Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 08:35:11
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2001.55 | 401.74 | 401.74 |
Net Site Energy | 2001.55 | 401.74 | 401.74 |
Total Source Energy | 5602.36 | 1124.48 | 1124.48 |
Net Source Energy | 5602.36 | 1124.48 | 1124.48 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 290.04 | 241.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 137.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 92.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 112.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1647.95 | 353.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 290.04 | 241.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 137.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 280.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 71.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 92.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 112.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 290.04 | 241.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 137.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 280.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 71.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 92.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 112.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 104.41 | 70.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 330.77 | 70.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 104.41 | 70.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 330.77 | 70.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1647.951 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1647.951 | 100.00 |
Total On-Site and Utility Electric Sources | 1647.951 | 100.00 |
Total Electricity End Uses | 1647.951 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 556.17 |
Time Setpoint Not Met During Occupied Cooling | 54.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2845.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.5763 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 7.5763 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 7.5763 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 07-FEB-07:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 201180.70 | 109362.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 9359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21853.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 256.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7050.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8222.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 245258.45 | 117585.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 201180.70 | 109362.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 9359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 16082.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 256.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7050.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8222.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 918.55 | 261.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 436.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 889.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 227.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2413.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 41.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 292.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 121.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5219.06 | 383.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 184.37 | 52.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 87.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 178.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 58.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1047.54 | 76.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 184.37 | 52.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 87.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 178.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 58.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1047.54 | 76.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.87 | 0.261306 | 0.271000 | 0.777259 | 0.696815 | 0.500000 | 0.001458 |
CORE_MID VAV BOX COMPONENT | 2.09 | 0.357763 | 0.359000 | 0.752046 | 0.954035 | 0.500000 | 0.001065 |
CORE_TOP VAV BOX COMPONENT | 2.22 | 0.337498 | 0.353000 | 0.783878 | 0.899996 | 0.500000 | 0.001129 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.687943 | 0.229658 | 0.240000 | 0.165106 | 0.612421 | 0.500000 | 0.001659 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.779529 | 0.128311 | 0.200000 | 0.155906 | 0.342161 | 0.500000 | 0.002969 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.985455 | 0.160324 | 0.200000 | 0.197091 | 0.427530 | 0.500000 | 0.002376 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.862104 | 0.116013 | 0.200000 | 0.172421 | 0.309368 | 0.500000 | 0.003284 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.532311 | 0.296804 | 0.308000 | 0.163952 | 0.791476 | 0.500000 | 0.001284 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.634843 | 0.157554 | 0.200000 | 0.126969 | 0.420143 | 0.500000 | 0.002418 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.778527 | 0.202937 | 0.210000 | 0.163491 | 0.541165 | 0.500000 | 0.001877 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.669472 | 0.149394 | 0.200000 | 0.133894 | 0.398385 | 0.500000 | 0.002550 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.597865 | 0.264260 | 0.265000 | 0.158434 | 0.704693 | 0.500000 | 0.001442 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.757878 | 0.131976 | 0.200000 | 0.151576 | 0.351936 | 0.500000 | 0.002887 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.889114 | 0.177696 | 0.200000 | 0.177823 | 0.473855 | 0.500000 | 0.002144 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.790221 | 0.126566 | 0.200000 | 0.158044 | 0.337510 | 0.500000 | 0.003010 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25307.70 |
CORE_MID VAV BOX REHEAT COIL | 25542.31 |
CORE_TOP VAV BOX REHEAT COIL | 43541.19 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21393.32 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13888.84 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21377.93 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14006.01 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 15878.07 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10386.26 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 15878.05 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10484.64 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 16709.74 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10898.44 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 16691.93 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10999.30 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.74 | 1.37 | 5.48 | 2.04 | 4.89 | 4.89 | 0.300000 | 0.417194 | 4.89 |
PACU_VAV_MID | 2.56 | 1.40 | 5.13 | 2.48 | 4.36 | 4.36 | 0.300000 | 0.569197 | 4.36 |
PACU_VAV_TOP | 2.77 | 1.47 | 5.54 | 3.51 | 5.04 | 5.04 | 0.300000 | 0.695648 | 5.04 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.89 |
PACU_VAV_MID_OA_CONTROLLER | 4.36 |
PACU_VAV_TOP_OA_CONTROLLER | 5.04 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.89 | 101812.86 | 0.760437 | 1.63 | 33934.23 | 0.760437 |
PACU_VAV_MID COOLING COIL | 4.36 | 93710.33 | 0.749290 | 1.45 | 31233.65 | 0.749290 |
PACU_VAV_TOP COOLING COIL | 5.04 | 104805.28 | 0.761797 | 1.68 | 34931.60 | 0.761797 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 39076.08 |
PACU_VAV_MID HEATING COIL | 40397.21 |
PACU_VAV_TOP HEATING COIL | 39906.06 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.89 |
PACU_VAV_MID FAN | 4.36 |
PACU_VAV_TOP FAN | 5.04 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 32.411 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9320 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9163 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.269 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8390 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8573 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5538 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.27971961E-12 | 0.14534712E-14 | -0.84678956E-13 | 0.82684317E-16 |
43 | 6 | 0.26817376E-07 | 0.25687399E-09 | 0.61588016E-08 | -0.12527087E-12 |
44 | 5 | -0.18065003E-03 | 0.22251366E-05 | -0.93037841E-04 | 0.60936178E-08 |
45 | 4 | 0.28101542 | 0.10946024E-02 | 0.95683253E-01 | -0.32007147E-04 |
46 | 3 | -7.0457283 | 0.34231649E-01 | -2.2734647 | 0.27928366E-01 |
47 | 2 | 40.143429 | 0.12270019 | 14.996275 | -0.32523640 |
48 | 1 | -79.987958 | 0.55761501E-01 | -28.900564 | 1.0667320 |
49 | 0 | 46.824342 | 0.11295401E-02 | 16.297084 | |
50 | 7 | -0.28233695E-12 | 0.14433069E-14 | -0.85363548E-13 | 0.83491456E-16 |
51 | 6 | 0.27004714E-07 | 0.25312183E-09 | 0.62001510E-08 | -0.12627076E-12 |
52 | 5 | -0.18161011E-03 | 0.21898175E-05 | -0.93520278E-04 | 0.61339935E-08 |
53 | 4 | 0.28215201 | 0.10760039E-02 | 0.96091377E-01 | -0.32166146E-04 |
54 | 3 | -7.0682688 | 0.33616209E-01 | -2.2801509 | 0.28038740E-01 |
55 | 2 | 40.217804 | 0.12038787 | 15.023777 | -0.32606455 |
56 | 1 | -80.044990 | 0.54668782E-01 | -28.925243 | 1.0679473 |
57 | 0 | 46.824342 | 0.11065724E-02 | 16.296477 | |
58 | 6 | 0.22748378E-07 | 0.33059726E-09 | 0.52605359E-08 | -0.10371465E-12 |
59 | 5 | -0.15952455E-03 | 0.29533519E-05 | -0.82380770E-04 | 0.52144884E-08 |
60 | 4 | 0.25560578 | 0.14926938E-02 | 0.86578981E-01 | -0.28493712E-04 |
61 | 3 | -6.5408460 | 0.47808585E-01 | -2.1237636 | 0.25458881E-01 |
62 | 2 | 38.476406 | 0.17496760 | 14.378110 | -0.30668036 |
63 | 1 | -78.708466 | 0.80951212E-01 | -28.345189 | 1.0394692 |
64 | 0 | 46.824351 | 0.16689207E-02 | 16.311239 | |
65 | 7 | -0.18042418E-08 | -0.42925973E-15 | 0.63337540E-14 | -0.83764910E-16 |
66 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
67 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
68 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
69 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
70 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
71 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
72 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
73 | 7 | -0.17078159E-08 | -0.36552483E-15 | 0.71259391E-14 | -0.98899249E-16 |
74 | 6 | 0.68798867E-05 | 0.47165251E-08 | 0.31862110E-02 | -0.26728608E-04 |
75 | 5 | -0.49558197E-03 | 0.27953368E-05 | -0.22351660 | 0.19543146E-02 |
76 | 4 | 0.11404824E-01 | 0.12725100E-03 | 4.8260817 | -0.45231683E-01 |
77 | 3 | -0.10016651 | 0.10121065E-02 | -38.001848 | 0.39843745 |
78 | 2 | 0.35569192 | 0.16837830E-02 | 116.44586 | -1.4174299 |
79 | 1 | -0.51340120 | 0.51323984E-03 | -143.88489 | 2.0486714 |
80 | 0 | 0.25031121 | 0.12359947E-04 | 60.838472 | |
81 | 7 | -0.18042418E-08 | -0.42925997E-15 | 0.63337541E-14 | -0.83764912E-16 |
82 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
83 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
84 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
85 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
86 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
87 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
88 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
89 | 7 | -0.17076967E-08 | -0.36446083E-15 | 0.71390403E-14 | -0.94439575E-16 |
90 | 6 | 0.68803475E-05 | 0.47168467E-08 | 0.31862096E-02 | -0.26728597E-04 |
91 | 5 | -0.49561596E-03 | 0.27955299E-05 | -0.22351653 | 0.19543140E-02 |
92 | 4 | 0.11405612E-01 | 0.12725979E-03 | 4.8260805 | -0.45231671E-01 |
93 | 3 | -0.10017344 | 0.10121766E-02 | -38.001841 | 0.39843738 |
94 | 2 | 0.35571654 | 0.16838995E-02 | 116.44585 | -1.4174297 |
95 | 1 | -0.51343675 | 0.51327568E-03 | -143.88488 | 2.0486713 |
96 | 0 | 0.25032854 | 0.12360692E-04 | 60.838472 | |
97 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
98 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
99 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
100 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
101 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
102 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
103 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
104 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
105 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3822_SHGC_EAST_0.38 | 35 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 | ||
2 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 36 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 | ||
3 | WINDOW_U_0.3822_SHGC_WEST_0.38 | 37 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 | ||
4 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 38 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0218E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0276E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1321E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1370E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.8734E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9132E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6395E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6611E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1448 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8205E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1654 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.8925E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1020 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3739E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.2271E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5852E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0220E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0288E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1323E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1383E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.8751E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9219E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6393E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6609E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.6385E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8828E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.3759E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6483E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4773E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2595E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9184E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3003E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8423E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8656E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6031E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6199E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2277E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.2336E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2478E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2552E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8896E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9409E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2519E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2934E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8254E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8565E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6393E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6609E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.7074E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1830E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8685E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6668E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7493E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1641E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.2271E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5852E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8893E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9412E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2511E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2919E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8238E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8503E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6395E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6611E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5275E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3403E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9829E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9653E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5804E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8359E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9184E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3003E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1573E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2221E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7391E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.8103E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7008E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7275E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2479E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2553E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1430 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.3457E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1606 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1058 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1079 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.4558E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.7521E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.2047E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.3811E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.7385E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.1391E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.5161E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.2850E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.1552E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8008E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2370E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.1928E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.8098E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3033E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2075E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1825E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6626E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.7521E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2047E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.3124E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.2226E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.7995E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.8668E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.4201E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7511E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8008E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2371E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1430 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.3449E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1606 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1058 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1079 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.4552E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.7517E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.2044E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.3811E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.7383E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.1391E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.5158E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.2847E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.1549E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8004E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2368E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.1931E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.8097E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3034E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2074E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1823E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6624E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.7517E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2044E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.3125E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.2224E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.7996E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.8667E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.4199E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7508E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8005E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2369E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 38805.65381 | 38805.65381 | 2.86812 | 2.86812 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 9438.45410 | 9438.45410 | 0.41549 | 0.42469 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 28377.70348 | 28377.70348 | 2.09484 | 2.09484 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 18038.70739 | 18038.70739 | 0.78446 | 0.78446 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 29795.85587 | 29795.85587 | 2.22062 | 2.22062 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 30.11400 | 1.33666E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 30641.43463 | 30641.43463 | 1.33725 | 1.33725 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9229.97433 | 9229.97433 | 0.68794 | 0.68794 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 30.20700 | 1.33668E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 15016.75117 | 15016.75117 | 0.65704 | 0.65704 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10458.81711 | 10458.81711 | 0.77953 | 0.77953 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.23900 | 1.33598E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 9748.65673 | 9748.65673 | 0.42656 | 0.42656 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13221.67817 | 13221.67817 | 0.98545 | 0.98545 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 15005.97362 | 15005.97362 | 0.65657 | 0.65657 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11566.74084 | 11566.74084 | 0.86210 | 0.86210 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 9830.72860 | 9830.72860 | 0.43016 | 0.43016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7142.15125 | 7142.15125 | 0.53231 | 0.53231 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 11151.91144 | 11151.91144 | 0.48765 | 0.48765 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8517.92251 | 8517.92251 | 0.63484 | 0.63484 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 26.50250 | 1.33602E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 7294.14479 | 7294.14479 | 0.31899 | 0.31899 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10445.75257 | 10445.75257 | 0.77853 | 0.77853 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 30.22250 | 1.33668E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 11151.90000 | 11151.90000 | 0.48765 | 0.48765 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8982.56615 | 8982.56615 | 0.66947 | 0.66947 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 28.22300 | 1.33633E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 7363.05031 | 7363.05031 | 0.32201 | 0.32201 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8021.51202 | 8021.51202 | 0.59786 | 0.59786 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 11735.42824 | 11735.42824 | 0.51320 | 0.51320 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10168.47029 | 10168.47029 | 0.75788 | 0.75788 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.71200 | 1.33588E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 7653.54599 | 7653.54599 | 0.33472 | 0.33472 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11929.24782 | 11929.24782 | 0.88911 | 0.88911 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 11722.94897 | 11722.94897 | 0.51265 | 0.51265 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10602.42985 | 10602.42985 | 0.79022 | 0.79022 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 7724.18840 | 7724.18840 | 0.33781 | 0.33781 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 73495.89 | 4.89218 | 4.89218 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 40751.29 | 2.04099 | 2.04099 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 66415.78 | 4.36201 | 4.36201 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 40793.16 | 2.48284 | 2.48284 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 75285.56 | 5.04217 | 5.04217 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 40745.78 | 3.50758 | 3.50758 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.86812 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26131 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27100 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77726 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69682 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45806E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25307.70054 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.09484 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35776 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35900 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.75205 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.95403 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.06495E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25542.31177 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.22062 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33750 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35300 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78388 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12889E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 43541.19130 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68794 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22966 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16511 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61242 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.65899E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21393.31598 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77953 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12831 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15591 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34216 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.96936E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13888.84478 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.98545 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16032 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19709 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42753 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.37644E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21377.93150 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86210 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11601 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17242 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30937 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.28412E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14006.01067 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.53231 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29680 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30800 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16395 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79148 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.28368E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15878.06955 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63484 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15755 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12697 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42014 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.41822E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10386.25784 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77853 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20294 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16349 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54116 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.87743E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15878.05321 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66947 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14939 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13389 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39838 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.55030E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10484.64209 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59786 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26426 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26500 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15843 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70469 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44176E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16709.74473 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75788 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13198 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15158 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35194 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.88688E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10898.44431 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88911 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17770 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17782 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47385 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.14412E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16691.92946 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79022 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12657 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15804 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33751 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.01028E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10999.30158 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.74163 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.36556 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.48327 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.04099 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.89218 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.89218 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.41719 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.56496 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39792 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.12991 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.48284 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.36201 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.36201 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.56920 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.76782 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.47440 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.53565 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.50758 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.04217 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.04217 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.69565 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.89218 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.36201 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.04217 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.89218 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.89218 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 101812.86289 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.76044 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.63056 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 33934.22720 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.76044 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 39076.08253 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.89218 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.36201 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.36201 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 93710.33405 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74929 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.45386 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31233.65434 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74929 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 40397.21276 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.36201 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.04217 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.04217 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 104805.28203 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.76180 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.68056 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34931.60050 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.76180 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 39906.06025 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.04217 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 101033.98 | 344742.26 | 11.34 | 2.90 | 3.25 | 3.42 | 3.58 | 9.90 | 11.08 | 11.67 | 12.23 | 5.5163 | 4.3996 | 2.9622 | 1.2069 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 93102.36 | 317678.43 | 11.41 | 2.92 | 3.27 | 3.44 | 3.60 | 9.95 | 11.15 | 11.75 | 12.27 | 4.9184 | 3.9224 | 2.6408 | 1.0848 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 103998.72 | 354858.35 | 11.34 | 2.90 | 3.25 | 3.42 | 3.58 | 9.90 | 11.08 | 11.67 | 12.23 | 5.6854 | 4.5401 | 3.0580 | 1.2409 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.246 | 0.232 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.246 | 0.232 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.4302122039E-002 | 3.1460315783E-002 | Pass | Pass | 0.4982255156 | 0.4939146248 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1468220503 | 9.6338222170E-002 | Pass | Pass | 0.4975165779 | 0.4752660724 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.8849078343E-002 | 4.1659873817E-002 | Pass | Pass | 0.5009132751 | 0.4639313272 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.7274591638E-002 | 4.3158037406E-002 | Pass | Pass | 0.4944006840 | 0.4614698517 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.0782911850E-002 | 6.9549272048E-003 | Pass | Pass | 0.5150163132 | 0.5212853900 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 6.8040690916E-002 | 7.0911042420E-002 | Pass | Pass | 22.4924438049 | 51.1860562413 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3918022471 | 0.3893070503 | Pass | Pass | 16.2138765378 | 67.8608558370 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4147849955 | 0.4051260769 | Pass | Pass | 46.7872682214 | 250.7780795883 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3828186006 | 0.3814466009 | Pass | Pass | 32.8304052125 | 102.2736415981 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4169219701 | 0.4092705813 | Pass | Pass | 25.9210224668 | 79.4920000388 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2735986630 | 0.2559912859 | Pass | Pass | 17.3174536442 | 41.6222784577 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2823532741 | 0.2656035709 | Pass | Pass | 15.3432247029 | 36.7969892372 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2446497255 | 0.2374852487 | Pass | Pass | 15.9122666660 | 37.7308784088 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2839169250 | 0.2680388610 | Pass | Pass | 14.7886344889 | 35.4276072783 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2857609732 | 0.2726387033 | Pass | Pass | 33.4516696301 | 98.1186184258 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2921984519 | 0.2805048972 | Pass | Pass | 21.3840186616 | 68.0478486460 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2602371128 | 0.2584325397 | Pass | Pass | 40.0668105300 | 146.8625961403 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2943520903 | 0.2837316248 | Pass | Pass | 25.5431745144 | 92.8542010555 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3584.62 | 201.55 | 0.00 | 1715.84 | 749.76 | 6251.79 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3822_SHGC_EAST_0.38 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3822_SHGC_EAST_0.38 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3822_SHGC_WEST_0.38 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3822_SHGC_WEST_0.38 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.171 | 0.381 | 0.381 | |||||||||||||||||
North Total or Average | 177.99 | 2.171 | 0.381 | 0.381 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.171 | 0.381 | 0.381 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.38 | 0.0000 | Y | 9.25 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.31 | 0.0000 | Y | 5.84 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.19 | 0.0000 | Y | 9.20 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.28 | 0.0000 | Y | 5.84 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.34 | 0.0000 | Y | 9.24 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.28 | 0.0000 | Y | 5.84 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.16 | 0.0000 | Y | 9.19 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.25 | 0.0000 | Y | 5.83 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.38 | 0.0000 | Y | 9.25 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.31 | 0.0000 | Y | 5.84 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.19 | 0.0000 | Y | 9.20 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.28 | 0.0000 | Y | 5.84 |
Interior Lighting Total | 7.5763 | 4982.19 | 37746.71 | 280.82 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 42.04 | 42.04 | 3.35 | |
EXTERIOR_LIGHTS_B | 5132.60 | AstronomicalClock | - | 83.67 | 71.18 | 68.58 | |
Exterior Lighting Total | 5557.43 | 71.93 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 101812.86 | 77422.25 | 24390.61 | 0.76 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 93710.33 | 70216.18 | 23494.15 | 0.75 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 104805.28 | 79840.33 | 24964.95 | 0.76 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 101034.0 | 2.90 | 9.90 | N/A | N/A | 11.34 | |
PACU_VAV_MID COOLING COIL | 93102.4 | 2.92 | 9.95 | N/A | N/A | 11.41 | |
PACU_VAV_TOP COOLING COIL | 103998.7 | 2.90 | 9.90 | N/A | N/A | 11.34 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25307.70 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 25542.31 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 43541.19 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 21393.32 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13888.84 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 21377.93 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14006.01 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15878.07 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10386.26 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15878.05 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10484.64 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16709.74 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10898.44 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16691.93 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10999.30 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 39076.08 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 40397.21 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 39906.06 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.89 | 11244.50 | 2298.46 | 1.00 | 1.14 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.36 | 10091.01 | 2313.39 | 1.00 | 1.14 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.04 | 11589.24 | 2298.46 | 1.00 | 1.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 101033.98 | 2.90 | 9.90 | 11.34 | 5.5163 | 3.25 | 11.08 | 4.3996 | 3.42 | 11.67 | 2.9622 | 3.58 | 12.23 | 1.2069 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 93102.36 | 2.92 | 9.95 | 11.41 | 4.9184 | 3.27 | 11.15 | 3.9224 | 3.44 | 11.75 | 2.6408 | 3.60 | 12.27 | 1.0848 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 103998.72 | 2.90 | 9.90 | 11.34 | 5.6854 | 3.25 | 11.08 | 4.5401 | 3.42 | 11.67 | 3.0580 | 3.58 | 12.23 | 1.2409 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 38805.65 | 38805.65 | 39.46 | 2.868 | 2.868 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00881 | 23.42 | 0.01335 | 0.425 | 0.00 |
CORE_MID | 28377.70 | 28377.70 | 28.85 | 2.095 | 2.095 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 23.42 | 0.01335 | 0.425 | 0.00 |
CORE_TOP | 29795.86 | 29795.86 | 30.29 | 2.221 | 2.221 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00890 | 30.11 | 0.01337 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9229.97 | 9229.97 | 44.52 | 0.688 | 0.688 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00903 | 30.21 | 0.01337 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10458.82 | 10458.82 | 79.68 | 0.780 | 0.780 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00881 | 26.24 | 0.01336 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13221.68 | 13221.68 | 63.77 | 0.985 | 0.985 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00888 | 30.14 | 0.01337 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11566.74 | 11566.74 | 88.13 | 0.862 | 0.862 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00878 | 28.84 | 0.01336 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7142.15 | 7142.15 | 34.45 | 0.532 | 0.532 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00903 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8517.92 | 8517.92 | 64.89 | 0.635 | 0.635 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00879 | 26.50 | 0.01336 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10445.75 | 10445.75 | 50.38 | 0.779 | 0.779 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00887 | 30.22 | 0.01337 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8982.57 | 8982.57 | 68.44 | 0.669 | 0.669 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 24.00 | 24.00 | 0.00878 | 28.22 | 0.01336 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8021.51 | 8021.51 | 38.69 | 0.598 | 0.598 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00906 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10168.47 | 10168.47 | 77.47 | 0.758 | 0.758 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00880 | 25.71 | 0.01336 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11929.25 | 11929.25 | 57.54 | 0.889 | 0.889 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00888 | 30.07 | 0.01337 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10602.43 | 10602.43 | 80.78 | 0.790 | 0.790 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00878 | 28.84 | 0.01336 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 9438.45 | 9438.45 | 9.60 | 0.415 | 0.425 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
CORE_MID | 18038.71 | 18038.71 | 18.34 | 0.784 | 0.784 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
CORE_TOP | 30641.43 | 30641.43 | 31.15 | 1.337 | 1.337 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 15016.75 | 15016.75 | 72.43 | 0.657 | 0.657 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00755 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9748.66 | 9748.66 | 74.27 | 0.427 | 0.427 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15005.97 | 15005.97 | 72.37 | 0.657 | 0.657 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00755 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9830.73 | 9830.73 | 74.90 | 0.430 | 0.430 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 11151.91 | 11151.91 | 53.79 | 0.488 | 0.488 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7294.14 | 7294.14 | 55.57 | 0.319 | 0.319 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11151.90 | 11151.90 | 53.79 | 0.488 | 0.488 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7363.05 | 7363.05 | 56.10 | 0.322 | 0.322 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 11735.43 | 11735.43 | 56.60 | 0.513 | 0.513 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 7653.55 | 7653.55 | 58.31 | 0.335 | 0.335 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11722.95 | 11722.95 | 56.54 | 0.513 | 0.513 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 7724.19 | 7724.19 | 58.85 | 0.338 | 0.338 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -16.30 | 0.00092 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.89 | 4.89 | 2.04 | 2.04 | 4.8922 | 2.0410 | 4.8922 | 0.4172 | 0.3000 |
PACU_VAV_MID | 4.36 | 4.36 | 2.48 | 2.48 | 4.3620 | 2.4828 | 4.3620 | 0.5692 | 0.3000 |
PACU_VAV_TOP | 5.04 | 5.04 | 3.51 | 3.51 | 5.0422 | 3.5076 | 5.0422 | 0.6956 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25307.701 | 25307.701 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 25307.70 | 13828.02 | 0.424691 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 9438.45 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 25542.312 | 25542.312 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25542.31 | 25542.31 | 0.784465 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 18038.71 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 43541.191 | 43541.191 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 43541.19 | 43541.19 | 1.337253 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 30641.43 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 21393.316 | 21393.316 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21393.32 | 21393.32 | 0.657039 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00754542 | 47.5957 | 15016.75 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 13888.845 | 13888.845 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13888.84 | 13888.84 | 0.426559 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00753414 | 47.5257 | 9748.66 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 21377.932 | 21377.932 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21377.93 | 21377.93 | 0.656567 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00754511 | 47.5938 | 15005.97 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 14006.011 | 14006.011 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14006.01 | 14006.01 | 0.430158 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00753784 | 47.5488 | 9830.73 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 15878.070 | 15878.070 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15878.07 | 15878.07 | 0.487653 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765608 | 48.2823 | 11151.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 10386.258 | 10386.258 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10386.26 | 10386.26 | 0.318987 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765246 | 48.2598 | 7294.14 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 15878.053 | 15878.053 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15878.05 | 15878.05 | 0.487653 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765608 | 48.2823 | 11151.90 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 10484.642 | 10484.642 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10484.64 | 10484.64 | 0.322008 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765626 | 48.2835 | 7363.05 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 16709.745 | 16709.745 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16709.74 | 16709.74 | 0.513196 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00751088 | 47.3796 | 11735.43 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 10898.444 | 10898.444 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10898.44 | 10898.44 | 0.334717 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00750231 | 47.3264 | 7653.55 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 16691.929 | 16691.929 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16691.93 | 16691.93 | 0.512649 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00751034 | 47.3763 | 11722.95 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 10999.302 | 10999.302 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10999.30 | 10999.30 | 0.337815 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00750695 | 47.3553 | 7724.19 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 101812.863 | 77422.251 | 4.892184 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 104188.00 | 82908.72 | 4.892184 | 25.54 | 17.87 | 0.00997237 | 10.89 | 10.89 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 24.4302 | 24.00 | 0.00887464 | 46.5496 | 65626.52 | 0.00 | 104982.73 | 77633.09 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 39076.083 | 39076.083 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39076.08 | 39076.08 | 1.467655 | -9.77 | -9.77 | 0.00213926 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 81.4340 | 19.34 | 0.00720314 | 50.3595 | 20822.19 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 93710.334 | 70216.184 | 4.362006 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 96336.70 | 74828.04 | 4.362006 | 25.73 | 18.09 | 0.01017052 | 10.88 | 10.88 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 27.3995 | 24.00 | 0.00896157 | 46.9998 | 58434.88 | 0.00 | 96627.93 | 70482.87 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 40397.213 | 40397.213 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40397.21 | 40397.21 | 1.308602 | -13.37 | -13.37 | 0.00147520 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 91.3318 | 17.60 | 0.00693411 | 54.1113 | 22573.72 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 104805.282 | 79840.328 | 5.042171 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 107229.41 | 85214.38 | 5.042171 | 25.50 | 17.86 | 0.00997779 | 10.89 | 10.89 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 23.7035 | 24.00 | 0.00892059 | 46.7880 | 67443.89 | 0.00 | 108068.31 | 80069.65 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 39906.060 | 39906.060 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39906.06 | 39906.06 | 1.512651 | -9.56 | -9.56 | 0.00225751 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 79.0116 | 17.38 | 0.00712107 | 56.3365 | 30198.63 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25307.701 | 25307.701 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 25307.70 | 13828.02 | 1.0000 | 0.49855562 | 0.424691 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25307.70 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.02 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 9438.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 25542.312 | 25542.312 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25542.31 | 25542.31 | 1.0000 | 0.92090311 | 0.784465 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25542.31 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 18038.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 43541.191 | 43541.191 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 43541.19 | 43541.19 | 1.0000 | 1.56983513 | 1.337253 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 43541.19 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 30641.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 21393.316 | 21393.316 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21393.32 | 21393.32 | 1.0000 | 0.77131511 | 0.657039 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21393.32 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00754542 | 21.00 | 0.00754542 | 47.5957 | 15016.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 13888.845 | 13888.845 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13888.84 | 13888.84 | 1.0000 | 0.50074873 | 0.426559 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13888.84 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00753414 | 21.00 | 0.00753414 | 47.5257 | 9748.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 21377.932 | 21377.932 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21377.93 | 21377.93 | 1.0000 | 0.77076044 | 0.656567 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21377.93 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00754511 | 21.00 | 0.00754511 | 47.5938 | 15005.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 14006.011 | 14006.011 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14006.01 | 14006.01 | 1.0000 | 0.50497304 | 0.430158 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14006.01 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00753784 | 21.00 | 0.00753784 | 47.5488 | 9830.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 15878.070 | 15878.070 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15878.07 | 15878.07 | 1.0000 | 0.57246829 | 0.487653 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15878.07 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00765608 | 21.00 | 0.00765608 | 48.2823 | 11151.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10386.258 | 10386.258 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10386.26 | 10386.26 | 1.0000 | 0.37446638 | 0.318987 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10386.26 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00765246 | 21.00 | 0.00765246 | 48.2598 | 7294.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 15878.053 | 15878.053 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15878.05 | 15878.05 | 1.0000 | 0.57246770 | 0.487653 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15878.05 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00765608 | 21.00 | 0.00765608 | 48.2823 | 11151.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10484.642 | 10484.642 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10484.64 | 10484.64 | 1.0000 | 0.37801353 | 0.322008 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10484.64 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00765626 | 21.00 | 0.00765626 | 48.2835 | 7363.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 16709.745 | 16709.745 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16709.74 | 16709.74 | 1.0000 | 0.60245353 | 0.513196 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16709.74 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00751088 | 21.00 | 0.00751088 | 47.3796 | 11735.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10898.444 | 10898.444 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10898.44 | 10898.44 | 1.0000 | 0.39293277 | 0.334717 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10898.44 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00750231 | 21.00 | 0.00750231 | 47.3264 | 7653.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 16691.929 | 16691.929 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16691.93 | 16691.93 | 1.0000 | 0.60181122 | 0.512649 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16691.93 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00751034 | 21.00 | 0.00751034 | 47.3763 | 11722.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10999.302 | 10999.302 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10999.30 | 10999.30 | 1.0000 | 0.39656908 | 0.337815 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10999.30 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00750695 | 21.00 | 0.00750695 | 47.3553 | 7724.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 101812.863 | 77422.251 | 4.892184 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.3781 | 1004.8586 | 1.1739 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.892184 | 5.74305848 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 104188.00 | 82908.72 | 1.0233 | 5.74305848 | 4.892184 | 25.54 | 17.87 | 0.00997237 | 51075.7 | 10.89 | 10.89 | 0.00850000 | 32369.5 | -999.0 | -999.00 | -999.00 | -999.00 | 11244.496 | 92943.50 | 30.30 | 0.01336696 | 21.83 | 1.19517000 | 24.4302 | 24.00 | 0.00887464 | 24.00 | 0.00887464 | 46.5496 | 65626.52 | 0.00 | 104982.73 | 77633.09 | 5.51625109 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.90 | 12.87 | 0.00924074 | 36290.9 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 39076.083 | 39076.083 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.892184 | 5.74305848 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39076.08 | 39076.08 | 1.0000 | 1.72291754 | 1.467655 | -9.77 | -9.77 | 0.00213926 | -4506.5 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39076.08 | -16.30 | 0.00092409 | -16.30 | 1.19517000 | 81.4340 | 18.87 | 0.00746919 | 19.34 | 0.00720314 | 50.3595 | 20822.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 93710.334 | 70216.184 | 4.362006 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7465 | 1004.8586 | 1.1739 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.362006 | 5.12066921 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 96336.70 | 74828.04 | 1.0280 | 5.12066921 | 4.362006 | 25.73 | 18.09 | 0.01017052 | 51774.4 | 10.88 | 10.88 | 0.00850000 | 32357.5 | -999.0 | -999.00 | -999.00 | -999.00 | 10091.006 | 86245.70 | 30.30 | 0.01336696 | 21.83 | 1.19517000 | 27.3995 | 24.00 | 0.00896157 | 24.00 | 0.00896157 | 46.9998 | 58434.88 | 0.00 | 96627.93 | 70482.87 | 4.91844148 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.64 | 12.63 | 0.00910049 | 35676.3 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 40397.213 | 40397.213 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.362006 | 5.12066921 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 40397.21 | 40397.21 | 1.0000 | 1.53620076 | 1.308602 | -13.37 | -13.37 | 0.00147520 | -9781.7 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40397.21 | -16.30 | 0.00092409 | -16.30 | 1.19517000 | 91.3318 | 17.51 | 0.00728193 | 17.60 | 0.00693411 | 54.1113 | 22573.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 104805.282 | 79840.328 | 5.042171 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.3882 | 1004.8586 | 1.1739 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.042171 | 5.91913184 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 107229.41 | 85214.38 | 1.0231 | 5.91913184 | 5.042171 | 25.50 | 17.86 | 0.00997779 | 51046.8 | 10.89 | 10.89 | 0.00850000 | 32369.5 | -999.0 | -999.00 | -999.00 | -999.00 | 11589.235 | 95640.17 | 30.30 | 0.01336696 | 21.83 | 1.19517000 | 23.7035 | 24.00 | 0.00892059 | 24.00 | 0.00892059 | 46.7880 | 67443.89 | 0.00 | 108068.31 | 80069.65 | 5.68537088 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.89 | 12.88 | 0.00925380 | 36314.2 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 39906.060 | 39906.060 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.042171 | 5.91913184 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39906.06 | 39906.06 | 1.0000 | 1.77573955 | 1.512651 | -9.56 | -9.56 | 0.00225751 | -4004.8 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39906.06 | -16.30 | 0.00092409 | -16.30 | 1.19517000 | 79.0116 | 15.79 | 0.00727721 | 17.38 | 0.00712107 | 56.3365 | 30198.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.89 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.36 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.04 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2029.00 | 2970.33 | 138.00 |
CORE_MID | 2497.17 | 3650.00 | 1047.17 |
CORE_TOP | 3017.33 | 3951.00 | 1710.67 |
PERIMETER_TOP_ZN_3 | 3672.67 | 4235.67 | 2475.00 |
PERIMETER_TOP_ZN_2 | 3832.83 | 3996.50 | 2356.17 |
PERIMETER_TOP_ZN_1 | 3547.33 | 3956.17 | 2100.83 |
PERIMETER_TOP_ZN_4 | 3737.33 | 4227.17 | 2399.67 |
PERIMETER_BOT_ZN_3 | 3308.17 | 4303.83 | 2178.00 |
PERIMETER_BOT_ZN_2 | 3545.83 | 3876.50 | 2003.00 |
PERIMETER_BOT_ZN_1 | 3430.33 | 4286.67 | 2180.00 |
PERIMETER_BOT_ZN_4 | 3490.00 | 3999.00 | 2040.00 |
PERIMETER_MID_ZN_3 | 3421.33 | 4016.17 | 2105.33 |
PERIMETER_MID_ZN_2 | 3056.33 | 3344.17 | 1801.83 |
PERIMETER_MID_ZN_1 | 3285.00 | 3670.50 | 1697.00 |
PERIMETER_MID_ZN_4 | 3532.17 | 3996.17 | 2045.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4871.50 | 4827.67 | 2845.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.33 | 1.67 | 0.33 | 0.00 |
CORE_MID | 2.50 | 0.00 | 2.33 | 0.00 |
CORE_TOP | 7.33 | 0.67 | 4.67 | 0.67 |
PERIMETER_TOP_ZN_3 | 161.33 | 2.33 | 72.00 | 2.00 |
PERIMETER_TOP_ZN_2 | 106.50 | 12.33 | 20.67 | 12.17 |
PERIMETER_TOP_ZN_1 | 89.50 | 17.33 | 17.17 | 17.00 |
PERIMETER_TOP_ZN_4 | 107.00 | 22.50 | 24.17 | 13.33 |
PERIMETER_BOT_ZN_3 | 45.83 | 0.00 | 32.67 | 0.00 |
PERIMETER_BOT_ZN_2 | 13.83 | 3.67 | 0.67 | 3.67 |
PERIMETER_BOT_ZN_1 | 534.33 | 8.83 | 525.33 | 8.83 |
PERIMETER_BOT_ZN_4 | 14.17 | 13.17 | 0.83 | 6.67 |
PERIMETER_MID_ZN_3 | 58.67 | 0.00 | 25.00 | 0.00 |
PERIMETER_MID_ZN_2 | 34.17 | 11.83 | 2.00 | 11.83 |
PERIMETER_MID_ZN_1 | 27.00 | 13.67 | 2.33 | 13.67 |
PERIMETER_MID_ZN_4 | 35.33 | 20.00 | 2.83 | 11.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 676.83 | 71.50 | 556.17 | 54.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.74 | 52.94 | 2698.04 | 0.944 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.74 | 52.94 | 2698.04 | 0.690 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.74 | 52.94 | 2698.04 | 0.694 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.58 | 11.16 | 568.77 | 0.786 | 0.114 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 1.239 | 0.120 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.58 | 11.16 | 568.77 | 1.092 | 0.114 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 1.266 | 0.120 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.58 | 11.16 | 568.77 | 0.679 | 0.061 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 1.010 | 0.064 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.58 | 11.16 | 568.77 | 0.870 | 1.350 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 0.988 | 0.064 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.58 | 11.16 | 568.77 | 0.759 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 1.109 | 0.106 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.58 | 11.16 | 568.77 | 1.040 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 1.188 | 0.100 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.74 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.74 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.74 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.74 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.74 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.74 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.54 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.75 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 15109776.20 | 0.00 | 15109776.20 | 0.00 | 15109776.20 | 13393058.27 | 5650.58 | 242.28 | 2867.14 | 188.38 |
CORE_MID | 11044951.34 | 0.00 | 11044951.34 | 0.00 | 11044951.34 | 13393058.27 | 6421.24 | 30.65 | 2308.12 | 199.98 |
CORE_TOP | 11092688.29 | 0.00 | 11092688.29 | 0.00 | 11092688.29 | 13393058.27 | 6368.28 | 18.51 | 2373.21 | 108.96 |
PERIMETER_TOP_ZN_3 | 2641265.50 | 0.00 | 2641265.50 | 750436.27 | 3391701.78 | 2823374.22 | 5700.13 | 45.21 | 3014.67 | 108.96 |
PERIMETER_TOP_ZN_2 | 2635330.52 | 0.00 | 2635330.52 | 500287.84 | 3135618.36 | 1787429.43 | 4083.87 | 1.86 | 4674.27 | 108.96 |
PERIMETER_TOP_ZN_1 | 3664144.50 | 0.00 | 3664144.50 | 750436.27 | 4414580.77 | 2823374.22 | 4106.08 | 1.75 | 4652.17 | 108.96 |
PERIMETER_TOP_ZN_4 | 2705656.49 | 0.00 | 2705656.49 | 500287.84 | 3205944.33 | 1787312.18 | 4083.12 | 1.28 | 4675.59 | 108.96 |
PERIMETER_BOT_ZN_3 | 2310748.33 | 0.00 | 2310748.33 | 399002.08 | 2709750.41 | 2823374.22 | 5873.13 | 251.17 | 2635.70 | 188.38 |
PERIMETER_BOT_ZN_2 | 2163422.92 | 0.00 | 2163422.92 | 265999.79 | 2429422.70 | 1787429.43 | 4125.38 | 29.40 | 4605.22 | 188.38 |
PERIMETER_BOT_ZN_1 | 2952673.39 | 0.00 | 2952673.39 | 4729192.30 | 7681865.69 | 2823374.22 | 4992.83 | 153.92 | 3613.25 | 188.38 |
PERIMETER_BOT_ZN_4 | 2125804.85 | 0.00 | 2125804.85 | 265999.79 | 2391804.64 | 1787312.18 | 4137.97 | 13.77 | 4608.26 | 188.38 |
PERIMETER_MID_ZN_3 | 2556907.28 | 0.00 | 2556907.28 | 624679.86 | 3181587.13 | 2823374.22 | 5913.12 | 43.45 | 2803.43 | 199.96 |
PERIMETER_MID_ZN_2 | 2569514.45 | 0.00 | 2569514.45 | 416450.74 | 2985965.18 | 1787429.43 | 4075.68 | 1.53 | 4682.80 | 1108.96 |
PERIMETER_MID_ZN_1 | 3491820.17 | 0.00 | 3491820.17 | 624679.86 | 4116500.03 | 2823374.22 | 4108.54 | 6.78 | 4644.68 | 199.96 |
PERIMETER_MID_ZN_4 | 2540646.94 | 0.00 | 2540646.94 | 416450.74 | 2957097.68 | 1787312.18 | 4073.86 | 4.02 | 4682.12 | 199.96 |
Total Facility | 69605351.17 | 0.00 | 69605351.17 | 10243903.37 | 79849254.54 | 67843644.98 | 6566.31 | 446.35 | 4797.92 | 1240.34 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6925 | 0.0000 | 0.6925 | 0.0000 | 0.6925 | 0.4247 | 2920.73 | 242.17 | 2780.10 |
CORE_MID | 0.5075 | 0.0000 | 0.5075 | 0.0000 | 0.5075 | 0.4247 | 3661.49 | 30.65 | 2250.87 |
CORE_TOP | 0.5107 | 0.0000 | 0.5107 | 0.0000 | 0.5107 | 0.4247 | 3606.87 | 18.51 | 2317.61 |
PERIMETER_TOP_ZN_3 | 0.1218 | 0.0000 | 0.1218 | 0.0178 | 0.1396 | 0.0895 | 2938.72 | 45.21 | 2959.07 |
PERIMETER_TOP_ZN_2 | 0.1216 | 0.0000 | 0.1216 | 0.0119 | 0.1335 | 0.0567 | 1322.47 | 1.86 | 4618.67 |
PERIMETER_TOP_ZN_1 | 0.1693 | 0.0000 | 0.1693 | 0.0178 | 0.1871 | 0.0895 | 1344.68 | 1.75 | 4596.57 |
PERIMETER_TOP_ZN_4 | 0.1243 | 0.0000 | 0.1243 | 0.0119 | 0.1362 | 0.0567 | 1321.72 | 1.28 | 4620.00 |
PERIMETER_BOT_ZN_3 | 0.1054 | 0.0000 | 0.1054 | 0.0095 | 0.1149 | 0.0895 | 3143.14 | 251.06 | 2548.81 |
PERIMETER_BOT_ZN_2 | 0.0991 | 0.0000 | 0.0991 | 0.0063 | 0.1054 | 0.0567 | 1396.74 | 29.40 | 4516.86 |
PERIMETER_BOT_ZN_1 | 0.1354 | 0.0000 | 0.1354 | 0.2119 | 0.3473 | 0.0895 | 2262.78 | 153.87 | 3526.35 |
PERIMETER_BOT_ZN_4 | 0.0970 | 0.0000 | 0.0970 | 0.0063 | 0.1034 | 0.0567 | 1409.31 | 13.77 | 4519.92 |
PERIMETER_MID_ZN_3 | 0.1177 | 0.0000 | 0.1177 | 0.0148 | 0.1325 | 0.0895 | 3153.37 | 43.45 | 2746.18 |
PERIMETER_MID_ZN_2 | 0.1090 | 0.0000 | 0.1090 | 0.0105 | 0.1194 | 0.0567 | 1316.10 | 1.50 | 3716.40 |
PERIMETER_MID_ZN_1 | 0.1612 | 0.0000 | 0.1612 | 0.0148 | 0.1760 | 0.0895 | 1348.81 | 6.76 | 4587.43 |
PERIMETER_MID_ZN_4 | 0.1166 | 0.0000 | 0.1166 | 0.0099 | 0.1265 | 0.0567 | 1314.36 | 4.00 | 4624.64 |
Total Facility | 3.1891 | 0.0000 | 3.1891 | 0.3433 | 3.5324 | 2.1513 | 3778.46 | 446.17 | 4681.39 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 33987272.89 | 0.00 | 33987272.89 | 22614548.33 | 4062.59 | 3.21 | 4694.20 | 188.38 |
PACU_VAV_MID | 30599144.17 | 0.00 | 30599144.17 | 22614548.33 | 4076.45 | 1.16 | 4682.39 | 199.85 |
PACU_VAV_TOP | 31336749.93 | 0.00 | 31336749.93 | 22614548.33 | 4081.59 | 1.82 | 4676.58 | 108.76 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.5565 | 0.0000 | 1.5565 | 0.7171 | 1333.93 | 3.21 | 4605.86 |
PACU_VAV_MID | 1.4075 | 0.0000 | 1.4075 | 0.7171 | 1316.70 | 1.16 | 4625.14 |
PACU_VAV_TOP | 1.4439 | 0.0000 | 1.4439 | 0.7171 | 1320.19 | 1.82 | 4620.99 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.96 | 2898.72 | 0.00 | 0.00 | 0.00 | 2020.99 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.07 | 2721.43 | 0.00 | 0.00 | 0.00 | 2255.67 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.17 | 2706.73 | 0.00 | 0.00 | 0.00 | 2187.86 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.6194 | 0.0000 | 0.0000 | 0.0000 | 1.0623 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.3656 | 0.0000 | 0.0000 | 0.0000 | 1.0647 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.4087 | 0.0000 | 0.0000 | 0.0000 | 1.0628 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 824 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1647.95 | 15539.06 | 12-MAR-17:10 | 245258.45 | 02-JAN-07:10 |
Electricity:Building | 1042.87 | 15341.49 | 01-JAN-09:10 | 75353.13 | 02-NOV-07:10 |
Electricity:Zone:CORE_BOTTOM | 310.83 | 4652.71 | 01-JAN-00:10 | 24063.48 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1042.87 | 15341.49 | 01-JAN-09:10 | 75353.13 | 02-NOV-07:10 |
InteriorLights:Electricity | 280.83 | 1316.11 | 01-JAN-09:10 | 28079.40 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 280.83 | 1316.11 | 01-JAN-09:10 | 28079.40 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 280.83 | 1316.11 | 01-JAN-09:10 | 28079.40 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 280.83 | 1316.11 | 01-JAN-09:10 | 28079.40 | 02-JAN-16:50 |
Electricity:Zone:CORE_MID | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 35.94 | 541.99 | 01-JAN-09:10 | 2674.44 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.25 | 40.03 | 01-JAN-09:10 | 1168.55 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.25 | 40.03 | 01-JAN-09:10 | 1168.55 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 22.74 | 343.10 | 01-JAN-08:40 | 1693.08 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.84 | 25.34 | 01-JAN-08:40 | 739.79 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.84 | 25.34 | 01-JAN-08:40 | 739.79 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 35.89 | 541.99 | 01-JAN-08:50 | 2674.43 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.20 | 40.03 | 01-JAN-08:50 | 1168.55 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.20 | 40.03 | 01-JAN-08:50 | 1168.55 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 22.73 | 343.10 | 01-JAN-09:10 | 1693.03 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.84 | 25.34 | 01-JAN-09:10 | 739.74 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.84 | 25.34 | 01-JAN-09:10 | 739.74 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 35.93 | 541.99 | 01-JAN-09:00 | 2674.44 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.24 | 40.03 | 01-JAN-09:00 | 1168.55 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.24 | 40.03 | 01-JAN-09:00 | 1168.55 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 22.73 | 343.10 | 01-JAN-08:40 | 1693.08 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.84 | 25.34 | 01-JAN-08:40 | 739.79 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.84 | 25.34 | 01-JAN-08:40 | 739.79 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 35.88 | 541.99 | 01-JAN-08:40 | 2674.43 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.19 | 40.03 | 01-JAN-08:40 | 1168.55 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.19 | 40.03 | 01-JAN-08:40 | 1168.55 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 22.73 | 343.10 | 01-JAN-09:10 | 1693.03 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.83 | 25.34 | 01-JAN-09:10 | 739.74 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.83 | 25.34 | 01-JAN-09:10 | 739.74 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 35.94 | 541.99 | 01-JAN-09:10 | 2674.44 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.25 | 40.03 | 01-JAN-09:10 | 1168.55 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.25 | 40.03 | 01-JAN-09:10 | 1168.55 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 22.74 | 343.10 | 01-JAN-08:40 | 1693.08 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.84 | 25.34 | 01-JAN-08:40 | 739.79 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.84 | 25.34 | 01-JAN-08:40 | 739.79 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 35.89 | 541.99 | 01-JAN-08:50 | 2674.43 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.20 | 40.03 | 01-JAN-08:50 | 1168.55 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.20 | 40.03 | 01-JAN-08:50 | 1168.55 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 22.73 | 343.10 | 01-JAN-09:10 | 1693.03 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.84 | 25.34 | 01-JAN-09:10 | 739.74 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.84 | 25.34 | 01-JAN-09:10 | 739.74 | 02-JAN-16:50 |
InteriorEquipment:Electricity | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 247.34 | 4344.73 | 01-JAN-00:10 | 18520.31 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 533.14 | 197.57 | 14-MAY-14:30 | 208487.34 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 927.79 | 02-NOV-07:20 |
Transformer:ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 927.79 | 02-NOV-07:20 |
ElectricityPurchased:Facility | 1647.95 | 15539.06 | 08-JUL-18:20 | 245258.45 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1647.95 | 15539.06 | 08-JUL-18:20 | 245258.45 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1647.95 | 15539.06 | 08-JUL-18:20 | 245258.45 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1647.95 | 15539.06 | 08-JUL-18:20 | 245258.45 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1647.95 | 15539.06 | 08-JUL-18:20 | 245258.45 | 02-JAN-07:10 |
ElectricityNet:Plant | 1647.95 | 15539.06 | 08-JUL-18:20 | 245258.45 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1647.95 | 15539.06 | 08-JUL-18:20 | 245258.45 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1647.95 | 15539.06 | 08-JUL-18:20 | 245258.45 | 02-JAN-07:10 |
Heating:Electricity | 290.04 | 0.00 | 01-JAN-00:40 | 201182.34 | 02-JAN-06:20 |
General:Heating:Electricity | 290.04 | 0.00 | 01-JAN-00:40 | 201182.34 | 02-JAN-06:20 |
Fans:Electricity | 92.39 | 0.00 | 01-JAN-00:40 | 28081.09 | 17-JUL-12:10 |
General:Fans:Electricity | 92.39 | 0.00 | 01-JAN-00:40 | 28081.09 | 17-JUL-12:10 |
ExteriorLights:Electricity | 71.93 | 0.00 | 01-JAN-08:00 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 71.93 | 0.00 | 01-JAN-08:00 | 5557.43 | 01-JAN-06:10 |
Cooling:Electricity | 137.73 | 0.00 | 01-JAN-00:10 | 76834.88 | 15-AUG-14:30 |
General:Cooling:Electricity | 137.73 | 0.00 | 01-JAN-00:10 | 76834.88 | 15-AUG-14:30 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 7.89 | 0.00 | 01-JAN-00:10 | 789.03 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 641.94 | 12061.80 | 01-JAN-00:10 | 36271.65 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 353.60 | 1156.00 | 10-JAN-05:10 | 117585.48 | 07-FEB-07:20 |
NaturalGas:HVAC | 241.29 | 0.00 | 01-JAN-00:40 | 109362.93 | 07-FEB-07:20 |
Heating:NaturalGas | 241.29 | 0.00 | 01-JAN-00:40 | 109362.93 | 07-FEB-07:20 |
General:Heating:NaturalGas | 241.29 | 0.00 | 01-JAN-00:40 | 109362.93 | 07-FEB-07:20 |
NaturalGas:Plant | 112.31 | 1156.00 | 02-JAN-17:20 | 10471.87 | 07-FEB-12:30 |
WaterSystems:NaturalGas | 112.31 | 1156.00 | 02-JAN-17:20 | 10471.87 | 07-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 112.31 | 1156.00 | 02-JAN-17:20 | 10471.87 | 07-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2198.45 | 0.00 | 01-JAN-00:40 | 478146.51 | 15-AUG-14:30 |
EnergyTransfer:Building | 1098.73 | 0.00 | 01-JAN-00:40 | 196595.10 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 207.50 | 0.00 | 01-JAN-00:40 | 26934.60 | 17-JUL-08:00 |
Heating:EnergyTransfer | 248.46 | 0.00 | 01-JAN-00:40 | 196595.10 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.33 | 0.00 | 01-JAN-00:10 | 19688.48 | 02-JAN-06:30 |
General:Heating:EnergyTransfer | 248.46 | 0.00 | 01-JAN-00:40 | 196595.10 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.33 | 0.00 | 01-JAN-00:10 | 19688.48 | 02-JAN-06:30 |
Cooling:EnergyTransfer | 850.27 | 0.00 | 01-JAN-00:40 | 158883.45 | 09-AUG-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 207.16 | 0.00 | 01-JAN-00:40 | 26934.60 | 17-JUL-08:00 |
General:Cooling:EnergyTransfer | 850.27 | 0.00 | 01-JAN-00:40 | 158883.45 | 09-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 207.16 | 0.00 | 01-JAN-00:40 | 26934.60 | 17-JUL-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 57.04 | 0.00 | 01-JAN-00:40 | 16181.22 | 11-DEC-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 32.66 | 0.00 | 01-JAN-00:40 | 16181.22 | 11-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 32.66 | 0.00 | 01-JAN-00:40 | 16181.22 | 11-DEC-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 24.39 | 0.00 | 01-JAN-00:10 | 10350.40 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 24.39 | 0.00 | 01-JAN-00:10 | 10350.40 | 21-JUL-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 28.48 | 0.00 | 01-JAN-00:40 | 9502.03 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.05 | 0.00 | 01-JAN-00:40 | 9502.03 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.05 | 0.00 | 01-JAN-00:40 | 9502.03 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.42 | 0.00 | 01-JAN-00:10 | 5179.41 | 17-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.42 | 0.00 | 01-JAN-00:10 | 5179.41 | 17-JUL-12:10 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 27.94 | 0.00 | 01-JAN-00:40 | 7877.70 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.78 | 0.00 | 01-JAN-00:40 | 7877.70 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.78 | 0.00 | 01-JAN-00:40 | 7877.70 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.17 | 0.00 | 01-JAN-00:10 | 5406.34 | 17-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.17 | 0.00 | 01-JAN-00:10 | 5406.34 | 17-JUL-12:10 |
EnergyTransfer:Zone:CORE_MID | 137.22 | 0.00 | 01-JAN-00:40 | 21827.06 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 2.77 | 0.00 | 01-JAN-00:20 | 21827.06 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 2.77 | 0.00 | 01-JAN-00:20 | 21827.06 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 134.45 | 0.00 | 01-JAN-00:40 | 18988.42 | 17-JUL-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 134.45 | 0.00 | 01-JAN-00:40 | 18988.42 | 17-JUL-07:40 |
EnergyTransfer:Zone:CORE_TOP | 135.73 | 0.00 | 01-JAN-00:40 | 28172.75 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 12.46 | 0.00 | 01-JAN-00:40 | 28172.75 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 12.46 | 0.00 | 01-JAN-00:40 | 28172.75 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 123.27 | 0.00 | 01-JAN-00:20 | 21079.68 | 27-JUN-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 123.27 | 0.00 | 01-JAN-00:20 | 21079.68 | 27-JUN-15:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 48.72 | 0.00 | 01-JAN-00:40 | 10004.04 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.90 | 0.00 | 01-JAN-00:40 | 10004.04 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.90 | 0.00 | 01-JAN-00:40 | 10004.04 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 24.82 | 0.00 | 01-JAN-00:10 | 7133.17 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 24.82 | 0.00 | 01-JAN-00:10 | 7133.17 | 21-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 39.72 | 0.00 | 01-JAN-00:40 | 9619.33 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 13.94 | 0.00 | 01-JAN-00:40 | 9619.33 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 13.94 | 0.00 | 01-JAN-00:40 | 9619.33 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.78 | 0.00 | 01-JAN-00:20 | 8439.82 | 17-JUL-07:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.78 | 0.00 | 01-JAN-00:20 | 8439.82 | 17-JUL-07:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 57.08 | 0.00 | 01-JAN-00:40 | 13312.07 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 17.79 | 0.00 | 01-JAN-00:40 | 13312.07 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 17.79 | 0.00 | 01-JAN-00:40 | 13312.07 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 39.29 | 0.00 | 01-JAN-00:20 | 12110.10 | 21-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 39.29 | 0.00 | 01-JAN-00:20 | 12110.10 | 21-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 40.93 | 0.00 | 01-JAN-00:40 | 10382.16 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 14.98 | 0.00 | 01-JAN-00:40 | 10382.16 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 14.98 | 0.00 | 01-JAN-00:40 | 10382.16 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.95 | 0.00 | 01-JAN-00:20 | 8916.82 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.95 | 0.00 | 01-JAN-00:20 | 8916.82 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 35.30 | 0.00 | 01-JAN-00:40 | 7258.64 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 13.04 | 0.00 | 01-JAN-00:40 | 7258.64 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 13.04 | 0.00 | 01-JAN-00:40 | 7258.64 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 22.26 | 0.00 | 01-JAN-00:20 | 5516.84 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 22.26 | 0.00 | 01-JAN-00:20 | 5516.84 | 21-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 30.03 | 0.00 | 01-JAN-00:40 | 7196.01 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 7.15 | 0.00 | 01-JAN-00:40 | 7196.01 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 7.15 | 0.00 | 01-JAN-00:40 | 7196.01 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 22.88 | 0.00 | 01-JAN-00:20 | 6737.86 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 22.88 | 0.00 | 01-JAN-00:20 | 6737.86 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 65.82 | 0.00 | 01-JAN-00:40 | 15238.05 | 07-FEB-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 38.82 | 0.00 | 01-JAN-00:40 | 15238.05 | 07-FEB-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 38.82 | 0.00 | 01-JAN-00:40 | 15238.05 | 07-FEB-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 27.00 | 0.00 | 01-JAN-00:20 | 11463.72 | 10-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 27.00 | 0.00 | 01-JAN-00:20 | 11463.72 | 10-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 30.22 | 0.00 | 01-JAN-00:40 | 7311.17 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 7.77 | 0.00 | 01-JAN-00:40 | 7311.17 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 7.77 | 0.00 | 01-JAN-00:40 | 7311.17 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 22.45 | 0.00 | 01-JAN-00:20 | 7014.26 | 04-AUG-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 22.45 | 0.00 | 01-JAN-00:20 | 7014.26 | 04-AUG-17:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 39.01 | 0.00 | 01-JAN-00:40 | 8263.69 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 12.82 | 0.00 | 01-JAN-00:40 | 8263.69 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 12.82 | 0.00 | 01-JAN-00:40 | 8263.69 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.19 | 0.00 | 01-JAN-00:20 | 6435.99 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.19 | 0.00 | 01-JAN-00:20 | 6435.99 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 34.02 | 0.00 | 01-JAN-00:40 | 8339.60 | 17-JUL-07:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 7.53 | 0.00 | 01-JAN-00:40 | 8061.73 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 7.53 | 0.00 | 01-JAN-00:40 | 8061.73 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 26.49 | 0.00 | 01-JAN-00:20 | 8339.60 | 17-JUL-07:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 26.49 | 0.00 | 01-JAN-00:20 | 8339.60 | 17-JUL-07:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 49.45 | 0.00 | 01-JAN-00:40 | 11618.86 | 21-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 8.74 | 0.00 | 01-JAN-00:40 | 10949.67 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 8.74 | 0.00 | 01-JAN-00:40 | 10949.67 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 40.71 | 0.00 | 01-JAN-00:20 | 11618.86 | 21-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 40.71 | 0.00 | 01-JAN-00:20 | 11618.86 | 21-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 34.52 | 0.00 | 01-JAN-00:40 | 8414.71 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 7.93 | 0.00 | 01-JAN-00:40 | 8022.37 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 7.93 | 0.00 | 01-JAN-00:40 | 8022.37 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 26.58 | 0.00 | 01-JAN-00:20 | 8414.71 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 26.58 | 0.00 | 01-JAN-00:20 | 8414.71 | 10-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 52.88 | 0.00 | 01-JAN-00:10 | 6711.65 | 15-FEB-12:10 |
PlantLoopHeatingDemand:Plant | 52.88 | 0.00 | 01-JAN-00:10 | 6711.65 | 15-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 52.88 | 0.00 | 01-JAN-00:10 | 6711.65 | 15-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 52.88 | 0.00 | 01-JAN-00:10 | 6711.65 | 15-FEB-12:10 |
EnergyTransfer:HVAC | 1046.84 | 0.00 | 01-JAN-00:40 | 337476.38 | 15-AUG-14:30 |
HeatingCoils:EnergyTransfer | 483.07 | 0.00 | 01-JAN-00:40 | 267536.90 | 11-DEC-07:10 |
CoolingCoils:EnergyTransfer | 563.77 | 0.00 | 01-JAN-00:10 | 337476.38 | 15-AUG-14:30 |
EnergyTransfer:Plant | 52.88 | 0.00 | 01-JAN-00:10 | 6711.65 | 15-FEB-12:10 |
WaterSystems:EnergyTransfer | 52.88 | 0.00 | 01-JAN-00:10 | 6711.65 | 15-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 52.88 | 0.00 | 01-JAN-00:10 | 6711.65 | 15-FEB-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.335 | -207.161 | 0.000 | 0.000 | 33.358 | 63.485 | 247.342 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -137.359 |
CORE_MID | 0.000 | 0.000 | 2.773 | -134.445 | 0.000 | 0.000 | 34.905 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -93.319 |
CORE_TOP | 0.000 | 0.000 | 12.457 | -123.268 | 0.000 | 0.000 | 35.574 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -114.849 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 23.898 | -24.818 | 0.000 | 0.000 | 7.648 | 9.253 | 26.688 | 15.301 | 0.000 | 0.063 | 0.001 | 0.000 | -31.990 | 0.000 | -11.582 | -14.462 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 13.940 | -25.781 | 0.000 | 0.000 | 4.804 | 5.844 | 16.895 | 28.241 | 0.000 | 0.041 | 0.000 | 0.000 | -20.094 | 0.000 | -7.790 | -16.100 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 17.790 | -39.294 | 0.000 | 0.000 | 7.516 | 9.198 | 26.688 | 52.475 | 0.000 | 0.059 | 0.001 | 0.000 | -30.177 | 0.000 | -11.917 | -32.339 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 14.980 | -25.947 | 0.000 | 0.000 | 4.860 | 5.839 | 16.895 | 28.419 | 0.000 | 0.042 | 0.000 | 0.000 | -20.872 | 0.000 | -7.822 | -16.395 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 13.036 | -22.260 | 0.000 | 0.000 | 7.626 | 9.240 | 26.688 | 15.612 | 0.000 | 0.041 | 0.000 | 0.000 | -33.098 | 0.000 | -6.453 | -10.433 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 7.152 | -22.883 | 0.000 | 0.000 | 4.766 | 5.839 | 16.895 | 28.382 | 0.000 | 0.023 | 0.000 | 0.000 | -21.070 | 0.000 | -4.389 | -14.715 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 38.817 | -27.002 | 0.000 | 0.000 | 7.791 | 9.189 | 26.688 | 53.416 | 0.000 | 1.210 | 0.000 | 0.000 | -31.065 | 0.000 | -62.521 | -16.523 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 7.769 | -22.452 | 0.000 | 0.000 | 4.807 | 5.833 | 16.895 | 28.622 | 0.000 | 0.023 | 0.000 | 0.000 | -21.869 | 0.000 | -4.404 | -15.224 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 12.822 | -26.190 | 0.000 | 0.000 | 7.569 | 9.253 | 26.688 | 15.065 | 0.000 | 0.055 | 0.000 | 0.000 | -33.637 | 0.000 | -10.095 | -1.530 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 7.534 | -26.489 | 0.000 | 0.000 | 3.529 | 5.844 | 16.895 | 28.059 | 0.000 | 0.036 | 0.000 | 0.000 | -21.084 | 0.000 | -6.775 | -7.549 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 8.737 | -40.712 | 0.000 | 0.000 | 7.421 | 9.198 | 26.688 | 52.173 | 0.000 | 0.050 | 0.000 | 0.000 | -31.782 | 0.000 | -10.413 | -21.360 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 7.934 | -26.583 | 0.000 | 0.000 | 4.806 | 5.839 | 16.895 | 28.267 | 0.000 | 0.036 | 0.000 | 0.000 | -21.936 | 0.000 | -6.811 | -8.446 |
TOPFLOOR_PLENUM | 32.655 | -24.386 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.048 | 9.273 | 0.000 | 0.000 | 0.000 | -17.590 | -0.002 |
MIDFLOOR_PLENUM | 15.054 | -13.422 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.074 | 15.523 | 0.000 | 0.000 | 0.000 | -17.229 | -0.000 |
FIRSTFLOOR_PLENUM | 10.776 | -17.169 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.057 | 20.342 | 0.000 | 0.000 | 0.000 | -14.007 | -0.000 |
Total Facility | 58.485 | -54.976 | 189.975 | -795.283 | 0.000 | 0.000 | 176.979 | 280.826 | 762.041 | 374.031 | 0.000 | 1.858 | 45.142 | 0.000 | -318.674 | 0.000 | -199.798 | -520.606 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 18-SEP-04:02 | 0.00 | 0.00 | 0.00 | -44709.83 | 0.00 | 0.00 | 0.00 | 615.87 | 5138.45 | 0.00 | 0.00 | 0.00 | 38955.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 17-JUL-04:04 | 0.00 | 0.00 | 0.00 | -32710.76 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 28920.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 07-AUG-04:02 | 0.00 | 0.00 | 0.00 | -34412.10 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 30621.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-16:52 | 0.00 | 0.00 | 0.00 | -9362.13 | 0.00 | 0.00 | 27.75 | 40.03 | 501.96 | 2047.45 | 0.00 | 24.34 | 6720.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUL-09:02 | 0.00 | 0.00 | 0.00 | -13209.17 | 0.00 | 0.00 | 14.02 | 25.34 | 317.77 | 9945.43 | 0.00 | 0.00 | 3065.52 | 0.00 | -0.00 | 0.00 | -158.90 | 0.00 |
PERIMETER_TOP_ZN_1 | 30-JUL-12:02 | 0.00 | 0.00 | 0.00 | -16751.72 | 0.00 | 0.00 | 25.27 | 40.03 | 501.96 | 10861.18 | 0.00 | 0.00 | 5418.03 | 0.00 | -0.00 | 0.00 | -94.74 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-17:22 | 0.00 | 0.00 | 0.00 | -15259.28 | 0.00 | 0.00 | 0.00 | 25.34 | 317.76 | 10634.56 | 0.00 | 0.00 | 4380.26 | 0.00 | -0.00 | 0.00 | -98.64 | 0.00 |
PERIMETER_BOT_ZN_3 | 21-JUL-13:50 | 0.00 | 0.00 | 0.00 | -5516.99 | 0.00 | 0.00 | 757.18 | 720.41 | 1505.89 | 4002.86 | 0.00 | 46.81 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1516.16 |
PERIMETER_BOT_ZN_2 | 04-JUL-09:32 | 0.00 | 0.00 | 0.00 | -11152.02 | 0.00 | 0.00 | 16.06 | 25.34 | 317.77 | 8617.56 | 0.00 | 0.00 | 2258.25 | 0.00 | -0.00 | 0.00 | -82.95 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-14:13 | 0.00 | 0.00 | 0.00 | -13168.24 | 0.00 | 0.00 | 26.68 | 40.03 | 501.96 | 10563.05 | 0.00 | 0.00 | 2276.58 | 0.00 | -0.00 | 0.00 | -240.06 | 0.00 |
PERIMETER_BOT_ZN_4 | 16-JUL-16:41 | 0.00 | 0.00 | 0.00 | -11392.88 | 0.00 | 0.00 | 15.80 | 25.34 | 317.76 | 9090.99 | 0.00 | 14.74 | 1928.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 13-AUG-15:52 | 0.00 | 0.00 | 0.00 | -7753.85 | 0.00 | 0.00 | 29.75 | 40.03 | 501.96 | 2487.12 | 0.00 | 191.27 | 4503.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-09:32 | 0.00 | 0.00 | 0.00 | -13937.37 | 0.00 | 0.00 | 14.06 | 25.34 | 317.77 | 8520.57 | 0.00 | 0.00 | 5206.58 | 0.00 | -0.00 | 0.00 | -146.95 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-14:13 | 0.00 | 0.00 | 0.00 | -15144.20 | 0.00 | 0.00 | 25.68 | 40.03 | 501.96 | 10490.70 | 0.00 | 0.00 | 4468.92 | 0.00 | -0.00 | 0.00 | -383.09 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JUL-16:42 | 0.00 | 0.00 | 0.00 | -13919.95 | 0.00 | 0.00 | 12.81 | 25.34 | 317.76 | 11201.78 | 0.00 | 0.00 | 2442.02 | 0.00 | -0.00 | 0.00 | -79.76 | 0.00 |
TOPFLOOR_PLENUM | 27-JUN-14:55 | 0.00 | -10484.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10490.19 | 0.00 | -0.00 | 0.00 | -5.50 | 0.00 |
MIDFLOOR_PLENUM | 17-JUL-12:10 | 0.00 | -5179.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.71 | 5131.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 17-JUL-12:10 | 0.00 | -5404.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.40 | 5367.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-04:02 | 0.00 | 9289.88 | 0.00 | -169846.98 | 0.00 | 0.00 | 0.00 | 3119.77 | 18045.99 | 0.00 | 0.00 | 0.00 | 148907.71 | 0.00 | -7021.69 | 0.00 | -2494.67 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 22747.06 | 0.00 | 0.00 | 0.00 | 0.00 | 615.87 | 5138.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -28501.38 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 24964.92 | 0.00 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -28755.66 |
CORE_TOP | 26-DEC-05:01 | 0.00 | 0.00 | 31848.41 | 0.00 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -35639.15 |
PERIMETER_TOP_ZN_3 | 05-FEB-22:32 | 0.00 | 0.00 | 10863.52 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2997.37 | 0.00 | -2537.83 | -5895.21 |
PERIMETER_TOP_ZN_2 | 26-DEC-01:42 | 0.00 | 0.00 | 12074.48 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1901.07 | 0.00 | -1610.41 | -9027.79 |
PERIMETER_TOP_ZN_1 | 26-DEC-01:42 | 0.00 | 0.00 | 15344.79 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2954.00 | 0.00 | -2402.48 | -10722.52 |
PERIMETER_TOP_ZN_4 | 05-FEB-22:32 | 0.00 | 0.00 | 13309.03 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 317.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2063.29 | 0.00 | -1730.61 | -9874.00 |
PERIMETER_BOT_ZN_3 | 06-FEB-02:13 | 0.00 | 0.00 | 7881.85 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3317.72 | 0.00 | -1354.06 | -3944.28 |
PERIMETER_BOT_ZN_2 | 13-FEB-03:32 | 0.00 | 0.00 | 9186.48 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1781.38 | 0.00 | -1089.08 | -6780.82 |
PERIMETER_BOT_ZN_1 | 07-FEB-07:10 | 0.00 | 0.00 | 15632.60 | 0.00 | 0.00 | 0.00 | 214.33 | 389.51 | 669.28 | 0.00 | 0.00 | 0.00 | 19179.02 | 0.00 | -3768.43 | 0.00 | -32316.31 | 0.00 |
PERIMETER_BOT_ZN_4 | 13-FEB-03:32 | 0.00 | 0.00 | 9687.46 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1844.08 | 0.00 | -1089.10 | -7219.06 |
PERIMETER_MID_ZN_3 | 21-FEB-04:02 | 0.00 | 0.00 | 9061.28 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2992.14 | 0.00 | -2132.24 | -4671.11 |
PERIMETER_MID_ZN_2 | 21-FEB-04:02 | 0.00 | 0.00 | 11245.52 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1924.10 | 0.00 | -1451.51 | -8334.69 |
PERIMETER_MID_ZN_1 | 21-FEB-03:22 | 0.00 | 0.00 | 13300.72 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2921.88 | 0.00 | -2225.40 | -8887.64 |
PERIMETER_MID_ZN_4 | 21-FEB-04:02 | 0.00 | 0.00 | 11386.16 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1995.31 | 0.00 | -1451.94 | -8403.69 |
TOPFLOOR_PLENUM | 11-DEC-06:12 | 16831.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -276.82 | -16554.73 |
MIDFLOOR_PLENUM | 02-JAN-07:11 | 10108.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -267.37 | -9841.11 |
FIRSTFLOOR_PLENUM | 02-JAN-07:01 | 8834.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -210.58 | -8624.18 |
Total Facility | 02-JAN-05:01 | 12458.47 | 0.00 | 205167.07 | 0.00 | 0.00 | 0.00 | 0.00 | 3119.77 | 18045.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17457.06 | 0.00 | -8534.02 | -212800.22 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.4833 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.8922 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.1299 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.3620 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.5356 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0422 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.7416 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3656 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.5650 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3979 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.7678 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4744 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8681 | 2.8681 | 0.7773 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0948 | 2.0948 | 0.7520 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2206 | 2.2206 | 0.7839 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6879 | 0.6879 | 0.1651 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7795 | 0.7795 | 0.1559 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9855 | 0.9855 | 0.1971 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8621 | 0.8621 | 0.1724 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5323 | 0.5323 | 0.1640 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6348 | 0.6348 | 0.1270 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7785 | 0.7785 | 0.1635 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6695 | 0.6695 | 0.1339 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5979 | 0.5979 | 0.1584 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7579 | 0.7579 | 0.1516 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8891 | 0.8891 | 0.1778 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7902 | 0.7902 | 0.1580 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.4833 | 4.8922 | 5.4833 | 1.3656 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.1299 | 4.3620 | 5.1299 | 1.3979 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.5356 | 5.0422 | 5.5356 | 1.4744 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4341 | 1.4341 | 0.7773 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0474 | 1.0474 | 0.7520 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1103 | 1.1103 | 0.7839 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3440 | 0.3440 | 0.1651 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3898 | 0.3898 | 0.1559 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4927 | 0.4927 | 0.1971 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4311 | 0.4311 | 0.1724 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2662 | 0.2662 | 0.1640 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3174 | 0.3174 | 0.1270 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3893 | 0.3893 | 0.1635 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3347 | 0.3347 | 0.1339 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2989 | 0.2989 | 0.1584 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3789 | 0.3789 | 0.1516 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4446 | 0.4446 | 0.1778 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3951 | 0.3951 | 0.1580 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.7416 | 1.3656 | 1.3656 | 1.3656 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.5650 | 1.3979 | 1.3979 | 1.3979 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.7678 | 1.4744 | 1.4744 | 1.4744 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 556.17 |
Number of hours cooling loads not met | 54.33 |
Number of hours not met | 610.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 290.04 | 201182.34 | 241.29 | 109362.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 137.73 | 76834.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 280.83 | 28079.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 71.93 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 641.30 | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 12.98 | 927.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 92.39 | 28081.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 112.31 | 10471.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 762.04 | 1647.95 |
Natural Gas | 0.00 | 353.60 |
Additional | 0.00 | 0.00 |
Total | 762.04 | 2001.55 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 56.37 |
Space Heating | 58.21 |
Space Cooling | 27.64 |
Fans (All) | 18.54 |
Service Water Heating | 0.00 |
Receptacle Equipment | 152.95 |
Miscellaneous (All) | 330.77 |
Subtotal | 330.77 |
Natural Gas [MJ/m2] | |
Space Heating | 48.43 |
Service Water Heating | 22.54 |
Miscellaneous (All) | 70.97 |
Subtotal | 70.97 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.03 |
Space Heating | 26.55 |
Space Cooling | 6.88 |
Fans (All) | 4.62 |
Service Water Heating | 5.61 |
Receptacle Equipment | 38.07 |
Miscellaneous | 4.24 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2429. | 8760. |
BLDG_EQUIP_SCH | 4487. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8676.83 | 83.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8729.00 | 31.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8700.00 | 60.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8696.17 | 63.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8663.33 | 96.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8758.17 | 1.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8716.17 | 43.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8721.33 | 38.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8682.83 | 77.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8736.17 | 23.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8702.33 | 57.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8700.33 | 59.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8660.00 | 100.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8663.17 | 96.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8660.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 100.00 | 0.00 | 0.00 | 0.00 |
Average | 8712.72 | 47.28 | 0.00 | 0.00 | 0.00 |
Sum | 156829.00 | 851.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128292.00 | 12.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128301.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 12.00 | 0.00 | 0.00 | 0.00 |
Average | 34142.54 | 0.80 | 0.00 | 0.00 | 0.00 |
Sum | 614565.67 | 14.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8254.83 | 505.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8363.50 | 396.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8419.17 | 340.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8320.50 | 439.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8305.50 | 454.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8291.17 | 468.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8287.33 | 472.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8387.67 | 372.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8328.83 | 431.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8215.50 | 544.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8282.67 | 477.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8296.33 | 463.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8285.83 | 474.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8270.83 | 489.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8255.83 | 504.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8005.33 | 754.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8292.17 | 467.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8292.33 | 467.67 | 0.00 | 0.00 | 0.00 |
Min | 8005.33 | 340.83 | 0.00 | 0.00 | 0.00 |
Max | 8419.17 | 754.67 | 0.00 | 0.00 | 0.00 |
Average | 8286.41 | 473.59 | 0.00 | 0.00 | 0.00 |
Sum | 149155.33 | 8524.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128054.67 | 249.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128142.50 | 161.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128121.67 | 182.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24885.67 | 23.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14012.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24893.50 | 15.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14012.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24903.50 | 5.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24251.00 | 658.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24897.50 | 11.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24899.00 | 10.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128142.50 | 658.00 | 0.00 | 0.00 | 0.00 |
Average | 34069.72 | 73.61 | 0.00 | 0.00 | 0.00 |
Sum | 613255.00 | 1325.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:11
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.870931E+10 | 9086.56 | 20-JAN-17:00 | -1.1 | -3.7 | 0.175776E+10 | 2606.54 | 20-JAN-14:09 | -1.1 | -3.7 |
February | 0.853358E+10 | 9416.44 | 17-FEB-17:00 | 1.10 | 0.20 | 0.162033E+10 | 2606.58 | 17-FEB-14:20 | 1.10 | 0.20 |
March | 0.128822E+11 | 21716.30 | 17-MAR-05:03 | 10.50 | 9.94 | 0.210097E+10 | 2608.70 | 30-MAR-13:50 | 7.12 | 6.04 |
April | 0.143294E+11 | 19049.74 | 25-APR-05:03 | 6.70 | 5.86 | 0.189838E+10 | 2606.67 | 21-APR-13:00 | 6.70 | 5.86 |
May | 0.203284E+11 | 40456.24 | 22-MAY-05:03 | 9.08 | 7.07 | 0.207511E+10 | 2606.68 | 05-MAY-13:09 | 9.08 | 7.07 |
June | 0.254317E+11 | 43023.77 | 19-JUN-04:03 | 16.70 | 15.97 | 0.206991E+10 | 2606.81 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.264480E+11 | 44252.39 | 24-JUL-04:02 | 16.10 | 15.07 | 0.192508E+10 | 2606.68 | 12-JUL-09:00 | 16.10 | 15.07 |
August | 0.280523E+11 | 44051.50 | 21-AUG-04:02 | 14.90 | 13.34 | 0.216065E+10 | 2629.26 | 14-AUG-09:00 | 14.90 | 13.34 |
September | 0.231431E+11 | 44722.59 | 18-SEP-04:02 | 10.40 | 9.46 | 0.191744E+10 | 2606.78 | 12-SEP-13:09 | 10.40 | 9.46 |
October | 0.170640E+11 | 39953.05 | 13-OCT-05:03 | 10.50 | 10.16 | 0.198562E+10 | 2606.67 | 03-OCT-09:00 | 10.50 | 10.16 |
November | 0.127057E+11 | 18885.00 | 02-NOV-07:02 | 4.40 | 3.64 | 0.194637E+10 | 2606.71 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.953341E+10 | 12152.46 | 01-DEC-09:00 | 13.30 | 11.15 | 0.177891E+10 | 2606.63 | 01-DEC-10:09 | 14.50 | 11.95 |
Annual Sum or Average | 0.207161E+12 | 0.232365E+11 | ||||||||
Minimum of Months | 0.853358E+10 | 9086.56 | -1.1 | -3.7 | 0.162033E+10 | 2606.54 | -1.1 | -3.7 | ||
Maximum of Months | 0.280523E+11 | 44722.59 | 16.70 | 15.97 | 0.216065E+10 | 2629.26 | 20.60 | 15.40 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 196599.28 | 177.11 | 22-FEB-17:20 | 12.07 | 5.77 | 0.00 | 0.00 | 01-FEB-00:10 | 12.07 | 5.77 |
March | 0.317919E+09 | 5347.68 | 15-MAR-14:10 | 26.02 | 16.09 | 0.00 | 0.00 | 01-MAR-00:10 | 26.02 | 16.09 |
April | 0.905368E+09 | 4315.42 | 21-APR-14:50 | 14.90 | 8.32 | 0.00 | 0.00 | 01-APR-00:10 | 14.90 | 8.32 |
May | 0.255633E+10 | 7000.58 | 26-MAY-14:20 | 21.70 | 13.62 | 0.00 | 0.00 | 01-MAY-00:10 | 21.70 | 13.62 |
June | 0.511012E+10 | 10484.69 | 27-JUN-14:55 | 25.60 | 22.78 | 0.00 | 0.00 | 01-JUN-00:10 | 25.60 | 22.78 |
July | 0.642488E+10 | 10350.40 | 21-JUL-13:30 | 31.15 | 21.91 | 0.00 | 0.00 | 01-JUL-00:10 | 31.15 | 21.91 |
August | 0.561943E+10 | 10258.92 | 09-AUG-15:00 | 29.40 | 18.10 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.10 |
September | 0.283270E+10 | 8047.88 | 21-SEP-15:30 | 26.10 | 16.91 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 16.91 |
October | 0.571441E+09 | 4164.06 | 11-OCT-15:10 | 22.12 | 14.59 | 0.00 | 0.00 | 01-OCT-00:10 | 22.12 | 14.59 |
November | 47937933.48 | 947.60 | 04-NOV-15:20 | 18.30 | 13.65 | 0.00 | 0.00 | 01-NOV-00:10 | 18.30 | 13.65 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
Annual Sum or Average | 0.243863E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -1.0 | -1.6 | 0.00 | 0.00 | -1.0 | -1.6 | ||
Maximum of Months | 0.642488E+10 | 10484.69 | 31.15 | 22.78 | 0.00 | 0.00 | 31.15 | 22.78 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3304990.08 | 1994.31 | 04-JAN-05:01 | -12.2 | -12.8 | 0.00 | 0.00 | 01-JAN-00:10 | -12.2 | -12.8 |
February | 3146353.53 | 1858.43 | 09-FEB-05:01 | -11.0 | -11.7 | 0.00 | 0.00 | 01-FEB-00:10 | -11.0 | -11.7 |
March | 0.116443E+09 | 1778.36 | 18-MAR-06:03 | 2.12 | 1.35 | 0.00 | 0.00 | 01-MAR-00:10 | 2.12 | 1.35 |
April | 0.248554E+09 | 1940.13 | 11-APR-06:01 | 3.30 | 2.15 | 0.00 | 0.00 | 01-APR-00:10 | 3.30 | 2.15 |
May | 0.100582E+10 | 2211.65 | 31-MAY-16:00 | 22.20 | 14.47 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 14.47 |
June | 0.277604E+10 | 4417.24 | 12-JUN-15:30 | 29.15 | 20.10 | 0.00 | 0.00 | 01-JUN-00:10 | 29.15 | 20.10 |
July | 0.377045E+10 | 5179.41 | 17-JUL-12:10 | 27.30 | 21.00 | 0.00 | 0.00 | 01-JUL-00:10 | 27.30 | 21.00 |
August | 0.345660E+10 | 4729.54 | 07-AUG-06:15 | 20.77 | 18.75 | 0.00 | 0.00 | 01-AUG-00:10 | 20.77 | 18.75 |
September | 0.169079E+10 | 3285.11 | 18-SEP-13:00 | 18.90 | 12.42 | 0.00 | 0.00 | 01-SEP-00:10 | 18.90 | 12.42 |
October | 0.308622E+09 | 2312.93 | 24-OCT-06:01 | 1.70 | 0.40 | 0.00 | 0.00 | 01-OCT-00:10 | 1.70 | 0.40 |
November | 38774413.69 | 1407.15 | 02-NOV-06:02 | 4.40 | 3.64 | 0.00 | 0.00 | 01-NOV-00:10 | 4.40 | 3.64 |
December | 3317336.70 | 1756.91 | 28-DEC-05:01 | -11.8 | -12.1 | 0.00 | 0.00 | 01-DEC-00:10 | -11.8 | -12.1 |
Annual Sum or Average | 0.134219E+11 | 0.00 | ||||||||
Minimum of Months | 3146353.53 | 1407.15 | -12.2 | -12.8 | 0.00 | 0.00 | -12.2 | -12.8 | ||
Maximum of Months | 0.377045E+10 | 5179.41 | 29.15 | 21.00 | 0.00 | 0.00 | 29.15 | 21.00 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 49196558.89 | 1782.20 | 06-JAN-07:10 | -12.4 | -13.0 | 0.00 | 0.00 | 01-JAN-00:10 | -12.4 | -13.0 |
February | 50389419.86 | 1947.01 | 10-FEB-17:10 | -7.4 | -8.0 | 0.00 | 0.00 | 01-FEB-00:10 | -7.4 | -8.0 |
March | 0.256289E+09 | 2422.06 | 24-MAR-06:10 | -5.1 | -6.3 | 0.00 | 0.00 | 01-MAR-00:10 | -5.1 | -6.3 |
April | 0.493997E+09 | 2511.51 | 10-APR-17:01 | 2.80 | 2.25 | 0.00 | 0.00 | 01-APR-00:10 | 2.80 | 2.25 |
May | 0.154474E+10 | 2477.64 | 24-MAY-16:08 | 11.70 | 11.07 | 0.00 | 0.00 | 01-MAY-00:10 | 11.70 | 11.07 |
June | 0.322607E+10 | 4694.79 | 12-JUN-12:10 | 29.40 | 20.05 | 0.00 | 0.00 | 01-JUN-00:10 | 29.40 | 20.05 |
July | 0.415481E+10 | 5406.34 | 17-JUL-12:10 | 27.30 | 21.00 | 0.00 | 0.00 | 01-JUL-00:10 | 27.30 | 21.00 |
August | 0.411942E+10 | 5267.59 | 07-AUG-06:15 | 20.77 | 18.75 | 0.00 | 0.00 | 01-AUG-00:10 | 20.77 | 18.75 |
September | 0.247137E+10 | 4405.10 | 18-SEP-12:10 | 18.40 | 12.35 | 0.00 | 0.00 | 01-SEP-00:10 | 18.40 | 12.35 |
October | 0.623608E+09 | 2296.11 | 13-OCT-16:06 | 11.02 | 7.99 | 0.00 | 0.00 | 01-OCT-00:10 | 11.02 | 7.99 |
November | 0.140607E+09 | 1889.03 | 07-NOV-07:01 | 1.78 | 0.46 | 0.00 | 0.00 | 01-NOV-00:10 | 1.78 | 0.46 |
December | 38356189.34 | 1552.83 | 08-DEC-07:10 | -10.4 | -10.8 | 0.00 | 0.00 | 01-DEC-00:10 | -10.4 | -10.8 |
Annual Sum or Average | 0.171689E+11 | 0.00 | ||||||||
Minimum of Months | 38356189.34 | 1552.83 | -12.4 | -13.0 | 0.00 | 0.00 | -12.4 | -13.0 | ||
Maximum of Months | 0.415481E+10 | 5406.34 | 29.40 | 21.00 | 0.00 | 0.00 | 29.40 | 21.00 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.473024E+10 | 6052.65 | 12-JAN-16:50 | -6.6 | -8.3 | 0.151308E+10 | 2185.84 | 20-JAN-14:00 | 0.60 | -3.3 |
February | 0.460159E+10 | 6192.70 | 17-FEB-17:00 | 1.10 | 0.20 | 0.138628E+10 | 2229.28 | 17-FEB-14:00 | 1.10 | 0.20 |
March | 0.859936E+10 | 11813.05 | 16-MAR-16:00 | 15.60 | 13.95 | 0.184537E+10 | 2606.61 | 16-MAR-09:00 | 15.60 | 13.95 |
April | 0.915268E+10 | 10688.74 | 21-APR-16:00 | 13.30 | 8.77 | 0.177166E+10 | 2606.62 | 21-APR-13:00 | 13.30 | 8.77 |
May | 0.132859E+11 | 22673.19 | 24-MAY-05:03 | 18.80 | 15.75 | 0.204948E+10 | 2606.65 | 05-MAY-13:09 | 18.80 | 15.75 |
June | 0.177000E+11 | 31774.05 | 19-JUN-04:03 | 16.70 | 15.97 | 0.206397E+10 | 2606.79 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.191005E+11 | 32716.06 | 17-JUL-04:04 | 23.22 | 21.05 | 0.192114E+10 | 2606.66 | 12-JUL-09:00 | 23.22 | 21.05 |
August | 0.193649E+11 | 31939.80 | 07-AUG-04:02 | 20.00 | 18.50 | 0.215668E+10 | 2606.82 | 02-AUG-13:09 | 20.00 | 18.50 |
September | 0.148464E+11 | 32301.87 | 18-SEP-04:02 | 10.40 | 9.46 | 0.190607E+10 | 2606.76 | 12-SEP-13:09 | 10.40 | 9.46 |
October | 0.997107E+10 | 12471.77 | 12-OCT-16:00 | 18.30 | 14.87 | 0.188169E+10 | 2606.61 | 06-OCT-13:00 | 18.30 | 14.87 |
November | 0.771915E+10 | 7760.24 | 01-NOV-16:00 | 9.40 | 6.91 | 0.170794E+10 | 2589.46 | 01-NOV-13:00 | 9.40 | 6.91 |
December | 0.537344E+10 | 6528.32 | 01-DEC-17:00 | 7.20 | 4.89 | 0.148533E+10 | 2318.99 | 01-DEC-14:00 | 7.20 | 4.89 |
Annual Sum or Average | 0.134445E+12 | 0.216887E+11 | ||||||||
Minimum of Months | 0.460159E+10 | 6052.65 | -6.6 | -8.3 | 0.138628E+10 | 2185.84 | 0.60 | -3.3 | ||
Maximum of Months | 0.193649E+11 | 32716.06 | 23.22 | 21.05 | 0.215668E+10 | 2606.82 | 23.22 | 21.05 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296818E+10 | 5729.80 | 11-JAN-17:00 | 11.10 | 9.84 | 0.146627E+10 | 2052.65 | 06-JAN-14:00 | 11.10 | 9.84 |
February | 0.321743E+10 | 6002.22 | 28-FEB-17:00 | -0.6 | -3.0 | 0.134257E+10 | 2114.16 | 17-FEB-14:00 | -0.6 | -3.0 |
March | 0.713667E+10 | 11960.39 | 16-MAR-16:00 | 15.60 | 13.95 | 0.175627E+10 | 2606.61 | 15-MAR-13:30 | 15.60 | 13.95 |
April | 0.844531E+10 | 11441.40 | 21-APR-16:00 | 13.30 | 8.77 | 0.167794E+10 | 2606.62 | 21-APR-13:00 | 13.30 | 8.77 |
May | 0.128425E+11 | 15789.97 | 31-MAY-16:00 | 22.20 | 14.47 | 0.200974E+10 | 2606.65 | 05-MAY-13:09 | 22.20 | 14.47 |
June | 0.178188E+11 | 32214.38 | 19-JUN-05:03 | 16.70 | 15.97 | 0.205639E+10 | 2690.13 | 27-JUN-15:30 | 25.85 | 22.66 |
July | 0.195771E+11 | 33739.45 | 05-JUL-04:02 | 18.48 | 16.54 | 0.191903E+10 | 2606.66 | 24-JUL-13:39 | 25.93 | 17.98 |
August | 0.192334E+11 | 34411.96 | 07-AUG-04:02 | 20.00 | 18.50 | 0.215089E+10 | 2606.82 | 02-AUG-13:09 | 20.00 | 18.50 |
September | 0.138084E+11 | 24438.84 | 18-SEP-05:03 | 9.50 | 8.65 | 0.188178E+10 | 2606.76 | 12-SEP-13:09 | 9.50 | 8.65 |
October | 0.885738E+10 | 12089.44 | 12-OCT-16:00 | 18.30 | 14.87 | 0.176347E+10 | 2606.60 | 06-OCT-13:00 | 18.30 | 14.87 |
November | 0.604309E+10 | 7327.74 | 01-NOV-16:00 | 9.40 | 6.91 | 0.157500E+10 | 2452.69 | 01-NOV-13:00 | 9.40 | 6.91 |
December | 0.331970E+10 | 6195.19 | 01-DEC-15:00 | 7.20 | 5.63 | 0.142027E+10 | 2185.34 | 01-DEC-14:00 | 7.20 | 5.63 |
Annual Sum or Average | 0.123268E+12 | 0.210196E+11 | ||||||||
Minimum of Months | 0.296818E+10 | 5729.80 | -0.6 | -3.0 | 0.134257E+10 | 2052.65 | -0.6 | -3.0 | ||
Maximum of Months | 0.195771E+11 | 34411.96 | 22.20 | 18.50 | 0.215089E+10 | 2690.13 | 25.93 | 22.66 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12835350.12 | 992.21 | 14-JAN-17:03 | 3.22 | 2.72 | 0.304170E+09 | 406.69 | 23-JAN-14:30 | -7.5 | -8.9 |
February | 18555630.70 | 998.44 | 18-FEB-17:03 | 0.82 | -0.6 | 0.275521E+09 | 406.69 | 06-FEB-14:30 | 0.82 | -0.6 |
March | 0.677642E+09 | 3688.25 | 15-MAR-14:50 | 25.68 | 16.21 | 0.349486E+09 | 549.50 | 15-MAR-13:30 | 25.68 | 16.21 |
April | 0.122772E+10 | 2336.55 | 21-APR-15:20 | 14.43 | 8.49 | 0.327445E+09 | 549.49 | 21-APR-13:00 | 14.43 | 8.49 |
May | 0.267759E+10 | 4704.01 | 23-MAY-14:40 | 23.90 | 13.32 | 0.409518E+09 | 549.50 | 10-MAY-13:00 | 23.90 | 13.32 |
June | 0.472739E+10 | 7319.36 | 27-JUN-15:47 | 26.02 | 22.57 | 0.431286E+09 | 578.44 | 27-JUN-15:30 | 26.02 | 22.57 |
July | 0.565653E+10 | 9363.69 | 16-JUL-16:52 | 27.20 | 20.15 | 0.404606E+09 | 549.57 | 21-JUL-13:39 | 31.33 | 21.85 |
August | 0.515120E+10 | 7360.45 | 06-AUG-14:02 | 26.97 | 18.51 | 0.450969E+09 | 549.54 | 02-AUG-13:09 | 26.97 | 18.51 |
September | 0.298121E+10 | 4824.88 | 15-SEP-14:00 | 25.60 | 21.03 | 0.385149E+09 | 549.52 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.128533E+10 | 2457.85 | 12-OCT-15:30 | 18.30 | 15.05 | 0.343865E+09 | 549.49 | 12-OCT-13:00 | 18.30 | 15.05 |
November | 0.368479E+09 | 1386.33 | 16-NOV-16:50 | 18.12 | 13.51 | 0.307476E+09 | 477.91 | 16-NOV-14:00 | 18.12 | 13.51 |
December | 33883413.33 | 1087.46 | 01-DEC-13:20 | 12.03 | 10.45 | 0.293124E+09 | 406.69 | 11-DEC-14:39 | -8.1 | -9.2 |
Annual Sum or Average | 0.248184E+11 | 0.428261E+10 | ||||||||
Minimum of Months | 12835350.12 | 992.21 | 0.82 | -0.6 | 0.275521E+09 | 406.69 | -8.1 | -9.2 | ||
Maximum of Months | 0.565653E+10 | 9363.69 | 27.20 | 22.57 | 0.450969E+09 | 578.44 | 31.33 | 22.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12646455.51 | 927.55 | 14-JAN-17:03 | 3.22 | 2.72 | 0.192966E+09 | 257.46 | 03-JAN-10:09 | 3.22 | 2.72 |
February | 89545773.46 | 1187.38 | 28-FEB-10:10 | -3.6 | -5.3 | 0.175463E+09 | 286.78 | 28-FEB-10:20 | -3.3 | -5.1 |
March | 0.848962E+09 | 2842.77 | 15-MAR-14:00 | 26.10 | 16.06 | 0.226211E+09 | 347.88 | 15-MAR-13:30 | 26.10 | 16.06 |
April | 0.155379E+10 | 4813.09 | 24-APR-09:20 | 6.47 | 3.13 | 0.220578E+09 | 347.88 | 21-APR-13:00 | 6.47 | 3.13 |
May | 0.310205E+10 | 7178.00 | 31-MAY-09:00 | 17.80 | 13.21 | 0.264196E+09 | 347.88 | 26-MAY-09:00 | 17.80 | 13.21 |
June | 0.473432E+10 | 10546.87 | 11-JUN-10:43 | 24.90 | 17.26 | 0.273860E+09 | 348.31 | 12-JUN-09:00 | 27.80 | 19.41 |
July | 0.544468E+10 | 13211.41 | 04-JUL-09:02 | 21.28 | 17.22 | 0.256442E+09 | 348.45 | 17-JUL-09:09 | 25.10 | 20.50 |
August | 0.502343E+10 | 12222.61 | 06-AUG-09:23 | 24.75 | 17.55 | 0.285930E+09 | 348.31 | 10-AUG-09:00 | 27.80 | 20.31 |
September | 0.320728E+10 | 6153.84 | 18-SEP-09:30 | 16.15 | 11.54 | 0.246193E+09 | 347.89 | 12-SEP-13:09 | 16.15 | 11.54 |
October | 0.135064E+10 | 3708.58 | 11-OCT-09:40 | 16.13 | 11.96 | 0.224906E+09 | 347.87 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.385543E+09 | 1365.82 | 03-NOV-09:50 | 5.32 | 2.80 | 0.196085E+09 | 315.00 | 03-NOV-09:00 | 5.60 | 2.99 |
December | 28676017.69 | 934.68 | 16-DEC-17:03 | 3.30 | 1.70 | 0.186107E+09 | 257.47 | 26-DEC-14:30 | -9.4 | -11.0 |
Annual Sum or Average | 0.257816E+11 | 0.274894E+10 | ||||||||
Minimum of Months | 12646455.51 | 927.55 | -3.6 | -5.3 | 0.175463E+09 | 257.46 | -9.4 | -11.0 | ||
Maximum of Months | 0.544468E+10 | 13211.41 | 26.10 | 17.55 | 0.285930E+09 | 348.45 | 27.80 | 20.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.357235E+09 | 2820.55 | 12-JAN-13:30 | -6.7 | -9.2 | 0.314878E+09 | 549.49 | 12-JAN-14:00 | -5.6 | -8.1 |
February | 0.474929E+09 | 5308.69 | 28-FEB-13:50 | 0.00 | -3.0 | 0.289076E+09 | 549.49 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.182219E+10 | 9675.23 | 15-MAR-13:30 | 25.55 | 15.84 | 0.380714E+09 | 549.53 | 15-MAR-13:30 | 25.55 | 15.84 |
April | 0.236561E+10 | 7678.94 | 21-APR-13:30 | 15.00 | 8.17 | 0.347355E+09 | 549.52 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.407359E+10 | 7954.34 | 26-MAY-13:30 | 20.85 | 13.56 | 0.410561E+09 | 549.52 | 10-MAY-13:00 | 20.85 | 13.56 |
June | 0.589552E+10 | 9842.14 | 12-JUN-13:10 | 29.60 | 19.81 | 0.428978E+09 | 568.38 | 27-JUN-15:20 | 25.77 | 22.70 |
July | 0.707322E+10 | 16758.63 | 30-JUL-12:02 | 25.60 | 19.84 | 0.403686E+09 | 550.02 | 31-JUL-13:00 | 25.00 | 19.43 |
August | 0.735030E+10 | 16609.44 | 13-AUG-12:43 | 29.82 | 22.72 | 0.450425E+09 | 550.02 | 03-AUG-13:00 | 29.82 | 22.72 |
September | 0.562554E+10 | 16523.16 | 04-SEP-14:13 | 18.17 | 13.03 | 0.389488E+09 | 550.16 | 22-SEP-13:50 | 23.72 | 15.13 |
October | 0.292163E+10 | 11402.72 | 11-OCT-12:30 | 21.95 | 13.79 | 0.371559E+09 | 549.85 | 31-OCT-13:00 | 15.00 | 10.56 |
November | 0.106425E+10 | 6782.51 | 03-NOV-12:35 | 8.53 | 4.68 | 0.328737E+09 | 549.50 | 01-NOV-13:00 | 8.53 | 4.68 |
December | 0.270323E+09 | 3159.08 | 16-DEC-13:30 | 5.60 | 3.03 | 0.298677E+09 | 543.02 | 04-DEC-14:50 | 5.60 | 3.03 |
Annual Sum or Average | 0.392943E+11 | 0.441413E+10 | ||||||||
Minimum of Months | 0.270323E+09 | 2820.55 | -6.7 | -9.2 | 0.289076E+09 | 543.02 | -5.6 | -8.1 | ||
Maximum of Months | 0.735030E+10 | 16758.63 | 29.82 | 22.72 | 0.450425E+09 | 568.38 | 29.82 | 22.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40477153.31 | 1145.46 | 06-JAN-15:40 | -2.2 | -4.8 | 0.192985E+09 | 257.46 | 23-JAN-10:09 | -7.0 | -8.8 |
February | 0.102545E+09 | 1646.30 | 28-FEB-16:40 | -0.2 | -2.7 | 0.176090E+09 | 327.44 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.862904E+09 | 3601.35 | 15-MAR-14:20 | 25.93 | 16.12 | 0.223555E+09 | 347.85 | 15-MAR-13:39 | 25.93 | 16.12 |
April | 0.154045E+10 | 5922.77 | 24-APR-16:00 | 13.30 | 7.63 | 0.207037E+09 | 347.85 | 21-APR-13:00 | 13.30 | 7.63 |
May | 0.317203E+10 | 11565.86 | 07-MAY-17:23 | 14.45 | 5.57 | 0.251415E+09 | 347.86 | 10-MAY-13:00 | 26.10 | 17.84 |
June | 0.489286E+10 | 14284.06 | 11-JUN-16:42 | 25.60 | 17.82 | 0.269134E+09 | 372.98 | 27-JUN-15:50 | 26.02 | 22.57 |
July | 0.532508E+10 | 15259.34 | 02-JUL-17:22 | 24.45 | 16.81 | 0.254389E+09 | 347.87 | 24-JUL-13:39 | 25.93 | 17.98 |
August | 0.501245E+10 | 13947.02 | 12-AUG-17:05 | 24.72 | 16.93 | 0.282399E+09 | 347.88 | 02-AUG-13:09 | 24.72 | 16.93 |
September | 0.314604E+10 | 11400.40 | 10-SEP-16:03 | 17.52 | 11.16 | 0.238248E+09 | 347.86 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.139545E+10 | 5749.08 | 11-OCT-16:00 | 21.70 | 14.52 | 0.215530E+09 | 347.84 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.410644E+09 | 1640.07 | 03-NOV-15:40 | 9.27 | 5.12 | 0.195841E+09 | 325.70 | 03-NOV-15:50 | 9.08 | 5.02 |
December | 46495199.54 | 1172.06 | 04-DEC-15:50 | -0.5 | -3.2 | 0.186097E+09 | 259.56 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.259474E+11 | 0.269272E+10 | ||||||||
Minimum of Months | 40477153.31 | 1145.46 | -2.2 | -4.8 | 0.176090E+09 | 257.46 | -7.0 | -8.8 | ||
Maximum of Months | 0.532508E+10 | 15259.34 | 25.93 | 17.82 | 0.282399E+09 | 372.98 | 26.10 | 22.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14102209.07 | 995.27 | 14-JAN-17:03 | 3.22 | 2.72 | 0.304852E+09 | 406.70 | 30-JAN-14:30 | -8.3 | -9.9 |
February | 15887253.06 | 995.88 | 18-FEB-17:03 | 0.82 | -0.6 | 0.276580E+09 | 406.69 | 06-FEB-14:30 | 0.82 | -0.6 |
March | 0.559563E+09 | 1609.08 | 15-MAR-15:30 | 25.30 | 16.10 | 0.344712E+09 | 532.28 | 15-MAR-13:00 | 25.30 | 16.10 |
April | 0.112575E+10 | 1469.87 | 21-APR-15:30 | 14.15 | 8.57 | 0.317812E+09 | 500.80 | 07-APR-13:00 | 14.15 | 8.57 |
May | 0.206962E+10 | 2725.75 | 23-MAY-14:40 | 23.90 | 13.32 | 0.398099E+09 | 549.49 | 10-MAY-13:50 | 23.90 | 13.32 |
June | 0.358954E+10 | 4740.64 | 27-JUN-13:30 | 28.90 | 23.32 | 0.431081E+09 | 549.52 | 22-JUN-13:09 | 28.90 | 23.32 |
July | 0.456334E+10 | 5516.84 | 21-JUL-13:50 | 31.52 | 21.79 | 0.404209E+09 | 549.50 | 12-JUL-09:00 | 31.52 | 21.79 |
August | 0.455396E+10 | 5486.81 | 14-AUG-12:20 | 26.50 | 21.48 | 0.452811E+09 | 556.12 | 14-AUG-09:00 | 26.50 | 21.48 |
September | 0.296881E+10 | 4090.76 | 15-SEP-14:00 | 25.60 | 21.03 | 0.394726E+09 | 549.52 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.177381E+10 | 2228.05 | 05-OCT-14:40 | 18.90 | 12.59 | 0.365437E+09 | 549.48 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.935343E+09 | 1399.55 | 16-NOV-16:50 | 18.12 | 13.51 | 0.318452E+09 | 487.71 | 01-NOV-13:50 | 18.12 | 13.51 |
December | 90335721.60 | 1200.40 | 01-DEC-13:30 | 11.10 | 9.57 | 0.295312E+09 | 431.64 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.222601E+11 | 0.430408E+10 | ||||||||
Minimum of Months | 14102209.07 | 995.27 | 0.82 | -0.6 | 0.276580E+09 | 406.69 | -8.3 | -9.9 | ||
Maximum of Months | 0.456334E+10 | 5516.84 | 31.52 | 23.32 | 0.452811E+09 | 556.12 | 31.52 | 23.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12984854.28 | 826.61 | 14-JAN-07:05 | 3.30 | 2.57 | 0.193551E+09 | 257.48 | 02-JAN-14:30 | 3.30 | 2.57 |
February | 70513288.87 | 891.83 | 28-FEB-10:10 | -3.6 | -5.3 | 0.175902E+09 | 272.25 | 28-FEB-10:20 | -3.3 | -5.1 |
March | 0.689686E+09 | 1458.03 | 15-MAR-14:00 | 26.10 | 16.06 | 0.224915E+09 | 347.86 | 15-MAR-13:00 | 26.10 | 16.06 |
April | 0.126317E+10 | 3376.49 | 24-APR-09:30 | 6.65 | 3.34 | 0.221333E+09 | 347.88 | 21-APR-13:00 | 6.65 | 3.34 |
May | 0.223037E+10 | 4689.68 | 31-MAY-09:20 | 17.97 | 13.39 | 0.264809E+09 | 347.88 | 26-MAY-09:00 | 17.97 | 13.39 |
June | 0.380744E+10 | 7824.26 | 11-JUN-10:13 | 24.60 | 17.02 | 0.274841E+09 | 347.89 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.465200E+10 | 11152.67 | 04-JUL-09:32 | 21.83 | 17.44 | 0.256698E+09 | 348.27 | 17-JUL-09:09 | 25.10 | 20.50 |
August | 0.458478E+10 | 8192.81 | 06-AUG-09:23 | 24.75 | 17.55 | 0.287393E+09 | 348.70 | 14-AUG-09:00 | 23.90 | 22.00 |
September | 0.313132E+10 | 5188.26 | 18-SEP-09:30 | 16.15 | 11.54 | 0.252071E+09 | 347.89 | 12-SEP-13:09 | 16.15 | 11.54 |
October | 0.158517E+10 | 3402.40 | 11-OCT-09:40 | 16.13 | 11.96 | 0.243243E+09 | 347.88 | 10-OCT-09:09 | 16.13 | 11.96 |
November | 0.788164E+09 | 1241.65 | 03-NOV-08:50 | 3.72 | 1.73 | 0.205173E+09 | 341.80 | 03-NOV-09:09 | 4.18 | 2.03 |
December | 67166861.80 | 898.61 | 01-DEC-13:30 | 11.10 | 9.57 | 0.187155E+09 | 267.57 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.228828E+11 | 0.278708E+10 | ||||||||
Minimum of Months | 12984854.28 | 826.61 | -3.6 | -5.3 | 0.175902E+09 | 257.48 | -3.3 | -5.1 | ||
Maximum of Months | 0.465200E+10 | 11152.67 | 26.10 | 17.55 | 0.287393E+09 | 348.70 | 26.10 | 22.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34131294.96 | 1171.82 | 21-JAN-12:30 | -0.6 | -3.1 | 0.275690E+09 | 406.64 | 26-JAN-10:00 | -4.4 | -6.5 |
February | 55248311.01 | 1377.51 | 18-FEB-14:40 | 2.80 | 0.63 | 0.249457E+09 | 412.32 | 22-FEB-14:00 | 10.60 | 4.92 |
March | 0.585566E+09 | 5896.40 | 15-MAR-13:30 | 25.55 | 15.84 | 0.332521E+09 | 549.50 | 15-MAR-13:00 | 26.10 | 16.06 |
April | 0.893061E+09 | 3212.26 | 22-APR-13:40 | 15.20 | 6.94 | 0.311126E+09 | 549.51 | 21-APR-13:00 | 15.20 | 6.94 |
May | 0.195461E+10 | 4673.24 | 23-MAY-14:30 | 23.90 | 13.29 | 0.378582E+09 | 549.51 | 05-MAY-13:09 | 23.90 | 13.29 |
June | 0.391196E+10 | 11136.91 | 27-JUN-12:00 | 30.00 | 22.87 | 0.416590E+09 | 568.04 | 27-JUN-12:09 | 30.10 | 23.02 |
July | 0.597429E+10 | 11425.89 | 21-JUL-12:00 | 30.00 | 21.57 | 0.401289E+09 | 585.32 | 21-JUL-12:09 | 30.10 | 21.65 |
August | 0.640238E+10 | 13009.31 | 13-AUG-12:43 | 29.82 | 22.72 | 0.447050E+09 | 586.78 | 10-AUG-12:09 | 29.82 | 22.72 |
September | 0.448972E+10 | 13169.01 | 04-SEP-14:13 | 18.17 | 13.03 | 0.387761E+09 | 549.79 | 22-SEP-13:30 | 23.35 | 14.79 |
October | 0.200108E+10 | 9254.27 | 11-OCT-12:40 | 22.03 | 13.91 | 0.357424E+09 | 549.77 | 11-OCT-13:39 | 22.20 | 14.14 |
November | 0.617434E+09 | 2079.40 | 03-NOV-14:30 | 9.70 | 5.23 | 0.311109E+09 | 549.50 | 03-NOV-13:00 | 9.70 | 5.23 |
December | 82862676.30 | 1608.45 | 16-DEC-13:40 | 5.60 | 2.97 | 0.271181E+09 | 406.64 | 13-DEC-10:09 | 5.60 | 2.97 |
Annual Sum or Average | 0.270023E+11 | 0.413978E+10 | ||||||||
Minimum of Months | 34131294.96 | 1171.82 | -0.6 | -3.1 | 0.249457E+09 | 406.64 | -4.4 | -6.5 | ||
Maximum of Months | 0.640238E+10 | 13169.01 | 30.00 | 22.87 | 0.447050E+09 | 586.78 | 30.10 | 23.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34525085.28 | 944.24 | 12-JAN-16:10 | -6.2 | -8.3 | 0.193545E+09 | 265.79 | 12-JAN-16:19 | -6.3 | -8.3 |
February | 71006072.16 | 1177.48 | 28-FEB-16:40 | -0.2 | -2.7 | 0.176207E+09 | 307.98 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.669477E+09 | 1674.72 | 15-MAR-14:20 | 25.93 | 16.12 | 0.221408E+09 | 347.82 | 15-MAR-13:00 | 25.93 | 16.12 |
April | 0.120132E+10 | 3525.62 | 24-APR-17:30 | 11.70 | 7.64 | 0.209103E+09 | 347.63 | 21-APR-13:00 | 11.70 | 7.64 |
May | 0.220329E+10 | 6394.81 | 27-MAY-17:10 | 20.32 | 11.21 | 0.255275E+09 | 347.84 | 23-MAY-13:09 | 20.32 | 11.21 |
June | 0.391049E+10 | 11252.27 | 11-JUN-17:51 | 25.00 | 17.50 | 0.273349E+09 | 347.87 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.445510E+10 | 11393.34 | 16-JUL-16:41 | 27.77 | 20.68 | 0.256263E+09 | 347.86 | 03-JUL-13:39 | 27.77 | 20.68 |
August | 0.450629E+10 | 10806.54 | 27-AUG-17:12 | 22.20 | 18.81 | 0.286946E+09 | 348.70 | 14-AUG-09:00 | 22.20 | 18.81 |
September | 0.293582E+10 | 7037.94 | 04-SEP-17:33 | 17.23 | 12.32 | 0.250404E+09 | 347.87 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.160146E+10 | 4798.16 | 11-OCT-16:00 | 21.70 | 14.52 | 0.233130E+09 | 347.84 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.782560E+09 | 1327.53 | 03-NOV-15:50 | 9.08 | 5.02 | 0.202855E+09 | 336.35 | 03-NOV-15:00 | 8.90 | 4.93 |
December | 80961584.28 | 979.09 | 04-DEC-15:50 | -0.5 | -3.2 | 0.187120E+09 | 271.61 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.224523E+11 | 0.274560E+10 | ||||||||
Minimum of Months | 34525085.28 | 944.24 | -6.2 | -8.3 | 0.176207E+09 | 265.79 | -6.3 | -8.3 | ||
Maximum of Months | 0.450629E+10 | 11393.34 | 27.77 | 20.68 | 0.286946E+09 | 348.70 | 27.77 | 20.68 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26292787.28 | 967.65 | 14-JAN-17:03 | 3.22 | 2.72 | 0.305074E+09 | 406.69 | 23-JAN-10:09 | -7.0 | -8.8 |
February | 49034690.83 | 970.07 | 18-FEB-17:03 | 0.82 | -0.6 | 0.276773E+09 | 406.69 | 06-FEB-14:30 | 0.82 | -0.6 |
March | 0.888318E+09 | 3228.25 | 15-MAR-14:50 | 25.68 | 16.21 | 0.356080E+09 | 549.49 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.149452E+10 | 2225.31 | 21-APR-15:20 | 14.43 | 8.49 | 0.341110E+09 | 549.49 | 21-APR-13:00 | 14.43 | 8.49 |
May | 0.276803E+10 | 4444.80 | 23-MAY-14:40 | 23.90 | 13.32 | 0.421469E+09 | 549.50 | 17-MAY-09:00 | 23.90 | 13.32 |
June | 0.468346E+10 | 6079.28 | 12-JUN-14:50 | 30.10 | 20.02 | 0.434143E+09 | 549.53 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.548980E+10 | 7188.40 | 31-JUL-06:02 | 17.30 | 16.91 | 0.405189E+09 | 549.60 | 20-JUL-13:30 | 17.30 | 16.91 |
August | 0.511684E+10 | 7754.29 | 13-AUG-15:52 | 29.40 | 23.42 | 0.453504E+09 | 549.54 | 02-AUG-13:09 | 29.40 | 23.42 |
September | 0.315150E+10 | 4561.49 | 15-SEP-14:00 | 25.60 | 21.03 | 0.395019E+09 | 549.52 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.167481E+10 | 2606.48 | 12-OCT-15:20 | 18.30 | 15.11 | 0.362542E+09 | 549.49 | 12-OCT-13:00 | 18.30 | 15.11 |
November | 0.761538E+09 | 1409.27 | 16-NOV-17:00 | 18.30 | 13.48 | 0.316345E+09 | 497.51 | 01-NOV-13:50 | 18.30 | 13.48 |
December | 86023614.32 | 1147.91 | 01-DEC-13:30 | 11.10 | 9.57 | 0.294713E+09 | 427.45 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.261902E+11 | 0.436196E+10 | ||||||||
Minimum of Months | 26292787.28 | 967.65 | 0.82 | -0.6 | 0.276773E+09 | 406.69 | -7.0 | -8.8 | ||
Maximum of Months | 0.548980E+10 | 7754.29 | 30.10 | 23.42 | 0.453504E+09 | 549.60 | 29.40 | 23.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 29246518.90 | 916.29 | 14-JAN-17:03 | 3.22 | 2.72 | 0.142242E+09 | 250.68 | 02-JAN-09:00 | 3.22 | 2.72 |
February | 0.127160E+09 | 1268.69 | 28-FEB-10:00 | -3.9 | -5.5 | 0.129579E+09 | 296.53 | 28-FEB-09:00 | -3.9 | -5.5 |
March | 0.101116E+10 | 2583.18 | 14-MAR-10:30 | 20.80 | 17.14 | 0.169070E+09 | 338.72 | 15-MAR-14:20 | 25.93 | 16.12 |
April | 0.179906E+10 | 5600.22 | 24-APR-08:50 | 5.92 | 2.67 | 0.165667E+09 | 339.05 | 06-APR-10:30 | 5.92 | 2.67 |
May | 0.315537E+10 | 7331.92 | 31-MAY-08:40 | 17.60 | 13.16 | 0.197179E+09 | 339.18 | 08-MAY-07:00 | 17.60 | 13.16 |
June | 0.460405E+10 | 11328.84 | 11-JUN-10:23 | 24.70 | 17.10 | 0.202666E+09 | 338.82 | 23-JUN-08:00 | 15.60 | 11.53 |
July | 0.521296E+10 | 13938.87 | 04-JUL-09:32 | 21.83 | 17.44 | 0.190127E+09 | 342.41 | 17-JUL-07:19 | 23.50 | 20.94 |
August | 0.488474E+10 | 12902.89 | 06-AUG-09:52 | 25.60 | 17.82 | 0.211565E+09 | 339.89 | 15-AUG-14:39 | 24.23 | 21.18 |
September | 0.329487E+10 | 6642.67 | 10-SEP-10:03 | 15.68 | 10.52 | 0.183925E+09 | 338.74 | 12-SEP-12:20 | 20.77 | 15.37 |
October | 0.164794E+10 | 4323.04 | 11-OCT-09:00 | 15.00 | 11.35 | 0.171535E+09 | 338.73 | 03-OCT-10:09 | 15.00 | 11.35 |
November | 0.660146E+09 | 1482.70 | 03-NOV-09:00 | 3.90 | 1.83 | 0.147387E+09 | 330.30 | 03-NOV-08:00 | 3.90 | 1.83 |
December | 62119186.34 | 1027.11 | 01-DEC-07:05 | 10.68 | 9.22 | 0.137360E+09 | 256.31 | 01-DEC-13:39 | 10.17 | 8.68 |
Annual Sum or Average | 0.264888E+11 | 0.204830E+10 | ||||||||
Minimum of Months | 29246518.90 | 916.29 | -3.9 | -5.5 | 0.129579E+09 | 250.68 | -3.9 | -5.5 | ||
Maximum of Months | 0.521296E+10 | 13938.87 | 25.60 | 17.82 | 0.211565E+09 | 342.41 | 25.93 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472754E+09 | 3816.53 | 12-JAN-13:40 | -6.5 | -9.0 | 0.319559E+09 | 549.49 | 12-JAN-14:00 | -5.6 | -8.1 |
February | 0.601883E+09 | 5524.76 | 28-FEB-13:40 | 0.00 | -2.9 | 0.293934E+09 | 549.49 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.211642E+10 | 9101.29 | 15-MAR-13:30 | 25.55 | 15.84 | 0.392041E+09 | 549.79 | 15-MAR-13:50 | 25.92 | 15.99 |
April | 0.263134E+10 | 7568.24 | 24-APR-13:10 | 11.38 | 6.04 | 0.360969E+09 | 549.52 | 21-APR-13:00 | 11.38 | 6.04 |
May | 0.410077E+10 | 7390.50 | 26-MAY-13:30 | 20.85 | 13.56 | 0.422333E+09 | 549.51 | 05-MAY-13:09 | 20.85 | 13.56 |
June | 0.573860E+10 | 11430.43 | 25-JUN-13:23 | 26.10 | 17.43 | 0.433064E+09 | 549.63 | 12-JUN-13:30 | 26.10 | 17.43 |
July | 0.678154E+10 | 15065.38 | 30-JUL-12:02 | 25.60 | 19.84 | 0.405147E+09 | 550.03 | 17-JUL-13:50 | 25.60 | 19.84 |
August | 0.718586E+10 | 14941.25 | 06-AUG-14:32 | 27.77 | 18.96 | 0.453688E+09 | 550.00 | 03-AUG-13:00 | 27.77 | 18.96 |
September | 0.575235E+10 | 15144.89 | 04-SEP-14:13 | 18.17 | 13.03 | 0.397570E+09 | 550.21 | 22-SEP-13:00 | 23.90 | 15.30 |
October | 0.338093E+10 | 11411.60 | 11-OCT-12:30 | 21.95 | 13.79 | 0.388386E+09 | 549.82 | 11-OCT-13:30 | 22.20 | 14.14 |
November | 0.153424E+10 | 7665.90 | 03-NOV-12:25 | 8.35 | 4.56 | 0.340984E+09 | 549.89 | 06-NOV-10:39 | 8.53 | 4.46 |
December | 0.415428E+09 | 3688.14 | 16-DEC-13:30 | 5.60 | 3.03 | 0.302166E+09 | 549.48 | 04-DEC-14:09 | 5.60 | 3.03 |
Annual Sum or Average | 0.407121E+11 | 0.450984E+10 | ||||||||
Minimum of Months | 0.415428E+09 | 3688.14 | -6.5 | -9.0 | 0.293934E+09 | 549.48 | -5.6 | -8.1 | ||
Maximum of Months | 0.718586E+10 | 15144.89 | 27.77 | 19.84 | 0.453688E+09 | 550.21 | 27.77 | 19.84 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 69405665.00 | 1152.58 | 12-JAN-16:10 | -6.2 | -8.3 | 0.193512E+09 | 271.56 | 12-JAN-16:19 | -6.3 | -8.3 |
February | 0.141881E+09 | 1559.24 | 28-FEB-16:40 | -0.2 | -2.7 | 0.176773E+09 | 335.81 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.102083E+10 | 3287.11 | 15-MAR-14:20 | 25.93 | 16.12 | 0.228112E+09 | 347.85 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.174821E+10 | 5841.71 | 24-APR-16:00 | 13.30 | 7.63 | 0.214397E+09 | 347.85 | 21-APR-13:00 | 13.30 | 7.63 |
May | 0.315787E+10 | 11495.45 | 07-MAY-17:23 | 14.45 | 5.57 | 0.260693E+09 | 347.85 | 17-MAY-09:00 | 18.90 | 14.77 |
June | 0.475227E+10 | 13505.60 | 25-JUN-17:21 | 26.95 | 18.28 | 0.272733E+09 | 347.87 | 22-JUN-13:09 | 26.95 | 18.28 |
July | 0.510339E+10 | 13920.23 | 02-JUL-16:42 | 25.00 | 17.06 | 0.255891E+09 | 347.86 | 03-JUL-13:39 | 25.20 | 16.81 |
August | 0.487897E+10 | 13658.20 | 13-AUG-15:52 | 29.40 | 23.42 | 0.285756E+09 | 347.88 | 02-AUG-13:09 | 29.40 | 23.42 |
September | 0.318140E+10 | 11392.93 | 10-SEP-16:03 | 17.52 | 11.16 | 0.246472E+09 | 347.87 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.171775E+10 | 5643.85 | 11-OCT-16:00 | 21.70 | 14.52 | 0.225684E+09 | 347.84 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.715194E+09 | 1683.73 | 03-NOV-15:00 | 10.00 | 5.48 | 0.200118E+09 | 339.76 | 15-NOV-14:00 | 11.70 | 6.59 |
December | 96600411.80 | 1167.96 | 04-DEC-15:50 | -0.5 | -3.2 | 0.186712E+09 | 273.52 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.265838E+11 | 0.274685E+10 | ||||||||
Minimum of Months | 69405665.00 | 1152.58 | -6.2 | -8.3 | 0.176773E+09 | 271.56 | -6.3 | -8.3 | ||
Maximum of Months | 0.510339E+10 | 13920.23 | 29.40 | 23.42 | 0.285756E+09 | 347.88 | 29.40 | 23.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.309084E+09 | 22747.10 | 02-JAN-05:01 | -0.7 |
February | 16673312.02 | 19583.65 | 06-FEB-07:03 | -14.1 |
March | 822652.48 | 13710.87 | 06-MAR-07:01 | -10.8 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 8208473.11 | 17662.24 | 11-DEC-07:01 | -16.4 |
Annual Sum or Average | 0.334789E+09 | |||
Minimum of Months | 0.00 | 0.00 | -16.4 | |
Maximum of Months | 0.309084E+09 | 22747.10 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.810810E+10 | 15544.40 | 24-JAN-06:13 | -12.0 |
February | 0.710493E+10 | 16316.04 | 06-FEB-06:08 | -13.9 |
March | 0.347676E+10 | 15867.71 | 06-MAR-06:12 | -11.1 |
April | 0.137792E+10 | 11883.62 | 17-APR-05:13 | -4.1 |
May | 0.469892E+09 | 4498.59 | 08-MAY-05:03 | 3.40 |
June | 0.160970E+09 | 5118.62 | 28-JUN-05:03 | 17.20 |
July | 88031476.11 | 7603.71 | 03-JUL-05:03 | 11.78 |
August | 0.138172E+09 | 6535.45 | 01-AUG-05:03 | 11.10 |
September | 0.363942E+09 | 7886.65 | 18-SEP-05:03 | 9.50 |
October | 0.123231E+10 | 9641.51 | 30-OCT-06:02 | -0.4 |
November | 0.273808E+10 | 11786.95 | 24-NOV-06:13 | -3.7 |
December | 0.739610E+10 | 16831.54 | 11-DEC-06:12 | -18.2 |
Annual Sum or Average | 0.326552E+11 | |||
Minimum of Months | 88031476.11 | 4498.59 | -18.2 | |
Maximum of Months | 0.810810E+10 | 16831.54 | 17.20 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.376567E+10 | 10108.47 | 02-JAN-07:11 | -1.1 |
February | 0.328401E+10 | 9184.91 | 06-FEB-07:06 | -14.1 |
March | 0.171231E+10 | 7147.25 | 06-MAR-07:11 | -10.5 |
April | 0.760179E+09 | 3895.04 | 17-APR-06:11 | -4.0 |
May | 0.123095E+09 | 3187.65 | 07-MAY-17:23 | 14.45 |
June | 26129072.42 | 2440.34 | 13-JUN-05:03 | 8.90 |
July | 28560572.41 | 2883.30 | 21-JUL-04:03 | 26.52 |
August | 25145812.34 | 3388.11 | 13-AUG-15:11 | 29.80 |
September | 43666682.53 | 3424.83 | 10-SEP-16:03 | 17.52 |
October | 0.692517E+09 | 3296.38 | 30-OCT-11:01 | 10.97 |
November | 0.133662E+10 | 4226.10 | 24-NOV-07:02 | -3.2 |
December | 0.325558E+10 | 9465.77 | 11-DEC-07:11 | -16.1 |
Annual Sum or Average | 0.150535E+11 | |||
Minimum of Months | 25145812.34 | 2440.34 | -16.1 | |
Maximum of Months | 0.376567E+10 | 10108.47 | 29.80 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286937E+10 | 8834.75 | 02-JAN-07:01 | -1.1 |
February | 0.241234E+10 | 5290.68 | 06-FEB-07:01 | -14.1 |
March | 0.124362E+10 | 4185.38 | 06-MAR-08:55 | -8.3 |
April | 0.432195E+09 | 3631.01 | 05-APR-07:17 | 2.23 |
May | 34898031.46 | 4840.49 | 22-MAY-05:03 | 9.08 |
June | 29167445.39 | 5256.96 | 14-JUN-05:03 | 6.78 |
July | 31908015.96 | 4045.10 | 06-JUL-04:03 | 12.12 |
August | 31199477.59 | 4022.18 | 29-AUG-04:03 | 15.50 |
September | 32559940.96 | 4564.70 | 29-SEP-05:03 | 10.50 |
October | 0.312252E+09 | 5678.41 | 02-OCT-05:02 | 7.20 |
November | 0.978618E+09 | 3300.83 | 09-NOV-08:06 | 5.60 |
December | 0.236794E+10 | 5362.86 | 26-DEC-07:01 | -12.3 |
Annual Sum or Average | 0.107761E+11 | |||
Minimum of Months | 29167445.39 | 3300.83 | -14.1 | |
Maximum of Months | 0.286937E+10 | 8834.75 | 15.50 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117869E+10 | 24964.94 | 02-JAN-05:01 | -0.7 |
February | 0.824252E+09 | 23392.48 | 06-FEB-05:01 | -14.8 |
March | 0.108577E+09 | 21770.29 | 06-MAR-06:01 | -11.1 |
April | 12400229.51 | 20165.57 | 17-APR-06:01 | -4.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 1165006.32 | 19416.77 | 30-OCT-06:01 | -0.4 |
November | 31382827.17 | 20845.32 | 24-NOV-06:01 | -3.8 |
December | 0.617033E+09 | 23267.15 | 11-DEC-05:11 | -17.8 |
Annual Sum or Average | 0.277350E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.8 | |
Maximum of Months | 0.117869E+10 | 24964.94 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.403049E+10 | 31700.90 | 30-JAN-05:11 | -9.6 |
February | 0.339208E+10 | 31792.66 | 06-FEB-05:11 | -14.6 |
March | 0.103786E+10 | 30635.06 | 06-MAR-05:01 | -11.1 |
April | 0.175697E+09 | 28774.38 | 17-APR-05:01 | -4.0 |
May | 345854.85 | 5187.82 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.118554E+09 | 28138.03 | 30-OCT-05:01 | -0.1 |
November | 0.523105E+09 | 28746.34 | 24-NOV-06:01 | -3.8 |
December | 0.317912E+10 | 31848.59 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.124573E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.6 | |
Maximum of Months | 0.403049E+10 | 31848.59 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.688192E+10 | 10616.98 | 09-JAN-02:22 | -8.9 |
February | 0.597124E+10 | 10863.69 | 05-FEB-22:32 | -12.8 |
March | 0.254935E+10 | 10370.02 | 06-MAR-04:42 | -11.1 |
April | 0.527365E+09 | 9971.33 | 17-APR-04:01 | -3.4 |
May | 10275060.48 | 8045.15 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 5691659.90 | 7853.02 | 30-SEP-06:03 | 7.30 |
October | 0.385815E+09 | 9657.36 | 30-OCT-04:01 | -0.5 |
November | 0.149921E+10 | 9753.92 | 24-NOV-05:01 | -3.0 |
December | 0.606748E+10 | 10851.30 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.238983E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.688192E+10 | 10863.69 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408871E+10 | 11747.18 | 09-JAN-02:22 | -8.9 |
February | 0.352087E+10 | 12073.09 | 05-FEB-22:32 | -12.8 |
March | 0.119883E+10 | 11406.87 | 06-MAR-04:42 | -11.1 |
April | 0.226212E+09 | 11137.75 | 17-APR-04:01 | -3.4 |
May | 4003066.87 | 5531.82 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 3252491.85 | 5700.22 | 30-SEP-06:03 | 7.30 |
October | 0.204498E+09 | 10800.74 | 30-OCT-04:01 | -0.5 |
November | 0.872667E+09 | 10852.86 | 24-NOV-05:01 | -3.0 |
December | 0.382120E+10 | 12074.83 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.139402E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.408871E+10 | 12074.83 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.511248E+10 | 14898.26 | 09-JAN-02:22 | -8.9 |
February | 0.457919E+10 | 15315.34 | 13-FEB-03:32 | -8.9 |
March | 0.153945E+10 | 14436.31 | 06-MAR-04:42 | -11.1 |
April | 0.434304E+09 | 14046.69 | 17-APR-04:01 | -3.4 |
May | 16397961.90 | 11437.10 | 01-MAY-06:01 | 2.35 |
June | 188074.08 | 940.37 | 14-JUN-06:03 | 7.67 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 4546162.03 | 8689.14 | 30-SEP-06:03 | 7.30 |
October | 0.259461E+09 | 13550.24 | 30-OCT-04:01 | -0.5 |
November | 0.111468E+10 | 13821.15 | 24-NOV-05:01 | -3.0 |
December | 0.472944E+10 | 15345.29 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.177901E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.6 | |
Maximum of Months | 0.511248E+10 | 15345.29 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.438597E+10 | 12940.28 | 09-JAN-02:22 | -8.9 |
February | 0.378235E+10 | 13309.23 | 05-FEB-22:32 | -12.8 |
March | 0.139050E+10 | 12492.33 | 06-MAR-04:42 | -11.1 |
April | 0.319355E+09 | 12153.50 | 17-APR-04:01 | -3.4 |
May | 11062782.37 | 9891.43 | 01-MAY-06:01 | 2.35 |
June | 231832.17 | 1159.16 | 14-JUN-06:03 | 7.67 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 4404543.42 | 5610.50 | 30-SEP-06:03 | 7.30 |
October | 0.239126E+09 | 11790.53 | 30-OCT-04:01 | -0.5 |
November | 0.953981E+09 | 11943.91 | 24-NOV-05:01 | -3.0 |
December | 0.389319E+10 | 13301.72 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.149802E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.438597E+10 | 13309.23 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.432413E+10 | 7823.91 | 02-JAN-02:62 | -1.7 |
February | 0.367421E+10 | 7881.89 | 06-FEB-02:13 | -13.9 |
March | 0.163996E+10 | 7680.72 | 06-MAR-05:11 | -11.1 |
April | 0.241840E+09 | 7031.08 | 17-APR-05:01 | -4.0 |
May | 3141432.18 | 6199.86 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 21585518.35 | 6363.99 | 30-OCT-05:01 | -0.1 |
November | 0.248337E+09 | 6773.16 | 24-NOV-06:01 | -3.8 |
December | 0.288272E+10 | 7748.16 | 11-DEC-02:42 | -16.1 |
Annual Sum or Average | 0.130359E+11 | |||
Minimum of Months | 0.00 | 0.00 | -16.1 | |
Maximum of Months | 0.432413E+10 | 7881.89 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250582E+10 | 9066.76 | 09-JAN-05:01 | -9.4 |
February | 0.204822E+10 | 9186.49 | 13-FEB-03:32 | -8.9 |
March | 0.591528E+09 | 8938.26 | 06-MAR-05:11 | -11.1 |
April | 64799444.50 | 8238.84 | 17-APR-05:01 | -4.0 |
May | 427531.57 | 1924.39 | 02-MAY-06:03 | 7.98 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 11124427.40 | 7355.33 | 30-OCT-06:01 | -0.4 |
November | 0.141472E+09 | 8012.23 | 24-NOV-06:01 | -3.8 |
December | 0.178845E+10 | 8966.13 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.715183E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.250582E+10 | 9186.49 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.910714E+10 | 14645.39 | 04-JAN-08:00 | -13.3 |
February | 0.801438E+10 | 15632.86 | 07-FEB-07:10 | -16.5 |
March | 0.469323E+10 | 14582.44 | 07-MAR-07:10 | -12.9 |
April | 0.248881E+10 | 12632.58 | 17-APR-06:10 | -4.2 |
May | 0.105813E+10 | 11005.87 | 01-MAY-06:10 | 2.35 |
June | 0.289994E+09 | 9571.78 | 14-JUN-06:10 | 7.67 |
July | 54079228.58 | 7442.87 | 03-JUL-06:06 | 12.77 |
August | 0.129207E+09 | 8922.67 | 03-AUG-06:05 | 11.57 |
September | 0.415461E+09 | 9457.14 | 06-SEP-06:10 | 6.28 |
October | 0.152347E+10 | 11960.07 | 17-OCT-06:10 | -2.8 |
November | 0.325959E+10 | 12439.13 | 24-NOV-07:10 | -3.2 |
December | 0.778396E+10 | 15581.33 | 11-DEC-07:10 | -16.4 |
Annual Sum or Average | 0.388175E+11 | |||
Minimum of Months | 54079228.58 | 7442.87 | -16.5 | |
Maximum of Months | 0.910714E+10 | 15632.86 | 12.77 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.274843E+10 | 9586.52 | 09-JAN-05:01 | -9.4 |
February | 0.225345E+10 | 9687.47 | 13-FEB-03:32 | -8.9 |
March | 0.667514E+09 | 9418.95 | 06-MAR-05:11 | -11.1 |
April | 96108204.35 | 8503.51 | 17-APR-05:01 | -4.0 |
May | 1488973.80 | 7662.77 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 12048793.86 | 7742.92 | 30-OCT-06:01 | -0.4 |
November | 0.152934E+09 | 8367.42 | 24-NOV-06:01 | -3.8 |
December | 0.183692E+10 | 9443.70 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.776889E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.274843E+10 | 9687.47 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.413275E+10 | 8819.50 | 02-JAN-02:62 | -1.7 |
February | 0.348340E+10 | 9061.57 | 21-FEB-04:02 | -11.2 |
March | 0.115710E+10 | 8647.12 | 06-MAR-04:42 | -11.1 |
April | 0.136450E+09 | 7981.93 | 17-APR-04:01 | -3.4 |
May | 155964.14 | 2339.46 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 70472880.28 | 7622.37 | 30-OCT-05:01 | -0.1 |
November | 0.459455E+09 | 8010.19 | 24-NOV-05:01 | -3.0 |
December | 0.338248E+10 | 9017.33 | 26-DEC-02:42 | -11.7 |
Annual Sum or Average | 0.128223E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.7 | |
Maximum of Months | 0.413275E+10 | 9061.57 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244415E+10 | 10904.53 | 24-JAN-05:11 | -11.9 |
February | 0.204608E+10 | 11245.61 | 21-FEB-04:02 | -11.2 |
March | 0.498501E+09 | 10514.27 | 06-MAR-05:01 | -11.1 |
April | 55084757.77 | 9617.06 | 17-APR-04:01 | -3.4 |
May | 80619.48 | 537.46 | 02-MAY-06:03 | 7.98 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 288978.00 | 1926.52 | 30-SEP-06:03 | 7.30 |
October | 43892088.91 | 9523.95 | 30-OCT-05:01 | -0.1 |
November | 0.283310E+09 | 10019.00 | 24-NOV-05:01 | -3.0 |
December | 0.216245E+10 | 11107.01 | 26-DEC-02:42 | -11.7 |
Annual Sum or Average | 0.753383E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.9 | |
Maximum of Months | 0.244415E+10 | 11245.61 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.284066E+10 | 12845.82 | 24-JAN-05:11 | -11.9 |
February | 0.246169E+10 | 13300.90 | 21-FEB-03:22 | -11.1 |
March | 0.560414E+09 | 12454.88 | 06-MAR-05:01 | -11.1 |
April | 0.106466E+09 | 11362.86 | 17-APR-05:01 | -4.0 |
May | 580513.27 | 8707.70 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 47390096.28 | 11107.96 | 30-OCT-05:01 | -0.1 |
November | 0.323030E+09 | 11733.21 | 24-NOV-05:01 | -3.0 |
December | 0.239672E+10 | 13168.67 | 26-DEC-02:42 | -11.7 |
Annual Sum or Average | 0.873696E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.9 | |
Maximum of Months | 0.284066E+10 | 13300.90 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.260973E+10 | 11019.56 | 24-JAN-05:11 | -11.9 |
February | 0.216737E+10 | 11386.23 | 21-FEB-04:02 | -11.2 |
March | 0.578347E+09 | 10617.87 | 06-MAR-05:01 | -11.1 |
April | 81320157.40 | 9643.58 | 17-APR-05:01 | -4.0 |
May | 572521.33 | 6294.77 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 182018.05 | 1213.45 | 30-SEP-06:03 | 7.30 |
October | 47575515.86 | 9479.81 | 30-OCT-05:01 | -0.1 |
November | 0.301829E+09 | 9713.73 | 25-NOV-06:01 | -1.7 |
December | 0.214719E+10 | 11251.37 | 26-DEC-02:42 | -11.7 |
Annual Sum or Average | 0.793412E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.9 | |
Maximum of Months | 0.260973E+10 | 11386.23 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.208150E+11 | 18520.31 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.188385E+11 | 18520.31 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.216654E+11 | 18520.31 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.200796E+11 | 18520.31 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.212402E+11 | 18520.31 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.208620E+11 | 18520.31 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.204550E+11 | 18520.31 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.216654E+11 | 18520.31 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.200739E+11 | 18520.31 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.208179E+11 | 18520.31 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.203773E+11 | 18520.31 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.204522E+11 | 18520.31 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.247342E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.188385E+11 | 18520.31 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.216654E+11 | 18520.31 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.825427E+09 | 1168.55 | 02-JAN-16:49 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.719739E+09 | 1061.10 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.822082E+09 | 924.30 | 17-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.718825E+09 | 830.84 | 12-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.762645E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.752434E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.707826E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.794019E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.728806E+09 | 899.64 | 26-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.782975E+09 | 1141.31 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.821312E+09 | 1168.55 | 06-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.816882E+09 | 1168.55 | 01-DEC-16:40 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.925297E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.707826E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.825427E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.517487E+09 | 739.79 | 02-JAN-16:49 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.454454E+09 | 675.86 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.519556E+09 | 537.62 | 17-MAR-07:10 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.455496E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.484364E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.477950E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.449468E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.504129E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.460994E+09 | 520.13 | 26-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.492766E+09 | 681.54 | 31-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.516177E+09 | 739.79 | 06-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.511314E+09 | 739.79 | 01-DEC-16:40 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.584416E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.449468E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.519556E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.808127E+09 | 1168.55 | 02-JAN-16:49 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.713406E+09 | 1044.63 | 01-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.818361E+09 | 906.24 | 17-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.719791E+09 | 825.79 | 12-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.765406E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.755441E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.710575E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.796006E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.728099E+09 | 885.93 | 26-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.775007E+09 | 1052.02 | 30-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.807452E+09 | 1168.55 | 06-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.800348E+09 | 1168.55 | 01-DEC-16:40 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.919802E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.710575E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.818361E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.516713E+09 | 739.74 | 02-JAN-16:49 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.453235E+09 | 669.17 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.519288E+09 | 605.73 | 17-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.455421E+09 | 550.76 | 12-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.483255E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.476858E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.448722E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.502957E+09 | 456.05 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.461562E+09 | 590.33 | 26-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.494736E+09 | 722.60 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.515195E+09 | 739.74 | 06-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.511552E+09 | 739.74 | 01-DEC-16:40 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.583949E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.448722E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.519288E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.823017E+09 | 1168.55 | 02-JAN-16:49 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.718684E+09 | 1056.34 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.820989E+09 | 913.24 | 17-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.718511E+09 | 815.85 | 12-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.762167E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.752177E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.707568E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.793598E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.728094E+09 | 887.63 | 26-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.781568E+09 | 1139.59 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.819433E+09 | 1168.55 | 06-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.814571E+09 | 1168.55 | 01-DEC-16:40 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.924038E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.707568E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.823017E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.516671E+09 | 739.79 | 02-JAN-16:49 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.453926E+09 | 673.68 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.519173E+09 | 529.71 | 17-MAR-07:10 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.455297E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.484061E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.477717E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.449253E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.503842E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.460691E+09 | 511.59 | 26-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.492194E+09 | 676.10 | 31-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.515342E+09 | 739.79 | 06-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.510580E+09 | 739.79 | 01-DEC-16:40 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.583875E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.449253E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.519173E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.806902E+09 | 1168.55 | 02-JAN-16:49 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.712707E+09 | 1038.90 | 01-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.817853E+09 | 894.16 | 17-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.719325E+09 | 810.54 | 12-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.764825E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.755005E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.710099E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.795469E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.727440E+09 | 873.17 | 26-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.774357E+09 | 1045.40 | 30-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.806304E+09 | 1168.55 | 06-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.799002E+09 | 1168.55 | 01-DEC-16:40 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.918929E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.710099E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.817853E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.515734E+09 | 739.74 | 02-JAN-16:49 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.452748E+09 | 666.78 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.518843E+09 | 601.18 | 17-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.455086E+09 | 544.41 | 12-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.482984E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.476676E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.448538E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.502644E+09 | 456.05 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.461137E+09 | 585.29 | 26-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.494104E+09 | 721.70 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.514410E+09 | 739.74 | 06-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.510558E+09 | 739.74 | 01-DEC-16:40 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.583346E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.448538E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.518843E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.825426E+09 | 1168.55 | 02-JAN-16:49 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.719738E+09 | 1061.10 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.822081E+09 | 924.28 | 17-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.718825E+09 | 830.82 | 12-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.762645E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.752434E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.707826E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.794019E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.728806E+09 | 899.63 | 26-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.782974E+09 | 1141.31 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.821310E+09 | 1168.55 | 06-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.816880E+09 | 1168.55 | 01-DEC-16:40 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.925296E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.707826E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.825426E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.517486E+09 | 739.79 | 02-JAN-16:49 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.454454E+09 | 675.86 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.519556E+09 | 537.61 | 17-MAR-07:10 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.455495E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.484363E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.477950E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.449468E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.504129E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.460994E+09 | 520.12 | 26-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.492766E+09 | 681.54 | 31-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.516176E+09 | 739.79 | 06-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.511313E+09 | 739.79 | 01-DEC-16:40 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.584415E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.449468E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.519556E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.808126E+09 | 1168.55 | 02-JAN-16:49 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.713406E+09 | 1044.62 | 01-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.818361E+09 | 906.23 | 17-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.719790E+09 | 825.77 | 12-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.765406E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.755441E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.710575E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.796006E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.728099E+09 | 885.92 | 26-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.775007E+09 | 1052.03 | 30-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.807411E+09 | 1168.55 | 06-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.800347E+09 | 1168.55 | 01-DEC-16:40 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.919797E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.710575E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.818361E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.516712E+09 | 739.74 | 02-JAN-16:49 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.453235E+09 | 669.16 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.519288E+09 | 605.72 | 17-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.455421E+09 | 550.75 | 12-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.483255E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.476858E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.448722E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.502957E+09 | 456.05 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.461561E+09 | 590.32 | 26-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.494735E+09 | 722.60 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.515194E+09 | 739.74 | 06-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.511551E+09 | 739.74 | 01-DEC-16:40 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.583949E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.448722E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.519288E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.208150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.200796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.212402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.208620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.204550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.200739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.208179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.203773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.204522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.247342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.825427E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187831E+10 |
February | 0.901968E+09 | 0.719739E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200002E+10 |
March | 0.107774E+10 | 0.822082E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 472971.31 | 0.121713E+10 |
April | 0.956342E+09 | 0.718825E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.980966E+09 |
May | 0.103597E+10 | 0.762645E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 500504.95 | 0.607565E+09 |
June | 0.103308E+10 | 0.752434E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11328012.65 | 0.360486E+09 |
July | 0.959235E+09 | 0.707826E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26795305.97 | 0.215167E+09 |
August | 0.107774E+10 | 0.794019E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21963009.27 | 0.246127E+09 |
September | 0.956342E+09 | 0.728806E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1548472.03 | 0.354800E+09 |
October | 0.994195E+09 | 0.782975E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743646E+09 |
November | 0.984487E+09 | 0.821312E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998530E+09 |
December | 0.959235E+09 | 0.816882E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197901E+10 |
Annual Sum or Average | 0.119305E+11 | 0.925297E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62608276.19 | 0.115818E+11 |
Minimum of Months | 0.901968E+09 | 0.707826E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215167E+09 |
Maximum of Months | 0.107774E+10 | 0.825427E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26795305.97 | 0.200002E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.517487E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125391E+10 |
February | 0.571020E+09 | 0.454454E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133612E+10 |
March | 0.682301E+09 | 0.519556E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 293773.63 | 0.817522E+09 |
April | 0.605444E+09 | 0.455496E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666434E+09 |
May | 0.655854E+09 | 0.484364E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 352750.42 | 0.418161E+09 |
June | 0.654023E+09 | 0.477950E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7396952.43 | 0.244686E+09 |
July | 0.607275E+09 | 0.449468E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17577256.50 | 0.145861E+09 |
August | 0.682301E+09 | 0.504129E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14203507.50 | 0.166947E+09 |
September | 0.605444E+09 | 0.460994E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1077703.46 | 0.241708E+09 |
October | 0.629407E+09 | 0.492766E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507710E+09 |
November | 0.623262E+09 | 0.516177E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669671E+09 |
December | 0.607275E+09 | 0.511314E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132090E+10 |
Annual Sum or Average | 0.755301E+10 | 0.584416E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40901943.94 | 0.778963E+10 |
Minimum of Months | 0.571020E+09 | 0.449468E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145861E+09 |
Maximum of Months | 0.682301E+09 | 0.519556E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17577256.50 | 0.133612E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.808127E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190907E+10 |
February | 0.901968E+09 | 0.713406E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202162E+10 |
March | 0.107774E+10 | 0.818361E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 437535.27 | 0.127488E+10 |
April | 0.956342E+09 | 0.719791E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101890E+10 |
May | 0.103597E+10 | 0.765406E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 201888.56 | 0.627018E+09 |
June | 0.103308E+10 | 0.755441E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10799234.97 | 0.362749E+09 |
July | 0.959235E+09 | 0.710575E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26085168.17 | 0.219555E+09 |
August | 0.107774E+10 | 0.796006E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20052096.52 | 0.255813E+09 |
September | 0.956342E+09 | 0.728099E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1409627.02 | 0.378053E+09 |
October | 0.994195E+09 | 0.775007E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.799915E+09 |
November | 0.984487E+09 | 0.807452E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103781E+10 |
December | 0.959235E+09 | 0.800348E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201132E+10 |
Annual Sum or Average | 0.119305E+11 | 0.919802E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58985550.52 | 0.119167E+11 |
Minimum of Months | 0.901968E+09 | 0.710575E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219555E+09 |
Maximum of Months | 0.107774E+10 | 0.818361E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26085168.17 | 0.202162E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.516713E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125425E+10 |
February | 0.570983E+09 | 0.453235E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133790E+10 |
March | 0.682256E+09 | 0.519288E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 392044.38 | 0.830090E+09 |
April | 0.605404E+09 | 0.455421E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673674E+09 |
May | 0.655811E+09 | 0.483255E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 134607.27 | 0.421139E+09 |
June | 0.653980E+09 | 0.476858E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7768981.56 | 0.249470E+09 |
July | 0.607235E+09 | 0.448722E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18062007.30 | 0.150761E+09 |
August | 0.682256E+09 | 0.502957E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14826289.81 | 0.172378E+09 |
September | 0.605404E+09 | 0.461562E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 937966.96 | 0.242807E+09 |
October | 0.629366E+09 | 0.494736E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502580E+09 |
November | 0.623221E+09 | 0.515195E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666592E+09 |
December | 0.607235E+09 | 0.511552E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132028E+10 |
Annual Sum or Average | 0.755252E+10 | 0.583949E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42121897.29 | 0.782192E+10 |
Minimum of Months | 0.570983E+09 | 0.448722E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150761E+09 |
Maximum of Months | 0.682256E+09 | 0.519288E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18062007.30 | 0.133790E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.823017E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104060E+10 |
February | 0.901968E+09 | 0.718684E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110086E+10 |
March | 0.107774E+10 | 0.820989E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 540245.06 | 0.673309E+09 |
April | 0.956342E+09 | 0.718511E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534709E+09 |
May | 0.103597E+10 | 0.762167E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 496215.39 | 0.311787E+09 |
June | 0.103308E+10 | 0.752177E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8471796.11 | 0.185728E+09 |
July | 0.959235E+09 | 0.707568E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16659004.19 | 0.107580E+09 |
August | 0.107774E+10 | 0.793598E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14089217.09 | 0.130850E+09 |
September | 0.956342E+09 | 0.728094E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 922021.94 | 0.200983E+09 |
October | 0.994195E+09 | 0.781568E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448773E+09 |
November | 0.984487E+09 | 0.819433E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595412E+09 |
December | 0.959235E+09 | 0.814571E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112226E+10 |
Annual Sum or Average | 0.119305E+11 | 0.924038E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41178499.79 | 0.645285E+10 |
Minimum of Months | 0.901968E+09 | 0.707568E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107580E+09 |
Maximum of Months | 0.107774E+10 | 0.823017E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16659004.19 | 0.112226E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.516671E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696281E+09 |
February | 0.571020E+09 | 0.453926E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735921E+09 |
March | 0.682301E+09 | 0.519173E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 229542.66 | 0.455803E+09 |
April | 0.605444E+09 | 0.455297E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372067E+09 |
May | 0.655854E+09 | 0.484061E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 171152.99 | 0.225225E+09 |
June | 0.654023E+09 | 0.477717E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4283474.02 | 0.131824E+09 |
July | 0.607275E+09 | 0.449253E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9929103.81 | 77771051.66 |
August | 0.682301E+09 | 0.503842E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8061143.86 | 93024364.21 |
September | 0.605444E+09 | 0.460691E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 595746.91 | 0.140543E+09 |
October | 0.629407E+09 | 0.492194E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310508E+09 |
November | 0.623262E+09 | 0.515342E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401356E+09 |
December | 0.607275E+09 | 0.510580E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748774E+09 |
Annual Sum or Average | 0.755301E+10 | 0.583875E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23270164.25 | 0.438910E+10 |
Minimum of Months | 0.571020E+09 | 0.449253E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77771051.66 |
Maximum of Months | 0.682301E+09 | 0.519173E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9929103.81 | 0.748774E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.806902E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100385E+11 |
February | 0.901968E+09 | 0.712707E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925679E+10 |
March | 0.107774E+10 | 0.817853E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12328123.19 | 0.779220E+10 |
April | 0.956342E+09 | 0.719325E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532861E+10 |
May | 0.103597E+10 | 0.764825E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3895402.04 | 0.344075E+10 |
June | 0.103308E+10 | 0.755005E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197953E+09 | 0.182604E+10 |
July | 0.959235E+09 | 0.710099E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551252E+09 | 0.745426E+09 |
August | 0.107774E+10 | 0.795469E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423265E+09 | 0.130678E+10 |
September | 0.956342E+09 | 0.727440E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21358341.22 | 0.228078E+10 |
October | 0.994195E+09 | 0.774357E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492352E+10 |
November | 0.984487E+09 | 0.806304E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633028E+10 |
December | 0.959235E+09 | 0.799002E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925122E+10 |
Annual Sum or Average | 0.119305E+11 | 0.918929E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121005E+10 | 0.625209E+11 |
Minimum of Months | 0.901968E+09 | 0.710099E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745426E+09 |
Maximum of Months | 0.107774E+10 | 0.817853E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551252E+09 | 0.100385E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.515734E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694194E+09 |
February | 0.570983E+09 | 0.452748E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736326E+09 |
March | 0.682256E+09 | 0.518843E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 328123.34 | 0.461858E+09 |
April | 0.605404E+09 | 0.455086E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372690E+09 |
May | 0.655811E+09 | 0.482984E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78681.75 | 0.228178E+09 |
June | 0.653980E+09 | 0.476676E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4243511.34 | 0.136554E+09 |
July | 0.607235E+09 | 0.448538E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10156693.06 | 82148123.03 |
August | 0.682256E+09 | 0.502644E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8039118.46 | 96963891.47 |
September | 0.605404E+09 | 0.461137E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 507825.99 | 0.141894E+09 |
October | 0.629366E+09 | 0.494104E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306094E+09 |
November | 0.623221E+09 | 0.514410E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399134E+09 |
December | 0.607235E+09 | 0.510558E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748097E+09 |
Annual Sum or Average | 0.755252E+10 | 0.583346E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23353953.94 | 0.440413E+10 |
Minimum of Months | 0.570983E+09 | 0.448538E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82148123.03 |
Maximum of Months | 0.682256E+09 | 0.518843E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10156693.06 | 0.748097E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.825426E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160723E+10 |
February | 0.901968E+09 | 0.719738E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170623E+10 |
March | 0.107774E+10 | 0.822081E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 406681.60 | 0.106657E+10 |
April | 0.956342E+09 | 0.718825E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.869279E+09 |
May | 0.103597E+10 | 0.762645E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 611740.55 | 0.531851E+09 |
June | 0.103308E+10 | 0.752434E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10281313.19 | 0.309875E+09 |
July | 0.959235E+09 | 0.707826E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23161245.16 | 0.183151E+09 |
August | 0.107774E+10 | 0.794019E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19117697.55 | 0.213142E+09 |
September | 0.956342E+09 | 0.728806E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1344774.40 | 0.315920E+09 |
October | 0.994195E+09 | 0.782974E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679322E+09 |
November | 0.984487E+09 | 0.821310E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901379E+09 |
December | 0.959235E+09 | 0.816880E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171130E+10 |
Annual Sum or Average | 0.119305E+11 | 0.925296E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54923452.45 | 0.100952E+11 |
Minimum of Months | 0.901968E+09 | 0.707826E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183151E+09 |
Maximum of Months | 0.107774E+10 | 0.825426E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23161245.16 | 0.171130E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.517486E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107314E+10 |
February | 0.421807E+09 | 0.454454E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113886E+10 |
March | 0.502994E+09 | 0.519556E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 257089.98 | 0.716974E+09 |
April | 0.447140E+09 | 0.455495E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587716E+09 |
May | 0.484071E+09 | 0.484363E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 414510.42 | 0.363751E+09 |
June | 0.482240E+09 | 0.477950E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6542601.60 | 0.209427E+09 |
July | 0.448971E+09 | 0.449468E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15111428.12 | 0.123790E+09 |
August | 0.502994E+09 | 0.504129E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12433514.40 | 0.144161E+09 |
September | 0.447140E+09 | 0.460994E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 938128.28 | 0.213432E+09 |
October | 0.465148E+09 | 0.492766E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460494E+09 |
November | 0.460569E+09 | 0.516176E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602480E+09 |
December | 0.448971E+09 | 0.511313E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114074E+10 |
Annual Sum or Average | 0.557719E+10 | 0.584415E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35697272.79 | 0.677496E+10 |
Minimum of Months | 0.421807E+09 | 0.449468E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123790E+09 |
Maximum of Months | 0.502994E+09 | 0.519556E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15111428.12 | 0.114074E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.808126E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164439E+10 |
February | 0.901968E+09 | 0.713406E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173215E+10 |
March | 0.107774E+10 | 0.818361E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 374473.70 | 0.112068E+10 |
April | 0.956342E+09 | 0.719790E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900766E+09 |
May | 0.103597E+10 | 0.765406E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 171673.86 | 0.548461E+09 |
June | 0.103308E+10 | 0.755441E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9254903.59 | 0.313260E+09 |
July | 0.959235E+09 | 0.710575E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22182505.52 | 0.188417E+09 |
August | 0.107774E+10 | 0.796006E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16982273.59 | 0.221990E+09 |
September | 0.956342E+09 | 0.728099E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1200204.15 | 0.334141E+09 |
October | 0.994195E+09 | 0.775007E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.724841E+09 |
November | 0.984487E+09 | 0.807411E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935862E+09 |
December | 0.959235E+09 | 0.800347E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174808E+10 |
Annual Sum or Average | 0.119305E+11 | 0.919797E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50166034.40 | 0.104130E+11 |
Minimum of Months | 0.901968E+09 | 0.710575E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188417E+09 |
Maximum of Months | 0.107774E+10 | 0.818361E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22182505.52 | 0.174808E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.516712E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107185E+10 |
February | 0.570983E+09 | 0.453235E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113967E+10 |
March | 0.682256E+09 | 0.519288E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 317581.61 | 0.727867E+09 |
April | 0.605404E+09 | 0.455421E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594752E+09 |
May | 0.655811E+09 | 0.483255E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114462.33 | 0.368556E+09 |
June | 0.653980E+09 | 0.476858E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6653524.19 | 0.215482E+09 |
July | 0.607235E+09 | 0.448722E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15417027.03 | 0.129761E+09 |
August | 0.682256E+09 | 0.502957E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12452949.16 | 0.149784E+09 |
September | 0.605404E+09 | 0.461561E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 777321.91 | 0.216075E+09 |
October | 0.629366E+09 | 0.494735E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457133E+09 |
November | 0.623221E+09 | 0.515194E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600332E+09 |
December | 0.607235E+09 | 0.511551E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114022E+10 |
Annual Sum or Average | 0.755252E+10 | 0.583949E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35732866.23 | 0.681148E+10 |
Minimum of Months | 0.570983E+09 | 0.448722E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129761E+09 |
Maximum of Months | 0.682256E+09 | 0.519288E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15417027.03 | 0.114022E+10 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220651E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233021E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598317.29 | 0.148901E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121404E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549579.85 | 0.721358E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9892893.03 | 0.417767E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24406998.26 | 0.243460E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20477932.77 | 0.290261E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1046865.62 | 0.443398E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976081E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129345E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238118E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56972586.82 | 0.140067E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243460E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24406998.26 | 0.238118E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272234E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287485E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 888143.37 | 0.183752E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150396E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 935024.18 | 0.910977E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13078420.76 | 0.533898E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31038725.34 | 0.311925E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26767452.82 | 0.368311E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1430213.10 | 0.550047E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116841E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154142E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290540E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74137979.56 | 0.172290E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311925E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31038725.34 | 0.290540E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277997E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295944E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34762.50 | 0.186616E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153360E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26633.09 | 0.969116E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7506992.79 | 0.576104E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22882247.25 | 0.344241E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16407976.23 | 0.388343E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 695586.24 | 0.565475E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115648E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151151E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293975E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47554198.10 | 0.175902E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344241E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22882247.25 | 0.295944E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 18520.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 18520.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 18520.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 18520.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 18520.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 18520.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 18520.31 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 18520.31 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 18520.31 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 18520.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 18520.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 18520.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:49 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3589.26 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1061.10 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3630.05 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 924.30 | 17-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.47 | 15-MAR-14:00 | 2008.07 | 01-MAR-22:02 |
April | 1306.65 | 03-APR-09:09 | 830.84 | 12-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1817.97 | 04-APR-21:03 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.94 | 14-MAY-14:53 | 1152.33 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.26 | 17-JUN-17:03 | 1040.95 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.94 | 15-JUL-15:00 | 750.17 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.41 | 13-AUG-13:00 | 484.60 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 899.64 | 26-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.43 | 16-SEP-17:03 | 815.71 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1141.31 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 970.32 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1768.50 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:40 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3356.62 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.60 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 367.41 | 3630.05 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 739.79 | 02-JAN-16:49 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2392.91 | 12-JAN-06:00 |
February | 827.22 | 01-FEB-10:09 | 675.86 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2503.12 | 13-FEB-06:00 |
March | 827.22 | 01-MAR-10:09 | 537.62 | 17-MAR-07:10 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 15-MAR-14:00 | 1339.26 | 01-MAR-22:02 |
April | 827.22 | 03-APR-09:09 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1210.89 | 04-APR-21:03 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.99 | 14-MAY-14:53 | 840.72 | 29-MAY-14:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.34 | 17-JUN-17:03 | 695.86 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.63 | 15-JUL-15:00 | 497.19 | 06-JUL-02:00 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.69 | 13-AUG-12:50 | 314.76 | 30-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 520.13 | 26-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.67 | 16-SEP-17:03 | 536.36 | 29-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 681.54 | 31-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 675.87 | 08-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 06-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1168.83 | 17-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-16:40 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2225.02 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.76 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 256.69 | 2503.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:49 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3589.39 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1044.63 | 01-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3754.71 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 906.24 | 17-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.47 | 15-MAR-14:00 | 2089.18 | 26-MAR-13:00 |
April | 1306.65 | 03-APR-09:09 | 825.79 | 12-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1817.65 | 04-APR-21:03 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 10-MAY-14:00 | 1254.27 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.18 | 17-JUN-17:03 | 1048.75 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.94 | 15-JUL-15:00 | 753.02 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 353.76 | 13-AUG-12:48 | 495.09 | 20-AUG-15:00 |
September | 1306.65 | 01-SEP-09:09 | 885.93 | 26-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.38 | 16-SEP-13:00 | 818.72 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1052.02 | 30-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1018.49 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1791.46 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:40 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3376.70 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.09 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 353.76 | 3754.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-16:49 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2392.91 | 12-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 669.17 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2503.12 | 13-FEB-06:00 |
March | 827.17 | 01-MAR-10:09 | 605.73 | 17-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 15-MAR-14:00 | 1438.84 | 25-MAR-17:10 |
April | 827.17 | 03-APR-09:09 | 550.76 | 12-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1210.36 | 04-APR-21:03 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.58 | 10-MAY-14:00 | 894.35 | 06-MAY-17:10 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.15 | 12-JUN-13:00 | 699.33 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.92 | 16-JUL-10:20 | 505.88 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 456.05 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.09 | 13-AUG-13:00 | 377.19 | 27-AUG-16:40 |
September | 827.17 | 01-SEP-09:09 | 590.33 | 26-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 | 16-SEP-13:00 | 534.04 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 722.60 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 646.82 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 06-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1165.00 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:40 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2226.89 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.19 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 266.09 | 2503.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:49 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1904.55 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1056.34 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1992.56 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 913.24 | 17-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.05 | 14-MAR-14:00 | 1107.72 | 02-MAR-01:00 |
April | 1306.65 | 03-APR-09:09 | 815.85 | 12-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1066.69 | 16-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.04 | 14-MAY-15:00 | 561.48 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.70 | 17-JUN-17:03 | 571.35 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.48 | 21-JUL-03:00 | 418.53 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.10 | 13-AUG-13:00 | 270.80 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 887.63 | 26-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.40 | 16-SEP-17:03 | 508.34 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1139.59 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 637.34 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1084.83 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:40 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1878.72 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.80 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 239.10 | 1992.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 739.79 | 02-JAN-16:49 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1269.73 | 12-JAN-05:55 |
February | 827.22 | 01-FEB-10:09 | 673.68 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1328.37 | 13-FEB-05:53 |
March | 827.22 | 01-MAR-10:09 | 529.71 | 17-MAR-07:10 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 | 15-MAR-14:00 | 756.85 | 02-MAR-01:00 |
April | 827.22 | 03-APR-09:09 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 712.63 | 16-APR-06:55 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.19 | 14-MAY-15:00 | 421.35 | 29-MAY-14:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.60 | 17-JUN-17:03 | 395.68 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.22 | 21-JUL-03:00 | 286.75 | 06-JUL-02:00 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.66 | 13-AUG-13:00 | 179.54 | 30-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 511.59 | 26-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.02 | 16-SEP-17:03 | 336.70 | 29-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 676.10 | 31-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 439.90 | 08-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 06-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 726.72 | 17-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-16:40 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1247.83 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.54 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 139.66 | 1328.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:49 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 43434.41 | 31-JAN-17:01 |
February | 1306.65 | 01-FEB-10:09 | 1038.90 | 01-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 46180.89 | 07-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 894.16 | 17-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1225.32 | 15-MAR-12:00 | 43849.17 | 07-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 810.54 | 12-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 31519.79 | 17-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 384.52 | 10-MAY-16:10 | 22429.85 | 01-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6431.89 | 27-JUN-12:00 | 16421.18 | 06-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6657.72 | 19-JUL-16:10 | 11353.25 | 03-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6161.38 | 18-AUG-16:10 | 12759.06 | 01-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 873.17 | 26-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2569.40 | 15-SEP-12:00 | 19179.59 | 05-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 1045.40 | 30-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 29842.63 | 17-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 29999.31 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:40 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 46727.03 | 11-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11353.25 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 6657.72 | 46727.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-16:49 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1269.73 | 12-JAN-05:55 |
February | 827.17 | 01-FEB-10:09 | 666.78 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1328.37 | 13-FEB-05:53 |
March | 827.17 | 01-MAR-10:09 | 601.18 | 17-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 15-MAR-12:00 | 766.18 | 02-MAR-01:00 |
April | 827.17 | 03-APR-09:09 | 544.41 | 12-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 706.55 | 16-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | 14-MAY-15:10 | 432.94 | 06-MAY-17:10 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.25 | 17-JUN-17:03 | 399.67 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.30 | 16-JUL-11:30 | 292.92 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 456.05 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.42 | 13-AUG-13:00 | 179.18 | 30-AUG-21:10 |
September | 827.17 | 01-SEP-09:09 | 585.29 | 26-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.11 | 16-SEP-13:00 | 335.58 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 721.70 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 428.02 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 06-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 726.48 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:40 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1248.22 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.18 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 142.42 | 1328.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:49 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2984.81 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1061.10 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3074.64 | 13-FEB-05:50 |
March | 1306.65 | 01-MAR-10:09 | 924.28 | 17-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 | 15-MAR-14:00 | 1739.58 | 02-MAR-01:00 |
April | 1306.65 | 03-APR-09:09 | 830.82 | 12-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1628.90 | 16-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.46 | 14-MAY-14:53 | 978.27 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.46 | 17-JUN-17:03 | 906.06 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.69 | 15-JUL-15:00 | 660.75 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.59 | 13-AUG-13:00 | 420.56 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 899.63 | 26-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.86 | 16-SEP-17:03 | 759.11 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1141.31 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 932.31 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1623.35 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:40 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2892.08 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.56 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 327.59 | 3074.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 739.79 | 02-JAN-16:49 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1989.87 | 12-JAN-06:00 |
February | 805.43 | 01-FEB-08:09 | 675.86 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2049.78 | 13-FEB-05:45 |
March | 805.43 | 01-MAR-08:09 | 537.61 | 17-MAR-07:10 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 | 15-MAR-14:00 | 1166.23 | 02-MAR-01:00 |
April | 805.43 | 03-APR-07:10 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1087.70 | 16-APR-06:55 |
May | 805.43 | 01-MAY-07:10 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.02 | 14-MAY-14:53 | 711.84 | 29-MAY-14:00 |
June | 805.43 | 01-JUN-07:10 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.49 | 17-JUN-17:03 | 605.54 | 13-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.79 | 15-JUL-15:00 | 438.18 | 06-JUL-02:00 |
August | 805.43 | 01-AUG-07:10 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.65 | 13-AUG-12:43 | 272.74 | 30-AUG-21:10 |
September | 805.43 | 01-SEP-07:10 | 520.12 | 26-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.61 | 16-SEP-17:03 | 498.86 | 29-SEP-04:00 |
October | 805.43 | 02-OCT-07:10 | 681.54 | 31-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 645.18 | 08-OCT-09:00 |
November | 805.43 | 01-NOV-07:10 | 739.79 | 06-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1071.19 | 17-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 739.79 | 01-DEC-16:40 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1915.29 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.74 | |||||
Maximum of Months | 805.43 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 214.65 | 2049.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-16:49 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2984.82 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1044.62 | 01-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3074.68 | 13-FEB-05:50 |
March | 1306.65 | 01-MAR-10:09 | 906.23 | 17-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 | 15-MAR-14:00 | 1862.03 | 26-MAR-13:00 |
April | 1306.65 | 03-APR-09:09 | 825.77 | 12-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1633.15 | 16-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 | 10-MAY-14:00 | 1064.21 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.19 | 17-JUN-17:03 | 912.50 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.69 | 15-JUL-15:00 | 663.47 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.32 | 13-AUG-13:14 | 420.24 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 885.92 | 26-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.51 | 16-SEP-13:00 | 761.29 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1052.03 | 30-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 972.39 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 06-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1644.31 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:40 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2911.16 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.24 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 279.32 | 3074.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-16:49 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1989.87 | 12-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 669.16 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2049.78 | 13-FEB-05:45 |
March | 827.17 | 01-MAR-10:09 | 605.72 | 17-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 | 15-MAR-14:00 | 1227.29 | 25-MAR-17:10 |
April | 827.17 | 03-APR-09:09 | 550.75 | 12-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1075.78 | 16-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.13 | 10-MAY-14:00 | 750.81 | 06-MAY-17:10 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.08 | 12-JUN-13:00 | 608.90 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.76 | 16-JUL-10:20 | 445.70 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 456.05 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.80 | 13-AUG-12:55 | 301.00 | 27-AUG-16:30 |
September | 827.17 | 01-SEP-09:09 | 590.32 | 26-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.34 | 16-SEP-13:00 | 497.64 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 722.60 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 620.77 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 06-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1069.53 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:40 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1917.76 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.00 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 235.80 | 2049.78 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3984.46 | 12-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3900.64 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.60 | 15-MAR-14:00 | 2559.65 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2398.24 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.99 | 14-MAY-14:53 | 1203.02 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.60 | 17-JUN-17:03 | 1240.62 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.84 | 21-JUL-03:00 | 904.74 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.14 | 13-AUG-13:00 | 575.43 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.70 | 16-SEP-13:00 | 1093.01 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1355.04 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2384.38 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4029.50 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.43 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.14 | 4029.50 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4935.94 | 12-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4723.68 | 13-FEB-05:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.13 | 14-MAR-14:00 | 3178.80 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2917.56 | 16-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.39 | 14-MAY-15:00 | 1495.02 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.55 | 17-JUN-17:03 | 1589.66 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.98 | 21-JUL-03:00 | 1147.92 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.42 | 13-AUG-13:00 | 733.87 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.84 | 16-SEP-17:03 | 1334.43 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1603.19 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2895.37 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5021.32 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 733.87 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.42 | 5021.32 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4930.39 | 12-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4993.57 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 | 15-MAR-14:00 | 2972.49 | 25-MAR-17:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2748.95 | 16-APR-06:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.77 | 10-MAY-15:00 | 1984.27 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.97 | 17-JUN-17:03 | 1586.62 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.03 | 21-JUL-02:00 | 1122.64 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.59 | 13-AUG-13:00 | 747.31 | 30-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.97 | 16-SEP-13:00 | 1236.29 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1466.33 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2694.21 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5380.74 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 747.31 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.59 | 5380.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9086.56 | 20-JAN-17:00 | 6035.01 | 5543.17 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9416.44 | 17-FEB-17:00 | 6035.01 | 5543.17 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21716.30 | 17-MAR-05:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19049.74 | 25-APR-05:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40456.24 | 22-MAY-05:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 43023.77 | 19-JUN-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 44252.39 | 24-JUL-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 44051.50 | 21-AUG-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44722.59 | 18-SEP-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39953.05 | 13-OCT-05:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18885.00 | 02-NOV-07:02 | 60350.08 | 55431.73 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12152.46 | 01-DEC-09:00 | 6035.01 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 9086.56 | 0.00 | 2463.50 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44722.59 | 60350.08 | 55431.73 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 968.25 |
February | 177.11 | 22-FEB-17:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.38 |
March | 5347.68 | 15-MAR-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.63 | 0.00 |
April | 4315.42 | 21-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.60 |
May | 7000.58 | 26-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.27 |
June | 10484.69 | 27-JUN-14:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 |
July | 10350.40 | 21-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.91 | 0.00 |
August | 10258.92 | 09-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.53 | 0.00 |
September | 8047.88 | 21-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 | 0.00 |
October | 4164.06 | 11-OCT-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.67 |
November | 947.60 | 04-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.65 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1130.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10484.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.91 | 1130.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1994.31 | 04-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1064.02 |
February | 1858.43 | 09-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1469.20 |
March | 1778.36 | 18-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.97 |
April | 1940.13 | 11-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.41 |
May | 2211.65 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.98 |
June | 4417.24 | 12-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.65 | 0.00 |
July | 5179.41 | 17-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.71 | 0.00 |
August | 4729.54 | 07-AUG-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.38 |
September | 3285.11 | 18-SEP-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.44 |
October | 2312.93 | 24-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.14 |
November | 1407.15 | 02-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.14 |
December | 1756.91 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1407.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5179.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.65 | 1854.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1782.20 | 06-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.25 |
February | 1947.01 | 10-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.57 |
March | 2422.06 | 24-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.07 |
April | 2511.51 | 10-APR-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.24 |
May | 2477.64 | 24-MAY-16:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.69 |
June | 4694.79 | 12-JUN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.64 | 0.00 |
July | 5406.34 | 17-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.40 | 0.00 |
August | 5267.59 | 07-AUG-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.87 |
September | 4405.10 | 18-SEP-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.59 |
October | 2296.11 | 13-OCT-16:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.92 |
November | 1889.03 | 07-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.93 |
December | 1552.83 | 08-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1552.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5406.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.64 | 387.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6052.65 | 12-JAN-16:50 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6192.70 | 17-FEB-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11813.05 | 16-MAR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10688.74 | 21-APR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22673.19 | 24-MAY-05:03 | 1905.79 | 1847.62 | 9524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31774.05 | 19-JUN-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32716.06 | 17-JUL-04:04 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31939.80 | 07-AUG-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32301.87 | 18-SEP-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12471.77 | 12-OCT-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7760.24 | 01-NOV-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6528.32 | 01-DEC-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6052.65 | 0.00 | 1847.62 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32716.06 | 6035.01 | 5543.17 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5729.80 | 11-JAN-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6002.22 | 28-FEB-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11960.39 | 16-MAR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11441.40 | 21-APR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15789.97 | 31-MAY-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32214.38 | 19-JUN-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33739.45 | 05-JUL-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34411.96 | 07-AUG-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 24438.84 | 18-SEP-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12089.44 | 12-OCT-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7327.74 | 01-NOV-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6195.19 | 01-DEC-15:00 | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5729.80 | 0.00 | 2463.50 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34411.96 | 6198.29 | 5543.17 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 992.21 | 14-JAN-17:03 | 267.84 | 259.70 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.62 |
February | 998.44 | 18-FEB-17:03 | 267.84 | 206.80 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.06 |
March | 3688.25 | 15-MAR-14:50 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 17.95 | 0.00 |
April | 2336.55 | 21-APR-15:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.10 |
May | 4704.01 | 23-MAY-14:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 |
June | 7319.36 | 27-JUN-15:47 | 3816.70 | 2161.23 | 4517.68 | 0.00 | 0.00 | 0.00 | 0.00 | 30.95 | 0.00 |
July | 9363.69 | 16-JUL-16:52 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 24.34 | 0.00 |
August | 7360.45 | 06-AUG-14:02 | 267.84 | 160.10 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 10.85 | 0.00 |
September | 4824.88 | 15-SEP-14:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 | 0.00 |
October | 2457.85 | 12-OCT-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.35 |
November | 1386.33 | 16-NOV-16:50 | 1272.23 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.52 |
December | 1087.46 | 01-DEC-13:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 992.21 | 267.84 | 160.10 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9363.69 | 3816.70 | 2161.23 | 4517.68 | 0.00 | 0.00 | 0.00 | 0.00 | 30.95 | 313.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 927.55 | 14-JAN-17:03 | 169.56 | 164.41 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.61 |
February | 1187.38 | 28-FEB-10:10 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.63 |
March | 2842.77 | 15-MAR-14:00 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 0.00 |
April | 4813.09 | 24-APR-09:20 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.86 |
May | 7178.00 | 31-MAY-09:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.88 |
June | 10546.87 | 11-JUN-10:43 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.16 |
July | 13211.41 | 04-JUL-09:02 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.90 |
August | 12222.61 | 06-AUG-09:23 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.85 |
September | 6153.84 | 18-SEP-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.88 |
October | 3708.58 | 11-OCT-09:40 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.70 |
November | 1365.82 | 03-NOV-09:50 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.86 |
December | 934.68 | 16-DEC-17:03 | 169.56 | 164.41 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 927.55 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13211.41 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 178.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2820.55 | 12-JAN-13:30 | 2544.47 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 932.86 |
February | 5308.69 | 28-FEB-13:50 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.13 |
March | 9675.23 | 15-MAR-13:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 23.99 | 0.00 |
April | 7678.94 | 21-APR-13:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.11 |
May | 7954.34 | 26-MAY-13:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.01 |
June | 9842.14 | 12-JUN-13:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 135.98 | 0.00 |
July | 16758.63 | 30-JUL-12:02 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.74 |
August | 16609.44 | 13-AUG-12:43 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 266.44 | 0.00 |
September | 16523.16 | 04-SEP-14:13 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.68 |
October | 11402.72 | 11-OCT-12:30 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.70 |
November | 6782.51 | 03-NOV-12:35 | 2544.47 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.78 |
December | 3159.08 | 16-DEC-13:30 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2820.55 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16758.63 | 2544.47 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 266.44 | 932.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1145.46 | 06-JAN-15:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.06 |
February | 1646.30 | 28-FEB-16:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.84 |
March | 3601.35 | 15-MAR-14:20 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 | 0.00 |
April | 5922.77 | 24-APR-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.44 |
May | 11565.86 | 07-MAY-17:23 | 0.00 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.84 |
June | 14284.06 | 11-JUN-16:42 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.73 |
July | 15259.34 | 02-JUL-17:22 | 0.00 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.64 |
August | 13947.02 | 12-AUG-17:05 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.37 |
September | 11400.40 | 10-SEP-16:03 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.81 |
October | 5749.08 | 11-OCT-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.39 |
November | 1640.07 | 03-NOV-15:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.53 |
December | 1172.06 | 04-DEC-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1145.46 | 0.00 | 101.35 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15259.34 | 805.38 | 456.05 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 | 378.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 995.27 | 14-JAN-17:03 | 267.84 | 259.70 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.68 |
February | 995.88 | 18-FEB-17:03 | 267.84 | 203.75 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.21 |
March | 1609.08 | 15-MAR-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 | 0.00 |
April | 1469.87 | 21-APR-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.89 |
May | 2725.75 | 23-MAY-14:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 |
June | 4740.64 | 27-JUN-13:30 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 50.07 | 0.00 |
July | 5516.84 | 21-JUL-13:50 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 46.81 | 0.00 |
August | 5486.81 | 14-AUG-12:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 17.77 | 0.00 |
September | 4090.76 | 15-SEP-14:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 5.89 | 0.00 |
October | 2228.05 | 05-OCT-14:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 |
November | 1399.55 | 16-NOV-16:50 | 1272.23 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.89 |
December | 1200.40 | 01-DEC-13:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 995.27 | 267.84 | 203.75 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5516.84 | 1306.65 | 1168.55 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 50.07 | 166.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 826.61 | 14-JAN-07:05 | 339.13 | 328.78 | 1694.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.96 |
February | 891.83 | 28-FEB-10:10 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.05 |
March | 1458.03 | 15-MAR-14:00 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 | 0.00 |
April | 3376.49 | 24-APR-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.52 |
May | 4689.68 | 31-MAY-09:20 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.58 |
June | 7824.26 | 11-JUN-10:13 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.00 |
July | 11152.67 | 04-JUL-09:32 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.95 |
August | 8192.81 | 06-AUG-09:23 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.57 |
September | 5188.26 | 18-SEP-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.31 |
October | 3402.40 | 11-OCT-09:40 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 |
November | 1241.65 | 03-NOV-08:50 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.35 |
December | 898.61 | 01-DEC-13:30 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 826.61 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11152.67 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 | 121.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1171.82 | 21-JAN-12:30 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.80 |
February | 1377.51 | 18-FEB-14:40 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.41 |
March | 5896.40 | 15-MAR-13:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 284.01 | 0.00 |
April | 3212.26 | 22-APR-13:40 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.02 |
May | 4673.24 | 23-MAY-14:30 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.36 |
June | 11136.91 | 27-JUN-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 6431.89 | 0.00 |
July | 11425.89 | 21-JUL-12:00 | 687.71 | 720.41 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 6033.32 | 0.00 |
August | 13009.31 | 13-AUG-12:43 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 154.57 | 0.00 |
September | 13169.01 | 04-SEP-14:13 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.06 |
October | 9254.27 | 11-OCT-12:40 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.08 |
November | 2079.40 | 03-NOV-14:30 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2708.84 |
December | 1608.45 | 16-DEC-13:40 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1171.82 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13169.01 | 1306.65 | 720.41 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 6431.89 | 2708.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 944.24 | 12-JAN-16:10 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.66 |
February | 1177.48 | 28-FEB-16:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.13 |
March | 1674.72 | 15-MAR-14:20 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 | 0.00 |
April | 3525.62 | 24-APR-17:30 | 84.78 | 152.01 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.87 |
May | 6394.81 | 27-MAY-17:10 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.89 |
June | 11252.27 | 11-JUN-17:51 | 0.00 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 |
July | 11393.34 | 16-JUL-16:41 | 339.11 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.74 | 0.00 |
August | 10806.54 | 27-AUG-17:12 | 0.00 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.08 |
September | 7037.94 | 04-SEP-17:33 | 0.00 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.15 |
October | 4798.16 | 11-OCT-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 |
November | 1327.53 | 03-NOV-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.13 |
December | 979.09 | 04-DEC-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 944.24 | 0.00 | 101.35 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11393.34 | 805.38 | 456.05 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.74 | 262.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 967.65 | 14-JAN-17:03 | 267.84 | 259.70 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.32 |
February | 970.07 | 18-FEB-17:03 | 267.84 | 206.80 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.09 |
March | 3228.25 | 15-MAR-14:50 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 0.00 |
April | 2225.31 | 21-APR-15:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.46 |
May | 4444.80 | 23-MAY-14:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
June | 6079.28 | 12-JUN-14:50 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 85.83 | 0.00 |
July | 7188.40 | 31-JUL-06:02 | 1339.19 | 1200.67 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.90 |
August | 7754.29 | 13-AUG-15:52 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 191.27 | 0.00 |
September | 4561.49 | 15-SEP-14:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 | 0.00 |
October | 2606.48 | 12-OCT-15:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.93 |
November | 1409.27 | 16-NOV-17:00 | 1272.23 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.39 |
December | 1147.91 | 01-DEC-13:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 967.65 | 267.84 | 206.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7754.29 | 1339.19 | 1200.67 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 191.27 | 261.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 916.29 | 14-JAN-17:03 | 169.56 | 164.41 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.42 |
February | 1268.69 | 28-FEB-10:00 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.58 |
March | 2583.18 | 14-MAR-10:30 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.85 |
April | 5600.22 | 24-APR-08:50 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.50 |
May | 7331.92 | 31-MAY-08:40 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.10 |
June | 11328.84 | 11-JUN-10:23 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.96 |
July | 13938.87 | 04-JUL-09:32 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.95 |
August | 12902.89 | 06-AUG-09:52 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.80 |
September | 6642.67 | 10-SEP-10:03 | 127.17 | 76.02 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.92 |
October | 4323.04 | 11-OCT-09:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.91 |
November | 1482.70 | 03-NOV-09:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.61 |
December | 1027.11 | 01-DEC-07:05 | 678.26 | 986.37 | 1694.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 916.29 | 127.17 | 76.02 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.85 | |
Maximum of Months | 13938.87 | 1610.86 | 986.37 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3816.53 | 12-JAN-13:40 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 753.85 |
February | 5524.76 | 28-FEB-13:40 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.91 |
March | 9101.29 | 15-MAR-13:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 20.30 | 0.00 |
April | 7568.24 | 24-APR-13:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.72 |
May | 7390.50 | 26-MAY-13:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 |
June | 11430.43 | 25-JUN-13:23 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.08 |
July | 15065.38 | 30-JUL-12:02 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.64 |
August | 14941.25 | 06-AUG-14:32 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 18.79 | 0.00 |
September | 15144.89 | 04-SEP-14:13 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.09 |
October | 11411.60 | 11-OCT-12:30 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.07 |
November | 7665.90 | 03-NOV-12:25 | 2544.47 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.32 |
December | 3688.14 | 16-DEC-13:30 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3688.14 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15144.89 | 2544.47 | 1440.82 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 20.30 | 753.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1152.58 | 12-JAN-16:10 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.64 |
February | 1559.24 | 28-FEB-16:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.74 |
March | 3287.11 | 15-MAR-14:20 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 | 0.00 |
April | 5841.71 | 24-APR-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.95 |
May | 11495.45 | 07-MAY-17:23 | 0.00 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.33 |
June | 13505.60 | 25-JUN-17:21 | 0.00 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.27 |
July | 13920.23 | 02-JUL-16:42 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.76 |
August | 13658.20 | 13-AUG-15:52 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 77.28 | 0.00 |
September | 11392.93 | 10-SEP-16:03 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.09 |
October | 5643.85 | 11-OCT-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 |
November | 1683.73 | 03-NOV-15:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.53 |
December | 1167.96 | 04-DEC-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1152.58 | 0.00 | 101.35 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13920.23 | 805.38 | 456.05 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 77.28 | 414.64 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.183900E+12 | 245258.45 | 02-JAN-07:10 | 0.746847E+11 | 100847.43 | 04-JAN-07:19 |
February | 0.161243E+12 | 232504.26 | 06-FEB-07:10 | 0.690320E+11 | 117585.48 | 07-FEB-07:19 |
March | 0.136008E+12 | 190676.52 | 06-MAR-07:10 | 0.431469E+11 | 97083.73 | 07-MAR-07:10 |
April | 0.105038E+12 | 151529.08 | 17-APR-06:10 | 0.175551E+11 | 61356.27 | 17-APR-06:10 |
May | 0.109416E+12 | 106959.17 | 23-MAY-15:09 | 0.989106E+10 | 31975.03 | 01-MAY-06:10 |
June | 0.132648E+12 | 158939.43 | 27-JUN-15:20 | 0.913156E+10 | 9739.95 | 06-JUN-06:10 |
July | 0.152935E+12 | 167444.51 | 17-JUL-07:10 | 0.870235E+10 | 9139.08 | 03-JUL-11:20 |
August | 0.151328E+12 | 171011.37 | 15-AUG-14:30 | 0.910600E+10 | 9092.38 | 31-AUG-11:09 |
September | 0.117289E+12 | 135194.35 | 15-SEP-10:00 | 0.861347E+10 | 14190.76 | 30-SEP-06:19 |
October | 0.108168E+12 | 131905.56 | 30-OCT-06:10 | 0.132194E+11 | 54292.01 | 17-OCT-06:40 |
November | 0.120089E+12 | 163571.53 | 24-NOV-07:10 | 0.251374E+11 | 58344.48 | 24-NOV-07:40 |
December | 0.169887E+12 | 230646.09 | 11-DEC-07:10 | 0.653782E+11 | 111898.73 | 11-DEC-07:30 |
Annual Sum or Average | 0.164795E+13 | 0.353598E+12 | ||||
Minimum of Months | 0.105038E+12 | 106959.17 | 0.861347E+10 | 9092.38 | ||
Maximum of Months | 0.183900E+12 | 245258.45 | 0.746847E+11 | 117585.48 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.238890E+11 | 0.785092E+10 | 0.641572E+11 | 0.109125E+10 | 0.516731E+10 | 1312252.65 | 0.817432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.214342E+11 | 0.646105E+10 | 0.580684E+11 | 0.987359E+09 | 0.466193E+10 | 1186778.30 | 0.696292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251638E+11 | 0.628373E+10 | 0.666107E+11 | 0.114317E+10 | 0.484968E+10 | 1343621.24 | 0.304869E+11 | 0.146904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223465E+11 | 0.520245E+10 | 0.619407E+11 | 0.105056E+10 | 0.457951E+10 | 1267813.82 | 0.937629E+10 | 0.541118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.239952E+11 | 0.463499E+10 | 0.653840E+11 | 0.111684E+10 | 0.686836E+10 | 1327936.95 | 0.156908E+10 | 0.584666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.238169E+11 | 0.415280E+10 | 0.641577E+11 | 0.109954E+10 | 0.123289E+11 | 1296568.36 | 0.377557E+09 | 0.267132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.223276E+11 | 0.440178E+10 | 0.631525E+11 | 0.106756E+10 | 0.156862E+11 | 1299182.41 | 79117572.92 | 0.462190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.249182E+11 | 0.502997E+10 | 0.666107E+11 | 0.114304E+10 | 0.150832E+11 | 1343621.24 | 0.183363E+09 | 0.383583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.224355E+11 | 0.570262E+10 | 0.619118E+11 | 0.105020E+10 | 0.918211E+10 | 1267813.82 | 0.621550E+09 | 0.163838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.235244E+11 | 0.679390E+10 | 0.641717E+11 | 0.109112E+10 | 0.503187E+10 | 1312252.65 | 0.569258E+10 | 0.186149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.236807E+11 | 0.735651E+10 | 0.627379E+11 | 0.107139E+10 | 0.413437E+10 | 1278270.02 | 0.207668E+11 | 0.339630E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232939E+11 | 0.806099E+10 | 0.631380E+11 | 0.106817E+10 | 0.481289E+10 | 1299182.41 | 0.695117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280826E+12 | 0.719317E+11 | 0.762041E+12 | 0.129802E+11 | 0.923863E+11 | 15535293.87 | 0.290037E+12 | 0.137732E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.214342E+11 | 0.415280E+10 | 0.580684E+11 | 0.987359E+09 | 0.413437E+10 | 1186778.30 | 79117572.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.251638E+11 | 0.806099E+10 | 0.666107E+11 | 0.114317E+10 | 0.156862E+11 | 1343621.24 | 0.817432E+11 | 0.462190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.646198E+11 | 0.00 | 0.100649E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.598301E+11 | 0.00 | 0.920182E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.326545E+11 | 0.00 | 0.104924E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.808811E+10 | 0.00 | 0.946701E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.245714E+09 | 0.00 | 0.964534E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5259661.51 | 0.00 | 0.912631E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.870235E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.910600E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 61802498.29 | 0.00 | 0.855167E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.412950E+10 | 0.00 | 0.908992E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.159223E+11 | 0.00 | 0.921514E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.557337E+11 | 0.00 | 0.964453E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.241291E+12 | 0.00 | 0.112307E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.855167E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.646198E+11 | 0.00 | 0.104924E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28079.40 | 02-JAN-16:49 | 5557.43 | 01-JAN-06:10 | 47562.27 | 02-JAN-08:09 | 926.74 | 02-JAN-16:00 | 7050.59 | 02-JAN-07:10 | 0.73 | 02-JAN-06:10 | 201182.34 | 02-JAN-06:19 |
February | 26916.44 | 01-FEB-16:00 | 5557.43 | 01-FEB-06:10 | 47562.27 | 01-FEB-08:09 | 926.46 | 01-FEB-08:20 | 6491.33 | 06-FEB-07:10 | 0.73 | 01-FEB-08:09 | 188985.77 | 06-FEB-07:10 |
March | 25515.54 | 17-MAR-07:10 | 5557.43 | 01-MAR-06:10 | 47562.27 | 01-MAR-08:09 | 924.52 | 17-MAR-07:19 | 7911.17 | 15-MAR-13:50 | 0.73 | 01-MAR-07:10 | 155222.79 | 06-MAR-07:10 |
April | 24583.29 | 12-APR-07:10 | 5557.43 | 01-APR-05:10 | 47562.27 | 03-APR-07:10 | 923.18 | 12-APR-07:19 | 7215.93 | 21-APR-15:30 | 0.73 | 03-APR-06:10 | 117349.30 | 17-APR-06:10 |
May | 23688.37 | 01-MAY-07:10 | 5557.43 | 01-MAY-05:10 | 47562.27 | 01-MAY-07:10 | 921.90 | 01-MAY-07:19 | 13797.02 | 31-MAY-15:00 | 0.73 | 01-MAY-07:10 | 29560.06 | 01-MAY-06:10 |
June | 23688.37 | 01-JUN-07:10 | 5557.43 | 01-JUN-19:49 | 47562.27 | 01-JUN-07:10 | 921.90 | 01-JUN-07:19 | 27116.74 | 27-JUN-15:20 | 0.73 | 01-JUN-05:30 | 12834.96 | 14-JUN-06:10 |
July | 23688.37 | 03-JUL-07:10 | 5557.43 | 01-JUL-19:00 | 47562.27 | 03-JUL-07:10 | 921.90 | 03-JUL-07:19 | 28081.09 | 17-JUL-12:09 | 0.73 | 01-JUL-05:19 | 6958.62 | 13-JUL-06:19 |
August | 23688.37 | 01-AUG-07:10 | 5557.43 | 01-AUG-19:40 | 47562.27 | 01-AUG-07:10 | 921.90 | 01-AUG-07:19 | 27296.19 | 14-AUG-15:50 | 0.73 | 01-AUG-05:10 | 9529.04 | 31-AUG-06:40 |
September | 25279.22 | 26-SEP-07:10 | 5557.43 | 01-SEP-05:10 | 47562.27 | 01-SEP-07:10 | 924.18 | 26-SEP-07:19 | 19838.10 | 21-SEP-15:00 | 0.73 | 01-SEP-05:30 | 20054.29 | 29-SEP-06:10 |
October | 27392.57 | 31-OCT-07:10 | 5557.43 | 01-OCT-05:10 | 47562.27 | 02-OCT-07:10 | 927.22 | 31-OCT-07:19 | 10390.27 | 11-OCT-15:50 | 0.73 | 16-OCT-07:10 | 91124.99 | 30-OCT-06:10 |
November | 28079.40 | 06-NOV-16:00 | 5557.43 | 01-NOV-05:10 | 47562.27 | 01-NOV-07:10 | 927.79 | 02-NOV-07:19 | 4485.63 | 03-NOV-12:50 | 0.73 | 01-NOV-11:09 | 122335.93 | 24-NOV-07:10 |
December | 28079.40 | 01-DEC-16:40 | 5557.43 | 01-DEC-06:10 | 47562.27 | 01-DEC-08:09 | 926.94 | 18-DEC-08:20 | 6432.32 | 11-DEC-07:10 | 0.73 | 04-DEC-07:10 | 187186.61 | 11-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 23688.37 | 5557.43 | 47562.27 | 921.90 | 4485.63 | 0.73 | 6958.62 | |||||||
Maximum of Months | 28079.40 | 5557.43 | 47562.27 | 927.79 | 28081.09 | 0.73 | 201182.34 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24299.85 | 15-MAR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10443.86 | 08-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28512.75 | 10-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 63553.88 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 70552.37 | 17-JUL-07:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 76834.88 | 15-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 51762.83 | 15-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19476.58 | 11-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7980.67 | 16-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76834.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 245258.45 | 02-JAN-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 7050.59 | 0.73 | 201180.70 | 0.00 | 0.00 |
February | 232504.26 | 06-FEB-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 6491.33 | 0.73 | 188985.77 | 0.00 | 0.00 |
March | 190676.52 | 06-MAR-07:10 | 8286.88 | 21853.28 | 0.00 | 255.93 | 5056.91 | 0.73 | 155222.79 | 0.00 | 0.00 |
April | 151529.08 | 17-APR-06:10 | 7990.03 | 21853.28 | 0.00 | 255.87 | 4079.87 | 0.73 | 117349.30 | 0.00 | 0.00 |
May | 106959.17 | 23-MAY-15:09 | 23688.37 | 43769.98 | 0.00 | 920.43 | 12927.91 | 0.73 | 0.00 | 25651.75 | 0.00 |
June | 158939.43 | 27-JUN-15:20 | 23688.37 | 43769.98 | 0.00 | 920.43 | 27116.74 | 0.73 | 0.00 | 63443.19 | 0.00 |
July | 167444.51 | 17-JUL-07:10 | 23688.37 | 47562.27 | 0.00 | 899.47 | 25884.59 | 0.73 | 0.00 | 69409.08 | 0.00 |
August | 171011.37 | 15-AUG-14:30 | 23688.37 | 42286.04 | 0.00 | 919.86 | 27281.50 | 0.73 | 0.00 | 76834.88 | 0.00 |
September | 135194.35 | 15-SEP-10:00 | 23688.37 | 43275.33 | 0.00 | 920.24 | 15899.64 | 0.73 | 0.00 | 51410.04 | 0.00 |
October | 131905.56 | 30-OCT-06:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 3753.40 | 0.73 | 91124.99 | 0.00 | 0.00 |
November | 163571.53 | 24-NOV-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 4208.43 | 0.73 | 122335.93 | 0.00 | 0.00 |
December | 230646.09 | 11-DEC-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 6432.32 | 0.73 | 187186.61 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 106959.17 | 7990.03 | 21853.28 | 0.00 | 255.87 | 3753.40 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 245258.45 | 23688.37 | 47562.27 | 5557.43 | 920.43 | 27281.50 | 0.73 | 201180.70 | 76834.88 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 92640.53 | 04-JAN-07:19 | 0.00 | 10165.41 | 19-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 109362.93 | 07-FEB-07:19 | 0.00 | 10471.87 | 07-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 89595.83 | 07-MAR-07:19 | 0.00 | 10125.48 | 13-MAR-11:00 | 0.00 |
April | 0.00 | 0.00 | 54340.63 | 17-APR-06:19 | 0.00 | 9509.19 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 23831.36 | 01-MAY-06:10 | 0.00 | 9401.13 | 02-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 2169.09 | 14-JUN-06:10 | 0.00 | 9269.88 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9139.08 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9092.38 | 31-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 6275.23 | 30-SEP-06:19 | 0.00 | 9138.27 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 46428.73 | 17-OCT-06:19 | 0.00 | 9265.07 | 30-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 50847.50 | 24-NOV-07:30 | 0.00 | 9399.04 | 29-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 103732.78 | 11-DEC-07:30 | 0.00 | 9523.32 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9092.38 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 109362.93 | 0.00 | 10471.87 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.71 | 0.33 | 19.71 | 0.00 | 19.71 | 0.00 | 19.71 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.19 | 0.00 | 26.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.18 | 0.00 | 26.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.17 | 0.00 | 26.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.71 | 0.33 | 19.71 | 1.67 | 24.33 | 0.00 | 24.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.71 | 0.33 | 19.71 | 1.00 | 26.19 | 0.00 | 26.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 19.34 | 1.50 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
February | 0.50 | 19.39 | 0.50 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.32 | 0.33 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Annual Sum or Average | 2.50 | 19.35 | 2.33 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.39 | 1.50 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 18.40 | 1.67 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 |
February | 2.17 | 18.27 | 1.33 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
March | 0.33 | 18.12 | 0.17 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.60 | 0.67 | 24.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.33 | 18.51 | 1.50 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
Annual Sum or Average | 7.33 | 18.38 | 4.67 | 18.75 | 0.67 | 19.05 | 0.67 | 19.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 18.51 | 1.67 | 18.87 | 0.67 | 24.60 | 0.67 | 24.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 52.17 | 16.31 | 24.00 | 16.75 | 0.00 | 16.75 | 0.00 | 16.75 |
February | 53.00 | 16.29 | 23.33 | 16.80 | 0.00 | 16.80 | 0.00 | 16.80 |
March | 13.00 | 16.73 | 5.17 | 17.27 | 0.00 | 17.27 | 0.00 | 17.27 |
April | 0.33 | 17.91 | 0.17 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.82 | 0.67 | 24.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.43 | 1.00 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 |
November | 0.83 | 17.38 | 0.17 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 |
December | 41.83 | 16.26 | 19.17 | 16.71 | 0.00 | 16.71 | 0.00 | 16.71 |
Annual Sum or Average | 161.33 | 16.33 | 72.00 | 16.81 | 2.33 | 16.90 | 2.00 | 16.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.00 | 17.91 | 24.00 | 18.31 | 1.33 | 27.43 | 1.00 | 27.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.33 | 15.03 | 7.17 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 |
February | 33.83 | 14.96 | 6.00 | 15.06 | 0.00 | 15.06 | 0.00 | 15.06 |
March | 7.17 | 15.43 | 0.33 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
April | 0.33 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.65 | 2.50 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.79 | 6.67 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.57 | 2.83 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
October | 0.17 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 |
November | 1.50 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
December | 29.17 | 14.93 | 7.17 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
Annual Sum or Average | 106.50 | 15.04 | 20.67 | 15.10 | 12.33 | 16.21 | 12.17 | 17.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.33 | 17.08 | 7.17 | 17.08 | 6.83 | 27.79 | 6.67 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.67 | 15.21 | 5.33 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 |
February | 30.00 | 15.36 | 6.17 | 15.66 | 0.00 | 15.66 | 0.00 | 15.66 |
March | 5.33 | 15.86 | 0.67 | 15.99 | 0.00 | 15.99 | 0.00 | 15.99 |
April | 0.17 | 16.80 | 0.00 | 16.80 | 0.17 | 22.07 | 0.17 | 23.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.34 | 0.50 | 27.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.04 | 3.00 | 27.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.64 | 6.33 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.77 | 4.00 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.71 | 3.00 | 27.71 |
October | 0.17 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
November | 0.50 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 |
December | 23.67 | 15.41 | 5.00 | 15.68 | 0.00 | 15.68 | 0.00 | 15.68 |
Annual Sum or Average | 89.50 | 15.37 | 17.17 | 15.58 | 17.33 | 17.26 | 17.00 | 18.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 | 0.00 | 15.32 |
Maximum of Months | 30.00 | 16.99 | 6.17 | 16.99 | 6.50 | 27.77 | 6.33 | 27.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 35.67 | 14.91 | 9.17 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
February | 34.00 | 14.87 | 7.50 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
March | 7.17 | 15.48 | 1.00 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
April | 0.17 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.77 | 0.83 | 27.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.75 | 3.83 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.10 | 4.50 | 28.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.00 | 2.83 | 28.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.72 | 1.33 | 27.73 |
October | 0.17 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 |
November | 1.33 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
December | 28.50 | 14.88 | 6.50 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
Annual Sum or Average | 107.00 | 14.96 | 24.17 | 14.97 | 22.50 | 16.87 | 13.33 | 17.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.90 | 0.00 | 14.90 |
Maximum of Months | 35.67 | 17.07 | 9.17 | 17.07 | 8.17 | 28.10 | 4.50 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.33 | 18.43 | 11.17 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
February | 17.33 | 18.38 | 12.00 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
March | 3.83 | 18.86 | 3.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
April | 0.17 | 19.26 | 0.17 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8.17 | 18.83 | 6.33 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
Annual Sum or Average | 45.83 | 18.52 | 32.67 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.33 | 19.26 | 12.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 15.73 | 0.33 | 15.80 | 0.00 | 15.80 | 0.00 | 15.80 |
February | 5.17 | 15.72 | 0.17 | 15.83 | 0.00 | 15.83 | 0.00 | 15.83 |
March | 0.50 | 16.43 | 0.00 | 16.43 | 0.00 | 16.43 | 0.00 | 16.43 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.44 | 0.33 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.65 | 2.50 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.49 | 0.67 | 27.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 16.31 | 0.17 | 16.53 | 0.00 | 16.53 | 0.00 | 16.53 |
Annual Sum or Average | 13.83 | 15.83 | 0.67 | 15.94 | 3.67 | 18.29 | 3.67 | 19.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.17 | 16.43 | 0.33 | 16.53 | 2.50 | 27.65 | 2.50 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 120.50 | 16.11 | 116.50 | 16.11 | 0.00 | 16.11 | 0.00 | 16.11 |
February | 108.50 | 16.05 | 105.00 | 16.05 | 0.00 | 16.05 | 0.00 | 16.05 |
March | 69.67 | 17.07 | 69.33 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
April | 43.00 | 18.28 | 43.00 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 |
May | 13.17 | 19.24 | 13.17 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
June | 2.83 | 20.05 | 2.83 | 20.05 | 0.33 | 20.30 | 0.33 | 20.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.08 | 2.00 | 26.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.55 | 3.83 | 26.55 |
September | 3.00 | 20.17 | 3.00 | 20.17 | 2.67 | 22.44 | 2.67 | 23.63 |
October | 23.67 | 18.78 | 23.67 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
November | 53.50 | 18.05 | 53.50 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 |
December | 96.50 | 16.09 | 95.33 | 16.08 | 0.00 | 16.08 | 0.00 | 16.08 |
Annual Sum or Average | 534.33 | 16.83 | 525.33 | 16.83 | 8.83 | 16.91 | 8.83 | 16.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.05 | 0.00 | 16.05 |
Maximum of Months | 120.50 | 20.17 | 116.50 | 20.17 | 3.83 | 26.55 | 3.83 | 26.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.67 | 15.72 | 0.50 | 15.77 | 0.00 | 15.77 | 0.00 | 15.77 |
February | 4.83 | 15.73 | 0.17 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 |
March | 0.50 | 16.44 | 0.00 | 16.44 | 0.00 | 16.44 | 0.00 | 16.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.37 | 0.17 | 27.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.68 | 1.50 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.82 | 2.33 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.65 | 2.00 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.60 | 0.67 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.17 | 16.21 | 0.17 | 16.43 | 0.00 | 16.43 | 0.00 | 16.43 |
Annual Sum or Average | 14.17 | 15.83 | 0.83 | 15.92 | 13.17 | 21.43 | 6.67 | 22.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.67 | 16.44 | 0.50 | 16.44 | 4.83 | 27.82 | 2.33 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.50 | 17.01 | 7.50 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 |
February | 22.17 | 17.09 | 9.50 | 17.78 | 0.00 | 17.78 | 0.00 | 17.78 |
March | 2.00 | 18.78 | 1.50 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15.00 | 17.02 | 6.50 | 17.63 | 0.00 | 17.63 | 0.00 | 17.63 |
Annual Sum or Average | 58.67 | 17.10 | 25.00 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.17 | 18.78 | 9.50 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.33 | 15.53 | 1.00 | 15.66 | 0.00 | 15.66 | 0.00 | 15.66 |
February | 11.83 | 15.33 | 0.50 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 |
March | 1.00 | 17.27 | 0.17 | 17.58 | 0.00 | 17.58 | 0.00 | 17.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.67 | 2.17 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.75 | 6.00 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.62 | 1.67 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.49 | 1.67 | 27.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9.00 | 15.47 | 0.33 | 15.60 | 0.00 | 15.60 | 0.00 | 15.60 |
Annual Sum or Average | 34.17 | 15.49 | 2.00 | 15.65 | 11.83 | 18.61 | 11.83 | 20.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.33 | 17.27 | 1.00 | 17.58 | 6.00 | 27.75 | 6.00 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.33 | 15.70 | 0.50 | 15.88 | 0.00 | 15.88 | 0.00 | 15.88 |
February | 10.50 | 15.56 | 0.83 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 |
March | 0.67 | 17.41 | 0.17 | 17.79 | 0.00 | 17.79 | 0.00 | 17.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.40 | 1.33 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.51 | 5.00 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.65 | 3.83 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.74 | 3.17 | 27.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.50 | 15.99 | 0.83 | 16.35 | 0.00 | 16.35 | 0.00 | 16.35 |
Annual Sum or Average | 27.00 | 15.76 | 2.33 | 16.03 | 13.67 | 19.70 | 13.67 | 21.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.50 | 17.41 | 0.83 | 17.79 | 5.00 | 27.74 | 5.00 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.83 | 15.46 | 1.33 | 15.57 | 0.00 | 15.57 | 0.00 | 15.57 |
February | 11.67 | 15.32 | 0.50 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 |
March | 0.50 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.64 | 0.83 | 27.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.01 | 2.83 | 28.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.06 | 3.50 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.85 | 2.50 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.73 | 1.50 | 27.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9.33 | 15.45 | 1.00 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 |
Annual Sum or Average | 35.33 | 15.43 | 2.83 | 15.54 | 20.00 | 19.81 | 11.17 | 21.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.83 | 16.65 | 1.33 | 16.65 | 6.67 | 28.06 | 3.50 | 28.06 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.16 | 80.67 | 21.91 | 80.67 | 21.73 |
February | 454.00 | 22.39 | 35.33 | 22.28 | 35.33 | 22.19 |
March | 452.50 | 23.36 | 14.50 | 23.37 | 3.00 | 23.35 |
April | 329.67 | 23.70 | 11.00 | 23.76 | 0.00 | 23.76 |
May | 105.17 | 23.95 | 154.17 | 24.54 | 0.00 | 24.54 |
June | 0.00 | 0.00 | 342.00 | 24.48 | 0.00 | 24.48 |
July | 0.00 | 0.00 | 486.67 | 24.45 | 0.00 | 24.45 |
August | 0.00 | 0.00 | 478.83 | 24.41 | 0.00 | 24.41 |
September | 5.17 | 23.87 | 335.50 | 24.53 | 0.00 | 24.53 |
October | 182.33 | 23.87 | 71.33 | 24.12 | 0.00 | 24.12 |
November | 447.33 | 23.68 | 0.00 | 23.68 | 0.00 | 23.68 |
December | 492.17 | 22.70 | 19.00 | 22.63 | 19.00 | 22.57 |
Annual Sum or Average | 2970.33 | 23.04 | 2029.00 | 23.53 | 138.00 | 23.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.91 | 0.00 | 21.73 |
Maximum of Months | 502.00 | 23.95 | 486.67 | 24.54 | 80.67 | 24.54 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.80 | 363.00 | 20.68 | 363.00 | 20.63 |
February | 454.00 | 20.97 | 290.17 | 20.83 | 290.17 | 20.77 |
March | 483.33 | 21.91 | 95.00 | 21.76 | 90.83 | 21.64 |
April | 468.33 | 22.87 | 5.50 | 22.85 | 5.50 | 22.83 |
May | 246.83 | 23.56 | 59.17 | 23.74 | 0.00 | 23.74 |
June | 44.17 | 23.78 | 276.17 | 24.20 | 0.00 | 24.20 |
July | 0.00 | 0.00 | 468.17 | 24.31 | 0.00 | 24.31 |
August | 0.17 | 23.59 | 417.33 | 24.31 | 0.00 | 24.31 |
September | 66.50 | 23.44 | 217.67 | 24.17 | 0.00 | 24.17 |
October | 398.67 | 22.96 | 7.33 | 22.99 | 0.00 | 22.99 |
November | 489.00 | 22.16 | 17.67 | 22.11 | 17.67 | 22.06 |
December | 497.00 | 21.02 | 280.00 | 20.87 | 280.00 | 20.80 |
Annual Sum or Average | 3650.00 | 21.95 | 2497.17 | 22.28 | 1047.17 | 22.04 |
Minimum of Months | 0.00 | 0.00 | 5.50 | 20.68 | 0.00 | 20.63 |
Maximum of Months | 502.00 | 23.78 | 468.17 | 24.31 | 363.00 | 24.31 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.34 | 455.17 | 20.30 | 455.17 | 20.28 |
February | 454.00 | 20.46 | 382.17 | 20.37 | 382.17 | 20.34 |
March | 490.67 | 21.31 | 212.83 | 21.09 | 208.67 | 20.95 |
April | 477.67 | 22.24 | 47.17 | 22.07 | 47.17 | 21.92 |
May | 310.67 | 23.27 | 46.67 | 23.40 | 0.00 | 23.40 |
June | 78.67 | 23.55 | 258.33 | 24.07 | 0.67 | 24.07 |
July | 5.33 | 23.53 | 450.83 | 24.30 | 0.00 | 24.30 |
August | 20.17 | 23.40 | 387.33 | 24.22 | 0.00 | 24.22 |
September | 165.33 | 23.17 | 157.00 | 23.72 | 0.00 | 23.72 |
October | 460.50 | 22.18 | 42.50 | 22.05 | 39.50 | 21.93 |
November | 489.00 | 21.26 | 159.00 | 21.04 | 159.00 | 20.91 |
December | 497.00 | 20.43 | 418.33 | 20.36 | 418.33 | 20.33 |
Annual Sum or Average | 3951.00 | 21.48 | 3017.33 | 21.71 | 1710.67 | 21.44 |
Minimum of Months | 5.33 | 20.34 | 42.50 | 20.30 | 0.00 | 20.28 |
Maximum of Months | 502.00 | 23.55 | 455.17 | 24.30 | 455.17 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.76 | 494.50 | 19.75 | 494.50 | 19.75 |
February | 454.00 | 19.81 | 454.00 | 19.81 | 454.00 | 19.81 |
March | 495.83 | 20.55 | 348.83 | 20.39 | 340.33 | 20.29 |
April | 479.00 | 21.36 | 150.83 | 21.04 | 150.83 | 20.85 |
May | 350.17 | 22.69 | 56.50 | 22.80 | 10.50 | 22.74 |
June | 106.50 | 23.48 | 266.00 | 24.04 | 15.00 | 24.10 |
July | 49.33 | 24.94 | 445.50 | 24.43 | 36.50 | 24.51 |
August | 76.17 | 23.48 | 368.00 | 24.12 | 12.33 | 24.16 |
September | 255.00 | 22.79 | 138.67 | 23.28 | 13.83 | 23.35 |
October | 481.67 | 21.28 | 139.67 | 20.99 | 137.00 | 20.79 |
November | 489.00 | 20.41 | 329.50 | 20.25 | 329.50 | 20.19 |
December | 497.00 | 19.76 | 480.67 | 19.74 | 480.67 | 19.74 |
Annual Sum or Average | 4235.67 | 20.93 | 3672.67 | 21.15 | 2475.00 | 20.89 |
Minimum of Months | 49.33 | 19.76 | 56.50 | 19.74 | 10.50 | 19.74 |
Maximum of Months | 502.00 | 24.94 | 494.50 | 24.43 | 494.50 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.82 | 495.00 | 19.81 | 495.00 | 19.81 |
February | 454.00 | 19.89 | 444.83 | 19.87 | 444.83 | 19.87 |
March | 489.67 | 20.68 | 305.00 | 20.51 | 287.83 | 20.37 |
April | 406.00 | 21.38 | 118.50 | 21.14 | 106.17 | 20.91 |
May | 266.33 | 22.54 | 133.50 | 23.10 | 8.33 | 23.06 |
June | 96.17 | 23.73 | 335.83 | 24.22 | 22.17 | 24.32 |
July | 66.67 | 25.86 | 463.67 | 24.63 | 58.00 | 24.79 |
August | 76.00 | 23.81 | 402.67 | 24.23 | 21.17 | 24.31 |
September | 201.33 | 22.65 | 229.17 | 23.51 | 14.33 | 23.56 |
October | 452.33 | 21.39 | 109.33 | 21.13 | 103.00 | 20.94 |
November | 489.00 | 20.50 | 313.83 | 20.33 | 313.83 | 20.25 |
December | 497.00 | 19.82 | 481.50 | 19.80 | 481.50 | 19.80 |
Annual Sum or Average | 3996.50 | 20.95 | 3832.83 | 21.34 | 2356.17 | 21.07 |
Minimum of Months | 66.67 | 19.82 | 109.33 | 19.80 | 8.33 | 19.80 |
Maximum of Months | 502.00 | 25.86 | 495.00 | 24.63 | 495.00 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.11 | 441.33 | 19.97 | 441.33 | 19.92 |
February | 450.33 | 20.12 | 381.67 | 19.95 | 381.67 | 19.89 |
March | 467.83 | 21.12 | 252.67 | 20.85 | 235.00 | 20.66 |
April | 394.33 | 21.43 | 140.67 | 21.28 | 116.83 | 21.05 |
May | 291.17 | 22.53 | 117.67 | 22.96 | 15.83 | 22.90 |
June | 127.83 | 23.42 | 294.33 | 24.05 | 22.17 | 24.15 |
July | 83.33 | 25.11 | 438.33 | 24.54 | 57.33 | 24.69 |
August | 90.83 | 23.82 | 392.83 | 24.24 | 22.83 | 24.33 |
September | 192.00 | 22.97 | 245.17 | 23.77 | 22.17 | 23.88 |
October | 391.67 | 21.58 | 146.67 | 21.59 | 89.67 | 21.35 |
November | 469.33 | 20.86 | 250.17 | 20.58 | 250.17 | 20.45 |
December | 495.50 | 20.05 | 445.83 | 19.96 | 445.83 | 19.92 |
Annual Sum or Average | 3956.17 | 21.20 | 3547.33 | 21.53 | 2100.83 | 21.25 |
Minimum of Months | 83.33 | 20.05 | 117.67 | 19.95 | 15.83 | 19.89 |
Maximum of Months | 502.00 | 25.11 | 445.83 | 24.54 | 445.83 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 492.67 | 19.81 | 492.67 | 19.81 |
February | 454.00 | 19.91 | 436.00 | 19.88 | 436.00 | 19.87 |
March | 493.33 | 20.75 | 297.67 | 20.53 | 288.67 | 20.41 |
April | 422.33 | 21.20 | 162.17 | 21.10 | 134.83 | 20.90 |
May | 321.83 | 22.37 | 120.83 | 22.83 | 17.83 | 22.80 |
June | 141.17 | 23.38 | 305.50 | 24.04 | 25.67 | 24.16 |
July | 80.50 | 24.74 | 429.50 | 24.47 | 48.00 | 24.61 |
August | 103.83 | 23.38 | 376.83 | 24.12 | 18.33 | 24.20 |
September | 257.83 | 22.61 | 181.17 | 23.32 | 20.17 | 23.41 |
October | 464.33 | 21.21 | 144.33 | 21.02 | 126.83 | 20.83 |
November | 489.00 | 20.46 | 312.67 | 20.29 | 312.67 | 20.21 |
December | 497.00 | 19.81 | 478.00 | 19.79 | 478.00 | 19.78 |
Annual Sum or Average | 4227.17 | 20.97 | 3737.33 | 21.28 | 2399.67 | 21.03 |
Minimum of Months | 80.50 | 19.81 | 120.83 | 19.79 | 17.83 | 19.78 |
Maximum of Months | 502.00 | 24.74 | 492.67 | 24.47 | 492.67 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.03 | 494.67 | 20.02 | 494.67 | 20.02 |
February | 454.00 | 20.09 | 454.00 | 20.09 | 454.00 | 20.09 |
March | 514.00 | 20.75 | 354.00 | 20.59 | 354.00 | 20.53 |
April | 485.00 | 21.26 | 142.00 | 21.06 | 142.00 | 20.93 |
May | 457.50 | 22.63 | 13.33 | 22.63 | 5.83 | 22.60 |
June | 144.67 | 23.50 | 212.00 | 23.90 | 8.50 | 23.92 |
July | 28.33 | 24.65 | 442.17 | 24.30 | 21.00 | 24.34 |
August | 43.17 | 23.59 | 370.17 | 24.17 | 6.67 | 24.18 |
September | 214.50 | 23.30 | 143.17 | 23.68 | 10.33 | 23.74 |
October | 474.67 | 22.13 | 26.00 | 22.07 | 24.33 | 22.00 |
November | 489.00 | 21.02 | 190.00 | 20.86 | 190.00 | 20.77 |
December | 497.00 | 20.20 | 466.67 | 20.17 | 466.67 | 20.16 |
Annual Sum or Average | 4303.83 | 21.25 | 3308.17 | 21.41 | 2178.00 | 21.17 |
Minimum of Months | 28.33 | 20.03 | 13.33 | 20.02 | 5.83 | 20.02 |
Maximum of Months | 514.00 | 24.65 | 494.67 | 24.30 | 494.67 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.11 | 494.50 | 20.10 | 494.50 | 20.10 |
February | 454.00 | 20.18 | 448.17 | 20.18 | 448.17 | 20.17 |
March | 506.33 | 20.94 | 287.67 | 20.74 | 287.67 | 20.65 |
April | 451.00 | 21.81 | 73.83 | 21.61 | 71.33 | 21.44 |
May | 315.67 | 22.85 | 76.83 | 23.19 | 1.17 | 23.18 |
June | 71.67 | 23.66 | 316.00 | 24.25 | 8.50 | 24.29 |
July | 35.33 | 26.19 | 478.33 | 24.57 | 34.83 | 24.68 |
August | 29.67 | 24.25 | 433.50 | 24.34 | 10.00 | 24.38 |
September | 120.50 | 23.34 | 282.83 | 24.06 | 10.67 | 24.11 |
October | 404.33 | 22.33 | 31.17 | 22.36 | 13.17 | 22.31 |
November | 489.00 | 21.17 | 155.50 | 21.00 | 155.50 | 20.89 |
December | 497.00 | 20.25 | 467.50 | 20.23 | 467.50 | 20.22 |
Annual Sum or Average | 3876.50 | 21.28 | 3545.83 | 21.68 | 2003.00 | 21.41 |
Minimum of Months | 29.67 | 20.11 | 31.17 | 20.10 | 1.17 | 20.10 |
Maximum of Months | 506.33 | 26.19 | 494.50 | 24.57 | 494.50 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.16 | 479.33 | 19.10 | 479.33 | 19.08 |
February | 454.00 | 19.16 | 433.17 | 19.11 | 433.17 | 19.09 |
March | 501.17 | 20.43 | 286.00 | 20.17 | 278.83 | 20.02 |
April | 459.50 | 21.07 | 131.00 | 20.84 | 122.33 | 20.63 |
May | 418.50 | 22.16 | 50.67 | 22.27 | 16.50 | 22.17 |
June | 211.67 | 22.89 | 220.67 | 23.59 | 38.00 | 23.62 |
July | 111.50 | 23.97 | 439.33 | 24.31 | 82.83 | 24.35 |
August | 110.67 | 23.39 | 403.50 | 24.16 | 54.50 | 24.19 |
September | 148.33 | 22.96 | 282.50 | 23.95 | 30.00 | 24.04 |
October | 392.67 | 21.82 | 82.67 | 22.03 | 23.00 | 21.88 |
November | 479.67 | 20.97 | 166.00 | 20.64 | 166.00 | 20.45 |
December | 497.00 | 19.52 | 455.50 | 19.42 | 455.50 | 19.39 |
Annual Sum or Average | 4286.67 | 20.84 | 3430.33 | 21.12 | 2180.00 | 20.82 |
Minimum of Months | 110.67 | 19.16 | 50.67 | 19.10 | 16.50 | 19.08 |
Maximum of Months | 502.00 | 23.97 | 479.33 | 24.31 | 479.33 | 24.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.08 | 492.33 | 20.07 | 492.33 | 20.07 |
February | 454.00 | 20.18 | 440.33 | 20.16 | 440.33 | 20.15 |
March | 509.83 | 20.96 | 282.50 | 20.76 | 282.50 | 20.67 |
April | 450.50 | 21.56 | 96.00 | 21.38 | 91.67 | 21.22 |
May | 348.50 | 22.71 | 67.67 | 23.02 | 1.00 | 23.02 |
June | 87.33 | 23.58 | 305.50 | 24.19 | 13.00 | 24.24 |
July | 37.50 | 25.49 | 461.67 | 24.52 | 31.50 | 24.60 |
August | 41.00 | 24.38 | 430.67 | 24.37 | 15.50 | 24.43 |
September | 144.33 | 23.33 | 234.33 | 23.98 | 12.00 | 24.06 |
October | 438.00 | 22.17 | 38.50 | 22.19 | 19.67 | 22.12 |
November | 489.00 | 21.10 | 174.83 | 20.93 | 174.83 | 20.84 |
December | 497.00 | 20.23 | 465.67 | 20.21 | 465.67 | 20.20 |
Annual Sum or Average | 3999.00 | 21.26 | 3490.00 | 21.62 | 2040.00 | 21.36 |
Minimum of Months | 37.50 | 20.08 | 38.50 | 20.07 | 1.00 | 20.07 |
Maximum of Months | 509.83 | 25.49 | 492.33 | 24.52 | 492.33 | 24.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.96 | 491.83 | 19.95 | 491.83 | 19.95 |
February | 454.00 | 20.03 | 440.67 | 20.02 | 440.67 | 20.01 |
March | 493.33 | 20.86 | 295.50 | 20.68 | 287.33 | 20.57 |
April | 479.00 | 21.82 | 76.33 | 21.59 | 76.33 | 21.41 |
May | 314.67 | 23.09 | 52.00 | 23.26 | 0.00 | 23.26 |
June | 70.50 | 23.78 | 274.00 | 24.17 | 7.50 | 24.19 |
July | 30.17 | 25.46 | 465.00 | 24.45 | 29.33 | 24.51 |
August | 31.17 | 23.61 | 403.33 | 24.24 | 5.00 | 24.24 |
September | 191.50 | 23.24 | 161.83 | 23.70 | 11.83 | 23.77 |
October | 463.83 | 21.87 | 68.33 | 21.71 | 63.00 | 21.57 |
November | 489.00 | 20.85 | 227.50 | 20.66 | 227.50 | 20.56 |
December | 497.00 | 20.04 | 465.00 | 20.00 | 465.00 | 19.99 |
Annual Sum or Average | 4016.17 | 21.18 | 3421.33 | 21.45 | 2105.33 | 21.17 |
Minimum of Months | 30.17 | 19.96 | 52.00 | 19.95 | 0.00 | 19.95 |
Maximum of Months | 502.00 | 25.46 | 491.83 | 24.45 | 491.83 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.85 | 420.00 | 19.84 | 420.00 | 19.84 |
February | 385.00 | 19.95 | 369.67 | 19.92 | 369.67 | 19.91 |
March | 415.50 | 20.92 | 224.67 | 20.74 | 213.50 | 20.61 |
April | 351.50 | 21.69 | 71.50 | 21.58 | 57.00 | 21.38 |
May | 228.83 | 22.86 | 97.50 | 23.40 | 1.33 | 23.42 |
June | 72.50 | 23.94 | 277.17 | 24.35 | 14.67 | 24.44 |
July | 48.67 | 26.26 | 400.17 | 24.73 | 47.17 | 24.88 |
August | 42.67 | 24.08 | 343.67 | 24.37 | 12.33 | 24.43 |
September | 158.50 | 23.15 | 189.33 | 23.86 | 15.67 | 23.97 |
October | 375.00 | 21.80 | 59.33 | 21.71 | 47.17 | 21.57 |
November | 417.00 | 20.83 | 202.83 | 20.64 | 202.83 | 20.54 |
December | 422.00 | 19.91 | 400.50 | 19.88 | 400.50 | 19.87 |
Annual Sum or Average | 3344.17 | 21.13 | 3056.33 | 21.53 | 1801.83 | 21.25 |
Minimum of Months | 42.67 | 19.85 | 59.33 | 19.84 | 1.33 | 19.84 |
Maximum of Months | 427.00 | 26.26 | 420.00 | 24.73 | 420.00 | 24.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.67 | 20.38 | 414.83 | 20.21 | 414.83 | 20.15 |
February | 450.17 | 20.44 | 355.67 | 20.24 | 355.67 | 20.16 |
March | 455.50 | 21.50 | 187.33 | 21.26 | 168.67 | 21.06 |
April | 381.50 | 21.92 | 78.17 | 21.87 | 55.50 | 21.68 |
May | 250.17 | 22.95 | 109.83 | 23.42 | 1.17 | 23.43 |
June | 85.17 | 23.73 | 308.67 | 24.19 | 13.00 | 24.25 |
July | 61.33 | 25.69 | 460.17 | 24.60 | 51.67 | 24.74 |
August | 49.00 | 24.69 | 423.83 | 24.40 | 22.00 | 24.49 |
September | 139.83 | 23.57 | 280.50 | 24.14 | 22.50 | 24.27 |
October | 346.00 | 22.13 | 102.33 | 22.36 | 32.00 | 22.23 |
November | 457.33 | 21.33 | 156.67 | 21.09 | 153.00 | 20.93 |
December | 494.83 | 20.39 | 407.00 | 20.25 | 407.00 | 20.20 |
Annual Sum or Average | 3670.50 | 21.49 | 3285.00 | 21.89 | 1697.00 | 21.61 |
Minimum of Months | 49.00 | 20.38 | 78.17 | 20.21 | 1.17 | 20.15 |
Maximum of Months | 499.67 | 25.69 | 460.17 | 24.60 | 414.83 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.01 | 486.00 | 19.99 | 486.00 | 19.98 |
February | 454.00 | 20.11 | 421.17 | 20.06 | 421.17 | 20.04 |
March | 493.00 | 21.09 | 248.17 | 20.88 | 237.33 | 20.73 |
April | 417.67 | 21.64 | 94.83 | 21.61 | 68.00 | 21.44 |
May | 279.33 | 22.76 | 122.33 | 23.29 | 3.00 | 23.32 |
June | 98.17 | 23.80 | 323.17 | 24.22 | 21.50 | 24.33 |
July | 57.67 | 25.34 | 457.33 | 24.53 | 42.50 | 24.65 |
August | 64.33 | 23.94 | 412.00 | 24.29 | 15.83 | 24.36 |
September | 196.00 | 23.07 | 212.17 | 23.75 | 17.00 | 23.85 |
October | 448.50 | 21.76 | 77.33 | 21.70 | 55.67 | 21.56 |
November | 488.50 | 20.87 | 216.33 | 20.68 | 216.33 | 20.57 |
December | 497.00 | 20.06 | 461.33 | 20.03 | 461.33 | 20.01 |
Annual Sum or Average | 3996.17 | 21.21 | 3532.17 | 21.58 | 2045.67 | 21.32 |
Minimum of Months | 57.67 | 20.01 | 77.33 | 19.99 | 3.00 | 19.98 |
Maximum of Months | 502.00 | 25.34 | 486.00 | 24.53 | 486.00 | 24.65 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.15964 | 19.06124 | -0.3391 | 8.95611 |
February | 454.00000 | 22.38919 | 18.47179 | -0.2807 | 7.42142 |
March | 514.00000 | 23.44847 | 25.01116 | 0.04645 | 5.97371 |
April | 485.00000 | 23.93431 | 28.52222 | 0.21479 | 6.32984 |
May | 508.00000 | 24.34949 | 32.27838 | -0.4929 | 10.64729 |
June | 496.00000 | 24.34454 | 43.24396 | -0.3612 | 8.21059 |
July | 497.00000 | 24.44508 | 51.10612 | -0.2593 | 6.92745 |
August | 514.00000 | 24.37973 | 47.79128 | -0.3015 | 7.36845 |
September | 485.00000 | 24.38337 | 43.47005 | -0.3598 | 8.30075 |
October | 502.00000 | 24.18622 | 33.62552 | 0.33032 | 7.53873 |
November | 489.00000 | 23.73815 | 28.31179 | 0.14737 | 5.83889 |
December | 497.00000 | 22.70982 | 21.91366 | -0.1759 | 6.57262 |
Annual Sum or Average | 5943.00000 | 23.71470 | 32.83752 | -0.1526 | 7.51295 |
Minimum of Months | 454.00000 | 22.15964 | 18.47179 | -0.4929 | 5.83889 |
Maximum of Months | 514.00000 | 24.44508 | 51.10612 | 0.33032 | 10.64729 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.80334 | 20.15324 | -0.6536 | 15.15271 |
February | 454.00000 | 20.96546 | 19.63566 | -0.6134 | 13.71312 |
March | 514.00000 | 22.04032 | 27.19474 | -0.2687 | 8.29955 |
April | 485.00000 | 22.91442 | 31.11694 | -0.0184 | 6.06459 |
May | 508.00000 | 23.90859 | 34.11219 | -0.6474 | 14.51972 |
June | 496.00000 | 24.15944 | 44.38582 | -0.4402 | 9.47705 |
July | 497.00000 | 24.29212 | 52.30791 | -0.3247 | 7.54116 |
August | 514.00000 | 24.25232 | 48.94888 | -0.3667 | 8.12020 |
September | 485.00000 | 24.09724 | 44.88715 | -0.4815 | 10.53101 |
October | 502.00000 | 23.18616 | 36.76135 | 0.08954 | 6.03664 |
November | 489.00000 | 22.15706 | 31.65372 | -0.2157 | 6.83701 |
December | 497.00000 | 21.01903 | 23.63969 | -0.5692 | 12.71716 |
Annual Sum or Average | 5943.00000 | 22.83009 | 34.67180 | -0.3748 | 9.90068 |
Minimum of Months | 454.00000 | 20.80334 | 19.63566 | -0.6536 | 6.03664 |
Maximum of Months | 514.00000 | 24.29212 | 52.30791 | 0.08954 | 15.15271 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.34397 | 20.20818 | -0.7975 | 20.17098 |
February | 454.00000 | 20.45625 | 20.04274 | -0.7642 | 19.01441 |
March | 514.00000 | 21.43457 | 27.79848 | -0.4308 | 11.52820 |
April | 485.00000 | 22.27184 | 31.97499 | -0.1753 | 7.36088 |
May | 508.00000 | 23.61121 | 34.64622 | -0.7479 | 18.06955 |
June | 496.00000 | 24.06356 | 44.66400 | -0.4667 | 10.22839 |
July | 497.00000 | 24.26474 | 52.27585 | -0.3259 | 7.60707 |
August | 514.00000 | 24.16840 | 49.03663 | -0.3937 | 8.60785 |
September | 485.00000 | 23.80632 | 45.57359 | -0.5867 | 13.51653 |
October | 502.00000 | 22.32968 | 38.39912 | -0.1195 | 7.08979 |
November | 489.00000 | 21.26239 | 32.96263 | -0.4465 | 10.39771 |
December | 497.00000 | 20.43058 | 24.14312 | -0.7444 | 18.33313 |
Annual Sum or Average | 5943.00000 | 22.38567 | 35.24771 | -0.4984 | 12.62364 |
Minimum of Months | 454.00000 | 20.34397 | 20.04274 | -0.7975 | 7.08979 |
Maximum of Months | 514.00000 | 24.26474 | 52.27585 | -0.1195 | 20.17098 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.76213 | 20.93393 | -1.0113 | 28.92387 |
February | 454.00000 | 19.80936 | 21.03639 | -0.9834 | 27.84261 |
March | 514.00000 | 20.67213 | 29.47996 | -0.6456 | 17.77546 |
April | 485.00000 | 21.39702 | 33.66536 | -0.3865 | 10.89322 |
May | 508.00000 | 23.11745 | 36.91492 | -0.8964 | 24.58170 |
June | 496.00000 | 23.99324 | 45.77170 | -0.4619 | 11.10904 |
July | 497.00000 | 24.31596 | 53.72687 | -0.2640 | 7.43708 |
August | 514.00000 | 24.07363 | 50.25325 | -0.3985 | 9.50389 |
September | 485.00000 | 23.37191 | 47.85474 | -0.7241 | 18.98701 |
October | 502.00000 | 21.39067 | 40.46767 | -0.3477 | 10.45176 |
November | 489.00000 | 20.40616 | 34.14047 | -0.6830 | 16.82659 |
December | 497.00000 | 19.76447 | 25.10396 | -0.9701 | 27.48236 |
Annual Sum or Average | 5943.00000 | 21.85686 | 36.71940 | -0.6454 | 17.58394 |
Minimum of Months | 454.00000 | 19.76213 | 20.93393 | -1.0113 | 7.43708 |
Maximum of Months | 514.00000 | 24.31596 | 53.72687 | -0.2640 | 28.92387 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.82172 | 20.61222 | -0.9843 | 27.79415 |
February | 454.00000 | 19.88511 | 20.72614 | -0.9455 | 26.40251 |
March | 514.00000 | 20.82995 | 28.90994 | -0.5734 | 15.87420 |
April | 485.00000 | 21.83610 | 32.45876 | -0.2474 | 10.16499 |
May | 508.00000 | 23.33976 | 35.77370 | -0.7527 | 20.69943 |
June | 496.00000 | 24.07619 | 45.10633 | -0.3533 | 9.97715 |
July | 497.00000 | 24.39890 | 52.99165 | -0.1535 | 7.26712 |
August | 514.00000 | 24.10773 | 49.73998 | -0.3078 | 8.80499 |
September | 485.00000 | 23.52123 | 46.87122 | -0.6063 | 16.43244 |
October | 502.00000 | 21.64638 | 39.48021 | -0.2643 | 9.59650 |
November | 489.00000 | 20.50069 | 33.59310 | -0.6503 | 15.92197 |
December | 497.00000 | 19.82345 | 24.81096 | -0.9519 | 26.63610 |
Annual Sum or Average | 5943.00000 | 21.99947 | 36.02858 | -0.5634 | 16.22774 |
Minimum of Months | 454.00000 | 19.82172 | 20.61222 | -0.9843 | 7.26712 |
Maximum of Months | 514.00000 | 24.39890 | 52.99165 | -0.1535 | 27.79415 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.10827 | 20.26616 | -0.8816 | 24.75605 |
February | 454.00000 | 20.14976 | 20.35995 | -0.8516 | 24.22039 |
March | 514.00000 | 21.37182 | 28.05718 | -0.4316 | 13.77529 |
April | 485.00000 | 21.96270 | 31.96445 | -0.2258 | 10.31505 |
May | 508.00000 | 23.24020 | 35.94291 | -0.8125 | 22.94061 |
June | 496.00000 | 23.94277 | 45.55002 | -0.4428 | 11.76642 |
July | 497.00000 | 24.32131 | 53.37841 | -0.2211 | 7.90565 |
August | 514.00000 | 24.11438 | 49.64650 | -0.3216 | 9.22580 |
September | 485.00000 | 23.68823 | 46.18324 | -0.5370 | 15.37791 |
October | 502.00000 | 22.14846 | 38.00403 | -0.1320 | 9.59465 |
November | 489.00000 | 20.98434 | 32.60451 | -0.5196 | 14.00638 |
December | 497.00000 | 20.06245 | 24.44333 | -0.8649 | 23.78474 |
Annual Sum or Average | 5943.00000 | 22.19135 | 35.64011 | -0.5180 | 15.58354 |
Minimum of Months | 454.00000 | 20.06245 | 20.26616 | -0.8816 | 7.90565 |
Maximum of Months | 514.00000 | 24.32131 | 53.37841 | -0.1320 | 24.75605 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.82621 | 20.38167 | -0.9929 | 28.14823 |
February | 454.00000 | 19.91257 | 20.46442 | -0.9493 | 26.66095 |
March | 514.00000 | 20.87400 | 28.69313 | -0.5726 | 15.94014 |
April | 485.00000 | 21.60721 | 32.58483 | -0.3078 | 10.92831 |
May | 508.00000 | 23.04358 | 36.43769 | -0.8484 | 24.97066 |
June | 496.00000 | 23.89957 | 45.67413 | -0.4072 | 11.95085 |
July | 497.00000 | 24.25617 | 53.59935 | -0.2106 | 8.14614 |
August | 514.00000 | 23.99652 | 50.20039 | -0.3473 | 10.01873 |
September | 485.00000 | 23.28376 | 47.63179 | -0.6882 | 19.50436 |
October | 502.00000 | 21.42294 | 39.69480 | -0.3181 | 10.35302 |
November | 489.00000 | 20.46322 | 33.44198 | -0.6621 | 16.38144 |
December | 497.00000 | 19.81279 | 24.62259 | -0.9563 | 26.86268 |
Annual Sum or Average | 5943.00000 | 21.88323 | 36.22745 | -0.6027 | 17.42504 |
Minimum of Months | 454.00000 | 19.81279 | 20.38167 | -0.9929 | 8.14614 |
Maximum of Months | 514.00000 | 24.25617 | 53.59935 | -0.2106 | 28.14823 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.02606 | 20.91436 | -0.9271 | 24.82643 |
February | 454.00000 | 20.09387 | 21.03539 | -0.9009 | 23.69781 |
March | 514.00000 | 20.74918 | 29.78948 | -0.6319 | 15.65365 |
April | 485.00000 | 21.25742 | 34.13665 | -0.4284 | 10.00055 |
May | 508.00000 | 22.76536 | 38.18350 | -1.0489 | 29.81841 |
June | 496.00000 | 23.91213 | 46.21983 | -0.5382 | 11.96243 |
July | 497.00000 | 24.23452 | 53.66097 | -0.3379 | 7.82045 |
August | 514.00000 | 24.11697 | 49.93645 | -0.4107 | 9.01130 |
September | 485.00000 | 23.71053 | 47.08322 | -0.6176 | 14.37120 |
October | 502.00000 | 22.23134 | 38.73294 | -0.1318 | 6.81576 |
November | 489.00000 | 21.01817 | 33.30127 | -0.4914 | 10.90040 |
December | 497.00000 | 20.20317 | 24.90924 | -0.8243 | 20.87250 |
Annual Sum or Average | 5943.00000 | 22.04192 | 36.60100 | -0.6060 | 15.44895 |
Minimum of Months | 454.00000 | 20.02606 | 20.91436 | -1.0489 | 6.81576 |
Maximum of Months | 514.00000 | 24.23452 | 53.66097 | -0.1318 | 29.81841 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.10865 | 21.00167 | -0.8965 | 23.54713 |
February | 454.00000 | 20.18397 | 21.14827 | -0.8619 | 22.16757 |
March | 514.00000 | 20.98489 | 29.56916 | -0.5406 | 13.37352 |
April | 485.00000 | 21.99633 | 32.89888 | -0.2244 | 8.40418 |
May | 508.00000 | 23.39086 | 36.40135 | -0.7908 | 20.79703 |
June | 496.00000 | 24.15682 | 44.96481 | -0.3810 | 9.38558 |
July | 497.00000 | 24.42997 | 52.54301 | -0.1914 | 6.85222 |
August | 514.00000 | 24.25488 | 49.11532 | -0.2868 | 7.69943 |
September | 485.00000 | 23.99289 | 45.81466 | -0.4605 | 11.17488 |
October | 502.00000 | 22.67375 | 37.72670 | -0.0098 | 6.71985 |
November | 489.00000 | 21.17332 | 33.14126 | -0.4438 | 10.23276 |
December | 497.00000 | 20.25108 | 25.00791 | -0.8092 | 20.20892 |
Annual Sum or Average | 5943.00000 | 22.31581 | 35.88191 | -0.4894 | 13.33649 |
Minimum of Months | 454.00000 | 20.10865 | 21.00167 | -0.8965 | 6.71985 |
Maximum of Months | 514.00000 | 24.42997 | 52.54301 | -0.0098 | 23.54713 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.15752 | 18.91575 | -1.0377 | 30.16044 |
February | 454.00000 | 19.15869 | 19.33595 | -1.0231 | 29.27205 |
March | 514.00000 | 20.51920 | 27.37539 | -0.5884 | 15.54999 |
April | 485.00000 | 21.26739 | 32.04578 | -0.3676 | 10.49382 |
May | 508.00000 | 22.55755 | 36.90138 | -1.0485 | 31.14495 |
June | 496.00000 | 23.64327 | 46.98862 | -0.5712 | 14.29534 |
July | 497.00000 | 24.24248 | 54.88362 | -0.2787 | 8.12934 |
August | 514.00000 | 24.08785 | 50.33024 | -0.3380 | 9.22694 |
September | 485.00000 | 23.85352 | 46.00757 | -0.4643 | 12.63025 |
October | 502.00000 | 22.36935 | 36.23470 | -0.0309 | 7.78543 |
November | 489.00000 | 21.02521 | 30.70364 | -0.4368 | 11.32795 |
December | 497.00000 | 19.51769 | 23.16002 | -0.9172 | 25.33194 |
Annual Sum or Average | 5943.00000 | 21.80256 | 35.35498 | -0.5897 | 17.05714 |
Minimum of Months | 454.00000 | 19.15752 | 18.91575 | -1.0485 | 7.78543 |
Maximum of Months | 514.00000 | 24.24248 | 54.88362 | -0.0309 | 31.14495 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.07876 | 20.86800 | -0.9111 | 24.22068 |
February | 454.00000 | 20.17794 | 20.97786 | -0.8717 | 22.64455 |
March | 514.00000 | 20.98788 | 29.43118 | -0.5449 | 13.41360 |
April | 485.00000 | 21.75650 | 33.08648 | -0.2854 | 8.89844 |
May | 508.00000 | 23.20980 | 36.84744 | -0.8524 | 23.22921 |
June | 496.00000 | 24.10868 | 45.22927 | -0.3931 | 9.81464 |
July | 497.00000 | 24.38472 | 52.88267 | -0.2175 | 7.09884 |
August | 514.00000 | 24.25162 | 49.28549 | -0.2931 | 7.91728 |
September | 485.00000 | 23.91270 | 46.26148 | -0.4972 | 12.09731 |
October | 502.00000 | 22.40970 | 38.08497 | -0.0709 | 6.85080 |
November | 489.00000 | 21.09716 | 33.11147 | -0.4631 | 10.48123 |
December | 497.00000 | 20.23463 | 24.87721 | -0.8145 | 20.44170 |
Annual Sum or Average | 5943.00000 | 22.23346 | 36.01764 | -0.5160 | 13.88305 |
Minimum of Months | 454.00000 | 20.07876 | 20.86800 | -0.9111 | 6.85080 |
Maximum of Months | 514.00000 | 24.38472 | 52.88267 | -0.0709 | 24.22068 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.95956 | 20.88663 | -0.9214 | 24.97532 |
February | 454.00000 | 20.02971 | 20.95024 | -0.8890 | 23.68076 |
March | 514.00000 | 20.98852 | 29.14691 | -0.5377 | 14.31885 |
April | 485.00000 | 21.85296 | 32.99674 | -0.2617 | 8.52562 |
May | 508.00000 | 23.47257 | 36.19838 | -0.7779 | 19.41887 |
June | 496.00000 | 24.11285 | 45.31328 | -0.4277 | 9.67514 |
July | 497.00000 | 24.35879 | 53.51272 | -0.2592 | 7.07730 |
August | 514.00000 | 24.18777 | 49.92834 | -0.3638 | 8.42396 |
September | 485.00000 | 23.72802 | 46.93613 | -0.6010 | 14.26126 |
October | 502.00000 | 22.03118 | 39.20023 | -0.1777 | 7.72326 |
November | 489.00000 | 20.85363 | 33.51132 | -0.5361 | 12.28534 |
December | 497.00000 | 20.03625 | 24.83656 | -0.8597 | 22.70101 |
Annual Sum or Average | 5943.00000 | 22.15145 | 36.22378 | -0.5490 | 14.36618 |
Minimum of Months | 454.00000 | 19.95956 | 20.88663 | -0.9214 | 7.07730 |
Maximum of Months | 514.00000 | 24.35879 | 53.51272 | -0.1777 | 24.97532 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.84821 | 19.93947 | -0.9387 | 25.66827 |
February | 385.00000 | 19.95133 | 20.05958 | -0.8941 | 23.93860 |
March | 433.00000 | 21.03900 | 28.07674 | -0.5030 | 13.24548 |
April | 410.00000 | 22.07052 | 31.59533 | -0.1820 | 8.64900 |
May | 430.00000 | 23.54823 | 35.04371 | -0.6959 | 18.24285 |
June | 418.00000 | 24.19284 | 44.56156 | -0.3422 | 9.37151 |
July | 422.00000 | 24.50656 | 52.61818 | -0.1538 | 7.20994 |
August | 433.00000 | 24.23521 | 49.21210 | -0.2948 | 8.31746 |
September | 410.00000 | 23.77693 | 46.17594 | -0.5326 | 13.75916 |
October | 427.00000 | 22.08346 | 37.97782 | -0.1487 | 7.73285 |
November | 417.00000 | 20.82646 | 32.29076 | -0.5395 | 12.41971 |
December | 422.00000 | 19.90930 | 23.89323 | -0.8869 | 23.66036 |
Annual Sum or Average | 5034.00000 | 22.17992 | 35.21146 | -0.5072 | 14.29693 |
Minimum of Months | 385.00000 | 19.84821 | 19.93947 | -0.9387 | 7.20994 |
Maximum of Months | 433.00000 | 24.50656 | 52.61818 | -0.1487 | 25.66827 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.40562 | 20.15158 | -0.7738 | 20.71213 |
February | 454.00000 | 20.47154 | 20.20292 | -0.7394 | 19.79568 |
March | 514.00000 | 21.78521 | 27.62912 | -0.3079 | 10.82714 |
April | 485.00000 | 22.42586 | 31.26177 | -0.1021 | 8.34071 |
May | 508.00000 | 23.59846 | 35.22645 | -0.6951 | 17.82133 |
June | 496.00000 | 24.10339 | 45.02134 | -0.3990 | 9.87810 |
July | 497.00000 | 24.40132 | 53.08073 | -0.2078 | 7.25317 |
August | 514.00000 | 24.25089 | 49.28671 | -0.2833 | 7.99426 |
September | 485.00000 | 24.00690 | 45.41263 | -0.4276 | 11.47317 |
October | 502.00000 | 22.77518 | 36.77234 | 0.03187 | 7.95562 |
November | 489.00000 | 21.50736 | 31.92585 | -0.3605 | 10.32960 |
December | 497.00000 | 20.40212 | 24.13743 | -0.7423 | 19.05745 |
Annual Sum or Average | 5943.00000 | 22.52751 | 35.11434 | -0.4154 | 12.57660 |
Minimum of Months | 454.00000 | 20.40212 | 20.15158 | -0.7738 | 7.25317 |
Maximum of Months | 514.00000 | 24.40132 | 53.08073 | 0.03187 | 20.71213 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.00605 | 20.29900 | -0.9070 | 24.45605 |
February | 454.00000 | 20.11415 | 20.38345 | -0.8594 | 22.80456 |
March | 514.00000 | 21.20461 | 28.37630 | -0.4630 | 12.76321 |
April | 485.00000 | 22.02062 | 31.99182 | -0.1922 | 8.81701 |
May | 508.00000 | 23.43078 | 35.73075 | -0.7229 | 19.41768 |
June | 496.00000 | 24.07738 | 45.13481 | -0.3591 | 9.87322 |
July | 497.00000 | 24.35216 | 53.26578 | -0.1931 | 7.35298 |
August | 514.00000 | 24.16247 | 49.78465 | -0.3005 | 8.47978 |
September | 485.00000 | 23.68064 | 46.74960 | -0.5557 | 14.40642 |
October | 502.00000 | 21.99676 | 38.60715 | -0.1614 | 7.87667 |
November | 489.00000 | 20.87346 | 32.93797 | -0.5227 | 12.09338 |
December | 497.00000 | 20.06351 | 24.32408 | -0.8507 | 22.30353 |
Annual Sum or Average | 5943.00000 | 22.18205 | 35.73889 | -0.5050 | 14.16470 |
Minimum of Months | 454.00000 | 20.00605 | 20.29900 | -0.9070 | 7.35298 |
Maximum of Months | 514.00000 | 24.35216 | 53.26578 | -0.1614 | 24.45605 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.191964E+10 | 0.491267E+09 | 33.50 | 0.157709E+10 | 0.342557E+09 | 0.00 | 0.88 | 15-MAR-14:00 | 0.00 | 01-MAR-00:10 | 29618.73 | 15-MAR-14:00 | 29618.73 | 15-MAR-14:00 | 8364.12 | 14-MAR-11:00 | 7398.81 | 15-MAR-14:00 | 0.00 |
April | 0.641863E+09 | 0.178456E+09 | 34.33 | 0.571024E+09 | 70839142.81 | 0.00 | 0.42 | 07-APR-13:00 | 0.00 | 01-APR-00:10 | 12550.65 | 07-APR-13:00 | 12550.65 | 07-APR-13:00 | 2805.58 | 08-APR-14:00 | 3359.99 | 07-APR-13:00 | 0.00 |
May | 0.739141E+10 | 0.191888E+10 | 185.92 | 0.664161E+10 | 0.749794E+09 | 0.00 | 1.00 | 10-MAY-14:10 | 0.00 | 01-MAY-00:10 | 38081.18 | 10-MAY-15:10 | 37577.24 | 23-MAY-15:10 | 7320.55 | 17-MAY-13:00 | 9133.66 | 10-MAY-15:10 | 0.00 |
June | 0.371018E+11 | 0.906663E+10 | 375.18 | 0.278289E+11 | 0.927284E+10 | 0.00 | 1.00 | 01-JUN-14:20 | 0.00 | 01-JUN-00:10 | 99295.73 | 27-JUN-07:40 | 61676.14 | 12-JUN-15:10 | 56423.44 | 27-JUN-07:40 | 22410.77 | 27-JUN-07:40 | 0.00 |
July | 0.662732E+11 | 0.159924E+11 | 431.16 | 0.465940E+11 | 0.196792E+11 | 0.00 | 1.00 | 03-JUL-10:10 | 0.00 | 01-JUL-00:10 | 119379.88 | 20-JUL-04:03 | 67202.21 | 21-JUL-06:03 | 71427.42 | 20-JUL-04:03 | 27235.27 | 21-JUL-04:03 | 0.00 |
August | 0.564293E+11 | 0.136731E+11 | 423.60 | 0.432204E+11 | 0.132089E+11 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 119354.13 | 14-AUG-08:00 | 64663.02 | 09-AUG-15:50 | 74832.78 | 14-AUG-04:02 | 26805.02 | 15-AUG-08:20 | 0.00 |
September | 0.247910E+11 | 0.602461E+10 | 306.21 | 0.184801E+11 | 0.631092E+10 | 0.00 | 1.00 | 08-SEP-12:00 | 0.00 | 01-SEP-00:10 | 81521.71 | 15-SEP-14:50 | 55230.55 | 21-SEP-16:00 | 37488.63 | 15-SEP-14:50 | 18762.15 | 15-SEP-14:50 | 0.00 |
October | 0.258184E+10 | 0.686294E+09 | 83.50 | 0.217135E+10 | 0.410486E+09 | 0.00 | 0.91 | 11-OCT-15:10 | 0.00 | 01-OCT-00:10 | 30931.77 | 11-OCT-15:10 | 30931.77 | 11-OCT-15:10 | 5950.08 | 12-OCT-15:00 | 7258.69 | 11-OCT-15:10 | 0.00 |
November | 0.430241E+09 | 0.119827E+09 | 18.83 | 0.306001E+09 | 0.124239E+09 | 0.00 | 0.36 | 16-NOV-18:00 | 0.00 | 01-NOV-00:10 | 10699.79 | 16-NOV-18:00 | 8719.68 | 16-NOV-13:00 | 2802.75 | 04-NOV-15:00 | 2905.69 | 16-NOV-18:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.197560E+12 | 0.481515E+11 | 1892.23 | 0.147390E+12 | 0.501698E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.662732E+11 | 0.159924E+11 | 431.16 | 0.465940E+11 | 0.196792E+11 | 0.00 | 1.00 | 0.00 | 119379.88 | 67202.21 | 74832.78 | 27235.27 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.182828E+10 | 0.464634E+09 | 33.50 | 0.151079E+10 | 0.317489E+09 | 0.00 | 0.98 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 | 31319.32 | 15-MAR-13:50 | 31319.32 | 15-MAR-13:50 | 7860.88 | 14-MAR-10:40 | 7577.48 | 15-MAR-14:00 | 0.00 |
April | 0.641270E+09 | 0.178016E+09 | 37.61 | 0.578581E+09 | 62688758.48 | 0.00 | 0.47 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 13066.87 | 08-APR-13:30 | 11421.49 | 07-APR-14:00 | 2142.34 | 08-APR-14:10 | 3454.62 | 08-APR-13:30 | 0.00 |
May | 0.743017E+10 | 0.191977E+10 | 194.67 | 0.671035E+10 | 0.719825E+09 | 0.00 | 1.00 | 10-MAY-13:30 | 0.00 | 01-MAY-00:10 | 37888.27 | 23-MAY-14:30 | 37888.27 | 23-MAY-14:30 | 7201.34 | 14-MAY-16:13 | 9057.40 | 10-MAY-15:00 | 0.00 |
June | 0.349759E+11 | 0.853966E+10 | 380.52 | 0.265269E+11 | 0.844899E+10 | 0.00 | 1.00 | 01-JUN-13:50 | 0.00 | 01-JUN-00:10 | 84965.80 | 27-JUN-07:40 | 59667.49 | 12-JUN-14:10 | 48235.73 | 27-JUN-07:40 | 20226.88 | 27-JUN-13:00 | 0.00 |
July | 0.605083E+11 | 0.145934E+11 | 434.85 | 0.427601E+11 | 0.177483E+11 | 0.00 | 1.00 | 02-JUL-14:02 | 0.00 | 01-JUL-00:10 | 109879.33 | 20-JUL-04:03 | 60887.22 | 21-JUL-13:40 | 65486.31 | 20-JUL-04:03 | 25188.83 | 21-JUL-04:03 | 0.00 |
August | 0.494184E+11 | 0.120017E+11 | 418.93 | 0.382276E+11 | 0.111907E+11 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 109713.50 | 14-AUG-04:02 | 62161.05 | 09-AUG-15:20 | 68943.05 | 14-AUG-04:02 | 24539.62 | 15-AUG-14:30 | 0.00 |
September | 0.209809E+11 | 0.513486E+10 | 300.87 | 0.157346E+11 | 0.524633E+10 | 0.00 | 1.00 | 08-SEP-12:10 | 0.00 | 01-SEP-00:10 | 72972.60 | 15-SEP-11:00 | 50934.27 | 21-SEP-15:40 | 32793.26 | 15-SEP-11:00 | 16705.90 | 15-SEP-11:00 | 0.00 |
October | 0.221312E+10 | 0.594172E+09 | 83.39 | 0.183683E+10 | 0.376294E+09 | 0.00 | 0.83 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 25578.27 | 11-OCT-15:00 | 25578.27 | 11-OCT-15:00 | 5308.22 | 12-OCT-15:00 | 6131.77 | 11-OCT-15:00 | 0.00 |
November | 0.380973E+09 | 0.106434E+09 | 18.83 | 0.264720E+09 | 0.116253E+09 | 0.00 | 0.33 | 16-NOV-18:00 | 0.00 | 01-NOV-00:10 | 8941.35 | 16-NOV-18:00 | 6741.39 | 16-NOV-13:00 | 2667.00 | 04-NOV-15:00 | 2446.90 | 16-NOV-18:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.178377E+12 | 0.435327E+11 | 1903.17 | 0.134150E+12 | 0.442269E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.605083E+11 | 0.145934E+11 | 434.85 | 0.427601E+11 | 0.177483E+11 | 0.00 | 1.00 | 0.00 | 109879.33 | 62161.05 | 68943.05 | 25188.83 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.202180E+10 | 0.513139E+09 | 33.50 | 0.169064E+10 | 0.331158E+09 | 0.00 | 1.00 | 15-MAR-13:30 | 0.00 | 01-MAR-00:10 | 38623.37 | 15-MAR-14:00 | 38623.37 | 15-MAR-14:00 | 8658.33 | 14-MAR-10:50 | 9323.55 | 15-MAR-14:00 | 0.00 |
April | 0.663087E+09 | 0.184645E+09 | 36.03 | 0.586878E+09 | 76209359.56 | 0.00 | 0.45 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 13937.20 | 08-APR-13:30 | 11907.88 | 07-APR-14:00 | 2592.71 | 08-APR-14:00 | 3703.14 | 08-APR-13:30 | 0.00 |
May | 0.773543E+10 | 0.200800E+10 | 194.13 | 0.690879E+10 | 0.826646E+09 | 0.00 | 1.00 | 10-MAY-13:00 | 0.00 | 01-MAY-00:10 | 43850.57 | 10-MAY-14:30 | 43850.57 | 10-MAY-14:30 | 7937.31 | 14-MAY-16:13 | 10577.56 | 10-MAY-14:30 | 0.00 |
June | 0.371763E+11 | 0.910689E+10 | 376.49 | 0.280503E+11 | 0.912602E+10 | 0.00 | 1.00 | 01-JUN-14:00 | 0.00 | 01-JUN-00:10 | 122643.29 | 27-JUN-14:55 | 73319.87 | 27-JUN-15:43 | 68702.34 | 27-JUN-14:55 | 28026.02 | 27-JUN-15:40 | 0.00 |
July | 0.646039E+11 | 0.156331E+11 | 432.40 | 0.457896E+11 | 0.188143E+11 | 0.00 | 1.00 | 02-JUL-14:02 | 0.00 | 01-JUL-00:10 | 122720.51 | 20-JUL-05:03 | 72530.26 | 21-JUL-13:30 | 74077.39 | 20-JUL-05:03 | 28212.39 | 21-JUL-04:03 | 0.00 |
August | 0.519432E+11 | 0.126835E+11 | 417.21 | 0.401179E+11 | 0.118254E+11 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 122703.17 | 14-AUG-04:02 | 71431.78 | 09-AUG-15:10 | 77037.75 | 14-AUG-04:02 | 27674.67 | 15-AUG-14:20 | 0.00 |
September | 0.211470E+11 | 0.522437E+10 | 299.32 | 0.154993E+11 | 0.564769E+10 | 0.00 | 1.00 | 08-SEP-13:00 | 0.00 | 01-SEP-00:10 | 85919.48 | 15-SEP-12:30 | 57460.68 | 21-SEP-15:30 | 38094.20 | 15-SEP-12:30 | 19963.60 | 15-SEP-12:30 | 0.00 |
October | 0.214142E+10 | 0.581023E+09 | 81.50 | 0.171966E+10 | 0.421763E+09 | 0.00 | 0.75 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 25029.75 | 11-OCT-15:00 | 25029.75 | 11-OCT-15:00 | 5655.32 | 12-OCT-15:00 | 6146.81 | 11-OCT-15:00 | 0.00 |
November | 0.404647E+09 | 0.113369E+09 | 18.83 | 0.276534E+09 | 0.128113E+09 | 0.00 | 0.32 | 27-NOV-07:03 | 0.00 | 01-NOV-00:10 | 9693.22 | 27-NOV-07:03 | 8259.98 | 27-NOV-07:03 | 2929.84 | 04-NOV-15:00 | 2658.86 | 27-NOV-07:03 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.187837E+12 | 0.460480E+11 | 1889.40 | 0.140640E+12 | 0.471973E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.646039E+11 | 0.156331E+11 | 432.40 | 0.457896E+11 | 0.188143E+11 | 0.00 | 1.00 | 0.00 | 122720.51 | 73319.87 | 77037.75 | 28212.39 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 330.08 | 0.00 | 330.08 | 5.49 | 1960.14 | 0.00 | 0.00 | 0.00 |
February | 502.92 | 0.00 | 502.92 | 34.01 | 1830.62 | 0.00 | 0.00 | 0.00 |
March | 609.91 | 0.00 | 609.91 | 205.08 | 1306.31 | 0.00 | 0.00 | 0.00 |
April | 777.14 | 3.10 | 774.04 | 435.61 | 919.41 | 0.00 | 0.00 | 0.00 |
May | 903.00 | 38.29 | 864.71 | 713.91 | 606.06 | 0.00 | 0.00 | 0.00 |
June | 1086.12 | 92.46 | 993.67 | 1167.78 | 403.67 | 0.00 | 0.00 | 0.00 |
July | 1007.52 | 65.04 | 942.49 | 1253.01 | 286.22 | 0.00 | 0.00 | 0.00 |
August | 871.79 | 13.26 | 858.53 | 1025.70 | 375.79 | 0.00 | 0.00 | 0.00 |
September | 663.45 | 0.14 | 663.31 | 604.14 | 597.60 | 0.00 | 0.00 | 0.00 |
October | 495.96 | 0.00 | 495.96 | 257.88 | 907.43 | 0.00 | 0.00 | 0.00 |
November | 333.27 | 0.00 | 333.27 | 81.03 | 1173.99 | 0.00 | 0.00 | 0.00 |
December | 308.95 | 0.00 | 308.95 | 6.33 | 1853.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 658.15 | 17.77 | 640.38 | 485.20 | 1014.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.95 | 0.00 | 308.95 | 5.49 | 286.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1086.12 | 92.46 | 993.67 | 1253.01 | 1960.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 402.70 | 129.85 | 272.85 | 159.21 | 1185.88 | 0.00 | 0.00 | 0.00 |
February | 590.88 | 177.31 | 413.57 | 285.51 | 1120.98 | 0.00 | 0.00 | 0.00 |
March | 847.90 | 355.09 | 492.81 | 674.11 | 799.74 | 0.00 | 0.00 | 0.00 |
April | 1122.25 | 495.87 | 626.38 | 1067.34 | 582.81 | 0.00 | 0.00 | 0.00 |
May | 1257.32 | 556.18 | 701.14 | 1367.07 | 410.09 | 0.00 | 0.00 | 0.00 |
June | 1404.21 | 620.59 | 783.62 | 1703.54 | 273.09 | 0.00 | 0.00 | 0.00 |
July | 1348.41 | 593.69 | 754.73 | 1758.26 | 192.02 | 0.00 | 0.00 | 0.00 |
August | 1217.77 | 511.15 | 706.62 | 1554.74 | 248.69 | 0.00 | 0.00 | 0.00 |
September | 1013.39 | 449.50 | 563.89 | 1171.94 | 381.72 | 0.00 | 0.00 | 0.00 |
October | 687.67 | 284.44 | 403.23 | 629.07 | 572.30 | 0.00 | 0.00 | 0.00 |
November | 390.06 | 125.13 | 264.93 | 252.14 | 747.07 | 0.00 | 0.00 | 0.00 |
December | 314.02 | 64.88 | 249.13 | 83.89 | 1160.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 884.36 | 364.52 | 519.84 | 895.51 | 637.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 314.02 | 64.88 | 249.13 | 83.89 | 192.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1404.21 | 620.59 | 783.62 | 1758.26 | 1185.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1419.34 | 828.51 | 590.83 | 1157.83 | 1667.62 | 0.00 | 0.00 | 0.00 |
February | 1620.54 | 781.41 | 839.13 | 1302.36 | 1636.86 | 0.00 | 0.00 | 0.00 |
March | 1977.97 | 1111.41 | 866.56 | 1955.18 | 1205.89 | 0.00 | 0.00 | 0.00 |
April | 1638.07 | 654.58 | 983.50 | 1690.96 | 954.80 | 0.00 | 0.00 | 0.00 |
May | 1433.46 | 416.34 | 1017.13 | 1596.42 | 668.03 | 0.00 | 0.00 | 0.00 |
June | 1392.86 | 295.15 | 1097.71 | 1727.59 | 442.76 | 0.00 | 0.00 | 0.00 |
July | 1421.89 | 344.99 | 1076.89 | 1952.60 | 310.46 | 0.00 | 0.00 | 0.00 |
August | 1596.30 | 517.56 | 1078.74 | 2159.46 | 397.85 | 0.00 | 0.00 | 0.00 |
September | 1856.02 | 904.02 | 952.00 | 2319.82 | 613.35 | 0.00 | 0.00 | 0.00 |
October | 1775.94 | 1014.45 | 761.49 | 1937.15 | 883.45 | 0.00 | 0.00 | 0.00 |
November | 1271.89 | 718.02 | 553.87 | 1224.19 | 1112.53 | 0.00 | 0.00 | 0.00 |
December | 1186.85 | 614.25 | 572.60 | 919.03 | 1632.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1548.78 | 683.03 | 865.75 | 1663.97 | 956.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1186.85 | 295.15 | 553.87 | 919.03 | 310.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1977.97 | 1111.41 | 1097.71 | 2319.82 | 1667.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 345.51 | 81.11 | 264.40 | 98.29 | 1233.23 | 0.00 | 0.00 | 0.00 |
February | 559.98 | 143.92 | 416.06 | 245.38 | 1158.86 | 0.00 | 0.00 | 0.00 |
March | 877.66 | 375.79 | 501.87 | 712.57 | 822.24 | 0.00 | 0.00 | 0.00 |
April | 1074.58 | 440.62 | 633.96 | 1023.66 | 610.37 | 0.00 | 0.00 | 0.00 |
May | 1267.64 | 572.89 | 694.75 | 1394.22 | 434.51 | 0.00 | 0.00 | 0.00 |
June | 1529.44 | 719.38 | 810.06 | 1881.91 | 297.90 | 0.00 | 0.00 | 0.00 |
July | 1367.38 | 599.50 | 767.87 | 1794.09 | 212.53 | 0.00 | 0.00 | 0.00 |
August | 1236.71 | 525.86 | 710.85 | 1598.21 | 266.23 | 0.00 | 0.00 | 0.00 |
September | 971.20 | 419.42 | 551.78 | 1129.31 | 401.59 | 0.00 | 0.00 | 0.00 |
October | 629.58 | 221.77 | 407.81 | 566.32 | 592.88 | 0.00 | 0.00 | 0.00 |
November | 373.09 | 107.51 | 265.58 | 232.97 | 762.22 | 0.00 | 0.00 | 0.00 |
December | 323.44 | 70.47 | 252.96 | 95.09 | 1179.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 881.13 | 357.55 | 523.58 | 901.17 | 661.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 323.44 | 70.47 | 252.96 | 95.09 | 212.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1529.44 | 719.38 | 810.06 | 1881.91 | 1233.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.02 | 0.00 | 110.02 | 1.03 | 668.32 | 0.00 | 0.00 | 0.00 |
February | 167.63 | 0.00 | 167.63 | 10.55 | 623.98 | 0.00 | 0.00 | 0.00 |
March | 203.29 | 0.00 | 203.29 | 72.26 | 442.75 | 0.00 | 0.00 | 0.00 |
April | 259.04 | 1.03 | 258.00 | 153.40 | 308.07 | 0.00 | 0.00 | 0.00 |
May | 300.99 | 12.76 | 288.22 | 252.77 | 195.37 | 0.00 | 0.00 | 0.00 |
June | 362.02 | 30.82 | 331.21 | 400.41 | 131.00 | 0.00 | 0.00 | 0.00 |
July | 335.83 | 21.68 | 314.15 | 427.28 | 92.07 | 0.00 | 0.00 | 0.00 |
August | 290.58 | 4.42 | 286.16 | 346.59 | 126.19 | 0.00 | 0.00 | 0.00 |
September | 221.14 | 0.05 | 221.09 | 201.08 | 211.36 | 0.00 | 0.00 | 0.00 |
October | 165.31 | 0.00 | 165.31 | 79.01 | 337.12 | 0.00 | 0.00 | 0.00 |
November | 111.08 | 0.00 | 111.08 | 23.16 | 429.87 | 0.00 | 0.00 | 0.00 |
December | 102.98 | 0.00 | 102.98 | 1.43 | 648.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 219.37 | 5.92 | 213.45 | 165.01 | 349.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.98 | 0.00 | 102.98 | 1.03 | 92.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.02 | 30.82 | 331.21 | 427.28 | 668.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.03 | 0.00 | 110.03 | 1.03 | 668.36 | 0.00 | 0.00 | 0.00 |
February | 167.64 | 0.00 | 167.64 | 10.55 | 624.01 | 0.00 | 0.00 | 0.00 |
March | 203.30 | 0.00 | 203.30 | 72.27 | 442.78 | 0.00 | 0.00 | 0.00 |
April | 259.05 | 1.03 | 258.02 | 153.41 | 308.09 | 0.00 | 0.00 | 0.00 |
May | 301.01 | 12.76 | 288.24 | 252.79 | 195.39 | 0.00 | 0.00 | 0.00 |
June | 362.05 | 30.82 | 331.23 | 400.44 | 131.01 | 0.00 | 0.00 | 0.00 |
July | 335.85 | 21.68 | 314.17 | 427.31 | 92.08 | 0.00 | 0.00 | 0.00 |
August | 290.60 | 4.42 | 286.18 | 346.62 | 126.20 | 0.00 | 0.00 | 0.00 |
September | 221.15 | 0.05 | 221.11 | 201.09 | 211.37 | 0.00 | 0.00 | 0.00 |
October | 165.32 | 0.00 | 165.32 | 79.01 | 337.15 | 0.00 | 0.00 | 0.00 |
November | 111.09 | 0.00 | 111.09 | 23.16 | 429.89 | 0.00 | 0.00 | 0.00 |
December | 102.98 | 0.00 | 102.98 | 1.43 | 648.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 219.39 | 5.92 | 213.46 | 165.02 | 349.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.98 | 0.00 | 102.98 | 1.03 | 92.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.05 | 30.82 | 331.23 | 427.31 | 668.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.03 | 0.00 | 110.03 | 1.03 | 668.36 | 0.00 | 0.00 | 0.00 |
February | 167.64 | 0.00 | 167.64 | 10.55 | 624.01 | 0.00 | 0.00 | 0.00 |
March | 203.30 | 0.00 | 203.30 | 72.27 | 442.78 | 0.00 | 0.00 | 0.00 |
April | 259.05 | 1.03 | 258.02 | 153.41 | 308.09 | 0.00 | 0.00 | 0.00 |
May | 301.01 | 12.76 | 288.24 | 252.79 | 195.39 | 0.00 | 0.00 | 0.00 |
June | 362.05 | 30.82 | 331.23 | 400.44 | 131.01 | 0.00 | 0.00 | 0.00 |
July | 335.85 | 21.68 | 314.17 | 427.31 | 92.08 | 0.00 | 0.00 | 0.00 |
August | 290.60 | 4.42 | 286.18 | 346.62 | 126.20 | 0.00 | 0.00 | 0.00 |
September | 221.15 | 0.05 | 221.11 | 201.09 | 211.37 | 0.00 | 0.00 | 0.00 |
October | 165.32 | 0.00 | 165.32 | 79.01 | 337.15 | 0.00 | 0.00 | 0.00 |
November | 111.09 | 0.00 | 111.09 | 23.16 | 429.89 | 0.00 | 0.00 | 0.00 |
December | 102.98 | 0.00 | 102.98 | 1.43 | 648.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 219.39 | 5.92 | 213.46 | 165.02 | 349.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.98 | 0.00 | 102.98 | 1.03 | 92.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.05 | 30.82 | 331.23 | 427.31 | 668.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 387.38 | 124.91 | 262.47 | 152.25 | 1172.49 | 0.00 | 0.00 | 0.00 |
February | 568.40 | 170.56 | 397.84 | 274.82 | 1106.76 | 0.00 | 0.00 | 0.00 |
March | 815.64 | 341.58 | 474.06 | 658.50 | 792.22 | 0.00 | 0.00 | 0.00 |
April | 1079.55 | 477.00 | 602.55 | 1039.20 | 579.36 | 0.00 | 0.00 | 0.00 |
May | 1209.49 | 535.02 | 674.47 | 1335.20 | 397.13 | 0.00 | 0.00 | 0.00 |
June | 1350.80 | 596.98 | 753.81 | 1656.48 | 266.07 | 0.00 | 0.00 | 0.00 |
July | 1297.12 | 571.10 | 726.02 | 1707.30 | 186.55 | 0.00 | 0.00 | 0.00 |
August | 1171.44 | 491.70 | 679.74 | 1504.50 | 249.78 | 0.00 | 0.00 | 0.00 |
September | 974.84 | 432.40 | 542.44 | 1125.69 | 400.18 | 0.00 | 0.00 | 0.00 |
October | 661.51 | 273.62 | 387.89 | 587.19 | 623.83 | 0.00 | 0.00 | 0.00 |
November | 375.22 | 120.37 | 254.85 | 231.63 | 794.35 | 0.00 | 0.00 | 0.00 |
December | 302.07 | 62.41 | 239.66 | 77.99 | 1171.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 850.72 | 350.66 | 500.06 | 865.74 | 642.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 302.07 | 62.41 | 239.66 | 77.99 | 186.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1350.80 | 596.98 | 753.81 | 1707.30 | 1172.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.32 | 4.94 | 10.38 | 6.02 | 46.36 | 0.00 | 0.00 | 0.00 |
February | 22.47 | 6.74 | 15.73 | 10.87 | 43.76 | 0.00 | 0.00 | 0.00 |
March | 32.25 | 13.51 | 18.74 | 26.04 | 31.32 | 0.00 | 0.00 | 0.00 |
April | 42.68 | 18.86 | 23.82 | 41.09 | 22.91 | 0.00 | 0.00 | 0.00 |
May | 47.82 | 21.15 | 26.67 | 52.79 | 15.70 | 0.00 | 0.00 | 0.00 |
June | 53.41 | 23.60 | 29.81 | 65.50 | 10.52 | 0.00 | 0.00 | 0.00 |
July | 51.29 | 22.58 | 28.71 | 67.51 | 7.38 | 0.00 | 0.00 | 0.00 |
August | 46.32 | 19.44 | 26.88 | 59.49 | 9.88 | 0.00 | 0.00 | 0.00 |
September | 38.54 | 17.10 | 21.45 | 44.51 | 15.82 | 0.00 | 0.00 | 0.00 |
October | 26.16 | 10.82 | 15.34 | 23.22 | 24.67 | 0.00 | 0.00 | 0.00 |
November | 14.84 | 4.76 | 10.08 | 9.16 | 31.41 | 0.00 | 0.00 | 0.00 |
December | 11.94 | 2.47 | 9.48 | 3.08 | 46.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.64 | 13.86 | 19.77 | 34.23 | 25.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.94 | 2.47 | 9.48 | 3.08 | 7.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.41 | 23.60 | 29.81 | 67.51 | 46.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 473.13 | 276.18 | 196.95 | 395.93 | 559.09 | 0.00 | 0.00 | 0.00 |
February | 540.20 | 260.48 | 279.72 | 448.30 | 546.97 | 0.00 | 0.00 | 0.00 |
March | 659.34 | 370.48 | 288.86 | 670.73 | 411.35 | 0.00 | 0.00 | 0.00 |
April | 546.04 | 218.20 | 327.84 | 580.25 | 320.95 | 0.00 | 0.00 | 0.00 |
May | 477.83 | 138.78 | 339.05 | 551.25 | 216.21 | 0.00 | 0.00 | 0.00 |
June | 464.30 | 98.39 | 365.91 | 590.95 | 144.48 | 0.00 | 0.00 | 0.00 |
July | 473.98 | 115.00 | 358.97 | 661.42 | 102.46 | 0.00 | 0.00 | 0.00 |
August | 532.12 | 172.53 | 359.59 | 726.80 | 137.27 | 0.00 | 0.00 | 0.00 |
September | 618.69 | 301.35 | 317.34 | 776.83 | 221.44 | 0.00 | 0.00 | 0.00 |
October | 592.00 | 338.16 | 253.84 | 646.30 | 328.86 | 0.00 | 0.00 | 0.00 |
November | 423.98 | 239.35 | 184.63 | 407.65 | 406.19 | 0.00 | 0.00 | 0.00 |
December | 395.63 | 204.76 | 190.87 | 310.79 | 559.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 516.28 | 227.68 | 288.59 | 564.61 | 328.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 395.63 | 98.39 | 184.63 | 310.79 | 102.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 659.34 | 370.48 | 365.91 | 776.83 | 559.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 473.13 | 276.18 | 196.95 | 395.93 | 559.09 | 0.00 | 0.00 | 0.00 |
February | 540.20 | 260.48 | 279.72 | 448.30 | 546.97 | 0.00 | 0.00 | 0.00 |
March | 659.34 | 370.48 | 288.86 | 670.73 | 411.35 | 0.00 | 0.00 | 0.00 |
April | 546.04 | 218.20 | 327.84 | 580.25 | 320.95 | 0.00 | 0.00 | 0.00 |
May | 477.83 | 138.78 | 339.05 | 551.25 | 216.21 | 0.00 | 0.00 | 0.00 |
June | 464.30 | 98.39 | 365.91 | 590.95 | 144.48 | 0.00 | 0.00 | 0.00 |
July | 473.98 | 115.00 | 358.97 | 661.42 | 102.46 | 0.00 | 0.00 | 0.00 |
August | 532.12 | 172.53 | 359.59 | 726.80 | 137.27 | 0.00 | 0.00 | 0.00 |
September | 618.69 | 301.35 | 317.34 | 776.83 | 221.44 | 0.00 | 0.00 | 0.00 |
October | 592.00 | 338.16 | 253.84 | 646.30 | 328.86 | 0.00 | 0.00 | 0.00 |
November | 423.98 | 239.35 | 184.63 | 407.65 | 406.19 | 0.00 | 0.00 | 0.00 |
December | 395.63 | 204.76 | 190.87 | 310.79 | 559.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 516.28 | 227.68 | 288.59 | 564.61 | 328.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 395.63 | 98.39 | 184.63 | 310.79 | 102.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 659.34 | 370.48 | 365.91 | 776.83 | 559.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 473.10 | 276.16 | 196.94 | 395.90 | 559.06 | 0.00 | 0.00 | 0.00 |
February | 540.16 | 260.46 | 279.70 | 448.27 | 546.94 | 0.00 | 0.00 | 0.00 |
March | 659.30 | 370.46 | 288.84 | 670.69 | 411.33 | 0.00 | 0.00 | 0.00 |
April | 546.01 | 218.19 | 327.82 | 580.21 | 320.93 | 0.00 | 0.00 | 0.00 |
May | 477.80 | 138.77 | 339.03 | 551.22 | 216.20 | 0.00 | 0.00 | 0.00 |
June | 464.27 | 98.38 | 365.89 | 590.91 | 144.47 | 0.00 | 0.00 | 0.00 |
July | 473.95 | 114.99 | 358.95 | 661.38 | 102.45 | 0.00 | 0.00 | 0.00 |
August | 532.08 | 172.51 | 359.57 | 726.76 | 137.27 | 0.00 | 0.00 | 0.00 |
September | 618.65 | 301.33 | 317.32 | 776.78 | 221.42 | 0.00 | 0.00 | 0.00 |
October | 591.96 | 338.14 | 253.82 | 646.26 | 328.84 | 0.00 | 0.00 | 0.00 |
November | 423.95 | 239.33 | 184.62 | 407.62 | 406.16 | 0.00 | 0.00 | 0.00 |
December | 395.61 | 204.74 | 190.86 | 310.77 | 559.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 516.24 | 227.67 | 288.57 | 564.58 | 328.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 395.61 | 98.38 | 184.62 | 310.77 | 102.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 659.30 | 370.46 | 365.89 | 776.78 | 559.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 332.37 | 78.03 | 254.34 | 94.96 | 1214.30 | 0.00 | 0.00 | 0.00 |
February | 538.67 | 138.44 | 400.23 | 240.36 | 1141.69 | 0.00 | 0.00 | 0.00 |
March | 844.27 | 361.50 | 482.78 | 700.50 | 816.06 | 0.00 | 0.00 | 0.00 |
April | 1033.70 | 423.86 | 609.84 | 1001.84 | 605.18 | 0.00 | 0.00 | 0.00 |
May | 1219.41 | 551.09 | 668.32 | 1362.33 | 423.14 | 0.00 | 0.00 | 0.00 |
June | 1471.26 | 692.02 | 779.24 | 1828.96 | 293.91 | 0.00 | 0.00 | 0.00 |
July | 1315.36 | 576.70 | 738.66 | 1742.06 | 208.47 | 0.00 | 0.00 | 0.00 |
August | 1189.67 | 505.85 | 683.81 | 1545.19 | 269.67 | 0.00 | 0.00 | 0.00 |
September | 934.26 | 403.46 | 530.79 | 1083.79 | 421.95 | 0.00 | 0.00 | 0.00 |
October | 605.63 | 213.34 | 392.29 | 530.54 | 642.77 | 0.00 | 0.00 | 0.00 |
November | 358.90 | 103.42 | 255.48 | 215.67 | 808.17 | 0.00 | 0.00 | 0.00 |
December | 311.13 | 67.79 | 243.34 | 90.06 | 1188.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 847.61 | 343.95 | 503.66 | 873.07 | 667.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 311.13 | 67.79 | 243.34 | 90.06 | 208.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1471.26 | 692.02 | 779.24 | 1828.96 | 1214.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.14 | 3.09 | 10.06 | 3.75 | 48.01 | 0.00 | 0.00 | 0.00 |
February | 21.30 | 5.47 | 15.82 | 9.50 | 45.14 | 0.00 | 0.00 | 0.00 |
March | 33.38 | 14.29 | 19.09 | 27.70 | 32.27 | 0.00 | 0.00 | 0.00 |
April | 40.87 | 16.76 | 24.11 | 39.61 | 23.93 | 0.00 | 0.00 | 0.00 |
May | 48.21 | 21.79 | 26.42 | 53.87 | 16.73 | 0.00 | 0.00 | 0.00 |
June | 58.17 | 27.36 | 30.81 | 72.32 | 11.62 | 0.00 | 0.00 | 0.00 |
July | 52.01 | 22.80 | 29.21 | 68.88 | 8.24 | 0.00 | 0.00 | 0.00 |
August | 47.04 | 20.00 | 27.04 | 61.10 | 10.66 | 0.00 | 0.00 | 0.00 |
September | 36.94 | 15.95 | 20.99 | 42.85 | 16.68 | 0.00 | 0.00 | 0.00 |
October | 23.95 | 8.44 | 15.51 | 20.98 | 25.41 | 0.00 | 0.00 | 0.00 |
November | 14.19 | 4.09 | 10.10 | 8.53 | 31.95 | 0.00 | 0.00 | 0.00 |
December | 12.30 | 2.68 | 9.62 | 3.56 | 46.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.51 | 13.60 | 19.91 | 34.52 | 26.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.30 | 2.68 | 9.62 | 3.56 | 8.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 58.17 | 27.36 | 30.81 | 72.32 | 48.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 330.08 | 0.00 | 330.08 | 3.32 | 2024.82 | 0.00 | 0.00 | 0.00 |
February | 502.92 | 0.00 | 502.92 | 28.92 | 1895.02 | 0.00 | 0.00 | 0.00 |
March | 609.91 | 0.00 | 609.91 | 195.75 | 1376.72 | 0.00 | 0.00 | 0.00 |
April | 777.14 | 3.10 | 774.04 | 418.17 | 980.95 | 0.00 | 0.00 | 0.00 |
May | 903.00 | 38.29 | 864.71 | 700.40 | 640.78 | 0.00 | 0.00 | 0.00 |
June | 1086.12 | 92.46 | 993.67 | 1166.12 | 418.22 | 0.00 | 0.00 | 0.00 |
July | 1007.52 | 65.04 | 942.49 | 1256.76 | 293.58 | 0.00 | 0.00 | 0.00 |
August | 871.79 | 13.26 | 858.53 | 1024.94 | 390.62 | 0.00 | 0.00 | 0.00 |
September | 663.45 | 0.14 | 663.31 | 594.14 | 638.23 | 0.00 | 0.00 | 0.00 |
October | 495.96 | 0.00 | 495.96 | 237.16 | 989.42 | 0.00 | 0.00 | 0.00 |
November | 333.27 | 0.00 | 333.27 | 69.90 | 1266.92 | 0.00 | 0.00 | 0.00 |
December | 308.95 | 0.00 | 308.95 | 4.36 | 1933.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 658.15 | 17.77 | 640.38 | 477.71 | 1066.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.95 | 0.00 | 308.95 | 3.32 | 293.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1086.12 | 92.46 | 993.67 | 1256.76 | 2024.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 402.70 | 129.85 | 272.85 | 154.92 | 1226.02 | 0.00 | 0.00 | 0.00 |
February | 590.88 | 177.31 | 413.57 | 278.26 | 1159.66 | 0.00 | 0.00 | 0.00 |
March | 847.90 | 355.09 | 492.81 | 664.01 | 842.84 | 0.00 | 0.00 | 0.00 |
April | 1122.25 | 495.87 | 626.38 | 1055.21 | 618.01 | 0.00 | 0.00 | 0.00 |
May | 1257.32 | 556.18 | 701.14 | 1361.19 | 430.87 | 0.00 | 0.00 | 0.00 |
June | 1404.21 | 620.59 | 783.62 | 1704.57 | 282.21 | 0.00 | 0.00 | 0.00 |
July | 1348.41 | 593.69 | 754.73 | 1762.15 | 196.58 | 0.00 | 0.00 | 0.00 |
August | 1217.77 | 511.15 | 706.62 | 1555.83 | 257.77 | 0.00 | 0.00 | 0.00 |
September | 1013.39 | 449.50 | 563.89 | 1166.10 | 404.46 | 0.00 | 0.00 | 0.00 |
October | 687.67 | 284.44 | 403.23 | 613.24 | 620.05 | 0.00 | 0.00 | 0.00 |
November | 390.06 | 125.13 | 264.93 | 241.64 | 804.01 | 0.00 | 0.00 | 0.00 |
December | 314.02 | 64.88 | 249.13 | 80.15 | 1209.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 884.36 | 364.52 | 519.84 | 889.74 | 668.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 314.02 | 64.88 | 249.13 | 80.15 | 196.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1404.21 | 620.59 | 783.62 | 1762.15 | 1226.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1419.34 | 828.51 | 590.83 | 1146.54 | 1730.43 | 0.00 | 0.00 | 0.00 |
February | 1620.54 | 781.41 | 839.13 | 1289.49 | 1698.47 | 0.00 | 0.00 | 0.00 |
March | 1977.97 | 1111.41 | 866.56 | 1939.62 | 1274.73 | 0.00 | 0.00 | 0.00 |
April | 1638.07 | 654.58 | 983.50 | 1675.23 | 1015.45 | 0.00 | 0.00 | 0.00 |
May | 1433.46 | 416.34 | 1017.13 | 1588.64 | 706.59 | 0.00 | 0.00 | 0.00 |
June | 1392.86 | 295.15 | 1097.71 | 1729.03 | 461.37 | 0.00 | 0.00 | 0.00 |
July | 1421.89 | 344.99 | 1076.89 | 1958.17 | 320.15 | 0.00 | 0.00 | 0.00 |
August | 1596.30 | 517.56 | 1078.74 | 2161.59 | 414.44 | 0.00 | 0.00 | 0.00 |
September | 1856.02 | 904.02 | 952.00 | 2313.47 | 651.67 | 0.00 | 0.00 | 0.00 |
October | 1775.94 | 1014.45 | 761.49 | 1914.28 | 958.76 | 0.00 | 0.00 | 0.00 |
November | 1271.89 | 718.02 | 553.87 | 1204.38 | 1199.73 | 0.00 | 0.00 | 0.00 |
December | 1186.85 | 614.25 | 572.60 | 906.78 | 1706.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1548.78 | 683.03 | 865.75 | 1654.39 | 1007.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1186.85 | 295.15 | 553.87 | 906.78 | 320.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1977.97 | 1111.41 | 1097.71 | 2313.47 | 1730.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 345.51 | 81.11 | 264.40 | 95.69 | 1273.74 | 0.00 | 0.00 | 0.00 |
February | 559.98 | 143.92 | 416.06 | 241.19 | 1198.66 | 0.00 | 0.00 | 0.00 |
March | 877.66 | 375.79 | 501.87 | 704.96 | 867.89 | 0.00 | 0.00 | 0.00 |
April | 1074.58 | 440.62 | 633.96 | 1013.58 | 649.61 | 0.00 | 0.00 | 0.00 |
May | 1267.64 | 572.89 | 694.75 | 1387.81 | 459.51 | 0.00 | 0.00 | 0.00 |
June | 1529.44 | 719.38 | 810.06 | 1883.18 | 309.90 | 0.00 | 0.00 | 0.00 |
July | 1367.38 | 599.50 | 767.87 | 1797.82 | 219.00 | 0.00 | 0.00 | 0.00 |
August | 1236.71 | 525.86 | 710.85 | 1598.62 | 277.11 | 0.00 | 0.00 | 0.00 |
September | 971.20 | 419.42 | 551.78 | 1122.64 | 428.14 | 0.00 | 0.00 | 0.00 |
October | 629.58 | 221.77 | 407.81 | 552.45 | 644.17 | 0.00 | 0.00 | 0.00 |
November | 373.09 | 107.51 | 265.58 | 223.93 | 820.75 | 0.00 | 0.00 | 0.00 |
December | 323.44 | 70.47 | 252.96 | 91.97 | 1228.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 881.13 | 357.55 | 523.58 | 896.33 | 695.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 323.44 | 70.47 | 252.96 | 91.97 | 219.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1529.44 | 719.38 | 810.06 | 1883.18 | 1273.74 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.884097E+09 | 0.00 | 0.884097E+09 | 14701898.09 | 0.525003E+10 |
February | 0.121667E+10 | 0.00 | 0.121667E+10 | 82280480.17 | 0.442864E+10 |
March | 0.163357E+10 | 0.00 | 0.163357E+10 | 0.549278E+09 | 0.349881E+10 |
April | 0.201436E+10 | 8038086.86 | 0.200632E+10 | 0.112911E+10 | 0.238310E+10 |
May | 0.241860E+10 | 0.102563E+09 | 0.231604E+10 | 0.191214E+10 | 0.162326E+10 |
June | 0.281523E+10 | 0.239647E+09 | 0.257558E+10 | 0.302689E+10 | 0.104632E+10 |
July | 0.269855E+10 | 0.174197E+09 | 0.252435E+10 | 0.335607E+10 | 0.766603E+09 |
August | 0.233500E+10 | 35521897.19 | 0.229947E+10 | 0.274723E+10 | 0.100651E+10 |
September | 0.171966E+10 | 357270.95 | 0.171930E+10 | 0.156593E+10 | 0.154898E+10 |
October | 0.132837E+10 | 0.00 | 0.132837E+10 | 0.690694E+09 | 0.243046E+10 |
November | 0.863837E+09 | 0.00 | 0.863837E+09 | 0.210027E+09 | 0.304298E+10 |
December | 0.827489E+09 | 0.00 | 0.827489E+09 | 16948774.62 | 0.496439E+10 |
Annual Sum or Average | 0.207554E+11 | 0.560324E+09 | 0.201951E+11 | 0.153013E+11 | 0.319901E+11 |
Minimum of Months | 0.827489E+09 | 0.00 | 0.827489E+09 | 14701898.09 | 0.766603E+09 |
Maximum of Months | 0.281523E+10 | 0.239647E+09 | 0.257558E+10 | 0.335607E+10 | 0.525003E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107859E+10 | 0.347796E+09 | 0.730792E+09 | 0.426430E+09 | 0.317626E+10 |
February | 0.142946E+10 | 0.428945E+09 | 0.100052E+10 | 0.690697E+09 | 0.271187E+10 |
March | 0.227101E+10 | 0.951083E+09 | 0.131993E+10 | 0.180553E+10 | 0.214203E+10 |
April | 0.290887E+10 | 0.128529E+10 | 0.162358E+10 | 0.276656E+10 | 0.151064E+10 |
May | 0.336761E+10 | 0.148967E+10 | 0.187794E+10 | 0.366155E+10 | 0.109839E+10 |
June | 0.363972E+10 | 0.160857E+10 | 0.203115E+10 | 0.441557E+10 | 0.707842E+09 |
July | 0.361159E+10 | 0.159013E+10 | 0.202146E+10 | 0.470932E+10 | 0.514303E+09 |
August | 0.326166E+10 | 0.136907E+10 | 0.189260E+10 | 0.416422E+10 | 0.666085E+09 |
September | 0.262671E+10 | 0.116511E+10 | 0.146161E+10 | 0.303767E+10 | 0.989427E+09 |
October | 0.184186E+10 | 0.761840E+09 | 0.108002E+10 | 0.168491E+10 | 0.153285E+10 |
November | 0.101103E+10 | 0.324327E+09 | 0.686706E+09 | 0.653559E+09 | 0.193640E+10 |
December | 0.841065E+09 | 0.173782E+09 | 0.667283E+09 | 0.224703E+09 | 0.310793E+10 |
Annual Sum or Average | 0.278892E+11 | 0.114956E+11 | 0.163936E+11 | 0.282407E+11 | 0.200940E+11 |
Minimum of Months | 0.841065E+09 | 0.173782E+09 | 0.667283E+09 | 0.224703E+09 | 0.514303E+09 |
Maximum of Months | 0.363972E+10 | 0.160857E+10 | 0.203115E+10 | 0.470932E+10 | 0.317626E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380157E+10 | 0.221909E+10 | 0.158248E+10 | 0.310114E+10 | 0.446656E+10 |
February | 0.392040E+10 | 0.189038E+10 | 0.203002E+10 | 0.315066E+10 | 0.395990E+10 |
March | 0.529780E+10 | 0.297679E+10 | 0.232100E+10 | 0.523675E+10 | 0.322985E+10 |
April | 0.424589E+10 | 0.169666E+10 | 0.254922E+10 | 0.438297E+10 | 0.247484E+10 |
May | 0.383938E+10 | 0.111511E+10 | 0.272427E+10 | 0.427585E+10 | 0.178926E+10 |
June | 0.361030E+10 | 0.765037E+09 | 0.284527E+10 | 0.447792E+10 | 0.114764E+10 |
July | 0.380838E+10 | 0.924034E+09 | 0.288435E+10 | 0.522984E+10 | 0.831531E+09 |
August | 0.427553E+10 | 0.138623E+10 | 0.288930E+10 | 0.578389E+10 | 0.106560E+10 |
September | 0.481081E+10 | 0.234322E+10 | 0.246759E+10 | 0.601297E+10 | 0.158981E+10 |
October | 0.475667E+10 | 0.271710E+10 | 0.203957E+10 | 0.518847E+10 | 0.236624E+10 |
November | 0.329673E+10 | 0.186112E+10 | 0.143562E+10 | 0.317309E+10 | 0.288367E+10 |
December | 0.317887E+10 | 0.164521E+10 | 0.153366E+10 | 0.246152E+10 | 0.437204E+10 |
Annual Sum or Average | 0.488423E+11 | 0.215400E+11 | 0.273024E+11 | 0.524751E+11 | 0.301769E+11 |
Minimum of Months | 0.317887E+10 | 0.765037E+09 | 0.143562E+10 | 0.246152E+10 | 0.831531E+09 |
Maximum of Months | 0.529780E+10 | 0.297679E+10 | 0.288930E+10 | 0.601297E+10 | 0.446656E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.925412E+09 | 0.217250E+09 | 0.708162E+09 | 0.263257E+09 | 0.330308E+10 |
February | 0.135469E+10 | 0.348165E+09 | 0.100653E+10 | 0.593627E+09 | 0.280352E+10 |
March | 0.235073E+10 | 0.100652E+10 | 0.134420E+10 | 0.190856E+10 | 0.220227E+10 |
April | 0.278531E+10 | 0.114208E+10 | 0.164322E+10 | 0.265334E+10 | 0.158209E+10 |
May | 0.339524E+10 | 0.153442E+10 | 0.186081E+10 | 0.373427E+10 | 0.116380E+10 |
June | 0.396431E+10 | 0.186464E+10 | 0.209967E+10 | 0.487790E+10 | 0.772167E+09 |
July | 0.366239E+10 | 0.160571E+10 | 0.205667E+10 | 0.480528E+10 | 0.569233E+09 |
August | 0.331241E+10 | 0.140847E+10 | 0.190395E+10 | 0.428065E+10 | 0.713059E+09 |
September | 0.251736E+10 | 0.108713E+10 | 0.143022E+10 | 0.292718E+10 | 0.104092E+10 |
October | 0.168627E+10 | 0.593999E+09 | 0.109227E+10 | 0.151682E+10 | 0.158796E+10 |
November | 0.967054E+09 | 0.278670E+09 | 0.688384E+09 | 0.603863E+09 | 0.197568E+10 |
December | 0.866294E+09 | 0.188755E+09 | 0.677539E+09 | 0.254688E+09 | 0.315843E+10 |
Annual Sum or Average | 0.277875E+11 | 0.112758E+11 | 0.165116E+11 | 0.284194E+11 | 0.208722E+11 |
Minimum of Months | 0.866294E+09 | 0.188755E+09 | 0.677539E+09 | 0.254688E+09 | 0.569233E+09 |
Maximum of Months | 0.396431E+10 | 0.186464E+10 | 0.209967E+10 | 0.487790E+10 | 0.330308E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294685E+09 | 0.00 | 0.294685E+09 | 2766132.23 | 0.179002E+10 |
February | 0.405539E+09 | 0.00 | 0.405539E+09 | 25522869.17 | 0.150952E+10 |
March | 0.544498E+09 | 0.00 | 0.544498E+09 | 0.193550E+09 | 0.118587E+10 |
April | 0.671421E+09 | 2679235.52 | 0.668742E+09 | 0.397612E+09 | 0.798515E+09 |
May | 0.806163E+09 | 34185907.45 | 0.771977E+09 | 0.677027E+09 | 0.523290E+09 |
June | 0.938366E+09 | 79878478.38 | 0.858487E+09 | 0.103788E+10 | 0.339554E+09 |
July | 0.899474E+09 | 58063085.82 | 0.841411E+09 | 0.114442E+10 | 0.246601E+09 |
August | 0.778295E+09 | 11840072.19 | 0.766455E+09 | 0.928315E+09 | 0.337998E+09 |
September | 0.573193E+09 | 119084.68 | 0.573074E+09 | 0.521198E+09 | 0.547849E+09 |
October | 0.442769E+09 | 0.00 | 0.442769E+09 | 0.211616E+09 | 0.902955E+09 |
November | 0.287932E+09 | 0.00 | 0.287932E+09 | 60019019.45 | 0.111422E+10 |
December | 0.275817E+09 | 0.00 | 0.275817E+09 | 3831497.69 | 0.173592E+10 |
Annual Sum or Average | 0.691815E+10 | 0.186766E+09 | 0.673139E+10 | 0.520375E+10 | 0.110323E+11 |
Minimum of Months | 0.275817E+09 | 0.00 | 0.275817E+09 | 2766132.23 | 0.246601E+09 |
Maximum of Months | 0.938366E+09 | 79878478.38 | 0.858487E+09 | 0.114442E+10 | 0.179002E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294704E+09 | 0.00 | 0.294704E+09 | 2766307.04 | 0.179013E+10 |
February | 0.405565E+09 | 0.00 | 0.405565E+09 | 25524482.18 | 0.150962E+10 |
March | 0.544532E+09 | 0.00 | 0.544532E+09 | 0.193562E+09 | 0.118595E+10 |
April | 0.671463E+09 | 2679404.84 | 0.668784E+09 | 0.397637E+09 | 0.798566E+09 |
May | 0.806214E+09 | 34188067.94 | 0.772026E+09 | 0.677069E+09 | 0.523323E+09 |
June | 0.938425E+09 | 79883526.57 | 0.858542E+09 | 0.103794E+10 | 0.339576E+09 |
July | 0.899531E+09 | 58066755.31 | 0.841464E+09 | 0.114450E+10 | 0.246617E+09 |
August | 0.778344E+09 | 11840820.47 | 0.766504E+09 | 0.928374E+09 | 0.338019E+09 |
September | 0.573229E+09 | 119092.21 | 0.573110E+09 | 0.521231E+09 | 0.547883E+09 |
October | 0.442797E+09 | 0.00 | 0.442797E+09 | 0.211630E+09 | 0.903012E+09 |
November | 0.287950E+09 | 0.00 | 0.287950E+09 | 60022812.55 | 0.111429E+10 |
December | 0.275834E+09 | 0.00 | 0.275834E+09 | 3831739.83 | 0.173603E+10 |
Annual Sum or Average | 0.691859E+10 | 0.186778E+09 | 0.673181E+10 | 0.520408E+10 | 0.110330E+11 |
Minimum of Months | 0.275834E+09 | 0.00 | 0.275834E+09 | 2766307.04 | 0.246617E+09 |
Maximum of Months | 0.938425E+09 | 79883526.57 | 0.858542E+09 | 0.114450E+10 | 0.179013E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294704E+09 | 0.00 | 0.294704E+09 | 2766307.04 | 0.179013E+10 |
February | 0.405565E+09 | 0.00 | 0.405565E+09 | 25524482.18 | 0.150962E+10 |
March | 0.544532E+09 | 0.00 | 0.544532E+09 | 0.193562E+09 | 0.118595E+10 |
April | 0.671463E+09 | 2679404.84 | 0.668784E+09 | 0.397637E+09 | 0.798566E+09 |
May | 0.806214E+09 | 34188067.94 | 0.772026E+09 | 0.677069E+09 | 0.523323E+09 |
June | 0.938425E+09 | 79883526.57 | 0.858542E+09 | 0.103794E+10 | 0.339576E+09 |
July | 0.899531E+09 | 58066755.31 | 0.841464E+09 | 0.114450E+10 | 0.246617E+09 |
August | 0.778344E+09 | 11840820.47 | 0.766504E+09 | 0.928374E+09 | 0.338019E+09 |
September | 0.573229E+09 | 119092.21 | 0.573110E+09 | 0.521231E+09 | 0.547883E+09 |
October | 0.442797E+09 | 0.00 | 0.442797E+09 | 0.211630E+09 | 0.903012E+09 |
November | 0.287950E+09 | 0.00 | 0.287950E+09 | 60022812.55 | 0.111429E+10 |
December | 0.275834E+09 | 0.00 | 0.275834E+09 | 3831739.83 | 0.173603E+10 |
Annual Sum or Average | 0.691859E+10 | 0.186778E+09 | 0.673181E+10 | 0.520408E+10 | 0.110330E+11 |
Minimum of Months | 0.275834E+09 | 0.00 | 0.275834E+09 | 2766307.04 | 0.246617E+09 |
Maximum of Months | 0.938425E+09 | 79883526.57 | 0.858542E+09 | 0.114450E+10 | 0.179013E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103756E+10 | 0.334564E+09 | 0.702991E+09 | 0.407780E+09 | 0.314040E+10 |
February | 0.137508E+10 | 0.412626E+09 | 0.962454E+09 | 0.664849E+09 | 0.267747E+10 |
March | 0.218462E+10 | 0.914899E+09 | 0.126972E+10 | 0.176372E+10 | 0.212189E+10 |
April | 0.279820E+10 | 0.123639E+10 | 0.156181E+10 | 0.269361E+10 | 0.150171E+10 |
May | 0.323949E+10 | 0.143299E+10 | 0.180650E+10 | 0.357621E+10 | 0.106367E+10 |
June | 0.350126E+10 | 0.154738E+10 | 0.195388E+10 | 0.429359E+10 | 0.689645E+09 |
July | 0.347420E+10 | 0.152963E+10 | 0.194457E+10 | 0.457284E+10 | 0.499661E+09 |
August | 0.313758E+10 | 0.131698E+10 | 0.182060E+10 | 0.402965E+10 | 0.669007E+09 |
September | 0.252679E+10 | 0.112078E+10 | 0.140601E+10 | 0.291779E+10 | 0.103727E+10 |
October | 0.177179E+10 | 0.732856E+09 | 0.103893E+10 | 0.157274E+10 | 0.167088E+10 |
November | 0.972571E+09 | 0.311988E+09 | 0.660583E+09 | 0.600374E+09 | 0.205895E+10 |
December | 0.809068E+09 | 0.167170E+09 | 0.641898E+09 | 0.208895E+09 | 0.313771E+10 |
Annual Sum or Average | 0.268282E+11 | 0.110583E+11 | 0.157699E+11 | 0.273020E+11 | 0.202683E+11 |
Minimum of Months | 0.809068E+09 | 0.167170E+09 | 0.641898E+09 | 0.208895E+09 | 0.499661E+09 |
Maximum of Months | 0.350126E+10 | 0.154738E+10 | 0.195388E+10 | 0.457284E+10 | 0.314040E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41024007.43 | 13228371.45 | 27795635.98 | 16123255.53 | 0.124169E+09 |
February | 54369427.35 | 16314846.49 | 38054580.86 | 26287518.54 | 0.105865E+09 |
March | 86377782.88 | 36174296.78 | 50203486.10 | 69735756.98 | 83897685.47 |
April | 0.110638E+09 | 48885792.30 | 61752691.01 | 0.106503E+09 | 59376392.92 |
May | 0.128087E+09 | 56659274.04 | 71427368.49 | 0.141400E+09 | 42056751.16 |
June | 0.138437E+09 | 61181866.60 | 77254827.74 | 0.169765E+09 | 27267943.17 |
July | 0.137367E+09 | 60480322.99 | 76886380.32 | 0.180806E+09 | 19756130.35 |
August | 0.124057E+09 | 52072164.91 | 71985038.67 | 0.159329E+09 | 26451933.94 |
September | 99906859.06 | 44314631.90 | 55592227.15 | 0.115367E+09 | 41012639.24 |
October | 70054905.41 | 28976462.07 | 41078443.35 | 62184808.66 | 66064895.87 |
November | 38454578.54 | 12335725.91 | 26118852.63 | 23738260.80 | 81408953.45 |
December | 31989832.31 | 6609754.45 | 25380077.86 | 8259522.04 | 0.124062E+09 |
Annual Sum or Average | 0.106076E+10 | 0.437234E+09 | 0.623530E+09 | 0.107950E+10 | 0.801389E+09 |
Minimum of Months | 31989832.31 | 6609754.45 | 25380077.86 | 8259522.04 | 19756130.35 |
Maximum of Months | 0.138437E+09 | 61181866.60 | 77254827.74 | 0.180806E+09 | 0.124169E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126723E+10 | 0.739720E+09 | 0.527511E+09 | 0.106046E+10 | 0.149748E+10 |
February | 0.130684E+10 | 0.630147E+09 | 0.676693E+09 | 0.108453E+10 | 0.132324E+10 |
March | 0.176599E+10 | 0.992297E+09 | 0.773690E+09 | 0.179649E+10 | 0.110177E+10 |
April | 0.141534E+10 | 0.565573E+09 | 0.849765E+09 | 0.150401E+10 | 0.831915E+09 |
May | 0.127983E+10 | 0.371717E+09 | 0.908114E+09 | 0.147647E+10 | 0.579094E+09 |
June | 0.120347E+10 | 0.255021E+09 | 0.948447E+09 | 0.153175E+10 | 0.374480E+09 |
July | 0.126950E+10 | 0.308022E+09 | 0.961475E+09 | 0.177155E+10 | 0.274417E+09 |
August | 0.142522E+10 | 0.462092E+09 | 0.963127E+09 | 0.194667E+10 | 0.367676E+09 |
September | 0.160365E+10 | 0.781097E+09 | 0.822554E+09 | 0.201354E+10 | 0.573960E+09 |
October | 0.158561E+10 | 0.905728E+09 | 0.679877E+09 | 0.173106E+10 | 0.880830E+09 |
November | 0.109895E+10 | 0.620392E+09 | 0.478554E+09 | 0.105663E+10 | 0.105284E+10 |
December | 0.105966E+10 | 0.548420E+09 | 0.511236E+09 | 0.832414E+09 | 0.149754E+10 |
Annual Sum or Average | 0.162813E+11 | 0.718023E+10 | 0.910104E+10 | 0.178056E+11 | 0.103552E+11 |
Minimum of Months | 0.105966E+10 | 0.255021E+09 | 0.478554E+09 | 0.832414E+09 | 0.274417E+09 |
Maximum of Months | 0.176599E+10 | 0.992297E+09 | 0.963127E+09 | 0.201354E+10 | 0.149754E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126723E+10 | 0.739720E+09 | 0.527511E+09 | 0.106046E+10 | 0.149748E+10 |
February | 0.130684E+10 | 0.630147E+09 | 0.676693E+09 | 0.108453E+10 | 0.132324E+10 |
March | 0.176599E+10 | 0.992297E+09 | 0.773690E+09 | 0.179649E+10 | 0.110177E+10 |
April | 0.141534E+10 | 0.565573E+09 | 0.849765E+09 | 0.150401E+10 | 0.831915E+09 |
May | 0.127983E+10 | 0.371717E+09 | 0.908114E+09 | 0.147647E+10 | 0.579094E+09 |
June | 0.120347E+10 | 0.255021E+09 | 0.948447E+09 | 0.153175E+10 | 0.374480E+09 |
July | 0.126950E+10 | 0.308022E+09 | 0.961475E+09 | 0.177155E+10 | 0.274417E+09 |
August | 0.142522E+10 | 0.462092E+09 | 0.963127E+09 | 0.194667E+10 | 0.367676E+09 |
September | 0.160365E+10 | 0.781097E+09 | 0.822554E+09 | 0.201354E+10 | 0.573960E+09 |
October | 0.158561E+10 | 0.905728E+09 | 0.679877E+09 | 0.173106E+10 | 0.880830E+09 |
November | 0.109895E+10 | 0.620392E+09 | 0.478554E+09 | 0.105663E+10 | 0.105284E+10 |
December | 0.105966E+10 | 0.548420E+09 | 0.511236E+09 | 0.832414E+09 | 0.149754E+10 |
Annual Sum or Average | 0.162813E+11 | 0.718023E+10 | 0.910104E+10 | 0.178056E+11 | 0.103552E+11 |
Minimum of Months | 0.105966E+10 | 0.255021E+09 | 0.478554E+09 | 0.832414E+09 | 0.274417E+09 |
Maximum of Months | 0.176599E+10 | 0.992297E+09 | 0.963127E+09 | 0.201354E+10 | 0.149754E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126715E+10 | 0.739673E+09 | 0.527477E+09 | 0.106039E+10 | 0.149738E+10 |
February | 0.130676E+10 | 0.630107E+09 | 0.676651E+09 | 0.108446E+10 | 0.132316E+10 |
March | 0.176588E+10 | 0.992235E+09 | 0.773641E+09 | 0.179638E+10 | 0.110170E+10 |
April | 0.141525E+10 | 0.565538E+09 | 0.849711E+09 | 0.150391E+10 | 0.831862E+09 |
May | 0.127975E+10 | 0.371693E+09 | 0.908057E+09 | 0.147638E+10 | 0.579058E+09 |
June | 0.120339E+10 | 0.255005E+09 | 0.948387E+09 | 0.153165E+10 | 0.374457E+09 |
July | 0.126942E+10 | 0.308002E+09 | 0.961415E+09 | 0.177143E+10 | 0.274399E+09 |
August | 0.142513E+10 | 0.462063E+09 | 0.963067E+09 | 0.194655E+10 | 0.367653E+09 |
September | 0.160355E+10 | 0.781048E+09 | 0.822502E+09 | 0.201341E+10 | 0.573923E+09 |
October | 0.158550E+10 | 0.905671E+09 | 0.679834E+09 | 0.173095E+10 | 0.880775E+09 |
November | 0.109888E+10 | 0.620353E+09 | 0.478524E+09 | 0.105656E+10 | 0.105277E+10 |
December | 0.105959E+10 | 0.548385E+09 | 0.511204E+09 | 0.832361E+09 | 0.149745E+10 |
Annual Sum or Average | 0.162802E+11 | 0.717977E+10 | 0.910047E+10 | 0.178044E+11 | 0.103546E+11 |
Minimum of Months | 0.105959E+10 | 0.255005E+09 | 0.478524E+09 | 0.832361E+09 | 0.274399E+09 |
Maximum of Months | 0.176588E+10 | 0.992235E+09 | 0.963067E+09 | 0.201341E+10 | 0.149745E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.890207E+09 | 0.208985E+09 | 0.681222E+09 | 0.254328E+09 | 0.325239E+10 |
February | 0.130316E+10 | 0.334919E+09 | 0.968237E+09 | 0.581478E+09 | 0.276199E+10 |
March | 0.226130E+10 | 0.968232E+09 | 0.129307E+10 | 0.187623E+10 | 0.218573E+10 |
April | 0.267935E+10 | 0.109863E+10 | 0.158071E+10 | 0.259676E+10 | 0.156863E+10 |
May | 0.326607E+10 | 0.147605E+10 | 0.179003E+10 | 0.364886E+10 | 0.113333E+10 |
June | 0.381350E+10 | 0.179370E+10 | 0.201980E+10 | 0.474066E+10 | 0.761803E+09 |
July | 0.352306E+10 | 0.154462E+10 | 0.197844E+10 | 0.466592E+10 | 0.558370E+09 |
August | 0.318640E+10 | 0.135488E+10 | 0.183152E+10 | 0.413863E+10 | 0.722272E+09 |
September | 0.242159E+10 | 0.104578E+10 | 0.137582E+10 | 0.280919E+10 | 0.109369E+10 |
October | 0.162212E+10 | 0.571400E+09 | 0.105072E+10 | 0.142099E+10 | 0.172159E+10 |
November | 0.930264E+09 | 0.268068E+09 | 0.662197E+09 | 0.559012E+09 | 0.209478E+10 |
December | 0.833338E+09 | 0.181574E+09 | 0.651764E+09 | 0.241204E+09 | 0.318264E+10 |
Annual Sum or Average | 0.267304E+11 | 0.108468E+11 | 0.158835E+11 | 0.275333E+11 | 0.210372E+11 |
Minimum of Months | 0.833338E+09 | 0.181574E+09 | 0.651764E+09 | 0.241204E+09 | 0.558370E+09 |
Maximum of Months | 0.381350E+10 | 0.179370E+10 | 0.201980E+10 | 0.474066E+10 | 0.325239E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35197892.37 | 8263041.20 | 26934851.18 | 10055839.59 | 0.128597E+09 |
February | 51525504.54 | 13242363.98 | 38283140.56 | 22990989.91 | 0.109207E+09 |
March | 89409537.00 | 38282891.65 | 51126645.34 | 74184100.14 | 86421618.56 |
April | 0.105939E+09 | 43438881.87 | 62499741.07 | 0.102673E+09 | 62022178.27 |
May | 0.129137E+09 | 58361382.25 | 70775868.59 | 0.144272E+09 | 44810917.76 |
June | 0.150782E+09 | 70921213.46 | 79860709.65 | 0.187441E+09 | 30120985.44 |
July | 0.139298E+09 | 61072813.34 | 78225453.51 | 0.184486E+09 | 22077440.44 |
August | 0.125987E+09 | 53570612.27 | 72416404.57 | 0.163637E+09 | 28557957.38 |
September | 95747289.72 | 41348869.00 | 54398420.71 | 0.111072E+09 | 43243384.02 |
October | 64136911.94 | 22592577.70 | 41544334.24 | 56184596.46 | 68070164.05 |
November | 36781718.95 | 10599125.91 | 26182593.04 | 22102737.63 | 82825761.81 |
December | 32949350.07 | 7179259.31 | 25770090.76 | 9536937.08 | 0.125839E+09 |
Annual Sum or Average | 0.105689E+10 | 0.428873E+09 | 0.628018E+09 | 0.108864E+10 | 0.831792E+09 |
Minimum of Months | 32949350.07 | 7179259.31 | 25770090.76 | 9536937.08 | 22077440.44 |
Maximum of Months | 0.150782E+09 | 70921213.46 | 79860709.65 | 0.187441E+09 | 0.128597E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.884097E+09 | 0.00 | 0.884097E+09 | 8896369.57 | 0.542329E+10 |
February | 0.121667E+10 | 0.00 | 0.121667E+10 | 69966121.16 | 0.458444E+10 |
March | 0.163357E+10 | 0.00 | 0.163357E+10 | 0.524305E+09 | 0.368740E+10 |
April | 0.201436E+10 | 8038086.86 | 0.200632E+10 | 0.108390E+10 | 0.254261E+10 |
May | 0.241860E+10 | 0.102563E+09 | 0.231604E+10 | 0.187596E+10 | 0.171626E+10 |
June | 0.281523E+10 | 0.239647E+09 | 0.257558E+10 | 0.302258E+10 | 0.108402E+10 |
July | 0.269855E+10 | 0.174197E+09 | 0.252435E+10 | 0.336611E+10 | 0.786314E+09 |
August | 0.233500E+10 | 35521897.19 | 0.229947E+10 | 0.274519E+10 | 0.104625E+10 |
September | 0.171966E+10 | 357270.95 | 0.171930E+10 | 0.154001E+10 | 0.165430E+10 |
October | 0.132837E+10 | 0.00 | 0.132837E+10 | 0.635217E+09 | 0.265007E+10 |
November | 0.863837E+09 | 0.00 | 0.863837E+09 | 0.181183E+09 | 0.328385E+10 |
December | 0.827489E+09 | 0.00 | 0.827489E+09 | 11682969.55 | 0.517791E+10 |
Annual Sum or Average | 0.207554E+11 | 0.560324E+09 | 0.201951E+11 | 0.150650E+11 | 0.336367E+11 |
Minimum of Months | 0.827489E+09 | 0.00 | 0.827489E+09 | 8896369.57 | 0.786314E+09 |
Maximum of Months | 0.281523E+10 | 0.239647E+09 | 0.257558E+10 | 0.336611E+10 | 0.542329E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107859E+10 | 0.347796E+09 | 0.730792E+09 | 0.414947E+09 | 0.328378E+10 |
February | 0.142946E+10 | 0.428945E+09 | 0.100052E+10 | 0.673171E+09 | 0.280544E+10 |
March | 0.227101E+10 | 0.951083E+09 | 0.131993E+10 | 0.177848E+10 | 0.225747E+10 |
April | 0.290887E+10 | 0.128529E+10 | 0.162358E+10 | 0.273511E+10 | 0.160189E+10 |
May | 0.336761E+10 | 0.148967E+10 | 0.187794E+10 | 0.364581E+10 | 0.115403E+10 |
June | 0.363972E+10 | 0.160857E+10 | 0.203115E+10 | 0.441824E+10 | 0.731480E+09 |
July | 0.361159E+10 | 0.159013E+10 | 0.202146E+10 | 0.471975E+10 | 0.526525E+09 |
August | 0.326166E+10 | 0.136907E+10 | 0.189260E+10 | 0.416713E+10 | 0.690399E+09 |
September | 0.262671E+10 | 0.116511E+10 | 0.146161E+10 | 0.302253E+10 | 0.104836E+10 |
October | 0.184186E+10 | 0.761840E+09 | 0.108002E+10 | 0.164251E+10 | 0.166074E+10 |
November | 0.101103E+10 | 0.324327E+09 | 0.686706E+09 | 0.626340E+09 | 0.208401E+10 |
December | 0.841065E+09 | 0.173782E+09 | 0.667283E+09 | 0.214685E+09 | 0.323977E+10 |
Annual Sum or Average | 0.278892E+11 | 0.114956E+11 | 0.163936E+11 | 0.280587E+11 | 0.210839E+11 |
Minimum of Months | 0.841065E+09 | 0.173782E+09 | 0.667283E+09 | 0.214685E+09 | 0.526525E+09 |
Maximum of Months | 0.363972E+10 | 0.160857E+10 | 0.203115E+10 | 0.471975E+10 | 0.328378E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380157E+10 | 0.221909E+10 | 0.158248E+10 | 0.307088E+10 | 0.463479E+10 |
February | 0.392040E+10 | 0.189038E+10 | 0.203002E+10 | 0.311954E+10 | 0.410894E+10 |
March | 0.529780E+10 | 0.297679E+10 | 0.232100E+10 | 0.519509E+10 | 0.341423E+10 |
April | 0.424589E+10 | 0.169666E+10 | 0.254922E+10 | 0.434221E+10 | 0.263205E+10 |
May | 0.383938E+10 | 0.111511E+10 | 0.272427E+10 | 0.425502E+10 | 0.189254E+10 |
June | 0.361030E+10 | 0.765037E+09 | 0.284527E+10 | 0.448165E+10 | 0.119586E+10 |
July | 0.380838E+10 | 0.924034E+09 | 0.288435E+10 | 0.524477E+10 | 0.857494E+09 |
August | 0.427553E+10 | 0.138623E+10 | 0.288930E+10 | 0.578961E+10 | 0.111003E+10 |
September | 0.481081E+10 | 0.234322E+10 | 0.246759E+10 | 0.599652E+10 | 0.168914E+10 |
October | 0.475667E+10 | 0.271710E+10 | 0.203957E+10 | 0.512721E+10 | 0.256795E+10 |
November | 0.329673E+10 | 0.186112E+10 | 0.143562E+10 | 0.312175E+10 | 0.310971E+10 |
December | 0.317887E+10 | 0.164521E+10 | 0.153366E+10 | 0.242871E+10 | 0.456951E+10 |
Annual Sum or Average | 0.488423E+11 | 0.215400E+11 | 0.273024E+11 | 0.521730E+11 | 0.317822E+11 |
Minimum of Months | 0.317887E+10 | 0.765037E+09 | 0.143562E+10 | 0.242871E+10 | 0.857494E+09 |
Maximum of Months | 0.529780E+10 | 0.297679E+10 | 0.288930E+10 | 0.599652E+10 | 0.463479E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.925412E+09 | 0.217250E+09 | 0.708162E+09 | 0.256292E+09 | 0.341159E+10 |
February | 0.135469E+10 | 0.348165E+09 | 0.100653E+10 | 0.583494E+09 | 0.289980E+10 |
March | 0.235073E+10 | 0.100652E+10 | 0.134420E+10 | 0.188816E+10 | 0.232456E+10 |
April | 0.278531E+10 | 0.114208E+10 | 0.164322E+10 | 0.262720E+10 | 0.168379E+10 |
May | 0.339524E+10 | 0.153442E+10 | 0.186081E+10 | 0.371712E+10 | 0.123075E+10 |
June | 0.396431E+10 | 0.186464E+10 | 0.209967E+10 | 0.488120E+10 | 0.803268E+09 |
July | 0.366239E+10 | 0.160571E+10 | 0.205667E+10 | 0.481528E+10 | 0.586569E+09 |
August | 0.331241E+10 | 0.140847E+10 | 0.190395E+10 | 0.428174E+10 | 0.742223E+09 |
September | 0.251736E+10 | 0.108713E+10 | 0.143022E+10 | 0.290988E+10 | 0.110975E+10 |
October | 0.168627E+10 | 0.593999E+09 | 0.109227E+10 | 0.147968E+10 | 0.172533E+10 |
November | 0.967054E+09 | 0.278670E+09 | 0.688384E+09 | 0.580431E+09 | 0.212737E+10 |
December | 0.866294E+09 | 0.188755E+09 | 0.677539E+09 | 0.246323E+09 | 0.329058E+10 |
Annual Sum or Average | 0.277875E+11 | 0.112758E+11 | 0.165116E+11 | 0.282668E+11 | 0.219356E+11 |
Minimum of Months | 0.866294E+09 | 0.188755E+09 | 0.677539E+09 | 0.246323E+09 | 0.586569E+09 |
Maximum of Months | 0.396431E+10 | 0.186464E+10 | 0.209967E+10 | 0.488120E+10 | 0.341159E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.49 | 1960.14 | 330.08 | 0.00 | 330.08 | 0.00 | 0.00 |
February | 34.01 | 1830.62 | 502.92 | 0.00 | 502.92 | 0.00 | 0.00 |
March | 205.08 | 1306.31 | 609.91 | 0.00 | 609.91 | 0.00 | 0.00 |
April | 435.61 | 919.41 | 777.14 | 3.10 | 774.04 | 0.00 | 0.00 |
May | 713.91 | 606.06 | 903.00 | 38.29 | 864.71 | 0.00 | 0.00 |
June | 1167.78 | 403.67 | 1086.12 | 92.46 | 993.67 | 0.00 | 0.00 |
July | 1253.01 | 286.22 | 1007.52 | 65.04 | 942.49 | 0.00 | 0.00 |
August | 1025.70 | 375.79 | 871.79 | 13.26 | 858.53 | 0.00 | 0.00 |
September | 604.14 | 597.60 | 663.45 | 0.14 | 663.31 | 0.00 | 0.00 |
October | 257.88 | 907.43 | 495.96 | 0.00 | 495.96 | 0.00 | 0.00 |
November | 81.03 | 1173.99 | 333.27 | 0.00 | 333.27 | 0.00 | 0.00 |
December | 6.33 | 1853.49 | 308.95 | 0.00 | 308.95 | 0.00 | 0.00 |
Annual Sum or Average | 485.20 | 1014.40 | 658.15 | 17.77 | 640.38 | 0.00 | 0.00 |
Minimum of Months | 5.49 | 286.22 | 308.95 | 0.00 | 308.95 | 0.00 | 0.00 |
Maximum of Months | 1253.01 | 1960.14 | 1086.12 | 92.46 | 993.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 159.21 | 1185.88 | 402.70 | 129.85 | 272.85 | 0.00 | 0.00 |
February | 285.51 | 1120.98 | 590.88 | 177.31 | 413.57 | 0.00 | 0.00 |
March | 674.11 | 799.74 | 847.90 | 355.09 | 492.81 | 0.00 | 0.00 |
April | 1067.34 | 582.81 | 1122.25 | 495.87 | 626.38 | 0.00 | 0.00 |
May | 1367.07 | 410.09 | 1257.32 | 556.18 | 701.14 | 0.00 | 0.00 |
June | 1703.54 | 273.09 | 1404.21 | 620.59 | 783.62 | 0.00 | 0.00 |
July | 1758.26 | 192.02 | 1348.41 | 593.69 | 754.73 | 0.00 | 0.00 |
August | 1554.74 | 248.69 | 1217.77 | 511.15 | 706.62 | 0.00 | 0.00 |
September | 1171.94 | 381.72 | 1013.39 | 449.50 | 563.89 | 0.00 | 0.00 |
October | 629.07 | 572.30 | 687.67 | 284.44 | 403.23 | 0.00 | 0.00 |
November | 252.14 | 747.07 | 390.06 | 125.13 | 264.93 | 0.00 | 0.00 |
December | 83.89 | 1160.37 | 314.02 | 64.88 | 249.13 | 0.00 | 0.00 |
Annual Sum or Average | 895.51 | 637.18 | 884.36 | 364.52 | 519.84 | 0.00 | 0.00 |
Minimum of Months | 83.89 | 192.02 | 314.02 | 64.88 | 249.13 | 0.00 | 0.00 |
Maximum of Months | 1758.26 | 1185.88 | 1404.21 | 620.59 | 783.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1157.83 | 1667.62 | 1419.34 | 828.51 | 590.83 | 0.00 | 0.00 |
February | 1302.36 | 1636.86 | 1620.54 | 781.41 | 839.13 | 0.00 | 0.00 |
March | 1955.18 | 1205.89 | 1977.97 | 1111.41 | 866.56 | 0.00 | 0.00 |
April | 1690.96 | 954.80 | 1638.07 | 654.58 | 983.50 | 0.00 | 0.00 |
May | 1596.42 | 668.03 | 1433.46 | 416.34 | 1017.13 | 0.00 | 0.00 |
June | 1727.59 | 442.76 | 1392.86 | 295.15 | 1097.71 | 0.00 | 0.00 |
July | 1952.60 | 310.46 | 1421.89 | 344.99 | 1076.89 | 0.00 | 0.00 |
August | 2159.46 | 397.85 | 1596.30 | 517.56 | 1078.74 | 0.00 | 0.00 |
September | 2319.82 | 613.35 | 1856.02 | 904.02 | 952.00 | 0.00 | 0.00 |
October | 1937.15 | 883.45 | 1775.94 | 1014.45 | 761.49 | 0.00 | 0.00 |
November | 1224.19 | 1112.53 | 1271.89 | 718.02 | 553.87 | 0.00 | 0.00 |
December | 919.03 | 1632.33 | 1186.85 | 614.25 | 572.60 | 0.00 | 0.00 |
Annual Sum or Average | 1663.97 | 956.90 | 1548.78 | 683.03 | 865.75 | 0.00 | 0.00 |
Minimum of Months | 919.03 | 310.46 | 1186.85 | 295.15 | 553.87 | 0.00 | 0.00 |
Maximum of Months | 2319.82 | 1667.62 | 1977.97 | 1111.41 | 1097.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 98.29 | 1233.23 | 345.51 | 81.11 | 264.40 | 0.00 | 0.00 |
February | 245.38 | 1158.86 | 559.98 | 143.92 | 416.06 | 0.00 | 0.00 |
March | 712.57 | 822.24 | 877.66 | 375.79 | 501.87 | 0.00 | 0.00 |
April | 1023.66 | 610.37 | 1074.58 | 440.62 | 633.96 | 0.00 | 0.00 |
May | 1394.22 | 434.51 | 1267.64 | 572.89 | 694.75 | 0.00 | 0.00 |
June | 1881.91 | 297.90 | 1529.44 | 719.38 | 810.06 | 0.00 | 0.00 |
July | 1794.09 | 212.53 | 1367.38 | 599.50 | 767.87 | 0.00 | 0.00 |
August | 1598.21 | 266.23 | 1236.71 | 525.86 | 710.85 | 0.00 | 0.00 |
September | 1129.31 | 401.59 | 971.20 | 419.42 | 551.78 | 0.00 | 0.00 |
October | 566.32 | 592.88 | 629.58 | 221.77 | 407.81 | 0.00 | 0.00 |
November | 232.97 | 762.22 | 373.09 | 107.51 | 265.58 | 0.00 | 0.00 |
December | 95.09 | 1179.22 | 323.44 | 70.47 | 252.96 | 0.00 | 0.00 |
Annual Sum or Average | 901.17 | 661.85 | 881.13 | 357.55 | 523.58 | 0.00 | 0.00 |
Minimum of Months | 95.09 | 212.53 | 323.44 | 70.47 | 252.96 | 0.00 | 0.00 |
Maximum of Months | 1881.91 | 1233.23 | 1529.44 | 719.38 | 810.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.10 | 2005.03 | 330.08 | 0.00 | 330.08 | 0.00 | 0.00 |
February | 31.65 | 1872.00 | 502.92 | 0.00 | 502.92 | 0.00 | 0.00 |
March | 216.80 | 1328.32 | 609.90 | 0.00 | 609.90 | 0.00 | 0.00 |
April | 460.22 | 924.25 | 777.14 | 3.10 | 774.04 | 0.00 | 0.00 |
May | 758.35 | 586.15 | 903.00 | 38.29 | 864.71 | 0.00 | 0.00 |
June | 1201.29 | 393.02 | 1086.12 | 92.46 | 993.66 | 0.00 | 0.00 |
July | 1281.89 | 276.22 | 1007.52 | 65.04 | 942.48 | 0.00 | 0.00 |
August | 1039.82 | 378.60 | 871.78 | 13.26 | 858.52 | 0.00 | 0.00 |
September | 603.26 | 634.11 | 663.45 | 0.14 | 663.31 | 0.00 | 0.00 |
October | 237.04 | 1011.42 | 495.95 | 0.00 | 495.95 | 0.00 | 0.00 |
November | 69.47 | 1289.66 | 333.27 | 0.00 | 333.27 | 0.00 | 0.00 |
December | 4.29 | 1944.44 | 308.95 | 0.00 | 308.95 | 0.00 | 0.00 |
Annual Sum or Average | 495.05 | 1049.54 | 658.15 | 17.77 | 640.38 | 0.00 | 0.00 |
Minimum of Months | 3.10 | 276.22 | 308.95 | 0.00 | 308.95 | 0.00 | 0.00 |
Maximum of Months | 1281.89 | 2005.03 | 1086.12 | 92.46 | 993.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 158.27 | 1218.85 | 402.70 | 129.85 | 272.84 | 0.00 | 0.00 |
February | 285.69 | 1150.52 | 590.88 | 177.31 | 413.57 | 0.00 | 0.00 |
March | 684.53 | 823.55 | 847.89 | 355.09 | 492.80 | 0.00 | 0.00 |
April | 1080.29 | 602.27 | 1122.24 | 495.86 | 626.38 | 0.00 | 0.00 |
May | 1388.00 | 412.83 | 1257.31 | 556.17 | 701.14 | 0.00 | 0.00 |
June | 1721.97 | 276.59 | 1404.20 | 620.59 | 783.62 | 0.00 | 0.00 |
July | 1774.81 | 193.93 | 1348.40 | 593.68 | 754.72 | 0.00 | 0.00 |
August | 1563.98 | 259.65 | 1217.76 | 511.15 | 706.61 | 0.00 | 0.00 |
September | 1170.20 | 416.00 | 1013.38 | 449.50 | 563.89 | 0.00 | 0.00 |
October | 610.41 | 648.50 | 687.67 | 284.44 | 403.23 | 0.00 | 0.00 |
November | 240.78 | 825.76 | 390.06 | 125.12 | 264.93 | 0.00 | 0.00 |
December | 81.08 | 1217.81 | 314.02 | 64.88 | 249.13 | 0.00 | 0.00 |
Annual Sum or Average | 899.97 | 668.11 | 884.35 | 364.52 | 519.83 | 0.00 | 0.00 |
Minimum of Months | 81.08 | 193.93 | 314.02 | 64.88 | 249.13 | 0.00 | 0.00 |
Maximum of Months | 1774.81 | 1218.85 | 1404.20 | 620.59 | 783.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1187.76 | 1677.25 | 1419.36 | 828.52 | 590.84 | 0.00 | 0.00 |
February | 1344.87 | 1640.89 | 1620.55 | 781.42 | 839.14 | 0.00 | 0.00 |
March | 2012.16 | 1234.04 | 1977.99 | 1111.42 | 866.57 | 0.00 | 0.00 |
April | 1740.71 | 962.84 | 1638.09 | 654.58 | 983.50 | 0.00 | 0.00 |
May | 1653.72 | 648.61 | 1433.47 | 416.34 | 1017.13 | 0.00 | 0.00 |
June | 1772.82 | 433.42 | 1392.87 | 295.16 | 1097.72 | 0.00 | 0.00 |
July | 1984.22 | 307.36 | 1421.90 | 345.00 | 1076.90 | 0.00 | 0.00 |
August | 2180.36 | 411.81 | 1596.31 | 517.57 | 1078.75 | 0.00 | 0.00 |
September | 2330.44 | 664.29 | 1856.04 | 904.03 | 952.01 | 0.00 | 0.00 |
October | 1938.87 | 986.57 | 1775.95 | 1014.46 | 761.49 | 0.00 | 0.00 |
November | 1222.92 | 1218.54 | 1271.90 | 718.03 | 553.87 | 0.00 | 0.00 |
December | 932.34 | 1677.32 | 1186.87 | 614.26 | 572.61 | 0.00 | 0.00 |
Annual Sum or Average | 1693.80 | 985.07 | 1548.79 | 683.04 | 865.76 | 0.00 | 0.00 |
Minimum of Months | 932.34 | 307.36 | 1186.87 | 295.16 | 553.87 | 0.00 | 0.00 |
Maximum of Months | 2330.44 | 1677.32 | 1977.99 | 1111.42 | 1097.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 98.71 | 1262.31 | 345.51 | 81.11 | 264.40 | 0.00 | 0.00 |
February | 249.86 | 1186.84 | 559.97 | 143.92 | 416.06 | 0.00 | 0.00 |
March | 728.20 | 848.32 | 877.65 | 375.79 | 501.86 | 0.00 | 0.00 |
April | 1041.45 | 629.11 | 1074.57 | 440.61 | 633.95 | 0.00 | 0.00 |
May | 1416.20 | 439.87 | 1267.63 | 572.88 | 694.74 | 0.00 | 0.00 |
June | 1901.28 | 305.53 | 1529.43 | 719.38 | 810.05 | 0.00 | 0.00 |
July | 1810.93 | 216.71 | 1367.37 | 599.50 | 767.87 | 0.00 | 0.00 |
August | 1606.28 | 280.33 | 1236.70 | 525.86 | 710.85 | 0.00 | 0.00 |
September | 1126.64 | 438.63 | 971.20 | 419.42 | 551.78 | 0.00 | 0.00 |
October | 551.52 | 668.18 | 629.58 | 221.77 | 407.80 | 0.00 | 0.00 |
November | 224.20 | 840.13 | 373.09 | 107.51 | 265.58 | 0.00 | 0.00 |
December | 93.62 | 1235.24 | 323.43 | 70.47 | 252.96 | 0.00 | 0.00 |
Annual Sum or Average | 907.59 | 693.46 | 881.13 | 357.55 | 523.58 | 0.00 | 0.00 |
Minimum of Months | 93.62 | 216.71 | 323.43 | 70.47 | 252.96 | 0.00 | 0.00 |
Maximum of Months | 1901.28 | 1262.31 | 1529.43 | 719.38 | 810.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.32 | 2024.82 | 330.08 | 0.00 | 330.08 | 0.00 | 0.00 |
February | 28.92 | 1895.02 | 502.92 | 0.00 | 502.92 | 0.00 | 0.00 |
March | 195.75 | 1376.72 | 609.91 | 0.00 | 609.91 | 0.00 | 0.00 |
April | 418.17 | 980.95 | 777.14 | 3.10 | 774.04 | 0.00 | 0.00 |
May | 700.40 | 640.78 | 903.00 | 38.29 | 864.71 | 0.00 | 0.00 |
June | 1166.12 | 418.22 | 1086.12 | 92.46 | 993.67 | 0.00 | 0.00 |
July | 1256.76 | 293.58 | 1007.52 | 65.04 | 942.49 | 0.00 | 0.00 |
August | 1024.94 | 390.62 | 871.79 | 13.26 | 858.53 | 0.00 | 0.00 |
September | 594.14 | 638.23 | 663.45 | 0.14 | 663.31 | 0.00 | 0.00 |
October | 237.16 | 989.42 | 495.96 | 0.00 | 495.96 | 0.00 | 0.00 |
November | 69.90 | 1266.92 | 333.27 | 0.00 | 333.27 | 0.00 | 0.00 |
December | 4.36 | 1933.21 | 308.95 | 0.00 | 308.95 | 0.00 | 0.00 |
Annual Sum or Average | 477.71 | 1066.61 | 658.15 | 17.77 | 640.38 | 0.00 | 0.00 |
Minimum of Months | 3.32 | 293.58 | 308.95 | 0.00 | 308.95 | 0.00 | 0.00 |
Maximum of Months | 1256.76 | 2024.82 | 1086.12 | 92.46 | 993.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 154.92 | 1226.02 | 402.70 | 129.85 | 272.85 | 0.00 | 0.00 |
February | 278.26 | 1159.66 | 590.88 | 177.31 | 413.57 | 0.00 | 0.00 |
March | 664.01 | 842.84 | 847.90 | 355.09 | 492.81 | 0.00 | 0.00 |
April | 1055.21 | 618.01 | 1122.25 | 495.87 | 626.38 | 0.00 | 0.00 |
May | 1361.19 | 430.87 | 1257.32 | 556.18 | 701.14 | 0.00 | 0.00 |
June | 1704.57 | 282.21 | 1404.21 | 620.59 | 783.62 | 0.00 | 0.00 |
July | 1762.15 | 196.58 | 1348.41 | 593.69 | 754.73 | 0.00 | 0.00 |
August | 1555.83 | 257.77 | 1217.77 | 511.15 | 706.62 | 0.00 | 0.00 |
September | 1166.10 | 404.46 | 1013.39 | 449.50 | 563.89 | 0.00 | 0.00 |
October | 613.24 | 620.05 | 687.67 | 284.44 | 403.23 | 0.00 | 0.00 |
November | 241.64 | 804.01 | 390.06 | 125.13 | 264.93 | 0.00 | 0.00 |
December | 80.15 | 1209.59 | 314.02 | 64.88 | 249.13 | 0.00 | 0.00 |
Annual Sum or Average | 889.74 | 668.57 | 884.36 | 364.52 | 519.84 | 0.00 | 0.00 |
Minimum of Months | 80.15 | 196.58 | 314.02 | 64.88 | 249.13 | 0.00 | 0.00 |
Maximum of Months | 1762.15 | 1226.02 | 1404.21 | 620.59 | 783.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1146.54 | 1730.43 | 1419.34 | 828.51 | 590.83 | 0.00 | 0.00 |
February | 1289.49 | 1698.47 | 1620.54 | 781.41 | 839.13 | 0.00 | 0.00 |
March | 1939.62 | 1274.73 | 1977.97 | 1111.41 | 866.56 | 0.00 | 0.00 |
April | 1675.23 | 1015.45 | 1638.07 | 654.58 | 983.50 | 0.00 | 0.00 |
May | 1588.64 | 706.59 | 1433.46 | 416.34 | 1017.13 | 0.00 | 0.00 |
June | 1729.03 | 461.37 | 1392.86 | 295.15 | 1097.71 | 0.00 | 0.00 |
July | 1958.17 | 320.15 | 1421.89 | 344.99 | 1076.89 | 0.00 | 0.00 |
August | 2161.59 | 414.44 | 1596.30 | 517.56 | 1078.74 | 0.00 | 0.00 |
September | 2313.47 | 651.67 | 1856.02 | 904.02 | 952.00 | 0.00 | 0.00 |
October | 1914.28 | 958.76 | 1775.94 | 1014.45 | 761.49 | 0.00 | 0.00 |
November | 1204.38 | 1199.73 | 1271.89 | 718.02 | 553.87 | 0.00 | 0.00 |
December | 906.78 | 1706.06 | 1186.85 | 614.25 | 572.60 | 0.00 | 0.00 |
Annual Sum or Average | 1654.39 | 1007.81 | 1548.78 | 683.03 | 865.75 | 0.00 | 0.00 |
Minimum of Months | 906.78 | 320.15 | 1186.85 | 295.15 | 553.87 | 0.00 | 0.00 |
Maximum of Months | 2313.47 | 1730.43 | 1977.97 | 1111.41 | 1097.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 95.69 | 1273.74 | 345.51 | 81.11 | 264.40 | 0.00 | 0.00 |
February | 241.19 | 1198.66 | 559.98 | 143.92 | 416.06 | 0.00 | 0.00 |
March | 704.96 | 867.89 | 877.66 | 375.79 | 501.87 | 0.00 | 0.00 |
April | 1013.58 | 649.61 | 1074.58 | 440.62 | 633.96 | 0.00 | 0.00 |
May | 1387.81 | 459.51 | 1267.64 | 572.89 | 694.75 | 0.00 | 0.00 |
June | 1883.18 | 309.90 | 1529.44 | 719.38 | 810.06 | 0.00 | 0.00 |
July | 1797.82 | 219.00 | 1367.38 | 599.50 | 767.87 | 0.00 | 0.00 |
August | 1598.62 | 277.11 | 1236.71 | 525.86 | 710.85 | 0.00 | 0.00 |
September | 1122.64 | 428.14 | 971.20 | 419.42 | 551.78 | 0.00 | 0.00 |
October | 552.45 | 644.17 | 629.58 | 221.77 | 407.81 | 0.00 | 0.00 |
November | 223.93 | 820.75 | 373.09 | 107.51 | 265.58 | 0.00 | 0.00 |
December | 91.97 | 1228.56 | 323.44 | 70.47 | 252.96 | 0.00 | 0.00 |
Annual Sum or Average | 896.33 | 695.57 | 881.13 | 357.55 | 523.58 | 0.00 | 0.00 |
Minimum of Months | 91.97 | 219.00 | 323.44 | 70.47 | 252.96 | 0.00 | 0.00 |
Maximum of Months | 1883.18 | 1273.74 | 1529.44 | 719.38 | 810.06 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 14701898.09 | 0.525003E+10 | 0.884097E+09 | 0.00 | 0.884097E+09 | 0.00 | 0.00 |
February | 82280480.17 | 0.442864E+10 | 0.121667E+10 | 0.00 | 0.121667E+10 | 0.00 | 0.00 |
March | 0.549278E+09 | 0.349881E+10 | 0.163357E+10 | 0.00 | 0.163357E+10 | 0.00 | 0.00 |
April | 0.112911E+10 | 0.238310E+10 | 0.201436E+10 | 8038086.86 | 0.200632E+10 | 0.00 | 0.00 |
May | 0.191214E+10 | 0.162326E+10 | 0.241860E+10 | 0.102563E+09 | 0.231604E+10 | 0.00 | 0.00 |
June | 0.302689E+10 | 0.104632E+10 | 0.281523E+10 | 0.239647E+09 | 0.257558E+10 | 0.00 | 0.00 |
July | 0.335607E+10 | 0.766603E+09 | 0.269855E+10 | 0.174197E+09 | 0.252435E+10 | 0.00 | 0.00 |
August | 0.274723E+10 | 0.100651E+10 | 0.233500E+10 | 35521897.19 | 0.229947E+10 | 0.00 | 0.00 |
September | 0.156593E+10 | 0.154898E+10 | 0.171966E+10 | 357270.95 | 0.171930E+10 | 0.00 | 0.00 |
October | 0.690694E+09 | 0.243046E+10 | 0.132837E+10 | 0.00 | 0.132837E+10 | 0.00 | 0.00 |
November | 0.210027E+09 | 0.304298E+10 | 0.863837E+09 | 0.00 | 0.863837E+09 | 0.00 | 0.00 |
December | 16948774.62 | 0.496439E+10 | 0.827489E+09 | 0.00 | 0.827489E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.153013E+11 | 0.319901E+11 | 0.207554E+11 | 0.560324E+09 | 0.201951E+11 | 0.00 | 0.00 |
Minimum of Months | 14701898.09 | 0.766603E+09 | 0.827489E+09 | 0.00 | 0.827489E+09 | 0.00 | 0.00 |
Maximum of Months | 0.335607E+10 | 0.525003E+10 | 0.281523E+10 | 0.239647E+09 | 0.257558E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.426430E+09 | 0.317626E+10 | 0.107859E+10 | 0.347796E+09 | 0.730792E+09 | 0.00 | 0.00 |
February | 0.690697E+09 | 0.271187E+10 | 0.142946E+10 | 0.428945E+09 | 0.100052E+10 | 0.00 | 0.00 |
March | 0.180553E+10 | 0.214203E+10 | 0.227101E+10 | 0.951083E+09 | 0.131993E+10 | 0.00 | 0.00 |
April | 0.276656E+10 | 0.151064E+10 | 0.290887E+10 | 0.128529E+10 | 0.162358E+10 | 0.00 | 0.00 |
May | 0.366155E+10 | 0.109839E+10 | 0.336761E+10 | 0.148967E+10 | 0.187794E+10 | 0.00 | 0.00 |
June | 0.441557E+10 | 0.707842E+09 | 0.363972E+10 | 0.160857E+10 | 0.203115E+10 | 0.00 | 0.00 |
July | 0.470932E+10 | 0.514303E+09 | 0.361159E+10 | 0.159013E+10 | 0.202146E+10 | 0.00 | 0.00 |
August | 0.416422E+10 | 0.666085E+09 | 0.326166E+10 | 0.136907E+10 | 0.189260E+10 | 0.00 | 0.00 |
September | 0.303767E+10 | 0.989427E+09 | 0.262671E+10 | 0.116511E+10 | 0.146161E+10 | 0.00 | 0.00 |
October | 0.168491E+10 | 0.153285E+10 | 0.184186E+10 | 0.761840E+09 | 0.108002E+10 | 0.00 | 0.00 |
November | 0.653559E+09 | 0.193640E+10 | 0.101103E+10 | 0.324327E+09 | 0.686706E+09 | 0.00 | 0.00 |
December | 0.224703E+09 | 0.310793E+10 | 0.841065E+09 | 0.173782E+09 | 0.667283E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.282407E+11 | 0.200940E+11 | 0.278892E+11 | 0.114956E+11 | 0.163936E+11 | 0.00 | 0.00 |
Minimum of Months | 0.224703E+09 | 0.514303E+09 | 0.841065E+09 | 0.173782E+09 | 0.667283E+09 | 0.00 | 0.00 |
Maximum of Months | 0.470932E+10 | 0.317626E+10 | 0.363972E+10 | 0.160857E+10 | 0.203115E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.310114E+10 | 0.446656E+10 | 0.380157E+10 | 0.221909E+10 | 0.158248E+10 | 0.00 | 0.00 |
February | 0.315066E+10 | 0.395990E+10 | 0.392040E+10 | 0.189038E+10 | 0.203002E+10 | 0.00 | 0.00 |
March | 0.523675E+10 | 0.322985E+10 | 0.529780E+10 | 0.297679E+10 | 0.232100E+10 | 0.00 | 0.00 |
April | 0.438297E+10 | 0.247484E+10 | 0.424589E+10 | 0.169666E+10 | 0.254922E+10 | 0.00 | 0.00 |
May | 0.427585E+10 | 0.178926E+10 | 0.383938E+10 | 0.111511E+10 | 0.272427E+10 | 0.00 | 0.00 |
June | 0.447792E+10 | 0.114764E+10 | 0.361030E+10 | 0.765037E+09 | 0.284527E+10 | 0.00 | 0.00 |
July | 0.522984E+10 | 0.831531E+09 | 0.380838E+10 | 0.924034E+09 | 0.288435E+10 | 0.00 | 0.00 |
August | 0.578389E+10 | 0.106560E+10 | 0.427553E+10 | 0.138623E+10 | 0.288930E+10 | 0.00 | 0.00 |
September | 0.601297E+10 | 0.158981E+10 | 0.481081E+10 | 0.234322E+10 | 0.246759E+10 | 0.00 | 0.00 |
October | 0.518847E+10 | 0.236624E+10 | 0.475667E+10 | 0.271710E+10 | 0.203957E+10 | 0.00 | 0.00 |
November | 0.317309E+10 | 0.288367E+10 | 0.329673E+10 | 0.186112E+10 | 0.143562E+10 | 0.00 | 0.00 |
December | 0.246152E+10 | 0.437204E+10 | 0.317887E+10 | 0.164521E+10 | 0.153366E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.524751E+11 | 0.301769E+11 | 0.488423E+11 | 0.215400E+11 | 0.273024E+11 | 0.00 | 0.00 |
Minimum of Months | 0.246152E+10 | 0.831531E+09 | 0.317887E+10 | 0.765037E+09 | 0.143562E+10 | 0.00 | 0.00 |
Maximum of Months | 0.601297E+10 | 0.446656E+10 | 0.529780E+10 | 0.297679E+10 | 0.288930E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.263257E+09 | 0.330308E+10 | 0.925412E+09 | 0.217250E+09 | 0.708162E+09 | 0.00 | 0.00 |
February | 0.593627E+09 | 0.280352E+10 | 0.135469E+10 | 0.348165E+09 | 0.100653E+10 | 0.00 | 0.00 |
March | 0.190856E+10 | 0.220227E+10 | 0.235073E+10 | 0.100652E+10 | 0.134420E+10 | 0.00 | 0.00 |
April | 0.265334E+10 | 0.158209E+10 | 0.278531E+10 | 0.114208E+10 | 0.164322E+10 | 0.00 | 0.00 |
May | 0.373427E+10 | 0.116380E+10 | 0.339524E+10 | 0.153442E+10 | 0.186081E+10 | 0.00 | 0.00 |
June | 0.487790E+10 | 0.772167E+09 | 0.396431E+10 | 0.186464E+10 | 0.209967E+10 | 0.00 | 0.00 |
July | 0.480528E+10 | 0.569233E+09 | 0.366239E+10 | 0.160571E+10 | 0.205667E+10 | 0.00 | 0.00 |
August | 0.428065E+10 | 0.713059E+09 | 0.331241E+10 | 0.140847E+10 | 0.190395E+10 | 0.00 | 0.00 |
September | 0.292718E+10 | 0.104092E+10 | 0.251736E+10 | 0.108713E+10 | 0.143022E+10 | 0.00 | 0.00 |
October | 0.151682E+10 | 0.158796E+10 | 0.168627E+10 | 0.593999E+09 | 0.109227E+10 | 0.00 | 0.00 |
November | 0.603863E+09 | 0.197568E+10 | 0.967054E+09 | 0.278670E+09 | 0.688384E+09 | 0.00 | 0.00 |
December | 0.254688E+09 | 0.315843E+10 | 0.866294E+09 | 0.188755E+09 | 0.677539E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.284194E+11 | 0.208722E+11 | 0.277875E+11 | 0.112758E+11 | 0.165116E+11 | 0.00 | 0.00 |
Minimum of Months | 0.254688E+09 | 0.569233E+09 | 0.866294E+09 | 0.188755E+09 | 0.677539E+09 | 0.00 | 0.00 |
Maximum of Months | 0.487790E+10 | 0.330308E+10 | 0.396431E+10 | 0.186464E+10 | 0.209967E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 8298746.32 | 0.537027E+10 | 0.884093E+09 | 0.00 | 0.884093E+09 | 0.00 | 0.00 |
February | 76571833.53 | 0.452875E+10 | 0.121667E+10 | 0.00 | 0.121667E+10 | 0.00 | 0.00 |
March | 0.580674E+09 | 0.355776E+10 | 0.163356E+10 | 0.00 | 0.163356E+10 | 0.00 | 0.00 |
April | 0.119289E+10 | 0.239565E+10 | 0.201435E+10 | 8038045.20 | 0.200631E+10 | 0.00 | 0.00 |
May | 0.203117E+10 | 0.156993E+10 | 0.241859E+10 | 0.102562E+09 | 0.231603E+10 | 0.00 | 0.00 |
June | 0.311376E+10 | 0.101871E+10 | 0.281522E+10 | 0.239646E+09 | 0.257557E+10 | 0.00 | 0.00 |
July | 0.343341E+10 | 0.739834E+09 | 0.269854E+10 | 0.174197E+09 | 0.252434E+10 | 0.00 | 0.00 |
August | 0.278506E+10 | 0.101404E+10 | 0.233498E+10 | 35521713.12 | 0.229946E+10 | 0.00 | 0.00 |
September | 0.156366E+10 | 0.164361E+10 | 0.171965E+10 | 357269.10 | 0.171929E+10 | 0.00 | 0.00 |
October | 0.634876E+09 | 0.270898E+10 | 0.132836E+10 | 0.00 | 0.132836E+10 | 0.00 | 0.00 |
November | 0.180065E+09 | 0.334279E+10 | 0.863833E+09 | 0.00 | 0.863833E+09 | 0.00 | 0.00 |
December | 11494977.35 | 0.520798E+10 | 0.827484E+09 | 0.00 | 0.827484E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.156119E+11 | 0.330983E+11 | 0.207553E+11 | 0.560321E+09 | 0.201950E+11 | 0.00 | 0.00 |
Minimum of Months | 8298746.32 | 0.739834E+09 | 0.827484E+09 | 0.00 | 0.827484E+09 | 0.00 | 0.00 |
Maximum of Months | 0.343341E+10 | 0.537027E+10 | 0.281522E+10 | 0.239646E+09 | 0.257557E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.423903E+09 | 0.326457E+10 | 0.107858E+10 | 0.347793E+09 | 0.730787E+09 | 0.00 | 0.00 |
February | 0.691136E+09 | 0.278333E+10 | 0.142945E+10 | 0.428940E+09 | 0.100051E+10 | 0.00 | 0.00 |
March | 0.183345E+10 | 0.220579E+10 | 0.227099E+10 | 0.951074E+09 | 0.131992E+10 | 0.00 | 0.00 |
April | 0.280011E+10 | 0.156109E+10 | 0.290884E+10 | 0.128528E+10 | 0.162357E+10 | 0.00 | 0.00 |
May | 0.371761E+10 | 0.110573E+10 | 0.336758E+10 | 0.148965E+10 | 0.187793E+10 | 0.00 | 0.00 |
June | 0.446335E+10 | 0.716913E+09 | 0.363970E+10 | 0.160856E+10 | 0.203114E+10 | 0.00 | 0.00 |
July | 0.475365E+10 | 0.519417E+09 | 0.361157E+10 | 0.159011E+10 | 0.202145E+10 | 0.00 | 0.00 |
August | 0.418898E+10 | 0.695459E+09 | 0.326164E+10 | 0.136905E+10 | 0.189259E+10 | 0.00 | 0.00 |
September | 0.303316E+10 | 0.107828E+10 | 0.262669E+10 | 0.116509E+10 | 0.146160E+10 | 0.00 | 0.00 |
October | 0.163493E+10 | 0.173694E+10 | 0.184184E+10 | 0.761832E+09 | 0.108001E+10 | 0.00 | 0.00 |
November | 0.624113E+09 | 0.214036E+10 | 0.101103E+10 | 0.324324E+09 | 0.686702E+09 | 0.00 | 0.00 |
December | 0.217155E+09 | 0.326177E+10 | 0.841058E+09 | 0.173780E+09 | 0.667278E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.283815E+11 | 0.210697E+11 | 0.278890E+11 | 0.114955E+11 | 0.163935E+11 | 0.00 | 0.00 |
Minimum of Months | 0.217155E+09 | 0.519417E+09 | 0.841058E+09 | 0.173780E+09 | 0.667278E+09 | 0.00 | 0.00 |
Maximum of Months | 0.475365E+10 | 0.326457E+10 | 0.363970E+10 | 0.160856E+10 | 0.203114E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.318130E+10 | 0.449233E+10 | 0.380161E+10 | 0.221911E+10 | 0.158250E+10 | 0.00 | 0.00 |
February | 0.325351E+10 | 0.396963E+10 | 0.392044E+10 | 0.189040E+10 | 0.203004E+10 | 0.00 | 0.00 |
March | 0.538936E+10 | 0.330524E+10 | 0.529785E+10 | 0.297683E+10 | 0.232102E+10 | 0.00 | 0.00 |
April | 0.451193E+10 | 0.249569E+10 | 0.424592E+10 | 0.169668E+10 | 0.254924E+10 | 0.00 | 0.00 |
May | 0.442933E+10 | 0.173725E+10 | 0.383941E+10 | 0.111513E+10 | 0.272429E+10 | 0.00 | 0.00 |
June | 0.459514E+10 | 0.112342E+10 | 0.361033E+10 | 0.765046E+09 | 0.284528E+10 | 0.00 | 0.00 |
July | 0.531453E+10 | 0.823233E+09 | 0.380841E+10 | 0.924045E+09 | 0.288437E+10 | 0.00 | 0.00 |
August | 0.583989E+10 | 0.110300E+10 | 0.427557E+10 | 0.138625E+10 | 0.288932E+10 | 0.00 | 0.00 |
September | 0.604049E+10 | 0.172184E+10 | 0.481085E+10 | 0.234324E+10 | 0.246761E+10 | 0.00 | 0.00 |
October | 0.519308E+10 | 0.264244E+10 | 0.475672E+10 | 0.271713E+10 | 0.203959E+10 | 0.00 | 0.00 |
November | 0.316982E+10 | 0.315845E+10 | 0.329677E+10 | 0.186114E+10 | 0.143563E+10 | 0.00 | 0.00 |
December | 0.249719E+10 | 0.449252E+10 | 0.317890E+10 | 0.164523E+10 | 0.153368E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.534156E+11 | 0.310651E+11 | 0.488428E+11 | 0.215402E+11 | 0.273026E+11 | 0.00 | 0.00 |
Minimum of Months | 0.249719E+10 | 0.823233E+09 | 0.317890E+10 | 0.765046E+09 | 0.143563E+10 | 0.00 | 0.00 |
Maximum of Months | 0.604049E+10 | 0.449252E+10 | 0.529785E+10 | 0.297683E+10 | 0.288932E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.264384E+09 | 0.338098E+10 | 0.925405E+09 | 0.217248E+09 | 0.708157E+09 | 0.00 | 0.00 |
February | 0.604469E+09 | 0.287119E+10 | 0.135468E+10 | 0.348162E+09 | 0.100652E+10 | 0.00 | 0.00 |
March | 0.195041E+10 | 0.227215E+10 | 0.235071E+10 | 0.100651E+10 | 0.134420E+10 | 0.00 | 0.00 |
April | 0.269944E+10 | 0.163065E+10 | 0.278528E+10 | 0.114207E+10 | 0.164321E+10 | 0.00 | 0.00 |
May | 0.379314E+10 | 0.117814E+10 | 0.339521E+10 | 0.153441E+10 | 0.186080E+10 | 0.00 | 0.00 |
June | 0.492811E+10 | 0.791924E+09 | 0.396428E+10 | 0.186463E+10 | 0.209966E+10 | 0.00 | 0.00 |
July | 0.485041E+10 | 0.580448E+09 | 0.366236E+10 | 0.160570E+10 | 0.205666E+10 | 0.00 | 0.00 |
August | 0.430227E+10 | 0.750830E+09 | 0.331239E+10 | 0.140845E+10 | 0.190393E+10 | 0.00 | 0.00 |
September | 0.292026E+10 | 0.113693E+10 | 0.251734E+10 | 0.108712E+10 | 0.143021E+10 | 0.00 | 0.00 |
October | 0.147718E+10 | 0.178966E+10 | 0.168625E+10 | 0.593993E+09 | 0.109226E+10 | 0.00 | 0.00 |
November | 0.581115E+09 | 0.217761E+10 | 0.967046E+09 | 0.278667E+09 | 0.688379E+09 | 0.00 | 0.00 |
December | 0.250741E+09 | 0.330847E+10 | 0.866287E+09 | 0.188754E+09 | 0.677534E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.286219E+11 | 0.218690E+11 | 0.277872E+11 | 0.112757E+11 | 0.165115E+11 | 0.00 | 0.00 |
Minimum of Months | 0.250741E+09 | 0.580448E+09 | 0.866287E+09 | 0.188754E+09 | 0.677534E+09 | 0.00 | 0.00 |
Maximum of Months | 0.492811E+10 | 0.338098E+10 | 0.396428E+10 | 0.186463E+10 | 0.209966E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 8896369.57 | 0.542329E+10 | 0.884097E+09 | 0.00 | 0.884097E+09 | 0.00 | 0.00 |
February | 69966121.16 | 0.458444E+10 | 0.121667E+10 | 0.00 | 0.121667E+10 | 0.00 | 0.00 |
March | 0.524305E+09 | 0.368740E+10 | 0.163357E+10 | 0.00 | 0.163357E+10 | 0.00 | 0.00 |
April | 0.108390E+10 | 0.254261E+10 | 0.201436E+10 | 8038086.86 | 0.200632E+10 | 0.00 | 0.00 |
May | 0.187596E+10 | 0.171626E+10 | 0.241860E+10 | 0.102563E+09 | 0.231604E+10 | 0.00 | 0.00 |
June | 0.302258E+10 | 0.108402E+10 | 0.281523E+10 | 0.239647E+09 | 0.257558E+10 | 0.00 | 0.00 |
July | 0.336611E+10 | 0.786314E+09 | 0.269855E+10 | 0.174197E+09 | 0.252435E+10 | 0.00 | 0.00 |
August | 0.274519E+10 | 0.104625E+10 | 0.233500E+10 | 35521897.19 | 0.229947E+10 | 0.00 | 0.00 |
September | 0.154001E+10 | 0.165430E+10 | 0.171966E+10 | 357270.95 | 0.171930E+10 | 0.00 | 0.00 |
October | 0.635217E+09 | 0.265007E+10 | 0.132837E+10 | 0.00 | 0.132837E+10 | 0.00 | 0.00 |
November | 0.181183E+09 | 0.328385E+10 | 0.863837E+09 | 0.00 | 0.863837E+09 | 0.00 | 0.00 |
December | 11682969.55 | 0.517791E+10 | 0.827489E+09 | 0.00 | 0.827489E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.150650E+11 | 0.336367E+11 | 0.207554E+11 | 0.560324E+09 | 0.201951E+11 | 0.00 | 0.00 |
Minimum of Months | 8896369.57 | 0.786314E+09 | 0.827489E+09 | 0.00 | 0.827489E+09 | 0.00 | 0.00 |
Maximum of Months | 0.336611E+10 | 0.542329E+10 | 0.281523E+10 | 0.239647E+09 | 0.257558E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.414947E+09 | 0.328378E+10 | 0.107859E+10 | 0.347796E+09 | 0.730792E+09 | 0.00 | 0.00 |
February | 0.673171E+09 | 0.280544E+10 | 0.142946E+10 | 0.428945E+09 | 0.100052E+10 | 0.00 | 0.00 |
March | 0.177848E+10 | 0.225747E+10 | 0.227101E+10 | 0.951083E+09 | 0.131993E+10 | 0.00 | 0.00 |
April | 0.273511E+10 | 0.160189E+10 | 0.290887E+10 | 0.128529E+10 | 0.162358E+10 | 0.00 | 0.00 |
May | 0.364581E+10 | 0.115403E+10 | 0.336761E+10 | 0.148967E+10 | 0.187794E+10 | 0.00 | 0.00 |
June | 0.441824E+10 | 0.731480E+09 | 0.363972E+10 | 0.160857E+10 | 0.203115E+10 | 0.00 | 0.00 |
July | 0.471975E+10 | 0.526525E+09 | 0.361159E+10 | 0.159013E+10 | 0.202146E+10 | 0.00 | 0.00 |
August | 0.416713E+10 | 0.690399E+09 | 0.326166E+10 | 0.136907E+10 | 0.189260E+10 | 0.00 | 0.00 |
September | 0.302253E+10 | 0.104836E+10 | 0.262671E+10 | 0.116511E+10 | 0.146161E+10 | 0.00 | 0.00 |
October | 0.164251E+10 | 0.166074E+10 | 0.184186E+10 | 0.761840E+09 | 0.108002E+10 | 0.00 | 0.00 |
November | 0.626340E+09 | 0.208401E+10 | 0.101103E+10 | 0.324327E+09 | 0.686706E+09 | 0.00 | 0.00 |
December | 0.214685E+09 | 0.323977E+10 | 0.841065E+09 | 0.173782E+09 | 0.667283E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.280587E+11 | 0.210839E+11 | 0.278892E+11 | 0.114956E+11 | 0.163936E+11 | 0.00 | 0.00 |
Minimum of Months | 0.214685E+09 | 0.526525E+09 | 0.841065E+09 | 0.173782E+09 | 0.667283E+09 | 0.00 | 0.00 |
Maximum of Months | 0.471975E+10 | 0.328378E+10 | 0.363972E+10 | 0.160857E+10 | 0.203115E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.307088E+10 | 0.463479E+10 | 0.380157E+10 | 0.221909E+10 | 0.158248E+10 | 0.00 | 0.00 |
February | 0.311954E+10 | 0.410894E+10 | 0.392040E+10 | 0.189038E+10 | 0.203002E+10 | 0.00 | 0.00 |
March | 0.519509E+10 | 0.341423E+10 | 0.529780E+10 | 0.297679E+10 | 0.232100E+10 | 0.00 | 0.00 |
April | 0.434221E+10 | 0.263205E+10 | 0.424589E+10 | 0.169666E+10 | 0.254922E+10 | 0.00 | 0.00 |
May | 0.425502E+10 | 0.189254E+10 | 0.383938E+10 | 0.111511E+10 | 0.272427E+10 | 0.00 | 0.00 |
June | 0.448165E+10 | 0.119586E+10 | 0.361030E+10 | 0.765037E+09 | 0.284527E+10 | 0.00 | 0.00 |
July | 0.524477E+10 | 0.857494E+09 | 0.380838E+10 | 0.924034E+09 | 0.288435E+10 | 0.00 | 0.00 |
August | 0.578961E+10 | 0.111003E+10 | 0.427553E+10 | 0.138623E+10 | 0.288930E+10 | 0.00 | 0.00 |
September | 0.599652E+10 | 0.168914E+10 | 0.481081E+10 | 0.234322E+10 | 0.246759E+10 | 0.00 | 0.00 |
October | 0.512721E+10 | 0.256795E+10 | 0.475667E+10 | 0.271710E+10 | 0.203957E+10 | 0.00 | 0.00 |
November | 0.312175E+10 | 0.310971E+10 | 0.329673E+10 | 0.186112E+10 | 0.143562E+10 | 0.00 | 0.00 |
December | 0.242871E+10 | 0.456951E+10 | 0.317887E+10 | 0.164521E+10 | 0.153366E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.521730E+11 | 0.317822E+11 | 0.488423E+11 | 0.215400E+11 | 0.273024E+11 | 0.00 | 0.00 |
Minimum of Months | 0.242871E+10 | 0.857494E+09 | 0.317887E+10 | 0.765037E+09 | 0.143562E+10 | 0.00 | 0.00 |
Maximum of Months | 0.599652E+10 | 0.463479E+10 | 0.529780E+10 | 0.297679E+10 | 0.288930E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.256292E+09 | 0.341159E+10 | 0.925412E+09 | 0.217250E+09 | 0.708162E+09 | 0.00 | 0.00 |
February | 0.583494E+09 | 0.289980E+10 | 0.135469E+10 | 0.348165E+09 | 0.100653E+10 | 0.00 | 0.00 |
March | 0.188816E+10 | 0.232456E+10 | 0.235073E+10 | 0.100652E+10 | 0.134420E+10 | 0.00 | 0.00 |
April | 0.262720E+10 | 0.168379E+10 | 0.278531E+10 | 0.114208E+10 | 0.164322E+10 | 0.00 | 0.00 |
May | 0.371712E+10 | 0.123075E+10 | 0.339524E+10 | 0.153442E+10 | 0.186081E+10 | 0.00 | 0.00 |
June | 0.488120E+10 | 0.803268E+09 | 0.396431E+10 | 0.186464E+10 | 0.209967E+10 | 0.00 | 0.00 |
July | 0.481528E+10 | 0.586569E+09 | 0.366239E+10 | 0.160571E+10 | 0.205667E+10 | 0.00 | 0.00 |
August | 0.428174E+10 | 0.742223E+09 | 0.331241E+10 | 0.140847E+10 | 0.190395E+10 | 0.00 | 0.00 |
September | 0.290988E+10 | 0.110975E+10 | 0.251736E+10 | 0.108713E+10 | 0.143022E+10 | 0.00 | 0.00 |
October | 0.147968E+10 | 0.172533E+10 | 0.168627E+10 | 0.593999E+09 | 0.109227E+10 | 0.00 | 0.00 |
November | 0.580431E+09 | 0.212737E+10 | 0.967054E+09 | 0.278670E+09 | 0.688384E+09 | 0.00 | 0.00 |
December | 0.246323E+09 | 0.329058E+10 | 0.866294E+09 | 0.188755E+09 | 0.677539E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.282668E+11 | 0.219356E+11 | 0.277875E+11 | 0.112758E+11 | 0.165116E+11 | 0.00 | 0.00 |
Minimum of Months | 0.246323E+09 | 0.586569E+09 | 0.866294E+09 | 0.188755E+09 | 0.677539E+09 | 0.00 | 0.00 |
Maximum of Months | 0.488120E+10 | 0.341159E+10 | 0.396431E+10 | 0.186464E+10 | 0.209967E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.563286E+10 | -0.488346E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -749393093.5 | 58.98 | 0.00 | 0.00 |
February | 0.517421E+10 | -0.450247E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -671737530.1 | 58.99 | 0.00 | 0.00 |
March | 0.597556E+10 | -0.525700E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -718552791.2 | 58.98 | 0.00 | 0.00 |
April | 0.522657E+10 | -0.454428E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -682284072.1 | 58.98 | 0.00 | 0.00 |
May | 0.529160E+10 | -0.459880E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692802680.0 | 58.99 | 0.00 | 0.00 |
June | 0.495366E+10 | -0.428521E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668447433.9 | 58.98 | 0.00 | 0.00 |
July | 0.452775E+10 | -0.384055E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687199057.7 | 58.98 | 0.00 | 0.00 |
August | 0.485628E+10 | -0.416738E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688899360.5 | 58.98 | 0.00 | 0.00 |
September | 0.448789E+10 | -0.382034E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667547900.4 | 58.98 | 0.00 | 0.00 |
October | 0.484095E+10 | -0.414286E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -698090385.4 | 58.98 | 0.00 | 0.00 |
November | 0.502595E+10 | -0.433784E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -688110602.1 | 58.98 | 0.00 | 0.00 |
December | 0.528874E+10 | -0.455280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -735936046.4 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.612820E+11 | -0.529330E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.834900E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.448789E+10 | -0.525700E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -749393093.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.597556E+10 | -0.382034E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -667547900.4 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.62 | 01-JAN-08:39 | 3900.36 | 32.07 | 234.00 | 243.83 | 3167.71 | 33.40 | 241.50 | 217.17 |
February | 262.50 | 0.63 | 0.62 | 01-FEB-09:09 | 4915.76 | 32.29 | 243.33 | 251.50 | 1616.01 | 26.55 | 232.33 | 232.50 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:30 | 7091.69 | 29.11 | 246.33 | 321.50 | 1288.21 | 21.15 | 159.83 | 285.00 |
April | 371.17 | 0.64 | 0.62 | 01-APR-06:40 | 1783.40 | 17.51 | 0.00 | 338.17 | 997.47 | 20.26 | 153.00 | 297.50 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-06:19 | 1608.00 | 17.56 | 0.00 | 374.17 | 945.63 | 20.38 | 123.83 | 322.17 |
June | 430.67 | 0.64 | 0.62 | 01-JUN-05:49 | 1450.25 | 17.35 | 0.00 | 383.67 | 833.33 | 20.13 | 149.67 | 339.50 |
July | 439.00 | 0.64 | 0.62 | 01-JUL-05:49 | 1523.42 | 17.39 | 0.00 | 390.00 | 862.87 | 20.16 | 168.33 | 340.00 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-05:00 | 1810.58 | 17.90 | 0.00 | 368.67 | 1003.12 | 20.66 | 204.17 | 325.50 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2597.07 | 19.46 | 17.00 | 318.00 | 1321.95 | 21.32 | 178.83 | 281.67 |
October | 314.33 | 0.63 | 0.62 | 01-OCT-06:00 | 5715.51 | 31.67 | 272.33 | 294.33 | 1363.49 | 21.76 | 164.67 | 271.17 |
November | 258.33 | 0.64 | 0.62 | 01-NOV-07:40 | 3678.51 | 31.90 | 237.67 | 236.50 | 1476.29 | 27.36 | 198.83 | 209.67 |
December | 230.67 | 0.63 | 0.62 | 01-DEC-07:00 | 3258.68 | 29.83 | 197.00 | 231.83 | 2588.04 | 32.32 | 216.50 | 199.00 |
Annual Sum or Average | 3928.50 | 0.63 | 3096.88 | 23.40 | 1447.67 | 3752.17 | 1346.09 | 23.01 | 2191.50 | 3320.83 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 1450.25 | 17.35 | 0.00 | 231.83 | 833.33 | 20.13 | 123.83 | 199.00 | |
Maximum of Months | 439.00 | 0.64 | 0.62 | 7091.69 | 32.29 | 272.33 | 390.00 | 3167.71 | 33.40 | 241.50 | 340.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.62 | 01-JAN-08:39 | 1317.75 | 19.66 | 68.83 | 227.17 | 656.45 | 20.82 | 70.67 | 171.33 |
February | 262.50 | 0.63 | 0.62 | 01-FEB-09:09 | 1792.06 | 19.62 | 68.33 | 240.83 | 946.13 | 22.19 | 81.83 | 206.17 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:30 | 2471.45 | 20.49 | 101.83 | 311.17 | 1050.46 | 20.87 | 53.33 | 268.17 |
April | 371.17 | 0.63 | 0.62 | 01-APR-06:19 | 2690.23 | 20.04 | 103.67 | 342.83 | 1504.82 | 21.72 | 77.83 | 300.67 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-05:30 | 3543.52 | 20.25 | 86.67 | 381.67 | 1508.85 | 21.70 | 56.33 | 332.50 |
June | 430.67 | 0.63 | 0.62 | 01-JUN-05:40 | 3275.78 | 20.73 | 131.00 | 393.83 | 1424.56 | 21.44 | 75.83 | 359.83 |
July | 439.00 | 0.63 | 0.62 | 01-JUL-04:00 | 3032.51 | 19.73 | 113.83 | 399.67 | 1346.36 | 21.45 | 75.50 | 358.17 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-05:49 | 2832.84 | 20.13 | 106.50 | 370.67 | 1252.23 | 21.69 | 67.33 | 334.33 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2777.88 | 20.00 | 67.17 | 315.17 | 1587.39 | 23.07 | 67.17 | 275.83 |
October | 314.33 | 0.64 | 0.62 | 01-OCT-06:00 | 1807.87 | 19.41 | 77.67 | 280.33 | 961.16 | 21.06 | 60.00 | 237.33 |
November | 258.33 | 0.64 | 0.62 | 01-NOV-07:40 | 1282.70 | 18.46 | 69.33 | 220.67 | 730.95 | 21.26 | 77.83 | 159.17 |
December | 230.67 | 0.63 | 0.62 | 01-DEC-07:00 | 1133.08 | 18.96 | 59.00 | 217.17 | 566.95 | 20.30 | 55.33 | 156.67 |
Annual Sum or Average | 3928.50 | 0.63 | 2463.36 | 19.87 | 1053.83 | 3701.17 | 1177.49 | 21.49 | 819.00 | 3160.17 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 1133.08 | 18.46 | 59.00 | 217.17 | 566.95 | 20.30 | 53.33 | 156.67 | |
Maximum of Months | 439.00 | 0.64 | 0.62 | 3543.52 | 20.73 | 131.00 | 399.67 | 1587.39 | 23.07 | 81.83 | 359.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.64 | 0.62 | 01-JAN-08:00 | 559.79 | 14.37 | 0.00 | 207.00 | 314.44 | 17.20 | 0.00 | 89.50 |
February | 262.50 | 0.64 | 0.62 | 01-FEB-09:30 | 736.53 | 15.54 | 0.00 | 233.50 | 410.74 | 18.24 | 0.00 | 169.50 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:00 | 775.52 | 16.10 | 0.00 | 303.83 | 455.97 | 18.91 | 0.00 | 243.50 |
April | 371.17 | 0.63 | 0.62 | 01-APR-06:40 | 895.05 | 16.75 | 0.00 | 342.00 | 528.82 | 19.43 | 1.17 | 297.67 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-05:40 | 1063.36 | 17.90 | 3.33 | 393.67 | 652.41 | 21.74 | 79.50 | 350.50 |
June | 430.67 | 0.63 | 0.62 | 01-JUN-05:49 | 1205.42 | 20.68 | 74.33 | 408.67 | 708.20 | 22.03 | 152.67 | 381.67 |
July | 439.00 | 0.63 | 0.62 | 01-JUL-05:10 | 1146.77 | 20.32 | 71.00 | 414.00 | 672.27 | 21.76 | 134.67 | 380.83 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-05:49 | 1012.83 | 17.50 | 0.00 | 380.83 | 604.51 | 20.22 | 44.33 | 341.67 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 841.13 | 16.96 | 0.00 | 312.33 | 524.61 | 19.75 | 1.00 | 252.83 |
October | 314.33 | 0.64 | 0.62 | 01-OCT-07:10 | 681.50 | 15.26 | 0.00 | 269.83 | 393.70 | 18.06 | 0.00 | 189.33 |
November | 258.33 | 0.65 | 0.62 | 01-NOV-07:00 | 543.34 | 13.88 | 0.00 | 204.00 | 303.49 | 16.60 | 0.00 | 88.00 |
December | 230.67 | 0.64 | 0.62 | 01-DEC-11:20 | 564.93 | 14.31 | 0.00 | 192.17 | 309.94 | 17.06 | 0.00 | 82.50 |
Annual Sum or Average | 3928.50 | 0.63 | 877.35 | 17.03 | 148.67 | 3661.83 | 515.89 | 19.57 | 413.33 | 2867.50 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 543.34 | 13.88 | 0.00 | 192.17 | 303.49 | 16.60 | 0.00 | 82.50 | |
Maximum of Months | 439.00 | 0.65 | 0.62 | 1205.42 | 20.68 | 74.33 | 414.00 | 708.20 | 22.03 | 152.67 | 381.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.62 | 01-JAN-09:09 | 1199.93 | 18.60 | 63.50 | 224.00 | 674.41 | 21.50 | 74.17 | 167.17 |
February | 262.50 | 0.63 | 0.62 | 01-FEB-09:30 | 1666.63 | 19.28 | 67.17 | 241.83 | 900.99 | 22.05 | 75.67 | 204.83 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:00 | 2431.55 | 20.43 | 99.67 | 313.83 | 1372.62 | 22.08 | 78.17 | 272.83 |
April | 371.17 | 0.63 | 0.62 | 01-APR-06:00 | 2834.15 | 19.77 | 103.67 | 337.33 | 1207.71 | 20.19 | 49.33 | 299.83 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-06:30 | 3073.23 | 16.93 | 43.00 | 381.17 | 1681.74 | 18.17 | 0.00 | 335.83 |
June | 430.67 | 0.63 | 0.62 | 01-JUN-05:00 | 3221.99 | 16.70 | 52.33 | 391.83 | 1383.22 | 18.14 | 0.00 | 356.67 |
July | 439.00 | 0.63 | 0.62 | 01-JUL-05:00 | 2873.09 | 16.76 | 54.50 | 396.83 | 1303.72 | 18.32 | 3.67 | 359.67 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-06:10 | 2712.23 | 18.78 | 84.33 | 373.50 | 1467.67 | 20.60 | 53.50 | 330.83 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2974.26 | 21.29 | 83.50 | 313.83 | 1261.28 | 21.50 | 42.33 | 278.33 |
October | 314.33 | 0.64 | 0.62 | 01-OCT-07:19 | 1695.80 | 18.98 | 73.67 | 278.17 | 916.92 | 21.73 | 65.17 | 238.00 |
November | 258.33 | 0.64 | 0.62 | 01-NOV-07:00 | 1241.14 | 18.30 | 71.33 | 218.67 | 677.69 | 20.83 | 67.17 | 163.00 |
December | 230.67 | 0.63 | 0.62 | 01-DEC-09:30 | 1170.18 | 18.41 | 50.33 | 210.83 | 629.58 | 20.97 | 63.50 | 154.50 |
Annual Sum or Average | 3928.50 | 0.63 | 2386.47 | 18.57 | 847.00 | 3681.83 | 1175.61 | 20.31 | 572.67 | 3161.50 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 1170.18 | 16.70 | 43.00 | 210.83 | 629.58 | 18.14 | 0.00 | 154.50 | |
Maximum of Months | 439.00 | 0.64 | 0.62 | 3221.99 | 21.29 | 103.67 | 396.83 | 1681.74 | 22.08 | 78.17 | 359.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.62 | 01-JAN-08:50 | 3771.68 | 31.70 | 231.50 | 242.17 | 3080.39 | 32.94 | 231.50 | 214.33 |
February | 262.50 | 0.63 | 0.62 | 01-FEB-09:09 | 4775.20 | 32.00 | 240.17 | 250.50 | 1524.03 | 24.54 | 105.83 | 230.33 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:30 | 6959.58 | 28.10 | 226.33 | 319.67 | 1196.63 | 18.37 | 9.00 | 281.67 |
April | 371.17 | 0.64 | 0.62 | 01-APR-06:40 | 1687.57 | 13.79 | 0.00 | 336.83 | 933.65 | 17.70 | 0.17 | 293.67 |
May | 332.17 | 0.64 | 0.62 | 01-MAY-06:19 | 1525.85 | 14.06 | 0.00 | 370.67 | 892.34 | 18.07 | 0.00 | 316.00 |
June | 430.67 | 0.64 | 0.62 | 01-JUN-05:49 | 1381.16 | 13.88 | 0.00 | 380.67 | 791.08 | 17.82 | 0.00 | 334.33 |
July | 439.00 | 0.64 | 0.62 | 01-JUL-05:00 | 1449.51 | 13.84 | 0.00 | 386.67 | 817.03 | 17.77 | 0.00 | 336.17 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-05:00 | 1717.77 | 14.29 | 0.00 | 365.17 | 943.68 | 18.21 | 0.00 | 321.83 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2462.47 | 16.05 | 17.00 | 315.83 | 1229.02 | 18.87 | 3.50 | 278.17 |
October | 314.33 | 0.63 | 0.62 | 01-OCT-06:00 | 5587.85 | 31.16 | 267.67 | 293.00 | 1272.86 | 18.86 | 20.67 | 268.83 |
November | 258.33 | 0.64 | 0.62 | 01-NOV-07:40 | 3563.43 | 31.65 | 234.67 | 234.33 | 1400.94 | 25.66 | 132.83 | 207.17 |
December | 230.67 | 0.63 | 0.62 | 01-DEC-08:09 | 3130.70 | 28.93 | 190.67 | 229.17 | 2509.10 | 31.87 | 210.67 | 195.00 |
Annual Sum or Average | 3928.50 | 0.63 | 2991.09 | 21.12 | 1408.00 | 3724.67 | 1276.25 | 20.84 | 714.17 | 3277.50 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 1381.16 | 13.79 | 0.00 | 229.17 | 791.08 | 17.70 | 0.00 | 195.00 | |
Maximum of Months | 439.00 | 0.64 | 0.62 | 6959.58 | 32.00 | 267.67 | 386.67 | 3080.39 | 32.94 | 231.50 | 336.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.64 | 0.62 | 01-JAN-08:39 | 1273.63 | 19.21 | 68.67 | 224.83 | 625.20 | 20.56 | 65.17 | 167.00 |
February | 262.50 | 0.64 | 0.62 | 01-FEB-09:09 | 1733.60 | 19.19 | 67.67 | 239.67 | 904.88 | 21.96 | 73.00 | 203.00 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:30 | 2403.66 | 20.09 | 101.67 | 308.83 | 1000.17 | 20.65 | 49.33 | 263.67 |
April | 371.17 | 0.63 | 0.62 | 01-APR-06:19 | 2612.67 | 19.64 | 103.17 | 339.33 | 1446.26 | 21.53 | 77.83 | 297.50 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-05:30 | 3441.03 | 19.75 | 85.67 | 378.17 | 1441.59 | 21.53 | 56.00 | 328.50 |
June | 430.67 | 0.63 | 0.62 | 01-JUN-05:40 | 3108.57 | 19.01 | 107.17 | 390.83 | 1364.10 | 21.27 | 75.83 | 357.00 |
July | 439.00 | 0.63 | 0.62 | 01-JUL-04:00 | 2948.19 | 19.33 | 113.67 | 395.17 | 1282.03 | 21.21 | 74.67 | 354.50 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-05:49 | 2749.94 | 19.73 | 106.33 | 368.50 | 1162.72 | 20.63 | 54.33 | 328.67 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2689.90 | 19.57 | 67.17 | 312.00 | 1520.96 | 22.88 | 63.67 | 270.00 |
October | 314.33 | 0.64 | 0.62 | 01-OCT-06:00 | 1748.10 | 18.98 | 77.67 | 278.00 | 917.23 | 20.83 | 55.50 | 231.67 |
November | 258.33 | 0.64 | 0.62 | 01-NOV-07:40 | 1240.62 | 18.03 | 69.00 | 218.17 | 701.73 | 21.03 | 70.67 | 153.50 |
December | 230.67 | 0.63 | 0.62 | 01-DEC-07:00 | 1086.87 | 18.19 | 54.67 | 213.83 | 540.20 | 20.04 | 52.17 | 150.83 |
Annual Sum or Average | 3928.50 | 0.63 | 2381.68 | 19.29 | 1022.50 | 3667.33 | 1122.17 | 21.19 | 768.17 | 3105.83 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 1086.87 | 18.03 | 54.67 | 213.83 | 540.20 | 20.04 | 49.33 | 150.83 | |
Maximum of Months | 439.00 | 0.64 | 0.62 | 3441.03 | 20.09 | 113.67 | 395.17 | 1520.96 | 22.88 | 77.83 | 357.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.64 | 0.62 | 01-JAN-09:09 | 535.35 | 10.44 | 0.00 | 201.83 | 301.27 | 14.50 | 0.00 | 74.33 |
February | 262.50 | 0.64 | 0.62 | 01-FEB-09:39 | 705.38 | 11.88 | 0.00 | 231.50 | 393.99 | 15.76 | 0.00 | 162.00 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:00 | 743.06 | 12.66 | 0.00 | 300.50 | 438.85 | 16.64 | 0.00 | 234.50 |
April | 371.17 | 0.63 | 0.62 | 01-APR-06:40 | 862.66 | 13.40 | 0.00 | 342.67 | 509.17 | 17.30 | 0.00 | 292.67 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-05:40 | 1019.39 | 14.64 | 3.33 | 390.50 | 629.00 | 19.88 | 24.67 | 344.67 |
June | 430.67 | 0.63 | 0.62 | 01-JUN-05:49 | 1155.64 | 17.99 | 73.67 | 406.00 | 680.90 | 20.02 | 37.00 | 379.00 |
July | 439.00 | 0.63 | 0.62 | 01-JUL-05:10 | 1099.26 | 17.57 | 70.50 | 412.00 | 646.41 | 19.74 | 36.67 | 377.50 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-05:49 | 970.10 | 14.19 | 0.00 | 377.83 | 581.79 | 18.15 | 0.00 | 336.83 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 804.82 | 13.96 | 0.00 | 308.17 | 505.70 | 17.92 | 0.00 | 246.67 |
October | 314.33 | 0.64 | 0.62 | 01-OCT-07:10 | 652.48 | 11.65 | 0.00 | 264.83 | 378.27 | 15.62 | 0.00 | 178.00 |
November | 258.33 | 0.65 | 0.62 | 01-NOV-07:00 | 519.83 | 10.02 | 0.00 | 198.50 | 290.83 | 13.92 | 0.00 | 74.50 |
December | 230.67 | 0.64 | 0.62 | 01-DEC-11:20 | 540.47 | 10.35 | 0.00 | 187.00 | 296.70 | 14.33 | 0.00 | 72.83 |
Annual Sum or Average | 3928.50 | 0.63 | 840.94 | 13.70 | 147.50 | 3621.33 | 496.13 | 17.35 | 98.33 | 2773.50 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 519.83 | 10.02 | 0.00 | 187.00 | 290.83 | 13.92 | 0.00 | 72.83 | |
Maximum of Months | 439.00 | 0.65 | 0.62 | 1155.64 | 17.99 | 73.67 | 412.00 | 680.90 | 20.02 | 37.00 | 379.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.64 | 0.62 | 01-JAN-09:09 | 1161.21 | 18.24 | 63.17 | 221.83 | 647.98 | 21.39 | 73.50 | 162.00 |
February | 262.50 | 0.63 | 0.62 | 01-FEB-09:39 | 1610.15 | 18.92 | 66.83 | 240.17 | 861.56 | 21.94 | 74.50 | 200.50 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:00 | 2360.73 | 20.08 | 99.50 | 310.17 | 1319.37 | 21.95 | 77.67 | 269.50 |
April | 371.17 | 0.64 | 0.62 | 01-APR-07:10 | 2761.97 | 19.40 | 103.50 | 335.33 | 1153.41 | 20.03 | 49.33 | 295.67 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-06:30 | 2978.95 | 16.51 | 43.00 | 379.33 | 1612.26 | 18.01 | 0.00 | 331.00 |
June | 430.67 | 0.63 | 0.62 | 01-JUN-05:00 | 3127.71 | 16.27 | 52.33 | 389.33 | 1314.73 | 17.96 | 0.00 | 352.83 |
July | 439.00 | 0.63 | 0.62 | 01-JUL-05:00 | 2773.66 | 16.33 | 54.50 | 394.50 | 1241.64 | 18.14 | 3.67 | 356.00 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-06:10 | 2530.55 | 18.39 | 84.33 | 371.00 | 1407.03 | 20.45 | 53.50 | 325.00 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2891.94 | 20.93 | 83.50 | 311.33 | 1193.70 | 21.24 | 41.17 | 274.33 |
October | 314.33 | 0.64 | 0.62 | 01-OCT-07:19 | 1639.06 | 18.61 | 73.50 | 276.17 | 855.31 | 20.69 | 54.33 | 231.50 |
November | 258.33 | 0.65 | 0.62 | 01-NOV-07:00 | 1201.17 | 17.96 | 71.17 | 216.50 | 650.21 | 20.69 | 66.17 | 157.67 |
December | 230.67 | 0.64 | 0.62 | 01-DEC-10:00 | 1130.09 | 18.06 | 50.17 | 208.17 | 586.73 | 20.01 | 52.83 | 149.00 |
Annual Sum or Average | 3928.50 | 0.63 | 2303.47 | 18.19 | 845.50 | 3653.83 | 1120.72 | 20.03 | 546.67 | 3105.00 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 1130.09 | 16.27 | 43.00 | 208.17 | 586.73 | 17.96 | 0.00 | 149.00 | |
Maximum of Months | 439.00 | 0.65 | 0.62 | 3127.71 | 20.93 | 103.50 | 394.50 | 1612.26 | 21.95 | 77.67 | 356.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.62 | 01-JAN-08:50 | 3771.69 | 31.70 | 231.50 | 242.17 | 3080.32 | 32.94 | 231.50 | 214.33 |
February | 262.50 | 0.63 | 0.62 | 01-FEB-09:09 | 4775.17 | 32.00 | 240.17 | 250.50 | 1523.93 | 24.54 | 105.83 | 230.33 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:30 | 6959.51 | 28.10 | 226.33 | 319.67 | 1196.55 | 18.37 | 9.00 | 281.67 |
April | 371.17 | 0.64 | 0.62 | 01-APR-06:40 | 1687.50 | 13.79 | 0.00 | 336.83 | 933.58 | 17.70 | 0.17 | 293.67 |
May | 332.17 | 0.64 | 0.62 | 01-MAY-06:19 | 1525.79 | 14.06 | 0.00 | 370.67 | 892.28 | 18.07 | 0.00 | 316.00 |
June | 430.67 | 0.64 | 0.62 | 01-JUN-05:49 | 1381.11 | 13.89 | 0.00 | 380.67 | 791.03 | 17.82 | 0.00 | 334.33 |
July | 439.00 | 0.64 | 0.62 | 01-JUL-05:00 | 1449.45 | 13.84 | 0.00 | 386.67 | 816.98 | 17.77 | 0.00 | 336.17 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-05:00 | 1717.70 | 14.29 | 0.00 | 365.17 | 943.61 | 18.21 | 0.00 | 321.67 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2462.39 | 16.05 | 17.00 | 315.83 | 1228.93 | 18.87 | 3.50 | 278.17 |
October | 314.33 | 0.63 | 0.62 | 01-OCT-06:00 | 5587.81 | 31.16 | 267.67 | 293.00 | 1272.78 | 18.86 | 20.67 | 268.83 |
November | 258.33 | 0.64 | 0.62 | 01-NOV-07:40 | 3563.43 | 31.65 | 234.67 | 234.33 | 1400.86 | 25.66 | 132.83 | 207.17 |
December | 230.67 | 0.63 | 0.62 | 01-DEC-08:09 | 3130.71 | 28.93 | 190.67 | 229.17 | 2509.02 | 31.87 | 210.67 | 195.00 |
Annual Sum or Average | 3928.50 | 0.63 | 2991.04 | 21.12 | 1408.00 | 3724.67 | 1276.18 | 20.84 | 714.17 | 3277.33 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 1381.11 | 13.79 | 0.00 | 229.17 | 791.03 | 17.70 | 0.00 | 195.00 | |
Maximum of Months | 439.00 | 0.64 | 0.62 | 6959.51 | 32.00 | 267.67 | 386.67 | 3080.32 | 32.94 | 231.50 | 336.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.64 | 0.62 | 01-JAN-08:39 | 1273.62 | 19.21 | 68.67 | 224.83 | 625.16 | 20.56 | 65.17 | 167.00 |
February | 262.50 | 0.64 | 0.62 | 01-FEB-09:09 | 1733.57 | 19.19 | 67.67 | 239.67 | 904.83 | 21.96 | 73.00 | 203.00 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:30 | 2403.65 | 20.09 | 101.67 | 308.83 | 1000.12 | 20.65 | 49.33 | 263.67 |
April | 371.17 | 0.63 | 0.62 | 01-APR-06:19 | 2612.65 | 19.64 | 103.17 | 339.33 | 1446.20 | 21.53 | 77.83 | 297.50 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-05:30 | 3441.01 | 19.75 | 85.67 | 378.17 | 1441.53 | 21.53 | 56.00 | 328.50 |
June | 430.67 | 0.63 | 0.62 | 01-JUN-05:40 | 3108.55 | 19.02 | 107.17 | 390.83 | 1364.04 | 21.27 | 75.83 | 357.00 |
July | 439.00 | 0.63 | 0.62 | 01-JUL-04:00 | 2948.16 | 19.33 | 113.67 | 395.17 | 1281.97 | 21.21 | 74.67 | 354.50 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-05:49 | 2749.91 | 19.73 | 106.33 | 368.50 | 1162.66 | 20.63 | 54.33 | 328.67 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2689.89 | 19.57 | 67.17 | 312.00 | 1520.91 | 22.88 | 63.67 | 270.00 |
October | 314.33 | 0.64 | 0.62 | 01-OCT-06:00 | 1748.08 | 18.98 | 77.67 | 278.00 | 917.18 | 20.83 | 55.50 | 231.67 |
November | 258.33 | 0.64 | 0.62 | 01-NOV-07:40 | 1240.60 | 18.03 | 69.00 | 218.17 | 701.69 | 21.03 | 70.67 | 153.50 |
December | 230.67 | 0.63 | 0.62 | 01-DEC-07:00 | 1086.85 | 18.19 | 54.67 | 213.83 | 540.16 | 20.04 | 52.17 | 150.83 |
Annual Sum or Average | 3928.50 | 0.63 | 2381.66 | 19.29 | 1022.50 | 3667.33 | 1122.12 | 21.19 | 768.17 | 3105.83 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 1086.85 | 18.03 | 54.67 | 213.83 | 540.16 | 20.04 | 49.33 | 150.83 | |
Maximum of Months | 439.00 | 0.64 | 0.62 | 3441.01 | 20.09 | 113.67 | 395.17 | 1520.91 | 22.88 | 77.83 | 357.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.64 | 0.62 | 01-JAN-09:09 | 535.33 | 10.44 | 0.00 | 201.83 | 301.25 | 14.50 | 0.00 | 74.33 |
February | 262.50 | 0.64 | 0.62 | 01-FEB-09:39 | 705.36 | 11.88 | 0.00 | 231.50 | 393.96 | 15.76 | 0.00 | 162.00 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:00 | 743.04 | 12.66 | 0.00 | 300.50 | 438.82 | 16.65 | 0.00 | 234.50 |
April | 371.17 | 0.63 | 0.62 | 01-APR-06:40 | 862.64 | 13.40 | 0.00 | 342.67 | 509.14 | 17.30 | 0.00 | 292.67 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-05:40 | 1019.38 | 14.64 | 3.33 | 390.50 | 628.97 | 19.88 | 24.67 | 344.67 |
June | 430.67 | 0.63 | 0.62 | 01-JUN-05:49 | 1155.62 | 17.99 | 73.67 | 406.00 | 680.86 | 20.02 | 37.00 | 379.00 |
July | 439.00 | 0.63 | 0.62 | 01-JUL-05:10 | 1099.24 | 17.58 | 70.50 | 412.00 | 646.37 | 19.74 | 36.67 | 377.50 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-05:49 | 970.09 | 14.19 | 0.00 | 377.83 | 581.75 | 18.15 | 0.00 | 336.83 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 804.82 | 13.96 | 0.00 | 308.17 | 505.68 | 17.92 | 0.00 | 246.67 |
October | 314.33 | 0.64 | 0.62 | 01-OCT-07:10 | 652.47 | 11.65 | 0.00 | 264.83 | 378.24 | 15.62 | 0.00 | 178.00 |
November | 258.33 | 0.65 | 0.62 | 01-NOV-07:00 | 519.81 | 10.02 | 0.00 | 198.50 | 290.80 | 13.92 | 0.00 | 74.50 |
December | 230.67 | 0.64 | 0.62 | 01-DEC-11:20 | 540.46 | 10.35 | 0.00 | 187.00 | 296.67 | 14.33 | 0.00 | 72.83 |
Annual Sum or Average | 3928.50 | 0.63 | 840.92 | 13.70 | 147.50 | 3621.33 | 496.10 | 17.35 | 98.33 | 2773.50 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 519.81 | 10.02 | 0.00 | 187.00 | 290.80 | 13.92 | 0.00 | 72.83 | |
Maximum of Months | 439.00 | 0.65 | 0.62 | 1155.62 | 17.99 | 73.67 | 412.00 | 680.86 | 20.02 | 37.00 | 379.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.64 | 0.62 | 01-JAN-09:09 | 1161.19 | 18.24 | 63.17 | 221.83 | 647.94 | 21.39 | 73.50 | 162.00 |
February | 262.50 | 0.63 | 0.62 | 01-FEB-09:39 | 1610.12 | 18.92 | 67.00 | 240.17 | 861.51 | 21.94 | 74.50 | 200.50 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:00 | 2360.71 | 20.08 | 99.50 | 310.33 | 1319.32 | 21.95 | 77.67 | 269.50 |
April | 371.17 | 0.64 | 0.62 | 01-APR-07:10 | 2761.94 | 19.40 | 103.50 | 335.33 | 1153.35 | 20.03 | 49.33 | 295.67 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-06:30 | 2978.94 | 16.51 | 43.00 | 379.33 | 1612.21 | 18.01 | 0.00 | 331.00 |
June | 430.67 | 0.63 | 0.62 | 01-JUN-05:00 | 3127.69 | 16.28 | 52.33 | 389.33 | 1314.67 | 17.96 | 0.00 | 352.83 |
July | 439.00 | 0.63 | 0.62 | 01-JUL-05:00 | 2773.63 | 16.33 | 54.50 | 394.50 | 1241.58 | 18.15 | 3.67 | 356.00 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-06:10 | 2530.52 | 18.39 | 84.33 | 371.00 | 1406.97 | 20.45 | 53.50 | 325.00 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2891.94 | 20.93 | 83.50 | 311.33 | 1193.64 | 21.24 | 41.17 | 274.33 |
October | 314.33 | 0.64 | 0.62 | 01-OCT-07:19 | 1639.04 | 18.61 | 73.50 | 276.17 | 855.26 | 20.69 | 54.33 | 231.50 |
November | 258.33 | 0.65 | 0.62 | 01-NOV-07:00 | 1201.15 | 17.96 | 71.17 | 216.50 | 650.18 | 20.69 | 66.17 | 157.67 |
December | 230.67 | 0.64 | 0.62 | 01-DEC-10:00 | 1130.07 | 18.06 | 50.17 | 208.17 | 586.69 | 20.01 | 52.83 | 149.00 |
Annual Sum or Average | 3928.50 | 0.63 | 2303.45 | 18.19 | 845.67 | 3654.00 | 1120.66 | 20.03 | 546.67 | 3105.00 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 1130.07 | 16.28 | 43.00 | 208.17 | 586.69 | 17.96 | 0.00 | 149.00 | |
Maximum of Months | 439.00 | 0.65 | 0.62 | 3127.69 | 20.93 | 103.50 | 394.50 | 1612.21 | 21.95 | 77.67 | 356.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.727223E+09 | 25307.70 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 78448033.55 | 25307.70 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1118191.41 | 18636.52 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33798307.49 | 25307.70 | 11-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.840588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.727223E+09 | 25307.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105634E+11 | 11371.32 | 11-JAN-17:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.927153E+10 | 11338.76 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.585741E+10 | 11401.59 | 14-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.326914E+10 | 11379.95 | 13-APR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136978E+10 | 11407.10 | 22-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.375387E+09 | 11602.98 | 13-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 79117572.92 | 9723.49 | 13-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.183363E+09 | 11596.55 | 03-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.535176E+09 | 11620.76 | 06-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.191911E+10 | 11435.34 | 13-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.421352E+10 | 11377.15 | 02-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.915127E+10 | 11350.19 | 01-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.467882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 79117572.92 | 9723.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105634E+11 | 11620.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.366790E+10 | 9261.91 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.305743E+10 | 9245.84 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121188E+10 | 9220.79 | 31-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.233858E+09 | 9190.92 | 13-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2578178.80 | 2735.78 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34874288.93 | 9189.80 | 16-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.512480E+09 | 9200.66 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.285635E+10 | 9233.37 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.366790E+10 | 9261.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.587062E+10 | 7766.01 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.508309E+10 | 7752.40 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.273797E+10 | 7775.90 | 14-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.666183E+09 | 7745.51 | 13-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12921399.28 | 7737.08 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84649021.58 | 7744.40 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.779534E+09 | 7746.39 | 20-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.427735E+10 | 7756.91 | 14-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.587062E+10 | 7775.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.394934E+10 | 9767.14 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.332397E+10 | 9750.16 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137320E+10 | 9723.64 | 31-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.335456E+09 | 9692.21 | 13-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8063433.46 | 9730.03 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 50803752.85 | 9691.07 | 16-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.579599E+09 | 9702.49 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.294931E+10 | 9737.02 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.394934E+10 | 9767.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.381946E+10 | 25542.31 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.305489E+10 | 25542.31 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.523498E+09 | 25542.31 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 50168235.78 | 25542.31 | 17-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7923245.13 | 25542.31 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223678E+09 | 25542.31 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.263742E+10 | 25542.31 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.381946E+10 | 25542.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.412590E+10 | 12982.19 | 18-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.354332E+10 | 12965.56 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104980E+10 | 12954.96 | 06-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.261266E+09 | 12935.07 | 17-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2517848.04 | 11134.55 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 97192.52 | 92.38 | 30-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108696E+09 | 12805.54 | 16-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.807371E+09 | 12920.84 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.367756E+10 | 12975.90 | 19-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.412590E+10 | 12982.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.378854E+10 | 10898.44 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.318431E+10 | 10898.44 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112933E+10 | 10898.44 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202509E+09 | 10898.44 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 649112.33 | 1508.19 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1129460.56 | 2899.47 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155615E+09 | 10898.44 | 16-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.967829E+09 | 10898.44 | 03-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.345106E+10 | 10898.44 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.378854E+10 | 10898.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.561466E+10 | 8744.98 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.482073E+10 | 8751.59 | 15-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197739E+10 | 8741.18 | 09-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.335883E+09 | 8762.97 | 18-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 223108.75 | 3346.63 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 418173.89 | 415.74 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.181304E+09 | 8754.01 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111134E+10 | 8771.16 | 21-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.476083E+10 | 8779.27 | 14-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.561466E+10 | 8779.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.396932E+10 | 10999.30 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.335186E+10 | 10999.30 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127924E+10 | 10999.30 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.298413E+09 | 10999.30 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3779853.11 | 8049.71 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2176704.58 | 2228.54 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186010E+09 | 10999.30 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.993200E+09 | 10999.30 | 03-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.345924E+10 | 10999.30 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.396932E+10 | 10999.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.881796E+10 | 32373.17 | 11-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.738935E+10 | 32427.15 | 15-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.282882E+10 | 32458.07 | 10-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.546966E+09 | 32449.61 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 981668.27 | 10128.33 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.325428E+09 | 32463.93 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197399E+10 | 32462.21 | 13-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.753651E+10 | 32522.29 | 14-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.294200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.881796E+10 | 32522.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.674532E+10 | 14371.77 | 17-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.600300E+10 | 14359.13 | 23-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.240793E+10 | 14339.78 | 03-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.855299E+09 | 14371.14 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 55864308.78 | 14285.10 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720002.64 | 2205.27 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15976391.33 | 11109.86 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.583780E+09 | 14384.31 | 16-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.208555E+10 | 14397.21 | 14-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.637980E+10 | 14397.52 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.251332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.674532E+10 | 14397.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.553848E+10 | 11316.25 | 18-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.478145E+10 | 11316.00 | 23-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203902E+10 | 11326.34 | 10-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.541345E+09 | 11359.63 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17205176.55 | 7058.27 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15689628.23 | 7287.38 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.533755E+09 | 11310.43 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.186119E+10 | 11323.96 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.522919E+10 | 11364.62 | 14-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.553848E+10 | 11364.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.860277E+10 | 10072.16 | 18-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.751820E+10 | 10064.18 | 02-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.369046E+10 | 10080.83 | 23-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.981499E+09 | 10071.89 | 13-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34125919.74 | 9972.83 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21756536.28 | 9984.98 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.812459E+09 | 10055.34 | 30-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.259660E+10 | 10070.89 | 09-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.769517E+10 | 10075.72 | 14-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.860277E+10 | 10080.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.594231E+10 | 12497.58 | 07-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.516764E+10 | 12504.10 | 10-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.237984E+10 | 12526.07 | 10-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.798307E+09 | 12472.03 | 17-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 60389911.99 | 12496.17 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1450498.44 | 2263.68 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29129868.39 | 7173.05 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.708172E+09 | 12426.74 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.206092E+10 | 12483.72 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.541687E+10 | 12568.45 | 14-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.594231E+10 | 12568.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.162576E+11 | 24732.70 | 04-JAN-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150576E+11 | 29068.09 | 07-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.784414E+10 | 24361.16 | 07-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152914E+10 | 13742.52 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24151114.69 | 5216.02 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1717106.73 | 647.45 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.593495E+09 | 11089.25 | 17-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.303408E+10 | 12574.34 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137144E+11 | 29674.17 | 11-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.580564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.162576E+11 | 29674.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.170452E+11 | 24294.88 | 04-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157959E+11 | 29069.86 | 07-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.900820E+10 | 24136.35 | 07-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237797E+10 | 15054.95 | 17-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 57914645.66 | 6322.53 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12137987.45 | 1492.41 | 06-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120913E+10 | 12190.64 | 17-OCT-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.465452E+10 | 14212.27 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148118E+11 | 29516.11 | 11-DEC-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.649727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.170452E+11 | 29516.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.183930E+11 | 27083.81 | 04-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170106E+11 | 31520.95 | 07-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.927125E+10 | 26919.83 | 07-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.256337E+10 | 16801.97 | 17-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114506E+09 | 8003.59 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4207729.21 | 1763.87 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35586904.46 | 3126.79 | 06-SEP-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150097E+10 | 14928.58 | 17-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.504922E+10 | 15580.99 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160608E+11 | 28155.89 | 11-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.700035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.183930E+11 | 31520.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.191964E+10 | 0.157709E+10 | 29618.73 | 15-MAR-14:00 | 29618.73 | 0.00 |
April | 0.00 | 0.00 | 0.641863E+09 | 0.571024E+09 | 12550.65 | 07-APR-13:00 | 12550.65 | 0.00 |
May | 0.00 | 0.00 | 0.739141E+10 | 0.664161E+10 | 38081.18 | 10-MAY-15:10 | 36464.58 | 0.00 |
June | 0.00 | 0.00 | 0.371018E+11 | 0.278289E+11 | 99295.73 | 27-JUN-07:40 | 42872.29 | 0.00 |
July | 0.00 | 0.00 | 0.662732E+11 | 0.465940E+11 | 119379.88 | 20-JUL-04:03 | 47952.46 | 0.00 |
August | 0.00 | 0.00 | 0.564293E+11 | 0.432204E+11 | 119354.13 | 14-AUG-08:00 | 50584.20 | 0.00 |
September | 0.00 | 0.00 | 0.247910E+11 | 0.184801E+11 | 81521.71 | 15-SEP-14:50 | 44033.08 | 0.00 |
October | 0.00 | 0.00 | 0.258184E+10 | 0.217135E+10 | 30931.77 | 11-OCT-15:10 | 30931.77 | 0.00 |
November | 0.00 | 0.00 | 0.430241E+09 | 0.306001E+09 | 10699.79 | 16-NOV-18:00 | 8062.26 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.197560E+12 | 0.147390E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.662732E+11 | 0.465940E+11 | 119379.88 | 50584.20 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.182828E+10 | 0.151079E+10 | 31319.32 | 15-MAR-13:50 | 31319.32 | 0.00 |
April | 0.00 | 0.00 | 0.641270E+09 | 0.578581E+09 | 13066.87 | 08-APR-13:30 | 11368.65 | 0.00 |
May | 0.00 | 0.00 | 0.743017E+10 | 0.671035E+10 | 37888.27 | 23-MAY-14:30 | 37888.27 | 0.00 |
June | 0.00 | 0.00 | 0.349759E+11 | 0.265269E+11 | 84965.80 | 27-JUN-07:40 | 36730.06 | 0.00 |
July | 0.00 | 0.00 | 0.605083E+11 | 0.427601E+11 | 109879.33 | 20-JUL-04:03 | 44393.01 | 0.00 |
August | 0.00 | 0.00 | 0.494184E+11 | 0.382276E+11 | 109713.50 | 14-AUG-04:02 | 40770.45 | 0.00 |
September | 0.00 | 0.00 | 0.209809E+11 | 0.157346E+11 | 72972.60 | 15-SEP-11:00 | 40179.34 | 0.00 |
October | 0.00 | 0.00 | 0.221312E+10 | 0.183683E+10 | 25578.27 | 11-OCT-15:00 | 25578.27 | 0.00 |
November | 0.00 | 0.00 | 0.380973E+09 | 0.264720E+09 | 8941.35 | 16-NOV-18:00 | 6447.59 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.178377E+12 | 0.134150E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.605083E+11 | 0.427601E+11 | 109879.33 | 44393.01 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.202180E+10 | 0.169064E+10 | 38623.37 | 15-MAR-14:00 | 38623.37 | 0.00 |
April | 0.00 | 0.00 | 0.663087E+09 | 0.586878E+09 | 13937.20 | 08-APR-13:30 | 11746.93 | 0.00 |
May | 0.00 | 0.00 | 0.773543E+10 | 0.690879E+10 | 43850.57 | 10-MAY-14:30 | 43850.57 | 0.00 |
June | 0.00 | 0.00 | 0.371763E+11 | 0.280503E+11 | 122643.29 | 27-JUN-14:55 | 53940.95 | 0.00 |
July | 0.00 | 0.00 | 0.646039E+11 | 0.457896E+11 | 122720.51 | 20-JUL-05:03 | 48643.12 | 0.00 |
August | 0.00 | 0.00 | 0.519432E+11 | 0.401179E+11 | 122703.17 | 14-AUG-04:02 | 45665.42 | 0.00 |
September | 0.00 | 0.00 | 0.211470E+11 | 0.154993E+11 | 85919.48 | 15-SEP-12:30 | 47825.28 | 0.00 |
October | 0.00 | 0.00 | 0.214142E+10 | 0.171966E+10 | 25029.75 | 11-OCT-15:00 | 25029.75 | 0.00 |
November | 0.00 | 0.00 | 0.404647E+09 | 0.276534E+09 | 9693.22 | 27-NOV-07:03 | 8259.98 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.187837E+12 | 0.140640E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.646039E+11 | 0.457896E+11 | 122720.51 | 53940.95 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1975.70 | 6956.66 | 31-JAN-12:18 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2013.91 | 6979.92 | 16-FEB-12:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2118.79 | 6958.18 | 01-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1905.70 | 6735.25 | 04-APR-11:09 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1871.98 | 6418.54 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1809.34 | 6032.98 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1585.60 | 5668.32 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1712.99 | 5522.30 | 31-AUG-11:06 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1627.11 | 5690.54 | 28-SEP-11:09 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1700.12 | 6030.79 | 30-OCT-11:09 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1827.64 | 6409.54 | 29-NOV-12:07 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1851.02 | 6740.87 | 29-DEC-12:13 |
Annual Sum or Average | 0.00 | 1832.29 | ||||
Minimum of Months | 0.00 | 0.00 | 1585.60 | 5522.30 | ||
Maximum of Months | 0.00 | 0.00 | 2118.79 | 6979.92 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154932E+10 | 0.33 | 2623.51 | 02-JAN-05:01 | 0.81 |
February | 0.138342E+10 | 0.32 | 2623.51 | 06-FEB-07:01 | 0.81 |
March | 0.160632E+10 | 0.32 | 2254.79 | 17-MAR-05:03 | 0.74 |
April | 0.165083E+10 | 0.31 | 2643.57 | 13-APR-07:04 | 0.81 |
May | 0.248870E+10 | 0.36 | 4491.07 | 15-MAY-05:03 | 1.09 |
June | 0.431928E+10 | 0.50 | 8531.76 | 12-JUN-15:10 | 1.60 |
July | 0.558741E+10 | 0.55 | 11240.00 | 17-JUL-04:02 | 1.91 |
August | 0.563933E+10 | 0.56 | 11240.00 | 14-AUG-04:02 | 1.91 |
September | 0.372745E+10 | 0.45 | 8689.64 | 18-SEP-12:10 | 1.63 |
October | 0.201051E+10 | 0.32 | 4491.07 | 02-OCT-05:02 | 1.09 |
November | 0.147438E+10 | 0.29 | 2662.43 | 02-NOV-07:02 | 0.81 |
December | 0.141604E+10 | 0.30 | 2623.51 | 11-DEC-07:01 | 0.81 |
Annual Sum or Average | 0.328530E+11 | 0.39 | |||
Minimum of Months | 0.138342E+10 | 0.29 | 2254.79 | 0.74 | |
Maximum of Months | 0.563933E+10 | 0.56 | 11240.00 | 1.91 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.159622E+10 | 0.35 | 2615.72 | 02-JAN-05:01 | 0.86 |
February | 0.142730E+10 | 0.34 | 2615.72 | 01-FEB-07:01 | 0.86 |
March | 0.153289E+10 | 0.33 | 2763.77 | 15-MAR-13:40 | 0.88 |
April | 0.144938E+10 | 0.31 | 2616.31 | 21-APR-15:20 | 0.86 |
May | 0.226783E+10 | 0.37 | 4947.44 | 23-MAY-14:30 | 1.24 |
June | 0.416369E+10 | 0.52 | 8835.74 | 12-JUN-15:30 | 1.77 |
July | 0.523199E+10 | 0.56 | 10086.97 | 17-JUL-04:02 | 1.92 |
August | 0.496944E+10 | 0.55 | 10086.97 | 14-AUG-04:02 | 1.92 |
September | 0.293430E+10 | 0.42 | 7275.05 | 21-SEP-15:40 | 1.57 |
October | 0.153376E+10 | 0.30 | 3366.04 | 11-OCT-15:20 | 0.98 |
November | 0.128378E+10 | 0.29 | 2615.72 | 20-NOV-07:01 | 0.86 |
December | 0.149852E+10 | 0.33 | 2615.72 | 04-DEC-06:01 | 0.86 |
Annual Sum or Average | 0.298891E+11 | 0.39 | |||
Minimum of Months | 0.128378E+10 | 0.29 | 2615.72 | 0.86 | |
Maximum of Months | 0.523199E+10 | 0.56 | 10086.97 | 1.92 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.202177E+10 | 0.41 | 2587.15 | 09-JAN-07:02 | 0.79 |
February | 0.185122E+10 | 0.41 | 2587.15 | 06-FEB-07:04 | 0.79 |
March | 0.171047E+10 | 0.35 | 3016.73 | 15-MAR-13:50 | 0.85 |
April | 0.147930E+10 | 0.30 | 2587.15 | 03-APR-06:01 | 0.79 |
May | 0.211183E+10 | 0.34 | 4782.35 | 31-MAY-16:00 | 1.11 |
June | 0.384590E+10 | 0.46 | 11584.60 | 27-JUN-14:55 | 1.90 |
July | 0.486678E+10 | 0.50 | 11584.60 | 17-JUL-04:02 | 1.91 |
August | 0.447444E+10 | 0.49 | 11584.60 | 15-AUG-14:20 | 1.91 |
September | 0.252036E+10 | 0.37 | 6864.29 | 21-SEP-15:30 | 1.38 |
October | 0.148760E+10 | 0.29 | 2774.86 | 11-OCT-15:20 | 0.81 |
November | 0.137621E+10 | 0.30 | 2587.15 | 14-NOV-06:01 | 0.79 |
December | 0.189834E+10 | 0.39 | 2587.15 | 04-DEC-07:01 | 0.79 |
Annual Sum or Average | 0.296442E+11 | 0.38 | |||
Minimum of Months | 0.137621E+10 | 0.29 | 2587.15 | 0.79 | |
Maximum of Months | 0.486678E+10 | 0.50 | 11584.60 | 1.91 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:03 | 0.22 | 0.22 | 57.46 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:01 | 0.22 | 0.22 | 55.38 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:01 | 0.22 | 0.22 | 55.75 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:02 | 0.22 | 0.22 | 56.35 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:03 | 0.22 | 0.22 | 56.01 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 55.98 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 56.34 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 56.55 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 56.67 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 57.44 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:03 | 0.22 | 0.22 | 55.51 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:01 | 0.22 | 0.22 | 55.65 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 55.38 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.46 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.34 | 57.34 | 1975.70 | 6956.66 | 31-JAN-12:18 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 55.84 | 55.84 | 2013.91 | 6979.92 | 16-FEB-12:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.24 | 56.24 | 2118.79 | 6958.18 | 01-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.84 | 56.84 | 1905.70 | 6735.25 | 04-APR-11:09 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.66 | 57.66 | 1871.98 | 6418.54 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.33 | 57.33 | 1809.34 | 6032.98 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.77 | 56.77 | 1585.60 | 5668.32 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.58 | 57.58 | 1712.99 | 5522.30 | 31-AUG-11:06 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.09 | 57.09 | 1627.11 | 5690.54 | 28-SEP-11:09 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.34 | 55.34 | 1700.12 | 6030.79 | 30-OCT-11:09 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.00 | 56.00 | 1827.64 | 6409.54 | 29-NOV-12:07 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.07 | 56.07 | 1851.02 | 6740.87 | 29-DEC-12:13 |
Annual Sum or Average | 0.00 | 1832.29 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.34 | 55.34 | 1585.60 | 5522.30 | ||
Maximum of Months | 0.00 | 0.00 | 57.66 | 57.66 | 2118.79 | 6979.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.263278E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.221979E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.132792E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.633392E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.580092E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.137613E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.216590E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.194958E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.102872E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.478625E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.767934E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.206841E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.172293E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.478625E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.263278E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.229141E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.193824E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.795678E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.277563E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.419478E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.127033E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.198254E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.169711E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.807298E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.276748E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.549363E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.194846E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.142542E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.276748E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.229141E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.376686E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.327108E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.155697E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.538737E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.428840E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.129550E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.204999E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.171579E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.782729E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.503222E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.120678E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.341559E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.205321E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.428840E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.376686E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154932E+10 | 0.00 | 0.410361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138342E+10 | 0.00 | 0.358721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160632E+10 | 0.191964E+10 | 0.190257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165083E+10 | 0.641863E+09 | 0.603378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.248870E+10 | 0.739141E+10 | 0.141749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.431928E+10 | 0.371018E+11 | 0.375387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.558741E+10 | 0.662732E+11 | 79117572.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.563933E+10 | 0.564293E+11 | 0.183363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.372745E+10 | 0.247910E+11 | 0.536894E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201051E+10 | 0.258184E+10 | 0.268294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147438E+10 | 0.430241E+09 | 0.911921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141604E+10 | 0.00 | 0.329825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.328530E+11 | 0.197560E+12 | 0.149345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138342E+10 | 0.00 | 79117572.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.563933E+10 | 0.662732E+11 | 0.410361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.159622E+10 | 0.00 | 0.383631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142730E+10 | 0.00 | 0.337510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153289E+10 | 0.182828E+10 | 0.149675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144938E+10 | 0.641270E+09 | 0.352621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.226783E+10 | 0.743017E+10 | 65084567.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.416369E+10 | 0.349759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.523199E+10 | 0.605083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.496944E+10 | 0.494184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.293430E+10 | 0.209809E+11 | 15959519.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153376E+10 | 0.221312E+10 | 0.184868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128378E+10 | 0.380973E+09 | 0.875794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149852E+10 | 0.00 | 0.327979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.298891E+11 | 0.178377E+12 | 0.134093E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.523199E+10 | 0.605083E+11 | 0.383631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.202177E+10 | 0.00 | 0.540399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185122E+10 | 0.00 | 0.478702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171047E+10 | 0.202180E+10 | 0.226173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147930E+10 | 0.663087E+09 | 0.628679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.211183E+10 | 0.773543E+10 | 0.283073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.384590E+10 | 0.371763E+11 | 6378230.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.486678E+10 | 0.646039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.447444E+10 | 0.519432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252036E+10 | 0.211470E+11 | 0.118139E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148760E+10 | 0.214142E+10 | 0.446457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137621E+10 | 0.404647E+09 | 0.156275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189834E+10 | 0.00 | 0.483183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296442E+11 | 0.187837E+12 | 0.199632E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.486678E+10 | 0.646039E+11 | 0.540399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.154932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160632E+10 | 0.00 | 0.00 | 0.00 | 0.491267E+09 | 0.111816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165083E+10 | 0.00 | 0.00 | 0.00 | 0.178456E+09 | 0.450463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.248870E+10 | 0.00 | 0.00 | 0.00 | 0.191888E+10 | 0.139334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.431928E+10 | 0.00 | 0.00 | 0.00 | 0.906663E+10 | 0.375387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.558741E+10 | 0.00 | 0.00 | 0.00 | 0.159924E+11 | 79117572.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.563933E+10 | 0.00 | 0.00 | 0.00 | 0.136731E+11 | 0.183363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.372745E+10 | 0.00 | 0.00 | 0.00 | 0.602461E+10 | 0.535176E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201051E+10 | 0.00 | 0.00 | 0.00 | 0.686294E+09 | 0.208944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147438E+10 | 0.00 | 0.00 | 0.00 | 0.119827E+09 | 0.608513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.328530E+11 | 0.00 | 0.00 | 0.00 | 0.481515E+11 | 0.912882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79117572.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.563933E+10 | 0.00 | 0.00 | 0.00 | 0.159924E+11 | 0.247785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.159622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153289E+10 | 0.00 | 0.00 | 0.00 | 0.464634E+09 | 0.595926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144938E+10 | 0.00 | 0.00 | 0.00 | 0.178016E+09 | 0.114824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.226783E+10 | 0.00 | 0.00 | 0.00 | 0.191977E+10 | 7169922.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.416369E+10 | 0.00 | 0.00 | 0.00 | 0.853966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.523199E+10 | 0.00 | 0.00 | 0.00 | 0.145934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.496944E+10 | 0.00 | 0.00 | 0.00 | 0.120017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.293430E+10 | 0.00 | 0.00 | 0.00 | 0.513486E+10 | 3821531.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153376E+10 | 0.00 | 0.00 | 0.00 | 0.594172E+09 | 0.639548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128378E+10 | 0.00 | 0.00 | 0.00 | 0.106434E+09 | 0.410342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.298891E+11 | 0.00 | 0.00 | 0.00 | 0.435327E+11 | 0.691206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.523199E+10 | 0.00 | 0.00 | 0.00 | 0.145934E+11 | 0.213179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.202177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171047E+10 | 0.00 | 0.00 | 0.00 | 0.513139E+09 | 0.133461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147930E+10 | 0.00 | 0.00 | 0.00 | 0.184645E+09 | 0.372342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.211183E+10 | 0.00 | 0.00 | 0.00 | 0.200800E+10 | 0.168567E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.384590E+10 | 0.00 | 0.00 | 0.00 | 0.910689E+10 | 2170501.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.486678E+10 | 0.00 | 0.00 | 0.00 | 0.156331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.447444E+10 | 0.00 | 0.00 | 0.00 | 0.126835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252036E+10 | 0.00 | 0.00 | 0.00 | 0.522437E+10 | 82552424.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148760E+10 | 0.00 | 0.00 | 0.00 | 0.581023E+09 | 0.296359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137621E+10 | 0.00 | 0.00 | 0.00 | 0.113369E+09 | 0.105783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296442E+11 | 0.00 | 0.00 | 0.00 | 0.460480E+11 | 0.129629E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.486678E+10 | 0.00 | 0.00 | 0.00 | 0.156331E+11 | 0.356468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145214E+11 | 0.00 | 0.00 | 1045814.82 | 0.00 | 0.409227E+09 | 0.194894E+10 | 0.00 | 0.27 |
February | 0.135002E+11 | 0.00 | 0.00 | 1282928.15 | 0.00 | 16432711.42 | 0.223703E+10 | 0.00 | 0.28 |
March | 0.731569E+10 | 9092723.50 | 0.00 | 17572067.74 | 0.00 | 729119.04 | 0.941642E+10 | 0.00 | 0.39 |
April | 0.285412E+10 | 0.00 | 0.00 | 25636527.19 | 0.00 | 0.00 | 0.136008E+11 | 0.00 | 0.49 |
May | 0.965311E+09 | 2009159.83 | 0.00 | 40487864.40 | 6981825.97 | 0.00 | 0.190533E+11 | 0.00 | 0.90 |
June | 0.683042E+09 | 0.175356E+10 | 0.00 | 35255769.63 | 0.178007E+09 | 0.00 | 0.121161E+11 | 0.00 | 1.11 |
July | 0.335870E+09 | 0.606108E+10 | 0.00 | 19095386.07 | 0.417932E+09 | 0.00 | 0.378734E+10 | 0.00 | 0.89 |
August | 0.587072E+09 | 0.344986E+10 | 0.00 | 34301375.26 | 0.148994E+09 | 0.00 | 0.800522E+10 | 0.00 | 1.07 |
September | 0.132549E+10 | 0.119412E+10 | 0.00 | 36542180.94 | 24970917.30 | 0.00 | 0.143873E+11 | 0.00 | 1.11 |
October | 0.130141E+10 | 0.00 | 0.00 | 34223158.46 | 420233.78 | 0.00 | 0.173890E+11 | 0.00 | 0.63 |
November | 0.417183E+10 | 0.00 | 0.00 | 21680342.89 | 3665761.63 | 0.00 | 0.107746E+11 | 0.00 | 0.38 |
December | 0.115417E+11 | 0.00 | 0.00 | 4663659.56 | 0.00 | 10404435.25 | 0.465368E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.591030E+11 | 0.124697E+11 | 0.00 | 0.271787E+09 | 0.780972E+09 | 0.436793E+09 | 0.117370E+12 | 0.00 | 0.65 |
Minimum of Months | 0.335870E+09 | 0.00 | 0.00 | 1045814.82 | 0.00 | 0.00 | 0.194894E+10 | 0.00 | 0.27 |
Maximum of Months | 0.145214E+11 | 0.606108E+10 | 0.00 | 40487864.40 | 0.417932E+09 | 0.409227E+09 | 0.190533E+11 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.137476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282062E+10 | 0.00 | 0.00 | 0.27 |
February | 0.126897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259124E+10 | 0.00 | 0.00 | 0.28 |
March | 0.133355E+11 | 1816749.29 | 0.00 | 1721595.92 | 5840048.54 | 0.222826E+09 | 0.926758E+09 | 0.00 | 0.33 |
April | 0.839864E+10 | 0.00 | 0.00 | 3976148.77 | 0.00 | 42408746.74 | 0.352882E+10 | 0.00 | 0.36 |
May | 0.369665E+10 | 682790.88 | 0.00 | 17693905.36 | 21508963.61 | 0.00 | 0.973673E+10 | 0.00 | 0.60 |
June | 0.897519E+09 | 0.127324E+10 | 0.00 | 21578757.36 | 0.170259E+09 | 0.00 | 0.782693E+10 | 0.00 | 0.78 |
July | 0.492737E+09 | 0.443639E+10 | 0.00 | 12828641.40 | 0.444472E+09 | 0.00 | 0.245048E+10 | 0.00 | 0.66 |
August | 0.690368E+09 | 0.243974E+10 | 0.00 | 22162154.40 | 0.149574E+09 | 0.00 | 0.512744E+10 | 0.00 | 0.74 |
September | 0.211749E+10 | 0.773888E+09 | 0.00 | 18812719.89 | 23609516.03 | 0.00 | 0.787716E+10 | 0.00 | 0.72 |
October | 0.702746E+10 | 0.00 | 0.00 | 6641006.22 | 1859286.65 | 554667.40 | 0.470855E+10 | 0.00 | 0.40 |
November | 0.108106E+11 | 0.00 | 0.00 | 312553.81 | 6873521.45 | 63730651.03 | 0.561237E+09 | 0.00 | 0.30 |
December | 0.137472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175201E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.876515E+11 | 0.892576E+10 | 0.00 | 0.105727E+09 | 0.823997E+09 | 0.749339E+10 | 0.427441E+11 | 0.00 | 0.48 |
Minimum of Months | 0.492737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.137476E+11 | 0.443639E+10 | 0.00 | 22162154.40 | 0.444472E+09 | 0.282062E+10 | 0.973673E+10 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.778152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745495E+10 | 0.00 | 0.00 | 0.26 |
February | 0.793720E+10 | 0.00 | 0.00 | 0.00 | 36396.24 | 0.623630E+10 | 0.00 | 0.00 | 0.26 |
March | 0.110244E+11 | 265085.10 | 0.00 | 1358830.41 | 595014.68 | 0.182515E+10 | 0.759053E+09 | 0.00 | 0.33 |
April | 0.941582E+10 | 0.00 | 0.00 | 1739986.41 | 0.00 | 0.224148E+09 | 0.200353E+10 | 0.00 | 0.35 |
May | 0.482293E+10 | 824740.03 | 0.00 | 14370025.87 | 23129126.26 | 587376.99 | 0.838415E+10 | 0.00 | 0.59 |
June | 0.146739E+10 | 0.133857E+10 | 0.00 | 19742313.02 | 0.227325E+09 | 0.00 | 0.732707E+10 | 0.00 | 0.82 |
July | 0.538027E+09 | 0.453153E+10 | 0.00 | 11688020.67 | 0.457472E+09 | 0.00 | 0.227503E+10 | 0.00 | 0.71 |
August | 0.999407E+09 | 0.244474E+10 | 0.00 | 18801760.72 | 0.222996E+09 | 0.00 | 0.436587E+10 | 0.00 | 0.77 |
September | 0.321604E+10 | 0.766520E+09 | 0.00 | 13352129.91 | 50120960.62 | 0.00 | 0.578554E+10 | 0.00 | 0.69 |
October | 0.830473E+10 | 0.00 | 0.00 | 2712543.79 | 16420.86 | 0.134270E+09 | 0.235278E+10 | 0.00 | 0.38 |
November | 0.988332E+10 | 0.00 | 541885.15 | 361.84 | 10755504.70 | 0.741375E+09 | 15515435.03 | 40178.76 | 0.30 |
December | 0.822736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595175E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.736181E+11 | 0.908246E+10 | 541885.15 | 83765972.65 | 0.992446E+09 | 0.225685E+11 | 0.332685E+11 | 40178.76 | 0.48 |
Minimum of Months | 0.538027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.110244E+11 | 0.453153E+10 | 541885.15 | 19742313.02 | 0.457472E+09 | 0.745495E+10 | 0.838415E+10 | 40178.76 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 45803254.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372266E+10 | 0.00 | 0.00 | 0.30 |
February | 82500113.62 | 0.00 | 987.63 | 0.00 | 783.13 | 0.342103E+10 | 0.00 | 6925.31 | 0.30 |
March | 0.932982E+09 | 160922.65 | 0.00 | 252391.72 | 20238.22 | 0.199980E+10 | 83423602.52 | 0.00 | 0.34 |
April | 0.173373E+10 | 0.00 | 0.00 | 200304.10 | 0.00 | 0.522298E+09 | 0.205320E+09 | 0.00 | 0.35 |
May | 0.137703E+10 | 0.00 | 0.00 | 2768851.37 | 5020191.87 | 17841036.40 | 0.141093E+10 | 0.00 | 0.62 |
June | 0.385215E+09 | 0.434193E+09 | 0.00 | 4938156.58 | 47785549.71 | 0.00 | 0.164449E+10 | 0.00 | 1.00 |
July | 0.133884E+09 | 0.140884E+10 | 0.00 | 3010003.13 | 88372673.56 | 0.00 | 0.561293E+09 | 0.00 | 0.92 |
August | 0.320166E+09 | 0.718292E+09 | 0.00 | 4520291.63 | 43871514.07 | 0.00 | 0.931300E+09 | 0.00 | 0.93 |
September | 0.945507E+09 | 0.192160E+09 | 0.00 | 2431707.79 | 17316280.33 | 8685201.40 | 0.929760E+09 | 0.00 | 0.73 |
October | 0.167895E+10 | 0.00 | 0.00 | 262282.47 | 3458.69 | 0.391891E+09 | 0.195574E+09 | 0.00 | 0.38 |
November | 0.787524E+09 | 0.00 | 314574.51 | 0.00 | 2099823.93 | 0.148665E+10 | 0.00 | 11207.92 | 0.30 |
December | 0.129009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331402E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.855230E+10 | 0.275364E+10 | 315562.14 | 18383988.79 | 0.204491E+09 | 0.148849E+11 | 0.596209E+10 | 18133.24 | 0.54 |
Minimum of Months | 45803254.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.173373E+10 | 0.140884E+10 | 314574.51 | 4938156.58 | 88372673.56 | 0.372266E+10 | 0.164449E+10 | 11207.92 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 53683069.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306760E+10 | 0.00 | 0.00 | 0.40 |
February | 0.438139E+09 | 0.00 | 841.24 | 0.00 | 1807.17 | 0.248296E+10 | 0.00 | 5816.41 | 0.41 |
March | 0.143480E+10 | 221609.19 | 0.00 | 278763.91 | 0.00 | 0.117588E+10 | 0.103966E+09 | 0.00 | 0.49 |
April | 0.141828E+10 | 0.00 | 0.00 | 1287409.09 | 0.00 | 0.272325E+09 | 0.825830E+09 | 0.00 | 0.58 |
May | 0.100526E+10 | 0.00 | 0.00 | 4183707.44 | 4740439.13 | 4692846.71 | 0.222157E+10 | 0.00 | 1.11 |
June | 0.324504E+09 | 0.399299E+09 | 0.00 | 5506802.37 | 28122833.32 | 0.00 | 0.210412E+10 | 0.00 | 1.60 |
July | 91905629.13 | 0.117511E+10 | 0.00 | 4341033.00 | 88657789.76 | 0.00 | 0.841523E+09 | 0.00 | 1.49 |
August | 0.250982E+09 | 0.563464E+09 | 0.00 | 5092841.33 | 49676956.70 | 0.00 | 0.111634E+10 | 0.00 | 1.47 |
September | 0.757418E+09 | 0.164537E+09 | 0.00 | 3305014.61 | 21470578.10 | 4551290.85 | 0.139583E+10 | 0.00 | 1.23 |
October | 0.155105E+10 | 0.00 | 0.00 | 496113.48 | 3265.95 | 0.262892E+09 | 0.338777E+09 | 0.00 | 0.57 |
November | 0.893508E+09 | 0.00 | 265939.21 | 0.00 | 1982810.18 | 0.122940E+10 | 0.00 | 7262.80 | 0.45 |
December | 0.136004E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276600E+10 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.835554E+10 | 0.230263E+10 | 266780.44 | 24491685.23 | 0.194656E+09 | 0.112663E+11 | 0.894796E+10 | 13079.22 | 0.85 |
Minimum of Months | 53683069.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.155105E+10 | 0.117511E+10 | 265939.21 | 5506802.37 | 88657789.76 | 0.306760E+10 | 0.222157E+10 | 7262.80 | 1.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.816927E+09 | 0.00 | 0.00 | 132815.30 | 0.00 | 0.314509E+10 | 0.104939E+09 | 0.00 | 0.33 |
February | 0.939631E+09 | 0.00 | 1176.16 | 383074.15 | 2284.56 | 0.272755E+10 | 0.214564E+09 | 7240.23 | 0.34 |
March | 0.161851E+10 | 823032.94 | 0.00 | 1916141.68 | 0.00 | 0.121523E+10 | 0.926699E+09 | 0.00 | 0.46 |
April | 0.159979E+10 | 0.00 | 0.00 | 2834430.23 | 0.00 | 0.445946E+09 | 0.168323E+10 | 0.00 | 0.56 |
May | 0.136751E+10 | 4153564.03 | 0.00 | 5725732.76 | 2015553.14 | 33415891.38 | 0.282534E+10 | 0.00 | 0.94 |
June | 0.539960E+09 | 0.504961E+09 | 0.00 | 6330089.14 | 44147809.97 | 326159.03 | 0.215697E+10 | 0.00 | 1.25 |
July | 0.191344E+09 | 0.167308E+10 | 0.00 | 3915951.03 | 0.106968E+09 | 0.00 | 0.697944E+09 | 0.00 | 1.12 |
August | 0.388118E+09 | 0.892985E+09 | 0.00 | 6884720.37 | 43595005.42 | 0.00 | 0.135867E+10 | 0.00 | 1.28 |
September | 0.820700E+09 | 0.289212E+09 | 0.00 | 6957388.16 | 18648723.69 | 5717651.46 | 0.265196E+10 | 0.00 | 1.32 |
October | 0.159155E+10 | 0.00 | 0.00 | 3743548.24 | 4128.71 | 0.255125E+09 | 0.180773E+10 | 0.00 | 0.68 |
November | 0.124555E+10 | 0.00 | 358817.30 | 902534.69 | 2506602.49 | 0.115787E+10 | 0.466004E+09 | 9755.32 | 0.38 |
December | 0.641525E+09 | 0.00 | 0.00 | 66853.51 | 0.00 | 0.303750E+10 | 69310718.46 | 0.00 | 0.33 |
Annual Sum or Average | 0.117611E+11 | 0.336521E+10 | 359993.45 | 39793279.24 | 0.217888E+09 | 0.120238E+11 | 0.149634E+11 | 16995.55 | 0.75 |
Minimum of Months | 0.191344E+09 | 0.00 | 0.00 | 66853.51 | 0.00 | 0.00 | 69310718.46 | 0.00 | 0.33 |
Maximum of Months | 0.161851E+10 | 0.167308E+10 | 358817.30 | 6957388.16 | 0.106968E+09 | 0.314509E+10 | 0.282534E+10 | 9755.32 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.199735E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322595E+10 | 0.00 | 0.00 | 0.44 |
February | 0.327891E+09 | 0.00 | 923.44 | 3724.39 | 1998.60 | 0.287741E+10 | 9613970.96 | 6401.48 | 0.45 |
March | 0.135795E+10 | 15675.91 | 0.00 | 365392.01 | 173510.56 | 0.149236E+10 | 0.164956E+09 | 0.00 | 0.54 |
April | 0.157569E+10 | 0.00 | 0.00 | 1309849.98 | 0.00 | 0.468414E+09 | 0.821896E+09 | 0.00 | 0.66 |
May | 0.137798E+10 | 935325.74 | 0.00 | 3858819.48 | 4354471.24 | 21700124.12 | 0.202191E+10 | 0.00 | 1.18 |
June | 0.509505E+09 | 0.395823E+09 | 0.00 | 5674793.57 | 45729301.20 | 285333.33 | 0.175487E+10 | 0.00 | 1.65 |
July | 0.176315E+09 | 0.119565E+10 | 0.00 | 3046391.01 | 95142221.50 | 0.00 | 0.469490E+09 | 0.00 | 1.34 |
August | 0.393752E+09 | 0.596792E+09 | 0.00 | 4366084.46 | 48686092.61 | 0.00 | 0.784441E+09 | 0.00 | 1.39 |
September | 0.986660E+09 | 0.146028E+09 | 0.00 | 2865796.97 | 31774367.83 | 10464166.80 | 0.110215E+10 | 0.00 | 1.22 |
October | 0.171834E+10 | 0.00 | 0.00 | 658604.37 | 3611.91 | 0.357936E+09 | 0.356575E+09 | 0.00 | 0.66 |
November | 0.944268E+09 | 0.00 | 286348.18 | 9529.61 | 2192848.19 | 0.137763E+10 | 23493265.59 | 7600.90 | 0.49 |
December | 0.217350E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296590E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.978543E+10 | 0.233525E+10 | 287271.63 | 22158985.85 | 0.228058E+09 | 0.127980E+11 | 0.750939E+10 | 14002.38 | 0.87 |
Minimum of Months | 0.176315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.171834E+10 | 0.119565E+10 | 286348.18 | 5674793.57 | 95142221.50 | 0.322595E+10 | 0.202191E+10 | 7600.90 | 1.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 76554462.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378227E+10 | 0.00 | 0.00 | 0.29 |
February | 81016237.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353999E+10 | 0.00 | 0.00 | 0.30 |
March | 0.108410E+10 | 0.00 | 0.00 | 13678.31 | 1322032.03 | 0.209994E+10 | 9779386.15 | 0.00 | 0.33 |
April | 0.202749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494015E+09 | 0.00 | 0.00 | 0.35 |
May | 0.199011E+10 | 614.30 | 0.00 | 624593.95 | 1762437.53 | 5229175.45 | 0.403367E+09 | 0.00 | 0.50 |
June | 0.498896E+09 | 0.287371E+09 | 0.00 | 3070413.24 | 49583055.20 | 0.00 | 0.107848E+10 | 0.00 | 0.73 |
July | 0.169321E+09 | 0.105341E+10 | 0.00 | 2165683.72 | 0.118024E+09 | 0.00 | 0.421247E+09 | 0.00 | 0.69 |
August | 0.370379E+09 | 0.608566E+09 | 0.00 | 3827490.80 | 46825347.64 | 0.00 | 0.811294E+09 | 0.00 | 0.79 |
September | 0.973287E+09 | 0.180104E+09 | 0.00 | 2443058.03 | 10198364.83 | 0.00 | 0.100171E+10 | 0.00 | 0.70 |
October | 0.215652E+10 | 0.00 | 0.00 | 379978.25 | 88642.26 | 45663064.46 | 0.282347E+09 | 0.00 | 0.39 |
November | 0.188375E+10 | 0.00 | 5525.45 | 0.00 | 764347.05 | 0.619508E+09 | 0.00 | 4179.54 | 0.30 |
December | 0.356247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319253E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.116677E+11 | 0.212945E+10 | 5525.45 | 12524896.31 | 0.228568E+09 | 0.137791E+11 | 0.400823E+10 | 4179.54 | 0.47 |
Minimum of Months | 76554462.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.215652E+10 | 0.105341E+10 | 5525.45 | 3827490.80 | 0.118024E+09 | 0.378227E+10 | 0.107848E+10 | 4179.54 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 92152770.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276856E+10 | 0.00 | 0.00 | 0.35 |
February | 0.347827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234002E+10 | 0.00 | 0.00 | 0.35 |
March | 0.137444E+10 | 775380.74 | 0.00 | 66834.17 | 248436.29 | 0.102927E+10 | 19452021.44 | 0.00 | 0.40 |
April | 0.140322E+10 | 0.00 | 0.00 | 691930.10 | 0.00 | 0.165098E+09 | 0.481012E+09 | 0.00 | 0.45 |
May | 0.947886E+09 | 66730.79 | 0.00 | 2636020.62 | 1298724.40 | 689428.38 | 0.138428E+10 | 0.00 | 0.80 |
June | 0.276040E+09 | 0.286908E+09 | 0.00 | 4362667.73 | 29288566.50 | 0.00 | 0.160152E+10 | 0.00 | 1.23 |
July | 0.105394E+09 | 0.962162E+09 | 0.00 | 3432366.66 | 83574575.36 | 0.00 | 0.680314E+09 | 0.00 | 1.16 |
August | 0.234220E+09 | 0.518300E+09 | 0.00 | 4757879.37 | 28902282.76 | 0.00 | 0.103547E+10 | 0.00 | 1.26 |
September | 0.566605E+09 | 0.159906E+09 | 0.00 | 3737252.24 | 6137724.94 | 0.00 | 0.154116E+10 | 0.00 | 1.15 |
October | 0.141482E+10 | 0.00 | 0.00 | 1000685.19 | 68646.94 | 20958467.28 | 0.586208E+09 | 0.00 | 0.51 |
November | 0.151868E+10 | 0.00 | 4880.77 | 10135.87 | 591930.84 | 0.401863E+09 | 18860850.42 | 2005.84 | 0.37 |
December | 0.294574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238801E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.857587E+10 | 0.192812E+10 | 4880.77 | 20695771.95 | 0.150111E+09 | 0.911447E+10 | 0.734829E+10 | 2005.84 | 0.70 |
Minimum of Months | 92152770.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.151868E+10 | 0.962162E+09 | 4880.77 | 4757879.37 | 83574575.36 | 0.276856E+10 | 0.160152E+10 | 2005.84 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582004E+10 | 0.00 | 0.00 | 0.44 |
February | 0.164135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521819E+10 | 0.00 | 0.00 | 0.44 |
March | 0.838210E+09 | 2724501.21 | 0.00 | 206072.74 | 70650.63 | 0.324169E+10 | 11082976.86 | 0.00 | 0.42 |
April | 0.130129E+10 | 0.00 | 0.00 | 277365.01 | 0.00 | 0.153959E+10 | 0.199390E+09 | 0.00 | 0.41 |
May | 0.168963E+10 | 152739.44 | 0.00 | 1069860.02 | 1605945.29 | 0.576895E+09 | 0.455803E+09 | 0.00 | 0.58 |
June | 0.833902E+09 | 0.348309E+09 | 0.00 | 2355778.33 | 60084489.50 | 0.155696E+09 | 0.642558E+09 | 0.00 | 0.78 |
July | 0.223069E+09 | 0.134483E+10 | 0.00 | 2245963.85 | 0.116427E+09 | 38167186.48 | 0.344577E+09 | 0.00 | 0.78 |
August | 0.449814E+09 | 0.836355E+09 | 0.00 | 4866716.58 | 39282685.48 | 87355931.37 | 0.771689E+09 | 0.00 | 0.99 |
September | 0.813588E+09 | 0.256775E+09 | 0.00 | 4992229.19 | 11760530.31 | 0.230129E+09 | 0.171091E+10 | 0.00 | 1.06 |
October | 0.155990E+10 | 33416.87 | 0.00 | 1523099.65 | 70416.15 | 0.859993E+09 | 0.782674E+09 | 0.00 | 0.54 |
November | 0.884789E+09 | 0.00 | 8420.48 | 92943.91 | 758665.08 | 0.214658E+10 | 89906822.60 | 3979.58 | 0.37 |
December | 0.188623E+09 | 0.00 | 0.00 | 7919.90 | 0.00 | 0.508817E+10 | 10580625.47 | 0.00 | 0.41 |
Annual Sum or Average | 0.907899E+10 | 0.278918E+10 | 8420.48 | 17637949.18 | 0.230061E+09 | 0.250025E+11 | 0.501917E+10 | 3979.58 | 0.60 |
Minimum of Months | 0.132039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38167186.48 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.168963E+10 | 0.134483E+10 | 8420.48 | 4992229.19 | 0.116427E+09 | 0.582004E+10 | 0.171091E+10 | 3979.58 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.198246E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281183E+10 | 0.00 | 0.00 | 0.36 |
February | 0.282790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255129E+10 | 0.00 | 0.00 | 0.37 |
March | 0.133789E+10 | 0.00 | 0.00 | 37455.14 | 1079663.68 | 0.121063E+10 | 12952644.93 | 0.00 | 0.42 |
April | 0.156665E+10 | 0.00 | 0.00 | 573780.15 | 0.00 | 0.235754E+09 | 0.345775E+09 | 0.00 | 0.48 |
May | 0.124381E+10 | 246609.66 | 0.00 | 2136688.02 | 1315225.63 | 2861156.77 | 0.107518E+10 | 0.00 | 0.81 |
June | 0.356286E+09 | 0.300118E+09 | 0.00 | 4151671.86 | 34186855.25 | 0.00 | 0.133293E+10 | 0.00 | 1.24 |
July | 0.143858E+09 | 0.984326E+09 | 0.00 | 2451849.50 | 69823262.61 | 0.00 | 0.387014E+09 | 0.00 | 1.01 |
August | 0.281631E+09 | 0.576174E+09 | 0.00 | 3921000.45 | 21943636.16 | 0.00 | 0.750670E+09 | 0.00 | 1.16 |
September | 0.668892E+09 | 0.144373E+09 | 0.00 | 3271541.04 | 7757218.47 | 0.00 | 0.121462E+10 | 0.00 | 1.07 |
October | 0.161038E+10 | 0.00 | 0.00 | 796842.81 | 72391.46 | 29125429.89 | 0.474518E+09 | 0.00 | 0.54 |
November | 0.156101E+10 | 0.00 | 5076.55 | 13405.85 | 624219.18 | 0.463468E+09 | 20366082.53 | 2185.71 | 0.39 |
December | 0.358861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246041E+10 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.961031E+10 | 0.200524E+10 | 5076.55 | 17354234.82 | 0.136802E+09 | 0.976537E+10 | 0.561402E+10 | 2185.71 | 0.69 |
Minimum of Months | 0.143858E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.161038E+10 | 0.984326E+09 | 5076.55 | 4151671.86 | 69823262.61 | 0.281183E+10 | 0.133293E+10 | 2185.71 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.159082E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358238E+10 | 0.00 | 0.00 | 0.29 |
February | 0.331528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317299E+10 | 0.00 | 0.00 | 0.30 |
March | 0.147619E+10 | 896094.17 | 0.00 | 275649.84 | 723417.70 | 0.149874E+10 | 0.109624E+09 | 0.00 | 0.33 |
April | 0.203683E+10 | 0.00 | 0.00 | 237109.05 | 0.00 | 0.244752E+09 | 0.217429E+09 | 0.00 | 0.35 |
May | 0.115974E+10 | 0.00 | 0.00 | 3228731.86 | 4583138.99 | 162410.96 | 0.161736E+10 | 0.00 | 0.62 |
June | 0.309099E+09 | 0.416827E+09 | 0.00 | 5092577.71 | 35151186.13 | 0.00 | 0.166989E+10 | 0.00 | 0.94 |
July | 0.130818E+09 | 0.137767E+10 | 0.00 | 3060550.11 | 90514999.87 | 0.00 | 0.564016E+09 | 0.00 | 0.84 |
August | 0.273105E+09 | 0.714613E+09 | 0.00 | 4756145.70 | 32295230.24 | 0.00 | 0.100166E+10 | 0.00 | 0.89 |
September | 0.820225E+09 | 0.200979E+09 | 0.00 | 2971622.39 | 6404095.14 | 0.00 | 0.115097E+10 | 0.00 | 0.73 |
October | 0.193205E+10 | 0.00 | 0.00 | 515360.70 | 391697.45 | 0.127414E+09 | 0.327202E+09 | 0.00 | 0.38 |
November | 0.156883E+10 | 0.00 | 42166.26 | 0.00 | 1414900.91 | 0.849367E+09 | 0.00 | 5337.03 | 0.30 |
December | 0.334676E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313738E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.105322E+11 | 0.271099E+10 | 42166.26 | 20137747.35 | 0.171479E+09 | 0.126132E+11 | 0.665815E+10 | 5337.03 | 0.52 |
Minimum of Months | 0.130818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.203683E+10 | 0.137767E+10 | 42166.26 | 5092577.71 | 90514999.87 | 0.358238E+10 | 0.166989E+10 | 5337.03 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.254890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312996E+10 | 0.00 | 0.00 | 0.42 |
February | 0.629096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250760E+10 | 0.00 | 0.00 | 0.42 |
March | 0.182733E+10 | 1846247.95 | 0.00 | 282521.02 | 0.00 | 0.946734E+09 | 0.126713E+09 | 0.00 | 0.49 |
April | 0.161934E+10 | 0.00 | 0.00 | 1527143.02 | 0.00 | 0.118952E+09 | 0.933737E+09 | 0.00 | 0.60 |
May | 0.991576E+09 | 0.00 | 0.00 | 4456254.09 | 4384732.84 | 215745.56 | 0.224358E+10 | 0.00 | 1.10 |
June | 0.294369E+09 | 0.363983E+09 | 0.00 | 5471600.92 | 23316494.49 | 0.00 | 0.206521E+10 | 0.00 | 1.49 |
July | 0.107783E+09 | 0.112337E+10 | 0.00 | 4234827.01 | 86953567.63 | 0.00 | 0.821957E+09 | 0.00 | 1.35 |
August | 0.247074E+09 | 0.544994E+09 | 0.00 | 5114499.22 | 34230122.99 | 0.00 | 0.115789E+10 | 0.00 | 1.38 |
September | 0.757582E+09 | 0.165548E+09 | 0.00 | 3643205.28 | 9144845.17 | 229550.83 | 0.151040E+10 | 0.00 | 1.22 |
October | 0.173595E+10 | 0.00 | 0.00 | 801397.39 | 374740.69 | 85597745.51 | 0.498133E+09 | 0.00 | 0.59 |
November | 0.153784E+10 | 0.00 | 36416.01 | 9007.78 | 1353649.21 | 0.753374E+09 | 18318561.86 | 4674.53 | 0.46 |
December | 0.274056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289177E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.102769E+11 | 0.219974E+10 | 36416.01 | 25540455.73 | 0.159758E+09 | 0.104344E+11 | 0.937594E+10 | 4674.53 | 0.83 |
Minimum of Months | 0.107783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.182733E+10 | 0.112337E+10 | 36416.01 | 5471600.92 | 86953567.63 | 0.312996E+10 | 0.224358E+10 | 4674.53 | 1.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110291E+10 | 0.00 | 0.00 | 310748.18 | 0.00 | 0.279924E+10 | 0.197896E+09 | 0.00 | 0.32 |
February | 0.122578E+10 | 0.00 | 0.00 | 506664.62 | 0.00 | 0.234685E+10 | 0.297826E+09 | 0.00 | 0.33 |
March | 0.191070E+10 | 6760992.64 | 0.00 | 2392813.64 | 0.00 | 0.764508E+09 | 0.116869E+10 | 0.00 | 0.43 |
April | 0.176167E+10 | 0.00 | 0.00 | 3135347.84 | 0.00 | 0.184268E+09 | 0.169644E+10 | 0.00 | 0.55 |
May | 0.115485E+10 | 3014607.85 | 0.00 | 6135305.94 | 2224983.88 | 392835.22 | 0.283166E+10 | 0.00 | 0.91 |
June | 0.437740E+09 | 0.467942E+09 | 0.00 | 6339263.10 | 37656481.76 | 0.00 | 0.204476E+10 | 0.00 | 1.15 |
July | 0.181204E+09 | 0.163024E+10 | 0.00 | 3649192.10 | 89696290.16 | 0.00 | 0.628825E+09 | 0.00 | 0.99 |
August | 0.323434E+09 | 0.883278E+09 | 0.00 | 6892902.94 | 32225204.29 | 0.00 | 0.132873E+10 | 0.00 | 1.18 |
September | 0.696573E+09 | 0.293174E+09 | 0.00 | 7553218.25 | 7187806.24 | 0.00 | 0.273084E+10 | 0.00 | 1.30 |
October | 0.155814E+10 | 154439.62 | 0.00 | 4706760.09 | 352242.94 | 73450362.50 | 0.216499E+10 | 0.00 | 0.70 |
November | 0.172025E+10 | 0.00 | 34042.65 | 1383336.43 | 1588051.61 | 0.630612E+09 | 0.660578E+09 | 3163.58 | 0.38 |
December | 0.105031E+10 | 0.00 | 0.00 | 176312.70 | 0.00 | 0.263920E+10 | 0.101454E+09 | 0.00 | 0.32 |
Annual Sum or Average | 0.131236E+11 | 0.328456E+10 | 34042.65 | 43181865.81 | 0.170931E+09 | 0.943853E+10 | 0.158527E+11 | 3163.58 | 0.71 |
Minimum of Months | 0.181204E+09 | 0.00 | 0.00 | 176312.70 | 0.00 | 0.00 | 0.101454E+09 | 0.00 | 0.32 |
Maximum of Months | 0.191070E+10 | 0.163024E+10 | 34042.65 | 7553218.25 | 89696290.16 | 0.279924E+10 | 0.283166E+10 | 3163.58 | 1.30 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.353041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317139E+10 | 0.00 | 0.00 | 0.43 |
February | 0.612855E+09 | 0.00 | 0.00 | 7306.55 | 0.00 | 0.264465E+10 | 12964231.37 | 0.00 | 0.44 |
March | 0.176441E+10 | 505325.57 | 0.00 | 393770.06 | 1120078.24 | 0.107852E+10 | 0.197299E+09 | 0.00 | 0.51 |
April | 0.178220E+10 | 0.00 | 0.00 | 1376459.72 | 0.00 | 0.208625E+09 | 0.801105E+09 | 0.00 | 0.64 |
May | 0.123238E+10 | 121521.76 | 0.00 | 4137160.67 | 4450334.55 | 645349.83 | 0.195618E+10 | 0.00 | 1.13 |
June | 0.411593E+09 | 0.375083E+09 | 0.00 | 5317262.45 | 28384005.18 | 0.00 | 0.166323E+10 | 0.00 | 1.51 |
July | 0.179524E+09 | 0.118099E+10 | 0.00 | 2888713.82 | 69350802.00 | 0.00 | 0.420236E+09 | 0.00 | 1.18 |
August | 0.347822E+09 | 0.592210E+09 | 0.00 | 4250586.89 | 28410213.17 | 0.00 | 0.776820E+09 | 0.00 | 1.26 |
September | 0.844422E+09 | 0.159942E+09 | 0.00 | 3303082.08 | 12009406.15 | 239347.17 | 0.119844E+10 | 0.00 | 1.17 |
October | 0.187842E+10 | 0.00 | 0.00 | 826573.47 | 390733.17 | 0.114973E+09 | 0.460344E+09 | 0.00 | 0.64 |
November | 0.160430E+10 | 0.00 | 111055.79 | 31815.17 | 1338107.56 | 0.775844E+09 | 28082536.91 | 4878.46 | 0.47 |
December | 0.437865E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286202E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.114488E+11 | 0.230885E+10 | 111055.79 | 22532730.88 | 0.145454E+09 | 0.108569E+11 | 0.751470E+10 | 4878.46 | 0.82 |
Minimum of Months | 0.179524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.187842E+10 | 0.118099E+10 | 111055.79 | 5317262.45 | 69350802.00 | 0.317139E+10 | 0.195618E+10 | 4878.46 | 1.51 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:11
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.143685E+12 | 0.335852E+11 | 0.00 | 0.135010E+12 | 0.129240E+11 |
February | 0.217859E+12 | 0.340185E+11 | 0.00 | 0.125491E+12 | 0.119660E+11 |
March | 0.318339E+12 | 0.237586E+11 | 0.00 | 0.159565E+12 | 0.137697E+11 |
April | 0.374176E+12 | 0.184769E+11 | 0.00 | 0.192457E+12 | 0.410496E+10 |
May | 0.453933E+12 | 0.111117E+11 | 0.00 | 0.218163E+12 | 0.284528E+11 |
June | 0.486901E+12 | 0.429849E+10 | 0.00 | 0.122938E+12 | 0.135968E+12 |
July | 0.452125E+12 | -0.125229E+10 | 0.00 | 0.107183E+11 | 0.237604E+12 |
August | 0.388187E+12 | 0.152485E+10 | 0.00 | 0.834237E+11 | 0.196149E+12 |
September | 0.300364E+12 | 0.634789E+10 | 0.00 | 0.173083E+12 | 0.833151E+11 |
October | 0.207946E+12 | 0.152598E+11 | 0.00 | 0.200356E+12 | 0.962377E+10 |
November | 0.112154E+12 | 0.201334E+11 | 0.00 | 0.156445E+12 | 0.473995E+10 |
December | 0.128952E+12 | 0.342862E+11 | 0.00 | 0.138192E+12 | 0.111467E+11 |
Annual Sum or Average | 0.358462E+13 | 0.201549E+12 | 0.00 | 0.171584E+13 | 0.749765E+12 |
Minimum of Months | 0.112154E+12 | -0.125229E+10 | 0.00 | 0.107183E+11 | 0.410496E+10 |
Maximum of Months | 0.486901E+12 | 0.342862E+11 | 0.00 | 0.218163E+12 | 0.237604E+12 |