Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2023-10-16 08:35:13
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2002.85 | 402.00 | 402.00 |
Net Site Energy | 2002.85 | 402.00 | 402.00 |
Total Source Energy | 5593.84 | 1122.77 | 1122.77 |
Net Source Energy | 5593.84 | 1122.77 | 1122.77 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 299.88 | 244.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 112.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 281.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 102.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 115.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1643.18 | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 299.88 | 244.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 112.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 281.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 71.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 102.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 115.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 299.88 | 244.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 112.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 281.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 71.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 12.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 102.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 115.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 103.38 | 72.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 329.81 | 72.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 103.38 | 72.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 155.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 329.81 | 72.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1643.181 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1643.181 | 100.00 |
Total On-Site and Utility Electric Sources | 1643.181 | 100.00 |
Total Electricity End Uses | 1643.181 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 543.33 |
Time Setpoint Not Met During Occupied Cooling | 92.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2938.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.5763 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 7.5763 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 7.5763 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-JAN-08:09 | 10-JAN-21:00 | - | - | - | - | - | - | - | - | - | - | 04-JAN-12:09 |
Heating | 173914.64 | 153887.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 28079.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 47562.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 901.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6090.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1156.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 262106.25 | 155043.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 173914.64 | 153887.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 28079.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 901.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6090.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 1156.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 949.71 | 265.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 355.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 890.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 227.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2413.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 41.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 325.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 124.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5203.95 | 389.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 190.62 | 53.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 178.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 65.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 25.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1044.51 | 78.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 190.62 | 53.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 178.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 65.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 25.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1044.51 | 78.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.21 | 0.233449 | 0.251000 | 0.805799 | 0.622531 | 0.500000 | 0.001632 |
CORE_MID VAV BOX COMPONENT | 2.35 | 0.319054 | 0.335000 | 0.786911 | 0.850811 | 0.500000 | 0.001194 |
CORE_TOP VAV BOX COMPONENT | 2.53 | 0.296498 | 0.323000 | 0.816445 | 0.790660 | 0.500000 | 0.001285 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.801051 | 0.197231 | 0.215000 | 0.172226 | 0.525948 | 0.500000 | 0.001932 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.919884 | 0.108733 | 0.200000 | 0.183977 | 0.300000 | 0.500000 | 0.003504 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.25 | 0.126237 | 0.200000 | 0.250309 | 0.336633 | 0.500000 | 0.003018 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.06 | 0.094727 | 0.200000 | 0.211165 | 0.300000 | 0.500000 | 0.004022 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.611077 | 0.258546 | 0.278000 | 0.169879 | 0.689457 | 0.500000 | 0.001474 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.748561 | 0.133619 | 0.200000 | 0.149712 | 0.356316 | 0.500000 | 0.002851 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.981897 | 0.160904 | 0.200000 | 0.196379 | 0.429079 | 0.500000 | 0.002368 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.825140 | 0.121210 | 0.200000 | 0.165028 | 0.323227 | 0.500000 | 0.003143 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.690609 | 0.228771 | 0.240000 | 0.165746 | 0.610057 | 0.500000 | 0.001665 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.902723 | 0.110800 | 0.200000 | 0.180545 | 0.300000 | 0.500000 | 0.003439 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.13 | 0.139489 | 0.200000 | 0.226529 | 0.371972 | 0.500000 | 0.002731 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.967339 | 0.103392 | 0.200000 | 0.193468 | 0.300000 | 0.500000 | 0.003685 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 23537.44 |
CORE_MID VAV BOX REHEAT COIL | 28485.04 |
CORE_TOP VAV BOX REHEAT COIL | 49429.74 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 23398.73 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 15306.82 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 23586.44 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 15444.20 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17629.26 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11637.43 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 17796.04 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11748.21 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 18090.61 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 11902.93 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 18242.15 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 12018.65 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.19 | 1.49 | 6.38 | 2.54 | 5.67 | 5.67 | 0.300000 | 0.448125 | 5.67 |
PACU_VAV_MID | 3.02 | 1.55 | 6.04 | 3.04 | 5.12 | 5.12 | 0.300000 | 0.593552 | 5.12 |
PACU_VAV_TOP | 3.28 | 1.63 | 6.56 | 4.35 | 5.94 | 5.94 | 0.300000 | 0.732960 | 5.94 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.67 |
PACU_VAV_MID_OA_CONTROLLER | 5.12 |
PACU_VAV_TOP_OA_CONTROLLER | 5.94 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.67 | 93913.08 | 0.800655 | 1.89 | 31301.23 | 0.800655 |
PACU_VAV_MID COOLING COIL | 5.12 | 84903.69 | 0.800886 | 1.71 | 28298.40 | 0.800886 |
PACU_VAV_TOP COOLING COIL | 5.94 | 98321.73 | 0.800655 | 1.98 | 32770.63 | 0.800655 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 48144.13 |
PACU_VAV_MID HEATING COIL | 49421.04 |
PACU_VAV_TOP HEATING COIL | 48173.15 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.67 |
PACU_VAV_MID FAN | 5.12 |
PACU_VAV_TOP FAN | 5.94 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 32.411 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9320 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9163 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.269 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8390 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8573 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5538 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.27971961E-12 | 0.14534712E-14 | -0.84678956E-13 | 0.82684317E-16 |
43 | 6 | 0.26817376E-07 | 0.25687399E-09 | 0.61588016E-08 | -0.12527087E-12 |
44 | 5 | -0.18065003E-03 | 0.22251366E-05 | -0.93037841E-04 | 0.60936178E-08 |
45 | 4 | 0.28101542 | 0.10946024E-02 | 0.95683253E-01 | -0.32007147E-04 |
46 | 3 | -7.0457283 | 0.34231649E-01 | -2.2734647 | 0.27928366E-01 |
47 | 2 | 40.143429 | 0.12270019 | 14.996275 | -0.32523640 |
48 | 1 | -79.987958 | 0.55761501E-01 | -28.900564 | 1.0667320 |
49 | 0 | 46.824342 | 0.11295401E-02 | 16.297084 | |
50 | 7 | -0.28233695E-12 | 0.14433069E-14 | -0.85363548E-13 | 0.83491456E-16 |
51 | 6 | 0.27004714E-07 | 0.25312183E-09 | 0.62001510E-08 | -0.12627076E-12 |
52 | 5 | -0.18161011E-03 | 0.21898175E-05 | -0.93520278E-04 | 0.61339935E-08 |
53 | 4 | 0.28215201 | 0.10760039E-02 | 0.96091377E-01 | -0.32166146E-04 |
54 | 3 | -7.0682688 | 0.33616209E-01 | -2.2801509 | 0.28038740E-01 |
55 | 2 | 40.217804 | 0.12038787 | 15.023777 | -0.32606455 |
56 | 1 | -80.044990 | 0.54668782E-01 | -28.925243 | 1.0679473 |
57 | 0 | 46.824342 | 0.11065724E-02 | 16.296477 | |
58 | 6 | 0.22748378E-07 | 0.33059726E-09 | 0.52605359E-08 | -0.10371465E-12 |
59 | 5 | -0.15952455E-03 | 0.29533519E-05 | -0.82380770E-04 | 0.52144884E-08 |
60 | 4 | 0.25560578 | 0.14926938E-02 | 0.86578981E-01 | -0.28493712E-04 |
61 | 3 | -6.5408460 | 0.47808585E-01 | -2.1237636 | 0.25458881E-01 |
62 | 2 | 38.476406 | 0.17496760 | 14.378110 | -0.30668036 |
63 | 1 | -78.708466 | 0.80951212E-01 | -28.345189 | 1.0394692 |
64 | 0 | 46.824351 | 0.16689207E-02 | 16.311239 | |
65 | 7 | -0.18042418E-08 | -0.42925973E-15 | 0.63337540E-14 | -0.83764910E-16 |
66 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
67 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
68 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
69 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
70 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
71 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
72 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
73 | 7 | -0.17078159E-08 | -0.36552483E-15 | 0.71259391E-14 | -0.98899249E-16 |
74 | 6 | 0.68798867E-05 | 0.47165251E-08 | 0.31862110E-02 | -0.26728608E-04 |
75 | 5 | -0.49558197E-03 | 0.27953368E-05 | -0.22351660 | 0.19543146E-02 |
76 | 4 | 0.11404824E-01 | 0.12725100E-03 | 4.8260817 | -0.45231683E-01 |
77 | 3 | -0.10016651 | 0.10121065E-02 | -38.001848 | 0.39843745 |
78 | 2 | 0.35569192 | 0.16837830E-02 | 116.44586 | -1.4174299 |
79 | 1 | -0.51340120 | 0.51323984E-03 | -143.88489 | 2.0486714 |
80 | 0 | 0.25031121 | 0.12359947E-04 | 60.838472 | |
81 | 7 | -0.18042418E-08 | -0.42925997E-15 | 0.63337541E-14 | -0.83764912E-16 |
82 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
83 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
84 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
85 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
86 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
87 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
88 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
89 | 7 | -0.17076967E-08 | -0.36446083E-15 | 0.71390403E-14 | -0.94439575E-16 |
90 | 6 | 0.68803475E-05 | 0.47168467E-08 | 0.31862096E-02 | -0.26728597E-04 |
91 | 5 | -0.49561596E-03 | 0.27955299E-05 | -0.22351653 | 0.19543140E-02 |
92 | 4 | 0.11405612E-01 | 0.12725979E-03 | 4.8260805 | -0.45231671E-01 |
93 | 3 | -0.10017344 | 0.10121766E-02 | -38.001841 | 0.39843738 |
94 | 2 | 0.35571654 | 0.16838995E-02 | 116.44585 | -1.4174297 |
95 | 1 | -0.51343675 | 0.51327568E-03 | -143.88488 | 2.0486713 |
96 | 0 | 0.25032854 | 0.12360692E-04 | 60.838472 | |
97 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
98 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
99 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
100 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
101 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
102 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
103 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
104 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
105 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1260E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1321E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2640E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2693E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.1348E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1771E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8297E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8525E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1520 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.0653E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1746 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1052 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1040 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5962E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4494E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6685E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1263E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1341E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2643E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2715E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.1375E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1896E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8295E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8523E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.5382E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4289E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.4066E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2641E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.1009E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5870E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1768E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4209E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5195E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.5453E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.3592E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.3780E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6739E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6806E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4698E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4776E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.2544E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3107E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5530E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.5992E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0648E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0998E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8295E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.8523E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1312E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4331E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2036E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8632E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0525E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2877E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4494E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6685E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.2539E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3115E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5517E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.5970E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0624E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0909E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8297E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.8525E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8570E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5788E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2558E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1714E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8660E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9931E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1769E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4210E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4771E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5520E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0189E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.1028E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9452E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9736E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4700E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.4778E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1544 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1093 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1753 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1265 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1110 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.7382E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.0018E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.3204E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.2395E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.2613E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.1231E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.1054E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.8863E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.4706E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.0531E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3544E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.6545E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.1146E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6714E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4501E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.5182E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8259E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.0018E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3204E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.6248E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4521E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.0582E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0656E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.6966E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9036E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.0532E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3545E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1544 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1093 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1753 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1265 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1110 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.7376E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.0015E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.3201E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.2396E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.2610E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.1232E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.1052E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.8861E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.4702E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.0527E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3542E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.6547E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.1145E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6716E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4500E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.5181E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8257E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.0015E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3201E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.6250E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4519E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.0583E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0655E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.6964E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9033E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.0528E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3542E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 38954.99921 | 38954.99921 | 3.21036 | 3.21036 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 10952.97862 | 10952.97862 | 0.52896 | 0.52896 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 28533.70342 | 28533.70342 | 2.34899 | 2.34899 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 20079.33658 | 20079.33658 | 0.97518 | 0.97518 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 30426.30599 | 30426.30599 | 2.52769 | 2.52769 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 32.60000 | 6.30558E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 34752.85925 | 34752.85925 | 1.69222 | 1.69222 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9629.01050 | 9629.01050 | 0.79989 | 0.79989 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 32.92000 | 6.30608E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 16417.80603 | 16417.80603 | 0.80105 | 0.80105 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11073.54305 | 11073.54305 | 0.91988 | 0.91988 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.41333 | 6.29608E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 10739.56497 | 10739.56497 | 0.52403 | 0.52403 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 15065.99720 | 15065.99720 | 1.25155 | 1.25155 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40000 | 6.30683E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 16549.29753 | 16549.29753 | 0.80748 | 0.80748 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12709.98049 | 12709.98049 | 1.05582 | 1.05582 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 10835.80522 | 10835.80522 | 0.52873 | 0.52873 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7355.90089 | 7355.90089 | 0.61108 | 0.61108 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.24000 | 6.30658E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 12374.95363 | 12374.95363 | 0.60353 | 0.60353 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9010.97547 | 9010.97547 | 0.74856 | 0.74856 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.32000 | 6.29745E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 8168.25506 | 8168.25506 | 0.39840 | 0.39840 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 11819.75255 | 11819.75255 | 0.98190 | 0.98190 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.40000 | 6.30683E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 12491.76390 | 12491.76390 | 0.60924 | 0.60924 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9932.80473 | 9932.80473 | 0.82514 | 0.82514 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 28.36000 | 6.29904E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 8245.85237 | 8245.85237 | 0.40220 | 0.40220 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8313.40326 | 8313.40326 | 0.69061 | 0.69061 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.24000 | 6.30658E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 12699.02539 | 12699.02539 | 0.61933 | 0.61933 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10866.88858 | 10866.88858 | 0.90272 | 0.90272 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.50667 | 6.29470E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 8354.83220 | 8354.83220 | 0.40749 | 0.40749 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 13634.56266 | 13634.56266 | 1.13264 | 1.13264 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.30663E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 12805.16962 | 12805.16962 | 0.62452 | 0.62452 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11644.71155 | 11644.71155 | 0.96734 | 0.96734 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 8435.88380 | 8435.88380 | 0.41146 | 0.41146 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 79027.32 | 5.67329 | 5.67329 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 50897.21 | 2.54234 | 2.54234 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 72338.03 | 5.11829 | 5.11829 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 50882.38 | 3.03797 | 3.03797 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 81786.75 | 5.93962 | 5.93962 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 51076.36 | 4.35350 | 4.35350 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.21036 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23345 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25100 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80580 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62253 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.63205E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23537.43938 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.34899 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31905 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33500 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78691 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85081 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19415E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 28485.03845 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.52769 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29650 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32300 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81644 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79066 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.28500E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 49429.73720 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80105 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19723 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21500 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17223 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52595 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.93175E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23398.72841 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91988 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10873 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18398 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.50400E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15306.81554 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.25155 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12624 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25031 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33663 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.01813E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23586.44240 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05582 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.47271E-002 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21116 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.02208E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15444.20457 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61108 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25855 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27800 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16988 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68946 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47362E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17629.26346 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74856 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13362 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14971 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35632 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.85140E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11637.42516 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.98190 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16090 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19638 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42908 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.36786E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17796.03623 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82514 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12121 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16503 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32323 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.14330E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11748.21389 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69061 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22877 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16575 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61006 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.66542E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18090.61056 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90272 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11080 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18054 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.43863E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11902.93287 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.13264 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13949 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22653 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37197 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.73139E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18242.15091 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96734 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10339 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19347 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.68500E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12018.64809 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.18852 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.48680 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.37703 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.54234 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.67329 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.67329 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.44813 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.02115 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.55320 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.04230 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 3.03797 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.11829 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.11829 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.59355 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.27800 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.63412 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.55600 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 4.35350 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.93962 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.93962 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.73296 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.67329 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.11829 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.93962 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.67329 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.67329 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 93913.08189 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.89091 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31301.23019 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 48144.13160 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.67329 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.11829 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.11829 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 84903.68721 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80089 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.70593 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28298.39895 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80089 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 49421.04466 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.11829 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.93962 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.93962 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 98321.72521 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.97967 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32770.63101 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 48173.15166 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.93962 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 92297.07 | 314930.68 | 11.07 | 2.80 | 3.17 | 3.34 | 3.50 | 9.54 | 10.82 | 11.40 | 11.93 | 5.7388 | 4.5377 | 3.0414 | 1.2806 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 83451.01 | 284746.66 | 11.08 | 2.80 | 3.17 | 3.34 | 3.50 | 9.54 | 10.82 | 11.41 | 11.94 | 5.1774 | 4.0947 | 2.7442 | 1.1546 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 96629.85 | 329714.74 | 11.07 | 2.80 | 3.17 | 3.34 | 3.50 | 9.54 | 10.82 | 11.40 | 11.93 | 6.0082 | 4.7507 | 3.1842 | 1.3407 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.246 | 0.232 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.246 | 0.232 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.5293519707E-002 | 7.8209677500E-002 | Pass | Pass | 7.7747336841E-002 | 0.2617337027 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1350146734 | 9.4726782477E-002 | Pass | Pass | 0.3814392948 | 0.4762173524 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.0841263211E-002 | 2.5908893529E-002 | Pass | Pass | 0.1192601574 | 0.3106598995 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.8322186359E-002 | 2.5069919802E-002 | Pass | Pass | 9.8498160436E-002 | 0.3005962347 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.3332917478E-002 | 3.9561278099E-002 | Pass | Pass | 0.1201917864 | 0.3146926039 | Pass | Fail |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.7668513838E-002 | 2.8490230524E-002 | Pass | Pass | 0.3752700366 | 0.4900095940 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2499417910 | 0.2977895915 | Pass | Pass | 5.4357858102 | 20.3974296508 | Fail | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1974937715 | 0.2672323973 | Pass | Pass | 6.3078501835 | 27.6871107140 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2114899033 | 0.2096121210 | Pass | Pass | 1.2804547166 | 6.7758913278 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2402069506 | 0.2811087403 | Pass | Pass | 5.5031704426 | 24.1465466257 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.1204778813E-002 | 0.1197846570 | Pass | Pass | 9.1162771898 | 77.6878003610 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.5480587740E-002 | 6.5049309903E-002 | Pass | Pass | 0.3479675077 | 1.8742830598 | Fail | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1074732541 | 9.7262109220E-002 | Pass | Pass | 7.5783691219E-002 | 0.2492028010 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.1580543178E-002 | 6.6611230365E-002 | Pass | Pass | 0.8344708708 | 4.6083013536 | Fail | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.3302783376E-002 | 0.1170537164 | Pass | Pass | 25.3551686717 | 249.0741407154 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.2305820467E-002 | 0.1095196312 | Pass | Pass | 97.3330732709 | 1152.4425779594 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1260606218 | 0.1248605846 | Pass | Pass | 0.3581781449 | 2.3867345736 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.9029147202E-002 | 0.1101210552 | Pass | Pass | 91.0711609925 | 1079.7752565501 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3665.24 | 209.21 | 0.00 | 2117.00 | 598.71 | 6590.17 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3622_SHGC_EAST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3622_SHGC_WEST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3622_SHGC_EAST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3622_SHGC_WEST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.058 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 177.99 | 2.058 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.058 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.57 | 0.0000 | Y | 9.31 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.40 | 0.0000 | Y | 5.86 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.28 | 0.0000 | Y | 9.22 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.44 | 0.0000 | Y | 5.87 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.52 | 0.0000 | Y | 9.30 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.37 | 0.0000 | Y | 5.86 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.25 | 0.0000 | Y | 9.21 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.41 | 0.0000 | Y | 5.86 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.57 | 0.0000 | Y | 9.31 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.40 | 0.0000 | Y | 5.86 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.28 | 0.0000 | Y | 9.22 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 31.44 | 0.0000 | Y | 5.87 |
Interior Lighting Total | 7.5763 | 4982.19 | 37746.71 | 281.21 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 42.11 | 42.11 | 3.36 | |
EXTERIOR_LIGHTS_B | 5132.60 | AstronomicalClock | - | 83.57 | 71.13 | 68.53 | |
Exterior Lighting Total | 5557.43 | 71.89 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 93913.08 | 75192.00 | 18721.08 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 84903.69 | 67998.14 | 16905.55 | 0.80 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 98321.73 | 78721.81 | 19599.92 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 92297.1 | 2.80 | 9.54 | N/A | N/A | 11.07 | |
PACU_VAV_MID COOLING COIL | 83451.0 | 2.80 | 9.54 | N/A | N/A | 11.08 | |
PACU_VAV_TOP COOLING COIL | 96629.9 | 2.80 | 9.54 | N/A | N/A | 11.07 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 23537.44 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 28485.04 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 49429.74 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 23398.73 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15306.82 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 23586.44 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15444.20 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17629.26 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11637.43 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17796.04 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11748.21 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18090.61 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11902.93 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18242.15 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12018.65 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 48144.13 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 49421.04 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 48173.15 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.67 | 13039.84 | 2298.46 | 1.00 | 1.13 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.12 | 11764.20 | 2298.46 | 1.00 | 1.13 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.94 | 13651.98 | 2298.46 | 1.00 | 1.13 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 92297.07 | 2.80 | 9.54 | 11.07 | 5.7388 | 3.17 | 10.82 | 4.5377 | 3.34 | 11.40 | 3.0414 | 3.50 | 11.93 | 1.2806 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 83451.01 | 2.80 | 9.54 | 11.08 | 5.1774 | 3.17 | 10.82 | 4.0947 | 3.34 | 11.41 | 2.7442 | 3.50 | 11.94 | 1.1546 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 96629.85 | 2.80 | 9.54 | 11.07 | 6.0082 | 3.17 | 10.82 | 4.7507 | 3.34 | 11.40 | 3.1842 | 3.50 | 11.93 | 1.3407 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 38955.00 | 38955.00 | 39.61 | 3.210 | 3.210 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00881 | 21.56 | 0.00629 | 0.425 | 0.00 |
CORE_MID | 28533.70 | 28533.70 | 29.01 | 2.349 | 2.349 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 21.56 | 0.00629 | 0.425 | 0.00 |
CORE_TOP | 30426.31 | 30426.31 | 30.94 | 2.528 | 2.528 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00889 | 32.60 | 0.00631 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9629.01 | 9629.01 | 46.44 | 0.800 | 0.800 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00866 | 32.92 | 0.00631 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11073.54 | 11073.54 | 84.36 | 0.920 | 0.920 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00858 | 26.41 | 0.00630 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15066.00 | 15066.00 | 72.66 | 1.252 | 1.252 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00860 | 33.40 | 0.00631 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12709.98 | 12709.98 | 96.84 | 1.056 | 1.056 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00857 | 30.36 | 0.00630 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7355.90 | 7355.90 | 35.48 | 0.611 | 0.611 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00877 | 33.24 | 0.00631 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9010.98 | 9010.98 | 68.65 | 0.749 | 0.749 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 24.00 | 24.00 | 0.00864 | 27.32 | 0.00630 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11819.75 | 11819.75 | 57.01 | 0.982 | 0.982 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00867 | 33.40 | 0.00631 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9932.80 | 9932.80 | 75.68 | 0.825 | 0.825 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 24.00 | 24.00 | 0.00862 | 28.36 | 0.00630 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8313.40 | 8313.40 | 40.10 | 0.691 | 0.691 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00870 | 33.24 | 0.00631 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10866.89 | 10866.89 | 82.79 | 0.903 | 0.903 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00860 | 25.51 | 0.00629 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 13634.56 | 13634.56 | 65.76 | 1.133 | 1.133 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00862 | 33.27 | 0.00631 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11644.71 | 11644.71 | 88.72 | 0.967 | 0.967 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00859 | 30.36 | 0.00630 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 10952.98 | 10952.98 | 11.14 | 0.529 | 0.529 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 0.425 | 0.00 |
CORE_MID | 20079.34 | 20079.34 | 20.42 | 0.975 | 0.975 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 0.425 | 0.00 |
CORE_TOP | 34752.86 | 34752.86 | 35.33 | 1.692 | 1.692 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 16417.81 | 16417.81 | 79.18 | 0.801 | 0.801 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10739.56 | 10739.56 | 81.82 | 0.524 | 0.524 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 16549.30 | 16549.30 | 79.82 | 0.807 | 0.807 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10835.81 | 10835.81 | 82.56 | 0.529 | 0.529 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 12374.95 | 12374.95 | 59.68 | 0.604 | 0.604 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8168.26 | 8168.26 | 62.23 | 0.398 | 0.398 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12491.76 | 12491.76 | 60.25 | 0.609 | 0.609 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8245.85 | 8245.85 | 62.82 | 0.402 | 0.402 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 12699.03 | 12699.03 | 61.25 | 0.619 | 0.619 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8354.83 | 8354.83 | 63.65 | 0.407 | 0.407 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12805.17 | 12805.17 | 61.76 | 0.625 | 0.625 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 8435.88 | 8435.88 | 64.27 | 0.411 | 0.411 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -27.60 | 0.00034 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.67 | 5.67 | 2.54 | 2.54 | 5.6733 | 2.5423 | 5.6733 | 0.4481 | 0.3000 |
PACU_VAV_MID | 5.12 | 5.12 | 3.04 | 3.04 | 5.1183 | 3.0380 | 5.1183 | 0.5936 | 0.3000 |
PACU_VAV_TOP | 5.94 | 5.94 | 4.35 | 4.35 | 5.9396 | 4.3535 | 5.9396 | 0.7330 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 23537.439 | 23537.439 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23537.44 | 15451.04 | 0.528963 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 10952.98 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 28485.038 | 28485.038 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28485.04 | 28485.04 | 0.975179 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 20079.34 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 49429.737 | 49429.737 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 49429.74 | 49429.74 | 1.692217 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 34752.86 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 23398.728 | 23398.728 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23398.73 | 23398.73 | 0.801051 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00776855 | 43.9426 | 16417.81 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 15306.816 | 15306.816 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15306.82 | 15306.82 | 0.524026 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00776418 | 43.9183 | 10739.56 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 23586.442 | 23586.442 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23586.44 | 23586.44 | 0.807477 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00777033 | 43.9526 | 16549.30 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 15444.205 | 15444.205 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15444.20 | 15444.20 | 0.528729 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00776620 | 43.9296 | 10835.81 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 17629.263 | 17629.263 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17629.26 | 17629.26 | 0.603534 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00783474 | 44.3106 | 12374.95 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 11637.425 | 11637.425 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11637.43 | 11637.43 | 0.398405 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00783353 | 44.3039 | 8168.26 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 17796.036 | 17796.036 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17796.04 | 17796.04 | 0.609244 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00783636 | 44.3196 | 12491.76 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11748.214 | 11748.214 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11748.21 | 11748.21 | 0.402198 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00783514 | 44.3129 | 8245.85 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 18090.611 | 18090.611 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18090.61 | 18090.61 | 0.619328 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00775116 | 43.8449 | 12699.03 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 11902.933 | 11902.933 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11902.93 | 11902.93 | 0.407494 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00774821 | 43.8286 | 8354.83 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 18242.151 | 18242.151 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18242.15 | 18242.15 | 0.624516 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00775322 | 43.8565 | 12805.17 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 12018.648 | 12018.648 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12018.65 | 12018.65 | 0.411456 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00775060 | 43.8419 | 8435.88 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 93913.082 | 75192.003 | 5.673289 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 91796.78 | 91796.78 | 5.673289 | 25.98 | 15.48 | 0.00825050 | 10.66 | 9.78 | 0.00825050 | 33.40 | 0.00630683 | 16.37 | 21.0666 | 24.00 | 0.00877022 | 41.2748 | 68191.25 | 0.00 | 96836.99 | 71349.66 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 48144.132 | 48144.132 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 48144.13 | 48144.13 | 1.701987 | -13.93 | -13.93 | 0.00252733 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 70.2220 | 18.15 | 0.00770196 | 52.0165 | 18939.81 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 84903.687 | 67998.139 | 5.118294 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 82990.41 | 82990.41 | 5.118294 | 26.20 | 15.52 | 0.00820372 | 10.66 | 9.74 | 0.00820372 | 33.40 | 0.00630683 | 16.37 | 23.3509 | 24.00 | 0.00878424 | 41.3395 | 61397.06 | 0.00 | 87547.10 | 64521.19 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 49421.045 | 49421.045 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 49421.04 | 49421.04 | 1.535488 | -17.61 | -17.61 | 0.00194194 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 77.8365 | 17.60 | 0.00736247 | 51.4819 | 21326.99 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 98321.725 | 78721.806 | 5.939615 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 96106.08 | 96106.08 | 5.939615 | 25.90 | 15.45 | 0.00824582 | 10.66 | 9.78 | 0.00824582 | 33.40 | 0.00630683 | 16.37 | 20.1220 | 24.00 | 0.00873862 | 41.1277 | 70994.25 | 0.00 | 101382.90 | 74699.09 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 48173.152 | 48173.152 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 48173.15 | 48173.15 | 1.781885 | -12.75 | -12.75 | 0.00270308 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 67.0734 | 15.66 | 0.00764496 | 60.4557 | 20303.67 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 23537.439 | 23537.439 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23537.44 | 15451.04 | 1.0000 | 0.55707201 | 0.528963 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23537.44 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 10952.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 28485.038 | 28485.038 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 28485.04 | 28485.04 | 1.0000 | 1.02700024 | 0.975179 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28485.04 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 20079.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 49429.737 | 49429.737 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 49429.74 | 49429.74 | 1.0000 | 1.78214090 | 1.692217 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49429.74 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 34752.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 23398.728 | 23398.728 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23398.73 | 23398.73 | 1.0000 | 0.84361830 | 0.801051 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23398.73 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00776855 | 21.00 | 0.00776855 | 43.9426 | 16417.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 15306.816 | 15306.816 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15306.82 | 15306.82 | 1.0000 | 0.55187229 | 0.524026 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15306.82 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00776418 | 21.00 | 0.00776418 | 43.9183 | 10739.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 23586.442 | 23586.442 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23586.44 | 23586.44 | 1.0000 | 0.85038615 | 0.807477 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23586.44 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00777033 | 21.00 | 0.00777033 | 43.9526 | 16549.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 15444.205 | 15444.205 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15444.20 | 15444.20 | 1.0000 | 0.55682571 | 0.528729 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15444.20 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00776620 | 21.00 | 0.00776620 | 43.9296 | 10835.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 17629.263 | 17629.263 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17629.26 | 17629.26 | 1.0000 | 0.63560588 | 0.603534 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17629.26 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00783474 | 21.00 | 0.00783474 | 44.3106 | 12374.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 11637.425 | 11637.425 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11637.43 | 11637.43 | 1.0000 | 0.41957600 | 0.398405 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11637.43 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00783353 | 21.00 | 0.00783353 | 44.3039 | 8168.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 17796.036 | 17796.036 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17796.04 | 17796.04 | 1.0000 | 0.64161871 | 0.609244 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17796.04 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00783636 | 21.00 | 0.00783636 | 44.3196 | 12491.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 11748.214 | 11748.214 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11748.21 | 11748.21 | 1.0000 | 0.42357038 | 0.402198 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11748.21 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00783514 | 21.00 | 0.00783514 | 44.3129 | 8245.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 18090.611 | 18090.611 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18090.61 | 18090.61 | 1.0000 | 0.65223930 | 0.619328 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18090.61 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00775116 | 21.00 | 0.00775116 | 43.8449 | 12699.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 11902.933 | 11902.933 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11902.93 | 11902.93 | 1.0000 | 0.42914862 | 0.407494 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11902.93 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00774821 | 21.00 | 0.00774821 | 43.8286 | 8354.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 18242.151 | 18242.151 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18242.15 | 18242.15 | 1.0000 | 0.65770294 | 0.624516 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18242.15 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00775322 | 21.00 | 0.00775322 | 43.8565 | 12805.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 12018.648 | 12018.648 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12018.65 | 12018.65 | 1.0000 | 0.43332062 | 0.411456 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12018.65 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00775060 | 21.00 | 0.00775060 | 43.8419 | 8435.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 93913.082 | 75192.003 | 5.673289 | -999.0 | -999.000 | -999.0000 | 1.01150 | 1.00000 | 1020.1773 | 1004.8586 | 1.0531 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.673289 | 5.97476719 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 91796.78 | 91796.78 | 0.9775 | 5.97476719 | 5.673289 | 25.98 | 15.48 | 0.00825050 | 47140.5 | 10.66 | 9.78 | 0.00825050 | 31509.8 | -999.0 | -999.00 | -999.00 | -999.00 | 13039.837 | 78756.95 | 33.40 | 0.00630683 | 16.37 | 1.19517000 | 21.0666 | 24.00 | 0.00877022 | 24.00 | 0.00877022 | 41.2748 | 68191.25 | 0.00 | 96836.99 | 71349.66 | 5.73880905 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.51 | 13.70 | 0.00944336 | 38448.3 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 48144.132 | 48144.132 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.673289 | 5.97476719 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 48144.13 | 48144.13 | 1.0000 | 1.79243016 | 1.701987 | -13.93 | -13.93 | 0.00252733 | -7742.0 | 12.80 | 10.41 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48144.13 | -27.60 | 0.00034190 | -27.60 | 1.19517000 | 70.2220 | 18.31 | 0.00768098 | 18.15 | 0.00770196 | 52.0165 | 18939.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 84903.687 | 67998.139 | 5.118294 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0903 | 1004.8586 | 1.0531 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.118294 | 5.39027984 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 82990.41 | 82990.41 | 0.9775 | 5.39027984 | 5.118294 | 26.20 | 15.52 | 0.00820372 | 47245.3 | 10.66 | 9.74 | 0.00820372 | 31391.7 | -999.0 | -999.00 | -999.00 | -999.00 | 11764.203 | 71226.21 | 33.40 | 0.00630683 | 16.37 | 1.19517000 | 23.3509 | 24.00 | 0.00878424 | 24.00 | 0.00878424 | 41.3395 | 61397.06 | 0.00 | 87547.10 | 64521.19 | 5.17740453 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.48 | 13.69 | 0.00944094 | 38412.9 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 49421.045 | 49421.045 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.118294 | 5.39027984 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 49421.04 | 49421.04 | 1.0000 | 1.61708395 | 1.535488 | -17.61 | -17.61 | 0.00194194 | -12906.2 | 12.80 | 10.41 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49421.04 | -27.60 | 0.00034190 | -27.60 | 1.19517000 | 77.8365 | 17.46 | 0.00756116 | 17.60 | 0.00736247 | 51.4819 | 21326.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 98321.725 | 78721.806 | 5.939615 | -999.0 | -999.000 | -999.0000 | 1.01643 | 1.00000 | 1020.1686 | 1004.8586 | 1.0531 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.939615 | 6.25524587 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 96106.08 | 96106.08 | 0.9775 | 6.25524587 | 5.939615 | 25.90 | 15.45 | 0.00824582 | 47048.9 | 10.66 | 9.78 | 0.00824582 | 31498.0 | -999.0 | -999.00 | -999.00 | -999.00 | 13651.978 | 82454.10 | 33.40 | 0.00630683 | 16.37 | 1.19517000 | 20.1220 | 24.00 | 0.00873862 | 24.00 | 0.00873862 | 41.1277 | 70994.25 | 0.00 | 101382.90 | 74699.09 | 6.00821094 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.51 | 13.70 | 0.00944336 | 38448.3 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 48173.152 | 48173.152 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.939615 | 6.25524587 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 48173.15 | 48173.15 | 1.0000 | 1.87657376 | 1.781885 | -12.75 | -12.75 | 0.00270308 | -6112.2 | 12.80 | 10.41 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48173.15 | -27.60 | 0.00034190 | -27.60 | 1.19517000 | 67.0734 | 17.51 | 0.00751294 | 15.66 | 0.00764496 | 60.4557 | 20303.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.67 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.12 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.94 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1276.83 | 3329.17 | 211.00 |
CORE_MID | 1644.00 | 4132.67 | 922.67 |
CORE_TOP | 2383.50 | 4401.67 | 1748.00 |
PERIMETER_TOP_ZN_3 | 3339.50 | 4561.67 | 2641.67 |
PERIMETER_TOP_ZN_2 | 3483.00 | 4243.67 | 2411.67 |
PERIMETER_TOP_ZN_1 | 3114.33 | 4026.67 | 1994.33 |
PERIMETER_TOP_ZN_4 | 3430.00 | 4502.67 | 2487.00 |
PERIMETER_BOT_ZN_3 | 2949.67 | 4688.83 | 2449.00 |
PERIMETER_BOT_ZN_2 | 3175.33 | 4145.83 | 2058.17 |
PERIMETER_BOT_ZN_1 | 2808.17 | 4211.00 | 1814.17 |
PERIMETER_BOT_ZN_4 | 3064.00 | 4318.67 | 2114.83 |
PERIMETER_MID_ZN_3 | 2938.33 | 4367.50 | 2181.17 |
PERIMETER_MID_ZN_2 | 2690.83 | 3571.17 | 1793.83 |
PERIMETER_MID_ZN_1 | 2771.67 | 3748.83 | 1528.00 |
PERIMETER_MID_ZN_4 | 3050.50 | 4262.33 | 2029.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4729.00 | 5009.33 | 2938.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.50 | 0.00 | 0.00 |
CORE_MID | 0.67 | 0.00 | 0.67 | 0.00 |
CORE_TOP | 7.50 | 0.00 | 4.83 | 0.00 |
PERIMETER_TOP_ZN_3 | 192.50 | 6.50 | 92.17 | 4.33 |
PERIMETER_TOP_ZN_2 | 118.00 | 22.67 | 25.17 | 21.33 |
PERIMETER_TOP_ZN_1 | 94.17 | 23.50 | 18.67 | 20.67 |
PERIMETER_TOP_ZN_4 | 116.67 | 25.50 | 27.33 | 12.17 |
PERIMETER_BOT_ZN_3 | 95.83 | 0.00 | 68.33 | 0.00 |
PERIMETER_BOT_ZN_2 | 31.50 | 16.83 | 6.67 | 16.00 |
PERIMETER_BOT_ZN_1 | 495.50 | 35.00 | 479.17 | 33.00 |
PERIMETER_BOT_ZN_4 | 31.50 | 16.17 | 7.50 | 6.83 |
PERIMETER_MID_ZN_3 | 78.00 | 2.83 | 39.00 | 1.83 |
PERIMETER_MID_ZN_2 | 44.83 | 22.50 | 7.33 | 21.83 |
PERIMETER_MID_ZN_1 | 31.33 | 24.17 | 5.67 | 22.00 |
PERIMETER_MID_ZN_4 | 45.83 | 23.83 | 9.00 | 11.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 689.17 | 116.33 | 543.33 | 92.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.938 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.663 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.650 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.735 | 0.114 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 1.350 | 0.120 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 1.286 | 0.114 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 1.349 | 0.120 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.637 | 0.060 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 1.116 | 0.064 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.991 | 1.358 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 1.050 | 0.064 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.720 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 1.235 | 0.106 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 1.254 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 1.278 | 0.100 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.51 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 108.48 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 15057098.77 | 0.00 | 15057098.77 | 0.00 | 15057098.77 | 13393058.27 | 5778.67 | 52.16 | 2929.17 | 212.07 |
CORE_MID | 10655912.74 | 0.00 | 10655912.74 | 0.00 | 10655912.74 | 13393058.27 | 6553.81 | 40.54 | 2165.65 | 229.26 |
CORE_TOP | 10430120.03 | 0.00 | 10430120.03 | 0.00 | 10430120.03 | 13393058.27 | 6566.75 | 29.83 | 2163.42 | 105.15 |
PERIMETER_TOP_ZN_3 | 2482636.44 | 0.00 | 2482636.44 | 759318.16 | 3241954.60 | 2823374.22 | 5741.24 | 56.07 | 2962.69 | 105.13 |
PERIMETER_TOP_ZN_2 | 2882988.72 | 0.00 | 2882988.72 | 506209.06 | 3389197.79 | 1787429.43 | 4129.09 | 2.02 | 4628.89 | 105.13 |
PERIMETER_TOP_ZN_1 | 4329628.13 | 0.00 | 4329628.13 | 759318.16 | 5088946.30 | 2823374.22 | 4143.10 | 0.85 | 4616.05 | 105.13 |
PERIMETER_TOP_ZN_4 | 2897435.34 | 0.00 | 2897435.34 | 506209.06 | 3403644.40 | 1787312.18 | 4133.65 | 6.30 | 4620.05 | 105.13 |
PERIMETER_BOT_ZN_3 | 2178242.17 | 0.00 | 2178242.17 | 403724.27 | 2581966.44 | 2823374.22 | 6141.82 | 47.38 | 2570.81 | 212.07 |
PERIMETER_BOT_ZN_2 | 2400359.49 | 0.00 | 2400359.49 | 269147.90 | 2669507.39 | 1787429.43 | 4103.88 | 10.98 | 4645.13 | 212.07 |
PERIMETER_BOT_ZN_1 | 3371982.73 | 0.00 | 3371982.73 | 4769666.18 | 8141648.91 | 2823374.22 | 4319.81 | 59.33 | 4380.86 | 212.07 |
PERIMETER_BOT_ZN_4 | 2272098.71 | 0.00 | 2272098.71 | 269147.90 | 2541246.61 | 1787312.18 | 4145.49 | 11.69 | 4602.82 | 212.07 |
PERIMETER_MID_ZN_3 | 2437921.20 | 0.00 | 2437921.20 | 632073.14 | 3069994.34 | 2823374.22 | 5952.08 | 61.73 | 2746.18 | 229.22 |
PERIMETER_MID_ZN_2 | 2887416.51 | 0.00 | 2887416.51 | 421379.56 | 3308796.07 | 1787429.43 | 4068.99 | 4.48 | 4686.54 | 1138.24 |
PERIMETER_MID_ZN_1 | 4225285.32 | 0.00 | 4225285.32 | 632073.14 | 4857358.47 | 2823374.22 | 4109.13 | 2.69 | 4648.19 | 229.24 |
PERIMETER_MID_ZN_4 | 2751096.51 | 0.00 | 2751096.51 | 421379.56 | 3172476.07 | 1787312.18 | 4064.87 | 12.18 | 4682.95 | 229.24 |
Total Facility | 71260222.81 | 0.00 | 71260222.81 | 10349646.11 | 81609868.92 | 67843644.98 | 6756.70 | 302.74 | 4807.66 | 1277.37 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6901 | 0.0000 | 0.6901 | 0.0000 | 0.6901 | 0.4247 | 3051.33 | 51.94 | 2839.73 |
CORE_MID | 0.4886 | 0.0000 | 0.4886 | 0.0000 | 0.4886 | 0.4247 | 3796.10 | 40.54 | 2106.36 |
CORE_TOP | 0.4797 | 0.0000 | 0.4797 | 0.0000 | 0.4797 | 0.4247 | 3804.10 | 29.83 | 2109.07 |
PERIMETER_TOP_ZN_3 | 0.1144 | 0.0000 | 0.1144 | 0.0178 | 0.1322 | 0.0895 | 2978.59 | 56.07 | 2908.35 |
PERIMETER_TOP_ZN_2 | 0.1330 | 0.0000 | 0.1330 | 0.0119 | 0.1449 | 0.0567 | 1366.44 | 2.02 | 4574.54 |
PERIMETER_TOP_ZN_1 | 0.2000 | 0.0000 | 0.2000 | 0.0178 | 0.2178 | 0.0895 | 1380.45 | 0.85 | 4561.70 |
PERIMETER_TOP_ZN_4 | 0.1330 | 0.0000 | 0.1330 | 0.0119 | 0.1448 | 0.0567 | 1370.99 | 6.30 | 4565.71 |
PERIMETER_BOT_ZN_3 | 0.0992 | 0.0000 | 0.0992 | 0.0095 | 0.1086 | 0.0895 | 3414.48 | 47.10 | 2481.42 |
PERIMETER_BOT_ZN_2 | 0.1099 | 0.0000 | 0.1099 | 0.0063 | 0.1162 | 0.0567 | 1376.89 | 10.94 | 4555.17 |
PERIMETER_BOT_ZN_1 | 0.1545 | 0.0000 | 0.1545 | 0.2135 | 0.3681 | 0.0895 | 1592.70 | 59.33 | 4290.97 |
PERIMETER_BOT_ZN_4 | 0.1035 | 0.0000 | 0.1035 | 0.0063 | 0.1098 | 0.0567 | 1418.54 | 11.69 | 4512.76 |
PERIMETER_MID_ZN_3 | 0.1120 | 0.0000 | 0.1120 | 0.0148 | 0.1268 | 0.0895 | 3194.37 | 61.73 | 2686.89 |
PERIMETER_MID_ZN_2 | 0.1216 | 0.0000 | 0.1216 | 0.0105 | 0.1321 | 0.0567 | 1311.14 | 4.14 | 3718.71 |
PERIMETER_MID_ZN_1 | 0.1948 | 0.0000 | 0.1948 | 0.0148 | 0.2097 | 0.0895 | 1351.48 | 2.69 | 4588.83 |
PERIMETER_MID_ZN_4 | 0.1260 | 0.0000 | 0.1260 | 0.0099 | 0.1359 | 0.0567 | 1307.42 | 12.18 | 4623.40 |
Total Facility | 3.2601 | 0.0000 | 3.2601 | 0.3449 | 3.6051 | 2.1513 | 3964.67 | 302.42 | 4685.86 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 28037881.93 | 0.00 | 28037881.93 | 22614548.33 | 4103.89 | 3.34 | 4652.77 | 212.07 |
PACU_VAV_MID | 25462410.92 | 0.00 | 25462410.92 | 22614548.33 | 4114.87 | 3.67 | 4641.46 | 228.45 |
PACU_VAV_TOP | 25534672.41 | 0.00 | 25534672.41 | 22614548.33 | 4146.23 | 1.10 | 4612.67 | 104.67 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.2834 | 0.0000 | 1.2834 | 0.7171 | 1376.72 | 3.34 | 4562.94 |
PACU_VAV_MID | 1.1693 | 0.0000 | 1.1693 | 0.7171 | 1357.16 | 3.67 | 4582.17 |
PACU_VAV_TOP | 1.1756 | 0.0000 | 1.1756 | 0.7171 | 1383.58 | 1.10 | 4558.32 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 2979.38 | 0.00 | 0.00 | 0.00 | 2010.02 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.08 | 2752.75 | 0.00 | 0.00 | 0.00 | 2286.05 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2590.85 | 0.00 | 0.00 | 0.00 | 2270.38 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.1158 | 0.0000 | 0.0000 | 0.0000 | 0.8821 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 1.9544 | 0.0000 | 0.0000 | 0.0000 | 0.8818 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.0071 | 0.0000 | 0.0000 | 0.0000 | 0.8797 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 824 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1643.18 | 15539.06 | 12-MAR-17:10 | 262106.25 | 09-JAN-08:10 |
Electricity:Building | 1043.25 | 15341.49 | 01-JAN-09:40 | 75641.67 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 310.83 | 4652.71 | 01-JAN-00:10 | 24063.48 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1043.25 | 15341.49 | 01-JAN-09:40 | 75641.67 | 02-JAN-08:10 |
InteriorLights:Electricity | 281.21 | 1316.11 | 01-JAN-09:40 | 28079.40 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 281.21 | 1316.11 | 01-JAN-09:40 | 28079.40 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 281.21 | 1316.11 | 01-JAN-09:40 | 28079.40 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 281.21 | 1316.11 | 01-JAN-09:40 | 28079.40 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.00 | 541.99 | 01-JAN-09:40 | 2674.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.31 | 40.03 | 01-JAN-09:40 | 1168.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.31 | 40.03 | 01-JAN-09:40 | 1168.55 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 22.76 | 343.10 | 01-JAN-08:50 | 1693.08 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.86 | 25.34 | 01-JAN-08:50 | 739.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.86 | 25.34 | 01-JAN-08:50 | 739.79 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 35.91 | 541.99 | 01-JAN-08:50 | 2674.43 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.22 | 40.03 | 01-JAN-08:50 | 1168.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.22 | 40.03 | 01-JAN-08:50 | 1168.55 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 22.76 | 343.10 | 01-JAN-09:40 | 1693.03 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.87 | 25.34 | 01-JAN-09:40 | 739.74 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.87 | 25.34 | 01-JAN-09:40 | 739.74 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 35.98 | 541.99 | 01-JAN-09:30 | 2674.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.30 | 40.03 | 01-JAN-09:30 | 1168.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.30 | 40.03 | 01-JAN-09:30 | 1168.55 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 22.75 | 343.10 | 01-JAN-08:50 | 1693.08 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.86 | 25.34 | 01-JAN-08:50 | 739.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.86 | 25.34 | 01-JAN-08:50 | 739.79 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 35.90 | 541.99 | 01-JAN-08:50 | 2674.43 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.21 | 40.03 | 01-JAN-08:50 | 1168.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.21 | 40.03 | 01-JAN-08:50 | 1168.55 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 22.76 | 343.10 | 01-JAN-09:30 | 1693.03 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.86 | 25.34 | 01-JAN-09:30 | 739.74 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.86 | 25.34 | 01-JAN-09:30 | 739.74 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 36.00 | 541.99 | 01-JAN-09:40 | 2674.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.31 | 40.03 | 01-JAN-09:40 | 1168.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.31 | 40.03 | 01-JAN-09:40 | 1168.55 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 22.76 | 343.10 | 01-JAN-08:50 | 1693.08 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.86 | 25.34 | 01-JAN-08:50 | 739.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.86 | 25.34 | 01-JAN-08:50 | 739.79 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 35.91 | 541.99 | 01-JAN-08:50 | 2674.43 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.22 | 40.03 | 01-JAN-08:50 | 1168.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.22 | 40.03 | 01-JAN-08:50 | 1168.55 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 22.76 | 343.10 | 01-JAN-09:40 | 1693.03 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.87 | 25.34 | 01-JAN-09:40 | 739.74 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.87 | 25.34 | 01-JAN-09:40 | 739.74 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 247.34 | 4344.73 | 01-JAN-00:10 | 18520.31 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 528.02 | 197.13 | 01-JAN-00:10 | 222101.55 | 09-JAN-07:10 |
ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 928.21 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 12.98 | 197.13 | 01-JAN-00:10 | 928.21 | 02-JAN-08:20 |
ElectricityPurchased:Facility | 1643.18 | 15539.06 | 24-JUN-18:20 | 262106.25 | 09-JAN-08:10 |
ElectricityPurchased:Plant | 1643.18 | 15539.06 | 24-JUN-18:20 | 262106.25 | 09-JAN-08:10 |
Cogeneration:ElectricityPurchased | 1643.18 | 15539.06 | 24-JUN-18:20 | 262106.25 | 09-JAN-08:10 |
General:Cogeneration:ElectricityPurchased | 1643.18 | 15539.06 | 24-JUN-18:20 | 262106.25 | 09-JAN-08:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1643.18 | 15539.06 | 24-JUN-18:20 | 262106.25 | 09-JAN-08:10 |
ElectricityNet:Plant | 1643.18 | 15539.06 | 24-JUN-18:20 | 262106.25 | 09-JAN-08:10 |
Cogeneration:ElectricityNet | 1643.18 | 15539.06 | 24-JUN-18:20 | 262106.25 | 09-JAN-08:10 |
General:Cogeneration:ElectricityNet | 1643.18 | 15539.06 | 24-JUN-18:20 | 262106.25 | 09-JAN-08:10 |
Heating:Electricity | 299.88 | 0.00 | 01-JAN-00:10 | 213664.15 | 09-JAN-07:10 |
General:Heating:Electricity | 299.88 | 0.00 | 01-JAN-00:10 | 213664.15 | 09-JAN-07:10 |
Fans:Electricity | 102.86 | 0.00 | 01-JAN-00:10 | 33242.96 | 25-JUL-15:50 |
General:Fans:Electricity | 102.86 | 0.00 | 01-JAN-00:10 | 33242.96 | 25-JUL-15:50 |
ExteriorLights:Electricity | 71.89 | 0.00 | 01-JAN-08:20 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 71.89 | 0.00 | 01-JAN-08:20 | 5557.43 | 01-JAN-06:10 |
Cooling:Electricity | 112.31 | 0.00 | 01-JAN-00:10 | 81395.66 | 17-JUL-16:00 |
General:Cooling:Electricity | 112.31 | 0.00 | 01-JAN-00:10 | 81395.66 | 17-JUL-16:00 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-07:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-07:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-07:10 |
WIRED_LTG_ELECTRICITY | 7.90 | 0.00 | 01-JAN-00:10 | 789.03 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 641.94 | 12061.80 | 01-JAN-00:10 | 36271.65 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 359.67 | 1156.00 | 05-JAN-06:10 | 155043.69 | 10-JAN-22:00 |
NaturalGas:HVAC | 244.66 | 0.00 | 01-JAN-00:10 | 153887.69 | 10-JAN-22:00 |
Heating:NaturalGas | 244.66 | 0.00 | 01-JAN-00:10 | 153887.69 | 10-JAN-22:00 |
General:Heating:NaturalGas | 244.66 | 0.00 | 01-JAN-00:10 | 153887.69 | 10-JAN-22:00 |
NaturalGas:Plant | 115.01 | 1156.00 | 04-JAN-05:10 | 11463.44 | 17-FEB-12:20 |
WaterSystems:NaturalGas | 115.01 | 1156.00 | 04-JAN-05:10 | 11463.44 | 17-FEB-12:20 |
Water Heater:WaterSystems:NaturalGas | 115.01 | 1156.00 | 04-JAN-05:10 | 11463.44 | 17-FEB-12:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2129.27 | 0.00 | 01-JAN-00:10 | 526495.59 | 09-JAN-07:10 |
EnergyTransfer:Building | 1141.12 | 0.00 | 01-JAN-00:10 | 215392.03 | 09-JAN-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 206.09 | 0.00 | 01-JAN-00:10 | 27434.84 | 05-SEP-08:00 |
Heating:EnergyTransfer | 267.01 | 0.00 | 01-JAN-00:10 | 215046.07 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.11 | 0.00 | 01-JAN-00:10 | 8298.99 | 09-JAN-07:10 |
General:Heating:EnergyTransfer | 267.01 | 0.00 | 01-JAN-00:10 | 215046.07 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.11 | 0.00 | 01-JAN-00:10 | 8298.99 | 09-JAN-07:10 |
Cooling:EnergyTransfer | 874.11 | 0.00 | 01-JAN-00:10 | 186763.79 | 17-JUL-16:00 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 205.98 | 0.00 | 01-JAN-00:10 | 27434.84 | 05-SEP-08:00 |
General:Cooling:EnergyTransfer | 874.11 | 0.00 | 01-JAN-00:10 | 186763.79 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 205.98 | 0.00 | 01-JAN-00:10 | 27434.84 | 05-SEP-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 63.41 | 0.00 | 01-JAN-00:10 | 18522.65 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 38.10 | 0.00 | 01-JAN-00:10 | 18522.65 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 38.10 | 0.00 | 01-JAN-00:10 | 18522.65 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 25.31 | 0.00 | 01-JAN-00:10 | 13244.38 | 17-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 25.31 | 0.00 | 01-JAN-00:10 | 13244.38 | 17-JUL-15:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 29.05 | 0.00 | 01-JAN-00:10 | 11274.24 | 09-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.19 | 0.00 | 01-JAN-00:10 | 11274.24 | 09-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.19 | 0.00 | 01-JAN-00:10 | 11274.24 | 09-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.87 | 0.00 | 01-JAN-00:10 | 6182.28 | 17-JUL-15:40 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.87 | 0.00 | 01-JAN-00:10 | 6182.28 | 17-JUL-15:40 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 27.60 | 0.00 | 01-JAN-00:10 | 6103.95 | 17-JUL-16:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.68 | 0.00 | 01-JAN-00:10 | 5612.06 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.68 | 0.00 | 01-JAN-00:10 | 5612.06 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 16.92 | 0.00 | 01-JAN-00:10 | 6103.95 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 16.92 | 0.00 | 01-JAN-00:10 | 6103.95 | 17-JUL-16:00 |
EnergyTransfer:Zone:CORE_MID | 133.65 | 0.00 | 01-JAN-00:10 | 23863.95 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 2.78 | 0.00 | 01-JAN-00:10 | 23863.95 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 2.78 | 0.00 | 01-JAN-00:10 | 23863.95 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 130.87 | 0.00 | 01-JAN-00:10 | 19637.97 | 05-SEP-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 130.87 | 0.00 | 01-JAN-00:10 | 19637.97 | 05-SEP-07:40 |
EnergyTransfer:Zone:CORE_TOP | 130.57 | 0.00 | 01-JAN-00:10 | 29624.68 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 13.64 | 0.00 | 01-JAN-00:10 | 29624.68 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 13.64 | 0.00 | 01-JAN-00:10 | 29624.68 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 116.94 | 0.00 | 01-JAN-00:10 | 21714.31 | 17-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 116.94 | 0.00 | 01-JAN-00:10 | 21714.31 | 17-JUL-15:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 49.58 | 0.00 | 01-JAN-00:10 | 10527.35 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 26.51 | 0.00 | 01-JAN-00:10 | 10527.35 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 26.51 | 0.00 | 01-JAN-00:10 | 10527.35 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.07 | 0.00 | 01-JAN-00:10 | 7665.78 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.07 | 0.00 | 01-JAN-00:10 | 7665.78 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 43.72 | 0.00 | 01-JAN-00:10 | 10520.18 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 15.33 | 0.00 | 01-JAN-00:10 | 10520.18 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 15.33 | 0.00 | 01-JAN-00:10 | 10520.18 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 28.39 | 0.00 | 01-JAN-00:10 | 10232.97 | 07-AUG-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 28.39 | 0.00 | 01-JAN-00:10 | 10232.97 | 07-AUG-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 67.26 | 0.00 | 01-JAN-00:10 | 14935.45 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 18.88 | 0.00 | 01-JAN-00:10 | 14935.45 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 18.88 | 0.00 | 01-JAN-00:10 | 14935.45 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 48.38 | 0.00 | 01-JAN-00:10 | 14549.24 | 01-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 48.38 | 0.00 | 01-JAN-00:10 | 14549.24 | 01-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 44.29 | 0.00 | 01-JAN-00:10 | 11547.77 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 16.53 | 0.00 | 01-JAN-00:10 | 11547.77 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 16.53 | 0.00 | 01-JAN-00:10 | 11547.77 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 27.76 | 0.00 | 01-JAN-00:10 | 10834.72 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 27.76 | 0.00 | 01-JAN-00:10 | 10834.72 | 17-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 34.64 | 0.00 | 01-JAN-00:10 | 7634.78 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 14.35 | 0.00 | 01-JAN-00:10 | 7634.78 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 14.35 | 0.00 | 01-JAN-00:10 | 7634.78 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.29 | 0.00 | 01-JAN-00:10 | 5893.35 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.29 | 0.00 | 01-JAN-00:10 | 5893.35 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 33.31 | 0.00 | 01-JAN-00:10 | 8366.93 | 17-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 7.83 | 0.00 | 01-JAN-00:10 | 8233.38 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 7.83 | 0.00 | 01-JAN-00:10 | 8233.38 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 25.48 | 0.00 | 01-JAN-00:10 | 8366.93 | 17-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 25.48 | 0.00 | 01-JAN-00:10 | 8366.93 | 17-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 71.94 | 0.00 | 01-JAN-00:10 | 19031.92 | 09-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 38.52 | 0.00 | 01-JAN-00:10 | 19031.92 | 09-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 38.52 | 0.00 | 01-JAN-00:10 | 19031.92 | 09-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 33.42 | 0.00 | 01-JAN-00:10 | 14145.66 | 17-JUL-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 33.42 | 0.00 | 01-JAN-00:10 | 14145.66 | 17-JUL-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 32.30 | 0.00 | 01-JAN-00:10 | 8624.74 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 8.40 | 0.00 | 01-JAN-00:10 | 8624.74 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 8.40 | 0.00 | 01-JAN-00:10 | 8624.74 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 23.91 | 0.00 | 01-JAN-00:10 | 8451.56 | 04-AUG-18:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 23.91 | 0.00 | 01-JAN-00:10 | 8451.56 | 04-AUG-18:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 38.67 | 0.00 | 01-JAN-00:10 | 8825.84 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 13.70 | 0.00 | 01-JAN-00:10 | 8825.84 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 13.70 | 0.00 | 01-JAN-00:10 | 8825.84 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.97 | 0.00 | 01-JAN-00:10 | 6884.20 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.97 | 0.00 | 01-JAN-00:10 | 6884.20 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 37.90 | 0.00 | 01-JAN-00:10 | 10082.73 | 07-AUG-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 8.07 | 0.00 | 01-JAN-00:10 | 9291.43 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 8.07 | 0.00 | 01-JAN-00:10 | 9291.43 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.83 | 0.00 | 01-JAN-00:10 | 10082.73 | 07-AUG-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.83 | 0.00 | 01-JAN-00:10 | 10082.73 | 07-AUG-08:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 59.69 | 0.00 | 01-JAN-00:10 | 13711.78 | 01-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 8.91 | 0.00 | 01-JAN-00:10 | 12541.43 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 8.91 | 0.00 | 01-JAN-00:10 | 12541.43 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 50.79 | 0.00 | 01-JAN-00:10 | 13711.78 | 01-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 50.79 | 0.00 | 01-JAN-00:10 | 13711.78 | 01-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 37.45 | 0.00 | 01-JAN-00:10 | 10105.77 | 17-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 8.48 | 0.00 | 01-JAN-00:10 | 9253.48 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 8.48 | 0.00 | 01-JAN-00:10 | 9253.48 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 28.97 | 0.00 | 01-JAN-00:10 | 10105.77 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 28.97 | 0.00 | 01-JAN-00:10 | 10105.77 | 17-JUL-17:00 |
PlantLoopHeatingDemand:Facility | 55.07 | 0.00 | 01-JAN-00:10 | 6983.85 | 24-FEB-12:20 |
PlantLoopHeatingDemand:Plant | 55.07 | 0.00 | 01-JAN-00:10 | 6983.85 | 24-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 55.07 | 0.00 | 01-JAN-00:10 | 6983.85 | 24-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 55.07 | 0.00 | 01-JAN-00:10 | 6983.85 | 24-FEB-12:20 |
EnergyTransfer:HVAC | 933.07 | 0.00 | 01-JAN-00:10 | 313676.98 | 09-JAN-07:10 |
HeatingCoils:EnergyTransfer | 495.60 | 0.00 | 01-JAN-00:10 | 313676.98 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 437.47 | 0.00 | 01-JAN-00:10 | 292077.38 | 07-SEP-15:00 |
EnergyTransfer:Plant | 55.07 | 0.00 | 01-JAN-00:10 | 6983.85 | 24-FEB-12:20 |
WaterSystems:EnergyTransfer | 55.07 | 0.00 | 01-JAN-00:10 | 6983.85 | 24-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 55.07 | 0.00 | 01-JAN-00:10 | 6983.85 | 24-FEB-12:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.112 | -205.980 | 0.000 | 0.000 | 33.236 | 63.485 | 247.342 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -138.196 |
CORE_MID | 0.000 | 0.000 | 2.779 | -130.867 | 0.000 | 0.000 | 34.722 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -96.720 |
CORE_TOP | 0.000 | 0.000 | 13.639 | -116.935 | 0.000 | 0.000 | 35.600 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -122.389 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 26.509 | -23.073 | 0.000 | 0.000 | 7.704 | 9.310 | 26.688 | 16.567 | 0.000 | 0.111 | 0.001 | 0.000 | -36.561 | 0.000 | -11.183 | -16.072 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 15.335 | -28.389 | 0.000 | 0.000 | 4.816 | 5.862 | 16.895 | 36.496 | 0.000 | 0.072 | 0.001 | 0.000 | -22.979 | 0.000 | -7.567 | -20.540 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 18.884 | -48.375 | 0.000 | 0.000 | 7.499 | 9.223 | 26.688 | 78.595 | 0.000 | 0.105 | 0.001 | 0.000 | -34.477 | 0.000 | -11.716 | -46.426 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 16.527 | -27.763 | 0.000 | 0.000 | 4.898 | 5.869 | 16.895 | 34.921 | 0.000 | 0.074 | 0.001 | 0.000 | -24.132 | 0.000 | -7.583 | -19.706 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 14.352 | -20.288 | 0.000 | 0.000 | 7.679 | 9.295 | 26.688 | 16.856 | 0.000 | 0.065 | 0.001 | 0.000 | -37.684 | 0.000 | -6.240 | -10.723 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 7.831 | -25.476 | 0.000 | 0.000 | 4.767 | 5.856 | 16.895 | 36.580 | 0.000 | 0.039 | 0.001 | 0.000 | -24.056 | 0.000 | -4.289 | -18.147 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 38.522 | -33.416 | 0.000 | 0.000 | 7.746 | 9.214 | 26.688 | 79.431 | 0.000 | 1.869 | 0.001 | 0.000 | -35.857 | 0.000 | -65.410 | -28.787 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 8.396 | -23.905 | 0.000 | 0.000 | 4.834 | 5.863 | 16.895 | 35.081 | 0.000 | 0.039 | 0.000 | 0.000 | -25.220 | 0.000 | -4.293 | -17.691 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 13.699 | -24.969 | 0.000 | 0.000 | 7.602 | 9.310 | 26.688 | 16.242 | 0.000 | 0.094 | 0.003 | 0.000 | -38.367 | 0.000 | -9.820 | -0.479 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 8.073 | -29.827 | 0.000 | 0.000 | 3.534 | 5.862 | 16.895 | 36.254 | 0.000 | 0.061 | 0.000 | 0.000 | -24.049 | 0.000 | -6.626 | -10.177 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 8.909 | -50.785 | 0.000 | 0.000 | 7.383 | 9.223 | 26.688 | 78.209 | 0.000 | 0.088 | 0.002 | 0.000 | -36.224 | 0.000 | -10.301 | -33.191 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 8.480 | -28.965 | 0.000 | 0.000 | 4.835 | 5.869 | 16.895 | 34.715 | 0.000 | 0.061 | 0.000 | 0.000 | -25.299 | 0.000 | -6.649 | -9.942 |
TOPFLOOR_PLENUM | 38.104 | -25.306 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.112 | 4.080 | 0.000 | 0.000 | 0.000 | -16.989 | -0.001 |
MIDFLOOR_PLENUM | 16.186 | -12.866 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.135 | 13.399 | 0.000 | 0.000 | 0.000 | -16.855 | -0.001 |
FIRSTFLOOR_PLENUM | 10.677 | -16.921 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.104 | 19.823 | 0.000 | 0.000 | 0.000 | -13.683 | -0.000 |
Total Facility | 64.967 | -55.093 | 202.047 | -819.011 | 0.000 | 0.000 | 176.855 | 281.212 | 762.041 | 499.947 | 0.000 | 3.028 | 37.313 | 0.000 | -364.907 | 0.000 | -199.203 | -589.186 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 14-AUG-04:02 | 0.00 | 0.00 | 0.00 | -44152.63 | 0.00 | 0.00 | 0.00 | 615.87 | 5138.45 | 0.00 | 0.00 | 0.00 | 38398.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 17-JUL-04:02 | 0.00 | 0.00 | 0.00 | -32400.95 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 28610.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 05-SEP-04:02 | 0.00 | 0.00 | 0.00 | -35073.48 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 31282.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-18:41 | 0.00 | 0.00 | 0.00 | -11824.35 | 0.00 | 0.00 | 0.00 | 40.03 | 501.96 | 3617.15 | 0.00 | 121.88 | 7543.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 06-AUG-09:32 | 0.00 | 0.00 | 0.00 | -14697.29 | 0.00 | 0.00 | 11.63 | 25.34 | 317.77 | 10789.39 | 0.00 | 29.77 | 3523.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 03-SEP-13:02 | 0.00 | 0.00 | 0.00 | -20271.63 | 0.00 | 0.00 | 17.93 | 40.03 | 501.96 | 15758.35 | 0.00 | 337.47 | 3615.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 09-JUL-16:31 | 0.00 | 0.00 | 0.00 | -17801.40 | 0.00 | 0.00 | 12.19 | 25.34 | 317.76 | 12535.58 | 0.00 | 0.00 | 4931.49 | 0.00 | -0.00 | 0.00 | -20.97 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-JUL-18:31 | 0.00 | 0.00 | 0.00 | -8277.88 | 0.00 | 0.00 | 0.00 | 40.03 | 501.96 | 4129.84 | 0.00 | 65.91 | 3540.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 16-JUL-09:51 | 0.00 | 0.00 | 0.00 | -12295.40 | 0.00 | 0.00 | 14.94 | 25.34 | 317.77 | 8818.24 | 0.00 | 0.00 | 3175.57 | 0.00 | -0.00 | 0.00 | -56.45 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-11:42 | 0.00 | 0.00 | 0.00 | -15711.49 | 0.00 | 0.00 | 24.02 | 40.03 | 501.96 | 11212.76 | 0.00 | 94.54 | 3838.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 16-JUL-18:31 | 0.00 | 0.00 | 0.00 | -14362.86 | 0.00 | 0.00 | 0.00 | 25.34 | 317.76 | 9573.55 | 0.00 | 22.01 | 4424.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-18:32 | 0.00 | 0.00 | 0.00 | -10969.02 | 0.00 | 0.00 | 0.00 | 40.03 | 501.96 | 4022.03 | 0.00 | 101.74 | 6303.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-08:31 | 0.00 | 0.00 | 0.00 | -15590.15 | 0.00 | 0.00 | 12.69 | 25.34 | 317.77 | 11980.31 | 0.00 | 0.00 | 3406.06 | 0.00 | -0.00 | 0.00 | -152.01 | 0.00 |
PERIMETER_MID_ZN_1 | 03-SEP-13:22 | 0.00 | 0.00 | 0.00 | -18299.69 | 0.00 | 0.00 | 19.09 | 40.03 | 501.96 | 15224.60 | 0.00 | 254.04 | 2259.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 16-JUL-17:12 | 0.00 | 0.00 | 0.00 | -17097.36 | 0.00 | 0.00 | 0.00 | 25.34 | 317.76 | 12650.78 | 0.00 | 50.86 | 4052.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 17-JUL-15:00 | 0.00 | -13244.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13244.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 17-JUL-15:40 | 0.00 | -6182.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.82 | 6087.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 17-JUL-12:08 | 0.00 | -6546.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.15 | 6493.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-JUL-16:00 | 0.00 | -24524.91 | 0.00 | -162235.52 | 0.00 | 0.00 | 17714.51 | 23688.37 | 43769.98 | 70432.87 | 0.00 | 3340.36 | 27814.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-06:03 | 0.00 | 0.00 | 18689.58 | 0.00 | 0.00 | 0.00 | 475.84 | 615.87 | 5138.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24919.75 |
CORE_MID | 09-JAN-05:01 | 0.00 | 0.00 | 27299.95 | 0.00 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -31090.69 |
CORE_TOP | 31-DEC-23:21 | 0.00 | 0.00 | 32938.03 | 0.00 | 0.00 | 0.00 | 0.00 | 307.97 | 2381.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -35627.15 |
PERIMETER_TOP_ZN_3 | 09-JAN-06:01 | 0.00 | 0.00 | 11558.37 | 0.00 | 0.00 | 0.00 | 122.49 | 129.83 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4159.50 | 0.00 | -257.40 | -8063.07 |
PERIMETER_TOP_ZN_2 | 29-JAN-23:01 | 0.00 | 0.00 | 12969.42 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 317.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2699.47 | 0.00 | -766.22 | -9862.60 |
PERIMETER_TOP_ZN_1 | 31-DEC-23:21 | 0.00 | 0.00 | 17610.68 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3852.32 | 0.00 | -906.24 | -13419.01 |
PERIMETER_TOP_ZN_4 | 31-DEC-23:21 | 0.00 | 0.00 | 14750.57 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 317.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2556.77 | 0.00 | -607.25 | -11945.41 |
PERIMETER_BOT_ZN_3 | 11-JAN-03:42 | 0.00 | 0.00 | 8175.83 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4511.49 | 0.00 | -587.49 | -3811.06 |
PERIMETER_BOT_ZN_2 | 09-JAN-02:52 | 0.00 | 0.00 | 9819.83 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2834.85 | 0.00 | -521.17 | -6928.60 |
PERIMETER_BOT_ZN_1 | 11-JAN-07:10 | 0.00 | 0.00 | 19486.09 | 0.00 | 0.00 | 0.00 | 223.52 | 389.51 | 669.28 | 0.00 | 0.00 | 0.00 | 22757.58 | 0.00 | -4420.65 | 0.00 | -39105.33 | 0.00 |
PERIMETER_BOT_ZN_4 | 09-JAN-02:52 | 0.00 | 0.00 | 10761.86 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2764.67 | 0.00 | -522.93 | -7939.04 |
PERIMETER_MID_ZN_3 | 09-JAN-03:02 | 0.00 | 0.00 | 9692.61 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4253.95 | 0.00 | -1120.35 | -5052.52 |
PERIMETER_MID_ZN_2 | 09-JAN-03:02 | 0.00 | 0.00 | 12362.94 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2831.81 | 0.00 | -758.67 | -9237.25 |
PERIMETER_MID_ZN_1 | 09-JAN-03:02 | 0.00 | 0.00 | 15548.93 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4148.00 | 0.00 | -1136.29 | -10998.84 |
PERIMETER_MID_ZN_4 | 09-JAN-03:02 | 0.00 | 0.00 | 12785.55 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2754.64 | 0.00 | -760.66 | -9735.04 |
TOPFLOOR_PLENUM | 28-JAN-06:12 | 20173.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -461.80 | -19711.99 |
MIDFLOOR_PLENUM | 09-JAN-07:04 | 11563.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -406.93 | -11156.48 |
FIRSTFLOOR_PLENUM | 22-MAY-05:01 | 8235.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -927.04 | -7308.86 |
Total Facility | 09-JAN-06:01 | 30009.08 | 0.00 | 211331.04 | 0.00 | 0.00 | 0.00 | 2602.02 | 3119.77 | 18045.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43213.55 | 0.00 | -11687.26 | -210207.08 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.3770 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.6733 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 6.0423 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.1183 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.5560 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.9396 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.1885 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4868 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 3.0212 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5532 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.2780 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.6341 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2104 | 3.2104 | 0.8058 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3490 | 2.3490 | 0.7869 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5277 | 2.5277 | 0.8164 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8011 | 0.8011 | 0.1722 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9199 | 0.9199 | 0.1840 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2515 | 1.2515 | 0.2503 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0558 | 1.0558 | 0.2112 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6111 | 0.6111 | 0.1699 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7486 | 0.7486 | 0.1497 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9819 | 0.9819 | 0.1964 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8251 | 0.8251 | 0.1650 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6906 | 0.6906 | 0.1657 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9027 | 0.9027 | 0.1805 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1326 | 1.1326 | 0.2265 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9673 | 0.9673 | 0.1935 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.3770 | 5.6733 | 6.3770 | 1.4868 | 0.0000 | 1.0000 |
PACU_VAV_MID | 6.0423 | 5.1183 | 6.0423 | 1.5532 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.5560 | 5.9396 | 6.5560 | 1.6341 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6052 | 1.6052 | 0.8058 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1745 | 1.1745 | 0.7869 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2638 | 1.2638 | 0.8164 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4005 | 0.4005 | 0.1722 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4599 | 0.4599 | 0.1840 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6258 | 0.6258 | 0.2503 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5279 | 0.5279 | 0.2112 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3055 | 0.3055 | 0.1699 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3743 | 0.3743 | 0.1497 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4909 | 0.4909 | 0.1964 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4126 | 0.4126 | 0.1650 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3453 | 0.3453 | 0.1657 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4514 | 0.4514 | 0.1805 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5663 | 0.5663 | 0.2265 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4837 | 0.4837 | 0.1935 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.1885 | 1.4868 | 1.4868 | 1.4868 | 0.0000 | 1.0000 |
PACU_VAV_MID | 3.0212 | 1.5532 | 1.5532 | 1.5532 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.2780 | 1.6341 | 1.6341 | 1.6341 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 543.33 |
Number of hours cooling loads not met | 92.67 |
Number of hours not met | 636.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 299.88 | 213664.15 | 244.66 | 153887.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 112.31 | 81395.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 281.21 | 28079.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 71.89 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 641.30 | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 12.98 | 928.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 102.86 | 33242.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 115.01 | 11463.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 762.04 | 1643.18 |
Natural Gas | 0.00 | 359.67 |
Additional | 0.00 | 0.00 |
Total | 762.04 | 2002.85 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 56.44 |
Space Heating | 60.19 |
Space Cooling | 22.54 |
Fans (All) | 20.65 |
Service Water Heating | 0.00 |
Receptacle Equipment | 152.95 |
Miscellaneous (All) | 329.81 |
Subtotal | 329.81 |
Natural Gas [MJ/m2] | |
Space Heating | 49.11 |
Service Water Heating | 23.08 |
Miscellaneous (All) | 72.19 |
Subtotal | 72.19 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.04 |
Space Heating | 27.19 |
Space Cooling | 5.61 |
Fans (All) | 5.14 |
Service Water Heating | 5.74 |
Receptacle Equipment | 38.05 |
Miscellaneous | 4.24 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2429. | 8760. |
BLDG_EQUIP_SCH | 4487. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8758.17 | 1.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8742.67 | 17.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8746.50 | 13.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8742.00 | 18.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8750.67 | 9.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8743.17 | 16.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8747.33 | 12.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8742.67 | 17.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8712.33 | 47.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8712.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 47.67 | 0.00 | 0.00 | 0.00 |
Average | 8749.94 | 10.06 | 0.00 | 0.00 | 0.00 |
Sum | 157498.83 | 181.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128297.67 | 6.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 6.33 | 0.00 | 0.00 | 0.00 |
Average | 34142.98 | 0.35 | 0.00 | 0.00 | 0.00 |
Sum | 614573.67 | 6.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8725.50 | 34.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8747.17 | 12.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8756.67 | 3.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8754.17 | 5.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8750.17 | 9.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8751.83 | 8.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8754.67 | 5.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8747.33 | 12.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8749.83 | 10.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8747.33 | 12.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8725.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 34.50 | 0.00 | 0.00 | 0.00 |
Average | 8751.56 | 8.44 | 0.00 | 0.00 | 0.00 |
Sum | 157528.17 | 151.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128273.67 | 30.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128288.33 | 15.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128297.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128297.33 | 30.33 | 0.00 | 0.00 | 0.00 |
Average | 34140.41 | 2.93 | 0.00 | 0.00 | 0.00 |
Sum | 614527.33 | 52.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.891097E+10 | 8535.91 | 19-JAN-16:50 | -6.4 | -8.0 | 0.176451E+10 | 2606.57 | 20-JAN-14:09 | 0.50 | -3.2 |
February | 0.933647E+10 | 16037.07 | 28-FEB-08:15 | -3.9 | -4.2 | 0.170184E+10 | 2606.63 | 28-FEB-10:09 | 1.57 | -0.3 |
March | 0.132870E+11 | 17957.00 | 24-MAR-07:04 | -1.7 | -3.1 | 0.210459E+10 | 2606.68 | 28-MAR-09:30 | 6.10 | 1.03 |
April | 0.147376E+11 | 24050.77 | 26-APR-05:03 | 5.37 | 2.97 | 0.190218E+10 | 2608.56 | 19-APR-09:50 | 5.37 | 2.97 |
May | 0.180865E+11 | 41030.50 | 22-MAY-05:01 | -0.6 | -0.6 | 0.207010E+10 | 2606.83 | 02-MAY-13:09 | -0.6 | -0.6 |
June | 0.246371E+11 | 40414.20 | 15-JUN-05:02 | 3.17 | 1.44 | 0.206959E+10 | 2606.67 | 29-JUN-09:20 | 25.17 | 12.64 |
July | 0.264164E+11 | 43203.87 | 17-JUL-04:02 | 16.10 | 11.78 | 0.192483E+10 | 2606.72 | 13-JUL-09:00 | 16.10 | 11.78 |
August | 0.275088E+11 | 44148.82 | 14-AUG-04:02 | 12.20 | 9.91 | 0.216084E+10 | 2606.67 | 24-AUG-09:00 | 20.00 | 12.25 |
September | 0.222756E+11 | 42921.75 | 11-SEP-04:03 | 11.10 | 10.17 | 0.191717E+10 | 2606.73 | 07-SEP-09:00 | 11.10 | 10.17 |
October | 0.177945E+11 | 40637.34 | 20-OCT-05:02 | 2.70 | 0.86 | 0.198735E+10 | 2606.63 | 06-OCT-09:00 | 2.70 | 0.86 |
November | 0.129398E+11 | 17881.51 | 03-NOV-16:00 | 14.30 | 7.69 | 0.193737E+10 | 2608.48 | 06-NOV-10:39 | 3.60 | 0.54 |
December | 0.100493E+11 | 13862.15 | 08-DEC-08:08 | -0.4 | -3.2 | 0.181797E+10 | 2608.29 | 20-DEC-14:30 | 6.65 | 0.79 |
Annual Sum or Average | 0.205980E+12 | 0.233583E+11 | ||||||||
Minimum of Months | 0.891097E+10 | 8535.91 | -6.4 | -8.0 | 0.170184E+10 | 2606.57 | -0.6 | -3.2 | ||
Maximum of Months | 0.275088E+11 | 44148.82 | 16.10 | 11.78 | 0.216084E+10 | 2608.56 | 25.17 | 12.64 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 601659.52 | 314.37 | 14-JAN-17:25 | 8.90 | 3.99 | 0.00 | 0.00 | 01-JAN-00:10 | 8.90 | 3.99 |
February | 88918924.52 | 1876.03 | 26-FEB-14:30 | 16.15 | 6.12 | 0.00 | 0.00 | 01-FEB-00:10 | 16.15 | 6.12 |
March | 0.342619E+09 | 2324.80 | 22-MAR-16:10 | 11.10 | 4.35 | 0.00 | 0.00 | 01-MAR-00:10 | 11.10 | 4.35 |
April | 0.108392E+10 | 5820.60 | 25-APR-15:20 | 17.27 | 7.54 | 0.00 | 0.00 | 01-APR-00:10 | 17.27 | 7.54 |
May | 0.236499E+10 | 9243.05 | 19-MAY-15:20 | 28.13 | 14.77 | 0.00 | 0.00 | 01-MAY-00:10 | 28.13 | 14.77 |
June | 0.508148E+10 | 10648.65 | 23-JUN-13:30 | 31.40 | 15.21 | 0.00 | 0.00 | 01-JUN-00:10 | 31.40 | 15.21 |
July | 0.690940E+10 | 13244.38 | 17-JUL-15:00 | 36.10 | 17.00 | 0.00 | 0.00 | 01-JUL-00:10 | 36.10 | 17.00 |
August | 0.589927E+10 | 11915.01 | 07-AUG-15:30 | 32.50 | 16.07 | 0.00 | 0.00 | 01-AUG-00:10 | 32.50 | 16.07 |
September | 0.274971E+10 | 8836.83 | 01-SEP-15:40 | 28.30 | 14.15 | 0.00 | 0.00 | 01-SEP-00:10 | 28.30 | 14.15 |
October | 0.734306E+09 | 5461.14 | 18-OCT-15:20 | 24.80 | 11.42 | 0.00 | 0.00 | 01-OCT-00:10 | 24.80 | 11.42 |
November | 51690075.75 | 1162.56 | 03-NOV-14:30 | 14.80 | 7.76 | 0.00 | 0.00 | 01-NOV-00:10 | 14.80 | 7.76 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 |
Annual Sum or Average | 0.253069E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.1 | -4.2 | 0.00 | 0.00 | -2.1 | -4.2 | ||
Maximum of Months | 0.690940E+10 | 13244.38 | 36.10 | 17.00 | 0.00 | 0.00 | 36.10 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11846252.11 | 2482.68 | 07-JAN-05:01 | -21.6 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.6 | -22.1 |
February | 20677953.91 | 2893.51 | 01-FEB-05:01 | -25.0 | -25.2 | 0.00 | 0.00 | 01-FEB-00:10 | -25.0 | -25.2 |
March | 73069076.58 | 3156.74 | 04-MAR-05:01 | -19.1 | -19.6 | 0.00 | 0.00 | 01-MAR-00:10 | -19.1 | -19.6 |
April | 0.279290E+09 | 3334.18 | 27-APR-06:01 | -1.7 | -3.3 | 0.00 | 0.00 | 01-APR-00:10 | -1.7 | -3.3 |
May | 0.743494E+09 | 3104.94 | 19-MAY-16:00 | 27.80 | 14.54 | 0.00 | 0.00 | 01-MAY-00:10 | 27.80 | 14.54 |
June | 0.255684E+10 | 4364.13 | 23-JUN-15:30 | 27.50 | 14.33 | 0.00 | 0.00 | 01-JUN-00:10 | 27.50 | 14.33 |
July | 0.379642E+10 | 6182.28 | 17-JUL-15:40 | 36.83 | 17.19 | 0.00 | 0.00 | 01-JUL-00:10 | 36.83 | 17.19 |
August | 0.341094E+10 | 6047.94 | 07-AUG-15:30 | 32.50 | 16.07 | 0.00 | 0.00 | 01-AUG-00:10 | 32.50 | 16.07 |
September | 0.157234E+10 | 5350.70 | 05-SEP-06:15 | 18.90 | 12.98 | 0.00 | 0.00 | 01-SEP-00:10 | 18.90 | 12.98 |
October | 0.327667E+09 | 2279.21 | 27-OCT-06:01 | -0.1 | -2.5 | 0.00 | 0.00 | 01-OCT-00:10 | -0.1 | -2.5 |
November | 67250269.58 | 1807.97 | 02-NOV-06:01 | -1.6 | -3.2 | 0.00 | 0.00 | 01-NOV-00:10 | -1.6 | -3.2 |
December | 5851937.15 | 2444.04 | 30-DEC-05:01 | -20.6 | -21.1 | 0.00 | 0.00 | 01-DEC-00:10 | -20.6 | -21.1 |
Annual Sum or Average | 0.128657E+11 | 0.00 | ||||||||
Minimum of Months | 5851937.15 | 1807.97 | -25.0 | -25.2 | 0.00 | 0.00 | -25.0 | -25.2 | ||
Maximum of Months | 0.379642E+10 | 6182.28 | 36.83 | 17.19 | 0.00 | 0.00 | 36.83 | 17.19 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111867E+09 | 3453.30 | 27-JAN-17:10 | -23.3 | -23.9 | 0.00 | 0.00 | 01-JAN-00:10 | -23.3 | -23.9 |
February | 0.141371E+09 | 3281.31 | 01-FEB-07:10 | -24.9 | -25.2 | 0.00 | 0.00 | 01-FEB-00:10 | -24.9 | -25.2 |
March | 0.250545E+09 | 3563.48 | 03-MAR-17:10 | -14.4 | -15.2 | 0.00 | 0.00 | 01-MAR-00:10 | -14.4 | -15.2 |
April | 0.582674E+09 | 3609.34 | 27-APR-06:01 | -1.7 | -3.3 | 0.00 | 0.00 | 01-APR-00:10 | -1.7 | -3.3 |
May | 0.113270E+10 | 3284.48 | 19-MAY-16:00 | 27.80 | 14.54 | 0.00 | 0.00 | 01-MAY-00:10 | 27.80 | 14.54 |
June | 0.309261E+10 | 4545.12 | 29-JUN-16:00 | 31.10 | 14.33 | 0.00 | 0.00 | 01-JUN-00:10 | 31.10 | 14.33 |
July | 0.425868E+10 | 6546.30 | 17-JUL-12:08 | 35.18 | 16.48 | 0.00 | 0.00 | 01-JUL-00:10 | 35.18 | 16.48 |
August | 0.408045E+10 | 5921.05 | 07-AUG-17:10 | 32.02 | 15.78 | 0.00 | 0.00 | 01-AUG-00:10 | 32.02 | 15.78 |
September | 0.221199E+10 | 5782.22 | 05-SEP-06:15 | 18.90 | 12.98 | 0.00 | 0.00 | 01-SEP-00:10 | 18.90 | 12.98 |
October | 0.759953E+09 | 2735.54 | 20-OCT-06:06 | 2.48 | 0.77 | 0.00 | 0.00 | 01-OCT-00:10 | 2.48 | 0.77 |
November | 0.186049E+09 | 2803.93 | 02-NOV-06:01 | -1.6 | -3.2 | 0.00 | 0.00 | 01-NOV-00:10 | -1.6 | -3.2 |
December | 0.112690E+09 | 2609.83 | 29-DEC-17:10 | -21.3 | -21.7 | 0.00 | 0.00 | 01-DEC-00:10 | -21.3 | -21.7 |
Annual Sum or Average | 0.169216E+11 | 0.00 | ||||||||
Minimum of Months | 0.111867E+09 | 2609.83 | -24.9 | -25.2 | 0.00 | 0.00 | -24.9 | -25.2 | ||
Maximum of Months | 0.425868E+10 | 6546.30 | 35.18 | 16.48 | 0.00 | 0.00 | 35.18 | 16.48 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.464471E+10 | 5932.60 | 13-JAN-16:20 | 8.53 | 4.43 | 0.151752E+10 | 2223.36 | 13-JAN-16:00 | 7.80 | 3.93 |
February | 0.575951E+10 | 7888.15 | 28-FEB-17:00 | 10.00 | 4.31 | 0.147038E+10 | 2558.98 | 28-FEB-14:00 | 10.00 | 4.31 |
March | 0.815829E+10 | 8031.46 | 01-MAR-17:00 | 7.80 | 3.22 | 0.188605E+10 | 2585.49 | 02-MAR-14:00 | 11.10 | 4.79 |
April | 0.917742E+10 | 12069.57 | 25-APR-16:00 | 17.80 | 7.70 | 0.181008E+10 | 2606.60 | 13-APR-09:00 | 17.80 | 7.70 |
May | 0.113404E+11 | 30474.24 | 30-MAY-05:03 | 15.60 | 11.34 | 0.198651E+10 | 2606.66 | 04-MAY-13:20 | 15.60 | 11.34 |
June | 0.168715E+11 | 30566.44 | 29-JUN-05:03 | 8.35 | 5.45 | 0.206057E+10 | 2606.64 | 20-JUN-09:00 | 8.35 | 5.45 |
July | 0.188341E+11 | 32401.65 | 17-JUL-04:02 | 16.10 | 11.78 | 0.192069E+10 | 2606.68 | 13-JUL-09:00 | 16.10 | 11.78 |
August | 0.187619E+11 | 32159.65 | 07-AUG-04:02 | 20.03 | 10.92 | 0.215508E+10 | 2606.65 | 01-AUG-13:09 | 20.03 | 10.92 |
September | 0.139884E+11 | 31485.42 | 05-SEP-04:02 | 18.30 | 12.13 | 0.189379E+10 | 2606.70 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.100324E+11 | 13076.85 | 19-OCT-16:00 | 21.10 | 10.04 | 0.190816E+10 | 2606.62 | 20-OCT-09:20 | 8.17 | 4.16 |
November | 0.737984E+10 | 8817.93 | 03-NOV-16:00 | 14.30 | 7.69 | 0.172358E+10 | 2606.50 | 09-NOV-14:00 | 9.00 | 3.82 |
December | 0.591881E+10 | 6637.01 | 07-DEC-15:50 | 6.97 | 2.29 | 0.153978E+10 | 2444.36 | 07-DEC-14:00 | 6.97 | 2.29 |
Annual Sum or Average | 0.130867E+12 | 0.218722E+11 | ||||||||
Minimum of Months | 0.464471E+10 | 5932.60 | 6.97 | 2.29 | 0.147038E+10 | 2223.36 | 6.97 | 2.29 | ||
Maximum of Months | 0.188341E+11 | 32401.65 | 21.10 | 12.13 | 0.215508E+10 | 2606.70 | 20.03 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.271118E+10 | 5861.94 | 13-JAN-16:50 | 7.98 | 4.06 | 0.146604E+10 | 2154.74 | 13-JAN-16:00 | 7.80 | 3.93 |
February | 0.400620E+10 | 7162.54 | 28-FEB-17:00 | 10.00 | 4.31 | 0.138851E+10 | 2486.27 | 28-FEB-16:00 | 10.00 | 4.31 |
March | 0.663984E+10 | 7165.74 | 02-MAR-17:00 | 8.30 | 3.80 | 0.175621E+10 | 2531.26 | 23-MAR-13:00 | 10.00 | 2.51 |
April | 0.825157E+10 | 13161.30 | 25-APR-16:00 | 17.80 | 7.70 | 0.170488E+10 | 2606.59 | 13-APR-13:00 | 17.80 | 7.70 |
May | 0.107519E+11 | 16665.51 | 19-MAY-16:00 | 27.80 | 14.54 | 0.191358E+10 | 2606.62 | 19-MAY-13:09 | 27.80 | 14.54 |
June | 0.166384E+11 | 33022.35 | 21-JUN-05:03 | 15.87 | 11.84 | 0.204620E+10 | 2606.64 | 29-JUN-09:30 | 25.55 | 12.82 |
July | 0.189509E+11 | 34894.66 | 17-JUL-04:02 | 16.10 | 11.78 | 0.191510E+10 | 2606.67 | 13-JUL-09:00 | 16.10 | 11.78 |
August | 0.182422E+11 | 34637.17 | 07-AUG-04:02 | 20.03 | 10.92 | 0.214398E+10 | 2606.65 | 01-AUG-13:09 | 20.03 | 10.92 |
September | 0.128027E+11 | 35072.40 | 05-SEP-04:02 | 18.30 | 12.13 | 0.183579E+10 | 2606.69 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.861125E+10 | 12714.21 | 18-OCT-16:00 | 24.40 | 11.02 | 0.178255E+10 | 2606.57 | 19-OCT-13:09 | 21.10 | 10.07 |
November | 0.567197E+10 | 7271.86 | 03-NOV-16:00 | 14.30 | 7.69 | 0.158948E+10 | 2513.23 | 03-NOV-15:00 | 14.30 | 7.69 |
December | 0.365762E+10 | 6362.49 | 06-DEC-16:20 | 8.50 | 3.80 | 0.145149E+10 | 2307.26 | 07-DEC-14:00 | 8.30 | 2.55 |
Annual Sum or Average | 0.116936E+12 | 0.209938E+11 | ||||||||
Minimum of Months | 0.271118E+10 | 5861.94 | 7.98 | 3.80 | 0.138851E+10 | 2154.74 | 7.80 | 2.51 | ||
Maximum of Months | 0.189509E+11 | 35072.40 | 27.80 | 14.54 | 0.214398E+10 | 2606.69 | 27.80 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13135613.37 | 936.52 | 14-JAN-17:03 | 8.90 | 4.06 | 0.301609E+09 | 406.72 | 05-JAN-14:39 | 8.90 | 4.06 |
February | 0.157877E+09 | 1355.04 | 27-FEB-16:10 | 17.78 | 6.92 | 0.279063E+09 | 485.11 | 27-FEB-16:30 | 15.55 | 6.44 |
March | 0.561411E+09 | 1401.66 | 29-MAR-16:00 | 12.20 | 4.07 | 0.342451E+09 | 497.12 | 29-MAR-15:00 | 12.20 | 4.07 |
April | 0.119979E+10 | 3338.42 | 07-APR-14:30 | 22.50 | 9.29 | 0.331347E+09 | 549.48 | 07-APR-13:00 | 22.50 | 9.29 |
May | 0.220695E+10 | 5453.13 | 19-MAY-16:00 | 27.80 | 14.54 | 0.383899E+09 | 549.50 | 19-MAY-13:09 | 27.80 | 14.54 |
June | 0.445508E+10 | 6895.73 | 21-JUN-06:03 | 17.38 | 13.20 | 0.425503E+09 | 549.50 | 29-JUN-09:30 | 25.55 | 12.82 |
July | 0.547727E+10 | 11824.50 | 16-JUL-18:41 | 32.30 | 17.18 | 0.402664E+09 | 549.51 | 13-JUL-09:00 | 32.30 | 17.18 |
August | 0.471088E+10 | 11561.01 | 06-AUG-16:11 | 35.40 | 16.13 | 0.445155E+09 | 549.50 | 01-AUG-13:09 | 35.40 | 16.13 |
September | 0.260724E+10 | 10432.42 | 04-SEP-16:31 | 32.80 | 16.68 | 0.367723E+09 | 549.50 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.120177E+10 | 2694.96 | 19-OCT-14:40 | 21.50 | 10.24 | 0.344212E+09 | 549.48 | 19-OCT-13:00 | 21.50 | 10.24 |
November | 0.418202E+09 | 1298.93 | 03-NOV-16:00 | 14.30 | 7.69 | 0.309420E+09 | 476.66 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 63228920.12 | 1030.61 | 06-DEC-16:00 | 9.40 | 4.51 | 0.293565E+09 | 412.27 | 06-DEC-14:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.230728E+11 | 0.422661E+10 | ||||||||
Minimum of Months | 13135613.37 | 936.52 | 8.90 | 4.06 | 0.279063E+09 | 406.72 | 8.90 | 4.06 | ||
Maximum of Months | 0.547727E+10 | 11824.50 | 35.40 | 17.18 | 0.445155E+09 | 549.51 | 35.40 | 17.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 49359496.38 | 989.96 | 14-JAN-17:03 | 8.90 | 4.06 | 0.193000E+09 | 257.49 | 10-JAN-14:30 | 8.90 | 4.06 |
February | 0.369358E+09 | 1616.42 | 27-FEB-10:40 | 13.50 | 5.02 | 0.180490E+09 | 342.84 | 27-FEB-10:50 | 13.95 | 5.20 |
March | 0.905889E+09 | 3425.84 | 23-MAR-10:20 | 8.50 | 1.64 | 0.227709E+09 | 347.88 | 22-MAR-09:00 | 8.50 | 1.64 |
April | 0.177324E+10 | 6095.75 | 25-APR-09:30 | 10.80 | 5.26 | 0.221122E+09 | 347.88 | 12-APR-09:39 | 10.80 | 5.26 |
May | 0.279227E+10 | 7659.16 | 19-MAY-08:50 | 17.52 | 11.29 | 0.253563E+09 | 347.89 | 02-MAY-13:09 | 17.52 | 11.29 |
June | 0.514025E+10 | 13847.08 | 11-JUN-09:52 | 21.70 | 11.89 | 0.271190E+09 | 348.53 | 23-JUN-09:00 | 27.80 | 15.44 |
July | 0.635808E+10 | 14467.88 | 16-JUL-09:22 | 22.75 | 16.30 | 0.255376E+09 | 348.43 | 03-JUL-09:00 | 22.75 | 16.30 |
August | 0.568124E+10 | 14697.38 | 06-AUG-09:32 | 29.07 | 14.77 | 0.283862E+09 | 348.58 | 11-AUG-09:00 | 27.80 | 12.62 |
September | 0.309538E+10 | 11570.98 | 04-SEP-08:32 | 26.33 | 14.69 | 0.238024E+09 | 347.88 | 14-SEP-13:00 | 21.70 | 13.42 |
October | 0.151798E+10 | 4373.88 | 18-OCT-09:50 | 19.53 | 8.61 | 0.227668E+09 | 347.87 | 11-OCT-09:50 | 19.53 | 8.61 |
November | 0.580682E+09 | 1599.02 | 03-NOV-10:00 | 8.70 | 5.33 | 0.198484E+09 | 338.29 | 03-NOV-09:00 | 8.70 | 5.33 |
December | 0.125500E+09 | 1132.90 | 06-DEC-10:40 | 9.07 | 5.19 | 0.186318E+09 | 266.37 | 06-DEC-10:50 | 9.53 | 5.40 |
Annual Sum or Average | 0.283892E+11 | 0.273681E+10 | ||||||||
Minimum of Months | 49359496.38 | 989.96 | 8.50 | 1.64 | 0.180490E+09 | 257.49 | 8.50 | 1.64 | ||
Maximum of Months | 0.635808E+10 | 14697.38 | 29.07 | 16.30 | 0.283862E+09 | 348.58 | 27.80 | 16.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.699115E+09 | 4791.04 | 19-JAN-14:00 | -5.6 | -7.5 | 0.322580E+09 | 549.49 | 31-JAN-14:00 | -1.1 | -4.4 |
February | 0.167046E+10 | 12636.32 | 26-FEB-12:53 | 15.00 | 5.51 | 0.311645E+09 | 549.49 | 01-FEB-14:00 | 15.00 | 5.51 |
March | 0.250760E+10 | 10642.20 | 01-MAR-14:10 | 6.97 | 2.89 | 0.377396E+09 | 549.50 | 14-MAR-13:00 | 15.00 | 6.94 |
April | 0.296681E+10 | 10851.65 | 25-APR-13:40 | 16.30 | 6.98 | 0.346325E+09 | 549.50 | 13-APR-13:00 | 16.30 | 6.98 |
May | 0.398881E+10 | 10637.41 | 19-MAY-13:40 | 26.83 | 14.98 | 0.390945E+09 | 549.52 | 02-MAY-13:09 | 26.83 | 14.98 |
June | 0.628309E+10 | 12698.97 | 11-JUN-13:13 | 25.53 | 13.23 | 0.420126E+09 | 549.50 | 29-JUN-09:30 | 25.55 | 12.82 |
July | 0.801111E+10 | 18532.83 | 16-JUL-14:02 | 31.97 | 18.55 | 0.399976E+09 | 550.01 | 14-JUL-13:00 | 31.97 | 18.55 |
August | 0.863060E+10 | 19382.29 | 06-AUG-13:32 | 34.23 | 15.17 | 0.443318E+09 | 550.13 | 31-AUG-13:39 | 25.37 | 13.99 |
September | 0.633777E+10 | 20271.65 | 03-SEP-13:02 | 33.40 | 15.99 | 0.375975E+09 | 550.14 | 05-SEP-13:00 | 24.40 | 15.14 |
October | 0.415786E+10 | 18094.37 | 15-OCT-13:32 | 22.93 | 11.00 | 0.376004E+09 | 549.70 | 18-OCT-13:50 | 24.90 | 11.31 |
November | 0.211110E+10 | 10946.66 | 03-NOV-13:30 | 14.35 | 7.74 | 0.347992E+09 | 550.28 | 13-NOV-14:20 | 4.77 | -1.6 |
December | 0.101101E+10 | 5255.22 | 12-DEC-14:30 | -2.2 | -5.4 | 0.318938E+09 | 549.49 | 12-DEC-14:00 | -2.8 | -5.6 |
Annual Sum or Average | 0.483753E+11 | 0.443122E+10 | ||||||||
Minimum of Months | 0.699115E+09 | 4791.04 | -5.6 | -7.5 | 0.311645E+09 | 549.49 | -2.8 | -5.6 | ||
Maximum of Months | 0.863060E+10 | 20271.65 | 34.23 | 18.55 | 0.443318E+09 | 550.28 | 31.97 | 18.55 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101406E+09 | 1539.43 | 13-JAN-15:50 | 9.08 | 4.76 | 0.193331E+09 | 290.71 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.403448E+09 | 3972.03 | 28-FEB-16:50 | 10.18 | 4.40 | 0.180404E+09 | 338.70 | 27-FEB-16:40 | 10.18 | 4.40 |
March | 0.880024E+09 | 4932.64 | 28-MAR-16:00 | 10.60 | 3.09 | 0.220364E+09 | 347.83 | 02-MAR-14:00 | 10.60 | 3.09 |
April | 0.180156E+10 | 9348.26 | 22-APR-17:06 | 16.10 | 8.62 | 0.206256E+09 | 347.84 | 07-APR-13:00 | 16.10 | 8.62 |
May | 0.302022E+10 | 15561.17 | 13-MAY-18:22 | 21.95 | 8.73 | 0.237517E+09 | 347.85 | 19-MAY-13:09 | 26.28 | 14.91 |
June | 0.483788E+10 | 16037.73 | 24-JUN-17:42 | 26.38 | 11.78 | 0.261744E+09 | 347.85 | 29-JUN-09:30 | 25.55 | 12.82 |
July | 0.581288E+10 | 17794.70 | 09-JUL-16:31 | 28.30 | 12.98 | 0.250863E+09 | 347.86 | 13-JUL-09:00 | 23.30 | 13.98 |
August | 0.523404E+10 | 16512.84 | 06-AUG-16:11 | 35.40 | 16.13 | 0.275268E+09 | 347.85 | 01-AUG-13:09 | 35.40 | 16.13 |
September | 0.323742E+10 | 16654.33 | 04-SEP-16:31 | 32.80 | 16.68 | 0.225893E+09 | 347.85 | 05-SEP-09:09 | 17.20 | 11.96 |
October | 0.163108E+10 | 6575.19 | 18-OCT-16:00 | 24.40 | 11.02 | 0.215307E+09 | 347.83 | 18-OCT-13:00 | 24.40 | 11.02 |
November | 0.620148E+09 | 3020.58 | 03-NOV-15:50 | 14.35 | 7.69 | 0.200146E+09 | 338.68 | 09-NOV-16:30 | 8.50 | 3.41 |
December | 0.183647E+09 | 1680.76 | 06-DEC-15:50 | 9.68 | 4.65 | 0.187353E+09 | 309.36 | 06-DEC-15:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.277637E+11 | 0.265445E+10 | ||||||||
Minimum of Months | 0.101406E+09 | 1539.43 | 9.08 | 3.09 | 0.180404E+09 | 290.71 | 8.50 | 3.09 | ||
Maximum of Months | 0.581288E+10 | 17794.70 | 35.40 | 16.68 | 0.275268E+09 | 347.86 | 35.40 | 16.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11968701.33 | 924.27 | 14-JAN-17:03 | 8.90 | 4.06 | 0.301603E+09 | 406.71 | 10-JAN-14:30 | 8.90 | 4.06 |
February | 0.148257E+09 | 1170.84 | 27-FEB-16:20 | 16.67 | 6.71 | 0.278787E+09 | 445.76 | 27-FEB-14:00 | 16.67 | 6.71 |
March | 0.469832E+09 | 1208.02 | 29-MAR-16:00 | 12.20 | 4.07 | 0.337591E+09 | 457.75 | 02-MAR-14:00 | 12.20 | 4.07 |
April | 0.994402E+09 | 1454.11 | 07-APR-14:50 | 21.97 | 9.03 | 0.317150E+09 | 525.63 | 07-APR-13:00 | 21.97 | 9.03 |
May | 0.173600E+10 | 3217.91 | 19-MAY-16:00 | 27.80 | 14.54 | 0.376336E+09 | 549.48 | 19-MAY-13:00 | 27.80 | 14.54 |
June | 0.331388E+10 | 4654.01 | 29-JUN-15:30 | 31.65 | 14.51 | 0.426972E+09 | 549.49 | 23-JUN-09:09 | 31.65 | 14.51 |
July | 0.441871E+10 | 8277.90 | 16-JUL-18:31 | 32.40 | 17.11 | 0.403193E+09 | 549.50 | 13-JUL-09:00 | 32.40 | 17.11 |
August | 0.395297E+10 | 5545.07 | 09-AUG-15:00 | 33.30 | 15.95 | 0.449323E+09 | 549.50 | 01-AUG-13:09 | 33.30 | 15.95 |
September | 0.266498E+10 | 6286.78 | 04-SEP-13:02 | 30.92 | 15.72 | 0.380951E+09 | 549.50 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.166228E+10 | 2398.96 | 19-OCT-14:30 | 21.40 | 10.24 | 0.364582E+09 | 549.48 | 19-OCT-13:00 | 21.40 | 10.24 |
November | 0.784587E+09 | 1335.29 | 08-NOV-14:10 | 13.78 | 7.92 | 0.319858E+09 | 495.79 | 08-NOV-14:20 | 13.67 | 7.87 |
December | 0.130517E+09 | 1047.77 | 06-DEC-15:50 | 9.68 | 4.65 | 0.295097E+09 | 422.30 | 06-DEC-14:00 | 9.68 | 4.65 |
Annual Sum or Average | 0.202884E+11 | 0.425144E+10 | ||||||||
Minimum of Months | 11968701.33 | 924.27 | 8.90 | 4.06 | 0.278787E+09 | 406.71 | 8.90 | 4.06 | ||
Maximum of Months | 0.441871E+10 | 8277.90 | 33.30 | 17.11 | 0.449323E+09 | 549.50 | 33.30 | 17.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 46566521.95 | 892.95 | 20-JAN-10:05 | -3.1 | -5.8 | 0.193573E+09 | 263.22 | 20-JAN-10:20 | -2.9 | -5.7 |
February | 0.354668E+09 | 1302.11 | 27-FEB-10:40 | 13.50 | 5.02 | 0.182006E+09 | 340.25 | 27-FEB-10:50 | 13.95 | 5.20 |
March | 0.765360E+09 | 1996.54 | 23-MAR-10:30 | 8.60 | 1.66 | 0.227970E+09 | 347.89 | 28-MAR-09:30 | 6.10 | 1.03 |
April | 0.134683E+10 | 3751.49 | 25-APR-09:40 | 11.27 | 5.45 | 0.220894E+09 | 347.87 | 12-APR-09:50 | 11.27 | 5.45 |
May | 0.210062E+10 | 4995.10 | 19-MAY-09:30 | 18.90 | 11.91 | 0.254909E+09 | 347.87 | 02-MAY-09:00 | 18.90 | 11.91 |
June | 0.421315E+10 | 8354.97 | 25-JUN-08:52 | 16.70 | 11.81 | 0.273016E+09 | 348.28 | 23-JUN-09:00 | 16.70 | 11.81 |
July | 0.561362E+10 | 12296.42 | 16-JUL-09:51 | 23.30 | 16.52 | 0.256621E+09 | 348.12 | 13-JUL-09:39 | 23.30 | 16.52 |
August | 0.514587E+10 | 11443.16 | 06-AUG-09:32 | 29.07 | 14.77 | 0.286554E+09 | 348.23 | 11-AUG-09:50 | 27.52 | 12.49 |
September | 0.305949E+10 | 11660.87 | 04-SEP-08:22 | 26.15 | 14.59 | 0.247829E+09 | 347.88 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.177574E+10 | 3790.39 | 18-OCT-10:00 | 20.00 | 8.80 | 0.244531E+09 | 347.87 | 11-OCT-09:09 | 20.00 | 8.80 |
November | 0.839857E+09 | 1667.41 | 03-NOV-09:15 | 7.10 | 4.34 | 0.210333E+09 | 347.87 | 03-NOV-09:20 | 7.10 | 4.34 |
December | 0.213958E+09 | 995.69 | 07-DEC-10:50 | 5.55 | 2.29 | 0.187904E+09 | 281.02 | 07-DEC-10:00 | 6.10 | 2.52 |
Annual Sum or Average | 0.254757E+11 | 0.278614E+10 | ||||||||
Minimum of Months | 46566521.95 | 892.95 | -3.1 | -5.8 | 0.182006E+09 | 263.22 | -2.9 | -5.7 | ||
Maximum of Months | 0.561362E+10 | 12296.42 | 29.07 | 16.52 | 0.286554E+09 | 348.28 | 27.52 | 16.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205190E+09 | 1770.78 | 14-JAN-12:40 | 10.40 | 5.04 | 0.270825E+09 | 457.03 | 02-JAN-14:20 | 10.40 | 5.04 |
February | 0.643464E+09 | 8171.26 | 26-FEB-12:53 | 15.00 | 5.51 | 0.275314E+09 | 549.50 | 24-FEB-14:00 | 15.00 | 5.51 |
March | 0.796830E+09 | 4379.47 | 01-MAR-14:50 | 8.03 | 3.34 | 0.344919E+09 | 549.50 | 01-MAR-14:09 | 8.03 | 3.34 |
April | 0.120409E+10 | 5217.60 | 06-APR-14:30 | 20.85 | 10.20 | 0.321636E+09 | 549.50 | 25-APR-13:09 | 16.60 | 7.41 |
May | 0.192979E+10 | 8656.56 | 19-MAY-16:10 | 27.52 | 14.54 | 0.362140E+09 | 549.51 | 19-MAY-13:00 | 27.52 | 14.54 |
June | 0.429812E+10 | 12548.11 | 30-JUN-16:10 | 30.92 | 14.60 | 0.408054E+09 | 552.87 | 29-JUN-12:09 | 30.92 | 14.60 |
July | 0.697508E+10 | 15216.26 | 16-JUL-13:12 | 30.17 | 18.28 | 0.398956E+09 | 652.19 | 17-JUL-12:09 | 35.18 | 16.48 |
August | 0.739738E+10 | 14947.47 | 06-AUG-13:32 | 34.23 | 15.17 | 0.442735E+09 | 637.46 | 07-AUG-12:09 | 32.80 | 15.88 |
September | 0.516992E+10 | 15711.29 | 04-SEP-11:42 | 31.73 | 15.79 | 0.373337E+09 | 555.69 | 07-SEP-15:09 | 24.78 | 20.11 |
October | 0.316575E+10 | 14674.54 | 15-OCT-14:12 | 23.13 | 11.13 | 0.370467E+09 | 549.71 | 23-OCT-13:00 | 20.60 | 9.52 |
November | 0.126261E+10 | 7071.22 | 03-NOV-12:06 | 12.62 | 7.22 | 0.331650E+09 | 549.88 | 13-NOV-14:00 | 4.30 | -1.8 |
December | 0.367907E+09 | 2683.43 | 02-DEC-13:30 | 9.40 | 4.37 | 0.284416E+09 | 549.50 | 06-DEC-14:00 | 11.10 | 5.34 |
Annual Sum or Average | 0.334161E+11 | 0.418445E+10 | ||||||||
Minimum of Months | 0.205190E+09 | 1770.78 | 8.03 | 3.34 | 0.270825E+09 | 457.03 | 4.30 | -1.8 | ||
Maximum of Months | 0.739738E+10 | 15711.29 | 34.23 | 18.28 | 0.442735E+09 | 652.19 | 35.18 | 20.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66773664.41 | 1182.65 | 13-JAN-15:50 | 9.08 | 4.76 | 0.193812E+09 | 287.27 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.343929E+09 | 2909.57 | 28-FEB-16:50 | 10.18 | 4.40 | 0.180451E+09 | 338.69 | 27-FEB-16:30 | 10.18 | 4.40 |
March | 0.707169E+09 | 3031.43 | 28-MAR-17:30 | 9.75 | 2.59 | 0.219230E+09 | 340.78 | 02-MAR-14:00 | 9.75 | 2.59 |
April | 0.131235E+10 | 5264.86 | 25-APR-17:40 | 17.40 | 7.73 | 0.206177E+09 | 343.91 | 25-APR-13:00 | 17.40 | 7.73 |
May | 0.222405E+10 | 12493.73 | 28-MAY-18:31 | 19.27 | 10.23 | 0.242181E+09 | 347.84 | 30-MAY-13:00 | 18.90 | 10.34 |
June | 0.376285E+10 | 10544.52 | 24-JUN-17:42 | 26.38 | 11.78 | 0.268478E+09 | 347.85 | 29-JUN-09:20 | 25.17 | 12.64 |
July | 0.490897E+10 | 14363.56 | 16-JUL-18:31 | 32.40 | 17.11 | 0.255276E+09 | 347.86 | 13-JUL-09:00 | 32.40 | 17.11 |
August | 0.453545E+10 | 12665.59 | 05-AUG-18:22 | 33.60 | 16.58 | 0.283505E+09 | 347.85 | 01-AUG-13:09 | 33.60 | 16.58 |
September | 0.304997E+10 | 13214.50 | 04-SEP-17:01 | 32.62 | 16.70 | 0.240696E+09 | 347.86 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.186878E+10 | 5495.04 | 18-OCT-16:00 | 24.40 | 11.02 | 0.232427E+09 | 347.84 | 19-OCT-13:00 | 21.10 | 10.22 |
November | 0.896804E+09 | 2697.76 | 03-NOV-15:50 | 14.35 | 7.69 | 0.207405E+09 | 339.91 | 09-NOV-14:00 | 9.00 | 3.82 |
December | 0.228010E+09 | 1342.99 | 06-DEC-15:50 | 9.68 | 4.65 | 0.188868E+09 | 314.36 | 06-DEC-15:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.239051E+11 | 0.271851E+10 | ||||||||
Minimum of Months | 66773664.41 | 1182.65 | 9.08 | 2.59 | 0.180451E+09 | 287.27 | 8.90 | 2.59 | ||
Maximum of Months | 0.490897E+10 | 14363.56 | 33.60 | 17.11 | 0.283505E+09 | 347.86 | 33.60 | 17.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26009660.82 | 951.07 | 13-JAN-16:40 | 8.17 | 4.18 | 0.303896E+09 | 406.71 | 10-JAN-14:39 | 8.17 | 4.18 |
February | 0.294809E+09 | 1367.65 | 27-FEB-13:30 | 17.75 | 6.76 | 0.281760E+09 | 496.21 | 27-FEB-16:19 | 16.67 | 6.71 |
March | 0.855511E+09 | 1398.14 | 29-MAR-16:00 | 12.20 | 4.07 | 0.351657E+09 | 511.80 | 29-MAR-13:00 | 12.20 | 4.07 |
April | 0.150105E+10 | 3305.44 | 07-APR-14:30 | 22.50 | 9.29 | 0.346062E+09 | 549.48 | 13-APR-13:00 | 13.30 | 7.60 |
May | 0.236133E+10 | 4904.93 | 19-MAY-16:00 | 27.80 | 14.54 | 0.397027E+09 | 549.49 | 19-MAY-13:20 | 27.80 | 14.54 |
June | 0.447472E+10 | 8133.91 | 21-JUN-06:03 | 17.38 | 13.20 | 0.431351E+09 | 549.50 | 29-JUN-09:20 | 25.17 | 12.64 |
July | 0.538556E+10 | 10969.62 | 16-JUL-18:32 | 32.40 | 17.11 | 0.404500E+09 | 550.35 | 18-JUL-13:30 | 32.80 | 17.37 |
August | 0.472992E+10 | 9378.26 | 06-AUG-16:51 | 35.00 | 15.69 | 0.451097E+09 | 549.50 | 01-AUG-13:09 | 35.00 | 15.69 |
September | 0.285459E+10 | 10035.88 | 04-SEP-13:02 | 30.92 | 15.72 | 0.382017E+09 | 549.51 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.160080E+10 | 3000.19 | 19-OCT-14:30 | 21.40 | 10.24 | 0.364366E+09 | 549.48 | 19-OCT-13:00 | 21.40 | 10.24 |
November | 0.731353E+09 | 1417.76 | 03-NOV-13:30 | 14.35 | 7.74 | 0.320022E+09 | 505.29 | 08-NOV-14:30 | 13.55 | 7.81 |
December | 0.153866E+09 | 1063.79 | 06-DEC-16:00 | 9.40 | 4.51 | 0.295251E+09 | 430.47 | 06-DEC-14:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.249695E+11 | 0.432901E+10 | ||||||||
Minimum of Months | 26009660.82 | 951.07 | 8.17 | 4.07 | 0.281760E+09 | 406.71 | 8.17 | 4.07 | ||
Maximum of Months | 0.538556E+10 | 10969.62 | 35.00 | 17.11 | 0.451097E+09 | 550.35 | 35.00 | 17.37 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 89151838.91 | 1127.95 | 20-JAN-10:00 | -3.3 | -5.9 | 0.142363E+09 | 260.59 | 20-JAN-09:00 | -3.3 | -5.9 |
February | 0.492096E+09 | 2316.61 | 28-FEB-09:55 | 1.10 | -0.5 | 0.134513E+09 | 338.71 | 28-FEB-09:50 | 1.10 | -0.5 |
March | 0.114392E+10 | 4045.27 | 23-MAR-10:10 | 8.40 | 1.62 | 0.169919E+09 | 338.72 | 22-MAR-10:09 | 8.40 | 1.62 |
April | 0.206780E+10 | 6608.24 | 25-APR-09:00 | 9.40 | 4.65 | 0.165562E+09 | 338.72 | 24-APR-07:19 | 9.40 | 4.65 |
May | 0.293058E+10 | 7814.32 | 19-MAY-08:50 | 17.52 | 11.29 | 0.189273E+09 | 338.75 | 02-MAY-12:09 | 17.52 | 11.29 |
June | 0.508160E+10 | 12021.04 | 25-JUN-08:42 | 16.52 | 11.73 | 0.201282E+09 | 338.98 | 23-JUN-10:09 | 16.52 | 11.73 |
July | 0.620186E+10 | 15592.15 | 02-JUL-08:31 | 21.67 | 15.15 | 0.189730E+09 | 344.11 | 17-JUL-07:19 | 23.53 | 15.09 |
August | 0.558819E+10 | 14390.83 | 06-AUG-08:52 | 27.20 | 14.17 | 0.210481E+09 | 340.28 | 07-AUG-10:50 | 30.60 | 14.99 |
September | 0.331431E+10 | 14437.46 | 04-SEP-08:22 | 26.15 | 14.59 | 0.179010E+09 | 340.09 | 07-SEP-15:09 | 24.78 | 20.11 |
October | 0.186503E+10 | 4832.85 | 18-OCT-10:10 | 20.28 | 8.90 | 0.172941E+09 | 338.72 | 19-OCT-10:09 | 19.18 | 9.33 |
November | 0.836227E+09 | 2223.22 | 03-NOV-10:10 | 9.10 | 5.57 | 0.150637E+09 | 338.72 | 03-NOV-10:09 | 9.10 | 5.57 |
December | 0.215765E+09 | 1212.00 | 20-DEC-10:00 | 3.30 | -0.6 | 0.137820E+09 | 272.46 | 20-DEC-09:00 | 3.30 | -0.6 |
Annual Sum or Average | 0.298265E+11 | 0.204353E+10 | ||||||||
Minimum of Months | 89151838.91 | 1127.95 | -3.3 | -5.9 | 0.134513E+09 | 260.59 | -3.3 | -5.9 | ||
Maximum of Months | 0.620186E+10 | 15592.15 | 27.20 | 15.15 | 0.210481E+09 | 344.11 | 30.60 | 20.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.831285E+09 | 5610.23 | 19-JAN-13:40 | -6.0 | -7.8 | 0.327931E+09 | 549.49 | 13-JAN-14:39 | -6.0 | -7.8 |
February | 0.194131E+10 | 16939.03 | 26-FEB-12:53 | 15.00 | 5.51 | 0.320838E+09 | 549.52 | 28-FEB-14:00 | 10.60 | 4.78 |
March | 0.292680E+10 | 11288.69 | 01-MAR-13:50 | 6.52 | 2.64 | 0.387871E+09 | 549.54 | 01-MAR-14:00 | 8.30 | 3.44 |
April | 0.331164E+10 | 10409.33 | 25-APR-13:20 | 16.50 | 7.26 | 0.358493E+09 | 549.82 | 25-APR-13:00 | 16.10 | 6.69 |
May | 0.410139E+10 | 10012.73 | 19-MAY-13:30 | 26.65 | 14.96 | 0.402628E+09 | 549.52 | 02-MAY-13:09 | 26.65 | 14.96 |
June | 0.615962E+10 | 9941.52 | 30-JUN-13:30 | 28.05 | 13.89 | 0.428118E+09 | 549.52 | 19-JUN-13:30 | 28.05 | 13.89 |
July | 0.775328E+10 | 18047.25 | 16-JUL-13:12 | 30.17 | 18.28 | 0.403674E+09 | 550.08 | 18-JUL-13:50 | 32.07 | 17.42 |
August | 0.845331E+10 | 17594.76 | 06-AUG-13:32 | 34.23 | 15.17 | 0.450087E+09 | 550.66 | 22-AUG-13:50 | 24.13 | 15.51 |
September | 0.660376E+10 | 18299.68 | 03-SEP-13:22 | 33.60 | 16.11 | 0.387935E+09 | 563.03 | 07-SEP-15:09 | 24.78 | 20.11 |
October | 0.480299E+10 | 17254.32 | 15-OCT-13:32 | 22.93 | 11.00 | 0.391139E+09 | 552.58 | 18-OCT-13:39 | 24.80 | 11.21 |
November | 0.264740E+10 | 11467.82 | 03-NOV-13:20 | 14.13 | 7.69 | 0.361279E+09 | 549.49 | 03-NOV-09:39 | 14.13 | 7.69 |
December | 0.125243E+10 | 6044.91 | 12-DEC-14:30 | -2.2 | -5.4 | 0.327609E+09 | 549.49 | 12-DEC-10:00 | -2.2 | -5.4 |
Annual Sum or Average | 0.507852E+11 | 0.454760E+10 | ||||||||
Minimum of Months | 0.831285E+09 | 5610.23 | -6.0 | -7.8 | 0.320838E+09 | 549.49 | -6.0 | -7.8 | ||
Maximum of Months | 0.845331E+10 | 18299.68 | 34.23 | 18.28 | 0.450087E+09 | 563.03 | 32.07 | 20.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129454E+09 | 1492.68 | 13-JAN-15:50 | 9.08 | 4.76 | 0.194087E+09 | 302.51 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.524061E+09 | 4179.20 | 28-FEB-16:40 | 10.37 | 4.49 | 0.182394E+09 | 347.14 | 27-FEB-14:00 | 10.37 | 4.49 |
March | 0.114915E+10 | 4939.47 | 28-MAR-16:00 | 10.60 | 3.09 | 0.223928E+09 | 347.84 | 02-MAR-14:39 | 10.60 | 3.09 |
April | 0.204918E+10 | 8514.65 | 22-APR-17:06 | 16.10 | 8.62 | 0.213010E+09 | 347.84 | 07-APR-13:00 | 16.10 | 8.62 |
May | 0.309343E+10 | 12770.33 | 28-MAY-17:22 | 20.55 | 10.38 | 0.245120E+09 | 347.85 | 25-MAY-13:09 | 20.55 | 10.38 |
June | 0.472502E+10 | 14663.32 | 24-JUN-17:42 | 26.38 | 11.78 | 0.268072E+09 | 347.85 | 29-JUN-09:20 | 25.17 | 12.64 |
July | 0.561516E+10 | 17099.66 | 16-JUL-17:12 | 33.13 | 17.22 | 0.254241E+09 | 347.86 | 13-JUL-09:00 | 33.13 | 17.22 |
August | 0.510394E+10 | 14966.10 | 06-AUG-16:11 | 35.40 | 16.13 | 0.281495E+09 | 347.85 | 01-AUG-13:09 | 35.40 | 16.13 |
September | 0.338817E+10 | 15433.59 | 04-SEP-16:21 | 32.80 | 16.63 | 0.235019E+09 | 347.86 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.199640E+10 | 6477.67 | 18-OCT-16:00 | 24.40 | 11.02 | 0.225353E+09 | 347.84 | 19-OCT-13:00 | 21.10 | 10.22 |
November | 0.917177E+09 | 3315.80 | 03-NOV-15:50 | 14.35 | 7.69 | 0.205616E+09 | 347.78 | 09-NOV-14:00 | 9.00 | 3.82 |
December | 0.274327E+09 | 1631.09 | 06-DEC-15:50 | 9.68 | 4.65 | 0.189045E+09 | 322.60 | 06-DEC-15:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.289655E+11 | 0.271738E+10 | ||||||||
Minimum of Months | 0.129454E+09 | 1492.68 | 9.08 | 3.09 | 0.182394E+09 | 302.51 | 8.90 | 3.09 | ||
Maximum of Months | 0.561516E+10 | 17099.66 | 35.40 | 17.22 | 0.281495E+09 | 347.86 | 35.40 | 17.22 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 91483617.82 | 18689.87 | 02-JAN-06:03 | -1.3 |
February | 11927192.78 | 16955.82 | 06-FEB-06:01 | 0.60 |
March | 1938569.07 | 15640.86 | 06-MAR-07:01 | -19.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 6655581.39 | 18106.60 | 29-DEC-07:01 | -26.0 |
Annual Sum or Average | 0.112005E+09 | |||
Minimum of Months | 0.00 | 0.00 | -26.0 | |
Maximum of Months | 91483617.82 | 18689.87 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107168E+11 | 20173.78 | 28-JAN-06:12 | -25.9 |
February | 0.555523E+10 | 17662.95 | 04-FEB-06:12 | -19.6 |
March | 0.396903E+10 | 18493.83 | 06-MAR-06:12 | -17.1 |
April | 0.158274E+10 | 9624.99 | 29-APR-06:03 | -6.8 |
May | 0.112456E+10 | 12291.62 | 08-MAY-05:12 | -2.8 |
June | 0.352748E+09 | 6407.23 | 26-JUN-05:03 | 9.87 |
July | 0.187575E+09 | 8152.75 | 03-JUL-05:03 | 10.65 |
August | 0.314794E+09 | 5959.91 | 08-AUG-05:03 | 18.22 |
September | 0.711430E+09 | 5404.62 | 19-SEP-06:02 | 2.20 |
October | 0.154284E+10 | 11411.66 | 10-OCT-06:01 | -6.1 |
November | 0.396671E+10 | 17495.36 | 27-NOV-06:13 | -14.4 |
December | 0.807925E+10 | 18354.58 | 29-DEC-06:13 | -25.2 |
Annual Sum or Average | 0.381037E+11 | |||
Minimum of Months | 0.187575E+09 | 5404.62 | -25.9 | |
Maximum of Months | 0.107168E+11 | 20173.78 | 18.22 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.439177E+10 | 11563.39 | 09-JAN-07:04 | -27.2 |
February | 0.250102E+10 | 9510.21 | 06-FEB-06:12 | 0.60 |
March | 0.188317E+10 | 9505.67 | 06-MAR-06:12 | -17.1 |
April | 0.682945E+09 | 3886.89 | 16-APR-12:02 | 17.38 |
May | 0.649090E+09 | 3245.84 | 28-MAY-16:42 | 20.92 |
June | 32465036.51 | 3565.70 | 18-JUN-17:22 | 25.30 |
July | 41236624.01 | 4222.71 | 16-JUL-15:51 | 32.80 |
August | 37605392.53 | 4157.69 | 06-AUG-15:32 | 35.20 |
September | 0.240957E+09 | 5331.48 | 17-SEP-13:13 | 11.47 |
October | 0.749273E+09 | 6165.94 | 15-OCT-12:52 | 22.20 |
November | 0.187015E+10 | 9205.87 | 27-NOV-07:11 | -13.4 |
December | 0.310620E+10 | 9862.71 | 26-DEC-07:11 | -8.7 |
Annual Sum or Average | 0.161859E+11 | |||
Minimum of Months | 32465036.51 | 3245.84 | -27.2 | |
Maximum of Months | 0.439177E+10 | 11563.39 | 35.20 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316322E+10 | 7476.69 | 09-JAN-07:01 | -27.2 |
February | 0.177993E+10 | 6223.80 | 06-FEB-07:02 | 0.50 |
March | 0.125276E+10 | 5389.31 | 06-MAR-07:01 | -19.7 |
April | 0.353552E+09 | 3687.93 | 10-APR-07:04 | 4.08 |
May | 0.336107E+09 | 8232.91 | 22-MAY-05:01 | -0.6 |
June | 30257872.63 | 5456.47 | 09-JUN-05:03 | 5.47 |
July | 36863070.87 | 5083.65 | 05-JUL-04:03 | 9.40 |
August | 33374399.64 | 5177.55 | 18-AUG-05:03 | 7.30 |
September | 77885278.21 | 6588.51 | 12-SEP-05:03 | 4.60 |
October | 0.280450E+09 | 7004.66 | 02-OCT-05:02 | 4.60 |
November | 0.113447E+10 | 4606.28 | 27-NOV-09:00 | -11.9 |
December | 0.219806E+10 | 5785.10 | 26-DEC-07:01 | -8.5 |
Annual Sum or Average | 0.106769E+11 | |||
Minimum of Months | 30257872.63 | 3687.93 | -27.2 | |
Maximum of Months | 0.316322E+10 | 8232.91 | 9.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148845E+10 | 27299.97 | 09-JAN-05:01 | -27.2 |
February | 0.384973E+09 | 26520.52 | 06-FEB-05:01 | -0.4 |
March | 0.171174E+09 | 25563.81 | 06-MAR-06:01 | -16.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 8274180.36 | 22856.80 | 01-MAY-06:01 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 3395966.89 | 22819.79 | 10-OCT-06:01 | -6.1 |
November | 0.153307E+09 | 25305.92 | 27-NOV-06:01 | -14.5 |
December | 0.569864E+09 | 26341.43 | 26-DEC-05:01 | -7.3 |
Annual Sum or Average | 0.277944E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.148845E+10 | 27299.97 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.561342E+10 | 32837.33 | 08-JAN-20:01 | -26.7 |
February | 0.215037E+10 | 32130.54 | 06-FEB-05:01 | -0.4 |
March | 0.109398E+10 | 32208.19 | 06-MAR-05:01 | -18.4 |
April | 80897145.66 | 27389.11 | 29-APR-05:01 | -7.7 |
May | 0.186091E+09 | 29128.30 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 4796929.98 | 24946.55 | 19-SEP-06:02 | 2.20 |
October | 0.128949E+09 | 29396.26 | 10-OCT-05:01 | -6.1 |
November | 0.112997E+10 | 32316.26 | 27-NOV-05:11 | -15.3 |
December | 0.325033E+10 | 32937.90 | 31-DEC-23:21 | -23.6 |
Annual Sum or Average | 0.136388E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.561342E+10 | 32937.90 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.893280E+10 | 11558.48 | 09-JAN-06:01 | -27.2 |
February | 0.444683E+10 | 11026.08 | 05-FEB-23:32 | -7.0 |
March | 0.260588E+10 | 11249.88 | 06-MAR-02:42 | -18.2 |
April | 0.536410E+09 | 9853.47 | 29-APR-04:02 | -7.8 |
May | 0.367092E+09 | 10145.86 | 08-MAY-04:01 | -2.3 |
June | 2073757.94 | 6619.89 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 1089595.48 | 6352.20 | 18-AUG-06:03 | 8.17 |
September | 83729581.02 | 8970.93 | 20-SEP-05:02 | 3.30 |
October | 0.519518E+09 | 10145.75 | 10-OCT-04:01 | -5.2 |
November | 0.266236E+10 | 11266.23 | 27-NOV-04:32 | -15.7 |
December | 0.635065E+10 | 11494.29 | 31-DEC-21:21 | -24.1 |
Annual Sum or Average | 0.265084E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.893280E+10 | 11558.48 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.540630E+10 | 12969.48 | 29-JAN-23:01 | -26.1 |
February | 0.247617E+10 | 12324.35 | 05-FEB-03:32 | -20.0 |
March | 0.142443E+10 | 12624.75 | 06-MAR-02:42 | -18.2 |
April | 0.255264E+09 | 11093.13 | 29-APR-04:02 | -7.8 |
May | 0.191855E+09 | 11452.24 | 01-MAY-04:01 | -0.6 |
June | 1488687.05 | 5521.16 | 16-JUN-06:02 | 2.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 319424.81 | 894.31 | 18-AUG-05:03 | 7.30 |
September | 44080972.76 | 10061.61 | 19-SEP-05:02 | 2.20 |
October | 0.265017E+09 | 11398.45 | 10-OCT-04:01 | -5.2 |
November | 0.151814E+10 | 12653.19 | 27-NOV-04:32 | -15.7 |
December | 0.375159E+10 | 12936.79 | 31-DEC-21:21 | -24.1 |
Annual Sum or Average | 0.153346E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.1 | |
Maximum of Months | 0.540630E+10 | 12969.48 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.661356E+10 | 17574.57 | 08-JAN-20:01 | -26.7 |
February | 0.290723E+10 | 16806.53 | 05-FEB-03:32 | -20.0 |
March | 0.193197E+10 | 17185.98 | 06-MAR-02:42 | -18.2 |
April | 0.470554E+09 | 15093.97 | 29-APR-04:02 | -7.8 |
May | 0.392456E+09 | 15597.88 | 08-MAY-04:01 | -2.3 |
June | 8134245.79 | 8211.62 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 2566071.60 | 7637.40 | 18-AUG-06:03 | 8.17 |
September | 66776789.03 | 13688.58 | 19-SEP-05:02 | 2.20 |
October | 0.325716E+09 | 15604.80 | 10-OCT-04:01 | -5.2 |
November | 0.176133E+10 | 17230.10 | 27-NOV-04:32 | -15.7 |
December | 0.440388E+10 | 17610.76 | 31-DEC-23:21 | -23.6 |
Annual Sum or Average | 0.188842E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.661356E+10 | 17610.76 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.571352E+10 | 14733.42 | 08-JAN-20:01 | -26.7 |
February | 0.265040E+10 | 13994.13 | 05-FEB-09:32 | -19.8 |
March | 0.162131E+10 | 14380.58 | 06-MAR-02:42 | -18.2 |
April | 0.338494E+09 | 12331.07 | 29-APR-04:02 | -7.8 |
May | 0.252776E+09 | 12975.65 | 08-MAY-04:01 | -2.3 |
June | 6316484.17 | 5262.44 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 2391078.31 | 4965.10 | 18-AUG-06:03 | 8.17 |
September | 56066825.26 | 11473.63 | 19-SEP-05:02 | 2.20 |
October | 0.317996E+09 | 12989.91 | 10-OCT-04:01 | -5.2 |
November | 0.161201E+10 | 14419.90 | 27-NOV-04:32 | -15.7 |
December | 0.395604E+10 | 14750.62 | 31-DEC-23:21 | -23.6 |
Annual Sum or Average | 0.165273E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.571352E+10 | 14750.62 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.575523E+10 | 8175.83 | 11-JAN-03:42 | -29.3 |
February | 0.288318E+10 | 7902.85 | 06-FEB-05:01 | -0.4 |
March | 0.152299E+10 | 8129.98 | 06-MAR-03:42 | -18.4 |
April | 0.242198E+09 | 6993.62 | 29-APR-05:01 | -7.7 |
May | 0.118763E+09 | 7142.24 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 1822831.22 | 6201.56 | 19-SEP-06:02 | 2.20 |
October | 41085606.88 | 6736.87 | 10-OCT-05:01 | -6.1 |
November | 0.805874E+09 | 7880.84 | 27-NOV-05:11 | -15.3 |
December | 0.298068E+10 | 8117.85 | 31-DEC-23:51 | -23.3 |
Annual Sum or Average | 0.143518E+11 | |||
Minimum of Months | 0.00 | 0.00 | -29.3 | |
Maximum of Months | 0.575523E+10 | 8175.83 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.338220E+10 | 9819.82 | 09-JAN-02:52 | -27.2 |
February | 0.148936E+10 | 9490.80 | 06-FEB-05:01 | -0.4 |
March | 0.669720E+09 | 9718.46 | 06-MAR-05:01 | -18.4 |
April | 79892033.09 | 8404.99 | 29-APR-05:01 | -7.7 |
May | 46684404.37 | 8559.56 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 589167.02 | 2575.37 | 20-SEP-06:02 | 3.48 |
October | 15386560.35 | 8067.16 | 10-OCT-05:01 | -6.1 |
November | 0.444973E+09 | 9509.55 | 27-NOV-05:11 | -15.3 |
December | 0.170216E+10 | 9787.21 | 31-DEC-23:51 | -23.3 |
Annual Sum or Average | 0.783097E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.338220E+10 | 9819.82 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100649E+11 | 19486.35 | 11-JAN-07:10 | -27.2 |
February | 0.576762E+10 | 18569.55 | 01-FEB-07:10 | -24.9 |
March | 0.471863E+10 | 17237.56 | 06-MAR-07:10 | -19.7 |
April | 0.256638E+10 | 14016.95 | 28-APR-06:10 | -5.2 |
May | 0.217419E+10 | 13404.37 | 08-MAY-06:10 | -2.7 |
June | 0.518793E+09 | 11607.26 | 16-JUN-07:00 | 2.20 |
July | 99901235.51 | 10086.95 | 05-JUL-06:07 | 9.40 |
August | 0.392877E+09 | 10492.01 | 18-AUG-06:10 | 8.17 |
September | 0.803016E+09 | 11713.98 | 19-SEP-06:10 | 2.20 |
October | 0.142877E+10 | 14161.29 | 10-OCT-06:10 | -6.1 |
November | 0.340169E+10 | 15610.54 | 27-NOV-07:10 | -13.5 |
December | 0.658524E+10 | 18881.54 | 29-DEC-07:10 | -26.0 |
Annual Sum or Average | 0.385220E+11 | |||
Minimum of Months | 99901235.51 | 10086.95 | -27.2 | |
Maximum of Months | 0.100649E+11 | 19486.35 | 9.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362364E+10 | 10761.84 | 09-JAN-02:52 | -27.2 |
February | 0.155323E+10 | 10435.39 | 06-FEB-05:01 | -0.4 |
March | 0.781178E+09 | 10684.60 | 06-MAR-05:01 | -18.4 |
April | 0.110042E+09 | 9101.96 | 29-APR-05:01 | -7.7 |
May | 57430816.81 | 9447.74 | 08-MAY-05:01 | -2.8 |
June | 169203.67 | 1128.02 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 821077.05 | 3413.79 | 19-SEP-06:02 | 2.20 |
October | 20468647.81 | 8910.06 | 10-OCT-05:01 | -6.1 |
November | 0.446390E+09 | 10462.62 | 27-NOV-05:11 | -15.3 |
December | 0.180300E+10 | 10760.77 | 31-DEC-23:51 | -23.3 |
Annual Sum or Average | 0.839638E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.362364E+10 | 10761.84 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.559367E+10 | 9692.66 | 09-JAN-03:02 | -27.2 |
February | 0.241683E+10 | 9012.72 | 05-FEB-22:42 | -11.6 |
March | 0.104559E+10 | 9203.47 | 06-MAR-05:11 | -17.8 |
April | 93337726.40 | 7857.23 | 29-APR-05:01 | -7.7 |
May | 90585131.07 | 8172.31 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 5878848.20 | 7144.49 | 19-SEP-06:02 | 2.20 |
October | 96291044.40 | 8054.55 | 10-OCT-05:01 | -6.1 |
November | 0.106949E+10 | 9269.08 | 27-NOV-04:32 | -15.7 |
December | 0.328702E+10 | 9279.26 | 31-DEC-23:51 | -23.3 |
Annual Sum or Average | 0.136987E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.559367E+10 | 9692.66 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.336540E+10 | 12362.98 | 09-JAN-03:02 | -27.2 |
February | 0.134615E+10 | 11321.17 | 10-FEB-05:01 | -19.5 |
March | 0.577905E+09 | 11833.17 | 06-MAR-05:11 | -17.8 |
April | 46584435.13 | 10088.25 | 29-APR-05:01 | -7.7 |
May | 53297566.72 | 10282.46 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 4356420.23 | 7205.82 | 19-SEP-06:02 | 2.20 |
October | 52657966.33 | 10317.46 | 10-OCT-05:01 | -6.1 |
November | 0.658513E+09 | 11811.20 | 27-NOV-04:32 | -15.7 |
December | 0.196838E+10 | 11883.37 | 31-DEC-23:51 | -23.3 |
Annual Sum or Average | 0.807324E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.336540E+10 | 12362.98 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.380114E+10 | 15549.00 | 09-JAN-03:02 | -27.2 |
February | 0.137967E+10 | 14186.29 | 06-FEB-05:01 | -0.4 |
March | 0.702699E+09 | 14840.56 | 06-MAR-05:11 | -17.8 |
April | 85298527.69 | 12661.59 | 29-APR-05:01 | -7.7 |
May | 0.104364E+09 | 12994.57 | 08-MAY-05:01 | -2.8 |
June | 182255.34 | 1215.04 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 5441101.11 | 11164.24 | 19-SEP-06:02 | 2.20 |
October | 59452217.62 | 12997.36 | 10-OCT-05:01 | -6.1 |
November | 0.690838E+09 | 14845.90 | 27-NOV-04:32 | -15.7 |
December | 0.208023E+10 | 14970.47 | 31-DEC-23:51 | -23.3 |
Annual Sum or Average | 0.890932E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.380114E+10 | 15549.00 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351745E+10 | 12785.59 | 09-JAN-03:02 | -27.2 |
February | 0.139414E+10 | 11711.38 | 10-FEB-05:01 | -19.5 |
March | 0.659391E+09 | 12246.67 | 06-MAR-05:11 | -17.8 |
April | 68813793.32 | 10255.32 | 29-APR-05:01 | -7.7 |
May | 66605282.62 | 10554.98 | 08-MAY-05:01 | -2.8 |
June | 353877.81 | 2277.59 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 159335.07 | 1062.23 | 18-AUG-06:03 | 8.17 |
September | 5720648.63 | 7230.59 | 19-SEP-06:02 | 2.20 |
October | 63469849.00 | 10583.69 | 10-OCT-05:01 | -6.1 |
November | 0.658794E+09 | 12247.61 | 27-NOV-04:32 | -15.7 |
December | 0.204465E+10 | 12327.62 | 31-DEC-07:51 | -27.8 |
Annual Sum or Average | 0.847955E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.8 | |
Maximum of Months | 0.351745E+10 | 12785.59 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.208150E+11 | 18520.31 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.188385E+11 | 18520.31 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.216654E+11 | 18520.31 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.200796E+11 | 18520.31 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.212402E+11 | 18520.31 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.208620E+11 | 18520.31 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.204550E+11 | 18520.31 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.216654E+11 | 18520.31 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.200739E+11 | 18520.31 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.208179E+11 | 18520.31 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.203773E+11 | 18520.31 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.204522E+11 | 18520.31 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.247342E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.188385E+11 | 18520.31 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.216654E+11 | 18520.31 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.860391E+09 | 1168.55 | 02-JAN-08:09 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.723964E+09 | 1047.23 | 01-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.826482E+09 | 1123.43 | 17-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.718341E+09 | 920.14 | 14-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.759309E+09 | 818.62 | 03-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.745611E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.707298E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.790744E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.729001E+09 | 935.87 | 11-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.786642E+09 | 1168.55 | 30-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.824963E+09 | 1168.55 | 01-NOV-07:10 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.837036E+09 | 1168.55 | 01-DEC-16:40 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.930978E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.707298E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.860391E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.535323E+09 | 739.79 | 02-JAN-08:09 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.454635E+09 | 637.73 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.520609E+09 | 710.93 | 17-MAR-07:10 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.454136E+09 | 562.51 | 14-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.481537E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.474054E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.448500E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.501799E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.460827E+09 | 534.72 | 13-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.492882E+09 | 739.79 | 30-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.515939E+09 | 739.79 | 01-NOV-07:10 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.521416E+09 | 739.79 | 01-DEC-16:40 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.586166E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.448500E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.535323E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.837948E+09 | 1168.55 | 02-JAN-08:09 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.712261E+09 | 950.00 | 02-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.821223E+09 | 1123.43 | 17-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.719038E+09 | 918.70 | 14-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.761527E+09 | 824.31 | 03-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.749406E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.709811E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.793284E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.728070E+09 | 917.24 | 11-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.775016E+09 | 1168.55 | 30-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.804191E+09 | 1168.55 | 01-NOV-07:10 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.811705E+09 | 1168.55 | 01-DEC-16:40 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.922348E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.709811E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.837948E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.538703E+09 | 739.74 | 02-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.454791E+09 | 666.38 | 02-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.522386E+09 | 710.88 | 17-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.455473E+09 | 591.32 | 14-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.481382E+09 | 536.43 | 03-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.472756E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.448711E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.501411E+09 | 515.95 | 17-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.461655E+09 | 626.67 | 11-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.496286E+09 | 739.74 | 30-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.514530E+09 | 739.74 | 01-NOV-07:10 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.521370E+09 | 739.74 | 01-DEC-16:40 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.586945E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.448711E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.538703E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.858043E+09 | 1168.55 | 02-JAN-08:09 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.722237E+09 | 1039.55 | 01-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.825336E+09 | 1121.50 | 17-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.717641E+09 | 909.29 | 14-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.759078E+09 | 803.30 | 03-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.745397E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.707112E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.790455E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.728483E+09 | 925.12 | 11-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.784993E+09 | 1168.55 | 30-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.822352E+09 | 1168.55 | 01-NOV-07:10 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.834291E+09 | 1168.55 | 01-DEC-16:40 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.929542E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.707112E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.858043E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.534576E+09 | 739.79 | 02-JAN-08:09 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.454068E+09 | 632.29 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.520286E+09 | 709.97 | 17-MAR-07:10 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.453853E+09 | 556.02 | 14-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.481324E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.473789E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.448326E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.501533E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.460514E+09 | 527.01 | 13-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.492390E+09 | 739.79 | 30-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.515176E+09 | 739.79 | 01-NOV-07:10 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.520458E+09 | 739.79 | 01-DEC-16:40 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.585629E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.448326E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.534576E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.836609E+09 | 1168.55 | 02-JAN-08:09 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.711084E+09 | 937.66 | 02-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.820659E+09 | 1121.50 | 17-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.718312E+09 | 907.78 | 14-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.761126E+09 | 809.30 | 03-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.748926E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.709479E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.792716E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.727626E+09 | 905.42 | 11-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.774434E+09 | 1168.55 | 30-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.802145E+09 | 1168.55 | 01-NOV-07:10 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.810547E+09 | 1168.55 | 01-DEC-16:40 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.921366E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.709479E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.836609E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.537758E+09 | 739.74 | 02-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.454160E+09 | 663.51 | 02-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.521893E+09 | 709.92 | 17-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.455092E+09 | 586.34 | 14-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.481173E+09 | 529.62 | 03-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.472593E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.448582E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.501172E+09 | 508.43 | 17-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.461226E+09 | 622.84 | 11-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.495502E+09 | 739.74 | 30-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.513621E+09 | 739.74 | 01-NOV-07:10 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.520462E+09 | 739.74 | 01-DEC-16:40 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.586323E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.448582E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.537758E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.860390E+09 | 1168.55 | 02-JAN-08:09 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.723964E+09 | 1047.24 | 01-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.826481E+09 | 1123.43 | 17-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.718341E+09 | 920.12 | 14-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.759309E+09 | 818.59 | 03-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.745611E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.707298E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.790743E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.729001E+09 | 935.86 | 11-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.786642E+09 | 1168.55 | 30-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.824963E+09 | 1168.55 | 01-NOV-07:10 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.837036E+09 | 1168.55 | 01-DEC-16:40 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.930978E+10 | 0.266883E+11 | ||||
Minimum of Months | 0.707298E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.860390E+09 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.535323E+09 | 739.79 | 02-JAN-08:09 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.454626E+09 | 637.73 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.520609E+09 | 710.93 | 17-MAR-07:10 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.454135E+09 | 562.50 | 14-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.481537E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.474054E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.448500E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.501799E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.460827E+09 | 534.71 | 13-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.492882E+09 | 739.79 | 30-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.515939E+09 | 739.79 | 01-NOV-07:10 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.521416E+09 | 739.79 | 01-DEC-16:40 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.586165E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.448500E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.535323E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.837947E+09 | 1168.55 | 02-JAN-08:09 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.712261E+09 | 950.00 | 02-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.821223E+09 | 1123.43 | 17-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.719038E+09 | 918.69 | 14-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.761527E+09 | 824.29 | 03-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.749406E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.709811E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.793283E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.728070E+09 | 917.23 | 11-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.775016E+09 | 1168.55 | 30-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.804192E+09 | 1168.55 | 01-NOV-07:10 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.811705E+09 | 1168.55 | 01-DEC-16:40 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.922348E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.709811E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.837947E+09 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.538703E+09 | 739.74 | 02-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.454791E+09 | 666.38 | 02-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.522386E+09 | 710.88 | 17-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.455472E+09 | 591.30 | 14-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.481382E+09 | 536.41 | 03-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.472756E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.448711E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.501411E+09 | 515.93 | 17-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.461655E+09 | 626.66 | 11-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.496286E+09 | 739.74 | 30-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.514531E+09 | 739.74 | 01-NOV-07:10 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.521370E+09 | 739.74 | 01-DEC-16:40 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.586945E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.448711E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.538703E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.208150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.200796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.212402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.208620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.204550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.200739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.208179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.203773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.204522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.247342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.860391E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173300E+10 |
February | 0.901968E+09 | 0.723964E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129899E+10 |
March | 0.107774E+10 | 0.826482E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120913E+10 |
April | 0.956342E+09 | 0.718341E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.859861E+09 |
May | 0.103597E+10 | 0.759309E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2245310.93 | 0.886017E+09 |
June | 0.103308E+10 | 0.745611E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11721763.72 | 0.470695E+09 |
July | 0.959235E+09 | 0.707298E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40173533.89 | 0.320166E+09 |
August | 0.107774E+10 | 0.790744E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34171329.80 | 0.344111E+09 |
September | 0.956342E+09 | 0.729001E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21355947.26 | 0.589264E+09 |
October | 0.994195E+09 | 0.786642E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1032566.30 | 0.809089E+09 |
November | 0.984487E+09 | 0.824963E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115617E+10 |
December | 0.959235E+09 | 0.837036E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150631E+10 |
Annual Sum or Average | 0.119305E+11 | 0.930978E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110700E+09 | 0.111828E+11 |
Minimum of Months | 0.901968E+09 | 0.707298E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320166E+09 |
Maximum of Months | 0.107774E+10 | 0.860391E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40173533.89 | 0.173300E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.535323E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116203E+10 |
February | 0.571020E+09 | 0.454635E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882793E+09 |
March | 0.682301E+09 | 0.520609E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820807E+09 |
April | 0.605444E+09 | 0.454136E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591669E+09 |
May | 0.655854E+09 | 0.481537E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1541406.49 | 0.593141E+09 |
June | 0.654023E+09 | 0.474054E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7880846.51 | 0.318259E+09 |
July | 0.607275E+09 | 0.448500E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25955904.02 | 0.219339E+09 |
August | 0.682301E+09 | 0.501799E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22525793.99 | 0.232944E+09 |
September | 0.605444E+09 | 0.460827E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13573777.96 | 0.403234E+09 |
October | 0.629407E+09 | 0.492882E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 183656.04 | 0.557221E+09 |
November | 0.623262E+09 | 0.515939E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776903E+09 |
December | 0.607275E+09 | 0.521416E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100820E+10 |
Annual Sum or Average | 0.755301E+10 | 0.586166E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71661385.02 | 0.756654E+10 |
Minimum of Months | 0.571020E+09 | 0.448500E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219339E+09 |
Maximum of Months | 0.682301E+09 | 0.535323E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25955904.02 | 0.116203E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.837948E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178476E+10 |
February | 0.901968E+09 | 0.712261E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139777E+10 |
March | 0.107774E+10 | 0.821223E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127388E+10 |
April | 0.956342E+09 | 0.719038E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.907516E+09 |
May | 0.103597E+10 | 0.761527E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2243325.25 | 0.901809E+09 |
June | 0.103308E+10 | 0.749406E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11628845.40 | 0.471273E+09 |
July | 0.959235E+09 | 0.709811E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38249392.83 | 0.323332E+09 |
August | 0.107774E+10 | 0.793284E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33401047.74 | 0.352934E+09 |
September | 0.956342E+09 | 0.728070E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18871899.38 | 0.619390E+09 |
October | 0.994195E+09 | 0.775016E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 128292.46 | 0.892161E+09 |
November | 0.984487E+09 | 0.804191E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122394E+10 |
December | 0.959235E+09 | 0.811705E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156726E+10 |
Annual Sum or Average | 0.119305E+11 | 0.922348E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104523E+09 | 0.117160E+11 |
Minimum of Months | 0.901968E+09 | 0.709811E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323332E+09 |
Maximum of Months | 0.107774E+10 | 0.837948E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38249392.83 | 0.178476E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.538703E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116012E+10 |
February | 0.570983E+09 | 0.454791E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883048E+09 |
March | 0.682256E+09 | 0.522386E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821829E+09 |
April | 0.605404E+09 | 0.455473E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593943E+09 |
May | 0.655811E+09 | 0.481382E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1489543.08 | 0.608333E+09 |
June | 0.653980E+09 | 0.472756E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7749831.19 | 0.319368E+09 |
July | 0.607235E+09 | 0.448711E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26690116.76 | 0.221703E+09 |
August | 0.682256E+09 | 0.501411E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22863179.68 | 0.233015E+09 |
September | 0.605404E+09 | 0.461655E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14521170.08 | 0.399484E+09 |
October | 0.629366E+09 | 0.496286E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 305384.26 | 0.552932E+09 |
November | 0.623221E+09 | 0.514530E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780114E+09 |
December | 0.607235E+09 | 0.521370E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100927E+10 |
Annual Sum or Average | 0.755252E+10 | 0.586945E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73619225.05 | 0.758316E+10 |
Minimum of Months | 0.570983E+09 | 0.448711E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221703E+09 |
Maximum of Months | 0.682256E+09 | 0.538703E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26690116.76 | 0.116012E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.858043E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952058E+09 |
February | 0.901968E+09 | 0.722237E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728459E+09 |
March | 0.107774E+10 | 0.825336E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664951E+09 |
April | 0.956342E+09 | 0.717641E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462767E+09 |
May | 0.103597E+10 | 0.759078E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1391103.22 | 0.479139E+09 |
June | 0.103308E+10 | 0.745397E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6781992.94 | 0.249393E+09 |
July | 0.959235E+09 | 0.707112E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24138708.61 | 0.168676E+09 |
August | 0.107774E+10 | 0.790455E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19456844.95 | 0.186984E+09 |
September | 0.956342E+09 | 0.728483E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12860802.92 | 0.337128E+09 |
October | 0.994195E+09 | 0.784993E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 320864.79 | 0.484757E+09 |
November | 0.984487E+09 | 0.822352E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675175E+09 |
December | 0.959235E+09 | 0.834291E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850528E+09 |
Annual Sum or Average | 0.119305E+11 | 0.929542E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64950317.42 | 0.624001E+10 |
Minimum of Months | 0.901968E+09 | 0.707112E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168676E+09 |
Maximum of Months | 0.107774E+10 | 0.858043E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24138708.61 | 0.952058E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.534576E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640260E+09 |
February | 0.571020E+09 | 0.454068E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498105E+09 |
March | 0.682301E+09 | 0.520286E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455423E+09 |
April | 0.605444E+09 | 0.453853E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326859E+09 |
May | 0.655854E+09 | 0.481324E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 836190.58 | 0.331709E+09 |
June | 0.654023E+09 | 0.473789E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4310393.68 | 0.175729E+09 |
July | 0.607275E+09 | 0.448326E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14237589.58 | 0.122153E+09 |
August | 0.682301E+09 | 0.501533E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12211341.44 | 0.131954E+09 |
September | 0.605444E+09 | 0.460514E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7383288.11 | 0.236675E+09 |
October | 0.629407E+09 | 0.492390E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49318.89 | 0.339835E+09 |
November | 0.623262E+09 | 0.515176E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458209E+09 |
December | 0.607275E+09 | 0.520458E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572286E+09 |
Annual Sum or Average | 0.755301E+10 | 0.585629E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39028122.27 | 0.428919E+10 |
Minimum of Months | 0.571020E+09 | 0.448326E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122153E+09 |
Maximum of Months | 0.682301E+09 | 0.534576E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14237589.58 | 0.640260E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.836609E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108314E+11 |
February | 0.901968E+09 | 0.711084E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812104E+10 |
March | 0.107774E+10 | 0.820659E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790613E+10 |
April | 0.956342E+09 | 0.718312E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505183E+10 |
May | 0.103597E+10 | 0.761126E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24158874.96 | 0.473025E+10 |
June | 0.103308E+10 | 0.748926E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348961E+09 | 0.230043E+10 |
July | 0.959235E+09 | 0.709479E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812140E+09 | 0.100526E+10 |
August | 0.107774E+10 | 0.792716E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579650E+09 | 0.184906E+10 |
September | 0.956342E+09 | 0.727626E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102658E+09 | 0.318983E+10 |
October | 0.994195E+09 | 0.774434E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1483843.01 | 0.488920E+10 |
November | 0.984487E+09 | 0.802145E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679625E+10 |
December | 0.959235E+09 | 0.810547E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.873959E+10 |
Annual Sum or Average | 0.119305E+11 | 0.921366E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186905E+10 | 0.654103E+11 |
Minimum of Months | 0.901968E+09 | 0.709479E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100526E+10 |
Maximum of Months | 0.107774E+10 | 0.836609E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812140E+09 | 0.108314E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.537758E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638575E+09 |
February | 0.570983E+09 | 0.454160E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497255E+09 |
March | 0.682256E+09 | 0.521893E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454897E+09 |
April | 0.605404E+09 | 0.455092E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326580E+09 |
May | 0.655811E+09 | 0.481173E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 830086.86 | 0.341263E+09 |
June | 0.653980E+09 | 0.472593E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4144346.99 | 0.176160E+09 |
July | 0.607235E+09 | 0.448582E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14445386.10 | 0.123773E+09 |
August | 0.682256E+09 | 0.501172E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12273655.02 | 0.131734E+09 |
September | 0.605404E+09 | 0.461226E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7650443.05 | 0.235587E+09 |
October | 0.629366E+09 | 0.495502E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52435.62 | 0.336599E+09 |
November | 0.623221E+09 | 0.513621E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458714E+09 |
December | 0.607235E+09 | 0.520462E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571844E+09 |
Annual Sum or Average | 0.755252E+10 | 0.586323E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39396353.62 | 0.429298E+10 |
Minimum of Months | 0.570983E+09 | 0.448582E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123773E+09 |
Maximum of Months | 0.682256E+09 | 0.537758E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14445386.10 | 0.638575E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.860390E+09 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148145E+10 |
February | 0.901968E+09 | 0.723964E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114350E+10 |
March | 0.107774E+10 | 0.826481E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105934E+10 |
April | 0.956342E+09 | 0.718341E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764418E+09 |
May | 0.103597E+10 | 0.759309E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1891856.09 | 0.782416E+09 |
June | 0.103308E+10 | 0.745611E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9987742.55 | 0.407585E+09 |
July | 0.959235E+09 | 0.707298E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34556075.12 | 0.277201E+09 |
August | 0.107774E+10 | 0.790743E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28896418.80 | 0.301060E+09 |
September | 0.956342E+09 | 0.729001E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18066115.25 | 0.527240E+09 |
October | 0.994195E+09 | 0.786642E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 453310.21 | 0.741279E+09 |
November | 0.984487E+09 | 0.824963E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103166E+10 |
December | 0.959235E+09 | 0.837036E+09 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130241E+10 |
Annual Sum or Average | 0.119305E+11 | 0.930978E+10 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93851518.02 | 0.981956E+10 |
Minimum of Months | 0.901968E+09 | 0.707298E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277201E+09 |
Maximum of Months | 0.107774E+10 | 0.860390E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34556075.12 | 0.148145E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.535323E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.993198E+09 |
February | 0.421807E+09 | 0.454626E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776482E+09 |
March | 0.502994E+09 | 0.520609E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717749E+09 |
April | 0.447140E+09 | 0.454135E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522357E+09 |
May | 0.484071E+09 | 0.481537E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1306122.91 | 0.521665E+09 |
June | 0.482240E+09 | 0.474054E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6733301.86 | 0.274238E+09 |
July | 0.448971E+09 | 0.448500E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22374909.59 | 0.188608E+09 |
August | 0.502994E+09 | 0.501799E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19045901.53 | 0.202562E+09 |
September | 0.447140E+09 | 0.460827E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11641512.75 | 0.356991E+09 |
October | 0.465148E+09 | 0.492882E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92313.73 | 0.506102E+09 |
November | 0.460569E+09 | 0.515939E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692286E+09 |
December | 0.448971E+09 | 0.521416E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874082E+09 |
Annual Sum or Average | 0.557719E+10 | 0.586165E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61194062.37 | 0.662632E+10 |
Minimum of Months | 0.421807E+09 | 0.448500E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188608E+09 |
Maximum of Months | 0.502994E+09 | 0.535323E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22374909.59 | 0.993198E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.837947E+09 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153550E+10 |
February | 0.901968E+09 | 0.712261E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123093E+10 |
March | 0.107774E+10 | 0.821223E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111530E+10 |
April | 0.956342E+09 | 0.719038E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802830E+09 |
May | 0.103597E+10 | 0.761527E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1873527.54 | 0.795393E+09 |
June | 0.103308E+10 | 0.749406E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9821788.95 | 0.409460E+09 |
July | 0.959235E+09 | 0.709811E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32225985.91 | 0.280903E+09 |
August | 0.107774E+10 | 0.793283E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28000882.52 | 0.308739E+09 |
September | 0.956342E+09 | 0.728070E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15879040.89 | 0.549997E+09 |
October | 0.994195E+09 | 0.775016E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108336.42 | 0.806148E+09 |
November | 0.984487E+09 | 0.804192E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109344E+10 |
December | 0.959235E+09 | 0.811705E+09 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137256E+10 |
Annual Sum or Average | 0.119305E+11 | 0.922348E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87909562.22 | 0.103012E+11 |
Minimum of Months | 0.901968E+09 | 0.709811E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280903E+09 |
Maximum of Months | 0.107774E+10 | 0.837947E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32225985.91 | 0.153550E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.538703E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.990882E+09 |
February | 0.570983E+09 | 0.454791E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776384E+09 |
March | 0.682256E+09 | 0.522386E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718491E+09 |
April | 0.605404E+09 | 0.455472E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525779E+09 |
May | 0.655811E+09 | 0.481382E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1246264.34 | 0.535845E+09 |
June | 0.653980E+09 | 0.472756E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6460346.05 | 0.277398E+09 |
July | 0.607235E+09 | 0.448711E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22270765.43 | 0.192211E+09 |
August | 0.682256E+09 | 0.501411E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19119086.37 | 0.204231E+09 |
September | 0.605404E+09 | 0.461655E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11993886.84 | 0.356020E+09 |
October | 0.629366E+09 | 0.496286E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 101551.03 | 0.503306E+09 |
November | 0.623221E+09 | 0.514531E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694411E+09 |
December | 0.607235E+09 | 0.521370E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.873546E+09 |
Annual Sum or Average | 0.755252E+10 | 0.586945E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61191900.06 | 0.664850E+10 |
Minimum of Months | 0.570983E+09 | 0.448711E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192211E+09 |
Maximum of Months | 0.682256E+09 | 0.538703E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22270765.43 | 0.990882E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200849E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160112E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147276E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106591E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1865856.04 | 0.107441E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10014583.61 | 0.549681E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38538559.85 | 0.374047E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32660845.36 | 0.411422E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20760296.43 | 0.742903E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41205.70 | 0.107207E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147439E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183588E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103881E+09 | 0.136831E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374047E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38538559.85 | 0.200849E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249104E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196135E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182271E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132427E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2480292.14 | 0.134351E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13027155.08 | 0.700579E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50233423.69 | 0.476257E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42226125.63 | 0.520424E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27110619.15 | 0.920610E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104802.38 | 0.128909E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177440E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223035E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135182E+09 | 0.168546E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476257E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50233423.69 | 0.249104E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255831E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196784E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184837E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134050E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1426492.82 | 0.137088E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10555883.52 | 0.729962E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40230574.80 | 0.491782E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37815737.10 | 0.528845E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21624211.79 | 0.914774E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125953E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174139E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223672E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111653E+09 | 0.169889E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491782E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40230574.80 | 0.255831E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 18520.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 18520.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 18520.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 18520.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 18520.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 18520.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 18520.31 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 18520.31 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 18520.31 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 18520.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 18520.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 18520.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-08:09 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3205.43 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 1047.23 | 01-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1761.34 | 08-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 1123.43 | 17-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2173.48 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 920.14 | 14-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1511.66 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 818.62 | 03-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.49 | 20-MAY-17:03 | 2775.33 | 22-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.87 | 29-JUN-15:00 | 1221.54 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.22 | 30-JUL-11:53 | 728.82 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.66 | 06-AUG-17:36 | 899.57 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 935.87 | 11-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 465.39 | 03-SEP-12:51 | 1566.37 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1168.55 | 30-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.77 | 15-OCT-13:55 | 1379.28 | 30-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 01-NOV-07:10 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1781.64 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:40 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2430.49 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 728.82 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 465.39 | 3205.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 739.79 | 02-JAN-08:09 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2136.27 | 05-JAN-22:01 |
February | 827.22 | 01-FEB-10:09 | 637.73 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1173.48 | 08-FEB-22:02 |
March | 827.22 | 01-MAR-10:09 | 710.93 | 17-MAR-07:10 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1447.11 | 02-MAR-23:00 |
April | 827.22 | 03-APR-09:09 | 562.51 | 14-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1006.35 | 27-APR-02:00 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.62 | 20-MAY-17:03 | 1850.19 | 22-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.58 | 29-JUN-15:00 | 832.58 | 04-JUN-14:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.98 | 30-JUL-14:50 | 483.71 | 05-JUL-01:00 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.59 | 06-AUG-17:38 | 588.96 | 22-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 534.72 | 13-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.34 | 03-SEP-13:05 | 1032.23 | 12-SEP-03:00 |
October | 827.22 | 02-OCT-09:09 | 739.79 | 30-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 15-OCT-14:20 | 920.44 | 30-OCT-21:05 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 01-NOV-07:10 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1186.59 | 29-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-16:40 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1621.39 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.71 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 310.34 | 2136.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-08:09 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3206.36 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 950.00 | 02-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1765.45 | 08-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 1123.43 | 17-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2237.96 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 918.70 | 14-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1522.31 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 824.31 | 03-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.48 | 20-MAY-17:03 | 2775.33 | 22-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.87 | 29-JUN-15:00 | 1220.80 | 04-JUN-14:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 307.03 | 30-JUL-14:10 | 734.55 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 425.55 | 06-AUG-17:36 | 904.80 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 917.24 | 11-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 423.04 | 03-SEP-13:10 | 1565.91 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1168.55 | 30-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.52 | 18-OCT-14:00 | 1400.05 | 30-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 01-NOV-07:10 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1782.08 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:40 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2446.96 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 734.55 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 425.55 | 3206.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2135.83 | 05-JAN-22:01 |
February | 827.17 | 01-FEB-10:09 | 666.38 | 02-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1174.60 | 08-FEB-22:02 |
March | 827.17 | 01-MAR-10:09 | 710.88 | 17-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1469.05 | 02-MAR-23:00 |
April | 827.17 | 03-APR-09:09 | 591.32 | 14-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1005.39 | 27-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 536.43 | 03-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.53 | 20-MAY-17:03 | 1850.19 | 22-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.58 | 29-JUN-15:00 | 813.99 | 14-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.33 | 30-JUL-12:10 | 501.15 | 05-JUL-01:00 |
August | 827.17 | 01-AUG-09:09 | 515.95 | 17-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 283.72 | 06-AUG-12:00 | 601.35 | 22-AUG-21:10 |
September | 827.17 | 01-SEP-09:09 | 626.67 | 11-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.30 | 03-SEP-12:51 | 1025.93 | 12-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 739.74 | 30-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.35 | 15-OCT-13:00 | 922.84 | 30-OCT-21:05 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 01-NOV-07:10 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1186.36 | 29-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:40 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1620.32 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.15 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 340.30 | 2135.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-08:09 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1708.73 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 1039.55 | 01-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 938.50 | 08-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 1121.50 | 17-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1197.05 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 909.29 | 14-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 830.74 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 803.30 | 03-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.67 | 20-MAY-17:03 | 1669.90 | 22-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.15 | 29-JUN-15:00 | 693.68 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.99 | 30-JUL-11:53 | 412.98 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.19 | 06-AUG-18:00 | 522.22 | 23-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 925.12 | 11-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 285.44 | 03-SEP-13:00 | 967.14 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1168.55 | 30-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.75 | 15-OCT-13:55 | 786.62 | 30-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 01-NOV-07:10 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 953.31 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:40 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1377.59 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.98 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 285.44 | 1708.73 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 739.79 | 02-JAN-08:09 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1138.83 | 05-JAN-22:01 |
February | 827.22 | 01-FEB-10:09 | 632.29 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 625.45 | 08-FEB-22:02 |
March | 827.22 | 01-MAR-10:09 | 709.97 | 17-MAR-07:10 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 806.99 | 02-MAR-23:00 |
April | 827.22 | 03-APR-09:09 | 556.02 | 14-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 575.48 | 27-APR-02:00 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.01 | 20-MAY-17:03 | 1115.19 | 22-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.10 | 29-JUN-15:00 | 465.97 | 14-JUN-02:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.12 | 30-JUL-14:00 | 282.96 | 05-JUL-01:00 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.73 | 06-AUG-17:40 | 358.71 | 23-AUG-03:00 |
September | 827.22 | 01-SEP-09:09 | 527.01 | 13-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.57 | 03-SEP-12:51 | 643.76 | 12-SEP-03:00 |
October | 827.22 | 02-OCT-09:09 | 739.79 | 30-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 18-OCT-14:00 | 536.29 | 30-OCT-22:00 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 01-NOV-07:10 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 635.04 | 29-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-16:40 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 910.59 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.96 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 167.57 | 1138.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-08:09 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 55502.21 | 10-JAN-17:01 |
February | 1306.65 | 01-FEB-10:09 | 937.66 | 02-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 54252.09 | 01-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1121.50 | 17-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 45698.76 | 06-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 907.78 | 14-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 29387.06 | 28-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 809.30 | 03-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3848.84 | 19-MAY-16:10 | 26483.29 | 08-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7542.30 | 28-JUN-16:10 | 19888.50 | 16-JUN-06:02 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13079.89 | 17-JUL-16:02 | 13537.85 | 05-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8205.23 | 07-AUG-16:03 | 16233.35 | 28-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 905.42 | 11-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4314.66 | 01-SEP-16:10 | 20646.68 | 19-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 1168.55 | 30-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.93 | 18-OCT-14:00 | 30904.26 | 10-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 01-NOV-07:10 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 40185.89 | 27-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:40 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 53914.64 | 29-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13537.85 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 13079.89 | 55502.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1138.66 | 05-JAN-22:01 |
February | 827.17 | 01-FEB-10:09 | 663.51 | 02-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 630.22 | 17-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 709.92 | 17-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 825.54 | 02-MAR-23:00 |
April | 827.17 | 03-APR-09:09 | 586.34 | 14-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 570.86 | 27-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 529.62 | 03-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.92 | 20-MAY-17:03 | 1116.77 | 22-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.10 | 29-JUN-15:00 | 471.49 | 14-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.50 | 30-JUL-12:10 | 289.13 | 05-JUL-01:00 |
August | 827.17 | 01-AUG-09:09 | 508.43 | 17-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.58 | 06-AUG-12:00 | 359.42 | 23-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 622.84 | 11-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.08 | 03-SEP-12:51 | 643.53 | 12-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 739.74 | 30-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.46 | 18-OCT-14:00 | 539.35 | 30-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 01-NOV-07:10 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 634.95 | 29-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:40 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 916.74 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.13 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 184.08 | 1138.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-08:09 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2674.37 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 1047.24 | 01-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1471.03 | 08-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 1123.43 | 17-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1898.44 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 920.12 | 14-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1348.44 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 818.59 | 03-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.78 | 20-MAY-17:03 | 2541.53 | 22-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.01 | 29-JUN-15:00 | 1091.52 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.01 | 30-JUL-12:00 | 650.28 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 342.40 | 06-AUG-17:36 | 810.37 | 23-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 935.86 | 11-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.16 | 03-SEP-13:00 | 1439.01 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1168.55 | 30-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.85 | 15-OCT-13:55 | 1194.74 | 30-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 01-NOV-07:10 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1490.61 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:40 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2020.95 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.28 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 407.16 | 2674.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 739.79 | 02-JAN-08:09 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1782.39 | 05-JAN-22:01 |
February | 805.43 | 01-FEB-08:09 | 637.73 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 980.14 | 08-FEB-22:02 |
March | 805.43 | 01-MAR-08:09 | 710.93 | 17-MAR-07:10 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1261.99 | 02-MAR-23:00 |
April | 805.43 | 03-APR-07:10 | 562.50 | 14-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 896.09 | 27-APR-02:00 |
May | 805.43 | 01-MAY-07:10 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.14 | 20-MAY-17:03 | 1681.95 | 22-MAY-04:00 |
June | 805.43 | 01-JUN-07:10 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.67 | 29-JUN-15:00 | 717.43 | 14-JUN-02:00 |
July | 805.43 | 03-JUL-07:10 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.47 | 30-JUL-11:50 | 431.56 | 05-JUL-01:00 |
August | 805.43 | 01-AUG-07:10 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.58 | 06-AUG-17:40 | 536.73 | 23-AUG-03:00 |
September | 805.43 | 01-SEP-07:10 | 534.71 | 13-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.43 | 03-SEP-12:51 | 948.65 | 12-SEP-03:00 |
October | 805.43 | 02-OCT-07:10 | 739.79 | 30-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 | 15-OCT-14:20 | 795.87 | 30-OCT-22:00 |
November | 805.43 | 01-NOV-07:10 | 739.79 | 01-NOV-07:10 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 992.87 | 29-NOV-22:02 |
December | 805.43 | 01-DEC-08:09 | 739.79 | 01-DEC-16:40 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1377.17 | 01-DEC-05:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.56 | |||||
Maximum of Months | 805.43 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 264.43 | 1782.39 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-08:09 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2675.07 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 950.00 | 02-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1474.40 | 17-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 1123.43 | 17-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1950.73 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 918.69 | 14-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1356.39 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 824.29 | 03-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.35 | 20-MAY-17:03 | 2548.94 | 22-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.00 | 29-JUN-15:00 | 1086.88 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.73 | 30-JUL-14:30 | 654.97 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 349.21 | 06-AUG-17:36 | 820.02 | 23-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 917.23 | 11-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.82 | 03-SEP-12:56 | 1440.71 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1168.55 | 30-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 | 18-OCT-14:20 | 1251.05 | 30-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 01-NOV-07:10 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1491.07 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-16:40 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2052.12 | 01-DEC-05:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.97 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 373.82 | 2675.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1782.10 | 05-JAN-22:01 |
February | 827.17 | 01-FEB-10:09 | 666.38 | 02-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 981.03 | 08-FEB-22:02 |
March | 827.17 | 01-MAR-10:09 | 710.88 | 17-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1280.29 | 02-MAR-23:00 |
April | 827.17 | 03-APR-09:09 | 591.30 | 14-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 897.63 | 27-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 536.41 | 03-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.41 | 20-MAY-17:03 | 1679.28 | 22-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.67 | 29-JUN-15:00 | 728.01 | 14-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.11 | 30-JUL-11:55 | 446.03 | 05-JUL-01:00 |
August | 827.17 | 01-AUG-09:09 | 515.93 | 17-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.72 | 06-AUG-12:00 | 542.22 | 23-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 626.66 | 11-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.55 | 03-SEP-12:52 | 944.79 | 12-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 739.74 | 30-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.32 | 18-OCT-14:00 | 802.83 | 30-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 01-NOV-07:10 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 992.75 | 29-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-16:40 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1375.51 | 01-DEC-05:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.03 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 292.55 | 1782.10 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3364.10 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2117.68 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2659.44 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1881.92 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.94 | 20-MAY-17:03 | 3731.89 | 22-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.51 | 29-JUN-15:00 | 1518.51 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.72 | 30-JUL-11:53 | 896.37 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.14 | 06-AUG-18:00 | 1148.01 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.06 | 03-SEP-13:00 | 2072.04 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.03 | 18-OCT-14:00 | 1721.34 | 30-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1994.95 | 26-NOV-19:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3045.12 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 896.37 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.06 | 3731.89 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4285.39 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2594.15 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3344.17 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2385.42 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.29 | 20-MAY-17:03 | 4633.89 | 22-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.72 | 29-JUN-15:00 | 1927.07 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 511.94 | 30-JUL-12:00 | 1122.57 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 545.25 | 06-AUG-18:00 | 1441.42 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 655.34 | 03-SEP-13:00 | 2562.41 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 18-OCT-14:00 | 2106.06 | 30-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2417.03 | 26-NOV-20:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3663.97 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1122.57 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 655.34 | 4633.89 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4638.86 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2563.82 | 08-FEB-22:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3379.63 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2307.04 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.83 | 20-MAY-17:03 | 4359.19 | 22-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.30 | 29-JUN-15:00 | 1984.47 | 04-JUN-14:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.33 | 30-JUL-11:53 | 1093.65 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.90 | 06-AUG-18:00 | 1416.69 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.85 | 03-SEP-12:51 | 2384.70 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2099.55 | 30-OCT-21:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2534.33 | 29-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3407.75 | 31-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.65 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.85 | 4638.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8535.91 | 19-JAN-16:50 | 12070.02 | 11086.35 | 29456.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16037.07 | 28-FEB-08:15 | 24140.03 | 22172.69 | 74081.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17957.00 | 24-MAR-07:04 | 60350.08 | 55431.73 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24050.77 | 26-APR-05:03 | 2541.06 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41030.50 | 22-MAY-05:01 | 4446.85 | 4311.12 | 35969.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40414.20 | 15-JUN-05:02 | 3176.32 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 43203.87 | 17-JUL-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 44148.82 | 14-AUG-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 42921.75 | 11-SEP-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40637.34 | 20-OCT-05:02 | 3176.32 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17881.51 | 03-NOV-16:00 | 6035.01 | 5543.17 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13862.15 | 08-DEC-08:08 | 60350.08 | 55431.73 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 8535.91 | 0.00 | 2463.50 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44148.82 | 60350.08 | 55431.73 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 314.37 | 14-JAN-17:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.12 |
February | 1876.03 | 26-FEB-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.76 |
March | 2324.80 | 22-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.73 |
April | 5820.60 | 25-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.64 |
May | 9243.05 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.63 | 0.00 |
June | 10648.65 | 23-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.43 | 0.00 |
July | 13244.38 | 17-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11915.01 | 07-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.22 | 0.00 |
September | 8836.83 | 01-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.55 | 0.00 |
October | 5461.14 | 18-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 |
November | 1162.56 | 03-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.24 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2173.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13244.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.63 | 2173.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2482.68 | 07-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2101.21 |
February | 2893.51 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 708.91 |
March | 3156.74 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1304.45 |
April | 3334.18 | 27-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.52 |
May | 3104.94 | 19-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.50 | 0.00 |
June | 4364.13 | 23-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 | 0.00 |
July | 6182.28 | 17-JUL-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.82 | 0.00 |
August | 6047.94 | 07-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.11 | 0.00 |
September | 5350.70 | 05-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.64 |
October | 2279.21 | 27-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.25 |
November | 1807.97 | 02-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.85 |
December | 2444.04 | 30-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 962.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1807.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6182.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.50 | 2101.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3453.30 | 27-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.93 |
February | 3281.31 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.92 |
March | 3563.48 | 03-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.98 |
April | 3609.34 | 27-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.65 |
May | 3284.48 | 19-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.75 | 0.00 |
June | 4545.12 | 29-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.07 | 0.00 |
July | 6546.30 | 17-JUL-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.15 | 0.00 |
August | 5921.05 | 07-AUG-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.42 | 0.00 |
September | 5782.22 | 05-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 |
October | 2735.54 | 20-OCT-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.37 |
November | 2803.93 | 02-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.15 |
December | 2609.83 | 29-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 381.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2609.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6546.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.07 | 424.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5932.60 | 13-JAN-16:20 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7888.15 | 28-FEB-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8031.46 | 01-MAR-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12069.57 | 25-APR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30474.24 | 30-MAY-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30566.44 | 29-JUN-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32401.65 | 17-JUL-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32159.65 | 07-AUG-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31485.42 | 05-SEP-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13076.85 | 19-OCT-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8817.93 | 03-NOV-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6637.01 | 07-DEC-15:50 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5932.60 | 0.00 | 2463.50 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32401.65 | 6035.01 | 5543.17 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5861.94 | 13-JAN-16:50 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7162.54 | 28-FEB-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7165.74 | 02-MAR-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13161.30 | 25-APR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16665.51 | 19-MAY-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33022.35 | 21-JUN-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34894.66 | 17-JUL-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34637.17 | 07-AUG-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35072.40 | 05-SEP-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12714.21 | 18-OCT-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7271.86 | 03-NOV-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6362.49 | 06-DEC-16:20 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5861.94 | 0.00 | 2463.50 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35072.40 | 6035.01 | 5543.17 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 936.52 | 14-JAN-17:03 | 200.88 | 194.77 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.40 |
February | 1355.04 | 27-FEB-16:10 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.90 |
March | 1401.66 | 29-MAR-16:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.40 |
April | 3338.42 | 07-APR-14:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.82 |
May | 5453.13 | 19-MAY-16:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 99.40 | 0.00 |
June | 6895.73 | 21-JUN-06:03 | 1071.35 | 960.53 | 2677.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.15 |
July | 11824.50 | 16-JUL-18:41 | 0.00 | 280.18 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 121.88 | 0.00 |
August | 11561.01 | 06-AUG-16:11 | 468.72 | 280.18 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 350.42 | 0.00 |
September | 10432.42 | 04-SEP-16:31 | 468.72 | 280.18 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 129.06 | 0.00 |
October | 2694.96 | 19-OCT-14:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.91 |
November | 1298.93 | 03-NOV-16:00 | 1272.23 | 839.89 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.67 |
December | 1030.61 | 06-DEC-16:00 | 1272.23 | 942.52 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 936.52 | 0.00 | 194.77 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11824.50 | 1272.23 | 960.53 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 350.42 | 306.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 989.96 | 14-JAN-17:03 | 127.17 | 123.31 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.35 |
February | 1616.42 | 27-FEB-10:40 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.68 |
March | 3425.84 | 23-MAR-10:20 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.27 |
April | 6095.75 | 25-APR-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.74 |
May | 7659.16 | 19-MAY-08:50 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.35 |
June | 13847.08 | 11-JUN-09:52 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.16 |
July | 14467.88 | 16-JUL-09:22 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.97 |
August | 14697.38 | 06-AUG-09:32 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 29.77 | 0.00 |
September | 11570.98 | 04-SEP-08:32 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.21 |
October | 4373.88 | 18-OCT-09:50 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.09 |
November | 1599.02 | 03-NOV-10:00 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.88 |
December | 1132.90 | 06-DEC-10:40 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 989.96 | 127.17 | 123.31 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14697.38 | 827.22 | 456.08 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 29.77 | 298.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4791.04 | 19-JAN-14:00 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.16 |
February | 12636.32 | 26-FEB-12:53 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 609.00 |
March | 10642.20 | 01-MAR-14:10 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.28 |
April | 10851.65 | 25-APR-13:40 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.61 |
May | 10637.41 | 19-MAY-13:40 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 47.58 | 0.00 |
June | 12698.97 | 11-JUN-13:13 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.77 |
July | 18532.83 | 16-JUL-14:02 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 111.35 | 0.00 |
August | 19382.29 | 06-AUG-13:32 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 267.17 | 0.00 |
September | 20271.65 | 03-SEP-13:02 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 337.47 | 0.00 |
October | 18094.37 | 15-OCT-13:32 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.77 |
November | 10946.66 | 03-NOV-13:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.10 |
December | 5255.22 | 12-DEC-14:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4791.04 | 267.84 | 160.10 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20271.65 | 1306.65 | 720.41 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 337.47 | 609.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1539.43 | 13-JAN-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.98 |
February | 3972.03 | 28-FEB-16:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.27 |
March | 4932.64 | 28-MAR-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.39 |
April | 9348.26 | 22-APR-17:06 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.06 |
May | 15561.17 | 13-MAY-18:22 | 0.00 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.02 |
June | 16037.73 | 24-JUN-17:42 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.20 |
July | 17794.70 | 09-JUL-16:31 | 339.11 | 202.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 |
August | 16512.84 | 06-AUG-16:11 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 202.42 | 0.00 |
September | 16654.33 | 04-SEP-16:31 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 67.34 | 0.00 |
October | 6575.19 | 18-OCT-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 3.59 | 0.00 |
November | 3020.58 | 03-NOV-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.11 |
December | 1680.76 | 06-DEC-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1539.43 | 0.00 | 126.69 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17794.70 | 805.38 | 456.05 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.42 | 243.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 924.27 | 14-JAN-17:03 | 200.88 | 194.77 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.99 |
February | 1170.84 | 27-FEB-16:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.56 |
March | 1208.02 | 29-MAR-16:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.21 |
April | 1454.11 | 07-APR-14:50 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 |
May | 3217.91 | 19-MAY-16:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 53.58 | 0.00 |
June | 4654.01 | 29-JUN-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 79.47 | 0.00 |
July | 8277.90 | 16-JUL-18:31 | 0.00 | 400.26 | 5019.64 | 0.00 | 0.00 | 0.00 | 0.00 | 65.91 | 0.00 |
August | 5545.07 | 09-AUG-15:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 39.43 | 0.00 |
September | 6286.78 | 04-SEP-13:02 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 137.91 | 0.00 |
October | 2398.96 | 19-OCT-14:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.01 |
November | 1335.29 | 08-NOV-14:10 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.87 |
December | 1047.77 | 06-DEC-15:50 | 1272.23 | 884.26 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 924.27 | 0.00 | 194.77 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8277.90 | 1306.65 | 884.26 | 5019.64 | 0.00 | 0.00 | 0.00 | 0.00 | 137.91 | 169.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 892.95 | 20-JAN-10:05 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.54 |
February | 1302.11 | 27-FEB-10:40 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.87 |
March | 1996.54 | 23-MAR-10:30 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.03 |
April | 3751.49 | 25-APR-09:40 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.04 |
May | 4995.10 | 19-MAY-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.70 |
June | 8354.97 | 25-JUN-08:52 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.16 |
July | 12296.42 | 16-JUL-09:51 | 339.13 | 202.72 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 |
August | 11443.16 | 06-AUG-09:32 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 24.55 | 0.00 |
September | 11660.87 | 04-SEP-08:22 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.23 |
October | 3790.39 | 18-OCT-10:00 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.66 |
November | 1667.41 | 03-NOV-09:15 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.48 |
December | 995.69 | 07-DEC-10:50 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 892.95 | 254.35 | 152.04 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12296.42 | 1654.44 | 912.16 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 24.55 | 176.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1770.78 | 14-JAN-12:40 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.83 |
February | 8171.26 | 26-FEB-12:53 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.90 |
March | 4379.47 | 01-MAR-14:50 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2741.43 |
April | 5217.60 | 06-APR-14:30 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.50 |
May | 8656.56 | 19-MAY-16:10 | 401.76 | 400.23 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 3848.84 | 0.00 |
June | 12548.11 | 30-JUN-16:10 | 401.76 | 400.23 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 7341.77 | 0.00 |
July | 15216.26 | 16-JUL-13:12 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 26.62 | 0.00 |
August | 14947.47 | 06-AUG-13:32 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 153.35 | 0.00 |
September | 15711.29 | 04-SEP-11:42 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 94.54 | 0.00 |
October | 14674.54 | 15-OCT-14:12 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.41 |
November | 7071.22 | 03-NOV-12:06 | 10177.86 | 5763.29 | 12047.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1968.01 |
December | 2683.43 | 02-DEC-13:30 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1770.78 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15711.29 | 10177.86 | 5763.29 | 12047.06 | 0.00 | 0.00 | 0.00 | 0.00 | 7341.77 | 2741.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1182.65 | 13-JAN-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.31 |
February | 2909.57 | 28-FEB-16:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.76 |
March | 3031.43 | 28-MAR-17:30 | 84.78 | 152.01 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.56 |
April | 5264.86 | 25-APR-17:40 | 84.78 | 152.01 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.05 |
May | 12493.73 | 28-MAY-18:31 | 0.00 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.48 |
June | 10544.52 | 24-JUN-17:42 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 |
July | 14363.56 | 16-JUL-18:31 | 0.00 | 253.38 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 22.01 | 0.00 |
August | 12665.59 | 05-AUG-18:22 | 0.00 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 78.38 | 0.00 |
September | 13214.50 | 04-SEP-17:01 | 0.00 | 253.38 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 31.90 | 0.00 |
October | 5495.04 | 18-OCT-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 2.19 | 0.00 |
November | 2697.76 | 03-NOV-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.37 |
December | 1342.99 | 06-DEC-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1182.65 | 0.00 | 152.01 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14363.56 | 805.38 | 456.05 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 78.38 | 161.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 951.07 | 13-JAN-16:40 | 1272.23 | 1133.42 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.47 |
February | 1367.65 | 27-FEB-13:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.37 |
March | 1398.14 | 29-MAR-16:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.33 |
April | 3305.44 | 07-APR-14:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.04 |
May | 4904.93 | 19-MAY-16:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 83.32 | 0.00 |
June | 8133.91 | 21-JUN-06:03 | 1071.35 | 960.53 | 2677.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.91 |
July | 10969.62 | 16-JUL-18:32 | 0.00 | 400.26 | 5019.64 | 0.00 | 0.00 | 0.00 | 0.00 | 101.74 | 0.00 |
August | 9378.26 | 06-AUG-16:51 | 468.72 | 280.18 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 303.11 | 0.00 |
September | 10035.88 | 04-SEP-13:02 | 401.76 | 240.15 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 193.15 | 0.00 |
October | 3000.19 | 19-OCT-14:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.63 |
November | 1417.76 | 03-NOV-13:30 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.57 |
December | 1063.79 | 06-DEC-16:00 | 1272.23 | 942.53 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 951.07 | 0.00 | 240.15 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10969.62 | 1306.65 | 1133.42 | 5019.64 | 0.00 | 0.00 | 0.00 | 0.00 | 303.11 | 262.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1127.95 | 20-JAN-10:00 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.61 |
February | 2316.61 | 28-FEB-09:55 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.48 |
March | 4045.27 | 23-MAR-10:10 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.08 |
April | 6608.24 | 25-APR-09:00 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.69 |
May | 7814.32 | 19-MAY-08:50 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.45 |
June | 12021.04 | 25-JUN-08:42 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.91 |
July | 15592.15 | 02-JUL-08:31 | 339.13 | 202.72 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.01 |
August | 14390.83 | 06-AUG-08:52 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.90 |
September | 14437.46 | 04-SEP-08:22 | 254.35 | 152.04 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.06 |
October | 4832.85 | 18-OCT-10:10 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.71 |
November | 2223.22 | 03-NOV-10:10 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.59 |
December | 1212.00 | 20-DEC-10:00 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1127.95 | 211.95 | 126.70 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.90 | |
Maximum of Months | 15592.15 | 1610.86 | 912.16 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5610.23 | 19-JAN-13:40 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.64 |
February | 16939.03 | 26-FEB-12:53 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.23 |
March | 11288.69 | 01-MAR-13:50 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.14 |
April | 10409.33 | 25-APR-13:20 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.61 |
May | 10012.73 | 19-MAY-13:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 35.87 | 0.00 |
June | 9941.52 | 30-JUN-13:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 18.86 | 0.00 |
July | 18047.25 | 16-JUL-13:12 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 32.84 | 0.00 |
August | 17594.76 | 06-AUG-13:32 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 226.48 | 0.00 |
September | 18299.68 | 03-SEP-13:22 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 254.04 | 0.00 |
October | 17254.32 | 15-OCT-13:32 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.92 |
November | 11467.82 | 03-NOV-13:20 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.14 |
December | 6044.91 | 12-DEC-14:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5610.23 | 267.84 | 160.10 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18299.68 | 1306.65 | 720.41 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 254.04 | 514.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1492.68 | 13-JAN-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.12 |
February | 4179.20 | 28-FEB-16:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.99 |
March | 4939.47 | 28-MAR-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.72 |
April | 8514.65 | 22-APR-17:06 | 211.94 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.53 |
May | 12770.33 | 28-MAY-17:22 | 0.00 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.06 |
June | 14663.32 | 24-JUN-17:42 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.08 |
July | 17099.66 | 16-JUL-17:12 | 0.00 | 253.38 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 50.86 | 0.00 |
August | 14966.10 | 06-AUG-16:11 | 296.72 | 177.36 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 172.75 | 0.00 |
September | 15433.59 | 04-SEP-16:21 | 423.88 | 253.38 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 53.57 | 0.00 |
October | 6477.67 | 18-OCT-16:00 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 3.21 | 0.00 |
November | 3315.80 | 03-NOV-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.51 |
December | 1631.09 | 06-DEC-15:50 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1492.68 | 0.00 | 126.69 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17099.66 | 805.38 | 456.05 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 172.75 | 278.06 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.202509E+12 | 262106.25 | 09-JAN-08:09 | 0.892188E+11 | 155043.69 | 10-JAN-21:00 |
February | 0.141696E+12 | 225688.28 | 06-FEB-07:10 | 0.535900E+11 | 133058.98 | 01-FEB-07:30 |
March | 0.136703E+12 | 225599.25 | 06-MAR-07:10 | 0.387075E+11 | 112258.09 | 04-MAR-07:19 |
April | 0.107080E+12 | 104742.77 | 28-APR-07:10 | 0.180054E+11 | 59954.99 | 29-APR-06:19 |
May | 0.114523E+12 | 144859.17 | 08-MAY-06:10 | 0.148566E+11 | 49259.07 | 08-MAY-06:30 |
June | 0.127776E+12 | 154361.28 | 29-JUN-15:09 | 0.957802E+10 | 20305.87 | 16-JUN-07:10 |
July | 0.145243E+12 | 181870.99 | 17-JUL-15:30 | 0.892710E+10 | 9235.81 | 05-JUL-11:09 |
August | 0.145086E+12 | 166523.20 | 07-AUG-15:39 | 0.932918E+10 | 9361.95 | 18-AUG-06:19 |
September | 0.116581E+12 | 165020.27 | 07-SEP-14:00 | 0.992256E+10 | 27994.48 | 19-SEP-06:40 |
October | 0.110946E+12 | 151851.26 | 10-OCT-06:10 | 0.150401E+11 | 61598.68 | 10-OCT-06:30 |
November | 0.128178E+12 | 217945.11 | 27-NOV-07:10 | 0.298631E+11 | 90608.49 | 27-NOV-08:09 |
December | 0.166860E+12 | 227410.79 | 26-DEC-07:10 | 0.626318E+11 | 145272.12 | 29-DEC-07:00 |
Annual Sum or Average | 0.164318E+13 | 0.359670E+12 | ||||
Minimum of Months | 0.107080E+12 | 104742.77 | 0.892710E+10 | 9235.81 | ||
Maximum of Months | 0.202509E+12 | 262106.25 | 0.892188E+11 | 155043.69 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.242029E+11 | 0.814102E+10 | 0.641572E+11 | 0.109166E+10 | 0.620528E+10 | 1312252.65 | 0.987091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.214473E+11 | 0.662444E+10 | 0.580684E+11 | 0.987370E+09 | 0.489956E+10 | 1186778.30 | 0.495437E+11 | 0.123763E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251980E+11 | 0.631374E+10 | 0.666107E+11 | 0.114321E+10 | 0.555762E+10 | 1343621.24 | 0.318785E+11 | 311734.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223380E+11 | 0.507908E+10 | 0.619407E+11 | 0.105056E+10 | 0.539349E+10 | 1267813.82 | 0.986908E+10 | 0.140790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.239600E+11 | 0.437197E+10 | 0.653840E+11 | 0.111683E+10 | 0.710500E+10 | 1327936.95 | 0.691935E+10 | 0.566454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.237543E+11 | 0.382137E+10 | 0.641577E+11 | 0.109951E+10 | 0.133017E+11 | 1296568.36 | 0.791423E+09 | 0.208490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.223211E+11 | 0.411269E+10 | 0.631525E+11 | 0.106756E+10 | 0.175150E+11 | 1299182.41 | 0.144406E+09 | 0.369283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.248888E+11 | 0.483657E+10 | 0.666107E+11 | 0.114303E+10 | 0.164384E+11 | 1343621.24 | 0.550220E+09 | 0.306167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.224361E+11 | 0.565927E+10 | 0.619118E+11 | 0.105020E+10 | 0.968716E+10 | 1267813.82 | 0.196694E+10 | 0.138679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.235402E+11 | 0.690727E+10 | 0.641717E+11 | 0.109115E+10 | 0.613028E+10 | 1312252.65 | 0.637836E+10 | 0.272604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.236775E+11 | 0.761660E+10 | 0.627379E+11 | 0.107138E+10 | 0.506661E+10 | 1278270.02 | 0.278844E+11 | 0.122635E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.234478E+11 | 0.840444E+10 | 0.631380E+11 | 0.106837E+10 | 0.555941E+10 | 1299182.41 | 0.652407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281212E+12 | 0.718885E+11 | 0.762041E+12 | 0.129808E+11 | 0.102859E+12 | 15535293.87 | 0.299876E+12 | 0.112307E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.214473E+11 | 0.382137E+10 | 0.580684E+11 | 0.987370E+09 | 0.489956E+10 | 1186778.30 | 0.144406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.251980E+11 | 0.840444E+10 | 0.666107E+11 | 0.114321E+10 | 0.175150E+11 | 1343621.24 | 0.987091E+11 | 0.369283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.789288E+11 | 0.00 | 0.102900E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.441775E+11 | 0.00 | 0.941254E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.279314E+11 | 0.00 | 0.107761E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.827903E+10 | 0.00 | 0.972639E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.492383E+10 | 0.00 | 0.993272E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.192937E+09 | 0.00 | 0.938508E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.892710E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 3595643.05 | 0.00 | 0.932559E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.118656E+10 | 0.00 | 0.873600E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.577267E+10 | 0.00 | 0.926745E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.204662E+11 | 0.00 | 0.939688E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.527978E+11 | 0.00 | 0.983396E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.244660E+12 | 0.00 | 0.115010E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.873600E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.789288E+11 | 0.00 | 0.107761E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28079.40 | 02-JAN-08:09 | 5557.43 | 01-JAN-06:10 | 47562.27 | 02-JAN-08:09 | 928.21 | 02-JAN-08:20 | 8181.35 | 09-JAN-07:10 | 0.73 | 02-JAN-07:10 | 213664.15 | 09-JAN-07:10 |
February | 26221.23 | 02-FEB-08:09 | 5557.43 | 01-FEB-06:10 | 47562.27 | 01-FEB-08:09 | 925.53 | 02-FEB-08:20 | 6286.21 | 06-FEB-07:10 | 0.73 | 01-FEB-07:10 | 182374.91 | 06-FEB-07:10 |
March | 27629.75 | 17-MAR-07:10 | 5557.43 | 01-MAR-06:10 | 47562.27 | 01-MAR-08:09 | 927.56 | 17-MAR-07:19 | 6819.43 | 06-MAR-07:10 | 0.73 | 01-MAR-07:10 | 187908.21 | 06-MAR-07:10 |
April | 25574.24 | 14-APR-07:10 | 5557.43 | 01-APR-05:10 | 47562.27 | 03-APR-07:10 | 924.60 | 14-APR-07:19 | 12438.88 | 25-APR-15:00 | 0.73 | 03-APR-07:10 | 72560.46 | 29-APR-05:10 |
May | 24498.62 | 03-MAY-07:10 | 5557.43 | 01-MAY-05:10 | 47562.27 | 01-MAY-07:10 | 923.06 | 03-MAY-07:19 | 22157.58 | 19-MAY-15:30 | 0.73 | 01-MAY-06:10 | 110353.34 | 08-MAY-06:10 |
June | 23688.37 | 01-JUN-07:10 | 5557.43 | 01-JUN-20:10 | 47562.27 | 01-JUN-07:10 | 921.90 | 01-JUN-07:19 | 29090.60 | 29-JUN-15:09 | 0.73 | 16-JUN-07:10 | 20499.37 | 16-JUN-06:10 |
July | 23688.37 | 03-JUL-07:10 | 5557.43 | 01-JUL-20:30 | 47562.27 | 03-JUL-07:10 | 921.90 | 03-JUL-07:19 | 33242.96 | 25-JUL-15:50 | 0.73 | 16-JUL-15:00 | 12270.84 | 05-JUL-06:19 |
August | 23860.52 | 17-AUG-07:10 | 5557.43 | 01-AUG-19:00 | 47562.27 | 01-AUG-07:10 | 922.14 | 17-AUG-07:19 | 31956.97 | 10-AUG-15:39 | 0.73 | 06-AUG-16:10 | 22010.81 | 18-AUG-06:10 |
September | 25410.68 | 11-SEP-07:10 | 5557.43 | 01-SEP-05:10 | 47562.27 | 01-SEP-07:10 | 924.37 | 11-SEP-07:19 | 30836.66 | 07-SEP-14:00 | 0.73 | 04-SEP-15:50 | 51510.01 | 19-SEP-06:10 |
October | 28079.40 | 30-OCT-07:10 | 5557.43 | 01-OCT-05:10 | 47562.27 | 02-OCT-07:10 | 928.21 | 30-OCT-07:19 | 14916.24 | 18-OCT-15:00 | 0.73 | 04-OCT-07:10 | 110469.89 | 10-OCT-06:10 |
November | 28079.40 | 01-NOV-07:10 | 5557.43 | 01-NOV-05:10 | 47562.27 | 01-NOV-07:10 | 928.21 | 01-NOV-07:19 | 7068.56 | 03-NOV-15:30 | 0.73 | 02-NOV-07:10 | 174588.83 | 27-NOV-07:10 |
December | 28079.40 | 01-DEC-16:40 | 5557.43 | 01-DEC-06:10 | 47562.27 | 01-DEC-08:09 | 928.21 | 13-DEC-08:20 | 6490.01 | 26-DEC-07:10 | 0.73 | 01-DEC-08:09 | 183893.62 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 23688.37 | 5557.43 | 47562.27 | 921.90 | 6286.21 | 0.73 | 12270.84 | |||||||
Maximum of Months | 28079.40 | 5557.43 | 47562.27 | 928.21 | 33242.96 | 0.73 | 213664.15 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8652.10 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 79.08 | 14-MAR-13:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18915.66 | 06-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 42646.20 | 19-MAY-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 57032.98 | 29-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81395.66 | 17-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 66536.38 | 07-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 67288.61 | 07-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30581.30 | 18-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4194.55 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81395.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 262106.25 | 09-JAN-08:09 | 28079.40 | 47562.27 | 5557.43 | 901.53 | 6090.25 | 0.73 | 173914.64 | 0.00 | 0.00 |
February | 225688.28 | 06-FEB-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 6286.21 | 0.73 | 182374.91 | 0.00 | 0.00 |
March | 225599.25 | 06-MAR-07:10 | 8761.56 | 21853.28 | 0.00 | 256.05 | 6819.43 | 0.73 | 187908.21 | 0.00 | 0.00 |
April | 104742.77 | 28-APR-07:10 | 23688.37 | 47562.27 | 0.00 | 899.47 | 3990.14 | 0.73 | 28601.78 | 0.00 | 0.00 |
May | 144859.17 | 08-MAY-06:10 | 8088.17 | 21853.28 | 0.00 | 255.90 | 4307.76 | 0.73 | 110353.34 | 0.00 | 0.00 |
June | 154361.28 | 29-JUN-15:09 | 23688.37 | 43769.98 | 0.00 | 920.43 | 29090.60 | 0.73 | 0.00 | 56891.17 | 0.00 |
July | 181870.99 | 17-JUL-15:30 | 23688.37 | 43769.98 | 0.00 | 920.43 | 32899.56 | 0.73 | 0.00 | 80591.92 | 0.00 |
August | 166523.20 | 07-AUG-15:39 | 23688.37 | 43769.98 | 0.00 | 920.43 | 31831.74 | 0.73 | 0.00 | 66311.95 | 0.00 |
September | 165020.27 | 07-SEP-14:00 | 23688.37 | 42286.04 | 0.00 | 919.86 | 30836.66 | 0.73 | 0.00 | 67288.61 | 0.00 |
October | 151851.26 | 10-OCT-06:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 4354.21 | 0.73 | 110469.89 | 0.00 | 0.00 |
November | 217945.11 | 27-NOV-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 6329.12 | 0.73 | 174588.83 | 0.00 | 0.00 |
December | 227410.79 | 26-DEC-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 6490.01 | 0.73 | 183893.62 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 104742.77 | 8088.17 | 21853.28 | 0.00 | 255.90 | 3990.14 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 262106.25 | 28079.40 | 47562.27 | 5557.43 | 920.43 | 32899.56 | 0.73 | 187908.21 | 80591.92 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 153887.69 | 10-JAN-21:00 | 0.00 | 11364.45 | 30-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 124826.44 | 01-FEB-07:30 | 0.00 | 11463.44 | 17-FEB-12:20 | 0.00 |
March | 0.00 | 0.00 | 104287.17 | 04-MAR-07:19 | 0.00 | 11396.58 | 02-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 52645.37 | 29-APR-06:10 | 0.00 | 10674.85 | 04-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 41131.96 | 08-MAY-06:19 | 0.00 | 9512.59 | 02-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 13107.74 | 16-JUN-06:00 | 0.00 | 9371.87 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9235.81 | 05-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 1493.46 | 18-AUG-06:10 | 0.00 | 9171.17 | 02-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 20163.90 | 19-SEP-06:19 | 0.00 | 9206.28 | 26-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 53477.94 | 10-OCT-06:30 | 0.00 | 9335.52 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 81935.89 | 27-NOV-08:09 | 0.00 | 9479.45 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 137080.29 | 29-DEC-07:00 | 0.00 | 10348.87 | 26-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9171.17 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 153887.69 | 0.00 | 11463.44 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.19 | 0.00 | 26.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 26.19 | 0.00 | 26.19 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.19 | 0.00 | 26.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.29 | 0.33 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
February | 0.17 | 19.40 | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.44 | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
Annual Sum or Average | 0.67 | 19.35 | 0.67 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.44 | 0.33 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 18.71 | 3.33 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
February | 0.33 | 17.99 | 0.17 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
March | 0.83 | 18.34 | 0.50 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 17.61 | 0.33 | 18.06 | 0.00 | 18.06 | 0.00 | 18.06 |
December | 0.83 | 18.16 | 0.50 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
Annual Sum or Average | 7.50 | 18.45 | 4.83 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.67 | 18.71 | 3.33 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 83.50 | 16.39 | 43.50 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
February | 27.33 | 16.44 | 12.33 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
March | 14.67 | 16.03 | 5.83 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
April | 0.17 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
May | 0.83 | 17.09 | 0.17 | 17.42 | 0.00 | 17.42 | 0.00 | 17.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.46 | 1.17 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.56 | 1.17 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.49 | 2.00 | 27.50 |
October | 0.50 | 17.70 | 0.17 | 18.12 | 0.00 | 18.12 | 0.00 | 18.12 |
November | 16.67 | 15.83 | 7.33 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 |
December | 48.83 | 15.94 | 22.83 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 |
Annual Sum or Average | 192.50 | 16.21 | 92.17 | 16.68 | 6.50 | 16.93 | 4.33 | 17.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.50 | 17.70 | 43.50 | 18.12 | 2.33 | 27.56 | 2.00 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.50 | 14.54 | 10.50 | 14.64 | 0.00 | 14.64 | 0.00 | 14.64 |
February | 17.50 | 14.93 | 2.50 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
March | 10.00 | 14.88 | 1.33 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
April | 0.33 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
May | 0.83 | 16.26 | 0.00 | 16.26 | 0.00 | 16.26 | 0.00 | 16.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.81 | 4.50 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 28.04 | 9.50 | 28.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.39 | 2.83 | 28.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.98 | 4.50 | 27.99 |
October | 0.33 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
November | 12.00 | 14.93 | 3.17 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
December | 33.50 | 14.74 | 7.67 | 14.70 | 0.00 | 14.70 | 0.00 | 14.70 |
Annual Sum or Average | 118.00 | 14.75 | 25.17 | 14.77 | 22.67 | 16.58 | 21.33 | 17.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.64 | 0.00 | 14.64 |
Maximum of Months | 43.50 | 17.01 | 10.50 | 17.01 | 10.17 | 28.39 | 9.50 | 28.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 37.17 | 14.93 | 9.67 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
February | 13.50 | 15.09 | 1.00 | 15.08 | 0.83 | 15.77 | 0.83 | 16.39 |
March | 8.67 | 14.90 | 1.17 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 |
April | 0.17 | 16.89 | 0.00 | 16.89 | 0.33 | 23.82 | 0.33 | 25.20 |
May | 0.67 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.58 | 2.17 | 27.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.90 | 6.67 | 27.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.05 | 3.50 | 28.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.22 | 5.50 | 28.26 |
October | 0.17 | 16.54 | 0.00 | 16.54 | 1.67 | 26.93 | 1.67 | 27.42 |
November | 7.17 | 15.17 | 1.33 | 15.28 | 0.00 | 15.28 | 0.00 | 15.28 |
December | 26.67 | 14.81 | 5.50 | 14.77 | 0.00 | 14.77 | 0.00 | 14.77 |
Annual Sum or Average | 94.17 | 14.95 | 18.67 | 15.06 | 23.50 | 17.28 | 20.67 | 18.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.77 | 0.00 | 14.77 |
Maximum of Months | 37.17 | 16.89 | 9.67 | 16.89 | 7.67 | 28.22 | 6.67 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.17 | 14.44 | 10.17 | 14.48 | 0.00 | 14.48 | 0.00 | 14.48 |
February | 17.50 | 14.89 | 3.17 | 14.83 | 0.00 | 14.83 | 0.00 | 14.83 |
March | 9.67 | 14.77 | 1.67 | 14.80 | 0.00 | 14.80 | 0.00 | 14.80 |
April | 0.33 | 17.05 | 0.00 | 17.05 | 0.83 | 24.80 | 0.50 | 25.74 |
May | 0.83 | 16.32 | 0.00 | 16.32 | 3.33 | 25.59 | 1.17 | 26.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.26 | 1.67 | 28.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.55 | 4.33 | 28.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.36 | 1.83 | 28.41 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.29 | 2.50 | 28.36 |
October | 0.33 | 16.83 | 0.00 | 16.83 | 0.17 | 20.31 | 0.17 | 22.05 |
November | 11.00 | 14.77 | 3.00 | 14.75 | 0.00 | 14.75 | 0.00 | 14.75 |
December | 34.83 | 14.70 | 9.33 | 14.64 | 0.00 | 14.64 | 0.00 | 14.64 |
Annual Sum or Average | 116.67 | 14.67 | 27.33 | 14.65 | 25.50 | 16.71 | 12.17 | 17.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.48 | 0.00 | 14.48 |
Maximum of Months | 42.17 | 17.05 | 10.17 | 17.05 | 9.00 | 28.55 | 4.33 | 28.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 63.17 | 17.98 | 46.67 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
February | 12.00 | 17.87 | 8.00 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
March | 6.17 | 17.59 | 3.50 | 18.21 | 0.00 | 18.21 | 0.00 | 18.21 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.83 | 18.70 | 1.17 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
December | 12.67 | 17.55 | 9.00 | 17.92 | 0.00 | 17.92 | 0.00 | 17.92 |
Annual Sum or Average | 95.83 | 17.90 | 68.33 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.17 | 18.70 | 46.67 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.17 | 15.15 | 4.00 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
February | 4.83 | 15.69 | 0.67 | 15.73 | 0.00 | 15.73 | 0.00 | 15.73 |
March | 2.17 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.66 | 1.33 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.71 | 7.50 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.90 | 2.67 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.65 | 4.50 | 27.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 16.35 | 0.00 | 16.35 | 0.00 | 16.35 | 0.00 | 16.35 |
December | 5.83 | 15.26 | 2.00 | 15.23 | 0.00 | 15.23 | 0.00 | 15.23 |
Annual Sum or Average | 31.50 | 15.27 | 6.67 | 15.33 | 16.83 | 19.12 | 16.00 | 21.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 18.17 | 16.35 | 4.00 | 16.35 | 8.00 | 27.90 | 7.50 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 140.83 | 15.65 | 130.00 | 15.67 | 0.00 | 15.67 | 0.00 | 15.67 |
February | 70.67 | 16.28 | 69.67 | 16.28 | 0.83 | 16.34 | 0.83 | 16.41 |
March | 57.33 | 17.04 | 56.33 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
April | 35.17 | 18.04 | 35.17 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 |
May | 29.67 | 18.30 | 29.67 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
June | 4.67 | 19.64 | 4.67 | 19.64 | 0.00 | 19.64 | 0.00 | 19.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 25.76 | 12.67 | 25.74 |
August | 0.67 | 20.18 | 0.67 | 20.18 | 11.83 | 25.06 | 11.33 | 25.28 |
September | 11.00 | 19.36 | 11.00 | 19.36 | 6.83 | 21.39 | 5.67 | 22.48 |
October | 21.17 | 18.59 | 21.17 | 18.59 | 2.50 | 19.10 | 2.50 | 19.56 |
November | 39.50 | 17.04 | 39.17 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
December | 84.83 | 16.24 | 81.67 | 16.26 | 0.00 | 16.26 | 0.00 | 16.26 |
Annual Sum or Average | 495.50 | 16.69 | 479.17 | 16.72 | 35.00 | 17.05 | 33.00 | 17.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 0.00 | 15.67 |
Maximum of Months | 140.83 | 20.18 | 130.00 | 20.18 | 13.00 | 25.76 | 12.67 | 25.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.83 | 15.00 | 4.17 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 |
February | 4.83 | 15.54 | 1.00 | 15.44 | 0.00 | 15.44 | 0.00 | 15.44 |
March | 2.17 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.75 | 0.17 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.72 | 1.00 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.09 | 2.50 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.17 | 1.00 | 28.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.03 | 2.00 | 28.07 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.40 | 0.17 | 27.40 |
November | 0.50 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 |
December | 6.17 | 15.11 | 2.33 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
Annual Sum or Average | 31.50 | 15.13 | 7.50 | 15.10 | 16.17 | 18.88 | 6.83 | 19.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.83 | 16.33 | 4.17 | 16.33 | 6.50 | 28.17 | 2.50 | 28.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 44.00 | 16.71 | 23.67 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
February | 10.67 | 15.97 | 4.33 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
March | 5.50 | 16.69 | 2.17 | 17.42 | 0.00 | 17.42 | 0.00 | 17.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.42 | 0.00 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.35 | 0.50 | 27.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.38 | 1.33 | 27.38 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5.17 | 16.61 | 1.67 | 17.35 | 0.00 | 17.35 | 0.00 | 17.35 |
December | 12.67 | 16.59 | 7.17 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
Annual Sum or Average | 78.00 | 16.58 | 39.00 | 17.06 | 2.83 | 17.31 | 1.83 | 17.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.00 | 16.71 | 23.67 | 17.42 | 1.50 | 27.42 | 1.33 | 27.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.33 | 14.79 | 4.00 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 |
February | 7.33 | 15.29 | 0.83 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
March | 4.00 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.89 | 4.67 | 27.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.05 | 8.67 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.18 | 3.17 | 28.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.81 | 5.33 | 27.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.17 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 |
December | 8.00 | 14.89 | 2.50 | 14.80 | 0.00 | 14.80 | 0.00 | 14.80 |
Annual Sum or Average | 44.83 | 14.92 | 7.33 | 14.89 | 22.50 | 18.83 | 21.83 | 20.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.33 | 15.29 | 4.00 | 15.25 | 9.00 | 28.18 | 8.67 | 28.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.83 | 15.05 | 3.00 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
February | 3.50 | 16.08 | 0.83 | 16.20 | 1.17 | 18.68 | 1.17 | 20.29 |
March | 2.33 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.38 | 0.67 | 27.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.45 | 1.67 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.75 | 6.33 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.97 | 3.33 | 27.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.13 | 5.83 | 28.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.95 | 2.50 | 27.95 |
November | 1.50 | 15.19 | 0.00 | 15.19 | 0.33 | 17.40 | 0.33 | 18.92 |
December | 6.17 | 14.99 | 1.83 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
Annual Sum or Average | 31.33 | 15.16 | 5.67 | 15.19 | 24.17 | 20.20 | 22.00 | 22.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.90 | 0.00 | 14.90 |
Maximum of Months | 17.83 | 16.08 | 3.00 | 16.20 | 7.17 | 28.13 | 6.33 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.67 | 14.79 | 4.67 | 14.78 | 0.00 | 14.78 | 0.00 | 14.78 |
February | 7.50 | 15.29 | 1.17 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
March | 4.17 | 14.89 | 0.17 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.84 | 0.33 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.95 | 1.33 | 27.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.11 | 1.33 | 28.14 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.43 | 4.00 | 28.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.16 | 2.00 | 28.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.26 | 2.33 | 28.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.44 | 0.33 | 27.44 |
November | 3.00 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 |
December | 8.50 | 14.86 | 3.00 | 14.76 | 0.00 | 14.76 | 0.00 | 14.76 |
Annual Sum or Average | 45.83 | 14.91 | 9.00 | 14.87 | 23.83 | 18.91 | 11.67 | 20.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.76 | 0.00 | 14.76 |
Maximum of Months | 22.67 | 15.29 | 4.67 | 15.22 | 8.33 | 28.43 | 4.00 | 28.42 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.19 | 129.17 | 21.90 | 129.17 | 21.71 |
February | 452.83 | 22.93 | 30.00 | 22.79 | 30.00 | 22.67 |
March | 511.00 | 23.50 | 6.33 | 23.47 | 6.33 | 23.44 |
April | 409.83 | 23.87 | 0.00 | 23.87 | 0.00 | 23.87 |
May | 230.17 | 23.88 | 68.33 | 24.29 | 0.00 | 24.29 |
June | 9.33 | 23.94 | 211.83 | 24.63 | 0.00 | 24.63 |
July | 1.17 | 26.75 | 351.00 | 24.58 | 1.17 | 24.59 |
August | 0.00 | 0.00 | 237.33 | 24.80 | 0.00 | 24.80 |
September | 37.33 | 24.01 | 174.50 | 24.69 | 0.00 | 24.69 |
October | 243.00 | 23.98 | 24.00 | 24.14 | 0.00 | 24.14 |
November | 435.50 | 23.67 | 1.17 | 23.67 | 1.17 | 23.66 |
December | 497.00 | 22.90 | 43.17 | 22.73 | 43.17 | 22.58 |
Annual Sum or Average | 3329.17 | 23.27 | 1276.83 | 23.51 | 211.00 | 23.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.90 | 0.00 | 21.71 |
Maximum of Months | 511.00 | 26.75 | 351.00 | 24.80 | 129.17 | 24.80 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.85 | 353.33 | 20.72 | 353.33 | 20.67 |
February | 454.00 | 21.48 | 185.17 | 21.25 | 185.17 | 21.12 |
March | 514.00 | 22.17 | 66.00 | 21.98 | 66.00 | 21.83 |
April | 477.67 | 23.03 | 0.00 | 23.03 | 0.00 | 23.03 |
May | 364.83 | 23.21 | 46.33 | 23.38 | 6.00 | 23.34 |
June | 104.00 | 23.64 | 139.67 | 24.08 | 0.00 | 24.08 |
July | 25.00 | 23.76 | 261.67 | 24.43 | 0.00 | 24.43 |
August | 33.33 | 23.62 | 151.67 | 24.51 | 0.00 | 24.51 |
September | 202.50 | 23.51 | 129.50 | 23.95 | 1.50 | 23.95 |
October | 469.33 | 23.27 | 2.00 | 23.26 | 2.00 | 23.25 |
November | 489.00 | 22.27 | 68.00 | 22.09 | 68.00 | 21.94 |
December | 497.00 | 21.20 | 240.67 | 20.95 | 240.67 | 20.83 |
Annual Sum or Average | 4132.67 | 22.27 | 1644.00 | 22.29 | 922.67 | 22.05 |
Minimum of Months | 25.00 | 20.85 | 0.00 | 20.72 | 0.00 | 20.67 |
Maximum of Months | 514.00 | 23.76 | 353.33 | 24.51 | 353.33 | 24.51 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.33 | 454.67 | 20.28 | 454.67 | 20.26 |
February | 454.00 | 20.84 | 328.33 | 20.67 | 328.33 | 20.61 |
March | 514.00 | 21.38 | 201.50 | 21.10 | 201.50 | 20.94 |
April | 479.00 | 22.32 | 64.17 | 22.11 | 64.17 | 21.94 |
May | 390.67 | 22.76 | 59.83 | 22.68 | 38.17 | 22.51 |
June | 161.00 | 23.41 | 127.83 | 23.82 | 0.00 | 23.82 |
July | 48.83 | 23.48 | 246.17 | 24.24 | 0.00 | 24.24 |
August | 97.83 | 23.48 | 139.17 | 24.10 | 0.00 | 24.10 |
September | 273.67 | 22.98 | 105.17 | 23.40 | 4.50 | 23.39 |
October | 494.67 | 22.41 | 41.67 | 22.25 | 41.67 | 22.12 |
November | 489.00 | 21.29 | 226.67 | 21.01 | 226.67 | 20.87 |
December | 497.00 | 20.49 | 388.33 | 20.35 | 388.33 | 20.29 |
Annual Sum or Average | 4401.67 | 21.68 | 2383.50 | 21.59 | 1748.00 | 21.33 |
Minimum of Months | 48.83 | 20.33 | 41.67 | 20.28 | 0.00 | 20.26 |
Maximum of Months | 514.00 | 23.48 | 454.67 | 24.24 | 454.67 | 24.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.66 | 497.83 | 19.65 | 497.83 | 19.65 |
February | 454.00 | 20.10 | 428.67 | 20.05 | 428.67 | 20.04 |
March | 514.00 | 20.49 | 370.67 | 20.32 | 370.67 | 20.25 |
April | 479.50 | 21.39 | 181.33 | 21.05 | 181.33 | 20.85 |
May | 406.67 | 22.09 | 121.33 | 21.90 | 92.00 | 21.64 |
June | 173.67 | 22.95 | 164.33 | 23.59 | 1.33 | 23.57 |
July | 75.67 | 23.44 | 270.17 | 24.22 | 3.33 | 24.24 |
August | 150.83 | 23.06 | 156.33 | 23.74 | 2.67 | 23.75 |
September | 319.83 | 22.24 | 125.83 | 22.59 | 40.83 | 22.45 |
October | 499.50 | 21.37 | 170.00 | 21.06 | 170.00 | 20.87 |
November | 489.00 | 20.28 | 370.83 | 20.13 | 370.83 | 20.06 |
December | 497.00 | 19.82 | 482.17 | 19.80 | 482.17 | 19.79 |
Annual Sum or Average | 4561.67 | 20.95 | 3339.50 | 20.92 | 2641.67 | 20.68 |
Minimum of Months | 75.67 | 19.66 | 121.33 | 19.65 | 1.33 | 19.65 |
Maximum of Months | 514.00 | 23.44 | 497.83 | 24.22 | 497.83 | 24.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.85 | 486.17 | 19.83 | 486.17 | 19.82 |
February | 454.00 | 20.37 | 372.17 | 20.23 | 372.17 | 20.18 |
March | 506.67 | 20.79 | 313.67 | 20.53 | 313.67 | 20.41 |
April | 402.17 | 21.44 | 142.50 | 21.17 | 130.17 | 20.95 |
May | 319.00 | 21.89 | 136.67 | 21.96 | 71.83 | 21.68 |
June | 133.50 | 23.11 | 260.00 | 23.99 | 16.00 | 24.08 |
July | 79.83 | 24.62 | 368.33 | 24.55 | 30.83 | 24.71 |
August | 122.50 | 23.15 | 293.00 | 24.02 | 11.50 | 24.09 |
September | 268.83 | 22.40 | 175.00 | 23.05 | 44.83 | 23.04 |
October | 469.17 | 21.56 | 124.83 | 21.26 | 123.83 | 21.05 |
November | 489.00 | 20.47 | 338.83 | 20.28 | 338.83 | 20.21 |
December | 497.00 | 19.89 | 471.83 | 19.86 | 471.83 | 19.85 |
Annual Sum or Average | 4243.67 | 21.03 | 3483.00 | 21.23 | 2411.67 | 20.98 |
Minimum of Months | 79.83 | 19.85 | 124.83 | 19.83 | 11.50 | 19.82 |
Maximum of Months | 506.67 | 24.62 | 486.17 | 24.55 | 486.17 | 24.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.00 | 20.36 | 406.33 | 20.16 | 405.67 | 20.08 |
February | 414.67 | 20.87 | 286.17 | 20.62 | 274.17 | 20.47 |
March | 444.83 | 20.91 | 286.33 | 20.71 | 268.17 | 20.55 |
April | 383.50 | 21.43 | 177.50 | 21.31 | 142.67 | 21.07 |
May | 337.17 | 21.86 | 160.67 | 21.97 | 87.17 | 21.69 |
June | 184.83 | 22.69 | 200.17 | 23.55 | 10.33 | 23.57 |
July | 115.00 | 23.65 | 302.33 | 24.26 | 19.67 | 24.39 |
August | 149.83 | 23.05 | 268.17 | 23.92 | 11.17 | 23.98 |
September | 238.17 | 22.41 | 216.17 | 23.22 | 46.00 | 23.20 |
October | 361.67 | 21.64 | 177.67 | 21.72 | 111.33 | 21.49 |
November | 426.67 | 20.96 | 260.00 | 20.72 | 245.17 | 20.56 |
December | 476.33 | 20.34 | 372.83 | 20.11 | 372.83 | 20.02 |
Annual Sum or Average | 4026.67 | 21.30 | 3114.33 | 21.48 | 1994.33 | 21.20 |
Minimum of Months | 115.00 | 20.34 | 160.67 | 20.11 | 10.33 | 20.02 |
Maximum of Months | 494.00 | 23.65 | 406.33 | 24.26 | 405.67 | 24.39 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 481.50 | 19.81 | 481.50 | 19.80 |
February | 447.50 | 20.30 | 373.17 | 20.17 | 372.50 | 20.12 |
March | 495.67 | 20.61 | 338.00 | 20.41 | 338.00 | 20.33 |
April | 425.83 | 21.22 | 184.67 | 21.05 | 163.67 | 20.87 |
May | 364.17 | 21.88 | 163.00 | 22.01 | 87.00 | 21.78 |
June | 209.17 | 22.62 | 221.83 | 23.50 | 11.50 | 23.52 |
July | 135.83 | 23.43 | 300.67 | 24.15 | 20.50 | 24.28 |
August | 182.33 | 22.77 | 234.00 | 23.68 | 8.83 | 23.73 |
September | 307.83 | 22.05 | 166.83 | 22.63 | 49.50 | 22.57 |
October | 450.50 | 21.20 | 167.83 | 21.00 | 155.50 | 20.82 |
November | 484.83 | 20.48 | 337.00 | 20.28 | 337.00 | 20.20 |
December | 497.00 | 19.91 | 461.50 | 19.86 | 461.50 | 19.84 |
Annual Sum or Average | 4502.67 | 20.99 | 3430.00 | 21.11 | 2487.00 | 20.87 |
Minimum of Months | 135.83 | 19.83 | 163.00 | 19.81 | 8.83 | 19.80 |
Maximum of Months | 502.00 | 23.43 | 481.50 | 24.15 | 481.50 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.89 | 502.00 | 19.89 | 502.00 | 19.89 |
February | 454.00 | 20.32 | 438.00 | 20.30 | 438.00 | 20.29 |
March | 514.00 | 20.57 | 414.00 | 20.49 | 414.00 | 20.46 |
April | 485.00 | 21.17 | 201.67 | 20.97 | 201.67 | 20.85 |
May | 465.00 | 22.16 | 92.67 | 21.94 | 84.83 | 21.76 |
June | 248.67 | 23.33 | 90.00 | 23.56 | 0.00 | 23.56 |
July | 69.83 | 23.59 | 215.50 | 24.17 | 0.00 | 24.17 |
August | 151.50 | 23.42 | 106.50 | 23.83 | 0.00 | 23.83 |
September | 310.83 | 22.79 | 86.50 | 23.17 | 5.67 | 23.16 |
October | 502.00 | 22.15 | 46.00 | 22.03 | 46.00 | 21.92 |
November | 489.00 | 20.90 | 279.33 | 20.70 | 279.33 | 20.61 |
December | 497.00 | 20.14 | 477.50 | 20.12 | 477.50 | 20.11 |
Annual Sum or Average | 4688.83 | 21.28 | 2949.67 | 21.15 | 2449.00 | 20.92 |
Minimum of Months | 69.83 | 19.89 | 46.00 | 19.89 | 0.00 | 19.89 |
Maximum of Months | 514.00 | 23.59 | 502.00 | 24.17 | 502.00 | 24.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.11 | 496.50 | 20.10 | 496.50 | 20.10 |
February | 454.00 | 20.65 | 361.50 | 20.51 | 361.50 | 20.46 |
March | 514.00 | 21.02 | 295.50 | 20.78 | 295.50 | 20.68 |
April | 452.00 | 21.84 | 113.17 | 21.57 | 112.33 | 21.38 |
May | 362.17 | 22.37 | 88.17 | 22.36 | 49.00 | 22.16 |
June | 116.67 | 23.25 | 245.50 | 24.11 | 3.83 | 24.14 |
July | 39.33 | 25.20 | 395.50 | 24.62 | 19.33 | 24.73 |
August | 70.83 | 23.64 | 308.17 | 24.32 | 7.00 | 24.37 |
September | 211.00 | 23.06 | 169.17 | 23.80 | 15.00 | 23.89 |
October | 437.83 | 22.50 | 24.83 | 22.44 | 20.83 | 22.36 |
November | 489.00 | 21.25 | 219.67 | 21.00 | 219.67 | 20.87 |
December | 497.00 | 20.26 | 457.67 | 20.22 | 457.67 | 20.20 |
Annual Sum or Average | 4145.83 | 21.42 | 3175.33 | 21.60 | 2058.17 | 21.34 |
Minimum of Months | 39.33 | 20.11 | 24.83 | 20.10 | 3.83 | 20.10 |
Maximum of Months | 514.00 | 25.20 | 496.50 | 24.62 | 496.50 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.83 | 19.15 | 427.67 | 18.95 | 426.67 | 18.87 |
February | 426.33 | 20.15 | 296.17 | 19.88 | 287.83 | 19.71 |
March | 490.33 | 20.60 | 261.50 | 20.27 | 261.33 | 20.11 |
April | 455.17 | 21.34 | 159.17 | 21.05 | 152.17 | 20.82 |
May | 410.50 | 21.57 | 128.00 | 21.47 | 95.17 | 21.21 |
June | 237.17 | 22.41 | 143.33 | 23.15 | 2.67 | 23.13 |
July | 80.83 | 23.03 | 298.33 | 24.24 | 6.83 | 24.29 |
August | 123.33 | 22.72 | 267.83 | 24.00 | 5.67 | 24.04 |
September | 216.83 | 22.50 | 209.67 | 23.55 | 28.67 | 23.60 |
October | 347.17 | 22.07 | 85.83 | 22.29 | 30.83 | 22.16 |
November | 430.33 | 21.09 | 174.50 | 20.81 | 160.17 | 20.55 |
December | 494.17 | 19.91 | 356.17 | 19.61 | 356.17 | 19.49 |
Annual Sum or Average | 4211.00 | 20.96 | 2808.17 | 21.08 | 1814.17 | 20.75 |
Minimum of Months | 80.83 | 19.15 | 85.83 | 18.95 | 2.67 | 18.87 |
Maximum of Months | 498.83 | 23.03 | 427.67 | 24.24 | 426.67 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.08 | 491.00 | 20.07 | 491.00 | 20.06 |
February | 452.17 | 20.57 | 374.83 | 20.45 | 374.83 | 20.41 |
March | 509.17 | 20.84 | 331.83 | 20.67 | 331.83 | 20.59 |
April | 461.00 | 21.54 | 137.17 | 21.34 | 132.00 | 21.18 |
May | 377.50 | 22.25 | 98.33 | 22.32 | 52.83 | 22.14 |
June | 178.17 | 23.07 | 186.67 | 23.78 | 2.33 | 23.80 |
July | 55.17 | 23.95 | 335.00 | 24.40 | 9.33 | 24.46 |
August | 110.67 | 23.29 | 239.83 | 24.11 | 4.50 | 24.15 |
September | 248.83 | 22.81 | 156.83 | 23.54 | 11.33 | 23.61 |
October | 441.17 | 22.22 | 43.00 | 22.15 | 35.33 | 22.04 |
November | 485.83 | 21.17 | 227.67 | 20.92 | 227.67 | 20.80 |
December | 497.00 | 20.25 | 441.83 | 20.18 | 441.83 | 20.16 |
Annual Sum or Average | 4318.67 | 21.34 | 3064.00 | 21.46 | 2114.83 | 21.21 |
Minimum of Months | 55.17 | 20.08 | 43.00 | 20.07 | 2.33 | 20.06 |
Maximum of Months | 509.17 | 23.95 | 491.00 | 24.40 | 491.00 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.91 | 494.17 | 19.90 | 494.17 | 19.90 |
February | 454.00 | 20.39 | 400.67 | 20.32 | 400.67 | 20.30 |
March | 514.00 | 20.85 | 298.50 | 20.63 | 298.50 | 20.53 |
April | 482.17 | 21.90 | 105.17 | 21.63 | 105.17 | 21.44 |
May | 382.00 | 22.47 | 81.50 | 22.40 | 49.17 | 22.19 |
June | 133.33 | 23.37 | 171.00 | 23.89 | 0.00 | 23.89 |
July | 34.00 | 23.69 | 295.50 | 24.38 | 0.50 | 24.38 |
August | 106.00 | 23.44 | 161.67 | 24.07 | 0.50 | 24.07 |
September | 277.83 | 22.69 | 109.00 | 23.18 | 11.33 | 23.15 |
October | 496.17 | 22.04 | 70.83 | 21.83 | 70.83 | 21.67 |
November | 489.00 | 20.77 | 285.17 | 20.54 | 285.17 | 20.43 |
December | 497.00 | 20.03 | 465.17 | 19.99 | 465.17 | 19.98 |
Annual Sum or Average | 4367.50 | 21.26 | 2938.33 | 21.25 | 2181.17 | 20.99 |
Minimum of Months | 34.00 | 19.91 | 70.83 | 19.90 | 0.00 | 19.90 |
Maximum of Months | 514.00 | 23.69 | 494.17 | 24.38 | 494.17 | 24.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.90 | 410.83 | 19.87 | 410.83 | 19.87 |
February | 383.67 | 20.54 | 295.17 | 20.39 | 295.17 | 20.32 |
March | 426.67 | 20.97 | 224.33 | 20.71 | 224.33 | 20.59 |
April | 348.00 | 21.77 | 85.33 | 21.62 | 72.17 | 21.43 |
May | 270.33 | 22.16 | 94.83 | 22.34 | 38.17 | 22.12 |
June | 117.33 | 23.58 | 215.67 | 24.23 | 15.33 | 24.35 |
July | 54.17 | 25.27 | 315.33 | 24.76 | 28.33 | 24.93 |
August | 91.17 | 23.48 | 229.00 | 24.26 | 9.50 | 24.34 |
September | 222.83 | 22.75 | 136.83 | 23.49 | 21.00 | 23.58 |
October | 392.00 | 21.95 | 59.33 | 21.79 | 54.83 | 21.62 |
November | 416.00 | 20.83 | 233.50 | 20.60 | 233.50 | 20.50 |
December | 422.00 | 19.96 | 390.67 | 19.92 | 390.67 | 19.90 |
Annual Sum or Average | 3571.17 | 21.26 | 2690.83 | 21.45 | 1793.83 | 21.20 |
Minimum of Months | 54.17 | 19.90 | 59.33 | 19.87 | 9.50 | 19.87 |
Maximum of Months | 427.00 | 25.27 | 410.83 | 24.76 | 410.83 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 489.83 | 20.66 | 379.17 | 20.44 | 376.33 | 20.34 |
February | 402.67 | 21.22 | 248.17 | 20.98 | 233.67 | 20.80 |
March | 435.33 | 21.32 | 216.00 | 21.12 | 195.00 | 20.93 |
April | 375.17 | 21.94 | 115.67 | 21.92 | 80.00 | 21.71 |
May | 311.67 | 22.25 | 122.67 | 22.45 | 49.17 | 22.23 |
June | 151.00 | 23.13 | 205.17 | 23.88 | 2.83 | 23.91 |
July | 66.17 | 24.26 | 334.17 | 24.48 | 17.83 | 24.58 |
August | 108.50 | 23.52 | 284.50 | 24.21 | 9.50 | 24.28 |
September | 199.50 | 22.94 | 217.33 | 23.80 | 24.17 | 23.91 |
October | 335.00 | 22.29 | 122.67 | 22.56 | 43.83 | 22.44 |
November | 408.50 | 21.48 | 204.50 | 21.32 | 174.00 | 21.10 |
December | 465.50 | 20.69 | 321.67 | 20.41 | 321.67 | 20.29 |
Annual Sum or Average | 3748.83 | 21.66 | 2771.67 | 21.91 | 1528.00 | 21.63 |
Minimum of Months | 66.17 | 20.66 | 115.67 | 20.41 | 2.83 | 20.29 |
Maximum of Months | 489.83 | 24.26 | 379.17 | 24.48 | 376.33 | 24.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.04 | 475.67 | 20.01 | 475.67 | 19.99 |
February | 446.17 | 20.58 | 343.17 | 20.43 | 342.17 | 20.37 |
March | 492.83 | 20.92 | 262.50 | 20.69 | 262.50 | 20.58 |
April | 419.83 | 21.66 | 118.50 | 21.55 | 97.50 | 21.39 |
May | 329.83 | 22.19 | 130.00 | 22.42 | 52.33 | 22.24 |
June | 171.67 | 23.06 | 225.17 | 23.81 | 6.83 | 23.87 |
July | 78.17 | 23.98 | 329.17 | 24.39 | 18.67 | 24.51 |
August | 134.50 | 23.16 | 244.83 | 24.00 | 6.50 | 24.05 |
September | 273.17 | 22.48 | 159.50 | 23.21 | 20.67 | 23.26 |
October | 437.67 | 21.77 | 80.83 | 21.67 | 65.83 | 21.52 |
November | 479.50 | 20.90 | 251.17 | 20.65 | 251.17 | 20.53 |
December | 497.00 | 20.13 | 430.00 | 20.04 | 430.00 | 20.01 |
Annual Sum or Average | 4262.33 | 21.26 | 3050.50 | 21.42 | 2029.83 | 21.17 |
Minimum of Months | 78.17 | 20.04 | 80.83 | 20.01 | 6.50 | 19.99 |
Maximum of Months | 502.00 | 23.98 | 475.67 | 24.39 | 475.67 | 24.51 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.18525 | 14.53054 | -0.3607 | 9.11577 |
February | 454.00000 | 22.93447 | 16.23662 | -0.1543 | 6.62554 |
March | 514.00000 | 23.50891 | 17.16547 | 0.01200 | 5.70818 |
April | 485.00000 | 23.98536 | 20.13549 | 0.17334 | 5.86237 |
May | 508.00000 | 24.25002 | 23.09596 | -0.6187 | 14.09076 |
June | 496.00000 | 24.32780 | 30.75973 | -0.4619 | 9.88539 |
July | 497.00000 | 24.42649 | 34.56087 | -0.3832 | 8.65001 |
August | 514.00000 | 24.39210 | 30.53835 | -0.4254 | 9.28642 |
September | 485.00000 | 24.37408 | 30.16782 | -0.4692 | 10.26201 |
October | 502.00000 | 24.21375 | 22.26396 | 0.26309 | 6.62863 |
November | 489.00000 | 23.77961 | 18.42699 | 0.09114 | 5.76343 |
December | 497.00000 | 22.90182 | 15.84067 | -0.1634 | 6.84343 |
Annual Sum or Average | 5943.00000 | 23.77856 | 22.85194 | -0.2096 | 8.24820 |
Minimum of Months | 454.00000 | 22.18525 | 14.53054 | -0.6187 | 5.70818 |
Maximum of Months | 514.00000 | 24.42649 | 34.56087 | 0.26309 | 14.09076 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.84678 | 15.49232 | -0.6749 | 15.75782 |
February | 454.00000 | 21.47650 | 17.63492 | -0.4852 | 11.22864 |
March | 514.00000 | 22.17069 | 19.09955 | -0.2939 | 8.21229 |
April | 485.00000 | 23.05614 | 22.26873 | -0.0419 | 5.97053 |
May | 508.00000 | 23.58532 | 24.84563 | -0.8479 | 22.37765 |
June | 496.00000 | 24.09021 | 31.92802 | -0.5588 | 12.07018 |
July | 497.00000 | 24.27569 | 35.55908 | -0.4515 | 9.72049 |
August | 514.00000 | 24.22574 | 31.54637 | -0.5041 | 10.74820 |
September | 485.00000 | 23.99456 | 31.76602 | -0.6220 | 14.34078 |
October | 502.00000 | 23.33805 | 24.63666 | 0.04575 | 5.74504 |
November | 489.00000 | 22.27449 | 20.65570 | -0.2617 | 7.86891 |
December | 497.00000 | 21.19818 | 17.33804 | -0.5574 | 13.13657 |
Annual Sum or Average | 5943.00000 | 22.88765 | 24.43854 | -0.4384 | 11.45069 |
Minimum of Months | 454.00000 | 20.84678 | 15.49232 | -0.8479 | 5.74504 |
Maximum of Months | 514.00000 | 24.27569 | 35.55908 | 0.04575 | 22.37765 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.32715 | 15.43605 | -0.8360 | 21.57701 |
February | 454.00000 | 20.83842 | 18.03967 | -0.6649 | 15.97730 |
March | 514.00000 | 21.37996 | 19.63621 | -0.4975 | 12.11989 |
April | 485.00000 | 22.34080 | 22.96231 | -0.2164 | 7.72689 |
May | 508.00000 | 23.13015 | 25.23836 | -1.0053 | 29.12829 |
June | 496.00000 | 23.92797 | 32.01154 | -0.6137 | 13.91094 |
July | 497.00000 | 24.17623 | 35.46107 | -0.4804 | 10.39976 |
August | 514.00000 | 24.09476 | 31.59720 | -0.5517 | 12.09215 |
September | 485.00000 | 23.56250 | 32.44609 | -0.7758 | 20.21978 |
October | 502.00000 | 22.43515 | 25.87315 | -0.1761 | 7.13328 |
November | 489.00000 | 21.28875 | 21.39961 | -0.5153 | 12.55077 |
December | 497.00000 | 20.48927 | 17.53814 | -0.7619 | 19.49527 |
Annual Sum or Average | 5943.00000 | 22.34423 | 24.84235 | -0.5914 | 15.20403 |
Minimum of Months | 454.00000 | 20.32715 | 15.43605 | -1.0053 | 7.13328 |
Maximum of Months | 514.00000 | 24.17623 | 35.46107 | -0.1761 | 29.12829 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.65903 | 15.54835 | -1.0885 | 32.17011 |
February | 454.00000 | 20.09678 | 18.72855 | -0.9062 | 24.50924 |
March | 514.00000 | 20.49291 | 20.58544 | -0.7433 | 19.02885 |
April | 485.00000 | 21.42322 | 24.55228 | -0.4392 | 11.97790 |
May | 508.00000 | 22.52995 | 26.83805 | -1.1922 | 37.66076 |
June | 496.00000 | 23.74860 | 32.64826 | -0.6458 | 16.02387 |
July | 497.00000 | 24.15480 | 35.46518 | -0.4545 | 10.76436 |
August | 514.00000 | 23.87825 | 32.31694 | -0.6055 | 14.71080 |
September | 485.00000 | 22.95892 | 34.10451 | -0.9752 | 29.85756 |
October | 502.00000 | 21.38679 | 27.69616 | -0.4325 | 11.34144 |
November | 489.00000 | 20.27972 | 22.56824 | -0.7929 | 20.89066 |
December | 497.00000 | 19.81563 | 18.22238 | -1.0038 | 28.63952 |
Annual Sum or Average | 5943.00000 | 21.71558 | 25.81150 | -0.7728 | 21.45064 |
Minimum of Months | 454.00000 | 19.65903 | 15.54835 | -1.1922 | 10.76436 |
Maximum of Months | 514.00000 | 24.15480 | 35.46518 | -0.4325 | 37.66076 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.84612 | 15.18841 | -1.0289 | 29.51607 |
February | 454.00000 | 20.36685 | 17.93042 | -0.8132 | 21.55998 |
March | 514.00000 | 20.83753 | 19.53285 | -0.6303 | 16.68060 |
April | 485.00000 | 21.90561 | 23.07277 | -0.2841 | 10.90486 |
May | 508.00000 | 22.75072 | 25.71747 | -1.0441 | 32.23286 |
June | 496.00000 | 23.93179 | 31.77357 | -0.4755 | 13.55491 |
July | 497.00000 | 24.31464 | 34.80350 | -0.2692 | 9.26510 |
August | 514.00000 | 23.98328 | 31.51003 | -0.4470 | 12.37974 |
September | 485.00000 | 23.22862 | 33.02254 | -0.8083 | 25.00306 |
October | 502.00000 | 21.72924 | 26.47076 | -0.3193 | 10.07308 |
November | 489.00000 | 20.46586 | 21.70891 | -0.7287 | 18.67170 |
December | 497.00000 | 19.88656 | 17.72060 | -0.9704 | 27.27883 |
Annual Sum or Average | 5943.00000 | 21.94998 | 24.90996 | -0.6509 | 18.91379 |
Minimum of Months | 454.00000 | 19.84612 | 15.18841 | -1.0441 | 9.26510 |
Maximum of Months | 514.00000 | 24.31464 | 34.80350 | -0.2692 | 32.23286 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.42717 | 14.51316 | -0.8446 | 24.41836 |
February | 454.00000 | 21.17356 | 16.84362 | -0.5753 | 17.89329 |
March | 514.00000 | 21.33994 | 18.56281 | -0.4862 | 15.39795 |
April | 485.00000 | 22.03541 | 22.64438 | -0.2555 | 11.31126 |
May | 508.00000 | 22.68009 | 25.62952 | -1.0862 | 34.60021 |
June | 496.00000 | 23.65483 | 32.33996 | -0.6205 | 17.20036 |
July | 497.00000 | 24.11137 | 35.22963 | -0.3931 | 11.31999 |
August | 514.00000 | 23.90725 | 31.53999 | -0.4831 | 13.72566 |
September | 485.00000 | 23.37461 | 32.36885 | -0.7192 | 23.63609 |
October | 502.00000 | 22.36416 | 24.93908 | -0.1344 | 10.36847 |
November | 489.00000 | 21.37055 | 20.27497 | -0.4772 | 15.05334 |
December | 497.00000 | 20.48853 | 16.88546 | -0.7776 | 22.57676 |
Annual Sum or Average | 5943.00000 | 22.25233 | 24.35847 | -0.5718 | 18.14262 |
Minimum of Months | 454.00000 | 20.42717 | 14.51316 | -1.0862 | 10.36847 |
Maximum of Months | 514.00000 | 24.11137 | 35.22963 | -0.1344 | 34.60021 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83400 | 14.97766 | -1.0405 | 30.08847 |
February | 454.00000 | 20.35604 | 17.67994 | -0.8233 | 22.56477 |
March | 514.00000 | 20.73079 | 19.34671 | -0.6666 | 17.89136 |
April | 485.00000 | 21.58598 | 23.36358 | -0.3635 | 11.89952 |
May | 508.00000 | 22.55781 | 25.96809 | -1.1047 | 35.74229 |
June | 496.00000 | 23.53385 | 32.76651 | -0.6240 | 17.99850 |
July | 497.00000 | 23.99719 | 35.71084 | -0.4067 | 12.19081 |
August | 514.00000 | 23.71700 | 32.24259 | -0.5589 | 15.66712 |
September | 485.00000 | 22.86287 | 33.55864 | -0.9263 | 29.97454 |
October | 502.00000 | 21.50568 | 26.49805 | -0.3721 | 11.23814 |
November | 489.00000 | 20.51275 | 21.38299 | -0.7213 | 19.12270 |
December | 497.00000 | 19.90830 | 17.45009 | -0.9705 | 27.46278 |
Annual Sum or Average | 5943.00000 | 21.77048 | 25.12080 | -0.7145 | 20.98124 |
Minimum of Months | 454.00000 | 19.83400 | 14.97766 | -1.1047 | 11.23814 |
Maximum of Months | 514.00000 | 23.99719 | 35.71084 | -0.3635 | 35.74229 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.88613 | 15.71802 | -1.0103 | 28.37336 |
February | 454.00000 | 20.32027 | 18.81899 | -0.8434 | 21.33339 |
March | 514.00000 | 20.57315 | 20.81751 | -0.7254 | 17.32397 |
April | 485.00000 | 21.16936 | 25.08722 | -0.5106 | 11.49756 |
May | 508.00000 | 22.33562 | 27.59198 | -1.2809 | 41.22180 |
June | 496.00000 | 23.71991 | 33.25199 | -0.7036 | 16.64932 |
July | 497.00000 | 24.12504 | 35.79616 | -0.5058 | 10.92512 |
August | 514.00000 | 23.96202 | 32.48945 | -0.6077 | 13.62819 |
September | 485.00000 | 23.33804 | 33.50185 | -0.8516 | 23.21889 |
October | 502.00000 | 22.15373 | 26.59327 | -0.2315 | 7.29022 |
November | 489.00000 | 20.90284 | 22.05833 | -0.6039 | 14.22313 |
December | 497.00000 | 20.13818 | 18.33104 | -0.8794 | 23.11840 |
Annual Sum or Average | 5943.00000 | 21.89777 | 25.87868 | -0.7295 | 19.08276 |
Minimum of Months | 454.00000 | 19.88613 | 15.71802 | -1.2809 | 7.29022 |
Maximum of Months | 514.00000 | 24.12504 | 35.79616 | -0.2315 | 41.22180 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.10792 | 15.51409 | -0.9448 | 25.54834 |
February | 454.00000 | 20.64738 | 18.29104 | -0.7374 | 18.39546 |
March | 514.00000 | 21.01999 | 20.05849 | -0.5851 | 14.31451 |
April | 485.00000 | 22.00095 | 23.54364 | -0.2799 | 9.16571 |
May | 508.00000 | 22.91132 | 26.14852 | -1.0295 | 30.96768 |
June | 496.00000 | 24.07167 | 31.80654 | -0.4793 | 12.12055 |
July | 497.00000 | 24.44182 | 34.61517 | -0.2680 | 8.09176 |
August | 514.00000 | 24.21555 | 31.24298 | -0.3990 | 9.92202 |
September | 485.00000 | 23.79442 | 32.12300 | -0.6280 | 16.90279 |
October | 502.00000 | 22.71123 | 25.29350 | -0.0728 | 6.73626 |
November | 489.00000 | 21.24806 | 21.38304 | -0.5056 | 12.20238 |
December | 497.00000 | 20.25578 | 18.03958 | -0.8375 | 21.53223 |
Annual Sum or Average | 5943.00000 | 22.29757 | 24.87667 | -0.5635 | 15.49599 |
Minimum of Months | 454.00000 | 20.10792 | 15.51409 | -1.0295 | 6.73626 |
Maximum of Months | 514.00000 | 24.44182 | 34.61517 | -0.0728 | 30.96768 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.19190 | 13.42853 | -1.0458 | 31.00257 |
February | 454.00000 | 20.42524 | 15.99406 | -0.6876 | 20.45483 |
March | 514.00000 | 20.76137 | 17.90095 | -0.5741 | 15.65563 |
April | 485.00000 | 21.54377 | 22.36591 | -0.3614 | 10.85775 |
May | 508.00000 | 22.12822 | 25.77130 | -1.2632 | 41.41901 |
June | 496.00000 | 23.38593 | 32.63693 | -0.7401 | 19.95512 |
July | 497.00000 | 24.14364 | 34.81405 | -0.4237 | 10.87266 |
August | 514.00000 | 23.97697 | 31.05121 | -0.4779 | 12.74747 |
September | 485.00000 | 23.57899 | 31.59088 | -0.6249 | 19.28013 |
October | 502.00000 | 22.78582 | 23.41860 | 0.01379 | 8.27827 |
November | 489.00000 | 21.50879 | 18.93313 | -0.3694 | 12.47487 |
December | 497.00000 | 19.93555 | 15.79696 | -0.8193 | 23.10407 |
Annual Sum or Average | 5943.00000 | 21.95720 | 23.68849 | -0.6153 | 18.87040 |
Minimum of Months | 454.00000 | 19.19190 | 13.42853 | -1.2632 | 8.27827 |
Maximum of Months | 514.00000 | 24.14364 | 34.81405 | 0.01379 | 41.41901 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.08035 | 15.33246 | -0.9598 | 26.18398 |
February | 454.00000 | 20.58830 | 18.08315 | -0.7557 | 19.14143 |
March | 514.00000 | 20.87213 | 19.91902 | -0.6282 | 15.33743 |
April | 485.00000 | 21.67524 | 23.82276 | -0.3599 | 9.83369 |
May | 508.00000 | 22.80704 | 26.21817 | -1.0606 | 32.81404 |
June | 496.00000 | 23.82069 | 32.59224 | -0.5855 | 14.59796 |
July | 497.00000 | 24.26146 | 35.26734 | -0.3653 | 9.27953 |
August | 514.00000 | 24.06915 | 31.81650 | -0.4784 | 11.64990 |
September | 485.00000 | 23.56618 | 32.50395 | -0.7062 | 19.62016 |
October | 502.00000 | 22.45979 | 25.41659 | -0.1290 | 7.08539 |
November | 489.00000 | 21.18547 | 21.17241 | -0.5180 | 12.64788 |
December | 497.00000 | 20.24831 | 17.80344 | -0.8425 | 21.95263 |
Annual Sum or Average | 5943.00000 | 22.14811 | 25.03624 | -0.6156 | 16.68608 |
Minimum of Months | 454.00000 | 20.08035 | 15.33246 | -1.0606 | 7.08539 |
Maximum of Months | 514.00000 | 24.26146 | 35.26734 | -0.1290 | 32.81404 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.91200 | 15.62648 | -0.9824 | 27.43800 |
February | 454.00000 | 20.39079 | 18.65846 | -0.7933 | 19.97020 |
March | 514.00000 | 20.84667 | 20.44424 | -0.6194 | 14.96955 |
April | 485.00000 | 21.90948 | 24.10824 | -0.3033 | 8.88933 |
May | 508.00000 | 22.92237 | 26.43656 | -1.0483 | 31.52600 |
June | 496.00000 | 23.95475 | 32.38771 | -0.5779 | 13.09798 |
July | 497.00000 | 24.27580 | 35.41876 | -0.4193 | 9.47567 |
August | 514.00000 | 24.07393 | 32.07914 | -0.5403 | 12.13307 |
September | 485.00000 | 23.39798 | 33.37907 | -0.8180 | 22.76517 |
October | 502.00000 | 22.06117 | 26.81981 | -0.2509 | 8.03981 |
November | 489.00000 | 20.77222 | 22.08664 | -0.6331 | 15.66635 |
December | 497.00000 | 20.02532 | 18.29971 | -0.8974 | 24.26526 |
Annual Sum or Average | 5943.00000 | 22.05833 | 25.51739 | -0.6566 | 17.34838 |
Minimum of Months | 454.00000 | 19.91200 | 15.62648 | -1.0483 | 8.03981 |
Maximum of Months | 514.00000 | 24.27580 | 35.41876 | -0.2509 | 31.52600 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.89585 | 14.52295 | -0.9743 | 27.08795 |
February | 385.00000 | 20.55659 | 17.20819 | -0.7355 | 18.75064 |
March | 433.00000 | 21.01735 | 18.77310 | -0.5607 | 14.20262 |
April | 410.00000 | 22.15190 | 22.40508 | -0.2123 | 8.96040 |
May | 430.00000 | 22.95264 | 25.18655 | -0.9759 | 29.58562 |
June | 418.00000 | 24.08368 | 31.41448 | -0.4480 | 12.22667 |
July | 422.00000 | 24.46959 | 34.50089 | -0.2547 | 8.85046 |
August | 433.00000 | 24.14793 | 31.05233 | -0.4238 | 11.26834 |
September | 410.00000 | 23.49640 | 32.27655 | -0.7205 | 21.40538 |
October | 427.00000 | 22.14378 | 25.32352 | -0.2057 | 8.01943 |
November | 417.00000 | 20.83543 | 20.53189 | -0.6074 | 14.88085 |
December | 422.00000 | 19.96168 | 16.99554 | -0.9035 | 24.46993 |
Annual Sum or Average | 5034.00000 | 22.15188 | 24.21300 | -0.5850 | 16.64438 |
Minimum of Months | 385.00000 | 19.89585 | 14.52295 | -0.9759 | 8.01943 |
Maximum of Months | 433.00000 | 24.46959 | 34.50089 | -0.2057 | 29.58562 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.75995 | 14.39017 | -0.7253 | 20.41020 |
February | 454.00000 | 21.58967 | 16.56697 | -0.4430 | 14.46965 |
March | 514.00000 | 21.75727 | 18.31401 | -0.3541 | 12.01646 |
April | 485.00000 | 22.48643 | 22.21492 | -0.1293 | 8.79702 |
May | 508.00000 | 23.05273 | 25.25349 | -0.9502 | 28.82794 |
June | 496.00000 | 23.90603 | 32.04809 | -0.5424 | 13.62465 |
July | 497.00000 | 24.28514 | 35.08234 | -0.3467 | 9.46311 |
August | 514.00000 | 24.12421 | 31.30561 | -0.4166 | 10.96849 |
September | 485.00000 | 23.75238 | 31.75306 | -0.5829 | 17.79547 |
October | 502.00000 | 22.94575 | 24.12680 | 0.02460 | 8.49899 |
November | 489.00000 | 21.95990 | 19.68787 | -0.3040 | 11.61450 |
December | 497.00000 | 20.90174 | 16.65111 | -0.6361 | 18.24339 |
Annual Sum or Average | 5943.00000 | 22.63425 | 23.99452 | -0.4515 | 14.57939 |
Minimum of Months | 454.00000 | 20.75995 | 14.39017 | -0.9502 | 8.49899 |
Maximum of Months | 514.00000 | 24.28514 | 35.08234 | 0.02460 | 28.82794 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.04053 | 14.90742 | -0.9448 | 25.95207 |
February | 454.00000 | 20.64799 | 17.50248 | -0.7126 | 18.49964 |
March | 514.00000 | 21.04247 | 19.23671 | -0.5518 | 14.22896 |
April | 485.00000 | 22.01005 | 23.01238 | -0.2407 | 9.13332 |
May | 508.00000 | 22.92499 | 25.62236 | -0.9696 | 30.00392 |
June | 496.00000 | 23.80164 | 32.48494 | -0.5411 | 14.19969 |
July | 497.00000 | 24.19454 | 35.53649 | -0.3534 | 10.01174 |
August | 514.00000 | 23.97050 | 31.97036 | -0.4810 | 12.41017 |
September | 485.00000 | 23.28284 | 32.93390 | -0.7760 | 23.22948 |
October | 502.00000 | 22.08029 | 25.76427 | -0.2109 | 8.34286 |
November | 489.00000 | 20.95817 | 20.95603 | -0.5718 | 14.58228 |
December | 497.00000 | 20.13162 | 17.39826 | -0.8631 | 23.21121 |
Annual Sum or Average | 5943.00000 | 22.10209 | 24.81953 | -0.6012 | 16.98316 |
Minimum of Months | 454.00000 | 20.04053 | 14.90742 | -0.9696 | 8.34286 |
Maximum of Months | 514.00000 | 24.19454 | 35.53649 | -0.2109 | 30.00392 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.150890E+09 | 41585266.51 | 8.17 | 0.150833E+09 | 57664.25 | 0.00 | 0.41 | 27-FEB-15:40 | 0.00 | 01-FEB-00:10 | 11233.52 | 27-FEB-15:40 | 11233.52 | 27-FEB-15:40 | 15.77 | 26-FEB-16:00 | 3015.98 | 27-FEB-15:40 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.169334E+10 | 0.450331E+09 | 58.37 | 0.168245E+10 | 10892094.36 | 0.00 | 0.83 | 07-APR-14:00 | 0.00 | 01-APR-00:10 | 25724.09 | 07-APR-14:00 | 25724.09 | 07-APR-14:00 | 544.65 | 22-APR-15:00 | 6162.58 | 07-APR-14:00 | 0.00 |
May | 0.705633E+10 | 0.181234E+10 | 142.96 | 0.687655E+10 | 0.179778E+09 | 0.00 | 1.00 | 19-MAY-11:40 | 0.00 | 01-MAY-00:10 | 52133.12 | 19-MAY-15:40 | 52133.12 | 19-MAY-15:40 | 5089.32 | 02-MAY-13:00 | 13227.15 | 19-MAY-15:30 | 0.00 |
June | 0.274812E+11 | 0.691474E+10 | 304.52 | 0.262610E+11 | 0.122029E+10 | 0.00 | 1.00 | 05-JUN-12:10 | 0.00 | 01-JUN-00:10 | 66317.63 | 20-JUN-16:10 | 65531.10 | 29-JUN-15:10 | 13378.78 | 22-JUN-06:02 | 18589.01 | 29-JUN-15:10 | 0.00 |
July | 0.484798E+11 | 0.125678E+11 | 406.18 | 0.468071E+11 | 0.167269E+10 | 0.00 | 1.00 | 01-JUL-12:50 | 0.00 | 01-JUL-00:10 | 79917.12 | 17-JUL-16:00 | 79917.12 | 17-JUL-16:00 | 19719.53 | 19-JUL-04:03 | 26523.81 | 17-JUL-16:00 | 0.00 |
August | 0.411628E+11 | 0.105417E+11 | 367.35 | 0.407512E+11 | 0.411631E+09 | 0.00 | 1.00 | 01-AUG-10:40 | 0.00 | 01-AUG-00:10 | 73426.30 | 07-AUG-16:00 | 73426.30 | 07-AUG-16:00 | 4758.24 | 08-AUG-12:00 | 21035.29 | 07-AUG-15:10 | 0.00 |
September | 0.193283E+11 | 0.488870E+10 | 240.45 | 0.176771E+11 | 0.165120E+10 | 0.00 | 1.00 | 01-SEP-09:20 | 0.00 | 01-SEP-00:10 | 104277.46 | 07-SEP-15:00 | 62035.81 | 01-SEP-16:00 | 49248.67 | 07-SEP-14:55 | 24018.10 | 07-SEP-14:55 | 0.00 |
October | 0.410638E+10 | 0.103509E+10 | 94.31 | 0.408490E+10 | 21475746.37 | 0.00 | 1.00 | 18-OCT-11:50 | 0.00 | 01-OCT-00:10 | 47241.06 | 18-OCT-15:40 | 47241.06 | 18-OCT-15:40 | 730.99 | 15-OCT-11:17 | 10987.31 | 18-OCT-15:40 | 0.00 |
November | 0.149120E+09 | 42801190.83 | 14.83 | 0.143613E+09 | 5507155.41 | 0.00 | 0.22 | 17-NOV-17:00 | 0.00 | 01-NOV-00:10 | 5670.75 | 17-NOV-17:00 | 5636.31 | 17-NOV-17:00 | 370.60 | 17-NOV-18:05 | 1596.46 | 17-NOV-17:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.149608E+12 | 0.382952E+11 | 1637.13 | 0.144435E+12 | 0.517352E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.484798E+11 | 0.125678E+11 | 406.18 | 0.468071E+11 | 0.167269E+10 | 0.00 | 1.00 | 0.00 | 104277.46 | 79917.12 | 49248.67 | 26523.81 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.153035E+09 | 42043651.68 | 9.25 | 0.153035E+09 | -0.0 | 0.00 | 0.42 | 27-FEB-15:30 | 0.00 | 01-FEB-00:10 | 10552.65 | 27-FEB-15:30 | 10552.65 | 27-FEB-15:30 | 0.00 | 27-FEB-11:50 | 2822.85 | 27-FEB-15:30 | 0.00 |
March | 1055157.94 | 311734.37 | 1.17 | 1055157.94 | -0.0 | 0.00 | 0.01 | 14-MAR-13:40 | 0.00 | 01-MAR-00:10 | 267.71 | 14-MAR-13:40 | 267.71 | 14-MAR-13:40 | 0.00 | 14-MAR-13:50 | 79.08 | 14-MAR-13:40 | 0.00 |
April | 0.179162E+10 | 0.473963E+09 | 64.82 | 0.178360E+10 | 8024606.32 | 0.00 | 0.92 | 06-APR-16:00 | 0.00 | 01-APR-00:10 | 26306.95 | 06-APR-16:00 | 26306.95 | 06-APR-16:00 | 480.31 | 23-APR-13:25 | 6148.02 | 06-APR-16:00 | 0.00 |
May | 0.731576E+10 | 0.185566E+10 | 150.03 | 0.716954E+10 | 0.146224E+09 | 0.00 | 1.00 | 18-MAY-15:00 | 0.00 | 01-MAY-00:10 | 53140.33 | 19-MAY-15:30 | 53140.33 | 19-MAY-15:30 | 4758.97 | 02-MAY-13:00 | 13482.25 | 19-MAY-15:20 | 0.00 |
June | 0.265844E+11 | 0.666768E+10 | 315.07 | 0.254784E+11 | 0.110594E+10 | 0.00 | 1.00 | 05-JUN-12:10 | 0.00 | 01-JUN-00:10 | 63146.55 | 29-JUN-14:50 | 63146.55 | 29-JUN-14:50 | 7997.22 | 20-JUN-15:00 | 17969.84 | 29-JUN-15:00 | 0.00 |
July | 0.449729E+11 | 0.116558E+11 | 405.85 | 0.436526E+11 | 0.132029E+10 | 0.00 | 1.00 | 01-JUL-09:50 | 0.00 | 01-JUL-00:10 | 78089.68 | 17-JUL-15:40 | 78089.68 | 17-JUL-15:40 | 18516.69 | 19-JUL-05:03 | 25614.31 | 17-JUL-15:40 | 0.00 |
August | 0.376795E+11 | 0.967032E+10 | 369.70 | 0.373301E+11 | 0.349377E+09 | 0.00 | 1.00 | 01-AUG-10:30 | 0.00 | 01-AUG-00:10 | 73862.98 | 07-AUG-15:30 | 73862.98 | 07-AUG-15:30 | 4017.12 | 22-AUG-15:30 | 21236.28 | 07-AUG-15:30 | 0.00 |
September | 0.173478E+11 | 0.439224E+10 | 233.80 | 0.159841E+11 | 0.136370E+10 | 0.00 | 1.00 | 01-SEP-09:20 | 0.00 | 01-SEP-00:10 | 94273.78 | 07-SEP-14:55 | 69607.83 | 04-SEP-15:41 | 44670.53 | 07-SEP-14:50 | 21713.97 | 07-SEP-14:55 | 0.00 |
October | 0.339934E+10 | 0.865184E+09 | 92.17 | 0.338494E+10 | 14397697.79 | 0.00 | 1.00 | 18-OCT-12:10 | 0.00 | 01-OCT-00:10 | 41383.64 | 18-OCT-15:50 | 41383.64 | 18-OCT-15:50 | 442.83 | 15-OCT-10:57 | 9627.91 | 18-OCT-15:20 | 0.00 |
November | 0.139182E+09 | 39979927.88 | 15.50 | 0.132441E+09 | 6740493.53 | 0.00 | 0.22 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 5152.41 | 04-NOV-14:00 | 5152.41 | 04-NOV-14:00 | 353.22 | 17-NOV-17:00 | 1450.17 | 04-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.139384E+12 | 0.356632E+11 | 1657.36 | 0.135070E+12 | 0.431469E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.449729E+11 | 0.116558E+11 | 405.85 | 0.436526E+11 | 0.136370E+10 | 0.00 | 1.00 | 0.00 | 94273.78 | 78089.68 | 44670.53 | 25614.31 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.144329E+09 | 40134322.31 | 8.00 | 0.144329E+09 | 0.00 | 0.00 | 0.37 | 27-FEB-15:30 | 0.00 | 01-FEB-00:10 | 10392.57 | 27-FEB-15:30 | 10392.57 | 27-FEB-15:30 | 0.00 | 27-FEB-11:50 | 2820.91 | 27-FEB-15:30 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.180611E+10 | 0.483604E+09 | 62.77 | 0.179397E+10 | 12139210.16 | 0.00 | 0.86 | 06-APR-16:00 | 0.00 | 01-APR-00:10 | 27931.10 | 06-APR-16:00 | 27931.10 | 06-APR-16:00 | 630.32 | 23-APR-13:25 | 6644.16 | 06-APR-16:00 | 0.00 |
May | 0.781200E+10 | 0.199655E+10 | 148.08 | 0.760038E+10 | 0.211618E+09 | 0.00 | 1.00 | 19-MAY-11:50 | 0.00 | 01-MAY-00:10 | 62837.47 | 19-MAY-15:30 | 62837.47 | 19-MAY-15:30 | 5280.03 | 02-MAY-13:00 | 15953.50 | 19-MAY-15:20 | 0.00 |
June | 0.287658E+11 | 0.726662E+10 | 311.55 | 0.274802E+11 | 0.128565E+10 | 0.00 | 1.00 | 05-JUN-12:50 | 0.00 | 01-JUN-00:10 | 72869.08 | 29-JUN-14:50 | 72869.08 | 29-JUN-14:50 | 8126.56 | 20-JUN-15:00 | 20768.61 | 29-JUN-15:00 | 0.00 |
July | 0.486023E+11 | 0.127047E+11 | 402.08 | 0.470883E+11 | 0.151402E+10 | 0.00 | 1.00 | 01-JUL-11:40 | 0.00 | 01-JUL-00:10 | 91272.12 | 17-JUL-15:30 | 91272.12 | 17-JUL-15:30 | 19897.89 | 19-JUL-05:03 | 29766.97 | 17-JUL-15:30 | 0.00 |
August | 0.401235E+11 | 0.104046E+11 | 365.39 | 0.396336E+11 | 0.489945E+09 | 0.00 | 1.00 | 01-AUG-11:30 | 0.00 | 01-AUG-00:10 | 86986.52 | 06-AUG-16:11 | 86986.52 | 06-AUG-16:11 | 4448.55 | 22-AUG-15:30 | 27300.24 | 06-AUG-16:11 | 0.00 |
September | 0.179041E+11 | 0.458697E+10 | 229.98 | 0.163678E+11 | 0.153629E+10 | 0.00 | 1.00 | 01-SEP-09:50 | 0.00 | 01-SEP-00:10 | 96571.79 | 07-SEP-15:20 | 78771.08 | 03-SEP-15:42 | 45900.76 | 07-SEP-15:00 | 23721.33 | 03-SEP-15:42 | 0.00 |
October | 0.317856E+10 | 0.825760E+09 | 88.38 | 0.314565E+10 | 32907783.53 | 0.00 | 1.00 | 18-OCT-13:00 | 0.00 | 01-OCT-00:10 | 42840.50 | 18-OCT-15:00 | 42840.50 | 18-OCT-15:00 | 676.17 | 15-OCT-11:13 | 10062.31 | 18-OCT-15:00 | 0.00 |
November | 0.138338E+09 | 39853413.55 | 14.33 | 0.127735E+09 | 10603294.66 | 0.00 | 0.18 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4961.93 | 04-NOV-14:00 | 4961.93 | 04-NOV-14:00 | 495.92 | 17-NOV-17:00 | 1408.36 | 04-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.148475E+12 | 0.383488E+11 | 1630.56 | 0.143382E+12 | 0.509316E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.486023E+11 | 0.127047E+11 | 402.08 | 0.470883E+11 | 0.153629E+10 | 0.00 | 1.00 | 0.00 | 96571.79 | 91272.12 | 45900.76 | 29766.97 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 308.53 | 0.00 | 308.53 | 14.85 | 2420.93 | 0.00 | 0.00 | 0.00 |
February | 435.63 | 0.00 | 435.63 | 94.42 | 1765.40 | 0.00 | 0.00 | 0.00 |
March | 707.66 | 0.00 | 707.66 | 285.96 | 1404.20 | 0.00 | 0.00 | 0.00 |
April | 806.88 | 4.71 | 802.17 | 467.99 | 986.61 | 0.00 | 0.00 | 0.00 |
May | 1059.63 | 62.79 | 996.84 | 824.83 | 745.98 | 0.00 | 0.00 | 0.00 |
June | 1233.87 | 141.82 | 1092.05 | 1274.17 | 499.70 | 0.00 | 0.00 | 0.00 |
July | 1127.21 | 105.58 | 1021.64 | 1371.36 | 423.81 | 0.00 | 0.00 | 0.00 |
August | 903.24 | 24.21 | 879.03 | 1002.94 | 477.59 | 0.00 | 0.00 | 0.00 |
September | 676.46 | 0.24 | 676.22 | 599.02 | 707.99 | 0.00 | 0.00 | 0.00 |
October | 493.44 | 0.00 | 493.44 | 258.08 | 1014.96 | 0.00 | 0.00 | 0.00 |
November | 335.45 | 0.00 | 335.45 | 70.70 | 1447.53 | 0.00 | 0.00 | 0.00 |
December | 258.72 | 0.00 | 258.72 | 8.05 | 2044.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 696.96 | 28.42 | 668.54 | 525.34 | 1159.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 258.72 | 0.00 | 258.72 | 8.05 | 423.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1233.87 | 141.82 | 1092.05 | 1371.36 | 2420.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 472.31 | 216.53 | 255.77 | 264.41 | 1485.62 | 0.00 | 0.00 | 0.00 |
February | 738.73 | 366.76 | 371.97 | 578.05 | 1082.71 | 0.00 | 0.00 | 0.00 |
March | 993.29 | 411.00 | 582.30 | 841.27 | 884.05 | 0.00 | 0.00 | 0.00 |
April | 1267.34 | 628.08 | 639.26 | 1251.24 | 633.98 | 0.00 | 0.00 | 0.00 |
May | 1399.95 | 622.89 | 777.06 | 1469.13 | 502.80 | 0.00 | 0.00 | 0.00 |
June | 1812.05 | 932.48 | 879.57 | 2163.23 | 342.30 | 0.00 | 0.00 | 0.00 |
July | 1901.80 | 1075.13 | 826.66 | 2442.33 | 283.53 | 0.00 | 0.00 | 0.00 |
August | 1652.74 | 920.86 | 731.89 | 2075.43 | 316.46 | 0.00 | 0.00 | 0.00 |
September | 1169.15 | 603.51 | 565.64 | 1341.21 | 448.69 | 0.00 | 0.00 | 0.00 |
October | 838.81 | 425.93 | 412.87 | 819.68 | 639.97 | 0.00 | 0.00 | 0.00 |
November | 531.62 | 248.20 | 283.42 | 392.14 | 886.18 | 0.00 | 0.00 | 0.00 |
December | 392.10 | 168.41 | 223.69 | 209.98 | 1252.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1099.37 | 552.60 | 546.77 | 1157.29 | 728.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 392.10 | 168.41 | 223.69 | 209.98 | 283.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1901.80 | 1075.13 | 879.57 | 2442.33 | 1485.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2174.77 | 1553.26 | 621.51 | 2057.48 | 2081.07 | 0.00 | 0.00 | 0.00 |
February | 2769.54 | 1991.95 | 777.58 | 2876.71 | 1546.26 | 0.00 | 0.00 | 0.00 |
March | 2475.61 | 1390.18 | 1085.42 | 2564.57 | 1373.43 | 0.00 | 0.00 | 0.00 |
April | 1989.97 | 951.81 | 1038.16 | 2139.55 | 1021.09 | 0.00 | 0.00 | 0.00 |
May | 1768.04 | 587.21 | 1180.83 | 1928.91 | 812.30 | 0.00 | 0.00 | 0.00 |
June | 1756.73 | 512.34 | 1244.38 | 2169.15 | 574.36 | 0.00 | 0.00 | 0.00 |
July | 1893.93 | 699.61 | 1194.32 | 2602.39 | 463.68 | 0.00 | 0.00 | 0.00 |
August | 2250.81 | 1134.81 | 1115.99 | 3002.64 | 516.63 | 0.00 | 0.00 | 0.00 |
September | 2496.41 | 1529.63 | 966.78 | 3094.88 | 722.10 | 0.00 | 0.00 | 0.00 |
October | 2609.87 | 1804.69 | 805.18 | 2989.20 | 993.88 | 0.00 | 0.00 | 0.00 |
November | 2379.42 | 1723.56 | 655.87 | 2505.46 | 1280.89 | 0.00 | 0.00 | 0.00 |
December | 2068.08 | 1493.36 | 574.72 | 2011.04 | 1752.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2215.61 | 1276.31 | 939.30 | 2492.22 | 1093.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1756.73 | 512.34 | 574.72 | 1928.91 | 463.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2769.54 | 1991.95 | 1244.38 | 3094.88 | 2081.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 427.81 | 172.41 | 255.40 | 229.63 | 1548.36 | 0.00 | 0.00 | 0.00 |
February | 730.21 | 358.93 | 371.28 | 581.19 | 1111.56 | 0.00 | 0.00 | 0.00 |
March | 934.49 | 342.41 | 592.08 | 774.72 | 923.95 | 0.00 | 0.00 | 0.00 |
April | 1219.98 | 540.51 | 679.48 | 1218.08 | 672.16 | 0.00 | 0.00 | 0.00 |
May | 1509.03 | 688.20 | 820.83 | 1631.38 | 535.29 | 0.00 | 0.00 | 0.00 |
June | 1641.77 | 754.12 | 887.65 | 1968.51 | 377.79 | 0.00 | 0.00 | 0.00 |
July | 1681.81 | 849.84 | 831.97 | 2183.68 | 318.57 | 0.00 | 0.00 | 0.00 |
August | 1428.08 | 700.87 | 727.21 | 1807.30 | 342.19 | 0.00 | 0.00 | 0.00 |
September | 1148.80 | 580.79 | 568.02 | 1341.55 | 478.43 | 0.00 | 0.00 | 0.00 |
October | 821.08 | 407.95 | 413.13 | 821.45 | 673.46 | 0.00 | 0.00 | 0.00 |
November | 581.25 | 288.35 | 292.90 | 475.94 | 922.65 | 0.00 | 0.00 | 0.00 |
December | 390.70 | 164.90 | 225.80 | 222.17 | 1291.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1044.34 | 487.91 | 556.43 | 1107.33 | 765.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 390.70 | 164.90 | 225.80 | 222.17 | 318.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1681.81 | 849.84 | 887.65 | 2183.68 | 1548.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.84 | 0.00 | 102.84 | 4.33 | 818.87 | 0.00 | 0.00 | 0.00 |
February | 145.20 | 0.00 | 145.20 | 31.20 | 600.60 | 0.00 | 0.00 | 0.00 |
March | 235.87 | 0.00 | 235.87 | 99.19 | 476.46 | 0.00 | 0.00 | 0.00 |
April | 268.95 | 1.57 | 267.38 | 165.99 | 327.74 | 0.00 | 0.00 | 0.00 |
May | 353.19 | 20.93 | 332.26 | 287.01 | 250.27 | 0.00 | 0.00 | 0.00 |
June | 411.27 | 47.27 | 364.00 | 434.57 | 165.03 | 0.00 | 0.00 | 0.00 |
July | 375.72 | 35.19 | 340.53 | 464.42 | 139.80 | 0.00 | 0.00 | 0.00 |
August | 301.07 | 8.07 | 293.00 | 338.50 | 160.90 | 0.00 | 0.00 | 0.00 |
September | 225.48 | 0.08 | 225.40 | 199.33 | 249.43 | 0.00 | 0.00 | 0.00 |
October | 164.47 | 0.00 | 164.47 | 79.55 | 370.07 | 0.00 | 0.00 | 0.00 |
November | 111.81 | 0.00 | 111.81 | 20.58 | 520.03 | 0.00 | 0.00 | 0.00 |
December | 86.24 | 0.00 | 86.24 | 2.53 | 709.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.31 | 9.47 | 222.83 | 178.16 | 398.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.24 | 0.00 | 86.24 | 2.53 | 139.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 411.27 | 47.27 | 364.00 | 464.42 | 818.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.85 | 0.00 | 102.85 | 4.33 | 818.92 | 0.00 | 0.00 | 0.00 |
February | 145.21 | 0.00 | 145.21 | 31.20 | 600.63 | 0.00 | 0.00 | 0.00 |
March | 235.89 | 0.00 | 235.89 | 99.20 | 476.49 | 0.00 | 0.00 | 0.00 |
April | 268.96 | 1.57 | 267.39 | 166.00 | 327.76 | 0.00 | 0.00 | 0.00 |
May | 353.21 | 20.93 | 332.28 | 287.03 | 250.28 | 0.00 | 0.00 | 0.00 |
June | 411.30 | 47.28 | 364.02 | 434.59 | 165.04 | 0.00 | 0.00 | 0.00 |
July | 375.74 | 35.19 | 340.55 | 464.45 | 139.81 | 0.00 | 0.00 | 0.00 |
August | 301.09 | 8.07 | 293.01 | 338.52 | 160.91 | 0.00 | 0.00 | 0.00 |
September | 225.49 | 0.08 | 225.41 | 199.34 | 249.44 | 0.00 | 0.00 | 0.00 |
October | 164.48 | 0.00 | 164.48 | 79.55 | 370.09 | 0.00 | 0.00 | 0.00 |
November | 111.82 | 0.00 | 111.82 | 20.58 | 520.07 | 0.00 | 0.00 | 0.00 |
December | 86.24 | 0.00 | 86.24 | 2.53 | 709.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.32 | 9.47 | 222.85 | 178.17 | 398.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.24 | 0.00 | 86.24 | 2.53 | 139.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 411.30 | 47.28 | 364.02 | 464.45 | 818.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.85 | 0.00 | 102.85 | 4.33 | 818.92 | 0.00 | 0.00 | 0.00 |
February | 145.21 | 0.00 | 145.21 | 31.20 | 600.63 | 0.00 | 0.00 | 0.00 |
March | 235.89 | 0.00 | 235.89 | 99.20 | 476.49 | 0.00 | 0.00 | 0.00 |
April | 268.96 | 1.57 | 267.39 | 166.00 | 327.76 | 0.00 | 0.00 | 0.00 |
May | 353.21 | 20.93 | 332.28 | 287.03 | 250.28 | 0.00 | 0.00 | 0.00 |
June | 411.30 | 47.28 | 364.02 | 434.59 | 165.04 | 0.00 | 0.00 | 0.00 |
July | 375.74 | 35.19 | 340.55 | 464.45 | 139.81 | 0.00 | 0.00 | 0.00 |
August | 301.09 | 8.07 | 293.01 | 338.52 | 160.91 | 0.00 | 0.00 | 0.00 |
September | 225.49 | 0.08 | 225.41 | 199.34 | 249.44 | 0.00 | 0.00 | 0.00 |
October | 164.48 | 0.00 | 164.48 | 79.55 | 370.09 | 0.00 | 0.00 | 0.00 |
November | 111.82 | 0.00 | 111.82 | 20.58 | 520.07 | 0.00 | 0.00 | 0.00 |
December | 86.24 | 0.00 | 86.24 | 2.53 | 709.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.32 | 9.47 | 222.85 | 178.17 | 398.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.24 | 0.00 | 86.24 | 2.53 | 139.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 411.30 | 47.28 | 364.02 | 464.45 | 818.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 454.34 | 208.30 | 246.04 | 253.75 | 1457.19 | 0.00 | 0.00 | 0.00 |
February | 710.63 | 352.81 | 357.82 | 556.67 | 1071.11 | 0.00 | 0.00 | 0.00 |
March | 955.50 | 395.36 | 560.15 | 817.16 | 878.22 | 0.00 | 0.00 | 0.00 |
April | 1219.13 | 604.19 | 614.94 | 1218.48 | 626.20 | 0.00 | 0.00 | 0.00 |
May | 1346.69 | 599.19 | 747.50 | 1428.05 | 501.25 | 0.00 | 0.00 | 0.00 |
June | 1743.11 | 897.00 | 846.11 | 2094.98 | 338.79 | 0.00 | 0.00 | 0.00 |
July | 1829.45 | 1034.23 | 795.22 | 2360.11 | 283.98 | 0.00 | 0.00 | 0.00 |
August | 1589.87 | 885.82 | 704.05 | 2003.13 | 320.98 | 0.00 | 0.00 | 0.00 |
September | 1124.68 | 580.55 | 544.13 | 1286.77 | 470.23 | 0.00 | 0.00 | 0.00 |
October | 806.90 | 409.73 | 397.17 | 771.27 | 686.32 | 0.00 | 0.00 | 0.00 |
November | 511.40 | 238.75 | 272.64 | 363.43 | 927.04 | 0.00 | 0.00 | 0.00 |
December | 377.18 | 162.00 | 215.18 | 198.21 | 1258.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1057.55 | 531.58 | 525.97 | 1115.83 | 733.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 377.18 | 162.00 | 215.18 | 198.21 | 283.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1829.45 | 1034.23 | 846.11 | 2360.11 | 1457.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.96 | 8.24 | 9.73 | 10.03 | 57.62 | 0.00 | 0.00 | 0.00 |
February | 28.10 | 13.95 | 14.15 | 22.01 | 42.35 | 0.00 | 0.00 | 0.00 |
March | 37.78 | 15.63 | 22.15 | 32.31 | 34.72 | 0.00 | 0.00 | 0.00 |
April | 48.20 | 23.89 | 24.31 | 48.18 | 24.76 | 0.00 | 0.00 | 0.00 |
May | 53.25 | 23.69 | 29.56 | 56.46 | 19.82 | 0.00 | 0.00 | 0.00 |
June | 68.92 | 35.47 | 33.45 | 82.83 | 13.40 | 0.00 | 0.00 | 0.00 |
July | 72.33 | 40.89 | 31.44 | 93.32 | 11.23 | 0.00 | 0.00 | 0.00 |
August | 62.86 | 35.02 | 27.84 | 79.20 | 12.69 | 0.00 | 0.00 | 0.00 |
September | 44.47 | 22.95 | 21.51 | 50.88 | 18.59 | 0.00 | 0.00 | 0.00 |
October | 31.90 | 16.20 | 15.70 | 30.50 | 27.14 | 0.00 | 0.00 | 0.00 |
November | 20.22 | 9.44 | 10.78 | 14.37 | 36.65 | 0.00 | 0.00 | 0.00 |
December | 14.91 | 6.41 | 8.51 | 7.84 | 49.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.81 | 21.02 | 20.80 | 44.12 | 29.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.91 | 6.41 | 8.51 | 7.84 | 11.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 72.33 | 40.89 | 33.45 | 93.32 | 57.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 724.95 | 517.77 | 207.18 | 697.98 | 694.77 | 0.00 | 0.00 | 0.00 |
February | 923.21 | 664.01 | 259.20 | 972.90 | 531.40 | 0.00 | 0.00 | 0.00 |
March | 825.23 | 463.41 | 361.82 | 868.99 | 472.68 | 0.00 | 0.00 | 0.00 |
April | 663.34 | 317.28 | 346.06 | 727.74 | 346.11 | 0.00 | 0.00 | 0.00 |
May | 589.36 | 195.74 | 393.62 | 659.28 | 273.80 | 0.00 | 0.00 | 0.00 |
June | 585.59 | 170.79 | 414.81 | 736.67 | 191.00 | 0.00 | 0.00 | 0.00 |
July | 631.33 | 233.21 | 398.12 | 875.13 | 158.11 | 0.00 | 0.00 | 0.00 |
August | 750.29 | 378.28 | 372.01 | 1007.34 | 180.65 | 0.00 | 0.00 | 0.00 |
September | 832.16 | 509.89 | 322.27 | 1036.20 | 262.94 | 0.00 | 0.00 | 0.00 |
October | 869.98 | 601.58 | 268.40 | 996.46 | 372.20 | 0.00 | 0.00 | 0.00 |
November | 793.17 | 574.54 | 218.63 | 834.19 | 466.87 | 0.00 | 0.00 | 0.00 |
December | 689.38 | 497.80 | 191.58 | 674.49 | 604.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 738.56 | 425.45 | 313.11 | 839.60 | 379.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 585.59 | 170.79 | 191.58 | 659.28 | 158.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 923.21 | 664.01 | 414.81 | 1036.20 | 694.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 724.95 | 517.77 | 207.18 | 697.98 | 694.77 | 0.00 | 0.00 | 0.00 |
February | 923.21 | 664.01 | 259.20 | 972.90 | 531.40 | 0.00 | 0.00 | 0.00 |
March | 825.23 | 463.41 | 361.82 | 868.99 | 472.68 | 0.00 | 0.00 | 0.00 |
April | 663.34 | 317.28 | 346.06 | 727.74 | 346.11 | 0.00 | 0.00 | 0.00 |
May | 589.36 | 195.74 | 393.62 | 659.28 | 273.80 | 0.00 | 0.00 | 0.00 |
June | 585.59 | 170.79 | 414.81 | 736.67 | 191.00 | 0.00 | 0.00 | 0.00 |
July | 631.33 | 233.21 | 398.12 | 875.13 | 158.11 | 0.00 | 0.00 | 0.00 |
August | 750.29 | 378.28 | 372.01 | 1007.34 | 180.65 | 0.00 | 0.00 | 0.00 |
September | 832.16 | 509.89 | 322.27 | 1036.20 | 262.94 | 0.00 | 0.00 | 0.00 |
October | 869.98 | 601.58 | 268.40 | 996.46 | 372.20 | 0.00 | 0.00 | 0.00 |
November | 793.17 | 574.54 | 218.63 | 834.19 | 466.87 | 0.00 | 0.00 | 0.00 |
December | 689.38 | 497.80 | 191.58 | 674.49 | 604.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 738.56 | 425.45 | 313.11 | 839.60 | 379.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 585.59 | 170.79 | 191.58 | 659.28 | 158.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 923.21 | 664.01 | 414.81 | 1036.20 | 694.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 724.90 | 517.74 | 207.16 | 697.94 | 694.73 | 0.00 | 0.00 | 0.00 |
February | 923.15 | 663.96 | 259.19 | 972.84 | 531.37 | 0.00 | 0.00 | 0.00 |
March | 825.18 | 463.38 | 361.79 | 868.93 | 472.65 | 0.00 | 0.00 | 0.00 |
April | 663.30 | 317.26 | 346.04 | 727.69 | 346.08 | 0.00 | 0.00 | 0.00 |
May | 589.33 | 195.73 | 393.60 | 659.24 | 273.78 | 0.00 | 0.00 | 0.00 |
June | 585.56 | 170.78 | 414.78 | 736.62 | 190.99 | 0.00 | 0.00 | 0.00 |
July | 631.29 | 233.20 | 398.09 | 875.07 | 158.10 | 0.00 | 0.00 | 0.00 |
August | 750.24 | 378.26 | 371.98 | 1007.28 | 180.64 | 0.00 | 0.00 | 0.00 |
September | 832.11 | 509.86 | 322.25 | 1036.13 | 262.93 | 0.00 | 0.00 | 0.00 |
October | 869.93 | 601.54 | 268.38 | 996.40 | 372.18 | 0.00 | 0.00 | 0.00 |
November | 793.12 | 574.50 | 218.61 | 834.13 | 466.84 | 0.00 | 0.00 | 0.00 |
December | 689.34 | 497.77 | 191.57 | 674.44 | 604.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 738.51 | 425.42 | 313.09 | 839.55 | 378.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 585.56 | 170.78 | 191.57 | 659.24 | 158.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 923.15 | 663.96 | 414.78 | 1036.13 | 694.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 411.54 | 165.85 | 245.69 | 222.71 | 1514.26 | 0.00 | 0.00 | 0.00 |
February | 702.43 | 345.28 | 357.15 | 564.86 | 1101.02 | 0.00 | 0.00 | 0.00 |
March | 898.94 | 329.38 | 569.56 | 758.00 | 914.49 | 0.00 | 0.00 | 0.00 |
April | 1173.57 | 519.94 | 653.63 | 1189.52 | 660.18 | 0.00 | 0.00 | 0.00 |
May | 1451.63 | 662.02 | 789.61 | 1585.36 | 535.15 | 0.00 | 0.00 | 0.00 |
June | 1579.31 | 725.43 | 853.88 | 1907.96 | 374.07 | 0.00 | 0.00 | 0.00 |
July | 1617.83 | 817.51 | 800.32 | 2109.90 | 318.14 | 0.00 | 0.00 | 0.00 |
August | 1373.76 | 674.21 | 699.55 | 1743.76 | 345.99 | 0.00 | 0.00 | 0.00 |
September | 1105.10 | 558.69 | 546.41 | 1287.50 | 501.27 | 0.00 | 0.00 | 0.00 |
October | 789.84 | 392.43 | 397.41 | 777.10 | 720.25 | 0.00 | 0.00 | 0.00 |
November | 559.13 | 277.38 | 281.76 | 450.28 | 963.46 | 0.00 | 0.00 | 0.00 |
December | 375.84 | 158.63 | 217.21 | 213.18 | 1296.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1004.61 | 469.35 | 535.26 | 1070.09 | 769.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 375.84 | 158.63 | 217.21 | 213.18 | 318.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1617.83 | 817.51 | 853.88 | 2109.90 | 1514.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.27 | 6.56 | 9.71 | 8.81 | 59.87 | 0.00 | 0.00 | 0.00 |
February | 27.77 | 13.65 | 14.12 | 22.33 | 43.53 | 0.00 | 0.00 | 0.00 |
March | 35.54 | 13.02 | 22.52 | 29.97 | 36.16 | 0.00 | 0.00 | 0.00 |
April | 46.40 | 20.56 | 25.84 | 47.03 | 26.10 | 0.00 | 0.00 | 0.00 |
May | 57.40 | 26.18 | 31.22 | 62.68 | 21.16 | 0.00 | 0.00 | 0.00 |
June | 62.44 | 28.68 | 33.76 | 75.44 | 14.79 | 0.00 | 0.00 | 0.00 |
July | 63.97 | 32.32 | 31.64 | 83.42 | 12.58 | 0.00 | 0.00 | 0.00 |
August | 54.32 | 26.66 | 27.66 | 68.95 | 13.68 | 0.00 | 0.00 | 0.00 |
September | 43.69 | 22.09 | 21.60 | 50.91 | 19.82 | 0.00 | 0.00 | 0.00 |
October | 31.23 | 15.52 | 15.71 | 30.73 | 28.48 | 0.00 | 0.00 | 0.00 |
November | 22.11 | 10.97 | 11.14 | 17.80 | 38.09 | 0.00 | 0.00 | 0.00 |
December | 14.86 | 6.27 | 8.59 | 8.43 | 51.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.72 | 18.56 | 21.16 | 42.31 | 30.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.86 | 6.27 | 8.59 | 8.43 | 12.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.97 | 32.32 | 33.76 | 83.42 | 59.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 308.53 | 0.00 | 308.53 | 12.21 | 2487.30 | 0.00 | 0.00 | 0.00 |
February | 435.63 | 0.00 | 435.63 | 85.38 | 1838.11 | 0.00 | 0.00 | 0.00 |
March | 707.66 | 0.00 | 707.66 | 271.26 | 1477.61 | 0.00 | 0.00 | 0.00 |
April | 806.88 | 4.71 | 802.17 | 450.00 | 1051.61 | 0.00 | 0.00 | 0.00 |
May | 1059.63 | 62.79 | 996.84 | 808.57 | 791.79 | 0.00 | 0.00 | 0.00 |
June | 1233.87 | 141.82 | 1092.05 | 1265.74 | 520.19 | 0.00 | 0.00 | 0.00 |
July | 1127.21 | 105.58 | 1021.64 | 1368.53 | 437.14 | 0.00 | 0.00 | 0.00 |
August | 903.24 | 24.21 | 879.03 | 997.17 | 499.33 | 0.00 | 0.00 | 0.00 |
September | 676.46 | 0.24 | 676.22 | 586.25 | 755.89 | 0.00 | 0.00 | 0.00 |
October | 493.44 | 0.00 | 493.44 | 235.80 | 1098.55 | 0.00 | 0.00 | 0.00 |
November | 335.45 | 0.00 | 335.45 | 60.80 | 1545.63 | 0.00 | 0.00 | 0.00 |
December | 258.72 | 0.00 | 258.72 | 6.90 | 2124.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 696.96 | 28.42 | 668.54 | 515.04 | 1216.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 258.72 | 0.00 | 258.72 | 6.90 | 437.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1233.87 | 141.82 | 1092.05 | 1368.53 | 2487.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 472.31 | 216.53 | 255.77 | 259.32 | 1525.20 | 0.00 | 0.00 | 0.00 |
February | 738.73 | 366.76 | 371.97 | 567.37 | 1126.49 | 0.00 | 0.00 | 0.00 |
March | 993.29 | 411.00 | 582.30 | 828.94 | 928.72 | 0.00 | 0.00 | 0.00 |
April | 1267.34 | 628.08 | 639.26 | 1239.83 | 671.44 | 0.00 | 0.00 | 0.00 |
May | 1399.95 | 622.89 | 777.06 | 1461.42 | 531.07 | 0.00 | 0.00 | 0.00 |
June | 1812.05 | 932.48 | 879.57 | 2161.34 | 354.93 | 0.00 | 0.00 | 0.00 |
July | 1901.80 | 1075.13 | 826.66 | 2443.47 | 291.93 | 0.00 | 0.00 | 0.00 |
August | 1652.74 | 920.86 | 731.89 | 2074.37 | 329.07 | 0.00 | 0.00 | 0.00 |
September | 1169.15 | 603.51 | 565.64 | 1333.96 | 474.62 | 0.00 | 0.00 | 0.00 |
October | 838.81 | 425.93 | 412.87 | 802.95 | 687.89 | 0.00 | 0.00 | 0.00 |
November | 531.62 | 248.20 | 283.42 | 378.32 | 943.39 | 0.00 | 0.00 | 0.00 |
December | 392.10 | 168.41 | 223.69 | 204.21 | 1301.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1099.37 | 552.60 | 546.77 | 1149.60 | 762.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 392.10 | 168.41 | 223.69 | 204.21 | 291.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1901.80 | 1075.13 | 879.57 | 2443.47 | 1525.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2174.77 | 1553.26 | 621.51 | 2044.92 | 2144.68 | 0.00 | 0.00 | 0.00 |
February | 2769.54 | 1991.95 | 777.58 | 2859.53 | 1615.78 | 0.00 | 0.00 | 0.00 |
March | 2475.61 | 1390.18 | 1085.42 | 2548.88 | 1445.86 | 0.00 | 0.00 | 0.00 |
April | 1989.97 | 951.81 | 1038.16 | 2124.69 | 1084.03 | 0.00 | 0.00 | 0.00 |
May | 1768.04 | 587.21 | 1180.83 | 1918.53 | 861.00 | 0.00 | 0.00 | 0.00 |
June | 1756.73 | 512.34 | 1244.38 | 2165.95 | 600.89 | 0.00 | 0.00 | 0.00 |
July | 1893.93 | 699.61 | 1194.32 | 2602.92 | 481.14 | 0.00 | 0.00 | 0.00 |
August | 2250.81 | 1134.81 | 1115.99 | 3001.79 | 540.74 | 0.00 | 0.00 | 0.00 |
September | 2496.41 | 1529.63 | 966.78 | 3087.20 | 766.75 | 0.00 | 0.00 | 0.00 |
October | 2609.87 | 1804.69 | 805.18 | 2968.71 | 1069.08 | 0.00 | 0.00 | 0.00 |
November | 2379.42 | 1723.56 | 655.87 | 2478.62 | 1365.54 | 0.00 | 0.00 | 0.00 |
December | 2068.08 | 1493.36 | 574.72 | 1992.80 | 1828.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2215.61 | 1276.31 | 939.30 | 2479.99 | 1148.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1756.73 | 512.34 | 574.72 | 1918.53 | 481.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2769.54 | 1991.95 | 1244.38 | 3087.20 | 2144.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 427.81 | 172.41 | 255.40 | 226.67 | 1589.11 | 0.00 | 0.00 | 0.00 |
February | 730.21 | 358.93 | 371.28 | 574.04 | 1158.68 | 0.00 | 0.00 | 0.00 |
March | 934.49 | 342.41 | 592.08 | 766.09 | 971.40 | 0.00 | 0.00 | 0.00 |
April | 1219.98 | 540.51 | 679.48 | 1207.44 | 712.89 | 0.00 | 0.00 | 0.00 |
May | 1509.03 | 688.20 | 820.83 | 1624.07 | 566.73 | 0.00 | 0.00 | 0.00 |
June | 1641.77 | 754.12 | 887.65 | 1965.49 | 394.68 | 0.00 | 0.00 | 0.00 |
July | 1681.81 | 849.84 | 831.97 | 2183.10 | 329.77 | 0.00 | 0.00 | 0.00 |
August | 1428.08 | 700.87 | 727.21 | 1804.38 | 358.02 | 0.00 | 0.00 | 0.00 |
September | 1148.80 | 580.79 | 568.02 | 1334.02 | 508.96 | 0.00 | 0.00 | 0.00 |
October | 821.08 | 407.95 | 413.13 | 807.57 | 725.90 | 0.00 | 0.00 | 0.00 |
November | 581.25 | 288.35 | 292.90 | 465.82 | 982.84 | 0.00 | 0.00 | 0.00 |
December | 390.70 | 164.90 | 225.80 | 218.16 | 1342.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1044.34 | 487.91 | 556.43 | 1100.79 | 802.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 390.70 | 164.90 | 225.80 | 218.16 | 329.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1681.81 | 849.84 | 887.65 | 2183.10 | 1589.11 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.826371E+09 | 0.00 | 0.826371E+09 | 39778091.22 | 0.648422E+10 |
February | 0.105387E+10 | 0.00 | 0.105387E+10 | 0.228418E+09 | 0.427087E+10 |
March | 0.189539E+10 | 0.00 | 0.189539E+10 | 0.765927E+09 | 0.376100E+10 |
April | 0.209143E+10 | 12205121.80 | 0.207923E+10 | 0.121304E+10 | 0.255729E+10 |
May | 0.283810E+10 | 0.168175E+09 | 0.266993E+10 | 0.220922E+10 | 0.199804E+10 |
June | 0.319820E+10 | 0.367606E+09 | 0.283060E+10 | 0.330266E+10 | 0.129522E+10 |
July | 0.301912E+10 | 0.282777E+09 | 0.273635E+10 | 0.367305E+10 | 0.113513E+10 |
August | 0.241924E+10 | 64846941.02 | 0.235439E+10 | 0.268627E+10 | 0.127916E+10 |
September | 0.175340E+10 | 629213.91 | 0.175277E+10 | 0.155265E+10 | 0.183511E+10 |
October | 0.132163E+10 | 0.00 | 0.132163E+10 | 0.691253E+09 | 0.271848E+10 |
November | 0.869477E+09 | 0.00 | 0.869477E+09 | 0.183251E+09 | 0.375200E+10 |
December | 0.692959E+09 | 0.00 | 0.692959E+09 | 21562486.52 | 0.547485E+10 |
Annual Sum or Average | 0.219792E+11 | 0.896240E+09 | 0.210830E+11 | 0.165671E+11 | 0.365614E+11 |
Minimum of Months | 0.692959E+09 | 0.00 | 0.692959E+09 | 21562486.52 | 0.113513E+10 |
Maximum of Months | 0.319820E+10 | 0.367606E+09 | 0.283060E+10 | 0.367305E+10 | 0.648422E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126503E+10 | 0.579964E+09 | 0.685066E+09 | 0.708200E+09 | 0.397909E+10 |
February | 0.178714E+10 | 0.887271E+09 | 0.899870E+09 | 0.139842E+10 | 0.261928E+10 |
March | 0.266043E+10 | 0.110081E+10 | 0.155962E+10 | 0.225325E+10 | 0.236784E+10 |
April | 0.328495E+10 | 0.162800E+10 | 0.165696E+10 | 0.324322E+10 | 0.164326E+10 |
May | 0.374962E+10 | 0.166834E+10 | 0.208128E+10 | 0.393491E+10 | 0.134669E+10 |
June | 0.469683E+10 | 0.241698E+10 | 0.227985E+10 | 0.560708E+10 | 0.887245E+09 |
July | 0.509377E+10 | 0.287964E+10 | 0.221413E+10 | 0.654153E+10 | 0.759395E+09 |
August | 0.442671E+10 | 0.246642E+10 | 0.196029E+10 | 0.555883E+10 | 0.847599E+09 |
September | 0.303045E+10 | 0.156430E+10 | 0.146615E+10 | 0.347642E+10 | 0.116301E+10 |
October | 0.224666E+10 | 0.114082E+10 | 0.110584E+10 | 0.219543E+10 | 0.171409E+10 |
November | 0.137796E+10 | 0.643324E+09 | 0.734635E+09 | 0.101644E+10 | 0.229697E+10 |
December | 0.105020E+10 | 0.451063E+09 | 0.599139E+09 | 0.562417E+09 | 0.335499E+10 |
Annual Sum or Average | 0.346698E+11 | 0.174269E+11 | 0.172428E+11 | 0.364961E+11 | 0.229795E+11 |
Minimum of Months | 0.105020E+10 | 0.451063E+09 | 0.599139E+09 | 0.562417E+09 | 0.759395E+09 |
Maximum of Months | 0.509377E+10 | 0.287964E+10 | 0.227985E+10 | 0.654153E+10 | 0.397909E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.582490E+10 | 0.416026E+10 | 0.166464E+10 | 0.551074E+10 | 0.557393E+10 |
February | 0.670006E+10 | 0.481893E+10 | 0.188113E+10 | 0.695934E+10 | 0.374072E+10 |
March | 0.663066E+10 | 0.372347E+10 | 0.290719E+10 | 0.686893E+10 | 0.367861E+10 |
April | 0.515801E+10 | 0.246710E+10 | 0.269091E+10 | 0.554571E+10 | 0.264667E+10 |
May | 0.473552E+10 | 0.157279E+10 | 0.316273E+10 | 0.516638E+10 | 0.217567E+10 |
June | 0.455344E+10 | 0.132800E+10 | 0.322545E+10 | 0.562245E+10 | 0.148875E+10 |
July | 0.507270E+10 | 0.187383E+10 | 0.319887E+10 | 0.697024E+10 | 0.124193E+10 |
August | 0.602857E+10 | 0.303949E+10 | 0.298908E+10 | 0.804227E+10 | 0.138375E+10 |
September | 0.647071E+10 | 0.396480E+10 | 0.250590E+10 | 0.802194E+10 | 0.187167E+10 |
October | 0.699027E+10 | 0.483367E+10 | 0.215659E+10 | 0.800627E+10 | 0.266200E+10 |
November | 0.616747E+10 | 0.446746E+10 | 0.170001E+10 | 0.649416E+10 | 0.332006E+10 |
December | 0.553915E+10 | 0.399982E+10 | 0.153933E+10 | 0.538637E+10 | 0.469372E+10 |
Annual Sum or Average | 0.698715E+11 | 0.402496E+11 | 0.296218E+11 | 0.785948E+11 | 0.344775E+11 |
Minimum of Months | 0.455344E+10 | 0.132800E+10 | 0.153933E+10 | 0.516638E+10 | 0.124193E+10 |
Maximum of Months | 0.699027E+10 | 0.483367E+10 | 0.322545E+10 | 0.804227E+10 | 0.557393E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114585E+10 | 0.461786E+09 | 0.684066E+09 | 0.615051E+09 | 0.414712E+10 |
February | 0.176653E+10 | 0.868335E+09 | 0.898190E+09 | 0.140601E+10 | 0.268908E+10 |
March | 0.250294E+10 | 0.917114E+09 | 0.158583E+10 | 0.207501E+10 | 0.247472E+10 |
April | 0.316220E+10 | 0.140100E+10 | 0.176120E+10 | 0.315726E+10 | 0.174224E+10 |
May | 0.404179E+10 | 0.184327E+10 | 0.219852E+10 | 0.436950E+10 | 0.143373E+10 |
June | 0.425547E+10 | 0.195469E+10 | 0.230078E+10 | 0.510237E+10 | 0.979235E+09 |
July | 0.450456E+10 | 0.227622E+10 | 0.222835E+10 | 0.584878E+10 | 0.853266E+09 |
August | 0.382498E+10 | 0.187722E+10 | 0.194777E+10 | 0.484067E+10 | 0.916529E+09 |
September | 0.297770E+10 | 0.150540E+10 | 0.147230E+10 | 0.347730E+10 | 0.124010E+10 |
October | 0.219918E+10 | 0.109265E+10 | 0.110653E+10 | 0.220018E+10 | 0.180381E+10 |
November | 0.150659E+10 | 0.747396E+09 | 0.759194E+09 | 0.123365E+10 | 0.239151E+10 |
December | 0.104646E+10 | 0.441681E+09 | 0.604780E+09 | 0.595059E+09 | 0.346040E+10 |
Annual Sum or Average | 0.329343E+11 | 0.153868E+11 | 0.175475E+11 | 0.349208E+11 | 0.241317E+11 |
Minimum of Months | 0.104646E+10 | 0.441681E+09 | 0.604780E+09 | 0.595059E+09 | 0.853266E+09 |
Maximum of Months | 0.450456E+10 | 0.227622E+10 | 0.230078E+10 | 0.584878E+10 | 0.414712E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275444E+09 | 0.00 | 0.275444E+09 | 11608383.95 | 0.219326E+10 |
February | 0.351273E+09 | 0.00 | 0.351273E+09 | 75476216.82 | 0.145296E+10 |
March | 0.631767E+09 | 0.00 | 0.631767E+09 | 0.265674E+09 | 0.127616E+10 |
April | 0.697111E+09 | 4068181.45 | 0.693042E+09 | 0.430240E+09 | 0.849505E+09 |
May | 0.945989E+09 | 56055681.31 | 0.889933E+09 | 0.768726E+09 | 0.670314E+09 |
June | 0.106602E+10 | 0.122530E+09 | 0.943488E+09 | 0.112640E+10 | 0.427761E+09 |
July | 0.100633E+10 | 94254631.29 | 0.912073E+09 | 0.124391E+10 | 0.374449E+09 |
August | 0.806375E+09 | 21614624.33 | 0.784761E+09 | 0.906638E+09 | 0.430953E+09 |
September | 0.584438E+09 | 209728.05 | 0.584228E+09 | 0.516656E+09 | 0.646510E+09 |
October | 0.440524E+09 | 0.00 | 0.440524E+09 | 0.213063E+09 | 0.991191E+09 |
November | 0.289812E+09 | 0.00 | 0.289812E+09 | 53343566.08 | 0.134793E+10 |
December | 0.230975E+09 | 0.00 | 0.230975E+09 | 6788056.92 | 0.189988E+10 |
Annual Sum or Average | 0.732605E+10 | 0.298732E+09 | 0.702732E+10 | 0.561852E+10 | 0.125609E+11 |
Minimum of Months | 0.230975E+09 | 0.00 | 0.230975E+09 | 6788056.92 | 0.374449E+09 |
Maximum of Months | 0.106602E+10 | 0.122530E+09 | 0.943488E+09 | 0.124391E+10 | 0.219326E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275461E+09 | 0.00 | 0.275461E+09 | 11609117.58 | 0.219339E+10 |
February | 0.351295E+09 | 0.00 | 0.351295E+09 | 75480986.79 | 0.145306E+10 |
March | 0.631807E+09 | 0.00 | 0.631807E+09 | 0.265690E+09 | 0.127624E+10 |
April | 0.697155E+09 | 4068438.55 | 0.693086E+09 | 0.430267E+09 | 0.849559E+09 |
May | 0.946048E+09 | 56059223.94 | 0.889989E+09 | 0.768774E+09 | 0.670356E+09 |
June | 0.106608E+10 | 0.122537E+09 | 0.943548E+09 | 0.112647E+10 | 0.427789E+09 |
July | 0.100639E+10 | 94260588.03 | 0.912130E+09 | 0.124398E+10 | 0.374473E+09 |
August | 0.806426E+09 | 21615990.33 | 0.784810E+09 | 0.906695E+09 | 0.430980E+09 |
September | 0.584475E+09 | 209741.30 | 0.584265E+09 | 0.516689E+09 | 0.646551E+09 |
October | 0.440552E+09 | 0.00 | 0.440552E+09 | 0.213076E+09 | 0.991254E+09 |
November | 0.289830E+09 | 0.00 | 0.289830E+09 | 53346937.31 | 0.134801E+10 |
December | 0.230990E+09 | 0.00 | 0.230990E+09 | 6788485.91 | 0.190000E+10 |
Annual Sum or Average | 0.732652E+10 | 0.298751E+09 | 0.702776E+10 | 0.561887E+10 | 0.125617E+11 |
Minimum of Months | 0.230990E+09 | 0.00 | 0.230990E+09 | 6788485.91 | 0.374473E+09 |
Maximum of Months | 0.106608E+10 | 0.122537E+09 | 0.943548E+09 | 0.124398E+10 | 0.219339E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275461E+09 | 0.00 | 0.275461E+09 | 11609117.58 | 0.219339E+10 |
February | 0.351295E+09 | 0.00 | 0.351295E+09 | 75480986.79 | 0.145306E+10 |
March | 0.631807E+09 | 0.00 | 0.631807E+09 | 0.265690E+09 | 0.127624E+10 |
April | 0.697155E+09 | 4068438.55 | 0.693086E+09 | 0.430267E+09 | 0.849559E+09 |
May | 0.946048E+09 | 56059223.94 | 0.889989E+09 | 0.768774E+09 | 0.670356E+09 |
June | 0.106608E+10 | 0.122537E+09 | 0.943548E+09 | 0.112647E+10 | 0.427789E+09 |
July | 0.100639E+10 | 94260588.03 | 0.912130E+09 | 0.124398E+10 | 0.374473E+09 |
August | 0.806426E+09 | 21615990.33 | 0.784810E+09 | 0.906695E+09 | 0.430980E+09 |
September | 0.584475E+09 | 209741.30 | 0.584265E+09 | 0.516689E+09 | 0.646551E+09 |
October | 0.440552E+09 | 0.00 | 0.440552E+09 | 0.213076E+09 | 0.991254E+09 |
November | 0.289830E+09 | 0.00 | 0.289830E+09 | 53346937.31 | 0.134801E+10 |
December | 0.230990E+09 | 0.00 | 0.230990E+09 | 6788485.91 | 0.190000E+10 |
Annual Sum or Average | 0.732652E+10 | 0.298751E+09 | 0.702776E+10 | 0.561887E+10 | 0.125617E+11 |
Minimum of Months | 0.230990E+09 | 0.00 | 0.230990E+09 | 6788485.91 | 0.374473E+09 |
Maximum of Months | 0.106608E+10 | 0.122537E+09 | 0.943548E+09 | 0.124398E+10 | 0.219339E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121690E+10 | 0.557899E+09 | 0.659005E+09 | 0.679642E+09 | 0.390294E+10 |
February | 0.171915E+10 | 0.853514E+09 | 0.865638E+09 | 0.134670E+10 | 0.259124E+10 |
March | 0.255922E+10 | 0.105893E+10 | 0.150029E+10 | 0.218869E+10 | 0.235224E+10 |
April | 0.315998E+10 | 0.156606E+10 | 0.159393E+10 | 0.315831E+10 | 0.162312E+10 |
May | 0.360697E+10 | 0.160487E+10 | 0.200210E+10 | 0.382488E+10 | 0.134256E+10 |
June | 0.451815E+10 | 0.232502E+10 | 0.219312E+10 | 0.543018E+10 | 0.878131E+09 |
July | 0.489999E+10 | 0.277008E+10 | 0.212991E+10 | 0.632133E+10 | 0.760617E+09 |
August | 0.425831E+10 | 0.237259E+10 | 0.188572E+10 | 0.536520E+10 | 0.859719E+09 |
September | 0.291516E+10 | 0.150479E+10 | 0.141037E+10 | 0.333532E+10 | 0.121884E+10 |
October | 0.216119E+10 | 0.109741E+10 | 0.106378E+10 | 0.206576E+10 | 0.183824E+10 |
November | 0.132554E+10 | 0.618849E+09 | 0.706688E+09 | 0.942001E+09 | 0.240288E+10 |
December | 0.101025E+10 | 0.433902E+09 | 0.576347E+09 | 0.530889E+09 | 0.337051E+10 |
Annual Sum or Average | 0.333508E+11 | 0.167639E+11 | 0.165869E+11 | 0.351889E+11 | 0.231410E+11 |
Minimum of Months | 0.101025E+10 | 0.433902E+09 | 0.576347E+09 | 0.530889E+09 | 0.760617E+09 |
Maximum of Months | 0.489999E+10 | 0.277008E+10 | 0.219312E+10 | 0.632133E+10 | 0.390294E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48115300.62 | 22058822.69 | 26056477.93 | 26872451.09 | 0.154319E+09 |
February | 67973726.17 | 33747189.78 | 34226536.39 | 53247451.13 | 0.102455E+09 |
March | 0.101189E+09 | 41869148.32 | 59320263.08 | 86538836.15 | 93005261.66 |
April | 0.124943E+09 | 61920525.37 | 63022430.98 | 0.124877E+09 | 64176794.02 |
May | 0.142616E+09 | 63455013.33 | 79161367.93 | 0.151232E+09 | 53083592.21 |
June | 0.178644E+09 | 91929394.42 | 86714152.14 | 0.214704E+09 | 34720526.10 |
July | 0.193741E+09 | 0.109527E+09 | 84214614.64 | 0.249940E+09 | 30074094.47 |
August | 0.168370E+09 | 93809897.34 | 74559739.09 | 0.212135E+09 | 33992513.11 |
September | 0.115263E+09 | 59497982.38 | 55764905.85 | 0.131876E+09 | 48191742.54 |
October | 85451568.25 | 43390786.92 | 42060781.34 | 81678235.45 | 72682426.12 |
November | 52410537.60 | 24468723.25 | 27941814.35 | 37245884.36 | 95007746.16 |
December | 39944330.08 | 17156108.03 | 22788222.06 | 20990867.15 | 0.133267E+09 |
Annual Sum or Average | 0.131866E+10 | 0.662830E+09 | 0.655831E+09 | 0.139134E+10 | 0.914975E+09 |
Minimum of Months | 39944330.08 | 17156108.03 | 22788222.06 | 20990867.15 | 30074094.47 |
Maximum of Months | 0.193741E+09 | 0.109527E+09 | 86714152.14 | 0.249940E+09 | 0.154319E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194170E+10 | 0.138680E+10 | 0.554898E+09 | 0.186947E+10 | 0.186088E+10 |
February | 0.223342E+10 | 0.160636E+10 | 0.627062E+09 | 0.235365E+10 | 0.128556E+10 |
March | 0.221029E+10 | 0.124120E+10 | 0.969092E+09 | 0.232749E+10 | 0.126602E+10 |
April | 0.171939E+10 | 0.822395E+09 | 0.896994E+09 | 0.188629E+10 | 0.897107E+09 |
May | 0.157855E+10 | 0.524281E+09 | 0.105427E+10 | 0.176582E+10 | 0.733343E+09 |
June | 0.151786E+10 | 0.442680E+09 | 0.107518E+10 | 0.190945E+10 | 0.495072E+09 |
July | 0.169095E+10 | 0.624631E+09 | 0.106632E+10 | 0.234394E+10 | 0.423483E+09 |
August | 0.200958E+10 | 0.101320E+10 | 0.996387E+09 | 0.269806E+10 | 0.483849E+09 |
September | 0.215697E+10 | 0.132164E+10 | 0.835324E+09 | 0.268582E+10 | 0.681553E+09 |
October | 0.233016E+10 | 0.161128E+10 | 0.718885E+09 | 0.266893E+10 | 0.996912E+09 |
November | 0.205589E+10 | 0.148920E+10 | 0.566686E+09 | 0.216221E+10 | 0.121013E+10 |
December | 0.184644E+10 | 0.133332E+10 | 0.513125E+09 | 0.180654E+10 | 0.161875E+10 |
Annual Sum or Average | 0.232912E+11 | 0.134170E+11 | 0.987422E+10 | 0.264777E+11 | 0.119527E+11 |
Minimum of Months | 0.151786E+10 | 0.442680E+09 | 0.513125E+09 | 0.176582E+10 | 0.423483E+09 |
Maximum of Months | 0.233016E+10 | 0.161128E+10 | 0.107518E+10 | 0.269806E+10 | 0.186088E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194170E+10 | 0.138680E+10 | 0.554898E+09 | 0.186947E+10 | 0.186088E+10 |
February | 0.223342E+10 | 0.160636E+10 | 0.627062E+09 | 0.235365E+10 | 0.128556E+10 |
March | 0.221029E+10 | 0.124120E+10 | 0.969092E+09 | 0.232749E+10 | 0.126602E+10 |
April | 0.171939E+10 | 0.822395E+09 | 0.896994E+09 | 0.188629E+10 | 0.897107E+09 |
May | 0.157855E+10 | 0.524281E+09 | 0.105427E+10 | 0.176582E+10 | 0.733343E+09 |
June | 0.151786E+10 | 0.442680E+09 | 0.107518E+10 | 0.190945E+10 | 0.495072E+09 |
July | 0.169095E+10 | 0.624631E+09 | 0.106632E+10 | 0.234394E+10 | 0.423483E+09 |
August | 0.200958E+10 | 0.101320E+10 | 0.996387E+09 | 0.269806E+10 | 0.483849E+09 |
September | 0.215697E+10 | 0.132164E+10 | 0.835324E+09 | 0.268582E+10 | 0.681553E+09 |
October | 0.233016E+10 | 0.161128E+10 | 0.718885E+09 | 0.266893E+10 | 0.996912E+09 |
November | 0.205589E+10 | 0.148920E+10 | 0.566686E+09 | 0.216221E+10 | 0.121013E+10 |
December | 0.184644E+10 | 0.133332E+10 | 0.513125E+09 | 0.180654E+10 | 0.161875E+10 |
Annual Sum or Average | 0.232912E+11 | 0.134170E+11 | 0.987422E+10 | 0.264777E+11 | 0.119527E+11 |
Minimum of Months | 0.151786E+10 | 0.442680E+09 | 0.513125E+09 | 0.176582E+10 | 0.423483E+09 |
Maximum of Months | 0.233016E+10 | 0.161128E+10 | 0.107518E+10 | 0.269806E+10 | 0.186088E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194157E+10 | 0.138671E+10 | 0.554863E+09 | 0.186935E+10 | 0.186076E+10 |
February | 0.223328E+10 | 0.160626E+10 | 0.627023E+09 | 0.235350E+10 | 0.128548E+10 |
March | 0.221015E+10 | 0.124112E+10 | 0.969031E+09 | 0.232734E+10 | 0.126594E+10 |
April | 0.171928E+10 | 0.822343E+09 | 0.896938E+09 | 0.188618E+10 | 0.897050E+09 |
May | 0.157845E+10 | 0.524248E+09 | 0.105421E+10 | 0.176571E+10 | 0.733297E+09 |
June | 0.151776E+10 | 0.442652E+09 | 0.107511E+10 | 0.190932E+10 | 0.495041E+09 |
July | 0.169084E+10 | 0.624592E+09 | 0.106625E+10 | 0.234379E+10 | 0.423456E+09 |
August | 0.200946E+10 | 0.101313E+10 | 0.996324E+09 | 0.269789E+10 | 0.483818E+09 |
September | 0.215683E+10 | 0.132156E+10 | 0.835272E+09 | 0.268565E+10 | 0.681510E+09 |
October | 0.233002E+10 | 0.161118E+10 | 0.718839E+09 | 0.266876E+10 | 0.996849E+09 |
November | 0.205576E+10 | 0.148911E+10 | 0.566650E+09 | 0.216208E+10 | 0.121005E+10 |
December | 0.184633E+10 | 0.133323E+10 | 0.513092E+09 | 0.180643E+10 | 0.161864E+10 |
Annual Sum or Average | 0.232897E+11 | 0.134161E+11 | 0.987360E+10 | 0.264760E+11 | 0.119519E+11 |
Minimum of Months | 0.151776E+10 | 0.442652E+09 | 0.513092E+09 | 0.176571E+10 | 0.423456E+09 |
Maximum of Months | 0.233002E+10 | 0.161118E+10 | 0.107511E+10 | 0.269789E+10 | 0.186076E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110226E+10 | 0.444217E+09 | 0.658043E+09 | 0.596508E+09 | 0.405579E+10 |
February | 0.169932E+10 | 0.835300E+09 | 0.864022E+09 | 0.136651E+10 | 0.266360E+10 |
March | 0.240773E+10 | 0.882223E+09 | 0.152550E+10 | 0.203024E+10 | 0.244938E+10 |
April | 0.304190E+10 | 0.134770E+10 | 0.169420E+10 | 0.308324E+10 | 0.171119E+10 |
May | 0.388803E+10 | 0.177314E+10 | 0.211489E+10 | 0.424622E+10 | 0.143336E+10 |
June | 0.409358E+10 | 0.188033E+10 | 0.221326E+10 | 0.494544E+10 | 0.969587E+09 |
July | 0.433320E+10 | 0.218962E+10 | 0.214358E+10 | 0.565117E+10 | 0.852107E+09 |
August | 0.367947E+10 | 0.180580E+10 | 0.187367E+10 | 0.467049E+10 | 0.926704E+09 |
September | 0.286442E+10 | 0.144813E+10 | 0.141629E+10 | 0.333719E+10 | 0.129928E+10 |
October | 0.211552E+10 | 0.105108E+10 | 0.106443E+10 | 0.208139E+10 | 0.192913E+10 |
November | 0.144927E+10 | 0.718961E+09 | 0.730313E+09 | 0.116713E+10 | 0.249728E+10 |
December | 0.100665E+10 | 0.424877E+09 | 0.581773E+09 | 0.570976E+09 | 0.347354E+10 |
Annual Sum or Average | 0.316814E+11 | 0.148014E+11 | 0.168800E+11 | 0.337465E+11 | 0.242609E+11 |
Minimum of Months | 0.100665E+10 | 0.424877E+09 | 0.581773E+09 | 0.570976E+09 | 0.852107E+09 |
Maximum of Months | 0.433320E+10 | 0.218962E+10 | 0.221326E+10 | 0.565117E+10 | 0.405579E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43582264.69 | 17563896.56 | 26018368.14 | 23585286.93 | 0.160362E+09 |
February | 67189465.44 | 33026888.72 | 34162576.72 | 54030166.71 | 0.105316E+09 |
March | 95199034.68 | 34882191.24 | 60316843.44 | 80273443.16 | 96846306.99 |
April | 0.120274E+09 | 53286561.48 | 66987152.23 | 0.121908E+09 | 67658988.37 |
May | 0.153729E+09 | 70108290.58 | 83620681.57 | 0.167891E+09 | 56673598.99 |
June | 0.161856E+09 | 74346155.87 | 87509946.85 | 0.195538E+09 | 38336577.69 |
July | 0.171330E+09 | 86575281.78 | 84755084.97 | 0.223441E+09 | 33691539.95 |
August | 0.145483E+09 | 71399390.54 | 74083175.70 | 0.184667E+09 | 36641027.02 |
September | 0.113256E+09 | 57257535.20 | 55998812.51 | 0.131949E+09 | 51372381.60 |
October | 83645381.51 | 41558693.16 | 42086688.35 | 82295853.71 | 76275876.67 |
November | 57302847.95 | 28426987.77 | 28875860.18 | 46146929.81 | 98740349.58 |
December | 39801924.82 | 16799197.69 | 23002727.13 | 22575776.65 | 0.137341E+09 |
Annual Sum or Average | 0.125265E+10 | 0.585231E+09 | 0.667418E+09 | 0.133430E+10 | 0.959256E+09 |
Minimum of Months | 39801924.82 | 16799197.69 | 23002727.13 | 22575776.65 | 33691539.95 |
Maximum of Months | 0.171330E+09 | 86575281.78 | 87509946.85 | 0.223441E+09 | 0.160362E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.826371E+09 | 0.00 | 0.826371E+09 | 32712519.11 | 0.666199E+10 |
February | 0.105387E+10 | 0.00 | 0.105387E+10 | 0.206560E+09 | 0.444675E+10 |
March | 0.189539E+10 | 0.00 | 0.189539E+10 | 0.726538E+09 | 0.395762E+10 |
April | 0.209143E+10 | 12205121.80 | 0.207923E+10 | 0.116639E+10 | 0.272576E+10 |
May | 0.283810E+10 | 0.168175E+09 | 0.266993E+10 | 0.216568E+10 | 0.212074E+10 |
June | 0.319820E+10 | 0.367606E+09 | 0.283060E+10 | 0.328080E+10 | 0.134833E+10 |
July | 0.301912E+10 | 0.282777E+09 | 0.273635E+10 | 0.366548E+10 | 0.117085E+10 |
August | 0.241924E+10 | 64846941.02 | 0.235439E+10 | 0.267083E+10 | 0.133740E+10 |
September | 0.175340E+10 | 629213.91 | 0.175277E+10 | 0.151956E+10 | 0.195926E+10 |
October | 0.132163E+10 | 0.00 | 0.132163E+10 | 0.631565E+09 | 0.294237E+10 |
November | 0.869477E+09 | 0.00 | 0.869477E+09 | 0.157604E+09 | 0.400628E+10 |
December | 0.692959E+09 | 0.00 | 0.692959E+09 | 18488771.63 | 0.568965E+10 |
Annual Sum or Average | 0.219792E+11 | 0.896240E+09 | 0.210830E+11 | 0.162422E+11 | 0.383670E+11 |
Minimum of Months | 0.692959E+09 | 0.00 | 0.692959E+09 | 18488771.63 | 0.117085E+10 |
Maximum of Months | 0.319820E+10 | 0.367606E+09 | 0.283060E+10 | 0.366548E+10 | 0.666199E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126503E+10 | 0.579964E+09 | 0.685066E+09 | 0.694576E+09 | 0.408508E+10 |
February | 0.178714E+10 | 0.887271E+09 | 0.899870E+09 | 0.137258E+10 | 0.272520E+10 |
March | 0.266043E+10 | 0.110081E+10 | 0.155962E+10 | 0.222022E+10 | 0.248748E+10 |
April | 0.328495E+10 | 0.162800E+10 | 0.165696E+10 | 0.321363E+10 | 0.174038E+10 |
May | 0.374962E+10 | 0.166834E+10 | 0.208128E+10 | 0.391426E+10 | 0.142242E+10 |
June | 0.469683E+10 | 0.241698E+10 | 0.227985E+10 | 0.560219E+10 | 0.919972E+09 |
July | 0.509377E+10 | 0.287964E+10 | 0.221413E+10 | 0.654460E+10 | 0.781896E+09 |
August | 0.442671E+10 | 0.246642E+10 | 0.196029E+10 | 0.555599E+10 | 0.881373E+09 |
September | 0.303045E+10 | 0.156430E+10 | 0.146615E+10 | 0.345761E+10 | 0.123022E+10 |
October | 0.224666E+10 | 0.114082E+10 | 0.110584E+10 | 0.215063E+10 | 0.184243E+10 |
November | 0.137796E+10 | 0.643324E+09 | 0.734635E+09 | 0.980598E+09 | 0.244528E+10 |
December | 0.105020E+10 | 0.451063E+09 | 0.599139E+09 | 0.546953E+09 | 0.348681E+10 |
Annual Sum or Average | 0.346698E+11 | 0.174269E+11 | 0.172428E+11 | 0.362539E+11 | 0.240485E+11 |
Minimum of Months | 0.105020E+10 | 0.451063E+09 | 0.599139E+09 | 0.546953E+09 | 0.781896E+09 |
Maximum of Months | 0.509377E+10 | 0.287964E+10 | 0.227985E+10 | 0.654460E+10 | 0.408508E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.582490E+10 | 0.416026E+10 | 0.166464E+10 | 0.547711E+10 | 0.574430E+10 |
February | 0.670006E+10 | 0.481893E+10 | 0.188113E+10 | 0.691778E+10 | 0.390889E+10 |
March | 0.663066E+10 | 0.372347E+10 | 0.290719E+10 | 0.682691E+10 | 0.387259E+10 |
April | 0.515801E+10 | 0.246710E+10 | 0.269091E+10 | 0.550719E+10 | 0.280981E+10 |
May | 0.473552E+10 | 0.157279E+10 | 0.316273E+10 | 0.513859E+10 | 0.230610E+10 |
June | 0.455344E+10 | 0.132800E+10 | 0.322545E+10 | 0.561413E+10 | 0.155751E+10 |
July | 0.507270E+10 | 0.187383E+10 | 0.319887E+10 | 0.697167E+10 | 0.128868E+10 |
August | 0.602857E+10 | 0.303949E+10 | 0.298908E+10 | 0.803999E+10 | 0.144833E+10 |
September | 0.647071E+10 | 0.396480E+10 | 0.250590E+10 | 0.800201E+10 | 0.198743E+10 |
October | 0.699027E+10 | 0.483367E+10 | 0.215659E+10 | 0.795141E+10 | 0.286343E+10 |
November | 0.616747E+10 | 0.446746E+10 | 0.170001E+10 | 0.642459E+10 | 0.353948E+10 |
December | 0.553915E+10 | 0.399982E+10 | 0.153933E+10 | 0.533752E+10 | 0.489746E+10 |
Annual Sum or Average | 0.698715E+11 | 0.402496E+11 | 0.296218E+11 | 0.782089E+11 | 0.362240E+11 |
Minimum of Months | 0.455344E+10 | 0.132800E+10 | 0.153933E+10 | 0.513859E+10 | 0.128868E+10 |
Maximum of Months | 0.699027E+10 | 0.483367E+10 | 0.322545E+10 | 0.803999E+10 | 0.574430E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114585E+10 | 0.461786E+09 | 0.684066E+09 | 0.607106E+09 | 0.425626E+10 |
February | 0.176653E+10 | 0.868335E+09 | 0.898190E+09 | 0.138872E+10 | 0.280307E+10 |
March | 0.250294E+10 | 0.917114E+09 | 0.158583E+10 | 0.205189E+10 | 0.260180E+10 |
April | 0.316220E+10 | 0.140100E+10 | 0.176120E+10 | 0.312969E+10 | 0.184781E+10 |
May | 0.404179E+10 | 0.184327E+10 | 0.219852E+10 | 0.434992E+10 | 0.151793E+10 |
June | 0.425547E+10 | 0.195469E+10 | 0.230078E+10 | 0.509456E+10 | 0.102300E+10 |
July | 0.450456E+10 | 0.227622E+10 | 0.222835E+10 | 0.584722E+10 | 0.883252E+09 |
August | 0.382498E+10 | 0.187722E+10 | 0.194777E+10 | 0.483286E+10 | 0.958915E+09 |
September | 0.297770E+10 | 0.150540E+10 | 0.147230E+10 | 0.345779E+10 | 0.131921E+10 |
October | 0.219918E+10 | 0.109265E+10 | 0.110653E+10 | 0.216301E+10 | 0.194425E+10 |
November | 0.150659E+10 | 0.747396E+09 | 0.759194E+09 | 0.120742E+10 | 0.254752E+10 |
December | 0.104646E+10 | 0.441681E+09 | 0.604780E+09 | 0.584325E+09 | 0.359628E+10 |
Annual Sum or Average | 0.329343E+11 | 0.153868E+11 | 0.175475E+11 | 0.347145E+11 | 0.252993E+11 |
Minimum of Months | 0.104646E+10 | 0.441681E+09 | 0.604780E+09 | 0.584325E+09 | 0.883252E+09 |
Maximum of Months | 0.450456E+10 | 0.227622E+10 | 0.230078E+10 | 0.584722E+10 | 0.425626E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 14.85 | 2420.93 | 308.53 | 0.00 | 308.53 | 0.00 | 0.00 |
February | 94.42 | 1765.40 | 435.63 | 0.00 | 435.63 | 0.00 | 0.00 |
March | 285.96 | 1404.20 | 707.66 | 0.00 | 707.66 | 0.00 | 0.00 |
April | 467.99 | 986.61 | 806.88 | 4.71 | 802.17 | 0.00 | 0.00 |
May | 824.83 | 745.98 | 1059.63 | 62.79 | 996.84 | 0.00 | 0.00 |
June | 1274.17 | 499.70 | 1233.87 | 141.82 | 1092.05 | 0.00 | 0.00 |
July | 1371.36 | 423.81 | 1127.21 | 105.58 | 1021.64 | 0.00 | 0.00 |
August | 1002.94 | 477.59 | 903.24 | 24.21 | 879.03 | 0.00 | 0.00 |
September | 599.02 | 707.99 | 676.46 | 0.24 | 676.22 | 0.00 | 0.00 |
October | 258.08 | 1014.96 | 493.44 | 0.00 | 493.44 | 0.00 | 0.00 |
November | 70.70 | 1447.53 | 335.45 | 0.00 | 335.45 | 0.00 | 0.00 |
December | 8.05 | 2044.07 | 258.72 | 0.00 | 258.72 | 0.00 | 0.00 |
Annual Sum or Average | 525.34 | 1159.35 | 696.96 | 28.42 | 668.54 | 0.00 | 0.00 |
Minimum of Months | 8.05 | 423.81 | 258.72 | 0.00 | 258.72 | 0.00 | 0.00 |
Maximum of Months | 1371.36 | 2420.93 | 1233.87 | 141.82 | 1092.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 264.41 | 1485.62 | 472.31 | 216.53 | 255.77 | 0.00 | 0.00 |
February | 578.05 | 1082.71 | 738.73 | 366.76 | 371.97 | 0.00 | 0.00 |
March | 841.27 | 884.05 | 993.29 | 411.00 | 582.30 | 0.00 | 0.00 |
April | 1251.24 | 633.98 | 1267.34 | 628.08 | 639.26 | 0.00 | 0.00 |
May | 1469.13 | 502.80 | 1399.95 | 622.89 | 777.06 | 0.00 | 0.00 |
June | 2163.23 | 342.30 | 1812.05 | 932.48 | 879.57 | 0.00 | 0.00 |
July | 2442.33 | 283.53 | 1901.80 | 1075.13 | 826.66 | 0.00 | 0.00 |
August | 2075.43 | 316.46 | 1652.74 | 920.86 | 731.89 | 0.00 | 0.00 |
September | 1341.21 | 448.69 | 1169.15 | 603.51 | 565.64 | 0.00 | 0.00 |
October | 819.68 | 639.97 | 838.81 | 425.93 | 412.87 | 0.00 | 0.00 |
November | 392.14 | 886.18 | 531.62 | 248.20 | 283.42 | 0.00 | 0.00 |
December | 209.98 | 1252.61 | 392.10 | 168.41 | 223.69 | 0.00 | 0.00 |
Annual Sum or Average | 1157.29 | 728.67 | 1099.37 | 552.60 | 546.77 | 0.00 | 0.00 |
Minimum of Months | 209.98 | 283.53 | 392.10 | 168.41 | 223.69 | 0.00 | 0.00 |
Maximum of Months | 2442.33 | 1485.62 | 1901.80 | 1075.13 | 879.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2057.48 | 2081.07 | 2174.77 | 1553.26 | 621.51 | 0.00 | 0.00 |
February | 2876.71 | 1546.26 | 2769.54 | 1991.95 | 777.58 | 0.00 | 0.00 |
March | 2564.57 | 1373.43 | 2475.61 | 1390.18 | 1085.42 | 0.00 | 0.00 |
April | 2139.55 | 1021.09 | 1989.97 | 951.81 | 1038.16 | 0.00 | 0.00 |
May | 1928.91 | 812.30 | 1768.04 | 587.21 | 1180.83 | 0.00 | 0.00 |
June | 2169.15 | 574.36 | 1756.73 | 512.34 | 1244.38 | 0.00 | 0.00 |
July | 2602.39 | 463.68 | 1893.93 | 699.61 | 1194.32 | 0.00 | 0.00 |
August | 3002.64 | 516.63 | 2250.81 | 1134.81 | 1115.99 | 0.00 | 0.00 |
September | 3094.88 | 722.10 | 2496.41 | 1529.63 | 966.78 | 0.00 | 0.00 |
October | 2989.20 | 993.88 | 2609.87 | 1804.69 | 805.18 | 0.00 | 0.00 |
November | 2505.46 | 1280.89 | 2379.42 | 1723.56 | 655.87 | 0.00 | 0.00 |
December | 2011.04 | 1752.43 | 2068.08 | 1493.36 | 574.72 | 0.00 | 0.00 |
Annual Sum or Average | 2492.22 | 1093.27 | 2215.61 | 1276.31 | 939.30 | 0.00 | 0.00 |
Minimum of Months | 1928.91 | 463.68 | 1756.73 | 512.34 | 574.72 | 0.00 | 0.00 |
Maximum of Months | 3094.88 | 2081.07 | 2769.54 | 1991.95 | 1244.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 229.63 | 1548.36 | 427.81 | 172.41 | 255.40 | 0.00 | 0.00 |
February | 581.19 | 1111.56 | 730.21 | 358.93 | 371.28 | 0.00 | 0.00 |
March | 774.72 | 923.95 | 934.49 | 342.41 | 592.08 | 0.00 | 0.00 |
April | 1218.08 | 672.16 | 1219.98 | 540.51 | 679.48 | 0.00 | 0.00 |
May | 1631.38 | 535.29 | 1509.03 | 688.20 | 820.83 | 0.00 | 0.00 |
June | 1968.51 | 377.79 | 1641.77 | 754.12 | 887.65 | 0.00 | 0.00 |
July | 2183.68 | 318.57 | 1681.81 | 849.84 | 831.97 | 0.00 | 0.00 |
August | 1807.30 | 342.19 | 1428.08 | 700.87 | 727.21 | 0.00 | 0.00 |
September | 1341.55 | 478.43 | 1148.80 | 580.79 | 568.02 | 0.00 | 0.00 |
October | 821.45 | 673.46 | 821.08 | 407.95 | 413.13 | 0.00 | 0.00 |
November | 475.94 | 922.65 | 581.25 | 288.35 | 292.90 | 0.00 | 0.00 |
December | 222.17 | 1291.97 | 390.70 | 164.90 | 225.80 | 0.00 | 0.00 |
Annual Sum or Average | 1107.33 | 765.21 | 1044.34 | 487.91 | 556.43 | 0.00 | 0.00 |
Minimum of Months | 222.17 | 318.57 | 390.70 | 164.90 | 225.80 | 0.00 | 0.00 |
Maximum of Months | 2183.68 | 1548.36 | 1681.81 | 849.84 | 887.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13.00 | 2456.71 | 308.53 | 0.00 | 308.53 | 0.00 | 0.00 |
February | 93.60 | 1801.87 | 435.62 | 0.00 | 435.62 | 0.00 | 0.00 |
March | 297.59 | 1429.45 | 707.65 | 0.00 | 707.65 | 0.00 | 0.00 |
April | 497.98 | 983.27 | 806.87 | 4.71 | 802.17 | 0.00 | 0.00 |
May | 861.06 | 750.83 | 1059.62 | 62.79 | 996.83 | 0.00 | 0.00 |
June | 1303.76 | 495.12 | 1233.87 | 141.82 | 1092.05 | 0.00 | 0.00 |
July | 1393.32 | 419.43 | 1127.21 | 105.58 | 1021.63 | 0.00 | 0.00 |
August | 1015.54 | 482.72 | 903.24 | 24.21 | 879.03 | 0.00 | 0.00 |
September | 598.01 | 748.31 | 676.46 | 0.24 | 676.22 | 0.00 | 0.00 |
October | 238.66 | 1110.25 | 493.44 | 0.00 | 493.44 | 0.00 | 0.00 |
November | 61.74 | 1560.17 | 335.44 | 0.00 | 335.44 | 0.00 | 0.00 |
December | 7.60 | 2128.09 | 258.72 | 0.00 | 258.72 | 0.00 | 0.00 |
Annual Sum or Average | 534.51 | 1194.96 | 696.95 | 28.42 | 668.53 | 0.00 | 0.00 |
Minimum of Months | 7.60 | 419.43 | 258.72 | 0.00 | 258.72 | 0.00 | 0.00 |
Maximum of Months | 1393.32 | 2456.71 | 1233.87 | 141.82 | 1092.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 263.78 | 1514.81 | 472.30 | 216.53 | 255.77 | 0.00 | 0.00 |
February | 578.68 | 1113.46 | 738.73 | 366.76 | 371.97 | 0.00 | 0.00 |
March | 849.47 | 912.95 | 993.28 | 410.99 | 582.29 | 0.00 | 0.00 |
April | 1266.66 | 650.96 | 1267.33 | 628.08 | 639.26 | 0.00 | 0.00 |
May | 1484.51 | 521.07 | 1399.94 | 622.88 | 777.06 | 0.00 | 0.00 |
June | 2177.81 | 352.18 | 1812.03 | 932.47 | 879.57 | 0.00 | 0.00 |
July | 2453.43 | 295.21 | 1901.78 | 1075.12 | 826.66 | 0.00 | 0.00 |
August | 2082.34 | 333.67 | 1652.73 | 920.85 | 731.89 | 0.00 | 0.00 |
September | 1337.65 | 488.82 | 1169.15 | 603.51 | 565.64 | 0.00 | 0.00 |
October | 801.76 | 713.46 | 838.80 | 425.93 | 412.87 | 0.00 | 0.00 |
November | 377.80 | 963.69 | 531.62 | 248.19 | 283.42 | 0.00 | 0.00 |
December | 206.05 | 1308.16 | 392.10 | 168.41 | 223.69 | 0.00 | 0.00 |
Annual Sum or Average | 1159.95 | 762.81 | 1099.36 | 552.60 | 546.76 | 0.00 | 0.00 |
Minimum of Months | 206.05 | 295.21 | 392.10 | 168.41 | 223.69 | 0.00 | 0.00 |
Maximum of Months | 2453.43 | 1514.81 | 1901.78 | 1075.12 | 879.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2093.89 | 2084.27 | 2174.79 | 1553.28 | 621.51 | 0.00 | 0.00 |
February | 2918.65 | 1594.17 | 2769.57 | 1991.97 | 777.59 | 0.00 | 0.00 |
March | 2606.90 | 1418.00 | 2475.63 | 1390.20 | 1085.43 | 0.00 | 0.00 |
April | 2183.17 | 1038.30 | 1989.99 | 951.83 | 1038.17 | 0.00 | 0.00 |
May | 1977.80 | 821.38 | 1768.06 | 587.22 | 1180.84 | 0.00 | 0.00 |
June | 2209.96 | 572.99 | 1756.74 | 512.35 | 1244.39 | 0.00 | 0.00 |
July | 2625.33 | 474.32 | 1893.94 | 699.62 | 1194.33 | 0.00 | 0.00 |
August | 3021.96 | 541.93 | 2250.83 | 1134.83 | 1116.00 | 0.00 | 0.00 |
September | 3108.52 | 788.82 | 2496.44 | 1529.65 | 966.79 | 0.00 | 0.00 |
October | 2989.32 | 1116.59 | 2609.89 | 1804.71 | 805.19 | 0.00 | 0.00 |
November | 2502.51 | 1400.58 | 2379.45 | 1723.58 | 655.87 | 0.00 | 0.00 |
December | 2023.42 | 1813.07 | 2068.11 | 1493.38 | 574.72 | 0.00 | 0.00 |
Annual Sum or Average | 2518.75 | 1137.02 | 2215.63 | 1276.32 | 939.31 | 0.00 | 0.00 |
Minimum of Months | 1977.80 | 474.32 | 1756.74 | 512.35 | 574.72 | 0.00 | 0.00 |
Maximum of Months | 3108.52 | 2084.27 | 2769.57 | 1991.97 | 1244.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 231.52 | 1574.13 | 427.81 | 172.41 | 255.40 | 0.00 | 0.00 |
February | 587.19 | 1144.56 | 730.20 | 358.93 | 371.27 | 0.00 | 0.00 |
March | 787.97 | 950.65 | 934.48 | 342.41 | 592.08 | 0.00 | 0.00 |
April | 1236.55 | 686.29 | 1219.97 | 540.50 | 679.47 | 0.00 | 0.00 |
May | 1648.04 | 556.31 | 1509.02 | 688.19 | 820.83 | 0.00 | 0.00 |
June | 1983.40 | 388.86 | 1641.76 | 754.12 | 887.64 | 0.00 | 0.00 |
July | 2193.33 | 330.72 | 1681.80 | 849.83 | 831.97 | 0.00 | 0.00 |
August | 1812.71 | 359.67 | 1428.07 | 700.87 | 727.21 | 0.00 | 0.00 |
September | 1338.40 | 521.09 | 1148.80 | 580.78 | 568.01 | 0.00 | 0.00 |
October | 807.83 | 748.73 | 821.07 | 407.95 | 413.13 | 0.00 | 0.00 |
November | 468.08 | 1001.55 | 581.24 | 288.34 | 292.90 | 0.00 | 0.00 |
December | 221.61 | 1348.15 | 390.70 | 164.90 | 225.80 | 0.00 | 0.00 |
Annual Sum or Average | 1112.40 | 799.73 | 1044.33 | 487.91 | 556.42 | 0.00 | 0.00 |
Minimum of Months | 221.61 | 330.72 | 390.70 | 164.90 | 225.80 | 0.00 | 0.00 |
Maximum of Months | 2193.33 | 1574.13 | 1681.80 | 849.83 | 887.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12.21 | 2487.30 | 308.53 | 0.00 | 308.53 | 0.00 | 0.00 |
February | 85.38 | 1838.11 | 435.63 | 0.00 | 435.63 | 0.00 | 0.00 |
March | 271.26 | 1477.61 | 707.66 | 0.00 | 707.66 | 0.00 | 0.00 |
April | 450.00 | 1051.61 | 806.88 | 4.71 | 802.17 | 0.00 | 0.00 |
May | 808.57 | 791.79 | 1059.63 | 62.79 | 996.84 | 0.00 | 0.00 |
June | 1265.74 | 520.19 | 1233.87 | 141.82 | 1092.05 | 0.00 | 0.00 |
July | 1368.53 | 437.14 | 1127.21 | 105.58 | 1021.64 | 0.00 | 0.00 |
August | 997.17 | 499.33 | 903.24 | 24.21 | 879.03 | 0.00 | 0.00 |
September | 586.25 | 755.89 | 676.46 | 0.24 | 676.22 | 0.00 | 0.00 |
October | 235.80 | 1098.55 | 493.44 | 0.00 | 493.44 | 0.00 | 0.00 |
November | 60.80 | 1545.63 | 335.45 | 0.00 | 335.45 | 0.00 | 0.00 |
December | 6.90 | 2124.27 | 258.72 | 0.00 | 258.72 | 0.00 | 0.00 |
Annual Sum or Average | 515.04 | 1216.61 | 696.96 | 28.42 | 668.54 | 0.00 | 0.00 |
Minimum of Months | 6.90 | 437.14 | 258.72 | 0.00 | 258.72 | 0.00 | 0.00 |
Maximum of Months | 1368.53 | 2487.30 | 1233.87 | 141.82 | 1092.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 259.32 | 1525.20 | 472.31 | 216.53 | 255.77 | 0.00 | 0.00 |
February | 567.37 | 1126.49 | 738.73 | 366.76 | 371.97 | 0.00 | 0.00 |
March | 828.94 | 928.72 | 993.29 | 411.00 | 582.30 | 0.00 | 0.00 |
April | 1239.83 | 671.44 | 1267.34 | 628.08 | 639.26 | 0.00 | 0.00 |
May | 1461.42 | 531.07 | 1399.95 | 622.89 | 777.06 | 0.00 | 0.00 |
June | 2161.34 | 354.93 | 1812.05 | 932.48 | 879.57 | 0.00 | 0.00 |
July | 2443.47 | 291.93 | 1901.80 | 1075.13 | 826.66 | 0.00 | 0.00 |
August | 2074.37 | 329.07 | 1652.74 | 920.86 | 731.89 | 0.00 | 0.00 |
September | 1333.96 | 474.62 | 1169.15 | 603.51 | 565.64 | 0.00 | 0.00 |
October | 802.95 | 687.89 | 838.81 | 425.93 | 412.87 | 0.00 | 0.00 |
November | 378.32 | 943.39 | 531.62 | 248.20 | 283.42 | 0.00 | 0.00 |
December | 204.21 | 1301.83 | 392.10 | 168.41 | 223.69 | 0.00 | 0.00 |
Annual Sum or Average | 1149.60 | 762.57 | 1099.37 | 552.60 | 546.77 | 0.00 | 0.00 |
Minimum of Months | 204.21 | 291.93 | 392.10 | 168.41 | 223.69 | 0.00 | 0.00 |
Maximum of Months | 2443.47 | 1525.20 | 1901.80 | 1075.13 | 879.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2044.92 | 2144.68 | 2174.77 | 1553.26 | 621.51 | 0.00 | 0.00 |
February | 2859.53 | 1615.78 | 2769.54 | 1991.95 | 777.58 | 0.00 | 0.00 |
March | 2548.88 | 1445.86 | 2475.61 | 1390.18 | 1085.42 | 0.00 | 0.00 |
April | 2124.69 | 1084.03 | 1989.97 | 951.81 | 1038.16 | 0.00 | 0.00 |
May | 1918.53 | 861.00 | 1768.04 | 587.21 | 1180.83 | 0.00 | 0.00 |
June | 2165.95 | 600.89 | 1756.73 | 512.34 | 1244.38 | 0.00 | 0.00 |
July | 2602.92 | 481.14 | 1893.93 | 699.61 | 1194.32 | 0.00 | 0.00 |
August | 3001.79 | 540.74 | 2250.81 | 1134.81 | 1115.99 | 0.00 | 0.00 |
September | 3087.20 | 766.75 | 2496.41 | 1529.63 | 966.78 | 0.00 | 0.00 |
October | 2968.71 | 1069.08 | 2609.87 | 1804.69 | 805.18 | 0.00 | 0.00 |
November | 2478.62 | 1365.54 | 2379.42 | 1723.56 | 655.87 | 0.00 | 0.00 |
December | 1992.80 | 1828.50 | 2068.08 | 1493.36 | 574.72 | 0.00 | 0.00 |
Annual Sum or Average | 2479.99 | 1148.66 | 2215.61 | 1276.31 | 939.30 | 0.00 | 0.00 |
Minimum of Months | 1918.53 | 481.14 | 1756.73 | 512.34 | 574.72 | 0.00 | 0.00 |
Maximum of Months | 3087.20 | 2144.68 | 2769.54 | 1991.95 | 1244.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 226.67 | 1589.11 | 427.81 | 172.41 | 255.40 | 0.00 | 0.00 |
February | 574.04 | 1158.68 | 730.21 | 358.93 | 371.28 | 0.00 | 0.00 |
March | 766.09 | 971.40 | 934.49 | 342.41 | 592.08 | 0.00 | 0.00 |
April | 1207.44 | 712.89 | 1219.98 | 540.51 | 679.48 | 0.00 | 0.00 |
May | 1624.07 | 566.73 | 1509.03 | 688.20 | 820.83 | 0.00 | 0.00 |
June | 1965.49 | 394.68 | 1641.77 | 754.12 | 887.65 | 0.00 | 0.00 |
July | 2183.10 | 329.77 | 1681.81 | 849.84 | 831.97 | 0.00 | 0.00 |
August | 1804.38 | 358.02 | 1428.08 | 700.87 | 727.21 | 0.00 | 0.00 |
September | 1334.02 | 508.96 | 1148.80 | 580.79 | 568.02 | 0.00 | 0.00 |
October | 807.57 | 725.90 | 821.08 | 407.95 | 413.13 | 0.00 | 0.00 |
November | 465.82 | 982.84 | 581.25 | 288.35 | 292.90 | 0.00 | 0.00 |
December | 218.16 | 1342.70 | 390.70 | 164.90 | 225.80 | 0.00 | 0.00 |
Annual Sum or Average | 1100.79 | 802.24 | 1044.34 | 487.91 | 556.43 | 0.00 | 0.00 |
Minimum of Months | 218.16 | 329.77 | 390.70 | 164.90 | 225.80 | 0.00 | 0.00 |
Maximum of Months | 2183.10 | 1589.11 | 1681.81 | 849.84 | 887.65 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 39778091.22 | 0.648422E+10 | 0.826371E+09 | 0.00 | 0.826371E+09 | 0.00 | 0.00 |
February | 0.228418E+09 | 0.427087E+10 | 0.105387E+10 | 0.00 | 0.105387E+10 | 0.00 | 0.00 |
March | 0.765927E+09 | 0.376100E+10 | 0.189539E+10 | 0.00 | 0.189539E+10 | 0.00 | 0.00 |
April | 0.121304E+10 | 0.255729E+10 | 0.209143E+10 | 12205121.80 | 0.207923E+10 | 0.00 | 0.00 |
May | 0.220922E+10 | 0.199804E+10 | 0.283810E+10 | 0.168175E+09 | 0.266993E+10 | 0.00 | 0.00 |
June | 0.330266E+10 | 0.129522E+10 | 0.319820E+10 | 0.367606E+09 | 0.283060E+10 | 0.00 | 0.00 |
July | 0.367305E+10 | 0.113513E+10 | 0.301912E+10 | 0.282777E+09 | 0.273635E+10 | 0.00 | 0.00 |
August | 0.268627E+10 | 0.127916E+10 | 0.241924E+10 | 64846941.02 | 0.235439E+10 | 0.00 | 0.00 |
September | 0.155265E+10 | 0.183511E+10 | 0.175340E+10 | 629213.91 | 0.175277E+10 | 0.00 | 0.00 |
October | 0.691253E+09 | 0.271848E+10 | 0.132163E+10 | 0.00 | 0.132163E+10 | 0.00 | 0.00 |
November | 0.183251E+09 | 0.375200E+10 | 0.869477E+09 | 0.00 | 0.869477E+09 | 0.00 | 0.00 |
December | 21562486.52 | 0.547485E+10 | 0.692959E+09 | 0.00 | 0.692959E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.165671E+11 | 0.365614E+11 | 0.219792E+11 | 0.896240E+09 | 0.210830E+11 | 0.00 | 0.00 |
Minimum of Months | 21562486.52 | 0.113513E+10 | 0.692959E+09 | 0.00 | 0.692959E+09 | 0.00 | 0.00 |
Maximum of Months | 0.367305E+10 | 0.648422E+10 | 0.319820E+10 | 0.367606E+09 | 0.283060E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.708200E+09 | 0.397909E+10 | 0.126503E+10 | 0.579964E+09 | 0.685066E+09 | 0.00 | 0.00 |
February | 0.139842E+10 | 0.261928E+10 | 0.178714E+10 | 0.887271E+09 | 0.899870E+09 | 0.00 | 0.00 |
March | 0.225325E+10 | 0.236784E+10 | 0.266043E+10 | 0.110081E+10 | 0.155962E+10 | 0.00 | 0.00 |
April | 0.324322E+10 | 0.164326E+10 | 0.328495E+10 | 0.162800E+10 | 0.165696E+10 | 0.00 | 0.00 |
May | 0.393491E+10 | 0.134669E+10 | 0.374962E+10 | 0.166834E+10 | 0.208128E+10 | 0.00 | 0.00 |
June | 0.560708E+10 | 0.887245E+09 | 0.469683E+10 | 0.241698E+10 | 0.227985E+10 | 0.00 | 0.00 |
July | 0.654153E+10 | 0.759395E+09 | 0.509377E+10 | 0.287964E+10 | 0.221413E+10 | 0.00 | 0.00 |
August | 0.555883E+10 | 0.847599E+09 | 0.442671E+10 | 0.246642E+10 | 0.196029E+10 | 0.00 | 0.00 |
September | 0.347642E+10 | 0.116301E+10 | 0.303045E+10 | 0.156430E+10 | 0.146615E+10 | 0.00 | 0.00 |
October | 0.219543E+10 | 0.171409E+10 | 0.224666E+10 | 0.114082E+10 | 0.110584E+10 | 0.00 | 0.00 |
November | 0.101644E+10 | 0.229697E+10 | 0.137796E+10 | 0.643324E+09 | 0.734635E+09 | 0.00 | 0.00 |
December | 0.562417E+09 | 0.335499E+10 | 0.105020E+10 | 0.451063E+09 | 0.599139E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.364961E+11 | 0.229795E+11 | 0.346698E+11 | 0.174269E+11 | 0.172428E+11 | 0.00 | 0.00 |
Minimum of Months | 0.562417E+09 | 0.759395E+09 | 0.105020E+10 | 0.451063E+09 | 0.599139E+09 | 0.00 | 0.00 |
Maximum of Months | 0.654153E+10 | 0.397909E+10 | 0.509377E+10 | 0.287964E+10 | 0.227985E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.551074E+10 | 0.557393E+10 | 0.582490E+10 | 0.416026E+10 | 0.166464E+10 | 0.00 | 0.00 |
February | 0.695934E+10 | 0.374072E+10 | 0.670006E+10 | 0.481893E+10 | 0.188113E+10 | 0.00 | 0.00 |
March | 0.686893E+10 | 0.367861E+10 | 0.663066E+10 | 0.372347E+10 | 0.290719E+10 | 0.00 | 0.00 |
April | 0.554571E+10 | 0.264667E+10 | 0.515801E+10 | 0.246710E+10 | 0.269091E+10 | 0.00 | 0.00 |
May | 0.516638E+10 | 0.217567E+10 | 0.473552E+10 | 0.157279E+10 | 0.316273E+10 | 0.00 | 0.00 |
June | 0.562245E+10 | 0.148875E+10 | 0.455344E+10 | 0.132800E+10 | 0.322545E+10 | 0.00 | 0.00 |
July | 0.697024E+10 | 0.124193E+10 | 0.507270E+10 | 0.187383E+10 | 0.319887E+10 | 0.00 | 0.00 |
August | 0.804227E+10 | 0.138375E+10 | 0.602857E+10 | 0.303949E+10 | 0.298908E+10 | 0.00 | 0.00 |
September | 0.802194E+10 | 0.187167E+10 | 0.647071E+10 | 0.396480E+10 | 0.250590E+10 | 0.00 | 0.00 |
October | 0.800627E+10 | 0.266200E+10 | 0.699027E+10 | 0.483367E+10 | 0.215659E+10 | 0.00 | 0.00 |
November | 0.649416E+10 | 0.332006E+10 | 0.616747E+10 | 0.446746E+10 | 0.170001E+10 | 0.00 | 0.00 |
December | 0.538637E+10 | 0.469372E+10 | 0.553915E+10 | 0.399982E+10 | 0.153933E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.785948E+11 | 0.344775E+11 | 0.698715E+11 | 0.402496E+11 | 0.296218E+11 | 0.00 | 0.00 |
Minimum of Months | 0.516638E+10 | 0.124193E+10 | 0.455344E+10 | 0.132800E+10 | 0.153933E+10 | 0.00 | 0.00 |
Maximum of Months | 0.804227E+10 | 0.557393E+10 | 0.699027E+10 | 0.483367E+10 | 0.322545E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.615051E+09 | 0.414712E+10 | 0.114585E+10 | 0.461786E+09 | 0.684066E+09 | 0.00 | 0.00 |
February | 0.140601E+10 | 0.268908E+10 | 0.176653E+10 | 0.868335E+09 | 0.898190E+09 | 0.00 | 0.00 |
March | 0.207501E+10 | 0.247472E+10 | 0.250294E+10 | 0.917114E+09 | 0.158583E+10 | 0.00 | 0.00 |
April | 0.315726E+10 | 0.174224E+10 | 0.316220E+10 | 0.140100E+10 | 0.176120E+10 | 0.00 | 0.00 |
May | 0.436950E+10 | 0.143373E+10 | 0.404179E+10 | 0.184327E+10 | 0.219852E+10 | 0.00 | 0.00 |
June | 0.510237E+10 | 0.979235E+09 | 0.425547E+10 | 0.195469E+10 | 0.230078E+10 | 0.00 | 0.00 |
July | 0.584878E+10 | 0.853266E+09 | 0.450456E+10 | 0.227622E+10 | 0.222835E+10 | 0.00 | 0.00 |
August | 0.484067E+10 | 0.916529E+09 | 0.382498E+10 | 0.187722E+10 | 0.194777E+10 | 0.00 | 0.00 |
September | 0.347730E+10 | 0.124010E+10 | 0.297770E+10 | 0.150540E+10 | 0.147230E+10 | 0.00 | 0.00 |
October | 0.220018E+10 | 0.180381E+10 | 0.219918E+10 | 0.109265E+10 | 0.110653E+10 | 0.00 | 0.00 |
November | 0.123365E+10 | 0.239151E+10 | 0.150659E+10 | 0.747396E+09 | 0.759194E+09 | 0.00 | 0.00 |
December | 0.595059E+09 | 0.346040E+10 | 0.104646E+10 | 0.441681E+09 | 0.604780E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.349208E+11 | 0.241317E+11 | 0.329343E+11 | 0.153868E+11 | 0.175475E+11 | 0.00 | 0.00 |
Minimum of Months | 0.595059E+09 | 0.853266E+09 | 0.104646E+10 | 0.441681E+09 | 0.604780E+09 | 0.00 | 0.00 |
Maximum of Months | 0.584878E+10 | 0.414712E+10 | 0.450456E+10 | 0.227622E+10 | 0.230078E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 34826619.12 | 0.658005E+10 | 0.826367E+09 | 0.00 | 0.826367E+09 | 0.00 | 0.00 |
February | 0.226438E+09 | 0.435908E+10 | 0.105386E+10 | 0.00 | 0.105386E+10 | 0.00 | 0.00 |
March | 0.797054E+09 | 0.382863E+10 | 0.189538E+10 | 0.00 | 0.189538E+10 | 0.00 | 0.00 |
April | 0.129077E+10 | 0.254862E+10 | 0.209142E+10 | 12205058.56 | 0.207921E+10 | 0.00 | 0.00 |
May | 0.230627E+10 | 0.201103E+10 | 0.283809E+10 | 0.168174E+09 | 0.266991E+10 | 0.00 | 0.00 |
June | 0.337934E+10 | 0.128334E+10 | 0.319819E+10 | 0.367604E+09 | 0.283058E+10 | 0.00 | 0.00 |
July | 0.373187E+10 | 0.112340E+10 | 0.301911E+10 | 0.282776E+09 | 0.273633E+10 | 0.00 | 0.00 |
August | 0.272003E+10 | 0.129291E+10 | 0.241923E+10 | 64846604.99 | 0.235438E+10 | 0.00 | 0.00 |
September | 0.155003E+10 | 0.193961E+10 | 0.175339E+10 | 629210.65 | 0.175276E+10 | 0.00 | 0.00 |
October | 0.639215E+09 | 0.297370E+10 | 0.132163E+10 | 0.00 | 0.132163E+10 | 0.00 | 0.00 |
November | 0.160037E+09 | 0.404396E+10 | 0.869473E+09 | 0.00 | 0.869473E+09 | 0.00 | 0.00 |
December | 20365028.74 | 0.569988E+10 | 0.692955E+09 | 0.00 | 0.692955E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.168563E+11 | 0.376842E+11 | 0.219791E+11 | 0.896235E+09 | 0.210828E+11 | 0.00 | 0.00 |
Minimum of Months | 20365028.74 | 0.112340E+10 | 0.692955E+09 | 0.00 | 0.692955E+09 | 0.00 | 0.00 |
Maximum of Months | 0.373187E+10 | 0.658005E+10 | 0.319819E+10 | 0.367604E+09 | 0.283058E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.706515E+09 | 0.405725E+10 | 0.126502E+10 | 0.579958E+09 | 0.685062E+09 | 0.00 | 0.00 |
February | 0.139995E+10 | 0.269369E+10 | 0.178713E+10 | 0.887262E+09 | 0.899864E+09 | 0.00 | 0.00 |
March | 0.227523E+10 | 0.244524E+10 | 0.266041E+10 | 0.110080E+10 | 0.155961E+10 | 0.00 | 0.00 |
April | 0.328319E+10 | 0.168730E+10 | 0.328493E+10 | 0.162798E+10 | 0.165695E+10 | 0.00 | 0.00 |
May | 0.397611E+10 | 0.139564E+10 | 0.374959E+10 | 0.166832E+10 | 0.208126E+10 | 0.00 | 0.00 |
June | 0.564488E+10 | 0.912852E+09 | 0.469679E+10 | 0.241695E+10 | 0.227984E+10 | 0.00 | 0.00 |
July | 0.657127E+10 | 0.790691E+09 | 0.509373E+10 | 0.287961E+10 | 0.221412E+10 | 0.00 | 0.00 |
August | 0.557733E+10 | 0.893711E+09 | 0.442668E+10 | 0.246640E+10 | 0.196028E+10 | 0.00 | 0.00 |
September | 0.346720E+10 | 0.126703E+10 | 0.303043E+10 | 0.156429E+10 | 0.146614E+10 | 0.00 | 0.00 |
October | 0.214744E+10 | 0.191092E+10 | 0.224664E+10 | 0.114081E+10 | 0.110584E+10 | 0.00 | 0.00 |
November | 0.979247E+09 | 0.249789E+10 | 0.137795E+10 | 0.643317E+09 | 0.734630E+09 | 0.00 | 0.00 |
December | 0.551880E+09 | 0.350377E+10 | 0.105019E+10 | 0.451058E+09 | 0.599135E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.365802E+11 | 0.240560E+11 | 0.346695E+11 | 0.174267E+11 | 0.172427E+11 | 0.00 | 0.00 |
Minimum of Months | 0.551880E+09 | 0.790691E+09 | 0.105019E+10 | 0.451058E+09 | 0.599135E+09 | 0.00 | 0.00 |
Maximum of Months | 0.657127E+10 | 0.405725E+10 | 0.509373E+10 | 0.287961E+10 | 0.227984E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.560829E+10 | 0.558252E+10 | 0.582496E+10 | 0.416030E+10 | 0.166466E+10 | 0.00 | 0.00 |
February | 0.706080E+10 | 0.385661E+10 | 0.670013E+10 | 0.481899E+10 | 0.188115E+10 | 0.00 | 0.00 |
March | 0.698232E+10 | 0.379798E+10 | 0.663073E+10 | 0.372351E+10 | 0.290722E+10 | 0.00 | 0.00 |
April | 0.565877E+10 | 0.269126E+10 | 0.515806E+10 | 0.246713E+10 | 0.269093E+10 | 0.00 | 0.00 |
May | 0.529735E+10 | 0.219998E+10 | 0.473556E+10 | 0.157281E+10 | 0.316275E+10 | 0.00 | 0.00 |
June | 0.572822E+10 | 0.148519E+10 | 0.455348E+10 | 0.132801E+10 | 0.322546E+10 | 0.00 | 0.00 |
July | 0.703168E+10 | 0.127042E+10 | 0.507274E+10 | 0.187385E+10 | 0.319889E+10 | 0.00 | 0.00 |
August | 0.809402E+10 | 0.145152E+10 | 0.602862E+10 | 0.303952E+10 | 0.298910E+10 | 0.00 | 0.00 |
September | 0.805729E+10 | 0.204462E+10 | 0.647077E+10 | 0.396485E+10 | 0.250592E+10 | 0.00 | 0.00 |
October | 0.800661E+10 | 0.299067E+10 | 0.699034E+10 | 0.483373E+10 | 0.215661E+10 | 0.00 | 0.00 |
November | 0.648650E+10 | 0.363032E+10 | 0.616754E+10 | 0.446751E+10 | 0.170002E+10 | 0.00 | 0.00 |
December | 0.541952E+10 | 0.485613E+10 | 0.553921E+10 | 0.399987E+10 | 0.153934E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.794314E+11 | 0.358572E+11 | 0.698721E+11 | 0.402501E+11 | 0.296220E+11 | 0.00 | 0.00 |
Minimum of Months | 0.529735E+10 | 0.127042E+10 | 0.455348E+10 | 0.132801E+10 | 0.153934E+10 | 0.00 | 0.00 |
Maximum of Months | 0.809402E+10 | 0.558252E+10 | 0.699034E+10 | 0.483373E+10 | 0.322546E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.620094E+09 | 0.421615E+10 | 0.114584E+10 | 0.461781E+09 | 0.684061E+09 | 0.00 | 0.00 |
February | 0.142054E+10 | 0.276891E+10 | 0.176651E+10 | 0.868327E+09 | 0.898185E+09 | 0.00 | 0.00 |
March | 0.211051E+10 | 0.254623E+10 | 0.250292E+10 | 0.917105E+09 | 0.158582E+10 | 0.00 | 0.00 |
April | 0.320515E+10 | 0.177885E+10 | 0.316218E+10 | 0.140098E+10 | 0.176119E+10 | 0.00 | 0.00 |
May | 0.441411E+10 | 0.149003E+10 | 0.404176E+10 | 0.184325E+10 | 0.219851E+10 | 0.00 | 0.00 |
June | 0.514098E+10 | 0.100792E+10 | 0.425544E+10 | 0.195467E+10 | 0.230077E+10 | 0.00 | 0.00 |
July | 0.587461E+10 | 0.885799E+09 | 0.450453E+10 | 0.227619E+10 | 0.222834E+10 | 0.00 | 0.00 |
August | 0.485516E+10 | 0.963345E+09 | 0.382495E+10 | 0.187720E+10 | 0.194776E+10 | 0.00 | 0.00 |
September | 0.346914E+10 | 0.135065E+10 | 0.297768E+10 | 0.150539E+10 | 0.147229E+10 | 0.00 | 0.00 |
October | 0.216368E+10 | 0.200540E+10 | 0.219916E+10 | 0.109264E+10 | 0.110652E+10 | 0.00 | 0.00 |
November | 0.121327E+10 | 0.259602E+10 | 0.150658E+10 | 0.747388E+09 | 0.759189E+09 | 0.00 | 0.00 |
December | 0.593552E+09 | 0.361088E+10 | 0.104645E+10 | 0.441676E+09 | 0.604776E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.350808E+11 | 0.252202E+11 | 0.329340E+11 | 0.153866E+11 | 0.175474E+11 | 0.00 | 0.00 |
Minimum of Months | 0.593552E+09 | 0.885799E+09 | 0.104645E+10 | 0.441676E+09 | 0.604776E+09 | 0.00 | 0.00 |
Maximum of Months | 0.587461E+10 | 0.421615E+10 | 0.450453E+10 | 0.227619E+10 | 0.230077E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 32712519.11 | 0.666199E+10 | 0.826371E+09 | 0.00 | 0.826371E+09 | 0.00 | 0.00 |
February | 0.206560E+09 | 0.444675E+10 | 0.105387E+10 | 0.00 | 0.105387E+10 | 0.00 | 0.00 |
March | 0.726538E+09 | 0.395762E+10 | 0.189539E+10 | 0.00 | 0.189539E+10 | 0.00 | 0.00 |
April | 0.116639E+10 | 0.272576E+10 | 0.209143E+10 | 12205121.80 | 0.207923E+10 | 0.00 | 0.00 |
May | 0.216568E+10 | 0.212074E+10 | 0.283810E+10 | 0.168175E+09 | 0.266993E+10 | 0.00 | 0.00 |
June | 0.328080E+10 | 0.134833E+10 | 0.319820E+10 | 0.367606E+09 | 0.283060E+10 | 0.00 | 0.00 |
July | 0.366548E+10 | 0.117085E+10 | 0.301912E+10 | 0.282777E+09 | 0.273635E+10 | 0.00 | 0.00 |
August | 0.267083E+10 | 0.133740E+10 | 0.241924E+10 | 64846941.02 | 0.235439E+10 | 0.00 | 0.00 |
September | 0.151956E+10 | 0.195926E+10 | 0.175340E+10 | 629213.91 | 0.175277E+10 | 0.00 | 0.00 |
October | 0.631565E+09 | 0.294237E+10 | 0.132163E+10 | 0.00 | 0.132163E+10 | 0.00 | 0.00 |
November | 0.157604E+09 | 0.400628E+10 | 0.869477E+09 | 0.00 | 0.869477E+09 | 0.00 | 0.00 |
December | 18488771.63 | 0.568965E+10 | 0.692959E+09 | 0.00 | 0.692959E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.162422E+11 | 0.383670E+11 | 0.219792E+11 | 0.896240E+09 | 0.210830E+11 | 0.00 | 0.00 |
Minimum of Months | 18488771.63 | 0.117085E+10 | 0.692959E+09 | 0.00 | 0.692959E+09 | 0.00 | 0.00 |
Maximum of Months | 0.366548E+10 | 0.666199E+10 | 0.319820E+10 | 0.367606E+09 | 0.283060E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.694576E+09 | 0.408508E+10 | 0.126503E+10 | 0.579964E+09 | 0.685066E+09 | 0.00 | 0.00 |
February | 0.137258E+10 | 0.272520E+10 | 0.178714E+10 | 0.887271E+09 | 0.899870E+09 | 0.00 | 0.00 |
March | 0.222022E+10 | 0.248748E+10 | 0.266043E+10 | 0.110081E+10 | 0.155962E+10 | 0.00 | 0.00 |
April | 0.321363E+10 | 0.174038E+10 | 0.328495E+10 | 0.162800E+10 | 0.165696E+10 | 0.00 | 0.00 |
May | 0.391426E+10 | 0.142242E+10 | 0.374962E+10 | 0.166834E+10 | 0.208128E+10 | 0.00 | 0.00 |
June | 0.560219E+10 | 0.919972E+09 | 0.469683E+10 | 0.241698E+10 | 0.227985E+10 | 0.00 | 0.00 |
July | 0.654460E+10 | 0.781896E+09 | 0.509377E+10 | 0.287964E+10 | 0.221413E+10 | 0.00 | 0.00 |
August | 0.555599E+10 | 0.881373E+09 | 0.442671E+10 | 0.246642E+10 | 0.196029E+10 | 0.00 | 0.00 |
September | 0.345761E+10 | 0.123022E+10 | 0.303045E+10 | 0.156430E+10 | 0.146615E+10 | 0.00 | 0.00 |
October | 0.215063E+10 | 0.184243E+10 | 0.224666E+10 | 0.114082E+10 | 0.110584E+10 | 0.00 | 0.00 |
November | 0.980598E+09 | 0.244528E+10 | 0.137796E+10 | 0.643324E+09 | 0.734635E+09 | 0.00 | 0.00 |
December | 0.546953E+09 | 0.348681E+10 | 0.105020E+10 | 0.451063E+09 | 0.599139E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.362539E+11 | 0.240485E+11 | 0.346698E+11 | 0.174269E+11 | 0.172428E+11 | 0.00 | 0.00 |
Minimum of Months | 0.546953E+09 | 0.781896E+09 | 0.105020E+10 | 0.451063E+09 | 0.599139E+09 | 0.00 | 0.00 |
Maximum of Months | 0.654460E+10 | 0.408508E+10 | 0.509377E+10 | 0.287964E+10 | 0.227985E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.547711E+10 | 0.574430E+10 | 0.582490E+10 | 0.416026E+10 | 0.166464E+10 | 0.00 | 0.00 |
February | 0.691778E+10 | 0.390889E+10 | 0.670006E+10 | 0.481893E+10 | 0.188113E+10 | 0.00 | 0.00 |
March | 0.682691E+10 | 0.387259E+10 | 0.663066E+10 | 0.372347E+10 | 0.290719E+10 | 0.00 | 0.00 |
April | 0.550719E+10 | 0.280981E+10 | 0.515801E+10 | 0.246710E+10 | 0.269091E+10 | 0.00 | 0.00 |
May | 0.513859E+10 | 0.230610E+10 | 0.473552E+10 | 0.157279E+10 | 0.316273E+10 | 0.00 | 0.00 |
June | 0.561413E+10 | 0.155751E+10 | 0.455344E+10 | 0.132800E+10 | 0.322545E+10 | 0.00 | 0.00 |
July | 0.697167E+10 | 0.128868E+10 | 0.507270E+10 | 0.187383E+10 | 0.319887E+10 | 0.00 | 0.00 |
August | 0.803999E+10 | 0.144833E+10 | 0.602857E+10 | 0.303949E+10 | 0.298908E+10 | 0.00 | 0.00 |
September | 0.800201E+10 | 0.198743E+10 | 0.647071E+10 | 0.396480E+10 | 0.250590E+10 | 0.00 | 0.00 |
October | 0.795141E+10 | 0.286343E+10 | 0.699027E+10 | 0.483367E+10 | 0.215659E+10 | 0.00 | 0.00 |
November | 0.642459E+10 | 0.353948E+10 | 0.616747E+10 | 0.446746E+10 | 0.170001E+10 | 0.00 | 0.00 |
December | 0.533752E+10 | 0.489746E+10 | 0.553915E+10 | 0.399982E+10 | 0.153933E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.782089E+11 | 0.362240E+11 | 0.698715E+11 | 0.402496E+11 | 0.296218E+11 | 0.00 | 0.00 |
Minimum of Months | 0.513859E+10 | 0.128868E+10 | 0.455344E+10 | 0.132800E+10 | 0.153933E+10 | 0.00 | 0.00 |
Maximum of Months | 0.803999E+10 | 0.574430E+10 | 0.699027E+10 | 0.483367E+10 | 0.322545E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.607106E+09 | 0.425626E+10 | 0.114585E+10 | 0.461786E+09 | 0.684066E+09 | 0.00 | 0.00 |
February | 0.138872E+10 | 0.280307E+10 | 0.176653E+10 | 0.868335E+09 | 0.898190E+09 | 0.00 | 0.00 |
March | 0.205189E+10 | 0.260180E+10 | 0.250294E+10 | 0.917114E+09 | 0.158583E+10 | 0.00 | 0.00 |
April | 0.312969E+10 | 0.184781E+10 | 0.316220E+10 | 0.140100E+10 | 0.176120E+10 | 0.00 | 0.00 |
May | 0.434992E+10 | 0.151793E+10 | 0.404179E+10 | 0.184327E+10 | 0.219852E+10 | 0.00 | 0.00 |
June | 0.509456E+10 | 0.102300E+10 | 0.425547E+10 | 0.195469E+10 | 0.230078E+10 | 0.00 | 0.00 |
July | 0.584722E+10 | 0.883252E+09 | 0.450456E+10 | 0.227622E+10 | 0.222835E+10 | 0.00 | 0.00 |
August | 0.483286E+10 | 0.958915E+09 | 0.382498E+10 | 0.187722E+10 | 0.194777E+10 | 0.00 | 0.00 |
September | 0.345779E+10 | 0.131921E+10 | 0.297770E+10 | 0.150540E+10 | 0.147230E+10 | 0.00 | 0.00 |
October | 0.216301E+10 | 0.194425E+10 | 0.219918E+10 | 0.109265E+10 | 0.110653E+10 | 0.00 | 0.00 |
November | 0.120742E+10 | 0.254752E+10 | 0.150659E+10 | 0.747396E+09 | 0.759194E+09 | 0.00 | 0.00 |
December | 0.584325E+09 | 0.359628E+10 | 0.104646E+10 | 0.441681E+09 | 0.604780E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.347145E+11 | 0.252993E+11 | 0.329343E+11 | 0.153868E+11 | 0.175475E+11 | 0.00 | 0.00 |
Minimum of Months | 0.584325E+09 | 0.883252E+09 | 0.104646E+10 | 0.441681E+09 | 0.604780E+09 | 0.00 | 0.00 |
Maximum of Months | 0.584722E+10 | 0.425626E+10 | 0.450456E+10 | 0.227622E+10 | 0.230078E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.581433E+10 | -0.506487E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -749463258.2 | 58.98 | 0.00 | 0.00 |
February | 0.534433E+10 | -0.468388E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -660448521.4 | 58.98 | 0.00 | 0.00 |
March | 0.620449E+10 | -0.548731E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -717185224.4 | 58.98 | 0.00 | 0.00 |
April | 0.543896E+10 | -0.475761E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -681344405.9 | 58.99 | 0.00 | 0.00 |
May | 0.552038E+10 | -0.482397E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -696414555.4 | 58.98 | 0.00 | 0.00 |
June | 0.516455E+10 | -0.449551E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669037926.3 | 58.98 | 0.00 | 0.00 |
July | 0.470841E+10 | -0.402040E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688012095.9 | 58.98 | 0.00 | 0.00 |
August | 0.503502E+10 | -0.434603E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688990831.8 | 58.98 | 0.00 | 0.00 |
September | 0.463511E+10 | -0.396663E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668477262.7 | 58.99 | 0.00 | 0.00 |
October | 0.498518E+10 | -0.428815E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -697035773.2 | 58.98 | 0.00 | 0.00 |
November | 0.517177E+10 | -0.448473E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -687040106.1 | 58.98 | 0.00 | 0.00 |
December | 0.544293E+10 | -0.471053E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -732399615.1 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.634655E+11 | -0.551296E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.833585E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.463511E+10 | -0.548731E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -749463258.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.620449E+10 | -0.396663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -660448521.4 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.64 | 0.62 | 01-JAN-08:50 | 5360.10 | 32.83 | 186.33 | 224.83 | 4703.59 | 37.57 | 217.67 | 210.67 |
February | 275.00 | 0.63 | 0.62 | 01-FEB-08:20 | 7514.79 | 35.86 | 256.67 | 254.67 | 3246.06 | 31.65 | 235.33 | 243.67 |
March | 304.00 | 0.63 | 0.62 | 01-MAR-07:49 | 8800.35 | 32.33 | 255.00 | 317.83 | 1772.00 | 21.97 | 185.67 | 287.67 |
April | 325.17 | 0.63 | 0.62 | 01-APR-08:39 | 2118.50 | 18.16 | 0.00 | 343.17 | 1226.29 | 20.99 | 159.33 | 305.33 |
May | 385.83 | 0.63 | 0.62 | 01-MAY-06:10 | 1862.59 | 17.91 | 0.00 | 389.83 | 1055.26 | 20.71 | 160.83 | 345.00 |
June | 434.17 | 0.64 | 0.62 | 01-JUN-13:39 | 1585.13 | 17.34 | 0.00 | 400.67 | 929.45 | 20.18 | 181.67 | 350.83 |
July | 417.33 | 0.63 | 0.62 | 01-JUL-06:40 | 1705.19 | 17.76 | 0.00 | 396.50 | 1028.95 | 20.63 | 143.00 | 358.83 |
August | 421.33 | 0.64 | 0.62 | 01-AUG-06:10 | 1838.20 | 17.25 | 0.00 | 376.17 | 1112.70 | 20.08 | 152.83 | 336.33 |
September | 352.17 | 0.64 | 0.62 | 01-SEP-06:49 | 2643.01 | 18.81 | 29.50 | 322.17 | 1334.67 | 20.48 | 143.50 | 291.00 |
October | 317.67 | 0.63 | 0.62 | 01-OCT-07:40 | 7633.79 | 33.95 | 280.50 | 297.83 | 2165.32 | 24.72 | 192.00 | 281.50 |
November | 269.50 | 0.63 | 0.62 | 01-NOV-07:49 | 5623.65 | 35.29 | 246.33 | 245.67 | 5062.50 | 38.25 | 263.17 | 238.33 |
December | 236.83 | 0.64 | 0.62 | 01-DEC-08:50 | 4270.64 | 33.36 | 197.00 | 224.67 | 3888.97 | 38.60 | 238.50 | 216.33 |
Annual Sum or Average | 3965.83 | 0.63 | 3888.81 | 24.45 | 1451.33 | 3794.00 | 2029.64 | 24.98 | 2273.50 | 3465.50 | ||
Minimum of Months | 226.83 | 0.63 | 0.62 | 1585.13 | 17.25 | 0.00 | 224.67 | 929.45 | 20.08 | 143.00 | 210.67 | |
Maximum of Months | 434.17 | 0.64 | 0.62 | 8800.35 | 35.86 | 280.50 | 400.67 | 5062.50 | 38.60 | 263.17 | 358.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.65 | 0.62 | 01-JAN-08:50 | 1618.61 | 20.57 | 74.67 | 206.33 | 975.67 | 23.41 | 77.83 | 170.00 |
February | 275.00 | 0.64 | 0.62 | 01-FEB-08:09 | 1854.64 | 20.16 | 74.67 | 236.50 | 984.06 | 21.35 | 75.50 | 201.17 |
March | 304.00 | 0.63 | 0.62 | 01-MAR-07:40 | 2977.56 | 21.87 | 94.00 | 312.83 | 1658.19 | 23.18 | 106.50 | 277.33 |
April | 325.17 | 0.63 | 0.62 | 01-APR-08:39 | 2993.44 | 21.03 | 85.17 | 349.83 | 1668.67 | 22.56 | 61.17 | 309.83 |
May | 385.83 | 0.63 | 0.62 | 01-MAY-05:40 | 3221.27 | 20.10 | 96.00 | 401.00 | 1431.95 | 21.66 | 57.83 | 357.83 |
June | 434.17 | 0.63 | 0.62 | 01-JUN-13:39 | 4015.57 | 21.55 | 133.17 | 412.50 | 1724.04 | 21.94 | 78.50 | 377.33 |
July | 417.33 | 0.62 | 0.62 | 01-JUL-06:40 | 4259.15 | 21.04 | 110.67 | 414.00 | 1854.84 | 22.45 | 74.17 | 384.17 |
August | 421.33 | 0.63 | 0.62 | 01-AUG-05:40 | 3429.04 | 20.51 | 112.67 | 382.67 | 1970.12 | 22.24 | 86.67 | 347.50 |
September | 352.17 | 0.64 | 0.62 | 01-SEP-06:30 | 2517.49 | 19.34 | 84.83 | 318.17 | 1450.54 | 22.42 | 85.67 | 283.00 |
October | 317.67 | 0.64 | 0.62 | 01-OCT-07:40 | 2338.85 | 21.41 | 106.50 | 279.67 | 1332.81 | 22.69 | 106.00 | 240.83 |
November | 269.50 | 0.65 | 0.62 | 01-NOV-07:49 | 1463.24 | 19.87 | 80.50 | 222.00 | 791.80 | 21.18 | 72.00 | 181.83 |
December | 236.83 | 0.65 | 0.62 | 01-DEC-08:50 | 1248.40 | 20.11 | 79.83 | 196.50 | 790.63 | 23.54 | 85.33 | 151.17 |
Annual Sum or Average | 3965.83 | 0.64 | 2845.26 | 20.67 | 1132.67 | 3732.00 | 1457.11 | 22.33 | 967.17 | 3282.00 | ||
Minimum of Months | 226.83 | 0.62 | 0.62 | 1248.40 | 19.34 | 74.67 | 196.50 | 790.63 | 21.18 | 57.83 | 151.17 | |
Maximum of Months | 434.17 | 0.65 | 0.62 | 4259.15 | 21.87 | 133.17 | 414.00 | 1970.12 | 23.54 | 106.50 | 384.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.67 | 0.62 | 01-JAN-09:30 | 534.13 | 13.55 | 0.00 | 179.17 | 318.27 | 16.58 | 0.00 | 91.17 |
February | 275.00 | 0.65 | 0.62 | 01-FEB-09:00 | 582.41 | 14.51 | 0.00 | 218.83 | 361.63 | 17.59 | 0.00 | 148.17 |
March | 304.00 | 0.63 | 0.62 | 01-MAR-07:49 | 924.24 | 16.72 | 0.00 | 304.17 | 545.75 | 19.56 | 0.33 | 256.50 |
April | 325.17 | 0.63 | 0.62 | 01-APR-08:39 | 961.39 | 17.42 | 0.00 | 346.50 | 576.56 | 20.17 | 14.33 | 296.33 |
May | 385.83 | 0.63 | 0.62 | 01-MAY-05:40 | 1196.19 | 19.53 | 38.50 | 407.00 | 673.44 | 20.79 | 86.17 | 367.50 |
June | 434.17 | 0.63 | 0.62 | 01-JUN-13:39 | 1241.24 | 21.19 | 96.50 | 435.00 | 704.11 | 22.12 | 164.83 | 406.33 |
July | 417.33 | 0.62 | 0.62 | 01-JUL-06:40 | 1213.62 | 20.72 | 72.17 | 422.00 | 700.39 | 21.05 | 108.67 | 391.50 |
August | 421.33 | 0.63 | 0.62 | 01-AUG-05:40 | 936.85 | 17.04 | 0.00 | 394.67 | 600.84 | 19.84 | 23.67 | 366.83 |
September | 352.17 | 0.64 | 0.62 | 01-SEP-06:49 | 763.75 | 15.98 | 0.00 | 316.67 | 477.50 | 18.83 | 0.50 | 258.50 |
October | 317.67 | 0.65 | 0.62 | 01-OCT-07:40 | 631.36 | 14.92 | 0.00 | 259.67 | 387.75 | 17.92 | 0.00 | 186.33 |
November | 269.50 | 0.66 | 0.62 | 01-NOV-08:09 | 500.27 | 13.60 | 0.00 | 193.33 | 303.47 | 16.70 | 0.00 | 93.50 |
December | 236.83 | 0.67 | 0.62 | 01-DEC-08:00 | 434.84 | 12.91 | 0.00 | 163.00 | 263.22 | 16.08 | 0.00 | 44.50 |
Annual Sum or Average | 3965.83 | 0.64 | 878.48 | 17.01 | 207.17 | 3640.00 | 522.33 | 19.29 | 398.50 | 2907.17 | ||
Minimum of Months | 226.83 | 0.62 | 0.62 | 434.84 | 12.91 | 0.00 | 163.00 | 263.22 | 16.08 | 0.00 | 44.50 | |
Maximum of Months | 434.17 | 0.67 | 0.62 | 1241.24 | 21.19 | 96.50 | 435.00 | 704.11 | 22.12 | 164.83 | 406.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.65 | 0.62 | 01-JAN-09:30 | 1483.09 | 19.43 | 68.33 | 199.83 | 928.03 | 22.33 | 69.67 | 157.67 |
February | 275.00 | 0.64 | 0.62 | 01-FEB-09:00 | 1967.82 | 20.12 | 77.17 | 235.33 | 1117.58 | 23.11 | 92.50 | 203.83 |
March | 304.00 | 0.63 | 0.62 | 01-MAR-07:00 | 2778.33 | 21.40 | 91.33 | 309.17 | 1526.19 | 22.94 | 96.00 | 274.33 |
April | 325.17 | 0.63 | 0.62 | 01-APR-08:39 | 2771.81 | 19.69 | 75.83 | 340.50 | 1632.44 | 21.41 | 48.17 | 303.00 |
May | 385.83 | 0.63 | 0.62 | 01-MAY-06:19 | 3256.81 | 18.63 | 74.50 | 394.33 | 1537.92 | 18.63 | 0.00 | 356.17 |
June | 434.17 | 0.63 | 0.62 | 01-JUN-13:39 | 3314.78 | 16.68 | 52.00 | 416.17 | 1525.38 | 18.29 | 0.50 | 377.67 |
July | 417.33 | 0.63 | 0.62 | 01-JUL-06:40 | 3874.81 | 18.71 | 79.67 | 403.50 | 1772.45 | 18.64 | 3.67 | 369.50 |
August | 421.33 | 0.63 | 0.62 | 01-AUG-06:19 | 3030.36 | 18.47 | 88.17 | 380.83 | 1665.61 | 20.43 | 59.17 | 345.67 |
September | 352.17 | 0.64 | 0.62 | 01-SEP-06:00 | 3024.36 | 20.46 | 98.33 | 319.00 | 1272.81 | 21.83 | 70.83 | 285.33 |
October | 317.67 | 0.64 | 0.62 | 01-OCT-07:49 | 1973.24 | 19.58 | 80.50 | 276.50 | 1134.32 | 22.61 | 91.83 | 239.17 |
November | 269.50 | 0.65 | 0.62 | 01-NOV-08:09 | 1676.28 | 19.90 | 81.83 | 218.67 | 1008.56 | 23.03 | 90.33 | 180.17 |
December | 236.83 | 0.65 | 0.62 | 01-DEC-08:00 | 1198.32 | 20.06 | 76.83 | 199.83 | 661.79 | 20.98 | 66.50 | 153.33 |
Annual Sum or Average | 3965.83 | 0.64 | 2683.06 | 19.27 | 944.50 | 3693.67 | 1373.45 | 20.91 | 689.17 | 3245.83 | ||
Minimum of Months | 226.83 | 0.63 | 0.62 | 1198.32 | 16.68 | 52.00 | 199.83 | 661.79 | 18.29 | 0.00 | 153.33 | |
Maximum of Months | 434.17 | 0.65 | 0.62 | 3874.81 | 21.40 | 98.33 | 416.17 | 1772.45 | 23.11 | 96.00 | 377.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.64 | 0.62 | 01-JAN-08:50 | 5184.32 | 32.03 | 185.17 | 223.00 | 4569.86 | 37.29 | 215.17 | 208.00 |
February | 275.00 | 0.63 | 0.62 | 01-FEB-08:20 | 7274.78 | 33.79 | 239.83 | 250.50 | 3106.04 | 30.24 | 179.67 | 243.00 |
March | 304.00 | 0.63 | 0.62 | 01-MAR-07:49 | 8613.53 | 31.62 | 252.33 | 316.17 | 1646.56 | 19.14 | 14.17 | 286.00 |
April | 325.17 | 0.63 | 0.62 | 01-APR-08:39 | 1996.35 | 14.49 | 0.00 | 341.17 | 1141.67 | 18.49 | 5.67 | 299.83 |
May | 385.83 | 0.63 | 0.62 | 01-MAY-06:10 | 1766.35 | 14.37 | 0.00 | 386.50 | 992.56 | 18.30 | 0.83 | 340.67 |
June | 434.17 | 0.64 | 0.62 | 01-JUN-13:39 | 1505.00 | 13.90 | 0.00 | 397.17 | 878.12 | 17.91 | 0.00 | 346.33 |
July | 417.33 | 0.63 | 0.62 | 01-JUL-06:40 | 1615.11 | 14.34 | 0.00 | 394.50 | 969.09 | 18.39 | 0.83 | 354.00 |
August | 421.33 | 0.64 | 0.62 | 01-AUG-06:19 | 1730.66 | 13.65 | 0.00 | 373.50 | 1036.38 | 17.68 | 0.83 | 332.00 |
September | 352.17 | 0.64 | 0.62 | 01-SEP-06:49 | 2503.13 | 15.30 | 29.50 | 319.67 | 1232.30 | 17.88 | 10.67 | 288.67 |
October | 317.67 | 0.63 | 0.62 | 01-OCT-07:40 | 7452.68 | 33.11 | 274.83 | 295.33 | 2041.86 | 22.32 | 80.67 | 279.83 |
November | 269.50 | 0.64 | 0.62 | 01-NOV-07:49 | 5364.45 | 32.45 | 223.00 | 241.83 | 4937.34 | 37.86 | 260.67 | 236.83 |
December | 236.83 | 0.64 | 0.62 | 01-DEC-08:50 | 3922.32 | 29.52 | 169.00 | 223.33 | 3736.09 | 36.94 | 219.00 | 212.00 |
Annual Sum or Average | 3965.83 | 0.64 | 3733.39 | 21.64 | 1373.67 | 3762.67 | 1932.99 | 22.92 | 988.17 | 3427.17 | ||
Minimum of Months | 226.83 | 0.63 | 0.62 | 1505.00 | 13.65 | 0.00 | 223.00 | 878.12 | 17.68 | 0.00 | 208.00 | |
Maximum of Months | 434.17 | 0.64 | 0.62 | 8613.53 | 33.79 | 274.83 | 397.17 | 4937.34 | 37.86 | 260.67 | 354.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.65 | 0.62 | 01-JAN-08:50 | 1568.60 | 20.16 | 74.50 | 205.00 | 938.34 | 23.18 | 73.00 | 163.83 |
February | 275.00 | 0.64 | 0.62 | 01-FEB-08:09 | 1789.15 | 19.73 | 74.67 | 234.33 | 934.68 | 21.11 | 66.50 | 197.00 |
March | 304.00 | 0.63 | 0.62 | 01-MAR-07:40 | 2728.32 | 19.74 | 74.00 | 311.00 | 1592.24 | 22.98 | 94.67 | 274.17 |
April | 325.17 | 0.63 | 0.62 | 01-APR-08:39 | 2733.87 | 18.80 | 65.17 | 348.17 | 1601.53 | 22.37 | 60.17 | 303.83 |
May | 385.83 | 0.63 | 0.62 | 01-MAY-05:40 | 3134.23 | 19.69 | 95.83 | 397.50 | 1366.63 | 21.48 | 57.83 | 353.00 |
June | 434.17 | 0.63 | 0.62 | 01-JUN-13:39 | 3794.18 | 19.63 | 107.17 | 409.17 | 1647.90 | 21.78 | 78.33 | 375.00 |
July | 417.33 | 0.62 | 0.62 | 01-JUL-06:40 | 4150.50 | 20.64 | 110.67 | 412.50 | 1770.91 | 22.28 | 74.17 | 381.17 |
August | 421.33 | 0.63 | 0.62 | 01-AUG-05:40 | 3332.15 | 20.10 | 112.67 | 380.67 | 1894.84 | 22.07 | 86.17 | 343.00 |
September | 352.17 | 0.64 | 0.62 | 01-SEP-06:30 | 2418.17 | 18.71 | 81.83 | 316.00 | 1389.23 | 22.24 | 80.33 | 279.33 |
October | 317.67 | 0.64 | 0.62 | 01-OCT-07:40 | 2131.58 | 19.08 | 81.50 | 277.00 | 1284.78 | 22.47 | 99.17 | 236.67 |
November | 269.50 | 0.65 | 0.62 | 01-NOV-07:49 | 1414.62 | 19.43 | 80.17 | 218.83 | 755.59 | 20.93 | 66.00 | 176.83 |
December | 236.83 | 0.65 | 0.62 | 01-DEC-08:50 | 1208.90 | 19.68 | 79.83 | 193.33 | 762.02 | 23.32 | 81.50 | 146.33 |
Annual Sum or Average | 3965.83 | 0.64 | 2711.96 | 19.63 | 1038.00 | 3703.50 | 1396.01 | 22.14 | 917.83 | 3230.17 | ||
Minimum of Months | 226.83 | 0.62 | 0.62 | 1208.90 | 18.71 | 65.17 | 193.33 | 755.59 | 20.93 | 57.83 | 146.33 | |
Maximum of Months | 434.17 | 0.65 | 0.62 | 4150.50 | 20.64 | 112.67 | 412.50 | 1894.84 | 23.32 | 99.17 | 381.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.67 | 0.62 | 01-JAN-09:39 | 510.19 | 9.96 | 0.00 | 174.50 | 305.54 | 14.07 | 0.00 | 79.83 |
February | 275.00 | 0.65 | 0.62 | 01-FEB-10:09 | 556.85 | 11.00 | 0.00 | 213.33 | 348.31 | 15.21 | 0.00 | 140.17 |
March | 304.00 | 0.63 | 0.62 | 01-MAR-07:00 | 885.27 | 13.39 | 0.00 | 301.50 | 525.21 | 17.36 | 0.00 | 250.67 |
April | 325.17 | 0.63 | 0.62 | 01-APR-08:39 | 921.46 | 14.22 | 0.00 | 344.50 | 555.76 | 18.21 | 0.00 | 287.33 |
May | 385.83 | 0.63 | 0.62 | 01-MAY-05:49 | 1147.83 | 16.52 | 38.17 | 405.00 | 677.64 | 20.19 | 42.67 | 367.67 |
June | 434.17 | 0.63 | 0.62 | 01-JUN-13:39 | 1191.04 | 18.63 | 96.33 | 433.17 | 665.78 | 18.82 | 6.17 | 398.17 |
July | 417.33 | 0.62 | 0.62 | 01-JUL-06:40 | 1166.26 | 18.05 | 72.17 | 419.50 | 674.97 | 19.06 | 15.33 | 388.33 |
August | 421.33 | 0.63 | 0.62 | 01-AUG-05:40 | 899.00 | 13.83 | 0.00 | 392.50 | 581.12 | 17.91 | 0.33 | 362.83 |
September | 352.17 | 0.64 | 0.62 | 01-SEP-06:49 | 731.79 | 12.79 | 0.00 | 313.17 | 461.03 | 16.79 | 0.00 | 250.67 |
October | 317.67 | 0.65 | 0.62 | 01-OCT-07:49 | 604.05 | 11.49 | 0.00 | 255.00 | 373.49 | 15.63 | 0.00 | 178.33 |
November | 269.50 | 0.66 | 0.62 | 01-NOV-08:09 | 477.89 | 9.98 | 0.00 | 187.33 | 291.66 | 14.20 | 0.00 | 76.83 |
December | 236.83 | 0.67 | 0.62 | 01-DEC-09:09 | 414.29 | 9.20 | 0.00 | 156.17 | 252.27 | 13.45 | 0.00 | 26.83 |
Annual Sum or Average | 3965.83 | 0.64 | 842.09 | 13.83 | 206.67 | 3595.67 | 504.78 | 17.13 | 64.50 | 2807.67 | ||
Minimum of Months | 226.83 | 0.62 | 0.62 | 414.29 | 9.20 | 0.00 | 156.17 | 252.27 | 13.45 | 0.00 | 26.83 | |
Maximum of Months | 434.17 | 0.67 | 0.62 | 1191.04 | 18.63 | 96.33 | 433.17 | 677.64 | 20.19 | 42.67 | 398.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.66 | 0.62 | 01-JAN-09:39 | 1436.89 | 19.11 | 68.33 | 197.67 | 894.45 | 22.24 | 69.33 | 153.50 |
February | 275.00 | 0.64 | 0.62 | 01-FEB-10:09 | 1908.14 | 19.77 | 77.17 | 232.83 | 1070.74 | 23.02 | 91.00 | 200.67 |
March | 304.00 | 0.63 | 0.62 | 01-MAR-07:00 | 2696.61 | 21.05 | 91.33 | 307.00 | 1467.20 | 22.82 | 94.33 | 272.17 |
April | 325.17 | 0.63 | 0.62 | 01-APR-08:39 | 2681.15 | 19.31 | 75.83 | 337.67 | 1564.00 | 21.26 | 48.00 | 299.50 |
May | 385.83 | 0.63 | 0.62 | 01-MAY-06:19 | 3157.81 | 18.23 | 74.50 | 391.33 | 1464.82 | 18.47 | 0.00 | 352.67 |
June | 434.17 | 0.63 | 0.62 | 01-JUN-13:39 | 3222.16 | 16.25 | 52.00 | 412.67 | 1457.19 | 18.12 | 0.17 | 374.50 |
July | 417.33 | 0.63 | 0.62 | 01-JUL-06:40 | 3772.43 | 18.30 | 79.67 | 400.00 | 1695.71 | 18.48 | 3.67 | 365.33 |
August | 421.33 | 0.64 | 0.62 | 01-AUG-06:30 | 2943.47 | 18.08 | 88.17 | 377.83 | 1591.77 | 20.11 | 56.33 | 341.83 |
September | 352.17 | 0.64 | 0.62 | 01-SEP-06:00 | 2946.03 | 20.11 | 98.33 | 317.00 | 1159.23 | 20.37 | 51.83 | 279.00 |
October | 317.67 | 0.64 | 0.62 | 01-OCT-07:00 | 1907.57 | 19.22 | 80.50 | 273.67 | 1028.68 | 21.22 | 75.17 | 232.83 |
November | 269.50 | 0.65 | 0.62 | 01-NOV-08:09 | 1625.17 | 19.55 | 81.50 | 216.00 | 970.51 | 22.94 | 89.83 | 175.50 |
December | 236.83 | 0.65 | 0.62 | 01-DEC-09:09 | 1157.91 | 19.74 | 76.67 | 196.83 | 632.18 | 20.89 | 65.00 | 147.33 |
Annual Sum or Average | 3965.83 | 0.64 | 2604.71 | 18.89 | 944.00 | 3660.50 | 1304.75 | 20.54 | 644.67 | 3194.83 | ||
Minimum of Months | 226.83 | 0.63 | 0.62 | 1157.91 | 16.25 | 52.00 | 196.83 | 632.18 | 18.12 | 0.00 | 147.33 | |
Maximum of Months | 434.17 | 0.66 | 0.62 | 3772.43 | 21.05 | 98.33 | 412.67 | 1695.71 | 23.02 | 94.33 | 374.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.64 | 0.62 | 01-JAN-08:50 | 5184.36 | 32.03 | 185.17 | 223.00 | 4569.79 | 37.29 | 215.17 | 208.00 |
February | 275.00 | 0.63 | 0.62 | 01-FEB-08:20 | 7274.80 | 33.79 | 239.83 | 250.50 | 3105.96 | 30.24 | 179.67 | 243.00 |
March | 304.00 | 0.63 | 0.62 | 01-MAR-07:49 | 8613.46 | 31.62 | 252.33 | 316.17 | 1646.45 | 19.14 | 14.17 | 286.00 |
April | 325.17 | 0.63 | 0.62 | 01-APR-08:39 | 1996.27 | 14.49 | 0.00 | 341.17 | 1141.60 | 18.49 | 5.67 | 299.83 |
May | 385.83 | 0.63 | 0.62 | 01-MAY-06:10 | 1766.28 | 14.37 | 0.00 | 386.50 | 992.50 | 18.30 | 0.83 | 340.67 |
June | 434.17 | 0.64 | 0.62 | 01-JUN-13:39 | 1504.95 | 13.90 | 0.00 | 397.17 | 878.07 | 17.91 | 0.00 | 346.33 |
July | 417.33 | 0.63 | 0.62 | 01-JUL-06:40 | 1615.06 | 14.34 | 0.00 | 394.50 | 969.03 | 18.39 | 0.83 | 354.00 |
August | 421.33 | 0.64 | 0.62 | 01-AUG-06:19 | 1730.60 | 13.66 | 0.00 | 373.50 | 1036.32 | 17.68 | 0.83 | 332.00 |
September | 352.17 | 0.64 | 0.62 | 01-SEP-06:49 | 2503.08 | 15.30 | 29.50 | 319.67 | 1232.23 | 17.88 | 10.67 | 288.67 |
October | 317.67 | 0.63 | 0.62 | 01-OCT-07:40 | 7452.68 | 33.11 | 274.83 | 295.33 | 2041.78 | 22.32 | 80.83 | 279.83 |
November | 269.50 | 0.64 | 0.62 | 01-NOV-07:49 | 5364.49 | 32.45 | 223.00 | 241.83 | 4937.27 | 37.86 | 260.67 | 236.83 |
December | 236.83 | 0.64 | 0.62 | 01-DEC-08:50 | 3922.39 | 29.52 | 169.00 | 223.33 | 3736.04 | 36.94 | 219.00 | 212.00 |
Annual Sum or Average | 3965.83 | 0.64 | 3733.36 | 21.65 | 1373.67 | 3762.67 | 1932.92 | 22.92 | 988.33 | 3427.17 | ||
Minimum of Months | 226.83 | 0.63 | 0.62 | 1504.95 | 13.66 | 0.00 | 223.00 | 878.07 | 17.68 | 0.00 | 208.00 | |
Maximum of Months | 434.17 | 0.64 | 0.62 | 8613.46 | 33.79 | 274.83 | 397.17 | 4937.27 | 37.86 | 260.67 | 354.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.65 | 0.62 | 01-JAN-08:50 | 1568.60 | 20.16 | 74.50 | 205.00 | 938.31 | 23.18 | 73.00 | 163.83 |
February | 275.00 | 0.64 | 0.62 | 01-FEB-08:09 | 1789.15 | 19.73 | 74.67 | 234.33 | 934.64 | 21.11 | 66.50 | 197.00 |
March | 304.00 | 0.63 | 0.62 | 01-MAR-07:40 | 2728.30 | 19.74 | 74.00 | 311.00 | 1592.18 | 22.98 | 94.67 | 274.17 |
April | 325.17 | 0.63 | 0.62 | 01-APR-08:39 | 2733.85 | 18.80 | 65.17 | 348.17 | 1601.47 | 22.37 | 60.17 | 303.83 |
May | 385.83 | 0.63 | 0.62 | 01-MAY-05:40 | 3134.20 | 19.69 | 95.83 | 397.50 | 1366.57 | 21.48 | 57.83 | 353.00 |
June | 434.17 | 0.63 | 0.62 | 01-JUN-13:39 | 3794.17 | 19.63 | 107.17 | 409.17 | 1647.84 | 21.78 | 78.33 | 375.00 |
July | 417.33 | 0.62 | 0.62 | 01-JUL-06:40 | 4150.50 | 20.64 | 110.67 | 412.50 | 1770.85 | 22.28 | 74.17 | 381.17 |
August | 421.33 | 0.63 | 0.62 | 01-AUG-05:40 | 3332.14 | 20.11 | 112.67 | 380.67 | 1894.79 | 22.07 | 86.17 | 343.00 |
September | 352.17 | 0.64 | 0.62 | 01-SEP-06:30 | 2418.16 | 18.71 | 81.83 | 316.00 | 1389.19 | 22.24 | 80.33 | 279.33 |
October | 317.67 | 0.64 | 0.62 | 01-OCT-07:40 | 2131.58 | 19.08 | 81.50 | 277.00 | 1284.74 | 22.48 | 99.17 | 236.67 |
November | 269.50 | 0.65 | 0.62 | 01-NOV-07:49 | 1414.62 | 19.43 | 80.17 | 218.83 | 755.56 | 20.93 | 66.00 | 176.83 |
December | 236.83 | 0.65 | 0.62 | 01-DEC-08:50 | 1208.90 | 19.68 | 79.83 | 193.33 | 761.99 | 23.32 | 81.50 | 146.33 |
Annual Sum or Average | 3965.83 | 0.64 | 2711.95 | 19.63 | 1038.00 | 3703.50 | 1395.96 | 22.14 | 917.83 | 3230.17 | ||
Minimum of Months | 226.83 | 0.62 | 0.62 | 1208.90 | 18.71 | 65.17 | 193.33 | 755.56 | 20.93 | 57.83 | 146.33 | |
Maximum of Months | 434.17 | 0.65 | 0.62 | 4150.50 | 20.64 | 112.67 | 412.50 | 1894.79 | 23.32 | 99.17 | 381.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.67 | 0.62 | 01-JAN-09:39 | 510.18 | 9.96 | 0.00 | 174.50 | 305.53 | 14.07 | 0.00 | 79.67 |
February | 275.00 | 0.65 | 0.62 | 01-FEB-10:09 | 556.85 | 11.00 | 0.00 | 213.33 | 348.29 | 15.21 | 0.00 | 140.00 |
March | 304.00 | 0.63 | 0.62 | 01-MAR-07:00 | 885.26 | 13.40 | 0.00 | 301.50 | 525.17 | 17.36 | 0.00 | 250.67 |
April | 325.17 | 0.63 | 0.62 | 01-APR-08:39 | 921.45 | 14.22 | 0.00 | 344.50 | 555.73 | 18.21 | 0.00 | 287.17 |
May | 385.83 | 0.63 | 0.62 | 01-MAY-05:49 | 1147.82 | 16.52 | 38.17 | 404.83 | 677.60 | 20.19 | 42.67 | 367.67 |
June | 434.17 | 0.63 | 0.62 | 01-JUN-13:39 | 1191.03 | 18.64 | 96.33 | 433.17 | 665.74 | 18.83 | 6.33 | 398.17 |
July | 417.33 | 0.62 | 0.62 | 01-JUL-06:40 | 1166.26 | 18.05 | 72.17 | 419.50 | 674.94 | 19.06 | 15.33 | 388.33 |
August | 421.33 | 0.63 | 0.62 | 01-AUG-05:40 | 899.00 | 13.83 | 0.00 | 392.50 | 581.09 | 17.91 | 0.33 | 362.83 |
September | 352.17 | 0.64 | 0.62 | 01-SEP-06:49 | 731.79 | 12.79 | 0.00 | 313.17 | 461.01 | 16.79 | 0.00 | 250.67 |
October | 317.67 | 0.65 | 0.62 | 01-OCT-07:49 | 604.04 | 11.49 | 0.00 | 255.00 | 373.47 | 15.63 | 0.00 | 178.33 |
November | 269.50 | 0.66 | 0.62 | 01-NOV-08:09 | 477.89 | 9.98 | 0.00 | 187.33 | 291.65 | 14.21 | 0.00 | 76.83 |
December | 236.83 | 0.67 | 0.62 | 01-DEC-09:09 | 414.29 | 9.20 | 0.00 | 156.17 | 252.25 | 13.45 | 0.00 | 26.83 |
Annual Sum or Average | 3965.83 | 0.64 | 842.09 | 13.83 | 206.67 | 3595.50 | 504.75 | 17.13 | 64.67 | 2807.17 | ||
Minimum of Months | 226.83 | 0.62 | 0.62 | 414.29 | 9.20 | 0.00 | 156.17 | 252.25 | 13.45 | 0.00 | 26.83 | |
Maximum of Months | 434.17 | 0.67 | 0.62 | 1191.03 | 18.64 | 96.33 | 433.17 | 677.60 | 20.19 | 42.67 | 398.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.66 | 0.62 | 01-JAN-09:39 | 1436.89 | 19.11 | 68.33 | 197.67 | 894.41 | 22.24 | 69.33 | 153.50 |
February | 275.00 | 0.64 | 0.62 | 01-FEB-10:09 | 1908.14 | 19.77 | 77.17 | 232.83 | 1070.71 | 23.02 | 91.17 | 200.67 |
March | 304.00 | 0.63 | 0.62 | 01-MAR-07:00 | 2696.59 | 21.05 | 91.33 | 307.00 | 1467.13 | 22.82 | 94.33 | 272.17 |
April | 325.17 | 0.63 | 0.62 | 01-APR-08:39 | 2681.14 | 19.31 | 75.83 | 337.67 | 1563.94 | 21.26 | 48.00 | 299.50 |
May | 385.83 | 0.63 | 0.62 | 01-MAY-06:19 | 3157.79 | 18.24 | 74.50 | 391.33 | 1464.76 | 18.47 | 0.00 | 352.67 |
June | 434.17 | 0.63 | 0.62 | 01-JUN-13:39 | 3222.14 | 16.25 | 52.00 | 412.67 | 1457.13 | 18.12 | 0.17 | 374.50 |
July | 417.33 | 0.63 | 0.62 | 01-JUL-06:40 | 3772.42 | 18.30 | 79.67 | 400.00 | 1695.65 | 18.48 | 3.67 | 365.33 |
August | 421.33 | 0.64 | 0.62 | 01-AUG-06:30 | 2943.46 | 18.08 | 88.17 | 377.83 | 1591.72 | 20.11 | 56.33 | 341.83 |
September | 352.17 | 0.64 | 0.62 | 01-SEP-06:00 | 2946.03 | 20.11 | 98.33 | 317.00 | 1159.18 | 20.37 | 51.83 | 279.00 |
October | 317.67 | 0.64 | 0.62 | 01-OCT-07:00 | 1907.57 | 19.22 | 80.50 | 273.67 | 1028.64 | 21.22 | 75.17 | 232.83 |
November | 269.50 | 0.65 | 0.62 | 01-NOV-08:09 | 1625.17 | 19.56 | 81.50 | 216.00 | 970.48 | 22.94 | 89.83 | 175.50 |
December | 236.83 | 0.65 | 0.62 | 01-DEC-09:09 | 1157.91 | 19.74 | 76.67 | 196.83 | 632.16 | 20.89 | 65.00 | 147.33 |
Annual Sum or Average | 3965.83 | 0.64 | 2604.70 | 18.89 | 944.00 | 3660.50 | 1304.70 | 20.54 | 644.83 | 3194.83 | ||
Minimum of Months | 226.83 | 0.63 | 0.62 | 1157.91 | 16.25 | 52.00 | 196.83 | 632.16 | 18.12 | 0.00 | 147.33 | |
Maximum of Months | 434.17 | 0.66 | 0.62 | 3772.42 | 21.05 | 98.33 | 412.67 | 1695.65 | 23.02 | 94.33 | 374.50 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.415180E+09 | 23537.44 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 58963557.16 | 23537.44 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9817302.09 | 23537.44 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 30273856.26 | 23537.44 | 26-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.514234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.415180E+09 | 23537.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113219E+11 | 12856.14 | 12-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.686142E+10 | 12862.95 | 07-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.586340E+10 | 12845.28 | 24-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.334070E+10 | 12890.71 | 20-APR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.279185E+10 | 13309.86 | 22-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.698907E+09 | 13031.09 | 16-JUN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143861E+09 | 13162.72 | 05-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.512731E+09 | 13128.04 | 21-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103114E+10 | 13119.92 | 27-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.178105E+10 | 13061.53 | 20-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.417225E+10 | 12804.43 | 09-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.781334E+10 | 12851.34 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.463325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.143861E+09 | 12804.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113219E+11 | 13309.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.465493E+10 | 9788.85 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.229337E+10 | 9777.67 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130632E+10 | 9726.21 | 20-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.307222E+09 | 9730.10 | 21-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136299E+09 | 9730.82 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2447298.66 | 3434.49 | 20-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 57483784.30 | 9713.64 | 06-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.878779E+09 | 9724.32 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.269098E+10 | 9719.49 | 19-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.465493E+10 | 9788.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.734481E+10 | 8000.08 | 12-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.407815E+10 | 8005.30 | 07-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.255188E+10 | 7967.89 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.688194E+09 | 7987.23 | 21-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.285700E+09 | 7970.33 | 23-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8146213.42 | 7954.33 | 19-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121762E+09 | 7968.83 | 05-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141670E+10 | 7960.74 | 06-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.427750E+10 | 7999.83 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.734481E+10 | 8005.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.498618E+10 | 10790.15 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.248185E+10 | 10777.91 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159852E+10 | 10739.68 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.430344E+09 | 10725.33 | 21-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.177731E+09 | 10721.49 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1476727.16 | 2079.26 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6347163.68 | 4379.22 | 19-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84612746.88 | 10707.16 | 06-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.950228E+09 | 10719.07 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.289797E+10 | 10713.75 | 19-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.498618E+10 | 10790.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.407535E+10 | 28485.04 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142166E+10 | 28485.04 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.580565E+09 | 28485.04 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40120020.50 | 28485.04 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16196257.86 | 28485.04 | 10-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.552751E+09 | 28485.04 | 13-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196698E+10 | 28485.04 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.865361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.407535E+10 | 28485.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.519737E+10 | 14802.59 | 10-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217376E+10 | 14821.52 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129639E+10 | 14733.98 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.294836E+09 | 14648.81 | 21-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.247312E+09 | 14773.67 | 09-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1179788.26 | 2521.37 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7303.65 | 48.69 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20520057.60 | 14228.69 | 19-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147912E+09 | 14733.38 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123495E+10 | 14765.51 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.314143E+10 | 14789.29 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.519737E+10 | 14821.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.477873E+10 | 11759.49 | 09-JAN-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.225680E+10 | 11751.01 | 10-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122131E+10 | 11699.67 | 08-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.234811E+09 | 11675.27 | 21-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151402E+09 | 11728.48 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27649503.95 | 9182.83 | 19-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201593E+09 | 11656.45 | 04-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131843E+10 | 11696.44 | 28-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.318889E+10 | 11762.78 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.477873E+10 | 11762.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.716109E+10 | 9070.41 | 12-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.343255E+10 | 9079.78 | 22-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172101E+10 | 9086.73 | 10-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.266495E+09 | 9032.70 | 28-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183243E+09 | 9084.77 | 09-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17954067.57 | 8960.62 | 20-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.226742E+09 | 9061.61 | 10-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171990E+10 | 9069.05 | 20-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.454858E+10 | 9094.42 | 20-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.716109E+10 | 9094.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.499177E+10 | 12018.65 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.239649E+10 | 12018.65 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143878E+10 | 12018.65 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.318666E+09 | 12018.65 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205440E+09 | 12018.65 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2631078.41 | 3390.43 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1315641.63 | 2175.81 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40760692.78 | 9214.28 | 19-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.257634E+09 | 12018.65 | 04-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137638E+10 | 12018.65 | 02-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331784E+10 | 12018.65 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.499177E+10 | 12018.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101790E+11 | 33112.07 | 13-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.484250E+10 | 33149.36 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.259820E+10 | 33132.13 | 21-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.441034E+09 | 33120.16 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.420494E+09 | 33069.80 | 09-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 22497909.96 | 31724.55 | 19-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.335432E+09 | 33174.65 | 05-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.277286E+10 | 33126.14 | 06-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.690606E+10 | 33158.35 | 20-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.101790E+11 | 33174.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.839262E+10 | 16353.13 | 17-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.399674E+10 | 16305.90 | 07-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.294192E+10 | 16310.18 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101434E+10 | 16351.48 | 29-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.725704E+09 | 16321.44 | 08-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33871051.13 | 10514.98 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 166258.90 | 554.20 | 08-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12218475.20 | 9784.16 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.204620E+09 | 16207.76 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.705324E+09 | 16323.70 | 10-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.266885E+10 | 16335.77 | 29-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.585728E+10 | 16334.93 | 22-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 166258.90 | 554.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.839262E+10 | 16353.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.698451E+10 | 11974.93 | 30-JAN-05:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.354833E+10 | 11975.26 | 04-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.228938E+10 | 11956.42 | 20-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.641049E+09 | 11941.20 | 28-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.385181E+09 | 11964.35 | 08-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8719772.06 | 7073.43 | 16-JUN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3985494.63 | 1758.03 | 18-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149857E+09 | 11912.63 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.622213E+09 | 11969.34 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.242433E+10 | 11978.54 | 13-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.515075E+10 | 11971.20 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.698451E+10 | 11978.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107965E+11 | 10510.42 | 24-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.579147E+10 | 10524.44 | 15-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366622E+10 | 10521.20 | 15-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.985088E+09 | 10501.43 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.602741E+09 | 10529.08 | 23-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9353168.23 | 8482.23 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4413217.14 | 8143.05 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.195894E+09 | 10452.40 | 13-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.959653E+09 | 10537.46 | 04-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.368417E+10 | 10531.14 | 09-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.795708E+10 | 10514.15 | 20-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.346526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107965E+11 | 10537.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.742919E+10 | 13725.32 | 07-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.390968E+10 | 13703.15 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.279483E+10 | 13684.64 | 08-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.906299E+09 | 13705.72 | 28-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.566138E+09 | 13717.66 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35284216.72 | 6738.13 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 378343.86 | 596.42 | 08-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15548261.42 | 6360.04 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.239110E+09 | 13673.05 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.860752E+09 | 13663.79 | 06-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.271378E+10 | 13748.80 | 13-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.549573E+10 | 13726.23 | 28-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.249667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 378343.86 | 596.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.742919E+10 | 13748.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.197077E+11 | 40343.78 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108260E+11 | 32949.51 | 01-FEB-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.623512E+10 | 29178.00 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141342E+10 | 12571.98 | 29-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.816560E+09 | 9974.71 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2431703.70 | 1417.87 | 16-JUN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 82878658.22 | 3682.56 | 19-SEP-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.885643E+09 | 13054.38 | 10-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.445448E+10 | 22473.82 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126139E+11 | 36856.89 | 29-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.570382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.197077E+11 | 40343.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.201874E+11 | 39599.66 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116703E+11 | 33152.31 | 01-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.757778E+10 | 28746.81 | 06-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.238843E+10 | 14152.35 | 29-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145819E+10 | 11401.09 | 08-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 43844437.45 | 4063.96 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.337774E+09 | 5535.18 | 19-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164366E+10 | 14430.38 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.554149E+10 | 23631.83 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137653E+11 | 34639.97 | 29-DEC-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.646141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.201874E+11 | 39599.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.232479E+11 | 43166.71 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128456E+11 | 37062.08 | 01-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.853218E+10 | 32055.98 | 04-MAR-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.282138E+10 | 16518.62 | 29-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166432E+10 | 13368.78 | 08-MAY-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108074E+09 | 5664.48 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2876514.44 | 1402.18 | 18-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.528594E+09 | 7457.28 | 19-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208883E+10 | 16795.67 | 10-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.637703E+10 | 22545.20 | 27-NOV-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158591E+11 | 38256.77 | 29-DEC-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.740759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.232479E+11 | 43166.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.150890E+09 | 0.150833E+09 | 11233.52 | 27-FEB-15:40 | 11233.52 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.169334E+10 | 0.168245E+10 | 25724.09 | 07-APR-14:00 | 25724.09 | 0.00 |
May | 0.00 | 0.00 | 0.705633E+10 | 0.687655E+10 | 52133.12 | 19-MAY-15:40 | 52133.12 | 0.00 |
June | 0.00 | 0.00 | 0.274812E+11 | 0.262610E+11 | 66317.63 | 20-JUN-16:10 | 53449.08 | 0.00 |
July | 0.00 | 0.00 | 0.484798E+11 | 0.468071E+11 | 79917.12 | 17-JUL-16:00 | 79917.12 | 0.00 |
August | 0.00 | 0.00 | 0.411628E+11 | 0.407512E+11 | 73426.30 | 07-AUG-16:00 | 73426.30 | 0.00 |
September | 0.00 | 0.00 | 0.193283E+11 | 0.176771E+11 | 104277.46 | 07-SEP-15:00 | 55028.79 | 0.00 |
October | 0.00 | 0.00 | 0.410638E+10 | 0.408490E+10 | 47241.06 | 18-OCT-15:40 | 47241.06 | 0.00 |
November | 0.00 | 0.00 | 0.149120E+09 | 0.143613E+09 | 5670.75 | 17-NOV-17:00 | 5636.31 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.149608E+12 | 0.144435E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.484798E+11 | 0.468071E+11 | 104277.46 | 79917.12 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.153035E+09 | 0.153035E+09 | 10552.65 | 27-FEB-15:30 | 10552.65 | 0.00 |
March | 0.00 | 0.00 | 1055157.94 | 1055157.94 | 267.71 | 14-MAR-13:40 | 267.71 | 0.00 |
April | 0.00 | 0.00 | 0.179162E+10 | 0.178360E+10 | 26306.95 | 06-APR-16:00 | 26306.95 | 0.00 |
May | 0.00 | 0.00 | 0.731576E+10 | 0.716954E+10 | 53140.33 | 19-MAY-15:30 | 53140.33 | 0.00 |
June | 0.00 | 0.00 | 0.265844E+11 | 0.254784E+11 | 63146.55 | 29-JUN-14:50 | 63146.55 | 0.00 |
July | 0.00 | 0.00 | 0.449729E+11 | 0.436526E+11 | 78089.68 | 17-JUL-15:40 | 78089.68 | 0.00 |
August | 0.00 | 0.00 | 0.376795E+11 | 0.373301E+11 | 73862.98 | 07-AUG-15:30 | 73862.98 | 0.00 |
September | 0.00 | 0.00 | 0.173478E+11 | 0.159841E+11 | 94273.78 | 07-SEP-14:55 | 49761.76 | 0.00 |
October | 0.00 | 0.00 | 0.339934E+10 | 0.338494E+10 | 41383.64 | 18-OCT-15:50 | 41383.64 | 0.00 |
November | 0.00 | 0.00 | 0.139182E+09 | 0.132441E+09 | 5152.41 | 04-NOV-14:00 | 5152.41 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.139384E+12 | 0.135070E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.449729E+11 | 0.436526E+11 | 94273.78 | 78089.68 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.144329E+09 | 0.144329E+09 | 10392.57 | 27-FEB-15:30 | 10392.57 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.180611E+10 | 0.179397E+10 | 27931.10 | 06-APR-16:00 | 27931.10 | 0.00 |
May | 0.00 | 0.00 | 0.781200E+10 | 0.760038E+10 | 62837.47 | 19-MAY-15:30 | 62837.47 | 0.00 |
June | 0.00 | 0.00 | 0.287658E+11 | 0.274802E+11 | 72869.08 | 29-JUN-14:50 | 72869.08 | 0.00 |
July | 0.00 | 0.00 | 0.486023E+11 | 0.470883E+11 | 91272.12 | 17-JUL-15:30 | 91272.12 | 0.00 |
August | 0.00 | 0.00 | 0.401235E+11 | 0.396336E+11 | 86986.52 | 06-AUG-16:11 | 86986.52 | 0.00 |
September | 0.00 | 0.00 | 0.179041E+11 | 0.163678E+11 | 96571.79 | 07-SEP-15:20 | 52325.85 | 0.00 |
October | 0.00 | 0.00 | 0.317856E+10 | 0.314565E+10 | 42840.50 | 18-OCT-15:00 | 42840.50 | 0.00 |
November | 0.00 | 0.00 | 0.138338E+09 | 0.127735E+09 | 4961.93 | 04-NOV-14:00 | 4961.93 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.148475E+12 | 0.143382E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.486023E+11 | 0.470883E+11 | 96571.79 | 91272.12 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2042.90 | 7214.65 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2088.53 | 7250.43 | 22-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2204.18 | 7225.52 | 03-MAR-12:13 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1988.21 | 7013.02 | 04-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1955.50 | 6709.83 | 02-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1889.99 | 6333.19 | 01-JUN-11:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1652.74 | 5949.83 | 05-JUL-11:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1778.71 | 5758.39 | 02-AUG-11:09 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1683.64 | 5878.69 | 28-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1754.34 | 6235.12 | 31-OCT-11:06 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1884.06 | 6628.84 | 30-NOV-12:08 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1909.82 | 6972.44 | 29-DEC-12:09 |
Annual Sum or Average | 0.00 | 1901.64 | ||||
Minimum of Months | 0.00 | 0.00 | 1652.74 | 5758.39 | ||
Maximum of Months | 0.00 | 0.00 | 2204.18 | 7250.43 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.189143E+10 | 0.40 | 3061.26 | 10-JAN-07:02 | 0.91 |
February | 0.155323E+10 | 0.36 | 3061.26 | 06-FEB-06:01 | 0.90 |
March | 0.186235E+10 | 0.37 | 3061.26 | 06-MAR-07:01 | 0.91 |
April | 0.192530E+10 | 0.35 | 3438.35 | 25-APR-16:00 | 0.96 |
May | 0.253005E+10 | 0.39 | 8246.49 | 22-MAY-06:01 | 1.61 |
June | 0.468951E+10 | 0.54 | 10659.03 | 29-JUN-12:10 | 1.89 |
July | 0.610504E+10 | 0.61 | 13034.62 | 25-JUL-12:08 | 2.14 |
August | 0.594610E+10 | 0.60 | 10080.40 | 11-AUG-12:10 | 1.83 |
September | 0.382051E+10 | 0.48 | 13034.62 | 07-SEP-15:00 | 2.12 |
October | 0.247408E+10 | 0.38 | 5430.46 | 18-OCT-16:00 | 1.25 |
November | 0.175189E+10 | 0.34 | 3158.94 | 03-NOV-15:30 | 0.91 |
December | 0.164358E+10 | 0.35 | 3061.26 | 26-DEC-07:02 | 0.90 |
Annual Sum or Average | 0.361931E+11 | 0.43 | |||
Minimum of Months | 0.155323E+10 | 0.34 | 3061.26 | 0.90 | |
Maximum of Months | 0.610504E+10 | 0.61 | 13034.62 | 2.14 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.190103E+10 | 0.41 | 3075.42 | 09-JAN-07:03 | 0.96 |
February | 0.155630E+10 | 0.37 | 3075.42 | 10-FEB-06:01 | 0.96 |
March | 0.176805E+10 | 0.37 | 3075.42 | 20-MAR-06:01 | 0.96 |
April | 0.173478E+10 | 0.35 | 4605.89 | 25-APR-16:00 | 1.21 |
May | 0.231367E+10 | 0.39 | 7707.07 | 19-MAY-15:30 | 1.64 |
June | 0.448310E+10 | 0.55 | 9891.20 | 29-JUN-14:30 | 1.92 |
July | 0.591841E+10 | 0.62 | 11759.50 | 17-JUL-11:02 | 2.14 |
August | 0.550318E+10 | 0.60 | 11759.50 | 07-AUG-15:40 | 2.14 |
September | 0.310007E+10 | 0.45 | 11759.50 | 07-SEP-14:55 | 2.12 |
October | 0.188236E+10 | 0.35 | 5467.54 | 18-OCT-15:50 | 1.33 |
November | 0.156541E+10 | 0.34 | 3075.42 | 14-NOV-07:01 | 0.96 |
December | 0.171920E+10 | 0.38 | 3075.42 | 27-DEC-06:01 | 0.96 |
Annual Sum or Average | 0.334456E+11 | 0.43 | |||
Minimum of Months | 0.155630E+10 | 0.34 | 3075.42 | 0.96 | |
Maximum of Months | 0.591841E+10 | 0.62 | 11759.50 | 2.14 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.241282E+10 | 0.47 | 3082.51 | 04-JAN-07:01 | 0.89 |
February | 0.179003E+10 | 0.40 | 3082.51 | 07-FEB-07:01 | 0.88 |
March | 0.192723E+10 | 0.39 | 3082.51 | 08-MAR-07:01 | 0.89 |
April | 0.173341E+10 | 0.34 | 4394.65 | 25-APR-16:00 | 1.08 |
May | 0.226128E+10 | 0.38 | 7900.53 | 19-MAY-15:30 | 1.52 |
June | 0.412909E+10 | 0.50 | 9842.29 | 29-JUN-14:50 | 1.74 |
July | 0.549152E+10 | 0.55 | 13646.52 | 17-JUL-15:10 | 2.14 |
August | 0.498913E+10 | 0.53 | 12991.45 | 07-AUG-15:40 | 2.07 |
September | 0.276658E+10 | 0.41 | 9708.01 | 01-SEP-16:00 | 1.72 |
October | 0.177384E+10 | 0.34 | 4548.68 | 18-OCT-15:30 | 1.10 |
November | 0.174932E+10 | 0.37 | 3082.51 | 10-NOV-07:01 | 0.88 |
December | 0.219662E+10 | 0.45 | 3082.51 | 20-DEC-07:01 | 0.88 |
Annual Sum or Average | 0.332209E+11 | 0.43 | |||
Minimum of Months | 0.173341E+10 | 0.34 | 3082.51 | 0.88 | |
Maximum of Months | 0.549152E+10 | 0.55 | 13646.52 | 2.14 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:03 | 0.22 | 0.22 | 57.62 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:01 | 0.22 | 0.22 | 55.53 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:01 | 0.22 | 0.22 | 55.99 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:01 | 0.22 | 0.22 | 55.80 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:01 | 0.22 | 0.22 | 55.96 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 55.85 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 56.08 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 55.70 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 56.23 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 56.52 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:03 | 0.22 | 0.22 | 55.56 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:01 | 0.22 | 0.22 | 56.35 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 55.53 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.62 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.55 | 57.55 | 2042.90 | 7214.65 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 55.98 | 55.98 | 2088.53 | 7250.43 | 22-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.46 | 56.46 | 2204.18 | 7225.52 | 03-MAR-12:13 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.48 | 56.48 | 1988.21 | 7013.02 | 04-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.53 | 56.53 | 1955.50 | 6709.83 | 02-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.31 | 56.31 | 1889.99 | 6333.19 | 01-JUN-11:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.50 | 56.50 | 1652.74 | 5949.83 | 05-JUL-11:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.12 | 56.12 | 1778.71 | 5758.39 | 02-AUG-11:09 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.62 | 56.62 | 1683.64 | 5878.69 | 28-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.85 | 55.85 | 1754.34 | 6235.12 | 31-OCT-11:06 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.05 | 56.05 | 1884.06 | 6628.84 | 30-NOV-12:08 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.82 | 56.82 | 1909.82 | 6972.44 | 29-DEC-12:09 |
Annual Sum or Average | 0.00 | 1901.64 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.85 | 55.85 | 1652.74 | 5758.39 | ||
Maximum of Months | 0.00 | 0.00 | 57.55 | 57.55 | 2204.18 | 7250.43 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.306144E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.173686E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.131923E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.714209E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.773396E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.123046E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.188167E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.170006E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.975729E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.555408E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.921265E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.193536E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.168051E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.555408E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.306144E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.281053E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.132796E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.802641E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.332355E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.499684E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.111546E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.175743E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.151748E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.759920E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.359762E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.780779E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.178829E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.138523E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.332355E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.281053E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.461946E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.239189E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.162178E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.620482E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.695809E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.114829E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.181967E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.154299E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.816553E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.608297E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.160532E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.335635E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.208469E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.608297E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.461946E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.189143E+10 | 0.00 | 0.484307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155323E+10 | 0.150890E+09 | 0.265998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186235E+10 | 0.00 | 0.175651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192530E+10 | 0.169334E+10 | 0.617988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.253005E+10 | 0.705633E+10 | 0.420813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.468951E+10 | 0.274812E+11 | 0.702815E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.610504E+10 | 0.484798E+11 | 0.143861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.594610E+10 | 0.411628E+11 | 0.512731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.382051E+10 | 0.193283E+11 | 0.113096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.247408E+10 | 0.410638E+10 | 0.293055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.175189E+10 | 0.149120E+09 | 0.118724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164358E+10 | 0.00 | 0.303240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.361931E+11 | 0.149608E+12 | 0.150601E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155323E+10 | 0.00 | 0.143861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.610504E+10 | 0.484798E+11 | 0.484307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.190103E+10 | 0.00 | 0.463917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155630E+10 | 0.153035E+09 | 0.233516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176805E+10 | 1055157.94 | 0.138358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173478E+10 | 0.179162E+10 | 0.350324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.231367E+10 | 0.731576E+10 | 0.228570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.448310E+10 | 0.265844E+11 | 47655304.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.591841E+10 | 0.449729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.550318E+10 | 0.376795E+11 | 1322945.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.310007E+10 | 0.173478E+11 | 0.444659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.188236E+10 | 0.339934E+10 | 0.249374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156541E+10 | 0.139182E+09 | 0.117439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171920E+10 | 0.00 | 0.299290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.334456E+11 | 0.139384E+12 | 0.134028E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.591841E+10 | 0.449729E+11 | 0.463917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.241282E+10 | 0.00 | 0.670297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179003E+10 | 0.144329E+09 | 0.349343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192723E+10 | 0.00 | 0.228227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173341E+10 | 0.180611E+10 | 0.680919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.226128E+10 | 0.781200E+10 | 0.436458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.412909E+10 | 0.287658E+11 | 0.195302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.549152E+10 | 0.486023E+11 | 544602.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.498913E+10 | 0.401235E+11 | 39041962.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.276658E+10 | 0.179041E+11 | 0.134057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177384E+10 | 0.317856E+10 | 0.557220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174932E+10 | 0.138338E+09 | 0.206410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219662E+10 | 0.00 | 0.472260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.332209E+11 | 0.148475E+12 | 0.210975E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.173341E+10 | 0.00 | 544602.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.549152E+10 | 0.486023E+11 | 0.670297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.189143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155323E+10 | 0.00 | 0.00 | 0.00 | 41585266.51 | 0.157738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192530E+10 | 0.00 | 0.00 | 0.00 | 0.450331E+09 | 0.476646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.253005E+10 | 0.00 | 0.00 | 0.00 | 0.181234E+10 | 0.339157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.468951E+10 | 0.00 | 0.00 | 0.00 | 0.691474E+10 | 0.700384E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.610504E+10 | 0.00 | 0.00 | 0.00 | 0.125678E+11 | 0.143861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.594610E+10 | 0.00 | 0.00 | 0.00 | 0.105417E+11 | 0.512731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.382051E+10 | 0.00 | 0.00 | 0.00 | 0.488870E+10 | 0.104808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.247408E+10 | 0.00 | 0.00 | 0.00 | 0.103509E+10 | 0.204491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.175189E+10 | 0.00 | 0.00 | 0.00 | 42801190.83 | 0.741796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.361931E+11 | 0.00 | 0.00 | 0.00 | 0.382952E+11 | 0.935627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.610504E+10 | 0.00 | 0.00 | 0.00 | 0.125678E+11 | 0.287230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.190103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155630E+10 | 0.00 | 0.00 | 0.00 | 42043651.68 | 0.116813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176805E+10 | 0.00 | 0.00 | 0.00 | 311734.37 | 0.625805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173478E+10 | 0.00 | 0.00 | 0.00 | 0.473963E+09 | 0.111481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.231367E+10 | 0.00 | 0.00 | 0.00 | 0.185566E+10 | 0.827517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.448310E+10 | 0.00 | 0.00 | 0.00 | 0.666768E+10 | 3810866.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.591841E+10 | 0.00 | 0.00 | 0.00 | 0.116558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.550318E+10 | 0.00 | 0.00 | 0.00 | 0.967032E+10 | 1322945.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.310007E+10 | 0.00 | 0.00 | 0.00 | 0.439224E+10 | 0.106884E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.188236E+10 | 0.00 | 0.00 | 0.00 | 0.865184E+09 | 0.850077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156541E+10 | 0.00 | 0.00 | 0.00 | 39979927.88 | 0.620241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.334456E+11 | 0.00 | 0.00 | 0.00 | 0.356632E+11 | 0.694142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.591841E+10 | 0.00 | 0.00 | 0.00 | 0.116558E+11 | 0.262043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.241282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179003E+10 | 0.00 | 0.00 | 0.00 | 40134322.31 | 0.220887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173341E+10 | 0.00 | 0.00 | 0.00 | 0.483604E+09 | 0.398781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.226128E+10 | 0.00 | 0.00 | 0.00 | 0.199655E+10 | 0.270026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.412909E+10 | 0.00 | 0.00 | 0.00 | 0.726662E+10 | 87228208.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.549152E+10 | 0.00 | 0.00 | 0.00 | 0.127047E+11 | 544602.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.498913E+10 | 0.00 | 0.00 | 0.00 | 0.104046E+11 | 36165448.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.276658E+10 | 0.00 | 0.00 | 0.00 | 0.458697E+10 | 0.811979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177384E+10 | 0.00 | 0.00 | 0.00 | 0.825760E+09 | 0.348337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174932E+10 | 0.00 | 0.00 | 0.00 | 39853413.55 | 0.142640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.332209E+11 | 0.00 | 0.00 | 0.00 | 0.383488E+11 | 0.136899E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.173341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 544602.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.549152E+10 | 0.00 | 0.00 | 0.00 | 0.127047E+11 | 0.437818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139946E+11 | 0.00 | 0.00 | 1283864.54 | 0.00 | 0.441138E+09 | 0.276075E+10 | 0.00 | 0.27 |
February | 0.915404E+10 | 0.00 | 0.00 | 8910370.87 | 0.00 | 23592247.16 | 0.542191E+10 | 0.00 | 0.32 |
March | 0.626824E+10 | 0.00 | 0.00 | 22227815.43 | 0.00 | 2358663.03 | 0.110530E+11 | 0.00 | 0.39 |
April | 0.224153E+10 | 0.00 | 0.00 | 29183548.06 | 0.00 | 0.00 | 0.142089E+11 | 0.00 | 0.56 |
May | 0.150400E+10 | 17910613.35 | 0.00 | 35638476.41 | 2882926.49 | 0.00 | 0.162696E+11 | 0.00 | 0.75 |
June | 0.818293E+09 | 0.196961E+09 | 0.00 | 41651586.72 | 20760484.75 | 0.00 | 0.155350E+11 | 0.00 | 1.07 |
July | 0.709148E+09 | 0.409774E+09 | 0.00 | 34818237.98 | 17540985.11 | 0.00 | 0.846916E+10 | 0.00 | 0.91 |
August | 0.720805E+09 | 0.222304E+09 | 0.00 | 42580606.90 | 18898810.19 | 0.00 | 0.132245E+11 | 0.00 | 1.07 |
September | 0.831190E+09 | 0.270537E+09 | 0.00 | 40560265.12 | 15920672.36 | 0.00 | 0.168326E+11 | 0.00 | 0.97 |
October | 0.131959E+10 | 0.00 | 0.00 | 38628067.09 | 0.00 | 0.00 | 0.177925E+11 | 0.00 | 0.72 |
November | 0.419075E+10 | 0.00 | 0.00 | 23528696.52 | 0.00 | 0.00 | 0.119844E+11 | 0.00 | 0.45 |
December | 0.982186E+10 | 0.00 | 0.00 | 11469660.16 | 0.00 | 8051153.83 | 0.613049E+10 | 0.00 | 0.29 |
Annual Sum or Average | 0.515741E+11 | 0.111749E+10 | 0.00 | 0.330481E+09 | 76003878.90 | 0.475140E+09 | 0.139683E+12 | 0.00 | 0.65 |
Minimum of Months | 0.709148E+09 | 0.00 | 0.00 | 1283864.54 | 0.00 | 0.00 | 0.276075E+10 | 0.00 | 0.27 |
Maximum of Months | 0.139946E+11 | 0.409774E+09 | 0.00 | 42580606.90 | 20760484.75 | 0.441138E+09 | 0.177925E+11 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421786E+10 | 0.00 | 0.00 | 0.26 |
February | 0.117353E+11 | 0.00 | 0.00 | 195985.07 | 0.00 | 0.124817E+10 | 0.227007E+09 | 0.00 | 0.29 |
March | 0.118883E+11 | 0.00 | 0.00 | 797421.01 | 0.00 | 0.403000E+09 | 0.128601E+10 | 0.00 | 0.30 |
April | 0.701352E+10 | 0.00 | 0.00 | 5701666.82 | 0.00 | 0.00 | 0.449057E+10 | 0.00 | 0.39 |
May | 0.498897E+10 | 8404918.18 | 0.00 | 12021895.75 | 9688350.82 | 12588094.61 | 0.680407E+10 | 0.00 | 0.50 |
June | 0.157715E+10 | 0.139010E+09 | 0.00 | 24995358.67 | 21610677.76 | 0.00 | 0.931304E+10 | 0.00 | 0.74 |
July | 0.926456E+09 | 0.278070E+09 | 0.00 | 23121746.65 | 13814233.24 | 0.00 | 0.543450E+10 | 0.00 | 0.65 |
August | 0.110311E+10 | 0.156442E+09 | 0.00 | 26535191.01 | 18630384.18 | 0.00 | 0.806568E+10 | 0.00 | 0.73 |
September | 0.280764E+10 | 0.205865E+09 | 0.00 | 17778796.41 | 15658886.00 | 0.00 | 0.796141E+10 | 0.00 | 0.61 |
October | 0.598197E+10 | 0.00 | 0.00 | 8858373.01 | 0.00 | 5033544.58 | 0.552379E+10 | 0.00 | 0.43 |
November | 0.961141E+10 | 0.00 | 0.00 | 1355785.36 | 0.00 | 0.421093E+09 | 0.147590E+10 | 0.00 | 0.31 |
December | 0.124297E+11 | 0.00 | 0.00 | 1251.93 | 0.00 | 0.203621E+10 | 25253978.20 | 0.00 | 0.27 |
Annual Sum or Average | 0.826099E+11 | 0.787793E+09 | 0.00 | 0.121363E+09 | 79402531.99 | 0.834396E+10 | 0.506072E+11 | 0.00 | 0.46 |
Minimum of Months | 0.926456E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.125465E+11 | 0.278070E+09 | 0.00 | 26535191.01 | 21610677.76 | 0.421786E+10 | 0.931304E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.639110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.860723E+10 | 0.00 | 0.00 | 0.25 |
February | 0.845626E+10 | 0.00 | 0.00 | 50816.15 | 0.00 | 0.359686E+10 | 0.113745E+09 | 0.00 | 0.28 |
March | 0.106938E+11 | 0.00 | 0.00 | 235671.88 | 0.00 | 0.162413E+10 | 0.506927E+09 | 0.00 | 0.30 |
April | 0.820288E+10 | 0.00 | 0.00 | 3321010.70 | 0.00 | 0.171962E+09 | 0.269017E+10 | 0.00 | 0.38 |
May | 0.642432E+10 | 3516704.89 | 0.00 | 8855176.60 | 2680740.36 | 0.129938E+09 | 0.510910E+10 | 0.00 | 0.50 |
June | 0.212864E+10 | 98669144.43 | 0.00 | 22712231.54 | 7196137.53 | 0.00 | 0.822586E+10 | 0.00 | 0.75 |
July | 0.133430E+10 | 0.205357E+09 | 0.00 | 21310188.20 | 14809106.23 | 0.00 | 0.452258E+10 | 0.00 | 0.66 |
August | 0.166236E+10 | 0.103701E+09 | 0.00 | 23592900.51 | 14811311.17 | 0.00 | 0.650922E+10 | 0.00 | 0.70 |
September | 0.416002E+10 | 0.201139E+09 | 0.00 | 11913359.54 | 11216785.82 | 1920669.36 | 0.530100E+10 | 0.00 | 0.58 |
October | 0.772498E+10 | 0.00 | 0.00 | 3227306.89 | 0.00 | 0.141970E+09 | 0.247692E+10 | 0.00 | 0.41 |
November | 0.854868E+10 | 0.00 | 0.00 | 153098.39 | 0.00 | 0.157884E+10 | 0.405434E+09 | 0.00 | 0.30 |
December | 0.776592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527236E+10 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.734933E+11 | 0.612383E+09 | 0.00 | 95371760.37 | 50714081.12 | 0.211252E+11 | 0.358609E+11 | 0.00 | 0.45 |
Minimum of Months | 0.133430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.106938E+11 | 0.205357E+09 | 0.00 | 23592900.51 | 14811311.17 | 0.860723E+10 | 0.822586E+10 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 59968924.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467991E+10 | 0.00 | 0.00 | 0.34 |
February | 0.437095E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265414E+10 | 0.00 | 0.00 | 0.32 |
March | 0.119825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167950E+10 | 0.00 | 0.00 | 0.31 |
April | 0.150720E+10 | 0.00 | 0.00 | 409412.73 | 0.00 | 0.518556E+09 | 0.297841E+09 | 0.00 | 0.38 |
May | 0.131660E+10 | 1784019.73 | 0.00 | 2070994.46 | 565491.68 | 0.278139E+09 | 0.962695E+09 | 0.00 | 0.55 |
June | 0.583588E+09 | 33897077.52 | 0.00 | 6033387.68 | 1517997.03 | 3198315.61 | 0.184869E+10 | 0.00 | 0.92 |
July | 0.315135E+09 | 72684789.32 | 0.00 | 5824884.28 | 3123922.97 | 0.00 | 0.107772E+10 | 0.00 | 0.82 |
August | 0.540231E+09 | 39523962.64 | 0.00 | 5461368.71 | 3124388.09 | 935667.79 | 0.126211E+10 | 0.00 | 0.80 |
September | 0.110545E+10 | 59499745.20 | 0.00 | 2003259.28 | 2580969.33 | 99022520.47 | 0.724659E+09 | 0.00 | 0.59 |
October | 0.148926E+10 | 0.00 | 0.00 | 271848.96 | 0.00 | 0.511367E+09 | 0.174270E+09 | 0.00 | 0.40 |
November | 0.788779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157794E+10 | 0.00 | 0.00 | 0.32 |
December | 0.216549E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328394E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.955811E+10 | 0.207390E+09 | 0.00 | 22075156.10 | 10912769.10 | 0.152867E+11 | 0.634798E+10 | 0.00 | 0.51 |
Minimum of Months | 59968924.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.150720E+10 | 72684789.32 | 0.00 | 6033387.68 | 3124388.09 | 0.467991E+10 | 0.184869E+10 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.235807E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347307E+10 | 0.00 | 0.00 | 0.44 |
February | 0.778390E+09 | 0.00 | 0.00 | 19209.14 | 0.00 | 0.200753E+10 | 24729189.24 | 0.00 | 0.48 |
March | 0.152771E+10 | 0.00 | 0.00 | 342637.92 | 0.00 | 0.121942E+10 | 0.194212E+09 | 0.00 | 0.51 |
April | 0.134276E+10 | 0.00 | 0.00 | 1948723.21 | 0.00 | 0.385630E+09 | 0.108911E+10 | 0.00 | 0.74 |
May | 0.112414E+10 | 1538652.45 | 0.00 | 3601338.93 | 417274.67 | 0.207998E+09 | 0.179562E+10 | 0.00 | 1.05 |
June | 0.502958E+09 | 27212523.22 | 0.00 | 8300043.84 | 1621570.11 | 5972597.85 | 0.255365E+10 | 0.00 | 1.75 |
July | 0.257852E+09 | 60376072.04 | 0.00 | 9166302.02 | 2835453.15 | 0.00 | 0.177782E+10 | 0.00 | 1.72 |
August | 0.467720E+09 | 40140121.80 | 0.00 | 7414810.01 | 3149018.04 | 847760.06 | 0.204688E+10 | 0.00 | 1.65 |
September | 0.994653E+09 | 49470651.72 | 0.00 | 3120100.29 | 2448365.97 | 78411421.81 | 0.126223E+10 | 0.00 | 1.10 |
October | 0.156768E+10 | 0.00 | 0.00 | 791199.80 | 0.00 | 0.359732E+09 | 0.423020E+09 | 0.00 | 0.70 |
November | 0.108821E+10 | 0.00 | 0.00 | 7810.24 | 0.00 | 0.129462E+10 | 8159827.41 | 0.00 | 0.52 |
December | 0.414342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264586E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.103022E+11 | 0.178738E+09 | 0.00 | 34712175.40 | 10471681.95 | 0.116791E+11 | 0.111754E+11 | 0.00 | 0.93 |
Minimum of Months | 0.235807E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.156768E+10 | 60376072.04 | 0.00 | 9166302.02 | 3149018.04 | 0.347307E+10 | 0.255365E+10 | 0.00 | 1.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.884700E+09 | 0.00 | 0.00 | 557265.67 | 0.00 | 0.390488E+10 | 0.407016E+09 | 0.00 | 0.39 |
February | 0.121083E+10 | 0.00 | 0.00 | 2320498.52 | 0.00 | 0.205390E+10 | 0.120024E+10 | 0.00 | 0.53 |
March | 0.159179E+10 | 0.00 | 0.00 | 4110067.61 | 0.00 | 0.149516E+10 | 0.209030E+10 | 0.00 | 0.60 |
April | 0.153030E+10 | 0.00 | 0.00 | 4229249.64 | 0.00 | 0.596348E+09 | 0.235260E+10 | 0.00 | 0.79 |
May | 0.153685E+10 | 3185706.87 | 0.00 | 5330195.75 | 567721.69 | 0.366505E+09 | 0.254298E+10 | 0.00 | 0.98 |
June | 0.970737E+09 | 46835244.58 | 0.00 | 8327061.10 | 2036486.30 | 15543551.16 | 0.252592E+10 | 0.00 | 1.30 |
July | 0.539150E+09 | 0.103991E+09 | 0.00 | 8511886.83 | 2552174.79 | 0.00 | 0.154036E+10 | 0.00 | 1.19 |
August | 0.779277E+09 | 77272906.50 | 0.00 | 10596311.32 | 3298725.66 | 5515661.58 | 0.239907E+10 | 0.00 | 1.46 |
September | 0.117347E+10 | 0.141304E+09 | 0.00 | 7695544.15 | 1070710.40 | 0.104332E+09 | 0.285809E+10 | 0.00 | 1.34 |
October | 0.148280E+10 | 0.00 | 0.00 | 6528531.84 | 0.00 | 0.383734E+09 | 0.296365E+10 | 0.00 | 1.01 |
November | 0.130476E+10 | 0.00 | 0.00 | 3229088.32 | 0.00 | 0.128712E+10 | 0.150068E+10 | 0.00 | 0.57 |
December | 0.110661E+10 | 0.00 | 0.00 | 1069961.40 | 0.00 | 0.274309E+10 | 0.543348E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.141113E+11 | 0.372589E+09 | 0.00 | 62505662.15 | 9525818.83 | 0.129561E+11 | 0.229243E+11 | 0.00 | 0.88 |
Minimum of Months | 0.539150E+09 | 0.00 | 0.00 | 557265.67 | 0.00 | 0.00 | 0.407016E+09 | 0.00 | 0.39 |
Maximum of Months | 0.159179E+10 | 0.141304E+09 | 0.00 | 10596311.32 | 3298725.66 | 0.390488E+10 | 0.296365E+10 | 0.00 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.333627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379618E+10 | 0.00 | 0.00 | 0.50 |
February | 0.776459E+09 | 0.00 | 0.00 | 190588.11 | 0.00 | 0.231626E+10 | 0.123136E+09 | 0.00 | 0.55 |
March | 0.143649E+10 | 0.00 | 0.00 | 684486.91 | 0.00 | 0.164020E+10 | 0.382206E+09 | 0.00 | 0.61 |
April | 0.174930E+10 | 0.00 | 0.00 | 1786556.41 | 0.00 | 0.522803E+09 | 0.941339E+09 | 0.00 | 0.87 |
May | 0.144749E+10 | 1557547.56 | 0.00 | 3915847.37 | 693345.29 | 0.299820E+09 | 0.172780E+10 | 0.00 | 1.19 |
June | 0.907556E+09 | 38318903.46 | 0.00 | 6589139.49 | 262031.78 | 13476979.80 | 0.178941E+10 | 0.00 | 1.59 |
July | 0.498642E+09 | 81833051.10 | 0.00 | 6252564.59 | 1813775.83 | 0.00 | 0.991776E+09 | 0.00 | 1.35 |
August | 0.778203E+09 | 43216119.58 | 0.00 | 5739074.65 | 1868991.44 | 5693133.25 | 0.122766E+10 | 0.00 | 1.41 |
September | 0.135956E+10 | 82034658.76 | 0.00 | 2596726.02 | 1304223.89 | 0.112776E+09 | 0.995152E+09 | 0.00 | 1.17 |
October | 0.169835E+10 | 0.00 | 0.00 | 1099743.83 | 0.00 | 0.518975E+09 | 0.571584E+09 | 0.00 | 0.84 |
November | 0.113057E+10 | 0.00 | 0.00 | 130575.02 | 0.00 | 0.148519E+10 | 0.127999E+09 | 0.00 | 0.59 |
December | 0.530028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291530E+10 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.126463E+11 | 0.246960E+09 | 0.00 | 28985302.41 | 5942368.23 | 0.136267E+11 | 0.887806E+10 | 0.00 | 0.93 |
Minimum of Months | 0.333627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.174930E+10 | 82034658.76 | 0.00 | 6589139.49 | 1868991.44 | 0.379618E+10 | 0.178941E+10 | 0.00 | 1.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 71215432.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455692E+10 | 0.00 | 0.00 | 0.32 |
February | 0.457780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271679E+10 | 0.00 | 0.00 | 0.31 |
March | 0.114269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185172E+10 | 0.00 | 0.00 | 0.31 |
April | 0.174767E+10 | 0.00 | 0.00 | 3675.43 | 0.00 | 0.551469E+09 | 6215375.39 | 0.00 | 0.36 |
May | 0.175874E+10 | 1567501.07 | 0.00 | 652262.68 | 1991478.99 | 0.191312E+09 | 0.302496E+09 | 0.00 | 0.45 |
June | 0.733714E+09 | 35003571.10 | 0.00 | 3516388.43 | 4376742.96 | 0.00 | 0.120778E+10 | 0.00 | 0.67 |
July | 0.377268E+09 | 91051528.60 | 0.00 | 4015592.95 | 3698005.32 | 0.00 | 0.852610E+09 | 0.00 | 0.65 |
August | 0.636119E+09 | 48813926.25 | 0.00 | 3780497.26 | 3984263.15 | 0.00 | 0.105979E+10 | 0.00 | 0.67 |
September | 0.131701E+10 | 48872999.70 | 0.00 | 1907989.40 | 3356409.62 | 4406740.38 | 0.743701E+09 | 0.00 | 0.57 |
October | 0.204818E+10 | 0.00 | 0.00 | 301519.23 | 0.00 | 94372330.78 | 0.223760E+09 | 0.00 | 0.41 |
November | 0.148474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108385E+10 | 0.00 | 0.00 | 0.32 |
December | 0.400721E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304307E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.121758E+11 | 0.225310E+09 | 0.00 | 14177925.40 | 17406900.05 | 0.140939E+11 | 0.439635E+10 | 0.00 | 0.44 |
Minimum of Months | 71215432.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.204818E+10 | 91051528.60 | 0.00 | 4015592.95 | 4376742.96 | 0.455692E+10 | 0.120778E+10 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.226256E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334886E+10 | 0.00 | 0.00 | 0.40 |
February | 0.752217E+09 | 0.00 | 0.00 | 16544.06 | 0.00 | 0.181010E+10 | 28476603.68 | 0.00 | 0.41 |
March | 0.144104E+10 | 0.00 | 0.00 | 141955.14 | 0.00 | 0.105927E+10 | 91773452.24 | 0.00 | 0.43 |
April | 0.134861E+10 | 0.00 | 0.00 | 1051717.48 | 0.00 | 0.235228E+09 | 0.612170E+09 | 0.00 | 0.55 |
May | 0.110794E+10 | 2693814.21 | 0.00 | 2371677.56 | 535629.06 | 91262569.55 | 0.112783E+10 | 0.00 | 0.76 |
June | 0.453427E+09 | 38990930.16 | 0.00 | 6049457.96 | 3814439.35 | 0.00 | 0.200828E+10 | 0.00 | 1.36 |
July | 0.228254E+09 | 91048187.97 | 0.00 | 7329939.21 | 2516096.73 | 0.00 | 0.155590E+10 | 0.00 | 1.42 |
August | 0.392823E+09 | 55094121.93 | 0.00 | 6500918.30 | 3448161.83 | 0.00 | 0.193343E+10 | 0.00 | 1.45 |
September | 0.807321E+09 | 43134093.53 | 0.00 | 3495273.65 | 2681742.33 | 514823.21 | 0.145617E+10 | 0.00 | 1.01 |
October | 0.141842E+10 | 0.00 | 0.00 | 1414277.75 | 0.00 | 33129425.32 | 0.777448E+09 | 0.00 | 0.63 |
November | 0.142697E+10 | 0.00 | 0.00 | 54404.75 | 0.00 | 0.757965E+09 | 57288112.07 | 0.00 | 0.44 |
December | 0.677773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215243E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.102810E+11 | 0.230961E+09 | 0.00 | 28426165.84 | 12996069.29 | 0.948876E+10 | 0.964877E+10 | 0.00 | 0.77 |
Minimum of Months | 0.226256E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.144104E+10 | 91048187.97 | 0.00 | 7329939.21 | 3814439.35 | 0.334886E+10 | 0.200828E+10 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.412645E+09 | 0.00 | 0.00 | 8027.48 | 0.00 | 0.689414E+10 | 7559089.13 | 0.00 | 0.50 |
February | 0.551787E+09 | 0.00 | 0.00 | 583898.03 | 0.00 | 0.417710E+10 | 0.342549E+09 | 0.00 | 0.50 |
March | 0.959744E+09 | 0.00 | 0.00 | 451461.49 | 0.00 | 0.311971E+10 | 0.333409E+09 | 0.00 | 0.45 |
April | 0.122226E+10 | 0.00 | 0.00 | 638999.44 | 0.00 | 0.163832E+10 | 0.386610E+09 | 0.00 | 0.51 |
May | 0.139814E+10 | 3646835.08 | 0.00 | 1403136.61 | 1672718.91 | 0.126600E+10 | 0.465579E+09 | 0.00 | 0.62 |
June | 0.116164E+10 | 65033988.54 | 0.00 | 3407720.52 | 4924196.50 | 0.316065E+09 | 0.800080E+09 | 0.00 | 0.82 |
July | 0.560075E+09 | 0.169713E+09 | 0.00 | 5447848.53 | 4028399.97 | 69756244.46 | 0.857794E+09 | 0.00 | 0.88 |
August | 0.738977E+09 | 0.114041E+09 | 0.00 | 7120575.50 | 3463921.08 | 0.212230E+09 | 0.147385E+10 | 0.00 | 1.13 |
September | 0.109114E+10 | 0.125793E+09 | 0.00 | 5517298.69 | 1403253.03 | 0.431300E+09 | 0.184679E+10 | 0.00 | 1.07 |
October | 0.140462E+10 | 0.00 | 0.00 | 3934544.80 | 0.00 | 0.796090E+09 | 0.185592E+10 | 0.00 | 0.81 |
November | 0.131796E+10 | 0.00 | 0.00 | 816079.22 | 0.00 | 0.207503E+10 | 0.555247E+09 | 0.00 | 0.49 |
December | 0.690432E+09 | 0.00 | 0.00 | 47653.98 | 0.00 | 0.474721E+10 | 42844582.16 | 0.00 | 0.44 |
Annual Sum or Average | 0.115094E+11 | 0.478228E+09 | 0.00 | 29377244.28 | 15492489.49 | 0.257430E+11 | 0.896823E+10 | 0.00 | 0.69 |
Minimum of Months | 0.412645E+09 | 0.00 | 0.00 | 8027.48 | 0.00 | 69756244.46 | 7559089.13 | 0.00 | 0.44 |
Maximum of Months | 0.140462E+10 | 0.169713E+09 | 0.00 | 7120575.50 | 4924196.50 | 0.689414E+10 | 0.185592E+10 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.246521E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360678E+10 | 0.00 | 0.00 | 0.44 |
February | 0.763341E+09 | 0.00 | 0.00 | 91700.81 | 0.00 | 0.201892E+10 | 60329976.77 | 0.00 | 0.45 |
March | 0.146539E+10 | 0.00 | 0.00 | 260579.60 | 0.00 | 0.127979E+10 | 0.138859E+09 | 0.00 | 0.47 |
April | 0.165823E+10 | 0.00 | 0.00 | 704508.23 | 0.00 | 0.334240E+09 | 0.375461E+09 | 0.00 | 0.61 |
May | 0.141217E+10 | 1775570.80 | 0.00 | 2219571.27 | 1934606.82 | 0.118356E+09 | 0.909579E+09 | 0.00 | 0.81 |
June | 0.704280E+09 | 47616086.62 | 0.00 | 4178823.87 | 2541801.43 | 242357.97 | 0.135265E+10 | 0.00 | 1.15 |
July | 0.355785E+09 | 0.114328E+09 | 0.00 | 4824101.49 | 1762372.37 | 0.00 | 0.902573E+09 | 0.00 | 1.08 |
August | 0.586343E+09 | 61680207.14 | 0.00 | 4571400.72 | 2184529.90 | 0.00 | 0.114147E+10 | 0.00 | 1.15 |
September | 0.110299E+10 | 67283118.64 | 0.00 | 2688804.75 | 1115746.64 | 729710.36 | 0.105737E+10 | 0.00 | 0.99 |
October | 0.177838E+10 | 0.00 | 0.00 | 1179946.77 | 0.00 | 59612672.65 | 0.605758E+09 | 0.00 | 0.69 |
November | 0.146466E+10 | 0.00 | 0.00 | 174521.20 | 0.00 | 0.862302E+09 | 0.155721E+09 | 0.00 | 0.49 |
December | 0.660677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243028E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.121988E+11 | 0.292683E+09 | 0.00 | 20893958.72 | 9539057.17 | 0.107112E+11 | 0.669977E+10 | 0.00 | 0.73 |
Minimum of Months | 0.246521E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.177838E+10 | 0.114328E+09 | 0.00 | 4824101.49 | 2541801.43 | 0.360678E+10 | 0.135265E+10 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116714E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440532E+10 | 0.00 | 0.00 | 0.32 |
February | 0.692466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231060E+10 | 0.00 | 0.00 | 0.30 |
March | 0.174782E+10 | 0.00 | 0.00 | 45.25 | 0.00 | 0.117153E+10 | 2236641.23 | 0.00 | 0.31 |
April | 0.185448E+10 | 0.00 | 0.00 | 494353.45 | 0.00 | 0.190843E+09 | 0.328915E+09 | 0.00 | 0.38 |
May | 0.135762E+10 | 3411850.38 | 0.00 | 2362456.08 | 2262346.89 | 97854486.32 | 0.105482E+10 | 0.00 | 0.54 |
June | 0.478670E+09 | 48518205.13 | 0.00 | 6130577.60 | 4551831.60 | 0.00 | 0.200970E+10 | 0.00 | 0.90 |
July | 0.269441E+09 | 0.103734E+09 | 0.00 | 5804912.95 | 2909675.68 | 0.00 | 0.118828E+10 | 0.00 | 0.80 |
August | 0.461389E+09 | 60540595.61 | 0.00 | 5384902.83 | 3924095.88 | 0.00 | 0.142842E+10 | 0.00 | 0.80 |
September | 0.112954E+10 | 62470927.81 | 0.00 | 2507051.34 | 3298212.71 | 12134371.75 | 0.939125E+09 | 0.00 | 0.60 |
October | 0.182494E+10 | 0.00 | 0.00 | 516348.56 | 0.00 | 0.164597E+09 | 0.302377E+09 | 0.00 | 0.40 |
November | 0.134877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112833E+10 | 0.00 | 0.00 | 0.32 |
December | 0.430219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296714E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.117121E+11 | 0.278675E+09 | 0.00 | 23200648.06 | 16946162.76 | 0.124484E+11 | 0.725387E+10 | 0.00 | 0.50 |
Minimum of Months | 0.116714E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.185448E+10 | 0.103734E+09 | 0.00 | 6130577.60 | 4551831.60 | 0.440532E+10 | 0.200970E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.357819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365216E+10 | 0.00 | 0.00 | 0.46 |
February | 0.999562E+09 | 0.00 | 0.00 | 94830.46 | 0.00 | 0.200715E+10 | 55349549.61 | 0.00 | 0.50 |
March | 0.188749E+10 | 0.00 | 0.00 | 540631.00 | 0.00 | 0.101317E+10 | 0.295519E+09 | 0.00 | 0.54 |
April | 0.166227E+10 | 0.00 | 0.00 | 2245486.68 | 0.00 | 0.141773E+09 | 0.120598E+10 | 0.00 | 0.77 |
May | 0.122707E+10 | 4646820.70 | 0.00 | 3873841.84 | 748751.69 | 0.109836E+09 | 0.183149E+10 | 0.00 | 1.04 |
June | 0.476012E+09 | 40124162.19 | 0.00 | 8157080.55 | 4862742.38 | 0.00 | 0.263175E+10 | 0.00 | 1.69 |
July | 0.246982E+09 | 85342039.26 | 0.00 | 8949374.14 | 2726973.96 | 0.00 | 0.186088E+10 | 0.00 | 1.66 |
August | 0.484591E+09 | 57558514.77 | 0.00 | 7133705.56 | 4231634.34 | 0.00 | 0.215034E+10 | 0.00 | 1.63 |
September | 0.106161E+10 | 50658643.56 | 0.00 | 3550420.90 | 3415480.94 | 7313211.90 | 0.149030E+10 | 0.00 | 1.12 |
October | 0.179496E+10 | 0.00 | 0.00 | 1210823.56 | 0.00 | 0.117707E+09 | 0.674867E+09 | 0.00 | 0.73 |
November | 0.156577E+10 | 0.00 | 0.00 | 60840.35 | 0.00 | 0.103894E+10 | 40689371.65 | 0.00 | 0.54 |
December | 0.724390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263819E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.124885E+11 | 0.238330E+09 | 0.00 | 35817035.05 | 15985583.30 | 0.107262E+11 | 0.122372E+11 | 0.00 | 0.93 |
Minimum of Months | 0.246982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.188749E+10 | 85342039.26 | 0.00 | 8949374.14 | 4862742.38 | 0.365216E+10 | 0.263175E+10 | 0.00 | 1.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112092E+10 | 0.00 | 0.00 | 920878.54 | 0.00 | 0.360872E+10 | 0.600805E+09 | 0.00 | 0.39 |
February | 0.139492E+10 | 0.00 | 0.00 | 3047576.10 | 0.00 | 0.178840E+10 | 0.145016E+10 | 0.00 | 0.55 |
March | 0.202013E+10 | 0.00 | 0.00 | 4758205.27 | 0.00 | 0.105532E+10 | 0.218312E+10 | 0.00 | 0.60 |
April | 0.184828E+10 | 0.00 | 0.00 | 4695605.69 | 0.00 | 0.214250E+09 | 0.231687E+10 | 0.00 | 0.78 |
May | 0.155908E+10 | 11231702.05 | 0.00 | 5606936.95 | 939455.51 | 0.153953E+09 | 0.244463E+10 | 0.00 | 0.93 |
June | 0.830135E+09 | 72780447.71 | 0.00 | 7998617.96 | 2873614.81 | 319107.19 | 0.250230E+10 | 0.00 | 1.21 |
July | 0.475003E+09 | 0.152787E+09 | 0.00 | 7928593.75 | 3609550.05 | 0.00 | 0.148743E+10 | 0.00 | 1.11 |
August | 0.666356E+09 | 0.121199E+09 | 0.00 | 9759810.86 | 4025040.59 | 0.00 | 0.236385E+10 | 0.00 | 1.39 |
September | 0.112790E+10 | 0.151965E+09 | 0.00 | 8215082.51 | 1984656.70 | 17395437.45 | 0.302105E+10 | 0.00 | 1.33 |
October | 0.155412E+10 | 0.00 | 0.00 | 8099665.02 | 0.00 | 96016001.78 | 0.346173E+10 | 0.00 | 1.04 |
November | 0.154691E+10 | 0.00 | 0.00 | 4321913.22 | 0.00 | 0.948372E+09 | 0.198229E+10 | 0.00 | 0.60 |
December | 0.140620E+10 | 0.00 | 0.00 | 1564300.52 | 0.00 | 0.239987E+10 | 0.798207E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.155500E+11 | 0.509963E+09 | 0.00 | 66917186.38 | 13432317.66 | 0.102826E+11 | 0.246124E+11 | 0.00 | 0.86 |
Minimum of Months | 0.475003E+09 | 0.00 | 0.00 | 920878.54 | 0.00 | 0.00 | 0.600805E+09 | 0.00 | 0.39 |
Maximum of Months | 0.202013E+10 | 0.152787E+09 | 0.00 | 9759810.86 | 4025040.59 | 0.360872E+10 | 0.346173E+10 | 0.00 | 1.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.414564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384241E+10 | 0.00 | 0.00 | 0.49 |
February | 0.102039E+10 | 0.00 | 0.00 | 238440.64 | 0.00 | 0.214638E+10 | 0.135679E+09 | 0.00 | 0.54 |
March | 0.190709E+10 | 0.00 | 0.00 | 783420.62 | 0.00 | 0.118984E+10 | 0.398604E+09 | 0.00 | 0.59 |
April | 0.198383E+10 | 0.00 | 0.00 | 1875548.29 | 0.00 | 0.206571E+09 | 0.924856E+09 | 0.00 | 0.84 |
May | 0.146076E+10 | 2873997.30 | 0.00 | 3998722.55 | 2880050.90 | 0.124138E+09 | 0.165552E+10 | 0.00 | 1.10 |
June | 0.751321E+09 | 54838280.14 | 0.00 | 5943081.95 | 3844299.55 | 545818.34 | 0.180184E+10 | 0.00 | 1.45 |
July | 0.436455E+09 | 0.122042E+09 | 0.00 | 5934003.13 | 1217939.21 | 0.00 | 0.992895E+09 | 0.00 | 1.25 |
August | 0.681812E+09 | 68668942.46 | 0.00 | 5242807.62 | 2310887.53 | 254130.30 | 0.125727E+10 | 0.00 | 1.32 |
September | 0.132394E+10 | 87403638.10 | 0.00 | 2850122.03 | 820648.41 | 15933415.19 | 0.111666E+10 | 0.00 | 1.12 |
October | 0.199907E+10 | 0.00 | 0.00 | 1352953.61 | 0.00 | 0.167822E+09 | 0.668306E+09 | 0.00 | 0.81 |
November | 0.151131E+10 | 0.00 | 0.00 | 257564.52 | 0.00 | 0.113551E+10 | 0.209347E+09 | 0.00 | 0.58 |
December | 0.782734E+09 | 0.00 | 0.00 | 2534.44 | 0.00 | 0.280483E+10 | 6658685.36 | 0.00 | 0.49 |
Annual Sum or Average | 0.142733E+11 | 0.335827E+09 | 0.00 | 28479199.39 | 11073825.60 | 0.116342E+11 | 0.916763E+10 | 0.00 | 0.89 |
Minimum of Months | 0.414564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.199907E+10 | 0.122042E+09 | 0.00 | 5943081.95 | 3844299.55 | 0.384241E+10 | 0.180184E+10 | 0.00 | 1.45 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.157822E+12 | 0.325453E+11 | 0.00 | 0.144824E+12 | 0.157858E+11 |
February | 0.207216E+12 | 0.249948E+11 | 0.00 | 0.140833E+12 | 0.940751E+10 |
March | 0.333394E+12 | 0.239484E+11 | 0.00 | 0.168487E+12 | 0.558764E+10 |
April | 0.350561E+12 | 0.165587E+11 | 0.00 | 0.196034E+12 | 0.835478E+10 |
May | 0.458246E+12 | 0.161559E+11 | 0.00 | 0.208408E+12 | 0.288334E+11 |
June | 0.493582E+12 | 0.792490E+10 | 0.00 | 0.193288E+12 | 0.103719E+12 |
July | 0.490005E+12 | 0.420489E+10 | 0.00 | 0.162806E+12 | 0.178983E+12 |
August | 0.411840E+12 | 0.581678E+10 | 0.00 | 0.187221E+12 | 0.149583E+12 |
September | 0.317272E+12 | 0.107370E+11 | 0.00 | 0.192103E+12 | 0.686854E+11 |
October | 0.215415E+12 | 0.161087E+11 | 0.00 | 0.213161E+12 | 0.145648E+11 |
November | 0.125138E+12 | 0.221782E+11 | 0.00 | 0.166739E+12 | 0.464252E+10 |
December | 0.104751E+12 | 0.280402E+11 | 0.00 | 0.143095E+12 | 0.105596E+11 |
Annual Sum or Average | 0.366524E+13 | 0.209214E+12 | 0.00 | 0.211700E+13 | 0.598707E+12 |