Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 08:35:17
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1584.19 | 317.97 | 317.97 |
Net Site Energy | 1584.19 | 317.97 | 317.97 |
Total Source Energy | 4649.65 | 933.26 | 933.26 |
Net Source Energy | 4649.65 | 933.26 | 933.26 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 127.31 | 67.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 74.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 282.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 77.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 109.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1407.77 | 176.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 127.31 | 67.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 74.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 282.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 72.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 77.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 109.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 127.31 | 67.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 74.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 282.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 72.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 77.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 109.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 71.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 55.93 | 35.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 282.56 | 35.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 71.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 55.93 | 35.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 282.56 | 35.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1407.774 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1407.774 | 100.00 |
Total On-Site and Utility Electric Sources | 1407.774 | 100.00 |
Total Electricity End Uses | 1407.774 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 359.33 |
Time Setpoint Not Met During Occupied Cooling | 45.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1846.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.5763 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 7.5763 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 7.5763 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 07-JAN-07:00 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:20 |
Heating | 184080.49 | 50787.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 9359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21853.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 256.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6282.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7945.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 227390.58 | 58733.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 184080.49 | 50787.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 9359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 16082.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 256.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6282.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 7945.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 403.20 | 73.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 234.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 893.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 228.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2413.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 41.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 244.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 118.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4458.42 | 191.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 80.93 | 14.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 47.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 179.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 49.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 894.87 | 38.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 80.93 | 14.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 47.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 179.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 49.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 894.87 | 38.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.84 | 0.264295 | 0.275000 | 0.779811 | 0.704786 | 0.500000 | 0.001442 |
CORE_MID VAV BOX COMPONENT | 2.05 | 0.364747 | 0.366000 | 0.752029 | 0.972660 | 0.500000 | 0.001045 |
CORE_TOP VAV BOX COMPONENT | 2.14 | 0.349489 | 0.363000 | 0.778427 | 0.931972 | 0.500000 | 0.001090 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.607889 | 0.259902 | 0.270000 | 0.164130 | 0.693072 | 0.500000 | 0.001466 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.747962 | 0.133726 | 0.200000 | 0.149592 | 0.356602 | 0.500000 | 0.002849 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.15 | 0.137112 | 0.200000 | 0.230456 | 0.365633 | 0.500000 | 0.002779 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.835750 | 0.119671 | 0.200000 | 0.167150 | 0.319123 | 0.500000 | 0.003184 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.482740 | 0.327281 | 0.340000 | 0.164131 | 0.872750 | 0.500000 | 0.001164 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.619059 | 0.161571 | 0.200000 | 0.123812 | 0.430855 | 0.500000 | 0.002358 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.935858 | 0.168820 | 0.200000 | 0.187172 | 0.450187 | 0.500000 | 0.002257 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.695918 | 0.143717 | 0.200000 | 0.139184 | 0.383245 | 0.500000 | 0.002651 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.533146 | 0.296338 | 0.297000 | 0.158344 | 0.790236 | 0.500000 | 0.001286 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.743499 | 0.134528 | 0.200000 | 0.148700 | 0.358743 | 0.500000 | 0.002832 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.06 | 0.149501 | 0.200000 | 0.211359 | 0.398669 | 0.500000 | 0.002548 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.771225 | 0.129684 | 0.200000 | 0.154245 | 0.345823 | 0.500000 | 0.002938 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25673.38 |
CORE_MID VAV BOX REHEAT COIL | 24758.70 |
CORE_TOP VAV BOX REHEAT COIL | 32642.03 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 15348.65 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 10040.94 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 15260.16 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 9989.58 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 11135.56 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7386.24 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 11059.21 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7335.91 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 11908.38 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 7837.05 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 11828.79 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 7793.15 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.78 | 1.39 | 5.57 | 1.55 | 4.93 | 4.93 | 0.300000 | 0.313662 | 4.93 |
PACU_VAV_MID | 2.58 | 1.42 | 5.16 | 1.76 | 4.35 | 4.35 | 0.300000 | 0.405232 | 4.35 |
PACU_VAV_TOP | 2.74 | 1.49 | 5.49 | 2.53 | 4.95 | 4.95 | 0.300000 | 0.510958 | 4.95 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.93 |
PACU_VAV_MID_OA_CONTROLLER | 4.35 |
PACU_VAV_TOP_OA_CONTROLLER | 4.95 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.93 | 86602.22 | 0.800382 | 1.64 | 28864.52 | 0.800382 |
PACU_VAV_MID COOLING COIL | 4.35 | 77593.70 | 0.800481 | 1.45 | 25861.98 | 0.800481 |
PACU_VAV_TOP COOLING COIL | 4.95 | 86966.28 | 0.800457 | 1.65 | 28985.86 | 0.800457 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 21755.08 |
PACU_VAV_MID HEATING COIL | 23384.09 |
PACU_VAV_TOP HEATING COIL | 22495.19 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.93 |
PACU_VAV_MID FAN | 4.35 |
PACU_VAV_TOP FAN | 4.95 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 32.411 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9320 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9163 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.269 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8390 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8573 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5538 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.27971961E-12 | 0.14534712E-14 | -0.84678956E-13 | 0.82684317E-16 |
43 | 6 | 0.26817376E-07 | 0.25687399E-09 | 0.61588016E-08 | -0.12527087E-12 |
44 | 5 | -0.18065003E-03 | 0.22251366E-05 | -0.93037841E-04 | 0.60936178E-08 |
45 | 4 | 0.28101542 | 0.10946024E-02 | 0.95683253E-01 | -0.32007147E-04 |
46 | 3 | -7.0457283 | 0.34231649E-01 | -2.2734647 | 0.27928366E-01 |
47 | 2 | 40.143429 | 0.12270019 | 14.996275 | -0.32523640 |
48 | 1 | -79.987958 | 0.55761501E-01 | -28.900564 | 1.0667320 |
49 | 0 | 46.824342 | 0.11295401E-02 | 16.297084 | |
50 | 7 | -0.28233695E-12 | 0.14433069E-14 | -0.85363548E-13 | 0.83491456E-16 |
51 | 6 | 0.27004714E-07 | 0.25312183E-09 | 0.62001510E-08 | -0.12627076E-12 |
52 | 5 | -0.18161011E-03 | 0.21898175E-05 | -0.93520278E-04 | 0.61339935E-08 |
53 | 4 | 0.28215201 | 0.10760039E-02 | 0.96091377E-01 | -0.32166146E-04 |
54 | 3 | -7.0682688 | 0.33616209E-01 | -2.2801509 | 0.28038740E-01 |
55 | 2 | 40.217804 | 0.12038787 | 15.023777 | -0.32606455 |
56 | 1 | -80.044990 | 0.54668782E-01 | -28.925243 | 1.0679473 |
57 | 0 | 46.824342 | 0.11065724E-02 | 16.296477 | |
58 | 6 | 0.22748378E-07 | 0.33059726E-09 | 0.52605359E-08 | -0.10371465E-12 |
59 | 5 | -0.15952455E-03 | 0.29533519E-05 | -0.82380770E-04 | 0.52144884E-08 |
60 | 4 | 0.25560578 | 0.14926938E-02 | 0.86578981E-01 | -0.28493712E-04 |
61 | 3 | -6.5408460 | 0.47808585E-01 | -2.1237636 | 0.25458881E-01 |
62 | 2 | 38.476406 | 0.17496760 | 14.378110 | -0.30668036 |
63 | 1 | -78.708466 | 0.80951212E-01 | -28.345189 | 1.0394692 |
64 | 0 | 46.824351 | 0.16689207E-02 | 16.311239 | |
65 | 7 | -0.18042418E-08 | -0.42925973E-15 | 0.63337540E-14 | -0.83764910E-16 |
66 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
67 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
68 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
69 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
70 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
71 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
72 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
73 | 7 | -0.17078159E-08 | -0.36552483E-15 | 0.71259391E-14 | -0.98899249E-16 |
74 | 6 | 0.68798867E-05 | 0.47165251E-08 | 0.31862110E-02 | -0.26728608E-04 |
75 | 5 | -0.49558197E-03 | 0.27953368E-05 | -0.22351660 | 0.19543146E-02 |
76 | 4 | 0.11404824E-01 | 0.12725100E-03 | 4.8260817 | -0.45231683E-01 |
77 | 3 | -0.10016651 | 0.10121065E-02 | -38.001848 | 0.39843745 |
78 | 2 | 0.35569192 | 0.16837830E-02 | 116.44586 | -1.4174299 |
79 | 1 | -0.51340120 | 0.51323984E-03 | -143.88489 | 2.0486714 |
80 | 0 | 0.25031121 | 0.12359947E-04 | 60.838472 | |
81 | 7 | -0.18042418E-08 | -0.42925997E-15 | 0.63337541E-14 | -0.83764912E-16 |
82 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
83 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
84 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
85 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
86 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
87 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
88 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
89 | 7 | -0.17076967E-08 | -0.36446083E-15 | 0.71390403E-14 | -0.94439575E-16 |
90 | 6 | 0.68803475E-05 | 0.47168467E-08 | 0.31862096E-02 | -0.26728597E-04 |
91 | 5 | -0.49561596E-03 | 0.27955299E-05 | -0.22351653 | 0.19543140E-02 |
92 | 4 | 0.11405612E-01 | 0.12725979E-03 | 4.8260805 | -0.45231671E-01 |
93 | 3 | -0.10017344 | 0.10121766E-02 | -38.001841 | 0.39843738 |
94 | 2 | 0.35571654 | 0.16838995E-02 | 116.44585 | -1.4174297 |
95 | 1 | -0.51343675 | 0.51327568E-03 | -143.88488 | 2.0486713 |
96 | 0 | 0.25032854 | 0.12360692E-04 | 60.838472 | |
97 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
98 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
99 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
100 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
101 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
102 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
103 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
104 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
105 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3822_SHGC_EAST_0.36 | 35 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.361 | ||
2 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 36 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.361 | ||
3 | WINDOW_U_0.3822_SHGC_WEST_0.36 | 37 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.361 | ||
4 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 38 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.43662E-002 | 0.27318 | 0.51756 | 0.51756 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.43662E-002 | 0.27318 | 0.51756 | 0.51756 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.43662E-002 | 0.27318 | 0.51756 | 0.51756 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.43662E-002 | 0.27318 | 0.51756 | 0.51756 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0491E-002 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0552E-002 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1869E-002 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1923E-002 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.3812E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.4232E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4493E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4697E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1354 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.5871E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1557 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1006 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.1817E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1224E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.0047E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5019E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0491E-002 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0555E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1869E-002 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1926E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.3813E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.4248E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4490E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4695E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0859E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6589E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.7637E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4121E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9406E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0214E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6599E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1796E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4454E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.4699E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1734E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.1912E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8470E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8529E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0258E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0328E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9114E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9628E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2579E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2995E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7934E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8231E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4490E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4695E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8311E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2596E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9654E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7280E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8068E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1803E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0047E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5019E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9115E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9632E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2579E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2994E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7932E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8218E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4493E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4697E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8173E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5179E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4170E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2291E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7490E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9277E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6599E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1796E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2996E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3900E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9850E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0910E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7398E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7672E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0259E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0329E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1333 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.8603E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1504 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1143 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.7669E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.1029E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.5023E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.0890E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.8419E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.5229E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.5410E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.2888E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.7628E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9256E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.5485E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1197E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.3079E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.8838E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3908E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2643E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.2305E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6702E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.5023E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0890E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5849E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3906E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.2093E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.1172E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5786E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.8368E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.5485E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1197E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1333 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.8598E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1504 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1143 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.7668E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.1024E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.5020E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.0887E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.8421E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.5228E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.5411E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.2886E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.7626E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9254E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.5481E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1194E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.3082E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.8837E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3909E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2642E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.2304E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6700E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.5020E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0887E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5850E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3905E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.2094E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.1170E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5784E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.8365E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.5482E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1195E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 38795.01048 | 38795.01048 | 2.83568 | 2.83568 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 6546.78038 | 6546.78038 | 0.27886 | 0.42469 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 28146.26324 | 28146.26324 | 2.05472 | 2.05472 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 13256.75269 | 13256.75269 | 0.56851 | 0.56851 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 29093.80044 | 29093.80044 | 2.14443 | 2.14443 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 29.19200 | 8.82116E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 23008.33932 | 23008.33932 | 0.99148 | 0.99148 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8247.44034 | 8247.44034 | 0.60789 | 0.60789 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 29.29600 | 8.82133E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 10782.36978 | 10782.36978 | 0.46620 | 0.46620 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10147.93261 | 10147.93261 | 0.74796 | 0.74796 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 23.97467 | 8.81286E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 7053.08373 | 7053.08373 | 0.30499 | 0.30499 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 15633.44506 | 15633.44506 | 1.15228 | 1.15228 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.82122E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 10720.39313 | 10720.39313 | 0.46352 | 0.46352 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11338.99348 | 11338.99348 | 0.83575 | 0.83575 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 7017.11369 | 7017.11369 | 0.30343 | 0.30343 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6549.47222 | 6549.47222 | 0.48274 | 0.48274 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.82150E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 7830.53044 | 7830.53044 | 0.33823 | 0.33823 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8399.02965 | 8399.02965 | 0.61906 | 0.61906 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 24.26933 | 8.81333E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 5193.07967 | 5193.07967 | 0.22435 | 0.22435 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 12697.16027 | 12697.16027 | 0.93586 | 0.93586 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 7777.06441 | 7777.06441 | 0.33592 | 0.33592 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9441.81637 | 9441.81637 | 0.69592 | 0.69592 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 26.90400 | 8.81750E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 5157.83279 | 5157.83279 | 0.22282 | 0.22282 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7233.36652 | 7233.36652 | 0.53315 | 0.53315 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.82150E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 8372.44550 | 8372.44550 | 0.36171 | 0.36171 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10087.37628 | 10087.37628 | 0.74350 | 0.74350 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 23.35067 | 8.81188E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5509.22787 | 5509.22787 | 0.23804 | 0.23804 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 14337.96566 | 14337.96566 | 1.05679 | 1.05679 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 8316.71222 | 8316.71222 | 0.35929 | 0.35929 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10463.54268 | 10463.54268 | 0.77122 | 0.77122 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 5478.48728 | 5478.48728 | 0.23671 | 0.23671 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 73530.59 | 4.92892 | 4.92892 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 24000.36 | 1.54602 | 1.54602 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 65844.40 | 4.35373 | 4.35373 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 24078.81 | 1.76427 | 1.76427 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 73756.44 | 4.95073 | 4.95073 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 23969.39 | 2.52961 | 2.52961 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.83568 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26429 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27500 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77981 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70479 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44157E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25673.37594 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.05472 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36475 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36600 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.75203 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97266 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04456E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24758.70421 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.14443 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34949 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36300 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77843 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93197 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09016E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 32642.02966 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.60789 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25990 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16413 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69307 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.46594E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15348.64658 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74796 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13373 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14959 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35660 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.84912E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10040.93768 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.15228 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13711 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23046 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36563 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.77874E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15260.15635 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83575 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11967 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16715 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31912 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.18372E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9989.58106 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.48274 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32728 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16413 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87275 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16414E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11135.55753 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61906 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16157 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12381 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43086 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35810E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7386.23950 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93586 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16882 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18717 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45019 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.25684E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11059.21412 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69592 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14372 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13918 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38325 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.65104E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7335.91294 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.53315 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29634 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29700 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15834 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79024 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.28569E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11908.37620 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74350 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13453 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14870 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35874 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.83211E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7837.04881 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05679 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14950 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21136 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39867 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54848E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11828.79165 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77122 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12968 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15424 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34582 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.93792E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7793.15417 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.78463 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39411 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.56925 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.54602 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.92892 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.92892 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.31366 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.57969 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.42468 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.15939 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.76427 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.35373 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.35373 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.40523 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.74415 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.48976 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.48831 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.52961 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.95073 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.95073 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.51096 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.92892 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.35373 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.95073 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.92892 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.92892 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 86602.22261 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80038 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.64281 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28864.52080 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80038 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 21755.08408 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.92892 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.35373 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.35373 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 77593.70266 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80048 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.45110 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 25861.98110 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80048 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 23384.09256 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.35373 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.95073 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.95073 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 86966.27995 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80046 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.65008 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28985.86111 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80046 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 22495.18658 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.95073 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 85346.11 | 291213.00 | 10.95 | 2.83 | 3.13 | 3.30 | 3.48 | 9.64 | 10.69 | 11.25 | 11.87 | 5.6195 | 4.4566 | 2.9910 | 1.2192 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 76516.56 | 261085.35 | 10.98 | 2.83 | 3.14 | 3.31 | 3.49 | 9.66 | 10.72 | 11.28 | 11.91 | 4.9637 | 3.9412 | 2.6459 | 1.0715 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 85704.04 | 292434.34 | 10.95 | 2.83 | 3.13 | 3.30 | 3.48 | 9.64 | 10.69 | 11.25 | 11.87 | 5.6444 | 4.4763 | 3.0042 | 1.2246 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.36 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.36 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.36 | N/A | 2.171 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.36 | N/A | 2.171 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.246 | 0.232 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.36 | N/A | 2.171 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.36 | N/A | 2.171 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.246 | 0.232 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.36 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.36 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 8.0024751457E-002 | 5.4271050319E-002 | Pass | Pass | 0.3126704481 | 0.4473485578 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1228215150 | 7.5401103573E-002 | Pass | Pass | 0.4546312216 | 0.4749418354 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.1789032718E-002 | 4.2572398145E-002 | Pass | Pass | 0.3778706954 | 0.4485116991 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.0499477418E-002 | 4.7241359315E-002 | Pass | Pass | 0.2950640827 | 0.4147281572 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.7637993907E-002 | 1.6929125174E-002 | Pass | Pass | 0.5754975946 | 1.0001321340 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.0538346642E-002 | 1.0131543933E-002 | Pass | Pass | 9.7242112649 | 23.0832010262 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2550079814 | 0.2389154827 | Pass | Pass | 16.6830831649 | 33.8453508897 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2607742551 | 0.2491183199 | Pass | Pass | 12.9877345658 | 26.2377989585 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2448971237 | 0.2356259276 | Pass | Pass | 12.9814291660 | 25.9218536632 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2631577592 | 0.2517568345 | Pass | Pass | 12.1322425619 | 24.4904108479 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1278732983 | 0.1420084130 | Pass | Pass | 2.5831290744 | 6.8900031634 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1408380904 | 0.1581513398 | Pass | Pass | 1.9795723246 | 4.1073439322 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1229056010 | 0.1358681525 | Pass | Pass | 3.2078421073 | 11.8945710770 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1428462676 | 0.1605323485 | Pass | Pass | 1.8714016573 | 3.7160262083 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1502498341 | 0.1636979996 | Pass | Pass | 6.0867019690 | 17.6262441577 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1581702617 | 0.1743586485 | Pass | Pass | 4.9774811014 | 14.2422522957 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1451405615 | 0.1595861365 | Pass | Pass | 5.2870308030 | 14.8236767063 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1601523695 | 0.1767779597 | Pass | Pass | 4.8310640677 | 13.8285459933 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3081.38 | 141.44 | 0.00 | 2319.21 | 386.82 | 5928.85 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.36 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.36 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3822_SHGC_EAST_0.36 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3822_SHGC_EAST_0.36 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3822_SHGC_WEST_0.36 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3822_SHGC_WEST_0.36 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.36 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.36 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.171 | 0.361 | 0.361 | |||||||||||||||||
North Total or Average | 177.99 | 2.171 | 0.361 | 0.361 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.171 | 0.361 | 0.361 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.87 | 0.0000 | Y | 9.40 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.73 | 0.0000 | Y | 5.92 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.56 | 0.0000 | Y | 9.30 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.69 | 0.0000 | Y | 5.92 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.81 | 0.0000 | Y | 9.38 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.69 | 0.0000 | Y | 5.92 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.51 | 0.0000 | Y | 9.29 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.65 | 0.0000 | Y | 5.91 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.87 | 0.0000 | Y | 9.40 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.73 | 0.0000 | Y | 5.92 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.56 | 0.0000 | Y | 9.30 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.69 | 0.0000 | Y | 5.92 |
Interior Lighting Total | 7.5763 | 4982.19 | 37746.71 | 282.03 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 42.59 | 42.59 | 3.40 | |
EXTERIOR_LIGHTS_B | 5132.60 | AstronomicalClock | - | 83.55 | 71.26 | 68.66 | |
Exterior Lighting Total | 5557.43 | 72.05 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 86602.22 | 69314.82 | 17287.40 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 77593.70 | 62112.31 | 15481.39 | 0.80 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 86966.28 | 69612.81 | 17353.47 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 85346.1 | 2.83 | 9.64 | N/A | N/A | 10.95 | |
PACU_VAV_MID COOLING COIL | 76516.6 | 2.83 | 9.66 | N/A | N/A | 10.98 | |
PACU_VAV_TOP COOLING COIL | 85704.0 | 2.83 | 9.64 | N/A | N/A | 10.95 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25673.38 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 24758.70 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 32642.03 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15348.65 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10040.94 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15260.16 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9989.58 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11135.56 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7386.24 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11059.21 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7335.91 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11908.38 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7837.05 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11828.79 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7793.15 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 21755.08 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 23384.09 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 22495.19 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.93 | 10789.46 | 2189.01 | 1.00 | 1.13 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.35 | 9530.36 | 2189.01 | 1.00 | 1.14 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.95 | 10837.19 | 2189.01 | 1.00 | 1.13 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 85346.11 | 2.83 | 9.64 | 10.95 | 5.6195 | 3.13 | 10.69 | 4.4566 | 3.30 | 11.25 | 2.9910 | 3.48 | 11.87 | 1.2192 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 76516.56 | 2.83 | 9.66 | 10.98 | 4.9637 | 3.14 | 10.72 | 3.9412 | 3.31 | 11.28 | 2.6459 | 3.49 | 11.91 | 1.0715 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 85704.04 | 2.83 | 9.64 | 10.95 | 5.6444 | 3.13 | 10.69 | 4.4763 | 3.30 | 11.25 | 3.0042 | 3.48 | 11.87 | 1.2246 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 38795.01 | 38795.01 | 39.44 | 2.836 | 2.836 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00882 | 21.70 | 0.00881 | 0.425 | 0.00 |
CORE_MID | 28146.26 | 28146.26 | 28.62 | 2.055 | 2.055 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 21.70 | 0.00881 | 0.425 | 0.00 |
CORE_TOP | 29093.80 | 29093.80 | 29.58 | 2.144 | 2.144 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00891 | 29.19 | 0.00882 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8247.44 | 8247.44 | 39.78 | 0.608 | 0.608 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00881 | 29.30 | 0.00882 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10147.93 | 10147.93 | 77.31 | 0.748 | 0.748 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00866 | 23.97 | 0.00881 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15633.45 | 15633.45 | 75.40 | 1.152 | 1.152 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00867 | 29.23 | 0.00882 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11338.99 | 11338.99 | 86.39 | 0.836 | 0.836 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00865 | 27.94 | 0.00882 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6549.47 | 6549.47 | 31.59 | 0.483 | 0.483 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00888 | 29.40 | 0.00882 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8399.03 | 8399.03 | 63.99 | 0.619 | 0.619 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 24.00 | 24.00 | 0.00869 | 24.27 | 0.00881 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12697.16 | 12697.16 | 61.24 | 0.936 | 0.936 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00870 | 29.31 | 0.00882 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9441.82 | 9441.82 | 71.94 | 0.696 | 0.696 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.00 | 24.00 | 0.00867 | 26.90 | 0.00882 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7233.37 | 7233.37 | 34.89 | 0.533 | 0.533 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00885 | 29.40 | 0.00882 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10087.38 | 10087.38 | 76.85 | 0.743 | 0.743 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00866 | 23.35 | 0.00881 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 14337.97 | 14337.97 | 69.15 | 1.057 | 1.057 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00868 | 29.14 | 0.00882 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10463.54 | 10463.54 | 79.72 | 0.771 | 0.771 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00866 | 27.94 | 0.00882 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 6546.78 | 6546.78 | 6.66 | 0.279 | 0.425 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
CORE_MID | 13256.75 | 13256.75 | 13.48 | 0.569 | 0.569 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
CORE_TOP | 23008.34 | 23008.34 | 23.39 | 0.991 | 0.991 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10782.37 | 10782.37 | 52.00 | 0.466 | 0.466 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00758 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 7053.08 | 7053.08 | 53.73 | 0.305 | 0.305 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00758 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10720.39 | 10720.39 | 51.70 | 0.464 | 0.464 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00758 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 7017.11 | 7017.11 | 53.46 | 0.303 | 0.303 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00758 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7830.53 | 7830.53 | 37.77 | 0.338 | 0.338 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 5193.08 | 5193.08 | 39.56 | 0.224 | 0.224 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00755 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 7777.06 | 7777.06 | 37.51 | 0.336 | 0.336 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 5157.83 | 5157.83 | 39.30 | 0.223 | 0.223 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8372.45 | 8372.45 | 40.38 | 0.362 | 0.362 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00747 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 5509.23 | 5509.23 | 41.97 | 0.238 | 0.238 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00748 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 8316.71 | 8316.71 | 40.11 | 0.359 | 0.359 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00746 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 5478.49 | 5478.49 | 41.74 | 0.237 | 0.237 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00748 | -4.20 | 0.00269 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.93 | 4.93 | 1.55 | 1.55 | 4.9289 | 1.5460 | 4.9289 | 0.3137 | 0.3000 |
PACU_VAV_MID | 4.35 | 4.35 | 1.76 | 1.76 | 4.3537 | 1.7643 | 4.3537 | 0.4052 | 0.3000 |
PACU_VAV_TOP | 4.95 | 4.95 | 2.53 | 2.53 | 4.9507 | 2.5296 | 4.9507 | 0.5110 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25673.376 | 25673.376 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25673.38 | 13981.92 | 0.424691 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 6546.78 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 24758.704 | 24758.704 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24758.70 | 18716.94 | 0.568514 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 13256.75 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 32642.030 | 32642.030 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 32642.03 | 32642.03 | 0.991479 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 23008.34 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 15348.647 | 15348.647 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15348.65 | 15348.65 | 0.466205 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00758409 | 48.3667 | 10782.37 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 10040.938 | 10040.938 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10040.94 | 10040.94 | 0.304987 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00758039 | 48.3436 | 7053.08 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 15260.156 | 15260.156 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15260.16 | 15260.16 | 0.463517 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00758120 | 48.3485 | 10720.39 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 9989.581 | 9989.581 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9989.58 | 9989.58 | 0.303427 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00757787 | 48.3277 | 7017.11 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 11135.558 | 11135.558 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11135.56 | 11135.56 | 0.338235 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00752766 | 48.0110 | 7830.53 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 7386.239 | 7386.239 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7386.24 | 7386.24 | 0.224352 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00754852 | 48.1424 | 5193.08 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 11059.214 | 11059.214 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11059.21 | 11059.21 | 0.335916 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00752125 | 47.9707 | 7777.06 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 7335.913 | 7335.913 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7335.91 | 7335.91 | 0.222823 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00754256 | 48.1049 | 5157.83 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 11908.376 | 11908.376 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11908.38 | 11908.38 | 0.361709 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00746841 | 47.6383 | 8372.45 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 7837.049 | 7837.049 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7837.05 | 7837.05 | 0.238045 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00748175 | 47.7223 | 5509.23 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 11828.792 | 11828.792 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11828.79 | 11828.79 | 0.359291 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00746141 | 47.5942 | 8316.71 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 7793.154 | 7793.154 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7793.15 | 7793.15 | 0.236712 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00747641 | 47.6887 | 5478.49 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 86602.223 | 69314.821 | 4.928921 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 87572.96 | 82995.92 | 4.928921 | 25.31 | 16.96 | 0.00880766 | 10.99 | 10.99 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 24.2481 | 24.00 | 0.00880322 | 46.6934 | 66864.89 | 0.00 | 89298.52 | 69750.93 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 21755.084 | 21755.084 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21755.08 | 21755.08 | 1.478676 | 0.47 | -0.08 | 0.00361125 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 80.8270 | 20.73 | 0.00730328 | 47.3749 | 21703.29 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 77593.703 | 62112.310 | 4.353730 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 78578.53 | 74144.67 | 4.353730 | 25.48 | 17.04 | 0.00883772 | 10.99 | 10.99 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 27.4516 | 24.00 | 0.00884385 | 46.9059 | 59057.99 | 0.00 | 80009.52 | 62517.96 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 23384.093 | 23384.093 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 23384.09 | 23384.09 | 1.306119 | -2.21 | -2.37 | 0.00308376 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 91.5054 | 19.60 | 0.00718873 | 50.0217 | 25641.53 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 86966.280 | 69612.811 | 4.950726 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 87939.09 | 83338.10 | 4.950726 | 25.30 | 16.96 | 0.00880790 | 10.99 | 10.99 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 24.1413 | 24.00 | 0.00880356 | 46.6952 | 67094.31 | 0.00 | 89673.91 | 70050.51 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 22495.187 | 22495.187 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22495.19 | 22495.19 | 1.485218 | 0.10 | -0.25 | 0.00362514 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 80.4710 | 19.38 | 0.00742257 | 52.3180 | 29947.13 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25673.376 | 25673.376 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25673.38 | 13981.92 | 1.0000 | 0.50410441 | 0.424691 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25673.38 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.61 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 6546.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 24758.704 | 24758.704 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 24758.70 | 18716.94 | 1.0000 | 0.67482094 | 0.568514 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24758.70 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 13256.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 32642.030 | 32642.030 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 32642.03 | 32642.03 | 1.0000 | 1.17687650 | 0.991479 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32642.03 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 23008.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 15348.647 | 15348.647 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15348.65 | 15348.65 | 1.0000 | 0.55338046 | 0.466205 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15348.65 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00758409 | 21.00 | 0.00758409 | 48.3667 | 10782.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10040.938 | 10040.938 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10040.94 | 10040.94 | 1.0000 | 0.36201620 | 0.304987 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10040.94 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00758039 | 21.00 | 0.00758039 | 48.3436 | 7053.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 15260.156 | 15260.156 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15260.16 | 15260.16 | 1.0000 | 0.55019003 | 0.463517 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15260.16 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00758120 | 21.00 | 0.00758120 | 48.3485 | 10720.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9989.581 | 9989.581 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9989.58 | 9989.58 | 1.0000 | 0.36016459 | 0.303427 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9989.58 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00757787 | 21.00 | 0.00757787 | 48.3277 | 7017.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 11135.558 | 11135.558 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11135.56 | 11135.56 | 1.0000 | 0.40148165 | 0.338235 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11135.56 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00752766 | 21.00 | 0.00752766 | 48.0110 | 7830.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7386.239 | 7386.239 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7386.24 | 7386.24 | 1.0000 | 0.26630365 | 0.224352 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7386.24 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00754852 | 21.00 | 0.00754852 | 48.1424 | 5193.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 11059.214 | 11059.214 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11059.21 | 11059.21 | 1.0000 | 0.39872916 | 0.335916 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11059.21 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00752125 | 21.00 | 0.00752125 | 47.9707 | 7777.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7335.913 | 7335.913 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7335.91 | 7335.91 | 1.0000 | 0.26448918 | 0.222823 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7335.91 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00754256 | 21.00 | 0.00754256 | 48.1049 | 5157.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 11908.376 | 11908.376 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11908.38 | 11908.38 | 1.0000 | 0.42934487 | 0.361709 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11908.38 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00746841 | 21.00 | 0.00746841 | 47.6383 | 8372.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7837.049 | 7837.049 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7837.05 | 7837.05 | 1.0000 | 0.28255714 | 0.238045 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7837.05 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00748175 | 21.00 | 0.00748175 | 47.7223 | 5509.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 11828.792 | 11828.792 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11828.79 | 11828.79 | 1.0000 | 0.42647553 | 0.359291 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11828.79 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00746141 | 21.00 | 0.00746141 | 47.5942 | 8316.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7793.154 | 7793.154 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7793.15 | 7793.15 | 1.0000 | 0.28097456 | 0.236712 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7793.15 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00747641 | 21.00 | 0.00747641 | 47.6887 | 5478.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 86602.223 | 69314.821 | 4.928921 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2130 | 1004.8586 | 1.1870 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.928921 | 5.85058359 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 87572.96 | 82995.92 | 1.0112 | 5.85058359 | 4.928921 | 25.31 | 16.96 | 0.00880766 | 47872.9 | 10.99 | 10.99 | 0.00850000 | 32479.1 | -999.0 | -999.00 | -999.00 | -999.00 | 10789.462 | 76783.50 | 29.40 | 0.00882150 | 18.34 | 1.19517000 | 24.2481 | 24.00 | 0.00880322 | 24.00 | 0.00880322 | 46.6934 | 66864.89 | 0.00 | 89298.52 | 69750.93 | 5.61952976 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.53 | 14.07 | 0.00982082 | 39431.6 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 21755.084 | 21755.084 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.928921 | 5.85058359 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21755.08 | 21755.08 | 1.0000 | 1.75517508 | 1.478676 | 0.47 | -0.08 | 0.00361125 | 9502.0 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21755.08 | -4.20 | 0.00269032 | -4.20 | 1.19517000 | 80.8270 | 20.13 | 0.00749362 | 20.73 | 0.00730328 | 47.3749 | 21703.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 77593.703 | 62112.310 | 4.353730 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2689 | 1004.8586 | 1.1870 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.353730 | 5.16783723 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 78578.53 | 74144.67 | 1.0127 | 5.16783723 | 4.353730 | 25.48 | 17.04 | 0.00883772 | 48126.4 | 10.99 | 10.99 | 0.00850000 | 32479.2 | -999.0 | -999.00 | -999.00 | -999.00 | 9530.363 | 69048.17 | 29.40 | 0.00882150 | 18.34 | 1.19517000 | 27.4516 | 24.00 | 0.00884385 | 24.00 | 0.00884385 | 46.9059 | 59057.99 | 0.00 | 80009.52 | 62517.96 | 4.96374672 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.36 | 13.98 | 0.00980303 | 39203.6 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23384.093 | 23384.093 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.353730 | 5.16783723 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 23384.09 | 23384.09 | 1.0000 | 1.55035117 | 1.306119 | -2.21 | -2.37 | 0.00308376 | 5478.8 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23384.09 | -4.20 | 0.00269032 | -4.20 | 1.19517000 | 91.5054 | 19.22 | 0.00732201 | 19.60 | 0.00718873 | 50.0217 | 25641.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 86966.280 | 69612.811 | 4.950726 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2134 | 1004.8586 | 1.1870 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.950726 | 5.87646636 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 87939.09 | 83338.10 | 1.0112 | 5.87646636 | 4.950726 | 25.30 | 16.96 | 0.00880790 | 47869.0 | 10.99 | 10.99 | 0.00850000 | 32479.1 | -999.0 | -999.00 | -999.00 | -999.00 | 10837.194 | 77101.90 | 29.40 | 0.00882150 | 18.34 | 1.19517000 | 24.1413 | 24.00 | 0.00880356 | 24.00 | 0.00880356 | 46.6952 | 67094.31 | 0.00 | 89673.91 | 70050.51 | 5.64439036 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.54 | 14.07 | 0.00982156 | 39435.1 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22495.187 | 22495.187 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.950726 | 5.87646636 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 22495.19 | 22495.19 | 1.0000 | 1.76293991 | 1.485218 | 0.10 | -0.25 | 0.00362514 | 9169.1 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22495.19 | -4.20 | 0.00269032 | -4.20 | 1.19517000 | 80.4710 | 17.83 | 0.00747718 | 19.38 | 0.00742257 | 52.3180 | 29947.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.93 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.35 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.95 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1743.17 | 2437.50 | 33.33 |
CORE_MID | 1192.83 | 3584.83 | 195.50 |
CORE_TOP | 1480.83 | 4145.17 | 716.00 |
PERIMETER_TOP_ZN_3 | 2316.33 | 4499.17 | 1605.50 |
PERIMETER_TOP_ZN_2 | 2626.50 | 4198.33 | 1511.17 |
PERIMETER_TOP_ZN_1 | 2489.67 | 4064.50 | 1288.67 |
PERIMETER_TOP_ZN_4 | 2580.00 | 4458.00 | 1585.17 |
PERIMETER_BOT_ZN_3 | 1662.17 | 4607.67 | 1128.50 |
PERIMETER_BOT_ZN_2 | 2155.67 | 3997.17 | 1000.17 |
PERIMETER_BOT_ZN_1 | 2098.17 | 4360.50 | 1073.00 |
PERIMETER_BOT_ZN_4 | 2151.67 | 4134.83 | 1052.50 |
PERIMETER_MID_ZN_3 | 1865.00 | 4167.17 | 1049.00 |
PERIMETER_MID_ZN_2 | 1886.67 | 3482.50 | 950.67 |
PERIMETER_MID_ZN_1 | 2169.33 | 3699.17 | 799.67 |
PERIMETER_MID_ZN_4 | 2194.33 | 4147.50 | 1040.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4115.50 | 5008.00 | 1846.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.17 | 0.17 | 0.17 | 0.00 |
CORE_MID | 0.83 | 0.00 | 0.67 | 0.00 |
CORE_TOP | 1.50 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 11.17 | 0.00 | 6.83 | 0.00 |
PERIMETER_TOP_ZN_2 | 7.83 | 7.50 | 1.83 | 7.50 |
PERIMETER_TOP_ZN_1 | 3.17 | 9.17 | 0.17 | 9.00 |
PERIMETER_TOP_ZN_4 | 7.67 | 14.00 | 2.67 | 7.33 |
PERIMETER_BOT_ZN_3 | 3.50 | 0.00 | 3.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.67 | 4.67 | 0.17 | 4.67 |
PERIMETER_BOT_ZN_1 | 353.83 | 5.67 | 353.50 | 5.67 |
PERIMETER_BOT_ZN_4 | 0.83 | 8.83 | 0.33 | 4.17 |
PERIMETER_MID_ZN_3 | 2.17 | 0.00 | 1.67 | 0.00 |
PERIMETER_MID_ZN_2 | 0.67 | 8.00 | 0.17 | 8.00 |
PERIMETER_MID_ZN_1 | 0.67 | 8.83 | 0.17 | 8.83 |
PERIMETER_MID_ZN_4 | 0.83 | 13.67 | 0.33 | 7.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 366.83 | 58.17 | 359.33 | 45.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.63 | 52.94 | 2698.04 | 1.028 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.63 | 52.94 | 2698.04 | 0.713 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.63 | 52.94 | 2698.04 | 0.699 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.56 | 11.16 | 568.77 | 0.739 | 0.079 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.89 | 7.07 | 360.08 | 1.184 | 0.083 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.56 | 11.16 | 568.77 | 1.246 | 0.079 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.89 | 7.06 | 360.05 | 1.265 | 0.083 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.56 | 11.16 | 568.77 | 0.676 | 0.042 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.89 | 7.07 | 360.08 | 1.005 | 0.044 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.56 | 11.16 | 568.77 | 0.958 | 1.323 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.89 | 7.06 | 360.05 | 1.048 | 0.044 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.56 | 11.16 | 568.77 | 0.739 | 0.066 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.53 | 7.07 | 360.08 | 1.090 | 0.073 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.56 | 11.16 | 568.77 | 1.216 | 0.066 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.89 | 7.06 | 360.05 | 1.212 | 0.069 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.63 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.63 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.63 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.56 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.89 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.56 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.89 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.56 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.89 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.56 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.89 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.56 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.53 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.56 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.89 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.63 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.63 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.63 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.56 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.89 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.56 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.89 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.56 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.89 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.56 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.89 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.56 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.53 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.56 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.89 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.20 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 16330079.57 | 0.00 | 16330079.57 | 0.00 | 16330079.57 | 13393058.27 | 5021.58 | 48.06 | 3690.36 | 83.69 |
CORE_MID | 11294158.80 | 0.00 | 11294158.80 | 0.00 | 11294158.80 | 13393058.27 | 5761.20 | 54.54 | 2944.26 | 49.22 |
CORE_TOP | 11091279.24 | 0.00 | 11091279.24 | 0.00 | 11091279.24 | 13393058.27 | 5803.53 | 48.64 | 2907.83 | 61.32 |
PERIMETER_TOP_ZN_3 | 2471035.62 | 0.00 | 2471035.62 | 539250.78 | 3010286.40 | 2823374.22 | 5661.18 | 66.82 | 3032.01 | 61.32 |
PERIMETER_TOP_ZN_2 | 2505504.44 | 0.00 | 2505504.44 | 359498.36 | 2865002.80 | 1787429.43 | 4107.91 | 2.29 | 4649.81 | 61.32 |
PERIMETER_TOP_ZN_1 | 4160724.44 | 0.00 | 4160724.44 | 539250.78 | 4699975.23 | 2823374.22 | 4110.74 | 1.94 | 4647.32 | 61.32 |
PERIMETER_TOP_ZN_4 | 2685781.56 | 0.00 | 2685781.56 | 359498.36 | 3045279.92 | 1787312.18 | 4096.84 | 4.32 | 4658.84 | 61.32 |
PERIMETER_BOT_ZN_3 | 2279854.32 | 0.00 | 2279854.32 | 286716.78 | 2566571.10 | 2823374.22 | 5507.98 | 64.46 | 3187.56 | 83.69 |
PERIMETER_BOT_ZN_2 | 2137110.87 | 0.00 | 2137110.87 | 191143.37 | 2328254.24 | 1787429.43 | 4118.18 | 42.19 | 4599.64 | 83.69 |
PERIMETER_BOT_ZN_1 | 3229867.76 | 0.00 | 3229867.76 | 4572275.41 | 7802143.17 | 2823374.22 | 4156.57 | 46.62 | 4556.81 | 83.69 |
PERIMETER_BOT_ZN_4 | 2236802.22 | 0.00 | 2236802.22 | 191143.37 | 2427945.58 | 1787312.18 | 4069.15 | 8.44 | 4682.40 | 83.69 |
PERIMETER_MID_ZN_3 | 2470527.86 | 0.00 | 2470527.86 | 448884.86 | 2919412.73 | 2823374.22 | 5637.29 | 69.22 | 3053.50 | 49.22 |
PERIMETER_MID_ZN_2 | 2515608.38 | 0.00 | 2515608.38 | 299254.78 | 2814863.16 | 1787429.43 | 4065.43 | 4.18 | 4690.39 | 958.22 |
PERIMETER_MID_ZN_1 | 4055765.58 | 0.00 | 4055765.58 | 448884.86 | 4504650.44 | 2823374.22 | 4083.06 | 4.80 | 4672.14 | 49.22 |
PERIMETER_MID_ZN_4 | 2569700.33 | 0.00 | 2569700.33 | 299254.78 | 2868955.11 | 1787312.18 | 4061.85 | 5.37 | 4692.78 | 49.22 |
Total Facility | 72033801.00 | 0.00 | 72033801.00 | 8535056.49 | 80568857.49 | 67843644.98 | 5941.34 | 319.75 | 4790.59 | 1043.01 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7539 | 0.0000 | 0.7539 | 0.0000 | 0.7539 | 0.4247 | 2274.61 | 48.06 | 3620.33 |
CORE_MID | 0.5234 | 0.0000 | 0.5234 | 0.0000 | 0.5234 | 0.4247 | 2979.17 | 54.54 | 2909.29 |
CORE_TOP | 0.5139 | 0.0000 | 0.5139 | 0.0000 | 0.5139 | 0.4247 | 3017.97 | 48.64 | 2876.38 |
PERIMETER_TOP_ZN_3 | 0.1146 | 0.0000 | 0.1146 | 0.0123 | 0.1268 | 0.0895 | 2875.62 | 66.82 | 3000.56 |
PERIMETER_TOP_ZN_2 | 0.1162 | 0.0000 | 0.1162 | 0.0082 | 0.1244 | 0.0567 | 1322.74 | 2.23 | 4618.03 |
PERIMETER_TOP_ZN_1 | 0.1931 | 0.0000 | 0.1931 | 0.0123 | 0.2054 | 0.0895 | 1325.51 | 1.94 | 4615.55 |
PERIMETER_TOP_ZN_4 | 0.1242 | 0.0000 | 0.1242 | 0.0082 | 0.1324 | 0.0567 | 1311.79 | 4.32 | 4626.90 |
PERIMETER_BOT_ZN_3 | 0.1048 | 0.0000 | 0.1048 | 0.0065 | 0.1113 | 0.0895 | 2761.01 | 64.46 | 3117.53 |
PERIMETER_BOT_ZN_2 | 0.0986 | 0.0000 | 0.0986 | 0.0043 | 0.1029 | 0.0567 | 1371.22 | 42.19 | 4529.59 |
PERIMETER_BOT_ZN_1 | 0.1490 | 0.0000 | 0.1490 | 0.2068 | 0.3558 | 0.0895 | 1409.60 | 46.62 | 4486.78 |
PERIMETER_BOT_ZN_4 | 0.1029 | 0.0000 | 0.1029 | 0.0043 | 0.1072 | 0.0567 | 1322.20 | 8.44 | 4612.36 |
PERIMETER_MID_ZN_3 | 0.1145 | 0.0000 | 0.1145 | 0.0102 | 0.1247 | 0.0895 | 2855.26 | 69.22 | 3018.53 |
PERIMETER_MID_ZN_2 | 0.1070 | 0.0000 | 0.1070 | 0.0072 | 0.1142 | 0.0567 | 1283.42 | 4.18 | 3746.39 |
PERIMETER_MID_ZN_1 | 0.1883 | 0.0000 | 0.1883 | 0.0102 | 0.1985 | 0.0895 | 1301.03 | 4.80 | 4637.17 |
PERIMETER_MID_ZN_4 | 0.1189 | 0.0000 | 0.1189 | 0.0068 | 0.1257 | 0.0567 | 1279.82 | 5.37 | 4657.81 |
Total Facility | 3.3233 | 0.0000 | 3.3233 | 0.2973 | 3.6206 | 2.1513 | 3139.53 | 319.69 | 4704.02 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 36933741.91 | 0.00 | 36933741.91 | 22614548.33 | 4029.21 | 2.38 | 4728.41 | 83.69 |
PACU_VAV_MID | 32273021.70 | 0.00 | 32273021.70 | 22614548.33 | 4050.21 | 7.93 | 4701.85 | 49.22 |
PACU_VAV_TOP | 32285077.52 | 0.00 | 32285077.52 | 22614548.33 | 4096.58 | 2.83 | 4660.59 | 60.99 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.7036 | 0.0000 | 1.7036 | 0.7171 | 1282.24 | 2.38 | 4658.38 |
PACU_VAV_MID | 1.4961 | 0.0000 | 1.4961 | 0.7171 | 1268.19 | 7.93 | 4666.88 |
PACU_VAV_TOP | 1.4964 | 0.0000 | 1.4964 | 0.7171 | 1311.52 | 2.83 | 4628.65 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 3674.84 | 0.00 | 0.00 | 0.00 | 1121.18 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 3288.78 | 0.00 | 0.00 | 0.00 | 1503.69 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 3281.51 | 0.00 | 0.00 | 0.00 | 1525.85 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.4786 | 0.0000 | 0.0000 | 0.0000 | 1.0919 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.2391 | 0.0000 | 0.0000 | 0.0000 | 1.0903 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.2472 | 0.0000 | 0.0000 | 0.0000 | 1.0867 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 824 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1407.77 | 15539.06 | 19-MAR-17:10 | 227390.58 | 02-JAN-07:10 |
Electricity:Building | 1044.07 | 15341.49 | 01-JAN-09:50 | 75537.45 | 28-DEC-08:10 |
Electricity:Zone:CORE_BOTTOM | 310.83 | 4652.71 | 01-JAN-00:10 | 24063.48 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1044.07 | 15341.49 | 01-JAN-09:50 | 75537.45 | 28-DEC-08:10 |
InteriorLights:Electricity | 282.03 | 1316.11 | 01-JAN-09:50 | 28079.40 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 282.03 | 1316.11 | 01-JAN-09:50 | 28079.40 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 282.03 | 1316.11 | 01-JAN-09:50 | 28079.40 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 282.03 | 1316.11 | 01-JAN-09:50 | 28079.40 | 02-JAN-16:30 |
Electricity:Zone:CORE_MID | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.09 | 541.99 | 01-JAN-09:50 | 2674.44 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.40 | 40.03 | 01-JAN-09:50 | 1168.55 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.40 | 40.03 | 01-JAN-09:50 | 1168.55 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 22.82 | 343.10 | 01-JAN-09:20 | 1693.08 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.92 | 25.34 | 01-JAN-09:20 | 739.79 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.92 | 25.34 | 01-JAN-09:20 | 739.79 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 35.99 | 541.99 | 01-JAN-09:20 | 2674.43 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.31 | 40.03 | 01-JAN-09:20 | 1168.55 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.31 | 40.03 | 01-JAN-09:20 | 1168.55 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 22.81 | 343.10 | 01-JAN-09:50 | 1693.03 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.92 | 25.34 | 01-JAN-09:50 | 739.74 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.92 | 25.34 | 01-JAN-09:50 | 739.74 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.07 | 541.99 | 01-JAN-09:50 | 2674.44 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.38 | 40.03 | 01-JAN-09:50 | 1168.55 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.38 | 40.03 | 01-JAN-09:50 | 1168.55 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 22.81 | 343.10 | 01-JAN-09:20 | 1693.08 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.92 | 25.34 | 01-JAN-09:20 | 739.79 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.92 | 25.34 | 01-JAN-09:20 | 739.79 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 35.98 | 541.99 | 01-JAN-09:20 | 2674.43 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.29 | 40.03 | 01-JAN-09:20 | 1168.55 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.29 | 40.03 | 01-JAN-09:20 | 1168.55 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 22.80 | 343.10 | 01-JAN-09:40 | 1693.03 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.91 | 25.34 | 01-JAN-09:40 | 739.74 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.91 | 25.34 | 01-JAN-09:40 | 739.74 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 36.09 | 541.99 | 01-JAN-09:50 | 2674.44 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.40 | 40.03 | 01-JAN-09:50 | 1168.55 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.40 | 40.03 | 01-JAN-09:50 | 1168.55 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 22.82 | 343.10 | 01-JAN-09:20 | 1693.08 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.92 | 25.34 | 01-JAN-09:20 | 739.79 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.92 | 25.34 | 01-JAN-09:20 | 739.79 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 35.99 | 541.99 | 01-JAN-09:20 | 2674.43 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.30 | 40.03 | 01-JAN-09:20 | 1168.55 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.30 | 40.03 | 01-JAN-09:20 | 1168.55 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 22.81 | 343.10 | 01-JAN-09:50 | 1693.03 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.92 | 25.34 | 01-JAN-09:50 | 739.74 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.92 | 25.34 | 01-JAN-09:50 | 739.74 | 02-JAN-16:30 |
InteriorEquipment:Electricity | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 247.34 | 4344.73 | 01-JAN-00:10 | 18520.31 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 291.63 | 197.57 | 15-JUL-17:40 | 190619.47 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 928.06 | 28-DEC-08:20 |
Transformer:ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 928.06 | 28-DEC-08:20 |
ElectricityPurchased:Facility | 1407.77 | 15539.06 | 19-MAR-17:10 | 227390.58 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1407.77 | 15539.06 | 19-MAR-17:10 | 227390.58 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1407.77 | 15539.06 | 19-MAR-17:10 | 227390.58 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1407.77 | 15539.06 | 19-MAR-17:10 | 227390.58 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1407.77 | 15539.06 | 19-MAR-17:10 | 227390.58 | 02-JAN-07:10 |
ElectricityNet:Plant | 1407.77 | 15539.06 | 19-MAR-17:10 | 227390.58 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1407.77 | 15539.06 | 19-MAR-17:10 | 227390.58 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1407.77 | 15539.06 | 19-MAR-17:10 | 227390.58 | 02-JAN-07:10 |
Heating:Electricity | 127.31 | 0.00 | 01-JAN-00:40 | 184080.49 | 02-JAN-07:10 |
General:Heating:Electricity | 127.31 | 0.00 | 01-JAN-00:40 | 184080.49 | 02-JAN-07:10 |
Fans:Electricity | 77.33 | 0.00 | 01-JAN-00:40 | 25983.35 | 10-AUG-15:10 |
General:Fans:Electricity | 77.33 | 0.00 | 01-JAN-00:40 | 25983.35 | 10-AUG-15:10 |
ExteriorLights:Electricity | 72.05 | 0.00 | 01-JAN-08:10 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 72.05 | 0.00 | 01-JAN-08:10 | 5557.43 | 01-JAN-06:10 |
Cooling:Electricity | 74.01 | 0.00 | 01-JAN-00:10 | 57126.35 | 29-AUG-15:30 |
General:Cooling:Electricity | 74.01 | 0.00 | 01-JAN-00:10 | 57126.35 | 29-AUG-15:30 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 7.93 | 0.00 | 01-JAN-00:10 | 789.03 | 02-JAN-16:40 |
WIRED_INT_EQUIP | 641.94 | 12061.80 | 01-JAN-00:10 | 36271.65 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 176.41 | 1156.00 | 28-JAN-06:10 | 58733.11 | 07-JAN-08:00 |
NaturalGas:HVAC | 67.36 | 0.00 | 01-JAN-00:40 | 50787.73 | 07-JAN-08:00 |
Heating:NaturalGas | 67.36 | 0.00 | 01-JAN-00:40 | 50787.73 | 07-JAN-08:00 |
General:Heating:NaturalGas | 67.36 | 0.00 | 01-JAN-00:40 | 50787.73 | 07-JAN-08:00 |
NaturalGas:Plant | 109.06 | 1156.00 | 03-JAN-18:10 | 9394.87 | 13-FEB-12:10 |
WaterSystems:NaturalGas | 109.06 | 1156.00 | 03-JAN-18:10 | 9394.87 | 13-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 109.06 | 1156.00 | 03-JAN-18:10 | 9394.87 | 13-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1479.32 | 0.00 | 01-JAN-00:40 | 371822.07 | 10-AUG-15:20 |
EnergyTransfer:Building | 948.46 | 0.00 | 01-JAN-00:40 | 169615.91 | 02-JAN-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 213.82 | 0.00 | 01-JAN-00:40 | 25217.38 | 14-AUG-08:00 |
Heating:EnergyTransfer | 93.00 | 0.00 | 01-JAN-00:40 | 169539.55 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.17 | 0.00 | 01-JAN-00:10 | 17203.71 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 93.00 | 0.00 | 01-JAN-00:40 | 169539.55 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.17 | 0.00 | 01-JAN-00:10 | 17203.71 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 855.46 | 0.00 | 01-JAN-00:40 | 157140.93 | 10-AUG-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 213.64 | 0.00 | 01-JAN-00:40 | 25217.38 | 14-AUG-08:00 |
General:Cooling:EnergyTransfer | 855.46 | 0.00 | 01-JAN-00:40 | 157140.93 | 10-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 213.64 | 0.00 | 01-JAN-00:40 | 25217.38 | 14-AUG-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 37.54 | 0.00 | 01-JAN-00:40 | 10208.36 | 10-AUG-14:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 16.61 | 0.00 | 01-JAN-00:40 | 9674.61 | 26-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 16.61 | 0.00 | 01-JAN-00:40 | 9674.61 | 26-DEC-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 20.93 | 0.00 | 01-JAN-00:10 | 10208.36 | 10-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 20.93 | 0.00 | 01-JAN-00:10 | 10208.36 | 10-AUG-14:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 18.83 | 0.00 | 01-JAN-00:40 | 8671.00 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.81 | 0.00 | 01-JAN-00:40 | 8671.00 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.81 | 0.00 | 01-JAN-00:40 | 8671.00 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.02 | 0.00 | 01-JAN-00:10 | 4447.46 | 14-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.02 | 0.00 | 01-JAN-00:10 | 4447.46 | 14-AUG-15:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 21.45 | 0.00 | 01-JAN-00:40 | 6943.13 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 5.46 | 0.00 | 01-JAN-00:40 | 6943.13 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 5.46 | 0.00 | 01-JAN-00:40 | 6943.13 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 15.99 | 0.00 | 01-JAN-00:10 | 4888.55 | 14-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 15.99 | 0.00 | 01-JAN-00:10 | 4888.55 | 14-AUG-16:00 |
EnergyTransfer:Zone:CORE_MID | 137.77 | 0.00 | 01-JAN-00:40 | 20844.17 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.68 | 0.00 | 01-JAN-00:10 | 20844.17 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.68 | 0.00 | 01-JAN-00:10 | 20844.17 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 137.08 | 0.00 | 01-JAN-00:40 | 17268.95 | 14-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 137.08 | 0.00 | 01-JAN-00:40 | 17268.95 | 14-AUG-16:00 |
EnergyTransfer:Zone:CORE_TOP | 127.57 | 0.00 | 01-JAN-00:40 | 27258.12 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 3.12 | 0.00 | 01-JAN-00:40 | 27258.12 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 3.12 | 0.00 | 01-JAN-00:40 | 27258.12 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 124.45 | 0.00 | 01-JAN-00:20 | 18928.27 | 14-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 124.45 | 0.00 | 01-JAN-00:20 | 18928.27 | 14-AUG-15:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.30 | 0.00 | 01-JAN-00:40 | 7835.13 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 7.56 | 0.00 | 01-JAN-00:40 | 7835.13 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 7.56 | 0.00 | 01-JAN-00:40 | 7835.13 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 22.75 | 0.00 | 01-JAN-00:20 | 6299.42 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 22.75 | 0.00 | 01-JAN-00:20 | 6299.42 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 28.43 | 0.00 | 01-JAN-00:40 | 8482.94 | 31-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.54 | 0.00 | 01-JAN-00:40 | 6922.25 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.54 | 0.00 | 01-JAN-00:40 | 6922.25 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 23.90 | 0.00 | 01-JAN-00:20 | 8482.94 | 31-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 23.90 | 0.00 | 01-JAN-00:20 | 8482.94 | 31-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 48.42 | 0.00 | 01-JAN-00:40 | 13116.60 | 29-AUG-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.75 | 0.00 | 01-JAN-00:40 | 10642.34 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.75 | 0.00 | 01-JAN-00:40 | 10642.34 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 42.67 | 0.00 | 01-JAN-00:20 | 13116.60 | 29-AUG-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 42.67 | 0.00 | 01-JAN-00:20 | 13116.60 | 29-AUG-12:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 29.82 | 0.00 | 01-JAN-00:40 | 9462.83 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.80 | 0.00 | 01-JAN-00:40 | 6892.05 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.80 | 0.00 | 01-JAN-00:40 | 6892.05 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.01 | 0.00 | 01-JAN-00:20 | 9462.83 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.01 | 0.00 | 01-JAN-00:20 | 9462.83 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 24.97 | 0.00 | 01-JAN-00:40 | 6269.80 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.75 | 0.00 | 01-JAN-00:40 | 6269.80 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.75 | 0.00 | 01-JAN-00:40 | 6269.80 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 22.23 | 0.00 | 01-JAN-00:10 | 4709.46 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 22.23 | 0.00 | 01-JAN-00:10 | 4709.46 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 23.95 | 0.00 | 01-JAN-00:40 | 6846.07 | 24-JUL-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.66 | 0.00 | 01-JAN-00:40 | 5888.36 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.66 | 0.00 | 01-JAN-00:40 | 5888.36 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 22.29 | 0.00 | 01-JAN-00:10 | 6846.07 | 24-JUL-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 22.29 | 0.00 | 01-JAN-00:10 | 6846.07 | 24-JUL-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 49.96 | 0.00 | 01-JAN-00:40 | 13584.97 | 08-AUG-16:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 22.34 | 0.00 | 01-JAN-00:40 | 12272.04 | 06-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 22.34 | 0.00 | 01-JAN-00:40 | 12272.04 | 06-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 27.62 | 0.00 | 01-JAN-00:10 | 13584.97 | 08-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 27.62 | 0.00 | 01-JAN-00:10 | 13584.97 | 08-AUG-16:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 24.70 | 0.00 | 01-JAN-00:40 | 7548.87 | 10-AUG-17:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.69 | 0.00 | 01-JAN-00:40 | 5873.79 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.69 | 0.00 | 01-JAN-00:40 | 5873.79 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 23.02 | 0.00 | 01-JAN-00:10 | 7548.87 | 10-AUG-17:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 23.02 | 0.00 | 01-JAN-00:10 | 7548.87 | 10-AUG-17:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 28.06 | 0.00 | 01-JAN-00:40 | 6734.29 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.64 | 0.00 | 01-JAN-00:40 | 6734.29 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.64 | 0.00 | 01-JAN-00:40 | 6734.29 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.42 | 0.00 | 01-JAN-00:20 | 5708.30 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.42 | 0.00 | 01-JAN-00:20 | 5708.30 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 27.34 | 0.00 | 01-JAN-00:40 | 8422.31 | 31-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.73 | 0.00 | 01-JAN-00:40 | 5714.46 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.73 | 0.00 | 01-JAN-00:40 | 5714.46 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 25.61 | 0.00 | 01-JAN-00:20 | 8422.31 | 31-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 25.61 | 0.00 | 01-JAN-00:20 | 8422.31 | 31-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 47.24 | 0.00 | 01-JAN-00:40 | 12805.97 | 04-OCT-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.97 | 0.00 | 01-JAN-00:40 | 8735.27 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.97 | 0.00 | 01-JAN-00:40 | 8735.27 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 45.27 | 0.00 | 01-JAN-00:20 | 12805.97 | 04-OCT-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 45.27 | 0.00 | 01-JAN-00:20 | 12805.97 | 04-OCT-13:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 28.28 | 0.00 | 01-JAN-00:40 | 8897.41 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.71 | 0.00 | 01-JAN-00:40 | 5686.22 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.71 | 0.00 | 01-JAN-00:40 | 5686.22 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 26.57 | 0.00 | 01-JAN-00:20 | 8897.41 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 26.57 | 0.00 | 01-JAN-00:20 | 8897.41 | 10-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 50.33 | 0.00 | 01-JAN-00:10 | 6124.40 | 17-FEB-12:10 |
PlantLoopHeatingDemand:Plant | 50.33 | 0.00 | 01-JAN-00:10 | 6124.40 | 17-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 50.33 | 0.00 | 01-JAN-00:10 | 6124.40 | 17-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 50.33 | 0.00 | 01-JAN-00:10 | 6124.40 | 17-FEB-12:10 |
EnergyTransfer:HVAC | 480.53 | 0.00 | 01-JAN-00:40 | 210621.52 | 10-AUG-15:20 |
HeatingCoils:EnergyTransfer | 181.20 | 0.00 | 01-JAN-00:40 | 192983.34 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 299.34 | 0.00 | 01-JAN-00:10 | 210621.52 | 10-AUG-15:20 |
EnergyTransfer:Plant | 50.33 | 0.00 | 01-JAN-00:10 | 6124.40 | 17-FEB-12:10 |
WaterSystems:EnergyTransfer | 50.33 | 0.00 | 01-JAN-00:10 | 6124.40 | 17-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 50.33 | 0.00 | 01-JAN-00:10 | 6124.40 | 17-FEB-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.174 | -213.644 | 0.000 | 0.000 | 32.966 | 63.485 | 247.342 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -130.323 |
CORE_MID | 0.000 | 0.000 | 0.682 | -137.084 | 0.000 | 0.000 | 34.315 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -87.998 |
CORE_TOP | 0.000 | 0.000 | 3.122 | -124.446 | 0.000 | 0.000 | 35.166 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -103.928 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 7.557 | -22.746 | 0.000 | 0.000 | 7.624 | 9.398 | 26.688 | 12.594 | 0.000 | 0.021 | 0.000 | 0.000 | -26.455 | 0.000 | -6.835 | -7.847 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 4.540 | -23.895 | 0.000 | 0.000 | 4.794 | 5.923 | 16.895 | 23.978 | 0.000 | 0.012 | 0.000 | 0.000 | -17.034 | 0.000 | -4.594 | -10.619 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 5.749 | -42.674 | 0.000 | 0.000 | 7.515 | 9.305 | 26.688 | 51.870 | 0.000 | 0.016 | 0.000 | 0.000 | -26.124 | 0.000 | -7.080 | -25.266 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 4.805 | -25.012 | 0.000 | 0.000 | 4.859 | 5.915 | 16.895 | 25.976 | 0.000 | 0.011 | 0.000 | 0.000 | -17.585 | 0.000 | -4.637 | -11.227 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 2.746 | -22.227 | 0.000 | 0.000 | 7.568 | 9.379 | 26.688 | 12.741 | 0.000 | 0.013 | 0.001 | 0.000 | -27.841 | 0.000 | -3.865 | -5.202 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.664 | -22.290 | 0.000 | 0.000 | 4.733 | 5.915 | 16.895 | 23.997 | 0.000 | 0.007 | 0.000 | 0.000 | -18.145 | 0.000 | -2.635 | -10.140 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 22.337 | -27.621 | 0.000 | 0.000 | 7.722 | 9.292 | 26.688 | 52.481 | 0.000 | 0.603 | 0.000 | 0.000 | -27.510 | 0.000 | -50.366 | -13.628 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 1.688 | -23.016 | 0.000 | 0.000 | 4.783 | 5.908 | 16.895 | 26.066 | 0.000 | 0.006 | 0.000 | 0.000 | -18.757 | 0.000 | -2.658 | -10.915 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 2.643 | -25.415 | 0.000 | 0.000 | 7.503 | 9.398 | 26.688 | 12.273 | 0.000 | 0.018 | 1.295 | 0.000 | -28.316 | 0.000 | -6.087 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.733 | -25.606 | 0.000 | 0.000 | 3.512 | 5.923 | 16.895 | 23.748 | 0.000 | 0.011 | 0.000 | 0.000 | -18.136 | 0.000 | -4.074 | -4.005 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 1.968 | -45.273 | 0.000 | 0.000 | 7.386 | 9.305 | 26.688 | 51.496 | 0.000 | 0.014 | 0.000 | 0.000 | -27.873 | 0.000 | -6.294 | -17.418 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 1.708 | -26.568 | 0.000 | 0.000 | 4.781 | 5.915 | 16.895 | 25.768 | 0.000 | 0.010 | 0.000 | 0.000 | -18.774 | 0.000 | -4.121 | -5.614 |
TOPFLOOR_PLENUM | 16.610 | -20.928 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.011 | 14.827 | 0.000 | 0.000 | 0.000 | -10.520 | -0.001 |
MIDFLOOR_PLENUM | 7.810 | -11.023 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.022 | 13.657 | 0.000 | 0.000 | 0.000 | -10.465 | -0.000 |
FIRSTFLOOR_PLENUM | 5.463 | -15.987 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.016 | 19.051 | 0.000 | 0.000 | 0.000 | -8.543 | -0.000 |
Total Facility | 29.883 | -47.939 | 63.114 | -807.515 | 0.000 | 0.000 | 175.227 | 282.030 | 762.041 | 342.990 | 0.000 | 0.791 | 48.832 | 0.000 | -272.549 | 0.000 | -132.773 | -444.130 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 05-SEP-04:03 | 0.00 | 0.00 | 0.00 | -43158.89 | 0.00 | 0.00 | 0.00 | 615.87 | 5138.45 | 0.00 | 0.00 | 0.00 | 37404.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 14-AUG-04:03 | 0.00 | 0.00 | 0.00 | -31435.92 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 27645.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 14-AUG-05:03 | 0.00 | 0.00 | 0.00 | -31621.86 | 0.00 | 0.00 | 317.62 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 27513.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -6299.40 | 0.00 | 0.00 | 737.22 | 720.41 | 1505.89 | 3290.22 | 0.00 | 44.75 | 0.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 06-AUG-09:02 | 0.00 | 0.00 | 0.00 | -12500.49 | 0.00 | 0.00 | 16.04 | 25.34 | 317.77 | 9098.54 | 0.00 | 0.00 | 3232.09 | 0.00 | -0.00 | 0.00 | -189.28 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-13:32 | 0.00 | 0.00 | 0.00 | -21084.99 | 0.00 | 0.00 | 22.98 | 40.03 | 501.96 | 12674.46 | 0.00 | 0.00 | 8007.16 | 0.00 | -0.00 | 0.00 | -161.59 | 0.00 |
PERIMETER_TOP_ZN_4 | 14-MAY-16:12 | 0.00 | 0.00 | 0.00 | -15194.53 | 0.00 | 0.00 | 14.15 | 25.34 | 317.76 | 10750.15 | 0.00 | 0.00 | 4281.54 | 0.00 | -0.00 | 0.00 | -194.41 | 0.00 |
PERIMETER_BOT_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -4709.47 | 0.00 | 0.00 | 737.22 | 720.41 | 1505.89 | 3338.18 | 0.00 | 23.98 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1616.22 |
PERIMETER_BOT_ZN_2 | 13-AUG-09:42 | 0.00 | 0.00 | 0.00 | -10864.64 | 0.00 | 0.00 | 16.43 | 25.34 | 317.77 | 7835.13 | 0.00 | 0.00 | 2731.32 | 0.00 | -0.00 | 0.00 | -61.35 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-14:32 | 0.00 | 0.00 | 0.00 | -16177.20 | 0.00 | 0.00 | 25.26 | 40.03 | 501.96 | 10377.74 | 0.00 | 0.00 | 5304.22 | 0.00 | -0.00 | 0.00 | -72.01 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-JUL-17:41 | 0.00 | 0.00 | 0.00 | -12284.19 | 0.00 | 0.00 | 0.00 | 25.34 | 317.76 | 10049.90 | 0.00 | 0.00 | 1903.09 | 0.00 | -0.00 | 0.00 | -11.90 | 0.00 |
PERIMETER_MID_ZN_3 | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | -5765.15 | 0.00 | 0.00 | 150.14 | 240.13 | 669.29 | 1969.62 | 0.00 | 0.00 | 2763.47 | 0.00 | -0.00 | 0.00 | -27.50 | 0.00 |
PERIMETER_MID_ZN_2 | 13-AUG-09:02 | 0.00 | 0.00 | 0.00 | -13560.65 | 0.00 | 0.00 | 14.73 | 25.34 | 317.77 | 9244.72 | 0.00 | 0.00 | 4126.77 | 0.00 | -0.00 | 0.00 | -168.68 | 0.00 |
PERIMETER_MID_ZN_1 | 13-AUG-12:22 | 0.00 | 0.00 | 0.00 | -18615.86 | 0.00 | 0.00 | 24.45 | 40.03 | 501.96 | 12247.08 | 0.00 | 0.00 | 5845.76 | 0.00 | -0.00 | 0.00 | -43.42 | 0.00 |
PERIMETER_MID_ZN_4 | 23-JUL-18:11 | 0.00 | 0.00 | 0.00 | -14563.61 | 0.00 | 0.00 | 0.00 | 25.34 | 317.76 | 8839.45 | 0.00 | 0.00 | 5454.56 | 0.00 | -0.00 | 0.00 | -73.50 | 0.00 |
TOPFLOOR_PLENUM | 10-AUG-14:50 | 0.00 | -10208.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.21 | 10166.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 14-AUG-15:20 | 0.00 | -4447.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.56 | 4424.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 14-AUG-16:00 | 0.00 | -4888.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.08 | 4872.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-15:20 | 0.00 | -19059.73 | 0.00 | -138079.66 | 0.00 | 0.00 | 17713.97 | 23688.37 | 43769.98 | 63208.53 | 0.00 | 1533.68 | 7224.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-06:01 | 0.00 | 0.00 | 21744.82 | 0.00 | 0.00 | 0.00 | 500.42 | 615.87 | 5138.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -27999.56 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 23701.77 | 0.00 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -27492.50 |
CORE_TOP | 02-JAN-05:11 | 0.00 | 0.00 | 30951.69 | 0.00 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -34742.43 |
PERIMETER_TOP_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 8934.12 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -982.28 | 0.00 | -521.99 | -8228.97 |
PERIMETER_TOP_ZN_2 | 17-JAN-05:01 | 0.00 | 0.00 | 9974.48 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -998.02 | 0.00 | -207.48 | -9274.86 |
PERIMETER_TOP_ZN_1 | 17-JAN-05:01 | 0.00 | 0.00 | 15141.87 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1472.94 | 0.00 | -311.72 | -14156.32 |
PERIMETER_TOP_ZN_4 | 17-JAN-05:01 | 0.00 | 0.00 | 9915.32 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -977.01 | 0.00 | -207.48 | -9236.71 |
PERIMETER_BOT_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 7040.15 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1018.15 | 0.00 | -281.56 | -6539.56 |
PERIMETER_BOT_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 7261.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -676.22 | 0.00 | -191.98 | -6898.68 |
PERIMETER_BOT_ZN_1 | 06-JAN-07:10 | 0.00 | 0.00 | 12344.68 | 0.00 | 0.00 | 0.00 | 193.30 | 389.51 | 669.28 | 0.00 | 0.00 | 0.00 | 10104.66 | 0.00 | -2512.00 | 0.00 | -21189.44 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 7200.07 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -690.51 | 0.00 | -191.75 | -6823.68 |
PERIMETER_MID_ZN_3 | 02-JAN-05:01 | 0.00 | 0.00 | 7687.47 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1037.66 | 0.00 | -434.44 | -7014.49 |
PERIMETER_MID_ZN_2 | 02-JAN-05:01 | 0.00 | 0.00 | 7633.64 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -690.93 | 0.00 | -297.22 | -7151.37 |
PERIMETER_MID_ZN_1 | 02-JAN-05:01 | 0.00 | 0.00 | 11553.55 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1063.85 | 0.00 | -444.88 | -10843.94 |
PERIMETER_MID_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 7585.29 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -708.02 | 0.00 | -297.02 | -7086.12 |
TOPFLOOR_PLENUM | 26-DEC-06:12 | 12006.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -45.89 | -11960.46 |
MIDFLOOR_PLENUM | 02-JAN-07:04 | 9517.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -180.30 | -9337.37 |
FIRSTFLOOR_PLENUM | 02-JAN-07:01 | 8105.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -141.37 | -7964.37 |
Total Facility | 02-JAN-06:01 | 17444.02 | 0.00 | 173712.73 | 0.00 | 0.00 | 0.00 | 2564.95 | 3119.77 | 18045.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11337.74 | 0.00 | -4241.92 | -199307.80 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.5693 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9289 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.1594 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.3537 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.4883 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9507 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.7846 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3941 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.5797 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4247 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.7442 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4898 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8357 | 2.8357 | 0.7798 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0547 | 2.0547 | 0.7520 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1444 | 2.1444 | 0.7784 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6079 | 0.6079 | 0.1641 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7480 | 0.7480 | 0.1496 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1523 | 1.1523 | 0.2305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8358 | 0.8358 | 0.1672 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4827 | 0.4827 | 0.1641 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6191 | 0.6191 | 0.1238 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9359 | 0.9359 | 0.1872 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6959 | 0.6959 | 0.1392 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5331 | 0.5331 | 0.1583 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7435 | 0.7435 | 0.1487 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0568 | 1.0568 | 0.2114 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7712 | 0.7712 | 0.1542 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.5693 | 4.9289 | 5.5693 | 1.3941 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.1594 | 4.3537 | 5.1594 | 1.4247 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.4883 | 4.9507 | 5.4883 | 1.4898 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4178 | 1.4178 | 0.7798 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0274 | 1.0274 | 0.7520 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0722 | 1.0722 | 0.7784 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3039 | 0.3039 | 0.1641 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3740 | 0.3740 | 0.1496 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5761 | 0.5761 | 0.2305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4179 | 0.4179 | 0.1672 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2414 | 0.2414 | 0.1641 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3095 | 0.3095 | 0.1238 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4679 | 0.4679 | 0.1872 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3480 | 0.3480 | 0.1392 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2666 | 0.2666 | 0.1583 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3717 | 0.3717 | 0.1487 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5284 | 0.5284 | 0.2114 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3856 | 0.3856 | 0.1542 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.7846 | 1.3941 | 1.3941 | 1.3941 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.5797 | 1.4247 | 1.4247 | 1.4247 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.7442 | 1.4898 | 1.4898 | 1.4898 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 359.33 |
Number of hours cooling loads not met | 45.00 |
Number of hours not met | 404.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 127.31 | 184080.49 | 67.36 | 50787.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 74.01 | 57126.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 282.03 | 28079.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 72.05 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 641.30 | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 12.98 | 928.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 77.33 | 25983.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 109.06 | 9394.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 762.04 | 1407.77 |
Natural Gas | 0.00 | 176.41 |
Additional | 0.00 | 0.00 |
Total | 762.04 | 1584.19 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 56.61 |
Space Heating | 25.55 |
Space Cooling | 14.86 |
Fans (All) | 15.52 |
Service Water Heating | 0.00 |
Receptacle Equipment | 152.95 |
Miscellaneous (All) | 282.56 |
Subtotal | 282.56 |
Natural Gas [MJ/m2] | |
Space Heating | 13.52 |
Service Water Heating | 21.89 |
Miscellaneous (All) | 35.41 |
Subtotal | 35.41 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 17.80 |
Space Heating | 12.29 |
Space Cooling | 4.67 |
Fans (All) | 4.88 |
Service Water Heating | 6.88 |
Receptacle Equipment | 48.10 |
Miscellaneous | 5.37 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2429. | 8760. |
BLDG_EQUIP_SCH | 4487. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8744.50 | 15.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8736.33 | 23.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8751.83 | 8.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8746.33 | 13.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8746.17 | 13.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8749.17 | 10.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8744.83 | 15.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8738.33 | 21.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8739.17 | 20.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8736.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 23.67 | 0.00 | 0.00 | 0.00 |
Average | 8751.28 | 8.72 | 0.00 | 0.00 | 0.00 |
Sum | 157523.00 | 157.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8666.33 | 93.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8728.67 | 31.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8755.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8747.00 | 13.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8734.83 | 25.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8728.00 | 32.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8747.50 | 12.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8738.50 | 21.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8723.00 | 37.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8744.17 | 15.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8733.67 | 26.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8726.00 | 34.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8740.83 | 19.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8666.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 93.67 | 0.00 | 0.00 | 0.00 |
Average | 8739.47 | 20.53 | 0.00 | 0.00 | 0.00 |
Sum | 157310.50 | 369.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128247.00 | 57.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128292.67 | 11.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128298.33 | 5.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128298.33 | 57.00 | 0.00 | 0.00 | 0.00 |
Average | 34139.22 | 4.11 | 0.00 | 0.00 | 0.00 |
Sum | 614506.00 | 74.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.985876E+10 | 12527.73 | 13-JAN-08:30 | 2.80 | 1.90 | 0.186191E+10 | 2608.48 | 27-JAN-10:20 | 8.53 | 6.98 |
February | 0.108346E+11 | 16292.20 | 28-FEB-08:20 | 10.60 | 10.00 | 0.176378E+10 | 2606.64 | 09-FEB-10:20 | 10.60 | 10.00 |
March | 0.157756E+11 | 20097.25 | 16-MAR-07:03 | 4.60 | 3.59 | 0.214062E+10 | 2606.78 | 29-MAR-09:09 | 5.87 | 4.44 |
April | 0.167545E+11 | 39012.47 | 27-APR-05:03 | 9.37 | 7.96 | 0.191041E+10 | 2606.65 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.217115E+11 | 40816.04 | 06-MAY-05:03 | 13.07 | 11.42 | 0.207488E+10 | 2606.68 | 05-MAY-09:09 | 13.07 | 11.42 |
June | 0.235840E+11 | 41772.22 | 12-JUN-04:03 | 14.90 | 13.65 | 0.207015E+10 | 2606.71 | 05-JUN-13:00 | 14.90 | 13.65 |
July | 0.242023E+11 | 43138.58 | 10-JUL-04:03 | 13.30 | 12.00 | 0.192508E+10 | 2606.65 | 28-JUL-13:39 | 21.10 | 15.48 |
August | 0.266251E+11 | 43144.52 | 14-AUG-04:03 | 15.15 | 13.39 | 0.215975E+10 | 2606.91 | 09-AUG-09:00 | 15.15 | 13.39 |
September | 0.218954E+11 | 43165.21 | 05-SEP-04:03 | 11.52 | 9.75 | 0.191796E+10 | 2606.66 | 22-SEP-09:09 | 14.37 | 14.11 |
October | 0.178351E+11 | 40746.14 | 03-OCT-05:02 | 8.07 | 6.44 | 0.198681E+10 | 2606.65 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.132764E+11 | 17777.53 | 09-NOV-08:02 | 6.78 | 6.00 | 0.194973E+10 | 2606.63 | 10-NOV-10:20 | 7.07 | 5.84 |
December | 0.112915E+11 | 15470.58 | 07-DEC-08:20 | 6.30 | 3.36 | 0.186746E+10 | 2606.68 | 05-DEC-10:39 | 6.30 | 3.36 |
Annual Sum or Average | 0.213645E+12 | 0.236286E+11 | ||||||||
Minimum of Months | 0.985876E+10 | 12527.73 | 2.80 | 1.90 | 0.176378E+10 | 2606.63 | 5.87 | 3.36 | ||
Maximum of Months | 0.266251E+11 | 43165.21 | 15.15 | 13.65 | 0.215975E+10 | 2608.48 | 26.10 | 16.46 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39308.09 | 56.62 | 11-JAN-17:20 | 12.40 | 9.38 | 0.00 | 0.00 | 01-JAN-00:10 | 12.40 | 9.38 |
February | 78215204.93 | 1941.30 | 27-FEB-15:30 | 19.70 | 12.30 | 0.00 | 0.00 | 01-FEB-00:10 | 19.70 | 12.30 |
March | 0.499409E+09 | 2869.37 | 14-MAR-15:00 | 16.10 | 10.31 | 0.00 | 0.00 | 01-MAR-00:10 | 16.10 | 10.31 |
April | 0.146746E+10 | 8496.55 | 27-APR-14:30 | 26.65 | 17.06 | 0.00 | 0.00 | 01-APR-00:10 | 26.65 | 17.06 |
May | 0.270465E+10 | 8703.72 | 15-MAY-14:30 | 23.30 | 13.06 | 0.00 | 0.00 | 01-MAY-00:10 | 23.30 | 13.06 |
June | 0.352853E+10 | 8771.05 | 28-JUN-14:30 | 25.55 | 15.61 | 0.00 | 0.00 | 01-JUN-00:10 | 25.55 | 15.61 |
July | 0.475227E+10 | 10010.82 | 24-JUL-14:00 | 29.40 | 18.12 | 0.00 | 0.00 | 01-JUL-00:10 | 29.40 | 18.12 |
August | 0.468322E+10 | 10208.36 | 10-AUG-14:50 | 30.07 | 18.95 | 0.00 | 0.00 | 01-AUG-00:10 | 30.07 | 18.95 |
September | 0.246899E+10 | 7903.80 | 14-SEP-14:40 | 23.90 | 17.01 | 0.00 | 0.00 | 01-SEP-00:10 | 23.90 | 17.01 |
October | 0.680454E+09 | 5378.54 | 04-OCT-14:40 | 21.50 | 11.47 | 0.00 | 0.00 | 01-OCT-00:10 | 21.50 | 11.47 |
November | 63476235.68 | 2495.84 | 04-NOV-14:20 | 21.10 | 15.94 | 0.00 | 0.00 | 01-NOV-00:10 | 21.10 | 15.94 |
December | 2160519.49 | 336.50 | 02-DEC-14:50 | 11.78 | 5.57 | 0.00 | 0.00 | 01-DEC-00:10 | 11.78 | 5.57 |
Annual Sum or Average | 0.209289E+11 | 0.00 | ||||||||
Minimum of Months | 39308.09 | 56.62 | 11.78 | 5.57 | 0.00 | 0.00 | 11.78 | 5.57 | ||
Maximum of Months | 0.475227E+10 | 10208.36 | 30.07 | 18.95 | 0.00 | 0.00 | 30.07 | 18.95 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6445818.06 | 1061.57 | 07-JAN-06:01 | -2.2 | -2.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.2 | -2.2 |
February | 70818274.41 | 1127.83 | 10-FEB-07:01 | 0.60 | -0.1 | 0.00 | 0.00 | 01-FEB-00:10 | 0.60 | -0.1 |
March | 0.249487E+09 | 2198.23 | 02-MAR-07:01 | 0.78 | -0.1 | 0.00 | 0.00 | 01-MAR-00:10 | 0.78 | -0.1 |
April | 0.555519E+09 | 2775.09 | 27-APR-16:00 | 27.20 | 16.90 | 0.00 | 0.00 | 01-APR-00:10 | 27.20 | 16.90 |
May | 0.109157E+10 | 2867.11 | 15-MAY-15:30 | 23.60 | 12.74 | 0.00 | 0.00 | 01-MAY-00:10 | 23.60 | 12.74 |
June | 0.177264E+10 | 3313.69 | 28-JUN-15:50 | 26.10 | 16.17 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 16.17 |
July | 0.247083E+10 | 4332.33 | 31-JUL-15:20 | 28.50 | 19.00 | 0.00 | 0.00 | 01-JUL-00:10 | 28.50 | 19.00 |
August | 0.280006E+10 | 4447.46 | 14-AUG-15:20 | 27.17 | 17.34 | 0.00 | 0.00 | 01-AUG-00:10 | 27.17 | 17.34 |
September | 0.146743E+10 | 3468.97 | 14-SEP-15:50 | 24.32 | 17.03 | 0.00 | 0.00 | 01-SEP-00:10 | 24.32 | 17.03 |
October | 0.444315E+09 | 1988.48 | 04-OCT-16:00 | 21.10 | 11.40 | 0.00 | 0.00 | 01-OCT-00:10 | 21.10 | 11.40 |
November | 85650466.75 | 1404.58 | 10-NOV-07:01 | 4.08 | 3.61 | 0.00 | 0.00 | 01-NOV-00:10 | 4.08 | 3.61 |
December | 8579880.81 | 722.87 | 07-DEC-07:02 | 6.10 | 3.18 | 0.00 | 0.00 | 01-DEC-00:10 | 6.10 | 3.18 |
Annual Sum or Average | 0.110233E+11 | 0.00 | ||||||||
Minimum of Months | 6445818.06 | 722.87 | -2.2 | -2.2 | 0.00 | 0.00 | -2.2 | -2.2 | ||
Maximum of Months | 0.280006E+10 | 4447.46 | 28.50 | 19.00 | 0.00 | 0.00 | 28.50 | 19.00 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 75263635.66 | 2038.85 | 06-JAN-07:10 | -2.3 | -2.5 | 0.00 | 0.00 | 01-JAN-00:10 | -2.3 | -2.5 |
February | 0.173971E+09 | 2225.91 | 09-FEB-07:09 | -0.7 | -1.1 | 0.00 | 0.00 | 01-FEB-00:10 | -0.7 | -1.1 |
March | 0.494382E+09 | 2921.03 | 16-MAR-06:01 | 3.98 | 3.04 | 0.00 | 0.00 | 01-MAR-00:10 | 3.98 | 3.04 |
April | 0.959286E+09 | 3175.44 | 27-APR-16:00 | 27.20 | 16.90 | 0.00 | 0.00 | 01-APR-00:10 | 27.20 | 16.90 |
May | 0.177072E+10 | 3317.47 | 15-MAY-16:00 | 23.90 | 12.85 | 0.00 | 0.00 | 01-MAY-00:10 | 23.90 | 12.85 |
June | 0.244996E+10 | 3698.37 | 28-JUN-16:00 | 26.10 | 16.29 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 16.29 |
July | 0.310827E+10 | 4705.73 | 31-JUL-16:00 | 28.90 | 19.18 | 0.00 | 0.00 | 01-JUL-00:10 | 28.90 | 19.18 |
August | 0.352149E+10 | 4888.55 | 14-AUG-16:00 | 27.50 | 16.95 | 0.00 | 0.00 | 01-AUG-00:10 | 27.50 | 16.95 |
September | 0.220201E+10 | 4138.24 | 11-SEP-16:00 | 23.30 | 16.14 | 0.00 | 0.00 | 01-SEP-00:10 | 23.30 | 16.14 |
October | 0.893289E+09 | 2897.74 | 04-OCT-16:00 | 21.10 | 11.40 | 0.00 | 0.00 | 01-OCT-00:10 | 21.10 | 11.40 |
November | 0.229114E+09 | 2360.82 | 10-NOV-07:01 | 4.08 | 3.61 | 0.00 | 0.00 | 01-NOV-00:10 | 4.08 | 3.61 |
December | 0.109619E+09 | 2065.50 | 06-DEC-17:08 | 1.10 | 0.97 | 0.00 | 0.00 | 01-DEC-00:10 | 1.10 | 0.97 |
Annual Sum or Average | 0.159874E+11 | 0.00 | ||||||||
Minimum of Months | 75263635.66 | 2038.85 | -2.3 | -2.5 | 0.00 | 0.00 | -2.3 | -2.5 | ||
Maximum of Months | 0.352149E+10 | 4888.55 | 28.90 | 19.18 | 0.00 | 0.00 | 28.90 | 19.18 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.645510E+10 | 6753.51 | 12-JAN-17:00 | 7.20 | 5.41 | 0.160061E+10 | 2354.40 | 12-JAN-14:00 | 7.20 | 5.41 |
February | 0.708965E+10 | 7540.57 | 28-FEB-17:00 | 14.40 | 10.82 | 0.153307E+10 | 2541.86 | 28-FEB-14:00 | 14.40 | 10.82 |
March | 0.974169E+10 | 8762.44 | 02-MAR-17:00 | 12.80 | 8.57 | 0.198031E+10 | 2606.34 | 02-MAR-14:00 | 12.80 | 8.57 |
April | 0.104789E+11 | 25349.12 | 28-APR-05:03 | 11.10 | 9.92 | 0.184485E+10 | 2606.65 | 14-APR-09:09 | 11.10 | 9.92 |
May | 0.138456E+11 | 28457.31 | 08-MAY-05:03 | 9.50 | 9.45 | 0.205367E+10 | 2606.66 | 05-MAY-09:09 | 9.50 | 9.45 |
June | 0.155469E+11 | 29949.61 | 22-JUN-05:03 | 11.20 | 10.53 | 0.205944E+10 | 2606.68 | 09-JUN-13:09 | 11.20 | 10.53 |
July | 0.163554E+11 | 30153.09 | 28-JUL-05:03 | 14.50 | 12.30 | 0.191849E+10 | 2606.63 | 28-JUL-13:39 | 21.10 | 15.48 |
August | 0.179170E+11 | 31437.48 | 14-AUG-04:03 | 15.15 | 13.39 | 0.215309E+10 | 2606.83 | 09-AUG-09:00 | 15.15 | 13.39 |
September | 0.138195E+11 | 30500.34 | 14-SEP-05:02 | 12.62 | 12.25 | 0.190260E+10 | 2606.64 | 22-SEP-09:09 | 14.37 | 14.11 |
October | 0.105128E+11 | 13834.50 | 04-OCT-16:00 | 21.10 | 11.40 | 0.190383E+10 | 2606.65 | 12-OCT-09:20 | 9.47 | 7.95 |
November | 0.810305E+10 | 7739.89 | 06-NOV-17:00 | 11.70 | 10.80 | 0.173383E+10 | 2591.83 | 06-NOV-14:00 | 11.70 | 10.80 |
December | 0.721904E+10 | 7071.70 | 06-DEC-16:10 | 2.93 | 2.59 | 0.159535E+10 | 2446.44 | 06-DEC-14:00 | 2.93 | 2.59 |
Annual Sum or Average | 0.137085E+12 | 0.222791E+11 | ||||||||
Minimum of Months | 0.645510E+10 | 6753.51 | 2.93 | 2.59 | 0.153307E+10 | 2354.40 | 2.93 | 2.59 | ||
Maximum of Months | 0.179170E+11 | 31437.48 | 21.10 | 13.39 | 0.215309E+10 | 2606.83 | 21.10 | 15.48 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.463503E+10 | 6533.61 | 11-JAN-17:00 | 12.20 | 9.27 | 0.151950E+10 | 2241.24 | 11-JAN-14:00 | 12.20 | 9.27 |
February | 0.569957E+10 | 7529.24 | 28-FEB-17:00 | 14.40 | 10.82 | 0.143896E+10 | 2466.10 | 28-FEB-14:00 | 14.40 | 10.82 |
March | 0.882423E+10 | 7874.59 | 02-MAR-17:00 | 12.80 | 8.57 | 0.184856E+10 | 2542.57 | 02-MAR-14:00 | 12.80 | 8.57 |
April | 0.988309E+10 | 15869.92 | 27-APR-16:00 | 27.20 | 16.90 | 0.176428E+10 | 2606.64 | 27-APR-13:50 | 27.20 | 16.90 |
May | 0.131384E+11 | 16551.69 | 15-MAY-16:00 | 23.90 | 12.85 | 0.201374E+10 | 2606.65 | 05-MAY-09:09 | 23.90 | 12.85 |
June | 0.150417E+11 | 17468.70 | 28-JUN-16:00 | 26.10 | 16.29 | 0.204290E+10 | 2606.68 | 09-JUN-13:09 | 26.10 | 16.29 |
July | 0.161866E+11 | 29849.28 | 24-JUL-05:03 | 15.87 | 13.15 | 0.190859E+10 | 2606.64 | 20-JUL-13:09 | 15.87 | 13.15 |
August | 0.173962E+11 | 31624.06 | 14-AUG-05:03 | 15.37 | 13.48 | 0.214274E+10 | 2606.81 | 09-AUG-09:00 | 15.37 | 13.48 |
September | 0.127112E+11 | 16859.60 | 14-SEP-15:40 | 24.23 | 17.01 | 0.186524E+10 | 2606.61 | 07-SEP-09:30 | 24.23 | 17.01 |
October | 0.935698E+10 | 13697.14 | 04-OCT-16:00 | 21.10 | 11.40 | 0.179242E+10 | 2606.59 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.651072E+10 | 7360.76 | 02-NOV-16:00 | 13.30 | 10.88 | 0.160297E+10 | 2421.84 | 06-NOV-14:00 | 11.10 | 10.22 |
December | 0.506211E+10 | 6778.77 | 05-DEC-15:40 | 7.40 | 5.40 | 0.148803E+10 | 2302.77 | 06-DEC-14:00 | 5.00 | 4.36 |
Annual Sum or Average | 0.124446E+12 | 0.214279E+11 | ||||||||
Minimum of Months | 0.463503E+10 | 6533.61 | 7.40 | 5.40 | 0.143896E+10 | 2241.24 | 5.00 | 4.36 | ||
Maximum of Months | 0.173962E+11 | 31624.06 | 27.20 | 17.01 | 0.214274E+10 | 2606.81 | 27.20 | 17.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146662E+09 | 1180.12 | 11-JAN-16:10 | 14.03 | 10.30 | 0.305792E+09 | 427.33 | 11-JAN-14:00 | 14.03 | 10.30 |
February | 0.437770E+09 | 1473.91 | 27-FEB-16:30 | 19.15 | 12.30 | 0.283501E+09 | 497.49 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.114999E+10 | 1559.31 | 10-MAR-15:00 | 16.10 | 11.51 | 0.357129E+09 | 521.33 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.175575E+10 | 4503.88 | 27-APR-15:30 | 27.20 | 17.10 | 0.348828E+09 | 549.50 | 27-APR-13:00 | 27.20 | 17.10 |
May | 0.281364E+10 | 4672.23 | 15-MAY-14:40 | 23.30 | 12.92 | 0.410032E+09 | 549.50 | 15-MAY-13:09 | 23.30 | 12.92 |
June | 0.347180E+10 | 5185.21 | 21-JUN-15:40 | 24.80 | 15.84 | 0.424039E+09 | 549.51 | 09-JUN-13:09 | 24.80 | 15.84 |
July | 0.403820E+10 | 6299.42 | 24-JUL-15:00 | 30.60 | 18.78 | 0.398901E+09 | 549.50 | 20-JUL-13:09 | 30.60 | 18.78 |
August | 0.418299E+10 | 5756.25 | 09-AUG-15:30 | 28.70 | 18.83 | 0.446777E+09 | 549.54 | 09-AUG-09:00 | 28.70 | 18.83 |
September | 0.255281E+10 | 4312.09 | 12-SEP-15:20 | 24.40 | 16.82 | 0.377859E+09 | 549.49 | 12-SEP-13:00 | 24.40 | 16.82 |
October | 0.143207E+10 | 2592.25 | 04-OCT-15:30 | 21.40 | 11.45 | 0.346722E+09 | 549.48 | 05-OCT-13:00 | 16.10 | 10.65 |
November | 0.586007E+09 | 1400.25 | 02-NOV-14:40 | 13.67 | 11.26 | 0.311208E+09 | 478.37 | 02-NOV-13:00 | 13.67 | 11.26 |
December | 0.178033E+09 | 1102.33 | 29-DEC-15:10 | 10.60 | 8.76 | 0.295251E+09 | 412.99 | 05-DEC-14:00 | 10.60 | 8.76 |
Annual Sum or Average | 0.227457E+11 | 0.430604E+10 | ||||||||
Minimum of Months | 0.146662E+09 | 1102.33 | 10.60 | 8.76 | 0.283501E+09 | 412.99 | 10.60 | 8.76 | ||
Maximum of Months | 0.418299E+10 | 6299.42 | 30.60 | 18.83 | 0.446777E+09 | 549.54 | 30.60 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150927E+09 | 1018.91 | 12-JAN-07:03 | 6.70 | 6.17 | 0.193520E+09 | 262.11 | 20-JAN-10:00 | 5.60 | 3.25 |
February | 0.475047E+09 | 1319.13 | 27-FEB-15:50 | 19.50 | 12.39 | 0.180980E+09 | 309.24 | 27-FEB-14:00 | 19.50 | 12.39 |
March | 0.118147E+10 | 2336.42 | 14-MAR-10:00 | 10.00 | 7.75 | 0.233542E+09 | 347.87 | 02-MAR-10:09 | 10.00 | 7.75 |
April | 0.199470E+10 | 6350.03 | 27-APR-09:30 | 18.35 | 12.60 | 0.232561E+09 | 347.88 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.288164E+10 | 6687.79 | 14-MAY-08:13 | 15.17 | 10.71 | 0.262325E+09 | 347.89 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.374783E+10 | 11405.76 | 25-JUN-09:02 | 16.88 | 12.18 | 0.270007E+09 | 347.88 | 09-JUN-13:09 | 16.88 | 12.18 |
July | 0.408428E+10 | 9580.91 | 30-JUL-09:13 | 21.13 | 15.97 | 0.252758E+09 | 348.35 | 31-JUL-09:00 | 23.30 | 17.69 |
August | 0.439991E+10 | 12503.03 | 06-AUG-09:02 | 15.60 | 12.97 | 0.283862E+09 | 348.34 | 08-AUG-09:00 | 23.60 | 17.64 |
September | 0.279358E+10 | 10585.78 | 10-SEP-09:32 | 16.83 | 13.52 | 0.240772E+09 | 347.88 | 11-SEP-09:00 | 18.90 | 14.30 |
October | 0.143991E+10 | 4342.47 | 04-OCT-09:30 | 16.40 | 10.73 | 0.225081E+09 | 347.88 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.528484E+09 | 1291.64 | 02-NOV-10:40 | 12.43 | 10.47 | 0.196535E+09 | 303.43 | 02-NOV-13:00 | 14.40 | 11.37 |
December | 0.217234E+09 | 1076.93 | 05-DEC-10:35 | 7.77 | 5.32 | 0.187113E+09 | 273.59 | 05-DEC-10:39 | 7.77 | 5.32 |
Annual Sum or Average | 0.238950E+11 | 0.275906E+10 | ||||||||
Minimum of Months | 0.150927E+09 | 1018.91 | 6.70 | 5.32 | 0.180980E+09 | 262.11 | 5.60 | 3.25 | ||
Maximum of Months | 0.439991E+10 | 12503.03 | 21.13 | 15.97 | 0.283862E+09 | 348.35 | 26.10 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.692360E+09 | 6243.05 | 20-JAN-13:30 | 6.70 | 4.72 | 0.316300E+09 | 549.59 | 20-JAN-14:09 | 6.78 | 4.76 |
February | 0.135912E+10 | 8181.18 | 27-FEB-14:30 | 19.15 | 11.80 | 0.306716E+09 | 549.49 | 27-FEB-14:50 | 19.72 | 12.05 |
March | 0.275487E+10 | 9342.68 | 14-MAR-13:40 | 15.20 | 10.17 | 0.383396E+09 | 549.50 | 02-MAR-14:00 | 15.20 | 10.17 |
April | 0.362669E+10 | 11676.19 | 27-APR-13:20 | 26.10 | 16.46 | 0.362040E+09 | 549.51 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.462433E+10 | 15769.15 | 14-MAY-13:32 | 22.60 | 12.25 | 0.408247E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.505281E+10 | 9217.88 | 28-JUN-13:10 | 24.50 | 15.71 | 0.418760E+09 | 549.51 | 09-JUN-13:09 | 24.50 | 15.71 |
July | 0.615682E+10 | 18920.11 | 30-JUL-11:53 | 26.10 | 17.22 | 0.395037E+09 | 549.98 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.701618E+10 | 18673.19 | 06-AUG-13:43 | 22.45 | 15.67 | 0.444130E+09 | 550.35 | 29-AUG-13:30 | 29.30 | 20.07 |
September | 0.572205E+10 | 21084.76 | 10-SEP-13:32 | 21.67 | 14.47 | 0.379490E+09 | 549.93 | 12-SEP-13:00 | 24.40 | 16.54 |
October | 0.349325E+10 | 13105.53 | 04-OCT-13:10 | 20.68 | 11.25 | 0.364977E+09 | 549.81 | 04-OCT-13:00 | 21.10 | 11.41 |
November | 0.128675E+10 | 8334.09 | 04-NOV-13:30 | 20.85 | 16.00 | 0.324273E+09 | 549.49 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.888865E+09 | 6102.88 | 05-DEC-12:30 | 10.30 | 6.13 | 0.312661E+09 | 549.50 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.426741E+11 | 0.441603E+10 | ||||||||
Minimum of Months | 0.692360E+09 | 6102.88 | 6.70 | 4.72 | 0.306716E+09 | 549.49 | 6.78 | 4.76 | ||
Maximum of Months | 0.701618E+10 | 21084.76 | 26.10 | 17.22 | 0.444130E+09 | 550.35 | 29.30 | 20.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176101E+09 | 1346.58 | 05-JAN-15:50 | 6.20 | 4.71 | 0.194099E+09 | 286.50 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.466649E+09 | 3127.32 | 27-FEB-15:30 | 19.70 | 12.30 | 0.182182E+09 | 347.78 | 27-FEB-14:00 | 19.70 | 12.30 |
March | 0.121065E+10 | 4773.34 | 14-MAR-16:00 | 17.20 | 10.94 | 0.225905E+09 | 347.84 | 02-MAR-14:00 | 17.20 | 10.94 |
April | 0.204900E+10 | 7753.32 | 26-APR-16:00 | 24.40 | 14.49 | 0.216882E+09 | 347.85 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.316249E+10 | 15193.70 | 14-MAY-16:12 | 23.13 | 11.97 | 0.252517E+09 | 347.85 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.358455E+10 | 10731.62 | 18-JUN-18:23 | 16.40 | 12.43 | 0.261684E+09 | 347.86 | 05-JUN-13:00 | 16.40 | 12.43 |
July | 0.458968E+10 | 14833.55 | 23-JUL-17:02 | 26.60 | 15.64 | 0.248680E+09 | 347.85 | 28-JUL-13:39 | 21.10 | 15.48 |
August | 0.447990E+10 | 13684.05 | 06-AUG-17:02 | 23.47 | 15.14 | 0.278309E+09 | 347.88 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.303828E+10 | 14879.46 | 10-SEP-16:12 | 22.20 | 14.38 | 0.232965E+09 | 347.85 | 12-SEP-13:00 | 24.40 | 16.54 |
October | 0.151753E+10 | 6310.30 | 04-OCT-16:00 | 21.10 | 11.40 | 0.215690E+09 | 347.83 | 03-OCT-13:00 | 21.10 | 11.40 |
November | 0.515134E+09 | 2254.60 | 04-NOV-15:40 | 20.37 | 15.93 | 0.195991E+09 | 314.46 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.222241E+09 | 1458.07 | 05-DEC-15:40 | 7.40 | 5.40 | 0.188206E+09 | 302.06 | 05-DEC-15:50 | 6.75 | 4.97 |
Annual Sum or Average | 0.250122E+11 | 0.269311E+10 | ||||||||
Minimum of Months | 0.176101E+09 | 1346.58 | 6.20 | 4.71 | 0.182182E+09 | 286.50 | 6.10 | 4.61 | ||
Maximum of Months | 0.458968E+10 | 15193.70 | 26.60 | 15.93 | 0.278309E+09 | 347.88 | 26.10 | 16.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.281445E+09 | 1172.59 | 11-JAN-16:20 | 13.67 | 10.10 | 0.307217E+09 | 428.05 | 11-JAN-14:00 | 13.67 | 10.10 |
February | 0.569221E+09 | 1382.29 | 28-FEB-15:00 | 13.90 | 10.81 | 0.284129E+09 | 477.54 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.136010E+10 | 1440.27 | 10-MAR-14:40 | 16.30 | 11.68 | 0.357741E+09 | 492.20 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.171646E+10 | 2600.30 | 27-APR-16:00 | 27.20 | 16.90 | 0.345495E+09 | 549.49 | 27-APR-13:00 | 27.20 | 16.90 |
May | 0.240135E+10 | 3126.45 | 05-MAY-15:30 | 24.70 | 17.20 | 0.413326E+09 | 549.49 | 26-MAY-13:00 | 13.90 | 12.34 |
June | 0.289942E+10 | 3838.67 | 21-JUN-15:40 | 24.80 | 15.84 | 0.427105E+09 | 549.50 | 09-JUN-13:09 | 24.80 | 15.84 |
July | 0.340479E+10 | 4709.46 | 24-JUL-15:00 | 30.60 | 18.78 | 0.401118E+09 | 549.49 | 21-JUL-13:00 | 30.60 | 18.78 |
August | 0.368323E+10 | 4459.43 | 09-AUG-15:30 | 28.70 | 18.83 | 0.449876E+09 | 549.53 | 09-AUG-09:00 | 28.70 | 18.83 |
September | 0.248511E+10 | 3347.46 | 14-SEP-15:50 | 24.32 | 17.03 | 0.388084E+09 | 549.49 | 14-SEP-09:09 | 24.32 | 17.03 |
October | 0.183068E+10 | 2060.11 | 04-OCT-15:30 | 21.40 | 11.45 | 0.365960E+09 | 549.48 | 05-OCT-13:00 | 16.10 | 10.65 |
November | 0.111939E+10 | 1449.60 | 06-NOV-12:00 | 13.90 | 10.05 | 0.324822E+09 | 491.57 | 06-NOV-14:09 | 11.60 | 10.16 |
December | 0.475919E+09 | 1154.75 | 29-DEC-15:00 | 10.60 | 8.76 | 0.298041E+09 | 424.83 | 29-DEC-14:20 | 10.60 | 8.76 |
Annual Sum or Average | 0.222271E+11 | 0.436291E+10 | ||||||||
Minimum of Months | 0.281445E+09 | 1154.75 | 10.60 | 8.76 | 0.284129E+09 | 424.83 | 10.60 | 8.76 | ||
Maximum of Months | 0.368323E+10 | 4709.46 | 30.60 | 18.83 | 0.449876E+09 | 549.53 | 30.60 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245648E+09 | 874.94 | 20-JAN-10:50 | 5.32 | 3.17 | 0.194559E+09 | 270.65 | 20-JAN-10:00 | 5.60 | 3.25 |
February | 0.512337E+09 | 1055.99 | 27-FEB-15:40 | 19.60 | 12.34 | 0.183748E+09 | 304.60 | 27-FEB-14:00 | 19.60 | 12.34 |
March | 0.119421E+10 | 1368.18 | 14-MAR-10:00 | 10.00 | 7.75 | 0.238433E+09 | 347.87 | 02-MAR-10:30 | 10.00 | 7.75 |
April | 0.170440E+10 | 4686.47 | 27-APR-09:30 | 18.35 | 12.60 | 0.236161E+09 | 347.88 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.235626E+10 | 5235.71 | 15-MAY-09:20 | 17.77 | 12.22 | 0.267336E+09 | 347.89 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.319803E+10 | 5593.65 | 28-JUN-09:30 | 20.00 | 13.97 | 0.273458E+09 | 347.88 | 28-JUN-13:50 | 24.90 | 15.66 |
July | 0.355605E+10 | 10555.85 | 23-JUL-09:32 | 20.37 | 14.49 | 0.255031E+09 | 348.11 | 31-JUL-09:00 | 23.30 | 17.69 |
August | 0.406027E+10 | 10865.13 | 13-AUG-09:42 | 22.40 | 16.47 | 0.286437E+09 | 348.13 | 14-AUG-09:00 | 21.10 | 15.94 |
September | 0.260245E+10 | 5444.94 | 11-SEP-09:30 | 17.80 | 13.71 | 0.248609E+09 | 347.88 | 11-SEP-09:00 | 18.90 | 14.30 |
October | 0.160077E+10 | 3709.13 | 04-OCT-09:30 | 16.40 | 10.73 | 0.239623E+09 | 347.88 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.843954E+09 | 1151.27 | 02-NOV-10:40 | 12.43 | 10.47 | 0.206724E+09 | 316.26 | 02-NOV-10:50 | 12.62 | 10.55 |
December | 0.415555E+09 | 999.02 | 05-DEC-10:30 | 7.50 | 5.28 | 0.190001E+09 | 293.06 | 05-DEC-10:39 | 7.77 | 5.32 |
Annual Sum or Average | 0.222899E+11 | 0.282012E+10 | ||||||||
Minimum of Months | 0.245648E+09 | 874.94 | 5.32 | 3.17 | 0.183748E+09 | 270.65 | 5.60 | 3.25 | ||
Maximum of Months | 0.406027E+10 | 10865.13 | 22.40 | 16.47 | 0.286437E+09 | 348.13 | 26.10 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172744E+09 | 1705.50 | 07-JAN-14:30 | 3.05 | 1.81 | 0.295893E+09 | 485.83 | 20-JAN-14:09 | 6.78 | 4.76 |
February | 0.587736E+09 | 4276.87 | 27-FEB-15:00 | 20.00 | 12.17 | 0.282829E+09 | 549.49 | 27-FEB-14:00 | 20.00 | 12.17 |
March | 0.124596E+10 | 4256.80 | 18-MAR-13:40 | 19.07 | 10.73 | 0.353439E+09 | 549.50 | 02-MAR-14:00 | 19.07 | 10.73 |
April | 0.195066E+10 | 9435.53 | 27-APR-16:10 | 27.02 | 16.89 | 0.335180E+09 | 549.51 | 27-APR-13:00 | 27.02 | 16.89 |
May | 0.259034E+10 | 7359.20 | 14-MAY-14:02 | 22.88 | 12.30 | 0.383154E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.308602E+10 | 7185.52 | 28-JUN-17:00 | 26.70 | 16.74 | 0.400520E+09 | 549.52 | 28-JUN-13:50 | 26.70 | 16.74 |
July | 0.443360E+10 | 12681.67 | 31-JUL-16:10 | 28.80 | 19.11 | 0.388721E+09 | 549.57 | 31-JUL-13:30 | 28.80 | 19.11 |
August | 0.590670E+10 | 16070.84 | 13-AUG-14:22 | 27.65 | 18.96 | 0.438680E+09 | 549.85 | 29-AUG-13:30 | 29.30 | 20.07 |
September | 0.414787E+10 | 16176.17 | 10-SEP-14:32 | 22.60 | 14.43 | 0.373130E+09 | 549.70 | 15-SEP-13:30 | 21.70 | 16.59 |
October | 0.239589E+10 | 13184.81 | 08-OCT-13:23 | 18.90 | 13.91 | 0.355730E+09 | 549.62 | 04-OCT-13:00 | 18.90 | 13.91 |
November | 0.730553E+09 | 5934.70 | 04-NOV-13:50 | 21.02 | 15.96 | 0.308303E+09 | 531.02 | 15-NOV-14:20 | 9.63 | 6.74 |
December | 0.372797E+09 | 3359.96 | 02-DEC-13:30 | 12.20 | 5.86 | 0.292969E+09 | 542.87 | 05-DEC-14:50 | 10.10 | 6.91 |
Annual Sum or Average | 0.276209E+11 | 0.420855E+10 | ||||||||
Minimum of Months | 0.172744E+09 | 1705.50 | 3.05 | 1.81 | 0.282829E+09 | 485.83 | 6.78 | 4.76 | ||
Maximum of Months | 0.590670E+10 | 16176.17 | 28.80 | 19.11 | 0.438680E+09 | 549.85 | 29.30 | 20.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.246452E+09 | 1099.10 | 05-JAN-15:50 | 6.20 | 4.71 | 0.194923E+09 | 282.63 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.526242E+09 | 1892.28 | 27-FEB-15:40 | 19.60 | 12.34 | 0.183018E+09 | 338.69 | 27-FEB-14:00 | 19.60 | 12.34 |
March | 0.124766E+10 | 2715.04 | 02-MAR-16:40 | 12.97 | 8.50 | 0.229003E+09 | 340.88 | 02-MAR-14:00 | 12.97 | 8.50 |
April | 0.173667E+10 | 5345.21 | 26-APR-17:30 | 23.60 | 13.73 | 0.222066E+09 | 347.85 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.255179E+10 | 11990.26 | 07-MAY-17:42 | 21.20 | 15.98 | 0.261736E+09 | 347.85 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.298112E+10 | 7266.34 | 25-JUN-16:42 | 21.70 | 13.39 | 0.268893E+09 | 347.85 | 28-JUN-13:50 | 24.90 | 15.66 |
July | 0.396645E+10 | 12284.10 | 30-JUL-17:41 | 26.70 | 17.71 | 0.254696E+09 | 347.85 | 21-JUL-13:00 | 26.70 | 17.71 |
August | 0.401742E+10 | 11778.87 | 13-AUG-17:02 | 27.32 | 18.38 | 0.284769E+09 | 347.88 | 09-AUG-09:00 | 27.32 | 18.38 |
September | 0.275203E+10 | 7781.71 | 10-SEP-16:33 | 22.20 | 14.28 | 0.245943E+09 | 347.85 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.170516E+10 | 5545.63 | 04-OCT-16:00 | 21.10 | 11.40 | 0.231340E+09 | 347.84 | 05-OCT-13:00 | 16.10 | 10.65 |
November | 0.881195E+09 | 1786.40 | 04-NOV-15:40 | 20.37 | 15.93 | 0.203391E+09 | 321.99 | 10-NOV-14:00 | 10.00 | 6.84 |
December | 0.403711E+09 | 1239.93 | 05-DEC-15:30 | 8.05 | 5.82 | 0.190102E+09 | 307.44 | 05-DEC-15:39 | 7.40 | 5.40 |
Annual Sum or Average | 0.230159E+11 | 0.276988E+10 | ||||||||
Minimum of Months | 0.246452E+09 | 1099.10 | 6.20 | 4.71 | 0.183018E+09 | 282.63 | 6.10 | 4.61 | ||
Maximum of Months | 0.401742E+10 | 12284.10 | 27.32 | 18.38 | 0.284769E+09 | 347.88 | 27.32 | 18.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.369864E+09 | 1214.73 | 11-JAN-16:20 | 13.67 | 10.10 | 0.308057E+09 | 445.97 | 11-JAN-14:00 | 13.67 | 10.10 |
February | 0.716020E+09 | 1477.10 | 28-FEB-15:00 | 13.90 | 10.81 | 0.289568E+09 | 513.32 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.158689E+10 | 1537.90 | 10-MAR-14:50 | 16.20 | 11.59 | 0.374574E+09 | 530.18 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.196728E+10 | 4120.87 | 27-APR-16:00 | 27.20 | 16.90 | 0.364427E+09 | 549.50 | 27-APR-13:00 | 27.20 | 16.90 |
May | 0.293461E+10 | 4337.50 | 05-MAY-15:30 | 24.70 | 17.20 | 0.423100E+09 | 549.50 | 05-MAY-09:09 | 24.70 | 17.20 |
June | 0.355746E+10 | 4804.26 | 21-JUN-15:40 | 24.80 | 15.84 | 0.430881E+09 | 549.50 | 09-JUN-13:09 | 24.80 | 15.84 |
July | 0.404644E+10 | 5764.99 | 24-JUL-06:03 | 17.48 | 14.11 | 0.402731E+09 | 549.60 | 24-JUL-13:39 | 29.03 | 18.20 |
August | 0.424886E+10 | 5254.68 | 09-AUG-15:30 | 28.70 | 18.83 | 0.451491E+09 | 549.54 | 09-AUG-09:00 | 28.70 | 18.83 |
September | 0.271799E+10 | 4129.25 | 12-SEP-14:50 | 24.40 | 16.68 | 0.391319E+09 | 549.49 | 07-SEP-09:30 | 24.40 | 16.68 |
October | 0.179509E+10 | 2695.86 | 04-OCT-15:30 | 21.40 | 11.45 | 0.368703E+09 | 549.48 | 05-OCT-13:00 | 16.10 | 10.65 |
November | 0.997897E+09 | 1426.03 | 02-NOV-14:30 | 13.85 | 11.29 | 0.323706E+09 | 499.17 | 02-NOV-13:00 | 13.85 | 11.29 |
December | 0.476922E+09 | 1160.25 | 29-DEC-17:00 | 9.40 | 7.98 | 0.298920E+09 | 433.64 | 05-DEC-14:00 | 9.40 | 7.98 |
Annual Sum or Average | 0.254153E+11 | 0.442748E+10 | ||||||||
Minimum of Months | 0.369864E+09 | 1160.25 | 9.40 | 7.98 | 0.289568E+09 | 433.64 | 9.40 | 7.98 | ||
Maximum of Months | 0.424886E+10 | 5764.99 | 28.70 | 18.83 | 0.451491E+09 | 549.60 | 29.03 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280302E+09 | 1072.18 | 05-JAN-09:50 | 2.23 | 2.03 | 0.143205E+09 | 266.86 | 05-JAN-09:00 | 2.80 | 2.54 |
February | 0.640129E+09 | 1343.73 | 08-FEB-10:00 | 2.20 | 1.26 | 0.135734E+09 | 309.64 | 08-FEB-09:00 | 2.20 | 1.26 |
March | 0.151318E+10 | 2799.53 | 14-MAR-10:10 | 10.28 | 7.92 | 0.176189E+09 | 338.72 | 14-MAR-10:09 | 10.28 | 7.92 |
April | 0.218404E+10 | 6540.51 | 27-APR-09:00 | 17.80 | 12.21 | 0.174190E+09 | 338.73 | 20-APR-10:09 | 17.80 | 12.21 |
May | 0.296009E+10 | 6696.55 | 15-MAY-08:50 | 16.83 | 11.57 | 0.196177E+09 | 338.74 | 15-MAY-10:09 | 19.18 | 13.24 |
June | 0.374678E+10 | 12007.09 | 25-JUN-09:13 | 17.07 | 12.34 | 0.200575E+09 | 338.73 | 07-JUN-10:09 | 17.07 | 12.34 |
July | 0.401325E+10 | 13236.65 | 23-JUL-08:12 | 18.17 | 13.67 | 0.188176E+09 | 338.98 | 31-JUL-08:00 | 22.20 | 16.89 |
August | 0.436752E+10 | 13562.10 | 13-AUG-09:02 | 21.20 | 16.02 | 0.210445E+09 | 338.91 | 24-AUG-08:00 | 21.90 | 16.62 |
September | 0.290493E+10 | 12120.76 | 10-SEP-09:02 | 16.28 | 13.48 | 0.181164E+09 | 338.73 | 14-SEP-07:10 | 14.18 | 13.39 |
October | 0.176498E+10 | 4999.77 | 04-OCT-09:00 | 15.60 | 10.49 | 0.171324E+09 | 338.73 | 05-OCT-10:09 | 14.08 | 9.36 |
November | 0.819710E+09 | 1382.28 | 02-NOV-10:30 | 12.25 | 10.40 | 0.148562E+09 | 316.29 | 02-NOV-10:39 | 12.43 | 10.47 |
December | 0.411079E+09 | 1200.70 | 05-DEC-10:00 | 6.70 | 5.10 | 0.139182E+09 | 284.97 | 05-DEC-09:00 | 6.70 | 5.10 |
Annual Sum or Average | 0.256060E+11 | 0.206492E+10 | ||||||||
Minimum of Months | 0.280302E+09 | 1072.18 | 2.20 | 1.26 | 0.135734E+09 | 266.86 | 2.20 | 1.26 | ||
Maximum of Months | 0.436752E+10 | 13562.10 | 21.20 | 16.02 | 0.210445E+09 | 338.98 | 22.20 | 16.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.959634E+09 | 6632.30 | 20-JAN-13:30 | 6.70 | 4.72 | 0.322903E+09 | 549.49 | 20-JAN-14:50 | 7.12 | 4.90 |
February | 0.175203E+10 | 8156.14 | 27-FEB-14:30 | 19.15 | 11.80 | 0.314758E+09 | 550.17 | 06-FEB-14:09 | 19.15 | 11.80 |
March | 0.326275E+10 | 9428.43 | 01-MAR-13:35 | 11.33 | 6.09 | 0.398189E+09 | 549.50 | 02-MAR-14:00 | 13.30 | 8.57 |
April | 0.385358E+10 | 11028.72 | 27-APR-13:10 | 26.10 | 16.37 | 0.374600E+09 | 549.95 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.468280E+10 | 11512.04 | 14-MAY-13:03 | 22.30 | 12.21 | 0.420855E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.501619E+10 | 8595.79 | 28-JUN-13:10 | 24.50 | 15.71 | 0.427580E+09 | 549.52 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.600088E+10 | 17977.45 | 30-JUL-12:13 | 26.10 | 17.39 | 0.401145E+09 | 549.96 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.692678E+10 | 18617.40 | 13-AUG-12:22 | 26.30 | 18.24 | 0.450259E+09 | 550.37 | 29-AUG-13:30 | 29.30 | 20.07 |
September | 0.579894E+10 | 17893.57 | 10-SEP-13:42 | 21.93 | 14.56 | 0.391801E+09 | 550.33 | 15-SEP-13:00 | 21.70 | 16.45 |
October | 0.397308E+10 | 17791.65 | 08-OCT-13:23 | 18.90 | 13.91 | 0.381734E+09 | 549.80 | 04-OCT-13:00 | 18.90 | 13.91 |
November | 0.176501E+10 | 8315.44 | 04-NOV-13:30 | 20.85 | 16.00 | 0.339697E+09 | 549.49 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.128173E+10 | 6886.01 | 05-DEC-12:30 | 10.30 | 6.13 | 0.320658E+09 | 549.50 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.452734E+11 | 0.454418E+10 | ||||||||
Minimum of Months | 0.959634E+09 | 6632.30 | 6.70 | 4.72 | 0.314758E+09 | 549.49 | 7.12 | 4.90 | ||
Maximum of Months | 0.692678E+10 | 18617.40 | 26.30 | 18.24 | 0.450259E+09 | 550.37 | 29.30 | 20.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333046E+09 | 1317.49 | 05-JAN-15:50 | 6.20 | 4.71 | 0.195478E+09 | 298.29 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.684889E+09 | 3168.69 | 27-FEB-15:30 | 19.70 | 12.30 | 0.185511E+09 | 347.83 | 27-FEB-14:00 | 19.70 | 12.30 |
March | 0.156429E+10 | 4595.98 | 14-MAR-16:00 | 17.20 | 10.94 | 0.234288E+09 | 347.84 | 02-MAR-14:00 | 17.20 | 10.94 |
April | 0.220257E+10 | 7416.55 | 26-APR-16:00 | 24.40 | 14.49 | 0.225874E+09 | 347.85 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.317288E+10 | 12469.14 | 07-MAY-16:32 | 21.87 | 16.22 | 0.262180E+09 | 347.85 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.353957E+10 | 12047.12 | 25-JUN-16:42 | 21.70 | 13.39 | 0.268670E+09 | 347.86 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.446789E+10 | 14562.50 | 23-JUL-18:11 | 25.53 | 15.86 | 0.253266E+09 | 347.85 | 28-JUL-13:39 | 21.10 | 15.48 |
August | 0.440535E+10 | 13259.21 | 13-AUG-17:02 | 27.32 | 18.38 | 0.283544E+09 | 347.88 | 09-AUG-09:00 | 27.32 | 18.38 |
September | 0.307728E+10 | 13533.45 | 10-SEP-17:02 | 21.93 | 14.12 | 0.242968E+09 | 347.84 | 12-SEP-13:00 | 24.40 | 16.54 |
October | 0.182768E+10 | 6234.47 | 04-OCT-16:00 | 21.10 | 11.40 | 0.227525E+09 | 347.84 | 05-OCT-13:00 | 16.10 | 10.65 |
November | 0.856977E+09 | 2315.76 | 04-NOV-15:30 | 20.55 | 15.94 | 0.201649E+09 | 331.86 | 10-NOV-14:00 | 10.00 | 6.84 |
December | 0.435963E+09 | 1427.83 | 05-DEC-15:40 | 7.40 | 5.40 | 0.190358E+09 | 315.98 | 05-DEC-15:50 | 6.75 | 4.97 |
Annual Sum or Average | 0.265684E+11 | 0.277131E+10 | ||||||||
Minimum of Months | 0.333046E+09 | 1317.49 | 6.20 | 4.71 | 0.185511E+09 | 298.29 | 6.10 | 4.61 | ||
Maximum of Months | 0.446789E+10 | 14562.50 | 27.32 | 18.38 | 0.283544E+09 | 347.88 | 27.32 | 18.38 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174288E+09 | 21744.81 | 02-JAN-06:01 | 6.10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.174288E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.174288E+09 | 21744.81 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.401673E+10 | 10976.20 | 09-JAN-06:13 | -1.3 |
February | 0.246153E+10 | 10619.98 | 21-FEB-06:13 | 1.70 |
March | 0.147266E+10 | 6486.09 | 06-MAR-07:01 | 6.70 |
April | 0.776001E+09 | 5491.01 | 19-APR-06:01 | 2.48 |
May | 0.431333E+09 | 4461.33 | 11-MAY-05:03 | 5.10 |
June | 0.235086E+09 | 3894.31 | 12-JUN-05:03 | 14.40 |
July | 0.157624E+09 | 5314.19 | 24-JUL-05:03 | 15.87 |
August | 0.193132E+09 | 6090.86 | 14-AUG-05:03 | 15.37 |
September | 0.400499E+09 | 4650.93 | 10-SEP-07:38 | 13.67 |
October | 0.990260E+09 | 4156.60 | 16-OCT-05:02 | 7.12 |
November | 0.207778E+10 | 8721.74 | 24-NOV-07:02 | 1.20 |
December | 0.339676E+10 | 12006.35 | 26-DEC-06:12 | -1.0 |
Annual Sum or Average | 0.166094E+11 | |||
Minimum of Months | 0.157624E+09 | 3894.31 | -1.3 | |
Maximum of Months | 0.401673E+10 | 12006.35 | 15.87 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207537E+10 | 9517.64 | 02-JAN-07:04 | 6.20 |
February | 0.124490E+10 | 5895.69 | 21-FEB-07:02 | 1.60 |
March | 0.831688E+09 | 2533.86 | 06-MAR-07:06 | 6.70 |
April | 0.390201E+09 | 2624.99 | 02-APR-11:43 | 16.93 |
May | 89479920.14 | 3943.94 | 29-MAY-16:53 | 16.70 |
June | 29149794.68 | 2514.71 | 20-JUN-05:03 | 13.98 |
July | 31930111.01 | 3480.67 | 30-JUL-14:53 | 27.20 |
August | 24075604.83 | 3818.32 | 06-AUG-15:23 | 23.75 |
September | 71295289.12 | 3435.25 | 10-SEP-15:02 | 22.70 |
October | 0.419650E+09 | 4769.42 | 08-OCT-12:43 | 17.80 |
November | 0.103256E+10 | 3099.41 | 11-NOV-12:43 | 6.42 |
December | 0.156965E+10 | 6996.89 | 26-DEC-07:03 | -1.6 |
Annual Sum or Average | 0.780995E+10 | |||
Minimum of Months | 24075604.83 | 2514.71 | -1.6 | |
Maximum of Months | 0.207537E+10 | 9517.64 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171060E+10 | 8105.72 | 02-JAN-07:01 | 6.20 |
February | 0.923487E+09 | 3652.95 | 09-FEB-08:15 | -0.2 |
March | 0.447959E+09 | 3164.16 | 27-MAR-07:06 | 4.50 |
April | 0.123706E+09 | 4398.71 | 26-APR-05:03 | 7.20 |
May | 31445639.82 | 5410.11 | 11-MAY-05:03 | 5.10 |
June | 28212847.02 | 5461.96 | 14-JUN-05:03 | 10.00 |
July | 31155505.01 | 4711.57 | 05-JUL-04:03 | 11.20 |
August | 29252890.71 | 4376.20 | 05-AUG-05:03 | 12.68 |
September | 29313210.32 | 5381.78 | 18-SEP-05:03 | 12.20 |
October | 0.174293E+09 | 5663.90 | 11-OCT-05:03 | 8.22 |
November | 0.715090E+09 | 3719.65 | 15-NOV-08:09 | 4.78 |
December | 0.121844E+10 | 3782.45 | 26-DEC-08:40 | -1.1 |
Annual Sum or Average | 0.546295E+10 | |||
Minimum of Months | 28212847.02 | 3164.16 | -1.1 | |
Maximum of Months | 0.171060E+10 | 8105.72 | 12.68 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.514543E+09 | 23701.78 | 02-JAN-05:01 | 6.10 |
February | 63999679.32 | 20899.73 | 21-FEB-06:01 | 1.70 |
March | 3998834.25 | 18977.53 | 06-MAR-07:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 12538493.46 | 18941.32 | 24-NOV-07:01 | 1.20 |
December | 86532407.70 | 20994.24 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.681613E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.514543E+09 | 23701.78 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138835E+10 | 30951.71 | 02-JAN-05:11 | 6.10 |
February | 0.534513E+09 | 29288.39 | 21-FEB-05:11 | 1.70 |
March | 0.109457E+09 | 27205.09 | 06-MAR-06:01 | 6.70 |
April | 13441610.23 | 24992.57 | 18-APR-06:01 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 22691735.06 | 25029.89 | 23-OCT-06:03 | 10.40 |
November | 0.277339E+09 | 27475.72 | 13-NOV-06:01 | 1.70 |
December | 0.776122E+09 | 29716.50 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.312192E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.138835E+10 | 30951.71 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259149E+10 | 8934.12 | 02-JAN-05:11 | 6.10 |
February | 0.139379E+10 | 8858.08 | 21-FEB-05:11 | 1.70 |
March | 0.433609E+09 | 8249.64 | 06-MAR-05:03 | 6.70 |
April | 0.120765E+09 | 7671.76 | 18-APR-05:02 | 3.30 |
May | 6793666.20 | 7083.44 | 18-MAY-06:02 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 2588435.40 | 6856.04 | 27-SEP-06:03 | 8.40 |
October | 0.141860E+09 | 7702.95 | 30-OCT-05:02 | 7.20 |
November | 0.895088E+09 | 8474.06 | 13-NOV-05:02 | 1.20 |
December | 0.197066E+10 | 8767.37 | 18-DEC-05:01 | 3.40 |
Annual Sum or Average | 0.755664E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.20 | |
Maximum of Months | 0.259149E+10 | 8934.12 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158602E+10 | 9974.48 | 17-JAN-05:01 | 1.60 |
February | 0.797745E+09 | 9913.66 | 21-FEB-05:11 | 1.70 |
March | 0.232876E+09 | 8827.43 | 13-MAR-05:01 | 6.70 |
April | 58194148.66 | 8431.12 | 18-APR-05:02 | 3.30 |
May | 6203610.49 | 6789.23 | 18-MAY-06:02 | 5.68 |
June | 220764.72 | 735.88 | 14-JUN-06:05 | 10.10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 1980012.98 | 5229.27 | 28-SEP-06:03 | 8.40 |
October | 92550786.41 | 8369.73 | 30-OCT-05:02 | 7.20 |
November | 0.553573E+09 | 9395.46 | 13-NOV-05:02 | 1.20 |
December | 0.121021E+10 | 9799.79 | 18-DEC-05:01 | 3.40 |
Annual Sum or Average | 0.453957E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.20 | |
Maximum of Months | 0.158602E+10 | 9974.48 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198337E+10 | 15141.87 | 17-JAN-05:01 | 1.60 |
February | 0.949768E+09 | 15005.93 | 21-FEB-05:11 | 1.70 |
March | 0.337392E+09 | 13332.37 | 06-MAR-06:01 | 6.70 |
April | 0.114653E+09 | 12730.42 | 18-APR-05:02 | 3.30 |
May | 10783678.88 | 10625.01 | 18-MAY-06:02 | 5.68 |
June | 329849.46 | 609.88 | 14-JUN-06:05 | 10.10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 3444727.84 | 8113.48 | 27-SEP-06:03 | 8.40 |
October | 0.115423E+09 | 12456.65 | 16-OCT-05:02 | 7.12 |
November | 0.698759E+09 | 13988.02 | 24-NOV-05:02 | 2.70 |
December | 0.153476E+10 | 14824.45 | 18-DEC-05:01 | 3.40 |
Annual Sum or Average | 0.574868E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.60 | |
Maximum of Months | 0.198337E+10 | 15141.87 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163918E+10 | 9915.32 | 17-JAN-05:01 | 1.60 |
February | 0.844858E+09 | 9833.23 | 21-FEB-05:11 | 1.70 |
March | 0.283699E+09 | 8629.07 | 13-MAR-05:01 | 6.70 |
April | 85641137.79 | 8216.10 | 18-APR-05:02 | 3.30 |
May | 9027001.56 | 6822.09 | 18-MAY-06:02 | 5.68 |
June | 245344.73 | 655.21 | 14-JUN-06:05 | 10.10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 2862704.07 | 5179.83 | 28-SEP-06:03 | 8.40 |
October | 99894515.28 | 8094.08 | 16-OCT-05:02 | 7.12 |
November | 0.583895E+09 | 9164.02 | 13-NOV-05:02 | 1.20 |
December | 0.125541E+10 | 9720.26 | 18-DEC-05:01 | 3.40 |
Annual Sum or Average | 0.480471E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.20 | |
Maximum of Months | 0.163918E+10 | 9915.32 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138925E+10 | 7040.15 | 02-JAN-05:11 | 6.10 |
February | 0.542027E+09 | 6498.46 | 21-FEB-05:02 | 1.70 |
March | 88792420.51 | 5978.23 | 06-MAR-06:01 | 6.70 |
April | 16461841.89 | 5717.96 | 18-APR-06:01 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 4545477.33 | 5580.09 | 30-OCT-06:03 | 7.20 |
November | 0.115208E+09 | 5875.59 | 24-NOV-06:01 | 2.02 |
December | 0.590040E+09 | 6449.81 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.274633E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.138925E+10 | 7040.15 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.864975E+09 | 7261.00 | 02-JAN-05:11 | 6.10 |
February | 0.278539E+09 | 6451.68 | 21-FEB-06:01 | 1.70 |
March | 38289584.70 | 5909.53 | 06-MAR-06:01 | 6.70 |
April | 6076731.29 | 5597.27 | 18-APR-06:01 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 3012103.09 | 3868.33 | 31-OCT-06:03 | 10.18 |
November | 77000903.61 | 5914.61 | 24-NOV-06:01 | 2.02 |
December | 0.396241E+09 | 6557.14 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.166413E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.864975E+09 | 7261.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.489292E+10 | 12345.26 | 06-JAN-07:10 | -2.3 |
February | 0.307941E+10 | 11646.17 | 14-FEB-07:10 | 0.68 |
March | 0.240693E+10 | 11277.79 | 01-MAR-07:10 | -0.1 |
April | 0.145530E+10 | 10808.92 | 19-APR-06:10 | 2.48 |
May | 0.986750E+09 | 9758.23 | 18-MAY-06:10 | 5.68 |
June | 0.600027E+09 | 8684.83 | 15-JUN-06:20 | 9.80 |
July | 0.245158E+09 | 8493.30 | 13-JUL-06:07 | 12.98 |
August | 0.205123E+09 | 8528.67 | 18-AUG-06:20 | 11.77 |
September | 0.554172E+09 | 9056.11 | 28-SEP-06:10 | 8.40 |
October | 0.126644E+10 | 9648.64 | 24-OCT-06:10 | 6.28 |
November | 0.274230E+10 | 11602.05 | 24-NOV-07:10 | 1.20 |
December | 0.390295E+10 | 12265.01 | 26-DEC-07:50 | -1.2 |
Annual Sum or Average | 0.223375E+11 | |||
Minimum of Months | 0.205123E+09 | 8493.30 | -2.3 | |
Maximum of Months | 0.489292E+10 | 12345.26 | 12.98 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.872309E+09 | 7200.07 | 02-JAN-05:11 | 6.10 |
February | 0.285533E+09 | 6277.15 | 21-FEB-06:01 | 1.70 |
March | 53123584.18 | 5724.93 | 06-MAR-06:01 | 6.70 |
April | 10604070.74 | 5705.94 | 17-APR-06:02 | 6.10 |
May | 8794.13 | 73.28 | 18-MAY-06:02 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 3514793.58 | 3580.66 | 31-OCT-06:03 | 10.18 |
November | 79115956.88 | 5885.04 | 24-NOV-06:01 | 2.02 |
December | 0.383604E+09 | 6411.10 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.168781E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.872309E+09 | 7200.07 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120568E+10 | 7687.46 | 02-JAN-05:01 | 6.10 |
February | 0.440129E+09 | 7329.44 | 21-FEB-05:02 | 1.70 |
March | 69262427.66 | 6710.11 | 06-MAR-06:01 | 6.70 |
April | 11590639.35 | 6305.51 | 18-APR-06:01 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 13072924.50 | 6199.24 | 30-OCT-06:03 | 7.20 |
November | 0.215283E+09 | 6762.13 | 24-NOV-06:01 | 2.02 |
December | 0.687824E+09 | 7433.10 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.264284E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.120568E+10 | 7687.46 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.776908E+09 | 7633.63 | 02-JAN-05:01 | 6.10 |
February | 0.267755E+09 | 7119.87 | 21-FEB-05:02 | 1.70 |
March | 39249362.28 | 6433.60 | 13-MAR-05:01 | 6.70 |
April | 7047607.11 | 6086.54 | 17-APR-06:02 | 6.10 |
May | 231200.33 | 1926.67 | 18-MAY-06:02 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 12752936.79 | 6065.21 | 24-OCT-06:02 | 6.28 |
November | 0.150569E+09 | 6410.45 | 24-NOV-06:01 | 2.02 |
December | 0.478103E+09 | 7314.82 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.173262E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.776908E+09 | 7633.63 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.889964E+09 | 11553.54 | 02-JAN-05:01 | 6.10 |
February | 0.297631E+09 | 10248.79 | 21-FEB-06:01 | 1.70 |
March | 55347536.86 | 9588.19 | 06-MAR-06:01 | 6.70 |
April | 12754410.82 | 9181.36 | 17-APR-06:02 | 6.10 |
May | 174510.79 | 1454.26 | 18-MAY-06:02 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 12692027.29 | 8365.53 | 16-OCT-06:03 | 6.60 |
November | 0.157627E+09 | 9691.14 | 24-NOV-06:01 | 2.02 |
December | 0.541743E+09 | 10929.73 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.196793E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.889964E+09 | 11553.54 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.761173E+09 | 7585.29 | 02-JAN-05:01 | 6.10 |
February | 0.269985E+09 | 7091.54 | 21-FEB-05:02 | 1.70 |
March | 51132003.02 | 6220.33 | 06-MAR-06:01 | 6.70 |
April | 10985408.99 | 6046.33 | 17-APR-06:02 | 6.10 |
May | 269282.30 | 2244.02 | 18-MAY-06:02 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 12783970.81 | 6069.59 | 24-OCT-06:02 | 6.28 |
November | 0.149739E+09 | 6354.82 | 24-NOV-06:03 | 2.02 |
December | 0.451752E+09 | 7246.28 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.170782E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.761173E+09 | 7585.29 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.208150E+11 | 18520.31 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.188385E+11 | 18520.31 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.216654E+11 | 18520.31 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.200796E+11 | 18520.31 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.212402E+11 | 18520.31 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.208620E+11 | 18520.31 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.204550E+11 | 18520.31 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.216654E+11 | 18520.31 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.200739E+11 | 18520.31 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.208179E+11 | 18520.31 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.203773E+11 | 18520.31 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.204522E+11 | 18520.31 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.247342E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.188385E+11 | 18520.31 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.216654E+11 | 18520.31 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.865365E+09 | 1168.55 | 02-JAN-16:30 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.736296E+09 | 1090.39 | 02-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.830116E+09 | 995.39 | 22-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.720164E+09 | 861.00 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.764392E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.751710E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.706838E+09 | 833.77 | 12-JUL-08:30 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.793675E+09 | 790.69 | 02-AUG-07:30 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.733407E+09 | 1000.45 | 25-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.796506E+09 | 1157.78 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.840980E+09 | 1168.55 | 06-NOV-16:49 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.858469E+09 | 1168.55 | 01-DEC-16:19 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.939792E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.706838E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.865365E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.539322E+09 | 739.79 | 02-JAN-16:30 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.463126E+09 | 695.43 | 02-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.524567E+09 | 611.93 | 22-MAR-07:10 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.456320E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.485172E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.477444E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.449495E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.504424E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.463035E+09 | 616.23 | 25-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.500738E+09 | 731.27 | 31-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.526780E+09 | 739.79 | 06-NOV-16:49 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.532386E+09 | 739.79 | 01-DEC-16:19 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.592281E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.449495E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.539322E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.840685E+09 | 1168.55 | 02-JAN-16:30 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.722500E+09 | 1072.56 | 02-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.825251E+09 | 987.68 | 22-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.720790E+09 | 850.00 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.766569E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.754588E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.711273E+09 | 810.16 | 12-JUL-07:30 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.796745E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.731918E+09 | 994.61 | 25-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.785245E+09 | 1155.78 | 31-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.822919E+09 | 1168.55 | 06-NOV-16:49 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.826519E+09 | 1168.55 | 01-DEC-16:19 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.930500E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.711273E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.840685E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.539175E+09 | 739.74 | 02-JAN-16:30 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.460394E+09 | 676.95 | 02-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.523957E+09 | 636.79 | 22-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.456029E+09 | 571.16 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.484233E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.476481E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.449230E+09 | 584.83 | 12-JUL-07:30 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.503181E+09 | 584.12 | 28-AUG-07:30 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.464442E+09 | 639.24 | 25-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.501127E+09 | 733.06 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.525417E+09 | 739.74 | 06-NOV-16:49 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.531580E+09 | 739.74 | 01-DEC-16:19 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.591525E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.449230E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.539175E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.862125E+09 | 1168.55 | 02-JAN-16:30 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.733981E+09 | 1086.84 | 02-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.828569E+09 | 987.76 | 22-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.719719E+09 | 847.28 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.763909E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.751297E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.706517E+09 | 819.15 | 12-JUL-08:30 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.793219E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.732668E+09 | 993.10 | 25-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.794509E+09 | 1157.31 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.837737E+09 | 1168.55 | 06-NOV-16:49 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.854414E+09 | 1168.55 | 01-DEC-16:19 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.937867E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.706517E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.862125E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.538220E+09 | 739.79 | 02-JAN-16:30 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.462379E+09 | 693.89 | 02-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.524010E+09 | 607.23 | 22-MAR-07:10 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.456080E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.484895E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.477203E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.449163E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.504043E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.462678E+09 | 611.72 | 25-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.499929E+09 | 730.96 | 31-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.525783E+09 | 739.79 | 06-NOV-16:49 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.530809E+09 | 739.79 | 01-DEC-16:19 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.591519E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.449163E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.538220E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.838394E+09 | 1168.55 | 02-JAN-16:30 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.721156E+09 | 1067.93 | 02-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.824310E+09 | 979.62 | 22-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.720274E+09 | 835.71 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.766076E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.754129E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.710535E+09 | 794.00 | 12-JUL-07:30 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.796137E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.731261E+09 | 986.95 | 25-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.784211E+09 | 1155.19 | 31-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.821271E+09 | 1168.55 | 06-NOV-16:49 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.824597E+09 | 1168.55 | 01-DEC-16:19 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.929235E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.710535E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.838394E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.538051E+09 | 739.74 | 02-JAN-16:30 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.459587E+09 | 674.81 | 02-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.523368E+09 | 633.32 | 22-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.455710E+09 | 565.49 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.484024E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.476243E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.448917E+09 | 579.74 | 12-JUL-07:30 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.502793E+09 | 578.69 | 28-AUG-07:30 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.463931E+09 | 635.87 | 25-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.500255E+09 | 732.84 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.524391E+09 | 739.74 | 06-NOV-16:49 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.530324E+09 | 739.74 | 01-DEC-16:19 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.590759E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.448917E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.538051E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.865363E+09 | 1168.55 | 02-JAN-16:30 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.736254E+09 | 1090.39 | 02-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.830115E+09 | 995.37 | 22-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.720164E+09 | 860.98 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.764391E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.751710E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.706838E+09 | 833.75 | 12-JUL-08:30 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.793675E+09 | 790.67 | 02-AUG-07:30 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.733407E+09 | 1000.44 | 25-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.796505E+09 | 1157.78 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.840978E+09 | 1168.55 | 06-NOV-16:49 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.858468E+09 | 1168.55 | 01-DEC-16:19 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.939787E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.706838E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.865363E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.539321E+09 | 739.79 | 02-JAN-16:30 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.463126E+09 | 695.43 | 02-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.524566E+09 | 611.93 | 22-MAR-07:10 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.456319E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.485171E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.477444E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.449495E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.504424E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.463035E+09 | 616.22 | 25-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.500737E+09 | 731.27 | 31-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.526779E+09 | 739.79 | 06-NOV-16:49 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.532386E+09 | 739.79 | 01-DEC-16:19 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.592280E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.449495E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.539321E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.840684E+09 | 1168.55 | 02-JAN-16:30 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.722499E+09 | 1072.56 | 02-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.825250E+09 | 987.67 | 22-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.720790E+09 | 849.99 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.766569E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.754587E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.711273E+09 | 810.14 | 12-JUL-07:30 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.796745E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.731918E+09 | 994.60 | 25-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.785244E+09 | 1155.78 | 31-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.822918E+09 | 1168.55 | 06-NOV-16:49 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.826519E+09 | 1168.55 | 01-DEC-16:19 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.930500E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.711273E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.840684E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.539174E+09 | 739.74 | 02-JAN-16:30 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.460394E+09 | 676.94 | 02-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.523956E+09 | 636.78 | 22-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.456028E+09 | 571.15 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.484233E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.476480E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.449230E+09 | 584.82 | 12-JUL-07:30 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.503181E+09 | 584.12 | 28-AUG-07:30 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.464441E+09 | 639.23 | 25-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.501127E+09 | 733.06 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.525417E+09 | 739.74 | 06-NOV-16:49 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.531580E+09 | 739.74 | 01-DEC-16:19 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.591524E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.449230E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.539174E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.208150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.200796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.212402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.208620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.204550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.200739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.208179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.203773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.204522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.247342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.865365E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.805544E+09 |
February | 0.901968E+09 | 0.736296E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719554E+09 |
March | 0.107774E+10 | 0.830116E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704949E+09 |
April | 0.956342E+09 | 0.720164E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1785629.25 | 0.689560E+09 |
May | 0.103597E+10 | 0.764392E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42235.23 | 0.567179E+09 |
June | 0.103308E+10 | 0.751710E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 466740.37 | 0.480125E+09 |
July | 0.959235E+09 | 0.706838E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7227897.52 | 0.405676E+09 |
August | 0.107774E+10 | 0.793675E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10985906.98 | 0.328927E+09 |
September | 0.956342E+09 | 0.733407E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43169.49 | 0.262131E+09 |
October | 0.994195E+09 | 0.796506E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564340E+09 |
November | 0.984487E+09 | 0.840980E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625349E+09 |
December | 0.959235E+09 | 0.858469E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681390E+09 |
Annual Sum or Average | 0.119305E+11 | 0.939792E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20551578.83 | 0.683472E+10 |
Minimum of Months | 0.901968E+09 | 0.706838E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262131E+09 |
Maximum of Months | 0.107774E+10 | 0.865365E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10985906.98 | 0.805544E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.539322E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536212E+09 |
February | 0.571020E+09 | 0.463126E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484693E+09 |
March | 0.682301E+09 | 0.524567E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473735E+09 |
April | 0.605444E+09 | 0.456320E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1076904.33 | 0.467539E+09 |
May | 0.655854E+09 | 0.485172E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28160.46 | 0.382240E+09 |
June | 0.654023E+09 | 0.477444E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 311170.60 | 0.325343E+09 |
July | 0.607275E+09 | 0.449495E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3621902.80 | 0.273454E+09 |
August | 0.682301E+09 | 0.504424E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6807969.22 | 0.223277E+09 |
September | 0.605444E+09 | 0.463035E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28781.95 | 0.176733E+09 |
October | 0.629407E+09 | 0.500738E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380174E+09 |
November | 0.623262E+09 | 0.526780E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416195E+09 |
December | 0.607275E+09 | 0.532386E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453950E+09 |
Annual Sum or Average | 0.755301E+10 | 0.592281E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11874889.36 | 0.459355E+10 |
Minimum of Months | 0.571020E+09 | 0.449495E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176733E+09 |
Maximum of Months | 0.682301E+09 | 0.539322E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6807969.22 | 0.536212E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.840685E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823620E+09 |
February | 0.901968E+09 | 0.722500E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765145E+09 |
March | 0.107774E+10 | 0.825251E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736610E+09 |
April | 0.956342E+09 | 0.720790E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1102586.91 | 0.715681E+09 |
May | 0.103597E+10 | 0.766569E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42227.53 | 0.579371E+09 |
June | 0.103308E+10 | 0.754588E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 466712.04 | 0.485593E+09 |
July | 0.959235E+09 | 0.711273E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4472576.79 | 0.412782E+09 |
August | 0.107774E+10 | 0.796745E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9962090.02 | 0.338393E+09 |
September | 0.956342E+09 | 0.731918E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43078.36 | 0.275375E+09 |
October | 0.994195E+09 | 0.785245E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600030E+09 |
November | 0.984487E+09 | 0.822919E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643777E+09 |
December | 0.959235E+09 | 0.826519E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703344E+09 |
Annual Sum or Average | 0.119305E+11 | 0.930500E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16089271.65 | 0.707972E+10 |
Minimum of Months | 0.901968E+09 | 0.711273E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275375E+09 |
Maximum of Months | 0.107774E+10 | 0.840685E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9962090.02 | 0.823620E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.539175E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537586E+09 |
February | 0.570983E+09 | 0.460394E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487918E+09 |
March | 0.682256E+09 | 0.523957E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477373E+09 |
April | 0.605404E+09 | 0.456029E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 529843.44 | 0.469062E+09 |
May | 0.655811E+09 | 0.484233E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28161.33 | 0.390536E+09 |
June | 0.653980E+09 | 0.476481E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 311160.97 | 0.326190E+09 |
July | 0.607235E+09 | 0.449230E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3483246.85 | 0.282912E+09 |
August | 0.682256E+09 | 0.503181E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7037976.14 | 0.228119E+09 |
September | 0.605404E+09 | 0.464442E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28781.83 | 0.181957E+09 |
October | 0.629366E+09 | 0.501127E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382735E+09 |
November | 0.623221E+09 | 0.525417E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417671E+09 |
December | 0.607235E+09 | 0.531580E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455417E+09 |
Annual Sum or Average | 0.755252E+10 | 0.591525E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11419170.57 | 0.463748E+10 |
Minimum of Months | 0.570983E+09 | 0.449230E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181957E+09 |
Maximum of Months | 0.682256E+09 | 0.539175E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7037976.14 | 0.537586E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.862125E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459281E+09 |
February | 0.901968E+09 | 0.733981E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412331E+09 |
March | 0.107774E+10 | 0.828569E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395839E+09 |
April | 0.956342E+09 | 0.719719E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1172237.09 | 0.378630E+09 |
May | 0.103597E+10 | 0.763909E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26257.44 | 0.308612E+09 |
June | 0.103308E+10 | 0.751297E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 263729.50 | 0.260430E+09 |
July | 0.959235E+09 | 0.706517E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5219968.77 | 0.219412E+09 |
August | 0.107774E+10 | 0.793219E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6417888.06 | 0.178649E+09 |
September | 0.956342E+09 | 0.732668E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26159.74 | 0.146990E+09 |
October | 0.994195E+09 | 0.794509E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332409E+09 |
November | 0.984487E+09 | 0.837737E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372186E+09 |
December | 0.959235E+09 | 0.854414E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400010E+09 |
Annual Sum or Average | 0.119305E+11 | 0.937867E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13126240.60 | 0.386478E+10 |
Minimum of Months | 0.901968E+09 | 0.706517E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146990E+09 |
Maximum of Months | 0.107774E+10 | 0.862125E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6417888.06 | 0.459281E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.538220E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305766E+09 |
February | 0.571020E+09 | 0.462379E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279044E+09 |
March | 0.682301E+09 | 0.524010E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269930E+09 |
April | 0.605444E+09 | 0.456080E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 612055.33 | 0.263945E+09 |
May | 0.655854E+09 | 0.484895E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17504.59 | 0.213510E+09 |
June | 0.654023E+09 | 0.477203E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 175819.52 | 0.182414E+09 |
July | 0.607275E+09 | 0.449163E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2195588.96 | 0.151645E+09 |
August | 0.682301E+09 | 0.504043E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3707883.95 | 0.125551E+09 |
September | 0.605444E+09 | 0.462678E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17439.91 | 0.101581E+09 |
October | 0.629407E+09 | 0.499929E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227011E+09 |
November | 0.623262E+09 | 0.525783E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248357E+09 |
December | 0.607275E+09 | 0.530809E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266696E+09 |
Annual Sum or Average | 0.755301E+10 | 0.591519E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6726292.25 | 0.263545E+10 |
Minimum of Months | 0.571020E+09 | 0.449163E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101581E+09 |
Maximum of Months | 0.682301E+09 | 0.538220E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3707883.95 | 0.305766E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.838394E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622129E+10 |
February | 0.901968E+09 | 0.721156E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540486E+10 |
March | 0.107774E+10 | 0.824310E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571385E+10 |
April | 0.956342E+09 | 0.720274E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22805246.02 | 0.428360E+10 |
May | 0.103597E+10 | 0.766076E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2565116.94 | 0.375290E+10 |
June | 0.103308E+10 | 0.754129E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24846790.91 | 0.288353E+10 |
July | 0.959235E+09 | 0.710535E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148409E+09 | 0.188301E+10 |
August | 0.107774E+10 | 0.796137E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399222E+09 | 0.177757E+10 |
September | 0.956342E+09 | 0.731261E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5476026.15 | 0.271244E+10 |
October | 0.994195E+09 | 0.784211E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431982E+10 |
November | 0.984487E+09 | 0.821271E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543693E+10 |
December | 0.959235E+09 | 0.824597E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597592E+10 |
Annual Sum or Average | 0.119305E+11 | 0.929235E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.603324E+09 | 0.503657E+11 |
Minimum of Months | 0.901968E+09 | 0.710535E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177757E+10 |
Maximum of Months | 0.107774E+10 | 0.838394E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399222E+09 | 0.622129E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.538051E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306537E+09 |
February | 0.570983E+09 | 0.459587E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279669E+09 |
March | 0.682256E+09 | 0.523368E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270593E+09 |
April | 0.605404E+09 | 0.455710E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 337453.94 | 0.262393E+09 |
May | 0.655811E+09 | 0.484024E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17505.39 | 0.219173E+09 |
June | 0.653980E+09 | 0.476243E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 175820.99 | 0.181898E+09 |
July | 0.607235E+09 | 0.448917E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1950681.84 | 0.159785E+09 |
August | 0.682256E+09 | 0.502793E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3763040.18 | 0.129040E+09 |
September | 0.605404E+09 | 0.463931E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17440.24 | 0.105194E+09 |
October | 0.629366E+09 | 0.500255E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227564E+09 |
November | 0.623221E+09 | 0.524391E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248448E+09 |
December | 0.607235E+09 | 0.530324E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267340E+09 |
Annual Sum or Average | 0.755252E+10 | 0.590759E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6261942.58 | 0.265763E+10 |
Minimum of Months | 0.570983E+09 | 0.448917E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105194E+09 |
Maximum of Months | 0.682256E+09 | 0.538051E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3763040.18 | 0.306537E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.865363E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711171E+09 |
February | 0.901968E+09 | 0.736254E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642925E+09 |
March | 0.107774E+10 | 0.830115E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632885E+09 |
April | 0.956342E+09 | 0.720164E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1531114.23 | 0.614178E+09 |
May | 0.103597E+10 | 0.764391E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38097.65 | 0.498278E+09 |
June | 0.103308E+10 | 0.751710E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 400603.84 | 0.417729E+09 |
July | 0.959235E+09 | 0.706838E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6691196.99 | 0.352539E+09 |
August | 0.107774E+10 | 0.793675E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9364562.29 | 0.287330E+09 |
September | 0.956342E+09 | 0.733407E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38411.18 | 0.233363E+09 |
October | 0.994195E+09 | 0.796505E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514982E+09 |
November | 0.984487E+09 | 0.840978E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567794E+09 |
December | 0.959235E+09 | 0.858468E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613534E+09 |
Annual Sum or Average | 0.119305E+11 | 0.939787E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18063986.19 | 0.608671E+10 |
Minimum of Months | 0.901968E+09 | 0.706838E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233363E+09 |
Maximum of Months | 0.107774E+10 | 0.865363E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9364562.29 | 0.711171E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.539321E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473021E+09 |
February | 0.421807E+09 | 0.463126E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433035E+09 |
March | 0.502994E+09 | 0.524566E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423389E+09 |
April | 0.447140E+09 | 0.456319E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 934224.60 | 0.413871E+09 |
May | 0.484071E+09 | 0.485171E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25393.94 | 0.333817E+09 |
June | 0.482240E+09 | 0.477444E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 267066.94 | 0.281541E+09 |
July | 0.448971E+09 | 0.449495E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3504632.30 | 0.236705E+09 |
August | 0.502994E+09 | 0.504424E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5833731.90 | 0.193765E+09 |
September | 0.447140E+09 | 0.463035E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25604.81 | 0.156098E+09 |
October | 0.465148E+09 | 0.500737E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343900E+09 |
November | 0.460569E+09 | 0.526779E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376356E+09 |
December | 0.448971E+09 | 0.532386E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408266E+09 |
Annual Sum or Average | 0.557719E+10 | 0.592280E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10590654.49 | 0.407376E+10 |
Minimum of Months | 0.421807E+09 | 0.449495E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156098E+09 |
Maximum of Months | 0.502994E+09 | 0.539321E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5833731.90 | 0.473021E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.840684E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729356E+09 |
February | 0.901968E+09 | 0.722499E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683479E+09 |
March | 0.107774E+10 | 0.825250E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658477E+09 |
April | 0.956342E+09 | 0.720790E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 951076.96 | 0.634593E+09 |
May | 0.103597E+10 | 0.766569E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38090.40 | 0.508494E+09 |
June | 0.103308E+10 | 0.754587E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 400576.38 | 0.423146E+09 |
July | 0.959235E+09 | 0.711273E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3955839.74 | 0.359282E+09 |
August | 0.107774E+10 | 0.796745E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8393755.94 | 0.295488E+09 |
September | 0.956342E+09 | 0.731918E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38223.42 | 0.243705E+09 |
October | 0.994195E+09 | 0.785244E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542124E+09 |
November | 0.984487E+09 | 0.822918E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582949E+09 |
December | 0.959235E+09 | 0.826519E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633008E+09 |
Annual Sum or Average | 0.119305E+11 | 0.930500E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13777562.83 | 0.629410E+10 |
Minimum of Months | 0.901968E+09 | 0.711273E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243705E+09 |
Maximum of Months | 0.107774E+10 | 0.840684E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8393755.94 | 0.729356E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.539174E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474330E+09 |
February | 0.570983E+09 | 0.460394E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435274E+09 |
March | 0.682256E+09 | 0.523956E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426873E+09 |
April | 0.605404E+09 | 0.456028E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 445830.02 | 0.416332E+09 |
May | 0.655811E+09 | 0.484233E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25402.23 | 0.342766E+09 |
June | 0.653980E+09 | 0.476480E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 267073.91 | 0.284329E+09 |
July | 0.607235E+09 | 0.449230E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2926094.79 | 0.246011E+09 |
August | 0.682256E+09 | 0.503181E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5854476.00 | 0.199418E+09 |
September | 0.605404E+09 | 0.464441E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25608.05 | 0.161377E+09 |
October | 0.629366E+09 | 0.501127E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347128E+09 |
November | 0.623221E+09 | 0.525417E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377869E+09 |
December | 0.607235E+09 | 0.531580E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409609E+09 |
Annual Sum or Average | 0.755252E+10 | 0.591524E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9544484.99 | 0.412132E+10 |
Minimum of Months | 0.570983E+09 | 0.449230E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161377E+09 |
Maximum of Months | 0.682256E+09 | 0.539174E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5854476.00 | 0.474330E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995262E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.916067E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895853E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1463693.10 | 0.853640E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3171.79 | 0.684467E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189561.35 | 0.568967E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5793223.57 | 0.479436E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8775690.34 | 0.396019E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1042.74 | 0.326358E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737220E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.813613E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876413E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16226382.88 | 0.854331E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326358E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8775690.34 | 0.995262E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120623E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110571E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109655E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2257141.86 | 0.105761E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4236.64 | 0.859070E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242339.45 | 0.719248E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7632083.59 | 0.605585E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11489362.66 | 0.499445E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 950.88 | 0.405732E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.889115E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970650E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105054E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21626115.08 | 0.104655E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405732E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11489362.66 | 0.120623E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120020E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110215E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108544E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1067853.71 | 0.107469E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895158E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69639.42 | 0.756065E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2438436.47 | 0.640459E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7866326.27 | 0.513030E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410651E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874684E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943644E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102334E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11442255.87 | 0.105195E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410651E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7866326.27 | 0.120020E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 18520.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 18520.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 18520.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 18520.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 18520.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 18520.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 18520.31 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 18520.31 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 18520.31 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 18520.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 18520.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 18520.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:30 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1351.62 | 12-JAN-22:03 |
February | 1306.65 | 01-FEB-10:09 | 1090.39 | 02-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1271.91 | 16-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 995.39 | 22-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1159.51 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 861.00 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.15 | 01-APR-17:03 | 1267.92 | 10-APR-21:05 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.56 | 05-MAY-16:00 | 945.33 | 22-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 28-JUN-16:00 | 1240.49 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 833.77 | 12-JUL-08:30 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.51 | 23-JUL-14:00 | 628.49 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 790.69 | 02-AUG-07:30 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.50 | 13-AUG-14:53 | 907.48 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 1000.45 | 25-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.64 | 14-SEP-17:00 | 590.52 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1157.78 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1169.90 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1270.02 | 29-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:19 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1051.75 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 590.52 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 224.15 | 1351.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 739.79 | 02-JAN-16:30 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 899.81 | 12-JAN-22:03 |
February | 827.22 | 01-FEB-10:09 | 695.43 | 02-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 847.14 | 16-FEB-22:03 |
March | 827.22 | 01-MAR-10:09 | 611.93 | 22-MAR-07:10 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 781.71 | 28-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.89 | 01-APR-17:03 | 850.46 | 07-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.71 | 05-MAY-16:00 | 626.19 | 22-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 | 28-JUN-16:00 | 819.61 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.10 | 23-JUL-15:50 | 414.89 | 02-JUL-04:00 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.03 | 08-AUG-17:00 | 605.45 | 11-AUG-04:00 |
September | 827.22 | 01-SEP-09:09 | 616.23 | 25-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 | 14-SEP-17:00 | 387.57 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 731.27 | 31-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 778.78 | 31-OCT-21:03 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 06-NOV-16:49 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 845.68 | 29-NOV-22:03 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-16:19 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 700.48 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.57 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 139.89 | 899.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:30 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1351.91 | 12-JAN-22:03 |
February | 1306.65 | 01-FEB-10:09 | 1072.56 | 02-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1288.37 | 19-FEB-12:00 |
March | 1306.65 | 01-MAR-10:09 | 987.68 | 22-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1207.84 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 850.00 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.35 | 01-APR-17:30 | 1283.47 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.56 | 05-MAY-16:00 | 945.80 | 22-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 28-JUN-16:00 | 1234.17 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 810.16 | 12-JUL-07:30 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.57 | 23-JUL-15:50 | 633.69 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.54 | 08-AUG-17:00 | 920.44 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 994.61 | 25-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.64 | 14-SEP-17:00 | 588.79 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1155.78 | 31-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1169.46 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1269.90 | 29-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:19 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1052.50 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 588.79 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 129.35 | 1351.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-16:30 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 899.67 | 12-JAN-22:03 |
February | 827.17 | 01-FEB-10:09 | 676.95 | 02-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 846.93 | 16-FEB-22:03 |
March | 827.17 | 01-MAR-10:09 | 636.79 | 22-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 778.02 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 571.16 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.63 | 01-APR-16:00 | 847.63 | 10-APR-21:05 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.71 | 05-MAY-16:00 | 628.96 | 22-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 | 28-JUN-16:00 | 814.84 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 584.83 | 12-JUL-07:30 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.70 | 23-JUL-13:23 | 423.38 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 584.12 | 28-AUG-07:30 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.74 | 13-AUG-12:00 | 620.80 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 639.24 | 25-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 | 14-SEP-17:00 | 386.18 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 733.06 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 778.41 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 06-NOV-16:49 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 845.48 | 29-NOV-22:03 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:19 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 700.67 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.18 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 91.70 | 899.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:30 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 772.05 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 1086.84 | 02-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 710.66 | 16-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 987.76 | 22-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 660.56 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 847.28 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.44 | 01-APR-17:03 | 703.45 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.12 | 05-MAY-16:00 | 544.55 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | 28-JUN-16:00 | 726.74 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 819.15 | 12-JUL-08:30 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.12 | 23-JUL-16:00 | 364.41 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.11 | 13-AUG-15:10 | 509.61 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 993.10 | 25-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 | 14-SEP-17:00 | 345.34 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1157.31 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 630.40 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 739.83 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:19 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 591.44 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.34 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 149.44 | 772.05 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 739.79 | 02-JAN-16:30 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 510.97 | 12-JAN-24:00 |
February | 827.22 | 01-FEB-10:09 | 693.89 | 02-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 470.58 | 16-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 607.23 | 22-MAR-07:10 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 459.41 | 28-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.36 | 01-APR-17:03 | 492.96 | 07-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 | 05-MAY-16:00 | 361.09 | 18-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 28-JUN-16:00 | 493.92 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.65 | 23-JUL-15:50 | 243.60 | 02-JUL-04:00 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.60 | 08-AUG-17:00 | 352.65 | 11-AUG-04:00 |
September | 827.22 | 01-SEP-09:09 | 611.72 | 25-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 | 14-SEP-17:00 | 229.08 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 730.96 | 31-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 419.94 | 31-OCT-21:03 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 06-NOV-16:49 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 490.11 | 29-NOV-23:00 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-16:19 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 392.58 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.08 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 86.36 | 510.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:30 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 28996.23 | 06-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1067.93 | 02-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 26931.61 | 09-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 979.62 | 22-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 26342.66 | 01-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 835.71 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3680.46 | 27-APR-16:10 | 22733.32 | 19-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 781.82 | 05-MAY-16:10 | 18077.15 | 18-MAY-06:02 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3311.61 | 28-JUN-17:00 | 13901.85 | 01-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 794.00 | 12-JUL-07:30 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5864.52 | 31-JUL-16:10 | 11724.83 | 03-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8589.18 | 10-AUG-17:00 | 13474.22 | 01-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 986.95 | 25-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1234.26 | 14-SEP-17:00 | 14950.05 | 27-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 1155.19 | 31-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 17792.93 | 13-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 24577.15 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:19 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 28215.24 | 26-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11724.83 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 8589.18 | 28996.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-16:30 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 510.86 | 12-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 674.81 | 02-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 469.03 | 16-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 633.32 | 22-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 449.31 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 565.49 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.76 | 01-APR-17:03 | 468.25 | 07-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 | 05-MAY-16:00 | 362.22 | 22-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 28-JUN-16:00 | 481.53 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 579.74 | 12-JUL-07:30 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.54 | 23-JUL-14:00 | 251.95 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 578.69 | 28-AUG-07:30 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.60 | 08-AUG-17:00 | 364.05 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 635.87 | 25-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 | 14-SEP-17:00 | 229.27 | 30-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 732.84 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 419.97 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 06-NOV-16:49 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 489.24 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:19 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 393.08 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.27 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 55.54 | 510.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:30 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1188.86 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 1090.39 | 02-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1095.69 | 16-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 995.37 | 22-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1053.30 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 860.98 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.15 | 01-APR-17:03 | 1125.81 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.75 | 05-MAY-16:00 | 840.97 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.85 | 28-JUN-16:00 | 1122.85 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 833.75 | 12-JUL-08:30 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.28 | 23-JUL-15:40 | 568.52 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 790.67 | 02-AUG-07:30 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.84 | 13-AUG-15:10 | 796.49 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 1000.44 | 25-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 14-SEP-17:00 | 534.65 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1157.78 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 983.96 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1123.43 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:19 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 912.69 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.65 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 195.15 | 1188.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 739.79 | 02-JAN-16:30 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 785.40 | 12-JAN-24:00 |
February | 805.43 | 01-FEB-08:09 | 695.43 | 02-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 724.25 | 16-FEB-04:00 |
March | 805.43 | 01-MAR-08:09 | 611.93 | 22-MAR-07:10 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 707.61 | 28-MAR-24:00 |
April | 805.43 | 03-APR-07:10 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.48 | 01-APR-17:03 | 755.27 | 07-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 05-MAY-16:00 | 553.21 | 18-MAY-05:00 |
June | 805.43 | 01-JUN-07:10 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.90 | 28-JUN-16:00 | 741.97 | 13-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.98 | 23-JUL-16:00 | 375.38 | 02-JUL-04:00 |
August | 805.43 | 01-AUG-07:10 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 | 13-AUG-15:10 | 531.24 | 11-AUG-04:00 |
September | 805.43 | 01-SEP-07:10 | 616.22 | 25-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 14-SEP-17:00 | 350.45 | 18-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 731.27 | 31-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 654.62 | 31-OCT-21:03 |
November | 805.43 | 01-NOV-07:10 | 739.79 | 06-NOV-16:49 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 743.84 | 29-NOV-23:00 |
December | 805.43 | 01-DEC-08:09 | 739.79 | 01-DEC-16:19 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 605.24 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.45 | |||||
Maximum of Months | 805.43 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 123.48 | 785.40 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:30 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1190.69 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 1072.56 | 02-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1161.02 | 19-FEB-12:00 |
March | 1306.65 | 01-MAR-10:09 | 987.67 | 22-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1093.18 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 849.99 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.47 | 01-APR-17:03 | 1141.80 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.75 | 05-MAY-16:00 | 836.00 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.85 | 28-JUN-16:00 | 1118.44 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 810.14 | 12-JUL-07:30 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.80 | 23-JUL-16:20 | 572.53 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.53 | 08-AUG-17:00 | 807.19 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 994.60 | 25-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 14-SEP-17:00 | 534.39 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1155.78 | 31-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 983.57 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:49 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1123.66 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:19 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 918.43 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.39 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 113.47 | 1190.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-16:30 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 785.41 | 12-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 676.94 | 02-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 721.99 | 16-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 636.78 | 22-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 706.03 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 571.15 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.23 | 01-APR-16:00 | 745.33 | 07-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 05-MAY-16:00 | 555.89 | 22-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.90 | 28-JUN-16:00 | 739.26 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 584.82 | 12-JUL-07:30 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.60 | 23-JUL-13:55 | 382.53 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 584.12 | 28-AUG-07:30 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.69 | 08-AUG-17:00 | 544.03 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 639.23 | 25-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 14-SEP-17:00 | 351.01 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 733.06 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 654.47 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 06-NOV-16:49 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 742.67 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:19 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 606.44 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.01 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 76.60 | 785.41 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1712.24 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1587.19 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1516.26 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.84 | 01-APR-17:03 | 1588.38 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.19 | 05-MAY-16:00 | 1196.10 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.75 | 28-JUN-15:10 | 1591.66 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.71 | 23-JUL-14:00 | 800.21 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.34 | 13-AUG-14:53 | 1098.98 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 | 14-SEP-17:00 | 741.65 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1385.72 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1608.08 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1296.13 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 741.65 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.84 | 1712.24 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2096.33 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1924.95 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1870.34 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.00 | 01-APR-17:03 | 1993.94 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 | 05-MAY-16:00 | 1481.28 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.13 | 28-JUN-15:00 | 1998.61 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.38 | 23-JUL-14:00 | 998.01 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.82 | 13-AUG-14:53 | 1398.54 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 | 14-SEP-17:00 | 911.94 | 30-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1683.06 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1951.80 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1589.63 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 911.94 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.00 | 2096.33 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2002.78 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1835.18 | 16-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1739.63 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.33 | 01-APR-17:03 | 1940.08 | 10-APR-21:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1415.38 | 22-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.57 | 28-JUN-17:00 | 1850.61 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.38 | 24-JUL-14:00 | 934.30 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.08 | 08-AUG-17:00 | 1362.71 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 882.38 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1732.35 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1932.30 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1632.76 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 882.38 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.33 | 2002.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12527.73 | 13-JAN-08:30 | 12070.02 | 11086.35 | 37040.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16292.20 | 28-FEB-08:20 | 12070.02 | 11086.35 | 37040.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20097.25 | 16-MAR-07:03 | 60350.08 | 55431.73 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39012.47 | 27-APR-05:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40816.04 | 06-MAY-05:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41772.22 | 12-JUN-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 43138.58 | 10-JUL-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43144.52 | 14-AUG-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43165.21 | 05-SEP-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40746.14 | 03-OCT-05:02 | 3176.32 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17777.53 | 09-NOV-08:02 | 54315.07 | 49888.55 | 166682.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15470.58 | 07-DEC-08:20 | 12070.02 | 11086.35 | 37040.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12527.73 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43165.21 | 60350.08 | 55431.73 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 56.62 | 11-JAN-17:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.24 |
February | 1941.30 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.78 |
March | 2869.37 | 14-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.66 |
April | 8496.55 | 27-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.95 | 0.00 |
May | 8703.72 | 15-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.42 |
June | 8771.05 | 28-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.35 |
July | 10010.82 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.38 | 0.00 |
August | 10208.36 | 10-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.21 | 0.00 |
September | 7903.80 | 14-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.11 |
October | 5378.54 | 04-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.81 |
November | 2495.84 | 04-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.10 |
December | 336.50 | 02-DEC-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 56.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10208.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.38 | 255.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1061.57 | 07-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.18 |
February | 1127.83 | 10-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.42 |
March | 2198.23 | 02-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.90 |
April | 2775.09 | 27-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.47 | 0.00 |
May | 2867.11 | 15-MAY-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.70 |
June | 3313.69 | 28-JUN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.80 | 0.00 |
July | 4332.33 | 31-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.84 | 0.00 |
August | 4447.46 | 14-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.56 | 0.00 |
September | 3468.97 | 14-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.75 |
October | 1988.48 | 04-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.39 |
November | 1404.58 | 10-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.47 |
December | 722.87 | 07-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 722.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4447.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.84 | 210.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2038.85 | 06-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.37 |
February | 2225.91 | 09-FEB-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.35 |
March | 2921.03 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.39 |
April | 3175.44 | 27-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.15 | 0.00 |
May | 3317.47 | 15-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.09 |
June | 3698.37 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.56 | 0.00 |
July | 4705.73 | 31-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.99 | 0.00 |
August | 4888.55 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.08 | 0.00 |
September | 4138.24 | 11-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.30 |
October | 2897.74 | 04-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.02 |
November | 2360.82 | 10-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.67 |
December | 2065.50 | 06-DEC-17:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2038.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4888.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.99 | 177.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6753.51 | 12-JAN-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7540.57 | 28-FEB-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8762.44 | 02-MAR-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25349.12 | 28-APR-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28457.31 | 08-MAY-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29949.61 | 22-JUN-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30153.09 | 28-JUL-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31437.48 | 14-AUG-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30500.34 | 14-SEP-05:02 | 3176.32 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13834.50 | 04-OCT-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7739.89 | 06-NOV-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7071.70 | 06-DEC-16:10 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6753.51 | 0.00 | 2463.50 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31437.48 | 6035.01 | 5543.17 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6533.61 | 11-JAN-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7529.24 | 28-FEB-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7874.59 | 02-MAR-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15869.92 | 27-APR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16551.69 | 15-MAY-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17468.70 | 28-JUN-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29849.28 | 24-JUL-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31624.06 | 14-AUG-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16859.60 | 14-SEP-15:40 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13697.14 | 04-OCT-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7360.76 | 02-NOV-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6778.77 | 05-DEC-15:40 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6533.61 | 2541.06 | 2463.50 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31624.06 | 6035.01 | 5543.17 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1180.12 | 11-JAN-16:10 | 1272.23 | 1066.25 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.31 |
February | 1473.91 | 27-FEB-16:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.42 |
March | 1559.31 | 10-MAR-15:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.17 |
April | 4503.88 | 27-APR-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 28.75 | 0.00 |
May | 4672.23 | 15-MAY-14:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.25 |
June | 5185.21 | 21-JUN-15:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 6.08 | 0.00 |
July | 6299.42 | 24-JUL-15:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 44.75 | 0.00 |
August | 5756.25 | 09-AUG-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 53.26 | 0.00 |
September | 4312.09 | 12-SEP-15:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 2.44 | 0.00 |
October | 2592.25 | 04-OCT-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.18 |
November | 1400.25 | 02-NOV-14:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.77 |
December | 1102.33 | 29-DEC-15:10 | 1272.23 | 945.95 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1102.33 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6299.42 | 1306.65 | 1066.25 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 53.26 | 106.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1018.91 | 12-JAN-07:03 | 1017.38 | 1479.56 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.42 |
February | 1319.13 | 27-FEB-15:50 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 |
March | 2336.42 | 14-MAR-10:00 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.89 |
April | 6350.03 | 27-APR-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.74 |
May | 6687.79 | 14-MAY-08:13 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.36 |
June | 11405.76 | 25-JUN-09:02 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.25 |
July | 9580.91 | 30-JUL-09:13 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.58 |
August | 12503.03 | 06-AUG-09:02 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.28 |
September | 10585.78 | 10-SEP-09:32 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.49 |
October | 4342.47 | 04-OCT-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.51 |
November | 1291.64 | 02-NOV-10:40 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.99 |
December | 1076.93 | 05-DEC-10:35 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1018.91 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | |
Maximum of Months | 12503.03 | 1654.44 | 1479.56 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6243.05 | 20-JAN-13:30 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.52 |
February | 8181.18 | 27-FEB-14:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.25 |
March | 9342.68 | 14-MAR-13:40 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.75 |
April | 11676.19 | 27-APR-13:20 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 | 0.00 |
May | 15769.15 | 14-MAY-13:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.32 |
June | 9217.88 | 28-JUN-13:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 | 0.00 |
July | 18920.11 | 30-JUL-11:53 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.75 |
August | 18673.19 | 06-AUG-13:43 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.05 |
September | 21084.76 | 10-SEP-13:32 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.59 |
October | 13105.53 | 04-OCT-13:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.38 |
November | 8334.09 | 04-NOV-13:30 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6102.88 | 05-DEC-12:30 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6102.88 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21084.76 | 1306.65 | 720.41 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 | 306.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1346.58 | 05-JAN-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.73 |
February | 3127.32 | 27-FEB-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.28 |
March | 4773.34 | 14-MAR-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.21 |
April | 7753.32 | 26-APR-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 0.00 |
May | 15193.70 | 14-MAY-16:12 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.41 |
June | 10731.62 | 18-JUN-18:23 | 0.00 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.58 |
July | 14833.55 | 23-JUL-17:02 | 0.00 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.38 |
August | 13684.05 | 06-AUG-17:02 | 0.00 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.51 |
September | 14879.46 | 10-SEP-16:12 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.43 |
October | 6310.30 | 04-OCT-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.15 |
November | 2254.60 | 04-NOV-15:40 | 84.78 | 76.01 | 370.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.94 |
December | 1458.07 | 05-DEC-15:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1346.58 | 0.00 | 76.01 | 370.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15193.70 | 805.38 | 456.05 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 303.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1172.59 | 11-JAN-16:20 | 1272.23 | 1105.38 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.05 |
February | 1382.29 | 28-FEB-15:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1440.27 | 10-MAR-14:40 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.95 |
April | 2600.30 | 27-APR-16:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 15.54 | 0.00 |
May | 3126.45 | 05-MAY-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 0.00 |
June | 3838.67 | 21-JUN-15:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 0.00 |
July | 4709.46 | 24-JUL-15:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 23.98 | 0.00 |
August | 4459.43 | 09-AUG-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 28.63 | 0.00 |
September | 3347.46 | 14-SEP-15:50 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 | 0.00 |
October | 2060.11 | 04-OCT-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.26 |
November | 1449.60 | 06-NOV-12:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.74 |
December | 1154.75 | 29-DEC-15:00 | 1306.65 | 904.15 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1154.75 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4709.46 | 1306.65 | 1105.38 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 28.63 | 57.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 874.94 | 20-JAN-10:50 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.93 |
February | 1055.99 | 27-FEB-15:40 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 |
March | 1368.18 | 14-MAR-10:00 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.84 |
April | 4686.47 | 27-APR-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.98 |
May | 5235.71 | 15-MAY-09:20 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.10 |
June | 5593.65 | 28-JUN-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.46 |
July | 10555.85 | 23-JUL-09:32 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.69 |
August | 10865.13 | 13-AUG-09:42 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.35 |
September | 5444.94 | 11-SEP-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.47 |
October | 3709.13 | 04-OCT-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.45 |
November | 1151.27 | 02-NOV-10:40 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.20 |
December | 999.02 | 05-DEC-10:30 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 874.94 | 211.95 | 126.70 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 | |
Maximum of Months | 10865.13 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1705.50 | 07-JAN-14:30 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.54 |
February | 4276.87 | 27-FEB-15:00 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 731.65 |
March | 4256.80 | 18-MAR-13:40 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.13 |
April | 9435.53 | 27-APR-16:10 | 401.76 | 400.23 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 3680.46 | 0.00 |
May | 7359.20 | 14-MAY-14:02 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.19 |
June | 7185.52 | 28-JUN-17:00 | 401.76 | 400.23 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 3311.61 | 0.00 |
July | 12681.67 | 31-JUL-16:10 | 401.76 | 400.23 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 5864.52 | 0.00 |
August | 16070.84 | 13-AUG-14:22 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 0.00 |
September | 16176.17 | 10-SEP-14:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.01 |
October | 13184.81 | 08-OCT-13:23 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.34 |
November | 5934.70 | 04-NOV-13:50 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3359.96 | 02-DEC-13:30 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1705.50 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16176.17 | 1306.65 | 720.41 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 5864.52 | 731.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1099.10 | 05-JAN-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.86 |
February | 1892.28 | 27-FEB-15:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.29 |
March | 2715.04 | 02-MAR-16:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.75 |
April | 5345.21 | 26-APR-17:30 | 84.78 | 152.01 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
May | 11990.26 | 07-MAY-17:42 | 0.00 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.88 |
June | 7266.34 | 25-JUN-16:42 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.42 |
July | 12284.10 | 30-JUL-17:41 | 0.00 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.90 |
August | 11778.87 | 13-AUG-17:02 | 0.00 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 | 0.00 |
September | 7781.71 | 10-SEP-16:33 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.83 |
October | 5545.63 | 04-OCT-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.10 |
November | 1786.40 | 04-NOV-15:40 | 84.78 | 76.01 | 370.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.06 |
December | 1239.93 | 05-DEC-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1099.10 | 0.00 | 76.01 | 370.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12284.10 | 805.38 | 456.05 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 | 77.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1214.73 | 11-JAN-16:20 | 1272.23 | 1108.06 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.57 |
February | 1477.10 | 28-FEB-15:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1537.90 | 10-MAR-14:50 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.38 |
April | 4120.87 | 27-APR-16:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 24.13 | 0.00 |
May | 4337.50 | 05-MAY-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 | 0.00 |
June | 4804.26 | 21-JUN-15:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 | 0.00 |
July | 5764.99 | 24-JUL-06:03 | 1071.35 | 960.53 | 2677.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 |
August | 5254.68 | 09-AUG-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 44.58 | 0.00 |
September | 4129.25 | 12-SEP-14:50 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 2.18 | 0.00 |
October | 2695.86 | 04-OCT-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.70 |
November | 1426.03 | 02-NOV-14:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.35 |
December | 1160.25 | 29-DEC-17:00 | 1272.23 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1160.25 | 1071.35 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5764.99 | 1306.65 | 1168.55 | 2677.14 | 0.00 | 0.00 | 0.00 | 0.00 | 44.58 | 94.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1072.18 | 05-JAN-09:50 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.78 |
February | 1343.73 | 08-FEB-10:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.80 |
March | 2799.53 | 14-MAR-10:10 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.78 |
April | 6540.51 | 27-APR-09:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.72 |
May | 6696.55 | 15-MAY-08:50 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.78 |
June | 12007.09 | 25-JUN-09:13 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.83 |
July | 13236.65 | 23-JUL-08:12 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.90 |
August | 13562.10 | 13-AUG-09:02 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.68 |
September | 12120.76 | 10-SEP-09:02 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.27 |
October | 4999.77 | 04-OCT-09:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.07 |
November | 1382.28 | 02-NOV-10:30 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.24 |
December | 1200.70 | 05-DEC-10:00 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1072.18 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.72 | |
Maximum of Months | 13562.10 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6632.30 | 20-JAN-13:30 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.20 |
February | 8156.14 | 27-FEB-14:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.22 |
March | 9428.43 | 01-MAR-13:35 | 2544.47 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.08 |
April | 11028.72 | 27-APR-13:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 13.26 | 0.00 |
May | 11512.04 | 14-MAY-13:03 | 200.88 | 120.08 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.48 |
June | 8595.79 | 28-JUN-13:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 | 0.00 |
July | 17977.45 | 30-JUL-12:13 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.70 |
August | 18617.40 | 13-AUG-12:22 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.42 |
September | 17893.57 | 10-SEP-13:42 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.64 |
October | 17791.65 | 08-OCT-13:23 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.63 |
November | 8315.44 | 04-NOV-13:30 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6886.01 | 05-DEC-12:30 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6632.30 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18617.40 | 2544.47 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 13.26 | 277.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1317.49 | 05-JAN-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.22 |
February | 3168.69 | 27-FEB-15:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 |
March | 4595.98 | 14-MAR-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.42 |
April | 7416.55 | 26-APR-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 | 0.00 |
May | 12469.14 | 07-MAY-16:32 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.17 |
June | 12047.12 | 25-JUN-16:42 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.46 |
July | 14562.50 | 23-JUL-18:11 | 0.00 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.50 |
August | 13259.21 | 13-AUG-17:02 | 0.00 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 2.31 | 0.00 |
September | 13533.45 | 10-SEP-17:02 | 0.00 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.31 |
October | 6234.47 | 04-OCT-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.10 |
November | 2315.76 | 04-NOV-15:30 | 84.78 | 76.01 | 370.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.63 |
December | 1427.83 | 05-DEC-15:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1317.49 | 0.00 | 76.01 | 370.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14562.50 | 805.38 | 456.05 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 2.31 | 105.46 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.141916E+12 | 227390.58 | 02-JAN-07:10 | 0.314136E+11 | 58733.11 | 07-JAN-07:00 |
February | 0.112239E+12 | 172776.15 | 21-FEB-07:10 | 0.222094E+11 | 51511.87 | 18-FEB-07:10 |
March | 0.113509E+12 | 118174.51 | 06-MAR-07:10 | 0.144148E+11 | 39871.64 | 01-MAR-07:30 |
April | 0.101702E+12 | 124058.18 | 27-APR-15:09 | 0.106383E+11 | 30781.99 | 19-APR-06:19 |
May | 0.108753E+12 | 115954.92 | 15-MAY-15:30 | 0.953496E+10 | 17208.01 | 18-MAY-06:19 |
June | 0.112387E+12 | 125802.09 | 28-JUN-15:30 | 0.896798E+10 | 9183.88 | 01-JUN-11:09 |
July | 0.120722E+12 | 146108.56 | 31-JUL-15:20 | 0.866184E+10 | 9121.34 | 03-JUL-11:09 |
August | 0.135869E+12 | 150866.62 | 10-AUG-15:20 | 0.911662E+10 | 9092.35 | 01-AUG-11:09 |
September | 0.109141E+12 | 125743.32 | 14-SEP-15:30 | 0.855651E+10 | 10281.97 | 27-SEP-06:10 |
October | 0.106081E+12 | 104535.78 | 04-OCT-15:09 | 0.960589E+10 | 20265.41 | 16-OCT-06:00 |
November | 0.115522E+12 | 131196.42 | 24-NOV-07:10 | 0.171175E+11 | 42830.88 | 13-NOV-08:09 |
December | 0.129932E+12 | 182276.39 | 26-DEC-07:10 | 0.261740E+11 | 54690.64 | 26-DEC-07:30 |
Annual Sum or Average | 0.140777E+13 | 0.176411E+12 | ||||
Minimum of Months | 0.101702E+12 | 104535.78 | 0.855651E+10 | 9092.35 | ||
Maximum of Months | 0.141916E+12 | 227390.58 | 0.314136E+11 | 58733.11 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.242371E+11 | 0.816103E+10 | 0.641572E+11 | 0.109171E+10 | 0.422615E+10 | 1312252.65 | 0.400413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.215562E+11 | 0.662444E+10 | 0.580684E+11 | 0.987489E+09 | 0.375828E+10 | 1186778.30 | 0.210779E+11 | 0.165265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252364E+11 | 0.631040E+10 | 0.666107E+11 | 0.114323E+10 | 0.464185E+10 | 1343621.24 | 0.930527E+10 | 0.259897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223576E+11 | 0.507908E+10 | 0.619407E+11 | 0.105056E+10 | 0.515897E+10 | 1267813.82 | 0.355123E+10 | 0.256254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.240094E+11 | 0.442306E+10 | 0.653840E+11 | 0.111685E+10 | 0.692175E+10 | 1327936.95 | 0.148509E+10 | 0.541179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.238093E+11 | 0.386050E+10 | 0.641577E+11 | 0.109954E+10 | 0.852895E+10 | 1296568.36 | 0.809769E+09 | 0.101196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.223278E+11 | 0.415495E+10 | 0.631525E+11 | 0.106757E+10 | 0.106401E+11 | 1299182.41 | 0.334060E+09 | 0.190437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.249207E+11 | 0.484482E+10 | 0.666107E+11 | 0.114304E+10 | 0.123350E+11 | 1343621.24 | 0.287925E+09 | 0.257258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.224753E+11 | 0.565927E+10 | 0.619118E+11 | 0.105023E+10 | 0.798754E+10 | 1267813.82 | 0.800658E+09 | 0.925526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.236373E+11 | 0.691061E+10 | 0.641717E+11 | 0.109124E+10 | 0.515196E+10 | 1312252.65 | 0.392728E+10 | 0.119004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.238463E+11 | 0.761993E+10 | 0.627379E+11 | 0.107161E+10 | 0.399156E+10 | 1278270.02 | 0.159760E+11 | 0.277849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.236171E+11 | 0.840444E+10 | 0.631380E+11 | 0.106860E+10 | 0.398474E+10 | 1299182.41 | 0.297176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.282030E+12 | 0.720525E+11 | 0.762041E+12 | 0.129817E+11 | 0.773269E+11 | 15535293.87 | 0.127314E+12 | 0.740118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.215562E+11 | 0.386050E+10 | 0.580684E+11 | 0.987489E+09 | 0.375828E+10 | 1186778.30 | 0.287925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.252364E+11 | 0.840444E+10 | 0.666107E+11 | 0.114323E+10 | 0.123350E+11 | 1343621.24 | 0.400413E+11 | 0.257258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.218524E+11 | 0.00 | 0.956128E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.135218E+11 | 0.00 | 0.868760E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.449211E+10 | 0.00 | 0.992264E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.159708E+10 | 0.00 | 0.904122E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.200270E+09 | 0.00 | 0.933469E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.896798E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.866184E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.911662E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 19209110.55 | 0.00 | 0.853730E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.627280E+09 | 0.00 | 0.897861E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.813208E+10 | 0.00 | 0.898538E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.169133E+11 | 0.00 | 0.926066E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.673555E+11 | 0.00 | 0.109056E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.853730E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.218524E+11 | 0.00 | 0.992264E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28079.40 | 02-JAN-16:30 | 5557.43 | 01-JAN-06:10 | 47562.27 | 02-JAN-08:09 | 927.39 | 04-JAN-08:20 | 6282.93 | 02-JAN-07:10 | 0.73 | 02-JAN-06:10 | 184080.49 | 02-JAN-07:10 |
February | 27200.62 | 02-FEB-16:00 | 5557.43 | 01-FEB-06:10 | 47562.27 | 01-FEB-08:09 | 926.61 | 02-FEB-08:20 | 4481.21 | 27-FEB-15:30 | 0.73 | 02-FEB-08:09 | 131491.50 | 21-FEB-07:10 |
March | 26300.97 | 22-MAR-07:10 | 5557.43 | 01-MAR-06:10 | 47562.27 | 01-MAR-08:09 | 925.65 | 22-MAR-07:19 | 5107.08 | 14-MAR-15:39 | 0.73 | 01-MAR-07:10 | 84366.44 | 06-MAR-07:10 |
April | 24810.50 | 03-APR-07:10 | 5557.43 | 01-APR-05:10 | 47562.27 | 03-APR-07:10 | 923.51 | 03-APR-07:19 | 17424.57 | 27-APR-14:30 | 0.73 | 11-APR-07:10 | 52795.75 | 18-APR-06:10 |
May | 23688.37 | 01-MAY-07:10 | 5557.43 | 01-MAY-19:19 | 47562.27 | 01-MAY-07:10 | 921.90 | 01-MAY-07:19 | 18172.69 | 15-MAY-15:09 | 0.73 | 18-MAY-07:10 | 25589.55 | 18-MAY-06:10 |
June | 23688.37 | 01-JUN-07:10 | 5557.43 | 01-JUN-19:00 | 47562.27 | 01-JUN-07:10 | 921.90 | 01-JUN-07:19 | 19183.65 | 28-JUN-15:30 | 0.73 | 01-JUN-05:10 | 14099.59 | 14-JUN-06:10 |
July | 24548.07 | 12-JUL-07:40 | 5557.43 | 01-JUL-20:10 | 47562.27 | 03-JUL-07:10 | 923.13 | 12-JUL-07:49 | 25634.17 | 31-JUL-15:09 | 0.73 | 01-JUL-05:10 | 9821.24 | 03-JUL-06:19 |
August | 24067.14 | 28-AUG-07:30 | 5557.43 | 01-AUG-19:40 | 47562.27 | 01-AUG-07:10 | 922.44 | 28-AUG-07:40 | 25983.35 | 10-AUG-15:09 | 0.73 | 01-AUG-05:10 | 10935.77 | 18-AUG-06:19 |
September | 26358.19 | 25-SEP-07:10 | 5557.43 | 01-SEP-05:10 | 47562.27 | 01-SEP-07:10 | 925.73 | 25-SEP-07:19 | 21555.51 | 11-SEP-15:30 | 0.73 | 01-SEP-05:30 | 20938.55 | 28-SEP-06:10 |
October | 27961.61 | 31-OCT-07:10 | 5557.43 | 01-OCT-05:10 | 47562.27 | 02-OCT-07:10 | 928.04 | 31-OCT-07:19 | 14988.43 | 04-OCT-15:09 | 0.73 | 01-OCT-05:10 | 53048.99 | 30-OCT-06:10 |
November | 28079.40 | 06-NOV-16:49 | 5557.43 | 01-NOV-05:10 | 47562.27 | 01-NOV-07:10 | 928.05 | 03-NOV-07:19 | 4165.63 | 04-NOV-13:30 | 0.73 | 10-NOV-08:09 | 90453.17 | 24-NOV-07:10 |
December | 28079.40 | 01-DEC-16:19 | 5557.43 | 01-DEC-06:10 | 47562.27 | 01-DEC-08:09 | 928.06 | 28-DEC-08:20 | 4624.07 | 26-DEC-07:10 | 0.73 | 01-DEC-08:09 | 140625.16 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 23688.37 | 5557.43 | 47562.27 | 921.90 | 4165.63 | 0.73 | 9821.24 | |||||||
Maximum of Months | 28079.40 | 5557.43 | 47562.27 | 928.06 | 25983.35 | 0.73 | 184080.49 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9741.28 | 27-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8681.58 | 18-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38320.21 | 27-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30815.09 | 04-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38238.93 | 28-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 53694.95 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 57126.35 | 29-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36919.88 | 14-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21279.09 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13953.80 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57126.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 227390.58 | 02-JAN-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 6282.93 | 0.73 | 184080.49 | 0.00 | 0.00 |
February | 172776.15 | 21-FEB-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 4257.49 | 0.73 | 131491.50 | 0.00 | 0.00 |
March | 118174.51 | 06-MAR-07:10 | 8153.76 | 21853.28 | 0.00 | 255.91 | 3544.39 | 0.73 | 84366.44 | 0.00 | 0.00 |
April | 124058.18 | 27-APR-15:09 | 23688.37 | 43769.98 | 0.00 | 920.43 | 17358.47 | 0.73 | 0.00 | 38320.21 | 0.00 |
May | 115954.92 | 15-MAY-15:30 | 23688.37 | 43769.98 | 0.00 | 920.43 | 17965.99 | 0.73 | 0.00 | 29609.42 | 0.00 |
June | 125802.09 | 28-JUN-15:30 | 23688.37 | 43769.98 | 0.00 | 920.43 | 19183.65 | 0.73 | 0.00 | 38238.93 | 0.00 |
July | 146108.56 | 31-JUL-15:20 | 23688.37 | 43769.98 | 0.00 | 920.43 | 25511.19 | 0.73 | 0.00 | 52217.86 | 0.00 |
August | 150866.62 | 10-AUG-15:20 | 23688.37 | 43769.98 | 0.00 | 920.43 | 25850.64 | 0.73 | 0.00 | 56636.47 | 0.00 |
September | 125743.32 | 14-SEP-15:30 | 23688.37 | 43769.98 | 0.00 | 920.43 | 21035.32 | 0.73 | 0.00 | 36328.49 | 0.00 |
October | 104535.78 | 04-OCT-15:09 | 23688.37 | 43769.98 | 0.00 | 920.43 | 14988.43 | 0.73 | 0.00 | 21167.84 | 0.00 |
November | 131196.42 | 24-NOV-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 3716.08 | 0.73 | 90453.17 | 0.00 | 0.00 |
December | 182276.39 | 26-DEC-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 4624.07 | 0.73 | 140625.16 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 104535.78 | 8153.76 | 21853.28 | 0.00 | 255.91 | 3544.39 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 227390.58 | 23688.37 | 43769.98 | 5557.43 | 920.43 | 25850.64 | 0.73 | 184080.49 | 56636.47 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 50787.73 | 07-JAN-07:00 | 0.00 | 9389.50 | 31-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 44245.30 | 18-FEB-07:19 | 0.00 | 9394.87 | 13-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 33995.91 | 01-MAR-07:10 | 0.00 | 9372.47 | 02-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 24679.34 | 19-APR-06:19 | 0.00 | 9330.02 | 05-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 9184.53 | 18-MAY-06:10 | 0.00 | 9263.62 | 02-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9183.88 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9121.34 | 03-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9092.35 | 01-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 2227.72 | 28-SEP-06:19 | 0.00 | 9132.93 | 28-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 12173.67 | 16-OCT-06:00 | 0.00 | 9192.15 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 0.00 | 34997.00 | 13-NOV-07:00 | 0.00 | 9279.02 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 46781.32 | 26-DEC-07:40 | 0.00 | 9347.74 | 26-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9092.35 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 50787.73 | 0.00 | 9394.87 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.28 | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.16 | 0.00 | 26.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.28 | 0.17 | 19.28 | 0.17 | 21.57 | 0.00 | 21.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.28 | 0.17 | 19.28 | 0.17 | 26.16 | 0.00 | 26.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 19.14 | 0.67 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 19.14 | 0.67 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 19.14 | 0.67 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 18.29 | 0.67 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 |
February | 0.33 | 18.13 | 0.17 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.23 | 0.17 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
Annual Sum or Average | 1.50 | 18.36 | 1.00 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.23 | 0.67 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.83 | 17.19 | 3.83 | 17.56 | 0.00 | 17.56 | 0.00 | 17.56 |
February | 2.00 | 16.78 | 1.33 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 18.68 | 0.33 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
December | 1.83 | 18.72 | 1.33 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
Annual Sum or Average | 11.17 | 17.44 | 6.83 | 17.78 | 0.00 | 17.78 | 0.00 | 17.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.83 | 18.72 | 3.83 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 15.33 | 1.00 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
February | 1.17 | 15.54 | 0.50 | 15.38 | 0.00 | 15.38 | 0.00 | 15.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.47 | 0.67 | 27.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.69 | 0.83 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.92 | 2.67 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.83 | 2.50 | 27.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.59 | 0.83 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
December | 1.67 | 16.59 | 0.33 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 |
Annual Sum or Average | 7.83 | 15.75 | 1.83 | 15.68 | 7.50 | 20.97 | 7.50 | 23.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.50 | 17.18 | 1.00 | 17.18 | 2.67 | 27.92 | 2.67 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 15.79 | 0.00 | 15.79 | 0.00 | 15.79 | 0.00 | 15.79 |
February | 0.50 | 16.44 | 0.00 | 16.44 | 0.00 | 16.44 | 0.00 | 16.44 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.60 | 1.00 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.39 | 0.83 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.81 | 2.67 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.93 | 2.50 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.06 | 1.67 | 28.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.50 | 0.33 | 27.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 17.35 | 0.17 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 |
Annual Sum or Average | 3.17 | 16.22 | 0.17 | 16.38 | 9.17 | 24.77 | 9.00 | 26.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 17.35 | 0.17 | 17.76 | 2.67 | 28.06 | 2.67 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 15.32 | 1.50 | 15.24 | 0.00 | 15.24 | 0.00 | 15.24 |
February | 1.33 | 15.49 | 0.83 | 15.30 | 0.00 | 15.30 | 0.00 | 15.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.06 | 1.83 | 28.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.87 | 0.83 | 27.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.30 | 2.17 | 28.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.11 | 1.83 | 28.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.08 | 0.67 | 28.11 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
December | 1.17 | 16.95 | 0.33 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
Annual Sum or Average | 7.67 | 15.72 | 2.67 | 15.61 | 14.00 | 22.81 | 7.33 | 24.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.67 | 17.21 | 1.50 | 17.21 | 4.67 | 28.30 | 2.17 | 28.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 19.02 | 2.67 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
February | 0.17 | 19.31 | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.31 | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Annual Sum or Average | 3.50 | 19.05 | 3.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.31 | 2.67 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 16.60 | 0.17 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.56 | 2.17 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.55 | 2.00 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.35 | 0.50 | 27.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 16.60 | 0.17 | 17.14 | 4.67 | 25.96 | 4.67 | 26.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 16.60 | 0.17 | 17.14 | 2.17 | 27.56 | 2.17 | 27.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 72.50 | 17.78 | 72.17 | 17.78 | 0.00 | 17.78 | 0.00 | 17.78 |
February | 52.50 | 18.18 | 52.50 | 18.18 | 0.00 | 18.18 | 0.00 | 18.18 |
March | 45.50 | 18.78 | 45.50 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
April | 26.67 | 18.97 | 26.67 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
May | 14.33 | 19.59 | 14.33 | 19.59 | 0.00 | 19.59 | 0.00 | 19.59 |
June | 3.17 | 20.12 | 3.17 | 20.12 | 0.00 | 20.12 | 0.00 | 20.12 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.50 | 1.00 | 27.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.54 | 2.83 | 26.54 |
September | 2.50 | 19.51 | 2.50 | 19.51 | 1.50 | 21.42 | 1.50 | 22.61 |
October | 19.33 | 19.45 | 19.33 | 19.45 | 0.33 | 19.52 | 0.33 | 19.58 |
November | 53.33 | 18.70 | 53.33 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
December | 64.00 | 17.93 | 64.00 | 17.93 | 0.00 | 17.93 | 0.00 | 17.93 |
Annual Sum or Average | 353.83 | 18.42 | 353.50 | 18.42 | 5.67 | 18.49 | 5.67 | 18.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.78 | 0.00 | 17.78 |
Maximum of Months | 72.50 | 20.12 | 72.17 | 20.12 | 2.83 | 27.50 | 2.83 | 27.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 17.35 | 0.33 | 18.06 | 0.00 | 18.06 | 0.00 | 18.06 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.75 | 0.67 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.40 | 0.33 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.01 | 1.50 | 27.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.75 | 1.33 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.84 | 0.33 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 17.35 | 0.33 | 18.06 | 8.83 | 26.69 | 4.17 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 17.35 | 0.33 | 18.06 | 3.33 | 28.01 | 1.50 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 18.78 | 1.33 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
February | 0.17 | 19.43 | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.33 | 0.17 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
Annual Sum or Average | 2.17 | 18.87 | 1.67 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.43 | 1.33 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 17.34 | 0.17 | 17.73 | 0.00 | 17.73 | 0.00 | 17.73 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.59 | 0.83 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.75 | 1.00 | 27.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.98 | 2.67 | 27.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.91 | 2.50 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.67 | 1.00 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 17.34 | 0.17 | 17.73 | 8.00 | 26.89 | 8.00 | 27.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 17.34 | 0.17 | 17.73 | 2.67 | 27.98 | 2.67 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 17.38 | 0.17 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.46 | 1.17 | 27.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.32 | 0.33 | 27.32 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.69 | 2.50 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.83 | 2.50 | 27.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.02 | 1.67 | 28.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.59 | 0.67 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 17.38 | 0.17 | 17.76 | 8.83 | 26.88 | 8.83 | 27.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 17.38 | 0.17 | 17.76 | 2.50 | 28.02 | 2.50 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 16.88 | 0.33 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.95 | 1.83 | 27.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.84 | 0.67 | 27.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.20 | 2.00 | 28.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.92 | 1.83 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.98 | 0.83 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 16.88 | 0.33 | 16.96 | 13.67 | 27.14 | 7.17 | 27.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 16.88 | 0.33 | 16.96 | 4.33 | 28.20 | 2.00 | 28.22 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.82 | 33.33 | 22.63 | 33.33 | 22.45 |
February | 436.17 | 23.44 | 0.00 | 23.44 | 0.00 | 23.44 |
March | 391.00 | 23.81 | 1.33 | 23.81 | 0.00 | 23.81 |
April | 163.67 | 23.82 | 57.50 | 24.13 | 0.00 | 24.13 |
May | 14.17 | 23.88 | 164.67 | 24.77 | 0.00 | 24.77 |
June | 0.00 | 0.00 | 231.83 | 24.74 | 0.00 | 24.74 |
July | 0.00 | 0.00 | 384.17 | 24.58 | 0.00 | 24.58 |
August | 0.00 | 0.00 | 454.33 | 24.41 | 0.00 | 24.41 |
September | 0.00 | 0.00 | 324.17 | 24.60 | 0.00 | 24.60 |
October | 95.17 | 23.74 | 70.50 | 24.46 | 0.00 | 24.46 |
November | 338.33 | 23.65 | 21.33 | 23.73 | 0.00 | 23.73 |
December | 497.00 | 23.38 | 0.00 | 23.38 | 0.00 | 23.38 |
Annual Sum or Average | 2437.50 | 23.43 | 1743.17 | 23.89 | 33.33 | 23.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.63 | 0.00 | 22.45 |
Maximum of Months | 502.00 | 23.88 | 454.33 | 24.77 | 33.33 | 24.77 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.30 | 120.17 | 21.07 | 120.17 | 20.92 |
February | 454.00 | 21.91 | 43.00 | 21.78 | 43.00 | 21.67 |
March | 513.83 | 22.82 | 0.67 | 22.82 | 0.67 | 22.82 |
April | 385.00 | 23.27 | 26.17 | 23.36 | 0.00 | 23.36 |
May | 202.33 | 23.55 | 53.50 | 23.74 | 0.00 | 23.74 |
June | 80.00 | 23.59 | 117.67 | 24.16 | 0.00 | 24.16 |
July | 7.33 | 23.50 | 271.50 | 24.42 | 0.00 | 24.42 |
August | 23.83 | 23.50 | 351.50 | 24.26 | 0.00 | 24.26 |
September | 76.17 | 23.36 | 167.17 | 24.12 | 0.00 | 24.12 |
October | 361.33 | 23.05 | 9.83 | 23.10 | 0.00 | 23.10 |
November | 482.00 | 22.33 | 1.50 | 22.33 | 1.50 | 22.32 |
December | 497.00 | 21.69 | 30.17 | 21.61 | 30.17 | 21.55 |
Annual Sum or Average | 3584.83 | 22.42 | 1192.83 | 22.75 | 195.50 | 22.65 |
Minimum of Months | 7.33 | 21.30 | 0.67 | 21.07 | 0.00 | 20.92 |
Maximum of Months | 513.83 | 23.59 | 351.50 | 24.42 | 120.17 | 24.42 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.68 | 241.17 | 20.43 | 241.17 | 20.30 |
February | 454.00 | 21.17 | 148.50 | 20.92 | 148.50 | 20.77 |
March | 514.00 | 22.03 | 37.50 | 21.92 | 37.50 | 21.83 |
April | 417.17 | 22.70 | 16.33 | 22.75 | 1.33 | 22.74 |
May | 287.00 | 23.18 | 39.17 | 23.31 | 0.00 | 23.31 |
June | 157.17 | 23.42 | 85.67 | 23.74 | 0.00 | 23.74 |
July | 75.50 | 23.48 | 238.33 | 24.11 | 0.00 | 24.11 |
August | 74.00 | 23.37 | 283.33 | 24.06 | 0.00 | 24.06 |
September | 216.50 | 23.17 | 103.33 | 23.51 | 0.00 | 23.51 |
October | 461.83 | 22.47 | 7.17 | 22.44 | 7.17 | 22.41 |
November | 489.00 | 21.49 | 85.17 | 21.30 | 85.17 | 21.16 |
December | 497.00 | 20.93 | 195.17 | 20.72 | 195.17 | 20.60 |
Annual Sum or Average | 4145.17 | 21.93 | 1480.83 | 22.02 | 716.00 | 21.80 |
Minimum of Months | 74.00 | 20.68 | 7.17 | 20.43 | 0.00 | 20.30 |
Maximum of Months | 514.00 | 23.48 | 283.33 | 24.11 | 241.17 | 24.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.04 | 403.83 | 19.93 | 403.83 | 19.89 |
February | 454.00 | 20.38 | 281.50 | 20.19 | 281.50 | 20.10 |
March | 514.00 | 21.09 | 167.67 | 20.87 | 167.67 | 20.73 |
April | 440.50 | 21.93 | 67.33 | 21.79 | 57.17 | 21.63 |
May | 333.00 | 22.55 | 50.67 | 22.71 | 4.00 | 22.69 |
June | 201.17 | 23.01 | 86.17 | 23.38 | 0.00 | 23.38 |
July | 128.83 | 23.18 | 231.33 | 23.84 | 0.00 | 23.84 |
August | 146.83 | 23.07 | 265.00 | 23.78 | 0.00 | 23.78 |
September | 301.67 | 22.59 | 72.33 | 22.88 | 0.83 | 22.87 |
October | 491.17 | 21.58 | 69.17 | 21.39 | 69.17 | 21.24 |
November | 489.00 | 20.61 | 238.50 | 20.39 | 238.50 | 20.28 |
December | 497.00 | 20.20 | 382.83 | 20.09 | 382.83 | 20.05 |
Annual Sum or Average | 4499.17 | 21.31 | 2316.33 | 21.28 | 1605.50 | 21.03 |
Minimum of Months | 128.83 | 20.04 | 50.67 | 19.93 | 0.00 | 19.89 |
Maximum of Months | 514.00 | 23.18 | 403.83 | 23.84 | 403.83 | 23.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.06 | 396.50 | 19.95 | 396.50 | 19.91 |
February | 454.00 | 20.51 | 259.67 | 20.31 | 259.67 | 20.21 |
March | 510.50 | 21.28 | 131.00 | 21.02 | 131.00 | 20.85 |
April | 353.67 | 21.91 | 79.67 | 21.92 | 42.67 | 21.76 |
May | 272.33 | 22.36 | 120.83 | 22.93 | 5.17 | 22.91 |
June | 159.83 | 22.90 | 202.50 | 23.72 | 3.00 | 23.75 |
July | 124.67 | 23.36 | 305.67 | 24.06 | 10.00 | 24.13 |
August | 123.00 | 23.31 | 328.50 | 24.01 | 11.83 | 24.09 |
September | 261.00 | 22.41 | 150.50 | 23.09 | 4.67 | 23.10 |
October | 451.33 | 21.58 | 64.50 | 21.43 | 59.50 | 21.28 |
November | 489.00 | 20.64 | 224.00 | 20.42 | 224.00 | 20.31 |
December | 497.00 | 20.22 | 363.17 | 20.10 | 363.17 | 20.05 |
Annual Sum or Average | 4198.33 | 21.26 | 2626.50 | 21.48 | 1511.17 | 21.22 |
Minimum of Months | 123.00 | 20.06 | 64.50 | 19.95 | 3.00 | 19.91 |
Maximum of Months | 510.50 | 23.36 | 396.50 | 24.06 | 396.50 | 24.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.83 | 20.35 | 333.83 | 20.13 | 333.83 | 20.04 |
February | 415.67 | 20.83 | 208.00 | 20.61 | 201.33 | 20.47 |
March | 435.00 | 21.28 | 145.83 | 21.13 | 124.00 | 20.95 |
April | 334.83 | 21.79 | 112.67 | 22.00 | 48.83 | 21.82 |
May | 289.17 | 22.32 | 125.67 | 22.90 | 9.67 | 22.90 |
June | 211.00 | 22.74 | 156.67 | 23.45 | 2.50 | 23.47 |
July | 157.33 | 23.16 | 274.00 | 23.93 | 9.50 | 23.99 |
August | 159.33 | 23.14 | 303.83 | 23.90 | 11.33 | 23.98 |
September | 249.67 | 22.54 | 190.33 | 23.31 | 7.67 | 23.35 |
October | 378.67 | 21.60 | 127.00 | 21.92 | 46.17 | 21.78 |
November | 459.00 | 20.83 | 203.83 | 20.70 | 186.00 | 20.54 |
December | 477.00 | 20.51 | 308.00 | 20.29 | 307.83 | 20.19 |
Annual Sum or Average | 4064.50 | 21.42 | 2489.67 | 21.70 | 1288.67 | 21.44 |
Minimum of Months | 157.33 | 20.35 | 112.67 | 20.13 | 2.50 | 20.04 |
Maximum of Months | 497.83 | 23.16 | 333.83 | 23.93 | 333.83 | 23.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.08 | 397.00 | 19.97 | 397.00 | 19.92 |
February | 451.33 | 20.53 | 265.83 | 20.32 | 265.83 | 20.22 |
March | 493.33 | 21.08 | 163.33 | 20.89 | 157.33 | 20.75 |
April | 388.17 | 21.64 | 97.17 | 21.72 | 56.33 | 21.56 |
May | 320.00 | 22.33 | 114.00 | 22.82 | 14.50 | 22.86 |
June | 229.50 | 22.71 | 160.17 | 23.37 | 3.00 | 23.40 |
July | 161.33 | 23.13 | 278.17 | 23.92 | 11.83 | 24.00 |
August | 176.83 | 22.98 | 277.00 | 23.79 | 9.33 | 23.85 |
September | 295.00 | 22.40 | 141.67 | 23.03 | 5.33 | 23.05 |
October | 457.00 | 21.41 | 78.67 | 21.36 | 59.50 | 21.22 |
November | 486.50 | 20.63 | 233.67 | 20.44 | 231.83 | 20.33 |
December | 497.00 | 20.26 | 373.33 | 20.13 | 373.33 | 20.09 |
Annual Sum or Average | 4458.00 | 21.26 | 2580.00 | 21.43 | 1585.17 | 21.19 |
Minimum of Months | 161.33 | 20.08 | 78.67 | 19.97 | 3.00 | 19.92 |
Maximum of Months | 502.00 | 23.13 | 397.00 | 23.92 | 397.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.37 | 367.83 | 20.26 | 367.83 | 20.22 |
February | 454.00 | 20.67 | 238.83 | 20.52 | 238.83 | 20.45 |
March | 514.00 | 21.24 | 102.33 | 21.11 | 102.33 | 21.02 |
April | 473.33 | 22.06 | 14.33 | 22.02 | 13.50 | 21.98 |
May | 406.50 | 22.93 | 14.33 | 22.97 | 0.00 | 22.97 |
June | 239.33 | 23.33 | 41.83 | 23.47 | 0.00 | 23.47 |
July | 111.33 | 23.46 | 174.33 | 23.91 | 0.00 | 23.91 |
August | 129.67 | 23.37 | 240.83 | 23.88 | 0.00 | 23.88 |
September | 301.33 | 23.10 | 61.50 | 23.28 | 0.00 | 23.28 |
October | 490.17 | 22.25 | 1.83 | 22.24 | 1.83 | 22.24 |
November | 489.00 | 21.23 | 109.17 | 21.08 | 109.17 | 20.97 |
December | 497.00 | 20.62 | 295.00 | 20.52 | 295.00 | 20.47 |
Annual Sum or Average | 4607.67 | 21.71 | 1662.17 | 21.66 | 1128.50 | 21.44 |
Minimum of Months | 111.33 | 20.37 | 1.83 | 20.26 | 0.00 | 20.22 |
Maximum of Months | 514.00 | 23.46 | 367.83 | 23.91 | 367.83 | 23.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.39 | 351.33 | 20.28 | 351.33 | 20.23 |
February | 454.00 | 20.87 | 210.50 | 20.70 | 210.50 | 20.61 |
March | 514.00 | 21.61 | 58.50 | 21.47 | 58.50 | 21.36 |
April | 382.33 | 22.45 | 29.67 | 22.50 | 6.83 | 22.46 |
May | 272.67 | 22.86 | 90.83 | 23.27 | 0.00 | 23.27 |
June | 114.50 | 23.20 | 194.33 | 24.02 | 0.00 | 24.02 |
July | 79.50 | 23.71 | 313.17 | 24.27 | 6.83 | 24.31 |
August | 67.00 | 23.67 | 357.83 | 24.21 | 6.50 | 24.26 |
September | 208.67 | 23.06 | 175.67 | 23.66 | 1.33 | 23.68 |
October | 416.50 | 22.31 | 16.67 | 22.39 | 1.17 | 22.39 |
November | 489.00 | 21.29 | 96.00 | 21.13 | 96.00 | 21.02 |
December | 497.00 | 20.67 | 261.17 | 20.54 | 261.17 | 20.47 |
Annual Sum or Average | 3997.17 | 21.65 | 2155.67 | 21.95 | 1000.17 | 21.72 |
Minimum of Months | 67.00 | 20.39 | 16.67 | 20.28 | 0.00 | 20.23 |
Maximum of Months | 514.00 | 23.71 | 357.83 | 24.27 | 351.33 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.14 | 355.00 | 19.95 | 355.00 | 19.87 |
February | 447.17 | 20.74 | 172.50 | 20.46 | 172.50 | 20.30 |
March | 489.50 | 21.19 | 83.83 | 20.96 | 82.17 | 20.77 |
April | 401.83 | 21.66 | 71.67 | 21.75 | 30.67 | 21.60 |
May | 377.33 | 22.15 | 69.33 | 22.47 | 6.00 | 22.43 |
June | 284.83 | 22.49 | 94.67 | 23.04 | 0.00 | 23.04 |
July | 144.17 | 22.77 | 247.00 | 23.83 | 2.50 | 23.85 |
August | 142.83 | 22.79 | 297.50 | 23.85 | 6.17 | 23.89 |
September | 232.33 | 22.52 | 205.67 | 23.43 | 7.33 | 23.45 |
October | 381.67 | 21.82 | 82.67 | 22.23 | 11.67 | 22.16 |
November | 467.17 | 20.88 | 134.50 | 20.76 | 117.17 | 20.58 |
December | 489.67 | 20.46 | 283.83 | 20.24 | 281.83 | 20.13 |
Annual Sum or Average | 4360.50 | 21.35 | 2098.17 | 21.59 | 1073.00 | 21.33 |
Minimum of Months | 142.83 | 20.14 | 69.33 | 19.95 | 0.00 | 19.87 |
Maximum of Months | 502.00 | 22.79 | 355.00 | 23.85 | 355.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.40 | 356.33 | 20.29 | 356.33 | 20.24 |
February | 453.00 | 20.84 | 211.83 | 20.66 | 211.83 | 20.57 |
March | 504.17 | 21.40 | 77.50 | 21.27 | 77.50 | 21.17 |
April | 407.17 | 22.10 | 38.67 | 22.20 | 11.17 | 22.16 |
May | 303.00 | 22.86 | 90.50 | 23.25 | 1.67 | 23.27 |
June | 192.83 | 23.17 | 141.33 | 23.71 | 0.33 | 23.71 |
July | 70.50 | 23.68 | 324.00 | 24.32 | 6.67 | 24.36 |
August | 81.00 | 23.41 | 332.00 | 24.13 | 5.17 | 24.17 |
September | 201.00 | 23.02 | 181.50 | 23.69 | 1.67 | 23.70 |
October | 438.17 | 22.18 | 17.50 | 22.28 | 0.33 | 22.28 |
November | 485.00 | 21.20 | 104.67 | 21.06 | 104.00 | 20.96 |
December | 497.00 | 20.68 | 275.83 | 20.55 | 275.83 | 20.49 |
Annual Sum or Average | 4134.83 | 21.61 | 2151.67 | 21.88 | 1052.50 | 21.66 |
Minimum of Months | 70.50 | 20.40 | 17.50 | 20.29 | 0.33 | 20.24 |
Maximum of Months | 504.17 | 23.68 | 356.33 | 24.32 | 356.33 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.32 | 330.50 | 20.17 | 330.50 | 20.10 |
February | 454.00 | 20.74 | 208.33 | 20.52 | 208.33 | 20.41 |
March | 514.00 | 21.60 | 69.00 | 21.44 | 69.00 | 21.32 |
April | 426.50 | 22.42 | 27.00 | 22.44 | 10.33 | 22.40 |
May | 291.00 | 23.03 | 51.50 | 23.19 | 0.00 | 23.19 |
June | 139.00 | 23.36 | 94.33 | 23.72 | 0.00 | 23.72 |
July | 63.17 | 23.49 | 255.33 | 24.08 | 0.00 | 24.08 |
August | 80.50 | 23.38 | 300.67 | 24.02 | 0.00 | 24.02 |
September | 238.50 | 23.08 | 97.50 | 23.41 | 0.00 | 23.41 |
October | 472.50 | 22.19 | 12.33 | 22.14 | 12.33 | 22.09 |
November | 489.00 | 21.12 | 133.33 | 20.91 | 133.33 | 20.78 |
December | 497.00 | 20.55 | 285.17 | 20.41 | 285.17 | 20.34 |
Annual Sum or Average | 4167.17 | 21.63 | 1865.00 | 21.71 | 1049.00 | 21.47 |
Minimum of Months | 63.17 | 20.32 | 12.33 | 20.17 | 0.00 | 20.10 |
Maximum of Months | 514.00 | 23.49 | 330.50 | 24.08 | 330.50 | 24.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.21 | 293.00 | 20.06 | 293.00 | 19.99 |
February | 385.00 | 20.77 | 178.17 | 20.57 | 178.17 | 20.46 |
March | 427.83 | 21.55 | 52.67 | 21.39 | 52.67 | 21.26 |
April | 298.83 | 22.23 | 44.50 | 22.41 | 8.33 | 22.36 |
May | 237.33 | 22.78 | 88.50 | 23.26 | 2.00 | 23.28 |
June | 123.67 | 23.20 | 158.83 | 23.93 | 3.67 | 23.97 |
July | 84.83 | 23.72 | 252.33 | 24.29 | 9.67 | 24.37 |
August | 84.67 | 23.62 | 283.33 | 24.20 | 9.50 | 24.27 |
September | 205.33 | 22.87 | 128.67 | 23.48 | 3.50 | 23.51 |
October | 369.00 | 21.94 | 29.67 | 21.99 | 13.17 | 21.93 |
November | 417.00 | 21.00 | 122.50 | 20.80 | 122.50 | 20.67 |
December | 422.00 | 20.47 | 254.50 | 20.33 | 254.50 | 20.26 |
Annual Sum or Average | 3482.50 | 21.52 | 1886.67 | 21.79 | 950.67 | 21.56 |
Minimum of Months | 84.67 | 20.21 | 29.67 | 20.06 | 2.00 | 19.99 |
Maximum of Months | 427.83 | 23.72 | 293.00 | 24.29 | 293.00 | 24.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.83 | 20.68 | 257.33 | 20.43 | 257.17 | 20.31 |
February | 404.00 | 21.18 | 148.83 | 21.04 | 134.83 | 20.88 |
March | 417.50 | 21.74 | 76.50 | 21.71 | 50.00 | 21.58 |
April | 310.50 | 22.28 | 85.50 | 22.67 | 8.00 | 22.63 |
May | 254.00 | 22.83 | 129.33 | 23.37 | 2.50 | 23.39 |
June | 162.83 | 23.13 | 173.83 | 23.78 | 1.67 | 23.80 |
July | 101.00 | 23.57 | 298.50 | 24.19 | 8.67 | 24.25 |
August | 100.50 | 23.56 | 339.00 | 24.14 | 10.00 | 24.21 |
September | 188.67 | 23.06 | 221.17 | 23.77 | 6.17 | 23.82 |
October | 351.17 | 22.18 | 100.67 | 22.65 | 9.33 | 22.63 |
November | 449.50 | 21.32 | 121.50 | 21.28 | 98.00 | 21.12 |
December | 465.67 | 20.87 | 217.17 | 20.67 | 213.33 | 20.55 |
Annual Sum or Average | 3699.17 | 21.77 | 2169.33 | 22.18 | 799.67 | 21.96 |
Minimum of Months | 100.50 | 20.68 | 76.50 | 20.43 | 1.67 | 20.31 |
Maximum of Months | 493.83 | 23.57 | 339.00 | 24.19 | 257.17 | 24.25 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.35 | 323.83 | 20.19 | 323.83 | 20.12 |
February | 449.33 | 20.86 | 191.50 | 20.64 | 191.50 | 20.52 |
March | 487.67 | 21.50 | 74.00 | 21.38 | 68.17 | 21.26 |
April | 373.83 | 22.13 | 63.00 | 22.37 | 11.33 | 22.31 |
May | 282.83 | 22.83 | 121.17 | 23.32 | 6.33 | 23.38 |
June | 177.17 | 23.09 | 177.33 | 23.72 | 2.50 | 23.74 |
July | 103.33 | 23.57 | 309.00 | 24.20 | 10.67 | 24.27 |
August | 115.50 | 23.37 | 322.50 | 24.06 | 8.83 | 24.12 |
September | 235.83 | 22.92 | 170.67 | 23.55 | 4.67 | 23.58 |
October | 438.83 | 21.95 | 37.33 | 22.06 | 11.00 | 22.01 |
November | 484.17 | 21.05 | 132.00 | 20.88 | 129.83 | 20.76 |
December | 497.00 | 20.60 | 272.00 | 20.44 | 272.00 | 20.36 |
Annual Sum or Average | 4147.50 | 21.58 | 2194.33 | 21.87 | 1040.67 | 21.65 |
Minimum of Months | 103.33 | 20.35 | 37.33 | 20.19 | 2.50 | 20.12 |
Maximum of Months | 502.00 | 23.57 | 323.83 | 24.20 | 323.83 | 24.27 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.81912 | 31.38685 | -0.0885 | 6.86680 |
February | 454.00000 | 23.46532 | 31.42972 | 0.09252 | 5.71231 |
March | 514.00000 | 23.92033 | 30.10560 | 0.22417 | 6.22614 |
April | 485.00000 | 24.20113 | 32.82853 | 0.33125 | 7.55139 |
May | 508.00000 | 24.32018 | 36.37798 | -0.4591 | 9.76063 |
June | 496.00000 | 24.36006 | 38.24920 | -0.4083 | 8.90934 |
July | 497.00000 | 24.44879 | 42.46290 | -0.3414 | 7.96858 |
August | 514.00000 | 24.36023 | 45.56313 | -0.3378 | 7.81389 |
September | 485.00000 | 24.40631 | 43.24987 | -0.3667 | 8.35157 |
October | 502.00000 | 24.23219 | 36.18107 | 0.36481 | 8.04911 |
November | 489.00000 | 23.83015 | 36.15342 | 0.22845 | 6.49334 |
December | 497.00000 | 23.37966 | 31.60559 | 0.06831 | 5.49163 |
Annual Sum or Average | 5943.00000 | 23.98195 | 36.33226 | -0.0597 | 7.44625 |
Minimum of Months | 454.00000 | 22.81912 | 30.10560 | -0.4591 | 5.49163 |
Maximum of Months | 514.00000 | 24.44879 | 45.56313 | 0.36481 | 9.76063 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.29581 | 34.10513 | -0.4275 | 10.28384 |
February | 454.00000 | 21.91468 | 34.64784 | -0.2561 | 7.46652 |
March | 514.00000 | 22.82370 | 33.30242 | -0.0290 | 5.59803 |
April | 485.00000 | 23.46780 | 35.41110 | 0.15757 | 6.13794 |
May | 508.00000 | 23.89629 | 38.19224 | -0.6180 | 13.52133 |
June | 496.00000 | 24.08416 | 39.65004 | -0.5199 | 10.95778 |
July | 497.00000 | 24.22960 | 43.71039 | -0.4339 | 9.25742 |
August | 514.00000 | 24.17422 | 46.89939 | -0.4225 | 9.06394 |
September | 485.00000 | 24.05365 | 45.01101 | -0.5085 | 10.87506 |
October | 502.00000 | 23.37806 | 39.30963 | 0.15719 | 6.16240 |
November | 489.00000 | 22.35650 | 40.12186 | -0.1100 | 6.21515 |
December | 497.00000 | 21.68775 | 35.04137 | -0.3147 | 7.70159 |
Annual Sum or Average | 5943.00000 | 23.12278 | 38.80869 | -0.2780 | 8.61604 |
Minimum of Months | 454.00000 | 21.29581 | 33.30242 | -0.6180 | 5.59803 |
Maximum of Months | 514.00000 | 24.22960 | 46.89939 | 0.15757 | 13.52133 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.67529 | 34.82678 | -0.5985 | 14.59432 |
February | 454.00000 | 21.17013 | 35.47897 | -0.4511 | 11.13122 |
March | 514.00000 | 22.02925 | 34.55849 | -0.2226 | 7.06001 |
April | 485.00000 | 22.89805 | 36.41856 | 0.02113 | 6.19138 |
May | 508.00000 | 23.56185 | 38.93244 | -0.7332 | 17.48738 |
June | 496.00000 | 23.90483 | 39.95552 | -0.5821 | 12.64125 |
July | 497.00000 | 24.07939 | 43.81846 | -0.4827 | 10.31154 |
August | 514.00000 | 24.02853 | 47.01676 | -0.4742 | 10.21171 |
September | 485.00000 | 23.68580 | 46.00589 | -0.6403 | 14.55753 |
October | 502.00000 | 22.59313 | 41.12259 | -0.0341 | 6.17513 |
November | 489.00000 | 21.48675 | 42.00897 | -0.3307 | 8.54454 |
December | 497.00000 | 20.93002 | 36.19068 | -0.5200 | 11.75012 |
Annual Sum or Average | 5943.00000 | 22.59831 | 39.71767 | -0.4210 | 10.88967 |
Minimum of Months | 454.00000 | 20.67529 | 34.55849 | -0.7332 | 6.17513 |
Maximum of Months | 514.00000 | 24.07939 | 47.01676 | 0.02113 | 17.48738 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.04062 | 36.25943 | -0.7968 | 20.99424 |
February | 454.00000 | 20.38176 | 36.88868 | -0.6723 | 17.10718 |
March | 514.00000 | 21.09156 | 36.97273 | -0.4541 | 10.78579 |
April | 485.00000 | 22.12209 | 38.33452 | -0.1601 | 7.69477 |
May | 508.00000 | 23.06010 | 40.63131 | -0.8890 | 24.34087 |
June | 496.00000 | 23.64732 | 41.20105 | -0.6563 | 15.47278 |
July | 497.00000 | 23.89197 | 44.47491 | -0.5290 | 11.94832 |
August | 514.00000 | 23.81665 | 48.26849 | -0.5338 | 12.20600 |
September | 485.00000 | 23.13429 | 48.35832 | -0.8254 | 21.56439 |
October | 502.00000 | 21.63419 | 44.08951 | -0.2628 | 8.05813 |
November | 489.00000 | 20.60956 | 43.80454 | -0.5658 | 13.55838 |
December | 497.00000 | 20.19540 | 37.98949 | -0.7399 | 18.30494 |
Annual Sum or Average | 5943.00000 | 21.98205 | 41.46463 | -0.5901 | 15.15480 |
Minimum of Months | 454.00000 | 20.04062 | 36.25943 | -0.8890 | 7.69477 |
Maximum of Months | 514.00000 | 23.89197 | 48.35832 | -0.1601 | 24.34087 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.06270 | 35.89565 | -0.7868 | 20.56911 |
February | 454.00000 | 20.51035 | 36.36628 | -0.6284 | 15.57295 |
March | 514.00000 | 21.30214 | 36.26332 | -0.3837 | 10.01998 |
April | 485.00000 | 22.48688 | 37.04678 | -0.0397 | 7.73262 |
May | 508.00000 | 23.19038 | 39.88767 | -0.7908 | 22.01912 |
June | 496.00000 | 23.77250 | 40.35429 | -0.5387 | 13.64204 |
July | 497.00000 | 23.99172 | 43.91938 | -0.4227 | 10.99892 |
August | 514.00000 | 23.93194 | 47.55808 | -0.4138 | 10.78187 |
September | 485.00000 | 23.21624 | 47.57693 | -0.7357 | 20.15608 |
October | 502.00000 | 21.82940 | 43.16376 | -0.1963 | 8.00618 |
November | 489.00000 | 20.64096 | 43.40839 | -0.5511 | 13.18904 |
December | 497.00000 | 20.22176 | 37.62926 | -0.7268 | 17.88545 |
Annual Sum or Average | 5943.00000 | 22.10958 | 40.78073 | -0.5173 | 14.19994 |
Minimum of Months | 454.00000 | 20.06270 | 35.89565 | -0.7908 | 7.73262 |
Maximum of Months | 514.00000 | 23.99172 | 47.57693 | -0.0397 | 22.01912 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.37796 | 34.82907 | -0.6907 | 18.19523 |
February | 454.00000 | 21.10802 | 34.69471 | -0.4687 | 13.43030 |
March | 514.00000 | 21.70027 | 34.73345 | -0.2745 | 9.94845 |
April | 485.00000 | 22.53998 | 36.30655 | -0.0214 | 8.36378 |
May | 508.00000 | 23.11698 | 39.61108 | -0.8141 | 23.48044 |
June | 496.00000 | 23.57123 | 40.72464 | -0.6307 | 16.33657 |
July | 497.00000 | 23.87786 | 43.99626 | -0.4688 | 12.36050 |
August | 514.00000 | 23.83516 | 47.55623 | -0.4448 | 11.98465 |
September | 485.00000 | 23.33808 | 46.59695 | -0.6583 | 18.81691 |
October | 502.00000 | 22.26557 | 41.35667 | -0.0718 | 8.58274 |
November | 489.00000 | 21.05243 | 41.89311 | -0.4413 | 12.06795 |
December | 497.00000 | 20.65435 | 36.23022 | -0.6042 | 15.88926 |
Annual Sum or Average | 5943.00000 | 22.29649 | 39.90945 | -0.4662 | 14.12898 |
Minimum of Months | 454.00000 | 20.37796 | 34.69471 | -0.8141 | 8.36378 |
Maximum of Months | 514.00000 | 23.87786 | 47.55623 | -0.0214 | 23.48044 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.07991 | 35.58886 | -0.7845 | 20.55712 |
February | 454.00000 | 20.54926 | 36.00132 | -0.6242 | 15.96082 |
March | 514.00000 | 21.20577 | 36.06626 | -0.4101 | 10.70155 |
April | 485.00000 | 22.15492 | 37.58219 | -0.1183 | 8.35182 |
May | 508.00000 | 22.98914 | 40.31256 | -0.8463 | 25.00948 |
June | 496.00000 | 23.47378 | 41.30776 | -0.6454 | 16.89147 |
July | 497.00000 | 23.85586 | 44.29111 | -0.4489 | 12.44365 |
August | 514.00000 | 23.73128 | 48.25294 | -0.4798 | 12.87928 |
September | 485.00000 | 23.09930 | 47.79264 | -0.7635 | 21.60739 |
October | 502.00000 | 21.66259 | 43.29628 | -0.2344 | 8.32917 |
November | 489.00000 | 20.65162 | 43.12524 | -0.5523 | 13.29184 |
December | 497.00000 | 20.25672 | 37.28173 | -0.7217 | 17.88264 |
Annual Sum or Average | 5943.00000 | 21.98790 | 40.93710 | -0.5522 | 15.32101 |
Minimum of Months | 454.00000 | 20.07991 | 35.58886 | -0.8463 | 8.32917 |
Maximum of Months | 514.00000 | 23.85586 | 48.25294 | -0.1183 | 25.00948 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.36668 | 35.99911 | -0.6975 | 16.72056 |
February | 454.00000 | 20.67279 | 36.65388 | -0.5854 | 13.47159 |
March | 514.00000 | 21.24114 | 36.59151 | -0.4110 | 9.13137 |
April | 485.00000 | 22.10832 | 38.45692 | -0.1691 | 6.70021 |
May | 508.00000 | 23.14236 | 40.91955 | -0.8858 | 22.90114 |
June | 496.00000 | 23.71498 | 41.57367 | -0.6619 | 14.87748 |
July | 497.00000 | 23.96451 | 44.70880 | -0.5337 | 11.40532 |
August | 514.00000 | 23.90533 | 48.29558 | -0.5264 | 11.34105 |
September | 485.00000 | 23.45967 | 47.66028 | -0.7238 | 17.00788 |
October | 502.00000 | 22.29384 | 42.41583 | -0.0968 | 6.05763 |
November | 489.00000 | 21.23226 | 42.46852 | -0.3818 | 9.03667 |
December | 497.00000 | 20.62489 | 37.22272 | -0.5993 | 13.06918 |
Annual Sum or Average | 5943.00000 | 22.23948 | 41.10697 | -0.5229 | 12.64812 |
Minimum of Months | 454.00000 | 20.36668 | 35.99911 | -0.8858 | 6.05763 |
Maximum of Months | 514.00000 | 23.96451 | 48.29558 | -0.0968 | 22.90114 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.38777 | 36.19356 | -0.6868 | 16.34167 |
February | 454.00000 | 20.86702 | 36.54991 | -0.5271 | 11.96240 |
March | 514.00000 | 21.61115 | 36.17074 | -0.3069 | 7.96126 |
April | 485.00000 | 22.79643 | 36.90632 | 0.01826 | 6.64299 |
May | 508.00000 | 23.47834 | 39.78782 | -0.7291 | 18.40003 |
June | 496.00000 | 24.02074 | 40.18437 | -0.4911 | 11.48112 |
July | 497.00000 | 24.17517 | 43.80906 | -0.3954 | 9.47284 |
August | 514.00000 | 24.12908 | 47.16569 | -0.3707 | 9.05116 |
September | 485.00000 | 23.71362 | 46.54931 | -0.5850 | 14.10029 |
October | 502.00000 | 22.62435 | 41.56938 | -0.0015 | 6.35533 |
November | 489.00000 | 21.29015 | 42.55043 | -0.3605 | 8.78871 |
December | 497.00000 | 20.67196 | 37.36646 | -0.5814 | 12.68558 |
Annual Sum or Average | 5943.00000 | 22.49281 | 40.42346 | -0.4179 | 11.10247 |
Minimum of Months | 454.00000 | 20.38777 | 36.17074 | -0.7291 | 6.35533 |
Maximum of Months | 514.00000 | 24.17517 | 47.16569 | 0.01826 | 18.40003 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.13614 | 33.88145 | -0.7027 | 17.41420 |
February | 454.00000 | 20.79829 | 34.02706 | -0.4905 | 12.25672 |
March | 514.00000 | 21.33312 | 34.03133 | -0.3220 | 9.01662 |
April | 485.00000 | 22.12916 | 36.32568 | -0.0995 | 7.67035 |
May | 508.00000 | 22.71113 | 40.20211 | -0.9368 | 26.73162 |
June | 496.00000 | 23.26049 | 41.32537 | -0.7373 | 19.08663 |
July | 497.00000 | 23.83737 | 44.28750 | -0.5013 | 12.38934 |
August | 514.00000 | 23.80933 | 47.75726 | -0.4580 | 11.63211 |
September | 485.00000 | 23.45582 | 46.06833 | -0.6025 | 16.33368 |
October | 502.00000 | 22.46867 | 39.90745 | 0.01558 | 7.59851 |
November | 489.00000 | 21.05725 | 40.29016 | -0.3767 | 10.10769 |
December | 497.00000 | 20.52797 | 34.87275 | -0.5733 | 13.87025 |
Annual Sum or Average | 5943.00000 | 22.13747 | 39.45067 | -0.4827 | 13.69959 |
Minimum of Months | 454.00000 | 20.13614 | 33.88145 | -0.9368 | 7.59851 |
Maximum of Months | 514.00000 | 23.83737 | 47.75726 | 0.01558 | 26.73162 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.40018 | 35.79989 | -0.6858 | 16.34670 |
February | 454.00000 | 20.84391 | 36.18872 | -0.5338 | 12.41354 |
March | 514.00000 | 21.45632 | 35.96283 | -0.3434 | 8.54415 |
April | 485.00000 | 22.44581 | 37.38750 | -0.0636 | 6.96040 |
May | 508.00000 | 23.41182 | 39.79455 | -0.7428 | 19.10555 |
June | 496.00000 | 23.80352 | 40.96725 | -0.5737 | 13.38238 |
July | 497.00000 | 24.20681 | 43.64662 | -0.3690 | 9.19640 |
August | 514.00000 | 24.06011 | 47.48234 | -0.3981 | 9.61224 |
September | 485.00000 | 23.73600 | 46.34590 | -0.5715 | 13.85844 |
October | 502.00000 | 22.44546 | 41.69880 | -0.0399 | 6.43844 |
November | 489.00000 | 21.22475 | 42.34105 | -0.3759 | 9.01421 |
December | 497.00000 | 20.68021 | 36.97491 | -0.5814 | 12.77558 |
Annual Sum or Average | 5943.00000 | 22.40498 | 40.40798 | -0.4398 | 11.47143 |
Minimum of Months | 454.00000 | 20.40018 | 35.79989 | -0.7428 | 6.43844 |
Maximum of Months | 514.00000 | 24.20681 | 47.48234 | -0.0399 | 19.10555 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.31977 | 35.85727 | -0.6921 | 16.97631 |
February | 454.00000 | 20.74215 | 36.34998 | -0.5501 | 13.25316 |
March | 514.00000 | 21.59530 | 36.18426 | -0.3111 | 8.05631 |
April | 485.00000 | 22.62042 | 37.44470 | -0.0342 | 6.49648 |
May | 508.00000 | 23.46088 | 39.74246 | -0.7541 | 18.43237 |
June | 496.00000 | 23.88344 | 40.66624 | -0.5773 | 12.59294 |
July | 497.00000 | 24.07589 | 44.17130 | -0.4697 | 10.04945 |
August | 514.00000 | 24.00457 | 47.90440 | -0.4706 | 10.19640 |
September | 485.00000 | 23.58156 | 47.15168 | -0.6717 | 15.61807 |
October | 502.00000 | 22.30106 | 42.57288 | -0.0915 | 6.40350 |
November | 489.00000 | 21.11710 | 42.75758 | -0.4113 | 9.84872 |
December | 497.00000 | 20.55014 | 37.25115 | -0.6126 | 13.77248 |
Annual Sum or Average | 5943.00000 | 22.36726 | 40.69673 | -0.4704 | 11.79982 |
Minimum of Months | 454.00000 | 20.31977 | 35.85727 | -0.7541 | 6.40350 |
Maximum of Months | 514.00000 | 24.07589 | 47.90440 | -0.0342 | 18.43237 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.20723 | 34.82948 | -0.7191 | 17.78656 |
February | 385.00000 | 20.77231 | 35.03438 | -0.5395 | 12.70716 |
March | 433.00000 | 21.57532 | 35.06563 | -0.3007 | 8.17361 |
April | 410.00000 | 22.75320 | 35.88752 | 0.02388 | 6.95942 |
May | 430.00000 | 23.42333 | 38.85173 | -0.7228 | 18.74985 |
June | 418.00000 | 23.92689 | 39.85895 | -0.5031 | 12.23122 |
July | 422.00000 | 24.16271 | 43.37092 | -0.3891 | 9.91086 |
August | 433.00000 | 24.07803 | 47.01130 | -0.3854 | 9.82155 |
September | 410.00000 | 23.52763 | 46.32554 | -0.6395 | 16.19641 |
October | 427.00000 | 22.24346 | 41.60277 | -0.0871 | 6.84662 |
November | 417.00000 | 20.99515 | 41.84968 | -0.4372 | 10.23079 |
December | 422.00000 | 20.47271 | 36.27728 | -0.6304 | 14.26713 |
Annual Sum or Average | 5034.00000 | 22.35428 | 39.69043 | -0.4440 | 11.98666 |
Minimum of Months | 385.00000 | 20.20723 | 34.82948 | -0.7228 | 6.84662 |
Maximum of Months | 433.00000 | 24.16271 | 47.01130 | 0.02388 | 18.74985 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.74098 | 34.37330 | -0.5709 | 14.48515 |
February | 454.00000 | 21.52222 | 34.10793 | -0.3388 | 10.61508 |
March | 514.00000 | 22.17568 | 33.94880 | -0.1405 | 7.86193 |
April | 485.00000 | 22.98706 | 35.47376 | 0.09197 | 7.50748 |
May | 508.00000 | 23.51284 | 38.76074 | -0.6828 | 17.66165 |
June | 496.00000 | 23.84585 | 40.17447 | -0.5433 | 12.89339 |
July | 497.00000 | 24.10683 | 43.63140 | -0.4002 | 9.96424 |
August | 514.00000 | 24.04789 | 47.16063 | -0.3783 | 9.71140 |
September | 485.00000 | 23.75452 | 45.55259 | -0.5177 | 13.45892 |
October | 502.00000 | 22.83528 | 40.03582 | 0.07763 | 7.72085 |
November | 489.00000 | 21.57968 | 40.90143 | -0.2846 | 9.19890 |
December | 497.00000 | 21.08482 | 35.39848 | -0.4645 | 11.96710 |
Annual Sum or Average | 5943.00000 | 22.69220 | 39.15902 | -0.3466 | 11.09430 |
Minimum of Months | 454.00000 | 20.74098 | 33.94880 | -0.6828 | 7.50748 |
Maximum of Months | 514.00000 | 24.10683 | 47.16063 | 0.09197 | 17.66165 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.35057 | 35.28496 | -0.6813 | 16.66106 |
February | 454.00000 | 20.88748 | 35.58911 | -0.5066 | 12.48581 |
March | 514.00000 | 21.63129 | 35.46762 | -0.2825 | 8.26989 |
April | 485.00000 | 22.61416 | 36.78164 | -0.0008 | 7.22126 |
May | 508.00000 | 23.41585 | 39.45096 | -0.7057 | 18.74224 |
June | 496.00000 | 23.77497 | 40.74339 | -0.5501 | 13.17674 |
July | 497.00000 | 24.09835 | 43.89583 | -0.3763 | 9.92760 |
August | 514.00000 | 23.97611 | 47.80595 | -0.4033 | 10.26896 |
September | 485.00000 | 23.56782 | 46.64255 | -0.6066 | 15.45923 |
October | 502.00000 | 22.24326 | 42.02788 | -0.0799 | 6.86042 |
November | 489.00000 | 21.07883 | 42.33672 | -0.4126 | 9.90023 |
December | 497.00000 | 20.60199 | 36.62989 | -0.5965 | 13.54654 |
Annual Sum or Average | 5943.00000 | 22.36526 | 40.24997 | -0.4334 | 11.87446 |
Minimum of Months | 454.00000 | 20.35057 | 35.28496 | -0.7057 | 6.86042 |
Maximum of Months | 514.00000 | 24.09835 | 47.80595 | -0.0008 | 18.74224 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.201651E+09 | 55096982.69 | 8.00 | 0.182249E+09 | 19401704.74 | 0.00 | 0.45 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 11646.73 | 27-FEB-15:00 | 11646.73 | 27-FEB-15:00 | 1261.39 | 27-FEB-17:25 | 3090.96 | 27-FEB-15:00 | 0.00 |
March | 0.311199E+09 | 87202370.25 | 22.33 | 0.272749E+09 | 38449817.87 | 0.00 | 0.39 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 9832.44 | 18-MAR-16:00 | 9832.44 | 18-MAR-16:00 | 1452.03 | 09-MAR-12:00 | 2652.43 | 18-MAR-16:00 | 0.00 |
April | 0.333517E+10 | 0.840029E+09 | 65.92 | 0.319529E+10 | 0.139888E+09 | 0.00 | 1.00 | 26-APR-13:30 | 0.00 | 01-APR-00:10 | 50335.34 | 27-APR-15:10 | 50335.34 | 27-APR-15:10 | 4148.46 | 28-APR-13:00 | 12486.83 | 27-APR-15:10 | 0.00 |
May | 0.730036E+10 | 0.182383E+10 | 155.24 | 0.650393E+10 | 0.796431E+09 | 0.00 | 1.00 | 04-MAY-12:50 | 0.00 | 01-MAY-00:10 | 44387.10 | 15-MAY-16:00 | 44387.10 | 15-MAY-16:00 | 6734.40 | 07-MAY-17:42 | 10156.83 | 15-MAY-16:00 | 0.00 |
June | 0.139945E+11 | 0.348510E+10 | 259.46 | 0.130278E+11 | 0.966680E+09 | 0.00 | 1.00 | 09-JUN-14:00 | 0.00 | 01-JUN-00:10 | 52369.05 | 28-JUN-15:50 | 52369.05 | 28-JUN-15:50 | 9596.53 | 12-JUN-06:02 | 12627.85 | 28-JUN-15:50 | 0.00 |
July | 0.270174E+11 | 0.661870E+10 | 345.89 | 0.239311E+11 | 0.308627E+10 | 0.00 | 1.00 | 06-JUL-14:50 | 0.00 | 01-JUL-00:10 | 72225.52 | 31-JUL-16:10 | 64511.00 | 24-JUL-15:10 | 15243.10 | 31-JUL-16:10 | 18548.10 | 31-JUL-16:10 | 0.00 |
August | 0.372085E+11 | 0.916459E+10 | 378.57 | 0.325869E+11 | 0.462156E+10 | 0.00 | 1.00 | 07-AUG-09:10 | 0.00 | 01-AUG-00:10 | 71583.48 | 09-AUG-16:10 | 67807.15 | 10-AUG-15:50 | 18834.08 | 30-AUG-06:02 | 19503.20 | 10-AUG-16:10 | 0.00 |
September | 0.134804E+11 | 0.329994E+10 | 227.64 | 0.112668E+11 | 0.221356E+10 | 0.00 | 1.00 | 08-SEP-14:00 | 0.00 | 01-SEP-00:10 | 56779.66 | 14-SEP-13:00 | 53443.48 | 12-SEP-15:30 | 14848.52 | 14-SEP-13:00 | 13037.19 | 14-SEP-13:00 | 0.00 |
October | 0.168767E+10 | 0.437858E+09 | 58.08 | 0.159307E+10 | 94604108.94 | 0.00 | 1.00 | 04-OCT-14:00 | 0.00 | 01-OCT-00:10 | 33461.57 | 04-OCT-15:10 | 33461.57 | 04-OCT-15:10 | 2926.77 | 08-OCT-13:23 | 7640.01 | 04-OCT-15:10 | 0.00 |
November | 0.344745E+09 | 89265019.40 | 7.67 | 0.232484E+09 | 0.112261E+09 | 0.00 | 0.66 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 17827.45 | 04-NOV-14:00 | 13087.48 | 04-NOV-14:00 | 5332.08 | 04-NOV-13:00 | 4483.83 | 04-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.104882E+12 | 0.259016E+11 | 1528.79 | 0.927925E+11 | 0.120891E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.372085E+11 | 0.916459E+10 | 378.57 | 0.325869E+11 | 0.462156E+10 | 0.00 | 1.00 | 0.00 | 72225.52 | 67807.15 | 18834.08 | 19503.20 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.198752E+09 | 53858176.77 | 8.00 | 0.185797E+09 | 12955300.36 | 0.00 | 0.54 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 12702.10 | 27-FEB-15:00 | 12702.10 | 27-FEB-15:00 | 1104.10 | 27-FEB-17:25 | 3296.58 | 27-FEB-15:00 | 0.00 |
March | 0.305941E+09 | 84697032.66 | 22.17 | 0.275679E+09 | 30262376.65 | 0.00 | 0.49 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 11317.92 | 18-MAR-14:00 | 11317.92 | 18-MAR-14:00 | 1274.78 | 09-MAR-12:00 | 2977.51 | 18-MAR-14:00 | 0.00 |
April | 0.328947E+10 | 0.825792E+09 | 69.51 | 0.317970E+10 | 0.109774E+09 | 0.00 | 1.00 | 26-APR-13:20 | 0.00 | 01-APR-00:10 | 48273.52 | 27-APR-14:50 | 48273.52 | 27-APR-14:50 | 4009.67 | 28-APR-13:00 | 11961.13 | 27-APR-15:00 | 0.00 |
May | 0.700990E+10 | 0.174390E+10 | 161.04 | 0.633137E+10 | 0.678532E+09 | 0.00 | 1.00 | 04-MAY-12:30 | 0.00 | 01-MAY-00:10 | 42967.54 | 04-MAY-15:00 | 42967.54 | 04-MAY-15:00 | 5059.00 | 05-MAY-18:00 | 9944.23 | 04-MAY-15:00 | 0.00 |
June | 0.129538E+11 | 0.322007E+10 | 266.56 | 0.121452E+11 | 0.808591E+09 | 0.00 | 1.00 | 09-JUN-13:20 | 0.00 | 01-JUN-00:10 | 48869.15 | 28-JUN-15:30 | 48869.15 | 28-JUN-15:30 | 5349.85 | 12-JUN-12:50 | 11782.54 | 28-JUN-15:30 | 0.00 |
July | 0.244580E+11 | 0.598187E+10 | 350.22 | 0.219495E+11 | 0.250847E+10 | 0.00 | 1.00 | 06-JUL-14:30 | 0.00 | 01-JUL-00:10 | 64160.18 | 31-JUL-14:40 | 58385.59 | 31-JUL-15:20 | 11278.29 | 31-JUL-10:30 | 16541.61 | 24-JUL-15:00 | 0.00 |
August | 0.324888E+11 | 0.801120E+10 | 376.44 | 0.287766E+11 | 0.371225E+10 | 0.00 | 1.00 | 06-AUG-15:23 | 0.00 | 01-AUG-00:10 | 65951.98 | 29-AUG-14:30 | 61067.60 | 10-AUG-15:10 | 15328.81 | 30-AUG-13:00 | 17916.37 | 29-AUG-15:30 | 0.00 |
September | 0.120481E+11 | 0.294746E+10 | 228.91 | 0.101593E+11 | 0.188883E+10 | 0.00 | 1.00 | 08-SEP-13:50 | 0.00 | 01-SEP-00:10 | 51595.08 | 14-SEP-13:00 | 48343.10 | 12-SEP-15:20 | 14136.73 | 14-SEP-13:00 | 11846.26 | 14-SEP-13:00 | 0.00 |
October | 0.148815E+10 | 0.385284E+09 | 56.42 | 0.140808E+10 | 80062042.37 | 0.00 | 1.00 | 04-OCT-13:50 | 0.00 | 01-OCT-00:10 | 30331.35 | 04-OCT-15:00 | 30331.35 | 04-OCT-15:00 | 3418.88 | 08-OCT-13:23 | 6925.17 | 04-OCT-15:00 | 0.00 |
November | 0.362264E+09 | 91857287.83 | 7.67 | 0.260450E+09 | 0.101814E+09 | 0.00 | 0.75 | 04-NOV-13:40 | 0.00 | 01-NOV-00:10 | 18722.56 | 04-NOV-13:40 | 14810.53 | 04-NOV-14:00 | 4860.80 | 04-NOV-16:00 | 4589.78 | 04-NOV-13:40 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.946032E+11 | 0.233460E+11 | 1546.93 | 0.846716E+11 | 0.993154E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.324888E+11 | 0.801120E+10 | 376.44 | 0.287766E+11 | 0.371225E+10 | 0.00 | 1.00 | 0.00 | 65951.98 | 61067.60 | 15328.81 | 17916.37 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.206430E+09 | 56310041.75 | 8.00 | 0.187835E+09 | 18595351.27 | 0.00 | 0.49 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 12756.02 | 27-FEB-15:00 | 12756.02 | 27-FEB-15:00 | 1317.17 | 27-FEB-17:13 | 3353.74 | 27-FEB-15:00 | 0.00 |
March | 0.316106E+09 | 87997391.86 | 22.17 | 0.280389E+09 | 35717136.80 | 0.00 | 0.45 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 11510.42 | 18-MAR-16:00 | 11510.42 | 18-MAR-16:00 | 1437.56 | 09-MAR-12:00 | 3059.83 | 18-MAR-16:00 | 0.00 |
April | 0.356310E+10 | 0.896723E+09 | 69.17 | 0.341502E+10 | 0.148078E+09 | 0.00 | 1.00 | 26-APR-13:30 | 0.00 | 01-APR-00:10 | 56619.78 | 27-APR-14:50 | 56619.78 | 27-APR-14:50 | 3822.33 | 28-APR-13:00 | 14012.58 | 27-APR-15:00 | 0.00 |
May | 0.739158E+10 | 0.184406E+10 | 158.56 | 0.658684E+10 | 0.804737E+09 | 0.00 | 1.00 | 04-MAY-12:50 | 0.00 | 01-MAY-00:10 | 47193.63 | 04-MAY-15:00 | 47193.63 | 04-MAY-15:00 | 5961.07 | 05-MAY-18:00 | 10922.86 | 04-MAY-15:00 | 0.00 |
June | 0.136761E+11 | 0.341446E+10 | 264.64 | 0.126876E+11 | 0.988518E+09 | 0.00 | 1.00 | 09-JUN-13:30 | 0.00 | 01-JUN-00:10 | 57425.35 | 28-JUN-15:20 | 57425.35 | 28-JUN-15:20 | 5249.74 | 12-JUN-12:40 | 13843.51 | 28-JUN-15:20 | 0.00 |
July | 0.262365E+11 | 0.644312E+10 | 348.08 | 0.232642E+11 | 0.297222E+10 | 0.00 | 1.00 | 06-JUL-14:50 | 0.00 | 01-JUL-00:10 | 73669.71 | 31-JUL-14:40 | 68017.06 | 24-JUL-15:00 | 11656.11 | 31-JUL-10:30 | 19208.99 | 24-JUL-15:00 | 0.00 |
August | 0.344681E+11 | 0.855006E+10 | 372.86 | 0.303208E+11 | 0.414734E+10 | 0.00 | 1.00 | 06-AUG-13:43 | 0.00 | 01-AUG-00:10 | 75395.18 | 10-AUG-15:20 | 71227.15 | 10-AUG-15:20 | 15633.85 | 30-AUG-13:00 | 20232.70 | 10-AUG-15:20 | 0.00 |
September | 0.122194E+11 | 0.300787E+10 | 225.31 | 0.101260E+11 | 0.209340E+10 | 0.00 | 1.00 | 08-SEP-14:10 | 0.00 | 01-SEP-00:10 | 52972.02 | 14-SEP-13:30 | 49935.86 | 12-SEP-15:20 | 13828.20 | 14-SEP-13:00 | 12152.32 | 14-SEP-13:30 | 0.00 |
October | 0.139509E+10 | 0.366901E+09 | 54.17 | 0.129592E+10 | 99170548.48 | 0.00 | 1.00 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 29815.61 | 04-OCT-15:00 | 29815.61 | 04-OCT-15:00 | 2809.90 | 08-OCT-13:50 | 6814.89 | 04-OCT-15:00 | 0.00 |
November | 0.378068E+09 | 96726631.30 | 7.67 | 0.263191E+09 | 0.114876E+09 | 0.00 | 0.72 | 04-NOV-13:50 | 0.00 | 01-NOV-00:10 | 19777.98 | 04-NOV-13:50 | 15129.09 | 04-NOV-14:00 | 5422.00 | 04-NOV-13:00 | 4897.02 | 04-NOV-13:50 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.998505E+11 | 0.247642E+11 | 1530.61 | 0.884278E+11 | 0.114226E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.344681E+11 | 0.855006E+10 | 372.86 | 0.303208E+11 | 0.414734E+10 | 0.00 | 1.00 | 0.00 | 75395.18 | 71227.15 | 15633.85 | 20232.70 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 219.21 | 0.00 | 219.21 | 9.56 | 1312.45 | 0.00 | 0.00 | 0.00 |
February | 341.09 | 0.00 | 341.09 | 74.54 | 1158.20 | 0.00 | 0.00 | 0.00 |
March | 502.54 | 0.00 | 502.54 | 224.04 | 952.06 | 0.00 | 0.00 | 0.00 |
April | 711.15 | 2.52 | 708.63 | 474.29 | 773.02 | 0.00 | 0.00 | 0.00 |
May | 915.07 | 27.19 | 887.89 | 748.39 | 639.30 | 0.00 | 0.00 | 0.00 |
June | 962.18 | 63.54 | 898.64 | 861.37 | 500.99 | 0.00 | 0.00 | 0.00 |
July | 914.49 | 71.70 | 842.79 | 927.88 | 454.33 | 0.00 | 0.00 | 0.00 |
August | 740.29 | 20.01 | 720.28 | 767.41 | 444.11 | 0.00 | 0.00 | 0.00 |
September | 575.03 | 0.17 | 574.86 | 444.71 | 650.12 | 0.00 | 0.00 | 0.00 |
October | 393.99 | 0.00 | 393.99 | 189.80 | 840.98 | 0.00 | 0.00 | 0.00 |
November | 248.18 | 0.00 | 248.18 | 40.71 | 1045.07 | 0.00 | 0.00 | 0.00 |
December | 186.27 | 0.00 | 186.27 | 5.41 | 1314.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 560.20 | 15.54 | 544.66 | 399.36 | 838.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.27 | 0.00 | 186.27 | 5.41 | 444.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 962.18 | 71.70 | 898.64 | 927.88 | 1314.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 234.82 | 59.53 | 175.29 | 85.90 | 829.53 | 0.00 | 0.00 | 0.00 |
February | 430.87 | 152.93 | 277.95 | 288.58 | 727.33 | 0.00 | 0.00 | 0.00 |
March | 643.33 | 232.89 | 410.44 | 544.74 | 606.01 | 0.00 | 0.00 | 0.00 |
April | 997.26 | 414.38 | 582.89 | 1016.56 | 496.32 | 0.00 | 0.00 | 0.00 |
May | 1061.18 | 368.95 | 692.23 | 1130.44 | 427.84 | 0.00 | 0.00 | 0.00 |
June | 1270.88 | 552.97 | 717.91 | 1450.63 | 340.56 | 0.00 | 0.00 | 0.00 |
July | 1183.49 | 531.22 | 652.27 | 1413.27 | 303.24 | 0.00 | 0.00 | 0.00 |
August | 1163.20 | 581.90 | 581.30 | 1438.41 | 295.40 | 0.00 | 0.00 | 0.00 |
September | 860.02 | 396.65 | 463.37 | 948.06 | 416.33 | 0.00 | 0.00 | 0.00 |
October | 560.56 | 238.18 | 322.37 | 518.27 | 539.65 | 0.00 | 0.00 | 0.00 |
November | 274.75 | 77.57 | 197.19 | 151.92 | 670.26 | 0.00 | 0.00 | 0.00 |
December | 225.36 | 72.55 | 152.81 | 108.63 | 839.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 743.51 | 307.32 | 436.20 | 760.34 | 540.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 225.36 | 59.53 | 152.81 | 85.90 | 295.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1270.88 | 581.90 | 717.91 | 1450.63 | 839.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 968.51 | 575.10 | 393.40 | 867.01 | 1185.50 | 0.00 | 0.00 | 0.00 |
February | 1489.41 | 921.97 | 567.45 | 1523.55 | 1074.54 | 0.00 | 0.00 | 0.00 |
March | 1602.18 | 854.42 | 747.76 | 1710.72 | 941.87 | 0.00 | 0.00 | 0.00 |
April | 1691.60 | 734.48 | 957.12 | 1909.58 | 811.34 | 0.00 | 0.00 | 0.00 |
May | 1546.75 | 460.79 | 1085.96 | 1757.39 | 688.94 | 0.00 | 0.00 | 0.00 |
June | 1415.13 | 379.94 | 1035.19 | 1637.57 | 552.34 | 0.00 | 0.00 | 0.00 |
July | 1543.26 | 565.22 | 978.04 | 1975.78 | 504.34 | 0.00 | 0.00 | 0.00 |
August | 1658.04 | 773.17 | 884.87 | 2198.35 | 486.16 | 0.00 | 0.00 | 0.00 |
September | 1837.03 | 1014.47 | 822.56 | 2287.80 | 663.76 | 0.00 | 0.00 | 0.00 |
October | 1664.04 | 1027.42 | 636.62 | 1899.38 | 835.02 | 0.00 | 0.00 | 0.00 |
November | 983.84 | 563.82 | 420.02 | 949.80 | 989.37 | 0.00 | 0.00 | 0.00 |
December | 1029.37 | 666.15 | 363.23 | 1015.57 | 1221.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1451.80 | 710.10 | 741.70 | 1644.80 | 828.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 968.51 | 379.94 | 363.23 | 867.01 | 486.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1837.03 | 1027.42 | 1085.96 | 2287.80 | 1221.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 247.68 | 73.04 | 174.64 | 108.07 | 836.04 | 0.00 | 0.00 | 0.00 |
February | 444.07 | 166.89 | 277.18 | 319.68 | 739.20 | 0.00 | 0.00 | 0.00 |
March | 622.26 | 210.03 | 412.23 | 531.99 | 621.02 | 0.00 | 0.00 | 0.00 |
April | 946.70 | 361.96 | 584.74 | 965.23 | 522.56 | 0.00 | 0.00 | 0.00 |
May | 1218.18 | 494.88 | 723.30 | 1349.39 | 449.47 | 0.00 | 0.00 | 0.00 |
June | 1171.55 | 454.87 | 716.68 | 1323.63 | 358.88 | 0.00 | 0.00 | 0.00 |
July | 1447.29 | 760.77 | 686.52 | 1793.61 | 332.94 | 0.00 | 0.00 | 0.00 |
August | 1197.26 | 611.35 | 585.91 | 1508.35 | 322.62 | 0.00 | 0.00 | 0.00 |
September | 974.98 | 467.82 | 507.17 | 1132.52 | 440.58 | 0.00 | 0.00 | 0.00 |
October | 555.06 | 226.16 | 328.90 | 523.56 | 555.49 | 0.00 | 0.00 | 0.00 |
November | 276.42 | 77.96 | 198.46 | 159.60 | 674.17 | 0.00 | 0.00 | 0.00 |
December | 232.38 | 79.63 | 152.75 | 129.00 | 848.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 779.85 | 333.38 | 446.48 | 823.68 | 557.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 232.38 | 73.04 | 152.75 | 108.07 | 322.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1447.29 | 760.77 | 723.30 | 1793.61 | 848.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.07 | 0.00 | 73.07 | 2.70 | 459.99 | 0.00 | 0.00 | 0.00 |
February | 113.69 | 0.00 | 113.69 | 24.11 | 406.09 | 0.00 | 0.00 | 0.00 |
March | 167.51 | 0.00 | 167.51 | 75.94 | 329.40 | 0.00 | 0.00 | 0.00 |
April | 237.04 | 0.84 | 236.20 | 163.40 | 262.03 | 0.00 | 0.00 | 0.00 |
May | 305.01 | 9.06 | 295.95 | 255.50 | 216.78 | 0.00 | 0.00 | 0.00 |
June | 320.71 | 21.18 | 299.53 | 293.27 | 168.98 | 0.00 | 0.00 | 0.00 |
July | 304.82 | 23.90 | 280.92 | 314.65 | 153.10 | 0.00 | 0.00 | 0.00 |
August | 246.75 | 6.67 | 240.08 | 259.27 | 150.73 | 0.00 | 0.00 | 0.00 |
September | 191.67 | 0.06 | 191.61 | 148.06 | 227.83 | 0.00 | 0.00 | 0.00 |
October | 131.32 | 0.00 | 131.32 | 58.75 | 306.86 | 0.00 | 0.00 | 0.00 |
November | 82.72 | 0.00 | 82.72 | 11.06 | 384.29 | 0.00 | 0.00 | 0.00 |
December | 62.09 | 0.00 | 62.09 | 1.10 | 471.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 186.73 | 5.18 | 181.55 | 134.67 | 294.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.09 | 0.00 | 62.09 | 1.10 | 150.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 320.71 | 23.90 | 299.53 | 314.65 | 471.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.07 | 0.00 | 73.07 | 2.70 | 460.02 | 0.00 | 0.00 | 0.00 |
February | 113.70 | 0.00 | 113.70 | 24.11 | 406.11 | 0.00 | 0.00 | 0.00 |
March | 167.52 | 0.00 | 167.52 | 75.95 | 329.42 | 0.00 | 0.00 | 0.00 |
April | 237.05 | 0.84 | 236.21 | 163.41 | 262.04 | 0.00 | 0.00 | 0.00 |
May | 305.03 | 9.06 | 295.97 | 255.52 | 216.79 | 0.00 | 0.00 | 0.00 |
June | 320.73 | 21.18 | 299.55 | 293.29 | 168.99 | 0.00 | 0.00 | 0.00 |
July | 304.84 | 23.90 | 280.94 | 314.67 | 153.11 | 0.00 | 0.00 | 0.00 |
August | 246.77 | 6.67 | 240.10 | 259.29 | 150.73 | 0.00 | 0.00 | 0.00 |
September | 191.68 | 0.06 | 191.62 | 148.07 | 227.84 | 0.00 | 0.00 | 0.00 |
October | 131.33 | 0.00 | 131.33 | 58.75 | 306.88 | 0.00 | 0.00 | 0.00 |
November | 82.73 | 0.00 | 82.73 | 11.06 | 384.31 | 0.00 | 0.00 | 0.00 |
December | 62.09 | 0.00 | 62.09 | 1.10 | 471.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 186.74 | 5.18 | 181.56 | 134.68 | 294.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.09 | 0.00 | 62.09 | 1.10 | 150.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 320.73 | 23.90 | 299.55 | 314.67 | 471.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.07 | 0.00 | 73.07 | 2.70 | 460.02 | 0.00 | 0.00 | 0.00 |
February | 113.70 | 0.00 | 113.70 | 24.11 | 406.11 | 0.00 | 0.00 | 0.00 |
March | 167.52 | 0.00 | 167.52 | 75.95 | 329.42 | 0.00 | 0.00 | 0.00 |
April | 237.05 | 0.84 | 236.21 | 163.41 | 262.04 | 0.00 | 0.00 | 0.00 |
May | 305.03 | 9.06 | 295.97 | 255.52 | 216.79 | 0.00 | 0.00 | 0.00 |
June | 320.73 | 21.18 | 299.55 | 293.29 | 168.99 | 0.00 | 0.00 | 0.00 |
July | 304.84 | 23.90 | 280.94 | 314.67 | 153.11 | 0.00 | 0.00 | 0.00 |
August | 246.77 | 6.67 | 240.10 | 259.29 | 150.73 | 0.00 | 0.00 | 0.00 |
September | 191.68 | 0.06 | 191.62 | 148.07 | 227.84 | 0.00 | 0.00 | 0.00 |
October | 131.33 | 0.00 | 131.33 | 58.75 | 306.88 | 0.00 | 0.00 | 0.00 |
November | 82.73 | 0.00 | 82.73 | 11.06 | 384.31 | 0.00 | 0.00 | 0.00 |
December | 62.09 | 0.00 | 62.09 | 1.10 | 471.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 186.74 | 5.18 | 181.56 | 134.68 | 294.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.09 | 0.00 | 62.09 | 1.10 | 150.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 320.73 | 23.90 | 299.55 | 314.67 | 471.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 225.89 | 57.27 | 168.62 | 80.26 | 838.68 | 0.00 | 0.00 | 0.00 |
February | 414.48 | 147.11 | 267.37 | 274.22 | 739.27 | 0.00 | 0.00 | 0.00 |
March | 618.85 | 224.03 | 394.82 | 525.41 | 613.60 | 0.00 | 0.00 | 0.00 |
April | 959.33 | 398.61 | 560.71 | 983.31 | 500.21 | 0.00 | 0.00 | 0.00 |
May | 1020.81 | 354.91 | 665.90 | 1095.07 | 428.99 | 0.00 | 0.00 | 0.00 |
June | 1222.53 | 531.93 | 690.60 | 1404.61 | 342.83 | 0.00 | 0.00 | 0.00 |
July | 1138.46 | 511.01 | 627.46 | 1368.19 | 302.52 | 0.00 | 0.00 | 0.00 |
August | 1118.95 | 559.76 | 559.19 | 1389.65 | 298.79 | 0.00 | 0.00 | 0.00 |
September | 827.30 | 381.56 | 445.74 | 909.46 | 431.08 | 0.00 | 0.00 | 0.00 |
October | 539.23 | 229.12 | 310.11 | 487.74 | 576.42 | 0.00 | 0.00 | 0.00 |
November | 264.30 | 74.61 | 189.69 | 138.08 | 711.56 | 0.00 | 0.00 | 0.00 |
December | 216.79 | 69.79 | 147.00 | 100.03 | 868.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 715.23 | 295.62 | 419.60 | 732.00 | 553.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 216.79 | 57.27 | 147.00 | 80.26 | 298.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1222.53 | 559.76 | 690.60 | 1404.61 | 868.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 8.93 | 2.26 | 6.67 | 3.17 | 33.16 | 0.00 | 0.00 | 0.00 |
February | 16.39 | 5.82 | 10.57 | 10.84 | 29.23 | 0.00 | 0.00 | 0.00 |
March | 24.47 | 8.86 | 15.61 | 20.77 | 24.26 | 0.00 | 0.00 | 0.00 |
April | 37.93 | 15.76 | 22.17 | 38.88 | 19.78 | 0.00 | 0.00 | 0.00 |
May | 40.36 | 14.03 | 26.33 | 43.30 | 16.96 | 0.00 | 0.00 | 0.00 |
June | 48.34 | 21.03 | 27.31 | 55.54 | 13.56 | 0.00 | 0.00 | 0.00 |
July | 45.01 | 20.20 | 24.81 | 54.10 | 11.96 | 0.00 | 0.00 | 0.00 |
August | 44.24 | 22.13 | 22.11 | 54.95 | 11.81 | 0.00 | 0.00 | 0.00 |
September | 32.71 | 15.09 | 17.62 | 35.96 | 17.04 | 0.00 | 0.00 | 0.00 |
October | 21.32 | 9.06 | 12.26 | 19.28 | 22.79 | 0.00 | 0.00 | 0.00 |
November | 10.45 | 2.95 | 7.50 | 5.46 | 28.13 | 0.00 | 0.00 | 0.00 |
December | 8.57 | 2.76 | 5.81 | 3.96 | 34.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.28 | 11.69 | 16.59 | 28.94 | 21.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.57 | 2.26 | 5.81 | 3.17 | 11.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.34 | 22.13 | 27.31 | 55.54 | 34.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 322.85 | 191.71 | 131.14 | 291.67 | 411.69 | 0.00 | 0.00 | 0.00 |
February | 496.49 | 307.33 | 189.15 | 513.07 | 377.83 | 0.00 | 0.00 | 0.00 |
March | 534.08 | 284.82 | 249.26 | 579.69 | 329.64 | 0.00 | 0.00 | 0.00 |
April | 563.88 | 244.84 | 319.05 | 648.81 | 277.68 | 0.00 | 0.00 | 0.00 |
May | 515.60 | 153.60 | 362.00 | 599.51 | 233.53 | 0.00 | 0.00 | 0.00 |
June | 471.72 | 126.65 | 345.07 | 558.85 | 186.18 | 0.00 | 0.00 | 0.00 |
July | 514.43 | 188.41 | 326.02 | 667.43 | 172.63 | 0.00 | 0.00 | 0.00 |
August | 552.70 | 257.73 | 294.96 | 739.82 | 169.13 | 0.00 | 0.00 | 0.00 |
September | 612.36 | 338.17 | 274.20 | 766.22 | 237.70 | 0.00 | 0.00 | 0.00 |
October | 554.70 | 342.48 | 212.21 | 634.37 | 307.30 | 0.00 | 0.00 | 0.00 |
November | 327.96 | 187.95 | 140.01 | 316.27 | 358.51 | 0.00 | 0.00 | 0.00 |
December | 343.14 | 222.06 | 121.08 | 339.37 | 432.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 483.95 | 236.71 | 247.24 | 554.74 | 290.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 322.85 | 126.65 | 121.08 | 291.67 | 169.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 612.36 | 342.48 | 362.00 | 766.22 | 432.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 322.85 | 191.71 | 131.14 | 291.67 | 411.69 | 0.00 | 0.00 | 0.00 |
February | 496.49 | 307.33 | 189.15 | 513.07 | 377.83 | 0.00 | 0.00 | 0.00 |
March | 534.08 | 284.82 | 249.26 | 579.69 | 329.64 | 0.00 | 0.00 | 0.00 |
April | 563.88 | 244.84 | 319.05 | 648.81 | 277.68 | 0.00 | 0.00 | 0.00 |
May | 515.60 | 153.60 | 362.00 | 599.51 | 233.53 | 0.00 | 0.00 | 0.00 |
June | 471.72 | 126.65 | 345.07 | 558.85 | 186.18 | 0.00 | 0.00 | 0.00 |
July | 514.43 | 188.41 | 326.02 | 667.43 | 172.63 | 0.00 | 0.00 | 0.00 |
August | 552.70 | 257.73 | 294.96 | 739.82 | 169.13 | 0.00 | 0.00 | 0.00 |
September | 612.36 | 338.17 | 274.20 | 766.22 | 237.70 | 0.00 | 0.00 | 0.00 |
October | 554.70 | 342.48 | 212.21 | 634.37 | 307.30 | 0.00 | 0.00 | 0.00 |
November | 327.96 | 187.95 | 140.01 | 316.27 | 358.51 | 0.00 | 0.00 | 0.00 |
December | 343.14 | 222.06 | 121.08 | 339.37 | 432.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 483.95 | 236.71 | 247.24 | 554.74 | 290.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 322.85 | 126.65 | 121.08 | 291.67 | 169.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 612.36 | 342.48 | 362.00 | 766.22 | 432.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 322.83 | 191.70 | 131.13 | 291.66 | 411.66 | 0.00 | 0.00 | 0.00 |
February | 496.46 | 307.31 | 189.14 | 513.04 | 377.81 | 0.00 | 0.00 | 0.00 |
March | 534.04 | 284.80 | 249.24 | 579.66 | 329.62 | 0.00 | 0.00 | 0.00 |
April | 563.85 | 244.82 | 319.03 | 648.77 | 277.66 | 0.00 | 0.00 | 0.00 |
May | 515.57 | 153.59 | 361.97 | 599.47 | 233.51 | 0.00 | 0.00 | 0.00 |
June | 471.69 | 126.64 | 345.05 | 558.82 | 186.17 | 0.00 | 0.00 | 0.00 |
July | 514.40 | 188.40 | 326.00 | 667.39 | 172.62 | 0.00 | 0.00 | 0.00 |
August | 552.66 | 257.71 | 294.95 | 739.77 | 169.12 | 0.00 | 0.00 | 0.00 |
September | 612.32 | 338.15 | 274.18 | 766.17 | 237.69 | 0.00 | 0.00 | 0.00 |
October | 554.66 | 342.46 | 212.20 | 634.33 | 307.28 | 0.00 | 0.00 | 0.00 |
November | 327.93 | 187.93 | 140.00 | 316.25 | 358.48 | 0.00 | 0.00 | 0.00 |
December | 343.11 | 222.04 | 121.07 | 339.35 | 432.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 483.92 | 236.69 | 247.23 | 554.70 | 290.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 322.83 | 126.64 | 121.07 | 291.66 | 169.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 612.32 | 342.46 | 361.97 | 766.17 | 432.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 238.26 | 70.26 | 168.00 | 103.63 | 846.41 | 0.00 | 0.00 | 0.00 |
February | 427.18 | 160.54 | 266.63 | 308.15 | 752.24 | 0.00 | 0.00 | 0.00 |
March | 598.58 | 202.04 | 396.55 | 516.71 | 628.44 | 0.00 | 0.00 | 0.00 |
April | 910.68 | 348.19 | 562.49 | 938.79 | 523.42 | 0.00 | 0.00 | 0.00 |
May | 1171.84 | 476.05 | 695.78 | 1308.06 | 454.53 | 0.00 | 0.00 | 0.00 |
June | 1126.99 | 437.57 | 689.42 | 1284.16 | 360.17 | 0.00 | 0.00 | 0.00 |
July | 1392.24 | 731.83 | 660.41 | 1734.68 | 337.91 | 0.00 | 0.00 | 0.00 |
August | 1151.71 | 588.09 | 563.62 | 1457.36 | 328.27 | 0.00 | 0.00 | 0.00 |
September | 937.89 | 450.02 | 487.87 | 1086.81 | 458.97 | 0.00 | 0.00 | 0.00 |
October | 533.95 | 217.56 | 316.39 | 495.09 | 591.87 | 0.00 | 0.00 | 0.00 |
November | 265.90 | 75.00 | 190.91 | 147.57 | 714.63 | 0.00 | 0.00 | 0.00 |
December | 223.54 | 76.60 | 146.94 | 122.18 | 878.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 750.19 | 320.69 | 429.49 | 795.12 | 572.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 223.54 | 70.26 | 146.94 | 103.63 | 328.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1392.24 | 731.83 | 695.78 | 1734.68 | 878.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.42 | 2.78 | 6.64 | 4.10 | 33.47 | 0.00 | 0.00 | 0.00 |
February | 16.89 | 6.35 | 10.54 | 12.18 | 29.74 | 0.00 | 0.00 | 0.00 |
March | 23.67 | 7.99 | 15.68 | 20.43 | 24.85 | 0.00 | 0.00 | 0.00 |
April | 36.01 | 13.77 | 22.24 | 37.12 | 20.70 | 0.00 | 0.00 | 0.00 |
May | 46.33 | 18.82 | 27.51 | 51.72 | 17.97 | 0.00 | 0.00 | 0.00 |
June | 44.56 | 17.30 | 27.26 | 50.77 | 14.24 | 0.00 | 0.00 | 0.00 |
July | 55.05 | 28.94 | 26.11 | 68.59 | 13.36 | 0.00 | 0.00 | 0.00 |
August | 45.54 | 23.25 | 22.28 | 57.62 | 12.98 | 0.00 | 0.00 | 0.00 |
September | 37.08 | 17.79 | 19.29 | 42.97 | 18.15 | 0.00 | 0.00 | 0.00 |
October | 21.11 | 8.60 | 12.51 | 19.58 | 23.40 | 0.00 | 0.00 | 0.00 |
November | 10.51 | 2.97 | 7.55 | 5.83 | 28.26 | 0.00 | 0.00 | 0.00 |
December | 8.84 | 3.03 | 5.81 | 4.83 | 34.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.66 | 12.68 | 16.98 | 31.44 | 22.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.84 | 2.78 | 5.81 | 4.10 | 12.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.05 | 28.94 | 27.51 | 68.59 | 34.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 219.21 | 0.00 | 219.21 | 7.14 | 1390.82 | 0.00 | 0.00 | 0.00 |
February | 341.09 | 0.00 | 341.09 | 65.92 | 1240.34 | 0.00 | 0.00 | 0.00 |
March | 502.54 | 0.00 | 502.54 | 207.56 | 1026.37 | 0.00 | 0.00 | 0.00 |
April | 711.15 | 2.52 | 708.63 | 456.58 | 827.56 | 0.00 | 0.00 | 0.00 |
May | 915.07 | 27.19 | 887.89 | 733.33 | 678.20 | 0.00 | 0.00 | 0.00 |
June | 962.18 | 63.54 | 898.64 | 852.42 | 525.67 | 0.00 | 0.00 | 0.00 |
July | 914.49 | 71.70 | 842.79 | 922.94 | 474.74 | 0.00 | 0.00 | 0.00 |
August | 740.29 | 20.01 | 720.28 | 761.56 | 465.92 | 0.00 | 0.00 | 0.00 |
September | 575.03 | 0.17 | 574.86 | 431.47 | 696.64 | 0.00 | 0.00 | 0.00 |
October | 393.99 | 0.00 | 393.99 | 171.02 | 920.19 | 0.00 | 0.00 | 0.00 |
November | 248.18 | 0.00 | 248.18 | 32.62 | 1138.38 | 0.00 | 0.00 | 0.00 |
December | 186.27 | 0.00 | 186.27 | 3.17 | 1409.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 560.20 | 15.54 | 544.66 | 389.17 | 897.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.27 | 0.00 | 186.27 | 3.17 | 465.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 962.18 | 71.70 | 898.64 | 922.94 | 1409.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 234.82 | 59.53 | 175.29 | 81.26 | 878.44 | 0.00 | 0.00 | 0.00 |
February | 430.87 | 152.93 | 277.95 | 277.94 | 776.69 | 0.00 | 0.00 | 0.00 |
March | 643.33 | 232.89 | 410.44 | 532.57 | 649.40 | 0.00 | 0.00 | 0.00 |
April | 997.26 | 414.38 | 582.89 | 1005.53 | 526.92 | 0.00 | 0.00 | 0.00 |
May | 1061.18 | 368.95 | 692.23 | 1122.80 | 450.93 | 0.00 | 0.00 | 0.00 |
June | 1270.88 | 552.97 | 717.91 | 1447.79 | 355.60 | 0.00 | 0.00 | 0.00 |
July | 1183.49 | 531.22 | 652.27 | 1411.19 | 315.06 | 0.00 | 0.00 | 0.00 |
August | 1163.20 | 581.90 | 581.30 | 1436.48 | 307.74 | 0.00 | 0.00 | 0.00 |
September | 860.02 | 396.65 | 463.37 | 940.17 | 442.54 | 0.00 | 0.00 | 0.00 |
October | 560.56 | 238.18 | 322.37 | 505.25 | 584.65 | 0.00 | 0.00 | 0.00 |
November | 274.75 | 77.57 | 197.19 | 143.41 | 726.11 | 0.00 | 0.00 | 0.00 |
December | 225.36 | 72.55 | 152.81 | 102.98 | 898.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 743.51 | 307.32 | 436.20 | 753.04 | 575.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 225.36 | 59.53 | 152.81 | 81.26 | 307.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1270.88 | 581.90 | 717.91 | 1447.79 | 898.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 968.51 | 575.10 | 393.40 | 853.10 | 1257.62 | 0.00 | 0.00 | 0.00 |
February | 1489.41 | 921.97 | 567.45 | 1504.27 | 1147.46 | 0.00 | 0.00 | 0.00 |
March | 1602.18 | 854.42 | 747.76 | 1694.99 | 1011.79 | 0.00 | 0.00 | 0.00 |
April | 1691.60 | 734.48 | 957.12 | 1895.87 | 863.75 | 0.00 | 0.00 | 0.00 |
May | 1546.75 | 460.79 | 1085.96 | 1747.77 | 730.41 | 0.00 | 0.00 | 0.00 |
June | 1415.13 | 379.94 | 1035.19 | 1633.14 | 581.30 | 0.00 | 0.00 | 0.00 |
July | 1543.26 | 565.22 | 978.04 | 1974.00 | 527.62 | 0.00 | 0.00 | 0.00 |
August | 1658.04 | 773.17 | 884.87 | 2196.52 | 509.70 | 0.00 | 0.00 | 0.00 |
September | 1837.03 | 1014.47 | 822.56 | 2276.98 | 706.85 | 0.00 | 0.00 | 0.00 |
October | 1664.04 | 1027.42 | 636.62 | 1880.88 | 905.33 | 0.00 | 0.00 | 0.00 |
November | 983.84 | 563.82 | 420.02 | 930.94 | 1071.82 | 0.00 | 0.00 | 0.00 |
December | 1029.37 | 666.15 | 363.23 | 1000.96 | 1307.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1451.80 | 710.10 | 741.70 | 1632.94 | 883.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 968.51 | 379.94 | 363.23 | 853.10 | 509.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1837.03 | 1027.42 | 1085.96 | 2276.98 | 1307.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 247.68 | 73.04 | 174.64 | 104.50 | 885.68 | 0.00 | 0.00 | 0.00 |
February | 444.07 | 166.89 | 277.18 | 311.61 | 790.07 | 0.00 | 0.00 | 0.00 |
March | 622.26 | 210.03 | 412.23 | 521.80 | 667.12 | 0.00 | 0.00 | 0.00 |
April | 946.70 | 361.96 | 584.74 | 955.04 | 557.30 | 0.00 | 0.00 | 0.00 |
May | 1218.18 | 494.88 | 723.30 | 1341.82 | 476.61 | 0.00 | 0.00 | 0.00 |
June | 1171.55 | 454.87 | 716.68 | 1319.76 | 377.77 | 0.00 | 0.00 | 0.00 |
July | 1447.29 | 760.77 | 686.52 | 1792.38 | 348.05 | 0.00 | 0.00 | 0.00 |
August | 1197.26 | 611.35 | 585.91 | 1505.93 | 338.21 | 0.00 | 0.00 | 0.00 |
September | 974.98 | 467.82 | 507.17 | 1124.04 | 470.13 | 0.00 | 0.00 | 0.00 |
October | 555.06 | 226.16 | 328.90 | 511.38 | 604.15 | 0.00 | 0.00 | 0.00 |
November | 276.42 | 77.96 | 198.46 | 152.11 | 730.96 | 0.00 | 0.00 | 0.00 |
December | 232.38 | 79.63 | 152.75 | 125.18 | 908.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 779.85 | 333.38 | 446.48 | 817.11 | 595.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 232.38 | 73.04 | 152.75 | 104.50 | 338.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1447.29 | 760.77 | 723.30 | 1792.38 | 908.73 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.587122E+09 | 0.00 | 0.587122E+09 | 25602144.86 | 0.351527E+10 |
February | 0.825167E+09 | 0.00 | 0.825167E+09 | 0.180336E+09 | 0.280191E+10 |
March | 0.134601E+10 | 0.00 | 0.134601E+10 | 0.600056E+09 | 0.255000E+10 |
April | 0.184330E+10 | 6538753.27 | 0.183676E+10 | 0.122936E+10 | 0.200367E+10 |
May | 0.245093E+10 | 72813512.30 | 0.237811E+10 | 0.200448E+10 | 0.171231E+10 |
June | 0.249396E+10 | 0.164691E+09 | 0.232927E+10 | 0.223266E+10 | 0.129856E+10 |
July | 0.244938E+10 | 0.192043E+09 | 0.225734E+10 | 0.248522E+10 | 0.121687E+10 |
August | 0.198279E+10 | 53600856.92 | 0.192919E+10 | 0.205544E+10 | 0.118950E+10 |
September | 0.149048E+10 | 439520.07 | 0.149004E+10 | 0.115269E+10 | 0.168512E+10 |
October | 0.105527E+10 | 0.00 | 0.105527E+10 | 0.508356E+09 | 0.225249E+10 |
November | 0.643273E+09 | 0.00 | 0.643273E+09 | 0.105521E+09 | 0.270882E+10 |
December | 0.498902E+09 | 0.00 | 0.498902E+09 | 14489534.85 | 0.352064E+10 |
Annual Sum or Average | 0.176666E+11 | 0.490126E+09 | 0.171765E+11 | 0.125942E+11 | 0.264551E+11 |
Minimum of Months | 0.498902E+09 | 0.00 | 0.498902E+09 | 14489534.85 | 0.118950E+10 |
Maximum of Months | 0.249396E+10 | 0.192043E+09 | 0.237811E+10 | 0.248522E+10 | 0.352064E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.628946E+09 | 0.159458E+09 | 0.469487E+09 | 0.230067E+09 | 0.222182E+10 |
February | 0.104237E+10 | 0.369959E+09 | 0.672413E+09 | 0.698130E+09 | 0.175956E+10 |
March | 0.172308E+10 | 0.623769E+09 | 0.109931E+10 | 0.145902E+10 | 0.162313E+10 |
April | 0.258491E+10 | 0.107407E+10 | 0.151085E+10 | 0.263492E+10 | 0.128646E+10 |
May | 0.284226E+10 | 0.988186E+09 | 0.185408E+10 | 0.302778E+10 | 0.114594E+10 |
June | 0.329412E+10 | 0.143329E+10 | 0.186083E+10 | 0.376004E+10 | 0.882726E+09 |
July | 0.316985E+10 | 0.142281E+10 | 0.174704E+10 | 0.378529E+10 | 0.812201E+09 |
August | 0.311552E+10 | 0.155856E+10 | 0.155696E+10 | 0.385263E+10 | 0.791193E+09 |
September | 0.222916E+10 | 0.102811E+10 | 0.120106E+10 | 0.245736E+10 | 0.107912E+10 |
October | 0.150140E+10 | 0.637951E+09 | 0.863446E+09 | 0.138815E+10 | 0.144539E+10 |
November | 0.712163E+09 | 0.201050E+09 | 0.511113E+09 | 0.393766E+09 | 0.173730E+10 |
December | 0.603605E+09 | 0.194318E+09 | 0.409287E+09 | 0.290944E+09 | 0.224872E+10 |
Annual Sum or Average | 0.234474E+11 | 0.969152E+10 | 0.137559E+11 | 0.239781E+11 | 0.170336E+11 |
Minimum of Months | 0.603605E+09 | 0.159458E+09 | 0.409287E+09 | 0.230067E+09 | 0.791193E+09 |
Maximum of Months | 0.329412E+10 | 0.155856E+10 | 0.186083E+10 | 0.385263E+10 | 0.224872E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.259405E+10 | 0.154036E+10 | 0.105369E+10 | 0.232221E+10 | 0.317525E+10 |
February | 0.360319E+10 | 0.223042E+10 | 0.137277E+10 | 0.368577E+10 | 0.259954E+10 |
March | 0.429128E+10 | 0.228849E+10 | 0.200279E+10 | 0.458198E+10 | 0.252272E+10 |
April | 0.438463E+10 | 0.190378E+10 | 0.248085E+10 | 0.494964E+10 | 0.210300E+10 |
May | 0.414282E+10 | 0.123418E+10 | 0.290864E+10 | 0.470698E+10 | 0.184526E+10 |
June | 0.366801E+10 | 0.984811E+09 | 0.268320E+10 | 0.424459E+10 | 0.143166E+10 |
July | 0.413346E+10 | 0.151389E+10 | 0.261958E+10 | 0.529194E+10 | 0.135082E+10 |
August | 0.444088E+10 | 0.207085E+10 | 0.237003E+10 | 0.588807E+10 | 0.130212E+10 |
September | 0.476159E+10 | 0.262950E+10 | 0.213209E+10 | 0.592998E+10 | 0.172046E+10 |
October | 0.445697E+10 | 0.275184E+10 | 0.170512E+10 | 0.508730E+10 | 0.223652E+10 |
November | 0.255010E+10 | 0.146142E+10 | 0.108868E+10 | 0.246189E+10 | 0.256446E+10 |
December | 0.275707E+10 | 0.178421E+10 | 0.972864E+09 | 0.272011E+10 | 0.327177E+10 |
Annual Sum or Average | 0.457841E+11 | 0.223938E+11 | 0.233903E+11 | 0.518705E+11 | 0.261236E+11 |
Minimum of Months | 0.255010E+10 | 0.984811E+09 | 0.972864E+09 | 0.232221E+10 | 0.130212E+10 |
Maximum of Months | 0.476159E+10 | 0.275184E+10 | 0.290864E+10 | 0.592998E+10 | 0.327177E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.663386E+09 | 0.195620E+09 | 0.467766E+09 | 0.289445E+09 | 0.223924E+10 |
February | 0.107430E+10 | 0.403750E+09 | 0.670546E+09 | 0.773374E+09 | 0.178827E+10 |
March | 0.166665E+10 | 0.562538E+09 | 0.110411E+10 | 0.142488E+10 | 0.166333E+10 |
April | 0.245384E+10 | 0.938194E+09 | 0.151564E+10 | 0.250189E+10 | 0.135447E+10 |
May | 0.326277E+10 | 0.132548E+10 | 0.193729E+10 | 0.361421E+10 | 0.120386E+10 |
June | 0.303667E+10 | 0.117903E+10 | 0.185763E+10 | 0.343085E+10 | 0.930225E+09 |
July | 0.387643E+10 | 0.203765E+10 | 0.183879E+10 | 0.480400E+10 | 0.891743E+09 |
August | 0.320674E+10 | 0.163745E+10 | 0.156929E+10 | 0.403995E+10 | 0.864092E+09 |
September | 0.252716E+10 | 0.121258E+10 | 0.131458E+10 | 0.293550E+10 | 0.114198E+10 |
October | 0.148668E+10 | 0.605749E+09 | 0.880929E+09 | 0.140230E+10 | 0.148782E+10 |
November | 0.716474E+09 | 0.202075E+09 | 0.514399E+09 | 0.413686E+09 | 0.174744E+10 |
December | 0.622413E+09 | 0.213285E+09 | 0.409128E+09 | 0.345509E+09 | 0.227238E+10 |
Annual Sum or Average | 0.245935E+11 | 0.105134E+11 | 0.140801E+11 | 0.259756E+11 | 0.175849E+11 |
Minimum of Months | 0.622413E+09 | 0.195620E+09 | 0.409128E+09 | 0.289445E+09 | 0.864092E+09 |
Maximum of Months | 0.387643E+10 | 0.203765E+10 | 0.193729E+10 | 0.480400E+10 | 0.227238E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195698E+09 | 0.00 | 0.195698E+09 | 7225155.63 | 0.123205E+10 |
February | 0.275043E+09 | 0.00 | 0.275043E+09 | 58325460.48 | 0.982407E+09 |
March | 0.448650E+09 | 0.00 | 0.448650E+09 | 0.203408E+09 | 0.882262E+09 |
April | 0.614405E+09 | 2179481.30 | 0.612225E+09 | 0.423532E+09 | 0.679171E+09 |
May | 0.816937E+09 | 24270022.45 | 0.792667E+09 | 0.684340E+09 | 0.580623E+09 |
June | 0.831280E+09 | 54894266.62 | 0.776386E+09 | 0.760157E+09 | 0.437998E+09 |
July | 0.816422E+09 | 64011385.35 | 0.752411E+09 | 0.842771E+09 | 0.410072E+09 |
August | 0.660900E+09 | 17866106.98 | 0.643034E+09 | 0.694436E+09 | 0.403702E+09 |
September | 0.496803E+09 | 146499.76 | 0.496657E+09 | 0.383778E+09 | 0.590535E+09 |
October | 0.351739E+09 | 0.00 | 0.351739E+09 | 0.157356E+09 | 0.821890E+09 |
November | 0.214414E+09 | 0.00 | 0.214414E+09 | 28668849.44 | 0.996068E+09 |
December | 0.166293E+09 | 0.00 | 0.166293E+09 | 2939017.50 | 0.126330E+10 |
Annual Sum or Average | 0.588859E+10 | 0.163368E+09 | 0.572522E+10 | 0.424694E+10 | 0.928007E+10 |
Minimum of Months | 0.166293E+09 | 0.00 | 0.166293E+09 | 2939017.50 | 0.403702E+09 |
Maximum of Months | 0.831280E+09 | 64011385.35 | 0.792667E+09 | 0.842771E+09 | 0.126330E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195711E+09 | 0.00 | 0.195711E+09 | 7225612.25 | 0.123213E+10 |
February | 0.275060E+09 | 0.00 | 0.275060E+09 | 58329146.56 | 0.982469E+09 |
March | 0.448678E+09 | 0.00 | 0.448678E+09 | 0.203421E+09 | 0.882318E+09 |
April | 0.614444E+09 | 2179619.04 | 0.612264E+09 | 0.423559E+09 | 0.679214E+09 |
May | 0.816989E+09 | 24271556.27 | 0.792718E+09 | 0.684383E+09 | 0.580660E+09 |
June | 0.831333E+09 | 54897735.85 | 0.776435E+09 | 0.760205E+09 | 0.438026E+09 |
July | 0.816474E+09 | 64015430.76 | 0.752459E+09 | 0.842824E+09 | 0.410098E+09 |
August | 0.660942E+09 | 17867236.09 | 0.643074E+09 | 0.694480E+09 | 0.403728E+09 |
September | 0.496835E+09 | 146509.02 | 0.496688E+09 | 0.383802E+09 | 0.590573E+09 |
October | 0.351762E+09 | 0.00 | 0.351762E+09 | 0.157366E+09 | 0.821942E+09 |
November | 0.214428E+09 | 0.00 | 0.214428E+09 | 28670661.26 | 0.996131E+09 |
December | 0.166303E+09 | 0.00 | 0.166303E+09 | 2939203.24 | 0.126338E+10 |
Annual Sum or Average | 0.588896E+10 | 0.163378E+09 | 0.572558E+10 | 0.424720E+10 | 0.928066E+10 |
Minimum of Months | 0.166303E+09 | 0.00 | 0.166303E+09 | 2939203.24 | 0.403728E+09 |
Maximum of Months | 0.831333E+09 | 64015430.76 | 0.792718E+09 | 0.842824E+09 | 0.126338E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195711E+09 | 0.00 | 0.195711E+09 | 7225612.25 | 0.123213E+10 |
February | 0.275060E+09 | 0.00 | 0.275060E+09 | 58329146.56 | 0.982469E+09 |
March | 0.448678E+09 | 0.00 | 0.448678E+09 | 0.203421E+09 | 0.882318E+09 |
April | 0.614444E+09 | 2179619.04 | 0.612264E+09 | 0.423559E+09 | 0.679214E+09 |
May | 0.816989E+09 | 24271556.27 | 0.792718E+09 | 0.684383E+09 | 0.580660E+09 |
June | 0.831333E+09 | 54897735.85 | 0.776435E+09 | 0.760205E+09 | 0.438026E+09 |
July | 0.816474E+09 | 64015430.76 | 0.752459E+09 | 0.842824E+09 | 0.410098E+09 |
August | 0.660942E+09 | 17867236.09 | 0.643074E+09 | 0.694480E+09 | 0.403728E+09 |
September | 0.496835E+09 | 146509.02 | 0.496688E+09 | 0.383802E+09 | 0.590573E+09 |
October | 0.351762E+09 | 0.00 | 0.351762E+09 | 0.157366E+09 | 0.821942E+09 |
November | 0.214428E+09 | 0.00 | 0.214428E+09 | 28670661.26 | 0.996131E+09 |
December | 0.166303E+09 | 0.00 | 0.166303E+09 | 2939203.24 | 0.126338E+10 |
Annual Sum or Average | 0.588896E+10 | 0.163378E+09 | 0.572558E+10 | 0.424720E+10 | 0.928066E+10 |
Minimum of Months | 0.166303E+09 | 0.00 | 0.166303E+09 | 2939203.24 | 0.403728E+09 |
Maximum of Months | 0.831333E+09 | 64015430.76 | 0.792718E+09 | 0.842824E+09 | 0.126338E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.605019E+09 | 0.153392E+09 | 0.451627E+09 | 0.214966E+09 | 0.224633E+10 |
February | 0.100272E+10 | 0.355884E+09 | 0.646833E+09 | 0.663382E+09 | 0.178844E+10 |
March | 0.165753E+10 | 0.600038E+09 | 0.105749E+10 | 0.140725E+10 | 0.164346E+10 |
April | 0.248657E+10 | 0.103320E+10 | 0.145337E+10 | 0.254874E+10 | 0.129654E+10 |
May | 0.273414E+10 | 0.950591E+09 | 0.178355E+10 | 0.293302E+10 | 0.114902E+10 |
June | 0.316881E+10 | 0.137876E+10 | 0.179004E+10 | 0.364076E+10 | 0.888615E+09 |
July | 0.304926E+10 | 0.136868E+10 | 0.168059E+10 | 0.366457E+10 | 0.810282E+09 |
August | 0.299699E+10 | 0.149926E+10 | 0.149773E+10 | 0.372205E+10 | 0.800287E+09 |
September | 0.214436E+10 | 0.988992E+09 | 0.115537E+10 | 0.235731E+10 | 0.111735E+10 |
October | 0.144428E+10 | 0.613680E+09 | 0.830600E+09 | 0.130635E+10 | 0.154389E+10 |
November | 0.685071E+09 | 0.193401E+09 | 0.491669E+09 | 0.357909E+09 | 0.184435E+10 |
December | 0.580642E+09 | 0.186925E+09 | 0.393717E+09 | 0.267922E+09 | 0.232676E+10 |
Annual Sum or Average | 0.225554E+11 | 0.932281E+10 | 0.132326E+11 | 0.230842E+11 | 0.174553E+11 |
Minimum of Months | 0.580642E+09 | 0.153392E+09 | 0.393717E+09 | 0.214966E+09 | 0.800287E+09 |
Maximum of Months | 0.316881E+10 | 0.149926E+10 | 0.179004E+10 | 0.372205E+10 | 0.232676E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 23921898.09 | 6064965.85 | 17856932.24 | 8499568.64 | 88817726.52 |
February | 39646506.05 | 14071314.79 | 25575191.26 | 26229535.06 | 70713135.59 |
March | 65537342.28 | 23724958.93 | 41812383.35 | 55641259.53 | 64981061.30 |
April | 98316886.11 | 40851901.75 | 57464984.36 | 0.100775E+09 | 51264019.85 |
May | 0.108105E+09 | 37585511.86 | 70519764.21 | 0.115969E+09 | 45431122.07 |
June | 0.125292E+09 | 54515071.73 | 70776748.80 | 0.143952E+09 | 35135021.57 |
July | 0.120565E+09 | 54116211.48 | 66448838.13 | 0.144894E+09 | 32037805.90 |
August | 0.118498E+09 | 59279433.31 | 59219049.17 | 0.147166E+09 | 31642619.90 |
September | 84786050.88 | 39103868.49 | 45682182.38 | 93205821.08 | 44178961.98 |
October | 57105528.01 | 24264369.64 | 32841158.37 | 51651995.45 | 61044093.78 |
November | 27087072.74 | 7646912.87 | 19440159.86 | 14151413.24 | 72924012.03 |
December | 22958061.59 | 7390845.48 | 15567216.11 | 10593380.01 | 91997904.02 |
Annual Sum or Average | 0.891820E+09 | 0.368615E+09 | 0.523205E+09 | 0.912729E+09 | 0.690167E+09 |
Minimum of Months | 22958061.59 | 6064965.85 | 15567216.11 | 8499568.64 | 31642619.90 |
Maximum of Months | 0.125292E+09 | 59279433.31 | 70776748.80 | 0.147166E+09 | 91997904.02 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.864710E+09 | 0.513469E+09 | 0.351241E+09 | 0.781222E+09 | 0.110267E+10 |
February | 0.120110E+10 | 0.743498E+09 | 0.457603E+09 | 0.124121E+10 | 0.914050E+09 |
March | 0.143047E+10 | 0.762855E+09 | 0.667616E+09 | 0.155265E+10 | 0.882915E+09 |
April | 0.146159E+10 | 0.634613E+09 | 0.826974E+09 | 0.168171E+10 | 0.719734E+09 |
May | 0.138098E+10 | 0.411408E+09 | 0.969573E+09 | 0.160573E+10 | 0.625483E+09 |
June | 0.122271E+10 | 0.328281E+09 | 0.894425E+09 | 0.144855E+10 | 0.482589E+09 |
July | 0.137786E+10 | 0.504646E+09 | 0.873215E+09 | 0.178764E+10 | 0.462384E+09 |
August | 0.148034E+10 | 0.690306E+09 | 0.790032E+09 | 0.198153E+10 | 0.452999E+09 |
September | 0.158725E+10 | 0.876530E+09 | 0.710716E+09 | 0.198605E+10 | 0.616130E+09 |
October | 0.148570E+10 | 0.917311E+09 | 0.568391E+09 | 0.169911E+10 | 0.823062E+09 |
November | 0.850061E+09 | 0.487157E+09 | 0.362905E+09 | 0.819762E+09 | 0.929245E+09 |
December | 0.919054E+09 | 0.594756E+09 | 0.324298E+09 | 0.908978E+09 | 0.115877E+10 |
Annual Sum or Average | 0.152618E+11 | 0.746483E+10 | 0.779699E+10 | 0.174941E+11 | 0.917003E+10 |
Minimum of Months | 0.850061E+09 | 0.328281E+09 | 0.324298E+09 | 0.781222E+09 | 0.452999E+09 |
Maximum of Months | 0.158725E+10 | 0.917311E+09 | 0.969573E+09 | 0.198605E+10 | 0.115877E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.864710E+09 | 0.513469E+09 | 0.351241E+09 | 0.781222E+09 | 0.110267E+10 |
February | 0.120110E+10 | 0.743498E+09 | 0.457603E+09 | 0.124121E+10 | 0.914050E+09 |
March | 0.143047E+10 | 0.762855E+09 | 0.667616E+09 | 0.155265E+10 | 0.882915E+09 |
April | 0.146159E+10 | 0.634613E+09 | 0.826974E+09 | 0.168171E+10 | 0.719734E+09 |
May | 0.138098E+10 | 0.411408E+09 | 0.969573E+09 | 0.160573E+10 | 0.625483E+09 |
June | 0.122271E+10 | 0.328281E+09 | 0.894425E+09 | 0.144855E+10 | 0.482589E+09 |
July | 0.137786E+10 | 0.504646E+09 | 0.873215E+09 | 0.178764E+10 | 0.462384E+09 |
August | 0.148034E+10 | 0.690306E+09 | 0.790032E+09 | 0.198153E+10 | 0.452999E+09 |
September | 0.158725E+10 | 0.876530E+09 | 0.710716E+09 | 0.198605E+10 | 0.616130E+09 |
October | 0.148570E+10 | 0.917311E+09 | 0.568391E+09 | 0.169911E+10 | 0.823062E+09 |
November | 0.850061E+09 | 0.487157E+09 | 0.362905E+09 | 0.819762E+09 | 0.929245E+09 |
December | 0.919054E+09 | 0.594756E+09 | 0.324298E+09 | 0.908978E+09 | 0.115877E+10 |
Annual Sum or Average | 0.152618E+11 | 0.746483E+10 | 0.779699E+10 | 0.174941E+11 | 0.917003E+10 |
Minimum of Months | 0.850061E+09 | 0.328281E+09 | 0.324298E+09 | 0.781222E+09 | 0.452999E+09 |
Maximum of Months | 0.158725E+10 | 0.917311E+09 | 0.969573E+09 | 0.198605E+10 | 0.115877E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.864655E+09 | 0.513436E+09 | 0.351219E+09 | 0.781173E+09 | 0.110260E+10 |
February | 0.120103E+10 | 0.743451E+09 | 0.457575E+09 | 0.124114E+10 | 0.913992E+09 |
March | 0.143038E+10 | 0.762806E+09 | 0.667574E+09 | 0.155255E+10 | 0.882859E+09 |
April | 0.146149E+10 | 0.634573E+09 | 0.826921E+09 | 0.168161E+10 | 0.719689E+09 |
May | 0.138089E+10 | 0.411382E+09 | 0.969512E+09 | 0.160563E+10 | 0.625444E+09 |
June | 0.122263E+10 | 0.328260E+09 | 0.894368E+09 | 0.144846E+10 | 0.482559E+09 |
July | 0.137777E+10 | 0.504614E+09 | 0.873160E+09 | 0.178753E+10 | 0.462355E+09 |
August | 0.148024E+10 | 0.690263E+09 | 0.789982E+09 | 0.198141E+10 | 0.452970E+09 |
September | 0.158715E+10 | 0.876474E+09 | 0.710671E+09 | 0.198592E+10 | 0.616091E+09 |
October | 0.148561E+10 | 0.917253E+09 | 0.568355E+09 | 0.169900E+10 | 0.823010E+09 |
November | 0.850007E+09 | 0.487126E+09 | 0.362882E+09 | 0.819710E+09 | 0.929186E+09 |
December | 0.918996E+09 | 0.594719E+09 | 0.324277E+09 | 0.908920E+09 | 0.115869E+10 |
Annual Sum or Average | 0.152609E+11 | 0.746436E+10 | 0.779650E+10 | 0.174930E+11 | 0.916945E+10 |
Minimum of Months | 0.850007E+09 | 0.328260E+09 | 0.324277E+09 | 0.781173E+09 | 0.452970E+09 |
Maximum of Months | 0.158715E+10 | 0.917253E+09 | 0.969512E+09 | 0.198592E+10 | 0.115869E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.638149E+09 | 0.188178E+09 | 0.449971E+09 | 0.277567E+09 | 0.226703E+10 |
February | 0.103343E+10 | 0.388389E+09 | 0.645037E+09 | 0.745479E+09 | 0.181982E+10 |
March | 0.160325E+10 | 0.541137E+09 | 0.106211E+10 | 0.138395E+10 | 0.168322E+10 |
April | 0.236049E+10 | 0.902501E+09 | 0.145799E+10 | 0.243335E+10 | 0.135671E+10 |
May | 0.313864E+10 | 0.127506E+10 | 0.186359E+10 | 0.350351E+10 | 0.121740E+10 |
June | 0.292115E+10 | 0.113418E+10 | 0.178697E+10 | 0.332855E+10 | 0.933565E+09 |
July | 0.372896E+10 | 0.196013E+10 | 0.176884E+10 | 0.464616E+10 | 0.905059E+09 |
August | 0.308475E+10 | 0.157515E+10 | 0.150959E+10 | 0.390339E+10 | 0.879229E+09 |
September | 0.243102E+10 | 0.116645E+10 | 0.126457E+10 | 0.281700E+10 | 0.118964E+10 |
October | 0.143012E+10 | 0.582703E+09 | 0.847417E+09 | 0.132604E+10 | 0.158528E+10 |
November | 0.689217E+09 | 0.194387E+09 | 0.494830E+09 | 0.382498E+09 | 0.185233E+10 |
December | 0.598734E+09 | 0.205170E+09 | 0.393564E+09 | 0.327250E+09 | 0.235414E+10 |
Annual Sum or Average | 0.236579E+11 | 0.101134E+11 | 0.135445E+11 | 0.250748E+11 | 0.180434E+11 |
Minimum of Months | 0.598734E+09 | 0.188178E+09 | 0.393564E+09 | 0.277567E+09 | 0.879229E+09 |
Maximum of Months | 0.372896E+10 | 0.196013E+10 | 0.186359E+10 | 0.464616E+10 | 0.235414E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25231767.38 | 7440354.05 | 17791413.33 | 10974696.69 | 89636404.00 |
February | 40860647.86 | 15356510.63 | 25504137.23 | 29475452.27 | 71954232.17 |
March | 63390830.16 | 21395991.30 | 41994838.86 | 54720070.02 | 66552831.91 |
April | 93331294.65 | 35683953.99 | 57647340.66 | 96211963.72 | 53642992.36 |
May | 0.124099E+09 | 50414380.86 | 73684463.84 | 0.138525E+09 | 48134943.89 |
June | 0.115499E+09 | 44844233.36 | 70654925.38 | 0.131608E+09 | 36912309.68 |
July | 0.147439E+09 | 77501338.57 | 69938125.96 | 0.183705E+09 | 35785199.88 |
August | 0.121968E+09 | 62279936.84 | 59687787.71 | 0.154336E+09 | 34763922.23 |
September | 96120062.69 | 46120298.40 | 49999764.29 | 0.111381E+09 | 47037256.51 |
October | 56545518.75 | 23039491.93 | 33506026.81 | 52430346.95 | 62680429.79 |
November | 27250956.70 | 7685865.85 | 19565090.85 | 15123546.26 | 73239540.37 |
December | 23673346.52 | 8112218.00 | 15561128.53 | 12939099.20 | 93080657.25 |
Annual Sum or Average | 0.935410E+09 | 0.399875E+09 | 0.535535E+09 | 0.991430E+09 | 0.713421E+09 |
Minimum of Months | 23673346.52 | 7440354.05 | 15561128.53 | 10974696.69 | 34763922.23 |
Maximum of Months | 0.147439E+09 | 77501338.57 | 73684463.84 | 0.183705E+09 | 93080657.25 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.587122E+09 | 0.00 | 0.587122E+09 | 19123361.13 | 0.372519E+10 |
February | 0.825167E+09 | 0.00 | 0.825167E+09 | 0.159462E+09 | 0.300062E+10 |
March | 0.134601E+10 | 0.00 | 0.134601E+10 | 0.555933E+09 | 0.274902E+10 |
April | 0.184330E+10 | 6538753.27 | 0.183676E+10 | 0.118344E+10 | 0.214503E+10 |
May | 0.245093E+10 | 72813512.30 | 0.237811E+10 | 0.196414E+10 | 0.181650E+10 |
June | 0.249396E+10 | 0.164691E+09 | 0.232927E+10 | 0.220948E+10 | 0.136253E+10 |
July | 0.244938E+10 | 0.192043E+09 | 0.225734E+10 | 0.247201E+10 | 0.127154E+10 |
August | 0.198279E+10 | 53600856.92 | 0.192919E+10 | 0.203976E+10 | 0.124793E+10 |
September | 0.149048E+10 | 439520.07 | 0.149004E+10 | 0.111836E+10 | 0.180569E+10 |
October | 0.105527E+10 | 0.00 | 0.105527E+10 | 0.458060E+09 | 0.246464E+10 |
November | 0.643273E+09 | 0.00 | 0.643273E+09 | 84561618.71 | 0.295069E+10 |
December | 0.498902E+09 | 0.00 | 0.498902E+09 | 8499574.58 | 0.377627E+10 |
Annual Sum or Average | 0.176666E+11 | 0.490126E+09 | 0.171765E+11 | 0.122728E+11 | 0.283156E+11 |
Minimum of Months | 0.498902E+09 | 0.00 | 0.498902E+09 | 8499574.58 | 0.124793E+10 |
Maximum of Months | 0.249396E+10 | 0.192043E+09 | 0.237811E+10 | 0.247201E+10 | 0.377627E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.628946E+09 | 0.159458E+09 | 0.469487E+09 | 0.217655E+09 | 0.235280E+10 |
February | 0.104237E+10 | 0.369959E+09 | 0.672413E+09 | 0.672383E+09 | 0.187896E+10 |
March | 0.172308E+10 | 0.623769E+09 | 0.109931E+10 | 0.142644E+10 | 0.173934E+10 |
April | 0.258491E+10 | 0.107407E+10 | 0.151085E+10 | 0.260632E+10 | 0.136578E+10 |
May | 0.284226E+10 | 0.988186E+09 | 0.185408E+10 | 0.300730E+10 | 0.120777E+10 |
June | 0.329412E+10 | 0.143329E+10 | 0.186083E+10 | 0.375267E+10 | 0.921727E+09 |
July | 0.316985E+10 | 0.142281E+10 | 0.174704E+10 | 0.377974E+10 | 0.843849E+09 |
August | 0.311552E+10 | 0.155856E+10 | 0.155696E+10 | 0.384748E+10 | 0.824253E+09 |
September | 0.222916E+10 | 0.102811E+10 | 0.120106E+10 | 0.243692E+10 | 0.114707E+10 |
October | 0.150140E+10 | 0.637951E+09 | 0.863446E+09 | 0.135326E+10 | 0.156593E+10 |
November | 0.712163E+09 | 0.201050E+09 | 0.511113E+09 | 0.371724E+09 | 0.188209E+10 |
December | 0.603605E+09 | 0.194318E+09 | 0.409287E+09 | 0.275833E+09 | 0.240685E+10 |
Annual Sum or Average | 0.234474E+11 | 0.969152E+10 | 0.137559E+11 | 0.237477E+11 | 0.181364E+11 |
Minimum of Months | 0.603605E+09 | 0.159458E+09 | 0.409287E+09 | 0.217655E+09 | 0.824253E+09 |
Maximum of Months | 0.329412E+10 | 0.155856E+10 | 0.186083E+10 | 0.384748E+10 | 0.240685E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.259405E+10 | 0.154036E+10 | 0.105369E+10 | 0.228494E+10 | 0.336842E+10 |
February | 0.360319E+10 | 0.223042E+10 | 0.137277E+10 | 0.363912E+10 | 0.277593E+10 |
March | 0.429128E+10 | 0.228849E+10 | 0.200279E+10 | 0.453986E+10 | 0.270997E+10 |
April | 0.438463E+10 | 0.190378E+10 | 0.248085E+10 | 0.491411E+10 | 0.223884E+10 |
May | 0.414282E+10 | 0.123418E+10 | 0.290864E+10 | 0.468123E+10 | 0.195632E+10 |
June | 0.366801E+10 | 0.984811E+09 | 0.268320E+10 | 0.423311E+10 | 0.150672E+10 |
July | 0.413346E+10 | 0.151389E+10 | 0.261958E+10 | 0.528717E+10 | 0.141319E+10 |
August | 0.444088E+10 | 0.207085E+10 | 0.237003E+10 | 0.588315E+10 | 0.136518E+10 |
September | 0.476159E+10 | 0.262950E+10 | 0.213209E+10 | 0.590193E+10 | 0.183215E+10 |
October | 0.445697E+10 | 0.275184E+10 | 0.170512E+10 | 0.503775E+10 | 0.242484E+10 |
November | 0.255010E+10 | 0.146142E+10 | 0.108868E+10 | 0.241300E+10 | 0.277815E+10 |
December | 0.275707E+10 | 0.178421E+10 | 0.972864E+09 | 0.268098E+10 | 0.350299E+10 |
Annual Sum or Average | 0.457841E+11 | 0.223938E+11 | 0.233903E+11 | 0.514963E+11 | 0.278727E+11 |
Minimum of Months | 0.255010E+10 | 0.984811E+09 | 0.972864E+09 | 0.228494E+10 | 0.136518E+10 |
Maximum of Months | 0.476159E+10 | 0.275184E+10 | 0.290864E+10 | 0.590193E+10 | 0.350299E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.663386E+09 | 0.195620E+09 | 0.467766E+09 | 0.279900E+09 | 0.237221E+10 |
February | 0.107430E+10 | 0.403750E+09 | 0.670546E+09 | 0.753840E+09 | 0.191134E+10 |
March | 0.166665E+10 | 0.562538E+09 | 0.110411E+10 | 0.139760E+10 | 0.178682E+10 |
April | 0.245384E+10 | 0.938194E+09 | 0.151564E+10 | 0.247546E+10 | 0.144453E+10 |
May | 0.326277E+10 | 0.132548E+10 | 0.193729E+10 | 0.359394E+10 | 0.127656E+10 |
June | 0.303667E+10 | 0.117903E+10 | 0.185763E+10 | 0.342083E+10 | 0.979175E+09 |
July | 0.387643E+10 | 0.203765E+10 | 0.183879E+10 | 0.480070E+10 | 0.932214E+09 |
August | 0.320674E+10 | 0.163745E+10 | 0.156929E+10 | 0.403349E+10 | 0.905858E+09 |
September | 0.252716E+10 | 0.121258E+10 | 0.131458E+10 | 0.291351E+10 | 0.121858E+10 |
October | 0.148668E+10 | 0.605749E+09 | 0.880929E+09 | 0.136968E+10 | 0.161815E+10 |
November | 0.716474E+09 | 0.202075E+09 | 0.514399E+09 | 0.394269E+09 | 0.189466E+10 |
December | 0.622413E+09 | 0.213285E+09 | 0.409128E+09 | 0.335271E+09 | 0.243395E+10 |
Annual Sum or Average | 0.245935E+11 | 0.105134E+11 | 0.140801E+11 | 0.257685E+11 | 0.187740E+11 |
Minimum of Months | 0.622413E+09 | 0.195620E+09 | 0.409128E+09 | 0.279900E+09 | 0.905858E+09 |
Maximum of Months | 0.387643E+10 | 0.203765E+10 | 0.193729E+10 | 0.480070E+10 | 0.243395E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 9.56 | 1312.45 | 219.21 | 0.00 | 219.21 | 0.00 | 0.00 |
February | 74.54 | 1158.20 | 341.09 | 0.00 | 341.09 | 0.00 | 0.00 |
March | 224.04 | 952.06 | 502.54 | 0.00 | 502.54 | 0.00 | 0.00 |
April | 474.29 | 773.02 | 711.15 | 2.52 | 708.63 | 0.00 | 0.00 |
May | 748.39 | 639.30 | 915.07 | 27.19 | 887.89 | 0.00 | 0.00 |
June | 861.37 | 500.99 | 962.18 | 63.54 | 898.64 | 0.00 | 0.00 |
July | 927.88 | 454.33 | 914.49 | 71.70 | 842.79 | 0.00 | 0.00 |
August | 767.41 | 444.11 | 740.29 | 20.01 | 720.28 | 0.00 | 0.00 |
September | 444.71 | 650.12 | 575.03 | 0.17 | 574.86 | 0.00 | 0.00 |
October | 189.80 | 840.98 | 393.99 | 0.00 | 393.99 | 0.00 | 0.00 |
November | 40.71 | 1045.07 | 248.18 | 0.00 | 248.18 | 0.00 | 0.00 |
December | 5.41 | 1314.46 | 186.27 | 0.00 | 186.27 | 0.00 | 0.00 |
Annual Sum or Average | 399.36 | 838.89 | 560.20 | 15.54 | 544.66 | 0.00 | 0.00 |
Minimum of Months | 5.41 | 444.11 | 186.27 | 0.00 | 186.27 | 0.00 | 0.00 |
Maximum of Months | 927.88 | 1314.46 | 962.18 | 71.70 | 898.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 85.90 | 829.53 | 234.82 | 59.53 | 175.29 | 0.00 | 0.00 |
February | 288.58 | 727.33 | 430.87 | 152.93 | 277.95 | 0.00 | 0.00 |
March | 544.74 | 606.01 | 643.33 | 232.89 | 410.44 | 0.00 | 0.00 |
April | 1016.56 | 496.32 | 997.26 | 414.38 | 582.89 | 0.00 | 0.00 |
May | 1130.44 | 427.84 | 1061.18 | 368.95 | 692.23 | 0.00 | 0.00 |
June | 1450.63 | 340.56 | 1270.88 | 552.97 | 717.91 | 0.00 | 0.00 |
July | 1413.27 | 303.24 | 1183.49 | 531.22 | 652.27 | 0.00 | 0.00 |
August | 1438.41 | 295.40 | 1163.20 | 581.90 | 581.30 | 0.00 | 0.00 |
September | 948.06 | 416.33 | 860.02 | 396.65 | 463.37 | 0.00 | 0.00 |
October | 518.27 | 539.65 | 560.56 | 238.18 | 322.37 | 0.00 | 0.00 |
November | 151.92 | 670.26 | 274.75 | 77.57 | 197.19 | 0.00 | 0.00 |
December | 108.63 | 839.58 | 225.36 | 72.55 | 152.81 | 0.00 | 0.00 |
Annual Sum or Average | 760.34 | 540.13 | 743.51 | 307.32 | 436.20 | 0.00 | 0.00 |
Minimum of Months | 85.90 | 295.40 | 225.36 | 59.53 | 152.81 | 0.00 | 0.00 |
Maximum of Months | 1450.63 | 839.58 | 1270.88 | 581.90 | 717.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 867.01 | 1185.50 | 968.51 | 575.10 | 393.40 | 0.00 | 0.00 |
February | 1523.55 | 1074.54 | 1489.41 | 921.97 | 567.45 | 0.00 | 0.00 |
March | 1710.72 | 941.87 | 1602.18 | 854.42 | 747.76 | 0.00 | 0.00 |
April | 1909.58 | 811.34 | 1691.60 | 734.48 | 957.12 | 0.00 | 0.00 |
May | 1757.39 | 688.94 | 1546.75 | 460.79 | 1085.96 | 0.00 | 0.00 |
June | 1637.57 | 552.34 | 1415.13 | 379.94 | 1035.19 | 0.00 | 0.00 |
July | 1975.78 | 504.34 | 1543.26 | 565.22 | 978.04 | 0.00 | 0.00 |
August | 2198.35 | 486.16 | 1658.04 | 773.17 | 884.87 | 0.00 | 0.00 |
September | 2287.80 | 663.76 | 1837.03 | 1014.47 | 822.56 | 0.00 | 0.00 |
October | 1899.38 | 835.02 | 1664.04 | 1027.42 | 636.62 | 0.00 | 0.00 |
November | 949.80 | 989.37 | 983.84 | 563.82 | 420.02 | 0.00 | 0.00 |
December | 1015.57 | 1221.54 | 1029.37 | 666.15 | 363.23 | 0.00 | 0.00 |
Annual Sum or Average | 1644.80 | 828.37 | 1451.80 | 710.10 | 741.70 | 0.00 | 0.00 |
Minimum of Months | 867.01 | 486.16 | 968.51 | 379.94 | 363.23 | 0.00 | 0.00 |
Maximum of Months | 2287.80 | 1221.54 | 1837.03 | 1027.42 | 1085.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 108.07 | 836.04 | 247.68 | 73.04 | 174.64 | 0.00 | 0.00 |
February | 319.68 | 739.20 | 444.07 | 166.89 | 277.18 | 0.00 | 0.00 |
March | 531.99 | 621.02 | 622.26 | 210.03 | 412.23 | 0.00 | 0.00 |
April | 965.23 | 522.56 | 946.70 | 361.96 | 584.74 | 0.00 | 0.00 |
May | 1349.39 | 449.47 | 1218.18 | 494.88 | 723.30 | 0.00 | 0.00 |
June | 1323.63 | 358.88 | 1171.55 | 454.87 | 716.68 | 0.00 | 0.00 |
July | 1793.61 | 332.94 | 1447.29 | 760.77 | 686.52 | 0.00 | 0.00 |
August | 1508.35 | 322.62 | 1197.26 | 611.35 | 585.91 | 0.00 | 0.00 |
September | 1132.52 | 440.58 | 974.98 | 467.82 | 507.17 | 0.00 | 0.00 |
October | 523.56 | 555.49 | 555.06 | 226.16 | 328.90 | 0.00 | 0.00 |
November | 159.60 | 674.17 | 276.42 | 77.96 | 198.46 | 0.00 | 0.00 |
December | 129.00 | 848.41 | 232.38 | 79.63 | 152.75 | 0.00 | 0.00 |
Annual Sum or Average | 823.68 | 557.61 | 779.85 | 333.38 | 446.48 | 0.00 | 0.00 |
Minimum of Months | 108.07 | 322.62 | 232.38 | 73.04 | 152.75 | 0.00 | 0.00 |
Maximum of Months | 1793.61 | 848.41 | 1447.29 | 760.77 | 723.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 8.09 | 1380.04 | 219.21 | 0.00 | 219.21 | 0.00 | 0.00 |
February | 72.33 | 1218.31 | 341.09 | 0.00 | 341.09 | 0.00 | 0.00 |
March | 227.84 | 988.24 | 502.54 | 0.00 | 502.54 | 0.00 | 0.00 |
April | 490.22 | 786.11 | 711.15 | 2.52 | 708.62 | 0.00 | 0.00 |
May | 766.54 | 650.37 | 915.07 | 27.19 | 887.88 | 0.00 | 0.00 |
June | 879.85 | 506.96 | 962.17 | 63.54 | 898.63 | 0.00 | 0.00 |
July | 944.00 | 459.33 | 914.49 | 71.70 | 842.79 | 0.00 | 0.00 |
August | 777.85 | 452.19 | 740.29 | 20.01 | 720.27 | 0.00 | 0.00 |
September | 444.21 | 683.52 | 575.03 | 0.17 | 574.86 | 0.00 | 0.00 |
October | 176.26 | 920.61 | 393.99 | 0.00 | 393.99 | 0.00 | 0.00 |
November | 33.18 | 1152.91 | 248.17 | 0.00 | 248.17 | 0.00 | 0.00 |
December | 3.29 | 1415.04 | 186.27 | 0.00 | 186.27 | 0.00 | 0.00 |
Annual Sum or Average | 404.03 | 882.84 | 560.20 | 15.54 | 544.66 | 0.00 | 0.00 |
Minimum of Months | 3.29 | 452.19 | 186.27 | 0.00 | 186.27 | 0.00 | 0.00 |
Maximum of Months | 944.00 | 1415.04 | 962.17 | 71.70 | 898.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 83.43 | 871.84 | 234.82 | 59.53 | 175.29 | 0.00 | 0.00 |
February | 285.06 | 768.50 | 430.87 | 152.92 | 277.95 | 0.00 | 0.00 |
March | 546.18 | 637.86 | 643.32 | 232.89 | 410.43 | 0.00 | 0.00 |
April | 1022.19 | 519.99 | 997.26 | 414.37 | 582.88 | 0.00 | 0.00 |
May | 1138.36 | 445.96 | 1061.17 | 368.94 | 692.23 | 0.00 | 0.00 |
June | 1460.15 | 356.38 | 1270.87 | 552.96 | 717.91 | 0.00 | 0.00 |
July | 1422.29 | 314.49 | 1183.48 | 531.21 | 652.27 | 0.00 | 0.00 |
August | 1444.60 | 310.61 | 1163.19 | 581.89 | 581.30 | 0.00 | 0.00 |
September | 945.41 | 448.12 | 860.01 | 396.64 | 463.37 | 0.00 | 0.00 |
October | 507.02 | 599.21 | 560.55 | 238.18 | 322.37 | 0.00 | 0.00 |
November | 143.54 | 739.69 | 274.75 | 77.56 | 197.19 | 0.00 | 0.00 |
December | 103.99 | 903.06 | 225.36 | 72.55 | 152.81 | 0.00 | 0.00 |
Annual Sum or Average | 760.94 | 575.39 | 743.51 | 307.31 | 436.19 | 0.00 | 0.00 |
Minimum of Months | 83.43 | 310.61 | 225.36 | 59.53 | 152.81 | 0.00 | 0.00 |
Maximum of Months | 1460.15 | 903.06 | 1270.87 | 581.89 | 717.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 875.01 | 1235.05 | 968.52 | 575.11 | 393.41 | 0.00 | 0.00 |
February | 1539.17 | 1133.47 | 1489.43 | 921.98 | 567.45 | 0.00 | 0.00 |
March | 1739.04 | 988.91 | 1602.20 | 854.43 | 747.76 | 0.00 | 0.00 |
April | 1946.39 | 833.01 | 1691.62 | 734.49 | 957.13 | 0.00 | 0.00 |
May | 1798.50 | 700.57 | 1546.77 | 460.80 | 1085.97 | 0.00 | 0.00 |
June | 1676.53 | 558.54 | 1415.14 | 379.95 | 1035.19 | 0.00 | 0.00 |
July | 2002.24 | 517.89 | 1543.27 | 565.23 | 978.04 | 0.00 | 0.00 |
August | 2219.41 | 507.38 | 1658.05 | 773.18 | 884.87 | 0.00 | 0.00 |
September | 2298.62 | 713.10 | 1837.05 | 1014.48 | 822.57 | 0.00 | 0.00 |
October | 1903.08 | 921.87 | 1664.06 | 1027.43 | 636.62 | 0.00 | 0.00 |
November | 948.78 | 1075.49 | 983.85 | 563.83 | 420.02 | 0.00 | 0.00 |
December | 1018.10 | 1297.88 | 1029.39 | 666.16 | 363.23 | 0.00 | 0.00 |
Annual Sum or Average | 1664.17 | 872.32 | 1451.82 | 710.11 | 741.71 | 0.00 | 0.00 |
Minimum of Months | 875.01 | 507.38 | 968.52 | 379.95 | 363.23 | 0.00 | 0.00 |
Maximum of Months | 2298.62 | 1297.88 | 1837.05 | 1027.43 | 1085.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 107.73 | 879.88 | 247.68 | 73.04 | 174.64 | 0.00 | 0.00 |
February | 320.34 | 781.99 | 444.07 | 166.89 | 277.17 | 0.00 | 0.00 |
March | 537.14 | 653.29 | 622.25 | 210.03 | 412.23 | 0.00 | 0.00 |
April | 975.91 | 544.12 | 946.69 | 361.95 | 584.74 | 0.00 | 0.00 |
May | 1359.78 | 472.50 | 1218.17 | 494.87 | 723.30 | 0.00 | 0.00 |
June | 1334.94 | 374.41 | 1171.55 | 454.87 | 716.68 | 0.00 | 0.00 |
July | 1803.27 | 351.27 | 1447.28 | 760.76 | 686.52 | 0.00 | 0.00 |
August | 1514.98 | 341.25 | 1197.25 | 611.35 | 585.90 | 0.00 | 0.00 |
September | 1129.78 | 477.11 | 974.98 | 467.81 | 507.16 | 0.00 | 0.00 |
October | 514.66 | 615.28 | 555.06 | 226.16 | 328.90 | 0.00 | 0.00 |
November | 153.40 | 742.89 | 276.42 | 77.96 | 198.45 | 0.00 | 0.00 |
December | 127.01 | 913.69 | 232.38 | 79.63 | 152.75 | 0.00 | 0.00 |
Annual Sum or Average | 826.55 | 594.78 | 779.85 | 333.37 | 446.47 | 0.00 | 0.00 |
Minimum of Months | 107.73 | 341.25 | 232.38 | 73.04 | 152.75 | 0.00 | 0.00 |
Maximum of Months | 1803.27 | 913.69 | 1447.28 | 760.76 | 723.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.14 | 1390.82 | 219.21 | 0.00 | 219.21 | 0.00 | 0.00 |
February | 65.92 | 1240.34 | 341.09 | 0.00 | 341.09 | 0.00 | 0.00 |
March | 207.56 | 1026.37 | 502.54 | 0.00 | 502.54 | 0.00 | 0.00 |
April | 456.58 | 827.56 | 711.15 | 2.52 | 708.63 | 0.00 | 0.00 |
May | 733.33 | 678.20 | 915.07 | 27.19 | 887.89 | 0.00 | 0.00 |
June | 852.42 | 525.67 | 962.18 | 63.54 | 898.64 | 0.00 | 0.00 |
July | 922.94 | 474.74 | 914.49 | 71.70 | 842.79 | 0.00 | 0.00 |
August | 761.56 | 465.92 | 740.29 | 20.01 | 720.28 | 0.00 | 0.00 |
September | 431.47 | 696.64 | 575.03 | 0.17 | 574.86 | 0.00 | 0.00 |
October | 171.02 | 920.19 | 393.99 | 0.00 | 393.99 | 0.00 | 0.00 |
November | 32.62 | 1138.38 | 248.18 | 0.00 | 248.18 | 0.00 | 0.00 |
December | 3.17 | 1409.90 | 186.27 | 0.00 | 186.27 | 0.00 | 0.00 |
Annual Sum or Average | 389.17 | 897.88 | 560.20 | 15.54 | 544.66 | 0.00 | 0.00 |
Minimum of Months | 3.17 | 465.92 | 186.27 | 0.00 | 186.27 | 0.00 | 0.00 |
Maximum of Months | 922.94 | 1409.90 | 962.18 | 71.70 | 898.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 81.26 | 878.44 | 234.82 | 59.53 | 175.29 | 0.00 | 0.00 |
February | 277.94 | 776.69 | 430.87 | 152.93 | 277.95 | 0.00 | 0.00 |
March | 532.57 | 649.40 | 643.33 | 232.89 | 410.44 | 0.00 | 0.00 |
April | 1005.53 | 526.92 | 997.26 | 414.38 | 582.89 | 0.00 | 0.00 |
May | 1122.80 | 450.93 | 1061.18 | 368.95 | 692.23 | 0.00 | 0.00 |
June | 1447.79 | 355.60 | 1270.88 | 552.97 | 717.91 | 0.00 | 0.00 |
July | 1411.19 | 315.06 | 1183.49 | 531.22 | 652.27 | 0.00 | 0.00 |
August | 1436.48 | 307.74 | 1163.20 | 581.90 | 581.30 | 0.00 | 0.00 |
September | 940.17 | 442.54 | 860.02 | 396.65 | 463.37 | 0.00 | 0.00 |
October | 505.25 | 584.65 | 560.56 | 238.18 | 322.37 | 0.00 | 0.00 |
November | 143.41 | 726.11 | 274.75 | 77.57 | 197.19 | 0.00 | 0.00 |
December | 102.98 | 898.62 | 225.36 | 72.55 | 152.81 | 0.00 | 0.00 |
Annual Sum or Average | 753.04 | 575.10 | 743.51 | 307.32 | 436.20 | 0.00 | 0.00 |
Minimum of Months | 81.26 | 307.74 | 225.36 | 59.53 | 152.81 | 0.00 | 0.00 |
Maximum of Months | 1447.79 | 898.62 | 1270.88 | 581.90 | 717.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 853.10 | 1257.62 | 968.51 | 575.10 | 393.40 | 0.00 | 0.00 |
February | 1504.27 | 1147.46 | 1489.41 | 921.97 | 567.45 | 0.00 | 0.00 |
March | 1694.99 | 1011.79 | 1602.18 | 854.42 | 747.76 | 0.00 | 0.00 |
April | 1895.87 | 863.75 | 1691.60 | 734.48 | 957.12 | 0.00 | 0.00 |
May | 1747.77 | 730.41 | 1546.75 | 460.79 | 1085.96 | 0.00 | 0.00 |
June | 1633.14 | 581.30 | 1415.13 | 379.94 | 1035.19 | 0.00 | 0.00 |
July | 1974.00 | 527.62 | 1543.26 | 565.22 | 978.04 | 0.00 | 0.00 |
August | 2196.52 | 509.70 | 1658.04 | 773.17 | 884.87 | 0.00 | 0.00 |
September | 2276.98 | 706.85 | 1837.03 | 1014.47 | 822.56 | 0.00 | 0.00 |
October | 1880.88 | 905.33 | 1664.04 | 1027.42 | 636.62 | 0.00 | 0.00 |
November | 930.94 | 1071.82 | 983.84 | 563.82 | 420.02 | 0.00 | 0.00 |
December | 1000.96 | 1307.87 | 1029.37 | 666.15 | 363.23 | 0.00 | 0.00 |
Annual Sum or Average | 1632.94 | 883.84 | 1451.80 | 710.10 | 741.70 | 0.00 | 0.00 |
Minimum of Months | 853.10 | 509.70 | 968.51 | 379.94 | 363.23 | 0.00 | 0.00 |
Maximum of Months | 2276.98 | 1307.87 | 1837.03 | 1027.42 | 1085.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 104.50 | 885.68 | 247.68 | 73.04 | 174.64 | 0.00 | 0.00 |
February | 311.61 | 790.07 | 444.07 | 166.89 | 277.18 | 0.00 | 0.00 |
March | 521.80 | 667.12 | 622.26 | 210.03 | 412.23 | 0.00 | 0.00 |
April | 955.04 | 557.30 | 946.70 | 361.96 | 584.74 | 0.00 | 0.00 |
May | 1341.82 | 476.61 | 1218.18 | 494.88 | 723.30 | 0.00 | 0.00 |
June | 1319.76 | 377.77 | 1171.55 | 454.87 | 716.68 | 0.00 | 0.00 |
July | 1792.38 | 348.05 | 1447.29 | 760.77 | 686.52 | 0.00 | 0.00 |
August | 1505.93 | 338.21 | 1197.26 | 611.35 | 585.91 | 0.00 | 0.00 |
September | 1124.04 | 470.13 | 974.98 | 467.82 | 507.17 | 0.00 | 0.00 |
October | 511.38 | 604.15 | 555.06 | 226.16 | 328.90 | 0.00 | 0.00 |
November | 152.11 | 730.96 | 276.42 | 77.96 | 198.46 | 0.00 | 0.00 |
December | 125.18 | 908.73 | 232.38 | 79.63 | 152.75 | 0.00 | 0.00 |
Annual Sum or Average | 817.11 | 595.32 | 779.85 | 333.38 | 446.48 | 0.00 | 0.00 |
Minimum of Months | 104.50 | 338.21 | 232.38 | 73.04 | 152.75 | 0.00 | 0.00 |
Maximum of Months | 1792.38 | 908.73 | 1447.29 | 760.77 | 723.30 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 25602144.86 | 0.351527E+10 | 0.587122E+09 | 0.00 | 0.587122E+09 | 0.00 | 0.00 |
February | 0.180336E+09 | 0.280191E+10 | 0.825167E+09 | 0.00 | 0.825167E+09 | 0.00 | 0.00 |
March | 0.600056E+09 | 0.255000E+10 | 0.134601E+10 | 0.00 | 0.134601E+10 | 0.00 | 0.00 |
April | 0.122936E+10 | 0.200367E+10 | 0.184330E+10 | 6538753.27 | 0.183676E+10 | 0.00 | 0.00 |
May | 0.200448E+10 | 0.171231E+10 | 0.245093E+10 | 72813512.30 | 0.237811E+10 | 0.00 | 0.00 |
June | 0.223266E+10 | 0.129856E+10 | 0.249396E+10 | 0.164691E+09 | 0.232927E+10 | 0.00 | 0.00 |
July | 0.248522E+10 | 0.121687E+10 | 0.244938E+10 | 0.192043E+09 | 0.225734E+10 | 0.00 | 0.00 |
August | 0.205544E+10 | 0.118950E+10 | 0.198279E+10 | 53600856.92 | 0.192919E+10 | 0.00 | 0.00 |
September | 0.115269E+10 | 0.168512E+10 | 0.149048E+10 | 439520.07 | 0.149004E+10 | 0.00 | 0.00 |
October | 0.508356E+09 | 0.225249E+10 | 0.105527E+10 | 0.00 | 0.105527E+10 | 0.00 | 0.00 |
November | 0.105521E+09 | 0.270882E+10 | 0.643273E+09 | 0.00 | 0.643273E+09 | 0.00 | 0.00 |
December | 14489534.85 | 0.352064E+10 | 0.498902E+09 | 0.00 | 0.498902E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.125942E+11 | 0.264551E+11 | 0.176666E+11 | 0.490126E+09 | 0.171765E+11 | 0.00 | 0.00 |
Minimum of Months | 14489534.85 | 0.118950E+10 | 0.498902E+09 | 0.00 | 0.498902E+09 | 0.00 | 0.00 |
Maximum of Months | 0.248522E+10 | 0.352064E+10 | 0.249396E+10 | 0.192043E+09 | 0.237811E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.230067E+09 | 0.222182E+10 | 0.628946E+09 | 0.159458E+09 | 0.469487E+09 | 0.00 | 0.00 |
February | 0.698130E+09 | 0.175956E+10 | 0.104237E+10 | 0.369959E+09 | 0.672413E+09 | 0.00 | 0.00 |
March | 0.145902E+10 | 0.162313E+10 | 0.172308E+10 | 0.623769E+09 | 0.109931E+10 | 0.00 | 0.00 |
April | 0.263492E+10 | 0.128646E+10 | 0.258491E+10 | 0.107407E+10 | 0.151085E+10 | 0.00 | 0.00 |
May | 0.302778E+10 | 0.114594E+10 | 0.284226E+10 | 0.988186E+09 | 0.185408E+10 | 0.00 | 0.00 |
June | 0.376004E+10 | 0.882726E+09 | 0.329412E+10 | 0.143329E+10 | 0.186083E+10 | 0.00 | 0.00 |
July | 0.378529E+10 | 0.812201E+09 | 0.316985E+10 | 0.142281E+10 | 0.174704E+10 | 0.00 | 0.00 |
August | 0.385263E+10 | 0.791193E+09 | 0.311552E+10 | 0.155856E+10 | 0.155696E+10 | 0.00 | 0.00 |
September | 0.245736E+10 | 0.107912E+10 | 0.222916E+10 | 0.102811E+10 | 0.120106E+10 | 0.00 | 0.00 |
October | 0.138815E+10 | 0.144539E+10 | 0.150140E+10 | 0.637951E+09 | 0.863446E+09 | 0.00 | 0.00 |
November | 0.393766E+09 | 0.173730E+10 | 0.712163E+09 | 0.201050E+09 | 0.511113E+09 | 0.00 | 0.00 |
December | 0.290944E+09 | 0.224872E+10 | 0.603605E+09 | 0.194318E+09 | 0.409287E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239781E+11 | 0.170336E+11 | 0.234474E+11 | 0.969152E+10 | 0.137559E+11 | 0.00 | 0.00 |
Minimum of Months | 0.230067E+09 | 0.791193E+09 | 0.603605E+09 | 0.159458E+09 | 0.409287E+09 | 0.00 | 0.00 |
Maximum of Months | 0.385263E+10 | 0.224872E+10 | 0.329412E+10 | 0.155856E+10 | 0.186083E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.232221E+10 | 0.317525E+10 | 0.259405E+10 | 0.154036E+10 | 0.105369E+10 | 0.00 | 0.00 |
February | 0.368577E+10 | 0.259954E+10 | 0.360319E+10 | 0.223042E+10 | 0.137277E+10 | 0.00 | 0.00 |
March | 0.458198E+10 | 0.252272E+10 | 0.429128E+10 | 0.228849E+10 | 0.200279E+10 | 0.00 | 0.00 |
April | 0.494964E+10 | 0.210300E+10 | 0.438463E+10 | 0.190378E+10 | 0.248085E+10 | 0.00 | 0.00 |
May | 0.470698E+10 | 0.184526E+10 | 0.414282E+10 | 0.123418E+10 | 0.290864E+10 | 0.00 | 0.00 |
June | 0.424459E+10 | 0.143166E+10 | 0.366801E+10 | 0.984811E+09 | 0.268320E+10 | 0.00 | 0.00 |
July | 0.529194E+10 | 0.135082E+10 | 0.413346E+10 | 0.151389E+10 | 0.261958E+10 | 0.00 | 0.00 |
August | 0.588807E+10 | 0.130212E+10 | 0.444088E+10 | 0.207085E+10 | 0.237003E+10 | 0.00 | 0.00 |
September | 0.592998E+10 | 0.172046E+10 | 0.476159E+10 | 0.262950E+10 | 0.213209E+10 | 0.00 | 0.00 |
October | 0.508730E+10 | 0.223652E+10 | 0.445697E+10 | 0.275184E+10 | 0.170512E+10 | 0.00 | 0.00 |
November | 0.246189E+10 | 0.256446E+10 | 0.255010E+10 | 0.146142E+10 | 0.108868E+10 | 0.00 | 0.00 |
December | 0.272011E+10 | 0.327177E+10 | 0.275707E+10 | 0.178421E+10 | 0.972864E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.518705E+11 | 0.261236E+11 | 0.457841E+11 | 0.223938E+11 | 0.233903E+11 | 0.00 | 0.00 |
Minimum of Months | 0.232221E+10 | 0.130212E+10 | 0.255010E+10 | 0.984811E+09 | 0.972864E+09 | 0.00 | 0.00 |
Maximum of Months | 0.592998E+10 | 0.327177E+10 | 0.476159E+10 | 0.275184E+10 | 0.290864E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.289445E+09 | 0.223924E+10 | 0.663386E+09 | 0.195620E+09 | 0.467766E+09 | 0.00 | 0.00 |
February | 0.773374E+09 | 0.178827E+10 | 0.107430E+10 | 0.403750E+09 | 0.670546E+09 | 0.00 | 0.00 |
March | 0.142488E+10 | 0.166333E+10 | 0.166665E+10 | 0.562538E+09 | 0.110411E+10 | 0.00 | 0.00 |
April | 0.250189E+10 | 0.135447E+10 | 0.245384E+10 | 0.938194E+09 | 0.151564E+10 | 0.00 | 0.00 |
May | 0.361421E+10 | 0.120386E+10 | 0.326277E+10 | 0.132548E+10 | 0.193729E+10 | 0.00 | 0.00 |
June | 0.343085E+10 | 0.930225E+09 | 0.303667E+10 | 0.117903E+10 | 0.185763E+10 | 0.00 | 0.00 |
July | 0.480400E+10 | 0.891743E+09 | 0.387643E+10 | 0.203765E+10 | 0.183879E+10 | 0.00 | 0.00 |
August | 0.403995E+10 | 0.864092E+09 | 0.320674E+10 | 0.163745E+10 | 0.156929E+10 | 0.00 | 0.00 |
September | 0.293550E+10 | 0.114198E+10 | 0.252716E+10 | 0.121258E+10 | 0.131458E+10 | 0.00 | 0.00 |
October | 0.140230E+10 | 0.148782E+10 | 0.148668E+10 | 0.605749E+09 | 0.880929E+09 | 0.00 | 0.00 |
November | 0.413686E+09 | 0.174744E+10 | 0.716474E+09 | 0.202075E+09 | 0.514399E+09 | 0.00 | 0.00 |
December | 0.345509E+09 | 0.227238E+10 | 0.622413E+09 | 0.213285E+09 | 0.409128E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.259756E+11 | 0.175849E+11 | 0.245935E+11 | 0.105134E+11 | 0.140801E+11 | 0.00 | 0.00 |
Minimum of Months | 0.289445E+09 | 0.864092E+09 | 0.622413E+09 | 0.195620E+09 | 0.409128E+09 | 0.00 | 0.00 |
Maximum of Months | 0.480400E+10 | 0.227238E+10 | 0.387643E+10 | 0.203765E+10 | 0.193729E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 21676380.13 | 0.369630E+10 | 0.587119E+09 | 0.00 | 0.587119E+09 | 0.00 | 0.00 |
February | 0.174984E+09 | 0.294734E+10 | 0.825163E+09 | 0.00 | 0.825163E+09 | 0.00 | 0.00 |
March | 0.610249E+09 | 0.264690E+10 | 0.134601E+10 | 0.00 | 0.134601E+10 | 0.00 | 0.00 |
April | 0.127065E+10 | 0.203760E+10 | 0.184329E+10 | 6538719.38 | 0.183675E+10 | 0.00 | 0.00 |
May | 0.205311E+10 | 0.174194E+10 | 0.245092E+10 | 72813134.99 | 0.237810E+10 | 0.00 | 0.00 |
June | 0.228057E+10 | 0.131405E+10 | 0.249395E+10 | 0.164690E+09 | 0.232926E+10 | 0.00 | 0.00 |
July | 0.252842E+10 | 0.123027E+10 | 0.244937E+10 | 0.192042E+09 | 0.225733E+10 | 0.00 | 0.00 |
August | 0.208340E+10 | 0.121116E+10 | 0.198278E+10 | 53600579.17 | 0.192918E+10 | 0.00 | 0.00 |
September | 0.115138E+10 | 0.177168E+10 | 0.149047E+10 | 439517.79 | 0.149003E+10 | 0.00 | 0.00 |
October | 0.472087E+09 | 0.246577E+10 | 0.105526E+10 | 0.00 | 0.105526E+10 | 0.00 | 0.00 |
November | 86010171.97 | 0.298833E+10 | 0.643269E+09 | 0.00 | 0.643269E+09 | 0.00 | 0.00 |
December | 8817423.97 | 0.379005E+10 | 0.498900E+09 | 0.00 | 0.498900E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127413E+11 | 0.278414E+11 | 0.176665E+11 | 0.490124E+09 | 0.171764E+11 | 0.00 | 0.00 |
Minimum of Months | 8817423.97 | 0.121116E+10 | 0.498900E+09 | 0.00 | 0.498900E+09 | 0.00 | 0.00 |
Maximum of Months | 0.252842E+10 | 0.379005E+10 | 0.249395E+10 | 0.192042E+09 | 0.237810E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.223466E+09 | 0.233514E+10 | 0.628941E+09 | 0.159457E+09 | 0.469484E+09 | 0.00 | 0.00 |
February | 0.689612E+09 | 0.185915E+10 | 0.104236E+10 | 0.369955E+09 | 0.672408E+09 | 0.00 | 0.00 |
March | 0.146289E+10 | 0.170844E+10 | 0.172307E+10 | 0.623763E+09 | 0.109931E+10 | 0.00 | 0.00 |
April | 0.264951E+10 | 0.134780E+10 | 0.258489E+10 | 0.107405E+10 | 0.151084E+10 | 0.00 | 0.00 |
May | 0.304899E+10 | 0.119445E+10 | 0.284224E+10 | 0.988177E+09 | 0.185406E+10 | 0.00 | 0.00 |
June | 0.378471E+10 | 0.923750E+09 | 0.329410E+10 | 0.143328E+10 | 0.186082E+10 | 0.00 | 0.00 |
July | 0.380946E+10 | 0.842319E+09 | 0.316983E+10 | 0.142279E+10 | 0.174703E+10 | 0.00 | 0.00 |
August | 0.386921E+10 | 0.831929E+09 | 0.311549E+10 | 0.155854E+10 | 0.155695E+10 | 0.00 | 0.00 |
September | 0.245051E+10 | 0.116153E+10 | 0.222915E+10 | 0.102810E+10 | 0.120105E+10 | 0.00 | 0.00 |
October | 0.135800E+10 | 0.160494E+10 | 0.150139E+10 | 0.637945E+09 | 0.863441E+09 | 0.00 | 0.00 |
November | 0.372061E+09 | 0.191728E+10 | 0.712158E+09 | 0.201048E+09 | 0.511109E+09 | 0.00 | 0.00 |
December | 0.278515E+09 | 0.241876E+10 | 0.603600E+09 | 0.194316E+09 | 0.409284E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239969E+11 | 0.181455E+11 | 0.234472E+11 | 0.969142E+10 | 0.137558E+11 | 0.00 | 0.00 |
Minimum of Months | 0.223466E+09 | 0.831929E+09 | 0.603600E+09 | 0.159457E+09 | 0.409284E+09 | 0.00 | 0.00 |
Maximum of Months | 0.386921E+10 | 0.241876E+10 | 0.329410E+10 | 0.155854E+10 | 0.186082E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.234362E+10 | 0.330795E+10 | 0.259408E+10 | 0.154037E+10 | 0.105370E+10 | 0.00 | 0.00 |
February | 0.372356E+10 | 0.274209E+10 | 0.360323E+10 | 0.223045E+10 | 0.137278E+10 | 0.00 | 0.00 |
March | 0.465785E+10 | 0.264869E+10 | 0.429132E+10 | 0.228852E+10 | 0.200281E+10 | 0.00 | 0.00 |
April | 0.504503E+10 | 0.215916E+10 | 0.438467E+10 | 0.190380E+10 | 0.248087E+10 | 0.00 | 0.00 |
May | 0.481709E+10 | 0.187641E+10 | 0.414286E+10 | 0.123420E+10 | 0.290866E+10 | 0.00 | 0.00 |
June | 0.434555E+10 | 0.144774E+10 | 0.366804E+10 | 0.984823E+09 | 0.268322E+10 | 0.00 | 0.00 |
July | 0.536281E+10 | 0.138712E+10 | 0.413350E+10 | 0.151391E+10 | 0.261959E+10 | 0.00 | 0.00 |
August | 0.594448E+10 | 0.135897E+10 | 0.444092E+10 | 0.207088E+10 | 0.237005E+10 | 0.00 | 0.00 |
September | 0.595801E+10 | 0.184835E+10 | 0.476164E+10 | 0.262953E+10 | 0.213210E+10 | 0.00 | 0.00 |
October | 0.509722E+10 | 0.246914E+10 | 0.445701E+10 | 0.275188E+10 | 0.170514E+10 | 0.00 | 0.00 |
November | 0.245923E+10 | 0.278768E+10 | 0.255013E+10 | 0.146144E+10 | 0.108869E+10 | 0.00 | 0.00 |
December | 0.272688E+10 | 0.347623E+10 | 0.275710E+10 | 0.178423E+10 | 0.972873E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.524813E+11 | 0.275095E+11 | 0.457845E+11 | 0.223940E+11 | 0.233905E+11 | 0.00 | 0.00 |
Minimum of Months | 0.234362E+10 | 0.135897E+10 | 0.255013E+10 | 0.984823E+09 | 0.972873E+09 | 0.00 | 0.00 |
Maximum of Months | 0.595801E+10 | 0.347623E+10 | 0.476164E+10 | 0.275188E+10 | 0.290866E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.288542E+09 | 0.235667E+10 | 0.663381E+09 | 0.195618E+09 | 0.467763E+09 | 0.00 | 0.00 |
February | 0.774955E+09 | 0.189178E+10 | 0.107429E+10 | 0.403746E+09 | 0.670542E+09 | 0.00 | 0.00 |
March | 0.143867E+10 | 0.174977E+10 | 0.166664E+10 | 0.562533E+09 | 0.110411E+10 | 0.00 | 0.00 |
April | 0.252956E+10 | 0.141035E+10 | 0.245382E+10 | 0.938185E+09 | 0.151563E+10 | 0.00 | 0.00 |
May | 0.364204E+10 | 0.126554E+10 | 0.326274E+10 | 0.132547E+10 | 0.193727E+10 | 0.00 | 0.00 |
June | 0.346016E+10 | 0.970477E+09 | 0.303664E+10 | 0.117902E+10 | 0.185762E+10 | 0.00 | 0.00 |
July | 0.482987E+10 | 0.940844E+09 | 0.387640E+10 | 0.203763E+10 | 0.183878E+10 | 0.00 | 0.00 |
August | 0.405773E+10 | 0.913993E+09 | 0.320671E+10 | 0.163743E+10 | 0.156928E+10 | 0.00 | 0.00 |
September | 0.292838E+10 | 0.123668E+10 | 0.252714E+10 | 0.121257E+10 | 0.131457E+10 | 0.00 | 0.00 |
October | 0.137847E+10 | 0.164796E+10 | 0.148667E+10 | 0.605743E+09 | 0.880923E+09 | 0.00 | 0.00 |
November | 0.397621E+09 | 0.192557E+10 | 0.716468E+09 | 0.202073E+09 | 0.514395E+09 | 0.00 | 0.00 |
December | 0.340189E+09 | 0.244722E+10 | 0.622408E+09 | 0.213282E+09 | 0.409125E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.260662E+11 | 0.187568E+11 | 0.245933E+11 | 0.105133E+11 | 0.140800E+11 | 0.00 | 0.00 |
Minimum of Months | 0.288542E+09 | 0.913993E+09 | 0.622408E+09 | 0.195618E+09 | 0.409125E+09 | 0.00 | 0.00 |
Maximum of Months | 0.482987E+10 | 0.244722E+10 | 0.387640E+10 | 0.203763E+10 | 0.193727E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 19123361.13 | 0.372519E+10 | 0.587122E+09 | 0.00 | 0.587122E+09 | 0.00 | 0.00 |
February | 0.159462E+09 | 0.300062E+10 | 0.825167E+09 | 0.00 | 0.825167E+09 | 0.00 | 0.00 |
March | 0.555933E+09 | 0.274902E+10 | 0.134601E+10 | 0.00 | 0.134601E+10 | 0.00 | 0.00 |
April | 0.118344E+10 | 0.214503E+10 | 0.184330E+10 | 6538753.27 | 0.183676E+10 | 0.00 | 0.00 |
May | 0.196414E+10 | 0.181650E+10 | 0.245093E+10 | 72813512.30 | 0.237811E+10 | 0.00 | 0.00 |
June | 0.220948E+10 | 0.136253E+10 | 0.249396E+10 | 0.164691E+09 | 0.232927E+10 | 0.00 | 0.00 |
July | 0.247201E+10 | 0.127154E+10 | 0.244938E+10 | 0.192043E+09 | 0.225734E+10 | 0.00 | 0.00 |
August | 0.203976E+10 | 0.124793E+10 | 0.198279E+10 | 53600856.92 | 0.192919E+10 | 0.00 | 0.00 |
September | 0.111836E+10 | 0.180569E+10 | 0.149048E+10 | 439520.07 | 0.149004E+10 | 0.00 | 0.00 |
October | 0.458060E+09 | 0.246464E+10 | 0.105527E+10 | 0.00 | 0.105527E+10 | 0.00 | 0.00 |
November | 84561618.71 | 0.295069E+10 | 0.643273E+09 | 0.00 | 0.643273E+09 | 0.00 | 0.00 |
December | 8499574.58 | 0.377627E+10 | 0.498902E+09 | 0.00 | 0.498902E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.122728E+11 | 0.283156E+11 | 0.176666E+11 | 0.490126E+09 | 0.171765E+11 | 0.00 | 0.00 |
Minimum of Months | 8499574.58 | 0.124793E+10 | 0.498902E+09 | 0.00 | 0.498902E+09 | 0.00 | 0.00 |
Maximum of Months | 0.247201E+10 | 0.377627E+10 | 0.249396E+10 | 0.192043E+09 | 0.237811E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.217655E+09 | 0.235280E+10 | 0.628946E+09 | 0.159458E+09 | 0.469487E+09 | 0.00 | 0.00 |
February | 0.672383E+09 | 0.187896E+10 | 0.104237E+10 | 0.369959E+09 | 0.672413E+09 | 0.00 | 0.00 |
March | 0.142644E+10 | 0.173934E+10 | 0.172308E+10 | 0.623769E+09 | 0.109931E+10 | 0.00 | 0.00 |
April | 0.260632E+10 | 0.136578E+10 | 0.258491E+10 | 0.107407E+10 | 0.151085E+10 | 0.00 | 0.00 |
May | 0.300730E+10 | 0.120777E+10 | 0.284226E+10 | 0.988186E+09 | 0.185408E+10 | 0.00 | 0.00 |
June | 0.375267E+10 | 0.921727E+09 | 0.329412E+10 | 0.143329E+10 | 0.186083E+10 | 0.00 | 0.00 |
July | 0.377974E+10 | 0.843849E+09 | 0.316985E+10 | 0.142281E+10 | 0.174704E+10 | 0.00 | 0.00 |
August | 0.384748E+10 | 0.824253E+09 | 0.311552E+10 | 0.155856E+10 | 0.155696E+10 | 0.00 | 0.00 |
September | 0.243692E+10 | 0.114707E+10 | 0.222916E+10 | 0.102811E+10 | 0.120106E+10 | 0.00 | 0.00 |
October | 0.135326E+10 | 0.156593E+10 | 0.150140E+10 | 0.637951E+09 | 0.863446E+09 | 0.00 | 0.00 |
November | 0.371724E+09 | 0.188209E+10 | 0.712163E+09 | 0.201050E+09 | 0.511113E+09 | 0.00 | 0.00 |
December | 0.275833E+09 | 0.240685E+10 | 0.603605E+09 | 0.194318E+09 | 0.409287E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.237477E+11 | 0.181364E+11 | 0.234474E+11 | 0.969152E+10 | 0.137559E+11 | 0.00 | 0.00 |
Minimum of Months | 0.217655E+09 | 0.824253E+09 | 0.603605E+09 | 0.159458E+09 | 0.409287E+09 | 0.00 | 0.00 |
Maximum of Months | 0.384748E+10 | 0.240685E+10 | 0.329412E+10 | 0.155856E+10 | 0.186083E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.228494E+10 | 0.336842E+10 | 0.259405E+10 | 0.154036E+10 | 0.105369E+10 | 0.00 | 0.00 |
February | 0.363912E+10 | 0.277593E+10 | 0.360319E+10 | 0.223042E+10 | 0.137277E+10 | 0.00 | 0.00 |
March | 0.453986E+10 | 0.270997E+10 | 0.429128E+10 | 0.228849E+10 | 0.200279E+10 | 0.00 | 0.00 |
April | 0.491411E+10 | 0.223884E+10 | 0.438463E+10 | 0.190378E+10 | 0.248085E+10 | 0.00 | 0.00 |
May | 0.468123E+10 | 0.195632E+10 | 0.414282E+10 | 0.123418E+10 | 0.290864E+10 | 0.00 | 0.00 |
June | 0.423311E+10 | 0.150672E+10 | 0.366801E+10 | 0.984811E+09 | 0.268320E+10 | 0.00 | 0.00 |
July | 0.528717E+10 | 0.141319E+10 | 0.413346E+10 | 0.151389E+10 | 0.261958E+10 | 0.00 | 0.00 |
August | 0.588315E+10 | 0.136518E+10 | 0.444088E+10 | 0.207085E+10 | 0.237003E+10 | 0.00 | 0.00 |
September | 0.590193E+10 | 0.183215E+10 | 0.476159E+10 | 0.262950E+10 | 0.213209E+10 | 0.00 | 0.00 |
October | 0.503775E+10 | 0.242484E+10 | 0.445697E+10 | 0.275184E+10 | 0.170512E+10 | 0.00 | 0.00 |
November | 0.241300E+10 | 0.277815E+10 | 0.255010E+10 | 0.146142E+10 | 0.108868E+10 | 0.00 | 0.00 |
December | 0.268098E+10 | 0.350299E+10 | 0.275707E+10 | 0.178421E+10 | 0.972864E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.514963E+11 | 0.278727E+11 | 0.457841E+11 | 0.223938E+11 | 0.233903E+11 | 0.00 | 0.00 |
Minimum of Months | 0.228494E+10 | 0.136518E+10 | 0.255010E+10 | 0.984811E+09 | 0.972864E+09 | 0.00 | 0.00 |
Maximum of Months | 0.590193E+10 | 0.350299E+10 | 0.476159E+10 | 0.275184E+10 | 0.290864E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.279900E+09 | 0.237221E+10 | 0.663386E+09 | 0.195620E+09 | 0.467766E+09 | 0.00 | 0.00 |
February | 0.753840E+09 | 0.191134E+10 | 0.107430E+10 | 0.403750E+09 | 0.670546E+09 | 0.00 | 0.00 |
March | 0.139760E+10 | 0.178682E+10 | 0.166665E+10 | 0.562538E+09 | 0.110411E+10 | 0.00 | 0.00 |
April | 0.247546E+10 | 0.144453E+10 | 0.245384E+10 | 0.938194E+09 | 0.151564E+10 | 0.00 | 0.00 |
May | 0.359394E+10 | 0.127656E+10 | 0.326277E+10 | 0.132548E+10 | 0.193729E+10 | 0.00 | 0.00 |
June | 0.342083E+10 | 0.979175E+09 | 0.303667E+10 | 0.117903E+10 | 0.185763E+10 | 0.00 | 0.00 |
July | 0.480070E+10 | 0.932214E+09 | 0.387643E+10 | 0.203765E+10 | 0.183879E+10 | 0.00 | 0.00 |
August | 0.403349E+10 | 0.905858E+09 | 0.320674E+10 | 0.163745E+10 | 0.156929E+10 | 0.00 | 0.00 |
September | 0.291351E+10 | 0.121858E+10 | 0.252716E+10 | 0.121258E+10 | 0.131458E+10 | 0.00 | 0.00 |
October | 0.136968E+10 | 0.161815E+10 | 0.148668E+10 | 0.605749E+09 | 0.880929E+09 | 0.00 | 0.00 |
November | 0.394269E+09 | 0.189466E+10 | 0.716474E+09 | 0.202075E+09 | 0.514399E+09 | 0.00 | 0.00 |
December | 0.335271E+09 | 0.243395E+10 | 0.622413E+09 | 0.213285E+09 | 0.409128E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.257685E+11 | 0.187740E+11 | 0.245935E+11 | 0.105134E+11 | 0.140801E+11 | 0.00 | 0.00 |
Minimum of Months | 0.279900E+09 | 0.905858E+09 | 0.622413E+09 | 0.195620E+09 | 0.409128E+09 | 0.00 | 0.00 |
Maximum of Months | 0.480070E+10 | 0.243395E+10 | 0.387643E+10 | 0.203765E+10 | 0.193729E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.522478E+10 | -0.449082E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -733955195.2 | 58.98 | 0.00 | 0.00 |
February | 0.475816E+10 | -0.410984E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -648322997.3 | 58.98 | 0.00 | 0.00 |
March | 0.551558E+10 | -0.481004E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -705535977.6 | 58.99 | 0.00 | 0.00 |
April | 0.488424E+10 | -0.420947E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -674769995.7 | 58.98 | 0.00 | 0.00 |
May | 0.504032E+10 | -0.434739E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692930370.9 | 58.98 | 0.00 | 0.00 |
June | 0.482449E+10 | -0.415598E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668515430.8 | 58.98 | 0.00 | 0.00 |
July | 0.449477E+10 | -0.380656E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688215073.3 | 58.98 | 0.00 | 0.00 |
August | 0.486411E+10 | -0.417398E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690132642.0 | 58.98 | 0.00 | 0.00 |
September | 0.447609E+10 | -0.380878E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667308388.9 | 58.98 | 0.00 | 0.00 |
October | 0.475529E+10 | -0.405895E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -696339059.4 | 58.98 | 0.00 | 0.00 |
November | 0.483729E+10 | -0.415179E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -685504159.9 | 58.98 | 0.00 | 0.00 |
December | 0.497984E+10 | -0.426009E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -719752950.8 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.586550E+11 | -0.503837E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.827128E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.447609E+10 | -0.481004E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -733955195.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.551558E+10 | -0.380656E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -648322997.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.64 | 0.62 | 01-JAN-09:20 | 2392.79 | 30.51 | 207.17 | 211.33 | 1944.84 | 33.24 | 224.67 | 176.33 |
February | 259.50 | 0.63 | 0.62 | 01-FEB-08:20 | 4140.24 | 32.03 | 231.83 | 237.17 | 1813.01 | 28.99 | 208.67 | 212.50 |
March | 247.00 | 0.63 | 0.62 | 01-MAR-07:30 | 6912.01 | 32.38 | 207.83 | 304.50 | 1449.11 | 21.17 | 130.33 | 256.50 |
April | 379.50 | 0.64 | 0.62 | 01-APR-06:49 | 1877.35 | 17.39 | 0.00 | 337.67 | 1040.91 | 20.18 | 174.67 | 294.33 |
May | 427.83 | 0.64 | 0.62 | 01-MAY-06:49 | 1716.13 | 17.26 | 0.00 | 376.33 | 935.48 | 20.00 | 161.50 | 328.67 |
June | 375.17 | 0.64 | 0.62 | 01-JUN-05:40 | 1492.42 | 16.84 | 0.00 | 383.50 | 856.90 | 19.60 | 118.67 | 328.17 |
July | 471.00 | 0.66 | 0.62 | 01-JUL-05:10 | 1329.76 | 15.59 | 0.00 | 379.67 | 778.65 | 18.36 | 116.67 | 316.33 |
August | 366.67 | 0.64 | 0.62 | 01-AUG-05:49 | 1579.92 | 16.66 | 0.00 | 361.00 | 946.73 | 19.46 | 115.67 | 311.33 |
September | 301.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2582.33 | 19.61 | 27.00 | 311.83 | 1262.37 | 20.99 | 143.33 | 274.00 |
October | 245.33 | 0.64 | 0.62 | 01-OCT-07:40 | 6407.52 | 33.77 | 218.17 | 279.00 | 1705.13 | 22.39 | 129.17 | 248.67 |
November | 242.67 | 0.64 | 0.62 | 01-NOV-07:49 | 2683.40 | 30.42 | 213.17 | 217.67 | 2186.59 | 32.86 | 229.00 | 183.17 |
December | 160.33 | 0.64 | 0.62 | 01-DEC-09:39 | 3160.52 | 32.50 | 131.00 | 199.33 | 2790.23 | 36.59 | 149.67 | 151.33 |
Annual Sum or Average | 3714.00 | 0.64 | 2711.51 | 22.65 | 1236.17 | 3599.00 | 1318.81 | 23.06 | 1902.00 | 3081.33 | ||
Minimum of Months | 160.33 | 0.63 | 0.62 | 1329.76 | 15.59 | 0.00 | 199.33 | 778.65 | 18.36 | 115.67 | 151.33 | |
Maximum of Months | 471.00 | 0.66 | 0.62 | 6912.01 | 33.77 | 231.83 | 383.50 | 2790.23 | 36.59 | 229.00 | 328.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.65 | 0.62 | 01-JAN-09:20 | 751.92 | 15.92 | 42.83 | 187.33 | 493.76 | 20.47 | 69.17 | 107.50 |
February | 259.50 | 0.64 | 0.62 | 01-FEB-08:20 | 1276.45 | 18.52 | 66.50 | 218.00 | 682.61 | 21.17 | 67.00 | 160.83 |
March | 247.00 | 0.64 | 0.62 | 01-MAR-07:30 | 2329.63 | 20.99 | 79.00 | 291.00 | 997.28 | 20.98 | 50.67 | 230.00 |
April | 379.50 | 0.64 | 0.62 | 01-APR-06:10 | 2446.85 | 20.04 | 105.17 | 337.17 | 1360.44 | 21.60 | 78.33 | 290.00 |
May | 427.83 | 0.64 | 0.62 | 01-MAY-06:49 | 2529.51 | 20.00 | 131.67 | 380.67 | 1090.87 | 20.71 | 76.67 | 333.33 |
June | 375.17 | 0.64 | 0.62 | 01-JUN-04:00 | 2645.22 | 19.18 | 89.00 | 391.67 | 1460.71 | 21.65 | 73.67 | 339.17 |
July | 471.00 | 0.65 | 0.62 | 01-JUL-04:49 | 2499.84 | 19.53 | 146.50 | 393.67 | 1121.55 | 20.18 | 86.67 | 349.33 |
August | 366.67 | 0.64 | 0.62 | 01-AUG-05:30 | 2881.87 | 19.57 | 98.50 | 364.33 | 1266.48 | 21.32 | 67.00 | 320.83 |
September | 301.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2386.21 | 20.67 | 82.50 | 315.00 | 1330.41 | 22.16 | 60.67 | 266.33 |
October | 245.33 | 0.65 | 0.62 | 01-OCT-07:19 | 2138.48 | 20.65 | 81.00 | 259.67 | 913.64 | 20.67 | 54.83 | 202.67 |
November | 242.67 | 0.65 | 0.62 | 01-NOV-07:49 | 967.73 | 17.79 | 64.67 | 194.67 | 517.05 | 20.41 | 63.83 | 119.17 |
December | 160.33 | 0.65 | 0.62 | 01-DEC-09:39 | 919.16 | 20.05 | 54.67 | 168.50 | 502.83 | 21.38 | 52.00 | 86.00 |
Annual Sum or Average | 3714.00 | 0.64 | 2140.09 | 19.48 | 1042.00 | 3501.67 | 1048.85 | 21.05 | 800.50 | 2805.17 | ||
Minimum of Months | 160.33 | 0.63 | 0.62 | 751.92 | 15.92 | 42.83 | 168.50 | 493.76 | 20.18 | 50.67 | 86.00 | |
Maximum of Months | 471.00 | 0.65 | 0.62 | 2881.87 | 20.99 | 146.50 | 393.67 | 1460.71 | 22.16 | 86.67 | 349.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.67 | 0.62 | 01-JAN-09:50 | 420.39 | 12.68 | 0.00 | 153.67 | 230.54 | 15.44 | 0.00 | 10.50 |
February | 259.50 | 0.65 | 0.62 | 01-FEB-08:50 | 530.88 | 13.93 | 0.00 | 196.83 | 302.16 | 16.76 | 0.00 | 89.17 |
March | 247.00 | 0.64 | 0.62 | 01-MAR-07:00 | 710.76 | 15.53 | 0.00 | 282.33 | 424.32 | 18.37 | 0.00 | 169.50 |
April | 379.50 | 0.64 | 0.62 | 01-APR-06:40 | 836.88 | 16.37 | 0.00 | 341.00 | 487.38 | 19.06 | 0.00 | 276.17 |
May | 427.83 | 0.63 | 0.62 | 01-MAY-06:49 | 1043.62 | 18.20 | 26.50 | 394.33 | 599.44 | 21.37 | 84.50 | 351.83 |
June | 375.17 | 0.63 | 0.62 | 01-JUN-04:00 | 1095.46 | 20.03 | 58.83 | 407.17 | 647.53 | 22.66 | 120.50 | 373.33 |
July | 471.00 | 0.64 | 0.62 | 01-JUL-04:00 | 920.19 | 17.72 | 44.50 | 416.00 | 557.60 | 21.73 | 121.17 | 362.83 |
August | 366.67 | 0.63 | 0.62 | 01-AUG-05:40 | 801.25 | 16.45 | 0.00 | 380.50 | 497.97 | 19.20 | 5.50 | 320.83 |
September | 301.17 | 0.64 | 0.62 | 01-SEP-07:40 | 769.78 | 16.45 | 0.00 | 305.17 | 471.70 | 19.24 | 0.00 | 231.17 |
October | 245.33 | 0.65 | 0.62 | 01-OCT-07:40 | 573.77 | 14.47 | 0.00 | 241.67 | 351.26 | 17.40 | 0.00 | 132.33 |
November | 242.67 | 0.66 | 0.62 | 01-NOV-07:00 | 453.11 | 13.03 | 0.00 | 169.50 | 248.18 | 15.74 | 0.00 | 29.33 |
December | 160.33 | 0.68 | 0.62 | 01-DEC-09:50 | 388.12 | 12.58 | 0.00 | 124.50 | 229.94 | 15.65 | 0.00 | 11.50 |
Annual Sum or Average | 3714.00 | 0.64 | 770.15 | 16.16 | 129.83 | 3412.67 | 455.83 | 19.15 | 331.67 | 2358.50 | ||
Minimum of Months | 160.33 | 0.63 | 0.62 | 388.12 | 12.58 | 0.00 | 124.50 | 229.94 | 15.44 | 0.00 | 10.50 | |
Maximum of Months | 471.00 | 0.68 | 0.62 | 1095.46 | 20.03 | 58.83 | 416.00 | 647.53 | 22.66 | 121.17 | 373.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.65 | 0.62 | 01-JAN-09:39 | 885.20 | 17.70 | 63.33 | 188.67 | 486.51 | 20.41 | 60.67 | 109.17 |
February | 259.50 | 0.64 | 0.62 | 01-FEB-08:00 | 1274.10 | 18.71 | 65.50 | 218.17 | 652.68 | 19.93 | 49.83 | 162.17 |
March | 247.00 | 0.64 | 0.62 | 01-MAR-07:00 | 1978.29 | 19.22 | 59.83 | 293.17 | 1099.51 | 22.34 | 62.83 | 229.50 |
April | 379.50 | 0.64 | 0.62 | 01-APR-07:10 | 2433.29 | 19.74 | 105.17 | 334.67 | 1070.75 | 20.06 | 51.00 | 291.50 |
May | 427.83 | 0.63 | 0.62 | 01-MAY-06:00 | 2539.72 | 16.50 | 51.83 | 382.67 | 1360.45 | 17.89 | 1.33 | 334.00 |
June | 375.17 | 0.64 | 0.62 | 01-JUN-05:49 | 2571.77 | 16.14 | 42.83 | 389.33 | 1164.10 | 17.71 | 0.00 | 348.67 |
July | 471.00 | 0.65 | 0.62 | 01-JUL-05:10 | 2843.87 | 15.26 | 58.83 | 391.33 | 1248.68 | 16.50 | 3.67 | 343.83 |
August | 366.67 | 0.64 | 0.62 | 01-AUG-05:00 | 2721.52 | 18.11 | 75.83 | 369.17 | 1562.88 | 20.03 | 50.50 | 324.17 |
September | 301.17 | 0.64 | 0.62 | 01-SEP-07:40 | 3006.15 | 21.91 | 100.50 | 306.00 | 1670.91 | 22.97 | 75.67 | 252.00 |
October | 245.33 | 0.64 | 0.62 | 01-OCT-07:40 | 2055.01 | 21.24 | 87.33 | 260.17 | 890.01 | 20.94 | 53.17 | 201.33 |
November | 242.67 | 0.65 | 0.62 | 01-NOV-08:09 | 946.40 | 17.65 | 61.67 | 197.17 | 491.48 | 18.84 | 43.83 | 113.67 |
December | 160.33 | 0.66 | 0.62 | 01-DEC-09:39 | 943.67 | 19.11 | 48.67 | 170.33 | 506.01 | 20.26 | 41.33 | 79.67 |
Annual Sum or Average | 3714.00 | 0.64 | 2189.68 | 18.15 | 821.33 | 3500.83 | 1094.49 | 19.51 | 493.83 | 2789.67 | ||
Minimum of Months | 160.33 | 0.63 | 0.62 | 885.20 | 15.26 | 42.83 | 170.33 | 486.51 | 16.50 | 0.00 | 79.67 | |
Maximum of Months | 471.00 | 0.66 | 0.62 | 3006.15 | 21.91 | 105.17 | 391.33 | 1670.91 | 22.97 | 75.67 | 348.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.64 | 0.62 | 01-JAN-09:20 | 2266.99 | 28.18 | 189.17 | 208.50 | 1883.88 | 32.92 | 221.00 | 170.67 |
February | 259.50 | 0.63 | 0.62 | 01-FEB-08:30 | 4008.37 | 30.49 | 218.00 | 234.50 | 1731.08 | 27.55 | 155.50 | 209.50 |
March | 247.00 | 0.63 | 0.62 | 01-MAR-07:40 | 6761.89 | 31.61 | 206.50 | 302.67 | 1348.77 | 18.31 | 8.17 | 250.17 |
April | 379.50 | 0.64 | 0.62 | 01-APR-06:49 | 1773.88 | 13.56 | 0.00 | 335.33 | 971.76 | 17.49 | 0.17 | 290.00 |
May | 427.83 | 0.64 | 0.62 | 01-MAY-06:49 | 1629.87 | 13.49 | 0.00 | 373.17 | 880.77 | 17.36 | 0.00 | 323.17 |
June | 375.17 | 0.65 | 0.62 | 01-JUN-05:40 | 1417.68 | 13.34 | 0.00 | 381.33 | 809.20 | 17.22 | 0.00 | 323.33 |
July | 471.00 | 0.66 | 0.62 | 01-JUL-05:10 | 1260.94 | 11.95 | 0.00 | 374.50 | 732.89 | 15.86 | 0.00 | 311.00 |
August | 366.67 | 0.65 | 0.62 | 01-AUG-05:49 | 1488.98 | 13.09 | 0.00 | 357.33 | 882.80 | 17.09 | 0.83 | 307.83 |
September | 301.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2452.44 | 16.20 | 27.00 | 310.00 | 1169.55 | 18.42 | 9.50 | 269.50 |
October | 245.33 | 0.64 | 0.62 | 01-OCT-07:40 | 6255.84 | 33.04 | 216.33 | 276.83 | 1599.29 | 19.69 | 26.33 | 244.00 |
November | 242.67 | 0.64 | 0.62 | 01-NOV-07:00 | 2572.78 | 28.44 | 196.83 | 213.83 | 2125.45 | 32.55 | 225.50 | 178.67 |
December | 160.33 | 0.64 | 0.62 | 01-DEC-09:39 | 2934.41 | 28.91 | 114.17 | 195.17 | 2700.65 | 36.19 | 149.67 | 145.83 |
Annual Sum or Average | 3714.00 | 0.64 | 2600.95 | 19.73 | 1168.00 | 3563.17 | 1249.83 | 20.96 | 796.67 | 3023.67 | ||
Minimum of Months | 160.33 | 0.63 | 0.62 | 1260.94 | 11.95 | 0.00 | 195.17 | 732.89 | 15.86 | 0.00 | 145.83 | |
Maximum of Months | 471.00 | 0.66 | 0.62 | 6761.89 | 33.04 | 218.00 | 381.33 | 2700.65 | 36.19 | 225.50 | 323.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.65 | 0.62 | 01-JAN-09:20 | 723.04 | 15.43 | 42.83 | 182.67 | 474.22 | 20.24 | 68.17 | 101.00 |
February | 259.50 | 0.64 | 0.62 | 01-FEB-08:20 | 1234.90 | 18.07 | 66.33 | 213.83 | 629.02 | 19.64 | 48.17 | 153.83 |
March | 247.00 | 0.64 | 0.62 | 01-MAR-07:30 | 2262.95 | 20.58 | 79.00 | 288.50 | 941.29 | 20.65 | 41.00 | 223.50 |
April | 379.50 | 0.64 | 0.62 | 01-APR-06:19 | 2374.86 | 19.64 | 105.17 | 335.50 | 1306.92 | 21.41 | 78.17 | 284.67 |
May | 427.83 | 0.64 | 0.62 | 01-MAY-06:49 | 2420.69 | 18.51 | 110.00 | 379.00 | 1040.86 | 20.50 | 73.50 | 329.17 |
June | 375.17 | 0.64 | 0.62 | 01-JUN-04:00 | 2557.74 | 18.72 | 88.00 | 388.67 | 1385.20 | 20.70 | 63.00 | 333.33 |
July | 471.00 | 0.65 | 0.62 | 01-JUL-04:49 | 2375.62 | 17.61 | 118.67 | 389.00 | 1074.04 | 20.01 | 86.67 | 345.50 |
August | 366.67 | 0.64 | 0.62 | 01-AUG-05:30 | 2795.18 | 19.03 | 96.33 | 360.67 | 1207.23 | 21.14 | 66.83 | 317.83 |
September | 301.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2197.24 | 18.74 | 66.33 | 312.67 | 1278.48 | 21.95 | 59.17 | 259.83 |
October | 245.33 | 0.65 | 0.62 | 01-OCT-07:19 | 2079.48 | 20.24 | 81.00 | 256.33 | 869.69 | 20.44 | 47.50 | 196.17 |
November | 242.67 | 0.65 | 0.62 | 01-NOV-07:49 | 934.27 | 17.13 | 61.83 | 192.17 | 494.88 | 20.17 | 61.50 | 110.50 |
December | 160.33 | 0.66 | 0.62 | 01-DEC-09:39 | 818.09 | 17.07 | 38.17 | 163.33 | 479.45 | 21.13 | 49.33 | 80.33 |
Annual Sum or Average | 3714.00 | 0.64 | 2052.09 | 18.47 | 953.67 | 3462.33 | 999.83 | 20.66 | 743.00 | 2735.67 | ||
Minimum of Months | 160.33 | 0.63 | 0.62 | 723.04 | 15.43 | 38.17 | 163.33 | 474.22 | 19.64 | 41.00 | 80.33 | |
Maximum of Months | 471.00 | 0.66 | 0.62 | 2795.18 | 20.58 | 118.67 | 389.00 | 1385.20 | 21.95 | 86.67 | 345.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.67 | 0.62 | 01-JAN-09:50 | 401.92 | 8.58 | 0.00 | 146.50 | 220.52 | 12.58 | 0.00 | 5.83 |
February | 259.50 | 0.65 | 0.62 | 01-FEB-08:50 | 507.85 | 10.08 | 0.00 | 191.83 | 289.83 | 14.11 | 0.00 | 76.50 |
March | 247.00 | 0.64 | 0.62 | 01-MAR-07:00 | 680.40 | 12.09 | 0.00 | 277.83 | 408.33 | 16.09 | 0.00 | 157.17 |
April | 379.50 | 0.64 | 0.62 | 01-APR-06:40 | 801.84 | 12.96 | 0.00 | 338.83 | 468.80 | 16.86 | 0.00 | 268.50 |
May | 427.83 | 0.63 | 0.62 | 01-MAY-06:49 | 993.31 | 13.57 | 1.50 | 390.83 | 575.93 | 19.27 | 40.33 | 345.00 |
June | 375.17 | 0.64 | 0.62 | 01-JUN-05:10 | 1040.54 | 15.89 | 35.83 | 404.50 | 623.34 | 20.89 | 61.67 | 369.50 |
July | 471.00 | 0.64 | 0.62 | 01-JUL-04:00 | 884.03 | 14.53 | 44.50 | 414.00 | 537.96 | 19.85 | 78.83 | 357.50 |
August | 366.67 | 0.64 | 0.62 | 01-AUG-05:40 | 768.74 | 13.20 | 0.00 | 377.00 | 480.96 | 17.27 | 0.00 | 310.67 |
September | 301.17 | 0.64 | 0.62 | 01-SEP-07:40 | 736.65 | 13.32 | 0.00 | 301.67 | 454.41 | 17.28 | 0.00 | 222.67 |
October | 245.33 | 0.66 | 0.62 | 01-OCT-07:40 | 548.57 | 11.05 | 0.00 | 237.33 | 338.03 | 15.13 | 0.00 | 123.17 |
November | 242.67 | 0.66 | 0.62 | 01-NOV-07:00 | 433.48 | 8.96 | 0.00 | 161.00 | 237.56 | 12.90 | 0.00 | 19.83 |
December | 160.33 | 0.68 | 0.62 | 01-DEC-09:50 | 369.79 | 8.72 | 0.00 | 114.33 | 220.09 | 12.99 | 0.00 | 6.00 |
Annual Sum or Average | 3714.00 | 0.65 | 736.20 | 12.47 | 81.83 | 3355.67 | 438.65 | 16.94 | 180.83 | 2262.33 | ||
Minimum of Months | 160.33 | 0.63 | 0.62 | 369.79 | 8.58 | 0.00 | 114.33 | 220.09 | 12.58 | 0.00 | 5.83 | |
Maximum of Months | 471.00 | 0.68 | 0.62 | 1040.54 | 15.89 | 44.50 | 414.00 | 623.34 | 20.89 | 78.83 | 369.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.65 | 0.62 | 01-JAN-09:50 | 855.33 | 17.37 | 62.83 | 184.17 | 446.82 | 18.82 | 45.17 | 100.17 |
February | 259.50 | 0.64 | 0.62 | 01-FEB-08:00 | 1230.44 | 18.35 | 65.50 | 215.33 | 621.35 | 19.80 | 49.50 | 156.17 |
March | 247.00 | 0.64 | 0.62 | 01-MAR-08:09 | 1915.29 | 18.85 | 59.83 | 289.83 | 1053.59 | 22.23 | 61.50 | 223.83 |
April | 379.50 | 0.64 | 0.62 | 01-APR-07:10 | 2366.60 | 19.38 | 105.00 | 332.17 | 1021.12 | 19.92 | 51.00 | 287.83 |
May | 427.83 | 0.64 | 0.62 | 01-MAY-06:00 | 2459.56 | 16.08 | 51.50 | 380.67 | 1301.68 | 17.72 | 0.83 | 329.83 |
June | 375.17 | 0.64 | 0.62 | 01-JUN-05:49 | 2494.05 | 15.72 | 42.83 | 386.50 | 1107.72 | 17.53 | 0.00 | 344.00 |
July | 471.00 | 0.65 | 0.62 | 01-JUL-05:19 | 2738.98 | 14.84 | 58.83 | 388.00 | 1187.86 | 16.33 | 3.67 | 338.33 |
August | 366.67 | 0.64 | 0.62 | 01-AUG-05:00 | 2504.29 | 17.73 | 75.83 | 365.17 | 1499.82 | 19.89 | 50.33 | 320.50 |
September | 301.17 | 0.64 | 0.62 | 01-SEP-07:40 | 2919.87 | 21.56 | 100.50 | 303.00 | 1605.55 | 22.85 | 75.33 | 248.83 |
October | 245.33 | 0.65 | 0.62 | 01-OCT-07:49 | 1995.48 | 20.91 | 87.33 | 257.33 | 845.27 | 20.82 | 52.67 | 194.17 |
November | 242.67 | 0.65 | 0.62 | 01-NOV-08:09 | 914.00 | 17.31 | 61.33 | 194.00 | 469.20 | 18.71 | 43.33 | 108.67 |
December | 160.33 | 0.66 | 0.62 | 01-DEC-09:39 | 910.51 | 18.77 | 48.67 | 166.67 | 482.86 | 20.16 | 40.67 | 76.00 |
Annual Sum or Average | 3714.00 | 0.64 | 2107.40 | 17.77 | 820.00 | 3462.83 | 1044.52 | 19.27 | 474.00 | 2728.33 | ||
Minimum of Months | 160.33 | 0.64 | 0.62 | 855.33 | 14.84 | 42.83 | 166.67 | 446.82 | 16.33 | 0.00 | 76.00 | |
Maximum of Months | 471.00 | 0.66 | 0.62 | 2919.87 | 21.56 | 105.00 | 388.00 | 1605.55 | 22.85 | 75.33 | 344.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.64 | 0.62 | 01-JAN-09:20 | 2267.00 | 28.18 | 189.17 | 208.50 | 1883.83 | 32.92 | 221.00 | 170.67 |
February | 259.50 | 0.63 | 0.62 | 01-FEB-08:30 | 4008.37 | 30.49 | 218.00 | 234.50 | 1731.01 | 27.55 | 155.50 | 209.33 |
March | 247.00 | 0.63 | 0.62 | 01-MAR-07:40 | 6761.85 | 31.61 | 206.50 | 302.67 | 1348.68 | 18.31 | 8.17 | 250.17 |
April | 379.50 | 0.64 | 0.62 | 01-APR-06:49 | 1773.80 | 13.56 | 0.00 | 335.33 | 971.69 | 17.49 | 0.17 | 290.00 |
May | 427.83 | 0.64 | 0.62 | 01-MAY-06:49 | 1629.79 | 13.49 | 0.00 | 373.17 | 880.70 | 17.37 | 0.00 | 323.17 |
June | 375.17 | 0.65 | 0.62 | 01-JUN-05:40 | 1417.62 | 13.34 | 0.00 | 381.33 | 809.14 | 17.22 | 0.00 | 323.33 |
July | 471.00 | 0.66 | 0.62 | 01-JUL-05:10 | 1260.89 | 11.96 | 0.00 | 374.50 | 732.84 | 15.86 | 0.00 | 311.00 |
August | 366.67 | 0.65 | 0.62 | 01-AUG-05:49 | 1488.93 | 13.09 | 0.00 | 357.33 | 882.74 | 17.09 | 0.83 | 307.83 |
September | 301.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2452.38 | 16.20 | 27.00 | 310.00 | 1169.47 | 18.42 | 9.67 | 269.50 |
October | 245.33 | 0.64 | 0.62 | 01-OCT-07:40 | 6255.84 | 33.04 | 216.33 | 276.83 | 1599.21 | 19.69 | 26.33 | 244.00 |
November | 242.67 | 0.64 | 0.62 | 01-NOV-07:00 | 2572.78 | 28.44 | 196.83 | 213.83 | 2125.40 | 32.55 | 225.50 | 178.67 |
December | 160.33 | 0.64 | 0.62 | 01-DEC-09:39 | 2934.46 | 28.91 | 114.17 | 195.17 | 2700.60 | 36.19 | 149.67 | 145.83 |
Annual Sum or Average | 3714.00 | 0.64 | 2600.91 | 19.74 | 1168.00 | 3563.17 | 1249.76 | 20.96 | 796.83 | 3023.50 | ||
Minimum of Months | 160.33 | 0.63 | 0.62 | 1260.89 | 11.96 | 0.00 | 195.17 | 732.84 | 15.86 | 0.00 | 145.83 | |
Maximum of Months | 471.00 | 0.66 | 0.62 | 6761.85 | 33.04 | 218.00 | 381.33 | 2700.60 | 36.19 | 225.50 | 323.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.65 | 0.62 | 01-JAN-09:20 | 723.03 | 15.43 | 42.83 | 182.67 | 474.19 | 20.24 | 68.17 | 101.00 |
February | 259.50 | 0.64 | 0.62 | 01-FEB-08:20 | 1234.88 | 18.07 | 66.33 | 213.83 | 628.99 | 19.64 | 48.17 | 153.83 |
March | 247.00 | 0.64 | 0.62 | 01-MAR-07:30 | 2262.93 | 20.58 | 79.00 | 288.50 | 941.24 | 20.65 | 41.00 | 223.50 |
April | 379.50 | 0.64 | 0.62 | 01-APR-06:19 | 2374.83 | 19.64 | 105.17 | 335.50 | 1306.87 | 21.41 | 78.17 | 284.50 |
May | 427.83 | 0.64 | 0.62 | 01-MAY-06:49 | 2420.65 | 18.51 | 110.00 | 379.00 | 1040.80 | 20.50 | 73.50 | 329.17 |
June | 375.17 | 0.64 | 0.62 | 01-JUN-04:00 | 2557.72 | 18.72 | 88.00 | 388.67 | 1385.14 | 20.70 | 63.00 | 333.33 |
July | 471.00 | 0.65 | 0.62 | 01-JUL-04:49 | 2375.60 | 17.61 | 118.67 | 389.00 | 1074.00 | 20.01 | 86.67 | 345.50 |
August | 366.67 | 0.64 | 0.62 | 01-AUG-05:30 | 2795.17 | 19.03 | 96.33 | 360.67 | 1207.18 | 21.14 | 66.83 | 317.83 |
September | 301.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2197.23 | 18.74 | 66.33 | 312.67 | 1278.43 | 21.95 | 59.17 | 259.83 |
October | 245.33 | 0.65 | 0.62 | 01-OCT-07:19 | 2079.48 | 20.24 | 81.00 | 256.33 | 869.65 | 20.44 | 47.50 | 196.17 |
November | 242.67 | 0.65 | 0.62 | 01-NOV-07:49 | 934.25 | 17.13 | 61.83 | 192.17 | 494.85 | 20.17 | 61.50 | 110.50 |
December | 160.33 | 0.66 | 0.62 | 01-DEC-09:39 | 818.09 | 17.07 | 38.17 | 163.33 | 479.43 | 21.13 | 49.33 | 80.33 |
Annual Sum or Average | 3714.00 | 0.64 | 2052.07 | 18.48 | 953.67 | 3462.33 | 999.79 | 20.67 | 743.00 | 2735.50 | ||
Minimum of Months | 160.33 | 0.63 | 0.62 | 723.03 | 15.43 | 38.17 | 163.33 | 474.19 | 19.64 | 41.00 | 80.33 | |
Maximum of Months | 471.00 | 0.66 | 0.62 | 2795.17 | 20.58 | 118.67 | 389.00 | 1385.14 | 21.95 | 86.67 | 345.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.67 | 0.62 | 01-JAN-09:50 | 401.90 | 8.58 | 0.00 | 146.50 | 220.51 | 12.58 | 0.00 | 5.83 |
February | 259.50 | 0.65 | 0.62 | 01-FEB-08:50 | 507.84 | 10.08 | 0.00 | 191.83 | 289.81 | 14.11 | 0.00 | 76.33 |
March | 247.00 | 0.64 | 0.62 | 01-MAR-07:00 | 680.40 | 12.09 | 0.00 | 277.83 | 408.30 | 16.09 | 0.00 | 157.17 |
April | 379.50 | 0.64 | 0.62 | 01-APR-06:40 | 801.82 | 12.96 | 0.00 | 338.83 | 468.77 | 16.86 | 0.00 | 268.50 |
May | 427.83 | 0.63 | 0.62 | 01-MAY-06:49 | 993.28 | 13.57 | 1.50 | 390.83 | 575.89 | 19.27 | 40.33 | 345.00 |
June | 375.17 | 0.64 | 0.62 | 01-JUN-05:10 | 1040.53 | 15.89 | 35.83 | 404.50 | 623.30 | 20.89 | 61.67 | 369.50 |
July | 471.00 | 0.64 | 0.62 | 01-JUL-04:00 | 884.01 | 14.53 | 44.50 | 414.00 | 537.94 | 19.86 | 78.83 | 357.33 |
August | 366.67 | 0.64 | 0.62 | 01-AUG-05:40 | 768.73 | 13.20 | 0.00 | 377.00 | 480.94 | 17.27 | 0.00 | 310.67 |
September | 301.17 | 0.64 | 0.62 | 01-SEP-07:40 | 736.64 | 13.32 | 0.00 | 301.67 | 454.39 | 17.29 | 0.00 | 222.50 |
October | 245.33 | 0.66 | 0.62 | 01-OCT-07:40 | 548.57 | 11.05 | 0.00 | 237.33 | 338.01 | 15.13 | 0.00 | 123.17 |
November | 242.67 | 0.66 | 0.62 | 01-NOV-07:00 | 433.47 | 8.96 | 0.00 | 161.00 | 237.54 | 12.90 | 0.00 | 19.83 |
December | 160.33 | 0.68 | 0.62 | 01-DEC-09:50 | 369.79 | 8.72 | 0.00 | 114.33 | 220.08 | 12.99 | 0.00 | 6.00 |
Annual Sum or Average | 3714.00 | 0.65 | 736.19 | 12.47 | 81.83 | 3355.67 | 438.62 | 16.94 | 180.83 | 2261.83 | ||
Minimum of Months | 160.33 | 0.63 | 0.62 | 369.79 | 8.58 | 0.00 | 114.33 | 220.08 | 12.58 | 0.00 | 5.83 | |
Maximum of Months | 471.00 | 0.68 | 0.62 | 1040.53 | 15.89 | 44.50 | 414.00 | 623.30 | 20.89 | 78.83 | 369.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.65 | 0.62 | 01-JAN-09:50 | 855.32 | 17.37 | 62.83 | 184.17 | 446.79 | 18.82 | 45.17 | 100.00 |
February | 259.50 | 0.64 | 0.62 | 01-FEB-08:00 | 1230.43 | 18.35 | 65.50 | 215.33 | 621.31 | 19.80 | 49.50 | 156.17 |
March | 247.00 | 0.64 | 0.62 | 01-MAR-08:09 | 1915.27 | 18.85 | 59.83 | 289.83 | 1053.54 | 22.24 | 61.50 | 223.83 |
April | 379.50 | 0.64 | 0.62 | 01-APR-07:10 | 2366.57 | 19.38 | 105.00 | 332.17 | 1021.06 | 19.92 | 51.00 | 287.83 |
May | 427.83 | 0.64 | 0.62 | 01-MAY-06:00 | 2459.52 | 16.08 | 51.50 | 380.67 | 1301.61 | 17.72 | 0.83 | 329.83 |
June | 375.17 | 0.64 | 0.62 | 01-JUN-05:49 | 2494.02 | 15.72 | 42.83 | 386.50 | 1107.67 | 17.53 | 0.00 | 344.00 |
July | 471.00 | 0.65 | 0.62 | 01-JUL-05:19 | 2738.95 | 14.85 | 58.83 | 388.00 | 1187.81 | 16.33 | 3.67 | 338.33 |
August | 366.67 | 0.64 | 0.62 | 01-AUG-05:00 | 2504.28 | 17.73 | 75.83 | 365.17 | 1499.78 | 19.89 | 50.33 | 320.50 |
September | 301.17 | 0.64 | 0.62 | 01-SEP-07:40 | 2919.87 | 21.57 | 100.50 | 303.00 | 1605.49 | 22.85 | 75.33 | 248.83 |
October | 245.33 | 0.65 | 0.62 | 01-OCT-07:49 | 1995.48 | 20.91 | 87.33 | 257.33 | 845.23 | 20.82 | 52.67 | 194.17 |
November | 242.67 | 0.65 | 0.62 | 01-NOV-08:09 | 913.98 | 17.31 | 61.33 | 194.00 | 469.17 | 18.71 | 43.33 | 108.67 |
December | 160.33 | 0.66 | 0.62 | 01-DEC-09:39 | 910.52 | 18.77 | 48.67 | 166.67 | 482.84 | 20.16 | 40.67 | 76.00 |
Annual Sum or Average | 3714.00 | 0.64 | 2107.39 | 17.77 | 820.00 | 3462.83 | 1044.47 | 19.27 | 474.00 | 2728.17 | ||
Minimum of Months | 160.33 | 0.64 | 0.62 | 855.32 | 14.85 | 42.83 | 166.67 | 446.79 | 16.33 | 0.00 | 76.00 | |
Maximum of Months | 471.00 | 0.66 | 0.62 | 2919.87 | 21.57 | 105.00 | 388.00 | 1605.49 | 22.85 | 75.33 | 344.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.450556E+09 | 25673.38 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.450556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.450556E+09 | 25673.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.646760E+10 | 11059.21 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.418416E+10 | 11059.21 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.338143E+10 | 11059.21 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196091E+10 | 11059.21 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131790E+10 | 11059.21 | 02-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.802304E+09 | 11059.21 | 01-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.334060E+09 | 11059.21 | 03-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.287925E+09 | 11059.21 | 01-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.741949E+09 | 11059.21 | 05-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171060E+10 | 11059.21 | 02-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.390260E+10 | 11059.21 | 01-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.529896E+10 | 11059.21 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.303904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.287925E+09 | 11059.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.646760E+10 | 11059.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.173177E+10 | 7386.24 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.817738E+09 | 7386.24 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.215414E+09 | 7386.24 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33855577.84 | 7386.24 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79891.34 | 409.32 | 18-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23722156.64 | 4962.51 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.393528E+09 | 7386.24 | 10-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108338E+10 | 7386.24 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.429949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.173177E+10 | 7386.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.257739E+10 | 7151.47 | 03-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133809E+10 | 7123.37 | 24-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.433771E+09 | 7116.48 | 13-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80649095.10 | 7107.38 | 12-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30635413.99 | 7107.51 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.526388E+09 | 7113.68 | 21-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156365E+10 | 7110.38 | 08-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.655058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.257739E+10 | 7151.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.187599E+10 | 7335.91 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.939035E+09 | 7335.91 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.318826E+09 | 7335.91 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 63682248.23 | 7335.91 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 466778.92 | 980.40 | 18-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36473961.42 | 4594.03 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.478639E+09 | 7335.91 | 10-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121879E+10 | 7335.91 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.493190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.187599E+10 | 7335.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.154897E+10 | 24758.70 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.329626E+09 | 24758.70 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18452434.30 | 24758.70 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112104E+09 | 24758.70 | 13-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.519884E+09 | 24758.70 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.252904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.154897E+10 | 24758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.198335E+10 | 11828.79 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.889477E+09 | 11828.79 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.239165E+09 | 11828.79 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 57612701.12 | 11828.79 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1282538.96 | 2828.34 | 18-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72505149.71 | 10687.44 | 16-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.693603E+09 | 11828.79 | 10-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146865E+10 | 11828.79 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.540564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.198335E+10 | 11828.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.182710E+10 | 7837.05 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.897471E+09 | 7837.05 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227898E+09 | 7837.05 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41034626.10 | 7837.05 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1576707.47 | 2892.65 | 18-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33288.98 | 221.93 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86376177.01 | 7837.05 | 24-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.685903E+09 | 7837.05 | 10-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138455E+10 | 7837.05 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.515195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.182710E+10 | 7837.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.226315E+10 | 7945.52 | 03-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107464E+10 | 7912.98 | 22-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.237543E+09 | 7924.97 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40160901.59 | 7882.72 | 18-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 57612193.91 | 7837.45 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.692174E+09 | 7907.65 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161925E+10 | 7918.84 | 20-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.598452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.226315E+10 | 7945.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181534E+10 | 7793.15 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.921068E+09 | 7793.15 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.283669E+09 | 7793.15 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 63909437.50 | 7793.15 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1743737.57 | 3245.75 | 18-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 99614857.66 | 7793.15 | 24-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.703073E+09 | 7793.15 | 10-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139290E+10 | 7793.15 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.528131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.181534E+10 | 7793.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.426892E+10 | 31788.20 | 03-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.197368E+10 | 31768.91 | 22-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.412264E+09 | 31801.86 | 13-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 64890006.63 | 31201.72 | 18-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 94110691.01 | 31447.12 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137835E+10 | 31792.74 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.311585E+10 | 31761.08 | 08-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.426892E+10 | 31801.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.349785E+10 | 15260.16 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196557E+10 | 15260.16 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.936899E+09 | 15260.16 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.348047E+09 | 15260.16 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 56414916.19 | 13573.15 | 18-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3069146.11 | 2107.95 | 14-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16765967.55 | 10383.46 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.449215E+09 | 15260.16 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172819E+10 | 15260.16 | 10-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.292216E+10 | 15260.16 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.349785E+10 | 15260.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.279309E+10 | 10040.94 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159046E+10 | 10040.94 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.681484E+09 | 10040.94 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.181731E+09 | 10040.94 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29725761.77 | 8672.67 | 18-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1359746.17 | 1707.33 | 14-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12179699.86 | 6689.04 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.362497E+09 | 10040.94 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135456E+10 | 10040.94 | 10-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232793E+10 | 10040.94 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.933502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.279309E+10 | 10040.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.396060E+10 | 9022.92 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235029E+10 | 9007.51 | 22-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.100134E+10 | 9014.72 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.299678E+09 | 9004.69 | 18-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23969041.43 | 8910.54 | 18-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 170680.07 | 525.40 | 14-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9665445.45 | 8778.80 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.434528E+09 | 8975.56 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177658E+10 | 9015.06 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.327215E+10 | 9010.17 | 11-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.396060E+10 | 9022.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.297964E+10 | 9989.58 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.180663E+10 | 9989.58 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.917106E+09 | 9989.58 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.315076E+09 | 9989.58 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 51936587.76 | 8714.39 | 18-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2865390.60 | 1740.08 | 14-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20064277.47 | 6626.24 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.469386E+09 | 9989.58 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155027E+10 | 9989.58 | 10-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.252945E+10 | 9989.58 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.297964E+10 | 9989.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.485277E+10 | 12423.15 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.278546E+10 | 10499.76 | 18-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.505536E+09 | 7925.08 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163718E+09 | 5326.33 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1901992.93 | 843.65 | 18-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20883658.64 | 1597.12 | 30-OCT-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132634E+10 | 8080.12 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.332871E+10 | 12178.27 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.485277E+10 | 12423.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.611866E+10 | 13446.92 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385010E+10 | 11800.12 | 18-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133194E+10 | 9109.77 | 01-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.452703E+09 | 6809.32 | 19-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43424058.00 | 2906.74 | 18-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 386599.61 | 269.11 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156280E+09 | 3497.08 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.244946E+10 | 9582.67 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.487082E+10 | 13191.04 | 26-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.611866E+10 | 13446.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.651046E+10 | 14760.11 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.418188E+10 | 13881.83 | 18-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175622E+10 | 11335.21 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.661246E+09 | 8691.20 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114890E+09 | 4580.98 | 18-MAY-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14980688.83 | 1815.95 | 27-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.324660E+09 | 4692.52 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.272986E+10 | 10846.33 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.533113E+10 | 13674.88 | 26-DEC-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.651046E+10 | 14760.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.201651E+09 | 0.182249E+09 | 11646.73 | 27-FEB-15:00 | 11646.73 | 0.00 |
March | 0.00 | 0.00 | 0.311199E+09 | 0.272749E+09 | 9832.44 | 18-MAR-16:00 | 9832.44 | 0.00 |
April | 0.00 | 0.00 | 0.333517E+10 | 0.319529E+10 | 50335.34 | 27-APR-15:10 | 50335.34 | 0.00 |
May | 0.00 | 0.00 | 0.730036E+10 | 0.650393E+10 | 44387.10 | 15-MAY-16:00 | 44387.10 | 0.00 |
June | 0.00 | 0.00 | 0.139945E+11 | 0.130278E+11 | 52369.05 | 28-JUN-15:50 | 52369.05 | 0.00 |
July | 0.00 | 0.00 | 0.270174E+11 | 0.239311E+11 | 72225.52 | 31-JUL-16:10 | 56982.42 | 0.00 |
August | 0.00 | 0.00 | 0.372085E+11 | 0.325869E+11 | 71583.48 | 09-AUG-16:10 | 57026.36 | 0.00 |
September | 0.00 | 0.00 | 0.134804E+11 | 0.112668E+11 | 56779.66 | 14-SEP-13:00 | 41931.14 | 0.00 |
October | 0.00 | 0.00 | 0.168767E+10 | 0.159307E+10 | 33461.57 | 04-OCT-15:10 | 33461.57 | 0.00 |
November | 0.00 | 0.00 | 0.344745E+09 | 0.232484E+09 | 17827.45 | 04-NOV-14:00 | 13087.48 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.104882E+12 | 0.927925E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.372085E+11 | 0.325869E+11 | 72225.52 | 57026.36 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.198752E+09 | 0.185797E+09 | 12702.10 | 27-FEB-15:00 | 12702.10 | 0.00 |
March | 0.00 | 0.00 | 0.305941E+09 | 0.275679E+09 | 11317.92 | 18-MAR-14:00 | 11317.92 | 0.00 |
April | 0.00 | 0.00 | 0.328947E+10 | 0.317970E+10 | 48273.52 | 27-APR-14:50 | 48273.52 | 0.00 |
May | 0.00 | 0.00 | 0.700990E+10 | 0.633137E+10 | 42967.54 | 04-MAY-15:00 | 42967.54 | 0.00 |
June | 0.00 | 0.00 | 0.129538E+11 | 0.121452E+11 | 48869.15 | 28-JUN-15:30 | 48869.15 | 0.00 |
July | 0.00 | 0.00 | 0.244580E+11 | 0.219495E+11 | 64160.18 | 31-JUL-14:40 | 58070.98 | 0.00 |
August | 0.00 | 0.00 | 0.324888E+11 | 0.287766E+11 | 65951.98 | 29-AUG-14:30 | 57793.57 | 0.00 |
September | 0.00 | 0.00 | 0.120481E+11 | 0.101593E+11 | 51595.08 | 14-SEP-13:00 | 37458.36 | 0.00 |
October | 0.00 | 0.00 | 0.148815E+10 | 0.140808E+10 | 30331.35 | 04-OCT-15:00 | 30331.35 | 0.00 |
November | 0.00 | 0.00 | 0.362264E+09 | 0.260450E+09 | 18722.56 | 04-NOV-13:40 | 14609.02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.946032E+11 | 0.846716E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.324888E+11 | 0.287766E+11 | 65951.98 | 58070.98 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.206430E+09 | 0.187835E+09 | 12756.02 | 27-FEB-15:00 | 12756.02 | 0.00 |
March | 0.00 | 0.00 | 0.316106E+09 | 0.280389E+09 | 11510.42 | 18-MAR-16:00 | 11510.42 | 0.00 |
April | 0.00 | 0.00 | 0.356310E+10 | 0.341502E+10 | 56619.78 | 27-APR-14:50 | 56619.78 | 0.00 |
May | 0.00 | 0.00 | 0.739158E+10 | 0.658684E+10 | 47193.63 | 04-MAY-15:00 | 47193.63 | 0.00 |
June | 0.00 | 0.00 | 0.136761E+11 | 0.126876E+11 | 57425.35 | 28-JUN-15:20 | 57425.35 | 0.00 |
July | 0.00 | 0.00 | 0.262365E+11 | 0.232642E+11 | 73669.71 | 31-JUL-14:40 | 67128.13 | 0.00 |
August | 0.00 | 0.00 | 0.344681E+11 | 0.303208E+11 | 75395.18 | 10-AUG-15:20 | 71227.15 | 0.00 |
September | 0.00 | 0.00 | 0.122194E+11 | 0.101260E+11 | 52972.02 | 14-SEP-13:30 | 42632.90 | 0.00 |
October | 0.00 | 0.00 | 0.139509E+10 | 0.129592E+10 | 29815.61 | 04-OCT-15:00 | 29815.61 | 0.00 |
November | 0.00 | 0.00 | 0.378068E+09 | 0.263191E+09 | 19777.98 | 04-NOV-13:50 | 15007.03 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.998505E+11 | 0.884278E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.344681E+11 | 0.303208E+11 | 75395.18 | 71227.15 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1829.55 | 6378.45 | 31-JAN-12:06 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1851.40 | 6398.55 | 13-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1952.69 | 6375.84 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1776.93 | 6215.95 | 05-APR-11:07 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1777.83 | 6035.85 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1760.15 | 5795.21 | 01-JUN-11:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1572.87 | 5614.83 | 03-JUL-11:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1715.22 | 5527.90 | 01-AUG-11:09 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1622.28 | 5648.43 | 28-SEP-11:09 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1668.93 | 5817.72 | 25-OCT-11:06 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1755.88 | 6081.19 | 30-NOV-12:13 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1742.26 | 6263.10 | 27-DEC-12:09 |
Annual Sum or Average | 0.00 | 1751.61 | ||||
Minimum of Months | 0.00 | 0.00 | 1572.87 | 5527.90 | ||
Maximum of Months | 0.00 | 0.00 | 1952.69 | 6398.55 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135925E+10 | 0.28 | 2561.60 | 02-JAN-06:03 | 0.76 |
February | 0.126762E+10 | 0.28 | 1715.90 | 10-FEB-08:06 | 0.63 |
March | 0.171503E+10 | 0.31 | 2917.40 | 16-MAR-07:03 | 0.82 |
April | 0.192665E+10 | 0.31 | 5564.17 | 27-APR-15:10 | 1.19 |
May | 0.261024E+10 | 0.36 | 5792.63 | 15-MAY-15:10 | 1.23 |
June | 0.320276E+10 | 0.40 | 6347.67 | 28-JUN-15:10 | 1.29 |
July | 0.392390E+10 | 0.43 | 8716.27 | 24-JUL-15:10 | 1.58 |
August | 0.463949E+10 | 0.48 | 9499.91 | 10-AUG-15:50 | 1.66 |
September | 0.312815E+10 | 0.39 | 7722.81 | 11-SEP-15:30 | 1.46 |
October | 0.206661E+10 | 0.31 | 5701.85 | 04-OCT-15:10 | 1.22 |
November | 0.147347E+10 | 0.28 | 2385.84 | 09-NOV-08:02 | 0.73 |
December | 0.134763E+10 | 0.27 | 1563.44 | 07-DEC-08:20 | 0.60 |
Annual Sum or Average | 0.286608E+11 | 0.34 | |||
Minimum of Months | 0.126762E+10 | 0.27 | 1563.44 | 0.60 | |
Maximum of Months | 0.463949E+10 | 0.48 | 9499.91 | 1.66 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132588E+10 | 0.29 | 2512.81 | 02-JAN-05:01 | 0.81 |
February | 0.118839E+10 | 0.28 | 2512.81 | 06-FEB-07:01 | 0.81 |
March | 0.145313E+10 | 0.30 | 2512.81 | 06-MAR-07:01 | 0.81 |
April | 0.163840E+10 | 0.31 | 6058.41 | 27-APR-14:30 | 1.36 |
May | 0.222936E+10 | 0.35 | 6088.06 | 15-MAY-14:50 | 1.37 |
June | 0.277866E+10 | 0.40 | 6288.57 | 28-JUN-15:20 | 1.39 |
July | 0.348264E+10 | 0.43 | 8352.24 | 31-JUL-14:50 | 1.66 |
August | 0.402286E+10 | 0.47 | 8663.99 | 10-AUG-15:10 | 1.70 |
September | 0.257695E+10 | 0.37 | 7308.98 | 11-SEP-15:00 | 1.53 |
October | 0.159307E+10 | 0.29 | 5059.98 | 04-OCT-15:10 | 1.22 |
November | 0.123691E+10 | 0.27 | 2512.81 | 13-NOV-07:01 | 0.81 |
December | 0.126054E+10 | 0.27 | 2512.81 | 04-DEC-07:01 | 0.81 |
Annual Sum or Average | 0.247868E+11 | 0.34 | |||
Minimum of Months | 0.118839E+10 | 0.27 | 2512.81 | 0.81 | |
Maximum of Months | 0.402286E+10 | 0.47 | 8663.99 | 1.70 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154102E+10 | 0.32 | 2469.73 | 02-JAN-05:11 | 0.75 |
February | 0.130226E+10 | 0.29 | 2469.73 | 02-FEB-07:01 | 0.75 |
March | 0.147369E+10 | 0.29 | 2469.73 | 01-MAR-07:01 | 0.75 |
April | 0.159392E+10 | 0.29 | 6172.37 | 27-APR-14:30 | 1.27 |
May | 0.208215E+10 | 0.33 | 6309.28 | 15-MAY-14:50 | 1.29 |
June | 0.254753E+10 | 0.37 | 6580.74 | 28-JUN-15:20 | 1.32 |
July | 0.323359E+10 | 0.39 | 8652.15 | 31-JUL-15:00 | 1.56 |
August | 0.367263E+10 | 0.42 | 9160.24 | 10-AUG-15:20 | 1.62 |
September | 0.228244E+10 | 0.34 | 6778.77 | 14-SEP-14:40 | 1.34 |
October | 0.149228E+10 | 0.28 | 4329.41 | 04-OCT-14:50 | 1.03 |
November | 0.128118E+10 | 0.27 | 2469.73 | 10-NOV-07:01 | 0.75 |
December | 0.137658E+10 | 0.28 | 2469.73 | 01-DEC-07:01 | 0.75 |
Annual Sum or Average | 0.238793E+11 | 0.32 | |||
Minimum of Months | 0.128118E+10 | 0.27 | 2469.73 | 0.75 | |
Maximum of Months | 0.367263E+10 | 0.42 | 9160.24 | 1.62 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:05 | 0.22 | 0.22 | 57.43 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:02 | 0.22 | 0.22 | 56.27 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:02 | 0.22 | 0.22 | 56.11 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:03 | 0.22 | 0.22 | 55.39 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:03 | 0.22 | 0.22 | 55.90 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 56.48 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 56.94 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 56.19 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 55.98 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 57.22 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:03 | 0.22 | 0.22 | 56.11 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:01 | 0.22 | 0.22 | 56.38 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 55.39 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.43 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.94 | 56.94 | 1829.55 | 6378.45 | 31-JAN-12:06 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.74 | 56.74 | 1851.40 | 6398.55 | 13-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.01 | 57.01 | 1952.69 | 6375.84 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 55.90 | 55.90 | 1776.93 | 6215.95 | 05-APR-11:07 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.36 | 57.36 | 1777.83 | 6035.85 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.40 | 57.40 | 1760.15 | 5795.21 | 01-JUN-11:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.45 | 57.45 | 1572.87 | 5614.83 | 03-JUL-11:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.55 | 56.55 | 1715.22 | 5527.90 | 01-AUG-11:09 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.40 | 56.40 | 1622.28 | 5648.43 | 28-SEP-11:09 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.56 | 56.56 | 1668.93 | 5817.72 | 25-OCT-11:06 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.63 | 56.63 | 1755.88 | 6081.19 | 30-NOV-12:13 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.75 | 56.75 | 1742.26 | 6263.10 | 27-DEC-12:09 |
Annual Sum or Average | 0.00 | 1751.61 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.90 | 55.90 | 1572.87 | 5527.90 | ||
Maximum of Months | 0.00 | 0.00 | 57.45 | 57.45 | 1952.69 | 6398.55 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.144626E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.860174E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.615167E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.490578E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.575252E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.749017E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.108767E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.140920E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.717004E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.430590E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.686389E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.105124E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.101185E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.430590E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.144626E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.107638E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.535453E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.254456E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.266691E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.397786E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.599873E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.946451E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.120341E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.552444E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.229446E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.421562E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.764577E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.724853E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.229446E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.120341E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.190411E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.110452E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.551078E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.370006E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.408825E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.596945E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.967671E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.122227E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.534898E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.366891E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.916585E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.155441E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.104982E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.366891E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.190411E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135925E+10 | 0.00 | 0.179561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126762E+10 | 0.201651E+09 | 0.100645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171503E+10 | 0.311199E+09 | 0.485498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192665E+10 | 0.333517E+10 | 0.230281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261024E+10 | 0.730036E+10 | 0.132035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.320276E+10 | 0.139945E+11 | 0.802304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.392390E+10 | 0.270174E+11 | 0.334060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.463949E+10 | 0.372085E+11 | 0.287925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.312815E+10 | 0.134804E+11 | 0.741949E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.206661E+10 | 0.168767E+10 | 0.182231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147347E+10 | 0.344745E+09 | 0.662749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134763E+10 | 0.00 | 0.124935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.286608E+11 | 0.104882E+12 | 0.596082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126762E+10 | 0.00 | 0.287925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.463949E+10 | 0.372085E+11 | 0.179561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.132588E+10 | 0.00 | 0.155566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118839E+10 | 0.198752E+09 | 0.796238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145313E+10 | 0.305941E+09 | 0.233867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163840E+10 | 0.328947E+10 | 0.655421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.222936E+10 | 0.700990E+10 | 48027042.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.277866E+10 | 0.129538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.348264E+10 | 0.244580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.402286E+10 | 0.324888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.257695E+10 | 0.120481E+11 | 419888.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159307E+10 | 0.148815E+10 | 0.472388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123691E+10 | 0.362264E+09 | 0.533631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126054E+10 | 0.00 | 0.112561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247868E+11 | 0.946032E+11 | 0.436262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.402286E+10 | 0.324888E+11 | 0.155566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154102E+10 | 0.00 | 0.240106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130226E+10 | 0.206430E+09 | 0.138685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147369E+10 | 0.316106E+09 | 0.570531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159392E+10 | 0.356310E+10 | 0.187067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208215E+10 | 0.739158E+10 | 0.276936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.254753E+10 | 0.136761E+11 | 7464962.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.323359E+10 | 0.262365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.367263E+10 | 0.344681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.228244E+10 | 0.122194E+11 | 73656079.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149228E+10 | 0.139509E+10 | 0.213440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128118E+10 | 0.378068E+09 | 0.105178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137658E+10 | 0.00 | 0.194987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238793E+11 | 0.998505E+11 | 0.779640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.367263E+10 | 0.344681E+11 | 0.240106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126762E+10 | 0.00 | 0.00 | 0.00 | 55096982.69 | 0.727902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171503E+10 | 0.00 | 0.00 | 0.00 | 87202370.25 | 0.434944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192665E+10 | 0.00 | 0.00 | 0.00 | 0.840029E+09 | 0.213909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261024E+10 | 0.00 | 0.00 | 0.00 | 0.182383E+10 | 0.131844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.320276E+10 | 0.00 | 0.00 | 0.00 | 0.348510E+10 | 0.802304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.392390E+10 | 0.00 | 0.00 | 0.00 | 0.661870E+10 | 0.334060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.463949E+10 | 0.00 | 0.00 | 0.00 | 0.916459E+10 | 0.287925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.312815E+10 | 0.00 | 0.00 | 0.00 | 0.329994E+10 | 0.741949E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.206661E+10 | 0.00 | 0.00 | 0.00 | 0.437858E+09 | 0.180143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147347E+10 | 0.00 | 0.00 | 0.00 | 89265019.40 | 0.530115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.916478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.286608E+11 | 0.00 | 0.00 | 0.00 | 0.259016E+11 | 0.466229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.463949E+10 | 0.00 | 0.00 | 0.00 | 0.916459E+10 | 0.131033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.132588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118839E+10 | 0.00 | 0.00 | 0.00 | 53858176.77 | 0.411228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145313E+10 | 0.00 | 0.00 | 0.00 | 84697032.66 | 0.100673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163840E+10 | 0.00 | 0.00 | 0.00 | 0.825792E+09 | 0.202718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.222936E+10 | 0.00 | 0.00 | 0.00 | 0.174390E+10 | 4602984.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.277866E+10 | 0.00 | 0.00 | 0.00 | 0.322007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.348264E+10 | 0.00 | 0.00 | 0.00 | 0.598187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.402286E+10 | 0.00 | 0.00 | 0.00 | 0.801120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.257695E+10 | 0.00 | 0.00 | 0.00 | 0.294746E+10 | 33288.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159307E+10 | 0.00 | 0.00 | 0.00 | 0.385284E+09 | 0.316108E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123691E+10 | 0.00 | 0.00 | 0.00 | 91857287.83 | 0.288686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247868E+11 | 0.00 | 0.00 | 0.00 | 0.233460E+11 | 0.243525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.402286E+10 | 0.00 | 0.00 | 0.00 | 0.801120E+10 | 0.943791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.154102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130226E+10 | 0.00 | 0.00 | 0.00 | 56310041.75 | 0.968663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147369E+10 | 0.00 | 0.00 | 0.00 | 87997391.86 | 0.394909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159392E+10 | 0.00 | 0.00 | 0.00 | 0.896723E+09 | 0.120942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208215E+10 | 0.00 | 0.00 | 0.00 | 0.184406E+10 | 0.162046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.254753E+10 | 0.00 | 0.00 | 0.00 | 0.341446E+10 | 7464962.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.323359E+10 | 0.00 | 0.00 | 0.00 | 0.644312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.367263E+10 | 0.00 | 0.00 | 0.00 | 0.855006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.228244E+10 | 0.00 | 0.00 | 0.00 | 0.300787E+10 | 58675390.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149228E+10 | 0.00 | 0.00 | 0.00 | 0.366901E+09 | 0.180974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128118E+10 | 0.00 | 0.00 | 0.00 | 96726631.30 | 0.778795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238793E+11 | 0.00 | 0.00 | 0.00 | 0.247642E+11 | 0.563387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.367263E+10 | 0.00 | 0.00 | 0.00 | 0.855006E+10 | 0.175001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.751883E+10 | 0.00 | 0.00 | 8363539.92 | 0.00 | 0.190892E+09 | 0.508419E+10 | 0.00 | 0.30 |
February | 0.534718E+10 | 0.00 | 0.00 | 14559650.49 | 0.00 | 0.00 | 0.740029E+10 | 0.00 | 0.36 |
March | 0.270248E+10 | 0.00 | 0.00 | 26861679.08 | 0.00 | 0.00 | 0.148302E+11 | 0.00 | 0.50 |
April | 0.104768E+10 | 7875998.64 | 0.00 | 32250698.12 | 5385679.04 | 0.00 | 0.167199E+11 | 0.00 | 0.63 |
May | 0.118316E+10 | 9504244.25 | 0.00 | 43702178.99 | 0.00 | 0.00 | 0.208874E+11 | 0.00 | 0.93 |
June | 0.102923E+10 | 10534293.94 | 0.00 | 45935084.42 | 2081064.23 | 0.00 | 0.200456E+11 | 0.00 | 1.12 |
July | 0.916865E+09 | 0.140849E+09 | 0.00 | 40551409.04 | 15798582.76 | 0.00 | 0.145225E+11 | 0.00 | 1.08 |
August | 0.877980E+09 | 0.424594E+09 | 0.00 | 41559572.47 | 14441999.48 | 0.00 | 0.127196E+11 | 0.00 | 1.06 |
September | 0.105845E+10 | 7488510.10 | 0.00 | 43031796.61 | 0.00 | 0.00 | 0.184943E+11 | 0.00 | 1.04 |
October | 0.142783E+10 | 0.00 | 0.00 | 34559364.52 | 0.00 | 0.00 | 0.185061E+11 | 0.00 | 0.70 |
November | 0.347134E+10 | 0.00 | 0.00 | 20909341.36 | 0.00 | 0.00 | 0.113247E+11 | 0.00 | 0.42 |
December | 0.618296E+10 | 0.00 | 0.00 | 14510079.66 | 0.00 | 0.00 | 0.713789E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.327640E+11 | 0.600845E+09 | 0.00 | 0.366794E+09 | 37707325.51 | 0.190892E+09 | 0.167673E+12 | 0.00 | 0.71 |
Minimum of Months | 0.877980E+09 | 0.00 | 0.00 | 8363539.92 | 0.00 | 0.00 | 0.508419E+10 | 0.00 | 0.30 |
Maximum of Months | 0.751883E+10 | 0.424594E+09 | 0.00 | 45935084.42 | 15798582.76 | 0.190892E+09 | 0.208874E+11 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655694E+09 | 0.00 | 0.00 | 0.28 |
February | 0.101333E+11 | 0.00 | 0.00 | 112028.63 | 0.00 | 59034841.22 | 0.307973E+09 | 0.00 | 0.31 |
March | 0.938699E+10 | 0.00 | 0.00 | 1860679.63 | 0.00 | 3707951.02 | 0.280167E+10 | 0.00 | 0.35 |
April | 0.574842E+10 | 4705442.03 | 0.00 | 8324412.04 | 6924495.16 | 0.00 | 0.591275E+10 | 0.00 | 0.41 |
May | 0.362330E+10 | 5219383.15 | 0.00 | 19172940.39 | 0.00 | 0.00 | 0.106223E+11 | 0.00 | 0.61 |
June | 0.185903E+10 | 5262028.87 | 0.00 | 25059134.89 | 2171671.50 | 0.00 | 0.120804E+11 | 0.00 | 0.75 |
July | 0.126375E+10 | 89718409.93 | 0.00 | 24729975.59 | 8731878.58 | 0.00 | 0.907371E+10 | 0.00 | 0.73 |
August | 0.116170E+10 | 0.275474E+09 | 0.00 | 24938924.28 | 8443396.14 | 0.00 | 0.792925E+10 | 0.00 | 0.72 |
September | 0.259997E+10 | 92330.77 | 0.00 | 20715930.23 | 5039112.92 | 0.00 | 0.964792E+10 | 0.00 | 0.67 |
October | 0.619584E+10 | 0.00 | 0.00 | 8544361.19 | 0.00 | 0.00 | 0.598204E+10 | 0.00 | 0.43 |
November | 0.949855E+10 | 0.00 | 0.00 | 786617.76 | 0.00 | 15423437.01 | 0.120354E+10 | 0.00 | 0.31 |
December | 0.111895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127225E+09 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.736614E+11 | 0.380472E+09 | 0.00 | 0.134245E+09 | 31310554.31 | 0.861086E+09 | 0.655616E+11 | 0.00 | 0.49 |
Minimum of Months | 0.116170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.111895E+11 | 0.275474E+09 | 0.00 | 25059134.89 | 8731878.58 | 0.655694E+09 | 0.120804E+11 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.898101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198131E+10 | 0.00 | 0.00 | 0.27 |
February | 0.901555E+10 | 0.00 | 0.00 | 19348.22 | 0.00 | 0.793462E+09 | 0.111034E+09 | 0.00 | 0.30 |
March | 0.105721E+11 | 0.00 | 0.00 | 450611.56 | 0.00 | 0.101692E+09 | 0.998899E+09 | 0.00 | 0.35 |
April | 0.723302E+10 | 707977.11 | 0.00 | 5036041.15 | 334155.56 | 6937257.01 | 0.401394E+10 | 0.00 | 0.41 |
May | 0.475393E+10 | 1716635.88 | 0.00 | 14995115.46 | 0.00 | 0.00 | 0.897539E+10 | 0.00 | 0.59 |
June | 0.303287E+10 | 1652289.77 | 0.00 | 21276700.14 | 1426523.25 | 0.00 | 0.105310E+11 | 0.00 | 0.74 |
July | 0.207072E+10 | 73174468.63 | 0.00 | 21121318.22 | 11783803.87 | 0.00 | 0.803675E+10 | 0.00 | 0.74 |
August | 0.177612E+10 | 0.208953E+09 | 0.00 | 20654684.50 | 22756741.21 | 0.00 | 0.641027E+10 | 0.00 | 0.71 |
September | 0.420228E+10 | 0.00 | 0.00 | 13865031.41 | 1673931.37 | 0.00 | 0.682778E+10 | 0.00 | 0.63 |
October | 0.805075E+10 | 0.00 | 0.00 | 3468429.56 | 0.00 | 21481213.29 | 0.287457E+10 | 0.00 | 0.41 |
November | 0.952637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323366E+09 | 0.00 | 0.00 | 0.31 |
December | 0.918965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130402E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.784044E+11 | 0.286205E+09 | 0.00 | 0.100887E+09 | 37975155.26 | 0.453228E+10 | 0.487797E+11 | 0.00 | 0.48 |
Minimum of Months | 0.177612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.105721E+11 | 0.208953E+09 | 0.00 | 21276700.14 | 22756741.21 | 0.198131E+10 | 0.105310E+11 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.493658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186656E+10 | 0.00 | 0.00 | 0.28 |
February | 0.908142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121055E+10 | 0.00 | 0.00 | 0.31 |
March | 0.199373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474697E+09 | 0.00 | 0.00 | 0.35 |
April | 0.173191E+10 | 196411.23 | 0.00 | 739963.12 | 70456.16 | 0.145205E+09 | 0.469006E+09 | 0.00 | 0.41 |
May | 0.133963E+10 | 616102.20 | 0.00 | 3038435.83 | 0.00 | 7747600.57 | 0.164265E+10 | 0.00 | 0.63 |
June | 0.798507E+09 | 492978.07 | 0.00 | 4880788.76 | 300780.11 | 0.00 | 0.221377E+10 | 0.00 | 0.82 |
July | 0.528415E+09 | 22434755.84 | 0.00 | 5226502.62 | 2484595.91 | 0.00 | 0.182769E+10 | 0.00 | 0.87 |
August | 0.546427E+09 | 62757639.94 | 0.00 | 4421207.84 | 4798221.92 | 0.00 | 0.123331E+10 | 0.00 | 0.78 |
September | 0.126526E+10 | 352945.71 | 0.00 | 2288805.22 | 0.00 | 3456624.88 | 0.101334E+10 | 0.00 | 0.63 |
October | 0.188180E+10 | 0.00 | 0.00 | 227862.86 | 0.00 | 0.185683E+09 | 0.189090E+09 | 0.00 | 0.39 |
November | 0.113102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.958893E+09 | 0.00 | 0.00 | 0.31 |
December | 0.565339E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168236E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.131838E+11 | 86850832.98 | 0.00 | 20823566.26 | 7654054.09 | 0.653515E+10 | 0.858885E+10 | 0.00 | 0.51 |
Minimum of Months | 0.493658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.199373E+10 | 62757639.94 | 0.00 | 5226502.62 | 4798221.92 | 0.186656E+10 | 0.221377E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.607272E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151030E+10 | 0.00 | 0.00 | 0.39 |
February | 0.976830E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936039E+09 | 0.00 | 0.00 | 0.44 |
March | 0.178029E+10 | 0.00 | 0.00 | 161487.76 | 0.00 | 0.314614E+09 | 0.159147E+09 | 0.00 | 0.51 |
April | 0.113433E+10 | 172542.97 | 0.00 | 1964243.64 | 64215.59 | 81717748.11 | 0.119290E+10 | 0.00 | 0.67 |
May | 0.105680E+10 | 576990.59 | 0.00 | 3768454.74 | 0.00 | 10004208.50 | 0.198158E+10 | 0.00 | 1.00 |
June | 0.627791E+09 | 345350.79 | 0.00 | 5875280.27 | 274138.86 | 668303.17 | 0.276877E+10 | 0.00 | 1.40 |
July | 0.455040E+09 | 18309294.49 | 0.00 | 6131822.44 | 2171598.33 | 0.00 | 0.203083E+10 | 0.00 | 1.40 |
August | 0.391471E+09 | 55670802.37 | 0.00 | 5867459.47 | 2121419.79 | 0.00 | 0.154206E+10 | 0.00 | 1.36 |
September | 0.103513E+10 | 402059.53 | 0.00 | 3407934.96 | 0.00 | 2500721.29 | 0.143615E+10 | 0.00 | 1.08 |
October | 0.147408E+10 | 0.00 | 0.00 | 724275.58 | 0.00 | 0.142714E+09 | 0.546230E+09 | 0.00 | 0.60 |
November | 0.111057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.786345E+09 | 0.00 | 0.00 | 0.44 |
December | 0.688108E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133823E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.113377E+11 | 75477040.74 | 0.00 | 27900958.88 | 4631372.56 | 0.512314E+10 | 0.116577E+11 | 0.00 | 0.81 |
Minimum of Months | 0.391471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.178029E+10 | 55670802.37 | 0.00 | 6131822.44 | 2171598.33 | 0.151030E+10 | 0.276877E+10 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131686E+10 | 0.00 | 0.00 | 217508.41 | 0.00 | 0.186219E+10 | 0.114725E+09 | 0.00 | 0.39 |
February | 0.143292E+10 | 0.00 | 0.00 | 1392695.48 | 0.00 | 0.108454E+10 | 0.714024E+09 | 0.00 | 0.47 |
March | 0.202516E+10 | 0.00 | 0.00 | 3233222.73 | 0.00 | 0.455064E+09 | 0.183461E+10 | 0.00 | 0.62 |
April | 0.170150E+10 | 734922.82 | 0.00 | 4573312.36 | 0.00 | 0.166863E+09 | 0.245214E+10 | 0.00 | 0.79 |
May | 0.168640E+10 | 1175612.32 | 0.00 | 6409901.46 | 0.00 | 17407901.93 | 0.322084E+10 | 0.00 | 1.04 |
June | 0.128097E+10 | 636083.84 | 0.00 | 7127169.96 | 422326.25 | 1029558.42 | 0.315249E+10 | 0.00 | 1.21 |
July | 0.874722E+09 | 40445248.32 | 0.00 | 7784484.84 | 741563.85 | 0.00 | 0.261784E+10 | 0.00 | 1.32 |
August | 0.801504E+09 | 0.124533E+09 | 0.00 | 7399617.28 | 1171488.63 | 0.00 | 0.191153E+10 | 0.00 | 1.27 |
September | 0.146546E+10 | 1958774.30 | 0.00 | 8426074.41 | 0.00 | 4127961.95 | 0.311747E+10 | 0.00 | 1.39 |
October | 0.184523E+10 | 0.00 | 0.00 | 4599546.64 | 0.00 | 0.178540E+09 | 0.250894E+10 | 0.00 | 0.83 |
November | 0.170750E+10 | 0.00 | 0.00 | 721494.28 | 0.00 | 0.103333E+10 | 0.288637E+09 | 0.00 | 0.47 |
December | 0.124312E+10 | 0.00 | 0.00 | 693544.95 | 0.00 | 0.162748E+10 | 0.345739E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.173813E+11 | 0.169484E+09 | 0.00 | 52578572.79 | 2335378.73 | 0.643058E+10 | 0.222790E+11 | 0.00 | 0.85 |
Minimum of Months | 0.801504E+09 | 0.00 | 0.00 | 217508.41 | 0.00 | 0.00 | 0.114725E+09 | 0.00 | 0.39 |
Maximum of Months | 0.202516E+10 | 0.124533E+09 | 0.00 | 8426074.41 | 1171488.63 | 0.186219E+10 | 0.322084E+10 | 0.00 | 1.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.617810E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174359E+10 | 0.00 | 0.00 | 0.44 |
February | 0.956292E+09 | 0.00 | 0.00 | 59229.40 | 0.00 | 0.113158E+10 | 51442634.30 | 0.00 | 0.49 |
March | 0.181602E+10 | 0.00 | 0.00 | 480862.61 | 0.00 | 0.449332E+09 | 0.338255E+09 | 0.00 | 0.59 |
April | 0.157420E+10 | 377648.69 | 0.00 | 1792124.74 | 0.00 | 0.144238E+09 | 0.953535E+09 | 0.00 | 0.76 |
May | 0.140998E+10 | 477476.68 | 0.00 | 4336981.63 | 0.00 | 17577568.21 | 0.185633E+10 | 0.00 | 1.14 |
June | 0.102507E+10 | 1171704.73 | 0.00 | 4742091.39 | 306314.33 | 746741.40 | 0.194746E+10 | 0.00 | 1.36 |
July | 0.647699E+09 | 37832440.64 | 0.00 | 6487749.80 | 1156871.27 | 0.00 | 0.180258E+10 | 0.00 | 1.54 |
August | 0.643782E+09 | 80626109.10 | 0.00 | 4614508.66 | 3687760.60 | 0.00 | 0.111451E+10 | 0.00 | 1.25 |
September | 0.133692E+10 | 602121.04 | 0.00 | 3456796.83 | 0.00 | 7195498.00 | 0.124291E+10 | 0.00 | 1.20 |
October | 0.176761E+10 | 0.00 | 0.00 | 802148.04 | 0.00 | 0.188485E+09 | 0.493069E+09 | 0.00 | 0.69 |
November | 0.115951E+10 | 0.00 | 0.00 | 20034.99 | 0.00 | 0.956829E+09 | 2076490.27 | 0.00 | 0.50 |
December | 0.682440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157810E+10 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.136373E+11 | 0.121088E+09 | 0.00 | 26792528.10 | 5150946.20 | 0.621768E+10 | 0.980216E+10 | 0.00 | 0.87 |
Minimum of Months | 0.617810E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.181602E+10 | 80626109.10 | 0.00 | 6487749.80 | 3687760.60 | 0.174359E+10 | 0.194746E+10 | 0.00 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.840117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175950E+10 | 0.00 | 0.00 | 0.28 |
February | 0.130767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102952E+10 | 0.00 | 0.00 | 0.31 |
March | 0.246846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211341E+09 | 0.00 | 0.00 | 0.36 |
April | 0.228494E+10 | 914924.58 | 0.00 | 121145.53 | 1133555.83 | 36492021.25 | 71712570.53 | 0.00 | 0.39 |
May | 0.168903E+10 | 1707503.66 | 0.00 | 1491313.74 | 0.00 | 0.00 | 0.936915E+09 | 0.00 | 0.54 |
June | 0.950097E+09 | 1492598.70 | 0.00 | 3411360.42 | 438013.94 | 0.00 | 0.159491E+10 | 0.00 | 0.68 |
July | 0.599153E+09 | 24645759.35 | 0.00 | 4047388.23 | 3325221.49 | 0.00 | 0.142997E+10 | 0.00 | 0.72 |
August | 0.653154E+09 | 73513403.32 | 0.00 | 3531241.57 | 3039693.35 | 0.00 | 0.108770E+10 | 0.00 | 0.68 |
September | 0.137015E+10 | 87214.75 | 0.00 | 1977548.95 | 1253119.43 | 0.00 | 0.947113E+09 | 0.00 | 0.60 |
October | 0.230779E+10 | 0.00 | 0.00 | 242414.60 | 0.00 | 7162270.41 | 0.243742E+09 | 0.00 | 0.42 |
November | 0.197510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412789E+09 | 0.00 | 0.00 | 0.32 |
December | 0.119396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131584E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.176396E+11 | 0.102361E+09 | 0.00 | 14822413.05 | 9189604.05 | 0.477264E+10 | 0.631206E+10 | 0.00 | 0.47 |
Minimum of Months | 0.599153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.246846E+10 | 73513403.32 | 0.00 | 4047388.23 | 3325221.49 | 0.175950E+10 | 0.159491E+10 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.769805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119230E+10 | 0.00 | 0.00 | 0.34 |
February | 0.110701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656917E+09 | 0.00 | 0.00 | 0.37 |
March | 0.183754E+10 | 0.00 | 0.00 | 78798.99 | 0.00 | 99120313.48 | 86604186.04 | 0.00 | 0.43 |
April | 0.115039E+10 | 1212914.99 | 0.00 | 1472117.48 | 855091.98 | 12383060.50 | 0.859691E+09 | 0.00 | 0.54 |
May | 0.910835E+09 | 1948657.62 | 0.00 | 2959480.46 | 0.00 | 0.00 | 0.151010E+10 | 0.00 | 0.81 |
June | 0.467400E+09 | 1316011.00 | 0.00 | 5179997.60 | 330413.55 | 0.00 | 0.230430E+10 | 0.00 | 1.17 |
July | 0.367570E+09 | 26362696.88 | 0.00 | 5201330.36 | 2426901.60 | 0.00 | 0.170492E+10 | 0.00 | 1.17 |
August | 0.333782E+09 | 77681097.75 | 0.00 | 5315873.04 | 1160014.90 | 0.00 | 0.147744E+10 | 0.00 | 1.19 |
September | 0.802443E+09 | 1320572.36 | 0.00 | 3521765.10 | 0.00 | 0.00 | 0.146902E+10 | 0.00 | 0.98 |
October | 0.141442E+10 | 0.00 | 0.00 | 1053299.94 | 0.00 | 4774458.94 | 0.685228E+09 | 0.00 | 0.55 |
November | 0.151488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287647E+09 | 0.00 | 0.00 | 0.38 |
December | 0.990692E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904762E+09 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.116668E+11 | 0.109842E+09 | 0.00 | 24782662.98 | 4772422.03 | 0.315790E+10 | 0.100973E+11 | 0.00 | 0.69 |
Minimum of Months | 0.333782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.183754E+10 | 77681097.75 | 0.00 | 5315873.04 | 2426901.60 | 0.119230E+10 | 0.230430E+10 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.396454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343231E+10 | 0.00 | 0.00 | 0.41 |
February | 0.109955E+10 | 0.00 | 0.00 | 76556.31 | 0.00 | 0.221783E+10 | 30661817.80 | 0.00 | 0.44 |
March | 0.176092E+10 | 0.00 | 0.00 | 403294.16 | 0.00 | 0.169924E+10 | 0.287792E+09 | 0.00 | 0.50 |
April | 0.185598E+10 | 5409477.46 | 0.00 | 955756.62 | 0.00 | 0.944145E+09 | 0.416655E+09 | 0.00 | 0.55 |
May | 0.203608E+10 | 3693633.14 | 0.00 | 1655070.96 | 0.00 | 0.608124E+09 | 0.708006E+09 | 0.00 | 0.71 |
June | 0.168966E+10 | 2338152.03 | 0.00 | 2615946.67 | 499500.75 | 0.355540E+09 | 0.912153E+09 | 0.00 | 0.82 |
July | 0.999576E+09 | 54404213.46 | 0.00 | 4137685.63 | 3684782.59 | 0.152757E+09 | 0.117549E+10 | 0.00 | 0.91 |
August | 0.978197E+09 | 0.179638E+09 | 0.00 | 4390373.54 | 2098223.54 | 0.128516E+09 | 0.972885E+09 | 0.00 | 0.96 |
September | 0.142590E+10 | 5748576.84 | 0.00 | 5209663.87 | 0.00 | 0.335304E+09 | 0.164706E+10 | 0.00 | 1.07 |
October | 0.190536E+10 | 0.00 | 0.00 | 1968008.50 | 0.00 | 0.758811E+09 | 0.117874E+10 | 0.00 | 0.66 |
November | 0.130581E+10 | 0.00 | 0.00 | 172817.27 | 0.00 | 0.206154E+10 | 30141735.76 | 0.00 | 0.46 |
December | 0.615557E+09 | 0.00 | 0.00 | 85485.87 | 0.00 | 0.298248E+10 | 63780756.77 | 0.00 | 0.40 |
Annual Sum or Average | 0.160690E+11 | 0.251232E+09 | 0.00 | 21670659.39 | 6282506.88 | 0.156766E+11 | 0.742337E+10 | 0.00 | 0.66 |
Minimum of Months | 0.396454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128516E+09 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.203608E+10 | 0.179638E+09 | 0.00 | 5209663.87 | 3684782.59 | 0.343231E+10 | 0.164706E+10 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.776994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142540E+10 | 0.00 | 0.00 | 0.38 |
February | 0.124409E+10 | 0.00 | 0.00 | 23665.24 | 0.00 | 0.715106E+09 | 23330336.16 | 0.00 | 0.42 |
March | 0.199817E+10 | 0.00 | 0.00 | 218253.41 | 0.00 | 0.150708E+09 | 0.151459E+09 | 0.00 | 0.49 |
April | 0.158838E+10 | 1768626.93 | 0.00 | 1067930.73 | 575111.18 | 26249305.01 | 0.543659E+09 | 0.00 | 0.59 |
May | 0.119671E+10 | 1692560.28 | 0.00 | 3063146.07 | 0.00 | 184096.97 | 0.134030E+10 | 0.00 | 0.89 |
June | 0.770147E+09 | 3571154.52 | 0.00 | 3951483.68 | 371436.24 | 0.00 | 0.159306E+10 | 0.00 | 1.09 |
July | 0.422218E+09 | 44853063.65 | 0.00 | 5154286.79 | 623616.36 | 0.00 | 0.160591E+10 | 0.00 | 1.27 |
August | 0.464934E+09 | 0.100146E+09 | 0.00 | 4313952.16 | 2172072.84 | 0.00 | 0.114521E+10 | 0.00 | 1.08 |
September | 0.961189E+09 | 1745478.03 | 0.00 | 3401024.73 | 0.00 | 0.00 | 0.129838E+10 | 0.00 | 1.04 |
October | 0.177116E+10 | 0.00 | 0.00 | 842344.42 | 0.00 | 4948820.09 | 0.531354E+09 | 0.00 | 0.61 |
November | 0.168682E+10 | 0.00 | 0.00 | 12953.78 | 0.00 | 0.334161E+09 | 5038714.49 | 0.00 | 0.43 |
December | 0.109491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103414E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.139757E+11 | 0.153777E+09 | 0.00 | 22049041.01 | 3742236.62 | 0.369090E+10 | 0.823771E+10 | 0.00 | 0.72 |
Minimum of Months | 0.422218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.199817E+10 | 0.100146E+09 | 0.00 | 5154286.79 | 2172072.84 | 0.142540E+10 | 0.160591E+10 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.951002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152050E+10 | 0.00 | 0.00 | 0.28 |
February | 0.141601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802390E+09 | 0.00 | 0.00 | 0.31 |
March | 0.241440E+10 | 0.00 | 0.00 | 3298.92 | 0.00 | 0.135524E+09 | 18403423.71 | 0.00 | 0.35 |
April | 0.178218E+10 | 1314223.25 | 0.00 | 932999.43 | 1457996.83 | 30184021.61 | 0.577339E+09 | 0.00 | 0.40 |
May | 0.112847E+10 | 1803292.87 | 0.00 | 3687953.79 | 0.00 | 0.00 | 0.186709E+10 | 0.00 | 0.64 |
June | 0.607753E+09 | 1639639.50 | 0.00 | 5520455.56 | 457259.35 | 0.00 | 0.240871E+10 | 0.00 | 0.82 |
July | 0.438985E+09 | 27917896.11 | 0.00 | 5554734.71 | 1838552.99 | 0.00 | 0.189398E+10 | 0.00 | 0.85 |
August | 0.439481E+09 | 83373001.23 | 0.00 | 4878678.27 | 1777811.16 | 0.00 | 0.146145E+10 | 0.00 | 0.78 |
September | 0.107791E+10 | 1084637.95 | 0.00 | 3031345.52 | 0.00 | 0.00 | 0.131694E+10 | 0.00 | 0.65 |
October | 0.201067E+10 | 0.00 | 0.00 | 483839.56 | 0.00 | 24136490.34 | 0.376242E+09 | 0.00 | 0.40 |
November | 0.176578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494217E+09 | 0.00 | 0.00 | 0.31 |
December | 0.112564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126876E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.151583E+11 | 0.117133E+09 | 0.00 | 24093305.76 | 5531620.34 | 0.427571E+10 | 0.992015E+10 | 0.00 | 0.51 |
Minimum of Months | 0.438985E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.241440E+10 | 83373001.23 | 0.00 | 5554734.71 | 1838552.99 | 0.152050E+10 | 0.240871E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.960266E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135295E+10 | 0.00 | 0.00 | 0.41 |
February | 0.140543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676029E+09 | 0.00 | 0.00 | 0.45 |
March | 0.211755E+10 | 0.00 | 0.00 | 309756.47 | 0.00 | 91060178.25 | 0.238072E+09 | 0.00 | 0.53 |
April | 0.126574E+10 | 1132472.10 | 0.00 | 2233327.63 | 1369191.94 | 16141026.30 | 0.127661E+10 | 0.00 | 0.69 |
May | 0.101845E+10 | 1622856.17 | 0.00 | 3986364.04 | 0.00 | 208101.03 | 0.203484E+10 | 0.00 | 1.01 |
June | 0.566996E+09 | 1117716.43 | 0.00 | 6040631.19 | 429408.22 | 0.00 | 0.278741E+10 | 0.00 | 1.37 |
July | 0.426013E+09 | 23093232.31 | 0.00 | 6129664.98 | 1705356.80 | 0.00 | 0.201433E+10 | 0.00 | 1.35 |
August | 0.383438E+09 | 71675849.54 | 0.00 | 5989251.77 | 777126.03 | 0.00 | 0.167131E+10 | 0.00 | 1.32 |
September | 0.100504E+10 | 1158990.92 | 0.00 | 3740106.23 | 0.00 | 0.00 | 0.160918E+10 | 0.00 | 1.10 |
October | 0.168843E+10 | 0.00 | 0.00 | 1025288.68 | 0.00 | 22658847.99 | 0.699079E+09 | 0.00 | 0.63 |
November | 0.164500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477640E+09 | 0.00 | 0.00 | 0.46 |
December | 0.111327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113153E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.135956E+11 | 99801117.47 | 0.00 | 29454391.00 | 4281082.99 | 0.376821E+10 | 0.123308E+11 | 0.00 | 0.81 |
Minimum of Months | 0.383438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.211755E+10 | 71675849.54 | 0.00 | 6129664.98 | 1705356.80 | 0.135295E+10 | 0.278741E+10 | 0.00 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.172337E+10 | 0.00 | 0.00 | 306705.94 | 0.00 | 0.141404E+10 | 0.201738E+09 | 0.00 | 0.38 |
February | 0.185140E+10 | 0.00 | 0.00 | 1755433.22 | 0.00 | 0.611822E+09 | 0.880048E+09 | 0.00 | 0.47 |
March | 0.232763E+10 | 0.00 | 0.00 | 3849214.65 | 0.00 | 0.116560E+09 | 0.199132E+10 | 0.00 | 0.62 |
April | 0.169417E+10 | 8102049.57 | 0.00 | 4910565.22 | 11685.06 | 37843702.93 | 0.252215E+10 | 0.00 | 0.77 |
May | 0.141616E+10 | 3380607.40 | 0.00 | 6909618.76 | 0.00 | 295790.41 | 0.327809E+10 | 0.00 | 1.03 |
June | 0.101465E+10 | 2062394.20 | 0.00 | 7616481.81 | 610351.78 | 0.00 | 0.317224E+10 | 0.00 | 1.17 |
July | 0.708950E+09 | 47600830.38 | 0.00 | 7772588.37 | 2299568.31 | 0.00 | 0.251280E+10 | 0.00 | 1.24 |
August | 0.671838E+09 | 0.158716E+09 | 0.00 | 7416281.74 | 1298114.77 | 0.00 | 0.201871E+10 | 0.00 | 1.19 |
September | 0.121681E+10 | 5824434.04 | 0.00 | 9005588.86 | 0.00 | 0.00 | 0.324555E+10 | 0.00 | 1.38 |
October | 0.192150E+10 | 0.00 | 0.00 | 5464048.71 | 0.00 | 25446641.54 | 0.280374E+10 | 0.00 | 0.85 |
November | 0.232305E+10 | 0.00 | 0.00 | 973493.59 | 0.00 | 0.434082E+09 | 0.415608E+09 | 0.00 | 0.46 |
December | 0.177042E+10 | 0.00 | 0.00 | 1035603.12 | 0.00 | 0.111018E+10 | 0.492670E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.186400E+11 | 0.225686E+09 | 0.00 | 57015624.00 | 4219719.92 | 0.375027E+10 | 0.235347E+11 | 0.00 | 0.83 |
Minimum of Months | 0.671838E+09 | 0.00 | 0.00 | 306705.94 | 0.00 | 0.00 | 0.201738E+09 | 0.00 | 0.38 |
Maximum of Months | 0.232763E+10 | 0.158716E+09 | 0.00 | 9005588.86 | 2299568.31 | 0.141404E+10 | 0.327809E+10 | 0.00 | 1.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138085E+10 | 0.00 | 0.00 | 0.43 |
February | 0.143312E+10 | 0.00 | 0.00 | 88821.06 | 0.00 | 0.660242E+09 | 70744600.00 | 0.00 | 0.47 |
March | 0.208516E+10 | 0.00 | 0.00 | 579052.06 | 0.00 | 0.142770E+09 | 0.379200E+09 | 0.00 | 0.57 |
April | 0.160083E+10 | 3247407.45 | 0.00 | 1865159.04 | 468547.66 | 30336884.67 | 0.961330E+09 | 0.00 | 0.72 |
May | 0.113549E+10 | 1506422.40 | 0.00 | 4628490.91 | 0.00 | 215861.30 | 0.194279E+10 | 0.00 | 1.10 |
June | 0.778145E+09 | 3917967.85 | 0.00 | 5151881.00 | 445421.22 | 0.00 | 0.200453E+10 | 0.00 | 1.29 |
July | 0.502634E+09 | 45632847.91 | 0.00 | 5881896.48 | 276029.74 | 0.00 | 0.175323E+10 | 0.00 | 1.43 |
August | 0.550985E+09 | 0.106089E+09 | 0.00 | 4763096.45 | 1624543.11 | 0.00 | 0.119152E+10 | 0.00 | 1.18 |
September | 0.107954E+10 | 1859208.36 | 0.00 | 3853669.15 | 0.00 | 0.00 | 0.143320E+10 | 0.00 | 1.17 |
October | 0.188989E+10 | 0.00 | 0.00 | 984805.18 | 0.00 | 28484763.14 | 0.588095E+09 | 0.00 | 0.68 |
November | 0.171538E+10 | 0.00 | 0.00 | 28493.80 | 0.00 | 0.467715E+09 | 18692732.53 | 0.00 | 0.48 |
December | 0.120051E+10 | 0.00 | 0.00 | 7.93 | 0.00 | 0.112633E+10 | 1007338.25 | 0.00 | 0.42 |
Annual Sum or Average | 0.149895E+11 | 0.162253E+09 | 0.00 | 27825373.06 | 2814541.73 | 0.383694E+10 | 0.103443E+11 | 0.00 | 0.83 |
Minimum of Months | 0.502634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.208516E+10 | 0.106089E+09 | 0.00 | 5881896.48 | 1624543.11 | 0.138085E+10 | 0.200453E+10 | 0.00 | 1.43 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.674478E+11 | 0.171502E+11 | 0.00 | 0.137971E+12 | 0.437033E+10 |
February | 0.129446E+12 | 0.153220E+11 | 0.00 | 0.147215E+12 | 0.347646E+10 |
March | 0.224168E+12 | 0.153145E+11 | 0.00 | 0.188022E+12 | 0.209157E+10 |
April | 0.343790E+12 | 0.134977E+11 | 0.00 | 0.211673E+12 | 0.130697E+11 |
May | 0.447058E+12 | 0.111695E+11 | 0.00 | 0.234954E+12 | 0.271537E+11 |
June | 0.448712E+12 | 0.895525E+10 | 0.00 | 0.223369E+12 | 0.507440E+11 |
July | 0.475103E+12 | 0.669927E+10 | 0.00 | 0.221684E+12 | 0.967555E+11 |
August | 0.374792E+12 | 0.514267E+10 | 0.00 | 0.173563E+12 | 0.129891E+12 |
September | 0.268978E+12 | 0.618542E+10 | 0.00 | 0.230476E+12 | 0.470070E+11 |
October | 0.173590E+12 | 0.121946E+11 | 0.00 | 0.221494E+12 | 0.588640E+10 |
November | 0.749651E+11 | 0.143502E+11 | 0.00 | 0.175345E+12 | 0.298934E+10 |
December | 0.533267E+11 | 0.154585E+11 | 0.00 | 0.153447E+12 | 0.338267E+10 |
Annual Sum or Average | 0.308138E+13 | 0.141440E+12 | 0.00 | 0.231921E+13 | 0.386818E+12 |
Minimum of Months | 0.533267E+11 | 0.514267E+10 | 0.00 | 0.137971E+12 | 0.209157E+10 |
Maximum of Months | 0.475103E+12 | 0.171502E+11 | 0.00 | 0.234954E+12 | 0.129891E+12 |