 6260.41 | 03-APR-11:07 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.03 | 57.03 | 1719.67 | 5925.36 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.79 | 56.79 | 1646.16 | 5482.71 | 02-JUN-11:08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.45 | 57.45 | 1438.46 | 5116.29 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.03 | 57.03 | 1560.12 | 4999.05 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.02 | 57.02 | 1499.55 | 5227.02 | 27-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.97 | 56.97 | 1587.93 | 5631.91 | 30-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.29 | 57.29 | 1726.40 | 6062.41 | 30-NOV-12:13 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.96 | 56.96 | 1760.56 | 6409.17 | 29-DEC-12:09 |
Annual Sum or Average | 0.00 | 1706.43 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.86 | 55.86 | 1438.46 | 4999.05 | ||
Maximum of Months | 0.00 | 0.00 | 57.68 | 57.68 | 1991.05 | 6609.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.179604E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.143398E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.848491E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.589035E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.791677E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.190817E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.265659E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.278905E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.152518E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.853587E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.592528E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.101523E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.167996E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.589035E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.278905E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.153199E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.108847E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.418885E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.342577E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.686210E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.177946E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.246193E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.253900E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.128932E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.645185E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.451755E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.827843E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.140626E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.342577E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.253900E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.264735E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.211244E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.891814E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.516021E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.681221E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.180912E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.252662E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.259042E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.125169E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.622761E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.957313E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.176843E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.183752E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.516021E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.264735E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136882E+10 | 0.00 | 0.257273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121090E+10 | 0.00 | 0.222663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153669E+10 | 0.458260E+09 | 0.106781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.181587E+10 | 0.413474E+10 | 0.346527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.280658E+10 | 0.166086E+11 | 0.849484E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.458783E+10 | 0.591475E+11 | 28556917.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.572908E+10 | 0.844502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.631004E+10 | 0.862993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.416878E+10 | 0.451515E+11 | 0.108544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.323532E+10 | 0.192906E+11 | 0.648956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159160E+10 | 0.415396E+09 | 0.643852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130110E+10 | 0.00 | 0.147199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.356626E+11 | 0.315956E+12 | 0.849308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.631004E+10 | 0.862993E+11 | 0.257273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.145365E+10 | 0.00 | 0.240842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128484E+10 | 0.00 | 0.198780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148795E+10 | 0.429498E+09 | 0.769617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170601E+10 | 0.413579E+10 | 0.155929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.275813E+10 | 0.160290E+11 | 3014714.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.456522E+10 | 0.540965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.565640E+10 | 0.770409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.629590E+10 | 0.764358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.355465E+10 | 0.382197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.249579E+10 | 0.160886E+11 | 0.128121E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134369E+10 | 0.374870E+09 | 0.625285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130764E+10 | 0.00 | 0.144644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.339099E+11 | 0.282851E+12 | 0.740660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.629590E+10 | 0.770409E+11 | 0.240842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.170919E+10 | 175648.00 | 0.358061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146822E+10 | 0.00 | 0.305288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146235E+10 | 0.446582E+09 | 0.126564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158469E+10 | 0.435760E+10 | 0.360299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.245865E+10 | 0.166977E+11 | 61318027.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.405419E+10 | 0.570525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.510609E+10 | 0.816496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.567174E+10 | 0.807089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.299828E+10 | 0.386054E+11 | 224631.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202834E+10 | 0.155259E+11 | 0.560663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133237E+10 | 0.330843E+09 | 0.116222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140565E+10 | 0.00 | 0.242556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.312798E+11 | 0.295375E+12 | 0.119094E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.567174E+10 | 0.816496E+11 | 0.358061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.136882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153669E+10 | 0.00 | 0.00 | 0.00 | 0.120648E+09 | 0.682757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.181587E+10 | 0.00 | 0.00 | 0.00 | 0.107315E+10 | 0.300133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.280658E+10 | 0.00 | 0.00 | 0.00 | 0.426071E+10 | 0.849484E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.458783E+10 | 0.00 | 0.00 | 0.00 | 0.144653E+11 | 28556917.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.572908E+10 | 0.00 | 0.00 | 0.00 | 0.208368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.631004E+10 | 0.00 | 0.00 | 0.00 | 0.215805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.416878E+10 | 0.00 | 0.00 | 0.00 | 0.109744E+11 | 0.108544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.323532E+10 | 0.00 | 0.00 | 0.00 | 0.467791E+10 | 0.622636E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159160E+10 | 0.00 | 0.00 | 0.00 | 0.117401E+09 | 0.421628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.885123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.356626E+11 | 0.00 | 0.00 | 0.00 | 0.781068E+11 | 0.542261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.631004E+10 | 0.00 | 0.00 | 0.00 | 0.215805E+11 | 0.165916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.145365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148795E+10 | 0.00 | 0.00 | 0.00 | 0.113066E+09 | 0.258784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170601E+10 | 0.00 | 0.00 | 0.00 | 0.107136E+10 | 0.648396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.275813E+10 | 0.00 | 0.00 | 0.00 | 0.410316E+10 | 812551.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.456522E+10 | 0.00 | 0.00 | 0.00 | 0.132294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.565640E+10 | 0.00 | 0.00 | 0.00 | 0.189629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.629590E+10 | 0.00 | 0.00 | 0.00 | 0.190941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.355465E+10 | 0.00 | 0.00 | 0.00 | 0.933855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.249579E+10 | 0.00 | 0.00 | 0.00 | 0.393645E+10 | 19607147.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134369E+10 | 0.00 | 0.00 | 0.00 | 0.105997E+09 | 0.306786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.339099E+11 | 0.00 | 0.00 | 0.00 | 0.699550E+11 | 0.367613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.629590E+10 | 0.00 | 0.00 | 0.00 | 0.190941E+11 | 0.138662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.170919E+10 | 0.00 | 0.00 | 0.00 | 51908.34 | 0.247643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146235E+10 | 0.00 | 0.00 | 0.00 | 0.118375E+09 | 0.733741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158469E+10 | 0.00 | 0.00 | 0.00 | 0.113377E+10 | 0.244175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.245865E+10 | 0.00 | 0.00 | 0.00 | 0.429931E+10 | 54249561.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.405419E+10 | 0.00 | 0.00 | 0.00 | 0.140370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.510609E+10 | 0.00 | 0.00 | 0.00 | 0.201601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.567174E+10 | 0.00 | 0.00 | 0.00 | 0.202324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.299828E+10 | 0.00 | 0.00 | 0.00 | 0.951842E+10 | 224631.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202834E+10 | 0.00 | 0.00 | 0.00 | 0.384961E+10 | 0.349659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133237E+10 | 0.00 | 0.00 | 0.00 | 94146036.56 | 0.814661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.312798E+11 | 0.00 | 0.00 | 0.00 | 0.734432E+11 | 0.790290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.567174E+10 | 0.00 | 0.00 | 0.00 | 0.202324E+11 | 0.247643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.959695E+10 | 0.00 | 0.00 | 6770007.42 | 0.00 | 0.543460E+09 | 0.447665E+10 | 0.00 | 0.29 |
February | 0.868071E+10 | 0.00 | 0.00 | 8544193.69 | 0.00 | 885203.15 | 0.585057E+10 | 0.00 | 0.29 |
March | 0.530268E+10 | 0.00 | 0.00 | 24656837.65 | 0.00 | 0.00 | 0.119461E+11 | 0.00 | 0.42 |
April | 0.233763E+10 | 10753727.85 | 0.00 | 28890019.26 | 0.00 | 0.00 | 0.142100E+11 | 0.00 | 0.61 |
May | 0.987004E+09 | 0.113532E+09 | 0.00 | 38813797.26 | 0.00 | 0.00 | 0.162192E+11 | 0.00 | 0.97 |
June | 0.342205E+09 | 0.346697E+10 | 0.00 | 16463005.43 | 43259503.36 | 0.00 | 0.347015E+10 | 0.00 | 0.68 |
July | 12353675.65 | 0.823006E+10 | 0.00 | 1122658.38 | 0.111707E+09 | 0.00 | 0.129292E+09 | 0.00 | 0.30 |
August | 0.188473E+09 | 0.641600E+10 | 0.00 | 13417853.63 | 91206862.93 | 0.00 | 0.158295E+10 | 0.00 | 0.56 |
September | 0.728836E+09 | 0.211651E+10 | 0.00 | 26325695.34 | 20171060.31 | 0.00 | 0.818622E+10 | 0.00 | 0.82 |
October | 0.134309E+10 | 0.168975E+09 | 0.00 | 42074556.93 | 0.00 | 0.00 | 0.157612E+11 | 0.00 | 0.91 |
November | 0.304562E+10 | 0.00 | 0.00 | 28135932.27 | 0.00 | 0.00 | 0.143157E+11 | 0.00 | 0.50 |
December | 0.654289E+10 | 0.00 | 0.00 | 16118011.55 | 0.00 | 0.00 | 0.847920E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.391084E+11 | 0.205228E+11 | 0.00 | 0.251333E+09 | 0.266344E+09 | 0.544346E+09 | 0.104627E+12 | 0.00 | 0.56 |
Minimum of Months | 12353675.65 | 0.00 | 0.00 | 1122658.38 | 0.00 | 0.00 | 0.129292E+09 | 0.00 | 0.29 |
Maximum of Months | 0.959695E+10 | 0.823006E+10 | 0.00 | 42074556.93 | 0.111707E+09 | 0.543460E+09 | 0.162192E+11 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.122708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145852E+10 | 0.00 | 0.00 | 0.28 |
February | 0.126933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644806E+09 | 0.00 | 0.00 | 0.28 |
March | 0.123566E+11 | 0.00 | 0.00 | 819559.10 | 0.00 | 17304073.22 | 0.119700E+10 | 0.00 | 0.33 |
April | 0.644038E+10 | 4909986.74 | 0.00 | 7831877.16 | 8873.29 | 2514968.26 | 0.510577E+10 | 0.00 | 0.43 |
May | 0.290469E+10 | 87682816.53 | 0.00 | 18467756.61 | 0.00 | 0.00 | 0.877079E+10 | 0.00 | 0.66 |
June | 0.379211E+09 | 0.262683E+10 | 0.00 | 10754677.87 | 39624988.68 | 0.00 | 0.231878E+10 | 0.00 | 0.49 |
July | 19630594.73 | 0.688085E+10 | 0.00 | 993713.35 | 0.104733E+09 | 0.00 | 98710425.96 | 0.00 | 0.25 |
August | 0.260176E+09 | 0.549966E+10 | 0.00 | 9173264.27 | 88091100.42 | 0.00 | 0.105148E+10 | 0.00 | 0.44 |
September | 0.118107E+10 | 0.171768E+10 | 0.00 | 14023209.93 | 19673459.76 | 0.00 | 0.458265E+10 | 0.00 | 0.56 |
October | 0.287339E+10 | 0.144390E+09 | 0.00 | 17102226.55 | 3378319.38 | 0.00 | 0.733921E+10 | 0.00 | 0.56 |
November | 0.924216E+10 | 0.00 | 0.00 | 3052453.84 | 0.00 | 82613286.84 | 0.249585E+10 | 0.00 | 0.34 |
December | 0.128176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96520474.38 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.734390E+11 | 0.169620E+11 | 0.00 | 82218738.67 | 0.255510E+09 | 0.230228E+10 | 0.329602E+11 | 0.00 | 0.41 |
Minimum of Months | 19630594.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.128176E+11 | 0.688085E+10 | 0.00 | 18467756.61 | 0.104733E+09 | 0.145852E+10 | 0.877079E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.920733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365700E+10 | 0.00 | 0.00 | 0.27 |
February | 0.965140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280445E+10 | 0.00 | 0.00 | 0.27 |
March | 0.120380E+11 | 0.00 | 0.00 | 472296.23 | 0.00 | 0.484567E+09 | 0.557580E+09 | 0.00 | 0.33 |
April | 0.733427E+10 | 672547.05 | 0.00 | 6002264.69 | 2129087.31 | 67470580.66 | 0.385611E+10 | 0.00 | 0.43 |
May | 0.419932E+10 | 71803836.14 | 0.00 | 15590118.38 | 0.00 | 0.00 | 0.762357E+10 | 0.00 | 0.67 |
June | 0.543321E+09 | 0.250804E+10 | 0.00 | 9888594.50 | 36522693.76 | 0.00 | 0.229669E+10 | 0.00 | 0.50 |
July | 29077955.28 | 0.659190E+10 | 0.00 | 1131095.27 | 96762960.27 | 0.00 | 83848253.06 | 0.00 | 0.26 |
August | 0.203352E+09 | 0.524684E+10 | 0.00 | 8713780.04 | 81984556.81 | 0.00 | 0.101625E+10 | 0.00 | 0.45 |
September | 0.179450E+10 | 0.166067E+10 | 0.00 | 10411757.09 | 29560137.18 | 0.00 | 0.358600E+10 | 0.00 | 0.55 |
October | 0.447334E+10 | 87665327.59 | 0.00 | 10095124.43 | 5830120.14 | 0.00 | 0.461258E+10 | 0.00 | 0.53 |
November | 0.910190E+10 | 0.00 | 0.00 | 713027.26 | 0.00 | 0.837758E+09 | 0.991048E+09 | 0.00 | 0.33 |
December | 0.102366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177373E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.688124E+11 | 0.161676E+11 | 0.00 | 63018057.88 | 0.252790E+09 | 0.962497E+10 | 0.246237E+11 | 0.00 | 0.41 |
Minimum of Months | 29077955.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.120380E+11 | 0.659190E+10 | 0.00 | 15590118.38 | 96762960.27 | 0.365700E+10 | 0.762357E+10 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.343627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258210E+10 | 0.00 | 0.00 | 0.29 |
February | 0.391912E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243579E+10 | 0.00 | 0.00 | 0.29 |
March | 0.153644E+10 | 0.00 | 0.00 | 10982.93 | 0.00 | 0.122490E+10 | 26837163.65 | 0.00 | 0.33 |
April | 0.157438E+10 | 536842.60 | 0.00 | 1067137.48 | 91740.83 | 0.312994E+09 | 0.501257E+09 | 0.00 | 0.44 |
May | 0.102845E+10 | 22601156.67 | 0.00 | 3761463.94 | 0.00 | 5619578.32 | 0.164105E+10 | 0.00 | 0.75 |
June | 0.130426E+09 | 0.780181E+09 | 0.00 | 2634931.59 | 9511787.65 | 0.00 | 0.590679E+09 | 0.00 | 0.66 |
July | 7127501.67 | 0.214076E+10 | 0.00 | 357538.53 | 20031530.06 | 0.00 | 20589362.61 | 0.00 | 0.39 |
August | 57237532.72 | 0.169186E+10 | 0.00 | 2209608.58 | 19571912.43 | 0.00 | 0.247459E+09 | 0.00 | 0.61 |
September | 0.492492E+09 | 0.418527E+09 | 0.00 | 2145490.01 | 14882295.12 | 0.00 | 0.686254E+09 | 0.00 | 0.60 |
October | 0.123208E+10 | 17993629.11 | 0.00 | 1340804.69 | 3913398.33 | 48093768.16 | 0.560977E+09 | 0.00 | 0.52 |
November | 0.126798E+10 | 0.00 | 0.00 | 13550.63 | 0.00 | 0.104761E+10 | 20540291.67 | 0.00 | 0.33 |
December | 0.414986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217406E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.847714E+10 | 0.507246E+10 | 0.00 | 13541508.39 | 68002664.42 | 0.983116E+10 | 0.429564E+10 | 0.00 | 0.46 |
Minimum of Months | 7127501.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.157438E+10 | 0.214076E+10 | 0.00 | 3761463.94 | 20031530.06 | 0.258210E+10 | 0.164105E+10 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.558442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194005E+10 | 0.00 | 0.00 | 0.39 |
February | 0.799217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161172E+10 | 0.00 | 0.00 | 0.39 |
March | 0.155409E+10 | 0.00 | 0.00 | 248285.21 | 0.00 | 0.726850E+09 | 0.261213E+09 | 0.00 | 0.48 |
April | 0.118800E+10 | 1218410.51 | 0.00 | 2006170.46 | 0.00 | 0.246296E+09 | 0.101694E+10 | 0.00 | 0.74 |
May | 0.891869E+09 | 22876818.40 | 0.00 | 4663837.50 | 0.00 | 808302.74 | 0.197361E+10 | 0.00 | 1.22 |
June | 92105058.66 | 0.629314E+09 | 0.00 | 2901308.39 | 22775742.72 | 0.00 | 0.688732E+09 | 0.00 | 0.96 |
July | 4373599.95 | 0.176586E+10 | 0.00 | 400469.03 | 19140746.31 | 0.00 | 31007584.38 | 0.00 | 0.53 |
August | 40442123.94 | 0.150730E+10 | 0.00 | 2473877.00 | 16681673.90 | 0.00 | 0.306482E+09 | 0.00 | 0.93 |
September | 0.370609E+09 | 0.339626E+09 | 0.00 | 2858089.08 | 26573980.54 | 0.00 | 0.875568E+09 | 0.00 | 0.94 |
October | 0.845297E+09 | 15502874.85 | 0.00 | 2282055.90 | 4306635.02 | 26976901.42 | 0.965474E+09 | 0.00 | 0.85 |
November | 0.132544E+10 | 0.00 | 0.00 | 79913.52 | 0.00 | 0.678454E+09 | 95742165.27 | 0.00 | 0.47 |
December | 0.835390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147770E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.850528E+10 | 0.428170E+10 | 0.00 | 17914006.09 | 89478778.50 | 0.670886E+10 | 0.621477E+10 | 0.00 | 0.69 |
Minimum of Months | 4373599.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.155409E+10 | 0.176586E+10 | 0.00 | 4663837.50 | 26573980.54 | 0.194005E+10 | 0.197361E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.990777E+09 | 0.00 | 0.00 | 782493.07 | 0.00 | 0.186020E+10 | 0.500152E+09 | 0.00 | 0.33 |
February | 0.108413E+10 | 0.00 | 0.00 | 1295062.17 | 0.00 | 0.153400E+10 | 0.745113E+09 | 0.00 | 0.34 |
March | 0.155221E+10 | 0.00 | 0.00 | 3566978.30 | 0.00 | 0.767772E+09 | 0.188578E+10 | 0.00 | 0.52 |
April | 0.137920E+10 | 1477793.15 | 0.00 | 4075814.78 | 0.00 | 0.298984E+09 | 0.198294E+10 | 0.00 | 0.72 |
May | 0.118490E+10 | 28368170.92 | 0.00 | 5770611.46 | 27933.37 | 8137008.90 | 0.239092E+10 | 0.00 | 0.99 |
June | 0.170501E+09 | 0.871677E+09 | 0.00 | 3069028.98 | 17153294.03 | 0.00 | 0.702536E+09 | 0.00 | 0.77 |
July | 8253079.87 | 0.242841E+10 | 0.00 | 483039.72 | 25602948.91 | 0.00 | 22079729.21 | 0.00 | 0.44 |
August | 62918469.47 | 0.220439E+10 | 0.00 | 3576151.55 | 22658175.27 | 0.00 | 0.374400E+09 | 0.00 | 0.86 |
September | 0.436766E+09 | 0.609274E+09 | 0.00 | 6313255.94 | 18269495.98 | 0.00 | 0.176134E+10 | 0.00 | 1.07 |
October | 0.766309E+09 | 50732003.27 | 0.00 | 8354249.00 | 642252.15 | 29524625.14 | 0.332455E+10 | 0.00 | 1.18 |
November | 0.131446E+10 | 0.00 | 0.00 | 2700742.97 | 0.00 | 0.674499E+09 | 0.140241E+10 | 0.00 | 0.51 |
December | 0.106194E+10 | 0.00 | 0.00 | 1120875.79 | 0.00 | 0.148726E+10 | 0.586088E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.100124E+11 | 0.619433E+10 | 0.00 | 41108303.73 | 84354099.72 | 0.666038E+10 | 0.156783E+11 | 0.00 | 0.67 |
Minimum of Months | 8253079.87 | 0.00 | 0.00 | 483039.72 | 0.00 | 0.00 | 22079729.21 | 0.00 | 0.33 |
Maximum of Months | 0.155221E+10 | 0.242841E+10 | 0.00 | 8354249.00 | 25602948.91 | 0.186020E+10 | 0.332455E+10 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.637661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208837E+10 | 0.00 | 0.00 | 0.42 |
February | 0.679348E+09 | 0.00 | 0.00 | 40495.57 | 0.00 | 0.189268E+10 | 69091249.39 | 0.00 | 0.43 |
March | 0.141544E+10 | 0.00 | 0.00 | 855332.29 | 0.00 | 0.930371E+09 | 0.543407E+09 | 0.00 | 0.55 |
April | 0.136667E+10 | 223589.44 | 0.00 | 2354207.55 | 382545.86 | 0.280973E+09 | 0.110575E+10 | 0.00 | 0.82 |
May | 0.111307E+10 | 21441103.40 | 0.00 | 4320465.76 | 383752.21 | 7764217.56 | 0.175319E+10 | 0.00 | 1.24 |
June | 0.140817E+09 | 0.657270E+09 | 0.00 | 2484595.23 | 22087128.01 | 0.00 | 0.547285E+09 | 0.00 | 0.97 |
July | 7411024.93 | 0.178670E+10 | 0.00 | 404090.98 | 19431059.04 | 0.00 | 14066566.39 | 0.00 | 0.52 |
August | 65228638.61 | 0.155047E+10 | 0.00 | 2103565.00 | 22183165.00 | 0.00 | 0.206874E+09 | 0.00 | 0.92 |
September | 0.496698E+09 | 0.375845E+09 | 0.00 | 2706329.06 | 25635323.22 | 0.00 | 0.754523E+09 | 0.00 | 0.97 |
October | 0.112468E+10 | 24133059.32 | 0.00 | 2257383.32 | 2728576.11 | 46434067.62 | 0.921130E+09 | 0.00 | 0.93 |
November | 0.127487E+10 | 0.00 | 0.00 | 194697.74 | 0.00 | 0.890673E+09 | 0.148399E+09 | 0.00 | 0.52 |
December | 0.663975E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185360E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.898587E+10 | 0.441609E+10 | 0.00 | 17721162.51 | 92831549.45 | 0.799087E+10 | 0.606371E+10 | 0.00 | 0.73 |
Minimum of Months | 7411024.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.141544E+10 | 0.178670E+10 | 0.00 | 4320465.76 | 25635323.22 | 0.208837E+10 | 0.175319E+10 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.573612E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255377E+10 | 0.00 | 0.00 | 0.29 |
February | 0.523933E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249868E+10 | 0.00 | 0.00 | 0.29 |
March | 0.192748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100818E+10 | 0.00 | 0.00 | 0.33 |
April | 0.199265E+10 | 606905.02 | 0.00 | 193980.77 | 709804.01 | 0.203320E+09 | 0.143999E+09 | 0.00 | 0.39 |
May | 0.143356E+10 | 19255099.81 | 0.00 | 1625777.93 | 0.00 | 341519.69 | 0.734928E+09 | 0.00 | 0.58 |
June | 0.171581E+09 | 0.608522E+09 | 0.00 | 1718972.03 | 13935508.10 | 0.00 | 0.384714E+09 | 0.00 | 0.50 |
July | 9786528.48 | 0.167919E+10 | 0.00 | 179791.78 | 23563901.29 | 0.00 | 15094987.11 | 0.00 | 0.28 |
August | 88142067.48 | 0.138465E+10 | 0.00 | 1766762.98 | 19558654.34 | 0.00 | 0.195919E+09 | 0.00 | 0.48 |
September | 0.474409E+09 | 0.364201E+09 | 0.00 | 2382574.19 | 4256097.54 | 0.00 | 0.765917E+09 | 0.00 | 0.58 |
October | 0.131978E+10 | 25692589.04 | 0.00 | 1881109.90 | 446052.27 | 0.00 | 0.809666E+09 | 0.00 | 0.54 |
November | 0.201018E+10 | 0.00 | 0.00 | 34779.82 | 0.00 | 0.502655E+09 | 80430744.33 | 0.00 | 0.34 |
December | 0.120749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161783E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.117326E+11 | 0.408212E+10 | 0.00 | 9783749.40 | 62470017.54 | 0.838478E+10 | 0.313067E+10 | 0.00 | 0.41 |
Minimum of Months | 9786528.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.201018E+10 | 0.167919E+10 | 0.00 | 2382574.19 | 23563901.29 | 0.255377E+10 | 0.809666E+09 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.733664E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158673E+10 | 0.00 | 0.00 | 0.34 |
February | 0.846101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139569E+10 | 0.00 | 0.00 | 0.34 |
March | 0.172825E+10 | 0.00 | 0.00 | 109637.26 | 0.00 | 0.414238E+09 | 93898852.22 | 0.00 | 0.40 |
April | 0.123870E+10 | 1938181.61 | 0.00 | 1368164.34 | 0.00 | 0.108880E+09 | 0.663785E+09 | 0.00 | 0.57 |
May | 0.830537E+09 | 22300211.98 | 0.00 | 3162525.98 | 0.00 | 0.00 | 0.130123E+10 | 0.00 | 0.92 |
June | 84944129.06 | 0.521617E+09 | 0.00 | 2241976.40 | 13384674.47 | 0.00 | 0.527446E+09 | 0.00 | 0.76 |
July | 4227960.89 | 0.145884E+10 | 0.00 | 230155.12 | 17888941.06 | 0.00 | 24599345.98 | 0.00 | 0.40 |
August | 59108126.60 | 0.129594E+10 | 0.00 | 2161589.69 | 14606024.36 | 0.00 | 0.259413E+09 | 0.00 | 0.78 |
September | 0.261956E+09 | 0.320016E+09 | 0.00 | 3230282.62 | 3585445.72 | 0.00 | 0.985296E+09 | 0.00 | 0.89 |
October | 0.672268E+09 | 24849728.82 | 0.00 | 3473761.05 | 473.18 | 0.00 | 0.137803E+10 | 0.00 | 0.86 |
November | 0.132089E+10 | 0.00 | 0.00 | 481100.05 | 0.00 | 0.289519E+09 | 0.393057E+09 | 0.00 | 0.42 |
December | 0.122101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.924555E+09 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.900166E+10 | 0.364550E+10 | 0.00 | 16459192.51 | 49465558.80 | 0.471961E+10 | 0.562675E+10 | 0.00 | 0.58 |
Minimum of Months | 4227960.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.172825E+10 | 0.145884E+10 | 0.00 | 3473761.05 | 17888941.06 | 0.158673E+10 | 0.137803E+10 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.513044E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359288E+10 | 0.00 | 0.00 | 0.37 |
February | 0.573983E+09 | 0.00 | 0.00 | 17257.97 | 0.00 | 0.340649E+10 | 24977112.31 | 0.00 | 0.37 |
March | 0.126408E+10 | 0.00 | 0.00 | 207422.47 | 0.00 | 0.218532E+10 | 0.164424E+09 | 0.00 | 0.40 |
April | 0.140069E+10 | 3767505.87 | 0.00 | 872457.92 | 0.00 | 0.104849E+10 | 0.368295E+09 | 0.00 | 0.50 |
May | 0.151081E+10 | 30132218.14 | 0.00 | 1384873.57 | 143235.10 | 0.334713E+09 | 0.525086E+09 | 0.00 | 0.64 |
June | 0.219276E+09 | 0.743285E+09 | 0.00 | 1447586.43 | 37525093.06 | 18630138.06 | 0.313368E+09 | 0.00 | 0.54 |
July | 11735266.57 | 0.225747E+10 | 0.00 | 191981.48 | 39911783.87 | 0.00 | 12396067.76 | 0.00 | 0.37 |
August | 0.103616E+09 | 0.225148E+10 | 0.00 | 2624616.52 | 24953987.48 | 0.00 | 0.248754E+09 | 0.00 | 0.73 |
September | 0.405543E+09 | 0.578735E+09 | 0.00 | 5075158.81 | 20369929.00 | 45383575.86 | 0.137057E+10 | 0.00 | 0.91 |
October | 0.763401E+09 | 67189064.14 | 0.00 | 6306597.77 | 30429.73 | 0.246518E+09 | 0.252402E+10 | 0.00 | 1.00 |
November | 0.133973E+10 | 0.00 | 0.00 | 957775.34 | 0.00 | 0.139475E+10 | 0.623319E+09 | 0.00 | 0.45 |
December | 0.896659E+09 | 0.00 | 0.00 | 87417.86 | 0.00 | 0.259576E+10 | 63132568.25 | 0.00 | 0.34 |
Annual Sum or Average | 0.900258E+10 | 0.593206E+10 | 0.00 | 19173146.14 | 0.122934E+09 | 0.148689E+11 | 0.623834E+10 | 0.00 | 0.55 |
Minimum of Months | 11735266.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.151081E+10 | 0.225747E+10 | 0.00 | 6306597.77 | 39911783.87 | 0.359288E+10 | 0.252402E+10 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.711956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169468E+10 | 0.00 | 0.00 | 0.35 |
February | 0.742773E+09 | 0.00 | 0.00 | 3458.79 | 0.00 | 0.156881E+10 | 15553688.41 | 0.00 | 0.35 |
March | 0.167620E+10 | 0.00 | 0.00 | 351628.45 | 0.00 | 0.444796E+09 | 0.215513E+09 | 0.00 | 0.42 |
April | 0.134101E+10 | 918322.78 | 0.00 | 1344832.50 | 371820.42 | 0.108885E+09 | 0.620060E+09 | 0.00 | 0.59 |
May | 0.914655E+09 | 20937162.92 | 0.00 | 2710789.97 | 0.00 | 267332.74 | 0.111315E+10 | 0.00 | 0.89 |
June | 0.115577E+09 | 0.588600E+09 | 0.00 | 1832328.51 | 6892677.46 | 0.00 | 0.402356E+09 | 0.00 | 0.75 |
July | 7450570.48 | 0.150840E+10 | 0.00 | 145339.66 | 14789727.66 | 0.00 | 10754587.81 | 0.00 | 0.39 |
August | 64413737.76 | 0.137269E+10 | 0.00 | 1771763.22 | 13830597.85 | 0.00 | 0.176432E+09 | 0.00 | 0.75 |
September | 0.326550E+09 | 0.349166E+09 | 0.00 | 2810202.47 | 2851221.37 | 0.00 | 0.814568E+09 | 0.00 | 0.87 |
October | 0.774770E+09 | 33729522.10 | 0.00 | 3174581.74 | 0.00 | 0.00 | 0.125917E+10 | 0.00 | 0.87 |
November | 0.149715E+10 | 0.00 | 0.00 | 288192.85 | 0.00 | 0.355469E+09 | 0.222784E+09 | 0.00 | 0.44 |
December | 0.114679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106508E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.931930E+10 | 0.387444E+10 | 0.00 | 14433118.16 | 38736044.76 | 0.523800E+10 | 0.485034E+10 | 0.00 | 0.58 |
Minimum of Months | 7450570.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.167620E+10 | 0.150840E+10 | 0.00 | 3174581.74 | 14789727.66 | 0.169468E+10 | 0.125917E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.617847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238233E+10 | 0.00 | 0.00 | 0.28 |
February | 0.742734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216398E+10 | 0.00 | 0.00 | 0.29 |
March | 0.216000E+10 | 0.00 | 0.00 | 20249.40 | 0.00 | 0.683434E+09 | 27872836.48 | 0.00 | 0.33 |
April | 0.177907E+10 | 1289514.56 | 0.00 | 1087920.97 | 0.00 | 91629590.43 | 0.533332E+09 | 0.00 | 0.43 |
May | 0.890556E+09 | 28369847.34 | 0.00 | 4133175.21 | 0.00 | 0.00 | 0.169159E+10 | 0.00 | 0.73 |
June | 94229598.45 | 0.842151E+09 | 0.00 | 2665885.33 | 8368676.66 | 0.00 | 0.571553E+09 | 0.00 | 0.64 |
July | 4586755.18 | 0.227304E+10 | 0.00 | 236674.41 | 22119379.60 | 0.00 | 23234661.15 | 0.00 | 0.38 |
August | 65396417.81 | 0.180409E+10 | 0.00 | 2115689.68 | 18604571.53 | 0.00 | 0.234557E+09 | 0.00 | 0.59 |
September | 0.452284E+09 | 0.450118E+09 | 0.00 | 2486576.81 | 4703481.75 | 0.00 | 0.757225E+09 | 0.00 | 0.61 |
October | 0.119612E+10 | 34947466.70 | 0.00 | 1890959.67 | 1299850.47 | 544382.32 | 0.764797E+09 | 0.00 | 0.53 |
November | 0.172002E+10 | 0.00 | 0.00 | 52238.67 | 0.00 | 0.669241E+09 | 82659626.21 | 0.00 | 0.33 |
December | 0.108550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165491E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.108083E+11 | 0.543400E+10 | 0.00 | 14689370.15 | 55095960.01 | 0.764607E+10 | 0.468682E+10 | 0.00 | 0.45 |
Minimum of Months | 4586755.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.216000E+10 | 0.227304E+10 | 0.00 | 4133175.21 | 22119379.60 | 0.238233E+10 | 0.169159E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.863683E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178660E+10 | 0.00 | 0.00 | 0.40 |
February | 0.109586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147928E+10 | 0.00 | 0.00 | 0.40 |
March | 0.192136E+10 | 0.00 | 0.00 | 395320.38 | 0.00 | 0.410507E+09 | 0.333229E+09 | 0.00 | 0.49 |
April | 0.137806E+10 | 1806085.12 | 0.00 | 2133516.45 | 0.00 | 72970645.81 | 0.105358E+10 | 0.00 | 0.73 |
May | 0.816566E+09 | 26336403.06 | 0.00 | 4729914.29 | 0.00 | 0.00 | 0.195032E+10 | 0.00 | 1.18 |
June | 83396721.41 | 0.670418E+09 | 0.00 | 2785254.83 | 9957392.99 | 0.00 | 0.647664E+09 | 0.00 | 0.91 |
July | 3457048.76 | 0.183380E+10 | 0.00 | 272477.13 | 20099436.50 | 0.00 | 31388670.68 | 0.00 | 0.51 |
August | 58006135.83 | 0.155579E+10 | 0.00 | 2351312.47 | 16905600.91 | 0.00 | 0.290811E+09 | 0.00 | 0.89 |
September | 0.362807E+09 | 0.354641E+09 | 0.00 | 3110916.64 | 13917661.77 | 0.00 | 0.922984E+09 | 0.00 | 0.93 |
October | 0.861181E+09 | 29372823.81 | 0.00 | 2775554.65 | 1290464.61 | 2304826.57 | 0.115037E+10 | 0.00 | 0.86 |
November | 0.159978E+10 | 0.00 | 0.00 | 242659.90 | 0.00 | 0.446180E+09 | 0.210204E+09 | 0.00 | 0.48 |
December | 0.120666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127831E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.102508E+11 | 0.447216E+10 | 0.00 | 18796926.74 | 62170556.78 | 0.547615E+10 | 0.659055E+10 | 0.00 | 0.68 |
Minimum of Months | 3457048.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.192136E+10 | 0.183380E+10 | 0.00 | 4729914.29 | 20099436.50 | 0.178660E+10 | 0.195032E+10 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127261E+10 | 0.00 | 0.00 | 1185851.15 | 0.00 | 0.142182E+10 | 0.700658E+09 | 0.00 | 0.32 |
February | 0.139113E+10 | 0.00 | 0.00 | 1725261.67 | 0.00 | 0.115024E+10 | 0.967370E+09 | 0.00 | 0.35 |
March | 0.185724E+10 | 0.00 | 0.00 | 4124928.32 | 0.00 | 0.351046E+09 | 0.197971E+10 | 0.00 | 0.51 |
April | 0.148221E+10 | 3356686.08 | 0.00 | 4224231.98 | 0.00 | 78714747.43 | 0.191867E+10 | 0.00 | 0.69 |
May | 0.925058E+09 | 36682754.09 | 0.00 | 5852968.42 | 0.00 | 0.00 | 0.235431E+10 | 0.00 | 0.94 |
June | 0.128227E+09 | 0.959277E+09 | 0.00 | 2966054.60 | 9004046.84 | 0.00 | 0.635727E+09 | 0.00 | 0.73 |
July | 7672700.88 | 0.261321E+10 | 0.00 | 254107.51 | 24013525.77 | 0.00 | 20195464.07 | 0.00 | 0.43 |
August | 70914615.12 | 0.239384E+10 | 0.00 | 3168669.78 | 19937783.05 | 0.00 | 0.318110E+09 | 0.00 | 0.81 |
September | 0.343892E+09 | 0.665652E+09 | 0.00 | 6651505.61 | 5701212.21 | 0.00 | 0.173832E+10 | 0.00 | 1.05 |
October | 0.704119E+09 | 94194201.42 | 0.00 | 9217237.81 | 1709.74 | 333373.82 | 0.353722E+10 | 0.00 | 1.18 |
November | 0.146050E+10 | 0.00 | 0.00 | 3669547.54 | 0.00 | 0.358580E+09 | 0.182769E+10 | 0.00 | 0.54 |
December | 0.144929E+10 | 0.00 | 0.00 | 1672665.31 | 0.00 | 0.995630E+09 | 0.883465E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.110929E+11 | 0.676621E+10 | 0.00 | 44713029.69 | 58658277.61 | 0.435637E+10 | 0.168814E+11 | 0.00 | 0.66 |
Minimum of Months | 7672700.88 | 0.00 | 0.00 | 254107.51 | 0.00 | 0.00 | 20195464.07 | 0.00 | 0.32 |
Maximum of Months | 0.185724E+10 | 0.261321E+10 | 0.00 | 9217237.81 | 24013525.77 | 0.142182E+10 | 0.353722E+10 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.847227E+09 | 0.00 | 0.00 | 4707.09 | 0.00 | 0.188111E+10 | 13895280.31 | 0.00 | 0.41 |
February | 0.948936E+09 | 0.00 | 0.00 | 76645.95 | 0.00 | 0.163907E+10 | 82655267.65 | 0.00 | 0.42 |
March | 0.187731E+10 | 0.00 | 0.00 | 990990.51 | 0.00 | 0.442241E+09 | 0.540934E+09 | 0.00 | 0.53 |
April | 0.149790E+10 | 1148017.86 | 0.00 | 2343847.19 | 14220.44 | 92903536.22 | 0.103699E+10 | 0.00 | 0.78 |
May | 0.881951E+09 | 28383747.49 | 0.00 | 4311532.18 | 0.00 | 318768.84 | 0.174156E+10 | 0.00 | 1.16 |
June | 0.124238E+09 | 0.737026E+09 | 0.00 | 2272110.23 | 6869478.93 | 0.00 | 0.481197E+09 | 0.00 | 0.92 |
July | 7977117.64 | 0.193158E+10 | 0.00 | 176334.47 | 10822701.46 | 0.00 | 12130020.52 | 0.00 | 0.50 |
August | 73027041.17 | 0.168389E+10 | 0.00 | 1878830.46 | 16043320.61 | 0.00 | 0.181047E+09 | 0.00 | 0.88 |
September | 0.433268E+09 | 0.408974E+09 | 0.00 | 2727458.32 | 7182090.43 | 0.00 | 0.760298E+09 | 0.00 | 0.93 |
October | 0.105905E+10 | 44947233.08 | 0.00 | 2581348.93 | 103756.72 | 2168199.54 | 0.104154E+10 | 0.00 | 0.91 |
November | 0.157755E+10 | 0.00 | 0.00 | 288722.12 | 0.00 | 0.571347E+09 | 0.212041E+09 | 0.00 | 0.51 |
December | 0.118124E+10 | 0.00 | 0.00 | 869.00 | 0.00 | 0.137840E+10 | 6008890.69 | 0.00 | 0.41 |
Annual Sum or Average | 0.105097E+11 | 0.483595E+10 | 0.00 | 17653396.45 | 41035568.60 | 0.600757E+10 | 0.611030E+10 | 0.00 | 0.70 |
Minimum of Months | 7977117.64 | 0.00 | 0.00 | 869.00 | 0.00 | 0.00 | 6008890.69 | 0.00 | 0.41 |
Maximum of Months | 0.187731E+10 | 0.193158E+10 | 0.00 | 4311532.18 | 16043320.61 | 0.188111E+10 | 0.174156E+10 | 0.00 | 1.16 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:16
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.137846E+12 | 0.282240E+11 | 0.00 | 0.133215E+12 | 0.759909E+10 |
February | 0.211725E+12 | 0.262987E+11 | 0.00 | 0.137504E+12 | 0.757203E+10 |
March | 0.340508E+12 | 0.224446E+11 | 0.00 | 0.178950E+12 | 0.525588E+10 |
April | 0.358316E+12 | 0.144115E+11 | 0.00 | 0.194209E+12 | 0.165404E+11 |
May | 0.453404E+12 | 0.818130E+10 | 0.00 | 0.203174E+12 | 0.620007E+11 |
June | 0.435794E+12 | -0.113678E+10 | 0.00 | 0.424432E+11 | 0.212028E+12 |
July | 0.427218E+12 | -0.926308E+10 | 0.00 | -0.427274E+11 | 0.303100E+12 |
August | 0.414747E+12 | -0.588467E+10 | 0.00 | -0.248412E+10 | 0.304351E+12 |
September | 0.296610E+12 | 0.193635E+10 | 0.00 | 0.104850E+12 | 0.151808E+12 |
October | 0.292263E+12 | 0.109625E+11 | 0.00 | 0.207529E+12 | 0.634556E+11 |
November | 0.148080E+12 | 0.209326E+11 | 0.00 | 0.180684E+12 | 0.365934E+10 |
December | 0.111996E+12 | 0.247023E+11 | 0.00 | 0.150043E+12 | 0.533479E+10 |
Annual Sum or Average | 0.362851E+13 | 0.141809E+12 | 0.00 | 0.148739E+13 | 0.114271E+13 |
Minimum of Months | 0.111996E+12 | -0.926308E+10 | 0.00 | -0.427274E+11 | 0.365934E+10 |
Maximum of Months | 0.453404E+12 | 0.282240E+11 | 0.00 | 0.207529E+12 | 0.304351E+12 |