Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 08:35:17
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1840.37 | 369.39 | 369.39 |
Net Site Energy | 1840.37 | 369.39 | 369.39 |
Total Source Energy | 5626.34 | 1129.29 | 1129.29 |
Net Source Energy | 5626.34 | 1129.29 | 1129.29 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 12.35 | 2.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 455.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 148.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 94.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1743.34 | 97.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 12.35 | 2.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 455.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 280.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 71.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 148.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 94.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 12.35 | 2.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 455.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 280.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 71.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 148.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 94.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 123.58 | 19.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 349.92 | 19.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 123.58 | 19.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 349.92 | 19.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1743.344 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1743.344 | 100.00 |
Total On-Site and Utility Electric Sources | 1743.344 | 100.00 |
Total Electricity End Uses | 1743.344 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 73.50 |
Time Setpoint Not Met During Occupied Cooling | 462.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1010.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.5763 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 7.5763 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 7.5763 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-15:09 | 06-DEC-07:30 | - | - | - | - | - | - | - | - | - | - | 01-FEB-12:09 |
Heating | 0.00 | 28269.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 95616.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 23688.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 43769.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 920.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25880.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8051.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 189877.00 | 36321.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 28269.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 95616.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 23688.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 7527.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 920.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 25880.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8051.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 39.13 | 3.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1441.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 888.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 227.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2413.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 41.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 468.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 102.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5521.17 | 105.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 7.85 | 0.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 289.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 94.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1108.18 | 21.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 7.85 | 0.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 289.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 94.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1108.18 | 21.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.13 | 0.239226 | 0.258000 | 0.808270 | 0.637936 | 0.500000 | 0.001593 |
CORE_MID VAV BOX COMPONENT | 2.34 | 0.320908 | 0.336000 | 0.784700 | 0.855755 | 0.500000 | 0.001187 |
CORE_TOP VAV BOX COMPONENT | 2.58 | 0.290387 | 0.317000 | 0.818141 | 0.774365 | 0.500000 | 0.001312 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.949570 | 0.166382 | 0.200000 | 0.189914 | 0.443686 | 0.500000 | 0.002290 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.806193 | 0.124067 | 0.200000 | 0.161239 | 0.330845 | 0.500000 | 0.003071 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.04 | 0.151634 | 0.200000 | 0.208385 | 0.404357 | 0.500000 | 0.002513 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.922226 | 0.108450 | 0.200000 | 0.184445 | 0.300000 | 0.500000 | 0.003513 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.763740 | 0.206866 | 0.223000 | 0.170314 | 0.551642 | 0.500000 | 0.001842 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.695759 | 0.143759 | 0.200000 | 0.139152 | 0.383358 | 0.500000 | 0.002650 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.845099 | 0.186950 | 0.202000 | 0.170710 | 0.498535 | 0.500000 | 0.002038 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.739821 | 0.135188 | 0.200000 | 0.147964 | 0.360503 | 0.500000 | 0.002818 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.806385 | 0.195926 | 0.205000 | 0.165309 | 0.522469 | 0.500000 | 0.001945 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.753351 | 0.132769 | 0.200000 | 0.150670 | 0.354051 | 0.500000 | 0.002870 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.895203 | 0.176487 | 0.200000 | 0.179041 | 0.470632 | 0.500000 | 0.002159 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.815135 | 0.122698 | 0.200000 | 0.163027 | 0.327194 | 0.500000 | 0.003105 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 24507.56 |
CORE_MID VAV BOX REHEAT COIL | 23792.90 |
CORE_TOP VAV BOX REHEAT COIL | 30745.47 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 13996.87 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 9195.52 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 14050.75 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 9152.25 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 9036.58 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6027.79 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9106.33 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5982.28 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 10771.72 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 7144.89 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 10824.38 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 7102.93 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.09 | 1.44 | 6.18 | 1.44 | 5.70 | 5.70 | 0.300000 | 0.251820 | 5.70 |
PACU_VAV_MID | 2.80 | 1.44 | 5.61 | 1.75 | 5.07 | 5.07 | 0.300000 | 0.345974 | 5.07 |
PACU_VAV_TOP | 3.15 | 1.56 | 6.30 | 2.54 | 6.06 | 6.06 | 0.300000 | 0.419926 | 6.06 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.70 |
PACU_VAV_MID_OA_CONTROLLER | 5.07 |
PACU_VAV_TOP_OA_CONTROLLER | 6.06 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.70 | 112471.98 | 0.781657 | 1.90 | 37486.91 | 0.781657 |
PACU_VAV_MID COOLING COIL | 5.07 | 102491.85 | 0.771838 | 1.69 | 34160.53 | 0.771838 |
PACU_VAV_TOP COOLING COIL | 6.06 | 117789.97 | 0.788035 | 2.02 | 39259.40 | 0.788035 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 11500.34 |
PACU_VAV_MID HEATING COIL | 13769.60 |
PACU_VAV_TOP HEATING COIL | 12715.12 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.70 |
PACU_VAV_MID FAN | 5.07 |
PACU_VAV_TOP FAN | 6.06 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 32.411 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.029 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 1.013 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.375 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7377 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7531 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4931 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27613173E-12 | 0.13648587E-14 | -0.80406974E-13 | 0.78369587E-16 |
43 | 6 | 0.25651297E-07 | 0.27955499E-09 | 0.59014154E-08 | -0.11905989E-12 |
44 | 5 | -0.17465063E-03 | 0.24416492E-05 | -0.90019538E-04 | 0.58421144E-08 |
45 | 4 | 0.27387862 | 0.12098825E-02 | 0.93122264E-01 | -0.31012301E-04 |
46 | 3 | -6.9041115 | 0.38080793E-01 | -2.2314619 | 0.27235146E-01 |
47 | 2 | 39.676056 | 0.13726811 | 14.823303 | -0.32003278 |
48 | 1 | -79.629469 | 0.62686726E-01 | -28.745292 | 1.0590931 |
49 | 0 | 46.824345 | 0.12759187E-02 | 16.300942 | |
50 | 7 | -0.27182421E-12 | 0.13107754E-14 | -0.81108189E-13 | 0.79120162E-16 |
51 | 6 | 0.25844325E-07 | 0.27588229E-09 | 0.59440225E-08 | -0.12008605E-12 |
52 | 5 | -0.17564658E-03 | 0.24062150E-05 | -0.90521036E-04 | 0.58837691E-08 |
53 | 4 | 0.27506755 | 0.11908598E-02 | 0.93548701E-01 | -0.31177608E-04 |
54 | 3 | -6.9277136 | 0.37441415E-01 | -2.2384615 | 0.27350651E-01 |
55 | 2 | 39.753961 | 0.13483533 | 14.852153 | -0.32090009 |
56 | 1 | -79.689237 | 0.61525268E-01 | -28.771196 | 1.0603666 |
57 | 0 | 46.824344 | 0.12512697E-02 | 16.300293 | |
58 | 6 | 0.21465343E-07 | 0.35044740E-09 | 0.49771822E-08 | -0.96989815E-13 |
59 | 5 | -0.15274237E-03 | 0.31655188E-05 | -0.78941554E-04 | 0.49363227E-08 |
60 | 4 | 0.24727258 | 0.16154212E-02 | 0.83601931E-01 | -0.27359285E-04 |
61 | 3 | -6.3748395 | 0.52179222E-01 | -2.0745682 | 0.24648141E-01 |
62 | 2 | 37.927790 | 0.19236366 | 14.173893 | -0.30057625 |
63 | 1 | -78.286849 | 0.89555956E-01 | -28.161423 | 1.0304865 |
64 | 0 | 46.824354 | 0.18576719E-02 | 16.316151 | |
65 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
66 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
67 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
68 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
69 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
70 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
71 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
72 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
73 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
74 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
75 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
76 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
77 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
78 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
79 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
80 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
81 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
82 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
83 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
84 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
85 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
86 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
87 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
88 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
89 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
90 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
91 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
92 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
93 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
94 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
95 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
96 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
97 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
98 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
99 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
100 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
101 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
102 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
103 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
104 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
105 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 0.140 | 6.770E-004 | 1.025E-003 | 0.888 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 9.358E-002 | 7.129E-004 | 1.025E-003 | 0.936 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 0.140 | 6.770E-004 | 1.025E-003 | 0.888 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 9.358E-002 | 7.130E-004 | 1.025E-003 | 0.936 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 0.140 | 6.770E-004 | 9.968E-004 | 0.888 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 9.358E-002 | 7.129E-004 | 1.004E-003 | 0.936 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.140 | 6.770E-004 | 9.968E-004 | 0.888 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 9.358E-002 | 7.130E-004 | 1.004E-003 | 0.936 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 0.140 | 6.770E-004 | 1.025E-003 | 0.888 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 9.358E-002 | 7.129E-004 | 1.025E-003 | 0.936 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 0.140 | 6.770E-004 | 1.025E-003 | 0.888 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 9.358E-002 | 7.130E-004 | 1.025E-003 | 0.936 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.208 | 1.252E-004 | 1.025E-003 | 0.370 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.208 | 1.252E-004 | 1.025E-003 | 0.370 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.208 | 1.252E-004 | 1.116E-004 | 0.370 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.0300E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.0672E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.5097E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5412E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5103E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5358E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4264E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4410E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.9944E-002 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2257E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1011 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6293E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.7991E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7505E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8057E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0496E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.0308E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.0732E-003 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.5106E-003 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5478E-003 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5113E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5405E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4263E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4409E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1213E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3839E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8855E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1941E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0855E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.0372E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2668E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5265E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6898E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7043E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4933E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5038E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3533E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3570E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8320E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8371E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4614E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4945E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0698E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0962E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8086E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8278E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4263E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4409E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2862E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3351E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7739E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0215E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6935E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.1840E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8057E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0496E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4612E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4944E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0694E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0953E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8077E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8245E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4264E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4410E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5603E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1226E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2001E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8742E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5760E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8037E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2668E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5265E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3441E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3792E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0680E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1048E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0535E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0704E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8321E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8372E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.9174E-002 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.1272E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.8623E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.5983E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.1622E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.4618E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.1564E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.4627E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9661E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2968E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.7467E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1165E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9673E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9729E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.1886E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.4843E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.6010E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7357E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0571E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3690E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.9745E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.0394E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1564E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4627E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.4254E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0485E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.0863E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8127E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.4756E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7503E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.1887E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.4843E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.9175E-002 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.1267E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.8624E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.5978E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.1619E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.4614E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.1562E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.4625E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9662E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2966E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.7467E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1163E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9672E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9727E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.1884E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.4841E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.6011E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7356E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0572E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3690E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.9744E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.0393E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1562E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4625E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.4255E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0484E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.0863E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8126E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.4754E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7501E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.1884E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4842E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 39462.46235 | 39462.46235 | 3.13283 | 3.13283 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 5022.79920 | 5022.79920 | 0.23360 | 0.42469 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 29448.40834 | 29448.40834 | 2.33542 | 2.33542 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 12253.89127 | 12253.89127 | 0.57066 | 0.57066 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 32248.26045 | 32248.26045 | 2.58089 | 2.58089 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 40.26800 | 5.63027E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 21667.57569 | 21667.57569 | 1.01400 | 1.01400 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 11866.15123 | 11866.15123 | 0.94957 | 0.94957 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 40.53400 | 5.63070E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 9832.66177 | 9832.66177 | 0.46162 | 0.46162 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10074.53262 | 10074.53262 | 0.80619 | 0.80619 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 36.74350 | 5.62481E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 6459.08763 | 6459.08763 | 0.30327 | 0.30327 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13020.28644 | 13020.28644 | 1.04193 | 1.04193 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 40.80000 | 5.63111E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 9870.39947 | 9870.39947 | 0.46340 | 0.46340 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11524.50565 | 11524.50565 | 0.92223 | 0.92223 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 6428.77852 | 6428.77852 | 0.30185 | 0.30185 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 9543.56390 | 9543.56390 | 0.76374 | 0.76374 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 6357.07004 | 6357.07004 | 0.29803 | 0.29803 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8694.13852 | 8694.13852 | 0.69576 | 0.69576 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 36.74350 | 5.62481E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 4239.71178 | 4239.71178 | 0.19880 | 0.19880 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10560.22027 | 10560.22027 | 0.84510 | 0.84510 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 40.80000 | 5.63111E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 6405.96356 | 6405.96356 | 0.30033 | 0.30033 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9244.72277 | 9244.72277 | 0.73982 | 0.73982 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 38.71633 | 5.62786E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 4207.80532 | 4207.80532 | 0.19730 | 0.19730 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 10076.71698 | 10076.71698 | 0.80638 | 0.80638 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 7573.47821 | 7573.47821 | 0.35526 | 0.35526 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9414.06624 | 9414.06624 | 0.75335 | 0.75335 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 36.07850 | 5.62379E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5022.62666 | 5022.62666 | 0.23564 | 0.23564 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11186.60396 | 11186.60396 | 0.89520 | 0.89520 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 40.80000 | 5.63111E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 7610.36007 | 7610.36007 | 0.35699 | 0.35699 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10186.11331 | 10186.11331 | 0.81513 | 0.81513 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 4993.24373 | 4993.24373 | 0.23426 | 0.23426 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 92110.52 | 5.70411 | 5.70411 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 16145.74 | 1.41915 | 1.41915 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 18:20:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 84049.27 | 5.06630 | 5.06630 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 15833.64 | 1.75281 | 1.75281 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 96017.66 | 6.05855 | 6.05855 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 15932.65 | 2.54414 | 2.54414 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.13283 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23923 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25800 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80827 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63794 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.59264E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24507.56430 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.33542 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32091 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33600 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78470 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85576 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18726E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23792.90233 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.58089 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29039 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31700 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81814 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77436 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.31204E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 30745.47165 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94957 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16638 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18991 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44369 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.28991E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13996.86657 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80619 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12407 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16124 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33084 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.07093E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9195.52326 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.04193 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15163 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20839 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40436 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.51263E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14050.75333 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.92223 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10845 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18445 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.51314E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9152.24735 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76374 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20687 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17031 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55164 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.84177E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9036.57559 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69576 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14376 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13915 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38336 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.65026E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6027.78603 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84510 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18695 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20200 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17071 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49853 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.03797E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9106.33379 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73982 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13519 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14796 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36050 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.81829E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5982.27766 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80638 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19593 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20500 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16531 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52247 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.94461E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10771.71911 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75335 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13277 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15067 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35405 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.86964E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7144.88655 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89520 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17649 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17904 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47063 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.15880E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10824.38431 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81513 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12270 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16303 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32719 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.10519E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7102.93070 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.08862 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.43641 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.17725 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.43641 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.70411 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.70411 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.25182 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.80275 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.44275 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.60549 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.75281 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.06630 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.06630 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.34597 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.15040 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.56212 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.30080 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.54414 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.05855 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 6.05855 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.41993 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.70411 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.06630 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 6.05855 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.70411 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.70411 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 112471.98017 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.78166 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.90118 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37486.91099 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.78166 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 11500.33536 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.70411 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.06630 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.06630 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 102491.85411 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.77184 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.68860 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34160.53497 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.77184 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 13769.60017 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.06630 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.05855 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.05855 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 117789.97020 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.78803 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.01931 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 39259.39707 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.78803 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 12715.12329 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 6.05855 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 111379.76 | 380043.53 | 11.37 | 2.88 | 3.26 | 3.43 | 3.60 | 9.82 | 11.11 | 11.70 | 12.27 | 5.9894 | 4.7843 | 3.2218 | 1.2985 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 101598.37 | 346668.02 | 11.42 | 2.89 | 3.27 | 3.45 | 3.61 | 9.86 | 11.17 | 11.76 | 12.31 | 5.3197 | 4.2475 | 2.8610 | 1.1617 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 116580.59 | 397789.48 | 11.34 | 2.87 | 3.25 | 3.42 | 3.59 | 9.80 | 11.08 | 11.67 | 12.26 | 6.3616 | 5.0883 | 3.4279 | 1.3716 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 7.1222268839E-003 | 3.3734339199E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1285042880 | 7.9876571370E-002 | Pass | Pass | 4.5670253379E-002 | 0.2055594421 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.3527538530E-002 | 1.3739551175E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.0443746539E-002 | 1.1971480412E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.0482947914E-002 | 5.8635606916E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.8722880313E-002 | 3.6473391006E-002 | Pass | Pass | 4.4000443743E-002 | 0.2032584243 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.5328984933E-002 | 8.6961135032E-002 | Pass | Pass | 0.3263091562 | 3.1601176476 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 7.4500544915E-002 | 8.8178631290E-002 | Pass | Pass | 0.2958154392 | 2.4534561549 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1347958239 | 9.4865126737E-002 | Pass | Pass | 7.4272321369E-002 | 0.3708433707 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1285164239 | 0.1014809399 | Pass | Pass | 0.3152972551 | 3.1572521713 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.1150755770E-002 | 2.0067281533E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.2993943973E-002 | 6.3273572255E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.5253650576E-002 | 6.9970646573E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.9462513759E-002 | 7.7258803901E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.8714186635E-002 | 2.3437493934E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.4201432671E-002 | 7.5468063300E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1129899755 | 8.9945744485E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.8624038413E-002 | 9.0357623195E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2915.56 | 33.53 | 0.00 | 1194.54 | 2044.45 | 6188.10 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5047_SHGC_EAST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5047_SHGC_WEST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5047_SHGC_EAST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5047_SHGC_WEST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.869 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 177.99 | 2.869 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.869 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.46 | 0.0000 | Y | 9.28 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.15 | 0.0000 | Y | 5.82 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.03 | 0.0000 | Y | 9.15 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.38 | 0.0000 | Y | 5.86 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.38 | 0.0000 | Y | 9.25 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.11 | 0.0000 | Y | 5.81 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 30.99 | 0.0000 | Y | 9.14 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.32 | 0.0000 | Y | 5.85 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.46 | 0.0000 | Y | 9.28 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.15 | 0.0000 | Y | 5.82 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.03 | 0.0000 | Y | 9.15 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.38 | 0.0000 | Y | 5.86 |
Interior Lighting Total | 7.5763 | 4982.19 | 37746.71 | 280.70 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 41.79 | 41.79 | 3.33 | |
EXTERIOR_LIGHTS_B | 5132.60 | AstronomicalClock | - | 83.79 | 71.19 | 68.58 | |
Exterior Lighting Total | 5557.43 | 71.92 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 112471.98 | 87914.45 | 24557.53 | 0.78 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 102491.85 | 79107.15 | 23384.70 | 0.77 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 117789.97 | 92822.56 | 24967.41 | 0.79 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 111379.8 | 2.88 | 9.82 | N/A | N/A | 11.37 | |
PACU_VAV_MID COOLING COIL | 101598.4 | 2.89 | 9.86 | N/A | N/A | 11.42 | |
PACU_VAV_TOP COOLING COIL | 116580.6 | 2.87 | 9.80 | N/A | N/A | 11.34 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 24507.56 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 23792.90 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 30745.47 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13996.87 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9195.52 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14050.75 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9152.25 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9036.58 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6027.79 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9106.33 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5982.28 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10771.72 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7144.89 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10824.38 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7102.93 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 11500.34 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 13769.60 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 12715.12 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.70 | 12405.80 | 2174.89 | 1.00 | 1.13 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.07 | 11018.63 | 2174.89 | 1.00 | 1.14 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 6.06 | 13176.67 | 2174.89 | 1.00 | 1.13 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 111379.76 | 2.88 | 9.82 | 11.37 | 5.9894 | 3.26 | 11.11 | 4.7843 | 3.43 | 11.70 | 3.2218 | 3.60 | 12.27 | 1.2985 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 101598.37 | 2.89 | 9.86 | 11.42 | 5.3197 | 3.27 | 11.17 | 4.2475 | 3.45 | 11.76 | 2.8610 | 3.61 | 12.31 | 1.1617 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 116580.59 | 2.87 | 9.80 | 11.34 | 6.3616 | 3.25 | 11.08 | 5.0883 | 3.42 | 11.67 | 3.4279 | 3.59 | 12.26 | 1.3716 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 39462.46 | 39462.46 | 40.12 | 3.133 | 3.133 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00881 | 30.96 | 0.00562 | 0.425 | 0.00 |
CORE_MID | 29448.41 | 29448.41 | 29.94 | 2.335 | 2.335 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 30.96 | 0.00562 | 0.425 | 0.00 |
CORE_TOP | 32248.26 | 32248.26 | 32.79 | 2.581 | 2.581 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00887 | 40.27 | 0.00563 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 11866.15 | 11866.15 | 57.23 | 0.950 | 0.950 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00853 | 40.53 | 0.00563 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10074.53 | 10074.53 | 76.75 | 0.806 | 0.806 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.00 | 24.00 | 0.00851 | 36.74 | 0.00562 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13020.29 | 13020.29 | 62.80 | 1.042 | 1.042 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00852 | 40.80 | 0.00563 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11524.51 | 11524.51 | 87.80 | 0.922 | 0.922 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00851 | 38.94 | 0.00563 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 9543.56 | 9543.56 | 46.03 | 0.764 | 0.764 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00864 | 40.67 | 0.00563 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8694.14 | 8694.14 | 66.23 | 0.696 | 0.696 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.00 | 24.00 | 0.00859 | 36.74 | 0.00562 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10560.22 | 10560.22 | 50.93 | 0.845 | 0.845 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00862 | 40.80 | 0.00563 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9244.72 | 9244.72 | 70.43 | 0.740 | 0.740 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00859 | 38.72 | 0.00563 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 10076.72 | 10076.72 | 48.60 | 0.806 | 0.806 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00857 | 40.67 | 0.00563 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9414.07 | 9414.07 | 71.72 | 0.753 | 0.753 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00854 | 36.08 | 0.00562 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11186.60 | 11186.60 | 53.95 | 0.895 | 0.895 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00856 | 40.80 | 0.00563 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10186.11 | 10186.11 | 77.61 | 0.815 | 0.815 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00854 | 38.94 | 0.00563 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 5022.80 | 5022.80 | 5.11 | 0.234 | 0.425 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 0.425 | 0.00 |
CORE_MID | 12253.89 | 12253.89 | 12.46 | 0.571 | 0.571 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 0.425 | 0.00 |
CORE_TOP | 21667.58 | 21667.58 | 22.03 | 1.014 | 1.014 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9832.66 | 9832.66 | 47.42 | 0.462 | 0.462 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00776 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 6459.09 | 6459.09 | 49.21 | 0.303 | 0.303 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00776 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9870.40 | 9870.40 | 47.61 | 0.463 | 0.463 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00776 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 6428.78 | 6428.78 | 48.98 | 0.302 | 0.302 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6357.07 | 6357.07 | 30.66 | 0.298 | 0.298 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00768 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 4239.71 | 4239.71 | 32.30 | 0.199 | 0.199 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 6405.96 | 6405.96 | 30.90 | 0.300 | 0.300 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00768 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 4207.81 | 4207.81 | 32.06 | 0.197 | 0.197 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7573.48 | 7573.48 | 36.53 | 0.355 | 0.355 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 5022.63 | 5022.63 | 38.26 | 0.236 | 0.236 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00770 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 7610.36 | 7610.36 | 36.71 | 0.357 | 0.357 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 4993.24 | 4993.24 | 38.04 | 0.234 | 0.234 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | 0.50 | 0.00432 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.70 | 5.70 | 1.42 | 1.42 | 5.7041 | 1.4364 | 5.7041 | 0.2518 | 0.3000 |
PACU_VAV_MID | 5.07 | 5.07 | 1.75 | 1.75 | 5.0663 | 1.7528 | 5.0663 | 0.3460 | 0.3000 |
PACU_VAV_TOP | 6.06 | 6.06 | 2.54 | 2.54 | 6.0585 | 2.5441 | 6.0585 | 0.4199 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 24507.564 | 24507.564 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24507.56 | 12877.06 | 0.424691 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 5022.80 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 23792.902 | 23792.902 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 23792.90 | 17303.00 | 0.570661 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 12253.89 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 30745.472 | 30745.472 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 30745.47 | 30745.47 | 1.013999 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 21667.58 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 13996.867 | 13996.867 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13996.87 | 13996.87 | 0.461623 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00775717 | 45.5465 | 9832.66 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 9195.523 | 9195.523 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9195.52 | 9195.52 | 0.303272 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00775600 | 45.5398 | 6459.09 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 14050.753 | 14050.753 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14050.75 | 14050.75 | 0.463400 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00775828 | 45.5530 | 9870.40 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 9152.247 | 9152.247 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9152.25 | 9152.25 | 0.301845 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00775468 | 45.5322 | 6428.78 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 9036.576 | 9036.576 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9036.58 | 9036.58 | 0.298030 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00767524 | 45.0716 | 6357.07 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6027.786 | 6027.786 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6027.79 | 6027.79 | 0.198799 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00769386 | 45.1795 | 4239.71 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9106.334 | 9106.334 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9106.33 | 9106.33 | 0.300331 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00768036 | 45.1012 | 6405.96 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 5982.278 | 5982.278 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5982.28 | 5982.28 | 0.197298 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00768917 | 45.1523 | 4207.81 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 10771.719 | 10771.719 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10771.72 | 10771.72 | 0.355256 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00768662 | 45.1377 | 7573.48 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 7144.887 | 7144.887 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7144.89 | 7144.89 | 0.235641 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00769696 | 45.1977 | 5022.63 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 10824.384 | 10824.384 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10824.38 | 10824.38 | 0.356993 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00768908 | 45.1520 | 7610.36 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 7102.931 | 7102.931 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7102.93 | 7102.93 | 0.234258 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00769392 | 45.1800 | 4993.24 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 112471.980 | 87914.455 | 5.704109 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 102539.16 | 102539.16 | 5.704109 | 27.53 | 16.25 | 0.00807771 | 10.85 | 10.01 | 0.00807771 | 40.80 | 0.00563111 | 18.58 | 20.9528 | 24.00 | 0.00872764 | 42.6390 | 71152.79 | 0.00 | 115973.71 | 85111.99 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 11500.335 | 11500.335 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 18:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11500.34 | 11500.34 | 1.711233 | 6.68 | 5.13 | 0.00537956 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 69.8426 | 21.00 | 0.00779739 | 45.7782 | 19536.48 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 102491.854 | 79107.150 | 5.066298 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 93440.42 | 93440.42 | 5.066298 | 27.98 | 16.33 | 0.00798967 | 10.85 | 9.92 | 0.00798967 | 40.80 | 0.00563111 | 18.58 | 23.5906 | 24.00 | 0.00872303 | 42.6162 | 62965.24 | 0.00 | 105682.86 | 76695.79 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 13769.600 | 13769.600 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13769.60 | 13769.60 | 1.519889 | 4.55 | 3.59 | 0.00500034 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 78.6353 | 19.60 | 0.00742958 | 47.5923 | 23977.51 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 117789.970 | 92822.561 | 6.058548 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 107548.02 | 107548.02 | 6.058548 | 27.31 | 16.17 | 0.00806822 | 10.85 | 10.00 | 0.00806822 | 40.67 | 0.00563090 | 18.54 | 19.7270 | 24.00 | 0.00867123 | 42.3664 | 75299.09 | 0.00 | 121457.27 | 89802.41 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 12715.123 | 12715.123 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12715.12 | 12715.12 | 1.817565 | 6.43 | 5.09 | 0.00545086 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 65.7567 | 19.39 | 0.00757778 | 49.1575 | 25335.54 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 24507.564 | 24507.564 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 24507.56 | 12877.06 | 1.0000 | 0.46426985 | 0.424691 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24507.56 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.70 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 5022.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 23792.902 | 23792.902 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 23792.90 | 17303.00 | 1.0000 | 0.62384283 | 0.570661 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23792.90 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 12253.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 30745.472 | 30745.472 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 30745.47 | 30745.47 | 1.0000 | 1.10849795 | 1.013999 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30745.47 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 21667.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13996.867 | 13996.867 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13996.87 | 13996.87 | 1.0000 | 0.50464335 | 0.461623 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13996.87 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00775717 | 21.00 | 0.00775717 | 45.5465 | 9832.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9195.523 | 9195.523 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9195.52 | 9195.52 | 1.0000 | 0.33153561 | 0.303272 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9195.52 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00775600 | 21.00 | 0.00775600 | 45.5398 | 6459.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 14050.753 | 14050.753 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14050.75 | 14050.75 | 1.0000 | 0.50658619 | 0.463400 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14050.75 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00775828 | 21.00 | 0.00775828 | 45.5530 | 9870.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9152.247 | 9152.247 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9152.25 | 9152.25 | 1.0000 | 0.32997534 | 0.301845 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9152.25 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00775468 | 21.00 | 0.00775468 | 45.5322 | 6428.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 9036.576 | 9036.576 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9036.58 | 9036.58 | 1.0000 | 0.32580491 | 0.298030 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9036.58 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00767524 | 21.00 | 0.00767524 | 45.0716 | 6357.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 6027.786 | 6027.786 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6027.79 | 6027.79 | 1.0000 | 0.21732594 | 0.198799 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6027.79 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00769386 | 21.00 | 0.00769386 | 45.1795 | 4239.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 9106.334 | 9106.334 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9106.33 | 9106.33 | 1.0000 | 0.32831997 | 0.300331 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9106.33 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00768036 | 21.00 | 0.00768036 | 45.1012 | 6405.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5982.278 | 5982.278 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5982.28 | 5982.28 | 1.0000 | 0.21568518 | 0.197298 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5982.28 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00768917 | 21.00 | 0.00768917 | 45.1523 | 4207.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10771.719 | 10771.719 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10771.72 | 10771.72 | 1.0000 | 0.38836381 | 0.355256 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10771.72 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00768662 | 21.00 | 0.00768662 | 45.1377 | 7573.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7144.887 | 7144.887 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7144.89 | 7144.89 | 1.0000 | 0.25760191 | 0.235641 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7144.89 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00769696 | 21.00 | 0.00769696 | 45.1977 | 5022.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10824.384 | 10824.384 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10824.38 | 10824.38 | 1.0000 | 0.39026261 | 0.356993 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10824.38 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00768908 | 21.00 | 0.00768908 | 45.1520 | 7610.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7102.931 | 7102.931 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7102.93 | 7102.93 | 1.0000 | 0.25608923 | 0.234258 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7102.93 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00769392 | 21.00 | 0.00769392 | 45.1800 | 4993.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 112471.980 | 87914.455 | 5.704109 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8561 | 1004.8586 | 1.0932 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.704109 | 6.23569912 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 102539.16 | 102539.16 | 0.9117 | 6.23569912 | 5.704109 | 27.53 | 16.25 | 0.00807771 | 48273.8 | 10.85 | 10.01 | 0.00807771 | 31266.5 | -999.0 | -999.00 | -999.00 | -999.00 | 12405.800 | 90133.36 | 40.80 | 0.00563111 | 18.58 | 1.19517000 | 20.9528 | 24.00 | 0.00872764 | 24.00 | 0.00872764 | 42.6390 | 71152.79 | 0.00 | 115973.71 | 85111.99 | 5.98943614 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.76 | 12.74 | 0.00916441 | 35959.3 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11500.335 | 11500.335 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.704109 | 6.23569912 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 18:20:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11500.34 | 11500.34 | 1.0000 | 1.87070973 | 1.711233 | 6.68 | 5.13 | 0.00537956 | 20235.3 | 12.80 | 10.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11500.34 | 0.50 | 0.00431558 | 0.50 | 1.19517000 | 69.8426 | 21.00 | 0.00784368 | 21.00 | 0.00779739 | 45.7782 | 19536.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 102491.854 | 79107.150 | 5.066298 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6924 | 1004.8586 | 1.0932 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.066298 | 5.53844721 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 93440.42 | 93440.42 | 0.9117 | 5.53844721 | 5.066298 | 27.98 | 16.33 | 0.00798967 | 48516.9 | 10.85 | 9.92 | 0.00798967 | 31044.3 | -999.0 | -999.00 | -999.00 | -999.00 | 11018.632 | 82421.79 | 40.80 | 0.00563111 | 18.58 | 1.19517000 | 23.5906 | 24.00 | 0.00872303 | 24.00 | 0.00872303 | 42.6162 | 62965.24 | 0.00 | 105682.86 | 76695.79 | 5.31972041 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.56 | 12.54 | 0.00904824 | 35456.1 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 13769.600 | 13769.600 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.066298 | 5.53844721 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13769.60 | 13769.60 | 1.0000 | 1.66153416 | 1.519889 | 4.55 | 3.59 | 0.00500034 | 17122.7 | 12.80 | 10.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13769.60 | 0.50 | 0.00431558 | 0.50 | 1.19517000 | 78.6353 | 19.47 | 0.00752068 | 19.60 | 0.00742958 | 47.5923 | 23977.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 117789.970 | 92822.561 | 6.058548 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8384 | 1004.8586 | 1.0932 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.058548 | 6.62317000 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 107548.02 | 107548.02 | 0.9130 | 6.62317000 | 6.058548 | 27.31 | 16.17 | 0.00806822 | 48025.0 | 10.85 | 10.00 | 0.00806822 | 31242.6 | -999.0 | -999.00 | -999.00 | -999.00 | 13176.666 | 94371.36 | 40.67 | 0.00563090 | 18.54 | 1.19517000 | 19.7270 | 24.00 | 0.00867123 | 24.00 | 0.00867123 | 42.3664 | 75299.09 | 0.00 | 121457.27 | 89802.41 | 6.36160485 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.85 | 12.85 | 0.00923371 | 36230.1 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 12715.123 | 12715.123 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.058548 | 6.62317000 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12715.12 | 12715.12 | 1.0000 | 1.98695100 | 1.817565 | 6.43 | 5.09 | 0.00545086 | 20160.2 | 12.80 | 10.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12715.12 | 0.50 | 0.00431558 | 0.50 | 1.19517000 | 65.7567 | 17.82 | 0.00763089 | 19.39 | 0.00757778 | 49.1575 | 25335.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.70 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.07 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 6.06 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2100.50 | 1120.00 | 15.17 |
CORE_MID | 1655.83 | 2402.50 | 26.33 |
CORE_TOP | 1695.00 | 2791.50 | 106.67 |
PERIMETER_TOP_ZN_3 | 2473.83 | 3107.33 | 685.50 |
PERIMETER_TOP_ZN_2 | 2816.00 | 2685.50 | 577.83 |
PERIMETER_TOP_ZN_1 | 2877.00 | 2182.00 | 480.00 |
PERIMETER_TOP_ZN_4 | 2789.00 | 2883.00 | 706.17 |
PERIMETER_BOT_ZN_3 | 1909.83 | 3042.67 | 179.17 |
PERIMETER_BOT_ZN_2 | 2482.83 | 2362.67 | 213.83 |
PERIMETER_BOT_ZN_1 | 2569.33 | 2038.83 | 286.33 |
PERIMETER_BOT_ZN_4 | 2397.17 | 2503.17 | 200.17 |
PERIMETER_MID_ZN_3 | 2051.33 | 2901.83 | 273.33 |
PERIMETER_MID_ZN_2 | 2147.17 | 2198.17 | 325.17 |
PERIMETER_MID_ZN_1 | 2672.83 | 1872.50 | 237.50 |
PERIMETER_MID_ZN_4 | 2482.00 | 2622.00 | 339.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4170.00 | 3687.00 | 1010.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 2.33 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.50 | 46.67 | 0.17 | 27.33 |
PERIMETER_TOP_ZN_2 | 0.33 | 79.17 | 0.00 | 62.17 |
PERIMETER_TOP_ZN_1 | 0.00 | 74.33 | 0.00 | 55.00 |
PERIMETER_TOP_ZN_4 | 0.33 | 68.33 | 0.00 | 35.33 |
PERIMETER_BOT_ZN_3 | 0.00 | 13.67 | 0.00 | 8.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 56.83 | 0.00 | 49.67 |
PERIMETER_BOT_ZN_1 | 73.33 | 321.67 | 73.33 | 313.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 53.17 | 0.00 | 28.67 |
PERIMETER_MID_ZN_3 | 0.00 | 28.83 | 0.00 | 17.17 |
PERIMETER_MID_ZN_2 | 0.00 | 65.33 | 0.00 | 57.00 |
PERIMETER_MID_ZN_1 | 0.00 | 63.83 | 0.00 | 52.83 |
PERIMETER_MID_ZN_4 | 0.00 | 55.83 | 0.00 | 29.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 73.83 | 524.67 | 73.50 | 462.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.84 | 52.94 | 2698.04 | 0.975 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.84 | 52.94 | 2698.04 | 0.658 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.84 | 52.94 | 2698.04 | 0.632 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.750 | 0.121 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 1.137 | 0.128 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 1.233 | 0.121 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 1.182 | 0.128 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.676 | 0.065 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 1.057 | 0.068 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 1.090 | 1.307 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 1.006 | 0.068 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.721 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 1.077 | 0.114 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 1.204 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 1.121 | 0.106 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.56 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.30 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 15774231.38 | 0.00 | 15774231.38 | 0.00 | 15774231.38 | 13393058.27 | 5765.32 | 65.96 | 2928.71 | 131.28 |
CORE_MID | 10576260.25 | 0.00 | 10576260.25 | 0.00 | 10576260.25 | 13393058.27 | 6370.10 | 17.36 | 2372.54 | 73.28 |
CORE_TOP | 10103716.33 | 0.00 | 10103716.33 | 0.00 | 10103716.33 | 13393058.27 | 6441.89 | 12.54 | 2305.56 | 52.34 |
PERIMETER_TOP_ZN_3 | 2526242.31 | 0.00 | 2526242.31 | 803986.63 | 3330228.93 | 2823374.22 | 4315.63 | 43.74 | 4400.63 | 52.34 |
PERIMETER_TOP_ZN_2 | 2417388.97 | 0.00 | 2417388.97 | 535987.86 | 2953376.83 | 1787429.43 | 4064.95 | 4.62 | 4690.42 | 52.34 |
PERIMETER_TOP_ZN_1 | 4129530.81 | 0.00 | 4129530.81 | 803986.63 | 4933517.44 | 2823374.22 | 4177.90 | 23.60 | 4558.50 | 52.34 |
PERIMETER_TOP_ZN_4 | 2519056.08 | 0.00 | 2519056.08 | 535987.86 | 3055043.94 | 1787312.18 | 4170.21 | 28.65 | 4561.14 | 52.34 |
PERIMETER_BOT_ZN_3 | 2323517.68 | 0.00 | 2323517.68 | 427478.21 | 2750995.89 | 2823374.22 | 5243.33 | 120.96 | 3395.70 | 131.28 |
PERIMETER_BOT_ZN_2 | 2283735.10 | 0.00 | 2283735.10 | 284983.76 | 2568718.86 | 1787429.43 | 4007.90 | 23.64 | 4728.46 | 131.28 |
PERIMETER_BOT_ZN_1 | 3697726.03 | 0.00 | 3697726.03 | 4551340.55 | 8249066.58 | 2823374.22 | 4174.55 | 36.99 | 4548.46 | 131.28 |
PERIMETER_BOT_ZN_4 | 2182003.73 | 0.00 | 2182003.73 | 284983.76 | 2466987.49 | 1787312.18 | 4364.57 | 63.08 | 4332.34 | 131.28 |
PERIMETER_MID_ZN_3 | 2434909.66 | 0.00 | 2434909.66 | 669259.31 | 3104168.96 | 2823374.22 | 4433.83 | 48.89 | 4277.28 | 73.28 |
PERIMETER_MID_ZN_2 | 2437448.17 | 0.00 | 2437448.17 | 446170.19 | 2883618.36 | 1787429.43 | 4028.04 | 7.18 | 4724.78 | 982.28 |
PERIMETER_MID_ZN_1 | 4041435.12 | 0.00 | 4041435.12 | 669259.31 | 4710694.42 | 2823374.22 | 4097.56 | 27.45 | 4634.99 | 73.28 |
PERIMETER_MID_ZN_4 | 2398198.25 | 0.00 | 2398198.25 | 446170.19 | 2844368.44 | 1787312.18 | 4101.73 | 29.56 | 4628.71 | 73.28 |
Total Facility | 69845399.85 | 0.00 | 69845399.85 | 10459594.26 | 80304994.11 | 67843644.98 | 6590.70 | 439.50 | 4896.65 | 1058.46 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7164 | 0.0000 | 0.7164 | 0.0000 | 0.7164 | 0.4247 | 3079.60 | 65.96 | 2797.44 |
CORE_MID | 0.4832 | 0.0000 | 0.4832 | 0.0000 | 0.4832 | 0.4247 | 3626.38 | 17.36 | 2299.26 |
CORE_TOP | 0.4647 | 0.0000 | 0.4647 | 0.0000 | 0.4647 | 0.4247 | 3673.93 | 12.54 | 2256.53 |
PERIMETER_TOP_ZN_3 | 0.1164 | 0.0000 | 0.1164 | 0.0188 | 0.1352 | 0.0895 | 1547.67 | 43.74 | 4351.59 |
PERIMETER_TOP_ZN_2 | 0.1116 | 0.0000 | 0.1116 | 0.0125 | 0.1241 | 0.0567 | 1296.99 | 4.62 | 4641.39 |
PERIMETER_TOP_ZN_1 | 0.1912 | 0.0000 | 0.1912 | 0.0188 | 0.2100 | 0.0895 | 1409.94 | 23.60 | 4509.47 |
PERIMETER_TOP_ZN_4 | 0.1161 | 0.0000 | 0.1161 | 0.0125 | 0.1287 | 0.0567 | 1402.25 | 28.65 | 4512.10 |
PERIMETER_BOT_ZN_3 | 0.1048 | 0.0000 | 0.1048 | 0.0100 | 0.1148 | 0.0895 | 2557.61 | 120.96 | 3264.43 |
PERIMETER_BOT_ZN_2 | 0.1036 | 0.0000 | 0.1036 | 0.0067 | 0.1103 | 0.0567 | 1322.18 | 23.64 | 4597.18 |
PERIMETER_BOT_ZN_1 | 0.1689 | 0.0000 | 0.1689 | 0.2027 | 0.3717 | 0.0895 | 1488.82 | 36.99 | 4417.18 |
PERIMETER_BOT_ZN_4 | 0.0987 | 0.0000 | 0.0987 | 0.0067 | 0.1053 | 0.0567 | 1678.85 | 63.08 | 4201.07 |
PERIMETER_MID_ZN_3 | 0.1117 | 0.0000 | 0.1117 | 0.0156 | 0.1273 | 0.0895 | 1690.11 | 48.89 | 4203.99 |
PERIMETER_MID_ZN_2 | 0.1056 | 0.0000 | 0.1056 | 0.0112 | 0.1168 | 0.0567 | 1273.66 | 5.34 | 3755.00 |
PERIMETER_MID_ZN_1 | 0.1866 | 0.0000 | 0.1866 | 0.0156 | 0.2022 | 0.0895 | 1353.85 | 27.45 | 4561.71 |
PERIMETER_MID_ZN_4 | 0.1100 | 0.0000 | 0.1100 | 0.0104 | 0.1204 | 0.0567 | 1358.02 | 29.56 | 4555.43 |
Total Facility | 3.1897 | 0.0000 | 3.1897 | 0.3416 | 3.5312 | 2.1513 | 3810.81 | 439.50 | 4750.50 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 31384081.46 | 0.00 | 31384081.46 | 22614548.33 | 3923.78 | 1.31 | 4834.91 | 131.28 |
PACU_VAV_MID | 26158077.11 | 0.00 | 26158077.11 | 22614548.33 | 4003.45 | 1.02 | 4755.52 | 73.28 |
PACU_VAV_TOP | 25928237.15 | 0.00 | 25928237.15 | 22614548.33 | 4073.17 | 4.65 | 4682.17 | 52.34 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.4251 | 0.0000 | 1.4251 | 0.7171 | 1238.06 | 1.31 | 4703.64 |
PACU_VAV_MID | 1.1992 | 0.0000 | 1.1992 | 0.7171 | 1259.74 | 1.02 | 4682.24 |
PACU_VAV_TOP | 1.1952 | 0.0000 | 1.1952 | 0.7171 | 1305.21 | 4.65 | 4633.14 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.22 | 2638.11 | 0.00 | 0.00 | 0.00 | 2210.31 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.20 | 2467.89 | 0.00 | 0.00 | 0.00 | 2303.70 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2433.43 | 0.00 | 0.00 | 0.00 | 2308.92 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.5628 | 0.0000 | 0.0000 | 0.0000 | 0.9261 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.0622 | 0.0000 | 0.0000 | 0.0000 | 0.9509 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.0741 | 0.0000 | 0.0000 | 0.0000 | 0.9378 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 824 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1743.34 | 15539.06 | 13-AUG-17:30 | 189877.00 | 28-JUN-15:10 |
Electricity:Building | 1042.74 | 15341.49 | 01-JAN-09:30 | 74465.13 | 20-JAN-08:30 |
Electricity:Zone:CORE_BOTTOM | 310.83 | 4652.71 | 01-JAN-00:10 | 24063.48 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1042.74 | 15341.49 | 01-JAN-09:30 | 74465.13 | 20-JAN-08:30 |
InteriorLights:Electricity | 280.70 | 1316.11 | 01-JAN-09:30 | 28079.40 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 280.70 | 1316.11 | 01-JAN-09:30 | 28079.40 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity | 280.70 | 1316.11 | 01-JAN-09:30 | 28079.40 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 280.70 | 1316.11 | 01-JAN-09:30 | 28079.40 | 28-NOV-16:30 |
Electricity:Zone:CORE_MID | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 35.96 | 541.99 | 01-JAN-09:30 | 2674.44 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.28 | 40.03 | 01-JAN-09:30 | 1168.55 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.28 | 40.03 | 01-JAN-09:30 | 1168.55 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 22.71 | 343.10 | 01-JAN-08:00 | 1693.08 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.82 | 25.34 | 01-JAN-08:00 | 739.79 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.82 | 25.34 | 01-JAN-08:00 | 739.79 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 35.84 | 541.99 | 01-JAN-08:10 | 2674.43 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.15 | 40.03 | 01-JAN-08:10 | 1168.55 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.15 | 40.03 | 01-JAN-08:10 | 1168.55 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 22.75 | 343.10 | 01-JAN-09:30 | 1693.03 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.86 | 25.34 | 01-JAN-09:30 | 739.74 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.86 | 25.34 | 01-JAN-09:30 | 739.74 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 35.94 | 541.99 | 01-JAN-09:20 | 2674.44 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.25 | 40.03 | 01-JAN-09:20 | 1168.55 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.25 | 40.03 | 01-JAN-09:20 | 1168.55 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 22.70 | 343.10 | 01-JAN-08:00 | 1693.08 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.81 | 25.34 | 01-JAN-08:00 | 739.79 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.81 | 25.34 | 01-JAN-08:00 | 739.79 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 35.83 | 541.99 | 01-JAN-07:50 | 2674.43 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.14 | 40.03 | 01-JAN-07:50 | 1168.55 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.14 | 40.03 | 01-JAN-07:50 | 1168.55 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 22.74 | 343.10 | 01-JAN-09:20 | 1693.03 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.85 | 25.34 | 01-JAN-09:20 | 739.74 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.85 | 25.34 | 01-JAN-09:20 | 739.74 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 35.96 | 541.99 | 01-JAN-09:30 | 2674.44 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.28 | 40.03 | 01-JAN-09:30 | 1168.55 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.28 | 40.03 | 01-JAN-09:30 | 1168.55 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 22.71 | 343.10 | 01-JAN-08:00 | 1693.08 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.82 | 25.34 | 01-JAN-08:00 | 739.79 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.82 | 25.34 | 01-JAN-08:00 | 739.79 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 35.84 | 541.99 | 01-JAN-08:10 | 2674.43 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.15 | 40.03 | 01-JAN-08:10 | 1168.55 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.15 | 40.03 | 01-JAN-08:10 | 1168.55 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 22.75 | 343.10 | 01-JAN-09:30 | 1693.03 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.86 | 25.34 | 01-JAN-09:30 | 739.74 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.86 | 25.34 | 01-JAN-09:30 | 739.74 | 28-NOV-16:30 |
InteriorEquipment:Electricity | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 247.34 | 4344.73 | 01-JAN-00:10 | 18520.31 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 628.67 | 197.13 | 01-JAN-00:10 | 123652.98 | 28-JUN-15:00 |
ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 926.74 | 28-NOV-16:40 |
Transformer:ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 926.74 | 28-NOV-16:40 |
ElectricityPurchased:Facility | 1743.34 | 15539.06 | 03-JUN-18:20 | 189877.00 | 28-JUN-15:10 |
ElectricityPurchased:Plant | 1743.34 | 15539.06 | 03-JUN-18:20 | 189877.00 | 28-JUN-15:10 |
Cogeneration:ElectricityPurchased | 1743.34 | 15539.06 | 03-JUN-18:20 | 189877.00 | 28-JUN-15:10 |
General:Cogeneration:ElectricityPurchased | 1743.34 | 15539.06 | 03-JUN-18:20 | 189877.00 | 28-JUN-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1743.34 | 15539.06 | 03-JUN-18:20 | 189877.00 | 28-JUN-15:10 |
ElectricityNet:Plant | 1743.34 | 15539.06 | 03-JUN-18:20 | 189877.00 | 28-JUN-15:10 |
Cogeneration:ElectricityNet | 1743.34 | 15539.06 | 03-JUN-18:20 | 189877.00 | 28-JUN-15:10 |
General:Cogeneration:ElectricityNet | 1743.34 | 15539.06 | 03-JUN-18:20 | 189877.00 | 28-JUN-15:10 |
Heating:Electricity | 12.35 | 0.00 | 01-JAN-00:10 | 93091.75 | 02-JAN-07:10 |
General:Heating:Electricity | 12.35 | 0.00 | 01-JAN-00:10 | 93091.75 | 02-JAN-07:10 |
Fans:Electricity | 148.05 | 0.00 | 01-JAN-00:10 | 28932.60 | 19-JUN-15:00 |
General:Fans:Electricity | 148.05 | 0.00 | 01-JAN-00:10 | 28932.60 | 19-JUN-15:00 |
ExteriorLights:Electricity | 71.92 | 0.00 | 01-JAN-07:30 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 71.92 | 0.00 | 01-JAN-07:30 | 5557.43 | 01-JAN-06:10 |
Cooling:Electricity | 455.28 | 0.00 | 01-JAN-00:10 | 95685.14 | 28-JUN-15:00 |
General:Cooling:Electricity | 455.28 | 0.00 | 01-JAN-00:10 | 95685.14 | 28-JUN-15:00 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-08:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-08:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-08:10 |
WIRED_LTG_ELECTRICITY | 7.89 | 0.00 | 01-JAN-00:10 | 789.03 | 28-NOV-16:40 |
WIRED_INT_EQUIP | 641.94 | 12061.80 | 01-JAN-00:10 | 36271.65 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 97.02 | 1156.00 | 07-MAY-16:10 | 36321.59 | 06-DEC-07:30 |
NaturalGas:HVAC | 2.83 | 0.00 | 01-JAN-00:10 | 30205.54 | 06-DEC-07:20 |
Heating:NaturalGas | 2.83 | 0.00 | 01-JAN-00:10 | 30205.54 | 06-DEC-07:20 |
General:Heating:NaturalGas | 2.83 | 0.00 | 01-JAN-00:10 | 30205.54 | 06-DEC-07:20 |
NaturalGas:Plant | 94.19 | 1156.00 | 08-FEB-08:10 | 9054.60 | 03-FEB-12:10 |
WaterSystems:NaturalGas | 94.19 | 1156.00 | 08-FEB-08:10 | 9054.60 | 03-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 94.19 | 1156.00 | 08-FEB-08:10 | 9054.60 | 03-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3208.45 | 0.00 | 01-JAN-00:10 | 430449.85 | 28-JUN-15:20 |
EnergyTransfer:Building | 1566.76 | 0.00 | 01-JAN-00:10 | 181009.61 | 28-JUN-16:00 |
EnergyTransfer:Zone:CORE_BOTTOM | 294.12 | 0.00 | 01-JAN-00:10 | 29141.87 | 05-SEP-07:20 |
Heating:EnergyTransfer | 14.92 | 0.00 | 01-JAN-00:10 | 78451.02 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 14.92 | 0.00 | 01-JAN-00:10 | 78451.02 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1551.84 | 0.00 | 01-JAN-00:10 | 181009.61 | 28-JUN-16:00 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 294.12 | 0.00 | 01-JAN-00:10 | 29141.87 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer | 1551.84 | 0.00 | 01-JAN-00:10 | 181009.61 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 294.12 | 0.00 | 01-JAN-00:10 | 29141.87 | 05-SEP-07:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 72.41 | 0.00 | 01-JAN-00:10 | 13878.17 | 28-JUN-15:00 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.90 | 0.00 | 01-JAN-00:10 | 7279.09 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.90 | 0.00 | 01-JAN-00:10 | 7279.09 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 66.51 | 0.00 | 01-JAN-00:10 | 13878.17 | 28-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 66.51 | 0.00 | 01-JAN-00:10 | 13878.17 | 28-JUN-15:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 37.52 | 0.00 | 01-JAN-00:10 | 6451.33 | 19-JUN-14:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.96 | 0.00 | 01-JAN-00:10 | 2789.03 | 02-JAN-11:40 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.96 | 0.00 | 01-JAN-00:10 | 2789.03 | 02-JAN-11:40 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 35.56 | 0.00 | 01-JAN-00:10 | 6451.33 | 19-JUN-14:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 35.56 | 0.00 | 01-JAN-00:10 | 6451.33 | 19-JUN-14:10 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 42.60 | 0.00 | 01-JAN-00:10 | 6533.73 | 28-AUG-07:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.81 | 0.00 | 01-JAN-00:10 | 2718.09 | 02-JAN-08:50 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.81 | 0.00 | 01-JAN-00:10 | 2718.09 | 02-JAN-08:50 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 41.79 | 0.00 | 01-JAN-00:10 | 6533.73 | 28-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 41.79 | 0.00 | 01-JAN-00:10 | 6533.73 | 28-AUG-07:10 |
EnergyTransfer:Zone:CORE_MID | 199.83 | 0.00 | 01-JAN-00:10 | 20094.96 | 05-SEP-07:40 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 5308.08 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 5308.08 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 199.83 | 0.00 | 01-JAN-00:10 | 20094.96 | 05-SEP-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 199.83 | 0.00 | 01-JAN-00:10 | 20094.96 | 05-SEP-07:40 |
EnergyTransfer:Zone:CORE_TOP | 200.54 | 0.00 | 01-JAN-00:10 | 21997.68 | 19-JUN-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.15 | 0.00 | 01-JAN-00:10 | 14109.83 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.15 | 0.00 | 01-JAN-00:10 | 14109.83 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 200.40 | 0.00 | 01-JAN-00:10 | 21997.68 | 19-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 200.40 | 0.00 | 01-JAN-00:10 | 21997.68 | 19-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 57.12 | 0.00 | 01-JAN-00:10 | 8715.38 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 1.03 | 0.00 | 01-JAN-00:10 | 7233.84 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 1.03 | 0.00 | 01-JAN-00:10 | 7233.84 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 56.09 | 0.00 | 01-JAN-00:10 | 8715.38 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 56.09 | 0.00 | 01-JAN-00:10 | 8715.38 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 53.76 | 0.00 | 01-JAN-00:10 | 8828.72 | 19-JUN-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.46 | 0.00 | 01-JAN-00:10 | 4603.52 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.46 | 0.00 | 01-JAN-00:10 | 4603.52 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 53.30 | 0.00 | 01-JAN-00:10 | 8828.72 | 19-JUN-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 53.30 | 0.00 | 01-JAN-00:10 | 8828.72 | 19-JUN-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 81.67 | 0.00 | 01-JAN-00:10 | 13132.04 | 02-OCT-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.56 | 0.00 | 01-JAN-00:10 | 6121.82 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.56 | 0.00 | 01-JAN-00:10 | 6121.82 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 81.11 | 0.00 | 01-JAN-00:10 | 13132.04 | 02-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 81.11 | 0.00 | 01-JAN-00:10 | 13132.04 | 02-OCT-12:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 53.20 | 0.00 | 01-JAN-00:10 | 9784.89 | 26-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.63 | 0.00 | 01-JAN-00:10 | 4393.55 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.63 | 0.00 | 01-JAN-00:10 | 4393.55 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 52.58 | 0.00 | 01-JAN-00:10 | 9784.89 | 26-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 52.58 | 0.00 | 01-JAN-00:10 | 9784.89 | 26-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 52.44 | 0.00 | 01-JAN-00:10 | 7419.40 | 17-JUL-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.07 | 0.00 | 01-JAN-00:10 | 3453.59 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.07 | 0.00 | 01-JAN-00:10 | 3453.59 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 52.37 | 0.00 | 01-JAN-00:10 | 7419.40 | 17-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 52.37 | 0.00 | 01-JAN-00:10 | 7419.40 | 17-JUL-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 51.31 | 0.00 | 01-JAN-00:10 | 7905.71 | 14-AUG-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1698.42 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1698.42 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 51.30 | 0.00 | 01-JAN-00:10 | 7905.71 | 14-AUG-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 51.30 | 0.00 | 01-JAN-00:10 | 7905.71 | 14-AUG-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 87.24 | 0.00 | 01-JAN-00:10 | 14633.20 | 28-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.98 | 0.00 | 01-JAN-00:10 | 8619.55 | 06-DEC-07:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.98 | 0.00 | 01-JAN-00:10 | 8619.55 | 06-DEC-07:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 84.26 | 0.00 | 01-JAN-00:10 | 14633.20 | 28-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 84.26 | 0.00 | 01-JAN-00:10 | 14633.20 | 28-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 49.10 | 0.00 | 01-JAN-00:10 | 7933.48 | 26-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 1425.26 | 13-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 1425.26 | 13-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 49.08 | 0.00 | 01-JAN-00:10 | 7933.48 | 26-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 49.08 | 0.00 | 01-JAN-00:10 | 7933.48 | 26-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 53.64 | 0.00 | 01-JAN-00:10 | 7694.38 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.13 | 0.00 | 01-JAN-00:10 | 4291.44 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.13 | 0.00 | 01-JAN-00:10 | 4291.44 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 53.51 | 0.00 | 01-JAN-00:10 | 7694.38 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 53.51 | 0.00 | 01-JAN-00:10 | 7694.38 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 51.17 | 0.00 | 01-JAN-00:10 | 8449.90 | 19-JUN-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.07 | 0.00 | 01-JAN-00:10 | 2695.75 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.07 | 0.00 | 01-JAN-00:10 | 2695.75 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 51.10 | 0.00 | 01-JAN-00:10 | 8449.90 | 19-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 51.10 | 0.00 | 01-JAN-00:10 | 8449.90 | 19-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 78.60 | 0.00 | 01-JAN-00:10 | 11587.73 | 02-OCT-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.06 | 0.00 | 01-JAN-00:10 | 3153.64 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.06 | 0.00 | 01-JAN-00:10 | 3153.64 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 78.54 | 0.00 | 01-JAN-00:10 | 11587.73 | 02-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 78.54 | 0.00 | 01-JAN-00:10 | 11587.73 | 02-OCT-12:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 50.49 | 0.00 | 01-JAN-00:10 | 8990.82 | 26-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.09 | 0.00 | 01-JAN-00:10 | 2496.48 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.09 | 0.00 | 01-JAN-00:10 | 2496.48 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 50.40 | 0.00 | 01-JAN-00:10 | 8990.82 | 26-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 50.40 | 0.00 | 01-JAN-00:10 | 8990.82 | 26-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 38.47 | 0.00 | 01-JAN-00:10 | 5186.70 | 23-JAN-12:50 |
PlantLoopHeatingDemand:Plant | 38.47 | 0.00 | 01-JAN-00:10 | 5186.70 | 23-JAN-12:50 |
WaterSystems:PlantLoopHeatingDemand | 38.47 | 0.00 | 01-JAN-00:10 | 5186.70 | 23-JAN-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 38.47 | 0.00 | 01-JAN-00:10 | 5186.70 | 23-JAN-12:50 |
EnergyTransfer:HVAC | 1603.22 | 0.00 | 01-JAN-00:10 | 283030.41 | 05-SEP-07:40 |
HeatingCoils:EnergyTransfer | 14.62 | 0.00 | 01-JAN-00:10 | 102578.04 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 1588.60 | 0.00 | 01-JAN-00:10 | 283030.41 | 05-SEP-07:40 |
EnergyTransfer:Plant | 38.47 | 0.00 | 01-JAN-00:10 | 5186.70 | 23-JAN-12:50 |
WaterSystems:EnergyTransfer | 38.47 | 0.00 | 01-JAN-00:10 | 5186.70 | 23-JAN-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 38.47 | 0.00 | 01-JAN-00:10 | 5186.70 | 23-JAN-12:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -294.125 | 0.000 | 0.000 | 32.689 | 63.485 | 247.342 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -49.391 |
CORE_MID | 0.000 | 0.000 | 0.004 | -199.830 | 0.000 | 0.000 | 32.945 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -23.205 |
CORE_TOP | 0.000 | 0.000 | 0.145 | -200.399 | 0.000 | 0.000 | 33.414 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -23.246 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 1.032 | -56.090 | 0.000 | 0.000 | 7.208 | 9.276 | 26.688 | 23.485 | 0.000 | 1.766 | 9.604 | 0.000 | -19.170 | 0.000 | -3.800 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.457 | -53.300 | 0.000 | 0.000 | 4.476 | 5.815 | 16.895 | 40.122 | 0.000 | 1.160 | 0.000 | 0.000 | -12.052 | 0.000 | -2.633 | -0.941 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.560 | -81.106 | 0.000 | 0.000 | 7.037 | 9.151 | 26.688 | 65.941 | 0.000 | 1.728 | 0.001 | 0.000 | -19.118 | 0.000 | -4.172 | -6.708 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.626 | -52.576 | 0.000 | 0.000 | 4.577 | 5.857 | 16.895 | 38.755 | 0.000 | 1.155 | 0.454 | 0.000 | -13.112 | 0.000 | -2.631 | -0.001 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.066 | -52.371 | 0.000 | 0.000 | 7.109 | 9.254 | 26.688 | 23.492 | 0.000 | 0.977 | 7.624 | 0.000 | -20.606 | 0.000 | -2.233 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.017 | -51.296 | 0.000 | 0.000 | 4.420 | 5.808 | 16.895 | 40.103 | 0.000 | 0.625 | 0.000 | 0.000 | -13.247 | 0.000 | -1.585 | -1.740 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 2.979 | -84.257 | 0.000 | 0.000 | 6.990 | 9.139 | 26.688 | 65.994 | 0.000 | 15.441 | 0.002 | 0.000 | -21.047 | 0.000 | -17.058 | -4.869 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.022 | -49.075 | 0.000 | 0.000 | 4.483 | 5.847 | 16.895 | 38.781 | 0.000 | 0.616 | 0.000 | 0.000 | -14.441 | 0.000 | -1.587 | -1.541 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.130 | -53.506 | 0.000 | 0.000 | 7.094 | 9.276 | 26.688 | 23.321 | 0.000 | 1.477 | 9.629 | 0.000 | -20.635 | 0.000 | -3.474 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.067 | -51.104 | 0.000 | 0.000 | 3.282 | 5.815 | 16.895 | 40.026 | 0.000 | 0.976 | 0.001 | 0.000 | -12.836 | 0.000 | -2.378 | -0.743 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.058 | -78.540 | 0.000 | 0.000 | 6.967 | 9.151 | 26.688 | 65.823 | 0.000 | 1.447 | 0.001 | 0.000 | -20.370 | 0.000 | -3.758 | -7.465 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.088 | -50.400 | 0.000 | 0.000 | 4.512 | 5.857 | 16.895 | 38.701 | 0.000 | 0.961 | 0.001 | 0.000 | -14.031 | 0.000 | -2.387 | -0.195 |
TOPFLOOR_PLENUM | 5.901 | -66.505 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.277 | 64.128 | 0.000 | 0.000 | 0.000 | -5.801 | -0.001 |
MIDFLOOR_PLENUM | 1.956 | -35.565 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.303 | 37.494 | 0.000 | 0.000 | 0.000 | -6.189 | -0.000 |
FIRSTFLOOR_PLENUM | 0.813 | -41.791 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.782 | 44.271 | 0.000 | 0.000 | 0.000 | -5.075 | 0.000 |
Total Facility | 8.670 | -143.861 | 6.251 | -1407.975 | 0.000 | 0.000 | 167.202 | 280.702 | 762.041 | 504.545 | 0.000 | 34.691 | 173.209 | 0.000 | -200.665 | 0.000 | -64.760 | -120.048 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 10-OCT-04:02 | 0.00 | 0.00 | 0.00 | -44546.33 | 0.00 | 0.00 | 0.00 | 615.87 | 5138.45 | 0.00 | 0.00 | 0.00 | 38792.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 11-SEP-04:02 | 0.00 | 0.00 | 0.00 | -33850.24 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 30059.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 11-SEP-04:02 | 0.00 | 0.00 | 0.00 | -37877.68 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 34086.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-AUG-16:11 | 0.00 | 0.00 | 0.00 | -14961.27 | 0.00 | 0.00 | 23.96 | 40.03 | 501.96 | 2509.56 | 0.00 | 1337.45 | 10548.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 18-JUN-09:12 | 0.00 | 0.00 | 0.00 | -13242.55 | 0.00 | 0.00 | 12.63 | 25.34 | 317.77 | 7194.37 | 0.00 | 191.69 | 5500.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 15-OCT-13:52 | 0.00 | 0.00 | 0.00 | -17736.56 | 0.00 | 0.00 | 22.61 | 40.03 | 501.96 | 9597.99 | 0.00 | 159.25 | 7414.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 13-AUG-16:51 | 0.00 | 0.00 | 0.00 | -15664.63 | 0.00 | 0.00 | 10.16 | 25.34 | 317.76 | 8152.63 | 0.00 | 699.79 | 6458.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 27-AUG-17:41 | 0.00 | 0.00 | 0.00 | -11978.98 | 0.00 | 0.00 | 0.00 | 40.03 | 501.96 | 2265.23 | 0.00 | 432.95 | 8738.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUL-10:22 | 0.00 | 0.00 | 0.00 | -11561.49 | 0.00 | 0.00 | 15.14 | 25.34 | 317.77 | 5138.19 | 0.00 | 68.82 | 5996.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 28-JUN-17:00 | 0.00 | 0.00 | 0.00 | -14629.24 | 0.00 | 0.00 | 158.15 | 400.23 | 836.60 | 3089.94 | 0.00 | 14691.56 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4547.24 |
PERIMETER_BOT_ZN_4 | 27-AUG-17:41 | 0.00 | 0.00 | 0.00 | -12993.06 | 0.00 | 0.00 | 0.00 | 25.34 | 317.76 | 6044.54 | 0.00 | 247.22 | 6358.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-18:11 | 0.00 | 0.00 | 0.00 | -12587.81 | 0.00 | 0.00 | 0.00 | 40.03 | 501.96 | 4127.26 | 0.00 | 828.56 | 7089.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUN-09:21 | 0.00 | 0.00 | 0.00 | -13060.27 | 0.00 | 0.00 | 13.82 | 25.34 | 317.77 | 7007.64 | 0.00 | 36.87 | 5658.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 25-DEC-13:32 | 0.00 | 0.00 | 0.00 | -14842.28 | 0.00 | 0.00 | 24.13 | 40.03 | 501.96 | 12724.17 | 0.00 | 0.00 | 1608.13 | 0.00 | -0.00 | 0.00 | -56.14 | 0.00 |
PERIMETER_MID_ZN_4 | 25-JUN-17:31 | 0.00 | 0.00 | 0.00 | -13774.59 | 0.00 | 0.00 | 0.00 | 25.34 | 317.76 | 8625.28 | 0.00 | 459.35 | 4346.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 28-JUN-15:00 | 0.00 | -13878.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.71 | 13290.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 19-JUN-14:10 | 0.00 | -6452.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 726.47 | 5725.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 19-JUN-12:06 | 0.00 | -8070.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.63 | 7756.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-JUL-04:02 | 0.00 | 10793.11 | 0.00 | -224188.71 | 0.00 | 0.00 | 0.00 | 3119.77 | 18045.99 | 0.00 | 0.00 | 617.52 | 194974.13 | 0.00 | -3361.80 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-07:02 | 0.00 | 0.00 | 17761.73 | 0.00 | 0.00 | 0.00 | 912.84 | 1847.70 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23697.13 |
CORE_TOP | 02-JAN-06:01 | 0.00 | 0.00 | 26666.99 | 0.00 | 0.00 | 0.00 | 493.03 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -30950.76 |
PERIMETER_TOP_ZN_3 | 02-JAN-05:02 | 0.00 | 0.00 | 12158.77 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1889.02 | 0.00 | -225.10 | -10843.78 |
PERIMETER_TOP_ZN_2 | 02-JAN-05:02 | 0.00 | 0.00 | 8560.17 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1285.62 | 0.00 | -152.43 | -7628.00 |
PERIMETER_TOP_ZN_1 | 02-JAN-06:01 | 0.00 | 0.00 | 12347.91 | 0.00 | 0.00 | 0.00 | 105.49 | 129.83 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2062.59 | 0.00 | -91.97 | -11097.95 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:02 | 0.00 | 0.00 | 8309.17 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1294.93 | 0.00 | -155.09 | -7365.03 |
PERIMETER_BOT_ZN_3 | 02-JAN-06:01 | 0.00 | 0.00 | 7570.54 | 0.00 | 0.00 | 0.00 | 102.60 | 129.83 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2187.47 | 0.00 | -50.49 | -6234.30 |
PERIMETER_BOT_ZN_2 | 03-JAN-07:03 | 0.00 | 0.00 | 4671.69 | 0.00 | 0.00 | 0.00 | 122.37 | 246.59 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1146.84 | 0.00 | -75.23 | -4242.27 |
PERIMETER_BOT_ZN_1 | 06-DEC-07:10 | 0.00 | 0.00 | 9043.29 | 0.00 | 0.00 | 0.00 | 193.30 | 389.51 | 669.28 | 0.00 | 0.00 | 0.00 | 12884.26 | 0.00 | -3173.55 | 0.00 | -20006.09 | 0.00 |
PERIMETER_BOT_ZN_4 | 08-FEB-07:02 | 0.00 | 0.00 | 4626.40 | 0.00 | 0.00 | 0.00 | 121.49 | 246.58 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1350.81 | 0.00 | -22.48 | -4044.86 |
PERIMETER_MID_ZN_3 | 02-JAN-06:01 | 0.00 | 0.00 | 9509.96 | 0.00 | 0.00 | 0.00 | 105.10 | 129.83 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2113.37 | 0.00 | -76.44 | -8224.36 |
PERIMETER_MID_ZN_2 | 02-JAN-06:01 | 0.00 | 0.00 | 5943.64 | 0.00 | 0.00 | 0.00 | 66.39 | 82.19 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1437.94 | 0.00 | -51.15 | -5026.82 |
PERIMETER_MID_ZN_1 | 02-JAN-06:01 | 0.00 | 0.00 | 9014.35 | 0.00 | 0.00 | 0.00 | 101.76 | 129.83 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2268.51 | 0.00 | -80.87 | -7565.83 |
PERIMETER_MID_ZN_4 | 02-JAN-06:01 | 0.00 | 0.00 | 5711.31 | 0.00 | 0.00 | 0.00 | 65.83 | 82.19 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1438.60 | 0.00 | -51.87 | -4792.54 |
TOPFLOOR_PLENUM | 07-DEC-07:01 | 9534.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -298.13 | -9236.41 |
MIDFLOOR_PLENUM | 25-DEC-11:32 | 4408.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -32.82 | -4375.44 |
FIRSTFLOOR_PLENUM | 24-NOV-06:01 | 7336.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -180.65 | -7155.50 |
Total Facility | 02-JAN-07:02 | 5435.45 | 5783.51 | 127290.42 | -5783.51 | 0.00 | 0.00 | 4555.05 | 9359.67 | 21853.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20871.13 | 0.00 | -17774.76 | -129847.98 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.1772 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.7041 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.6055 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0663 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.3008 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.0585 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.0886 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4364 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.8027 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4427 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.1504 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5621 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1328 | 3.1328 | 0.8083 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3354 | 2.3354 | 0.7847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5809 | 2.5809 | 0.8181 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9496 | 0.9496 | 0.1899 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8062 | 0.8062 | 0.1612 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0419 | 1.0419 | 0.2084 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9222 | 0.9222 | 0.1844 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7637 | 0.7637 | 0.1703 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6958 | 0.6958 | 0.1392 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8451 | 0.8451 | 0.1707 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7398 | 0.7398 | 0.1480 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8064 | 0.8064 | 0.1653 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7534 | 0.7534 | 0.1507 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8952 | 0.8952 | 0.1790 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8151 | 0.8151 | 0.1630 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.1772 | 5.7041 | 6.1772 | 1.4364 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.6055 | 5.0663 | 5.6055 | 1.4427 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.3008 | 6.0585 | 6.3008 | 1.5621 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5664 | 1.5664 | 0.8083 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1677 | 1.1677 | 0.7847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2904 | 1.2904 | 0.8181 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4748 | 0.4748 | 0.1899 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4031 | 0.4031 | 0.1612 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5210 | 0.5210 | 0.2084 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4611 | 0.4611 | 0.1844 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3819 | 0.3819 | 0.1703 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3479 | 0.3479 | 0.1392 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4225 | 0.4225 | 0.1707 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3699 | 0.3699 | 0.1480 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4032 | 0.4032 | 0.1653 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3767 | 0.3767 | 0.1507 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4476 | 0.4476 | 0.1790 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4076 | 0.4076 | 0.1630 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.0886 | 1.4364 | 1.4364 | 1.4364 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.8027 | 1.4427 | 1.4427 | 1.4427 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.1504 | 1.5621 | 1.5621 | 1.5621 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 73.50 |
Number of hours cooling loads not met | 462.33 |
Number of hours not met | 535.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 12.35 | 93091.75 | 2.83 | 30205.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 455.28 | 95685.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 280.70 | 28079.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 71.92 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 641.30 | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 12.98 | 926.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 148.05 | 28932.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 94.19 | 9054.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 762.04 | 1743.34 |
Natural Gas | 0.00 | 97.02 |
Additional | 0.00 | 0.00 |
Total | 762.04 | 1840.37 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 56.34 |
Space Heating | 2.48 |
Space Cooling | 91.38 |
Fans (All) | 29.72 |
Service Water Heating | 0.00 |
Receptacle Equipment | 152.95 |
Miscellaneous (All) | 349.92 |
Subtotal | 349.92 |
Natural Gas [MJ/m2] | |
Space Heating | 0.57 |
Service Water Heating | 18.91 |
Miscellaneous (All) | 19.47 |
Subtotal | 19.47 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.25 |
Space Heating | 0.83 |
Space Cooling | 24.74 |
Fans (All) | 8.04 |
Service Water Heating | 5.12 |
Receptacle Equipment | 41.41 |
Miscellaneous | 4.61 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2429. | 8760. |
BLDG_EQUIP_SCH | 4487. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8581.67 | 178.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8734.33 | 25.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8725.00 | 35.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8615.67 | 144.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8572.83 | 187.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8580.17 | 179.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8549.50 | 210.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8715.50 | 44.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8564.50 | 195.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8565.50 | 194.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8556.17 | 203.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8625.50 | 134.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8566.50 | 193.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8580.50 | 179.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8537.17 | 222.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8505.50 | 254.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8736.67 | 23.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8753.50 | 6.50 | 0.00 | 0.00 | 0.00 |
Min | 8505.50 | 6.50 | 0.00 | 0.00 | 0.00 |
Max | 8753.50 | 254.50 | 0.00 | 0.00 | 0.00 |
Average | 8614.79 | 145.21 | 0.00 | 0.00 | 0.00 |
Sum | 155066.17 | 2613.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128269.00 | 35.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128300.00 | 4.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128299.67 | 4.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24855.00 | 54.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128300.00 | 54.00 | 0.00 | 0.00 | 0.00 |
Average | 34137.93 | 5.41 | 0.00 | 0.00 | 0.00 |
Sum | 614482.67 | 97.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8430.67 | 329.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8507.50 | 252.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8584.33 | 175.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8345.50 | 414.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8327.00 | 433.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8331.83 | 428.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8340.17 | 419.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8384.00 | 376.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8333.83 | 426.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8299.67 | 460.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8336.17 | 423.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8302.33 | 457.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8297.17 | 462.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8285.17 | 474.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8301.67 | 458.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7970.50 | 789.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8396.00 | 364.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8442.83 | 317.17 | 0.00 | 0.00 | 0.00 |
Min | 7970.50 | 175.67 | 0.00 | 0.00 | 0.00 |
Max | 8584.33 | 789.50 | 0.00 | 0.00 | 0.00 |
Average | 8345.35 | 414.65 | 0.00 | 0.00 | 0.00 |
Sum | 150216.33 | 7463.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128138.33 | 165.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128206.67 | 97.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128209.83 | 94.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24905.50 | 3.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24906.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24905.50 | 3.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24753.00 | 156.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24881.33 | 27.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24895.00 | 14.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128209.83 | 165.67 | 0.00 | 0.00 | 0.00 |
Average | 34111.95 | 31.38 | 0.00 | 0.00 | 0.00 |
Sum | 614015.17 | 564.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:17
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194821E+11 | 36717.85 | 09-JAN-06:03 | 9.83 | 9.83 | 0.198777E+10 | 2606.69 | 23-JAN-14:09 | 21.83 | 11.36 |
February | 0.159488E+11 | 33981.28 | 01-FEB-06:03 | 5.00 | 3.59 | 0.180344E+10 | 2606.74 | 15-FEB-14:00 | 20.00 | 13.98 |
March | 0.209383E+11 | 38359.89 | 23-MAR-05:03 | 9.95 | 6.26 | 0.215769E+10 | 2606.69 | 17-MAR-09:00 | 9.95 | 6.26 |
April | 0.249133E+11 | 41381.93 | 08-APR-05:03 | 12.00 | 4.56 | 0.191679E+10 | 2606.67 | 03-APR-09:30 | 12.00 | 4.56 |
May | 0.281027E+11 | 43779.92 | 30-MAY-04:03 | 18.00 | 9.20 | 0.207667E+10 | 2606.65 | 12-MAY-09:09 | 18.00 | 9.20 |
June | 0.302448E+11 | 44288.68 | 12-JUN-04:02 | 20.00 | 10.45 | 0.207060E+10 | 2606.66 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.295979E+11 | 43914.83 | 27-JUL-04:03 | 22.00 | 18.54 | 0.192517E+10 | 2606.70 | 28-JUL-13:50 | 29.50 | 20.43 |
August | 0.311252E+11 | 43617.75 | 07-AUG-04:03 | 21.00 | 17.63 | 0.216054E+10 | 2606.75 | 29-AUG-13:39 | 28.67 | 21.18 |
September | 0.283775E+11 | 43928.56 | 12-SEP-04:02 | 22.28 | 18.52 | 0.191963E+10 | 2606.66 | 15-SEP-09:09 | 25.45 | 16.44 |
October | 0.258214E+11 | 44539.64 | 10-OCT-04:02 | 18.00 | 12.10 | 0.199492E+10 | 2606.67 | 17-OCT-09:30 | 25.00 | 10.00 |
November | 0.216301E+11 | 43960.62 | 13-NOV-05:03 | 17.00 | 17.00 | 0.197379E+10 | 2606.76 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.179426E+11 | 32733.23 | 27-DEC-06:03 | 6.00 | 2.08 | 0.191817E+10 | 2606.65 | 13-DEC-10:09 | 6.00 | 2.08 |
Annual Sum or Average | 0.294125E+12 | 0.239052E+11 | ||||||||
Minimum of Months | 0.159488E+11 | 32733.23 | 5.00 | 2.08 | 0.180344E+10 | 2606.65 | 6.00 | 2.08 | ||
Maximum of Months | 0.311252E+11 | 44539.64 | 22.28 | 18.54 | 0.216054E+10 | 2606.76 | 33.17 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199553E+10 | 5936.24 | 31-JAN-15:40 | 28.67 | 10.84 | 0.00 | 0.00 | 01-JAN-00:10 | 28.67 | 10.84 |
February | 0.104822E+10 | 4252.70 | 23-FEB-14:30 | 18.00 | 10.57 | 0.00 | 0.00 | 01-FEB-00:10 | 18.00 | 10.57 |
March | 0.229730E+10 | 7164.00 | 16-MAR-15:30 | 28.80 | 13.83 | 0.00 | 0.00 | 01-MAR-00:10 | 28.80 | 13.83 |
April | 0.638436E+10 | 11301.60 | 14-APR-14:50 | 34.83 | 14.49 | 0.00 | 0.00 | 01-APR-00:10 | 34.83 | 14.49 |
May | 0.822394E+10 | 11346.57 | 19-MAY-14:20 | 36.00 | 14.39 | 0.00 | 0.00 | 01-MAY-00:10 | 36.00 | 14.39 |
June | 0.114165E+11 | 13878.17 | 28-JUN-15:00 | 42.00 | 19.34 | 0.00 | 0.00 | 01-JUN-00:10 | 42.00 | 19.34 |
July | 0.100615E+11 | 12991.26 | 20-JUL-14:20 | 39.33 | 20.22 | 0.00 | 0.00 | 01-JUL-00:10 | 39.33 | 20.22 |
August | 0.984140E+10 | 12997.16 | 09-AUG-14:00 | 38.00 | 21.22 | 0.00 | 0.00 | 01-AUG-00:10 | 38.00 | 21.22 |
September | 0.757531E+10 | 12137.73 | 07-SEP-15:00 | 37.20 | 19.77 | 0.00 | 0.00 | 01-SEP-00:10 | 37.20 | 19.77 |
October | 0.443207E+10 | 11014.44 | 02-OCT-14:20 | 35.00 | 19.60 | 0.00 | 0.00 | 01-OCT-00:10 | 35.00 | 19.60 |
November | 0.207150E+10 | 7379.41 | 01-NOV-15:30 | 28.50 | 15.96 | 0.00 | 0.00 | 01-NOV-00:10 | 28.50 | 15.96 |
December | 0.115797E+10 | 4761.69 | 22-DEC-16:00 | 25.00 | 10.09 | 0.00 | 0.00 | 01-DEC-00:10 | 25.00 | 10.09 |
Annual Sum or Average | 0.665056E+11 | 0.00 | ||||||||
Minimum of Months | 0.104822E+10 | 4252.70 | 18.00 | 10.09 | 0.00 | 0.00 | 18.00 | 10.09 | ||
Maximum of Months | 0.114165E+11 | 13878.17 | 42.00 | 21.22 | 0.00 | 0.00 | 42.00 | 21.22 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.634349E+09 | 1886.27 | 27-JAN-16:40 | 26.33 | 9.40 | 0.00 | 0.00 | 01-JAN-00:10 | 26.33 | 9.40 |
February | 0.397013E+09 | 1467.97 | 09-FEB-07:02 | 6.17 | 4.62 | 0.00 | 0.00 | 01-FEB-00:10 | 6.17 | 4.62 |
March | 0.860976E+09 | 2513.46 | 28-MAR-06:01 | 3.90 | 0.38 | 0.00 | 0.00 | 01-MAR-00:10 | 3.90 | 0.38 |
April | 0.315599E+10 | 4573.81 | 24-APR-15:30 | 33.50 | 13.37 | 0.00 | 0.00 | 01-APR-00:10 | 33.50 | 13.37 |
May | 0.441587E+10 | 5099.62 | 08-MAY-16:00 | 34.00 | 13.77 | 0.00 | 0.00 | 01-MAY-00:10 | 34.00 | 13.77 |
June | 0.617969E+10 | 6451.33 | 19-JUN-14:10 | 38.83 | 18.35 | 0.00 | 0.00 | 01-JUN-00:10 | 38.83 | 18.35 |
July | 0.575909E+10 | 6161.23 | 31-JUL-16:00 | 39.00 | 19.54 | 0.00 | 0.00 | 01-JUL-00:10 | 39.00 | 19.54 |
August | 0.570630E+10 | 6339.79 | 14-AUG-15:20 | 38.00 | 19.72 | 0.00 | 0.00 | 01-AUG-00:10 | 38.00 | 19.72 |
September | 0.467427E+10 | 5877.43 | 05-SEP-16:00 | 33.80 | 20.30 | 0.00 | 0.00 | 01-SEP-00:10 | 33.80 | 20.30 |
October | 0.254045E+10 | 5688.77 | 02-OCT-15:30 | 34.50 | 19.17 | 0.00 | 0.00 | 01-OCT-00:10 | 34.50 | 19.17 |
November | 0.910519E+09 | 2934.77 | 01-NOV-16:00 | 28.00 | 15.72 | 0.00 | 0.00 | 01-NOV-00:10 | 28.00 | 15.72 |
December | 0.330261E+09 | 2474.31 | 14-DEC-07:01 | 1.33 | -1.0 | 0.00 | 0.00 | 01-DEC-00:10 | 1.33 | -1.0 |
Annual Sum or Average | 0.355648E+11 | 0.00 | ||||||||
Minimum of Months | 0.330261E+09 | 1467.97 | 1.33 | -1.0 | 0.00 | 0.00 | 1.33 | -1.0 | ||
Maximum of Months | 0.617969E+10 | 6451.33 | 39.00 | 20.30 | 0.00 | 0.00 | 39.00 | 20.30 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137364E+10 | 2816.04 | 27-JAN-17:00 | 26.00 | 9.22 | 0.00 | 0.00 | 01-JAN-00:10 | 26.00 | 9.22 |
February | 0.811917E+09 | 2510.87 | 01-FEB-07:05 | 5.00 | 3.59 | 0.00 | 0.00 | 01-FEB-00:10 | 5.00 | 3.59 |
March | 0.146672E+10 | 3018.25 | 20-MAR-16:00 | 28.30 | 14.35 | 0.00 | 0.00 | 01-MAR-00:10 | 28.30 | 14.35 |
April | 0.365697E+10 | 5000.38 | 14-APR-17:08 | 34.83 | 14.48 | 0.00 | 0.00 | 01-APR-00:10 | 34.83 | 14.48 |
May | 0.474982E+10 | 5921.45 | 08-MAY-12:07 | 32.17 | 13.12 | 0.00 | 0.00 | 01-MAY-00:10 | 32.17 | 13.12 |
June | 0.625702E+10 | 8069.92 | 19-JUN-12:06 | 37.17 | 17.20 | 0.00 | 0.00 | 01-JUN-00:10 | 37.17 | 17.20 |
July | 0.598445E+10 | 7911.27 | 31-JUL-12:09 | 36.17 | 18.75 | 0.00 | 0.00 | 01-JUL-00:10 | 36.17 | 18.75 |
August | 0.609729E+10 | 7447.81 | 18-AUG-12:09 | 36.17 | 21.47 | 0.00 | 0.00 | 01-AUG-00:10 | 36.17 | 21.47 |
September | 0.527692E+10 | 6763.55 | 06-SEP-17:08 | 35.72 | 20.47 | 0.00 | 0.00 | 01-SEP-00:10 | 35.72 | 20.47 |
October | 0.347681E+10 | 5647.93 | 06-OCT-17:08 | 33.67 | 14.88 | 0.00 | 0.00 | 01-OCT-00:10 | 33.67 | 14.88 |
November | 0.183801E+10 | 3713.75 | 02-NOV-16:00 | 26.00 | 15.13 | 0.00 | 0.00 | 01-NOV-00:10 | 26.00 | 15.13 |
December | 0.801489E+09 | 2859.96 | 06-DEC-07:01 | -0.5 | -5.0 | 0.00 | 0.00 | 01-DEC-00:10 | -0.5 | -5.0 |
Annual Sum or Average | 0.417910E+11 | 0.00 | ||||||||
Minimum of Months | 0.801489E+09 | 2510.87 | -0.5 | -5.0 | 0.00 | 0.00 | -0.5 | -5.0 | ||
Maximum of Months | 0.625702E+10 | 8069.92 | 37.17 | 21.47 | 0.00 | 0.00 | 37.17 | 21.47 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115891E+11 | 13532.11 | 27-JAN-17:00 | 26.00 | 9.22 | 0.193927E+10 | 2606.64 | 09-JAN-10:09 | 26.00 | 9.22 |
February | 0.941438E+10 | 12342.24 | 01-FEB-17:00 | 15.00 | 6.61 | 0.175021E+10 | 2606.65 | 10-FEB-14:09 | 15.83 | 11.90 |
March | 0.126164E+11 | 18935.34 | 20-MAR-05:03 | 11.18 | 7.43 | 0.212669E+10 | 2606.66 | 17-MAR-09:00 | 11.18 | 7.43 |
April | 0.174491E+11 | 31677.71 | 15-APR-05:03 | 20.83 | 11.87 | 0.191126E+10 | 2606.66 | 03-APR-09:30 | 20.83 | 11.87 |
May | 0.204779E+11 | 33317.03 | 30-MAY-04:03 | 18.00 | 9.20 | 0.207397E+10 | 2606.64 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.231384E+11 | 33522.82 | 12-JUN-04:02 | 20.00 | 10.45 | 0.206883E+10 | 2606.65 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.224705E+11 | 33150.48 | 06-JUL-04:02 | 22.00 | 11.55 | 0.192300E+10 | 2606.69 | 05-JUL-09:09 | 22.00 | 11.55 |
August | 0.229096E+11 | 32825.94 | 23-AUG-04:03 | 22.00 | 12.42 | 0.215841E+10 | 2606.67 | 28-AUG-09:09 | 31.50 | 20.35 |
September | 0.202391E+11 | 33852.07 | 11-SEP-04:02 | 22.28 | 18.64 | 0.191747E+10 | 2606.67 | 22-SEP-09:09 | 24.00 | 17.33 |
October | 0.167509E+11 | 33136.03 | 03-OCT-04:02 | 22.83 | 19.31 | 0.198537E+10 | 2606.66 | 03-OCT-13:30 | 33.00 | 20.21 |
November | 0.126064E+11 | 27213.08 | 03-NOV-05:03 | 16.00 | 12.46 | 0.195065E+10 | 2606.71 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.101675E+11 | 12379.59 | 28-DEC-17:00 | 18.60 | 7.88 | 0.184392E+10 | 2606.57 | 22-DEC-10:09 | 18.60 | 7.88 |
Annual Sum or Average | 0.199829E+12 | 0.236491E+11 | ||||||||
Minimum of Months | 0.941438E+10 | 12342.24 | 11.18 | 6.61 | 0.175021E+10 | 2606.57 | 11.18 | 7.43 | ||
Maximum of Months | 0.231384E+11 | 33852.07 | 26.00 | 19.31 | 0.215841E+10 | 2606.71 | 38.17 | 20.35 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103789E+11 | 13435.56 | 27-JAN-17:00 | 26.00 | 9.22 | 0.185829E+10 | 2606.60 | 26-JAN-14:09 | 26.00 | 9.22 |
February | 0.861031E+10 | 11763.95 | 22-FEB-17:00 | 20.00 | 11.26 | 0.166403E+10 | 2606.55 | 03-FEB-14:00 | 20.00 | 11.26 |
March | 0.117915E+11 | 15651.66 | 17-MAR-16:00 | 26.60 | 14.13 | 0.205576E+10 | 2606.65 | 14-MAR-13:50 | 26.60 | 14.13 |
April | 0.176231E+11 | 31622.78 | 15-APR-05:03 | 20.83 | 11.87 | 0.190278E+10 | 2606.65 | 06-APR-09:30 | 20.83 | 11.87 |
May | 0.212244E+11 | 36102.66 | 08-MAY-04:03 | 22.00 | 10.09 | 0.207185E+10 | 2606.64 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.253614E+11 | 36777.82 | 12-JUN-04:02 | 20.00 | 10.45 | 0.206876E+10 | 2606.65 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.244359E+11 | 36665.63 | 03-JUL-04:02 | 20.83 | 7.74 | 0.192348E+10 | 2606.71 | 21-JUL-09:09 | 31.17 | 20.71 |
August | 0.244295E+11 | 36377.96 | 22-AUG-04:02 | 23.83 | 15.27 | 0.215833E+10 | 2606.70 | 18-AUG-09:09 | 23.83 | 15.27 |
September | 0.208477E+11 | 37880.47 | 11-SEP-04:02 | 22.28 | 18.64 | 0.191652E+10 | 2606.66 | 22-SEP-09:09 | 24.00 | 17.33 |
October | 0.156923E+11 | 35467.69 | 02-OCT-04:02 | 26.00 | 17.05 | 0.195805E+10 | 2606.64 | 05-OCT-09:09 | 26.50 | 16.68 |
November | 0.111152E+11 | 15998.17 | 01-NOV-16:00 | 28.00 | 15.72 | 0.188897E+10 | 2606.68 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.888819E+10 | 11826.09 | 22-DEC-17:00 | 24.00 | 9.52 | 0.171295E+10 | 2606.59 | 22-DEC-14:39 | 24.00 | 9.52 |
Annual Sum or Average | 0.200398E+12 | 0.231798E+11 | ||||||||
Minimum of Months | 0.861031E+10 | 11763.95 | 20.00 | 7.74 | 0.166403E+10 | 2606.55 | 18.00 | 9.22 | ||
Maximum of Months | 0.253614E+11 | 37880.47 | 28.00 | 18.64 | 0.215833E+10 | 2606.71 | 38.17 | 20.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187454E+10 | 2984.12 | 31-JAN-16:30 | 29.00 | 10.73 | 0.362323E+09 | 549.48 | 06-JAN-14:00 | 29.00 | 10.73 |
February | 0.146325E+10 | 2186.13 | 22-FEB-16:20 | 20.67 | 11.54 | 0.320013E+09 | 549.46 | 22-FEB-14:00 | 20.67 | 11.54 |
March | 0.238611E+10 | 4335.95 | 16-MAR-16:00 | 28.80 | 13.95 | 0.406387E+09 | 549.50 | 21-MAR-13:30 | 25.25 | 12.80 |
April | 0.470385E+10 | 10113.75 | 30-APR-15:52 | 33.00 | 11.94 | 0.395639E+09 | 549.50 | 06-APR-09:30 | 33.00 | 11.94 |
May | 0.650198E+10 | 12691.16 | 07-MAY-17:32 | 35.33 | 14.08 | 0.436258E+09 | 549.50 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.924580E+10 | 14866.86 | 25-JUN-18:21 | 37.00 | 14.68 | 0.437046E+09 | 549.50 | 19-JUN-13:09 | 37.00 | 14.68 |
July | 0.847231E+10 | 14960.34 | 16-JUL-17:51 | 36.00 | 21.58 | 0.406551E+09 | 549.51 | 21-JUL-09:09 | 31.17 | 20.71 |
August | 0.794858E+10 | 14961.52 | 13-AUG-16:11 | 38.00 | 20.37 | 0.455431E+09 | 549.51 | 18-AUG-09:09 | 32.50 | 20.95 |
September | 0.636578E+10 | 14399.36 | 17-SEP-13:13 | 34.80 | 17.97 | 0.403684E+09 | 549.50 | 13-SEP-09:09 | 34.80 | 17.97 |
October | 0.372085E+10 | 12192.41 | 02-OCT-04:02 | 26.00 | 17.05 | 0.397369E+09 | 549.50 | 03-OCT-13:30 | 33.00 | 20.21 |
November | 0.207960E+10 | 4299.87 | 01-NOV-15:30 | 28.50 | 15.96 | 0.374350E+09 | 549.49 | 16-NOV-14:00 | 18.00 | 12.18 |
December | 0.132756E+10 | 2142.69 | 22-DEC-16:40 | 24.33 | 9.71 | 0.327361E+09 | 547.90 | 22-DEC-14:00 | 24.33 | 9.71 |
Annual Sum or Average | 0.560902E+11 | 0.472241E+10 | ||||||||
Minimum of Months | 0.132756E+10 | 2142.69 | 20.67 | 9.71 | 0.320013E+09 | 547.90 | 18.00 | 9.71 | ||
Maximum of Months | 0.924580E+10 | 14961.52 | 38.00 | 21.58 | 0.455431E+09 | 549.51 | 37.00 | 20.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188583E+10 | 2783.61 | 27-JAN-10:40 | 21.33 | 7.83 | 0.246902E+09 | 347.87 | 24-JAN-14:39 | 21.33 | 7.83 |
February | 0.143839E+10 | 3077.50 | 23-FEB-10:30 | 15.00 | 11.05 | 0.218214E+09 | 347.87 | 23-FEB-10:09 | 15.00 | 11.05 |
March | 0.242474E+10 | 4405.24 | 23-MAR-10:30 | 22.70 | 10.73 | 0.270892E+09 | 347.88 | 14-MAR-13:50 | 22.70 | 10.73 |
April | 0.509811E+10 | 11307.76 | 30-APR-08:32 | 24.33 | 8.89 | 0.254339E+09 | 347.90 | 03-APR-09:20 | 24.33 | 8.89 |
May | 0.643275E+10 | 11591.37 | 28-MAY-08:43 | 26.50 | 11.27 | 0.277018E+09 | 348.13 | 18-MAY-09:00 | 26.50 | 11.27 |
June | 0.825946E+10 | 13242.52 | 18-JUN-09:12 | 32.67 | 17.60 | 0.276845E+09 | 348.16 | 08-JUN-09:00 | 32.67 | 17.60 |
July | 0.751205E+10 | 12900.08 | 23-JUL-10:02 | 33.17 | 22.19 | 0.257565E+09 | 348.11 | 05-JUL-09:00 | 33.17 | 22.19 |
August | 0.729524E+10 | 12942.08 | 13-AUG-09:32 | 32.67 | 21.08 | 0.288511E+09 | 348.14 | 01-AUG-09:00 | 32.67 | 21.08 |
September | 0.570164E+10 | 11783.50 | 10-SEP-10:32 | 32.73 | 19.21 | 0.255844E+09 | 348.40 | 08-SEP-09:00 | 32.73 | 19.21 |
October | 0.380544E+10 | 7889.45 | 02-OCT-04:02 | 26.00 | 17.05 | 0.259864E+09 | 347.89 | 17-OCT-09:20 | 24.67 | 9.84 |
November | 0.206868E+10 | 3762.76 | 01-NOV-10:30 | 24.00 | 16.09 | 0.249764E+09 | 347.89 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.137732E+10 | 1919.98 | 25-DEC-16:03 | 25.67 | 11.87 | 0.221295E+09 | 347.87 | 22-DEC-14:50 | 25.67 | 11.87 |
Annual Sum or Average | 0.532997E+11 | 0.307705E+10 | ||||||||
Minimum of Months | 0.137732E+10 | 1919.98 | 15.00 | 7.83 | 0.218214E+09 | 347.87 | 15.00 | 7.83 | ||
Maximum of Months | 0.825946E+10 | 13242.52 | 33.17 | 22.19 | 0.288511E+09 | 348.40 | 33.17 | 22.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.604574E+10 | 16196.05 | 15-JAN-14:02 | 23.00 | 10.38 | 0.399237E+09 | 549.70 | 31-JAN-14:00 | 28.00 | 11.02 |
February | 0.335066E+10 | 9145.90 | 23-FEB-14:00 | 18.00 | 10.78 | 0.350831E+09 | 549.50 | 13-FEB-14:00 | 18.00 | 10.78 |
March | 0.422748E+10 | 8690.73 | 16-MAR-13:40 | 27.53 | 13.09 | 0.423542E+09 | 549.51 | 09-MAR-14:00 | 27.53 | 13.09 |
April | 0.679586E+10 | 16258.86 | 30-APR-12:32 | 33.00 | 12.07 | 0.396533E+09 | 549.77 | 24-APR-13:00 | 33.00 | 12.07 |
May | 0.716802E+10 | 14815.45 | 07-MAY-12:53 | 34.00 | 14.12 | 0.435280E+09 | 549.50 | 16-MAY-13:00 | 36.00 | 15.44 |
June | 0.902082E+10 | 15885.41 | 25-JUN-17:41 | 38.00 | 15.02 | 0.436615E+09 | 549.50 | 19-JUN-13:09 | 38.00 | 15.02 |
July | 0.872368E+10 | 16188.12 | 30-JUL-17:41 | 38.00 | 18.99 | 0.406335E+09 | 549.70 | 31-JUL-13:00 | 37.00 | 19.00 |
August | 0.929976E+10 | 16634.66 | 13-AUG-16:11 | 38.00 | 20.37 | 0.455422E+09 | 549.79 | 09-AUG-13:00 | 38.00 | 20.37 |
September | 0.878776E+10 | 16951.78 | 24-SEP-12:12 | 31.63 | 18.27 | 0.404054E+09 | 552.58 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.757143E+10 | 17736.33 | 15-OCT-13:52 | 31.00 | 12.59 | 0.409330E+09 | 553.43 | 02-OCT-13:20 | 31.00 | 12.59 |
November | 0.567189E+10 | 16234.73 | 19-NOV-14:43 | 26.83 | 11.41 | 0.400284E+09 | 549.73 | 02-NOV-13:39 | 26.83 | 11.41 |
December | 0.444443E+10 | 16974.45 | 25-DEC-14:02 | 26.00 | 11.93 | 0.376281E+09 | 549.66 | 22-DEC-14:50 | 26.00 | 11.93 |
Annual Sum or Average | 0.811075E+11 | 0.489374E+10 | ||||||||
Minimum of Months | 0.335066E+10 | 8690.73 | 18.00 | 10.38 | 0.350831E+09 | 549.50 | 18.00 | 10.78 | ||
Maximum of Months | 0.929976E+10 | 17736.33 | 38.00 | 20.37 | 0.455422E+09 | 553.43 | 38.00 | 20.37 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230483E+10 | 5854.87 | 31-JAN-16:30 | 29.00 | 10.73 | 0.229037E+09 | 347.85 | 24-JAN-14:50 | 29.00 | 10.73 |
February | 0.159413E+10 | 5716.47 | 22-FEB-16:30 | 20.50 | 11.47 | 0.201842E+09 | 347.83 | 23-FEB-14:00 | 18.00 | 10.35 |
March | 0.257655E+10 | 7812.13 | 18-MAR-17:08 | 26.92 | 12.85 | 0.252403E+09 | 347.85 | 09-MAR-14:00 | 26.92 | 12.85 |
April | 0.508896E+10 | 14657.22 | 23-APR-16:52 | 33.00 | 12.65 | 0.247567E+09 | 347.85 | 06-APR-09:39 | 33.00 | 12.65 |
May | 0.624996E+10 | 14914.37 | 28-MAY-17:22 | 32.50 | 12.51 | 0.274411E+09 | 347.85 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.802007E+10 | 15548.74 | 25-JUN-17:41 | 38.00 | 15.02 | 0.276200E+09 | 347.85 | 19-JUN-13:00 | 38.00 | 15.02 |
July | 0.684825E+10 | 15533.50 | 30-JUL-17:41 | 38.00 | 18.99 | 0.256961E+09 | 347.86 | 21-JUL-09:09 | 38.00 | 18.99 |
August | 0.671243E+10 | 15664.69 | 13-AUG-16:51 | 38.00 | 19.94 | 0.287773E+09 | 347.86 | 18-AUG-09:09 | 32.50 | 20.95 |
September | 0.541088E+10 | 13884.48 | 04-SEP-15:52 | 31.60 | 21.45 | 0.254585E+09 | 347.85 | 13-SEP-09:09 | 27.98 | 18.77 |
October | 0.378707E+10 | 15176.44 | 15-OCT-15:52 | 31.00 | 12.59 | 0.248267E+09 | 347.86 | 03-OCT-13:30 | 31.00 | 12.59 |
November | 0.243926E+10 | 7158.22 | 01-NOV-16:00 | 28.00 | 15.72 | 0.234902E+09 | 347.85 | 16-NOV-14:39 | 18.00 | 12.04 |
December | 0.154454E+10 | 5867.72 | 22-DEC-16:30 | 24.50 | 9.81 | 0.211877E+09 | 347.85 | 22-DEC-14:50 | 24.50 | 9.81 |
Annual Sum or Average | 0.525769E+11 | 0.297583E+10 | ||||||||
Minimum of Months | 0.154454E+10 | 5716.47 | 20.50 | 9.81 | 0.201842E+09 | 347.83 | 18.00 | 9.81 | ||
Maximum of Months | 0.802007E+10 | 15664.69 | 38.00 | 21.45 | 0.287773E+09 | 347.86 | 38.00 | 20.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194106E+10 | 2324.58 | 27-JAN-16:30 | 26.50 | 9.48 | 0.376968E+09 | 549.48 | 06-JAN-14:00 | 26.50 | 9.48 |
February | 0.154324E+10 | 1556.25 | 22-FEB-16:40 | 20.33 | 11.40 | 0.328267E+09 | 537.31 | 22-FEB-14:00 | 20.33 | 11.40 |
March | 0.209022E+10 | 2952.77 | 20-MAR-14:30 | 27.70 | 14.31 | 0.410648E+09 | 549.49 | 21-MAR-13:00 | 25.50 | 12.96 |
April | 0.373078E+10 | 5034.32 | 25-APR-15:00 | 33.00 | 15.10 | 0.398622E+09 | 549.49 | 06-APR-09:30 | 33.00 | 15.10 |
May | 0.509770E+10 | 5593.66 | 08-MAY-15:30 | 34.00 | 13.77 | 0.436163E+09 | 549.50 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.756154E+10 | 11696.97 | 25-JUN-18:21 | 37.00 | 14.68 | 0.436700E+09 | 549.50 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.768328E+10 | 11858.31 | 16-JUL-17:41 | 36.17 | 21.47 | 0.406450E+09 | 549.51 | 28-JUL-13:50 | 29.50 | 20.43 |
August | 0.760332E+10 | 11978.86 | 27-AUG-17:41 | 39.17 | 18.06 | 0.455617E+09 | 549.52 | 29-AUG-13:39 | 28.67 | 21.18 |
September | 0.672042E+10 | 11647.30 | 10-SEP-14:12 | 35.37 | 19.76 | 0.404722E+09 | 549.50 | 22-SEP-09:09 | 24.00 | 17.33 |
October | 0.413460E+10 | 9749.25 | 01-OCT-13:53 | 37.00 | 19.01 | 0.413968E+09 | 549.50 | 05-OCT-09:20 | 27.00 | 16.87 |
November | 0.245932E+10 | 4060.33 | 02-NOV-14:00 | 27.00 | 15.44 | 0.399262E+09 | 549.51 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.180597E+10 | 1960.21 | 03-DEC-14:32 | 21.00 | 10.61 | 0.354230E+09 | 549.46 | 01-DEC-14:00 | 21.00 | 10.61 |
Annual Sum or Average | 0.523714E+11 | 0.482162E+10 | ||||||||
Minimum of Months | 0.154324E+10 | 1556.25 | 20.33 | 9.48 | 0.328267E+09 | 537.31 | 20.00 | 9.48 | ||
Maximum of Months | 0.768328E+10 | 11978.86 | 39.17 | 21.47 | 0.455617E+09 | 549.52 | 33.17 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.196782E+10 | 2819.01 | 27-JAN-10:30 | 21.00 | 7.83 | 0.255585E+09 | 347.87 | 11-JAN-10:20 | 21.00 | 7.83 |
February | 0.146207E+10 | 2581.91 | 23-FEB-10:30 | 15.00 | 11.05 | 0.224981E+09 | 347.87 | 09-FEB-10:50 | 15.00 | 11.05 |
March | 0.212277E+10 | 3537.00 | 23-MAR-10:30 | 22.70 | 10.73 | 0.276024E+09 | 347.88 | 17-MAR-09:00 | 22.70 | 10.73 |
April | 0.444792E+10 | 8804.80 | 30-APR-10:22 | 29.50 | 10.94 | 0.255146E+09 | 347.89 | 28-APR-09:00 | 29.50 | 10.94 |
May | 0.548667E+10 | 9624.13 | 29-MAY-09:22 | 27.00 | 11.90 | 0.277088E+09 | 347.88 | 12-MAY-09:09 | 27.00 | 11.90 |
June | 0.713261E+10 | 11349.24 | 11-JUN-09:42 | 29.67 | 13.21 | 0.276861E+09 | 348.07 | 02-JUN-09:50 | 29.67 | 13.21 |
July | 0.700860E+10 | 11561.39 | 04-JUL-10:22 | 32.50 | 15.55 | 0.257680E+09 | 348.00 | 13-JUL-09:50 | 31.83 | 20.83 |
August | 0.712938E+10 | 11481.05 | 27-AUG-11:02 | 37.17 | 17.45 | 0.288807E+09 | 348.06 | 30-AUG-09:00 | 33.00 | 19.22 |
September | 0.599022E+10 | 11348.56 | 10-SEP-10:52 | 33.30 | 19.18 | 0.256444E+09 | 348.05 | 11-SEP-09:30 | 28.85 | 20.36 |
October | 0.430645E+10 | 8325.00 | 01-OCT-13:53 | 37.00 | 19.01 | 0.264746E+09 | 347.89 | 17-OCT-09:30 | 25.00 | 10.00 |
November | 0.250934E+10 | 3930.51 | 02-NOV-08:40 | 21.00 | 14.47 | 0.259461E+09 | 347.89 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.173204E+10 | 2476.88 | 01-DEC-10:30 | 18.50 | 8.87 | 0.240244E+09 | 347.87 | 13-DEC-10:20 | 11.67 | 10.42 |
Annual Sum or Average | 0.512959E+11 | 0.313307E+10 | ||||||||
Minimum of Months | 0.146207E+10 | 2476.88 | 15.00 | 7.83 | 0.224981E+09 | 347.87 | 11.67 | 7.83 | ||
Maximum of Months | 0.713261E+10 | 11561.39 | 37.17 | 19.18 | 0.288807E+09 | 348.07 | 33.00 | 20.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.537002E+10 | 13366.22 | 15-JAN-14:02 | 23.00 | 10.38 | 0.404518E+09 | 549.61 | 04-JAN-14:39 | 23.00 | 10.38 |
February | 0.213523E+10 | 7802.11 | 27-FEB-13:06 | 16.17 | 9.56 | 0.341979E+09 | 549.50 | 13-FEB-14:00 | 16.17 | 9.56 |
March | 0.306588E+10 | 10136.15 | 16-MAR-16:10 | 28.72 | 13.89 | 0.415916E+09 | 549.51 | 16-MAR-13:00 | 28.72 | 13.89 |
April | 0.644363E+10 | 12300.03 | 30-APR-15:41 | 33.00 | 11.94 | 0.397597E+09 | 615.92 | 14-APR-12:09 | 33.00 | 11.94 |
May | 0.737152E+10 | 12719.25 | 15-MAY-17:00 | 37.00 | 15.57 | 0.436945E+09 | 616.76 | 18-MAY-12:09 | 34.00 | 13.67 |
June | 0.999336E+10 | 14633.20 | 28-JUN-17:00 | 42.00 | 19.33 | 0.445069E+09 | 726.37 | 28-JUN-12:09 | 42.00 | 19.33 |
July | 0.100742E+11 | 13779.16 | 20-JUL-17:00 | 39.00 | 20.23 | 0.413366E+09 | 709.71 | 12-JUL-12:09 | 39.00 | 20.23 |
August | 0.112445E+11 | 14441.92 | 25-AUG-17:00 | 41.00 | 17.61 | 0.465579E+09 | 760.22 | 25-AUG-12:09 | 41.00 | 17.61 |
September | 0.105504E+11 | 14201.95 | 10-SEP-13:32 | 34.80 | 19.48 | 0.414612E+09 | 709.34 | 07-SEP-12:09 | 34.80 | 19.48 |
October | 0.833536E+10 | 14526.05 | 09-OCT-13:52 | 32.00 | 17.25 | 0.420314E+09 | 691.28 | 02-OCT-12:09 | 32.00 | 17.25 |
November | 0.564996E+10 | 13494.64 | 19-NOV-14:32 | 26.67 | 11.36 | 0.406525E+09 | 569.51 | 20-NOV-14:30 | 27.00 | 11.68 |
December | 0.402431E+10 | 13278.45 | 03-DEC-13:13 | 20.33 | 10.37 | 0.378451E+09 | 549.75 | 29-DEC-14:00 | 20.00 | 9.12 |
Annual Sum or Average | 0.842585E+11 | 0.494087E+10 | ||||||||
Minimum of Months | 0.213523E+10 | 7802.11 | 16.17 | 9.56 | 0.341979E+09 | 549.50 | 16.17 | 9.12 | ||
Maximum of Months | 0.112445E+11 | 14633.20 | 42.00 | 20.23 | 0.465579E+09 | 760.22 | 42.00 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.221830E+10 | 4874.87 | 24-JAN-16:40 | 24.33 | 10.79 | 0.243698E+09 | 347.84 | 23-JAN-14:00 | 24.33 | 10.79 |
February | 0.152432E+10 | 4218.62 | 22-FEB-16:30 | 20.50 | 11.47 | 0.210371E+09 | 347.83 | 23-FEB-14:00 | 18.00 | 10.35 |
March | 0.213288E+10 | 4510.80 | 18-MAR-17:10 | 26.92 | 12.85 | 0.261292E+09 | 347.85 | 21-MAR-13:00 | 25.50 | 12.96 |
April | 0.426507E+10 | 11799.39 | 23-APR-17:21 | 32.50 | 12.41 | 0.253243E+09 | 347.85 | 06-APR-09:30 | 32.50 | 12.41 |
May | 0.516477E+10 | 12036.64 | 29-MAY-17:21 | 31.50 | 13.80 | 0.276357E+09 | 347.85 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.682034E+10 | 12211.96 | 11-JUN-17:41 | 34.00 | 15.03 | 0.276616E+09 | 347.85 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.625954E+10 | 12387.51 | 30-JUL-17:31 | 38.00 | 19.05 | 0.257413E+09 | 347.86 | 28-JUL-13:50 | 38.00 | 19.05 |
August | 0.646704E+10 | 12992.98 | 27-AUG-17:41 | 39.17 | 18.06 | 0.288587E+09 | 347.87 | 29-AUG-13:39 | 28.67 | 21.18 |
September | 0.562160E+10 | 12326.42 | 04-SEP-17:32 | 31.60 | 21.23 | 0.256337E+09 | 347.85 | 15-SEP-09:09 | 25.45 | 16.44 |
October | 0.403560E+10 | 11881.81 | 09-OCT-15:12 | 32.33 | 17.29 | 0.262185E+09 | 347.85 | 16-OCT-09:30 | 25.50 | 10.18 |
November | 0.268886E+10 | 6475.65 | 01-NOV-16:00 | 28.00 | 15.72 | 0.254354E+09 | 347.86 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.187780E+10 | 5330.48 | 22-DEC-16:30 | 24.50 | 9.81 | 0.229262E+09 | 347.83 | 20-DEC-14:00 | 24.50 | 9.81 |
Annual Sum or Average | 0.490761E+11 | 0.306971E+10 | ||||||||
Minimum of Months | 0.152432E+10 | 4218.62 | 20.50 | 9.81 | 0.210371E+09 | 347.83 | 18.00 | 9.81 | ||
Maximum of Months | 0.682034E+10 | 12992.98 | 39.17 | 21.23 | 0.288587E+09 | 347.87 | 38.00 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199923E+10 | 2955.42 | 31-JAN-16:30 | 29.00 | 10.73 | 0.381861E+09 | 549.49 | 06-JAN-14:09 | 29.00 | 10.73 |
February | 0.159468E+10 | 2180.93 | 22-FEB-16:20 | 20.67 | 11.54 | 0.339307E+09 | 549.46 | 23-FEB-14:00 | 18.00 | 10.35 |
March | 0.242239E+10 | 4087.42 | 20-MAR-14:30 | 27.70 | 14.31 | 0.424843E+09 | 549.50 | 17-MAR-09:00 | 27.70 | 14.31 |
April | 0.445326E+10 | 5920.85 | 25-APR-15:00 | 33.00 | 15.10 | 0.400577E+09 | 549.50 | 06-APR-09:30 | 33.00 | 15.10 |
May | 0.608925E+10 | 12149.86 | 21-MAY-18:31 | 29.67 | 12.39 | 0.437266E+09 | 549.50 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.836566E+10 | 12587.66 | 25-JUN-18:11 | 37.33 | 14.77 | 0.437221E+09 | 549.51 | 19-JUN-13:00 | 37.33 | 14.77 |
July | 0.767946E+10 | 12505.34 | 04-JUL-19:01 | 35.50 | 14.61 | 0.406639E+09 | 549.51 | 05-JUL-09:09 | 31.33 | 16.71 |
August | 0.732552E+10 | 12439.35 | 13-AUG-16:11 | 38.00 | 20.37 | 0.455665E+09 | 549.50 | 28-AUG-09:09 | 31.50 | 20.35 |
September | 0.600311E+10 | 12174.61 | 10-SEP-17:02 | 33.53 | 19.28 | 0.404477E+09 | 549.50 | 22-SEP-09:09 | 24.00 | 17.33 |
October | 0.371243E+10 | 10318.73 | 02-OCT-04:02 | 26.00 | 17.05 | 0.409267E+09 | 549.51 | 03-OCT-13:30 | 33.00 | 20.21 |
November | 0.223742E+10 | 4042.51 | 02-NOV-14:00 | 27.00 | 15.44 | 0.392298E+09 | 549.50 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.162426E+10 | 2210.17 | 22-DEC-16:40 | 24.33 | 9.71 | 0.347543E+09 | 549.47 | 22-DEC-14:00 | 24.33 | 9.71 |
Annual Sum or Average | 0.535067E+11 | 0.483696E+10 | ||||||||
Minimum of Months | 0.159468E+10 | 2180.93 | 20.67 | 9.71 | 0.339307E+09 | 549.46 | 18.00 | 9.71 | ||
Maximum of Months | 0.836566E+10 | 12587.66 | 38.00 | 20.37 | 0.455665E+09 | 549.51 | 37.33 | 20.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206100E+10 | 3312.24 | 27-JAN-10:00 | 20.00 | 7.78 | 0.185206E+09 | 338.72 | 26-JAN-13:09 | 20.00 | 7.78 |
February | 0.160996E+10 | 3569.55 | 23-FEB-10:00 | 14.00 | 11.11 | 0.164801E+09 | 338.72 | 16-FEB-16:10 | 14.00 | 11.11 |
March | 0.250100E+10 | 4600.10 | 23-MAR-10:20 | 22.33 | 10.61 | 0.202542E+09 | 338.73 | 16-MAR-10:09 | 22.33 | 10.61 |
April | 0.484613E+10 | 10652.71 | 30-APR-08:13 | 23.67 | 8.60 | 0.188511E+09 | 338.74 | 28-APR-10:09 | 23.67 | 8.60 |
May | 0.603259E+10 | 12533.73 | 21-MAY-09:12 | 27.67 | 11.66 | 0.204973E+09 | 338.79 | 11-MAY-08:39 | 27.67 | 11.66 |
June | 0.753380E+10 | 13059.83 | 04-JUN-09:21 | 31.55 | 16.04 | 0.204668E+09 | 342.22 | 19-JUN-07:19 | 29.00 | 12.63 |
July | 0.683183E+10 | 12704.57 | 04-JUL-09:02 | 30.33 | 13.33 | 0.191010E+09 | 339.47 | 10-JUL-07:40 | 29.00 | 18.45 |
August | 0.669435E+10 | 12987.90 | 27-AUG-09:11 | 33.67 | 16.18 | 0.213191E+09 | 339.46 | 28-AUG-10:30 | 35.00 | 21.28 |
September | 0.532515E+10 | 12535.75 | 10-SEP-10:22 | 32.45 | 19.22 | 0.189517E+09 | 338.90 | 07-SEP-10:20 | 32.45 | 19.22 |
October | 0.380785E+10 | 8034.90 | 01-OCT-10:02 | 32.33 | 18.67 | 0.193595E+09 | 338.74 | 04-OCT-07:30 | 23.00 | 17.79 |
November | 0.224476E+10 | 4151.00 | 10-NOV-09:40 | 22.33 | 9.69 | 0.187531E+09 | 338.74 | 22-NOV-11:09 | 19.33 | 11.05 |
December | 0.161559E+10 | 2359.34 | 27-DEC-10:00 | 14.00 | 6.80 | 0.169397E+09 | 338.71 | 29-DEC-11:30 | 17.50 | 8.08 |
Annual Sum or Average | 0.511040E+11 | 0.229494E+10 | ||||||||
Minimum of Months | 0.160996E+10 | 2359.34 | 14.00 | 6.80 | 0.164801E+09 | 338.71 | 14.00 | 7.78 | ||
Maximum of Months | 0.753380E+10 | 13059.83 | 33.67 | 19.22 | 0.213191E+09 | 342.22 | 35.00 | 21.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.631921E+10 | 14283.50 | 29-JAN-12:43 | 23.67 | 9.44 | 0.408600E+09 | 549.66 | 31-JAN-14:00 | 28.00 | 11.02 |
February | 0.358548E+10 | 8906.44 | 28-FEB-14:10 | 18.17 | 7.92 | 0.362911E+09 | 549.63 | 23-FEB-14:39 | 18.17 | 7.92 |
March | 0.430813E+10 | 8202.47 | 23-MAR-13:50 | 25.42 | 11.73 | 0.437018E+09 | 549.52 | 09-MAR-14:20 | 25.42 | 11.73 |
April | 0.639894E+10 | 14069.09 | 30-APR-13:32 | 34.00 | 12.40 | 0.401297E+09 | 549.77 | 12-APR-13:00 | 34.00 | 12.40 |
May | 0.667286E+10 | 13337.21 | 07-MAY-16:01 | 36.00 | 14.10 | 0.437004E+09 | 549.50 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.813221E+10 | 13629.36 | 04-JUN-15:21 | 38.00 | 16.25 | 0.436942E+09 | 549.50 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.788017E+10 | 13905.88 | 16-JUL-15:32 | 36.67 | 19.93 | 0.406548E+09 | 549.68 | 31-JUL-13:50 | 37.00 | 19.00 |
August | 0.855420E+10 | 14043.18 | 27-AUG-15:51 | 40.00 | 18.27 | 0.455794E+09 | 550.31 | 28-AUG-13:09 | 37.83 | 20.53 |
September | 0.824481E+10 | 14462.84 | 10-SEP-13:01 | 34.50 | 19.00 | 0.404971E+09 | 566.96 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.752698E+10 | 14312.41 | 09-OCT-14:02 | 32.00 | 17.25 | 0.415941E+09 | 569.08 | 02-OCT-13:09 | 32.00 | 17.25 |
November | 0.597788E+10 | 14207.90 | 05-NOV-13:32 | 22.00 | 8.04 | 0.408474E+09 | 551.26 | 01-NOV-13:00 | 22.00 | 8.04 |
December | 0.494060E+10 | 14842.42 | 25-DEC-13:32 | 25.67 | 11.87 | 0.387848E+09 | 549.72 | 29-DEC-14:00 | 20.00 | 9.12 |
Annual Sum or Average | 0.785415E+11 | 0.496335E+10 | ||||||||
Minimum of Months | 0.358548E+10 | 8202.47 | 18.17 | 7.92 | 0.362911E+09 | 549.50 | 18.17 | 7.92 | ||
Maximum of Months | 0.855420E+10 | 14842.42 | 40.00 | 19.93 | 0.455794E+09 | 569.08 | 38.17 | 20.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244297E+10 | 5640.70 | 31-JAN-16:30 | 29.00 | 10.73 | 0.238835E+09 | 347.85 | 06-JAN-14:09 | 29.00 | 10.73 |
February | 0.175925E+10 | 5560.78 | 22-FEB-16:30 | 20.50 | 11.47 | 0.211017E+09 | 347.84 | 03-FEB-14:00 | 20.50 | 11.47 |
March | 0.260265E+10 | 6733.34 | 18-MAR-17:08 | 26.92 | 12.85 | 0.263252E+09 | 347.85 | 14-MAR-13:00 | 26.92 | 12.85 |
April | 0.478128E+10 | 13314.94 | 02-APR-17:52 | 30.00 | 11.74 | 0.252185E+09 | 347.85 | 06-APR-09:30 | 25.00 | 12.31 |
May | 0.584244E+10 | 13636.89 | 21-MAY-18:31 | 29.67 | 12.39 | 0.276143E+09 | 347.85 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.733332E+10 | 13774.52 | 25-JUN-17:31 | 38.00 | 15.08 | 0.276571E+09 | 347.85 | 19-JUN-13:09 | 38.00 | 15.08 |
July | 0.623698E+10 | 13465.79 | 30-JUL-17:41 | 38.00 | 18.99 | 0.257201E+09 | 347.86 | 05-JUL-09:09 | 38.00 | 18.99 |
August | 0.618653E+10 | 13674.07 | 27-AUG-16:31 | 40.00 | 18.00 | 0.288251E+09 | 347.86 | 28-AUG-09:09 | 31.50 | 20.35 |
September | 0.507635E+10 | 13642.81 | 04-SEP-15:41 | 31.60 | 21.45 | 0.255655E+09 | 347.85 | 22-SEP-09:09 | 24.00 | 17.33 |
October | 0.373364E+10 | 10849.29 | 09-OCT-16:02 | 32.83 | 17.35 | 0.255942E+09 | 347.86 | 03-OCT-13:30 | 32.83 | 17.35 |
November | 0.257912E+10 | 6800.71 | 01-NOV-16:00 | 28.00 | 15.72 | 0.244774E+09 | 347.86 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.182675E+10 | 5697.83 | 22-DEC-16:30 | 24.50 | 9.81 | 0.220741E+09 | 347.84 | 20-DEC-14:00 | 24.50 | 9.81 |
Annual Sum or Average | 0.504013E+11 | 0.304057E+10 | ||||||||
Minimum of Months | 0.175925E+10 | 5560.78 | 20.50 | 9.81 | 0.211017E+09 | 347.84 | 18.00 | 9.81 | ||
Maximum of Months | 0.733332E+10 | 13774.52 | 40.00 | 21.45 | 0.288251E+09 | 347.86 | 38.00 | 20.35 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.995890E+09 | 9470.27 | 02-JAN-07:02 | 6.00 |
February | 0.819022E+09 | 4505.18 | 28-FEB-06:03 | 5.00 |
March | 0.831800E+09 | 7389.07 | 27-MAR-06:01 | 1.97 |
April | 0.320328E+09 | 6712.37 | 24-APR-05:03 | 15.17 |
May | 0.163465E+09 | 7033.64 | 01-MAY-05:03 | 13.00 |
June | 50311256.60 | 6350.94 | 05-JUN-04:02 | 23.83 |
July | 35055763.22 | 6058.75 | 03-JUL-04:02 | 20.83 |
August | 33417609.83 | 6011.94 | 24-AUG-05:03 | 19.83 |
September | 47165813.69 | 5494.21 | 11-SEP-04:02 | 22.28 |
October | 0.476557E+09 | 5900.35 | 05-OCT-05:03 | 19.00 |
November | 0.694200E+09 | 7062.26 | 24-NOV-07:02 | 4.50 |
December | 0.143382E+10 | 9534.53 | 07-DEC-07:01 | 1.33 |
Annual Sum or Average | 0.590103E+10 | |||
Minimum of Months | 33417609.83 | 4505.18 | 1.33 | |
Maximum of Months | 0.143382E+10 | 9534.53 | 23.83 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.350298E+09 | 4049.18 | 22-JAN-14:43 | 19.00 |
February | 0.363941E+09 | 2902.43 | 20-FEB-15:23 | 18.00 |
March | 0.223187E+09 | 2566.78 | 26-MAR-16:12 | 18.30 |
April | 27755850.13 | 2955.84 | 02-APR-15:51 | 31.00 |
May | 26845773.40 | 3022.14 | 07-MAY-16:01 | 36.00 |
June | 23144742.17 | 2655.08 | 29-JUN-04:02 | 28.00 |
July | 26622896.10 | 3079.84 | 12-JUL-04:02 | 27.83 |
August | 22363061.29 | 2936.74 | 16-AUG-04:02 | 28.17 |
September | 20886010.10 | 2666.69 | 08-SEP-04:02 | 25.92 |
October | 47170163.91 | 3090.11 | 15-OCT-16:03 | 30.83 |
November | 0.171879E+09 | 4019.59 | 19-NOV-15:53 | 27.00 |
December | 0.651882E+09 | 4408.56 | 25-DEC-11:32 | 22.33 |
Annual Sum or Average | 0.195598E+10 | |||
Minimum of Months | 20886010.10 | 2566.78 | 18.00 | |
Maximum of Months | 0.651882E+09 | 4408.56 | 36.00 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154025E+09 | 6039.53 | 10-JAN-06:03 | 7.83 |
February | 0.104791E+09 | 5628.79 | 01-FEB-06:03 | 5.00 |
March | 49955167.46 | 4883.20 | 24-MAR-05:03 | 6.70 |
April | 28065302.93 | 4197.55 | 22-APR-05:03 | 11.00 |
May | 25234064.33 | 3676.91 | 02-MAY-04:03 | 20.00 |
June | 24489930.06 | 3374.82 | 30-JUN-04:02 | 27.83 |
July | 31991077.56 | 4027.77 | 12-JUL-04:02 | 27.83 |
August | 30961694.53 | 4096.82 | 09-AUG-04:02 | 26.00 |
September | 36788502.13 | 4272.85 | 07-SEP-04:02 | 26.10 |
October | 44079665.54 | 6044.51 | 27-OCT-05:03 | 11.83 |
November | 55762450.41 | 7336.22 | 24-NOV-06:01 | 3.17 |
December | 0.226651E+09 | 6460.84 | 05-DEC-06:01 | 1.50 |
Annual Sum or Average | 0.812795E+09 | |||
Minimum of Months | 24489930.06 | 3374.82 | 1.50 | |
Maximum of Months | 0.226651E+09 | 7336.22 | 27.83 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4313330.11 | 17762.15 | 02-JAN-07:02 | 6.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 4313330.11 | |||
Minimum of Months | 0.00 | 0.00 | 6.00 | |
Maximum of Months | 4313330.11 | 17762.15 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 67614718.27 | 26667.06 | 02-JAN-06:01 | 4.33 |
February | 10239928.03 | 23639.25 | 13-FEB-07:03 | 8.33 |
March | 2915624.33 | 23825.73 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 2699756.65 | 23485.66 | 24-NOV-07:02 | 4.50 |
December | 61775433.00 | 25110.53 | 18-DEC-06:01 | 3.83 |
Annual Sum or Average | 0.145245E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.97 | |
Maximum of Months | 67614718.27 | 26667.06 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184555E+09 | 12158.80 | 02-JAN-05:02 | 4.00 |
February | 0.135413E+09 | 10944.74 | 13-FEB-06:02 | 8.00 |
March | 0.109441E+09 | 11335.95 | 27-MAR-05:01 | 2.52 |
April | 45330.08 | 226.65 | 21-APR-06:03 | 9.33 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 14290135.70 | 9114.74 | 25-OCT-06:02 | 5.00 |
November | 90259648.04 | 11222.90 | 24-NOV-06:01 | 3.17 |
December | 0.498214E+09 | 11301.88 | 08-DEC-06:01 | 2.00 |
Annual Sum or Average | 0.103222E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.00 | |
Maximum of Months | 0.498214E+09 | 12158.80 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 82961094.01 | 8560.19 | 02-JAN-05:02 | 4.00 |
February | 60807904.17 | 7566.81 | 13-FEB-06:02 | 8.00 |
March | 50819185.33 | 7904.29 | 27-MAR-05:01 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 9185327.45 | 7080.90 | 25-OCT-06:02 | 5.00 |
November | 31793734.62 | 7872.20 | 24-NOV-06:01 | 3.17 |
December | 0.221673E+09 | 7980.69 | 08-DEC-06:01 | 2.00 |
Annual Sum or Average | 0.457241E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.00 | |
Maximum of Months | 0.221673E+09 | 8560.19 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 90002894.42 | 12347.80 | 02-JAN-06:01 | 4.33 |
February | 77874054.34 | 11890.82 | 13-FEB-06:02 | 8.00 |
March | 83387772.81 | 12092.26 | 27-MAR-05:01 | 2.52 |
April | 77601.53 | 388.01 | 21-APR-06:03 | 9.33 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 8284430.71 | 8688.85 | 25-OCT-06:02 | 5.00 |
November | 35638720.56 | 11864.67 | 24-NOV-06:01 | 3.17 |
December | 0.264284E+09 | 12300.46 | 18-DEC-06:01 | 3.83 |
Annual Sum or Average | 0.559550E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.52 | |
Maximum of Months | 0.264284E+09 | 12347.80 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106810E+09 | 8309.20 | 02-JAN-05:02 | 4.00 |
February | 85054281.58 | 7317.83 | 13-FEB-06:02 | 8.00 |
March | 67198525.75 | 7576.88 | 27-MAR-05:01 | 2.52 |
April | 193442.77 | 967.21 | 21-APR-06:03 | 9.33 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 10639372.44 | 7141.31 | 25-OCT-06:02 | 5.00 |
November | 52994622.09 | 7550.53 | 24-NOV-06:01 | 3.17 |
December | 0.303101E+09 | 7738.34 | 08-DEC-06:01 | 2.00 |
Annual Sum or Average | 0.625991E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.00 | |
Maximum of Months | 0.303101E+09 | 8309.20 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24019831.94 | 7570.63 | 02-JAN-06:01 | 4.33 |
February | 10173700.21 | 6942.81 | 13-FEB-07:03 | 8.33 |
March | 13332138.34 | 7044.01 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 143324.53 | 1433.25 | 24-NOV-07:02 | 4.50 |
December | 17980807.95 | 7049.53 | 06-DEC-07:01 | -0.5 |
Annual Sum or Average | 65649802.97 | |||
Minimum of Months | 0.00 | 0.00 | -0.5 | |
Maximum of Months | 24019831.94 | 7570.63 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6368331.22 | 4671.71 | 03-JAN-07:03 | 10.33 |
February | 3178659.85 | 4661.95 | 13-FEB-07:03 | 8.33 |
March | 2634352.95 | 4415.73 | 28-MAR-06:01 | 3.90 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 4589884.83 | 4210.57 | 07-DEC-07:01 | 1.33 |
Annual Sum or Average | 16771228.84 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 6368331.22 | 4671.71 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.523324E+09 | 8075.08 | 02-JAN-07:10 | 6.00 |
February | 0.564511E+09 | 8020.03 | 08-FEB-07:10 | 6.17 |
March | 0.647018E+09 | 8771.17 | 27-MAR-06:10 | 1.97 |
April | 99971677.28 | 7126.32 | 21-APR-06:10 | 9.33 |
May | 4265080.85 | 5413.28 | 01-MAY-06:05 | 13.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.210844E+09 | 7681.18 | 25-OCT-06:10 | 5.00 |
November | 0.291326E+09 | 7788.31 | 24-NOV-07:10 | 4.50 |
December | 0.637650E+09 | 9043.36 | 06-DEC-07:10 | -0.5 |
Annual Sum or Average | 0.297891E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.5 | |
Maximum of Months | 0.647018E+09 | 9043.36 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6444031.43 | 4540.06 | 03-JAN-07:03 | 10.33 |
February | 4973149.77 | 4626.40 | 08-FEB-07:02 | 6.17 |
March | 3194153.62 | 4614.72 | 28-MAR-06:01 | 3.90 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 7862998.02 | 4592.03 | 05-DEC-07:01 | -0.5 |
Annual Sum or Average | 22474332.84 | |||
Minimum of Months | 0.00 | 0.00 | -0.5 | |
Maximum of Months | 7862998.02 | 4626.40 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32595590.59 | 9510.01 | 02-JAN-06:01 | 4.33 |
February | 11350235.83 | 7952.62 | 13-FEB-07:03 | 8.33 |
March | 11064292.45 | 8665.46 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 4070670.76 | 8545.00 | 24-NOV-07:02 | 4.50 |
December | 70850513.37 | 9136.30 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 0.129931E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 70850513.37 | 9510.01 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16612724.44 | 5943.70 | 02-JAN-06:01 | 4.33 |
February | 8545321.77 | 5453.63 | 09-FEB-07:02 | 6.17 |
March | 6276300.35 | 5186.19 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 2009201.41 | 5329.27 | 24-NOV-07:02 | 4.50 |
December | 33183971.73 | 5670.20 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 66627519.71 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 33183971.73 | 5943.70 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15061242.20 | 9014.42 | 02-JAN-06:01 | 4.33 |
February | 5417226.34 | 7952.57 | 13-FEB-07:03 | 8.33 |
March | 6180477.17 | 8478.02 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 816409.65 | 7862.02 | 24-NOV-07:02 | 4.50 |
December | 30058541.75 | 8804.76 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 57533897.11 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 30058541.75 | 9014.42 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19378434.65 | 5711.37 | 02-JAN-06:01 | 4.33 |
February | 10031245.60 | 5526.69 | 09-FEB-07:02 | 6.17 |
March | 7097190.11 | 5317.46 | 29-MAR-06:01 | 3.08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 3325428.94 | 5170.31 | 24-NOV-07:02 | 4.50 |
December | 48354382.50 | 5706.75 | 06-DEC-06:01 | 0.67 |
Annual Sum or Average | 88186681.79 | |||
Minimum of Months | 0.00 | 0.00 | 0.67 | |
Maximum of Months | 48354382.50 | 5711.37 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.208150E+11 | 18520.31 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.188385E+11 | 18520.31 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.216654E+11 | 18520.31 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.200796E+11 | 18520.31 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.212402E+11 | 18520.31 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.208620E+11 | 18520.31 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.204550E+11 | 18520.31 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.216654E+11 | 18520.31 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.200739E+11 | 18520.31 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.208179E+11 | 18520.31 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.203773E+11 | 18520.31 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.204522E+11 | 18520.31 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.247342E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.188385E+11 | 18520.31 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.216654E+11 | 18520.31 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.820897E+09 | 1085.56 | 20-JAN-08:09 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.726038E+09 | 1050.42 | 03-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.826888E+09 | 991.69 | 21-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.723451E+09 | 846.01 | 04-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.769384E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.756257E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.713535E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.807069E+09 | 994.39 | 04-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.732129E+09 | 917.28 | 29-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.793934E+09 | 1064.76 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.801604E+09 | 1168.55 | 28-NOV-16:30 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.804908E+09 | 1168.55 | 01-DEC-16:30 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.927609E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.713535E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.826888E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.504438E+09 | 680.11 | 20-JAN-16:00 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.452192E+09 | 637.52 | 10-FEB-08:09 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.520711E+09 | 567.29 | 09-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.456679E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.488634E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.480745E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.453548E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.510315E+09 | 617.61 | 04-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.462519E+09 | 456.08 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.491927E+09 | 582.90 | 31-OCT-15:00 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.497673E+09 | 739.79 | 28-NOV-16:30 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.495708E+09 | 739.79 | 01-DEC-16:30 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.581509E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.452192E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.520711E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.787212E+09 | 1063.91 | 20-JAN-16:00 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.708028E+09 | 1019.15 | 10-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.817703E+09 | 963.81 | 21-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.725165E+09 | 865.97 | 04-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.775109E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.763349E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.720529E+09 | 855.78 | 27-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.810268E+09 | 997.87 | 04-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.730359E+09 | 842.85 | 18-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.766481E+09 | 948.81 | 27-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.775729E+09 | 1168.55 | 28-NOV-16:30 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.770999E+09 | 1168.55 | 01-DEC-16:30 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.915093E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.708028E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.817703E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.512277E+09 | 693.02 | 20-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.456600E+09 | 666.29 | 03-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.523128E+09 | 661.76 | 21-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.459775E+09 | 587.34 | 04-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.490091E+09 | 517.78 | 05-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.482207E+09 | 508.00 | 27-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.455721E+09 | 559.33 | 27-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.513774E+09 | 636.55 | 04-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.464911E+09 | 614.41 | 29-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.498029E+09 | 677.98 | 27-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.500302E+09 | 739.74 | 28-NOV-16:30 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.500362E+09 | 739.74 | 01-DEC-16:30 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.585718E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.455721E+09 | 508.00 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.523128E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.816839E+09 | 1081.40 | 20-JAN-08:09 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.723979E+09 | 1044.99 | 03-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.825061E+09 | 983.24 | 21-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.722829E+09 | 828.65 | 04-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.769078E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.756127E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.713200E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.806196E+09 | 986.80 | 04-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.731210E+09 | 905.66 | 29-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.790551E+09 | 1058.17 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.797906E+09 | 1168.55 | 28-NOV-16:30 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.800994E+09 | 1168.55 | 01-DEC-16:30 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.925397E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.713200E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.825061E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.503464E+09 | 678.09 | 20-JAN-16:00 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.451676E+09 | 633.79 | 10-FEB-08:09 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.520157E+09 | 561.21 | 09-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.456301E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.488462E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.480527E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.453269E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.509925E+09 | 613.20 | 04-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.462080E+09 | 456.08 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.491064E+09 | 578.22 | 31-OCT-15:00 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.496531E+09 | 739.79 | 28-NOV-16:30 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.494760E+09 | 739.79 | 01-DEC-16:30 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.580822E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.451676E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.520157E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.784037E+09 | 1059.24 | 20-JAN-16:00 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.707701E+09 | 1012.48 | 10-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.817166E+09 | 954.17 | 21-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.724445E+09 | 850.03 | 04-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.774505E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.762445E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.719559E+09 | 841.76 | 27-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.809248E+09 | 990.46 | 04-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.729859E+09 | 824.98 | 18-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.766109E+09 | 938.32 | 27-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.774852E+09 | 1168.55 | 28-NOV-16:30 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.769479E+09 | 1168.55 | 01-DEC-16:30 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.913941E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.707701E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.817166E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.510964E+09 | 691.16 | 20-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.455738E+09 | 663.55 | 03-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.522233E+09 | 659.07 | 21-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.459052E+09 | 580.52 | 04-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.489689E+09 | 509.07 | 05-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.481750E+09 | 499.44 | 27-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.455173E+09 | 552.75 | 27-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.512793E+09 | 633.09 | 04-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.464171E+09 | 610.12 | 29-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.496926E+09 | 675.31 | 27-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.499315E+09 | 739.74 | 28-NOV-16:30 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.499299E+09 | 739.74 | 01-DEC-16:30 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.584710E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.455173E+09 | 499.44 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.522233E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.820898E+09 | 1085.56 | 20-JAN-08:09 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.726038E+09 | 1050.43 | 03-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.826888E+09 | 991.69 | 21-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.723451E+09 | 846.02 | 04-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.769384E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.756257E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.713535E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.807069E+09 | 994.38 | 04-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.732129E+09 | 917.27 | 29-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.793935E+09 | 1064.77 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.801605E+09 | 1168.55 | 28-NOV-16:30 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.804910E+09 | 1168.55 | 01-DEC-16:30 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.927610E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.713535E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.826888E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.504438E+09 | 680.11 | 20-JAN-16:00 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.452192E+09 | 637.51 | 10-FEB-08:09 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.520711E+09 | 567.30 | 09-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.456680E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.488634E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.480745E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.453548E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.510315E+09 | 617.61 | 04-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.462519E+09 | 456.08 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.491928E+09 | 582.91 | 31-OCT-15:00 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.497673E+09 | 739.79 | 28-NOV-16:30 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.495709E+09 | 739.79 | 01-DEC-16:30 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.581509E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.452192E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.520711E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.787212E+09 | 1063.91 | 20-JAN-16:00 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.708027E+09 | 1019.14 | 10-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.817703E+09 | 963.80 | 21-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.725165E+09 | 865.98 | 04-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.775109E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.763350E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.720529E+09 | 855.79 | 27-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.810268E+09 | 997.86 | 04-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.730359E+09 | 842.86 | 18-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.766481E+09 | 948.81 | 27-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.775729E+09 | 1168.55 | 28-NOV-16:30 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.770999E+09 | 1168.55 | 01-DEC-16:30 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.915093E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.708027E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.817703E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.512277E+09 | 693.02 | 20-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.456600E+09 | 666.29 | 03-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.523128E+09 | 661.75 | 21-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.459775E+09 | 587.35 | 04-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.490092E+09 | 517.79 | 05-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.482207E+09 | 508.01 | 27-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.455721E+09 | 559.34 | 27-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.513774E+09 | 636.54 | 04-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.464911E+09 | 614.40 | 29-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.498030E+09 | 677.98 | 27-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.500302E+09 | 739.74 | 28-NOV-16:30 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.500362E+09 | 739.74 | 01-DEC-16:30 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.585718E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.455721E+09 | 508.01 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.523128E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.208150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.200796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.212402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.208620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.204550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.200739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.208179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.203773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.204522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.247342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.820897E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6989728.75 | 0.596535E+09 |
February | 0.901968E+09 | 0.726038E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483246E+09 |
March | 0.107774E+10 | 0.826888E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6718041.16 | 0.642429E+09 |
April | 0.956342E+09 | 0.723451E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122995E+09 | 0.226857E+09 |
May | 0.103597E+10 | 0.769384E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227420E+09 | 0.147788E+09 |
June | 0.103308E+10 | 0.756257E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410851E+09 | 44501012.58 |
July | 0.959235E+09 | 0.713535E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402243E+09 | 39515985.81 |
August | 0.107774E+10 | 0.807069E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281720E+09 | 53553726.35 |
September | 0.956342E+09 | 0.732129E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209092E+09 | 0.100819E+09 |
October | 0.994195E+09 | 0.793934E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82840851.79 | 0.333695E+09 |
November | 0.984487E+09 | 0.801604E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11436545.56 | 0.551139E+09 |
December | 0.959235E+09 | 0.804908E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3533566.86 | 0.580137E+09 |
Annual Sum or Average | 0.119305E+11 | 0.927609E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176584E+10 | 0.380021E+10 |
Minimum of Months | 0.901968E+09 | 0.713535E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39515985.81 |
Maximum of Months | 0.107774E+10 | 0.826888E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410851E+09 | 0.642429E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.504438E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2788803.98 | 0.415462E+09 |
February | 0.571020E+09 | 0.452192E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334166E+09 |
March | 0.682301E+09 | 0.520711E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4300667.83 | 0.444586E+09 |
April | 0.605444E+09 | 0.456679E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78184899.05 | 0.160704E+09 |
May | 0.655854E+09 | 0.488634E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148255E+09 | 0.102361E+09 |
June | 0.654023E+09 | 0.480745E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275102E+09 | 29877043.06 |
July | 0.607275E+09 | 0.453548E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269046E+09 | 26987424.00 |
August | 0.682301E+09 | 0.510315E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185451E+09 | 37402846.02 |
September | 0.605444E+09 | 0.462519E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138200E+09 | 68776149.88 |
October | 0.629407E+09 | 0.491927E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51518978.14 | 0.232542E+09 |
November | 0.623262E+09 | 0.497673E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5565906.10 | 0.381422E+09 |
December | 0.607275E+09 | 0.495708E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1431933.56 | 0.398316E+09 |
Annual Sum or Average | 0.755301E+10 | 0.581509E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115984E+10 | 0.263260E+10 |
Minimum of Months | 0.571020E+09 | 0.452192E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26987424.00 |
Maximum of Months | 0.682301E+09 | 0.520711E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275102E+09 | 0.444586E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.787212E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2150099.60 | 0.690743E+09 |
February | 0.901968E+09 | 0.708028E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527661E+09 |
March | 0.107774E+10 | 0.817703E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5996265.28 | 0.685434E+09 |
April | 0.956342E+09 | 0.725165E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114009E+09 | 0.234635E+09 |
May | 0.103597E+10 | 0.775109E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226934E+09 | 0.146912E+09 |
June | 0.103308E+10 | 0.763349E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416471E+09 | 42920421.45 |
July | 0.959235E+09 | 0.720529E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405205E+09 | 38584413.14 |
August | 0.107774E+10 | 0.810268E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279383E+09 | 54958011.65 |
September | 0.956342E+09 | 0.730359E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203114E+09 | 0.106315E+09 |
October | 0.994195E+09 | 0.766481E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70731061.79 | 0.369648E+09 |
November | 0.984487E+09 | 0.775729E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3920193.65 | 0.620625E+09 |
December | 0.959235E+09 | 0.770999E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 191869.31 | 0.653736E+09 |
Annual Sum or Average | 0.119305E+11 | 0.915093E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172811E+10 | 0.417217E+10 |
Minimum of Months | 0.901968E+09 | 0.708028E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38584413.14 |
Maximum of Months | 0.107774E+10 | 0.817703E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416471E+09 | 0.690743E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.512277E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3106552.57 | 0.416356E+09 |
February | 0.570983E+09 | 0.456600E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331033E+09 |
March | 0.682256E+09 | 0.523128E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4386470.93 | 0.442080E+09 |
April | 0.605404E+09 | 0.459775E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75122273.12 | 0.160819E+09 |
May | 0.655811E+09 | 0.490091E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148146E+09 | 0.103270E+09 |
June | 0.653980E+09 | 0.482207E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273188E+09 | 30568092.93 |
July | 0.607235E+09 | 0.455721E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267320E+09 | 27404559.93 |
August | 0.682256E+09 | 0.513774E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185715E+09 | 37185479.64 |
September | 0.605404E+09 | 0.464911E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138255E+09 | 69166161.19 |
October | 0.629366E+09 | 0.498029E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52391118.97 | 0.231578E+09 |
November | 0.623221E+09 | 0.500302E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5922774.11 | 0.382136E+09 |
December | 0.607235E+09 | 0.500362E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1169887.94 | 0.399057E+09 |
Annual Sum or Average | 0.755252E+10 | 0.585718E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115472E+10 | 0.263065E+10 |
Minimum of Months | 0.570983E+09 | 0.455721E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27404559.93 |
Maximum of Months | 0.682256E+09 | 0.523128E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273188E+09 | 0.442080E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.816839E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3356318.53 | 0.357184E+09 |
February | 0.901968E+09 | 0.723979E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279529E+09 |
March | 0.107774E+10 | 0.825061E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4013263.87 | 0.356863E+09 |
April | 0.956342E+09 | 0.722829E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72938043.08 | 0.120371E+09 |
May | 0.103597E+10 | 0.769078E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131915E+09 | 75094108.78 |
June | 0.103308E+10 | 0.756127E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226038E+09 | 21821440.28 |
July | 0.959235E+09 | 0.713200E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220436E+09 | 20850129.33 |
August | 0.107774E+10 | 0.806196E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153886E+09 | 30935471.87 |
September | 0.956342E+09 | 0.731210E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114561E+09 | 58665744.29 |
October | 0.994195E+09 | 0.790551E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44072934.02 | 0.205173E+09 |
November | 0.984487E+09 | 0.797906E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5056435.76 | 0.347411E+09 |
December | 0.959235E+09 | 0.800994E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1189723.56 | 0.359241E+09 |
Annual Sum or Average | 0.119305E+11 | 0.925397E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.977462E+09 | 0.223314E+10 |
Minimum of Months | 0.901968E+09 | 0.713200E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20850129.33 |
Maximum of Months | 0.107774E+10 | 0.825061E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226038E+09 | 0.359241E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.503464E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1187173.16 | 0.254853E+09 |
February | 0.571020E+09 | 0.451676E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196597E+09 |
March | 0.682301E+09 | 0.520157E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2339028.76 | 0.253766E+09 |
April | 0.605444E+09 | 0.456301E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43668710.28 | 89183294.36 |
May | 0.655854E+09 | 0.488462E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82081412.69 | 55080087.19 |
June | 0.654023E+09 | 0.480527E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148343E+09 | 15968226.29 |
July | 0.607275E+09 | 0.453269E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144398E+09 | 15552081.09 |
August | 0.682301E+09 | 0.509925E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99112486.63 | 23203889.48 |
September | 0.605444E+09 | 0.462080E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74364318.34 | 42097749.30 |
October | 0.629407E+09 | 0.491064E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27135026.06 | 0.144930E+09 |
November | 0.623262E+09 | 0.496531E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2378912.72 | 0.243042E+09 |
December | 0.607275E+09 | 0.494760E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 425083.29 | 0.251124E+09 |
Annual Sum or Average | 0.755301E+10 | 0.580822E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625433E+09 | 0.158540E+10 |
Minimum of Months | 0.571020E+09 | 0.451676E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15552081.09 |
Maximum of Months | 0.682301E+09 | 0.520157E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148343E+09 | 0.254853E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.784037E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45700853.00 | 0.256134E+10 |
February | 0.901968E+09 | 0.707701E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300285E+10 |
March | 0.107774E+10 | 0.817166E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151545E+09 | 0.255659E+10 |
April | 0.956342E+09 | 0.724445E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120426E+10 | 0.780245E+09 |
May | 0.103597E+10 | 0.774505E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211194E+10 | 0.352802E+09 |
June | 0.103308E+10 | 0.762445E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337479E+10 | 72455558.87 |
July | 0.959235E+09 | 0.719559E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274892E+10 | 36368992.65 |
August | 0.107774E+10 | 0.809248E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289025E+10 | 0.104700E+09 |
September | 0.956342E+09 | 0.729859E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195605E+10 | 0.248168E+09 |
October | 0.994195E+09 | 0.766109E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853765E+09 | 0.147768E+10 |
November | 0.984487E+09 | 0.774852E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99190068.10 | 0.237454E+10 |
December | 0.959235E+09 | 0.769479E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4653930.44 | 0.349025E+10 |
Annual Sum or Average | 0.119305E+11 | 0.913941E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154411E+11 | 0.170580E+11 |
Minimum of Months | 0.901968E+09 | 0.707701E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36368992.65 |
Maximum of Months | 0.107774E+10 | 0.817166E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337479E+10 | 0.349025E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.510964E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1212089.36 | 0.255863E+09 |
February | 0.570983E+09 | 0.455738E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194043E+09 |
March | 0.682256E+09 | 0.522233E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2266668.01 | 0.251548E+09 |
April | 0.605404E+09 | 0.459052E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40867813.45 | 90664672.42 |
May | 0.655811E+09 | 0.489689E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80432979.54 | 56624238.11 |
June | 0.653980E+09 | 0.481750E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146183E+09 | 16820952.58 |
July | 0.607235E+09 | 0.455173E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142506E+09 | 15796050.12 |
August | 0.682256E+09 | 0.512793E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98619028.77 | 22941672.16 |
September | 0.605404E+09 | 0.464171E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73723054.88 | 42433936.93 |
October | 0.629366E+09 | 0.496926E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27091594.41 | 0.145750E+09 |
November | 0.623221E+09 | 0.499315E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2413648.83 | 0.244618E+09 |
December | 0.607235E+09 | 0.499299E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 282529.97 | 0.249852E+09 |
Annual Sum or Average | 0.755252E+10 | 0.584710E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.615598E+09 | 0.158696E+10 |
Minimum of Months | 0.570983E+09 | 0.455173E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15796050.12 |
Maximum of Months | 0.682256E+09 | 0.522233E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146183E+09 | 0.255863E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.820898E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4438625.93 | 0.555176E+09 |
February | 0.901968E+09 | 0.726038E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443876E+09 |
March | 0.107774E+10 | 0.826888E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5476954.91 | 0.581877E+09 |
April | 0.956342E+09 | 0.723451E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104656E+09 | 0.200961E+09 |
May | 0.103597E+10 | 0.769384E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192123E+09 | 0.129128E+09 |
June | 0.103308E+10 | 0.756257E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343068E+09 | 38698825.34 |
July | 0.959235E+09 | 0.713535E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337581E+09 | 34139482.14 |
August | 0.107774E+10 | 0.807069E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235806E+09 | 47080639.87 |
September | 0.956342E+09 | 0.732129E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175751E+09 | 87965831.71 |
October | 0.994195E+09 | 0.793935E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68247177.89 | 0.305255E+09 |
November | 0.984487E+09 | 0.801605E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8201541.11 | 0.512614E+09 |
December | 0.959235E+09 | 0.804910E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2037812.57 | 0.537101E+09 |
Annual Sum or Average | 0.119305E+11 | 0.927610E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147739E+10 | 0.347387E+10 |
Minimum of Months | 0.901968E+09 | 0.713535E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34139482.14 |
Maximum of Months | 0.107774E+10 | 0.826888E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343068E+09 | 0.581877E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.504438E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1980431.69 | 0.381971E+09 |
February | 0.421807E+09 | 0.452192E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302874E+09 |
March | 0.502994E+09 | 0.520711E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3591419.73 | 0.397873E+09 |
April | 0.447140E+09 | 0.456680E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67131515.26 | 0.140332E+09 |
May | 0.484071E+09 | 0.488634E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126213E+09 | 88439785.69 |
June | 0.482240E+09 | 0.480745E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230332E+09 | 25793815.72 |
July | 0.448971E+09 | 0.453548E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226451E+09 | 23157339.75 |
August | 0.502994E+09 | 0.510315E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155659E+09 | 32551102.99 |
September | 0.447140E+09 | 0.462519E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116570E+09 | 59444864.48 |
October | 0.465148E+09 | 0.491928E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43236841.12 | 0.209224E+09 |
November | 0.460569E+09 | 0.497673E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4216172.12 | 0.350454E+09 |
December | 0.448971E+09 | 0.495709E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 934342.76 | 0.366047E+09 |
Annual Sum or Average | 0.557719E+10 | 0.581509E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976316E+09 | 0.237816E+10 |
Minimum of Months | 0.421807E+09 | 0.452192E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23157339.75 |
Maximum of Months | 0.502994E+09 | 0.520711E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230332E+09 | 0.397873E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.787212E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1821339.08 | 0.627723E+09 |
February | 0.901968E+09 | 0.708027E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477254E+09 |
March | 0.107774E+10 | 0.817703E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5054949.33 | 0.613791E+09 |
April | 0.956342E+09 | 0.725165E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96044960.59 | 0.207378E+09 |
May | 0.103597E+10 | 0.775109E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190988E+09 | 0.128654E+09 |
June | 0.103308E+10 | 0.763350E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347431E+09 | 37485290.16 |
July | 0.959235E+09 | 0.720529E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339450E+09 | 33467471.64 |
August | 0.107774E+10 | 0.810268E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233393E+09 | 48279399.06 |
September | 0.956342E+09 | 0.730359E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170082E+09 | 92544904.87 |
October | 0.994195E+09 | 0.766481E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59089804.87 | 0.332161E+09 |
November | 0.984487E+09 | 0.775729E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3285711.31 | 0.564656E+09 |
December | 0.959235E+09 | 0.770999E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 164090.95 | 0.594591E+09 |
Annual Sum or Average | 0.119305E+11 | 0.915093E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144680E+10 | 0.375799E+10 |
Minimum of Months | 0.901968E+09 | 0.708027E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33467471.64 |
Maximum of Months | 0.107774E+10 | 0.817703E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347431E+09 | 0.627723E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.512277E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2047116.48 | 0.383614E+09 |
February | 0.570983E+09 | 0.456600E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301267E+09 |
March | 0.682256E+09 | 0.523128E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3402987.03 | 0.397822E+09 |
April | 0.605404E+09 | 0.459775E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62830097.86 | 0.142070E+09 |
May | 0.655811E+09 | 0.490092E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123931E+09 | 90019139.14 |
June | 0.653980E+09 | 0.482207E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227226E+09 | 26665237.17 |
July | 0.607235E+09 | 0.455721E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223267E+09 | 23665330.66 |
August | 0.682256E+09 | 0.513774E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154647E+09 | 32668440.93 |
September | 0.605404E+09 | 0.464911E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115460E+09 | 60252955.55 |
October | 0.629366E+09 | 0.498030E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43016056.19 | 0.210314E+09 |
November | 0.623221E+09 | 0.500302E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4285610.55 | 0.351870E+09 |
December | 0.607235E+09 | 0.500362E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 610159.59 | 0.366369E+09 |
Annual Sum or Average | 0.755252E+10 | 0.585718E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.960723E+09 | 0.238660E+10 |
Minimum of Months | 0.570983E+09 | 0.455721E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23665330.66 |
Maximum of Months | 0.682256E+09 | 0.523128E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227226E+09 | 0.397822E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1639313.03 | 0.834284E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650528E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5364933.11 | 0.839222E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118943E+09 | 0.282440E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231016E+09 | 0.174746E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425777E+09 | 49307544.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421809E+09 | 42205744.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289366E+09 | 62610587.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209692E+09 | 0.117213E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72531622.66 | 0.448373E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5235114.54 | 0.767055E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583838.41 | 0.806842E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178196E+10 | 0.507483E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42205744.08 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425777E+09 | 0.839222E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3585130.25 | 0.100276E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787385E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7695849.58 | 0.103700E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155067E+09 | 0.358755E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295120E+09 | 0.225120E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544946E+09 | 64715239.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540636E+09 | 54821715.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372649E+09 | 77810423.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272977E+09 | 0.146696E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98448320.58 | 0.546768E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10368215.90 | 0.921877E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1718557.98 | 0.965138E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230321E+10 | 0.618884E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54821715.22 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544946E+09 | 0.103700E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1476086.90 | 0.933991E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766525E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3873287.00 | 0.100542E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129487E+09 | 0.335352E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273870E+09 | 0.194276E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567573E+09 | 54346627.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542307E+09 | 46791399.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385976E+09 | 66406205.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273839E+09 | 0.132814E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92651376.32 | 0.512955E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5306191.47 | 0.857660E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487821.43 | 0.894417E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227685E+10 | 0.580095E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46791399.40 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567573E+09 | 0.100542E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 18520.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 18520.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 18520.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 18520.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 18520.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 18520.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 18520.31 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 18520.31 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 18520.31 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 18520.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 18520.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 18520.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1085.56 | 20-JAN-08:09 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.17 | 16-JAN-12:10 | 1033.72 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 1050.42 | 03-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1400.18 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 991.69 | 21-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 145.18 | 18-MAR-17:03 | 1222.29 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 846.01 | 04-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 895.98 | 30-APR-15:55 | 656.76 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 818.38 | 20-MAY-17:02 | 554.69 | 23-MAY-04:55 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1320.01 | 17-JUN-17:08 | 285.59 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1652.32 | 22-JUL-18:00 | 445.86 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 994.39 | 04-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1494.37 | 13-AUG-16:00 | 663.34 | 05-AUG-17:50 |
September | 1306.65 | 01-SEP-09:09 | 917.28 | 29-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1043.62 | 17-SEP-11:57 | 459.16 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1064.76 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 664.36 | 01-OCT-14:58 | 1249.29 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 28-NOV-16:30 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.16 | 19-NOV-13:00 | 1172.11 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 155.57 | 25-DEC-15:53 | 1029.41 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.59 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1652.32 | 1400.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 680.11 | 20-JAN-16:00 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.70 | 29-JAN-16:10 | 703.12 | 01-JAN-01:00 |
February | 827.22 | 01-FEB-10:09 | 637.52 | 10-FEB-08:09 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 944.28 | 02-FEB-23:00 |
March | 827.22 | 01-MAR-10:09 | 567.29 | 09-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 93.02 | 18-MAR-17:03 | 816.45 | 28-MAR-04:00 |
April | 827.22 | 03-APR-09:09 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 612.40 | 30-APR-15:55 | 632.97 | 16-APR-09:00 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 556.73 | 20-MAY-17:02 | 368.08 | 23-MAY-04:55 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 883.33 | 17-JUN-17:10 | 195.67 | 11-JUN-06:30 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1119.88 | 22-JUL-17:43 | 297.05 | 26-JUL-24:00 |
August | 827.22 | 01-AUG-09:09 | 617.61 | 04-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 996.24 | 13-AUG-16:00 | 448.43 | 05-AUG-17:50 |
September | 827.22 | 01-SEP-09:09 | 456.08 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 702.44 | 17-SEP-11:57 | 304.36 | 03-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 582.90 | 31-OCT-15:00 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 453.23 | 01-OCT-14:58 | 911.96 | 22-OCT-14:00 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 28-NOV-16:30 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.75 | 19-NOV-15:00 | 784.54 | 29-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-16:30 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.72 | 25-DEC-15:53 | 685.63 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.67 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 1119.88 | 944.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1063.91 | 20-JAN-16:00 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.37 | 31-JAN-14:00 | 1172.32 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 1019.15 | 10-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1509.83 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 963.81 | 21-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 95.72 | 15-MAR-13:00 | 1253.16 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 865.97 | 04-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 890.53 | 30-APR-15:53 | 661.48 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 815.73 | 20-MAY-17:02 | 554.32 | 23-MAY-04:55 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1319.21 | 17-JUN-17:08 | 283.88 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 855.78 | 27-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1674.12 | 22-JUL-17:43 | 443.44 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 997.87 | 04-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1494.36 | 13-AUG-16:00 | 681.39 | 05-AUG-17:50 |
September | 1306.65 | 01-SEP-09:09 | 842.85 | 18-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1042.64 | 17-SEP-11:57 | 465.15 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 948.81 | 27-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 660.54 | 01-OCT-14:55 | 1479.29 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 28-NOV-16:30 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.07 | 01-NOV-16:00 | 1228.17 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.90 | 21-DEC-15:00 | 1068.15 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.88 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1674.12 | 1509.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 693.02 | 20-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 132.78 | 16-JAN-12:10 | 727.06 | 01-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 666.29 | 03-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 967.16 | 02-FEB-23:00 |
March | 827.17 | 01-MAR-10:09 | 661.76 | 21-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.82 | 15-MAR-13:00 | 829.53 | 28-MAR-04:00 |
April | 827.17 | 03-APR-09:09 | 587.34 | 04-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 584.40 | 30-APR-15:14 | 451.95 | 26-APR-21:10 |
May | 827.17 | 01-MAY-09:09 | 517.78 | 05-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 522.10 | 20-MAY-17:45 | 376.39 | 23-MAY-04:55 |
June | 827.17 | 01-JUN-09:09 | 508.00 | 27-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 885.13 | 17-JUN-17:10 | 197.47 | 13-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 559.33 | 27-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1101.19 | 22-JUL-18:00 | 315.82 | 26-JUL-24:00 |
August | 827.17 | 01-AUG-09:09 | 636.55 | 04-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 996.23 | 13-AUG-16:00 | 451.18 | 05-AUG-17:50 |
September | 827.17 | 01-SEP-09:09 | 614.41 | 29-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 713.68 | 17-SEP-12:00 | 303.61 | 03-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 677.98 | 27-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 450.92 | 01-OCT-14:58 | 850.74 | 22-OCT-14:00 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 28-NOV-16:30 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.51 | 19-NOV-12:23 | 781.81 | 29-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:30 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.73 | 25-DEC-13:52 | 690.44 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 508.00 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.47 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1101.19 | 967.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1081.40 | 20-JAN-08:09 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 68.53 | 16-JAN-11:53 | 677.12 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 1044.99 | 03-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 825.86 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 983.24 | 21-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 100.96 | 18-MAR-17:03 | 709.14 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 828.65 | 04-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 538.52 | 30-APR-15:30 | 376.85 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 485.15 | 20-MAY-17:02 | 283.62 | 23-MAY-04:55 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 729.53 | 17-JUN-17:02 | 154.66 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 892.73 | 22-JUL-17:45 | 248.42 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 986.80 | 04-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 799.44 | 13-AUG-16:00 | 366.76 | 05-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 905.66 | 29-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 576.52 | 17-SEP-12:20 | 282.57 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1058.17 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 375.50 | 01-OCT-14:38 | 737.92 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 28-NOV-16:30 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.81 | 19-NOV-15:00 | 744.74 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 76.03 | 25-DEC-15:53 | 629.59 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.66 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 892.73 | 825.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 678.09 | 20-JAN-16:00 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.25 | 29-JAN-16:00 | 478.62 | 01-JAN-01:00 |
February | 827.22 | 01-FEB-10:09 | 633.79 | 10-FEB-08:09 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 577.00 | 02-FEB-23:00 |
March | 827.22 | 01-MAR-10:09 | 561.21 | 09-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.48 | 18-MAR-17:03 | 491.63 | 28-MAR-04:00 |
April | 827.22 | 03-APR-09:09 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 328.90 | 30-APR-15:50 | 321.96 | 16-APR-08:50 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.65 | 20-MAY-18:00 | 193.03 | 01-MAY-04:45 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 479.54 | 17-JUN-17:02 | 107.88 | 11-JUN-06:20 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 602.36 | 22-JUL-18:00 | 173.13 | 26-JUL-24:00 |
August | 827.22 | 01-AUG-09:09 | 613.20 | 04-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 533.04 | 13-AUG-16:00 | 251.83 | 05-AUG-17:50 |
September | 827.22 | 01-SEP-09:09 | 456.08 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 390.76 | 17-SEP-12:20 | 193.15 | 03-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 578.22 | 31-OCT-15:00 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.90 | 01-OCT-14:38 | 537.34 | 22-OCT-14:00 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 28-NOV-16:30 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.21 | 19-NOV-15:00 | 511.90 | 29-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-16:30 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.59 | 25-DEC-15:53 | 427.52 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.88 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 602.36 | 577.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1059.24 | 20-JAN-16:00 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4823.97 | 31-JAN-17:10 | 18220.42 | 12-JAN-07:02 |
February | 1306.65 | 01-FEB-10:09 | 1012.48 | 10-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 18614.66 | 01-FEB-07:02 |
March | 1306.65 | 01-MAR-10:09 | 954.17 | 21-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5363.73 | 20-MAR-17:00 | 21358.55 | 27-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 850.03 | 04-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11426.83 | 14-APR-16:02 | 13555.16 | 21-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13521.24 | 31-MAY-16:02 | 10060.61 | 01-MAY-06:02 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18623.50 | 28-JUN-16:01 | 4373.69 | 21-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 841.76 | 27-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15632.29 | 20-JUL-16:01 | 1923.40 | 03-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 990.46 | 04-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17516.05 | 25-AUG-16:01 | 4780.80 | 24-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 824.98 | 18-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13974.74 | 08-SEP-16:01 | 6961.56 | 22-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 938.32 | 27-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11023.17 | 03-OCT-16:02 | 18853.64 | 25-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 28-NOV-16:30 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3618.08 | 01-NOV-16:05 | 19228.72 | 24-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 335.63 | 21-DEC-15:00 | 24510.48 | 05-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1923.40 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 18623.50 | 24510.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 691.16 | 20-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 16-JAN-12:10 | 492.10 | 01-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 663.55 | 03-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 584.83 | 02-FEB-23:00 |
March | 827.17 | 01-MAR-10:09 | 659.07 | 21-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.49 | 15-MAR-13:00 | 496.92 | 28-MAR-04:00 |
April | 827.17 | 03-APR-09:09 | 580.52 | 04-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.10 | 30-APR-15:03 | 259.73 | 21-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 509.07 | 05-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.18 | 20-MAY-18:50 | 196.12 | 01-MAY-04:45 |
June | 827.17 | 01-JUN-09:09 | 499.44 | 27-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 488.71 | 17-JUN-17:02 | 113.16 | 13-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 552.75 | 27-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 588.32 | 22-JUL-18:00 | 182.16 | 26-JUL-24:00 |
August | 827.17 | 01-AUG-09:09 | 633.09 | 04-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 532.12 | 13-AUG-16:00 | 251.38 | 05-AUG-17:50 |
September | 827.17 | 01-SEP-09:09 | 610.12 | 29-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 394.25 | 17-SEP-12:20 | 191.19 | 03-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 675.31 | 27-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.99 | 01-OCT-14:38 | 508.13 | 22-OCT-14:00 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 28-NOV-16:30 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.45 | 19-NOV-12:40 | 510.76 | 29-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:30 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.64 | 25-DEC-13:52 | 427.49 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 499.44 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.16 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 588.32 | 584.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1085.56 | 20-JAN-08:09 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.69 | 16-JAN-12:10 | 1004.06 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 1050.43 | 03-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1286.04 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 991.69 | 21-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 125.69 | 18-MAR-17:03 | 1117.41 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 846.02 | 04-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 741.22 | 30-APR-15:20 | 595.21 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 711.72 | 20-MAY-17:02 | 486.25 | 23-MAY-04:55 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1105.47 | 17-JUN-17:10 | 250.38 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1383.60 | 22-JUL-17:43 | 376.87 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 994.38 | 04-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1246.89 | 13-AUG-16:00 | 551.61 | 05-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 917.27 | 29-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 860.64 | 17-SEP-12:25 | 401.60 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1064.77 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 562.35 | 01-OCT-14:46 | 1084.05 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 28-NOV-16:30 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 299.33 | 19-NOV-15:00 | 1091.63 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 117.92 | 25-DEC-16:00 | 943.18 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.38 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1383.60 | 1286.04 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 680.11 | 20-JAN-16:00 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.55 | 29-JAN-16:10 | 680.27 | 01-JAN-01:00 |
February | 805.43 | 01-FEB-08:09 | 637.51 | 10-FEB-08:09 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 860.93 | 02-FEB-23:00 |
March | 805.43 | 01-MAR-08:09 | 567.30 | 09-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 84.10 | 18-MAR-17:03 | 744.87 | 28-MAR-04:00 |
April | 805.43 | 03-APR-07:10 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 502.77 | 30-APR-15:36 | 527.54 | 16-APR-08:40 |
May | 805.43 | 01-MAY-07:10 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 487.76 | 20-MAY-17:02 | 321.13 | 23-MAY-04:55 |
June | 805.43 | 01-JUN-07:10 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 742.08 | 17-JUN-17:02 | 174.40 | 11-JUN-06:20 |
July | 805.43 | 03-JUL-07:10 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 934.85 | 22-JUL-17:45 | 251.13 | 26-JUL-24:00 |
August | 805.43 | 01-AUG-07:10 | 617.61 | 04-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 832.36 | 13-AUG-16:00 | 371.84 | 05-AUG-18:00 |
September | 805.43 | 01-SEP-07:10 | 456.08 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 580.48 | 17-SEP-12:28 | 266.30 | 03-SEP-05:00 |
October | 805.43 | 02-OCT-07:10 | 582.91 | 31-OCT-15:00 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 383.26 | 01-OCT-14:46 | 784.07 | 22-OCT-14:00 |
November | 805.43 | 01-NOV-07:10 | 739.79 | 28-NOV-16:30 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.53 | 19-NOV-15:00 | 727.07 | 29-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 739.79 | 01-DEC-16:30 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.18 | 25-DEC-16:00 | 627.66 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.40 | |||||
Maximum of Months | 805.43 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 934.85 | 860.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1063.91 | 20-JAN-16:00 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.02 | 31-JAN-14:10 | 1115.01 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 1019.14 | 10-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1372.93 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 963.80 | 21-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 80.34 | 15-MAR-13:00 | 1141.14 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 865.98 | 04-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 736.00 | 30-APR-15:34 | 598.87 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 708.11 | 20-MAY-17:02 | 485.51 | 23-MAY-04:55 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1105.29 | 17-JUN-17:10 | 248.97 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 855.79 | 27-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1393.78 | 22-JUL-17:43 | 374.92 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 997.86 | 04-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1246.80 | 13-AUG-16:00 | 565.19 | 05-AUG-17:50 |
September | 1306.65 | 01-SEP-09:09 | 842.86 | 18-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 861.44 | 17-SEP-12:25 | 406.55 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 948.81 | 27-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 559.13 | 01-OCT-14:44 | 1263.55 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 28-NOV-16:30 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.06 | 01-NOV-16:00 | 1133.20 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:30 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 | 21-DEC-15:00 | 975.02 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.97 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1393.78 | 1372.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 693.02 | 20-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 79.79 | 16-JAN-12:07 | 698.71 | 01-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 666.29 | 03-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 882.01 | 02-FEB-23:00 |
March | 827.17 | 01-MAR-10:09 | 661.75 | 21-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.56 | 15-MAR-13:00 | 755.91 | 28-MAR-04:00 |
April | 827.17 | 03-APR-09:09 | 587.35 | 04-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 487.06 | 30-APR-15:34 | 400.46 | 21-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 517.79 | 05-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 437.00 | 20-MAY-17:47 | 327.64 | 23-MAY-04:55 |
June | 827.17 | 01-JUN-09:09 | 508.01 | 27-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 752.56 | 17-JUN-17:02 | 172.79 | 13-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 559.34 | 27-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 918.87 | 22-JUL-18:00 | 266.30 | 26-JUL-24:00 |
August | 827.17 | 01-AUG-09:09 | 636.54 | 04-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 831.19 | 13-AUG-16:00 | 374.85 | 05-AUG-17:50 |
September | 827.17 | 01-SEP-09:09 | 614.40 | 29-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 606.19 | 17-SEP-12:00 | 265.96 | 03-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 677.98 | 27-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.82 | 01-OCT-14:46 | 736.87 | 22-OCT-14:00 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 28-NOV-16:30 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.46 | 19-NOV-12:15 | 726.57 | 29-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:30 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 51.26 | 25-DEC-13:52 | 631.26 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 508.01 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.79 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 918.87 | 882.01 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.50 | 31-JAN-14:00 | 1580.98 | 01-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1938.07 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.68 | 18-MAR-17:03 | 1632.41 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 967.96 | 30-APR-14:53 | 841.36 | 21-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 918.14 | 20-MAY-17:02 | 680.49 | 23-MAY-04:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1463.07 | 17-JUN-17:02 | 333.77 | 13-JUN-04:05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1784.05 | 22-JUL-18:00 | 498.54 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1564.91 | 13-AUG-16:00 | 753.66 | 05-AUG-17:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1124.59 | 17-SEP-12:00 | 563.03 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 694.16 | 01-OCT-14:23 | 1509.93 | 22-OCT-14:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.22 | 19-NOV-15:00 | 1632.09 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.70 | 25-DEC-16:00 | 1389.93 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.77 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1784.05 | 1938.07 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.39 | 16-JAN-11:53 | 1817.70 | 01-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2384.04 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.76 | 18-MAR-17:03 | 2017.29 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1232.49 | 30-APR-15:20 | 1070.79 | 21-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1180.28 | 20-MAY-17:02 | 865.82 | 23-MAY-04:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1883.75 | 17-JUN-17:02 | 427.58 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2284.51 | 22-JUL-18:00 | 635.37 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1986.54 | 13-AUG-16:00 | 953.85 | 05-AUG-17:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1466.92 | 17-SEP-12:00 | 703.34 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 907.42 | 01-OCT-14:30 | 1829.22 | 22-OCT-14:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.52 | 19-NOV-15:00 | 1982.63 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.59 | 25-DEC-16:00 | 1703.59 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.58 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2284.51 | 2384.04 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.38 | 16-JAN-11:43 | 1577.35 | 01-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2141.93 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.38 | 15-MAR-13:00 | 1827.41 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 945.14 | 30-APR-16:00 | 991.86 | 26-APR-21:03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1063.98 | 20-MAY-17:02 | 787.02 | 23-MAY-04:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1919.07 | 17-JUN-17:02 | 397.96 | 13-JUN-04:08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2229.58 | 22-JUL-18:00 | 660.81 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1847.28 | 13-AUG-16:00 | 1112.01 | 05-AUG-17:35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1396.15 | 17-SEP-12:10 | 694.25 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 837.15 | 01-OCT-14:30 | 2308.95 | 22-OCT-14:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.66 | 19-NOV-15:00 | 1748.23 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.23 | 25-DEC-13:52 | 1530.37 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.96 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2229.58 | 2308.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 36717.85 | 09-JAN-06:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33981.28 | 01-FEB-06:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 38359.89 | 23-MAR-05:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41381.93 | 08-APR-05:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43779.92 | 30-MAY-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 44288.68 | 12-JUN-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 43914.83 | 27-JUL-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43617.75 | 07-AUG-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43928.56 | 12-SEP-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44539.64 | 10-OCT-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 43960.62 | 13-NOV-05:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 32733.23 | 27-DEC-06:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 32733.23 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44539.64 | 2541.06 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5936.24 | 31-JAN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.14 | 0.00 |
February | 4252.70 | 23-FEB-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.40 |
March | 7164.00 | 16-MAR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.23 | 0.00 |
April | 11301.60 | 14-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.34 | 0.00 |
May | 11346.57 | 19-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.18 | 0.00 |
June | 13878.17 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.71 | 0.00 |
July | 12991.26 | 20-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.09 | 0.00 |
August | 12997.16 | 09-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.65 | 0.00 |
September | 12137.73 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.97 | 0.00 |
October | 11014.44 | 02-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.57 | 0.00 |
November | 7379.41 | 01-NOV-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.54 | 0.00 |
December | 4761.69 | 22-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4252.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13878.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.71 | 124.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1886.27 | 27-JAN-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.29 | 0.00 |
February | 1467.97 | 09-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.30 |
March | 2513.46 | 28-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.05 |
April | 4573.81 | 24-APR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.17 | 0.00 |
May | 5099.62 | 08-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.12 | 0.00 |
June | 6451.33 | 19-JUN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 726.47 | 0.00 |
July | 6161.23 | 31-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.63 | 0.00 |
August | 6339.79 | 14-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.53 | 0.00 |
September | 5877.43 | 05-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.88 | 0.00 |
October | 5688.77 | 02-OCT-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.44 | 0.00 |
November | 2934.77 | 01-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.48 | 0.00 |
December | 2474.31 | 14-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1467.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6451.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 726.47 | 441.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2816.04 | 27-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 | 0.00 |
February | 2510.87 | 01-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.89 |
March | 3018.25 | 20-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.98 | 0.00 |
April | 5000.38 | 14-APR-17:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.38 | 0.00 |
May | 5921.45 | 08-MAY-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.37 | 0.00 |
June | 8069.92 | 19-JUN-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.63 | 0.00 |
July | 7911.27 | 31-JUL-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.26 | 0.00 |
August | 7447.81 | 18-AUG-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.46 | 0.00 |
September | 6763.55 | 06-SEP-17:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.40 | 0.00 |
October | 5647.93 | 06-OCT-17:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.64 | 0.00 |
November | 3713.75 | 02-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.44 | 0.00 |
December | 2859.96 | 06-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2510.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8069.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.63 | 280.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13532.11 | 27-JAN-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12342.24 | 01-FEB-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18935.34 | 20-MAR-05:03 | 1905.79 | 1847.62 | 9524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31677.71 | 15-APR-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33317.03 | 30-MAY-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33522.82 | 12-JUN-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33150.48 | 06-JUL-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32825.94 | 23-AUG-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33852.07 | 11-SEP-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33136.03 | 03-OCT-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27213.08 | 03-NOV-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12379.59 | 28-DEC-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12342.24 | 0.00 | 1847.62 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33852.07 | 6035.01 | 5543.17 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13435.56 | 27-JAN-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11763.95 | 22-FEB-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15651.66 | 17-MAR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31622.78 | 15-APR-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36102.66 | 08-MAY-04:03 | 0.00 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36777.82 | 12-JUN-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 36665.63 | 03-JUL-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36377.96 | 22-AUG-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37880.47 | 11-SEP-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35467.69 | 02-OCT-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15998.17 | 01-NOV-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11826.09 | 22-DEC-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11763.95 | 0.00 | 2463.50 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37880.47 | 6035.01 | 5543.17 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2984.12 | 31-JAN-16:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 38.36 | 0.00 |
February | 2186.13 | 22-FEB-16:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.05 |
March | 4335.95 | 16-MAR-16:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 71.50 | 0.00 |
April | 10113.75 | 30-APR-15:52 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 834.84 | 0.00 |
May | 12691.16 | 07-MAY-17:32 | 0.00 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 633.89 | 0.00 |
June | 14866.86 | 25-JUN-18:21 | 0.00 | 280.18 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 951.33 | 0.00 |
July | 14960.34 | 16-JUL-17:51 | 0.00 | 280.18 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1153.25 | 0.00 |
August | 14961.52 | 13-AUG-16:11 | 468.72 | 280.18 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1337.45 | 0.00 |
September | 14399.36 | 17-SEP-13:13 | 267.84 | 160.10 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 858.17 | 0.00 |
October | 12192.41 | 02-OCT-04:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 15.71 | 0.00 |
November | 4299.87 | 01-NOV-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 63.04 | 0.00 |
December | 2142.69 | 22-DEC-16:40 | 1272.23 | 914.33 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2142.69 | 0.00 | 160.10 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14961.52 | 1272.23 | 914.33 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1337.45 | 65.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2783.61 | 27-JAN-10:40 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.62 |
February | 3077.50 | 23-FEB-10:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.61 |
March | 4405.24 | 23-MAR-10:30 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.42 |
April | 11307.76 | 30-APR-08:32 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.39 |
May | 11591.37 | 28-MAY-08:43 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 |
June | 13242.52 | 18-JUN-09:12 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 191.69 | 0.00 |
July | 12900.08 | 23-JUL-10:02 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 174.24 | 0.00 |
August | 12942.08 | 13-AUG-09:32 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 89.64 | 0.00 |
September | 11783.50 | 10-SEP-10:32 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 190.28 | 0.00 |
October | 7889.45 | 02-OCT-04:02 | 0.00 | 410.97 | 2118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 10.24 | 0.00 |
November | 3762.76 | 01-NOV-10:30 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
December | 1919.98 | 25-DEC-16:03 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 63.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1919.98 | 0.00 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13242.52 | 827.22 | 456.08 | 2118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 191.69 | 52.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16196.05 | 15-JAN-14:02 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.43 |
February | 9145.90 | 23-FEB-14:00 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 |
March | 8690.73 | 16-MAR-13:40 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 43.72 | 0.00 |
April | 16258.86 | 30-APR-12:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 454.33 | 0.00 |
May | 14815.45 | 07-MAY-12:53 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 474.26 | 0.00 |
June | 15885.41 | 25-JUN-17:41 | 0.00 | 280.18 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 1045.34 | 0.00 |
July | 16188.12 | 30-JUL-17:41 | 0.00 | 280.18 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 1209.67 | 0.00 |
August | 16634.66 | 13-AUG-16:11 | 468.72 | 280.18 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 1313.92 | 0.00 |
September | 16951.78 | 24-SEP-12:12 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 240.29 | 0.00 |
October | 17736.33 | 15-OCT-13:52 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 159.25 | 0.00 |
November | 16234.73 | 19-NOV-14:43 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 |
December | 16974.45 | 25-DEC-14:02 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8690.73 | 0.00 | 160.10 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17736.33 | 1306.65 | 720.41 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 1313.92 | 84.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5854.87 | 31-JAN-16:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 25.57 | 0.00 |
February | 5716.47 | 22-FEB-16:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.53 |
March | 7812.13 | 18-MAR-17:08 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 2.07 | 0.00 |
April | 14657.22 | 23-APR-16:52 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 358.52 | 0.00 |
May | 14914.37 | 28-MAY-17:22 | 0.00 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 298.43 | 0.00 |
June | 15548.74 | 25-JUN-17:41 | 0.00 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 604.24 | 0.00 |
July | 15533.50 | 30-JUL-17:41 | 0.00 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 718.77 | 0.00 |
August | 15664.69 | 13-AUG-16:51 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 699.79 | 0.00 |
September | 13884.48 | 04-SEP-15:52 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 110.08 | 0.00 |
October | 15176.44 | 15-OCT-15:52 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 93.51 | 0.00 |
November | 7158.22 | 01-NOV-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 49.47 | 0.00 |
December | 5867.72 | 22-DEC-16:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5716.47 | 0.00 | 101.35 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15664.69 | 805.38 | 456.05 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 718.77 | 45.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2324.58 | 27-JAN-16:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 11.61 | 0.00 |
February | 1556.25 | 22-FEB-16:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.43 |
March | 2952.77 | 20-MAR-14:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 18.53 | 0.00 |
April | 5034.32 | 25-APR-15:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 107.68 | 0.00 |
May | 5593.66 | 08-MAY-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 64.48 | 0.00 |
June | 11696.97 | 25-JUN-18:21 | 0.00 | 280.18 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 538.24 | 0.00 |
July | 11858.31 | 16-JUL-17:41 | 0.00 | 400.26 | 5019.64 | 0.00 | 0.00 | 0.00 | 0.00 | 625.80 | 0.00 |
August | 11978.86 | 27-AUG-17:41 | 0.00 | 320.20 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 432.95 | 0.00 |
September | 11647.30 | 10-SEP-14:12 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 298.01 | 0.00 |
October | 9749.25 | 01-OCT-13:53 | 267.84 | 160.10 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 320.98 | 0.00 |
November | 4060.33 | 02-NOV-14:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 36.57 | 0.00 |
December | 1960.21 | 03-DEC-14:32 | 267.84 | 186.31 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1556.25 | 0.00 | 160.10 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11978.86 | 1306.65 | 720.41 | 5019.64 | 0.00 | 0.00 | 0.00 | 0.00 | 625.80 | 84.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2819.01 | 27-JAN-10:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.07 |
February | 2581.91 | 23-FEB-10:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 |
March | 3537.00 | 23-MAR-10:30 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.46 |
April | 8804.80 | 30-APR-10:22 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 21.78 | 0.00 |
May | 9624.13 | 29-MAY-09:22 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 | 0.00 |
June | 11349.24 | 11-JUN-09:42 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 15.85 | 0.00 |
July | 11561.39 | 04-JUL-10:22 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 68.82 | 0.00 |
August | 11481.05 | 27-AUG-11:02 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 184.65 | 0.00 |
September | 11348.56 | 10-SEP-10:52 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 107.04 | 0.00 |
October | 8325.00 | 01-OCT-13:53 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 213.02 | 0.00 |
November | 3930.51 | 02-NOV-08:40 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 |
December | 2476.88 | 01-DEC-10:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2476.88 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11561.39 | 827.22 | 456.08 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 213.02 | 29.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13366.22 | 15-JAN-14:02 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.89 |
February | 7802.11 | 27-FEB-13:06 | 6361.16 | 3602.05 | 7529.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1385.19 |
March | 10136.15 | 16-MAR-16:10 | 401.76 | 400.23 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 5285.71 | 0.00 |
April | 12300.03 | 30-APR-15:41 | 535.68 | 320.20 | 4015.69 | 0.00 | 0.00 | 0.00 | 0.00 | 448.03 | 0.00 |
May | 12719.25 | 15-MAY-17:00 | 401.76 | 400.23 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 11550.61 | 0.00 |
June | 14633.20 | 28-JUN-17:00 | 401.76 | 400.23 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 14691.56 | 0.00 |
July | 13779.16 | 20-JUL-17:00 | 401.76 | 400.23 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 12722.86 | 0.00 |
August | 14441.92 | 25-AUG-17:00 | 401.76 | 400.23 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 13877.35 | 0.00 |
September | 14201.95 | 10-SEP-13:32 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 289.67 | 0.00 |
October | 14526.05 | 09-OCT-13:52 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 28.07 | 0.00 |
November | 13494.64 | 19-NOV-14:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.98 |
December | 13278.45 | 03-DEC-13:13 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7802.11 | 267.84 | 160.10 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14633.20 | 6361.16 | 3602.05 | 7529.41 | 0.00 | 0.00 | 0.00 | 0.00 | 14691.56 | 1385.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4874.87 | 24-JAN-16:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 | 0.00 |
February | 4218.62 | 22-FEB-16:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.86 |
March | 4510.80 | 18-MAR-17:10 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 3.59 | 0.00 |
April | 11799.39 | 23-APR-17:21 | 0.00 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.58 | 0.00 |
May | 12036.64 | 29-MAY-17:21 | 0.00 | 228.04 | 2859.87 | 0.00 | 0.00 | 0.00 | 0.00 | 157.38 | 0.00 |
June | 12211.96 | 11-JUN-17:41 | 0.00 | 228.04 | 2859.87 | 0.00 | 0.00 | 0.00 | 0.00 | 144.19 | 0.00 |
July | 12387.51 | 30-JUL-17:31 | 0.00 | 253.38 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 372.83 | 0.00 |
August | 12992.98 | 27-AUG-17:41 | 0.00 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.22 | 0.00 |
September | 12326.42 | 04-SEP-17:32 | 0.00 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 79.02 | 0.00 |
October | 11881.81 | 09-OCT-15:12 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 70.38 | 0.00 |
November | 6475.65 | 01-NOV-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 26.65 | 0.00 |
December | 5330.48 | 22-DEC-16:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4218.62 | 0.00 | 101.35 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12992.98 | 805.38 | 456.05 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 372.83 | 23.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2955.42 | 31-JAN-16:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 32.10 | 0.00 |
February | 2180.93 | 22-FEB-16:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.74 |
March | 4087.42 | 20-MAR-14:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 28.80 | 0.00 |
April | 5920.85 | 25-APR-15:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 168.10 | 0.00 |
May | 12149.86 | 21-MAY-18:31 | 0.00 | 280.18 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 229.14 | 0.00 |
June | 12587.66 | 25-JUN-18:11 | 0.00 | 400.26 | 5019.64 | 0.00 | 0.00 | 0.00 | 0.00 | 828.56 | 0.00 |
July | 12505.34 | 04-JUL-19:01 | 0.00 | 360.04 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 527.06 | 0.00 |
August | 12439.35 | 13-AUG-16:11 | 468.72 | 280.18 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1138.09 | 0.00 |
September | 12174.61 | 10-SEP-17:02 | 0.00 | 200.13 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 673.71 | 0.00 |
October | 10318.73 | 02-OCT-04:02 | 0.00 | 649.16 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
November | 4042.51 | 02-NOV-14:00 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 56.76 | 0.00 |
December | 2210.17 | 22-DEC-16:40 | 1272.23 | 914.34 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2180.93 | 0.00 | 200.13 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12587.66 | 1306.65 | 914.34 | 5019.64 | 0.00 | 0.00 | 0.00 | 0.00 | 1138.09 | 53.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3312.24 | 27-JAN-10:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.03 |
February | 3569.55 | 23-FEB-10:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.49 |
March | 4600.10 | 23-MAR-10:20 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.18 |
April | 10652.71 | 30-APR-08:13 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.47 |
May | 12533.73 | 21-MAY-09:12 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 |
June | 13059.83 | 04-JUN-09:21 | 296.74 | 177.38 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 36.87 | 0.00 |
July | 12704.57 | 04-JUL-09:02 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 29.04 | 0.00 |
August | 12987.90 | 27-AUG-09:11 | 296.74 | 177.38 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 144.37 | 0.00 |
September | 12535.75 | 10-SEP-10:22 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 121.55 | 0.00 |
October | 8034.90 | 01-OCT-10:02 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 85.54 | 0.00 |
November | 4151.00 | 10-NOV-09:40 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.21 |
December | 2359.34 | 27-DEC-10:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2359.34 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13059.83 | 805.43 | 456.08 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 144.37 | 68.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14283.50 | 29-JAN-12:43 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.80 |
February | 8906.44 | 28-FEB-14:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.43 |
March | 8202.47 | 23-MAR-13:50 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 41.65 | 0.00 |
April | 14069.09 | 30-APR-13:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 473.32 | 0.00 |
May | 13337.21 | 07-MAY-16:01 | 602.64 | 360.23 | 4517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 494.07 | 0.00 |
June | 13629.36 | 04-JUN-15:21 | 602.64 | 360.23 | 4517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 792.48 | 0.00 |
July | 13905.88 | 16-JUL-15:32 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 344.59 | 0.00 |
August | 14043.18 | 27-AUG-15:51 | 669.60 | 400.26 | 5019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 843.35 | 0.00 |
September | 14462.84 | 10-SEP-13:01 | 468.72 | 280.18 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 442.05 | 0.00 |
October | 14312.41 | 09-OCT-14:02 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 68.35 | 0.00 |
November | 14207.90 | 05-NOV-13:32 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.50 |
December | 14842.42 | 25-DEC-13:32 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8202.47 | 267.84 | 160.10 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14842.42 | 1306.65 | 720.41 | 5019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 843.35 | 213.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5640.70 | 31-JAN-16:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 21.40 | 0.00 |
February | 5560.78 | 22-FEB-16:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.62 |
March | 6733.34 | 18-MAR-17:08 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 3.38 | 0.00 |
April | 13314.94 | 02-APR-17:52 | 0.00 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 68.10 | 0.00 |
May | 13636.89 | 21-MAY-18:31 | 0.00 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 70.91 | 0.00 |
June | 13774.52 | 25-JUN-17:31 | 0.00 | 253.38 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 459.35 | 0.00 |
July | 13465.79 | 30-JUL-17:41 | 0.00 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 614.47 | 0.00 |
August | 13674.07 | 27-AUG-16:31 | 423.88 | 253.38 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 389.53 | 0.00 |
September | 13642.81 | 04-SEP-15:41 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 79.93 | 0.00 |
October | 10849.29 | 09-OCT-16:02 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 195.94 | 0.00 |
November | 6800.71 | 01-NOV-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 41.45 | 0.00 |
December | 5697.83 | 22-DEC-16:30 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5560.78 | 0.00 | 101.35 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13774.52 | 805.38 | 456.05 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 614.47 | 37.62 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.116813E+12 | 133918.00 | 02-JAN-07:10 | 0.889683E+10 | 22264.88 | 02-JAN-07:30 |
February | 0.964388E+11 | 95952.95 | 13-FEB-07:10 | 0.812256E+10 | 16494.68 | 01-FEB-07:49 |
March | 0.119646E+12 | 118804.27 | 16-MAR-15:39 | 0.919760E+10 | 30302.75 | 27-MAR-06:19 |
April | 0.140857E+12 | 153927.18 | 14-APR-15:30 | 0.778353E+10 | 8882.03 | 03-APR-11:00 |
May | 0.164179E+12 | 161086.97 | 31-MAY-15:00 | 0.780208E+10 | 8757.78 | 01-MAY-11:50 |
June | 0.195223E+12 | 189877.00 | 28-JUN-15:09 | 0.732270E+10 | 8644.47 | 02-JUN-11:20 |
July | 0.185507E+12 | 177725.58 | 31-JUL-15:00 | 0.709814E+10 | 8565.17 | 05-JUL-11:20 |
August | 0.193305E+12 | 182583.07 | 25-AUG-15:20 | 0.748328E+10 | 8595.12 | 28-AUG-11:09 |
September | 0.167520E+12 | 172062.33 | 08-SEP-15:00 | 0.723096E+10 | 8683.14 | 29-SEP-11:20 |
October | 0.138487E+12 | 155823.34 | 02-OCT-15:09 | 0.788879E+10 | 15769.36 | 25-OCT-06:00 |
November | 0.115099E+12 | 121654.35 | 01-NOV-15:00 | 0.813839E+10 | 19317.28 | 24-NOV-07:19 |
December | 0.110270E+12 | 108242.90 | 18-DEC-07:10 | 0.100577E+11 | 36321.59 | 06-DEC-07:30 |
Annual Sum or Average | 0.174334E+13 | 0.970225E+11 | ||||
Minimum of Months | 0.964388E+11 | 95952.95 | 0.709814E+10 | 8565.17 | ||
Maximum of Months | 0.195223E+12 | 189877.00 | 0.100577E+11 | 36321.59 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.237561E+11 | 0.724405E+10 | 0.641572E+11 | 0.109112E+10 | 0.642209E+10 | 1312252.65 | 0.223011E+10 | 0.119104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.214393E+11 | 0.615428E+10 | 0.580684E+11 | 0.987380E+09 | 0.465042E+10 | 1186778.30 | 0.219293E+10 | 0.294488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251899E+11 | 0.623371E+10 | 0.666107E+11 | 0.114320E+10 | 0.644426E+10 | 1343621.24 | 0.182999E+10 | 0.121926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223919E+11 | 0.543920E+10 | 0.619407E+11 | 0.105058E+10 | 0.125143E+11 | 1267813.82 | 0.149014E+09 | 0.373699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.240780E+11 | 0.511000E+10 | 0.653840E+11 | 0.111688E+10 | 0.161781E+11 | 1327936.95 | 7776262.05 | 0.523026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.238759E+11 | 0.473229E+10 | 0.641577E+11 | 0.109957E+10 | 0.219644E+11 | 1296568.36 | 0.00 | 0.793918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.224069E+11 | 0.496995E+10 | 0.631525E+11 | 0.106760E+10 | 0.198741E+11 | 1299182.41 | 0.00 | 0.740344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.250494E+11 | 0.539009E+10 | 0.666107E+11 | 0.114312E+10 | 0.202430E+11 | 1343621.24 | 0.00 | 0.748676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.224663E+11 | 0.576931E+10 | 0.619118E+11 | 0.105022E+10 | 0.162523E+11 | 1267813.82 | 0.00 | 0.600689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.235366E+11 | 0.658049E+10 | 0.641717E+11 | 0.109116E+10 | 0.108892E+11 | 1312252.65 | 0.444563E+09 | 0.317722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.234242E+11 | 0.688635E+10 | 0.627379E+11 | 0.107110E+10 | 0.712539E+10 | 1278270.02 | 0.107350E+10 | 0.127789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230875E+11 | 0.740744E+10 | 0.631380E+11 | 0.106791E+10 | 0.549072E+10 | 1299182.41 | 0.442663E+10 | 0.565034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280702E+12 | 0.719172E+11 | 0.762041E+12 | 0.129798E+11 | 0.148048E+12 | 15535293.87 | 0.123545E+11 | 0.455285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.214393E+11 | 0.473229E+10 | 0.580684E+11 | 0.987380E+09 | 0.465042E+10 | 1186778.30 | 0.00 | 0.294488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.251899E+11 | 0.740744E+10 | 0.666107E+11 | 0.114320E+10 | 0.219644E+11 | 1343621.24 | 0.442663E+10 | 0.793918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.223563E+09 | 0.00 | 0.867327E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.298449E+09 | 0.00 | 0.782411E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.464318E+09 | 0.00 | 0.873329E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.778353E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.780208E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.732270E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.709814E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.748328E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.723096E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 60474811.96 | 0.00 | 0.782831E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.125492E+09 | 0.00 | 0.801290E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.165642E+10 | 0.00 | 0.840127E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.282871E+10 | 0.00 | 0.941938E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.709814E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.165642E+10 | 0.00 | 0.873329E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 27077.29 | 20-JAN-16:00 | 5557.43 | 01-JAN-06:10 | 47562.27 | 02-JAN-08:09 | 926.51 | 20-JAN-08:39 | 11575.68 | 27-JAN-16:00 | 0.73 | 02-JAN-08:09 | 93091.75 | 02-JAN-07:10 |
February | 26645.87 | 10-FEB-08:09 | 5557.43 | 01-FEB-06:10 | 47562.27 | 01-FEB-08:09 | 926.15 | 10-FEB-08:20 | 8453.39 | 22-FEB-16:30 | 0.73 | 01-FEB-06:10 | 55521.30 | 13-FEB-07:10 |
March | 26029.09 | 21-MAR-07:10 | 5557.43 | 01-MAR-06:10 | 47562.27 | 01-MAR-08:09 | 925.26 | 21-MAR-07:19 | 13438.38 | 16-MAR-15:30 | 0.73 | 13-MAR-07:10 | 55052.48 | 27-MAR-06:10 |
April | 24855.63 | 04-APR-07:10 | 5557.43 | 01-APR-05:10 | 47562.27 | 03-APR-07:10 | 923.57 | 04-APR-07:19 | 23053.37 | 25-APR-15:30 | 0.73 | 01-APR-05:19 | 11062.89 | 21-APR-06:10 |
May | 23864.86 | 05-MAY-07:10 | 5557.43 | 01-MAY-05:10 | 47562.27 | 01-MAY-07:10 | 922.15 | 05-MAY-07:19 | 25148.04 | 08-MAY-15:00 | 0.73 | 01-MAY-05:19 | 3893.10 | 01-MAY-06:19 |
June | 23835.67 | 27-JUN-07:10 | 5557.43 | 01-JUN-05:10 | 47562.27 | 01-JUN-07:10 | 922.11 | 27-JUN-07:19 | 28932.60 | 19-JUN-14:00 | 0.73 | 04-JUN-16:10 | 0.00 | 01-JUN-00:10 |
July | 24383.75 | 27-JUL-07:10 | 5557.43 | 01-JUL-05:10 | 47562.27 | 03-JUL-07:10 | 922.89 | 27-JUL-07:19 | 26914.01 | 05-JUL-15:20 | 0.73 | 30-JUL-16:19 | 0.00 | 01-JUL-00:10 |
August | 26345.89 | 04-AUG-07:10 | 5557.43 | 01-AUG-05:10 | 47562.27 | 01-AUG-07:10 | 925.71 | 04-AUG-07:19 | 27549.19 | 14-AUG-15:20 | 0.73 | 13-AUG-16:10 | 0.00 | 01-AUG-00:10 |
September | 25020.96 | 29-SEP-07:10 | 5557.43 | 01-SEP-05:10 | 47562.27 | 01-SEP-07:10 | 923.81 | 29-SEP-07:19 | 24800.84 | 05-SEP-15:00 | 0.73 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 26149.54 | 27-OCT-07:10 | 5557.43 | 01-OCT-05:10 | 47562.27 | 02-OCT-07:10 | 925.43 | 27-OCT-07:19 | 21731.25 | 02-OCT-15:30 | 0.73 | 01-OCT-05:10 | 21201.85 | 26-OCT-06:10 |
November | 28079.40 | 28-NOV-16:30 | 5557.43 | 01-NOV-05:10 | 47562.27 | 01-NOV-07:10 | 926.74 | 28-NOV-16:40 | 14469.79 | 02-NOV-15:39 | 0.73 | 01-NOV-05:30 | 43301.79 | 24-NOV-07:10 |
December | 28079.40 | 01-DEC-16:30 | 5557.43 | 01-DEC-06:10 | 47562.27 | 01-DEC-08:09 | 926.74 | 01-DEC-16:40 | 9998.08 | 22-DEC-16:40 | 0.73 | 04-DEC-08:09 | 67701.96 | 18-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 23835.67 | 5557.43 | 47562.27 | 922.11 | 8453.39 | 0.73 | 0.00 | |||||||
Maximum of Months | 28079.40 | 5557.43 | 47562.27 | 926.74 | 28932.60 | 0.73 | 93091.75 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 35275.46 | 31-JAN-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15962.15 | 22-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 36992.54 | 16-MAR-15:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 63101.27 | 14-APR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 68936.51 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 95685.14 | 28-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 86492.82 | 19-JUL-13:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 89004.55 | 25-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79351.98 | 08-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 69082.14 | 02-OCT-13:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 41262.58 | 01-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26762.40 | 22-DEC-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 15962.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 95685.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 133918.00 | 02-JAN-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 3799.09 | 0.73 | 93091.75 | 0.00 | 0.00 |
February | 95952.95 | 13-FEB-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 3404.49 | 0.73 | 55521.30 | 0.00 | 0.00 |
March | 118804.27 | 16-MAR-15:39 | 23688.37 | 43769.98 | 0.00 | 920.43 | 13432.22 | 0.73 | 0.00 | 36992.54 | 0.00 |
April | 153927.18 | 14-APR-15:30 | 23688.37 | 43769.98 | 0.00 | 920.43 | 22446.41 | 0.73 | 0.00 | 63101.27 | 0.00 |
May | 161086.97 | 31-MAY-15:00 | 23688.37 | 43769.98 | 0.00 | 920.43 | 23770.95 | 0.73 | 0.00 | 68936.51 | 0.00 |
June | 189877.00 | 28-JUN-15:09 | 23688.37 | 43769.98 | 0.00 | 920.43 | 25880.81 | 0.73 | 0.00 | 95616.68 | 0.00 |
July | 177725.58 | 31-JUL-15:00 | 23688.37 | 43769.98 | 0.00 | 920.43 | 26743.94 | 0.73 | 0.00 | 82602.13 | 0.00 |
August | 182583.07 | 25-AUG-15:20 | 23688.37 | 43769.98 | 0.00 | 920.43 | 25199.01 | 0.73 | 0.00 | 89004.55 | 0.00 |
September | 172062.33 | 08-SEP-15:00 | 23688.37 | 43769.98 | 0.00 | 920.43 | 24330.84 | 0.73 | 0.00 | 79351.98 | 0.00 |
October | 155823.34 | 02-OCT-15:09 | 23688.37 | 43769.98 | 0.00 | 920.43 | 21632.47 | 0.73 | 0.00 | 65811.37 | 0.00 |
November | 121654.35 | 01-NOV-15:00 | 23688.37 | 43769.98 | 0.00 | 920.43 | 12645.69 | 0.73 | 0.00 | 40629.16 | 0.00 |
December | 108242.90 | 18-DEC-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 3513.78 | 0.73 | 67701.96 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 95952.95 | 9359.67 | 21853.28 | 0.00 | 256.05 | 3404.49 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 189877.00 | 23688.37 | 43769.98 | 5557.43 | 920.43 | 26743.94 | 0.73 | 93091.75 | 95616.68 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 14210.25 | 02-JAN-07:30 | 0.00 | 9054.35 | 12-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 8630.65 | 28-FEB-07:10 | 0.00 | 9054.60 | 03-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 22262.25 | 27-MAR-06:19 | 0.00 | 9003.72 | 01-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 8882.03 | 03-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 8757.78 | 01-MAY-11:50 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 8644.47 | 02-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 8565.17 | 05-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 8595.12 | 28-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 8683.14 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 7765.10 | 25-OCT-06:00 | 0.00 | 8820.07 | 31-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 11280.83 | 24-NOV-07:19 | 0.00 | 8943.74 | 30-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 30205.54 | 06-DEC-07:19 | 0.00 | 9027.36 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8565.17 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 30205.54 | 0.00 | 9054.60 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.17 | 0.00 | 26.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.18 | 0.00 | 26.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.29 | 0.00 | 26.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.26 | 0.00 | 26.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.74 | 0.00 | 26.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.20 | 0.00 | 26.20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.33 | 26.27 | 0.00 | 26.27 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.74 | 0.00 | 26.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.18 | 0.00 | 26.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 26.18 | 0.00 | 26.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.18 | 0.00 | 26.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 16.03 | 0.17 | 15.69 | 0.00 | 15.69 | 0.00 | 15.69 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.42 | 0.67 | 27.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.50 | 2.50 | 27.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.77 | 5.83 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.71 | 8.67 | 27.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.72 | 4.33 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.59 | 4.17 | 27.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.57 | 1.17 | 27.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
Annual Sum or Average | 0.50 | 16.42 | 0.17 | 16.07 | 46.67 | 27.52 | 27.33 | 27.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 17.21 | 0.17 | 17.21 | 14.83 | 27.77 | 8.67 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.80 | 6.17 | 27.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.86 | 12.17 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 28.10 | 11.33 | 28.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 28.04 | 14.00 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.10 | 8.17 | 28.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.87 | 7.83 | 27.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.64 | 2.50 | 27.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
Annual Sum or Average | 0.33 | 17.11 | 0.00 | 17.11 | 79.17 | 27.93 | 62.17 | 27.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.15 | 0.00 | 17.15 | 19.00 | 28.10 | 14.00 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.70 | 4.50 | 27.70 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.76 | 5.33 | 27.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.59 | 5.83 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.75 | 6.00 | 27.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.80 | 9.33 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.96 | 5.17 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.02 | 6.83 | 28.07 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.97 | 6.67 | 28.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.69 | 2.17 | 27.69 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.75 | 3.17 | 27.75 |
Annual Sum or Average | 0.00 | 0.00 | 74.33 | 27.82 | 55.00 | 27.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 28.02 | 9.33 | 28.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.75 | 0.17 | 27.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.24 | 4.00 | 28.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 28.42 | 5.00 | 28.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 28.39 | 5.67 | 28.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 28.30 | 8.33 | 28.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.43 | 4.67 | 28.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.15 | 4.50 | 28.19 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.98 | 3.00 | 28.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
Annual Sum or Average | 0.33 | 17.18 | 0.00 | 17.18 | 68.33 | 28.26 | 35.33 | 28.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.21 | 0.00 | 17.21 | 16.50 | 28.43 | 8.33 | 28.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.44 | 1.17 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.47 | 3.00 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.33 | 1.83 | 27.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.35 | 1.67 | 27.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.67 | 27.41 | 8.00 | 27.41 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.47 | 3.00 | 27.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.58 | 2.33 | 27.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.70 | 5.17 | 27.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.79 | 9.67 | 27.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.75 | 13.00 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.80 | 7.67 | 27.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.60 | 8.50 | 27.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.45 | 3.33 | 27.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 56.83 | 27.71 | 49.67 | 27.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.80 | 13.00 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.17 | 19.65 | 13.17 | 19.65 | 5.00 | 20.94 | 5.00 | 21.86 |
February | 16.50 | 19.16 | 16.50 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
March | 16.33 | 18.88 | 16.33 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
April | 1.00 | 20.25 | 1.00 | 20.25 | 16.83 | 24.78 | 16.83 | 25.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 25.21 | 26.67 | 25.21 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 48.83 | 26.26 | 48.50 | 26.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 47.17 | 26.24 | 45.17 | 26.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 54.83 | 26.18 | 52.33 | 26.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 66.00 | 25.78 | 63.50 | 25.75 |
October | 4.67 | 19.84 | 4.67 | 19.84 | 47.00 | 24.76 | 45.67 | 25.18 |
November | 3.83 | 19.95 | 3.83 | 19.95 | 4.33 | 22.60 | 4.33 | 23.84 |
December | 17.83 | 18.64 | 17.83 | 18.64 | 5.00 | 19.75 | 5.00 | 20.62 |
Annual Sum or Average | 73.33 | 19.16 | 73.33 | 19.16 | 321.67 | 23.85 | 313.00 | 24.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.88 | 0.00 | 18.88 |
Maximum of Months | 17.83 | 20.25 | 17.83 | 20.25 | 66.00 | 26.26 | 63.50 | 26.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.91 | 2.83 | 27.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.05 | 3.83 | 28.04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.09 | 3.83 | 28.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 28.01 | 6.17 | 28.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.98 | 4.50 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.82 | 4.67 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.80 | 2.83 | 27.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 53.17 | 27.98 | 28.67 | 27.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 28.09 | 6.17 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.36 | 0.17 | 27.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.57 | 4.67 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.55 | 6.00 | 27.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.50 | 3.17 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.46 | 2.50 | 27.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.42 | 0.67 | 27.42 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 28.83 | 27.53 | 17.17 | 27.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.57 | 6.00 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.75 | 5.50 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.79 | 9.67 | 27.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.96 | 11.00 | 28.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.89 | 13.00 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.96 | 7.83 | 28.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.68 | 7.33 | 27.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.55 | 2.67 | 27.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 65.33 | 27.85 | 57.00 | 27.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.96 | 13.00 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.74 | 5.33 | 27.74 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.59 | 4.50 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.40 | 3.33 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.55 | 5.00 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.62 | 8.00 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.75 | 5.00 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.85 | 7.00 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.88 | 7.00 | 27.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.66 | 3.17 | 27.66 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.73 | 4.50 | 27.73 |
Annual Sum or Average | 0.00 | 0.00 | 63.83 | 27.69 | 52.83 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.88 | 8.00 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.44 | 0.33 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.09 | 3.50 | 28.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.28 | 4.67 | 28.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 28.26 | 4.50 | 28.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 28.31 | 5.83 | 28.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.27 | 3.83 | 28.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.97 | 4.33 | 28.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.91 | 2.83 | 27.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 55.83 | 28.20 | 29.83 | 28.22 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 28.31 | 5.83 | 28.36 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 211.17 | 23.91 | 54.83 | 24.14 | 12.33 | 24.10 |
February | 85.83 | 23.86 | 93.50 | 24.37 | 0.00 | 24.37 |
March | 122.67 | 24.03 | 80.33 | 24.54 | 0.00 | 24.54 |
April | 84.83 | 24.02 | 45.83 | 24.71 | 0.00 | 24.71 |
May | 39.67 | 24.02 | 47.17 | 25.26 | 0.00 | 25.26 |
June | 0.00 | 0.00 | 150.17 | 24.99 | 0.00 | 24.99 |
July | 9.33 | 24.00 | 412.33 | 24.48 | 0.00 | 24.48 |
August | 0.00 | 0.00 | 458.00 | 24.40 | 0.00 | 24.40 |
September | 0.17 | 27.22 | 414.83 | 24.53 | 0.17 | 24.53 |
October | 73.17 | 24.01 | 195.67 | 24.69 | 0.00 | 24.69 |
November | 153.17 | 24.02 | 145.17 | 24.42 | 2.67 | 24.41 |
December | 340.00 | 24.03 | 2.67 | 24.04 | 0.00 | 24.04 |
Annual Sum or Average | 1120.00 | 23.99 | 2100.50 | 24.46 | 15.17 | 24.46 |
Minimum of Months | 0.00 | 0.00 | 2.67 | 24.04 | 0.00 | 24.04 |
Maximum of Months | 340.00 | 27.22 | 458.00 | 25.26 | 12.33 | 25.26 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 426.17 | 23.47 | 14.00 | 23.40 | 12.33 | 23.33 |
February | 369.50 | 23.33 | 3.67 | 23.34 | 0.00 | 23.34 |
March | 311.67 | 23.58 | 16.17 | 23.63 | 0.00 | 23.63 |
April | 178.50 | 23.92 | 20.33 | 24.12 | 0.00 | 24.12 |
May | 115.67 | 24.02 | 30.00 | 24.43 | 0.00 | 24.43 |
June | 8.17 | 24.01 | 112.33 | 24.87 | 0.00 | 24.87 |
July | 11.50 | 24.02 | 398.67 | 24.39 | 0.00 | 24.39 |
August | 7.00 | 24.01 | 450.67 | 24.31 | 1.50 | 24.31 |
September | 0.00 | 0.00 | 391.50 | 24.45 | 0.00 | 24.45 |
October | 182.17 | 23.86 | 128.17 | 24.17 | 0.00 | 24.17 |
November | 301.50 | 23.68 | 90.33 | 23.87 | 12.50 | 23.87 |
December | 490.67 | 23.33 | 0.00 | 23.33 | 0.00 | 23.33 |
Annual Sum or Average | 2402.50 | 23.56 | 1655.83 | 23.93 | 26.33 | 23.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.33 | 0.00 | 23.33 |
Maximum of Months | 490.67 | 24.02 | 450.67 | 24.87 | 12.50 | 24.87 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 483.50 | 22.92 | 21.50 | 22.78 | 21.50 | 22.66 |
February | 422.67 | 22.68 | 4.17 | 22.66 | 4.17 | 22.64 |
March | 404.00 | 23.15 | 10.00 | 23.12 | 7.00 | 23.09 |
April | 198.33 | 23.78 | 20.17 | 23.90 | 0.00 | 23.90 |
May | 131.33 | 23.99 | 33.17 | 24.33 | 0.00 | 24.33 |
June | 6.67 | 24.01 | 146.67 | 24.74 | 0.00 | 24.74 |
July | 15.17 | 24.00 | 403.00 | 24.41 | 3.67 | 24.41 |
August | 10.67 | 24.00 | 452.83 | 24.32 | 5.17 | 24.32 |
September | 6.50 | 23.88 | 389.83 | 24.44 | 3.17 | 24.44 |
October | 247.83 | 23.52 | 110.50 | 23.80 | 1.17 | 23.80 |
November | 367.83 | 23.06 | 58.50 | 23.20 | 16.17 | 23.21 |
December | 497.00 | 22.42 | 44.67 | 22.27 | 44.67 | 22.15 |
Annual Sum or Average | 2791.50 | 23.03 | 1695.00 | 23.50 | 106.67 | 23.45 |
Minimum of Months | 6.50 | 22.42 | 4.17 | 22.27 | 0.00 | 22.15 |
Maximum of Months | 497.00 | 24.01 | 452.83 | 24.74 | 44.67 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.97 | 97.83 | 21.66 | 97.83 | 21.43 |
February | 446.83 | 21.66 | 58.50 | 21.48 | 58.50 | 21.34 |
March | 433.33 | 22.26 | 57.50 | 22.10 | 49.33 | 21.93 |
April | 213.33 | 23.36 | 55.67 | 23.67 | 2.00 | 23.65 |
May | 109.50 | 23.72 | 91.33 | 24.46 | 0.17 | 24.47 |
June | 22.67 | 25.94 | 318.00 | 24.80 | 14.17 | 24.89 |
July | 53.00 | 25.85 | 448.17 | 24.76 | 47.17 | 24.87 |
August | 37.67 | 25.36 | 469.00 | 24.51 | 29.67 | 24.58 |
September | 65.00 | 25.07 | 410.17 | 24.60 | 42.83 | 24.71 |
October | 294.50 | 22.86 | 127.17 | 23.18 | 24.17 | 23.11 |
November | 432.50 | 22.19 | 117.83 | 22.10 | 97.00 | 21.97 |
December | 497.00 | 21.34 | 222.67 | 21.06 | 222.67 | 20.92 |
Annual Sum or Average | 3107.33 | 22.34 | 2473.83 | 22.94 | 685.50 | 22.79 |
Minimum of Months | 22.67 | 21.34 | 55.67 | 21.06 | 0.17 | 20.92 |
Maximum of Months | 502.00 | 25.94 | 469.00 | 24.80 | 222.67 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 454.67 | 22.40 | 67.00 | 22.10 | 64.67 | 21.86 |
February | 396.33 | 21.96 | 46.33 | 21.86 | 36.83 | 21.72 |
March | 350.50 | 22.47 | 61.33 | 22.47 | 29.83 | 22.31 |
April | 108.83 | 23.45 | 186.33 | 24.30 | 7.33 | 24.34 |
May | 64.33 | 24.56 | 242.00 | 24.79 | 17.00 | 24.93 |
June | 42.83 | 26.78 | 402.83 | 24.83 | 38.33 | 25.01 |
July | 65.67 | 26.53 | 465.83 | 24.91 | 62.67 | 25.09 |
August | 50.00 | 26.29 | 486.00 | 24.66 | 46.17 | 24.81 |
September | 63.67 | 25.73 | 434.33 | 24.70 | 47.83 | 24.86 |
October | 216.33 | 23.01 | 187.17 | 23.63 | 22.33 | 23.58 |
November | 375.33 | 22.45 | 95.17 | 22.45 | 63.17 | 22.34 |
December | 497.00 | 21.84 | 141.67 | 21.52 | 141.67 | 21.32 |
Annual Sum or Average | 2685.50 | 22.71 | 2816.00 | 23.43 | 577.83 | 23.38 |
Minimum of Months | 42.83 | 21.84 | 46.33 | 21.52 | 7.33 | 21.32 |
Maximum of Months | 497.00 | 26.78 | 486.00 | 24.91 | 141.67 | 25.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 267.67 | 22.27 | 171.50 | 22.70 | 53.00 | 22.46 |
February | 305.83 | 21.82 | 102.83 | 22.11 | 34.00 | 21.96 |
March | 315.67 | 22.39 | 99.50 | 22.55 | 34.33 | 22.37 |
April | 164.00 | 23.32 | 151.83 | 24.00 | 5.33 | 24.02 |
May | 123.00 | 23.66 | 135.00 | 24.37 | 2.33 | 24.40 |
June | 40.83 | 25.10 | 296.17 | 24.74 | 15.83 | 24.85 |
July | 61.50 | 25.69 | 440.17 | 24.75 | 49.83 | 24.87 |
August | 46.00 | 25.57 | 472.17 | 24.55 | 36.50 | 24.65 |
September | 67.33 | 25.52 | 427.67 | 24.70 | 47.67 | 24.85 |
October | 191.17 | 23.34 | 234.17 | 23.99 | 32.33 | 24.06 |
November | 262.50 | 22.53 | 178.67 | 22.99 | 59.83 | 22.86 |
December | 336.50 | 22.06 | 167.33 | 22.10 | 109.00 | 21.84 |
Annual Sum or Average | 2182.00 | 22.79 | 2877.00 | 23.61 | 480.00 | 23.54 |
Minimum of Months | 40.83 | 21.82 | 99.50 | 22.10 | 2.33 | 21.84 |
Maximum of Months | 336.50 | 25.69 | 472.17 | 24.75 | 109.00 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 409.17 | 21.74 | 106.67 | 21.55 | 90.33 | 21.33 |
February | 404.00 | 21.50 | 71.00 | 21.43 | 56.00 | 21.29 |
March | 389.50 | 22.05 | 91.67 | 22.10 | 47.00 | 21.94 |
April | 192.17 | 23.23 | 155.50 | 23.87 | 15.67 | 23.95 |
May | 137.50 | 23.85 | 194.00 | 24.42 | 18.00 | 24.57 |
June | 53.83 | 25.10 | 334.50 | 24.71 | 22.50 | 24.85 |
July | 70.50 | 25.70 | 445.83 | 24.75 | 57.17 | 24.89 |
August | 53.17 | 25.22 | 461.67 | 24.53 | 39.17 | 24.62 |
September | 77.00 | 24.78 | 413.33 | 24.56 | 47.67 | 24.68 |
October | 266.00 | 22.73 | 180.50 | 23.30 | 32.00 | 23.27 |
November | 371.50 | 22.03 | 135.17 | 22.11 | 86.50 | 21.98 |
December | 458.67 | 21.40 | 199.17 | 21.15 | 194.17 | 20.99 |
Annual Sum or Average | 2883.00 | 22.33 | 2789.00 | 23.08 | 706.17 | 22.98 |
Minimum of Months | 53.17 | 21.40 | 71.00 | 21.15 | 15.67 | 20.99 |
Maximum of Months | 458.67 | 25.70 | 461.67 | 24.75 | 194.17 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.50 | 30.83 | 22.37 | 30.83 | 22.25 |
February | 454.00 | 22.07 | 6.50 | 22.05 | 6.50 | 22.02 |
March | 484.83 | 22.56 | 17.67 | 22.49 | 17.67 | 22.43 |
April | 274.83 | 23.68 | 11.67 | 23.73 | 0.00 | 23.73 |
May | 162.67 | 23.90 | 20.50 | 24.10 | 0.00 | 24.10 |
June | 6.50 | 24.51 | 223.83 | 24.87 | 0.83 | 24.88 |
July | 17.00 | 25.57 | 449.00 | 24.64 | 14.17 | 24.68 |
August | 8.33 | 25.74 | 468.67 | 24.48 | 7.67 | 24.50 |
September | 20.00 | 26.18 | 431.67 | 24.62 | 20.00 | 24.68 |
October | 228.33 | 23.59 | 130.17 | 23.94 | 0.00 | 23.94 |
November | 387.17 | 23.14 | 68.50 | 23.30 | 30.67 | 23.35 |
December | 497.00 | 22.27 | 50.83 | 22.13 | 50.83 | 22.02 |
Annual Sum or Average | 3042.67 | 22.81 | 1909.83 | 23.41 | 179.17 | 23.37 |
Minimum of Months | 6.50 | 22.07 | 6.50 | 22.05 | 0.00 | 22.02 |
Maximum of Months | 502.00 | 26.18 | 468.67 | 24.87 | 50.83 | 24.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 426.17 | 23.01 | 16.50 | 22.98 | 9.83 | 22.92 |
February | 390.50 | 22.49 | 13.33 | 22.54 | 2.17 | 22.53 |
March | 366.67 | 22.89 | 26.83 | 22.97 | 6.83 | 22.93 |
April | 97.00 | 23.68 | 141.83 | 24.45 | 0.33 | 24.45 |
May | 46.33 | 23.99 | 165.50 | 24.86 | 2.17 | 24.89 |
June | 23.83 | 26.97 | 381.83 | 24.79 | 22.33 | 24.91 |
July | 45.00 | 26.75 | 468.00 | 24.88 | 44.83 | 25.03 |
August | 34.17 | 26.85 | 493.50 | 24.69 | 34.17 | 24.82 |
September | 39.67 | 26.66 | 458.33 | 24.75 | 39.67 | 24.89 |
October | 125.00 | 23.68 | 205.50 | 24.35 | 2.67 | 24.37 |
November | 295.67 | 23.42 | 91.17 | 23.64 | 28.33 | 23.68 |
December | 472.67 | 22.85 | 20.50 | 22.76 | 20.50 | 22.68 |
Annual Sum or Average | 2362.67 | 23.24 | 2482.83 | 23.94 | 213.83 | 24.00 |
Minimum of Months | 23.83 | 22.49 | 13.33 | 22.54 | 0.33 | 22.53 |
Maximum of Months | 472.67 | 26.97 | 493.50 | 24.88 | 44.83 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 229.50 | 22.99 | 124.83 | 23.59 | 11.67 | 23.54 |
February | 337.00 | 22.11 | 46.50 | 22.28 | 11.00 | 22.19 |
March | 362.00 | 22.51 | 58.67 | 22.56 | 22.00 | 22.40 |
April | 162.67 | 23.30 | 91.17 | 23.97 | 0.83 | 23.96 |
May | 157.83 | 23.62 | 59.00 | 24.21 | 0.00 | 24.21 |
June | 23.67 | 24.35 | 228.00 | 25.18 | 3.50 | 25.22 |
July | 49.83 | 25.32 | 448.00 | 24.85 | 44.67 | 24.90 |
August | 48.17 | 25.74 | 481.67 | 24.81 | 46.17 | 24.89 |
September | 66.33 | 26.09 | 458.33 | 24.98 | 63.17 | 25.12 |
October | 121.33 | 23.80 | 272.00 | 24.63 | 28.33 | 24.75 |
November | 180.83 | 23.22 | 208.33 | 23.96 | 31.17 | 23.98 |
December | 299.67 | 22.58 | 92.83 | 22.95 | 23.83 | 22.80 |
Annual Sum or Average | 2038.83 | 23.08 | 2569.33 | 24.02 | 286.33 | 24.04 |
Minimum of Months | 23.67 | 22.11 | 46.50 | 22.28 | 0.00 | 22.19 |
Maximum of Months | 362.00 | 26.09 | 481.67 | 25.18 | 63.17 | 25.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 410.50 | 22.69 | 24.17 | 22.67 | 13.67 | 22.59 |
February | 415.83 | 22.14 | 5.83 | 22.16 | 1.67 | 22.15 |
March | 411.17 | 22.60 | 37.50 | 22.68 | 11.50 | 22.62 |
April | 152.67 | 23.61 | 120.00 | 24.15 | 1.83 | 24.18 |
May | 105.00 | 23.95 | 148.00 | 24.54 | 4.50 | 24.60 |
June | 15.17 | 26.10 | 317.67 | 24.78 | 9.67 | 24.85 |
July | 35.00 | 26.44 | 460.83 | 24.77 | 32.33 | 24.88 |
August | 24.33 | 26.56 | 487.00 | 24.59 | 24.33 | 24.68 |
September | 34.50 | 26.52 | 451.00 | 24.71 | 34.50 | 24.83 |
October | 157.67 | 23.65 | 192.83 | 24.20 | 6.17 | 24.25 |
November | 291.67 | 23.24 | 111.83 | 23.57 | 25.17 | 23.62 |
December | 449.67 | 22.47 | 40.50 | 22.39 | 34.83 | 22.28 |
Annual Sum or Average | 2503.17 | 22.94 | 2397.17 | 23.72 | 200.17 | 23.75 |
Minimum of Months | 15.17 | 22.14 | 5.83 | 22.16 | 1.67 | 22.15 |
Maximum of Months | 449.67 | 26.56 | 487.00 | 24.78 | 34.83 | 24.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.50 | 22.58 | 32.33 | 22.42 | 32.33 | 22.28 |
February | 437.67 | 22.27 | 7.67 | 22.24 | 7.67 | 22.21 |
March | 413.83 | 22.79 | 26.50 | 22.76 | 14.83 | 22.68 |
April | 196.33 | 23.72 | 36.17 | 23.96 | 0.00 | 23.96 |
May | 96.17 | 23.96 | 65.17 | 24.72 | 0.00 | 24.72 |
June | 7.67 | 26.92 | 271.67 | 24.92 | 7.17 | 24.98 |
July | 30.33 | 25.91 | 448.67 | 24.72 | 28.67 | 24.79 |
August | 22.83 | 25.39 | 467.83 | 24.51 | 18.50 | 24.55 |
September | 29.17 | 25.88 | 413.00 | 24.64 | 25.83 | 24.72 |
October | 265.67 | 23.37 | 117.67 | 23.72 | 1.83 | 23.73 |
November | 407.67 | 22.80 | 67.50 | 22.91 | 39.33 | 22.93 |
December | 497.00 | 21.99 | 97.17 | 21.77 | 97.17 | 21.61 |
Annual Sum or Average | 2901.83 | 22.79 | 2051.33 | 23.42 | 273.33 | 23.37 |
Minimum of Months | 7.67 | 21.99 | 7.67 | 21.77 | 0.00 | 21.61 |
Maximum of Months | 497.50 | 26.92 | 467.83 | 24.92 | 97.17 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 362.33 | 22.61 | 34.17 | 22.52 | 24.83 | 22.39 |
February | 322.33 | 22.24 | 24.17 | 22.31 | 8.33 | 22.26 |
March | 288.00 | 22.70 | 51.00 | 22.91 | 10.33 | 22.83 |
April | 96.67 | 23.75 | 126.83 | 24.55 | 5.00 | 24.62 |
May | 51.67 | 24.59 | 163.33 | 25.09 | 12.00 | 25.21 |
June | 32.00 | 27.00 | 307.50 | 25.03 | 30.33 | 25.20 |
July | 56.33 | 26.54 | 392.67 | 25.02 | 55.83 | 25.19 |
August | 41.67 | 26.41 | 407.83 | 24.77 | 39.67 | 24.91 |
September | 47.17 | 26.08 | 362.17 | 24.83 | 39.33 | 24.98 |
October | 177.83 | 23.29 | 146.50 | 24.00 | 3.67 | 24.04 |
November | 309.00 | 22.84 | 68.67 | 22.99 | 33.50 | 22.98 |
December | 413.17 | 22.22 | 62.33 | 22.01 | 62.33 | 21.84 |
Annual Sum or Average | 2198.17 | 22.99 | 2147.17 | 23.76 | 325.17 | 23.80 |
Minimum of Months | 32.00 | 22.22 | 24.17 | 22.01 | 3.67 | 21.84 |
Maximum of Months | 413.17 | 27.00 | 407.83 | 25.09 | 62.33 | 25.21 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 243.00 | 22.89 | 147.33 | 23.49 | 13.17 | 23.45 |
February | 281.83 | 22.42 | 84.50 | 22.85 | 3.17 | 22.83 |
March | 278.50 | 22.86 | 80.67 | 23.15 | 10.67 | 23.07 |
April | 138.83 | 23.66 | 128.50 | 24.25 | 0.67 | 24.25 |
May | 99.00 | 23.86 | 98.00 | 24.61 | 0.00 | 24.61 |
June | 17.67 | 25.48 | 256.67 | 24.88 | 8.33 | 24.94 |
July | 45.50 | 25.87 | 440.67 | 24.74 | 40.33 | 24.85 |
August | 32.67 | 25.89 | 476.50 | 24.57 | 27.83 | 24.65 |
September | 46.33 | 26.42 | 435.33 | 24.77 | 43.17 | 24.92 |
October | 157.00 | 23.84 | 237.33 | 24.37 | 19.83 | 24.50 |
November | 222.67 | 23.13 | 179.00 | 23.73 | 30.00 | 23.74 |
December | 309.50 | 22.64 | 108.33 | 22.92 | 40.33 | 22.77 |
Annual Sum or Average | 1872.50 | 23.23 | 2672.83 | 24.02 | 237.50 | 24.06 |
Minimum of Months | 17.67 | 22.42 | 80.67 | 22.85 | 0.00 | 22.77 |
Maximum of Months | 309.50 | 26.42 | 476.50 | 24.88 | 43.17 | 24.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 396.00 | 22.31 | 43.83 | 22.30 | 23.33 | 22.18 |
February | 393.17 | 22.04 | 24.50 | 22.09 | 9.00 | 22.05 |
March | 364.17 | 22.53 | 61.50 | 22.66 | 17.00 | 22.58 |
April | 160.67 | 23.57 | 141.67 | 24.14 | 7.50 | 24.22 |
May | 108.83 | 24.07 | 174.67 | 24.60 | 12.33 | 24.71 |
June | 29.83 | 25.94 | 318.67 | 24.83 | 19.00 | 24.94 |
July | 50.33 | 25.96 | 449.67 | 24.74 | 44.83 | 24.86 |
August | 35.33 | 25.82 | 475.83 | 24.55 | 29.50 | 24.64 |
September | 53.00 | 25.44 | 420.33 | 24.64 | 38.00 | 24.76 |
October | 231.00 | 23.21 | 170.50 | 23.79 | 9.67 | 23.86 |
November | 347.50 | 22.62 | 103.00 | 22.89 | 38.50 | 22.89 |
December | 452.17 | 21.95 | 97.83 | 21.77 | 91.17 | 21.61 |
Annual Sum or Average | 2622.00 | 22.73 | 2482.00 | 23.52 | 339.83 | 23.52 |
Minimum of Months | 29.83 | 21.95 | 24.50 | 21.77 | 7.50 | 21.61 |
Maximum of Months | 452.17 | 25.96 | 475.83 | 24.83 | 91.17 | 24.94 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.22544 | 22.23281 | 0.27995 | 6.91937 |
February | 454.00000 | 24.22719 | 33.34641 | 0.34352 | 7.65908 |
March | 514.00000 | 24.30320 | 26.02950 | 0.32960 | 7.53362 |
April | 485.00000 | 24.34706 | 18.65687 | 0.32817 | 7.47137 |
May | 508.00000 | 24.36785 | 18.05931 | -0.5109 | 10.85113 |
June | 496.00000 | 24.35236 | 25.51953 | -0.4409 | 9.46040 |
July | 497.00000 | 24.43638 | 41.64664 | -0.3071 | 7.51842 |
August | 514.00000 | 24.37378 | 44.22855 | -0.3051 | 7.40964 |
September | 485.00000 | 24.45704 | 43.37529 | -0.2904 | 7.44991 |
October | 502.00000 | 24.44622 | 26.08216 | 0.40203 | 8.86581 |
November | 489.00000 | 24.39591 | 25.99729 | 0.36665 | 8.40496 |
December | 497.00000 | 24.22140 | 15.40677 | 0.22267 | 6.20521 |
Annual Sum or Average | 5943.00000 | 24.34670 | 28.35128 | 0.03170 | 7.98493 |
Minimum of Months | 454.00000 | 24.22140 | 15.40677 | -0.5109 | 6.20521 |
Maximum of Months | 514.00000 | 24.45704 | 44.22855 | 0.40203 | 10.85113 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.60800 | 24.20251 | 0.12203 | 5.89869 |
February | 454.00000 | 23.47030 | 35.88881 | 0.15673 | 5.89359 |
March | 514.00000 | 23.83121 | 27.70205 | 0.20488 | 6.28172 |
April | 485.00000 | 24.17594 | 19.46905 | 0.27604 | 6.81398 |
May | 508.00000 | 24.26593 | 18.82433 | -0.5629 | 11.93438 |
June | 496.00000 | 24.28640 | 26.27762 | -0.4773 | 10.09981 |
July | 497.00000 | 24.35084 | 43.60914 | -0.3413 | 7.90832 |
August | 514.00000 | 24.29255 | 46.41205 | -0.3416 | 7.81379 |
September | 485.00000 | 24.37170 | 45.17711 | -0.3341 | 7.93563 |
October | 502.00000 | 24.19119 | 27.29742 | 0.32392 | 7.69822 |
November | 489.00000 | 23.91254 | 27.64679 | 0.23160 | 6.84298 |
December | 497.00000 | 23.34717 | 17.35591 | 0.00419 | 5.54781 |
Annual Sum or Average | 5943.00000 | 24.01215 | 29.95287 | -0.0640 | 7.57295 |
Minimum of Months | 454.00000 | 23.34717 | 17.35591 | -0.5629 | 5.54781 |
Maximum of Months | 514.00000 | 24.37170 | 46.41205 | 0.32392 | 11.93438 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.96190 | 23.38177 | -0.0462 | 6.50560 |
February | 454.00000 | 22.76650 | 37.35896 | -0.0132 | 5.91757 |
March | 514.00000 | 23.36007 | 28.15443 | 0.08859 | 6.11835 |
April | 485.00000 | 24.07373 | 19.63641 | 0.25611 | 6.71808 |
May | 508.00000 | 24.23779 | 18.93207 | -0.5595 | 11.91908 |
June | 496.00000 | 24.29111 | 26.22524 | -0.4514 | 9.68560 |
July | 497.00000 | 24.37919 | 43.31554 | -0.3131 | 7.61028 |
August | 514.00000 | 24.30062 | 46.18082 | -0.3245 | 7.61933 |
September | 485.00000 | 24.36265 | 45.08909 | -0.3292 | 7.88885 |
October | 502.00000 | 23.91111 | 27.57292 | 0.25204 | 7.24139 |
November | 489.00000 | 23.32318 | 28.40951 | 0.08389 | 6.56132 |
December | 497.00000 | 22.41669 | 18.03727 | -0.2226 | 7.31536 |
Annual Sum or Average | 5943.00000 | 23.70507 | 30.14474 | -0.1334 | 7.60871 |
Minimum of Months | 454.00000 | 22.41669 | 18.03727 | -0.5595 | 5.91757 |
Maximum of Months | 514.00000 | 24.37919 | 46.18082 | 0.25611 | 11.91908 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.97429 | 25.51971 | -0.2797 | 9.07043 |
February | 454.00000 | 21.69550 | 40.21972 | -0.2657 | 7.95203 |
March | 514.00000 | 22.55075 | 29.86711 | -0.0989 | 7.52096 |
April | 485.00000 | 23.90673 | 19.94268 | 0.22649 | 7.15235 |
May | 508.00000 | 24.27074 | 18.66149 | -0.5151 | 11.71019 |
June | 496.00000 | 24.48141 | 25.59539 | -0.3116 | 8.23624 |
July | 497.00000 | 24.58643 | 43.38909 | -0.1772 | 7.04267 |
August | 514.00000 | 24.40736 | 46.38518 | -0.2357 | 7.19892 |
September | 485.00000 | 24.41851 | 46.03869 | -0.2680 | 7.89307 |
October | 502.00000 | 23.43362 | 28.77357 | 0.14530 | 7.90563 |
November | 489.00000 | 22.40409 | 30.56169 | -0.1328 | 8.13382 |
December | 497.00000 | 21.33797 | 19.30832 | -0.4926 | 12.05435 |
Annual Sum or Average | 5943.00000 | 23.29986 | 31.12742 | -0.2010 | 8.49703 |
Minimum of Months | 454.00000 | 21.33797 | 18.66149 | -0.5151 | 7.04267 |
Maximum of Months | 514.00000 | 24.58643 | 46.38518 | 0.22649 | 12.05435 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.55420 | 24.34911 | -0.1160 | 7.91031 |
February | 454.00000 | 22.22836 | 38.83967 | -0.1178 | 7.45228 |
March | 514.00000 | 23.01034 | 28.68375 | 0.04137 | 7.37541 |
April | 485.00000 | 24.20708 | 19.17803 | 0.36758 | 9.20000 |
May | 508.00000 | 24.42809 | 18.28782 | -0.3604 | 9.61497 |
June | 496.00000 | 24.51705 | 25.41572 | -0.1975 | 7.57100 |
July | 497.00000 | 24.64010 | 43.09589 | -0.0692 | 6.91711 |
August | 514.00000 | 24.46537 | 45.97414 | -0.1231 | 6.91615 |
September | 485.00000 | 24.46176 | 45.63198 | -0.1781 | 7.47874 |
October | 502.00000 | 23.77067 | 27.79342 | 0.27238 | 9.14847 |
November | 489.00000 | 22.82671 | 29.63590 | -0.0037 | 7.46250 |
December | 497.00000 | 21.84380 | 18.59150 | -0.3477 | 9.92030 |
Annual Sum or Average | 5943.00000 | 23.58882 | 30.39925 | -0.0698 | 8.08327 |
Minimum of Months | 454.00000 | 21.84380 | 18.28782 | -0.3604 | 6.91615 |
Maximum of Months | 514.00000 | 24.64010 | 45.97414 | 0.36758 | 9.92030 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.24496 | 22.30858 | 0.10389 | 9.24045 |
February | 454.00000 | 22.59892 | 37.25753 | -0.0101 | 8.06977 |
March | 514.00000 | 23.09613 | 28.23327 | 0.06636 | 7.90123 |
April | 485.00000 | 24.03833 | 19.43333 | 0.30207 | 8.48862 |
May | 508.00000 | 24.24427 | 18.62321 | -0.5049 | 12.01646 |
June | 496.00000 | 24.42789 | 25.69311 | -0.3372 | 8.68071 |
July | 497.00000 | 24.56223 | 43.39238 | -0.1789 | 7.28505 |
August | 514.00000 | 24.42046 | 46.18642 | -0.1949 | 7.15748 |
September | 485.00000 | 24.47629 | 45.54566 | -0.1774 | 7.59553 |
October | 502.00000 | 23.93698 | 27.15649 | 0.34152 | 10.38487 |
November | 489.00000 | 23.36531 | 27.92055 | 0.16784 | 8.84739 |
December | 497.00000 | 22.83423 | 16.68294 | -0.0723 | 9.96386 |
Annual Sum or Average | 5943.00000 | 23.77795 | 29.82128 | -0.0426 | 8.81132 |
Minimum of Months | 454.00000 | 22.59892 | 16.68294 | -0.5049 | 7.15748 |
Maximum of Months | 514.00000 | 24.56223 | 46.18642 | 0.34152 | 12.01646 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.19609 | 24.47985 | -0.1882 | 9.16936 |
February | 454.00000 | 21.79117 | 39.49394 | -0.2156 | 8.13020 |
March | 514.00000 | 22.57420 | 29.29957 | -0.0563 | 8.00228 |
April | 485.00000 | 23.89412 | 19.76029 | 0.29089 | 8.86103 |
May | 508.00000 | 24.21202 | 18.72377 | -0.4485 | 11.97115 |
June | 496.00000 | 24.42934 | 25.71461 | -0.2495 | 8.31541 |
July | 497.00000 | 24.53791 | 43.39813 | -0.1426 | 7.46066 |
August | 514.00000 | 24.37448 | 46.33377 | -0.1847 | 7.51262 |
September | 485.00000 | 24.37620 | 45.98093 | -0.2233 | 8.05449 |
October | 502.00000 | 23.44995 | 28.33484 | 0.19615 | 8.97814 |
November | 489.00000 | 22.55012 | 29.69639 | -0.0586 | 8.47671 |
December | 497.00000 | 21.62341 | 18.39830 | -0.3991 | 11.50996 |
Annual Sum or Average | 5943.00000 | 23.34445 | 30.74268 | -0.1404 | 8.87753 |
Minimum of Months | 454.00000 | 21.62341 | 18.39830 | -0.4485 | 7.46066 |
Maximum of Months | 514.00000 | 24.53791 | 46.33377 | 0.29089 | 11.97115 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.50466 | 25.30818 | -0.1505 | 6.71992 |
February | 454.00000 | 22.06926 | 39.92192 | -0.1734 | 6.32378 |
March | 514.00000 | 22.65634 | 30.53590 | -0.0818 | 6.42781 |
April | 485.00000 | 23.92263 | 20.11767 | 0.20370 | 6.36850 |
May | 508.00000 | 24.19744 | 18.71653 | -0.5881 | 12.68779 |
June | 496.00000 | 24.42574 | 25.46579 | -0.3820 | 8.78034 |
July | 497.00000 | 24.56655 | 42.11117 | -0.2164 | 6.90430 |
August | 514.00000 | 24.42130 | 44.76756 | -0.2525 | 6.99820 |
September | 485.00000 | 24.48801 | 44.34544 | -0.2458 | 7.21125 |
October | 502.00000 | 24.00149 | 27.88302 | 0.28505 | 7.71055 |
November | 489.00000 | 23.34146 | 29.32973 | 0.09859 | 6.54813 |
December | 497.00000 | 22.27143 | 18.80402 | -0.2465 | 7.31259 |
Annual Sum or Average | 5943.00000 | 23.58111 | 30.54909 | -0.1470 | 7.51649 |
Minimum of Months | 454.00000 | 22.06926 | 18.71653 | -0.5881 | 6.32378 |
Maximum of Months | 514.00000 | 24.56655 | 44.76756 | 0.28505 | 12.68779 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.19542 | 23.84095 | 0.03873 | 6.29166 |
February | 454.00000 | 22.72329 | 38.35459 | 0.00068 | 6.21786 |
March | 514.00000 | 23.27881 | 29.04655 | 0.09362 | 6.50102 |
April | 485.00000 | 24.29100 | 19.03753 | 0.36097 | 8.43406 |
May | 508.00000 | 24.42595 | 18.09923 | -0.4091 | 9.67016 |
June | 496.00000 | 24.52240 | 25.12529 | -0.2473 | 7.53898 |
July | 497.00000 | 24.66166 | 41.66805 | -0.0944 | 6.50495 |
August | 514.00000 | 24.51870 | 44.21915 | -0.1252 | 6.46428 |
September | 485.00000 | 24.55687 | 43.88772 | -0.1462 | 6.74770 |
October | 502.00000 | 24.25823 | 26.88285 | 0.39904 | 9.53315 |
November | 489.00000 | 23.72106 | 28.20929 | 0.22093 | 7.05644 |
December | 497.00000 | 22.92108 | 17.87539 | -0.0725 | 6.41211 |
Annual Sum or Average | 5943.00000 | 23.93016 | 29.63110 | 0.00045 | 7.28865 |
Minimum of Months | 454.00000 | 22.72329 | 17.87539 | -0.4091 | 6.21786 |
Maximum of Months | 514.00000 | 24.66166 | 44.21915 | 0.39904 | 9.67016 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.77946 | 21.35489 | 0.25115 | 8.32668 |
February | 454.00000 | 22.66874 | 36.88945 | 0.03358 | 6.83915 |
March | 514.00000 | 23.04528 | 28.09936 | 0.05914 | 7.10429 |
April | 485.00000 | 24.08675 | 18.46268 | 0.28335 | 7.71743 |
May | 508.00000 | 24.22922 | 17.31511 | -0.5698 | 12.92204 |
June | 496.00000 | 24.60751 | 24.18470 | -0.3562 | 8.90544 |
July | 497.00000 | 24.73784 | 41.80496 | -0.1661 | 6.86021 |
August | 514.00000 | 24.67249 | 44.11548 | -0.1451 | 6.68510 |
September | 485.00000 | 24.76317 | 43.36214 | -0.0919 | 6.88541 |
October | 502.00000 | 24.39609 | 25.76324 | 0.46510 | 11.54580 |
November | 489.00000 | 23.97066 | 26.81310 | 0.34615 | 9.06284 |
December | 497.00000 | 23.38483 | 15.68466 | 0.10998 | 8.24383 |
Annual Sum or Average | 5943.00000 | 24.03622 | 28.60175 | 0.01662 | 8.44204 |
Minimum of Months | 454.00000 | 22.66874 | 15.68466 | -0.5698 | 6.68510 |
Maximum of Months | 514.00000 | 24.76317 | 44.11548 | 0.46510 | 12.92204 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.97214 | 23.95792 | -0.0062 | 6.51888 |
February | 454.00000 | 22.31080 | 39.07530 | -0.0929 | 6.23874 |
March | 514.00000 | 22.93197 | 29.62772 | 0.01291 | 6.52614 |
April | 485.00000 | 24.14813 | 19.48393 | 0.31948 | 8.04308 |
May | 508.00000 | 24.31629 | 18.43436 | -0.4650 | 10.84789 |
June | 496.00000 | 24.47915 | 25.34842 | -0.2833 | 7.91828 |
July | 497.00000 | 24.60819 | 41.94974 | -0.1520 | 6.81729 |
August | 514.00000 | 24.47290 | 44.52582 | -0.1731 | 6.71959 |
September | 485.00000 | 24.53655 | 44.09923 | -0.1726 | 6.87495 |
October | 502.00000 | 24.15765 | 27.28490 | 0.36581 | 9.02876 |
November | 489.00000 | 23.63279 | 28.30063 | 0.20505 | 7.29616 |
December | 497.00000 | 22.64313 | 17.83452 | -0.1335 | 6.96858 |
Annual Sum or Average | 5943.00000 | 23.77606 | 29.93540 | -0.0490 | 7.49427 |
Minimum of Months | 454.00000 | 22.31080 | 17.83452 | -0.4650 | 6.23874 |
Maximum of Months | 514.00000 | 24.60819 | 44.52582 | 0.36581 | 10.84789 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.59638 | 25.28575 | -0.1231 | 6.97937 |
February | 454.00000 | 22.33518 | 39.21338 | -0.1058 | 6.25593 |
March | 514.00000 | 23.04352 | 29.57992 | 0.02229 | 6.47227 |
April | 485.00000 | 24.08053 | 19.73304 | 0.25958 | 6.90768 |
May | 508.00000 | 24.33673 | 18.48938 | -0.5101 | 11.11422 |
June | 496.00000 | 24.50402 | 25.52588 | -0.3333 | 8.36924 |
July | 497.00000 | 24.59475 | 43.52344 | -0.1984 | 6.97136 |
August | 514.00000 | 24.42574 | 46.44974 | -0.2484 | 7.11110 |
September | 485.00000 | 24.46378 | 45.88752 | -0.2662 | 7.59245 |
October | 502.00000 | 23.80392 | 28.48866 | 0.23310 | 7.54231 |
November | 489.00000 | 23.01566 | 30.00255 | 0.01972 | 6.82707 |
December | 497.00000 | 21.99108 | 19.16021 | -0.3163 | 8.52094 |
Annual Sum or Average | 5943.00000 | 23.60780 | 30.89034 | -0.1317 | 7.56853 |
Minimum of Months | 454.00000 | 21.99108 | 18.48938 | -0.5101 | 6.25593 |
Maximum of Months | 514.00000 | 24.59475 | 46.44974 | 0.25958 | 11.11422 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.85865 | 23.96912 | -0.0364 | 6.89168 |
February | 385.00000 | 22.56706 | 37.96494 | -0.0292 | 6.61505 |
March | 433.00000 | 23.24767 | 28.22391 | 0.09603 | 6.93507 |
April | 410.00000 | 24.33862 | 18.65303 | 0.36995 | 8.93416 |
May | 430.00000 | 24.53351 | 17.68398 | -0.3733 | 9.68626 |
June | 418.00000 | 24.62934 | 24.83005 | -0.2230 | 7.88534 |
July | 422.00000 | 24.75333 | 42.51441 | -0.0902 | 6.95962 |
August | 433.00000 | 24.56480 | 45.22360 | -0.1465 | 7.02293 |
September | 410.00000 | 24.57791 | 44.99361 | -0.1848 | 7.46914 |
October | 427.00000 | 23.99446 | 27.17877 | 0.31171 | 8.99520 |
November | 417.00000 | 23.18830 | 29.02081 | 0.08615 | 6.86841 |
December | 422.00000 | 22.27171 | 17.75709 | -0.2322 | 7.94161 |
Annual Sum or Average | 5034.00000 | 23.80050 | 29.77232 | -0.0384 | 7.69036 |
Minimum of Months | 385.00000 | 22.27171 | 17.68398 | -0.3733 | 6.61505 |
Maximum of Months | 433.00000 | 24.75333 | 45.22360 | 0.36995 | 9.68626 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.66560 | 22.01706 | 0.21411 | 8.52327 |
February | 454.00000 | 23.10871 | 36.14915 | 0.11911 | 7.28030 |
March | 514.00000 | 23.49275 | 27.87588 | 0.16553 | 7.29890 |
April | 485.00000 | 24.21169 | 19.19865 | 0.33208 | 8.18822 |
May | 508.00000 | 24.33299 | 18.41973 | -0.4949 | 11.13096 |
June | 496.00000 | 24.46224 | 25.60715 | -0.3552 | 8.69687 |
July | 497.00000 | 24.58081 | 43.50345 | -0.1977 | 7.12150 |
August | 514.00000 | 24.44709 | 46.21993 | -0.2075 | 6.96193 |
September | 485.00000 | 24.52714 | 45.34586 | -0.1781 | 7.21953 |
October | 502.00000 | 24.19650 | 26.87577 | 0.40297 | 10.26663 |
November | 489.00000 | 23.79027 | 27.38973 | 0.27806 | 8.60967 |
December | 497.00000 | 23.33517 | 16.29226 | 0.06618 | 8.40018 |
Annual Sum or Average | 5943.00000 | 24.01811 | 29.53318 | 0.01008 | 8.31788 |
Minimum of Months | 454.00000 | 23.10871 | 16.29226 | -0.4949 | 6.96193 |
Maximum of Months | 514.00000 | 24.58081 | 46.21993 | 0.40297 | 11.13096 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.71843 | 24.21953 | -0.0537 | 7.36906 |
February | 454.00000 | 22.31620 | 38.52823 | -0.0795 | 6.61499 |
March | 514.00000 | 23.02255 | 29.00714 | 0.05464 | 7.00443 |
April | 485.00000 | 24.10158 | 19.53189 | 0.32814 | 8.50121 |
May | 508.00000 | 24.31558 | 18.51134 | -0.4357 | 10.80221 |
June | 496.00000 | 24.47719 | 25.59654 | -0.2658 | 8.07448 |
July | 497.00000 | 24.56513 | 43.50431 | -0.1594 | 7.15355 |
August | 514.00000 | 24.41589 | 46.35207 | -0.1932 | 7.15170 |
September | 485.00000 | 24.44495 | 45.78110 | -0.2176 | 7.50959 |
October | 502.00000 | 23.80032 | 28.04447 | 0.27786 | 8.59093 |
November | 489.00000 | 23.08113 | 29.16438 | 0.07600 | 7.41625 |
December | 497.00000 | 22.15828 | 18.14634 | -0.2484 | 8.54994 |
Annual Sum or Average | 5943.00000 | 23.62672 | 30.47975 | -0.0774 | 7.90514 |
Minimum of Months | 454.00000 | 22.15828 | 18.14634 | -0.4357 | 6.61499 |
Maximum of Months | 514.00000 | 24.56513 | 46.35207 | 0.32814 | 10.80221 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.177383E+11 | 0.447686E+10 | 276.64 | 0.176159E+11 | 0.122393E+09 | 0.00 | 1.00 | 17-JAN-14:30 | 0.00 | 01-JAN-00:10 | 49562.02 | 31-JAN-17:00 | 49562.02 | 31-JAN-17:00 | 3496.15 | 08-JAN-12:10 | 12913.40 | 31-JAN-17:00 | 0.00 |
February | 0.400265E+10 | 0.109417E+10 | 150.00 | 0.351487E+10 | 0.487783E+09 | 0.00 | 0.63 | 22-FEB-16:10 | 0.00 | 01-FEB-00:10 | 22173.99 | 22-FEB-16:10 | 22173.99 | 22-FEB-16:10 | 4342.60 | 17-FEB-12:00 | 5612.84 | 22-FEB-16:10 | 0.00 |
March | 0.171784E+11 | 0.442254E+10 | 293.46 | 0.167789E+11 | 0.399550E+09 | 0.00 | 1.00 | 15-MAR-14:30 | 0.00 | 01-MAR-00:10 | 47755.48 | 16-MAR-15:50 | 47755.48 | 16-MAR-15:50 | 2686.97 | 06-MAR-16:10 | 12375.29 | 16-MAR-15:50 | 0.00 |
April | 0.478301E+11 | 0.128639E+11 | 414.77 | 0.477370E+11 | 93065764.07 | 0.00 | 1.00 | 03-APR-09:30 | 0.00 | 01-APR-00:10 | 67152.00 | 14-APR-16:00 | 67152.00 | 14-APR-16:00 | 2554.32 | 16-APR-09:58 | 20847.75 | 14-APR-16:00 | 0.00 |
May | 0.637072E+11 | 0.178958E+11 | 470.71 | 0.636495E+11 | 57717098.81 | 0.00 | 1.00 | 01-MAY-09:50 | 0.00 | 01-MAY-00:10 | 70671.76 | 31-MAY-16:00 | 70671.76 | 31-MAY-16:00 | 2570.41 | 26-MAY-05:00 | 23335.75 | 31-MAY-16:00 | 0.00 |
June | 0.851688E+11 | 0.267361E+11 | 496.77 | 0.849049E+11 | 0.263851E+09 | 0.00 | 1.00 | 01-JUN-04:03 | 0.00 | 01-JUN-00:10 | 91190.75 | 29-JUN-06:03 | 91190.75 | 29-JUN-06:03 | 6073.34 | 30-JUN-11:03 | 31302.72 | 28-JUN-16:00 | 0.00 |
July | 0.881133E+11 | 0.260060E+11 | 503.95 | 0.814802E+11 | 0.663311E+10 | 0.00 | 1.00 | 01-JUL-08:40 | 0.00 | 01-JUL-00:10 | 130845.48 | 14-JUL-04:03 | 93041.23 | 17-JUL-06:03 | 79491.92 | 14-JUL-04:03 | 29800.75 | 19-JUL-13:00 | 0.00 |
August | 0.917145E+11 | 0.269038E+11 | 505.29 | 0.843370E+11 | 0.737750E+10 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:03 | 126589.18 | 01-AUG-04:02 | 93868.39 | 14-AUG-06:03 | 60511.77 | 01-AUG-04:02 | 29499.26 | 25-AUG-16:00 | 0.00 |
September | 0.797566E+11 | 0.222256E+11 | 468.12 | 0.722171E+11 | 0.753950E+10 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 122768.53 | 08-SEP-04:02 | 89461.23 | 18-SEP-06:03 | 72074.96 | 05-SEP-06:03 | 29151.49 | 08-SEP-04:02 | 0.00 |
October | 0.448220E+11 | 0.119374E+11 | 388.89 | 0.433837E+11 | 0.143828E+10 | 0.00 | 1.00 | 01-OCT-11:13 | 0.00 | 01-OCT-00:10 | 122767.58 | 03-OCT-04:02 | 88446.91 | 02-OCT-04:02 | 61257.34 | 03-OCT-04:02 | 28132.95 | 03-OCT-04:02 | 0.00 |
November | 0.202486E+11 | 0.505213E+10 | 283.52 | 0.189869E+11 | 0.126163E+10 | 0.00 | 1.00 | 01-NOV-10:20 | 0.00 | 01-NOV-00:10 | 57496.83 | 13-NOV-05:03 | 56630.54 | 01-NOV-16:00 | 37426.40 | 13-NOV-05:03 | 14489.22 | 01-NOV-15:10 | 0.00 |
December | 0.844509E+10 | 0.218741E+10 | 189.28 | 0.842122E+10 | 23867733.48 | 0.00 | 1.00 | 21-DEC-16:10 | 0.00 | 01-DEC-00:10 | 43685.50 | 22-DEC-16:30 | 43685.50 | 22-DEC-16:30 | 1009.27 | 03-DEC-13:55 | 10178.30 | 22-DEC-16:20 | 0.00 |
Annual Sum or Average | 0.568725E+12 | 0.161802E+12 | 4441.40 | 0.543027E+12 | 0.256982E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.400265E+10 | 0.109417E+10 | 150.00 | 0.351487E+10 | 23867733.48 | 0.00 | 0.63 | 0.00 | 22173.99 | 22173.99 | 1009.27 | 5612.84 | 0.00 | ||||||
Maximum of Months | 0.917145E+11 | 0.269038E+11 | 505.29 | 0.849049E+11 | 0.753950E+10 | 0.00 | 1.00 | 0.00 | 130845.48 | 93868.39 | 79491.92 | 31302.72 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.144263E+11 | 0.369727E+10 | 274.22 | 0.143006E+11 | 0.125672E+09 | 0.00 | 1.00 | 19-JAN-15:50 | 0.00 | 01-JAN-00:10 | 41152.67 | 31-JAN-16:30 | 41152.67 | 31-JAN-16:30 | 1779.82 | 22-JAN-16:05 | 10724.32 | 31-JAN-16:30 | 0.00 |
February | 0.330843E+10 | 0.910167E+09 | 149.67 | 0.281832E+10 | 0.490101E+09 | 0.00 | 0.64 | 22-FEB-16:00 | 0.00 | 01-FEB-00:10 | 20338.91 | 22-FEB-16:00 | 20338.91 | 22-FEB-16:00 | 3775.46 | 18-FEB-11:20 | 5143.43 | 22-FEB-16:00 | 0.00 |
March | 0.145137E+11 | 0.377270E+10 | 294.56 | 0.140519E+11 | 0.461832E+09 | 0.00 | 1.00 | 15-MAR-16:00 | 0.00 | 01-MAR-00:10 | 44085.51 | 16-MAR-15:40 | 44085.51 | 16-MAR-15:40 | 2524.63 | 18-MAR-09:20 | 11423.96 | 16-MAR-15:40 | 0.00 |
April | 0.429082E+11 | 0.115726E+11 | 413.65 | 0.428404E+11 | 67707696.27 | 0.00 | 1.00 | 02-APR-15:51 | 0.00 | 01-APR-00:10 | 62859.15 | 14-APR-15:30 | 62859.15 | 14-APR-15:30 | 2134.10 | 16-APR-09:43 | 19513.45 | 14-APR-15:30 | 0.00 |
May | 0.576942E+11 | 0.162282E+11 | 470.25 | 0.576602E+11 | 33950382.23 | 0.00 | 1.00 | 01-MAY-09:50 | 0.00 | 01-MAY-00:10 | 64083.73 | 18-MAY-15:30 | 64083.73 | 18-MAY-15:30 | 2025.15 | 26-MAY-04:30 | 20900.25 | 31-MAY-16:00 | 0.00 |
June | 0.783582E+11 | 0.246310E+11 | 497.62 | 0.782120E+11 | 0.146196E+09 | 0.00 | 1.00 | 01-JUN-05:03 | 0.00 | 01-JUN-00:10 | 78972.14 | 29-JUN-04:02 | 78972.14 | 29-JUN-04:02 | 4707.99 | 17-JUN-17:10 | 29749.38 | 28-JUN-15:00 | 0.00 |
July | 0.768277E+11 | 0.226532E+11 | 496.59 | 0.718371E+11 | 0.499061E+10 | 0.00 | 1.00 | 01-JUL-08:40 | 0.00 | 01-JUL-00:10 | 118842.49 | 14-JUL-05:03 | 82324.95 | 10-JUL-04:02 | 71092.80 | 14-JUL-05:03 | 26730.45 | 14-JUL-05:03 | 0.00 |
August | 0.775518E+11 | 0.227622E+11 | 492.13 | 0.723525E+11 | 0.519927E+10 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:03 | 115356.37 | 01-AUG-04:02 | 81146.32 | 28-AUG-06:03 | 55617.99 | 01-AUG-04:02 | 27464.78 | 25-AUG-15:20 | 0.00 |
September | 0.648494E+11 | 0.181534E+11 | 445.02 | 0.595335E+11 | 0.531587E+10 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 111874.74 | 08-SEP-04:02 | 74589.72 | 18-SEP-04:02 | 66131.55 | 05-SEP-06:03 | 26564.75 | 08-SEP-04:02 | 0.00 |
October | 0.358126E+11 | 0.964928E+10 | 377.46 | 0.346797E+11 | 0.113291E+10 | 0.00 | 1.00 | 01-OCT-12:42 | 0.00 | 01-OCT-00:10 | 81542.86 | 03-OCT-04:02 | 79046.48 | 02-OCT-04:02 | 40777.30 | 03-OCT-04:02 | 21637.25 | 02-OCT-14:00 | 0.00 |
November | 0.151489E+11 | 0.386351E+10 | 276.72 | 0.141440E+11 | 0.100498E+10 | 0.00 | 1.00 | 01-NOV-10:50 | 0.00 | 01-NOV-00:10 | 48648.28 | 01-NOV-15:30 | 48648.28 | 01-NOV-15:30 | 18340.16 | 13-NOV-15:30 | 12558.22 | 01-NOV-15:00 | 0.00 |
December | 0.659325E+10 | 0.173914E+10 | 185.83 | 0.655207E+10 | 41180304.66 | 0.00 | 0.99 | 22-DEC-16:30 | 0.00 | 01-DEC-00:10 | 34659.58 | 22-DEC-16:30 | 34659.58 | 22-DEC-16:30 | 1763.08 | 12-DEC-15:00 | 8075.16 | 22-DEC-16:30 | 0.00 |
Annual Sum or Average | 0.487993E+12 | 0.139633E+12 | 4373.72 | 0.468982E+12 | 0.190103E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.330843E+10 | 0.910167E+09 | 149.67 | 0.281832E+10 | 33950382.23 | 0.00 | 0.64 | 0.00 | 20338.91 | 20338.91 | 1763.08 | 5143.43 | 0.00 | ||||||
Maximum of Months | 0.783582E+11 | 0.246310E+11 | 497.62 | 0.782120E+11 | 0.531587E+10 | 0.00 | 1.00 | 0.00 | 118842.49 | 82324.95 | 71092.80 | 29749.38 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.143313E+11 | 0.373632E+10 | 272.54 | 0.141370E+11 | 0.194353E+09 | 0.00 | 1.00 | 27-JAN-14:40 | 0.00 | 01-JAN-00:10 | 44814.84 | 31-JAN-16:20 | 44814.84 | 31-JAN-16:20 | 2111.09 | 22-JAN-15:53 | 11679.84 | 31-JAN-16:20 | 0.00 |
February | 0.339257E+10 | 0.940543E+09 | 148.33 | 0.280170E+10 | 0.590865E+09 | 0.00 | 0.57 | 22-FEB-16:00 | 0.00 | 01-FEB-00:10 | 20344.53 | 22-FEB-16:00 | 20344.53 | 22-FEB-16:00 | 4350.60 | 18-FEB-14:00 | 5244.26 | 22-FEB-16:00 | 0.00 |
March | 0.152250E+11 | 0.399735E+10 | 294.75 | 0.145549E+11 | 0.670062E+09 | 0.00 | 1.00 | 16-MAR-12:50 | 0.00 | 01-MAR-00:10 | 50961.24 | 16-MAR-15:40 | 50961.24 | 16-MAR-15:40 | 3617.21 | 17-MAR-10:00 | 13205.53 | 16-MAR-15:40 | 0.00 |
April | 0.474929E+11 | 0.129334E+11 | 412.37 | 0.473776E+11 | 0.115322E+09 | 0.00 | 1.00 | 02-APR-16:02 | 0.00 | 01-APR-00:10 | 75028.93 | 30-APR-15:52 | 75028.93 | 30-APR-15:52 | 2599.77 | 16-APR-09:55 | 23078.60 | 14-APR-15:40 | 0.00 |
May | 0.639836E+11 | 0.181786E+11 | 463.48 | 0.639363E+11 | 47267955.32 | 0.00 | 1.00 | 01-MAY-10:50 | 0.00 | 01-MAY-00:10 | 78314.27 | 07-MAY-16:12 | 78314.27 | 07-MAY-16:12 | 2403.73 | 26-MAY-05:05 | 25064.66 | 07-MAY-16:12 | 0.00 |
June | 0.883743E+11 | 0.280247E+11 | 504.45 | 0.881763E+11 | 0.197917E+09 | 0.00 | 1.00 | 01-JUN-08:00 | 0.00 | 01-JUN-00:10 | 92359.85 | 28-JUN-15:00 | 92359.85 | 28-JUN-15:00 | 4842.56 | 17-JUN-17:08 | 35662.87 | 28-JUN-15:00 | 0.00 |
July | 0.855023E+11 | 0.253753E+11 | 503.74 | 0.803215E+11 | 0.518084E+10 | 0.00 | 1.00 | 01-JUL-09:30 | 0.00 | 01-JUL-00:10 | 127130.88 | 24-JUL-04:02 | 91103.99 | 10-JUL-04:02 | 76190.68 | 14-JUL-05:03 | 30913.96 | 19-JUL-13:40 | 0.00 |
August | 0.851901E+11 | 0.252016E+11 | 494.21 | 0.797988E+11 | 0.539137E+10 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:23 | 132574.67 | 01-AUG-04:02 | 90915.89 | 13-AUG-16:11 | 64837.12 | 01-AUG-04:02 | 32859.93 | 27-AUG-16:01 | 0.00 |
September | 0.697415E+11 | 0.196899E+11 | 443.51 | 0.643261E+11 | 0.541539E+10 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 107543.24 | 08-SEP-05:03 | 84386.64 | 08-SEP-16:00 | 57984.99 | 05-SEP-06:03 | 28302.97 | 08-SEP-16:00 | 0.00 |
October | 0.373236E+11 | 0.101855E+11 | 373.35 | 0.360618E+11 | 0.126178E+10 | 0.00 | 1.00 | 01-OCT-12:13 | 0.00 | 01-OCT-00:10 | 88168.41 | 02-OCT-04:02 | 88168.41 | 02-OCT-04:02 | 29327.05 | 03-OCT-04:02 | 24352.46 | 02-OCT-13:40 | 0.00 |
November | 0.148877E+11 | 0.386331E+10 | 274.18 | 0.138198E+11 | 0.106795E+10 | 0.00 | 1.00 | 01-NOV-12:10 | 0.00 | 01-NOV-00:10 | 55351.06 | 01-NOV-15:30 | 55351.06 | 01-NOV-15:30 | 15052.88 | 13-NOV-15:40 | 14239.68 | 01-NOV-15:20 | 0.00 |
December | 0.643520E+10 | 0.172378E+10 | 182.15 | 0.637399E+10 | 61207606.41 | 0.00 | 0.92 | 22-DEC-15:40 | 0.00 | 01-DEC-00:10 | 36426.24 | 22-DEC-15:40 | 36426.24 | 22-DEC-15:40 | 2122.08 | 12-DEC-15:00 | 8838.28 | 22-DEC-15:30 | 0.00 |
Annual Sum or Average | 0.531880E+12 | 0.153850E+12 | 4367.08 | 0.511686E+12 | 0.201943E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.339257E+10 | 0.940543E+09 | 148.33 | 0.280170E+10 | 47267955.32 | 0.00 | 0.57 | 0.00 | 20344.53 | 20344.53 | 2111.09 | 5244.26 | 0.00 | ||||||
Maximum of Months | 0.883743E+11 | 0.280247E+11 | 504.45 | 0.881763E+11 | 0.541539E+10 | 0.00 | 1.00 | 0.00 | 132574.67 | 92359.85 | 76190.68 | 35662.87 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 258.53 | 0.00 | 258.53 | 224.50 | 1025.75 | 0.00 | 0.00 | 0.00 |
February | 294.58 | 0.00 | 294.58 | 154.88 | 1004.93 | 0.00 | 0.00 | 0.00 |
March | 391.50 | 0.00 | 391.50 | 380.87 | 909.39 | 0.00 | 0.00 | 0.00 |
April | 476.99 | 4.95 | 472.04 | 800.52 | 515.81 | 0.00 | 0.00 | 0.00 |
May | 558.36 | 44.71 | 513.65 | 1096.54 | 354.57 | 0.00 | 0.00 | 0.00 |
June | 648.85 | 117.89 | 530.96 | 1713.75 | 153.70 | 0.00 | 0.00 | 0.00 |
July | 553.35 | 57.65 | 495.70 | 1459.13 | 118.56 | 0.00 | 0.00 | 0.00 |
August | 446.65 | 11.10 | 435.56 | 1212.03 | 148.00 | 0.00 | 0.00 | 0.00 |
September | 421.41 | 0.11 | 421.30 | 1007.65 | 221.15 | 0.00 | 0.00 | 0.00 |
October | 326.03 | 0.00 | 326.03 | 491.06 | 665.03 | 0.00 | 0.00 | 0.00 |
November | 271.65 | 0.00 | 271.65 | 220.36 | 951.95 | 0.00 | 0.00 | 0.00 |
December | 241.49 | 0.00 | 241.49 | 142.82 | 1244.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 407.86 | 19.74 | 388.12 | 744.71 | 607.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 241.49 | 0.00 | 241.49 | 142.82 | 118.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 648.85 | 117.89 | 530.96 | 1713.75 | 1244.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 556.77 | 349.28 | 207.49 | 730.43 | 638.94 | 0.00 | 0.00 | 0.00 |
February | 548.81 | 313.94 | 234.86 | 632.54 | 633.62 | 0.00 | 0.00 | 0.00 |
March | 686.81 | 353.30 | 333.51 | 905.40 | 570.11 | 0.00 | 0.00 | 0.00 |
April | 980.38 | 584.32 | 396.06 | 1626.90 | 328.69 | 0.00 | 0.00 | 0.00 |
May | 1016.03 | 602.29 | 413.74 | 1803.94 | 235.71 | 0.00 | 0.00 | 0.00 |
June | 1059.03 | 658.06 | 400.96 | 2173.72 | 98.24 | 0.00 | 0.00 | 0.00 |
July | 894.42 | 504.32 | 390.09 | 1854.18 | 75.69 | 0.00 | 0.00 | 0.00 |
August | 848.88 | 484.45 | 364.43 | 1748.68 | 94.81 | 0.00 | 0.00 | 0.00 |
September | 696.56 | 335.75 | 360.81 | 1377.98 | 138.90 | 0.00 | 0.00 | 0.00 |
October | 699.66 | 425.80 | 273.85 | 1106.69 | 415.38 | 0.00 | 0.00 | 0.00 |
November | 538.00 | 322.97 | 215.03 | 696.15 | 598.48 | 0.00 | 0.00 | 0.00 |
December | 490.51 | 296.18 | 194.33 | 574.08 | 770.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 752.25 | 436.46 | 315.79 | 1272.27 | 382.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 490.51 | 296.18 | 194.33 | 574.08 | 75.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1059.03 | 658.06 | 413.74 | 2173.72 | 770.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2128.69 | 1700.12 | 428.57 | 3260.45 | 1020.99 | 0.00 | 0.00 | 0.00 |
February | 1345.94 | 907.75 | 438.19 | 1846.12 | 975.63 | 0.00 | 0.00 | 0.00 |
March | 1119.92 | 576.82 | 543.10 | 1655.72 | 913.44 | 0.00 | 0.00 | 0.00 |
April | 953.35 | 385.24 | 568.10 | 1810.93 | 541.29 | 0.00 | 0.00 | 0.00 |
May | 638.84 | 105.54 | 533.30 | 1345.61 | 385.05 | 0.00 | 0.00 | 0.00 |
June | 547.04 | 42.17 | 504.87 | 1547.93 | 158.86 | 0.00 | 0.00 | 0.00 |
July | 558.97 | 57.83 | 501.14 | 1504.61 | 119.44 | 0.00 | 0.00 | 0.00 |
August | 679.68 | 187.83 | 491.85 | 1737.37 | 148.53 | 0.00 | 0.00 | 0.00 |
September | 979.36 | 417.82 | 561.54 | 2087.56 | 222.92 | 0.00 | 0.00 | 0.00 |
October | 1560.51 | 1080.10 | 480.40 | 2627.54 | 658.32 | 0.00 | 0.00 | 0.00 |
November | 1818.58 | 1392.93 | 425.64 | 2745.37 | 939.02 | 0.00 | 0.00 | 0.00 |
December | 1979.04 | 1566.68 | 412.37 | 2893.11 | 1208.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1192.52 | 701.60 | 490.92 | 2090.96 | 606.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 547.04 | 42.17 | 412.37 | 1345.61 | 119.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2128.69 | 1700.12 | 568.10 | 3260.45 | 1208.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 582.21 | 361.85 | 220.36 | 860.74 | 700.27 | 0.00 | 0.00 | 0.00 |
February | 471.64 | 228.01 | 243.63 | 559.69 | 666.29 | 0.00 | 0.00 | 0.00 |
March | 624.71 | 297.81 | 326.90 | 856.48 | 604.36 | 0.00 | 0.00 | 0.00 |
April | 959.26 | 547.19 | 412.07 | 1643.69 | 368.23 | 0.00 | 0.00 | 0.00 |
May | 961.72 | 539.24 | 422.48 | 1758.71 | 269.36 | 0.00 | 0.00 | 0.00 |
June | 1022.40 | 601.34 | 421.07 | 2134.46 | 117.19 | 0.00 | 0.00 | 0.00 |
July | 744.13 | 347.36 | 396.77 | 1608.22 | 86.60 | 0.00 | 0.00 | 0.00 |
August | 709.59 | 356.37 | 353.22 | 1525.99 | 105.93 | 0.00 | 0.00 | 0.00 |
September | 618.53 | 259.88 | 358.65 | 1262.50 | 152.07 | 0.00 | 0.00 | 0.00 |
October | 632.88 | 361.88 | 271.00 | 1044.64 | 450.75 | 0.00 | 0.00 | 0.00 |
November | 582.90 | 351.94 | 230.96 | 834.05 | 644.89 | 0.00 | 0.00 | 0.00 |
December | 469.79 | 267.49 | 202.31 | 624.01 | 835.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 699.11 | 377.22 | 321.89 | 1228.92 | 415.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 469.79 | 228.01 | 202.31 | 559.69 | 86.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1022.40 | 601.34 | 422.48 | 2134.46 | 835.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.17 | 0.00 | 86.17 | 70.53 | 370.00 | 0.00 | 0.00 | 0.00 |
February | 98.19 | 0.00 | 98.19 | 51.44 | 357.14 | 0.00 | 0.00 | 0.00 |
March | 130.49 | 0.00 | 130.49 | 131.06 | 310.65 | 0.00 | 0.00 | 0.00 |
April | 158.99 | 1.65 | 157.34 | 273.78 | 171.34 | 0.00 | 0.00 | 0.00 |
May | 186.11 | 14.90 | 171.21 | 374.00 | 113.91 | 0.00 | 0.00 | 0.00 |
June | 216.27 | 39.29 | 176.98 | 579.07 | 48.18 | 0.00 | 0.00 | 0.00 |
July | 184.44 | 19.22 | 165.23 | 490.29 | 39.17 | 0.00 | 0.00 | 0.00 |
August | 148.88 | 3.70 | 145.18 | 404.61 | 51.35 | 0.00 | 0.00 | 0.00 |
September | 140.46 | 0.04 | 140.43 | 333.70 | 79.68 | 0.00 | 0.00 | 0.00 |
October | 108.67 | 0.00 | 108.67 | 157.39 | 249.06 | 0.00 | 0.00 | 0.00 |
November | 90.54 | 0.00 | 90.54 | 64.61 | 362.95 | 0.00 | 0.00 | 0.00 |
December | 80.49 | 0.00 | 80.49 | 38.38 | 466.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 135.95 | 6.58 | 129.37 | 248.30 | 217.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.49 | 0.00 | 80.49 | 38.38 | 39.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 216.27 | 39.29 | 176.98 | 579.07 | 466.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.18 | 0.00 | 86.18 | 70.53 | 370.03 | 0.00 | 0.00 | 0.00 |
February | 98.20 | 0.00 | 98.20 | 51.45 | 357.16 | 0.00 | 0.00 | 0.00 |
March | 130.50 | 0.00 | 130.50 | 131.07 | 310.67 | 0.00 | 0.00 | 0.00 |
April | 159.00 | 1.65 | 157.35 | 273.80 | 171.35 | 0.00 | 0.00 | 0.00 |
May | 186.12 | 14.90 | 171.22 | 374.02 | 113.91 | 0.00 | 0.00 | 0.00 |
June | 216.29 | 39.30 | 176.99 | 579.11 | 48.18 | 0.00 | 0.00 | 0.00 |
July | 184.45 | 19.22 | 165.24 | 490.32 | 39.17 | 0.00 | 0.00 | 0.00 |
August | 148.89 | 3.70 | 145.19 | 404.64 | 51.35 | 0.00 | 0.00 | 0.00 |
September | 140.47 | 0.04 | 140.43 | 333.72 | 79.69 | 0.00 | 0.00 | 0.00 |
October | 108.68 | 0.00 | 108.68 | 157.40 | 249.07 | 0.00 | 0.00 | 0.00 |
November | 90.55 | 0.00 | 90.55 | 64.62 | 362.97 | 0.00 | 0.00 | 0.00 |
December | 80.50 | 0.00 | 80.50 | 38.39 | 466.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 135.96 | 6.58 | 129.37 | 248.32 | 217.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.50 | 0.00 | 80.50 | 38.39 | 39.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 216.29 | 39.30 | 176.99 | 579.11 | 466.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.18 | 0.00 | 86.18 | 70.53 | 370.03 | 0.00 | 0.00 | 0.00 |
February | 98.20 | 0.00 | 98.20 | 51.45 | 357.16 | 0.00 | 0.00 | 0.00 |
March | 130.50 | 0.00 | 130.50 | 131.07 | 310.67 | 0.00 | 0.00 | 0.00 |
April | 159.00 | 1.65 | 157.35 | 273.80 | 171.35 | 0.00 | 0.00 | 0.00 |
May | 186.12 | 14.90 | 171.22 | 374.02 | 113.91 | 0.00 | 0.00 | 0.00 |
June | 216.29 | 39.30 | 176.99 | 579.11 | 48.18 | 0.00 | 0.00 | 0.00 |
July | 184.45 | 19.22 | 165.24 | 490.32 | 39.17 | 0.00 | 0.00 | 0.00 |
August | 148.89 | 3.70 | 145.19 | 404.64 | 51.35 | 0.00 | 0.00 | 0.00 |
September | 140.47 | 0.04 | 140.43 | 333.72 | 79.69 | 0.00 | 0.00 | 0.00 |
October | 108.68 | 0.00 | 108.68 | 157.40 | 249.07 | 0.00 | 0.00 | 0.00 |
November | 90.55 | 0.00 | 90.55 | 64.62 | 362.97 | 0.00 | 0.00 | 0.00 |
December | 80.50 | 0.00 | 80.50 | 38.39 | 466.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 135.96 | 6.58 | 129.37 | 248.32 | 217.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.50 | 0.00 | 80.50 | 38.39 | 39.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 216.29 | 39.30 | 176.99 | 579.11 | 466.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 535.59 | 335.99 | 199.60 | 689.90 | 678.29 | 0.00 | 0.00 | 0.00 |
February | 527.93 | 302.00 | 225.93 | 607.01 | 662.31 | 0.00 | 0.00 | 0.00 |
March | 660.68 | 339.86 | 320.82 | 877.35 | 575.58 | 0.00 | 0.00 | 0.00 |
April | 943.08 | 562.09 | 381.00 | 1580.46 | 326.77 | 0.00 | 0.00 | 0.00 |
May | 977.37 | 579.38 | 398.00 | 1754.25 | 229.33 | 0.00 | 0.00 | 0.00 |
June | 1018.74 | 633.03 | 385.71 | 2107.87 | 95.57 | 0.00 | 0.00 | 0.00 |
July | 860.39 | 485.14 | 375.25 | 1791.81 | 77.76 | 0.00 | 0.00 | 0.00 |
August | 816.58 | 466.02 | 350.56 | 1685.93 | 102.42 | 0.00 | 0.00 | 0.00 |
September | 670.06 | 322.98 | 347.08 | 1323.79 | 150.40 | 0.00 | 0.00 | 0.00 |
October | 673.04 | 409.61 | 263.43 | 1054.40 | 455.14 | 0.00 | 0.00 | 0.00 |
November | 517.53 | 310.68 | 206.85 | 648.55 | 663.76 | 0.00 | 0.00 | 0.00 |
December | 471.85 | 284.92 | 186.94 | 523.31 | 844.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 723.63 | 419.85 | 303.78 | 1223.29 | 404.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 471.85 | 284.92 | 186.94 | 523.31 | 77.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1018.74 | 633.03 | 398.00 | 2107.87 | 844.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.18 | 13.28 | 7.89 | 27.28 | 26.82 | 0.00 | 0.00 | 0.00 |
February | 20.87 | 11.94 | 8.93 | 24.00 | 26.19 | 0.00 | 0.00 | 0.00 |
March | 26.12 | 13.44 | 12.69 | 34.69 | 22.76 | 0.00 | 0.00 | 0.00 |
April | 37.29 | 22.22 | 15.06 | 62.49 | 12.92 | 0.00 | 0.00 | 0.00 |
May | 38.64 | 22.91 | 15.74 | 69.36 | 9.07 | 0.00 | 0.00 | 0.00 |
June | 40.28 | 25.03 | 15.25 | 83.34 | 3.78 | 0.00 | 0.00 | 0.00 |
July | 34.02 | 19.18 | 14.84 | 70.85 | 3.07 | 0.00 | 0.00 | 0.00 |
August | 32.29 | 18.43 | 13.86 | 66.66 | 4.05 | 0.00 | 0.00 | 0.00 |
September | 26.49 | 12.77 | 13.72 | 52.34 | 5.95 | 0.00 | 0.00 | 0.00 |
October | 26.61 | 16.20 | 10.42 | 41.69 | 18.00 | 0.00 | 0.00 | 0.00 |
November | 20.46 | 12.28 | 8.18 | 25.64 | 26.24 | 0.00 | 0.00 | 0.00 |
December | 18.66 | 11.27 | 7.39 | 20.69 | 33.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.61 | 16.60 | 12.01 | 48.37 | 15.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.66 | 11.27 | 7.39 | 20.69 | 3.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.28 | 25.03 | 15.74 | 83.34 | 33.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 709.58 | 566.73 | 142.86 | 1085.22 | 385.54 | 0.00 | 0.00 | 0.00 |
February | 448.66 | 302.59 | 146.07 | 621.63 | 353.52 | 0.00 | 0.00 | 0.00 |
March | 373.32 | 192.28 | 181.04 | 560.46 | 318.04 | 0.00 | 0.00 | 0.00 |
April | 317.79 | 128.42 | 189.37 | 611.29 | 184.65 | 0.00 | 0.00 | 0.00 |
May | 212.95 | 35.18 | 177.77 | 455.77 | 126.01 | 0.00 | 0.00 | 0.00 |
June | 182.35 | 14.06 | 168.29 | 518.44 | 51.18 | 0.00 | 0.00 | 0.00 |
July | 186.33 | 19.28 | 167.05 | 501.12 | 41.07 | 0.00 | 0.00 | 0.00 |
August | 226.57 | 62.61 | 163.96 | 575.19 | 55.06 | 0.00 | 0.00 | 0.00 |
September | 326.46 | 139.28 | 187.19 | 690.89 | 85.35 | 0.00 | 0.00 | 0.00 |
October | 520.18 | 360.05 | 160.14 | 872.33 | 251.46 | 0.00 | 0.00 | 0.00 |
November | 606.21 | 464.33 | 141.88 | 910.41 | 362.54 | 0.00 | 0.00 | 0.00 |
December | 659.70 | 522.24 | 137.46 | 958.83 | 461.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 397.52 | 233.87 | 163.65 | 697.57 | 222.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 182.35 | 14.06 | 137.46 | 455.77 | 41.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 709.58 | 566.73 | 189.37 | 1085.22 | 461.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 709.58 | 566.73 | 142.86 | 1085.22 | 385.54 | 0.00 | 0.00 | 0.00 |
February | 448.66 | 302.59 | 146.07 | 621.63 | 353.52 | 0.00 | 0.00 | 0.00 |
March | 373.32 | 192.28 | 181.04 | 560.46 | 318.04 | 0.00 | 0.00 | 0.00 |
April | 317.79 | 128.42 | 189.37 | 611.29 | 184.65 | 0.00 | 0.00 | 0.00 |
May | 212.95 | 35.18 | 177.77 | 455.77 | 126.01 | 0.00 | 0.00 | 0.00 |
June | 182.35 | 14.06 | 168.29 | 518.44 | 51.18 | 0.00 | 0.00 | 0.00 |
July | 186.33 | 19.28 | 167.05 | 501.12 | 41.07 | 0.00 | 0.00 | 0.00 |
August | 226.57 | 62.61 | 163.96 | 575.19 | 55.06 | 0.00 | 0.00 | 0.00 |
September | 326.46 | 139.28 | 187.19 | 690.89 | 85.35 | 0.00 | 0.00 | 0.00 |
October | 520.18 | 360.05 | 160.14 | 872.33 | 251.46 | 0.00 | 0.00 | 0.00 |
November | 606.21 | 464.33 | 141.88 | 910.41 | 362.54 | 0.00 | 0.00 | 0.00 |
December | 659.70 | 522.24 | 137.46 | 958.83 | 461.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 397.52 | 233.87 | 163.65 | 697.57 | 222.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 182.35 | 14.06 | 137.46 | 455.77 | 41.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 709.58 | 566.73 | 189.37 | 1085.22 | 461.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 709.54 | 566.69 | 142.85 | 1085.15 | 385.51 | 0.00 | 0.00 | 0.00 |
February | 448.63 | 302.57 | 146.06 | 621.59 | 353.50 | 0.00 | 0.00 | 0.00 |
March | 373.29 | 192.27 | 181.03 | 560.43 | 318.02 | 0.00 | 0.00 | 0.00 |
April | 317.77 | 128.41 | 189.36 | 611.25 | 184.63 | 0.00 | 0.00 | 0.00 |
May | 212.94 | 35.18 | 177.76 | 455.74 | 126.00 | 0.00 | 0.00 | 0.00 |
June | 182.34 | 14.06 | 168.28 | 518.41 | 51.18 | 0.00 | 0.00 | 0.00 |
July | 186.32 | 19.28 | 167.04 | 501.09 | 41.07 | 0.00 | 0.00 | 0.00 |
August | 226.55 | 62.61 | 163.95 | 575.15 | 55.06 | 0.00 | 0.00 | 0.00 |
September | 326.44 | 139.27 | 187.17 | 690.85 | 85.35 | 0.00 | 0.00 | 0.00 |
October | 520.15 | 360.02 | 160.13 | 872.27 | 251.44 | 0.00 | 0.00 | 0.00 |
November | 606.17 | 464.30 | 141.88 | 910.36 | 362.52 | 0.00 | 0.00 | 0.00 |
December | 659.66 | 522.21 | 137.45 | 958.77 | 461.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 397.49 | 233.86 | 163.64 | 697.53 | 222.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 182.34 | 14.06 | 137.45 | 455.74 | 41.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 709.54 | 566.69 | 189.36 | 1085.15 | 461.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 560.06 | 348.08 | 211.97 | 820.68 | 746.45 | 0.00 | 0.00 | 0.00 |
February | 453.70 | 219.34 | 234.37 | 540.47 | 694.48 | 0.00 | 0.00 | 0.00 |
March | 600.94 | 286.48 | 314.46 | 832.60 | 611.17 | 0.00 | 0.00 | 0.00 |
April | 922.77 | 526.37 | 396.39 | 1595.23 | 369.47 | 0.00 | 0.00 | 0.00 |
May | 925.13 | 518.72 | 406.41 | 1708.18 | 265.14 | 0.00 | 0.00 | 0.00 |
June | 983.51 | 578.46 | 405.05 | 2068.01 | 115.96 | 0.00 | 0.00 | 0.00 |
July | 715.82 | 334.14 | 381.68 | 1552.79 | 88.61 | 0.00 | 0.00 | 0.00 |
August | 682.60 | 342.81 | 339.79 | 1468.82 | 112.90 | 0.00 | 0.00 | 0.00 |
September | 595.00 | 249.99 | 345.01 | 1211.36 | 164.33 | 0.00 | 0.00 | 0.00 |
October | 608.81 | 348.11 | 260.69 | 994.66 | 496.09 | 0.00 | 0.00 | 0.00 |
November | 560.73 | 338.55 | 222.18 | 786.88 | 720.03 | 0.00 | 0.00 | 0.00 |
December | 451.92 | 257.31 | 194.61 | 583.71 | 913.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 672.51 | 362.87 | 309.64 | 1182.96 | 440.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 451.92 | 219.34 | 194.61 | 540.47 | 88.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 983.51 | 578.46 | 406.41 | 2068.01 | 913.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.14 | 13.76 | 8.38 | 32.45 | 29.51 | 0.00 | 0.00 | 0.00 |
February | 17.94 | 8.67 | 9.27 | 21.37 | 27.46 | 0.00 | 0.00 | 0.00 |
March | 23.76 | 11.33 | 12.43 | 32.92 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 36.49 | 20.81 | 15.67 | 63.07 | 14.61 | 0.00 | 0.00 | 0.00 |
May | 36.58 | 20.51 | 16.07 | 67.54 | 10.48 | 0.00 | 0.00 | 0.00 |
June | 38.89 | 22.87 | 16.02 | 81.77 | 4.59 | 0.00 | 0.00 | 0.00 |
July | 28.30 | 13.21 | 15.09 | 61.40 | 3.50 | 0.00 | 0.00 | 0.00 |
August | 26.99 | 13.55 | 13.43 | 58.08 | 4.46 | 0.00 | 0.00 | 0.00 |
September | 23.53 | 9.88 | 13.64 | 47.90 | 6.50 | 0.00 | 0.00 | 0.00 |
October | 24.07 | 13.76 | 10.31 | 39.33 | 19.62 | 0.00 | 0.00 | 0.00 |
November | 22.17 | 13.39 | 8.78 | 31.11 | 28.47 | 0.00 | 0.00 | 0.00 |
December | 17.87 | 10.17 | 7.69 | 23.08 | 36.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.59 | 14.35 | 12.24 | 46.77 | 17.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.87 | 8.67 | 7.69 | 21.37 | 3.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.89 | 22.87 | 16.07 | 81.77 | 36.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 258.53 | 0.00 | 258.53 | 203.69 | 1116.69 | 0.00 | 0.00 | 0.00 |
February | 294.58 | 0.00 | 294.58 | 139.36 | 1102.26 | 0.00 | 0.00 | 0.00 |
March | 391.50 | 0.00 | 391.50 | 363.68 | 976.43 | 0.00 | 0.00 | 0.00 |
April | 476.99 | 4.95 | 472.04 | 801.03 | 540.93 | 0.00 | 0.00 | 0.00 |
May | 558.36 | 44.71 | 513.65 | 1099.65 | 364.23 | 0.00 | 0.00 | 0.00 |
June | 648.85 | 117.89 | 530.96 | 1724.45 | 156.18 | 0.00 | 0.00 | 0.00 |
July | 553.35 | 57.65 | 495.70 | 1471.48 | 119.78 | 0.00 | 0.00 | 0.00 |
August | 446.65 | 11.10 | 435.56 | 1220.45 | 151.89 | 0.00 | 0.00 | 0.00 |
September | 421.41 | 0.11 | 421.30 | 1013.00 | 228.69 | 0.00 | 0.00 | 0.00 |
October | 326.03 | 0.00 | 326.03 | 481.50 | 716.99 | 0.00 | 0.00 | 0.00 |
November | 271.65 | 0.00 | 271.65 | 201.52 | 1042.38 | 0.00 | 0.00 | 0.00 |
December | 241.49 | 0.00 | 241.49 | 121.50 | 1357.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 407.86 | 19.74 | 388.12 | 739.51 | 654.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 241.49 | 0.00 | 241.49 | 121.50 | 119.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 648.85 | 117.89 | 530.96 | 1724.45 | 1357.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 556.77 | 349.28 | 207.49 | 713.72 | 687.21 | 0.00 | 0.00 | 0.00 |
February | 548.81 | 313.94 | 234.86 | 619.77 | 686.43 | 0.00 | 0.00 | 0.00 |
March | 686.81 | 353.30 | 333.51 | 893.73 | 605.16 | 0.00 | 0.00 | 0.00 |
April | 980.38 | 584.32 | 396.06 | 1630.05 | 340.38 | 0.00 | 0.00 | 0.00 |
May | 1016.03 | 602.29 | 413.74 | 1810.63 | 241.39 | 0.00 | 0.00 | 0.00 |
June | 1059.03 | 658.06 | 400.96 | 2184.55 | 100.13 | 0.00 | 0.00 | 0.00 |
July | 894.42 | 504.32 | 390.09 | 1865.33 | 76.50 | 0.00 | 0.00 | 0.00 |
August | 848.88 | 484.45 | 364.43 | 1757.48 | 97.40 | 0.00 | 0.00 | 0.00 |
September | 696.56 | 335.75 | 360.81 | 1383.89 | 142.85 | 0.00 | 0.00 | 0.00 |
October | 699.66 | 425.80 | 273.85 | 1101.68 | 441.87 | 0.00 | 0.00 | 0.00 |
November | 538.00 | 322.97 | 215.03 | 680.91 | 647.04 | 0.00 | 0.00 | 0.00 |
December | 490.51 | 296.18 | 194.33 | 551.97 | 832.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 752.25 | 436.46 | 315.79 | 1269.22 | 407.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 490.51 | 296.18 | 194.33 | 551.97 | 76.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1059.03 | 658.06 | 413.74 | 2184.55 | 832.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2128.69 | 1700.12 | 428.57 | 3243.02 | 1093.03 | 0.00 | 0.00 | 0.00 |
February | 1345.94 | 907.75 | 438.19 | 1829.28 | 1057.90 | 0.00 | 0.00 | 0.00 |
March | 1119.92 | 576.82 | 543.10 | 1641.67 | 973.22 | 0.00 | 0.00 | 0.00 |
April | 953.35 | 385.24 | 568.10 | 1814.82 | 566.65 | 0.00 | 0.00 | 0.00 |
May | 638.84 | 105.54 | 533.30 | 1351.08 | 398.89 | 0.00 | 0.00 | 0.00 |
June | 547.04 | 42.17 | 504.87 | 1558.41 | 163.67 | 0.00 | 0.00 | 0.00 |
July | 558.97 | 57.83 | 501.14 | 1516.83 | 121.96 | 0.00 | 0.00 | 0.00 |
August | 679.68 | 187.83 | 491.85 | 1747.43 | 153.69 | 0.00 | 0.00 | 0.00 |
September | 979.36 | 417.82 | 561.54 | 2095.79 | 230.61 | 0.00 | 0.00 | 0.00 |
October | 1560.51 | 1080.10 | 480.40 | 2622.78 | 700.38 | 0.00 | 0.00 | 0.00 |
November | 1818.58 | 1392.93 | 425.64 | 2728.05 | 1010.40 | 0.00 | 0.00 | 0.00 |
December | 1979.04 | 1566.68 | 412.37 | 2867.87 | 1301.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1192.52 | 701.60 | 490.92 | 2087.24 | 645.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 547.04 | 42.17 | 412.37 | 1351.08 | 121.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2128.69 | 1700.12 | 568.10 | 3243.02 | 1301.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 582.21 | 361.85 | 220.36 | 849.80 | 756.08 | 0.00 | 0.00 | 0.00 |
February | 471.64 | 228.01 | 243.63 | 550.64 | 725.23 | 0.00 | 0.00 | 0.00 |
March | 624.71 | 297.81 | 326.90 | 846.65 | 646.10 | 0.00 | 0.00 | 0.00 |
April | 959.26 | 547.19 | 412.07 | 1645.77 | 384.69 | 0.00 | 0.00 | 0.00 |
May | 961.72 | 539.24 | 422.48 | 1763.81 | 277.96 | 0.00 | 0.00 | 0.00 |
June | 1022.40 | 601.34 | 421.07 | 2143.82 | 120.38 | 0.00 | 0.00 | 0.00 |
July | 744.13 | 347.36 | 396.77 | 1617.32 | 88.18 | 0.00 | 0.00 | 0.00 |
August | 709.59 | 356.37 | 353.22 | 1532.77 | 109.28 | 0.00 | 0.00 | 0.00 |
September | 618.53 | 259.88 | 358.65 | 1266.97 | 157.15 | 0.00 | 0.00 | 0.00 |
October | 632.88 | 361.88 | 271.00 | 1039.95 | 483.04 | 0.00 | 0.00 | 0.00 |
November | 582.90 | 351.94 | 230.96 | 823.49 | 700.23 | 0.00 | 0.00 | 0.00 |
December | 469.79 | 267.49 | 202.31 | 611.13 | 904.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 699.11 | 377.22 | 321.89 | 1227.19 | 444.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 469.79 | 228.01 | 202.31 | 550.64 | 88.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1022.40 | 601.34 | 422.48 | 2143.82 | 904.43 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.692434E+09 | 0.00 | 0.692434E+09 | 0.601311E+09 | 0.274736E+10 |
February | 0.712656E+09 | 0.00 | 0.712656E+09 | 0.374690E+09 | 0.243114E+10 |
March | 0.104860E+10 | 0.00 | 0.104860E+10 | 0.102011E+10 | 0.243570E+10 |
April | 0.123635E+10 | 12830113.86 | 0.122352E+10 | 0.207494E+10 | 0.133697E+10 |
May | 0.149552E+10 | 0.119747E+09 | 0.137577E+10 | 0.293698E+10 | 0.949672E+09 |
June | 0.168183E+10 | 0.305571E+09 | 0.137626E+10 | 0.444204E+10 | 0.398394E+09 |
July | 0.148209E+10 | 0.154404E+09 | 0.132768E+10 | 0.390815E+10 | 0.317558E+09 |
August | 0.119631E+10 | 29719197.80 | 0.116659E+10 | 0.324630E+10 | 0.396397E+09 |
September | 0.109229E+10 | 291589.31 | 0.109200E+10 | 0.261183E+10 | 0.573216E+09 |
October | 0.873252E+09 | 0.00 | 0.873252E+09 | 0.131526E+10 | 0.178121E+10 |
November | 0.704109E+09 | 0.00 | 0.704109E+09 | 0.571178E+09 | 0.246746E+10 |
December | 0.646797E+09 | 0.00 | 0.646797E+09 | 0.382525E+09 | 0.333448E+10 |
Annual Sum or Average | 0.128622E+11 | 0.622563E+09 | 0.122397E+11 | 0.234853E+11 | 0.191696E+11 |
Minimum of Months | 0.646797E+09 | 0.00 | 0.646797E+09 | 0.374690E+09 | 0.317558E+09 |
Maximum of Months | 0.168183E+10 | 0.305571E+09 | 0.137626E+10 | 0.444204E+10 | 0.333448E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.149126E+10 | 0.935504E+09 | 0.555752E+09 | 0.195637E+10 | 0.171134E+10 |
February | 0.132767E+10 | 0.759488E+09 | 0.568185E+09 | 0.153025E+10 | 0.153285E+10 |
March | 0.183954E+10 | 0.946272E+09 | 0.893270E+09 | 0.242503E+10 | 0.152698E+10 |
April | 0.254114E+10 | 0.151455E+10 | 0.102659E+10 | 0.421691E+10 | 0.851971E+09 |
May | 0.272132E+10 | 0.161317E+10 | 0.110815E+10 | 0.483167E+10 | 0.631318E+09 |
June | 0.274500E+10 | 0.170570E+10 | 0.103930E+10 | 0.563429E+10 | 0.254636E+09 |
July | 0.239560E+10 | 0.135078E+10 | 0.104482E+10 | 0.496624E+10 | 0.202725E+09 |
August | 0.227364E+10 | 0.129756E+10 | 0.976078E+09 | 0.468365E+10 | 0.253935E+09 |
September | 0.180549E+10 | 0.870276E+09 | 0.935215E+09 | 0.357172E+10 | 0.360035E+09 |
October | 0.187396E+10 | 0.114048E+10 | 0.733484E+09 | 0.296415E+10 | 0.111254E+10 |
November | 0.139449E+10 | 0.837126E+09 | 0.557360E+09 | 0.180441E+10 | 0.155126E+10 |
December | 0.131379E+10 | 0.793301E+09 | 0.520486E+09 | 0.153762E+10 | 0.206258E+10 |
Annual Sum or Average | 0.237229E+11 | 0.137642E+11 | 0.995870E+10 | 0.401223E+11 | 0.120522E+11 |
Minimum of Months | 0.131379E+10 | 0.759488E+09 | 0.520486E+09 | 0.153025E+10 | 0.202725E+09 |
Maximum of Months | 0.274500E+10 | 0.170570E+10 | 0.110815E+10 | 0.563429E+10 | 0.206258E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.570147E+10 | 0.455360E+10 | 0.114787E+10 | 0.873279E+10 | 0.273461E+10 |
February | 0.325610E+10 | 0.219602E+10 | 0.106007E+10 | 0.446613E+10 | 0.236024E+10 |
March | 0.299960E+10 | 0.154495E+10 | 0.145465E+10 | 0.443467E+10 | 0.244655E+10 |
April | 0.247108E+10 | 0.998553E+09 | 0.147253E+10 | 0.469392E+10 | 0.140302E+10 |
May | 0.171108E+10 | 0.282688E+09 | 0.142839E+10 | 0.360408E+10 | 0.103131E+10 |
June | 0.141792E+10 | 0.109302E+09 | 0.130862E+10 | 0.401222E+10 | 0.411775E+09 |
July | 0.149716E+10 | 0.154892E+09 | 0.134227E+10 | 0.402995E+10 | 0.319919E+09 |
August | 0.182047E+10 | 0.503085E+09 | 0.131738E+10 | 0.465338E+10 | 0.397820E+09 |
September | 0.253850E+10 | 0.108298E+10 | 0.145552E+10 | 0.541097E+10 | 0.577797E+09 |
October | 0.417966E+10 | 0.289294E+10 | 0.128671E+10 | 0.703760E+10 | 0.176324E+10 |
November | 0.471375E+10 | 0.361049E+10 | 0.110326E+10 | 0.711601E+10 | 0.243393E+10 |
December | 0.530067E+10 | 0.419619E+10 | 0.110448E+10 | 0.774891E+10 | 0.323784E+10 |
Annual Sum or Average | 0.376074E+11 | 0.221257E+11 | 0.154818E+11 | 0.659406E+11 | 0.191180E+11 |
Minimum of Months | 0.141792E+10 | 0.109302E+09 | 0.106007E+10 | 0.360408E+10 | 0.319919E+09 |
Maximum of Months | 0.570147E+10 | 0.455360E+10 | 0.147253E+10 | 0.873279E+10 | 0.323784E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.155938E+10 | 0.969179E+09 | 0.590203E+09 | 0.230542E+10 | 0.187561E+10 |
February | 0.114100E+10 | 0.551603E+09 | 0.589398E+09 | 0.135399E+10 | 0.161189E+10 |
March | 0.167322E+10 | 0.797647E+09 | 0.875569E+09 | 0.229399E+10 | 0.161872E+10 |
April | 0.248640E+10 | 0.141831E+10 | 0.106808E+10 | 0.426045E+10 | 0.954448E+09 |
May | 0.257587E+10 | 0.144429E+10 | 0.113158E+10 | 0.471053E+10 | 0.721455E+09 |
June | 0.265007E+10 | 0.155867E+10 | 0.109141E+10 | 0.553252E+10 | 0.303769E+09 |
July | 0.199308E+10 | 0.930359E+09 | 0.106272E+10 | 0.430744E+10 | 0.231947E+09 |
August | 0.190058E+10 | 0.954507E+09 | 0.946071E+09 | 0.408721E+10 | 0.283716E+09 |
September | 0.160323E+10 | 0.673609E+09 | 0.929617E+09 | 0.327239E+10 | 0.394154E+09 |
October | 0.169511E+10 | 0.969260E+09 | 0.725854E+09 | 0.279797E+10 | 0.120730E+10 |
November | 0.151088E+10 | 0.912223E+09 | 0.598656E+09 | 0.216187E+10 | 0.167156E+10 |
December | 0.125830E+10 | 0.716434E+09 | 0.541863E+09 | 0.167134E+10 | 0.223762E+10 |
Annual Sum or Average | 0.220471E+11 | 0.118961E+11 | 0.101510E+11 | 0.387551E+11 | 0.131122E+11 |
Minimum of Months | 0.114100E+10 | 0.551603E+09 | 0.541863E+09 | 0.135399E+10 | 0.231947E+09 |
Maximum of Months | 0.265007E+10 | 0.155867E+10 | 0.113158E+10 | 0.553252E+10 | 0.223762E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.230800E+09 | 0.00 | 0.230800E+09 | 0.188898E+09 | 0.991018E+09 |
February | 0.237541E+09 | 0.00 | 0.237541E+09 | 0.124451E+09 | 0.863991E+09 |
March | 0.349515E+09 | 0.00 | 0.349515E+09 | 0.351031E+09 | 0.832048E+09 |
April | 0.412096E+09 | 4276502.28 | 0.407820E+09 | 0.709647E+09 | 0.444102E+09 |
May | 0.498483E+09 | 39913884.74 | 0.458569E+09 | 0.100171E+10 | 0.305084E+09 |
June | 0.560582E+09 | 0.101852E+09 | 0.458730E+09 | 0.150095E+10 | 0.124884E+09 |
July | 0.494006E+09 | 51465646.98 | 0.442540E+09 | 0.131320E+10 | 0.104903E+09 |
August | 0.398752E+09 | 9905930.57 | 0.388846E+09 | 0.108372E+10 | 0.137526E+09 |
September | 0.364081E+09 | 97191.84 | 0.363983E+09 | 0.864942E+09 | 0.206534E+09 |
October | 0.291070E+09 | 0.00 | 0.291070E+09 | 0.421553E+09 | 0.667071E+09 |
November | 0.234692E+09 | 0.00 | 0.234692E+09 | 0.167481E+09 | 0.940758E+09 |
December | 0.215589E+09 | 0.00 | 0.215589E+09 | 0.102806E+09 | 0.125034E+10 |
Annual Sum or Average | 0.428721E+10 | 0.207511E+09 | 0.407970E+10 | 0.783039E+10 | 0.686826E+10 |
Minimum of Months | 0.215589E+09 | 0.00 | 0.215589E+09 | 0.102806E+09 | 0.104903E+09 |
Maximum of Months | 0.560582E+09 | 0.101852E+09 | 0.458730E+09 | 0.150095E+10 | 0.125034E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.230815E+09 | 0.00 | 0.230815E+09 | 0.188910E+09 | 0.991080E+09 |
February | 0.237556E+09 | 0.00 | 0.237556E+09 | 0.124459E+09 | 0.864045E+09 |
March | 0.349538E+09 | 0.00 | 0.349538E+09 | 0.351053E+09 | 0.832100E+09 |
April | 0.412122E+09 | 4276772.55 | 0.407846E+09 | 0.709692E+09 | 0.444130E+09 |
May | 0.498514E+09 | 39916407.23 | 0.458598E+09 | 0.100178E+10 | 0.305104E+09 |
June | 0.560618E+09 | 0.101858E+09 | 0.458759E+09 | 0.150104E+10 | 0.124892E+09 |
July | 0.494037E+09 | 51468899.52 | 0.442568E+09 | 0.131328E+10 | 0.104910E+09 |
August | 0.398777E+09 | 9906556.61 | 0.388871E+09 | 0.108379E+10 | 0.137535E+09 |
September | 0.364104E+09 | 97197.98 | 0.364006E+09 | 0.864997E+09 | 0.206547E+09 |
October | 0.291089E+09 | 0.00 | 0.291089E+09 | 0.421579E+09 | 0.667113E+09 |
November | 0.234707E+09 | 0.00 | 0.234707E+09 | 0.167492E+09 | 0.940817E+09 |
December | 0.215603E+09 | 0.00 | 0.215603E+09 | 0.102813E+09 | 0.125042E+10 |
Annual Sum or Average | 0.428748E+10 | 0.207524E+09 | 0.407995E+10 | 0.783088E+10 | 0.686869E+10 |
Minimum of Months | 0.215603E+09 | 0.00 | 0.215603E+09 | 0.102813E+09 | 0.104910E+09 |
Maximum of Months | 0.560618E+09 | 0.101858E+09 | 0.458759E+09 | 0.150104E+10 | 0.125042E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.230815E+09 | 0.00 | 0.230815E+09 | 0.188910E+09 | 0.991080E+09 |
February | 0.237556E+09 | 0.00 | 0.237556E+09 | 0.124459E+09 | 0.864045E+09 |
March | 0.349538E+09 | 0.00 | 0.349538E+09 | 0.351053E+09 | 0.832100E+09 |
April | 0.412122E+09 | 4276772.55 | 0.407846E+09 | 0.709692E+09 | 0.444130E+09 |
May | 0.498514E+09 | 39916407.23 | 0.458598E+09 | 0.100178E+10 | 0.305104E+09 |
June | 0.560618E+09 | 0.101858E+09 | 0.458759E+09 | 0.150104E+10 | 0.124892E+09 |
July | 0.494037E+09 | 51468899.52 | 0.442568E+09 | 0.131328E+10 | 0.104910E+09 |
August | 0.398777E+09 | 9906556.61 | 0.388871E+09 | 0.108379E+10 | 0.137535E+09 |
September | 0.364104E+09 | 97197.98 | 0.364006E+09 | 0.864997E+09 | 0.206547E+09 |
October | 0.291089E+09 | 0.00 | 0.291089E+09 | 0.421579E+09 | 0.667113E+09 |
November | 0.234707E+09 | 0.00 | 0.234707E+09 | 0.167492E+09 | 0.940817E+09 |
December | 0.215603E+09 | 0.00 | 0.215603E+09 | 0.102813E+09 | 0.125042E+10 |
Annual Sum or Average | 0.428748E+10 | 0.207524E+09 | 0.407995E+10 | 0.783088E+10 | 0.686869E+10 |
Minimum of Months | 0.215603E+09 | 0.00 | 0.215603E+09 | 0.102813E+09 | 0.104910E+09 |
Maximum of Months | 0.560618E+09 | 0.101858E+09 | 0.458759E+09 | 0.150104E+10 | 0.125042E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.143453E+10 | 0.899913E+09 | 0.534612E+09 | 0.184783E+10 | 0.181672E+10 |
February | 0.127716E+10 | 0.730593E+09 | 0.546571E+09 | 0.146847E+10 | 0.160227E+10 |
March | 0.176956E+10 | 0.910271E+09 | 0.859290E+09 | 0.234990E+10 | 0.154164E+10 |
April | 0.244447E+10 | 0.145693E+10 | 0.987542E+09 | 0.409655E+10 | 0.846986E+09 |
May | 0.261780E+10 | 0.155180E+10 | 0.106600E+10 | 0.469858E+10 | 0.614250E+09 |
June | 0.264057E+10 | 0.164081E+10 | 0.999767E+09 | 0.546360E+10 | 0.247713E+09 |
July | 0.230447E+10 | 0.129939E+10 | 0.100508E+10 | 0.479917E+10 | 0.208260E+09 |
August | 0.218714E+10 | 0.124819E+10 | 0.938948E+09 | 0.451559E+10 | 0.274329E+09 |
September | 0.173681E+10 | 0.837167E+09 | 0.899639E+09 | 0.343128E+10 | 0.389832E+09 |
October | 0.180267E+10 | 0.109709E+10 | 0.705582E+09 | 0.282409E+10 | 0.121906E+10 |
November | 0.134144E+10 | 0.805278E+09 | 0.536158E+09 | 0.168104E+10 | 0.172047E+10 |
December | 0.126381E+10 | 0.763120E+09 | 0.500687E+09 | 0.140162E+10 | 0.226132E+10 |
Annual Sum or Average | 0.228204E+11 | 0.132405E+11 | 0.957987E+10 | 0.385777E+11 | 0.127428E+11 |
Minimum of Months | 0.126381E+10 | 0.730593E+09 | 0.500687E+09 | 0.140162E+10 | 0.208260E+09 |
Maximum of Months | 0.264057E+10 | 0.164081E+10 | 0.106600E+10 | 0.546360E+10 | 0.226132E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 56719828.13 | 35581757.50 | 21138070.63 | 73061355.99 | 71831496.27 |
February | 50497914.78 | 28886985.18 | 21610929.59 | 58061936.52 | 63352203.46 |
March | 69966834.45 | 35991292.48 | 33975541.97 | 92912874.28 | 60955131.40 |
April | 96652142.40 | 57605634.02 | 39046508.38 | 0.161974E+09 | 33489061.77 |
May | 0.103505E+09 | 61356715.86 | 42148610.46 | 0.185778E+09 | 24286891.95 |
June | 0.104406E+09 | 64876028.27 | 39529895.41 | 0.216026E+09 | 9794344.73 |
July | 91116650.19 | 51376699.48 | 39739950.72 | 0.189755E+09 | 8234420.40 |
August | 86477595.18 | 49352440.62 | 37125154.56 | 0.178542E+09 | 10846738.85 |
September | 68671718.82 | 33100816.36 | 35570902.45 | 0.135670E+09 | 15413625.90 |
October | 71275881.63 | 43377800.09 | 27898081.54 | 0.111662E+09 | 48200442.39 |
November | 53039175.95 | 31839969.78 | 21199206.18 | 66466675.69 | 68025715.25 |
December | 49969795.95 | 30173082.91 | 19796713.04 | 55418828.43 | 89410629.80 |
Annual Sum or Average | 0.902299E+09 | 0.523519E+09 | 0.378780E+09 | 0.152533E+10 | 0.503841E+09 |
Minimum of Months | 49969795.95 | 28886985.18 | 19796713.04 | 55418828.43 | 8234420.40 |
Maximum of Months | 0.104406E+09 | 64876028.27 | 42148610.46 | 0.216026E+09 | 89410629.80 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190055E+10 | 0.151792E+10 | 0.382634E+09 | 0.290666E+10 | 0.103262E+10 |
February | 0.108540E+10 | 0.732031E+09 | 0.353368E+09 | 0.150384E+10 | 0.855242E+09 |
March | 0.999896E+09 | 0.514999E+09 | 0.484897E+09 | 0.150114E+10 | 0.851837E+09 |
April | 0.823716E+09 | 0.332862E+09 | 0.490854E+09 | 0.158446E+10 | 0.478601E+09 |
May | 0.570375E+09 | 94232517.90 | 0.476142E+09 | 0.122074E+10 | 0.337503E+09 |
June | 0.472651E+09 | 36435293.28 | 0.436216E+09 | 0.134380E+10 | 0.132663E+09 |
July | 0.499066E+09 | 51632483.83 | 0.447433E+09 | 0.134221E+10 | 0.110008E+09 |
August | 0.606839E+09 | 0.167701E+09 | 0.439139E+09 | 0.154059E+10 | 0.147476E+09 |
September | 0.846192E+09 | 0.361007E+09 | 0.485186E+09 | 0.179079E+10 | 0.221233E+09 |
October | 0.139326E+10 | 0.964345E+09 | 0.428917E+09 | 0.233645E+10 | 0.673498E+09 |
November | 0.157130E+10 | 0.120353E+10 | 0.367765E+09 | 0.235979E+10 | 0.939705E+09 |
December | 0.176695E+10 | 0.139878E+10 | 0.368171E+09 | 0.256814E+10 | 0.123550E+10 |
Annual Sum or Average | 0.125362E+11 | 0.737547E+10 | 0.516072E+10 | 0.219986E+11 | 0.701589E+10 |
Minimum of Months | 0.472651E+09 | 36435293.28 | 0.353368E+09 | 0.122074E+10 | 0.110008E+09 |
Maximum of Months | 0.190055E+10 | 0.151792E+10 | 0.490854E+09 | 0.290666E+10 | 0.123550E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190055E+10 | 0.151792E+10 | 0.382634E+09 | 0.290666E+10 | 0.103262E+10 |
February | 0.108540E+10 | 0.732031E+09 | 0.353368E+09 | 0.150384E+10 | 0.855242E+09 |
March | 0.999896E+09 | 0.514999E+09 | 0.484897E+09 | 0.150114E+10 | 0.851837E+09 |
April | 0.823716E+09 | 0.332862E+09 | 0.490854E+09 | 0.158446E+10 | 0.478601E+09 |
May | 0.570375E+09 | 94232517.90 | 0.476142E+09 | 0.122074E+10 | 0.337503E+09 |
June | 0.472651E+09 | 36435293.28 | 0.436216E+09 | 0.134380E+10 | 0.132663E+09 |
July | 0.499066E+09 | 51632483.83 | 0.447433E+09 | 0.134221E+10 | 0.110008E+09 |
August | 0.606839E+09 | 0.167701E+09 | 0.439139E+09 | 0.154059E+10 | 0.147476E+09 |
September | 0.846192E+09 | 0.361007E+09 | 0.485186E+09 | 0.179079E+10 | 0.221233E+09 |
October | 0.139326E+10 | 0.964345E+09 | 0.428917E+09 | 0.233645E+10 | 0.673498E+09 |
November | 0.157130E+10 | 0.120353E+10 | 0.367765E+09 | 0.235979E+10 | 0.939705E+09 |
December | 0.176695E+10 | 0.139878E+10 | 0.368171E+09 | 0.256814E+10 | 0.123550E+10 |
Annual Sum or Average | 0.125362E+11 | 0.737547E+10 | 0.516072E+10 | 0.219986E+11 | 0.701589E+10 |
Minimum of Months | 0.472651E+09 | 36435293.28 | 0.353368E+09 | 0.122074E+10 | 0.110008E+09 |
Maximum of Months | 0.190055E+10 | 0.151792E+10 | 0.490854E+09 | 0.290666E+10 | 0.123550E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190043E+10 | 0.151782E+10 | 0.382610E+09 | 0.290647E+10 | 0.103255E+10 |
February | 0.108533E+10 | 0.731985E+09 | 0.353346E+09 | 0.150375E+10 | 0.855188E+09 |
March | 0.999833E+09 | 0.514966E+09 | 0.484867E+09 | 0.150105E+10 | 0.851783E+09 |
April | 0.823664E+09 | 0.332841E+09 | 0.490823E+09 | 0.158436E+10 | 0.478570E+09 |
May | 0.570339E+09 | 94226562.93 | 0.476112E+09 | 0.122066E+10 | 0.337482E+09 |
June | 0.472621E+09 | 36432990.78 | 0.436188E+09 | 0.134371E+10 | 0.132655E+09 |
July | 0.499034E+09 | 51629220.94 | 0.447405E+09 | 0.134213E+10 | 0.110001E+09 |
August | 0.606801E+09 | 0.167690E+09 | 0.439111E+09 | 0.154049E+10 | 0.147467E+09 |
September | 0.846139E+09 | 0.360984E+09 | 0.485155E+09 | 0.179068E+10 | 0.221219E+09 |
October | 0.139317E+10 | 0.964285E+09 | 0.428890E+09 | 0.233630E+10 | 0.673455E+09 |
November | 0.157120E+10 | 0.120346E+10 | 0.367742E+09 | 0.235965E+10 | 0.939646E+09 |
December | 0.176684E+10 | 0.139869E+10 | 0.368147E+09 | 0.256797E+10 | 0.123542E+10 |
Annual Sum or Average | 0.125354E+11 | 0.737501E+10 | 0.516040E+10 | 0.219972E+11 | 0.701544E+10 |
Minimum of Months | 0.472621E+09 | 36432990.78 | 0.353346E+09 | 0.122066E+10 | 0.110001E+09 |
Maximum of Months | 0.190043E+10 | 0.151782E+10 | 0.490823E+09 | 0.290647E+10 | 0.123542E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150006E+10 | 0.932307E+09 | 0.567752E+09 | 0.219810E+10 | 0.199930E+10 |
February | 0.109759E+10 | 0.530618E+09 | 0.566977E+09 | 0.130752E+10 | 0.168008E+10 |
March | 0.160956E+10 | 0.767301E+09 | 0.842262E+09 | 0.223002E+10 | 0.163696E+10 |
April | 0.239181E+10 | 0.136435E+10 | 0.102745E+10 | 0.413484E+10 | 0.957659E+09 |
May | 0.247788E+10 | 0.138934E+10 | 0.108854E+10 | 0.457519E+10 | 0.710153E+09 |
June | 0.254926E+10 | 0.149937E+10 | 0.104989E+10 | 0.536027E+10 | 0.300577E+09 |
July | 0.191726E+10 | 0.894964E+09 | 0.102229E+10 | 0.415898E+10 | 0.237328E+09 |
August | 0.182828E+10 | 0.918193E+09 | 0.910084E+09 | 0.393408E+10 | 0.302401E+09 |
September | 0.154224E+10 | 0.647981E+09 | 0.894254E+09 | 0.313985E+10 | 0.425933E+09 |
October | 0.163063E+10 | 0.932385E+09 | 0.698243E+09 | 0.266409E+10 | 0.132873E+10 |
November | 0.145340E+10 | 0.877518E+09 | 0.575884E+09 | 0.203959E+10 | 0.186631E+10 |
December | 0.121043E+10 | 0.689177E+09 | 0.521250E+09 | 0.156342E+10 | 0.244607E+10 |
Annual Sum or Average | 0.212084E+11 | 0.114435E+11 | 0.976488E+10 | 0.373059E+11 | 0.138915E+11 |
Minimum of Months | 0.109759E+10 | 0.530618E+09 | 0.521250E+09 | 0.130752E+10 | 0.237328E+09 |
Maximum of Months | 0.254926E+10 | 0.149937E+10 | 0.108854E+10 | 0.536027E+10 | 0.244607E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59310802.78 | 36862441.60 | 22448361.18 | 86910682.33 | 79050410.92 |
February | 43397800.01 | 20980073.75 | 22417726.27 | 51697824.91 | 66428900.45 |
March | 63640511.41 | 30338286.32 | 33302225.09 | 88172835.85 | 64723993.26 |
April | 94569701.97 | 53945157.66 | 40624544.31 | 0.163487E+09 | 37864929.92 |
May | 97972901.83 | 54933205.91 | 43039695.92 | 0.180898E+09 | 28078752.10 |
June | 0.100795E+09 | 59283427.48 | 41511653.45 | 0.211940E+09 | 11884522.59 |
July | 75806424.69 | 35385937.36 | 40420487.33 | 0.164442E+09 | 9383701.26 |
August | 72288202.72 | 36304390.75 | 35983811.97 | 0.155550E+09 | 11956626.21 |
September | 60978432.03 | 25620519.82 | 35357912.21 | 0.124147E+09 | 16840991.86 |
October | 64473385.56 | 36865549.88 | 27607835.68 | 0.105335E+09 | 52536824.47 |
November | 57466037.47 | 34696164.32 | 22769873.15 | 80643128.92 | 73792197.50 |
December | 47859091.44 | 27249360.81 | 20609730.63 | 61815882.68 | 96715342.99 |
Annual Sum or Average | 0.838558E+09 | 0.452465E+09 | 0.386094E+09 | 0.147504E+10 | 0.549257E+09 |
Minimum of Months | 43397800.01 | 20980073.75 | 20609730.63 | 51697824.91 | 9383701.26 |
Maximum of Months | 0.100795E+09 | 59283427.48 | 43039695.92 | 0.211940E+09 | 96715342.99 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.692434E+09 | 0.00 | 0.692434E+09 | 0.545554E+09 | 0.299094E+10 |
February | 0.712656E+09 | 0.00 | 0.712656E+09 | 0.337133E+09 | 0.266658E+10 |
March | 0.104860E+10 | 0.00 | 0.104860E+10 | 0.974068E+09 | 0.261528E+10 |
April | 0.123635E+10 | 12830113.86 | 0.122352E+10 | 0.207628E+10 | 0.140208E+10 |
May | 0.149552E+10 | 0.119747E+09 | 0.137577E+10 | 0.294529E+10 | 0.975561E+09 |
June | 0.168183E+10 | 0.305571E+09 | 0.137626E+10 | 0.446978E+10 | 0.404825E+09 |
July | 0.148209E+10 | 0.154404E+09 | 0.132768E+10 | 0.394120E+10 | 0.320825E+09 |
August | 0.119631E+10 | 29719197.80 | 0.116659E+10 | 0.326884E+10 | 0.406832E+09 |
September | 0.109229E+10 | 291589.31 | 0.109200E+10 | 0.262569E+10 | 0.592774E+09 |
October | 0.873252E+09 | 0.00 | 0.873252E+09 | 0.128965E+10 | 0.192039E+10 |
November | 0.704109E+09 | 0.00 | 0.704109E+09 | 0.522331E+09 | 0.270186E+10 |
December | 0.646797E+09 | 0.00 | 0.646797E+09 | 0.325430E+09 | 0.363724E+10 |
Annual Sum or Average | 0.128622E+11 | 0.622563E+09 | 0.122397E+11 | 0.233212E+11 | 0.206352E+11 |
Minimum of Months | 0.646797E+09 | 0.00 | 0.646797E+09 | 0.325430E+09 | 0.320825E+09 |
Maximum of Months | 0.168183E+10 | 0.305571E+09 | 0.137626E+10 | 0.446978E+10 | 0.363724E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.149126E+10 | 0.935504E+09 | 0.555752E+09 | 0.191162E+10 | 0.184063E+10 |
February | 0.132767E+10 | 0.759488E+09 | 0.568185E+09 | 0.149934E+10 | 0.166060E+10 |
March | 0.183954E+10 | 0.946272E+09 | 0.893270E+09 | 0.239376E+10 | 0.162086E+10 |
April | 0.254114E+10 | 0.151455E+10 | 0.102659E+10 | 0.422508E+10 | 0.882259E+09 |
May | 0.272132E+10 | 0.161317E+10 | 0.110815E+10 | 0.484960E+10 | 0.646535E+09 |
June | 0.274500E+10 | 0.170570E+10 | 0.103930E+10 | 0.566235E+10 | 0.259544E+09 |
July | 0.239560E+10 | 0.135078E+10 | 0.104482E+10 | 0.499611E+10 | 0.204885E+09 |
August | 0.227364E+10 | 0.129756E+10 | 0.976078E+09 | 0.470723E+10 | 0.260883E+09 |
September | 0.180549E+10 | 0.870276E+09 | 0.935215E+09 | 0.358704E+10 | 0.370274E+09 |
October | 0.187396E+10 | 0.114048E+10 | 0.733484E+09 | 0.295074E+10 | 0.118351E+10 |
November | 0.139449E+10 | 0.837126E+09 | 0.557360E+09 | 0.176492E+10 | 0.167712E+10 |
December | 0.131379E+10 | 0.793301E+09 | 0.520486E+09 | 0.147841E+10 | 0.222896E+10 |
Annual Sum or Average | 0.237229E+11 | 0.137642E+11 | 0.995870E+10 | 0.400262E+11 | 0.128361E+11 |
Minimum of Months | 0.131379E+10 | 0.759488E+09 | 0.520486E+09 | 0.147841E+10 | 0.204885E+09 |
Maximum of Months | 0.274500E+10 | 0.170570E+10 | 0.110815E+10 | 0.566235E+10 | 0.222896E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.570147E+10 | 0.455360E+10 | 0.114787E+10 | 0.868610E+10 | 0.292756E+10 |
February | 0.325610E+10 | 0.219602E+10 | 0.106007E+10 | 0.442540E+10 | 0.255927E+10 |
March | 0.299960E+10 | 0.154495E+10 | 0.145465E+10 | 0.439706E+10 | 0.260668E+10 |
April | 0.247108E+10 | 0.998553E+09 | 0.147253E+10 | 0.470401E+10 | 0.146875E+10 |
May | 0.171108E+10 | 0.282688E+09 | 0.142839E+10 | 0.361874E+10 | 0.106840E+10 |
June | 0.141792E+10 | 0.109302E+09 | 0.130862E+10 | 0.403939E+10 | 0.424244E+09 |
July | 0.149716E+10 | 0.154892E+09 | 0.134227E+10 | 0.406269E+10 | 0.326659E+09 |
August | 0.182047E+10 | 0.503085E+09 | 0.131738E+10 | 0.468031E+10 | 0.411656E+09 |
September | 0.253850E+10 | 0.108298E+10 | 0.145552E+10 | 0.543228E+10 | 0.597738E+09 |
October | 0.417966E+10 | 0.289294E+10 | 0.128671E+10 | 0.702485E+10 | 0.187589E+10 |
November | 0.471375E+10 | 0.361049E+10 | 0.110326E+10 | 0.707110E+10 | 0.261896E+10 |
December | 0.530067E+10 | 0.419619E+10 | 0.110448E+10 | 0.768131E+10 | 0.348467E+10 |
Annual Sum or Average | 0.376074E+11 | 0.221257E+11 | 0.154818E+11 | 0.658232E+11 | 0.203705E+11 |
Minimum of Months | 0.141792E+10 | 0.109302E+09 | 0.106007E+10 | 0.361874E+10 | 0.326659E+09 |
Maximum of Months | 0.570147E+10 | 0.455360E+10 | 0.147253E+10 | 0.868610E+10 | 0.348467E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.155938E+10 | 0.969179E+09 | 0.590203E+09 | 0.227610E+10 | 0.202510E+10 |
February | 0.114100E+10 | 0.551603E+09 | 0.589398E+09 | 0.133211E+10 | 0.175447E+10 |
March | 0.167322E+10 | 0.797647E+09 | 0.875569E+09 | 0.226767E+10 | 0.173051E+10 |
April | 0.248640E+10 | 0.141831E+10 | 0.106808E+10 | 0.426582E+10 | 0.997123E+09 |
May | 0.257587E+10 | 0.144429E+10 | 0.113158E+10 | 0.472419E+10 | 0.744494E+09 |
June | 0.265007E+10 | 0.155867E+10 | 0.109141E+10 | 0.555677E+10 | 0.312013E+09 |
July | 0.199308E+10 | 0.930359E+09 | 0.106272E+10 | 0.433184E+10 | 0.236177E+09 |
August | 0.190058E+10 | 0.954507E+09 | 0.946071E+09 | 0.410537E+10 | 0.292704E+09 |
September | 0.160323E+10 | 0.673609E+09 | 0.929617E+09 | 0.328400E+10 | 0.407345E+09 |
October | 0.169511E+10 | 0.969260E+09 | 0.725854E+09 | 0.278541E+10 | 0.129379E+10 |
November | 0.151088E+10 | 0.912223E+09 | 0.598656E+09 | 0.213448E+10 | 0.181500E+10 |
December | 0.125830E+10 | 0.716434E+09 | 0.541863E+09 | 0.163685E+10 | 0.242243E+10 |
Annual Sum or Average | 0.220471E+11 | 0.118961E+11 | 0.101510E+11 | 0.387006E+11 | 0.140311E+11 |
Minimum of Months | 0.114100E+10 | 0.551603E+09 | 0.541863E+09 | 0.133211E+10 | 0.236177E+09 |
Maximum of Months | 0.265007E+10 | 0.155867E+10 | 0.113158E+10 | 0.555677E+10 | 0.242243E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 224.50 | 1025.75 | 258.53 | 0.00 | 258.53 | 0.00 | 0.00 |
February | 154.88 | 1004.93 | 294.58 | 0.00 | 294.58 | 0.00 | 0.00 |
March | 380.87 | 909.39 | 391.50 | 0.00 | 391.50 | 0.00 | 0.00 |
April | 800.52 | 515.81 | 476.99 | 4.95 | 472.04 | 0.00 | 0.00 |
May | 1096.54 | 354.57 | 558.36 | 44.71 | 513.65 | 0.00 | 0.00 |
June | 1713.75 | 153.70 | 648.85 | 117.89 | 530.96 | 0.00 | 0.00 |
July | 1459.13 | 118.56 | 553.35 | 57.65 | 495.70 | 0.00 | 0.00 |
August | 1212.03 | 148.00 | 446.65 | 11.10 | 435.56 | 0.00 | 0.00 |
September | 1007.65 | 221.15 | 421.41 | 0.11 | 421.30 | 0.00 | 0.00 |
October | 491.06 | 665.03 | 326.03 | 0.00 | 326.03 | 0.00 | 0.00 |
November | 220.36 | 951.95 | 271.65 | 0.00 | 271.65 | 0.00 | 0.00 |
December | 142.82 | 1244.95 | 241.49 | 0.00 | 241.49 | 0.00 | 0.00 |
Annual Sum or Average | 744.71 | 607.86 | 407.86 | 19.74 | 388.12 | 0.00 | 0.00 |
Minimum of Months | 142.82 | 118.56 | 241.49 | 0.00 | 241.49 | 0.00 | 0.00 |
Maximum of Months | 1713.75 | 1244.95 | 648.85 | 117.89 | 530.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 730.43 | 638.94 | 556.77 | 349.28 | 207.49 | 0.00 | 0.00 |
February | 632.54 | 633.62 | 548.81 | 313.94 | 234.86 | 0.00 | 0.00 |
March | 905.40 | 570.11 | 686.81 | 353.30 | 333.51 | 0.00 | 0.00 |
April | 1626.90 | 328.69 | 980.38 | 584.32 | 396.06 | 0.00 | 0.00 |
May | 1803.94 | 235.71 | 1016.03 | 602.29 | 413.74 | 0.00 | 0.00 |
June | 2173.72 | 98.24 | 1059.03 | 658.06 | 400.96 | 0.00 | 0.00 |
July | 1854.18 | 75.69 | 894.42 | 504.32 | 390.09 | 0.00 | 0.00 |
August | 1748.68 | 94.81 | 848.88 | 484.45 | 364.43 | 0.00 | 0.00 |
September | 1377.98 | 138.90 | 696.56 | 335.75 | 360.81 | 0.00 | 0.00 |
October | 1106.69 | 415.38 | 699.66 | 425.80 | 273.85 | 0.00 | 0.00 |
November | 696.15 | 598.48 | 538.00 | 322.97 | 215.03 | 0.00 | 0.00 |
December | 574.08 | 770.08 | 490.51 | 296.18 | 194.33 | 0.00 | 0.00 |
Annual Sum or Average | 1272.27 | 382.17 | 752.25 | 436.46 | 315.79 | 0.00 | 0.00 |
Minimum of Months | 574.08 | 75.69 | 490.51 | 296.18 | 194.33 | 0.00 | 0.00 |
Maximum of Months | 2173.72 | 770.08 | 1059.03 | 658.06 | 413.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3260.45 | 1020.99 | 2128.69 | 1700.12 | 428.57 | 0.00 | 0.00 |
February | 1846.12 | 975.63 | 1345.94 | 907.75 | 438.19 | 0.00 | 0.00 |
March | 1655.72 | 913.44 | 1119.92 | 576.82 | 543.10 | 0.00 | 0.00 |
April | 1810.93 | 541.29 | 953.35 | 385.24 | 568.10 | 0.00 | 0.00 |
May | 1345.61 | 385.05 | 638.84 | 105.54 | 533.30 | 0.00 | 0.00 |
June | 1547.93 | 158.86 | 547.04 | 42.17 | 504.87 | 0.00 | 0.00 |
July | 1504.61 | 119.44 | 558.97 | 57.83 | 501.14 | 0.00 | 0.00 |
August | 1737.37 | 148.53 | 679.68 | 187.83 | 491.85 | 0.00 | 0.00 |
September | 2087.56 | 222.92 | 979.36 | 417.82 | 561.54 | 0.00 | 0.00 |
October | 2627.54 | 658.32 | 1560.51 | 1080.10 | 480.40 | 0.00 | 0.00 |
November | 2745.37 | 939.02 | 1818.58 | 1392.93 | 425.64 | 0.00 | 0.00 |
December | 2893.11 | 1208.87 | 1979.04 | 1566.68 | 412.37 | 0.00 | 0.00 |
Annual Sum or Average | 2090.96 | 606.23 | 1192.52 | 701.60 | 490.92 | 0.00 | 0.00 |
Minimum of Months | 1345.61 | 119.44 | 547.04 | 42.17 | 412.37 | 0.00 | 0.00 |
Maximum of Months | 3260.45 | 1208.87 | 2128.69 | 1700.12 | 568.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 860.74 | 700.27 | 582.21 | 361.85 | 220.36 | 0.00 | 0.00 |
February | 559.69 | 666.29 | 471.64 | 228.01 | 243.63 | 0.00 | 0.00 |
March | 856.48 | 604.36 | 624.71 | 297.81 | 326.90 | 0.00 | 0.00 |
April | 1643.69 | 368.23 | 959.26 | 547.19 | 412.07 | 0.00 | 0.00 |
May | 1758.71 | 269.36 | 961.72 | 539.24 | 422.48 | 0.00 | 0.00 |
June | 2134.46 | 117.19 | 1022.40 | 601.34 | 421.07 | 0.00 | 0.00 |
July | 1608.22 | 86.60 | 744.13 | 347.36 | 396.77 | 0.00 | 0.00 |
August | 1525.99 | 105.93 | 709.59 | 356.37 | 353.22 | 0.00 | 0.00 |
September | 1262.50 | 152.07 | 618.53 | 259.88 | 358.65 | 0.00 | 0.00 |
October | 1044.64 | 450.75 | 632.88 | 361.88 | 271.00 | 0.00 | 0.00 |
November | 834.05 | 644.89 | 582.90 | 351.94 | 230.96 | 0.00 | 0.00 |
December | 624.01 | 835.43 | 469.79 | 267.49 | 202.31 | 0.00 | 0.00 |
Annual Sum or Average | 1228.92 | 415.79 | 699.11 | 377.22 | 321.89 | 0.00 | 0.00 |
Minimum of Months | 559.69 | 86.60 | 469.79 | 228.01 | 202.31 | 0.00 | 0.00 |
Maximum of Months | 2134.46 | 835.43 | 1022.40 | 601.34 | 422.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 211.59 | 1110.06 | 258.52 | 0.00 | 258.52 | 0.00 | 0.00 |
February | 154.34 | 1071.46 | 294.58 | 0.00 | 294.58 | 0.00 | 0.00 |
March | 393.20 | 931.99 | 391.50 | 0.00 | 391.50 | 0.00 | 0.00 |
April | 821.39 | 514.03 | 476.98 | 4.95 | 472.03 | 0.00 | 0.00 |
May | 1122.04 | 341.73 | 558.36 | 44.71 | 513.65 | 0.00 | 0.00 |
June | 1737.28 | 144.55 | 648.85 | 117.89 | 530.96 | 0.00 | 0.00 |
July | 1470.94 | 117.50 | 553.35 | 57.65 | 495.70 | 0.00 | 0.00 |
August | 1213.89 | 154.05 | 446.65 | 11.10 | 435.55 | 0.00 | 0.00 |
September | 1001.13 | 239.05 | 421.41 | 0.11 | 421.29 | 0.00 | 0.00 |
October | 472.19 | 747.20 | 326.03 | 0.00 | 326.03 | 0.00 | 0.00 |
November | 193.85 | 1088.89 | 271.65 | 0.00 | 271.65 | 0.00 | 0.00 |
December | 115.15 | 1400.53 | 241.49 | 0.00 | 241.49 | 0.00 | 0.00 |
Annual Sum or Average | 744.93 | 653.40 | 407.86 | 19.74 | 388.12 | 0.00 | 0.00 |
Minimum of Months | 115.15 | 117.50 | 241.49 | 0.00 | 241.49 | 0.00 | 0.00 |
Maximum of Months | 1737.28 | 1400.53 | 648.85 | 117.89 | 530.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 717.18 | 705.10 | 556.77 | 349.27 | 207.49 | 0.00 | 0.00 |
February | 631.01 | 688.50 | 548.80 | 313.94 | 234.86 | 0.00 | 0.00 |
March | 912.04 | 598.34 | 686.80 | 353.29 | 333.51 | 0.00 | 0.00 |
April | 1642.95 | 339.69 | 980.37 | 584.31 | 396.06 | 0.00 | 0.00 |
May | 1823.61 | 238.40 | 1016.02 | 602.28 | 413.73 | 0.00 | 0.00 |
June | 2191.21 | 99.35 | 1059.02 | 658.06 | 400.96 | 0.00 | 0.00 |
July | 1862.65 | 80.83 | 894.41 | 504.32 | 390.09 | 0.00 | 0.00 |
August | 1752.59 | 106.47 | 848.87 | 484.45 | 364.42 | 0.00 | 0.00 |
September | 1376.14 | 156.34 | 696.56 | 335.75 | 360.81 | 0.00 | 0.00 |
October | 1096.09 | 473.14 | 699.65 | 425.80 | 273.85 | 0.00 | 0.00 |
November | 674.19 | 690.00 | 537.99 | 322.96 | 215.03 | 0.00 | 0.00 |
December | 544.00 | 877.66 | 490.51 | 296.18 | 194.33 | 0.00 | 0.00 |
Annual Sum or Average | 1271.66 | 420.05 | 752.24 | 436.46 | 315.79 | 0.00 | 0.00 |
Minimum of Months | 544.00 | 80.83 | 490.51 | 296.18 | 194.33 | 0.00 | 0.00 |
Maximum of Months | 2191.21 | 877.66 | 1059.02 | 658.06 | 413.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3255.60 | 1156.58 | 2128.71 | 1700.14 | 428.57 | 0.00 | 0.00 |
February | 1864.84 | 1060.55 | 1345.95 | 907.76 | 438.20 | 0.00 | 0.00 |
March | 1681.35 | 954.10 | 1119.93 | 576.82 | 543.11 | 0.00 | 0.00 |
April | 1833.83 | 553.92 | 953.36 | 385.25 | 568.11 | 0.00 | 0.00 |
May | 1367.29 | 378.02 | 638.85 | 105.54 | 533.30 | 0.00 | 0.00 |
June | 1555.29 | 153.54 | 547.04 | 42.17 | 504.87 | 0.00 | 0.00 |
July | 1503.34 | 123.21 | 558.98 | 57.83 | 501.15 | 0.00 | 0.00 |
August | 1725.54 | 165.18 | 679.69 | 187.83 | 491.86 | 0.00 | 0.00 |
September | 2072.63 | 256.05 | 979.37 | 417.82 | 561.55 | 0.00 | 0.00 |
October | 2616.94 | 754.35 | 1560.52 | 1080.11 | 480.41 | 0.00 | 0.00 |
November | 2731.19 | 1087.60 | 1818.60 | 1392.95 | 425.64 | 0.00 | 0.00 |
December | 2876.44 | 1383.82 | 1979.07 | 1566.70 | 412.37 | 0.00 | 0.00 |
Annual Sum or Average | 2092.67 | 667.40 | 1192.54 | 701.61 | 490.93 | 0.00 | 0.00 |
Minimum of Months | 1367.29 | 123.21 | 547.04 | 42.17 | 412.37 | 0.00 | 0.00 |
Maximum of Months | 3255.60 | 1383.82 | 2128.71 | 1700.14 | 568.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 853.13 | 775.97 | 582.20 | 361.85 | 220.36 | 0.00 | 0.00 |
February | 561.84 | 721.94 | 471.64 | 228.01 | 243.63 | 0.00 | 0.00 |
March | 865.52 | 635.34 | 624.70 | 297.80 | 326.90 | 0.00 | 0.00 |
April | 1658.30 | 384.08 | 959.25 | 547.18 | 412.07 | 0.00 | 0.00 |
May | 1775.72 | 275.62 | 961.71 | 539.23 | 422.48 | 0.00 | 0.00 |
June | 2149.77 | 120.55 | 1022.40 | 601.33 | 421.07 | 0.00 | 0.00 |
July | 1614.18 | 92.11 | 744.12 | 347.35 | 396.77 | 0.00 | 0.00 |
August | 1526.89 | 117.37 | 709.59 | 356.37 | 353.22 | 0.00 | 0.00 |
September | 1259.26 | 170.82 | 618.52 | 259.88 | 358.65 | 0.00 | 0.00 |
October | 1033.98 | 515.71 | 632.88 | 361.88 | 271.00 | 0.00 | 0.00 |
November | 817.99 | 748.50 | 582.90 | 351.93 | 230.96 | 0.00 | 0.00 |
December | 606.79 | 949.37 | 469.79 | 267.48 | 202.31 | 0.00 | 0.00 |
Annual Sum or Average | 1229.74 | 457.91 | 699.10 | 377.22 | 321.89 | 0.00 | 0.00 |
Minimum of Months | 561.84 | 92.11 | 469.79 | 228.01 | 202.31 | 0.00 | 0.00 |
Maximum of Months | 2149.77 | 949.37 | 1022.40 | 601.33 | 422.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 203.69 | 1116.69 | 258.53 | 0.00 | 258.53 | 0.00 | 0.00 |
February | 139.36 | 1102.26 | 294.58 | 0.00 | 294.58 | 0.00 | 0.00 |
March | 363.68 | 976.43 | 391.50 | 0.00 | 391.50 | 0.00 | 0.00 |
April | 801.03 | 540.93 | 476.99 | 4.95 | 472.04 | 0.00 | 0.00 |
May | 1099.65 | 364.23 | 558.36 | 44.71 | 513.65 | 0.00 | 0.00 |
June | 1724.45 | 156.18 | 648.85 | 117.89 | 530.96 | 0.00 | 0.00 |
July | 1471.48 | 119.78 | 553.35 | 57.65 | 495.70 | 0.00 | 0.00 |
August | 1220.45 | 151.89 | 446.65 | 11.10 | 435.56 | 0.00 | 0.00 |
September | 1013.00 | 228.69 | 421.41 | 0.11 | 421.30 | 0.00 | 0.00 |
October | 481.50 | 716.99 | 326.03 | 0.00 | 326.03 | 0.00 | 0.00 |
November | 201.52 | 1042.38 | 271.65 | 0.00 | 271.65 | 0.00 | 0.00 |
December | 121.50 | 1357.99 | 241.49 | 0.00 | 241.49 | 0.00 | 0.00 |
Annual Sum or Average | 739.51 | 654.34 | 407.86 | 19.74 | 388.12 | 0.00 | 0.00 |
Minimum of Months | 121.50 | 119.78 | 241.49 | 0.00 | 241.49 | 0.00 | 0.00 |
Maximum of Months | 1724.45 | 1357.99 | 648.85 | 117.89 | 530.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 713.72 | 687.21 | 556.77 | 349.28 | 207.49 | 0.00 | 0.00 |
February | 619.77 | 686.43 | 548.81 | 313.94 | 234.86 | 0.00 | 0.00 |
March | 893.73 | 605.16 | 686.81 | 353.30 | 333.51 | 0.00 | 0.00 |
April | 1630.05 | 340.38 | 980.38 | 584.32 | 396.06 | 0.00 | 0.00 |
May | 1810.63 | 241.39 | 1016.03 | 602.29 | 413.74 | 0.00 | 0.00 |
June | 2184.55 | 100.13 | 1059.03 | 658.06 | 400.96 | 0.00 | 0.00 |
July | 1865.33 | 76.50 | 894.42 | 504.32 | 390.09 | 0.00 | 0.00 |
August | 1757.48 | 97.40 | 848.88 | 484.45 | 364.43 | 0.00 | 0.00 |
September | 1383.89 | 142.85 | 696.56 | 335.75 | 360.81 | 0.00 | 0.00 |
October | 1101.68 | 441.87 | 699.66 | 425.80 | 273.85 | 0.00 | 0.00 |
November | 680.91 | 647.04 | 538.00 | 322.97 | 215.03 | 0.00 | 0.00 |
December | 551.97 | 832.20 | 490.51 | 296.18 | 194.33 | 0.00 | 0.00 |
Annual Sum or Average | 1269.22 | 407.03 | 752.25 | 436.46 | 315.79 | 0.00 | 0.00 |
Minimum of Months | 551.97 | 76.50 | 490.51 | 296.18 | 194.33 | 0.00 | 0.00 |
Maximum of Months | 2184.55 | 832.20 | 1059.03 | 658.06 | 413.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3243.02 | 1093.03 | 2128.69 | 1700.12 | 428.57 | 0.00 | 0.00 |
February | 1829.28 | 1057.90 | 1345.94 | 907.75 | 438.19 | 0.00 | 0.00 |
March | 1641.67 | 973.22 | 1119.92 | 576.82 | 543.10 | 0.00 | 0.00 |
April | 1814.82 | 566.65 | 953.35 | 385.24 | 568.10 | 0.00 | 0.00 |
May | 1351.08 | 398.89 | 638.84 | 105.54 | 533.30 | 0.00 | 0.00 |
June | 1558.41 | 163.67 | 547.04 | 42.17 | 504.87 | 0.00 | 0.00 |
July | 1516.83 | 121.96 | 558.97 | 57.83 | 501.14 | 0.00 | 0.00 |
August | 1747.43 | 153.69 | 679.68 | 187.83 | 491.85 | 0.00 | 0.00 |
September | 2095.79 | 230.61 | 979.36 | 417.82 | 561.54 | 0.00 | 0.00 |
October | 2622.78 | 700.38 | 1560.51 | 1080.10 | 480.40 | 0.00 | 0.00 |
November | 2728.05 | 1010.40 | 1818.58 | 1392.93 | 425.64 | 0.00 | 0.00 |
December | 2867.87 | 1301.03 | 1979.04 | 1566.68 | 412.37 | 0.00 | 0.00 |
Annual Sum or Average | 2087.24 | 645.94 | 1192.52 | 701.60 | 490.92 | 0.00 | 0.00 |
Minimum of Months | 1351.08 | 121.96 | 547.04 | 42.17 | 412.37 | 0.00 | 0.00 |
Maximum of Months | 3243.02 | 1301.03 | 2128.69 | 1700.12 | 568.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 849.80 | 756.08 | 582.21 | 361.85 | 220.36 | 0.00 | 0.00 |
February | 550.64 | 725.23 | 471.64 | 228.01 | 243.63 | 0.00 | 0.00 |
March | 846.65 | 646.10 | 624.71 | 297.81 | 326.90 | 0.00 | 0.00 |
April | 1645.77 | 384.69 | 959.26 | 547.19 | 412.07 | 0.00 | 0.00 |
May | 1763.81 | 277.96 | 961.72 | 539.24 | 422.48 | 0.00 | 0.00 |
June | 2143.82 | 120.38 | 1022.40 | 601.34 | 421.07 | 0.00 | 0.00 |
July | 1617.32 | 88.18 | 744.13 | 347.36 | 396.77 | 0.00 | 0.00 |
August | 1532.77 | 109.28 | 709.59 | 356.37 | 353.22 | 0.00 | 0.00 |
September | 1266.97 | 157.15 | 618.53 | 259.88 | 358.65 | 0.00 | 0.00 |
October | 1039.95 | 483.04 | 632.88 | 361.88 | 271.00 | 0.00 | 0.00 |
November | 823.49 | 700.23 | 582.90 | 351.94 | 230.96 | 0.00 | 0.00 |
December | 611.13 | 904.43 | 469.79 | 267.49 | 202.31 | 0.00 | 0.00 |
Annual Sum or Average | 1227.19 | 444.92 | 699.11 | 377.22 | 321.89 | 0.00 | 0.00 |
Minimum of Months | 550.64 | 88.18 | 469.79 | 228.01 | 202.31 | 0.00 | 0.00 |
Maximum of Months | 2143.82 | 904.43 | 1022.40 | 601.34 | 422.48 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.601311E+09 | 0.274736E+10 | 0.692434E+09 | 0.00 | 0.692434E+09 | 0.00 | 0.00 |
February | 0.374690E+09 | 0.243114E+10 | 0.712656E+09 | 0.00 | 0.712656E+09 | 0.00 | 0.00 |
March | 0.102011E+10 | 0.243570E+10 | 0.104860E+10 | 0.00 | 0.104860E+10 | 0.00 | 0.00 |
April | 0.207494E+10 | 0.133697E+10 | 0.123635E+10 | 12830113.86 | 0.122352E+10 | 0.00 | 0.00 |
May | 0.293698E+10 | 0.949672E+09 | 0.149552E+10 | 0.119747E+09 | 0.137577E+10 | 0.00 | 0.00 |
June | 0.444204E+10 | 0.398394E+09 | 0.168183E+10 | 0.305571E+09 | 0.137626E+10 | 0.00 | 0.00 |
July | 0.390815E+10 | 0.317558E+09 | 0.148209E+10 | 0.154404E+09 | 0.132768E+10 | 0.00 | 0.00 |
August | 0.324630E+10 | 0.396397E+09 | 0.119631E+10 | 29719197.80 | 0.116659E+10 | 0.00 | 0.00 |
September | 0.261183E+10 | 0.573216E+09 | 0.109229E+10 | 291589.31 | 0.109200E+10 | 0.00 | 0.00 |
October | 0.131526E+10 | 0.178121E+10 | 0.873252E+09 | 0.00 | 0.873252E+09 | 0.00 | 0.00 |
November | 0.571178E+09 | 0.246746E+10 | 0.704109E+09 | 0.00 | 0.704109E+09 | 0.00 | 0.00 |
December | 0.382525E+09 | 0.333448E+10 | 0.646797E+09 | 0.00 | 0.646797E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.234853E+11 | 0.191696E+11 | 0.128622E+11 | 0.622563E+09 | 0.122397E+11 | 0.00 | 0.00 |
Minimum of Months | 0.374690E+09 | 0.317558E+09 | 0.646797E+09 | 0.00 | 0.646797E+09 | 0.00 | 0.00 |
Maximum of Months | 0.444204E+10 | 0.333448E+10 | 0.168183E+10 | 0.305571E+09 | 0.137626E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.195637E+10 | 0.171134E+10 | 0.149126E+10 | 0.935504E+09 | 0.555752E+09 | 0.00 | 0.00 |
February | 0.153025E+10 | 0.153285E+10 | 0.132767E+10 | 0.759488E+09 | 0.568185E+09 | 0.00 | 0.00 |
March | 0.242503E+10 | 0.152698E+10 | 0.183954E+10 | 0.946272E+09 | 0.893270E+09 | 0.00 | 0.00 |
April | 0.421691E+10 | 0.851971E+09 | 0.254114E+10 | 0.151455E+10 | 0.102659E+10 | 0.00 | 0.00 |
May | 0.483167E+10 | 0.631318E+09 | 0.272132E+10 | 0.161317E+10 | 0.110815E+10 | 0.00 | 0.00 |
June | 0.563429E+10 | 0.254636E+09 | 0.274500E+10 | 0.170570E+10 | 0.103930E+10 | 0.00 | 0.00 |
July | 0.496624E+10 | 0.202725E+09 | 0.239560E+10 | 0.135078E+10 | 0.104482E+10 | 0.00 | 0.00 |
August | 0.468365E+10 | 0.253935E+09 | 0.227364E+10 | 0.129756E+10 | 0.976078E+09 | 0.00 | 0.00 |
September | 0.357172E+10 | 0.360035E+09 | 0.180549E+10 | 0.870276E+09 | 0.935215E+09 | 0.00 | 0.00 |
October | 0.296415E+10 | 0.111254E+10 | 0.187396E+10 | 0.114048E+10 | 0.733484E+09 | 0.00 | 0.00 |
November | 0.180441E+10 | 0.155126E+10 | 0.139449E+10 | 0.837126E+09 | 0.557360E+09 | 0.00 | 0.00 |
December | 0.153762E+10 | 0.206258E+10 | 0.131379E+10 | 0.793301E+09 | 0.520486E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.401223E+11 | 0.120522E+11 | 0.237229E+11 | 0.137642E+11 | 0.995870E+10 | 0.00 | 0.00 |
Minimum of Months | 0.153025E+10 | 0.202725E+09 | 0.131379E+10 | 0.759488E+09 | 0.520486E+09 | 0.00 | 0.00 |
Maximum of Months | 0.563429E+10 | 0.206258E+10 | 0.274500E+10 | 0.170570E+10 | 0.110815E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.873279E+10 | 0.273461E+10 | 0.570147E+10 | 0.455360E+10 | 0.114787E+10 | 0.00 | 0.00 |
February | 0.446613E+10 | 0.236024E+10 | 0.325610E+10 | 0.219602E+10 | 0.106007E+10 | 0.00 | 0.00 |
March | 0.443467E+10 | 0.244655E+10 | 0.299960E+10 | 0.154495E+10 | 0.145465E+10 | 0.00 | 0.00 |
April | 0.469392E+10 | 0.140302E+10 | 0.247108E+10 | 0.998553E+09 | 0.147253E+10 | 0.00 | 0.00 |
May | 0.360408E+10 | 0.103131E+10 | 0.171108E+10 | 0.282688E+09 | 0.142839E+10 | 0.00 | 0.00 |
June | 0.401222E+10 | 0.411775E+09 | 0.141792E+10 | 0.109302E+09 | 0.130862E+10 | 0.00 | 0.00 |
July | 0.402995E+10 | 0.319919E+09 | 0.149716E+10 | 0.154892E+09 | 0.134227E+10 | 0.00 | 0.00 |
August | 0.465338E+10 | 0.397820E+09 | 0.182047E+10 | 0.503085E+09 | 0.131738E+10 | 0.00 | 0.00 |
September | 0.541097E+10 | 0.577797E+09 | 0.253850E+10 | 0.108298E+10 | 0.145552E+10 | 0.00 | 0.00 |
October | 0.703760E+10 | 0.176324E+10 | 0.417966E+10 | 0.289294E+10 | 0.128671E+10 | 0.00 | 0.00 |
November | 0.711601E+10 | 0.243393E+10 | 0.471375E+10 | 0.361049E+10 | 0.110326E+10 | 0.00 | 0.00 |
December | 0.774891E+10 | 0.323784E+10 | 0.530067E+10 | 0.419619E+10 | 0.110448E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.659406E+11 | 0.191180E+11 | 0.376074E+11 | 0.221257E+11 | 0.154818E+11 | 0.00 | 0.00 |
Minimum of Months | 0.360408E+10 | 0.319919E+09 | 0.141792E+10 | 0.109302E+09 | 0.106007E+10 | 0.00 | 0.00 |
Maximum of Months | 0.873279E+10 | 0.323784E+10 | 0.570147E+10 | 0.455360E+10 | 0.147253E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.230542E+10 | 0.187561E+10 | 0.155938E+10 | 0.969179E+09 | 0.590203E+09 | 0.00 | 0.00 |
February | 0.135399E+10 | 0.161189E+10 | 0.114100E+10 | 0.551603E+09 | 0.589398E+09 | 0.00 | 0.00 |
March | 0.229399E+10 | 0.161872E+10 | 0.167322E+10 | 0.797647E+09 | 0.875569E+09 | 0.00 | 0.00 |
April | 0.426045E+10 | 0.954448E+09 | 0.248640E+10 | 0.141831E+10 | 0.106808E+10 | 0.00 | 0.00 |
May | 0.471053E+10 | 0.721455E+09 | 0.257587E+10 | 0.144429E+10 | 0.113158E+10 | 0.00 | 0.00 |
June | 0.553252E+10 | 0.303769E+09 | 0.265007E+10 | 0.155867E+10 | 0.109141E+10 | 0.00 | 0.00 |
July | 0.430744E+10 | 0.231947E+09 | 0.199308E+10 | 0.930359E+09 | 0.106272E+10 | 0.00 | 0.00 |
August | 0.408721E+10 | 0.283716E+09 | 0.190058E+10 | 0.954507E+09 | 0.946071E+09 | 0.00 | 0.00 |
September | 0.327239E+10 | 0.394154E+09 | 0.160323E+10 | 0.673609E+09 | 0.929617E+09 | 0.00 | 0.00 |
October | 0.279797E+10 | 0.120730E+10 | 0.169511E+10 | 0.969260E+09 | 0.725854E+09 | 0.00 | 0.00 |
November | 0.216187E+10 | 0.167156E+10 | 0.151088E+10 | 0.912223E+09 | 0.598656E+09 | 0.00 | 0.00 |
December | 0.167134E+10 | 0.223762E+10 | 0.125830E+10 | 0.716434E+09 | 0.541863E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.387551E+11 | 0.131122E+11 | 0.220471E+11 | 0.118961E+11 | 0.101510E+11 | 0.00 | 0.00 |
Minimum of Months | 0.135399E+10 | 0.231947E+09 | 0.114100E+10 | 0.551603E+09 | 0.541863E+09 | 0.00 | 0.00 |
Maximum of Months | 0.553252E+10 | 0.223762E+10 | 0.265007E+10 | 0.155867E+10 | 0.113158E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.566718E+09 | 0.297318E+10 | 0.692431E+09 | 0.00 | 0.692431E+09 | 0.00 | 0.00 |
February | 0.373368E+09 | 0.259208E+10 | 0.712652E+09 | 0.00 | 0.712652E+09 | 0.00 | 0.00 |
March | 0.105314E+10 | 0.249625E+10 | 0.104859E+10 | 0.00 | 0.104859E+10 | 0.00 | 0.00 |
April | 0.212903E+10 | 0.133236E+10 | 0.123634E+10 | 12830047.38 | 0.122351E+10 | 0.00 | 0.00 |
May | 0.300527E+10 | 0.915292E+09 | 0.149551E+10 | 0.119747E+09 | 0.137576E+10 | 0.00 | 0.00 |
June | 0.450303E+10 | 0.374667E+09 | 0.168182E+10 | 0.305569E+09 | 0.137625E+10 | 0.00 | 0.00 |
July | 0.393976E+10 | 0.314724E+09 | 0.148208E+10 | 0.154403E+09 | 0.132768E+10 | 0.00 | 0.00 |
August | 0.325129E+10 | 0.412595E+09 | 0.119631E+10 | 29719043.80 | 0.116659E+10 | 0.00 | 0.00 |
September | 0.259494E+10 | 0.619627E+09 | 0.109229E+10 | 291587.80 | 0.109200E+10 | 0.00 | 0.00 |
October | 0.126471E+10 | 0.200130E+10 | 0.873247E+09 | 0.00 | 0.873247E+09 | 0.00 | 0.00 |
November | 0.502465E+09 | 0.282239E+10 | 0.704105E+09 | 0.00 | 0.704105E+09 | 0.00 | 0.00 |
December | 0.308431E+09 | 0.375118E+10 | 0.646794E+09 | 0.00 | 0.646794E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.234921E+11 | 0.206056E+11 | 0.128622E+11 | 0.622560E+09 | 0.122396E+11 | 0.00 | 0.00 |
Minimum of Months | 0.308431E+09 | 0.314724E+09 | 0.646794E+09 | 0.00 | 0.646794E+09 | 0.00 | 0.00 |
Maximum of Months | 0.450303E+10 | 0.375118E+10 | 0.168182E+10 | 0.305569E+09 | 0.137625E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.192089E+10 | 0.188855E+10 | 0.149124E+10 | 0.935495E+09 | 0.555750E+09 | 0.00 | 0.00 |
February | 0.152653E+10 | 0.166562E+10 | 0.132766E+10 | 0.759480E+09 | 0.568182E+09 | 0.00 | 0.00 |
March | 0.244281E+10 | 0.160260E+10 | 0.183953E+10 | 0.946262E+09 | 0.893265E+09 | 0.00 | 0.00 |
April | 0.425852E+10 | 0.880475E+09 | 0.254112E+10 | 0.151453E+10 | 0.102659E+10 | 0.00 | 0.00 |
May | 0.488436E+10 | 0.638537E+09 | 0.272130E+10 | 0.161316E+10 | 0.110815E+10 | 0.00 | 0.00 |
June | 0.567963E+10 | 0.257507E+09 | 0.274498E+10 | 0.170568E+10 | 0.103930E+10 | 0.00 | 0.00 |
July | 0.498893E+10 | 0.216495E+09 | 0.239559E+10 | 0.135077E+10 | 0.104482E+10 | 0.00 | 0.00 |
August | 0.469413E+10 | 0.285176E+09 | 0.227362E+10 | 0.129755E+10 | 0.976073E+09 | 0.00 | 0.00 |
September | 0.356695E+10 | 0.405246E+09 | 0.180548E+10 | 0.870267E+09 | 0.935210E+09 | 0.00 | 0.00 |
October | 0.293576E+10 | 0.126726E+10 | 0.187394E+10 | 0.114046E+10 | 0.733480E+09 | 0.00 | 0.00 |
November | 0.174750E+10 | 0.178849E+10 | 0.139448E+10 | 0.837118E+09 | 0.557357E+09 | 0.00 | 0.00 |
December | 0.145704E+10 | 0.235073E+10 | 0.131378E+10 | 0.793293E+09 | 0.520484E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.401030E+11 | 0.132467E+11 | 0.237227E+11 | 0.137641E+11 | 0.995865E+10 | 0.00 | 0.00 |
Minimum of Months | 0.145704E+10 | 0.216495E+09 | 0.131378E+10 | 0.759480E+09 | 0.520484E+09 | 0.00 | 0.00 |
Maximum of Months | 0.567963E+10 | 0.235073E+10 | 0.274498E+10 | 0.170568E+10 | 0.110815E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.871979E+10 | 0.309779E+10 | 0.570153E+10 | 0.455365E+10 | 0.114788E+10 | 0.00 | 0.00 |
February | 0.451143E+10 | 0.256567E+10 | 0.325613E+10 | 0.219605E+10 | 0.106008E+10 | 0.00 | 0.00 |
March | 0.450333E+10 | 0.255546E+10 | 0.299963E+10 | 0.154496E+10 | 0.145466E+10 | 0.00 | 0.00 |
April | 0.475329E+10 | 0.143577E+10 | 0.247110E+10 | 0.998564E+09 | 0.147253E+10 | 0.00 | 0.00 |
May | 0.366215E+10 | 0.101249E+10 | 0.171109E+10 | 0.282692E+09 | 0.142840E+10 | 0.00 | 0.00 |
June | 0.403131E+10 | 0.397982E+09 | 0.141792E+10 | 0.109304E+09 | 0.130862E+10 | 0.00 | 0.00 |
July | 0.402655E+10 | 0.330016E+09 | 0.149717E+10 | 0.154894E+09 | 0.134227E+10 | 0.00 | 0.00 |
August | 0.462167E+10 | 0.442418E+09 | 0.182048E+10 | 0.503091E+09 | 0.131739E+10 | 0.00 | 0.00 |
September | 0.537226E+10 | 0.663686E+09 | 0.253852E+10 | 0.108300E+10 | 0.145553E+10 | 0.00 | 0.00 |
October | 0.700920E+10 | 0.202045E+10 | 0.417970E+10 | 0.289298E+10 | 0.128672E+10 | 0.00 | 0.00 |
November | 0.707924E+10 | 0.281906E+10 | 0.471380E+10 | 0.361053E+10 | 0.110327E+10 | 0.00 | 0.00 |
December | 0.770425E+10 | 0.370642E+10 | 0.530073E+10 | 0.419624E+10 | 0.110449E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.659944E+11 | 0.210472E+11 | 0.376078E+11 | 0.221260E+11 | 0.154818E+11 | 0.00 | 0.00 |
Minimum of Months | 0.366215E+10 | 0.330016E+09 | 0.141792E+10 | 0.109304E+09 | 0.106008E+10 | 0.00 | 0.00 |
Maximum of Months | 0.871979E+10 | 0.370642E+10 | 0.570153E+10 | 0.455365E+10 | 0.147253E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.228501E+10 | 0.207835E+10 | 0.155937E+10 | 0.969169E+09 | 0.590200E+09 | 0.00 | 0.00 |
February | 0.135921E+10 | 0.174651E+10 | 0.114099E+10 | 0.551598E+09 | 0.589395E+09 | 0.00 | 0.00 |
March | 0.231820E+10 | 0.170169E+10 | 0.167320E+10 | 0.797639E+09 | 0.875565E+09 | 0.00 | 0.00 |
April | 0.429833E+10 | 0.995524E+09 | 0.248638E+10 | 0.141830E+10 | 0.106808E+10 | 0.00 | 0.00 |
May | 0.475609E+10 | 0.738231E+09 | 0.257585E+10 | 0.144428E+10 | 0.113158E+10 | 0.00 | 0.00 |
June | 0.557221E+10 | 0.312462E+09 | 0.265005E+10 | 0.155865E+10 | 0.109140E+10 | 0.00 | 0.00 |
July | 0.432343E+10 | 0.246711E+09 | 0.199306E+10 | 0.930349E+09 | 0.106271E+10 | 0.00 | 0.00 |
August | 0.408963E+10 | 0.314357E+09 | 0.190056E+10 | 0.954497E+09 | 0.946067E+09 | 0.00 | 0.00 |
September | 0.326399E+10 | 0.442774E+09 | 0.160321E+10 | 0.673602E+09 | 0.929612E+09 | 0.00 | 0.00 |
October | 0.276942E+10 | 0.138127E+10 | 0.169510E+10 | 0.969251E+09 | 0.725851E+09 | 0.00 | 0.00 |
November | 0.212023E+10 | 0.194010E+10 | 0.151087E+10 | 0.912214E+09 | 0.598654E+09 | 0.00 | 0.00 |
December | 0.162523E+10 | 0.254279E+10 | 0.125829E+10 | 0.716427E+09 | 0.541860E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.387810E+11 | 0.144408E+11 | 0.220469E+11 | 0.118960E+11 | 0.101510E+11 | 0.00 | 0.00 |
Minimum of Months | 0.135921E+10 | 0.246711E+09 | 0.114099E+10 | 0.551598E+09 | 0.541860E+09 | 0.00 | 0.00 |
Maximum of Months | 0.557221E+10 | 0.254279E+10 | 0.265005E+10 | 0.155865E+10 | 0.113158E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.545554E+09 | 0.299094E+10 | 0.692434E+09 | 0.00 | 0.692434E+09 | 0.00 | 0.00 |
February | 0.337133E+09 | 0.266658E+10 | 0.712656E+09 | 0.00 | 0.712656E+09 | 0.00 | 0.00 |
March | 0.974068E+09 | 0.261528E+10 | 0.104860E+10 | 0.00 | 0.104860E+10 | 0.00 | 0.00 |
April | 0.207628E+10 | 0.140208E+10 | 0.123635E+10 | 12830113.86 | 0.122352E+10 | 0.00 | 0.00 |
May | 0.294529E+10 | 0.975561E+09 | 0.149552E+10 | 0.119747E+09 | 0.137577E+10 | 0.00 | 0.00 |
June | 0.446978E+10 | 0.404825E+09 | 0.168183E+10 | 0.305571E+09 | 0.137626E+10 | 0.00 | 0.00 |
July | 0.394120E+10 | 0.320825E+09 | 0.148209E+10 | 0.154404E+09 | 0.132768E+10 | 0.00 | 0.00 |
August | 0.326884E+10 | 0.406832E+09 | 0.119631E+10 | 29719197.80 | 0.116659E+10 | 0.00 | 0.00 |
September | 0.262569E+10 | 0.592774E+09 | 0.109229E+10 | 291589.31 | 0.109200E+10 | 0.00 | 0.00 |
October | 0.128965E+10 | 0.192039E+10 | 0.873252E+09 | 0.00 | 0.873252E+09 | 0.00 | 0.00 |
November | 0.522331E+09 | 0.270186E+10 | 0.704109E+09 | 0.00 | 0.704109E+09 | 0.00 | 0.00 |
December | 0.325430E+09 | 0.363724E+10 | 0.646797E+09 | 0.00 | 0.646797E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.233212E+11 | 0.206352E+11 | 0.128622E+11 | 0.622563E+09 | 0.122397E+11 | 0.00 | 0.00 |
Minimum of Months | 0.325430E+09 | 0.320825E+09 | 0.646797E+09 | 0.00 | 0.646797E+09 | 0.00 | 0.00 |
Maximum of Months | 0.446978E+10 | 0.363724E+10 | 0.168183E+10 | 0.305571E+09 | 0.137626E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.191162E+10 | 0.184063E+10 | 0.149126E+10 | 0.935504E+09 | 0.555752E+09 | 0.00 | 0.00 |
February | 0.149934E+10 | 0.166060E+10 | 0.132767E+10 | 0.759488E+09 | 0.568185E+09 | 0.00 | 0.00 |
March | 0.239376E+10 | 0.162086E+10 | 0.183954E+10 | 0.946272E+09 | 0.893270E+09 | 0.00 | 0.00 |
April | 0.422508E+10 | 0.882259E+09 | 0.254114E+10 | 0.151455E+10 | 0.102659E+10 | 0.00 | 0.00 |
May | 0.484960E+10 | 0.646535E+09 | 0.272132E+10 | 0.161317E+10 | 0.110815E+10 | 0.00 | 0.00 |
June | 0.566235E+10 | 0.259544E+09 | 0.274500E+10 | 0.170570E+10 | 0.103930E+10 | 0.00 | 0.00 |
July | 0.499611E+10 | 0.204885E+09 | 0.239560E+10 | 0.135078E+10 | 0.104482E+10 | 0.00 | 0.00 |
August | 0.470723E+10 | 0.260883E+09 | 0.227364E+10 | 0.129756E+10 | 0.976078E+09 | 0.00 | 0.00 |
September | 0.358704E+10 | 0.370274E+09 | 0.180549E+10 | 0.870276E+09 | 0.935215E+09 | 0.00 | 0.00 |
October | 0.295074E+10 | 0.118351E+10 | 0.187396E+10 | 0.114048E+10 | 0.733484E+09 | 0.00 | 0.00 |
November | 0.176492E+10 | 0.167712E+10 | 0.139449E+10 | 0.837126E+09 | 0.557360E+09 | 0.00 | 0.00 |
December | 0.147841E+10 | 0.222896E+10 | 0.131379E+10 | 0.793301E+09 | 0.520486E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.400262E+11 | 0.128361E+11 | 0.237229E+11 | 0.137642E+11 | 0.995870E+10 | 0.00 | 0.00 |
Minimum of Months | 0.147841E+10 | 0.204885E+09 | 0.131379E+10 | 0.759488E+09 | 0.520486E+09 | 0.00 | 0.00 |
Maximum of Months | 0.566235E+10 | 0.222896E+10 | 0.274500E+10 | 0.170570E+10 | 0.110815E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.868610E+10 | 0.292756E+10 | 0.570147E+10 | 0.455360E+10 | 0.114787E+10 | 0.00 | 0.00 |
February | 0.442540E+10 | 0.255927E+10 | 0.325610E+10 | 0.219602E+10 | 0.106007E+10 | 0.00 | 0.00 |
March | 0.439706E+10 | 0.260668E+10 | 0.299960E+10 | 0.154495E+10 | 0.145465E+10 | 0.00 | 0.00 |
April | 0.470401E+10 | 0.146875E+10 | 0.247108E+10 | 0.998553E+09 | 0.147253E+10 | 0.00 | 0.00 |
May | 0.361874E+10 | 0.106840E+10 | 0.171108E+10 | 0.282688E+09 | 0.142839E+10 | 0.00 | 0.00 |
June | 0.403939E+10 | 0.424244E+09 | 0.141792E+10 | 0.109302E+09 | 0.130862E+10 | 0.00 | 0.00 |
July | 0.406269E+10 | 0.326659E+09 | 0.149716E+10 | 0.154892E+09 | 0.134227E+10 | 0.00 | 0.00 |
August | 0.468031E+10 | 0.411656E+09 | 0.182047E+10 | 0.503085E+09 | 0.131738E+10 | 0.00 | 0.00 |
September | 0.543228E+10 | 0.597738E+09 | 0.253850E+10 | 0.108298E+10 | 0.145552E+10 | 0.00 | 0.00 |
October | 0.702485E+10 | 0.187589E+10 | 0.417966E+10 | 0.289294E+10 | 0.128671E+10 | 0.00 | 0.00 |
November | 0.707110E+10 | 0.261896E+10 | 0.471375E+10 | 0.361049E+10 | 0.110326E+10 | 0.00 | 0.00 |
December | 0.768131E+10 | 0.348467E+10 | 0.530067E+10 | 0.419619E+10 | 0.110448E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.658232E+11 | 0.203705E+11 | 0.376074E+11 | 0.221257E+11 | 0.154818E+11 | 0.00 | 0.00 |
Minimum of Months | 0.361874E+10 | 0.326659E+09 | 0.141792E+10 | 0.109302E+09 | 0.106007E+10 | 0.00 | 0.00 |
Maximum of Months | 0.868610E+10 | 0.348467E+10 | 0.570147E+10 | 0.455360E+10 | 0.147253E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.227610E+10 | 0.202510E+10 | 0.155938E+10 | 0.969179E+09 | 0.590203E+09 | 0.00 | 0.00 |
February | 0.133211E+10 | 0.175447E+10 | 0.114100E+10 | 0.551603E+09 | 0.589398E+09 | 0.00 | 0.00 |
March | 0.226767E+10 | 0.173051E+10 | 0.167322E+10 | 0.797647E+09 | 0.875569E+09 | 0.00 | 0.00 |
April | 0.426582E+10 | 0.997123E+09 | 0.248640E+10 | 0.141831E+10 | 0.106808E+10 | 0.00 | 0.00 |
May | 0.472419E+10 | 0.744494E+09 | 0.257587E+10 | 0.144429E+10 | 0.113158E+10 | 0.00 | 0.00 |
June | 0.555677E+10 | 0.312013E+09 | 0.265007E+10 | 0.155867E+10 | 0.109141E+10 | 0.00 | 0.00 |
July | 0.433184E+10 | 0.236177E+09 | 0.199308E+10 | 0.930359E+09 | 0.106272E+10 | 0.00 | 0.00 |
August | 0.410537E+10 | 0.292704E+09 | 0.190058E+10 | 0.954507E+09 | 0.946071E+09 | 0.00 | 0.00 |
September | 0.328400E+10 | 0.407345E+09 | 0.160323E+10 | 0.673609E+09 | 0.929617E+09 | 0.00 | 0.00 |
October | 0.278541E+10 | 0.129379E+10 | 0.169511E+10 | 0.969260E+09 | 0.725854E+09 | 0.00 | 0.00 |
November | 0.213448E+10 | 0.181500E+10 | 0.151088E+10 | 0.912223E+09 | 0.598656E+09 | 0.00 | 0.00 |
December | 0.163685E+10 | 0.242243E+10 | 0.125830E+10 | 0.716434E+09 | 0.541863E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.387006E+11 | 0.140311E+11 | 0.220471E+11 | 0.118961E+11 | 0.101510E+11 | 0.00 | 0.00 |
Minimum of Months | 0.133211E+10 | 0.236177E+09 | 0.114100E+10 | 0.551603E+09 | 0.541863E+09 | 0.00 | 0.00 |
Maximum of Months | 0.555677E+10 | 0.242243E+10 | 0.265007E+10 | 0.155867E+10 | 0.113158E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.450774E+10 | -0.381225E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -695489703.5 | 58.98 | 0.00 | 0.00 |
February | 0.405989E+10 | -0.343052E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -629373331.1 | 58.98 | 0.00 | 0.00 |
March | 0.455535E+10 | -0.386169E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -693661447.3 | 58.98 | 0.00 | 0.00 |
April | 0.386671E+10 | -0.319914E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667575748.8 | 58.98 | 0.00 | 0.00 |
May | 0.380260E+10 | -0.311355E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689042019.5 | 58.98 | 0.00 | 0.00 |
June | 0.349515E+10 | -0.282783E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667318354.7 | 58.98 | 0.00 | 0.00 |
July | 0.323146E+10 | -0.254336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688100027.9 | 58.98 | 0.00 | 0.00 |
August | 0.354415E+10 | -0.285501E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689138439.2 | 58.98 | 0.00 | 0.00 |
September | 0.342166E+10 | -0.275683E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -664821870.4 | 58.98 | 0.00 | 0.00 |
October | 0.382206E+10 | -0.313424E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687823005.6 | 58.98 | 0.00 | 0.00 |
November | 0.405297E+10 | -0.338474E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668236455.6 | 58.98 | 0.00 | 0.00 |
December | 0.428543E+10 | -0.358958E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -695859593.4 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.466452E+11 | -0.385087E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.813644E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.323146E+10 | -0.386169E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -695859593.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.455535E+10 | -0.254336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -629373331.1 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.63 | 0.62 | 01-JAN-07:49 | 8248.13 | 38.40 | 306.33 | 289.50 | 2120.28 | 27.99 | 157.83 | 284.67 |
February | 241.00 | 0.63 | 0.62 | 01-FEB-07:49 | 7418.44 | 35.81 | 233.83 | 260.83 | 1142.11 | 22.12 | 94.17 | 215.50 |
March | 344.33 | 0.64 | 0.62 | 01-MAR-07:30 | 1344.96 | 16.61 | 2.33 | 321.67 | 795.04 | 19.37 | 44.83 | 275.67 |
April | 380.33 | 0.65 | 0.62 | 01-APR-07:30 | 1023.67 | 16.27 | 0.00 | 323.33 | 651.01 | 19.01 | 12.33 | 286.33 |
May | 403.17 | 0.64 | 0.62 | 01-MAY-06:00 | 803.61 | 15.98 | 0.00 | 345.50 | 510.59 | 18.78 | 0.00 | 291.33 |
June | 418.17 | 0.65 | 0.62 | 01-JUN-06:40 | 662.78 | 15.17 | 0.00 | 347.00 | 433.04 | 18.03 | 0.00 | 267.67 |
July | 399.50 | 0.65 | 0.62 | 01-JUL-07:10 | 776.45 | 15.61 | 0.00 | 346.50 | 472.78 | 18.41 | 0.00 | 261.17 |
August | 361.83 | 0.64 | 0.62 | 01-AUG-07:19 | 895.83 | 16.00 | 0.00 | 325.67 | 551.09 | 18.78 | 2.83 | 263.33 |
September | 350.17 | 0.64 | 0.62 | 01-SEP-06:49 | 1302.40 | 17.07 | 10.83 | 311.33 | 737.06 | 19.34 | 43.50 | 274.00 |
October | 348.00 | 0.64 | 0.62 | 01-OCT-06:00 | 2784.01 | 22.88 | 137.50 | 313.33 | 981.68 | 19.34 | 49.67 | 293.00 |
November | 288.50 | 0.63 | 0.62 | 01-NOV-07:30 | 7771.04 | 36.18 | 272.33 | 280.50 | 1433.40 | 24.53 | 118.17 | 263.50 |
December | 290.67 | 0.63 | 0.62 | 01-DEC-07:40 | 7586.56 | 37.31 | 278.83 | 276.33 | 1971.45 | 27.65 | 143.83 | 272.00 |
Annual Sum or Average | 4135.50 | 0.64 | 2975.05 | 22.36 | 1242.00 | 3741.50 | 922.51 | 20.74 | 667.17 | 3248.17 | ||
Minimum of Months | 241.00 | 0.63 | 0.62 | 662.78 | 15.17 | 0.00 | 260.83 | 433.04 | 18.03 | 0.00 | 215.50 | |
Maximum of Months | 418.17 | 0.65 | 0.62 | 8248.13 | 38.40 | 306.33 | 347.00 | 2120.28 | 27.99 | 157.83 | 293.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.65 | 0.62 | 01-JAN-07:00 | 1818.39 | 19.21 | 86.50 | 248.50 | 1043.94 | 22.30 | 74.67 | 187.67 |
February | 241.00 | 0.65 | 0.62 | 01-FEB-07:49 | 2147.10 | 18.99 | 65.00 | 235.33 | 1280.39 | 22.76 | 62.83 | 159.17 |
March | 344.33 | 0.65 | 0.62 | 01-MAR-07:30 | 1860.45 | 18.45 | 85.17 | 298.17 | 960.79 | 19.89 | 56.83 | 253.50 |
April | 380.33 | 0.64 | 0.62 | 01-APR-06:40 | 2686.77 | 20.18 | 112.33 | 339.17 | 1503.76 | 21.53 | 82.33 | 297.17 |
May | 403.17 | 0.63 | 0.62 | 01-MAY-05:00 | 3012.88 | 19.83 | 117.83 | 369.83 | 1149.54 | 19.73 | 56.67 | 325.50 |
June | 418.17 | 0.63 | 0.62 | 01-JUN-05:49 | 3017.05 | 18.98 | 115.00 | 371.33 | 1188.56 | 20.37 | 74.33 | 317.17 |
July | 399.50 | 0.63 | 0.62 | 01-JUL-05:00 | 2644.70 | 19.49 | 115.33 | 360.83 | 1036.51 | 19.35 | 55.50 | 293.17 |
August | 361.83 | 0.63 | 0.62 | 01-AUG-06:10 | 2600.78 | 20.14 | 111.67 | 338.83 | 1444.50 | 21.67 | 83.50 | 279.50 |
September | 350.17 | 0.64 | 0.62 | 01-SEP-06:30 | 1976.74 | 18.08 | 81.17 | 302.67 | 1097.16 | 21.46 | 75.17 | 258.00 |
October | 348.00 | 0.65 | 0.62 | 01-OCT-06:00 | 1937.77 | 18.21 | 87.83 | 267.83 | 1071.23 | 20.84 | 72.00 | 222.50 |
November | 288.50 | 0.64 | 0.62 | 01-NOV-07:19 | 1584.41 | 19.19 | 76.17 | 241.83 | 846.51 | 20.74 | 52.83 | 166.50 |
December | 290.67 | 0.65 | 0.62 | 01-DEC-07:49 | 1795.88 | 19.67 | 85.33 | 229.50 | 1045.52 | 22.79 | 74.00 | 170.33 |
Annual Sum or Average | 4135.50 | 0.64 | 2312.39 | 19.22 | 1139.33 | 3603.83 | 1145.47 | 21.00 | 820.67 | 2930.17 | ||
Minimum of Months | 241.00 | 0.63 | 0.62 | 1584.41 | 18.08 | 65.00 | 229.50 | 846.51 | 19.35 | 52.83 | 159.17 | |
Maximum of Months | 418.17 | 0.65 | 0.62 | 3017.05 | 20.18 | 117.83 | 371.33 | 1503.76 | 22.79 | 83.50 | 325.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.68 | 0.62 | 01-JAN-09:20 | 377.00 | 12.16 | 0.00 | 180.00 | 264.63 | 15.50 | 0.00 | 46.00 |
February | 241.00 | 0.67 | 0.62 | 01-FEB-09:50 | 469.46 | 13.25 | 0.00 | 195.00 | 305.19 | 16.25 | 0.00 | 79.17 |
March | 344.33 | 0.65 | 0.62 | 01-MAR-07:49 | 540.41 | 14.57 | 0.00 | 281.17 | 340.15 | 17.36 | 0.00 | 180.67 |
April | 380.33 | 0.64 | 0.62 | 01-APR-07:19 | 632.84 | 15.91 | 0.00 | 328.33 | 420.29 | 18.66 | 0.00 | 278.00 |
May | 403.17 | 0.63 | 0.62 | 01-MAY-06:10 | 752.36 | 16.68 | 1.50 | 382.83 | 499.76 | 19.53 | 9.67 | 360.33 |
June | 418.17 | 0.63 | 0.62 | 01-JUN-05:49 | 864.32 | 18.50 | 46.00 | 397.67 | 544.07 | 22.56 | 99.83 | 392.50 |
July | 399.50 | 0.63 | 0.62 | 01-JUL-05:00 | 779.44 | 19.21 | 62.33 | 389.50 | 499.72 | 21.83 | 70.00 | 339.83 |
August | 361.83 | 0.64 | 0.62 | 01-AUG-06:00 | 644.42 | 15.93 | 0.00 | 338.17 | 412.53 | 18.70 | 0.00 | 259.50 |
September | 350.17 | 0.65 | 0.62 | 01-SEP-06:49 | 615.66 | 15.22 | 0.00 | 302.83 | 379.85 | 17.94 | 0.00 | 218.00 |
October | 348.00 | 0.67 | 0.62 | 01-OCT-07:30 | 438.21 | 13.12 | 0.00 | 222.17 | 295.85 | 16.17 | 0.00 | 107.17 |
November | 288.50 | 0.67 | 0.62 | 01-NOV-07:49 | 412.01 | 12.85 | 0.00 | 187.33 | 277.53 | 16.12 | 0.00 | 50.67 |
December | 290.67 | 0.67 | 0.62 | 01-DEC-08:50 | 381.28 | 12.30 | 0.00 | 164.83 | 260.76 | 15.67 | 0.00 | 32.17 |
Annual Sum or Average | 4135.50 | 0.65 | 595.77 | 15.26 | 109.83 | 3369.83 | 387.44 | 18.31 | 179.50 | 2344.00 | ||
Minimum of Months | 241.00 | 0.63 | 0.62 | 377.00 | 12.16 | 0.00 | 164.83 | 260.76 | 15.50 | 0.00 | 32.17 | |
Maximum of Months | 418.17 | 0.68 | 0.62 | 864.32 | 19.21 | 62.33 | 397.67 | 544.07 | 22.56 | 99.83 | 392.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.67 | 0.62 | 01-JAN-09:20 | 1936.42 | 18.70 | 86.50 | 226.50 | 1141.53 | 21.61 | 74.67 | 174.67 |
February | 241.00 | 0.66 | 0.62 | 01-FEB-09:50 | 2068.38 | 20.08 | 81.00 | 220.17 | 793.67 | 19.33 | 36.50 | 155.17 |
March | 344.33 | 0.65 | 0.62 | 01-MAR-07:00 | 1689.89 | 17.81 | 79.00 | 296.67 | 895.16 | 19.42 | 50.67 | 249.50 |
April | 380.33 | 0.65 | 0.62 | 01-APR-07:00 | 2380.32 | 17.70 | 85.00 | 318.83 | 1381.84 | 19.49 | 55.00 | 288.17 |
May | 403.17 | 0.64 | 0.62 | 01-MAY-07:19 | 2687.92 | 15.35 | 54.50 | 349.33 | 1476.22 | 16.40 | 0.00 | 310.67 |
June | 418.17 | 0.64 | 0.62 | 01-JUN-06:00 | 2707.27 | 11.55 | 0.00 | 353.17 | 1048.68 | 15.97 | 0.00 | 310.67 |
July | 399.50 | 0.64 | 0.62 | 01-JUL-07:19 | 2009.46 | 12.44 | 3.67 | 352.50 | 877.46 | 16.40 | 0.00 | 290.83 |
August | 361.83 | 0.64 | 0.62 | 01-AUG-07:30 | 2079.45 | 15.13 | 49.17 | 326.33 | 1137.31 | 16.49 | 5.00 | 265.00 |
September | 350.17 | 0.65 | 0.62 | 01-SEP-06:00 | 1612.01 | 17.72 | 78.83 | 303.50 | 885.16 | 19.64 | 53.83 | 259.17 |
October | 348.00 | 0.66 | 0.62 | 01-OCT-07:40 | 1928.75 | 17.75 | 87.67 | 262.50 | 1095.39 | 21.00 | 78.50 | 219.50 |
November | 288.50 | 0.65 | 0.62 | 01-NOV-07:00 | 1836.23 | 19.00 | 80.83 | 232.50 | 965.83 | 20.10 | 52.33 | 173.33 |
December | 290.67 | 0.66 | 0.62 | 01-DEC-08:50 | 1547.63 | 18.95 | 80.67 | 217.33 | 807.06 | 19.83 | 49.67 | 167.50 |
Annual Sum or Average | 4135.50 | 0.65 | 2072.76 | 16.53 | 766.83 | 3459.33 | 1058.85 | 18.62 | 456.17 | 2864.17 | ||
Minimum of Months | 241.00 | 0.64 | 0.62 | 1547.63 | 11.55 | 0.00 | 217.33 | 793.67 | 15.97 | 0.00 | 155.17 | |
Maximum of Months | 418.17 | 0.67 | 0.62 | 2707.27 | 20.08 | 87.67 | 353.17 | 1476.22 | 21.61 | 78.50 | 310.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.64 | 0.62 | 01-JAN-08:09 | 7947.68 | 34.50 | 270.50 | 278.50 | 1999.90 | 25.91 | 145.33 | 283.83 |
February | 241.00 | 0.63 | 0.62 | 01-FEB-07:49 | 7301.69 | 35.62 | 233.67 | 259.33 | 1053.48 | 19.48 | 37.50 | 212.50 |
March | 344.33 | 0.64 | 0.62 | 01-MAR-07:30 | 1265.87 | 12.91 | 2.33 | 319.83 | 738.44 | 16.96 | 1.83 | 270.83 |
April | 380.33 | 0.65 | 0.62 | 01-APR-07:30 | 968.70 | 13.00 | 0.00 | 321.17 | 613.62 | 17.03 | 0.00 | 281.67 |
May | 403.17 | 0.64 | 0.62 | 01-MAY-06:00 | 768.25 | 12.72 | 0.00 | 340.83 | 489.93 | 16.79 | 0.00 | 283.33 |
June | 418.17 | 0.65 | 0.62 | 01-JUN-06:49 | 636.27 | 11.92 | 0.00 | 342.17 | 418.78 | 16.04 | 0.00 | 258.00 |
July | 399.50 | 0.65 | 0.62 | 01-JUL-07:10 | 742.96 | 12.23 | 0.00 | 342.67 | 453.73 | 16.26 | 0.00 | 253.17 |
August | 361.83 | 0.65 | 0.62 | 01-AUG-07:19 | 852.27 | 12.59 | 0.00 | 322.00 | 523.47 | 16.65 | 0.00 | 257.00 |
September | 350.17 | 0.65 | 0.62 | 01-SEP-06:49 | 1232.87 | 13.56 | 10.83 | 308.33 | 689.56 | 16.96 | 0.00 | 270.33 |
October | 348.00 | 0.64 | 0.62 | 01-OCT-07:10 | 2684.12 | 20.29 | 137.17 | 313.00 | 903.25 | 16.75 | 13.17 | 290.33 |
November | 288.50 | 0.63 | 0.62 | 01-NOV-07:30 | 7617.05 | 35.38 | 268.33 | 278.50 | 1326.59 | 22.01 | 88.83 | 262.17 |
December | 290.67 | 0.63 | 0.62 | 01-DEC-07:49 | 7364.15 | 35.21 | 262.50 | 269.50 | 1829.74 | 24.92 | 125.50 | 269.17 |
Annual Sum or Average | 4135.50 | 0.64 | 2880.25 | 19.46 | 1185.33 | 3695.83 | 864.43 | 18.47 | 412.17 | 3192.33 | ||
Minimum of Months | 241.00 | 0.63 | 0.62 | 636.27 | 11.92 | 0.00 | 259.33 | 418.78 | 16.04 | 0.00 | 212.50 | |
Maximum of Months | 418.17 | 0.65 | 0.62 | 7947.68 | 35.62 | 270.50 | 342.67 | 1999.90 | 25.91 | 145.33 | 290.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.65 | 0.62 | 01-JAN-07:00 | 1770.14 | 18.78 | 86.50 | 242.33 | 918.23 | 20.03 | 56.33 | 178.67 |
February | 241.00 | 0.65 | 0.62 | 01-FEB-07:00 | 2089.67 | 18.56 | 65.00 | 230.50 | 1235.82 | 22.56 | 62.83 | 156.17 |
March | 344.33 | 0.65 | 0.62 | 01-MAR-07:30 | 1803.55 | 18.02 | 85.17 | 295.67 | 913.29 | 19.68 | 56.83 | 249.00 |
April | 380.33 | 0.64 | 0.62 | 01-APR-06:40 | 2443.28 | 17.50 | 84.50 | 334.67 | 1448.92 | 21.36 | 82.33 | 291.83 |
May | 403.17 | 0.63 | 0.62 | 01-MAY-05:00 | 2937.25 | 19.43 | 117.83 | 366.50 | 1092.20 | 19.56 | 56.67 | 321.33 |
June | 418.17 | 0.64 | 0.62 | 01-JUN-05:49 | 2954.32 | 18.58 | 115.00 | 364.67 | 1133.85 | 20.22 | 74.33 | 314.33 |
July | 399.50 | 0.64 | 0.62 | 01-JUL-05:00 | 2579.70 | 19.10 | 115.33 | 356.83 | 984.62 | 19.19 | 55.50 | 290.00 |
August | 361.83 | 0.63 | 0.62 | 01-AUG-06:10 | 2528.33 | 19.75 | 111.67 | 335.83 | 1392.56 | 21.51 | 83.50 | 274.83 |
September | 350.17 | 0.65 | 0.62 | 01-SEP-06:40 | 1920.99 | 17.65 | 81.17 | 299.67 | 1047.85 | 21.10 | 73.17 | 254.00 |
October | 348.00 | 0.66 | 0.62 | 01-OCT-06:00 | 1880.83 | 17.79 | 87.83 | 264.67 | 963.14 | 19.23 | 56.83 | 215.83 |
November | 288.50 | 0.64 | 0.62 | 01-NOV-07:19 | 1537.94 | 18.76 | 76.17 | 236.67 | 809.14 | 20.53 | 52.83 | 160.83 |
December | 290.67 | 0.65 | 0.62 | 01-DEC-07:49 | 1750.39 | 19.23 | 85.33 | 223.83 | 991.06 | 22.18 | 70.67 | 164.67 |
Annual Sum or Average | 4135.50 | 0.64 | 2236.02 | 18.60 | 1111.50 | 3551.83 | 1084.07 | 20.50 | 781.83 | 2871.50 | ||
Minimum of Months | 241.00 | 0.63 | 0.62 | 1537.94 | 17.50 | 65.00 | 223.83 | 809.14 | 19.19 | 52.83 | 156.17 | |
Maximum of Months | 418.17 | 0.66 | 0.62 | 2954.32 | 19.75 | 117.83 | 366.50 | 1448.92 | 22.56 | 83.50 | 321.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.68 | 0.62 | 01-JAN-09:30 | 360.93 | 8.84 | 0.00 | 163.67 | 256.66 | 13.25 | 0.00 | 34.00 |
February | 241.00 | 0.67 | 0.62 | 01-FEB-09:00 | 450.28 | 9.94 | 0.00 | 184.50 | 295.45 | 14.09 | 0.00 | 69.17 |
March | 344.33 | 0.65 | 0.62 | 01-MAR-07:00 | 518.58 | 11.30 | 0.00 | 275.00 | 328.93 | 15.36 | 0.00 | 170.17 |
April | 380.33 | 0.64 | 0.62 | 01-APR-07:30 | 607.61 | 12.89 | 0.00 | 324.00 | 407.68 | 17.00 | 0.00 | 266.50 |
May | 403.17 | 0.63 | 0.62 | 01-MAY-06:10 | 722.26 | 13.37 | 1.50 | 382.50 | 483.73 | 17.61 | 2.67 | 352.17 |
June | 418.17 | 0.63 | 0.62 | 01-JUN-05:49 | 831.53 | 15.32 | 44.67 | 396.00 | 525.92 | 20.79 | 81.50 | 389.83 |
July | 399.50 | 0.63 | 0.62 | 01-JUL-05:00 | 734.45 | 14.79 | 32.50 | 385.50 | 481.72 | 19.96 | 62.83 | 330.00 |
August | 361.83 | 0.64 | 0.62 | 01-AUG-06:00 | 618.60 | 12.62 | 0.00 | 334.17 | 399.30 | 16.79 | 0.00 | 244.17 |
September | 350.17 | 0.65 | 0.62 | 01-SEP-06:00 | 590.25 | 11.97 | 0.00 | 299.50 | 366.60 | 15.94 | 0.00 | 205.17 |
October | 348.00 | 0.67 | 0.62 | 01-OCT-07:30 | 420.83 | 9.88 | 0.00 | 211.50 | 287.22 | 14.12 | 0.00 | 96.00 |
November | 288.50 | 0.67 | 0.62 | 01-NOV-07:49 | 394.84 | 9.40 | 0.00 | 175.33 | 268.91 | 13.83 | 0.00 | 41.83 |
December | 290.67 | 0.68 | 0.62 | 01-DEC-08:50 | 364.80 | 8.84 | 0.00 | 149.67 | 252.46 | 13.30 | 0.00 | 23.17 |
Annual Sum or Average | 4135.50 | 0.65 | 570.49 | 11.88 | 78.67 | 3281.33 | 374.85 | 16.31 | 147.00 | 2222.17 | ||
Minimum of Months | 241.00 | 0.63 | 0.62 | 360.93 | 8.84 | 0.00 | 149.67 | 252.46 | 13.25 | 0.00 | 23.17 | |
Maximum of Months | 418.17 | 0.68 | 0.62 | 831.53 | 15.32 | 44.67 | 396.00 | 525.92 | 20.79 | 81.50 | 389.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.67 | 0.62 | 01-JAN-09:30 | 1884.59 | 18.36 | 86.50 | 223.33 | 1098.93 | 21.52 | 74.67 | 170.33 |
February | 241.00 | 0.66 | 0.62 | 01-FEB-09:00 | 2015.91 | 19.75 | 81.00 | 216.50 | 755.30 | 19.22 | 36.50 | 151.83 |
March | 344.33 | 0.65 | 0.62 | 01-MAR-07:00 | 1637.34 | 17.43 | 79.00 | 293.67 | 852.78 | 19.28 | 50.67 | 245.17 |
April | 380.33 | 0.65 | 0.62 | 01-APR-08:09 | 2308.31 | 17.30 | 85.00 | 314.50 | 1325.53 | 19.33 | 55.00 | 284.33 |
May | 403.17 | 0.64 | 0.62 | 01-MAY-07:19 | 2610.60 | 14.92 | 54.50 | 346.83 | 1422.01 | 16.23 | 0.00 | 307.33 |
June | 418.17 | 0.64 | 0.62 | 01-JUN-06:00 | 2641.49 | 11.10 | 0.00 | 349.00 | 994.76 | 15.79 | 0.00 | 308.00 |
July | 399.50 | 0.64 | 0.62 | 01-JUL-07:19 | 1944.23 | 11.97 | 3.67 | 347.83 | 835.54 | 16.20 | 0.00 | 286.00 |
August | 361.83 | 0.64 | 0.62 | 01-AUG-07:40 | 1933.19 | 14.68 | 49.17 | 318.67 | 1087.43 | 16.31 | 5.00 | 261.00 |
September | 350.17 | 0.65 | 0.62 | 01-SEP-07:10 | 1561.23 | 17.34 | 78.67 | 299.83 | 823.82 | 19.49 | 53.83 | 252.83 |
October | 348.00 | 0.66 | 0.62 | 01-OCT-07:40 | 1876.74 | 17.38 | 87.67 | 259.00 | 1054.33 | 20.88 | 78.50 | 216.17 |
November | 288.50 | 0.66 | 0.62 | 01-NOV-07:00 | 1779.75 | 18.64 | 80.83 | 229.00 | 921.34 | 19.98 | 52.33 | 170.00 |
December | 290.67 | 0.66 | 0.62 | 01-DEC-08:50 | 1499.90 | 18.61 | 80.67 | 214.50 | 768.65 | 19.73 | 49.67 | 163.00 |
Annual Sum or Average | 4135.50 | 0.65 | 2005.56 | 16.13 | 766.67 | 3412.67 | 1011.11 | 18.47 | 456.17 | 2816.00 | ||
Minimum of Months | 241.00 | 0.64 | 0.62 | 1499.90 | 11.10 | 0.00 | 214.50 | 755.30 | 15.79 | 0.00 | 151.83 | |
Maximum of Months | 418.17 | 0.67 | 0.62 | 2641.49 | 19.75 | 87.67 | 349.00 | 1422.01 | 21.52 | 78.50 | 308.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.64 | 0.62 | 01-JAN-08:09 | 7947.70 | 34.50 | 270.50 | 278.67 | 1999.85 | 25.91 | 145.33 | 283.83 |
February | 241.00 | 0.63 | 0.62 | 01-FEB-07:49 | 7301.66 | 35.62 | 233.67 | 259.33 | 1053.42 | 19.48 | 37.50 | 212.50 |
March | 344.33 | 0.64 | 0.62 | 01-MAR-07:30 | 1265.83 | 12.91 | 2.33 | 319.83 | 738.40 | 16.96 | 1.83 | 270.83 |
April | 380.33 | 0.65 | 0.62 | 01-APR-07:30 | 968.68 | 13.00 | 0.00 | 321.17 | 613.59 | 17.03 | 0.00 | 281.50 |
May | 403.17 | 0.64 | 0.62 | 01-MAY-06:00 | 768.24 | 12.73 | 0.00 | 340.83 | 489.91 | 16.79 | 0.00 | 283.33 |
June | 418.17 | 0.65 | 0.62 | 01-JUN-06:49 | 636.27 | 11.92 | 0.00 | 342.17 | 418.76 | 16.04 | 0.00 | 258.00 |
July | 399.50 | 0.65 | 0.62 | 01-JUL-07:10 | 742.94 | 12.23 | 0.00 | 342.67 | 453.71 | 16.26 | 0.00 | 253.00 |
August | 361.83 | 0.65 | 0.62 | 01-AUG-07:19 | 852.25 | 12.59 | 0.00 | 322.00 | 523.44 | 16.65 | 0.00 | 257.00 |
September | 350.17 | 0.65 | 0.62 | 01-SEP-06:49 | 1232.82 | 13.56 | 10.83 | 308.33 | 689.52 | 16.96 | 0.00 | 270.33 |
October | 348.00 | 0.64 | 0.62 | 01-OCT-07:10 | 2684.09 | 20.29 | 137.17 | 313.00 | 903.21 | 16.75 | 13.17 | 290.33 |
November | 288.50 | 0.63 | 0.62 | 01-NOV-07:30 | 7617.05 | 35.39 | 268.33 | 278.50 | 1326.54 | 22.01 | 88.83 | 262.17 |
December | 290.67 | 0.63 | 0.62 | 01-DEC-07:49 | 7364.17 | 35.21 | 262.50 | 269.50 | 1829.69 | 24.92 | 125.50 | 269.17 |
Annual Sum or Average | 4135.50 | 0.64 | 2880.24 | 19.46 | 1185.33 | 3696.00 | 864.39 | 18.47 | 412.17 | 3192.00 | ||
Minimum of Months | 241.00 | 0.63 | 0.62 | 636.27 | 11.92 | 0.00 | 259.33 | 418.76 | 16.04 | 0.00 | 212.50 | |
Maximum of Months | 418.17 | 0.65 | 0.62 | 7947.70 | 35.62 | 270.50 | 342.67 | 1999.85 | 25.91 | 145.33 | 290.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.65 | 0.62 | 01-JAN-07:00 | 1770.15 | 18.78 | 86.50 | 242.33 | 918.21 | 20.03 | 56.33 | 178.67 |
February | 241.00 | 0.65 | 0.62 | 01-FEB-07:00 | 2089.67 | 18.56 | 65.00 | 230.50 | 1235.80 | 22.56 | 62.83 | 156.17 |
March | 344.33 | 0.65 | 0.62 | 01-MAR-07:30 | 1803.55 | 18.02 | 85.17 | 295.67 | 913.26 | 19.68 | 56.83 | 249.00 |
April | 380.33 | 0.64 | 0.62 | 01-APR-06:40 | 2443.29 | 17.51 | 84.50 | 334.67 | 1448.89 | 21.36 | 82.33 | 291.83 |
May | 403.17 | 0.63 | 0.62 | 01-MAY-05:00 | 2937.26 | 19.44 | 117.83 | 366.50 | 1092.17 | 19.56 | 56.67 | 321.33 |
June | 418.17 | 0.64 | 0.62 | 01-JUN-05:49 | 2954.32 | 18.58 | 115.00 | 364.67 | 1133.83 | 20.22 | 74.33 | 314.33 |
July | 399.50 | 0.64 | 0.62 | 01-JUL-05:00 | 2579.70 | 19.11 | 115.33 | 356.83 | 984.58 | 19.19 | 55.50 | 290.00 |
August | 361.83 | 0.63 | 0.62 | 01-AUG-06:10 | 2528.33 | 19.75 | 111.67 | 335.83 | 1392.53 | 21.51 | 83.50 | 274.83 |
September | 350.17 | 0.65 | 0.62 | 01-SEP-06:40 | 1920.98 | 17.65 | 81.17 | 299.67 | 1047.81 | 21.10 | 73.17 | 254.00 |
October | 348.00 | 0.66 | 0.62 | 01-OCT-06:00 | 1880.84 | 17.79 | 87.83 | 264.67 | 963.11 | 19.23 | 56.83 | 215.83 |
November | 288.50 | 0.64 | 0.62 | 01-NOV-07:19 | 1537.95 | 18.76 | 76.17 | 236.67 | 809.12 | 20.53 | 52.83 | 160.83 |
December | 290.67 | 0.65 | 0.62 | 01-DEC-07:49 | 1750.40 | 19.23 | 85.33 | 223.83 | 991.04 | 22.18 | 70.67 | 164.67 |
Annual Sum or Average | 4135.50 | 0.64 | 2236.02 | 18.60 | 1111.50 | 3551.83 | 1084.05 | 20.50 | 781.83 | 2871.50 | ||
Minimum of Months | 241.00 | 0.63 | 0.62 | 1537.95 | 17.51 | 65.00 | 223.83 | 809.12 | 19.19 | 52.83 | 156.17 | |
Maximum of Months | 418.17 | 0.66 | 0.62 | 2954.32 | 19.75 | 117.83 | 366.50 | 1448.89 | 22.56 | 83.50 | 321.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.68 | 0.62 | 01-JAN-09:30 | 360.94 | 8.85 | 0.00 | 163.67 | 256.65 | 13.25 | 0.00 | 34.00 |
February | 241.00 | 0.67 | 0.62 | 01-FEB-09:00 | 450.28 | 9.94 | 0.00 | 184.50 | 295.44 | 14.10 | 0.00 | 69.17 |
March | 344.33 | 0.65 | 0.62 | 01-MAR-07:00 | 518.58 | 11.30 | 0.00 | 275.00 | 328.91 | 15.36 | 0.00 | 170.17 |
April | 380.33 | 0.64 | 0.62 | 01-APR-07:30 | 607.62 | 12.89 | 0.00 | 324.00 | 407.66 | 17.00 | 0.00 | 266.50 |
May | 403.17 | 0.63 | 0.62 | 01-MAY-06:10 | 722.26 | 13.37 | 1.50 | 382.50 | 483.71 | 17.61 | 2.67 | 352.17 |
June | 418.17 | 0.63 | 0.62 | 01-JUN-05:49 | 831.53 | 15.32 | 44.67 | 396.00 | 525.90 | 20.79 | 81.50 | 389.83 |
July | 399.50 | 0.63 | 0.62 | 01-JUL-05:00 | 734.44 | 14.79 | 32.50 | 385.50 | 481.70 | 19.96 | 62.83 | 330.00 |
August | 361.83 | 0.64 | 0.62 | 01-AUG-06:00 | 618.60 | 12.62 | 0.00 | 334.17 | 399.28 | 16.79 | 0.00 | 244.17 |
September | 350.17 | 0.65 | 0.62 | 01-SEP-06:00 | 590.24 | 11.97 | 0.00 | 299.50 | 366.58 | 15.94 | 0.00 | 205.17 |
October | 348.00 | 0.67 | 0.62 | 01-OCT-07:30 | 420.83 | 9.88 | 0.00 | 211.67 | 287.21 | 14.12 | 0.00 | 96.00 |
November | 288.50 | 0.67 | 0.62 | 01-NOV-07:49 | 394.85 | 9.40 | 0.00 | 175.33 | 268.90 | 13.83 | 0.00 | 41.83 |
December | 290.67 | 0.68 | 0.62 | 01-DEC-08:50 | 364.81 | 8.85 | 0.00 | 149.67 | 252.45 | 13.30 | 0.00 | 23.17 |
Annual Sum or Average | 4135.50 | 0.65 | 570.49 | 11.88 | 78.67 | 3281.50 | 374.84 | 16.31 | 147.00 | 2222.17 | ||
Minimum of Months | 241.00 | 0.63 | 0.62 | 360.94 | 8.85 | 0.00 | 149.67 | 252.45 | 13.25 | 0.00 | 23.17 | |
Maximum of Months | 418.17 | 0.68 | 0.62 | 831.53 | 15.32 | 44.67 | 396.00 | 525.90 | 20.79 | 81.50 | 389.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.67 | 0.62 | 01-JAN-09:30 | 1884.60 | 18.36 | 86.50 | 223.33 | 1098.91 | 21.52 | 74.67 | 170.33 |
February | 241.00 | 0.66 | 0.62 | 01-FEB-09:00 | 2015.91 | 19.75 | 81.00 | 216.50 | 755.27 | 19.22 | 36.50 | 151.83 |
March | 344.33 | 0.65 | 0.62 | 01-MAR-07:00 | 1637.33 | 17.43 | 79.00 | 293.67 | 852.75 | 19.28 | 50.67 | 245.17 |
April | 380.33 | 0.65 | 0.62 | 01-APR-08:09 | 2308.31 | 17.31 | 85.00 | 314.50 | 1325.50 | 19.33 | 55.00 | 284.33 |
May | 403.17 | 0.64 | 0.62 | 01-MAY-07:19 | 2610.61 | 14.93 | 54.50 | 346.83 | 1421.98 | 16.23 | 0.00 | 307.17 |
June | 418.17 | 0.64 | 0.62 | 01-JUN-06:00 | 2641.50 | 11.11 | 0.00 | 349.17 | 994.74 | 15.79 | 0.00 | 308.00 |
July | 399.50 | 0.64 | 0.62 | 01-JUL-07:19 | 1944.22 | 11.97 | 3.67 | 347.83 | 835.50 | 16.20 | 0.00 | 286.00 |
August | 361.83 | 0.64 | 0.62 | 01-AUG-07:40 | 1933.18 | 14.69 | 49.17 | 318.67 | 1087.40 | 16.31 | 5.00 | 261.00 |
September | 350.17 | 0.65 | 0.62 | 01-SEP-07:10 | 1561.22 | 17.34 | 78.67 | 299.83 | 823.78 | 19.49 | 53.83 | 252.83 |
October | 348.00 | 0.66 | 0.62 | 01-OCT-07:40 | 1876.74 | 17.38 | 87.67 | 259.00 | 1054.31 | 20.88 | 78.50 | 216.17 |
November | 288.50 | 0.66 | 0.62 | 01-NOV-07:00 | 1779.77 | 18.64 | 80.83 | 229.00 | 921.32 | 19.98 | 52.33 | 170.00 |
December | 290.67 | 0.66 | 0.62 | 01-DEC-08:50 | 1499.92 | 18.61 | 80.67 | 214.50 | 768.63 | 19.73 | 49.67 | 163.00 |
Annual Sum or Average | 4135.50 | 0.65 | 2005.56 | 16.13 | 766.67 | 3412.83 | 1011.08 | 18.47 | 456.17 | 2815.83 | ||
Minimum of Months | 241.00 | 0.64 | 0.62 | 1499.92 | 11.11 | 0.00 | 214.50 | 755.27 | 15.79 | 0.00 | 151.83 | |
Maximum of Months | 418.17 | 0.67 | 0.62 | 2641.50 | 19.75 | 87.67 | 349.17 | 1421.98 | 21.52 | 78.50 | 308.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.672609E+09 | 9106.33 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.732134E+09 | 9106.33 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.827973E+09 | 9106.33 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142470E+09 | 9106.33 | 07-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7776262.05 | 6965.28 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277115E+09 | 9106.33 | 12-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.386346E+09 | 9106.33 | 06-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.791758E+09 | 9106.33 | 01-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.383818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.827973E+09 | 9106.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 16594301.48 | 6027.79 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10519105.52 | 6027.79 | 13-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9852404.00 | 6027.79 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14588627.71 | 6027.79 | 06-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51554438.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16594301.48 | 6027.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 61486500.18 | 9036.58 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 42787677.07 | 9036.58 | 13-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 42306104.58 | 9036.58 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 890566.88 | 2426.15 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 61405846.17 | 9036.58 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208877E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 61486500.18 | 9036.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 20090500.50 | 5982.28 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26983607.27 | 5982.28 | 08-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19213224.21 | 5982.28 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36166419.27 | 5982.28 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36166419.27 | 5982.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 17186893.64 | 23792.90 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17186893.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17186893.64 | 23792.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 27094368.39 | 10824.38 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18100130.09 | 10172.63 | 13-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22223649.18 | 10824.38 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2023741.72 | 10045.78 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 79144519.51 | 10824.38 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 79144519.51 | 10824.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 41097213.43 | 7144.89 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 32679586.22 | 6983.09 | 09-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22502830.13 | 7144.89 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 520562.50 | 811.86 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8382529.17 | 7144.89 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116556E+09 | 7144.89 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221739E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116556E+09 | 7144.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 70700767.68 | 10771.72 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 41916219.81 | 10172.72 | 13-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31937327.31 | 10771.72 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13552213.18 | 10771.72 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186643E+09 | 10771.72 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.344749E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.186643E+09 | 10771.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 61730379.56 | 7102.93 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 56496030.24 | 7102.93 | 08-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 38400558.75 | 7102.93 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1039498.59 | 810.53 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20693291.58 | 7102.93 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187532E+09 | 7102.93 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.365892E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.187532E+09 | 7102.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141352E+09 | 30745.47 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 40212415.97 | 30745.47 | 13-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15362972.81 | 30745.47 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14617857.35 | 30745.47 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229895E+09 | 30745.47 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.441440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.229895E+09 | 30745.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.195008E+09 | 14050.75 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.245572E+09 | 14050.75 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199876E+09 | 13996.82 | 31-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1058038.73 | 1625.51 | 21-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32836650.15 | 11134.72 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101413E+09 | 13957.06 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.489655E+09 | 14050.75 | 18-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.489655E+09 | 14050.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.195751E+09 | 9195.52 | 02-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.215194E+09 | 9195.52 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126807E+09 | 9195.52 | 27-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 524205.09 | 686.02 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30184167.06 | 9065.43 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 97836118.93 | 9195.52 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.492205E+09 | 9195.52 | 04-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.492205E+09 | 9195.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.389311E+09 | 12861.89 | 10-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.378680E+09 | 12868.50 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.246240E+09 | 12857.15 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1271436.42 | 1354.76 | 21-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 48925138.05 | 11679.41 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.226828E+09 | 12803.57 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.982451E+09 | 12845.45 | 18-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.982451E+09 | 12868.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.320095E+09 | 9152.25 | 02-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.351653E+09 | 9152.25 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227292E+09 | 9152.25 | 27-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3691053.07 | 2060.04 | 21-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 53941082.51 | 9152.25 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200915E+09 | 9152.25 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.758629E+09 | 9152.25 | 04-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.758629E+09 | 9152.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 10206151.73 | 2372.43 | 02-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1551107.22 | 624.02 | 25-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 36622297.73 | 4524.89 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1190664.63 | 1248.80 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191607E+09 | 6645.58 | 06-DEC-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241177E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.191607E+09 | 6645.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 44338326.23 | 4171.30 | 02-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 60502026.91 | 2652.14 | 28-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113233E+09 | 6110.75 | 27-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9339617.76 | 2213.68 | 25-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24147866.45 | 3840.27 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.420297E+09 | 8200.92 | 06-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.671857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.420297E+09 | 8200.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.124306E+09 | 5521.23 | 02-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176706E+09 | 4666.49 | 28-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.221599E+09 | 8386.66 | 27-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39040231.81 | 4007.30 | 25-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 75054949.07 | 6174.06 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.713229E+09 | 11074.70 | 06-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.713229E+09 | 11074.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.177383E+11 | 0.176159E+11 | 49562.02 | 31-JAN-17:00 | 49562.02 | 0.00 |
February | 0.00 | 0.00 | 0.400265E+10 | 0.351487E+10 | 22173.99 | 22-FEB-16:10 | 22173.99 | 0.00 |
March | 0.00 | 0.00 | 0.171784E+11 | 0.167789E+11 | 47755.48 | 16-MAR-15:50 | 47755.48 | 0.00 |
April | 0.00 | 0.00 | 0.478301E+11 | 0.477370E+11 | 67152.00 | 14-APR-16:00 | 67152.00 | 0.00 |
May | 0.00 | 0.00 | 0.637072E+11 | 0.636495E+11 | 70671.76 | 31-MAY-16:00 | 70671.76 | 0.00 |
June | 0.00 | 0.00 | 0.851688E+11 | 0.849049E+11 | 91190.75 | 29-JUN-06:03 | 91190.75 | 0.00 |
July | 0.00 | 0.00 | 0.881133E+11 | 0.814802E+11 | 130845.48 | 14-JUL-04:03 | 51353.57 | 0.00 |
August | 0.00 | 0.00 | 0.917145E+11 | 0.843370E+11 | 126589.18 | 01-AUG-04:02 | 66077.40 | 0.00 |
September | 0.00 | 0.00 | 0.797566E+11 | 0.722171E+11 | 122768.53 | 08-SEP-04:02 | 80434.30 | 0.00 |
October | 0.00 | 0.00 | 0.448220E+11 | 0.433837E+11 | 122767.58 | 03-OCT-04:02 | 61510.25 | 0.00 |
November | 0.00 | 0.00 | 0.202486E+11 | 0.189869E+11 | 57496.83 | 13-NOV-05:03 | 20070.43 | 0.00 |
December | 0.00 | 0.00 | 0.844509E+10 | 0.842122E+10 | 43685.50 | 22-DEC-16:30 | 43685.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.568725E+12 | 0.543027E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.400265E+10 | 0.351487E+10 | 22173.99 | 20070.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.917145E+11 | 0.849049E+11 | 130845.48 | 91190.75 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.144263E+11 | 0.143006E+11 | 41152.67 | 31-JAN-16:30 | 41152.67 | 0.00 |
February | 0.00 | 0.00 | 0.330843E+10 | 0.281832E+10 | 20338.91 | 22-FEB-16:00 | 20338.91 | 0.00 |
March | 0.00 | 0.00 | 0.145137E+11 | 0.140519E+11 | 44085.51 | 16-MAR-15:40 | 44085.51 | 0.00 |
April | 0.00 | 0.00 | 0.429082E+11 | 0.428404E+11 | 62859.15 | 14-APR-15:30 | 62859.15 | 0.00 |
May | 0.00 | 0.00 | 0.576942E+11 | 0.576602E+11 | 64083.73 | 18-MAY-15:30 | 64083.73 | 0.00 |
June | 0.00 | 0.00 | 0.783582E+11 | 0.782120E+11 | 78972.14 | 29-JUN-04:02 | 78972.14 | 0.00 |
July | 0.00 | 0.00 | 0.768277E+11 | 0.718371E+11 | 118842.49 | 14-JUL-05:03 | 47749.69 | 0.00 |
August | 0.00 | 0.00 | 0.775518E+11 | 0.723525E+11 | 115356.37 | 01-AUG-04:02 | 59738.38 | 0.00 |
September | 0.00 | 0.00 | 0.648494E+11 | 0.595335E+11 | 111874.74 | 08-SEP-04:02 | 71657.32 | 0.00 |
October | 0.00 | 0.00 | 0.358126E+11 | 0.346797E+11 | 81542.86 | 03-OCT-04:02 | 40765.56 | 0.00 |
November | 0.00 | 0.00 | 0.151489E+11 | 0.141440E+11 | 48648.28 | 01-NOV-15:30 | 48648.28 | 0.00 |
December | 0.00 | 0.00 | 0.659325E+10 | 0.655207E+10 | 34659.58 | 22-DEC-16:30 | 34659.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.487993E+12 | 0.468982E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.330843E+10 | 0.281832E+10 | 20338.91 | 20338.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.783582E+11 | 0.782120E+11 | 118842.49 | 78972.14 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.143313E+11 | 0.141370E+11 | 44814.84 | 31-JAN-16:20 | 44814.84 | 0.00 |
February | 0.00 | 0.00 | 0.339257E+10 | 0.280170E+10 | 20344.53 | 22-FEB-16:00 | 20344.53 | 0.00 |
March | 0.00 | 0.00 | 0.152250E+11 | 0.145549E+11 | 50961.24 | 16-MAR-15:40 | 50961.24 | 0.00 |
April | 0.00 | 0.00 | 0.474929E+11 | 0.473776E+11 | 75028.93 | 30-APR-15:52 | 75028.93 | 0.00 |
May | 0.00 | 0.00 | 0.639836E+11 | 0.639363E+11 | 78314.27 | 07-MAY-16:12 | 78314.27 | 0.00 |
June | 0.00 | 0.00 | 0.883743E+11 | 0.881763E+11 | 92359.85 | 28-JUN-15:00 | 92359.85 | 0.00 |
July | 0.00 | 0.00 | 0.855023E+11 | 0.803215E+11 | 127130.88 | 24-JUL-04:02 | 83391.40 | 0.00 |
August | 0.00 | 0.00 | 0.851901E+11 | 0.797988E+11 | 132574.67 | 01-AUG-04:02 | 67737.55 | 0.00 |
September | 0.00 | 0.00 | 0.697415E+11 | 0.643261E+11 | 107543.24 | 08-SEP-05:03 | 62490.63 | 0.00 |
October | 0.00 | 0.00 | 0.373236E+11 | 0.360618E+11 | 88168.41 | 02-OCT-04:02 | 88168.41 | 0.00 |
November | 0.00 | 0.00 | 0.148877E+11 | 0.138198E+11 | 55351.06 | 01-NOV-15:30 | 55351.06 | 0.00 |
December | 0.00 | 0.00 | 0.643520E+10 | 0.637399E+10 | 36426.24 | 22-DEC-15:40 | 36426.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.531880E+12 | 0.511686E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.339257E+10 | 0.280170E+10 | 20344.53 | 20344.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.883743E+11 | 0.881763E+11 | 132574.67 | 92359.85 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1576.30 | 5409.09 | 23-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1571.58 | 5422.31 | 06-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1598.87 | 5250.20 | 03-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1387.51 | 4881.45 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1318.21 | 4496.83 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1248.56 | 4103.34 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1102.77 | 3851.26 | 03-JUL-11:13 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 1224.10 | 3944.74 | 30-AUG-11:13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1217.87 | 4269.64 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1324.53 | 4686.81 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1460.70 | 5073.41 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1492.26 | 5332.44 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1375.87 | ||||
Minimum of Months | 0.00 | 0.00 | 1102.77 | 3851.26 | ||
Maximum of Months | 0.00 | 0.00 | 1598.87 | 5422.31 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.261789E+10 | 0.36 | 4789.25 | 27-JAN-17:00 | 1.09 |
February | 0.182554E+10 | 0.32 | 4188.59 | 01-FEB-06:03 | 1.01 |
March | 0.255890E+10 | 0.37 | 4825.93 | 20-MAR-15:10 | 1.09 |
April | 0.450542E+10 | 0.50 | 8025.74 | 24-APR-12:07 | 1.49 |
May | 0.579727E+10 | 0.57 | 9025.85 | 08-MAY-16:00 | 1.60 |
June | 0.737496E+10 | 0.68 | 12400.84 | 29-JUN-04:02 | 1.96 |
July | 0.695174E+10 | 0.64 | 12400.84 | 05-JUL-04:02 | 1.96 |
August | 0.706581E+10 | 0.64 | 12400.84 | 01-AUG-04:02 | 1.94 |
September | 0.604796E+10 | 0.59 | 12400.84 | 05-SEP-04:02 | 1.94 |
October | 0.442342E+10 | 0.48 | 12400.84 | 02-OCT-04:02 | 1.94 |
November | 0.311832E+10 | 0.40 | 6249.05 | 02-NOV-16:00 | 1.27 |
December | 0.224579E+10 | 0.34 | 4586.43 | 22-DEC-17:00 | 1.06 |
Annual Sum or Average | 0.545330E+11 | 0.49 | |||
Minimum of Months | 0.182554E+10 | 0.32 | 4188.59 | 1.01 | |
Maximum of Months | 0.737496E+10 | 0.68 | 12400.84 | 1.96 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.193741E+10 | 0.34 | 4045.98 | 27-JAN-16:40 | 1.06 |
February | 0.141708E+10 | 0.31 | 2821.32 | 22-FEB-16:30 | 0.86 |
March | 0.198109E+10 | 0.35 | 4565.94 | 20-MAR-14:30 | 1.13 |
April | 0.412859E+10 | 0.50 | 8126.19 | 24-APR-15:30 | 1.62 |
May | 0.531694E+10 | 0.57 | 8329.34 | 08-MAY-16:00 | 1.64 |
June | 0.730393E+10 | 0.72 | 11014.22 | 05-JUN-04:02 | 1.96 |
July | 0.655443E+10 | 0.65 | 11014.22 | 10-JUL-04:02 | 1.95 |
August | 0.670450E+10 | 0.65 | 11014.22 | 01-AUG-04:02 | 1.94 |
September | 0.524945E+10 | 0.56 | 11014.22 | 18-SEP-04:02 | 1.96 |
October | 0.337889E+10 | 0.43 | 11014.22 | 02-OCT-04:02 | 1.94 |
November | 0.209941E+10 | 0.35 | 4946.15 | 02-NOV-15:40 | 1.18 |
December | 0.162724E+10 | 0.32 | 3401.38 | 22-DEC-16:40 | 0.96 |
Annual Sum or Average | 0.476990E+11 | 0.48 | |||
Minimum of Months | 0.141708E+10 | 0.31 | 2821.32 | 0.86 | |
Maximum of Months | 0.730393E+10 | 0.72 | 11014.22 | 1.96 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.186678E+10 | 0.32 | 3381.37 | 27-JAN-16:30 | 0.86 |
February | 0.140780E+10 | 0.30 | 2447.80 | 22-FEB-16:30 | 0.73 |
March | 0.190426E+10 | 0.33 | 4303.82 | 16-MAR-15:40 | 0.98 |
April | 0.388030E+10 | 0.45 | 8158.51 | 14-APR-15:40 | 1.45 |
May | 0.506393E+10 | 0.51 | 8375.64 | 18-MAY-15:50 | 1.48 |
June | 0.728546E+10 | 0.66 | 11870.03 | 29-JUN-04:02 | 1.83 |
July | 0.636797E+10 | 0.59 | 12452.42 | 22-JUL-04:02 | 1.87 |
August | 0.647272E+10 | 0.58 | 10895.95 | 14-AUG-15:20 | 1.72 |
September | 0.495490E+10 | 0.50 | 10465.37 | 18-SEP-04:02 | 1.70 |
October | 0.308684E+10 | 0.39 | 11152.41 | 02-OCT-04:02 | 1.75 |
November | 0.190766E+10 | 0.32 | 4552.52 | 02-NOV-15:00 | 1.01 |
December | 0.161769E+10 | 0.31 | 2888.06 | 22-DEC-16:30 | 0.79 |
Annual Sum or Average | 0.458163E+11 | 0.44 | |||
Minimum of Months | 0.140780E+10 | 0.30 | 2447.80 | 0.73 | |
Maximum of Months | 0.728546E+10 | 0.66 | 12452.42 | 1.87 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:10 | 0.22 | 0.22 | 56.83 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:03 | 0.22 | 0.22 | 56.40 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:03 | 0.22 | 0.22 | 56.65 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:03 | 0.22 | 0.22 | 56.81 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:03 | 0.22 | 0.22 | 56.91 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 57.72 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 57.74 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 56.75 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 56.64 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 56.94 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:03 | 0.22 | 0.22 | 56.29 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:03 | 0.22 | 0.22 | 56.99 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 56.29 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.74 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.89 | 57.89 | 1576.30 | 5409.09 | 23-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.78 | 56.78 | 1571.58 | 5422.31 | 06-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.64 | 57.64 | 1598.87 | 5250.20 | 03-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.77 | 57.77 | 1387.51 | 4881.45 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.05 | 58.05 | 1318.21 | 4496.83 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.93 | 57.93 | 1248.56 | 4103.34 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.90 | 57.90 | 1102.77 | 3851.26 | 03-JUL-11:13 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 56.89 | 56.89 | 1224.10 | 3944.74 | 30-AUG-11:13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.83 | 56.83 | 1217.87 | 4269.64 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.42 | 56.42 | 1324.53 | 4686.81 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.60 | 56.60 | 1460.70 | 5073.41 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.68 | 57.68 | 1492.26 | 5332.44 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1375.87 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.42 | 56.42 | 1102.77 | 3851.26 | ||
Maximum of Months | 0.00 | 0.00 | 58.05 | 58.05 | 1598.87 | 5422.31 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.786554E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.373213E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.788079E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.175118E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.237008E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.341111E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.329577E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.339696E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.282736E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.166380E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.855769E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.533712E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.220536E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.373213E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.341111E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.585249E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.247644E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.586885E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.157011E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.215451E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.319349E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.292076E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.294667E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.234029E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.130297E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.600757E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.393626E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.188430E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.247644E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.319349E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.684461E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.357965E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.671719E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.168202E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.232426E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.353102E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.317432E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.316743E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.246448E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.134382E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.641258E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.629430E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.206722E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.357965E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.353102E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.261789E+10 | 0.177383E+11 | 0.780986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182554E+10 | 0.400265E+10 | 0.813976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.255890E+10 | 0.171784E+11 | 0.935968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.450542E+10 | 0.478301E+11 | 0.142470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.579727E+10 | 0.637072E+11 | 7776262.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.737496E+10 | 0.851688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.695174E+10 | 0.881133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.706581E+10 | 0.917145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.604796E+10 | 0.797566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.442342E+10 | 0.448220E+11 | 0.277115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.311832E+10 | 0.202486E+11 | 0.388428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.224579E+10 | 0.844509E+10 | 0.109553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.545330E+11 | 0.568725E+12 | 0.444224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.182554E+10 | 0.400265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.737496E+10 | 0.917145E+11 | 0.109553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.193741E+10 | 0.144263E+11 | 0.262148E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141708E+10 | 0.330843E+10 | 0.209694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198109E+10 | 0.145137E+11 | 0.228297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.412859E+10 | 0.429082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.531694E+10 | 0.576942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.730393E+10 | 0.783582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.655443E+10 | 0.768277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.670450E+10 | 0.775518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.524945E+10 | 0.648494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.337889E+10 | 0.358126E+11 | 10899678.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209941E+10 | 0.151489E+11 | 68799642.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162724E+10 | 0.659325E+10 | 0.990173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.476990E+11 | 0.487993E+12 | 0.177001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141708E+10 | 0.330843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.730393E+10 | 0.783582E+11 | 0.990173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.186678E+10 | 0.143313E+11 | 0.136582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140780E+10 | 0.339257E+10 | 0.140802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190426E+10 | 0.152250E+11 | 0.103718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.388030E+10 | 0.474929E+11 | 6544733.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.506393E+10 | 0.639836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.728546E+10 | 0.883743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.636797E+10 | 0.855023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.647272E+10 | 0.851901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.495490E+10 | 0.697415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.308684E+10 | 0.373236E+11 | 0.204927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190766E+10 | 0.148877E+11 | 0.716665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161769E+10 | 0.643520E+10 | 0.366606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.458163E+11 | 0.531880E+12 | 0.840522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140780E+10 | 0.339257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.728546E+10 | 0.883743E+11 | 0.366606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.261789E+10 | 0.00 | 0.00 | 0.00 | 0.447686E+10 | 0.770780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182554E+10 | 0.00 | 0.00 | 0.00 | 0.109417E+10 | 0.812425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.255890E+10 | 0.00 | 0.00 | 0.00 | 0.442254E+10 | 0.899345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.450542E+10 | 0.00 | 0.00 | 0.00 | 0.128639E+11 | 0.142470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.579727E+10 | 0.00 | 0.00 | 0.00 | 0.178958E+11 | 7776262.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.737496E+10 | 0.00 | 0.00 | 0.00 | 0.267361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.695174E+10 | 0.00 | 0.00 | 0.00 | 0.260060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.706581E+10 | 0.00 | 0.00 | 0.00 | 0.269038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.604796E+10 | 0.00 | 0.00 | 0.00 | 0.222256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.442342E+10 | 0.00 | 0.00 | 0.00 | 0.119374E+11 | 0.277115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.311832E+10 | 0.00 | 0.00 | 0.00 | 0.505213E+10 | 0.387237E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.224579E+10 | 0.00 | 0.00 | 0.00 | 0.218741E+10 | 0.903918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.545330E+11 | 0.00 | 0.00 | 0.00 | 0.161802E+12 | 0.420107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.182554E+10 | 0.00 | 0.00 | 0.00 | 0.109417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.737496E+10 | 0.00 | 0.00 | 0.00 | 0.269038E+11 | 0.903918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.193741E+10 | 0.00 | 0.00 | 0.00 | 0.369727E+10 | 0.217810E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141708E+10 | 0.00 | 0.00 | 0.00 | 0.910167E+09 | 0.149192E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198109E+10 | 0.00 | 0.00 | 0.00 | 0.377270E+10 | 0.115064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.412859E+10 | 0.00 | 0.00 | 0.00 | 0.115726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.531694E+10 | 0.00 | 0.00 | 0.00 | 0.162282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.730393E+10 | 0.00 | 0.00 | 0.00 | 0.246310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.655443E+10 | 0.00 | 0.00 | 0.00 | 0.226532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.670450E+10 | 0.00 | 0.00 | 0.00 | 0.227622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.524945E+10 | 0.00 | 0.00 | 0.00 | 0.181534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.337889E+10 | 0.00 | 0.00 | 0.00 | 0.964928E+10 | 1560061.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209941E+10 | 0.00 | 0.00 | 0.00 | 0.386351E+10 | 44651775.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162724E+10 | 0.00 | 0.00 | 0.00 | 0.173914E+10 | 0.569876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.476990E+11 | 0.00 | 0.00 | 0.00 | 0.139633E+12 | 0.109815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141708E+10 | 0.00 | 0.00 | 0.00 | 0.910167E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.730393E+10 | 0.00 | 0.00 | 0.00 | 0.246310E+11 | 0.569876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.186678E+10 | 0.00 | 0.00 | 0.00 | 0.373632E+10 | 0.124152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140780E+10 | 0.00 | 0.00 | 0.00 | 0.940543E+09 | 0.123131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190426E+10 | 0.00 | 0.00 | 0.00 | 0.399735E+10 | 0.815577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.388030E+10 | 0.00 | 0.00 | 0.00 | 0.129334E+11 | 6544733.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.506393E+10 | 0.00 | 0.00 | 0.00 | 0.181786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.728546E+10 | 0.00 | 0.00 | 0.00 | 0.280247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.636797E+10 | 0.00 | 0.00 | 0.00 | 0.253753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.647272E+10 | 0.00 | 0.00 | 0.00 | 0.252016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.495490E+10 | 0.00 | 0.00 | 0.00 | 0.196899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.308684E+10 | 0.00 | 0.00 | 0.00 | 0.101855E+11 | 0.165887E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190766E+10 | 0.00 | 0.00 | 0.00 | 0.386331E+10 | 0.641610E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161769E+10 | 0.00 | 0.00 | 0.00 | 0.172378E+10 | 0.295284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.458163E+11 | 0.00 | 0.00 | 0.00 | 0.153850E+12 | 0.705528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140780E+10 | 0.00 | 0.00 | 0.00 | 0.940543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.728546E+10 | 0.00 | 0.00 | 0.00 | 0.280247E+11 | 0.295284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118275E+10 | 3193717.72 | 0.00 | 35715480.94 | 21103.32 | 0.00 | 0.122796E+11 | 0.00 | 0.90 |
February | 0.811874E+09 | 0.00 | 0.00 | 34005152.70 | 2318097.91 | 0.00 | 0.155316E+11 | 0.00 | 0.85 |
March | 0.765048E+09 | 17561118.95 | 0.00 | 40348962.42 | 710718.76 | 0.00 | 0.137395E+11 | 0.00 | 0.94 |
April | 0.524770E+09 | 0.642201E+09 | 0.00 | 26413159.24 | 58212396.64 | 0.00 | 0.537553E+10 | 0.00 | 0.69 |
May | 0.324791E+09 | 0.134038E+10 | 0.00 | 17399926.95 | 44165324.83 | 0.00 | 0.242462E+10 | 0.00 | 0.53 |
June | 0.145487E+09 | 0.345246E+10 | 0.00 | 5606504.50 | 86028678.06 | 0.00 | 0.653843E+09 | 0.00 | 0.37 |
July | 65660182.95 | 0.464535E+10 | 0.00 | 1691554.47 | 0.182574E+09 | 0.00 | 0.196864E+09 | 0.00 | 0.33 |
August | 59745012.56 | 0.472585E+10 | 0.00 | 2940964.83 | 0.120417E+09 | 0.00 | 0.243788E+09 | 0.00 | 0.41 |
September | 93141630.86 | 0.326421E+10 | 0.00 | 9336825.55 | 0.405974E+09 | 0.00 | 0.794725E+09 | 0.00 | 0.50 |
October | 0.564329E+09 | 0.734105E+09 | 0.00 | 32845274.24 | 37546361.05 | 0.00 | 0.926401E+10 | 0.00 | 0.84 |
November | 0.984289E+09 | 17132074.31 | 0.00 | 42883428.93 | 13532779.29 | 0.00 | 0.140115E+11 | 0.00 | 1.00 |
December | 0.977169E+09 | 982759.90 | 0.00 | 37466227.59 | 190679.82 | 0.00 | 0.154696E+11 | 0.00 | 0.81 |
Annual Sum or Average | 0.649905E+10 | 0.188434E+11 | 0.00 | 0.286653E+09 | 0.951691E+09 | 0.00 | 0.899851E+11 | 0.00 | 0.68 |
Minimum of Months | 59745012.56 | 0.00 | 0.00 | 1691554.47 | 21103.32 | 0.00 | 0.196864E+09 | 0.00 | 0.33 |
Maximum of Months | 0.118275E+10 | 0.472585E+10 | 0.00 | 42883428.93 | 0.405974E+09 | 0.00 | 0.155316E+11 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.338935E+10 | 23302.75 | 0.00 | 11890732.09 | 5518490.44 | 7618333.67 | 0.467928E+10 | 0.00 | 0.53 |
February | 0.444970E+10 | 0.00 | 0.00 | 8837026.49 | 2931804.77 | 0.00 | 0.546357E+10 | 0.00 | 0.52 |
March | 0.325063E+10 | 3414910.52 | 0.00 | 15167749.03 | 853958.95 | 0.00 | 0.572998E+10 | 0.00 | 0.58 |
April | 0.771332E+09 | 0.426344E+09 | 0.00 | 17397114.49 | 94000020.16 | 0.00 | 0.322094E+10 | 0.00 | 0.49 |
May | 0.560493E+09 | 0.998554E+09 | 0.00 | 12722929.57 | 50729761.89 | 0.00 | 0.150548E+10 | 0.00 | 0.41 |
June | 0.183392E+09 | 0.293278E+10 | 0.00 | 4201278.29 | 88222495.77 | 0.00 | 0.504892E+09 | 0.00 | 0.32 |
July | 66183380.53 | 0.370815E+10 | 0.00 | 1535508.78 | 0.145159E+09 | 0.00 | 0.154878E+09 | 0.00 | 0.29 |
August | 73300679.23 | 0.367547E+10 | 0.00 | 1993911.65 | 0.103352E+09 | 0.00 | 0.156426E+09 | 0.00 | 0.35 |
September | 0.126603E+09 | 0.250772E+10 | 0.00 | 7177465.26 | 0.215114E+09 | 0.00 | 0.473961E+09 | 0.00 | 0.39 |
October | 0.104338E+10 | 0.580975E+09 | 0.00 | 17091455.82 | 22491486.79 | 0.00 | 0.481338E+10 | 0.00 | 0.54 |
November | 0.265916E+10 | 9956362.57 | 0.00 | 17032915.78 | 14721610.16 | 0.00 | 0.611956E+10 | 0.00 | 0.59 |
December | 0.537791E+10 | 162.25 | 0.00 | 6936674.55 | 2898740.88 | 0.00 | 0.414129E+10 | 0.00 | 0.48 |
Annual Sum or Average | 0.219514E+11 | 0.148434E+11 | 0.00 | 0.121985E+09 | 0.745993E+09 | 7618333.67 | 0.369636E+11 | 0.00 | 0.46 |
Minimum of Months | 66183380.53 | 0.00 | 0.00 | 1535508.78 | 853958.95 | 0.00 | 0.154878E+09 | 0.00 | 0.29 |
Maximum of Months | 0.537791E+10 | 0.370815E+10 | 0.00 | 17397114.49 | 0.215114E+09 | 7618333.67 | 0.611956E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.453285E+10 | 0.00 | 0.00 | 6458051.57 | 262788.73 | 35396367.11 | 0.268172E+10 | 0.00 | 0.54 |
February | 0.586038E+10 | 0.00 | 0.00 | 4040176.51 | 3610900.68 | 11399552.71 | 0.328610E+10 | 0.00 | 0.51 |
March | 0.449425E+10 | 1230326.36 | 0.00 | 9714095.88 | 1157838.07 | 3882640.21 | 0.371498E+10 | 0.00 | 0.57 |
April | 0.101396E+10 | 0.275031E+09 | 0.00 | 16172315.07 | 76409439.30 | 0.00 | 0.217960E+10 | 0.00 | 0.46 |
May | 0.497489E+09 | 0.732606E+09 | 0.00 | 13159807.57 | 39662117.48 | 0.00 | 0.842195E+09 | 0.00 | 0.36 |
June | 0.255725E+09 | 0.261184E+10 | 0.00 | 3002927.75 | 83296599.34 | 0.00 | 0.222273E+09 | 0.00 | 0.30 |
July | 43008668.94 | 0.339851E+10 | 0.00 | 1107270.53 | 0.191227E+09 | 0.00 | 88397734.81 | 0.00 | 0.27 |
August | 69653520.21 | 0.342738E+10 | 0.00 | 1235360.70 | 0.111312E+09 | 0.00 | 56693684.82 | 0.00 | 0.32 |
September | 0.119604E+09 | 0.229252E+10 | 0.00 | 6095555.90 | 0.272938E+09 | 0.00 | 0.241920E+09 | 0.00 | 0.36 |
October | 0.171588E+10 | 0.468298E+09 | 0.00 | 12545439.28 | 70651043.75 | 0.00 | 0.304686E+10 | 0.00 | 0.49 |
November | 0.387435E+10 | 11801238.95 | 0.00 | 10489749.79 | 20653108.32 | 1796328.14 | 0.384589E+10 | 0.00 | 0.57 |
December | 0.665514E+10 | 0.00 | 0.00 | 2573319.93 | 4966290.50 | 90719654.01 | 0.191858E+10 | 0.00 | 0.47 |
Annual Sum or Average | 0.291323E+11 | 0.132192E+11 | 0.00 | 86594070.49 | 0.876147E+09 | 0.143195E+09 | 0.221252E+11 | 0.00 | 0.44 |
Minimum of Months | 43008668.94 | 0.00 | 0.00 | 1107270.53 | 262788.73 | 0.00 | 56693684.82 | 0.00 | 0.27 |
Maximum of Months | 0.665514E+10 | 0.342738E+10 | 0.00 | 16172315.07 | 0.272938E+09 | 90719654.01 | 0.384589E+10 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125850E+10 | 0.00 | 0.00 | 614543.71 | 61000.82 | 0.146853E+09 | 0.225808E+09 | 0.00 | 0.57 |
February | 0.174870E+10 | 0.00 | 0.00 | 161191.98 | 838193.85 | 0.134236E+09 | 0.177056E+09 | 0.00 | 0.54 |
March | 0.131467E+10 | 315338.83 | 0.00 | 1594927.59 | 268767.50 | 0.104257E+09 | 0.436955E+09 | 0.00 | 0.62 |
April | 0.352082E+09 | 94844161.17 | 0.00 | 3490024.05 | 14344132.45 | 249198.30 | 0.341862E+09 | 0.00 | 0.52 |
May | 0.165458E+09 | 0.269160E+09 | 0.00 | 3042398.80 | 9243194.98 | 0.00 | 0.135253E+09 | 0.00 | 0.48 |
June | 68535591.02 | 0.106585E+10 | 0.00 | 592326.50 | 15369980.01 | 0.00 | 37222281.30 | 0.00 | 0.50 |
July | 17055937.93 | 0.122198E+10 | 0.00 | 225189.80 | 41179735.85 | 0.00 | 12867239.53 | 0.00 | 0.43 |
August | 20363300.64 | 0.111014E+10 | 0.00 | 187243.48 | 27325350.34 | 0.00 | 6185272.00 | 0.00 | 0.47 |
September | 48417755.58 | 0.706163E+09 | 0.00 | 1394903.20 | 67069720.99 | 0.00 | 39223456.71 | 0.00 | 0.47 |
October | 0.679885E+09 | 0.133959E+09 | 0.00 | 2127844.70 | 14320059.38 | 21064333.89 | 0.324203E+09 | 0.00 | 0.53 |
November | 0.118650E+10 | 1257168.49 | 0.00 | 1254008.27 | 6257056.19 | 91871338.22 | 0.386759E+09 | 0.00 | 0.58 |
December | 0.153910E+10 | 0.00 | 0.00 | 113454.59 | 1152818.79 | 0.388111E+09 | 67499727.46 | 0.00 | 0.50 |
Annual Sum or Average | 0.839926E+10 | 0.460368E+10 | 0.00 | 14798056.67 | 0.197430E+09 | 0.886642E+09 | 0.219089E+10 | 0.00 | 0.52 |
Minimum of Months | 17055937.93 | 0.00 | 0.00 | 113454.59 | 61000.82 | 0.00 | 6185272.00 | 0.00 | 0.43 |
Maximum of Months | 0.174870E+10 | 0.122198E+10 | 0.00 | 3490024.05 | 67069720.99 | 0.388111E+09 | 0.436955E+09 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.760287E+09 | 0.00 | 0.00 | 1437514.45 | 51790.23 | 73412355.06 | 0.609811E+09 | 0.00 | 0.81 |
February | 0.106378E+10 | 0.00 | 0.00 | 777012.74 | 711633.98 | 76392863.53 | 0.653411E+09 | 0.00 | 0.74 |
March | 0.781964E+09 | 739891.80 | 0.00 | 2620301.58 | 40496.66 | 53600670.21 | 0.934712E+09 | 0.00 | 0.93 |
April | 0.198738E+09 | 90183316.61 | 0.00 | 5140798.88 | 10775251.33 | 0.00 | 0.703674E+09 | 0.00 | 1.00 |
May | 0.107715E+09 | 0.211885E+09 | 0.00 | 4383465.85 | 7438052.75 | 0.00 | 0.280107E+09 | 0.00 | 0.84 |
June | 57338312.48 | 0.874914E+09 | 0.00 | 656801.28 | 12899136.25 | 0.00 | 38677435.47 | 0.00 | 0.71 |
July | 14203724.24 | 0.107248E+10 | 0.00 | 244967.06 | 38706379.21 | 0.00 | 15094124.58 | 0.00 | 0.61 |
August | 16136811.74 | 0.102704E+10 | 0.00 | 183690.67 | 25061521.36 | 0.00 | 7826905.87 | 0.00 | 0.68 |
September | 36657170.75 | 0.662522E+09 | 0.00 | 1274186.05 | 48686710.96 | 0.00 | 38976627.19 | 0.00 | 0.68 |
October | 0.374495E+09 | 0.127638E+09 | 0.00 | 3031005.36 | 10179011.51 | 10774441.86 | 0.681839E+09 | 0.00 | 0.86 |
November | 0.768380E+09 | 664687.60 | 0.00 | 2027285.34 | 5683971.45 | 36111029.99 | 0.697849E+09 | 0.00 | 0.84 |
December | 0.129367E+10 | 0.00 | 0.00 | 381887.03 | 978753.33 | 0.193755E+09 | 0.203601E+09 | 0.00 | 0.68 |
Annual Sum or Average | 0.547337E+10 | 0.406807E+10 | 0.00 | 22158916.30 | 0.161213E+09 | 0.444046E+09 | 0.486558E+10 | 0.00 | 0.78 |
Minimum of Months | 14203724.24 | 0.00 | 0.00 | 183690.67 | 40496.66 | 0.00 | 7826905.87 | 0.00 | 0.61 |
Maximum of Months | 0.129367E+10 | 0.107248E+10 | 0.00 | 5140798.88 | 48686710.96 | 0.193755E+09 | 0.934712E+09 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.687535E+09 | 242411.52 | 0.00 | 9491067.48 | 0.00 | 65614965.05 | 0.286382E+10 | 0.00 | 1.45 |
February | 0.100257E+10 | 0.00 | 0.00 | 5291907.04 | 919718.77 | 95535783.67 | 0.283054E+10 | 0.00 | 0.99 |
March | 0.934919E+09 | 910670.10 | 0.00 | 5711173.59 | 52338.06 | 86309019.35 | 0.178542E+10 | 0.00 | 0.98 |
April | 0.370249E+09 | 0.147567E+09 | 0.00 | 5370945.20 | 14246660.13 | 273435.97 | 0.539669E+09 | 0.00 | 0.72 |
May | 0.210646E+09 | 0.292915E+09 | 0.00 | 3090114.34 | 10411426.99 | 0.00 | 0.111403E+09 | 0.00 | 0.51 |
June | 82607828.46 | 0.103639E+10 | 0.00 | 414178.95 | 17946057.05 | 0.00 | 26631968.70 | 0.00 | 0.48 |
July | 20691051.27 | 0.122466E+10 | 0.00 | 193709.79 | 49910659.04 | 0.00 | 9712328.86 | 0.00 | 0.44 |
August | 24094799.06 | 0.126736E+10 | 0.00 | 181972.06 | 30412593.58 | 0.00 | 4859906.58 | 0.00 | 0.53 |
September | 52331802.91 | 0.945110E+09 | 0.00 | 2003737.14 | 69553744.65 | 0.00 | 54209767.32 | 0.00 | 0.60 |
October | 0.430357E+09 | 0.224795E+09 | 0.00 | 7377257.65 | 12664963.25 | 11692222.90 | 0.151391E+10 | 0.00 | 1.02 |
November | 0.714773E+09 | 3275823.16 | 0.00 | 8574371.66 | 5269601.18 | 28990823.34 | 0.281591E+10 | 0.00 | 1.32 |
December | 0.888785E+09 | 366683.82 | 0.00 | 6941139.74 | 1033503.30 | 0.169944E+09 | 0.287212E+10 | 0.00 | 1.10 |
Annual Sum or Average | 0.541956E+10 | 0.514358E+10 | 0.00 | 54641574.64 | 0.212421E+09 | 0.458360E+09 | 0.154282E+11 | 0.00 | 0.84 |
Minimum of Months | 20691051.27 | 0.00 | 0.00 | 181972.06 | 0.00 | 0.00 | 4859906.58 | 0.00 | 0.44 |
Maximum of Months | 0.100257E+10 | 0.126736E+10 | 0.00 | 9491067.48 | 69553744.65 | 0.169944E+09 | 0.287212E+10 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110372E+10 | 111614.41 | 0.00 | 1910761.94 | 0.00 | 0.125659E+09 | 0.542951E+09 | 0.00 | 1.04 |
February | 0.142877E+10 | 0.00 | 0.00 | 1099394.26 | 814056.84 | 0.123227E+09 | 0.660421E+09 | 0.00 | 0.91 |
March | 0.120108E+10 | 325086.97 | 0.00 | 2303552.47 | 214702.75 | 0.101061E+09 | 0.655885E+09 | 0.00 | 1.06 |
April | 0.362031E+09 | 0.118199E+09 | 0.00 | 3748413.60 | 7104467.75 | 242022.27 | 0.349243E+09 | 0.00 | 0.88 |
May | 0.196651E+09 | 0.291332E+09 | 0.00 | 2119736.68 | 3977826.01 | 0.00 | 68897946.27 | 0.00 | 0.69 |
June | 75936250.08 | 0.949525E+09 | 0.00 | 250419.54 | 12562912.92 | 0.00 | 19057131.14 | 0.00 | 0.66 |
July | 18921390.28 | 0.941384E+09 | 0.00 | 121101.90 | 48502654.14 | 0.00 | 7483952.81 | 0.00 | 0.54 |
August | 22255659.27 | 0.879726E+09 | 0.00 | 117826.18 | 36186192.16 | 0.00 | 3106155.65 | 0.00 | 0.61 |
September | 49121583.18 | 0.563310E+09 | 0.00 | 1179708.76 | 74704273.52 | 0.00 | 31611514.24 | 0.00 | 0.62 |
October | 0.611332E+09 | 0.106722E+09 | 0.00 | 2732833.61 | 20070040.63 | 19294827.84 | 0.467303E+09 | 0.00 | 0.87 |
November | 0.106921E+10 | 1361706.39 | 0.00 | 2268572.64 | 6076875.15 | 81753464.72 | 0.675670E+09 | 0.00 | 1.03 |
December | 0.127833E+10 | 0.00 | 0.00 | 898024.86 | 1119621.70 | 0.315128E+09 | 0.456034E+09 | 0.00 | 0.84 |
Annual Sum or Average | 0.741735E+10 | 0.385200E+10 | 0.00 | 18750346.46 | 0.211334E+09 | 0.766365E+09 | 0.393766E+10 | 0.00 | 0.81 |
Minimum of Months | 18921390.28 | 0.00 | 0.00 | 117826.18 | 0.00 | 0.00 | 3106155.65 | 0.00 | 0.54 |
Maximum of Months | 0.142877E+10 | 0.949525E+09 | 0.00 | 3748413.60 | 74704273.52 | 0.315128E+09 | 0.675670E+09 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.146418E+10 | 168324.10 | 0.00 | 459754.96 | 315664.79 | 36560843.95 | 0.174245E+09 | 0.00 | 0.51 |
February | 0.195355E+10 | 0.00 | 0.00 | 35077.19 | 488456.03 | 17390374.13 | 65182778.65 | 0.00 | 0.50 |
March | 0.154924E+10 | 1852482.93 | 0.00 | 657423.84 | 419694.22 | 25458189.73 | 0.182787E+09 | 0.00 | 0.52 |
April | 0.443035E+09 | 0.113903E+09 | 0.00 | 1930871.57 | 17452982.03 | 0.00 | 0.276549E+09 | 0.00 | 0.43 |
May | 0.244100E+09 | 0.289694E+09 | 0.00 | 1500263.98 | 9694417.28 | 0.00 | 0.146999E+09 | 0.00 | 0.40 |
June | 92511901.55 | 0.968083E+09 | 0.00 | 527356.10 | 21017011.68 | 0.00 | 52701728.05 | 0.00 | 0.42 |
July | 27084185.07 | 0.124284E+10 | 0.00 | 204466.65 | 43797144.19 | 0.00 | 22809074.56 | 0.00 | 0.39 |
August | 29965925.55 | 0.118468E+10 | 0.00 | 273640.55 | 31980378.59 | 0.00 | 22431281.44 | 0.00 | 0.44 |
September | 57371122.26 | 0.811573E+09 | 0.00 | 1352671.45 | 91624587.35 | 0.00 | 89543650.85 | 0.00 | 0.49 |
October | 0.561535E+09 | 0.159314E+09 | 0.00 | 2583906.48 | 12059536.30 | 0.00 | 0.617592E+09 | 0.00 | 0.55 |
November | 0.116033E+10 | 1400289.90 | 0.00 | 2207256.26 | 3646427.17 | 151676.37 | 0.666050E+09 | 0.00 | 0.57 |
December | 0.193578E+10 | 0.00 | 0.00 | 211553.48 | 165201.29 | 34174335.88 | 0.128034E+09 | 0.00 | 0.48 |
Annual Sum or Average | 0.951869E+10 | 0.477351E+10 | 0.00 | 11944242.51 | 0.232662E+09 | 0.113735E+09 | 0.244492E+10 | 0.00 | 0.48 |
Minimum of Months | 27084185.07 | 0.00 | 0.00 | 35077.19 | 165201.29 | 0.00 | 22431281.44 | 0.00 | 0.39 |
Maximum of Months | 0.195355E+10 | 0.124284E+10 | 0.00 | 2583906.48 | 91624587.35 | 36560843.95 | 0.666050E+09 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.802982E+09 | 227728.82 | 0.00 | 1870415.42 | 223453.07 | 11393813.76 | 0.708922E+09 | 0.00 | 0.74 |
February | 0.104711E+10 | 0.00 | 0.00 | 913581.27 | 399083.71 | 4942863.99 | 0.687541E+09 | 0.00 | 0.67 |
March | 0.854353E+09 | 1981012.10 | 0.00 | 2063987.12 | 122357.33 | 5010161.62 | 0.747911E+09 | 0.00 | 0.77 |
April | 0.230863E+09 | 0.124793E+09 | 0.00 | 3847791.70 | 10079225.49 | 0.00 | 0.701113E+09 | 0.00 | 0.89 |
May | 0.165784E+09 | 0.263358E+09 | 0.00 | 2809790.86 | 7641355.88 | 0.00 | 0.313676E+09 | 0.00 | 0.75 |
June | 61609099.74 | 0.837676E+09 | 0.00 | 693402.67 | 14615429.39 | 0.00 | 72125935.79 | 0.00 | 0.62 |
July | 18334654.86 | 0.109927E+10 | 0.00 | 255487.83 | 32922403.99 | 0.00 | 28847188.75 | 0.00 | 0.56 |
August | 21713410.64 | 0.108229E+10 | 0.00 | 325688.35 | 22723932.33 | 0.00 | 26477766.31 | 0.00 | 0.64 |
September | 46327743.98 | 0.732790E+09 | 0.00 | 1293731.08 | 64221918.18 | 0.00 | 90468416.04 | 0.00 | 0.71 |
October | 0.299769E+09 | 0.146174E+09 | 0.00 | 3856107.53 | 7060817.90 | 0.00 | 0.105620E+10 | 0.00 | 0.96 |
November | 0.643387E+09 | 1172829.53 | 0.00 | 3447785.62 | 2979243.96 | 0.00 | 0.115091E+10 | 0.00 | 0.89 |
December | 0.116989E+10 | 36055.42 | 0.00 | 1045408.21 | 98919.15 | 7854538.10 | 0.614288E+09 | 0.00 | 0.66 |
Annual Sum or Average | 0.536213E+10 | 0.428977E+10 | 0.00 | 22423177.67 | 0.163088E+09 | 29201377.46 | 0.619848E+10 | 0.00 | 0.74 |
Minimum of Months | 18334654.86 | 0.00 | 0.00 | 255487.83 | 98919.15 | 0.00 | 26477766.31 | 0.00 | 0.56 |
Maximum of Months | 0.116989E+10 | 0.109927E+10 | 0.00 | 3856107.53 | 64221918.18 | 11393813.76 | 0.115091E+10 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.596567E+09 | 2206704.21 | 0.00 | 8306282.08 | 4457.11 | 0.296075E+09 | 0.223074E+10 | 0.00 | 1.19 |
February | 0.129610E+10 | 0.00 | 0.00 | 1910892.04 | 489591.83 | 0.331347E+09 | 0.113803E+10 | 0.00 | 0.69 |
March | 0.113069E+10 | 4591661.74 | 0.00 | 2933233.10 | 150106.73 | 0.361096E+09 | 0.677542E+09 | 0.00 | 0.70 |
April | 0.424176E+09 | 0.243730E+09 | 0.00 | 3221203.85 | 12375444.61 | 65971099.80 | 0.323611E+09 | 0.00 | 0.62 |
May | 0.299929E+09 | 0.435719E+09 | 0.00 | 1472979.34 | 9767124.04 | 5071978.40 | 78638875.95 | 0.00 | 0.49 |
June | 0.111671E+09 | 0.126305E+10 | 0.00 | 353313.01 | 21237018.58 | 0.00 | 23955911.47 | 0.00 | 0.49 |
July | 31250702.19 | 0.158485E+10 | 0.00 | 179956.79 | 42895833.28 | 0.00 | 15035264.54 | 0.00 | 0.47 |
August | 34737499.71 | 0.170561E+10 | 0.00 | 257411.20 | 31278366.12 | 0.00 | 15457634.38 | 0.00 | 0.57 |
September | 64788799.44 | 0.124854E+10 | 0.00 | 1902301.63 | 77146270.67 | 0.00 | 91641649.67 | 0.00 | 0.66 |
October | 0.406636E+09 | 0.299356E+09 | 0.00 | 6796953.93 | 5581354.92 | 0.124845E+09 | 0.138283E+10 | 0.00 | 1.02 |
November | 0.555983E+09 | 3311536.08 | 0.00 | 8847175.77 | 3078192.99 | 0.169912E+09 | 0.258868E+10 | 0.00 | 1.18 |
December | 0.985937E+09 | 176424.84 | 0.00 | 5828004.03 | 81080.64 | 0.365942E+09 | 0.220129E+10 | 0.00 | 0.97 |
Annual Sum or Average | 0.593847E+10 | 0.679114E+10 | 0.00 | 42009706.77 | 0.204085E+09 | 0.172026E+10 | 0.107675E+11 | 0.00 | 0.76 |
Minimum of Months | 31250702.19 | 0.00 | 0.00 | 179956.79 | 4457.11 | 0.00 | 15035264.54 | 0.00 | 0.47 |
Maximum of Months | 0.129610E+10 | 0.170561E+10 | 0.00 | 8847175.77 | 77146270.67 | 0.365942E+09 | 0.258868E+10 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114560E+10 | 642891.86 | 0.00 | 1706964.75 | 16331.93 | 14683161.37 | 0.430785E+09 | 0.00 | 0.83 |
February | 0.144975E+10 | 0.00 | 0.00 | 803276.22 | 424357.30 | 11173592.13 | 0.442656E+09 | 0.00 | 0.75 |
March | 0.120940E+10 | 2428646.52 | 0.00 | 1429481.34 | 0.00 | 8098482.34 | 0.388569E+09 | 0.00 | 0.80 |
April | 0.348285E+09 | 0.157245E+09 | 0.00 | 2328992.10 | 7483988.96 | 0.00 | 0.330021E+09 | 0.00 | 0.73 |
May | 0.213999E+09 | 0.336727E+09 | 0.00 | 1110966.17 | 3528070.03 | 0.00 | 0.117065E+09 | 0.00 | 0.60 |
June | 73225894.64 | 0.920017E+09 | 0.00 | 408064.30 | 12993996.11 | 0.00 | 45465329.00 | 0.00 | 0.57 |
July | 22437090.57 | 0.992841E+09 | 0.00 | 172590.00 | 34189138.63 | 0.00 | 18503779.40 | 0.00 | 0.48 |
August | 20216927.86 | 0.993154E+09 | 0.00 | 237043.62 | 20693712.34 | 0.00 | 24107897.67 | 0.00 | 0.57 |
September | 47806341.40 | 0.679288E+09 | 0.00 | 1042076.18 | 74209368.94 | 0.00 | 69016440.53 | 0.00 | 0.63 |
October | 0.417032E+09 | 0.138650E+09 | 0.00 | 3008391.63 | 7678589.76 | 0.00 | 0.703757E+09 | 0.00 | 0.84 |
November | 0.803302E+09 | 1981396.15 | 0.00 | 3260015.68 | 3029254.07 | 0.00 | 0.993994E+09 | 0.00 | 0.92 |
December | 0.142244E+10 | 322.34 | 0.00 | 1124471.79 | 143200.04 | 23874874.93 | 0.518342E+09 | 0.00 | 0.74 |
Annual Sum or Average | 0.717349E+10 | 0.422298E+10 | 0.00 | 16632333.78 | 0.164390E+09 | 57830110.76 | 0.408228E+10 | 0.00 | 0.71 |
Minimum of Months | 20216927.86 | 0.00 | 0.00 | 172590.00 | 0.00 | 0.00 | 18503779.40 | 0.00 | 0.48 |
Maximum of Months | 0.144975E+10 | 0.993154E+09 | 0.00 | 3260015.68 | 74209368.94 | 23874874.93 | 0.993994E+09 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125951E+10 | 4855.95 | 0.00 | 930557.85 | 1162552.68 | 32248176.85 | 0.275689E+09 | 0.00 | 0.48 |
February | 0.163027E+10 | 0.00 | 0.00 | 359341.85 | 617628.59 | 16994292.20 | 0.294829E+09 | 0.00 | 0.49 |
March | 0.120459E+10 | 885319.92 | 0.00 | 1921959.45 | 179899.25 | 18500532.23 | 0.541620E+09 | 0.00 | 0.55 |
April | 0.334761E+09 | 0.150117E+09 | 0.00 | 2966496.41 | 12778499.03 | 0.00 | 0.404406E+09 | 0.00 | 0.51 |
May | 0.178019E+09 | 0.372899E+09 | 0.00 | 2524420.72 | 10728542.72 | 0.00 | 0.230630E+09 | 0.00 | 0.51 |
June | 62610040.95 | 0.123175E+10 | 0.00 | 797650.31 | 14966679.21 | 0.00 | 83131963.34 | 0.00 | 0.52 |
July | 21883547.94 | 0.135339E+10 | 0.00 | 256611.65 | 31498854.70 | 0.00 | 25030142.61 | 0.00 | 0.46 |
August | 27064672.52 | 0.122377E+10 | 0.00 | 284226.21 | 24597480.56 | 0.00 | 16783213.29 | 0.00 | 0.49 |
September | 48971102.60 | 0.794408E+09 | 0.00 | 1420976.13 | 49841684.72 | 0.00 | 69095245.76 | 0.00 | 0.49 |
October | 0.599880E+09 | 0.158475E+09 | 0.00 | 2164441.08 | 8104260.64 | 0.00 | 0.441442E+09 | 0.00 | 0.51 |
November | 0.111959E+10 | 1579183.91 | 0.00 | 1847954.70 | 3452230.37 | 6782747.87 | 0.517600E+09 | 0.00 | 0.52 |
December | 0.170540E+10 | 0.00 | 0.00 | 212252.02 | 610697.37 | 0.111947E+09 | 0.111982E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.819255E+10 | 0.528729E+10 | 0.00 | 15686888.37 | 0.158539E+09 | 0.186472E+09 | 0.301224E+10 | 0.00 | 0.50 |
Minimum of Months | 21883547.94 | 0.00 | 0.00 | 212252.02 | 179899.25 | 0.00 | 16783213.29 | 0.00 | 0.45 |
Maximum of Months | 0.170540E+10 | 0.135339E+10 | 0.00 | 2966496.41 | 49841684.72 | 0.111947E+09 | 0.541620E+09 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.812246E+09 | 17360.57 | 0.00 | 1897236.62 | 1047058.00 | 16281044.43 | 0.749060E+09 | 0.00 | 0.76 |
February | 0.107769E+10 | 0.00 | 0.00 | 1124299.80 | 562935.76 | 9299551.24 | 0.804639E+09 | 0.00 | 0.74 |
March | 0.813941E+09 | 680270.69 | 0.00 | 2908557.88 | 163968.64 | 13121241.06 | 0.103577E+10 | 0.00 | 0.90 |
April | 0.210687E+09 | 0.134824E+09 | 0.00 | 4629982.68 | 11124680.03 | 0.00 | 0.825100E+09 | 0.00 | 1.01 |
May | 0.152724E+09 | 0.292547E+09 | 0.00 | 3672466.70 | 9465616.31 | 0.00 | 0.382055E+09 | 0.00 | 0.89 |
June | 58271229.85 | 0.984595E+09 | 0.00 | 813244.89 | 14807700.43 | 0.00 | 79973895.48 | 0.00 | 0.74 |
July | 20514340.71 | 0.115328E+10 | 0.00 | 266136.64 | 36285572.68 | 0.00 | 25714564.65 | 0.00 | 0.64 |
August | 25827268.03 | 0.108514E+10 | 0.00 | 286255.05 | 23549604.04 | 0.00 | 17096045.23 | 0.00 | 0.70 |
September | 46344960.03 | 0.702792E+09 | 0.00 | 1310922.58 | 40958747.43 | 0.00 | 67976292.73 | 0.00 | 0.71 |
October | 0.397279E+09 | 0.138549E+09 | 0.00 | 3052006.92 | 7650923.36 | 0.00 | 0.825653E+09 | 0.00 | 0.89 |
November | 0.801582E+09 | 1174928.97 | 0.00 | 2530688.80 | 3256142.99 | 2028511.58 | 0.853702E+09 | 0.00 | 0.83 |
December | 0.137623E+10 | 0.00 | 0.00 | 657139.16 | 556618.32 | 57983574.25 | 0.358852E+09 | 0.00 | 0.66 |
Annual Sum or Average | 0.579334E+10 | 0.449360E+10 | 0.00 | 23148937.72 | 0.149430E+09 | 98713922.56 | 0.602559E+10 | 0.00 | 0.79 |
Minimum of Months | 20514340.71 | 0.00 | 0.00 | 266136.64 | 163968.64 | 0.00 | 17096045.23 | 0.00 | 0.64 |
Maximum of Months | 0.137623E+10 | 0.115328E+10 | 0.00 | 4629982.68 | 40958747.43 | 57983574.25 | 0.103577E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.660718E+09 | 4440144.57 | 0.00 | 9801215.41 | 219263.36 | 14429029.19 | 0.283118E+10 | 0.00 | 1.29 |
February | 0.975037E+09 | 0.00 | 0.00 | 5880943.76 | 668932.93 | 4990098.92 | 0.295236E+10 | 0.00 | 0.99 |
March | 0.856013E+09 | 1446606.69 | 0.00 | 6179355.92 | 194842.87 | 12755160.67 | 0.183280E+10 | 0.00 | 0.91 |
April | 0.357354E+09 | 0.239099E+09 | 0.00 | 4271837.96 | 13219385.35 | 0.00 | 0.558387E+09 | 0.00 | 0.70 |
May | 0.221428E+09 | 0.415633E+09 | 0.00 | 2324899.61 | 11619726.80 | 0.00 | 0.188347E+09 | 0.00 | 0.54 |
June | 79137725.73 | 0.120510E+10 | 0.00 | 600341.34 | 19008957.06 | 0.00 | 60695248.95 | 0.00 | 0.50 |
July | 25462547.18 | 0.136571E+10 | 0.00 | 216970.87 | 40299917.66 | 0.00 | 19666383.21 | 0.00 | 0.46 |
August | 29500697.71 | 0.142136E+10 | 0.00 | 276380.48 | 24407909.56 | 0.00 | 16214779.85 | 0.00 | 0.55 |
September | 52279667.94 | 0.108052E+10 | 0.00 | 1919503.97 | 52996620.16 | 0.00 | 83550001.84 | 0.00 | 0.62 |
October | 0.393331E+09 | 0.274532E+09 | 0.00 | 6653827.21 | 7518408.62 | 0.00 | 0.158264E+10 | 0.00 | 1.02 |
November | 0.644138E+09 | 2379399.68 | 0.00 | 9659113.33 | 3738995.58 | 475008.31 | 0.292412E+10 | 0.00 | 1.24 |
December | 0.903829E+09 | 258901.09 | 0.00 | 8094935.27 | 474082.91 | 54507645.08 | 0.316775E+10 | 0.00 | 1.12 |
Annual Sum or Average | 0.519823E+10 | 0.601049E+10 | 0.00 | 55879325.14 | 0.174367E+09 | 87156942.18 | 0.162177E+11 | 0.00 | 0.83 |
Minimum of Months | 25462547.18 | 0.00 | 0.00 | 216970.87 | 194842.87 | 0.00 | 16214779.85 | 0.00 | 0.46 |
Maximum of Months | 0.975037E+09 | 0.142136E+10 | 0.00 | 9801215.41 | 52996620.16 | 54507645.08 | 0.316775E+10 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119772E+10 | 1545148.77 | 0.00 | 1991547.81 | 305945.66 | 27899634.40 | 0.484156E+09 | 0.00 | 0.89 |
February | 0.147927E+10 | 0.00 | 0.00 | 1225209.78 | 609103.02 | 20069363.52 | 0.640124E+09 | 0.00 | 0.86 |
March | 0.118741E+10 | 1044534.29 | 0.00 | 2377366.68 | 0.00 | 18380340.26 | 0.640544E+09 | 0.00 | 0.95 |
April | 0.364600E+09 | 0.186524E+09 | 0.00 | 2790401.52 | 6366850.02 | 0.00 | 0.353552E+09 | 0.00 | 0.84 |
May | 0.229278E+09 | 0.412369E+09 | 0.00 | 1459181.35 | 3641577.17 | 0.00 | 0.112052E+09 | 0.00 | 0.72 |
June | 77919416.45 | 0.113505E+10 | 0.00 | 399917.89 | 13275745.78 | 0.00 | 42257964.40 | 0.00 | 0.70 |
July | 23949036.41 | 0.106677E+10 | 0.00 | 141968.32 | 34166395.26 | 0.00 | 15000331.67 | 0.00 | 0.56 |
August | 29241761.58 | 0.100598E+10 | 0.00 | 159427.15 | 19575908.40 | 0.00 | 10346516.47 | 0.00 | 0.64 |
September | 61973703.87 | 0.652305E+09 | 0.00 | 1025972.67 | 49110001.48 | 0.00 | 43005824.92 | 0.00 | 0.64 |
October | 0.599658E+09 | 0.136186E+09 | 0.00 | 2457783.15 | 8515149.08 | 0.00 | 0.496599E+09 | 0.00 | 0.82 |
November | 0.105286E+10 | 1970374.03 | 0.00 | 2578579.68 | 3298988.59 | 6651782.40 | 0.735771E+09 | 0.00 | 0.92 |
December | 0.146146E+10 | 0.00 | 0.00 | 1078762.27 | 602267.47 | 0.109084E+09 | 0.473786E+09 | 0.00 | 0.78 |
Annual Sum or Average | 0.776533E+10 | 0.459974E+10 | 0.00 | 17686118.25 | 0.139468E+09 | 0.182085E+09 | 0.404719E+10 | 0.00 | 0.77 |
Minimum of Months | 23949036.41 | 0.00 | 0.00 | 141968.32 | 0.00 | 0.00 | 10346516.47 | 0.00 | 0.56 |
Maximum of Months | 0.147927E+10 | 0.113505E+10 | 0.00 | 2790401.52 | 49110001.48 | 0.109084E+09 | 0.735771E+09 | 0.00 | 0.95 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:17
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.199589E+12 | 0.108234E+11 | 0.00 | 0.188806E+12 | 0.584511E+11 |
February | 0.206240E+12 | 0.966218E+10 | 0.00 | 0.198005E+12 | 0.137082E+11 |
March | 0.260561E+12 | 0.110657E+11 | 0.00 | 0.192414E+12 | 0.592026E+11 |
April | 0.306957E+12 | 0.218997E+10 | 0.00 | 0.107123E+12 | 0.175601E+12 |
May | 0.297848E+12 | -869816423.1 | 0.00 | 0.643040E+11 | 0.237688E+12 |
June | 0.303027E+12 | -0.553038E+10 | 0.00 | -0.449046E+10 | 0.331293E+12 |
July | 0.280958E+12 | -0.868859E+10 | 0.00 | -0.329629E+11 | 0.324478E+12 |
August | 0.253423E+12 | -0.668349E+10 | 0.00 | -0.266819E+11 | 0.329324E+12 |
September | 0.219990E+12 | -0.435599E+10 | 0.00 | -0.222624E+11 | 0.274416E+12 |
October | 0.219200E+12 | 0.440518E+10 | 0.00 | 0.140194E+12 | 0.149742E+12 |
November | 0.201015E+12 | 0.992803E+10 | 0.00 | 0.190732E+12 | 0.630892E+11 |
December | 0.166750E+12 | 0.115846E+11 | 0.00 | 0.199323E+12 | 0.274552E+11 |
Annual Sum or Average | 0.291556E+13 | 0.335308E+11 | 0.00 | 0.119450E+13 | 0.204445E+13 |
Minimum of Months | 0.166750E+12 | -0.868859E+10 | 0.00 | -0.329629E+11 | 0.137082E+11 |