Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2023-10-16 08:35:13
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2341.47 | 469.97 | 469.97 |
Net Site Energy | 2341.47 | 469.97 | 469.97 |
Total Source Energy | 6684.55 | 1341.69 | 1341.69 |
Net Source Energy | 6684.55 | 1341.69 | 1341.69 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 681.75 | 224.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 50.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 287.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 97.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 24.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 126.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1990.59 | 350.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 681.75 | 224.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 50.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 287.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 72.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 12.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 97.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 24.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 126.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 681.75 | 224.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 50.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 287.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 72.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 12.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 97.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 24.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 126.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 72.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 166.65 | 70.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 160.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 399.54 | 70.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 72.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 166.65 | 70.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 160.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 399.54 | 70.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1990.589 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1990.589 | 100.00 |
Total On-Site and Utility Electric Sources | 1990.589 | 100.00 |
Total Electricity End Uses | 1990.589 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 0.20 | 0.04 |
Air to Air Heat Recovery for Heating | 446.64 | 99.96 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 446.84 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1093.50 |
Time Setpoint Not Met During Occupied Cooling | 47.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3467.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 7.5763 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 7.5763 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 7.5763 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.5763 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 7.5763 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.5763 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.5763 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.5763 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.5763 | 18.58 | 8.0700 | |
Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 7.5763 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 7.5763 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-08:09 | 12-JAN-07:30 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 195529.74 | 202788.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 28079.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 47562.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 901.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5775.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2722.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8277.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 286129.70 | 211066.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 195529.74 | 202788.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 28079.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 901.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 5775.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 2722.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8277.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 2159.10 | 243.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 160.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 911.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 229.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2413.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 41.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 309.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 79.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 136.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6304.19 | 380.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 433.36 | 48.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 32.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 182.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 46.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 62.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 15.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1265.35 | 76.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 433.36 | 48.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 32.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 182.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 46.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 62.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 15.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1265.35 | 76.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.92 | 0.256699 | 0.271000 | 0.791208 | 0.684531 | 0.500000 | 0.001484 |
CORE_MID VAV BOX COMPONENT | 2.17 | 0.345941 | 0.355000 | 0.769080 | 0.922510 | 0.500000 | 0.001101 |
CORE_TOP VAV BOX COMPONENT | 2.14 | 0.350263 | 0.368000 | 0.787408 | 0.934033 | 0.500000 | 0.001088 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.718130 | 0.220004 | 0.261000 | 0.187432 | 0.586678 | 0.500000 | 0.001732 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.858220 | 0.116546 | 0.200000 | 0.171644 | 0.310788 | 0.500000 | 0.003269 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.37 | 0.115066 | 0.200000 | 0.274611 | 0.306842 | 0.500000 | 0.003311 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.904508 | 0.110574 | 0.200000 | 0.180902 | 0.300000 | 0.500000 | 0.003446 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.558738 | 0.282765 | 0.302000 | 0.168739 | 0.754041 | 0.500000 | 0.001347 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.703242 | 0.142230 | 0.200000 | 0.140648 | 0.379279 | 0.500000 | 0.002679 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.11 | 0.142065 | 0.200000 | 0.222421 | 0.378841 | 0.500000 | 0.002682 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.751835 | 0.133028 | 0.200000 | 0.150367 | 0.354742 | 0.500000 | 0.002864 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.612242 | 0.258054 | 0.265000 | 0.162244 | 0.688145 | 0.500000 | 0.001476 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.851769 | 0.117428 | 0.200000 | 0.170354 | 0.313142 | 0.500000 | 0.003245 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.29 | 0.122057 | 0.200000 | 0.258881 | 0.325486 | 0.500000 | 0.003121 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.852679 | 0.117295 | 0.200000 | 0.170536 | 0.312787 | 0.500000 | 0.003248 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 26014.55 |
CORE_MID VAV BOX REHEAT COIL | 28825.79 |
CORE_TOP VAV BOX REHEAT COIL | 51931.43 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 23611.78 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 15433.18 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 23494.71 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 15366.98 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 18371.03 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12123.34 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 18296.04 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 12074.02 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 17816.30 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 11718.39 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 17714.31 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 11665.70 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.02 | 1.47 | 6.05 | 2.34 | 5.24 | 5.24 | 0.300000 | 0.446748 | 5.24 |
PACU_VAV_MID | 2.89 | 1.53 | 5.78 | 2.67 | 4.72 | 4.72 | 0.300000 | 0.565948 | 4.72 |
PACU_VAV_TOP | 3.00 | 1.60 | 5.99 | 3.95 | 5.17 | 5.17 | 0.300000 | 0.764273 | 5.17 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.24 |
PACU_VAV_MID_OA_CONTROLLER | 4.72 |
PACU_VAV_TOP_OA_CONTROLLER | 5.17 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT OA HEAT RECOVERY | 1.20 |
PACU_VAV_MID OA HEAT RECOVERY | 1.20 |
PACU_VAV_TOP OA HEAT RECOVERY | 1.20 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.24 | 86691.50 | 0.800655 | 1.75 | 28894.28 | 0.800655 |
PACU_VAV_MID COOLING COIL | 4.72 | 78052.92 | 0.800655 | 1.57 | 26015.04 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 5.17 | 85530.16 | 0.800655 | 1.72 | 28507.20 | 0.800655 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 75334.25 |
PACU_VAV_MID HEATING COIL | 76651.63 |
PACU_VAV_TOP HEATING COIL | 76691.97 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.24 |
PACU_VAV_MID FAN | 4.72 |
PACU_VAV_TOP FAN | 5.17 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 32.411 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 7.576 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.646 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 7451.603 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7451.603 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 994.486 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.486 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1570.863 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1570.863 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 994.421 | 7.576 | 140.759 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 994.421 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7944 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7793 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.119 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1711 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1804 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1711 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1804 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.025 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.049 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6593 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.768 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.466 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.768 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.465 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
39 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
40 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
41 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
42 | 7 | -0.29839090E-12 | 0.94613664E-15 | -0.93984276E-13 | 0.14929621E-15 |
43 | 6 | 0.28459516E-07 | 0.22300724E-09 | 0.65212509E-08 | -0.13406672E-12 |
44 | 5 | -0.18903196E-03 | 0.19107794E-05 | -0.97244514E-04 | 0.64472671E-08 |
45 | 4 | 0.29088896 | 0.93090113E-03 | 0.99231010E-01 | -0.33393447E-04 |
46 | 3 | -7.2414209 | 0.28863778E-01 | -2.3315219 | 0.28886944E-01 |
47 | 2 | 40.789004 | 0.10268188 | 15.234791 | -0.33242551 |
48 | 1 | -80.482851 | 0.46359056E-01 | -29.114516 | 1.0772781 |
49 | 0 | 46.824339 | 0.93304599E-03 | 16.291883 | |
50 | 7 | -0.30147866E-12 | 0.32879259E-14 | -0.94788354E-13 | 0.15721988E-15 |
51 | 6 | 0.28638673E-07 | 0.21918405E-09 | 0.65607935E-08 | -0.13498453E-12 |
52 | 5 | -0.18994198E-03 | 0.18758515E-05 | -0.97700529E-04 | 0.64858157E-08 |
53 | 4 | 0.29195434 | 0.91295314E-03 | 0.99614140E-01 | -0.33543711E-04 |
54 | 3 | -7.2625212 | 0.28281717E-01 | -2.3377829 | 0.28990346E-01 |
55 | 2 | 40.858594 | 0.10053100 | 15.260475 | -0.33320057 |
56 | 1 | -80.536180 | 0.45356415E-01 | -29.137544 | 1.0784145 |
57 | 0 | 46.824339 | 0.91224283E-03 | 16.291331 | |
58 | 7 | -0.27660997E-12 | 0.14023004E-14 | -0.80712451E-13 | 0.13354543E-15 |
59 | 6 | 0.24561732E-07 | 0.29965487E-09 | 0.56608975E-08 | -0.11328042E-12 |
60 | 5 | -0.16900662E-03 | 0.26385003E-05 | -0.87174216E-04 | 0.56068092E-08 |
61 | 4 | 0.26710865 | 0.13167816E-02 | 0.90695657E-01 | -0.30074316E-04 |
62 | 3 | -6.7696400 | 0.41706905E-01 | -2.1915874 | 0.26577286E-01 |
63 | 2 | 39.232110 | 0.15116668 | 14.658763 | -0.31509082 |
64 | 1 | -79.288784 | 0.69361307E-01 | -28.597496 | 1.0518338 |
65 | 0 | 46.824347 | 0.14183552E-02 | 16.304685 | |
66 | 7 | -0.24742660E-08 | -0.10943249E-14 | 0.58004390E-14 | -0.93636906E-16 |
67 | 6 | 0.48508293E-05 | 0.32725533E-08 | 0.31920885E-02 | -0.26777914E-04 |
68 | 5 | -0.34494329E-03 | 0.19369032E-05 | -0.22385068 | 0.19572633E-02 |
69 | 4 | 0.79096117E-02 | 0.88130937E-04 | 4.8316460 | -0.45285171E-01 |
70 | 3 | -0.69381330E-01 | 0.70057705E-03 | -38.033282 | 0.39878490 |
71 | 2 | 0.24625431 | 0.11650871E-02 | 116.50704 | -1.4182482 |
72 | 1 | -0.35536509 | 0.35482444E-03 | -143.92090 | 2.0492634 |
73 | 0 | 0.17324174 | 0.85915519E-05 | 60.838472 | |
74 | 7 | -0.23440898E-08 | -0.93321999E-15 | 0.55807564E-14 | -0.85509042E-16 |
75 | 6 | 0.50995884E-05 | 0.34521263E-08 | 0.31913593E-02 | -0.26771796E-04 |
76 | 5 | -0.36354987E-03 | 0.20433482E-05 | -0.22380923 | 0.19568975E-02 |
77 | 4 | 0.83423098E-02 | 0.92983792E-04 | 4.8309558 | -0.45278535E-01 |
78 | 3 | -0.73195838E-01 | 0.73920573E-03 | -38.029382 | 0.39874180 |
79 | 2 | 0.25981955 | 0.12294351E-02 | 116.49945 | -1.4181467 |
80 | 1 | -0.37495780 | 0.37443474E-03 | -143.91643 | 2.0491899 |
81 | 0 | 0.18279742 | 0.90747285E-05 | 60.838472 | |
82 | 7 | -0.24742660E-08 | -0.10943249E-14 | 0.58004393E-14 | -0.93636910E-16 |
83 | 6 | 0.48508293E-05 | 0.32725533E-08 | 0.31920885E-02 | -0.26777914E-04 |
84 | 5 | -0.34494329E-03 | 0.19369032E-05 | -0.22385068 | 0.19572633E-02 |
85 | 4 | 0.79096117E-02 | 0.88130937E-04 | 4.8316460 | -0.45285171E-01 |
86 | 3 | -0.69381330E-01 | 0.70057705E-03 | -38.033282 | 0.39878490 |
87 | 2 | 0.24625431 | 0.11650871E-02 | 116.50704 | -1.4182482 |
88 | 1 | -0.35536509 | 0.35482444E-03 | -143.92090 | 2.0492634 |
89 | 0 | 0.17324174 | 0.85915519E-05 | 60.838472 | |
90 | 7 | -0.23439288E-08 | -0.93347870E-15 | 0.55887675E-14 | -0.85663837E-16 |
91 | 6 | 0.50999137E-05 | 0.34523603E-08 | 0.31913583E-02 | -0.26771788E-04 |
92 | 5 | -0.36357417E-03 | 0.20434871E-05 | -0.22380918 | 0.19568970E-02 |
93 | 4 | 0.83428746E-02 | 0.92990125E-04 | 4.8309549 | -0.45278527E-01 |
94 | 3 | -0.73200817E-01 | 0.73925614E-03 | -38.029377 | 0.39874175 |
95 | 2 | 0.25983726 | 0.12295191E-02 | 116.49944 | -1.4181466 |
96 | 1 | -0.37498338 | 0.37446036E-03 | -143.91643 | 2.0491898 |
97 | 0 | 0.18280989 | 0.90753466E-05 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.2925_SHGC_EAST_0.45 | 35 | 1 | VerySmooth | 1.661 | 1.661 | 1.000 | 0.451 | ||
2 | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 36 | 1 | VerySmooth | 1.661 | 1.661 | 1.000 | 0.451 | ||
3 | WINDOW_U_0.2925_SHGC_WEST_0.45 | 37 | 1 | VerySmooth | 1.661 | 1.661 | 1.000 | 0.451 | ||
4 | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 38 | 1 | VerySmooth | 1.661 | 1.661 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 4.24435E-002 | 0.36619 | 0.44086 | 0.44086 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.92517E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 4.24435E-002 | 0.36619 | 0.44086 | 0.44086 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.92517E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 4.24435E-002 | 0.36619 | 0.44086 | 0.44086 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.92517E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 4.24435E-002 | 0.36619 | 0.44086 | 0.44086 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.92517E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3855E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3935E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6359E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6431E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9592E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0066E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3410E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3672E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1467 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1040 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1701 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1257 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.3036E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1978E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0374E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8858E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3862E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3981E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6368E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6488E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9633E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0245E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3408E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3669E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 0.1009 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.3290E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 0.1053 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.6078E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.0244E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1017E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8621E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7388E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.7039E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 8.7404E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.9946E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.0227E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4792E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.4888E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0663E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0753E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.6825E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.7600E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8126E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.8810E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8570E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9021E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3408E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3669E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.9469E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4510E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7630E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7398E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0889E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6874E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0374E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8858E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.6815E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.7639E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8097E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.8771E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8533E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.8883E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3410E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3672E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.2793E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5483E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5761E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0947E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5263E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3323E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8621E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7389E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.7347E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.8396E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2178E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.3431E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5646E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5929E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0665E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0755E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1593 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1233 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1845 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1481 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1013 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.3014E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.6644E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.6249E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 9.6398E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 6.0750E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 0.1006 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 6.3417E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.7764E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.9667E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.7222E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6635E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.6111E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 4.3437E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.3589E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.5151E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.6591E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3545E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.6644E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6249E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.9741E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.3807E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3090E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.9506E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3377E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.2320E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.7222E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6636E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1593 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1233 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1845 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1481 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1013 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.3009E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.6639E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.6246E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 9.6403E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 6.0747E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 0.1006 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 6.3414E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.7762E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.9663E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.7217E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6632E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.6115E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 4.3436E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.3592E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.5150E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.6589E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3542E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.6639E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6246E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.9744E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.3805E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3092E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.9504E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3374E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.2317E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.7218E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6633E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 39888.03018 | 39888.03018 | 2.91959 | 2.91959 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 11399.81854 | 11399.81854 | 0.48850 | 0.48850 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 29631.77781 | 29631.77781 | 2.16642 | 2.16642 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 20336.74117 | 20336.74117 | 0.87671 | 0.87671 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 28991.64952 | 28991.64952 | 2.13969 | 2.13969 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 26.78800 | 7.00621E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 36521.67694 | 36521.67694 | 1.57945 | 1.57945 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8625.22126 | 8625.22126 | 0.63655 | 0.63655 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 21.53500 | 6.99833E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 16569.51364 | 16569.51364 | 0.71813 | 0.71813 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11628.90079 | 11628.90079 | 0.85822 | 0.85822 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 22.65700 | 7.00000E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 10829.59600 | 10829.59600 | 0.46939 | 0.46939 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 18604.88179 | 18604.88179 | 1.37305 | 1.37305 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 16487.51388 | 16487.51388 | 0.71457 | 0.71457 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12256.09293 | 12256.09293 | 0.90451 | 0.90451 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 10783.22514 | 10783.22514 | 0.46737 | 0.46737 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7483.80201 | 7483.80201 | 0.55232 | 0.55232 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 21.07600 | 6.99765E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 12897.55151 | 12897.55151 | 0.55874 | 0.55874 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9528.83892 | 9528.83892 | 0.70324 | 0.70324 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 22.94600 | 7.00043E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 8510.51016 | 8510.51016 | 0.36872 | 0.36872 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 15068.87426 | 15068.87426 | 1.11211 | 1.11211 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 12845.03190 | 12845.03190 | 0.55646 | 0.55646 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 10187.27436 | 10187.27436 | 0.75184 | 0.75184 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 23.04800 | 7.00058E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 8475.96393 | 8475.96393 | 0.36722 | 0.36722 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8295.77430 | 8295.77430 | 0.61224 | 0.61224 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38200 | 6.99811E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 12509.74246 | 12509.74246 | 0.54187 | 0.54187 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 11541.45583 | 11541.45583 | 0.85177 | 0.85177 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 22.07900 | 6.99914E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 8227.34691 | 8227.34691 | 0.35640 | 0.35640 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 17539.13763 | 17539.13763 | 1.29441 | 1.29441 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 12438.31246 | 12438.31246 | 0.53876 | 0.53876 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11553.77416 | 11553.77416 | 0.85268 | 0.85268 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 8190.44137 | 8190.44137 | 0.35480 | 0.35480 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 74582.31 | 5.23703 | 5.23703 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 77706.93 | 2.33964 | 2.33964 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 67580.19 | 4.71518 | 4.71518 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 77843.09 | 2.66854 | 2.66854 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 73365.43 | 5.16688 | 5.16688 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 77874.55 | 3.94890 | 3.94890 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.91959 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25670 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27100 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79121 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68453 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.48423E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26014.54722 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.16642 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34594 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35500 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76908 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92251 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10134E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 28825.78635 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.13969 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35026 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36800 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78741 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93403 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08776E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 51931.42990 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71813 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22000 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26100 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18743 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58668 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.73178E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23611.78047 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85822 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11655 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17164 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31079 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.26911E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15433.18125 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.37305 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11507 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27461 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30684 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.31115E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23494.71389 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90451 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11057 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18090 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.44565E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15366.98162 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.55874 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28277 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16874 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75404 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34741E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18371.03044 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70324 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14223 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14065 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37928 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.67877E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12123.34190 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.11211 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14207 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22242 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37884 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.68187E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18296.04330 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75184 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13303 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15037 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35474 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.86406E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12074.02019 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61224 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25805 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26500 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16224 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68815 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47643E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17816.29563 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85177 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11743 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17035 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31314 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.24453E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11718.39212 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.29441 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12206 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25888 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32549 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.12149E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17714.31261 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85268 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11730 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17054 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31279 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.24821E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11665.70231 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.02275 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.47338 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.04551 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.33964 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.23703 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.23703 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.44675 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.88876 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.53109 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.77752 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.66854 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.71518 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.71518 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.56595 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.99680 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.60200 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.99361 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.94890 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.16688 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.16688 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.76427 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.23703 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.71518 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.16688 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.23703 |
149 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_BOT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.19517 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.23703 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 86691.50448 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.74550 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28894.27844 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
156 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 75334.25307 |
157 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.23703 |
158 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.71518 |
159 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_MID OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.19517 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.71518 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 78052.91804 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.57157 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 26015.03758 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
166 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 76651.63289 |
167 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.71518 |
168 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.16688 |
169 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_TOP OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.19517 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.16688 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 85530.16003 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
173 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.72212 |
174 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28507.20234 |
175 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
176 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 76691.97500 |
177 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.16688 |
178 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
179 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
180 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
181 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
182 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 85199.76 | 290713.65 | 10.81 | 2.80 | 3.09 | 3.26 | 3.43 | 9.54 | 10.55 | 11.11 | 11.69 | 5.9630 | 4.7166 | 3.1607 | 1.3172 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 76709.82 | 261744.78 | 10.81 | 2.80 | 3.09 | 3.26 | 3.43 | 9.54 | 10.55 | 11.11 | 11.69 | 5.3688 | 4.2466 | 2.8458 | 1.1860 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 84058.40 | 286819.16 | 10.81 | 2.80 | 3.09 | 3.26 | 3.43 | 9.54 | 10.55 | 11.11 | 11.69 | 5.8831 | 4.6534 | 3.1184 | 1.2996 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.119 | 0.959 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.119 | 0.959 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.119 | 0.959 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.119 | 0.959 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.779 | 0.698 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.779 | 0.698 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.779 | 0.698 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.779 | 0.698 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.794 | 0.710 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.794 | 0.710 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.794 | 0.710 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.794 | 0.710 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.119 | 0.959 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.119 | 0.959 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_EAST_0.45 | N/A | 1.661 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.119 | 0.959 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.119 | 0.959 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_WEST_0.45 | N/A | 1.661 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.794 | 0.710 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.171 | 0.164 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.794 | 0.710 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_EAST_0.45 | N/A | 1.661 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_EAST_0.45 | N/A | 1.661 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.180 | 0.173 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.794 | 0.710 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.171 | 0.164 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.794 | 0.710 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_WEST_0.45 | N/A | 1.661 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_WEST_0.45 | N/A | 1.661 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.180 | 0.173 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.779 | 0.698 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.779 | 0.698 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_EAST_0.45 | N/A | 1.661 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.779 | 0.698 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.779 | 0.698 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_WEST_0.45 | N/A | 1.661 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 2.0959324344E-002 | 1.3279599729E-002 | Pass | Pass | 0.4872472544 | 0.4929549149 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2796995490 | 0.1915468180 | Pass | Pass | 0.4908520467 | 0.4964835759 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1358949659 | 8.5084198662E-002 | Pass | Pass | 0.4865052428 | 0.4832032910 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1217038113 | 7.3524613967E-002 | Pass | Pass | 0.4847431998 | 0.4838520659 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 7.4943637355E-002 | 6.9523202610E-002 | Pass | Pass | 0.9112903721 | 1.1716596143 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.2134513550 | 0.2077018136 | Pass | Pass | 0.7265347489 | 0.6819638349 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.7947864387 | 0.7001420224 | Pass | Pass | 0.6119481203 | 0.5826761748 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.8239657393 | 0.8060474881 | Pass | Pass | 0.6551404654 | 0.6439521882 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.7812338992 | 0.7674980391 | Pass | Pass | 0.6636421095 | 0.6562090099 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.8209421938 | 0.8075773780 | Pass | Pass | 0.6579301846 | 0.6469153690 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6277944673 | 0.5514176035 | Pass | Pass | 0.6175622140 | 0.6239802816 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6633170674 | 0.6430495048 | Pass | Pass | 0.6889905645 | 0.7188446035 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.6188924097 | 0.6041605417 | Pass | Pass | 0.7029728346 | 0.7392509747 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6607509824 | 0.6471890619 | Pass | Pass | 0.6956821633 | 0.7261007026 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5986086083 | 0.5411899627 | Pass | Pass | 0.6577243449 | 0.5792320971 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6393495579 | 0.6270016848 | Pass | Pass | 0.7101115117 | 0.6669585288 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.6021419820 | 0.5871954492 | Pass | Pass | 0.7192026055 | 0.6803726801 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6372170028 | 0.6245019282 | Pass | Pass | 0.7101291031 | 0.6667141259 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2453.28 | 219.96 | 0.00 | 2579.33 | 303.86 | 5556.44 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.959 | 1.119 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.959 | 1.119 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.959 | 1.119 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.959 | 1.119 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.159 | 0.163 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.779 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.779 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.779 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.779 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.710 | 0.794 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.710 | 0.794 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.710 | 0.794 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.710 | 0.794 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.959 | 1.119 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.959 | 1.119 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.959 | 1.119 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.959 | 1.119 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.710 | 0.794 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.166 | 0.171 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.710 | 0.794 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.175 | 0.180 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.710 | 0.794 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.166 | 0.171 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.710 | 0.794 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.175 | 0.180 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.779 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.779 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.779 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.779 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.661 | 0.451 | 0.452 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.2925_SHGC_EAST_0.45 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.661 | 0.451 | 0.452 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.661 | 0.451 | 0.452 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.2925_SHGC_WEST_0.45 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.661 | 0.451 | 0.452 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.2925_SHGC_EAST_0.45 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.2925_SHGC_EAST_0.45 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.2925_SHGC_WEST_0.45 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.2925_SHGC_WEST_0.45 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.661 | 0.451 | 0.452 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.2925_SHGC_EAST_0.45 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.661 | 0.451 | 0.452 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.661 | 0.451 | 0.452 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.2925_SHGC_WEST_0.45 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.661 | 0.451 | 0.452 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 1.661 | 0.451 | 0.452 | |||||||||||||||||
North Total or Average | 177.99 | 1.661 | 0.451 | 0.452 | |||||||||||||||||
Non-North Total or Average | 415.31 | 1.661 | 0.451 | 0.452 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.5763 | 983.54 | 7451.60 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 45.39 | 0.0000 | Y | 63.48 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 34.00 | 0.0000 | Y | 10.03 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 33.75 | 0.0000 | Y | 6.30 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 33.37 | 0.0000 | Y | 9.84 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 33.68 | 0.0000 | Y | 6.29 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 33.93 | 0.0000 | Y | 10.01 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 33.70 | 0.0000 | Y | 6.29 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 33.32 | 0.0000 | Y | 9.82 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 33.63 | 0.0000 | Y | 6.28 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 34.00 | 0.0000 | Y | 10.03 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.5763 | 131.26 | 994.49 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 33.75 | 0.0000 | Y | 6.30 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.5763 | 207.34 | 1570.86 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 33.37 | 0.0000 | Y | 9.84 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.5763 | 131.25 | 994.42 | LightsWired | LTG_SCH_OFFICE | 46.59 | 168.00 | 33.68 | 0.0000 | Y | 6.29 |
Interior Lighting Total | 7.5763 | 4982.19 | 37746.71 | 287.76 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.49 | 381.39 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.49 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1570.86 | 602.43 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1570.86 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 994.42 | 381.36 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 994.42 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 44.84 | 44.84 | 3.58 | |
EXTERIOR_LIGHTS_B | 5132.60 | AstronomicalClock | - | 83.06 | 71.59 | 68.98 | |
Exterior Lighting Total | 5557.43 | 72.55 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 86691.50 | 69410.01 | 17281.50 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 78052.92 | 62493.48 | 15559.44 | 0.80 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 85530.16 | 68480.17 | 17049.99 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 85199.8 | 2.80 | 9.54 | N/A | N/A | 10.81 | |
PACU_VAV_MID COOLING COIL | 76709.8 | 2.80 | 9.54 | N/A | N/A | 10.81 | |
PACU_VAV_TOP COOLING COIL | 84058.4 | 2.80 | 9.54 | N/A | N/A | 10.81 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 26014.55 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 28825.79 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 51931.43 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 23611.78 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15433.18 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 23494.71 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15366.98 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18371.03 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12123.34 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18296.04 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12074.02 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17816.30 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11718.39 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17714.31 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11665.70 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 75334.25 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 76651.63 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 76691.97 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.24 | 12037.12 | 2298.46 | 1.00 | 1.13 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.72 | 10908.03 | 2313.39 | 1.00 | 1.13 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.17 | 11875.87 | 2298.46 | 1.00 | 1.13 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 85199.76 | 2.80 | 9.54 | 10.81 | 5.9630 | 3.09 | 10.55 | 4.7166 | 3.26 | 11.11 | 3.1607 | 3.43 | 11.69 | 1.3172 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 76709.82 | 2.80 | 9.54 | 10.81 | 5.3688 | 3.09 | 10.55 | 4.2466 | 3.26 | 11.11 | 2.8458 | 3.43 | 11.69 | 1.1860 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 84058.40 | 2.80 | 9.54 | 10.81 | 5.8831 | 3.09 | 10.55 | 4.6534 | 3.26 | 11.11 | 3.1184 | 3.43 | 11.69 | 1.2996 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 39888.03 | 39888.03 | 40.56 | 2.920 | 2.920 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00881 | 19.85 | 0.00700 | 0.425 | 0.00 |
CORE_MID | 29631.78 | 29631.78 | 30.13 | 2.166 | 2.166 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 19.85 | 0.00700 | 0.425 | 0.00 |
CORE_TOP | 28991.65 | 28991.65 | 29.48 | 2.140 | 2.140 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 24.00 | 24.00 | 0.00891 | 26.79 | 0.00701 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8625.22 | 8625.22 | 41.60 | 0.637 | 0.637 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 24.00 | 24.00 | 0.00873 | 21.54 | 0.00700 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11628.90 | 11628.90 | 88.59 | 0.858 | 0.858 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00861 | 22.66 | 0.00700 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 18604.88 | 18604.88 | 89.73 | 1.373 | 1.373 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00861 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12256.09 | 12256.09 | 93.38 | 0.905 | 0.905 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00860 | 24.70 | 0.00700 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7483.80 | 7483.80 | 36.09 | 0.552 | 0.552 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 24.00 | 24.00 | 0.00880 | 21.08 | 0.00700 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9528.84 | 9528.84 | 72.59 | 0.703 | 0.703 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00865 | 22.95 | 0.00700 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 15068.87 | 15068.87 | 72.68 | 1.112 | 1.112 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00865 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 10187.27 | 10187.27 | 77.62 | 0.752 | 0.752 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.00 | 24.00 | 0.00864 | 23.05 | 0.00700 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8295.77 | 8295.77 | 40.01 | 0.612 | 0.612 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00875 | 21.38 | 0.00700 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 11541.46 | 11541.46 | 87.93 | 0.852 | 0.852 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00861 | 22.08 | 0.00700 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 17539.14 | 17539.14 | 84.59 | 1.294 | 1.294 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00862 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11553.77 | 11553.77 | 88.03 | 0.853 | 0.853 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00861 | 24.70 | 0.00700 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 11399.82 | 11399.82 | 11.59 | 0.489 | 0.489 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
CORE_MID | 20336.74 | 20336.74 | 20.68 | 0.877 | 0.877 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
CORE_TOP | 36521.68 | 36521.68 | 37.13 | 1.579 | 1.579 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 16569.51 | 16569.51 | 79.92 | 0.718 | 0.718 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10829.60 | 10829.60 | 82.50 | 0.469 | 0.469 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 16487.51 | 16487.51 | 79.52 | 0.715 | 0.715 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10783.23 | 10783.23 | 82.16 | 0.467 | 0.467 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 12897.55 | 12897.55 | 62.21 | 0.559 | 0.559 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8510.51 | 8510.51 | 64.84 | 0.369 | 0.369 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12845.03 | 12845.03 | 61.95 | 0.556 | 0.556 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8475.96 | 8475.96 | 64.58 | 0.367 | 0.367 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 12509.74 | 12509.74 | 60.33 | 0.542 | 0.542 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8227.35 | 8227.35 | 62.68 | 0.356 | 0.356 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12438.31 | 12438.31 | 59.99 | 0.539 | 0.539 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 8190.44 | 8190.44 | 62.40 | 0.355 | 0.355 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.24 | 5.24 | 2.34 | 2.34 | 5.2370 | 2.3396 | 5.2370 | 0.4467 | 0.3000 |
PACU_VAV_MID | 4.72 | 4.72 | 2.67 | 2.67 | 4.7152 | 2.6685 | 4.7152 | 0.5659 | 0.3000 |
PACU_VAV_TOP | 5.17 | 5.17 | 3.95 | 3.95 | 5.1669 | 3.9489 | 5.1669 | 0.7643 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 26014.547 | 26014.547 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26014.55 | 16061.71 | 0.488502 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 11399.82 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 28825.786 | 28825.786 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28825.79 | 28825.79 | 0.876709 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 20336.74 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 51931.430 | 51931.430 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 51931.43 | 51931.43 | 1.579446 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 36521.68 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 23611.780 | 23611.780 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23611.78 | 23611.78 | 0.718130 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796760 | 50.7101 | 16569.51 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 15433.181 | 15433.181 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15433.18 | 15433.18 | 0.469386 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796695 | 50.7060 | 10829.60 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 23494.714 | 23494.714 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23494.71 | 23494.71 | 0.714570 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796743 | 50.7090 | 16487.51 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 15366.982 | 15366.982 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15366.98 | 15366.98 | 0.467372 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796681 | 50.7051 | 10783.23 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 18371.030 | 18371.030 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18371.03 | 18371.03 | 0.558738 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797763 | 50.7728 | 12897.55 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 12123.342 | 12123.342 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12123.34 | 12123.34 | 0.368720 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797748 | 50.7719 | 8510.51 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 18296.043 | 18296.043 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18296.04 | 18296.04 | 0.556457 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797752 | 50.7722 | 12845.03 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 12074.020 | 12074.020 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12074.02 | 12074.02 | 0.367220 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797738 | 50.7713 | 8475.96 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 17816.296 | 17816.296 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17816.30 | 17816.30 | 0.541866 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796398 | 50.6872 | 12509.74 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 11718.392 | 11718.392 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11718.39 | 11718.39 | 0.356404 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796358 | 50.6848 | 8227.35 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 17714.313 | 17714.313 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17714.31 | 17714.31 | 0.538764 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796375 | 50.6858 | 12438.31 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 11665.702 | 11665.702 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11665.70 | 11665.70 | 0.354801 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796341 | 50.6837 | 8190.44 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 86691.504 | 69410.009 | 5.237034 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 88059.49 | 88059.48 | 5.237034 | 24.78 | 16.39 | 0.00836889 | 10.90 | 10.90 | 0.00836889 | 27.40 | 0.00700714 | 16.15 | 22.8215 | 24.00 | 0.00877247 | 46.4715 | 70835.54 | 0.00 | 89390.58 | 69798.50 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 75334.253 | 75334.253 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 75334.25 | 75334.25 | 1.571110 | -27.45 | -27.45 | 0.00195341 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 76.0717 | 18.08 | 0.00795993 | 60.7391 | 21933.85 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 78052.918 | 62493.479 | 4.715177 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 79284.58 | 79284.58 | 4.715177 | 24.86 | 16.40 | 0.00834049 | 10.89 | 10.89 | 0.00834049 | 27.40 | 0.00700714 | 16.15 | 25.3473 | 24.00 | 0.00879479 | 46.5880 | 63723.54 | 0.00 | 80483.04 | 62843.26 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 76651.633 | 76651.633 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 76651.63 | 76651.63 | 1.414553 | -32.69 | -32.69 | 0.00128538 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 84.4910 | 17.60 | 0.00790839 | 62.2110 | 23135.31 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 85530.160 | 68480.173 | 5.166877 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 86925.58 | 86925.58 | 5.166877 | 24.76 | 16.38 | 0.00835728 | 10.90 | 10.90 | 0.00835728 | 27.30 | 0.00700699 | 16.11 | 23.1314 | 24.00 | 0.00876560 | 46.4354 | 69747.19 | 0.00 | 88193.08 | 68863.46 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 76691.975 | 76691.975 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 76691.97 | 76691.97 | 1.550063 | -28.74 | -28.74 | 0.00186627 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 77.1046 | 15.60 | 0.00790937 | 70.6583 | 25647.65 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 26014.547 | 26014.547 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26014.55 | 16061.71 | 1.0000 | 0.57908924 | 0.488502 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26014.55 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.81 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 11399.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 28825.786 | 28825.786 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 28825.79 | 28825.79 | 1.0000 | 1.03928558 | 0.876709 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28825.79 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 20336.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 51931.430 | 51931.430 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 51931.43 | 51931.43 | 1.0000 | 1.87233699 | 1.579446 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51931.43 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 36521.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 23611.780 | 23611.780 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23611.78 | 23611.78 | 1.0000 | 0.85129969 | 0.718130 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23611.78 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796760 | 21.00 | 0.00796760 | 50.7101 | 16569.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 15433.181 | 15433.181 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15433.18 | 15433.18 | 1.0000 | 0.55642828 | 0.469386 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15433.18 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796695 | 21.00 | 0.00796695 | 50.7060 | 10829.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 23494.714 | 23494.714 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23494.71 | 23494.71 | 1.0000 | 0.84707896 | 0.714570 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23494.71 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796743 | 21.00 | 0.00796743 | 50.7090 | 16487.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 15366.982 | 15366.982 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15366.98 | 15366.98 | 1.0000 | 0.55404151 | 0.467372 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15366.98 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796681 | 21.00 | 0.00796681 | 50.7051 | 10783.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 18371.030 | 18371.030 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18371.03 | 18371.03 | 1.0000 | 0.66234956 | 0.558738 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18371.03 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797763 | 21.00 | 0.00797763 | 50.7728 | 12897.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 12123.342 | 12123.342 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12123.34 | 12123.34 | 1.0000 | 0.43709525 | 0.368720 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12123.34 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797748 | 21.00 | 0.00797748 | 50.7719 | 8510.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 18296.043 | 18296.043 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18296.04 | 18296.04 | 1.0000 | 0.65964597 | 0.556457 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18296.04 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797752 | 21.00 | 0.00797752 | 50.7722 | 12845.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 12074.020 | 12074.020 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12074.02 | 12074.02 | 1.0000 | 0.43531701 | 0.367220 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12074.02 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797738 | 21.00 | 0.00797738 | 50.7713 | 8475.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 17816.296 | 17816.296 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17816.30 | 17816.30 | 1.0000 | 0.64234914 | 0.541866 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17816.30 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796398 | 21.00 | 0.00796398 | 50.6872 | 12509.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 11718.392 | 11718.392 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11718.39 | 11718.39 | 1.0000 | 0.42249518 | 0.356404 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11718.39 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796358 | 21.00 | 0.00796358 | 50.6848 | 8227.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 17714.313 | 17714.313 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17714.31 | 17714.31 | 1.0000 | 0.63867224 | 0.538764 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17714.31 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796375 | 21.00 | 0.00796375 | 50.6858 | 12438.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 11665.702 | 11665.702 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11665.70 | 11665.70 | 1.0000 | 0.42059550 | 0.354801 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11665.70 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796341 | 21.00 | 0.00796341 | 50.6837 | 8190.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 86691.504 | 69410.009 | 5.237034 | -999.0 | -999.000 | -999.0000 | 1.02754 | 1.00000 | 1020.3973 | 1004.8586 | 1.1854 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.237034 | 6.20818563 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 88059.49 | 88059.48 | 1.0158 | 6.20818563 | 5.237034 | 24.78 | 16.39 | 0.00836889 | 46211.9 | 10.90 | 10.90 | 0.00836889 | 32052.3 | -999.0 | -999.00 | -999.00 | -999.00 | 12037.121 | 76022.37 | 27.40 | 0.00700714 | 16.15 | 1.19517000 | 22.8215 | 24.00 | 0.00877247 | 24.00 | 0.00877247 | 46.4715 | 70835.54 | 0.00 | 89390.58 | 69798.50 | 5.96300923 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 75334.253 | 75334.253 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.237034 | 6.20818563 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 75334.25 | 75334.25 | 1.0000 | 1.86245569 | 1.571110 | -27.45 | -27.45 | 0.00195341 | -22800.5 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 75334.25 | -41.90 | 0.00006450 | -41.90 | 1.19517000 | 76.0717 | 18.47 | 0.00795851 | 18.08 | 0.00795993 | 60.7391 | 21933.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 78052.918 | 62493.479 | 4.715177 | -999.0 | -999.000 | -999.0000 | 1.02051 | 1.00000 | 1020.3446 | 1004.8586 | 1.1854 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.715177 | 5.58955583 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 79284.58 | 79284.58 | 1.0158 | 5.58955583 | 4.715177 | 24.86 | 16.40 | 0.00834049 | 46228.2 | 10.89 | 10.89 | 0.00834049 | 31968.0 | -999.0 | -999.00 | -999.00 | -999.00 | 10908.027 | 68376.56 | 27.40 | 0.00700714 | 16.15 | 1.19517000 | 25.3473 | 24.00 | 0.00879479 | 24.00 | 0.00879479 | 46.5880 | 63723.54 | 0.00 | 80483.04 | 62843.26 | 5.36881063 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 76651.633 | 76651.633 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.715177 | 5.58955583 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 76651.63 | 76651.63 | 1.0000 | 1.67686675 | 1.414553 | -32.69 | -32.69 | 0.00128538 | -29711.9 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 76651.63 | -41.90 | 0.00006450 | -41.90 | 1.19517000 | 84.4910 | 17.48 | 0.00793658 | 17.60 | 0.00790839 | 62.2110 | 23135.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 85530.160 | 68480.173 | 5.166877 | -999.0 | -999.000 | -999.0000 | 1.02890 | 1.00000 | 1020.3758 | 1004.8586 | 1.1854 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.166877 | 6.12501898 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 86925.58 | 86925.58 | 1.0163 | 6.12501898 | 5.166877 | 24.76 | 16.38 | 0.00835728 | 46170.6 | 10.90 | 10.90 | 0.00835728 | 32023.0 | -999.0 | -999.00 | -999.00 | -999.00 | 11875.868 | 75049.71 | 27.30 | 0.00700699 | 16.11 | 1.19517000 | 23.1314 | 24.00 | 0.00876560 | 24.00 | 0.00876560 | 46.4354 | 69747.19 | 0.00 | 88193.08 | 68863.46 | 5.88312704 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 76691.975 | 76691.975 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.166877 | 6.12501898 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 76691.97 | 76691.97 | 1.0000 | 1.83750570 | 1.550063 | -28.74 | -28.74 | 0.00186627 | -24306.5 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 76691.97 | -41.90 | 0.00006450 | -41.90 | 1.19517000 | 77.1046 | 15.60 | 0.00793406 | 15.60 | 0.00790937 | 70.6583 | 25647.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.24 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.72 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.17 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2003.50 | 3703.67 | 1064.50 |
CORE_MID | 2750.50 | 4250.67 | 2186.50 |
CORE_TOP | 3256.50 | 4544.50 | 2829.17 |
PERIMETER_TOP_ZN_3 | 3904.33 | 4636.67 | 3317.67 |
PERIMETER_TOP_ZN_2 | 4124.17 | 4310.83 | 3110.17 |
PERIMETER_TOP_ZN_1 | 3945.00 | 4313.83 | 2931.00 |
PERIMETER_TOP_ZN_4 | 3980.83 | 4643.17 | 3234.50 |
PERIMETER_BOT_ZN_3 | 3634.67 | 4703.67 | 3189.00 |
PERIMETER_BOT_ZN_2 | 3989.17 | 4128.67 | 2905.50 |
PERIMETER_BOT_ZN_1 | 3773.00 | 4510.67 | 2903.00 |
PERIMETER_BOT_ZN_4 | 3766.67 | 4497.67 | 3042.67 |
PERIMETER_MID_ZN_3 | 3742.00 | 4423.50 | 3047.33 |
PERIMETER_MID_ZN_2 | 3361.83 | 3571.50 | 2473.83 |
PERIMETER_MID_ZN_1 | 3756.17 | 4052.83 | 2615.50 |
PERIMETER_MID_ZN_4 | 3821.83 | 4385.83 | 2974.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5215.67 | 5111.83 | 3467.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 1.67 | 0.00 | 1.50 | 0.00 |
CORE_MID | 5.50 | 0.00 | 4.33 | 0.00 |
CORE_TOP | 32.33 | 0.00 | 24.17 | 0.00 |
PERIMETER_TOP_ZN_3 | 441.67 | 0.33 | 230.50 | 0.00 |
PERIMETER_TOP_ZN_2 | 267.33 | 8.50 | 67.83 | 8.17 |
PERIMETER_TOP_ZN_1 | 225.17 | 12.50 | 53.33 | 12.33 |
PERIMETER_TOP_ZN_4 | 269.50 | 13.17 | 73.33 | 3.67 |
PERIMETER_BOT_ZN_3 | 284.17 | 0.33 | 217.33 | 0.00 |
PERIMETER_BOT_ZN_2 | 85.50 | 7.67 | 22.33 | 6.50 |
PERIMETER_BOT_ZN_1 | 1043.17 | 6.50 | 968.33 | 6.00 |
PERIMETER_BOT_ZN_4 | 87.00 | 4.00 | 21.00 | 0.50 |
PERIMETER_MID_ZN_3 | 176.17 | 2.33 | 104.17 | 0.00 |
PERIMETER_MID_ZN_2 | 102.00 | 10.67 | 28.17 | 9.17 |
PERIMETER_MID_ZN_1 | 77.00 | 14.83 | 19.00 | 14.67 |
PERIMETER_MID_ZN_4 | 103.50 | 13.33 | 28.17 | 4.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1385.17 | 67.83 | 1093.50 | 47.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 0.863 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.656 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.626 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.807 | 0.054 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 1.318 | 0.056 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 1.367 | 0.054 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 1.174 | 0.056 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.690 | 0.028 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 1.153 | 0.030 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 1.166 | 1.360 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.976 | 0.030 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.774 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 1.219 | 0.050 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 1.373 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 1.163 | 0.047 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.56 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.49 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 13834720.84 | 0.00 | 13834720.84 | 0.00 | 13834720.84 | 13393058.27 | 6428.09 | 22.34 | 2309.57 | 510.04 |
CORE_MID | 10530702.43 | 0.00 | 10530702.43 | 0.00 | 10530702.43 | 13393058.27 | 6808.26 | 16.74 | 1934.99 | 436.30 |
CORE_TOP | 9983473.70 | 0.00 | 9983473.70 | 0.00 | 9983473.70 | 13393058.27 | 6895.59 | 15.93 | 1848.48 | 93.53 |
PERIMETER_TOP_ZN_3 | 2710394.03 | 0.00 | 2710394.03 | 370406.43 | 3080800.46 | 2823374.22 | 4277.47 | 72.32 | 4410.21 | 93.53 |
PERIMETER_TOP_ZN_2 | 2796598.08 | 0.00 | 2796598.08 | 246936.13 | 3043534.21 | 1787429.43 | 4152.23 | 1.54 | 4606.23 | 93.53 |
PERIMETER_TOP_ZN_1 | 4578398.31 | 0.00 | 4578398.31 | 370406.43 | 4948804.74 | 2823374.22 | 4151.47 | 1.61 | 4606.91 | 93.53 |
PERIMETER_TOP_ZN_4 | 2503760.04 | 0.00 | 2503760.04 | 246936.13 | 2750696.17 | 1787312.18 | 4148.38 | 1.11 | 4610.52 | 93.53 |
PERIMETER_BOT_ZN_3 | 2348408.60 | 0.00 | 2348408.60 | 196941.88 | 2545350.48 | 2823374.22 | 5788.08 | 63.58 | 2908.34 | 510.04 |
PERIMETER_BOT_ZN_2 | 2468168.48 | 0.00 | 2468168.48 | 131293.80 | 2599462.28 | 1787429.43 | 4130.18 | 4.63 | 4625.19 | 510.04 |
PERIMETER_BOT_ZN_1 | 3968683.30 | 0.00 | 3968683.30 | 4689941.95 | 8658625.25 | 2823374.22 | 4130.37 | 4.25 | 4625.38 | 510.04 |
PERIMETER_BOT_ZN_4 | 2104276.33 | 0.00 | 2104276.33 | 131293.80 | 2235570.13 | 1787312.18 | 4124.78 | 2.34 | 4632.88 | 510.04 |
PERIMETER_MID_ZN_3 | 2614907.75 | 0.00 | 2614907.75 | 308333.93 | 2923241.68 | 2823374.22 | 6039.47 | 49.83 | 2670.70 | 436.30 |
PERIMETER_MID_ZN_2 | 2864661.85 | 0.00 | 2864661.85 | 205554.72 | 3070216.57 | 1787429.43 | 4099.38 | 2.81 | 4657.81 | 1345.30 |
PERIMETER_MID_ZN_1 | 4619773.74 | 0.00 | 4619773.74 | 308333.93 | 4928107.67 | 2823374.22 | 4103.98 | 3.68 | 4652.34 | 436.30 |
PERIMETER_MID_ZN_4 | 2495102.74 | 0.00 | 2495102.74 | 205554.72 | 2700657.46 | 1787312.18 | 4099.35 | 2.63 | 4658.03 | 436.30 |
Total Facility | 70422030.23 | 0.00 | 70422030.23 | 7411933.84 | 77833964.07 | 67843644.98 | 7005.73 | 238.26 | 4742.12 | 1573.74 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6319 | 0.0000 | 0.6319 | 0.0000 | 0.6319 | 0.4247 | 3695.66 | 21.84 | 2225.50 |
CORE_MID | 0.4812 | 0.0000 | 0.4812 | 0.0000 | 0.4812 | 0.4247 | 4064.45 | 16.34 | 1862.21 |
CORE_TOP | 0.4591 | 0.0000 | 0.4591 | 0.0000 | 0.4591 | 0.4247 | 4136.64 | 15.69 | 1790.67 |
PERIMETER_TOP_ZN_3 | 0.1249 | 0.0000 | 0.1249 | 0.0083 | 0.1332 | 0.0895 | 1520.23 | 72.15 | 4350.62 |
PERIMETER_TOP_ZN_2 | 0.1291 | 0.0000 | 0.1291 | 0.0056 | 0.1346 | 0.0567 | 1395.28 | 1.54 | 4546.17 |
PERIMETER_TOP_ZN_1 | 0.2114 | 0.0000 | 0.2114 | 0.0083 | 0.2197 | 0.0895 | 1394.53 | 1.61 | 4546.86 |
PERIMETER_TOP_ZN_4 | 0.1150 | 0.0000 | 0.1150 | 0.0056 | 0.1206 | 0.0567 | 1391.43 | 1.11 | 4550.46 |
PERIMETER_BOT_ZN_3 | 0.1068 | 0.0000 | 0.1068 | 0.0044 | 0.1112 | 0.0895 | 3055.03 | 62.89 | 2825.08 |
PERIMETER_BOT_ZN_2 | 0.1128 | 0.0000 | 0.1128 | 0.0030 | 0.1158 | 0.0567 | 1403.17 | 4.63 | 4535.20 |
PERIMETER_BOT_ZN_1 | 0.1816 | 0.0000 | 0.1816 | 0.2144 | 0.3960 | 0.0895 | 1403.41 | 4.23 | 4535.37 |
PERIMETER_BOT_ZN_4 | 0.0956 | 0.0000 | 0.0956 | 0.0030 | 0.0986 | 0.0567 | 1397.92 | 2.28 | 4542.81 |
PERIMETER_MID_ZN_3 | 0.1198 | 0.0000 | 0.1198 | 0.0069 | 0.1267 | 0.0895 | 3296.03 | 49.68 | 2597.29 |
PERIMETER_MID_ZN_2 | 0.1193 | 0.0000 | 0.1193 | 0.0050 | 0.1243 | 0.0567 | 1357.00 | 2.81 | 3674.19 |
PERIMETER_MID_ZN_1 | 0.2123 | 0.0000 | 0.2123 | 0.0069 | 0.2192 | 0.0895 | 1361.58 | 3.68 | 4577.74 |
PERIMETER_MID_ZN_4 | 0.1139 | 0.0000 | 0.1139 | 0.0046 | 0.1185 | 0.0567 | 1356.97 | 2.63 | 4583.40 |
Total Facility | 3.2147 | 0.0000 | 3.2147 | 0.2760 | 3.4906 | 2.1513 | 4218.18 | 236.68 | 4619.31 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 34744162.73 | 0.00 | 34744162.73 | 22614548.33 | 4107.53 | 2.76 | 4649.70 | 510.02 |
PACU_VAV_MID | 32497003.73 | 0.00 | 32497003.73 | 22614548.33 | 4100.34 | 2.96 | 4656.70 | 434.76 |
PACU_VAV_TOP | 31720557.41 | 0.00 | 31720557.41 | 22614548.33 | 4149.14 | 2.23 | 4608.63 | 93.53 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.5862 | 0.0000 | 1.5862 | 0.7171 | 1380.48 | 2.76 | 4559.76 |
PACU_VAV_MID | 1.4877 | 0.0000 | 1.4877 | 0.7171 | 1357.94 | 2.96 | 4582.10 |
PACU_VAV_TOP | 1.4606 | 0.0000 | 1.4606 | 0.7171 | 1392.20 | 2.23 | 4548.57 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 2944.14 | 0.00 | 0.00 | 0.00 | 2441.85 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 2762.70 | 0.00 | 0.00 | 0.00 | 2568.18 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2208.27 | 0.00 | 0.00 | 0.00 | 2597.65 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.7272 | 0.0000 | 0.0000 | 0.0000 | 1.1425 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.5721 | 0.0000 | 0.0000 | 0.0000 | 1.1121 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.7283 | 0.0000 | 0.0000 | 0.0000 | 1.1217 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 545 |
Fields with Defaults | 2289 |
Autosized Fields | 152 |
Autosizable Fields | 205 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1990.59 | 15539.06 | 02-APR-17:30 | 286129.70 | 02-JAN-08:10 |
Electricity:Building | 1049.80 | 15341.49 | 29-JAN-11:10 | 75641.67 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 310.83 | 4652.71 | 01-JAN-00:10 | 24063.48 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1049.80 | 15341.49 | 29-JAN-11:10 | 75641.67 | 02-JAN-08:10 |
InteriorLights:Electricity | 287.76 | 1316.11 | 29-JAN-11:10 | 28079.40 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 287.76 | 1316.11 | 29-JAN-11:10 | 28079.40 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 287.76 | 1316.11 | 29-JAN-11:10 | 28079.40 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 287.76 | 1316.11 | 29-JAN-11:10 | 28079.40 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 190.09 | 2689.12 | 01-JAN-00:10 | 12686.61 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 63.48 | 307.97 | 01-JAN-00:10 | 5543.17 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.72 | 541.99 | 29-JAN-11:10 | 2674.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.03 | 40.03 | 29-JAN-11:10 | 1168.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.03 | 40.03 | 29-JAN-11:10 | 1168.55 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.20 | 343.10 | 15-JAN-11:20 | 1693.08 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.30 | 25.34 | 15-JAN-11:20 | 739.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.30 | 25.34 | 15-JAN-11:20 | 739.79 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.53 | 541.99 | 08-JAN-11:20 | 2674.43 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.84 | 40.03 | 08-JAN-11:20 | 1168.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.84 | 40.03 | 08-JAN-11:20 | 1168.55 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.18 | 343.10 | 22-JAN-11:40 | 1693.03 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.29 | 25.34 | 22-JAN-11:40 | 739.74 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.29 | 25.34 | 22-JAN-11:40 | 739.74 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.69 | 541.99 | 29-JAN-11:00 | 2674.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.01 | 40.03 | 29-JAN-11:00 | 1168.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.01 | 40.03 | 29-JAN-11:00 | 1168.55 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.19 | 343.10 | 15-JAN-11:10 | 1693.08 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.29 | 25.34 | 15-JAN-11:10 | 739.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.29 | 25.34 | 15-JAN-11:10 | 739.79 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.51 | 541.99 | 08-JAN-11:20 | 2674.43 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.82 | 40.03 | 08-JAN-11:20 | 1168.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.82 | 40.03 | 08-JAN-11:20 | 1168.55 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.17 | 343.10 | 22-JAN-11:30 | 1693.03 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.28 | 25.34 | 22-JAN-11:30 | 739.74 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.28 | 25.34 | 22-JAN-11:30 | 739.74 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 36.72 | 541.99 | 29-JAN-11:10 | 2674.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 10.03 | 40.03 | 29-JAN-11:10 | 1168.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 10.03 | 40.03 | 29-JAN-11:10 | 1168.55 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 23.20 | 343.10 | 15-JAN-11:20 | 1693.08 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 6.30 | 25.34 | 15-JAN-11:20 | 739.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 6.30 | 25.34 | 15-JAN-11:20 | 739.79 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 36.53 | 541.99 | 08-JAN-11:20 | 2674.43 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.84 | 40.03 | 08-JAN-11:20 | 1168.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.84 | 40.03 | 08-JAN-11:20 | 1168.55 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 23.18 | 343.10 | 22-JAN-11:40 | 1693.03 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 6.29 | 25.34 | 22-JAN-11:40 | 739.74 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 6.29 | 25.34 | 22-JAN-11:40 | 739.74 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 247.34 | 4344.73 | 01-JAN-00:10 | 18520.31 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 868.22 | 197.57 | 20-FEB-10:20 | 238366.27 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 12.99 | 197.13 | 01-JAN-00:10 | 928.21 | 17-MAR-07:20 |
Transformer:ExteriorEquipment:Electricity | 12.99 | 197.13 | 01-JAN-00:10 | 928.21 | 17-MAR-07:20 |
ElectricityPurchased:Facility | 1990.59 | 15539.06 | 10-JUN-18:20 | 286129.70 | 02-JAN-08:10 |
ElectricityPurchased:Plant | 1990.59 | 15539.06 | 10-JUN-18:20 | 286129.70 | 02-JAN-08:10 |
Cogeneration:ElectricityPurchased | 1990.59 | 15539.06 | 10-JUN-18:20 | 286129.70 | 02-JAN-08:10 |
General:Cogeneration:ElectricityPurchased | 1990.59 | 15539.06 | 10-JUN-18:20 | 286129.70 | 02-JAN-08:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1990.59 | 15539.06 | 10-JUN-18:20 | 286129.70 | 02-JAN-08:10 |
ElectricityNet:Plant | 1990.59 | 15539.06 | 10-JUN-18:20 | 286129.70 | 02-JAN-08:10 |
Cogeneration:ElectricityNet | 1990.59 | 15539.06 | 10-JUN-18:20 | 286129.70 | 02-JAN-08:10 |
General:Cogeneration:ElectricityNet | 1990.59 | 15539.06 | 10-JUN-18:20 | 286129.70 | 02-JAN-08:10 |
Heating:Electricity | 681.75 | 0.00 | 01-JAN-00:40 | 228592.13 | 02-JAN-06:20 |
General:Heating:Electricity | 681.75 | 0.00 | 01-JAN-00:40 | 228592.13 | 02-JAN-06:20 |
Fans:Electricity | 97.86 | 0.00 | 01-JAN-00:40 | 28452.94 | 12-JUL-15:10 |
General:Fans:Electricity | 97.86 | 0.00 | 01-JAN-00:40 | 28452.94 | 12-JUL-15:10 |
ExteriorLights:Electricity | 72.55 | 0.00 | 01-JAN-11:20 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 72.55 | 0.00 | 01-JAN-11:20 | 5557.43 | 01-JAN-06:10 |
HeatRecovery:Electricity | 24.95 | 0.00 | 01-JAN-00:10 | 2722.67 | 04-JAN-18:30 |
General:HeatRecovery:Electricity | 24.95 | 0.00 | 01-JAN-00:10 | 2722.67 | 04-JAN-18:30 |
Cooling:Electricity | 50.66 | 0.00 | 01-JAN-00:10 | 48772.86 | 30-JUN-14:30 |
General:Cooling:Electricity | 50.66 | 0.00 | 01-JAN-00:10 | 48772.86 | 30-JUN-14:30 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 8.09 | 0.00 | 01-JAN-00:10 | 789.03 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 641.94 | 12061.80 | 01-JAN-00:10 | 36271.65 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 350.88 | 1156.00 | 09-JAN-05:20 | 211066.48 | 12-JAN-07:30 |
NaturalGas:HVAC | 224.55 | 0.00 | 01-JAN-00:40 | 202788.89 | 12-JAN-07:30 |
Heating:NaturalGas | 224.55 | 0.00 | 01-JAN-00:40 | 202788.89 | 12-JAN-07:30 |
General:Heating:NaturalGas | 224.55 | 0.00 | 01-JAN-00:40 | 202788.89 | 12-JAN-07:30 |
NaturalGas:Plant | 126.33 | 1156.00 | 03-JAN-05:10 | 13396.13 | 27-FEB-12:30 |
WaterSystems:NaturalGas | 126.33 | 1156.00 | 03-JAN-05:10 | 13396.13 | 27-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 126.33 | 1156.00 | 03-JAN-05:10 | 13396.13 | 27-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2964.94 | 0.00 | 01-JAN-00:40 | 586312.10 | 27-FEB-07:10 |
EnergyTransfer:Building | 1384.39 | 0.00 | 01-JAN-00:40 | 230406.66 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 192.91 | 0.00 | 01-JAN-00:40 | 26248.11 | 24-JUL-08:00 |
Heating:EnergyTransfer | 622.33 | 0.00 | 01-JAN-00:40 | 230406.66 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 1.39 | 0.00 | 01-JAN-00:20 | 21282.23 | 02-JAN-07:00 |
General:Heating:EnergyTransfer | 622.33 | 0.00 | 01-JAN-00:40 | 230406.66 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 1.39 | 0.00 | 01-JAN-00:20 | 21282.23 | 02-JAN-07:00 |
Cooling:EnergyTransfer | 762.06 | 0.00 | 01-JAN-00:40 | 159507.29 | 12-JUL-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 191.53 | 0.00 | 01-JAN-00:40 | 26248.11 | 24-JUL-08:00 |
General:Cooling:EnergyTransfer | 762.06 | 0.00 | 01-JAN-00:40 | 159507.29 | 12-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 191.53 | 0.00 | 01-JAN-00:40 | 26248.11 | 24-JUL-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 91.27 | 0.00 | 01-JAN-00:40 | 19677.05 | 27-FEB-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 75.46 | 0.00 | 01-JAN-00:40 | 19677.05 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 75.46 | 0.00 | 01-JAN-00:40 | 19677.05 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 15.81 | 0.00 | 01-JAN-00:10 | 8433.10 | 21-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 15.81 | 0.00 | 01-JAN-00:10 | 8433.10 | 21-JUL-14:40 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 40.73 | 0.00 | 01-JAN-00:40 | 11716.22 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 28.87 | 0.00 | 01-JAN-00:40 | 11716.22 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 28.87 | 0.00 | 01-JAN-00:40 | 11716.22 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.85 | 0.00 | 01-JAN-00:10 | 4709.11 | 12-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.85 | 0.00 | 01-JAN-00:10 | 4709.11 | 12-JUL-16:00 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 38.19 | 0.00 | 01-JAN-00:40 | 9749.66 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 20.56 | 0.00 | 01-JAN-00:40 | 9749.66 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 20.56 | 0.00 | 01-JAN-00:40 | 9749.66 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.63 | 0.00 | 01-JAN-00:10 | 5150.55 | 12-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.63 | 0.00 | 01-JAN-00:10 | 5150.55 | 12-JUL-16:00 |
EnergyTransfer:Zone:CORE_MID | 128.55 | 0.00 | 01-JAN-00:40 | 25116.92 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 10.79 | 0.00 | 01-JAN-00:40 | 25116.92 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 10.79 | 0.00 | 01-JAN-00:40 | 25116.92 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 117.76 | 0.00 | 01-JAN-00:20 | 18292.06 | 24-JUL-07:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 117.76 | 0.00 | 01-JAN-00:20 | 18292.06 | 24-JUL-07:50 |
EnergyTransfer:Zone:CORE_TOP | 135.52 | 0.00 | 01-JAN-00:40 | 28361.77 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 38.10 | 0.00 | 01-JAN-00:40 | 28361.77 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 38.10 | 0.00 | 01-JAN-00:40 | 28361.77 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 97.42 | 0.00 | 01-JAN-00:20 | 18385.86 | 24-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 97.42 | 0.00 | 01-JAN-00:20 | 18385.86 | 24-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 74.39 | 0.00 | 01-JAN-00:40 | 10453.46 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 54.16 | 0.00 | 01-JAN-00:40 | 10453.46 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 54.16 | 0.00 | 01-JAN-00:40 | 10453.46 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 20.23 | 0.00 | 01-JAN-00:10 | 6314.07 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 20.23 | 0.00 | 01-JAN-00:10 | 6314.07 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 58.48 | 0.00 | 01-JAN-00:40 | 10967.65 | 07-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.24 | 0.00 | 01-JAN-00:40 | 10640.07 | 30-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.24 | 0.00 | 01-JAN-00:40 | 10640.07 | 30-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.23 | 0.00 | 01-JAN-00:10 | 10967.65 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.23 | 0.00 | 01-JAN-00:10 | 10967.65 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 87.72 | 0.00 | 01-JAN-00:40 | 16848.63 | 30-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 44.51 | 0.00 | 01-JAN-00:40 | 16848.63 | 30-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 44.51 | 0.00 | 01-JAN-00:40 | 16848.63 | 30-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 43.21 | 0.00 | 01-JAN-00:10 | 15739.82 | 10-AUG-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 43.21 | 0.00 | 01-JAN-00:10 | 15739.82 | 10-AUG-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 55.26 | 0.00 | 01-JAN-00:40 | 11108.61 | 30-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 35.14 | 0.00 | 01-JAN-00:40 | 11108.61 | 30-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 35.14 | 0.00 | 01-JAN-00:40 | 11108.61 | 30-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 20.11 | 0.00 | 01-JAN-00:10 | 8813.34 | 11-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 20.11 | 0.00 | 01-JAN-00:10 | 8813.34 | 11-JUL-17:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 55.08 | 0.00 | 01-JAN-00:40 | 8068.18 | 30-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 37.28 | 0.00 | 01-JAN-00:40 | 8068.18 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 37.28 | 0.00 | 01-JAN-00:40 | 8068.18 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 17.79 | 0.00 | 01-JAN-00:10 | 5391.88 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 17.79 | 0.00 | 01-JAN-00:10 | 5391.88 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 46.15 | 0.00 | 01-JAN-00:40 | 8688.54 | 27-FEB-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 23.09 | 0.00 | 01-JAN-00:40 | 8688.54 | 27-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 23.09 | 0.00 | 01-JAN-00:40 | 8688.54 | 27-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 23.06 | 0.00 | 01-JAN-00:10 | 8294.29 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 23.06 | 0.00 | 01-JAN-00:10 | 8294.29 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 121.65 | 0.00 | 01-JAN-00:40 | 27189.56 | 12-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 95.49 | 0.00 | 01-JAN-00:40 | 27189.56 | 12-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 95.49 | 0.00 | 01-JAN-00:40 | 27189.56 | 12-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 26.16 | 0.00 | 01-JAN-00:20 | 13691.88 | 21-JUL-16:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 26.16 | 0.00 | 01-JAN-00:20 | 13691.88 | 21-JUL-16:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 42.17 | 0.00 | 01-JAN-00:40 | 9179.98 | 27-FEB-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 24.70 | 0.00 | 01-JAN-00:40 | 9179.98 | 27-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 24.70 | 0.00 | 01-JAN-00:40 | 9179.98 | 27-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 17.48 | 0.00 | 01-JAN-00:20 | 7040.91 | 31-JUL-18:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 17.48 | 0.00 | 01-JAN-00:20 | 7040.91 | 31-JUL-18:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 54.38 | 0.00 | 01-JAN-00:40 | 8735.41 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 32.41 | 0.00 | 01-JAN-00:40 | 8735.41 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 32.41 | 0.00 | 01-JAN-00:40 | 8735.41 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 21.98 | 0.00 | 01-JAN-00:10 | 6822.70 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 21.98 | 0.00 | 01-JAN-00:10 | 6822.70 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 47.37 | 0.00 | 01-JAN-00:40 | 10784.83 | 07-JUL-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 20.40 | 0.00 | 01-JAN-00:40 | 8874.38 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 20.40 | 0.00 | 01-JAN-00:40 | 8874.38 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 26.96 | 0.00 | 01-JAN-00:20 | 10784.83 | 07-JUL-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 26.96 | 0.00 | 01-JAN-00:20 | 10784.83 | 07-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 71.95 | 0.00 | 01-JAN-00:40 | 15289.13 | 10-AUG-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 25.64 | 0.00 | 01-JAN-00:40 | 13257.23 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 25.64 | 0.00 | 01-JAN-00:40 | 13257.23 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 46.31 | 0.00 | 01-JAN-00:20 | 15289.13 | 10-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 46.31 | 0.00 | 01-JAN-00:20 | 15289.13 | 10-AUG-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 42.63 | 0.00 | 01-JAN-00:40 | 8817.52 | 27-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 21.09 | 0.00 | 01-JAN-00:40 | 8817.52 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 21.09 | 0.00 | 01-JAN-00:40 | 8817.52 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 21.54 | 0.00 | 01-JAN-00:20 | 8443.41 | 11-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 21.54 | 0.00 | 01-JAN-00:20 | 8443.41 | 11-JUL-17:40 |
PlantLoopHeatingDemand:Facility | 64.03 | 0.00 | 01-JAN-00:10 | 7551.92 | 06-JAN-12:30 |
PlantLoopHeatingDemand:Plant | 64.03 | 0.00 | 01-JAN-00:10 | 7551.92 | 06-JAN-12:30 |
WaterSystems:PlantLoopHeatingDemand | 64.03 | 0.00 | 01-JAN-00:10 | 7551.92 | 06-JAN-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 64.03 | 0.00 | 01-JAN-00:10 | 7551.92 | 06-JAN-12:30 |
EnergyTransfer:HVAC | 1516.52 | 0.00 | 01-JAN-00:40 | 361851.50 | 27-FEB-07:10 |
HeatingCoils:EnergyTransfer | 861.39 | 0.00 | 01-JAN-00:40 | 361851.50 | 27-FEB-07:10 |
HeatRecoveryForHeating:EnergyTransfer | 446.64 | 0.00 | 01-JAN-00:10 | 99319.26 | 07-NOV-07:20 |
HeatRecoveryForCooling:EnergyTransfer | 0.20 | 0.00 | 01-JAN-00:10 | 13568.69 | 29-JUL-16:00 |
CoolingCoils:EnergyTransfer | 208.29 | 0.00 | 01-JAN-00:10 | 201123.13 | 30-JUN-12:10 |
EnergyTransfer:Plant | 64.03 | 0.00 | 01-JAN-00:10 | 7551.92 | 06-JAN-12:30 |
WaterSystems:EnergyTransfer | 64.03 | 0.00 | 01-JAN-00:10 | 7551.92 | 06-JAN-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 64.03 | 0.00 | 01-JAN-00:10 | 7551.92 | 06-JAN-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 1.385 | -191.527 | 0.000 | 0.000 | 34.324 | 63.485 | 247.342 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -155.010 |
CORE_MID | 0.000 | 0.000 | 10.795 | -117.758 | 0.000 | 0.000 | 35.810 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -118.932 |
CORE_TOP | 0.000 | 0.000 | 38.099 | -97.417 | 0.000 | 0.000 | 36.373 | 63.485 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -167.141 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 54.164 | -20.227 | 0.000 | 0.000 | 7.786 | 10.027 | 26.688 | 15.658 | 0.000 | 0.005 | 0.001 | 0.000 | -47.989 | 0.000 | -8.352 | -37.760 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 33.241 | -25.234 | 0.000 | 0.000 | 4.870 | 6.300 | 16.895 | 34.991 | 0.000 | 0.003 | 0.000 | 0.000 | -30.575 | 0.000 | -5.626 | -34.865 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 44.509 | -43.214 | 0.000 | 0.000 | 7.672 | 9.841 | 26.688 | 68.759 | 0.000 | 0.004 | 0.001 | 0.000 | -43.859 | 0.000 | -8.569 | -61.833 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 35.145 | -20.114 | 0.000 | 0.000 | 4.944 | 6.286 | 16.895 | 24.484 | 0.000 | 0.003 | 0.000 | 0.000 | -31.375 | 0.000 | -5.653 | -30.615 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 37.285 | -17.792 | 0.000 | 0.000 | 7.768 | 10.006 | 26.688 | 15.832 | 0.000 | 0.003 | 0.000 | 0.000 | -48.750 | 0.000 | -4.548 | -26.492 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 23.092 | -23.056 | 0.000 | 0.000 | 4.838 | 6.291 | 16.895 | 35.028 | 0.000 | 0.002 | 0.000 | 0.000 | -31.293 | 0.000 | -3.110 | -28.687 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 95.492 | -26.160 | 0.000 | 0.000 | 8.100 | 9.824 | 26.688 | 69.425 | 0.000 | 0.129 | 0.000 | 0.000 | -43.908 | 0.000 | -108.539 | -31.051 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 24.698 | -17.475 | 0.000 | 0.000 | 4.901 | 6.277 | 16.895 | 24.564 | 0.000 | 0.002 | 0.000 | 0.000 | -32.046 | 0.000 | -3.104 | -24.712 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 32.406 | -21.976 | 0.000 | 0.000 | 7.704 | 10.027 | 26.688 | 15.353 | 0.000 | 0.004 | 0.001 | 0.000 | -49.452 | 0.000 | -7.203 | -13.551 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 20.402 | -26.965 | 0.000 | 0.000 | 3.581 | 6.300 | 16.895 | 34.786 | 0.000 | 0.003 | 0.000 | 0.000 | -31.449 | 0.000 | -4.840 | -18.714 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 25.635 | -46.311 | 0.000 | 0.000 | 7.595 | 9.841 | 26.688 | 68.432 | 0.000 | 0.004 | 0.001 | 0.000 | -45.261 | 0.000 | -7.390 | -39.233 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 21.093 | -21.537 | 0.000 | 0.000 | 4.896 | 6.286 | 16.895 | 24.309 | 0.000 | 0.002 | 0.000 | 0.000 | -32.317 | 0.000 | -4.866 | -14.760 |
TOPFLOOR_PLENUM | 75.463 | -15.808 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.003 | 0.000 | 0.000 | 0.000 | 0.000 | -12.663 | -46.994 |
MIDFLOOR_PLENUM | 28.873 | -11.854 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.004 | 0.001 | 0.000 | 0.000 | 0.000 | -12.186 | -4.837 |
FIRSTFLOOR_PLENUM | 20.558 | -17.632 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.003 | 6.776 | 0.000 | 0.000 | 0.000 | -9.706 | -0.001 |
Total Facility | 124.894 | -45.294 | 497.442 | -716.763 | 0.000 | 0.000 | 181.161 | 287.761 | 762.041 | 431.622 | 0.000 | 0.172 | 6.783 | 0.000 | -468.274 | 0.000 | -206.353 | -855.187 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 14-AUG-04:02 | 0.00 | 0.00 | 0.00 | -45591.35 | 0.00 | 0.00 | 0.00 | 615.87 | 5138.45 | 0.00 | 0.00 | 0.00 | 39837.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 24-JUL-04:02 | 0.00 | 0.00 | 0.00 | -34045.12 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 30254.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-04:02 | 0.00 | 0.00 | 0.00 | -32584.90 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 28794.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 11-JUL-06:02 | 0.00 | 0.00 | 0.00 | -10109.18 | 0.00 | 0.00 | 144.48 | 240.13 | 669.29 | 5129.29 | 0.00 | 0.00 | 3971.29 | 0.00 | -0.00 | 0.00 | -45.30 | 0.00 |
PERIMETER_TOP_ZN_2 | 23-JUL-09:41 | 0.00 | 0.00 | 0.00 | -16619.78 | 0.00 | 0.00 | 12.88 | 25.34 | 317.77 | 11438.23 | 0.00 | 0.00 | 4926.09 | 0.00 | -0.00 | 0.00 | -100.52 | 0.00 |
PERIMETER_TOP_ZN_1 | 23-JUL-12:21 | 0.00 | 0.00 | 0.00 | -26468.21 | 0.00 | 0.00 | 19.79 | 40.03 | 501.96 | 18246.30 | 0.00 | 0.00 | 7703.96 | 0.00 | -0.00 | 0.00 | -43.82 | 0.00 |
PERIMETER_TOP_ZN_4 | 14-MAY-18:22 | 0.00 | 0.00 | 0.00 | -15418.71 | 0.00 | 0.00 | 0.00 | 25.34 | 317.76 | 10407.45 | 0.00 | 0.00 | 5077.20 | 0.00 | -0.00 | 0.00 | -409.04 | 0.00 |
PERIMETER_BOT_ZN_3 | 11-JUL-04:02 | 0.00 | 0.00 | 0.00 | -8413.35 | 0.00 | 0.00 | 0.00 | 80.04 | 669.29 | 9355.89 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -179.33 | -1512.53 |
PERIMETER_BOT_ZN_2 | 23-JUL-10:32 | 0.00 | 0.00 | 0.00 | -10187.68 | 0.00 | 0.00 | 15.09 | 25.34 | 317.77 | 8931.61 | 0.00 | 0.00 | 908.28 | 0.00 | -0.00 | 0.00 | -10.40 | 0.00 |
PERIMETER_BOT_ZN_1 | 23-JUL-13:52 | 0.00 | 0.00 | 0.00 | -18953.02 | 0.00 | 0.00 | 23.08 | 40.03 | 501.96 | 16645.43 | 0.00 | 0.00 | 1762.84 | 0.00 | -0.00 | 0.00 | -20.32 | 0.00 |
PERIMETER_BOT_ZN_4 | 14-MAY-19:02 | 0.00 | 0.00 | 0.00 | -10281.18 | 0.00 | 0.00 | 0.00 | 25.34 | 317.76 | 8840.95 | 0.00 | 0.00 | 1292.12 | 0.00 | -0.00 | 0.00 | -194.99 | 0.00 |
PERIMETER_MID_ZN_3 | 07-JUN-04:02 | 0.00 | 0.00 | 0.00 | -9740.94 | 0.00 | 0.00 | 0.00 | 80.04 | 669.29 | 9247.82 | 0.00 | 0.00 | 36.32 | 0.00 | -0.00 | 0.00 | -292.54 | 0.00 |
PERIMETER_MID_ZN_2 | 09-JUL-07:02 | 0.00 | 0.00 | 0.00 | -14828.85 | 0.00 | 0.00 | 15.01 | 25.34 | 317.77 | 10345.27 | 0.00 | 0.00 | 4302.69 | 0.00 | -0.00 | 0.00 | -177.22 | 0.00 |
PERIMETER_MID_ZN_1 | 27-AUG-13:01 | 0.00 | 0.00 | 0.00 | -24361.91 | 0.00 | 0.00 | 21.42 | 40.03 | 501.96 | 18387.12 | 0.00 | 0.00 | 5546.97 | 0.00 | -0.00 | 0.00 | -135.59 | 0.00 |
PERIMETER_MID_ZN_4 | 27-AUG-17:42 | 0.00 | 0.00 | 0.00 | -15019.79 | 0.00 | 0.00 | 0.00 | 25.34 | 317.76 | 9643.62 | 0.00 | 0.00 | 5254.10 | 0.00 | -0.00 | 0.00 | -221.03 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-14:40 | 0.00 | -8434.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 | 8421.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 24-JUL-06:13 | 0.00 | -4982.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5042.07 | 0.00 | -0.00 | 0.00 | -59.24 | 0.00 |
FIRSTFLOOR_PLENUM | 12-JAN-17:09 | 0.00 | -5956.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5956.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-06:01 | 0.00 | -6204.66 | 0.00 | -170901.86 | 0.00 | 0.00 | 3598.93 | 7896.02 | 21853.28 | 30090.60 | 0.00 | 0.00 | 125688.99 | 0.00 | 0.00 | 0.00 | -12021.29 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 24656.96 | 0.00 | 0.00 | 0.00 | 0.00 | 615.87 | 5138.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -30411.29 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 28565.53 | 0.00 | 0.00 | 0.00 | 0.00 | 615.87 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -32356.27 |
CORE_TOP | 01-JAN-20:42 | 0.00 | 0.00 | 31535.31 | 0.00 | 0.00 | 0.00 | 0.00 | 307.97 | 2381.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -34224.43 |
PERIMETER_TOP_ZN_3 | 30-JAN-06:01 | 0.00 | 0.00 | 11453.07 | 0.00 | 0.00 | 0.00 | 121.14 | 129.83 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3469.70 | 0.00 | -363.28 | -8540.35 |
PERIMETER_TOP_ZN_2 | 29-JAN-17:22 | 0.00 | 0.00 | 13333.06 | 0.00 | 0.00 | 0.00 | 38.50 | 41.10 | 317.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2076.77 | 0.00 | -845.41 | -10808.25 |
PERIMETER_TOP_ZN_1 | 01-JAN-19:22 | 0.00 | 0.00 | 21163.96 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2402.10 | 0.00 | -1409.11 | -17919.64 |
PERIMETER_TOP_ZN_4 | 29-JAN-14:02 | 0.00 | 0.00 | 14010.73 | 0.00 | 0.00 | 0.00 | 38.48 | 29.64 | 317.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1658.10 | 0.00 | -1170.89 | -11567.62 |
PERIMETER_BOT_ZN_3 | 01-JAN-19:22 | 0.00 | 0.00 | 8704.81 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2463.25 | 0.00 | -740.91 | -6067.54 |
PERIMETER_BOT_ZN_2 | 30-JAN-05:11 | 0.00 | 0.00 | 10786.73 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2287.62 | 0.00 | -490.45 | -8514.54 |
PERIMETER_BOT_ZN_1 | 12-JAN-07:10 | 0.00 | 0.00 | 27991.17 | 0.00 | 0.00 | 0.00 | 224.12 | 389.51 | 669.28 | 0.00 | 0.00 | 0.00 | 31426.10 | 0.00 | -4416.21 | 0.00 | -56283.97 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-JAN-05:11 | 0.00 | 0.00 | 11521.50 | 0.00 | 0.00 | 0.00 | 0.00 | 82.19 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2328.57 | 0.00 | -490.74 | -9208.07 |
PERIMETER_MID_ZN_3 | 29-JAN-01:02 | 0.00 | 0.00 | 9548.22 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3627.54 | 0.00 | -2954.68 | -3532.89 |
PERIMETER_MID_ZN_2 | 29-JAN-01:02 | 0.00 | 0.00 | 12377.06 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 317.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2413.20 | 0.00 | -2002.79 | -8319.94 |
PERIMETER_MID_ZN_1 | 01-JAN-19:22 | 0.00 | 0.00 | 18610.58 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2445.02 | 0.00 | -1190.97 | -15541.47 |
PERIMETER_MID_ZN_4 | 29-JAN-01:02 | 0.00 | 0.00 | 12309.26 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 317.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2352.13 | 0.00 | -2004.36 | -8311.62 |
TOPFLOOR_PLENUM | 12-JAN-06:13 | 20380.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -20380.56 |
MIDFLOOR_PLENUM | 02-JAN-07:03 | 12682.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -277.21 | -12405.67 |
FIRSTFLOOR_PLENUM | 02-JAN-07:01 | 10989.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -214.04 | -10775.89 |
Total Facility | 02-JAN-05:01 | 21462.16 | 0.00 | 231507.44 | 0.00 | 0.00 | 0.00 | 0.00 | 3119.77 | 18045.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25600.96 | 0.00 | -4660.34 | -243874.06 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.0455 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.2370 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.7775 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7152 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.9936 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.1669 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.0228 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4734 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.8888 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5311 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.9968 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.6020 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9196 | 2.9196 | 0.7912 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1664 | 2.1664 | 0.7691 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1397 | 2.1397 | 0.7874 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7181 | 0.7181 | 0.1874 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8582 | 0.8582 | 0.1716 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3731 | 1.3731 | 0.2746 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9045 | 0.9045 | 0.1809 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5587 | 0.5587 | 0.1687 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7032 | 0.7032 | 0.1406 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1121 | 1.1121 | 0.2224 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7518 | 0.7518 | 0.1504 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6122 | 0.6122 | 0.1622 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8518 | 0.8518 | 0.1704 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2944 | 1.2944 | 0.2589 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8527 | 0.8527 | 0.1705 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.0455 | 5.2370 | 6.0455 | 1.4734 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.7775 | 4.7152 | 5.7775 | 1.5311 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.9936 | 5.1669 | 5.9936 | 1.6020 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4598 | 1.4598 | 0.7912 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0832 | 1.0832 | 0.7691 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0698 | 1.0698 | 0.7874 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3591 | 0.3591 | 0.1874 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4291 | 0.4291 | 0.1716 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6865 | 0.6865 | 0.2746 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4523 | 0.4523 | 0.1809 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2794 | 0.2794 | 0.1687 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3516 | 0.3516 | 0.1406 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5561 | 0.5561 | 0.2224 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3759 | 0.3759 | 0.1504 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3061 | 0.3061 | 0.1622 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4259 | 0.4259 | 0.1704 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6472 | 0.6472 | 0.2589 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4263 | 0.4263 | 0.1705 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.0228 | 1.4734 | 1.4734 | 1.4734 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.8888 | 1.5311 | 1.5311 | 1.5311 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.9968 | 1.6020 | 1.6020 | 1.6020 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 1093.50 |
Number of hours cooling loads not met | 47.83 |
Number of hours not met | 1141.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 681.75 | 228592.13 | 224.55 | 202788.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 50.66 | 48772.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 287.76 | 28079.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 72.55 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 641.30 | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 12.99 | 928.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 97.86 | 28452.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 24.95 | 2722.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 126.33 | 13396.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 762.04 | 1990.59 |
Natural Gas | 0.00 | 350.88 |
Additional | 0.00 | 0.00 |
Total | 762.04 | 2341.47 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 57.76 |
Space Heating | 136.84 |
Space Cooling | 10.17 |
Fans (All) | 19.64 |
Service Water Heating | 0.00 |
Receptacle Equipment | 152.95 |
Miscellaneous (All) | 399.54 |
Subtotal | 399.54 |
Natural Gas [MJ/m2] | |
Space Heating | 45.07 |
Service Water Heating | 25.36 |
Miscellaneous (All) | 70.43 |
Subtotal | 70.43 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.29 |
Space Heating | 38.71 |
Space Cooling | 2.16 |
Fans (All) | 4.18 |
Service Water Heating | 5.40 |
Receptacle Equipment | 32.55 |
Miscellaneous | 4.72 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2429. | 8760. |
BLDG_EQUIP_SCH | 4487. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8745.33 | 14.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8750.00 | 10.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8747.00 | 13.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8748.83 | 11.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8751.83 | 8.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8746.33 | 13.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8756.17 | 3.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8746.00 | 14.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8744.00 | 16.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8754.33 | 5.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8744.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 16.00 | 0.00 | 0.00 | 0.00 |
Average | 8753.23 | 6.77 | 0.00 | 0.00 | 0.00 |
Sum | 157558.17 | 121.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8706.00 | 54.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8746.00 | 14.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8751.50 | 8.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8756.67 | 3.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8751.50 | 8.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8750.67 | 9.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8746.67 | 13.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8753.17 | 6.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8706.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 54.00 | 0.00 | 0.00 | 0.00 |
Average | 8752.63 | 7.37 | 0.00 | 0.00 | 0.00 |
Sum | 157547.33 | 132.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128275.67 | 28.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128300.00 | 4.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 28.33 | 0.00 | 0.00 | 0.00 |
Average | 34141.54 | 1.80 | 0.00 | 0.00 | 0.00 |
Sum | 614547.67 | 32.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:13
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.827231E+10 | 7335.94 | 27-JAN-17:00 | -12.2 | -12.5 | 0.160256E+10 | 2403.51 | 27-JAN-14:09 | -12.2 | -12.5 |
February | 0.885957E+10 | 7905.48 | 10-FEB-17:00 | -0.6 | -2.2 | 0.153549E+10 | 2557.37 | 17-FEB-14:09 | -13.4 | -14.5 |
March | 0.109086E+11 | 11324.71 | 23-MAR-07:50 | -3.3 | -5.1 | 0.198719E+10 | 2608.09 | 23-MAR-09:20 | -2.6 | -4.5 |
April | 0.144518E+11 | 39360.89 | 28-APR-05:02 | -1.5 | -2.2 | 0.188152E+10 | 2608.57 | 12-APR-09:20 | -1.5 | -2.2 |
May | 0.232778E+11 | 41648.98 | 10-MAY-05:02 | 5.28 | 0.78 | 0.207460E+10 | 2606.66 | 19-MAY-13:39 | 13.87 | 8.18 |
June | 0.267615E+11 | 44116.15 | 19-JUN-04:02 | 6.88 | 6.30 | 0.207136E+10 | 2606.70 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.261259E+11 | 44675.68 | 17-JUL-04:03 | 8.30 | 8.30 | 0.192563E+10 | 2607.04 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.264082E+11 | 45598.14 | 14-AUG-04:02 | 11.60 | 10.40 | 0.216031E+10 | 2606.65 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.177963E+11 | 42428.17 | 01-SEP-05:02 | 7.12 | 5.68 | 0.191024E+10 | 2608.79 | 22-SEP-09:20 | 2.97 | 1.53 |
October | 0.113666E+11 | 16323.53 | 06-OCT-07:06 | 6.28 | 2.55 | 0.191049E+10 | 2608.48 | 05-OCT-09:20 | 6.28 | 2.55 |
November | 0.865068E+10 | 7763.26 | 03-NOV-16:00 | -11.1 | -11.5 | 0.167111E+10 | 2511.12 | 03-NOV-13:09 | -11.1 | -11.5 |
December | 0.864711E+10 | 7026.28 | 21-DEC-17:00 | -16.7 | -17.3 | 0.153938E+10 | 2326.74 | 22-DEC-14:09 | -23.7 | -24.0 |
Annual Sum or Average | 0.191526E+12 | 0.222699E+11 | ||||||||
Minimum of Months | 0.827231E+10 | 7026.28 | -16.7 | -17.3 | 0.153549E+10 | 2326.74 | -23.7 | -24.0 | ||
Maximum of Months | 0.267615E+11 | 45598.14 | 11.60 | 10.40 | 0.216031E+10 | 2608.79 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 9943745.93 | 938.57 | 22-MAR-17:10 | 5.13 | 1.52 | 0.00 | 0.00 | 01-MAR-00:10 | 5.13 | 1.52 |
April | 0.707784E+09 | 3948.55 | 21-APR-15:40 | 14.23 | 5.51 | 0.00 | 0.00 | 01-APR-00:10 | 14.23 | 5.51 |
May | 0.256355E+10 | 7139.68 | 31-MAY-14:40 | 20.73 | 10.55 | 0.00 | 0.00 | 01-MAY-00:10 | 20.73 | 10.55 |
June | 0.463251E+10 | 8303.53 | 29-JUN-14:50 | 26.02 | 16.10 | 0.00 | 0.00 | 01-JUN-00:10 | 26.02 | 16.10 |
July | 0.459701E+10 | 8433.10 | 21-JUL-14:40 | 27.23 | 14.65 | 0.00 | 0.00 | 01-JUL-00:10 | 27.23 | 14.65 |
August | 0.289221E+10 | 7146.97 | 10-AUG-15:30 | 22.50 | 12.09 | 0.00 | 0.00 | 01-AUG-00:10 | 22.50 | 12.09 |
September | 0.399694E+09 | 2696.17 | 07-SEP-15:30 | 16.65 | 8.91 | 0.00 | 0.00 | 01-SEP-00:10 | 16.65 | 8.91 |
October | 6076433.94 | 805.38 | 03-OCT-16:10 | 11.60 | 6.16 | 0.00 | 0.00 | 01-OCT-00:10 | 11.60 | 6.16 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.158088E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.00 | 0.00 | -25.8 | -26.0 | ||
Maximum of Months | 0.463251E+10 | 8433.10 | 27.23 | 16.10 | 0.00 | 0.00 | 27.23 | 16.10 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8601883.03 | 2766.43 | 11-JAN-05:11 | -27.6 | -27.7 | 0.00 | 0.00 | 01-JAN-00:10 | -27.6 | -27.7 |
February | 6392584.94 | 2856.28 | 18-FEB-05:01 | -23.9 | -24.3 | 0.00 | 0.00 | 01-FEB-00:10 | -23.9 | -24.3 |
March | 11026569.04 | 3148.04 | 04-MAR-05:01 | -26.1 | -26.5 | 0.00 | 0.00 | 01-MAR-00:10 | -26.1 | -26.5 |
April | 0.276870E+09 | 2989.74 | 14-APR-06:01 | -5.8 | -7.0 | 0.00 | 0.00 | 01-APR-00:10 | -5.8 | -7.0 |
May | 0.168683E+10 | 3465.96 | 31-MAY-16:00 | 22.20 | 10.79 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 10.79 |
June | 0.356316E+10 | 4480.86 | 30-JUN-14:30 | 27.75 | 17.00 | 0.00 | 0.00 | 01-JUN-00:10 | 27.75 | 17.00 |
July | 0.348041E+10 | 4982.83 | 24-JUL-06:13 | 14.47 | 13.19 | 0.00 | 0.00 | 01-JUL-00:10 | 14.47 | 13.19 |
August | 0.240155E+10 | 4031.52 | 11-AUG-16:00 | 25.60 | 14.77 | 0.00 | 0.00 | 01-AUG-00:10 | 25.60 | 14.77 |
September | 0.364002E+09 | 1339.92 | 29-SEP-06:01 | -4.6 | -5.0 | 0.00 | 0.00 | 01-SEP-00:10 | -4.6 | -5.0 |
October | 38446277.36 | 2147.01 | 27-OCT-04:01 | -17.7 | -18.2 | 0.00 | 0.00 | 01-OCT-00:10 | -17.7 | -18.2 |
November | 6437961.30 | 2758.36 | 30-NOV-05:01 | -27.8 | -28.0 | 0.00 | 0.00 | 01-NOV-00:10 | -27.8 | -28.0 |
December | 10090055.39 | 3097.04 | 22-DEC-05:01 | -28.2 | -28.4 | 0.00 | 0.00 | 01-DEC-00:10 | -28.2 | -28.4 |
Annual Sum or Average | 0.118538E+11 | 0.00 | ||||||||
Minimum of Months | 6392584.94 | 1339.92 | -28.2 | -28.4 | 0.00 | 0.00 | -28.2 | -28.4 | ||
Maximum of Months | 0.356316E+10 | 4982.83 | 27.75 | 17.00 | 0.00 | 0.00 | 27.75 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.329225E+09 | 5956.14 | 12-JAN-17:09 | -35.8 | -35.9 | 0.00 | 0.00 | 01-JAN-00:10 | -35.8 | -35.9 |
February | 0.249137E+09 | 4594.25 | 17-FEB-07:09 | -23.3 | -23.5 | 0.00 | 0.00 | 01-FEB-00:10 | -23.3 | -23.5 |
March | 0.352966E+09 | 5835.91 | 31-MAR-06:09 | -25.6 | -26.1 | 0.00 | 0.00 | 01-MAR-00:10 | -25.6 | -26.1 |
April | 0.735022E+09 | 3723.92 | 13-APR-06:09 | -7.4 | -8.5 | 0.00 | 0.00 | 01-APR-00:10 | -7.4 | -8.5 |
May | 0.250842E+10 | 3644.65 | 31-MAY-16:00 | 22.20 | 10.79 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 10.79 |
June | 0.405299E+10 | 4733.66 | 22-JUN-06:15 | 15.57 | 11.82 | 0.00 | 0.00 | 01-JUN-00:10 | 15.57 | 11.82 |
July | 0.409787E+10 | 5810.91 | 24-JUL-06:13 | 14.47 | 13.19 | 0.00 | 0.00 | 01-JUL-00:10 | 14.47 | 13.19 |
August | 0.334327E+10 | 4671.51 | 11-AUG-16:00 | 25.60 | 14.77 | 0.00 | 0.00 | 01-AUG-00:10 | 25.60 | 14.77 |
September | 0.961800E+09 | 3206.71 | 15-SEP-06:08 | -0.5 | -0.7 | 0.00 | 0.00 | 01-SEP-00:10 | -0.5 | -0.7 |
October | 0.251111E+09 | 3756.55 | 27-OCT-06:09 | -18.4 | -18.8 | 0.00 | 0.00 | 01-OCT-00:10 | -18.4 | -18.8 |
November | 0.365208E+09 | 4724.49 | 09-NOV-07:09 | -26.7 | -26.9 | 0.00 | 0.00 | 01-NOV-00:10 | -26.7 | -26.9 |
December | 0.384944E+09 | 4988.94 | 15-DEC-07:09 | -33.4 | -33.5 | 0.00 | 0.00 | 01-DEC-00:10 | -33.4 | -33.5 |
Annual Sum or Average | 0.176320E+11 | 0.00 | ||||||||
Minimum of Months | 0.249137E+09 | 3206.71 | -35.8 | -35.9 | 0.00 | 0.00 | -35.8 | -35.9 | ||
Maximum of Months | 0.409787E+10 | 5956.14 | 25.60 | 14.77 | 0.00 | 0.00 | 25.60 | 14.77 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303165E+10 | 5585.41 | 20-JAN-17:00 | -11.1 | -11.2 | 0.146281E+10 | 2041.73 | 20-JAN-14:00 | -11.1 | -11.2 |
February | 0.413130E+10 | 6324.58 | 09-FEB-14:50 | -0.1 | -1.1 | 0.136120E+10 | 2230.14 | 09-FEB-14:00 | 0.00 | -1.0 |
March | 0.668099E+10 | 6988.85 | 22-MAR-15:40 | 5.60 | 2.48 | 0.170617E+10 | 2354.53 | 23-MAR-13:00 | -1.7 | -4.1 |
April | 0.940562E+10 | 12464.11 | 21-APR-16:00 | 14.40 | 5.45 | 0.173532E+10 | 2606.91 | 24-APR-09:39 | 1.33 | -3.0 |
May | 0.156591E+11 | 31377.56 | 15-MAY-05:02 | 6.88 | 1.81 | 0.206011E+10 | 2606.64 | 16-MAY-09:09 | 5.97 | 4.63 |
June | 0.190491E+11 | 32224.05 | 12-JUN-04:02 | 7.38 | 5.98 | 0.206645E+10 | 2606.65 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.185044E+11 | 34042.66 | 24-JUL-04:02 | 12.80 | 12.43 | 0.192082E+10 | 2606.93 | 19-JUL-09:09 | 12.80 | 12.43 |
August | 0.173827E+11 | 32816.93 | 14-AUG-04:02 | 11.60 | 10.40 | 0.215183E+10 | 2606.64 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.105055E+11 | 12747.77 | 01-SEP-16:00 | 15.60 | 10.82 | 0.182539E+10 | 2607.99 | 21-SEP-13:30 | 6.40 | 5.35 |
October | 0.682081E+10 | 7475.89 | 05-OCT-16:00 | 11.10 | 5.87 | 0.162379E+10 | 2507.39 | 04-OCT-13:00 | 11.10 | 5.87 |
November | 0.369032E+10 | 5783.15 | 02-NOV-16:00 | -8.9 | -9.4 | 0.146365E+10 | 2087.91 | 02-NOV-13:00 | -8.9 | -9.4 |
December | 0.289630E+10 | 5353.94 | 21-DEC-17:00 | -16.7 | -17.3 | 0.140685E+10 | 1987.72 | 21-DEC-14:00 | -16.7 | -17.3 |
Annual Sum or Average | 0.117758E+12 | 0.207844E+11 | ||||||||
Minimum of Months | 0.289630E+10 | 5353.94 | -16.7 | -17.3 | 0.136120E+10 | 1987.72 | -16.7 | -17.3 | ||
Maximum of Months | 0.190491E+11 | 34042.66 | 15.60 | 12.43 | 0.215183E+10 | 2607.99 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113682E+10 | 4938.98 | 07-JAN-17:02 | -9.0 | -9.0 | 0.144898E+10 | 1929.03 | 30-JAN-10:39 | -25.2 | -25.6 |
February | 0.209216E+10 | 6009.32 | 09-FEB-15:50 | 0.50 | -0.6 | 0.132379E+10 | 2123.20 | 09-FEB-14:00 | 0.50 | -0.6 |
March | 0.452784E+10 | 6968.10 | 22-MAR-16:00 | 5.60 | 2.61 | 0.162402E+10 | 2278.48 | 22-MAR-15:00 | 5.60 | 2.61 |
April | 0.796943E+10 | 12069.51 | 21-APR-16:00 | 14.40 | 5.45 | 0.163251E+10 | 2606.54 | 27-APR-13:00 | 11.10 | 4.54 |
May | 0.142874E+11 | 16762.14 | 31-MAY-16:00 | 22.20 | 10.79 | 0.203103E+10 | 2606.64 | 19-MAY-13:50 | 22.20 | 10.79 |
June | 0.183977E+11 | 23128.59 | 23-JUN-05:03 | 14.82 | 10.54 | 0.206076E+10 | 2606.62 | 27-JUN-09:09 | 13.90 | 13.18 |
July | 0.176861E+11 | 32582.66 | 24-JUL-04:02 | 12.80 | 12.43 | 0.191558E+10 | 2606.87 | 19-JUL-09:09 | 12.80 | 12.43 |
August | 0.157113E+11 | 28320.28 | 03-AUG-05:03 | 14.90 | 13.04 | 0.213115E+10 | 2606.63 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.871440E+10 | 11503.64 | 01-SEP-16:00 | 15.60 | 10.82 | 0.170062E+10 | 2606.62 | 08-SEP-13:20 | 11.47 | 7.77 |
October | 0.444258E+10 | 7110.21 | 03-OCT-16:00 | 11.70 | 6.37 | 0.151844E+10 | 2367.90 | 04-OCT-13:00 | 11.10 | 4.80 |
November | 0.141143E+10 | 5150.60 | 08-NOV-15:50 | -15.7 | -16.1 | 0.143621E+10 | 1931.37 | 08-NOV-14:00 | -15.7 | -16.1 |
December | 0.104014E+10 | 4923.27 | 02-DEC-17:01 | -21.7 | -22.0 | 0.139776E+10 | 1928.96 | 04-DEC-10:50 | -21.2 | -21.6 |
Annual Sum or Average | 0.974173E+11 | 0.202209E+11 | ||||||||
Minimum of Months | 0.104014E+10 | 4923.27 | -21.7 | -22.0 | 0.132379E+10 | 1928.96 | -25.2 | -25.6 | ||
Maximum of Months | 0.183977E+11 | 32582.66 | 22.20 | 13.04 | 0.213115E+10 | 2606.87 | 22.20 | 13.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6960624.27 | 1117.94 | 07-JAN-17:02 | -9.0 | -9.0 | 0.301841E+09 | 406.72 | 03-JAN-14:00 | -9.0 | -9.0 |
February | 8355165.35 | 1133.43 | 11-FEB-17:02 | -1.2 | -2.7 | 0.274651E+09 | 406.71 | 27-FEB-14:39 | -28.5 | -28.7 |
March | 79816232.79 | 1404.49 | 22-MAR-15:50 | 5.60 | 2.55 | 0.331296E+09 | 431.61 | 22-MAR-13:00 | 5.60 | 2.55 |
April | 0.113817E+10 | 2141.83 | 28-APR-15:20 | 12.20 | 4.90 | 0.317290E+09 | 546.93 | 28-APR-13:00 | 12.20 | 4.90 |
May | 0.323633E+10 | 9640.81 | 31-MAY-06:02 | 14.08 | 8.75 | 0.418907E+09 | 549.50 | 19-MAY-13:50 | 14.08 | 8.75 |
June | 0.545505E+10 | 10065.50 | 13-JUN-06:02 | 13.27 | 9.79 | 0.434546E+09 | 549.50 | 28-JUN-13:00 | 17.80 | 14.79 |
July | 0.510183E+10 | 10109.73 | 11-JUL-06:02 | 16.38 | 12.49 | 0.403495E+09 | 549.54 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.362765E+10 | 4998.75 | 02-AUG-15:30 | 22.75 | 14.69 | 0.438664E+09 | 549.49 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.137670E+10 | 2214.02 | 01-SEP-16:00 | 15.60 | 10.82 | 0.325245E+09 | 549.47 | 01-SEP-13:00 | 15.60 | 10.82 |
October | 0.180426E+09 | 1421.10 | 04-OCT-15:40 | 10.37 | 4.66 | 0.306800E+09 | 440.18 | 04-OCT-13:00 | 10.37 | 4.66 |
November | 6891177.94 | 1115.09 | 18-NOV-17:02 | -13.0 | -13.3 | 0.299946E+09 | 406.71 | 17-NOV-10:09 | -13.0 | -13.3 |
December | 9297198.93 | 1113.81 | 23-DEC-17:02 | -2.6 | -3.4 | 0.291514E+09 | 406.77 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.202275E+11 | 0.414419E+10 | ||||||||
Minimum of Months | 6891177.94 | 1113.81 | -13.0 | -13.3 | 0.274651E+09 | 406.71 | -28.5 | -28.7 | ||
Maximum of Months | 0.545505E+10 | 10109.73 | 22.75 | 14.69 | 0.438664E+09 | 549.54 | 17.80 | 14.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9406322.06 | 1013.97 | 07-JAN-17:02 | -9.0 | -9.0 | 0.192691E+09 | 257.50 | 03-JAN-14:00 | -9.0 | -9.0 |
February | 21441320.43 | 1029.78 | 11-FEB-17:02 | -1.2 | -2.7 | 0.175069E+09 | 257.49 | 27-FEB-14:39 | -28.5 | -28.7 |
March | 0.474444E+09 | 1959.38 | 22-MAR-10:30 | 2.25 | 0.43 | 0.216650E+09 | 346.19 | 22-MAR-09:00 | 2.25 | 0.43 |
April | 0.172921E+10 | 5736.04 | 22-APR-09:25 | 9.15 | 3.96 | 0.221658E+09 | 347.88 | 13-APR-09:00 | 9.15 | 3.96 |
May | 0.490744E+10 | 15918.05 | 14-MAY-09:41 | 15.92 | 8.37 | 0.272734E+09 | 348.80 | 12-MAY-09:09 | 15.92 | 8.37 |
June | 0.589155E+10 | 11847.98 | 13-JUN-06:02 | 13.27 | 9.79 | 0.275052E+09 | 348.49 | 08-JUN-09:39 | 13.27 | 9.79 |
July | 0.582165E+10 | 16619.50 | 23-JUL-09:41 | 20.63 | 14.69 | 0.255456E+09 | 348.66 | 07-JUL-09:50 | 20.63 | 14.69 |
August | 0.441748E+10 | 10897.66 | 11-AUG-06:02 | 10.97 | 7.10 | 0.283834E+09 | 348.27 | 10-AUG-09:00 | 10.97 | 7.10 |
September | 0.162519E+10 | 6337.96 | 10-SEP-09:53 | 12.80 | 7.13 | 0.216111E+09 | 347.88 | 08-SEP-13:09 | 12.80 | 7.13 |
October | 0.315824E+09 | 1719.80 | 03-OCT-10:15 | 4.63 | 3.18 | 0.196964E+09 | 343.49 | 03-OCT-09:00 | 4.63 | 3.18 |
November | 8972191.50 | 1013.12 | 18-NOV-17:02 | -13.0 | -13.3 | 0.190915E+09 | 257.49 | 27-NOV-14:30 | -23.9 | -24.2 |
December | 11606677.93 | 1009.99 | 30-DEC-17:02 | -10.0 | -10.4 | 0.185809E+09 | 257.53 | 27-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.252342E+11 | 0.268294E+10 | ||||||||
Minimum of Months | 8972191.50 | 1009.99 | -13.0 | -13.3 | 0.175069E+09 | 257.49 | -28.5 | -28.7 | ||
Maximum of Months | 0.589155E+10 | 16619.50 | 20.63 | 14.69 | 0.283834E+09 | 348.80 | 20.63 | 14.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 41752586.28 | 1830.11 | 25-JAN-13:30 | -19.8 | -20.0 | 0.304449E+09 | 408.00 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.444916E+09 | 4052.75 | 15-FEB-13:50 | -8.5 | -9.4 | 0.284368E+09 | 549.49 | 15-FEB-14:00 | -7.2 | -8.6 |
March | 0.174863E+10 | 8091.30 | 31-MAR-14:00 | -11.1 | -13.1 | 0.367000E+09 | 550.40 | 31-MAR-13:09 | -11.1 | -13.1 |
April | 0.453313E+10 | 13839.25 | 20-APR-14:00 | 14.40 | 6.23 | 0.355233E+09 | 549.49 | 26-APR-13:00 | 10.60 | 4.23 |
May | 0.708944E+10 | 24544.48 | 14-MAY-12:22 | 18.35 | 9.42 | 0.416466E+09 | 549.62 | 12-MAY-13:39 | 18.35 | 9.42 |
June | 0.841404E+10 | 18143.94 | 04-JUN-13:43 | 18.98 | 11.96 | 0.429554E+09 | 549.50 | 28-JUN-13:00 | 17.80 | 14.79 |
July | 0.837807E+10 | 26463.44 | 23-JUL-12:21 | 24.45 | 15.55 | 0.398834E+09 | 549.99 | 12-JUL-13:00 | 24.45 | 15.55 |
August | 0.775041E+10 | 22678.37 | 27-AUG-13:12 | 18.33 | 13.81 | 0.438334E+09 | 549.84 | 25-AUG-13:00 | 18.33 | 13.81 |
September | 0.358961E+10 | 10884.88 | 07-SEP-14:30 | 15.85 | 8.58 | 0.345648E+09 | 549.52 | 08-SEP-13:09 | 11.28 | 7.64 |
October | 0.108707E+10 | 9307.74 | 03-OCT-13:30 | 10.85 | 6.24 | 0.322650E+09 | 549.49 | 13-OCT-13:00 | 1.10 | -2.4 |
November | 0.117580E+09 | 2539.77 | 08-NOV-14:00 | -13.3 | -14.1 | 0.302876E+09 | 514.90 | 08-NOV-14:09 | -13.4 | -14.2 |
December | 19514460.55 | 1620.17 | 30-DEC-17:02 | -10.0 | -10.4 | 0.293529E+09 | 406.76 | 22-DEC-10:50 | -10.0 | -10.4 |
Annual Sum or Average | 0.432142E+11 | 0.425894E+10 | ||||||||
Minimum of Months | 19514460.55 | 1620.17 | -19.8 | -20.0 | 0.284368E+09 | 406.76 | -18.9 | -19.2 | ||
Maximum of Months | 0.841404E+10 | 26463.44 | 24.45 | 15.55 | 0.438334E+09 | 550.40 | 24.45 | 15.55 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9886633.12 | 1066.67 | 07-JAN-17:02 | -9.0 | -9.0 | 0.192677E+09 | 257.48 | 03-JAN-14:00 | -9.0 | -9.0 |
February | 20285238.40 | 1082.63 | 11-FEB-17:02 | -1.2 | -2.7 | 0.175040E+09 | 257.47 | 27-FEB-14:39 | -28.5 | -28.7 |
March | 0.240992E+09 | 1598.12 | 22-MAR-15:40 | 5.60 | 2.48 | 0.211479E+09 | 304.33 | 22-MAR-15:50 | 5.60 | 2.55 |
April | 0.181558E+10 | 7081.20 | 21-APR-17:50 | 14.40 | 5.94 | 0.205072E+09 | 345.00 | 28-APR-13:00 | 11.70 | 4.88 |
May | 0.341547E+10 | 15418.46 | 14-MAY-18:22 | 16.70 | 9.19 | 0.255647E+09 | 347.85 | 19-MAY-13:00 | 13.30 | 8.13 |
June | 0.490062E+10 | 14138.49 | 10-JUN-17:05 | 21.20 | 10.81 | 0.271333E+09 | 347.85 | 28-JUN-13:00 | 17.80 | 14.79 |
July | 0.445468E+10 | 11242.77 | 23-JUL-15:42 | 25.60 | 14.89 | 0.251371E+09 | 347.86 | 21-JUL-13:50 | 25.60 | 14.89 |
August | 0.362312E+10 | 9561.13 | 27-AUG-17:12 | 20.93 | 12.63 | 0.270624E+09 | 347.84 | 01-AUG-09:00 | 20.93 | 12.63 |
September | 0.140863E+10 | 4694.96 | 02-SEP-17:15 | 16.70 | 10.26 | 0.203794E+09 | 341.20 | 01-SEP-13:00 | 16.70 | 10.26 |
October | 0.202225E+09 | 1592.15 | 03-OCT-15:10 | 12.62 | 6.83 | 0.194522E+09 | 305.24 | 03-OCT-15:20 | 12.43 | 6.74 |
November | 9976186.27 | 1070.19 | 18-NOV-17:02 | -13.0 | -13.3 | 0.190906E+09 | 257.47 | 17-NOV-10:09 | -13.0 | -13.3 |
December | 12479741.73 | 1063.43 | 30-DEC-17:02 | -10.0 | -10.4 | 0.185795E+09 | 257.50 | 27-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.201140E+11 | 0.260826E+10 | ||||||||
Minimum of Months | 9886633.12 | 1063.43 | -13.0 | -13.3 | 0.175040E+09 | 257.47 | -28.5 | -28.7 | ||
Maximum of Months | 0.490062E+10 | 15418.46 | 25.60 | 14.89 | 0.271333E+09 | 347.86 | 25.60 | 14.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10219816.06 | 1014.30 | 07-JAN-17:02 | -9.0 | -9.0 | 0.297896E+09 | 406.72 | 03-JAN-14:00 | -9.0 | -9.0 |
February | 8184495.59 | 1022.70 | 11-FEB-17:02 | -1.2 | -2.7 | 0.271535E+09 | 406.69 | 23-FEB-14:30 | -18.0 | -18.6 |
March | 39111875.16 | 1095.53 | 22-MAR-15:20 | 5.60 | 2.35 | 0.330938E+09 | 406.68 | 03-MAR-14:09 | 5.60 | 2.35 |
April | 0.911641E+09 | 1532.35 | 28-APR-15:40 | 12.20 | 5.02 | 0.309841E+09 | 503.30 | 28-APR-13:00 | 12.20 | 5.02 |
May | 0.250706E+10 | 2975.57 | 31-MAY-14:30 | 20.55 | 10.45 | 0.414217E+09 | 549.49 | 19-MAY-13:00 | 20.55 | 10.45 |
June | 0.425281E+10 | 8282.36 | 07-JUN-04:02 | 5.87 | 4.55 | 0.434441E+09 | 549.50 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.439143E+10 | 8413.68 | 11-JUL-04:02 | 12.25 | 10.71 | 0.404180E+09 | 549.54 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.346831E+10 | 5137.00 | 02-AUG-06:02 | 11.28 | 10.30 | 0.447141E+09 | 549.49 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.173471E+10 | 1920.86 | 01-SEP-16:00 | 15.60 | 10.82 | 0.349273E+09 | 549.47 | 01-SEP-13:00 | 15.60 | 10.82 |
October | 0.440116E+09 | 1375.53 | 06-OCT-15:00 | 10.60 | 4.90 | 0.312234E+09 | 469.12 | 06-OCT-13:00 | 10.60 | 4.90 |
November | 8942209.07 | 1021.00 | 18-NOV-17:02 | -13.0 | -13.3 | 0.300368E+09 | 406.70 | 30-NOV-14:39 | -25.7 | -26.0 |
December | 19863978.09 | 1012.93 | 30-DEC-17:02 | -10.0 | -10.4 | 0.290682E+09 | 406.74 | 27-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.177924E+11 | 0.416275E+10 | ||||||||
Minimum of Months | 8184495.59 | 1012.93 | -13.0 | -13.3 | 0.271535E+09 | 406.68 | -25.7 | -26.0 | ||
Maximum of Months | 0.439143E+10 | 8413.68 | 20.55 | 10.82 | 0.447141E+09 | 549.54 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9996900.93 | 838.87 | 07-JAN-17:02 | -9.0 | -9.0 | 0.192894E+09 | 257.50 | 03-JAN-14:00 | -9.0 | -9.0 |
February | 16694322.01 | 848.07 | 11-FEB-17:02 | -1.2 | -2.7 | 0.175246E+09 | 257.49 | 27-FEB-14:30 | -28.6 | -28.8 |
March | 0.353635E+09 | 1394.43 | 31-MAR-09:30 | -17.0 | -18.1 | 0.215722E+09 | 343.62 | 31-MAR-09:39 | -16.7 | -17.8 |
April | 0.141228E+10 | 3989.87 | 22-APR-08:30 | 6.65 | 2.48 | 0.222783E+09 | 348.08 | 19-APR-09:20 | 6.65 | 2.48 |
May | 0.410528E+10 | 9298.25 | 31-MAY-06:02 | 14.08 | 8.75 | 0.274675E+09 | 347.88 | 19-MAY-09:09 | 14.08 | 8.75 |
June | 0.502991E+10 | 9589.56 | 13-JUN-06:02 | 13.27 | 9.79 | 0.275467E+09 | 348.10 | 08-JUN-09:30 | 13.27 | 9.79 |
July | 0.528311E+10 | 10187.61 | 23-JUL-10:32 | 22.23 | 15.22 | 0.256627E+09 | 348.47 | 07-JUL-09:00 | 22.23 | 15.22 |
August | 0.436622E+10 | 9385.58 | 11-AUG-06:02 | 10.97 | 7.10 | 0.286974E+09 | 348.19 | 11-AUG-09:09 | 16.97 | 10.66 |
September | 0.188659E+10 | 6739.39 | 10-SEP-09:53 | 12.80 | 7.13 | 0.234667E+09 | 347.88 | 08-SEP-13:09 | 12.80 | 7.13 |
October | 0.568947E+09 | 2100.19 | 03-OCT-09:35 | 2.97 | 2.01 | 0.203087E+09 | 347.87 | 03-OCT-09:00 | 3.90 | 2.68 |
November | 8530990.27 | 845.97 | 18-NOV-17:02 | -13.0 | -13.3 | 0.191262E+09 | 257.49 | 28-NOV-14:30 | -25.3 | -25.6 |
December | 14339019.79 | 837.89 | 30-DEC-17:02 | -10.0 | -10.4 | 0.186034E+09 | 257.52 | 27-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.230555E+11 | 0.271544E+10 | ||||||||
Minimum of Months | 8530990.27 | 837.89 | -17.0 | -18.1 | 0.175246E+09 | 257.49 | -28.6 | -28.8 | ||
Maximum of Months | 0.528311E+10 | 10187.61 | 22.23 | 15.22 | 0.286974E+09 | 348.47 | 22.23 | 15.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14154802.55 | 1332.10 | 28-JAN-17:01 | -21.8 | -22.5 | 0.236924E+09 | 406.61 | 19-JAN-10:09 | -21.8 | -22.5 |
February | 83770657.74 | 1613.45 | 18-FEB-13:00 | -15.0 | -16.3 | 0.238501E+09 | 406.61 | 07-FEB-10:09 | -15.0 | -16.3 |
March | 0.202320E+09 | 1967.60 | 11-MAR-13:50 | -3.8 | -5.8 | 0.304854E+09 | 454.69 | 22-MAR-14:50 | 5.60 | 2.17 |
April | 0.186365E+10 | 8272.41 | 22-APR-14:00 | 15.60 | 7.03 | 0.323000E+09 | 549.50 | 13-APR-13:00 | 15.60 | 7.03 |
May | 0.378742E+10 | 9197.24 | 12-MAY-13:30 | 20.60 | 9.86 | 0.394587E+09 | 549.51 | 19-MAY-13:00 | 13.30 | 8.13 |
June | 0.542751E+10 | 11505.79 | 04-JUN-14:52 | 19.40 | 11.69 | 0.417746E+09 | 549.54 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.628655E+10 | 18953.76 | 23-JUL-13:52 | 25.00 | 15.26 | 0.392400E+09 | 549.53 | 21-JUL-13:30 | 25.00 | 15.26 |
August | 0.560494E+10 | 15704.22 | 27-AUG-15:12 | 20.93 | 12.89 | 0.428227E+09 | 549.66 | 11-AUG-13:30 | 20.93 | 12.89 |
September | 0.235205E+10 | 10144.44 | 10-SEP-11:53 | 15.60 | 8.34 | 0.331645E+09 | 549.52 | 08-SEP-13:09 | 15.60 | 8.34 |
October | 0.504502E+09 | 4961.62 | 03-OCT-13:50 | 11.42 | 6.47 | 0.297106E+09 | 549.50 | 03-OCT-13:09 | 11.42 | 6.47 |
November | 19238752.33 | 1343.97 | 18-NOV-17:02 | -13.0 | -13.3 | 0.249286E+09 | 406.59 | 01-NOV-09:09 | -13.0 | -13.3 |
December | 13647519.59 | 1318.07 | 30-DEC-17:02 | -10.0 | -10.4 | 0.216459E+09 | 406.59 | 21-DEC-10:20 | -10.0 | -10.4 |
Annual Sum or Average | 0.261598E+11 | 0.383073E+10 | ||||||||
Minimum of Months | 13647519.59 | 1318.07 | -21.8 | -22.5 | 0.216459E+09 | 406.59 | -21.8 | -22.5 | ||
Maximum of Months | 0.628655E+10 | 18953.76 | 25.00 | 15.26 | 0.428227E+09 | 549.66 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10856831.18 | 895.17 | 07-JAN-17:02 | -9.0 | -9.0 | 0.192881E+09 | 257.48 | 03-JAN-14:00 | -9.0 | -9.0 |
February | 10532296.76 | 903.38 | 11-FEB-17:02 | -1.2 | -2.7 | 0.175181E+09 | 257.47 | 27-FEB-14:30 | -28.6 | -28.8 |
March | 0.129555E+09 | 1215.35 | 31-MAR-17:00 | -9.4 | -11.7 | 0.210759E+09 | 273.05 | 22-MAR-15:00 | -9.4 | -11.7 |
April | 0.144322E+10 | 5526.80 | 21-APR-18:20 | 14.03 | 5.87 | 0.206817E+09 | 338.68 | 28-APR-15:00 | 12.20 | 5.13 |
May | 0.262256E+10 | 10280.85 | 14-MAY-19:02 | 16.52 | 8.80 | 0.260025E+09 | 347.85 | 19-MAY-13:00 | 13.30 | 8.13 |
June | 0.396527E+10 | 7739.39 | 10-JUN-17:08 | 21.20 | 10.81 | 0.273705E+09 | 347.86 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.382680E+10 | 8717.28 | 09-JUL-19:53 | 19.40 | 13.11 | 0.254697E+09 | 347.86 | 19-JUL-09:30 | 17.75 | 14.39 |
August | 0.340018E+10 | 6695.99 | 27-AUG-17:53 | 20.60 | 12.18 | 0.282202E+09 | 347.85 | 25-AUG-13:00 | 20.60 | 12.18 |
September | 0.165451E+10 | 4228.52 | 02-SEP-17:15 | 16.70 | 10.26 | 0.220047E+09 | 347.84 | 01-SEP-13:00 | 16.70 | 10.26 |
October | 0.386740E+09 | 1359.30 | 03-OCT-15:20 | 12.43 | 6.74 | 0.197448E+09 | 311.20 | 03-OCT-15:30 | 12.25 | 6.65 |
November | 9982168.65 | 905.39 | 18-NOV-17:02 | -13.0 | -13.3 | 0.191249E+09 | 257.47 | 27-NOV-14:50 | -23.9 | -24.2 |
December | 15353941.48 | 894.75 | 30-DEC-17:02 | -10.0 | -10.4 | 0.186019E+09 | 257.50 | 27-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.174756E+11 | 0.265103E+10 | ||||||||
Minimum of Months | 9982168.65 | 894.75 | -13.0 | -13.3 | 0.175181E+09 | 257.47 | -28.6 | -28.8 | ||
Maximum of Months | 0.396527E+10 | 10280.85 | 21.20 | 13.11 | 0.282202E+09 | 347.86 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8446246.15 | 986.65 | 21-JAN-17:02 | -5.5 | -5.8 | 0.303443E+09 | 406.72 | 03-JAN-14:00 | -5.5 | -5.8 |
February | 15116884.97 | 999.71 | 11-FEB-17:02 | -1.2 | -2.7 | 0.275960E+09 | 406.71 | 27-FEB-14:39 | -28.5 | -28.7 |
March | 0.184344E+09 | 1295.53 | 22-MAR-15:40 | 5.60 | 2.48 | 0.333388E+09 | 454.10 | 22-MAR-13:00 | 5.60 | 2.48 |
April | 0.136463E+10 | 2492.42 | 28-APR-15:20 | 12.20 | 4.90 | 0.333879E+09 | 549.48 | 27-APR-13:00 | 12.20 | 4.90 |
May | 0.348204E+10 | 8510.52 | 31-MAY-06:02 | 14.08 | 8.75 | 0.431012E+09 | 549.50 | 19-MAY-13:50 | 14.08 | 8.75 |
June | 0.565614E+10 | 9741.23 | 07-JUN-04:02 | 5.87 | 4.55 | 0.435782E+09 | 549.51 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.527459E+10 | 9538.41 | 11-JUL-04:02 | 12.25 | 10.71 | 0.405163E+09 | 549.56 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.389294E+10 | 8017.69 | 02-AUG-06:02 | 11.28 | 10.30 | 0.449015E+09 | 549.49 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.168262E+10 | 2666.46 | 01-SEP-13:50 | 14.82 | 10.69 | 0.352534E+09 | 549.48 | 01-SEP-13:00 | 15.00 | 10.77 |
October | 0.397812E+09 | 1382.97 | 04-OCT-15:40 | 10.37 | 4.66 | 0.312311E+09 | 478.05 | 04-OCT-13:00 | 10.37 | 4.66 |
November | 7536813.49 | 984.55 | 18-NOV-17:02 | -13.0 | -13.3 | 0.301286E+09 | 406.71 | 17-NOV-10:00 | -13.0 | -13.3 |
December | 10218347.00 | 1001.37 | 30-DEC-17:02 | -10.0 | -10.4 | 0.293097E+09 | 406.76 | 27-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.219764E+11 | 0.422687E+10 | ||||||||
Minimum of Months | 7536813.49 | 984.55 | -13.0 | -13.3 | 0.275960E+09 | 406.71 | -28.5 | -28.7 | ||
Maximum of Months | 0.565614E+10 | 9741.23 | 14.82 | 10.71 | 0.449015E+09 | 549.56 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11126599.98 | 1023.73 | 21-JAN-17:02 | -5.5 | -5.8 | 0.141830E+09 | 250.71 | 10-JAN-16:00 | -5.5 | -5.8 |
February | 52676188.36 | 1154.64 | 09-FEB-11:35 | -2.2 | -2.5 | 0.128960E+09 | 257.25 | 09-FEB-11:50 | -2.0 | -2.3 |
March | 0.663251E+09 | 2634.48 | 31-MAR-10:10 | -15.9 | -17.2 | 0.161319E+09 | 338.72 | 31-MAR-10:20 | -15.7 | -17.0 |
April | 0.208856E+10 | 6486.83 | 22-APR-09:20 | 8.87 | 3.75 | 0.166361E+09 | 339.30 | 13-APR-08:50 | 8.87 | 3.75 |
May | 0.518483E+10 | 14293.24 | 14-MAY-09:12 | 15.37 | 8.02 | 0.202518E+09 | 339.05 | 12-MAY-10:20 | 15.37 | 8.02 |
June | 0.590444E+10 | 11405.60 | 13-JUN-06:02 | 13.27 | 9.79 | 0.203437E+09 | 339.71 | 12-JUN-10:30 | 13.27 | 9.79 |
July | 0.582410E+10 | 14830.07 | 09-JUL-07:02 | 15.18 | 12.43 | 0.189859E+09 | 339.73 | 31-JUL-10:30 | 18.85 | 11.80 |
August | 0.463912E+10 | 11119.16 | 11-AUG-06:02 | 10.97 | 7.10 | 0.210566E+09 | 339.54 | 10-AUG-10:30 | 10.97 | 7.10 |
September | 0.204179E+10 | 5350.83 | 10-SEP-09:23 | 11.95 | 6.71 | 0.166633E+09 | 339.02 | 08-SEP-08:30 | 11.95 | 6.71 |
October | 0.532518E+09 | 2473.59 | 03-OCT-10:05 | 4.27 | 2.93 | 0.147258E+09 | 338.72 | 03-OCT-10:09 | 4.27 | 2.93 |
November | 10132457.70 | 1023.60 | 18-NOV-17:02 | -13.0 | -13.3 | 0.140505E+09 | 250.70 | 07-NOV-09:20 | -13.0 | -13.3 |
December | 12235458.49 | 1039.73 | 30-DEC-17:02 | -10.0 | -10.4 | 0.136756E+09 | 250.70 | 27-DEC-13:50 | -10.0 | -10.4 |
Annual Sum or Average | 0.269648E+11 | 0.199600E+10 | ||||||||
Minimum of Months | 10132457.70 | 1023.60 | -15.9 | -17.2 | 0.128960E+09 | 250.70 | -15.7 | -17.0 | ||
Maximum of Months | 0.590444E+10 | 14830.07 | 15.37 | 12.43 | 0.210566E+09 | 339.73 | 18.85 | 11.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 88236877.39 | 1972.39 | 25-JAN-13:30 | -19.8 | -20.0 | 0.305204E+09 | 444.29 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.628881E+09 | 4869.72 | 15-FEB-13:40 | -8.7 | -9.6 | 0.288605E+09 | 549.49 | 09-FEB-14:00 | -8.7 | -9.6 |
March | 0.214708E+10 | 9085.87 | 31-MAR-13:30 | -11.4 | -13.3 | 0.374125E+09 | 549.49 | 30-MAR-13:00 | -11.4 | -13.3 |
April | 0.512209E+10 | 13628.00 | 20-APR-14:10 | 14.32 | 6.25 | 0.364631E+09 | 550.22 | 07-APR-13:00 | 14.32 | 6.25 |
May | 0.739974E+10 | 20304.72 | 14-MAY-12:32 | 18.53 | 9.40 | 0.426213E+09 | 550.35 | 12-MAY-13:50 | 18.53 | 9.40 |
June | 0.844228E+10 | 22189.74 | 18-JUN-12:22 | 16.40 | 11.93 | 0.433308E+09 | 549.58 | 29-JUN-13:00 | 25.60 | 16.24 |
July | 0.838000E+10 | 22879.32 | 23-JUL-13:12 | 25.00 | 15.26 | 0.403031E+09 | 550.00 | 12-JUL-13:00 | 25.00 | 15.26 |
August | 0.803172E+10 | 24366.23 | 27-AUG-13:01 | 18.07 | 13.70 | 0.447501E+09 | 549.83 | 25-AUG-13:00 | 18.07 | 13.70 |
September | 0.432213E+10 | 11178.25 | 09-SEP-13:30 | 13.35 | 8.71 | 0.363511E+09 | 549.52 | 08-SEP-13:09 | 13.35 | 8.71 |
October | 0.153440E+10 | 9957.10 | 03-OCT-13:30 | 10.85 | 6.24 | 0.330932E+09 | 549.49 | 04-OCT-13:20 | 11.50 | 5.03 |
November | 0.196093E+09 | 2769.59 | 08-NOV-13:50 | -13.4 | -14.2 | 0.304539E+09 | 549.49 | 08-NOV-14:09 | -13.4 | -14.2 |
December | 19076941.83 | 1585.49 | 30-DEC-17:02 | -10.0 | -10.4 | 0.293907E+09 | 406.73 | 22-DEC-10:50 | -10.0 | -10.4 |
Annual Sum or Average | 0.463117E+11 | 0.433551E+10 | ||||||||
Minimum of Months | 19076941.83 | 1585.49 | -19.8 | -20.0 | 0.288605E+09 | 406.73 | -18.9 | -19.2 | ||
Maximum of Months | 0.844228E+10 | 24366.23 | 25.00 | 15.26 | 0.447501E+09 | 550.35 | 25.60 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11186007.70 | 1023.96 | 07-JAN-17:02 | -9.0 | -9.0 | 0.192938E+09 | 257.47 | 03-JAN-14:00 | -9.0 | -9.0 |
February | 39942604.04 | 1038.95 | 11-FEB-17:02 | -1.2 | -2.7 | 0.175282E+09 | 257.47 | 27-FEB-14:39 | -28.5 | -28.7 |
March | 0.352496E+09 | 1612.75 | 31-MAR-17:00 | -9.4 | -11.7 | 0.212851E+09 | 315.07 | 31-MAR-15:00 | -9.4 | -11.7 |
April | 0.211402E+10 | 7387.84 | 22-APR-17:08 | 14.13 | 6.18 | 0.212302E+09 | 347.83 | 28-APR-13:00 | 11.70 | 4.88 |
May | 0.358987E+10 | 11937.54 | 28-MAY-17:12 | 16.70 | 8.41 | 0.265389E+09 | 347.85 | 19-MAY-13:00 | 16.70 | 8.41 |
June | 0.493460E+10 | 13372.17 | 10-JUN-17:05 | 21.20 | 10.81 | 0.274140E+09 | 347.86 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.449174E+10 | 9982.67 | 30-JUL-19:12 | 17.20 | 11.81 | 0.254600E+09 | 347.89 | 19-JUL-09:09 | 17.20 | 11.81 |
August | 0.377444E+10 | 15018.28 | 27-AUG-17:42 | 20.68 | 12.29 | 0.279421E+09 | 347.85 | 01-AUG-09:00 | 20.68 | 12.29 |
September | 0.181217E+10 | 5701.06 | 02-SEP-17:12 | 16.70 | 10.26 | 0.215940E+09 | 347.84 | 01-SEP-13:00 | 16.70 | 10.26 |
October | 0.391809E+09 | 1601.30 | 03-OCT-15:10 | 12.62 | 6.83 | 0.196963E+09 | 319.93 | 03-OCT-15:20 | 12.43 | 6.74 |
November | 12913717.53 | 1027.55 | 18-NOV-17:02 | -13.0 | -13.3 | 0.191131E+09 | 257.46 | 27-NOV-10:00 | -27.2 | -27.4 |
December | 12262801.50 | 1041.03 | 30-DEC-17:02 | -10.0 | -10.4 | 0.186017E+09 | 257.49 | 27-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.215375E+11 | 0.265697E+10 | ||||||||
Minimum of Months | 11186007.70 | 1023.96 | -13.0 | -13.3 | 0.175282E+09 | 257.46 | -28.5 | -28.7 | ||
Maximum of Months | 0.493460E+10 | 15018.28 | 21.20 | 12.29 | 0.279421E+09 | 347.89 | 25.00 | 15.96 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.851153E+09 | 24656.98 | 02-JAN-05:01 | -15.6 |
February | 0.169840E+09 | 21100.84 | 21-FEB-06:04 | -23.3 |
March | 13919487.17 | 19975.59 | 06-MAR-07:03 | -20.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 3361051.99 | 19656.67 | 30-OCT-06:02 | -15.1 |
November | 0.105264E+09 | 20262.11 | 28-NOV-06:01 | -27.4 |
December | 0.241553E+09 | 21314.69 | 27-DEC-06:01 | -20.8 |
Annual Sum or Average | 0.138509E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.4 | |
Maximum of Months | 0.851153E+09 | 24656.98 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149656E+11 | 20380.54 | 12-JAN-06:13 | -38.3 |
February | 0.112834E+11 | 20292.03 | 27-FEB-06:07 | -35.9 |
March | 0.832267E+10 | 18615.65 | 01-MAR-06:12 | -28.5 |
April | 0.280058E+10 | 17435.06 | 03-APR-05:13 | -21.3 |
May | 0.471510E+09 | 6001.99 | 21-MAY-07:32 | 8.50 |
June | 0.115314E+09 | 7149.98 | 23-JUN-05:03 | 14.82 |
July | 0.103224E+09 | 6152.60 | 24-JUL-04:02 | 12.80 |
August | 0.352986E+09 | 6726.68 | 01-AUG-05:02 | 10.00 |
September | 0.156337E+10 | 8287.05 | 28-SEP-06:01 | -2.8 |
October | 0.619273E+10 | 16869.07 | 27-OCT-05:12 | -17.6 |
November | 0.134940E+11 | 19336.50 | 28-NOV-06:12 | -27.6 |
December | 0.157972E+11 | 19441.61 | 15-DEC-06:13 | -33.0 |
Annual Sum or Average | 0.754626E+11 | |||
Minimum of Months | 0.103224E+09 | 6001.99 | -38.3 | |
Maximum of Months | 0.157972E+11 | 20380.54 | 14.82 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.599643E+10 | 12682.85 | 02-JAN-07:03 | -14.4 |
February | 0.430883E+10 | 11906.54 | 27-FEB-07:04 | -34.9 |
March | 0.328459E+10 | 9004.53 | 06-MAR-06:12 | -21.1 |
April | 0.122143E+10 | 6638.80 | 03-APR-06:02 | -21.5 |
May | 80748064.96 | 5186.47 | 21-MAY-13:42 | 15.40 |
June | 29999461.73 | 4243.85 | 08-JUN-04:02 | 8.30 |
July | 31685183.87 | 4902.34 | 23-JUL-11:12 | 23.17 |
August | 47692517.09 | 5203.38 | 27-AUG-15:42 | 20.68 |
September | 0.535527E+09 | 3710.69 | 17-SEP-11:43 | 13.22 |
October | 0.255266E+10 | 9312.42 | 30-OCT-06:02 | -15.1 |
November | 0.496275E+10 | 11565.48 | 27-NOV-07:03 | -26.7 |
December | 0.582017E+10 | 11557.23 | 04-DEC-07:03 | -19.4 |
Annual Sum or Average | 0.288725E+11 | |||
Minimum of Months | 29999461.73 | 3710.69 | -34.9 | |
Maximum of Months | 0.599643E+10 | 12682.85 | 23.17 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.458060E+10 | 10989.92 | 02-JAN-07:01 | -14.4 |
February | 0.326166E+10 | 7462.60 | 21-FEB-07:01 | -23.2 |
March | 0.228230E+10 | 5103.24 | 06-MAR-09:10 | -15.2 |
April | 0.636838E+09 | 6565.69 | 24-APR-05:02 | -3.4 |
May | 33547866.40 | 6099.46 | 30-MAY-05:02 | 7.57 |
June | 30881502.58 | 5363.01 | 07-JUN-04:02 | 5.87 |
July | 35384480.98 | 5555.27 | 11-JUL-04:02 | 12.25 |
August | 38146249.64 | 6151.46 | 30-AUG-05:02 | 0.00 |
September | 0.226641E+09 | 6317.98 | 05-SEP-05:02 | 5.00 |
October | 0.168897E+10 | 5439.86 | 30-OCT-06:01 | -15.1 |
November | 0.350810E+10 | 7529.76 | 13-NOV-07:01 | -17.1 |
December | 0.423483E+10 | 7845.40 | 04-DEC-07:01 | -19.4 |
Annual Sum or Average | 0.205579E+11 | |||
Minimum of Months | 30881502.58 | 5103.24 | -23.2 | |
Maximum of Months | 0.458060E+10 | 10989.92 | 12.25 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.327813E+10 | 28565.54 | 02-JAN-05:01 | -15.6 |
February | 0.167682E+10 | 27603.76 | 21-FEB-05:01 | -22.9 |
March | 0.413471E+09 | 25688.71 | 06-MAR-06:01 | -21.1 |
April | 56768004.79 | 24506.05 | 03-APR-05:01 | -21.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 180873.32 | 2713.10 | 25-SEP-06:01 | -1.8 |
October | 0.309863E+09 | 25698.34 | 30-OCT-05:01 | -14.5 |
November | 0.198432E+10 | 27502.42 | 13-NOV-05:01 | -20.2 |
December | 0.307531E+10 | 27657.91 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.107949E+11 | |||
Minimum of Months | 0.00 | 0.00 | -22.9 | |
Maximum of Months | 0.327813E+10 | 28565.54 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.947000E+10 | 31535.20 | 01-JAN-20:42 | -14.9 |
February | 0.585668E+10 | 31322.89 | 27-FEB-03:32 | -34.6 |
March | 0.296881E+10 | 30537.17 | 06-MAR-05:01 | -20.2 |
April | 0.593805E+09 | 29602.16 | 03-APR-04:11 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 78593702.66 | 26149.88 | 25-SEP-05:01 | -1.2 |
October | 0.218746E+10 | 30756.76 | 30-OCT-04:01 | -14.4 |
November | 0.744363E+10 | 31232.34 | 27-NOV-05:11 | -26.0 |
December | 0.950067E+10 | 31153.46 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.380997E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.6 | |
Maximum of Months | 0.950067E+10 | 31535.20 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116163E+11 | 11453.19 | 30-JAN-06:01 | -25.6 |
February | 0.862377E+10 | 11408.26 | 27-FEB-03:32 | -34.6 |
March | 0.596728E+10 | 10915.88 | 13-MAR-01:12 | -20.9 |
April | 0.149964E+10 | 10886.90 | 03-APR-00:12 | -16.9 |
May | 4650184.98 | 8210.74 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 7898676.05 | 8335.88 | 31-AUG-06:02 | -1.5 |
September | 0.425596E+09 | 9391.02 | 29-SEP-05:01 | -4.0 |
October | 0.424856E+10 | 10924.89 | 22-OCT-23:53 | -13.9 |
November | 0.996225E+10 | 11191.69 | 13-NOV-01:32 | -19.4 |
December | 0.118080E+11 | 11164.10 | 11-DEC-02:52 | -21.1 |
Annual Sum or Average | 0.541639E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.6 | |
Maximum of Months | 0.118080E+11 | 11453.19 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.771659E+10 | 13333.02 | 29-JAN-17:22 | -22.2 |
February | 0.512726E+10 | 13319.53 | 27-FEB-03:32 | -34.6 |
March | 0.269268E+10 | 12640.55 | 03-MAR-05:11 | -25.6 |
April | 0.649668E+09 | 12723.46 | 03-APR-04:11 | -21.1 |
May | 1117227.73 | 4873.87 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 2624317.17 | 8304.84 | 31-AUG-06:02 | -1.5 |
September | 0.187351E+09 | 10953.81 | 29-SEP-05:01 | -4.0 |
October | 0.234551E+10 | 12594.78 | 30-OCT-01:53 | -12.8 |
November | 0.655365E+10 | 13006.87 | 13-NOV-01:32 | -19.4 |
December | 0.796475E+10 | 12983.90 | 11-DEC-02:52 | -21.1 |
Annual Sum or Average | 0.332412E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.6 | |
Maximum of Months | 0.796475E+10 | 13333.02 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106602E+11 | 21163.98 | 01-JAN-19:22 | -14.4 |
February | 0.621307E+10 | 21155.19 | 26-FEB-07:32 | -25.6 |
March | 0.346645E+10 | 20057.10 | 03-MAR-05:11 | -25.6 |
April | 0.906974E+09 | 20101.68 | 03-APR-04:11 | -21.1 |
May | 8407465.16 | 8688.36 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 6087954.68 | 12655.62 | 30-AUG-06:02 | 0.10 |
September | 0.272259E+09 | 17422.01 | 25-SEP-05:01 | -1.2 |
October | 0.295199E+10 | 19931.54 | 31-OCT-04:01 | -17.9 |
November | 0.842378E+10 | 20668.67 | 13-NOV-01:32 | -19.4 |
December | 0.116003E+11 | 20663.81 | 11-DEC-02:52 | -21.1 |
Annual Sum or Average | 0.445095E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.6 | |
Maximum of Months | 0.116003E+11 | 21163.98 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.781180E+10 | 14010.62 | 29-JAN-14:02 | -21.7 |
February | 0.554154E+10 | 14000.88 | 26-FEB-07:32 | -25.6 |
March | 0.350202E+10 | 13289.01 | 03-MAR-05:11 | -25.6 |
April | 0.796031E+09 | 13291.45 | 03-APR-04:11 | -21.1 |
May | 7934659.81 | 5709.38 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 5466149.65 | 8188.78 | 30-AUG-06:02 | 0.10 |
September | 0.259504E+09 | 11477.82 | 25-SEP-05:01 | -1.2 |
October | 0.269702E+10 | 13179.82 | 31-OCT-04:01 | -17.9 |
November | 0.654278E+10 | 13650.67 | 13-NOV-01:32 | -19.4 |
December | 0.798045E+10 | 13628.23 | 11-DEC-02:52 | -21.1 |
Annual Sum or Average | 0.351445E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.6 | |
Maximum of Months | 0.798045E+10 | 14010.62 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.867826E+10 | 8704.82 | 01-JAN-19:22 | -14.4 |
February | 0.682243E+10 | 8508.95 | 20-FEB-07:02 | -25.0 |
March | 0.483364E+10 | 8190.66 | 02-MAR-05:11 | -26.7 |
April | 0.942282E+09 | 7992.40 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 36402172.19 | 6601.41 | 28-SEP-06:01 | -2.8 |
October | 0.169861E+10 | 8115.27 | 30-OCT-04:01 | -14.4 |
November | 0.614081E+10 | 8305.99 | 26-NOV-21:12 | -25.6 |
December | 0.813220E+10 | 8325.74 | 11-DEC-02:52 | -21.1 |
Annual Sum or Average | 0.372846E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.867826E+10 | 8704.82 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.603874E+10 | 10786.80 | 30-JAN-05:11 | -25.6 |
February | 0.414775E+10 | 10482.60 | 20-FEB-07:02 | -25.0 |
March | 0.185364E+10 | 10147.12 | 02-MAR-05:11 | -26.7 |
April | 0.277710E+09 | 9843.31 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 14758251.35 | 8184.45 | 28-SEP-06:01 | -2.8 |
October | 0.880749E+09 | 10091.66 | 30-OCT-04:01 | -14.4 |
November | 0.415458E+10 | 10303.22 | 27-NOV-05:11 | -26.0 |
December | 0.572421E+10 | 10310.13 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.230921E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.603874E+10 | 10786.80 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192081E+11 | 27991.63 | 12-JAN-07:10 | -38.3 |
February | 0.135558E+11 | 26622.05 | 27-FEB-07:10 | -34.9 |
March | 0.108050E+11 | 24533.43 | 01-MAR-07:10 | -28.8 |
April | 0.371765E+10 | 21896.74 | 03-APR-06:10 | -21.5 |
May | 0.120878E+10 | 14061.25 | 04-MAY-06:10 | 4.18 |
June | 0.407623E+09 | 12819.12 | 01-JUN-06:07 | 7.57 |
July | 0.328410E+09 | 12908.63 | 17-JUL-06:05 | 8.48 |
August | 0.752879E+09 | 14958.02 | 31-AUG-06:10 | -1.5 |
September | 0.236074E+10 | 16618.69 | 28-SEP-06:10 | -2.8 |
October | 0.740110E+10 | 21298.16 | 31-OCT-07:00 | -19.4 |
November | 0.162494E+11 | 24389.28 | 29-NOV-07:10 | -28.9 |
December | 0.194964E+11 | 26212.66 | 15-DEC-07:10 | -33.4 |
Annual Sum or Average | 0.954919E+11 | |||
Minimum of Months | 0.328410E+09 | 12819.12 | -38.3 | |
Maximum of Months | 0.194964E+11 | 27991.63 | 8.48 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.613525E+10 | 11521.56 | 30-JAN-05:11 | -25.6 |
February | 0.456028E+10 | 11202.34 | 20-FEB-07:02 | -25.0 |
March | 0.268795E+10 | 10827.35 | 02-MAR-05:11 | -26.7 |
April | 0.317483E+09 | 10210.52 | 03-APR-04:01 | -21.1 |
May | 483138.96 | 2539.97 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 21800208.17 | 8734.01 | 28-SEP-06:01 | -2.8 |
October | 0.108251E+10 | 10814.93 | 30-OCT-04:01 | -14.4 |
November | 0.415105E+10 | 10991.36 | 27-NOV-05:11 | -26.0 |
December | 0.574120E+10 | 11003.50 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.246980E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.613525E+10 | 11521.56 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.776252E+10 | 9548.41 | 29-JAN-01:02 | -25.1 |
February | 0.525003E+10 | 9367.82 | 27-FEB-03:32 | -34.6 |
March | 0.310553E+10 | 8940.24 | 02-MAR-05:11 | -26.7 |
April | 0.522162E+09 | 8746.76 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 63740093.05 | 7497.59 | 30-SEP-05:01 | -4.5 |
October | 0.195922E+10 | 8948.39 | 30-OCT-01:53 | -12.8 |
November | 0.604646E+10 | 9232.83 | 13-NOV-01:32 | -19.4 |
December | 0.769592E+10 | 9213.75 | 11-DEC-02:52 | -21.1 |
Annual Sum or Average | 0.324056E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.6 | |
Maximum of Months | 0.776252E+10 | 9548.41 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.525994E+10 | 12377.17 | 29-JAN-01:02 | -25.1 |
February | 0.308922E+10 | 12148.99 | 26-FEB-07:32 | -25.6 |
March | 0.130775E+10 | 11627.77 | 02-MAR-05:11 | -26.7 |
April | 0.222640E+09 | 11310.95 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 187416.65 | 1299.99 | 31-AUG-06:02 | -1.5 |
September | 35971797.34 | 9479.40 | 30-SEP-05:01 | -4.5 |
October | 0.110230E+10 | 11445.84 | 30-OCT-04:01 | -14.4 |
November | 0.406820E+10 | 11937.64 | 27-NOV-05:11 | -26.0 |
December | 0.531605E+10 | 11879.66 | 18-DEC-05:11 | -17.0 |
Annual Sum or Average | 0.204023E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.531605E+10 | 12377.17 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.688382E+10 | 18610.57 | 01-JAN-19:22 | -14.4 |
February | 0.344936E+10 | 18250.77 | 26-FEB-07:32 | -25.6 |
March | 0.153457E+10 | 17387.17 | 02-MAR-05:11 | -26.7 |
April | 0.274464E+09 | 16992.96 | 03-APR-04:01 | -21.1 |
May | 161859.30 | 1079.06 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 42935745.94 | 13976.79 | 28-SEP-06:01 | -2.8 |
October | 0.123725E+10 | 17306.89 | 30-OCT-04:01 | -14.4 |
November | 0.478148E+10 | 18001.92 | 27-NOV-05:11 | -26.0 |
December | 0.743102E+10 | 17931.00 | 18-DEC-05:11 | -17.0 |
Annual Sum or Average | 0.256351E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.743102E+10 | 18610.57 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.524701E+10 | 12309.36 | 29-JAN-01:02 | -25.1 |
February | 0.334463E+10 | 12122.72 | 26-FEB-07:32 | -25.6 |
March | 0.174985E+10 | 11567.71 | 02-MAR-05:11 | -26.7 |
April | 0.259687E+09 | 11239.85 | 03-APR-04:01 | -21.1 |
May | 268159.85 | 1787.73 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 61267.34 | 612.67 | 30-AUG-06:02 | 0.10 |
September | 43580417.56 | 9611.47 | 30-SEP-05:01 | -4.5 |
October | 0.124639E+10 | 11395.28 | 30-OCT-04:01 | -14.4 |
November | 0.396649E+10 | 11885.84 | 27-NOV-05:11 | -26.0 |
December | 0.523463E+10 | 11829.42 | 18-DEC-05:11 | -17.0 |
Annual Sum or Average | 0.210926E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.524701E+10 | 12309.36 | 14.88 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.208150E+11 | 18520.31 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.188385E+11 | 18520.31 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.216654E+11 | 18520.31 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.200796E+11 | 18520.31 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.212402E+11 | 18520.31 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.208620E+11 | 18520.31 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.204550E+11 | 18520.31 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.216654E+11 | 18520.31 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.200739E+11 | 18520.31 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.208179E+11 | 18520.31 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.203773E+11 | 18520.31 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.204522E+11 | 18520.31 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.247342E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.188385E+11 | 18520.31 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.216654E+11 | 18520.31 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529706E+10 | 5543.17 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.480483E+10 | 5543.17 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.570947E+10 | 5543.17 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.509972E+10 | 5543.17 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.550327E+10 | 5543.17 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.547666E+10 | 5543.17 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.512633E+10 | 5543.17 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.570947E+10 | 5543.17 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.509972E+10 | 5543.17 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.529706E+10 | 5543.17 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.523498E+10 | 5543.17 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.512633E+10 | 5543.17 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.634849E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.480483E+10 | 5543.17 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.570947E+10 | 5543.17 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105793E+10 | 1168.55 | 02-JAN-08:09 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.833213E+09 | 1168.55 | 01-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.850772E+09 | 1168.55 | 01-MAR-08:09 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.702594E+09 | 720.41 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.741078E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.727688E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.687485E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.781843E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.736030E+09 | 1122.40 | 28-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.851268E+09 | 1168.55 | 03-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.995165E+09 | 1168.55 | 01-NOV-07:10 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.106165E+10 | 1168.55 | 01-DEC-08:09 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.100267E+11 | 0.266883E+11 | ||||
Minimum of Months | 0.687485E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.106165E+10 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.653649E+09 | 739.79 | 02-JAN-08:09 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.517641E+09 | 739.79 | 01-FEB-08:09 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.535288E+09 | 739.79 | 01-MAR-08:09 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.445645E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.472907E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.463566E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.437990E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.497450E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.465374E+09 | 658.71 | 28-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.533841E+09 | 739.79 | 03-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.610288E+09 | 739.79 | 01-NOV-07:10 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.666623E+09 | 739.79 | 01-DEC-08:09 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.630026E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.437990E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.666623E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.100806E+10 | 1168.55 | 02-JAN-08:09 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.799804E+09 | 1168.55 | 01-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.838370E+09 | 1168.55 | 01-MAR-08:09 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.704646E+09 | 720.41 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.746512E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.732760E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.691815E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.784526E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.731018E+09 | 1086.37 | 28-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.832160E+09 | 1168.55 | 03-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.935963E+09 | 1168.55 | 01-NOV-07:10 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.103500E+10 | 1168.55 | 01-DEC-08:09 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.984063E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.691815E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.103500E+10 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.657352E+09 | 739.74 | 02-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.512502E+09 | 739.74 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.534269E+09 | 739.74 | 01-MAR-08:09 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.445997E+09 | 557.14 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.469451E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.461314E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.435492E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.494527E+09 | 456.05 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.463739E+09 | 712.35 | 29-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.531143E+09 | 739.74 | 03-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.611468E+09 | 739.74 | 01-NOV-07:10 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.668800E+09 | 739.74 | 01-DEC-08:09 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.628605E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.435492E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.668800E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105461E+10 | 1168.55 | 02-JAN-08:09 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.829766E+09 | 1168.55 | 01-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.849230E+09 | 1168.55 | 01-MAR-08:09 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.702041E+09 | 720.41 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.740768E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.727074E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.686807E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.781384E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.735010E+09 | 1119.46 | 28-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.848393E+09 | 1168.55 | 03-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.990832E+09 | 1168.55 | 01-NOV-07:10 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.106055E+10 | 1168.55 | 01-DEC-08:09 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.100065E+11 | 0.266883E+11 | ||||
Minimum of Months | 0.686807E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.106055E+10 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.651959E+09 | 739.79 | 02-JAN-08:09 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.516679E+09 | 739.79 | 01-FEB-08:09 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.534620E+09 | 739.79 | 01-MAR-08:09 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.445359E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.472621E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.463331E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.437735E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.497144E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.464901E+09 | 652.63 | 28-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.532925E+09 | 739.79 | 03-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.608379E+09 | 739.79 | 01-NOV-07:10 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.665772E+09 | 739.79 | 01-DEC-08:09 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.629143E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.437735E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.665772E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.100533E+10 | 1168.55 | 02-JAN-08:09 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.798050E+09 | 1168.55 | 01-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.837688E+09 | 1168.55 | 01-MAR-08:09 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.704166E+09 | 720.41 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.745988E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.732282E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.691374E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.783997E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.730460E+09 | 1080.55 | 28-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.830449E+09 | 1168.55 | 03-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.933682E+09 | 1168.55 | 01-NOV-07:10 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.103102E+10 | 1168.55 | 01-DEC-08:09 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.982448E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.691374E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.103102E+10 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.655650E+09 | 739.74 | 02-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.511428E+09 | 739.74 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.533471E+09 | 739.74 | 01-MAR-08:09 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.445632E+09 | 549.62 | 04-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.469205E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.461112E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.435308E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.494170E+09 | 456.05 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.463308E+09 | 710.86 | 29-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.530149E+09 | 739.74 | 03-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.609404E+09 | 739.74 | 01-NOV-07:10 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.668086E+09 | 739.74 | 01-DEC-08:09 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.627692E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.435308E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.668086E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105793E+10 | 1168.55 | 02-JAN-08:09 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.833213E+09 | 1168.55 | 01-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.850772E+09 | 1168.55 | 01-MAR-08:09 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.702594E+09 | 720.41 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.741078E+09 | 720.41 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.727688E+09 | 720.41 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.687485E+09 | 720.41 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.781843E+09 | 720.41 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.736029E+09 | 1122.40 | 28-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.851267E+09 | 1168.55 | 03-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.995164E+09 | 1168.55 | 01-NOV-07:10 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.106165E+10 | 1168.55 | 01-DEC-08:09 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.100267E+11 | 0.266883E+11 | ||||
Minimum of Months | 0.687485E+09 | 720.41 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.106165E+10 | 1168.55 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.653648E+09 | 739.79 | 02-JAN-08:09 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.517641E+09 | 739.79 | 01-FEB-08:09 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.535288E+09 | 739.79 | 01-MAR-08:09 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.445645E+09 | 456.08 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.472907E+09 | 456.08 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.463566E+09 | 456.08 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.437990E+09 | 456.08 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.497450E+09 | 456.08 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.465374E+09 | 658.72 | 28-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.533840E+09 | 739.79 | 03-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.610288E+09 | 739.79 | 01-NOV-07:10 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.666623E+09 | 739.79 | 01-DEC-08:09 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.630026E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.437990E+09 | 456.08 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.666623E+09 | 739.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.100806E+10 | 1168.55 | 02-JAN-08:09 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.799804E+09 | 1168.55 | 01-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.838369E+09 | 1168.55 | 01-MAR-08:09 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.704646E+09 | 720.41 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.746511E+09 | 720.41 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.732759E+09 | 720.41 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.691815E+09 | 720.41 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.784526E+09 | 720.41 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.731018E+09 | 1086.38 | 28-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.832159E+09 | 1168.55 | 03-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.935964E+09 | 1168.55 | 01-NOV-07:10 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.103500E+10 | 1168.55 | 01-DEC-08:09 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.984063E+10 | 0.266882E+11 | ||||
Minimum of Months | 0.691815E+09 | 720.41 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.103500E+10 | 1168.55 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.657352E+09 | 739.74 | 02-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.512502E+09 | 739.74 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.534269E+09 | 739.74 | 01-MAR-08:09 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.445997E+09 | 557.14 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.469451E+09 | 456.05 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.461314E+09 | 456.05 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.435492E+09 | 456.05 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.494527E+09 | 456.05 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.463739E+09 | 712.35 | 29-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.531143E+09 | 739.74 | 03-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.611468E+09 | 739.74 | 01-NOV-07:10 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.668800E+09 | 739.74 | 01-DEC-08:09 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.628605E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.435492E+09 | 456.05 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.668800E+09 | 739.74 | 0.147531E+10 | 953.29 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.208150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.200796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.212402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.208620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.204550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.200739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.208179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.203773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.204522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.247342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.529706E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.509972E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.550327E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.547666E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.512633E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.509972E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.529706E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.523498E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.512633E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.634849E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.480483E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.570947E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.105793E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939084E+09 |
February | 0.901968E+09 | 0.833213E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753702E+09 |
March | 0.107774E+10 | 0.850772E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110250E+10 |
April | 0.956342E+09 | 0.702594E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121399E+10 |
May | 0.103597E+10 | 0.741078E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748647E+09 |
June | 0.103308E+10 | 0.727688E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1007883.89 | 0.454506E+09 |
July | 0.959235E+09 | 0.687485E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3233134.49 | 0.339601E+09 |
August | 0.107774E+10 | 0.781843E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 459032.22 | 0.391498E+09 |
September | 0.956342E+09 | 0.736030E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442157E+09 |
October | 0.994195E+09 | 0.851268E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939124E+09 |
November | 0.984487E+09 | 0.995165E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344837E+09 |
December | 0.959235E+09 | 0.106165E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681885E+09 |
Annual Sum or Average | 0.119305E+11 | 0.100267E+11 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4700050.60 | 0.835153E+10 |
Minimum of Months | 0.901968E+09 | 0.687485E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339601E+09 |
Maximum of Months | 0.107774E+10 | 0.106165E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3233134.49 | 0.121399E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.653649E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626920E+09 |
February | 0.571020E+09 | 0.517641E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503071E+09 |
March | 0.682301E+09 | 0.535288E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740029E+09 |
April | 0.605444E+09 | 0.445645E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829333E+09 |
May | 0.655854E+09 | 0.472907E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512122E+09 |
June | 0.654023E+09 | 0.463566E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 671935.96 | 0.303296E+09 |
July | 0.607275E+09 | 0.437990E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2224852.08 | 0.228374E+09 |
August | 0.682301E+09 | 0.497450E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 307321.22 | 0.264689E+09 |
September | 0.605444E+09 | 0.465374E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303791E+09 |
October | 0.629407E+09 | 0.533841E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629637E+09 |
November | 0.623262E+09 | 0.610288E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229909E+09 |
December | 0.607275E+09 | 0.666623E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454943E+09 |
Annual Sum or Average | 0.755301E+10 | 0.630026E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3204109.26 | 0.562611E+10 |
Minimum of Months | 0.571020E+09 | 0.437990E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228374E+09 |
Maximum of Months | 0.682301E+09 | 0.666623E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2224852.08 | 0.829333E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.100806E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.941774E+09 |
February | 0.901968E+09 | 0.799804E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759135E+09 |
March | 0.107774E+10 | 0.838370E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113241E+10 |
April | 0.956342E+09 | 0.704646E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129498E+10 |
May | 0.103597E+10 | 0.746512E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.775026E+09 |
June | 0.103308E+10 | 0.732760E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1007854.66 | 0.455763E+09 |
July | 0.959235E+09 | 0.691815E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3025442.37 | 0.344487E+09 |
August | 0.107774E+10 | 0.784526E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 458278.01 | 0.406488E+09 |
September | 0.956342E+09 | 0.731018E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468182E+09 |
October | 0.994195E+09 | 0.832160E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961538E+09 |
November | 0.984487E+09 | 0.935963E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345733E+09 |
December | 0.959235E+09 | 0.103500E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683049E+09 |
Annual Sum or Average | 0.119305E+11 | 0.984063E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4491575.04 | 0.856857E+10 |
Minimum of Months | 0.901968E+09 | 0.691815E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344487E+09 |
Maximum of Months | 0.107774E+10 | 0.103500E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3025442.37 | 0.129498E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.657352E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626940E+09 |
February | 0.570983E+09 | 0.512502E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502991E+09 |
March | 0.682256E+09 | 0.534269E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738862E+09 |
April | 0.605404E+09 | 0.445997E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.849505E+09 |
May | 0.655811E+09 | 0.469451E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516745E+09 |
June | 0.653980E+09 | 0.461314E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 671942.52 | 0.306756E+09 |
July | 0.607235E+09 | 0.435492E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1776264.88 | 0.231050E+09 |
August | 0.682256E+09 | 0.494527E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 306033.29 | 0.266733E+09 |
September | 0.605404E+09 | 0.463739E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300838E+09 |
October | 0.629366E+09 | 0.531143E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627253E+09 |
November | 0.623221E+09 | 0.611468E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229975E+09 |
December | 0.607235E+09 | 0.668800E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454943E+09 |
Annual Sum or Average | 0.755252E+10 | 0.628605E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2754240.70 | 0.565259E+10 |
Minimum of Months | 0.570983E+09 | 0.435492E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229975E+09 |
Maximum of Months | 0.682256E+09 | 0.668800E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1776264.88 | 0.849505E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.105461E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503639E+09 |
February | 0.901968E+09 | 0.829766E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403930E+09 |
March | 0.107774E+10 | 0.849230E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597276E+09 |
April | 0.956342E+09 | 0.702041E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658866E+09 |
May | 0.103597E+10 | 0.740768E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398725E+09 |
June | 0.103308E+10 | 0.727074E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 555316.95 | 0.242178E+09 |
July | 0.959235E+09 | 0.686807E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1920352.67 | 0.181284E+09 |
August | 0.107774E+10 | 0.781384E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 260546.23 | 0.217457E+09 |
September | 0.956342E+09 | 0.735010E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255013E+09 |
October | 0.994195E+09 | 0.848393E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534008E+09 |
November | 0.984487E+09 | 0.990832E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187939E+09 |
December | 0.959235E+09 | 0.106055E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367335E+09 |
Annual Sum or Average | 0.119305E+11 | 0.100065E+11 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2736215.86 | 0.454765E+10 |
Minimum of Months | 0.901968E+09 | 0.686807E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181284E+09 |
Maximum of Months | 0.107774E+10 | 0.106055E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1920352.67 | 0.658866E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.651959E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336063E+09 |
February | 0.571020E+09 | 0.516679E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269753E+09 |
March | 0.682301E+09 | 0.534620E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403911E+09 |
April | 0.605444E+09 | 0.445359E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461847E+09 |
May | 0.655854E+09 | 0.472621E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285477E+09 |
June | 0.654023E+09 | 0.463331E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 370214.54 | 0.166709E+09 |
July | 0.607275E+09 | 0.437735E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1120724.52 | 0.126762E+09 |
August | 0.682301E+09 | 0.497144E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173258.38 | 0.150577E+09 |
September | 0.605444E+09 | 0.464901E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178472E+09 |
October | 0.629407E+09 | 0.532925E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360732E+09 |
November | 0.623262E+09 | 0.608379E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124970E+09 |
December | 0.607275E+09 | 0.665772E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244532E+09 |
Annual Sum or Average | 0.755301E+10 | 0.629143E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1664197.45 | 0.310980E+10 |
Minimum of Months | 0.571020E+09 | 0.437735E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124970E+09 |
Maximum of Months | 0.682301E+09 | 0.665772E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1120724.52 | 0.461847E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.100533E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153328E+11 |
February | 0.901968E+09 | 0.798050E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121504E+11 |
March | 0.107774E+10 | 0.837688E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135115E+11 |
April | 0.956342E+09 | 0.704166E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789311E+10 |
May | 0.103597E+10 | 0.745988E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473900E+10 |
June | 0.103308E+10 | 0.732282E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45858972.35 | 0.276298E+10 |
July | 0.959235E+09 | 0.691374E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67370033.56 | 0.211055E+10 |
August | 0.107774E+10 | 0.783997E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15659853.08 | 0.384710E+10 |
September | 0.956342E+09 | 0.730460E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586386E+10 |
October | 0.994195E+09 | 0.830449E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.986364E+10 |
November | 0.984487E+09 | 0.933682E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149910E+11 |
December | 0.959235E+09 | 0.103102E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154736E+11 |
Annual Sum or Average | 0.119305E+11 | 0.982448E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128889E+09 | 0.108539E+12 |
Minimum of Months | 0.901968E+09 | 0.691374E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211055E+10 |
Maximum of Months | 0.107774E+10 | 0.103102E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67370033.56 | 0.154736E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.655650E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336043E+09 |
February | 0.570983E+09 | 0.511428E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269507E+09 |
March | 0.682256E+09 | 0.533471E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401079E+09 |
April | 0.605404E+09 | 0.445632E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470934E+09 |
May | 0.655811E+09 | 0.469205E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281060E+09 |
June | 0.653980E+09 | 0.461112E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 370222.76 | 0.167277E+09 |
July | 0.607235E+09 | 0.435308E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1033653.10 | 0.125797E+09 |
August | 0.682256E+09 | 0.494170E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173264.27 | 0.150467E+09 |
September | 0.605404E+09 | 0.463308E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174846E+09 |
October | 0.629366E+09 | 0.530149E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357037E+09 |
November | 0.623221E+09 | 0.609404E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125058E+09 |
December | 0.607235E+09 | 0.668086E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244525E+09 |
Annual Sum or Average | 0.755252E+10 | 0.627692E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1577140.13 | 0.310363E+10 |
Minimum of Months | 0.570983E+09 | 0.435308E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125058E+09 |
Maximum of Months | 0.682256E+09 | 0.668086E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1033653.10 | 0.470934E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.105793E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789869E+09 |
February | 0.901968E+09 | 0.833213E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636276E+09 |
March | 0.107774E+10 | 0.850772E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943958E+09 |
April | 0.956342E+09 | 0.702594E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106310E+10 |
May | 0.103597E+10 | 0.741078E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657259E+09 |
June | 0.103308E+10 | 0.727688E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 854168.35 | 0.393062E+09 |
July | 0.959235E+09 | 0.687485E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2784900.83 | 0.292432E+09 |
August | 0.107774E+10 | 0.781843E+09 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 394408.02 | 0.343510E+09 |
September | 0.956342E+09 | 0.736029E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397180E+09 |
October | 0.994195E+09 | 0.851267E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820756E+09 |
November | 0.984487E+09 | 0.995164E+09 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291366E+09 |
December | 0.959235E+09 | 0.106165E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573820E+09 |
Annual Sum or Average | 0.119305E+11 | 0.100267E+11 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4033477.20 | 0.720259E+10 |
Minimum of Months | 0.901968E+09 | 0.687485E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291366E+09 |
Maximum of Months | 0.107774E+10 | 0.106165E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2784900.83 | 0.106310E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.653648E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526514E+09 |
February | 0.421807E+09 | 0.517641E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424289E+09 |
March | 0.502994E+09 | 0.535288E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635702E+09 |
April | 0.447140E+09 | 0.445645E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725298E+09 |
May | 0.484071E+09 | 0.472907E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444936E+09 |
June | 0.482240E+09 | 0.463566E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 569428.31 | 0.261029E+09 |
July | 0.448971E+09 | 0.437990E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1954064.12 | 0.195488E+09 |
August | 0.502994E+09 | 0.497450E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 264085.37 | 0.230127E+09 |
September | 0.447140E+09 | 0.465374E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269969E+09 |
October | 0.465148E+09 | 0.533840E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550221E+09 |
November | 0.460569E+09 | 0.610288E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193908E+09 |
December | 0.448971E+09 | 0.666623E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382056E+09 |
Annual Sum or Average | 0.557719E+10 | 0.630026E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2787577.81 | 0.483954E+10 |
Minimum of Months | 0.421807E+09 | 0.437990E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193908E+09 |
Maximum of Months | 0.502994E+09 | 0.666623E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1954064.12 | 0.725298E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.100806E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791588E+09 |
February | 0.901968E+09 | 0.799804E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642980E+09 |
March | 0.107774E+10 | 0.838369E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.977777E+09 |
April | 0.956342E+09 | 0.704646E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113289E+10 |
May | 0.103597E+10 | 0.746511E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675208E+09 |
June | 0.103308E+10 | 0.732759E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 854082.99 | 0.393823E+09 |
July | 0.959235E+09 | 0.691815E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2629510.50 | 0.296169E+09 |
August | 0.107774E+10 | 0.784526E+09 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 393511.96 | 0.353874E+09 |
September | 0.956342E+09 | 0.731018E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415164E+09 |
October | 0.994195E+09 | 0.832159E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.843556E+09 |
November | 0.984487E+09 | 0.935964E+09 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292701E+09 |
December | 0.959235E+09 | 0.103500E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574483E+09 |
Annual Sum or Average | 0.119305E+11 | 0.984063E+10 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3877105.45 | 0.739022E+10 |
Minimum of Months | 0.901968E+09 | 0.691815E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292701E+09 |
Maximum of Months | 0.107774E+10 | 0.103500E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2629510.50 | 0.113289E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.657352E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526495E+09 |
February | 0.570983E+09 | 0.512502E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424095E+09 |
March | 0.682256E+09 | 0.534269E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633795E+09 |
April | 0.605404E+09 | 0.445997E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742407E+09 |
May | 0.655811E+09 | 0.469451E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450706E+09 |
June | 0.653980E+09 | 0.461314E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 569463.00 | 0.265083E+09 |
July | 0.607235E+09 | 0.435492E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1535037.49 | 0.198586E+09 |
August | 0.682256E+09 | 0.494527E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262948.85 | 0.233213E+09 |
September | 0.605404E+09 | 0.463739E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267903E+09 |
October | 0.629366E+09 | 0.531143E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547768E+09 |
November | 0.623221E+09 | 0.611468E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194050E+09 |
December | 0.607235E+09 | 0.668800E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382065E+09 |
Annual Sum or Average | 0.755252E+10 | 0.628605E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2367449.33 | 0.486617E+10 |
Minimum of Months | 0.570983E+09 | 0.435492E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194050E+09 |
Maximum of Months | 0.682256E+09 | 0.668800E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1535037.49 | 0.742407E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102841E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838808E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127787E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147343E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.886456E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561344.03 | 0.519679E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2204147.48 | 0.386149E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123130.60 | 0.466794E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552311E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113365E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389947E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.752496E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2888622.10 | 0.970600E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386149E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2204147.48 | 0.147343E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130289E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106289E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160907E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184049E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112163E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 708785.96 | 0.661038E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2988734.27 | 0.491231E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162137.46 | 0.588330E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678193E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138877E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489168E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952431E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3859657.70 | 0.121861E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489168E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2988734.27 | 0.184049E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137108E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111359E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166618E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189284E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117064E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467186.38 | 0.704963E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2096329.77 | 0.530324E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35860.94 | 0.612734E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683313E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140862E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507821E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100114E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2599377.10 | 0.126633E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507821E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2096329.77 | 0.189284E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 18520.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 18520.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 18520.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 18520.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 18520.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 18520.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 18520.31 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 18520.31 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 18520.31 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 18520.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 18520.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 18520.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 5543.17 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 5543.17 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 5543.17 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 5543.17 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 5543.17 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 5543.17 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 5543.17 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 5543.17 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 5543.17 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 5543.17 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 5543.17 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 5543.17 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-08:09 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4205.13 | 28-JAN-23:51 |
February | 1306.65 | 01-FEB-10:09 | 1168.55 | 01-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2520.29 | 25-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1168.55 | 01-MAR-08:09 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1885.50 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2541.35 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1217.80 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.16 | 30-JUN-15:00 | 1162.99 | 24-JUN-21:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.46 | 21-JUL-16:00 | 899.11 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.41 | 11-AUG-16:00 | 953.87 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1122.40 | 28-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 721.71 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1168.55 | 03-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1560.58 | 21-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 01-NOV-07:10 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1343.43 | 09-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-08:09 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1449.42 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 721.71 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 144.46 | 4205.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 739.79 | 02-JAN-08:09 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2801.99 | 28-JAN-23:51 |
February | 827.22 | 01-FEB-10:09 | 739.79 | 01-FEB-08:09 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1680.18 | 25-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 739.79 | 01-MAR-08:09 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1257.29 | 14-MAR-21:02 |
April | 827.22 | 03-APR-09:09 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1690.72 | 01-APR-18:55 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 813.75 | 26-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.77 | 30-JUN-15:00 | 767.32 | 24-JUN-21:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.31 | 21-JUL-16:00 | 603.35 | 04-JUL-17:00 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 11-AUG-16:00 | 633.14 | 30-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 658.71 | 28-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 488.42 | 04-SEP-14:00 |
October | 827.22 | 02-OCT-09:09 | 739.79 | 03-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1043.47 | 21-OCT-04:04 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 01-NOV-07:10 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 895.26 | 09-NOV-22:01 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-08:09 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 966.27 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.42 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 96.31 | 2801.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-08:09 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4207.77 | 28-JAN-23:51 |
February | 1306.65 | 01-FEB-10:09 | 1168.55 | 01-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2520.29 | 25-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1168.55 | 01-MAR-08:09 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1906.07 | 12-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2797.76 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1233.96 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.16 | 30-JUN-15:00 | 1186.69 | 18-JUN-13:55 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.46 | 21-JUL-16:00 | 917.95 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.41 | 11-AUG-16:00 | 957.97 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1086.37 | 28-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 751.04 | 30-SEP-21:00 |
October | 1306.65 | 02-OCT-09:09 | 1168.55 | 03-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1560.58 | 21-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 01-NOV-07:10 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1344.55 | 09-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-08:09 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1449.42 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 751.04 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 144.46 | 4207.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2802.47 | 28-JAN-23:51 |
February | 827.17 | 01-FEB-10:09 | 739.74 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1680.18 | 25-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 739.74 | 01-MAR-08:09 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1257.60 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 557.14 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2080.67 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 813.51 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.77 | 30-JUN-15:00 | 763.85 | 24-JUN-21:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.31 | 21-JUL-16:00 | 611.71 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 456.05 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 11-AUG-16:00 | 631.23 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 712.35 | 29-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 479.48 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 739.74 | 03-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1042.37 | 21-OCT-04:04 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 01-NOV-07:10 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 895.45 | 09-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-08:09 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 966.28 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.48 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 96.31 | 2802.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-08:09 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2259.56 | 28-JAN-23:54 |
February | 1306.65 | 01-FEB-10:09 | 1168.55 | 01-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1333.50 | 25-FEB-00:53 |
March | 1306.65 | 01-MAR-10:09 | 1168.55 | 01-MAR-08:09 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1002.98 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1397.12 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 683.09 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.30 | 30-JUN-15:00 | 666.80 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.55 | 21-JUL-16:00 | 486.87 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 | 11-AUG-16:00 | 554.64 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1119.46 | 28-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 430.97 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1168.55 | 03-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 854.71 | 21-OCT-04:01 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 01-NOV-07:10 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 727.52 | 10-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-08:09 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 769.69 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.97 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 77.55 | 2259.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 739.79 | 02-JAN-08:09 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1510.39 | 28-JAN-23:52 |
February | 827.22 | 01-FEB-10:09 | 739.79 | 01-FEB-08:09 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 888.88 | 25-FEB-00:53 |
March | 827.22 | 01-MAR-10:09 | 739.79 | 01-MAR-08:09 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 669.54 | 14-MAR-21:02 |
April | 827.22 | 03-APR-09:09 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 944.73 | 01-APR-18:55 |
May | 827.22 | 01-MAY-09:09 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 473.21 | 26-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 | 30-JUN-15:00 | 447.46 | 25-JUN-06:00 |
July | 827.22 | 03-JUL-09:09 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 21-JUL-16:00 | 334.49 | 04-JUL-17:00 |
August | 827.22 | 01-AUG-09:09 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 11-AUG-16:00 | 375.22 | 30-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 652.63 | 28-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 300.87 | 04-SEP-14:00 |
October | 827.22 | 02-OCT-09:09 | 739.79 | 03-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 570.40 | 21-OCT-04:01 |
November | 827.22 | 01-NOV-09:09 | 739.79 | 01-NOV-07:10 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 483.01 | 10-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 739.79 | 01-DEC-08:09 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 513.12 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.87 | |||||
Maximum of Months | 827.22 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 1510.39 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-08:09 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 80147.40 | 12-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1168.55 | 01-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 73566.71 | 27-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1168.55 | 01-MAR-08:09 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 66166.27 | 01-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 57193.98 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 22332.72 | 16-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2561.06 | 21-JUN-17:00 | 18259.79 | 02-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6050.89 | 21-JUL-16:10 | 16494.51 | 05-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1955.25 | 11-AUG-16:50 | 28625.10 | 31-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 1080.55 | 28-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 31762.60 | 29-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 1168.55 | 03-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 52528.41 | 27-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 01-NOV-07:10 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 66798.28 | 28-NOV-12:01 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-08:09 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 73919.93 | 15-DEC-12:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16494.51 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 6050.89 | 80147.40 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1514.63 | 28-JAN-23:52 |
February | 827.17 | 01-FEB-10:09 | 739.74 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 888.45 | 25-FEB-00:53 |
March | 827.17 | 01-MAR-10:09 | 739.74 | 01-MAR-08:09 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 669.29 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 549.62 | 04-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1117.87 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 456.80 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 | 30-JUN-15:00 | 442.37 | 25-JUN-06:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 21-JUL-16:00 | 336.52 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 456.05 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 11-AUG-16:00 | 373.75 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 710.86 | 29-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 293.44 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 739.74 | 03-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 567.51 | 21-OCT-04:01 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 01-NOV-07:10 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 483.96 | 10-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-08:09 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 513.12 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.44 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 1514.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-08:09 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3537.00 | 28-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 1168.55 | 01-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2096.64 | 25-FEB-00:53 |
March | 1306.65 | 01-MAR-10:09 | 1168.55 | 01-MAR-08:09 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1573.99 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2211.04 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1089.46 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.70 | 30-JUN-15:00 | 1046.46 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.83 | 21-JUL-16:00 | 782.31 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 | 11-AUG-16:00 | 852.54 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1122.40 | 28-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 665.85 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1168.55 | 03-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1289.94 | 21-OCT-04:01 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 01-NOV-07:10 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1120.97 | 09-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-08:09 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1197.31 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 665.85 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 120.83 | 3537.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 739.79 | 02-JAN-08:09 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2357.99 | 28-JAN-24:00 |
February | 805.43 | 01-FEB-08:09 | 739.79 | 01-FEB-08:09 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1397.75 | 25-FEB-00:53 |
March | 805.43 | 01-MAR-08:09 | 739.79 | 01-MAR-08:09 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1049.69 | 14-MAR-21:02 |
April | 805.43 | 03-APR-07:10 | 456.08 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1473.01 | 01-APR-18:55 |
May | 805.43 | 01-MAY-07:10 | 456.08 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 726.22 | 26-MAY-02:00 |
June | 805.43 | 01-JUN-07:10 | 456.08 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 30-JUN-15:00 | 694.17 | 25-JUN-06:00 |
July | 805.43 | 03-JUL-07:10 | 456.08 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.12 | 29-JUL-20:00 | 525.01 | 04-JUL-17:00 |
August | 805.43 | 01-AUG-07:10 | 456.08 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.08 | 11-AUG-16:00 | 564.94 | 30-AUG-01:00 |
September | 805.43 | 01-SEP-07:10 | 658.72 | 28-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 449.60 | 04-SEP-14:00 |
October | 805.43 | 02-OCT-07:10 | 739.79 | 03-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 857.57 | 21-OCT-04:01 |
November | 805.43 | 01-NOV-07:10 | 739.79 | 01-NOV-07:10 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 747.04 | 09-NOV-22:01 |
December | 805.43 | 01-DEC-08:09 | 739.79 | 01-DEC-08:09 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 797.09 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.60 | |||||
Maximum of Months | 805.43 | 739.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 85.12 | 2357.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1168.55 | 02-JAN-08:09 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3537.01 | 28-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 1168.55 | 01-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2096.63 | 25-FEB-00:53 |
March | 1306.65 | 01-MAR-10:09 | 1168.55 | 01-MAR-08:09 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1713.64 | 12-MAR-14:55 |
April | 1306.65 | 03-APR-09:09 | 720.41 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2421.29 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 720.41 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1100.94 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 720.41 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.70 | 30-JUN-15:00 | 1032.38 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 720.41 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.83 | 21-JUL-16:00 | 798.53 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 720.41 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 | 11-AUG-16:00 | 854.61 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1086.38 | 28-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 680.18 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1168.55 | 03-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1317.09 | 22-OCT-17:53 |
November | 1306.65 | 01-NOV-09:09 | 1168.55 | 01-NOV-07:10 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1125.80 | 10-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1168.55 | 01-DEC-08:09 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1198.14 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 680.18 | |||||
Maximum of Months | 1306.65 | 1168.55 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 120.83 | 3537.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 739.74 | 02-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2357.99 | 28-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 739.74 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1397.75 | 25-FEB-00:53 |
March | 827.17 | 01-MAR-10:09 | 739.74 | 01-MAR-08:09 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1049.85 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 557.14 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1791.14 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 456.05 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 727.40 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 456.05 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 30-JUN-15:00 | 683.04 | 25-JUN-06:00 |
July | 827.17 | 03-JUL-09:09 | 456.05 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.56 | 21-JUL-16:00 | 532.47 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 456.05 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.08 | 11-AUG-16:00 | 564.96 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 712.35 | 29-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 442.61 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 739.74 | 03-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 856.02 | 21-OCT-04:01 |
November | 827.17 | 01-NOV-09:09 | 739.74 | 01-NOV-07:10 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 747.19 | 09-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 739.74 | 01-DEC-08:09 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 797.35 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.61 | |||||
Maximum of Months | 827.17 | 739.74 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 80.56 | 2357.99 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4680.51 | 28-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2821.31 | 25-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1996.49 | 14-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3122.03 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1500.89 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.62 | 30-JUN-15:00 | 1440.82 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.07 | 21-JUL-16:00 | 995.08 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.29 | 11-AUG-16:00 | 1177.11 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 901.14 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1844.76 | 21-OCT-04:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1547.64 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1614.18 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 901.14 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.07 | 4680.51 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 5887.22 | 28-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3597.02 | 25-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2546.28 | 14-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3902.64 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1900.62 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.56 | 30-JUN-15:00 | 1779.55 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.01 | 29-JUL-17:03 | 1246.21 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | 11-AUG-16:00 | 1483.17 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1072.42 | 30-SEP-21:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2265.85 | 21-OCT-04:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1950.57 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2059.46 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.42 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.01 | 5887.22 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 6059.35 | 28-JAN-23:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3756.67 | 25-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2760.38 | 14-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4208.11 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1849.94 | 26-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.54 | 30-JUN-15:00 | 1784.84 | 18-JUN-13:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.05 | 21-JUL-16:00 | 1417.33 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 | 11-AUG-16:00 | 1424.01 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1138.06 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2260.13 | 21-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2000.93 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2136.27 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1138.06 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.05 | 6059.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7335.94 | 27-JAN-17:00 | 6035.01 | 5543.17 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7905.48 | 10-FEB-17:00 | 6035.01 | 5543.17 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11324.71 | 23-MAR-07:50 | 6035.01 | 5543.17 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39360.89 | 28-APR-05:02 | 3811.58 | 3695.25 | 30830.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41648.98 | 10-MAY-05:02 | 3176.32 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 44116.15 | 19-JUN-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 44675.68 | 17-JUL-04:03 | 0.00 | 2463.50 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 45598.14 | 14-AUG-04:02 | 0.00 | 3079.37 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 42428.17 | 01-SEP-05:02 | 3811.58 | 3695.25 | 30830.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16323.53 | 06-OCT-07:06 | 30175.04 | 27715.86 | 92601.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7763.26 | 03-NOV-16:00 | 6035.01 | 5543.17 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7026.28 | 21-DEC-17:00 | 6035.01 | 5543.17 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7026.28 | 0.00 | 2463.50 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45598.14 | 30175.04 | 27715.86 | 92601.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1227.89 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1002.84 |
March | 938.57 | 22-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.13 |
April | 3948.55 | 21-APR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.18 |
May | 7139.68 | 31-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.98 |
June | 8303.53 | 29-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.26 | 0.00 |
July | 8433.10 | 21-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 | 0.00 |
August | 7146.97 | 10-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.95 |
September | 2696.17 | 07-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.76 |
October | 805.38 | 03-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.12 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1097.89 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8433.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 | 1227.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2766.43 | 11-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2856.28 | 18-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1157.99 |
March | 3148.04 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.13 |
April | 2989.74 | 14-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.46 |
May | 3465.96 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.54 |
June | 4480.86 | 30-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.62 | 0.00 |
July | 4982.83 | 24-JUL-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.24 |
August | 4031.52 | 11-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | 0.00 |
September | 1339.92 | 29-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.95 |
October | 2147.01 | 27-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2064.25 |
November | 2758.36 | 30-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3097.04 | 22-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1339.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4982.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.62 | 2064.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5956.14 | 12-JAN-17:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4594.25 | 17-FEB-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5835.91 | 31-MAR-06:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3723.92 | 13-APR-06:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.77 |
May | 3644.65 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 |
June | 4733.66 | 22-JUN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.64 |
July | 5810.91 | 24-JUL-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.54 |
August | 4671.51 | 11-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.29 | 0.00 |
September | 3206.71 | 15-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 |
October | 3756.55 | 27-OCT-06:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.16 |
November | 4724.49 | 09-NOV-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4988.94 | 15-DEC-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3206.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5956.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.29 | 370.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5585.41 | 20-JAN-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6324.58 | 09-FEB-14:50 | 6198.29 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6988.85 | 22-MAR-15:40 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12464.11 | 21-APR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31377.56 | 15-MAY-05:02 | 3176.32 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32224.05 | 12-JUN-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34042.66 | 24-JUL-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32816.93 | 14-AUG-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12747.77 | 01-SEP-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7475.89 | 05-OCT-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5783.15 | 02-NOV-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5353.94 | 21-DEC-17:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5353.94 | 0.00 | 3079.37 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34042.66 | 6198.29 | 5543.17 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 4938.98 | 07-JAN-17:02 | 1905.79 | 1847.85 | 14286.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6009.32 | 09-FEB-15:50 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6968.10 | 22-MAR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12069.51 | 21-APR-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16762.14 | 31-MAY-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23128.59 | 23-JUN-05:03 | 1905.79 | 1847.62 | 9524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32582.66 | 24-JUL-04:02 | 0.00 | 3079.37 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28320.28 | 03-AUG-05:03 | 2541.06 | 2463.50 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11503.64 | 01-SEP-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7110.21 | 03-OCT-16:00 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5150.60 | 08-NOV-15:50 | 6035.01 | 5543.17 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4923.27 | 02-DEC-17:01 | 2541.06 | 2463.80 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 4923.27 | 0.00 | 1847.62 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32582.66 | 6035.01 | 5543.17 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1117.94 | 07-JAN-17:02 | 401.76 | 389.54 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.94 |
February | 1133.43 | 11-FEB-17:02 | 334.80 | 324.62 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.17 |
March | 1404.49 | 22-MAR-15:50 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2141.83 | 28-APR-15:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.11 |
May | 9640.81 | 31-MAY-06:02 | 1339.19 | 1200.67 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.19 |
June | 10065.50 | 13-JUN-06:02 | 1607.03 | 1440.80 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.78 |
July | 10109.73 | 11-JUL-06:02 | 1339.19 | 1200.67 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.30 |
August | 4998.75 | 02-AUG-15:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.21 |
September | 2214.02 | 01-SEP-16:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.40 |
October | 1421.10 | 04-OCT-15:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.88 |
November | 1115.09 | 18-NOV-17:02 | 401.76 | 389.54 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1113.81 | 23-DEC-17:02 | 334.80 | 324.62 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1113.81 | 334.80 | 324.62 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10109.73 | 1607.03 | 1440.80 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1013.97 | 07-JAN-17:02 | 254.35 | 246.61 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.04 |
February | 1029.78 | 11-FEB-17:02 | 211.95 | 205.51 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.00 |
March | 1959.38 | 22-MAR-10:30 | 805.43 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.99 |
April | 5736.04 | 22-APR-09:25 | 522.45 | 304.05 | 1059.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.92 |
May | 15918.05 | 14-MAY-09:41 | 296.74 | 177.38 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.95 |
June | 11847.98 | 13-JUN-06:02 | 1017.38 | 912.15 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.51 |
July | 16619.50 | 23-JUL-09:41 | 339.13 | 202.72 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.52 |
August | 10897.66 | 11-AUG-06:02 | 1017.38 | 912.15 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.63 |
September | 6337.96 | 10-SEP-09:53 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.62 |
October | 1719.80 | 03-OCT-10:15 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.75 |
November | 1013.12 | 18-NOV-17:02 | 254.35 | 246.61 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1009.99 | 30-DEC-17:02 | 254.35 | 246.61 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1009.99 | 169.56 | 101.36 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16619.50 | 1610.86 | 912.16 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1830.11 | 25-JAN-13:30 | 3816.70 | 2161.23 | 4517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.50 |
February | 4052.75 | 15-FEB-13:50 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8091.30 | 31-MAR-14:00 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.27 |
April | 13839.25 | 20-APR-14:00 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.52 |
May | 24544.48 | 14-MAY-12:22 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.92 |
June | 18143.94 | 04-JUN-13:43 | 267.84 | 160.10 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.93 |
July | 26463.44 | 23-JUL-12:21 | 535.68 | 320.20 | 4015.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.82 |
August | 22678.37 | 27-AUG-13:12 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.83 |
September | 10884.88 | 07-SEP-14:30 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.75 |
October | 9307.74 | 03-OCT-13:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.47 |
November | 2539.77 | 08-NOV-14:00 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.01 |
December | 1620.17 | 30-DEC-17:02 | 401.76 | 389.54 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1620.17 | 267.84 | 160.10 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26463.44 | 3816.70 | 2161.23 | 4517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1066.67 | 07-JAN-17:02 | 254.33 | 246.60 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.99 |
February | 1082.63 | 11-FEB-17:02 | 211.94 | 205.50 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.97 |
March | 1598.12 | 22-MAR-15:40 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7081.20 | 21-APR-17:50 | 84.78 | 152.01 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.38 |
May | 15418.46 | 14-MAY-18:22 | 0.00 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.04 |
June | 14138.49 | 10-JUN-17:05 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.32 |
July | 11242.77 | 23-JUL-15:42 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 |
August | 9561.13 | 27-AUG-17:12 | 0.00 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.25 |
September | 4694.96 | 02-SEP-17:15 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.99 |
October | 1592.15 | 03-OCT-15:10 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.04 |
November | 1070.19 | 18-NOV-17:02 | 254.33 | 246.60 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1063.43 | 30-DEC-17:02 | 254.33 | 246.60 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1063.43 | 0.00 | 101.35 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15418.46 | 805.38 | 456.05 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1014.30 | 07-JAN-17:02 | 401.76 | 389.54 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.41 |
February | 1022.70 | 11-FEB-17:02 | 334.80 | 324.62 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.26 |
March | 1095.53 | 22-MAR-15:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1532.35 | 28-APR-15:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.87 |
May | 2975.57 | 31-MAY-14:30 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.22 |
June | 8282.36 | 07-JUN-04:02 | 0.00 | 400.21 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.79 |
July | 8413.68 | 11-JUL-04:02 | 0.00 | 400.21 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.33 |
August | 5137.00 | 02-AUG-06:02 | 1607.03 | 1440.80 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 |
September | 1920.86 | 01-SEP-16:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.63 |
October | 1375.53 | 06-OCT-15:00 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.82 |
November | 1021.00 | 18-NOV-17:02 | 401.76 | 389.54 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1012.93 | 30-DEC-17:02 | 401.76 | 389.54 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1012.93 | 0.00 | 324.62 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8413.68 | 1607.03 | 1440.80 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 838.87 | 07-JAN-17:02 | 254.35 | 246.61 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.49 |
February | 848.07 | 11-FEB-17:02 | 211.95 | 205.51 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.80 |
March | 1394.43 | 31-MAR-09:30 | 827.22 | 456.08 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.20 |
April | 3989.87 | 22-APR-08:30 | 254.35 | 152.02 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.20 |
May | 9298.25 | 31-MAY-06:02 | 847.82 | 760.12 | 2118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 |
June | 9589.56 | 13-JUN-06:02 | 1017.38 | 912.15 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.55 |
July | 10187.61 | 23-JUL-10:32 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.40 |
August | 9385.58 | 11-AUG-06:02 | 1017.38 | 912.15 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.31 |
September | 6739.39 | 10-SEP-09:53 | 169.56 | 101.36 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.50 |
October | 2100.19 | 03-OCT-09:35 | 1654.44 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.75 |
November | 845.97 | 18-NOV-17:02 | 254.35 | 246.61 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 837.89 | 30-DEC-17:02 | 254.35 | 246.61 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 837.89 | 169.56 | 101.36 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10187.61 | 1654.44 | 912.16 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1332.10 | 28-JAN-17:01 | 535.68 | 519.39 | 4015.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.39 |
February | 1613.45 | 18-FEB-13:00 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.15 |
March | 1967.60 | 11-MAR-13:50 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.21 |
April | 8272.41 | 22-APR-14:00 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.80 |
May | 9197.24 | 12-MAY-13:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.03 |
June | 11505.79 | 04-JUN-14:52 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.43 |
July | 18953.76 | 23-JUL-13:52 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.32 |
August | 15704.22 | 27-AUG-15:12 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.72 |
September | 10144.44 | 10-SEP-11:53 | 200.88 | 120.08 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.28 |
October | 4961.62 | 03-OCT-13:50 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2391.68 |
November | 1343.97 | 18-NOV-17:02 | 401.76 | 389.54 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1318.07 | 30-DEC-17:02 | 401.76 | 389.54 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1318.07 | 133.92 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18953.76 | 1306.65 | 720.41 | 4015.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2391.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 895.17 | 07-JAN-17:02 | 254.33 | 246.60 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.47 |
February | 903.38 | 11-FEB-17:02 | 211.94 | 205.50 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.78 |
March | 1215.35 | 31-MAR-17:00 | 254.33 | 253.36 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.15 |
April | 5526.80 | 21-APR-18:20 | 84.78 | 152.01 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 |
May | 10280.85 | 14-MAY-19:02 | 0.00 | 126.69 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.99 |
June | 7739.39 | 10-JUN-17:08 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.83 |
July | 8717.28 | 09-JUL-19:53 | 0.00 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.10 |
August | 6695.99 | 27-AUG-17:53 | 0.00 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.78 |
September | 4228.52 | 02-SEP-17:15 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.99 |
October | 1359.30 | 03-OCT-15:20 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.53 |
November | 905.39 | 18-NOV-17:02 | 254.33 | 246.60 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 894.75 | 30-DEC-17:02 | 254.33 | 246.60 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 894.75 | 0.00 | 101.35 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10280.85 | 805.38 | 456.05 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 986.65 | 21-JAN-17:02 | 334.80 | 324.62 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.39 |
February | 999.71 | 11-FEB-17:02 | 334.80 | 324.62 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.79 |
March | 1295.53 | 22-MAR-15:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2492.42 | 28-APR-15:20 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.83 |
May | 8510.52 | 31-MAY-06:02 | 1339.19 | 1200.67 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.04 |
June | 9741.23 | 07-JUN-04:02 | 0.00 | 400.21 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.54 |
July | 9538.41 | 11-JUL-04:02 | 0.00 | 400.21 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.68 |
August | 8017.69 | 02-AUG-06:02 | 1607.03 | 1440.80 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.13 |
September | 2666.46 | 01-SEP-13:50 | 1306.65 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.46 |
October | 1382.97 | 04-OCT-15:40 | 1272.23 | 720.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.92 |
November | 984.55 | 18-NOV-17:02 | 401.76 | 389.54 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1001.37 | 30-DEC-17:02 | 401.76 | 389.54 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 984.55 | 0.00 | 324.62 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9741.23 | 1607.03 | 1440.80 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1023.73 | 21-JAN-17:02 | 211.95 | 205.51 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.91 |
February | 1154.64 | 09-FEB-11:35 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.51 |
March | 2634.48 | 31-MAR-10:10 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.53 |
April | 6486.83 | 22-APR-09:20 | 0.00 | 304.05 | 1059.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.51 |
May | 14293.24 | 14-MAY-09:12 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.52 |
June | 11405.60 | 13-JUN-06:02 | 1017.38 | 912.15 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.02 |
July | 14830.07 | 09-JUL-07:02 | 211.95 | 126.70 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.22 |
August | 11119.16 | 11-AUG-06:02 | 1017.38 | 912.15 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.45 |
September | 5350.83 | 10-SEP-09:23 | 127.17 | 76.02 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.92 |
October | 2473.59 | 03-OCT-10:05 | 1610.86 | 912.16 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.61 |
November | 1023.60 | 18-NOV-17:02 | 254.35 | 246.61 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1039.73 | 30-DEC-17:02 | 254.35 | 246.61 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1023.60 | 0.00 | 76.02 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14830.07 | 1610.86 | 912.16 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1972.39 | 25-JAN-13:30 | 3816.70 | 2161.23 | 4517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.41 |
February | 4869.72 | 15-FEB-13:40 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9085.87 | 31-MAR-13:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.91 |
April | 13628.00 | 20-APR-14:10 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.54 |
May | 20304.72 | 14-MAY-12:32 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.45 |
June | 22189.74 | 18-JUN-12:22 | 334.80 | 200.13 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.27 |
July | 22879.32 | 23-JUL-13:12 | 401.76 | 240.15 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.98 |
August | 24366.23 | 27-AUG-13:01 | 468.72 | 280.18 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.59 |
September | 11178.25 | 09-SEP-13:30 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.58 |
October | 9957.10 | 03-OCT-13:30 | 1306.65 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.96 |
November | 2769.59 | 08-NOV-13:50 | 1272.23 | 720.41 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.68 |
December | 1585.49 | 30-DEC-17:02 | 401.76 | 389.54 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1585.49 | 137.54 | 120.07 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24366.23 | 3816.70 | 2161.23 | 4517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1023.96 | 07-JAN-17:02 | 254.33 | 246.60 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.97 |
February | 1038.95 | 11-FEB-17:02 | 211.94 | 205.50 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.40 |
March | 1612.75 | 31-MAR-17:00 | 254.33 | 253.36 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.50 |
April | 7387.84 | 22-APR-17:08 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.79 |
May | 11937.54 | 28-MAY-17:12 | 0.00 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.09 |
June | 13372.17 | 10-JUN-17:05 | 254.33 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.88 |
July | 9982.67 | 30-JUL-19:12 | 0.00 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.06 |
August | 15018.28 | 27-AUG-17:42 | 0.00 | 152.03 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.03 |
September | 5701.06 | 02-SEP-17:12 | 169.55 | 101.35 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.90 |
October | 1601.30 | 03-OCT-15:10 | 805.38 | 456.05 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.76 |
November | 1027.55 | 18-NOV-17:02 | 254.33 | 246.60 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1041.03 | 30-DEC-17:02 | 254.33 | 246.60 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1023.96 | 0.00 | 101.35 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15018.28 | 805.38 | 456.05 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.79 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.263961E+12 | 286129.70 | 02-JAN-08:09 | 0.661264E+11 | 211066.48 | 12-JAN-07:30 |
February | 0.203426E+12 | 272315.57 | 27-FEB-07:10 | 0.427355E+11 | 190532.12 | 27-FEB-08:39 |
March | 0.179517E+12 | 238875.94 | 06-MAR-07:10 | 0.221580E+11 | 167523.19 | 01-MAR-07:30 |
April | 0.115632E+12 | 206061.13 | 03-APR-06:10 | 0.111709E+11 | 28931.02 | 03-APR-06:30 |
May | 0.107701E+12 | 114379.84 | 31-MAY-15:00 | 0.110785E+11 | 13317.07 | 09-MAY-11:20 |
June | 0.120966E+12 | 145370.53 | 30-JUN-12:30 | 0.106294E+11 | 12669.21 | 02-JUN-11:00 |
July | 0.124085E+12 | 145355.24 | 11-JUL-15:00 | 0.101203E+11 | 11583.48 | 05-JUL-11:50 |
August | 0.119834E+12 | 139063.66 | 11-AUG-15:00 | 0.106160E+11 | 10885.24 | 01-AUG-11:20 |
September | 0.105742E+12 | 122312.15 | 25-SEP-06:10 | 0.989007E+10 | 14752.59 | 28-SEP-11:20 |
October | 0.155998E+12 | 228144.75 | 30-OCT-06:10 | 0.125293E+11 | 25936.22 | 31-OCT-07:10 |
November | 0.229724E+12 | 264342.46 | 27-NOV-07:10 | 0.586555E+11 | 168267.23 | 29-NOV-07:30 |
December | 0.264002E+12 | 260549.27 | 04-DEC-07:10 | 0.851674E+11 | 189513.51 | 15-DEC-07:30 |
Annual Sum or Average | 0.199059E+13 | 0.350877E+12 | ||||
Minimum of Months | 0.105742E+12 | 114379.84 | 0.989007E+10 | 10885.24 | ||
Maximum of Months | 0.264002E+12 | 286129.70 | 0.851674E+11 | 211066.48 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.260127E+11 | 0.106419E+11 | 0.641572E+11 | 0.109414E+10 | 0.699497E+10 | 1312252.65 | 0.151537E+12 | 2983378.50 | 0.00 | 0.00 | 0.351878E+10 | 0.00 | 0.00 |
February | 0.223967E+11 | 0.775815E+10 | 0.580684E+11 | 0.988605E+09 | 0.589570E+10 | 1186778.30 | 0.105088E+12 | 4333700.48 | 0.00 | 0.00 | 0.322473E+10 | 0.00 | 0.00 |
March | 0.254008E+11 | 0.649046E+10 | 0.666107E+11 | 0.114340E+10 | 0.565185E+10 | 1343621.24 | 0.704039E+11 | 13323673.14 | 0.00 | 0.00 | 0.380112E+10 | 0.00 | 0.00 |
April | 0.221941E+11 | 0.423980E+10 | 0.619407E+11 | 0.105049E+10 | 0.569357E+10 | 1267813.82 | 0.184503E+11 | 25769982.76 | 0.00 | 0.00 | 0.203578E+10 | 0.00 | 0.00 |
May | 0.237983E+11 | 0.257865E+10 | 0.653840E+11 | 0.111675E+10 | 0.963544E+10 | 1327936.95 | 0.176397E+10 | 0.318457E+10 | 0.00 | 0.00 | 0.238052E+09 | 0.00 | 0.00 |
June | 0.235844E+11 | 0.130285E+10 | 0.641577E+11 | 0.109943E+10 | 0.146150E+11 | 1296568.36 | 0.547286E+09 | 0.154752E+11 | 0.00 | 0.00 | 0.182963E+09 | 0.00 | 0.00 |
July | 0.221358E+11 | 0.188508E+10 | 0.631525E+11 | 0.106748E+10 | 0.143051E+11 | 1299182.41 | 0.441166E+09 | 0.208085E+11 | 0.00 | 0.00 | 0.288149E+09 | 0.00 | 0.00 |
August | 0.248018E+11 | 0.356412E+10 | 0.666107E+11 | 0.114299E+10 | 0.115561E+11 | 1343621.24 | 0.107468E+10 | 0.109430E+11 | 0.00 | 0.00 | 0.138856E+09 | 0.00 | 0.00 |
September | 0.224852E+11 | 0.539918E+10 | 0.619118E+11 | 0.105023E+10 | 0.546630E+10 | 1267813.82 | 0.774658E+10 | 0.188251E+09 | 0.00 | 0.00 | 0.149369E+10 | 0.00 | 0.00 |
October | 0.241299E+11 | 0.768420E+10 | 0.641717E+11 | 0.109182E+10 | 0.491748E+10 | 1312252.65 | 0.508469E+11 | 14309412.75 | 0.00 | 0.00 | 0.313999E+10 | 0.00 | 0.00 |
November | 0.251530E+11 | 0.952057E+10 | 0.627379E+11 | 0.107340E+10 | 0.610554E+10 | 1278270.02 | 0.121718E+12 | 2891352.64 | 0.00 | 0.00 | 0.341096E+10 | 0.00 | 0.00 |
December | 0.256686E+11 | 0.114888E+11 | 0.631380E+11 | 0.107135E+10 | 0.702222E+10 | 1299182.41 | 0.152131E+12 | 1530023.49 | 0.00 | 0.00 | 0.347957E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.287761E+12 | 0.725537E+11 | 0.762041E+12 | 0.129901E+11 | 0.978593E+11 | 15535293.87 | 0.681750E+12 | 0.506647E+11 | 0.00 | 0.00 | 0.249526E+11 | 0.00 | 0.00 |
Minimum of Months | 0.221358E+11 | 0.130285E+10 | 0.580684E+11 | 0.988605E+09 | 0.491748E+10 | 1186778.30 | 0.441166E+09 | 1530023.49 | 0.00 | 0.00 | 0.138856E+09 | 0.00 | 0.00 |
Maximum of Months | 0.260127E+11 | 0.114888E+11 | 0.666107E+11 | 0.114340E+10 | 0.146150E+11 | 1343621.24 | 0.152131E+12 | 0.208085E+11 | 0.00 | 0.00 | 0.380112E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.551746E+11 | 0.00 | 0.109518E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.328169E+11 | 0.00 | 0.991860E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.107227E+11 | 0.00 | 0.114353E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.642999E+09 | 0.00 | 0.105279E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 8382960.50 | 0.00 | 0.110701E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.106294E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.101203E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 6076864.63 | 0.00 | 0.106100E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 82213601.72 | 0.00 | 0.980785E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.224678E+10 | 0.00 | 0.102826E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.483400E+11 | 0.00 | 0.103155E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.745116E+11 | 0.00 | 0.106558E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.224552E+12 | 0.00 | 0.126325E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.980785E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.745116E+11 | 0.00 | 0.114353E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28079.40 | 02-JAN-08:09 | 5557.43 | 01-JAN-06:10 | 47562.27 | 02-JAN-08:09 | 928.21 | 02-JAN-08:20 | 8288.35 | 02-JAN-06:19 | 0.73 | 02-JAN-06:10 | 228592.13 | 02-JAN-06:19 |
February | 28079.40 | 01-FEB-08:09 | 5557.43 | 01-FEB-06:10 | 47562.27 | 01-FEB-08:09 | 928.21 | 01-FEB-08:20 | 7908.60 | 27-FEB-07:10 | 0.73 | 01-FEB-06:10 | 224657.15 | 27-FEB-07:10 |
March | 28079.40 | 01-MAR-08:09 | 5557.43 | 01-MAR-06:10 | 47562.27 | 01-MAR-08:09 | 928.21 | 17-MAR-07:19 | 6311.41 | 06-MAR-07:10 | 0.73 | 01-MAR-06:10 | 192778.46 | 06-MAR-07:10 |
April | 23984.00 | 03-APR-07:10 | 5557.43 | 01-APR-05:10 | 47562.27 | 03-APR-07:10 | 922.32 | 03-APR-07:19 | 12202.43 | 21-APR-15:00 | 0.73 | 03-APR-06:10 | 160958.70 | 03-APR-06:10 |
May | 23688.37 | 01-MAY-07:10 | 5557.43 | 01-MAY-21:10 | 47562.27 | 01-MAY-07:10 | 921.90 | 01-MAY-07:19 | 20748.55 | 31-MAY-15:09 | 0.73 | 01-MAY-05:10 | 22164.94 | 03-MAY-06:10 |
June | 23688.37 | 01-JUN-07:10 | 5557.43 | 01-JUN-22:49 | 47562.27 | 01-JUN-07:10 | 921.90 | 01-JUN-07:19 | 26132.81 | 20-JUN-15:30 | 0.73 | 01-JUN-05:10 | 16250.48 | 02-JUN-06:19 |
July | 23688.37 | 03-JUL-07:10 | 5557.43 | 11-JUL-22:00 | 47562.27 | 03-JUL-07:10 | 921.90 | 03-JUL-07:19 | 28452.94 | 12-JUL-15:09 | 0.73 | 01-JUL-05:10 | 15066.57 | 05-JUL-06:19 |
August | 23688.37 | 01-AUG-07:10 | 5557.43 | 01-AUG-21:00 | 47562.27 | 01-AUG-07:10 | 921.90 | 01-AUG-07:19 | 25756.82 | 10-AUG-15:39 | 0.73 | 30-AUG-07:10 | 30022.84 | 31-AUG-06:10 |
September | 27352.44 | 28-SEP-07:10 | 5557.43 | 01-SEP-05:10 | 47562.27 | 01-SEP-07:10 | 927.16 | 28-SEP-07:19 | 9457.40 | 08-SEP-15:30 | 0.73 | 08-SEP-11:09 | 78394.54 | 25-SEP-06:10 |
October | 28079.40 | 03-OCT-07:10 | 5557.43 | 01-OCT-05:10 | 47562.27 | 02-OCT-07:10 | 928.21 | 03-OCT-07:19 | 5905.18 | 30-OCT-06:10 | 0.73 | 03-OCT-07:10 | 182378.64 | 30-OCT-06:10 |
November | 28079.40 | 01-NOV-07:10 | 5557.43 | 01-NOV-05:10 | 47562.27 | 01-NOV-07:10 | 928.21 | 01-NOV-07:19 | 7618.97 | 27-NOV-06:10 | 0.73 | 01-NOV-05:10 | 217139.38 | 27-NOV-07:10 |
December | 28079.40 | 01-DEC-08:09 | 5557.43 | 01-DEC-06:10 | 47562.27 | 01-DEC-08:09 | 928.21 | 01-DEC-08:20 | 7205.68 | 04-DEC-06:10 | 0.73 | 01-DEC-07:10 | 213623.89 | 04-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 23688.37 | 5557.43 | 47562.27 | 921.90 | 5905.18 | 0.73 | 15066.57 | |||||||
Maximum of Months | 28079.40 | 5557.43 | 47562.27 | 928.21 | 28452.94 | 0.73 | 228592.13 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 506.92 | 07-JAN-07:10 | 0.00 | 0.00 | 2722.67 | 04-JAN-18:30 | 0.00 | 0.00 |
February | 537.44 | 11-FEB-07:10 | 0.00 | 0.00 | 2722.67 | 01-FEB-18:30 | 0.00 | 0.00 |
March | 641.23 | 18-MAR-06:10 | 0.00 | 0.00 | 2722.67 | 01-MAR-08:50 | 0.00 | 0.00 |
April | 1619.49 | 22-APR-13:00 | 0.00 | 0.00 | 2722.67 | 01-APR-16:19 | 0.00 | 0.00 |
May | 26499.64 | 31-MAY-15:00 | 0.00 | 0.00 | 2722.67 | 01-MAY-20:00 | 0.00 | 0.00 |
June | 48772.86 | 30-JUN-14:30 | 0.00 | 0.00 | 2722.67 | 20-JUN-15:50 | 0.00 | 0.00 |
July | 46730.92 | 11-JUL-15:00 | 0.00 | 0.00 | 2722.67 | 11-JUL-12:50 | 0.00 | 0.00 |
August | 42431.88 | 11-AUG-15:00 | 0.00 | 0.00 | 2722.67 | 30-AUG-06:19 | 0.00 | 0.00 |
September | 6918.71 | 07-SEP-15:00 | 0.00 | 0.00 | 2722.67 | 15-SEP-06:19 | 0.00 | 0.00 |
October | 482.32 | 28-OCT-06:10 | 0.00 | 0.00 | 2722.67 | 03-OCT-07:19 | 0.00 | 0.00 |
November | 506.89 | 04-NOV-06:10 | 0.00 | 0.00 | 2722.67 | 01-NOV-07:30 | 0.00 | 0.00 |
December | 505.35 | 23-DEC-07:10 | 0.00 | 0.00 | 2722.67 | 02-DEC-17:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 482.32 | 0.00 | 0.00 | 2722.67 | 0.00 | 0.00 | ||
Maximum of Months | 48772.86 | 0.00 | 0.00 | 2722.67 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 286129.70 | 02-JAN-08:09 | 28079.40 | 47562.27 | 5557.43 | 901.53 | 5775.93 | 0.73 | 195529.74 | 0.00 | 0.00 |
February | 272315.57 | 27-FEB-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 7908.60 | 0.73 | 224657.15 | 0.00 | 0.00 |
March | 238875.94 | 06-MAR-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 6311.41 | 0.73 | 192778.46 | 36.24 | 0.00 |
April | 206061.13 | 03-APR-06:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 5352.60 | 0.73 | 160958.70 | 0.00 | 0.00 |
May | 114379.84 | 31-MAY-15:00 | 23688.37 | 43769.98 | 0.00 | 920.43 | 19500.70 | 0.73 | 0.00 | 26499.64 | 0.00 |
June | 145370.53 | 30-JUN-12:30 | 23688.37 | 44099.74 | 0.00 | 920.56 | 25378.28 | 0.73 | 0.00 | 48560.18 | 0.00 |
July | 145355.24 | 11-JUL-15:00 | 23688.37 | 43769.98 | 0.00 | 920.43 | 27522.15 | 0.73 | 0.00 | 46730.92 | 0.00 |
August | 139063.66 | 11-AUG-15:00 | 23688.37 | 43769.98 | 0.00 | 920.43 | 25529.60 | 0.73 | 0.00 | 42431.88 | 0.00 |
September | 122312.15 | 25-SEP-06:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 3834.33 | 0.73 | 78394.54 | 333.45 | 0.00 |
October | 228144.75 | 30-OCT-06:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 5905.18 | 0.73 | 182378.64 | 111.10 | 0.00 |
November | 264342.46 | 27-NOV-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 7453.25 | 0.73 | 217139.38 | 0.00 | 0.00 |
December | 260549.27 | 04-DEC-07:10 | 9359.67 | 21853.28 | 5557.43 | 256.05 | 7175.55 | 0.73 | 213623.89 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 114379.84 | 9359.67 | 21853.28 | 0.00 | 256.05 | 3834.33 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 286129.70 | 28079.40 | 47562.27 | 5557.43 | 920.56 | 27522.15 | 0.73 | 224657.15 | 48560.18 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 202788.89 | 12-JAN-07:30 | 0.00 | 13382.77 | 02-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 181901.55 | 27-FEB-07:30 | 0.00 | 13396.13 | 27-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 160882.71 | 01-MAR-07:19 | 0.00 | 13364.68 | 02-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 20665.30 | 03-APR-06:30 | 0.00 | 13330.36 | 24-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 2282.93 | 16-MAY-08:39 | 0.00 | 13317.07 | 09-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 12669.21 | 02-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 11583.48 | 05-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 2129.87 | 31-AUG-06:10 | 0.00 | 10885.24 | 01-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 4044.15 | 28-SEP-11:20 | 0.00 | 10708.44 | 28-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 17556.01 | 31-OCT-06:00 | 0.00 | 11451.35 | 30-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 160031.51 | 29-NOV-07:30 | 0.00 | 12435.49 | 29-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 181253.26 | 15-DEC-07:30 | 0.00 | 13323.86 | 26-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10708.44 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 202788.89 | 0.00 | 13396.13 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 19.51 | 1.50 | 19.65 | 0.00 | 19.65 | 0.00 | 19.65 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.67 | 19.51 | 1.50 | 19.65 | 0.00 | 19.65 | 0.00 | 19.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.51 | 1.50 | 19.65 | 0.00 | 19.65 | 0.00 | 19.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 18.88 | 2.33 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
February | 0.50 | 19.24 | 0.50 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.43 | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
November | 0.83 | 18.78 | 0.67 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
December | 0.83 | 18.75 | 0.67 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
Annual Sum or Average | 5.50 | 18.89 | 4.33 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.43 | 2.33 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.17 | 18.81 | 7.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
February | 5.67 | 18.93 | 4.50 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
March | 1.50 | 19.06 | 1.33 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
April | 0.33 | 17.87 | 0.17 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.00 | 18.51 | 0.67 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 |
November | 6.50 | 18.66 | 4.67 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
December | 8.17 | 18.70 | 5.83 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
Annual Sum or Average | 32.33 | 18.77 | 24.17 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.17 | 19.06 | 7.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 99.00 | 16.34 | 52.67 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
February | 78.33 | 16.29 | 41.00 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
March | 43.83 | 17.03 | 21.33 | 17.65 | 0.00 | 17.65 | 0.00 | 17.65 |
April | 8.67 | 16.30 | 4.17 | 16.70 | 0.00 | 16.70 | 0.00 | 16.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.27 | 0.00 | 26.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22.17 | 16.21 | 10.83 | 16.58 | 0.00 | 16.58 | 0.00 | 16.58 |
November | 85.00 | 16.37 | 46.17 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 |
December | 104.67 | 16.57 | 54.33 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
Annual Sum or Average | 441.67 | 16.45 | 230.50 | 16.92 | 0.33 | 16.93 | 0.00 | 16.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.67 | 17.03 | 54.33 | 17.65 | 0.33 | 26.27 | 0.00 | 26.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 60.33 | 14.56 | 17.33 | 14.55 | 0.00 | 14.55 | 0.00 | 14.55 |
February | 44.83 | 14.69 | 11.00 | 14.71 | 0.00 | 14.71 | 0.00 | 14.71 |
March | 21.67 | 15.13 | 1.50 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 |
April | 4.83 | 15.18 | 0.50 | 15.15 | 0.00 | 15.15 | 0.00 | 15.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.15 | 2.67 | 28.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.43 | 1.17 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.99 | 4.00 | 28.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.44 | 0.33 | 27.44 |
September | 0.17 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 |
October | 14.17 | 15.03 | 2.83 | 15.03 | 0.00 | 15.03 | 0.00 | 15.03 |
November | 57.33 | 14.83 | 18.33 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
December | 64.00 | 14.64 | 16.33 | 14.61 | 0.00 | 14.61 | 0.00 | 14.61 |
Annual Sum or Average | 267.33 | 14.74 | 67.83 | 14.74 | 8.50 | 15.06 | 8.17 | 15.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 | 0.00 | 14.55 |
Maximum of Months | 64.00 | 17.24 | 18.33 | 17.24 | 4.17 | 28.15 | 4.00 | 28.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 56.67 | 14.63 | 16.50 | 14.63 | 0.00 | 14.63 | 0.00 | 14.63 |
February | 34.83 | 14.73 | 5.17 | 14.69 | 0.00 | 14.69 | 0.00 | 14.69 |
March | 12.67 | 15.33 | 0.67 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 |
April | 2.67 | 15.32 | 0.50 | 15.26 | 0.83 | 17.79 | 0.83 | 19.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.90 | 3.67 | 27.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.81 | 2.67 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.21 | 3.67 | 28.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.39 | 1.33 | 28.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
October | 11.50 | 15.15 | 2.33 | 15.09 | 0.00 | 15.09 | 0.00 | 15.09 |
November | 47.00 | 14.94 | 13.00 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
December | 59.83 | 14.69 | 15.17 | 14.65 | 0.00 | 14.65 | 0.00 | 14.65 |
Annual Sum or Average | 225.17 | 14.80 | 53.33 | 14.78 | 12.50 | 15.35 | 12.33 | 15.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.63 | 0.00 | 14.63 |
Maximum of Months | 59.83 | 15.33 | 16.50 | 15.31 | 3.67 | 28.39 | 3.67 | 28.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 61.17 | 14.55 | 17.83 | 14.54 | 0.00 | 14.54 | 0.00 | 14.54 |
February | 47.00 | 14.64 | 13.00 | 14.62 | 0.00 | 14.62 | 0.00 | 14.62 |
March | 22.00 | 15.14 | 2.83 | 15.14 | 0.00 | 15.14 | 0.00 | 15.14 |
April | 3.67 | 15.22 | 1.17 | 15.14 | 0.50 | 16.30 | 0.17 | 16.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.78 | 0.67 | 27.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.91 | 1.00 | 27.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.66 | 1.33 | 27.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.97 | 0.50 | 27.90 |
September | 0.17 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
October | 16.00 | 15.01 | 4.17 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
November | 55.83 | 14.81 | 18.33 | 14.82 | 0.00 | 14.82 | 0.00 | 14.82 |
December | 63.67 | 14.64 | 16.00 | 14.60 | 0.00 | 14.60 | 0.00 | 14.60 |
Annual Sum or Average | 269.50 | 14.73 | 73.33 | 14.71 | 13.17 | 15.19 | 3.67 | 15.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 | 0.00 | 14.54 |
Maximum of Months | 63.67 | 17.20 | 18.33 | 17.20 | 4.33 | 27.97 | 1.33 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 101.83 | 18.06 | 78.17 | 18.43 | 0.00 | 18.43 | 0.00 | 18.43 |
February | 76.17 | 18.13 | 57.33 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 |
March | 23.00 | 18.93 | 18.17 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
April | 2.33 | 19.25 | 2.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.42 | 0.00 | 26.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.00 | 18.86 | 1.33 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
November | 29.33 | 18.63 | 21.67 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
December | 49.50 | 18.59 | 38.67 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
Annual Sum or Average | 284.17 | 18.31 | 217.33 | 18.69 | 0.33 | 18.69 | 0.00 | 18.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.83 | 19.25 | 78.17 | 19.44 | 0.17 | 26.42 | 0.00 | 26.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 36.17 | 15.03 | 13.00 | 15.03 | 0.00 | 15.03 | 0.00 | 15.03 |
February | 19.67 | 15.31 | 4.50 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
March | 3.33 | 16.47 | 0.17 | 16.60 | 0.00 | 16.60 | 0.00 | 16.60 |
April | 0.17 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.73 | 2.33 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.50 | 0.17 | 26.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.55 | 3.33 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.36 | 0.17 | 27.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.41 | 0.50 | 27.41 |
October | 0.50 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
November | 9.33 | 15.79 | 1.17 | 15.92 | 0.00 | 15.92 | 0.00 | 15.92 |
December | 16.33 | 15.43 | 3.50 | 15.38 | 0.00 | 15.38 | 0.00 | 15.38 |
Annual Sum or Average | 85.50 | 15.32 | 22.33 | 15.33 | 7.67 | 16.14 | 6.50 | 16.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.03 | 0.00 | 15.03 |
Maximum of Months | 36.17 | 16.95 | 13.00 | 16.95 | 3.83 | 27.73 | 3.33 | 27.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 235.83 | 15.13 | 207.17 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
February | 134.17 | 14.94 | 120.17 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
March | 101.17 | 15.11 | 98.17 | 15.10 | 0.00 | 15.10 | 0.00 | 15.10 |
April | 37.33 | 17.04 | 37.33 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
May | 10.67 | 19.80 | 10.67 | 19.80 | 1.33 | 20.25 | 1.33 | 20.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.43 | 0.67 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.83 | 2.50 | 27.85 |
August | 3.00 | 18.66 | 3.00 | 18.66 | 1.67 | 20.69 | 1.33 | 21.79 |
September | 28.50 | 18.79 | 28.50 | 18.79 | 0.17 | 18.81 | 0.17 | 18.84 |
October | 64.83 | 15.96 | 64.50 | 15.95 | 0.00 | 15.95 | 0.00 | 15.95 |
November | 169.83 | 15.11 | 162.83 | 15.09 | 0.00 | 15.09 | 0.00 | 15.09 |
December | 257.83 | 15.52 | 236.00 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 |
Annual Sum or Average | 1043.17 | 15.47 | 968.33 | 15.48 | 6.50 | 15.52 | 6.00 | 15.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.92 | 0.00 | 14.92 |
Maximum of Months | 257.83 | 19.80 | 236.00 | 19.80 | 2.67 | 27.83 | 2.50 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 36.17 | 14.96 | 12.50 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
February | 22.50 | 15.10 | 4.83 | 15.09 | 0.00 | 15.09 | 0.00 | 15.09 |
March | 3.50 | 16.48 | 0.17 | 16.62 | 0.00 | 16.62 | 0.00 | 16.62 |
April | 0.17 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.48 | 0.00 | 27.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.56 | 0.33 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.42 | 0.00 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.63 | 0.17 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.50 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 |
November | 8.33 | 15.63 | 0.17 | 15.62 | 0.00 | 15.62 | 0.00 | 15.62 |
December | 15.83 | 15.37 | 3.33 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
Annual Sum or Average | 87.00 | 15.21 | 21.00 | 15.16 | 4.00 | 15.60 | 0.50 | 15.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 36.17 | 17.07 | 12.50 | 17.07 | 1.67 | 27.63 | 0.33 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 58.00 | 16.55 | 32.83 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 |
February | 35.33 | 16.87 | 20.00 | 17.30 | 0.00 | 17.30 | 0.00 | 17.30 |
March | 9.17 | 18.43 | 5.83 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
April | 0.67 | 18.79 | 0.50 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 26.55 | 0.00 | 26.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.47 | 0.00 | 26.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3.50 | 17.87 | 1.83 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 |
November | 28.83 | 17.34 | 18.50 | 17.75 | 0.00 | 17.75 | 0.00 | 17.75 |
December | 40.67 | 17.32 | 24.67 | 17.78 | 0.00 | 17.78 | 0.00 | 17.78 |
Annual Sum or Average | 176.17 | 17.05 | 104.17 | 17.49 | 2.33 | 17.56 | 0.00 | 17.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 58.00 | 18.79 | 32.83 | 19.12 | 1.83 | 26.55 | 0.00 | 26.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 38.00 | 14.84 | 13.00 | 14.81 | 0.00 | 14.81 | 0.00 | 14.81 |
February | 18.00 | 15.09 | 3.83 | 15.06 | 0.00 | 15.06 | 0.00 | 15.06 |
March | 3.50 | 16.61 | 0.17 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
April | 0.17 | 16.54 | 0.00 | 16.54 | 0.17 | 21.91 | 0.17 | 23.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.35 | 2.67 | 28.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.14 | 1.17 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.82 | 4.00 | 27.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.68 | 0.33 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.54 | 0.83 | 27.54 |
October | 1.50 | 15.95 | 0.00 | 15.95 | 0.00 | 15.95 | 0.00 | 15.95 |
November | 16.17 | 15.28 | 5.00 | 15.23 | 0.00 | 15.23 | 0.00 | 15.23 |
December | 24.67 | 15.15 | 6.17 | 15.09 | 0.00 | 15.09 | 0.00 | 15.09 |
Annual Sum or Average | 102.00 | 15.11 | 28.17 | 15.06 | 10.67 | 16.02 | 9.17 | 16.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 | 0.00 | 14.81 |
Maximum of Months | 38.00 | 16.61 | 13.00 | 16.74 | 4.50 | 28.35 | 4.00 | 28.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.00 | 14.93 | 9.83 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
February | 11.33 | 15.21 | 2.33 | 15.17 | 0.00 | 15.17 | 0.00 | 15.17 |
March | 2.50 | 16.78 | 0.17 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 |
April | 0.17 | 16.89 | 0.00 | 16.89 | 1.33 | 26.46 | 1.33 | 27.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.88 | 4.50 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.85 | 2.67 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.12 | 3.50 | 28.14 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.11 | 2.17 | 28.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.57 | 0.50 | 27.57 |
October | 0.83 | 16.45 | 0.00 | 16.45 | 0.00 | 16.45 | 0.00 | 16.45 |
November | 10.50 | 15.52 | 1.83 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
December | 19.67 | 15.23 | 4.83 | 15.16 | 0.00 | 15.16 | 0.00 | 15.16 |
Annual Sum or Average | 77.00 | 15.21 | 19.00 | 15.15 | 14.83 | 16.86 | 14.67 | 18.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.89 | 0.00 | 14.89 |
Maximum of Months | 32.00 | 16.89 | 9.83 | 16.94 | 4.50 | 28.12 | 4.50 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 38.17 | 14.84 | 13.00 | 14.80 | 0.00 | 14.80 | 0.00 | 14.80 |
February | 19.83 | 15.07 | 4.33 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 |
March | 4.00 | 16.61 | 0.17 | 16.72 | 0.00 | 16.72 | 0.00 | 16.72 |
April | 0.17 | 16.71 | 0.00 | 16.71 | 0.67 | 25.45 | 0.17 | 25.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.85 | 1.00 | 27.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.90 | 1.00 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.68 | 1.17 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.97 | 0.67 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.00 | 27.28 |
October | 1.50 | 15.94 | 0.00 | 15.94 | 0.00 | 15.94 | 0.00 | 15.94 |
November | 15.67 | 15.29 | 4.50 | 15.24 | 0.00 | 15.24 | 0.00 | 15.24 |
December | 24.17 | 15.16 | 6.17 | 15.09 | 0.00 | 15.09 | 0.00 | 15.09 |
Annual Sum or Average | 103.50 | 15.11 | 28.17 | 15.05 | 13.33 | 16.22 | 4.00 | 16.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | 0.00 | 14.80 |
Maximum of Months | 38.17 | 16.71 | 13.00 | 16.72 | 4.33 | 27.97 | 1.17 | 27.93 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.17 | 308.33 | 20.94 | 308.33 | 20.84 |
February | 454.00 | 21.74 | 169.83 | 21.45 | 169.83 | 21.29 |
March | 514.00 | 22.66 | 52.00 | 22.52 | 52.00 | 22.40 |
April | 437.17 | 23.63 | 2.00 | 23.62 | 2.00 | 23.60 |
May | 116.83 | 24.01 | 32.33 | 24.45 | 0.00 | 24.45 |
June | 0.00 | 0.00 | 211.33 | 24.90 | 0.00 | 24.90 |
July | 0.00 | 0.00 | 381.00 | 24.61 | 0.00 | 24.61 |
August | 19.50 | 24.00 | 264.00 | 24.65 | 0.00 | 24.65 |
September | 176.17 | 23.86 | 50.33 | 24.30 | 0.00 | 24.30 |
October | 498.00 | 23.26 | 5.67 | 23.23 | 5.67 | 23.20 |
November | 489.00 | 21.78 | 181.83 | 21.54 | 181.83 | 21.40 |
December | 497.00 | 21.23 | 344.83 | 21.06 | 344.83 | 20.99 |
Annual Sum or Average | 3703.67 | 22.34 | 2003.50 | 22.45 | 1064.50 | 22.18 |
Minimum of Months | 0.00 | 0.00 | 2.00 | 20.94 | 0.00 | 20.84 |
Maximum of Months | 514.00 | 24.01 | 381.00 | 24.90 | 344.83 | 24.90 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.39 | 471.83 | 20.36 | 471.83 | 20.35 |
February | 454.00 | 20.69 | 345.33 | 20.57 | 345.33 | 20.53 |
March | 514.00 | 21.28 | 255.67 | 21.11 | 255.67 | 21.02 |
April | 480.00 | 22.69 | 54.67 | 22.50 | 54.67 | 22.35 |
May | 322.50 | 23.76 | 2.33 | 23.77 | 0.00 | 23.77 |
June | 21.17 | 23.86 | 132.17 | 24.65 | 0.00 | 24.65 |
July | 0.00 | 0.00 | 284.17 | 24.51 | 0.00 | 24.51 |
August | 74.33 | 23.73 | 145.33 | 24.34 | 0.00 | 24.34 |
September | 394.67 | 23.14 | 0.00 | 23.14 | 0.00 | 23.14 |
October | 502.00 | 21.57 | 134.50 | 21.37 | 134.50 | 21.24 |
November | 489.00 | 20.60 | 433.50 | 20.55 | 433.50 | 20.53 |
December | 497.00 | 20.44 | 491.00 | 20.43 | 491.00 | 20.43 |
Annual Sum or Average | 4250.67 | 21.55 | 2750.50 | 21.46 | 2186.50 | 21.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 20.36 | 0.00 | 20.35 |
Maximum of Months | 514.00 | 23.86 | 491.00 | 24.65 | 491.00 | 24.65 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.05 | 502.00 | 20.05 | 502.00 | 20.05 |
February | 454.00 | 20.21 | 427.33 | 20.17 | 427.33 | 20.16 |
March | 514.00 | 20.71 | 403.33 | 20.61 | 403.33 | 20.57 |
April | 485.00 | 21.97 | 149.33 | 21.61 | 149.33 | 21.38 |
May | 386.67 | 23.46 | 0.83 | 23.47 | 0.00 | 23.47 |
June | 73.17 | 23.73 | 95.50 | 24.24 | 0.00 | 24.24 |
July | 19.67 | 23.45 | 235.00 | 24.38 | 0.00 | 24.38 |
August | 147.00 | 23.32 | 96.00 | 23.80 | 0.00 | 23.80 |
September | 475.00 | 22.47 | 34.17 | 22.35 | 34.17 | 22.24 |
October | 502.00 | 20.77 | 327.17 | 20.60 | 327.17 | 20.52 |
November | 489.00 | 20.11 | 488.83 | 20.11 | 488.83 | 20.11 |
December | 497.00 | 20.05 | 497.00 | 20.05 | 497.00 | 20.05 |
Annual Sum or Average | 4544.50 | 21.15 | 3256.50 | 20.99 | 2829.17 | 20.78 |
Minimum of Months | 19.67 | 20.05 | 0.83 | 20.05 | 0.00 | 20.05 |
Maximum of Months | 514.00 | 23.73 | 502.00 | 24.38 | 502.00 | 24.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.60 | 502.00 | 19.60 | 502.00 | 19.60 |
February | 454.00 | 19.72 | 454.00 | 19.72 | 454.00 | 19.72 |
March | 514.00 | 20.07 | 501.50 | 20.06 | 501.50 | 20.06 |
April | 485.00 | 21.00 | 267.50 | 20.68 | 267.50 | 20.52 |
May | 400.33 | 23.06 | 9.83 | 23.00 | 9.83 | 22.94 |
June | 57.00 | 23.35 | 170.50 | 24.16 | 0.00 | 24.16 |
July | 33.17 | 23.37 | 322.17 | 24.28 | 0.00 | 24.28 |
August | 221.17 | 22.86 | 99.67 | 23.25 | 5.67 | 23.20 |
September | 482.00 | 21.49 | 139.50 | 21.26 | 139.50 | 21.12 |
October | 502.00 | 20.08 | 451.67 | 20.02 | 451.67 | 20.00 |
November | 489.00 | 19.65 | 489.00 | 19.65 | 489.00 | 19.65 |
December | 497.00 | 19.58 | 497.00 | 19.58 | 497.00 | 19.58 |
Annual Sum or Average | 4636.67 | 20.59 | 3904.33 | 20.55 | 3317.67 | 20.34 |
Minimum of Months | 33.17 | 19.58 | 9.83 | 19.58 | 0.00 | 19.58 |
Maximum of Months | 514.00 | 23.37 | 502.00 | 24.28 | 502.00 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.69 | 502.00 | 19.69 | 502.00 | 19.69 |
February | 454.00 | 19.82 | 452.67 | 19.82 | 452.67 | 19.82 |
March | 513.33 | 20.38 | 433.67 | 20.25 | 433.67 | 20.21 |
April | 433.33 | 21.49 | 198.00 | 21.13 | 190.17 | 20.90 |
May | 218.67 | 23.04 | 116.50 | 23.52 | 11.33 | 23.58 |
June | 66.00 | 23.39 | 296.33 | 24.18 | 3.67 | 24.20 |
July | 60.83 | 24.26 | 380.67 | 24.44 | 17.83 | 24.53 |
August | 155.83 | 22.90 | 235.67 | 23.70 | 3.17 | 23.69 |
September | 418.83 | 21.61 | 109.50 | 21.48 | 96.50 | 21.30 |
October | 502.00 | 20.23 | 413.17 | 20.11 | 413.17 | 20.07 |
November | 489.00 | 19.72 | 489.00 | 19.72 | 489.00 | 19.72 |
December | 497.00 | 19.67 | 497.00 | 19.67 | 497.00 | 19.67 |
Annual Sum or Average | 4310.83 | 20.62 | 4124.17 | 20.81 | 3110.17 | 20.57 |
Minimum of Months | 60.83 | 19.67 | 109.50 | 19.67 | 3.17 | 19.67 |
Maximum of Months | 513.33 | 24.26 | 502.00 | 24.44 | 502.00 | 24.53 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.72 | 501.33 | 19.72 | 501.33 | 19.72 |
February | 454.00 | 20.09 | 416.00 | 20.00 | 416.00 | 19.96 |
March | 475.00 | 20.70 | 351.33 | 20.44 | 351.33 | 20.34 |
April | 346.67 | 21.42 | 220.67 | 21.41 | 161.67 | 21.15 |
May | 265.33 | 22.63 | 131.50 | 23.16 | 20.33 | 23.15 |
June | 124.67 | 23.28 | 251.67 | 24.01 | 10.00 | 24.08 |
July | 110.17 | 23.52 | 326.83 | 24.22 | 14.67 | 24.31 |
August | 195.33 | 22.82 | 238.50 | 23.65 | 11.67 | 23.68 |
September | 370.00 | 21.60 | 151.50 | 21.73 | 91.83 | 21.54 |
October | 484.67 | 20.43 | 375.17 | 20.27 | 371.67 | 20.20 |
November | 489.00 | 19.79 | 483.50 | 19.77 | 483.50 | 19.77 |
December | 497.00 | 19.68 | 497.00 | 19.68 | 497.00 | 19.68 |
Annual Sum or Average | 4313.83 | 20.77 | 3945.00 | 20.93 | 2931.00 | 20.68 |
Minimum of Months | 110.17 | 19.68 | 131.50 | 19.68 | 10.00 | 19.68 |
Maximum of Months | 502.00 | 23.52 | 501.33 | 24.22 | 501.33 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.69 | 502.00 | 19.69 | 502.00 | 19.69 |
February | 454.00 | 19.81 | 452.17 | 19.81 | 452.17 | 19.81 |
March | 514.00 | 20.22 | 472.00 | 20.16 | 472.00 | 20.14 |
April | 420.33 | 21.12 | 236.33 | 20.87 | 218.50 | 20.68 |
May | 328.00 | 22.52 | 65.83 | 22.70 | 17.50 | 22.61 |
June | 125.33 | 23.13 | 213.67 | 23.97 | 5.17 | 24.02 |
July | 108.67 | 23.20 | 305.33 | 24.08 | 6.00 | 24.12 |
August | 249.00 | 22.66 | 170.17 | 23.29 | 8.17 | 23.27 |
September | 453.83 | 21.43 | 139.00 | 21.28 | 128.67 | 21.13 |
October | 502.00 | 20.12 | 438.33 | 20.04 | 438.33 | 20.02 |
November | 489.00 | 19.72 | 489.00 | 19.72 | 489.00 | 19.72 |
December | 497.00 | 19.67 | 497.00 | 19.67 | 497.00 | 19.67 |
Annual Sum or Average | 4643.17 | 20.64 | 3980.83 | 20.69 | 3234.50 | 20.47 |
Minimum of Months | 108.67 | 19.67 | 65.83 | 19.67 | 5.17 | 19.67 |
Maximum of Months | 514.00 | 23.20 | 502.00 | 24.08 | 502.00 | 24.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.61 | 502.00 | 19.61 | 502.00 | 19.61 |
February | 454.00 | 19.72 | 454.00 | 19.72 | 454.00 | 19.72 |
March | 514.00 | 20.20 | 510.50 | 20.19 | 510.50 | 20.19 |
April | 485.00 | 20.93 | 291.33 | 20.72 | 291.33 | 20.63 |
May | 502.50 | 23.11 | 0.00 | 23.11 | 0.00 | 23.11 |
June | 85.67 | 23.69 | 92.33 | 24.09 | 0.00 | 24.09 |
July | 16.00 | 23.51 | 274.33 | 24.36 | 0.00 | 24.36 |
August | 174.50 | 23.30 | 79.00 | 23.67 | 0.00 | 23.67 |
September | 482.00 | 22.26 | 49.17 | 22.12 | 49.17 | 22.00 |
October | 502.00 | 20.59 | 396.00 | 20.50 | 396.00 | 20.46 |
November | 489.00 | 19.84 | 489.00 | 19.84 | 489.00 | 19.84 |
December | 497.00 | 19.70 | 497.00 | 19.70 | 497.00 | 19.70 |
Annual Sum or Average | 4703.67 | 20.83 | 3634.67 | 20.69 | 3189.00 | 20.48 |
Minimum of Months | 16.00 | 19.61 | 0.00 | 19.61 | 0.00 | 19.61 |
Maximum of Months | 514.00 | 23.69 | 510.50 | 24.36 | 510.50 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.79 | 502.00 | 19.79 | 502.00 | 19.79 |
February | 454.00 | 19.92 | 454.00 | 19.92 | 454.00 | 19.92 |
March | 514.00 | 20.53 | 454.67 | 20.45 | 454.67 | 20.42 |
April | 456.50 | 21.87 | 170.00 | 21.53 | 166.00 | 21.31 |
May | 201.50 | 23.42 | 91.33 | 23.85 | 2.17 | 23.88 |
June | 42.83 | 23.47 | 272.67 | 24.30 | 0.17 | 24.30 |
July | 23.00 | 25.28 | 415.67 | 24.56 | 12.17 | 24.63 |
August | 81.67 | 23.46 | 285.83 | 24.18 | 0.33 | 24.18 |
September | 365.17 | 22.46 | 47.83 | 22.61 | 18.83 | 22.53 |
October | 502.00 | 20.85 | 309.17 | 20.67 | 309.17 | 20.59 |
November | 489.00 | 19.89 | 489.00 | 19.89 | 489.00 | 19.89 |
December | 497.00 | 19.78 | 497.00 | 19.78 | 497.00 | 19.78 |
Annual Sum or Average | 4128.67 | 20.82 | 3989.17 | 21.04 | 2905.50 | 20.78 |
Minimum of Months | 23.00 | 19.78 | 47.83 | 19.78 | 0.17 | 19.78 |
Maximum of Months | 514.00 | 25.28 | 502.00 | 24.56 | 502.00 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 17.48 | 502.00 | 17.48 | 502.00 | 17.48 |
February | 454.00 | 18.52 | 444.00 | 18.49 | 444.00 | 18.48 |
March | 514.00 | 19.48 | 437.83 | 19.32 | 437.83 | 19.26 |
April | 418.33 | 21.24 | 160.50 | 20.98 | 140.50 | 20.70 |
May | 332.00 | 22.33 | 61.33 | 22.67 | 10.33 | 22.62 |
June | 148.50 | 22.66 | 187.50 | 23.70 | 0.67 | 23.71 |
July | 90.00 | 22.73 | 337.67 | 24.14 | 8.67 | 24.20 |
August | 189.00 | 22.52 | 236.17 | 23.62 | 8.17 | 23.64 |
September | 380.50 | 21.70 | 92.50 | 21.91 | 38.00 | 21.72 |
October | 496.33 | 20.24 | 327.50 | 19.95 | 326.83 | 19.83 |
November | 489.00 | 17.94 | 489.00 | 17.94 | 489.00 | 17.94 |
December | 497.00 | 17.20 | 497.00 | 17.20 | 497.00 | 17.20 |
Annual Sum or Average | 4510.67 | 19.68 | 3773.00 | 19.72 | 2903.00 | 19.36 |
Minimum of Months | 90.00 | 17.20 | 61.33 | 17.20 | 0.67 | 17.20 |
Maximum of Months | 514.00 | 22.73 | 502.00 | 24.14 | 502.00 | 24.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.79 | 502.00 | 19.79 | 502.00 | 19.79 |
February | 454.00 | 19.88 | 454.00 | 19.88 | 454.00 | 19.88 |
March | 514.00 | 20.32 | 493.00 | 20.29 | 493.00 | 20.28 |
April | 444.67 | 21.55 | 188.83 | 21.24 | 185.17 | 21.06 |
May | 378.83 | 22.99 | 14.17 | 23.05 | 2.33 | 23.04 |
June | 93.50 | 23.38 | 186.83 | 24.15 | 0.33 | 24.16 |
July | 43.83 | 23.32 | 323.67 | 24.29 | 0.17 | 24.29 |
August | 140.00 | 23.16 | 193.67 | 23.89 | 0.17 | 23.89 |
September | 438.83 | 22.25 | 41.17 | 22.17 | 36.17 | 22.07 |
October | 502.00 | 20.62 | 383.33 | 20.52 | 383.33 | 20.48 |
November | 489.00 | 19.89 | 489.00 | 19.89 | 489.00 | 19.89 |
December | 497.00 | 19.78 | 497.00 | 19.78 | 497.00 | 19.78 |
Annual Sum or Average | 4497.67 | 20.86 | 3766.67 | 20.87 | 3042.67 | 20.64 |
Minimum of Months | 43.83 | 19.78 | 14.17 | 19.78 | 0.17 | 19.78 |
Maximum of Months | 514.00 | 23.38 | 502.00 | 24.29 | 502.00 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.77 | 502.00 | 19.77 | 502.00 | 19.77 |
February | 454.00 | 19.89 | 453.50 | 19.89 | 453.50 | 19.89 |
March | 514.00 | 20.33 | 476.50 | 20.29 | 476.50 | 20.28 |
April | 485.00 | 21.58 | 187.33 | 21.20 | 187.33 | 20.99 |
May | 357.00 | 23.57 | 1.00 | 23.57 | 0.00 | 23.57 |
June | 17.83 | 23.60 | 201.83 | 24.45 | 0.00 | 24.45 |
July | 3.67 | 23.62 | 361.67 | 24.45 | 0.00 | 24.45 |
August | 128.00 | 23.25 | 130.17 | 23.81 | 0.00 | 23.81 |
September | 474.00 | 22.26 | 55.17 | 22.10 | 55.17 | 21.97 |
October | 502.00 | 20.46 | 386.83 | 20.34 | 386.83 | 20.30 |
November | 489.00 | 19.80 | 489.00 | 19.80 | 489.00 | 19.80 |
December | 497.00 | 19.75 | 497.00 | 19.75 | 497.00 | 19.75 |
Annual Sum or Average | 4423.50 | 20.82 | 3742.00 | 20.81 | 3047.33 | 20.58 |
Minimum of Months | 3.67 | 19.75 | 1.00 | 19.75 | 0.00 | 19.75 |
Maximum of Months | 514.00 | 23.62 | 502.00 | 24.45 | 502.00 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.61 | 427.00 | 19.61 | 427.00 | 19.61 |
February | 385.00 | 19.80 | 380.17 | 19.79 | 380.17 | 19.79 |
March | 432.00 | 20.56 | 344.00 | 20.42 | 344.00 | 20.37 |
April | 360.00 | 21.77 | 124.50 | 21.50 | 112.83 | 21.27 |
May | 182.17 | 23.42 | 106.83 | 23.93 | 9.17 | 24.03 |
June | 40.50 | 23.87 | 236.33 | 24.41 | 4.50 | 24.45 |
July | 28.00 | 25.42 | 333.00 | 24.67 | 16.17 | 24.77 |
August | 108.33 | 23.20 | 208.17 | 23.99 | 1.50 | 24.00 |
September | 343.50 | 22.07 | 56.67 | 22.16 | 33.33 | 22.05 |
October | 426.00 | 20.49 | 306.17 | 20.34 | 306.17 | 20.28 |
November | 417.00 | 19.62 | 417.00 | 19.62 | 417.00 | 19.62 |
December | 422.00 | 19.56 | 422.00 | 19.56 | 422.00 | 19.56 |
Annual Sum or Average | 3571.50 | 20.70 | 3361.83 | 20.91 | 2473.83 | 20.65 |
Minimum of Months | 28.00 | 19.56 | 56.67 | 19.56 | 1.50 | 19.56 |
Maximum of Months | 432.00 | 25.42 | 427.00 | 24.67 | 427.00 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.86 | 497.67 | 19.85 | 497.67 | 19.85 |
February | 450.17 | 20.35 | 390.50 | 20.23 | 390.50 | 20.18 |
March | 459.83 | 20.98 | 306.83 | 20.73 | 304.67 | 20.62 |
April | 328.50 | 21.91 | 167.67 | 21.99 | 98.33 | 21.73 |
May | 233.00 | 23.17 | 125.50 | 23.68 | 10.50 | 23.75 |
June | 80.67 | 23.74 | 274.17 | 24.26 | 9.67 | 24.33 |
July | 59.00 | 24.21 | 366.33 | 24.44 | 14.50 | 24.53 |
August | 136.50 | 23.25 | 264.00 | 24.03 | 7.67 | 24.09 |
September | 336.67 | 22.16 | 105.67 | 22.49 | 28.33 | 22.38 |
October | 480.50 | 20.90 | 286.33 | 20.68 | 282.17 | 20.57 |
November | 489.00 | 19.97 | 474.50 | 19.94 | 474.50 | 19.93 |
December | 497.00 | 19.80 | 497.00 | 19.80 | 497.00 | 19.80 |
Annual Sum or Average | 4052.83 | 20.97 | 3756.17 | 21.19 | 2615.50 | 20.92 |
Minimum of Months | 59.00 | 19.80 | 105.67 | 19.80 | 7.67 | 19.80 |
Maximum of Months | 502.00 | 24.21 | 497.67 | 24.44 | 497.67 | 24.53 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.82 | 502.00 | 19.82 | 502.00 | 19.82 |
February | 454.00 | 19.94 | 449.17 | 19.93 | 449.17 | 19.93 |
March | 514.00 | 20.47 | 438.17 | 20.38 | 438.17 | 20.35 |
April | 410.50 | 21.59 | 172.67 | 21.36 | 150.67 | 21.14 |
May | 288.00 | 23.04 | 53.50 | 23.28 | 2.83 | 23.28 |
June | 72.17 | 23.53 | 234.17 | 24.27 | 4.83 | 24.31 |
July | 48.50 | 23.62 | 345.67 | 24.32 | 5.17 | 24.36 |
August | 169.00 | 23.01 | 195.33 | 23.74 | 2.50 | 23.77 |
September | 439.67 | 22.01 | 61.33 | 21.95 | 49.00 | 21.83 |
October | 502.00 | 20.47 | 383.83 | 20.35 | 383.83 | 20.31 |
November | 489.00 | 19.83 | 489.00 | 19.83 | 489.00 | 19.83 |
December | 497.00 | 19.78 | 497.00 | 19.78 | 497.00 | 19.78 |
Annual Sum or Average | 4385.83 | 20.80 | 3821.83 | 20.89 | 2974.17 | 20.66 |
Minimum of Months | 48.50 | 19.78 | 53.50 | 19.78 | 2.50 | 19.78 |
Maximum of Months | 514.00 | 23.62 | 502.00 | 24.32 | 502.00 | 24.36 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.16662 | 14.51786 | -0.6140 | 14.54769 |
February | 454.00000 | 21.74112 | 15.88718 | -0.4531 | 10.80084 |
March | 514.00000 | 22.66423 | 16.54988 | -0.2206 | 6.99253 |
April | 485.00000 | 23.77917 | 16.05563 | 0.09086 | 5.94158 |
May | 508.00000 | 24.30454 | 20.88947 | -0.5580 | 11.82267 |
June | 496.00000 | 24.40013 | 32.84151 | -0.4057 | 8.97243 |
July | 497.00000 | 24.46480 | 40.97404 | -0.3277 | 7.87144 |
August | 514.00000 | 24.38058 | 36.16484 | -0.3990 | 8.90511 |
September | 485.00000 | 24.21090 | 27.16235 | -0.5912 | 13.05905 |
October | 502.00000 | 23.27026 | 21.77125 | -0.0255 | 5.91575 |
November | 489.00000 | 21.77728 | 14.91185 | -0.4556 | 10.26542 |
December | 497.00000 | 21.22672 | 12.37168 | -0.6073 | 13.42527 |
Annual Sum or Average | 5943.00000 | 23.12653 | 22.57983 | -0.3803 | 9.86428 |
Minimum of Months | 454.00000 | 21.16662 | 12.37168 | -0.6140 | 5.91575 |
Maximum of Months | 514.00000 | 24.46480 | 40.97404 | 0.09086 | 14.54769 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.39056 | 17.01279 | -0.8001 | 20.15651 |
February | 454.00000 | 20.68681 | 18.54937 | -0.6978 | 16.76073 |
March | 514.00000 | 21.28095 | 19.04210 | -0.5261 | 11.60000 |
April | 485.00000 | 22.71550 | 17.84913 | -0.1508 | 7.20879 |
May | 508.00000 | 23.96546 | 21.99522 | -0.6875 | 15.44976 |
June | 496.00000 | 24.23548 | 33.68837 | -0.4795 | 10.11789 |
July | 497.00000 | 24.29339 | 41.93690 | -0.4041 | 8.77178 |
August | 514.00000 | 24.15994 | 37.34685 | -0.4992 | 10.72371 |
September | 485.00000 | 23.34397 | 29.98170 | -0.8933 | 23.42715 |
October | 502.00000 | 21.57223 | 25.14581 | -0.4111 | 9.73263 |
November | 489.00000 | 20.60106 | 17.97930 | -0.7317 | 17.30948 |
December | 497.00000 | 20.43853 | 14.30384 | -0.8062 | 19.77570 |
Annual Sum or Average | 5943.00000 | 22.32097 | 24.63292 | -0.5897 | 14.21267 |
Minimum of Months | 454.00000 | 20.39056 | 14.30384 | -0.8933 | 7.20879 |
Maximum of Months | 514.00000 | 24.29339 | 41.93690 | -0.1508 | 23.42715 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.05222 | 17.63342 | -0.9224 | 25.14203 |
February | 454.00000 | 20.20673 | 19.49692 | -0.8487 | 22.47024 |
March | 514.00000 | 20.71222 | 19.41234 | -0.6954 | 16.59604 |
April | 485.00000 | 21.97283 | 18.33785 | -0.3402 | 10.08608 |
May | 508.00000 | 23.63705 | 22.61630 | -0.8067 | 19.86325 |
June | 496.00000 | 24.12968 | 33.79666 | -0.5192 | 10.97323 |
July | 497.00000 | 24.19035 | 42.07760 | -0.4440 | 9.44156 |
August | 514.00000 | 23.92462 | 37.93192 | -0.5911 | 13.28564 |
September | 485.00000 | 22.49715 | 31.72375 | -1.1927 | 36.40407 |
October | 502.00000 | 20.76935 | 26.28474 | -0.6322 | 15.13156 |
November | 489.00000 | 20.10606 | 18.99769 | -0.8915 | 23.79375 |
December | 497.00000 | 20.04852 | 14.90198 | -0.9420 | 25.63075 |
Annual Sum or Average | 5943.00000 | 21.86978 | 25.32631 | -0.7341 | 19.00136 |
Minimum of Months | 454.00000 | 20.04852 | 14.90198 | -1.1927 | 9.44156 |
Maximum of Months | 514.00000 | 24.19035 | 42.07760 | -0.3402 | 36.40407 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.59768 | 17.74919 | -1.1528 | 34.71251 |
February | 454.00000 | 19.71928 | 19.89980 | -1.0781 | 31.70319 |
March | 514.00000 | 20.07485 | 19.94464 | -0.9304 | 25.41895 |
April | 485.00000 | 21.00199 | 19.11366 | -0.5873 | 15.74649 |
May | 508.00000 | 23.27220 | 23.14537 | -0.9149 | 24.51364 |
June | 496.00000 | 24.10827 | 33.97412 | -0.4796 | 10.45361 |
July | 497.00000 | 24.19708 | 42.01054 | -0.4061 | 9.02523 |
August | 514.00000 | 23.57129 | 39.15252 | -0.6985 | 17.41767 |
September | 485.00000 | 21.50765 | 33.79475 | -1.5382 | 52.98823 |
October | 502.00000 | 20.07909 | 26.78645 | -0.8642 | 23.08666 |
November | 489.00000 | 19.64849 | 19.35929 | -1.1230 | 33.45642 |
December | 497.00000 | 19.57634 | 14.83510 | -1.1829 | 35.93817 |
Annual Sum or Average | 5943.00000 | 21.38063 | 25.87177 | -0.9106 | 26.09923 |
Minimum of Months | 454.00000 | 19.57634 | 14.83510 | -1.5382 | 9.02523 |
Maximum of Months | 514.00000 | 24.19708 | 42.01054 | -0.4061 | 52.98823 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.69490 | 17.79481 | -1.1346 | 33.84766 |
February | 454.00000 | 19.82104 | 19.74174 | -1.0364 | 29.96410 |
March | 514.00000 | 20.38005 | 19.43262 | -0.7993 | 21.20748 |
April | 485.00000 | 21.77593 | 17.86429 | -0.3543 | 12.52451 |
May | 508.00000 | 23.68664 | 21.73201 | -0.6439 | 17.30962 |
June | 496.00000 | 24.12782 | 33.59739 | -0.3641 | 9.26831 |
July | 497.00000 | 24.26941 | 41.42203 | -0.2658 | 8.37101 |
August | 514.00000 | 23.78207 | 38.08856 | -0.5286 | 13.35463 |
September | 485.00000 | 21.99540 | 32.53245 | -1.3269 | 44.15755 |
October | 502.00000 | 20.22780 | 26.34528 | -0.8055 | 21.25100 |
November | 489.00000 | 19.72010 | 19.31198 | -1.1083 | 32.77768 |
December | 497.00000 | 19.66846 | 15.01586 | -1.1687 | 35.23617 |
Annual Sum or Average | 5943.00000 | 21.61347 | 25.29476 | -0.7917 | 23.15504 |
Minimum of Months | 454.00000 | 19.66846 | 15.01586 | -1.3269 | 8.37101 |
Maximum of Months | 514.00000 | 24.26941 | 41.42203 | -0.2658 | 44.15755 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.71960 | 17.34940 | -1.1078 | 32.81123 |
February | 454.00000 | 20.09356 | 18.97082 | -0.9274 | 26.30371 |
March | 514.00000 | 20.94574 | 18.27003 | -0.6344 | 18.57348 |
April | 485.00000 | 22.23479 | 16.66480 | -0.2120 | 12.41473 |
May | 508.00000 | 23.39211 | 21.86664 | -0.7593 | 22.35477 |
June | 496.00000 | 23.96857 | 33.79242 | -0.4395 | 11.34903 |
July | 497.00000 | 24.08346 | 41.78751 | -0.3481 | 10.06208 |
August | 514.00000 | 23.68696 | 37.94052 | -0.5408 | 15.24491 |
September | 485.00000 | 22.24467 | 31.38939 | -1.2144 | 40.43344 |
October | 502.00000 | 20.55170 | 25.35684 | -0.7046 | 19.10920 |
November | 489.00000 | 19.78790 | 18.77304 | -1.0587 | 30.91682 |
December | 497.00000 | 19.68208 | 14.61213 | -1.1565 | 34.72925 |
Annual Sum or Average | 5943.00000 | 21.71492 | 24.79046 | -0.7565 | 22.78057 |
Minimum of Months | 454.00000 | 19.68208 | 14.61213 | -1.2144 | 10.06208 |
Maximum of Months | 514.00000 | 24.08346 | 41.78751 | -0.2120 | 40.43344 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.69440 | 17.70448 | -1.1381 | 33.97975 |
February | 454.00000 | 19.81139 | 19.63546 | -1.0546 | 30.65500 |
March | 514.00000 | 20.22370 | 19.45952 | -0.8761 | 23.61535 |
April | 485.00000 | 21.52223 | 18.03404 | -0.4203 | 14.27017 |
May | 508.00000 | 23.12289 | 22.95999 | -0.8988 | 25.84863 |
June | 496.00000 | 23.95404 | 34.39665 | -0.4668 | 11.72412 |
July | 497.00000 | 24.00147 | 42.51594 | -0.4153 | 10.42001 |
August | 514.00000 | 23.43028 | 39.23625 | -0.6817 | 18.07003 |
September | 485.00000 | 21.61240 | 33.10464 | -1.4715 | 50.56745 |
October | 502.00000 | 20.11544 | 26.40869 | -0.8504 | 22.65007 |
November | 489.00000 | 19.72263 | 19.20353 | -1.1081 | 32.76697 |
December | 497.00000 | 19.66860 | 14.95352 | -1.1695 | 35.26846 |
Annual Sum or Average | 5943.00000 | 21.42241 | 25.69552 | -0.8772 | 25.72683 |
Minimum of Months | 454.00000 | 19.66860 | 14.95352 | -1.4715 | 10.42001 |
Maximum of Months | 514.00000 | 24.00147 | 42.51594 | -0.4153 | 50.56745 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.61128 | 15.69112 | -1.1385 | 33.88021 |
February | 454.00000 | 19.71685 | 17.75941 | -1.0826 | 31.62247 |
March | 514.00000 | 20.19695 | 18.84335 | -0.9162 | 24.23714 |
April | 485.00000 | 20.93294 | 19.38434 | -0.6171 | 14.84890 |
May | 508.00000 | 23.11955 | 24.06163 | -1.0030 | 27.31496 |
June | 496.00000 | 24.09274 | 34.50990 | -0.5313 | 11.26078 |
July | 497.00000 | 24.21312 | 42.36522 | -0.4284 | 9.14485 |
August | 514.00000 | 23.85035 | 38.75414 | -0.6163 | 14.04143 |
September | 485.00000 | 22.26594 | 32.02511 | -1.2613 | 39.47709 |
October | 502.00000 | 20.58895 | 25.18635 | -0.6992 | 16.71138 |
November | 489.00000 | 19.84071 | 16.75173 | -1.0402 | 29.52398 |
December | 497.00000 | 19.69631 | 13.36396 | -1.1250 | 33.10015 |
Annual Sum or Average | 5943.00000 | 21.52845 | 24.96234 | -0.8693 | 23.67007 |
Minimum of Months | 454.00000 | 19.61128 | 13.36396 | -1.2613 | 9.14485 |
Maximum of Months | 514.00000 | 24.21312 | 42.36522 | -0.4284 | 39.47709 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.78828 | 15.79536 | -1.1089 | 32.50258 |
February | 454.00000 | 19.91996 | 17.79530 | -1.0246 | 29.03756 |
March | 514.00000 | 20.53312 | 18.59769 | -0.7787 | 19.44050 |
April | 485.00000 | 22.01801 | 18.03651 | -0.3123 | 10.52613 |
May | 508.00000 | 23.93471 | 21.68030 | -0.6050 | 14.75666 |
June | 496.00000 | 24.21644 | 33.70750 | -0.3786 | 8.89059 |
July | 497.00000 | 24.41164 | 41.34324 | -0.2460 | 7.47567 |
August | 514.00000 | 24.13055 | 37.36358 | -0.4208 | 9.86485 |
September | 485.00000 | 22.95422 | 30.44598 | -0.9890 | 29.13243 |
October | 502.00000 | 20.84915 | 24.77369 | -0.6165 | 14.77523 |
November | 489.00000 | 19.88685 | 16.82376 | -1.0345 | 29.25932 |
December | 497.00000 | 19.78133 | 13.60049 | -1.1172 | 32.73864 |
Annual Sum or Average | 5943.00000 | 21.88643 | 24.22837 | -0.7164 | 19.75674 |
Minimum of Months | 454.00000 | 19.78133 | 13.60049 | -1.1172 | 7.47567 |
Maximum of Months | 514.00000 | 24.41164 | 41.34324 | -0.2460 | 32.73864 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 17.48216 | 13.79219 | -1.5389 | 49.97428 |
February | 454.00000 | 18.51665 | 15.16260 | -1.2493 | 38.07541 |
March | 514.00000 | 19.48459 | 15.30236 | -0.9318 | 25.99171 |
April | 485.00000 | 21.70427 | 15.87286 | -0.3038 | 11.80872 |
May | 508.00000 | 23.05763 | 22.11709 | -0.8746 | 25.02494 |
June | 496.00000 | 23.78315 | 34.29566 | -0.5283 | 12.93857 |
July | 497.00000 | 24.02747 | 42.05856 | -0.3823 | 10.42019 |
August | 514.00000 | 23.66294 | 37.72762 | -0.5265 | 14.27093 |
September | 485.00000 | 22.33015 | 29.37709 | -1.1088 | 35.16393 |
October | 502.00000 | 20.28173 | 21.99181 | -0.6952 | 18.68157 |
November | 489.00000 | 17.93866 | 13.99419 | -1.3876 | 43.76008 |
December | 497.00000 | 17.19838 | 11.75339 | -1.6151 | 52.81338 |
Annual Sum or Average | 5943.00000 | 20.80928 | 22.86469 | -0.9256 | 28.13128 |
Minimum of Months | 454.00000 | 17.19838 | 11.75339 | -1.6151 | 10.42019 |
Maximum of Months | 514.00000 | 24.02747 | 42.05856 | -0.3038 | 52.81338 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.78634 | 15.68028 | -1.1130 | 32.66566 |
February | 454.00000 | 19.88456 | 17.63873 | -1.0486 | 30.04713 |
March | 514.00000 | 20.31646 | 18.56744 | -0.8693 | 22.48957 |
April | 485.00000 | 21.76301 | 18.12381 | -0.3728 | 11.36045 |
May | 508.00000 | 23.31642 | 23.21318 | -0.8792 | 23.44172 |
June | 496.00000 | 24.09721 | 34.42041 | -0.4671 | 10.67144 |
July | 497.00000 | 24.18721 | 42.41151 | -0.3870 | 8.97365 |
August | 514.00000 | 23.92528 | 38.34384 | -0.5332 | 12.38453 |
September | 485.00000 | 22.43983 | 31.24481 | -1.1709 | 36.07409 |
October | 502.00000 | 20.61575 | 24.88813 | -0.6883 | 16.41261 |
November | 489.00000 | 19.88794 | 16.65034 | -1.0351 | 29.28185 |
December | 497.00000 | 19.78102 | 13.51908 | -1.1182 | 32.78162 |
Annual Sum or Average | 5943.00000 | 21.68306 | 24.62962 | -0.8047 | 22.12390 |
Minimum of Months | 454.00000 | 19.78102 | 13.51908 | -1.1709 | 8.97365 |
Maximum of Months | 514.00000 | 24.18721 | 42.41151 | -0.3728 | 36.07409 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.77170 | 17.75652 | -1.0592 | 30.64965 |
February | 454.00000 | 19.89364 | 19.60502 | -0.9832 | 27.67178 |
March | 514.00000 | 20.32755 | 19.88357 | -0.8214 | 20.89305 |
April | 485.00000 | 21.58473 | 18.88233 | -0.4235 | 11.92202 |
May | 508.00000 | 23.72970 | 22.47885 | -0.7575 | 18.07956 |
June | 496.00000 | 24.22383 | 33.76506 | -0.4371 | 9.39910 |
July | 497.00000 | 24.33150 | 41.78936 | -0.3572 | 8.11538 |
August | 514.00000 | 23.93004 | 38.36571 | -0.5723 | 12.98631 |
September | 485.00000 | 22.30318 | 32.52730 | -1.2457 | 39.10511 |
October | 502.00000 | 20.46199 | 26.29337 | -0.7220 | 17.90717 |
November | 489.00000 | 19.79866 | 19.21753 | -1.0257 | 29.26393 |
December | 497.00000 | 19.75322 | 15.01124 | -1.0841 | 31.53416 |
Annual Sum or Average | 5943.00000 | 21.69349 | 25.52272 | -0.7885 | 21.36344 |
Minimum of Months | 454.00000 | 19.75322 | 15.01124 | -1.2457 | 8.11538 |
Maximum of Months | 514.00000 | 24.33150 | 41.78936 | -0.3572 | 39.10511 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.60944 | 16.96263 | -1.0982 | 32.42439 |
February | 385.00000 | 19.80016 | 18.50757 | -0.9923 | 28.08520 |
March | 433.00000 | 20.56639 | 18.41673 | -0.7262 | 18.19049 |
April | 410.00000 | 22.08309 | 16.91328 | -0.2666 | 10.38891 |
May | 430.00000 | 23.91948 | 21.13573 | -0.5758 | 14.91595 |
June | 418.00000 | 24.26118 | 33.31271 | -0.3426 | 8.74921 |
July | 422.00000 | 24.43401 | 41.13858 | -0.2347 | 7.87352 |
August | 433.00000 | 23.98137 | 37.34249 | -0.4724 | 11.54980 |
September | 410.00000 | 22.49458 | 30.81575 | -1.1375 | 35.84867 |
October | 427.00000 | 20.50306 | 24.96712 | -0.7000 | 17.39887 |
November | 417.00000 | 19.62222 | 18.35248 | -1.0665 | 31.10626 |
December | 422.00000 | 19.56395 | 14.42985 | -1.1288 | 33.62158 |
Annual Sum or Average | 5034.00000 | 21.75075 | 24.40564 | -0.7261 | 20.75399 |
Minimum of Months | 385.00000 | 19.56395 | 14.42985 | -1.1375 | 7.87352 |
Maximum of Months | 433.00000 | 24.43401 | 41.13858 | -0.2347 | 35.84867 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.86152 | 16.91883 | -1.0223 | 29.14673 |
February | 454.00000 | 20.38509 | 18.15264 | -0.8141 | 22.00804 |
March | 514.00000 | 21.32094 | 17.71008 | -0.5067 | 14.87676 |
April | 485.00000 | 22.68268 | 16.22556 | -0.0801 | 10.14165 |
May | 508.00000 | 23.75380 | 21.36222 | -0.6316 | 16.94823 |
June | 496.00000 | 24.14011 | 33.49874 | -0.3839 | 9.55066 |
July | 497.00000 | 24.26204 | 41.48466 | -0.2901 | 8.47690 |
August | 514.00000 | 23.97702 | 37.29216 | -0.4372 | 11.64494 |
September | 485.00000 | 22.81805 | 30.13245 | -0.9884 | 30.28871 |
October | 502.00000 | 21.03158 | 24.43103 | -0.5481 | 14.48291 |
November | 489.00000 | 19.96832 | 18.00294 | -0.9593 | 26.73004 |
December | 497.00000 | 19.80341 | 14.32837 | -1.0710 | 30.95053 |
Annual Sum or Average | 5943.00000 | 22.01575 | 24.19041 | -0.6425 | 18.70231 |
Minimum of Months | 454.00000 | 19.80341 | 14.32837 | -1.0710 | 8.47690 |
Maximum of Months | 514.00000 | 24.26204 | 41.48466 | -0.0801 | 30.95053 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.81517 | 17.38057 | -1.0570 | 30.49194 |
February | 454.00000 | 19.94049 | 19.00355 | -0.9706 | 27.12137 |
March | 514.00000 | 20.46846 | 19.08117 | -0.7712 | 19.51607 |
April | 485.00000 | 21.98893 | 17.61640 | -0.2815 | 11.10240 |
May | 508.00000 | 23.55738 | 22.39856 | -0.7481 | 19.32758 |
June | 496.00000 | 24.13473 | 34.06528 | -0.4073 | 9.81655 |
July | 497.00000 | 24.19395 | 42.17163 | -0.3516 | 8.71626 |
August | 514.00000 | 23.79508 | 38.45163 | -0.5549 | 13.49315 |
September | 485.00000 | 22.21582 | 31.82249 | -1.2330 | 39.22331 |
October | 502.00000 | 20.46950 | 25.65661 | -0.7162 | 17.68905 |
November | 489.00000 | 19.82645 | 18.61260 | -1.0231 | 29.12770 |
December | 497.00000 | 19.78079 | 14.75865 | -1.0859 | 31.58098 |
Annual Sum or Average | 5943.00000 | 21.69867 | 25.14770 | -0.7646 | 21.34162 |
Minimum of Months | 454.00000 | 19.78079 | 14.75865 | -1.2330 | 8.71626 |
Maximum of Months | 514.00000 | 24.19395 | 42.17163 | -0.2815 | 39.22331 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6546444.11 | 1892702.18 | 2.42 | 6545334.70 | 1109.40 | 0.00 | 0.28 | 20-JAN-07:01 | 0.00 | 01-JAN-00:02 | 6800.28 | 20-JAN-07:01 | 6800.28 | 20-JAN-07:01 | 5.61 | 19-JAN-17:11 | 1886.50 | 20-JAN-07:01 | 0.00 |
February | 10089375.74 | 2953222.36 | 5.51 | 10014150.85 | 75224.89 | 0.00 | 0.25 | 02-FEB-07:01 | 0.00 | 01-FEB-00:05 | 6212.17 | 02-FEB-07:01 | 6212.17 | 02-FEB-07:01 | 49.60 | 09-FEB-13:01 | 1732.85 | 02-FEB-07:01 | 0.00 |
March | 28253602.13 | 8305936.91 | 17.46 | 28023520.43 | 230081.70 | 0.00 | 0.27 | 07-MAR-07:01 | 0.00 | 01-MAR-00:05 | 6729.26 | 07-MAR-07:01 | 6729.26 | 07-MAR-07:01 | 113.15 | 21-MAR-17:13 | 1868.03 | 07-MAR-07:01 | 0.00 |
April | 30621074.10 | 8972506.47 | 14.14 | 30589143.05 | 31931.05 | 0.00 | 0.26 | 14-APR-07:03 | 0.00 | 01-APR-00:10 | 6382.92 | 14-APR-07:03 | 6382.92 | 14-APR-07:03 | 14.42 | 29-APR-07:20 | 1777.64 | 14-APR-07:03 | 0.00 |
May | 0.391820E+10 | 0.102138E+10 | 136.66 | 0.391102E+10 | 7184856.76 | 0.00 | 1.00 | 31-MAY-14:50 | 0.00 | 01-MAY-00:10 | 37601.41 | 31-MAY-16:00 | 37601.41 | 31-MAY-16:00 | 350.15 | 31-MAY-20:20 | 8583.36 | 31-MAY-16:00 | 0.00 |
June | 0.211376E+11 | 0.517376E+10 | 314.37 | 0.202642E+11 | 0.873378E+09 | 0.00 | 1.00 | 09-JUN-12:10 | 0.00 | 01-JUN-00:10 | 66543.00 | 30-JUN-11:40 | 58847.76 | 20-JUN-16:00 | 15323.36 | 30-JUN-06:02 | 15866.40 | 30-JUN-12:30 | 0.00 |
July | 0.299013E+11 | 0.716012E+10 | 334.09 | 0.275657E+11 | 0.233560E+10 | 0.00 | 1.00 | 03-JUL-14:40 | 0.00 | 01-JUL-00:10 | 66574.78 | 11-JUL-16:00 | 64200.47 | 12-JUL-16:00 | 32727.80 | 03-JUL-15:00 | 16122.52 | 21-JUL-16:00 | 0.00 |
August | 0.159308E+11 | 0.387510E+10 | 243.27 | 0.147720E+11 | 0.115873E+10 | 0.00 | 1.00 | 01-AUG-14:20 | 0.00 | 01-AUG-00:10 | 62290.49 | 11-AUG-16:00 | 62290.49 | 11-AUG-16:00 | 7981.26 | 03-AUG-12:10 | 14826.52 | 11-AUG-16:00 | 0.00 |
September | 0.240225E+09 | 68791966.27 | 30.85 | 0.225153E+09 | 15072513.86 | 0.00 | 0.38 | 07-SEP-16:00 | 0.00 | 01-SEP-00:10 | 9566.69 | 07-SEP-16:00 | 9566.69 | 07-SEP-16:00 | 612.51 | 02-SEP-15:00 | 2587.21 | 07-SEP-16:00 | 0.00 |
October | 33690402.14 | 9886712.62 | 16.81 | 32936077.92 | 754324.22 | 0.00 | 0.16 | 30-OCT-06:01 | 0.00 | 01-OCT-00:10 | 3896.31 | 30-OCT-06:01 | 3896.31 | 30-OCT-06:01 | 149.10 | 02-OCT-07:20 | 1110.98 | 30-OCT-06:01 | 0.00 |
November | 6928789.16 | 2021497.70 | 3.34 | 6928789.16 | -0.0 | 0.00 | 0.20 | 15-NOV-07:01 | 0.00 | 01-NOV-00:10 | 4904.82 | 15-NOV-07:01 | 4904.82 | 15-NOV-07:01 | 0.00 | 21-NOV-07:01 | 1385.15 | 15-NOV-07:01 | 0.00 |
December | 3260308.00 | 939090.47 | 0.77 | 3260308.00 | -0.0 | 0.00 | 0.26 | 21-DEC-07:01 | 0.00 | 01-DEC-00:10 | 6341.28 | 21-DEC-07:01 | 6341.28 | 21-DEC-07:01 | 0.00 | 29-DEC-07:01 | 1766.73 | 21-DEC-07:01 | 0.00 |
Annual Sum or Average | 0.712475E+11 | 0.173341E+11 | 1119.69 | 0.668564E+11 | 0.439105E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 3260308.00 | 939090.47 | 0.77 | 3260308.00 | -0.0 | 0.00 | 0.16 | 0.00 | 3896.31 | 3896.31 | 0.00 | 1110.98 | 0.00 | ||||||
Maximum of Months | 0.299013E+11 | 0.716012E+10 | 334.09 | 0.275657E+11 | 0.233560E+10 | 0.00 | 1.00 | 0.00 | 66574.78 | 64200.47 | 32727.80 | 16122.52 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3678778.37 | 1050826.77 | 0.73 | 3678778.37 | 0.00 | 0.00 | 0.26 | 20-JAN-07:01 | 0.00 | 01-JAN-00:02 | 5609.36 | 20-JAN-07:01 | 5609.36 | 20-JAN-07:01 | 0.00 | 14-JAN-07:03 | 1564.44 | 20-JAN-07:01 | 0.00 |
February | 4233538.86 | 1196234.96 | 0.51 | 4233119.36 | 419.50 | 0.00 | 0.31 | 09-FEB-07:01 | 0.00 | 01-FEB-00:05 | 6845.28 | 09-FEB-07:01 | 6845.28 | 09-FEB-07:01 | 4.20 | 09-FEB-07:12 | 1884.88 | 09-FEB-07:01 | 0.00 |
March | 9143680.99 | 2595131.20 | 3.16 | 9126477.98 | 17203.01 | 0.00 | 0.35 | 22-MAR-06:01 | 0.00 | 01-MAR-00:05 | 7875.40 | 22-MAR-06:01 | 7875.40 | 22-MAR-06:01 | 13.52 | 22-MAR-10:10 | 2145.81 | 22-MAR-06:01 | 0.00 |
April | 24930990.43 | 7256450.22 | 13.62 | 24930630.44 | 359.99 | 0.00 | 0.32 | 17-APR-06:01 | 0.00 | 01-APR-00:10 | 7207.00 | 17-APR-06:01 | 7207.00 | 17-APR-06:01 | 2.40 | 18-APR-12:05 | 1977.13 | 17-APR-06:01 | 0.00 |
May | 0.424014E+10 | 0.109161E+10 | 146.55 | 0.423626E+10 | 3884270.34 | 0.00 | 1.00 | 12-MAY-12:50 | 0.00 | 01-MAY-00:10 | 38278.69 | 31-MAY-16:00 | 38278.69 | 31-MAY-16:00 | 393.18 | 31-MAY-06:02 | 8735.69 | 31-MAY-16:00 | 0.00 |
June | 0.209789E+11 | 0.509784E+10 | 322.84 | 0.201439E+11 | 0.835013E+09 | 0.00 | 1.00 | 09-JUN-12:10 | 0.00 | 01-JUN-00:10 | 65256.44 | 30-JUN-12:10 | 58253.09 | 30-JUN-14:30 | 13309.88 | 30-JUN-06:02 | 15760.86 | 30-JUN-14:30 | 0.00 |
July | 0.282314E+11 | 0.674913E+10 | 342.43 | 0.260508E+11 | 0.218053E+10 | 0.00 | 1.00 | 03-JUL-14:30 | 0.00 | 01-JUL-00:10 | 63050.92 | 11-JUL-15:30 | 59261.54 | 11-JUL-15:40 | 32191.94 | 03-JUL-15:00 | 15117.99 | 11-JUL-16:00 | 0.00 |
August | 0.145344E+11 | 0.353506E+10 | 247.53 | 0.134537E+11 | 0.108070E+10 | 0.00 | 1.00 | 01-AUG-12:50 | 0.00 | 01-AUG-00:10 | 57257.68 | 11-AUG-15:30 | 57257.68 | 11-AUG-15:30 | 7228.67 | 04-AUG-10:50 | 13430.08 | 11-AUG-15:30 | 0.00 |
September | 0.222241E+09 | 63441178.38 | 29.71 | 0.210614E+09 | 11627025.23 | 0.00 | 0.37 | 07-SEP-16:00 | 0.00 | 01-SEP-00:10 | 8449.22 | 07-SEP-16:00 | 8449.22 | 07-SEP-16:00 | 482.58 | 02-SEP-14:20 | 2288.80 | 07-SEP-16:00 | 0.00 |
October | 8968310.98 | 2537426.42 | 2.29 | 8893713.95 | 74597.03 | 0.00 | 0.34 | 20-OCT-06:01 | 0.00 | 01-OCT-00:10 | 7537.68 | 20-OCT-06:01 | 7537.68 | 20-OCT-06:01 | 34.48 | 03-OCT-10:50 | 2060.87 | 20-OCT-06:01 | 0.00 |
November | 3058829.18 | 869854.94 | 0.46 | 3058829.18 | -0.0 | 0.00 | 0.26 | 02-NOV-06:01 | 0.00 | 01-NOV-00:10 | 5789.25 | 02-NOV-06:01 | 5789.25 | 02-NOV-06:01 | 0.00 | 14-NOV-07:01 | 1611.59 | 02-NOV-06:01 | 0.00 |
December | 1927114.35 | 554554.62 | 0.47 | 1927114.35 | 0.00 | 0.00 | 0.19 | 23-DEC-07:03 | 0.00 | 01-DEC-00:10 | 4097.91 | 23-DEC-07:03 | 4097.91 | 23-DEC-07:03 | 0.00 | 21-DEC-07:01 | 1161.17 | 23-DEC-07:03 | 0.00 |
Annual Sum or Average | 0.682630E+11 | 0.165531E+11 | 1110.30 | 0.641512E+11 | 0.411185E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 1927114.35 | 554554.62 | 0.46 | 1927114.35 | -0.0 | 0.00 | 0.19 | 0.00 | 4097.91 | 4097.91 | 0.00 | 1161.17 | 0.00 | ||||||
Maximum of Months | 0.282314E+11 | 0.674913E+10 | 342.43 | 0.260508E+11 | 0.218053E+10 | 0.00 | 1.00 | 0.00 | 65256.44 | 59261.54 | 32191.94 | 15760.86 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 136019.42 | 39849.56 | 0.04 | 136019.42 | -0.0 | 0.00 | 0.06 | 19-JAN-07:01 | 0.00 | 01-JAN-00:02 | 1333.57 | 19-JAN-07:01 | 1333.57 | 19-JAN-07:01 | 0.00 | 01-JAN-00:02 | 389.75 | 19-JAN-07:01 | 0.00 |
February | 634467.31 | 184243.16 | 0.31 | 629674.84 | 4792.47 | 0.00 | 0.17 | 09-FEB-07:01 | 0.00 | 01-FEB-00:05 | 4103.86 | 09-FEB-07:01 | 4103.86 | 09-FEB-07:01 | 24.28 | 09-FEB-13:05 | 1167.21 | 09-FEB-07:01 | 0.00 |
March | 8226319.00 | 2422605.02 | 7.81 | 8091286.66 | 135032.33 | 0.00 | 0.18 | 23-MAR-06:01 | 0.00 | 01-MAR-00:05 | 4192.19 | 23-MAR-06:01 | 4192.19 | 23-MAR-06:01 | 22.76 | 22-MAR-11:50 | 1191.31 | 23-MAR-06:01 | 0.00 |
April | 32487799.39 | 9541026.07 | 22.51 | 32472576.45 | 15222.95 | 0.00 | 0.23 | 19-APR-06:01 | 0.00 | 01-APR-00:10 | 5426.66 | 19-APR-06:01 | 5426.66 | 19-APR-06:01 | 17.21 | 18-APR-12:20 | 1523.91 | 19-APR-06:01 | 0.00 |
May | 0.413090E+10 | 0.107158E+10 | 145.67 | 0.412452E+10 | 6376932.63 | 0.00 | 1.00 | 12-MAY-13:10 | 0.00 | 01-MAY-00:10 | 40224.47 | 31-MAY-16:00 | 40224.47 | 31-MAY-16:00 | 459.21 | 31-MAY-06:02 | 9180.59 | 31-MAY-16:00 | 0.00 |
June | 0.212784E+11 | 0.520362E+10 | 318.91 | 0.204140E+11 | 0.864454E+09 | 0.00 | 1.00 | 12-JUN-13:00 | 0.00 | 01-JUN-00:10 | 70715.33 | 30-JUN-12:30 | 64225.30 | 30-JUN-14:30 | 13307.39 | 30-JUN-11:50 | 17285.13 | 30-JUN-14:30 | 0.00 |
July | 0.287034E+11 | 0.689926E+10 | 339.11 | 0.265022E+11 | 0.220116E+10 | 0.00 | 1.00 | 03-JUL-14:40 | 0.00 | 01-JUL-00:10 | 65634.42 | 21-JUL-14:40 | 65634.42 | 21-JUL-14:40 | 31786.48 | 03-JUL-15:00 | 16281.63 | 21-JUL-14:40 | 0.00 |
August | 0.144227E+11 | 0.353288E+10 | 243.74 | 0.132674E+11 | 0.115526E+10 | 0.00 | 1.00 | 02-AUG-12:10 | 0.00 | 01-AUG-00:10 | 60269.28 | 11-AUG-15:50 | 60269.28 | 11-AUG-15:50 | 7167.51 | 03-AUG-14:40 | 14276.09 | 11-AUG-15:50 | 0.00 |
September | 0.195339E+09 | 56017724.57 | 29.06 | 0.182455E+09 | 12883812.32 | 0.00 | 0.30 | 07-SEP-16:00 | 0.00 | 01-SEP-00:10 | 7412.27 | 07-SEP-16:00 | 7412.27 | 07-SEP-16:00 | 560.07 | 02-SEP-14:50 | 2042.70 | 07-SEP-16:00 | 0.00 |
October | 6483375.88 | 1885273.71 | 2.72 | 6289671.06 | 193704.82 | 0.00 | 0.22 | 05-OCT-06:01 | 0.00 | 01-OCT-00:10 | 5331.87 | 05-OCT-06:01 | 5331.87 | 05-OCT-06:01 | 72.51 | 03-OCT-11:00 | 1498.65 | 05-OCT-06:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 123842.25 | 36378.41 | 0.04 | 123842.25 | 0.00 | 0.00 | 0.04 | 23-DEC-07:03 | 0.00 | 01-DEC-00:10 | 825.62 | 23-DEC-07:03 | 825.62 | 23-DEC-07:03 | 0.00 | 23-DEC-07:03 | 242.52 | 23-DEC-07:03 | 0.00 |
Annual Sum or Average | 0.687788E+11 | 0.167775E+11 | 1109.92 | 0.645383E+11 | 0.424049E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.287034E+11 | 0.689926E+10 | 339.11 | 0.265022E+11 | 0.220116E+10 | 0.00 | 1.00 | 0.00 | 70715.33 | 65634.42 | 31786.48 | 17285.13 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.04 | 0.00 | 43.04 | 0.00 | 2949.17 | 0.00 | 0.00 | 0.00 |
February | 190.26 | 0.00 | 190.26 | 0.00 | 2624.95 | 0.00 | 0.00 | 0.00 |
March | 508.87 | 0.00 | 508.87 | 51.28 | 1916.89 | 0.00 | 0.00 | 0.00 |
April | 920.69 | 20.27 | 900.42 | 400.89 | 1001.68 | 0.00 | 0.00 | 0.00 |
May | 1411.11 | 224.35 | 1186.76 | 1101.47 | 459.45 | 0.00 | 0.00 | 0.00 |
June | 1841.11 | 409.44 | 1431.66 | 1782.02 | 217.00 | 0.00 | 0.00 | 0.00 |
July | 1545.21 | 251.16 | 1294.05 | 1526.90 | 265.64 | 0.00 | 0.00 | 0.00 |
August | 986.68 | 55.14 | 931.54 | 806.52 | 437.24 | 0.00 | 0.00 | 0.00 |
September | 550.46 | 0.55 | 549.90 | 228.54 | 853.90 | 0.00 | 0.00 | 0.00 |
October | 267.85 | 0.00 | 267.85 | 26.06 | 1615.41 | 0.00 | 0.00 | 0.00 |
November | 83.12 | 0.00 | 83.12 | 0.00 | 2879.45 | 0.00 | 0.00 | 0.00 |
December | 13.06 | 0.00 | 13.06 | 0.00 | 3109.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 699.29 | 80.43 | 618.85 | 496.50 | 1521.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.06 | 0.00 | 13.06 | 0.00 | 217.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1841.11 | 409.44 | 1431.66 | 1782.02 | 3109.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.59 | 23.79 | 51.80 | 7.25 | 1906.05 | 0.00 | 0.00 | 0.00 |
February | 417.63 | 199.28 | 218.35 | 224.51 | 1581.86 | 0.00 | 0.00 | 0.00 |
March | 1191.24 | 603.26 | 587.98 | 1005.08 | 1149.33 | 0.00 | 0.00 | 0.00 |
April | 1637.41 | 828.36 | 809.06 | 1509.06 | 621.56 | 0.00 | 0.00 | 0.00 |
May | 2378.69 | 1339.08 | 1039.61 | 2561.55 | 332.75 | 0.00 | 0.00 | 0.00 |
June | 2188.45 | 1019.53 | 1168.91 | 2429.68 | 165.85 | 0.00 | 0.00 | 0.00 |
July | 2078.74 | 1006.64 | 1072.10 | 2362.94 | 190.95 | 0.00 | 0.00 | 0.00 |
August | 1646.50 | 800.73 | 845.77 | 1795.32 | 295.89 | 0.00 | 0.00 | 0.00 |
September | 1018.56 | 445.87 | 572.69 | 947.05 | 539.72 | 0.00 | 0.00 | 0.00 |
October | 538.01 | 215.88 | 322.13 | 391.09 | 980.15 | 0.00 | 0.00 | 0.00 |
November | 114.44 | 39.99 | 74.45 | 10.35 | 1845.68 | 0.00 | 0.00 | 0.00 |
December | 16.35 | 3.91 | 12.44 | 0.00 | 2061.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1112.71 | 546.26 | 566.45 | 1109.56 | 969.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.35 | 3.91 | 12.44 | 0.00 | 165.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2378.69 | 1339.08 | 1168.91 | 2561.55 | 2061.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 516.35 | 340.19 | 176.16 | 305.53 | 2645.47 | 0.00 | 0.00 | 0.00 |
February | 1776.79 | 1235.94 | 540.85 | 1505.93 | 2115.40 | 0.00 | 0.00 | 0.00 |
March | 3051.12 | 2068.08 | 983.04 | 2962.53 | 1608.26 | 0.00 | 0.00 | 0.00 |
April | 3722.27 | 2315.63 | 1406.65 | 4008.35 | 1043.21 | 0.00 | 0.00 | 0.00 |
May | 3069.34 | 1590.39 | 1478.95 | 3390.32 | 574.64 | 0.00 | 0.00 | 0.00 |
June | 2802.42 | 1148.64 | 1653.78 | 3175.29 | 312.51 | 0.00 | 0.00 | 0.00 |
July | 2700.05 | 1175.87 | 1524.18 | 3132.08 | 334.43 | 0.00 | 0.00 | 0.00 |
August | 2796.18 | 1541.01 | 1255.16 | 3199.48 | 488.39 | 0.00 | 0.00 | 0.00 |
September | 2259.81 | 1360.97 | 898.84 | 2367.07 | 831.76 | 0.00 | 0.00 | 0.00 |
October | 1627.07 | 1032.33 | 594.74 | 1484.84 | 1364.15 | 0.00 | 0.00 | 0.00 |
November | 872.38 | 609.15 | 263.23 | 584.59 | 2458.70 | 0.00 | 0.00 | 0.00 |
December | 154.85 | 109.15 | 45.70 | 28.50 | 2952.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2111.84 | 1208.78 | 903.05 | 2180.35 | 1390.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 154.85 | 109.15 | 45.70 | 28.50 | 312.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3722.27 | 2315.63 | 1653.78 | 4008.35 | 2952.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.76 | 7.10 | 32.67 | 0.00 | 1944.42 | 0.00 | 0.00 | 0.00 |
February | 234.72 | 81.62 | 153.10 | 50.94 | 1642.58 | 0.00 | 0.00 | 0.00 |
March | 704.52 | 302.87 | 401.66 | 410.52 | 1173.49 | 0.00 | 0.00 | 0.00 |
April | 1671.76 | 866.32 | 805.44 | 1595.37 | 670.02 | 0.00 | 0.00 | 0.00 |
May | 1625.52 | 740.27 | 885.26 | 1634.42 | 352.15 | 0.00 | 0.00 | 0.00 |
June | 1781.49 | 759.58 | 1021.91 | 1932.88 | 193.58 | 0.00 | 0.00 | 0.00 |
July | 1490.59 | 563.85 | 926.74 | 1631.68 | 210.40 | 0.00 | 0.00 | 0.00 |
August | 1225.10 | 518.77 | 706.33 | 1278.61 | 310.30 | 0.00 | 0.00 | 0.00 |
September | 741.43 | 310.48 | 430.95 | 615.96 | 551.76 | 0.00 | 0.00 | 0.00 |
October | 290.37 | 87.29 | 203.07 | 116.08 | 1020.62 | 0.00 | 0.00 | 0.00 |
November | 116.18 | 42.21 | 73.97 | 13.88 | 1840.82 | 0.00 | 0.00 | 0.00 |
December | 10.43 | 1.10 | 9.33 | 0.00 | 2067.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 829.79 | 357.54 | 472.25 | 776.38 | 994.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.43 | 1.10 | 9.33 | 0.00 | 193.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1781.49 | 866.32 | 1021.91 | 1932.88 | 2067.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.35 | 0.00 | 14.35 | 0.00 | 987.24 | 0.00 | 0.00 | 0.00 |
February | 63.42 | 0.00 | 63.42 | 0.00 | 875.85 | 0.00 | 0.00 | 0.00 |
March | 169.62 | 0.00 | 169.62 | 17.70 | 641.28 | 0.00 | 0.00 | 0.00 |
April | 306.88 | 6.76 | 300.13 | 139.84 | 336.54 | 0.00 | 0.00 | 0.00 |
May | 470.35 | 74.78 | 395.57 | 377.04 | 151.74 | 0.00 | 0.00 | 0.00 |
June | 613.67 | 136.47 | 477.20 | 602.74 | 71.34 | 0.00 | 0.00 | 0.00 |
July | 515.05 | 83.72 | 431.33 | 513.97 | 88.91 | 0.00 | 0.00 | 0.00 |
August | 328.88 | 18.38 | 310.50 | 267.68 | 151.45 | 0.00 | 0.00 | 0.00 |
September | 183.48 | 0.18 | 183.29 | 70.54 | 307.78 | 0.00 | 0.00 | 0.00 |
October | 89.28 | 0.00 | 89.28 | 6.93 | 567.75 | 0.00 | 0.00 | 0.00 |
November | 27.71 | 0.00 | 27.71 | 0.00 | 979.30 | 0.00 | 0.00 | 0.00 |
December | 4.35 | 0.00 | 4.35 | 0.00 | 1047.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.08 | 26.81 | 206.27 | 167.33 | 515.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.35 | 0.00 | 4.35 | 0.00 | 71.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 613.67 | 136.47 | 477.20 | 602.74 | 1047.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.35 | 0.00 | 14.35 | 0.00 | 987.31 | 0.00 | 0.00 | 0.00 |
February | 63.42 | 0.00 | 63.42 | 0.00 | 875.90 | 0.00 | 0.00 | 0.00 |
March | 169.63 | 0.00 | 169.63 | 17.70 | 641.32 | 0.00 | 0.00 | 0.00 |
April | 306.90 | 6.76 | 300.15 | 139.85 | 336.56 | 0.00 | 0.00 | 0.00 |
May | 470.38 | 74.78 | 395.59 | 377.06 | 151.75 | 0.00 | 0.00 | 0.00 |
June | 613.71 | 136.48 | 477.23 | 602.77 | 71.34 | 0.00 | 0.00 | 0.00 |
July | 515.08 | 83.72 | 431.36 | 514.01 | 88.92 | 0.00 | 0.00 | 0.00 |
August | 328.90 | 18.38 | 310.52 | 267.70 | 151.46 | 0.00 | 0.00 | 0.00 |
September | 183.49 | 0.18 | 183.30 | 70.55 | 307.80 | 0.00 | 0.00 | 0.00 |
October | 89.28 | 0.00 | 89.28 | 6.93 | 567.79 | 0.00 | 0.00 | 0.00 |
November | 27.71 | 0.00 | 27.71 | 0.00 | 979.36 | 0.00 | 0.00 | 0.00 |
December | 4.35 | 0.00 | 4.35 | 0.00 | 1047.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.10 | 26.81 | 206.29 | 167.34 | 515.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.35 | 0.00 | 4.35 | 0.00 | 71.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 613.71 | 136.48 | 477.23 | 602.77 | 1047.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.35 | 0.00 | 14.35 | 0.00 | 987.31 | 0.00 | 0.00 | 0.00 |
February | 63.42 | 0.00 | 63.42 | 0.00 | 875.90 | 0.00 | 0.00 | 0.00 |
March | 169.63 | 0.00 | 169.63 | 17.70 | 641.32 | 0.00 | 0.00 | 0.00 |
April | 306.90 | 6.76 | 300.15 | 139.85 | 336.56 | 0.00 | 0.00 | 0.00 |
May | 470.38 | 74.78 | 395.59 | 377.06 | 151.75 | 0.00 | 0.00 | 0.00 |
June | 613.71 | 136.48 | 477.23 | 602.77 | 71.34 | 0.00 | 0.00 | 0.00 |
July | 515.08 | 83.72 | 431.36 | 514.01 | 88.92 | 0.00 | 0.00 | 0.00 |
August | 328.90 | 18.38 | 310.52 | 267.70 | 151.46 | 0.00 | 0.00 | 0.00 |
September | 183.49 | 0.18 | 183.30 | 70.55 | 307.80 | 0.00 | 0.00 | 0.00 |
October | 89.28 | 0.00 | 89.28 | 6.93 | 567.79 | 0.00 | 0.00 | 0.00 |
November | 27.71 | 0.00 | 27.71 | 0.00 | 979.36 | 0.00 | 0.00 | 0.00 |
December | 4.35 | 0.00 | 4.35 | 0.00 | 1047.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.10 | 26.81 | 206.29 | 167.34 | 515.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.35 | 0.00 | 4.35 | 0.00 | 71.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 613.71 | 136.48 | 477.23 | 602.77 | 1047.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.71 | 22.88 | 49.83 | 7.16 | 1843.30 | 0.00 | 0.00 | 0.00 |
February | 401.74 | 191.70 | 210.04 | 216.93 | 1527.60 | 0.00 | 0.00 | 0.00 |
March | 1145.92 | 580.31 | 565.61 | 973.16 | 1120.04 | 0.00 | 0.00 | 0.00 |
April | 1575.12 | 796.84 | 778.28 | 1458.63 | 620.01 | 0.00 | 0.00 | 0.00 |
May | 2288.20 | 1288.13 | 1000.06 | 2472.50 | 333.89 | 0.00 | 0.00 | 0.00 |
June | 2105.19 | 980.75 | 1124.45 | 2348.56 | 163.55 | 0.00 | 0.00 | 0.00 |
July | 1999.66 | 968.35 | 1031.31 | 2278.68 | 191.78 | 0.00 | 0.00 | 0.00 |
August | 1583.86 | 770.26 | 813.60 | 1725.16 | 304.20 | 0.00 | 0.00 | 0.00 |
September | 979.81 | 428.90 | 550.91 | 894.50 | 571.53 | 0.00 | 0.00 | 0.00 |
October | 517.54 | 207.67 | 309.88 | 368.41 | 1002.06 | 0.00 | 0.00 | 0.00 |
November | 110.09 | 38.47 | 71.62 | 9.72 | 1810.49 | 0.00 | 0.00 | 0.00 |
December | 15.73 | 3.77 | 11.96 | 0.00 | 2000.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1070.38 | 525.48 | 544.90 | 1068.48 | 954.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.73 | 3.77 | 11.96 | 0.00 | 163.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2288.20 | 1288.13 | 1124.45 | 2472.50 | 2000.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.87 | 0.90 | 1.97 | 0.28 | 72.88 | 0.00 | 0.00 | 0.00 |
February | 15.88 | 7.58 | 8.30 | 8.58 | 60.40 | 0.00 | 0.00 | 0.00 |
March | 45.31 | 22.94 | 22.36 | 38.48 | 44.29 | 0.00 | 0.00 | 0.00 |
April | 62.28 | 31.51 | 30.77 | 57.67 | 24.51 | 0.00 | 0.00 | 0.00 |
May | 90.47 | 50.93 | 39.54 | 97.76 | 13.20 | 0.00 | 0.00 | 0.00 |
June | 83.24 | 38.78 | 44.46 | 92.86 | 6.47 | 0.00 | 0.00 | 0.00 |
July | 79.06 | 38.29 | 40.78 | 90.10 | 7.58 | 0.00 | 0.00 | 0.00 |
August | 62.62 | 30.46 | 32.17 | 68.21 | 12.03 | 0.00 | 0.00 | 0.00 |
September | 38.74 | 16.96 | 21.78 | 35.37 | 22.60 | 0.00 | 0.00 | 0.00 |
October | 20.46 | 8.21 | 12.25 | 14.57 | 39.62 | 0.00 | 0.00 | 0.00 |
November | 4.35 | 1.52 | 2.83 | 0.38 | 71.59 | 0.00 | 0.00 | 0.00 |
December | 0.62 | 0.15 | 0.47 | 0.00 | 79.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.32 | 20.78 | 21.54 | 42.25 | 37.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.62 | 0.15 | 0.47 | 0.00 | 6.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.47 | 50.93 | 44.46 | 97.76 | 79.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 172.12 | 113.40 | 58.72 | 106.23 | 853.63 | 0.00 | 0.00 | 0.00 |
February | 592.28 | 411.99 | 180.29 | 511.66 | 692.42 | 0.00 | 0.00 | 0.00 |
March | 1017.07 | 689.38 | 327.69 | 1005.97 | 535.95 | 0.00 | 0.00 | 0.00 |
April | 1240.80 | 771.90 | 468.90 | 1348.64 | 363.79 | 0.00 | 0.00 | 0.00 |
May | 1023.14 | 530.15 | 493.00 | 1142.24 | 198.00 | 0.00 | 0.00 | 0.00 |
June | 934.17 | 382.89 | 551.28 | 1068.65 | 106.38 | 0.00 | 0.00 | 0.00 |
July | 900.04 | 391.97 | 508.07 | 1050.26 | 115.93 | 0.00 | 0.00 | 0.00 |
August | 932.09 | 513.69 | 418.40 | 1071.01 | 174.32 | 0.00 | 0.00 | 0.00 |
September | 753.29 | 453.67 | 299.62 | 788.75 | 301.79 | 0.00 | 0.00 | 0.00 |
October | 542.38 | 344.12 | 198.25 | 494.55 | 477.55 | 0.00 | 0.00 | 0.00 |
November | 290.80 | 203.06 | 87.75 | 199.93 | 810.58 | 0.00 | 0.00 | 0.00 |
December | 51.62 | 36.38 | 15.23 | 11.74 | 952.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.97 | 402.94 | 301.03 | 733.83 | 464.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.62 | 36.38 | 15.23 | 11.74 | 106.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1240.80 | 771.90 | 551.28 | 1348.64 | 952.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 172.12 | 113.40 | 58.72 | 106.23 | 853.63 | 0.00 | 0.00 | 0.00 |
February | 592.28 | 411.99 | 180.29 | 511.66 | 692.42 | 0.00 | 0.00 | 0.00 |
March | 1017.07 | 689.38 | 327.69 | 1005.97 | 535.95 | 0.00 | 0.00 | 0.00 |
April | 1240.80 | 771.90 | 468.90 | 1348.64 | 363.79 | 0.00 | 0.00 | 0.00 |
May | 1023.14 | 530.15 | 493.00 | 1142.24 | 198.00 | 0.00 | 0.00 | 0.00 |
June | 934.17 | 382.89 | 551.28 | 1068.65 | 106.38 | 0.00 | 0.00 | 0.00 |
July | 900.04 | 391.97 | 508.07 | 1050.26 | 115.93 | 0.00 | 0.00 | 0.00 |
August | 932.09 | 513.69 | 418.40 | 1071.01 | 174.32 | 0.00 | 0.00 | 0.00 |
September | 753.29 | 453.67 | 299.62 | 788.75 | 301.79 | 0.00 | 0.00 | 0.00 |
October | 542.38 | 344.12 | 198.25 | 494.55 | 477.55 | 0.00 | 0.00 | 0.00 |
November | 290.80 | 203.06 | 87.75 | 199.93 | 810.58 | 0.00 | 0.00 | 0.00 |
December | 51.62 | 36.38 | 15.23 | 11.74 | 952.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.97 | 402.94 | 301.03 | 733.83 | 464.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.62 | 36.38 | 15.23 | 11.74 | 106.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1240.80 | 771.90 | 551.28 | 1348.64 | 952.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 172.11 | 113.39 | 58.72 | 106.22 | 853.57 | 0.00 | 0.00 | 0.00 |
February | 592.25 | 411.97 | 180.28 | 511.63 | 692.38 | 0.00 | 0.00 | 0.00 |
March | 1017.01 | 689.34 | 327.67 | 1005.91 | 535.92 | 0.00 | 0.00 | 0.00 |
April | 1240.72 | 771.85 | 468.87 | 1348.55 | 363.76 | 0.00 | 0.00 | 0.00 |
May | 1023.08 | 530.11 | 492.96 | 1142.17 | 197.99 | 0.00 | 0.00 | 0.00 |
June | 934.11 | 382.87 | 551.24 | 1068.58 | 106.38 | 0.00 | 0.00 | 0.00 |
July | 899.99 | 391.95 | 508.04 | 1050.20 | 115.92 | 0.00 | 0.00 | 0.00 |
August | 932.03 | 513.65 | 418.37 | 1070.94 | 174.31 | 0.00 | 0.00 | 0.00 |
September | 753.25 | 453.64 | 299.60 | 788.70 | 301.77 | 0.00 | 0.00 | 0.00 |
October | 542.34 | 344.10 | 198.24 | 494.52 | 477.52 | 0.00 | 0.00 | 0.00 |
November | 290.78 | 203.04 | 87.74 | 199.92 | 810.53 | 0.00 | 0.00 | 0.00 |
December | 51.62 | 36.38 | 15.23 | 11.74 | 952.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.92 | 402.92 | 301.01 | 733.78 | 464.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.62 | 36.38 | 15.23 | 11.74 | 106.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1240.72 | 771.85 | 551.24 | 1348.55 | 952.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.25 | 6.83 | 31.42 | 0.00 | 1880.52 | 0.00 | 0.00 | 0.00 |
February | 225.79 | 78.51 | 147.28 | 49.95 | 1585.59 | 0.00 | 0.00 | 0.00 |
March | 677.72 | 291.34 | 386.38 | 401.79 | 1138.78 | 0.00 | 0.00 | 0.00 |
April | 1608.16 | 833.36 | 774.80 | 1545.71 | 669.40 | 0.00 | 0.00 | 0.00 |
May | 1563.68 | 712.10 | 851.58 | 1585.00 | 347.44 | 0.00 | 0.00 | 0.00 |
June | 1713.72 | 730.68 | 983.04 | 1871.25 | 189.37 | 0.00 | 0.00 | 0.00 |
July | 1433.89 | 542.40 | 891.49 | 1576.53 | 207.71 | 0.00 | 0.00 | 0.00 |
August | 1178.50 | 499.04 | 679.46 | 1226.57 | 317.77 | 0.00 | 0.00 | 0.00 |
September | 713.22 | 298.67 | 414.55 | 580.04 | 579.17 | 0.00 | 0.00 | 0.00 |
October | 279.32 | 83.97 | 195.35 | 106.81 | 1037.48 | 0.00 | 0.00 | 0.00 |
November | 111.76 | 40.60 | 71.15 | 13.02 | 1806.79 | 0.00 | 0.00 | 0.00 |
December | 10.03 | 1.05 | 8.98 | 0.00 | 2007.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 798.22 | 343.94 | 454.29 | 749.31 | 977.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.03 | 1.05 | 8.98 | 0.00 | 189.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1713.72 | 833.36 | 983.04 | 1871.25 | 2007.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.51 | 0.27 | 1.24 | 0.00 | 74.35 | 0.00 | 0.00 | 0.00 |
February | 8.93 | 3.10 | 5.82 | 1.97 | 62.69 | 0.00 | 0.00 | 0.00 |
March | 26.80 | 11.52 | 15.28 | 15.89 | 45.03 | 0.00 | 0.00 | 0.00 |
April | 63.59 | 32.95 | 30.63 | 61.12 | 26.47 | 0.00 | 0.00 | 0.00 |
May | 61.83 | 28.16 | 33.67 | 62.67 | 13.74 | 0.00 | 0.00 | 0.00 |
June | 67.76 | 28.89 | 38.87 | 73.99 | 7.49 | 0.00 | 0.00 | 0.00 |
July | 56.69 | 21.45 | 35.25 | 62.33 | 8.21 | 0.00 | 0.00 | 0.00 |
August | 46.60 | 19.73 | 26.87 | 48.50 | 12.56 | 0.00 | 0.00 | 0.00 |
September | 28.20 | 11.81 | 16.39 | 22.93 | 22.90 | 0.00 | 0.00 | 0.00 |
October | 11.04 | 3.32 | 7.72 | 4.22 | 41.02 | 0.00 | 0.00 | 0.00 |
November | 4.42 | 1.61 | 2.81 | 0.51 | 71.44 | 0.00 | 0.00 | 0.00 |
December | 0.40 | 0.04 | 0.36 | 0.00 | 79.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.56 | 13.60 | 17.96 | 29.63 | 38.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.40 | 0.04 | 0.36 | 0.00 | 7.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.76 | 32.95 | 38.87 | 73.99 | 79.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.04 | 0.00 | 43.04 | 0.00 | 3000.31 | 0.00 | 0.00 | 0.00 |
February | 190.26 | 0.00 | 190.26 | 0.00 | 2681.85 | 0.00 | 0.00 | 0.00 |
March | 508.87 | 0.00 | 508.87 | 47.35 | 1978.77 | 0.00 | 0.00 | 0.00 |
April | 920.69 | 20.27 | 900.42 | 378.91 | 1062.09 | 0.00 | 0.00 | 0.00 |
May | 1411.11 | 224.35 | 1186.76 | 1074.04 | 483.86 | 0.00 | 0.00 | 0.00 |
June | 1841.11 | 409.44 | 1431.66 | 1772.82 | 225.69 | 0.00 | 0.00 | 0.00 |
July | 1545.21 | 251.16 | 1294.05 | 1518.15 | 276.04 | 0.00 | 0.00 | 0.00 |
August | 986.68 | 55.14 | 931.54 | 790.27 | 461.41 | 0.00 | 0.00 | 0.00 |
September | 550.46 | 0.55 | 549.90 | 206.18 | 923.55 | 0.00 | 0.00 | 0.00 |
October | 267.85 | 0.00 | 267.85 | 20.42 | 1693.36 | 0.00 | 0.00 | 0.00 |
November | 83.12 | 0.00 | 83.12 | 0.00 | 2939.72 | 0.00 | 0.00 | 0.00 |
December | 13.06 | 0.00 | 13.06 | 0.00 | 3162.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 699.29 | 80.43 | 618.85 | 486.83 | 1568.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.06 | 0.00 | 13.06 | 0.00 | 225.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1841.11 | 409.44 | 1431.66 | 1772.82 | 3162.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.59 | 23.79 | 51.80 | 7.05 | 1938.14 | 0.00 | 0.00 | 0.00 |
February | 417.63 | 199.28 | 218.35 | 221.19 | 1616.32 | 0.00 | 0.00 | 0.00 |
March | 1191.24 | 603.26 | 587.98 | 995.58 | 1187.26 | 0.00 | 0.00 | 0.00 |
April | 1637.41 | 828.36 | 809.06 | 1493.18 | 655.10 | 0.00 | 0.00 | 0.00 |
May | 2378.69 | 1339.08 | 1039.61 | 2551.43 | 347.50 | 0.00 | 0.00 | 0.00 |
June | 2188.45 | 1019.53 | 1168.91 | 2425.88 | 171.71 | 0.00 | 0.00 | 0.00 |
July | 2078.74 | 1006.64 | 1072.10 | 2359.73 | 197.61 | 0.00 | 0.00 | 0.00 |
August | 1646.50 | 800.73 | 845.77 | 1788.71 | 309.51 | 0.00 | 0.00 | 0.00 |
September | 1018.56 | 445.87 | 572.69 | 931.03 | 576.82 | 0.00 | 0.00 | 0.00 |
October | 538.01 | 215.88 | 322.13 | 382.26 | 1027.36 | 0.00 | 0.00 | 0.00 |
November | 114.44 | 39.99 | 74.45 | 9.91 | 1883.62 | 0.00 | 0.00 | 0.00 |
December | 16.35 | 3.91 | 12.44 | 0.00 | 2093.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1112.71 | 546.26 | 566.45 | 1103.07 | 997.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.35 | 3.91 | 12.44 | 0.00 | 171.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2378.69 | 1339.08 | 1168.91 | 2551.43 | 2093.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 516.35 | 340.19 | 176.16 | 302.18 | 2693.17 | 0.00 | 0.00 | 0.00 |
February | 1776.79 | 1235.94 | 540.85 | 1493.72 | 2168.73 | 0.00 | 0.00 | 0.00 |
March | 3051.12 | 2068.08 | 983.04 | 2945.88 | 1667.34 | 0.00 | 0.00 | 0.00 |
April | 3722.27 | 2315.63 | 1406.65 | 3991.55 | 1099.15 | 0.00 | 0.00 | 0.00 |
May | 3069.34 | 1590.39 | 1478.95 | 3379.41 | 606.93 | 0.00 | 0.00 | 0.00 |
June | 2802.42 | 1148.64 | 1653.78 | 3171.03 | 326.71 | 0.00 | 0.00 | 0.00 |
July | 2700.05 | 1175.87 | 1524.18 | 3127.74 | 348.61 | 0.00 | 0.00 | 0.00 |
August | 2796.18 | 1541.01 | 1255.16 | 3191.44 | 513.86 | 0.00 | 0.00 | 0.00 |
September | 2259.81 | 1360.97 | 898.84 | 2345.81 | 888.56 | 0.00 | 0.00 | 0.00 |
October | 1627.07 | 1032.33 | 594.74 | 1465.28 | 1433.07 | 0.00 | 0.00 | 0.00 |
November | 872.38 | 609.15 | 263.23 | 577.59 | 2515.47 | 0.00 | 0.00 | 0.00 |
December | 154.85 | 109.15 | 45.70 | 28.00 | 3002.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2111.84 | 1208.78 | 903.05 | 2169.98 | 1435.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 154.85 | 109.15 | 45.70 | 28.00 | 326.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3722.27 | 2315.63 | 1653.78 | 3991.55 | 3002.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.76 | 7.10 | 32.67 | 0.00 | 1976.44 | 0.00 | 0.00 | 0.00 |
February | 234.72 | 81.62 | 153.10 | 49.95 | 1678.20 | 0.00 | 0.00 | 0.00 |
March | 704.52 | 302.87 | 401.66 | 405.58 | 1212.62 | 0.00 | 0.00 | 0.00 |
April | 1671.76 | 866.32 | 805.44 | 1582.79 | 707.57 | 0.00 | 0.00 | 0.00 |
May | 1625.52 | 740.27 | 885.26 | 1623.34 | 372.93 | 0.00 | 0.00 | 0.00 |
June | 1781.49 | 759.58 | 1021.91 | 1928.76 | 202.37 | 0.00 | 0.00 | 0.00 |
July | 1490.59 | 563.85 | 926.74 | 1627.55 | 219.45 | 0.00 | 0.00 | 0.00 |
August | 1225.10 | 518.77 | 706.33 | 1270.17 | 327.43 | 0.00 | 0.00 | 0.00 |
September | 741.43 | 310.48 | 430.95 | 601.93 | 592.16 | 0.00 | 0.00 | 0.00 |
October | 290.37 | 87.29 | 203.07 | 110.55 | 1069.59 | 0.00 | 0.00 | 0.00 |
November | 116.18 | 42.21 | 73.97 | 13.38 | 1878.67 | 0.00 | 0.00 | 0.00 |
December | 10.43 | 1.10 | 9.33 | 0.00 | 2099.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 829.79 | 357.54 | 472.25 | 770.84 | 1024.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.43 | 1.10 | 9.33 | 0.00 | 202.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1781.49 | 866.32 | 1021.91 | 1928.76 | 2099.98 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115282E+09 | 0.00 | 0.115282E+09 | 0.00 | 0.789906E+10 |
February | 0.460285E+09 | 0.00 | 0.460285E+09 | 0.00 | 0.635029E+10 |
March | 0.136296E+10 | 0.00 | 0.136296E+10 | 0.137354E+09 | 0.513421E+10 |
April | 0.238644E+10 | 52546477.35 | 0.233389E+10 | 0.103911E+10 | 0.259634E+10 |
May | 0.377951E+10 | 0.600895E+09 | 0.317862E+10 | 0.295017E+10 | 0.123058E+10 |
June | 0.477215E+10 | 0.106128E+10 | 0.371087E+10 | 0.461900E+10 | 0.562469E+09 |
July | 0.413869E+10 | 0.672709E+09 | 0.346598E+10 | 0.408966E+10 | 0.711486E+09 |
August | 0.264273E+10 | 0.147695E+09 | 0.249503E+10 | 0.216018E+10 | 0.117110E+10 |
September | 0.142679E+10 | 1436678.12 | 0.142535E+10 | 0.592375E+09 | 0.221332E+10 |
October | 0.717401E+09 | 0.00 | 0.717401E+09 | 69785818.09 | 0.432671E+10 |
November | 0.215453E+09 | 0.00 | 0.215453E+09 | 0.00 | 0.746353E+10 |
December | 34970479.77 | 0.00 | 34970479.77 | 0.00 | 0.832976E+10 |
Annual Sum or Average | 0.220527E+11 | 0.253656E+10 | 0.195161E+11 | 0.156576E+11 | 0.479889E+11 |
Minimum of Months | 34970479.77 | 0.00 | 34970479.77 | 0.00 | 0.562469E+09 |
Maximum of Months | 0.477215E+10 | 0.106128E+10 | 0.371087E+10 | 0.461900E+10 | 0.832976E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202455E+09 | 63715139.11 | 0.138740E+09 | 19408292.27 | 0.510518E+10 |
February | 0.101033E+10 | 0.482098E+09 | 0.528232E+09 | 0.543144E+09 | 0.382682E+10 |
March | 0.319061E+10 | 0.161576E+10 | 0.157485E+10 | 0.269201E+10 | 0.307836E+10 |
April | 0.424418E+10 | 0.214710E+10 | 0.209708E+10 | 0.391149E+10 | 0.161108E+10 |
May | 0.637108E+10 | 0.358659E+10 | 0.278450E+10 | 0.686086E+10 | 0.891248E+09 |
June | 0.567246E+10 | 0.264263E+10 | 0.302982E+10 | 0.629773E+10 | 0.429880E+09 |
July | 0.556770E+10 | 0.269620E+10 | 0.287151E+10 | 0.632890E+10 | 0.511434E+09 |
August | 0.440998E+10 | 0.214466E+10 | 0.226532E+10 | 0.480858E+10 | 0.792514E+09 |
September | 0.264011E+10 | 0.115568E+10 | 0.148442E+10 | 0.245476E+10 | 0.139895E+10 |
October | 0.144101E+10 | 0.578218E+09 | 0.862795E+09 | 0.104751E+10 | 0.262524E+10 |
November | 0.296634E+09 | 0.103654E+09 | 0.192980E+09 | 26819985.04 | 0.478401E+10 |
December | 43792763.19 | 10483189.90 | 33309573.29 | 0.00 | 0.552039E+10 |
Annual Sum or Average | 0.350903E+11 | 0.172268E+11 | 0.178636E+11 | 0.349912E+11 | 0.305751E+11 |
Minimum of Months | 43792763.19 | 10483189.90 | 33309573.29 | 0.00 | 0.429880E+09 |
Maximum of Months | 0.637108E+10 | 0.358659E+10 | 0.302982E+10 | 0.686086E+10 | 0.552039E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138300E+10 | 0.911169E+09 | 0.471828E+09 | 0.818343E+09 | 0.708563E+10 |
February | 0.429842E+10 | 0.298999E+10 | 0.130843E+10 | 0.364314E+10 | 0.511758E+10 |
March | 0.817212E+10 | 0.553914E+10 | 0.263297E+10 | 0.793484E+10 | 0.430755E+10 |
April | 0.964814E+10 | 0.600211E+10 | 0.364603E+10 | 0.103896E+11 | 0.270401E+10 |
May | 0.822091E+10 | 0.425971E+10 | 0.396121E+10 | 0.908062E+10 | 0.153912E+10 |
June | 0.726388E+10 | 0.297727E+10 | 0.428661E+10 | 0.823035E+10 | 0.810018E+09 |
July | 0.723182E+10 | 0.314945E+10 | 0.408236E+10 | 0.838898E+10 | 0.895743E+09 |
August | 0.748928E+10 | 0.412745E+10 | 0.336183E+10 | 0.856948E+10 | 0.130811E+10 |
September | 0.585744E+10 | 0.352764E+10 | 0.232979E+10 | 0.613544E+10 | 0.215591E+10 |
October | 0.435795E+10 | 0.276500E+10 | 0.159295E+10 | 0.397698E+10 | 0.365375E+10 |
November | 0.226121E+10 | 0.157891E+10 | 0.682301E+09 | 0.151527E+10 | 0.637294E+10 |
December | 0.414763E+09 | 0.292350E+09 | 0.122412E+09 | 76345473.23 | 0.790833E+10 |
Annual Sum or Average | 0.665989E+11 | 0.381202E+11 | 0.284787E+11 | 0.687594E+11 | 0.438587E+11 |
Minimum of Months | 0.414763E+09 | 0.292350E+09 | 0.122412E+09 | 76345473.23 | 0.810018E+09 |
Maximum of Months | 0.964814E+10 | 0.600211E+10 | 0.428661E+10 | 0.103896E+11 | 0.790833E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106498E+09 | 19004597.74 | 87493026.84 | 0.00 | 0.520792E+10 |
February | 0.567841E+09 | 0.197455E+09 | 0.370386E+09 | 0.123238E+09 | 0.397373E+10 |
March | 0.188699E+10 | 0.811195E+09 | 0.107580E+10 | 0.109954E+10 | 0.314306E+10 |
April | 0.433321E+10 | 0.224550E+10 | 0.208771E+10 | 0.413519E+10 | 0.173670E+10 |
May | 0.435380E+10 | 0.198273E+10 | 0.237107E+10 | 0.437762E+10 | 0.943205E+09 |
June | 0.461763E+10 | 0.196884E+10 | 0.264879E+10 | 0.501002E+10 | 0.501772E+09 |
July | 0.399241E+10 | 0.151022E+10 | 0.248218E+10 | 0.437030E+10 | 0.563535E+09 |
August | 0.328132E+10 | 0.138948E+10 | 0.189184E+10 | 0.342464E+10 | 0.831101E+09 |
September | 0.192179E+10 | 0.804767E+09 | 0.111702E+10 | 0.159658E+10 | 0.143017E+10 |
October | 0.777721E+09 | 0.233811E+09 | 0.543910E+09 | 0.310899E+09 | 0.273363E+10 |
November | 0.301130E+09 | 0.109411E+09 | 0.191719E+09 | 35978943.08 | 0.477140E+10 |
December | 27935562.83 | 2936530.56 | 24999032.28 | 0.00 | 0.553889E+10 |
Annual Sum or Average | 0.261683E+11 | 0.112754E+11 | 0.148929E+11 | 0.244840E+11 | 0.313751E+11 |
Minimum of Months | 27935562.83 | 2936530.56 | 24999032.28 | 0.00 | 0.501772E+09 |
Maximum of Months | 0.461763E+10 | 0.224550E+10 | 0.264879E+10 | 0.501002E+10 | 0.553889E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38425449.03 | 0.00 | 38425449.03 | 0.00 | 0.264423E+10 |
February | 0.153421E+09 | 0.00 | 0.153421E+09 | 0.00 | 0.211885E+10 |
March | 0.454299E+09 | 0.00 | 0.454299E+09 | 47396151.02 | 0.171761E+10 |
April | 0.795442E+09 | 17514663.76 | 0.777928E+09 | 0.362467E+09 | 0.872317E+09 |
May | 0.125978E+10 | 0.200289E+09 | 0.105949E+10 | 0.100986E+10 | 0.406431E+09 |
June | 0.159064E+10 | 0.353742E+09 | 0.123690E+10 | 0.156229E+10 | 0.184904E+09 |
July | 0.137950E+10 | 0.224226E+09 | 0.115527E+10 | 0.137663E+10 | 0.238143E+09 |
August | 0.880868E+09 | 49229389.61 | 0.831639E+09 | 0.716954E+09 | 0.405654E+09 |
September | 0.475574E+09 | 478870.05 | 0.475095E+09 | 0.182848E+09 | 0.797777E+09 |
October | 0.239122E+09 | 0.00 | 0.239122E+09 | 18571079.44 | 0.152066E+10 |
November | 71814425.66 | 0.00 | 71814425.66 | 0.00 | 0.253834E+10 |
December | 11656275.08 | 0.00 | 11656275.08 | 0.00 | 0.280434E+10 |
Annual Sum or Average | 0.735054E+10 | 0.845480E+09 | 0.650506E+10 | 0.527701E+10 | 0.162493E+11 |
Minimum of Months | 11656275.08 | 0.00 | 11656275.08 | 0.00 | 0.184904E+09 |
Maximum of Months | 0.159064E+10 | 0.353742E+09 | 0.123690E+10 | 0.156229E+10 | 0.280434E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38427877.45 | 0.00 | 38427877.45 | 0.00 | 0.264440E+10 |
February | 0.153431E+09 | 0.00 | 0.153431E+09 | 0.00 | 0.211899E+10 |
March | 0.454328E+09 | 0.00 | 0.454328E+09 | 47399146.38 | 0.171772E+10 |
April | 0.795493E+09 | 17515770.65 | 0.777977E+09 | 0.362490E+09 | 0.872373E+09 |
May | 0.125986E+10 | 0.200302E+09 | 0.105956E+10 | 0.100992E+10 | 0.406457E+09 |
June | 0.159074E+10 | 0.353765E+09 | 0.123698E+10 | 0.156239E+10 | 0.184915E+09 |
July | 0.137959E+10 | 0.224240E+09 | 0.115535E+10 | 0.137671E+10 | 0.238158E+09 |
August | 0.880924E+09 | 49232500.83 | 0.831691E+09 | 0.716999E+09 | 0.405679E+09 |
September | 0.475604E+09 | 478900.31 | 0.475125E+09 | 0.182860E+09 | 0.797828E+09 |
October | 0.239138E+09 | 0.00 | 0.239138E+09 | 18572253.10 | 0.152076E+10 |
November | 71818964.21 | 0.00 | 71818964.21 | 0.00 | 0.253850E+10 |
December | 11657011.74 | 0.00 | 11657011.74 | 0.00 | 0.280451E+10 |
Annual Sum or Average | 0.735101E+10 | 0.845533E+09 | 0.650547E+10 | 0.527735E+10 | 0.162503E+11 |
Minimum of Months | 11657011.74 | 0.00 | 11657011.74 | 0.00 | 0.184915E+09 |
Maximum of Months | 0.159074E+10 | 0.353765E+09 | 0.123698E+10 | 0.156239E+10 | 0.280451E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38427877.45 | 0.00 | 38427877.45 | 0.00 | 0.264440E+10 |
February | 0.153431E+09 | 0.00 | 0.153431E+09 | 0.00 | 0.211899E+10 |
March | 0.454328E+09 | 0.00 | 0.454328E+09 | 47399146.38 | 0.171772E+10 |
April | 0.795493E+09 | 17515770.65 | 0.777977E+09 | 0.362490E+09 | 0.872373E+09 |
May | 0.125986E+10 | 0.200302E+09 | 0.105956E+10 | 0.100992E+10 | 0.406457E+09 |
June | 0.159074E+10 | 0.353765E+09 | 0.123698E+10 | 0.156239E+10 | 0.184915E+09 |
July | 0.137959E+10 | 0.224240E+09 | 0.115535E+10 | 0.137671E+10 | 0.238158E+09 |
August | 0.880924E+09 | 49232500.83 | 0.831691E+09 | 0.716999E+09 | 0.405679E+09 |
September | 0.475604E+09 | 478900.31 | 0.475125E+09 | 0.182860E+09 | 0.797828E+09 |
October | 0.239138E+09 | 0.00 | 0.239138E+09 | 18572253.10 | 0.152076E+10 |
November | 71818964.21 | 0.00 | 71818964.21 | 0.00 | 0.253850E+10 |
December | 11657011.74 | 0.00 | 11657011.74 | 0.00 | 0.280451E+10 |
Annual Sum or Average | 0.735101E+10 | 0.845533E+09 | 0.650547E+10 | 0.527735E+10 | 0.162503E+11 |
Minimum of Months | 11657011.74 | 0.00 | 11657011.74 | 0.00 | 0.184915E+09 |
Maximum of Months | 0.159074E+10 | 0.353765E+09 | 0.123698E+10 | 0.156239E+10 | 0.280451E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194753E+09 | 61291100.40 | 0.133462E+09 | 19184552.67 | 0.493710E+10 |
February | 0.971893E+09 | 0.463757E+09 | 0.508136E+09 | 0.524790E+09 | 0.369558E+10 |
March | 0.306923E+10 | 0.155429E+10 | 0.151494E+10 | 0.260652E+10 | 0.299992E+10 |
April | 0.408272E+10 | 0.206541E+10 | 0.201730E+10 | 0.378077E+10 | 0.160705E+10 |
May | 0.612871E+10 | 0.345013E+10 | 0.267857E+10 | 0.662235E+10 | 0.894304E+09 |
June | 0.545666E+10 | 0.254210E+10 | 0.291456E+10 | 0.608747E+10 | 0.423910E+09 |
July | 0.535589E+10 | 0.259362E+10 | 0.276227E+10 | 0.610321E+10 | 0.513671E+09 |
August | 0.424221E+10 | 0.206307E+10 | 0.217914E+10 | 0.462067E+10 | 0.814773E+09 |
September | 0.253967E+10 | 0.111172E+10 | 0.142795E+10 | 0.231853E+10 | 0.148140E+10 |
October | 0.138619E+10 | 0.556220E+09 | 0.829972E+09 | 0.986752E+09 | 0.268393E+10 |
November | 0.285349E+09 | 99710194.74 | 0.185639E+09 | 25184444.20 | 0.469278E+10 |
December | 42126734.43 | 10084357.56 | 32042376.87 | 0.00 | 0.535873E+10 |
Annual Sum or Average | 0.337554E+11 | 0.165714E+11 | 0.171840E+11 | 0.336954E+11 | 0.301032E+11 |
Minimum of Months | 42126734.43 | 10084357.56 | 32042376.87 | 0.00 | 0.423910E+09 |
Maximum of Months | 0.612871E+10 | 0.345013E+10 | 0.291456E+10 | 0.662235E+10 | 0.535873E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7700356.42 | 2423394.93 | 5276961.49 | 758539.94 | 0.195208E+09 |
February | 38427777.84 | 18336519.76 | 20091258.08 | 20749739.10 | 0.146120E+09 |
March | 0.121355E+09 | 61455198.34 | 59899307.21 | 0.103060E+09 | 0.118614E+09 |
April | 0.161427E+09 | 81664603.48 | 79762303.54 | 0.149488E+09 | 63541462.78 |
May | 0.242324E+09 | 0.136415E+09 | 0.105908E+09 | 0.261842E+09 | 35359986.13 |
June | 0.215751E+09 | 0.100512E+09 | 0.115239E+09 | 0.240693E+09 | 16761038.60 |
July | 0.211767E+09 | 0.102549E+09 | 0.109218E+09 | 0.241315E+09 | 20310080.35 |
August | 0.167733E+09 | 81571912.55 | 86161249.25 | 0.182697E+09 | 32215379.66 |
September | 0.100416E+09 | 43956269.44 | 56460008.77 | 91672776.91 | 58573220.68 |
October | 54808781.96 | 21992444.70 | 32816337.26 | 39015304.58 | 0.106120E+09 |
November | 11282449.76 | 3942451.33 | 7339998.43 | 995770.25 | 0.185548E+09 |
December | 1665653.15 | 398726.42 | 1266926.73 | 0.00 | 0.211880E+09 |
Annual Sum or Average | 0.133466E+10 | 0.655218E+09 | 0.679440E+09 | 0.133229E+10 | 0.119025E+10 |
Minimum of Months | 1665653.15 | 398726.42 | 1266926.73 | 0.00 | 16761038.60 |
Maximum of Months | 0.242324E+09 | 0.136415E+09 | 0.115239E+09 | 0.261842E+09 | 0.211880E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.461014E+09 | 0.303733E+09 | 0.157281E+09 | 0.284513E+09 | 0.228636E+10 |
February | 0.143285E+10 | 0.996696E+09 | 0.436156E+09 | 0.123781E+10 | 0.167511E+10 |
March | 0.272413E+10 | 0.184644E+10 | 0.877684E+09 | 0.269440E+10 | 0.143550E+10 |
April | 0.321615E+10 | 0.200077E+10 | 0.121538E+10 | 0.349567E+10 | 0.942935E+09 |
May | 0.274039E+10 | 0.141995E+10 | 0.132044E+10 | 0.305938E+10 | 0.530317E+09 |
June | 0.242137E+10 | 0.992457E+09 | 0.142891E+10 | 0.276994E+10 | 0.275745E+09 |
July | 0.241068E+10 | 0.104985E+10 | 0.136083E+10 | 0.281303E+10 | 0.310503E+09 |
August | 0.249650E+10 | 0.137586E+10 | 0.112064E+10 | 0.286858E+10 | 0.466911E+09 |
September | 0.195254E+10 | 0.117592E+10 | 0.776621E+09 | 0.204443E+10 | 0.782227E+09 |
October | 0.145270E+10 | 0.921697E+09 | 0.531001E+09 | 0.132461E+10 | 0.127906E+10 |
November | 0.753761E+09 | 0.526320E+09 | 0.227441E+09 | 0.518218E+09 | 0.210102E+10 |
December | 0.138259E+09 | 97453346.43 | 40805366.93 | 31439961.89 | 0.255067E+10 |
Annual Sum or Average | 0.222003E+11 | 0.127071E+11 | 0.949319E+10 | 0.231420E+11 | 0.146364E+11 |
Minimum of Months | 0.138259E+09 | 97453346.43 | 40805366.93 | 31439961.89 | 0.275745E+09 |
Maximum of Months | 0.321615E+10 | 0.200077E+10 | 0.142891E+10 | 0.349567E+10 | 0.255067E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.461014E+09 | 0.303733E+09 | 0.157281E+09 | 0.284513E+09 | 0.228636E+10 |
February | 0.143285E+10 | 0.996696E+09 | 0.436156E+09 | 0.123781E+10 | 0.167511E+10 |
March | 0.272413E+10 | 0.184644E+10 | 0.877684E+09 | 0.269440E+10 | 0.143550E+10 |
April | 0.321615E+10 | 0.200077E+10 | 0.121538E+10 | 0.349567E+10 | 0.942935E+09 |
May | 0.274039E+10 | 0.141995E+10 | 0.132044E+10 | 0.305938E+10 | 0.530317E+09 |
June | 0.242137E+10 | 0.992457E+09 | 0.142891E+10 | 0.276994E+10 | 0.275745E+09 |
July | 0.241068E+10 | 0.104985E+10 | 0.136083E+10 | 0.281303E+10 | 0.310503E+09 |
August | 0.249650E+10 | 0.137586E+10 | 0.112064E+10 | 0.286858E+10 | 0.466911E+09 |
September | 0.195254E+10 | 0.117592E+10 | 0.776621E+09 | 0.204443E+10 | 0.782227E+09 |
October | 0.145270E+10 | 0.921697E+09 | 0.531001E+09 | 0.132461E+10 | 0.127906E+10 |
November | 0.753761E+09 | 0.526320E+09 | 0.227441E+09 | 0.518218E+09 | 0.210102E+10 |
December | 0.138259E+09 | 97453346.43 | 40805366.93 | 31439961.89 | 0.255067E+10 |
Annual Sum or Average | 0.222003E+11 | 0.127071E+11 | 0.949319E+10 | 0.231420E+11 | 0.146364E+11 |
Minimum of Months | 0.138259E+09 | 97453346.43 | 40805366.93 | 31439961.89 | 0.275745E+09 |
Maximum of Months | 0.321615E+10 | 0.200077E+10 | 0.142891E+10 | 0.349567E+10 | 0.255067E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.460985E+09 | 0.303714E+09 | 0.157271E+09 | 0.284495E+09 | 0.228621E+10 |
February | 0.143276E+10 | 0.996633E+09 | 0.436129E+09 | 0.123773E+10 | 0.167500E+10 |
March | 0.272395E+10 | 0.184632E+10 | 0.877629E+09 | 0.269423E+10 | 0.143541E+10 |
April | 0.321594E+10 | 0.200064E+10 | 0.121530E+10 | 0.349545E+10 | 0.942875E+09 |
May | 0.274022E+10 | 0.141986E+10 | 0.132036E+10 | 0.305918E+10 | 0.530284E+09 |
June | 0.242121E+10 | 0.992394E+09 | 0.142882E+10 | 0.276976E+10 | 0.275727E+09 |
July | 0.241053E+10 | 0.104979E+10 | 0.136074E+10 | 0.281285E+10 | 0.310484E+09 |
August | 0.249635E+10 | 0.137577E+10 | 0.112057E+10 | 0.286840E+10 | 0.466882E+09 |
September | 0.195242E+10 | 0.117584E+10 | 0.776572E+09 | 0.204430E+10 | 0.782178E+09 |
October | 0.145261E+10 | 0.921638E+09 | 0.530967E+09 | 0.132453E+10 | 0.127898E+10 |
November | 0.753713E+09 | 0.526287E+09 | 0.227427E+09 | 0.518185E+09 | 0.210089E+10 |
December | 0.138250E+09 | 97447187.93 | 40802788.27 | 31437975.06 | 0.255051E+10 |
Annual Sum or Average | 0.221989E+11 | 0.127063E+11 | 0.949259E+10 | 0.231406E+11 | 0.146354E+11 |
Minimum of Months | 0.138250E+09 | 97447187.93 | 40802788.27 | 31437975.06 | 0.275727E+09 |
Maximum of Months | 0.321594E+10 | 0.200064E+10 | 0.142882E+10 | 0.349545E+10 | 0.255051E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102446E+09 | 18281573.28 | 84164624.60 | 0.00 | 0.503678E+10 |
February | 0.546239E+09 | 0.189943E+09 | 0.356296E+09 | 0.120831E+09 | 0.383586E+10 |
March | 0.181521E+10 | 0.780334E+09 | 0.103487E+10 | 0.107615E+10 | 0.305010E+10 |
April | 0.416836E+10 | 0.216007E+10 | 0.200829E+10 | 0.400648E+10 | 0.173510E+10 |
May | 0.418817E+10 | 0.190730E+10 | 0.228087E+10 | 0.424525E+10 | 0.930596E+09 |
June | 0.444196E+10 | 0.189393E+10 | 0.254803E+10 | 0.485029E+10 | 0.490844E+09 |
July | 0.384053E+10 | 0.145277E+10 | 0.238776E+10 | 0.422256E+10 | 0.556331E+09 |
August | 0.315649E+10 | 0.133662E+10 | 0.181987E+10 | 0.328525E+10 | 0.851106E+09 |
September | 0.184868E+10 | 0.774150E+09 | 0.107453E+10 | 0.150347E+10 | 0.150121E+10 |
October | 0.748135E+09 | 0.224916E+09 | 0.523219E+09 | 0.286093E+09 | 0.277880E+10 |
November | 0.289674E+09 | 0.105248E+09 | 0.184426E+09 | 33748055.64 | 0.468320E+10 |
December | 26872825.67 | 2824811.10 | 24048014.58 | 0.00 | 0.537746E+10 |
Annual Sum or Average | 0.251728E+11 | 0.108464E+11 | 0.143264E+11 | 0.236301E+11 | 0.308274E+11 |
Minimum of Months | 26872825.67 | 2824811.10 | 24048014.58 | 0.00 | 0.490844E+09 |
Maximum of Months | 0.444196E+10 | 0.216007E+10 | 0.254803E+10 | 0.485029E+10 | 0.537746E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4050619.46 | 722834.60 | 3327784.86 | 0.00 | 0.199150E+09 |
February | 21597725.53 | 7510146.99 | 14087578.54 | 4777510.15 | 0.151666E+09 |
March | 71771443.10 | 30853587.48 | 40917855.62 | 42549869.13 | 0.120598E+09 |
April | 0.164813E+09 | 85406933.25 | 79405888.08 | 0.158412E+09 | 68604130.51 |
May | 0.165596E+09 | 75412635.58 | 90183438.78 | 0.167853E+09 | 36794929.22 |
June | 0.175631E+09 | 74884125.96 | 0.100747E+09 | 0.191775E+09 | 19407516.52 |
July | 0.151850E+09 | 57440944.61 | 94409550.51 | 0.166956E+09 | 21996815.58 |
August | 0.124804E+09 | 52848511.70 | 71955899.77 | 0.129896E+09 | 33651979.61 |
September | 73094754.77 | 30609083.16 | 42485671.61 | 59445424.58 | 59356379.84 |
October | 29580495.59 | 8892928.46 | 20687567.14 | 11311802.76 | 0.109871E+09 |
November | 11453402.50 | 4161403.46 | 7291999.05 | 1334353.03 | 0.185169E+09 |
December | 1062524.45 | 111690.13 | 950834.32 | 0.00 | 0.212620E+09 |
Annual Sum or Average | 0.995305E+09 | 0.428855E+09 | 0.566451E+09 | 0.934310E+09 | 0.121889E+10 |
Minimum of Months | 1062524.45 | 111690.13 | 950834.32 | 0.00 | 19407516.52 |
Maximum of Months | 0.175631E+09 | 85406933.25 | 0.100747E+09 | 0.191775E+09 | 0.212620E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115282E+09 | 0.00 | 0.115282E+09 | 0.00 | 0.803602E+10 |
February | 0.460285E+09 | 0.00 | 0.460285E+09 | 0.00 | 0.648794E+10 |
March | 0.136296E+10 | 0.00 | 0.136296E+10 | 0.126814E+09 | 0.529993E+10 |
April | 0.238644E+10 | 52546477.35 | 0.233389E+10 | 0.982141E+09 | 0.275294E+10 |
May | 0.377951E+10 | 0.600895E+09 | 0.317862E+10 | 0.287670E+10 | 0.129598E+10 |
June | 0.477215E+10 | 0.106128E+10 | 0.371087E+10 | 0.459515E+10 | 0.584991E+09 |
July | 0.413869E+10 | 0.672709E+09 | 0.346598E+10 | 0.406620E+10 | 0.739348E+09 |
August | 0.264273E+10 | 0.147695E+09 | 0.249503E+10 | 0.211665E+10 | 0.123584E+10 |
September | 0.142679E+10 | 1436678.12 | 0.142535E+10 | 0.534431E+09 | 0.239384E+10 |
October | 0.717401E+09 | 0.00 | 0.717401E+09 | 54696483.12 | 0.453550E+10 |
November | 0.215453E+09 | 0.00 | 0.215453E+09 | 0.00 | 0.761976E+10 |
December | 34970479.77 | 0.00 | 34970479.77 | 0.00 | 0.846944E+10 |
Annual Sum or Average | 0.220527E+11 | 0.253656E+10 | 0.195161E+11 | 0.153528E+11 | 0.494515E+11 |
Minimum of Months | 34970479.77 | 0.00 | 34970479.77 | 0.00 | 0.584991E+09 |
Maximum of Months | 0.477215E+10 | 0.106128E+10 | 0.371087E+10 | 0.459515E+10 | 0.846944E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202455E+09 | 63715139.11 | 0.138740E+09 | 18895187.70 | 0.519110E+10 |
February | 0.101033E+10 | 0.482098E+09 | 0.528232E+09 | 0.535109E+09 | 0.391019E+10 |
March | 0.319061E+10 | 0.161576E+10 | 0.157485E+10 | 0.266656E+10 | 0.317997E+10 |
April | 0.424418E+10 | 0.214710E+10 | 0.209708E+10 | 0.387032E+10 | 0.169802E+10 |
May | 0.637108E+10 | 0.358659E+10 | 0.278450E+10 | 0.683376E+10 | 0.930742E+09 |
June | 0.567246E+10 | 0.264263E+10 | 0.302982E+10 | 0.628789E+10 | 0.445076E+09 |
July | 0.556770E+10 | 0.269620E+10 | 0.287151E+10 | 0.632029E+10 | 0.529284E+09 |
August | 0.440998E+10 | 0.214466E+10 | 0.226532E+10 | 0.479088E+10 | 0.828983E+09 |
September | 0.264011E+10 | 0.115568E+10 | 0.148442E+10 | 0.241322E+10 | 0.149512E+10 |
October | 0.144101E+10 | 0.578218E+09 | 0.862795E+09 | 0.102385E+10 | 0.275168E+10 |
November | 0.296634E+09 | 0.103654E+09 | 0.192980E+09 | 25695724.00 | 0.488236E+10 |
December | 43792763.19 | 10483189.90 | 33309573.29 | 0.00 | 0.560657E+10 |
Annual Sum or Average | 0.350903E+11 | 0.172268E+11 | 0.178636E+11 | 0.347865E+11 | 0.314491E+11 |
Minimum of Months | 43792763.19 | 10483189.90 | 33309573.29 | 0.00 | 0.445076E+09 |
Maximum of Months | 0.637108E+10 | 0.358659E+10 | 0.302982E+10 | 0.683376E+10 | 0.560657E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138300E+10 | 0.911169E+09 | 0.471828E+09 | 0.809357E+09 | 0.721338E+10 |
February | 0.429842E+10 | 0.298999E+10 | 0.130843E+10 | 0.361360E+10 | 0.524658E+10 |
March | 0.817212E+10 | 0.553914E+10 | 0.263297E+10 | 0.789024E+10 | 0.446580E+10 |
April | 0.964814E+10 | 0.600211E+10 | 0.364603E+10 | 0.103461E+11 | 0.284899E+10 |
May | 0.822091E+10 | 0.425971E+10 | 0.396121E+10 | 0.905140E+10 | 0.162561E+10 |
June | 0.726388E+10 | 0.297727E+10 | 0.428661E+10 | 0.821931E+10 | 0.846843E+09 |
July | 0.723182E+10 | 0.314945E+10 | 0.408236E+10 | 0.837733E+10 | 0.933719E+09 |
August | 0.748928E+10 | 0.412745E+10 | 0.336183E+10 | 0.854794E+10 | 0.137632E+10 |
September | 0.585744E+10 | 0.352764E+10 | 0.232979E+10 | 0.608035E+10 | 0.230315E+10 |
October | 0.435795E+10 | 0.276500E+10 | 0.159295E+10 | 0.392460E+10 | 0.383833E+10 |
November | 0.226121E+10 | 0.157891E+10 | 0.682301E+09 | 0.149711E+10 | 0.652010E+10 |
December | 0.414763E+09 | 0.292350E+09 | 0.122412E+09 | 75001861.55 | 0.804215E+10 |
Annual Sum or Average | 0.665989E+11 | 0.381202E+11 | 0.284787E+11 | 0.684323E+11 | 0.452610E+11 |
Minimum of Months | 0.414763E+09 | 0.292350E+09 | 0.122412E+09 | 75001861.55 | 0.846843E+09 |
Maximum of Months | 0.964814E+10 | 0.600211E+10 | 0.428661E+10 | 0.103461E+11 | 0.804215E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106498E+09 | 19004597.74 | 87493026.84 | 0.00 | 0.529368E+10 |
February | 0.567841E+09 | 0.197455E+09 | 0.370386E+09 | 0.120850E+09 | 0.405990E+10 |
March | 0.188699E+10 | 0.811195E+09 | 0.107580E+10 | 0.108631E+10 | 0.324788E+10 |
April | 0.433321E+10 | 0.224550E+10 | 0.208771E+10 | 0.410258E+10 | 0.183403E+10 |
May | 0.435380E+10 | 0.198273E+10 | 0.237107E+10 | 0.434794E+10 | 0.998854E+09 |
June | 0.461763E+10 | 0.196884E+10 | 0.264879E+10 | 0.499935E+10 | 0.524547E+09 |
July | 0.399241E+10 | 0.151022E+10 | 0.248218E+10 | 0.435923E+10 | 0.587777E+09 |
August | 0.328132E+10 | 0.138948E+10 | 0.189184E+10 | 0.340203E+10 | 0.876983E+09 |
September | 0.192179E+10 | 0.804767E+09 | 0.111702E+10 | 0.156020E+10 | 0.153489E+10 |
October | 0.777721E+09 | 0.233811E+09 | 0.543910E+09 | 0.296094E+09 | 0.286479E+10 |
November | 0.301130E+09 | 0.109411E+09 | 0.191719E+09 | 34686072.13 | 0.486952E+10 |
December | 27935562.83 | 2936530.56 | 24999032.28 | 0.00 | 0.562458E+10 |
Annual Sum or Average | 0.261683E+11 | 0.112754E+11 | 0.148929E+11 | 0.243093E+11 | 0.323174E+11 |
Minimum of Months | 27935562.83 | 2936530.56 | 24999032.28 | 0.00 | 0.524547E+09 |
Maximum of Months | 0.461763E+10 | 0.224550E+10 | 0.264879E+10 | 0.499935E+10 | 0.562458E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2949.17 | 43.04 | 0.00 | 43.04 | 0.00 | 0.00 |
February | 0.00 | 2624.95 | 190.26 | 0.00 | 190.26 | 0.00 | 0.00 |
March | 51.28 | 1916.89 | 508.87 | 0.00 | 508.87 | 0.00 | 0.00 |
April | 400.89 | 1001.68 | 920.69 | 20.27 | 900.42 | 0.00 | 0.00 |
May | 1101.47 | 459.45 | 1411.11 | 224.35 | 1186.76 | 0.00 | 0.00 |
June | 1782.02 | 217.00 | 1841.11 | 409.44 | 1431.66 | 0.00 | 0.00 |
July | 1526.90 | 265.64 | 1545.21 | 251.16 | 1294.05 | 0.00 | 0.00 |
August | 806.52 | 437.24 | 986.68 | 55.14 | 931.54 | 0.00 | 0.00 |
September | 228.54 | 853.90 | 550.46 | 0.55 | 549.90 | 0.00 | 0.00 |
October | 26.06 | 1615.41 | 267.85 | 0.00 | 267.85 | 0.00 | 0.00 |
November | 0.00 | 2879.45 | 83.12 | 0.00 | 83.12 | 0.00 | 0.00 |
December | 0.00 | 3109.98 | 13.06 | 0.00 | 13.06 | 0.00 | 0.00 |
Annual Sum or Average | 496.50 | 1521.72 | 699.29 | 80.43 | 618.85 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 217.00 | 13.06 | 0.00 | 13.06 | 0.00 | 0.00 |
Maximum of Months | 1782.02 | 3109.98 | 1841.11 | 409.44 | 1431.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.25 | 1906.05 | 75.59 | 23.79 | 51.80 | 0.00 | 0.00 |
February | 224.51 | 1581.86 | 417.63 | 199.28 | 218.35 | 0.00 | 0.00 |
March | 1005.08 | 1149.33 | 1191.24 | 603.26 | 587.98 | 0.00 | 0.00 |
April | 1509.06 | 621.56 | 1637.41 | 828.36 | 809.06 | 0.00 | 0.00 |
May | 2561.55 | 332.75 | 2378.69 | 1339.08 | 1039.61 | 0.00 | 0.00 |
June | 2429.68 | 165.85 | 2188.45 | 1019.53 | 1168.91 | 0.00 | 0.00 |
July | 2362.94 | 190.95 | 2078.74 | 1006.64 | 1072.10 | 0.00 | 0.00 |
August | 1795.32 | 295.89 | 1646.50 | 800.73 | 845.77 | 0.00 | 0.00 |
September | 947.05 | 539.72 | 1018.56 | 445.87 | 572.69 | 0.00 | 0.00 |
October | 391.09 | 980.15 | 538.01 | 215.88 | 322.13 | 0.00 | 0.00 |
November | 10.35 | 1845.68 | 114.44 | 39.99 | 74.45 | 0.00 | 0.00 |
December | 0.00 | 2061.08 | 16.35 | 3.91 | 12.44 | 0.00 | 0.00 |
Annual Sum or Average | 1109.56 | 969.53 | 1112.71 | 546.26 | 566.45 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 165.85 | 16.35 | 3.91 | 12.44 | 0.00 | 0.00 |
Maximum of Months | 2561.55 | 2061.08 | 2378.69 | 1339.08 | 1168.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 305.53 | 2645.47 | 516.35 | 340.19 | 176.16 | 0.00 | 0.00 |
February | 1505.93 | 2115.40 | 1776.79 | 1235.94 | 540.85 | 0.00 | 0.00 |
March | 2962.53 | 1608.26 | 3051.12 | 2068.08 | 983.04 | 0.00 | 0.00 |
April | 4008.35 | 1043.21 | 3722.27 | 2315.63 | 1406.65 | 0.00 | 0.00 |
May | 3390.32 | 574.64 | 3069.34 | 1590.39 | 1478.95 | 0.00 | 0.00 |
June | 3175.29 | 312.51 | 2802.42 | 1148.64 | 1653.78 | 0.00 | 0.00 |
July | 3132.08 | 334.43 | 2700.05 | 1175.87 | 1524.18 | 0.00 | 0.00 |
August | 3199.48 | 488.39 | 2796.18 | 1541.01 | 1255.16 | 0.00 | 0.00 |
September | 2367.07 | 831.76 | 2259.81 | 1360.97 | 898.84 | 0.00 | 0.00 |
October | 1484.84 | 1364.15 | 1627.07 | 1032.33 | 594.74 | 0.00 | 0.00 |
November | 584.59 | 2458.70 | 872.38 | 609.15 | 263.23 | 0.00 | 0.00 |
December | 28.50 | 2952.63 | 154.85 | 109.15 | 45.70 | 0.00 | 0.00 |
Annual Sum or Average | 2180.35 | 1390.75 | 2111.84 | 1208.78 | 903.05 | 0.00 | 0.00 |
Minimum of Months | 28.50 | 312.51 | 154.85 | 109.15 | 45.70 | 0.00 | 0.00 |
Maximum of Months | 4008.35 | 2952.63 | 3722.27 | 2315.63 | 1653.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1944.42 | 39.76 | 7.10 | 32.67 | 0.00 | 0.00 |
February | 50.94 | 1642.58 | 234.72 | 81.62 | 153.10 | 0.00 | 0.00 |
March | 410.52 | 1173.49 | 704.52 | 302.87 | 401.66 | 0.00 | 0.00 |
April | 1595.37 | 670.02 | 1671.76 | 866.32 | 805.44 | 0.00 | 0.00 |
May | 1634.42 | 352.15 | 1625.52 | 740.27 | 885.26 | 0.00 | 0.00 |
June | 1932.88 | 193.58 | 1781.49 | 759.58 | 1021.91 | 0.00 | 0.00 |
July | 1631.68 | 210.40 | 1490.59 | 563.85 | 926.74 | 0.00 | 0.00 |
August | 1278.61 | 310.30 | 1225.10 | 518.77 | 706.33 | 0.00 | 0.00 |
September | 615.96 | 551.76 | 741.43 | 310.48 | 430.95 | 0.00 | 0.00 |
October | 116.08 | 1020.62 | 290.37 | 87.29 | 203.07 | 0.00 | 0.00 |
November | 13.88 | 1840.82 | 116.18 | 42.21 | 73.97 | 0.00 | 0.00 |
December | 0.00 | 2067.98 | 10.43 | 1.10 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 776.38 | 994.90 | 829.79 | 357.54 | 472.25 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 193.58 | 10.43 | 1.10 | 9.33 | 0.00 | 0.00 |
Maximum of Months | 1932.88 | 2067.98 | 1781.49 | 866.32 | 1021.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2961.86 | 43.04 | 0.00 | 43.04 | 0.00 | 0.00 |
February | 0.00 | 2627.66 | 190.26 | 0.00 | 190.26 | 0.00 | 0.00 |
March | 53.09 | 1923.93 | 508.87 | 0.00 | 508.87 | 0.00 | 0.00 |
April | 419.54 | 1009.67 | 920.69 | 20.27 | 900.42 | 0.00 | 0.00 |
May | 1131.16 | 455.25 | 1411.10 | 224.35 | 1186.75 | 0.00 | 0.00 |
June | 1808.28 | 214.02 | 1841.10 | 409.44 | 1431.66 | 0.00 | 0.00 |
July | 1541.98 | 266.75 | 1545.20 | 251.16 | 1294.04 | 0.00 | 0.00 |
August | 803.07 | 454.38 | 986.68 | 55.14 | 931.53 | 0.00 | 0.00 |
September | 211.64 | 923.39 | 550.46 | 0.55 | 549.90 | 0.00 | 0.00 |
October | 20.80 | 1703.32 | 267.85 | 0.00 | 267.85 | 0.00 | 0.00 |
November | 0.00 | 2938.01 | 83.12 | 0.00 | 83.12 | 0.00 | 0.00 |
December | 0.00 | 3141.19 | 13.06 | 0.00 | 13.06 | 0.00 | 0.00 |
Annual Sum or Average | 502.02 | 1545.85 | 699.28 | 80.43 | 618.85 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 214.02 | 13.06 | 0.00 | 13.06 | 0.00 | 0.00 |
Maximum of Months | 1808.28 | 3141.19 | 1841.10 | 409.44 | 1431.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.45 | 1916.18 | 75.59 | 23.79 | 51.80 | 0.00 | 0.00 |
February | 225.50 | 1588.00 | 417.63 | 199.28 | 218.35 | 0.00 | 0.00 |
March | 1011.64 | 1164.33 | 1191.23 | 603.25 | 587.98 | 0.00 | 0.00 |
April | 1516.30 | 644.52 | 1637.40 | 828.35 | 809.05 | 0.00 | 0.00 |
May | 2570.26 | 347.10 | 2378.67 | 1339.06 | 1039.61 | 0.00 | 0.00 |
June | 2441.42 | 170.01 | 2188.43 | 1019.52 | 1168.91 | 0.00 | 0.00 |
July | 2368.77 | 199.37 | 2078.72 | 1006.63 | 1072.09 | 0.00 | 0.00 |
August | 1793.37 | 316.23 | 1646.48 | 800.72 | 845.77 | 0.00 | 0.00 |
September | 929.86 | 594.13 | 1018.55 | 445.86 | 572.69 | 0.00 | 0.00 |
October | 382.98 | 1041.68 | 538.01 | 215.88 | 322.13 | 0.00 | 0.00 |
November | 10.10 | 1882.07 | 114.44 | 39.99 | 74.45 | 0.00 | 0.00 |
December | 0.00 | 2079.83 | 16.35 | 3.91 | 12.44 | 0.00 | 0.00 |
Annual Sum or Average | 1110.72 | 992.31 | 1112.70 | 546.25 | 566.45 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 170.01 | 16.35 | 3.91 | 12.44 | 0.00 | 0.00 |
Maximum of Months | 2570.26 | 2079.83 | 2378.67 | 1339.06 | 1168.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 318.67 | 2560.83 | 516.36 | 340.20 | 176.16 | 0.00 | 0.00 |
February | 1534.95 | 2077.22 | 1776.81 | 1235.96 | 540.86 | 0.00 | 0.00 |
March | 3017.86 | 1607.83 | 3051.15 | 2068.10 | 983.05 | 0.00 | 0.00 |
April | 4045.83 | 1091.34 | 3722.31 | 2315.65 | 1406.66 | 0.00 | 0.00 |
May | 3426.65 | 593.98 | 3069.37 | 1590.41 | 1478.96 | 0.00 | 0.00 |
June | 3205.88 | 319.14 | 2802.45 | 1148.65 | 1653.80 | 0.00 | 0.00 |
July | 3150.73 | 347.78 | 2700.08 | 1175.89 | 1524.19 | 0.00 | 0.00 |
August | 3212.95 | 522.96 | 2796.20 | 1541.03 | 1255.17 | 0.00 | 0.00 |
September | 2366.19 | 905.34 | 2259.84 | 1360.99 | 898.85 | 0.00 | 0.00 |
October | 1483.63 | 1432.61 | 1627.09 | 1032.34 | 594.75 | 0.00 | 0.00 |
November | 599.78 | 2431.69 | 872.39 | 609.15 | 263.24 | 0.00 | 0.00 |
December | 35.21 | 2856.88 | 154.86 | 109.15 | 45.70 | 0.00 | 0.00 |
Annual Sum or Average | 2201.44 | 1392.32 | 2111.86 | 1208.80 | 903.06 | 0.00 | 0.00 |
Minimum of Months | 35.21 | 319.14 | 154.86 | 109.15 | 45.70 | 0.00 | 0.00 |
Maximum of Months | 4045.83 | 2856.88 | 3722.31 | 2315.65 | 1653.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1954.87 | 39.76 | 7.10 | 32.67 | 0.00 | 0.00 |
February | 51.92 | 1648.28 | 234.72 | 81.62 | 153.10 | 0.00 | 0.00 |
March | 417.68 | 1183.80 | 704.52 | 302.86 | 401.65 | 0.00 | 0.00 |
April | 1606.82 | 695.87 | 1671.75 | 866.31 | 805.44 | 0.00 | 0.00 |
May | 1647.66 | 361.18 | 1625.51 | 740.26 | 885.25 | 0.00 | 0.00 |
June | 1945.24 | 196.86 | 1781.48 | 759.57 | 1021.90 | 0.00 | 0.00 |
July | 1638.86 | 215.92 | 1490.58 | 563.85 | 926.73 | 0.00 | 0.00 |
August | 1275.07 | 330.33 | 1225.09 | 518.77 | 706.33 | 0.00 | 0.00 |
September | 602.97 | 602.07 | 741.42 | 310.48 | 430.95 | 0.00 | 0.00 |
October | 111.04 | 1078.51 | 290.37 | 87.29 | 203.07 | 0.00 | 0.00 |
November | 13.53 | 1878.23 | 116.18 | 42.21 | 73.97 | 0.00 | 0.00 |
December | 0.00 | 2087.10 | 10.43 | 1.10 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 778.93 | 1016.18 | 829.78 | 357.54 | 472.25 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 196.86 | 10.43 | 1.10 | 9.33 | 0.00 | 0.00 |
Maximum of Months | 1945.24 | 2087.10 | 1781.48 | 866.31 | 1021.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 3000.31 | 43.04 | 0.00 | 43.04 | 0.00 | 0.00 |
February | 0.00 | 2681.85 | 190.26 | 0.00 | 190.26 | 0.00 | 0.00 |
March | 47.35 | 1978.77 | 508.87 | 0.00 | 508.87 | 0.00 | 0.00 |
April | 378.91 | 1062.09 | 920.69 | 20.27 | 900.42 | 0.00 | 0.00 |
May | 1074.04 | 483.86 | 1411.11 | 224.35 | 1186.76 | 0.00 | 0.00 |
June | 1772.82 | 225.69 | 1841.11 | 409.44 | 1431.66 | 0.00 | 0.00 |
July | 1518.15 | 276.04 | 1545.21 | 251.16 | 1294.05 | 0.00 | 0.00 |
August | 790.27 | 461.41 | 986.68 | 55.14 | 931.54 | 0.00 | 0.00 |
September | 206.18 | 923.55 | 550.46 | 0.55 | 549.90 | 0.00 | 0.00 |
October | 20.42 | 1693.36 | 267.85 | 0.00 | 267.85 | 0.00 | 0.00 |
November | 0.00 | 2939.72 | 83.12 | 0.00 | 83.12 | 0.00 | 0.00 |
December | 0.00 | 3162.13 | 13.06 | 0.00 | 13.06 | 0.00 | 0.00 |
Annual Sum or Average | 486.83 | 1568.10 | 699.29 | 80.43 | 618.85 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 225.69 | 13.06 | 0.00 | 13.06 | 0.00 | 0.00 |
Maximum of Months | 1772.82 | 3162.13 | 1841.11 | 409.44 | 1431.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.05 | 1938.14 | 75.59 | 23.79 | 51.80 | 0.00 | 0.00 |
February | 221.19 | 1616.32 | 417.63 | 199.28 | 218.35 | 0.00 | 0.00 |
March | 995.58 | 1187.26 | 1191.24 | 603.26 | 587.98 | 0.00 | 0.00 |
April | 1493.18 | 655.10 | 1637.41 | 828.36 | 809.06 | 0.00 | 0.00 |
May | 2551.43 | 347.50 | 2378.69 | 1339.08 | 1039.61 | 0.00 | 0.00 |
June | 2425.88 | 171.71 | 2188.45 | 1019.53 | 1168.91 | 0.00 | 0.00 |
July | 2359.73 | 197.61 | 2078.74 | 1006.64 | 1072.10 | 0.00 | 0.00 |
August | 1788.71 | 309.51 | 1646.50 | 800.73 | 845.77 | 0.00 | 0.00 |
September | 931.03 | 576.82 | 1018.56 | 445.87 | 572.69 | 0.00 | 0.00 |
October | 382.26 | 1027.36 | 538.01 | 215.88 | 322.13 | 0.00 | 0.00 |
November | 9.91 | 1883.62 | 114.44 | 39.99 | 74.45 | 0.00 | 0.00 |
December | 0.00 | 2093.25 | 16.35 | 3.91 | 12.44 | 0.00 | 0.00 |
Annual Sum or Average | 1103.07 | 997.24 | 1112.71 | 546.26 | 566.45 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 171.71 | 16.35 | 3.91 | 12.44 | 0.00 | 0.00 |
Maximum of Months | 2551.43 | 2093.25 | 2378.69 | 1339.08 | 1168.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 302.18 | 2693.17 | 516.35 | 340.19 | 176.16 | 0.00 | 0.00 |
February | 1493.72 | 2168.73 | 1776.79 | 1235.94 | 540.85 | 0.00 | 0.00 |
March | 2945.88 | 1667.34 | 3051.12 | 2068.08 | 983.04 | 0.00 | 0.00 |
April | 3991.55 | 1099.15 | 3722.27 | 2315.63 | 1406.65 | 0.00 | 0.00 |
May | 3379.41 | 606.93 | 3069.34 | 1590.39 | 1478.95 | 0.00 | 0.00 |
June | 3171.03 | 326.71 | 2802.42 | 1148.64 | 1653.78 | 0.00 | 0.00 |
July | 3127.74 | 348.61 | 2700.05 | 1175.87 | 1524.18 | 0.00 | 0.00 |
August | 3191.44 | 513.86 | 2796.18 | 1541.01 | 1255.16 | 0.00 | 0.00 |
September | 2345.81 | 888.56 | 2259.81 | 1360.97 | 898.84 | 0.00 | 0.00 |
October | 1465.28 | 1433.07 | 1627.07 | 1032.33 | 594.74 | 0.00 | 0.00 |
November | 577.59 | 2515.47 | 872.38 | 609.15 | 263.23 | 0.00 | 0.00 |
December | 28.00 | 3002.59 | 154.85 | 109.15 | 45.70 | 0.00 | 0.00 |
Annual Sum or Average | 2169.98 | 1435.22 | 2111.84 | 1208.78 | 903.05 | 0.00 | 0.00 |
Minimum of Months | 28.00 | 326.71 | 154.85 | 109.15 | 45.70 | 0.00 | 0.00 |
Maximum of Months | 3991.55 | 3002.59 | 3722.27 | 2315.63 | 1653.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1976.44 | 39.76 | 7.10 | 32.67 | 0.00 | 0.00 |
February | 49.95 | 1678.20 | 234.72 | 81.62 | 153.10 | 0.00 | 0.00 |
March | 405.58 | 1212.62 | 704.52 | 302.87 | 401.66 | 0.00 | 0.00 |
April | 1582.79 | 707.57 | 1671.76 | 866.32 | 805.44 | 0.00 | 0.00 |
May | 1623.34 | 372.93 | 1625.52 | 740.27 | 885.26 | 0.00 | 0.00 |
June | 1928.76 | 202.37 | 1781.49 | 759.58 | 1021.91 | 0.00 | 0.00 |
July | 1627.55 | 219.45 | 1490.59 | 563.85 | 926.74 | 0.00 | 0.00 |
August | 1270.17 | 327.43 | 1225.10 | 518.77 | 706.33 | 0.00 | 0.00 |
September | 601.93 | 592.16 | 741.43 | 310.48 | 430.95 | 0.00 | 0.00 |
October | 110.55 | 1069.59 | 290.37 | 87.29 | 203.07 | 0.00 | 0.00 |
November | 13.38 | 1878.67 | 116.18 | 42.21 | 73.97 | 0.00 | 0.00 |
December | 0.00 | 2099.98 | 10.43 | 1.10 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 770.84 | 1024.78 | 829.79 | 357.54 | 472.25 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 202.37 | 10.43 | 1.10 | 9.33 | 0.00 | 0.00 |
Maximum of Months | 1928.76 | 2099.98 | 1781.49 | 866.32 | 1021.91 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.789906E+10 | 0.115282E+09 | 0.00 | 0.115282E+09 | 0.00 | 0.00 |
February | 0.00 | 0.635029E+10 | 0.460285E+09 | 0.00 | 0.460285E+09 | 0.00 | 0.00 |
March | 0.137354E+09 | 0.513421E+10 | 0.136296E+10 | 0.00 | 0.136296E+10 | 0.00 | 0.00 |
April | 0.103911E+10 | 0.259634E+10 | 0.238644E+10 | 52546477.35 | 0.233389E+10 | 0.00 | 0.00 |
May | 0.295017E+10 | 0.123058E+10 | 0.377951E+10 | 0.600895E+09 | 0.317862E+10 | 0.00 | 0.00 |
June | 0.461900E+10 | 0.562469E+09 | 0.477215E+10 | 0.106128E+10 | 0.371087E+10 | 0.00 | 0.00 |
July | 0.408966E+10 | 0.711486E+09 | 0.413869E+10 | 0.672709E+09 | 0.346598E+10 | 0.00 | 0.00 |
August | 0.216018E+10 | 0.117110E+10 | 0.264273E+10 | 0.147695E+09 | 0.249503E+10 | 0.00 | 0.00 |
September | 0.592375E+09 | 0.221332E+10 | 0.142679E+10 | 1436678.12 | 0.142535E+10 | 0.00 | 0.00 |
October | 69785818.09 | 0.432671E+10 | 0.717401E+09 | 0.00 | 0.717401E+09 | 0.00 | 0.00 |
November | 0.00 | 0.746353E+10 | 0.215453E+09 | 0.00 | 0.215453E+09 | 0.00 | 0.00 |
December | 0.00 | 0.832976E+10 | 34970479.77 | 0.00 | 34970479.77 | 0.00 | 0.00 |
Annual Sum or Average | 0.156576E+11 | 0.479889E+11 | 0.220527E+11 | 0.253656E+10 | 0.195161E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.562469E+09 | 34970479.77 | 0.00 | 34970479.77 | 0.00 | 0.00 |
Maximum of Months | 0.461900E+10 | 0.832976E+10 | 0.477215E+10 | 0.106128E+10 | 0.371087E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 19408292.27 | 0.510518E+10 | 0.202455E+09 | 63715139.11 | 0.138740E+09 | 0.00 | 0.00 |
February | 0.543144E+09 | 0.382682E+10 | 0.101033E+10 | 0.482098E+09 | 0.528232E+09 | 0.00 | 0.00 |
March | 0.269201E+10 | 0.307836E+10 | 0.319061E+10 | 0.161576E+10 | 0.157485E+10 | 0.00 | 0.00 |
April | 0.391149E+10 | 0.161108E+10 | 0.424418E+10 | 0.214710E+10 | 0.209708E+10 | 0.00 | 0.00 |
May | 0.686086E+10 | 0.891248E+09 | 0.637108E+10 | 0.358659E+10 | 0.278450E+10 | 0.00 | 0.00 |
June | 0.629773E+10 | 0.429880E+09 | 0.567246E+10 | 0.264263E+10 | 0.302982E+10 | 0.00 | 0.00 |
July | 0.632890E+10 | 0.511434E+09 | 0.556770E+10 | 0.269620E+10 | 0.287151E+10 | 0.00 | 0.00 |
August | 0.480858E+10 | 0.792514E+09 | 0.440998E+10 | 0.214466E+10 | 0.226532E+10 | 0.00 | 0.00 |
September | 0.245476E+10 | 0.139895E+10 | 0.264011E+10 | 0.115568E+10 | 0.148442E+10 | 0.00 | 0.00 |
October | 0.104751E+10 | 0.262524E+10 | 0.144101E+10 | 0.578218E+09 | 0.862795E+09 | 0.00 | 0.00 |
November | 26819985.04 | 0.478401E+10 | 0.296634E+09 | 0.103654E+09 | 0.192980E+09 | 0.00 | 0.00 |
December | 0.00 | 0.552039E+10 | 43792763.19 | 10483189.90 | 33309573.29 | 0.00 | 0.00 |
Annual Sum or Average | 0.349912E+11 | 0.305751E+11 | 0.350903E+11 | 0.172268E+11 | 0.178636E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.429880E+09 | 43792763.19 | 10483189.90 | 33309573.29 | 0.00 | 0.00 |
Maximum of Months | 0.686086E+10 | 0.552039E+10 | 0.637108E+10 | 0.358659E+10 | 0.302982E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.818343E+09 | 0.708563E+10 | 0.138300E+10 | 0.911169E+09 | 0.471828E+09 | 0.00 | 0.00 |
February | 0.364314E+10 | 0.511758E+10 | 0.429842E+10 | 0.298999E+10 | 0.130843E+10 | 0.00 | 0.00 |
March | 0.793484E+10 | 0.430755E+10 | 0.817212E+10 | 0.553914E+10 | 0.263297E+10 | 0.00 | 0.00 |
April | 0.103896E+11 | 0.270401E+10 | 0.964814E+10 | 0.600211E+10 | 0.364603E+10 | 0.00 | 0.00 |
May | 0.908062E+10 | 0.153912E+10 | 0.822091E+10 | 0.425971E+10 | 0.396121E+10 | 0.00 | 0.00 |
June | 0.823035E+10 | 0.810018E+09 | 0.726388E+10 | 0.297727E+10 | 0.428661E+10 | 0.00 | 0.00 |
July | 0.838898E+10 | 0.895743E+09 | 0.723182E+10 | 0.314945E+10 | 0.408236E+10 | 0.00 | 0.00 |
August | 0.856948E+10 | 0.130811E+10 | 0.748928E+10 | 0.412745E+10 | 0.336183E+10 | 0.00 | 0.00 |
September | 0.613544E+10 | 0.215591E+10 | 0.585744E+10 | 0.352764E+10 | 0.232979E+10 | 0.00 | 0.00 |
October | 0.397698E+10 | 0.365375E+10 | 0.435795E+10 | 0.276500E+10 | 0.159295E+10 | 0.00 | 0.00 |
November | 0.151527E+10 | 0.637294E+10 | 0.226121E+10 | 0.157891E+10 | 0.682301E+09 | 0.00 | 0.00 |
December | 76345473.23 | 0.790833E+10 | 0.414763E+09 | 0.292350E+09 | 0.122412E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.687594E+11 | 0.438587E+11 | 0.665989E+11 | 0.381202E+11 | 0.284787E+11 | 0.00 | 0.00 |
Minimum of Months | 76345473.23 | 0.810018E+09 | 0.414763E+09 | 0.292350E+09 | 0.122412E+09 | 0.00 | 0.00 |
Maximum of Months | 0.103896E+11 | 0.790833E+10 | 0.964814E+10 | 0.600211E+10 | 0.428661E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.520792E+10 | 0.106498E+09 | 19004597.74 | 87493026.84 | 0.00 | 0.00 |
February | 0.123238E+09 | 0.397373E+10 | 0.567841E+09 | 0.197455E+09 | 0.370386E+09 | 0.00 | 0.00 |
March | 0.109954E+10 | 0.314306E+10 | 0.188699E+10 | 0.811195E+09 | 0.107580E+10 | 0.00 | 0.00 |
April | 0.413519E+10 | 0.173670E+10 | 0.433321E+10 | 0.224550E+10 | 0.208771E+10 | 0.00 | 0.00 |
May | 0.437762E+10 | 0.943205E+09 | 0.435380E+10 | 0.198273E+10 | 0.237107E+10 | 0.00 | 0.00 |
June | 0.501002E+10 | 0.501772E+09 | 0.461763E+10 | 0.196884E+10 | 0.264879E+10 | 0.00 | 0.00 |
July | 0.437030E+10 | 0.563535E+09 | 0.399241E+10 | 0.151022E+10 | 0.248218E+10 | 0.00 | 0.00 |
August | 0.342464E+10 | 0.831101E+09 | 0.328132E+10 | 0.138948E+10 | 0.189184E+10 | 0.00 | 0.00 |
September | 0.159658E+10 | 0.143017E+10 | 0.192179E+10 | 0.804767E+09 | 0.111702E+10 | 0.00 | 0.00 |
October | 0.310899E+09 | 0.273363E+10 | 0.777721E+09 | 0.233811E+09 | 0.543910E+09 | 0.00 | 0.00 |
November | 35978943.08 | 0.477140E+10 | 0.301130E+09 | 0.109411E+09 | 0.191719E+09 | 0.00 | 0.00 |
December | 0.00 | 0.553889E+10 | 27935562.83 | 2936530.56 | 24999032.28 | 0.00 | 0.00 |
Annual Sum or Average | 0.244840E+11 | 0.313751E+11 | 0.261683E+11 | 0.112754E+11 | 0.148929E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.501772E+09 | 27935562.83 | 2936530.56 | 24999032.28 | 0.00 | 0.00 |
Maximum of Months | 0.501002E+10 | 0.553889E+10 | 0.461763E+10 | 0.224550E+10 | 0.264879E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.793304E+10 | 0.115281E+09 | 0.00 | 0.115281E+09 | 0.00 | 0.00 |
February | 0.00 | 0.635682E+10 | 0.460282E+09 | 0.00 | 0.460282E+09 | 0.00 | 0.00 |
March | 0.142194E+09 | 0.515304E+10 | 0.136296E+10 | 0.00 | 0.136296E+10 | 0.00 | 0.00 |
April | 0.108745E+10 | 0.261706E+10 | 0.238643E+10 | 52546205.06 | 0.233388E+10 | 0.00 | 0.00 |
May | 0.302970E+10 | 0.121935E+10 | 0.377950E+10 | 0.600892E+09 | 0.317860E+10 | 0.00 | 0.00 |
June | 0.468707E+10 | 0.554734E+09 | 0.477212E+10 | 0.106127E+10 | 0.371085E+10 | 0.00 | 0.00 |
July | 0.413005E+10 | 0.714460E+09 | 0.413867E+10 | 0.672705E+09 | 0.346597E+10 | 0.00 | 0.00 |
August | 0.215095E+10 | 0.121701E+10 | 0.264272E+10 | 0.147694E+09 | 0.249502E+10 | 0.00 | 0.00 |
September | 0.548568E+09 | 0.239343E+10 | 0.142678E+10 | 1436670.68 | 0.142534E+10 | 0.00 | 0.00 |
October | 55715585.64 | 0.456218E+10 | 0.717398E+09 | 0.00 | 0.717398E+09 | 0.00 | 0.00 |
November | 0.00 | 0.761533E+10 | 0.215452E+09 | 0.00 | 0.215452E+09 | 0.00 | 0.00 |
December | 0.00 | 0.841337E+10 | 34970298.56 | 0.00 | 34970298.56 | 0.00 | 0.00 |
Annual Sum or Average | 0.158317E+11 | 0.487498E+11 | 0.220526E+11 | 0.253655E+10 | 0.195160E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.554734E+09 | 34970298.56 | 0.00 | 34970298.56 | 0.00 | 0.00 |
Maximum of Months | 0.468707E+10 | 0.841337E+10 | 0.477212E+10 | 0.106127E+10 | 0.371085E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 19943092.61 | 0.513231E+10 | 0.202453E+09 | 63714495.33 | 0.138739E+09 | 0.00 | 0.00 |
February | 0.545540E+09 | 0.384170E+10 | 0.101032E+10 | 0.482093E+09 | 0.528228E+09 | 0.00 | 0.00 |
March | 0.270958E+10 | 0.311854E+10 | 0.319058E+10 | 0.161574E+10 | 0.157484E+10 | 0.00 | 0.00 |
April | 0.393026E+10 | 0.167060E+10 | 0.424414E+10 | 0.214708E+10 | 0.209706E+10 | 0.00 | 0.00 |
May | 0.688419E+10 | 0.929664E+09 | 0.637103E+10 | 0.358655E+10 | 0.278448E+10 | 0.00 | 0.00 |
June | 0.632817E+10 | 0.440672E+09 | 0.567241E+10 | 0.264261E+10 | 0.302980E+10 | 0.00 | 0.00 |
July | 0.634452E+10 | 0.533981E+09 | 0.556766E+10 | 0.269617E+10 | 0.287149E+10 | 0.00 | 0.00 |
August | 0.480337E+10 | 0.846988E+09 | 0.440994E+10 | 0.214464E+10 | 0.226530E+10 | 0.00 | 0.00 |
September | 0.241021E+10 | 0.153997E+10 | 0.264009E+10 | 0.115567E+10 | 0.148441E+10 | 0.00 | 0.00 |
October | 0.102577E+10 | 0.279005E+10 | 0.144100E+10 | 0.578213E+09 | 0.862788E+09 | 0.00 | 0.00 |
November | 26180214.45 | 0.487833E+10 | 0.296632E+09 | 0.103653E+09 | 0.192979E+09 | 0.00 | 0.00 |
December | 0.00 | 0.557061E+10 | 43792387.58 | 10483083.98 | 33309303.61 | 0.00 | 0.00 |
Annual Sum or Average | 0.350277E+11 | 0.312934E+11 | 0.350900E+11 | 0.172266E+11 | 0.178634E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.440672E+09 | 43792387.58 | 10483083.98 | 33309303.61 | 0.00 | 0.00 |
Maximum of Months | 0.688419E+10 | 0.557061E+10 | 0.637103E+10 | 0.358655E+10 | 0.302980E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.853521E+09 | 0.685893E+10 | 0.138301E+10 | 0.911180E+09 | 0.471834E+09 | 0.00 | 0.00 |
February | 0.371334E+10 | 0.502521E+10 | 0.429847E+10 | 0.299003E+10 | 0.130844E+10 | 0.00 | 0.00 |
March | 0.808303E+10 | 0.430640E+10 | 0.817220E+10 | 0.553921E+10 | 0.263300E+10 | 0.00 | 0.00 |
April | 0.104868E+11 | 0.282874E+10 | 0.964824E+10 | 0.600217E+10 | 0.364606E+10 | 0.00 | 0.00 |
May | 0.917794E+10 | 0.159092E+10 | 0.822099E+10 | 0.425976E+10 | 0.396124E+10 | 0.00 | 0.00 |
June | 0.830964E+10 | 0.827217E+09 | 0.726395E+10 | 0.297731E+10 | 0.428664E+10 | 0.00 | 0.00 |
July | 0.843891E+10 | 0.931490E+09 | 0.723189E+10 | 0.314949E+10 | 0.408239E+10 | 0.00 | 0.00 |
August | 0.860556E+10 | 0.140070E+10 | 0.748935E+10 | 0.412749E+10 | 0.336186E+10 | 0.00 | 0.00 |
September | 0.613317E+10 | 0.234663E+10 | 0.585750E+10 | 0.352768E+10 | 0.232981E+10 | 0.00 | 0.00 |
October | 0.397375E+10 | 0.383711E+10 | 0.435800E+10 | 0.276503E+10 | 0.159297E+10 | 0.00 | 0.00 |
November | 0.155462E+10 | 0.630293E+10 | 0.226123E+10 | 0.157893E+10 | 0.682308E+09 | 0.00 | 0.00 |
December | 94317898.83 | 0.765186E+10 | 0.414767E+09 | 0.292354E+09 | 0.122414E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.694246E+11 | 0.439082E+11 | 0.665996E+11 | 0.381206E+11 | 0.284790E+11 | 0.00 | 0.00 |
Minimum of Months | 94317898.83 | 0.827217E+09 | 0.414767E+09 | 0.292354E+09 | 0.122414E+09 | 0.00 | 0.00 |
Maximum of Months | 0.104868E+11 | 0.765186E+10 | 0.964824E+10 | 0.600217E+10 | 0.428664E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.523593E+10 | 0.106497E+09 | 19004407.89 | 87492409.46 | 0.00 | 0.00 |
February | 0.125608E+09 | 0.398752E+10 | 0.567836E+09 | 0.197453E+09 | 0.370383E+09 | 0.00 | 0.00 |
March | 0.111870E+10 | 0.317070E+10 | 0.188698E+10 | 0.811187E+09 | 0.107579E+10 | 0.00 | 0.00 |
April | 0.416489E+10 | 0.180370E+10 | 0.433318E+10 | 0.224548E+10 | 0.208770E+10 | 0.00 | 0.00 |
May | 0.441310E+10 | 0.967391E+09 | 0.435377E+10 | 0.198271E+10 | 0.237106E+10 | 0.00 | 0.00 |
June | 0.504206E+10 | 0.510251E+09 | 0.461759E+10 | 0.196882E+10 | 0.264878E+10 | 0.00 | 0.00 |
July | 0.438952E+10 | 0.578327E+09 | 0.399238E+10 | 0.151021E+10 | 0.248217E+10 | 0.00 | 0.00 |
August | 0.341515E+10 | 0.884758E+09 | 0.328129E+10 | 0.138947E+10 | 0.189183E+10 | 0.00 | 0.00 |
September | 0.156291E+10 | 0.156056E+10 | 0.192177E+10 | 0.804759E+09 | 0.111701E+10 | 0.00 | 0.00 |
October | 0.297405E+09 | 0.288867E+10 | 0.777715E+09 | 0.233808E+09 | 0.543907E+09 | 0.00 | 0.00 |
November | 35082408.67 | 0.486837E+10 | 0.301127E+09 | 0.109410E+09 | 0.191718E+09 | 0.00 | 0.00 |
December | 0.00 | 0.559008E+10 | 27935350.12 | 2936501.22 | 24998848.90 | 0.00 | 0.00 |
Annual Sum or Average | 0.245644E+11 | 0.320463E+11 | 0.261681E+11 | 0.112752E+11 | 0.148928E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.510251E+09 | 27935350.12 | 2936501.22 | 24998848.90 | 0.00 | 0.00 |
Maximum of Months | 0.504206E+10 | 0.559008E+10 | 0.461759E+10 | 0.224548E+10 | 0.264878E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.803602E+10 | 0.115282E+09 | 0.00 | 0.115282E+09 | 0.00 | 0.00 |
February | 0.00 | 0.648794E+10 | 0.460285E+09 | 0.00 | 0.460285E+09 | 0.00 | 0.00 |
March | 0.126814E+09 | 0.529993E+10 | 0.136296E+10 | 0.00 | 0.136296E+10 | 0.00 | 0.00 |
April | 0.982141E+09 | 0.275294E+10 | 0.238644E+10 | 52546477.35 | 0.233389E+10 | 0.00 | 0.00 |
May | 0.287670E+10 | 0.129598E+10 | 0.377951E+10 | 0.600895E+09 | 0.317862E+10 | 0.00 | 0.00 |
June | 0.459515E+10 | 0.584991E+09 | 0.477215E+10 | 0.106128E+10 | 0.371087E+10 | 0.00 | 0.00 |
July | 0.406620E+10 | 0.739348E+09 | 0.413869E+10 | 0.672709E+09 | 0.346598E+10 | 0.00 | 0.00 |
August | 0.211665E+10 | 0.123584E+10 | 0.264273E+10 | 0.147695E+09 | 0.249503E+10 | 0.00 | 0.00 |
September | 0.534431E+09 | 0.239384E+10 | 0.142679E+10 | 1436678.12 | 0.142535E+10 | 0.00 | 0.00 |
October | 54696483.12 | 0.453550E+10 | 0.717401E+09 | 0.00 | 0.717401E+09 | 0.00 | 0.00 |
November | 0.00 | 0.761976E+10 | 0.215453E+09 | 0.00 | 0.215453E+09 | 0.00 | 0.00 |
December | 0.00 | 0.846944E+10 | 34970479.77 | 0.00 | 34970479.77 | 0.00 | 0.00 |
Annual Sum or Average | 0.153528E+11 | 0.494515E+11 | 0.220527E+11 | 0.253656E+10 | 0.195161E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.584991E+09 | 34970479.77 | 0.00 | 34970479.77 | 0.00 | 0.00 |
Maximum of Months | 0.459515E+10 | 0.846944E+10 | 0.477215E+10 | 0.106128E+10 | 0.371087E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 18895187.70 | 0.519110E+10 | 0.202455E+09 | 63715139.11 | 0.138740E+09 | 0.00 | 0.00 |
February | 0.535109E+09 | 0.391019E+10 | 0.101033E+10 | 0.482098E+09 | 0.528232E+09 | 0.00 | 0.00 |
March | 0.266656E+10 | 0.317997E+10 | 0.319061E+10 | 0.161576E+10 | 0.157485E+10 | 0.00 | 0.00 |
April | 0.387032E+10 | 0.169802E+10 | 0.424418E+10 | 0.214710E+10 | 0.209708E+10 | 0.00 | 0.00 |
May | 0.683376E+10 | 0.930742E+09 | 0.637108E+10 | 0.358659E+10 | 0.278450E+10 | 0.00 | 0.00 |
June | 0.628789E+10 | 0.445076E+09 | 0.567246E+10 | 0.264263E+10 | 0.302982E+10 | 0.00 | 0.00 |
July | 0.632029E+10 | 0.529284E+09 | 0.556770E+10 | 0.269620E+10 | 0.287151E+10 | 0.00 | 0.00 |
August | 0.479088E+10 | 0.828983E+09 | 0.440998E+10 | 0.214466E+10 | 0.226532E+10 | 0.00 | 0.00 |
September | 0.241322E+10 | 0.149512E+10 | 0.264011E+10 | 0.115568E+10 | 0.148442E+10 | 0.00 | 0.00 |
October | 0.102385E+10 | 0.275168E+10 | 0.144101E+10 | 0.578218E+09 | 0.862795E+09 | 0.00 | 0.00 |
November | 25695724.00 | 0.488236E+10 | 0.296634E+09 | 0.103654E+09 | 0.192980E+09 | 0.00 | 0.00 |
December | 0.00 | 0.560657E+10 | 43792763.19 | 10483189.90 | 33309573.29 | 0.00 | 0.00 |
Annual Sum or Average | 0.347865E+11 | 0.314491E+11 | 0.350903E+11 | 0.172268E+11 | 0.178636E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.445076E+09 | 43792763.19 | 10483189.90 | 33309573.29 | 0.00 | 0.00 |
Maximum of Months | 0.683376E+10 | 0.560657E+10 | 0.637108E+10 | 0.358659E+10 | 0.302982E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.809357E+09 | 0.721338E+10 | 0.138300E+10 | 0.911169E+09 | 0.471828E+09 | 0.00 | 0.00 |
February | 0.361360E+10 | 0.524658E+10 | 0.429842E+10 | 0.298999E+10 | 0.130843E+10 | 0.00 | 0.00 |
March | 0.789024E+10 | 0.446580E+10 | 0.817212E+10 | 0.553914E+10 | 0.263297E+10 | 0.00 | 0.00 |
April | 0.103461E+11 | 0.284899E+10 | 0.964814E+10 | 0.600211E+10 | 0.364603E+10 | 0.00 | 0.00 |
May | 0.905140E+10 | 0.162561E+10 | 0.822091E+10 | 0.425971E+10 | 0.396121E+10 | 0.00 | 0.00 |
June | 0.821931E+10 | 0.846843E+09 | 0.726388E+10 | 0.297727E+10 | 0.428661E+10 | 0.00 | 0.00 |
July | 0.837733E+10 | 0.933719E+09 | 0.723182E+10 | 0.314945E+10 | 0.408236E+10 | 0.00 | 0.00 |
August | 0.854794E+10 | 0.137632E+10 | 0.748928E+10 | 0.412745E+10 | 0.336183E+10 | 0.00 | 0.00 |
September | 0.608035E+10 | 0.230315E+10 | 0.585744E+10 | 0.352764E+10 | 0.232979E+10 | 0.00 | 0.00 |
October | 0.392460E+10 | 0.383833E+10 | 0.435795E+10 | 0.276500E+10 | 0.159295E+10 | 0.00 | 0.00 |
November | 0.149711E+10 | 0.652010E+10 | 0.226121E+10 | 0.157891E+10 | 0.682301E+09 | 0.00 | 0.00 |
December | 75001861.55 | 0.804215E+10 | 0.414763E+09 | 0.292350E+09 | 0.122412E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.684323E+11 | 0.452610E+11 | 0.665989E+11 | 0.381202E+11 | 0.284787E+11 | 0.00 | 0.00 |
Minimum of Months | 75001861.55 | 0.846843E+09 | 0.414763E+09 | 0.292350E+09 | 0.122412E+09 | 0.00 | 0.00 |
Maximum of Months | 0.103461E+11 | 0.804215E+10 | 0.964814E+10 | 0.600211E+10 | 0.428661E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.529368E+10 | 0.106498E+09 | 19004597.74 | 87493026.84 | 0.00 | 0.00 |
February | 0.120850E+09 | 0.405990E+10 | 0.567841E+09 | 0.197455E+09 | 0.370386E+09 | 0.00 | 0.00 |
March | 0.108631E+10 | 0.324788E+10 | 0.188699E+10 | 0.811195E+09 | 0.107580E+10 | 0.00 | 0.00 |
April | 0.410258E+10 | 0.183403E+10 | 0.433321E+10 | 0.224550E+10 | 0.208771E+10 | 0.00 | 0.00 |
May | 0.434794E+10 | 0.998854E+09 | 0.435380E+10 | 0.198273E+10 | 0.237107E+10 | 0.00 | 0.00 |
June | 0.499935E+10 | 0.524547E+09 | 0.461763E+10 | 0.196884E+10 | 0.264879E+10 | 0.00 | 0.00 |
July | 0.435923E+10 | 0.587777E+09 | 0.399241E+10 | 0.151022E+10 | 0.248218E+10 | 0.00 | 0.00 |
August | 0.340203E+10 | 0.876983E+09 | 0.328132E+10 | 0.138948E+10 | 0.189184E+10 | 0.00 | 0.00 |
September | 0.156020E+10 | 0.153489E+10 | 0.192179E+10 | 0.804767E+09 | 0.111702E+10 | 0.00 | 0.00 |
October | 0.296094E+09 | 0.286479E+10 | 0.777721E+09 | 0.233811E+09 | 0.543910E+09 | 0.00 | 0.00 |
November | 34686072.13 | 0.486952E+10 | 0.301130E+09 | 0.109411E+09 | 0.191719E+09 | 0.00 | 0.00 |
December | 0.00 | 0.562458E+10 | 27935562.83 | 2936530.56 | 24999032.28 | 0.00 | 0.00 |
Annual Sum or Average | 0.243093E+11 | 0.323174E+11 | 0.261683E+11 | 0.112754E+11 | 0.148929E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.524547E+09 | 27935562.83 | 2936530.56 | 24999032.28 | 0.00 | 0.00 |
Maximum of Months | 0.499935E+10 | 0.562458E+10 | 0.461763E+10 | 0.224550E+10 | 0.264879E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.634928E+10 | -0.557597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -773303659.2 | 58.99 | 0.00 | 0.00 |
February | 0.575349E+10 | -0.506757E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -685928819.6 | 58.99 | 0.00 | 0.00 |
March | 0.673793E+10 | -0.600002E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -737910320.2 | 58.99 | 0.00 | 0.00 |
April | 0.608455E+10 | -0.539874E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -685800900.9 | 58.98 | 0.00 | 0.00 |
May | 0.644102E+10 | -0.574804E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692985552.1 | 58.98 | 0.00 | 0.00 |
June | 0.616856E+10 | -0.550145E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667117679.5 | 58.99 | 0.00 | 0.00 |
July | 0.567424E+10 | -0.498729E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -686955965.0 | 58.98 | 0.00 | 0.00 |
August | 0.607142E+10 | -0.538184E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689581148.0 | 58.98 | 0.00 | 0.00 |
September | 0.550116E+10 | -0.482764E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -673514571.1 | 58.98 | 0.00 | 0.00 |
October | 0.580680E+10 | -0.508455E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -722246974.6 | 58.98 | 0.00 | 0.00 |
November | 0.591355E+10 | -0.518040E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -733144781.8 | 58.98 | 0.00 | 0.00 |
December | 0.610839E+10 | -0.533730E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -771095547.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.726104E+11 | -0.640908E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.851959E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.550116E+10 | -0.600002E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -773303659.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.673793E+10 | -0.482764E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -667117679.5 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.71 | 0.62 | 03-JAN-11:20 | 583.45 | 10.33 | 2.83 | 62.33 | 454.74 | 15.43 | 6.00 | 38.67 |
February | 205.83 | 0.66 | 0.62 | 01-FEB-10:39 | 1940.03 | 21.99 | 76.33 | 167.83 | 2301.36 | 35.99 | 191.33 | 156.00 |
March | 329.50 | 0.64 | 0.62 | 01-MAR-09:20 | 5921.86 | 31.96 | 272.00 | 298.00 | 5264.15 | 33.94 | 286.17 | 281.17 |
April | 421.83 | 0.64 | 0.62 | 01-APR-07:10 | 8501.27 | 30.66 | 283.67 | 379.17 | 1628.52 | 20.93 | 245.33 | 334.67 |
May | 545.00 | 0.65 | 0.62 | 01-MAY-04:49 | 4098.36 | 20.70 | 114.67 | 447.67 | 1178.68 | 19.66 | 253.33 | 391.17 |
June | 583.50 | 0.66 | 0.62 | 01-JUN-03:00 | 1936.52 | 16.65 | 0.00 | 471.33 | 1074.82 | 19.41 | 267.50 | 404.83 |
July | 562.83 | 0.65 | 0.62 | 01-JUL-03:00 | 2326.75 | 17.29 | 15.67 | 468.50 | 1099.31 | 19.45 | 260.00 | 396.17 |
August | 467.17 | 0.65 | 0.62 | 01-AUG-04:49 | 6058.86 | 26.09 | 241.50 | 403.17 | 1249.63 | 20.05 | 223.67 | 350.67 |
September | 356.33 | 0.65 | 0.62 | 01-SEP-06:40 | 4887.25 | 30.10 | 270.33 | 315.83 | 1669.95 | 21.63 | 188.33 | 277.33 |
October | 265.50 | 0.65 | 0.62 | 01-OCT-07:40 | 2624.55 | 29.30 | 205.33 | 232.50 | 2255.50 | 33.21 | 234.50 | 209.00 |
November | 135.83 | 0.67 | 0.62 | 01-NOV-09:50 | 712.67 | 11.83 | 0.00 | 113.33 | 813.02 | 29.70 | 94.17 | 86.50 |
December | 71.17 | 0.83 | 0.62 | 04-DEC-10:00 | 166.57 | 5.23 | 0.00 | 4.50 | 117.80 | 9.64 | 0.00 | 0.17 |
Annual Sum or Average | 4053.17 | 0.66 | 3960.04 | 22.82 | 1482.33 | 3364.17 | 1660.28 | 22.87 | 2250.33 | 2926.33 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 166.57 | 5.23 | 0.00 | 4.50 | 117.80 | 9.64 | 0.00 | 0.17 | |
Maximum of Months | 583.50 | 0.83 | 0.62 | 8501.27 | 31.96 | 283.67 | 471.33 | 5264.15 | 35.99 | 286.17 | 404.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.77 | 0.62 | 10-JAN-10:00 | 279.06 | 9.80 | 1.67 | 27.17 | 173.03 | 13.06 | 2.83 | 11.17 |
February | 205.83 | 0.69 | 0.62 | 01-FEB-10:50 | 931.11 | 16.51 | 45.67 | 137.83 | 633.73 | 21.48 | 78.50 | 94.83 |
March | 329.50 | 0.66 | 0.62 | 01-MAR-09:20 | 2170.20 | 18.77 | 83.33 | 275.00 | 1474.01 | 22.24 | 131.00 | 234.33 |
April | 421.83 | 0.64 | 0.62 | 01-APR-06:49 | 2964.01 | 20.71 | 109.67 | 382.17 | 1879.81 | 23.99 | 178.67 | 341.67 |
May | 545.00 | 0.65 | 0.62 | 01-MAY-04:40 | 4037.70 | 21.72 | 180.33 | 457.33 | 2110.67 | 23.22 | 189.00 | 414.00 |
June | 583.50 | 0.65 | 0.62 | 01-JUN-03:09 | 3422.49 | 20.23 | 168.17 | 490.83 | 1538.53 | 22.07 | 191.00 | 431.33 |
July | 562.83 | 0.65 | 0.62 | 01-JUL-03:39 | 3435.79 | 20.41 | 173.00 | 476.00 | 1799.38 | 22.15 | 192.67 | 419.50 |
August | 467.17 | 0.65 | 0.62 | 01-AUG-04:30 | 2809.54 | 20.44 | 143.67 | 404.17 | 1441.13 | 22.07 | 158.50 | 354.33 |
September | 356.33 | 0.66 | 0.62 | 01-SEP-06:19 | 2105.71 | 19.00 | 104.67 | 294.83 | 1133.13 | 21.04 | 121.33 | 248.67 |
October | 265.50 | 0.67 | 0.62 | 01-OCT-07:30 | 1104.02 | 17.64 | 73.50 | 207.17 | 683.84 | 20.60 | 82.17 | 149.50 |
November | 135.83 | 0.73 | 0.62 | 01-NOV-09:50 | 382.04 | 15.42 | 33.83 | 65.67 | 226.07 | 18.25 | 35.50 | 18.50 |
December | 71.17 | 0.90 | 0.69 | 04-DEC-11:30 | 93.94 | 5.67 | 0.00 | 0.00 | 55.28 | 8.29 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 2648.12 | 19.25 | 1117.50 | 3218.17 | 1426.52 | 21.62 | 1361.17 | 2717.83 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 93.94 | 5.67 | 0.00 | 0.00 | 55.28 | 8.29 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.90 | 0.69 | 4037.70 | 21.72 | 180.33 | 490.83 | 2110.67 | 23.99 | 192.67 | 431.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.84 | 0.62 | 21-JAN-12:30 | 161.43 | 7.13 | 0.00 | 3.33 | 94.45 | 10.02 | 0.00 | 0.00 |
February | 205.83 | 0.71 | 0.62 | 01-FEB-11:00 | 355.35 | 11.40 | 0.00 | 100.17 | 210.32 | 14.35 | 0.00 | 19.50 |
March | 329.50 | 0.66 | 0.62 | 01-MAR-09:50 | 654.75 | 14.77 | 0.00 | 265.17 | 389.41 | 17.60 | 0.83 | 188.17 |
April | 421.83 | 0.63 | 0.62 | 01-APR-06:00 | 861.00 | 17.09 | 0.00 | 393.17 | 536.44 | 19.91 | 24.17 | 333.67 |
May | 545.00 | 0.64 | 0.62 | 01-MAY-04:40 | 1046.97 | 20.06 | 104.83 | 497.67 | 642.02 | 23.47 | 193.33 | 465.83 |
June | 583.50 | 0.64 | 0.62 | 01-JUN-03:09 | 1280.32 | 21.38 | 150.67 | 532.83 | 741.59 | 23.27 | 250.17 | 496.50 |
July | 562.83 | 0.64 | 0.62 | 01-JUL-03:39 | 1162.06 | 21.05 | 138.83 | 515.17 | 650.58 | 22.08 | 184.83 | 459.83 |
August | 467.17 | 0.64 | 0.62 | 01-AUG-04:40 | 894.18 | 18.79 | 63.83 | 421.50 | 510.43 | 19.39 | 52.17 | 356.33 |
September | 356.33 | 0.66 | 0.62 | 01-SEP-06:40 | 641.76 | 14.88 | 0.00 | 290.83 | 371.28 | 17.56 | 1.50 | 189.00 |
October | 265.50 | 0.67 | 0.62 | 01-OCT-07:40 | 449.01 | 12.86 | 0.00 | 180.67 | 249.46 | 15.59 | 0.00 | 24.83 |
November | 135.83 | 0.79 | 0.62 | 01-NOV-09:00 | 216.13 | 8.88 | 0.00 | 20.67 | 124.55 | 12.05 | 0.00 | 0.00 |
December | 71.17 | 0.94 | 0.81 | 04-DEC-11:30 | 63.60 | 2.80 | 0.00 | 0.00 | 37.65 | 5.21 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 848.93 | 17.11 | 458.17 | 3221.17 | 496.78 | 19.37 | 707.00 | 2533.67 | ||
Minimum of Months | 71.17 | 0.63 | 0.62 | 63.60 | 2.80 | 0.00 | 0.00 | 37.65 | 5.21 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.94 | 0.81 | 1280.32 | 21.38 | 150.67 | 532.83 | 741.59 | 23.47 | 250.17 | 496.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.78 | 0.62 | 21-JAN-11:39 | 235.33 | 9.24 | 1.33 | 19.00 | 142.97 | 12.55 | 1.83 | 4.17 |
February | 205.83 | 0.67 | 0.62 | 01-FEB-11:20 | 756.31 | 16.64 | 44.67 | 146.50 | 493.97 | 21.70 | 68.33 | 79.33 |
March | 329.50 | 0.65 | 0.62 | 01-MAR-09:50 | 1674.06 | 18.60 | 75.67 | 285.50 | 1054.45 | 21.94 | 102.17 | 247.67 |
April | 421.83 | 0.64 | 0.62 | 01-APR-07:30 | 3473.23 | 22.27 | 139.50 | 382.67 | 1747.26 | 22.62 | 141.67 | 340.17 |
May | 545.00 | 0.64 | 0.62 | 01-MAY-04:00 | 2708.75 | 18.95 | 117.83 | 474.00 | 1354.54 | 20.03 | 72.17 | 427.17 |
June | 583.50 | 0.64 | 0.62 | 01-JUN-03:49 | 2889.44 | 18.37 | 111.33 | 500.17 | 1459.92 | 19.75 | 64.33 | 446.33 |
July | 562.83 | 0.64 | 0.62 | 01-JUL-03:00 | 2496.78 | 18.32 | 114.50 | 492.67 | 1292.60 | 19.63 | 78.50 | 434.00 |
August | 467.17 | 0.64 | 0.62 | 01-AUG-04:00 | 2259.66 | 19.40 | 114.50 | 417.17 | 1374.17 | 21.51 | 115.00 | 367.17 |
September | 356.33 | 0.65 | 0.62 | 01-SEP-06:49 | 1765.43 | 19.75 | 101.00 | 310.17 | 1103.98 | 22.83 | 111.33 | 254.00 |
October | 265.50 | 0.65 | 0.62 | 01-OCT-07:49 | 878.88 | 17.39 | 67.50 | 210.00 | 526.68 | 20.74 | 65.17 | 130.17 |
November | 135.83 | 0.73 | 0.62 | 01-NOV-09:00 | 365.97 | 14.97 | 33.83 | 61.83 | 248.14 | 19.98 | 45.17 | 24.17 |
December | 71.17 | 0.92 | 0.77 | 04-DEC-11:30 | 81.83 | 4.96 | 0.00 | 0.00 | 47.62 | 7.59 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 2156.12 | 18.36 | 921.67 | 3299.67 | 1167.38 | 20.49 | 865.67 | 2754.33 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 81.83 | 4.96 | 0.00 | 0.00 | 47.62 | 7.59 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.92 | 0.77 | 3473.23 | 22.27 | 139.50 | 500.17 | 1747.26 | 22.83 | 141.67 | 446.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.71 | 0.62 | 03-JAN-11:30 | 513.96 | 5.41 | 0.00 | 57.33 | 413.70 | 11.56 | 5.83 | 35.50 |
February | 205.83 | 0.66 | 0.62 | 01-FEB-10:50 | 1258.03 | 9.28 | 0.00 | 165.33 | 2136.53 | 33.59 | 171.17 | 150.67 |
March | 329.50 | 0.64 | 0.62 | 01-MAR-09:20 | 5694.26 | 31.10 | 266.83 | 295.50 | 5122.54 | 33.50 | 280.00 | 279.33 |
April | 421.83 | 0.64 | 0.62 | 01-APR-07:10 | 8324.36 | 29.63 | 283.67 | 375.83 | 1501.12 | 18.41 | 30.83 | 330.17 |
May | 545.00 | 0.65 | 0.62 | 01-MAY-04:00 | 3979.03 | 18.14 | 114.67 | 444.50 | 1095.63 | 17.29 | 10.67 | 385.17 |
June | 583.50 | 0.66 | 0.62 | 01-JUN-04:10 | 1830.72 | 13.13 | 0.00 | 466.17 | 1005.40 | 16.94 | 8.33 | 398.17 |
July | 562.83 | 0.66 | 0.62 | 01-JUL-03:00 | 2217.91 | 13.85 | 15.67 | 462.83 | 1026.79 | 16.94 | 9.83 | 389.83 |
August | 467.17 | 0.65 | 0.62 | 01-AUG-04:49 | 5929.27 | 24.48 | 238.50 | 399.17 | 1158.58 | 17.44 | 10.67 | 346.50 |
September | 356.33 | 0.65 | 0.62 | 01-SEP-06:40 | 4705.22 | 28.96 | 261.67 | 314.17 | 1574.22 | 19.06 | 38.67 | 272.50 |
October | 265.50 | 0.65 | 0.62 | 01-OCT-07:40 | 2430.15 | 25.39 | 170.83 | 228.33 | 2148.31 | 32.12 | 224.83 | 206.33 |
November | 135.83 | 0.68 | 0.62 | 01-NOV-09:50 | 647.60 | 7.24 | 0.00 | 108.00 | 653.25 | 21.78 | 56.00 | 76.33 |
December | 71.17 | 0.84 | 0.62 | 04-DEC-11:09 | 151.70 | 1.82 | 0.00 | 2.00 | 109.87 | 5.70 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 3794.12 | 19.79 | 1351.83 | 3319.17 | 1563.38 | 20.39 | 846.83 | 2870.50 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 151.70 | 1.82 | 0.00 | 2.00 | 109.87 | 5.70 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.84 | 0.62 | 8324.36 | 31.10 | 283.67 | 466.17 | 5122.54 | 33.59 | 280.00 | 398.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.78 | 0.62 | 10-JAN-11:09 | 266.88 | 9.23 | 1.67 | 25.33 | 164.89 | 12.67 | 1.83 | 10.33 |
February | 205.83 | 0.69 | 0.62 | 01-FEB-10:50 | 894.15 | 16.06 | 45.67 | 134.33 | 539.80 | 19.10 | 56.33 | 87.33 |
March | 329.50 | 0.66 | 0.62 | 01-MAR-09:20 | 2088.08 | 18.36 | 83.17 | 272.83 | 1401.89 | 21.95 | 123.50 | 230.00 |
April | 421.83 | 0.64 | 0.62 | 01-APR-06:49 | 2868.20 | 20.29 | 109.67 | 379.00 | 1806.49 | 23.80 | 166.83 | 337.67 |
May | 545.00 | 0.65 | 0.62 | 01-MAY-04:40 | 3807.04 | 19.98 | 150.17 | 454.33 | 2031.07 | 23.06 | 175.17 | 409.00 |
June | 583.50 | 0.65 | 0.62 | 01-JUN-03:09 | 3328.75 | 19.86 | 167.83 | 487.33 | 1470.94 | 21.91 | 172.33 | 426.83 |
July | 562.83 | 0.65 | 0.62 | 01-JUL-03:39 | 3327.00 | 19.95 | 171.00 | 471.50 | 1730.10 | 21.98 | 171.17 | 414.17 |
August | 467.17 | 0.65 | 0.62 | 01-AUG-04:40 | 2622.07 | 18.72 | 116.17 | 401.17 | 1377.03 | 21.89 | 139.33 | 349.67 |
September | 356.33 | 0.66 | 0.62 | 01-SEP-06:19 | 2035.92 | 18.61 | 104.33 | 291.33 | 1081.81 | 20.82 | 116.00 | 242.17 |
October | 265.50 | 0.67 | 0.62 | 01-OCT-07:30 | 1063.91 | 17.22 | 73.00 | 203.50 | 655.20 | 20.38 | 80.50 | 144.50 |
November | 135.83 | 0.73 | 0.62 | 01-NOV-09:50 | 366.81 | 14.96 | 33.83 | 61.33 | 215.95 | 17.99 | 35.17 | 15.33 |
December | 71.17 | 0.91 | 0.70 | 04-DEC-11:30 | 89.50 | 5.21 | 0.00 | 0.00 | 52.45 | 7.99 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.67 | 2538.70 | 18.50 | 1056.50 | 3182.00 | 1363.82 | 21.31 | 1238.17 | 2667.00 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 89.50 | 5.21 | 0.00 | 0.00 | 52.45 | 7.99 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.91 | 0.70 | 3807.04 | 20.29 | 171.00 | 487.33 | 2031.07 | 23.80 | 175.17 | 426.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.84 | 0.62 | 28-JAN-11:30 | 152.90 | 3.74 | 0.00 | 2.00 | 89.77 | 7.36 | 0.00 | 0.00 |
February | 205.83 | 0.71 | 0.62 | 01-FEB-12:09 | 337.82 | 7.88 | 0.00 | 89.17 | 200.84 | 11.84 | 0.00 | 14.33 |
March | 329.50 | 0.66 | 0.62 | 01-MAR-09:50 | 624.88 | 11.54 | 0.00 | 261.83 | 373.52 | 15.44 | 0.00 | 177.00 |
April | 421.83 | 0.64 | 0.62 | 01-APR-07:10 | 814.62 | 14.09 | 0.00 | 388.00 | 516.11 | 18.12 | 1.50 | 326.17 |
May | 545.00 | 0.64 | 0.62 | 01-MAY-04:40 | 1001.63 | 17.50 | 104.00 | 494.83 | 612.79 | 20.99 | 116.00 | 459.67 |
June | 583.50 | 0.64 | 0.62 | 01-JUN-03:09 | 1212.79 | 17.75 | 124.17 | 526.33 | 693.46 | 20.69 | 111.00 | 490.67 |
July | 562.83 | 0.64 | 0.62 | 01-JUL-03:39 | 1072.76 | 16.63 | 93.33 | 508.67 | 629.13 | 20.41 | 103.83 | 455.17 |
August | 467.17 | 0.64 | 0.62 | 01-AUG-04:40 | 855.48 | 16.03 | 62.83 | 417.83 | 512.48 | 19.52 | 68.00 | 352.17 |
September | 356.33 | 0.66 | 0.62 | 01-SEP-06:40 | 613.21 | 11.58 | 0.00 | 287.00 | 356.04 | 15.40 | 0.00 | 174.50 |
October | 265.50 | 0.67 | 0.62 | 01-OCT-07:49 | 428.89 | 9.18 | 0.00 | 172.67 | 238.55 | 13.05 | 0.00 | 19.67 |
November | 135.83 | 0.80 | 0.62 | 01-NOV-09:00 | 205.17 | 5.19 | 0.00 | 15.17 | 118.55 | 9.25 | 0.00 | 0.00 |
December | 71.17 | 0.94 | 0.82 | 04-DEC-11:30 | 60.04 | 0.66 | 0.00 | 0.00 | 35.68 | 3.02 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 803.62 | 13.78 | 384.33 | 3163.50 | 476.87 | 17.40 | 400.33 | 2469.33 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 60.04 | 0.66 | 0.00 | 0.00 | 35.68 | 3.02 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.94 | 0.82 | 1212.79 | 17.75 | 124.17 | 526.33 | 693.46 | 20.99 | 116.00 | 490.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.79 | 0.62 | 21-JAN-11:50 | 225.36 | 8.91 | 1.33 | 17.50 | 136.49 | 12.56 | 1.83 | 3.67 |
February | 205.83 | 0.68 | 0.62 | 01-FEB-11:30 | 728.10 | 16.31 | 44.67 | 142.67 | 474.04 | 21.64 | 68.33 | 74.50 |
March | 329.50 | 0.65 | 0.62 | 01-MAR-09:50 | 1616.85 | 18.25 | 75.33 | 283.17 | 1011.98 | 21.83 | 100.83 | 242.17 |
April | 421.83 | 0.64 | 0.62 | 01-APR-07:30 | 3380.61 | 21.92 | 139.50 | 378.50 | 1678.08 | 22.49 | 139.83 | 336.00 |
May | 545.00 | 0.64 | 0.62 | 01-MAY-04:00 | 2633.25 | 18.56 | 117.83 | 469.33 | 1297.09 | 19.87 | 68.67 | 421.50 |
June | 583.50 | 0.65 | 0.62 | 01-JUN-03:00 | 2812.42 | 17.96 | 111.17 | 496.83 | 1402.49 | 19.57 | 59.33 | 438.83 |
July | 562.83 | 0.64 | 0.62 | 01-JUL-03:00 | 2411.62 | 17.92 | 114.50 | 487.83 | 1236.55 | 19.47 | 74.67 | 425.67 |
August | 467.17 | 0.64 | 0.62 | 01-AUG-04:00 | 2141.41 | 19.02 | 114.33 | 412.33 | 1316.76 | 21.37 | 113.33 | 360.00 |
September | 356.33 | 0.65 | 0.62 | 01-SEP-06:49 | 1711.67 | 19.40 | 101.00 | 308.17 | 1064.22 | 22.72 | 110.50 | 248.33 |
October | 265.50 | 0.66 | 0.62 | 01-OCT-07:49 | 849.02 | 17.05 | 67.50 | 205.67 | 503.94 | 20.32 | 62.50 | 122.17 |
November | 135.83 | 0.73 | 0.62 | 01-NOV-09:00 | 349.87 | 14.69 | 33.83 | 57.67 | 220.06 | 17.76 | 34.50 | 18.50 |
December | 71.17 | 0.92 | 0.78 | 04-DEC-11:30 | 78.10 | 4.78 | 0.00 | 0.00 | 45.26 | 7.69 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 2086.14 | 17.99 | 921.00 | 3259.67 | 1119.18 | 20.27 | 834.33 | 2691.33 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 78.10 | 4.78 | 0.00 | 0.00 | 45.26 | 7.69 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.92 | 0.78 | 3380.61 | 21.92 | 139.50 | 496.83 | 1678.08 | 22.72 | 139.83 | 438.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.71 | 0.62 | 03-JAN-11:30 | 513.99 | 5.41 | 0.00 | 57.33 | 413.70 | 11.56 | 5.83 | 35.50 |
February | 205.83 | 0.66 | 0.62 | 01-FEB-10:50 | 1258.09 | 9.28 | 0.00 | 165.33 | 2136.50 | 33.59 | 171.17 | 150.67 |
March | 329.50 | 0.64 | 0.62 | 01-MAR-09:20 | 5694.31 | 31.10 | 266.83 | 295.50 | 5122.46 | 33.50 | 280.00 | 279.33 |
April | 421.83 | 0.64 | 0.62 | 01-APR-07:10 | 8324.35 | 29.63 | 283.67 | 375.83 | 1501.02 | 18.41 | 30.83 | 330.17 |
May | 545.00 | 0.65 | 0.62 | 01-MAY-04:00 | 3978.96 | 18.14 | 114.67 | 444.50 | 1095.55 | 17.29 | 10.67 | 385.17 |
June | 583.50 | 0.66 | 0.62 | 01-JUN-04:10 | 1830.65 | 13.13 | 0.00 | 466.17 | 1005.32 | 16.94 | 8.33 | 398.17 |
July | 562.83 | 0.66 | 0.62 | 01-JUL-03:00 | 2217.83 | 13.85 | 15.67 | 462.83 | 1026.71 | 16.95 | 9.83 | 389.83 |
August | 467.17 | 0.65 | 0.62 | 01-AUG-04:49 | 5929.22 | 24.48 | 238.50 | 399.17 | 1158.49 | 17.44 | 10.67 | 346.50 |
September | 356.33 | 0.65 | 0.62 | 01-SEP-06:40 | 4705.22 | 28.96 | 261.67 | 314.17 | 1574.14 | 19.06 | 38.67 | 272.50 |
October | 265.50 | 0.65 | 0.62 | 01-OCT-07:40 | 2430.17 | 25.39 | 170.83 | 228.33 | 2148.27 | 32.12 | 224.83 | 206.33 |
November | 135.83 | 0.68 | 0.62 | 01-NOV-09:50 | 647.63 | 7.24 | 0.00 | 108.00 | 653.24 | 21.78 | 56.00 | 76.33 |
December | 71.17 | 0.84 | 0.62 | 04-DEC-11:09 | 151.71 | 1.83 | 0.00 | 2.00 | 109.87 | 5.70 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 3794.10 | 19.79 | 1351.83 | 3319.17 | 1563.31 | 20.39 | 846.83 | 2870.50 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 151.71 | 1.83 | 0.00 | 2.00 | 109.87 | 5.70 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.84 | 0.62 | 8324.35 | 31.10 | 283.67 | 466.17 | 5122.46 | 33.59 | 280.00 | 398.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.78 | 0.62 | 10-JAN-11:09 | 266.88 | 9.23 | 1.67 | 25.33 | 164.88 | 12.67 | 1.83 | 10.33 |
February | 205.83 | 0.69 | 0.62 | 01-FEB-10:50 | 894.16 | 16.06 | 45.67 | 134.33 | 539.78 | 19.11 | 56.33 | 87.33 |
March | 329.50 | 0.66 | 0.62 | 01-MAR-09:20 | 2088.10 | 18.36 | 83.17 | 272.83 | 1401.85 | 21.95 | 123.50 | 230.00 |
April | 421.83 | 0.64 | 0.62 | 01-APR-06:49 | 2868.22 | 20.29 | 109.67 | 379.00 | 1806.44 | 23.80 | 166.83 | 337.67 |
May | 545.00 | 0.65 | 0.62 | 01-MAY-04:40 | 3807.05 | 19.98 | 150.17 | 454.33 | 2031.01 | 23.06 | 175.50 | 409.00 |
June | 583.50 | 0.65 | 0.62 | 01-JUN-03:09 | 3328.73 | 19.86 | 167.83 | 487.33 | 1470.87 | 21.91 | 172.50 | 426.83 |
July | 562.83 | 0.65 | 0.62 | 01-JUL-03:39 | 3326.98 | 19.95 | 171.00 | 471.50 | 1730.03 | 21.98 | 171.33 | 414.17 |
August | 467.17 | 0.65 | 0.62 | 01-AUG-04:40 | 2622.06 | 18.72 | 116.17 | 401.17 | 1376.97 | 21.89 | 139.50 | 349.67 |
September | 356.33 | 0.66 | 0.62 | 01-SEP-06:19 | 2035.92 | 18.61 | 104.33 | 291.33 | 1081.76 | 20.82 | 116.17 | 242.17 |
October | 265.50 | 0.67 | 0.62 | 01-OCT-07:30 | 1063.90 | 17.22 | 73.00 | 203.50 | 655.17 | 20.38 | 80.50 | 144.50 |
November | 135.83 | 0.73 | 0.62 | 01-NOV-09:50 | 366.81 | 14.96 | 33.83 | 61.33 | 215.94 | 18.00 | 35.17 | 15.33 |
December | 71.17 | 0.91 | 0.70 | 04-DEC-11:30 | 89.50 | 5.21 | 0.00 | 0.00 | 52.45 | 7.99 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.67 | 2538.69 | 18.50 | 1056.50 | 3182.00 | 1363.77 | 21.31 | 1239.17 | 2667.00 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 89.50 | 5.21 | 0.00 | 0.00 | 52.45 | 7.99 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.91 | 0.70 | 3807.05 | 20.29 | 171.00 | 487.33 | 2031.01 | 23.80 | 175.50 | 426.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.84 | 0.62 | 28-JAN-11:30 | 152.90 | 3.74 | 0.00 | 2.00 | 89.77 | 7.36 | 0.00 | 0.00 |
February | 205.83 | 0.71 | 0.62 | 01-FEB-12:09 | 337.82 | 7.89 | 0.00 | 89.17 | 200.82 | 11.84 | 0.00 | 14.33 |
March | 329.50 | 0.66 | 0.62 | 01-MAR-09:50 | 624.88 | 11.54 | 0.00 | 261.83 | 373.50 | 15.44 | 0.00 | 177.00 |
April | 421.83 | 0.64 | 0.62 | 01-APR-07:10 | 814.62 | 14.09 | 0.00 | 388.00 | 516.08 | 18.12 | 1.50 | 326.17 |
May | 545.00 | 0.64 | 0.62 | 01-MAY-04:40 | 1001.62 | 17.51 | 104.00 | 494.83 | 612.76 | 20.99 | 116.00 | 459.67 |
June | 583.50 | 0.64 | 0.62 | 01-JUN-03:09 | 1212.78 | 17.75 | 124.17 | 526.33 | 693.42 | 20.69 | 111.00 | 490.67 |
July | 562.83 | 0.64 | 0.62 | 01-JUL-03:39 | 1072.74 | 16.63 | 93.33 | 508.67 | 629.09 | 20.41 | 103.83 | 455.17 |
August | 467.17 | 0.64 | 0.62 | 01-AUG-04:40 | 855.47 | 16.03 | 62.83 | 417.83 | 512.45 | 19.52 | 68.00 | 352.17 |
September | 356.33 | 0.66 | 0.62 | 01-SEP-06:40 | 613.20 | 11.59 | 0.00 | 287.00 | 356.02 | 15.40 | 0.00 | 174.50 |
October | 265.50 | 0.67 | 0.62 | 01-OCT-07:49 | 428.88 | 9.18 | 0.00 | 172.67 | 238.54 | 13.05 | 0.00 | 19.67 |
November | 135.83 | 0.80 | 0.62 | 01-NOV-09:00 | 205.17 | 5.19 | 0.00 | 15.17 | 118.54 | 9.26 | 0.00 | 0.00 |
December | 71.17 | 0.94 | 0.82 | 04-DEC-11:30 | 60.04 | 0.66 | 0.00 | 0.00 | 35.68 | 3.02 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 803.61 | 13.78 | 384.33 | 3163.50 | 476.84 | 17.40 | 400.33 | 2469.33 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 60.04 | 0.66 | 0.00 | 0.00 | 35.68 | 3.02 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.94 | 0.82 | 1212.78 | 17.75 | 124.17 | 526.33 | 693.42 | 20.99 | 116.00 | 490.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.79 | 0.62 | 21-JAN-11:50 | 225.36 | 8.91 | 1.33 | 17.50 | 136.48 | 12.56 | 1.83 | 3.67 |
February | 205.83 | 0.68 | 0.62 | 01-FEB-11:30 | 728.10 | 16.31 | 44.67 | 142.67 | 474.02 | 21.64 | 68.33 | 74.50 |
March | 329.50 | 0.65 | 0.62 | 01-MAR-09:50 | 1616.85 | 18.25 | 75.33 | 283.17 | 1011.95 | 21.83 | 100.83 | 242.17 |
April | 421.83 | 0.64 | 0.62 | 01-APR-07:30 | 3380.62 | 21.92 | 139.50 | 378.50 | 1678.03 | 22.49 | 140.00 | 336.00 |
May | 545.00 | 0.64 | 0.62 | 01-MAY-04:00 | 2633.25 | 18.56 | 117.83 | 469.33 | 1297.04 | 19.87 | 68.83 | 421.50 |
June | 583.50 | 0.65 | 0.62 | 01-JUN-03:00 | 2812.40 | 17.96 | 111.17 | 496.83 | 1402.43 | 19.57 | 59.33 | 438.83 |
July | 562.83 | 0.64 | 0.62 | 01-JUL-03:00 | 2411.59 | 17.92 | 114.50 | 487.83 | 1236.49 | 19.47 | 74.67 | 425.67 |
August | 467.17 | 0.64 | 0.62 | 01-AUG-04:00 | 2141.40 | 19.02 | 114.33 | 412.33 | 1316.71 | 21.37 | 113.33 | 360.00 |
September | 356.33 | 0.65 | 0.62 | 01-SEP-06:49 | 1711.67 | 19.40 | 101.00 | 308.17 | 1064.18 | 22.72 | 110.50 | 248.33 |
October | 265.50 | 0.66 | 0.62 | 01-OCT-07:49 | 849.01 | 17.05 | 67.50 | 205.83 | 503.91 | 20.32 | 62.50 | 122.17 |
November | 135.83 | 0.73 | 0.62 | 01-NOV-09:00 | 349.87 | 14.69 | 33.83 | 57.67 | 220.05 | 17.76 | 34.50 | 18.50 |
December | 71.17 | 0.92 | 0.78 | 04-DEC-11:30 | 78.10 | 4.78 | 0.00 | 0.00 | 45.25 | 7.69 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 2086.14 | 17.99 | 921.00 | 3259.83 | 1119.14 | 20.27 | 834.67 | 2691.33 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 78.10 | 4.78 | 0.00 | 0.00 | 45.25 | 7.69 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.92 | 0.78 | 3380.62 | 21.92 | 139.50 | 496.83 | 1678.03 | 22.72 | 140.00 | 438.83 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.232842E+10 | 26014.55 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.789107E+09 | 26014.55 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 87563318.83 | 26014.55 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8621589.73 | 26014.55 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.644838E+09 | 26014.55 | 06-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156660E+10 | 26014.55 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.542515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.232842E+10 | 26014.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.206887E+11 | 16391.20 | 05-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151149E+11 | 16400.90 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124767E+11 | 16349.84 | 07-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.461894E+10 | 16362.20 | 14-APR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156612E+10 | 16788.54 | 11-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.547286E+09 | 16909.91 | 08-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.441166E+09 | 16706.13 | 05-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.982545E+09 | 16834.04 | 25-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.308852E+10 | 16584.71 | 05-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.892150E+10 | 16357.76 | 19-OCT-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178341E+11 | 16385.10 | 14-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208007E+11 | 16384.73 | 20-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107081E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.441166E+09 | 16349.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.208007E+11 | 16909.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.756433E+10 | 10341.94 | 18-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.544089E+10 | 10345.84 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.294076E+10 | 10341.99 | 07-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.592371E+09 | 10259.23 | 05-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79781971.41 | 10261.37 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163156E+10 | 10312.73 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.548290E+10 | 10340.57 | 15-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.721431E+10 | 10338.87 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.309469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.756433E+10 | 10345.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106193E+11 | 8238.54 | 05-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.847674E+10 | 8241.81 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.657755E+10 | 8216.74 | 07-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164317E+10 | 8195.77 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 446810.95 | 191.85 | 27-MAY-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.188973E+09 | 8203.29 | 25-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.280643E+10 | 8215.56 | 03-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.785148E+10 | 8236.12 | 14-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101321E+11 | 8237.13 | 20-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.482962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106193E+11 | 8241.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.771189E+10 | 11056.52 | 18-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.593567E+10 | 11045.46 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.407063E+10 | 11032.78 | 03-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.702299E+09 | 10968.09 | 05-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10947603.26 | 3509.95 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152502E+09 | 10970.25 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205989E+10 | 11025.34 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.553978E+10 | 11053.90 | 07-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.726302E+10 | 11053.27 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.334466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.771189E+10 | 11056.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.794039E+10 | 28825.79 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.481517E+10 | 28825.79 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208465E+10 | 28825.79 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.301120E+09 | 28825.79 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1063242.44 | 7488.85 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145839E+10 | 28825.79 | 10-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.579040E+10 | 28825.79 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.791974E+10 | 28825.79 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.303109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.794039E+10 | 28825.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.920521E+10 | 17714.31 | 01-JAN-01:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.516433E+10 | 17714.31 | 01-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.284057E+10 | 17714.31 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.625782E+09 | 17714.31 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2414004.87 | 2751.83 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 45047.91 | 450.48 | 30-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.205223E+09 | 17714.31 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.250030E+10 | 17714.31 | 03-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.691854E+10 | 17714.31 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.978453E+10 | 17714.31 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.372469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.978453E+10 | 17714.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.683874E+10 | 11718.39 | 01-JAN-01:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.447676E+10 | 11718.39 | 01-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.240200E+10 | 11718.39 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.517171E+09 | 11718.39 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 536235.69 | 2399.59 | 31-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173568E+09 | 11718.39 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.214591E+10 | 11718.39 | 03-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.558119E+10 | 11718.39 | 01-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.687038E+10 | 11718.39 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.687038E+10 | 11718.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.955893E+10 | 9063.09 | 24-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.675469E+10 | 9058.42 | 09-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.458044E+10 | 9077.84 | 22-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.925420E+09 | 9056.86 | 17-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.238670E+09 | 9036.37 | 25-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.306836E+10 | 9081.70 | 20-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.767895E+10 | 9065.19 | 07-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.954763E+10 | 9047.97 | 09-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.423531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.955893E+10 | 9081.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.682591E+10 | 11665.70 | 01-JAN-01:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.474377E+10 | 11665.70 | 01-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.309749E+10 | 11665.70 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.617281E+09 | 11665.70 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5054790.26 | 2888.40 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 993014.25 | 1714.36 | 30-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.249952E+09 | 11665.70 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.240035E+10 | 11665.70 | 03-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.547659E+10 | 11665.70 | 01-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.678742E+10 | 11665.70 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.302048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.682591E+10 | 11665.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160477E+11 | 31659.26 | 23-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108669E+11 | 31722.90 | 04-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.699597E+10 | 31635.51 | 22-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159545E+10 | 31574.59 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.415707E+09 | 31634.12 | 28-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.549034E+10 | 31692.75 | 03-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135703E+11 | 31682.07 | 21-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162934E+11 | 31578.99 | 20-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.712757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.162934E+11 | 31722.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.132992E+11 | 20145.50 | 18-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.827153E+10 | 20080.48 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.521359E+10 | 20103.64 | 22-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156173E+10 | 20028.02 | 07-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 63728892.71 | 11116.60 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28762594.54 | 16144.15 | 30-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.760248E+09 | 19945.50 | 28-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471922E+10 | 20259.25 | 10-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108809E+11 | 20142.04 | 07-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142772E+11 | 20119.29 | 22-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.590761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142772E+11 | 20259.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.944078E+10 | 12591.84 | 18-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.663379E+10 | 12556.94 | 28-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.402284E+10 | 12568.49 | 02-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110451E+10 | 12578.85 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18843247.33 | 6238.00 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9554284.92 | 10588.91 | 31-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.500521E+09 | 12466.86 | 27-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.362810E+10 | 12662.86 | 10-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.818186E+10 | 12589.73 | 07-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.971097E+10 | 12575.44 | 22-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.432518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.971097E+10 | 12662.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138757E+11 | 10624.81 | 23-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104881E+11 | 10645.23 | 04-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.789977E+10 | 10614.69 | 22-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.224939E+10 | 10596.78 | 13-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39488435.45 | 10489.92 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23970169.48 | 10459.28 | 30-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.929359E+09 | 10614.95 | 27-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.585690E+10 | 10633.41 | 03-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120572E+11 | 10633.26 | 21-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142006E+11 | 10597.12 | 20-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.676204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142006E+11 | 10645.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.959224E+10 | 13270.98 | 18-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.711618E+10 | 13227.78 | 24-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511342E+10 | 13243.54 | 22-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139569E+10 | 13202.75 | 07-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 56925539.64 | 7304.28 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28275660.46 | 10445.33 | 30-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.762488E+09 | 13139.21 | 28-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.415105E+10 | 13345.94 | 10-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.822949E+10 | 13268.75 | 07-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.976196E+10 | 13253.71 | 22-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.462077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.976196E+10 | 13345.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128144E+11 | 55556.14 | 12-JAN-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.739469E+10 | 52899.07 | 27-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210288E+10 | 43920.27 | 01-MAR-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 74646979.34 | 4572.22 | 03-APR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1210767.97 | 1121.75 | 06-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2018203.50 | 6240.31 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43673287.77 | 3904.53 | 08-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135928E+09 | 4448.40 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109754E+11 | 43674.67 | 29-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180669E+11 | 49675.64 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.516118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.180669E+11 | 55556.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128238E+11 | 53486.60 | 12-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.746114E+10 | 47652.35 | 27-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.223858E+10 | 41676.32 | 01-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 75154181.35 | 7265.71 | 10-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3092998.48 | 1978.81 | 16-MAY-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1890074.55 | 1365.31 | 30-AUG-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11376504.78 | 3447.30 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.301578E+09 | 7688.97 | 20-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112932E+11 | 41919.62 | 28-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177629E+11 | 46871.15 | 15-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.519728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.177629E+11 | 53486.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.185014E+11 | 56032.54 | 12-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113977E+11 | 48819.55 | 27-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.423672E+10 | 45528.04 | 01-MAR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.364598E+09 | 9734.29 | 03-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2402601.95 | 1826.34 | 16-MAY-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 953213.66 | 2206.21 | 30-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10721088.82 | 3145.82 | 30-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135992E+10 | 8656.27 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164034E+11 | 45228.84 | 29-NOV-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.237794E+11 | 50724.29 | 15-DEC-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.760573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.237794E+11 | 56032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6546444.11 | 6545334.70 | 6800.28 | 20-JAN-07:01 | 6800.28 | 0.00 |
February | 0.00 | 0.00 | 10089375.74 | 10014150.85 | 6212.17 | 02-FEB-07:01 | 6212.17 | 0.00 |
March | 0.00 | 0.00 | 28253602.13 | 28023520.43 | 6729.26 | 07-MAR-07:01 | 6729.26 | 0.00 |
April | 0.00 | 0.00 | 30621074.10 | 30589143.05 | 6382.92 | 14-APR-07:03 | 6382.92 | 0.00 |
May | 0.00 | 0.00 | 0.391820E+10 | 0.391102E+10 | 37601.41 | 31-MAY-16:00 | 37601.41 | 0.00 |
June | 0.00 | 0.00 | 0.211376E+11 | 0.202642E+11 | 66543.00 | 30-JUN-11:40 | 53153.76 | 0.00 |
July | 0.00 | 0.00 | 0.299013E+11 | 0.275657E+11 | 66574.78 | 11-JUL-16:00 | 63085.18 | 0.00 |
August | 0.00 | 0.00 | 0.159308E+11 | 0.147720E+11 | 62290.49 | 11-AUG-16:00 | 62290.49 | 0.00 |
September | 0.00 | 0.00 | 0.240225E+09 | 0.225153E+09 | 9566.69 | 07-SEP-16:00 | 9566.69 | 0.00 |
October | 0.00 | 0.00 | 33690402.14 | 32936077.92 | 3896.31 | 30-OCT-06:01 | 3896.31 | 0.00 |
November | 0.00 | 0.00 | 6928789.16 | 6928789.16 | 4904.82 | 15-NOV-07:01 | 4904.82 | 0.00 |
December | 0.00 | 0.00 | 3260308.00 | 3260308.00 | 6341.28 | 21-DEC-07:01 | 6341.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.712475E+11 | 0.668564E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 3260308.00 | 3260308.00 | 3896.31 | 3896.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.299013E+11 | 0.275657E+11 | 66574.78 | 63085.18 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3678778.37 | 3678778.37 | 5609.36 | 20-JAN-07:01 | 5609.36 | 0.00 |
February | 0.00 | 0.00 | 4233538.86 | 4233119.36 | 6845.28 | 09-FEB-07:01 | 6845.28 | 0.00 |
March | 0.00 | 0.00 | 9143680.99 | 9126477.98 | 7875.40 | 22-MAR-06:01 | 7875.40 | 0.00 |
April | 0.00 | 0.00 | 24930990.43 | 24930630.44 | 7207.00 | 17-APR-06:01 | 7207.00 | 0.00 |
May | 0.00 | 0.00 | 0.424014E+10 | 0.423626E+10 | 38278.69 | 31-MAY-16:00 | 38278.69 | 0.00 |
June | 0.00 | 0.00 | 0.209789E+11 | 0.201439E+11 | 65256.44 | 30-JUN-12:10 | 57466.26 | 0.00 |
July | 0.00 | 0.00 | 0.282314E+11 | 0.260508E+11 | 63050.92 | 11-JUL-15:30 | 59251.07 | 0.00 |
August | 0.00 | 0.00 | 0.145344E+11 | 0.134537E+11 | 57257.68 | 11-AUG-15:30 | 57257.68 | 0.00 |
September | 0.00 | 0.00 | 0.222241E+09 | 0.210614E+09 | 8449.22 | 07-SEP-16:00 | 8449.22 | 0.00 |
October | 0.00 | 0.00 | 8968310.98 | 8893713.95 | 7537.68 | 20-OCT-06:01 | 7537.68 | 0.00 |
November | 0.00 | 0.00 | 3058829.18 | 3058829.18 | 5789.25 | 02-NOV-06:01 | 5789.25 | 0.00 |
December | 0.00 | 0.00 | 1927114.35 | 1927114.35 | 4097.91 | 23-DEC-07:03 | 4097.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.682630E+11 | 0.641512E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1927114.35 | 1927114.35 | 4097.91 | 4097.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.282314E+11 | 0.260508E+11 | 65256.44 | 59251.07 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 136019.42 | 136019.42 | 1333.57 | 19-JAN-07:01 | 1333.57 | 0.00 |
February | 0.00 | 0.00 | 634467.31 | 629674.84 | 4103.86 | 09-FEB-07:01 | 4103.86 | 0.00 |
March | 0.00 | 0.00 | 8226319.00 | 8091286.66 | 4192.19 | 23-MAR-06:01 | 4192.19 | 0.00 |
April | 0.00 | 0.00 | 32487799.39 | 32472576.45 | 5426.66 | 19-APR-06:01 | 5426.66 | 0.00 |
May | 0.00 | 0.00 | 0.413090E+10 | 0.412452E+10 | 40224.47 | 31-MAY-16:00 | 40224.47 | 0.00 |
June | 0.00 | 0.00 | 0.212784E+11 | 0.204140E+11 | 70715.33 | 30-JUN-12:30 | 62970.47 | 0.00 |
July | 0.00 | 0.00 | 0.287034E+11 | 0.265022E+11 | 65634.42 | 21-JUL-14:40 | 65634.42 | 0.00 |
August | 0.00 | 0.00 | 0.144227E+11 | 0.132674E+11 | 60269.28 | 11-AUG-15:50 | 60269.28 | 0.00 |
September | 0.00 | 0.00 | 0.195339E+09 | 0.182455E+09 | 7412.27 | 07-SEP-16:00 | 7412.27 | 0.00 |
October | 0.00 | 0.00 | 6483375.88 | 6289671.06 | 5331.87 | 05-OCT-06:01 | 5331.87 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 123842.25 | 123842.25 | 825.62 | 23-DEC-07:03 | 825.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.687788E+11 | 0.645383E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.287034E+11 | 0.265022E+11 | 70715.33 | 65634.42 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 2233.73 | 7810.31 | 05-JAN-12:12 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 2246.70 | 7810.27 | 01-FEB-12:12 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 2395.62 | 7810.02 | 06-MAR-12:09 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2234.15 | 7808.14 | 07-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 2299.60 | 7802.34 | 04-MAY-11:06 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 2277.85 | 7604.00 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 2012.63 | 7265.39 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 2165.44 | 7059.39 | 01-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 2014.53 | 7039.67 | 27-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 2050.71 | 7254.75 | 31-OCT-11:09 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 2151.58 | 7534.66 | 30-NOV-12:16 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2143.23 | 7806.72 | 28-DEC-12:15 |
Annual Sum or Average | 0.00 | 2185.15 | ||||
Minimum of Months | 0.00 | 0.00 | 2012.63 | 7039.67 | ||
Maximum of Months | 0.00 | 0.00 | 2395.62 | 7810.31 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.236623E+10 | 0.42 | 2994.46 | 02-JAN-07:11 | 0.83 |
February | 0.195203E+10 | 0.40 | 2994.46 | 06-FEB-07:01 | 0.83 |
March | 0.177124E+10 | 0.34 | 2994.46 | 01-MAR-07:01 | 0.83 |
April | 0.185879E+10 | 0.32 | 4499.83 | 21-APR-05:02 | 1.04 |
May | 0.331492E+10 | 0.41 | 7172.62 | 11-MAY-06:03 | 1.38 |
June | 0.493347E+10 | 0.51 | 8914.82 | 22-JUN-06:02 | 1.57 |
July | 0.513142E+10 | 0.50 | 9913.66 | 12-JUL-15:10 | 1.69 |
August | 0.444195E+10 | 0.47 | 9298.79 | 11-AUG-16:00 | 1.62 |
September | 0.215795E+10 | 0.33 | 4499.83 | 01-SEP-05:02 | 1.04 |
October | 0.155836E+10 | 0.29 | 2994.46 | 30-OCT-06:01 | 0.83 |
November | 0.188161E+10 | 0.35 | 2994.46 | 07-NOV-07:01 | 0.83 |
December | 0.235219E+10 | 0.42 | 2994.46 | 05-DEC-07:02 | 0.83 |
Annual Sum or Average | 0.337202E+11 | 0.40 | |||
Minimum of Months | 0.155836E+10 | 0.29 | 2994.46 | 0.83 | |
Maximum of Months | 0.513142E+10 | 0.51 | 9913.66 | 1.69 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.207992E+10 | 0.40 | 3101.79 | 02-JAN-05:01 | 0.90 |
February | 0.178087E+10 | 0.39 | 3101.79 | 01-FEB-06:01 | 0.90 |
March | 0.173379E+10 | 0.34 | 3101.79 | 01-MAR-06:01 | 0.90 |
April | 0.191786E+10 | 0.34 | 4753.54 | 21-APR-15:40 | 1.15 |
May | 0.341229E+10 | 0.44 | 7395.40 | 31-MAY-14:50 | 1.51 |
June | 0.513568E+10 | 0.55 | 9265.00 | 30-JUN-12:10 | 1.72 |
July | 0.485756E+10 | 0.51 | 9489.03 | 12-JUL-15:20 | 1.76 |
August | 0.385665E+10 | 0.46 | 8952.27 | 11-AUG-15:20 | 1.69 |
September | 0.170830E+10 | 0.32 | 3381.97 | 08-SEP-15:30 | 0.94 |
October | 0.154588E+10 | 0.31 | 3101.79 | 10-OCT-06:01 | 0.89 |
November | 0.184383E+10 | 0.38 | 3101.79 | 01-NOV-05:01 | 0.90 |
December | 0.203616E+10 | 0.40 | 3101.79 | 01-DEC-06:01 | 0.90 |
Annual Sum or Average | 0.319088E+11 | 0.40 | |||
Minimum of Months | 0.154588E+10 | 0.31 | 3101.79 | 0.89 | |
Maximum of Months | 0.513568E+10 | 0.55 | 9489.03 | 1.76 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.254883E+10 | 0.45 | 2986.14 | 11-JAN-07:02 | 0.84 |
February | 0.216281E+10 | 0.44 | 2986.14 | 06-FEB-07:01 | 0.83 |
March | 0.214682E+10 | 0.40 | 2986.14 | 02-MAR-07:01 | 0.83 |
April | 0.191691E+10 | 0.34 | 3949.38 | 21-APR-16:00 | 0.98 |
May | 0.290823E+10 | 0.39 | 7364.70 | 31-MAY-15:00 | 1.42 |
June | 0.454583E+10 | 0.49 | 8976.57 | 20-JUN-15:30 | 1.60 |
July | 0.431616E+10 | 0.46 | 9173.35 | 12-JUL-15:20 | 1.62 |
August | 0.325754E+10 | 0.40 | 8361.11 | 10-AUG-15:30 | 1.53 |
September | 0.160005E+10 | 0.30 | 2986.14 | 25-SEP-05:01 | 0.83 |
October | 0.181325E+10 | 0.34 | 2986.14 | 11-OCT-05:01 | 0.83 |
November | 0.238010E+10 | 0.45 | 2986.14 | 02-NOV-06:01 | 0.83 |
December | 0.263387E+10 | 0.47 | 2986.14 | 08-DEC-07:01 | 0.84 |
Annual Sum or Average | 0.322304E+11 | 0.41 | |||
Minimum of Months | 0.160005E+10 | 0.30 | 2986.14 | 0.83 | |
Maximum of Months | 0.454583E+10 | 0.49 | 9173.35 | 1.62 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:02 | 0.22 | 0.22 | 57.02 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:01 | 0.22 | 0.22 | 55.17 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:01 | 0.22 | 0.22 | 55.42 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:01 | 0.22 | 0.22 | 55.64 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:02 | 0.22 | 0.22 | 55.67 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:02 | 0.22 | 0.22 | 54.83 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 55.84 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:02 | 0.22 | 0.22 | 55.83 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:02 | 0.22 | 0.22 | 56.01 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 56.36 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:01 | 0.22 | 0.22 | 56.24 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:01 | 0.22 | 0.22 | 55.64 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 54.83 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.02 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 56.92 | 56.92 | 2233.73 | 7810.31 | 05-JAN-12:12 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 55.64 | 55.64 | 2246.70 | 7810.27 | 01-FEB-12:12 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 55.89 | 55.89 | 2395.62 | 7810.02 | 06-MAR-12:09 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.19 | 56.19 | 2234.15 | 7808.14 | 07-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.41 | 56.41 | 2299.60 | 7802.34 | 04-MAY-11:06 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 55.39 | 55.39 | 2277.85 | 7604.00 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.41 | 56.41 | 2012.63 | 7265.39 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.88 | 56.88 | 2165.44 | 7059.39 | 01-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.47 | 56.47 | 2014.53 | 7039.67 | 27-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.70 | 55.70 | 2050.71 | 7254.75 | 31-OCT-11:09 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.54 | 56.54 | 2151.58 | 7534.66 | 30-NOV-12:16 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.21 | 56.21 | 2143.23 | 7806.72 | 28-DEC-12:15 |
Annual Sum or Average | 0.00 | 2185.15 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.39 | 55.39 | 2012.63 | 7039.67 | ||
Maximum of Months | 0.00 | 0.00 | 56.92 | 56.92 | 2395.62 | 7810.31 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.512807E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.377123E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.279327E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.942454E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.591382E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.106545E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.127327E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.929959E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.573652E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.169962E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.392367E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.493298E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.276250E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.573652E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.512807E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.424501E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.277368E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.167415E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.491190E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.451136E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.102335E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.116067E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.739329E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.264021E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.131217E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.332904E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.429464E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.217584E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.264021E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.429464E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.648045E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.455394E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.313948E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.983323E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.415880E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.974945E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.112154E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.688099E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.502439E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.256607E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.552998E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.668781E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.336440E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.415880E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.668781E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.236623E+10 | 6546444.11 | 0.617270E+11 | 0.263961E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195203E+10 | 10089375.74 | 0.431520E+11 | 0.218507E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177124E+10 | 28253602.13 | 0.282561E+11 | 0.241021E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185879E+10 | 30621074.10 | 0.763142E+10 | 0.610125E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.331492E+10 | 0.391820E+10 | 0.157873E+10 | 0.185924E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.493347E+10 | 0.211376E+11 | 0.547286E+09 | 48086371.86 | 5969495.11 | 0.00 | 0.00 | 0.00 |
July | 0.513142E+10 | 0.299013E+11 | 0.441166E+09 | 0.116455E+09 | 62121138.53 | 0.00 | 0.00 | 0.00 |
August | 0.444195E+10 | 0.159308E+11 | 0.984563E+09 | 46676043.59 | 175609.86 | 0.00 | 0.00 | 0.00 |
September | 0.215795E+10 | 0.240225E+09 | 0.355345E+10 | 0.198379E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155836E+10 | 33690402.14 | 0.155639E+11 | 0.152960E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188161E+10 | 6928789.16 | 0.483285E+11 | 0.255425E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.235219E+10 | 3260308.00 | 0.650436E+11 | 0.234163E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.337202E+11 | 0.712475E+11 | 0.276808E+12 | 0.145086E+12 | 68266243.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155836E+10 | 3260308.00 | 0.441166E+09 | 46676043.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.513142E+10 | 0.299013E+11 | 0.650436E+11 | 0.263961E+11 | 62121138.53 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.207992E+10 | 3678778.37 | 0.531930E+11 | 0.258885E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178087E+10 | 4233538.86 | 0.334159E+11 | 0.221344E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173379E+10 | 9143680.99 | 0.172437E+11 | 0.255368E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191786E+10 | 24930990.43 | 0.306193E+10 | 0.732329E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.341229E+10 | 0.424014E+10 | 10561793.60 | 0.298943E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.513568E+10 | 0.209789E+11 | 0.00 | 61595934.29 | 7415763.05 | 0.00 | 0.00 | 0.00 |
July | 0.485756E+10 | 0.282314E+11 | 0.00 | 0.148877E+09 | 67302332.16 | 0.00 | 0.00 | 0.00 |
August | 0.385665E+10 | 0.145344E+11 | 3464372.40 | 0.140099E+09 | 53148.13 | 0.00 | 0.00 | 0.00 |
September | 0.170830E+10 | 0.222241E+09 | 0.879852E+09 | 0.337222E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154588E+10 | 8968310.98 | 0.118749E+11 | 0.171438E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.184383E+10 | 3058829.18 | 0.427389E+11 | 0.255422E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203616E+10 | 1927114.35 | 0.586726E+11 | 0.225827E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319088E+11 | 0.682630E+11 | 0.221095E+12 | 0.150173E+12 | 74771243.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154588E+10 | 1927114.35 | 0.00 | 61595934.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.513568E+10 | 0.282314E+11 | 0.586726E+11 | 0.258885E+11 | 67302332.16 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.254883E+10 | 136019.42 | 0.807570E+11 | 0.255743E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216281E+10 | 634467.31 | 0.547741E+11 | 0.221954E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.214682E+10 | 8226319.00 | 0.334823E+11 | 0.255239E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191691E+10 | 32487799.39 | 0.827138E+10 | 0.790153E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.290823E+10 | 0.413090E+10 | 0.181389E+09 | 0.463446E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.454583E+10 | 0.212784E+11 | 0.00 | 31665463.17 | 7220527.95 | 0.00 | 0.00 | 0.00 |
July | 0.431616E+10 | 0.287034E+11 | 0.00 | 0.107582E+09 | 48252725.82 | 0.00 | 0.00 | 0.00 |
August | 0.325754E+10 | 0.144227E+11 | 91515923.07 | 0.247049E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160005E+10 | 0.195339E+09 | 0.337904E+10 | 0.419621E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.181325E+10 | 6483375.88 | 0.252055E+11 | 0.177419E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.238010E+10 | 0.00 | 0.693231E+11 | 0.251614E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.263387E+10 | 123842.25 | 0.880236E+11 | 0.222407E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.322304E+11 | 0.687788E+11 | 0.363489E+12 | 0.151385E+12 | 55473253.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160005E+10 | 0.00 | 0.00 | 31665463.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.454583E+10 | 0.287034E+11 | 0.880236E+11 | 0.255743E+11 | 48252725.82 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.236623E+10 | 0.00 | 0.00 | 0.00 | 1892702.18 | 0.489126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195203E+10 | 0.00 | 0.00 | 0.00 | 2953222.36 | 0.357573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177124E+10 | 0.00 | 0.00 | 0.00 | 8305936.91 | 0.261532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185879E+10 | 0.00 | 0.00 | 0.00 | 8972506.47 | 0.755677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.331492E+10 | 0.00 | 0.00 | 0.00 | 0.102138E+10 | 0.157752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.493347E+10 | 0.00 | 0.00 | 0.00 | 0.517376E+10 | 0.547286E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.513142E+10 | 0.00 | 0.00 | 0.00 | 0.716012E+10 | 0.441166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.444195E+10 | 0.00 | 0.00 | 0.00 | 0.387510E+10 | 0.982545E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.215795E+10 | 0.00 | 0.00 | 0.00 | 68791966.27 | 0.350978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155836E+10 | 0.00 | 0.00 | 0.00 | 9886712.62 | 0.154280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188161E+10 | 0.00 | 0.00 | 0.00 | 2021497.70 | 0.373531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.235219E+10 | 0.00 | 0.00 | 0.00 | 939090.47 | 0.469767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.337202E+11 | 0.00 | 0.00 | 0.00 | 0.173341E+11 | 0.225196E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155836E+10 | 0.00 | 0.00 | 0.00 | 939090.47 | 0.441166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.513142E+10 | 0.00 | 0.00 | 0.00 | 0.716012E+10 | 0.489126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.207992E+10 | 0.00 | 0.00 | 0.00 | 1050826.77 | 0.403692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178087E+10 | 0.00 | 0.00 | 0.00 | 1196234.96 | 0.259547E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173379E+10 | 0.00 | 0.00 | 0.00 | 2595131.20 | 0.150052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191786E+10 | 0.00 | 0.00 | 0.00 | 7256450.22 | 0.298677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.341229E+10 | 0.00 | 0.00 | 0.00 | 0.109161E+10 | 7468795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.513568E+10 | 0.00 | 0.00 | 0.00 | 0.509784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.485756E+10 | 0.00 | 0.00 | 0.00 | 0.674913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.385665E+10 | 0.00 | 0.00 | 0.00 | 0.353506E+10 | 1574297.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170830E+10 | 0.00 | 0.00 | 0.00 | 63441178.38 | 0.868475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154588E+10 | 0.00 | 0.00 | 0.00 | 2537426.42 | 0.115733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.184383E+10 | 0.00 | 0.00 | 0.00 | 869854.94 | 0.314457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203616E+10 | 0.00 | 0.00 | 0.00 | 554554.62 | 0.409097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319088E+11 | 0.00 | 0.00 | 0.00 | 0.165531E+11 | 0.169122E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154588E+10 | 0.00 | 0.00 | 0.00 | 554554.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.513568E+10 | 0.00 | 0.00 | 0.00 | 0.674913E+10 | 0.409097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.254883E+10 | 0.00 | 0.00 | 0.00 | 39849.56 | 0.622556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216281E+10 | 0.00 | 0.00 | 0.00 | 184243.16 | 0.433764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.214682E+10 | 0.00 | 0.00 | 0.00 | 2422605.02 | 0.292456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191691E+10 | 0.00 | 0.00 | 0.00 | 9541026.07 | 0.790678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.290823E+10 | 0.00 | 0.00 | 0.00 | 0.107158E+10 | 0.178986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.454583E+10 | 0.00 | 0.00 | 0.00 | 0.520362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.431616E+10 | 0.00 | 0.00 | 0.00 | 0.689926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.325754E+10 | 0.00 | 0.00 | 0.00 | 0.353288E+10 | 90562709.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160005E+10 | 0.00 | 0.00 | 0.00 | 56017724.57 | 0.336832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.181325E+10 | 0.00 | 0.00 | 0.00 | 1885273.71 | 0.238456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.238010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.263387E+10 | 0.00 | 0.00 | 0.00 | 36378.41 | 0.642442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.322304E+11 | 0.00 | 0.00 | 0.00 | 0.167775E+11 | 0.287432E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.454583E+10 | 0.00 | 0.00 | 0.00 | 0.689926E+10 | 0.642442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112362E+10 | 0.00 | 0.00 | 0.25 |
February | 0.961463E+10 | 0.00 | 0.00 | 423267.34 | 0.00 | 0.727713E+09 | 0.573998E+09 | 0.00 | 0.27 |
March | 0.795620E+10 | 0.00 | 0.00 | 6071554.63 | 0.00 | 25734588.10 | 0.305926E+10 | 0.00 | 0.29 |
April | 0.337674E+10 | 0.00 | 0.00 | 26729471.74 | 0.00 | 0.00 | 0.125557E+11 | 0.00 | 0.42 |
May | 0.179328E+10 | 0.00 | 0.00 | 47047459.34 | 0.00 | 0.00 | 0.245458E+11 | 0.00 | 0.95 |
June | 0.129858E+10 | 6656804.47 | 0.00 | 50945339.02 | 0.00 | 0.00 | 0.212651E+11 | 0.00 | 1.26 |
July | 0.148912E+10 | 62472456.33 | 0.00 | 47199211.13 | 5624688.33 | 0.00 | 0.161998E+11 | 0.00 | 1.17 |
August | 0.128383E+10 | 150655.66 | 0.00 | 54070492.15 | 0.00 | 0.00 | 0.234160E+11 | 0.00 | 1.15 |
September | 0.213172E+10 | 0.00 | 0.00 | 37080386.89 | 0.00 | 0.00 | 0.182932E+11 | 0.00 | 0.58 |
October | 0.487840E+10 | 0.00 | 0.00 | 13345997.51 | 0.00 | 954175.03 | 0.634423E+10 | 0.00 | 0.31 |
November | 0.115813E+11 | 0.00 | 0.00 | 72088.33 | 0.00 | 0.449786E+09 | 0.186114E+09 | 0.00 | 0.26 |
December | 0.142064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.954378E+09 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.710829E+11 | 69279916.46 | 0.00 | 0.282985E+09 | 5624688.33 | 0.328218E+10 | 0.126439E+12 | 0.00 | 0.60 |
Minimum of Months | 0.128383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.142064E+11 | 62472456.33 | 0.00 | 54070492.15 | 5624688.33 | 0.112362E+10 | 0.245458E+11 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.699887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588389E+10 | 0.00 | 0.00 | 0.26 |
February | 0.635155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415306E+10 | 0.00 | 0.00 | 0.27 |
March | 0.915381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878269E+09 | 0.00 | 0.00 | 0.28 |
April | 0.752314E+10 | 0.00 | 0.00 | 5057714.14 | 0.00 | 51066987.94 | 0.372628E+10 | 0.00 | 0.32 |
May | 0.336236E+10 | 0.00 | 0.00 | 25234055.19 | 0.00 | 0.00 | 0.145128E+11 | 0.00 | 0.66 |
June | 0.206583E+10 | 5710781.79 | 0.00 | 32928647.48 | 0.00 | 0.00 | 0.140052E+11 | 0.00 | 0.90 |
July | 0.209959E+10 | 43152992.18 | 0.00 | 30368173.99 | 7432120.50 | 0.00 | 0.103957E+11 | 0.00 | 0.83 |
August | 0.197313E+10 | 171942.90 | 0.00 | 30851201.49 | 0.00 | 0.00 | 0.141521E+11 | 0.00 | 0.76 |
September | 0.655166E+10 | 0.00 | 0.00 | 9096973.39 | 0.00 | 283848.01 | 0.590242E+10 | 0.00 | 0.38 |
October | 0.794038E+10 | 0.00 | 0.00 | 132046.30 | 0.00 | 0.403820E+09 | 0.410839E+09 | 0.00 | 0.27 |
November | 0.804910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452770E+10 | 0.00 | 0.00 | 0.26 |
December | 0.846956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695751E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.705390E+11 | 49035716.87 | 0.00 | 0.133669E+09 | 7432120.50 | 0.228556E+11 | 0.631053E+11 | 0.00 | 0.46 |
Minimum of Months | 0.197313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.915381E+10 | 43152992.18 | 0.00 | 32928647.48 | 7432120.50 | 0.695751E+10 | 0.145128E+11 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.140350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.968563E+10 | 0.00 | 0.00 | 0.24 |
February | 0.256862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632955E+10 | 0.00 | 0.00 | 0.25 |
March | 0.578129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294233E+10 | 0.00 | 0.00 | 0.27 |
April | 0.771337E+10 | 0.00 | 0.00 | 1872152.49 | 0.00 | 0.413751E+09 | 0.198898E+10 | 0.00 | 0.31 |
May | 0.442226E+10 | 0.00 | 0.00 | 19135259.30 | 0.00 | 0.00 | 0.119311E+11 | 0.00 | 0.61 |
June | 0.221647E+10 | 12581312.96 | 0.00 | 29451008.16 | 0.00 | 0.00 | 0.131838E+11 | 0.00 | 0.88 |
July | 0.240032E+10 | 40472754.75 | 0.00 | 26315589.30 | 4860962.41 | 0.00 | 0.920335E+10 | 0.00 | 0.81 |
August | 0.289617E+10 | 445119.27 | 0.00 | 22564445.17 | 0.00 | 0.00 | 0.111911E+11 | 0.00 | 0.71 |
September | 0.809333E+10 | 0.00 | 0.00 | 2124082.97 | 0.00 | 86417158.89 | 0.223306E+10 | 0.00 | 0.34 |
October | 0.565411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176707E+10 | 0.00 | 0.00 | 0.26 |
November | 0.213846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.869916E+10 | 0.00 | 0.00 | 0.24 |
December | 0.134401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119240E+11 | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.466319E+11 | 53499186.98 | 0.00 | 0.101463E+09 | 4860962.41 | 0.418479E+11 | 0.497314E+11 | 0.00 | 0.43 |
Minimum of Months | 0.134401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.809333E+10 | 40472754.75 | 0.00 | 29451008.16 | 4860962.41 | 0.119240E+11 | 0.131838E+11 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 15927464.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395593E+10 | 0.00 | 0.00 | 0.37 |
February | 17933333.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285536E+10 | 0.00 | 0.00 | 0.34 |
March | 0.223877E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214204E+10 | 0.00 | 0.00 | 0.33 |
April | 0.167163E+10 | 0.00 | 0.00 | 103975.16 | 0.00 | 0.574168E+09 | 0.149344E+09 | 0.00 | 0.35 |
May | 0.143859E+10 | 0.00 | 0.00 | 3840856.67 | 0.00 | 9530676.45 | 0.235484E+10 | 0.00 | 0.69 |
June | 0.407849E+09 | 4810782.35 | 0.00 | 9715675.56 | 0.00 | 0.00 | 0.398073E+10 | 0.00 | 1.23 |
July | 0.484634E+09 | 12992173.08 | 0.00 | 8107774.32 | 1157087.69 | 0.00 | 0.264255E+10 | 0.00 | 1.10 |
August | 0.109811E+10 | 112493.17 | 0.00 | 4628155.00 | 0.00 | 11045346.38 | 0.212554E+10 | 0.00 | 0.80 |
September | 0.198728E+10 | 0.00 | 0.00 | 59377.52 | 0.00 | 0.378095E+09 | 92361849.05 | 0.00 | 0.38 |
October | 0.372822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147353E+10 | 0.00 | 0.00 | 0.31 |
November | 13144938.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360954E+10 | 0.00 | 0.00 | 0.36 |
December | 20537263.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480198E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.775233E+10 | 17915448.60 | 0.00 | 26455814.24 | 1157087.69 | 0.198112E+11 | 0.113454E+11 | 0.00 | 0.56 |
Minimum of Months | 13144938.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.198728E+10 | 12992173.08 | 0.00 | 9715675.56 | 1157087.69 | 0.480198E+10 | 0.398073E+10 | 0.00 | 1.23 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 14627087.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277833E+10 | 0.00 | 0.00 | 0.43 |
February | 57754020.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205627E+10 | 0.00 | 0.00 | 0.43 |
March | 0.694054E+09 | 0.00 | 0.00 | 45197.68 | 0.00 | 0.126644E+10 | 28226142.91 | 0.00 | 0.45 |
April | 0.120177E+10 | 0.00 | 0.00 | 1840569.64 | 0.00 | 0.278527E+09 | 0.997424E+09 | 0.00 | 0.56 |
May | 0.786296E+09 | 0.00 | 0.00 | 9136985.49 | 0.00 | 1101631.82 | 0.478005E+10 | 0.00 | 1.53 |
June | 0.395276E+09 | 3645333.74 | 0.00 | 10692258.42 | 0.00 | 0.00 | 0.476799E+10 | 0.00 | 2.09 |
July | 0.431363E+09 | 9761250.66 | 0.00 | 10546002.15 | 1043978.93 | 0.00 | 0.340066E+10 | 0.00 | 2.00 |
August | 0.670590E+09 | 97029.85 | 0.00 | 7183282.15 | 0.00 | 2069585.93 | 0.341737E+10 | 0.00 | 1.48 |
September | 0.167499E+10 | 0.00 | 0.00 | 1017883.65 | 0.00 | 0.168500E+09 | 0.525211E+09 | 0.00 | 0.58 |
October | 0.552560E+09 | 0.00 | 0.00 | 18078.50 | 0.00 | 0.107089E+10 | 8692948.81 | 0.00 | 0.43 |
November | 12044424.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259255E+10 | 0.00 | 0.00 | 0.42 |
December | 18807346.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327909E+10 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.651013E+10 | 13503614.25 | 0.00 | 40480257.68 | 1043978.93 | 0.134938E+11 | 0.179256E+11 | 0.00 | 0.91 |
Minimum of Months | 12044424.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.167499E+10 | 9761250.66 | 0.00 | 10692258.42 | 1043978.93 | 0.327909E+10 | 0.478005E+10 | 0.00 | 2.09 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108013E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412890E+10 | 0.00 | 0.00 | 0.42 |
February | 0.490379E+09 | 0.00 | 0.00 | 181208.03 | 0.00 | 0.273991E+10 | 58069118.42 | 0.00 | 0.43 |
March | 0.951277E+09 | 0.00 | 0.00 | 2324923.85 | 0.00 | 0.161704E+10 | 0.931967E+09 | 0.00 | 0.50 |
April | 0.124708E+10 | 0.00 | 0.00 | 8073338.74 | 0.00 | 0.378859E+09 | 0.436246E+10 | 0.00 | 0.84 |
May | 0.165362E+10 | 0.00 | 0.00 | 12924612.42 | 0.00 | 16191394.17 | 0.659497E+10 | 0.00 | 1.53 |
June | 0.110253E+10 | 6747430.53 | 0.00 | 13456937.51 | 0.00 | 0.00 | 0.556623E+10 | 0.00 | 1.93 |
July | 0.116996E+10 | 23572764.84 | 0.00 | 12995596.02 | 1346689.52 | 0.00 | 0.362701E+10 | 0.00 | 1.81 |
August | 0.138485E+10 | 155449.75 | 0.00 | 12610625.64 | 0.00 | 11798210.65 | 0.525191E+10 | 0.00 | 1.71 |
September | 0.196652E+10 | 0.00 | 0.00 | 4583268.39 | 0.00 | 0.280053E+09 | 0.259948E+10 | 0.00 | 0.77 |
October | 0.103775E+10 | 0.00 | 0.00 | 948001.36 | 0.00 | 0.131985E+10 | 0.432604E+09 | 0.00 | 0.46 |
November | 0.166375E+09 | 0.00 | 0.00 | 825.47 | 0.00 | 0.384371E+10 | 6021407.15 | 0.00 | 0.42 |
December | 30089621.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499604E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.113084E+11 | 30475645.11 | 0.00 | 68099337.43 | 1346689.52 | 0.193323E+11 | 0.294307E+11 | 0.00 | 0.94 |
Minimum of Months | 30089621.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.196652E+10 | 23572764.84 | 0.00 | 13456937.51 | 1346689.52 | 0.499604E+10 | 0.659497E+10 | 0.00 | 1.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 15415991.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285816E+10 | 0.00 | 0.00 | 0.45 |
February | 54138969.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216336E+10 | 0.00 | 0.00 | 0.45 |
March | 0.486010E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160813E+10 | 0.00 | 0.00 | 0.47 |
April | 0.125863E+10 | 0.00 | 0.00 | 2323462.61 | 0.00 | 0.388170E+09 | 0.124103E+10 | 0.00 | 0.66 |
May | 0.145896E+10 | 0.00 | 0.00 | 4677766.53 | 0.00 | 19312778.75 | 0.252128E+10 | 0.00 | 1.17 |
June | 0.729654E+09 | 5233819.91 | 0.00 | 7721593.62 | 0.00 | 0.00 | 0.289964E+10 | 0.00 | 1.75 |
July | 0.809190E+09 | 15786966.55 | 0.00 | 5908907.92 | 769344.20 | 0.00 | 0.170155E+10 | 0.00 | 1.52 |
August | 0.123077E+10 | 119912.12 | 0.00 | 4465975.92 | 0.00 | 9087766.35 | 0.185114E+10 | 0.00 | 1.28 |
September | 0.173058E+10 | 0.00 | 0.00 | 677420.77 | 0.00 | 0.303918E+09 | 0.442188E+09 | 0.00 | 0.61 |
October | 0.455323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126110E+10 | 0.00 | 0.00 | 0.45 |
November | 15310892.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267145E+10 | 0.00 | 0.00 | 0.44 |
December | 19832835.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333954E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.826382E+10 | 21140698.58 | 0.00 | 25775127.37 | 769344.20 | 0.146222E+11 | 0.106568E+11 | 0.00 | 0.81 |
Minimum of Months | 15310892.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.173058E+10 | 15786966.55 | 0.00 | 7721593.62 | 769344.20 | 0.333954E+10 | 0.289964E+10 | 0.00 | 1.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 51865653.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374843E+10 | 0.00 | 0.00 | 0.34 |
February | 39236521.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302932E+10 | 0.00 | 0.00 | 0.33 |
March | 0.145739E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245589E+10 | 0.00 | 0.00 | 0.32 |
April | 0.172034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774359E+09 | 0.00 | 0.00 | 0.31 |
May | 0.196726E+10 | 0.00 | 0.00 | 1513328.16 | 0.00 | 0.00 | 0.114526E+10 | 0.00 | 0.53 |
June | 0.431898E+09 | 1175681.01 | 0.00 | 7339602.74 | 0.00 | 0.00 | 0.302225E+10 | 0.00 | 0.95 |
July | 0.490596E+09 | 11352257.39 | 0.00 | 7028779.86 | 1199561.86 | 0.00 | 0.228271E+10 | 0.00 | 0.93 |
August | 0.965518E+09 | 23770.42 | 0.00 | 4826508.52 | 0.00 | 0.00 | 0.222665E+10 | 0.00 | 0.75 |
September | 0.227546E+10 | 0.00 | 0.00 | 151839.67 | 0.00 | 0.116214E+09 | 0.284380E+09 | 0.00 | 0.36 |
October | 0.932096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119945E+10 | 0.00 | 0.00 | 0.28 |
November | 39996299.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323941E+10 | 0.00 | 0.00 | 0.31 |
December | 0.131648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435960E+10 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.919166E+10 | 12551708.82 | 0.00 | 20860058.96 | 1199561.86 | 0.189227E+11 | 0.896125E+10 | 0.00 | 0.48 |
Minimum of Months | 39236521.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.227546E+10 | 11352257.39 | 0.00 | 7339602.74 | 1199561.86 | 0.435960E+10 | 0.302225E+10 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 45838376.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277932E+10 | 0.00 | 0.00 | 0.40 |
February | 66675465.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222249E+10 | 0.00 | 0.00 | 0.39 |
March | 0.617791E+09 | 0.00 | 0.00 | 7324.57 | 0.00 | 0.139437E+10 | 10881283.96 | 0.00 | 0.39 |
April | 0.121472E+10 | 0.00 | 0.00 | 1312899.00 | 0.00 | 0.291792E+09 | 0.759632E+09 | 0.00 | 0.45 |
May | 0.609658E+09 | 0.00 | 0.00 | 7723716.67 | 0.00 | 0.00 | 0.409390E+10 | 0.00 | 1.28 |
June | 0.293203E+09 | 1469840.25 | 0.00 | 9264072.49 | 0.00 | 0.00 | 0.405388E+10 | 0.00 | 1.78 |
July | 0.309859E+09 | 11252332.55 | 0.00 | 9640321.05 | 944129.34 | 0.00 | 0.309779E+10 | 0.00 | 1.77 |
August | 0.466879E+09 | 19549.83 | 0.00 | 7916404.80 | 0.00 | 0.00 | 0.360593E+10 | 0.00 | 1.43 |
September | 0.132835E+10 | 0.00 | 0.00 | 1880980.40 | 0.00 | 27500870.13 | 0.115576E+10 | 0.00 | 0.53 |
October | 0.927327E+09 | 0.00 | 0.00 | 42951.92 | 0.00 | 0.817803E+09 | 20460996.54 | 0.00 | 0.36 |
November | 34739855.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241156E+10 | 0.00 | 0.00 | 0.37 |
December | 95397045.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312907E+10 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.601043E+10 | 12741722.63 | 0.00 | 37788670.90 | 944129.34 | 0.130739E+11 | 0.167982E+11 | 0.00 | 0.80 |
Minimum of Months | 34739855.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.132835E+10 | 11252332.55 | 0.00 | 9640321.05 | 944129.34 | 0.312907E+10 | 0.409390E+10 | 0.00 | 1.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 57210853.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.746146E+10 | 0.00 | 0.00 | 0.68 |
February | 0.155660E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533348E+10 | 0.00 | 0.00 | 0.61 |
March | 0.365113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417148E+10 | 0.00 | 0.00 | 0.55 |
April | 0.155790E+10 | 0.00 | 0.00 | 1361827.62 | 0.00 | 0.169435E+10 | 0.103859E+10 | 0.00 | 0.55 |
May | 0.225655E+10 | 0.00 | 0.00 | 3867663.65 | 0.00 | 0.644755E+09 | 0.225959E+10 | 0.00 | 0.93 |
June | 0.133173E+10 | 2491179.98 | 0.00 | 6908543.07 | 0.00 | 0.234621E+09 | 0.270419E+10 | 0.00 | 1.26 |
July | 0.116071E+10 | 22740330.85 | 0.00 | 8666829.68 | 1199547.17 | 0.207285E+09 | 0.210406E+10 | 0.00 | 1.33 |
August | 0.159653E+10 | 40160.12 | 0.00 | 7591759.22 | 0.00 | 0.428738E+09 | 0.288467E+10 | 0.00 | 1.29 |
September | 0.203137E+10 | 0.00 | 0.00 | 1732806.96 | 0.00 | 0.130399E+10 | 0.123201E+10 | 0.00 | 0.63 |
October | 0.685615E+09 | 0.00 | 0.00 | 172375.18 | 0.00 | 0.293611E+10 | 0.117429E+09 | 0.00 | 0.49 |
November | 74308307.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699935E+10 | 0.00 | 0.00 | 0.66 |
December | 71986280.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913988E+10 | 0.00 | 0.00 | 0.70 |
Annual Sum or Average | 0.113447E+11 | 25271670.95 | 0.00 | 30301805.38 | 1199547.17 | 0.405555E+11 | 0.123405E+11 | 0.00 | 0.81 |
Minimum of Months | 57210853.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207285E+09 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.225655E+10 | 22740330.85 | 0.00 | 8666829.68 | 1199547.17 | 0.913988E+10 | 0.288467E+10 | 0.00 | 1.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 49506654.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286144E+10 | 0.00 | 0.00 | 0.41 |
February | 54233337.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238642E+10 | 0.00 | 0.00 | 0.42 |
March | 0.347067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181992E+10 | 0.00 | 0.00 | 0.42 |
April | 0.142201E+10 | 0.00 | 0.00 | 1265187.57 | 0.00 | 0.353921E+09 | 0.697555E+09 | 0.00 | 0.50 |
May | 0.142486E+10 | 0.00 | 0.00 | 2792124.97 | 0.00 | 707133.58 | 0.169127E+10 | 0.00 | 0.89 |
June | 0.571214E+09 | 860546.76 | 0.00 | 6216662.75 | 0.00 | 0.00 | 0.236152E+10 | 0.00 | 1.39 |
July | 0.589779E+09 | 14401469.61 | 0.00 | 5299352.41 | 1068957.83 | 0.00 | 0.158911E+10 | 0.00 | 1.26 |
August | 0.789293E+09 | 25710.86 | 0.00 | 4975661.72 | 0.00 | 0.00 | 0.208344E+10 | 0.00 | 1.15 |
September | 0.187303E+10 | 0.00 | 0.00 | 729008.46 | 0.00 | 67555733.16 | 0.538547E+09 | 0.00 | 0.54 |
October | 0.874063E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100895E+10 | 0.00 | 0.00 | 0.39 |
November | 41423971.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250056E+10 | 0.00 | 0.00 | 0.39 |
December | 0.101943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319243E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.813843E+10 | 15287727.23 | 0.00 | 21277997.89 | 1068957.83 | 0.141919E+11 | 0.896144E+10 | 0.00 | 0.68 |
Minimum of Months | 41423971.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.187303E+10 | 14401469.61 | 0.00 | 6216662.75 | 1068957.83 | 0.319243E+10 | 0.236152E+10 | 0.00 | 1.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 23025203.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361905E+10 | 0.00 | 0.00 | 0.32 |
February | 63687842.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269334E+10 | 0.00 | 0.00 | 0.30 |
March | 0.434849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188019E+10 | 0.00 | 0.00 | 0.29 |
April | 0.167758E+10 | 0.00 | 0.00 | 301495.07 | 0.00 | 0.367579E+09 | 0.293028E+09 | 0.00 | 0.32 |
May | 0.888102E+09 | 0.00 | 0.00 | 5548548.65 | 0.00 | 0.00 | 0.307886E+10 | 0.00 | 0.72 |
June | 0.274447E+09 | 1914374.82 | 0.00 | 10947599.65 | 0.00 | 0.00 | 0.432328E+10 | 0.00 | 1.25 |
July | 0.359942E+09 | 13590977.32 | 0.00 | 9196445.80 | 1567869.70 | 0.00 | 0.294315E+10 | 0.00 | 1.11 |
August | 0.690167E+09 | 44637.87 | 0.00 | 6215513.14 | 0.00 | 0.00 | 0.277697E+10 | 0.00 | 0.84 |
September | 0.191829E+10 | 0.00 | 0.00 | 463417.98 | 0.00 | 0.130878E+09 | 0.436251E+09 | 0.00 | 0.36 |
October | 0.749465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113807E+10 | 0.00 | 0.00 | 0.28 |
November | 21995222.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324029E+10 | 0.00 | 0.00 | 0.30 |
December | 30678596.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425664E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.713223E+10 | 15549990.00 | 0.00 | 32673020.30 | 1567869.70 | 0.173260E+11 | 0.138515E+11 | 0.00 | 0.54 |
Minimum of Months | 21995222.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.191829E+10 | 13590977.32 | 0.00 | 10947599.65 | 1567869.70 | 0.425664E+10 | 0.432328E+10 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 26754080.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294490E+10 | 0.00 | 0.00 | 0.44 |
February | 0.177964E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222339E+10 | 0.00 | 0.00 | 0.45 |
March | 0.967450E+09 | 0.00 | 0.00 | 155409.06 | 0.00 | 0.122415E+10 | 76959074.06 | 0.00 | 0.47 |
April | 0.132475E+10 | 0.00 | 0.00 | 2473615.19 | 0.00 | 0.230834E+09 | 0.133573E+10 | 0.00 | 0.61 |
May | 0.731590E+09 | 0.00 | 0.00 | 9944461.61 | 0.00 | 0.00 | 0.521113E+10 | 0.00 | 1.60 |
June | 0.314103E+09 | 2125749.92 | 0.00 | 11049540.51 | 0.00 | 0.00 | 0.489619E+10 | 0.00 | 2.08 |
July | 0.374579E+09 | 10613283.75 | 0.00 | 10697299.73 | 1593750.84 | 0.00 | 0.352412E+10 | 0.00 | 1.96 |
August | 0.621977E+09 | 37193.97 | 0.00 | 8047917.11 | 0.00 | 346593.30 | 0.381237E+10 | 0.00 | 1.53 |
September | 0.177761E+10 | 0.00 | 0.00 | 1572327.00 | 0.00 | 88521120.13 | 0.957599E+09 | 0.00 | 0.63 |
October | 0.946783E+09 | 0.00 | 0.00 | 50042.79 | 0.00 | 0.981119E+09 | 22373191.16 | 0.00 | 0.45 |
November | 26648852.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283522E+10 | 0.00 | 0.00 | 0.44 |
December | 33844218.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347083E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.732406E+10 | 12776227.64 | 0.00 | 43990613.01 | 1593750.84 | 0.139993E+11 | 0.198365E+11 | 0.00 | 0.93 |
Minimum of Months | 26648852.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.177761E+10 | 10613283.75 | 0.00 | 11049540.51 | 1593750.84 | 0.347083E+10 | 0.521113E+10 | 0.00 | 2.08 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.208492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426870E+10 | 0.00 | 0.00 | 0.42 |
February | 0.780312E+09 | 0.00 | 0.00 | 345211.34 | 0.00 | 0.274292E+10 | 0.126500E+09 | 0.00 | 0.43 |
March | 0.132410E+10 | 0.00 | 0.00 | 3450629.87 | 0.00 | 0.146328E+10 | 0.113056E+10 | 0.00 | 0.52 |
April | 0.146032E+10 | 0.00 | 0.00 | 9358301.05 | 0.00 | 0.265511E+09 | 0.472117E+10 | 0.00 | 0.88 |
May | 0.144999E+10 | 0.00 | 0.00 | 13838591.95 | 0.00 | 364454.26 | 0.690273E+10 | 0.00 | 1.57 |
June | 0.892685E+09 | 4070380.13 | 0.00 | 14054967.60 | 0.00 | 0.00 | 0.564313E+10 | 0.00 | 1.90 |
July | 0.931932E+09 | 26916289.84 | 0.00 | 13447099.32 | 2015316.19 | 0.00 | 0.374542E+10 | 0.00 | 1.75 |
August | 0.112832E+10 | 58872.15 | 0.00 | 14123432.59 | 0.00 | 0.00 | 0.567163E+10 | 0.00 | 1.72 |
September | 0.218743E+10 | 0.00 | 0.00 | 6070105.52 | 0.00 | 86906853.97 | 0.326403E+10 | 0.00 | 0.82 |
October | 0.142913E+10 | 0.00 | 0.00 | 1392667.60 | 0.00 | 0.116404E+10 | 0.641577E+09 | 0.00 | 0.47 |
November | 0.344942E+09 | 0.00 | 0.00 | 32740.12 | 0.00 | 0.396471E+10 | 16765605.76 | 0.00 | 0.42 |
December | 51871937.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525618E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.121895E+11 | 31045542.11 | 0.00 | 76113746.96 | 2015316.19 | 0.192126E+11 | 0.318635E+11 | 0.00 | 0.95 |
Minimum of Months | 51871937.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.218743E+10 | 26916289.84 | 0.00 | 14123432.59 | 2015316.19 | 0.525618E+10 | 0.690273E+10 | 0.00 | 1.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 26778577.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294559E+10 | 0.00 | 0.00 | 0.44 |
February | 0.124855E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228757E+10 | 0.00 | 0.00 | 0.45 |
March | 0.721917E+09 | 0.00 | 0.00 | 1096.48 | 0.00 | 0.153665E+10 | 4120708.18 | 0.00 | 0.47 |
April | 0.140841E+10 | 0.00 | 0.00 | 2640539.56 | 0.00 | 0.269826E+09 | 0.140618E+10 | 0.00 | 0.67 |
May | 0.112491E+10 | 0.00 | 0.00 | 5531240.42 | 0.00 | 240081.12 | 0.293166E+10 | 0.00 | 1.19 |
June | 0.570433E+09 | 1243457.71 | 0.00 | 8236356.83 | 0.00 | 0.00 | 0.303366E+10 | 0.00 | 1.73 |
July | 0.619086E+09 | 16416388.39 | 0.00 | 6393938.07 | 1239906.18 | 0.00 | 0.189135E+10 | 0.00 | 1.48 |
August | 0.915380E+09 | 45621.00 | 0.00 | 5438018.92 | 0.00 | 186864.17 | 0.225426E+10 | 0.00 | 1.28 |
September | 0.195440E+10 | 0.00 | 0.00 | 993255.36 | 0.00 | 0.115497E+09 | 0.676485E+09 | 0.00 | 0.63 |
October | 0.845461E+09 | 0.00 | 0.00 | 1618.95 | 0.00 | 0.109545E+10 | 8616501.18 | 0.00 | 0.45 |
November | 34364184.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282628E+10 | 0.00 | 0.00 | 0.44 |
December | 33846192.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346883E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.837984E+10 | 17705467.11 | 0.00 | 29236064.59 | 1239906.18 | 0.145461E+11 | 0.122063E+11 | 0.00 | 0.81 |
Minimum of Months | 26778577.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.195440E+10 | 16416388.39 | 0.00 | 8236356.83 | 1239906.18 | 0.346883E+10 | 0.303366E+10 | 0.00 | 1.73 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:13
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 46207854.50 | 0.275808E+11 | 0.00 | 0.183447E+12 | 0.110483E+11 |
February | 0.552448E+11 | 0.222864E+11 | 0.00 | 0.162236E+12 | 0.658268E+10 |
March | 0.216564E+12 | 0.285968E+11 | 0.00 | 0.194066E+12 | 0.220349E+10 |
April | 0.361446E+12 | 0.238645E+11 | 0.00 | 0.211661E+12 | 0.242410E+09 |
May | 0.436086E+12 | 0.144744E+11 | 0.00 | 0.279085E+12 | 0.154755E+11 |
June | 0.444064E+12 | 0.814425E+10 | 0.00 | 0.243893E+12 | 0.788701E+11 |
July | 0.403460E+12 | 0.628819E+10 | 0.00 | 0.251037E+12 | 0.107645E+12 |
August | 0.306432E+12 | 0.897067E+10 | 0.00 | 0.257101E+12 | 0.558321E+11 |
September | 0.151521E+12 | 0.121110E+11 | 0.00 | 0.235092E+12 | 0.862499E+09 |
October | 0.727105E+11 | 0.228719E+11 | 0.00 | 0.185723E+12 | 0.512807E+09 |
November | 0.147868E+11 | 0.202729E+11 | 0.00 | 0.188115E+12 | 0.968088E+10 |
December | -0.907707E+10 | 0.244935E+11 | 0.00 | 0.187870E+12 | 0.149092E+11 |
Annual Sum or Average | 0.245328E+13 | 0.219955E+12 | 0.00 | 0.257933E+13 | 0.303864E+12 |
Minimum of Months | -0.907707E+10 | 0.628819E+10 | 0.00 | 0.162236E+12 | 0.242410E+09 |
Maximum of Months | 0.444064E+12 | 0.285968E+11 | 0.00 | 0.279085E+12 | 0.107645E+12 |